Inside the Ultra Forced Air
Transcription
Inside the Ultra Forced Air
Engineering Specifications Ultra Forced Air EV 17 thru 47 Inside the Ultra Forced Air Installation & Operating Instructions Ultra Vertical Unit Intelligent 5/10 kW Electric Elements (Optional) Air Filter Air Coil Blower Transformer Contactor Controller Thermostatic Expansion Valve Reversing Valve Low Pressure Switch Double-Wall Vented Desuperheater and Pump (Optional) Scroll Compressor High Pressure Switch Air Pad Legend for Tables BTU/hr CAP COP CFM DB DHW DWR dP EER EWT FLA GND GPM Heating or cooling capacity Capacity Coefficient of performance (BTU/hr out BTU/hr in) Cubic feet per minute Dry-bulb entering air temperature Domestic hot water Domestic hot water, extra capacity Pressure drop across heat pump (in feet of water and psi) Energy efficiency ratio (BTU/hr CAP watts in) Entering water temperature (in degrees Fahrenheit) Full-load amperage Ground Gallons per minute of water flow HE HR HYD KW LRA MBTU/hr RLA SR SUP VA WB Heat extracted Heat rejected Hydronic Kilowatt input Locked-rotor amperage Btu/hr X 1000 Rated-load amperage Sensible Ratio (sensible cooling capacity total cooling capacity) Supplemental domestic water heating Volt-amperes Wet-bulb entering air temperature All Pressure Drop Ratings are for Pure Water. See last page for Correction Factors. Performance values are +/- 10%, and are subject to change without notice Key to Model Numbers EV470–1–UOOO CABINET STYLE V = Vertical (Forced Air) H = Horizontal (Forced Air) W = Water (Hydronic) D = Domestic (Hot Water) WATER COIL O = Standard N = Cupro Nickel Well Water Coil P = Cupro Nickel Hydronic Coil V = Cupro Nickel Well Water and Hydronic Coil NOMINAL COOLING CAPACITY X 1,000 BTU/hr UNIT TYPE O = Standard V = Variable Speed ECM Blower D = Demonstrator H = Heat only (Hydronic) S = Special T = Staged Tandems U = Staged Tandems Heat Only M = Modulating Valve B = Variable Speed ECM Blower with Modulating Valve 2 = Two-Step Compressor C = Commercial DESUPERHEATER OPTION 0 = None 1 = Part Time, 65% DHW ELECTRICAL SUPPLY OPTION 1 = 208/230V-60Hz, Single Phase 2 = 208/230V-60Hz, Three Phase 3 = 460V-60Hz, Three Phase 4 = 220V-50Hz, Single Phase 5 = 277V-60Hz, Single Phase 6 = 208/230-60Hz, Single Phase w/ EMS 7 = 208/230-60Hz, Three Phase w/ EMS 8 = 460-60Hz, Three Phase w/ EMS 9 = 380V-60Hz, Three Phase A = 200/220V-50/60Hz, Three Phase B = 380V-50Hz, Three Phase C = 575V-60Hz, Three Phase AIR OPTION O = Standard R = Right Return Vertical B = Bottom Discharge Right Return Vertical C = Front Right Discharge Horizontal S = Split System DESIGN D = DualTEK V = Vara, Vara 2 Plus U = Ultra 3 TABLE OF CONTENTS Section Title Page I. Introduction to ECONAR Heat Pumps 2 II. Unit Sizing A. Building Heat Loss / Heat Gain B. Ground Sources & Design Water Temperatures 1. Ground Loop Applications 2. Ground Water Applications C. Temperature Limitations 3 III. Unit Location / Mounting 4 IV. Condensate Drain 4 V. Duct System / Blower 5 VI. Ground Source Design A. Ground Loop Installation B. Ground Water Installation 1. Ground Water Freeze Protection Switch 2. Water Coil Maintenance 6 VII. Electrical Service 8 VIII. 24 Volt Control Circuit A. Transformer B. Thermostat C. Controller 9 IX. Startup / Checkout 11 X. Service and Lockout Lights A. Lockout Lights B. Air Filter C. Preseason Inspection D. Ground Water Heat Exchanger 12 XI. Room Thermostat Operation 12 XII. Desuperheater (Optional) 12 XIII. XIV. XV. XVI. XVII. XVIII. XIX. XX. Performance Ratings & Configuration options Performance Data Fan Performance Data Physical Data Dimensions & Electrical Data Correction Factors & Pressure Drop Wiring Diagrams Troubleshooting Guide for Lockout Conditions 14 15 18 18 19 20 21 23 XXI. Troubleshooting Guide for Unit Operation 24 XXII. Troubleshooting Guide for ECM Blower 26 XXIII. Additional Figures 27 1 I. INTRODUCTION TO ECONAR HEAT PUMPS Enertech Global, LLC, is home to ECONAR geothermal heat pumps, a brand that has been in Minnesota for over twenty years. The cold winter climate has driven the design of ECONAR’s heating and cooling equipment to what is known as a "ColdClimate" geothermal heat pump. This cold climate technology focuses on maximizing the energy savings available in heating dominated regions without sacrificing comfort. Extremely efficient heating, cooling, dehumidification and optional domestic hot water heating are provided in one neatly packaged system. Enertech produces three types of ECONAR heat pumps: hydronic, which transfers energy from water to water; forced air, which transfers energy from water to air; and combination, which incorporates the hydronic heating unit into a forced air unit. Geothermal heat pumps get their name from the transfer of energy to and from the ground. The ground-coupled heat exchanger (geothermal loop) supplies the source energy for heating and absorbs the discharged energy from cooling. The system uses a compression cycle, much like your refrigerator, to collect the ground’s energy supplied by the sun and uses it to heat your home. Since the process only moves energy, and does not create it, the efficiencies are three to four times higher than most efficient fossil fuel systems. Safety and comfort are designed into every ECONAR geothermal heat pump. Since the system runs completely on electrical energy, the entire home can have the safety of being gas-free. The best engineering and quality control is in every heat pump. Proper application and correct installation will ensure excellent performance and customer satisfaction. The Enertech commitment to quality is written on the side of every heat pump built. Throughout the manufacturing process, the technicians who assemble each unit sign their names to the quality assurance label after completing their inspections. As a final quality test, every unit goes through a full run-test where the performance and operation is verified in both the heating and cooling modes. No other manufacturer goes as far as to run a full performance check to ensure system quality. This guide discusses Ultra forced air units. The Ultra uses R-410A refrigerant, which is environmentally friendly to the earth’s protective ozone layer. WARNING – Service of refrigerant-based equipment can be hazardous due to elevated system pressures and hazardous voltages. Only trained and qualified personnel should install, repair or service. The installer is responsible to ensure that all local electrical, plumbing, heating and air conditioning codes are followed. WARNING – ELECTRICAL SHOCK CAN CAUSE PERSONAL INJURY OR DEATH. Disconnect all power supplies before installing or servicing electrical devices. Only trained and qualified personnel should install, repair or service this equipment. WARNING –Verify refrigerant type before servicing. The nameplate on the heat pump identifies the type and the amount of refrigerant. All refrigerant removed from these units must be reclaimed by following accepted industry and agency procedures. CAUTION – Ground loops must be freeze protected. Insufficient amounts of antifreeze may cause severe damage and may void warranty. Never operate with ground loop flow rates less than specified. Continuous operation at low flow rates, or no flow, may cause severe damage and may void warranty. CAUTION – R410A refrigerant requires extra precaution when service work is being performed. The operating pressures are approximately 150% higher than R-22 – which can cause personal injury. Invasion into the refrigerant system must be a last resort. Ensure all other diagnosis and methods have been used before attaching refrigerant instruments and before opening the refrigerant system. Synthetic oil (POE) is extremely hydroscopic, meaning it has a strong chemical attraction to moisture. Brief exposure to ambient air could cause POE to absorb enough moisture that a typical vacuum may not remove. COMMON ACRONYMS CFM DHW dP EAT ECM EWT GPM/gpm Ground Loop Ground Water GTF HP kW LP P/T PSC VA Cubic Feet per Minute Domestic Hot Water Pressure Differential Entering Air Temperature Electronically Commutated Motor Entering Water Temperature Gallons per Minute Also known as Closed Loop Also known as Open Loop GeoThermal Transfer Fluid High Pressure Kilowatts Low Pressure Pressure/Temperature Permanent Split Capacitor Volt Amperes II. UNIT SIZING Selecting the unit capacity of a forced air geothermal heat pump requires three things: A) Building Heat Loss/Heat Gain. B) Ground Sources and Design Water Temperatures. C) Temperature Limitations. A. Building Heat Loss/Heat Gain The space load must be estimated accurately for any successful HVAC installation. There are many guides or computer programs available for estimating heat loss and gain, including the Enertech Geothermal Heat Pump Handbook, Manual J, and others. After the heat loss and gain analysis is completed, Entering Water Temperatures 2 (EWT’s) are established, and the heat pump can now be selected using forced air heat pump data in the Engineering Specifications. Choose the capacity of the heat pump based on both heating and cooling loads. B. Ground-Sources and Design Water Temperatures Ground sources include the Ground Water (typically a well) and the Ground Loop varieties. Water flow-rate requirements vary based on configuration. ECONAR Engineering Specifications provide capacities at different loop water temperatures. Note: Table 1 shows the waterflow (GPM) requirements and water-flow pressure differential (dP) for the heat exchanger, and Table 2 shows the dP multiplier for various levels of freeze protection. Table 1 – Ground-Side Flow Rate Requirements o Ground Loop 50 F Ground Water Flow dP* Flow dP* (gpm) (psig) (gpm) (psig) 5 2.2 3 0.9 17 Series 8 2.8 5 2.2 27 Series 9 3.1 6 1.6 37 Series 12 5.3 7 2.4 47 Series * dP (psig) heat exchanger pressure drops are for pure water. Note: dP values are for standard heat exchanger configurations. Cupro Nickel heat exchanger configurations for Ground Water applications have higher dP. Model Table 2 – Heat Exchanger Pressure Differential (dP) Correction Factors for Freeze Protection (Typical) AntiFreeze (1) Percent Volume Freeze Level dP Multiplier 25oF 35oF 90oF 110oF o GTF 50% GTF 12 F 125% 123% N/a N/a Propylene 20% 18oF 136% 133% 118% 114% Glycol 25% 15oF 145% 142% N/a N/a (1) GTF = Geothermal Transfer Fluid. 60% water, 40% methanol. 1. Ground Loop Systems Loop systems use a high density polyethylene pipe buried underground to supply a tempered water solution back to the heat pump. Ground loops operate at higher flow rates than ground water systems because the entering water temperature (EWT) is lower. EWT affects the capacity of the unit in the heating mode, and loops in cold climates are normally sized to supply a wintertime EWT to the heat pump down to 25oF. When selecting the heat pump, choose a unit that will supply the necessary heating or cooling capacity at the minimum and maximum ground loop EWT conditions respectively. Example; if a residential system requires 45,000 Btu/hr to heat a house on an earth loop system (designed for 32oF minimum winter EWT), and 40,000 Btu/hr to cool the house on an earth loop (designed for 77oF summer EWT), an EV47 Ultra heat pump is required. 2. Ground Water Systems Note: If a heat pump is installed with ground water, it should have a Cupro-Nickel water coil (EVxxx-x-UxxN). Cupro-Nickel coils withstand well water much better than standard water coils. The design water temperature will be the well water temperature in your geographic region for ground water systems. Typical well water temperatures are in the 50 oF range in many cold climates. If well water temperatures are lower than 50oF (Canadian well water can be as low as 40oF) the flow rate must be increased to avoid leaving water temperatures below the freezing point. If well water temperatures are above 50oF (Some southern states are above 70oF) the flow rates may need to be increased to dump heat more efficiently in the cooling mode. Varying well water temperatures will have little effect on unit capacity in the cooling mode (since the well is connected to the heat pump condenser), but can have large effects on capacity in the heating mode (since the well is connected to the evaporator). If well water temperatures exceed 70oF, special considerations, such as ground loop systems, should be considered. C. Temperature Limitations Be aware of the operating range of the geothermal system when sizing the particular heat pump to avoid premature equipment failure. Operating outside of these limitations may cause severe damage to the equipment and may void warranty. CAUTIONS; –The acceptable Ground Loop EWT is 15oF to 70oF for heating and 40oF to 95oF for cooling. –The acceptable Ground Water EWT is 45 oF minimum in heating and 70oF maximum in cooling. III. UNIT LOCATION / MOUNTING CAUTION – Units must be kept in an upright position during transportation and installation, or severe internal damage may occur. Bottom Discharge units are very “top heavy.” Important – To ensure easy removal and replacement of access panels, leave panels secured in place until the unit is set in place and leveled. Important – Locate the unit in an indoor area where the ambient temperature will remain above 45 oF. Service is done primarily from the front. Top and rear access is desirable and should be provided when possible. Important – A field installed drain pan is required under the entire unit where accidental water discharge could damage surrounding floors, walls or ceilings. CAUTION – Do not use this unit during construction. Dust and debris may quickly contaminate electrical and mechanical components; resulting in damage. CAUTION - Before driving screws into the cabinet, check on the inside of the unit to ensure the screw will not 3 damage electrical, water, or refrigeration lines. Important – Units must be mounted on a vibrationabsorbing pad slightly larger than the base to provide isolation between the unit and the floor. Water supply pumps should not be hard plumbed directly to the unit with copper pipe; this could transfer vibration from the water pump to the refrigeration circuit, causing a resonating sound. Hard plumbing must be isolated from building structures that could also transfer vibration noise from the unit through the piping to the living space. CAUTION – Always use plastic male fittings into plastic female or into metal female fittings. Never use metal male fittings into plastic female fittings. On metalto-metal fittings, use pipe thread compound, do not use pipe thread tape, hand tighten first, and then only tighten an additional ½ turn with a tool if necessary. On plastic fittings, always use 2 to 3 wraps of pipe thread tape, do not use pipe thread compound, hand tighten first, and then only tighten an additional ½ turn with a tool if necessary. Do not over-tighten, or damage may occur. IV. CONDENSATE DRAIN Condensate traps are built into every Ultra Vertical Top Discharge unit, so an external trap should not be installed. Important – All Horizontal and Vertical units must be installed level to ensure proper condensate drainage. CAUTION – Horizontal units have a ¾” FPT drain and require an external ¾” condensate vented trap in order to drain water from the heat pump. CAUTION – Bottom Discharge (downflow) units have two ½” MPT drains; one for the condensate, and one for the cabinet. Each drain requires a separate external ¾” condensate-vented trap, and the unit must be elevated enough to provide clearance for the drain traps. The line leaving the U bend of the condensate trap must be at least 3” below the base of the heat pump. This requires the U bend to be 6” below the unit to give the upward portion of the U bend a 3” lift (see Figure 1). The trap should be vented after the U bend. The line should be pitched away from the unit a minimum of 1/8” per foot. If the unit produces an odor in the cooling mode, the condensate trap or line may be plugged, or the unit may not be pitched correctly. Bleach may be poured down the condensate drain in the heat pump to kill any bacterial growth in the condensate line. Vented condensate traps are necessary to break the negative pressure in the air chamber and allow the condensate to flow. Construct condensate traps to the following diagram. Heat Pump Base Heat Pump Base Air Vent 6" drop minimum 3" Rise To drain with 1/8" per foot minimum pitch Horizontal Units V. DUCT SYSTEM/BLOWER Metal ductwork should be used, and flexible connectors are required for discharge and return air duct connections. An air inlet collar is provided on all Ultra® forced air units to connect the return duct. For acceptable duct sizes, see Table 3. If the duct is installed in an uninsulated space, it should be insulated on the outside to prevent heat loss, absorb noise, and prevent condensation from collecting on the ductwork. Important – If the unit is connected to existing ductwork, the existing ductwork must have the capacity to handle the air volume required by the heat pump. Undersized ductwork will cause noisy operation due to high air velocity, poor operating efficiencies, and nuisance high, or low, pressure lockouts. The Ultra heat pump is standard with a 230 Volt threespeed Permanent Split Capacitor (PSC) blower motor. The motor can be set at three adjustment settings low, medium, or high at the fan terminal strip, located in the electrical box. The GH87 and GH110 have dual blowers. Refer to Table 4 for factory settings and CFM outputs. The EV/H37-77 series is also available with an optional variable speed Electronically Commutated Motor (ECM) blower motor. The ECM motor converts 230 Volt AC to internal DC power and then modulates the DC power to turn the motor at various speeds. There are four different CFM outputs in each of the three blower speed ranges (Low, Medium, and High). Refer to Table 4 for factory settings and CFM outputs. Important – The blower will not operate properly if ductwork is not attached. Ductwork supplies static pressure for the blower motor to work against. The blower compartment access door must be on for the unit to run properly. Blower motors may overheat if run for extended periods of time without a load. Note – If problems occur, refer to the ECM Motor Troubleshooting Guide at the rear of this manual Air Vent 6" drop minimum 3" Rise Bottom Discharge Figure 1 – Condensate Drain - Horizontal and Bottom Discharge Units Only 4 Table 3 - Duct Sizing Chart CFM 100 150 200 250 300 350 400 450 500 600 800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000 3200 Acceptable Branch Duct Sizes Round Rectangular 6” 4x8, 4x6 7” 4x10, 5x8, 6x6 8” 5x10, 6x8, 4x14, 7x7 9” 6x10, 8x8, 4x16 10” 6x14, 8x10, 7x12 10” 6x20, 6x16, 9x10 12” 6x18, 10x10, 9x12 12” 6x20, 8x14, 9x12, 10x11 Acceptable Main or Trunk Duct Sizes Round Rectangular 10” 10” 10” 12” 12” 14” 16” 16” 18” 20” 20” 22” 22” 22” 22” 24” 24” 4x20, 7x10, 6x12, 8x9 5x20, 6x16, 9x10, 8x12 10x10, 6x18, 8x12, 7x14 6x20, 7x18, 8x16, 10x12 8x18, 9x15, 10x14, 12x12 10x18, 12x14, 8x24 10x20, 12x18, 14x15 10x25, 12x20, 14x18, 15x16 10x30, 15x18, 14x20 10x35, 15x20, 16x19, 12x30, 14x25 10x40, 12x30, 15x25, 18x20 10x40, 15x25, 20x20 12x40, 16x25, 20x20 14x28, 15x25, 16x24, 20x20 14x30, 15x28, 16x25, 20x20 14x33, 15x30, 16x28, 20x22 16x30, 20x26 Tables calculated for 0.05 to 0.10 inches of water friction per 100’ of duct. At these duct design conditions, along with the pressure drop through the filter, the total design external static pressure is 0.20 inches of water. Table 4 – PSC Fan Performance & Settings External Static Pressure – in WG Model Fan Speed 17x-x-Uxxx Series Low Medium High* 27x-x-Uxxx Series Low Medium* High 37x-x-Uxxx Series 47x-x-Uxxx Series Low Medium* High Low Medium High* 0.10 550 610 675 870 980 1090 1005 1140 1210 0.15 520 580 650 825 935 1050 965 1100 1150 0.20 490 550 625 800 900 1000 935 1065 1110 0.25 460 430 600 775 870 965 890 1010 1070 0.30 445 510 580 750 845 940 855 965 1030 1325 1505 1685 1275 1450 1625 1235 1415 1550 1200 1375 1500 1165 1320 1435 *denotes factory setting. . Table 5 – ECM Blower Speed Settings Model 37x-x-UxVx Series 47x-x-UxVx Series TAP D C Low (G) 485 680 Medium(Y) 1100 1550 High (W/E) 1210 1705 Note: Adjust Tap set to “+” will increase these numbers by 10%. Adjust Tap set to “-” will decrease these numbers by 10%. 5 VI. GROUND SOURCE DESIGN Since water is the source of energy in the winter and the energy sink in the summer, a good water supply is possibly the most important requirement of a geothermal heat pump system installation. A. Ground Loop Installation A ground loop system circulates the same antifreeze solution through a closed system of high-density underground polyethylene pipe. As the solution passes through the pipe, it collects energy (in the heating mode) from the relatively warm surrounding soil through the pipe and into the relatively cold solution. The solution circulates to the heat pump, which transfers energy with the solution, and then the solution circulates back through the ground to extract more energy. The Ultra is designed to operate on either vertical or horizontal ground loop applications. Vertical loops are typically installed with a well drilling rig up to 200 feet deep, or more. Horizontal loops are installed with excavating or trenching equipment to a depth of about six to eight feet deep, depending on geographic location and length of pipe used. Loops must be sized properly for each particular geographic area, soil type, and individual capacity requirements. Contact Enertech Customer Support or the local installer for loop sizing requirements in your area. Typical winter operating EWT to the heat pump ranges from 25oF to 32oF. CAUTION – Ground Loops must be properly freeze protected. Insufficient amounts of antifreeze may result in a freeze rupture of the unit or can cause unit shutdown problems during cold weather operation. Propylene glycol and Geothermal Transfer Fluid (GTF) are common antifreeze solutions. GTF is methanol-based antifreeze and should be mixed 50% with water to achieve freeze protection of 12oF. Propylene glycol antifreeze solution should be mixed 25% with water to obtain a 15 oF freeze protection. Important – Do not mix more than 25% propylene glycol with water in an attempt to achieve a lower than 15oF freeze protection, since more concentrated mixtures of propylene glycol become too viscous at low temperatures and cannot be pumped through the earth loop. Horizontal loops typically use GTF, and vertical loops typically use propylene glycol. Note – Always check state and local codes for any special requirements on antifreeze solutions. Flow rate requirements for ground loops are higher (see Table 1) than ground water systems because water temperatures are generally lower. CAUTION – Never operate with flow rates less than specified. Low flow rates, or no flow, may cause the unit to shut down on a pressure lockout or may cause a freeze rupture of the heat exchanger. Important – Figure 4 shows that Pressure/Temperature (P/T) ports must be installed in the entering and leaving water lines of the heat pump. A thermometer can be inserted into the P/T ports to check entering and leaving water temperatures. A pressure gauge can also be inserted into these P/T ports to determine the pressure differential between the entering and leaving water. This pressure differential can then be compared to the specification data on each particular heat pump to confirm the proper flow rate of the system. An individually-sized Enertech flow center can supply pumping requirements for the Ground Loop fluid, and can also be used to purge the loop system. Note – Refer to instructions included with the flow center for properly purging the ground loop. Important – the pump must be installed to supply fluid into the heat pump. Filling and purging a loop system are very important steps to ensure proper heat pump operation. Each loop must be purged with enough water flow to ensure a two feet per second flow rate in each circuit on the loop. This normally requires a 1½ to 3 HP high head pump to circulate fluid through the loop to remove all the air out of the loop and into a purging tank. Allow the pump to run 10 to 15 minutes after the last air bubbles have been removed. After purging is completed, add the calculated proper amount of antifreeze to give a 12 oF to 15oF freeze protection. After antifreeze has been installed and thoroughly circulated, it should be measured with a hydrometer, refractometer or any other suitable device to determine the actual freezing point of the solution. The purge pump can be used to pressurize the system for a final static pressure of 30-40 psig after the loop pipe has had enough time to stretch. In order to achieve the 30 to 40 psig final pressure, the loop may need to be initially pressurized to 60-65 psig. This static pressure may vary 10 psig from heating to cooling season, but the pressure should always remain above 20 psig, so circulation pumps do not cavitate or pull air into the system. Contact your local installer, distributor or factory representative for more information. B. Ground Water Installation A ground water system gets its name from the open discharge of water after it has been used by the heat pump. A well must be available that can supply all of the water requirements (see Table 1) of the heat pump for up to 24 hours/day on the coldest winter day plus any other water requirements drawing off that same well. Figure 5 shows the necessary components for ground water piping. First, a bladder type pressure tank with a “draw down” of at least 1½ times the well pump capacity must be installed on the supply side of the heat pump. Shut off valves and boiler drains on the entering and 6 leaving water lines are necessary for future maintenance. Important – A screen strainer must be placed on the supply line with a mesh size of 40 or 60 and enough surface area to allow for particle buildup between cleanings. Important – Pressure/Temperature (P/T) ports must be placed in the supply and discharge lines so that thermometers or pressure gauges can be inserted into the water stream. Important – A visual flow meter must be installed to allow visual inspection of the flow to determine when maintenance is required. (If you can’t read the flow, cleaning is required. See Water Coil Maintenance for cleaning instructions.) A solenoid control valve must be installed on the water discharge side of the heat pump to regulate the flow through the unit. Wire the solenoid to the “Plug, Accessory” connector on the controller. This valve opens when the unit is running and closes when the unit stops. Schedule 40 PVC piping, copper tubing, polyethylene or rubber hose can be used for supply and discharge water lines. Make sure line sizes are large enough to supply the required flow with a reasonable pressure drop (generally 1” diameter minimum). Water discharge is generally made to a drain field, stream, pond, surface discharge, tile line, or storm sewer. Important – ensure the discharge line has a pitch of at least three inches per 12 feet, has a minimum 2 feet of unobstructed freefall at the end of the line, and has at least 100 feet of unobstructed grade sloping away from the discharge outlet. CAUTION – A drain field requires soil conditions and adequate sizing to ensure rapid percolation. Consult local codes and ordinances to assure compliance. DO NOT discharge the water into a septic system. CAUTION – Never operate with flow rates less than specified. Low flow rates, or no flow, may cause the unit to shut down on a pressure lockout or may cause a freeze rupture of the heat exchanger. 1. Ground Water Freeze Protection CAUTION – Only specifically ordered equipment with a factory-installed 60 psig low-pressure switch can be used on ground water applications. (The low-pressure switch on a ground loop system has a 35 psig (previously 50) nominal cutout pressure.) If the water supply to the heat pump were interrupted for any reason, continued operation of the compressor would cause the water remaining in the heat exchanger to freeze, rupture the heat exchanger and may void warranty. 2. Water Coil Maintenance Water quality is a major concern for ground water systems. Problems can occur from scaling, particle buildup, suspended solids, corrosion, pH levels outside the 7-9 range, biological growth, or water hardness of greater than 100-PPM. If poor water quality is known to exist in your area, a cupro-nickel water coil may be required when ordering the system; or installing a ground loop system may be the best application. Water coil cleaning on ground water systems may be necessary on a regular basis. Depending on the specific water quality, the water coil can be cleaned by the following methods (Note – always remember to clean the strainer.): a. Chlorine Cleaning (Bacterial Growth) 1. Turn off all power to the heat pump during this procedure. 2. Close the shut-off valves upstream and downstream of the heat exchanger. 3. Connect a submersible pump to the hose bibs on the entering and leaving-water sides of the heat exchanger for reverse-direction flow. 4. Submerse the pump in a 5-gallon pail of water with enough chlorine bleach to kill the bacteria. Suggested mixture is 1 part chlorine bleach to 4 parts water. 5. Open the hose bibs to allow circulation of the solution. CAUTION – DO NOT allow the chlorine mixture to stand idle in the heat exchanger. 6. Start the pump and circulate the solution through the heat exchanger for about 15 minutes with at least 150% of the normal rated flow rate. The solution should change color to indicate the chlorine is killing and removing the bacteria from the heat exchanger. 7. Flush out the used solution by adding a fresh water supply to the pail. Repeat until the leaving water is clear. This procedure can be repeated annually, semiannually, or as often as it takes to keep bacteria out of the heat exchanger, or when bacteria appears in the visual flow meter to the point the flow cannot be read. Another alternative to bacteria problems is to shock your entire well. Shocking the well may give longer term relief from bacteria problems than cleaning the heat exchanger, but will probably need to be repeated, possibly every three to five years. Contact a well driller in your area for more information. b. Muriatic Acid Cleaning (Difficult Scaling and Particle Buildup Problems) 1. WARNING – Consult installer because of the dangerous nature of acids. Only an experienced and trained professional should perform this procedure. (Note – Use Oxalic Acid, CLR, Iron-Out or other descaling products before using Muriatic Acid.) 2. Turn off all power to the heat pump during this procedure. 3. Close the shut-off valves upstream and downstream of the heat exchanger. 4. Connect a submersible circulating pump to the hose bibs on the entering and leaving water sides of the heat exchanger for reverse-direction flow. Note – these are corrosive chemicals. Use disposable or suitable pump. 5. Submerse the pump in a five-gallon pail of water with a small amount of muriatic acid to create a final concentration of 5% muriatic acid. 7 WARNING – Always add acid to water; never add water to acid. 6. Open the hose bibs to allow circulation. 7. Start the pump and circulate the solution through the heat exchanger for about 15-30 minutes with at least 150% of the normal rated flow rate. 8. Flush out the used solution by adding a fresh water supply to the pail. Repeat until the leaving water is clear. Note – observe local codes for disposal. c. Freeze Cleaning (Scale/Particle Buildup) This applies only to Cupro Nickel heat exchangers, cylinder shape, used on Ground Water Applications. WARNING – Never attempt this process on a braze plate heat exchanger. It could cause the braze plate heat exchanger to rupture and may void the warranty. I. Before using the freeze cleaning procedure, verify it needs to be done by answering the following questions. 1. Determine and verify that the required water flow rate in GPM is both present and correct. 2. Determine the temperature differential of the water. Under normal conditions in the cooling mode, there should be a temperature difference of about 10-15°F between the supply side and discharge side. If the temperature difference is 8°F or less, consideration should be given to cleaning the water coil. II. If the water coil requires cleaning, carefully use the following steps for the freeze cleaning method. 1. Turn off the heat pump and its water supply. 2. Open a plumbing connection on the water supply side, if possible, to break the system vacuum and allow easier drainage of the system and water coil. 3. Drain the water out of the system and water coil via the boiler drains on the entering and leaving water lines, and the drain on the heat exchanger. WARNING – FAILURE TO COMPLETELY DRAIN THE WATER COIL HEAT EXCHANGER COULD FREEZE RUPTURE THE HEAT EXCHANGER! 4. Set the thermostat to "Heat" to start the heat pump in the heating mode and quickly freeze the coil. 5. Allow the heat pump to run until it automatically shuts off on low pressure and then turn the thermostat to the "Off" position. 6. Recap the water coil drain and tighten any plumbing connections that may have been loosened. 7. If so equipped, open the field installed drain cock on the water discharge side of the heat pump, and install a short piece of rubber hose to drain into a drain or bucket. A drain cock on the discharge side allows water flow to bypass the solenoid valve, flow valve, flow meter, or any other item that may be clogged by mineral debris. Draining to a bucket helps prevent clogging of drains and allows observing effectiveness of the procedure. 8. Turn on the water supply to the heat pump to start the process of flushing any mineral debris from the unit. 9. Set the thermostat to "Cool" and start the heat pump in the cooling mode to quickly thaw out the water coil. 10. Run the heat pump until the water coil is completely thawed out and loosened scale, mineral deposits, or other debris is flushed completely from the water coil. Allow at least five minutes of operation to ensure that the water coil is thoroughly thawed out. 11. If the water still contains mineral debris, and if the flow through the unit did not improve along with an increase in the temperature difference between the water supply and water discharge, repeat the entire procedure. 12. Reset the heat pump for normal operation. VII. ELECTRICAL SERVICE Note – Always refer to the inside of the electrical box cover for the correct wiring diagram, and always refer to the nameplate on the exterior of the cabinet for the correct electrical specifications. WARNING – ELECTRICAL SHOCK CAN CAUSE PERSONAL INJURY OR DEATH. Disconnect all power supplies before installing or servicing electrical devices. Only trained and qualified personnel should install, repair or service this equipment. WARNING – THE UNIT MUST BE PROPERLY GROUNDED! The main electrical service must be protected by a fuse or circuit breaker, and be capable of providing the amperes required by the unit at nameplate voltage. All wiring shall comply with the national electrical code and/or any local codes that may apply. Access to the line voltage contactor is through the knockouts provided on either side of the heat pump next to the front corner. Route EMT or flexible conduit with appropriate size and type of wire. Ensure adequate supply wiring to minimize the level of dimming lights during compressor startup on single-phase installations. Some dimming is normal, and a variety of start-assist accessories are available if dimming is objectionable. Important – some models already have a factory-installed start assist. Do not add additional start assists to those units. CAUTION – Route field electrical wiring to avoid contact with electrically live bare metal parts inside the electrical box and to avoid contact with the surface of the factory-installed start assist (if provided). CAUTION – Disconnect the power from the unit before removing or replacing any connectors, or servicing the blower motor. CAUTION – When servicing an ECM blower motor, disconnect power and wait at least five minutes before opening the motor to avoid electric shock from the motor’s internal capacitors. CAUTION – Three-phase units must be wired properly to ensure proper compressor rotation. Improper rotation may result in compressor damage. An electronic phase sequence indicator must be used to check supply-wiring 8 phases. Also, the “Wild” leg of the three-phase power must be connected to the middle leg on the contactor. Important – Only 208Vac FlowCenters can be wired directly to the compressor contactor and can be grounded in the grounding lug for 208/230Vac. An alternative loop pump or a pump for a different supply voltage must be powered from a separate fused power supply and controlled through an isolation relay that has its coil wired to the contactor circuit. Important – Units with internal installed Supplemental Electric Heat require a separate power supply for the Supplemental Electric Heat. For units with the PSC blower motor, an internal relay provides the power through the 3-pole terminal block (BF) for the forced-air blower motor. To change blower speeds, move the blower motor wire on BF to the desired speed. The effect of changing the blower speed setting on CFM output is shown in Table 4. VIII. 24 VOLT CONTROL CIRCUIT Note – Always refer to the inside of the electrical box cover for the correct wiring diagram. There are three basic sections of the low voltage circuit; transformer, thermostat, and controller. A. Transformer An internal transformer provides 24Vac for all control features of the heat pump. Even though the transformer is larger than the industry standard, it is in a warm electrical box and can be overloaded quickly. Table 5 shows the transformer usage. Table 5 – Transformer Usage (VA) Usage (VA) Component Contactor Reversing Valve Controller 20-1038 Thermostat Blower Motor Blower Relay Elec. Heat Relay (2) Plug Accessory (PA) Total Transformer VA size 17-27 UxOx 37-57 UxVx 87 UxOx 110 UxTx 7 8 2 1 --6 6 10 40 VA 60 7 8 2 1 2 --6 10 36 VA 75 16 8 2 1 --6 --10 43 VA 75 7 (2) 8 2 1 --6 (2) --5 42 VA 75 Important - If the system’s external controls require more than shown in table 5, an external transformer and isolation relays should be used. Important – Incorrect wiring of 24Vac control voltage on system controls can result in transformer burnout. Important – Units with a dual voltage rating (example, 208/230) are factory-wired for the higher voltage (example, 230). If connected to a power supply having the lower voltage, change the wiring to the transformer primary to the correct lead; otherwise premature failure, or inability to operate the control components may occur. B. Thermostat At a minimum, a 1-heat/1-cool heat pump thermostat must be used. If the unit is equipped with supplemental electric heat, a 2-heat/1-cool heat pump thermostat must be used. The thermostat controls all stages of operation of the heat pump. Initiation of each stage is implemented based on the recovery rate of the actual temperature to the set point temperature. This means that switching to a higher stage will require time (sometimes 15 minutes or more) for the thermostat to calculate rate of change. Consult the instructions in the thermostat box for proper mounting, installer set-up, and operation. Important – Be careful to select a thermostat location where external temperature sources will not affect sensed temperature. Important – If a single thermostat controls multiple heat pumps, the control wiring of the heat pumps must be isolated from each other with isolation relays to avoid excessive voltages or overheating and premature failure of the control components. Important – Thermostat cable with at least eight conductors must be run from the heat pump to the thermostat. Power is supplied to the thermostat by connecting the R and X (C) terminals to the heat pump terminal strip. C. Controller The controller receives a signal from the thermostat and initiates the correct sequence of operations for the heat pump. The controller performs the following functions: 1. Compressor Anti-Short-Cycle 2. Compressor Control 3. Ground Loop Pump / Ground Water Initiation 4. Compressor Staging 5. Blower Motor Control a. PSC Blower Operation and Speed Control (-UxOx) b. ECM Blower Operation and Speed Control (-UxVx) 6. Supplemental Electric Heat for 2nd Stage Heat 7. 4-Way Valve Control 8. Compressor Lockouts 9. Air Coil Defrost 10. System Diagnostics 11. 24Vac Fuse 12. Plug Accessory 13. Alarm Output 1. Compressor Anti-Short-Cycle An Anti-Short-Cycle (ASC) is a delay period between the time a compressor shuts down and when it is allowed to come on again. This protects the compressor and avoids nuisance lockouts for these two conditions; 1. A 70 to 130-second random time-out period occurs 9 before a re-start after the last shut down. 2. A 4-minute/25-second to 4-minute/45-second randomstart delay occurs immediately after power is applied to the heat pump. This occurs only after reapplying power to the unit. To reduce this timeout delay while servicing the unit, apply power, disconnect and reapply power very quickly to shorten the delay. Note - The thermostat supplied with the heat pump may also have a five-minute delay period after compressor shutdown before it will start again. A “Wait” indicator on the thermostat shows this delay. This delay can be reprogrammed to be from zero to five minutes. 2. Compressor Control When 24Vac is applied to the Y terminal on the controller wiring block, the controller decides, based on lockout and anti-short-cycle periods, when to turn on the compressor contactor. The M1 output of the controller energizes the contactor until 24Vac is removed from the Y terminal. 3. Ground Loop Pump / Ground Water Initiation On ground loop systems, a M1 output from the controller energizes the contactor to start the compressor and the ground loop pump. For Ground Water systems, the M1 output will also energize the ground water solenoid valve through the “Plug Accessory” connector. . 5. a. PSC Blower Operation and Speed Control (-UxOx) When 24Vac is applied to the G terminal on the controller wiring block, the controller passes this 24Vac power directly to the blower motor relay 5. b. ECM Blower Operation and Speed Control (-UxVx) When 24Vac is applied to the G terminal on the controller wiring block, the controller will energize the blower to operate at Low (G) speed. If 24Vac is applied to both G and Y (during 1st-stage operation), the controller will energize the blower to operate at Medium(Y) speed. An input to W2 (2nd stage heat) or E (Emergency heat) from the thermostat energizes the blower in high speed. These blower speeds are shown in Table 5. The CFM outputs are factory set, and should not be changed in the field. There is an “Adjust” setting, which allows the blower to be operated at +/-10% of the factory setting. For example, if the Adjust tap is set to the “-”, all the speeds will operate at 90% of the factory setting. If the Adjust tap is set to the “+”, all the speeds will operate at 110% of the factory setting. The Adjust tap is the only tap on the Blower Speed Controller that should ever be moved from the factory setting. Important – Power to the unit has to be interrupted for a few seconds to enable new ECM speed settings. The blower motor has internal circuitry that will maintain the selected CFM when changes occur in the external static pressure, such as the filter getting dirty. The motor does this by increasing its torque output to compensate for external duct static pressure resistance changes. Important – The ECM motor is Factory programmed with soft start and soft stop speed profiles to ensure the blower motor softly ramps to the proper CFM. Ramping provides quieter operation and increased comfort. It may take a few seconds for the blower to start when the thermostat initially calls for heating or cooling, and for the blower to stop after the thermostat is satisfied. 6. Supplemental Electric Heat for 2nd Stage Heat & Emergency Heat Mode The Ultra Top Discharge vertical units have the option of field-installed electric supplemental heat. Use a separate duct-installed heater for Bottom Discharge and Horizontal applications. This provides an extra 5 kilowatts (approximately 17,000 BTU/hr) of supplemental heat when the room thermostat calls for auxiliary heat and provides 10 kilowatts (approximately 34,000 BTU/hr) of backup heat when the room thermostat is set to the emergency heat mode. The heater can also be wired to supply the full 10kW during either supplemental or emergency heat modes. Important – A jumper plug on the 20-1038 controller (marked J2) ties W2 signal to E. This jumper plug must be removed for 5 kW of supplemental heat and 10 kW of emergency heat. If the J2 jumper is not removed, the heater will supply the full 10 kW during either supplemental or emergency heat modes. 7. 4-Way Valve Control When 24Vac is applied to the O terminal on the wiring block, the controller energizes its O output to provide 24Vac power to the 4-way reversing valve to switch the refrigerant circuit to the cooling mode. 8. Compressor Lockouts The controller will lock out the compressor if either the high-pressure 600 psig or the low-pressure 35 psig (previously 50) on ground loop or 60 psig on ground water switch opens. This lockout condition means that the unit has shut down to protect itself, and will not come back on until power has been disconnected (via the circuit breaker) to the heat pump for one minute. Problems that could cause a lockout situation include: 1. Low water flow or extreme water temperatures 2. Low air flow or extreme air temperatures 3. Cold ambient air temperature conditions 4. Internal heat pump operation problems. If a lockout condition exists, the heat pump should not be reset more than once; and a service technician should be called immediately. CAUTION – Repeated reset may cause severe damage to the system and may void warranty. The cause of the lockout must be determined and corrected. 9. Air Coil Defrost Restricted airflow in the cooling mode, caused by a dirty air filter or airside heat exchanger, may result in an iced up air coil and/or low suction pressure. The controller will 10 automatically switch the heat pump to defrost mode if the low-pressure switch opens during the cooling mode: the O output will be de-energized to run the unit in heating, the blower will continue to run, and the Low Pressure indicator light will blink. This defrost mode will last for approximately 80 seconds, then the unit will go to the 70130-second time-out re-start delay. After the delay times out, the heat pump will resume normal operation. CAUTION – If the heat pump continually goes to the air coil defrost mode, a service technician should be called immediately. 10. System Diagnostics The controller is equipped with diagnostic LED lights that indicate the system status at any particular time. The lights indicate the following conditions: 1. 24 Volt system power GREEN 2. Fault or Lockout YELLOW 3. Anti-short-cycle mode RED If a room thermostat installed with the heat pump system has a lockout indicator, the controller will send a signal from L on the terminal strip to a LED on the thermostat to indicate a lockout condition. 11. 24 Vac Fuse The controller has a glass-cartridge fuse located on the circuit board adjacent to the 24Vac power connector. The green system power LED will be off if this fuse is open. A spare fuse is located in the saddle attached to the side of the 24Vac power connector.Note – Ensure the new fuse fits tightly in the fuse clips after replacement. 12. Plug Accessory (PA) The Plug Accessory output is internally connected to the M1 output and is energized whenever M1 turns on the compressor contactor. The maximum rating of this output is 10VA sealed and 20VA inrush and is typically intended to power a 24Vac ground water solenoid valve. 13. Alarm Output This output is a 2-position screw terminal connector identified as “Fault Test” on the controller board and as DO on the wiring diagram. It is an isolated dry contact output (0.1 ohm resistance) that closes during a controller lockout and is intended for use as an input to a dial-out type of monitoring system. The maximum electrical rating is 2mA up to 30Vac or 50mA up to 40Vdc. IX. STARTUP / CHECKOUT Before applying power to the heat pump, check the following items: Water supply plumbing to the heat pump is completed and operating. Manually open the water valve on well systems to check flow. Make sure all valves are open and air has been purged from a loop system. Never operate the system without correct water flow. All high voltage and low voltage wiring is correct and checked out, including wire sizes, fuses and breakers. Set thermostat to the “OFF” position. The heat pump is located in a warm area (above 45 oF). Starting the system with low ambient temperature conditions is more difficult. Do not leave until the space is brought up to operating temperatures. You may now apply power to the unit. A 4-minute/35second delay on power up is programmed into the heat pump before the compressor will operate. During this time you can verify airflow with the following procedure: Place the thermostat in the “FAN ON” position. The blower should start in low speed. Check airflow at the registers to make sure that they are open and that air is being distributed throughout the house. When airflow has been checked, move the thermostat to the “FAN AUTO” position. The blower should stop. The following steps will ensure the system is heating and cooling properly. After the initial time-out period, the red indicator light on the controller will shut off. The heat pump is now ready for operation. With the thermostat in the “HEAT” mode, turn it up to its highest temperature setting. The compressor should start, with the blower starting a few seconds later. The thermostat may have its own compressor delay (shown by “Wait” on the thermostat), but the compressor will start after all delays. After running the unit for five minutes, check the airside return and supply temperatures. An air temperature rise of 20oF to 30oF is normal in the heating mode, but variations in water temperature and water flow rate can cause variations outside the normal range. Use a single pressure gauge to check the fluid pressure drop through the ground-side heat exchanger to ensure proper flow for the system. Turn the thermostat to the “OFF” mode. The compressor will shut down in a few seconds, with the blower stopping shortly after. Next, set the thermostat to “COOL” and turn down to its lowest setting. The compressor will start after an anti-short cycle period of 70 to 130 seconds from its last shutdown, and the blower will start a few seconds later. The anti-short cycle period is indicated by the red light (labeled ASC) on the controller. After the unit has run in cooling for five minutes, check the airside return and supply temperatures. An air temperature drop of 15oF to 20oF is normal in the cooling mode but airflow and humidity can affect temperature drop. Set the thermostat for normal operation. Instruct the owner on the correct operation of the entire heat pump system. The unit is now operational. X. SERVICE and LOCKOUT LIGHTS Properly installed, the ECONAR Ultra heat pump requires only minor maintenance, such as periodic cleaning of the air coil, air filter, and the ground water 11 heat exchanger on a Ground Water system. Setting up regular service checkups with your Enertech dealer should be considered. Any major problems with the heat pump system operation will be indicated on the lockout lights. CAUTION – During evacuation of refrigerant of a system not having antifreeze protection of a water-side heat exchanger, water in the unprotected heat exchanger must be removed or continuously flowing to avoid a potential heat exchanger failure caused by freeze rupture. CAUTION – Service on systems using R410A refrigerant requires special consideration (Refer to ECONAR Instruction 10-2016 for more detail.). Always install a new filter/dryer after replacing a refrigeration component (compressor, etc.) and evacuate down to 150 microns. manner. Be careful in selecting optional filters so that excessive external resistance to airflow does not occur. C. Preseason Inspection Before each season, the air coil, drain pan, and condensate drain should be inspected and cleaned as follows: Turn off the circuit breakers. Remove the access panels. Clean the air coil by vacuuming it with a soft-brush attachment. Remove any foreign matter from the drain pan. Flush the pan and drain tube with clear water. Replace the access panels and return power to the unit. D. Ground Water Heat Exchanger Refer to Section VI.B.2 for details. A. Lockout Lights The heat pump controller and room thermostat will display a system lockout. If lockout occurs, follow the procedure below: 1. Determine and record which indicator lights on the Controller are illuminated. (Refer to Section XIII for more information on possible causes of Lockout Conditions.) 2. Check for a clean air filter, correct air-flow, and correct water supply from the ground loop or ground water system. 3. Reset the system by disconnecting power at the circuit breaker for one minute, and then reapplying power. 4. If shutdown reoccurs, call your Enertech dealer. Do not continuously reset the lockout condition or damage may occur. Note – Improper fluid flow, incorrect airflow, or incorrect antifreeze levels are the cause of almost all lockouts. B. Air Filter The Ultra forced air heat pump includes a disposable air filter. This filter should normally be replaced once a month during normal usage, or more frequently during extreme usage or if system performance has decreased. A dirty filter will increase static pressure to the system and decrease the amount of airflow (CFM) for a PSC blower motor. If a variable speed ECM blower is being used, an increase in static pressure will cause the variable speed blower to increase its speed in order to maintain airflow levels. In extreme cases, the blower will not be able produce the correct amount of airflow. These system changes will cause the unit to consume more power than normal, reducing the efficiency of the system. In the heating mode, reduced airflow may increase the cost of operation and, in extreme cases, cause system lockout due to high refrigerant pressures. In the cooling mode, reduced airflow may reduce cooling capacity and, in extreme cases, ice the air coil over causing system shutdown due to low refrigerant pressures. If a different filter is used in place of the factory-supplied filter, it should also be cleaned or changed in a timely XI. ROOM THERMOSTAT OPERATION Installations may include a wide variation of available electronic room thermostats, and most of them are required to be configured by the Installer (according to the Installation Guide included with the thermostat) and checked out after being installed. Important – At a minimum: 1. Ensure the thermostat is set up for the “System Type” it is installed on. 2. Ensure the thermostat is configured for “Manual Heat/Cool Changeover.” 3. Change other Installer Settings only if necessary. 4. Remember to press “Done” to save the settings and to exit “Installer Setup.” 5. Run the system through all modes of operation in the thermostat instructions to ensure correct operation. If you have additional questions, please refer to the installation manual that was sent with the thermostat. XII. DESUPERHEATER (OPTIONAL) A Ultra heat pump equipped with a double-wall vented desuperheater can provide supplemental heating of a home’s domestic hot water by stripping some energy from the superheated gas leaving the compressor and transferring it to a hot water tank. A desuperheater pump, manufactured into the unit, circulates water from the domestic hot water tank, heats it and returns it to the tank. The desuperheater only provides supplemental heating when the compressor is already running to heat or cool the conditioned space. Because the desuperheater is using some energy from the heat pump to heat water, the heat pump’s capacity in the winter is about 10% less than a unit without a desuperheater. During extremely cold weather, or if the heat pump cannot keep up with heating 12 the space, the desuperheater fuse may be removed to get full heating capacity out of the unit. WARNING – Do not remove the desuperheater’s high temperature cutout switch, or tank temperatures could become dangerously high. The desuperheater's high temperature cutout switch is located on the return line from the water heater and is wired in series with the desuperheater pump to disable it from circulating at entering water temperatures above 140oF. If the tank temperatures become uncomfortably hot, move this switch to the leaving water line, which will reduce the tank maximum temperatures 10oF to 15oF. CAUTION – Running the desuperheater pump without water flow will damage the pump. A fuse is attached to the fuse holder and must be inserted in the fuse holder after the desuperheater is purged and operational. Important – Do not insert the fuse until water flow is available and the desuperheater is completely purged of air, or the pump may be damaged. Remove the fuse to disable the pump if the desuperheater isn’t in operation. bottom of the water heater (See Figure 6). This is the preferred method for ease of installation, comfort and efficiency. The tee eliminates the need to tap into the domestic hot water lines and eliminates household water supply temperature variations that could occur from connecting to the hot water pipes. Poor water quality may restrict the effectiveness of using the desuperheater tee by plugging it with scale or buildup from the bottom of the tank, restricting water flow. METHOD 2 Taking water from the bottom drain and returning it to the cold water supply line (See Figure 7). This method maintains the same comfort and efficiency levels but increases installation time and costs. Important – This method requires a check valve in the return line to the cold water supply to prevent water from flowing backwards through the desuperheater when the tank is filling. Water passing through the pump backwards damages the rotor’s bearing, which reduces pump life and causes noise problems in the pump. Note - A spring-type check valve with a pressure-drop rating of 1/2 psig or less is recommended. All air must be purged from the desuperheater plumbing before the pump is engaged. To purge small amounts of air from the lines, loosen the desuperheater pump from its housing by turning the brass collar. Let water drip out of the housing until flow is established, and re-tighten the brass collar. Using 1/2-inch copper tubing from the tank to the desuperheater inlet is recommended to keep water velocities high, avoiding air pockets at the pump inlet. An air vent in the inlet line can also help systems where air is a problem. If one is used (recommend Watts Regulator brand FV-4 or Spirovent), mount it near the desuperheater inlet roughly 2-1/2 inches above the horizontal pipe. Shutoff valves allow access to the desuperheater plumbing without draining the hot water tank. Keep the valves open when the pump is running. Desuperheater maintenance includes periodically opening the drain on the hot water tank to remove deposits. If hard water, scale, or buildup causes regular problems in hot water tanks in your area, it may result in a loss of desuperheater effectiveness. This may require periodic cleaning with Iron Out. CAUTION – Insulated copper tubing must be used to run from the hot water tank to the desuperheater connections on the side of unit. The built-in desuperheater pump can provide the proper flow to the desuperheater if the total equivalent length of straight pipe and connections is kept to a maximum of 90 feet of ½-inch type L copper tubing (or a combination of approximately 60 feet with typical elbows and fittings). This tubing can be connected to the water tank in two ways: METHOD 1 Using a desuperheater tee installed in the drain at the 13 XIII. Performance Ratings Ultra Forced Air Vertical Models Ground Loop HEATING 32ºF EWT AHRI/ISO 13256-1 MODELS EV 170/171 EV 270/271 EV 370/371 EV 470/471 CFM 625 900 1100 1550 GPM 5 8 9 12 BTU/hr 14,500 22,300 32,000 41,000 COP 3.3 3.6 3.6 3.6 Ground Water COOLING 77ºF EWT BTU/hr 18,800 28,000 35,000 48,000 HEATING 50ºF EWT AHRI/ISO 13256-1 EER 17.4 18.0 17.1 17.1* MODELS EV 170/171 EV 270/271 EV 370/371 EV 470/471 CFM 625 900 1100 1550 GPM 5 8 9 12 BTU/hr 19,300 28,000 36,500 49,500 COP 4.0 4.2 4.1 4.1 COOLING 59ºF EWT BTU/hr 20,400 32,000 36,000 50,100 EER 23.9 25.0 21.1 21.1* Configuration Options Ultra Forced Air Models Model Suffix Exxx0-x-Uxxx Exxx1-x-Uxxx Exxxx-1-Uxxx Exxxx-2-Uxxx Exxxx-3-Uxxx Exxxx-5-Uxxx EHxxx-6-Uxxx EHxxx-7-Uxxx EHxxx-8-Uxxx EVxxx-x-UOxx EVxxx-x-URxx EVxxx-x-UBxx EHxxx-x-UOxx EHxxx-x-UCxx EHxxx-x-UxTx Exxxx-x-UxOx Exxxx-x-UxVx Exxxx-x-UxxO Exxxx-x-UxxN Description Standard, No Desuperheater Desuperheater Standard, 208/230-1, 60 Hz 208/230-3, 60Hz 460-3, 60Hz 277-1, 60Hz 208/230-1, 60Hz w/ EMS 208/230-3, 60Hz w/ EMS 460-3, 60Hz w/ EMS Standard, Left Side Air Return Right Side Return Bottom Discharge (right return) Standard, End Right Discharge Front Right Discharge Staged Tandem Compressor Standard PSC Blower Variable Speed ECM Blower Standard Earth Loop Coil Cupro-Nickel Well Water Coil 1 Brazed Plate Ground Loop Heat Exchanger Standard Special Order 17 Vertical 27 37 47 1 1 1 1 14 XIV. Performance Data, Ultra Forced Air Models EV 170/171 @ 625 CFM EWT GPM 4 15 5 6 4 20 5 6 4 25 5 6 4 30 5 6 4 35 5 6 2 45 3 5 2 50 3 5 2 60 3 5 2 70 3 5 dP ft 3.0 5.0 7.0 3.0 5.0 7.0 3.0 5.0 7.0 3.0 5.0 7.0 3.0 5.0 7.0 2.0 2.0 5.0 2.0 2.0 5.0 2.0 2.0 5.0 2.0 2.0 5.0 HEATING @ 68oF DB dP psi MBTU/hr KW COP 1.5 12.9 1.1 3.3 2.2 13.3 1.1 3.4 3.0 13.5 1.2 3.4 1.5 13.7 1.2 3.5 2.2 14.1 1.2 3.6 3.0 14.3 1.2 3.6 1.5 14.4 1.2 3.6 2.2 14.9 1.2 3.7 3.0 15.1 1.2 3.7 1.5 15.2 1.2 3.7 2.2 15.6 1.2 3.8 3.0 15.9 1.2 3.8 1.5 15.9 1.2 3.9 2.2 16.4 1.2 4.0 3.0 16.7 1.2 4.0 0.9 17.3 1.3 4.0 0.9 17.7 1.3 4.1 2.2 18.0 1.3 4.2 0.9 18.0 1.3 4.1 0.9 18.4 1.3 4.1 2.2 18.7 1.3 4.3 0.9 19.3 1.4 4.2 0.9 19.7 1.4 4.2 2.2 20.3 1.3 4.5 0.9 20.6 1.4 4.3 0.9 21.1 1.4 4.3 2.2 21.8 1.3 4.8 SUCT PRESS 52-62 53-63 54-64 60-70 61-71 62-72 67-77 68-78 69-79 74-84 75-85 76-86 82-92 83-93 84-94 97-107 98-108 99-109 101-111 102-112 105-115 110-120 111-121 120-130 118-128 119-129 135-145 HEAD PRESS EWT GPM 265-285 2 270-290 40 3 275-295 5 275-295 2 280-300 50 3 285-305 5 285-305 2 290-310 60 3 295-315 5 290-310 2 295-315 70 3 300-320 5 300-320 4 305-325 75 5 310-330 6 320-340 4 325-345 80 5 325-345 6 325-345 4 330-350 85 5 330-350 6 345-365 4 350-370 90 5 350-370 6 365-385 4 370-390 95 5 370-390 6 dP ft 2.0 2.0 5.0 2.0 2.0 5.0 2.0 2.0 5.0 2.0 2.0 5.0 3.0 5.0 7.0 3.0 5.0 7.0 3.0 5.0 7.0 3.0 5.0 7.0 3.0 5.0 7.0 COOLING @ 80oF DB/67oF WB dP psi MBTU/hr KW EER 0.9 21.4 0.9 23.4 0.9 21.8 0.9 24.6 2.2 22.5 0.9 25.8 0.9 21.0 1.0 21.5 0.9 21.5 1.0 22.6 2.2 22.1 0.9 23.7 0.9 20.7 1.0 19.8 0.9 21.1 1.0 20.8 2.2 21.8 1.0 21.9 0.9 20.4 1.1 18.3 0.9 20.8 1.1 19.3 2.2 21.4 1.1 20.2 1.5 18.4 1.2 15.8 2.2 18.7 1.1 16.6 3.0 18.9 1.1 16.9 1.5 17.9 1.2 15.0 2.2 18.2 1.2 15.8 3.0 18.4 1.1 16.1 1.5 17.4 1.2 14.3 2.2 17.7 1.2 15.0 3.0 17.9 1.2 15.4 1.5 16.9 1.2 13.6 2.2 17.3 1.2 14.3 3.0 17.4 1.2 14.6 1.5 16.4 1.3 13.0 2.2 16.8 1.2 13.6 3.0 16.9 1.2 13.9 SUCT PRESS 126-136 125-135 116-126 128-138 127-137 120-130 131-141 130-140 124-134 133-143 132-142 128-138 131-141 130-140 129-139 133-143 132-142 131-141 135-145 134-144 133-143 137-147 136-146 135-145 139-149 138-148 137-147 HEAD PRESS 175-195 170-190 140-160 210-230 205-225 180-200 250-270 245-265 215-235 290-310 285-305 255-275 280-300 275-295 270-290 295-315 290-310 285-305 315-335 310-330 305-325 335-355 330-350 325-345 355-375 350-370 345-365 dP ft 1.8 2.8 6.5 1.8 2.8 6.5 1.8 2.8 6.5 1.8 2.8 6.5 5.5 6.5 8.3 5.5 6.5 8.3 5.5 6.5 8.3 5.5 6.5 8.3 5.5 6.5 8.3 COOLING @ 80oF DB/67oF WB dP psi MBTU/hr KW EER 0.8 37.8 1.5 25.8 1.2 38.2 1.4 26.9 2.8 39.4 1.3 29.2 0.8 35.4 1.5 24.1 1.2 35.8 1.4 25.1 2.8 36.9 1.4 27.2 0.8 32.9 1.5 22.3 1.2 33.3 1.5 23.2 2.8 34.3 1.4 25.2 0.8 30.5 1.5 20.5 1.2 30.8 1.5 21.4 2.8 31.8 1.4 23.2 2.4 30.2 1.4 21.8 2.8 30.5 1.4 22.2 3.6 30.8 1.4 22.7 2.4 28.9 1.4 20.8 2.8 29.2 1.4 21.2 3.6 29.5 1.4 21.7 2.4 27.7 1.4 19.8 2.8 27.9 1.4 20.2 3.6 28.2 1.4 20.6 2.4 26.4 1.4 18.9 2.8 26.7 1.4 19.2 3.6 26.9 1.4 19.6 2.4 25.1 1.4 17.9 2.8 25.4 1.4 18.2 3.6 25.6 1.4 18.6 SUCT PRESS 130-140 129-139 123-133 133-143 132-142 126-136 135-145 134-144 128-138 137-147 136-146 130-140 133-143 132-142 131-141 134-144 133-143 132-142 135-145 134-144 133-143 136-146 135-145 134-144 137-147 136-146 135-145 HEAD PRESS 165-185 160-180 145-165 195-215 190-210 175-195 225-235 220-240 205-225 265-285 260-280 245-265 265-285 260-280 255-275 285-305 280-300 275-295 300-320 295-315 290-310 320-340 315-335 310-330 335-355 330-350 325-345 EV 270/271 @ 900 CFM EWT GPM 7 15 8 9 7 20 8 9 7 25 8 9 7 30 8 9 7 35 8 9 4 45 5 8 4 50 5 8 4 60 5 8 4 70 5 8 dP ft 5.5 6.5 8.3 5.5 6.5 8.3 5.5 6.5 8.3 5.5 6.5 8.3 5.5 6.5 8.3 1.8 2.8 6.5 1.8 2.8 6.5 1.8 2.8 6.5 1.8 2.8 6.5 HEATING @ 68oF DB dP psi MBTU/hr KW COP 2.4 17.5 1.7 3.0 2.8 17.7 1.7 3.1 3.6 17.9 1.7 3.1 2.4 18.8 1.7 3.2 2.8 19.0 1.7 3.2 3.6 19.2 1.7 3.3 2.4 20.2 1.7 3.4 2.8 20.4 1.8 3.4 3.6 20.6 1.8 3.4 2.4 21.5 1.7 3.6 2.8 21.7 1.8 3.6 3.6 21.9 1.8 3.6 2.4 22.8 1.8 3.7 2.8 23.1 1.8 3.7 3.6 23.3 1.8 3.7 0.8 24.2 1.8 3.9 1.2 24.5 1.8 4.0 2.8 25.8 1.9 4.1 0.8 25.3 1.8 4.0 1.2 25.8 1.8 4.1 2.8 27.1 1.9 4.2 0.8 27.8 1.8 4.4 1.2 28.3 1.9 4.5 2.8 29.8 1.9 4.6 0.8 30.3 1.9 4.7 1.2 30.9 1.9 4.8 2.8 32.5 1.9 4.9 SUCT PRESS 51-61 52-62 53-63 59-69 60-70 61-71 67-77 68-78 69-79 76-86 77-87 78-88 84-94 85-95 86-96 97-107 98-108 101-111 105-115 106-116 109-119 122-132 123-133 126-136 138-148 139-149 142-152 HEAD PRESS EWT GPM 255-275 4 260-280 40 5 265-285 8 265-285 4 270-290 50 5 275-295 8 275-295 4 280-300 60 5 285-305 8 285-305 4 290-310 70 5 295-315 8 295-315 7 300-320 75 8 305-325 9 315-335 7 320-340 80 8 325-345 9 325-345 7 330-350 85 8 335-355 9 350-370 7 355-375 90 8 360-380 9 370-390 7 375-395 95 8 380-400 9 15 EV 370/371 @ 1100 CFM EWT GPM 8 15 9 10 8 20 9 10 8 25 9 10 8 30 9 10 8 35 9 10 5 45 6 9 5 50 6 9 5 60 6 9 5 70 6 9 dP ft 6.5 8.3 8.8 6.5 8.3 8.8 6.5 8.3 8.8 6.5 8.3 8.8 6.5 8.3 8.8 5.0 7.0 8.3 5.0 7.0 8.3 5.0 7.0 8.3 5.0 7.0 8.3 HEATING @ 68oF DB dP psi MBTU/hr KW COP 2.8 24.5 2.4 3.0 3.6 24.7 2.4 3.0 3.8 25.0 2.4 3.0 2.8 26.6 2.5 3.2 3.6 26.9 2.5 3.2 3.8 27.1 2.5 3.2 2.8 28.7 2.5 3.4 3.6 29.0 2.5 3.4 3.8 29.3 2.6 3.4 2.8 30.8 2.6 3.5 3.6 31.1 2.6 3.5 3.8 31.5 2.6 3.5 2.8 33.0 2.6 3.7 3.6 33.3 2.6 3.7 3.8 33.6 2.7 3.7 2.2 37.0 2.7 4.1 3.0 37.8 2.7 4.1 3.6 37.6 2.7 4.0 2.2 37.6 2.6 4.2 3.0 38.4 2.7 4.2 3.6 39.7 2.8 4.2 2.2 38.9 2.6 4.4 3.0 39.6 2.7 4.4 3.6 44.0 2.9 4.5 2.2 40.1 2.6 4.6 3.0 40.9 2.6 4.6 3.6 48.3 3.0 4.7 SUCT PRESS 44-54 45-55 56-66 54-64 55-65 56-66 62-72 63-73 64-74 70-80 71-81 72-82 79-89 80-90 81-91 94-104 95-105 98-108 101-111 102-112 106-116 115-125 116-126 125-135 129-139 130-140 142-152 HEAD PRESS EWT GPM 250-270 5 255-275 40 6 260-280 9 265-285 5 270-290 50 6 275-295 9 280-300 5 285-305 60 6 290-310 9 300-320 5 305-325 70 6 310-330 9 315-335 8 320-340 75 9 325-345 10 345-365 8 350-370 80 9 355-375 10 355-375 8 360-380 85 9 370-390 10 380-400 8 385-405 90 9 405-425 10 405-425 8 410-430 95 9 435-455 10 dP ft 5 7 8.3 5 7 8.3 5 7 8.3 5 7 8.3 6.5 8.3 8.8 6.5 8.3 8.8 6.5 8.3 8.8 6.5 8.3 8.8 6.5 8.3 8.8 COOLING @ 80oF DB/67oF WB dP psi MBTU/hr KW EER 2.2 48.5 1.7 28.3 3 49.5 1.7 28.3 3.6 49.5 1.8 26.8 2.2 46.0 1.8 25.4 3 47.0 1.8 25.4 3.6 46.9 1.9 24.2 2.2 43.6 1.9 22.5 3 44.5 2.0 22.5 3.6 44.4 2.1 21.6 2.2 41.1 2.1 19.7 3 42.0 2.1 19.7 3.6 41.8 2.2 19.0 2.8 40.1 2.3 17.7 3.6 40.5 2.3 17.7 3.8 40.9 2.3 17.7 2.8 38.8 2.4 16.4 3.6 39.2 2.4 16.4 3.8 39.6 2.4 16.4 2.8 37.6 2.5 15.1 3.6 37.9 2.5 15.1 3.8 38.3 2.5 15.1 2.8 36.3 2.6 13.8 3.6 36.7 2.7 13.8 3.8 37.0 2.7 13.8 2.8 35.0 2.8 12.5 3.6 35.4 2.8 12.5 3.8 35.7 2.9 12.5 SUCT PRESS 124-134 125-135 126-136 124-134 125-135 126-136 124-134 125-135 126-136 125-135 126-136 128-138 127-137 128-138 129-139 127-137 128-138 129-139 127-137 128-138 129-139 128-138 129-139 130-140 128-138 129-139 130-140 HEAD PRESS 195-215 200-220 210-230 225-245 230-250 240-260 255-275 260-280 270-290 285-305 290-310 300-320 310-330 315-335 320-340 325-345 330-350 335-355 340-360 345-365 350-370 355-375 360-380 365-385 370-390 375-395 380-400 SUCT PRESS 47-57 48-58 49-59 54-64 56-66 57-67 62-72 63-73 64-74 70-80 71-81 72-82 78-88 79-89 80-90 87-97 88-98 89-99 95-105 96-106 102-112 110-120 111-121 117-127 125-135 126-136 133-143 HEAD PRESS EWT GPM 240-260 7 245-265 40 8 25-270 12 255-275 7 260-280 50 8 265-285 12 265-285 7 270-290 60 8 275-295 12 280-300 7 285-305 70 8 290-310 12 295-315 11 300-320 75 12 305-325 13 310-330 11 315-335 80 12 320-340 13 325-345 11 330-350 85 12 335-355 13 350-370 11 355-375 90 12 365-385 13 375-395 11 380-400 95 12 390-410 13 dP ft 5.5 6.5 12.2 5.5 6.5 12.2 5.5 6.5 12.2 5.5 6.5 12.2 10.6 12.2 14.1 10.6 12.2 14.1 10.6 12.2 14.1 10.6 12.2 14.1 10.6 12.2 14.1 COOLING @ 80oF DB/67oF WB dP psi MBTU/hr KW EER 2.4 59.9 2.4 24.5 2.8 60.5 2.4 25.0 5.3 63.6 2.4 27.0 2.4 57.6 2.6 22.2 2.8 58.2 2.6 22.6 5.3 60.5 2.5 24.2 2.4 55.3 2.8 19.8 2.8 55.9 2.8 20.2 5.3 57.4 2.7 21.4 2.4 53.0 3.0 17.5 2.8 53.6 3.0 17.9 5.3 54.3 2.9 18.7 4.6 52.3 3.1 16.9 5.3 52.8 3.1 17.3 6.1 53.3 3.0 17.6 4.6 50.7 3.3 15.6 5.3 51.2 3.2 15.9 6.1 51.8 3.2 16.2 4.6 49.2 3.5 14.2 5.3 49.7 3.4 14.5 6.1 50.2 3.6 13.9 4.6 47.7 3.7 12.8 5.3 48.2 3.7 13.1 6.1 48.6 3.6 13.4 4.6 46.1 4.0 11.5 5.3 46.6 4.0 11.7 6.1 47.1 3.9 11.9 SUCT PRESS 113-123 113-123 115-125 115-125 115-125 117-127 117-127 117-127 119-129 119-129 119-129 120-130 121-131 121-131 122-132 122-132 122-132 123-133 123-133 123-133 124-134 124-134 124-134 125-135 124-134 124-134 125-135 HEAD PRESS 170-190 165-185 135-155 205-225 200-220 175-195 235-255 230-250 210-230 270-290 265-285 250-270 270-290 265-285 260-280 290-310 285-305 280-300 310-330 305-325 300-320 330-350 325-345 320-340 345-365 340-360 335-355 EV 470/471 @ 1550 CFM EWT GPM 11 15 12 13 11 20 12 13 11 25 12 13 11 30 12 13 11 35 12 13 7 45 8 12 7 50 8 12 7 60 8 12 7 70 8 12 dP ft 10.6 12.2 14.1 10.6 12.2 14.1 10.6 12.2 14.1 10.6 12.2 14.1 10.6 12.2 14.1 5.5 6.5 12.2 5.5 6.5 12.2 5.5 6.5 12.2 5.5 6.5 12.2 HEATING @ 68oF DB dP psi MBTU/hr KW COP 4.6 31.3 2.9 3.2 5.3 31.6 2.9 3.2 6.1 32.0 2.9 3.2 4.6 33.8 3.0 3.3 5.3 34.2 3.0 3.3 6.1 34.5 3.1 3.3 4.6 36.3 3.1 3.4 5.3 36.7 3.2 3.4 6.1 37.0 3.2 3.4 4.6 38.8 3.2 3.6 5.3 39.2 3.2 3.6 6.1 39.6 3.2 3.6 4.6 41.3 3.3 3.7 5.3 41.7 3.3 3.7 6.1 42.1 3.3 3.7 2.4 45.0 3.4 3.9 2.8 45.5 3.4 3.9 5.3 46.7 3.6 3.8 2.4 47.7 3.5 4.0 2.8 48.2 3.5 4.0 5.3 49.2 3.7 3.9 2.4 53.1 3.7 4.2 2.8 53.6 3.7 4.2 5.3 54.3 3.9 4.1 2.4 58.4 3.9 4.4 2.8 59.0 3.9 4.4 5.3 59.3 4.0 4.3 16 XV. Fan Performance Data Ultra (-UxOx) UNIT SIZE EV 170/171 EV 270/271 EV 370/371 EV 470/471 FAN SPEED Low Medium High* Low Medium* High Low Medium High* Low Medium High* 0.10 550 610 675 870 980 1090 1005 1140 1210 1325 1505 1685 External Static Pressure - in WG 0.20 0.25 0.30 0.35 490 460 445 430 550 530 510 480 625 600 580 560 800 775 750 735 900 870 845 830 1000 965 940 920 935 890 855 815 1065 1010 965 935 1110 1070 1030 985 1235 1200 1165 1135 1415 1375 1320 1275 1550 1500 1435 1405 0.15 520 580 650 825 935 1050 965 1100 1150 1275 1450 1625 0.40 410 460 525 710 800 865 805 915 960 1105 1245 1360 0.50 385 440 480 650 760 840 740 840 895 1055 1185 1305 Ultra (-UxVx) UNIT SIZE EV 370/371 EV 470/471 Low (G) 485 680 Medium (Y) 1100 1550 High (W2, E) 1210 1705 XVI. Physical Data 37Ux0x 37UxVx 27 4 3 4 5 Vert. / 4 Horz. 5 5 9x7 9x7 10x8 10x8 10x8 11x10 PSC 1/6 PSC 1/4 225 235 Compressor Expansion Device Air Coil Type No. of Air Coil Rows Fan Wheel (dia. x width) Fan Motor Type Fan Motor (HP) Desuperheater Pump Transformer (VA) Weight (lbs) Ultra 47Ux0x 47 UxVx 57Ux0x 57UxVx Compliant Scroll Thermostatic High Density 17 1/3 3/4 280 UxOx = PSC; UxVx = Variable Speed ECM 1.0 1/2 3/4 3/4 1/150 HP 55 325 345 67Ux0x 67UxVx 1.0 1.0 385 GH87 GH110 5 10x8 (2) PSC 1/2 (2) 5 10x8 (2) PSC 3/4 (2) 495 645 17 XVII. Dimensions – EV Vertical Top Discharge Models B A C E F Access Panels 3.0" 0.88" Dia. Knockouts G H In from Ground Loop Condensate Drain Out to Ground Loop 0.88" Dia. Knockout Out to Water Heater In from Water Heater Desuperheater W D Model Top-Discharge Dimensions H W D Ultra 17 Uxxx 38.2 19.0 24.0 9.38 10.25 1.0 FPT 1.0 FPT 1.0 FPT 20 x 20 (top load) 0.6 19.9 0.88 18.0 7.0 Ultra 27 Uxxx 53.1 21.0 26.0 9.38 10.25 1.0 FPT 1.0 FPT 1.0 FPT 21-5/8 x 29 (top load) 0.6 21.9 1.3 28.5 8.3 53.1 27.0 31.1 12.00 10.25 1.0 FPT 1.0 FPT 1.0 FPT 21-5/8 x 29 (top load) 0.6 21.9 1.3 28.5 7.0 Ultra 37-47 Uxxx Blower Opening A B Water Inlets Outlets Cond. Drain Filter Size* (Inches) C Other Dimensions E F G I *Note: Filter Rack extends 1-1/4” outward from the cabinet. Electrical Data (all HCAR-type circuit breaker per NEC) Ultra Forced Air Models (-UxOx) – (*HCAR-type circuit breaker per NEC) Model 170/171 270/271 370/371 470/471 Voltage Phase Frequency (Hz) 208/230-1, 60 277-1, 60 208/230-1, 60 208/230-3, 60 460-3, 60 277-1, 60 208/230-1, 60 208/230-3, 60 460-3, 60 208/230-1, 60 208/230-3, 60 460-3, 60 Compressor RLA 9.0 7.1 12.8 8.3 5.1 10.9 15.4 11.5 5.1 23.1 16.0 7.1 LRA 48 43 64 58 28 60 83 77 35 134 91 46 Blower HP 1/6 1/4 1/4 1/4 1/4 1/4 1/3 1/3 1/3 1/2 1/2 1/2 FLA 1.1 2.0 1.7 1.7 0.9 2.0 2.6 2.6 1.1 3.1 3.1 1.6 Without FlowCenter Total Min. Max FLA Amp. Fuse ---9.1 10.9 15 ---10.0 12.1 20 6.0 7.3 10 12.9 15.6 25 ---14.1 17.0 25 6.2 7.5 10 ---19.1 23.1 35 8.7 10.5 15 FlowCenter HP 1/6 -1/3 ---1/3 --1/3 --- FLA 1.8 -3.6 ---3.6 --3.6 --- Total FLA 11.9 -18.1 ---21.6 --29.8 --- With FlowCenter Min. Max Fuse/ Amp. Ckt Brk* 14.2 20 --21.3 30 ------25.5 40 ----35.6 55 ----- Total FLA 25.8 -33.5 -- With FlowCenter Min. Max Fuse/ Amp. Ckt Brk* 29.7 45 --39.3 60 --- Ultra Forced Air Models (-UxVx) – (*HCAR-type circuit breaker per NEC) Model 370/371 470/471 Voltage Phase Frequency (Hz) 208/230-1, 60 208/230-3, 60 208/230-1, 60 208/230-3, 60 Compressor RLA 15.4 11.5 23.1 16.0 LRA 83 77 134 91 Blower HP 3/4 3/4 3/4 3/4 FLA 6.8 6.8 6.8 6.8 Without FlowCenter Total Min. Max FLA Amp. Fuse ---18.3 21.2 30 ---22.8 26.8 40 FlowCenter HP 1/3 -1/3 -- FLA 3.6 -3.6 -- 18 XVIII. Correction Factors EV Entering Air Temperature ENTERING AIR TEMP 60oF DB 65oF DB 70oF DB 75oF DB/63oF WB 80oF DB/67oF WB 85oF DB/71oF WB HEATING BTU/hr KW 1.04 0.96 1.02 0.98 1.00 1.00 0.97 1.03 0.93 1.07 --- EV Airflow COOLING BTU/hr KW --0.70 0.73 0.79 0.83 0.90 0.92 1.00 1.00 1.05 1.04 NOMINAL CFM 80% 85% 90% 95% 100% 105% 110% HEATING BTU/hr KW 0.92 1.04 0.95 1.03 0.97 1.02 0.99 1.01 1.00 1.00 1.01 0.99 1.02 0.98 COOLING BTU/hr KW 0.96 0.97 0.97 0.98 0.98 0.98 0.99 0.99 1.00 1.00 1.01 1.01 1.02 1.02 Ground Side Flow Rates NOMINAL GPM 50% 55% 60% 65% 70% 80% 90% 100% 110% 120% 130% 140% 150% HEATING BTU/hr KW 0.90 0.97 0.91 0.97 0.92 0.98 0.93 0.98 0.94 0.98 0.96 0.99 0.98 0.99 1.00 1.00 1.02 1.00 1.04 1.00 1.06 1.01 1.07 1.01 1.08 1.02 COOLING BTU/hr KW 0.97 1.05 0.97 1.05 0.98 1.04 0.98 1.04 0.98 1.03 0.99 1.02 0.99 1.01 1.00 1.00 1.01 0.99 1.02 0.98 1.02 0.98 1.03 0.97 1.03 0.96 Water Coil Pressure Drop Ratings (Pure Water)* EV17 EH17 Flow GPM 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 20 22 24 26 28 30 32 34 EV27 EH27 EV37 EH37 EV38 EH38 EV47 EH47 EV48 EH48 EV57 EH57 EV58 EH58 EV67 EH67 EV68 EH68 GH87 GH110 3.8 4.6 5.3 6.1 7.0 9.0 10.2 - 2.3 2.8 3.3 3.8 4.3 4.9 5.6 6.3 7.0 - 2.3 2.8 3.3 3.8 4.3 4.9 5.6 6.3 7.0 - 0.8 0.9 1.0 1.2 1.5 1.7 2.0 2.3 2.6 2.9 3.3 0.8 0.9 1.0 1.2 1.5 1.7 2.0 2.3 2.6 2.9 3.3 dP PSIG 0.9 0.9 1.5 2.2 3.5 3.9 5.2 6.5 - 0.8 1.2 1.6 2.4 2.8 3.6 4.4 5.2 6.4 7.6 - 0.8 1.2 1.6 2.4 2.8 3.6 4.4 5.2 6.4 7.6 - 0.8 1.2 1.6 2.4 2.8 3.6 4.4 5.2 6.4 7.6 - 1.6 2.0 2.5 3.1 3.8 4.3 4.8 6.0 7.5 9.4 - 1.6 2.0 2.5 3.1 3.8 4.3 4.8 6.0 7.5 9.4 - 3.8 4.6 5.3 6.1 7.0 9.0 10.2 - 19 XIX. Wiring Diagram – Ultra Forced Air Models [E(V,H)17-67x-x-UxOx] BRN BRN Heat Pump Thermostat YEL Optional Slide-In Heater E R G O Y Aux L C PB Fan Motor X W2 E BLK BLU RED Blu RED BLK Wht B Brn B R R BF PB H BLU W2 E DO M Blower Capacitor BLK Equipment Ground L RED Y E W2 E R G O Y W2 L X 24V Transf PWR SP J1 R ORG 240V 208V RED F1 J2 Yel X 1-Phase Power Blu BLK BLK J3 X RB R ASC Blu X SA BLK Controller Blu RC O X PA Blu X LP/ FP DT M1 Grn G HP Yel M1 BLK Blu Org 10VA Maximum External Connected Load (24Vac) Blu R Blk Blk VR F2 FREEZE 1 STAT (Optional) 2 S C Blu 3 BLU RED HL Blu COMPRESSOR LP / FP HP Desuperheater Pump (Optional) Three Phase Factory Low Voltage Factory Line Voltage Field Line Voltage Field Low Voltage Ultra [(T,U)xOx] Heat Pump Electrical Diagram 80-0010, U ECN 13-129-N01 BF DO DT F1 F2 FP Block, Fan Speed Dry Contact Output Discharge Thermostat Fuse, Transformer Fuse, Desuperheater Freeze Protection HL HP LP M1 PA High-Temp Limit High-Press Switch Low-Press Switch Contactor Plug, Accessory PB RB RC SA Plug, Blower Relay, Blower Run Capacitor Start Assist (Some Single Phase Models) To PumpPAK (Optional) M1 B U B K SP VR J1 J2 J3 Spare Fuse Valve, Reversing Remove for Hydronic Ties W2 to E Overflow Protection R D L2 L1 L3 COMPRESSOR 20 Wiring Diagram – Ultra Forced Air Models [E(V,H)37-67x-x-UxVx] 9GRN DC Blower Motor Heat Pump Thermostat Optional E R G O Y Aux L C Slide-In Heater 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 X W2 E 1 2 3 4 5 3GRN 2RED 12WHT/ BLU 4RED 5WHT/BLU Brn 10ORG Wht 3WHT/RED 2GRN/RED Blu 1BLK Equipment Ground 6GRN/BLU 8BLK 10WHT W2 E DO R A B C D A B C D A B C D LOW Y E W2 Adjust HIGH MED 1-Phase Power - + E R G O Y W2 L X 24V Transf PWR SP J1 Yel X Blu ORN 240V 208V RED F1 J2 R BLK J3 X ASC 11BLU Red R X SA Blu Controller RC O X PA Blu X LP/ FP DT HP M1 G Grn M1 Yel BLK Blu Org 10VA Maximum External Connected Load (24Vac) Blu FREEZE STAT (Optional) Blk R Blk VR Blu 2 S C HP Blu LP / FP Ultra (UxVx) Heat Pump Electrical Diagram 80-0053, F ECN 13-129-N01 F2 HL 3 1 BLU RED COMPRESSOR Desuperheater Pump (Optional) Factory Low Voltage Factory Line Voltage Field Line Voltage Field Low Voltage To FlowCenter (Optional) Three Phase M1 DO DT F1 F2 FP HL HP LP M1 Dry Contact Output Discharge Thermostat Fuse, Transformer Fuse, Desuperheater Freeze Protection High-Temp Limit High-Press Switch Low-Press Switch Contactor PA Plug, Accessory RC Run Capacitor SA Start Assist (Some Single Ph Models) SP Spare Fuse VR Valve, Reversing J1 Remove for Hydronic J2 Ties W2 to E J3 Overflow Protection BLOWER SPEEDS A = 67 or 77 Series B = 57 Series C = 47 Series D = 37 Series + = Incr CFM 10% - = Decr CFM 10% BLOWER MOTOR CONTROL WIRES 1 – 11BLU (X) 11 – 5WHT/BLU (Hi) 2 – 10WHT (W2) 12 – 4RED (R) 3 – 12WHT/BLU (X) 13 – 8BLK (E) 4 – 2GRN/RED (Md) 14 – 6GRN/BLU (Y) 5 – 3WHT/RED (Lo) 15 – 9GRN (G) 7 – 10ORG (+ / -) B U B K R D L2 L1 L3 COMPRESSOR 21 XX. TROUBLESHOOTING GUIDE FOR LOCKOUT CONDITIONS If the heat pump goes into lockout on a high or low pressure switch, the cause of the lockout can be narrowed down by knowing the operating mode and which pressure switch the unit locked out on. The following table will help track down the problem once this information is known. Note- A lockout condition is a result of the heat pump shutting itself off to protect itself, never bypass the lockout circuit. Serious damage can be caused by the system operating without lockout protection. CONDITION AC power applied AC power applied AC power applied Run cycle complete INDICATOR LIGHTS COMMENTS PWR ASC LP HP Off Off Off Off Blown fuse or power removed or loose fuse clips. X X ASC indicator on for 4' 35" on power initialization. X Power applied - unit running or waiting for a call to run. X X LOW PRESSURE INDICATOR Heating or Cooling – X X before Y call X X Heating - during Y call X Cooling - during Y call X 22 Flash -Check if Low Pressure switch is open. -Check electrical connections between Low Pressure switch and Controller. -Loss/lack of flow through ground-side heat exchanger. -Low fluid temperature operation in ground-side heat exchanger. -Freezing fluid in ground-side heat exchanger (lack of antifreeze). -Dirty (fouled) ground-side heat exchanger (on ground water systems). -Low ambient temperature at the heat pump. -Undercharged / overcharged refrigerant circuit. -Expansion valve / sensing bulb malfunction. -Excessive low return air temperature. -Freezing air coil (dirty air filter or air coil, undercharged refrigerant circuit) -Missing blower compartment access panel. -Loss/lack of airflow (dirty filter, closed vents, blower, restricted ductwork, etc.) -Low return air temperature. -Low ambient temperature at the heat pump. -Undercharged / overcharged refrigerant circuit. -Expansion valve / sensing bulb malfunction. -Excessively low fluid temperature in the ground side heat exchanger. X Cycle Blink On and Off every few min. HIGH PRESSURE INDICATOR Heating or Cooling – X before Y call X X Heating - during Y call Cooling – during Y call ASC indicator ON for 70 to 130 seconds after compressor shutdown. X X X X -Check if High Pressure switch is open. -Check electrical connections between High Pressure switch and Controller. -Missing blower compartment access panel. -Loss/lack of airflow (dirty filter, closed vents, blower, restricted ductwork, etc.) -High return air temperatures. -Overcharged refrigerant circuit. -Expansion valve / sensing bulb malfunction. -Dirty (fouled) air coil. -Loss/lack of flow through the ground-side heat exchanger. -High fluid temperature in the ground-side heat exchanger. -Dirty (fouled) ground-side heat exchanger (on ground water systems). -Overcharged refrigerant circuit. -Expansion valve / sensing bulb malfunction. XXI. TROUBLESHOOTING GUIDE FOR UNIT OPERATION PROBLEM POSSIBLE CAUSE Blown Fuse/Tripped Circuit Breaker Blown Fuse on Controller Broken or Loose Wires Voltage Supply Low Low Voltage Circuit Entire unit does not run Room Thermostat Unit will not operate on “heating” Evaporator (air coil) ices over in cooling mode Blower motor runs but compressor does not, or compressor short cycles Unit short cycles CHECKS AND CORRECTIONS Replace fuse or reset circuit breaker. (Check for correct size fuse or circuit breaker.) Replace fuse on controller. (Check for correct size fuse.) Check for loose fuse clips. Replace or tighten the wires. If voltage is below minimum voltage on data plate, contact local power company. Check 24-volt transformer and fuse for burnout or voltage less than 18 volts. Set thermostat on “Cool” and lowest temperature setting, unit should run. Set thermostat on “Heat” and highest temperature setting, unit should run. If unit does not run in both cases, the room thermostat could be faulty or incorrectly wired. To prove faulty or miswired thermostat, disconnect thermostat wires at the unit and jumper between “R”, “Y” and “G” terminals and unit should run. Replace thermostat only with correct heat pump thermostat. A substitute may not work properly. Interruptible Power Check incoming supply voltage. Dirty Filter Check filter. Clean or replace if found dirty. Thermostat Improperly Set Is it below room temperature? Check the thermostat setting. Defective Thermostat Check thermostat operation. Replace if found defective. Incorrect Wiring Check for broken, loose, or incorrect wires. Blower Motor Defective If it does not operate the compressor will go off on high head pressure. Dirty Air Filter or Air Coil Check filter. Clean or replace if found dirty. Clean air coil if found dirty. Airflow Lack of adequate airflow or improper distribution of air. Check the motor speed and duct sizing. Check the filter, it should be inspected every month and changed if dirty. Check for closed registers. Remove or add resistance accordingly. Blower Speed Set too Low Verify blower speed jumpers are in factory settings. Low Air Temperature Room temperatures below 65oF may ice over the evaporator. Room Thermostat Check setting, calibration, and wiring. Wiring Check for loose or broken wires at compressor, capacitor, or contactor. Blown Fuse Replace fuse or reset circuit breaker. (Check for correct size fuse or circuit breaker.) High or Low Pressure Controls The unit could be off on the high or low-pressure cutout control. Check water GPM, air CFM and filter, ambient temperature and loss of refrigerant. If the unit still fails to run, check for faulty pressure controls individually. Replace if defective. Voltage Supply Low If voltage is below minimum voltage specified on the data plate, contact local power company. Check voltage at compressor for possible open terminal. Low Voltage Circuit Check transformer and fuse for burn out or voltage less that 18 volts. With a voltmeter, check signal from thermostat at Y to X, M1 on controller to X, check for 24 volts across the compressor contactor. Replace component that does not energize. Compressor Overload Open In all cases an “internal” compressor overload is used. If the compressor motor is too hot, the overload will not reset until the compressor cools down. Compressor Motor Shorted to Internal winding grounded to the compressor shell. Replace the compressor. If Ground compressor burnout, replace inline filter drier. Compressor Windings Open Check continuity of the compressor windings with an ohmmeter. If the windings are open, replace the compressor. Seized Compressor Try an auxiliary capacitor in parallel with the run capacitor momentarily. If the compressor still does not start, replace it. Room Thermostat Improperly located thermostat (e.g. near kitchen, inaccurately sensing the comfort level in living areas). Verify Install Set-up configuration. Wiring and Controls Loose wiring connections, or control contactor defective. Compressor Overload Defective compressor overload, check and replace if necessary. If the compressor runs too hot, it may be due to insufficient refrigerant charge. PROBLEM POSSIBLE CAUSE CHECKS AND CORRECTIONS Unit does not Reversing Valve does not Shift Defective solenoid valve will not energize. Replace solenoid coil. cool (Heats Only) Room Thermostat Ensure that it is properly configured according to their own instructions for the “System Type” they are installed on. Reversing Valve does not The solenoid valve is de-energized due to miswiring at the unit or thermostat - correct Shift, the Valve is Stuck wiring. Replace if valve is tight or frozen and will not move. Switch from heating to cooling a few times to loosen valve. 23 Insufficient cooling or heating Water Lack of sufficient pressure, temperature and/or quantity of water. Unit Undersized Recalculate heat gains or losses for space to be conditioned. If excessive, rectify by adding insulation, shading, etc. Check for leaks in ductwork or introduction of ambient air through doors/windows Loss of Conditioned Air by Leaks Room Thermostat Water drips from unit Noisy Operation 24 Improperly located thermostat (e.g. near kitchen, not sensing the comfort level in living areas). Verify Install Set-up configuration. Airflow Lack of adequate airflow or improper distribution of air. Check the motor speed and duct sizing. Check the filter, it should be inspected every month and cleaned if dirty. Remove or add resistance accordingly. Refrigerant Charge Low on refrigerant charge causing inefficient operation. Adjust only after checking CFM,GPM, and inlet/outlet temperatures. Compressor Check for defective compressor. If discharge pressure is too low and suction pressure is too high, compressor is not pumping properly. Replace compressor. Desuperheater The desuperheater circuit (in-line fuse) should be disconnected during cold weather to allow full heating load to the house. Reversing Valve Defective reversing valve creating bypass of refrigerant from discharge to suction side of compressor. When it is necessary to replace the reversing valve, wrap it with a wet cloth and direct the heat away. Excessive heat can damage the valve. Unit not Level Level vertical units. Condensate Drain Line Kinked Clean condensate drain. Make sure external condensate drain is installed with adequate or Plugged drop and pitch. Compressor Make sure the compressor is not in direct contact with the base or sides of the cabinet. Cold surroundings can cause liquid slugging, increase ambient temperature. Blower and Blower Motor Blower wheel hitting the casing, adjust for clearance and alignment. Bent blower, check and replace if damaged. Loose blower wheel on shaft, check and tighten. Contactor A “clattering” or “humming” noise in the contactor could be due to control voltage less than 18 volts. Check for low supply voltage, low transformer output, or transformer tap setting. If the contactor contacts are pitted or corroded or coil is defective, repair or replace. Rattles and Vibrations Check for loose screws, panels, or internal components. Tighten and secure. Copper piping could be hitting the metal surfaces. Carefully readjust by bending slightly. Check that hard plumbing is isolated from building structures. Water and Airborne Noises Undersized ductwork will cause high airflow velocities and noisy operation. Excessive water through the water-cooled heat exchanger will cause a squealing sound. Check the water flow, ensuring adequate flow for good operation but eliminating the noise. Cavitating Pumps Purge air from ground loop system. Squealing Sound from Inside Purge air from the water side of the desuperheater heat exchanger or defective the Cabinet desuperheater heat exchanger. XXII. TROUBLESHOOTING GUIDE FOR ECM BLOWER PROBLEM Motor rocks slightly when starting Motor won’t start •No movement CHECKS AND CORRECTIONS •This is normal start-up for ECM. •Wait for completion of ramp-up at start. •Check power at motor. •Check low voltage (24 VAC R to X) at motor. •Check low voltage connections (G, Y, W2, R, X) at motor. •Check for unseated pins in connectors on motor harness. •Test with a temporary jumper between R and G. •Check motor for a tight shaft. •Perform Moisture Check*. Motor rocks, but won’t start •Check for loose or compliant motor mount. •Make sure blower wheel is tight on shaft. Motor starts, but runs erratically •Varies up and down or intermittent •Is ductwork attached? •Check line voltage for variation or “sag.” •Check low voltage connections (G, Y, W2, R, X) at motor, unseated pins in motor harness connectors. •Check out system controls, thermostat. •Perform Moisture Check*. ”Hunts” or “puffs” at high CFM (speed) •Does removing panel or filter reduce puffing? Reduce restriction. Stays at low CFM despite call for higher speed •Check low voltage wires and connections. •Verify fan is not in delay mode; wait until delay complete. •”R” missing/not connected at motor. Stays at high CFM •Verify fan is not in delay mode; wait until delay complete. •”R” missing/not connected at motor. Blower won’t change CFM after adjusting the speed control setting. Blower won’t shut off •Power to the unit must be reset to enable the new settings. •Verify fan is not in delay mode; wait until delay complete. •”R” missing/not connected at motor. Excessive noise •Determine if it’s air noise, cabinet, duct or motor noise. Air noise •High static creating high blower speed? - Does removing filter cause blower to slow down? Check filter. - Use low-pressure drop filter. Check/correct duct restrictions. Noisy blower or cabinet •Check for loose blower housing, panels, etc. •High static creating high blower speed? - Check for air whistling through seams in ducts, cabinets, or panels. Check for cabinet/duct deformation. •Current leakage from controls into G, Y, or W? *Moisture Check •Connectors are oriented as recommended by equipment manufacturer? •Is condensate drain plugged? •Check for low airflow (too much latent capacity) •Check for undercharged conditions. •Check and plug leaks in return ducts, cabinet. **Comfort Check •Check proper airflow settings. •Low static pressure for low noise. •Set low continuous-fan CFM. •Thermostat in good location? 25 XXIII. ADDITIONAL FIGURES Figure 2 – Electrical Diagram for optional ECONAR Intelligent Slide-In-Heater IN Pressure/Temperature (P/T) Ports Out PumpPAK To/From Closed Loop Figure 3 – Ground Loop Water Plumbing From Bladder-Type Pressure Tank Shutoff Valves Boiler Drains Strainer IN Visual Flow Meter Solenoid Valve Flow Control Valve Out Pressure/Temperature (P/T) Ports Discharge Figure 4 – Ground Water Plumbing 26 COLD HOT 1/2" or 3/4" Copper Pipe Air Vent 1/2" Copper Pipe Desuperheater Tee Shutoff Valves Drain (Hang Down) Note – Always use copper pipe. Check local codes and use proper plumbing procedures. Figure 5 – Preferred Desuperheater Installation COLD Check Valve HOT 1/2" or 3/4" Copper Pipe Air Vent Drain (Hang Down) 1/2" Copper Pipe Shutoff Valves Note – Always use copper pipe. Check local codes and use proper plumbing procedures. Figure 6 – Alternate Desuperheater Installation 27 WARRANTY AND FORMS SINGLE FAMILY OWNER OCCUPIED WARRANTY CERTIFICATE Enertech Global, LLC., for brands: “ECONAR” and “GeoSource” Residential Single Family, Owner Occupied 5-YEAR LIMITED WARRANTY STARTING JANUARY 01, 2013 Enertech Global, LLC. warrants all internal system components, including but not limited to the compressor, coaxial exchanger, air coil, contactor, circuit boards, capacitor, wiring harnesses, blower assembly, expansion valve and reversing valve, to be free from defects in material and workmanship for a period of five (5) year from the date of delivery to the original purchaser- user. Enertech Global, LLC. warrants its geothermal unit against defect in materials and workmanship for FIVE (5) year from the date of delivery to the original purchaser-user. CONDITIONS AND EXCLUSIONS: The Limited Warranty only applies if the following conditions are met: A. This Limited Warranty will not apply and shall be null and void if the Enertech Global, LLC. serial number has been altered, defaced or removed. B. This Limited Warranty shall be null and void if the Enertech Global, LLC. unit has been disconnected or removed from the location of original installation, or if dealer-seller has not been paid in full for the unit. C. This Limited Warranty shall not apply to unit failure or defect caused by improper installation, field modification, improper voltage, improper maintenance or misuse including operation during building construction, corrosion caused by airborne contaminants, chlorine or salt air exposure, corrosive liquids or water, abuse, neglect, Act of God, outdoor installation, damage from abuse, accident, fire, flood and the like, or to defects or damage caused by the use of any attachment, accessory or component not authorized by Enertech Global, LLC. D. Replacement or repaired parts and components are warranted only for the remainder of the original warranty period, as stated above. E. This Limited Warranty applies only to Enertech Global, LLC. commercial and/or muti-family use (i.e. non-residential-single-family) units sold and installed by a trained, independent, contractor-customer of Enertech Global, LLC., or an authorized representative and/or distributor, in the United States or Canada, and subjected to normal usage as described and rated on the applicable descriptive sheet for such unit. This warranty shall not be valid if equipment is not installed in accordance with methods prescribed in our data and technical manuals and in compliance with local codes. Improper installation may endanger the occupants of the dwelling. Contractor-customer must complete the warranty registration card supplied with the Enertech Global, LLC. unit, which must then be endorsed by original purchaser-user and mailed within ten (10) days after initial installation. If warranty card is not returned, warranty shall commence at date unit was shipped from Enertech Global, LLC. F. The obligation for Enertech Global, LLC. under this Limited Warranty is expressly limited to replacement of any parts or components as specified and found within the cabinet. Enertech Global, LLC. reserves the right to replace defective components under warranty with new or reconditioned parts. This warranty does not cover any labor expenses for service, nor for removing or reinstalling parts. Accessory, peripheral and ancillary parts and equipment or not covered by this warranty. G. Enertech Global, LLC. does not warrant equipment which has been custom built or modified to purchaser-user specifications. Likewise, any field modification of any equipment shall also void this, and any and all warranties. H. Regular maintenance such as filter changes, drain pan cleaning, loop flushing/pressurization, and other monthly/annual maintenance is not covered. I. All warranty claim items must be held for 90 days at customer location and returned to Enertech freight prepaid upon issuance of RMA by Warranty Administration. Notice: Outdoor or unconditioned space installation of any equipment other than units intended for outdoor installation shall cause this and all warranties to be deemed void. SHIPPING COSTS: The purchaser-user will be responsible for the cost of shipping warranty replacement parts from the Enertech Global, LLC. factory to the distributor of the parts. Purchaser-user is also responsible for any shipping cost of returning the failed part to the distributor. THE FOREGOING LIMITED WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES (AND IMPLIED CONDITIONS IN cANADA), EXPRESSED, IMPLIED AND STATUTORY, INCLUDING, WITHOUT LIMITATION, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, AND ALL SUCH WARRANTIES, EXPRESSED OR IMPLIED, ARE EXCLUDED AND SHALL NOT APPLY TO THE GOODS SOLD. IN NO EVENT SHALL WARRANTOR BE LIABLE FOR DIRECT, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES RESULTING FROM ANY DEFECT IN THE GOODS EXCEPT TO THE EXTENT SET FORTH HEREIN. (Some states do not allow exclusion or limitation of implied warranties or liability for incidental or consequential damage). For additional information or assistance, contact the WARRANTOR, which is: Enertech Global, LLC., 2506 South Elm Street, Greenville, IL 62246 Page 1 of 1 Greenville, IL & Mitchell, SD [email protected] www.gogogeo.com 90-1201 Rev D (2013-007) | 2012 Enertech Global, LLC. | All Rights Reserved