Installation manual Mixing module HHM

Transcription

Installation manual Mixing module HHM
Installation manual
Mixing module
6 720 615 683-00.1I
Mixing module HHM
For the installer
6 720 640 430 (2009/12) en
Read carefully before commissioning
Table of Contents
Table of Contents
1
Explanation of symbols and safety information 3
1.1
Explanation of symbols . . . . . . . . . . . . . . . 3
1.2
Safety precautions . . . . . . . . . . . . . . . . . . 3
2
Included in the delivery . . . . . . . . . . . . . . . . . . . 4
2.1
Included in the delivery . . . . . . . . . . . . . . . 4
2.2
Not included in delivery . . . . . . . . . . . . . . 4
3
Mixing module . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
5
Technical information . . . . . . . . . . . . . . . . . . . . . 7
5.1
System solutions . . . . . . . . . . . . . . . . . . . . 7
5.2
Technical information . . . . . . . . . . . . . . . 12
6
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1
CAN-BUS . . . . . . . . . . . . . . . . . . . . . . . . .
6.2
Handling circuit boards . . . . . . . . . . . . . .
6.3
Address selection . . . . . . . . . . . . . . . . . .
6.4
Assembly . . . . . . . . . . . . . . . . . . . . . . . . .
7
Electrical connections . . . . . . . . . . . . . . . . . . . 16
7.1
Wiring diagram, mixing module . . . . . . . . 16
7.2
Mixing module . . . . . . . . . . . . . . . . . . . . . 18
7.3
XB2 settings . . . . . . . . . . . . . . . . . . . . . . 19
7.4
Connection for heat pump and mixing
modules . . . . . . . . . . . . . . . . . . . . . . . . . . 20
8
Pool (accessory) . . . . . . . . . . . . . . . . . . . . . . . . 22
8.1
Diagnostics/monitoring . . . . . . . . . . . . . . 24
9
Pool function, mixed circuit . . . . . . . . . . . . . . . 26
13
13
14
15
15
10 Factory values . . . . . . . . . . . . . . . . . . . . . . . . . . 27
10.1 Pool (accessory) . . . . . . . . . . . . . . . . . . . 27
10.2 Pool function, mixed circuit . . . . . . . . . . 28
2
Mixing module HHM - Subject to change without notice
Explanation of symbols and safety information
1
Explanation of symbols and safety information
1.1
Explanation of symbols
Warning symbols
Safety instructions in this document are
framed and identified by a warning triangle
which is printed on a grey background.
Electrical hazards are identified by a lightning
symbol surrounded by a warning triangle.
Signal words indicate the seriousness of the hazard in
terms of the consequences of not following the safety
instructions.
• NOTICE indicates possible damage to property or
equipment, but where there is no risk of injury.
• CAUTION indicates possible injury.
• WARNING indicates possible severe injury.
• DANGER indicates possible risk to life.
1.2
1
Safety precautions
General
B Read the guide carefully and keep it to hand for future
use.
Installation and commissioning
B Installation and start-up may only be carried out by a
qualified installer.
Service and maintenance
B Only qualified personnel may carry out repairs. Incorrect repairs can lead to serious risks to the user, and a
reduction in savings.
B Only use original spare parts.
B Service and maintenance must be carried out annually
by an authorised service representative.
Important information
Notes contain important information in cases
where there is no risk of personal injury or
material losses and are identified by the symbol shown on the left. They are bordered by
horizontal lines above and below the text.
Additional symbols
Symbol
Meaning
B
a step in an action sequence
Æ
a reference to a related part in the document or to other related documents
•
a list entry
–
a list entry (second level)
Tab. 1
Mixing module HHM - Subject to change without notice
3
2
Included in the delivery
2
Included in the delivery
2.1
Included in the delivery
Mixing module
Installation manual
2.2
Not included in delivery
CAN-BUS cable
Sensor
Mixing valve
Circulation pump
Room temperature sensor
4
Mixing module HHM - Subject to change without notice
Mixing module
3
3
Mixing module
The mixing module has been designed for operation connected to Buderus heat pumps in conjunction with the
HMC 10 control unit; Logatherm WPS 22...60. It has an
XB2 board which is used to control an additional mixed
circuit.
A maximum of three mixing modules can be used per heat
pump with the Logatherm WPS 22...60. PKSET does not
count as a mixed additional circuit. This means that three
mixing modules can be used if PKSET is used.
Units that are connected to a mixing module are displayed
and can also be adjusted at the control panel for the heat
pump.The mixing module can also be used to control a
pool with the Logatherm WPS 22...60. If a mixing module
is used for controlling a pool, only two mixing modules can
be used to control additional circuits.
The mixing valve is closed completely once a day for 3-5
minutes to calibrate the function. No heat is supplied to
the heating circuits for this time.
When an air handling unit (Program Version 2.0) is
installed in the circuit, a different calibration method is
used to prevent freezing of the heating battery.
The settings for circuit 3-4 are described under Settings in the Logatherm WPS installation manual.
The settings for the cooling system are described under Settings in the PKSET installation instructions.
In addition to the mixing module, an additional mixed circuit must also be equipped with a mixing valve, circulation
pump, flow temperature sensor and possibly a room temperature sensor.
Circuit 1 must always be installed and used.
The task of the heat pump is to keep circuit 1
at the correct temperature in accordance
with the heat curve. The flow temperature in
circuit 2-4 cannot be higher than the value of
circuit 1. This means that an underfloor heating system in circuit 1 cannot be combined
with radiators in another circuit.
Under certain conditions, a room temperature reduction in circuit 1 may affect the other
circuits.
When the Use temperature from circuit
with highest temperature function under
Circuit 1 is used, the heat curve for Circuit
1 does not need to be adapted to the mixed
circuits. The heat pump automatically selects
the highest flow temperature set point value.
The mixing valve is controlled via PID regulation in order
to achieve the required flow temperatures. To allow the
mixing valve control system to operate properly, it is crucial to set the correct mixing valve running time in the
menu for the relevant heating circuit. The mixing valve running time is normally specified on the mixing valve. For
more information, refer to Settings in the installation manual for the heat pump.
Mixing module HHM - Subject to change without notice
5
4
4
Dimensions
Dimensions
6 720 615 683-14.1I
Fig. 1
Height and width in mm.
6 720 615 683-16.1I
Fig. 2
Depth in mm.
6 720 615 683-15.1I
Fig. 3
6
Connection dimensions in mm.
Mixing module HHM - Subject to change without notice
Technical information
5
Technical information
5.1
System solutions
5.1.1
System solution explanations
E10
E10.T2
Outdoor temperature sensor
Tab. 2
E11
E11.C101
E11.C111
E11.F101
E11.F111
E11.G1
E11.P101
E11.P111
E11.P112
E11.Q101
E11.Q102
E11.R101
E11.T1
E11.TT
Expansion vessel
Buffer tank
Safety valve
Ventilation (automatic)
Heating system pump
Pressure gauge
Thermometer
Thermometer
Shut-off valve
Shut-off valve
Non-return valve
Flow temperature sensor
Room temperature sensor
Tab. 3
E12
E12.G1
E12.P112
E12.Q101
E12.Q102
E12.Q11
E12.R101
E12.T1
E12.TT
Heating system pump
Thermometer
Shut-off valve
Shut-off valve
Mixing valve
Non-return valve
Flow temperature sensor
Room temperature sensor
Tab. 4
E13
E13.G1
E13.P112
E13.Q101
E13.Q102
E13.Q11
E13.R101
E13.T1
E13.TT
Heating system pump
Thermometer
Shut-off valve
Shut-off valve
Mixing valve
Non-return valve
Flow temperature sensor
Room temperature sensor
Tab. 5
E14
E14.E14
E14.G1
E14.P112
E14.Q101
E14.Q102
E14.Q11
E14.R101
E14.T1
E14.TT
E14.V101
5
Heat exchanger
Heating system pump
Thermometer
Shut-off valve
Shut-off valve
Mixing valve
Non-return valve
Flow temperature sensor
Room temperature sensor
Non-return valve
Tab. 6
E21
E21
E21.F111
E21.G2
E21.G3
E21.Q102
E21.Q21
E21.R101
E21.R102
E21.T8
E21.T9
E21.T10
E21.T11
E21.V102
Heat pump
Ventilation (automatic)
Heat carrier pump
Collector circuit pump
Shut-off valve
Three-way valve
Non-return valve
Non-return valve
Heat transfer fluid out
Heat transfer fluid in
Collector circuit in
Collector circuit out
Filter
Tab. 7
E22
E22
E22.F101
E22.G2
E22.G3
E22.Q101
E22.R101
E22.R102
E22.T8
E22.T9
E22.T10
E22.T11
E22.V101
Heat pump
Safety valve
Heat carrier pump
Collector circuit pump
Shut-off valve
Non-return valve
Non-return valve
Heat transfer fluid out
Heat transfer fluid in
Collector circuit in
Collector circuit out
Filter
Tab. 8
Mixing module HHM - Subject to change without notice
7
5
Technical information
E31
E31
E31.C101
E31.F101
E31.F111
E31.F102
E31.Q21
E31.Q22
E31.Q23
E31.Q24
E31.V101
Collector circuit compressor 1
Expansion vessel
Safety valve
Ventilation (automatic)
Safety valve
Ball valve, filling unit
Ball valve, filling unit
Shut-off valve
Shut-off valve
Filter
Tab. 9
E41
E41
E41.E1
E41.F101
E41.F102
E41.G6
E41.P111
E41.P112
E41.Q101
E41.Q104
E41.Q105
E41.Q106
E41.Q111
E41.R101
E41.R102
E41.T3
E41.V41
E41.W41
Hot water cylinder
Hot water electric heater
Safety valve
Safety valve
Circulation pump hot water
Thermometer
Thermometer
Shut-off valve
Shut-off valve
Shut-off valve
Shut-off valve
Balancing valve
Non-return valve
Non-return valve
Hot water sensor
Hot water
Cold water
Tab. 10
E81
E81.E81
E81.G1
E81.Q81
E81.T82
E81.V101
Pool heat exchanger
Pool pump
Pool mixing valve
Pool sensor
Filter
Tab. 11 E81
8
Mixing module HHM - Subject to change without notice
Technical information
5.1.2
5
Logatherm WPS 22...60 with additional circuits
6 720 616 846-01.1I
Fig. 4
Monovalent unmixed and mixed heating circuit with buffer tank and two mixing modules each with one circuit.
Circuits E11 and E12 are controlled by the heat pump.
Circuits E13 and E14 are controlled by the relevant mixing module. The selectable room temperature sensors
E11.TT and E12.TT are connected to the heat pump.
E13.TT and E14.TT are connected to the respective mixing module.
Mixing module HHM - Subject to change without notice
9
5
Technical information
Logatherm WPS 22...60 with pool
Fig. 5
Monoenergetic unmixed heating circuit with pool.
6 720 617 644-04.1I
5.1.3
10
Mixing module HHM - Subject to change without notice
Technical information
5.1.4
5
Logatherm WPS 22...60 with pool (mixed circuit)
6 720 617 644-06.1I
Fig. 6
Mixed heating circuit with pool.
Mixing module HHM - Subject to change without notice
11
5
Technical information
5.2
Technical information
5.2.1
Mixing module
Values for electrical connection
Unit
Electrical connections
V WS/Hz
230 V/1-50 Hz
Degree of protection
IP
X1
Dimensions (Width x Depth x Height)
mm
255 x 180 x 77
Weight
kg
1.5
General Information
Tab. 12
12
Mixing module HHM - Subject to change without notice
Installation
6
Installation
6.1
CAN-BUS
The various circuit boards in the heat pump are joined by
a communications cable, CAN-BUS. CAN (Controller
Area Network) is a two-wire system for communication
between microprocessor based modules/circuit boards.
CAUTION: Interference.
B The CAN-BUS cable must be screened
and laid separately from the power cable.
Suitable cable for external laying is cable LIYCY (TP)
2x2x0.5. The cable must be twisted pair and screened.
The screen must only be earthed at one end and to the
chassis.
Maximum cable length is 30 m.
CAN-BUS cable must not be laid alongside power supply cables. Minimum distance 100 mm. They may be laid
alongside sensor cables.
CAN-BUS
6
CAUTION: Do not mix up the 12V and CANBUS connections!
The processors are destroyed if 12V is connected to the CAN-BUS.
B Check that the four cables are connected
to the contacts with the corresponding
marking on the circuit board.
The connection between the circuit boards is by four
wires, because the 12V-supply between the circuit
boards must also be connected. The circuit boards have
markings for both the 12V and CAN-BUS connections.
Switch Term is used to mark the start and end of a CANBUS loop. Ensure that the correct circuit board is terminated and that all other switches are in the opposite position.
CAN-BUS
6 720 614 967-31.2I
Fig. 7
GND
CANL
CANH
+12V
EWP
Earth
CAN low
CAN high
Connection 12V
Heat pump
Mixing module HHM - Subject to change without notice
13
6
6.2
Installation
Handling circuit boards
Circuit boards with control electronics are sensitive to
discharges of static electricity (ESD – ElectroStatic Discharge) when handled. To prevent damaging the components, special care is therefore required when handled.
CAUTION: Never grasp a circuit board without wearing a ground-connected bracelet.
A condition for good ESD protection is a ground-connected bracelet when handling electronics. This bracelet
must be put on before opening the screened metal bag/
packaging or before exposing an installed board. The
bracelet must be worn until the circuit board is enclosed
in its screen packaging or closed electric box. Replaced,
returned circuit boards must be handled in the same way.
6 720 614 366-24.1I
Fig. 8
Bracelet
Damage is usually latent, and a circuit board can operate
impeccably during commissioning but show signs of
problems later. Charged objects may only be problematic
if they are in close proximity to the electronics. Keep a distance of at least one metre from expanded polystyrene,
protective plastic and other packaging, synthetic material
(e.g. fleeces) and similar before starting work.
14
6 720 614 366-25.1I
Fig. 9
Mixing module HHM - Subject to change without notice
Installation
6.3
Address selection
6.3.1
Circuit 3-4
6.4
6
Assembly
6 720 615 683-22.1I
Fig. 12
6 720 615 683-17.1I
Fig. 10 Address selection, circuit 3-4.
B Select the correct address and program for the mixing
module (XB2 board). The address selection of additional mixed circuit 1 must be set to 1 (circuit E13) and
the address selection of additional mixed circuit 2 must
be set to 2 (circuit E14). If more mixing modules are
added, make sure that with each additional module
switch A is numbered consecutively in accordance
with the heating circuits. The program selection for the
additional mixed circuit 1 and 2 must be set to 0.
The settings for the cooling system are described in the PKSET installation manual.
6.3.2
B Fasten the mixing module to the wall near the heat
pump. Mount the unit at the four corners with screws.
B Establish the electrical connections once the unit has
been fastened to the wall.
B Screw down the cover of the mixing module on the unit.
6.4.1
Room sensor T5 (accessory)
It is only the room where the room sensor is
located that can influence regulation of the
temperature for the relevant heating circuit.
Installation location requirements:
• If possible, interior wall without drafts or heat radiation.
• Unimpeded circulation of room air under room sensor
T5 (dotted area in figure 13 must be kept clear).
Pool
0,3 m
0,6 m
1,2 - 1,5 m
T5
0,3 m
6 720 615 683-18.1I
6 720 614 366-34.1I
Fig. 11 Address selection, pool.
B Select correct program and address at XB2 board. The
address selection and program selection for the pool
control system must be set to 0 and 1 respectively.
Mixing module HHM - Subject to change without notice
Fig. 13 Recommended installation location for room
sensor T5
15
7
Electrical connections
7
Electrical connections
7.1
Wiring diagram, mixing module
6 720 619 226-05.1I
Fig. 14 Wiring diagram, circuit 3-4
E1x.Q11
E1x.G1
E1x.T1
E1x.TT.T5
E1x.TT.P1
E1x.B11
E1x.F51
E1x.F52
Continuous line = always connected. Dotted line = accessory, optional:
x = 3, 4
1
If circuit board XB2 is the last board in the CAN-BUS loop,
Mixing valve, 230 V / 0-10 V
the switch must be in the TERM position.
Circulation pump
2
The switch must be in the 0 position.
Flow temperature sensor
3
The switch must be in the 0 position.
Room temperature sensor
4
Program selection (Æ Fig. 10)
Room temperature sensor LED
5
Address selection (Æ Fig. 10)
External input
Cables:
Fuse 6.3 A
Fuse 250 mA
Terminal L, N, PE
Input voltage
Min. 1.5 mm²
Terminal 51-58
Connections 230 V
Min. 0.75 mm²
Terminal 1-11
Sensor connections
Min. 0.5 mm²
Terminal 31-38
CAN-BUS
(Æ Chapter 6.1)
Tab. 13
16
Mixing module HHM - Subject to change without notice
7
6 720 615 683-03.2I
Electrical connections
Fig. 15 Wiring diagram, pool
1
2
3
4
5
E81.Q81
E81.T1
E81.T82
E81.B11
Continuous line = always connected. Dotted line = accessory, optional:
If circuit board XB2 is the last board in the CANE81.G1.F21 Alarm, pool pump
BUS loop, the switch must be in the Term posiE81.F51
Fuse 6.3 A
tion.
E81.F52
Fuse 250 mA
Switch must be in position 0.
Cables:
Switch must be in position 0.
Program selection (Æ Fig. 11)
Terminal L, N, PE
Input voltage
Address selection (Æ Fig. 11)
Terminal
51-58
Connections 230 V
Mixing valve, 230 V / 0-10 V
Terminal
1-11
Sensor
connections
Flow temperature sensor
Terminal
31-38
CAN-BUS
Pool sensor
External input
Tab. 14
Mixing module HHM - Subject to change without notice
Min. 1.5 mm²
Min. 0.75 mm²
Min. 0.5 mm²
(Æ Chapter 6.1)
17
7
7.2
Electrical connections
Mixing module
6 720 615 683-01.1I
Fig. 16 Mixing module XB2
1
2
3
4
5
6
7
8
9
10
18
Termination switch
Switch, emergency operation function (not used)
Switch 12 V, internal/external
Program selection (assignment as mixed circuit, 0 = mixed circuit)
Address selection (assignment of heating circuit)
High voltage connecting terminal (230 V)
Fuse 250 mA
Fuse 6.3 A
Low voltage connecting terminal (12 V)
CAN-BUS connecting terminal
Mixing module HHM - Subject to change without notice
Electrical connections
7.3
7
XB2 settings
1
5
2
6
3
7
4
6 720 615 683-21.1I
Fig. 17 Address selection, XB2 board
1
2
3
4
5
6
7
Switch off: factory setting, 12 V for mixing module supplied via CAN-BUS.
Switch on: not used, factory setting (0) must be applied.
Switch off: factory setting, transformer powers the mixing module.
Switch on: not used, factory setting (0) must be applied.
Additional mixed circuit, circuit 3.
Additional mixed circuit, circuit 4.
Pool
Mixing module HHM - Subject to change without notice
19
7
Electrical connections
7.4
Connection for heat pump and mixing modules
7.4.1
Connection for WPS 22 - WPS 60 and mixing modules
LCD
J4
J6
J5
4
3
4
3
2
1
2
1
PEL
CAN1
CAN1
0,1uF
J5
75Ω
75Ω
J2
J4
CAN1
J3
J7
1
2
3
4
TERM
J6
T1
1
5
PEL
BAS(2)
CAN1
CAN1
J3
J6
J5
J18
J19
1
2
1
2
3
4
3
4
J5
J2
J4
CAN1
J3
J7
T2
J2
1
2
3
4
TERM
A=1
P=0
4
XB1(1)
6
BAS(1)
A=0
P=0
A=0
P=0
J3
J8
J9
4
3
4
3
2
1
2
1
J5
J3
J1
J18
3
J19
1
2
1
2
3
4
3
4
J2
2
7
XB2 (2)
XB2 (1)
8
TR1
J4
T4
J5
J4
CAN1
CAN1
CAN1
CAN1
6 720 616 846-02.1I
T3
J5
TERM
TR1
A=1
P=0
TERM
A=2
P=0
Fig. 18
1
2
3
4
5
6
7
8
20
CAN-BUS cable 1-8
PEL (2) - PEL (1)
PEL (1) - BAS (1)
BAS (1) - XB1 (1)
XB1 (1) - BAS (2)
BAS (2) - LCD
PEL (1) - XB2 (1)
XB2 (1) - XB2 (2)
XB2 (2) - XB2 (?)
A
P
T1
T2
T3
T4
Address selection
Program select.
Is terminated
Is not terminated
Is terminated
Is not terminated
Mixing module HHM - Subject to change without notice
Electrical connections
7.4.2
7
Connection of WPS 22 - WPS 60 to pool
LCD
J4
J6
J5
4
3
4
3
2
1
2
1
PEL
CAN1
CAN1
0,1uF
J5
75Ω
75Ω
J2
J4
CAN1
J3
J7
1
2
3
4
TERM
J6
T1
1
5
PEL
BAS(2)
CAN1
CAN1
J3
J5
J18
J19
1
2
1
2
3
4
3
4
J5
J6
J2
J4
CAN1
J3
J7
T2
J2
1
2
3
4
TERM
A=1
P=0
4
XB1(1)
A=0
P=0
A=0
P=0
J3
J8
J9
4
3
4
3
2
1
2
1
J5
J3
J1
6
BAS(1)
J18
3
J19
1
2
1
2
3
4
3
4
J2
2
XB2 (1)
T4
J5
J4
CAN1
CAN1
6 720 617 644-05.1I
TR1
TERM
A=0
P=1
Fig. 19
1
2
3
4
5
6
CAN-BUS cable 1-6
PEL (2) - PEL (1)
PEL (1) - BAS (1)
BAS (1) - XB1 (1)
XB1 (1) - BAS (2)
BAS (2) - LCD
PEL (1) - XB2 (1)
Mixing module HHM - Subject to change without notice
A
P
T1
T2
T3
T4
Address selection
Program selection
Is terminated
Is not terminated
Is terminated
Is not terminated
21
8
8
Pool (accessory)
Pool (accessory)
The settings are only displayed if the pool was installed in
accordance with (Æ Chapter 5.1.3). An electric additional heater (0-10 V) must be connected to provide additional heat for the pool.
> Activate
Factory setting
No
Alternative
Yes/No
Tab. 15 Activating the pool
> Pool temperature
Factory setting
5 min
Lowest value
0 min
Highest value
30 min
Tab. 20 Ramp time close
B Adjust the time that the additional heater can take to
reach the maximum pool heating output once a CH
requirement has ended.
> Heat pump x
Factory setting
28.0 °C
Lowest value
10.0 °C
Highest value
40.0 °C
Tab. 16 Pool temperature
>> Active in pool heating
Factory setting
HP 1: No, HP 2: Yes
Alternative
No/Yes
Tab. 21 Active with pool heating
> Additional heat
>> Allow additional heat during pool heating
Factory setting
Alternative
> Ramp time close
Never
• Never
• With heating
>> Maximum pool hysteresis
Factory setting
2K
Lowest value
0.2K
Highest value
5K
Tab. 22 Maximum pool hysteresis
• Always
Tab. 17 Allow additional heat
>>Minimum pool hysteresis
> Additional heat start delay
Factory setting
0.2K
300 min
Lowest value
0.2K
Lowest value
0 min
Highest value
5K
Highest value
1200 min
Factory setting
Tab. 18 Additional heater, start delay
Tab. 23 Minimum pool hysteresis
>>Time factor pool hysteresis
This menu is only displayed if an additional heater is
allowed with pool heating.
Factory setting
10
> Ramp time open
Lowest value
1
Highest value
20
Factory setting
5 min
Lowest value
0 min
Highest value
30 min
Tab. 24 Time factor pool hysteresis
Tab. 19 Ramp time open
B Adjust the time that the additional heater can take to
reach the maximum pool heating output in the event of
an additional heat demand.
22
Mixing module HHM - Subject to change without notice
Pool (accessory)
> Pool heating start delay
>> Maximum PID signal
Factory setting
60 min
Factory setting
Lowest value
15 min
Lowest value
0%
Highest value
240 min
Highest value
100%
Tab. 25 Pool heating, start delay
Tab. 31 Maximum PID signal
The start delay only applies if more than one compressor
is allowed in pool mode. The first compressor to reach the
start status starts first. The next compressor start is prevented during the delay time.
>>Mixing valve running time
> Acknowledge extra pool sensor T81
Factory setting
Yes (if T81 is connected)
Alternative
8
Yes/No
Tab. 26 Extra pool sensor T81
> Regulator settings
>> P constant
Factory setting
1.0
Lowest value
0.1
Highest value
30.0
Factory setting
100%
300s
Lowest value
1s
Highest value
6000s
Tab. 32 Mixing valve running time
B Set the run time that is indicated on the mixing valve
and indicate value in number of seconds.
If there is no time indication on the mixing
valve, run it manually (Æ Chapter 8.1.3) and
measure how long it takes to go from fully
closed to a fully open mixing valve (the mixing
valve stops sounding and the endposition
switch switches off).
Tab. 27 P constant
>> I constant
Factory setting
300.0
Lowest value
5.0
Highest value
600.0
Tab. 28 I constant
>> D constant
Factory setting
0.0
Lowest value
0.0
Highest value
10.0
Tab. 29 D constant
>> Minimum PID signal
Factory setting
0%
Lowest value
0%
Highest value
100%
Tab. 30 Minimum PID signal
Mixing module HHM - Subject to change without notice
23
8
8.1
Pool (accessory)
Diagnostics/monitoring
8.1.1 Temperatures
> Pool
>> Additional pool sensor T81
>>> Adjust T81
>> Pool T82
>>> Adjust T82
8.1.2 Inputs
The status of all Inputs is displayed here. Only connected
Inputs are displayed.
> Inputs
>> External input pool
8.1.3 Outputs
The function of various central components can be tested
in the Outputs menu.
B Set the number of minutes for manual operation.
Different vital components can be put into operation/
turned off separately.
With 0min, status, e.g., On or Off, is displayed for each
component.
With the pool control system, it is essential
that the mixing valve (E81.Q81) opens and
closes in the right direction towards the heating system. When the mixing valve is fully
open, the entire flow is directed to the heating system. When the mixing valve is fully
closed, the entire flow is directed to the pool
exchanger.
The relevant components for the Pool function appear
under:
> Outputs
>> Pool
>>> Mixing valve signal
>>> Mixing valve open
>>> Mixing valve close
24
Mixing module HHM - Subject to change without notice
8
Pool (accessory)
8.1.4 Timers
Access level 0 = Customer
Access level 1 = Installer
Timers
Setting
Factory
setting
Access
level
300 min
1
Timer, pool
> Pool additional heat start delay
Diagnostics/monitoring\Timers \Additional heat
timers\Pool additional heat start delay
Tab. 33 Timers
Mixing module HHM - Subject to change without notice
25
9
9
Pool function, mixed circuit
Pool function, mixed circuit
One of the mixed circuits can be used to control the pool (Æ Chapter 5.1.4, circuit 4
(E14)). The settings in this chapter only apply
to the pool function.
B Make the following settings to obtain pool functionality.
>>> Heat curve
>>>> Type of heating system
Factory setting
Alternative
Underfloor
Radiator/Underfloor
> Settings
Tab. 38 Type of heating system
>> Circuit 1 Heating
B The value must not be changed.
>>> General
>>>> Flow temperature at minimum outdoor temperature
>>>> Use temperature from circuit with highest
temperature
Factory setting
35.0 °C
No
Lowest value
22.0 °C
Yes/No
Highest value
45.0 °C
Factory setting
Alternative
Tab. 34 Temperature from circuit with highest temperature
B Change setting to Yes.
Tab. 39 Underfloor
B Reduce the flow temperature to 22 °C.
>>>> Parallel offset
>>> Heat curve
Factory setting
>>>> Type of heating system
Factory setting
Alternative
Underfloor
Radiator/Underfloor
Tab. 35 Type of heating system
B Change to Radiator at Yes in Use temperature
from circuit with highest temperature.
>>>> Flow temperature at minimum outdoor temperature
0.0K
Lowest value
-10.0K
Highest value
10.0K
Tab. 40 Parallel offset
B Use Parallel offset to set the desired pool temperature. For example, 6.0 K for a pool temperature of 28°C.
B Switch to customer level.
> Room and hot water program
>> Circuit 4
Factory setting
60.0 °C
>>> Active program
Lowest value
22.0 °C
B Select HP optimized.
Highest value
80.0 °C
B Go back to the installer level and select Diagnostics/
monitoring.
Tab. 36 Radiators
B At Yes in Use temperature from circuit with highest temperature, set a low value for the flow temperature, e.g., 22 °C.
>> Circuit 4
> Diagnostics/monitoring
>> Temperatures
>>> Circuit 4
>>>> Damped room sensor T5
>>> Mixing valve mode
Factory setting
Alternative
Off
Heating/Off
Tab. 37 Mixing valve operating mode
B Select Heating to use the circuit for the pool.
26
Factory setting
0.25h
Lowest value
0.00h
Highest value
48h
Tab. 41 Damped room sensor T5
B Set damping to 0.00 h.
Mixing module HHM - Subject to change without notice
10
Factory values
10
Factory values
10.1 Pool (accessory)
Access level 0 = Customer
Access level 1 = Installer
Pool
Factory setting
Activate
Pool temperature
Additional heat
Allow additional heat during pool heating
Additional heat start delay
Heat pump x
No
0
28.0 °C
0
Never
0
300 min
0
Ramp time open
5 min
1
Ramp time close
5 min
1
Active in pool heating
Yes
1
Maximum pool hysteresis
2.0K
1
Minimum pool hysteresis
0.2K
1
10
1
Time factor pool hysteresis
Pool heating start delay
Acknowledge extra pool sensor T81
Regulator settings
Access
level
60 min
1
No
1
1
P constant
1.0
I constant
300.0
1
D constant
0.0
1
1
Minimum PID signal
0%
Maximum PID signal
100%
1
Mixing valve running time
300s
1
Tab. 42 Factory values pool accessory
Mixing module HHM - Subject to change without notice
27
10
Factory values
10.2 Pool function, mixed circuit
Access level 0 = Customer
Access level 1 = Installer
The settings applicable for the pool function with mixed
circuit are shown in bold text.
Factory setting
Circuit 1 Heating
General
External set point value
No
1
Use temperature from circuit with highest temperature
No
1
Fixed temperature
Shut down protection during change over from hot
water to heating
Heat curve
Type of heating system
Flow temperature at minimum outdoor temperature, Radiator/Underfloor
Parallel offset
Highest permitted flow temperature T1,
Radiator/Underfloor
No (0.0 °C)
1
300s
1
Underfloor
1
60/35 °C
1
0.0K
1
80/45 °C
1
Lowest permitted flow temperature T1
10 °C
1
Heat curve hysteresis heat
pump x
Maximum
Minimum
Time factor
16.0K
4.0K
10.0
1
1
1
Room sensor
Room temperature influence (if installed)
Knob's operating range (if installed)
Acknowledge room sensor
3.0
6K
(Auto)
1
1
1
Setting temp. increase/decrease
(no room temperature sensor)
Limit value for left or right end point
Change when much colder/warmer
Change when colder/warmer
0.0 °C
8%
3%
1
1
1
3.0
1
Room temperature influence
(no room temperature sensor)
Circuit 2, 3...
Access
level
Air handling unit in circuit
No
Mixing valve mode
Off
Heat curve
See Circuit 1 Heating
Room sensor (accessory)
Room temperature influence (if installed)
Acknowledge room sensor
Setting temp. increase/decrease
(no room temperature sensor)
See Circuit 1 Heating
Room temperature influence
(no room temperature sensor)
Regulator settings
P constant
I constant
D constant
Minimum PID signal
Maximum PID signal
Mixing valve running time
Mixing valve fully closed
Mixing valve start closing
Connected to output type
1
1
3.0
(Auto)
1
1
1
3.0
1
1
300
0.0
0%
100%
300s
2K
2K
Op/Cl
1
1
1
1
1
1
1
1
1
Tab. 43 Factory values pool mixed circuit
28
Mixing module HHM - Subject to change without notice
10
Notes
Mixing module HHM - Subject to change without notice
29
10
30
Mixing module HHM - Subject to change without notice
10
Mixing module HHM - Subject to change without notice
31