Electrak Lightrak lighting control system

Transcription

Electrak Lightrak lighting control system
Lightrak ...
®
KNX lighting
control system
LIGHTRAK / SYSTEM GUIDE
INCLUDING BUSCOM
POWERED BY SPECIALISTS
LTK_Bro_Covers v1.indd 1
29/08/2012 12:21
®
Electrak ... the specialist in power
distribution throughout the workplace
Electrak, part of the Legrand Group in the UK, is a leading manufacturer of power
distribution and lighting control solutions. Its power track, floor boxes and grommets,
desk modules and lighting control ranges are installed in high specification offices
around the world.
LTK_Bro_002_003 v1.indd 2
29/08/2012 12:14
Legrand is the global specialist in electrical
and digital building infrastructures. Innovation
is the driving force behind its development.
With an increasing investment in research
and development (circa 5% of sales) and more
than 4,000 active patents, the Legrand Group
is focused on maintaining a high rate of new
product launches that present innovative
solutions to the market.
CONTENTS
Buscom trunking
Lightrak system - features
Adapting to changing buildings
Integration with KNX and DALI
Lightrak sensors
System support service
Case studies
4
6
8
10
12
14
15
SUSTAINABLE DEVELOPMENT
From design through to manufacturing,
the Legrand Group selects materials and
processes that respect people and
the environment.
• Efficient and environmentally aware product design
• Product functions that help to avoid energy waste
• Management of manufacturing and logistics sites
• Integration of environmental concerns and ISO 14001
procedures at the Group’s global sites.*
ORDERING INFORMATION
System components, lighting
control units, sub-cabling
16
Standard switching devices
17
Sub-bus addressable devices
18
Buscom trunking
24 - 37
TECHNICAL INFORMATION
Lightrak
Buscom trunking
19 - 23
38 - 43
* 84% of sites are ISO 14001:2004 accredited including all UK sites.
LEGRAND IN THE UK POWERED BY SPECIALISTS
In the UK Legrand has developed a customer focused
structure which harnesses the power of its market
leading specialist brands to deliver innovative,
integrated solutions for every phase of construction.
LTK_Bro_002_003 v1.indd 3
29/08/2012 12:14
Buscom trunking...
a unique power and data backbone
Buscom is at the heart of Electrak’s lighting control solutions... distributing both
power and communications within a single busbar trunking system, it provides a
lexible and simple alternative to traditional wiring installations.
THE HEART OF YOUR LIGHTING CONTROL SYSTEM
Installing a matrix of Buscom trunking in the ceiling void creates an accessible power and
communications backbone throughout a building. The backbone can be tapped into at any point to
facilitate instant connection to power and control circuits.
Buscom incorporates a shielded twisted pair communications bus inside each length and tap-off,
and is suitable for use with any lighting control protocol, including: KNX, LonWorks and DALI.
MODULAR. FLEXIBLE. SIMPLE.
Trunking lengths simply push it together, saving time and money on installation. With cable
terminations only required for power and control circuits in the feed unit, Buscom delivers a plug
and play solution that allows for future lighting layout changes to be made quickly and eficiently,
whilst drastically reducing the potential points of failure in comparison with traditional wiring
methods.
04
• Power and communications within a single
trunking system
• Suitable for use with any lighting control protocol,
including: KNX, LonWorks and DALI
• Modular, lexible system which is quick and simple
to install and adapt
• Reduced potential points of failure in comparison
with traditional wiring installations
LTK_Bro_004_005 v1.indd 4
29/08/2012 12:15
Buscom adds a new dimension to lighting busbar that extends the unquestionable
plug and play advantages from the power circuit to the control circuit. This unique
system for distributing lighting control signals delivers unrivalled flexibility,
regardless of the location of the intelligence...
INTELLIGENCE IN THE PANEL
INTELLIGENCE IN THE BUSBAR
Lighting control modules
located in a central cabinet are
connected to the Buscom system
via communication circuits that
terminate in the feed unit. Control
signals are then distributed
along the trunking run and made
available at any tap-off outlet.
Integrating lighting control
technology into the Buscom feed
unit is particularly effective for
DALI control. Each trunking run
converts to an individual DALI
network into which luminaires can
tap-in at any point.
INTELLIGENCE IN THE LCU
Lighting control units (LCUs)
are mounted onto and plugged
into Buscom trunking, providing
a hub into which multiples of
luminaires and switching devices
are plugged. Buscom’s integrated
communication bus provides the
backbone which networks all
control devices together.
05
ENERGY SAVING
As with all Electrak
solutions, Buscom is
a modular system
designed to be quick
and simple to install,
reducing man hours and
energy usage on site.
energy saving
LTK_Bro_004_005 v1.indd 5
29/08/2012 12:15
Lightrak ...
®
fully addressable lighting control
Designed to work in harmony with
Electrak’s Buscom trunking, Lightrak’s
lighting control system offers high end
sophistication with unbeatable
lexibility and speed of installation.
PRESENCE OR
ABSENCE DETECTION
Saves energy and ensures that
lighting is only on when needed
TIMED EVENT CONTROLLER
Programmable touch screen units
optimise energy saving
SCENE SETTING SWITCH
Multiple lighting scenarios are
memorised and retrieved at the
touch of a button
EMERGENCY TEST
MULTI-GANG SWITCHES
Traditional key switch to enable
testing of self-contained emergency
luminaires
1, 2, 4 and 8 gang options connect
via CAT. 5 cable and RJ 45 plugs
06
SNAP ON... PLUG IN
Lightrak lighting control units
(LCUs) simply snap on and plug into
Electrak’s Buscom trunking and
are easily unplugged, moved and
reprogrammed to accommodate
future lighting layout changes.
LTK_Bro_006_007 v1.indd 6
29/08/2012 12:16
SOPHISTICATED TECHNOLOGY
FULLY ADDRESSABLE
Analogue and DSI dimming
through to full DALI
control in addressable
mode.
A full KNX network can
support in excess of 64,000
KNX devices.
Each output of every
lighting control unit (LCU)
is individually controllable.
Lightrak offers full
building-wide control
for even the largest of
projects.
Networked over a KNX
backbone that can be
integrated onto IP or BMS
systems.
DALI EMERGENCY FEEDBACK
WIDE RANGING CONTROL
Two way DALI
communication facilitates
feedback from DALI
emergency inverters onto
the KNX bus.
A comprehensive range
of control devices is
available: PIR / ultrasonic
sensors - wireless
reconiguration of sensor
parameters - scene setting
- remote control - time
scheduling - traditional
switching and emergency
key switch.
Monitoring and reporting
software can be easily
integrated with KNX.
DAYLIGHT LINKING
ABSENCE DETECTION
Lighting levels are
adjusted in relation to
the natural daylight
contribution.
Optimise energy savings
in cellular ofices and
meeting rooms. The
occupant chooses when
the lights are on; the
system ensures they are
switched off when the
space is vacated.
Sensors initiate dimming,
saving energy and
delivering a constant
luminance at the desk.
07
• Fast, easy installation. Snap on / plug in
• Fully addressable and PC reconigurable
• Analogue, DSI and DALI control
• Comprehensive range of energy saving switching,
sensing and scheduling devices available
• Seamless connectivity with KNX devices from close to
300 manufacturers
• Interface with other building control systems via the
open KNX protocol
• Two way communication with DALI, facilitating control
and feedback
• Traditional emergency lighting test functions
• Comprehensive design and commissioning service
LTK_Bro_006_007 v1.indd 7
29/08/2012 12:17
The ability to adapt with the b
08
At the Category A stage of an ofice it-out the
lighting requirements of the inal tenant are not
known.
With Lightrak, developers are able to install a
cost-effective lighting control solution that is
adequate for the client attraction phase, but can
be upgraded to meet the needs of the incoming
tenant with a minimum level of investment in
time and labour.
LTK_Bro_008_009 v3.indd 8
30/08/2012 16:19
e building throughout its life
09
With a matrix of Buscom trunking installed,
a Lightrak installation provides a future proof
solution where lighting schemes can be
completely reconigured without the need to
run or terminate any additional cables. Lighting
control units are simply unplugged, moved and
reprogrammed; additional devices and control
units can also be added to extend the capability
of any installation.
LTK_Bro_008_009 v3.indd 9
30/08/2012 16:19
Lightrak ...
®
seamless integration with your
technology of choice
The Lightrak system operates over a KNX backbone. This
enables all control devices connected to the system to
communicate with each other, and facilitates seamless
interoperability with any KNX certified product.
KNX PROTOCOL SYSTEMS
KNX is the worldwide standard for all applications
in home and building control, ranging from lighting
and shutter control to security, HVAC, metering and
energy management. With close to 300 members and
approximately 7000 certified product ranges, the KNX
Association holds partnership agreements with over
30,000 installer companies in over 100 countries.
All products bearing the KNX logo are certified in order
to guarantee system compatibility, interworking and
interoperability and are commissioned via a single,
manufacturer independent design and commissioning tool.
LEFT: KNX was used as the underlying technology at
Terminal 5, Heathrow... possibly the largest lighting
control installation in Europe
10
KNX IS APPROVED AS:
ENERGY SAVING
Lighting accounts
for up to 40% of a
commercial building’s
electricity use.
• European Standard (CENELEC EN 50090 and
CEN EN 13321-1)
• International Standard (ISO/IEC 14543-3)
(Lighting Industry Federation)
Lighting controls can
provide energy savings
of 30% to 55%.
energy saving
LTK_Bro_010_011 v1.indd 10
For more information about KNX, visit: www.knx.org
29/08/2012 12:18
DALI: DIGITAL LIGHTING CONTROL
DALI (Digital Addressable Lighting Interface) is a protocol
dedicated purely to lighting control, as set out in the
technical standard IEC 62386. Each unit in a DALI network
has its own address, allowing direct communication with
each individual itting.
DALI FEATURE
IMAGE
TECHNICAL FEATURES
The information low with DALI is bi-directional. Rather
than only giving commands about the light level from the
control system to the itting, DALI also enables information
feedback on the condition of the ittings.
The itting can transmit information related to:
• whether the light is switched on or off
• the preset light level
• the ballast condition
Therefore DALI is ideal for use with building automation
systems where remote supervising and service reports are
required.
11
DELIVERING DALI EMERGENCY FEEDBACK
The DALI lighting control unit (LCU) incorporates a
KNX to DALI interface that enables full DALI control in
addressable mode, and also facilitates the feedback from
the DALI network back onto the KNX bus.
Utilising widely available KNX gateways, this DALI
feedback can then be fed into building management
systems (BMS) or other monitoring and reporting software,
allowing emergency lighting test data to be logged and
alarms raised should essential maintenance be required.
For more information about DALI, visit: www.dali-ag.org
LTK_Bro_010_011 v1.indd 11
29/08/2012 12:18
The simple way to instant
energy savings
Combining lighting management sensors with traditional light switches puts users in
complete control. Lights can be manually switched on and off or, if users forget to switch
off lights, the sensors will do so automatically.
EVEN GREATER SAVINGS
Independent research shows that the
added control available through using
absence detection can provide an
additional 10% energy saving over and
above the significant savings already
offered by presence detection.
IN DARKNESS
Users feel in complete control by turning on
lights using a traditional switch, typically located
by the door
IN BRIGHT LIGHT
The sensor will automatically switch off lights to
save energy when available light is sufficient
(although lights can still be switched on if preferred)*
IN NORMAL
LIGHT
IN WEAK LIGHT
The sensor will automatically switch on lights
when movement is detected and available light
is insufficient*
When leaving the room, lights can be manually
turned off using a switch. If lights are not turned
off, the occupancy sensor will do so automatically
12
ENERGY SAVING
Lighting controls
are eligible for 100%
Enhanced Capital
Allowance under
the Carbon Trust
administered scheme.
energy saving
* Lux levels can be set according to user preferences
LTK_Bro_012_013 v2.indd 12
30/08/2012 09:51
THE RIGHT TECHNOLOGY
FOR EVERY ENVIRONMENT
Legrand lighting management
solutions are available in three
different technologies to provide
effective occupancy detection in
different environments... all of which
can be controlled and commissioned
remotely at the touch of a button.
For small, enclosed spaces
PIR sensors detect occupancy
using the heat difference between
people and the ambient space.
For large spaces and open
areas Ultrasonic sensors
transmit sound waves throughout an
area and measure the speed at which
they come back.
For spaces with low or
infrequent movement from
occupants Dual technology, as the
name suggests, combines both
infra-red and ultrasonic detection.
13
REMOTE CONFIGURATORS FOR INSTANT
PROGRAMMING OF EACH SENSOR
Sensors can be quickly and easily re-configured at the touch of a button,
and without the need to ever remove the sensors from the ceiling... putting
users in complete control and reducing health and safety risks.
• Advanced commissioning tool with LCD display
- Precise digital programming
- Instant visibility of individual sensor settings
- PIR / ultrasonic priority preferences for dual technology sensors
• Basic commissioning tool
- Pre-programmed settings
Save time. Save money. And, of course, save energy.
LTK_Bro_012_013 v2.indd 13
30/08/2012 09:22
Legrand...
supporting you from initial design
through installation and beyond
DEDICATED DESIGN TEAM
Lighting control units can either be supplied
unprogrammed for third party system integration,
or complete with a full in-house project design and
commissioning service.
Our experienced team provides support at all stages
of a project, from the outline brief through to inal site
commissioning.
Sales engineers work with designers at the early stages
of a project to recommend optimum Buscom layouts
and lighting control options. This service is backed by a
specialist support team who are on hand to work with
clients to complete detailed design schemes and provide
full support through the installation phase.
BESPOKE SOLUTIONS
Every project is unique and sets its own challenges.
Our bespoke product development service enables us to
provide solutions to these challenges, and has delivered
tailor-made lighting control installations in a wide range
of building developments, including: Terminal 5, Heathrow,
London Underground, Canary Wharf and Central Bank
of Kuwait.
14
LTK_Bro_014_015 v1.indd 14
29/08/2012 12:19
TRUSTED THOUGHOUT THE UK AND ACROSS THE WORLD
LIGHTRAK PROJECTS
• Royal Bank of Scotland – Delhi, India
• Fidelity Investments – Delhi, India
• Cyprus Postal Service – Nicosia, Cyprus
• 2 x ITTL Showrooms – Nicosia, Cyprus
• Barclays Bank – Pane, India
• UKPS – Liverpool, England
• Lloyds TSB Bank – Old Broad Street,
London, England
• Bridgewater Place, Mixed use
Development – Leeds, England
• Lloyds TSB Card Contact Centre Petriies, Scotland
• Gray’s School of Art - Robert Gordon
University, Aberdeen, Scotland
• Rolls Royce - Glasgow, Scotland
• Liverpool School of Tropical Medicine
Ofice and Labs – University of Liverpool,
England
• Quorum Business Park, Ofice
Development (16 Buildings) - Newcastle
upon Tyne, England
• Mann Island, Ofice Development –
Liverpool, England
• Rotherham Civic Quarters, Local
Government Ofices - Rotherham,
England
• First Street Manchester, Manchester City
Council - England
• Velocity Buildings, Ofice Development Brooklands, Surrey, England
• Broadgate West, Ofice Development –
London, England
• Abbey Gardens, Ofice Development Reading, England
• HSE – Dublin, Ireland
• KPMG – Manchester, England
• KPMG – Watford, England
• Rackspace Data Centre – Slough,
England
• Translational Research Building –
Newcastle University, England
• Shadon House Care Facility –
Gateshead, England
15
LTK_Bro_014_015 v1.indd 15
29/08/2012 12:20
Lightrak® KNX lighting control system
system components, lighting control units (LCUs) and sub-cabling to luminaires
Feed unit
Buscom mounting
power supply unit
See p. 28-29
Luminaire sub
cabling
FFA010
- - -/- - -
FFE115
Timed event
controller
Powered line
coupler
FFA004
FFA008
Lighting control
unit
FFD060
Dimensions and technical information (p. 19-23)
Proprietory lighting control system to work alongside Electrak’s 25 and 40 A buscom trunking with integral communications bus
Offers high speed installation and unrivaled flexibility for future reconfiguration. PC configurable, covers all lighting control requirements
Based on the KNX open protocol and compatible with 1-10 V, DSI and DALI lighting installations
Designed and manufactured in the UK from robust galvanised steel
Pack
Cat. Nos.
System components
1
1
1
1
1
1
1
1
FFA001
FFA004
FFA006
FFA008
FFA010
FFA012
FFA014
FFA016
Statutory warning plaque
Timed event controller (flush)
Timed event controller (surface)
Powered line coupler
Buscom mounting power supply unit
Line power supply
KNX signal cable – 100 m
USB to KNX interface
Lighting control units (LCUs) – 9 outputs
(fully addressable)
1
1
1
1
1
FFD054
FFD054B1
FFD054B2
FFD054B3
FFD055
Analogue dimming (1-10 V)
Buscom mounting (standard buscom)
L1 Key ‘B’ buscom mounting (3 phase buscom)
L2 Key ‘B’ buscom mounting (3 phase buscom)
L3 Key ‘B’ buscom mounting (3 phase buscom)
Rewirable surface mounting
1
1
1
1
1
FFD056
FFD056B1
FFD056B2
FFD056B3
FFD057
Digital dimming (DSI)
Buscom mounting (standard buscom)
L1 Key ‘B’ buscom mounting (3 phase buscom)
L2 Key ‘B’ buscom mounting (3 phase buscom)
L3 Key ‘B’ buscom mounting (3 phase buscom)
Rewirable surface mounting
FFD060
FFD060B1
FFD060B2
FFD060B3
FFD061
DALI (digital addressable lighting interface)
Buscom mounting (standard buscom)
L1 Key ‘B’ buscom mounting (3 phase buscom)
L2 Key ‘B’ buscom mounting (3 phase buscom)
L3 Key ‘B’ buscom mounting (3 phase buscom)
Rewirable surface mounting
NEW
1
1
1
1
1
Pack
Cat. Nos.
Sub-cabling to luminaires
1
FFE080
Plugs only
6 pole rewirable plug (male)
1
1
1
1
1
FFE085
FFE095
FFE115
FFE135
FFE120
1
FFE125
Pre-wired plugs and leads (5 m LSOH)
With 6 pole male plug to free end – 5 core
With 6 pole male plug to free end – 6 core
With 6 pole male plug to 6P female plug – 6 core
With 6 pole male plug to 4P female plug – 4 core
With 6 pole male plug to free end – 3 core no
dimming
With 6 pole male plug to free end – 4 core no
dimming
16
LTK_Bro_016_017 v4.indd 16
22/08/2012 15:31
Lightrak® KNX lighting control system
standard switching devices
Lighting control
unit
- - -/- - -
See p. 16
Multi-gang
switch interface
- - -/- - -
FFB020
4 gang switch
FFB022-4
Presence detector
1 gang switch
1 gang key switch
FFC047
FFB030
FFB032
Dimensions and technical information (p. 19-23)
Standard switching devices connect into the system via simple CAT 5 cabling either straight into a lighting control unit or into a multi-gang switch
interface. The inputs of the control units are addressable and can be commissioned to control any output or group of outputs throughout the entire
KNX network. Future layout changes can be accommodated easily as all control units are plug and play and can be re-commissioned through
KNX ETS software
Pack
Cat. Nos.
Standard presence detector
1
FFC047
Plug into lighting control unit
Presence detector
Pack
Cat. Nos.
CAT 5 cabling to switching devices
1
1
FFF205
FFF210
5 m CAT 5 lead – plug to plug
10 m CAT 5 lead – plug to plug
Switches
Switches for 1 gang back box
1
1
1
1
FFB030
FFB032
FFB033
FFB034
Plug into lighting control unit (see p. 16)
1 gang switch
1 gang key switch
1 gang key switch – surface (including back box)
2 gang switch
Switches for 2 gang back box
1
1
1
FFB022-2
FFB022-3
FFB022-4
Plug into multi-gang switch interface
(Cat. No. FFB020)
2 gang switch
3 gang switch
4 gang switch
Switches for 2 x 2 gang back box
1
1
1
1
FFB024-5
FFB024-6
FFB024-7
FFB024-8
Plug into multi-gang switch interface
(Cat. No. FFB020)
5 gang switch
6 gang switch
7 gang switch
8 gang switch
Multi-gang switch interface
1
FFB020
Buscom mounted multi-gang switch interface
Back boxes
1
1
1
FFB036
FFB026
FFB028
1 gang
2 gang
2 x 2 gang
17
LTK_Bro_016_017 v4.indd 17
22/08/2012 15:32
Lightrak KNX lighting control system
®
NEW 2013
able
i
a
Av l
sub-bus addressable devices
FFC020
FFC058
FFC055
FFC052
FFC021
FFC050
FFC023
FFC059
FFC024
Technical information (p. 21)
Addressable sensing and switching devices can be connected in series on a sub-bus
Each sub-bus connects onto the KNX network via a sub-bus to KNX interface unit
The addressable sensors offer a higher level of capability and functionality :
• Factory set to presence mode, absence mode activated by commissioning tool
• Factory pre-set light level threshold 500 lux for false ceiling, 300 lux for surface mounting / flush mounting detectors
• Factory pre-set time delay 15 minutes
• Precise adjustment on-site via commissioning tool
Devices can be commissioned to control any output or group of outputs throughout the entire KNX network. Future layout changes can be
accommodated easily as all devices can be re-commissioned through KNX ETS software
Pack
Cat. Nos.
Sub-bus to KNX interface unit
1
FFC020
Buscom mounting interface unit
Cat. Nos.
Sub-bus sensor – for corridors
FFC057
Connects into interface unit (Cat. No. FFC020)
With absence and presence modes
Includes 10 m connection lead
Maximum range 30 m – IP 42
PIR sensor 140°
Sub-bus sensors – ceiling mounting
IR remote control
Connect into interface unit (Cat. No. FFC020)
With absence and presence modes
Includes 5 m connection lead
FFC058
For sub-bus sensors (client use)
On / off – dimming controller
Pack
Sub-bus sensors – commissioning tool
1
FFC021
Digital hand-held commissioning tool
1
1
Other sub-bus devices
PIR sensor
1
1
FFC050
FFC051
Detection field 45 m2 – Ø 8 m
Optimum distance between detectors : 6 m
PIR ceiling mounting switch sensor 360°
Surface mounting box for FFC050
Combined PIR and ultrasonic sensor
1
1
FFC052
FFC053
Light measurement cell
1
FFC059
Sub-bus switches
Detection field 90 m2 – Ø 11 m
Optimum distance between detectors : 10 m
PIR and ultrasonic ceiling mounting sensor 360°
Surface mounting box for FFC052
Sub-bus sensors – wall mounting
1
FFC030
FFC033
Connect into interface unit (Cat. No. FFC020)
Includes 10 m connection lead
Complete with brushed stainless steel plate, yolk
and magnesium rockers
2 gang 2 way sub-bus switch
4 scenario sub-bus switch
1
1
1
FFC022
FFC023
FFC024
Sub-bus cable – 100 m
RJ45 doubler unit to extend sub-bus
Sub-bus to RJ45 connector
1
Connect into interface unit (Cat. No. FFC020)
With absence and presence modes
Includes 10 m connection lead
PIR sensor
1
FFC054
Maximum range 8 m – IP 42
PIR wall mounting sensor 180°
Connects into interface unit (Cat. No. FFC020)
Includes 5 m lead
Photocell light level sensor
Sub-bus accessories
Combined PIR and ultrasonic sensor
1
FFC055
Maximum range 11 m – IP 42
PIR and ultrasonic wall mounting sensor 180°
IP 55 sensor
1
FFC056
Maximum range 15 m – IP 55
PIR wall mounting sensor 270°
18
LTK_Bro_018 v4.indd 18
22/08/2012 15:37
Lightrak® KNX lighting control system
technical information
n KNX technical specification
n Buscom trunking mounted power supply unit FFA010
Each line coupler can support 64 bus devices (lighting control units,
multi-gang switch interface units, bus interface units etc)
A maximum of 15 line couplers may be linked with a main bus line
together to form an area; therefore an area can support up to 960
devices
The system may be further expanded with the addition of a backbone
bus line which would allow the linking together of 15 main bus lines
via 15 line couplers, therefore any single system could support 14 400
devices
By utilising additional line couplers this total can exceed 64 000 devices
(for additional information, please contact us on +44 (0) 845 600 6266)
Connections
• 230 V : Electrak integrated tap-off
• Bus : Electrak integrated tap-off
Physical specifications
• Housing : galvanised steel, natural finish
• Dimensions : length 330 mm, width 110 mm, height 60 mm
9 mm bracket clearance from busbar trunking
• Weight : approximately 1·90 kg
Technical specifications
Supply voltage : 230 V
50/60 Hz
Protection (supply) : 13 A BS 1362 fuse fitted in tap-off
Internal protection : 6·3 A fuse to IEC 127-2
Secondary output voltage : 30 Vdc +/- 2 V
Secondary output current : 640 mA
Tap-off ASTA approved : BS EN 60439-2 : 2000
EMC complies with : EN 50090-2-2 :1997, EN 55022B
Climatic condition class : 3K4 (5ºC to 40ºC)
IP rating : 4x
Certification : KNX certified
Within any KNX bus line the following cable lengths are permitted :
• Power supply unit to bus device 350 m maximum
• Bus device to bus device 700 m maximum
• Total bus line length 1 000 m maximum
• Minimum distance between 2 power supply units on one line is 200 m(1)
n Powered line coupler FFA008
Connections
• 230 V : screw connection block
• Primary line : screw connection block
• Secondary line : screw connection block
Physical specifications
• Housing : galvanised steel, natural finish
• Dimensions : length 358 mm, width 200 mm, depth 75 mm
• Weight : approximately 2·750 kg
Technical specifications
Supply voltage : 230V
50/60Hz
Protection (supply) : 13 A BS 1362 fused spur
Internal protection : 6·3 A fuse to IEC127-2
Primary line load : 15 mW
Secondary line load : 200 mW
Secondary output voltage : 30Vdc +/- 2 V
Secondary output current : 630 mA
EMC complies with : EN 50090-2-2 : 1997, EN 55022B
Climatic condition class : 3K4 (5ºC to 40ºC)
IP rating : 4x
Certification : KNX certified
±
±
(1) Electrak manufacture a buscom trunking mounted power supply unit for this application,
Cat. No. FFA010 see p. 16
±
±
n Line power supply FFA012
Connections
• 230 V : screw connection block
• Bus : screw connection block
Physical specifications
• Housing : galvanised steel, natural finish
• Dimensions : length 358 mm, width 110 mm, depth 75 mm
• Weight : approximately 1·95 kg
Technical specifications
Supply voltage : 230 V
50/60Hz
Protection (supply) : 13 A BS 362 fused spur
Internal protection : 6·3 A fuse to IEC 127-2
Secondary output voltage : 30 Vdc +/- 2 V
Secondary output current : 640 mA
EMC complies with : EN 50090-2-2 : 1997, EN 55022B
Climatic condition class : 3K4 (5ºC to 40ºC)
IP rating : 4x
Certification : KNX certified
±
±
All dimensions (mm) are nominal
19
LTK_Bro_019_023 v4.indd 19
23/08/2012 13:55
Lightrak® KNX lighting control system
technical information
n Lighting control unit – analogue dimming Cat. Nos.
FFD054/FFD055
Connections
• 4 RJ45 inputs : CAT 5 providing switching input
• 9 GST/6 providing 230 V to luminaires
L1 Switched live brown
E Earth green / yellow
N Neutral blue
L2 Maintained live black
2 Dimming common white
3 Dimming red
Physical specifications
• Housing : galvanised steel, natural finish
• Dimensions : length 358 mm, width 182 mm, depth 35 mm plus 9 mm
bracket clearance from buscom trunking
• Weight : approximately 1·75 kg
Technical specifications
Supply voltage : 230 V
50/60Hz
Maximum load : 10 A BS 1362 fuse fitted in tap-off
Maximum power : 2 300 VA
Bus voltage : 30 Vdc +/- 2 V
Tap-off ASTA approved : BS EN 60439-2 : 2000
EMC complies with : EN 50090-2-2 : 1997
Climatic condition class : 3K4 (5ºC to 40ºC)
IP rating : 4x
Certification : KNX certified
±
±
n Lighting control unit – DSI dimming Cat. Nos. FFD056/
FFD057
Connections
• 4 RJ45 inputs : CAT 5 providing switching input
• 9 GST/6 providing 230 V to luminaires
L1 Switched live brown
E Earth green / yellow
N Neutral blue
L2 Maintained live black
2 Dimming common white
3 Dimming red
Physical specifications
• Housing : galvanised steel, natural finish
• Dimensions : length 358 mm, width 182 mm, depth 35 mm plus 9 mm
bracket clearance from buscom trunking
• Weight : approximately 1·75 kg
Technical specifications
Supply voltage : 230 V
50/60 Hz
Maximum load : 10 A BS 1362 fuse fitted in tap-off
Maximum power : 2 300 VA
Bus voltage : 30 Vdc +/- 2 V
Tap-off ASTA approved : BS EN 60439-2 : 2000
EMC complies with : EN 50090-2-2 : 1997
Climatic condition class : 3K4 (5ºC to 40ºC)
IP rating : 4x
Certification : KNX certified
±
±
n 4 gang switch Cat. No. FFB022-4
Physical specifications
• Housing : steel back box 132 mm x 72 mm minimum 48 mm deep
• Dimensions : length 125 mm, width 64 mm, height 41 mm
• Weight : approximately 0·668 kg
Technical specifications
Supply voltage : 9 Vdc
EMC complies with : EN 50090-2-2 : 1997
Climatic condition class : 3K4 (5ºC to 40ºC)
IP rating : 4x
Certification : KNX certified
n 8 gang switch Cat. No. FFB024-8
Physical specifications
• Housing : steel back box 136 mm x 136 mm minimum 52 mm deep
• Dimensions : length 127 mm, width 122 mm, height 41 mm
• Weight : approximately 1·30 kg
Technical specifications
Supply voltage : 9 Vdc
EMC complies with : EN 50090-2-2 : 1997
Climatic condition class : 3K4 (5ºC to 40ºC)
IP rating : 4x
Certification : KNX certified
n Multi-gang switch interface Cat. No. FFB020
Connections
• 230 V : Electrak integrated tap-off
• Bus : Electrak integrated tap-off
• Switch : CAT 5 lead (RJ45 to RJ45)
Physical specifications
• Housing : galvanised steel, natural finish
• Dimensions : length 126 mm, width 102 mm, height 46 mm plus
9 mm mounting bracket
• Weight : approximately 0·66 kg
Technical specifications
Supply voltage : 230 V
50/60 Hz
Protection : 3 A BS 1362 fuse fitted in tap-off
Nominal load : 24 mA
Maximum bus load : 12 mA
Tap-off ASTA approved : BS EN 60439-2 : 2000
EMC complies with : EN 50090-2-2 : 1997
Climatic condition class : 3K4 (5ºC to 40ºC)
IP rating : 4x
Certification : KNX certified
±
±
n Lighting control unit – dimensions
Cat. Nos. FFD054, FFD056, FFD060
n Lighting control unit – DALI Cat. Nos. FFD060/FFD061
Connections
• 4 RJ45 inputs : CAT 5 providing switching input
• 9 GST/6 providing 230 V to luminaires
L1 Switched live brown
E Earth green / yellow
N Neutral blue
2 DALI
3 DALI
Physical specifications
• Housing : galvanised steel, natural finish
• Dimensions : length 358 mm, width 182 mm, depth 35 mm plus 9 mm
bracket clearance from buscom trunking
• Weight : approximately 1·75 kg
Technical specifications
Supply voltage : 230 V
50/60 Hz
Maximum load : 10 A
Maximum power : 2 300 VA
KNX bus voltage : 30 Vdc +/- 2 V
Tap-off ASTA approved : BS EN 60439-2 : 2000
EMC complies with : EN 50090-2-2 : 1997
Climatic condition class : 3K4 (5ºC to 40ºC)
IP rating : 4x
±
±
All dimensions (mm) are nominal
20
LTK_Bro_019_023 v4.indd 20
22/08/2012 16:06
Lightrak® KNX lighting control system
sub-bus sensors technical information
n Ceiling mounting
All sub-bus sensors have built-in bracket systems that
enable ceiling mounting. Most sensors are suitable for
standard EU boxes (Ø 65). This is important for applications
where the ceiling is unavailable for sensor installation. Only
one Cat. No. is required for two ways of mounting
n Sub-bus to KNX interface unit FFC020
Connections
• Bus : Electrak integrated tap-off connecting 230 V and KNX bus
Physical specifications
• Housing : galvanised steel, natural finish
• Dimensions : length 125 mm, width 154 mm, height 72 mm plus 9 mm
mounting bracket
Technical specifications
Supply voltage : 230 V
50/60 Hz
Protection : 3 A BS 1362 fuse fitted in tap-off
Tap-off ASTA approved : BS EN 60439-2 : 2000
EMC complies with : EN 50090-2-2 : 1997
Climatic condition class : 3K4 (5ºC to 40ºC)
IP rating : 4x
Certification : KNX certified
±
±
n Wall mounting
Wall mounting sensors are supplied with mounting base
Simply ix base to the wall, connect wires to the automatic
wiring block and ix sensor to base
n Settings
Most sensors feature Smart Factory Set technology. Adjustments are
typically not needed after installation
If adjustments need to be made (due to last minute changes in furniture
or ixture placement), sensitivity and time delays should match the
activity levels of the monitored spaces
Hand-held commissioning tool can be used to adjust settings :
This commissioning tool enables a very precise
commissioning of your sensors :
- Time: from 0 seconds to 60 min
- Lux: from 1 lux to 1 275 lux
- Detection mode : presence, presence
walkthrough, absence modes
- PIR and US detection sensibility : low, medium,
high, very high
- Provides access to advanced functions such as
calibration, alarms, choice of mode of detection
(initial detection, maintain detection, retrigger),
daylight function
- Allows downloading, saving and duplication of
sensor parameters
Cat.No FFC021
Presence mode
3'
Walkthrough mode
Absence mode
21
LTK_Bro_019_023 v4.indd 21
23/08/2012 13:56
Lightrak® KNX lighting control system
typical layout and system topology
n KNX system topology schematic diagram
Bus line
(max. 64 LCU)
Bus line
(max. 64 LCU)
Example of typical layout
Repeater
power line
coupler
1.5.64
Main line
powered
line coupler
1.5.128
KNX standard
bus cable
1.1 .0
1.2.0
1.3.0
1.4.0
1.5.0
AREA 1 main bus line
1.5.192
(maximum)
1.15.0 (maximum)
KNX standard bus cable interconnecting
main line powered line coupler
AREA 2 main bus line
AREA 3 main bus line
AREA 4 main bus line
Backbone
powered
line coupler
1.0. –
AREA 15 main bus line (maximum)
1.0.1
Backbone
power supply unit
1.0.2
1.0.3
1.0.4
1.0.15
Backbone bus line
KNX standard bus cable
interconnecting backbone
powered line coupler
n Example of ceiling layout for Lightrak KNX fully addressable system (see opposite)
Layout key
Electrical distribution board and power cabling
Powered line coupler and KNX cabling
Timed event controller
Buscom feed unit and lengths
1/1
Lighting control unit and reference number
Luminaires and sub-cabling
Standard presence detector and CAT 5 sub cabling
Sub-bus interface unit and sub-bus cabling
PIR bus sensor
Dual technology (PIR and ultrasonic) bus sensor
Bus switch
Bus scenario switch
22
LTK_Bro_019_023 v4.indd 22
23/08/2012 14:39
Cat A lighting layout
1/2
5/2
2/2
4/2
3/2
5/1
4/1
3/1
1/1
2/1
6/2
6/1
The left hand area fitted out to Cat B tenant layout
1/5
2/5
3/3
5/2
1/4
4/2
2/4
3/2
1/3
2/3
5/1
1/2
4/1
2/2
3/1
1/1
2/1
6/1
6/2
23
LTK_Bro_019_023 v4.indd 23
22/08/2012 17:47
®
pour exemple
XXXXXXxxxxxx
Electrak
buscom
trunking
xxxxxxxx
2P,
3P, dual circuit and 3 phase systems
SYSTEM
IP RATING
RATING
3 m track
0·5 m spacings
2 m track
0·5 m spacings
3 m track
1·0 m spacings
2 m track
1·0 m spacings
Single sided
BBA3145C
BBA2145C
BBA3141C
BBA2141C
Double sided
BBA3245C
BBA2245C
BBA3241C
BBA2241C
Single sided
CCA3145C
CCA2145C
CCA3141C
CCA2141C
Double sided
CCA3245C
CCA2245C
CCA3241C
CCA2241C
Single sided
BBA3155C
BBA2155C
BBA3151C
BBA2151C
Double sided
BBA3255C
BBA2255C
BBA3251C
BBA2251C
Single sided
CCA3155C
CCA2155C
CCA3151C
CCA2151C
Double sided
CCA3255C
CCA2255C
CCA3251C
CCA2251C
Single sided
BBB3145C
BBB2145C
BBB3141C
BBB2141C
Double sided
BBB3245C
BBB2245C
BBB3241C
BBB2241C
Single sided
CCB3145C
CCB2145C
CCB3141C
CCB2141C
Double sided
CCB3245C
CCB2245C
CCB3241C
CCB2241C
Single sided
BBB3155C
BBB2155C
BBB3151C
BBB2151C
Double sided
BBB3255C
BBB2255C
BBB3251C
BBB2251C
Single sided
CCB3155C
CCB2155C
CCB3151C
CCB2151C
Double sided
CCB3255C
CCB2255C
CCB3251C
CCB2251C
Single sided
BBC3145C
BBC2145C
BBC3141C
BBC2141C
Double sided
BBC3245C
BBC2245C
BBC3241C
BBC2241C
Single sided
CCC3145C
CCC2145C
CCC3141C
CCC2141C
Double sided
CCC3245C
CCC2245C
CCC3241C
CCC2241C
Single sided
BBC3155C
BBC2155C
BBC3151C
BBC2151C
Double sided
BBC3255C
BBC2255C
BBC3251C
BBC2251C
Single sided
CCC3155C
CCC2155C
CCC3151C
CCC2151C
Double sided
CCC3255C
CCC2255C
CCC3251C
CCC2251C
Single sided
BBD3145C
BBD2145C
BBD3141C
BBD2141C
Double sided
BBD3245C
BBD2245C
BBD3241C
BBD2241C
Single sided
CCD3145C
CCD2145C
CCD3141C
CCD2141C
Double sided
CCD3245C
CCD2245C
CCD3241C
CCD2241C
Single sided
BBD3155C
BBD2155C
BBD3151C
BBD2151C
Double sided
BBD3255C
BBD2255C
BBD3251C
BBD2251C
Single sided
CCD3155C
CCD2155C
CCD3151C
CCD2151C
Double sided
CCD3255C
CCD2255C
CCD3251C
CCD2251C
OUTLETS
25 A
IP 4X
40 A
Electrak 30
2P + E system
25 A
IP 54
40 A
25 A
IP 4X
40 A
Electrak 31
3P + E system
25 A
IP 54
40 A
25 A
IP 4X
40 A
Electrak 32
Dual circuit system
25 A
IP 54
40 A
25 A
IP 4X
40 A
Electrak 33
3 phase system
25 A
IP 54
40 A
24
LTK_Bro_024_025 v2.indd 24
22/08/2012 16:16
Centre feed
Suspended feed Suspended feed
unit left hand
unit right hand
Surface feed
unit left hand
Surface feed
unit right hand
Suspended
flexible corner
0·5 m
Suspended
flexible corner
2·0 m
Surface flexible
corner 0·5 m
Surface flexible
corner 2·0 m
BBA44FC
BBA14LFC
BBA14RFC
BBA34LFC
BBA34RFC
BBA140XC
BBA142XC
BBA340XC
BBA342XC
–
BBA24LFC
BBA24RFC
–
–
BBA240XC
BBA242XC
–
–
CCA44FC
CCA14LFC
CCA14RFC
CCA34LFC
CCA34RFC
CCA140XC
CCA142XC
CCA340XC
CCA342XC
–
CCA24LFC
CCA24RFC
–
–
CCA240XC
CCA242XC
–
–
–
BBA15LFC
BBA15RFC
BBA35LFC
BBA35RFC
BBA150XC
BBA152XC
BBA350XC
BBA352XC
–
BBA25LFC
BBA25RFC
–
–
BBA250XC
BBA252XC
–
–
–
CCA15LFC
CCA15RFC
CCA35LFC
CCA35RFC
CCA150XC
CCA152XC
CCA350XC
CCA352XC
–
CCA25LFC
CCA25RFC
–
–
CCA250XC
CCA252XC
–
–
BBB44FC
BBB14LFC
BBB14RFC
BBB34LFC
BBB34RFC
BBB140XC
BBB142XC
BBB340XC
BBB342XC
–
BBB24LFC
BBB24RFC
–
–
BBB240XC
BBB242XC
–
–
CCB44FC
CCB14LFC
CCB14RFC
CCB34LFC
CCB34RFC
CCB140XC
CCB142XC
CCB340XC
CCB342XC
–
CCB24LFC
CCB24RFC
–
–
CCB240XC
CCB242XC
–
–
–
BBB15LFC
BBB15RFC
BBB35LFC
BBB35RFC
BBB150XC
BBB152XC
BBB350XC
BBB352XC
–
BBB25LFC
BBB25RFC
–
–
BBB250XC
BBB252XC
–
–
–
CCB15LFC
CCB15RFC
CCB35LFC
CCB35RFC
CCB150XC
CCB152XC
CCB350XC
CCB352XC
–
CCB25LFC
CCB25RFC
–
–
CCB250XC
CCB252XC
–
–
BBC44FC
BBC14LFC
BBC14RFC
BBC34LFC
BBC34RFC
BBC140XC
BBC142XC
BBC340XC
BBC342XC
–
BBC24LFC
BBC24RFC
–
–
BBC240XC
BBC242XC
–
–
CCC44FC
CCC14LFC
CCC14RFC
CCC34LFC
CCC34RFC
CCC140XC
CCC142XC
CCC340XC
CCC342XC
–
CCC24LFC
CCC24RFC
–
–
CCC240XC
CCC242XC
–
–
–
BBC15LFC
BBC15RFC
BBC35LFC
BBC35RFC
BBC150XC
BBC152XC
BBC350XC
BBC352XC
–
BBC25LFC
BBC25RFC
–
–
BBC250XC
BBC252XC
–
–
–
CCC15LFC
CCC15RFC
CCC35LFC
CCC35RFC
CCC150XC
CCC152XC
CCC350XC
CCC352XC
–
CCC25LFC
CCC25RFC
–
–
CCC250XC
CCC252XC
–
–
BBD44FC
BBD14LFC
BBD14RFC
BBD34LFC
BBD34RFC
BBD140XC
BBD142XC
BBD340XC
BBD342XC
–
BBD24LFC
BBD24RFC
–
–
BBD240XC
BBD242XC
–
–
CCD44FC
CCD14LFC
CCD14RFC
CCD34LFC
CCD34RFC
CCD140XC
CCD142XC
CCD340XC
CCD342XC
–
CCD24LFC
CCD24RFC
–
–
CCD240XC
CCD242XC
–
–
–
BBD15LFC
BBD15RFC
BBD35LFC
BBD35RFC
BBD150XC
BBD152XC
BBD350XC
BBD352XC
–
BBD25LFC
BBD25RFC
–
–
BBD250XC
BBD252XC
–
–
–
CCD15LFC
CCD15RFC
CCD35LFC
CCD35RFC
CCD150XC
CCD152XC
CCD350XC
CCD352XC
–
CCD25LFC
CCD25RFC
–
–
CCD250XC
CCD252XC
–
–
25
LTK_Bro_024_025 v2.indd 25
22/08/2012 16:16
®
pour exemple
XXXXXXxxxxxx
Electrak
buscom
trunking
xxxxxxxx
tap-offs
Rewirable
0·8 m
2m
3m
5m
–
DDE408FC
DDE42FC
DDE43FC
DDE45FC
DDF4F
DDE408F
DDE42F
DDE43F
DDE45F
IP RATING
PHASE
With comms
L+ N
Electrak 30
2P + E system
SYSTEM
13 A FUSED TAP-OFFS
IP 4X
No comms
With comms
–
DDE508FC
DDE52FC
DDE53FC
DDE55FC
DDF5F
DDE508F
DDE52F
DDE53F
DDE55F
–
DDE408FC
DDE42FC
DDE43FC
DDE45FC
IP 54
No comms
With comms
L1 N
No comms
With comms
No comms
With comms
No comms
With comms
DDE42F
DDE43F
DDE45F
DDE508FC
DDE52FC
DDE53FC
DDE55FC
DDF5F
DDE508F
DDE52F
DDE53F
DDE55F
–
DDG408FC
DDG42FC
DDG43FC
DDG45FC
L1 N1
DDH4F
DDG408F
DDG42F
DDG43F
DDG45F
–
DDG508FC
DDG52FC
DDG53FC
DDG55FC
DDH5F
DDG508F
DDG52F
DDG53F
DDG55F
–
DDE408FC
DDE42FC
DDE43FC
DDE45FC
IP 54
With comms
IP 4X
No comms
With comms
DDF4F
DDE408F
DDE42F
DDE43F
DDE45F
–
DDE508FC
DDE52FC
DDE53FC
DDE55FC
DDF5F
DDE508F
DDE52F
DDE53F
DDE55F
–
DDJ408FC
DDJ42FC
DDJ43FC
DDJ45FC
IP 54
No comms
With comms
L2 N2
Electrak 32
DDE408F
–
IP 4X
No comms
Dual circuit system
DDF4F
IP 54
L1 L2 N
Electrak 31
3P + E system
IP 4X
IP 4X
No comms
With comms
DDK4F
DDJ408F
DDJ42F
DDJ43F
DDJ45F
–
DDJ508FC
DDJ52FC
DDJ53FC
DDJ55FC
DDK5F
DDJ508F
DDJ52F
DDJ53F
DDJ55F
IP 54
No comms
With comms
L1 N
IP 4X
No comms
With comms
IP 54
No comms
L2 N
With comms
IP 4X
With comms
No comms
With comms
DDM408L1FC
DDM42L1FC
DDM43L1FC
DDM45L1FC
DDM408L1F
DDM42L1F
DDM43L1F
DDM45L1F
–
DDM508L1FC
DDM52L1FC
DDM53L1FC
DDM55L1FC
DDN5L1F
DDM508L1F
DDM52L1F
DDM53L1F
DDM55L1F
–
DDM408L2FC
DDM42L2FC
DDM43L2FC
DDM45L2FC
DDN4L2F
DDM408L2F
DDM42L2F
DDM43L2F
DDM45L2F
–
DDM508L2FC
DDM52L2FC
DDM53L2FC
DDM55L2FC
DDN5L2F
DDM508L2F
DDM52L2F
DDM53L2F
DDM55L2F
–
DDM408L3FC
DDM42L3FC
DDM43L3FC
DDM45L3FC
DDN4L3F
DDM408L3F
DDM42L3F
DDM43L3F
DDM45L3F
–
DDM508L3FC
DDM52L3FC
DDM53L3FC
DDM55L3FC
DDN5L3F
DDM508L3F
DDM52L3F
DDM53L3F
DDM55L3F
–
–
–
–
–
DDP4SF
–
–
–
–
–
–
–
–
–
L3 N
IP 4X
No comms
With comms
IP 54
No comms
L+L+L+N
Phase
selectable
Electrak 33
IP 54
3 phase system
No comms
–
DDN4L1F
With comms
IP 4X
No comms
With comms
IP 54
DDP5SF
–
–
–
–
With comms
No comms
–
–
–
–
–
No comms
–
–
–
–
–
With comms
–
–
–
–
–
No comms
–
–
–
–
–
IP 4X
IP 54
26
LTK_Bro_026_027 v2.indd 26
22/08/2012 16:17
16 A UNFUSED TAP-OFFS
Rewirable
0·8 m
2m
3m
5m
–
DDE408C
DDE42C
DDE43C
DDE45C
DDF4
DDE408
DDE42
DDE43
DDE45
–
DDE508C
DDE52C
DDE53C
DDE55C
DDF5
DDE508
DDE52
DDE53
DDE55
–
DDE408C
DDE42C
DDE43C
DDE45C
DDF4
DDE408
DDE42
DDE43
DDE45
–
DDE508C
DDE52C
DDE53C
DDE55C
DDF5
DDE508
DDE52
DDE53
DDE55
–
DDG408C
DDG42C
DDG43C
DDG45C
DDH4
DDG408
DDG42
DDG43
DDG45
–
DDG508C
DDG52C
DDG53C
DDG55C
DDH5
DDG508
DDG52
DDG53
DDG55
–
DDE408C
DDE42C
DDE43C
DDE45C
DDF4
DDE408
DDE42
DDE43
DDE45
–
DDE508C
DDE52C
DDE53C
DDE55C
DDF5
DDE508
DDE52
DDE53
DDE55
–
DDJ408C
DDJ42C
DDJ43C
DDJ45C
DDK4
DDJ408
DDJ42
DDJ43
DDJ45
–
DDJ508C
DDJ52C
DDJ53C
DDJ55C
DDK5
DDJ508
DDJ52
DDJ53
DDJ55
–
DDM408L1C
DDM42L1C
DDM43L1C
DDM45L1C
DDN4L1
DDM408L1
DDM42L1
DDM43L1
DDM45L1
–
DDM508L1C
DDM52L1C
DDM53L1C
DDM55L1C
DDN5L1
DDM508L1
DDM52L1
DDM53L1
DDM55L1
–
DDM408L2C
DDM42L2C
DDM43L2C
DDM45L2C
DDN4L2
DDM408L2
DDM42L2
DDM43L2
DDM45L2
–
DDM508L2C
DDM52L2C
DDM53L2C
DDM55L2C
DDN5L2
DDM508L2
DDM52L2
DDM53L2
DDM55L2
–
DDM408L3C
DDM42L3C
DDM43L3C
DDM45L3C
DDN4L3
DDM408L3
DDM42L3
DDM43L3
DDM45L3
–
DDM508L3C
DDM52L3C
DDM53L3C
DDM55L3C
DDN5L3
DDM508L3
DDM52L3
DDM53L3
DDM55L3
–
–
–
–
–
DDP4S
–
–
–
–
–
–
–
–
–
DDP5S
–
–
–
–
–
–
–
–
–
–
DDR408
DDR42
DDR43
DDR45
–
–
–
–
–
–
DDR508
DDR52
DDR53
DDR55
27
LTK_Bro_026_027 v2.indd 27
22/08/2012 16:17
Electrak® 30 2P + E buscom trunking
power and communication distribution
CCA3145C
CCA2145C
CCA14RFC
CCA142XC
CCA14LFC
Selection chart (p. 24-27)
Dimensions and technical information (p. 38-43)
Integral communication bus suitable for KNX, Lonworks, DALI protocols, etc. 25 A and 40 A systems
Outlets on one or two sides. IP 4X or IP 54 ingress protection
Fast installation (trunking push fits together in seconds). High quality materials. Suspended or surface mounted
Pack
Cat. Nos.
Electrak 30
2 P + E + comms – single sided system
Pack
Cat. Nos.
2P + E buscom trunking system with integral
communications bus circuit available in IP 4X
and IP 54 versions
Socket outlets are colour coded white and are
located on just one side of the bar
2P + E trunking lengths
Trunking lengths push fit into each other, and
feed units or flexible lengths. Trunking lengths
can be surface mounted or suspended using the
various bracket options
1
1
1
1
1
1
1
1
25 A
BBA3145C
BBA2145C
BBA3141C
BBA2141C
40 A
CCA3145C
CCA2145C
CCA3141C
CCA2141C
Length
(m)
Tap-off
outlets
Weight
(kg)(1)
3
2
3
2
6
4
3
2
4·47
3·27
4·42
3·24
3
2
3
2
6
4
3
2
4·57
3·36
4·52
3·31
C
Flexible lengths for single sided system
Flexible lengths can be used to change
direction, change level or overcome
obstructions
Suspended – right to left
1
1
1
1
BBA140XC
BBA142XC
CCA140XC
CCA142XC
Length
(m)
Rating
(A)
Weight
(kg)(1)
0·5
2
0·5
2
25
25
40
40
2·91
3·21
2·94
3·33
Surface mounted – right to left
1
1
1
1
BBA340XC
BBA342XC
CCA340XC
CCA342XC
Length
(m)
Rating
(A)
Weight
(kg)(1)
0·5
2
0·5
2
25
25
40
40
2·99
3·05
3·02
3·41
L
N
PE
Feed units for single sided system
Feed units come with 2 x 25 mm Ø and
2 x 16 mm Ø cable entry holes and single screw
cable terminals for power and data
Left feed units are supplied with right end stop
Right feed units are supplied with left end stop
Centre feed units are supplied with right and left
end stops
Suspended
Weight
(kg)(1)
1
1
1
1
BBA14LFC
BBA14RFC
CCA14LFC
CCA14RFC
25 A left
25 A right
40 A left
40 A right
1·22
1·49
1·27
1·49
Surface mounted
Weight
(kg)(1)
1
1
1
1
BBA34LFC
BBA34RFC
CCA34LFC
CCA34RFC
25 A left
25 A right
40 A left
40 A right
1·31
1·54
1·31
1·54
Centre feed
Weight
(kg)(1)
1
1
BBA44FC
CCA44FC
25 A
40 A
1·8
1·8
(1) Weights shown are for IP 4X rated buscom. For all other
weights, contact us on +44 (0) 845 600 6266
Key : How to select the correct components
All examples on this page show IP 4X buscom trunking
IP rating is dictated by the red letters
4 = IP 4X. For IP 54 version, replace 4 with 5
28
LTK_Bro_028_029 v3.indd 28
23/08/2012 13:58
Electrak® 30 2P + E buscom trunking
power and communication distribution
CCA3245C
CCA2245C
DDE45
DDE45C
DDF4F
Selection chart (p. 24-27)
Dimensions and technical information (p. 38-43)
Integral communication bus suitable for KNX, Lonworks, DALI protocols, etc. 25 A and 40 A systems
Outlets on one or two sides. IP 4X or IP 54 ingress protection
Fast installation (trunking push fits together in seconds). High quality materials. Suspended or surface mounted
Pack
Cat. Nos.
Electrak 30
2 P + E + comms – double sided system
Pack
Cat. Nos.
2P + E buscom trunking system with integral
communications bus circuit available in IP 4X
and IP 54 versions
Socket outlets are colour coded white and are
located on both sides of the bar
The comms circuit is only available on one side
of the bar as shown in the diagram below
2P + E trunking lengths
Trunking lengths push fit into each other, and
feed units or flexible lengths. Double sided
trunking must be fixed using suspended fixing
brackets
1
1
1
1
1
1
1
1
25 A
BBA3245C
BBA2245C
BBA3241C
BBA2241C
40 A
CCA3245C
CCA2245C
CCA3241C
CCA2241C
Length
(m)
Tap-off
outlets
Weight
(kg)(1)
3
2
3
2
11
7
6
4
4·85
3·52
4·70
3·47
3
2
3
2
11
7
6
4
PE
N
L
Pre-wired tap-off units to pick-up L1+N, colour
coded white
Length
(m)
1
1
1
1
DDE408C
DDE42C
DDE43C
DDE45C
5·05
3·65
4·96
3·61
0·8
2
3
5
Fixed
polarity
Weight
(kg)(1)
L+N
0·2
0·4
0·5
0·7
13 A fused tap-off units
Pre-wired tap-off units to pick-up L1+N, supplied
with BS 1362 fuse, colour coded white
C
L
N
PE
Tap-off units with and without comms
Power only tap-offs can plug into any tap-off outlet
Tap-offs with comms can only be plugged into the
comms side of the bar
16 A unfused tap-off units
1
1
1
1
DDE408FC
DDE42FC
DDE43FC
DDE45FC
Length
(m)
Fixed
polarity
Weight
(kg)(1)
0·8
2
3
5
L+N
0·2
0·4
0·5
0·7
Tap-off units without comms – rewirable
16 A unfused tap-off unit
Feed units for double sided system
Double sided feed units come with 2 x 25 mm Ø
cable entry holes for each side of the bar, plus a
further 2 x 16 mm Ø. holes for the comms side of
the bar
Single screw cable terminals are provided for
power and data. Supplied with end stops
Rewirable tap-off unit to pick-up L1+N, colour
coded white, can plug into any tap-off outlet
1
DDF4
25 A left
25 A right
40 A left
40 A right
1·29
1·51
1·39
1·61
1
Flexible lengths for double sided system
Flexible lengths can be used to change
direction, change level or overcome obstructions
Suspended – right to left
1
1
1
1
BBA240XC
BBA242XC
CCA240XC
CCA242XC
Length
(m)
Rating
(A)
Weight
(kg)(1)
0·5
2
0·5
2
25
25
40
40
3·14
3·67
3·25
3·91
L+N
0·14
Rewirable tap-off unit to pick-up L1+N, supplied
with BS 1362 fuse, colour coded white, can plug
into any tap-off outlet
Weight(kg)(1)
BBA24LFC
BBA24RFC
CCA24LFC
CCA24RFC
Weight
(kg)(1)
13 A fused tap-off unit
Suspended
1
1
1
1
Fixed
polarity
DDF4F
Fixed
polarity
Weight
(kg)(1)
L+N
0·14
(1) Weights shown are for IP 4X rated buscom. For all other
weights, contact us on +44 (0) 845 600 6266
Key : How to select the correct components
All examples on this page show IP 4X buscom trunking
IP rating and tap-off type is dictated by the red letters
4 = IP 4X. For IP 54 version, replace 4 with 5
C = Tap-off with communications circuit
For power only, remove the C
29
LTK_Bro_028_029 v3.indd 29
22/08/2012 16:18
Electrak® 31 3P + E buscom trunking
power and communication distribution
CCB3145C
CCB2145C
CCB14RFC
CCB142XC
CCB14LFC
Selection chart (p. 24-27)
Dimensions and technical information (p. 38-43)
Integral communication bus suitable for KNX, Lonworks, DALI, protocols etc. 25 A and 40 A systems
Outlets on one or two sides. IP 4X or IP 54 ingress protection
Fast installation (trunking push fits together in seconds). High quality materials. Suspended or surface mounted
Pack
Cat. Nos.
Electrak 31
3P + E – single sided system
Pack
Cat. Nos.
Flexible lengths can be used to change
direction, change level or overcome
obstructions
3P + E buscom trunking system with integral
communications bus circuit available in IP 4X
and IP 54 versions
Socket outlets are colour coded white and are
located on just one side of the bar
3P + E trunking lengths
Trunking lengths push fit into each other, and
feed units or flexible lengths. Trunking lengths
can be surface mounted or suspended using the
various bracket options
1
1
1
1
1
1
1
1
25 A
BBB3145C
BBB2145C
BBB3141C
BBB2141C
40 A
CCB3145C
CCB2145C
CCB3141C
CCB2141C
Length
(m)
Tap-off
outlets
Weight
(kg)(1)
3
2
3
2
6
4
3
2
4·62
3·37
4·58
3·34
3
2
3
2
6
4
3
2
4·77
3·47
4·73
3·44
C
L2
L1
N
PE
Flexible lengths for single sided system
Suspended – right to left
1
1
1
1
BBB140XC
BBB142XC
CCB140XC
CCB142XC
Length
(m)
Rating
(A)
Weight
(kg)(1)
0·5
2
0·5
2
25
25
40
40
3·04
3·40
3·08
3·56
Surface mounted – right to left
1
1
1
1
BBB340XC
BBB342XC
CCB340XC
CCB342XC
Length
(m)
Rating
(A)
Weight
(kg)(1)
0·5
2
0·5
2
25
25
40
40
2·99
3·32
3·00
3·48
Feed units for single sided system
Feed units come with 2 x 25 mm Ø and
2 x 16 mm Ø cable entry holes and single screw
cable terminals for power and data
Left feed units are supplied with right end stop
Right feed units are supplied with left end stop
Centre feed units are supplied with right and left
end stops
Suspended
Weight
(kg)(1)
1
1
1
1
BBB14LFC
BBB14RFC
CCB14LFC
CCB14RFC
25 A left
25 A right
40 A left
40 A right
1·25
1·48
1·33
1·55
Surface mounted
Weight
(kg)(1)
1
1
1
1
BBB34LFC
BBB34RFC
CCB34LFC
CCB34RFC
25 A left
25 A right
40 A left
40 A right
1·29
1·52
1·37
1·59
Centre feed
Weight
(kg)(1)
1
1
BBB44FC
CCB44FC
25 A
40 A
1·8
1·8
(1) Weights shown are for IP 4X rated buscom. For all other
weights, contact us on +44 (0) 845 600 6266
Key : How to select the correct components
All examples on this page show IP 4X buscom trunking
IP rating is dictated by the red letters
4 = IP 4X. For IP 54 version, replace 4 with 5
30
LTK_Bro_030_031 v3.indd 30
23/08/2012 14:05
Electrak® 31 3P + E buscom trunking
power and communication distribution
CCB3245C
CCB2245C
DDE45
DDE45C
DDH4F
Selection chart (p. 24-27)
Dimensions and technical information (p. 38-43)
Integral communication bus suitable for KNX, Lonworks, DALI protocols,
etc. 25 A and 40 A systems
Outlets on one or two sides. IP 4X or IP 54 ingress protection
Fast installation (trunking push fits together in seconds). High quality
materials. Suspended or surface mounted
Pack
Cat. Nos.
Trunking lengths push fit into each other, and feed
units or flexible lengths. Double sided trunking
must be fixed using suspended fixing brackets
1
1
1
1
Length
(m)
Tap-off
outlets
Weight
(kg)(1)
3
2
3
2
11
7
6
4
5·15
3·72
5·06
3·68
3
2
3
2
11
7
6
4
5·45
3·92
5·36
3·88
Length
(m)
1
1
1
1
1
1
1
1
DDE408C
DDE42C
DDE43C
DDE45C
DDG408C
DDG42C
DDG43C
DDG45C
PE
N
L1
L2
C
L2
L1
N
PE
Suspended
Weight (kg)(1)
25 A left
25 A right
40 A left
40 A right
Length
(m)
1
1
1
1
1
1
1
1
DDE408FC
DDE42FC
DDE43FC
DDE45FC
DDG408FC
DDG42FC
DDG43FC
DDG45FC
0·8
2
3
5
0·8
2
3
5
Fixed
polarity
L+N
L1 + L2 + N
Weight
(kg)(1)
0·2
0·4
0·5
0·7
0·2
0·4
0·5
0·7
Tap-off units without comms – rewirable
1
1
DDF4
DDH4
Fixed
polarity
Weight
(kg)(1)
L+N
L1 L2 N1
0·14
0·14
13 A fused tap-off unit
Rewirable tap-off units supplied with BS 1362
fuse, colour coded white, can plug into any
tap-off outlet
Flexible lengths can be used to change
direction, change level or overcome obstructions
Suspended – right to left
BBB240XC
BBB242XC
CCB240XC
CCB242XC
L1 + L2 + N
0·2
0·4
0·5
0·7
0·2
0·4
0·5
0·7
16 A unfused tap-off unit
Rewirable tap-off units colour coded white, can
plug into any tap-off outlet
1·35
1·58
1·49
1·72
Flexible lengths for double sided system
1
1
1
1
L+N
Weight
(kg)(1)
Pre-wired tap-off units to pick-up L1, L2+N,
supplied with BS 1362 fuse, colour coded white
Feed units for double sided system
BBB24LFC
BBB24RFC
CCB24LFC
CCB24RFC
0·8
2
3
5
0·8
2
3
5
Fixed
polarity
13 A fused tap-off units
Double sided feed units come with 2 x 25 mm Ø
cable entry holes for each side of the bar, plus
a further 2 x 16 mm Ø. holes for the comms side
of the bar. Single screw cable terminals are
provided for power and data
1
1
1
1
Tap-off units with and without comms
Power only tap-offs can plug into any tap-off outlet
Tap-offs with comms can only be plugged into the
comms side of the bar
16 A unfused tap-off units
Pre-wired tap-off units to pick up L1, L2+N,
colour coded white
3P + E trunking lengths
25 A
BBB3245C
BBB2245C
BBB3241C
BBB2241C
40 A
CCB3245C
CCB2245C
CCB3241C
CCB2241C
Cat. Nos.
Electrak 31
3P + E – double sided system
3P + E buscom trunking system with integral
communications bus circuit available in IP 4X
and IP 54 versions
Socket outlets are colour coded white and are
located on both sides of the bar
The comms circuit is only available on one side
of the bar as shown in the diagram below
1
1
1
1
Pack
Length
(m)
Rating
(A)
Weight
(kg)(1)
0·5
2
0·5
2
25
25
40
40
3·45
4·03
3·53
4·35
1
1
DDF4F
DDH4F
Fixed
polarity
Weight
(kg)(1)
L+N
L1 L2 N1
0·14
0·14
(1) Weights shown are for IP 4X rated buscom. For all other
weights, contact us on +44 (0) 845 600 6266
Key : How to select the correct components
All examples on this page show IP 4X buscom trunking
IP rating and tap-off type is dictated by the red letters
4 = IP 4X. For IP 54 version, replace 4 with 5
C = Tap-off with communications circuit. For power only, remove the C
31
LTK_Bro_030_031 v3.indd 31
22/08/2012 16:20
Electrak® 32 4P + E (dual circuit) buscom trunking
power and communication distribution
CCC3145C
CCC2145C
CCC14RFC
CCC142XC
CCC14LFC
Selection chart (p. 24-27)
Dimensions and technical information (p. 38-43)
Integral communication bus suitable for KNX, Lonworks, DALI protocols, etc. 25 A and 40 A systems
Outlets on one or two sides. IP 4X or IP 54 ingress protection
Fast installation (trunking push fits together in seconds). High quality materials. Suspended or surface mounted
Pack
Cat. Nos.
Electrak 32
4P + E (dual circuit) – single sided system
Pack
Cat. Nos.
Flexible lengths can be used to change
direction, change level or overcome
obstructions
Dual circuit buscom trunking system with integral
communications bus circuit available in IP 4X
and IP 54 versions
Socket outlets are colour coded white and are
located on just one side of the bar
4 P + E trunking lengths
Trunking lengths push fit into each other, and
feed units or flexible lengths. Trunking lengths
can be surface mounted or suspended using the
various bracket options
1
1
1
1
1
1
1
1
25 A
BBC3145C
BBC2145C
BBC3141C
BBC2141C
40 A
CCC3145C
CCC2145C
CCC3141C
CCC2141C
Length
(m)
Tap-off
outlets
Weight
(kg)(1)
3
2
3
2
6
4
3
2
4·77
3·47
4·73
3·44
3
2
3
2
6
4
3
2
4·97
3·61
4·93
3·58
C
L2
N2
L1
N1
PE
Flexible lengths for single sided system
Suspended – right to left
1
1
1
1
BBC140XC
BBC142XC
CCC140XC
CCC142XC
Length
(m)
Rating
(A)
Weight
(kg)(1)
0·5
2
0·5
2
25
25
40
40
3·17
3·59
3·22
3·79
Surface mounted – right to left
1
1
1
1
BBC340XC
BBC342XC
CCC340XC
CCC342XC
Length
(m)
Rating
(A)
Weight
(kg)(1)
0·5
2
0·5
2
25
25
40
40
3·09
3·51
3·14
3·71
Feed units for single sided system
Feed units come with 2 x 25 mm Ø and
2 x 16 mm Ø cable entry holes and single screw
cable terminals for power and data
Left feed units are supplied with right end stop
Right feed units are supplied with left end stop
Centre feed units are supplied with right and left
end stops
Suspended
Weight
(kg)(1)
1
1
1
1
BBC14LFC
BBC14RFC
CCC14LFC
CCC14RFC
25 A left
1·29
25 A right
1·52
40 A left
1·38
40 A right
1·61
Surface mounted
Weight
(kg)(1)
1
1
1
1
BBC34LFC
BBC34RFC
CCC34LFC
CCC34RFC
25 A left
25 A right
40 A left
40 A right
Centre feed
1·33
1·56
1·42
1·65
Weight
(kg)(1)
1
1
BBC44FC
CCC44FC
25 A
40 A
1·8
1·8
(1) Weights shown are for IP 4X rated buscom. For all other
weights, contact us on +44 (0) 845 600 6266
Key : How to select the correct components
All examples on this page show IP 4X buscom trunking
IP rating is dictated by the red letters
4 = IP 4X. For IP 54 version, replace 4 with 5
32
LTK_Bro_032_033 v3.indd 32
23/08/2012 14:06
Electrak® 32 4P + E (dual circuit) buscom trunking
power and communication distribution
CCC3245C
CCC2245C
DDJ45
DDJ45C
DDK4F
Selection chart (p. 24-27)
Dimensions and technical information (p. 38-43)
Integral communication bus suitable for KNX, Lonworks, DALI protocols,
etc. 25 A and 40 A systems
Outlets on one or two sides. IP 4X or IP 54 ingress protection
Fast installation (trunking push fits together in seconds). High quality
materials. Suspended or surface mounted
Pack
Cat. Nos.
4 P + E trunking lengths
Trunking lengths push fit into each other, and
feed units or flexible lengths. Double sided
trunking must be fixed using suspended fixing
brackets
1
1
1
1
25 A
BBC3245C
BBC2245C
BBC3241C
BBC2241C
40 A
CCC3245C
CCC2245C
CCC3241C
CCC2241C
Length
(m)
Tap-off
outlets
Weight
(kg)(1)
3
2
3
2
11
7
6
4
5·46
3·92
5·37
3·88
3
2
3
2
11
7
6
4
5·86
4·70
5·77
4·15
BBC24LFC
BBC24RFC
CCC24LFC
CCC24RFC
PE
N1
L1
N2
L2
C
L2
N2
L1
N1
PE
DDE408C
DDE42C
DDE43C
DDE45C
DDJ408C
DDJ42C
DDJ43C
DDJ45C
0·8
2
3
5
0·8
2
3
5
Fixed
polarity
L1 + N1
L2 + N2
Weight
(kg)(1)
0·2
0·4
0·5
0·6
0·2
0·4
0·5
0·6
13 A fused tap-off units
Pre-wired tap-off units to pick up L1+N1 or L2+N2,
supplied with BS 1362 fuse, colour coded white
1
1
1
1
1
1
1
1
DDE408FC
DDE42FC
DDE43FC
DDE45FC
DDJ408FC
DDJ42FC
DDJ43FC
DDJ45FC
0·8
2
3
5
0·8
2
3
5
Fixed
polarity
L1 + N1
L2 + N2
Weight
(kg)(1)
0·2
0·4
0·5
0·6
0·2
0·4
0·5
0·6
Feed units for double sided system
Tap-off units without comms – rewirable
16 A unfused tap-off units
Rewirable tap-off units to pick up required
circuit, colour coded white, can plug into any
tap-off outlet
25 A left
25 A right
40 A left
40 A right
1
1
DDF4
DDK4
Fixed
polarity
Weight
(kg)(1)
L1 + N1
L2 + N2
0·14
0·14
13 A fused tap-off units
Rewirable tap-off units to pick up required
circuit, supplied with BS 1362 fuse, colour coded
white, can plug into any tap-off outlet
1·42
1·64
1·60
1·83
Flexible lengths can be used to change
direction, change level or overcome obstructions
Suspended – right to left
BBC240XC
BBC242XC
CCC240XC
CCC242XC
Length
(m)
1
1
1
1
1
1
1
1
Double sided feed units come with 2 x 25 mm Ø
cable entry holes for each side of the bar, plus
a further 2 x 16 mm Ø. holes for the comms side
of the bar. Single screw cable terminals are
provided for power and data
Supplied with end stops
Suspended
Flexible lengths for double sided system
1
1
1
1
Tap-off units with and without comms
Power only tap-offs can plug into any tap-off outlet
Tap-offs with comms can only be plugged into the
comms side of the bar
16 A unfused tap-off units
Pre-wired tap-off units to pick up L1+N1 or
L2+N2, colour coded white
Length
(m)
Weight
(kg)(1)
1
1
1
1
Cat. Nos.
Electrak 32
4P + E (dual circuit) – double sided system
Dual circuit buscom trunking system with integral
communications bus circuit available in IP 4X
and IP 54 versions
Socket outlets are colour coded white and are
located on both sides of the bar
The comms circuit is only available on one side
of the bar as shown in the diagram below
1
1
1
1
Pack
Length
(m)
Rating
(A)
Weight
(kg)(1)
0·5
2
0·5
2
25
25
40
40
3·42
4·52
3·91
5·32
1
1
DDF4F
DDK4F
Fixed
polarity
Weight
(kg)(1)
L1 + N1
L2 + N2
0·14
0·14
(1) Weights shown are for IP 4X rated buscom. For all other
weights, contact us on +44 (0) 845 600 6266
Key : How to select the correct components
All examples on this page show IP 4X buscom trunking
IP rating and tap-off type is dictated by the red letters
4 = IP 4X. For IP 54 version, replace 4 with 5
C = Tap-off with communications circuit. For power only, remove the C
33
LTK_Bro_032_033 v3.indd 33
22/08/2012 16:21
Electrak® 33 4P + E (3 phase) buscom trunking
power and communication distribution
CCD3145C
CCD2145C
CCD14RFC
CCD142XC
CCD14LFC
Selection chart (p. 24-27)
Dimensions and technical information (p. 38-43)
Integral communication bus suitable for KNX, Lonworks, DALI protocols, etc. 25 A and 40 A systems
Outlets on one or two sides. IP 4X or IP 54 ingress protection
Fast installation (trunking push fits together in seconds). High quality materials. Suspended or surface mounted
Pack
Cat. Nos.
Electrak 33
4P + E (3 phase) – single sided system
Pack
Cat. Nos.
3 phase buscom trunking system with integral
communications bus circuit available in IP 4X
and IP 54 versions
Socket outlets are colour coded grey and are
located on just one side of the bar
4 P + E trunking lengths
Trunking lengths push fit into each other, and
feed units or flexible lengths. Trunking lengths
can be surface mounted or suspended using the
various bracket options
1
1
1
1
1
1
1
1
25 A
BBD3145C
BBD2145C
BBD3141C
BBD2141C
40 A
CCD3145C
CCD2145C
CCD3141C
CCD2141C
Length
(m)
Tap-off
outlets
Weight
(kg)(1)
3
2
3
2
6
4
3
2
4·77
3·47
4·75
3·44
3
2
3
2
6
4
3
2
4·97
3·61
4·93
3·58
C
L3
L2
L1
N1
PE
Flexible lengths for single sided system
Flexible lengths can be used to change
direction, change level or overcome
obstructions
Suspended – right to left
1
1
1
1
BBD140XC
BBD142XC
CCD140XC
CCD142XC
Length
(m)
Rating
(A)
Weight
(kg)(1)
0·5
2
0·5
2
25
25
40
40
3·17
3·59
3·22
3·79
Surface mounted – right to left
1
1
1
1
BBD340XC
BBD342XC
CCD340XC
CCD342XC
Length
(m)
Rating
(A)
Weight
(kg)(1)
0·5
2
0·5
2
25
25
40
40
3·09
3·51
3·14
3·71
Feed units for single sided system
Feed units come with 2 x 25 mm Ø and
2 x 16 mm Ø cable entry holes and single screw
cable terminals for power and data
Left feed units are supplied with right end stop
Right feed units are supplied with left end stop
Centre feed units are supplied with right and left
end stops
Suspended
Weight
(kg)(1)
1
1
1
1
BBD14LFC
BBD14RFC
CCD14LFC
CCD14RFC
25 A left
1·29
25 A right
1·52
40 A left
1·38
40 A right
1·61
Surface mounted
Weight
(kg)(1)
1
1
1
1
BBD34LFC
BBD34RFC
CCD34LFC
CCD34RFC
25 A left
25 A right
40 A left
40 A right
Centre feed
1·33
1·56
1·42
1·65
Weight
(kg)(1)
1
1
BBD44FC
CCD44FC
25 A
40 A
1·80
1·80
(1) Weights shown are for IP 4X rated buscom. For all other
weights, contact us on +44 (0) 845 600 6266
Key : How to select the correct components
All examples on this page show IP 4X buscom trunking
IP rating is dictated by the red letters
4 = IP 4X. For IP 54 version, replace 4 with 5
34
LTK_Bro_034_036 v2.indd 34
23/08/2012 14:07
Electrak® 33 4P + E (3 phase) buscom trunking
power and communication distribution
CCD3245C
CCD2245C
DDM408L1C
DDM408L1
Selection chart (p. 24-27)
Dimensions and technical information (p. 38-43)
Integral communication bus suitable for KNX, Lonworks, DALI protocols, etc. 25 A and 40 A systems
Outlets on one or two sides. IP 4X or IP 54 ingress protection
Fast installation (trunking push fits together in seconds). High quality materials. Suspended or surface mounted
Pack
Cat. Nos.
Electrak 33
4P + E (3 phase) – double sided system
Pack
Cat. Nos.
3 phase buscom trunking system with integral
communications bus circuit available in IP 4X
and IP 54 versions
Socket outlets are colour coded grey and are
located on both sides of the bar
The comms circuit is only available on one side
of the bar as shown in the diagram below
Pre-wired tap-off units to pick up required circuit,
colour coded grey
Length
(m)
4 P + E trunking lengths
Trunking lengths push fit into each other, and
feed units or flexible lengths. Double sided
trunking must be fixed using suspended fixing
brackets
1
1
1
1
1
1
1
1
25 A
BBD3245C
BBD2245C
BBD3241C
BBD2241C
40 A
CCD3245C
CCD2245C
CCD3241C
CCD2241C
Length
(m)
Tap-off
outlets
Weight
(kg)(1)
3
2
3
2
11
7
6
4
5·46
3·92
5·37
3·88
3
2
3
2
11
7
6
4
5·86
4·70
5·77
4·15
PE
N
L1
L2
L3
C
L3
L2
L1
N
PE
1
1
1
1
1
1
1
1
1
1
1
1
DDM408L1C
DDM42L1C
DDM43L1C
DDM45L1C
DDM408L2C
DDM42L2C
DDM43L2C
DDM45L2C
DDM408L3C
DDM42L3C
DDM43L3C
DDM45L3C
Double sided feed units come with 2 x 25 mm Ø
cable entry holes for each side of the bar, plus
a further 2 x 16 mm Ø. holes for the comms side
of the bar. Single screw cable terminals are
provided for power and data
Suspended
BBD24LFC
BBD24RFC
CCD24LFC
CCD24RFC
25 A left
25 A right
40 A left
40 A right
1·42
1·64
1·60
1·83
Flexible lengths for double sided system
Flexible lengths can be used to change
direction, change level or overcome obstructions
Fixed
polarity
L1 + N
L2 + N
L3 + N
Weight
(kg)(1)
0·2
0·4
0·5
0·6
0·2
0·4
0·5
0·6
0·2
0·4
0·5
0·6
Pre-wired tap-off units to pick up required circuit,
supplied with BS 1362 fuse, colour coded grey,
can plug into any
Electrak 33 tap-off outlet
Length
(m)
1
1
1
1
1
1
1
1
Weight
(kg)(1)
0·8
2
3
5
0·8
2
3
5
0·8
2
3
5
13 A fused tap-off units
Feed units for double sided system
1
1
1
1
Tap-off units
Power only tap-offs can plug into any tap-off outlet
of the 3 phase bar
Tap-offs with comms can only be plugged into the
comms side of the 3 phase bar
16 A unfused tap-off units
1
1
1
1
DDM408L1FC
DDM42L1FC
DDM43L1FC
DDM45L1FC
DDM408L2FC
DDM42L2FC
DDM43L2FC
DDM45L2FC
DDM408L3FC
DDM42L3FC
DDM43L3FC
DDM45L3FC
0·8
2
3
5
0·8
2
3
5
0·8
2
3
5
Fixed
polarity
L1 + N
L2 + N
L3 + N
Weight
(kg)(1)
0·2
0·4
0·5
0·6
0·2
0·4
0·5
0·6
0·2
0·4
0·5
0·6
(1) Weights shown are for IP 4X rated buscom. For all other
weights, contact us on +44 (0) 845 600 6266
Suspended – right to left
1
1
1
1
BBD240XC
BBD242XC
CCD240XC
CCD242XC
Length
(m)
Rating
(A)
Weight
(kg)(1)
0·5
2
0·5
2
25
25
40
40
3·42
4·52
3·91
5·32
Key : How to select the correct components
All examples on this page show IP 4X buscom trunking
IP rating and tap-off type is dictated by the red letters
4 = IP 4X. For IP 54 version, replace 4 with 5
C = Tap-off with communications circuit. For power only, remove the C
35
LTK_Bro_034_036 v2.indd 35
22/08/2012 16:22
Electrak® 33 4P + E (3 phase) buscom trunking
power and communication distribution
DDN4L1F
DDR43
Selection chart (p. 24-27)
Dimensions and technical information (p. 38-43)
Integral communication bus suitable for KNX, Lonworks, DALI protocols, etc. 25 A and 40 A systems
Outlets on one or two sides. IP 4X or IP 54 ingress protection
Fast installation (trunking push fits together in seconds). High quality materials. Suspended or surface mounted
Pack
Cat. Nos.
Tap-off units without comms – rewirable
Pack
Cat. Nos.
16 A unfused tap-off units
Rewirable tap-off units to pick up required
circuit, colour coded grey, can plug into any
Electrak 33 tap-off outlet
1
1
1
DDN4L1
DDN4L2
DDN4L3
Fixed
polarity
Weight
(kg)(1)
L1 + N
L2 + N
L3 + N
0·14
0·14
0·14
13 A fused tap-off units
Rewirable tap-off units to pick up required
circuit, supplied with BS 1362 fuse, colour coded
grey, can plug into any
Electrak 33 tap-off outlet
1
1
1
DDN4L1F
DDN4L2F
DDN4L3F
Fixed
polarity
Weight
(kg)(1)
L1 + N
L2 + N
L3 + N
0·14
0·14
0·14
Tap-off units without comms –
4P + E pre-wired
(LSOH 5 x 1·5 mm2 cable)
16 A unfused tap-off units
Pre-wired tap-off units to pick up required circuit,
colour coded grey, can plug into any
Electrak 33 tap-off outlet
1
1
1
1
DDR408
DDR42
DDR43
DDR45
Length
(m)
Fixed
polarity
0·8
2
3
5
L+L+L+N
L+L+L+N
L+L+L+N
L+L+L+N
Weight
(kg)(1)
0·20
0·36
0·50
0·63
Phase selectable tap-off units without
comms 2P + E terminals – rewirable
16 A unfused tap-off unit
Rewirable tap-off units, phase selectable, colour
coded grey, can plug into any
Electrak 33 tap-off outlet
1
DDP4S
Fixed
polarity
Weight
(kg)(1)
L+N
0·14
13 A fused tap-off unit
Rewirable tap-off units, phase selectable,
supplied with BS 1362 fuse, colour coded grey,
can plug into any Electrak 33 tap-off outlet
1
DDP4SF
Fixed
polarity
Weight
(kg)(1)
L+N
0·14
(1) Weights shown are for IP 4X rated buscom. For all other
weights, contact us on +44 (0) 845 600 6266
Key : How to select the correct components
All examples on this page show IP 4X buscom trunking
IP rating is dictated by the red letters
4 = IP 4X. For IP 54 version, replace 4 with 5
36
LTK_Bro_034_036 v2.indd 36
23/08/2012 14:08
Electrak® buscom trunking
fixings and ancillary items
EEC348
EEA304
EEC356
EEB340
EEB344
EEA312
EEA308
EEA328
EEA332
EEA324
EEC352
EEC360
EEC364
Dimensions and technical information (p. 41)
Brackets are manufactured from robust galvanised steel, ensuring that the entire installation can be expected to stand up to all normal site conditions
Pack
Cat. Nos.
Fixings
1
EEA304
Ancillary items
Pack
Cat. Nos.
Trunking 57 mm edge surface mounting fixing
bracket
1
EEC356
2 m empty length for adjusting the length at the
end of a run (to be cut)
1
EEA308
Trunking suspended fixing bracket
1
EEC360
IP 54 outlet cover (spare or replacement)
1
EEA312
Trunking suspended fixing bracket c/w cable
duct stirrup. Used when running cable duct on
top of buscom trunking
1
EEC364
Joint sleeve is used if load is hung off trunking
joint or near when joint is centre of a fixing span
1
EEC366
Left hand end stop spare
1
EEA324
Luminaire suspension fixing bracket
1
EEC368
Right hand end stop spare
1
EEA328
Luminaire 45 mm edge suspension fixing
bracket (clip on)
1
EEA332
Luminaire 57 mm edge suspension fixing
bracket (clip on)
1
EEB340
Open hook luminaire suspended bracket
1
EEB344
Closed ring on luminaire
1
EEC348
Cable duct 3 m long x 50 mm(w) x 13 mm(h)
1
EEC357
Joint bracket cable duct
1
EEC352
Cable duct fixing bracket
37
LTK_Bro_037 v2.indd 37
22/08/2012 16:24
Electrak® buscom trunking
technical information
n Standards
Electrical test data
ASTA approved to BS EN 60439-2 and IEC 439-2
Manufactured within an approved ISO 9001 : 2008 facility
Assessed Quality Assurance Certificate No. 10679
Electrak fully complies with the requirements of BS 7671 : 2008
(IEE Wiring Regulations)
n Buscom trunking options
•L
•N
PE
• L2
• L1
•N
PE
• L2
• N2
• L1
• N1
PE
• L3
• L2
• L1
•N
PE
25 A
40 A
UOM
Derating factor for Electrak 32 single sided
–
0·8
–
Derating factor for Electrak 32 double sided
0·8
0·7
–
Derating factor for Electrak 33 double sided
–
0·8
–
Rated operational voltage (Ue)
230/400 230/400 V
Rated insulation voltage (Ui)
500
500
V
Frequency (f)
50/60
50/60
Hz
Rated impulse withstand voltage
4·0
4·0
KV
3·9
2·7
mΩ/m
Busbar resistance (R20)
4·2
3·0
mΩ/m
Resistance (R1)
4·8
3·4
mΩ/m
Impedance (Z1)
2·5
1·6
mΩ/m
Reactance (X1)
Protective conductor
1·5
1·5
mΩ/m
±
±
Communication bus
Electrak buscom trunking can be used with Electrak’s cost effective
lighting control system, Lightrak KNX, or any other systems using
control protocols such as KNX, Lonworks, DALI, etc.
Electrak’s overhead trunking couples high quality engineering with
rigidity of design, and provides power for a variety of applications
including lighting, heating and ventilation. The robust easy fix modular
system permits loads to be suspended directly from the trunking using
Electrak’s various fixing brackets
Push fit connection keeps installation costs to a minimum
Volt drops
25 A
40 A
UOM
Live and neutral : busbars
(R1+R2) Feed unit
Tap-off 0·8 m
Tap-off 2·0 m
Flexible length assembly 0·5 m
Flexible length assembly 2 m
9·0
3·0
22·0
52·0
5·0
20·0
6·0
2·4
22·0
52·0
3·5
14·0
mV/A/m
mV/A
mV/A
mV/A
mV/A
mV/A
Earth fault loop
25 A
40 A
UOM
Impedance : busbar
Earth housing
Feed unit
Tap-off 0·8m
Tap-off 2·0m
Flexible length assembly 0·5 m
Flexible length assembly 2 m
Rated conditional short-circuit current (Icc)
Rated short time withstand current (Icw) at 1 sec
Rated peak short-circuit current (Ipk)
Ambient temperature
4·5
1·5
2·4
23·0
53·0
2·5
10·0
16·0
0·65
0·975
35·0
3·0
1·5
2·4
23·0
53·0
1·75
7·0
16·0
1·0
1·5
35·0
mΩ/m
mΩ/m
mΩ
mΩ
mΩ
mV/A
mV/A
KA
KA
KA
˚C
Mechanical data
25 A
40 A
UOM
Track lengths simply push fit together
n Feed units
25 A rated - max. conductor size 6 mm2
40 A rated - max. conductor size 16 mm2
Double sided trunking feed units have power
cable terminals on both sides.
IP 4X galvanised steel
IP 54 ABS
Number of conductors
Busbar conductor cross sectional area
Cable terminal capacity
Cable terminal capacity bus
Tap-off cable 16 A
Tap-off cable 13 A fused
Tap-off entry
Feed unit entry holes power
Feed unit entry holes bus
IP rating (optional)
2-10
2-10
4·0
6·0
6·0
16·0
1·5
1·5
1·5
1·5
1·5
1·5
16·0
16·0
25·0
25·0
16·0
16·0
4 X (54) 4 X (54)
–
mm2
mm2
mm2
mm2
mm2
mmØ
mmØ
mmØ
–
Direct protection by enclosure. Indirect protection by protective circuit
2 pole + earth + comms
Comms bus
Max. conductor size 1·5 mm2
Red +
Black -
38
LTK_Bro_038_043 v3.indd 38
22/08/2012 16:27
Electrak® buscom trunking
technical data
Communication control circuit
Type
Construction
Insulation - conductor
Sheath
Bus cable (LSOH)
Sheathed 0·5 mm2 copper twisted pair
Flame retardant low emission HCL
LSOH material
Rated insulation voltage (Ui)
(between power circuit and bus)
500 V
Max. bus operating voltage
50 V
Max. bus operating current
0·65 A
Max. conductor resistance (@20˚C)
73·2 Ω/km
Max. mutual capacitance
100 nf/km
Material specifications
Buscom trunking housing
Galvanised steel
Busbars
High conductivity copper
Busbar insulator
Flame retardant LSOH to BS 7211
Trunking connector / tap-off entry box / cable connector
Flame retardant polycarbonate
Tap-off housing
Flame retardant polycarbonate
Trunking connector blades / tap-off blades
Copper
Feed unit IP 4X
Galvanised steel
Feed unit IP 54
ABS
Flexible length conduit
Flame retardant LSOH nylon
Feed unit terminals / earth block
Brass
Brackets
Galvanised steel
13 A tap-off, fuse
To BS 1362, ASTA approved
Durability
Electrak power and communications distribution systems are well designed and extremely robust. They can be expected to stand up to all normal
site conditions Electrak has been short circuit strength tested by ASTA
Earth fault loop impedance
BS 7671 : 2008 IEE Wiring Regulations require accurate determination of the total earth loop impedance, which must be sufficiently low to allow
the protective device to operate within the specified time, which for socket outlets is 0·4 seconds
The values relevant to Electrak for calculating the earth fault loop impedance are shown in the electrical test data table, see opposite
Buscom trunking rating in ambient temperatures
Average ambient air temperature
Rating factor (K1)
25˚C
30˚C
35˚C
40˚C
45˚C
50˚C
1·1
1·05
1
0·95
0·90
0·85
For ambient temperatures other than 35˚C apply the multiplier factor K1 to the rated current
Buscom trunking mechanical loading
For point loads and evenly distributed loads the maximum weight that can be supported is given below
Maximum loading for suspended buscom trunking
Fixing distance (m)
1·5
2
2·5
3
3·5
4
Max. point load (deflection = 1/500 x span) (Kg)
20
17
13
12
9
7
Max. distributed load (deflection = 1/500 x span) (Kg)
33
28
22
20
15
12
Max. point load (deflection = 1/350 x span) (Kg)
33
24
18
16
10
9
Max. distributed load (deflection = 1/350 x span) (Kg)
55
40
30
26
16
15
Maximum loading for surface mounted buscom trunking
Fixing distance in metres (m)
1·5
2
2·5
3
3·5
4
Max. point load (deflection = 1/500 x span) (Kg)
10
6
4·5
4
3·5
3
Max. distributed load (deflection = 1/500 x span) (Kg)
16
10
7·5
7
6
5
Max. point load (deflection = 1/350 x span) (Kg)
13
10
7
6
5
0
Max. distributed load (deflection = 1/350 x span) (Kg)
20
16
11
10
8
0
Notes
1. Where trunking joints occur in the middle of the suspension span, and weight is to be suspended from that point, it is recommened to use a
strenghting bracket EEC364 over the joint to stop deflection
2. If the load requirements exceed the above figures, please contact us on +44 (0) 845 600 6266
For design information and technical specification, please contact us on +44 (0) 845 600 6266
Suspension rods and fixings should be of suitable size to carry the weight of both the track and suspended load
39
LTK_Bro_038_043 v3.indd 39
22/08/2012 16:27
Electrak® buscom trunking
dimensions
n Fixing dimensions
Buscom trunking 3 m
0·5 m outlet spacings
220
195·5
3 000
500
195·5
500
500
500
1 000
500
1 000
304·5
804·5
0·5 m outlet spacings
Buscom trunking 2 m
Buscom trunking
End view
0·5 m outlet spacings
2 000
45
195·5
220
500
500
500
304·5
32
57
195·5
1 000
804·5
Suspended feed unit
0·5 m outlet spacings
Feed unit – left
Single sided
system
Feed unit – right
Double sided
system
2 x 16 Ø
2 x 16 Ø
148
57
209
308
220
517
2 x 25 Ø
209
104
End view both have 2 x 16 mm holes
extra in comms feed
429
Surface feed unit – end view
End stop – left
End stop – right
4 x 25 Ø
52
148
52
10
220
320
2 x 25 Ø
2 x 16 Ø
Centre feed – front view
57
2 x 25 Ø
220
218
2 x 16 Ø
300
308
828
(
All dimensions (mm) are nominal
40
LTK_Bro_038_043 v3.indd 40
22/08/2012 16:28
Cat. No. EEA304 Surface trunking fixing bracket
with trunking clipped in
107
7·5
Cat. No. EEA324 Luminaire
suspended fixing bracket
30
92
7·5
82
7Ø
99·7
7Ø
7Ø
94·5
60
15
8.5 Ø
22
57
12
8·5 Ø
38
Cat. No. EEA308 Suspended trunking
fixing bracket
82
8·5 Ø
Cat. No. EEA328 Luminaire 45 mm
edge suspension fixing bracket
12
70
38
21
21
13
108
125
130
8·5 Ø
30
6Ø
6Ø
60
35
Cat. No. EEA332 Luminaire 57 mm
edge suspension fixing bracket
21
82
38
53·5
Cat. No. EEA312 Suspended trunking
fixing bracket cable duct stirrup
12
8·5 Ø
8·5
39
6Ø
6Ø
30
78
141
163
8·5 Ø
Fused tap-off
Cat. No. EEC352 Cable duct fixing
bracket
12
Fuse holder
Tap-off
fuse removal
77
13
35
50
95
59
Pre-wired tap-offs – 33 mm deep
68
Cat. No. EEB344
Closed ring hook
Cat. No. EEB340
Open hook
M5
70
70
M5
All dimensions (mm) are nominal
96
Rewirable and phase selection
tap-offs – 35 mm deep
68
136
41
LTK_Bro_038_043 v3.indd 41
22/08/2012 16:28
Electrak® buscom trunking
installation
n Design and installation
Electrak’s buscom trunking system comprises continuous lengths of galvanised steel trunking available in 2 m and 3 m lengths with integral
connectors and regular tap-off outlets on one or both sides
Each trunking run commences with a feed unit for electrical and comms bus cable termination. The connection between the trunking, the feed
unit and subsequent trunking lengths is push fit and requires no tools to terminate the connection or ensure good earthing. Each complete track
run is finished with an end stop. Flexible lengths can be used to overcome obstructions or used as corners where required
The trunking system is available with IP 4X or IP 54 ingress protection, fully factory tested and ASTA approved to BS EN 60439-2 : 2008
End stop
Push fit connection
1
2
To install - push fit parts together
To take apart - use a screwdriver to depress the locking catch
2
1
1
2
Left feed unit
Buscom trunking
lengths
2
1
2
1
Push in
to release
Considerations before installation
Calculate the distance between fixing brackets - the maximum fixing distance should not exceed 4 m. If loads are to be hung,
please consult loading charts on page 39. The maximum buscom trunking weight is 2 kg/m
When fixing brackets to drop rods or surfaces, see mounting details below
Suspended trunking fixing brackets
Cable duct clips
into bracket
EEA312
When using cable
duct along trunking
EEA308
EEC352
Cable duct bracket
EEB344
Surface mounted trunking fixing brackets
2
1
EEA304 57 mm Edge surface fixing bracket
Considerations before installation
Ensure surface is level. Screw fix through both fixing holes of
surface fixing brackets to surface with No. 8 fixing screws
Hook trunking into place and push fit to close
42
LTK_Bro_038_043 v3.indd 42
22/08/2012 16:28
Luminaire mounting fixing brackets :
suspended trunking
EEA324 Luminaire fixing brackets
EEA328 45 mm Edge luminaire fixing brackets (maximum load 5 kg)
Luminaire mounting fixing brackets :
surface trunking
EEA304
EEA304
EEA332
EEA332
EEB340
EEB344
EEA332 57 mm Edge luminaire fixing bracket (maximum load 5 kg)
See maximum loading charts p. 39
All dimensions (mm) are nominal
43
LTK_Bro_038_043 v3.indd 43
22/08/2012 16:29
Contact details
Quotations and Technical Support:
The Power Distribution Division of
Legrand Electric Ltd.
Great King Street North,
Birmingham, B19 2LF
Tel: +44 (0) 845 600 6266
Fax: +44 (0) 845 600 6760
E-mail: [email protected]
Customer Services:
The Power Distribution Division of
Legrand Electric Ltd.
No. 1 Industrial Estate
Medomsley Road, Consett,
County Durham, DH8 6SR
Tel: +44 (0) 845 600 6266
Fax: +44 (0) 845 600 6366
E-mail: [email protected]
Accounts:
Legrand Electric Ltd.
Great King Street North,
Birmingham, B19 2LF
Tel: +44 (0) 870 608 9000
Fax: +44 (0) 870 608 9004
Head office (UK and Ireland):
Legrand Electric Limited
Great King Street North, Birmingham, B19 2LF
Tel: 0870 608 9000 Fax: 0870 608 9004
Website: www.legrand.co.uk
This document is printed on sustainably sourced paper. Please recycle.