Vertical Packaged Unit

Transcription

Vertical Packaged Unit
Multi-Positional
Vertical
Packaged Unit
GEOTHERMAL HEAT PUMP
TECHNICAL OVERVIEW
Revolution® Series HXT Multi-Positional Vertical Two-Stage Packaged Unit
ENERGY STAR® requirements,
government regulations, and
competition continue to drive the
geothermal industry to provide higher
efficiency levels and greater equipment
reliability. Overall, this is good for the
customer and the environment. These
challenges, however, are difficult to
meet in some parts of North America,
where indoor air quality and/or airborne
chemicals cause premature indoor
air coil failure (both conventional
air conditioners/heat pumps and
geothermal systems). Many failures
are attributed to formicary corrosion,
which is a type of corrosion that occurs
as airborne chemicals mix with the
condensation on the coil to form certain
acids that aggressively attack copper
tubing.
Hydron Module HXT units (2-6
tons) are built with a standard allaluminum, microchannel air coil.
This technology provides a solution that
can meet the efficiency and reliability
requirements while eliminating the risk
of failure from formicary corrosion.
Other benefits include:
n Single material construction (all
aluminum vs. copper/aluminum),
eliminating the corrosion potential
caused by dissimilar metals
n Improved heat transfer and thermal
performance, resulting in increased
unit efficiencies and lower operating
costs
n 40% less material than a standard
tube-and-fin copper/aluminum coil,
which saves on unit weight and is also
fully recyclable
n Enhanced structural robustness (less
chance of damaging a fin simply by
changing the unit’s filter)
Other Standard Features
n Quadruple compressor isolation (high density steel/foam layer, rubber
grommets, and two layers of insulation) provides excellent sound/vibration
absorption.
nCabinet design features a foamed-in, water-to-refrigerant coaxial heat
exchanger that not only prevents condensation, potentially leading to premature
failure, but also includes a sleeved opening for downflow configuration. This
feature means higher reliability and less SKUs.
n Top-mount control box provides eye level access for easier wiring and service, and
also allows the unit to be installed as left hand or right hand return.
n XT Vertical Packaged models are available in both residential and commercial
voltages – 208/230 V, 60 Hz, Single and 3-phase; 460 V, 60 Hz, 3-phase. Consult
engineering documentation for complete model information and selection
guide.
Unit Performance (Two-Stage)
Ground Loop Heat Pump
Model
XT024
XT036
XT048
XT060
XT072
Capacity
Full Load
BTU/H
19,800
38,900
18.3
29,200
Part Load
29,900
Part Load
37,400
Part Load
49,000
Part Load
57,500
Full Load
Full Load
BTU/H
20.3
21,400
Full Load
EER
27,200
Part Load
Full Load
Cooling
49,000
63,000
71,100
29.1
27.0
17.1
24.1
17.8
24.9
17.1
23.0
16,600
23,200
38,200
29,700
47,700
38,600
55,900
46,700
Heating
COP
Notes:
Rated in accordance with ISO Standard 13256-1,
which includes pump penalties.
4.8
Heating capacities based on 68.0°F DB, 59.0°F
WB entering air temperature.
4.3
4.2
Cooling capacities based on 80.6°F DB, 66.2°F
WB entering air temperature.
3.9
Entering water temperatures
Full Load: 32°F heating / 77°F cooling
Part Load: 41°F heating / 68°F cooling.
4.6
4.3
3.7
4.3
3.6
4.1
High and low voltage wiring as well
as all controls are at eye level
Blowers are mounted on
a slide out rail system
that allows conversion
from upflow or downflow
configuration
All-Aluminum
Microchannel
Air Coil
TXV and filterdryer are located
together in the
air handler
Anti-microbial
plastic drain pan
with factory installed
condensate overflow
sensor
Primary and secondary connections for
condensate drain
Easy to access
Schrader ports
Quadruple-isolation
(high density steel,
foam layer, rubber
grommets, two layers
of insulation)
Desuperheater pump
located for easy
access if service is
needed
Flow switch
protected and
standard 1” FPT
source water
connections
Foam enclosed coaxial water-torefrigerant heat exchanger
Left-hand return/down discharge
Downflow Conversion
Downflow conversion may be accomplished in the field
with an optional downflow kit and a few installation
steps. Simply add the downflow plenum, insulate the
plenum, rotate the blower, and reconnect any wiring.
There is no longer a need to stock upflow and downflow
units. One model does it all. Plus, the unit can be
installed as either right hand return or left hand return.
One unit replaces four!
Dimensional Data
Model
024 - 048
060 - 072
Height
56.1
Dimensional Data
without Control Box
Width*
60.1
Notes:
All Desuperheater connections are 3/4” FPT.
All measurements are in inches.
Ground loop connections are 1” FPT.
*Excludes filter rack
28.0
28.0
Depth
Dimensional Data
with Control Box
Height
32.2
66.5
32.2
62.5
Right-hand return/down discharge
www.hydronmodule.com
[email protected]
Greenville, IL ~ Mitchell, SD
Enertech Global is continually working to improve its products. As a result, the design and specifications of each product
may change without notice and may not be as described herein. For the most up-to-date information, please visit our
website, or contact our Customer Service department at [email protected]. Statements and other information
contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely
Enertech Global’s opinion or commendation of its products.