Deluge valve sets
Transcription
Deluge valve sets
WH 32 Deluge valve sets Manual electric release, pneumatic release, hydraulic release WH32en/03-01.03/PL-W ri-e-ma Order no.:84 0422-03 Deluge Valve Sets Page 2 Manual WH32en/03-01.03 /PL-W ri-e-ma Deluge valve sets Deluge valve sets Manual © 2002 Minimax GmbH All rights reserved. Written approval must be obtained from Minimax GmbH for any further use - also in extracts WH32en/03-01.03/PL-W ri-e-ma Manual Page 3 Deluge Valve Sets Page 4 Manual WH32en/03-01.03 /PL-W ri-e-ma Deluge valve sets Table of contents 1. Delivery program .............................................................................................................................6 1.1. General..........................................................................................................................................7 2. Safety notes......................................................................................................................................8 2.1 Basic safety notes .........................................................................................................................8 2.2 Safety regulations..........................................................................................................................8 2.2.1 Safety equipment .....................................................................................................................8 2.2.2 Informal safety measures .........................................................................................................9 2.2.3 Safety measures for normal operation .....................................................................................9 2.2.4 Electrical hazards .....................................................................................................................9 2.2.5 Upkeep and maintenance ........................................................................................................9 2.2.6 Structural changes of the system.............................................................................................9 2.2.7 Cleaning of the system and waste disposal .............................................................................9 3. Mode of functioning ......................................................................................................................10 3.1 Electric actuation (Fig. 1 and 2 or 3 and 4) .................................................................................10 3.1.1 Electric actuation with impulse solenoid valve (Fig. 1 and 2).............................................10 3.1.2 Electric actuation with 2/2-way solenoid valve (Fig. 3 and 4) ................................................12 3.2 Pneumatic actuation (Fig. 5 and 6) .............................................................................................13 3.3 Hydraulic actuation (Fig. 7 and 8) ...............................................................................................14 4. Function of the major components .............................................................................................16 4.1 Deluge valve (Fig. 9) ...................................................................................................................16 4.2 Solenoid valves (Figure 10 and 11) ............................................................................................17 4.2.1 Impulse solenoid valve (Fig. 10) ............................................................................................17 4.2.2 2/2-way solenoid valve (Fig. 11) ............................................................................................18 4.3 Quick drain valve (Fig. 12) ..........................................................................................................19 4.4 Diaphragm valve (Fig. 13) ...........................................................................................................20 5. Deluge valve sets maintenance regulations ...............................................................................21 5.1 Deluge valve maintenance regulations (Fig. 14).........................................................................22 5.2 Solenoid valve maintenance regulations (Fig. 15) ......................................................................24 5.2.1 Impulse solenoid valve maintenance regulations...................................................................24 5.2.2 2/2-way solenoid valve maintenance regulations (Fig. 16) ....................................................26 5.3 Quick drain valve maintenance regulations (Fig. 17)..................................................................28 5.4 Diaphragm valve maintenance regulations (Fig. 18) ..................................................................30 6. Technical data ................................................................................................................................31 7. Spare parts .....................................................................................................................................32 7.1 7.2 7.3 7.4 8 Deluge valve................................................................................................................................32 Solenoid valve .............................................................................................................................35 Quick drain valve .........................................................................................................................37 Deluge valve set ..........................................................................................................................38 Operating instructions ..................................................................................................................44 8.1 8.2 8.3 8.4 Deluge valve – electric impulse actuation ...................................................................................44 Deluge valve – electric actuation (12 or 24 V) ............................................................................45 Deluge valve set – hydraulic actuation........................................................................................46 Deluge valve – pneumatic actuation ...........................................................................................47 WH32en/03-01.03/PL-W ri-e-ma Manual Page 5 Deluge Valve Sets 1. Delivery program Deluge valve sets electrically actuated 24 V Impulse solenoid valve DN 50 DN 80 DN 100 DN 150 Order no. Order no. Order no. Order no. VdS approval G 4960053 88 2843 88 2855 88 2867 88 2879 Deluge valve sets electrically actuated 24 V 2/2-way solenoid valve DN 50 DN 80 DN 100 DN 150 Order no. Order no. Order no. Order no. 82 9619 82 9620 82 9632 82 9644 } VdS approval G 4920024 phasing out Deluge valve sets pneumatically actuated DN 50 DN 80 DN 100 DN 150 VdS approval G 4920025 Order no.82 9530 Order no. 82 9541 Order no. 82 9553 Order no. 82 9565 Deluge valve sets hydraulically actuated DN 50 DN 80 DN 100 DN 150 Page 6 Order no. Order no. Order no. Order no. VdS approval G 4920026 84 8740 84 8751 84 8763 84 8775 Manual WH32en/03-01.03 /PL-W ri-e-ma Deluge valve sets 1.1. General Deluge valve sets are used in water spray extinguishing systems with open downstream pipework. They are always to be used when large areas are to be extinguished with water through a correspondingly large number of nozzles. Typical fields of application are: • • • • Cooling of tank installations Fire protection for transformer stations Fire protection for platforms Fire protection for process plants, etc. Depending on the application the deluge valve sets are fitted with different actuators. The following actuating variants are approved by the German Damage Insurers Association (VdS): − Electric actuation via impulse solenoid valve 24 V/DC. Special designs with 12V impulse solenoid valve available upon request. A detection system is usually necessary to trip the solenoid valve. This deluge valve set returns to closed operating position by resetting the impulse solenoid valve (remote control possible). − Electric actuation via a normal 2/2-way solenoid valve 24 V/DC. Special designs with 12V 2/2-way solenoid valve available upon request. A detection system is also usually necessary to trip the solenoid valve. Resetting of this deluge valve set to operating mode is only possible at site by operating the quick drain valve (remote control not possible). Caution: Please use impulse actuation 24 V/DC in case of a new installation with electric actuation. We will phase out the electric actuation with normal 2/2-way solenoid valve 24 V/DC in combination with the quick drain valve. − Pneumatic release via diaphragm valve A diaphragm valve is actuated by pressure drop in a pilot pipework actuated by heat sensors. − Hydraulic actuation working directly on the control chamber of the deluge valve. Actuation via pilot pipework by pressure drop from sprinklers. In the case of hydraulic actuation the geodetic height difference between the pilot pipework and the deluge valve set, depending on the water supply, is a factor that must be taken into account. WH32en/03-01.03/PL-W ri-e-ma Manual Page 7 Deluge Valve Sets 2. Safety notes 2.1 Basic safety notes Observe the notes and directions given in this manual • A fundamental prerequisite for the safe and smooth operation of this system is awareness of the basic safety notes and regulations. • This manual contains the essential notes and directions necessary to safe operation of the system. • All personnel working with the system must pay due attention to this manual, and in particular to the safety notes. • In addition to this, the accident prevention regulations in force at the location in question must be observed. Notes on handling the system The deluge valve sets are state of the art and constructed in accordance with the accepted rules of safety engineering practice. The systems are only to be used: • for their stated purpose • in a state corresponding to the correct safety engineering requirements Any faults must be remedied immediately. Stated purpose The stated purpose of the deluge valve sets is that they are exclusively for use as part of a fire extinguishing system in order to supply water. Use for other or additional purposes is not permitted. Minimax GmbH accepts no liability for loss or damage incurred through use for purposes other than the stated purpose. Proper use in accordance with the stated purpose includes: • adherence to all the notes and directions given in this manual and • adherence to the inspection and maintenance instructions Warranty and liability Our "General terms and conditions of sale and delivery" shall be applicable. These shall be made available to the customer no later than the time at which the contract is concluded. Warranty and liability for personal injury or damage to property shall be excluded if these are attributable to one or more of the following causes: − Use of the system for a purpose other than the stated purpose. − Improper installation, commissioning, operation or maintenance of the system. − Operation of the system with defective safety equipment or improperly installed or improperly functioning safety and protective devices. − Failure to observe the notes and directions in this manual regarding transport, storage, installation, commissioning, operation and maintenance of the system. − Unauthorised structural alterations to the system. − Improperly effected repairs. 2.2 Safety regulations 2.2.1 Safety equipment All safety devices must be properly fitted and properly functioning before the system is started up at any time. • Safety devices may only be removed when the system has been brought − to full standstill and − secured against restarting • After the installation of spare parts the protective devices must be replaced in accordance with the regulations. Page 8 Manual WH32en/03-01.03 /PL-W ri-e-ma Deluge valve sets 2.2.2 Informal safety measures • In addition to this manual both the general and local accident prevention and environmental protection regulations must be made available and adhered to. • Only trained personnel who have been familiarised with the system may carry out work on it. 2.2.3 Safety measures for normal operation • The system must only be operated when all the safety devices are fully functional. • Before switching on ensure that no-one is likely to be endangered by the system starting up. • Carry out an external check on the system at least once a week for visible signs of damage (see Point 5). 2.2.4 Electrical hazards • Any work on the electrical equipment must be carried out by a qualified electrician. • Carry out regular checks on the electrical equipment. Any loose connections or heat-damaged wires must be fixed or replaced immediately. • The control cabinet must always be kept locked. Access must be restricted to authorised personnel with a key or special tools. 2.2.5 Upkeep and maintenance • The prescribed adjustment, maintenance and inspection must be carried out at the stated intervals (see Point 5). • Secure all plant, equipment and operating media upstream and downstream from the machine against inadvertent activation. De-energise the system before carrying out any maintenance, inspection or repair work and secure the main switch against inadvertent reactivation. Attach a sign warning against reactivating the switch. • Check that all screws and thread connections have been retightened. • On completion of maintenance work check that safety devices are properly functioning. 2.2.6 Structural changes of the system • No structural changes or additions must be made to the deluge valve sets without the approval of the manufacturer. This also applies to welding work on load bearing members. • Components, which are not in perfect condition must be replaced immediately. • Use only spares and wearing parts supplied by the manufacturer. − There is not guarantee that parts obtained from other sources will be designed and manufactured to meet the required standards of strength and safety. 2.2.7 Cleaning of the system and waste disposal • Ensure the proper use and disposal of materials, in particular: − when carrying out work on lubrication systems, − when using solvents for cleaning purposes. WH32en/03-01.03/PL-W ri-e-ma Manual Page 9 Deluge Valve Sets 3. Mode of functioning How electric, pneumatic and hydraulic actuation works is explained in the following description with the aid of illustrations and diagrams (Fig. 1 - 8). In addition to the automatic actuation systems (electric, pneumatic or hydraulic) each of these variants is also fitted with a manual actuation mechanism. When the manual actuation valve (5) is opened the control chamber of the deluge valve is depressurised and the deluge valve is actuated by water pressure on the valve head. Minimum water supply pressure is 3 bar for all variants of nominal diameter DN 50 -150. 3.1 Electric actuation (Fig. 1 and 2 or 3 and 4) Electric actuation of the deluge valve set is normally by means of a detection system, which actuates the solenoid valve (4) in the event of fire. The solenoid valve (4) opens, causing pressure in the control chamber of the deluge valve (1) to fall and the valve head to be actuated by water supply pressure. The downstream pipework is flooded with water and the alarm gong and the alarm pressure switch (alarm to a continuously manned post, e.g. fire brigade, porter, etc.) are activated. According to the VdS regulation the deluge valve must also remain in open position in case of a power failure, e.g. caused by fire. This requirement is met with the following activation technologies: • actuation with impulse solenoid valve • actuation with normal 2/2-way solenoid valve and additional quick drain valve 3.1.1 Electric actuation with impulse solenoid valve (Fig. 1 and 2) With this actuating technology the once actuated solenoid valve also remains in open position in case of a power failure. The solenoid valve and thus also the deluge valve are closed again only by reversing (current pulse to the reset coil). The activation coil must be de-energised (also the monitoring voltage must be switched off) for resetting the pulse valve because otherwise the solenoid valve will not close. These special features are included in Minimax activation technology. Page 10 Manual WH32en/03-01.03 /PL-W ri-e-ma Deluge valve sets Deluge valve set (electr. actuation with impulse solenoid valve) Figure 1: Illustration 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. Deluge valve Water supply gate valve Downstream pipework gate valve Impulse solenoid valve Manual actuation valve 3/2-way valve Strainer Drain valve Pressure switch (alarm) Drain valve Pressure gauge shutoff valve - water supply Pressure gauge - water supply Pressure gauge shutoff valve – downstream pipework Pressure gauge - downstream pipework Pressure gauge shutoff valve – control chamber Pressure gauge - control chamber Vent valve Alarm gong Downstream pipework Detector line Detection control panel Figure 2: Diagram WH32en/03-01.03/PL-W ri-e-ma Manual Page 11 Deluge Valve Sets 3.1.2 Electric actuation with 2/2-way solenoid valve (Fig. 3 and 4) A quick drain valve (6) is arranged in parallel to the 2/2-way solenoid valve (4) so that the deluge valve remains in open position after actuation and does not close again in case of a voltage drop, open circuit, etc. This spring-loaded valve opens if the pressure drops below 1.4 bar and keeps the control chamber in the deluge valve free from pressure. The deluge valve can only be closed again by closing the quick drain valve (6) on the deluge valve set itself (cf. function of the quick drain valve in Section 4.3). Deluge valve set (electr. actuation with 2/2-way solenoid valve) Figure 3: Illustration 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. Figure 4: Diagram Page 12 Manual 17. 18. 19. 20. 21. 22. Deluge valve Water supply gate valve Downstream pipework gate valve 2/2-way solenoid valve Manual actuation valve Quick drain valve 1.4 bar 3/2-way valve Strainer Drain valve Pressure switch (alarm) Drain valve Pressure gauge shutoff valve - water supply Pressure gauge - water supply Pressure gauge shutoff valve – downstream pipework Pressure gauge – downstream pipework Pressure gauge shutoff valve – control chamber Pressure gauge - control chamber Vent valve Alarm gong Downstream pipework Detector line Detection control panel WH32en/03-01.03 /PL-W ri-e-ma Deluge valve sets 3.2 Pneumatic actuation (Fig. 5 and 6) Pneumatic actuation of the deluge valve sets is effected by means of a pilot pipework filled with compressed air. This is a pipework of nominal diameter ≥ DN 8 fitted with special heat sensors (soldered link). The pilot pipework keeps the diaphragm valve (4) and accordingly the deluge valve (1) closed. An automatic compressed air supply (20-26) maintains the control pressure of approx. 2-3 bar. When one or more of the heat sensors responds, pressure in the pilot pipework and accordingly also in the diaphragm chamber of the diaphragm valve (4) falls. If control pressure in the pilot pipework is below 1/6 of the water supply pressure the diaphragm valve (4) opens and depressurises the control chamber of the deluge valve (1). The deluge valve opens, the downstream pipework is flooded with water and the alarm gong and the alarm pressure switch (alarm to a continuously manned post, e.g. fire brigade, porter, etc.) are activated. The diaphragm valve (4) and accordingly also the deluge valve (1) remain open because there is no possibility of pressure building up again in the pilot pipework after a heat sensor has responded even if compressed air is automatically replenished (throttle). For this reason there is no need to install a quick drain valve in a pneumatic actuation system. In order to avoid nuisance actuation the pneumatic pilot pipework must be kept at operating pressure by means of automatic compressed air replenishment. Depending on the size of the pilot pipework the recommended operating pressure is between 2 and 3 bar. In order to keep actuation time short even when the pilot pipework is a large one, operating pressure ought to be kept on the low side at around 2 bar. The compressed air supply connection is a prefabricated assembly consisting of the components item 20 to 26: Deluge valve set (pneum. actuation) 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. Figure 5: Illustration 21. 22. 23. 24. 25. 26. 27. Deluge valve Water supply gate valve Downstream pipework gate valve Diaphragm valve Manual actuation valve Pneum. pilot pipework 3/2-way valve Strainer Drain valve Pressure switch (alarm) Drain valve Pressure gauge shutoff valve - water supply Pressure gauge - water supply Pressure gauge shutoff valve - water pipework Pressure gauge - water pipework Pressure gauge shutoff valve – control chamber Pressure gauge - control chamber Vent valve Alarm gong Pressure gauge connection - compressed air supply Pressure switch connection - compressed air supply Ball valve connection - compressed air supply Non-return valve connection - compressed air supply Throttle connection - compressed air supply Strainer connection - compressed air supply Vent valve connection - compressed air supply Downstream pipework Figure 6: Diagram WH32en/03-01.03/PL-W ri-e-ma Manual Page 13 Deluge Valve Sets 3.3 Hydraulic actuation (Fig. 7 and 8) Unlike electric and pneumatic actuation, hydraulic actuation has the pilot pipework acting directly on the control chamber of the deluge valve (1). The pilot pipework is constantly supplied with water through the equaliser boring (throttle non-return valve) in the piston rod of the deluge valve. The actuate elements are sprinklers which, on responding to an outbreak of fire, depressurise the pilot pipework and accordingly the control chamber of the deluge valve. In the interests of assuring an adequate margin of safety for release of a deluge valve connected to a hydraulic pilot pipework, the maximum geodetic height difference between the control chamber of the deluge valve and the highest trigger sprinkler is limited in relation to water supply pressure. In addition to this, pressure losses at a flow rate “X“ over the distance to the most remote trigger sprinkler must be taken into account. The maximum permissible geodetic height for the pilot pipework is calculated with the aid of the following formula: H= p − ∆p Kges. H p Ktot. = = = Max. permissible geodetic height for the hydraulic pilot pipework [m] Pressure in the water supply system [m WH] Safety and gearing factor for deluge valve actuation [4] m WH X = = = Pressure loss in accordance with “Hazen/Williams“[m WH] Water head in metres Flow rate via throttle return valve in the deluge valve with a Kv of 8 l/min. ∆p Example: Given a water supply pressure of 9 bar and a calculated pressure loss in the pilot pipework of 2.5 m WH, permitted height ”H” will be as follows: H= p 90 − ∆p = − 2,5 = 20 m 4 4 The height difference in the pilot pipework between the deluge valve and the highest sprinkler may be up to 20 m. A quick drain valve (6) is fitted on the control chamber of the deluge valve in order to shorten the delay before release of the deluge valve in hydraulically actuated systems. When pressure in the pilot pipework falls below the actuation pressure of the quick drain valve, this valve opens and accelerates the fall in pressure in the hydraulic pilot pipework, which, in turn, cuts down the time required for the deluge valve to be released. The actuating pressure of the quick drain valve depends on the pressure of the water supply and will be approx. 50% of the lowest water supply pressure, as given in column 1 of the table below. The quick drain valve is factory set and marked accordingly. Four quick drain valves set at the following pressures can be supplied to match various water supply systems: Water supply ≥ 3 > 5 > 7.5 > 10 Page 14 to to to to 5 7.5 10 12.5 bar bar bar bar Actuating pressure 1.4 bar 2.3 bar 3.4 bar 4.5 bar Manual Order no. 84 1768 84 1770 86 1909 86 1910 WH32en/03-01.03 /PL-W ri-e-ma Deluge valve sets Deluge Valve Set (hydraulic actuation) Figure 7: Illustration 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. Deluge valve Water supply gate valve Downstream pipework gate valve Hydr. pilot pipework Manual actuation valve Quick drain valve 3/2-way valve Strainer Drain valve Pressure switch (alarm) Drain valve Pressure gauge shutoff valve - water supply Pressure gauge - water supply Pressure gauge shutoff valve – downstream pipework Pressure gauge - downstream pipework Pressure gauge shutoff valve – control chamber Pressure gauge - control chamber Vent valve Alarm gong Downstream pipework Figure 8: Diagram WH32en/03-01.03/PL-W ri-e-ma Manual Page 15 Deluge Valve Sets 4. Function of the major components 4.1 Deluge valve (Fig. 9) The deluge valve is a piston controlled shutoff valve, which establishes a seal at twice the pressure of the water supply system (see Fig. 9). The valve head is connected rigidly to the system by a piston rod. A pressure equaliser boring in the piston rod balances water supply pressure and pressure in the valve control chamber. A non-return ball valve in the equaliser boring prevents a fall in pressure in the control chamber even if pressure in the water supply system drops. As the surface area of the piston is greater than that of the valve head, a reliable seal (double pressure) is established against the water supply. This seal is reinforced by a spring which keeps the valve head closed even when the valve is depressurised. The cavity between the piston and valve head is connected to the downstream pipework at the valve outlet. The downstream pipework is, as a rule, at atmospheric pressure and is flooded when the deluge valve is released. The valve is released by falling pressure in the control chamber brought about by suitable actuate elements, e.g. solenoid valve, diaphragm valve or direct connection to a hydraulic pilot pipework. It must be ensured that water is drained from the control chamber by the actuate elements faster than it can be replenished through the equaliser boring (non-return ball valve) so that there is no renewed pressure build-up in the control chamber. Figure 9: Deluge valve Page 16 Manual WH32en/03-01.03 /PL-W ri-e-ma Deluge valve sets 4.2 Solenoid valves (Figure 10 and 11) The solenoid valve for electric actuation is a 2/2-way valve with an operating voltage of 24 V-DC, which is actuated by a detection system. In its READY state the solenoid valve is not actuated, i.e. it is normally closed (NC) and thus, establishes a seal against the control chamber of the deluge valve. In case of an actuation of the solenoid valve it must be ensured that the deluge valve remains in open position even if a power failure, open circuit, etc. occurs. This is guaranteed by using the following actuating technologies: ¾ Actuation with pulse valve which remains in open position after activation and only closes when being reversed (current pulse to the reset coil). ¾ Actuation with a normal solenoid valve in connection with a quick drain valve. In this case the solenoid valve switches back to closed position in case of a voltage drop. The quick drain valve switched in parallel remains in open position (cf. function of the quick drain valve in 4.3). 4.2.1 Impulse solenoid valve (Fig. 10) The impulse solenoid valve is in closed position when being activated at terminal 1 with phase (+). In this switching position the applied water pressure acts on the top of the diaphragm (3), which seals the valve seat. Owing to the difference in surface area (total area at the top compared to the smaller ring area at the bottom), the diaphragm establishes a secure seal on the valve seat. The conical spring (4) keeps the diaphragm on the valve seat closed even when the valve is depressurised. The reversal of the solenoid valve (phase (+) to terminal 2) causes a pressure drop in the diaphragm chamber and thus, the diaphragm (3) is lifted from the valve seat. A minimum pressure of 0.2 bar must always be available as pressure difference. The reversal is carried out via a clapper-type armature (10), which is moved to the corresponding operating state by the solenoid coils (13) and thus, closes or opens the throttle/relief boring. This facilitates the following switching states: a) valve closed ¾ ¾ ¾ throttle boring (x) open relief boring (y) closed by clapper-type armature pressure medium applied to diaphragm chamber b) valve open ¾ ¾ ¾ throttle boring (x) closed by clapper-type armature relief boring (y) open diaphragm chamber is depressurised Socket without plug Connection Terminal 1 = + (closed) Terminal 2 = + (open) Terminal 3 = Terminal =lead earth 1. 2. 3. 4. 5. 6. 7. Valve housing Valve cover Diaphragm Conical spring O-rings 4 x 1.5 Cheese head screws M4 x 10 * Cheese head screws M4 x 73 (diagonally arranged) 8. Plug head with resetting module 9. Cheese head screws M4 x 55 (diagonally arranged) 10. Clapper-type armature 11. Set screws 12. Coil base 13. Coil 14. O-rings 6 x 1.5 15. Formed gasket 16. Manual activation (locked) * not visible in the illustration Caution: Pos. 9-16 (coil set) must not be disassembled WH32en/03-01.03/PL-W ri-e-ma Figure 10: Impulse solenoid valve Manual Page 17 Deluge Valve Sets 4.2.2 2/2-way solenoid valve (Fig. 11) In its READY state the solenoid valve is not actuated, i.e. it is normally closed. In this position the pressure medium acts on the top of the membrane (3) through the 0.8 mm diameter throttle boring (throttle item 4). Owing to the difference in surface area (total area at the top compared to the smaller ring area at the bottom), the diaphragm establishes a secure seal on the valve seat. When the solenoid valve is actuated by activating the solenoid coil (10) the valve armature (8) uncovers the 1.8 mm diameter relief boring, depressurising the upper diaphragm chamber. The diaphragm lifts off the valve seat and the solenoid valve switches to continuity. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. Valve housing Valve cover Diaphragm Throttle ∅ 0.8 0.6 mesh sieve O-Ring 6 x 1.5 Tubus - NC Armature - NC Pressure spring Coil Hex nut Washer Plug Figure 11: 2/2-way solenoid valve Page 18 Manual WH32en/03-01.03 /PL-W ri-e-ma Deluge valve sets 4.3 Quick drain valve (Fig. 12) The quick drain valve has a spring loaded valve head (4) which is opened by falling pressure and remains open even when pressure subsequently rises. The valve head (4) can only be closed again by pressing the spherical button (11) and will remain in the closed position as long as sufficient pressure is maintained - between 1.4 and 4.5 bar, depending on the setting of the spring (marked on the housing). With the drain valve in its READY, i.e. closed, position the piston rod (8) and spherical button (11) can be moved freely. Because the piston or guide rod is jointed pulling or pushing the spherical button will have no effect and cannot result in advertent release of the deluge valve. This valve is used in electrically actuated deluge valve sets with normal 2/2-way solenoid valve (no pulse valve) and hydraulic pilot pipework. When the solenoid valve is electrically actuated the control chamber of the deluge valve is kept depressurised by the quick drain valve even when the solenoid valve closes again. In systems fitted with a hydraulic pilot pipework the quick drain valve speeds up emptying of the control chamber or pilot pipe and accelerates release of the deluge valve accordingly. To suit various applications, quick drain valves with the following spring settings are available: For electric actuation: 1.4 bar For hydraulic actuation: 1.4 bar 2.3 bar 3.4 bar 4.5 bar } Different actuation pressures depending on water supply pressure, see also hydraulic actuation in 3.3 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. Gasket Gasket O-ring Valve head Washer Hex nut Locking screw Piston rod Guide rod Pressure spring Spherical button Set screw Figure 12: Quick drain valve WH32en/03-01.03/PL-W ri-e-ma Manual Page 19 Deluge Valve Sets 4.4 Diaphragm valve (Fig. 13) In its READY position the diaphragm valve for pneumatic actuation is kept closed against the water pressure in the deluge valve control chamber by the pneumatic pilot pipework. An automatic supply of compressed air keeps pressure in the pilot pipework at between 2 and 3 bar. When a heat sensor responds pressure in the pilot pipework and diaphragm chamber of the diaphragm valve falls. When the pressure in the diaphragm chamber falls below the actuating point (approx. 1/6 of water supply pressure) the diaphragm valve opens and depressurises the control chamber of the deluge valve. The deluge valve opens and allows water to flow into the downstream pipework. 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. Diaphragm O-ring Valve head compl. O-ring Hex nut Washer Pressure spring Piston Piston rod Cheese-head screws 11. Cover Figure 13: Diaphragm valve Page 20 Manual WH32en/03-01.03 /PL-W ri-e-ma Deluge valve sets 5. Deluge valve sets maintenance regulations In addition to the usual tests laid down in the operating regulations, regular maintenance of functional parts is essential to the operating safety and reliability of deluge valve sets. Maintenance intervals should be no longer than annually and a function check of the following essential instruments: ¾ Deluge valve ¾ Solenoid valve ¾ Quick drain valve ¾ Diaphragm valve (only in pneumatically actuated systems) should be carried out in the event of the system being genuinely actuated (e.g. tripping by a detector system). Maintenance is to be carried out in the following sequence: 1. Function test on the deluge valve set comprising ¾ Tripping by detectors in the case of electrically actuated systems ¾ Test valve in the case of pneumatically and hydraulically actuated systems The outlet gate valve on the deluge valve set is to be closed in order to prevent flooding of the downstream pipework. 2. Maintenance of the release valves in accordance with the following maintenance regulations 5.1 Deluge valve (DN 50 – 150) 5.2 Solenoid valve 2/2-way-NC 5.2.1 Impulse solenoid valve 5.2.2 2/2-way solenoid valve 5.3 Quick drain valve 5.4 Diaphragm valve (only in pneumatically actuated systems) 3. Return to service in accordance with operating regulations 4. Final function test as per 1. above and return to service in accordance with operating regulations. WH32en/03-01.03/PL-W ri-e-ma Manual Page 21 Deluge Valve Sets 5.1 Deluge valve maintenance regulations (Fig. 14) As a basic rule before any maintenance of the deluge valve is carried out, the deluge valve set must be actuated using the appropriate actuation system, e.g. detector system, and checked for proper functioning. The outlet gate valve must be closed first in order to avoid flooding the downstream pipework. See also operating regulations for deluge valve sets. The following maintenance sequence is then to be observed: ¾ Close the inlet and outlet gate valves of the deluge valve set. ¾ Drain the deluge valve (set the 3/2-way valve to the test position and open the drain valve of the deluge valve set). ¾ Unscrew the inspection cover (13). ¾ Unscrew the cover of control chamber (12) Caution: Owing to the powerful springs (10) under the cover of control chamber (12) the nuts on the cover must be loosened carefully and evenly in order to avoid injury. ¾ Remove the complete piston (7) by twisting slightly and lifting upwards. ¾ Clean the inside of the valve and lubricate the piston sleeve (17). ¾ Check the O-ring (4) in the piston sleeve (17) for damage and replace if necessary. ¾ Check the valve head gasket (3) for damage and replace if necessary. ¾ Clean the inlet sieve (5), check for damage and replace if necessary. ¾ Clean the non-return ball valve (11), check for damage and replace if necessary. ¾ Clean and lubricate the sliding surface of the piston. ¾ Check the gaskets for cover of control chamber and inspection cover (1 and 2) and replace if necessary. ¾ Follow the above procedure in reverse to reassemble the deluge valve. ¾ Return to service the deluge valve in accordance with Section III of the operating regulations in the appendix. 1. Gasket for cover of control chamber 2. Gasket for inspection cover 3. Gasket for valve head 4. O-ring 5. Sieve 6. Snap ring 7. Piston, complete 8. Guide 9. Washer 10. Pressure spring 11. Non-return valve 12. Cover of control chamber 13. Inspection cover 14. Stud bold 15. Hex nut 16. Hex nut 17. Piston sleeve Figure 14: Deluge valve Page 22 Manual WH32en/03-01.03 /PL-W ri-e-ma Deluge valve sets Caution: The following wearing parts can be supplied as a set to fit each nominal size (see Spares, Section 6) and should be replaced whenever maintenance is carried out. ¾ Gasket for cover of control chamber (1) ¾ Gasket for inspection cover (2) ¾ Gasket for valve head (3) ¾ O-ring for piston sleeve (4) ¾ Sieve (5) ¾ Snap ring (6) for fixing the sieve (only DN80-150) Troubleshooting of the deluge valve set Fault Causes Deluge valve not released − − Water supply pressure too low Actuate valve not tripped or defective (cf.Maintenance regulations for solenoid valve and diaphragm valve in Sections 5.2 and 5.4) Deluge valve not closing − − − − Actuate valve is not reversed or still tripped (detector system) Quick drain valve not locking (only for 2/2-way solenoid valve) Actuate valve is defective (cf. Maintenance regulations for solenoid valve and diaphragm valve in Sections 5.2 and 5.3) Sieve in piston rod is blocked Non-return ball valve in piston is blocked Gasket for valve head is dirty or damaged − O-ring in piston sleeve is damaged − Contact surface of piston is damaged − Gasket for valve head is dirty or damaged − Gasket in non-return ball valve is dirty or damaged O-ring in piston sleeve is damaged Contact surface of piston is damaged − − Water running out of drain valve Pressure in control chamber falls when water supply pressure falls − − WH32en/03-01.03/PL-W ri-e-ma Manual Page 23 Deluge Valve Sets 5.2 Solenoid valve maintenance regulations (Fig. 15) Before any maintenance is carried out the solenoid valve must be tripped by means of the detector system or test detector and checked for proper functioning (cf. maintenance regulations for deluge valve set, Section 5 and 5.1). The solenoid valve, which actuates the deluge valve set is an extremely important component. It is accordingly essential to check on this valve when routine annual maintenance is carried out and to maintain this valve as described in Section 5.2.1 and 5.2.2. Especially the control component of the impulse solenoid valve is different from the conventional 2/2-way solenoid valve. Therefore different regulations must be observed when maintaining the valve. 5.2.1 Impulse solenoid valve maintenance regulations The control component (coil set) of this valve is completely sealed from the applied pressure media with a formed gasket (15). Thus, the armature room cannot become dirty so that the control component must not be maintained. This also applies to the set screws (11) with throttle and relief boring. These set screws (11) are factory adjusted and secured with screw safety paint. Caution: Loosening the two fastening screws (9) of the coil or changing the adjustment of the two set screws (11) (secured with red safety paint) causes malfunctions. If required, the complete control component (coil set) must be exchanged (see spare part list). Thus, maintenance of the impulse solenoid valve is limited to checking the diaphragm chamber and must be carried out as follows: ¾ Switch off the power supply to the solenoid valve (detector system) and unscrew or pull off the plug head (8) if necessary. ¾ Loosen the 2 diagonally arranged fastening screws (7) (without safety paint) and remove the complete coil set (9 - 16). Caution: ¾ The 3 O-rings 6 x 1.5 (14) for sealing the connection channels are just inserted loosely and may get lost. Loosening or adjusting the secured screws (9) or (11) (red safety paint) is not permissible. Loosen the 4 fastening screws (6) (not included in the drawing) at the valve housing (1) and remove the valve cover (2). Caution: The 2 O-rings 4 x 1.5 (5) for sealing the connection channels and the conical spring (4) are just inserted loosely and may get lost. ¾ Clean valve housing (1) and cover (2). ¾ Clean diaphragm (3), conical spring (4) and O-ring (5), check for damage and replace if necessary (for wearing parts set see spare part list) ¾ Insert diaphragm (3), conical spring (4) and O-ring (5) in the valve cover (2) and reattach to the housing (1): Caution: ¾ Screw in coil set (9 - 16) and plug head (8). Caution: ¾ The correct position of the components is extremely import for operating the valve. A missing O-ring causes a malfunction of the solenoid valve. Please observe position of the coil set (9 – 16) to the flow direction of the valve (see arrow). A wrongly assembled coil set (180° turned) reverses the function of the solenoid valve! Reconnect the solenoid valve to the power supply. Important: Final functional test of the solenoid valve is carried out with the detector system or test detector Page 24 Manual WH32en/03-01.03 /PL-W ri-e-ma Deluge valve sets 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. Valve housing Valve cover Diaphragm Conical spring O-rings 4 x 1.5 Cheese-head screws M4 x 10 Cheese-head screws M4 x 73 (diagonally arranged) Plug head with resetting module Cheese-head screws M4 x 55 (diagonally arranged) Clapper-type armature Set screws Coil base Coil O-rings 6 x 1,5 Formed gasket Manual activation (secured) Caution: Pos. 9-16 (coil set) may not be disassembled! Figure 15: Impulse solenoid valve Troubleshooting of the impulse solenoid valve Fault Causes Valve not opening − − − − − Valve not closing − − − − − Valve leaking − − − − WH32en/03-01.03/PL-W ri-e-ma No power supply Set screws (11) were changed without observing the regulations Coil set was disassembled or wrongly assembled without observing the regulations Diaphragm defective O-rings (5) or (14) are missing or defective Power supply to the reset coil is missing Monitoring voltage of the release coil was not removed during switching Set screws (11) were changed without observing the regulations Coil set was disassembled or wrongly assembled without observing the regulations O-rings (5) or (14) are missing or defective Diaphragm seat defective or dirty Set screws (11) were changed without observing the regulations Coil set was disassembled or wrongly assembled without observing the regulations O-rings (5) or (14) are missing or defective Manual Page 25 Deluge Valve Sets 5.2.2 2/2-way solenoid valve maintenance regulations (Fig. 16) The control component of this solenoid valve is a valve armature, which closes the relief boring being applied with the pressure media and supported by a pressure spring. Thus, the armature room is permanently in contact with water so that it may pollute easily. Therefore it is absolutely necessary to include not only the diaphragm chamber but also the armature room in the annual maintenance work. The maintenance work must be carried out as follows: ¾ Switch off the power supply to the solenoid valve (detector system) ¾ Loosen the retaining nut (11) with an AF 14 spanner and withdraw the solenoid from the tubus (7) ¾ Loosen the tubus (7) with an AF 22 spanner and unscrew it from the valve cover (2). Clean the tubus (7), armature (8) and pressure spring (9), check them for damage and if necessary replace. Caution: The tubus, armature and spring (7, 8, 9) must be replaced all together. Screw the complete tubus assembly back in and make finger tight (metal seal). ¾ Unscrew the valve cover (2) with an AF 4 socket wrench. ¾ Remove the diaphragm (3), clean it, check for damage and if necessary replace. ¾ Clean throttle with sieve and O-ring (4, 5, 6), check for damage and if necessary replace. Caution: ¾ The sieve must be absolutely clean. If there are any deposits of limescale the sieve must be replaced. Replace the diaphragm and throttle complete with O-ring in the valve housing and screw on the valve cover. Caution: It is extremely important that the diaphragm and throttle be correctly positioned. A missing throttle or O-ring causes a malfunction of the solenoid valve. ¾ Replace the coil and screw tight ¾ Switch on power supply to the solenoid valve again. Important: Final functional test of the solenoid valve carried out by the detector system or test detector 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. Valve housing Valve cover Diaphragm Throttle ∅ 0.8 0.6 mesh sieve O-ring 6 x 1.5 -NBR-70 Sh Tubus - NC Armature - NC Pressure spring Coil Hex nut Washer Plug Figure 16: Solenoid valve Page 26 Manual WH32en/03-01.03 /PL-W ri-e-ma Deluge valve sets Troubleshooting of the 2/2-way solenoid valve Fault Causes Valve not opening − − − − No power supply Throttle (Item 4) and/or O-ring (Item 6) are missing Armature stuck (limescale) Diaphragm defective Valve not closing − − − − Throttle (Item 4) blocked Sieve (Item 5) blocked Armature stuck (limescale) Armature gasket defective or dirty Valve leaking − − Diaphragm seat defective or dirty Armature gasket defective or dirty WH32en/03-01.03/PL-W ri-e-ma Manual Page 27 Deluge Valve Sets 5.3 Quick drain valve maintenance regulations (Fig. 17) The quick drain valve opens when pressure falls below the set value (marked on the valve) and keeps the control chamber of the deluge valve depressurised even if the solenoid valve closes again. Note: Electrically actuated deluge valve sets (only in case of the conventional 2/2-way solenoid valve in 4.2.2) must only be fitted with quick drain valves whose set response pressure is 1.4 bar. As a basic rule (depending on water supply), quick drain valves with higher response pressures are only permissible in hydraulically actuated systems. Maintenance is essentially confined to function testing, the set response pressure, e.g. 1.4 bar, being tested by reducing pressure in the control chamber of the deluge valve (vent valve). The following test sequence is to be observed: ¾ Close the inlet and outlet gate valves of the deluge valve set. ¾ Reduce pressure in the control chamber of the deluge valve by opening the vent valve on the pressure gauge shutoff valve in the cover of the control chamber. ¾ Check the response pressure at the pressure gauge; to be noticed by an immediate pressure drop to below 1.4 bar and simultaneous discharge of water from quick drain valve. ¾ Restore the valve to service by opening the inlet gate valve and at the same time pressing the spherical button on the quick drain valve (cf. start-up in the operating regulations under III). If the quick drain valve is found to be leaky the following maintenance must be carried out: ¾ Close the inlet and outlet gate valves of the deluge valve set. ¾ Use the drain valve to depressurise the control chamber of the deluge valve. Caution: It is advisable to remove the quick drain valve from the deluge valve entirely and to clamp it in a suitable vice for maintenance. ¾ Unscrew the locking screw (7) and remove the complete actuator element. ¾ Remove the entire valve head (4) complete with guide rod (9) and spring (10). ¾ Clean the individual parts, check for damage and if necessary replace. ¾ Lubricate the seal and friction surfaces and O-rings. ¾ Follow the above procedure in reverse to reassemble the quick drain valve. Caution: It is not permissible to change response pressure by adjusting the set screw (12). ¾ Return to service the deluge valve set in accordance with the operating regulations. ¾ Carry out a final check on the quick drain valve as described above. ¾ A deviation of ±0.3 bar from the response value marked on the valve means that it must be completely replaced. Page 28 Manual WH32en/03-01.03 /PL-W ri-e-ma Deluge valve sets 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. Gasket Gasket O-ring Valve head Washer Hex nut Locking screw Piston rod Guide rod Pressure spring Spherical button Set screw Figure 17: Quick drain valve WH32en/03-01.03/PL-W ri-e-ma Manual Page 29 Deluge Valve Sets 5.4 Diaphragm valve maintenance regulations (Fig. 18) The diaphragm valve is used for pneumatic actuation of the deluge valve set. When the valve is in its READY state compressed air in the diaphragm chamber holds the valve head closed against the water pressure in the deluge valve. When the pressure in the diaphragm chamber falls to approx. 1/6 of the water supply pressure the valve head opens and depressurises the control chamber of the deluge valve. In order to maintain the READY state of the valve an adequate supply of compressed air to the diaphragm chamber must be assured (automatic replenishment of compressed air and, if necessary, electrical supervisory switch). ¾ When carrying out maintenance, close the deluge valve set inlet and outlet gate valves and depressurise the control chamber using the vent valve. As a basic rule, it is a good idea to unscrew the complete diaphragm valve from the deluge valve and to observe the following sequence when carrying out maintenance in a vice: ¾ Unscrew and remove the complete control component at the position marked X - X. ¾ Unscrew the diaphragm cover (11). ¾ Clean diaphragm (1) and valve head (3), check for damage and if necessary replace. ¾ Check the piston rod (9) for smooth action and if necessary clean and lubricate. ¾ Lubricate friction surfaces, O-rings and seal surfaces. ¾ Reassemble the diaphragm valve and reinstall it in the deluge valve set. ¾ After returning the deluge valve set to service, carry out a test release by reducing the pressure in the diaphragm chamber of the diaphragm valve. 1. Diaphragm 2. O-ring 3. Valve head complete 4. O-ring 5. Hex nut 6. Washer 7. Pressure spring 8. Piston 9. Piston rod 10. Cheese-head screw 11. Diaphragm cover Figure 18: Diaphragm valve Page 30 Manual WH32en/03-01.03 /PL-W ri-e-ma Deluge valve sets 6. Technical data Approval: A B C H L Depth * to the back DN50 DN80 400 245 305 535 150 430 315 375 610 180 445 375 425 635 190 460 500 540 700 210 210 220 230 280 Depth DN100 DN150 Measure „C“ * to the front * from the pipe centre Nominal diameter ........................................ : DN50, DN80, DN100, DN150 Nominal pressure ........................................ : PN 12.5 / 175 psi Groove connection...................................... : DIN 2501 Medium ......................................................... : water / air Operating temperature................................ : max. 60 °C Gate valve..................................................... : DIN 3352 Equivalent length (incl. gate valve) DN 50: 11.4 m pipe 60.3 x 2.9 DN 80: 12.5 m pipe 88.9 x 2.9 DN 100: 21.4 m pipe 114.3 x 3.2 DN 150: 25.2 m pipe 168.3 x 4.0 Contact rating : 6A at 250 V AC 5A at 24 V DC Alarm : via 1 floating make contact or break contact each Actuation : electrically 24V DC pulse electrically 24V DC 2/2-way hydraulically pneumatically Drain valve : K 3 (operated K 25) Material: deluge valve housing : grey cast iron valve seat: red bronze piston : red bronze gaskets WH32en/03-01.03/PL-W ri-e-ma gate valve ...housing : spheroidal graphite .................... Iron ....................spindle : V2A trimming ...... : V2A / red .................... bronze/brass : Perbunan Manual Page 31 Deluge Valve Sets 7. Spare parts 7.1 Deluge valve Deluge valve type FSV - DN 50 Wearing parts Item Designation 1 Gasket 2 Gasket 3 Gasket 4 O-ring 5 Sieve 6 Snap ring Set of gaskets Other spare parts Item Designation 7 Piston complete ∗ 8 Guide 9 Washer 10 Pressure spring 11 Non-return valve ∗∗ 12 Cover 13 Cover 14 Stud bolt 15 Hex nut 16 Hex nut 17 Stud bolt 18 Hex nut Page 32 Order no.: 17 8623 DIN / Dimensions Cover, control chamber Inspection cover FSV DN 50 Valve head FSV DN 50 70x3-NBR-80Shore FSV DN 50 Not used in FSV DN 50 FSV DN 50 (Item 1 - 5) Quantity 1 1 1 1 1 1 Order no. 77 3398 77 3430 85 5498 13 2599 88 2016 85 8580 DIN / Dimensions FSV DN 50 FSV DN 50 FSV DN 50 FSV DN 50 FSV - M14x1.5-4 Control chamber FSV DN50 Inspection DN 50 DIN939 M12x35-5.6 DIN555 M12 DIN439 M14x1.5-Ms DIN939 M16x40-5.6 DIN555 M16 Quantity 1 1 1 1 1 1 1 4 4 2 4 4 Order no. 85 8542 85 5681 79 2213 85 5802 84 1635 17 8672 17 8684 10 7324 10 8330 83 0304 10 8006 10 8341 Manual WH32en/03-01.03 /PL-W ri-e-ma Deluge valve sets Deluge valve type FSV - DN 80 Wearing parts Item Designation 1 Gasket 2 Gasket 3 Gasket 4 O-ring 5 Sieve 6 Snap ring Set of gaskets Other spare parts Item Designation 7 Piston complete ∗ 8 Guide 9 Washer 10 Pressure spring 11 Non-return valve ∗∗ 12 Cover 13 Cover 14 Stud bolt 15 Hex nut 16 Hex nut 17 Stud bolt 18 Hex nut DIN / Dimensions Cover, control chamber Inspection cover FSV DN 80 Valve head FSV DN 80 110x4-NBR-80Shore FSV DN 80-150 DIN7993 B16-1.4310 FSV DN 80 (Item 1 - 6) Quantity 1 1 1 1 1 1 1 Order no. 77 3404 77 3441 85 5504 13 2897 81 8435 81 8411 85 8591 DIN / Dimensions FSV DN 80 FSV DN 80 FSV DN 80-150 FSV DN 80 FSV - M14x1.5-4 Control chamber FSV DN 80 Inspection DN 80-150 DIN939 M16x40-5.6 DIN555 M16 DIN439 M24x1.5-Ms DIN939 M16x40-5.6 DIN555 M16 Quantity 1 1 1 1 1 1 1 4 4 2 8 8 Order no. 85 8554 85 5644 79 2225 85 5784 84 1635 17 8799 17 9019 10 8006 10 8341 19 5915 10 8006 10 8341 Deluge valve type FSV - DN 100 Wearing parts Item Designation 1 Gasket 2 Gasket 3 Gasket 4 O-ring 5 Sieve 6 Snap ring Set of gaskets Other spare parts Item Designation 7 Piston complete ∗ 8 Guide 9 Washer 10 Pressure spring 11 Non-return valve ∗∗ 12 Cover 13 Cover 14 Stud bolt 15 Hex nut 16 Hex nut 17 Stud bolt 18 Hex nut WH32en/03-01.03/PL-W ri-e-ma Order no.: 17 8740 Order no.: 17 8854 DIN / Dimensions Cover, control chamber Inspection cover FSV DN 80 Valve head FSV DN100 135x5-NBR-80Shore FSV DN 80-150 DIN7993 B16-1.4310 FSV DN100 (Item 1 - 6) Quantity 1 1 1 1 1 1 1 Order no. 77 3416 77 3441 85 5516 13 2952 81 8435 81 8411 85 8608 DIN / Dimensions FSV DN100 FSV DN100 FSV DN 80-150 FSV DN100 FSV - M14x1.5-4 Control chamber FSV DN100 Inspection DN 80-150 DIN939 M16x40-5.6 DIN555 M16 DIN439 M24x1.5-Ms DIN939 M16x40-5.6 DIN555 M16 Quantity 1 1 1 1 1 1 1 4 4 2 8 8 Order no. 85 8566 85 5590 79 2225 85 5735 84 1635 17 8891 17 9019 10 8006 10 8341 19 5915 10 8006 10 8341 Manual Page 33 Deluge Valve Sets Deluge valve type FSV - DN 150 Wearing parts Item Designation 1 Gasket 2 Gasket 3 Gasket 4 O-ring 5 Sieve 6 Snap ring Set of gaskets Other spare parts Item Designation 7 Piston complete ∗ 8 Guide 9 Washer 10 Pressure spring 11 Non-return valve ∗∗ 12 Cover 13 Cover 14 Stud bolt 15 Hex nut 16 Hex nut 17 Stud bolt 18 Hex nut Order no.: 19 3980 DIN / Dimensions Cover, control chamber Inspection cover FSV DN 80 Valve head FSV DN150 200x5-NBR-80Shore FSV DN 80-150 DIN7993 B16-1.4310 FSV DN150 (Item 1 - 6) Quantity 1 1 1 1 1 1 1 Order no. 77 3428 77 3441 85 5528 13 3567 81 8435 81 8411 85 8610 DIN / Dimensions FSV DN 150 FSV DN 150 FSV DN 80-150 FSV DN 150 FSV - M14x1.5-4 Control chamber FSV DN150 Inspection DN 80-150 DIN939 M16x40-5.6 DIN555 M16 DIN439 M24x1.5-Ms DIN939 M20x45-5.6 DIN555 M20 Quantity 1 1 1 1 1 1 1 4 4 2 8 8 Order no. 85 8578 85 5577 79 2225 85 5530 84 1635 17 9007 17 9019 10 8006 10 8341 19 5915 10 8079 10 8523 Caution: ∗ The complete piston is supplied ready assembled including gasket (3), sieve (5), snap ring (6), guide (8), washer (9) and non-return valve (11). ∗∗ In the period 2nd quarter 1993 to 2nd quarter 1994 the non-return valve (11) was supplied with a M16x1.5 threaded connection. The following spare parts are available for their replacement: − Non-return valve M16x1.5 Order no.: 84 8362 or − Adapter M16x1.5 on M14x1.5 Order no.: 89 9781 and washer A16x20-Cu Order no.: 84 8374 − The valve seats in the housing cannot be replaced. − Gasket set and non-return valve (11) are available from stock. All other spare parts are to be ordered from purchase department with appropriately long delivery periods. Page 34 Manual WH32en/03-01.03 /PL-W ri-e-ma Deluge valve sets 7.2 Solenoid valve Solenoid valve DN15-impulse 24V/DC Spare parts Item Designation 1 Coil set compl. 2 Wearing part set 3 4 5 O-ring Plug Resetting module Order no.: 84 0131 DIN / Dimensions Contents: Diaphragm [1 piece] conical spring [1 piece] O-ring 4x1.5 [2 pieces] 6x1.5-NBR-70 Shore GDME 3013 for pulse valve Quantity 1 Order no. 84 0853 1 84 0938 3 1 1 81 5215 76 1094 80 0112 Caution: − The screws marked with safety paint must not be removed or adjusted. − The coil set must be replaced completely without being disassembled. WH32en/03-01.03/PL-W ri-e-ma Manual Page 35 Deluge Valve Sets − Solenoid valve DN15-NC Spare parts Item Designation 1 Armature 2 Tubus 3 Pressure spring 4 Throttle 5 Sieve 6 O-ring 7 Diaphragm 8 Coil 9 Hex nut 10 Washer 11 Plug Page 36 12V/DC 24V/DC 230V/AC Order no.: 84 7801 Order no.: 85 6776 Order no.: 12 6613 DIN / Dimensions Quantity Order no. Tubus, complete 1 89 9574 Diaphragm with throttle 1 89 9586 Coil complete 12V/DC Coil complete 24V/DC Coil complete 230V/AC including rectifier 1 1 89 9604 89 9616 1 89 9628 Manual WH32en/03-01.03 /PL-W ri-e-ma Deluge valve sets 7.3 Quick drain valve Quick drain valve Wearing parts Item Designation 1 Gasket 2 Gasket 3 O-ring Other spare parts Item Designation 4 Valve head 5 Washer 6 Hex nut 7 Locking screw 8 Piston rod 9 Guide rod 10 Pressure spring 11 Spherical button WH32en/03-01.03/PL-W ri-e-ma 1.4 bar 2.3 bar 3.4 bar 4.5 bar Order no.: 84 1768 Order no.: 84 1770 Order no.: 86 1909 Order no.: 86 1910 DIN / Dimensions 20x5x3- NBR 70Sh DIN7603 A30x36-Cu 4.4x1.78-NBR 70Sh Quantity 1 1 2 Order no. 84 8465 84 8489 84 8490 DIN / Dimensions Quantity 1 2 1 1 1 1 1 1 Order no. 84 8404 81 6840 10 8444 84 8453 84 8428 84 8416 84 8477 74 9504 DIN9021 B5.3-Ms-gal Ni DIN934 M5-Ms 1.4x9.6x28 - 1.4310 DIN319 C25-red Manual Page 37 Deluge Valve Sets 7.4 Deluge valve set Deluge valve set DN 50 - DN150 -electr. 24V - IMPULSE -electr. 12V -electr. 24V -hydr. -pneum. This design version available from December 2000 Deluge valve set spare parts Item Designation 1 Deluge valve 2 Gate valve 3 Gasket 4 Hex screw 5 Stud bolt Page 38 DIN / Dimensions / Remarks DN 50 DN 80 DN100 DN150 DIN3352 - DN 50 / PN16 - AVK DIN3352 - DN 80 / PN16 - AVK DIN3352 - DN100 / PN16 - AVK DIN3352 - DN150 / PN16 - AVK DIN2690 DN 50 / PN16 DIN2690 DN 80 / PN16 DIN2690 DN100 / PN16 DIN2690 DN150 / PN16 DIN601 M16x60 Mu DN 50-100 DIN601 M20x70 Mu DN150 DIN938 M16x60 DN 50-100 DIN938 M20x70 DN150 Manual Order no. 17 8623 17 8740 17 8854 19 3980 86 2770 86 2781 86 2793 86 2800 12 6704 12 6728 12 6730 12 6753 10 4712 10 4876 25 6985 10 8110 WH32en/03-01.03 /PL-W ri-e-ma Deluge valve sets Item Designation 6 Hex nut 7 Line 8 Line 9 10 11 12 13 14 15 16 17 18 19 20 21 Pressure gauge Label Label Label Ball valve Pressure switch Vent valve Padlock Strap Funnel Label frame Label Label ledge 22 Label 23 Notched nail WH32en/03-01.03/PL-W ri-e-ma DIN / Dimensions / Remarks DIN555 M16 DN 50-100 DIN555 M20 DN150 Deluge valve set alarm gong Deluge valve set impulse Deluge valve set pneum. Deluge valve set hydr. Deluge valve set electr. AR100 - 16bar – 2MAZ Control pressure Water supply Pipework Pressure gauge stop valve PMA 3 (0.8bar) G1/4-PN16 for KFS Multiple perforation 1.1/2 plastic for Minimax - A50 label Minimax for label ledges Deluge valve set FSV electr.-24V-IMPULSE FSV electr.-12V FSV electr.-24V FSV hydr. FSV pneum. DIN1476 - 3x6 Manual Order no. 10 8341 10 8365 84 1937 88 2892 84 7291 84 1781 84 7310 81 9828 81 2950 11 3870 11 3869 81 9830 11 6512 19 9933 13 1777 78 5320 75 7906 75 0894 75 0912 76 9330 88 2983 84 7333 84 7345 84 7357 84 7369 23 6643 Page 39 Deluge Valve Sets Pos.7 Spare parts for alarm gong line Order no: 84 1937 Item 1 2 3 4 5 6 7 8 9 10 11 Designation Ball valve Connection Ball valve Angle Union Locking cone Cap nut Strainer Double nipple Drip check valve Double junction 12 Line 15x1.5 13 14 15 16 17 18 19 20 21 22 23 Union Adapter Adapter O-ring Cap nut Clamping ring Union Union Tee Conduit nipple Ball valve Page 40 DIN / Dimensions / Remarks 3/2-way with label Line AG-TAV-TMX Pressure gauge stop valve 1/2-VS24-23-Ms/gal Ni 684/S-1224-15x15x1/2I Line AG2 63/S-15/Ms DN15-PN16-0.80 1/2-VS12-28-Ms K25 1/2-VS29-23-Ms/gal Ni FSV DN 50 FSV DN 80 FSV DN100 FSV DN150 1/2-ZUB17-04.B Ms/gal Ni Line SE2-TAV-TMX Line AG/SE2-TAV-TMX 18x2.5 NBR-70Shore 63/S-18/Ms-gal Ni 65-18/Ms 302 TA/S-15x1/2-Ms gal Ni 344-3/4-Zn B1-3/4x3/4x1/2-Zn-A DN20x200-Zn 3/4-PN30 Manual Order no. 84 1218 84 1086 81 9830 88 3045 84 1219 83 0158 84 1162 88 0056 86 3141 75 2921 88 4992 83 4310 83 4322 83 4334 83 4346 84 1217 83 4036 84 1087 88 3008 88 4001 88 4013 86 3130 81 3073 81 3360 11 2737 74 8688 WH32en/03-01.03 /PL-W ri-e-ma Deluge valve sets Other spare parts for … Deluge valve sets electr. 24V-impulse Item 1 2 3 4 5 6 7 8 9 10 11 12 Designation Valve Angle Tee Union Union Solenoid valve Plug Card Conduit nipple Conduit nipple Lead seal Seal wire DIN / Dimensions / Remarks DIN3512-1/2“-1 PN10-RG A4-1/2-Zn-A 135-1/2-Zn U12-1/2-Zn-A UA12-1/2-Zn-A 1/2-24V/DC-2/2-impulse GDME3013 MVA impulse DN15x270-1 thread DN15x305-1 thread DIN1367 0.5-Zn Order no. 12 9791 11 7700 17 5841 12 1342 12 4276 84 0131 76 1094 80 0112 85 4925 85 4937 35 4170 17 5567 Other spare parts for … Deluge valve sets electr. 12 and 24V Item 1 2 3 4 5 6 7 Designation Valve Angle Tee Tee Union Conduit nipple Quick drain valve 8 Solenoid valve 9 10 11 12 13 Conduit nipple Conduit nipple Conduit nipple Lead seal Seal wire WH32en/03-01.03/PL-W ri-e-ma DIN / Dimensions / Remarks DIN3512-1/2“-1 PN10-RG A4-1/2-Zn-A 135-1/2-Zn B1-1/2-Zn-A U12-1/2-Zn-A DN15x40-Zn 1.4 bar 12V 12.5bar-NC 24V 12.5bar-NC DN15x270-1 thread DN15x305-1 thread DN15x170-1 thread DIN1367 0.5-Zn Manual Order no. 12 9791 11 7700 17 5841 21 3350 12 1342 20 3648 84 1768 84 7801 85 6776 85 4925 85 4937 68 1458 35 4170 17 5567 Page 41 Deluge Valve Sets Other spare parts for … Deluge valve sets hydr. Item 1 2 3 4 5 6 7 8 Designation Valve Angle Tee Tee Union Conduit nipple Conduit nipple Conduit nipple 9 Quick drain valve 10 11 Lead seal Seal wire Page 42 DIN / Dimensions / Remarks DIN3512-1/2“-1 PN10-RG A4-1/2-Zn-A 135-1/2-Zn B1-1/2-Zn-A U12-1/2-Zn-A DN15x40-Zn DN15x270-1 thread DN15x305-1 thread 1.4 bar 2.3 bar 3.4 bar 4.5 bar DIN1367 0.5-Zn Manual Order no. 12 9791 11 7700 17 5841 21 3350 12 1342 20 3648 85 4925 85 4937 84 1768 84 1770 86 1909 86 1910 35 4170 17 5567 WH32en/03-01.03 /PL-W ri-e-ma Deluge valve sets Other spare parts for … Deluge valve sets pneum. Connection DN8-FSV-pneum. Item 1 2 3 4 5 6 7 8 9 10 11 Designation Valve Angle Tee Union Diaphragm valve Double nipple Angle Conduit nipple Conduit nipple Lead seal Seal wire 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 1.10 1.11 1.12 1.13 1.14 1.15 1.16 1.17 1.18 Connection DN8 deluge valve set pneum. Strainer DN15-PN16-0.30mm Throttle 0.35mm-R1/2 Non-return valve DN15-PN16 Ball valve DN15-PN40 Double nipple N8-1/2-Zn-A Nipple N4-1/2x1/4-Zn-A Union GE 10-PLR-ED A3C Union K 10-PL A3C Union 344-1/2-Zn Union MAVE 10-LR A3C Union EVGE 10-PLR-ED Vent valve G1/4-PN16 Sleeve M4 red-3/4x1/2-Zn-A Tee 134-1/2-Zn Tee B1-1/2-Zn-A Conduit nipple DN15x80-Zn Pressure gauge 16bar-AR-2MAZ Pressure switch PMÜ-3 (1.0-9.0bar) WH32en/03-01.03/PL-W ri-e-ma DIN / Dimensions / Remarks DIN3512-1/2“-1 PN10-RG A4-1/2-Zn-A 135-1/2-Zn U12-1/2-Zn-A DN15 - NO N8-1/2-Zn-A A1-1/2-Zn-A DN15x170-1 thread DN15x305-1 thread DIN1367 0.5-Zn Manual Order no. 12 9791 11 7700 17 5841 12 1342 20 9353 16 4930 11 4138 68 1458 85 4937 35 4170 17 5567 84 8271 75 5314 12 9754 75 1680 16 4930 12 0532 17 4666 84 1744 77 3295 84 1756 84 1732 19 9933 76 3832 77 2138 21 3350 11 2580 81 9828 79 2183 Page 43 Deluge Valve Sets 8 Operating instructions 8.1 Deluge valve – electric impulse actuation Page 44 Manual WH32en/03-01.03 /PL-W ri-e-ma Deluge valve sets 8.2 Deluge valve – electric actuation (12 or 24 V) WH32en/03-01.03/PL-W ri-e-ma Manual Page 45 Deluge Valve Sets 8.3 Page 46 Deluge valve set – hydraulic actuation Manual WH32en/03-01.03 /PL-W ri-e-ma Deluge valve sets 8.4 Deluge valve – pneumatic actuation WH32en/03-01.03/PL-W ri-e-ma Manual Page 47 Deluge Valve Sets Minimax GmbH z Industriestraße 10/12 z D-23840 Bad Oldesloe Phone +49 (0)4531 803-0 z Fax +49 (0)4531 803-248 Subject to technical alterations. Page 48 Manual WH32en/03-01.03 /PL-W ri-e-ma
Similar documents
catálogo de peças parts list catálogo de peças parts list - ZF
QUANTIDADE POR MODELO / QUANTITY PER MODEL
More informationPlasti-Tech Piping Systems
For gas applies: maximum work pressure is not similar to nominal pressure. See DVGW - Direction GW 335-B 2 or the Regulations of the
More information