surge arresters 081103 - Border States Electric

Transcription

surge arresters 081103 - Border States Electric
®
Product Guide
Protection and Control
SURGE ARRESTERS
• Exceeds IEEE 386
• EPDM Molded Rubber Construction
• Submersible
• Compact to allow installation in
existing cabinetry
• Ground Lead Tethered to the Jacket
MOV SURGE ARRESTERS
Protection and Control Products
Nowadays electric power underground distribution systems demand high
performance in the form of improved reliability and power quality, reduced
operational and maintenance costs, and flexibility of operation. These can be
accomplished by sectionalizing feeders, installing equipment with minimal
maintenance/installation costs, installing protection equipment, installing
automatic source transfer equipment, and/or providing ways to monitor the
system and quickly locate a fault.
Thomas & Betts’ Protection and Control products provide flexible solutions
to all of the above challenges. With a wide arrangement of products such
as arresters, canister and molded fuses, fault indicators, fused elbows, and
switchgear we are able to provide the equipment that you need to fulfill the
needs of underground distribution systems up to 35kV.
Thomas & Betts’ Elastimold® Metal Oxide Varistor (MOV) Surge Arresters
are fully sheilded, fully submersible and are equipped with IEEE 386 interfaces
for convenient energized connection with other 200 Amp loadbreak or deadbreak components up to 35kV. Arresters are available in three styles: Elbow
(ESA), Parking Stand (PSA) and Bushing (BSA). The PSA and BSA arresters
permit direct connection, eliminating the need for additional accessories.
SURGE ARRESTERS
Elastimold MOV Surge Arresters provide high voltage lightning and switching
surge protection of transformers, cable, equipment and other components
typically located on underground power distribution systems. Proper
placement, voltage selection and coordination with riser pole arresters
minimizes damaging surge voltages by improving protective margins.
Typical applications include installing an arrester at the end of a radial system, or at both ends of an open point on a loop
system. Additional arresters can be added at strategic locations upstream from the endpoint for optimum protection.
Request Form 2068 (Surge Protection Options for Underground Distribution) and Form 2069 (Arrester Applications -Underground Electrical Systems) for additional application and margin of protection information.
ESA Elbow Arresters are also available with a 200 Amp Deadbrak interface for mating with other Deadbreak Accessories.
FEATURE
BENEFIT / DESCRIPTION
n IEEE 386 Interfaces
n Convenient energized connection with other 200 Amp
loadbreak or deadbreak components
n EPDM Molded Rubber Construction
n Fully shielded, fully submersible
n Compact
n Allow installation in existing cabinetry
n Elbow (ESA), Parking Stand (PSA), and Bushing (BSA)
styles available
n Ease of application and installation
n Direct connection on PSA and BSA
n Eliminates the need for additional accessories
n No. 4AWG Ground Lead Tethered to the Jacket
n Withstands 10,000 amp for 10 cycles without fusing
n Controls end plug when ejected, preventing
uncontrolled trajectory
n Maintains the housing shield ground connection
after failure
MOV SURGE ARRESTERS
RATINGS
High Current
Short Duration
All MOV Arresters withstand two discharges of
40kA crest.
Low Current
Long Duration
All MOV Arresters withstand 20 surges of 75
amperes/2000 microsecond duration
Duty Cycle Test
All MOV Arresters withstand 22 operations of
5kA crest at 8 x 20 microsecond duration
while energized at rated voltage for the initial 20
operations and at maximum continuous
operating voltage (MCOV) for the final two
operations.
Following each of the preceding tests, MOV Arresters demonstrate
thermal recovery at MCOV.
PROTECTIVE CHARACTERISTICS
15kV
CLASS
25kV
CLASS
35kV
CLASS
MCOV Duty Cycle Maximum Discharge Voltage (kV crest)
8x20 microsecond current wave
(kVrms)
Rating
Note 1
(kVrms)
1.5kA 3kA
5kA
10kA 20kA
2.55
3
10.5
11.0
11.5
13.0
14.5
5.1
6
20.5
21.5
23.0
25.5
30.0
8.4
10
30.5
32.5
34.5
38.5
43.5
10.2
12
40.0
42.5
45.0
50.0
56.5
12.7
15
48.0
51.0
54.0
60.0
68.0
15.3
18
56.5
60.0
64.0
71.0
80.5
8.4
10.2
12.7
15.3
17.0
10
12
15
18
21
30.5
40.0
48.0
56.5
65.5
32.5
42.5
51.0
60.0
69.5
34.5
45.0
54.0
64.0
74.0
38.5
50.0
60.0
71.0
82.5
43.5
56.5
68.0
80.5
93.0
19.5
22.0
24.4
24
27
30
78.5
87.5
95.5
83.5
93.0
101.5
89.0
99.0
108.0
99.0
110.0
120.0
112.0
124.5
136.0
NOTES:
1. MCOV = Maximum Continuous Operating Voltage
INSTALLATION OPTIONS
MOV SURGE ARRESTERS
ORDERING INFORMATION
To specify and order an MOV Surge Arrester:
1. Determine the appropriate Maximum Continuous Operating Voltage (MCOV) for your system voltage by using the
ELASTIMOLD ARRESTER APPLICATION TABLE.
2. Specify the appropriate ELASTIMOLD part number from the SELECTION CHART.
ARRESTER APPLICATION TABLE
System Line-to-Line
Voltage kV rms
15kV
CLASS
25kV
CLASS
35kV
CLASS
SELECTION CHART
MCOV (Max. Continuous
Operating Voltage) kV rms
Solidly
3-Wire
Grounded
Ungrounded
Neutral Circuits
Circuits
Nominal
Max.
2.40
4.16
4.80
6.90
8.32
12.47
13.20
13.80
13.80
2.54
4.40
5.08
7.26
8.80
13.20
13.97
14.50
14.50
2.55
2.55
5.10
5.10
5.10
8.40
8.40
8.40*
10.20
2.55
5.10
5.10
8.40
8.40
15.30
15.30
15.30
15.30
6.90
8.32
12.47
13.20
13.80
13.80
20.78
20.78
23.00
24.94
24.94
28.00
7.26
8.80
13.20
13.97
14.50
14.50
22.00
22.00
24.34
26.40
26.40
29.80
5.10
5.10
8.40
8.40
8.40*
10.20
12.70
15.30*
15.30
15.30
17.00*
17.00
8.40
8.40
15.30
15.30
15.30
15.30
-
23.00
34.50
34.50
24.34
36.51
36.51
22.00*
24.40
22.00
-
* Preferred arrester MCOV for this system voltage.
SELECTION CHART NOTES
N1. Elastimold PSA and BSA Arresters are equipped with a fully
rated 200A switching and fault close loadbreak bushing.
N2. Elastimold Arresters use high-strength silver epoxy bonded
MOV blocks and shunted spring connections for the best
circuit connection.
N3. A 36 inch #4 AWG ground lead provided with each unit.
N4. BSA installed by turning internal hex bolt (accessed
through the 200 Amp Bushing Interface) with 5/16” hex
wrench supplied with each unit.
Picture
Description
BSA
Bushing
Surge Arrester
(includes
assembly
tool)
See Notes
N1, 2, 3, 4
ESA
Elbow
Surge Arrester
See Notes
N2, 3, 5
PSA
Parking Stand
Arrester
See Notes
N1, 2, 3
Voltage
Class
Elastimold
Part Number
MCOV
kVrms
15kV
15kV
15kV
15kV
15kV
15kV
25kV
25kV
25kV
25kV
25kV
35kV
35kV
35kV
167BSA-3
167BSA-6
167BSA-10
167BSA-12
167BSA-15
167BSA-18
273BSA-10
273BSA-12
273BSA-15
273BSA-18
273BSA-21
375BSA-24
375BSA-27
375BSA-30
2.55
5.10
8.40
10.20
12.70
15.30
8.40
10.20
12.70
15.30
17.00
19.50
22.00
24.40
15kV
15kV
15kV
15kV
15kV
15kV
25kV
25kV
25kV
25kV
25kV
35kV
35kV
35kV
167ESA-3
167ESA-6
167ESA-10
167ESA-12
167ESA-15
167ESA-18
273ESA-10
273ESA-12
273ESA-15
273ESA-18
273ESA-21
375ESA-24
375ESA-27
375ESA-30
2.55
5.10
8.40
10.20
12.70
15.30
8.40
10.20
12.70
15.30
17.00
19.50
22.00
24.40
15kV
15kV
15kV
15kV
15kV
15kV
25kV
25kV
25kV
25kV
25kV
35kV
35kV
35kV
167PSA-3
167PSA-6
167PSA-10
167PSA-12
167PSA-15
167PSA-18
273PSA-10
273PSA-12
273PSA-15
273PSA-18
273PSA-21
375PSA-24
375PSA-27
375PSA-30
2.55
5.10
8.40
10.20
12.70
15.30
8.40
10.20
12.70
15.30
17.00
19.50
22.00
24.40
N5. For 15kV and 25kV Class DEADBREAK system Elbow
Arresters, use part number 156ESA with the appropriate
Duty Cycle rating.
Thomas & Betts Corporation
T&B Utility
8155 T&B Blvd.
Memphis, TN 38125
Tel: (800) 888-0211 x5016
Fax: ((800)888-0690
www.tnb.com
Catalog# PC-ARRESTERS-0903
©2003 Thomas & Betts