CaptiveAire`s CASRE Utility Set

Transcription

CaptiveAire`s CASRE Utility Set
Ideal for High Temperature, Heavy Grease Applications
The release of the new CASRE unit shows
CaptiveAire's commitment to quality,
durability and value. This model offers
exceptional performance and is designed
for usage on high static pressure
applications. Both belt and direct drive
models are available to meet any
application.
The CASRE offers a curb mounted exhaust blower system that is easily
installed, delivers exceptional performance and offers a tilt-out wheel for
easy access when servicing or cleaning the unit. The motor base and shaft
seals provide a double layer of protection to prevent leakage into the
building and grease build-up on the motor. An automatic safety lock with
manual release ensures safe access to the wheel for cleaning.
Features & Benefits
Ideal for high temperature, heavy grease applications
Curb mounted design for easier installation
Ventilated motor housing for motor, shaft and drive protection
Adjustable motor plate assembly
Tilt out wheel - easy access during maintenance, automatic safety lock with manual release
Interlocked disconnect switch
Non-overloading, welded aluminum backward inclined wheel is statically and dynamically balanced and permits
usage on high static pressure applications
Heavy duty bearings in excess of 200,000 hours of operation
Motor base and shaft seals provide a double layer of protection to eliminate water leaks into the building and grease
build-up on motor
2" grease drain fully welded onto discharge elbow
Lock and retaining pin - keep wheel centered over the inlet
Belt and Direct Drive Options
Optional Rain Cap Assembly
Additional Product Views
Certifications
CaptiveAire Systems, Inc. certifies that Models CASRE13 through CASRE24 shown herein are licensed to bear the AMCA seal. The ratings
shown are based on tests and procedures performed in accordance with AMCA Publication 211 and Publication 311, and comply with the
requirements of the AMCA Certified Rating Program.
Models CASRE13 through CASRE24 have been certified by ITS. This certification mark indicates that the product has been tested to and has
met the minimum requirements of a widely recognized (consensus) U.S. products safety standard, that the manufacturing site has been
audited, and that the applicant has agreed to a program of periodic factory follow-up inspections to verify continued performance.
Models CASRE13 through CASRE24 are ETL Listed under file numbers 3049729-001 and 3049729-002 and comply with UL705 (electrical)
and UL762 Standards and CSA Std C22.2, No 113.
Catalog #112 C
June 2012
CASRE13BD Performance Curve
1 of 1
http://www.captiveaire.com/CATALOGCONTENT/FANS/EXH_CASRE...
CASRE13BD Performance Curve
Max Sizeable RPM = 2200 RPM. Curve shown extended beyond this point for reference only.
Max discharge velocity for restaurant applications is 1800 fpm. This equates to 1725 cfm.
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories).
Power rating (BHP) does not include transmission losses. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a
hemispherical free field calculated per AMCA Standard 301. Values shown are for Installation Type A: free inlet hemispherical sone levels.
Catalog #112C
June 2012
8/7/2012 3:09 PM
CASRE13BD Performance Table
1 of 1
http://www.captiveaire.com/CATALOGCONTENT/FANS/EXH_CASRE...
CASRE13BD Performance Table
Static Pressure in Inches W.G.
0.000
0.500
1.000
1.500
2.000
2.500
Discharge
Velocity
RPM
RPM
RPM
RPM
RPM
RPM
CFM
FPM
Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP
900
939
833
5.4 / 0.10
1169
9.3 / 0.26
1480
15.1 / 0.49
1744
20 / 0.76
1974
24 / 1.06
1100
1148
1019
8.0 / 0.18
1293
11.5 / 0.36
1565
16.8 / 0.60
1812
22 / 0.90
2033
26 / 1.22
1300
1357
1204
11.1 / 0.29
1435
14.6 / 0.50
1669
19.1 / 0.76
1895
23 / 1.06
2104
27 / 1.41
1500
1565
1389
14.8 / 0.45
1589
18.3 / 0.68
1790
21 / 0.95
1992
25 / 1.27
2187
29 / 1.64
1700
1774
1573
18.9 / 0.65
1749
22 / 0.91
1927
24 / 1.20
2107
27 / 1.53
1900
1983
1758
23 / 0.91
1915
25 / 1.19
2074
27 / 1.51
2100
2191
1943
26 / 1.23
2085
29 / 1.54
2300
2400
2128
31 / 1.62
2174
29 / 1.37
Max Sizeable RPM = 2200 RPM. Table shown extended beyond this point for reference
only.
Max discharge velocity for restaurant applications is 1800 fpm. This equates to 1725
cfm.
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power rating (BHP) does not include transmission
losses. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a hemispherical
free field calculated per AMCA Standard 301. Values shown are for Installation Type A: free inlet
hemispherical sone levels.
Catalog #112C
June 2012
8/7/2012 3:10 PM
CASRE13DD Performance Curve
1 of 1
http://www.captiveaire.com/CATALOGCONTENT/FANS/EXH_CASRE...
CASRE13DD Performance Curve
Max Sizeable RPM = 1800 RPM. Curve shown extended beyond this point for reference only.
Max discharge velocity for restaurant applications is 1800 fpm. This equates to 1725 cfm.
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories).
Power rating (BHP) does not include transmission losses. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a
hemispherical free field calculated per AMCA Standard 301. Values shown are for Installation Type A: free inlet hemispherical sone levels.
Catalog #112C
June 2012
8/7/2012 3:13 PM
CASRE13DD Performance Table
1 of 1
http://www.captiveaire.com/CATALOGCONTENT/FANS/EXH_CASRE...
CASRE13DD Performance Table
Static Pressure in Inches W.G.
0.000
0.250
0.500
0.750
1.000
1.250
1.500
Discharge
Velocity
RPM
RPM
RPM
RPM
RPM
RPM
RPM
CFM
FPM
Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP
750
783
696
4.6 / 0.05
904
8.2 / 0.10
1098
11.0 / 0.17
1278
14.0 / 0.25
1442
17.0 / 0.34
1589
21 / 0.44
1720
25 / 0.54
950
991
881
8.1 / 0.10
1050
10.4 / 0.16
1206
12.7 / 0.23
1359
15.4 / 0.32
1506
18.2 / 0.42
1644
22 / 0.52
1772
27 / 0.64
1150
1200
1067
11.1 / 0.17
1209
13.2 / 0.25
1340
15.1 / 0.33
1469
17.5 / 0.42
1595
21 / 0.52
1719
25 / 0.64
1350
1409
1252
14.5 / 0.28
1376
16.3 / 0.37
1490
18.3 / 0.46
1600
21 / 0.56
1709
25 / 0.67
1550
1617
1438
18.1 / 0.42
1547
20 / 0.52
1649
23 / 0.63
1745
27 / 0.74
1750
1826
1623
23 / 0.61
1722
26 / 0.72
Max Sizeable RPM = 1800 RPM. Table shown extended beyond this point for reference only.
Max discharge velocity for restaurant applications is 1800 fpm. This equates to 1725 cfm.
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the
effects of appurtenances (accessories). Power rating (BHP) does not include transmission losses. The sound
ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a hemispherical free field calculated per AMCA
Standard 301. Values shown are for Installation Type A: free inlet hemispherical sone levels.
Catalog #112C
June 2012
8/7/2012 3:13 PM
CASRE15BD Performance Curve
1 of 1
http://www.captiveaire.com/CATALOGCONTENT/FANS/EXH_CASRE...
CASRE15BD Performance Curve
Max Sizeable RPM = 2200 RPM. Curve shown extended beyond this point for reference only.
Max discharge velocity for restaurant applications is 1800 fpm. This equates to 2450 cfm.
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories).
Power rating (BHP) does not include transmission losses. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a
hemispherical free field calculated per AMCA Standard 301. Values shown are for Installation Type A: free inlet hemispherical sone levels.
Catalog #112C
June 2012
8/7/2012 3:14 PM
CASRE15BD Performance Table
1 of 1
http://www.captiveaire.com/CATALOGCONTENT/FANS/EXH_CASRE...
CASRE15BD Performance Table
Static Pressure in Inches W.G.
0.000
0.500
1.000
1.500
2.000
2.500
3.000
3.500
Discharge
Velocity
RPM
RPM
RPM
RPM
RPM
RPM
RPM
RPM
CFM
FPM
Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP
1200
882
715
4.9 / 0.11
1036
9.4 / 0.30
1281
14.2 / 0.55
1489
18.9 / 0.84
1681
24 / 1.17
1858
27 / 1.53
2024
31 / 1.92
1600
1176
953
8.9 / 0.25
1203
12.6 / 0.49
1427
17.4 / 0.79
1613
22 / 1.12
1778
26 / 1.46
1937
29 / 1.86
2083
33 / 2.27
2000
1469
1191
13.6 / 0.50
1385
16.5 / 0.77
1589
21 / 1.12
1764
25 / 1.50
1918
29 / 1.89
2060
32 / 2.31
2193
36 / 2.76
2400
1763
1429
19.0 / 0.86
1583
21 / 1.16
1761
25 / 1.55
1926
29 / 1.99
2073
32 / 2.44
2800
2057
1668
25 / 1.37
1794
27 / 1.70
1944
29 / 2.12
2096
33 / 2.60
3200
2351
1906
31 / 2.04
2013
32 / 2.40
2140
34 / 2.86
3600
2645
2144
38 / 2.90
2178
36 / 2.33
Max Sizeable RPM = 2200 RPM. Table shown extended beyond this point for reference only.
Max discharge velocity for restaurant applications is 1800 fpm. This equates to 2450 cfm.
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of
appurtenances (accessories). Power rating (BHP) does not include transmission losses. The sound ratings shown are
loudness values in fan sones at 5 ft. (1.5m) in a hemispherical free field calculated per AMCA Standard 301. Values shown
are for Installation Type A: free inlet hemispherical sone levels.
Catalog #112C
June 2012
8/7/2012 3:16 PM
CASRE15BDHP Performance Curve
1 of 1
http://www.captiveaire.com/CATALOGCONTENT/FANS/EXH_CASRE...
CASRE15BDHP Performance Curve
Max Sizeable RPM = 2200 RPM. Curve shown extended beyond this point for reference only.
Max discharge velocity for restaurant applications is 1800 fpm. This equates to 2450 cfm.
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories).
Power rating (BHP) does not include transmission losses. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a
hemispherical free field calculated per AMCA Standard 301. Values shown are for Installation Type A: free inlet hemispherical sone levels.
Catalog #112C
June 2012
8/7/2012 3:17 PM
CASRE15BDHP Performance Table
1 of 1
http://www.captiveaire.com/CATALOGCONTENT/FANS/EXH_CASRE...
CASRE15BDHP Performance Table
Static Pressure in Inches W.G.
0.000
0.500
1.000
1.500
2.000
2.500
Discharge
Velocity
RPM
RPM
RPM
RPM
RPM
RPM
CFM
FPM
Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP
1200
882
1111
8.7 / 0.22
1353
12.7 / 0.44
1565
16.8 / 0.69
1752
20 / 0.97
1920
23 / 1.28
1600
1176
1481
15.1 / 0.51
1668
18.9 / 0.80
1841
22 / 1.11
2000
24 / 1.44
2151
27 / 1.80
2000
1469
1852
22 / 1.00
2004
25 / 1.36
2148
27 / 1.73
2073
26 / 1.59
Max Sizeable RPM = 2200 RPM. Table shown extended beyond this point for reference
only.
Max discharge velocity for restaurant applications is 1800 fpm. This equates to 2450
cfm.
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power rating (BHP) does not include transmission
losses. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a hemispherical
free field calculated per AMCA Standard 301. Values shown are for Installation Type A: free inlet
hemispherical sone levels.
Catalog #112C
June 2012
8/7/2012 3:17 PM
CASRE15DD Performance Curve
1 of 1
http://www.captiveaire.com/CATALOGCONTENT/FANS/EXH_CASRE...
CASRE15DD Performance Curve
Max Sizeable RPM = 1800 RPM. Curve shown extended beyond this point for reference only.
Max discharge velocity for restaurant applications is 1800 fpm. This equates to 2450 cfm.
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories).
Power rating (BHP) does not include transmission losses. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a
hemispherical free field calculated per AMCA Standard 301. Values shown are for Installation Type A: free inlet hemispherical sone levels.
Catalog #112C
June 2012
8/7/2012 3:18 PM
CASRE15DD Performance Table
1 of 1
http://www.captiveaire.com/CATALOGCONTENT/FANS/EXH_CASRE...
CASRE15DD Performance Table
Static Pressure in Inches W.G.
0.000
0.250
0.500
0.750
1.000
1.250
1.500
1.750
2.000
2.250
Discharge
Velocity
RPM
RPM
RPM
RPM
RPM
RPM
RPM
RPM
RPM
RPM
CFM
FPM
Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP
1200
882
711
5.4 / 0.10
890
7.7 / 0.19
1043
10.0 / 0.29
1171
12.6 / 0.40
1285
15.1 / 0.51
1392
17.6 / 0.64
1493
20 / 0.77
1589
23 / 0.91
1683
25 / 1.06
1600
1176
948
8.9 / 0.23
1079
10.8 / 0.34
1215
13.5 / 0.47
1332
16.2 / 0.60
1435
18.6 / 0.74
1530
21 / 0.89
1619
24 / 1.04
1704
26 / 1.20
1786
27 / 1.36
2000
1469
1185
13.1 / 0.46
1285
15.3 / 0.58
1399
17.7 / 0.73
1506
21 / 0.89
1603
23 / 1.06
1692
25 / 1.23
1775
27 / 1.41
2400
1763
1422
18.4 / 0.79
1503
20 / 0.93
1595
23 / 1.10
1689
25 / 1.29
1779
27 / 1.48
2800
2057
1659
24 / 1.25
1726
26 / 1.41
1773
27 / 1.21
Max Sizeable RPM = 1800 RPM. Table shown extended beyond this point for reference only.
Max discharge velocity for restaurant applications is 1800 fpm. This equates to 2450 cfm.
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories).
Power rating (BHP) does not include transmission losses. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a hemispherical
free field calculated per AMCA Standard 301. Values shown are for Installation Type A: free inlet hemispherical sone levels.
Catalog #112C
June 2012
8/7/2012 3:18 PM
CASRE18BD Performance Curve
1 of 1
http://www.captiveaire.com/CATALOGCONTENT/FANS/EXH_CASRE...
CASRE18BD Performance Curve
Max Sizeable RPM = 1700 RPM. Curve shown extended beyond this point for reference only.
Max discharge velocity for restaurant applications is 1800 fpm. This equates to 3104 cfm.
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories).
Power rating (BHP) does not include transmission losses. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a
hemispherical free field calculated per AMCA Standard 301. Values shown are for Installation Type A: free inlet hemispherical sone levels.
Catalog #112C
June 2012
8/7/2012 3:18 PM
CASRE18BD Performance Table
1 of 1
http://www.captiveaire.com/CATALOGCONTENT/FANS/EXH_CASRE...
CASRE18BD Performance Table
Static Pressure in Inches W.G.
0.000
0.500
1.000
1.500
2.000
2.500
3.000
3.500
Discharge
Velocity
RPM
RPM
RPM
RPM
RPM
RPM
RPM
RPM
CFM
FPM
Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP
2500
1450
847
10.8 / 0.37
1004
13.1 / 0.63
1135
14.5 / 0.90
1254
17.1 / 1.20
1364
20 / 1.53
1465
23 / 1.88
1562
26 / 2.26
3000
1740
1016
14.5 / 0.64
1153
17.5 / 0.95
1267
19.6 / 1.26
1374
22 / 1.60
1474
24 / 1.96
1568
26 / 2.34
1657
28 / 2.74
3500
2030
1186
19.4 / 1.01
1307
23 / 1.38
1409
26 / 1.74
1505
28 / 2.11
1596
29 / 2.51
1683
30 / 2.92
4000
2320
1355
26 / 1.51
1464
30 / 1.93
1557
32 / 2.34
1643
33 / 2.76
4500
2610
1523
33 / 2.15
1624
35 / 2.63
5000
2900
1693
38 / 2.95
1653
28 / 2.66
Max Sizeable RPM = 1700 RPM. Table shown extended beyond this point for reference only.
Max discharge velocity for restaurant applications is 1800 fpm. This equates to 3104 cfm.
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of
appurtenances (accessories). Power rating (BHP) does not include transmission losses. The sound ratings shown are
loudness values in fan sones at 5 ft. (1.5m) in a hemispherical free field calculated per AMCA Standard 301. Values shown
are for Installation Type A: free inlet hemispherical sone levels.
Catalog #112C
June 2012
8/7/2012 3:20 PM
CASRE18BDHP Performance Curve
1 of 1
http://www.captiveaire.com/CATALOGCONTENT/FANS/EXH_CASRE...
CASRE18BDHP Performance Curve
Max Sizeable RPM = 1800 RPM. Curve shown extended beyond this point for reference only.
Max discharge velocity for restaurant applications is 1800 fpm. This equates to 3106 cfm.
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories).
Power rating (BHP) does not include transmission losses. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a
hemispherical free field calculated per AMCA Standard 301. Values shown are for Installation Type A: free inlet hemispherical sone levels.
Catalog #112C
June 2012
8/7/2012 3:20 PM
CASRE18BDHP Performance Table
1 of 1
http://www.captiveaire.com/CATALOGCONTENT/FANS/EXH_CASRE...
CASRE18BDHP Performance Table
Static Pressure in Inches W.G.
0.000
0.500
1.000
1.500
2.000
2.500
3.000
3.500
Discharge
Velocity
RPM
RPM
RPM
RPM
RPM
RPM
RPM
RPM
CFM
FPM
Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP
1500
869
693
5.8 / 0.12
895
8.4 / 0.29
1071
10.9 / 0.49
1227
14.3 / 0.72
1366
18.3 / 0.97
1493
22 / 1.23
1608
25 / 1.51
2000
1159
924
9.9 / 0.28
1082
12.3 / 0.50
1224
14.9 / 0.74
1358
18.2 / 1.01
1483
22 / 1.30
1599
25 / 1.60
1708
27 / 1.92
2500
1449
1154
14.8 / 0.55
1285
17.9 / 0.81
1402
21 / 1.09
1516
24 / 1.40
1624
26 / 1.73
3000
1739
1385
22 / 0.95
1496
25 / 1.26
1598
27 / 1.59
1695
29 / 1.94
3500
2029
1616
29 / 1.50
1712
31 / 1.87
1716
27 / 1.80
Max Sizeable RPM = 1800 RPM. Table shown extended beyond this point for reference only.
Max discharge velocity for restaurant applications is 1800 fpm. This equates to 3106 cfm.
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of
appurtenances (accessories). Power rating (BHP) does not include transmission losses. The sound ratings shown are
loudness values in fan sones at 5 ft. (1.5m) in a hemispherical free field calculated per AMCA Standard 301. Values shown
are for Installation Type A: free inlet hemispherical sone levels.
Catalog #112C
June 2012
8/7/2012 3:20 PM
CASRE18DD Performance Curve
1 of 1
http://www.captiveaire.com/CATALOGCONTENT/FANS/EXH_CASRE...
CASRE18DD Performance Curve
Max Sizeable RPM = 1700 RPM. Curve shown extended beyond this point for reference only.
Max discharge velocity for restaurant applications is 1800 fpm. This equates to 3104 cfm.
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories).
Power rating (BHP) does not include transmission losses. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a
hemispherical free field calculated per AMCA Standard 301. Values shown are for Installation Type A: free inlet hemispherical sone levels.
Catalog #112C
June 2012
8/7/2012 3:21 PM
CASRE18DD Performance Table
1 of 1
http://www.captiveaire.com/CATALOGCONTENT/FANS/EXH_CASRE...
CASRE18DD Performance Table
Static Pressure in Inches W.G.
0.000
0.500
1.000
1.500
2.000
2.500
3.000
3.500
Discharge
Velocity
RPM
RPM
RPM
RPM
RPM
RPM
RPM
RPM
CFM
FPM
Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP
1500
870
515
3.5 / 0.08
738
6.9 / 0.23
911
9.7 / 0.41
1067
12.7 / 0.63
1212
16.1 / 0.88
1349
19.7 / 1.15
1476
23 / 1.43
1596
26 / 1.73
2000
1160
687
6.1 / 0.18
867
8.9 / 0.37
1015
11.7 / 0.59
1146
14.6 / 0.83
1268
17.5 / 1.10
1385
21 / 1.40
1497
24 / 1.71
1604
26 / 2.05
2500
1450
858
8.7 / 0.36
1007
11.5 / 0.59
1138
14.4 / 0.84
1254
17.2 / 1.11
1362
20 / 1.41
1464
23 / 1.73
1562
25 / 2.07
1656
27 / 2.42
3000
1740
1030
12.0 / 0.62
1155
14.8 / 0.89
1272
17.6 / 1.18
1378
20 / 1.49
1476
23 / 1.81
1567
25 / 2.16
1656
27 / 2.53
3500
2030
1201
15.8 / 0.99
1309
18.6 / 1.30
1414
21 / 1.63
1511
24 / 1.97
1600
26 / 2.33
1685
28 / 2.71
4000
2320
1373
20 / 1.47
1467
23 / 1.83
1561
25 / 2.20
1649
27 / 2.58
4500
2610
1544
25 / 2.10
1628
27 / 2.50
Max Sizeable RPM = 1700 RPM. Table shown extended beyond this point for reference only.
Max discharge velocity for restaurant applications is 1800 fpm. This equates to 3104 cfm.
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of
appurtenances (accessories). Power rating (BHP) does not include transmission losses. The sound ratings shown are
loudness values in fan sones at 5 ft. (1.5m) in a hemispherical free field calculated per AMCA Standard 301. Values shown
are for Installation Type A: free inlet hemispherical sone levels.
Catalog #112C
June 2012
8/7/2012 3:19 PM
CASRE20BD Performance Curve
1 of 1
http://www.captiveaire.com/CATALOGCONTENT/FANS/EXH_CASRE...
CASRE20BD Performance Curve
Max Sizeable RPM = 1900 RPM. Curve shown extended beyond this point for reference only.
Max discharge velocity for restaurant applications is 1800 fpm. This equates to 3875 cfm.
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories).
Power rating (BHP) does not include transmission losses. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a
hemispherical free field calculated per AMCA Standard 301. Values shown are for Installation Type A: free inlet hemispherical sone levels.
Catalog #112C
June 2012
8/7/2012 3:21 PM
CASRE20BD Performance Table
1 of 1
http://www.captiveaire.com/CATALOGCONTENT/FANS/EXH_CASRE...
CASRE20BD Performance Table
Static Pressure in Inches W.G.
0.000
0.500
1.000
1.500
2.000
2.500
3.000
3.500
Discharge
Velocity
RPM
RPM
RPM
RPM
RPM
RPM
RPM
RPM
CFM
FPM
Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP
3500
1626
904
13.7 / 0.84
1046
15.7 / 1.27
1182
18.2 / 1.77
1306
21 / 2.32
1421
24 / 2.91
1529
27 / 3.53
1632
30 / 4.19
4000
1858
1034
17.5 / 1.26
1158
19.4 / 1.74
1280
22 / 2.28
1394
24 / 2.87
1501
27 / 3.51
1602
29 / 4.18
1698
33 / 4.89
4500
2090
1163
22 / 1.79
1273
24 / 2.33
1383
26 / 2.92
1488
28 / 3.55
1588
31 / 4.23
1683
33 / 4.95
5000
2323
1292
26 / 2.46
1391
28 / 3.05
1491
30 / 3.68
1588
32 / 4.37
5500
2555
1421
31 / 3.27
1511
33 / 3.91
1602
35 / 4.60
6000
2787
1550
37 / 4.25
1632
38 / 4.94
1730
34 / 4.89
Max Sizeable RPM = 1900 RPM. Table shown extended beyond this point for reference only.
Max discharge velocity for restaurant applications is 1800 fpm. This equates to 3875 cfm.
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of
appurtenances (accessories). Power rating (BHP) does not include transmission losses. The sound ratings shown are
loudness values in fan sones at 5 ft. (1.5m) in a hemispherical free field calculated per AMCA Standard 301. Values shown
are for Installation Type A: free inlet hemispherical sone levels.
Catalog #112C
June 2012
8/7/2012 3:32 PM
CASRE20BDHP Performance Curve
1 of 1
http://www.captiveaire.com/CATALOGCONTENT/FANS/EXH_CASRE...
CASRE20BDHP Performance Curve
Max Sizeable RPM = 2000 RPM. Curve shown extended beyond this point for reference only.
Max discharge velocity for restaurant applications is 1800 fpm. This equates to 3875 cfm.
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories).
Power rating (BHP) does not include transmission losses. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a
hemispherical free field calculated per AMCA Standard 301. Values shown are for Installation Type A: free inlet hemispherical sone levels.
Catalog #112C
June 2012
8/7/2012 3:33 PM
CASRE20BDHP Performance Table
1 of 1
http://www.captiveaire.com/CATALOGCONTENT/FANS/EXH_CASRE...
CASRE20BDHP Performance Table
Static Pressure in Inches W.G.
0.000
0.500
1.000
1.500
2.000
2.500
3.000
3.500
4.000
4.500
5.000
Discharge
Velocity
RPM
RPM
RPM
RPM
RPM
RPM
RPM
RPM
RPM
RPM
RPM
CFM
FPM
Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP
2000
929
696
6.4 / 0.20
888
9.6 / 0.45
1054
13.3 / 0.75
1200
16.7 / 1.08
1331
21 / 1.43
1451
25 / 1.81
1562
29 / 2.20
1668
33 / 2.61
1767
38 / 3.03
1860
42 / 3.47
2500
1161
870
9.8 / 0.38
1027
13.1 / 0.69
1171
16.3 / 1.04
1302
20 / 1.42
1422
24 / 1.82
1534
28 / 2.25
1638
32 / 2.69
1737
36 / 3.14
1832
41 / 3.62
1922
46 / 4.11
3000
1394
1043
13.9 / 0.66
1176
17.4 / 1.02
1302
21 / 1.42
1419
24 / 1.85
1528
28 / 2.30
1632
32 / 2.78
1729
36 / 3.27
1823
40 / 3.78
1911
45 / 4.30
1996
50 / 4.83
3500
1626
1217
18.8 / 1.05
1332
22 / 1.46
1442
26 / 1.91
1547
30 / 2.39
1647
33 / 2.89
1742
37 / 3.42
1833
41 / 3.96
1920
46 / 4.52
4000
1858
1391
25 / 1.57
1491
28 / 2.03
1590
32 / 2.53
1684
35 / 3.06
1775
39 / 3.61
1864
43 / 4.19
1948
48 / 4.79
4500
2090
1565
31 / 2.23
1654
34 / 2.74
1742
38 / 3.29
1828
42 / 3.87
1912
46 / 4.48
5000
2323
1739
38 / 3.07
1820
42 / 3.63
1899
46 / 4.22
1977
49 / 4.85
5500
2555
1913
47 / 4.08
1986
51 / 4.69
1951
47 / 3.94
Max Sizeable RPM = 2000 RPM. Table shown extended beyond this point for reference only.
Max discharge velocity for restaurant applications is 1800 fpm. This equates to 3875 cfm.
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating
(BHP) does not include transmission losses. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a hemispherical free field calculated per
AMCA Standard 301. Values shown are for Installation Type A: free inlet hemispherical sone levels.
Catalog #112C
June 2012
8/7/2012 3:33 PM
CASRE20DD Performance Curve
1 of 1
http://www.captiveaire.com/CATALOGCONTENT/FANS/EXH_CASRE...
CASRE20DD Performance Curve
Max Sizeable RPM = 1650 RPM. Curve shown extended beyond this point for reference only.
Max discharge velocity for restaurant applications is 1800 fpm. This equates to 3875 cfm.
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories).
Power rating (BHP) does not include transmission losses. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a
hemispherical free field calculated per AMCA Standard 301. Values shown are for Installation Type A: free inlet hemispherical sone levels.
Catalog #112C
June 2012
8/7/2012 3:34 PM
CASRE20DD Performance Table
1 of 1
http://www.captiveaire.com/CATALOGCONTENT/FANS/EXH_CASRE...
CASRE20DD Performance Table
Static Pressure in Inches W.G.
0.000
0.500
1.000
1.500
2.000
2.500
3.000
Discharge
Velocity
RPM
RPM
RPM
RPM
RPM
RPM
RPM
CFM
FPM
Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP
3000
1394
770
10.1 / 0.51
961
13.6 / 0.90
1103
17.2 / 1.33
1232
21 / 1.81
1353
24 / 2.33
1468
28 / 2.89
1578
32 / 3.48
3500
1626
898
13.0 / 0.81
1072
16.4 / 1.27
1202
19.8 / 1.74
1319
23 / 2.26
1429
27 / 2.82
1534
31 / 3.42
1635
33 / 4.06
4000
1858
1026
16.1 / 1.21
1186
19.4 / 1.74
1306
23 / 2.26
1414
26 / 2.82
1515
30 / 3.42
1612
33 / 4.06
4500
2090
1155
19.7 / 1.72
1302
23 / 2.32
1416
26 / 2.90
1516
30 / 3.51
1609
33 / 4.15
5000
2323
1283
23 / 2.35
1421
28 / 3.03
1527
30 / 3.67
1622
33 / 4.33
5500
2555
1411
28 / 3.13
1540
32 / 3.88
1641
34 / 4.59
6000
2787
1539
32 / 4.06
Max Sizeable RPM = 1650 RPM. Table shown extended beyond this point for reference only.
Max discharge velocity for restaurant applications is 1800 fpm. This equates to 3875 cfm.
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the
effects of appurtenances (accessories). Power rating (BHP) does not include transmission losses. The sound
ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a hemispherical free field calculated per AMCA
Standard 301. Values shown are for Installation Type A: free inlet hemispherical sone levels.
Catalog #112C
June 2012
8/7/2012 3:34 PM
CASRE24BD Performance Curve
1 of 1
http://www.captiveaire.com/CATALOGCONTENT/FANS/EXH_CASRE...
CASRE24BD Performance Curve
Max Sizeable RPM = 1600 RPM. Curve shown extended beyond this point for reference only.
Max discharge velocity for restaurant applications is 1800 fpm. This equates to 5302 cfm.
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories).
Power rating (BHP) does not include transmission losses. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a
hemispherical free field calculated per AMCA Standard 301. Values shown are for Installation Type A: free inlet hemispherical sone levels.
Catalog #112C
June 2012
8/7/2012 3:35 PM
CASRE24BD Performance Table
1 of 1
http://www.captiveaire.com/CATALOGCONTENT/FANS/EXH_CASRE...
CASRE24BD Performance Table
Static Pressure in Inches W.G.
0.000
0.500
1.000
1.500
2.000
2.500
3.000
3.500
4.000
4.500
Discharge
Velocity
RPM
RPM
RPM
RPM
RPM
RPM
RPM
RPM
RPM
RPM
CFM
FPM
Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP
4000
1358
674
15.3 / 0.71
822
21 / 1.23
949
27 / 1.83
1060
37 / 2.48
1160
43 / 3.16
1254
50 / 3.89
1342
57 / 4.65
1427
64 / 5.46
5000
1698
842
22 / 1.38
961
28 / 2.00
1075
38 / 2.72
1175
44 / 3.48
1266
51 / 4.28
1351
58 / 5.10
1431
64 / 5.95
1507
71 / 6.84
6000
2037
1010
34 / 2.39
1109
40 / 3.10
1208
47 / 3.93
1300
53 / 4.81
1384
60 / 5.72
1463
67 / 6.66
7000
2377
1179
45 / 3.79
1263
51 / 4.60
1349
57 / 5.53
1433
64 / 6.52
8000
2716
1347
57 / 5.66
1420
63 / 6.56
1508
71 / 6.30
1587
77 / 7.17
Max Sizeable RPM = 1600 RPM. Table shown extended beyond this point for reference only.
Max discharge velocity for restaurant applications is 1800 fpm. This equates to 5302 cfm.
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories).
Power rating (BHP) does not include transmission losses. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a hemispherical
free field calculated per AMCA Standard 301. Values shown are for Installation Type A: free inlet hemispherical sone levels.
Catalog #112C
June 2012
8/7/2012 3:35 PM
CASRE24BDHP Performance Curve
1 of 1
http://www.captiveaire.com/CATALOGCONTENT/FANS/EXH_CASRE...
CASRE24BDHP Performance Curve
Max Sizeable RPM = 1800 RPM. Curve shown extended beyond this point for reference only.
Max discharge velocity for restaurant applications is 1800 fpm. This equates to 5302 cfm.
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories).
Power rating (BHP) does not include transmission losses. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a
hemispherical free field calculated per AMCA Standard 301. Values shown are for Installation Type A: free inlet hemispherical sone levels.
Catalog #112C
June 2012
8/7/2012 3:36 PM
CASRE24BDHP Performance Table
1 of 1
http://www.captiveaire.com/CATALOGCONTENT/FANS/EXH_CASRE...
CASRE24BDHP Performance Table
Static Pressure in Inches W.G.
0.000
0.500
1.000
1.500
2.000
2.500
3.000
3.500
4.000
4.500
5.000
5.500
Discharge
Velocity
RPM
RPM
RPM
RPM
RPM
RPM
RPM
RPM
RPM
RPM
RPM
RPM
CFM
FPM
Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP
4000
1358
744
11.9 / 0.50
878
13.6 / 0.91
1000
16.6 / 1.36
1111
20 / 1.86
1211
23 / 2.38
1304
27 / 2.94
1392
30 / 3.52
1474
33 / 4.12
1552
36 / 4.75
1627
38 / 5.40
1699
41 / 6.07
5000
1698
930
16.7 / 0.98
1038
18.6 / 1.48
1142
21 / 2.01
1239
24 / 2.59
1329
27 / 3.20
1414
31 / 3.83
1495
34 / 4.49
1571
36 / 5.17
1644
39 / 5.87
1714
42 / 6.60
1781
44 / 7.34
6000
2037
1116
22 / 1.70
1206
25 / 2.28
1295
27 / 2.90
1380
30 / 3.56
1461
33 / 4.25
1539
35 / 4.97
1612
38 / 5.70
1684
41 / 6.47
1751
43 / 7.25
7000
2377
1302
29 / 2.70
1379
31 / 3.37
1456
34 / 4.08
1531
37 / 4.82
1604
39 / 5.59
1674
41 / 6.39
1742
43 / 7.21
8000
2716
1488
37 / 4.03
1556
39 / 4.79
1623
41 / 5.58
1690
43 / 6.41
1755
45 / 7.27
9000
3056
1674
44 / 5.74
1734
46 / 6.59
1794
48 / 7.47
1768
44 / 6.76
Max Sizeable RPM = 1800 RPM. Table shown extended beyond this point for reference only.
Max discharge velocity for restaurant applications is 1800 fpm. This equates to 5302 cfm.
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating (BHP) does not
include transmission losses. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a hemispherical free field calculated per AMCA Standard 301. Values
shown are for Installation Type A: free inlet hemispherical sone levels.
Catalog #112C
June 2012
8/7/2012 3:36 PM
CASRE24DD Performance Curve
1 of 1
http://www.captiveaire.com/CATALOGCONTENT/FANS/EXH_CASRE...
CASRE24DD Performance Curve
Max Sizeable RPM = 1400 RPM. Curve shown extended beyond this point for reference only.
Max discharge velocity for restaurant applications is 1800 fpm. This equates to 5302 cfm.
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories).
Power rating (BHP) does not include transmission losses. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a
hemispherical free field calculated per AMCA Standard 301. Values shown are for Installation Type A: free inlet hemispherical sone levels.
Catalog #112C
June 2012
8/7/2012 3:36 PM
CASRE24DD Performance Table
1 of 1
http://www.captiveaire.com/CATALOGCONTENT/FANS/EXH_CASRE...
CASRE24DD Performance Table
Static Pressure in Inches W.G.
0.000
0.250
0.500
0.750
1.000
1.250
1.500
1.750
2.000
2.250
2.500
2.750
3.000
Discharge
Velocity
RPM
RPM
RPM
RPM
RPM
RPM
RPM
RPM
RPM
RPM
RPM
RPM
RPM
CFM
FPM
Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP Sone/BHP
4000
1358
700
13.1 / 0.79
775
14.7 / 1.07
845
16.8 / 1.34
909
18.9 / 1.63
970
21 / 1.93
1028
23 / 2.26
1083
25 / 2.60
1136
27 / 2.97
1187
29 / 3.35
1236
31 / 3.74
1283
33 / 4.15
5000
1698
875
18.8 / 1.54
936
19.9 / 1.90
994
22 / 2.24
1049
24 / 2.58
1102
26 / 2.93
1152
28 / 3.29
1201
30 / 3.68
1248
31 / 4.08
1293
34 / 4.49
1337
36 / 4.92
1380
38 / 5.36
6000
2037
1050
25 / 2.67
1101
26 / 3.10
1150
28 / 3.51
1198
29 / 3.91
1244
31 / 4.32
1289
33 / 4.73
1332
35 / 5.16
1374
38 / 5.60
7000
2377
1225
32 / 4.24
1269
33 / 4.74
1312
35 / 5.22
1354
37 / 5.70
1394
39 / 6.17
8000
2716
1400
41 / 6.32
1329
35 / 4.56
1375
38 / 5.00
Max Sizeable RPM = 1400 RPM. Table shown extended beyond this point for reference only.
Max discharge velocity for restaurant applications is 1800 fpm. This equates to 5302 cfm.
Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories). Power rating (BHP) does not include
transmission losses. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for Installation
Type A: free inlet hemispherical sone levels.
Catalog #112C
June 2012
8/7/2012 3:37 PM

Similar documents

General Purpose Centrifugal Fan, Model US

General Purpose Centrifugal Fan, Model US moving unit. These units offer many features as standard equipment that other manufacturers consider options. Each unit is fully assembled, factory set at the specified RPM, and test run prior to s...

More information