Self dehydrating breather

Transcription

Self dehydrating breather
SDB
Self dehydrating breather
Index
SDB
General information
2
SDB-30 and SDB-15 operating principle 5
SDB-10 operating principle 8
Overall dimensions type SDB-30
6
Overall dimensions type SDB-15
7
Overall dimensions type SDB-10 9
Self dehydrating breather type SDB 10
Wiring terminals 11
Order sheet
21
SDB-C
General information
12
SDB-12C/14C operating principle 15
SDB-10C operating principle
17
Overall dimensions type SDB-12C/14C
16
Overall dimensions type SDB-10C
18
Self dehydrating breather type SDB-C
19
Wiring terminals 20
Order sheet
21
1
Self dehydrating breather type SDB
Main Benefits for End User are:
1. Increase transformer reliability
Consistent moisture absorption ensured by:
- two independent silicagel tanks working alternatively
- continuous monitoring of silicagel saturation.
2. Operational cost savings
Automatic silicagel regeneration process drastically reduce
expensive maintenance activities.
3. Easy to install
Suitable for new installation and retrofit case.
Compatible with with EN and DIN standards.
SDB
Ultimate safety performance through superior design
SDB-30
with double tank
2
SDB-15
with coaxial tank
SDB-10
single tank to be used in combination
with SDB-030 or SDB-015
Moisture is a leading cause of transformer aging.
Avoiding moisture ingress into the transformer is paramount to
avoiding outage and maximizing the lifetime of the equipment.
The traditional way of managing this problem is with
conventional breathers which are expensive to maintain
and present a significant risk of moisture entering into the
transformer between checks. In response to this situation,
COMEM has developed the Self Dehydrating Breather (SDB)
which delivers the best performance of any low maintenance
solution on the market:
COMEM SDB is the only solution to guarantee a consistent flow
of dry air, out-performing both conventional breathers and
alternative low maintenance solutions.
Self Dehydrating Breather SDB family is the right choice in order
to minimize the possible risk of transformer outage due to
insulation fluid impairment through moisture: thanks to its unique
and proven working principle, the air is always fully dehydrated
because silicagel tanks are independent each other thus the
regeneration process does not start simultaneously in the two
tanks.
3
Self dehydrating breather type SDB
Model selection
The below number and size of Self Dehydrating Breathers are ‘Rule of Thumb’ recommendations for the devices in question. This is to
be considered as a guide only and should not replace good design and engineering practice and experience
Application
SDB-10
SDB-10C*
SDB-12C
SDB-14C
SDB-15
SDB-30
OLTC
Petersen Coil
Cable boxes
Traction
Network <40 MVA
Phase shifting <40 MVA
Shunt reactors <40 MVA
Network ≥40 MVA ≤200 MVA
Phase shifting ≥40 MVA ≤200 MVA
Shunt reactors ≥40 MVA ≤200 MVA
Step up ≥40 MVA ≤200 MVA
Generator and network >200 MVA
Phase shifting >200 MVA
Shunt reactors >200 MVA
HVDC
Furnace
Cavern
GSU
* = SDB-10C to be used in combination with SDB-12C or SDB-14C
Main Features
4
SDB
Tank Working principle
Fitting
Notes
SDB-10
1
Continuous silicagel monitoring
OLTC
In combination with SDB-15 or SDB-30
SDB-10C
1
Adjustable time based regeneration
OLTC
In combination with SDB-12C or SDB-14C
SDB-12C
2
Adjustable time based regeneration
OLTC
Stand alone
SDB-14C
2
Adjustable time based regeneration
Oil conservator
Stand alone
SDB-15
2
Continuous silicagel monitoring
Oil conservator
Stand alone
SDB-030
2
Continuous silicagel monitoring
Oil conservator
Stand alone
SDB-30 and SDB-15 operating principle
The self-dehydrating air breather works in accordance with the
following principles.
During the normal operation the oil conservator intakes air that
passes through the metallic filter. The metallic filter stops dust,
sand and other particles from the contaminating air. The air then
passes through the salt tank 1.
The salt tank is filled with silica gel that absorbs the moisture.
The dehydrated air goes through piping to the oil conservator.
When the silica gel absorbs the moisture in the air, the weight
of the salt increases and is constantly monitored by a weighing
cell. When the weight increases and exceeds the pre-set value a
solenoid valve blocks the passage of air through salt tank 1 and
deviates through the “plenum chamber ” 2.
At the same time, a heating system inside tank 1 is activated.
The water vapor leaving the silica gel is expelled outward by a
fan that also dissipates the heat.
Inside the salt, a probe controls the temperature of the heating
element.
During the functioning of the device, the weighing cell
temperature is monitored by a temperature sensor mounted in
the upper part.
As soon as the salt regeneration in tank 1 is completed, the
solenoid valve is de-energized and the airflow through tank 2 is
inhibited. The salt in this tank (2) is also dehydrated, regeneration
of the salt in tank 2 follows automatically.
No maintenance is required for replacement and regeneration of
the desiccant.
5
Overall dimensions type SDB-30
302 (11.88")
88.5
753 (29.64")
711 (28")
12
CENTERING
SCREWS
M10
INLET/
OUTLET AIR
INLET/
OUTLET AIR
30
110
ANTIVIBRATION
DEVICE
213
=
195 (7.68")
323.5 (12.79")
N°2 CABLE GLANDS TYPE
M25x1.5
X DETAIL
394 (15.5")
Ø130
Ø42
EYE-BOLT
X DETAIL
EYE-BOLT
100 (3.93")
N°4 HOLES Ø14
The double tank solution is reliable and drastically reduces any moisture entering the transformer
6
=
ANTIVIBRATION
DEVICE
Overall dimensions type SDB-15
721 (28.38")
764 (30.07")
12 (0.47")
CENTERING
SCREWS
M10
ANTIVIBRATION
DEVICE
INLET/
OUTLET AIR
N°2 CABLE GLANDS TYPE
M25x1.5
30 (1.18")
110 (4.33")
213 (8.38")
323 (12.71")
DETAIL X
X DETAIL
N°4 HOLES Ø14 (0.55")
EYE-BOLT
100 (3.93")
EYE-BOLT
Ø42 (1.65")
207 (8.15")
Ø130 (5.12")
The coaxial tank allows you to have the advantages of the double tank while having a compact configuration
7
SDB-10 operating principle
During the normal operation the oil conservator intakes air that
passes through the metallic filter. The metallic filter stops dust,
sand and other particles from the contaminating air. The air then
passes through the salt tank 1.
The salt tank is filled with silica gel that absorbs the moisture.
The dehydrated air goes through piping to the oil conservator.
When the silica gel absorbs the moisture in the air, the weight
of the salt increases and is constantly monitored by a weighing
cell. When the weight increases and exceeds the pre-set value a
solenoid valve blocks the passage of air through salt tank 1 and
deviates through the main self-dehydrating breather by the pipe
connected on one of the two plug.
SDB-30
8
At the same time, a heating system inside tank 1 is activated. The
water vapor leaving the silica gel is expelled outward by a fan
that also dissipates the heat. Inside the salt, a probe controls the
temperature of the heating element.
During the functioning of the device, the weighing cell
temperature is monitored by a temperature sensor mounted in
the upper part.
After the salt regeneration in tank 1 (timed regeneration), the
solenoid valve is de-energized.
No maintenance is required for replacement and regeneration of
the desiccant.
SDB-10
Overall dimensions type SDB-10
12 (0.47")
CENTERING
SCREWS
713 (28.07")
756 (29.76")
MAIN TANK
CONNECTION (1/4"G)
M10
INLET/
OUTLET AIR
ANTIVIBRATION
DEVICE
110(4.33")
30 (1.18")
213 (8.38")
323.5 (12.73")
DETAIL X
N°4 HOLES Ø14
X DETAIL
100 (3.93")
Ø42
Ø130 (5.12")
207 (8.15")
The single tank used in combination with the SDB-30 or SDB-15 allows you to have the same advantages
as the other models while reducing the total cost.
9
Self dehydrating breather type SDB
Technical features
SDB-10
Standard connection flange
Maximum oil volume
SDB-15
SDB-30
DN40 flange in accordance with standard UNI EN 1092-1:2003
45 m , 40 tons oil, 12,000 gals
90 m3, 80 tons oil, 24,000 gals
3
Standard color
RAL 9002 **
Ambient temperature
-40 to +80°C / -40 to + 176 °F ***
Terminal box degree of protection
IP65 in accordance with EN 60529
Weight
Salt weight
22 Kg/48.5lb
28 kg/61.7 lb
37 kg/81.6 lb
tank 1 with approx.
2.0 Kg/4.4 lb
of silica gel
tank 1 with approx.
2.5 kg/5.5 lb and tank
2 with approx.
2 Kg/4.4 lb of silica gel
Two tanks with approx.
3 kg/6.6 lb
of silica gel each
Vibration damping
Optional antivibration supports can be anchored to the transformer
Environmental application
Standard painting for moderate salinity areas.
Special treatment for off-shore areas (on request) acc. to ISO 12944
Functional test
Available
Power panel
Degree of protection
IP65 in accordance with EN 60259
Ventilation valve
Available
Cable gland
Wires
Two M25x1.5
4 mm , AWG 24-10 flexible cables with or without terminals.
For digital/analog output advised 4x1 mm2 (4x0.00155”2) / 2x1 mm2 (2x0,0155”2) shielded twisted pair cable
2
Power supply
Supply voltage
115/230V AC/DC ±10% 50/60Hz
Current consumption
Max 100 mA
Current consumption
(during regeneration process)
Heating element insulation
Breaking capacity
3.0A
2 kV 50/60 Hz, 1 min, power terminals - ground /// contacts - ground
Voltage
230V AC
30/110/220V DC
Current
2A
10/03/0,12A
Braking capacity
500VA
cosϕ>0,5
L/R<40 ms
Analog output
Signal output (optional)
Distance for analogical output
4-20 mA
proportional to silica gel saturation level (0% - 4mA …… 100% - 20mA)
~ 200m / 656ft
Digital output (optional)
Digital output
Distance for digital output
Serial RS485 (for more information contact COMEM assistance dept.)
~ 500m / 1640ft
Signal contacts
Dielectric strength of contacts
(short duration power frequency
withstand voltage 1 min)
Between contacts and ground: 2kV
Between contacts in open position: 1kV
** For critical environmental conditions please contact COMEM
*** Below -20 °C/-4 °F the inscriptions on the display disappear until the temperature reaches over -20 °C/-4 °F again
10
SDB Wiring terminals
Standard:
-
POWER FAILURE (terminals 22-24-21) - change-over contact:
NO contact: terminals 24-21
NC contact: terminals 21-22
POWER SUPPLY:
terminals 31-32
SYSTEM FAILURE (terminal 12-14-11) - change-over contact:
NO contact: terminals 14-11
NC contact: terminals 11-12
ANALOG OUTPUT 4÷20 mA (optional):
terminals 41-44
DIGITAL OUTPUT RS485 (optional):
Digital Signal: terminals 3-4
DATA LOG
12
SYSTEM
POWER
POWER
FAILURE
FAILURE
SUPPLY
14
11
POWER FAILURE (terminals 22-21) - NC contact:
NC contact: terminals 24-21
HEATER ON (terminals 12-14-11) - change over contact:
NO contact: terminals 14-11
NC contact: terminals 11-12
ANALOG OUTPUT 4÷20 mA (optional):
terminals 41-44
DIGITAL OUTPUT RS485 (optional):
Digital Signal: terminals 3-4
DATA LOG
24
21
31
32
ANALOG
RS 485
OUTPUT
OUTPUT
41
44
3
4
+
-
B
A
4÷20 mA
230V AC
Available on demand:
-
22
GROUND
12
HEATER
POWER
POWER
ON
FAILURE
SUPPLY
14
11
22
21
31
32
230V AC
GROUND
ANALOG
RS 485
OUTPUT
OUTPUT
41
44
+
-
3
B
4
A
4÷20 mA
11
Self dehydrating breather type SDB-C
Main Benefits for End User are:
1. Increase transformer reliability
Continuous moisture absorption ensured by two independant
silicagel tanks working alternatively.
2. Operational cost savings
Automatic silicagel regeneration process drastically reduce
expensive maintenance activities.
3. Easy to install
Suitable for new installation and retrofit case.
Compatible with with EN and DIN standards.
SDB-C
Effective safety performance trough compact design
SDB-12C/14C
with double coaxial tank with
DIN connection flange*
* DIN flange connection is available for all SDB models upon request
12
SDB-10C
single tank to be used in
combination with other
SDB-12C or SDB-14C
Moisture is a leading cause of transformer aging.
Avoiding moisture ingress into the transformer is paramount to
avoiding outage and maximizing the lifetime of the equipment.
The traditional way of managing this problem is with
conventional breathers which are expensive to maintain
and present a significant risk of moisture entering into the
transformer between checks. In response to this situation,
COMEM has developed the Self Dehydrating Breather (SDB-C)
which delivers the best performance of any low maintenance
solution on the market:
COMEM SDB-C is the only solution to guarantee a consistent
flow of dry air, out-performing both conventional breathers and
alternative low maintenance solutions.
Self Dehydrating Breather SDB-C family is the right choice in
order to minimize the possible risk of transformer outage due to
insulation fluid impairment through moisture: thanks to its unique
and proven working principle, the air is always fully dehydrated
because silicagel tanks are independent each other thus the
regeneration process does not start simultaneously in the two
tanks.
13
Self dehydrating breather type SDB-C
Model selection
The below number and size of Self Dehydrating Breathers are ‘Rule of Thumb’ recommendations for the devices in question. This is to
be considered as a guide only and should not replace good design and engineering practice and experience
Application
SDB-10
SDB-10C*
SDB-12C
SDB-14C
SDB-15
SDB-30
OLTC
Petersen Coil
Cable boxes
Traction
Network <40 MVA
Phase shifting <40 MVA
Shunt reactors <40 MVA
Network ≥40 MVA ≤200 MVA
Phase shifting ≥40 MVA ≤200 MVA
Shunt reactors ≥40 MVA ≤200 MVA
Step up ≥40 MVA ≤200 MVA
Generator and network >200 MVA
Phase shifting >200 MVA
Shunt reactors >200 MVA
HVDC
Furnace
Cavern
GSU
* = SDB-10C to be used in combination with SDB-12C or SDB-14C
Main Features
SDB
Tank Working principle
Fitting
Notes
SDB-10
1
Continuous silicagel monitoring
OLTC
In combination with SDB-15 or SDB-30
SDB-10C
1
Adjustable time based regeneration
OLTC
In combination with SDB-12C or SDB-14C
SDB-12C
2
Adjustable time based regeneration
OLTC
Stand alone
SDB-14C
2
Adjustable time based regeneration
Oil conservator
Stand alone
SDB-15
2
Continuous silicagel monitoring
Oil conservator
Stand alone
SDB-030
2
Continuous silicagel monitoring
Oil conservator
Stand alone
14
SDB-12C/14C operating principle
The self-dehydrating air breather works in accordance with the
following principles.
During the normal operation the oil conservator intakes air that
passes through the metallic filter. The metallic filter stops dust,
sand and other particles from the contaminating air. The air then
passes through the salt tank 1.
The salt tank is filled with silica gel that absorbs the moisture.
The dehydrated air goes through piping to the oil conservator.
After a pre-determinate time (adjustable) a solenoid valve blocks
the passage of air through salt tank 1 and deviates through the
“plenum chamber ” 2.
At the same time, a heating system inside tank 1 is activated. The
water vapor leaving the silica gel is expelled outward by gravity.
Inside the salt, a probe controls the temperature of the heating
element.
As soon as the salt regeneration in tank 1 is completed, the
solenoid valve is de-energized and the airflow through tank 2 is
inhibited. The salt in this tank (2) is also dehydrated, regeneration
of the salt in tank 2 follows automatically.
No maintenance is required for replacement and regeneration of
the desiccant.
15
Overall dimensions type SDB-12C/14C
3
Detail A
N°4 HOLES
4
100
100
14 (0.55")
586 (23.07")
628.5 (24.74") 628.5 (24.74")
N°4 HOLES
586 (23.07")
100
35 (1.65")
35 (1.65")
275.5 (10.84")
110 (4.33")
35 (1.65")
A
130 (5.12")
A
5
275.5 (10.84")
175.5
(6.91")
110 (4.33")
285.5 (11.24")
INLET/
OUTLET AIR
175.5 (6.91")
285.5 (11.24")
275.5 (10.84")
110 (4.33")
175.5 (6.91")
Detail A
N°4 HOLES
628.5 (24.74")
B
NOTES:
200.5 (7.89")
1
---
Materiale
Material
Rives. / Tratt.
Protec. / Treat.
--
Rives. / Tratt.
Protec. / Treat.
Dimensioni in mm
Dimensions in mm
- MINIMUM CONNECTIONS
METAL SHEET THICKNESS:
5mm
- MINIMUM CONNECTIONS
METAL SHEET
THICKNESS: 5mm
Scala:
- ADVISED DIAMETER
HOLE
OF THE METAL
- ADVISED
DIAMETER
HOLE OF THE METAL
Scale:
1:5
SHEET CSUPPORT
DEVICE:
Ø13 mm
SHEET
SUPPORT
DEVICE: Ø13 mm
- FOR THE INSTALLATION
THE FOLLOW THE
- FOR THE FOLLOW
INSTALLATION
Data:
NOTES:
26/02/14
200.5 (7.89")
MANUAL INSTRUCTION
Date:
MANUAL INSTRUCTION
2
200.5 (7.89")
2
2
285.5 (11.24")
Materiale
Material
NOTES:
D
1
14 (0.55")
- MINIMUM CONNECTIONS METAL SHEET THICKNESS: 5mm
- ADVISED DIAMETER HOLE OF THE METAL
SHEET SUPPORT DEVICE: Ø13 mm
35 (1.65")
3 THE INSTALLATION
4
5
3
4
- FOR
FOLLOW
THE
130 (5.12")
MANUAL INSTRUCTION
---
100
--
Tolleranze Generali
General Tolerances
A
Dimensioni
Dimensions
---
<=3
>3
<=6
Dimensioni
>6
>30
<=30
<=120
Dimensions
0.05
0.1
0.15
>120
<=3
<=400
>400
>3
<=1000
<=6
0.2 0.05 0.3
>1000
>6
<=2000
<=30
>2000
>30
<=4000
<=120
0.5
0.1
0.15
Materiale
0.1
0.2
0.3
0.5 0.1 0.8
1.2
0.2
0.32
Material
Dimensioni in mm
Dimensions in mm
0.2
0.3
0.5
0.8
1.2
0.2
0.32
0.53
0.84
Rives. / Tratt.
Protec.
Treat.
Scala: /Proprietà
della COMEM. Senza autorizzazione
dalla stessa
il presente
disegno scritta
non potrà
pe
Proprietàscritta
della COMEM.
Senza
autorizzazione
dallaessere
stessautilizzato
il presente
Scale: dell'oggetto rappresentato né venire comunicato
o riprodotto.
società
proprietaria
tutela
i propri diritti
a no
dell'oggettoa terzi
rappresentato
né La
venire
comunicato
a terzi
o riprodotto.
La socie
Dimensioni
>3
>6
>30
<=3 must
All property rights of COMEM. This drawing
must not
be reproduced
anydrawing
medium
nor <=6
utilized
for<=30
the manufacture
All property
rights
of COMEM.inThis
not be reproduced
in any m
<=120
Dimensions
herein rapresented or disclosed to other
parties
without ourorlicence.
Anytoinfringement
be legally
persecuted.
herein
rapresented
disclosed
other partieswill
without
our licence.
Any infri
--
1:5
Data: Riferimenti:
Date: References:
Dimensioni in mm
Dimensions in mm
26/02/14
Scala:
Scale:
Data:
Date:
Riferimenti:
References:
Descrizione Description
0.05
Sost.:
Replaced:
NE-318
0.1
Descrizione Description
0.2
0.1
0.15
0.2
0.3
Disegn.:
Sost.:
Operat.:
Replaced:
Codice - Part Nu
0.3
0.5
0.8
ESSICCATORE
SDB-012/014
ESSICCATORE SDB-012
Proprietà della COMEM. Senza autorizzazione scritta dalla stessa il presente
dell'oggetto rappresentato né venire comunicato a terzi o riprodotto. La socie
INGOMBRI
INGOMBRI
1:5
All property rights of COMEM. This drawing must not be reproduced in any m
herein rapresented or disclosed to other parties without our licence. Any infrin
6
7
5
6
26/02/14
Riferimenti:
References:
INLET/
OUTLET AIR
3
12 (0.47")
INLET/
OUTLET AIR
4
586 (23.07")
INLET/
OUTLET AIR
3
130 (5.12")
Tolleranze Generali
General Tolerances
2
130 (5.12")
Tolleranze Generali
General Tolerances
1
A
6
14 (0.55")
Detail A
7
6
5
Detail A
14
(0.55")
N°4
HOLES
6
5
12 (0.47")
2
5
4
12 (0.47")
1
4
3
12 (0.47")
3
2
586 (23.07")
2
1
275.5 (10.84")
Sost.:
Replaced:
Descrizione Description
SDB-012
110ESSICCATORE
(4.33")
175.5 (6.91")
4
The double tank solution is reliable and drastically
reduces any moisture entering the transformer
A
5
INGOMBRI
6
285.5 (11.24")
E
---Tolleranze Generali
General Tolerances
Materiale
Material
Rives. / Tratt.
Protec. / Treat.
NOTES:
16
F
200.5 (7.89")
- MINIMUM CONNECTIONS METAL SHEET THICKNESS: 5mm
- ADVISED DIAMETER HOLE OF THE METAL
SHEET SUPPORT DEVICE: Ø13 mm
- FOR THE INSTALLATION FOLLOW THE
MANUAL INSTRUCTION
Dimensioni in mm
Dimensions in mm
Scala:
Scale:
Data:
Date:
1:5
26/02/14
Dim
Dim
Proprietà della COMEM.
dell'oggetto rappresentato
All property rights of COM
herein rapresented or dis
Riferimenti:
References:
Descr
SDB-10C operating principle
The self-dehydrating air breather works in accordance with the
following principles.
During the normal operation the oil conservator intakes air that
passes through the metallic filter. The metallic filter stops dust,
sand and other particles from the contaminating air.
The air then passes through the salt tank 1.
The salt tank is filled with silica gel that absorbs the moisture.
The dehydrated air goes through piping to the oil conservator.
After a pre-determinate time (settable) a solenoid valve blocks
the passage of air through salt tank 1 and deviates through the
main self-dehydrating breather (SDB-14C, SDB-15 or SDB-30) by
the pipe connected on one of the two plug.
At the same time, a heating system inside tank 1 is activated.
The water vapor leaving the silica gel is expelled outward by
gravity. Inside the salt, a probe controls the temperature of the
heating element.
As soon as the salt regeneration in tank 1 is completed, the
solenoid valve is de-energized.
No maintenance is required for replacement and regeneration of
the desiccant.
SDB-10C
SDB-14C
17
Overall dimensions type SDB-10C
1 2
2 3
3 4
4 5
1
2
3
4
5 6
260.5 (10.25")
14 (0.55") N°4 HOLES
14 (0.55")
100
Detail A
B
100
554 (21.81")
B
14 (0.55")
511 (20.12")
554 (21.81")
N°4 HOLES
511 (20.12")
100
C
260.5 (10.25")
12 (0.47")
N°4 HOLES
Detail A
6
12 (0.47")
A
12 (0.47")
Detail A
260.5 (10.25")
5
511 (20.12")
A
6 7
35 (1.65")
C
1
2
INLET/ 130 (5.12")
OUTLET AIR
INLET/
OUTLET AIR
D
35 (1.65")
4
175.5 (6.91")
285.5 (11.24")
110 (4.33")
130 (5.12")
INLET/
OUTLET AIR
A
5
110 (4.33")
175.5 (6.91")
285.5 (11.24")
35 (1.65")
A
A
3
110 (4.33")
130 (5.12")
Detail A
D
N°4 HOLES
260.5 (10.25")
175.5 (6.91")
285.5 (11.24")
14 (0.55")
100
554 (21.81")
NOTES:
NOTES:
Materiale
Material
---
Materiale
Material
Rives. / Tratt.
Protec. / Treat.
--
Rives. / Tratt.
Protec. / Treat.
----
Dimensioni
Dimensions
<=3
>3
>6
>30
>120Dimensioni
>400
>1000
<=3
>2000
>3
>6
Scale:
F
209 (8.22")
1 2
D
2 3
1:5
Scale:
dell'oggetto rappresentato
né venire comunicato a terzi o riprodotto.
dell'oggetto
La società
rappresentato
proprietaria
né venire
tutela comunicato
i propri dirittiaaterzi
norma
o riprodo
di leg
Dimensioni
>3
>6
All property rights of COMEM. This drawing must not be reproduced
All property
in any
rights
medium
of COMEM.
nor utilized
Thisfor
drawing
the<=3
manufacture
must not beofreprodu
the art
1:5
<=6
<=30
Dimensions
- MINIMUM CONNECTIONS METAL SHEET THICKNESS: 5mm
herein rapresented or disclosed to other parties without our licence.
herein rapresented
Any infringement
or disclosed
will be legally
to otherpersecuted.
parties without our licen
0.05
0.1
Data:
Riferimenti: Data:
Sost.:
Riferimenti:
Disegn.:
Sost
- ADVISED DIAMETER HOLE OF THE METAL
35
(1.65")
26/02/14
26/02/14
Ton
Date:
References: Date:
Replaced:
References:
Operat.:
Repl
0.1
0.2
SHEET SUPPORT DEVICE: Ø13 mm
Dimensioni in mm
Descrizione Description
Descrizione Description
Codice - Part Number
Dimensions in mm
0.2
0.3
0.5
- FOR THE INSTALLATION
FOLLOW
THE
110
(4.33")
175.5
(6
130
(5.12")
INLET/
ESSICCATORE SDB-010
ESSICCATORE SD
Scala:
MANUAL INSTRUCTION
Proprietà della COMEM. Senza autorizzazione scritta dalla stess
OUTLET AIR
Scale:
dell'oggetto rappresentato
né venire comunicato a terzi o riprodo
INGOMBRI
INGOMBRI
(11.24")
1:5
All property rights of COMEM. This285.5
drawing must
not be reprodu
herein rapresented or disclosed to other parties without our licen
3 4
4 5
5 6
6 7
Data:
Date:
The single tank used in combination with the SDB-30 or SDB-15 allows you to have the same advantages
as the other models while reducing the total cost.
A
1
2
3
4
26/02/14
Tolleranze Generali
General Tolerances
209 (8.22")
Tolleranze Generali
General Tolerances
Tolleranze Generali
General Tolerances
<=6
<=30
<=120
<=400
<=1000 <=2000 <=4000
<=6
<=30
Dimensions
Va
- MINIMUM CONNECTIONS
- MINIMUM
METAL SHEET
CONNECTIONS
THICKNESS:
METAL
5mmSHEET THICKNESS: 5mm
Ang
0.05
0.1
0.15
0.2
0.3
0.5 0.05
0.1
- ADVISED DIAMETER HOLE
- ADVISED
OF THEDIAMETER
METAL
HOLE OF THE METAL
Materiale
An
0.2
0.3
0.5
0.8
1.2 0.1 2
0.2
SHEET SUPPORT DEVICE:
SHEET
Ø13 mm
SUPPORT DEVICE: Ø13 mm Dimensioni in mm
- -0.1Dimensioni
Material in mm
Va
Dimensions in mm
Dimensions in mm
C
0.2
0.3
0.5
0.8
1.2
2
30.2
40.3
0.5
- FOR THE INSTALLATION
- FOR
FOLLOW
THE INSTALLATION
THE
FOLLOW THE
Rives. / Tratt.
209 (8.22")
NOTES:
Protec.
/
Treat.
Scala:
MANUAL INSTRUCTION MANUAL INSTRUCTION
Proprietà della Scala:
COMEM. Senza autorizzazione scritta dalla stessa
Proprietà
il presente
della COMEM.
disegno Senza
non potrà
autorizzazione
essere utilizzato
scrittaper
dalla
la costr
stess
E
F
511 (20.12")
A
B
E
Riferimenti:
References:
Sost
Repl
Descrizione Description
ESSICCATORE SD
INGOMBRI
6
5
E
209 (8.22")
18
- MINIMUM CONNECTIONS METAL SHEET THICKNESS: 5mm
- ADVISED DIAMETER HOLE OF THE METAL
SHEET SUPPORT DEVICE: Ø13 mm
- FOR THE INSTALLATION FOLLOW THE
MANUAL INSTRUCTION
Materiale
Material
---
Rives. / Tratt.
Protec. / Treat.
-Tolleranze Generali
General Tolerances
NOTES:
Dimensioni in mm
Dimensions in mm
Scala:
Scale:
F
Data:
1:5
D
D
Proprietà della COMEM
dell'oggetto rappresenta
All property rights of CO
herein rapresented or d
Riferimenti:
Self dehydrating breather type SDB-C
Technical features
SDB-10C
Standard connection flange
SDB-12C
DN40 flange in accordance with standard UNI EN 1092-1:2003
45 m3, 40 tons oil, 12,000 gals
Maximum oil volume
Standard color
RAL 9002 **
Ambient temperature
-40 to +80°C / -40 to + 176 °F ***
Terminal box degree of protection
IP65 in accordance with EN 60529
Weight
Salt weight
SDB-14C
12 kg/26,45 lb
18 kg/39,6 lb
18 kg/39,6 lb
tank 1 with approx.
2.0 Kg/4.4 lb
of silica gel
tank 1 with approx.
2 kg/4.4 lb and tank
2 with approx.
1 Kg/2.2 lb of silica gel
tank 1 with approx.
2 kg/4.4 lb and tank
2 with approx.
1 Kg/2.2 lb of silica gel
Vibration damping
Optional antivibration supports can be anchored to the transformer
Environmental application
Standard painting for moderate salinity areas.
Special treatment for off-shore areas (on request) acc. to ISO 12944
Functional test
Available
Power panel
Degree of protection
IP65 in accordance with EN 60259
Ventilation valve
Available
Cable gland
Wires
Two M25x1.5
4 mm , AWG 24-10 flexible cables with or without terminals.
For digital/analog output advised 4x1 mm2 (4x0.00155”2) / 2x1 mm2 (2x0,0155”2) shielded twisted pair cable
2
Power supply
Supply voltage
115/230V AC/DC ±10% 50/60Hz
Current consumption
Max 100 mA
Current consumption
(during regeneration process)
Heating element insulation
Breaking capacity
3.0A
2 kV 50/60 Hz, 1 min, power terminals - ground /// contacts - ground
Voltage
230V AC
30/110/220V DC
Current
2A
10/03/0,12A
Braking capacity
500VA
cosϕ>0,5
L/R<40 ms
Analog output
Signal output (optional)
Distance for analogical output
4-20 mA
proportional to tank 1 temperature
~ 200m / 656ft
Digital output (optional)
Digital output
Distance for digital output
Serial RS485 (for more information contact COMEM assistance dept.)
~ 500m / 1640ft
Signal contacts
Dielectric strength of contacts
(short duration power frequency
withstand voltage 1 min)
Between contacts and ground: 2kV
Between contacts in open position: 1kV
** For critical environmental conditions please contact COMEM
*** Below -20 °C/-4 °F the inscriptions on the display disappear until the temperature reaches over -20 °C/-4 °F again
19
SDB-C Wiring terminals
Standard:
-
POWER FAILURE (terminals 22-24-21) - change-over contact:
NO contact: terminals 24-21
NC contact: terminals 21-22
POWER SUPPLY:
terminals 31-32
SYSTEM FAILURE (terminal 12-14-11) - change-over contact:
NO contact: terminals 14-11
NC contact: terminals 11-12
ANALOG OUTPUT 4÷20 mA (optional):
terminals 41-44
DIGITAL OUTPUT RS485 (optional):
Digital Signal: terminals 3-4
DATA LOG
12
SYSTEM
POWER
POWER
FAILURE
FAILURE
SUPPLY
14
11
20
POWER FAILURE (terminals 22-21) - NC contact:
NC contact: terminals 24-21
HEATER ON (terminals 12-14-11) - change over contact:
NO contact: terminals 14-11
NC contact: terminals 11-12
ANALOG OUTPUT 4÷20 mA (optional):
terminals 41-44
DIGITAL OUTPUT RS485 (optional):
Digital Signal: terminals 3-4
DATA LOG
24
21
31
32
ANALOG
RS 485
OUTPUT
OUTPUT
41
44
3
4
+
-
B
A
4÷20 mA
230V AC
Available on demand:
-
22
GROUND
12
HEATER
POWER
POWER
ON
FAILURE
SUPPLY
14
11
22
21
31
32
230V AC
GROUND
ANALOG
RS 485
OUTPUT
OUTPUT
41
44
+
-
4÷20 mA
3
B
4
A
SDB and SDB-C order sheet
3
4
-
2
-
1
A
A
SDB-10
-
Others
-
SDB version
Damper
SDB-15
Connection flange
B
B
DN40 flange in accordance with
standard UNI EN 1092-1:2003
(standard)
SDB-30
DIN flange
(similar to DIN 42 562-3)
SDB-C version
SDB-10C
Overpressure valve
C
C
SDB-12C
Options
SDB-14C
MODBUS RTU
Supply Voltage
DATA LOGGER (DATA LOGGER
VIA MODBUS)
D
D
230V AC/DC
-
4-20 mA
115V AC/DC
Modifiche
Moderate
salinity areas
Alterations
acc. to ISO E12944 (standard)
E
Materiale
* extension voltage range between
90 to- 270V
AC/DC
-Material
Color
Dimensioni
in mm
RAL 9002
standard
Dimensions in mm
Scala:
Scale:
F
Special
Off-shore areas
acc. to ISO 12944
--
1:5
Data:
Date:
Tolleranze Generali
General Tolerances
Rives. / Tratt.
Protec. / Treat.
Dimensioni
Dimensions
>3
<=6
<=3
>6
<=30
>30
>120
>400 >1000 >2000
<=120 <=400 <=1000 <=2000 <=4000
0.05
0.1
0.15
0.2
0.3
0.5
0.1
0.2
0.3
0.5
0.8
1.2
2
0.5
0.8
1.2
2
3
4
0.2
0.3
Valori
Angolari
30'
Angular
Values
Riferimenti:
References:
Sost.:
Replaced:
Disegn.:
Operat.:
Peso Grezzo
Gross. Wt.
Codice Part Number
2
Peso Netto
Net. Wt.
Carton boxF(standard)
Contr.:
Chkd.:
3
03
Dis. Drwg.
1
Packaging
Proprietà della COMEM. Senza autorizzazione scritta dalla stessa il presente disegno non potrà essere utilizzato per la costruzione
dell'oggetto rappresentato né venire comunicato a terzi o riprodotto. La società proprietaria tutela i propri diritti a norma di legge.
All property rights of COMEM. This drawing must not be reproduced in any medium nor utilized for the manufacture of the article
herein rapresented or disclosed to other parties without our licence. Any infringement will be legally persecuted.
Descrizione Description
Cable gland
0
1
Environmental protection
Overvoltage protection*
3+
Wood box
4
2x M25x1,5 (standard)
Special
21
Strada Regionale 11, Signolo 22
36054 Montebello Vicentino (VI) - ITALY
Tel. +39 0444 449311
Fax +39 0444 449352 - 440359
E-mail: [email protected]
www.comem.com
Due to technical product updates, the information
contained in this catalogue may be subject to change
without notice.
© Copyright 2014 COMEM.
All rights reserved.
Ed. 03/2015