NYC Department of Education
Building Condition Assessment Survey 2014-2015
Architectural Inspection
M506
EDWARD A. REYNOLDS WEST SIDE HS-M, 140 WEST 102 STREET, MANHATTAN, NY, 10025
School:
InspectionId
Inspection Type
12231 ARCHITECTURAL - SENIOR
12304 ARCHITECTURAL - ASSOCIATE
Time In
Last Edited
2015-04-28 11:53AM
2015-04-28 12:23PM
2015-06-17 04:03PM
2015-05-13 01:16PM
Asset Data
Question
Answer
Was the Building Fully Accessible for Inspection?
Principal(s) Information
Principal Name
Principal Organization
Meeting with Principal?
Principal Feedback
Custodian
Fireman
Building Square Footage
Comments on the Area (Square Feet)
Comments on the Stories (Floors) plus Basements
Comments on the Year Built
Comments on the Student Population
Comments on the Staff Population
Comments on the Number of Classrooms
Weather
Facade Photo
Yes
Jean McTavish
Edward A. Reynolds West Side High School - Manhattan
No
No Feedback from Principal
Was not present
Ali Tarat
85,000
None
3+B
1999
541
63
27
Fair
West 102nd Street Facade
Main Entrance Photo
Main Entrance, 102nd Street
Mobile Validity Version 2.0 (P)
Page 1 of 31
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Architectural Inspection
M506
Roof Photo
Have any Systems/Major Building Components been upgraded?
Roof 1
Systems:
Limited Exterior Stair repairs
Years:
Systems:
2015
Flooring refinished, Gymnasium
Years:
Systems:
2008
Flooring replaced, Library
Years:
Systems:
2007
Exterior Soffit, Parapet repairs
Have there been any New Building Additions?
Tandem
Years:
2013
No New Construction
No Tandem
Leased Space?
No
Priority Condition
Priority Condition
Exist Last Year?
Priority
Category
Condition
Description
Component
Affected
Location
Description
Person(s) Notified
Person(s) Title
PhotoImage
No condition recorded
Structural Engineer Required
Structural Condition
Type
Condition
Description
Component
Affected
Location
Description
Person(s)
Notified
Person(s) Title
PhotoImage
No condition recorded
Accessibility
Accessibility Status Question
Response
Is the Primary or secondary entrance on an accessible route?
Is the building a multi-story building?
Are All floors of the building accessible through compliant means?
Accessible classrooms exists on each floor?
Boys and Girls or Unisex accessible toilets exist on at least every other floor?
If the following spaces exist, are they ALL accessible? Art Room, Auditorium,
Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs
Yes
Yes
Yes
Yes
Yes
Yes
Physical Breakdown Structure
Exists
Complies
Required
Deficiency
FUNCTIONAL ACCESSIBILITY
Exterior Routes
Yes
Exterior Entrances & Exits
Exterior H/C Lifts
No
Exterior Ramps and Railings
Yes
Yes
No
Yes
Yes
Interior Routes
Interior Corridor Doors And Hardware
Yes
Interior Corridors & Lobbies
Interior Elevators
Mobile Validity Version 2.0 (P)
Yes
Yes
Page 2 of 31
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Architectural Inspection
Physical Breakdown Structure
Interior H/C Lifts
M506
Exists
Complies
No
Required
Deficiency
No
Yes
Interior Lobby Doors And Hardware
No
Interior Ramps
Rooms & Spaces
Art Rooms
Room 222
Yes
Yes
No
Auditorium
Cafeteria
Basement
Yes
Yes
2nd, 3rd Floors
Yes
Yes
Yes
Yes
Basement
Yes
Yes
Room 100
Yes
Yes
Room 130
Yes
Yes
Classrooms
Computer Rooms
Rooms 203, 227, 327
Gymnasium
Library
Main Office
Multi-purpose Room
No
Nurse's Office
Room B12
Yes
Yes
No
Pool
Science Lab
Rooms 202, 210
Yes
Yes
Toilet Rooms (boys)
All Floors
Yes
Yes
Toilet Rooms (girls)
All Floors
Yes
Yes
Toilet Rooms (staff)
All Floors
Yes
Yes
Building Template
Inspection
Mobile Validity Version 2.0 (P)
Page 3 of 31
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Architectural Inspection
M506
Question
Response
Architectural
ATHLETIC FIELDS
Does not exist
EXTERIOR
Inspected
AREAWAY
Does not exist
AWNINGS AND CANOPIES
Does not exist
CHIMNEY
Does not exist
COPING
Inspected
3- Fair
Condition
Deficiency
CAST STONE:OPEN TRANSVERSE JOINTS WITH
DAMAGED CAULKING
Deficiency Location/Instance
Deficiency Quantity
80
L.F.
MAINTENANCE
PRIORITY 4
LEVEL 2
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
Roof 1, Facade A
Violations
No violations recorded
Deficiency
Deficiency Location/Instance
CAST STONE:CRACKED/BROKEN PIECES
Deficiency Quantity
60
L.F.
REPLACE-IN-KIND
PRIORITY 3
LEVEL 2
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
Roof 1, Facade C
Violations
No violations recorded
CORNICE
Does not exist
DOORS
Inspected
Mobile Validity Version 2.0 (P)
Page 4 of 31
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Architectural Inspection
M506
Question
Response
EXTERIOR
DOORS
Inspected
DOOR HARDWARE
Condition
2- Between Good and Fair
Inspected
DOORS AND FRAMES
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Inspected
LINTELS
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Inspected
TRANSOM/SIDE LIGHT
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Inspected
EXTERIOR SOFFITS
2- Between Good and Fair
Condition
Deficiency
No deficiencies recorded
Inspected
EXTERIOR WALLS
Material Type(s)
Masonry
Replacement Quantity
Replacement Uom
25,000
S.F.
Instance on All Facades
Inspected
Instance Condition
3- Fair
Instance Quantity
Instance Quantity Uom
25,000
SF
Deficiency
Roof Plan Reference
BRICK:MINOR CRACKS AND SPALLING
Elevation
Elevation Reference
Deficiency Quantity
Facade D
250
S.F.
RESTITCH
PRIORITY 3
LEVEL 2
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
Main Entrance
Violations
No violations recorded
Deficiency
Mobile Validity Version 2.0 (P)
BRICK:OPEN/BAD JOINTS
Page 5 of 31
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Architectural Inspection
M506
Question
Response
EXTERIOR
EXTERIOR WALLS
Roof Plan Reference
Elevation
Elevation Reference
Deficiency Quantity
All Facades
500
S.F.
REPOINT
PRIORITY 3
LEVEL 2
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
Facade A
Violations
No violations recorded
Deficiency
Roof Plan Reference
BRICK:MAJOR / THRU CRACKS
Elevation
Elevation Reference
Deficiency Quantity
Facade D
100
S.F.
REMOVE AND REBUILD
PRIORITY 4
LEVEL 2
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Mobile Validity Version 2.0 (P)
Page 6 of 31
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Architectural Inspection
M506
Question
Response
EXTERIOR
EXTERIOR WALLS
Deficiency Photo 1
Top of Stair
Deficiency Photo 2
Below first photo
Violations
No violations recorded
LOADING DOCK
Does not exist
LOUVER
Inspected
2- Between Good and Fair
Condition
Deficiency
No deficiencies recorded
Inspected
PARAPETS
Material Type(s)
Masonry, Concrete, Other
Replacement Quantity
Replacement Uom
8,000
C.F.
Instance on All Facades
Inspected
Instance Condition
2- Between Good and Fair
Instance Quantity
Instance Quantity Uom
8,000
CF
Deficiency
No deficiencies recorded
Inspected
PLAZA DECK
Instance on Concrete:Roof 3
Inspected
Instance Condition
3- Fair
Instance Quantity
Instance Quantity Uom
Installation Year
Source of Installation Year
4,000
SF
1999
Custodial staff
Deficiency
Deficiency Location/Instance
CONCRETE:OPEN JOINTS WITH DAMAGED CAULKING
Deficiency Quantity
80
L.F.
MAINTENANCE
PRIORITY 5
LEVEL 2
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Mobile Validity Version 2.0 (P)
Page 7 of 31
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Architectural Inspection
M506
Question
Response
EXTERIOR
PLAZA DECK
Deficiency Photo 1
Main Entrance
Violations
No violations recorded
Deficiency
Deficiency Location/Instance
CONCRETE:MAJOR LEAKAGE
Deficiency Quantity
100
S.F.
REPLACE
PRIORITY 5
LEVEL 6
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
Electrical Panel Room
Violations
No violations recorded
Inspected
ROOF
Inspected
Roofing
Replacement Quantity
Replacement Uom
26,000
S.F.
LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS
Inspected
2- Between Good and Fair
Condition
Deficiency
No deficiencies recorded
ROOF BARRIER
Does not exist
ROOF CAGE
Does not exist
ROOF FENCE
Does not exist
ROOF HATCH/SMOKE HATCH
Inspected
2- Between Good and Fair
Condition
Deficiency
No deficiencies recorded
Inspected
ROOFING
Instance on Single Ply, Fully Adhered Roof:Single Ply Fully Adhered Roofs 1 & 2
Instance Condition
Inspected
Instance Quantity
Instance Quantity Uom
"Does the roof have major mechanical equipment?'
Installation Year
26,000
S.F.
Yes
1999
Mobile Validity Version 2.0 (P)
Page 8 of 31
4- Between Fair and Poor
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Architectural Inspection
M506
Question
Response
EXTERIOR
ROOF
Roofing
ROOFING
Source of Installation Year
Custodial staff
Deficiency
SINGLE PLY, FULLY ADHERED ROOF:ROOFING:OPEN
SEAMS
Deficiency Location/Instance
Deficiency Quantity
180
L.F.
REPAIR
PRIORITY 5
LEVEL 2
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
Roof 1
Violations
No violations recorded
Deficiency
SINGLE PLY, FULLY ADHERED ROOF:ROOFING:MAJOR
ACTIVE ROOF LEAKS IN INSTRUCTIONAL SPACE
Deficiency Location/Instance
Deficiency Quantity
100
S.F.
REPLACE ROOFING WITH MAJOR EQUIPMENT
REMOVAL
PRIORITY 5
LEVEL 2
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
Room 318, also found in Gymnasium, Rooms 312, 314, 327, 328
Violations
No violations recorded
Inspected
ROOFING DRAINS
2- Between Good and Fair
Condition
Deficiency
Mobile Validity Version 2.0 (P)
No deficiencies recorded
Page 9 of 31
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Architectural Inspection
M506
Question
Response
EXTERIOR
ROOF
Inspected
Specialties
Inspected
BULKHEAD/PENTHOUSE
2- Between Good and Fair
Condition
Deficiency
No deficiencies recorded
CUPOLA/ SPIRES/ TOWERS
Does not exist
DORMER
Does not exist
DUNNAGE STEEL
Inspected
3- Fair
Condition
Deficiency
Deficiency Location/Instance
HEIGHT LESS THAN 18"
Deficiency Quantity
20
L.F.
REPLACE
PRIORITY 1
LEVEL 1
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
Roof 1
Violations
No violations recorded
Deficiency
Deficiency Location/Instance
MINOR RUSTING
Deficiency Quantity
40
L.F.
MAINTENANCE
PRIORITY 3
LEVEL 2
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
Roof 1
Violations
No violations recorded
Does not exist
ROOF/GRAVITY TANK
Mobile Validity Version 2.0 (P)
Page 10 of 31
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Architectural Inspection
M506
Question
Response
EXTERIOR
ROOF
Specialties
Does not exist
SKYLIGHT/ROOF VENT
Inspected
STAIRS/RAMPS: EXTERIOR
Inspected
BUILDING CHEEK/FLANK WALLS
Condition
4- Between Fair and Poor
Deficiency
Deficiency Location/Instance
BRICK:CRACKS/SPALLING - MAJOR
Deficiency Quantity
40
S.F.
REPLACE
PRIORITY 4
LEVEL 2
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
Facade D at Ramp
Violations
No violations recorded
Deficiency
Deficiency Location/Instance
CAST IN PLACE CONCRETE:CRACKS/SPALLING - MAJOR
Deficiency Quantity
20
S.F.
REPLACE
PRIORITY 4
LEVEL 2
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
Facade D, top of Ramp
Violations
No violations recorded
Deficiency
Mobile Validity Version 2.0 (P)
BRICK:BULGING/DISPLACED
Page 11 of 31
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Architectural Inspection
M506
Question
Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
BUILDING CHEEK/FLANK WALLS
Deficiency Location/Instance
Deficiency Quantity
40
S.F.
REPLACE
PRIORITY 4
LEVEL 2
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
Facade D, Main Entrance Stair
Violations
No violations recorded
Deficiency
Deficiency Location/Instance
STONE:BULGING/DISPLACED
Deficiency Quantity
100
S.F.
REPLACE
PRIORITY 5
LEVEL 2
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
Main Entrance Stair
Violations
No violations recorded
Deficiency
Deficiency Location/Instance
STONE:CRACKS/SPALLING - MINOR
Deficiency Quantity
20
S.F.
Quantity Uom
Mobile Validity Version 2.0 (P)
Page 12 of 31
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Architectural Inspection
M506
Question
Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
BUILDING CHEEK/FLANK WALLS
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
REPAIR
PRIORITY 4
LEVEL 2
Main Entrance Stair
Violations
No violations recorded
Inspected
RAILINGS
Condition
4- Between Fair and Poor
Deficiency
Deficiency Location/Instance
RUST - MAJOR
Deficiency Quantity
50
L.F.
REPLACE
PRIORITY 4
LEVEL 2
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
Severely rusted bases at Ramp
Violations
No violations recorded
Inspected
STAIRS/RAMPS
Condition
4- Between Fair and Poor
Deficiency
Deficiency Location/Instance
CAST IN PLACE CONCRETE:CRACKS/SPALLING - MAJOR
Deficiency Quantity
100
S.F.
REPLACE
PRIORITY 4
LEVEL 2
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Mobile Validity Version 2.0 (P)
Page 13 of 31
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Architectural Inspection
M506
Question
Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
STAIRS/RAMPS
Deficiency Photo 1
Landing at Main Entrance
Violations
No violations recorded
Deficiency
Deficiency Location/Instance
STONE:DETERIORATED SUBSTRATE
Deficiency Quantity
100
S.F.
REPLACE SUBSTRATE AND RESET
PRIORITY 4
LEVEL 2
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
Facade D
Violations
No violations recorded
Inspected
WINDOWS
Replacement Quantity
Replacement Uom
8,000
SF
EXTERIOR GUARDS
Inspected
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Inspected
LINTELS
Condition
3- Fair
Deficiency
Roof Plan Reference
Mobile Validity Version 2.0 (P)
STEEL:MINOR RUSTING
Page 14 of 31
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Architectural Inspection
M506
Question
Response
EXTERIOR
WINDOWS
LINTELS
Elevation
Deficiency Quantity
150
L.F.
MAINTENANCE
PRIORITY 3
LEVEL 2
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
Facade D above Main Entrance
Violations
No violations recorded
Inspected
WINDOWS
Material Type(s)
Instance on Aluminum:All Facades
Aluminum
Inspected
Instance Condition
3- Fair
Instance Quantity
Instance Quantity Uom
Installation Year
Source of Installation Year
8,000
SF
1999
Custodial staff
Deficiency
Roof Plan Reference
ALUMINUM:INOPERABLE BALANCE
Elevation
Elevation Reference
Deficiency Quantity
All Facades
50
EACH
MAINTENANCE
PRIORITY 3
LEVEL 2
No violations recorded
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Inspected
INTERIOR
Does not exist
AUDITORIUM
CAFETERIA
Mobile Validity Version 2.0 (P)
Page 15 of 31
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Architectural Inspection
M506
Question
Response
INTERIOR
CAFETERIA
Instance on Basement
Inspected
Ceiling
Instance on Basement
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Door(s)
Instance on Basement
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Fixed Equipment
Does not exist
Instance on Basement
Floor Finish
Instance on Basement
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Sliding-folding Partition
Instance on Basement
Does not exist
Instance on Basement
Does not exist
Instance on Basement
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Stage
Walls
Window Curtains/Shades/Blinds
Does not exist
Instance on Basement
Inspected
CLASSROOMS/CORRIDORS/ADMIN SPACES
Inspected
Ceiling
Condition
3- Fair
Deficiency
Deficiency Location/Instance
TECTUM:DAMAGED/MISSING
Rooms 300, 306, 310, 312, 324, Corridor at Rooms 114, 116, 130
and Other Locations
450
S.F.
REPLACE
PRIORITY 3
LEVEL 2
Deficiency Quantity
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
Corridor at Room 114
Deficiency Photo 2
East of Room 300
Mobile Validity Version 2.0 (P)
Page 16 of 31
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Architectural Inspection
M506
Question
Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Ceiling
Violations
No violations recorded
Deficiency
Deficiency Location/Instance
TECTUM:DAMAGED/MISSING - ACTIVE LEAK
Rooms 226, 302, 312, 314, 318, 327, Corridor at Room 305 and
Other Locations
400
S.F.
REPLACE
PRIORITY 5
LEVEL 2
Deficiency Quantity
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
Corridor at Room 305
Deficiency Photo 2
East of Room 302
Violations
No violations recorded
Inspected
Door(s)
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Inspected
Floor Finish
Condition
2- Between Good and Fair
Deficiency
Deficiency Location/Instance
Deficiency Quantity
VINYL TILES:BROKEN/DETERIORATED/MISSING TILES
Rooms B16, 130, 217, 226, 230B, 237 , 310 and Other Locations
400
S.F.
REPLACE
PRIORITY 3
LEVEL 2
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
Center of Room 130
Mobile Validity Version 2.0 (P)
Page 17 of 31
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Architectural Inspection
M506
Question
Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish
Deficiency Photo 2
South of Room 310
Violations
No violations recorded
Deficiency
Deficiency Location/Instance
Deficiency Quantity
EPOXY FLOORING:CRACKS/SPALLING
Room 202, 206, 210, 214, 216 & 218
350
S.F.
REPLACE
PRIORITY 3
LEVEL 2
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
Room 210
Deficiency Photo 2
Southwest corner to Room 210
Violations
No violations recorded
Deficiency
Deficiency Location/Instance
Deficiency Quantity
RUBBER NOSING:DETERIORATED
Room B16
10
L.F.
MAINTENANCE
PRIORITY 3
LEVEL 2
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
Center of Room B16
Violations
No violations recorded
Inspected
Specialties
Mobile Validity Version 2.0 (P)
Page 18 of 31
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Architectural Inspection
M506
Question
Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Specialties
Inspected
Classroom Locker(s)
2- Between Good and Fair
Condition
Deficiency
No deficiencies recorded
Does not exist
Fixed Seating
Inspected
Walls
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
GYMNASIUM
Inspected
Instance on Basement
Ceiling
Instance on Basement
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
Deficiency Location/Instance
Deficiency Quantity
METAL PAN:DAMAGED/MISSING - ACTIVE LEAK
East of Room
20
S.F.
REPLACE
PRIORITY 5
LEVEL 2
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
East of Room
Violations
No violations recorded
Door(s)
Instance on Basement
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Fixed Equipment
Instance on Basement
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Floor Finish
Instance on Basement
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
Deficiency Location/Instance
Deficiency Quantity
VINYL TILES:BROKEN/DETERIORATED/MISSING TILES
Center of weight Room (within Gymnasium)
100
S.F.
REPLACE
PRIORITY 3
LEVEL 2
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Mobile Validity Version 2.0 (P)
Page 19 of 31
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Architectural Inspection
M506
Question
Response
INTERIOR
GYMNASIUM
Floor Finish
Deficiency Photo 1
Center of weight Room (within Gymnasium)
Violations
No violations recorded
Seating
Instance on Basement
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Sliding-folding Partition
Instance on Basement
Does not exist
Instance on Basement
Does not exist
Instance on Basement
Inspected
Instance Condition
3- Fair
Deficiency
Deficiency Location/Instance
Deficiency Quantity
PLASTER:CRACKS/SPALLING
Along North and West of Room
200
S.F.
REPLACE
PRIORITY 3
LEVEL 2
Stage
Walls
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
West of Room
Deficiency Photo 2
North of Room
Violations
No violations recorded
Deficiency
Deficiency Location/Instance
Deficiency Quantity
GLAZED BLOCK:CRACKS/SPALLING
Southwest corner of Room
10
S.F.
REPLACE
PRIORITY 3
LEVEL 2
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Mobile Validity Version 2.0 (P)
Page 20 of 31
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Architectural Inspection
M506
Question
Response
INTERIOR
GYMNASIUM
Walls
Deficiency Photo 1
Southwest corner of Room
Violations
No violations recorded
Window Curtains/Shades/Blinds
Does not exist
Instance on Basement
Inspected
INTERIOR DOOR HARDWARE
2- Between Good and Fair
Condition
Inspected
INTERIOR GUARDS
2- Between Good and Fair
Condition
Deficiency
Deficiency Location/Instance
Deficiency Quantity
DETERIORATED/TORN-OUT/MISSING
South of Gymnasium
20
S.F.
REPLACE
PRIORITY 3
LEVEL 2
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
South of Gymnasium
Violations
No violations recorded
KITCHEN/WARMING PANTRY
Inspected
Instance on Basement
Ceiling
Instance on Basement
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
Deficiency Location/Instance
Deficiency Quantity
WASHABLE TILE:DAMAGED/MISSING
Near Compressor Room, South & North of Room
40
S.F.
REPLACE
PRIORITY 3
LEVEL 2
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
Mobile Validity Version 2.0 (P)
Page 21 of 31
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Architectural Inspection
M506
Question
Response
INTERIOR
KITCHEN/WARMING PANTRY
Ceiling
North of Room
Deficiency Photo 2
Near Compressor Room
Violations
No violations recorded
Door(s)
Instance on Basement
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Floor Finish
Instance on Basement
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
Deficiency Location/Instance
Deficiency Quantity
QUARRY TILE:BROKEN/MISSING TILES
Near the Servery & Center of M op Wash Room
20
S.F.
REPLACE
PRIORITY 3
LEVEL 2
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
Center of Mop Wash Room
Deficiency Photo 2
Near the Servery
Violations
No violations recorded
Walls
Instance on Basement
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
LIBRARY
Inspected
Instance on Room 100
Built-in Furnishing
Does not exist
Instance on Room 100
Ceiling
Mobile Validity Version 2.0 (P)
Page 22 of 31
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Architectural Inspection
M506
Question
Response
INTERIOR
LIBRARY
Ceiling
Instance on Room 100
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
Deficiency Location/Instance
Deficiency Quantity
TECTUM:DAMAGED/MISSING
Center of Room 100C (within Library)
30
S.F.
REPLACE
PRIORITY 3
LEVEL 2
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
Center of Room 100C (within Library)
Violations
No violations recorded
Door(s)
Instance on Room 100
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Floor Finish
Instance on Room 100
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Instance on Room 100
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Walls
LOCKER ROOM
Instance on Basement - Boys
Inspected
Alternative Use
No
Instance on Basement - Girls
Inspected
Alternative Use
No
Ceiling
Instance on Basement - Boys
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Instance on Basement - Girls
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Door(s)
Instance on Basement - Boys
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Instance on Basement - Girls
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Floor Finish
Inspected
Instance on Basement - Boys
Mobile Validity Version 2.0 (P)
Page 23 of 31
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Architectural Inspection
M506
Question
Response
INTERIOR
LOCKER ROOM
Floor Finish
Instance Condition
2- Between Good and Fair
Deficiency
Deficiency Location/Instance
Deficiency Quantity
CERAMIC TILE:BROKEN/MISSING TILES
Near Entrance to Room
35
S.F.
REPLACE
PRIORITY 3
LEVEL 2
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
Near Entrance to Room
Violations
No violations recorded
Instance on Basement - Girls
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
Deficiency Location/Instance
Deficiency Quantity
CERAMIC TILE:BROKEN/MISSING TILES
Near shower Room
30
S.F.
REPLACE
PRIORITY 3
LEVEL 2
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
Near shower Room
Violations
No violations recorded
Locker Room Lockers
Instance on Basement - Boys
Inspected
Instance Condition
3- Fair
Deficiency
Deficiency Location/Instance
DAMAGED UNITS
Units 1, 8, 9, 18, 257, 258, 259, 260, 261, 262, 391, 392, 393,
394, 395, 396, and other units
25
EACH
REPLACE
PRIORITY 3
LEVEL 2
Deficiency Quantity
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Mobile Validity Version 2.0 (P)
Page 24 of 31
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Architectural Inspection
M506
Question
Response
INTERIOR
LOCKER ROOM
Locker Room Lockers
Deficiency Photo 1
Unit 391
Deficiency Photo 2
Unit 280
Violations
No violations recorded
Instance on Basement - Girls
Inspected
Instance Condition
3- Fair
Deficiency
Deficiency Location/Instance
DAMAGED UNITS
Units 269, 270, 271, 272, 273, 274, 333, 338, 344, 403, 404,
405, 406, 407, 408, and other Units
25
EACH
REPLACE
PRIORITY 3
LEVEL 2
Deficiency Quantity
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
Unit 408
Violations
No violations recorded
Walls
Instance on Basement - Boys
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
Deficiency Location/Instance
Deficiency Quantity
CERAMIC TILE:BROKEN/ MISSING
Near Entrance to Room
10
S.F.
REPLACE
PRIORITY 3
LEVEL 2
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Mobile Validity Version 2.0 (P)
Page 25 of 31
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Architectural Inspection
M506
Question
Response
INTERIOR
LOCKER ROOM
Walls
Deficiency Photo 1
Near Entrance to Room
Violations
No violations recorded
Instance on Basement - Girls
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
Deficiency Location/Instance
Deficiency Quantity
CERAMIC TILE:BROKEN/ MISSING
Near Entrance to Room
10
S.F.
REPLACE
PRIORITY 3
LEVEL 2
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
Near Entrance to Room
Violations
No violations recorded
MULTI-PURPOSE ROOM
Does not exist
POOLS
Does not exist
SCIENCE DEMO ROOM
Instance on Rooms 214, 216, 218
Inspected
Alternative Use
No
Fixed Equipment
Instance on Rooms 214, 216, 218
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
SCIENCE LAB
Instance on Rooms 202, 210
Inspected
Alternative Use
No
Fixed Equipment
Instance on Rooms 202, 210
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
SCIENCE PREP ROOM
Instance on Room 206
Inspected
Alternative Use
No
Fixed Equipment
Instance on Room 206
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Mobile Validity Version 2.0 (P)
Page 26 of 31
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Architectural Inspection
M506
Question
Response
INTERIOR
SHOWER ROOM
Instance on Basement - Boys
Inspected
Alternative Use
No
Instance on Basement - Girls
Inspected
Alternative Use
No
Ceiling
Instance on Basement - Boys
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Instance on Basement - Girls
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Door(s)
Instance on Basement - Boys
Does not exist
Instance on Basement - Girls
Does not exist
Floor Finish
Instance on Basement - Boys
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Instance on Basement - Girls
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Instance on Basement - Boys
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Instance on Basement - Girls
Inspected
Instance Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Walls
Inspected
STAIRS/RAMPS: INTERIOR
Do Letter Stair Signs Exist?
Yes
Inspected
Ceiling
Condition
2- Between Good and Fair
Deficiency
Deficiency Location/Instance
Deficiency Quantity
PLASTER:CRACKS/SPALLING
Stair A/3
10
S.F.
REPLACE
PRIORITY 3
LEVEL 2
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
Stair A/3
Violations
No violations recorded
Inspected
Door(s)
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Does not exist
Partition
Mobile Validity Version 2.0 (P)
Page 27 of 31
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Architectural Inspection
M506
Question
Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Inspected
Railings
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Inspected
Stairs and Landings
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Inspected
Walls
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Inspected
STRUCTURAL
Inspected
COLUMNS/BEAMS/BEARING WALLS
Condition
3- Fair
Deficiency
Deficiency Location/Instance
Deficiency Quantity
STEEL COLUMNS/BEAMS:MINOR RUSTING
Main Entrance
50
S.F.
REPAIR AND REPAINT
PRIORITY 3
LEVEL 5
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
Main Entrance
Violations
No violations recorded
Inspected
FLOOR STRUCTURE
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Inspected
FOUNDATION WALLS
Material Type(s)
Concrete
Condition
4- Between Fair and Poor
Deficiency
CONCRETE:WATER INFILTRATION INTO NONINSTRUCTIONAL SPACE
Acid Tank Room
120
S.F.
INSTALL WATERPROOFING
PRIORITY 5
LEVEL 5
Deficiency Location/Instance
Deficiency Quantity
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
Acid Tank Room
Violations
Mobile Validity Version 2.0 (P)
No violations recorded
Page 28 of 31
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Architectural Inspection
M506
Question
Response
INTERIOR
STRUCTURAL
FOUNDATION WALLS
Deficiency
CONCRETE:WATER INFILTRATION INTO ELECTRICAL
PANEL ROOM
Electrical Panel Room
25
S.F.
INSTALL WATERPROOFING
PRIORITY 5
LEVEL 6
No violations recorded
Deficiency Location/Instance
Deficiency Quantity
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Violations
Inspected
ROOF STRUCTURE
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Does not exist
VAULTS-BUNKERS
Inspected
TOILET ROOMS - STAFF
Inspected
Ceiling
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Inspected
Door(s)
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Inspected
Floor Finish
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Inspected
Stalls
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Inspected
Walls
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Inspected
TOILET ROOMS - STUDENTS
Inspected
Ceiling
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Inspected
Door(s)
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Inspected
Floor Finish
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Inspected
Stalls
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Inspected
Walls
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Inspected
LIFE SAFETY
F.D. HOLDING AREA
Does not exist
STEEL STAIRS
Does not exist
Inspected
SITE
CONTAINERIZATION
Does not exist
Drainage System for Asphalt
Inspected
Mobile Validity Version 2.0 (P)
Page 29 of 31
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Architectural Inspection
M506
Question
Response
SITE
Drainage System for Asphalt
Does not exist
Catch Basins/Manhole - Surrounded by asphalt
Inspected
Drainage System for Concrete
Inspected
Catch Basins/Manhole - Surrounded by concrete
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Inspected
Drainage System for Soil
Does not exist
Catch Basins/Manhole - Surrounded by Soil
DRINKING FOUNTAINS
Does not exist
FENCES
Inspected
2- Between Good and Fair
Condition
Deficiency
Deficiency Location/Instance
Deficiency Quantity
CONCRETE CURB:DAMAGED/DETERIORATED
On South of Building (Easement)
10
S.F.
REPLACE
PRIORITY 3
LEVEL 2
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
On South of Building (Easement)
Violations
No violations recorded
IRRIGATION SYSTEM
Does not exist
PAVING
Inspected
Inspected
DOT Sidewalk
Asphalt
Does not exist
Concrete
Inspected
2- Between Good and Fair
Condition
Deficiency
Deficiency Location/Instance
Deficiency Quantity
DAMAGED/DETERIORATED/MISSING SECTIONS
On w 102 Street
50
S.F.
REPLACE
PRIORITY 3
LEVEL 2
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
On W102 Street
Violations
No violations recorded
Does not exist
Pavers
Inspected
Site Sidewalks & Walkways
Asphalt
Does not exist
Concrete
Inspected
Mobile Validity Version 2.0 (P)
Page 30 of 31
Print Date: 6/18/2015
NYC Department of Education
Building Condition Assessment Survey 2014-2015
Architectural Inspection
M506
Question
Response
SITE
PAVING
Site Sidewalks & Walkways
Concrete
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Does not exist
Pavers
Inspected
Student Non-Use
Gravel Exists?
Asphalt
No
Does not exist
Concrete
Inspected
2- Between Good and Fair
Condition
Deficiency
No deficiencies recorded
Does not exist
Pavers
Does not exist
Student Use
PLAYGROUNDS
Does not exist
PLAYING SURFACE
Does not exist
RETAINING WALLS
Does not exist
SEATING
Does not exist
SITE WALLS (NOT RETAINING WALLS)
Does not exist
STAIRS/RAMPS: EXTERIOR
Inspected
Inspected
Railings
Condition
2- Between Good and Fair
Deficiency
Deficiency Location/Instance
Deficiency Quantity
DAMAGED
Northwest corner of Building Site
10
L.F.
REPLACE
PRIORITY 3
LEVEL 2
Quantity Uom
Potential Action
Urgency of Action
Purpose of Action
Deficiency Photo 1
Northwest corner of Building Site
Violations
No violations recorded
Inspected
Site Cheek/flank Walls
Condition
2- Between Good and Fair
Deficiency
No deficiencies recorded
Inspected
Stairs/ramps
Condition
2- Between Good and Fair
Deficiency
Mobile Validity Version 2.0 (P)
No deficiencies recorded
Page 31 of 31
Print Date: 6/18/2015