HC AC GENERATORS Installation, Servicing, and Maintenance

Transcription

HC AC GENERATORS Installation, Servicing, and Maintenance
HC AC GENERATORS
Installation, Servicing, and Maintenance
English
Original Instructions
A040J849 (Issue 3)
Table of Contents
1.
FOREWORD...............................................................................................................................
1
2.
SAFETY PRECAUTIONS ...........................................................................................................
3
3.
SAFETY DIRECTIVES AND STANDARDS ...............................................................................
7
4.
INTRODUCTION ........................................................................................................................
9
5.
AUTOMATIC VOLTAGE REGULATORS (AVR) ......................................................................
13
6.
APPLICATION OF THE GENERATOR ....................................................................................
19
7.
INSTALLATION INTO THE GENERATING SET......................................................................
25
8.
SERVICE & MAINTENANCE....................................................................................................
33
9.
FAULT FINDING.......................................................................................................................
37
10. PARTS IDENTIFICATION ........................................................................................................
43
11. SPARES AND AFTER SALES SERVICE ................................................................................
53
12. END OF LIFE DISPOSAL.........................................................................................................
55
A040J849 (Issue 3)
i
Installation, Servicing, and Maintenance -
This page is intentionally blank.
ii
A040J849 (Issue 3)
1
Foreword
1.1
The Manual
This manual contains guidance and instructions for the installation, servicing and maintenance
of the generator.
Before operating the generator, read this manual and make sure that all personnel who work on
the equipment have access to the manual and all additional documentation supplied with it.
Misuse and failure to follow the instructions may invalidate the product warranty and lead to
potential accidents.
This manual is an essential part of the generator. Make sure that the manual is available to all
users throughout the life of the generator.
The manual is written for skilled electrical and mechanical technicians and engineers, who have
prior knowledge and experience of generating equipment of this type. If in doubt, please seek
expert advice or contact your local Cummins Generator Technologies subsidiary.
NOTICE
Information in this manual was correct when published. It may be superseded due to our policy
of continuous improvement. Please visit www.cumminsgeneratortechnologies.com for latest
documentation.
A040J849 (Issue 3)
1
Installation, Servicing, and Maintenance -
This page is intentionally blank.
2
A040J849 (Issue 3)
2
Safety Precautions
2.1
Safety Information and Notices used in this manual
Danger, Warning and Caution panels are used in this manual to describe the sources of
hazards, their consequences and how to avoid injury. Notice panels emphasise important or
critical instructions.
DANGER
Danger indicates a hazardous situation which, if not avoided, WILL result in death or serious
injury.
WARNING
Warning indicates a hazardous situation which, if not avoided, COULD result in death or serious
injury.
CAUTION
Caution indicates a hazardous situation which, if not avoided, COULD result in minor or
moderate injury.
NOTICE
Notice refers to a method or practice which can result in product damage, or to draw attention to
additional information or explanations.
2.2
Skill Requirements of Personnel
WARNING
Service and maintenance procedures should only be carried out by experienced and qualified
engineers, who are familiar with the procedures and the equipment.
2.3
Risk Assessment
WARNING
A risk assessment should be performed by the user/operating company to establish all
personnel related risks. All relevant personnel should be trained on identified risks.
Access to the Power Plant/Generator Set during operation should be restricted to
personnel that have been trained on these risks.
A040J849 (Issue 3)
3
Installation, Servicing, and Maintenance -
2.4
Personal Protective Equipment (PPE)
WARNING
All persons operating, servicing, maintaining or working in or with a power plant or a generating
set must wear appropriate Personal Protective Equipment (PPE).
Recommended PPE includes:
· Ear and Eye Protection
· Head and face protection
· Safety footwear
· Overalls that protect the lower arms and legs
Ensure that all persons are fully aware of the emergency procedures in case of accidents.
2.5
Noise
CAUTION
Generators emit noise. Ensure appropriate ear protection is worn at all times. Maximum Aweighted noise emissions may reach 109 dB(A). Contact supplier for application-specific details.
2.6
Electrical Equipment
CAUTION
All electrical equipment can be dangerous if not operated correctly. Always install, service and
maintain the generator in accordance with this manual.
Any Work that is likely to require access to electrical conductors must comply with all local and
national electrical safety procedures that are applicable to the site and to the voltage levels
involved as well as any site specific rules. Always use genuine ‘STAMFORD’ replacement parts.
2.7
Lock Out/Tag Out
WARNING
Isolate the generator from all sources of mechanical and electrical energy before servicing.
Adopt a suitable lock-out/tag out process.
2.8
Lifting
WARNING
The lifting points provided are designed for lifting the generator only. Do not lift the generating
set (generator coupled to motive power source) by the generator’s lifting points.
4
A040J849 (Issue 3)
Installation, Servicing, and Maintenance -
2.9
Generator Operating Areas
Operating in hatched areas or directly in-line with any air inlet/outlet should be avoided where
possible. Always wear suitable PPE when working in these areas.
WARNING
Do not place controls within the vicinity of the air inlet/outlet of the machine and ensure
personnel are restricted from these areas during operation. In the event of catastrophic failure,
machine parts may exit these areas
2.10
Hazard Warning Labels
Hazard warning labels are affixed to the generator.
If the original labels are missing, damaged or painted over, replace them with the spare set
supplied in a wallet attached to the generator. Follow the instructions on the back of the labels.
WARNING
Labels are fixed to the generator to alert users to the type and source of potential hazards. The
labels must be visible at all times. Always follow the label instructions to avoid risk of injury.
A040J849 (Issue 3)
5
Installation, Servicing, and Maintenance -
2.11
General Guidance
NOTICE
The above, constitutes generic guidance and should supplement your own safety procedures
and all applicable laws and standards.
6
A040J849 (Issue 3)
3
Safety Directives and Standards
STAMFORD AC generators meet applicable European safety directives, and national and
international standards relevant to generators. The generator must be operated within the limits
specified in the relevant standards and within the parameters on the generator rating plate.
Marine generators meet the requirements of all the major marine classification societies.
3.1
European Directives: EC Declaration of Conformity
Each generator is CE marked and supplied with an EC Declaration of Conformity for
incorporation into an electricity generating set. It is the responsibility of the generating set
manufacturer to ensure that the complete generating set complies with EC Directives and
standards.
Our authorized representative in the European Community is Mr Jeffrey Matthews, Engineering
Director, Cummins Generator Technologies Ltd.
All STAMFORD generators meet the following Standards and Directives:
Directives:
· 2004/108/EC EMC Directive
· 2006/95/EC Low Voltage Directive
· 2006/42/EC Machinery Directive
A040J849 (Issue 3)
7
Installation, Servicing, and Maintenance -
Standards:
· EN 61000-6-1 Electromagnetic Compatibility, Generic Standards - Immunity for residential,
commercial and light-industrial environments
· EN 61000-6-2 Electromagnetic Compatibility, Generic Standards - Immunity for industrial
environments
· EN 61000-6-4 Electromagnetic Compatibility, Generic Standards - Emission standard for
residential, commercial and light-industrial environments
· EN ISO 12100-1 Safety of Machinery, Basic concepts, general principles for design - Basic
terminology, methodology
· EN ISO 12100-2 Safety of Machinery, Basic concepts, general principles for design Technical principles
· EN ISO 14121-1 Safety of Machinery, Risk assessment - Principles
· EN 60034-1 Rotating electrical machines - Rating and performance
· BS ISO 8528-3 Reciprocating internal combustion engine driven alternating current
generating sets - alternating current generators for generating sets
· BS 5000-3 Rotating electrical machines - Generators to be driven by reciprocating internal
combustion engines - Requirements for resistance to vibration
NOTICE
Once the generator is built into a generating set, it is the responsibility of the generating set
manufacturer to ensure that the generating set complies with the relevant EC Directives.
3.2
Additional Information for EMC Compliance
STAMFORD generators are designed to meet EMC emissions and immunity standards for
industrial environments. Document reference N4/X/011 outlines additional equipment that may
be required when the generator is installed in residential, commercial and light industrial
environments.
The installation ‘earth/ground’ arrangements require the connection of the generator frame to
the site protective earth conductor using a minimum lead length.
Installation, maintenance and servicing must be carried out by adequately trained personnel
fully aware of the requirements of the relevant EC directives.
NOTICE
Cummins Generator Technologies is not liable for EMC compliance if unauthorised
parts, not of STAMFORD brand, are used for maintenance and servicing.
8
A040J849 (Issue 3)
4
Introduction
4.1
General Description - HC
HC generators are of brushless rotating field design, available up to 660V/50Hz (1500 rpm) or
60Hz (1800 rpm), and built to meet BS5000 Part 3 and international standards.
HC generators are self-excited, with excitation power derived from the main output windings,
using the AS440 AVR.
A permanent magnet generator (PMG) powered excitation system is available as an option
using either the MX341 or MX321 AVR.
4.2
Serial Number Location
The customer order number is stamped into the upper section of the drive end bracket. A
unique serial number is shown on two labels on the outside of the terminal box.
4.3
Rating Plate
The self-adhesive rating plate label, supplied with the generator, must be fixed after the
generator set is fully assembled and painted.
WARNING
The generator could overheat if operated outside the parameters specified on the rating plate.
Overheating can cause catastrophic failure and serious injury from ejected debris. Always
operate the generator within the rated parameters.
4.4
Product Authentication
The STAMFORD high security, anti-counterfeit hologram is located on the Tracking Label.
Check that the dots are visible around the STAMFORD logo when viewing the hologram from
different angles and the word "GENUINE" appears behind the logo. Use a flashlight to see
these security features in low ambient light. Check that the generator is genuine by entering the
unique 7 character hologram code at www.stamford-avk.com/verify.
A040J849 (Issue 3)
9
Installation, Servicing, and Maintenance -
FIGURE 1.
FIGURE 2.
GLOBAL STAMFORD AC GENERATOR NAMEPLATE, COMPRISING RATING PLATE
AND TRACKING LABEL
DOTS VISIBLE IN LEFT, RIGHT, UPPER AND LOWER VIEWS OF 3D HOLOGRAM
4.5
Self-Excited AVR Controlled Generators
4.5.1
Main Stator Powered AVR
The main stator provides power for excitation of the exciter stator via the AVR, which is the
controlling device governing the level of excitation provided to the exciter stator. The AVR
responds to a voltage-sensing signal derived from the main stator winding. By controlling the
low power of the exciter stator, control of the high power requirement of the main rotor is
achieved through the rectified output of the exciter rotor.
10
A040J849 (Issue 3)
Installation, Servicing, and Maintenance -
No.
Description
No.
Description
1
Main rotor
5
AVR
2
Rotating diodes
6
Main stator
3
Exciter rotor
7
Output
4
Exciter stator
8
Shaft
4.6
Separately-Excited AVR Controlled Generators
4.6.1
Permanent Magnet Generator (PMG) excited - AVR
controlled generators
WARNING
A Permanent Magnet Generator (PMG) has a strong magnetic field that could interfere
with an implanted medical device, such as a pacemaker. Do not go near the PMG if you
have an implanted medical device.
The Permanent Magnet Generator (PMG) provides power for the excitation of the exciter stator
via the Automatic Voltage Regulator (AVR) which is the controlling device governing the level of
excitation provided to the stator field. The AVR responds to a voltage-sensing signal derived, via
DM110 or MA330 (where fitted), from the main stator winding. By controlling the low power of
the exciter stator, control of the high power requirerment of the main rotor is achieved through
the rectified output of the exciter rotor.
A040J849 (Issue 3)
11
Installation, Servicing, and Maintenance -
No.
12
Description
No.
Description
No.
Description
1
Main rotor
5
PMG stator
9
Main stator
2
Rotating diodes (if fitted)
6
Exciter stator
10 Output
3
Exciter rotor
7
AVR
11 Shaft
4
PMG rotor
8
Isolating transformer (if
fitted)
A040J849 (Issue 3)
5
Automatic Voltage Regulators (AVR)
Cummins Generator Technologies offer a selection of Automatic Voltage Regulators designed
and built to achieve maximum performance from the range of STAMFORD brushless AC
generators. Self-excited and separately-excited types are available, from low-cost analogue to
sophisticated digital control. All STAMFORD AVR’s are encapsulated to provide protection
against moisture, salt and sand in the atmosphere, and are mounted on anti-vibration mounts
for added mechanical protection.
All STAMFORD AVRs have the following features:
· connections to a remote hand trimmer accessory for fine control of the generator output
voltage
· ‘Under-Frequency Roll-Off’ (UFRO) protection to reduce the generator output voltage if
speed falls below a threshold, and
· connections to power factor and droop accessories for sharing reactive load in parallel with
other generators or mains utility.
AVR specification, installation and adjustment information is available in the AVR manual
supplied with the generator, or at www.cumminsgeneratortechnologies.com
NOTICE
If the supplied AVR is to be replaced by a different make, check its compatibility with Cummins
Generator Technologies before use.
5.1
Self Excited Types
AVR’s for self excited generators receive their power direct from the generator output terminals,
and control generator output voltage through continual automatic adjustment of the exciter and
main rotor field strengths.
5.1.1
AS440
The AS440 achieves voltage regulation of ±1.0%. The design employs surface mount
technology, custom mouldings and heatsink in a compact assembly.
The AVR includes the following extra features:
· connections for excitation power from an auxilliary winding to support legacy generators
· connections to an analogue signal from a power factor controller accessory for example,
and
· 110V a.c. voltage sensing by selectable link accessory.
A040J849 (Issue 3)
13
Installation, Servicing, and Maintenance -
5.2
Permanent Magnet Generator (Pilot) Types
For the ultimate in control, an AVR designed to operate with the permanent magnet generator
(PMG) system is often specified. In this design, the AVR receives its power from a separate
source in the form of a small PMG, mounted on the main generator shaft. The advantage of this
arrangement is that the AVR power source is not affected by sudden loads applied to the
generator, hence the excitation remains at full capability, providing superior motor starting and
short circuit performance. By having a completely electrically isolated control system the
generator is better able to meet the more stringent EMC performance requirements.
5.2.1
MX341
The MX341 achieves voltage regulation of ±1.0% and protection against sustained overexcitation.
The AVR includes the following extra features:
· connections to an analogue signal from a power factor controller accessory, for example
· adjustable rate of voltage reduction with speed for (UFRO) protection
· soft-start control of generator output voltage rise when starting.
5.2.2
MX321
The MX321 achieves voltage regulation of ±0.5%.
The AVR includes the following extra features:
· connections to an analogue signal from a power factor controller accessory, for example
· adjustable rate of voltage reduction with speed for (UFRO) protection
· soft-start control of generator output voltage rise when starting
· three-phase RMS voltage sensing
· over-voltage protection by shutdown and isolation
· adjustable delayed response (dwell) of excitation voltage to speed changes, and
· adjustable short-circuit or starting current limit (with optional current sensing transformer
accessory).
5.3
AVR Accessories
Accessories to support AVR functions are factory-fitted or supplied separately with instructions
for fitting and wiring by a competent technician.
5.3.1
Hand Trimmer (for remote voltage adjustment)
A hand trimmer can be fitted in a convenient position (typically in the generator set control
panel) and connected to the AVR to provide fine adjustment of the generator voltage. The hand
trimmer value and the adjustment range obtained is as defined in the Technical Specification.
Refer to wiring diagrams to remove the shorting link and connect the hand trimmer.
14
A040J849 (Issue 3)
Installation, Servicing, and Maintenance -
5.3.2
Droop Transformer (for parallel operation – generator to
generator)
A droop transformer can be fitted in a defined position in the generator main output wiring and
connected to the AVR to enable parallel operation with other generators. The adjustment range
is as defined in the Technical Specification. Refer to wiring diagrams to remove the shorting link
and connect the droop transformer. The droop transformer MUST be connected in the correct
main output terminal for proper operation (details are as shown in the machine wiring diagram).
5.3.3
Power Factor Controller (for parallel operation – generator
to mains utility)
An electronic control module is available for use with the AVR to provide power factor control of
the generator output. The module uses generator voltage and output current as inputs and
interfaces with the AVR to ensure the necessary flexibility of the generator excitation and hence
control of the exported (or imported) kVAr. This allows full closed-loop control of the generator
power factor at the point of connection into the mains utility. Other features allow the generator
(or generators) to be automatically ‘voltage-matched’ prior to paralleling. This accessory is not
available with the AS480 AVR.
5.3.4
Low Voltage Link/Selector (AS480/AS440 AVR only)
Both the AS480 and the AS440 AVRs (self excited types) can be configured for low voltage
working. For operation between 100Vac and 120Vac the AS480 can be supplied with a special
wire link which connects between the generator main terminals and AVR input terminal ‘S1’. In
the case of the AS440 AVR, low voltage operation is enabled by fitting a shorting link across
terminals ‘La’ and ‘Lb’. In low-voltage operating mode and in both cases the overload
performance of the control system is reduced.
5.3.5
Current Limiting Transformers (MX321 AVR only)
Generator main output current can be electronically limited by connecting additional current
transformers to the MX321 AVR. In any situation where the output current attempts to rises
above a preset threshold (set on AVR) then the AVR will reduce the terminal voltage to restore
the set current level. For unbalanced loads, operation is based on the highest of the three phase
currents.
5.4
AVR Fault Finding
WARNING
Fault finding procedures present hazards, which can result in injury or death.
Only personnel qualified to perform electrical and mechanical service should carry out these
procedures. Ensure engine-starting circuits are disabled before commencing service or
maintenance procedures.
Isolate any anti-condensation heater supply.
A040J849 (Issue 3)
15
Installation, Servicing, and Maintenance -
NOTICE
Before commencing any fault finding procedures examine all wiring for broken or loose
connections.
Problem
Voltage does not build-up to
normal when starting the
generator set.
Action
1. Check link K1:K2 on AVR (not AS480) or auxiliary terminals:
- Replace if necessary and restart.
2. MX321 or MX341 only;
- Check the output from the PMG, Go to {Checking the PMG}.
Voltage builds-up but is at an
incorrect value.
1. Check AVR [VOLTS] control potentiometer setting:
- Correct if necessary.
- Check ‘Hand Trimmer’ if one is fitted - adjust if necessary.
2. Check generator speed:
- Correct if necessary and restart.
3. Check AVR ‘UFRO’ indicator:
- If it is illuminated, Go to {UFRO Setting Procedure}.
Voltage is very slow to build up.
1. Check generator accelerates as expected:
- Correct if necessary and restart.
2. MX321 only; Check setting of ramp potentiometer:
- Correct if necessary and restart.
Voltage rises and remains at a
high level.
1. Check AVR wiring:
Voltage rises to a high level and
then falls to a low level.
1. Check AVR wiring:
Voltage is normal and then falls
to a low level while the generator
set is running.
1. Check generator loading:
2. Check machine Rotating Rectifiers
Voltage is unstable either on noload or with load.
1. Check that the generator speed is stable:
- Correct if necessary and restart.
2. Check AVR wiring:
3. Adjust the AVR [Stability] control slowly clockwise until steady.
Voltage falls to a low level when
load is applied to the generator.
1. Check generator speed is not dropping as load is applied:
- Correct if necessary and restart.
2. Check AVR ‘UFRO’ indicator:
- If it illuminates as load is applied, Goto {UFRO Setting
Procedure}.
If all the tests and checks listed above fail to locate the generator fault then it must be assumed
that the AVR is faulty. There are no serviceable items on the AVR.
The AVR should be replaced only by a genuine STAMFORD part.
5.4.1
Checking The PMG (MA330, MX321 and MX341 AVRs only)
1. Start the generator set and run it at rated speed.
2. Measure the voltages at the AVR terminals P2, P3 and P4.These should be balanced and
within the following ranges:
16
A040J849 (Issue 3)
Installation, Servicing, and Maintenance -
50Hz generators: 170 ... 185VAC.
60Hz generators: 200 ... 220VAC.
3. Stop the generator.
4. Measure the PMG winding resistances (at the connections under the PMG cover). These
should be balanced and within the following range:
4 pole generators: 2.6 ohms +/-10%
6 pole generators: 5.6 ohms +/-10%
5. Use the results from tests 2) and 3) above together with the table below to identify the fault.
Phase/Phase Resistances:
PMG Voltages:
Correct
Low
5.4.2
Correct
Incorrect
Balanced
No fault with PMG
Recheck resistances
Unbalanced
Connector ?
Change PMG Stator
Balanced
Change PMG Rotor
Change PMG Stator
Unbalanced
Connector ?
Change PMG Stator
UFRO Setting Procedure
1. Stop the generator.
2. Check that the AVR UFRO selection link is set for the required 50Hz or 60Hz operation.
3. Start the generator set and run it at rated speed.
4. If the voltage is now correct and the UFRO indicator is not illuminated, return to the fault
finding procedure.
5. If the UFRO indicator is illuminated, continue as follows.
6. Adjust the [UFRO] control fully clockwise.
7. Set the generator speed at 95% of rated speed.
For 50Hz installations: 1425rpm or 47.5Hz
For 60Hz installations: 1710rpm or 57.0Hz
8. Adjust the [UFRO] control slowly counter-clockwise until the UFRO indicator just
illuminates.Return the control slightly clockwise until the indicator is just extinguished.
9. The UFRO setting is now correct - return to the fault finding procedure.
A040J849 (Issue 3)
17
Installation, Servicing, and Maintenance -
This page is intentionally blank.
18
A040J849 (Issue 3)
6
Application of the Generator
It is the customers' responsibility to ensure that the sizing selection of the generator is suitable
for the final application.
CAUTION
Overloading the generator may lead to catastrophic failure.
6.1
Environment
STAMFORD generators are protected to IP23. IP23 is not adequate protection for use outdoors
without additional measures.
Ambient Temperature
<40 °C
Humidity
<60%
Altitude
<1000m
This table represents the normal operating conditions that the generator is designed for.
Operation outside of these parameters is possible after due consideration and will be reflected
on the generator nameplate. If the operating environment for the generator has changed after
purchase, the rating of the generator needs to be revised, refer to the factory for details.
6.2
Air Flow
Ensure that the air inlets and outlets are not obstructed when the generator is running.
6.3
Airborne Contaminants
Contaminants such as salt, oil, exhaust fumes, chemicals, dust, sand, etc., will reduce the
effectiveness of the insulation and lead to premature failure of the windings. Consider using air
filters or an enclosure to protect the generator.
6.4
Air Filters
Filters present a restriction to the airflow so the rating of the generator must be reduced by 5%.
If the filters are supplied, factory fitted, the rating on the nameplate will include the reduced
rating. The filters can be retrofitted after delivery in which case the customer must apply the
power reduction.
Air filters remove airborne particulates above 5 microns. The frequency of changing and
cleaning the filters depend on the site conditions. We recommend that the filters are monitored
frequently until a suitable cycle of change is established.
A040J849 (Issue 3)
19
Installation, Servicing, and Maintenance -
Air filters do not remove water. Additional protection must be employed to prevent the filters
from getting wet. If the filters are allowed to get wet the airflow will be restricted and the
generator will overheat. This will reduce the life expectancy of the insulation leading to
premature failure of the generator.
6.5
Humid Conditions
The water carrying capacity of air depends on temperature. If the air temperature falls below its
saturation point, dew can condense on the insulation of windings reducing its electrical
resistance. In humid conditions additional protection may be required, even if the generator is
fitted inside an enclosure.
6.6
Anti-condensation heaters
Anti-condensation heaters are designed to raise the temperature of the windings above the
temperature of the surrounding material so that the condensation will not form on the windings.
We recommend that anti-condensation heaters are fitted to all generators that are left switched
off for any period of time. The best practice is to wire the heaters such that the heaters come on
when the generator is switched off. This is particularly important in applications where high
humidity is a significant problem.
6.7
Enclosures
An enclosure should be employed to protect the generator from adverse environmental
conditions.
If the generator is to be fitted inside an enclosure, ensure that there is adequate airflow to
support both the engine and the generator. Ensure that the generator air supply is clean (free
from moisture and contaminates) and at or below the ambient temperature stated on the rating
plate.
Also ensure that there are sufficient clearances around the generator for ease and safety of
maintenance.
6.8
Vibration
STAMFORD generators are designed to withstand the vibration levels encountered on
generating sets built to meet the requirements of ISO 8528-9 and BS 5000-3. (Where ISO 8528
is taken to be broad band measurements and BS5000 refers to the predominant frequency of
any vibrations on the generating set).
NOTICE
Exceeding either of the above specifications will have a detrimental effect on the life of the
bearings and other components. This will invalidate the generator warranty.
20
A040J849 (Issue 3)
Installation, Servicing, and Maintenance -
6.8.1
Definition of BS5000–3
Generators shall be capable of continuously withstanding linear vibration levels with amplitudes
of 0.25mm between 5Hz and 8Hz and velocities of 9.0mm/s rms between 8 Hz and 200 Hz,
when measured at any point directly on the carcass or main frame of the machine. These limits
refer only to the predominant frequency of vibration of any complex waveform.
6.8.2
Definition of ISO 8528-9
ISO 8528-9 refers to a broad band of frequencies; the broad band is taken to be between 10
Hertz and 1000 Hertz. The table below is an extract from ISO 8528-9 (Table C.1, value 1). This
simplified table lists the vibration limits by kVA and speed for acceptable operation of standard
generating set designs.
6.8.3
Linear Vibration Levels as Measured on the Generator HC
Linear Vibration Levels As Measured On The Generator - HC
Engine Speed
RPM
(min-1)
Power Output
S
(kVA)
Vibration
Displacement
r.m.s. (mm)
Vibration
Velocity
r.m.s. (mm/s)
Vibration
Acceleration
r.m.s. (mm/s2)
1300 ≤ RPM ≤ 2000
250 < S
0.32
20
13
720 ≤ RPM < 1300
250 < S ≤ 1250
0.32
20
13
The broad band is taken as 10 Hz - 1000 Hz
6.8.4
Linear Vibration Monitoring
We recommend using vibration analysing equipment to measure vibration at the positions
shown below. Check that vibration of the generating set is below the limits stated in the
standards. If vibration is above the limits, the generating set builder should investigate the root
causes and eliminate them. Best practice is for the generating set builder to take initial readings
as a reference and for the user to periodically monitor vibration, according to the recommended
service schedule, to detect a deteriorating trend.
A040J849 (Issue 3)
21
Installation, Servicing, and Maintenance -
6.8.5
Excessive Vibration levels
CAUTION
Excessive vibration can cause catastrophic failure of the generator, which could cause personal
injury.
If the vibration levels of the generating set are not within the parameters quoted above:
1. Consult the genset builder; the genset builder should address the genset design to reduce
the vibration levels as much as possible.
2. Contact Cummins Generator Technologies to understand the impact of not meeting the
above levels on both bearing and generator life expectancy.
22
A040J849 (Issue 3)
Installation, Servicing, and Maintenance -
6.9
Bearings
6.9.1
Re-greasable Bearings
When re-greasable bearings are fitted the bearing housings incorporate fittings for pipe work to
an external grease nipple. Generators with re-greasable bearings are supplied with information
labels advising the user of grease type, re-lubrication frequency and the quality of grease to be
used. These instructions must be followed. The grease used is a high specification synthetic
compound that must not be mixed with grease of a different specification.
6.9.2
Bearing Life
Factors that affect bearing life:
· The life of a bearing in service is subject to the working conditions and the environment:
· High levels of vibration from the engine or misalignment of the set will stress the bearing
and reduce its service life. Bearing life will be reduced if the vibration limits set out in BS
5000-3 and ISO 8528-9 are exceeded.
· Long stationary periods in an environment where the generator is subject to vibration can
cause false brinelling, which puts flats on the balls and grooves on the races, leading to
premature failure.
· Very humid or wet conditions can emulsify the grease causing deterioration of the grease
and corrosion, leading to premature failure of the bearings.
6.9.3
Health Monitoring of the Bearings
We recommend that the user checks the bearing condition, using vibration monitoring
equipment. Best practice is to take initial readings as a reference and periodically monitor the
bearings to detect a deteriorating trend. It will then be possible to plan a bearing change at an
appropriate generating set or engine service interval.
6.9.4
Bearing 'Service Life' Expectancy
Bearing manufacturers recognise that the "service life" of their bearings is dependent upon
many factors that are not in their control; they cannot therefore quote a "service life", however,
suggest practicable replacement intervals based on the L10 life of the bearing, the type of
grease and the recommendations of the bearing and grease manufacturers.
For general-purpose applications: providing the correct maintenance is carried out, vibration
levels do not exceed the levels stated in ISO 8528-9 and BS5000-3, and the ambient
temperature does not exceed 50°C. Plan to replace bearings within 30,000 hours of operation.
If in doubt about any aspect of the ‘bearing life’ on STAMFORD generators, contact your
nearest supplier of STAMFORD generators or contact the Stamford factory direct.
A040J849 (Issue 3)
23
Installation, Servicing, and Maintenance -
This page is intentionally blank.
24
A040J849 (Issue 3)
7
Installation into the Generating Set
7.1
Lifting the Generator
Lift the generator by shackle and pin attachment to the lifting points (lugs or eyes) provided. A
label attached to a lifting point shows the correct lifting arrangement. Use chains of sufficient
length, and a speader bar if necessary, to make sure that the chains are vertical when lifting.
Make sure that the capacity of the lifting equipment is sufficient for the generator mass shown
on the label.
FIGURE 3.
LIFTING LABEL
CAUTION
The generator lifting points are designed to lift the generator only. Do not lift the complete
generating set (generator coupled to motive power source) by the generator lifting points. Keep
the generator horizontal when lifting. Fit the transit bar to single bearing generators to keep the
main rotor in the frame.
7.2
Storage
If the generator is not to be used immediately, it must be stored in a clean, dry, vibration free
environment. We recommend the use of anti-condensation heaters.
7.2.1
After Storage
After a period of storage, carry out ‘pre running checks’ to determine the condition of the
windings. If the winding are damp or the insulation is low, follow one of the ‘drying out
procedures’, in the Service and Maintenance section of this manual.
If the generator has re-greasable bearings and has been in storage for 6 months or more, relubricate the bearings before use. If the bearings are sealed for life replace the bearings after 12
months in storage.
A040J849 (Issue 3)
25
Installation, Servicing, and Maintenance -
7.3
Generator Vibration, Frequency
The main vibration frequencies produced by the generator are as follows:
· 6-pole 1000 RPM 16⅔ Hz
· 6-pole 1200 RPM 20 Hz
· 4-pole 1500 RPM 25 Hz
· 4-pole 1800 RPM 30 Hz
However, vibrations induced by the engine are complex. It is the responsibility of the generating
set designer to ensure that the alignment and stiffness of the bedplate and mountings do not
exceed BS5000 part 3 and ISO 8528 part 9.
7.4
Generating Set Coupling
NOTICE
Do not attempt to rotate the generator rotor by levering against the vanes of the cooling fan. The
fan is not designed to withstand such forces and will be damaged.
Efficient operation and long component life depend on minimising mechanical stresses on the
generator. When coupled in a generating set, misalignment and vibration interactions with the
prime mover engine can cause mechanical stress.
Generating sets need a substantial flat continuous bedplate to suit the installation site floor
loading, with engine and generator mounting pads to make a firm base for accurate alignment.
The height of all mounting pads must be within 0.25 mm for skid mounting, 3 mm for nonadjustable anti-vibration mounts (AVM) or 10 mm for adjustable height AVMs. Use shims to
achieve level. The rotational axes of generator rotor and engine output shaft must be coaxial
(radial alignment) and perpendicular to the same plane (angular alignment). The axial alignment
of the generator and engine coupling must be within 0.5 mm, taking into account thermal
expansion, to minimise unwanted axial force on the bearings at operating temperature.
Vibration can occur by flexing of the coupling. The generator is designed for a maximum
bending moment not exceeding 140 kgm (1000 lbs ft) for frame sizes 4 and 5, and not
exceeding 275 kgm (2000 lbs ft) for frame size 6. Check the maximum bending moment of the
engine flange with the engine manufacturer.
Close-coupling of generator and engine can increase the rigidity of the generating set. Both
single and two bearing generators can be close-coupled.
26
A040J849 (Issue 3)
Installation, Servicing, and Maintenance -
To prevent rust during transit and storage, the generator frame spigot, rotor coupling plates and
shaft extension have been treated with a rust preventative coating. Remove this before coupling
the generating set.
FIGURE 4.
FIGURE 5.
7.4.1
SINGLE BEARING GENERATOR ROTOR SHOWING COUPLING DISCS BOLTED TO
DRIVE END COUPLING HUB (AT RIGHT)
TWO BEARING GENERATOR ROTOR SHOWING SHAFT WITH KEYWAY FOR FLEXIBLE
COUPLING (AT RIGHT)
Single Bearing
1. Check that the bracket which supports the rotor underneath the fan hub is fitted in position.
2. Position the generator close to the engine and remove the transit bar that keeps the rotor in
place during transport.
3. Remove air outlet covers from the drive end of the generator to access the coupling and
adaptor bolts.
4. Check that coupling discs are concentric with adaptor spigot. Adjust by suspending the
rotor into position. Use alignment studs to ensure that the disc and the flywheel are in
alignment.
5. Offer the generator to engine and engage both coupling discs and housing spigots at the
same time, pushing generator towards engine until coupling discs are against flywheel face
and the housing spigots are located.
CAUTION
Do not pull the generator to the engine using bolts through the flexible discs.
6. On the engine ensure the distance from flywheel coupling mating face to the flywheel
housing mating face is within 0.5mm of nominal dimension. This ensures there is no thrust
applied to the engine or generator bearings. Ensure securing bolts are tightened to relevant
torques.
A040J849 (Issue 3)
27
Installation, Servicing, and Maintenance -
CAUTION
Failure to secure bolts can lead to excessive vibration, which in turn can lead to
catastrophic generator failure.
7. Use heavy gauge washers to fit housing and coupling bolts. Tighten bolts evenly around
assembly sufficiently to ensure correct alignment.
Torque the bolts in the above sequence according to the correct bolt patten.
Then check the torque in each bolt in a clockwise direction around the bolt circle to ensure
all the bolts are properly torqued.
8. Tighten coupling disc to flywheel bolts. Refer to engine manufacturer’s manual for correct
tightening torque.
9. Remove the rotor support bracket.
10. Remove rotor aligning aids and replace all covers.
7.4.2
Two Bearing
A flexible coupling, designed to suit the specific engine/generator combination, is recommended
to minimise torsional vibration effects.
If a close coupling adaptor is used the alignment of machined faces must be checked by
offering the generator up to the engine. Shim the generator feet if necessary.
7.5
Pre-Running Checks
Before starting the generating set, test the insulation resistance of windings, check all
connections are tight and in the correct location. Ensure the generator air path is clear of
obstructions. Replace all covers.
7.6
Insulation Resistance Test
A resistance test by qualified personnel should be carried out based on the relevant operating
voltage:
28
A040J849 (Issue 3)
Installation, Servicing, and Maintenance -
NOTICE
The AVR should be disconnected during this test
Voltage
Test Voltage
LV – up to 1kv
Minimum Required Insulation Resistance
In Service
New
500V Megger
5 MΩ
10
MV – 1 - 4.6kv
2500V motorized
Megger
50 MΩ
100
HV – 4.6 - 20v
5000V motorized
Megger
150 MΩ
300
Should the insulation resistance be less than the quoted limits, drying out the generator
windings is essential. See the Service & Maintenance section of this Manual.
7.6.1
H.V. Testing
NOTICE
The windings have been H.V. tested during manufacture and further H.V. testing may degrade the
insulation with consequent reduction in operating life. Should it be necessary to demonstrate
H.V. testing, for customer acceptance, the tests must be carried out at reduced voltage levels i.e.
Test Voltage= 0.8 (2 X Rated Voltage + 1000)
This applies only to new machines, After being in service, testing levels should be further
reduced to 1.5 x Rated Voltage for maintenance testing. This HV test should only be completed
after megger tests and evaluation.
7.7
Direction of Rotation
The direction of rotation of the generator is designed to be clockwise as viewed from the drive
end of the generator. If it needs to run in reverse direction, please seek advice from Cummins
Generator Technologies.
A040J849 (Issue 3)
29
Installation, Servicing, and Maintenance -
7.8
Phase Rotation
The output from the generator will have a phase sequence of U V W with the generator running
clockwise as viewed from the drive end. If the phase rotation of the generator has to be
reversed, the customer must rearrange the output cables to a UVW configuration. Ask for a
circuit diagram of ‘reverse phase connections’.
7.9
Voltage and Frequency
Check that the voltage and frequency levels required for the generating set application are as
indicated on the generator nameplate.
7.10
AVR adjustment
To make AVR selections and adjustments remove the AVR cover. The AVR is factory set and
will give satisfactory performance during initial running tests. Subsequent voltage adjustment
both on and off load may be required. Guidance can be found in the section for the relevant
AVR.
7.11
Installation on Site
NOTICE
It is the responsibility of the end user and his contractors/subcontractors to ensure that the
overall electrical installation and system protection meets the needs of any inspectorate, local
electricity authority or safety rules, pertaining to the site location.
Cables should be supported appropriately to avoid a tight radius at the point of entry into the
terminal box panel and allow movement for the generator set on its anti vibration mountings
without causing excessive stress to the cables and generator load terminals.
To enable the system designer to achieve the necessary protection and/or discrimination, fault
current curves are available on request from the factory, together with generator reactance
values to enable fault current calculations to be made.
WARNING
Incorrect installation and/or protective systems can result in personal injury and/or equipment
damage. Installers must be qualified to perform electrical installation work.
7.12
Grid Connection: Voltage Surges and MicroInterruptions
Precautions should be taken to prevent transient voltages generated by the connected load
and/or the distribution system from causing damage to the generator components.
To identify any possible risk, all aspects of the generator’s proposed application should be
considered, especially the following:
· Loads with characteristics that result in large load step changes.
30
A040J849 (Issue 3)
Installation, Servicing, and Maintenance -
· Load control by Switchgear, and power control by any method likely to generate transient
voltage spikes.
· Distribution systems susceptible to external influences, such as overhead lines and
lightning strikes.
· Applications involving parallel operation to a mains supply, where the risk of a mains
disturbance in the form of a micro-interruption could occur.
If the generator is at risk of voltage surges or micro-interruptions adequate protection must be
incorporated into the generation system. This is normally in the form of surge arrestors and
suppressors.
7.13
Synchronisation
7.13.1 Parallel or Synchronizing AC Generators
· The synchronising switch/breaker should be of a type that will not cause “contact bounce”
when it operates.
· The synchronising switch/breaker should be adequately rated to withstand the continuous
full load current of the generator.
· The switch/breaker should be able to withstanding the rigorous closing cycles during
synchronising and the currents produced if the generator is parallelled out of synchronism.
· The closing time of the synchronising switch/breaker should be under the control of the
synchroniser settings.
· The switch/breaker should be capable of operation under fault conditions such as short
circuits. Generator data sheets are available.
NOTICE
The fault level may include a contribution from other generators as well as from the grid/mains
utility.
The method of synchronising should be either automatic, or by check synchronising. The use of
manual synchronising is not recommended. The settings on the synchronising equipment should
be such that the generator will close smoothly.
A040J849 (Issue 3)
31
Installation, Servicing, and Maintenance -
The Phase sequence must match
Voltage difference
+/- 0.5%
Frequency difference
0.1 Hz/sec
Phase angle
+/- 10o
C/B closing time
50 ms
The settings for the synchronising equipment to achieve this must be within these parameters.
The voltage difference when paralleling with the grid/mains utility is +/- 3% .
CAUTION
Synchronising outside these parameters may result in catastrophic failure of the generator.
32
A040J849 (Issue 3)
8
Service & Maintenance
8.1
Lock Out/Tag Out
WARNING
Before any dissembling or assembling procedures are carried out ensure that the generating set
is inhibited mechanically and isolated electrically.
WARNING
Service and fault finding procedures present hazards, which can result in severe personal injury
or death. Only personnel qualified to perform electrical and mechanical service should carry out
these procedures.
WARNING
The electrical supply to anti-condensation heaters must be isolated before attempting any work
adjacent to the heater.
It is suggested that a suitable lock-out/tag out process is adopted.
If anti condensations heaters are defect repair by replacement. Access is available via the air
inlets at the non-drive end.
8.2
Methods of Drying Out Generators
8.2.1
Cold Run
In many cases, the generator can be dried suitably using its own ventilation system. However, it
should not be electrically live whilst this is being carried out. De-excite the machine as indicated
in its circuit diagram. Operate the anti-condensation heater, where fitted, when drying out with
the machine’s own ventilation system. Run the machine in this condition until the minimum IR is
achieved.
8.2.2
Blown Air Drying
During drying, air must be able to flow freely through the generator in order to carry off the
moisture.
Direct hot air from two electrical fan heaters of around 1 – 3kW into the generator air inlet
apertures. Ensure the heat source is at least 300mm away from the windings to avoid over
heating and damage to the insulation.
Apply the heat and plot the insulation value at half hourly intervals. The process is complete
when the parameters covered in the section entitled, ‘Typical Drying Out Curve’, are met.
Remove the heaters, and re-commission as appropriate.
If the set is not to be run immediately ensure that the anti-condensation heaters are energised,
and retest prior to running.
A040J849 (Issue 3)
33
Installation, Servicing, and Maintenance -
8.3
Typical Drying Out Curve
Whichever method is used to dry out the generator the resistance should be measured every
half-hour and a curve plotted as shown
1. Y axis = Resistance
2. X axis = Time
3. Refer to One Megahom limit
The illustration shows a typical curve for a machine that has absorbed a considerable amount of
moisture. The curve indicates a temporary increase in resistance, a fall and then a gradual rise
to a steady state. Point ‘A’, the steady state, must be greater than 1.0 megahom. (If the
windings are only slightly damp the dotted portion of the curve may not appear). For general
guidance, expect that the typical time to reach point ‘A’ will be around 3 hours.
Drying should be continued after point “A” has been reached for at least one hour.
Values of insulation resistance significantly reduce as winding temperature increases,
Therefore, the reference values can only be established with windings at a temperature of
approximately 20°C.
If the IR value remains below the required values, even after the above drying methods have
been carried out correctly, then a Polarisation Index test [PI] should be carried out.
NOTICE
The generator must not be put into service until the minimum values are achieved.
8.4
Air Filters
Air filters for the removal of airborne particulate matter (dust) are offered as an addition to the
standard build option. The filter elements do not remove water and therefore must not be
allowed to get wet.
The frequency of filter maintenance will depend upon the severity of the site conditions. Regular
inspection of the elements will be required to establish when cleaning is necessary.
NOTICE
Do not charge filters with oil.
34
A040J849 (Issue 3)
Installation, Servicing, and Maintenance -
CAUTION
Only remove filter elements with the generator out of service, to avoid damage to the generator
8.4.1
Air Filter Cleaning Procedure
1. Remove the filter elements from the filter frames, taking care not to damage them.
2. Invert the filters dirty side down and agitate to remove particles of dirt. To remove stubborn
particles, low-pressure air can be used in the reverse direction of flow.If necessary use a
soft brush to gently brush off any remaining dirt particles.
3. Clean the sealing gaskets and surrounding area.
4. Visually check the condition of the filter elements and sealing gaskets, replace as
necessary.
5. Ensure that the filter elements are dry before putting them back into service.
6. Carefully replace the filter elements.
8.5
Generator Cleaning
Ensure generator is isolated prior to any cleaning operation. Avoid exposure of generator
windings to cleaning agents.
A040J849 (Issue 3)
35
Installation, Servicing, and Maintenance -
This page is intentionally blank.
36
A040J849 (Issue 3)
9
Fault Finding
WARNING
Fault finding procedures present hazards, which can result in injury or death. Only personnel
qualified to perform electrical and mechanical service should carry out these procedures.
Ensure engine-starting circuits are disabled before commencing service or maintenance
procedures and refer to detailed AVR instructions. Always use insulated screwdrivers when
adjusting AVR. Isolate any anti-condensation heater supply
NOTICE
Before commencing any fault finding procedures examine all wiring for broken or loose
connections.
A040J849 (Issue 3)
37
Installation, Servicing, and Maintenance -
FIGURE 6.
38
ELECTRICAL FAULT FINDING CHART PRT 1
A040J849 (Issue 3)
Installation, Servicing, and Maintenance -
FIGURE 7.
A040J849 (Issue 3)
ELECTRICAL FAULT FINDING CHART PRT 2
39
Installation, Servicing, and Maintenance -
FIGURE 8.
40
MECHANICAL FAULT FINDING CHART
A040J849 (Issue 3)
Installation, Servicing, and Maintenance -
9.1
Fault Finding Procedure for Rotating Diodes and
Surge Suppressor:
9.1.1
Check Rectifier Diodes
· Reverse the multimeter leads so that the Positive lead is on the Anode side of the diode,
the Multimeter should now read OL. (no electron flow).
· A faulty diode will give a short circuit reading in both directions, or an open circuit reading
in both directions, (usually because the solder joing has failed).
9.1.2
Testing the Surge Suppressor (Varistor)
· Disconnect one of the main rotor leads (+ or -)
· Switch the Multimeter to the position indicated for resistance "Ω" testing
· The Varistor should read Inifinity in both directions, and has no polarity
· A faulty Varistor will be short circuit, or burnt (destroyed) by fault current
A040J849 (Issue 3)
41
Installation, Servicing, and Maintenance -
This page is intentionally blank.
42
A040J849 (Issue 3)
10
Parts Identification
A040J849 (Issue 3)
43
Installation, Servicing, and Maintenance -
10.1
44
HC4 and HC5 Single Bearing Generator
A040J849 (Issue 3)
Installation, Servicing, and Maintenance -
A040J849 (Issue 3)
45
Installation, Servicing, and Maintenance -
10.2
46
HC4 and HC5 Two Bearing Generator
A040J849 (Issue 3)
Installation, Servicing, and Maintenance -
A040J849 (Issue 3)
47
Installation, Servicing, and Maintenance -
10.3
48
HC6 Single Bearing Generator
A040J849 (Issue 3)
Installation, Servicing, and Maintenance -
A040J849 (Issue 3)
49
Installation, Servicing, and Maintenance -
10.4
50
HC6 Two Bearing Generator
A040J849 (Issue 3)
Installation, Servicing, and Maintenance -
A040J849 (Issue 3)
51
Installation, Servicing, and Maintenance -
This page is intentionally blank.
52
A040J849 (Issue 3)
11
Spares and After Sales Service
We recommend the use of genuine STAMFORD service parts supplied from an authorised
service outlet. For details of your nearest service outlet visit www.stamford-avk.com.
Aftermarket Help Desk
Phone: +44 (0) 1780 484744
Email: [email protected]
11.1
Recommended Service Parts
In critical applications a set of these service spares should be held with the generator.
Part
11.2
Number
Diode Set
RSK6001
(3 forward & 3 reverse diodes with Surge
Suppressors)
MX321 AVR
E000-23212/1P
MX341 AVR
E000-23412/1P
Kluber Grease
45-0281
Kluber Asonic GHY72 Grease
All bearings trials and calculated life expectancy are based on the use of Kluber Asonic GHY72.
We recommend the use of this Ester Oil/Polyurea grease or an alternative grease with the same
specification. The grease specification is available by request. Kluber has a worldwide
distribution network, contact the manufacturers for your nearest stockist.
11.3
Parts Orders
When ordering parts the machine serial number or machine identity number and type should be
quoted, together with the part description. The machine serial number can be found on the
name plate or frame.
11.4
Customer Service
Cummins Generator Technologies' service engineers are experienced professionals, trained
extensively to deliver the best support possible. Our global service offers:
· 24/7 response to service emergencies, 365 days of the year.
· On-site ac generator commissioning
· On-site bearing maintenance & bearing condition monitoring
· On-site insulation integrity checks
· On-site AVR & accessories set-up
A040J849 (Issue 3)
53
Installation, Servicing, and Maintenance -
· Multi-lingual local engineers
Customer Service Help Desk:
Phone: +44 1780 484732 (24 hours)
Email: [email protected]
54
A040J849 (Issue 3)
12
End of Life Disposal
Companies specialising in reclaiming material from scrap products can reclaim most of the iron,
steel and copper from the generator. For more details, please contact STAMFORD Customer
Service.
12.1
Recyclable material
Mechanically separate the base materials, iron, copper and steel, removing paint, polyester
resin, and insulation tape and/or plastics residues from all components. Dispose of this ‘waste
material’
The iron, steel and copper can now be recycled.
12.2
Items requiring specialist treatment
Remove electrical cable, electronic accessories and plastic materials from the generator. These
components need special treatment to remove the waste from the reclaimable material.
Forward the reclaimed materials for recycling.
12.3
Waste material
Dispose of waste material from both of the above processes via a specialist disposal company.
A040J849 (Issue 3)
55
Installation, Servicing, and Maintenance -
This page is intentionally blank.
56
A040J849 (Issue 3)
Barnack Road
Stamford
Lincolnshire, PE9 2NB
United Kingdom
Tel: +44 (0) 1780 484000
Fax: +44 (0) 1780 484100
www.cumminsgeneratortechnologies.com
Copyright 2012, Cummins Generator Technologies Ltd. All Rights Reserved.
STAMFORD is a registered trade mark of Cummins Generator Technologies Ltd.
Cummins and the Cummins logo are registered trade marks of Cummins Inc.