Transconnect Sales Book2_13

Transcription

Transconnect Sales Book2_13
PSP Products, Inc.
Transconnect Overview
PSP Products, Inc. has developed a unique generator transfer switch like no other on the
market. Our patented technology greatly reduces install time, goes outside at the meter, and
can be customized to fit your needs.
Some of our features include:
I.
II
Retro fit version fits behind the meter for existing homes and small commercial, up
to 48kW loads.
Comes in three configurations:
•
semi automatic – manual start/stop
•
fully automatic start/stop
IV. Monitors generator power and stops power flow from generator if power falls below
105 Volts or exceeds 135 Volts on either leg, and will not transfer an unbalanced
load.
V. All models automatically transfer back to line power.
VI. Powers customer’s entire service distribution panel.
VII. Models available with plug for portable generator hook up.
VIII.Records power outages and errors.
IX. Test switch to exercise the system, reset button, and diagnostic lights.
X. Redundant controls and safety features to insure reliable and proper operation.
XI. Generator maintenance cycle on auto start versions.
XII. Whole house surge protection available on new meter base and modular versions.
XIII.
Internal electrical interlocks allow only one power source (utility company or generator)
to supply power to main service panel.
XIV.A built-in .2-3 minute time delay allows voltage monitoring of either power source
before the transfer occurs.
XV. Built-in surge protection is available on certain units.
Transconnect Product Line
200Amp [12”W x 14”H]
retro-fit version
(meter collar)
•
•
•
•
•
•
•
•
•
Quick and easy install
For existing homes
Typically installed by utility
Mounts behind the meter
Disconnects utility from house
Max generator size is 24kw
Max electrical service is 200A
Manual & Automatic versions available
30 & 50 Amp plugs available for easy, portable generator
hook up
• Available in optional saltwater resistant poly-carbonate case •
Whole home surge protection available
Transconnect Product Line
400 Amp [30”W x 36”H]
meter-base version 320Amp meter
• Perfect for new construction applications
– Installed in place of standard utility meter base
• Available with service disconnect breakers
• Max electrical service is 400A (feeding (2) 200A Panels) •
Max generator size is 36kw
• Standard & bypass meter blocks available
• Can be part pf a service upgrade/replacement or home
remodeling project
• Typically installed by contractor
• Whole home surge protection available
Transconnect Product Line
[18”W x 16”H]
200 Amp [12”W x 14”H]
200 Amp [14”W x 30”H]
non-meter version
• Can be installed by utility or contractor
• Can be used anywhere meter access is not available
• Installs between meter and circuit panel of 200A service •
Can be used to supply backup power to one circuit panel
of 320A service
• 400A version for (2) 200A panels
• Available in 2 versions depending on space available
– vertical & 2-piece
• All include (1) or (2) 200A service disconnect breaker(s) to
meet any local code requirement
• Max generator size is 36kw
• Max electrical service is 400A
• Whole Home Surge Protection can be added
Circuit Interrupter
The PSP Transconnect Interrupter is a relay board designed to disconnect loads from the main electric panel
that would otherwise overload a connected generator. The Interrupter should be used in any fully
automatic application where the connected generator does not have the capacity to carry the entire,
connected load. Loads such as electric hot water heaters, heat pumps, air conditioning systems, water
pumps or any devices that are not important to a homeowner to have in operation during a power outage,
can be safely taken off line. This allows the TransConnect to automatically operate a generator that is not
large enough to carry the entire home on its own.
Installation is simple. The Interrupter is mounted next to the existing electric panel and wires are rerouted to
the relay box from their current location in the electric panel. Short jumper wires are then installed
between each relay and the breaker in the main electric panel that services that circuit.
Some models have room to add additional relays in the field for future upgrades. All units are ARL listed
and approved to meet all safety standards.
Relays:
DPDT
24V DC coil voltage
Contacts are rated to 30 or 50 Amp, 240V continuous ratings
Note: TransConnect or other control device must have Form C contacts with a 2 Amp at 30 Volts maximum rating to operate relays.
Model Number
Number of Circuits
Pi-034B020
4 – 30 Amp
Pi-038K030
8 – 30 Amp
Pi-038K040
10 – 30 Amp
Pi-031T0P0
1 – 25 Amp
PiS060-D24
1 – 60 Amp
Description
2 double pole 30 amp relays
– no terminal block
4 double pole 30 amp relays
– with terminal block
5 double pole 30 amp relays
– with terminal block
Single pole unit
with chase nipple and pigtails
60 Amp relay add on – upgrades Pi-038K030
to a 10 circuit panel with 8 – 30 Amp and
2 – 50 Amp circuit that can be interrupted.
Size
8” W x 10” H
11” W x 14” H
16” W x 18” H
Note: AC or Heat Pump interrupt only: This can be done by routing the Thermostat wire through the “Interrupt” connections on the
TransConnect control board. When the generator is engaged, the circuit is broken and the thermostat will be rendered inoperative so the
AC or Heat Pump cannot turn on. This method avoids having to purchase an additional relay panel such as those listed above.
Install time depends on the distance between the TransConnect and the thermostat in the home.
Transconnect Operations
The Transconnect Generator Transfer Switch has built in safety features that prevent generator
back feed into the utility power system. The attached diagrams are intended to explain the
operational flow of electricity in Normal and Emergency conditions.
Normal Operation
When utility power is present, the normal flow of electricity is through the meter as usual. As the
power leaves the meter, it is diverted through a Latching Relay. The Latching Relay is in a closed
position to allow power to flow through from the utility to the panel inside the home. An optional
Service Disconnect Breaker is available if required by local codes. Voltage Sensor # 1on the
Control Board continually monitors the power on the utility side of the meter. The Control Board
will report problems with the Utility voltage but it will not disconnect utility power under this
type of condition. If a total blackout occurs, the Voltage Sensor # 1will respond by beginning
the auto start sequence of an attached stationary generator or it will wait and watch for a
portable generator to be hooked up.
Emergency Operation
Once a blackout condition is confirmed, the Control Board starts the generator or begins to
“watch” for a generator to be connected. Voltage Sensor # 3 is the main control component to
determine when generator power is present and has stabilized. The transfer switch will not
switch to generator power if it does not see 105V to 135V on each leg measured to neutral. The
Control Circuit for the Latching Relay energizes the latch, which locks the relay into an “off” or
open position. Sensor # 4 verifies the position of the Latching Relay. The Control Circuit(s) for
the Generator Relays are then energized to close these normally open relays. Voltage Sensor #
2 confirms power flow through the relays. Power is now supplied to the house without feed back
of power into the utility system. Zero voltage is verified at Voltage Sensor # 1.
When power is restored by the utility, Voltage Sensor # 1 waits a predetermined period of time
to confirm that the power is truly restored and constant. If for any reason the utility power is not
stable (such as 120V on one leg and 95V on the other); the TransConnect unit will not switch back
to utility power. The Generator Relays are disengaged when any utility voltage is restored by
Voltage Sensor # 1 releasing the Independent Control Relays. No Voltage can be present as
confirmed by Voltage Sensor # 2 before the Latching Relay is returned to a closed position.
Closing the Latching Relay reconnects utility power to the house. This is verified by Sensor # 4.
Stationary generators are automatically shut down. Portable generators are left running at an idle
and require manual shutdown.
Switch off breakers in the panel box to shed load to reduce usage below the generator’s rating.
Move the Portable Generator into position near the service entrance. (Not applicable if using a
stationary generator) Plug the generator into the TransConnect Transfer Switch. (Not applicable if
using a stationary generator) Start the Generator. (The TransConnect automatically switches to
generator and then switches back when utility is restored) Shutdown the Generator after
utility power is restored. Return the generator and the panel to normal.
Product Information Matrix
Meter Collar Units - Mounts behind any 200 Amp standard meter
Model
Number
TC-050M210
TC-050M213
TC-050M215
TC-050A210
TC-100M23W
TC-100A23E
TC-200M23W
TC-200A23W
Generator
Capacity
50 Amp / 12kW
50 Amp / 12kW
50 Amp / 12kW
50 Amp / 12kW
100 Amp / 12kW
100Amp / 12kW
200 Amp / 48kW
200 Amp / 48kW
Manual/
Automatic
Manual
Manual
Manual
Automatic
Manual
Automatic
Manual
Automatic
Wiring Between Collar
and Electronics Box
Flexible conduit
Flexible conduit
Rigid conduit
Flexible conduit
Rigid conduit
Rigid conduit
Rigid conduit
Rigid conduit
External Mount Style
Meter Base
L1430 Plug
•
•
•
Physical
Dimensions
12” x 14.5”
12” x 14.5”
12” x 14.5”
12” x 14.5”
12” x 14.5”
12” x 14.5”
12” x 14.5”
12” x 14.5”
• All units available with polycarbonate enclosure for wall unit housing
• All units available with 50Amp 4 wire plug
• Cords available for connections between generator & transfer switch
• All units available with Whole Home Surge Protection Kits
Non-Meter Version - Install between Meter Base and Service Panel
Model
Number
TC-05SM2P0
TC-10SM2P0
TC-20SM2P0
TC-05SA2P0
TC-10SA2P0
TC-20SA2P0
TC-05BM2V3
TC-10BM2V0
TC-20BM2V0
TC-05BA2V0
TC-10BA2V0
TC-20BA2V0
Generator
Capacity
50 Amp / 12kW
100 Amp / 24kW
200 Amp / 48kW
50 Amp / 12kW
100 Amp / 24kW
200 Amp / 48kW
50 Amp / 12kW
100 Amp / 24kW
200 Amp / 48kW
50 Amp / 12kW
100 Amp / 24kW
200 Amp / 48kW
Manual/
Automatic
Manual
Manual
Manual
Automatic
Automatic
Automatic
Manual
Manual
Manual
Automatic
Automatic
Automatic
• All units available in split enclosure version
• All units available with Whole Home Surge Protection
Service
Capacity
200A
400A
400A
400A
400A
400A
200A
200A
200A
200A
200A
200A
Breaker
Single 200
Dual 200
Dual 200
Dual 200
Dual 200
Dual 200
Single 200
Single 200
Single 200
Single 200
Single 200
Single 200
Horizontal/
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
L1430 Plug
•
•
•
Physical
Dimensions
13” x 30”
18” x 30”
13” x 30”
18” x 30”
18” x 30”
18” x 30”
13” x 30”
13” x 30”
13” x 30”
13” x 30”
13” x 30”
13” x 30”
Power Flow Diagram
normal operation voltage path
Utility Power
Control
Divi
Voltage Sensor 1*
Divi
Control Circuit
for
LatchingIndependant Control
Circuits for Relays
Relay
Voltage Sensor 4*
Set of Control Relays
that interact with Voltage
Sensor # 1 and Independent
Control Circuits
Voltage Sensor 3*
Latching
Meter Base
Generator
Relay
Optional Service
Disconnect Breaker
**NOTE:
House
Breaker Panel
* Voltage Sensor
Generator
Relay
Generator
Circuit
Breaker
Generator
Test
Switches
and
Indicator
Lights
Power Flow Diagram
emergency operation voltage path
Utility Power
Control
Divi
Voltage Sensor 1*
Divi
Control Circuit
for
LatchingIndependant Control
Circuits for Relays
Relay
Voltage Sensor 4*
Set of Control Relays
that interact with Voltage
Sensor # 1 and Independent
Control Circuits
Voltage Sensor 3*
Latching
Meter Base
Generator
Relay
Optional Service
Disconnect Breaker
**NOTE:
House
Breaker Panel
* Voltage Sensor
Generator
Relay
Generator
Circuit
Breaker
Generator
Test
Switches
and
Indicator
Lights
Limited Warranty
PSP Products, Inc. expressly warrants its product to the original purchaser of this product,
except as noted and listed below, to be free of defects in material and/or workmanship for a
period of two (2) years from date of installation or three (3) years from manufacturing date code.
Except for this express warranty, the purchaser accepts products(s) “as is”. Remedies under this
warranty are limited to repairing or replacing, at PSP Products’ option, any malfunctioning
part or component which shall, within the above stated warranty, be returned to PSP Products,
Inc. at the address listed below, freight prepaid.
This limited warranty does not cover- normal maintenance such as replacement of fuses etc.,
transportation and installation charges for the replacement part or component, or any other
service calls or labor repairs.
This warranty does not apply:
• If the unit is damaged by an act of God (lightning, flood, etc.)
• If the unit has been subject to alteration, neglect, misuse, or abuse.
• If installed in a hostile environment that has caused a premature failure.
• If damage occurs during shipment or handling by the freight carrier. It is the receiver’s
responsibility to process claims involving freight damage.
• If damage is caused by improper voltage or power supply source.
• If unit is not installed according to manufacturer’s specifications and installation instruction
manual.
• If incorrect model or size was installed for the application.
• If unit contains modifications to internal wiring, removal or bypass of parts, bypass of
safety circuits, modification of parts or circuit boards, or mechanical airflow changes
not authorized in writing by the factory.
• If the serial identification decal (label) is defaced.
The returned part or component must contain a warranty tag or information clearly stating
serial number, installation date, and nature of failure.
Replacement of a part component under this limited warranty does not extend the warranty term
or period.
There are no other express warranties. Specification sheets and descriptions of this product are
only to identify it, and are not a warranty claim that the unit fits the description. We do not
warranty this product suitable for a specific installation or application. It is the owner’s (or
installer’s) responsibility for proper application.
PSP Products, Inc. is not bound by representatives, installers, warranties, or promises made by
others beyond the terms of this express warranty. In no event shall PSP Products, Inc. be
responsible for any installation incidental or consequential damages.
Any action for branch of this limited warranty must be commenced within one year from the date
of the breach.
This warranty give you specific legal rights, and you may also have other rights which vary from
state to state. For example, some states do not allow the exclusion or limitation of incidental
or consequential damages.
So the above limitation may not apply to you.
www.pspproducts.com
PSP Products, Inc.
P.O.Box 4108 • Manassas, Va 20108
Tel 800.648.6802 • fax 800.767.6645
www.pspproducts.com • [email protected]