DEKRA Certification B.V.
Transcription
DEKRA Certification B.V.
NOTIFICATION OF TEST RESULTS Issued to: Wago-Kontakttechnik GmbH & Co. KG Hansastrasse 27, 32423 Minden/westfalen, Germany For the product: terminal blocks for copper conductors Trade name: WAGO Type/Model: 2060 Manufactured by: Wago-Kontakttechnik GmbH & Co. KG Hansastrasse 27, 32423 Minden/westfalen, Germany Ratings: see page 38 of the test report Additional information: This NTR replaces our NTR NL-7385 dated 2015-03-19 Pre-licence factory inspection carried out by DEKRA Certification B.V. A sample of the product has been tested and found to be in conformity with the current HD/EN and equivalent national standard EN 60947-7-1:2009 As shown in the Test Report 2184109.50 This Notification of Test Results is the result of testing a sample of the product submitted, in accordance with the provisions of the relevant specific standard. This Notification of Test Results has been established by a body, which participates in the CENELEC Certification Agreement (CCA) of 11th September 1973 as amended on 29th March 1983. Any other body participating in the CCA will take this Notification as a basis for granting a national mark of conformity or a national approval as specified in the CCA, as long as the standard referred to above is still in force in the country of that body. Arnhem, 24 June 2015 Number: NTR NL-7419 DEKRA Certification B.V. x F.S. Strikwerda Certification Manager © Integral publication of this attestation and adjoining reports is allowed CCA CENELEC CERTIFICATION AGREEMENT ACCORD DE CERTIFICATION DU CENELEC DEKRA Certification B.V. Meander 1051, 6825 MJ Arnhem P.O. Box 5185, 6802 ED Arnhem, The Netherlands T +31 88 96 83000 F +31 88 96 83100 www.dekra-certification.com Company registration 09085396 Responsible CB: OD ECS 040-1 ed. May 2013 TEST REPORT SUMMARY Report Reference No. ................... : 2184109.50 Date of issue................................... : 2015-06-24 Tested by (name + signature).......... : W.C. van Ginkel Witnessed by (name + signature).... : Approved by (name + signature) ..... : H.L. Schendstok Supervised by (name + signature)... : 4 r Testing Laboratory........................ : DEKRA Certification B.V. Address .......................................... : Meander 1051, 6825 MJ Arnhem, The Netherlands Testing procedure ........................... : ENEC/CCA-TL IECEE-CBTL TMP WMT Testing location ............................ : DEKRA Certification B.V. Address .......................................... : Meander 1051, 6825 MJ Arnhem, The Netherlands Applicant ....................................... : WAGO Kontakttechnik GmbH Address .......................................... : Hansastraße 27, 32423 Minden, Germany Manufacturer ................................. : WAGO Kontakttechnik GmbH Address .......................................... : Hansastraße 27, 32423 Minden, Germany Product.......................................... : Terminal blocks for copper conductors Model/Type reference ..................... : 2060 SMT Trademark ...................................... : Ratings ........................................... : Certification Scheme....................... : Standard(s).................................... : See page 38 of the test report ENEC CCA Other: ________ EN 60947-7-1:2009 The text of the a.m. European Standard was approved by CENELEC under the Unique Acceptance Procedure and is identical with the corresponding IEC Publication. The text of the a.m. European Standard was approved by CENELEC with agreed common modifications and is not identical with the corresponding IEC Publication. This EN test report consists of the following parts: IEC TRF No.: IEC60947_7_1A Report Reference No....................... : 2184109.50 CENELEC-Addendum Form No. Report Reference No. or Annex No.. : __________________ .................... : Copyright © 2013 EEPCA, Paris, France. All rights reserved. This ECS document together with the test report is only valid if signed by an approved ENEC or CCA Testing Laboratory and accompanied by the associated ENEC Licence or CCA Notification of Test Results, issued by a Certification Body member of ECS. doc20150715111256164.doc page 1 of 1 Test Report issued under the responsibility of: TEST REPORT IEC 60947-7-1 Low-voltage switchgear and controlgear Part 7: Ancillary equipment Section One: Terminal blocks for copper conductors Report Reference No. ................... : 2184109.50 Date of issue................................... : 2015-06-24 Total number of pages ..................... 38 pages CB/CCA Testing Laboratory......... : DEKRA Certification B.V. Address .......................................... : Meander 1051, 6825 MJ, Arnhem, The Netherlands Applicant’s name .......................... : WAGO Kontakttechnik GmbH Address .......................................... : Hansastraße 27, Minden, Germany Test specification: Standard......................................... : IEC 60947-7-1:2009 (Third Edition) Test procedure ............................... : CB Scheme Non-standard test method…………..: N/A Test Report Form No. ................... : IEC60947_7_1A Test Report Form(s) Originator ....... : KEMA Quality B.V. Master TRF .................................... : Dated 2009-07 Copyright © 2009 IEC System for Conformity Testing and Certification of Electrical Equipment (IECEE), Geneva, Switzerland. All rights reserved. This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as copyright owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting from the reader's interpretation of the reproduced material due to its placement and context. If this Test Report Form is used by non-IECEE members, the IECEE/IEC logo and the reference to the CB Scheme procedure shall be removed. This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory and appended to a CB Test Certificate issued by an NCB in accordance with IECEE 02. Test item description....................... : terminal blocks for copper conductors Trade Mark ..................................... : Manufacturer .................................. : WAGO Kontakttechnik GmbH Model/Type reference ..................... : 2060-… Ratings ........................................... : See page 38 Factory location ................................: WAGO Kontakttechnik GmbH, Hansastraße 27, Minden, Germany, See complete overview of factory locations: General product Information Page 2 of 38 Report No. 2184109.50 Testing procedure and testing location: CCA Testing Laboratory: Testing location/ address ..................... : Associated CCA Laboratory: Testing location/ address ..................... : DEKRA Certification B.V. Meander 1051, 6825 MJ Arnhem, The Netherlands 4 r Tested by (name + signature) .....: W.C van Ginkel Approved by (+ signature) ..........: H.L. Schendstok Testing procedure: TMP Tested by (name + signature) .....: Approved by (+ signature) ...........: Testing location/ address ..................... : Testing procedure: WMT Tested by (name + signature) .....: Witnessed by (+ signature) ..........: Approved by (+ signature) ..........: Testing location/ address ..................... : Testing procedure: SMT Tested by (name + signature) .....: Approved by (+ signature) .................................................... : Supervised by (+ signature) ........: Testing location/ address ............... : Testing procedure: RMT Tested by (name + signature) .....: Approved by (+ signature) .................................................... : Supervised by (+ signature) ........: Testing location/ address ..................... : TRF No. IEC 60947_7_1A Page 3 of 38 Report No. 2184109.50 Summary of testing: Tests performed (name of test and test clause): Type test Testing location: DEKRA Certification B.V. Meander 1051 6826 MJ Arnhem, The Netherlands Summary of compliance with National Differences: TRF No. IEC 60947_7_1A Page 4 of 38 Copy of marking plate: 2060 Test item particulars.............................................. : Classification of installation and use ......................... : Supply Connection .................................................. : ............................................................................... : ............................................................................... : Possible test case verdicts: - test case does not apply to the test object ............... : N/A - test object does meet the requirement..................... : P (Pass) - test object does not meet the requirement ............... : F (Fail) Testing.................................................................... : Date of receipt of test item ........................................ : 06-2012 and 07-2013 Date (s) of performance of tests ................................ : 07-2012 and 08-2013 TRF No. IEC 60947_7_1A Report No. 2184109.50 Page 5 of 38 Report No. 2184109.50 General remarks: The test results presented in this report relate only to the object tested. This report shall not be reproduced, except in full, without the written approval of the Issuing testing laboratory. "(see Enclosure #)" refers to additional information appended to the report. "(see appended table)" refers to a table appended to the report. Throughout this report a comma (point) is used as the decimal separator. All tests are carried out on type 2060-402 unless otherwise stated This TRF replaces TRF 2171408.51 dated 2014-06-23. General product information: See page 37 and 38 Factory locations: Wago Elwag sp.z.o.o. ul. Piekna 58 a, 50-506, Wroclaw Poland Wago & Controls (India) Ltd. C-27, Sector-58, Phase III, 201 301 Noida Gautam Budh Nagar (U.P) India Wago Electronic (Tianjin) Co. Ltd. No. 5 Quanhui Road, 301700, Tianjin China WAGO Kontakttechnik GmbH & Co. KG Hansastraße 27, 32423 Minden/Westfalen Germany WAGO Kontakttechnik GmbH & Co. KG, Werk Sondershausen Waldstraße 1, 99706, Sondershausen Germany WAGO Contact S.A. Route de l’Industrie 19, 1564, Domdidier Switzerland TRF No. IEC 60947_7_1A Page 6 of 38 Report No. 2184109.50 Particulars: test item vs. test requirements - method of fixing...................................................... : SMD technology - number of poles ..................................................... : 1 - 3 poles - type of clamping units............................................. : screwless-type terminals - ability to receive conductors.................................... : unprepared conductors, (flexible or rigid) - number of terminals on terminal assembly............... : 1 - rated cross-section (mm²) ....................................... : 0,75 mm² - rated connecting capacity (mm²) ............................. : 0,25 mm² - 0,75 mm² rigid and flexible - rated insulation voltage (Ui) .................................... : See page 37 and 38 - rated impulse withstand voltage (Uimp) ................... : See page 37 and 38 - Conventional free air thermal current (Ith)................ : 9 A TRF No. IEC 60947_7_1A Page 7 of 38 Report No. 2184109.50 IEC 60947-7-1 Clause Requirement Test 5.1 MARKING Result - Remark Verdict Terminal block shall be marked with: P - manufacturer's name or trademark - type designation 5.2 2060 P The following information shall be stated by the manufacturer if applicable, e.g. in the manufacturer's data sheet, or his catalogue or on the packing unit: IEC 60947-7-1 P - rated cross-section 0,75 mm2 P - rated connecting capacity 0,25 mm² - 0,75 mm² rigid and flexible P - rated insulation voltage (Ui) See page 37 and 38 P - rated impulse withstand voltage (Uimp) See page 37 and 38 P - conventional free air thermal current (Ith) 9A P - manufacturer's claim for compliance with EN 60 947-7-1 - service conditions if different from those of Cl. 6. 7. CONSTRUCTION 7.1 Constructional requirements 7.1.1 Clamping units All parts of clamping units which maintain contact 7.1.7.1 N P and carry current shall be of metal having adequate mechanical strength Clamping units connections shall be such that P necessary contact pressure is maintained Clamping units shall be so constructed that the P conductor is clamped between suitable surfaces without damage to the conductor and terminal Clamping units shall not allow the conductor to be displaced or to be displaced themselves in a manner detrimental to the operation of equipment and the insulation voltage shall not be reduced below the rated value TRF No. IEC 60947_7_1A P Page 8 of 38 Report No. 2184109.50 IEC 60947-7-1 Clause Requirement Test Result - Remark Clamping units shall allow the conductor to be Verdict P connected by means ensuring that a reliable mechanical linkage and electrical contact is properly maintained P Clamping units shall be able to withstand the forces that can be applied through the connected conductors P Contact pressure is not transmitted through insulation materials 7.1.2 Mounting P Terminal blocks shall be provided with means that allow them to be securely attached to a rail or a mounting surface (see 8.3.2) 7.1.3 Clearances and creepage distances For clearances and creepage distances see 8.4.2 7.1.4 Terminal identification and marking: N - terminals intended exclusively for the neutral conductor - other terminals P - terminal blocks shall have provision, or at least space, for identification marks or numbers for each terminal or terminal assembly to be related to the circuit of which it is to form a part P - For the identification of the terminal block the colour combination green-yellow is not allowed 7.1.5 Resistance to abnormal heat and fire P Needle flame test for insulation materials of terminal blocks (see 8.5) 7.1.6 Rated cross-section and rated connecting capacity Terminal blocks are so designed that conductors 0,25 mm² - 0,75 mm² rigid of the rated cross-section and/or the rated and flexible connecting capacity can be accepted TRF No. IEC 60947_7_1A P Page 9 of 38 Report No. 2184109.50 IEC 60947-7-1 Clause Requirement Test 8 TESTS 8.3 Verification of mechanical characteristics 8.3.2 Attachment of the terminal block on its support Result - Remark Verdict mounting rail ......................................................: SMD technology Tighting torque (Nm) ........................................... : - steel pin diameter (mm) ......................................: 1 mm force (N) .............................................................: 1 N During the test, no terminal block shall work free P from its rail or support, nor suffer any other damage 8.3.3 Mechanical properties of clamping units 8.3.3.1 Test of mechanical strenght of clamping units 8.2.4.1 Mechanical strength of clamping units (EN 60947-1) 2 rated cross-section of a rigid conductor (mm²) ....: 0,75 mm diameter of thread (mm) .....................................: torque (Nm) ........................................................: - 5 times on 2 clamping units at the centre terminal 5 times inserted and removed block out of 5 terminal blocks P Voltage drop before and after mechanical strength test 2 rated cross-section of a rigid conductor (mm²) ....: 0,75 mm test current (A) d.c. .............................................: 0,9 A 0,79 mV - 0,82 mV voltage drop (mV) before mechanical strength P test not exceeding 3,2 mV ..................................: If the measured value exceeds 3,2 mV, the voltage N drop is determined on each individual clamping unit seperately, which shall not exceed 1,6 mV voltage drop (mV) after mechanical strength test 0,74 mV - 0,84 mV P 0,25 mm2 not exceeding 150% of the value measured before mechanical strength test : minimum cross-section of a flexible conductor (mm²) .................................................................: test current (A) d.c. .............................................: 0,4 A TRF No. IEC 60947_7_1A Page 10 of 38 Report No. 2184109.50 IEC 60947-7-1 Clause Requirement Test Result - Remark voltage drop (mV) before mechanical strength 0,66 mV - 0,76 mV Verdict P test not exceeding 3,2 mV ..................................: N If the measured value exceeds 3,2 mV, the voltage drop is determined on each individual clamping unit separately, which shall not exceed 1,6 mV voltage drop (mV) after mechanical strength test 0,68 mV - 0,79 mV P not exceeding 150% of the value measured before mechanical strength test ..........................: 8.3.3.2 Testing for damage to and accidental loosening of conductors of a terminal block (flexion test) 2 conductor of the smallest cross-section (mm²) ....: 0,25 mm flexible and rigid 1 number of conductors of the smallest cross-section ......................................................: torque (Nm) ........................................................: diameter of bushing hole (mm) ...........................: 6,5 mm 260 mm height between the equipment and the platen (mm) ..................................................................: mass at the conductor(s) (kg) .............................: 0,2 kg P 135 continuous revolutions: the conductor shall P neither slip out of the terminal nor break near the clamping unit Pull-out test force (N) .............................................................: 10 N 1 min, the conductor shall neither slip out of the P terminal nor break near the clamping unit 2 conductor of the rated cross-section (mm²) .........: 0,75 mm flexible and rigid number of conductors of the rated cross-section .: 1 torque (Nm) ........................................................: diameter of bushing hole (mm) ...........................: 6,5 mm 260 mm height between the equipment and the platen (mm) ..................................................................: mass at the conductor(s) (kg) .............................: 0,4 kg TRF No. IEC 60947_7_1A Page 11 of 38 Report No. 2184109.50 IEC 60947-7-1 Clause Requirement Test Result - Remark Verdict P 135 continuous revolutions: the conductor shall neither slip out of the terminal nor break near the clamping unit Pull-out test force (N) .............................................................: 30 N 1 min, the conductor shall neither slip out of the P terminal nor break near the clamping unit 2 conductor of the largest cross-section (mm²) ......: 0,75 mm flexible and rigid number of conductors of the largest cross-section 1 ...........................................................................: torque (Nm) ........................................................: diameter of bushing hole (mm) ...........................: 6,5 mm 260 mm height between the equipment and the platen (mm) ..................................................................: mass at the conductor(s) (kg) .............................: 0,4 kg 135 continuous revolutions: the conductor shall P neither slip out of the terminal nor break near the clamping unit Pull-out test force (N) .............................................................: 30 N 1 min, the conductor shall neither slip out of the P terminal nor break near the clamping unit conductor of the largest or smallest cross-section (mm²) .................................................................: number of conductors of the largest or smallest cross-section ......................................................: torque (Nm) ........................................................: diameter of bushing hole (mm) ...........................: height between the equipment and the platen (mm) ..................................................................: mass at the conductor(s) (kg) .............................: TRF No. IEC 60947_7_1A Page 12 of 38 Report No. 2184109.50 IEC 60947-7-1 Clause Requirement Test Result - Remark Verdict N 135 continuous revolutions: the conductor shall neither slip out of the terminal nor break near the clamping unit Pull-out test force (N) .............................................................: 1 min, the conductor shall neither slip out of the N terminal nor break near the clamping unit 8.3.3.4 Verification of rated cross section and rated connecting capacity P One conductor of the two next smaller crosssections can be unhindered and connected in 0,25 mm² each clamping unit of one terminal block (up to 35 mm²) 8.4.2 Verification of clearances and creepage distances Conductor type and conductor cross-section 8.4.2.2 Conductor end length (mm) 6 - 7 mm Type of support SMD technology Clearances (pollution degree 3) Case A (mm) ....................................................... : 0,8 mm P Case B (mm) ....................................................... : 1,5 mm Measured (mm) ................................................... : 1,7 mm Rated impulse withstand voltage Uimp (kV) 8.4.2.2 2,5 kV P Clearances (pollution degree 2) Case A (mm) ....................................................... : 0,6 mm P Case B (mm) ....................................................... : 1,5 mm Measured (mm) ................................................... : 1,7 mm Rated impulse withstand voltage Uimp (kV) 8.4.2.3 2,5 kV P Creepage distances: - pollution degree ...............................................: 2 - comparative tracking index (V) .........................: 600 V - material group ..................................................: I - rated insulation voltage Ui (V) ..........................: 320 V TRF No. IEC 60947_7_1A Page 13 of 38 Report No. 2184109.50 IEC 60947-7-1 Clause Requirement Test Result - Remark - minimum creepage distances (mm) ..................: 1,6 mm - measured creepage distances (mm) ................: 1,7 mm 8.4.2.3 8.4.2.3 Verdict Creepage distances: - pollution degree ...............................................: 2 - comparative tracking index (V) .........................: 600 V - material group ..................................................: I - rated insulation voltage Ui (V) ..........................: 160 V - minimum creepage distances (mm) ..................: 0,8 mm - measured creepage distances (mm) ................: 1,7 mm Creepage distances: - pollution degree ...............................................: 3 - comparative tracking index (V) .........................: 600 V - material group ..................................................: I - rated insulation voltage Ui (V) ..........................: 63 V - minimum creepage distances (mm) ..................: 1,6 mm - measured creepage distances (mm) ................: 1,7 mm 8.4 Verification of electrical characteristics 8.4.3 Dielectric tests Dielectric test, Uimp indicated: - five terminal blocks connected with 0,75 mm² /rigid/ 6 – 7mm unfavourable cross-section (mm²) / type / conductor end length (mm) .................................: - rated impulse withstand voltage (kV) ................: 2,5 kV - test Uimp main circuits (kV) ..............................: 2,95 kV P Dielectric test, Uimp not indicated: - five terminal blocks connected with 0,75 mm² /rigid/ 6 – 7mm unfavourable cross-section (mm²) / type / conductor end length (mm) : - rated insulation voltage (V) ...............................: 320 V (tested with highest) - test voltage for 5 sec (V) ..................................: 1890 V TRF No. IEC 60947_7_1A P Page 14 of 38 Report No. 2184109.50 IEC 60947-7-1 Clause Requirement Test 8.4.2 Verification of clearances and creepage distances Result - Remark Verdict type 2060-802/998-404 and 2060-802 Conductor type and conductor cross-section 8.4.2.2 Conductor end length (mm) 6 - 7 mm Type of support SMD technology Clearances Case A (mm) ....................................................... : 5,5 mm P Case B (mm) ....................................................... : 2 mm Measured (mm) ................................................... : 6,8 mm Rated impulse withstand voltage Uimp (kV) 8.4.2.3 8.4.2.3 8.4.2.3 6 kV P Creepage distances: - pollution degree ...............................................: 3 - comparative tracking index (V) .........................: 175 V - material group ..................................................: I - rated insulation voltage Ui (V) ..........................: 400 V - minimum creepage distances (mm) ..................: 5 mm - measured creepage distances (mm) ................: 7,21 mm Creepage distances: - pollution degree ...............................................: 2 - comparative tracking index (V) .........................: 400 V - material group ..................................................: I - rated insulation voltage Ui (V) ..........................: 630 V - minimum creepage distances (mm) ..................: 3,2 mm - measured creepage distances (mm) ................: 7,21 mm Creepage distances: - pollution degree ...............................................: 2 - comparative tracking index (V) .........................: 400 V - material group ..................................................: I - rated insulation voltage Ui (V) ..........................: 1000 V - minimum creepage distances (mm) ..................: 5 mm TRF No. IEC 60947_7_1A Page 15 of 38 Report No. 2184109.50 IEC 60947-7-1 Clause Requirement Test Result - Remark - measured creepage distances (mm) ................: 7,21 mm 8.4 Verification of electrical characteristics 8.4.3 Dielectric tests Verdict Dielectric test, Uimp indicated: - five terminal blocks connected with 0,75 mm² /rigid/ 6 – 7 mm unfavourable cross-section (mm²) / type / conductor end length (mm) .................................: - rated impulse withstand voltage (kV) ................: 6 kV - test Uimp main circuits (kV) ..............................: 9,8 kV P Dielectric test, Uimp not indicated: - five terminal blocks connected with 0,75 mm² /rigid/ 6 – 7mm unfavourable cross-section (mm²) / type / conductor end length (mm) : - rated insulation voltage (V) ...............................: 1000 V (tested with highest) - test voltage for 5 sec (V) ..................................: 2200 V TRF No. IEC 60947_7_1A P Page 16 of 38 Report No. 2184109.50 IEC 60947-7-1 Clause Requirement Test 8.4.5 Temperature-rise test Result - Remark Verdict Temperature-rise conditions: - test current (A) .................................................: 9A - cross-section of the conductor (mm²) ................: 0,75 mm rigid - torque (Nm) ......................................................: 29,0 K – 32,6 K - temperature-rise does not exceed 45 K Voltage drop before and after temperature-rise test: - test current (A) d.c. ...........................................: 0,9 A - voltage drop (mV) before temperature-ise test 0,53 mV - 0,79 mV P P not exceeding 3,2 mV .........................................: If the measured value exceeds 3,2 mV, the voltage N drop is determined on each individual clamping unit separately, which shall not exceed 1,6 mV - voltage drop (mV) after temperature-rise test not 0,57 mV - 0,81 mV P exceeding 150% of the value measured before temperature-rise test ..........................................: 8.4.6 Short-time withstand current test 2 - rated cross-section of the conductor (mm²) .......: 0,75 mm - torque (Nm) ......................................................: - - test current (A) .................................................: 90 A - duration of the test current (s) ...........................: 1 s At the end of the test no damage that may impair P further use shall have occurred to any part of the terminal block Voltage drop before and after short-time withstand current test - test current (A) d.c. ...........................................: 0,9 A 0,91 mV - voltage drop (mV) before short-time withstand P current test not exceeding 3,2 mV ......................: If the measured value exceeds 3,2 mV, the voltage drop is determined on each individual clamping unit separately, which shall not exceed 1,6 mV TRF No. IEC 60947_7_1A N Page 17 of 38 Report No. 2184109.50 IEC 60947-7-1 Clause Requirement Test Result - Remark - voltage drop (mV) after short-time withstand 0,78 mV Verdict P current test not exceeding 150% of the value measured before short-time withstand current test ...........................................................................: 8.4.7 Ageing test (for screwless-type terminal blocks only) Maximum ambient temperature (C) ...................: 40 C / Rated cross-section rigid or stranded < 10 mm² 2 0,75 mm solid, > 10 mm² stranded (mm²) ..........................: Test current (A) according 8.4.5 .........................: 9 A Heating cabinet is increased, in each cycle to (C) 40 °C ...........................................................................: Test current (A) d.c. for measurement of the 0,9 A voltage drop .......................................................: Voltage drop after 0 cycles: - requirement: 3,2 mV (mV) .............................: 1,78 mV - 1,98 mV P If the measured value exceeds 3,2 mV, the voltage N drop is determined on each individual clamping unit separately, which shall not exceed 1,6 mV Voltage drop after the 24th cycle: - requirement: 4,8 mV (mV) ................................: 1,83 mV - 1,99 mV P Voltage drop after the 48th cycle - requirement: 4,8 mV or 1,5 times the value 1,83 mV - 1,99 mV P 1,83 mV - 1,99 mV P 1,83 mV - 1,99 mV P measured after the 24th cycle (mV) ....................: Voltage drop after the 72th cycle: - requirement: 4,8 mV or 1,5 times the value measured after the 24th cycle (mV) ....................: Voltage drop after the 96th cycle: - requirement: 4,8 mV or 1,5 times the value measured after the 24th cycle (mV) ....................: Voltage drop after the 120th cycle: TRF No. IEC 60947_7_1A Page 18 of 38 Report No. 2184109.50 IEC 60947-7-1 Clause Requirement Test Result - Remark - requirement: 4,8 mV or 1,5 times the value 1,83 mV - 1,99 mV P 1,84 mV - 1,99 mV P 1,83 mV - 1,99 mV P 1,83 mV - 1,99 mV P Verdict measured after the 24th cycle (mV) ....................: Voltage drop after the 144th cycle: - requirement: 4,8 mV or 1,5 times the value measured after the 24th cycle (mV) ....................: Voltage drop after the 168th cycle: - requirement: 4,8 mV or 1,5 times the value measured after the 24th cycle (mV) ....................: Voltage drop after the 192th cycle: - requirement: 4,8 mV or 1,5 times the value measured after the 24th cycle (mV) ....................: Pull-out test force (N) .............................................................: 30 N 1 min, the conductor shall neither slip out of the P terminal nor break near the clamping unit 8.5 P Verification of thermal characteristics are checked by the needle flame test. P Before the test, the terminal blocks are stored for 24 h in an atmosphere having a temperature between 15°C and 35°C and a relative humidity between 45% and 75% The flame is applied for 10 s. 5s P for insulation walls <1 mm and / or an area < 100 mm², the flame is applied for 5 s. The terminal blocks are considered to have passed the test if the duration of burning is < 30s in case of ignition. Moreover, the tissue paper on the pinewood board shall not ignite if burning or glowing particles fall from the terminal block. TRF No. IEC 60947_7_1A P Page 19 of 38 Report No. 2184109.50 IEC 60947-7-1 Clause Requirement Test 8.6 Verification of EMC characteristics Result - Remark Subclause 8.4 of EN 60947-1 applies with the Verdict N following addition: 8.6.1 Immunity Terminal blocks within the scope of this standard N are not sensitive of electromagnetic disturbances and therefore no immunity tests are necessary. 8.6.2 Emission Terminal blocks within the scope of this standard N do not generate electromagnetic disturbances and therefore no emission tests are necessary. Annex A vacant Annex B informative Items subject to agreement between manufacturer and user Annex C vacant Annex D ADDITIONAL REQUIREMENTS FOR TEST DISCONNECT N TERMINALBLOCKS D5 Product information - service life in number of cycles D6. Normal service, mounting and transport conditions Clause 6 applies. D7 Construction and performance conditions Clause 7 applies with the following additions D7.1 N Constructional requirements TRF No. IEC 60947_7_1A N Page 20 of 38 Report No. 2184109.50 IEC 60947-7-1 Clause Requirement Test D7.1.3 Clearances and creepages are not required to be Result - Remark Verdict N measured over the open disconnect contacts (Gap). However, the rated impulse withstand voltage (Uimp) stated by the manufacturer according to table 13 of EN 60947-1, without using the altitude correction factor, shall be verified across the open disconnect contacts (gap) (see D.7.2.2) D7.1.7 Disconnect unit For longitudinal and perpendicular disconnection, N test disconnect terminal blocks may be equipped with disconnect units, for instance of the following type: - plug - knife - slide (with or without busbar) the position of the disconnect unit shall be N recognizable in normal use and shall not be changed unintentionally D.7.2.2 Dielectric properties Dielectric test, Uimp indicated: - five terminal blocks connected with unfavourable cross-section (mm²) / type / conductor end length tested over open disconnect contacts (gap) (mm) ..........................: D.8.4.5 - rated impulse withstand voltage (kV) ................: - test Uimp without altitude correction factor (kV) : N Temperature-rise test Temperature-rise conditions: - test current (A) .................................................: - cross-section of the conductor (mm²) ................: TRF No. IEC 60947_7_1A Page 21 of 38 Report No. 2184109.50 IEC 60947-7-1 Clause Requirement Test Result - Remark Verdict - torque (Nm) ......................................................: - torque disconnect unit (Nm) .............................: - temperature-rise does not exceed 45 K N Voltage drop before and after temperature-rise test: - test current (A) d.c. ...........................................: - voltage drop (mV) before temperature-rise test N not exceeding 1,6 mV times the total of conductor clamping unit and disconnect unit contact points .....................................................: If the measured value exceeds this calculated N value, the voltage drop is measured on each individual conductor clamping unit and disconnect unit contact point. it shall not exceed 1,6 mV on any conductor clamping unit and disconnect unit contact point - voltage drop (mV) after temperature-rise test not N exceeding 150% of the value measured before temperature-rise test ..........................................: D.8.4.6 Short-time withstand current test - rated cross-section of the conductor (mm²) .......: - torque (Nm) ......................................................: - torque disconnect unit (Nm) .............................: - test current (A) .................................................: - duration of the test current (s) ...........................: At the end of the test, continuity shall exist on the N test sample assembly and the terminal blocks shall not show any cracking, breakage or other critical damage Voltage drop before and after short-time withstand current test - test current (A) d.c. ...........................................: TRF No. IEC 60947_7_1A Page 22 of 38 Report No. 2184109.50 IEC 60947-7-1 Clause Requirement Test Result - Remark Verdict N - voltage drop (mV) before temperature-rise test not exceeding 1,6 mV times the total of conductor clamping unit and disconnect unit contact points .....................................................: N If the measured value exceeds this calculated value, the voltage drop is measured on each individual conductor clamping unit and disconnect unit contact point. it shall not exceed 1,6 mV on any conductor clamping unit and disconnect unit contact point N - voltage drop (mV) after temperature-rise test not exceeding 150% of the value measured before temperature-rise test ..........................................: D.8.4.7 Ageing test for test disconnect terminal blocks with screwless-type clamping units Maximum ambient temperature (C) ...................: 40 C / Rated cross-section rigid or stranded < 10 mm² solid, > 10 mm² stranded (mm²) ..........................: Test current (A) according D.8.4.5 ......................: Torque disconnect unit (Nm) ..............................: Heating cabinet is increased, in each cycle to (C) ...........................................................................: Test current (A) d.c. for measurement of the voltage drop .......................................................: Voltage drop after 0 cycles: - requirement: 1,6 mV (mV) .............................: 1 the voltage drop is determined on each individual 2- clamping unit separately 345- Voltage drop after the 24th cycle: TRF No. IEC 60947_7_1A N Page 23 of 38 Report No. 2184109.50 IEC 60947-7-1 Clause Requirement Test Result - Remark - requirement: 2,4 mV (mV) ................................: 1 - Verdict N 2345Voltage drop after the 48th cycle - requirement: 2,4 mV or 1,5 times the value 1- measured after the 24th cycle, whichever is the 2- N lower (mV) .........................................................: 3 45Voltage drop after the 72th cycle: - requirement: 2,4 mV or 1,5 times the value 1- measured after the 24th cycle, whichever is the 2- N lower (mV) .........................................................: 3 45Voltage drop after the 96th cycle: - requirement: 2,4 mV or 1,5 times the value 1- measured after the 24th cycle, whichever is the 2- N lower (mV) .........................................................: 3 45Voltage drop after the 120th cycle: - requirement: 2,4 mV or 1,5 times the value 1- measured after the 24th cycle, whichever is the 2- lower (mV) .........................................................: 3 45Voltage drop after the 144th cycle: TRF No. IEC 60947_7_1A N Page 24 of 38 Report No. 2184109.50 IEC 60947-7-1 Clause Requirement Test Result - Remark - requirement: 2,4 mV or 1,5 times the value 1- measured after the 24th cycle, whichever is the 2- Verdict N lower (mV) .........................................................: 3 45Voltage drop after the 168th cycle: - requirement: 2,4 mV or 1,5 times the value 1- measured after the 24th cycle, whichever is the 2- N lower (mV) .........................................................: 3 45Voltage drop after the 192th cycle: - requirement: 2,4 mV or 1,5 times the value 1- measured after the 24th cycle, whichever is the 2- N lower (mV) .........................................................: 3 45Pull-out test force (N) .............................................................: 1 min, the conductor shall neither slip out of the N terminal nor break near the clamping unit D.8.5.1 Service life - rated cross-section of the conductor (mm²) .......: - torque (Nm) ......................................................: - torque disconnect unit (Nm) .............................: - number of operating cycles ..............................: Entire test apparatus is stored for 168 h in dry N heat at a temperature of 85 °C Voltage drop before and after service life - test current (A) d.c. ...........................................: TRF No. IEC 60947_7_1A Page 25 of 38 Report No. 2184109.50 IEC 60947-7-1 Clause Requirement Test - voltage drop (mV) before service life test not Result - Remark Verdict N exceeding 1,6 mV times the total of conductor clamping unit and disconnect unit contact points : If the measured value exceeds this calculated N value, the voltage drop is measured on each individual conductor clamping unit and disconnect unit contact point. it shall not exceed 1,6 mV on any conductor clamping unit and disconnect unit contact point - voltage drop (mV) after service life test not N exceeding 150% of the value measured before service life test ...................................................: D.8.4.5 Emission Terminal blocks within the scope of this standard N are not sensitive of electromagnetic disturbances and therefore no immunity tests are necessary. 8.6.2 Emission Terminal blocks within the scope of this standard do not generate electromagnetic disturbances and therefore no emission tests are necessary. TRF No. IEC 60947_7_1A N Page 26 of 38 Clause Requirement Test Report No. 2184109.50 Result - Remark Verdict ANNEX A EN 60998-2-2 screwless-type clamping units 8 MARKING 8.1 On main part: a) rated connecting capacity (mm²).......................: 0,75 mm² P b) rated insulation voltage (V)...............................: N c) T marking (°C) (if > 40 C or < -5 C) ................: N d) type reference .................................................: 2060 P e) manufacturer's or responsible vendor's name, Wago trademark or identification mark............................: P f) IP if > IP20 .......................................................: N Type of acceptable conductor "r" or "f" P Small devices: only d) and e) indicated on device P All marks visible on smallest package unit catalogue P 8.2 Multiway terminal devices: at least two adjacent P 8.4 Marking: durable and easily legible; 15 s water; 15 s hexane P 9 PROTECTION AGAINST ELECTRIC SHOCK Live parts not accessible P 10 CONNECTION OF CONDUCTORS 10.1 Connecting devices allow correct connection of conductors P 10.101 Connection or disconnection: use a general tool or simple insertion P TRF No. IEC 60947_7_1A Page 27 of 38 Clause Requirement Test Report No. 2184109.50 Result - Remark Disconnection operation other than a pull 10.102 Verdict P Terminals accept two or more conductors of same or different nominal crosssectional areas; see table 101 (as specified by manufacturer): P Rated connecting capacity (mm²) .........................: 0,75 mm² 0,25 mm² - 0,75 mm² Suitable for connecting cross-sectional areas (mm²) ..................................................................: (flexible or rigid) 10.103 Terminals accept rigid and flexible conductors (table 101), unless otherwise specified (see 8.1) P Smallest diameter (mm); largest diameter (mm)....: 0,25 mm²/ 0,51 mm/ rigid 0,25 mm²/ 0,61 mm/ flexible 0,75 mm² /1,00 mm/ rigid 0,75 mm² /1,30 mm/ flexible During the test: terminals show no damage 10.104 Terminals clamp the conductor without undue damage: 10.104.1 Connection/disconnection 5 times: smallest 0,25 mm²/ 0,51 mm/ rigid diameter (mm).....................................................: 0,25 mm²/ 0,61 mm/ flexible P Connection/disconnection 5 times: largest 0,75 mm² /1,00 mm/ rigid diameter (mm).....................................................: 0,75 mm² /1,30 mm/ flexible After the test, terminal not damaged 10.104.2 Rated cross-sectional areas (mm²) .......................: 0,75 mm² . Type....................................................................: rigid and flexible After the test, no wire of conductor escaped outside the terminal 10.105 P P Smallest cross-sectional area (mm²); height H 0,25 mm² rigid / 260 mm / (mm); mass (kg) ..................................................: 0,2 kg Largest cross-sectional area (mm²); height H 0,75 mm² rigid / 260 mm / (mm); mass (kg) ..................................................: 0,4 kg during the test: the conductor does not slip out, no break near clamping unit and no damage 10.106 Pull test: - min. cross-sectional area (mm²); pull (N).............: 0,25 mm² rigid / flexible 10 N TRF No. IEC 60947_7_1A P Page 28 of 38 Clause Requirement Test Report No. 2184109.50 Result - Remark Verdict - max. cross-sectional area (mm²); pull (N)............: 0,75 mm² rigid / flexible 30 N - during the test the conductor does not come out P 11 CONSTRUCTION 11.101 Contact pressure not transmitted via insulating material, unless there is sufficient resiliency 11.102 Insertion and disconnection, in accordance with manufacturer's instructions P Openings clearly distinguishable P 11.103 P Terminals so constructed that: - each conductor is clamped individually P - conductors can be connected or disconnected at same time or separately P Possible to clamp maximum number of conductors P 11.104 Inadequate insertion of conductor avoided P 11.2 Clamping units clamp conductors reliably and between metal surfaces P 11.3 Connecting devices: insulation of conductors not in contact with live parts of different polarity P 11.4 Insulating lining: adequate mechanical strength and secured in a reliable manner P 11.5 Current-carrying parts: adequate mechanical strength, electrical conductivity and resistance to corrosion; type of metal........................................: P Current-carrying parts not made with electroplated coating if subjected to mechanical wear P 11.6 Terminals: possible to connect number of conductors as specified by the manufacturer: - number of conductors ........................................: 1 - rigid, cross-sectional area (mm²) ........................: 0,25 mm² -0,75 mm² - flexible, cross-sectional area (mm²) ....................: 0,25 mm² -0,75 mm² 11.7 Fixing means of bases do not serve any other purpose 12 RESISTANCE TO AGEING, TO HUMIDITY CONDITIONS, TO INGRESS OF SOLID OBJECTS AND TO HARMFUL INGRESS OF WATER TRF No. IEC 60947_7_1A P Page 29 of 38 Report No. 2184109.50 Clause Requirement Test 12.1 Connecting devices resistant to ageing; after the test (168 h): no cracks visible, not sticky or greasy, no damage; test temperature (C) ........................: 12.2 After humidity test (91-95%): no damage; test 48 h duration (168 h for connecting devices > IPx2, 48 h for all other)..................................................: P 12.3 IP test (IEC 60529) ..............................................: IPx N After the test, electric strength test as 13.4, and by IPx inspection N no appreciable entry of water N Result - Remark 70 C 13 INSULATION RESISTANCE AND ELECTRIC STRENGTH 13.3 Clamping unit connected with: smallest cross-sectional area (mm²); largest cross-sectional area (mm²) ..........................................................: T + 30 °C = Verdict P Insulation resistance (500 V d.c. for 1 min): 1) between all clamping units connected together and the body > 5 M ...........................................: N 2) between each clamping unit and all others connected to the body > 5 M..............................: N 3) between metal foil and the body > 5 M ...........: N 3a) if necessary, between live parts and metal covers and enclosures > 5 M .............................: N 3b) if necessary, between live parts and surface on which the base is mounted > 5 M.......................: 13.4 Electric strength (a.c. for 1 min): no flashover or breakdown: 1) test voltage (V)...............................................: N 2) test voltage (V)...............................................: N 3) test voltage (V)...............................................: N 3a) test voltage (V) ..............................................: N 3b) test voltage (V) ..............................................: N 14 MECHANICAL STRENGTH 14.101 the test conductor, properly inserted into a clamping unit of the connection devices shall be allowed to be bent (deflected) in all 12 directions each of them differing from the adjacent directions by 30° ± 5° Deflection test (principle of test apparatus shown in figure 103a): a 10 th of the test current (A) .................................: 0,4 A TRF No. IEC 60947_7_1A Page 30 of 38 Clause Requirement Test Report No. 2184109.50 Result - Remark Verdict smallest cross-sectional area (mm2) 10.103 .........: 0,25 mm² Force (N) (table 104) ...........................................: 0,09 N Distance (mm) (table 104) ………………………….: 100 mm 1 2 3 st 0,51 0,59 0,65 P nd 0,56 0,58 0,66 P rd 0,57 0,56 0,64 P th 0,61 0,59 0,63 P th 0,65 0,57 0,65 P th 0,66 0,56 0,64 P th 0,64 0,57 0,68 P th - voltage drop measured (mV) (8 deflection) .......: 0,67 0,60 0,71 P - voltage drop measured (mV) (9th deflection) .......: - screwless terminal number.................................: - voltage drop measured (mV) (1 deflection) .......: - voltage drop measured (mV) (2 deflection) ......: - voltage drop measured (mV) (3 deflection) .......: - voltage drop measured (mV) (4 deflection) .......: - voltage drop measured (mV) (5 deflection) .......: - voltage drop measured (mV) (6 deflection) .......: - voltage drop measured (mV) (7 deflection) .......: 0,68 0,58 0,70 P th 0,65 0,57 0,67 P th - voltage drop measured (mV) (11 deflection) .....: 0,62 0,56 0,68 P - voltage drop measured (mV) (12th deflection) .....: 0,68 0,61 0,71 P - voltage drop measured (mV) (10 deflection) .....: - requirement: 2,5 mV P th a 10 of the test current (A) .................................: 0,9 A P 2 Largest cross-sectional area (mm ) 10.103 ..........: 0,75 mm² P force (N) (table 104) ............................................: 0,16 N Distance (mm) (table 104) ………………………….: 100 mm 1 2 3 st 0,71 0,84 0,89 P nd 0,76 0,84 0,88 P rd - voltage drop measured (mV) (3 deflection) .......: 0,78 0,86 0,84 P - voltage drop measured (mV) (4th deflection) .......: - screwless terminal number.................................: - voltage drop measured (mV) (1 deflection) .......: - voltage drop measured (mV) (2 deflection) ......: 0,79 0,85 0,86 P th 0,77 0,84 0,84 P th 0,74 0,85 0,82 P th 0,76 0,86 0,81 P th 0,78 0,84 0,81 P th - voltage drop measured (mV) (5 deflection) .......: - voltage drop measured (mV) (6 deflection) .......: - voltage drop measured (mV) (7 deflection) .......: - voltage drop measured (mV) (8 deflection) .......: 0,79 0,81 0,84 P th 0,79 0,83 0,83 P th 0,78 0,81 0,82 P th 0,77 0,79 0,80 P - voltage drop measured (mV) (9 deflection) .......: - voltage drop measured (mV) (10 deflection) .....: - voltage drop measured (mV) (11 deflection) .....: - voltage drop measured (mV) (12 deflection) .....: TRF No. IEC 60947_7_1A Page 31 of 38 Clause Requirement Test Report No. 2184109.50 Result - Remark - requirement: 2,5 mV Verdict P 14.2 Tumbling barrel (for < 50 g): 50 falls; after the test no damage 14.3 Impact test (for > 50 g): 10 blows: N - height of fall: 7,5 cm N - height of fall: 10 cm N - height of fall: 20 cm N - height of fall: 25 cm N After the test, no damage and live parts shall not become accessible N 15 0,47 gr P TEMPERATURE RISE Terminal..............................................................: T marking (C) .....................................................: single Yes multiway (C): P N Largest cross-sectional area (mm²) ......................: 0,75 mm² Conductors..........................................................: rigid Rated connecting capacity (mm²) .........................: 0,75 mm² rigid and flexible Test current (A)....................................................: 9 A Temperature rise does not exceed 45 K (1) ..........: 34,0 K 15.101 P Temperature rise does not exceed 45 K (2) ..........: 34,6 K P Temperature rise does not exceed 45 K (3) ..........: 32,6 K P Universal, rigid conductors - 6 samples P Universal, flexible conductors - 6 samples N Non-universal, rigid solid conductors - 6 samples N TRF No. IEC 60947_7_1A Page 32 of 38 Clause Requirement Test Report No. 2184109.50 Result - Remark Verdict Non-universal, rigid stranded conductors 6 samples N Non-universal, flexible conductors - 6 samples N Temperature (°C).................................................: 40 °C 80°C Smallest cross-sectional area (mm ) ...................: 0,25 mm² Current (A) ..........................................................: 4 A Voltage drop after 192 cycles: - requirement: 22,5 mV or 1,5 times 24th cycle value...................................................................: - solid conductors.................................................: 1 – 8,84 mV 2 – 8,95 mV 3 – 8,54 mV P - stranded conductors ..........................................: 1 23- N mV mV mV - flexible conductors.............................................: 1 – 10,33 mV 2 – 8,87 mV 3 – 9,17 mV P Largest cross-sectional area (mm²) ......................: 0,75 mm² Current (A) ..........................................................: 9 A Voltage drop after 192 cycles: - requirement: 22,5 mV or 1,5 times 24th cycle value...................................................................: - solid conductors.................................................: 1 – 18,78 mV 2 – 19,26 mV 3 – 17,85 mV - stranded conductors ..........................................: 1 23- mV mV mV - flexible conductors.............................................: 1 – 18,67 mV 2 – 18,30 mV 3 – 20,38 mV TRF No. IEC 60947_7_1A P N P Page 33 of 38 Clause Requirement Test 16 RESISTANCE TO HEAT 16.2 Heating cabinet: no damage, after the test, markings still legible; test temperature (C) 16.3 Ball-pressure test (125 C) for parts necessary to retain current-carrying parts in position Ball-pressure test for parts not necessary to retain current-carrying parts in position; test temperature (C) .....................................................................: Report No. 2184109.50 Result - Remark 85 C T + 45 C = P P 70 C 40 +T Diameter of impression not exceeding 2 mm.........: 0,98 mm 17 Verdict N P CREEPAGE DISTANCES, CLEARANCES AND DISTANCES THROUGH SEALING COMPOUND Creepage distances (mm) and clearances (mm) between live parts of different polarity ...................: idem, requirement (mm).......................................: N Creepage distances (mm) and clearances (mm) between live parts and metal covers and enclosures...........................................................: idem, requirement (mm).......................................: Creepage distances (mm) and clearances (mm) between live parts and surface on which the base is mounted ..........................................................: TRF No. IEC 60947_7_1A N Page 34 of 38 Clause Requirement Test Report No. 2184109.50 Result - Remark Verdict ANNEX B IEC 60598-1: 2008 screwless terminals (part of the luminaire) 15 SCREWLESS TERMINALS 15.2 Type of terminal ...................................................: Screwless Rated current (A) .................................................: 9 A 15.3.1 Material 15.3.2 Terminals and connections shall clamp the conductor with sufficient pressure and without undue damage Terminals so designed that, when the conductor has been adequately inserted into the terminal, further insertion of its end is prevented by a stop. 15.3.3 P P N/A 15.3.4 Unprepared conductors 15.3.5 Electrical conductivity is not transmitted through insulating material P 15.3.6 Clear connection method P 15.3.7 Clamping independently P 15.3.8 Terminals shall be suitably fixed to the equipment P 15.3.10 Conductor size Type of conductor 15.5.1 15.5.1.1 Terminals and connections shall have adequate mechanical strength. Compliance is checked by the tests of 15.5.1.1 and 15.5.1.2. Pull test spring-type terminals (4 N, 4 terminals) Smallest cross-sectional area (mm²)……………….. 0,25 mm², 5 times inserted and removed, two terminals P 0,75 mm², 5 times inserted and removed, two terminals P Largest cross-sectional area (mm²)…………………. 15.5.1.1.2 P N/A Pull test pin or tab terminals (4 N, 4 samples) Insertion force not exceeding 50 N N/A 15.5.2 Permanent connections: pull-off test (20 N) 15.6 Electrical tests 15.6.1.3 9 A for 0,75 mm² solid Voltage drop (mV) after 1 h with test current (A) (5 terminals).........................................................: 4 A for 0,2 mm² solid Voltage drop shall not exceed 15 mV 15.6.2 Heating test ( 50 cycles ) TRF No. IEC 60947_7_1A See table 1 P P Page 35 of 38 Clause 15.6.2 (15.7) (15.8.1) (15.9) Requirement Test Report No. 2184109.50 Result - Remark Verdict Number of cycles .................................................: 50 Voltage drop (mV) after 10th and 25th cycles with 4 A, 0,2 mm² solid test current (A) (4 samples) ..................................: Voltage drop shall not exceed more than 50 % of See table 2 the voltage drop measurements on the same terminal tested under 15.6.1, or if the increase in voltage drop is less than 2 mV, the terminals comply with the requirement. In no case the voltage drop shall exceeds 22,5 mV P P P Heating test ( 100 cycles ) Number of cycles .................................................: 100 P Voltage drop (mV) after 50th and 100th cycles with 9 A, 0,75 mm² solid test current (A) (4 samples) ..................................: Voltage drop shall not exceed more than 50 % of See table 2 the voltage drop measurements on the same terminal tested under 15.6.1, or if the increase in voltage drop is less than 2 mV, the terminals comply with the requirement. P In no case the voltage drop shall exceeds 22,5 mV P P Terminals external wiring N/A Terminal size and rating N/A Pull test spring-type terminals or weded connections (4 samples); pull (N) ........................: N/A Pull test pin or tab terminals (4 samples); pull (N) ................................................................: N/A Contact resistance test N/A Voltage drop (mV) after 1 h N/A TRF No. IEC 60947_7_1A Page 36 of 38 Report No. 2184109.50 Table 1 Voltage drop after 1 hour Smallest cross-sectional area (mm²) 0,25 mm² Test current (A) 4A terminal voltage drop (mV) 1 2 3 4 5 7,48 4,77 6,56 10,78 4,63 Largest cross-sectional area (mm²) 0,75 mm² Test current (A) 9A terminal voltage drop (mV) 1 2 3 4 5 7,13 9,03 7,80 7,06 7,77 Table 2 Heating test Smallest cross-sectional area (mm²) 0,25 mm² Test current (A) 4A terminal 1 2 3 4 5 th 7,16 4,71 6,38 9,96 4,54 th 7,31 4,68 6,41 10,26 4,7 1 2 3 4 5 6,84 9,88 9,11 5,58 8,98 6,89 9,9 9,12 5,57 8,93 voltage drop (mV) after 10 cycle voltage drop (mV) after 25 cycle Largest cross-sectional area (mm²) 0,75 mm² Test current (A) 9A terminal th voltage drop (mV) after 50 cycle th voltage drop (mV) after 100 cycle TRF No. IEC 60947_7_1A Page 37 of 38 Report No. 2184109.50 ANNEX C: photos and product information The in this test report mentioned types may also been used in combination with the connecting links 2060-901 through 2060-906 TRF No. IEC 60947_7_1A Page 38 of 38 Report No. 2184109.50 Product data - type 2060-401, 2060-401/998-404, 2060-421, 2060-421/998-404, 2060-451, 2060-451/998-404, 2060-471 and 2060-471/998-404 rated voltage : 400 V pollution degree 3 630 V pollution degree 2 1000 V pollution degree 2 rated impulse withstand voltage : 2,5 kV rated current : 9A rated connecting capacity : 0,75 mm² rigid and flexible connectable conductors : 0,25 mm² - 0,75 mm² rigid and flexible description : connection device with 1 screwless terminal per pole, for SM D mounting technology, 1-pole Product data - type 2060-402, 2060-402/998-404, 2060-422, 2060-422/998-404, 2060-452, 2060-452/998-404, 2060-472 and 2060-472/998-404 rated voltage : 63 V pollution degree 3 160 V pollution degree 2 320 V pollution degree 2 rated impulse withstand voltage : 2,5 kV rated current : 9A rated connecting capacity : 0,75 mm² rigid and flexible connectable conductors : 0,25 mm² - 0,75 mm² rigid and flexible description : connection device with 1 screwless terminal per pole, for SM D mounting technology, 2-poles Product data - type 2060-403, 2060-403/998-404, 2060-423, 2060-423/998-404, 2060-453, 2060-453/998-404, 2060-473 and 2060-473/998-404 rated voltage : 63 V pollution degree 3 160 V pollution degree 2 : 320 v pollution degree 2 rated impulse withstand voltage 2,5 kV rated current : 9A rated connecting capacity : 0,75 mm² rigid and flexible connectable conductors : 0,25 mm² - 0,75 mm² rigid and flexible description : connection device with 1 screwless terminal per pole, for SM D mounting technology, 3-poles Product data - type 2060-802, 2060-802/998-404, 2060-822, 2060-822/998-404, 2060-852, 2060-852/998-404, 2060-872 and 2060-872/998-404 rated voltage : 400 V pollution degree 3 630 V pollution degree 2 1000 V pollution degree 2 rated impulse withstand voltage : 6 kV rated current : 9A rated connecting capacity : 0,75 mm² rigid and flexible connectable conductors : 0,25 mm² - 0,75 mm² rigid and flexible description : connection device with 1 screwless terminal per pole,for SMD mounting technology, 2-poles These units are certified as components, when used in equipment the clearance and creepage distances must comply with the applicable standard for the combination. TRF No. IEC 60947_7_1A