USER MANUAL Longo programmable controller LPC-2.MC8

Transcription

USER MANUAL Longo programmable controller LPC-2.MC8
USER MANUAL
Longo programmable
controller
LPC-2.MC8
Version 6
SMARTEH d.o.o. / Poljubinj 114 / 5220 Tolmin / Slovenia / Tel.: +386(0) 388 44 00 / e-mail: [email protected] / www.smarteh.si
Longo programmable controller LPC-2.MC8
Written by SMARTEH d.o.o.
Copyright © 2014, SMARTEH d.o.o.
User Manual
Document Version: 006
February 1 , 2014
i
Longo programmable controller LPC-2.MC8
STANDARDS AND PROVISIONS: Standards, recommendations,
regulations and provisions of the country in which the devices
will operate, must be considered while planning and setting up
electrical devices. Work on 230 VAC network is allowed for
authorized personnel only.
DANGER WARNINGS: Devices or modules must be protected
from moisture, dirt and damage during transport, storing and
operation.
WARRANTY CONDITIONS: For all modules LONGO LPC-2 – if no
modifications are performed upon and are correctly connected
by authorized personnel – in consideration of maximum
allowed connecting power, we offer warranty for 24 months
from date of sale to end buyer. In case of claims within
warranty time, which are based on material malfunctions the
producer offers free replacement. The method of return of
malfunctioned module, together with description, can be
arranged with our authorized representative. Warranty does
not include damage due to transport or because of
unconsidered corresponding regulations of the country, where
the module is installed.
This device must be connected properly by the provided
connection scheme in this manual. Misconnections may result
in device damage, fire or personal injury.
Hazardous voltage in the device can cause electric shock and
may result in personal injury or death.
NEVER SERVICE THIS PRODUCT YOURSELF!
This device must not be installed in the systems critical for life
(e.g. medical devices, aircrafts, etc.).
If the device is used in a manner not specified by the
manufacturer, the degree of protection provided by the
equipment may be impaired.
Waste electrical and electronic equipment (WEEE) must be
collected separately!
LONGO LPC-2 complies to the following standards:
• EMC:EN 61000-6-2 (EN 50082), EN 61000-6-4 (EN 50081)
• LVD: IEC 61131-2
• Vibrations and climatic-mechanical: EN 60068-2-6, EN
60068-2-27, EN 60068-2-29
Smarteh d.o.o. operates a policy of continuous development.
Therefore we reserve the right to make changes and
improvements to any of the products described in this manual
without any prior notice.
MANUFACTURER:
SMARTEH d.o.o.
Poljubinj 114
5220 Tolmin
Slovenia
ii
Longo programmable controller LPC-2.MC8
Longo programmable controller LPC-2.MC8
1 DESCRIPTION............................................................................................1
2 FEATURES..................................................................................................2
3 OPERATION................................................................................................3
4 INSTALLATION...........................................................................................5
4.1 Connection scheme..........................................................................5
4.2 Mounting instructions.......................................................................7
4.3 Module labeling................................................................................8
5 TECHNICAL SPECIFICATIONS.....................................................................9
6 CHANGES................................................................................................10
7 NOTES.....................................................................................................10
iii
Longo programmable controller LPC-2.MC8
1 DESCRIPTION
LPC-2.MC8 is an open programmable PLC controller.
On its sides there are two extensions buses where various Input, output, special, and
communication modules can be attached. It has integrated USB programming port, port
for connection of intelligent peripheral modules and Ethernet Modbus port for network
connectivity.
Controller is powered from mains supply.
Controller is accompanied with three applications:
LPC Composer is a tool where various modules can be put together to a configuration.
Composer takes care for the proper modules position and number off additional modules
included to configuration.
There are wizards which enable users to build proper configuration based on number and
type of the signals needed in configuration. Another approach is to select needed number
of adequate models and then wizards puts them together with as many controller
modules as needed.
When configuration is finished LPC Manager is further used to write the PLC application.
This is where most of the work will be done. LPC Manager can only be started from within
LPC Composer.
NOTE: For proper system configuration and data allocation please refer to LPC Composer
software help menu.
1
Longo programmable controller LPC-2.MC8
2 FEATURES
Figure 1: LPC-2.MC8 module
Table 1: Technical data
Ethernet connectivity with Modbus TCP slave (server) functionality,
USB port for Debugging, Application and Default parameters transfer,
CAN ports,
RS485 connectivity for intelligent peripheral modules (thermostat, RFID, IR, operator
terminal...),
Integrated RTC with Super Cap backup,
32 kB non-volatile memory,
4 kb Flash memory available for parameter storage,
Mains power supplied.
2
Longo programmable controller LPC-2.MC8
3 OPERATION
There are several logical units attached with this module. They can be accessed from the
LPC Composer application. Some units are enabled by default, others can be enabled
through LPC composer. Unit is enabled when any of its variables is used.
PLC has 32 kB of non-volatile memory, which is available to any variable used inside
application simply by setting the variable Option to Retentive.
PLC also provides 4kB of ROM (flash) memory area to the user who would like to use some
initialization data or some fixed parameters. This area can be accessed from application
only for reading. Setting the values of variables in Flash can be issued with another
application, FlashUploader.
In Flash memory area there are some preloaded data stored:
MAC: is unique for every unit produced. This value can be also found on the label
attached on the housing of the unit.
IP: default value is 192.168.19.222
MASK: default value is 255.255.255.0
Gateway, Primary DNS, Secondary DNS: default 0.0.0.0
Flash memory unit
This unit enables only reading from its variables. Setting the variables is issued with one
of LPC Composer plugins, Flash Uploader.
Flash unit provides reading of a portion of a flash memory inside MC8 module. Flash
memory is non-volatile, therefor keeps data for ever.
Usually this area is used for setting some data to the default value even before
installation of the unit to its position. After, when PLC is commissioned, the data are
already present and there is no need for further setting. This keeps its data In this area
some startup parameters can be written
RTC unit
For RTC back-up and for Retain variables there is SuperCapacitor instead of battery
integrated inside PLC. This way replacement of the discharged battery is avoided.
The Retention time is minimum 30 days from the power down.
RTC time provides date and time information. Along, alarming function is also supported.
Modbus slave unit
ModbusTCP slave has 512 addresses in each memory section.
Coils:
Discrete Inputs:
Input Register:
Holding Registers:
00000
10000
30000
40000
to
to
to
to
00511
10511
30511
40511
Supports up to 3 connections to the slave unit.
Scan rate is 500ms or greater.
3
Longo programmable controller LPC-2.MC8
CANopen unit
CANopen unit consists of Master and Slave communication ports. They are independent,
thus can be connected to two different CAN networks at the same time.
The ports can operate at baud rates 50 kbps, 125 kbps or 250 kbps.
It follows the internationally standardized (EN 50325-4) CAN-based higher-layer protocol
for embedded control systems. Advised rules and concepts by this standard must be
followed to fulfill the conditions and so achieving normal operation and results.
The structure of the network as cable type and lengths, baud rates, number of the nodes
and termination must be taken into account within the recommendations and
requirements, when designing the network.
The bus network can consist of one Master and many Slave nodes by the standard, but it
is advised that with increased number of nodes, the Master node fastest interval is
extended (recommended: 8 Slave nodes and Master node, Master Cycle time should be
set to 100 ms or higher).
It is recommended to power-up all the nodes on the same network at the same time, to
reinitialize the communication properly.
Additional operational information
After the installation of the PLC it must be at least 20 minute enabled power supply,
before the internal battery is charged and the retain memory is ready to save variables
without loosing them switching power supply off.
RUN / STOP Switch
Run mode: Status (RUN) LED on indicate that the PLC program is up and user program is
running.
Stop mode: When the switch is turn to STOP state, the status (RUN) LED is Off. The
application switch to the bootloader, this fact allow users to program LPC-2.MC8.
When the user is done programing the PLC via USB the switch must be turned ON and the
MC8 starts the application.
4
Longo programmable controller LPC-2.MC8
4 INSTALLATION
4.1 Connection scheme
Figure 2: Connection scheme
Table 2: Power supply
PS.1(
)
PS.2 (N)
PS.3 (L)
Functional earthing
provides better EMI/EMC
Power supply
100..250 VAC, 50/60 Hz
5
Longo programmable controller LPC-2.MC8
Table 3: CAN
CAN1.4
CAN Low
CAN1.5
CAN High
CAN.6
Reference point
CAN2.7
CAN Low
CAN2.8
CAN High
0..5 V
0V
0..5 V
Table 4: Switches
S1
Operation
mode
RUN: PLC normal operational mode
STOP: application not running, connected modules outputs in
their off state
RST: when moved from STOP to RUN mode, PLC is reset and
application starts from its beginning.
S2
CAN bus
termination
ON: corresponding channel is internally terminated with 120
ohm
OFF: no internal termination present
Table 5: LED
LED1
Application running
On: application is running
Of: application is stopped or PLC in boot mode
LED2
USB connectivity
On: USB connection established
Of: no USB connection
LED3
Power
On: module is powered ON
Of: module has no power supply
6
Longo programmable controller LPC-2.MC8
4.2 Mounting instructions
53
•
36
95
90
Figure 3: Housing dimensions
60
Dimensions in millimeters.
EXTERNAL SWITCH OR CIRCUIT-BREAKER AND EXTERNAL OVERCURRENT
PROTECTION: The unit is allowed to be connected to installation with
over current protection that has nominal value of 16 A or less.
RECOMMENDATION ON SWITCH OR CIRCUIT-BREAKER PROTECTION:
There should be two poles main switch in the installation in order to
switch off the unit. The switch should meet the requirements of standard
IEC60947 and have a nominal value at least 6 A. The switch or
circuit-breaker should be within easy reach of the operator. It should be
marked as the disconnecting device for the equipment.
All connections, module attachments and assembling must be done
while module is not connected to the main power supply.
Wires connected to the module must have cross sectional area at least
0.75 mm2. Minimum temperature rating of wire insulation must be 85°C
1. Switch OFF main power supply.
2. Mount module to the provided place inside an electrical panel (DIN EN50022-35
rail mounting).
3. Mount other IO modules (if required). Mount each module to the DIN rail first, then
attach modules together through K1, K2 connectors.
4. Connect needed input, output and communication wires.
5. Switch ON main power supply.
Dismount in reverse order. For mounting/dismounting modules to/from DIN rail a free
space of at least one module must be left on the DIN rail.
7
Longo programmable controller LPC-2.MC8
4.3 Module labeling
Figure 5: Labels on housing
Label 1 (sample):
Label 2 (sample):
LPC-2.MC8
P/N:225MC813002001
D/C: 31/10
S/N: MC8-S9-1000000190
Label 1 descriptions:
1. LPC-2.MC8 is the full product name.
2. P/N:225MC8040001001 is the part number.
•
225 – general code for product family,
•
MC8 – short product name,
•
04001 – sequence code,
•
•
04 – year of code opening
•
001 – derivation code
001 – version code (reserved for future HW and/or SW firmware upgrades).
3. D/C:16/11 is the date code.
•
16 – week and
•
05 – year of production.
Label 2 descriptions:
1. S/N:MC8-S9-1100000190 is the serial number.
•
MC8 – short product name,
•
S9 – user code (test procedure, e.g. Smarteh person xxx),
•
1100000190 – year and current stack code,
•
11 – year (last two cyphers)
•
00000190 – current stack number; previous module would have the stack
number 00000189 and the next one 00000191.
8
Longo programmable controller LPC-2.MC8
5 TECHNICAL SPECIFICATIONS
Table 6: Technical specifications
Power supply
100..250 V AC, 50/60 Hz
Power consumption
Max. 35 W
Connection type
screw type connector for stranded wire 0.75 to 2.5
mm2
USB
B connector type, device mode,
Low speed, Full speed
RTC
capacitor backed up with retention cca. 30 days.
Dimensions (L x W x H)
90 x 53 x 60 mm
Weight
180 g
Ambient temperature
0 to 50°C
Ambient humidity
max. 95 %, no condensation
Maximum altitude
2000 m
Mounting position
vertical
Transport and storage
temperature
-20 to 60 °C
Pollution degree
2
Over-voltage category
II
Electrical equipment
Class II (double insulation)
Protection class
IP 30
9
Longo programmable controller LPC-2.MC8
6 CHANGES
The following table describes all the changes to the document.
Date
V.
Description
1.02.2014
006
CANOpen Unit section added.
23.9.2011
001
The initial version, issued as LPC-2.MC8 UserManual.
7 NOTES