EasyIO FG Series FAQ EasyIO FG Series FAQ v1.0 1

Transcription

EasyIO FG Series FAQ EasyIO FG Series FAQ v1.0 1
EasyIO FG Series FAQ v1.0
EasyIO FG Series FAQ
1
EasyIO FG Series FAQ v1.0
Document Change Log
16th Dec 2014
Document created.
2
EasyIO FG Series FAQ v1.0
Disclaimer
EasyIO 30P is a product by EasyIO Holdings Pte Ltd
The EasyIO 30P was built on the Sedona Framework ®.
EasyIO FG-32 is a product by EasyIO Holdings Pte Ltd
The EasyIO FG-32 was built on the Sedona Framework ®.
Sedona Framework is a trademark of Tridium, Inc.
CPT Tool is by Online Tools Inc.
3
EasyIO FG Series FAQ v1.0
Table of Contents
Introduction ............................................................................................................................................ 5
Frequently Asked Questions ................................................................................................................... 6
1)
Default IP address. ...................................................................................................................... 6
2)
Commonly used login credentials for EasyIO FG Series.............................................................. 6
3)
Default IP Ports for EasyIO FG Series .......................................................................................... 7
4)
How do I upgrade the firmware for EasyIO FG Series controllers? ............................................ 7
5)
Restore to factory default. .......................................................................................................... 8
6)
Micro SD Card ............................................................................................................................. 9
7)
EasyIO FG Series Modbus Master Driver limitation .................................................................. 10
8)
EasyIO FG Series Modbus Slave Driver limitation ..................................................................... 10
9)
EasyIO FG Bacnet Server Limitation (Bacnet IP only) ............................................................... 11
10)
EasyIO FG Series History storage .......................................................................................... 11
Technical Support ................................................................................................................................. 12
4
EasyIO FG Series FAQ v1.0
Introduction
This document is a quick reference to all most commonly asked questions.
5
EasyIO FG Series FAQ v1.0
Frequently Asked Questions
1) Default IP address.
Default IP address
Default Subnet
Default Gateway
: 192.168.10.11
: 255.255.255.0
: 192.168.10.1
The above IP address is the IP address if a restore to factory setting carried out at the controller.
2) Commonly used login credentials for EasyIO FG Series
Function
Username
Password
Remarks
No
password
Sedona (sox)
admin
Login to the Sedona sox protocol
(Leave it
blank)
Controller Web
scripts (via file
transfer client , FTP)
webuser
123456
Login to the webuser folder that contains web
server default files system.
CPT graphics
deployment
webuser
123456
Credentials for CPT graphics deployment
CPT graphics login
via web browser
admin
hellocpt
Credentials for CPT web server
Micro SD card (if a
micro SD card is
insert )
sdcard
123456
Login to the SD Card file system where it
contain the CPT deployed files.
SQL Lite browser
administrative page
Login to the SQL Lite Administrative Web Page.
-
123456
Link :
http://192.168.10.11/sdcard/phpliteadmin.php
6
EasyIO FG Series FAQ v1.0
3) Default IP Ports for EasyIO FG Series
Protocol
Port
Type
Sedona (sox)
1876
UDP
21
TCP
Graphics Deploy , File Transfer via FTP
Client
Modbus TCP
502
TCP
Modbus TCP Port
BACnet IP
47808
UDP
BACnet IP Port
Web Server
80
TCP
Build In Web Server port
Tcom
5021
UDP
Tcom Niagara Driver port
File Transfer Client (FTP)
Remarks
Sox connection
4) How do I upgrade the firmware for EasyIO FG Series controllers?
There are two types of flashing files which are explained below. Both types will erase the Sedona
apps in the controller, therefore please ensure a controller back up is performed before the
flashing procedure otherwise the controller App will be lost.
Type
Factory Default
Functions
Firmware upgrade
Restore back to factory default
Maintain IP address
Firmware upgrade
Remain the last IP address
Remarks
Sedona apps will be erase
IP address will restore back to default IP
address
IP address : 192.168.10.11
Sedona apps will be erase
IP address will remain the last valid IP
address set.
Get the required files from EasyIO technical support at [email protected].
Depending on version, quantity of files may differ. See below.
V2.1.2.0.01 and below has 2 files
V2.1.2.0.02 and above has only 1 file
7
EasyIO FG Series FAQ v1.0
The firmware file which is fg320.tar.gz needs to be copied into the fg320 folder using a file transfer
client or with a memory card reader plug into the computer.
You can copy the files over into the SD card by dragging the file into the “fg320” folder if a file
transfer client program is used.
**Note**
You might need 2 files or 1 file depending to the current firmware version of the controller.
Important: Please check the file size and compare with the source file. Make sure the file size is
correct.
**3 Important Tech Tips if using file transfer client program**
1. Files need to be transfer/copied into the “fg320” folder.
2. Files cannot be in the root directory of the SD card, they need to be copied into “fg320”
folder.
3. If “fg320” folder is not seen, refer to Step 3 above.
Login to the Sedona controller via Sedona workbench or the CPT tool and reboot the device.
**Tech Tip - The watchdog jumper must be in the “ON” position for the controller to automatically
reboot. By default the controller is shipped with the watchdog jumper in the ON position.
For detail explanation, please refer to EasyIO Basic 12 - EasyIO FG-32 Firmware Flashing.pdf.
5) Restore to factory default.
The new firmware release dated 1st August 2013 comes with “Restore Factory Settings”.
This function is done with just the by pressing the “Service” button while the controller is
booting up.
A restore to factory settings will do the following;
1. Restore the IP address to the default which is 192.168.10.11
2. Clear the Sedona application in the Sedona VM back to default (default app is an empty app)
3. A default Sedona apps default login is admin, <no password>.
8
EasyIO FG Series FAQ v1.0
Below is a simple explanation. For detail explanation, please refer to EasyIO Basic 07 - EasyIO FG32
User Reference.pdf
Step 1
Make sure you backup the Sedona apps if you have connection to the EasyIO FG32.
Step 2
Cycle power and within 5 seconds press and HOLD down the service button until the Error LED starts
to flash approximately 2 Hz.
This process will take approximately 15 seconds before the error Led start to blink.
Step 3
Once the Red LED flashes, a momentary press of the service button will restore back the FG Series
controller back to factory default state.
6) Micro SD Card
Each EasyIO FG Series comes with a micro SD memory card slot.
Specifications
Brand tested recommended
Capacity tested
Class
Remark
Transend, Kingston
2GB, 4GB, 8GB, 16GB
Class 4
Class 10
Please note that the Micro SD card in the EasyIO FG Series is optional and the controller does not
complete with the SD Micro Card as standard. The SD Micro card can be purchased separately
that have the following specifications.
9
EasyIO FG Series FAQ v1.0
Make sure the controller is power off before inserting the micro SD Card.
Above is a simple explanation. For detail explanation, please refer to EasyIO General 04 - FG32
Installation.pdf
7) EasyIO FG Series Modbus Master Driver limitation
Modbus RTU Master
Max. No. of MODBUS Serial Networks (per FG device)
Max. No. of MODBUS Serial Devices per Network
Max. No. of Points per MODBUS Serial Device
1
31
32
Modbus TCP Master
Max. No. of MODBUS TCP Networks (per FG device)
Max. No. of MODBUS TCP Devices per Network
Max. No. of Points per MODBUS TCP Device
1
31
32
Modbus TCP Gateway
Max. No. of TCP Gateway Networks (per FG device)
Max. No. of MODBUS Gateway Devices allowed
Max. No. of Points per MODBUS Gateway Device
1
31
32
For detail explanation, please refer to EasyIO Adv 12 - FG Series Modbus Master.pdf
8) EasyIO FG Series Modbus Slave Driver limitation
Modbus RTU Slave/ Modbus TCP Slave
Max Network allowed
Max Discrete Point allowed
Max Coil Output allowed
Max Input Register allowed
1 (of both drivers)
200 register address (total)
200 register address(total)
200 register address, depending to data type.
Max Holding Register allowed
Integer data type occupy 1 register address
Float data type occupy 2 register address
Long data type occupy 2 register address
200 register address, depending to data type.
Integer data type occupy 1 register address
Float data type occupy 2 registers address
Long data type occupy 2 registers address
For detail explanation, please refer to EasyIO Adv 13 - FG Series Modbus Slave.pdf
10
EasyIO FG Series FAQ v1.0
9) EasyIO FG Bacnet Server Limitation (Bacnet IP only)
Bacnet IP Server (Information is correct at the time of document)
Objects supported
Analog Value , Read Only or Read Write
Binary Value , Read Only or Read Write
Priority Array Supported
No
Writable Property
Present Value Only
Total Analog Value (AV)
32
Total Binary Value (BV)
32
For detail explanation, please refer to EasyIO Adv 14 - FG Series Bacnet Server.pdf
10) EasyIO FG Series History storage
There is no metric for calculating memory size for a history data table.
Table below display an estimation memory size used. Result is by EasyIO bench testing.
Number of Table
1
1
1
1
Number of Column
(Values)
1
10
1
32
Total records
Size on Disk
1000
1000
100,000
100,000
40 KB
132 KB
5,100 KB
27,000 KB
For detail explanation, please refer to EasyIO Adv 16 - FG Series SQL Lite.pdf
11
EasyIO FG Series FAQ v1.0
Technical Support
For technical support issues please contact technical support person as below;
Email: [email protected]
12