Lindsey # 9532 is a IEEE 386 type 200Amp 15 kV load break Elbow
Transcription
Lindsey # 9532 is a IEEE 386 type 200Amp 15 kV load break Elbow
BUSHING WELL LINDSEY #9592 LOADBREAK “T” VOLTAGE SENSOR Lindsey # 9592 is a IEEE 386 type 200 Amp 15 kV bushing load break “T” voltage sensor that provides a 1% accurate AC analog output voltage with an included 10 foot watertight connecting cable Part Number Lindsey # 9542/0111 Lindsey # 9542/0511 Output Voltage Device Impedance 0-5 Volts AC 1 Megohm 0-120 Volts AC 1 Megohm LOADBREAK BUSHING INSERT LINDSEY #9532 LOADBREAK ELBOW VOLTAGE SENSOR Lindsey # 9532 is a IEEE 386 type 200Amp 15 kV load break Elbow voltage sensor that provides a 1% accurate AC analog output voltage with an included 10 foot watertight connecting cable Part Number Lindsey # 9532/0111 Lindsey # 9532/0511 Output Voltage Device Impedance 0-5 Volts AC 1 Megohm 0-120 Volts AC 1 Megohm 760 N.Georgia Avenue Azusa, CA 91702 USA Tel. 626-969-3471 www.lindsey-usa.com Self contained 12 volt DC power source provides 5 ampere hours of continuous energy in event of loss of input power for pad mount control/communication system The Lindsey UG power supply (P/N 9251) uses a slip-core CT to generate DC energy to power customer’s control/communication system, in the mean time, it also charges a built-in 12V 5AH sealed Lead Acid battery. In the event of loss of input power, the self contained battery can provide more than 10 hours of energy for the control/communication system. The CT harvests the power from any phase of the 200A/600A underground cable system.Minimum of 30A line current is required to run the power supply. The system has a water-resistant design to avoid moisture. Features: Specifications: 12Vdc for a typical microprocessor based control/communication system 12V, 5AH telecom grade build-in battery with temperature compensation Applicable for 200A / 600A 15kV to 35kV underground systems Easy installation (split-core CT fits over the underground cable and magnet-mount to the inside wall of steel PAD mount enclosure), no maintenance or calibration required NEMA 4X fiberglass enclosure Magnetic mounting Utilizes passive Current Transformer for input power Temperature compensated charging circuit to prolong battery life Floating ground design allows mounting flexibility Long life internal sealed lead acid cell for low maintenance Wide operating temperature range DC voltage output: up to 14V, 2.5A max Build-in battery: 12V, 5 AH Dimensions in inches: With magnet mounts: 9 1/2” L x 7 5/8” W x 5” H Without magnet mounts: 9 1/2 L x 7 5/8” W x 4 5/8” H Operating temperature: -20F to 140F Power supply/CT weight: 15 lbs Shipping weight: 17 lbs. US Patent #7633262 and other Patents Pending 760 N.Georgia Avenue Azusa, CA 91702 USA Tel. 626-969-3471 www.lindsey-usa.com