Universal, retrofit and replacement VOLTAGE REGULATORS AVRs

Transcription

Universal, retrofit and replacement VOLTAGE REGULATORS AVRs
Universal, retrofit and replacement
VOLTAGE REGULATORS
AVRs
GENERATOR SPARE PARTS
PROTECTION RELAYS
INSULATION GUARDS
Contents:
- Voltage regulators
- Universal
AVRs
- Direct replacement AVRs
- Genuine
AVRs
- Options for voltage regulators
- Protections
- Parts for excitation systems
-
Voltage regulators
-Selection table
-Universal automatic EMRI voltage regulators
-
KASR10
KASR20
LX4V2
LX10.1
LX20
LX500
3TX20
ASR35-350
NOZERO35-350
LX10.1_GSR28.5
LX10.1_GSR750
EVA
SUBLX20
GSR
GLDR
LASR11DC.1
Static Exciters
Universal avr, 5 Amps
Universal avr 10 Amps,
Universal avr,
Universal avr 5-10 Amps
Universal avr 15 Amps
Universal avr volt per hertz avr
Universal avr 20 Amps
Universal avr, static exciter 35-350 Amps
Universal avr, static exciter 35-350 Amps
DC sensing AVR 28 Volt
DC sensing AVR 750 Volt
Universal avr, aux. winding supply
Derative current 8 Amps
DC generator AVR 110 / 220 VDC, 10 Amps
Battery charging AVRs 24 Volt AC/ DC
DC sensing AVR
Upon demand-specification
-
LASR11.1
3FLASR11
as long stock lasts
as long stock lasts
-
-EMRI direct replacements voltage regulators
-
CATAVR
KASR10
LX342
LX4V2
Piller400
EMRI2490
EMRI2491
AvKaick 7.4, 7.5
REG 112
REG01
VEMREG
RBC
-
Type A
Type A
SMUX
Caterpillar avr
Stamford Replacement
Stamford Replacement
AvK, EME R260,274,280,290 Ti7.5D replacement
Piller NKT generator avr
Siemens, Uljanik replacement 6GA2490
6GA2491, 6GA2492
7.4, 7.5 avr
TO1112
T01 avr
VEM, FIMAG TR4 avr
Replacment for Unelec, Alstohm LS derative
avr.
Jeumont Schneider ESCA, saturation choke
Jeumont Schneider ERTCR, reverse
Stromberg SMUX replacement
-
SF7
MAGREG
NEBB SF7 replacement
Makita, Honda replacement.
-Options for universal AVRs
-
LX_VPH
COSPHI3.2
KOMPOUNDBOOSTER
SERIES BOOSTER
POTUNIT3
TSV VOLTMATCH
Softstart and V/Hz option
Power factor controller
Compounding/Booster system incl. transformer
Booster system for serial sustained short circuit
Electronic potmeter voltage control reference
Voltage match unit ( generators, grid )
- Protection relays
-
-
LX_OVSCN
Overvoltage suicide protection unit
EX_CHECK
Over - excitation relay Excitation value alarm
IB1
Insulation guard for TN circuits
IB40
Insulation guard for TN circuits
FREQ_REL & F_MEET(N)Frequency guard relay F_MEET(N)
AKKUWACHTER
Battery voltage monitor
Thermistor relay
THERMAX
SPANMAX
Under/over-voltage relay
- Generator excitation system spare parts
-
Diodes, suppressors, rectifiers
- AVRs cross reference / replacement list
AEG
-
DKBL/LDW
SUBLX20
GR21
GR21
-
R280/290,R274
R280-290, R274
EVA
LX4V2
-
Ti7.3, Ti7.4
7PUNT3,
-
Ti7.5
TO1
TO12, TO112
REG01
REG112
Alconza
-
Alconza GR21 replacement
AVK
-
-
Analogue avr aux. windings
Digital avr for AvK/EME
canbus
7PUNT4 AvK TI 7.4 and identical
models
AvK T01 replacement
AvK TO112 replacement
-
TO1819
LX_TO18-19
VR3, VR6
CATAVR(EMRI) Universal AVR VR3,VR6
AvK TO18-19 replacement
Caterpillar
-
l
EME
-
R280/290
EVA / LX4V2
HIREX
SUBLX20
LCB,LSB
SUBLX20
FUJI
-
INDAR
-
Jeumont Schneider
-
Regulator Type A
ETCA or ESCA
REG TYPE A
Jeumont Schneider
Leroy Somer
-
15075/1100 series
RS128,129
RBC1100 AVR, SUBLX20
RBC, RBS
Unelec, Leroy Somer
SUBLX20
NEBB SF7 AVR
SF7 3TX20
NEBB SF7 Replacement
NKT
PILLER400
ANTON PILLER avr
NEBB
-
Piller
-
replacement
Siemens, Hyundai
-
Thyripart 2490 ®
EMRI2490
SIEMENS/ULJANIK/WUXI/Hyundai
TR4
SFR3000
LX10.1
SUBLX20
Reliance
-
Stamford Newage
-
-
MX321
MX341/2
SX460
LX321 (EMRI)
LX342 (EMRI)
KASR10
replacement
-
AS440
KASR20
Digital Newage MX321
Digital Newage MX342
Newage SX460
Stromberg
-
SMUX2R5
SMUX 3TX20
VEM FIMAG AEM
-
TR3
VEMREG
-Genuine AVRs
AVK
-
Cosimat N+
QPF
Regler COS
DSG, DKBN avr
R10K
derative avr
VR6
DVR
pmg avr
Power factor controller
Power factor controller
AEM
Caterpillar
-
Stamford Newage
AS440
SX460
MX341
MX342
MX321
PFC3
Leroy Somer
R438
R448
R449
R130
R129
McAlte / Spa
UVR6
SR7
Marelli
-
M25FA468
M25FA502
digital avr
SE generator avr
Stromberg SMUX 2R5
replacement
Siemens
-
M25FA600
M25FA603
6GA2490
GA2492
6GA2492
Spring 2010 available
Digital replacement version of COSIMAT N (© Cummins Generator Techn.)
Selection table universal avr’s
KASR10 KASR20 LX321 LX342 LX4V2/50 LX4V2/400 LX10.1 note ! LX20 LX500/10 LX500/20 3TX20 ASR35-­‐250 LX10.1 GSR28.5VDC LX10.1 GSR750VDC EVA SUBLX20 Output Amps 5 12.5 4 3 3 3 10 15 10 15 20 35-­‐250 10 10 4 -­‐20 Volts max. Volt 80 115-­‐260 80 150-­‐260 220 220 220 220 100 20-­‐100 100 20-­‐100 220 15-­‐260 140 15-­‐140 220 15-­‐260 140 15-­‐140 180 30-­‐400 180 230 220 15-­‐260 220 15-­‐260 100 22-­‐100 100 For other values, contact EMRI Electronics bv.
T:+31(0)318620427
T:+31(0)318620427
@:[email protected]
Supply range 120-­‐480 Sensing range Hertz Volts 1 50-­‐60 230 50-­‐60 230 DC-­‐200 230 DC-­‐200 230 DC-­‐400 230 DC-­‐400 230 DC-­‐400 230 DC-­‐400 230 DC-­‐400 230 DC-­‐400 230 50-­‐60 230 50-­‐60 230 DC-­‐400 28 DC-­‐400 750 DC-­‐400 230 50-­‐60 230 Volts 2 115 400 400 400 400 400 400 400 400 500 400 Hertz 50-­‐60 50-­‐60 50-­‐60 50-­‐60 50-­‐60 400 50-­‐60 50-­‐60 50-­‐60 50-­‐60 50-­‐60 50-­‐60 DC DC 50-­‐60 400 50-­‐60 UNIVERSAL AVRs
KASR10
The KASR10 is an electrically robust AVR with SCR technology. The KASR10 can
be applied in brushless generators upto approx. 150 kVA, where the sensing
voltage is 230 V or 115 V between phase / neutral or phase / phase. The KASR10 is
fully encapsulated rugged avr.
Specifications
Maximum field current
Maximum field voltage
Supply / Sensing input
:
:
:
Accuracy
Ambient temperature
Dimensions
:
:
:
5 A (unfused)
35% of the voltage between U and 0.
110-260 VAC (terminals U and 0), 50/60 Hz, 1phase (jumper selectable)
<1%
0
Max. 50 C
100 x 135 x 45 mm
Features
Underspeed trip with LED indicator
Self excitation circuit from 3 V residual voltage
Potentiometer input for external voltage adjustment
KASR20
The KASR20 is an electrically robust AVR with SCR technology. The KASR20 can
be applied in brushless generators where the sensing voltage is 230 V or 400 V,
enhanced P and I stability adjustments. Suitable for parallel operation. Sensing
and supply voltages are separated and isolated for various applications.
Specifications
Maximum field current
Maximum field voltage
Supply
Sensing input
Accuracy
Ambient temperature
Dimensions
Features
-
:
:
:
:
:
:
:
12.5 A (fused)
35% of the supply voltage.
150-260 VAC (terminals LH ), 50/60 Hz
1 phase 230 / 480 Volt
<1%
0
Max. 50 C
100 x 135 x 75 mm
Underspeed trip with LED indicator
Self excitation circuit from 3 V residual voltage
Potentiometer input for external voltage adjustment
Parallel operation
Isolated supply and sensing input
Option connector for additional features
LX321
The LX321 enhanced MX321 AVR (Newage). The LX321 features several special functions for a wide variety of
generator control. It is 1:1 suitable to replace the Newage MX321 and equivalent models. It has the power factor
controller PFC3 integrated.
The avr is completely digital and is equipped with special control features such as current limiting, remote full
scale voltage control or current control, in single as well as in parallel operation.
Protection options and fault contact. Equipped with Can interface and also re-programmable to meet special
customs applications.
The LX321 is completely encapsulated in PUR to improve thermal as well mechanical reliability.
LX342 (2010 available)
The LX342 is an enhanced MX341 (Newage). The LX342 features several special functions for a wide variety of
generator control. It is 1:1 suitable to replace the Newage MX341 and MX342 equivalent models.
The avr is completely digital and is equipped with special control features as well as integrated power factor
controller.
Equipped with Can interface and also re-programmable to meet special customs applications.
The LX321 is completely encapsulated in PUR to improve thermal as well mechanical reliability.
LX4V2
The LX4V2 is a replacement AVR for AvK DKB, WKB and EME DR generators and AVRs type R260/R261,
R260.3/R274, and R280/290.
The wide input and excitation output range enables application in many other generators.
The LX4V2 is an completely digital AVR with multiple selectable protections and operating modes.
A Can interface and re-programmable microprocessor enables
custom adaptation and on line value monitoring.
Specifications
Maximum field current
Maximum field voltage
Supply input
3~)
Sensing input
phase
Ambient temperature
Dimensions
:
:
:
3 A / 6 A ( 10 sec ) (fused)
75 % of the supply voltage
20 - 100 VAC 1~, ( 15 – 100 VAC
:
165 - 480 VAC max. 50/60 Hz, 3-
:
:
-20 - 50 C isolated heatsink
130 x 115 x 76 mm
0
Features
V/Hz operation or constant voltage
Isolated and separate supply and sensing voltage
Various protection, with error code LED
Self excitation circuit from 10 V residual voltage
Potentiometer input for external voltage adjustment
Temperature limiting / protection
Exciter field limitation
Parallel operation possible with optional external droopkit (sold separately)
LX10.1
The LX10.1 is a universal and very compatible AVR for brushless generators. Its unique characteristics allows it
to replace virtually any other brand of AVR. The LX10 has a wide supply voltage range which can be applied in
almost any generator, from PMG generators to simple phase supplied AVR systems or generators with auxiliary
windings etc. The use of modern high power IGBT technology makes the LX10.1 widely applicable and with
excellent performance for any kind of generator load.
Specifications
Maximum field current
Maximum field voltage
:
:
Supply input
Sensing input
:
:
Ambient temperature
Dimensions
:
:
10 A (fused)
100 % of the supply voltage or
limited by potentiometer max.
22 - 260 VAC 1- or 3- phase or DC
140 - 480 VAC 50/60 Hz (400 Hz
for LX10_XFR or 3 x 660 V
0
Max. 50 C isolated heatsink
160 x 145 x 110 mm
Features
Isolated and separate supply and sensing voltage
Underspeed trip with LED indicator
Self excitation circuit from 3 V residual voltage
Parallel operation possible with optional external droopkit (sold separately)
Connector for optional control systems
LX20
The LX20 is the increased powerfull version of the LX10.1.
Due to the higher current specifications and larger suppressor parts, the avr is applicable in larger generators or
generator with greater pole number such as 6, 8 or 10 pole generators.
Specifications
Maximum field current
Maximum field voltage
:
:
Supply input
Sensing input
Accuracy
Ambient temperature
:
:
:
:
Dimensions
:
15A (20 A fused)
100 % of the supply voltage or
limited by potentiometer max.
15 - 140 VAC 1- or 3- phase or DC
170 - 480 VAC 50/60 Hz
<1%
0
Max. 50 C isolated heatsink
case (cold plate technology)
160 x 145 x 110 mm
Features
Isolated and separate supply and sensing voltage
Underspeed trip in VpH mode as well shut down mode with
LED indicator
Self excitation circuit from 3 V residual voltage
Parallel operation possible with optional external droopkit (sold separately)
Connector for optional control systems
LX500
The LX500 is a universal and very compatible AVR for brushless generators. Its
unique characteristics allows it to replace virtually any other brand of AVR.
Due to modern high power and micro controller technology, several
operational modes can be selected. Unlike the LX10, the LX500 has a
proportional V/Hz mode from 35 Hz up to 60 Hz.
Specifications
Maximum field current
Maximum field voltage
:
:
10 A (fused)
100 % of the supply voltage or limited by
potentiometer max.
22 - 260 VAC 1- or 3- phase or DC
140 - 480 VAC 50/60 Hz, 3-phase
<1%
0
Max. 50 C isolated heatsink case (cold plate technology)
160 x 145 x 110 mm
Supply input
:
Sensing input
:
Accuracy
:
Ambient temperature
:
Dimensions
:
Features
Isolated and separate supply and sensing voltage
V/Hz operation
Underspeed trip with LED indicator
Self excitation circuit from 3 V residual voltage
Parallel operation possible with optional external droopkit (sold separately)
Potentiometer input for external voltage adjustment
Connector for optional control systems