0Motorpact 0installation instructions

Transcription

0Motorpact 0installation instructions
Motorpact
0
English
MV distribution
factory built assemblies
at your service
installation
instructions
0
FVNR, RVAT, RVSS,
and INC cable cubicles
0
contents
0
general information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
standard tightening torques . . . . . . . . . . . . . . . . . . . . . . . . . . .
list of accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
5
5
5
general description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
full voltage non-reversing controller (FVNR) cubicle . . . . . . . . 7
reduced voltage soft start (RVSS) cubicle . . . . . . . . . . . . . . . . 8
reduced voltage autotransformer (RVAT) cubicle . . . . . . . . . . 9
incoming cable cubicle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
dimensions and weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
FVNR, RVSS, RVAT, and incoming cubicles . . . . . . . . . . . . . 12
instructions for receiving, handling, storing . . . . . . . . . . . .
receiving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
15
15
15
15
17
installation and operation recommendation . . . . . . . . . . . . . 19
the switchboard’s resistance to aging depends on three main
factors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
floor finishing and cubicle fastening . . . . . . . . . . . . . . . . . .
surface condition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
floor quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
description of irons and accessories . . . . . . . . . . . . . . . . . . .
placing and adjusting on standard civil engineering works . .
placing and adjusting on earthquake resistant civil
engineering works . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
21
21
21
21
21
23
installation instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
placing cubicles in a switchboard lineup . . . . . . . . . . . . . . . . 26
seismic certification of motorpact medium voltage (mv) motor
controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
coupling of cubicles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
installing the main earth lead . . . . . . . . . . . . . . . . . . . . . . . . . 35
installing busbars . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
principal of assembling covers . . . . . . . . . . . . . . . . . . . . . . . 37
placing MV cables in cubicle . . . . . . . . . . . . . . . . . . . . . . . . . 37
FVNR load cable connections . . . . . . . . . . . . . . . . . . . . . . . . 38
loadbox cable connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
RVAT cable connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Autotransformer Cable Connections . . . . . . . . . . . . . . . . . . . 41
RVSS cable connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
accessing the LV compartment . . . . . . . . . . . . . . . . . . . . . . . 42
LV cable routing and connection . . . . . . . . . . . . . . . . . . . . . . 43
placing the tunnel sheets . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
steps to be taken for tests and inspections . . . . . . . . . . . . . 49
hi–pot (dielectric) test 1 min . . . . . . . . . . . . . . . . . . . . . . . . . . 49
final inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Schneider Electric
05/2007
46032-700-08B.fm/3
0
46032-700-08B.fm/4
05/2007
Schneider Electric
0
general information
recommendations
height of ceiling for
internal arc tunnel or
IPX1 installation
If H > 4 m: tunnel installation is not
necessary for internal arc
withstand.
installation above the
switchboard
All types of equipment installation
such as a lamp or light fitting are not
recommended in order to avoid . . .
If 3150 A, a tunnel is required.
A H > 2.80 m is needed to install a
tunnel.
. . . using switchboard roofing
sheets to access this equipment.
marking
It is strictly forbidden to walk on the
parts bearing this marking.
It is strictly forbidden to remove the
parts bearing this marking when the
equipment is energized.
standard tightening torques
(non-greased screws and bolts)
screw
busbar
torque in N•m
mech. torque
Application methods:
in N•m
Ø 6
—
10
Ø 8
28
20
Ø 10
50
35
Ø 12
75
55
Ø 14
—
120
The conical washers
placed on the external
sides of the busbars ensure
better distribution of stress
regarding bolts tightened to
the recommended torques.
list of accessories
accessories
— contactors*
— front cubicle fastening rails and
hardware
— disconnector operator handle
— rear leveling plate and hardware
— splice busbars and hardware
— fuses
— civil engineering guide
— fuse puller (optional)
— installation instructions guide
— contactor lifting device (optional)
— instructions for use
— contactor test plug (optional)
— intercubicle fastening hardware — injector stick (optional)
— cable entry plates and hardware — H connection kit (optional)
— internal arc tunnel/IPX1 assembly — current test wire set (optional)
— internal arc tunnel end sheet
assembly
— voltage test wire set (optional)
* Contactors are typically shipped inside the equipment; however, they are
shipped separately for RVSS and RVAT cubicles.
Schneider Electric
05/2007
46032-700-08B.fm/5
0
46032-700-08B.fm/6
05/2007
Schneider Electric
0
general description
full voltage non-reversing
controller (FVNR) cubicle
A: MV power cable entry plate
A
B: internal arc vent cover (optional)
B
C: LV control cable entry plate
D: LV compartment door
C
E: diagnostic thermal detection module
(optional)
O
F: operation and locking panel
D
G: VPIS indicator box (optional)
P
H. interlock shuttle
I: blown fuse indicator (optional)
J: cable earthing switch, load connection
lug pads
Q
K: MV power fuses
L: contactor door
E
R
M: vacuum contactor
N: fuseholder, control power transformer
(CPT), and voltage transformer (VT)
S
F
P: main busbar barrier
G
H
I
Q: disconnector
J
O: LV inter-unit top wireway
R: main busbars
S: earth main busbar
T
K
T: surge arresters (optional)
U: current transformers
L
U
V: MV cable support clamps (bottom entry)
W: VT
V
M
X: LV cable entry plate (bottom entry)
W
N
X
Schneider Electric
05/2007
46032-700-08B.fm/7
0
reduced voltage soft start
(RVSS) cubicle
A. internal arc vent cover (optional)
A
B. LV control entry plate
C. contactor door
B
D. LV door
E. human machine interface (HMI) soft start
control interface module
I
C
F. Soft Start power compartment door
J
G. heater (optional)
K
H. LV control entry plate
L
I. customer conduit wireway
J. bypass contactor
M
K. ground fault board (optional)
N
L. terminal control board
M. main busbar compartment
N. earth main busbar
D
O
E
P
Q
O. control power, CPU boards, RTD board
(optional)
R
P. main busbar access cover
Q. LV compartment
S
F
R. door interlock
T
S. ring transformers
S
T. silicon control rectifier stacks
G
H
46032-700-08B.fm/8
05/2007
Schneider Electric
0
reduced voltage
autotransformer (RVAT)
cubicle
A. internal arc vent cover (optional)
B
A
B. LV control cable entry plate
C. contactor door
D. run contactor
E. start contactor
C
F: LV door
G. autotransformer door
H: surge arresters
I. main busbar access cover
D
H
I
E
J
K
J. door interlock
K. main busbar compartment
L. earth main busbar
M. autotransformer
Schneider Electric
F
L
G
M
05/2007
46032-700-08B.fm/9
0
incoming cable cubicle
A. internal arc vent cover (optional)
A
B. LV control cable entry plate
C. MV upper barrier
B
D. MV upper door
E. MV lower door
F. VPIS indicator box (optional)
C
H
G. MV lower barrier
H. LV inter-cubicle top wireway
D
I
I. capacitive divider, VPIS (optional)
J
J. surge arresters (optional)
K. earth main busbar
L. main busbar lug pad
M. earth riser connection
N. current transformers (optional)
K
O. MV cable support clamps (bottom entry)
L
M
N
E
O
F
46032-700-08B.fm/10
G
05/2007
Schneider Electric
0
Schneider Electric
05/2007
46032-700-08B.fm/11
0
FVNR, RVSS, RVAT, and
incoming cubicles
dimensions and weights
(All dimensions in mm)
FVNR
2300
375
946
79
RVSS
2300
375
750
946
79
RVAT
2300
375
1125
946
79
2300
375
46032-700-08B.fm/12
1500
946
05/2007
79
Schneider Electric
0
incoming cubicles
2300
508
946
79
500 mm
554
416
2300
749
946
79
750 mm
approximate weights
Enclosure
Width (mm)
Approximate
Weight (kg)
FVNR
375
472
RVSS
750
1094**
RVAT*
1125
1200**
1500
1357**
500
350
750
900
Motor Starter Type
incoming cubicle
*Autotransformer weight to be added
**Includes FVNR module
Schneider Electric
05/2007
46032-700-08B.fm/13
0
46032-700-08B.fm/14
05/2007
Schneider Electric
0
receiving
instructions for receiving,
handling, storing
Check the packing list against the
equipment received to ensure the
order and shipments are complete.
Make claims for shortages or other
errors in writing within 30 days after
receipt of shipment. Failure to do so
constitutes unqualified acceptance
and a waiver of all such claims to
the purchaser.
Inspect the equipment for damage.
If you find or suspect damage,
immediately file a claim with the
carrier and notify Schneider
Electric.
identification
rating nameplate
handling
■
characteristics
■
designations
■
serial number
Equipment is normally shipped in
an upright position on a pallet and
wrapped in plastic.
Do not remove the skids
until the shipping
sections are at the final
location. Always use the skids to
prevent equipment distortion.
handling using a sling
overhead
lifting
provisions
Schneider Electric
05/2007
46032-700-08B.fm/15
0
using a forklift
Review the shipping
documentation to verify the
actual weight of the
equipment does not exceed that of the
lifting equipment. When an overhead
crane is not available, rollers, pipes, or
a forklift may be used.
If lifting the motor
controller by forklift,
stabilize the shipping
section with a safety strap to
reduce the possibility of tipping.
The forks must extend completely
under the pallet.
handling using a forklift
safety strap
This equipment is shipped up to a
maximum of 5 vertical units—1,873
mm wide.
46032-700-08B.fm/16
05/2007
Schneider Electric
0
storage
Keep this equipment in a clean,
dry place that is free from
corrosive elements and
mechanical abuse. Provide
area ventilation, heating, and air
conditioning to maintain the
ambient temperature around
the equipment between –5 °C
and 40 °C. Energize the heaters
inside the controller, or add heat
from a separate source, such as
a light bulb or blower. Use a
minimum of 125 watts of heat
per vertical section to keep the
equipment dry during storage.
Cover the equipment with a
tarpaulin when necessary to
protect it from contaminants
and moisture. Do not store units
considered for indoor use
outdoors.
Monitor the equipment closely
in areas with high humidity. If
necessary, use additional heat
to keep the equipment dry.
Contact the factory if the
internal heaters do not
adequately prevent
condensation for your location
or environmental condition.
40 °C
–5 °C
Schneider Electric
05/2007
46032-700-08B.fm/17
0
46032-700-08B.fm/18
05/2007
Schneider Electric
installation and operation
recommendation
0
the switchboard’s
resistance to aging
depends on three
main factors:
■
The necessity of correct
implementation of
connections:
■
Provide area ventilation,
heating, and air conditioning
to maintain the ambient
temperature around the
equipment between –5 °C
and 40 °C.
New cold shrink or slip–on
technology offers ease of
installation that favours
resistance over time. Their
design allows them to be
used in polluted
environments with harsh
climatic conditions.
■
Ventilation control:
The effect of the relative
humidity factor:
Heating resistor installation
is essential in climates with a
high rate of relative humidity
and with significant
temperature differentials.
operation
It is strongly advised to
periodically carry out (minimum
every two years approximately) a
few operation cycles on
operating devices.
Outside normal conditions of use
(between –5 °C and 40 °C,
absence of dust, corrosive gas,
etc.), it is recommended to
consult, with our Schneider
Electric services center, the
steps to be taken in order to
ensure correct functioning of the
installation.
Schneider Electric
05/2007
Our service center is at your
disposal at any time:
■
To undergo an installation
diagnostic.
■
To offer you, if need be,
suitable maintenance
operations.
■
To offer you maintenance
contracts.
■
To offer you adaptations.
46032-700-08B.fm/19
0
46032-700-08B.fm/20
05/2007
Schneider Electric
0
floor finishing and cubicle
fastening
The floor finishing and cubicle fastening instruction throughout this guide is for equipment installed above
a maintenance space. see the civil engineering guide for alternate mounting instructions.
surface condition
Floor evenness is such that a two
meter ruler moved over all surfaces
and in all . . .
. . . directions, does not display a
difference of more than 5 mm.
floor quality
For the rolling of mobile part
extraction tools without degrading
the floor . . .
. . . it must have a compression
withstand > 33 Mpa.
description of irons
and accessories
cubicle fastening
C
Take this equipment from
the civil engineering
package of the switchboard
packaging.
A
B
Standard civil engineering:
Earthquake resistant civil
engineering:
A. 1 iron section (length 2 m)
A. 2 iron sections (length 2 m)
B. 4 expansion pins
B. 8 expansion pins
C. 2 fastening shims
C. 4 fastening shims
placing and adjusting on standard civil
engineering works
preparation
70+2
Drill a hole in the floor and irons.
Ø 14
55
2000
100
Schneider Electric
600
600
05/2007
600
100
46032-700-08B.fm/21
0
placing the irons
Place and fix the irons to the floor
using the supplied expansion pins,
screws, and washers.
Cut the last iron to the required
length.
tightening irons
If the iron is bent: distribute the
loads on its length.
Longitudinal adjustment: use a
water level and shims before
tightening the screws.
Transversal adjustment: use a
spirit level and shims before
tightening the screws.
For the correct installation
of cubicles, it is advised
to comply with a tolerance
of + 0.1 cm/m and a maximum gap
of + 0.3 cm on the length of the
switchboard.
46032-700-08B.fm/22
05/2007
Schneider Electric
0
placing and adjusting on
earthquake resistant civil
engineering works
preparation
940
Drill a hole in the floor and irons.
ø14
70+2
ø14
55
55
2000
100
600
600
600
100
placing the irons
Place and fix the irons to the floor using the
supplied expansion pins, screws, and
washers.
Cut the last iron to the required length.
tightening irons
If the iron is bent: distribute the loads on its
length.
Longitudinal adjustment: use a water level
and shims before tightening the screws.
The irons must be very smooth,
because adjustment using
actuators is not possible.
Schneider Electric
05/2007
46032-700-08B.fm/23
0
Transversal adjustment: use a
spirit level and shims before
tightening the screws.
For the correct installation
of cubicles, it is advised
to comply with a tolerance
of + 0.1 cm/m and a maximum gap
of + 0.3 cm on the length of the
switchboard.
46032-700-08B.fm/24
05/2007
Schneider Electric
0
Schneider Electric
05/2007
46032-700-08B.fm/25
0
installation instructions
placing cubicles in a switchboard lineup
assembling, adjusting,
and fastening
Place the switchboard cubicles
according to front panel drawings
and the single–line diagram.
Start by placing the cubicle located
in the middle of the switchboard
(except in the case of an extension
of the existing switchboard) then
position the cubicles on either side
of it, according to the Civil
Engineering Guide indications.
Check customer drawings
to see if front-only
accessibility and shielded
cables are required. The cables
may need to be prepared before
the equipment is placed in
position.
1 bag of standard civil
engineering screws and bolts
containing:
Depending on the type of
civil engineering, take the
following from package 1 of
the cubicle packaging:
■
rear adjustment
accessories–
A. 4 x HM12 nuts (lock nuts)
B. 2 quick cage nuts
C. 5 flat washers
D. 4 x HM12 x 70 screws
(actuators)
B
C
E. 2 support irons
A
D
■
F
front fastening accessories–
F. 2 hook head bolts
G. 2 fastening shims
E
G
1 bag of earthquake resistant
civil engineering screws and
bolts containing:
■
I
front fastening accessories–
H. 2 hook head bolts
J
I.
2 fastening shims
■
rear fastening accessories–
H. 2 hook head bolts
J. 2 fastening shims
H
46032-700-08B.fm/26
05/2007
Schneider Electric
0
placing on maintenance space
Do not dismantle any part of the
cubicle.
Placing can be carried out by lifting or
rolling.
Handling of the cubicle by rolling.
adjusting cubicles on standard
civil engineering works
The operations described hereafter, must
only be carried out once the cubicle is
positioned on civil engineering works.
see "accessing the medium voltage
compartment" in the instructions for
use guide.
E
B
Position the support irons
(E) at the rear of the cubicle
by gaining access through
the maintenance space.
Place the 2 quick cage nuts
(B) at the rear of the cubicle
by gaining access
underneath the cubicle.
D
A
C
B
Screw the lock nut (A) on each
actuator (D), place washer (C),
then screw the actuators in the
quick cage nuts.
Schneider Electric
05/2007
Lift the rear of the cubicle by
screwing the 2 actuators to
level the cubicle.
46032-700-08B.fm/27
0
fastening to the floor on
standard civil engineering
works
Open the front door and secure the cubicle as
shown (front only).
G
F
G
F
To be retrieved from the bag
of screws and bolts.
fastening to the floor on
earthquake resistant civil
engineering works
Place the fastening screws at
the front of the cubicle and
tighten them.
I
H
I
Open the front door and secure the cubicle at
the front as shown. Rear access is required
for securing the rear of the cubicle.
H
To be retrieved from the 2 bags
of screws (I) and bolts (H).
Place the fastening screws at
the front of the cubicle and
tighten them.
J
J
H
H
To be retrieved from the 2 bags
of screws (J) and bolts (H).
46032-700-08B.fm/28
05/2007
Place the fastening screws at
the rear of the cubicle and
tighten them.
Schneider Electric
0
seismic certification of motorpact medium voltage (mv) motor controllers
Motorpact MV motor controllers that are seismically certified have been qualified
for the site-specific seismic requirements of the listed model building codes and
standards. Optional construction features may be required, depending on the
location of the installation and the particular code and standard of interest.
Seismic certificates of compliance and equipment labels are provided with all
seismically certified equipment. To maintain the validity of this certification, the
installation instructions provided in this bulletin must be followed.
responsibility for
mitigation of seismic
damage
For the purposes of the model building codes, Motorpact MV motor controllers are
considered nonstructural building components. Equipment capacity was
determined from tri-axial seismic shake table test results as defined in the
International Code Counsel Evaluation Service (ICC ES) Acceptance Criteria for
Seismic Qualification Testing of Nonstructural Components (AC156). Unless
otherwise indicated, an equipment importance factor of 1.5 (IP = 1.5) was used,
indicating that equipment functionality was verified before and after shaker table
seismic simulation testing. This importance factor is indicative of critical facilities
where maximizing the probability of post event functionality is a priority. AC156 is
published by the ICC ES and has been recognized by the Building Seismic Safety
Council (BSSC) as an appropriate methodology in the 2003 National Earthquake
Hazard Reduction Program (NEHRP) Commentary (FEMA 450 Part 2). The
National Institute of Building Sciences established the BSSC in 1979 to develop and
promote regulatory provisions for earthquake risk mitigation at the national level.
Incoming and outgoing cable and conduit must also be considered as related but
independent systems. They must be designed and restrained to withstand the
forces generated by the seismic event without increasing the load transferred to
the equipment. For applications where seismic hazard exists, bottom entry and
exit of cable and conduit is preferred. If the spectral acceleration value (Ss as
defined by the International Building Code or NFPA 5000) is in excess of 2.67g
(such as the New Madrid seismic area), then the equipment must also be braced
at the top using a lateral restraint system. A lateral restraint system is required in
situations where horizontal motion at the top of the equipment is not be desirable
(such as applications where top entry and exit of conduit are used). This system
must be capable of transferring the loads created to the load-bearing path of the
building structural system.
maintaining seismic
certification
Schneider Electric’s seismic qualification of nonstructural components is just one link
in the chain of responsibility required to maximize the probability that the equipment
will be intact and functional after a seismic event. During a seismic event, the
equipment must be able to transfer the loads that are created through the mounting
pad and anchorage to the loadbearing path of the building structural system.
The structural civil engineer or consulting engineer of record is responsible for
detailing the equipment connection and anchorage requirements (including the
lateral restraint system, if appropriate) for the given installation. The installer and
manufacturers of the anchorage and lateral restraint system are responsible for
assuring that the mounting requirements are met. Schneider Electric is not
responsible for the specification and performance of these systems.
Schneider Electric
05/2007
46032-700-08B.fm/29
0
coupling of cubicles
preparing the cubicle
Review the assembly drawings to ensure the shipping splits will be
assembled in the correct order. If a cubicle connects to an existing
switchboard, connect the cubicle first.
The following conditions must be met for each cubicle:
■
Remove (2) rear covers (A) and main busbar cover (B).
see "accessing the medium voltage compartment" in the
instructions for use guide.
■
Remove (2) cable trough covers (C) after opening the contactor door.
see "incoming cables from below, cubicle by cubicle."
(Not required for the cubicle on the far right side of the switchboard
unless connecting to an existing switchboard.)
■
Open the LV door and remove the operator cover (D) when
connecting internal arc withstand cubicles.
LV door
M6
operator
cover
B
B
A
A
C
D
contactor
door
M6
The operator cover must be
removed for internal arc
withstand cubicles.
A
■
Remove (4) M6 screws.
■
Replace after connecting
cubicles.
A
anchor
equipment per
"fastening to
the floor"
instruction
Tightening torque:10 N•m.
assembling cubicles
■
Assemble the (2) cubicles or shipping splits together with the
factory-supplied hardware. Tightening torque: 35 N•m.
Internal arc withstand equipment will also include caulk which is to be
used between each shipping split. see the instruction provided with
the hardware kit.
46032-700-08B.fm/30
■
Anchor the cubicle and repeat the process. see "fastening to the
floor."
■
Replace operator cover and covers using original hardware.
M6 tightening torque: 10 N•m.
M10 tightening torque: 35 N•m.
05/2007
Schneider Electric
0
installing the
autotransformer
RVAT
The autotransformer is shipped separate from the switchboard, and therefore,
requires it to be installed at the job site. After installation, for cable connection
information,
see "RVAT cable connection."
To install the autotransformer, some disassembly of the cubicle is required. The
disassembly will consist of removing the door latch center post, the cubicle
support gussets, and the lower door sill. All required information for this
procedure is provided.
starting position
■
Remove the autotransformer from its packaging.
■
Gain access to the lower compartment of the RVAT cubicle.
see "accessing the medium voltage compartments RVAT or RVSS"
in the instructions for use guide.
parts identification
A. door latch center post
B. cubicle support gussets
C. lower door sill
B
C
A
B
RVAT cubicle
tapped autotransformer
Schneider Electric
05/2007
46032-700-08B.fm/31
0
removing parts
RVAT
door latch center post A
■
Remove (2) screws holding lower latch to upper latch.
■
Remove (2) screws holding top of door latch center post to middle
tie channel.
■
Remove (2) screws holding bottom of door latch center post to lower
door sill.
upper latch
remove
remove
lower latch
A
top of post
B
remove
B
C
A
B
remove
C
remove
lower
door sill
A
remove
bottom of post
cubicle support gusset B
lower door sill C
46032-700-08B.fm/32
■
Remove the (4) carriage bolts holding the 2 cubicle support
gussets.
■
Remove the (2) carriage bolts holding the lower door sill.
05/2007
Schneider Electric
0
placing the autotransformer
RVAT
■
Roll autotransformer into the cubicle, and align 4 mating holes in base with
the mating holes in the cubicle floor.
■
Using M10 hardware, 4 places, anchor into the concrete. Tightening
torque: 35 N•m.
anchor autotransformer
(4) places
Schneider Electric
05/2007
46032-700-08B.fm/33
0
replacing parts
RVAT
lower door sill C cubicle support gusset B
■
Insert the lower door sill C as shown onto the cubicle floor.
■
Mount the (2) cubicle support gussets B to the lower door sill C and
the cubicle side sheets.
■
Hold all parts to embosses with (6) M10 carriage bolts, nuts, and
flat washers. Tightening torque 35 N•m.
upper latch
replace
replace
lower latch
A
top of post
B
replace
B
C
A
B
replace
C
replace
lower
door sill
A
replace
bottom of post
door latch center post A
46032-700-08B.fm/34
■
Mount the door latch center post A to lower door sill with (2) M6
screws and washers. Leave hardware loose until top of post is
secured.
■
Secure top of door latch center post A to the middle tie channel with
(2) M6 screws.
■
Attach the upper and lower latches together with (2) M6 carriage
bolts, washers, and nuts. Ensure upper latch is in front of lower
latch as shown.
■
Tightening all (6) screws to 10 N•m.
05/2007
Schneider Electric
0
installing the main earth lead
inter cubicles
This connection can be done during
the installation of each cubicle or
after the switchboard assembly.
Tightening torque: 50 N•m.
Connect to the
next cubicle
using main earth
bar existing
hardware.
from the switchboard to
the building’s earth
A
earth bar
Connect a cable from the earth bar
to the building’s earth on the left
side of an incoming cable cubicle.
If an incoming cubicle is not in the
switchboard, the earth connection
should be made at the connecting
equipment.
Tightening torque: 50 N•m.
Schneider Electric
05/2007
46032-700-08B.fm/35
0
installing busbars
This connection can be done during the installation of each cubicle.
Access the busbars through the cubicle side. If possible, access the main busbar
compartment from the rear of the cubicle.
Main busbars run between each disconnector switch in a switchboard lineup.
Retrieve in packaging:
A. splice main busbar (75 x 10); length depends on cubicle width
B. busbar shim (75 x 51 x 10)
C. M10 screws; length depends on busbar quantity. see table below.
D. conical washer
Connect all busbars throughout the switchboard lineup before tightening.
Tightening torque: 50 N•m.
The disconnector must be in the CLOSED position when busbars are installed. This is required for proper
operation of the disconnector. see "disconnector operation" in the instructions for use guide.
splice connection
pass–through connection
Existing main
busbar
C, D
C, D
A
screw C
B
3150 A: M10 x 100
3150 A
2500 A
1250 A
630 A
2500 A: M10 x 80
1250 A: M10 x 60
630 A: M10 x 40
L1
L2
L3
1,431.8
46032-700-08B.fm/36
05/2007
Schneider Electric
0
principal of assembling covers
(depending on needs)
Retrieve the covers from cubicle
packaging, if not provided in the
cubicle.
wire tie (typ)
Position the split-cover on the
connection pads.
Connect the split-cover using wire
ties.
placing MV cables in cubicle
general information
An explanation is given for single
pole and tri-plex cable.
A
From the cubicle packaging,
retrieve the floor plates, bushings,
and fastenings.
A. 3 single-pole cables
B. 1 tri-plex pole cable
To access the interior of a
cubicle, refer to the following:
"instructions for accessing
the medium voltage
compartment" in the
instructions for use guide.
B
Cut cable bushings according to the
number and diameter of cables.
Install them on the cables.
Fix the flange support to the bottom
plates on the cubicle floor.
Reassemble the bottom plates.
To produce cable ends, refer to
the accessories for manufacturer
instructions.
MV cable maintenance
Schneider Electric
05/2007
Fill in the openings that have not
been used with uncut cable
bushing.
46032-700-08B.fm/37
0
FVNR load cable connections
M10 x 40 hardware. Tightening
torque: 50 N•m. see "connecting
cables" for preparing lugs.
top entry
bottom entry
Avoid sharp turns, corners, and edges that could damage or
weaken the cable insulation. Follow the cable manufacturers
instructions to determine the minimum bending radius of cables.
It is highly recommended to insure cables do not come in contact
with metal parts or opposite phases.
Failure to follow this instruction will increase the electrical stress on the
cable, shortening the life of the equipment.
cable installation
Cables must be securely fastened or braced to withstand short circuit forces and
to prevent strain on the terminals.
Maximum length of unsupported cable is 457 mm for line side cable and 1100 mm
for load side cable.
connecting cables
Before making cable connections, check to see if special site preparation
requirements are needed. Determine the phase identity of each cable. Viewing
the controller from the front, standard busbar sequence is normally phased L1–
L2–L3 left to right and L3–L2–L1 top to bottom and front to rear, unless labeled
otherwise.
non-shielded cable
Follow the cable manufacturer’s instructions for stripping back the insulation and
preparing the cable for the lug.
shielded cable
Follow the cable manufacturer’s instructions for stripping the shield and cleaning the
unshielded portion of the cable. Install the appropriate stress cone in accordance with
the stress cone manufacturer’s instructions. It is recommended to use a 229 mm
maximum prefabricated stress cone. Follow the lug manufacturer’s instructions to
attach the cable lug on the cable.
46032-700-08B.fm/38
05/2007
Schneider Electric
0
loadbox cable
connection
The load-side connections are protected by a flexible barrier as shown. To attach
the cable, the upper and lower barriers must be folded out and the middle barrier
must be removed.
There are minimal electrical clearances in this area. It is critical that
all barriers be reinstalled after the load cable connection is made.
Failure to do so can result in equipment damage or personal injury.
loadbox flexible
upper and lower
barrier
loadbox flexible
middle barrier
(removable)
To attach the cable:
Schneider Electric
■
remove the middle barrier.
■
fold back the upper and lower barriers.
■
attach the cable, per cable manufacturer’s instruction. Tightening
torque: 50 N•m.
■
replace the upper and lower barriers.
■
replace the middle barrier.
05/2007
46032-700-08B.fm/39
0
RVAT cable
connection
Due to the autotransformer shipping separate from the RVAT cubicle, the cable
connections to the transformer will need to be made at the job site. All other cable
connections between the main controller and the RVAT are made at the factory.
The transformer lineside and loadside cables are cut to length and are properly
labeled for easy customer identification. For a tapped autotransformer, connect
cables to the taps as shown on the electrical drawings provided with each
lineup. The surge arrester cable connections to the transformer are required
after all dielectric tests
are complete.
All motor cable connections are made in the main controller cubicle.
see "loadbox cable connection."
Steps:
■
Connect the line and load cables to the appropriate tap connection
with M10 hardware provided. Tightening torque: 50 N•m.
For additional information on tap connections, see "RVAT operation"
in the instructions for use guide.
■
Connect the cables from the surge arresters to the Phase zero taps
with M10 hardware provided, after all dielectric testing is complete.
Tightening torque: 50 N•m.
cable
identification
label
surge arrester
connection
Connect surge arrester cables after all dielectric testing is
complete.
46032-700-08B.fm/40
05/2007
Schneider Electric
0
Autotransformer Cable Connections
Remove the cable identification tags and associated metal wire tie
from the power cables and surge arrester cables before energizing
equipment. Failure to follow this instruction can result in death,
serious injury, or equipment damage.
L1-phase 100% cable. Line side
connection from run contactor.
L2-phase load connection shown at
80% tap (select 50%, 65%, or 80%
depending upon customer
requirements). Load side connection
from load box.
L3-phase Zero Tap Cable. Start
connection from start contactor.
Additional cabling notes: The autotransformer line side connections (100%
taps) originate from the load side of the main contactor in the controller. The
autotransformer load side cables (50%, 65%, or 80% taps) are routed back to
the main controller and terminate at the load box on the left side. Customer
connections are made inside the controller at the load box.
RVSS cable
connections
Schneider Electric
Customer power cable connections should not be made within the RVSS
enclosure. All power cable connections have been made at the factory between
the RVSS enclosure and adjacent main controller. Customer power cable
connections should be made at the load box in the controller.
05/2007
46032-700-08B.fm/41
0
accessing the low voltage
compartment
opening the LV door
A handle locking screw is used on the LV door latch for seismic and internal arc
withstand protection. An optional key lockable latch is
also available.
Ensure the lock is used when closing the door.
Locking
screw
closed
latch
B
A
To open the LV door:
Closure: To place back into
operation:
46032-700-08B.fm/42
■
Turn handle locking screw (A) counter-clockwise.
■
Lift and turn handle (B) counter-clockwise.
The LV door can now be opened.
To close, carry out operations in the reverse order of opening.
05/2007
Schneider Electric
0
LV cable routing and connection
incoming cables at the end of the switchboard
customer
connection
Remove the roofing sheet on
each cubicle (4 screws).
Place the strand and the feed wires. Carry out connections to the
Route the wiring cubicle by cubicle, terminal blocks.
by passing wires through the cutout
Reassemble the roofing sheets
in cable troughs.
(4 screws per sheet). Tightening
torque: 10 N•m.
incoming cables through the
top, cubicle by cubicle
Remove the cable leadthrough
sheet located on the roofs of the
cubicles (2 screws), as well as the
roofing sheets (4 screws).
Cut the cable leadthrough sheets
according to the wires to be
installed.
Install the glands on these sheets
and pass the wires through.
Replace the sheet (2 screws).
Connect the wires to the
terminal blocks and fix the
roofing sheet (4 screws).
Tightening torque: 10 N•m.
Schneider Electric
05/2007
46032-700-08B.fm/43
0
incoming cables from below,
cubicle by cubicle
cubicle roof
cable
trough
covers
floor
trough
covers
operator
panel
■
Remove the cable trough covers
(4 screws).
■
Remove the operator cover
(4 screws).
■
Remove the floor trough covers and
floor plate (3 screws).
■
Remove the roofing sheet from the
cubicle roof (4 screws).
■
Cut the floor plate according to the
number and the diameter of cables,
maximum of 5 diameters (20 mm).
■
Feed the wiring up to the LV
compartment, and replace the
following covers:
■
Reattach floor plate to the cubicle
(2 screws). Tightening torque:
10 N•m.
■
Route the wiring across the LV
floor and up to the cubicle roof.
■
Connect the wiring to the terminal
blocks.
46032-700-08B.fm/44
— operator cover (4 screws)
— cable trough covers (4 screws)
— floor trough covers (1 screw)
■
05/2007
Reassemble the roofing sheet
(4 screws). Tightening torque:
10 N•m.
Schneider Electric
0
placing the tunnel sheets
4 side internal arc tunnel
A. front end of the cubicle
B. rear of the cubicle
1. top view
2. bottom view
A
A
B
1
B
A
2
B
Schneider Electric
05/2007
46032-700-08B.fm/45
0
internal arc tunnel end
A. front end of the cubicle
B. rear of the cubicle
1. side view
2. bottom view
B
A
B
A
2
1
46032-700-08B.fm/46
05/2007
Schneider Electric
0
non wall–mounted cubicle IPX1 roof
A. front end of the cubicle
B. rear of the cubicle
1. top view
2. bottom view
A
B
B
A
1
A
B
2
Schneider Electric
05/2007
46032-700-08B.fm/47
0
46032-700-08B.fm/48
05/2007
Schneider Electric
0
steps to be taken for tests and
inspections
hi–pot (dielectric) test
1 min
safety rules
During testing, maintain a minimum clearance of 1.8 m from
the equipment.
Perform a standard hi-pot (dielectric) test to measure insulation
integrity.
All operations described hereafter
must be carried out in compliance
with the safety standards in force,
under the responsibility of a competent
person.
Take the following minimum actions to help promote the safety of
personnel and equipment:
■
Restrict entry into the area to prevent any unauthorized
personnel from approaching the gear during testing.
■
Notify all persons that the test is going to be conducted.
■
Follow all local lockout and tag-out procedures.
■
Remove all fuses—low voltage and medium voltage.
■
Disconnect surge arresters, surge capacitors, and power factor
correction capacitors (if supplied).
NOTE: Do not use cable earthing switch (if supplied) to discharge
capacitors.
WARNING
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
If load is a capacitor bank, wait 5 minutes before servicing equipment.
Capacitors should have an internal resistor to dissipate voltage to 50 V
maximum after 5 minutes.
Failure to follow this instruction can result in death or serious injury.
Schneider Electric
■
Disconnect or earth capacitive dividers, if supplied.
■
Unearth or OPEN the cable earthing switch, if supplied. For
operation procedures, see “cable earthing switch operation”
in the instructions for use guide.
■
All earth connections must be properly made and tightened.
see "installing busbars."
■
Do not use unfiltered, half-wave rectified dc hi-pot test units.
Use of such devices greatly increases the chance of x-ray
generation.
05/2007
46032-700-08B.fm/49
0
After completing hi–pot testing, temporarily earth the busbars to
remove any residual charges.
Failure to follow this instruction can result in injury.
phase-to-phase hi-pot testing
Follow these steps to perform a phase-to-phase hi-pot test:
■
Perform a phase-to-phase hi-pot test on the main busbar.
— Gradually increase the voltage to the test levels of the
standards in force.
— Verify that the equipment sustains the required voltage
without flashover for one minute.
■
phase-to-ground hi-pot testing
Turn off the test equipment. Discharge to earth the phase
busbar before removing the test cables.
Follow these steps to perform a phase-to-ground hi-pot test:
■
Perform a phase-to-earth hi-pot test on the main busbar.
— Gradually increase the voltage to the levels shown in the test
levels of the standards in force.
— Verify that the equipment sustains the required voltage
without flashover for one minute.
■
Turn off the test equipment. Discharge to earth the phase
busbar before removing the test cables.
If the test is unsuccessful, inspect the insulators for leakage paths. If
necessary, clean the surface of the insulator(s) with denatured alcohol and
re-test. If problems persist, DO NOT ENERGIZE THE EQUIPMENT.
Contact your local field sales office or your distributor.
If the equipment has been stored for several months or has been exposed
to high humidity during the storage time period, PERFORM A STANDARD
HI–POT (DIELECTRIC) TEST. First energize the heater circuits for a
minimum of 24 hours. Follow other equipment testing procedures as
required by customer in-house standards.
46032-700-08B.fm/50
05/2007
Schneider Electric
0
final inspection
ALWAYS assume that all circuits are live until they
have been completely de-energized, tested, earthed,
and tagged.
Follow all lock-out/tag-out procedures. If disconnect switches
cannot be opened, disconnect the line leads.
After installing the equipment and making all interconnections,
follow the steps below to test the equipment and perform a final
inspection before placing it in service.
‰ Verify that a hi-pot test has been performed recently.
The following operations must only be carried out after
dielectric tests and before the equipment is energized.
‰ Check all control wiring with the wiring diagrams. Verify that all
connections are properly made and tightened, all secondary
fuses are installed, current transformer circuits are complete, all
fault detection devices have been properly connected and set,
and that loose connections are tightened to the proper
tightening torque.
‰ Verify that all protective relays have been configured with
proper settings per the outcome of customer’s coordination
study.
‰ Verify that all insulating surfaces, including the primary support
insulators and isolation barriers, are clean and dry.
‰ Verify that all primary fuses are installed and orientated
properly and do not exceed the nameplate rating for their
cubicles. see "installing fuses" in the instructions for use
guide.
‰ Verify all surge arresters, surge capacitors, and power factor
correction capacitors are connected. see "standard
tightening torques."
‰ Before energizing any source of electric power, make a final
check of the equipment. Inspect every compartment for loose
parts, tools, litter, and miscellaneous construction items.
‰ Review key interlock schemes carefully (if used). Insert only the
proper keys in the locks. Remove all extra keys and store them
where only authorized personnel can access them.
‰ Verify that all barriers, covers, and doors are secured using the
original mounting hardware.
Schneider Electric
05/2007
46032-700-08B.fm/51
The Schneider group service centers are at your
service for:
engineering and technical assistance
commissioning
training
preventive and corrective maintenance
adaptation
spare parts.
Schneider Electric Industries SAS
Address:
330 Weakley Road
Smyrna, TN 37167, USA
1888-778-2377
As standards, specifications and designs change from time to time, please ask for confirmation
of the information given in this publication.
This document has been printed
on ecological paper.
http:/www.schneiderelectric.com
Design: Schneider Electric Technical Publications Department, Nashville, TN, USA
46032-700-08B
05/2007
Motorpact © 2004—2007 - Schneider Electric - All rights reserved.
Contact your sales representative who will put you
in touch with your nearest Schneider group
service center or call us on
33 (0)4 76 57 60 60 (Grenoble, France).