Surge Protection Devices - GE Industrial Solutions

Transcription

Surge Protection Devices - GE Industrial Solutions
Surge Protection Devices (SPD)
Section 5
Critical Power Products
Introduction ....................................................................................................5-2
Integrated Tranquell™ ME (to connect with
GE “A”Series Panelboards).....................................................................5-3
Integrated Tranquell™ HE and ME
(for GE Distribution Equipment) ..........................................................5-5
Tranquell™ 9X and 24X (Box Extensions for
GE “A” Series Distribution Equipment) .............................................5-8
Tranquell™ HE and ME (Wall Mount) ....................................................5-12
Tranquell™ ME and LE (Wall Mount) .....................................................5-18
Tranquell™ DIN Rail Mount .......................................................................5-20
Protection Block Assembly ......................................................................5-22
Rev. 11/13
Data subject to change
without notice
www.geindustrial.com
BuyLog™ Catalog
5-1
Surge Protection Device (SPD)
Section 5
Critical Power Products
Introduction
General Electric has been a leader in lightning and surge
protection for commercial, industrial and utility applications for
decades. The GE Surge Protection Device product line utilizes the
combined strengths of GE engineering capabilities and surge
suppression technology.
GE SPD products use quality materials and innovative designs
to achieve the best possible performance while maintaining
competitive prices. All units are 3rd party tested to the NEMA LS-1
standards, are rated in accordance with NEC Article 285 and
comply with UL1449, 3rd Edition. We have a full line of SPD
products available, integral to GE Distribution Equipment,
or wall mounted.
GE has a strong commitment to customer service. We offer a
level of service and engineering support unmatched by our
competition. Many of our products are designed to suit specific
customer applications. Our application engineering team is ready
to provide solutions for your surge suppression needs.
Contact your local GE sales office for additional information.
References
Integrated SPD
Wall Mounted
DEA-390, DEA-391, DEA-393, DEA-394
DEA-300, DEA-320, DEA-391, DEA-392
5-2
BuyLog™ Catalog
www.geindustrial.com
Rev. 11/13
Data subject to change
without notice
Surge Protection Device (SPD)
Section 5
Critical Power Products
Integrated Tranquell™ ME
Designed to Connect within GE “A Series™” Panelboards
This SPD model connects directly to the A Series™ Panelboard bus
bars without adding width or depth to the panel enclosure. These
devices have been tested to surge current ratings per NEMA LS-1,
including the fuses in the surge path. Since these surge protection
units are mounted to the bus bars, a breaker feeder is not
required or used. This design allows for maximum protection.
Ratings are available from 65kA per mode to 100kA per mode.
All mode protection is provided with surge components (MOVs)
connected on the phase to neutral, phase to ground, and neutral
to ground paths as appropriate for the voltage configuration.
Integrated Tranquell™ ME products are engineered for reliability,
flexibility and long life in the most extreme surge environment.
The true maximum surge current rating, unlimited by fusing, has
been proven successful in 3rd party tests.
Features and Benefits
Specifications
—UL1449, 3rd Edition CUL
—Optional UL1283 Noise Filters
—UL Tested to 65,000 Amperes Symmetrical Withstand
—Tranquell™ ME Device is Capable of Surviving a minimum of
5,000 Category C3 Impulses (10kA, 20kV) per mode
—Form C Dry Contacts for Remote Monitoring
—Green Status Indicating Lights, Red Service Light
—Audible Alarm with Test/Disable Feature
—Standard Surge Counter on AS
—Factory installed in GE "A Series™" Panels
—Standard 5 year limited warranty, Optional 20 year warranty
Operating Frequency:
Connection:
Operating Temperature:
Operating Humidity:
Weight:
50/60 Hz
Direct Bus Connection, Parallel Connected
-40°C to +65°C
0% to 95% Non-Condensing
13 lbs.
1.331 [33.81]
0.312 [7.91] TYP
5.064 [128.62]
0.236 [ 5.99] HOLE
(4 PLACES)
6.000 [152.40]
5.331 [135.41]
8.321 [211.36]
9.494 [241.15]
2.869 [72.87]
9.400 [238.76]
Rev. 11/13
Data subject to change
without notice
www.geindustrial.com
BuyLog™ Catalog
5-3
Surge Protection Device (SPD)
Section 5
Critical Power Products
Integrated Tranquell™ ME
Designed to Connect within GE "A Series™" Panelboards
For GE "A" Series Panelboards - 65 kA Symmetrical
Fault Withstand
Panelboard, Lights, Alarm, Surge Counter, Form C Contacts
Maximum Surge Current
Product Number
65kA per mode / 130kA per phase
65kA per mode / 130kA per phase
65kA per mode / 130kA per phase
65kA per mode / 130kA per phase
65kA per mode / 130kA per phase
65kA per mode / 130kA per phase
65kA per mode / 130kA per phase
65kA per mode / 130kA per phase
65kA per mode / 130kA per phase
65kA per mode / 130kA per phase
80kA per mode / 160kA per phase
80kA per mode / 160kA per phase
80kA per mode / 130kA per phase
80kA per mode / 160kA per phase
80kA per mode / 160kA per phase
80kA per mode / 160kA per phase
80kA per mode / 160kA per phase
80kA per mode / 160kA per phase
80kA per mode / 160kA per phase
80kA per mode / 160kA per phase
100kA per mode / 200kA per phase
100kA per mode / 200kA per phase
100kA per mode / 200kA per phase
100kA per mode / 200kA per phase
100kA per mode / 200kA per phase
100kA per mode / 200kA per phase
100kA per mode / 200kA per phase
100kA per mode / 200kA per phase
100kA per mode / 200kA per phase
100kA per mode / 200kA per phase
TPME120S06AS
TPME120Y06AS
TPME220Y06AS
TPME277Y06AS
TPME480D06AS
TPME347Y06AS
TPME240H06AS
TPME240D06AS
TPME240Y06AS
TME600D065AS
TPME120S08AS
TPME120Y08AS
TPME220Y08AS
TPME277Y08AS
TPME480D08AS
TPME347Y08AS
TPME240H08AS
TPME240D08AS
TPME240Y08AS
TME600D080AS
TPME120S10AS
TPME120Y10AS
TPME220Y10AS
TPME277Y10AS
TPME480D10AS
TPME347Y10AS
TPME240H10AS
TPME240D10AS
TPME240Y10AS
TME600D100AS
Product #
T
P
*
M E
* AS
= Full featured, with UL 1283 noise filtering and surge counter
ASNF = without UL 1283 noise filtering (Available 100kA per Mode) only
ASNC = without UL 1283 noise filtering, without surge counter
(Available 100kA per Mode) only
Voltage Protection Rating (VPR)
UL 1449, 3rd Edition
September 2009 Revision
Nominal
System
Voltage
Voltage
(Volts RMS) Configuration
120S
HL-G
06
65kA
130kA
—
600
—
600 1200
125%
08
80kA
160kA
600 1200
125%
10
100kA
200kA
700
120Y
120Y/208
3 Ph, 4 W + G
700
—
600
—
240 Delta
3 Ph, 3 W
—
—
900
—
240H
120/240 Delta HL
240Y
1800
115%
3 Ph, 4 W + G
700 1200 600 1000 600 1200
115%
240Y/415
3 Ph, 4 W + G
1200
—
1000
—
1000 2000
130%
277Y
277Y/480
3 Ph, 4 W + G
1200
—
1000
—
1000 2000
115%
220Y
220Y/380
3 Ph, 4 W + G
1200
—
1000
—
1000 2000
145%
347Y
347Y/600
3 Ph, 4 W + G
1500
—
1500
—
1500 3000
115%
480D
480 Delta
3 Ph, 3 W
—
—
1500
—
—
—
3000
170%
Also available in 600D configurations. For details, please contact GE Power Quality Customer Service at 800 637 1738.
BuyLog™ Catalog
Per Phase
L-G
240D
5-4
Per Mode
HL-N
1 Ph, 3 W + G
L-L
Maximum Surge
Current Capacity
L-N
120/240
N-G
MCOV %
Max.
Continuous
Operating
Voltage
www.geindustrial.com
Phase Rating = (L-N + L-G)
Product # Example
TPME277Y10AS
—277Y/480 V, 3 Ph, 4 W + G
—100kA per mode
—Full featured, with UL 1283 noise
filtering and surge counter
Rev. 11/13
Data subject to change
without notice
Surge Protection Device (SPD)
Section 5
Critical Power Products
Integrated Tranquell™ HE and ME
Designed for GE Distribution Equipment
This SPD model connects to the panelboard or switchboard bus
bars without adding width or depth to the panel enclosure, and
only occupying 7X of vertical bus space. These units have been
tested to surge current ratings per NEMA LS-1, up to 200 kA per
mode, including the fuses in the surge path. Standard features
include a surge counter, audible alarm, indicating lights, dry
contacts, and an integral surge rated disconnect. Rating options
range from 65 kA per mode to 300 kA per mode.
All mode protection is provided with surge components (MOVs)
connected on the phase to neutral, phase to ground, and neutral
to ground paths as appropriate for the voltage configuration.
Integrated Tranquell™ HE and ME products are engineered for
reliability, flexibility and long life in the most extreme surge
environment. The true maximum surge current rating, unlimited
by fusing, has been proven successful in 3rd party tests.
Features and Benefits
Specifications
—UL1449, 3rd Edition CUL, UL1283
—UL Tested to 200,000 Amperes Symmetrical Withstand
—Integral Surge Rated Disconnect
—Factory installed in Spectra™ Series Panels and Switchboards
(7X Mounting Space), or Switchgear
—Tranquell™ ME Device is Capable of Surviving a minimum of
5,000 Category C3 Impulses (10kA, 20kV) per mode.
—Tranquell™ HE Device is Capable of Surviving a minimum of
20,000 Category C3 Impulses (10kA, 20kV) per mode.
—Device Capable of Surviving a minimum of 5,000 Longwave
(10x1000ms) Impulses per mode.
—Enhanced Thermal Protection Technology
—Form C Dry Contacts for Remote Monitoring
—Green Status Indicating Lights, Red Service Light
—Audible Alarm with Test/Disable Feature
—Standard Surge Counter
—Standard 5 year limited warranty, Optional 20 year warranty
Operating Frequency:
Connection:
Operating Temperature:
Operating Humidity:
Weight:
17.722
[450.130]
0.340
[8.636]
17.382
[441.494]
50/60 Hz
6 to 2/0 Conductors, Parallel Connected
-40°C to +65°C
0% to 95% Non-Condensing
24 lbs.
[
0.280
7.112] HOLE
(4 PLACES)
6.964
[176.877]
9.400
[238.755]
6.762
[171.751] TYP
7.202
[182.922]
2.638
[67.004] TYP
Rev. 11/13
Data subject to change
without notice
www.geindustrial.com
BuyLog™ Catalog
5-5
Surge Protection Device (SPD)
Section 5
Critical Power Products
Integrated Tranquell™ HE and ME
Designed for GE Distribution Equipment
For GE MCC Distribution Equipment
For GE Spectra™ Panel or Switch Board Distribution Equipment -
200 kA Symmetrical Fault Withstand
Panelboard, Lights, Alarm, Surge Counter, Form C Contacts
200 kA Symmetrical Fault Withstand
Panelboard, Lights, Alarm, Surge Counter, Form C Contacts
Maximum Surge Current
Product Number
Maximum Surge Current
Product Number
65kA per mode / 130kA per phase
65kA per mode / 130kA per phase
65kA per mode / 130kA per phase
65kA per mode / 130kA per phase
65kA per mode / 130kA per phase
65kA per mode / 130kA per phase
65kA per mode / 130kA per phase
65kA per mode / 130kA per phase
65kA per mode / 130kA per phase
80kA per mode / 160kA per phase
80kA per mode / 160kA per phase
80kA per mode / 130kA per phase
80kA per mode / 160kA per phase
80kA per mode / 160kA per phase
80kA per mode / 160kA per phase
80kA per mode / 160kA per phase
80kA per mode / 160kA per phase
80kA per mode / 160kA per phase
100kA per mode / 200kA per phase
100kA per mode / 200kA per phase
100kA per mode / 200kA per phase
100kA per mode / 200kA per phase
100kA per mode / 200kA per phase
100kA per mode / 200kA per phase
100kA per mode / 200kA per phase
100kA per mode / 200kA per phase
100kA per mode / 200kA per phase
150kA per mode / 300kA per phase
150kA per mode / 300kA per phase
150kA per mode / 300kA per phase
150kA per mode / 300kA per phase
150kA per mode / 300kA per phase
150kA per mode / 300kA per phase
150kA per mode / 300kA per phase
150kA per mode / 300kA per phase
150kA per mode / 300kA per phase
200kA per mode / 400kA per phase
200kA per mode / 400kA per phase
200kA per mode / 400kA per phase
200kA per mode / 400kA per phase
200kA per mode / 400kA per phase
200kA per mode / 400kA per phase
200kA per mode / 400kA per phase
200kA per mode / 400kA per phase
200kA per mode / 400kA per phase
300kA per mode / 600kA per phase
300kA per mode / 600kA per phase
300kA per mode / 600kA per phase
300kA per mode / 600kA per phase
300kA per mode / 600kA per phase
300kA per mode / 600kA per phase
300kA per mode / 600kA per phase
300kA per mode / 600kA per phase
300kA per mode / 600kA per phase
TPME120S06ME
TPME120Y06ME
TPME220Y06ME
TPME277Y06ME
TPME480D06ME
TPME347Y06ME
TPME240H06ME
TPME240D06ME
TPME240Y06ME
TPME120S08ME
TPME120Y08ME
TPME220Y08ME
TPME277Y08ME
TPME480D08ME
TPME347Y08ME
TPME240H08ME
TPME240D08ME
TPME240Y08ME
TPHE120S10ME
TPHE120Y10ME
TPHE220Y10ME
TPHE277Y10ME
TPHE480D10ME
TPHE347Y10ME
TPHE240H10ME
TPHE240D10ME
TPHE240Y10ME
TPHE120S15ME
TPHE120Y15ME
TPHE220Y15ME
TPHE277Y15ME
TPHE480D15ME
TPHE347Y15ME
TPHE240H15ME
TPHE240D15ME
TPHE240Y15ME
TPHE120S20ME
TPHE120Y20ME
TPHE220Y20ME
TPHE277Y20ME
TPHE480D20ME
TPHE347Y20ME
TPHE240H20ME
TPHE240D20ME
TPHE240Y20ME
TPHE120S30ME
TPHE120Y30ME
TPHE220Y30ME
TPHE277Y30ME
TPHE480D30ME
TPHE347Y30ME
TPHE240H30ME
TPHE240D30ME
TPHE240Y30ME
65kA per mode / 130kA per phase
65kA per mode / 130kA per phase
65kA per mode / 130kA per phase
65kA per mode / 130kA per phase
65kA per mode / 130kA per phase
65kA per mode / 130kA per phase
65kA per mode / 130kA per phase
65kA per mode / 130kA per phase
65kA per mode / 130kA per phase
80kA per mode / 160kA per phase
80kA per mode / 160kA per phase
80kA per mode / 130kA per phase
80kA per mode / 160kA per phase
80kA per mode / 160kA per phase
80kA per mode / 160kA per phase
80kA per mode / 160kA per phase
80kA per mode / 160kA per phase
80kA per mode / 160kA per phase
100kA per mode / 200kA per phase
100kA per mode / 200kA per phase
100kA per mode / 200kA per phase
100kA per mode / 200kA per phase
100kA per mode / 200kA per phase
100kA per mode / 200kA per phase
100kA per mode / 200kA per phase
100kA per mode / 200kA per phase
100kA per mode / 200kA per phase
150kA per mode / 300kA per phase
150kA per mode / 300kA per phase
150kA per mode / 300kA per phase
150kA per mode / 300kA per phase
150kA per mode / 300kA per phase
150kA per mode / 300kA per phase
150kA per mode / 300kA per phase
150kA per mode / 300kA per phase
150kA per mode / 300kA per phase
200kA per mode / 400kA per phase
200kA per mode / 400kA per phase
200kA per mode / 400kA per phase
200kA per mode / 400kA per phase
200kA per mode / 400kA per phase
200kA per mode / 400kA per phase
200kA per mode / 400kA per phase
200kA per mode / 400kA per phase
200kA per mode / 400kA per phase
300kA per mode / 600kA per phase
300kA per mode / 600kA per phase
300kA per mode / 600kA per phase
300kA per mode / 600kA per phase
300kA per mode / 600kA per phase
300kA per mode / 600kA per phase
300kA per mode / 600kA per phase
300kA per mode / 600kA per phase
300kA per mode / 600kA per phase
TPME120S06PP
TPME120Y06PP
TPME220Y06PP
TPME277Y06PP
TPME480D06PP
TPME347Y06PP
TPME240H06PP
TPME240D06PP
TPME240Y06PP
TPME120S08PP
TPME120Y08PP
TPME220Y08PP
TPME277Y08PP
TPME480D08PP
TPME347Y08PP
TPME240H08PP
TPME240D08PP
TPME240Y08PP
TPHE120S10PP
TPHE120Y10PP
TPHE220Y10PP
TPHE277Y10PP
TPHE480D10PP
TPHE347Y10PP
TPHE240H10PP
TPHE240D10PP
TPHE240Y10PP
TPHE120S15PP
TPHE120Y15PP
TPHE220Y15PP
TPHE277Y15PP
TPHE480D15PP
TPHE347Y15PP
TPHE240H15PP
TPHE240D15PP
TPHE240Y15PP
TPHE120S20PP
TPHE120Y20PP
TPHE220Y20PP
TPHE277Y20PP
TPHE480D20PP
TPHE347Y20PP
TPHE240H20PP
TPHE240D20PP
TPHE240Y20PP
TPHE120S30PP
TPHE120Y30PP
TPHE220Y30PP
TPHE277Y30PP
TPHE480D30PP
TPHE347Y30PP
TPHE240H30PP
TPHE240D30PP
TPHE240Y30PP
5-6
BuyLog™ Catalog
www.geindustrial.com
Rev. 11/13
Data subject to change
without notice
Surge Protection Device (SPD)
Section 5
Critical Power Products
Integrated Tranquell™ HE and ME
Designed for GE Distribution Equipment
For GE Switch Gear Distribution Equipment
200 kA Symmetrical Fault Withstand
Panelboard, Lights, Alarm, Surge Counter, Form C Contacts
Maximum Surge Current
100kA per mode / 200kA per phase
100kA per mode / 200kA per phase
100kA per mode / 200kA per phase
100kA per mode / 200kA per phase
100kA per mode / 200kA per phase
100kA per mode / 200kA per phase
100kA per mode / 200kA per phase
100kA per mode / 200kA per phase
100kA per mode / 200kA per phase
150kA per mode / 300kA per phase
150kA per mode / 300kA per phase
150kA per mode / 300kA per phase
150kA per mode / 300kA per phase
150kA per mode / 300kA per phase
150kA per mode / 300kA per phase
150kA per mode / 300kA per phase
150kA per mode / 300kA per phase
150kA per mode / 300kA per phase
200kA per mode / 400kA per phase
200kA per mode / 400kA per phase
200kA per mode / 400kA per phase
200kA per mode / 400kA per phase
200kA per mode / 400kA per phase
200kA per mode / 400kA per phase
200kA per mode / 400kA per phase
200kA per mode / 400kA per phase
200kA per mode / 400kA per phase
300kA per mode / 600kA per phase
300kA per mode / 600kA per phase
300kA per mode / 600kA per phase
300kA per mode / 600kA per phase
300kA per mode / 600kA per phase
300kA per mode / 600kA per phase
300kA per mode / 600kA per phase
300kA per mode / 600kA per phase
300kA per mode / 600kA per phase
Product Number
TPHE120S10SG
TPHE120Y10SG
TPHE220Y10SG
TPHE277Y10SG
TPHE480D10SG
TPHE347Y10SG
TPHE240H10SG
TPHE240D10SG
TPHE240Y10SG
TPHE120S15SG
TPHE120Y15SG
TPHE220Y15SG
TPHE277Y15SG
TPHE480D15SG
TPHE347Y15SG
TPHE240H15SG
TPHE240D15SG
TPHE240Y15SG
TPHE120S20SG
TPHE120Y20SG
TPHE220Y20SG
TPHE277Y20SG
TPHE480D20SG
TPHE347Y20SG
TPHE240H20SG
TPHE240D20SG
TPHE240Y20SG
TPHE120S30SG
TPHE120Y30SG
TPHE220Y30SG
TPHE277Y30SG
TPHE480D30SG
TPHE347Y30SG
TPHE240H30SG
TPHE240D30SG
TPHE240Y30SG
*
*
Product #
Voltage Protection Rating (VPR)
UL 1449, 3rd Edition
September 2009 Revision
System
Nominal
Voltage
Voltage
(Volts RMS) Configuration L-N
HL-N
L-G
HL-G
N-G
L-L
PP suffix available for all kA ratings
(integral to Spectra™ panel or switchboard)
SG suffix for all THE devices (100kA - 300kA)
integral to switchgear
ME suffix available for all kA ratings (integral to MCC)
Maximum Surge
Current Capacity
MCOV %
Max.
Continuous
Operating
Voltage
Exposure Level
Per Mode
Per Phase
06
TPME
65kA
130kA
TPHE
120S
120/240
1 Ph, 3 W + G
900
—
800
—
700 1200
125%
08
TPME
80KA
160KA
TPME
120Y
120Y/208
3 Ph, 4 W + G
900
—
800
—
700 1200
125%
10
TPME
100kA
200kA
1200 2000
220Y
220Y/380
3 Ph, 4 W + G 1500
—
1200
—
240D
240 Delta
3 Ph, 3 W + G
—
1200
—
240H
120/240 Delta HL
—
3 Ph, 4 W + G 1000 1200 800
1200
145%
12
TPHE
125kA
250kA
1800
196%
15
TPHE
150kA
300kA
700 2000
115%
20
TPHE
200kA
400kA
25
TPHE
250kA
500kA
30
TPHE
200kA
400kA
—
240Y
240Y/415
3 Ph, 4 W + G 1500
—
1200
—
1200 2000
130%
277Y
277Y/480
3 Ph, 4 W + G 1500
—
1200
—
1200 2000
115%
347Y
347Y/600
3 Ph, 4 W + G 1500
480D
480 Delta
3 Ph, 3 W + G
—
—
1500
—
—
1800
—
1500 2500
—
3000
115%
198%
Also available in 600D configurations. For details, please contact GE Power Quality Customer Service at 800 637-1738.
Rev. 11/13
Data subject to change
without notice
www.geindustrial.com
NOTE: For TVSS field installation kit, add the prefix “A”
and replace “PP” suffix with “K” suffix
Product # Example
TPHE277Y15PP
ATHE277Y15K
BuyLog™ Catalog
(factory installed)
(field installation)
5-7
Surge Protection Device (SPD)
Section 5
Critical Power Products
Tranquell™ 9X and 24X
Box Extensions Designed for GE “A Series™” Distribution Equipment
This SPD model is installed in an extended box and connects to
the "A Series™" Panelboard without adding width or depth to the
panel enclosure and is ideal for aftermarket installations. These
units have been tested to surge current ratings per NEMA LS-1,
up to 200 kA per mode, including the fuses in the surge path.
Standard features include a surge counter, audible alarm,
indicating lights, dry contacts. Rating options range from 65 kA
per mode to 300 kA per mode.
All mode protection is provided with surge components (MOVs)
connected on the phase-to-neutral, phase-to-ground, and neutralto-ground paths as appropriate for the voltage configuration.
Tranquell™ 9X and 24X products are engineered for reliability,
flexibility and long life in the most extreme surge environments.
The true maximum surge current rating, unlimited by fusing, has
been proven successful in 3rd party tests.
Features and Benefits
—UL1449, 3rd Edition
—UL Tested to 200,000 Amperes Symmetrical Withstand for 24X
—UL Tested to 65,000 Amperes Symmetrical Withstand for 9X
—Field Installed with "A Series™" panels
—Tranquell™ ME Device is Capable of Surviving a minimum of
5,000 Category C3 Impulses (10kA, 20kV) per mode.
—Tranquell™ HE Device is Capable of Surviving a minimum of
20,000 Category C3 Impulses (10kA, 20kV) per mode.
—Device Capable of Surviving a minimum of 5,000 Longwave
(10x1000µs) Impulses per mode.
—Form C Dry Contacts for Remote Monitoring
—Green Status Indicating Lights, Red Service Light
—Audible Alarm with Test/Disable Feature
—Surge Counter
—Standard 5 year limited warranty, Optional 20 year warranty
Specifications
Operating Frequency:
Connection:
Operating Temperature:
Operating Humidity:
Weight:
5-8
50/60 Hz
6 to 2/0 Conductors, Parallel Connected
-40°C to +65°C
0% to 95% Non-Condensing
9X - 30 lbs., 12X - 52 lbs.
BuyLog™ Catalog
www.geindustrial.com
Rev. 11/13
Data subject to change
without notice
Surge Protection Device (SPD)
Section 5
Critical Power Products
Tranquell™ 9X and 24X
Box Extensions Designed for GE “A Series™” Distribution Equipment
21.500
[546.10]
6.023
[152.98]
20.250
[514.35]
6.023
[152.984]
9.000
[228.60]
9.000
[228.6]
10.440
[265.18]
9.810
[249.174]
0.042
[1.067]
0.588
[14.94]
1.719
[43.675]
1.719
[43.67]
0.344 [8.738]
0.344 [8.74]
7.375
[187.338]
10.000
[254]
12.6255
[320.69]
15.400
[391.16]
7.375
[187.34]
10.000
[254.00]
12.625
[320.69]
15.400
[391.16]
BX9F Dimensions
BX9S Dimensions
21.500
[546.100]
20.250
[514.350]
6.023
[152.984]
9.000
[228.600]
6.412
[162.865]
6.023
[152.984]
9.000
[228.600]
7.042
[178.867]
9.810
[249.174]
10.440
[265.176]
1.617
[41.072]
7.239
[183.871]
0.588
[14.935]
2.247
[57.074]
6.609
[167.869]
13.624
[346.050]
14.254
[362.052]
2.389
[60.693]
2.389
[60.693]
0.344 [8.738]
7.375
[187.338]
10.000
[254.000]
12.625
[320.688]
15.400
[391.160]
15.400
[391.160]
BX9WF Dimensions
7.085
[179.95]
6.333
[160.86]
12.560
[319.02]
5.390
[136.91]
BX9WS Dimensions
6.074
[154.28]
6.899
[175.23]
7.624
[193.65]
7.085
[179.954]
6.810
[172.97]
6.333
[160.858]
0.711
[18.06]
21.500
[546.10]
20.280
[515.11]
[8.738] 0.344
7.375
[187.338]
10.000
[254.000]
12.625
[320.688]
1.400
[35.56]
8.030
[203.96]
11.940
[303.276]
6.274
[159.360]
8.635
[219.33]
20.280
[515.112]
6.810
[172.969]
0.711
[18.059]
5.390
[136.906]
8.030
[203.962]
6.074
[154.280]
8.635
[219.329]
11.635
[295.529]
7.624
[193.650]
1.400
[35.560]
3.176
[80.67]
24.000
[609.60]
7.246 [184.048]
25.440
[646.18]
Data subject to change
without notice
3.176
[80.672]
7.246
[184.044]
24.743
[628.47]
Rev. 11/13
24.000
[609.600]
24.743
[628.472]
BX24WF Dimensions
BX24WS Dimensions
www.geindustrial.com
BuyLog™ Catalog
5-9
Surge Protection Device (SPD)
Section 5
Critical Power Products
Tranquell™ 9X and 24X
Box Extensions Designed for GE “A Series™” Distribution Equipment
Tranquell™ 9X Box Extensions - 65 kA Symmetrical Fault Withstand
Maximum Surge Current
Enclosure Type
A
Series™
Extension Flush Mount
A
Series™
Extension Flush Mount
A
Series™
Extension Flush Mount
A
Series™
Extension Flush Mount
A
Series™
Extension Flush Mount
100kA per mode / 200kA per phase
A
Series™
Extension Flush Mount
65kA per mode / 130kA per phase
A
Series™
Extension Surface Mount
A
Series™
Extension Surface Mount
A
Series™
Extension Surface Mount
A
Series™
Extension Surface Mount
A
Series™
Extension Surface Mount
A
Series™
Extension Surface Mount
65kA per mode / 130kA per phase
80kA per mode / 160kA per phase
100kA per mode / 200kA per phase
65kA per mode / 130kA per phase
80kA per mode / 160kA per phase
80kA per mode / 160kA per phase
100kA per mode / 200kA per phase
65kA per mode / 130kA per phase
80kA per mode / 160kA per phase
100kA per mode / 200kA per phase
Description
9" Box Ext,Flush Mount, Lights, Alarm,
Counter, Contacts
9" Box Ext,Flush Mount, Lights, Alarm,
Counter, Contacts
9" Box Ext,Flush Mount, Lights, Alarm,
Counter, Contacts
9" Box Ext,Flush Mount, DisplayAccess,
Lights, Alarm, Counter, Contacts
9" Box Ext,Flush Mount, DisplayAccess,
Lights, Alarm, Counter, Contacts
9" Box Ext,Flush Mount, DisplayAccess,
Lights, Alarm, Counter, Contacts
9" Box Ext,Surface Mount, Lights, Alarm,
Counter, Contacts
9" Box Ext,Surface Mount, Lights, Alarm,
Counter, Contacts
9" Box Ext,Surface Mount, Lights, Alarm,
Counter, Contacts
9" Box Ext,Surface Mount, Access Display,
Lights, Alarm, Counter, Contacts
9" Box Ext,Surface Mount, Access Display,
Lights, Alarm, Counter, Contacts
9" Box Ext,Surface Mount, Access Display,
Lights, Alarm, Counter, Contacts
Product Number
TPMEXXXX06BX9F
TPMEXXXX08BX9F
TPMEXXXX10BX9F
TPMEXXXX06BX9WF
TPMEXXXX08BX9WF
TPMEXXXX10BX9WF
TPMEXXXX06BX9S
TPMEXXXX08BX9S
TPMEXXXX10BX9S
TPMEXXXX06BX9WS
TPMEXXXX08BX9WS
TPMEXXXX10BX9WS
Note: Replace XXXX in Product Number with nomenclature for Nominal Voltage (Volts RMS).
Tranquell™ 24X Box Extensions - 65kA Symmetrical Fault Withstand
Maximum Surge Current
Enclosure Type
A
Series™
Extension Flush Mount
A
Series™
Extension Flush Mount
100kA per mode / 200kA per phase
A
Series™
Extension Flush Mount
65kA per mode / 130kA per phase
A
Series™
Extension Surface Mount
A
Series™
Extension Surface Mount
A
Series™
Extension Surface Mount
65kA per mode / 130kA per phase
80kA per mode / 160kA per phase
80kA per mode / 160kA per phase
100kA per mode / 200kA per phase
Description
24" Box Ext,Flush Mount, DisplayAccess,
Lights, Alarm, Counter, Contacts
24" Box Ext,Flush Mount, DisplayAccess,
Lights, Alarm, Counter, Contacts
24" Box Ext,Flush Mount, DisplayAccess,
Lights, Alarm, Counter, Contacts
24" Box Ext,Surface Mount, DisplayAccess,
Lights, Alarm, Counter, Contacts
24" Box Ext,Surface Mount, DisplayAccess,
Lights, Alarm, Counter, Contacts
24" Box Ext,Surface Mount, DisplayAccess,
Lights, Alarm, Counter, Contacts
Product Number
TPMEXXXX06BX24WF
TPMEXXXX08BX24WF
TPMEXXXX10BX24WF
TPMEXXXX06BX24WS
TPMEXXXX08BX24WS
TPMEXXXX10BX24WS
Note: Replace XXXX in Product Number with nomenclature for Nominal Voltage (Volts RMS).
Tranquell™ 24X Box Extensions - 200kA Symmetrical Fault Withstand
Maximum Surge Current
Enclosure Type
100kA per mode / 200kA per phase
A Series™ Extension Surface Mount
150kA per mode / 300kA per phase
A Series™ Extension Surface Mount
200kA per mode / 400kA per phase
A Series™ Extension Surface Mount
300kA per mode / 600kA per phase
A Series™ Extension Surface Mount
100kA per mode / 200kA per phase
A Series™ Extension Flush Mount
150kA per mode / 300kA per phase
A Series™ Extension Flush Mount
200kA per mode / 400kA per phase
A Series™ Extension Flush Mount
300kA per mode / 600kA per phase
A Series™ Extension Flush Mount
Description
24" Box Ext,Surface Mount, DisplayAccess,
Lights, Alarm, Counter, Contacts
24" Box Ext,Surface Mount, DisplayAccess,
Lights, Alarm, Counter, Contacts
24" Box Ext,Surface Mount, DisplayAccess,
Lights, Alarm, Counter, Contacts
24" Box Ext,Surface Mount, DisplayAccess,
Lights, Alarm, Counter, Contacts
24" Box Ext,Flush Mount, DisplayAccess,
Lights, Alarm, Counter, Contacts
24" Box Ext,Flush Mount, DisplayAccess,
Lights, Alarm, Counter, Contacts
24" Box Ext,Flush Mount, DisplayAccess,
Lights, Alarm, Counter, Contacts
24" Box Ext,Flush Mount, DisplayAccess,
Lights, Alarm, Counter, Contacts
Product Number
TPHEXXXX10BX24WS
TPHEXXXX15BX24WS
TPHEXXXX20BX24WS
TPHEXXXX30BX24WS
TPHEXXXX10BX24WF
TPHEXXXX15BX24WF
TPHEXXXX20BX24WF
TPHEXXXX30BX24WF
Note: Replace XXXX in Product Number with nomenclature for Nominal Voltage (Volts RMS).
5-10
BuyLog™ Catalog
www.geindustrial.com
Rev. 11/13
Data subject to change
without notice
Surge Protection Device (SPD)
Section 5
Critical Power Products
Tranquell™ 9X and 24X
Box Extensions Designed for GE “A Series™” Distribution Equipment
ME – Medium Exposure Level
* 9S
T
Product #
P
- Surface mounted, no display
9WS - Surface mounted, display access
9F - Flush mounted , no display
9WF - Flush mounted, display access
X *
B
ME – Medium Exposure &
HE – High Exposure Level
* 24WS
- Surface mounted, display access
24WF - Flush mounted, display access
Nominal
System
Voltage
Voltage
(Volts RMS) Configuration
MCOV %
Max.
Continuous
Operating
Voltage
Maximum Surge
Current Capacity
Exposure
Level
ME
120S
120/240
1 Ph, 3 W + G
125%
06
ME
HE
120Y
120Y/208
3 Ph, 4 W + G
125%
08
220Y
220Y/380
3 Ph, 4 W + G
145%
10
240D
240 Delta
3 Ph, 3 W + G
115%
240H
120/240 Delta HL
3 Ph, 4 W + G
240Y
240Y/415
277Y
347Y
480D
Per Mode Per Phase
65kA
130kA
ME
80kA
160kA
ME
100kA
200kA
12
HE
125kA
250kA
115%
15
HE
150kA
300kA
3 Ph, 4 W + G
130%
20
HE
200kA
400kA
277Y/480
3 Ph, 4 W + G
115%
25
HE
250kA
500kA
347Y/600
3 Ph, 4 W + G
115%
30
HE
300kA
600kA
480 Delta
3 Ph, 3 W + G
170%
Product # Example
Phase Rating = (L-N + L-G)
Also available in 600D configurations. For details, please
contact GE Power Quality Customer Service at
800 637 1738.
TPHE277Y15BX24WF
—277Y/480 V, 3 Ph, 4 W + G
—150kA per mode
—Flush mounted, display access
Voltage Protection Rating (VPR)
UL 1449, 3rd Edition — September 2009 Revision
BX9
L-N
HL-N
L-G
HL-G
120S 1500
—
1500
—
120Y 1500
—
1500
220Y 1800
—
240D
—
—
BX24
N-G
L-L
L-N
HL-N
L-G
HL-G
900 1800
1500
—
1500
—
1000 1800
—
900 1800
1500
—
1500
—
1000 1800
2000
—
1500 2500
1800
—
1800
—
1500 2500
1800
—
—
—
1800
—
—
2500
N-G
—
L-L
2500
240H 1500 1800 1500 2000 900 1800
1500 1800 1500 1800 1000 1800
240Y 1800
—
2000
—
1500 2500
1800
—
1800
—
1500 2500
277Y 1800
—
2000
—
1500 2500
1800
—
1800
—
1500 2500
347Y 2000
—
2000
—
1800 3000
3000
—
2500
—
1800 3000
480D
—
2500
—
—
—
2500
—
Rev. 11/13
Data subject to change
without notice
—
—
4000
www.geindustrial.com
—
4000
BuyLog™ Catalog
5-11
Surge Protection Device (SPD)
Section 5
Critical Power Products
Tranquell™ HE and ME
Wall Mount
These devices are available in a standard NEMA 12 enclosure.
Optional enclosure types include NEMA 12 and 4X, flushmount,
surface mount and stainless steel. These units have been tested
to surge current ratings per NEMA LS-1, up to 200kA per mode,
including the fuses in the surge path. Standard features include
a surge counter, audible alarm, indicating lights, dry contacts, and
an integral surge rated disconnect (WMN1 and WMN4 only).
Rating options range from 65kA per mode to 300 kA per mode.
All mode protection is provided with surge components (MOVs)
connected on the phase to neutral, phase to ground, and neutral
to ground paths as appropriate for the voltage configuration.
Tranquell™ HE and ME products are engineered for reliability,
flexibility and long life in the most extreme surge environment.
The true maximum surge current rating, unlimited by fusing, has
been proven successful in 3rd party tests.
Features and Benefits
—UL1449, 3rd Edition CUL, UL1283
—UL Tested to 200,000 Amperes Symmetrical Withstand
—Integral Surge Rated Disconnect
—Tranquell™ ME Device is Capable of Surviving a minimum of
5,000 Category C3 Impulses (10kA, 20kV) per mode.
—Tranquell™ HE Device is Capable of Surviving a minimum of
20,000 Category C3 Impulses (10kA, 20kV) per mode.
—Device Capable of Surviving a minimum of 5,000 Longwave
(10x1000µs) Impulses per mode.
—Patented Thermal Fuse Technology in Combination with Surge
Rated Fuses
—Form C Dry Contacts for Remote Monitoring
—Green Status Indicating Lights, Red Service Light
—Audible Alarm with Test/Disable Feature
—Surge Counter
—Standard 10 year limited warranty, Optional 20 year warranty
Specifications
Operating Frequency:
Connection:
Operating Temperature:
Operating Humidity:
Weight:
50/60 Hz
6 to 2/0 Conductors, Parallel Connected
-40°C to +65°C
0% to 95% Non-Condensing
50 lbs.: (THE), 32 lbs. (TME)
*Must be installed downstream from breaker 60 Amp or less.
12.000
[304.80]
15.330
[389.38]
0.282
[
7.16] HOLES
(8 PLACES)
8.978
[228.04]
12.015
[305.18]
14.759
[374.88]
13.478
[342.34]
1.852
[47.04]
0.571
[14.50]
[
0.440
11.18] HOLE
(2 PLACES)
0.625
[15.87]
18.759
[476.48]
16.000
[406.40]
15.478
[393.14]
3.852
[97.84]
26.500
[673.10]
24.000
[609.60]
0.571
[14.50]
1.471
[37.36]
6.440
[163.58]
19.330
[490.98]
15.330
[389.38]
0.625
[15.87]
8.978
[228.04]
9.276
[235.61]
1.250
[31.75]
12.000
[304.80]
12.000
[304.80]
WMN12F Dimensions
5-12
BuyLog™ Catalog
10.750
[273.05]
0.440
[ 11.18]
(2 PLACES)
WMN1 Dimensions
www.geindustrial.com
Rev. 11/13
Data subject to change
without notice
Surge Protection Device (SPD)
Section 5
Critical Power Products
Tranquell™ HE and ME
Wall Mount
Wall Mount Tranquell™ ME - 200kA Symmetrical Fault Withstand – Lights, Alarm, Surge Counter, Form C Contacts
Maximum Surge Current
65kA per mode / 130kA per phase
80kA per mode / 160kA per phase
100kA per mode / 200kA per phase
65kA per mode / 130kA per phase
80kA per mode / 160kA per phase
100kA per mode / 200kA per phase
65kA per mode / 130kA per phase
80kA per mode / 160kA per phase
100kA per mode / 200kA per phase
65kA per mode / 130kA per phase
80kA per mode / 160kA per phase
100kA per mode / 200kA per phase
65kA per mode / 130kA per phase
80kA per mode / 160kA per phase
100kA per mode / 200kA per phase
65kA per mode / 130kA per phase
80kA per mode / 160kA per phase
100kA per mode / 200kA per phase
Enclosure Type
Product Number
NEMA 12 Flush
NEMA 12 Flush
NEMA 12 Flush
NEMA 12 Surface, Integral Disconnect
NEMA 12 Surface, Integral Disconnect
NEMA 12 Surface, Integral Disconnect
NEMA 12 Surface
NEMA 12 Surface
NEMA 12 Surface
NEMA 4 Painted Steel Surface
NEMA 4 Painted Steel Surface
NEMA 4 Painted Steel Surface
NEMA 4X Fiberglass, Integral Disconnect
NEMA 4X Fiberglass, Integral Disconnect
NEMA 4X Fiberglass, Integral Disconnect
NEMA 4X Stainless Steel
NEMA 4X Stainless Steel
NEMA 4X Stainless Steel
TMEXXXX065WMN12F
TMEXXXX080WMN12F
TMEXXXX100WMN12F
TMEXXXX065WMN1
TMEXXXX080WMN1
TMEXXXX100WMN1
TMEXXXX065WMN12S
TMEXXXX080WMN12S
TMEXXXX100WMN12S
TMEXXXX065WMN4S
TMEXXXX080WMN4S
TMEXXXX100WMN4S
TMEXXXX065WMN4
TMEXXXX080WMN4
TMEXXXX100WMN4
TMEXXXX065WMN4X
TMEXXXX080WMN4X
TMEXXXX100WMN4X
Note: Replace XXXX in Product Number with nomenclature for Nominal Voltage (Volts RMS).
Wall Mount Tranquell™ HE - 200kA Symmetrical Fault Withstand – Lights, Alarm, Surge Counter, Form C Contacts
Maximum Surge Current
100kA per mode / 200kA per phase
150kA per mode / 300kA per phase
200kA per mode / 400kA per phase
300kA per mode / 600kA per phase
100kA per mode / 200kA per phase
150kA per mode / 300kA per phase
200kA per mode / 400kA per phase
300kA per mode / 600kA per phase
100kA per mode / 200kA per phase
150kA per mode / 300kA per phase
200kA per mode / 400kA per phase
300kA per mode / 600kA per phase
100kA per mode / 200kA per phase
150kA per mode / 300kA per phase
200kA per mode / 400kA per phase
300kA per mode / 600kA per phase
100kA per mode / 200kA per phase
150kA per mode / 300kA per phase
200kA per mode / 400kA per phase
300kA per mode / 600kA per phase
100kA per mode / 200kA per phase
150kA per mode / 300kA per phase
200kA per mode / 400kA per phase
300kA per mode / 600kA per phase
Enclosure Type
Product Number
NEMA 12 Flush
NEMA 12 Flush
NEMA 12 Flush
NEMA 12 Flush
NEMA 12 Surface, Integral Disconnect
NEMA 12 Surface, Integral Disconnect
NEMA 12 Surface, Integral Disconnect
NEMA 12 Surface, Integral Disconnect
NEMA 12 Surface
NEMA 12 Surface
NEMA 12 Surface
NEMA 12 Surface
NEMA 4 Painted Steel Surface
NEMA 4 Painted Steel Surface
NEMA 4 Painted Steel Surface
NEMA 4 Painted Steel Surface
NEMA 4X Fiberglass, Integral Disconnect
NEMA 4X Fiberglass, Integral Disconnect
NEMA 4X Fiberglass, Integral Disconnect
NEMA 4X Fiberglass, Integral Disconnect
NEMA 4X Stainless Steel
NEMA 4X Stainless Steel
NEMA 4X Stainless Steel
NEMA 4X Stainless Steel
THEXXXX100WMN12F
THEXXXX150WMN12F
THEXXXX200WMN12F
THEXXXX300WMN12F
THEXXXX100WMN1
THEXXXX150WMN1
THEXXXX200WMN1
THEXXXX300WMN1
THEXXXX100WMN12S
THEXXXX150WMN12S
THEXXXX200WMN12S
THEXXXX300WMN12S
THEXXXX100WMN4S
THEXXXX150WMN4S
THEXXXX200WMN4S
THEXXXX300WMN4S
THEXXXX100WMN4
THEXXXX150WMN4
THEXXXX200WMN4
THEXXXX300WMN4
THEXXXX100WMN4X
THEXXXX150WMN4X
THEXXXX200WMN4X
THEXXXX300WMN4X
Note: Replace XXXX in Product Number with nomenclature for Nominal Voltage (Volts RMS).
Rev. 11/13
Data subject to change
without notice
www.geindustrial.com
BuyLog™ Catalog
5-13
Surge Protection Device (SPD)
Section 5
Critical Power Products
Tranquell™ HE and ME
Wall Mount
WM N
Product #
Nominal
Voltage
(Volts RMS)
System
Voltage
Configuration
Voltage Protection Rating (VPR)
UL 1449, 3rd Edition
September 2009 Revision
L–N
HL–N
L–G
HL–G
THE
120S
120/240
1 Ph, 3W + G 1000
—
1000
TME
120Y
120Y/208
3 Ph, 4W + G 1000
—
1000
—
-—
220Y
220Y/380
3 Ph, 4W + G 1500
—
1500
—
HL-L
MCOV %
Max.
Continuous
Operating
Voltage
700 1200
-—
125%
700 1200
—
125%
065
ME
65kA 130kA
1000 2000
—
145%
080
ME
80kA 160kA
N–G
L-L
240D
Exposure
Level
Per
Mode
Per
Phase
240 Delta
3 Ph, 4W
—
— 1500 —
— 1800 —
240H 120/240 Delta HL 3 Ph, 4W + G 1000 1500 1000 1500 700 1200 2500
196%
100
ME
100kA 200kA
115%
125
HE
125kA 250kA
240Y
240Y/415
3 Ph, 4W + G 1500
—
1500
—
1000 2000
—
130%
150
HE
150kA 300kA
277Y
277Y/480
3 Ph, 4W + G 1500
—
1500
—
1000 2000
—
115%
200
HE
200kA 400kA
347Y
347Y/600
3 Ph, 4W + G 1800
—
1500
—
1500 2500
—
115%
250
HE
250kA 500kA
480D
480 Delta
3 Ph, 4W
—
2000
—
4000
—
198%
300
HE
300kA 600kA
Product # Example
THE277Y150WMN12S
5-14
Maximum Surge
Current Capacity
BuyLog™ Catalog
—
—
Suffix
Description
NEMA
Enclosure
Mounting
Disconnect
1
Painted Steel
1
Surface
Yes
12S
Painted Steel
12
Surface
No
12F
Painted Steel
12
Flush
No
4
Fiberglass
4X
Surface
Yes
4S
Painted Steel
4
Surface
No
4X
Stainless Steel
4X
Surface
No
www.geindustrial.com
Rev. 11/13
Data subject to change
without notice
Surge Protection Device (SPD)
Section 5
Critical Power Products
Tranquell™ HE and ME
Wall Mount, with Enhanced Thermal Protection
Introduction
Recommended installation locations are primary and secondary
distribution and point of use levels. Designed for distribution and
point of use locations, but rated for service entrance, the
Tranquell™ HE and ME with enhanced thermal protection has
been third-party tested to ANSI/IEEE C3 10kA 8x20µs impulses.
The entire Tranquell™ HE and ME line-up has been engineered to
the highest standards and is designed for rigorous duty and long
life, as evidenced in our outstanding minimum repetitive surge
current capacity test results.
These devices are available in a standard NEMA 12 enclosure.
Optional enclosure types from NEMA 12 – NEMA 4x include flush
mount, surface mount, fiberglass and stainless steel.
These units have been tested to surge current ratings per NEMA
LS-1, up to 200kA per mode, 400kA per phase. Standard features
include a surge counter, audible alarm, indicating lights, dry
contacts, and an integral surge rated disconnect. Rating options
range from 65kA – 300kA per mode, 130kA – 600kA per phase.
GE engineers design and build transient voltage surge suppressors in our state-of-the-art lab and production facilities. Extensive
testing is performed at GE and third-party test labs across North
America. Production is carried out at our factory in Bonham, Texas
utilizing Six Sigma, ISO 9001 methodologies and lean
manufacturing processes.
Features and Benefits
Specifications
Operating Frequency
50/60 Hz
Connection
6 to 2/0 Conductors, Parallel Connected
Operating Temperature
-40° F to 140° F (-40° C to +65° C)
Operating Humidity
0% to 95% Non-Condensing
Weight
NEMA Enclosure Suffix:
1
63 lbs. (28.5 kg)
4
56 lbs. (25.4 kg)
4S, 12S, 12F
44 lbs. (20.0 kg)
4X
50 lbs. (22.7 kg)
—UL 1449 3rd Edition, September 2009, cUL
—UL 1283 noise filtering. The TVSS device EMI-RFI noise rejection
or attenuation value is measured in accordance with the
procedures outlined in NEMA LS 1-1992 (R2000)/MIL–STD-220B.
Attenuation is -50db minimum @ 100kHz.
—UL tested to 200,000 amperes symmetrical withstand
—Integral surge rated disconnect
—Tranquell™ ME device is capable of surviving a minimum of
5,000 category C3 impulses (10kA, 20kV) per mode
—Tranquell™ HE device is capable of surviving a minimum of
20,000 category C3 impulses (10kA, 20kV) per mode
—Thermally protected MOVS eliminate the need for additional
upstream fuses
—NO/NC Form C dry type contacts for remote monitoring
—Green status indicating lights, red service light
—Audible alarm with test/disable feature
—Standard LCD surge counter
—10 year limited warranty (standard),
20 year limited warranty (optional)
Rev. 11/13
Data subject to change
without notice
www.geindustrial.com
BuyLog™ Catalog
5-15
Surge Protection Device (SPD)
Section 5
Critical Power Products
Tranquell™ HE and ME
Wall Mount, with Enhanced Thermal Protection
12.000
[304.80]
20.000
[508.00]
12.015
[305.18]
12.651
[321.34]
0.440
[ 11.18] HOLE
(2 PLACES)
0.625
[15.87]
26.500
[673.10]
24.000
[609.60]
25.500
[647.70]
24.000
[609.60]
0.625
[15.87]
9.276
[235.61]
1.250
[31.75]
0.440
[ 11.18]
(2 PLACES)
10.750
[273.05]
12.000
[304.80]
21.500
[546.10]
9.912
[251.76]
WMN4 Dimensions
WMN1 Dimensions
15.330
[389.38]
[
0.282
7.16] HOLES
(8 PLACES)
8.978
[228.04]
14.759
[374.88]
13.478
[342.34]
1.852
[47.04]
[
9.226
[234.33]
10.399
[264.14]
0.380
9.65] HOLE
(4 PLACES)
0.571
[14.50]
18.759
[476.48]
16.000
[406.40]
15.478
[393.14]
19.118
[485.61]
19.330
[490.98]
17.659
[448.53]
3.852
[97.84]
0.571
[14.50]
1.471
[37.36]
1.475
[37.46]
15.330
[389.38]
6.440
[163.58]
6.439
[163.56]
11.999
[304.77]
8.978
[228.04]
9.226
[234.33]
12.000
[304.80]
WMN12S, WMN4S, WMN4X Dimensions
WMN12F Dimensions
Wall Mount Tranquell™ ME - 200kA Symmetrical Fault Withstand – Lights, Alarm, Surge Counter, Form C Contacts
Maximum Surge Current
65kA per mode / 130kA per phase
80kA per mode / 160kA per phase
100kA per mode / 200kA per phase
65kA per mode / 130kA per phase
80kA per mode / 160kA per phase
100kA per mode / 200kA per phase
65kA per mode / 130kA per phase
80kA per mode / 160kA per phase
100kA per mode / 200kA per phase
65kA per mode / 130kA per phase
80kA per mode / 160kA per phase
100kA per mode / 200kA per phase
65kA per mode / 130kA per phase
80kA per mode / 160kA per phase
100kA per mode / 200kA per phase
65kA per mode / 130kA per phase
80kA per mode / 160kA per phase
100kA per mode / 200kA per phase
Enclosure Type
Product Number
NEMA 12 Flush
NEMA 12 Flush
NEMA 12 Flush
NEMA 12 Surface, Integral Disconnect
NEMA 12 Surface, Integral Disconnect
NEMA 12 Surface, Integral Disconnect
NEMA 12 Surface
NEMA 12 Surface
NEMA 12 Surface
NEMA 4 Painted Steel Surface
NEMA 4 Painted Steel Surface
NEMA 4 Painted Steel Surface
NEMA 4X Fiberglass, Integral Disconnect
NEMA 4X Fiberglass, Integral Disconnect
NEMA 4X Fiberglass, Integral Disconnect
NEMA 4X Stainless Steel
NEMA 4X Stainless Steel
NEMA 4X Stainless Steel
TPMEXXXX06WMN12F
TPMEXXXX08WMN12F
TPMEXXXX10WMN12F
TPMEXXXX06WMN1
TPMEXXXX08WMN1
TPMEXXXX10WMN1
TPMEXXXX06WMN12S
TPMEXXXX08WMN12S
TPMEXXXX10WMN12S
TPMEXXXX06WMN4S
TPMEXXXX08WMN4S
TPMEXXXX10WMN4S
TPMEXXXX06WMN4
TPMEXXXX08WMN4
TPMEXXXX10WMN4
TPMEXXXX06WMN4X
TPMEXXXX08WMN4X
TPMEXXXX10WMN4X
Note: Replace XXXX in Product Number with nomenclature for Nominal Voltage (Volts RMS).
5-16
BuyLog™ Catalog
www.geindustrial.com
Rev. 11/13
Data subject to change
without notice
Surge Protection Device (SPD)
Section 5
Critical Power Products
Tranquell™ HE and ME
Wall Mount, with Enhanced Thermal Protection
Wall Mount Tranquell™ HE - 200kA Symmetrical Fault Withstand – Lights, Alarm, Surge Counter, Form C Contacts
Maximum Surge Current
100kA per mode / 200kA per phase
150kA per mode / 300kA per phase
200kA per mode / 400kA per phase
300kA per mode / 600kA per phase
100kA per mode / 200kA per phase
150kA per mode / 300kA per phase
200kA per mode / 400kA per phase
300kA per mode / 600kA per phase
100kA per mode / 200kA per phase
150kA per mode / 300kA per phase
200kA per mode / 400kA per phase
300kA per mode / 600kA per phase
100kA per mode / 200kA per phase
150kA per mode / 300kA per phase
200kA per mode / 400kA per phase
300kA per mode / 600kA per phase
100kA per mode / 200kA per phase
150kA per mode / 300kA per phase
200kA per mode / 400kA per phase
300kA per mode / 600kA per phase
100kA per mode / 200kA per phase
150kA per mode / 300kA per phase
200kA per mode / 400kA per phase
300kA per mode / 600kA per phase
Enclosure Type
Product Number
NEMA 12 Flush
NEMA 12 Flush
NEMA 12 Flush
NEMA 12 Flush
NEMA 12 Surface, Integral Disconnect
NEMA 12 Surface, Integral Disconnect
NEMA 12 Surface, Integral Disconnect
NEMA 12 Surface, Integral Disconnect
NEMA 12 Surface
NEMA 12 Surface
NEMA 12 Surface
NEMA 12 Surface
NEMA 4 Painted Steel Surface
NEMA 4 Painted Steel Surface
NEMA 4 Painted Steel Surface
NEMA 4 Painted Steel Surface
NEMA 4X Fiberglass, Integral Disconnect
NEMA 4X Fiberglass, Integral Disconnect
NEMA 4X Fiberglass, Integral Disconnect
NEMA 4X Fiberglass, Integral Disconnect
NEMA 4X Stainless Steel
NEMA 4X Stainless Steel
NEMA 4X Stainless Steel
NEMA 4X Stainless Steel
TPHEXXXX10WMN12F
TPHEXXXX15WMN12F
TPHEXXXX20WMN12F
TPHEXXXX30WMN12F
TPHEXXXX10WMN1
TPHEXXXX15WMN1
TPHEXXXX20WMN1
TPHEXXXX30WMN1
TPHEXXXX10WMN12S
TPHEXXXX15WMN12S
TPHEXXXX20WMN12S
TPHEXXXX30WMN12S
TPHEXXXX10WMN4S
TPHEXXXX15WMN4S
TPHEXXXX20WMN4S
TPHEXXXX30WMN4S
TPHEXXXX10WMN4
TPHEXXXX15WMN4
TPHEXXXX20WMN4
TPHEXXXX30WMN4
TPHEXXXX10WMN4X
TPHEXXXX15WMN4X
TPHEXXXX20WMN4X
TPHEXXXX30WMN4X
Note: Replace XXXX in Product Number with nomenclature for Nominal Voltage (Volts RMS).
Product # T
Nominal
Voltage
(Volts RMS)
P
System
Voltage
Configuration
W M
Voltage Protection Rating (VPR)
UL 1449, 3rd Edition
September 2009
L–N
HL–N
L–G
HL–G
N–G
L–L
—
800
—
700 1200
N
MCOV %
HL–L
Max.
Continuous
Operating
Voltage
—
125%
06
ME
65kA
Maximum Surge
Current Capacity
ME
120S
120/240
1 Ph, 3W + G
900
HE
120Y
120Y/208
3 Ph, 4W + G
900
—
800
—
700 1200
—
125%
220Y
220Y/380
3 Ph, 4W + G 1500
—
1200
—
1200 2000
—
145%
08
ME
80kA
160kA
240D
240 Delta
3 Ph, 4W
—
1200
—
1800
—
196%
10
ME
100kA
200kA
—
—
Exposure Level Per Mode
Per Phase
130kA
240H 120/240 Delta HL 3 Ph, 4W + G 1000 1200 800 1200 700 2000 2200
115%
12
HE
125kA
250kA
240Y
240Y/415
3 Ph, 4W + G 1500
—
1200
—
1200 2000
—
130%
15
HE
150kA
300kA
277Y
277Y/480
3 Ph, 4W + G 1500
—
1200
—
1200 2000
—
115%
20
HE
200kA
400kA
347Y
347Y/600
3 Ph, 4W + G 1500 ---- 1500 ---- 1500 2500 ----
115%
25
HE
250kA
500kA
480D
480 Delta
3 Ph, 4W
198%
30
HE
300kA
600kA
----
---- 1800 ----
---- 3000 ----
Also available in 600D configurations. For details, please contact GE Power Quality
Customer Service at 800 637 1738.
Phase Rating = (L-N + L-G)
Product # Example
TPHE277Y15WMN12S
—277Y/480 V, 3 Ph, 4 W + G
—150kA per mode
—Surface mount enclosure
without disconnect
—Painted steel
Rev. 11/13
Data subject to change
without notice
www.geindustrial.com
Suffix
Description
NEMA
Enclosure
Mounting
Disconnect
1
Painted Steel
1
Surface
Yes
12S
Painted Steel
12
Surface
No
12F
Painted Steel
12
Flush
No
4
Fiberglass
4X
Surface
Yes
4S
Painted Steel
4
Surface
No
4X
Stainless Steel
4X
Surface
No
BuyLog™ Catalog
5-17
Surge Protection Device (SPD)
Section 5
Critical Power Products
Tranquell™ ME and LE
Wall Mount
The Tranquell™ ME and LE feature compact, economical, universal
designs for use at medium exposure, distribution or branch
panels and are available in a standard NEMA 12 enclosure. These
devices have been tested to surge current ratings per NEMA LS-1,
including the fuses in the surge path. These units come standard
with indicating lights and dry contacts. Ratings are available from
25kA per mode to 100kA per mode.
These surge protection devices provide all mode protection, with
surge components (MOVs) connected on the phase- to-neutral,
phase-to-ground, and neutral-to-ground paths as appropriate for
the voltage configuration.
Features and Benefits
—Universal design allows for easy retrofit installation
—UL1449, 3rd Edition cUL
—Tranquell™ ME devices with UL1283 Noise Filters
—UL Tested to 65,000 Amperes Symmetrical Withstand
—Tranquell™ ME Device is Capable of Surviving a minimum of
5,000 Category C3 Impulses (10kA, 20kV) per mode
—Tranquell™ ME Device Capable of Surviving a minimum of 5,000
Longwave (10x1000ms) Impulses per mode
—Tranquell™ LE Device is Capable of Surviving a minimum of
3,500 Category C3 Impulses (10kA, 20kV) per mode
—Form C Dry Contacts for Remote Monitoring
—Green Status Indicating Light(s)
—Standard 10 year limited warranty, Optional 20 year warranty
Specifications
Operating Frequency:
Connection:
Operating Temperature:
Operating Humidity:
Weight:
50/60 Hz
10 AWG Conductors, Parallel Connected
-40°C to +65°C
0% to 95% Non-Condensing
(TME) 19 lbs., (TLE) 11.4 lbs.
*Must be installed downstream from 60 Amp breaker or less.
TME
TLE
4.00
3/4" N.P.T.
6.75
6.25
7.50
6.25
4.37
2.85
1.55
6.00
5-18
BuyLog™ Catalog
www.geindustrial.com
Rev. 11/13
Data subject to change
without notice
Surge Protection Device (SPD)
Section 5
Critical Power Products
Tranquell™ ME and LE
Wall Mount
Wall Mount Tranquell™ ME and LE - 65 kA Symmetrical Fault Withstand
Maximum Surge Current
25 kA per mode / 50 kA per phase
50 kA per mode / 100 kA per phase
65 kA per mode / 130 kA per phase
80 kA per mode / 160 kA per phase
100 kA per mode / 200 kA per phase
Enclosure Type
Description
Product Number
NEMA 12
NEMA 12
NEMA 12
NEMA 12
NEMA 12
Lights, Form C Contacts
Lights, Form C Contacts
Lights, Form C Contacts
Lights, Form C Contacts
Lights, Form C Contacts
TLEXXXX025WM
TLEXXXX050WM
TMEXXXX065WM
TMEXXXX080WM
TMEXXXX100WM
Note: Replace XXXX in Product Number with nomenclature for Nominal Voltage (Volts RMS).
* Voltage Protection Rating, UL1449, 3rd Edition
** Maximum Continuous Operating Voltage
Product #
WM
TLE Voltage Protection Rating (VPR)
UL 1449, 3rd Edition
September 2009
HL–G
N–G
L–L
HL–L
—
600
1000
—
125%
—
600
1000
—
125%
—
1200
1800
—
145%
—
—
1800
—
196%
600
1000
600
1000
1800
115%
—
1000
—
1200
1800
—
130%
1200
—
1000
—
1200
1800
—
115%
—
—
1800
—
—
4000
—
198%
System
Voltage
Configuration
L–N
HL–N
L–G
—
600
—
600
—
1000
—
900
600
1200
3 Ph, 4W + G
1200
277Y/480
3 Ph, 4W + G
480 Delta
3 Ph, 4W
TLE
120S
120/240
1 Ph, 3W + G
600
TME
120Y
120Y/208
3 Ph, 4W + G
600
220Y
220Y/380
3 Ph, 4W + G
1200
240D
240 Delta
3 Ph, 4W
—
240H
120/240 Delta HL
3 Ph, 4W + G
240Y
240Y/415
277Y
480D
Rev. 11/13
Data subject to change
without notice
www.geindustrial.com
MCOV %
Max.
Continuous
Operating
Voltage
Nominal
Voltage
(Volts RMS)
025
25kA per mode
50 kA per phase
(TLE)
050
50kA per mode
100 kA per phase
(TLE)
065
65 kA per mode
130 kA per phase
(TME)
080
80 kA per mode
160 kA per phas e
(TME)
100
100 kA per mode
200 kA per phase
(TME)
BuyLog™ Catalog
5-19
Surge Protection Device (SPD)
Section 5
Critical Power Products
Tranquell™ DIN Rail Mount
The full-featured Tranquell™ DIN Rail Mount SPD (Surge Protection
Device) is a Type 2 surge protection device that is modular and
easy to install. DIN Rail mount housing allows for quick installation. Each unit has a compact footprint and user-replaceable
phase surge pluggable modules with an IP20 finger-safe design.
Both visual indicators and remote indicators (dry contact) provide
SPD status to critical control circuits.
Features and Benefits
—Built-in thermal protection
—200kA interrupting rated
—DIN Rail mount
—Pluggable modules, finger-safe design – IP20 rating
—Built-in visual status indicator
—Remote indicator with 3 pin COM/NO/NC contacts
—Easy installation or retrofit
—Fail-safe / self-protected design
—Small footprint
—No external fusing or circuit breakers required
—Standard 5 year limited warranty, optional 20 year warranty
Dimensional Diagrams
3.89
98.9
.35
8.9
.60
15.2
.70
17.8
Poles
A
1-Pole
0.71 in [18 mm]
2-Pole
1.42 in [36 mm]
3-Pole
2.13 in [54 mm]
4-Pole
2.84 in [72 mm]
A
.15
3.9
Specifications
—UL1449, 3rd edition (September 2009)
—UL type 2 device
—RoHS compliant
—ANSI/IEEE C62.41
5-20
BuyLog™ Catalog
2.00
50.7
2.82
71.8
Microswitch
.44
11.1
NOTE:
All dimensions in the diagram above are for reference only
and are shown in Inches [millimeters]
www.geindustrial.com
Rev. 11/13
Data subject to change
without notice
Surge Protection Device (SPD)
Section 5
Critical Power Products
Tranquell™ DIN Rail Mount
Product Numbers and Specifications
Product Configuration
Nominal
Voltage
(50/60 Hz)
Product Number
TD120Y4025RMN
TD120Y4050RMN
TD277Y4025RMN
TD277Y4050RMN
TD347Y4025RMN
TD347Y4050RMN
TD240H4025RMN
TD240H4050RMN
TD480H4025RMN
TD480H4050RMN
TD120Y3025RMP
TD120Y3050RMP
TD277Y3025RMP
TD277Y3050RMP
TD347Y3025RMP
TD347Y3050RMP
TD240D3025RMP
TD240D3050RMP
TD480D3025RMP
TD480D3050RMP
TD120S2025RMP
TD120S2050RMP
TD240S2025RMP
TD240S2050RMP
TD120S1025RMP
TD120S1050RMP
TD240S1025RMP
TD240S1050RMP
TD277S1025RMP
TD277S1050RMP
TD347S1025RMP
TD347S1050RMP
No. of
Wires
120 / 208V
277 / 480V
347 / 600V
5-Wire /
4 Pole
120 / 240V
240 / 480V
120 / 208V
277 / 480V
347 / 600V
4-Wire /
3 Pole
240V
480V
120 / 208V,
120 / 240V
240 / 480V
3 Wire /
2 Pole
120V
240V
277V
2 Wire /
1 Pole
347V
Max Discharge
Current (Imax,
8/20 µs, kA)
25kA
50kA
25kA
50kA
25kA
50kA
25kA
50kA
25kA
50kA
25kA
50kA
25kA
50kA
25kA
50kA
25kA
50kA
25kA
50kA
25kA
50kA
25kA
50kA
25kA
50kA
25kA
50kA
25kA
50kA
25kA
50kA
Wiring
Configuration*
3 Phase Wye,
plus N-G
3 Phase
High Leg
Delta
3 Phase Wye,
common N/G
3 Phase Delta
Split Phase
Single Phase
UL Specifications
Nominal
Electrical
Discharge
Voltage
Current MCOV MCOV MCOV
Configuration** (In, kA) (Vc) L-L (Vc) L-G (Vc) L-N
20
360
360
180
20
360
360
180
20
640
500
320
Figure C
20
640
500
320
10
840
695
420
10
840
695
420
20
20
***
Figure E
10
10
—
20
360
180
20
360
—
180
20
640
320
Figure C
—
20
640
320
10
840
420
10
840
420
20
550
275
—
20
550
275
—
Figure D
10
1100
550
10
1100
550
—
20
360
180
20
360
—
180
Figure B
—
20
550
275
20
550
275
—
—
20
180
20
—
—
180
20
275
20
275
Figure A
—
—
20
320
20
320
10
420
10
420
Voltage Protection Rating (VPR) (Up @ In)
L-N
600
600
1000
1000
1500
1500
600
600
900
900
600
600
1000
1000
1500
1500
—
—
600
600
900
900
600
600
900
900
1000
1000
1500
1500
L-G
1200
1200
1500
1500
2000
2000
1200
1200
1500
1500
—
—
N-G
600
600
600
600
900
900
600
600
600
600
—
—
900
900
1800
1800
—
—
—
—
—
—
—
—
—
—
L-L
1200
1200
1800
1800
2500
2500
1200
1200
1800
1800
1200
1200
1800
1800
2500
2500
1800
1800
3000
3000
1200
1200
1800
1800
—
—
—
—
—
—
—
H-L1
—
—
H-N
—
—
H-G
—
1500
1500
2500
2500
—
—
—
900
900
1800
1800
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
1500
1500
2000
2000
—
***Please contact the factory for details
Configuration
Diagrams
(NOTE: Shown(NOTE
with no
power applied)
**Wiring
Wiring
Configuration
Diagrams
: Shown
with no power applied)
SINGLE
PHASE
3 PHASE DELTA /
3 PHASE WYE, COMMON N/G
SPLIT
PHASE
L1
L
L2
L1
L2
L3
3 PHASE HIGH LEG DELTA /
3 PHASE WYE, PLUS N-G
L2
L1
L3
G
G/N
G/N
G/N
N
**Electrical
Voltage
Configurations
**
Electrical
Voltage
Configurations
L
L1
L1
L1
L3
L2
N
N
N
N
G
L2
G
L2
L3
G
L3
G
L1
L2
FIGURE A
FIGURE B
FIGURE C
FIGURE D
FIGURE E
Single Phase
2 Wire + Ground
Split Phase
3 Wire + Ground
3 Phase Wye
4 Wire + Ground
3 Phase Delta
3 Wire + Ground
3 Phase Delta Hi-Leg
4 Wire + Ground
Rev. 11/13
Data subject to change
without notice
www.geindustrial.com
NOTE: GE’s Tranquell™ Series SPD
DIN Rail mount devices are tested
for safe operation without any
dedicated overcurrent protection,
when correctly matched to the
power system parameters.
A gG 160 Amp NH Fuse may be
chosen to meet other requirements
in an IEC application. Consult local
codes and standards for appropriate
fuse sizing.
BuyLog™ Catalog
5-21
Surge Protection Device (SPD)
Section 5
Critical Power Products
Protection Block Assembly–Surge Protection Device
Introduction
The GE 427 patented 5 Pin Protection Block Assembly is equipped
with a multi-layered printed circuit board, providing a connectorized interface for cable assemblies. It accommodates 25, 50 or
100 pair cable. It is used in many applications, including: central
offices, remote switching sites, customer premises and building
entrances, to protect telephone and voice/data lines.
When wiring cabinets with conventional wire wrap blocks each
block becomes a different part number and causes difficulty for
OEMs who have to inventory parts.
The same GE 427 Protection Block Assembly is used in every
position of a cabinet or mainframe. The cables are now treated as
less expensive parts and are stocked by length and mating connector type. Manual labor, in running cables and making
wire wrap connections, is reduced significantly by employing
GE Connectorized Block Assemblies.
Performance Features
—Gold pins and sockets ensure proper electrical connections
—Self-locking aluminum hood (optional) provides protection to
connectors and printed circuit board and serves as the cable
strain relief tie point
—Multi-layered printed circuit board
—Handle heavy transient current surges
—U.S. Patent No. 5,457,593
Protection Block Assembly
Protection Block Assembly–Surge Protection Device
Pair
Block Type
Hood
Product
Number
50
Marconi Block
YES
427-050-202
100
Avaya Block
YES
427-100-102
100
Marconi Block
YES
427-100-202
100
Corning Block
YES
427-100-302
Benefits
—Provides maximum reliability by eliminating all wire wraps
—Provides the high quality installation of a protection block
—Provides additional flexibility for equipment installations
—Easily serviceable in the field
—Eliminates the need for wire wrapping
—Allows connectorization into many different applications and
greatly reduces installation, labor and repair costs
—All cables connected to this unit can be removed, permitting
specific cable change out or change out of the entire protection
block assembly. This allows the protected equipment to quickly
be put back into service.
—Covered by a two year limited product warranty
Specifications
Voltage Class:
BIL rating:
Primary Currents:
5-22
600 V
10 kV
10 to 5000 amps
BuyLog™ Catalog
www.geindustrial.com
Rev. 11/13
Data subject to change
without notice