Medical Gas Piping - PD - Log into PIX (Phipps Information Exchange)

Transcription

Medical Gas Piping - PD - Log into PIX (Phipps Information Exchange)
226000-01 - Medical Gas Piping - PD
Submittal Stamp Sheet
Project:
Powers SNF
Phipps’ Job #: 13J2022
Submittal #: 226000-01 - Medical Gas Piping - PD
Gerald H. Phipps, Inc.:
Architect:
SUBMITTED
GH Phipps
Construction Companies
GH Phipps has reviewed, approved, and
herby submits the attached in accordance
with the contract documents.
Note to Subcontractor/Material Supplier:
Subcontractor/Material Supplier remains
responsible for the confirmation and
correlation of dimensions at the jobsite;
fabrication processes and construction
techniques; coordination of the work with
the work of other trades; and satisfactory
performance of the work.
Engineer:
Other:
NOTES:
Signed:
Nate Casten
H+L Architecture
1755 Blake St.
Denver, CO 80202
226000-01 - Medical Gas Piping - PD
PLUMBING & HEATING, INC.
Section 226000
SECTION TABLE OF CONTENTS
TAB #
1
Submittal Data
MEDICAL GAS PIPING
226000-01 - Medical Gas Piping - PD
TAB 1
226000-01 - Medical Gas Piping - PD
1800 Overview Drive
Rock Hill, SC 29730-7463
ph: 800-756-2590
fx: 803-817-5775
SUBMITTAL
Powers Skilled Nursing
PROJECT NAME:
ATTN:
Bobby Gilcrease
DATE:
COMPANY:
Harmon Bonded
QUOTE#:
STREET:
3415 Fillmore Ridge Heights
PO#:
CITY/ST/ZIP
Colorado Springs, CO 80907
NOTE#
ENCLOSED
x
x
Submittal
x
ACTION
For Your Approval
Colorago Springs, CO
Location:
x
4/8/2014
CPBJ13-0018-05
To Follow
COVERING
Pipeline System Equipment
Resubmit
For Your Use
Medical Vacuum System and Accessories
Disk
Review and Comment
Medical Air Compressor and Accessories
Email
For Record Only
Columns, Pedestals, Hose Reels
Copy
x
SYSTEM DESCRIPTION
VOLTAGE/PHASE/FREQUENCY
Equipment will not be released for production until stamped, approved submittal package is returned
BeaconMedaes to the attention of the Project Manager as listed below
CONTACT INFORMATION
SUBMITTAL APPROVAL
Please call us if you have any questions or need additional assistance
PHONE #
Med Gas Specialist
Manufactures Rep
Elizabeth Abell
303-257-0606
Beacon Medaes
PHONE #
Bill McCormick Jr.
303-279-6278
Signature:
Title:
Compliance Plus
PHONE #
Project Mgr:
Marcio De Sa
Project Manager Coordinator:
Beth Sanders
803-817-5665
803-817-5689
Phone #
226000-01 - Medical Gas Piping - PD
WARRANTY - PREMIUM
Beacon Medical Products LLC (“BeaconMedæs”) warrants the equipment it manufactures to be free of defects in materials or
workmanship when installed and operated in accordance with instructions. The Warranty Periods commence upon shipment or
at start up, whichever period terminates earlier.
This warranty covers all necessary parts and services as defined in the Conditions of Premium Warranty Periods, required for
correction of the defect whether by any or all of repair, replacement, or credit, which election shall be made by BeaconMedæs
at its sole discretion, and which are purchaser’s only remedies for breach of warranty.
This warranty requires the owner to ensure that the equipment is:
1. Installed in accordance with installation instructions provided with the product and installed with reasonable access
for maintenance and repair. Owner is responsible for the handling and lifting, if access is restricted.
2. Started up or placed in service by an authorized representative of BeaconMedæs, which includes the completion and
forwarding to BeaconMedæs of an appropriate start-up checklist
3. Installed and verified for operational compliance in accordance with the most recent edition of the NFPA 99
4. Maintained in strict accordance with Operation and Maintenance Instructions, including the recalibration, adjustment
or replacement of critical monitoring devices at the specified intervals
5. Serviced using BeaconMedæs supplied parts and lubricants
Warranty claims will be honored only after examination by BeaconMedæs and only when the examination discloses to
BeaconMedæs’ reasonable satisfaction that the equipment has not been damaged in shipment or installation, improperly
installed, operated outside of any published operating limits (including but not limited to temperature, pressure, elevation,
humidity, or ventilation), improperly or inadequately maintained, field modified in any way, improperly repaired, or in any
other way improperly applied or used.
All claims against this warranty require prompt notification, within the warranty period, of any seeming defect. Failure to
promptly notify BeaconMedæs of the seeming defect will invalidate all warranties.
BeaconMedæs in not liable for delay, damage or defect caused by shipping, acts of God, fire, war, labor difficulties, action of
government, or other cause beyond the reasonable control of BeaconMedæs. If there is a material delay in delivery for any
reason, purchasers only remedy is to cancel the purchase order.
This warranty is given in lieu of all other warranties, expressed or implied, including implied warranties of fitness for a
particular purpose and merchantability. In no event is BeaconMedæs liable for damages in excess of the value of the
defective product, nor is BeaconMedæs liable for any indirect, special or consequential damages, loss of profit of any
kind, or for loss of use of the products, even if BeaconMedæs is aware or should be aware of the possibility of the same.
Premium Warranty Periods
From Shipment
LifeLine Medical Air Systems
LifeLine Desiccant Air Dryer Systems
LifeLine Lubricated Vane Vacuum Systems
LifeLine Oil-less Vane Vacuum Systems
LifeLine Liquid Ring Vacuum Systems
Lifeline Claw (Standard and 02 Assured) Vacuum Systems
30 months
30 months
30 months
30 months
30 months
30 months
From Startup
24 months
24 months
24 months
24 months
24 months
24 months
All warranties exclude consumable items, which are warranted parts only until their first recommended change interval as
shown in the Operation and Maintenance Manual or the interval shown in Tables 1 and 2 as applicable for the equipment
category purchased, whichever occurs earlier.
Page 1 of 2
Warranty Doc 4107900000 Rev 05 Date 10/17/11
226000-01 - Medical Gas Piping - PD
Conditions of Premium Warranty Periods
Complete Systems:
Covers defective part and reasonable labor, travel and shipping costs for 30 months from the date of shipment or 24 months
from start-up, whichever comes first.
Components within Systems:
In addition to the Complete Systems warranty, the components listed are covered for the replacement of defective part only as
per the schedule in Table 1.
Table 1:
Premium Warranty - Components within Systems
Z Oil Free Compression Stages
LifeLine Dryer 441 Valve
From Shipment
66 months
66 months
From Start-up
60 months
60 months
Premium Warranty Periods
From Shipment
PipeLine Products
30 months
From Startup
24 months
PipeLine Products consisting of; Gas Outlets, Alarms, Manifolds, Valves, Valve Boxes, Emergency 02 Inlets, Gas Control
Panels, Ceiling Columns, Floor Pedestals, Hose Reels, Hose Assemblies, Pipeline Fittings and Adaptors.
Conditions of Premium Warranty Periods – Pipeline Products
Covers defective part and reasonable labor, travel and shipping costs for 30 months from the date of shipment or 24 months
from start-up, whichever comes first.
Page 2 of 2
Warranty Doc 4107900000 Rev 05 Date 10/17/11
226000-01 - Medical Gas Piping - PD
PROJECT:
Powers Skilled Nursing Facility
Quote ID: CPBJ13-0018-05
Base Bid
Qty
Part Number
Description
***** Sheet PFP 2.1AB Level 1
***** No Medical Gas
***** Sheet PFP 2.1C Level 1
***** Master Alarm Panel in Mechanical room 169
1
6-M2L-MBBB
***** Source - 02
4107203014 MEGA2 Alarm w/Local Sensors (SSB-830-07), Multi, Blank, Blank & Blank
1
4107215224
4
6-290641-04
MNE-HH4X4-O2-AS NFPA EN HPXHP 4X4 O2 55PSI STD AUTOMATIC MANIFOLD
(SSB-801-00)
4107200530 Wall Mount Cylinder Bracket Assembly (SSB-800-03), Double Cylinder
1
6-129030-10
4107200750 Pressure Switch, Gauge, DISS Connector, Oxygen, 40-60 psig Preset
●
●
●
●
1
6-M2L-MBBB
Gas specific pressure switch, Oxygen, 40-60 psig Preset
DISS gas specific demand valve
2 1/2" diameter, 0-100 psig pressure gauge
DISS nut and nipple assembly for connection to the demand valve
4107203014 MEGA2 Alarm w/Local Sensors (SSB-830-07), Multi, Blank, Blank & Blank
***** Riser Valves not shown but Required by NFPA 99
1
6-211604-00
***** Sheet PFP2.2C Level 2
***** Guest Rooms (Cont.)
4107206451 Shut-off Valve with locking handle, extensions & dual gauge port (SSB-820-10),
1-1/2"
1
6-150104-00
4107200587 Single Zone Valve Box Assembly (SSB-820-03), 1-1/4"
1
6-130108-00
4107200658 Zone Valve Box Assembly Gauge, 0-100 psig Pressure
1
6-TA2AL-OBBB
4107205815 TotalAlert2 Area Alm w/Local Sensors (SSB-830-41), O2, Blank, Blank & Blank
***** Floor Valves not shown but Required by NFPA 99
1
6-211603-00
***** Sheet PFP 2.3 C Level 3
***** Guest Rooms
4107206450 Shut-off Valve with locking handle, extensions & dual gauge port (SSB-820-10),
1-1/4"
1
6-150104-00
4107200587 Single Zone Valve Box Assembly (SSB-820-03), 1-1/4"
1
6-130108-00
4107200658 Zone Valve Box Assembly Gauge, 0-100 psig Pressure
1
6-TA2AL-OBBB
4107205815 TotalAlert2 Area Alm w/Local Sensors (SSB-830-41), O2, Blank, Blank & Blank
***** Floor Valves not shown but Required by NFPA 99
1
6-211603-00
***** Guest Rooms - MGO-1
80
4107206450 Shut-off Valve with locking handle, extensions & dual gauge port (SSB-820-10),
1-1/4"
6-121040-00
4107200782 Series B Concealed Outlet, Chemetron QC (SSB-840-07), Oxygen, Consisting of:
..6-233110-00
..4107200878 Concealed (Drywall) Rough-In Assembly, Oxygen
..6-230950-00
..4107200927 Latch Valve Assembly, Chemetron Quick Connect, Oxygen
..6-325161-00
..4107200910 Trim Plate, Die Cast - Concealed (5" x 5-1/2")
Page 2 of 4
SSB-840-07
4107 9507 41.00
Page 1 of 2
18 May 2012
Series B Medical Gas Outlet
Latch Key (NCG/Chemetron) Style
SPECIFICATION
Latch Key Medical Gas Wall Outlet
The latch key medical gas outlets are gas specific for the
services indicated and accept only corresponding latchkeyed adapters. The outlets are UL listed, CSA certified,
and are fully compliant with the latest edition of NFPA 99.
All outlets are 100% tested for flow, leaks and connector
attachment. The outlets are cleaned for oxygen service in
the manufacturing process. The outlets are made in the
U.S.A.
Gas service identification is affixed to the inlet tube and the
face of the rough-in plate. A secondary valve is installed in
the outlet block of the rough-in assembly (except vacuum
and WAGD) for both pressure testing and preventing gas
flow when the latch valve assembly is removed for service.
Outlet Design
A complete medical gas outlet consists of a gas specific
rough-in assembly for installation before the wall or
console is completed. A matching gas specific latch valve
assembly and trim plate are installed after the finish is
complete.
Latch Valve Assembly
The latch valve assembly includes a captured o-ring seal
primary valve, is gas specific for the labeled service, and
accepts only hose and apparatus with corresponding latchkeyed adapters. The latch valve assembly is indexed to the
corresponding rough in assembly to avoid accidental cross
connection and self adjusts up to 3/4" (1.9 cm) to allow
for variation in finished wall thickness from 1/2" (12.5
mm) up to 1-1/4" (3.175 cm).
The outlet block contains a double seal to prevent gas
leakage between the rough-in and latch valve assemblies
after the wall is finished. Outlets using a single o-ring seal
are not acceptable.
Rough-in Assembly
The rough-in assembly is of modular design and includes a
gas specific 16 gauge steel mounting plate. Wall versions
permit on site ganging of multiple outlets, in any order,
on 5" (12.7cm) centerline spacing. A 3/8" (9.5 mm) high
metal flange around the outlet opening provides a plaster
barrier. A temporary cover is provided to keep debris out
of the outlet during installation. Console rough-ins fit
standard electrical box cutouts and screw locations.
Trim Options
Either a die cast, light gray, epoxy powder-coated trim plate
or a smaller plastic trim plate can be provided to trim each
outlet. The die cast plate is designed specifically to fill the
space between adjacent outlets. Either trim plate allows
latch valves to be individually removed for servicing.
A machined brass outlet block is permanently attached to
the rough-in plate to permit the 1/2" OD (3/8" nominal),
type K copper inlet tube to swivel 360° for attachment to
the piping system.
Latch Key Outlets
(Note that a typical complete outlet consists of one Rough-in, one matching Latch Valve and one Trim Plate)
Gas Service
Color Code
(Background/Text)
Oxygen
Complete Assembly,
Wall Outlet
Rough-in Assembly,
Wall Outlet
Rough-in Assembly,
Console Outlet
Latch-Valve Assembly,
Wall or Console
White/Green
121040-00
233110-00
233010-00
230950-00
Blue/White
121041-00
233111-00
233011-00
230951-00
Medical Air
Yellow/Black
121042-00
233112-00
233012-00
230952-00
Vacuum
White/Black
121043-00
233113-00
233013-00
230953-00
WAGD
Purple/White
Nitrous Oxide
121049-00
233119-00
233019-00
230959-00
Medical Air (ISO) White-Black/Black-White
151042-00
233116-00
233016-00
230957-00
Vacuum (ISO)
151043-00
233117-00
233017-00
230958-00
Yellow/Black
Accessories (Note good design provides one slide with each vacuum)
Slide (Wall outlet style, Complete)
120978-00
Slide (Surface mount style)
Duplex Electrical Receptacle*
(Gray 15A, 125V, Wall outlet style, Complete)
120972-00
135012-00
Trim Plate, Wall (Large) Style
325161-00
Blank, Gas (Complete with RI and finish)
120979-00
Trim Plate, Console (Small) Style
616358-00
Blank, Gas (Cover plate only)
415169-00
*See specification sheet SSB-840-13 for additional electrical receptacles.
BeaconMedæs • 1800 Overview Drive, Rock Hill, SC 29730 • Phone: (803) 817-5600 • Fax: (803) 817-5750 • www.beaconmedaes.com
SERIES B LATCH KEY
WALL/CONSOLE OUTLET
226000-01 - Medical Gas Piping - PD
226000-01 - Medical Gas Piping - PD
SSB-840-07
4107 9507 41.00
Page 2 of 2
18 May 2012
Dimensions and Installation
360° Rotation
of inlet tube
Plaster guard
(provided)
Latch Valve
Interlock screws
(provided)
Mounting
Holes
(4 places)(2)
5” (127 mm)
5 1/2”
140 mm
/ ” OD (3/8” Nominal)
ASTM B-819
Type K
1 2
5 3/4”
146 mm
5”
127 mm
4 1/16”
103 mm
Trim Plate
(1)
When wallboard is less than 1/2” / 12.5 mm thick, as in consoles and headwalls, console outlets should be considered.
Plates may gang together in any length. Up to three may be ganged without additional support, however, top and bottom support is always
recommended. Total finished length will be 5”/127 mm x number of outlets in the gang (e.g. three outlets = 5 x 3 = 15”)
(2)
Wallboard and wall covering
1/2” / 12.5 mm MINIMUM(1), 1 1/4“ / 31mm MAXIMUM thickness
2 3/ 4”
70 m
m
8 / ”
215 mm
7 16
13/16”
21 mm
4 1/16”
104 mm
8 7/16”
215 mm
Console Rough in
Small
Console
Trim Plate
(616358-00)
1 13/
16
46 m ”
m
Finish Assembly
5”
127
mm
3 3/4”
96 mm
3 1 /4 ”
83 mm
1 /”
48 mm
7 8
2 7/1
6
62 m ”
m
5 1/2”
104 mm
”
7 16
2 / m
m
62
Standard Wall Trim Plate
(325161-00)
BeaconMedæs
1800 Overview Drive
Rock Hill, SC 29730
Phone: (803) 817-5600
Fax: (803) 817-5750
www.beaconmedaes.com
 
226000-01 - Medical Gas Piping - PD
Page 1 of 1
29 November 2011
Shut-Off Valve Assembly 1/2" through 4"
SPECIFICATION
Shut-Off Valve
Shut off valve shall be full port, double seal, ball type three
piece design with bronze/brass body and chrome plated
brass ball. Only 1/4 turn of the handle shall be required to
operate the valve from open to closed position. All valves
shall be serviceable in the line and supplied clean and
prepared for oxygen service. Color-coded gas identification
labels shall be provided with each valve. Valves are oxygen
cleaned, capped, and poly-bagged per CGA G-4.1. Each
polyethylene bag is labeled with CGA G-4.1 conformance.
Valve handle includes locking mechanism.
Shut-Off Valve Design
Valves shall be designed for a maximum working pressure
of 600 psig WOG or vacuum service to 29" Hg. Valve body
shall have reinforced PTFE ball seat and reinforced PTFE
stem seals, and include a blowout proof stem. Seats/seals,
lubricants and valve material shall be compatible with USP
oxygen, nitrous oxide, medical air, carbon dioxide, helium,
argon, nitrogen and mixtures thereof at continuous pressure
up to 600 psig and up to 100° F. Valves shall be provided
with type K copper tube extensions for making connections
to the pipeline. Valves conform to MSS SP-110. Type K
copper tube extensions conform to ASTM B88, UNS No.
C12200, and H58 temper.
Dual Port Shut-Off Valves with Locking Handle
Valve Size
1/2"
3/4"
1"
1-1/4"
1-1/2"
2"
Part Number
A
B
C
D
E
F
G
211600-00
3.35"
5/8" O.D. (1/2" nominal)
13.00
26.00
1.69
2.71
2.03
211601-00
4.33"
7/8" O.D. (3/4" nominal)
13.00
26.00
1.89
2.91
2.03
211602-00
4.33"
1-1/8" O.D. (1" nominal)
13.00
26.00
2.05
3.20
2.39
211603-00
5.12"
1-3/8" O.D. (1-1/4" nominal)
13.00
26.00
2.56
3.92
2.71
211604-00
5.12"
1-5/8" O.D. (1-1/2" nominal)
13.00
26.00
2.72
4.25
3.05
211605-00
6.30"
2-1/8" O.D. (2" nominal)
13.00
26.00
3.15
5.05
3.80






1/2" through 2"
1/8" NPT PORT
SEALED WITH
BRASS HEX HEAD PLUG
USING TEFLON TAPE
(2 PL.)
"A"
"E"
"B"
"C"
"F"
"G"
"D"
Dual Port Shut-Off Valves with Locking Handle
Valve Size
2-1/2"
3"
4"



Part Number
A
B
C
D
E
F
G
211606-00
9.06"
2-5/8" O.D. (2-1/2" nominal)
16.00
32.00
4.29
7.09
5.95
211607-00
9.06"
3-1/8" O.D. (3" nominal)
16.00
32.00
4.61
7.46
6.44
211608-00
11.73"
4-1/8" O.D. (4" nominal)
16.00
32.00
7.90
11.65
8.52
2-1/2" through 4"
"A"
1/8" NPT PORT
SEALED WITH
BRASS HEX HEAD PLUG
USING TEFLON TAPE
(2 PL.)
"E"
"F"
"B"
"C"
"D"
"G"
BeaconMedæs • 1800 Overview Drive, Rock Hill, SC 29730 • Phone: (803) 817-5600 • Fax: (803) 817-5750 • www.beaconmedaes.com
SHUT-OFF
1/2" - 4"
SSB-820-10
SSB-820-03
Page 1 of 2
30 November 2011
Single Zone Valve and Box Assembly
SPECIFICATION
Single Zone Valve and Box Assembly
Valves shall be full port, double seal, ball-type with three
piece bronze/brass body and a chrome plated brass ball.
Valves shall be designed for a maximum working pressure of
600 psig WOG or vacuum service to 29" Hg. Valve body shall
have reinforced PTFE ball seat and reinforced PTFE stem seals,
and stem shall be blowout proof. All valve materials shall
be compatible with USP oxygen, nitrous oxide, medical air,
carbon dioxide, helium, nitrogen, argon and mixtures thereof.
A 1/4 turn of the handle shall be required to operate the valve
from OPEN to CLOSED position. The valve shall be securely
attached to the box and provided with type K copper tube
extensions for making connection to system piping outside the
box. All valves shall be serviceable in the line, supplied clean
and prepared for oxygen service. All zone valve assemblies
shall include a 1/8" NPT port with pipe plug as a provision for
connection of a gauge. The gauge port shall be located on the
terminal outlet side of the valve to register pipeline pressure
or vacuum. The gauge shall be visible through the door of
the zone valve box. The zone valve and box assembly shall
meet all requirements of NFPA 99 and CAN/CSA Z305.1. The
valves conform to MSS SP-110. Type K copper tube extensions
conform to ASTM B88, UNS No. C12200, and H58 temper.
The gauges shall conform to ANSI B40.1.
Valve Size
Zone Valve Box
Assembly
1/2"
3/4"
1"
1-1/4"
1-1/2"
2"
2-1/2"
3"
Type
Gauges1
0-30" Hg
0-100 psig
0-300 psig
Smoked Finish Door Assembly2
Single Zone Box Design
The zone valve box shall be constructed of 18 gauge steel
with white epoxy finish and provided with two galvanized
steel brackets that anchors the box to the wall. Anchor
brackets shall be designed to permit box assemblies to be
ganged together in a vertical stack, 1/2” through 2” only. The
1/2” through 2” valves require a rough wall opening of 117/8” wide x 10” high x 3-7/8” deep. The 2-1/2” and 3” valves
require a rough wall opening of 15-7/8” wide x 10” high x
6-11/16” deep. The zone valve box assembly shall have a
sliding, opaque door with pull ring and clear gauge window.
The door shall be capable of sliding to the right or left to
facilitate installation requirements. In an emergency, the
door shall SNAP OUT by pulling the pull ring forward without
exposing sharp edges. The zone valve box shall be provided
with an anodized aluminum trim capable of adjusting to
variations in wall thickness up to 1" below flush. The zone
valve box assembly shall be supplied with color coded gas
identification labels. The assembly door shall have a label
that reads:
-CAUTIONMEDICAL GAS SHUT-OFF VALVES
CLOSE ONLY IN EMERGENCY
Complete Assembly
Note:








All zone valve box assemblies include 1/8" NPT gauge port/plug for
each valve and two labels each for the following services: Oxygen,
Nitrous Oxide, Medical Air, Nitrogen, Vacuum, WAGD, Carbon
Dioxide, and Instrument Air.
150101-00
150102-00
150103-00
150104-00
150105-00
150106-00
150107-00
150108-00
Part Number
System




130107-00
Vacuum, WAGD
130108-00
O2, Air, N2O, CO2 & Mixtures
130109-00
Nitrogen, Instrument Air, O2 (100 psig), Air (100 psig), CO2 (100 psig)
232172-SM
Note: 1. Order gauges separately for zone valve application.
2. Smoked door is an additional cost and will ship loose for customer to replace (not available for 2-1/2" and 3" Zone Valve Boxes).
BeaconMedæs • 1800 Overview Drive, Rock Hill, SC 29730 • Phone: (803) 817-5600 • Fax: (803) 817-5750 • www.beaconmedaes.com
SINGLE ZONE
VALVE BOX
226000-01 - Medical Gas Piping - PD
226000-01 - Medical Gas Piping - PD
SSB-820-03
Page 2 of 2
30 November 2011
Single Zone Valve and Box Assembly
1/2" through 2" Assemblies
25-13/16”
(TYP.)
11-7/8"
FINISHED
WALL
12-3/4”
CAUTION
MEDICAL GAS SHUT-OFF VALVES
CLOSE ONLY IN EMERGENCY
10”
11"
Supply
Source
Outlet
Side
5/8"
3-7/8"
2-1/2" through 3" Assemblies
FINISHED
WALL
31-13/16”
15-7/8”
16-3/4”
CAUTION
MEDICAL GAS SHUT-OFF VALVES
CLOSE ONLY IN EMERGENCY
10"
(TYP)
11"
(TYP)
Supply
Source
Outlet
Side
5/8”
(TYP)
6-11/16”
65
8"
Additional Labels: One Set per Package
Additional Labels: 20 Labels per Package











430259-00
435674-00
One Each: Oxygen, Nitrous
Oxide, Medical Air, Vacuum,
Nitrogen, WAGD, Carbon
Dioxide, Instrument Air
One Each: Oxygen, Nitrous
Oxide, Air, Vacuum,
Nitrogen (ISO)
BeaconMedæs
1800 Overview Drive
Rock Hill, SC 29730
Phone: (803) 817-5600
Fax: (803) 817-5750
www.beaconmedaes.com
435000-21
Carbon Dioxide-Oxygen Mixture (CO2 over 7.5%)
435000-22
Oxygen-Carbon Dioxide Mixture (CO2 not over 7.5%)
435000-23
Helium-Oxygen Mixture (He over 80.5%)
435000-24
Oxygen-Helium Mixture (He not over 80.5%)
435000-25
Helium
435000-28
Oxygen (100 psig)
435000-29
Medical Air (100 psig)
435000-30
Carbon Dioxide (100 psig)
435000-31
Argon
 
SSB-830-07
Page 1 of 4
12/31/2007
MEGA2® Medical Electronic Gas Alarm
SPECIFICATION
Medical Electronic Gas Alarm
The MEGA2® provides master and area alarm signals as
required by the latest edition of NFPA 99. The alarm is ETL
listed to UL 1069 and CSA C22.2 NO 601.1-M90. The
MEGA2® complies with the following electromagnetic
compatibility standards: FCC Part 15 Class A, ICES 003
Class A, EN 61326, EN 61000-3-2 and EN 61000-3-3. All
field wiring and signals are self-monitoring and on a closed
circuit. Fault signals activate on an open circuit.
Each digital display module is equipped with separate relays
for high and low alarms. Relays are single-pole doublethrow type (30 VAC/VDC 2A max). Digital readings from
one display module can be monitored by another digital
display module at a remote panel.
Input power to the alarm panel is 100 to 250 VAC 50/60 Hz,
double fused on the input side rated at 1 Amp, time-delayed.
An internal power supply converts the input voltage to low
voltage +5 and +24 VDC. All user accessible electronics and
wiring utilize low voltage. A guard must be removed to
access the high voltage wiring.
Sensor Module
The sensor module contains a transducer capable of
providing calibrated signals to the digital display module.
Sensor modules are gas specific. The alarm panel is factory
configured for sensor mounting within the alarm panel
rough-in box (local sensors) or mounting above ceiling
directly to the medical gas pipeline (remote sensors).
Remote sensors may be located up to 1524 m (5,000 feet)
from the alarm panel.
A green front panel POWER ON indicator illuminates when
the alarm panel is powered. Each monitored condition has a
separate red indicator illuminated when in alarm. A red
indicator on the alarm silence button is illuminated after any
audible alarm has been silenced.
A sensor module is required for each digital display module.
Pipeline connections are 3/8” nominal (1/2” OD) type K
copper tube. Connectors are provided for attaching field
wiring. Sensors are gas specific for periodic testing without
interrupting medical gas pipeline pressures or vacuum.
Each panel provides an audible signal that is activated by the
digital display module(s) or multi-signal alarm module(s).
The audible signal will produce a minimum sound pressure
level of 90 dBA measured at a distance of 3 ft (1m). The
alarm panel also contains alarm silence, test, and setup
buttons.
Multi-Signal Alarm Module
The multi-signal alarm module is capable of monitoring up to
five dry-contact signals. Each signal illuminates a green
LED to indicate that conditions are normal. When a fault
occurs, the green LED turns off, a red LED illuminates, and
the audible alarm sounds. The red LED flashes until the
front panel alarm silence button is pressed. After the alarm
silence button is pressed, the red LED remains illuminated,
but does not flash. The red indicator automatically turns off
and the green LED illuminates when the fault is corrected.
Each panel includes a general fault relay for the entire panel,
and an RS-485 data port for the MEGA network (An
additional auxiliary relay is available as an option).
Digital Display Module
The digital display module may be used as either a master
alarm or area alarm. The digital LED display continuously
indicates the pressure or vacuum in the piping system being
monitored. The brightness of the LED display is adjustable
to compensate for ambient lighting. The display is
programmable to read psig, in Hg, mm Hg, or kPa in
increments of 1 psig, 1 in Hg, 1 mm Hg, or 1 kPa
respectively.
The digital display module provides an audible and visual
signal when a fault condition occurs. The front panel alarm
mute button can silence the audio. The visual signal flashes
until the alarm silence button is pressed, and then remains
illuminated, but does not flash.
The visual signal
automatically cancels when the fault is corrected.
Separate visual signals for system pressure or vacuum are
NORMAL (green LED), LOW (red LED), and HIGH (red
LED). Signal limits are factory set per NFPA 99 and field
programmable without the use of tools. Pressing and holding
the front panel TEST button initiates a self-test function to
test the LED display, visual indicators, audible alarm, and to
view the alarm set points.
LED illumination for unused signals can be deactivated in
the field. Field programming can be accomplished without
the use of tools. Pressing and holding the front panel TEST
button shall initiate a self-test function to test the LED
indicators and audible alarm. As an option, the multi-signal
module may be supplied with five, dry-contact, normally
closed relays for connection to a building automation system.
Relay ratings are 30 VAC/VDC 2A max.
Blank Module
A blank overlay is used to fill unused alarm panel locations
or reserve a module location for future expansion. It may be
removed and either module style substituted at any time.
Transport & Storage
During transport and storage, do not exceed an ambient
temperature range of 0°F to 130°F (-18°C to 55°C), a relative
humidity range of 10% to 85% with non-condensation, and
an atmospheric pressure range of 950 hPa (millibar) to 1050
hPa (millibar).
BeaconMedæs Š 1800 Overview Drive Rock Hill, SC 29730 Š Phone: (803) 817-5600
Fax: (803) 817-5750
ELECTRONIC
GAS ALARM
226000-01 - Medical Gas Piping - PD
226000-01 - Medical Gas Piping - PD
SSB-830-07
Page 2 of 4
12/31/2007
MEGA2® Alarm Panel Configuration
The MEGA2® alarm panel is available in two sizes. The small panel will accommodate four alarm modules. The large panel will
accommodate eight alarm modules. An alarm panel may consist of any combination of Digital Display Modules, Multi-Signal
Modules, or Blank Modules in any order. If the alarm panel is configured with Digital Display Modules, pressure / vacuum sensors
will be included for connection to the medical gas / vacuum pipeline. Sensors may be located inside the alarm panel rough-in box
(local sensor) or outside the alarm panel rough-in box (remote sensor). Local sensors must be connected to the medical gas / vacuum
pipelines via copper tubing. Remote sensors may be mounted directly to or near the medical gas / vacuum pipeline and then wired to
the alarm panel.
The required alarm panel configuration must be specified within the part number scheme as described below:
6-M2L-MBBB
NOTE:
• All module locations within the alarm panel must be specified with a digital display,
multi-signal, or blank module.
• For multi-signal master panels, pressure switches and DISS disconnect kits must be
ordered separately (see page 3 – misc. part numbers).
BeaconMedæs Š 1800 Overview Drive Rock Hill, SC 29730 Š Phone: (803) 817-5600
Fax: (803) 817-5750
226000-01 - Medical Gas Piping - PD
SSB-830-07
Page 3 of 4
12/31/2007
MEGA2® Alarm Panel Part Number Examples
Miscellaneous
Installation, Operation, and Maintenance Manual
Pressure Switch 40-60 PSI
Pressure Switch 140-190 PSI
Vacuum Switch 12 in Hg
DISS Disconnect Kit
Oxygen
Nitrous Oxide
Medical Air
Vacuum
Nitrogen
WAGD
Carbon Dioxide
CO2 – O2
O2 – CO2
Part Number
F 6-847684-00
F 6-129020-01
F 0208-5096-300
F 6-129022-01
F
F
F
F
F
F
F
F
F
6-120004-10
6-120004-11
6-120004-12
6-120004-13
6-120004-14
6-120004-19
6-120004-20
6-120004-21
6-120004-22
BeaconMedæs Š 1800 Overview Drive Rock Hill, SC 29730 Š Phone: (803) 817-5600
Fax: (803) 817-5750
226000-01 - Medical Gas Piping - PD
SSB-830-07
Page 4 of 4
12/31/2007
MEGA2® Alarm Panel
BeaconMedæs Š 1800 Overview Drive Rock Hill, SC 29730 Š Phone: (803) 817-5600
Fax: (803) 817-5750
SSB-830-41
Page 1 of 3
12/31/2007
TotalAlert2 TM
Medical Electronic Gas Area Alarm
SPECIFICATION
Medical Electronic Gas Alarm
The TotalAlert2 provides area alarm signals as required by
the latest edition of NFPA 99. The alarm is ETL listed to UL
1069 and CSA C22.2 NO 601.1-M90. The TotalAlert2
complies with the following electromagnetic compatibility
standards: FCC Part 15 Class A, ICES 003 Class A, and EN
60601-1-2. All field wiring and signals are self-monitoring
and on a closed circuit. Fault signals activate on an open
circuit.
for system pressure or vacuum are NORMAL (green LED),
LOW (red LED), and HIGH (red LED). Signal limits are
factory set per NFPA 99 and field programmable.
Input power to the alarm panel is 100 to 250 VAC 50/60 Hz,
double fused on the input side rated at 1 Amp, time-delayed.
An internal power supply converts the input voltage to low
voltage. All user accessible electronics and wiring utilize low
voltage. A guard must be removed to access the high voltage
wiring.
Multi-Signal Alarm Module
The multi-signal alarm module is capable of monitoring up to
five normally closed dry-contact switch signals. Each signal
illuminates a green LED to indicate that conditions are
normal. When a fault occurs, the green LED turns off and a
red LED illuminates, and the audible alarm sounds. The red
LED flashes until the front panel alarm mute button is
pressed. After the alarm mute button is pressed, the red LED
remains illuminated but does not flash. The red indicator
automatically turns off and the green LED illuminates when
the fault is corrected.
Alarm Panel
All TotalAlert2 area alarm front panels feature a green
POWER ON indicator that illuminates when the alarm panel
is powered and operating normally. A red flashing alarm
system fault indicator is illuminated if a power supply or
microprocessor problem is detected. Each monitored
condition has a separate red flashing indicator illuminated
when in alarm. A red indicator on the alarm mute button is
illuminated after any audible alarm has been silenced. The
visual signal automatically cancels when the fault is
corrected.
Each panel provides an audible signal that is activated by a
monitored signal in fault condition. The audible signal
produces a minimum sound pressure level of 80 dBA
measured at a distance of 3 ft (1m). The front panel alarm
mute button can silence the audio. Audible alarm mute
duration is adjustable.
Each panel contains a general fault relay that activates on any
alarm panel fault condition and an auxiliary relay that
activates when the alarm is sounding.
Pressing and holding the front panel TEST button initiates a
self-test function to test the LED indicators, visual displays,
audible alarm, and to view alarm set points.
Two alarm panel sizes support either four or eight alarm
modules, consisting of any combination of digital display
modules, multi-signal modules, or blank modules.
Digital Display Module
The digital LED display continuously indicates the actual
pressure or vacuum in the piping system being monitored.
The brightness of the LED display is adjustable to
compensate for ambient lighting.
The display is
programmable to read psig, in Hg, mm Hg, or kPa.
The digital display module provides an audible and visual
signal when a fault condition occurs. Separate visual signals
Each digital display module is equipped with separate relays
for high and low alarms. Relays are single-pole doublethrow type (30 VAC/VDC 2A max). Digital readings from
one display module can be monitored by another digital
display module at a remote panel.
As an option, the multi-signal module may be supplied with
five, dry-contact, normally closed relays for connection to a
building automation system. Relay ratings are 30 VAC/VDC
2A max.
Blank Module
A blank overlay is used to fill unused alarm panel locations
or reserve a module location for future expansion. The blank
overlay may be removed and replaced by a digital display
module or multi-signal module style at any time.
Built-in Web Pages
Each TotalAlert2 area alarm panel features an embedded web
server with web pages to view and set up the alarm. Built-in
web pages require no additional setup.
Network
communication implementation provides browse, download,
configure, and troubleshooting of Area Alarms with a
personal computer that is connected to the facility’s Ethernet.
All panels contain an event log that captures all alarms and
events and saves the information at the panel. The event log
can be downloaded to a computer file for tracking data,
reporting and troubleshooting.
Connectivity
Each panel includes a 10Base-T Ethernet Jack and Ethernet
LINK, TX, and RX indicators. The Ethernet connection
provides interfacing capability to the facility’s Intranet. If
connected to the Ethernet, upon activation of an alarm, the
Area Alarm Modules send the location, alarm status, and
pressure or vacuum readings to the Master Alarm where they
are displayed and stored in an event log. All of the Area
Alarm readings and statistics can be browsed using a
personal computer logged onto the facility’s Ethernet.
BeaconMedæs Š 1800 Overview Drive Rock Hill, SC 29730 Š Phone: (803) 817-5600
Fax: (803) 817-5750
TOTALALERT2
AREA ALARM
226000-01 - Medical Gas Piping - PD
226000-01 - Medical Gas Piping - PD
SSB-830-41
Page 2 of 3
12/31/2007
Sensor Module
The sensor module contains a transducer which provides
calibrated signals to the digital display module. Sensor
modules are gas specific. The alarm panel is factory
configured for sensor mounting within the alarm panel
rough-in box (local sensors) or mounting above ceiling
directly to the medical gas pipeline (remote sensors).
Remote sensors may be located up to 1524 m (5,000 feet)
from the alarm panel.
A sensor module is required for each digital display module.
Pipeline connections are 3/8” nominal (1/2” OD) type K
copper tube. Connectors are provided for attaching field
wiring. Sensors may be disconnected for periodic testing
without interrupting medical gas pipeline pressures or
vacuum.
Figure 1: Small Area Alarm Panel
Figure 2: Large Area Alarm Panel
Rough-in Assembly
The rough-in assembly is constructed of 18-gauge polyester
powder-coated steel. Mounting brackets on each side of back
box are adjustable to fit drywall thicknesses of 1/2” to 1-1/2”.
Transport & Storage
During transport and storage, do not exceed an ambient
temperature range of 0°F to 130°F (-18°C to 55°C), a relative
humidity range of 10% to 85% with non-condensation, and
an atmospheric pressure range of 950 hPa (millibar) to 1050
hPa (millibar).
The required alarm panel configuration must be specified
within the model number scheme described as follows:
L-OBBB
Area Alarm Panel Components
Module Types
O
Oxygen
D
Oxygen – 100 psi
X
Nitrous Oxide
A
Medical Air
F
Medical Air – 100 psi
5
Air (ISO)
7
Laboratory Air
2
O2 – CO2 (CO2 not over 7%)
4
O2 – He (He not over 80%)
C
Carbon Dioxide
G
Carbon Dioxide – 100 psi
1
CO2 – O2 (CO2 over 7%)
3
He – O2 (He over 80%)
H
Helium
V
Vacuum
6
Vacuum (ISO)
8
Laboratory Vac
W
WAGD
N
Nitrogen
9
Instrument Air
J
Argon
M
Multi-Signal Module
R
Multi-Signal Module with Relays
B
Blank Module
BeaconMedæs Š 1800 Overview Drive Rock Hill, SC 29730 Š Phone: (803) 817-5600
Fax: (803) 817-5750
Digital Display Modules
Model Number Configuration
TotalAlert2 area alarms are available in two size housings
accommodating four or eight alarm modules. An alarm panel
may consist of any combination of Digital Display Modules,
Multi-Signal Modules, or Blank Modules in any order. If the
alarm panel is configured with Digital Display Modules,
pressure/vacuum sensors will be included for connection to
the medical gas / vacuum pipeline. Sensors may be located
inside the alarm panel rough-in box (local sensor) or outside
the alarm panel rough-in box (remote sensor). Local sensors
must be connected to the medical gas / vacuum pipelines via
copper tubing. Remote sensors may be mounted directly to
or near the medical gas / vacuum pipeline and then wired to
the alarm panel.
226000-01 - Medical Gas Piping - PD
SSB-830-41
Page 3 of 3
12/31/2007
TotalAlert2 Area Alarm Panel
BeaconMedæs Š 1800 Overview Drive Rock Hill, SC 29730 Š Phone: (803) 817-5600
Fax: (803) 817-5750
SSB-830-01
Page 1 of 2
05/14/2009
Gas Specific Pressure Switch for 50-55 PSIG Systems
SPECIFICATION
Gas Specific Pressure Switch
BeaconMedaes gas specific pressure switch assemblies are
designed to monitor medical gas pipeline systems operating
at nominal pressures of 50-55 psig. The switches shall be a
U.L. listed single pole double throw snap action microswitch. Electrical ratings are a minimum of 5 amps at 125
volts. Switches are factory preset to signal the master alarm
system when the pipeline pressure increases to 60 psig or
decreases to 40 psig (20% increase or decrease from
nominal pressure as recommended by NFPA-99). Cleaned
for O2 service, use no oil.
mounting of the assembly. A ¾” npt female connection is
provided for connection of a flexible conduit. (A 2’ flexible
conduit whip is suggested for connection to the switch to
allow for annual testing purposes as required by NFPA 99
without removing electrical connections.)
The pressure switches are rated at 150 psig proof pressure
and are field adjustable for non-standard operating systems.
The low set point may be adjusted from 20 to 90 psig on
decreasing pressure and the high set point may be adjusted
from 30 to 90 psig on increasing pressure. The approximate
deadband for the switches is 4 psig.
BeaconMedaes pressure switch assemblies are compatible
with medical gas alarm systems sensing fault on either the
opening or closing of the switch contacts.
Each assembly is provided with a DISS gas specific demand
valve for connection to the pipeline system. The switch
assembly will consist of the pressure switch, 2 ½” diameter,
0-100 psig pressure gauge and DISS nut and nipple
assembly for connection to the demand valve installed on
the pipeline.
The switch enclosure is epoxy powder coated die-cast
aluminum with gasketed cover and captive screws. The
switch cover is easily removable to provide access to the
switch contact terminals and adjustment screws. Each
switch is provided with ¼” clearance holes for optional wall
Gas Specific Pressure Switches – 55 psig
Part Number
Gas Service
Low Set
High Set
Gauge
□ 6-129030-10
Oxygen
40
60
0-100
□ 6-129030-11
Nitrous Oxide
40
60
0-100
□ 6-129030-12
Medical Air
40
60
0-100
□ 6-129030-20
Carbon Dioxide
40
60
0-100
□ 6-129030-21
CO2-O2 (CO2 > 7%)
40
60
0-100
□ 6-129030-22
O2-CO2 (CO2 < 7%)
40
60
0-100
□ 6-129030-23
He-O2 (He > 80%)
40
60
0-100
□ 6-129030-24
O2-He (He < 80%)
40
60
0-100
□ 6-129030-25
Helium
40
60
0-100
BeaconMedæs  1800 Overview Drive Rock Hill, SC 29730  Phone: (803) 817-5600
Fax: (803) 817-5750
GAS SPECIFIC
SWITCHES
226000-01 - Medical Gas Piping - PD
226000-01 - Medical Gas Piping - PD
SSB-830-01
Page 2 of 2
05/14/2009
Gas Specific Pressure Switch for 50-55 psig Systems
Typical Wiring Connections for Part Numbers
6-129030-10 through 6-129030-25
*Terminals to be used for BeaconMedaes MEGA, MEGA2,
TotalAlert, TotalAlert2 and other system sensing fault on
electrical contacts opening.
BeaconMedæs  1800 Overview Drive Rock Hill, SC 29730  Phone: (803) 817-5600
Fax: (803) 817-5750
226000-01 - Medical Gas Piping - PD
Page 1 of 5
30 October 2013
NFPA Automatic Changeover Medical High Pressure by High Pressure Manifold
(Lifeline)
AUTOMATIC
CHANGEOVER
SSB-801-00
4107 9508 46.01
SPECIFICATION
Automatic Changeover Medical High Pressure Gas Manifold
The BeaconMedæs Lifeline® automatic Changeover manifold
accommodates multiple high pressure cylinders equally
divided into two banks for a specific gas service. The cylinder
banks are arranged in a staggered configuration and provide
an uninterrupted supply of gas for the specific gas application.
The manifold is cleaned, tested, and prepared for the indicated
gas service and constructed in accordance with requirements
of the latest edition of NFPA 99 and CGA.
NOTE:
The flow capacity of a nitrous oxide and carbon
dioxide manifold depends upon environmental
conditions at the installation site and the number
of cylinders in service. Installing a nitrous oxide
or a carbon dioxide manifold in a location that
exposes it to an ambient temperature below 32°F
(0°C) is not recommended.
Manifold Design
A bank regulator (one for each cylinder bank) is used to initially
reduce the cylinder pressure to the two line regulators which
control the final line pressure. The manifold automatically
changes from the depleted primary supply bank to the
secondary supply bank without fluctuation in line pressure
utilizing dome-bias loading and unloading of the bank
regulators. After replacement of the depleted cylinders, the
manifold automatically indicates the replaced cylinder bank as
the secondary supply. Manual resetting of the control panel is
not necessary.
The manifold includes a line pressure gauge, two cylinder bank
pressure gauges (left bank and right bank), and color coded
LED visual indicators for "IN USE" (green), "READY" (green),
and "EMPTY" (red) for each cylinder bank.
The manifold has intermediate and line pressure relief valves
that are internally connected to a common vent port, terminating
into a 1/2" FNPT "O"-ring sealed "zero clearance" union.
Master shutoff valves (one for each cylinder bank) are located
outside the cabinet and both valves are fabricated with metallic
seating surfaces. The manifold is designed for placement of
four "H" cylinders directly underneath the manifold cabinet.
The cabinet enclosure is easily removable by releasing draw
latches for component accessibility and the enclosure may be
secured from unauthorized access by locking the draw latches
(locks provided by others).
The manifold includes high-pressure modular header
assemblies with gas specific pigtail-to-header high-flow check
valves to permit changing of cylinders without gas leakage.
Stainless steel flexible pigtails are provided for each cylinder
gas connection, except for O2, He, CO2O2, O2CO2, HeO2, and
O2He gases which are provided with rigid copper pigtails.
The power supply and control board are furnished inside a premounted NEMA 4 enclosure. The power supply has electrical
requirments as follows: 250mA max at 100-250VAC 50/60Hz
single phase input to 24VDC output. The control board includes
dry contacts for (2) separate, electrically isolated remote alarm
connections for manifold Changeover.
Environmental Considerations
Manifolds are to be installed in accordance with requirements
stated by NFPA 99, CGA and all applicable local codes. Manifold
components are designed to work best over a temperature
range of 0°F through 130°F. Wider temperature variation may
cause manifold malfunctions to occur. The BeaconMedæs
Lifeline® manifold has been environmentally tested to MIL
STD 810F. The Lifeline® power supply and control board is
fully contained inside a NEMA 4 enclosure, allowing for outdoor
installations.
Flow Characteristics at Minimum Cylinder
(Changeover) Pressure
Delivery Line Pressure
(PSIG)
Minimum Delivery Line
Flow (SCFH)
55
3,300*
100
4,620*
180
5,340*
* Tested flow rate at 10% fall off
Note: Flow is tested for compliance as
per ISO 10524-2 section 6.3.1
TESTING STANDARDS
Environmental Testing:
MIL STD 810F
Ignition Testing:
ISO 10524-2
The manifold is supplied with a ¾” FNPT "O"-ring sealed "zero
clearance" union outlet. The system also includes a ¾” full port,
three piece, ball-type source shut-off valve with ⅛” FNPT port.
The source valve has a ¾” NPT attachment to the union outlet
and a ¾” nominal copper (type K) tube for brazing to main
supply line.
BeaconMedæs • 1800 Overview Drive, Rock Hill, SC 29730 • Phone: (803) 817-5600 • Fax: (803) 817-5750 • www.beaconmedaes.com
226000-01 - Medical Gas Piping - PD
SSB-801-00
4107 9508 46.01
Page 2 of 5
30 October 2013
Standard Configuration
3
Standard Model Shown
4
5
2
7
6
8
10
1
9
1
New LED Electronics Overlay for easy visual status of gas flow
2
The NEMA 4 Enclosure houses both Power Supply and Control Board. It is pre-drilled for power, alarm, and data
connections for easy installation.
3
1/4 Turn Shut-Off Valve used to isolate manifold from hospital piping for repair
4
Vent Valve with ergonomic handle for easy operation. Mounted and tubed to conveniently vent to relief outlet
5
Service Valve to provide outlet gas to dome bias regulator and solenoid valve.
6
Bank regulator is housed in a brass forging to minimize connection points, therefore eliminating the opportunity
of leaks. The regulator is a dome loaded, single-stage, diaphragm type regulator used to reduce incoming
cylinder contents pressure to a lower intermediate pressure. Bleed valves are also present for servicing needs.
7
Line Regulator is housed in a brass forging to minimize connection points, therefore eliminating the opportunity
of leaks. The regulator is a single-stage, diaphragm type regulator used to reduce incoming bank regulator
pressure to a lower delivery pressure. Bleed valves are also present for servicing needs.
8
Pressure Switch is an adjustable, single pole switch that is connected to high pressure port of each bank
regulator to monitor pressure in each bank of cylinders. Pressure Transducer (only available on TAE models)
monitor pressure in each bank of cylinder and attach to each bank regulator and have a range of 0-3000 psi.
(A pressure tranducer ranging from 0-300 psi measures outlet pressure.)
9
Dome Bias Regulator with easily identifiable premounted gauge and locking ring to ensure constant bank
regulator dome pressure
10
New Robust Solenoid Valve made of Stainless Steel including mufflers to reduce noise during change-overs.
226000-01 - Medical Gas Piping - PD
SSB-801-00
4107 9508 46.01
Page 3 of 5
30 October 2013
TotalAlert Embedded (TAE)-Optional Feature
Ethernet Connectivity with Embedded Web Page
• Built-in web server allows remote operator to view system controls
and display information
• Ethernet communication compatible with TotalAlert and TotalAlert2
alarm systems
• Web page provided to show links to other devices on the TotalAlert
Embedded network, including alarms and other source equipment
• Electronic notification
» Accessible through any SMTP gateway
» Allows for remote alerts of alarm and warning conditions of manifold
» Allows for remote alerts of routine maintenance
» Allows for early warning of bank pressure
226000-01 - Medical Gas Piping - PD
SSB-801-00
4107 9508 46.01
Page 4 of 5
30 October 2013
Ordering Information
MN___ - HH___- ___ - ___ ___
A
B
C
D
E
MNE-HH4X4-O2-AS 4107215224
BeaconMedæs Manifold Parent Model Number Chart
Variable
Definition
Allowable Value
E
S
Description
A
Language
English
Spanish
B
No. of Cylinders
0×0
1×1S
2×2S
1×1
2×2
3×3
4×4
5×5
6×6
7×7
8×8
9×9
10×10
11×11
12×12
13×13
14×14
0×0
1×1 Space Saver Header
2×2 Space Saver Header
1×1
2×2
3×3
4×4
5×5
6×6
7×7
8×8
9×9
10×10
11×11
12×12
13×13
14×14
C
Gas
O2
N 2O
AIR
N2
IAIR
CO2
CO2O2
O2CO2
HEO2
O2HE
HE
AR
Oxygen
Nitrous Oxide
Medical Air
Nitrogen
Instrument Air
Carbon Dioxide
Carbon Dioxide-Oxygen (CO2 > 7%)
Oxygen-Carbon Dioxide (CO2 < 7%)
Helium-Oxygen (He > 80%)
Oxygen-Helium (He < 80%)
Helium
Argon
D
Delivery Pressure
A
B
C
55 psi delivery pressure
100 psi delivery pressure
180 psi delivery pressure
E
Electronics
S
T
Standard
Total Alert Embedded
Example: NFPA ENGLISH HP × HP 2×2 CYLINDER OXYGEN 55 PSI STANDARD ELEC
Example Model Number: MNE-HH2X2-O2-AS
Example: NFPA SPANISH HP × HP 2×2 SPACE SAVER NITROGEN 180 PSI TAE ELEC
Example Model Number: MNS-HH2X2S-N2-CT
226000-01 - Medical Gas Piping - PD
SSB-801-00
4107 9508 46.01
Page 5 of 5
30 October 2013
Standard Configuration
Space Saver Configuration
Manifold Length
No. of Cylinders Per Bank
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Overall Length (Inches)
36
36
38
39
41
54
56
74
76
86
104
114
116
134
BeaconMedæs
1800 Overview Drive
Rock Hill, SC 29730
Phone: (803) 817-5600
Fax: (803) 817-5750
www.beaconmedaes.com