single / dual duct terminals

Transcription

single / dual duct terminals
single / dual duct terminals
M
Redefine your comfort zone. ™ | www.titus-hvac.com
Redefine your comfort zone™ | www.titus-hvac.com
Table of Contents
SINGLE / DUAL DUCT TERMINALS
M
M2
single / dual duct terminals
single/dual duct terminal products
Single / Dual Duct Terminal Products.................................................................................................................................................. M3
single duct terminals
ESV Single Duct................................................................................................................................................................................... M5
Design Features............................................................................................................................................................................ M5
Control Strategies......................................................................................................................................................................... M7
ESV - Basic Unit with Controls..................................................................................................................................................... M9
Dimensions................................................................................................................................................................................. M10
Accessories................................................................................................................................................................................ M11
Performance Data....................................................................................................................................................................... M14
Electric Coils............................................................................................................................................................................... M21
AHRI Certification...................................................................................................................................................................... M23
dual duct terminals
EDV/MDV Dual Duct.......................................................................................................................................................................... M24
Design Features.......................................................................................................................................................................... M24
Control Strategies....................................................................................................................................................................... M25
EDV - Dual Duct without Attenuator.......................................................................................................................................... M26
Dimensions................................................................................................................................................................................. M27
Performance Data....................................................................................................................................................................... M28
EDV/EDC - Dual Duct with Attenuator....................................................................................................................................... M30
Dimensions................................................................................................................................................................................. M31
Performance Data....................................................................................................................................................................... M32
MDV/MDC - Dual Duct High Performance Blending................................................................................................................. M34
Dimensions................................................................................................................................................................................. M35
Performance Data....................................................................................................................................................................... M36
AHRI Certification...................................................................................................................................................................... M38
Single / Dual Duct Terminal Products
single / dual duct terminals
ESV
AVAILABLE CONFIGURATIONS
CONTROL OPTIONS
UNIT ACCESSORIES
• With integral attenuator
• With water coils
• With integral electric coil section
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Pneumatic
Electric
TA1 electronic
DDC controls
Factory mounting of controls by others
OEM controls (Titus Alpha BACnet)
EcoShield lining
Fibre Free lining
Steri-Loc™ lining
UltraLoc lining
Multi-outlet section
Round outlet adapter
Removable flow sensor
Access door
20g construction
Redefine your comfort zone™ | www.titus-hvac.com
single duct terminals
pages: M5-M23
M
SINGLE / DUAL DUCT TERMINALS
For detailed controls information, please refer to the Terminal Unit Accessories section
M3
single / dual duct terminals
Redefine your comfort zone™ | www.titus-hvac.com
Single / Dual Duct Terminal Products (continued)
dual duct terminals
pages: M24-M33
EDV
AVAILABLE CONFIGURATIONS
CONTROL OPTIONS
UNIT ACCESSORIES
• Non-mixing
• With integral attenuator/mixing section
• Optional mixing baffle
•
•
•
•
•
•
•
•
•
•
M
Pneumatic
DDC controls
Factory mounting of controls by others
OEM controls (Titus Alpha BACnet)
dual duct terminals
SINGLE / DUAL DUCT TERMINALS
pages: M34-M38
M4
EcoShield lining
Fibre Free lining
SteriLoc™ lining
UltraLoc lining
Removable flow sensor
20g construction
MDV
AVAILABLE CONFIGURATIONS
CONTROL OPTIONS
UNIT ACCESSORIES
• Special high performance blending
•
•
•
•
•
•
•
•
•
•
Pneumatic
DDC controls
Factory mounting of controls by others
OEM controls (Titus Alpha BACnet)
EcoShield lining
Fibre Free lining
SteriLoc™ lining
UltraLoc lining
Removable flow sensor
20g construction
single / dual duct terminals
Single Duct Design Features
Single duct terminals are the fundamental building blocks for a variable
air volume (VAV) system. Their primary function is to regulate airflow to
a zone, in response to zone temperature requirements. The Titus ESV is
unique as it incorporates many design features that increase performance,
decrease installation and service cost and offers increased value, over and
above this basic function.
All VAV terminals are not equal! By specifying the Titus ESV, you are
assured of accurate, AHRI Certified performance ratings. All units are
tested, and data shown, in accordance with AHRI Standards. A wide
selection of unit configurations, accessories and control types provide
considerable scope for problem solving and cost-effective innovation.
Building owners will benefit from the energy efficient low leakage design,
reducing utility expenses. Control accuracy, especially at minimum flow
rates, is easier to achieve with a Titus multi-point inlet velocity sensor.
Control accuracy is critical in maintaining good air quality reducing energy
waste.
The ESV’s standard insulation is a dual density liner. The skin resists
abrasion and erosion from air movement. The body maximizes thermal
and acoustical performance. The Titus single blade damper design helps
reduce noise levels too, for a quieter work environment.
Redefine your comfort zone™ | www.titus-hvac.com
LEADING THE INDUSTRY: THE TITUS ESV SINGLE DUCT VAV TERMINAL
The ESV’s compact size and easy access for service saves time and
expense in installation. The ESV fits easily in cramped mechanical spaces,
either in new building construction or retrofit.
ESV Casing Leakage, cfm
INLET
SIZE
4, 5, 6
7, 8
9, 10
12
14
16
0.5
2
4
4
5
6
7
∆PS, IN WG
1.0
2.0
3
4
5
7
6
8
7
10
9
13
10
14
Damper Leakage, cfm
INLET
SIZE
4, 5, 6
7, 8
9, 10
12
14
16
3.0
5
9
10
12
16
17
1.0
3
3
3
3
3
4
∆PS, IN WG
2.0
4.0
4
6
4
6
4
6
4
6
5
7
5
7
6.0
7
7
7
7
8
9
M
MORE REASONS TO SPECIFY AND SELECT THE TITUS ESV:
Titus innovation carries through the widest array of standard single duct
terminal configurations. ETL listed electric coils, manufactured by Titus,
are installed, wired and functionally tested as an integral unit before
shipment for quicker, trouble-free job-site installation. Multiple outlets
with standard locking balancing dampers and integral attenuators are
also available.
Fibre Free eliminates the requirement for foil linings and solid inner
liners since there is no fiberglass in the airstream. Additionally, Fibre
Free minimizes mold growth since it holds no moisture, is acoustically
preferable to foil or solid metal linings and maintains acceptable thermal
protection. All of these benefits are available at a competitive price and
significantly less than solid metal liners.
EcoShield is a sustainable liner comprised of recycled denim making it
environmentally friendly and contains no harmful irritants or chemicals.
Titus - experts in DDC zone control!
With a detailed understanding developed through years of selling and
supporting the powerful TD1 digital controller, and now the Titus BACnet
OEM controls, Titus has industry leading experience in the application
of Direct Digital Control (DDC) to terminals. This same expertise is made
available when your project requires quality engineering, coordination and
manufacturing for factory mounting when controls are supplied by others.
Count on Titus - the industry leader in VAV!
DESIGN FEATURES
Titus continues to offer the most innovative and popular lining alternatives
for special applications including Fibre Free; the industry benchmark
SteriLoc; and the premium double wall liner, UltraLoc and EcoShield
which is the only natural fiber insulation on the market.
SteriLoc adds the feature of a very high density, rigid insulation and
special “Z-Strip” construction for an extremely rigid terminal. Sound levels
are generally superior to dual wall construction, while offering virtually
identical levels of protection.
SteriLoc provides a smooth, nonporous skin to guard against mold and
bacteria growth. Erosion is eliminated, as there is no glass fiber exposure
to the airstream. It has reinforced surfaces that can be wiped down.
M5
single / dual duct terminals
Redefine your comfort zone™ | www.titus-hvac.com
Design Features (continued)
M
Removable flow sensor (optional)
Unique integral fold fabrication method increases lining and
casing integrity and minimizes leakage
Beaded inlet for consistent roundness and low leakage
construction, sized to fit standard round duct
Standard insulation is ½-inch dual density fiberglass, to resist
erosion at surface velocities up to 5,000 fpm. Meets requirements
of NFPA 90A and UL181.
Delrin® damper bearings provide smoother damper operation
AeroCrossTM multi-point, center averaging sensor amplifies flow
signal for best control of low flow rates. Center averaging feature
provides signal accuracy regardless of inlet duct configuration.
Damper design provides smoother airflow for reduced sound
levels and lower leakage
DESV
Flow measurement taps for easy balancing connections
NEMA 1 control enclosure available for protection of electronic
controls. Double backplane construction for strength and easier
control installation, with no exposed screw tips for safe handling.
Optional Fibre Free, reinforced sealed skin SteriLoc, or
metal lined UltraLoc liners guard against environments favoring
bacteria and mold growth. Fibre Free & EcoShield are ideal IAQ
insulation providing acoustical and thermal characteristics of
fiberglass insulation without the concern of fiberglass in the
airstream. All liners meet UL 181 and NFPA 225 (25/50).
UL Class II transformers and disconnect switches available installed
for use with any electronic control configuration
DESIGN FEATURES
Multiple knockouts in sizes from 7/16-inch to 11/8-inch to
accommodate almost any field connection requirement
M6
DESV
SINGLE DUCT CONTROL STRATEGIES
single / dual duct terminals
Pneumatic: See pg. O18 / Analog: See pg. O11 / Digital: See pg. O5
cfm Increase
For detailed information on specific control types, refer to the following pages in Section O:
Max.
Min.
Room Temperature Increase
ow
Fl
cfm Increase
er
at
Pneumatic: See pg. O18 / Analog: See pg. O11 / Digital: See pg. O5
Max.
tW
Ho
VAV Cooling, Hot Water Reheat
As the room temperature increases, the unit modulates the hot water coil valve toward the closed
position. On a further increase in room temperature, the unit modulates the cold airflow from the
minimum (which must be greater than zero) to the maximum setting.
Redefine your comfort zone™ | www.titus-hvac.com
Variable Air Volume - VAV Cooling
As the room temperature increases over setpoint, the unit modulates the cold airflow from the
minimum (which may be zero flow) to the maximum setting.
Min.
Room Temperature Increase
Ho
VAV Cooling, Dual Minimum Flows with Hot Water Reheat
In the cooling mode, as the room temperature increases, the unit thermostat modulates the cold
airflow from the lower minimum to the maximum setting.
ow
VAV Cooling and VAV Heating, Local Heat Flows
In the heating mode, as the room temperature increases, the unit modulates the airflow from maximum
to minimum and modulates the hot water coil valve toward the closed position.
Max.
Max.
Room Temperature Increase
VAV Cooling and VAV Heating, Central Heat Flows
In the heating mode, as the room temperature increases, the unit modulates the airflow from maximum
to minimum and modulates the hot water coil valve toward the closed position.
Max.
A further increase in room temperature changes the operation to the cooling mode, and the unit
modulates the cold airflow from minimum to maximum, which is different from the heating maximum
(usually higher). Both the heating and the cooling maximum airflows are adjustable.
Pneumatic: See pg. O18 / Analog: See pg. O11 / Digital: See pg. O5
cfm Increase
Max.
CONTROL STRATEGIES
low
rF
ate
cfm Increase
tW
Ho
Pneumatic: See pg. O18 / Analog: See pg. O11 / Digital: See pg. O5
Min.
Room Temperature Increase
Pneumatic: See pg. O18 / Analog: See pg. O11 / Digital: See pg. O5
A further increase in room temperature changes the operation to the cooling mode, and the unit
modulates the cold airflow from minimum to maximum, which is the same as the heating maximum.
Alt. Min.
M
Fl
In the heating mode, the unit references the alternate (higher) minimum airflow. As the room
temperature decreases, the unit modulates the airflow from the maximum to the higher minimum,
then modulates the hot water coil valve toward the open position. The valve operates only in the
heating mode.
cfm Increase
er
at
tW
Max.
Room Temperature Increase
M7
single / dual duct terminals
Constant Volume, Hot Water Reheat
The cold airflow remains constant regardless of changes in duct pressure or room temperature. As the
room temperature increases, the unit modulates the hot water coil valve toward the closed position.
low
rF
cfm Increase
a te
tW
Pneumatic: See pg. O18 / Analog: See pg. O11 / Digital: See pg. O5
Ho
Room Temperature Increase
VAV Cooling, Electric Reheat
As the room temperature increases, the unit de-energizes the electric heating coil one step at a time.
On a further increase in room temperature, the unit modulates the cold airflow from the minimum
(which must be greater than zero) to the maximum setting.
Pneumatic: See pg. O18 / Analog: See pg. O11 / Digital: See pg. O5
Step 2
Max.
Step 1
cfm Increase
Redefine your comfort zone™ | www.titus-hvac.com
Control Strategies (continued)
Min.
Room Temperature Increase
VAV Cooling, Dual Minimum Flows with Electric Reheat
In the cooling mode, as the room temperature increases, the room thermostat modulates the cold
airflow from the lower minimum to the maximum setting.
In the heating mode, as the room temperature decreases, the unit modulates the airflow from the
lower minimum to the higher minimum, then energizes the electric heating coil stages.
Pneumatic: See pg. O18 / Analog: See pg. O11 / Digital: See pg. O5
Step 2
Alt. Min.
cfm Increase
M
Max.
Step 1
Min.
Room Temperature Increase
M8
When the signal is removed, the unit resumes normal control of airflow. With the central system now
supplying cold air, as room temperature increases, the unit modulates the cold airflow from minimum
to the maximum setting.
Pneumatic: See pg. O18 / Analog: See pg. O11 / Digital: See pg. O5
Max.
cfm Increase
CONTROL STRATEGIES
VAV Cooling with Morning Warmup
When provided the appropriate signal, the damper in the terminal modulates to maximum or fully
open position. Heated air from the central system moves through the duct (the flow may be pressure
dependent with some control types).
Min.
Room Temperature Increase
Single Duct Terminal Units
single / dual duct terminals
Redefine your comfort zone™ | www.titus-hvac.com
ESV
• ESV can be installed horizontally, vertically or at any angle; unit
operation is not affected by position
• Choice of right or left hand control location
• Standard AeroCross multi-point center averaging velocity sensor
(except EESV)
• Standard dual density insulation
• Controls supplied by Titus are factory calibrated for a quicker start-up
• Standard 22-gauge casing with slip and drive connection
ESV
See website for Specifications
AVAILABLE MODELS:
PESV / Pneumatic
EESV / Electric
AESV / Analog Electronic
DESV / Digital Electronic
M
ESV cutaway view
OVERVIEW
Single Duct terminals are the fundamental building blocks for Variable
Air Volume (VAV) systems. Their primary function is to regulate airflow
to a zone, in response to zone temperature requirements. The Titus
ESV is unique as it incorporates many design features that increase
performance, decrease service and installation costs, and offer
increased value, over and above this basic function.
ESV
M9
single / dual duct terminals
Redefine your comfort zone™ | www.titus-hvac.com
DIMENSIONS
M
ESV UNIT DIMENSIONS
Pneumatic
Actuator
PESV
W
M
L
Thermostat &
20 psi Main Air
Connections for
¼” Dia. Tubing
Slip and Drive
Cleat Connection
D
H
Multi-Point
Center Averaging
Velocity Sensor
DESV
AESV
EESV
4½”
F
W
Control
Cover
(optional)
M
F
L
G
12¼”
H
F
D
Control
Enclosure
6½”
Slip & Drive
Cleat
Connection
18”
DIMENSIONS
(Optional for cooling only)
M10
F
INLET
SIZE
CFM
RANGE
D
4
5
6
7
8
9
10
12
14
16
24X16
0-225
0-350
0-500
0-650
0-900
0-1050
0-1400
0-2000
0-3000
0-4000
0-8000
37/8
47/8
57/8
67/8
77/8
87/8
97/8
117/8
137/8
157/8
7
23 /8 - 157/8
PESV
17/8
17/8
17/8
7
/8
7
/8
7
/8
AESV
DESV
EESV
21/8
21/8
21/8
11/8
11/8
11/8
G
H
L
M
W
73/8
73/8
73/8
73/8
73/8
53/8
53/8
53/8
33/8
33/8
53/8
8
8
8
10
10
12½
12½
15
17½
18
18
15½
15½
15½
15½
15½
15½
15½
15½
15½
15½
15
53/8
53/8
33/8
33/8
33/8
33/8
33/8
33/8
33/8
33/8
33/8
12
12
12
12
12
14
14
16
20
24
38
All dimensions are in inches
single / dual duct terminals
ACCESSORIES
Titus’ unique integral design minimizes casing
leakage and disturbance to airflow with no
casing or insulation seams.
39½
6½
W
18
INTEGRAL ELECTRIC COIL
12¼
With a rigid one piece assembly, Titus locates
the heating elements for optimal heat transfer
and insets them for protection during shipment
and installation.
STANDARD FEATURES:
• Primary automatic reset thermal
cutout (one per coil)
• Secondary manual reset thermal cutout
• Airflow switch (differential pressure)
• Derated nickel chrome heating elements
• Magnetic or safety contactors
(as required)
• Line terminal block
• Control terminal block
• ETL listed
• 80/20 nickel chrome element wire
H
6¼
39½
W
12
Redefine your comfort zone™ | www.titus-hvac.com
INTEGRAL SOUND ATTENUATOR
H
365/8
M
L
W
Side View
End View
OPTIONAL FEATURES:
•
•
•
•
•
•
Class ll, 24 volt control transformer
Mercury contactors
Door interlock disconnect switch
Main supply fuses
Dust tight construction
Removable flow sensor
H
HOT WATER REHEAT COILS
39½
M
Details on water coil features are shown on
performance pages M18-22.
L
W
H
INTEGRAL SOUND ATTENUATOR
WITH OPTIONAL HOT WATER REHEAT
COIL
Side View
H
M
W
4, 5
6
7, 8
9, 10
12
14
16
24 x 16
8
8
10
12½
15
17½
18
18
53/8
33/8
33/8
33/8
33/8
33/8
33/8
33/8
12
12
12
14
16
20
24
38
WATER COIL
L (1-2 ROW)
L (3-4 ROW)
5
7¼
5
7¼
5
7¼
5
7¼
5
7¼
7½
9¾
7½
9¾
5
7¼
ACCESSORIES
INLET
SIZE
End View
Note: The total length of the ESV basic unit and accessories (attenuators and coils) is the
summation of basic unit length and the accessories length
All dimensions are in inches
M11
single / dual duct terminals
Redefine your comfort zone™ | www.titus-hvac.com
ACCESSORIES
MULTI-OUTLET PLENUMS FOR SINGLE DUCT TERMINALS
2 Outlets
3 Outlets
36”
33/8” TYP.
G
2 Outlets
W
M
G
H
ESV Unit Sizes Outlet Size D
4, 5, 6
7, 8
8
9, 10
9, 10
12
12
14
14
16
16
57/8
77/8
77/8
97/8
77/8
117/8
97/8
117/8
97/8
117/8
97/8
W
D TYP.
36”
M
H
33/8” TYP.
G
5 Outlets
W
D TYP.
D TYP.
D TYP.
33/8” TYP.
4 Outlets
M
3 Outlets
5 Outlets
36”
33/8” TYP.
G
H
D TYP.
4 Outlets
36”
D TYP.
W
H
D TYP.
2 Outlets
G
M
43/8
53/8
53/8
63/8
63/8
63/8
-
3 Outlets
G
M
43/8
53/8
53/8
53/8
63/8
63/8
63/8
63/8
63/8
63/8
-
4 Outlets
G
M
53/8
12
53/8
14
53/8
12
63/8
14
63/8
14
63/8
14
5 Outlets
G
M
53/8
12
63/8
14
63/8
14
63/8
14
H
W
8
10
10
12½
12½
15
15
17½
17½
18
18
12
12
12
14
14
16
16
20
20
24
24
ROUND OUTLETS
ACCESSORIES
33/8“
M12
D
4“
W
D
H
All dimensions are in inches
D TYP.
Unit Size
4
5
6
7
8
9
10
12
14
16
D
37/8
47/8
57/8
67/8
77/8
87/8
97/8
117/8
137/8
157/8
H
8
8
8
10
10
12½
12½
15
17½
18
W
12
12
12
12
12
14
14
16
20
24
single / dual duct terminals
ACCESSORIES
Redefine your comfort zone™ | www.titus-hvac.com
REMOVABLE FLOW SENSOR
Removable Sensor
Installed
#8 Sheet metal screw
6 places
Sensor
Removed
Removable flow
sensor assembly
M
ESV WITH ACCESS DOOR OPTION
ESV Terminal Unit
Gasket (Access door is sealed with
foam gasket material)
Insulation type specified per order
Access Door (Insulated)
6.00
6.00
2.25
2.25
9.00
9.00
39.50
0.50
0.50
ACCESSORIES
15.50
Right Hand Unit Shown
Basic Unit w/Attenuator
(Bottom View)
Basic Unit
(Bottom View)
All dimensions are in inches
M13
single / dual duct terminals
Redefine your comfort zone™ | www.titus-hvac.com
PERFORMANCE DATA
M
RECOMMENDED PRIMARY AIR CFM RANGES / ALL TERMINALS
Control Types:
PESV / Pneumatic
AESV / Analog Electronic
DESV / Digital Electronic
QUICK SELECTION PROCEDURE
1.Select unit inlet size based upon acoustic
parameters and/or maximum pressure
drop requirements, using pages M15-M16
2.Check inlet size selection against cfm
control limits based on control type shown
on this page
3.Select accessories (multi-outlets,
attenuators) as required
4.Select reheat coil, if required. Make your
selection using the actual heating flow
rate, not cooling.
cfm Ranges of Minimum and Maximum Settings
Inlet Size
Total cfm
Range
4
5
6
7
8
9
10
12
14
16
24 x 16
0-225
0-350
0-500
0-650
0-900
0-1050
0-1400
0-2000
0-3000
0-4000
0-8000
PESV - Pneumatic
PESV - Pneumatic
AESV - Analog Electronic
DESV - Digital
Titus II Controller
Titus I Controller
TA1 Controller
Typical Controller
Minimum
45*-170
65*-270
80*-330
105*-425
145*-590
175*-700
230*-925
325*-1330
450*-1800
580*-2350
1400*-5200
Maximum
80-225
120-350
150-500
190-650
265-900
315-1050
415-1400
600-2000
810-3000
1100-4000
2600-8000
Minimum
55*-170
85*-270
105*-330
135*-425
190*-590
225*-700
300*-925
425*-1330
575*-1800
750*-2350
1800*-5200
Maximum
80-225
120-350
150-500
190-650
265-900
315-1050
415-1400
600-2000
810-3000
1100-4000
2600-8000
MINIMUM
45*-225
65*-350
80*-500
105*-650
145*-900
175*-1050
230*-1400
325*-2000
450*-3000
580*-4000
1400*-7500
MAXIMUM
45-225
65-350
80-500
105-650
145-900
175-1050
230-1400
325-2000
450-3000
580-4000
1400-7500
MINIMUM
30*-225
40*-350
45*-500
70*-650
90*-900
120*-1050
145*-1400
190*-2000
300*-3000
385*-4000
720*-7500
MAXIMUM
30-225
40-350
45-500
70-650
90-900
120-1050
145-1400
190-2000
300-3000
385-4000
720-7500
*Factory cfm settings (except zero) will not be made below this range because control accuracy is reduced. On pressure dependent units, minimum
cfm is always zero and there is no maximum.
PERFORMANCE DATA
Note: On controls mounted by Titus but supplied by others (FMA or Factory Mounting Authorization), these values are guidelines only. Controls
mounted on an FMA basis are calibrated in the field.
M14
single / dual duct terminals
PERFORMANCE DATA
Size
4
5
6
7
8
9
10
12
14
40
100
125
150
175
200
150
200
250
300
350
300
350
400
450
500
450
500
550
600
650
600
650
700
750
800
800
850
900
950
1000
900
1000
1100
1200
1300
1200
1400
1600
1800
2000
1500
1800
2100
2400
2700
2000
2400
2800
3200
3600
3900
4600
5300
6000
6700
Min
∆Ps
0.02
0.03
0.04
0.06
0.08
0.01
0.02
0.03
0.04
0.06
0.07
0.10
0.13
0.16
0.20
0.07
0.09
0.10
0.12
0.15
0.02
0.02
0.02
0.02
0.03
0.04
0.04
0.05
0.06
0.06
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.02
0.03
0.04
0.05
0.06
0.02
0.02
0.03
0.04
0.05
0.03
0.04
0.06
0.07
0.09
2
49
52
55
58
60
49
53
55
58
60
55
57
58
59
59
59
60
60
61
62
59
60
60
61
62
58
58
59
59
60
60
60
61
62
63
58
60
61
61
62
56
58
59
60
62
55
57
59
61
62
70
73
75
77
79
3
45
49
52
55
57
44
48
52
54
56
49
52
53
55
56
48
50
51
53
54
50
51
52
53
54
47
48
49
50
50
50
51
52
53
54
50
52
53
55
56
51
53
54
55
56
48
51
53
55
56
65
68
71
73
75
0.5” ∆Ps
4 5 6
36 33 31
39 36 32
41 37 34
42 39 35
44 40 36
36 32 31
39 35 34
41 37 35
43 39 37
45 40 38
40 35 32
42 37 34
44 39 35
45 40 36
47 42 37
42 38 33
43 39 34
44 40 35
45 42 35
46 43 36
44 40 38
44 41 39
45 42 40
46 43 40
47 43 41
43 36 34
43 37 34
44 37 35
44 37 35
44 38 36
47 45 42
48 46 43
48 47 44
48 47 45
49 48 45
47 41 37
48 42 38
50 43 40
51 44 41
52 45 43
45 43 40
46 44 41
47 45 42
48 46 43
49 47 44
43 41 39
45 43 41
46 44 42
48 46 44
49 47 45
63 59 57
66 62 59
68 64 61
71 66 63
72 67 64
7
26
27
28
29
30
25
27
29
30
31
28
29
30
31
32
24
24
25
25
26
32
32
33
34
34
30
31
31
31
31
29
30
32
32
33
30
32
34
35
36
36
36
37
38
38
31
33
34
36
37
54
55
56
57
58
NC
11
16
20
23
25
10
15
20
22
24
16
20
21
23
24
20
22
22
23
24
20
22
22
23
24
19
19
20
20
22
22
22
23
24
25
20
22
24
25
26
18
21
22
23
24
36
18
21
23
24
38
41
43
47
48
2
52
55
58
61
63
53
56
59
62
63
59
60
61
62
63
61
62
63
63
64
62
63
63
64
65
61
61
62
62
63
63
64
65
65
66
62
63
64
65
66
60
62
63
64
66
59
61
63
65
66
72
75
78
80
82
3
48
52
55
58
60
49
53
56
59
61
54
57
58
60
61
54
55
57
58
59
55
56
57
58
59
53
54
55
56
56
57
58
58
59
60
56
57
59
60
61
56
58
59
60
61
53
56
58
60
61
68
71
73
75
77
Octave Band Sound Power, Lw
1.0” ∆Ps
1.5” ∆Ps
4 5 6 7 NC 2 3 4 5 6
39 36 35 31 15 53 50 41 37 37
42 38 36 32 20 57 54 44 40 39
44 40 38 34 23 60 57 46 41 40
46 42 39 34 27 63 59 48 43 41
47 43 40 35 29 65 62 49 44 42
41 36 35 30 16 55 51 43 38 37
44 38 37 32 21 59 55 46 40 40
46 40 39 34 24 62 59 49 42 41
48 42 41 35 28 64 61 50 44 43
49 43 42 36 30 66 63 52 45 44
45 39 37 33 22 61 57 48 41 39
47 41 38 34 25 62 59 50 43 40
49 42 39 35 27 63 61 52 44 42
50 44 40 36 29 64 63 53 46 43
51 45 41 37 30 65 64 54 47 44
48 42 38 30 23 62 57 51 45 41
49 43 39 30 24 63 58 52 46 42
50 45 40 31 25 64 59 53 47 43
51 46 41 31 27 65 61 54 48 44
52 47 41 32 28 65 62 55 49 44
49 43 43 39 24 64 58 52 46 45
50 44 44 40 25 65 59 53 47 46
50 45 44 41 25 65 60 53 47 47
51 46 45 41 27 66 61 54 48 48
52 47 46 42 28 66 62 55 49 48
49 42 40 35 23 62 57 52 46 44
49 43 41 35 23 63 58 53 46 45
50 43 41 35 24 64 58 53 47 45
50 43 42 36 24 64 59 54 47 45
50 44 42 36 25 65 60 54 47 46
53 50 48 37 27 65 60 57 53 52
54 51 49 38 28 66 61 57 54 53
54 52 50 39 28 67 62 57 55 54
54 53 51 40 28 67 63 58 56 55
55 53 52 41 29 68 63 58 56 55
52 47 43 37 26 64 59 56 50 46
54 48 45 39 28 65 60 57 52 48
55 49 46 40 29 66 62 59 53 50
56 50 48 41 30 67 63 60 54 51
57 51 49 43 31 68 64 61 55 52
50 48 45 41 24 62 59 53 51 48
51 49 46 42 27 64 60 54 52 49
52 50 47 43 28 66 62 55 53 50
53 51 48 43 29 67 63 56 54 51
54 52 49 44 30 68 64 57 55 52
47 45 44 38 21 61 56 50 47 47
49 47 46 39 24 64 59 52 49 49
51 48 47 41 27 66 61 54 50 50
52 50 49 42 29 67 62 55 52 52
54 51 50 44 30 69 64 56 53 53
66 62 61 58 41 74 69 67 63 63
68 64 63 60 43 77 72 70 66 65
71 66 65 61 47 79 74 72 68 67
73 68 66 62 49 81 76 74 70 68
75 70 68 63 51 83 78 76 71 70
• Radiated sound is the noise transmitted through the unit casing
• Min ∆Ps is the static pressure drop from the unit inlet to the unit
outlet with primary damper full open
• Sound power levels are in dB, ref 10-12 watts
• Sound performance based on units lined with standard dual density
fiberglass lining
7
34
36
37
38
38
33
35
37
38
39
36
37
38
39
40
33
34
34
35
35
44
45
45
46
47
38
38
38
38
39
41
42
43
44
45
41
42
44
45
47
45
45
46
47
47
41
43
45
46
48
61
63
64
65
66
NC
17
22
25
28
31
18
23
28
30
33
25
28
30
33
34
25
27
28
30
31
27
28
29
30
31
26
27
27
28
29
31
31
31
33
33
30
31
34
35
36
28
29
31
33
34
24
28
30
31
34
42
46
48
50
52
2
55
58
61
64
66
57
60
63
65
67
63
64
65
66
67
63
64
66
66
66
65
66
67
67
68
63
64
65
65
66
67
67
68
69
69
66
67
68
69
69
64
66
67
69
70
63
65
67
69
71
75
78
80
82
84
3
51
55
58
61
63
53
57
61
63
65
59
62
63
65
67
59
60
62
63
64
60
61
62
63
64
59
60
61
62
62
63
64
64
65
66
61
63
64
65
67
61
63
64
65
66
58
61
63
64
66
70
73
75
77
79
2.0” ∆Ps
4 5 6
43 38 39
45 41 40
47 42 42
49 44 43
51 45 44
45 39 39
48 42 41
51 44 43
52 45 44
54 47 45
50 42 41
52 44 42
54 46 43
55 47 45
56 49 46
53 46 43
54 48 44
55 49 45
56 50 46
57 51 46
54 47 47
55 48 48
56 49 49
56 50 50
57 51 50
55 48 47
55 49 47
56 49 48
56 49 48
57 50 48
59 56 54
59 56 55
60 57 56
60 58 57
61 58 58
58 53 49
60 54 51
61 55 52
62 56 54
63 57 55
55 53 50
56 54 51
58 55 52
58 56 53
59 57 54
52 49 49
54 51 51
55 52 52
57 53 54
58 55 55
68 64 65
71 67 67
73 69 68
75 71 70
77 72 71
7
36
38
39
40
41
35
37
39
40
41
38
39
40
41
42
35
36
37
37
38
47
48
48
49
50
40
40
40
40
40
44
45
46
47
48
43
45
47
48
49
47
48
49
49
50
44
46
48
49
50
63
64
66
67
68
NC
18
23
27
30
33
21
25
30
33
35
28
31
33
35
37
28
29
31
33
34
29
30
31
33
34
29
29
30
31
31
34
34
35
35
36
32
35
36
37
38
30
33
34
35
36
27
30
33
34
36
43
47
49
51
53
• All performance based on tests conducted in accordance with
ASHRAE 130-2008 and AHRI 880-2011
• All NC levels determined using AHRI 885-2008 Appendix E. See
Terminal Unit Engineering Guidelines.
• Dash (-) in space denotes NC value less than NC10
• Only highlighted data points are AHRI certified. See page M23 for
AHRI Certified Performance Listings.
M
PERFORMANCE DATA
16
CFM
Redefine your comfort zone™ | www.titus-hvac.com
PESV, AESV, DESV / RADIATED SOUND PERFORMANCE
M15
single / dual duct terminals
Redefine your comfort zone™ | www.titus-hvac.com
PERFORMANCE DATA
PESV, AESV, DESV / DISCHARGE SOUND PERFORMANCE
Size
4
5
6
7
M
8
9
10
12
PERFORMANCE DATA
14
M16
16
40
CFM
100
125
150
175
200
150
200
250
300
350
300
350
400
450
500
450
500
550
600
650
600
650
700
750
800
800
850
900
950
1000
900
1000
1100
1200
1300
1200
1400
1600
1800
2000
1500
1800
2100
2400
2700
2000
2400
2800
3200
3600
3900
4600
5300
6000
6700
Min
∆Ps
0.02
0.03
0.04
0.06
0.08
0.01
0.02
0.03
0.04
0.06
0.07
0.10
0.13
0.16
0.20
0.07
0.09
0.10
0.12
0.15
0.02
0.02
0.02
0.02
0.03
0.04
0.04
0.05
0.06
0.06
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.02
0.03
0.04
0.05
0.06
0.02
0.02
0.03
0.04
0.05
0.03
0.04
0.06
0.07
0.09
2
70
72
73
75
76
68
71
73
74
76
68
69
71
72
73
71
71
72
72
72
73
74
74
75
75
73
74
74
75
75
75
76
76
77
78
73
74
75
76
76
69
70
71
72
72
68
70
71
73
74
76
77
79
80
81
3
56
60
63
65
67
53
57
60
62
64
60
62
63
65
66
61
62
64
65
66
63
64
65
66
67
61
62
63
63
64
62
63
63
64
65
64
65
66
68
69
57
59
60
61
62
59
62
64
65
67
70
71
73
74
75
0.5” ∆Ps
4 5 6
47 42 40
50 44 42
52 47 44
54 48 45
56 50 46
47 43 41
50 46 43
53 49 45
55 51 47
57 52 48
54 50 45
55 52 47
57 54 48
58 55 49
60 56 50
54 51 47
55 52 48
56 54 49
57 55 49
58 56 50
56 52 48
57 53 48
57 54 49
58 54 49
58 55 50
57 53 49
57 53 49
58 54 50
58 54 50
59 55 50
58 55 50
59 56 50
59 57 51
60 57 52
61 58 52
60 55 53
62 56 54
63 57 55
64 58 55
65 59 56
56 53 50
58 53 50
59 54 51
60 54 51
61 54 51
57 54 52
59 55 53
61 57 55
63 58 56
65 59 57
66 62 61
67 63 63
69 65 64
70 66 65
71 67 67
7
33
35
36
37
38
34
36
38
39
40
39
40
41
42
43
40
40
41
42
43
40
41
41
42
42
43
43
43
44
44
44
44
45
45
46
46
47
48
49
50
44
44
44
44
45
45
46
48
49
50
56
58
60
61
62
NC
28
30
31
34
35
25
29
31
29
31
21
22
25
26
28
25
25
26
26
26
28
29
29
28
28
25
26
26
28
28
28
29
29
30
31
25
26
28
29
29
20
21
22
24
24
19
21
22
25
26
29
30
33
34
35
2
71
73
75
76
77
70
73
75
77
78
72
74
75
76
77
74
74
75
75
75
76
77
77
77
78
76
76
77
78
78
77
78
79
79
80
76
77
78
79
79
72
73
74
75
76
71
73
75
76
77
81
82
84
85
86
3
59
63
65
68
70
58
61
65
67
69
65
67
69
70
72
66
68
69
70
72
69
70
71
72
73
66
67
68
68
69
67
68
69
70
70
69
71
72
73
74
63
65
66
67
68
63
66
68
69
71
75
77
78
79
80
Octave Band Sound Power, Lw
1.0” ∆Ps
1.5” ∆Ps
4 5 6 7 NC 2 3 4 5 6
51 46 47 41 29 72 61 54 49 50
54 49 49 43 31 74 64 57 52 52
57 51 50 44 34 76 67 60 54 54
59 53 51 45 35 77 69 62 56 55
61 55 53 46 36 78 72 63 58 56
52 47 47 42 28 72 60 55 50 51
56 51 49 44 31 75 64 59 53 53
58 53 51 45 34 77 67 61 56 55
60 55 53 46 33 78 70 63 58 56
62 57 54 47 34 80 72 65 60 57
59 54 51 46 26 75 68 62 57 54
61 56 52 47 29 76 70 64 59 55
62 58 53 48 30 78 72 65 60 57
64 59 54 49 31 79 73 67 62 58
65 61 55 50 33 80 75 68 63 59
59 54 51 46 29 75 70 61 56 54
60 56 52 47 29 76 71 63 58 55
61 57 53 48 30 76 73 64 59 56
62 58 54 48 30 77 74 64 60 57
63 59 55 49 32 77 75 65 61 58
60 55 52 47 31 78 72 62 56 55
61 56 53 47 33 78 73 63 57 55
61 56 53 48 33 79 74 64 58 56
62 57 54 48 31 79 75 64 58 56
63 58 54 49 32 79 76 65 59 57
61 57 54 49 29 77 69 63 59 57
61 57 54 50 29 78 70 63 59 57
62 57 55 50 30 79 70 64 59 57
62 58 55 50 31 79 71 64 60 58
62 58 55 50 31 80 72 65 60 58
62 59 55 50 30 78 70 65 61 58
63 60 56 51 31 79 71 66 62 59
64 61 56 51 33 80 72 66 63 60
64 61 57 52 33 81 73 67 64 60
65 62 58 53 34 81 74 68 65 61
64 59 57 52 29 78 72 66 62 60
66 61 59 53 30 79 74 68 63 61
67 62 59 55 31 80 75 69 64 62
68 63 60 56 33 80 76 71 65 63
69 64 61 56 33 81 77 72 66 64
56 59 57 53 24 74 67 56 62 62
58 59 58 53 25 75 68 58 63 62
59 60 58 54 26 76 69 59 63 63
60 60 59 54 28 77 70 60 64 63
61 61 59 54 29 78 71 61 64 63
57 58 56 51 22 73 66 57 61 59
59 60 58 52 25 75 68 59 62 61
61 61 59 54 28 77 70 61 64 62
63 62 60 55 29 78 72 63 65 63
65 63 61 56 30 79 73 65 66 64
66 67 67 62 35 84 78 66 69 70
67 68 68 64 37 85 80 67 71 71
69 69 70 65 39 87 81 69 72 73
70 71 71 67 40 88 82 70 73 74
71 72 72 68 42 89 83 71 74 75
• Discharge sound is the noise emitted from the unit discharge into
the downstream ductwork
• Min ∆Ps is the static pressure drop from the unit inlet to the unit
outlet with primary damper full open
• Sound power levels are in dB, ref 10-12 watts
• Sound performance based on units lined with standard dual density
fiberglass lining
7
46
47
49
50
51
46
48
50
51
52
50
51
52
53
54
49
50
51
52
53
51
51
52
52
53
53
54
54
54
54
54
55
55
56
56
56
57
58
59
60
59
59
59
59
60
54
56
57
59
60
66
67
69
70
71
NC
30
33
35
36
38
30
34
36
34
36
30
31
34
35
36
30
31
33
34
36
34
34
35
34
36
30
31
33
33
34
31
33
34
35
35
31
33
34
36
37
26
28
29
30
31
25
28
30
31
33
39
40
43
44
45
2
73
75
76
78
79
73
76
78
79
81
77
78
79
81
82
77
77
78
78
79
79
79
80
80
81
78
79
80
80
81
79
80
81
82
82
79
80
81
81
82
76
77
78
78
79
74
76
78
79
81
86
88
89
90
91
3
62
65
68
71
73
62
66
69
72
74
70
72
74
76
77
72
74
75
76
77
75
76
77
78
78
71
72
72
73
74
73
74
74
75
76
74
76
77
78
79
69
71
72
73
74
68
70
72
73
75
80
82
83
84
85
2.0” ∆Ps
4 5 6
56 51 53
59 54 55
61 56 57
64 58 58
65 60 59
58 52 53
61 55 55
63 58 57
66 60 59
67 61 60
64 58 56
66 60 58
67 62 59
69 63 60
70 65 61
63 58 56
64 59 57
65 60 58
66 61 59
67 62 59
64 57 57
65 58 57
65 59 58
66 60 58
67 60 59
65 60 59
65 61 59
66 61 59
66 61 60
66 62 60
67 63 61
68 64 61
68 65 62
69 66 63
69 66 63
68 64 62
70 65 63
71 66 64
72 67 65
73 68 66
56 65 65
58 65 65
59 66 66
60 66 66
61 67 66
57 63 61
59 64 62
61 66 64
63 67 65
65 68 66
66 71 72
67 73 74
69 74 75
70 75 76
71 76 77
7
49
51
52
53
54
49
51
53
54
55
53
54
55
56
57
52
53
54
55
55
54
54
55
55
56
56
56
57
57
57
57
57
58
59
59
59
60
61
62
63
62
63
63
63
63
57
58
60
61
62
68
70
71
73
74
NC
31
34
35
38
39
31
35
38
35
38
33
34
35
38
39
33
34
36
37
38
36
37
38
38
38
31
33
34
34
35
33
34
35
36
36
33
36
37
38
39
29
30
31
32
33
26
29
31
33
35
42
44
45
47
48
• All performance based on tests conducted in accordance with
ASHRAE 130-2008 and AHRI 880-2011
• All NC levels determined using AHRI 885-2008 Appendix E. See
Terminal Unit Engineering Guidelines.
• Dash (-) in space denotes NC value less than NC10
• Only highlighted data points are AHRI certified. See page M23 for
AHRI Certified Performance Listings.
single / dual duct terminals
PERFORMANCE DATA
Sizes 4-5-6
Rows
One-Row
Two-Row
Sizes 7-8
Rows
One-Row
Two-Row
Sizes 9-10
Rows
One-Row
Two-Row
Rows
Size 12
Two-Row
50
3.7
3.8
3.9
3.9
0.01
5.0
5.4
5.4
5.5
0.01
100
5.6
5.9
6.1
6.1
0.01
8.1
9.0
9.2
9.3
0.03
150
6.8
7.3
7.6
7.7
0.02
10.3
11.9
12.2
12.4
0.05
200
7.8
8.5
8.9
9.0
0.04
12.0
14.2
14.7
15.0
0.08
Head
gpm
Loss
1.0
0.64
2.0
2.46
3.0
5.38
4.0
9.39
Airside DPs
1.0
0.17
3.0
1.40
5.0
3.77
7.0
7.24
Airside DPs
100
6.2
6.6
6.7
6.8
0.01
8.8
9.7
9.9
10.0
0.02
200
8.9
9.7
10.0
10.1
0.02
13.4
15.6
16.2
16.5
0.05
300
10.7
11.8
12.3
12.5
0.05
16.3
20.0
21.0
21.4
0.10
400
12.1
13.5
14.1
14.4
0.07
18.5
23.4
24.8
25.5
0.16
Head
gpm
Loss
2.0
0.41
3.0
0.90
5.0
2.41
6.0
3.43
Airside DPs
2.0
0.47
4.0
1.84
6.0
4.08
8.0
5.00
Airside DPs
200
11.0
11.4
11.8
11.9
0.01
16.4
17.6
18.0
18.3
0.03
300
13.5
14.1
14.7
14.9
0.02
21.0
23.0
23.8
24.2
0.05
400
15.4
16.3
17.1
17.3
0.04
24.5
27.3
28.5
29.1
0.09
500
17.0
18.1
19.0
19.3
0.06
27.4
31.0
32.5
33.3
0.12
Head
gpm
Loss
2.0
0.54
3.0
1.19
5.0
3.18
6.0
4.52
Airside DPs
2.0
0.55
4.0
2.15
6.0
4.75
8.0
6.16
Airside DPs
300
15.5
16.2
16.9
17.0
0.01
23.2
25.3
26.1
26.5
0.03
500
19.8
21.0
22.1
22.4
0.03
30.8
34.8
36.4
37.2
0.07
700
22.9
24.5
26.0
26.5
0.06
36.2
41.9
44.3
45.6
0.13
900
25.2
27.2
29.1
29.7
0.09
40.2
47.6
50.7
52.5
0.20
Airflow, cfm
250
8.6
9.5
10.0
10.1
0.05
13.4
16.2
16.9
17.3
0.12
Airflow, cfm
500
13.1
14.8
15.5
15.9
0.11
20.2
26.3
28.0
28.8
0.23
Airflow, cfm
600
18.3
19.6
20.7
21.0
0.08
29.8
34.2
36.0
37.0
0.17
Airflow, cfm
1100
27.1
29.5
31.7
32.4
0.13
43.5
52.3
56.1
58.3
0.27
Performance notes appear at end of table
300
9.3
10.3
10.9
11.0
0.07
14.5
17.9
18.8
19.2
0.16
350
9.9
11.0
11.7
11.8
0.10
15.5
19.4
20.5
21.0
0.21
400
10.4
11.6
12.4
12.6
0.12
16.3
20.7
22.0
22.6
0.26
450
10.8
12.2
13.1
13.3
0.15
17.0
22.0
23.4
24.1
0.32
600
14.0
16.0
16.8
17.2
0.15
21.5
28.6
30.8
31.8
0.32
700
14.7
16.9
17.9
18.4
0.19
22.6
30.7
33.2
34.4
0.41
800
15.3
17.8
18.8
19.4
0.24
23.6
32.5
35.3
36.7
0.51
900
15.9
18.5
19.7
20.3
0.30
24.4
34.1
37.2
38.8
0.62
700
19.5
20.9
22.2
22.5
0.10
31.8
36.9
39.1
40.3
0.22
800
20.5
22.0
23.5
23.9
0.13
33.6
39.4
41.8
43.2
0.27
900
21.3
23.0
24.6
25.1
0.15
35.1
41.5
44.3
45.9
0.33
1000
22.1
23.9
25.7
26.2
0.19
36.5
43.5
46.6
48.3
0.40
1300
28.7
31.4
34.0
34.7
0.17
46.1
56.3
60.8
63.3
0.36
1500
30.1
33.0
35.9
36.7
0.22
48.3
59.7
64.8
67.8
0.46
1700
31.2
34.5
37.6
38.5
0.27
50.2
62.7
68.4
71.7
0.57
1900
32.3
35.7
39.2
40.1
0.33
51.9
65.4
71.6
75.3
0.68
M
PERFORMANCE DATA
One-Row
Head
gpm
Loss
1.0
0.48
2.0
1.82
4.0
6.98
5.0
10.75
Airside DPs
1.0
0.12
3.0
1.04
5.0
2.80
7.0
5.38
Airside DPs
Redefine your comfort zone™ | www.titus-hvac.com
PESV, AESV, DESV / HOT WATER COIL CAPACITY, MBH / 1- AND 2-ROW
M17
single / dual duct terminals
PESV, AESV, DESV / HOT WATER COIL CAPACITY, MBH / 1- AND 2-ROW
Rows
One-Row
Size 14
Redefine your comfort zone™ | www.titus-hvac.com
PERFORMANCE DATA
Two-Row
Rows
Size 16
One-Row
M
Two-Row
Rows
Size 24 x 16
One-Row
PERFORMANCE DATA
Two-Row
M18
•
•
•
•
•
•
•
•
Head
gpm
Loss
2.0
0.43
3.0
0.96
5.0
2.63
6.0
3.77
Airside DPs
2.0
0.39
4.0
1.51
6.0
3.36
8.0
3.95
Airside DPs
400
20.4
21.6
22.7
23.1
0.01
30.1
33.5
34.9
35.6
0.03
700
26.3
28.4
30.5
31.0
0.03
40.3
47.1
49.9
51.5
0.07
1000
30.3
33.2
36.0
36.8
0.06
47.0
56.8
61.1
63.5
0.12
1300
33.2
36.8
40.3
41.3
0.09
51.8
64.3
69.9
73.1
0.19
Head
gpm
Loss
3.0
1.07
5.0
2.92
7.0
5.65
9.0
6.48
Airside DPs
3.0
0.53
5.0
1.46
7.0
2.84
9.0
2.54
Airside DPs
600
29.5
31.4
32.4
32.9
0.02
43.1
47.0
49.0
50.2
0.04
1000
37.4
40.6
42.1
43.1
0.04
55.9
63.1
66.8
69.0
0.08
1400
42.8
47.2
49.3
50.6
0.07
64.7
74.6
80.0
83.3
0.14
1800
47.0
52.3
55.0
56.6
0.10
71.1
83.5
90.3
94.6
0.22
Head
gpm
Loss
3.0
1.31
5.0
3.57
7.0
6.89
9.0
8.50
Airside DPs
3.0
0.59
5.0
1.63
7.0
3.17
9.0
3.06
Airside DPs
600
35.3
37.6
38.7
39.3
0.01
48.8
53.1
55.2
56.4
0.02
1200
49.4
54.2
56.5
58.0
0.02
70.9
81.0
86.2
89.4
0.05
1800
58.3
65.2
68.7
70.8
0.05
84.3
99.4
107.6
112.8
0.10
2400
64.7
73.4
77.9
80.7
0.08
93.4
112.9
123.8
130.8
0.16
All coil performance in accordance with AHRI 410-2001
Heating capacities are in MBH
Data based on 180°F entering water and 55°F entering air
For temperature differentials other than 125°, multiply MBH by
correction factors below
Head loss is in feet of water
Always supply water to lowest connection pipe to prevent air
entrapment
Air temperature rise = 927 x MBH/cfm
Water temperature drop = 2.04 x MBH/gpm
Airflow, cfm
1600
35.5
39.7
43.8
45.0
0.13
55.5
70.3
77.2
81.1
0.27
Airflow, cfm
2200
50.4
56.5
59.7
61.6
0.14
76.1
90.7
98.8
104.1
0.30
Airflow, cfm
3000
69.6
79.9
85.4
88.7
0.11
100.1
123.3
136.6
145.3
0.24
1900
27.4
42.0
47.8
48.2
0.17
58.5
75.3
83.3
88.0
0.36
2200
39.0
44.1
49.3
50.9
0.22
60.9
79.6
88.6
93.9
0.46
2500
40.4
45.9
51.6
53.3
0.27
62.9
83.2
93.2
99.2
0.57
2800
41.5
47.4
53.6
55.4
0.33
64.7
86.4
97.3
103.8
0.69
2600
53.1
60.1
63.7
65.9
0.19
80.1
96.6
106.0
112.1
0.40
3000
55.5
63.1
67.1
69.6
0.24
83.4
101.6
112.1
119.0
0.51
3400
57.5
65.8
70.2
72.9
0.30
86.2
105.9
117.5
125.1
0.63
3800
59.3
68.2
72.9
75.9
0.36
88.6
109.7
122.2
130.5
0.76
3600
73.5
85.3
91.6
95.5
0.15
105.3
131.6
147.1
157.3
0.32
4200
76.8
89.9
96.9
101.3
0.20
109.4
138.5
155.9
167.5
0.42
4800
79.6
93.8
101.5
106.4
0.25
112.8
144.3
163.5
176.4
0.52
5400
82.0
97.3
105.6
110.9
0.30
115.7
149.3
170.0
184.2
0.63
• Connection size is ½” OD male solder for 1-row coil sizes 04-08. All
other coils have 7/8” OD male solder.
• Coils are not intended for steam applications and are labeled for a
maximum water temperature of 200°F
• Coils are tested for leakage at test pressure of 500 psi
• Water volumes less than those shown may result in laminar flow and
reduced heating capacity. If possible reduce the number of coil rows
to increase water velocity into turbulent range.
Correction Factors for Other Entering Conditions
∆T
50
60
70
80
90
100
110
125
140
150
Factor
0.40
0.48
0.56
0.64
0.72
0.80
0.88
1.00
1.12
1.20
Note: Airside ∆Ps reflects the air pressure drop of the hot water coil
single / dual duct terminals
PERFORMANCE DATA
Sizes 4-5-6
Rows
ThreeRow
FourRow
Sizes 7-8
Rows
ThreeRow
FourRow
Sizes 9-10
Rows
ThreeRow
FourRow
ThreeRow
FourRow
50
6.1
6.1
6.2
6.2
0.01
6.5
6.5
6.5
6.5
0.02
100
10.8
11.0
11.1
11.2
0.04
11.9
12.1
12.2
12.2
0.05
150
14.4
14.9
15.2
15.3
0.08
16.5
16.8
17.1
17.2
0.10
200
17.5
18.2
18.8
18.9
0.12
20.5
20.9
21.4
21.6
0.16
Head
gpm
Loss
2.0
0.50
4.0
1.95
6.0
4.33
8.0
5.42
Airside DPs
4.0
1.40
6.0
3.12
8.0
3.53
10.0
5.46
Airside DPs
100
11.2
11.6
11.7
11.7
0.02
12.4
12.5
12.6
12.6
0.03
200
18.6
19.8
20.2
20.4
0.08
22.1
22.5
22.7
22.9
0.10
300
23.8
26.0
26.9
27.3
0.15
29.6
30.6
31.1
31.4
0.20
400
27.9
31.1
32.3
33.0
0.24
358.0
37.3
38.1
38.6
0.32
Head
gpm
Loss
3.0
0.80
5.0
2.19
7.0
4.26
9.0
4.49
Airside DPs
4.0
1.16
5.0
1.80
8.0
2.75
10.0
4.25
Airside DPs
200
21.0
21.6
21.9
22.1
0.04
23.5
23.7
24.1
24.2
0.05
300
27.9
29.2
29.8
30.2
0.08
32.2
32.7
33.6
33.9
0.11
400
33.4
35.5
36.5
37.0
0.13
39.4
40.4
41.8
42.3
0.17
500
38.0
40.8
42.2
43.0
0.19
45.6
46.9
49.0
49.8
0.25
Head
gpm
Loss
3.0
0.91
4.0
1.61
6.0
3.57
8.0
4.32
Airside DPs
4.5
1.63
5.0
2.01
7.0
2.88
9.0
4.11
Airside DPs
300
30.3
31.0
31.8
32.2
0.05
34.6
34.8
35.1
35.6
0.06
500
42.2
44.0
45.9
46.9
0.11
50.5
51.1
52.6
53.4
0.15
700
50.9
53.8
56.9
58.5
0.19
62.9
63.9
66.5
68.0
0.26
900
57.6
61.5
65.8
68.2
0.29
72.7
74.2
78.0
80.3
0.39
Airflow, cfm
250
20.0
21.0
21.8
22.1
0.18
23.9
24.5
25.2
25.5
0.24
Airflow, cfm
500
31.1
35.3
37.0
37.9
0.35
40.9
43.0
44.2
44.9
0.47
Airflow, cfm
600
41.8
45.5
47.2
48.3
0.25
50.9
52.6
55.4
56.4
0.34
Airflow, cfm
1100
63.0
67.8
73.3
76.3
0.41
80.8
82.7
87.7
90.8
0.55
Performance notes appear at end of table
300
22.3
23.5
24.6
24.9
0.24
26.8
27.7
25.6
29.1
0.32
350
24.2
25.7
27.0
27.4
0.31
29.5
30.6
31.7
32.3
0.41
400
25.9
27.6
29.2
29.7
0.39
34.8
33.1
34.5
35.3
0.52
450
27.4
29.4
31.3
31.8
0.47
34.0
35.5
37.1
38.0
0.63
600
33.7
38.8
41.0
42.1
0.47
45.3
48.0
49.5
50.4
0.63
700
35.9
41.9
44.5
45.9
0.61
49.1
52.4
54.2
55.4
0.82
800
37.8
44.7
47.6
49.2
0.77
52.4
56.3
58.4
59.8
1.02
900
39.4
47.1
50.4
52.2
0.93
55.3
59.7
62.2
63.8
1.25
700
45.2
49.6
51.7
53.0
0.33
55.5
57.7
61.2
62.4
0.43
800
48.1
53.2
55.7
57.3
0.41
59.6
62.2
66.4
67.9
0.54
900
50.7
56.5
59.4
61.2
0.50
63.2
66.2
71.1
72.9
0.66
1000
52.9
59.4
62.7
64.7
0.59
66.5
69.8
75.5
77.5
0.79
1300
67.4
73.1
79.7
83.4
0.54
87.6
89.9
96.1
99.9
0.72
1500
71.1
77.6
85.2
89.6
0.69
93.4
96.0
103.4
107.9
0.92
1700
74.3
81.5
90.1
95.1
0.85
98.4
101.4
109.8
115.1
1.13
1900
77.0
84.9
94.5
100.0
1.02
102.8
106.1
115.6
121.5
1.36
M
PERFORMANCE DATA
Size 12
Rows
Head
gpm
Loss
2.0
0.70
3.0
1.54
5.0
4.14
6.0
5.90
Airside DPs
3.0
1.11
4.0
1.95
6.0
4.33
8.0
5.42
Airside DPs
Redefine your comfort zone™ | www.titus-hvac.com
PESV, AESV, DESV / HOT WATER COIL CAPACITY, MBH / 3- AND 4-ROW
M19
single / dual duct terminals
PESV, AESV, DESV / HOT WATER COIL CAPACITY, MBH / 3- AND 4-ROW
Rows
Size 14
ThreeRow
FourRow
Rows
ThreeRow
Size 16
Redefine your comfort zone™ | www.titus-hvac.com
PERFORMANCE DATA
M
FourRow
Rows
Size 24 x 16
ThreeRow
PERFORMANCE DATA
FourRow
M20
•
•
•
•
•
•
•
•
Head
gpm
Loss
4.0
1.30
5.0
2.01
6.0
2.88
8.0
3.27
Airside DPs
6.0
2.06
7.0
2.79
8.0
2.03
10.0
3.15
Airside DPs
400
41.3
42.1
42.6
43.3
0.04
46.7
47.1
47.4
47.8
0.05
700
59.8
61.8
63.2
65.0
0.10
71.1
72.2
73.1
74.4
0.14
1000
73.0
76.3
78.6
81.7
0.19
89.5
91.6
93.3
95.6
0.25
1300
83.0
87.6
90.8
95.2
0.29
104.0
107.1
109.5
113.0
0.38
Head
gpm
Loss
6.0
1.71
8.0
1.51
10.0
2.35
12.0
3.36
Airside DPs
9.0
1.58
10.0
1.95
11.0
2.36
12.0
2.80
Airside DPs
600
58.5
60.1
61.1
61.8
0.06
67.4
67.9
68.3
68.6
0.08
1000
80.9
84.4
86.7
88.2
0.14
97.6
98.8
99.7
100.5
0.18
1400
97.0
102.5
106.1
108.6
0.24
120.6
122.6
124.2
125.6
0.32
1800
109.3
116.7
121.6
125.1
0.37
138.8
141.6
144.0
146.0
0.49
Head
gpm
Loss
6.0
1.86
8.0
1.76
10.0
2.74
12.0
3.92
Airside DPs
9.0
1.80
10.0
2.22
11.0
2.68
12.0
3.18
Airside DPs
600
65.0
66.4
67.2
67.8
0.03
72.6
73.0
73.3
73.5
0.04
1200
103.8
108.6
111.5
113.6
0.09
124.0
125.5
126.7
127.7
0.12
1800
129.6
138.0
143.4
147.2
0.17
161.1
164.1
166.5
168.6
0.23
2400
148.2
160.0
167.9
173.4
0.27
189.2
193.6
197.3
200.5
0.37
All coil performance in accordance with AHRI 410-2001
Heating capacities are in MBH
Data based on 180°F entering water and 55°F entering air
For temperature differentials other than 125°, multiply MBH by
correction factors below
Head loss is in feet of water
Always supply water to lowest connection pipe to prevent air
entrapment
Air temperature rise = 927 x MBH/cfm
Water temperature drop = 2.04 x MBH/gpm
Airflow, cfm
1600
90.9
96.6
100.7
106.3
0.41
115.7
119.8
123.0
127.7
0.54
Airflow, cfm
2200
119.2
128.3
134.4
138.8
0.51
153.7
157.3
160.3
162.9
0.68
Airflow, cfm
3000
162.3
177.3
187.4
194.7
0.40
211.2
217.1
222.0
226.3
0.53
1900
97.3
104.1
109.0
115.8
0.54
125.5
130.4
134.4
140.2
0.72
2200
102.7
110.4
116.1
124.0
0.69
133.7
139.5
144.1
151.1
0.93
2500
107.3
115.8
122.2
131.2
0.86
140.8
147.4
152.7
160.7
1.15
2800
111.1
120.5
127.6
137.5
1.04
146.9
154.2
160.2
169.2
1.39
2600
127.3
138.0
145.3
150.5
0.68
166.2
170.5
174.1
177.3
0.90
3000
134.0
146.2
154.6
160.7
0.86
176.8
181.8
186.0
189.8
1.15
3400
139.9
153.4
162.7
169.6
1.06
185.9
191.6
196.4
200.7
1.42
3800
144.9
159.6
169.9
177.5
1.28
193.9
200.2
205.6
210.3
1.71
3600
173.5
191.2
203.4
212.3
0.54
229.0
236.2
242.3
247.6
0.72
4200
182.5
202.8
216.9
227.3
0.70
243.6
252.1
259.3
265.6
0.93
4800
190.1
212.6
228.5
240.3
0.88
256.0
265.6
273.9
281.1
1.17
5400
196.5
221.1
238.6
251.6
1.07
266.7
277.2
286.4
294.5
1.42
• Connection size is ½” OD male solder for 1-row coil sizes 04-08. All
other coils have 7/8” OD male solder.
• Coils are not intended for steam applications and are labeled for a
maximum water temperature of 200°F
• Coils are tested for leakage at test pressure of 500 psi
• Water volumes less than those shown may result in laminar flow and
reduced heating capacity. If possible reduce the number of coil rows
to increase water velocity into turbulent range.
Correction Factors for Other Entering Conditions
∆T
50
60
70
80
90
100
110
125
140
150
Factor
0.40
0.48
0.56
0.64
0.72
0.80
0.88
1.00
1.12
1.20
Note: Airside ∆Ps reflects the air pressure drop of the hot water coil
single / dual duct terminals
ELECTRIC COILS
Recommended Coil Selection Data
The table at the right describes the maximum recommended kW
capacities and number of stages available for Titus single duct terminals.
To make a coil selection:
1.Check the desired kW is available in desired unit size and number
of stages. (Required to prevent excessive watt density and current
draw, while taking into account unit size limitations.)
2.Check the desired minimum airflow limit is within recommended
operating range. (Ensures velocity pressure will be sufficient to
close airflow sensing switch.)
3.Multiply desired minimum airflow limit by a factor of 0.0142 and
check the result is equal to or greater than desired kW. (Limits
temperature rise across the coil to 45°F.)
kW ≤ cfm x 0.0142
Titus electric heating coils are specifically designed for use with VAV
terminal units. They include an extended plenum section and diffuser plate
to minimize stratification. The heating elements are designed to minimize
hot spots and nuisance tripping of the thermal cutouts.
must be within recommended ranges to ensure proper operation and long
service life. For optimum diffuser performance and maximum thermal
comfort, coil discharge temperatures should not be more than 15°F above
desired room temperatures. For proper coil operation it is recommended
that coil discharge temperatures do not to exceed 100°F.
These requirements established to prevent excessive temperature rise
caused by low airflow and/or oversized coils. Minimum airflow limits
M
PESV, AESV, DESV / APPLICATION DATA (STAGED HEAT)
Inlet
Size
Heating cfm
Range
55-225
5
85-350
6
105-500
7
135-650
8
190-900
9
225-1050
10
300-1400
12
425-2000
14
575-3000
16
750-4000
24x16
1800-8000
Min
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
0.5
1.0
1.5
0.5
1.0
1.5
0.5
1.0
1.5
0.5
1.0
1.5
0.5
1.0
1.5
0.5
1.0
1.5
0.5
1.0
1.5
0.5
1.0
1.5
1.0
2.0
3.0
1.0
2.0
3.0
1.0
2.0
3.0
Max
3.0
5.0
7.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
240V
1 Phase
kW Range
Min
1.0
1.5
2.0
1.0
1.5
2.0
1.0
1.5
2.0
1.0
1.5
2.0
1.0
1.5
2.0
1.0
1.5
2.0
1.0
1.5
2.0
1.0
1.5
2.0
1.0
2.0
3.0
1.0
2.0
3.0
1.0
2.0
3.0
Max
3.0
5.0
7.5
9.5
11.0
11.0
11.0
11.0
11.0
11.0
11.0
277V
1 Phase
kW Range
Min
1.0
1.5
2.5
1.0
1.5
2.5
1.0
1.5
2.5
1.0
1.5
2.5
1.0
1.5
2.5
1.0
1.5
2.5
1.0
1.5
2.5
1.0
1.5
2.5
1.5
2.0
3.0
1.5
2.0
3.0
1.5
3.0
4.5
208V
3 Phase
kW Range
480V
3 Phase
kW Range
Max
Min
Max
Min
Max
3.0
1.5
3.0
2.5
3.0
5.0
1.5
5.0
2.5
5.0
7.5
1.5
7.5
2.5
7.5
9.5
1.5
9.5
2.5
9.5
13.0
1.5
13.0
2.5
13.0
13.0
1.5
16.0
2.5
16.0
13.0
1.5
16.0
2.5
21.0
13.0
1.5
16.0
2.5
30.0
16.0
3.0
36.0
16.0
3.0
36.0
16.0
4.0
36.0
13.0
13.0
13.0
1.5
2.0
3.0
1.5
2.0
3.0
1.5
2.0
3.0
Note: The Titus 480V, 3-phase electric
heat configuration is 4-wire wye.
Contact your Titus representative for
other configuration options.
ELECTRIC COILS
4
208V
1 Phase
kW Range
Number
of
Steps
Available
Redefine your comfort zone™ | www.titus-hvac.com
SELECTION AND CAPACITIES
Useful formulas:
kW=
cfm x ∆T
3160
Where ∆T = air temperature rise.
or
∆T=
kW x 3160
cfm
or
cfm =
kW x 3160
∆T
M21
single / dual duct terminals
Redefine your comfort zone™ | www.titus-hvac.com
ELECTRIC COILS
ELECTRIC COILS
M
M22
PESV, AESV, DESV / APPLICATION DATA (LYNERGY HEAT)
Inlet
Size
Heating cfm
Range
208V
1 Phase
kW Range
240V
1 Phase
kW Range
277V
1 Phase
kW Range
208V
3 Phase
kW Range
480V
3 Phase
kW Range
Min
Max
Min
Max
Min
Max
Min
Max
Min
Max
4
55-225
0.5
3.0
1.0
3.0
1.0
3.0
1.5
3.0
2.5
3.0
5
85-350
0.5
5.0
1.0
5.0
1.0
5.0
1.5
5.0
2.5
5.0
6
105-500
0.5
7.5
1.0
7.5
1.0
7.5
1.5
7.5
2.5
7.5
7
135-650
0.5
9.5
1.0
9.5
1.0
9.5
1.5
9.5
2.5
9.5
8
190-900
0.5
9.5
1.0
11.0
1.0
13.0
1.5
10.5
2.5
13.0
9
225-1050
0.5
9.5
1.0
11.0
1.0
13.0
1.5
10.5
2.5
16.0
10
300-1400
0.5
9.5
1.0
11.0
1.0
13.0
1.5
10.5
2.5
21.0
12
425-2000
0.5
9.5
1.0
11.0
1.0
13.0
1.5
10.5
2.5
25.0
14
575-3000
1.0
9.5
1.0
11.0
1.5
13.0
1.5
10.5
3.0
25.0
16
750-4000
1.0
9.5
1.0
11.0
1.5
13.0
1.5
10.5
3.0
25.0
24x16
1800-8000
1.0
9.5
1.0
11.0
1.5
13.0
1.5
10.5
4.0
25.0
single / dual duct terminals
PERFORMANCE DATA
Titus is a charter member company and current partici- PESV, AESV, DESV
pant in the AHRI Directory of Certified Performance. This
Inlet
Rated Min
voluntary certification program was developed by parSize
CFM ∆Ps
ticipating manufacturers in conjunction with the former
Air-Conditioning and Refrigeration Institute (ARI) in the
04
150
0.04
1990’s. It is currently administrated by the Air-Condi05
250
0.03
tioning, Heating, and Refrigeration Institute (AHRI). The
06
400
0.13
purpose of this program is to provide for the independent
verification of manufacturers’ published performance
07
550
0.10
data. Only participating products are authorized to bear
08
700
0.02
the AHRI VAV Certification Mark. Certified data may be
09
900
0.05
viewed and downloaded at www.ahrinet.org.
In order to participate in this program, member companies pay annual dues based on sales volume, submit published performance data for all applicable model types,
and agree to provide a number of randomly selected
product samples for annual rounds of independent testing at the manufacturers’ expense. All verification testing is conducted in accordance with ASHRAE Standard
130 ‘Methods of Testing Air Terminal Units’. These tests
are conducted to verify that a manufacturer’s published
certified ratings are within the test tolerances outlined in
AHRI Standard 880 ‘Performance Rating of Air Terminals’.
Any failure to demonstrate the certified performance is
punished by additional testing requirements, mandatory
performance re-rating, monetary penalties and possible
expulsion from the Certified Directory.
Discharge
Radiated Sound Power
Discharge Sound Power
H
W
2
2
8
12
60 57 46 41 40 37 76 67 60 54 54 49
8
12
62 59 49 42 41 37 77 67 61 56 55 50
8
12
63 61 52 44 42 38 78 72 65 60 57 52
10
12
64 59 53 47 43 34 76 73 64 59 56 51
3
4
5
6
7
3
4
5
6
7
10
12
65 60 53 47 47 45 79 74 64 58 56 52
12.5
14
64 58 53 47 45 38 79 70 64 59 57 54
10
1100
0.01
12.5
14
67 62 57 55 54 43 80 72 66 63 60 55
12
1600
0.01
15
16
66 62 59 53 50 44 80 75 68 64 62 58
14
2100
0.04
17.5
20
66 62 55 53 50 46 76 69 66 63 63 59
16
2800
0.03
18
24
66 61 54 50 50 45 77 70 66 64 62 57
40
5300
0.06
18
38
79 74 72 68 67 64 87 81 77 72 73 69
Redefine your comfort zone™ | www.titus-hvac.com
AHRI Directory Of Certified Performance
M
Product samples provided for certification testing are
standard production units with standard ½” dual density fiberglass lining (unless otherwise specified) and no
optional appurtenances such as add-on attenuators or
heating/cooling coils. The certified ratings are measured
at the standard operating points under the following test
conditions:
PESV, EESV, AESV, DESV
PERFORMANCE DATA
• Rated airflow (cfm) – Based on an inlet velocity of
2000 fpm
• Rated Min ∆Ps (in wg) – Minimum static pressure
drop from the unit inlet to discharge at rated airflow
with damper full open
• Rated ∆Ps (in wg) – A static pressure drop of 1.5 in
wg from unit inlet to discharge
• Rated sound power by octave band (dB, re 10-12
watts) – Radiated and discharge sound performance
conducted in a reverberation room that meets both
the broadband and pure tone qualifications of AHRI
Standard 220
M23
single / dual duct terminals
Redefine your comfort zone™ | www.titus-hvac.com
Dual Duct Design Features
TITUS DUAL DUCT TERMINAL - LEADERSHIP IN A RE-EMERGING TECHNOLOGY!
The concern for IAQ has led to renewed interest in the benefits of dual
duct systems. Dual duct systems are an ideal vehicle for alternative
ventilation strategies and humidity control. Additionally, total filtration of
all air delivered to the zone is possible. Titus dual duct terminals provide
high performance and value, making them the preferred selection for
these applications.
Titus dual duct terminals vary the airflow individually between hot and
cold inlets for highly accurate temperature control.
As the ratio of hot and cold air is critical in most applications, pressure
independent controls are used with a separate velocity control loop to
each inlet.
Titus dual duct terminals are available in three styles. In those instances
where no blending of airstreams is required, the EDV without the integral
attenuator assembly can be an effective choice.
When blending of hot and cold supply air is needed for accurate
temperature control with minimum flow requirements, the EDV or EDC
with integral attenuator should be used.
The attenuator reduces discharge sound levels and provides some mixing
benefit. An optional mixing baffle is available for use with the attenuator
to provide maximum blending of hot and cold airstreams. Less than
1°F temperature variation is provided at the discharge with a 10°F inlet
temperature differential!
M
EDV NON MIXING
EDV WITH OPTIONAL
MIXING BAFFLE
MDV WITH INTEGRAL MIXING
ATTENUATOR
All Titus dual duct terminals are available with Fibre-Free and other lining options.
DESIGN FEATURES
The Titus MDV/MDC Dual Duct Terminals have been specially designed
for those applications where comfort levels are critical, as in hospitals,
research facilities, and other institutional applications.
M24
Like the EDV/EDC, the MDV/MDC terminals use separate pressure
independent velocity control loops for each inlet, rather than a single
velocity controller for discharge volume control only. This provides superior
temperature control during blending, as each inlet can compensate for
duct pressure changes without affecting the other.
The unique internal mixing baffle design provides for exceptional mixing
characteristics. Less than 1°F temperature variation is provided at the
discharge with a 20°F inlet temperature differential. Additional ductwork
is not required downstream to achieve proper mixing, allowing for
immediate take-off to diffusers. This is also beneficial for installations
with space limitations.
The tightly sealed casing typically allows less than 1 percent leakage of
conditioned air to the space at 1.5 inches wg. differential static pressure,
making this one of the most energy efficient dual duct terminals. The
dampers are the improved Titus low leakage design.
All Titus dual duct terminals are also available with EcoShield, Fibre
Free and SteriLoc lining options. Specify the MDV/MDC and you will be
providing the best performing dual duct terminal available.
DUAL DUCT CONTROL STRATEGIES
single / dual duct terminals
Pneumatic: O20 / Digital: O6 / Model: EDV
Max HTG
cfm Increase
As this is a non-blending application, a mixer/attenuator section is not required.
For detailed information on specific control types, refer to the following pages in Section O:
Max CLG*
Room Temperature Increase
Pneumatic: O20 / Digital: O6 / Model: EDV or MDV
Max CLG
cfm Increase
VAV, Minimum Mix Equal to Maximum HTG - blending
In cooling mode, as temperature approaches setpoint, cold air modulates from maximum to a minimum
mix flow rate. As temperature continues to drop, hot airflow modulates open as cold airflow closes,
maintaining a minimum total flow rate. Lower heating flow rates require unequal inlet sizes to maintain
control. A mixer/attenuator section is required.
Max HTG
M
Room Temperature Increase
VAV, Minimum Mix, Unequal Maximum Flows - blending
Similar in cooling mode to the sequence above, when entering the heating mode a flow rate higher
than the minimum mix is employed. Maximum flow rates may be close enough that equal inlet sizes
may be used. A mixer/attenuator section is required.
Max HTG
Max CLG
cfm Increase
Pneumatic: O20 / Digital: O6 / Model: EDV or MDV
Redefine your comfort zone™ | www.titus-hvac.com
VAV, Zero Minimum - non-blending
In cooling mode, as temperature approaches setpoint, cold airflow modulates from maximum to
zero flow. As room temperature drops below setpoint, hot airflow modulates from zero to maximum.
Heating and cooling maximum flow rates can be different. A deadband may be utilized.
Room Temperature Increase
Constant Volume Discharge - blending
In this sequence cooling and heating maximum flow rates are the same and minimum mix flow rates
are the same as maximums. The result is a constant airflow over the entire cooling and heating range.
A mixer/attenuator section is required.
cfm Increase
Max CLG
Room Temperature Increase
Optional Censor Location Configuration
For blending applications with integral mixer/attenuator. Multi-point velocity sensors are available in
four different configurations to match any application and control requirement. Configurations 3B and
3C are to match hot or cold inlet control requirements.
3A
Discharge
3B
Pneumatic: O20 / Digital: O6
3C
CONTROL STRATEGIES
Pneumatic: O20 / Digital: O6 / Model: EDC or MDC
Max HTG
3D
Inlet
= Sensor Location
M25
Redefine your comfort zone™ | www.titus-hvac.com
Dual Duct without Attentuator
single / dual duct terminals
EDV
• Standard AeroCrossTM multi-point center averaging velocity sensors
in each inlet for accurate flow control
• Standard matte faced insulation for maximum thermal and acoustic
performance
• Mechanically sealed and gasketed, leak resistant construction
• Choice of right or left hand cold duct location; right hand is standard
• Standard 22 gauge casing with slip and drive discharge connection
• Controls supplied by Titus are factory calibrated for quicker start-up
EDV
M
AVAILABLE MODELS:
PEDV / Pneumatic
DEDV / Digital Electronic
OVERVIEW
For Non-Blending Applications Only
Titus Dual Duct terminals vary the airflow individually between hot and
cold inlets for highly accurate temperature control. Dual duct systems
are an ideal vehicle for alternative ventilation strategies and humidity
control. Additionally, total filtration of all air delivered to the zone is
possible. Titus dual duct terminals provide high performance and value,
making them the preferred selection for these applications.
ADDITIONAL FEATURES
EDV
• Direct digital control package supplied by Titus includes: direct
digital controller, damper actuators and flow tranducers
• Dual density insulation, coated to prevent air erosion, meet
requirements of NFPA 90A and UL 181
M26
See website for Specifications
single / dual duct terminals
DIMENSIONS
PEDV - Basic Unit with Controls
W
4½”
M
4½”
L
Pneumatic
Actuator
D
H
Discharge
F
A
Control Cover
(optional)
M
DEDV - Basic Unit with Controls
L
M
W
F
Redefine your comfort zone™ | www.titus-hvac.com
EDV UNIT DIMENSIONS
G
12¼”
D
H
Discharge
A
F
Inlet Size cfm Range
0-225
0-350
0-500
0-650
0-900
0-1050
0-1400
0-2000
0-3000
0-4000
D
121/8
121/8
121/8
121/8
121/8
141/8
141/8
161/8
201/8
241/8
37/8
47/8
57/8
67/8
77/8
87/8
97/8
117/8
137/8
157/8
6½”
F
PEDV
17/8
17/8
17/8
7
/8
7
/8
-
DEDV
21/8
21/8
21/8
11/8
11/8
-
Slip & Drive
Cleat Connection
G
H
L
M
W
73/8
73/8
73/8
73/8
73/8
53/8
53/8
53/8
33/8
33/8
8
8
8
10
10
12½
12½
15
17½
18
15½
15½
15½
15½
15½
15½
15½
15½
15½
15½
53/8
53/8
33/8
33/8
33/8
33/8
33/8
33/8
33/8
33/8
241/8
241/8
241/8
241/8
241/8
281/8
281/8
321/8
401/8
481/8
All dimensions are in inches
DIMENSIONS
4
5
6
7
8
9
10
12
14
16
A
18”
Control
Enclosure
M27
single / dual duct terminals
Redefine your comfort zone™ | www.titus-hvac.com
PERFORMANCE DATA
PEDV, DEDV WITHOUT ATTENUATOR - RADIATED SOUND PERFORMANCE
Size
4
5
6
7
M
8
9
10
12
PERFORMANCE DATA
14
M28
16
CFM
100
125
150
175
200
150
200
250
300
350
300
350
400
450
500
450
500
550
600
650
600
650
700
750
800
800
850
900
950
1000
900
1000
1100
1200
1300
1200
1400
1600
1800
2000
1500
1800
2100
2400
2700
2000
2400
2800
3200
3600
Min
∆Ps
0.02
0.03
0.04
0.06
0.08
0.01
0.02
0.03
0.04
0.06
0.07
0.10
0.13
0.16
0.20
0.07
0.09
0.10
0.12
0.15
0.02
0.02
0.02
0.02
0.03
0.04
0.04
0.05
0.06
0.06
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.02
0.03
0.04
0.05
0.06
0.02
0.02
0.03
0.04
0.05
2
52
55
58
61
63
53
56
59
62
63
59
60
61
62
63
61
62
63
63
64
62
63
63
64
65
61
61
62
62
63
63
64
65
65
66
62
63
64
65
66
60
62
63
64
66
59
61
63
65
66
3
48
52
55
58
60
49
53
56
59
61
54
57
58
60
61
54
55
57
58
59
55
56
57
58
59
53
54
55
56
56
57
58
58
59
60
56
57
59
60
61
56
58
59
60
61
53
56
58
60
61
1.0” ∆Ps
4
5
6
39 36 35
42 38 36
44 40 38
46 42 39
47 43 40
41 36 35
44 38 37
46 40 39
48 42 41
49 43 42
45 39 37
47 41 38
49 42 39
50 44 40
51 45 41
48 42 38
49 43 39
50 45 40
51 46 41
52 47 41
49 43 43
50 44 44
50 45 44
51 46 45
52 47 46
49 42 40
49 43 41
50 43 41
50 43 42
50 44 42
53 50 48
54 51 49
54 52 50
54 53 51
55 53 52
52 47 43
54 48 45
55 49 46
56 50 48
57 51 49
50 48 45
51 49 46
52 50 47
53 51 48
54 52 49
47 45 44
49 47 46
51 48 47
52 50 49
54 51 50
7
31
32
34
34
35
30
32
34
35
36
33
34
35
36
37
30
30
31
31
32
39
40
41
41
42
35
35
35
36
36
37
38
39
40
41
37
39
40
41
43
41
42
43
43
44
38
39
41
42
44
NC
15
20
23
27
29
16
21
24
28
30
22
25
27
29
30
23
24
25
27
28
24
25
25
27
28
23
23
24
24
25
27
28
28
28
29
26
28
29
30
31
24
27
28
29
30
21
24
27
29
30
Octave Band Sound Power, Lw
1.5” ∆Ps
2
3
4
5
6
7
53 50 41 37 37 34
57 54 44 40 39 36
60 57 46 41 40 37
63 59 48 43 41 38
65 62 49 44 42 38
55 51 43 38 37 33
59 55 46 40 40 35
62 59 49 42 41 37
64 61 50 44 43 38
66 63 52 45 44 39
61 57 48 41 39 36
62 59 50 43 40 37
63 61 52 44 42 38
64 63 53 46 43 39
65 64 54 47 44 40
62 57 51 45 41 33
63 58 52 46 42 34
64 59 53 47 43 34
65 61 54 48 44 35
65 62 55 49 44 35
64 58 52 46 45 44
65 59 53 47 46 45
65 60 53 47 47 45
66 61 54 48 48 46
66 62 55 49 48 47
62 57 52 46 44 38
63 58 53 46 45 38
64 58 53 47 45 38
64 59 54 47 45 38
65 60 54 47 46 39
65 60 57 53 52 41
66 61 57 54 53 42
67 62 57 55 54 43
67 63 58 56 55 44
68 63 58 56 55 45
64 59 56 50 46 41
65 60 57 52 48 42
66 62 59 53 50 44
67 63 60 54 51 45
68 64 61 55 52 47
62 59 53 51 48 45
64 60 54 52 49 45
66 62 55 53 50 46
67 63 56 54 51 47
68 64 57 55 52 47
61 56 50 47 47 41
64 59 52 49 49 43
66 61 54 50 50 45
67 62 55 52 52 46
69 64 56 53 53 48
• Radiated sound is the noise transmitted through the unit casing
• Min ∆Ps is the static pressure drop from the unit inlet to the unit
outlet with the cold damper full open
• Sound power levels are in dB, ref 10-12 watts
• Sound performance based on units lined with standard dual density
fiberglass lining
NC
17
22
25
28
31
18
23
28
30
33
25
28
30
33
34
25
27
28
30
31
27
28
29
30
31
26
27
27
28
29
31
31
31
33
33
30
31
34
35
36
28
29
31
33
34
24
28
30
31
34
2
55
58
61
64
66
57
60
63
65
67
63
64
65
66
67
63
64
66
66
66
65
66
67
67
68
63
64
65
65
66
67
67
68
69
69
66
67
68
69
69
64
66
67
69
70
63
65
67
69
71
3
51
55
58
61
63
53
57
61
63
65
59
62
63
65
67
59
60
62
63
64
60
61
62
63
64
59
60
61
62
62
63
64
64
65
66
61
63
64
65
67
61
63
64
65
66
58
61
63
64
66
4
43
45
47
49
51
45
48
51
52
54
50
52
54
55
56
53
54
55
56
57
54
55
56
56
57
55
55
56
56
57
59
59
60
60
61
58
60
61
62
63
55
56
58
58
59
52
54
55
57
58
2.0” ∆Ps
5
6
38 39
41 40
42 42
44 43
45 44
39 39
42 41
44 43
45 44
47 45
42 41
44 42
46 43
47 45
49 46
46 43
48 44
49 45
50 46
51 46
47 47
48 48
49 49
50 50
51 50
48 47
49 47
49 48
49 48
50 48
56 54
56 55
57 56
58 57
58 58
53 49
54 51
55 52
56 54
57 55
53 50
54 51
55 52
56 53
57 54
49 49
51 51
52 52
53 54
55 55
7
36
38
39
40
41
35
37
39
40
41
38
39
40
41
42
35
36
37
37
38
47
48
48
49
50
40
40
40
40
40
44
45
46
47
48
43
45
47
48
49
47
48
49
49
50
44
46
48
49
50
NC
18
23
27
30
33
21
25
30
33
35
28
31
33
35
37
28
29
31
33
34
29
30
31
33
34
29
29
30
31
31
34
34
35
35
36
32
35
36
37
38
30
33
34
35
36
27
30
33
34
36
• All performance based on tests conducted in accordance with
ASHRAE 130-2008 and AHRI 880-2011
• All NC levels determined using AHRI 885-2008 Appendix E. See
Terminal Unit Engineering Guidelines.
• Dash (-) in space denotes NC value less than NC10
• Only highlighted data points are AHRI certified. Refer to page M38
for AHRI Certified Performance Listings.
single / dual duct terminals
PERFORMANCE DATA
Size
4
5
6
7
8
9
10
12
14
100
125
150
175
200
150
200
250
300
350
300
350
400
450
500
450
500
550
600
650
600
650
700
750
800
800
850
900
950
1000
900
1000
1100
1200
1300
1200
1400
1600
1800
2000
1500
1800
2100
2400
2700
2000
2400
2800
3200
3600
Min
∆Ps
0.02
0.03
0.04
0.06
0.08
0.01
0.02
0.03
0.04
0.06
0.07
0.10
0.13
0.16
0.20
0.07
0.09
0.10
0.12
0.15
0.02
0.02
0.02
0.02
0.03
0.04
0.04
0.05
0.06
0.06
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0.02
0.03
0.04
0.05
0.06
0.02
0.02
0.03
0.04
0.05
2
68
70
72
73
74
67
70
72
74
75
69
71
72
73
74
72
72
73
73
73
74
75
75
75
76
74
74
75
76
76
75
76
77
77
78
74
75
76
77
77
70
71
72
73
74
70
72
74
75
76
3
58
62
64
67
69
57
60
64
66
68
64
66
68
69
71
65
67
68
69
71
68
69
70
71
72
65
66
67
67
68
66
67
68
69
69
68
70
71
72
73
63
65
66
67
68
63
66
68
69
71
1.0” ∆Ps
4
5
6
51 46 47
54 49 49
57 51 50
59 53 51
61 55 53
52 47 47
56 51 49
58 53 51
60 55 53
62 57 54
59 54 51
61 56 52
62 58 53
64 59 54
65 61 55
58 54 51
59 56 52
60 57 53
61 58 54
62 59 55
59 55 52
60 56 53
60 56 53
61 57 54
62 58 54
60 57 54
60 57 54
61 57 55
61 58 55
61 58 55
61 59 55
62 60 56
63 61 56
63 61 57
64 62 58
63 59 57
65 61 59
66 62 59
67 63 60
68 64 61
61 59 57
62 59 58
64 60 58
65 60 59
66 61 59
60 58 56
63 60 58
65 61 59
66 62 60
68 63 61
7
41
43
44
45
46
42
44
45
46
47
46
47
48
49
50
46
47
48
48
49
47
47
48
48
49
49
50
50
50
50
50
51
51
52
53
52
53
55
56
56
53
53
54
54
54
51
52
54
55
56
NC
25
28
30
31
33
24
28
30
29
30
23
25
27
28
31
26
26
28
28
31
29
30
30
30
31
26
26
28
29
29
28
29
30
30
31
26
28
30
31
32
21
23
24
25
26
21
24
26
28
30
Octave Band Sound Power, Lw
1.5” ∆Ps
2
3
4
5
6
7
69 60 54 49 50 46
71 63 57 52 52 47
73 66 60 54 54 49
74 68 62 56 55 50
75 71 63 58 56 51
69 59 55 50 51 46
72 63 59 53 53 48
74 66 61 56 55 50
75 69 63 58 56 51
77 71 65 60 57 52
72 67 62 57 54 50
73 69 64 59 55 51
75 71 65 60 57 52
76 72 67 62 58 53
77 74 68 63 59 54
73 69 60 56 54 49
74 70 62 58 55 50
74 72 63 59 56 51
75 73 63 60 57 52
75 74 64 61 58 53
76 71 61 56 55 51
76 72 62 57 55 51
77 73 63 58 56 52
77 74 63 58 56 52
77 75 64 59 57 53
75 68 62 59 57 53
76 69 62 59 57 54
77 69 63 59 57 54
77 70 63 60 58 54
78 71 64 60 58 54
76 69 64 61 58 54
77 70 65 62 59 55
78 71 65 63 60 55
79 72 66 64 60 56
79 73 67 65 61 56
76 71 65 62 60 56
77 73 67 63 61 57
78 74 68 64 62 58
78 75 70 65 63 59
79 76 71 66 64 60
72 67 63 62 62 59
73 68 65 63 62 59
74 69 66 63 63 59
75 70 68 64 63 59
76 71 69 64 63 60
72 66 62 61 59 54
74 68 64 62 61 56
76 70 66 64 62 57
77 72 68 65 63 59
78 73 70 66 64 60
• Discharge sound is the noise emitted from the unit discharge into
the downstream ductwork
• Min ∆Ps is the static pressure drop from the unit inlet to the unit
outlet with the cold damper full open
• Sound power levels are in dB, ref 10-12 watts
• Sound performance based on units lined with standard dual density
fiberglass lining
NC
26
29
31
33
34
26
30
33
30
33
26
28
31
32
34
28
30
32
33
34
31
32
33
33
34
28
29
30
30
31
29
30
31
33
33
30
32
33
34
36
25
26
27
28
30
24
26
29
31
32
2
70
72
73
75
76
70
73
75
76
78
74
75
76
78
79
75
75
76
76
77
77
77
78
78
79
76
77
78
78
79
77
78
79
80
80
77
78
79
79
80
74
75
76
76
77
73
75
77
78
80
3
61
64
67
70
72
61
65
68
71
73
69
71
73
75
76
71
73
74
75
76
74
75
76
77
77
70
71
71
72
73
72
73
73
74
75
73
75
76
77
78
69
71
72
73
74
68
70
72
73
75
4
56
59
61
64
65
58
61
63
66
67
64
66
67
69
70
62
63
64
65
66
63
64
64
65
66
64
64
65
65
65
66
67
67
68
68
67
69
70
71
72
65
67
68
69
70
63
66
68
70
71
2.0” ∆Ps
5
6
51 53
54 55
56 57
58 58
60 59
52 53
55 55
58 57
60 59
61 60
58 56
60 58
62 59
63 60
65 61
58 56
59 57
60 58
61 59
62 59
57 57
58 57
59 58
60 58
60 59
60 59
61 59
61 59
61 60
62 60
63 61
64 61
65 62
66 63
66 63
64 62
65 63
66 64
67 65
68 66
65 65
65 65
66 66
66 66
67 66
63 61
64 62
66 64
67 65
68 66
7
49
51
52
53
54
49
51
53
54
55
53
54
55
56
57
52
53
54
55
55
54
54
55
55
56
56
56
57
57
57
57
57
58
59
59
59
60
61
62
63
62
63
63
63
63
57
58
60
61
62
NC
28
30
31
34
35
28
31
34
31
34
29
31
33
36
37
31
33
34
36
37
34
36
37
37
37
29
30
31
31
33
31
32
33
34
34
32
34
36
37
38
27
30
31
32
33
26
28
31
32
34
• All performance based on tests conducted in accordance with
ASHRAE 130-2008 and AHRI 880-2011
• All NC levels determined using AHRI 885-2008 Appendix E. See
Terminal Unit Engineering Guidelines.
• Dash (-) in space denotes NC value less than NC10
• Only highlighted data points are AHRI certified. Refer to
page M38 for AHRI Certified Performance Listings.
M
PERFORMANCE DATA
16
CFM
Redefine your comfort zone™ | www.titus-hvac.com
PEDV, DEDV WITHOUT ATTENUATOR - DISCHARGE SOUND PERFORMANCE
M29
Redefine your comfort zone™ | www.titus-hvac.com
Dual Duct with Attentuator
single / dual duct terminals
EDV / EDC
• Standard AeroCrossTM multi-point center averaging velocity sensors
in four location combinations to match any control requirement
• Standard matte faced insulation for maximum thermal and acoustic
performance
• Mechanically sealed and gasketed, leak resistant construction
• Choice of right or left hand cold duct location; right hand is standard
• Standard 22 gauge casing with slip and drive discharge connection
• Controls supplied by Titus are factory calibrated for quicker start-up
EDV / EDC
M
AVAILABLE MODELS:
PEDV / Pneumatic
PEDC / Pneumatic
DEDV / Digital Electronic
OVERVIEW
For Blending or Non-Blending Applications
Titus Dual Duct terminals vary the airflow individually between hot and
cold inlets for highly accurate temperature control. Dual duct systems
are an ideal vehicle for alternative ventilation strategies and humidity
control. Additionally, total filtration of all air delivered to the zone is
possible. Titus dual duct terminals provide high performance and value,
making them the preferred selection for these applications.
ADDITIONAL FEATURES
EDV / EDC
• Direct digital control package supplied by Titus includes: direct
digital controller, damper actuators and flow tranducers
• Dual density insulation, coated to prevent air erosion, meet
requirements of NFPA 90A and UL 181
M30
See website for Specifications
single / dual duct terminals
DIMENSIONS
PEDV - Basic Unit with Controls
4”
L
G
H
J
F
D
A
W
Discharge
D
E
Slip & Drive
Cleat Connection
Controller
4½”
Redefine your comfort zone™ | www.titus-hvac.com
EDV UNIT DIMENSIONS
Pneumatic Actuator
M
DEDV - Basic Unit with Controls
G
4"
L
H
F
D
W
Discharge
A
D
E
Slip and Drive
Duct Connection
6½"
18"
K
K
12¼"
Inlet Size cfm Range
0-225
0-350
0-500
0-650
0-900
0-1050
0-1400
0-2000
0-3000
0-4000
D
E
F
G
H
L
W
87/8
87/8
87/8
107/8
107/8
127/8
127/8
147/8
167/8
187/8
37/8
47/8
57/8
67/8
77/8
87/8
97/8
117/8
137/8
157/8
513/16
513/16
513/16
71/16
71/16
101/16
101/16
111/16
129/16
151/16
513/16
513/16
513/16
81/16
81/16
111/16
111/16
131/16
161/16
161/16
53/8
53/8
33/8
6¾
33/8
6¾
33/8
33/8
33/8
33/8
81/8
81/8
81/8
101/8
101/8
125/8
125/8
151/8
18
18
191/8
191/8
191/8
231/8
231/8
271/8
271/8
311/8
351/8
381/8
19
19
19
23
23
27
27
31
35
38
All dimensions are in inches
PEDV
J
17/8
17/8
17/8
7
/8
7
/8
-
DEDV
K
2
2
2
1
1
-
DIMENSIONS
4
5
6
7
8
9
10
12
14
16
A
M31
single / dual duct terminals
Redefine your comfort zone™ | www.titus-hvac.com
PERFORMANCE DATA
PEDV, PEDC, DEDV WITH INTEGRAL ATTENUATOR AND MIXING BAFFLES / RADIATED SOUND PERFORMANCE
Size
4
5
6
7
M
8
9
10
12
PERFORMANCE DATA
14
M32
16
CFM
100
125
150
175
200
150
200
250
300
350
300
350
400
450
500
450
500
550
600
650
600
650
700
750
800
800
850
900
950
1000
900
1000
1100
1200
1300
1200
1400
1600
1800
2000
1500
1800
2100
2400
2700
2000
2400
2800
3200
3600
Min
∆Ps
0.18
0.29
0.41
0.56
0.73
0.17
0.30
0.47
0.67
0.92
0.51
0.70
0.91
1.15
1.42
0.35
0.44
0.53
0.63
0.74
0.40
0.47
0.55
0.63
0.71
0.18
0.21
0.23
0.26
0.29
0.25
0.31
0.38
0.45
0.53
0.25
0.33
0.44
0.55
0.68
0.18
0.25
0.34
0.45
0.57
0.21
0.30
0.40
0.53
0.67
2
3
46 46
48 49
50 51
52 52
53 54
48 45
51 48
53 51
55 53
57 54
51 51
52 53
52 54
NA NA
NA NA
59 52
60 53
61 54
62 55
62 56
58 52
58 53
59 54
59 55
60 56
62 53
63 53
63 54
64 54
65 55
60 52
60 52
61 53
61 54
61 55
64 56
65 57
65 58
66 59
66 60
62 54
63 56
64 57
65 58
65 60
65 55
66 57
66 58
67 59
68 60
1.0” ∆Ps
4
5
6
7 NC
37 31 29 23 12
40 33 31 25 16
42 35 33 26 18
44 37 34 28 20
45 38 36 29 22
38 32 32 25 11
42 35 35 28 15
44 37 37 31 18
47 39 38 33 21
48 40 40 35 22
43 38 36 30 18
44 39 37 31 21
46 41 38 32 22
NA NA NA NA NA
NA NA NA NA NA
46 41 40 35 20
47 42 41 36 22
48 43 41 37 23
49 43 42 37 24
49 44 43 38 24
45 39 37 35 20
46 39 38 36 21
46 40 38 36 22
47 41 39 37 23
47 41 39 38 24
45 41 42 40 24
45 42 42 40 25
46 42 42 40 25
46 42 43 40 27
46 43 43 41 28
44 40 38 37 22
45 41 39 37 22
46 41 40 38 23
47 42 40 39 23
47 42 40 39 23
52 50 53 52 27
54 51 53 52 28
55 52 54 52 29
56 52 54 52 30
57 53 54 52 31
47 42 43 43 24
49 43 44 44 25
51 45 45 45 27
52 46 46 46 28
53 47 47 47 29
50 45 47 47 28
52 46 48 47 29
54 47 48 47 29
56 48 49 47 31
57 49 49 47 32
Octave Band Sound Power, Lw
1.5” ∆Ps
2
3
4
5
6
7
49 49 39 33 33 28
52 52 42 36 35 29
54 53 44 38 36 31
55 55 46 39 38 32
57 57 48 41 39 33
51 48 41 35 35 29
54 51 44 37 37 32
56 54 47 40 39 35
58 56 49 41 41 37
60 58 51 43 43 39
54 54 46 40 39 34
55 56 47 42 40 35
55 57 49 43 41 37
55 58 50 45 42 38
55 60 51 46 43 39
61 56 49 43 43 40
62 57 50 44 44 41
63 57 51 45 45 41
64 58 52 46 45 42
65 59 52 47 46 43
60 57 49 42 40 39
61 58 49 42 41 40
61 59 50 43 41 40
62 60 51 44 41 41
62 60 51 44 42 42
64 56 49 44 45 45
65 57 49 45 46 45
66 57 50 45 46 45
66 58 50 46 46 45
67 58 50 46 46 45
63 55 47 42 41 39
63 56 48 43 41 40
64 57 49 43 42 41
64 58 49 44 42 42
65 59 50 45 43 42
68 59 55 54 57 57
68 61 57 55 58 57
68 62 58 55 58 57
69 63 59 56 58 57
69 64 60 56 58 58
66 57 50 44 46 47
67 59 52 46 47 48
67 60 53 47 48 49
68 62 55 48 49 49
69 63 56 49 49 50
68 59 52 47 50 51
69 60 54 48 50 51
70 61 56 50 51 51
70 62 58 51 51 51
71 63 59 51 52 51
• Radiated sound is the noise transmitted through the unit casing
• Min ∆Ps is the static pressure drop from the unit inlet to the unit
outlet with the cold damper full open
• Sound power levels are in dB, ref 10-12 watts
• Sound performance based on units lined with standard dual density
fiberglass lining
NC
16
20
21
23
25
15
18
22
24
27
22
24
25
27
29
24
25
25
27
28
25
27
28
29
29
27
28
29
29
31
25
25
27
27
28
32
32
32
34
35
29
31
31
32
33
32
33
34
34
36
2
52
54
56
58
59
53
56
58
60
62
57
57
57
57
58
63
64
65
65
66
62
63
63
64
64
66
66
67
68
68
65
66
66
66
67
70
70
71
71
72
68
69
70
70
71
70
71
72
73
73
3
51
53
55
57
59
50
54
56
58
60
57
58
60
61
62
58
59
60
61
61
60
61
62
63
64
59
59
60
61
61
58
59
60
61
61
62
63
64
65
66
60
61
63
64
65
61
62
64
65
66
4
41
44
46
48
49
43
46
49
51
53
48
50
51
52
53
51
52
53
54
55
51
52
53
53
54
52
52
52
53
53
49
50
51
51
52
58
59
60
61
62
52
54
55
57
58
53
56
58
59
61
2.0” ∆Ps
5
6
35 35
38 37
40 39
41 40
43 41
36 36
39 39
41 41
43 43
45 44
42 41
44 42
45 44
47 45
48 45
45 45
46 46
47 47
48 48
48 48
44 42
44 43
45 43
46 43
46 44
47 48
47 48
47 48
48 49
48 49
44 42
44 43
45 44
46 44
46 44
57 60
58 61
58 61
59 61
59 62
46 47
47 49
49 49
50 50
51 51
49 51
50 52
51 53
52 53
53 54
7
31
33
34
36
37
32
35
38
40
42
37
39
40
41
42
43
44
45
45
46
42
43
43
44
44
48
48
48
49
49
41
42
43
44
44
61
61
61
61
61
49
50
51
52
53
53
53
53
53
53
NC
18
21
23
25
28
17
22
24
27
29
25
27
29
30
31
27
28
29
30
30
29
30
31
33
34
29
29
31
32
32
28
29
29
30
31
34
34
36
36
37
32
33
34
34
36
34
36
37
38
38
• All performance based on tests conducted in accordance with
ASHRAE 130-2008 and AHRI 880-2011
• All NC levels determined using AHRI 885-2008 Appendix E. See
Terminal Unit Engineering Guidelines.
• Dash (-) in space denotes NC value less than NC10
• Only highlighted data points are AHRI certified. Refer to page M38
for AHRI Certified Performance Listings.
single / dual duct terminals
PERFORMANCE DATA
Size
4
5
6
7
8
9
10
12
14
100
125
150
175
200
150
200
250
300
350
300
350
400
450
500
450
500
550
600
650
600
650
700
750
800
800
850
900
950
1000
900
1000
1100
1200
1300
1200
1400
1600
1800
2000
1500
1800
2100
2400
2700
2000
2400
2800
3200
3600
Min ∆Ps
0.18
0.29
0.41
0.56
0.73
0.17
0.30
0.47
0.67
0.92
0.51
0.70
0.91
1.15
1.42
0.35
0.44
0.53
0.63
0.74
0.40
0.47
0.55
0.63
0.71
0.18
0.21
0.23
0.26
0.29
0.25
0.31
0.38
0.45
0.53
0.25
0.33
0.44
0.55
0.68
0.18
0.25
0.34
0.45
0.57
0.21
0.30
0.40
0.53
0.67
2
67
70
72
74
76
65
69
72
74
76
68
69
70
N/A
N/A
69
71
72
73
74
70
71
71
72
72
74
75
75
76
77
74
75
76
76
77
73
74
76
77
77
71
73
75
76
77
73
74
75
76
77
3
58
61
64
66
68
57
61
64
67
69
62
63
64
N/A
N/A
65
66
67
68
69
66
67
68
68
69
64
64
65
65
66
63
64
65
66
67
64
65
67
68
69
62
64
65
66
67
62
64
66
67
68
1.0” ∆Ps
4
5
6
50 45 44
53 48 47
56 50 49
58 52 51
60 54 53
49 44 45
53 48 48
56 50 50
59 52 52
61 54 54
54 50 50
56 51 52
58 53 53
N/A N/A N/A
N/A N/A N/A
55 50 51
57 51 52
58 52 53
59 53 54
60 54 55
57 52 53
57 53 54
58 54 54
59 54 55
59 55 55
55 52 54
55 52 55
56 52 55
56 53 55
57 53 56
55 52 56
56 53 56
57 53 57
57 54 57
58 54 57
56 53 56
58 54 57
59 55 58
61 56 59
62 57 60
55 53 56
57 54 57
59 55 58
60 56 59
61 57 60
55 53 58
57 55 59
59 56 60
61 58 61
62 59 61
Octave Band Sound Power, Lw
1.5” ∆Ps
7 NC 2
3
4
5
6
7
36 24 68 59 51 46 45 38
40 28 71 62 54 49 48 41
43 30 74 65 57 51 50 45
46 33 76 67 59 53 52 47
48 35 78 69 61 55 54 50
40 21 67 59 52 46 48 43
44 26 71 63 56 50 50 47
47 30 74 67 59 52 53 50
50 29 76 69 61 54 54 53
52 31 78 71 63 56 56 55
48 21 71 65 57 52 53 51
49 22 72 66 59 53 54 53
51 24 73 67 60 55 55 54
N/A N/A 74 68 62 56 56 55
N/A N/A 75 69 63 57 57 56
48 24 71 67 58 53 54 51
49 25 73 68 59 54 55 53
50 26 74 69 60 54 56 54
52 28 75 71 61 55 56 55
53 29 76 72 62 56 57 56
51 25 72 69 59 54 55 54
52 26 73 70 60 55 56 55
52 27 73 71 61 56 57 56
53 26 74 72 62 56 57 57
54 27 74 72 62 57 58 57
52 26 77 67 58 55 57 56
52 28 77 68 59 55 57 56
53 28 78 68 59 55 58 57
54 29 79 69 60 56 58 57
54 30 79 69 60 56 58 58
55 26 77 67 59 55 58 59
56 28 78 68 60 56 59 60
57 29 79 69 61 57 59 61
58 29 80 70 61 57 60 62
59 30 80 71 62 57 60 62
55 25 76 68 59 56 58 58
57 26 78 69 61 57 59 60
58 29 79 70 62 58 60 61
59 30 80 71 64 59 61 62
60 30 81 72 65 60 62 63
56 22 75 66 59 56 58 59
58 25 76 68 61 57 60 61
59 28 78 69 62 58 61 62
61 29 79 70 63 59 62 64
62 30 80 71 65 60 62 65
58 25 76 66 58 56 60 61
60 26 78 68 60 58 61 63
61 28 79 69 62 59 62 64
62 29 80 71 64 60 63 66
63 30 81 72 65 61 64 67
• Discharge sound is the noise emitted from the unit discharge into
the downstream ductwork
• Min ∆Ps is the static pressure drop from the unit inlet to the unit
outlet with the cold damper full open
• Sound power levels are in dB, ref 10-12 watts
• Sound performance based on units lined with standard dual density
fiberglass lining
NC
25
29
33
35
38
24
29
33
31
34
25
26
28
29
30
26
28
29
31
32
28
30
31
31
31
30
30
31
33
33
30
31
33
34
34
29
31
33
34
35
28
29
31
33
34
29
31
33
34
35
2
69
72
75
77
79
68
72
75
77
79
73
75
76
76
77
73
74
75
76
77
74
74
75
76
76
79
79
80
81
81
79
80
81
82
83
79
80
81
82
83
77
79
80
82
83
79
80
82
83
84
3
60
63
66
68
70
61
65
68
71
73
67
68
70
71
72
69
70
71
72
73
72
72
73
74
75
70
70
71
71
72
70
71
72
73
73
70
72
73
74
75
69
70
72
73
74
69
71
72
73
75
4
52
55
58
60
62
53
57
60
63
65
59
61
63
64
65
60
61
62
63
64
61
62
63
64
64
61
62
62
62
63
62
63
63
64
64
62
63
65
66
67
61
63
65
66
67
60
63
64
66
67
2.0” ∆Ps
5
6
47 46
50 49
52 52
54 54
56 55
48 49
51 52
54 54
56 56
57 58
53 55
55 56
56 57
57 58
58 59
54 56
55 57
56 57
57 58
58 59
56 57
57 58
57 58
58 59
59 59
57 59
57 59
57 59
58 60
58 60
58 60
58 60
59 61
59 61
60 62
58 60
59 61
60 62
61 63
62 63
58 60
59 61
60 62
61 63
62 64
58 62
60 63
61 64
62 65
63 65
7
39
43
46
49
51
45
49
52
55
57
54
55
56
58
59
54
55
56
58
59
57
57
58
59
60
58
59
60
60
61
61
62
63
64
65
61
62
64
65
66
62
63
65
66
67
64
65
67
68
69
NC
26
30
34
36
39
25
30
34
33
35
28
30
31
31
33
28
30
31
32
33
32
32
33
33
34
33
33
34
35
35
33
34
35
36
38
33
34
35
36
38
30
33
34
36
38
33
34
36
38
39
• All performance based on tests conducted in accordance with
ASHRAE 130-2008 and AHRI 880-2011
• All NC levels determined using AHRI 885-2008 Appendix E. See
Terminal Unit Engineering Guidelines.
• Dash (-) in space denotes NC value less than NC10
• Only highlighted data points are AHRI certified. Refer to
page M38 for AHRI Certified Performance Listings.
M
PERFORMANCE DATA
16
CFM
Redefine your comfort zone™ | www.titus-hvac.com
PEDV, PEDC, DEDV WITH INTEGRAL ATTENUATOR AND MIXING BAFFLES / DISCHARGE SOUND PERFORMANCE
M33
Redefine your comfort zone™ | www.titus-hvac.com
Dual Duct High Performance Blending
single / dual duct terminals
MDV / MDC
• Standard AeroCrossTM multi-point center averaging velocity sensors
in multiple location combinations to match any control requirement
• Standard matte faced insulation for maximum thermal and acoustic
performance
• Mechanically sealed and gasketed, leak resistant construction
• High performance mixing section
• Choice of right or left hand cold duct location; right hand is standard
• Standard 22 gauge casing with slip and drive discharge connection
• Controls supplied by Titus are factory calibrated for quicker start-up
MDV / MDC
M
AVAILABLE MODELS:
PMDV / Pneumatic
PMDC / Pneumatic
DMDV / Digital Electronic
OVERVIEW
Titus Dual Duct terminals vary the airflow individually between hot and
cold inlets for highly accurate temperature control. Dual duct systems
are an ideal vehicle for alternative ventilation strategies and humidity
control. Additionally, total filtration of all air delivered to the zone is
possible. Titus dual duct terminals provide high performance and value,
making them the preferred selection for these applications.
ADDITIONAL FEATURES
MDV / MDC
• Direct digital control package supplied by Titus includes: direct
digital controller, damper actuators and flow tranducers
• Dual density insulation, coated to prevent air erosion, meet
requirements of NFPA 90A and UL 181
M34
See website for Specifications
single / dual duct terminals
DIMENSIONS
PMDV/PMDC - Basic Unit with Controls
G
L
4"
H
F
D
A
W
Discharge
D
E
Slip and Drive
Duct Connection
J
Controllers
4½"
Pneumatic Actuator
DMDV - Basic Unit with Controls
8"
Max
G
4"
L
Redefine your comfort zone™ | www.titus-hvac.com
MDV / MDC UNIT DIMENSIONS
H
M
6½"
F
D
W
Discharge
A
D
E
Slip and Drive
Duct Connection
6½"
18"
K
K
12¼"
Inlet Size cfm Range
0-225
0-350
0-500
0-650
0-900
0-1050
0-1400
0-2000
0-3000
0-4000
D
E
F
G
H
L
W
87/8
87/8
87/8
107/8
107/8
127/8
127/8
147/8
167/8
187/8
37/8
47/8
57/8
67/8
77/8
87/8
97/8
117/8
137/8
157/8
57/8
57/8
57/8
71/8
71/8
101/8
101/8
111/8
12½
151/8
57/8
57/8
57/8
81/8
81/8
111/8
111/8
131/8
161/8
161/8
53/8
53/8
33/8
6¾
33/8
6¾
33/8
33/8
33/8
33/8
8¼
8¼
8¼
10¼
10¼
12¾
12¾
15¼
181/8
181/8
34
34
34
42
42
50
50
58
66
72
19
19
19
23
23
27
27
31
35
38
All dimensions are in inches
PMDV
DMDV K
J
7
1 /8
2
17/8
2
17/8
2
7
/8
1
7
/8
1
-
DIMENSIONS
4
5
6
7
8
9
10
12
14
16
A
M35
single / dual duct terminals
Redefine your comfort zone™ | www.titus-hvac.com
PERFORMANCE DATA
PMDV, PMDC, DMDV / RADIATED SOUND PERFORMANCE
Size
4
5
6
7
M
8
9
10
12
PERFORMANCE DATA
14
M36
16
CFM
100
125
150
175
200
150
200
250
300
350
300
350
400
450
500
450
500
550
600
650
600
650
700
750
800
800
850
900
950
1000
900
1000
1100
1200
1300
1200
1400
1600
1800
2000
1500
1800
2100
2400
2700
2000
2400
2800
3200
3600
Min
∆Ps
0.18
0.29
0.41
0.56
0.74
0.15
0.27
0.42
0.60
0.82
0.43
0.58
0.76
0.96
0.39
0.32
0.39
0.47
0.56
0.66
0.37
0.43
0.50
0.57
0.65
0.20
0.22
0.25
0.28
0.31
0.21
0.26
0.31
0.37
0.44
0.29
0.39
0.51
0.64
0.80
0.16
0.23
0.31
0.41
0.52
0.20
0.28
0.39
0.50
0.64
2
55
56
57
58
59
55
58
60
62
63
58
59
60
60
63
62
63
64
64
65
62
63
63
64
64
67
67
68
68
68
63
64
65
65
66
68
69
70
70
71
66
67
68
69
70
70
71
72
73
74
3
50
52
53
55
56
51
54
55
57
58
54
54
55
56
57
56
57
58
58
59
56
57
57
58
58
57
58
58
58
59
58
59
59
60
61
60
61
62
63
64
58
60
61
62
63
60
61
62
63
64
1.0” ∆Ps
4
5
6
42 36 35
43 38 36
44 39 37
45 39 38
46 40 38
43 34 29
45 37 34
46 39 37
48 41 40
49 43 42
46 41 41
47 42 42
48 44 43
48 45 44
48 43 41
48 42 40
48 43 41
49 43 41
49 44 42
50 45 42
48 42 40
49 43 41
50 44 41
50 45 42
50 45 43
47 40 38
48 41 39
48 42 40
49 42 40
49 43 41
51 47 47
52 48 48
53 48 49
53 49 49
54 49 49
54 53 54
55 54 55
57 54 56
58 55 57
58 56 57
49 41 38
52 43 41
54 45 43
56 47 45
57 49 47
53 45 42
55 47 44
57 50 47
59 51 49
61 53 51
7
31
32
33
34
34
21
27
32
36
40
37
38
38
39
36
36
36
37
37
37
38
39
39
40
40
29
30
30
31
31
47
47
48
48
48
52
52
53
54
54
31
34
36
38
40
37
40
42
44
45
NC
17
20
21
23
24
18
22
23
25
27
22
22
23
24
25
24
25
27
27
28
24
25
25
27
27
31
31
32
32
32
27
28
28
29
30
32
33
34
34
36
29
31
32
33
34
34
36
37
38
40
Octave Band Sound Power, Lw
1.5” ∆Ps
2
3
4
5
6
7
57 53 45 38 37 34
58 55 46 40 38 35
59 56 47 41 39 36
60 58 48 42 40 36
61 59 49 42 41 37
58 55 47 37 32 24
60 57 49 40 36 30
63 59 50 43 40 35
64 60 52 45 42 40
66 62 53 46 45 43
61 58 50 44 45 41
66 62 53 46 45 43
63 59 51 47 47 43
64 60 52 48 48 43
64 60 53 49 49 44
64 60 51 45 44 41
65 61 52 46 45 42
66 61 53 46 45 42
67 62 53 47 46 42
68 62 54 48 46 43
65 61 52 45 44 43
66 61 53 46 45 43
67 61 53 47 45 44
67 62 54 48 46 44
68 62 54 48 47 45
70 61 51 43 41 34
70 62 52 44 42 34
71 62 52 45 42 35
71 62 52 46 43 35
71 63 53 46 44 36
68 63 54 50 51 51
69 63 55 51 52 51
69 64 56 51 52 52
70 65 56 52 53 52
70 65 57 52 53 53
71 63 58 57 58 57
72 65 59 58 59 58
73 66 60 58 60 58
74 67 61 59 61 59
75 67 62 60 62 59
70 62 52 43 40 35
71 64 54 46 43 37
72 65 56 48 46 40
73 66 58 50 48 42
74 67 60 51 50 44
74 64 56 48 44 41
75 65 58 50 47 43
76 66 60 52 49 45
77 68 62 54 51 47
78 68 64 56 53 49
• Radiated sound is the noise transmitted through the unit casing
• Min ∆Ps is the static pressure drop from the unit inlet to the unit
outlet with the cold damper full open
• Sound power levels are in dB, ref 10-12 watts
• Sound performance based on units lined with standard dual density
fiberglass lining
NC
21
23
24
27
28
23
25
28
29
31
27
31
28
29
29
29
30
30
31
32
30
30
31
31
32
34
34
36
36
36
33
33
34
35
35
36
37
38
40
41
34
36
37
38
40
40
41
42
43
45
2
58
60
61
62
62
59
62
64
66
67
64
67
65
66
67
66
67
68
69
70
68
68
69
69
70
72
72
73
73
73
71
72
73
73
74
74
75
76
77
78
73
74
75
76
77
77
78
79
80
80
3
55
57
58
60
61
57
59
61
63
64
61
64
62
63
63
62
63
64
64
65
63
64
64
65
65
64
65
65
65
66
66
66
67
68
68
66
67
68
69
70
65
66
68
69
69
67
68
69
70
71
2.0” ∆Ps
4
5
6
47 40 39
49 41 40
50 42 41
50 43 41
51 44 42
50 39 34
52 42 38
53 45 41
55 47 44
56 48 47
52 47 47
56 48 47
54 49 50
55 50 51
56 51 52
54 47 47
56 51 52
55 48 48
56 49 49
56 50 49
55 47 47
56 48 47
56 49 48
57 50 49
57 50 49
54 46 43
54 46 44
55 47 45
55 48 45
56 49 46
57 52 54
57 53 54
58 53 55
59 54 55
59 54 56
60 60 61
61 61 62
62 61 63
63 62 64
64 63 65
54 45 42
56 48 45
58 50 47
60 52 50
62 53 51
58 50 46
60 52 49
62 54 51
64 56 53
66 58 55
7
36
37
38
39
39
26
33
38
42
45
44
45
46
46
47
45
47
46
46
46
46
47
47
48
48
37
38
38
39
39
54
54
55
55
55
60
61
62
62
63
37
40
42
44
46
43
46
48
50
51
NC
23
25
27
29
30
25
28
30
33
34
30
34
31
33
33
31
33
34
34
35
33
34
34
35
35
37
37
38
38
38
36
37
38
38
40
40
41
42
43
45
38
40
41
42
43
43
45
46
47
47
• All performance based on tests conducted in accordance with
ASHRAE 130-2008 and AHRI 880-2011
• All NC levels determined using AHRI 885-2008 Appendix E. See
Terminal Unit Engineering Guidelines.
• Dash (-) in space denotes NC value less than NC10
• Only highlighted data points are AHRI certified. Refer to page M38
for AHRI Certified Performance Listings.
single / dual duct terminals
PERFORMANCE DATA
Size
4
5
6
7
8
9
10
12
14
100
125
150
175
200
150
200
250
300
350
300
350
400
450
500
450
500
550
600
650
600
650
700
750
800
800
850
900
950
1000
900
1000
1100
1200
1300
1200
1400
1600
1800
2000
1500
1800
2100
2400
2700
2000
2400
2800
3200
3600
Min
∆Ps
0.18
0.29
0.41
0.56
0.74
0.15
0.27
0.42
0.60
0.82
0.43
0.58
0.76
0.96
0.39
0.32
0.39
0.47
0.56
0.66
0.37
0.43
0.50
0.57
0.65
0.20
0.22
0.25
0.28
0.31
0.21
0.26
0.31
0.37
0.44
0.29
0.39
0.51
0.64
0.80
0.16
0.23
0.31
0.41
0.52
0.20
0.28
0.39
0.50
0.64
2
65
68
71
73
75
68
72
75
77
79
74
76
77
78
79
74
76
77
78
79
75
76
76
77
78
75
76
76
77
78
76
77
78
79
80
78
80
81
82
83
76
78
80
82
83
79
81
82
84
85
3
57
60
63
65
67
59
63
67
69
72
65
67
68
69
70
67
69
70
71
72
68
69
69
70
71
65
65
66
66
66
66
67
68
69
70
67
69
71
72
74
64
67
69
71
73
67
70
72
73
75
1.0” ∆Ps
4
5
6
50 45 38
52 47 42
55 49 45
56 51 48
58 53 50
52 46 38
55 49 44
58 52 48
60 54 51
62 56 54
56 51 46
57 53 49
58 54 51
59 55 53
60 53 52
58 52 50
59 53 52
60 54 53
61 55 55
62 56 56
59 53 51
60 54 52
61 54 53
62 55 54
62 56 55
58 50 48
59 51 49
59 52 50
59 52 51
60 53 52
59 54 52
60 55 53
61 56 55
62 57 56
63 58 58
61 54 53
63 56 56
64 58 59
66 60 61
67 61 63
59 51 51
61 54 54
63 56 57
65 59 59
67 60 61
61 55 54
63 58 58
66 61 60
67 63 63
69 65 65
7
28
34
38
42
46
31
39
45
50
54
39
43
45
48
48
45
48
50
52
54
46
48
50
51
53
44
45
47
48
49
46
48
50
52
53
49
52
55
57
59
45
48
51
54
56
49
52
56
58
61
NC
21
25
29
31
34
25
30
34
33
35
29
31
33
34
35
29
31
33
34
35
30
31
31
30
31
28
29
29
30
31
29
30
31
33
34
31
34
35
36
38
29
31
34
36
38
33
35
36
39
40
Octave Band Sound Power, Lw
1.5” ∆Ps
2
3
4
5
6
7
67 59 52 47 40 30
70 62 55 50 44 36
73 65 57 52 47 40
75 67 59 54 50 44
77 69 60 55 52 47
69 61 54 48 40 33
73 65 58 52 46 40
76 69 61 55 50 46
79 71 63 57 53 51
81 74 65 59 56 55
77 68 59 54 48 42
81 74 65 59 56 55
80 71 62 57 53 48
81 73 63 58 55 50
81 74 64 59 56 53
76 70 61 54 51 47
78 71 62 56 53 50
79 72 63 56 55 52
80 74 64 57 57 54
81 75 65 58 58 56
78 71 63 56 52 48
78 72 64 57 54 50
79 72 64 57 55 52
80 73 65 58 56 53
80 74 66 59 57 55
78 68 62 53 51 47
79 69 62 54 52 48
79 69 63 54 53 49
80 70 63 55 54 50
80 70 63 56 54 51
80 70 63 56 54 49
81 71 64 58 55 51
82 72 65 59 57 52
82 72 65 60 58 54
83 73 66 60 60 56
81 70 64 56 55 51
82 72 66 58 58 54
84 74 68 60 61 57
85 75 69 62 63 59
86 77 70 64 65 61
79 68 62 53 53 47
81 70 64 56 56 51
83 72 66 59 59 54
84 74 68 61 61 56
86 76 70 63 63 58
82 70 64 57 56 51
84 73 66 60 60 55
85 75 68 63 63 58
87 77 70 65 65 60
88 78 72 67 67 63
• Discharge sound is the noise emitted from the unit discharge into
the downstream ductwork
• Min ∆Ps is the static pressure drop from the unit inlet to the unit
outlet with the cold damper full open
• Sound power levels are in dB, ref 10-12 watts
• Sound performance based on units lined with standard dual density
fiberglass lining
NC
24
28
31
34
36
26
31
35
35
38
33
38
36
38
38
31
34
35
36
38
34
34
35
34
34
31
33
33
34
34
34
35
36
36
38
35
36
39
40
42
33
35
38
39
42
36
39
40
43
44
2
68
71
74
76
78
71
75
78
80
82
79
82
81
82
83
78
80
80
81
82
80
80
81
82
82
80
81
81
82
82
82
83
84
85
86
83
84
86
87
88
81
83
85
86
88
84
86
88
89
90
3
60
63
66
68
70
62
67
70
73
75
70
75
74
75
76
71
75
74
75
76
73
74
75
75
76
71
71
72
72
73
72
73
74
75
76
72
74
76
78
79
70
73
75
77
78
73
75
77
79
80
4
54
57
59
61
62
56
60
62
65
67
62
67
64
66
66
63
65
65
66
67
65
66
67
67
68
64
65
65
66
66
65
66
67
68
69
66
68
70
71
73
64
66
68
70
72
65
68
70
72
74
2.0” ∆Ps
5
6
49 42
52 45
54 49
56 51
57 54
50 42
54 47
57 51
59 55
61 57
56 50
61 57
59 54
60 56
61 58
56 52
61 58
58 56
59 58
60 59
58 54
59 55
60 56
60 57
61 58
55 52
56 53
57 54
57 55
58 56
58 55
60 57
61 58
62 60
62 61
58 57
60 60
62 62
64 64
65 66
55 54
58 57
60 60
62 63
64 65
59 58
62 61
65 64
67 66
69 69
7
32
37
42
46
49
34
41
47
52
56
43
56
49
52
54
48
54
53
55
57
50
51
53
55
56
48
50
51
52
53
50
52
54
56
57
53
56
58
61
63
49
53
55
58
60
53
56
59
62
64
NC
25
29
33
35
38
29
34
38
36
39
35
39
38
39
40
34
36
36
38
39
36
36
38
36
36
34
35
35
36
36
36
38
39
40
42
38
39
42
43
44
35
38
40
42
44
39
42
44
45
47
• All performance based on tests conducted in accordance with
ASHRAE 130-2008 and AHRI 880-2011
• All NC levels determined using AHRI 885-2008 Appendix E. See
Terminal Unit Engineering Guidelines.
• Dash (-) in space denotes NC value less than NC10
• Only highlighted data points are AHRI certified. Refer to page M38
for AHRI Certified Performance Listings.
M
PERFORMANCE DATA
16
CFM
Redefine your comfort zone™ | www.titus-hvac.com
PMDV, PMDC, DMDV / DISCHARGE SOUND PERFORMANCE
M37
single / dual duct terminals
Redefine your comfort zone™ | www.titus-hvac.com
PERFORMANCE DATA
M
AHRI Directory of Certified Performance
Titus is a charter member company and current partici- PMDV, PMDC, DMDV
pant in the AHRI Directory of Certified Performance. This
Inlet
Rated Min
voluntary certification program was developed by parSize
CFM ∆Ps
ticipating manufacturers in conjunction with the former
Air-Conditioning and Refrigeration Institute (ARI) in the
04
150
0.41
1990’s. It is currently administrated by the Air-Condi05
250
0.42
tioning, Heating, and Refrigeration Institute (AHRI). The
06
400
0.76
purpose of this program is to provide for the independent
07
550
0.47
verification of manufacturers’ published performance
data. Only participating products are authorized to bear
08
700
0.50
the AHRI VAV Certification Mark. Certified data may be
09
900
0.25
viewed and downloaded at www.ahrinet.org.
10
PEDV, PEDC, PMDV, PMDC, DEDV, DMDV
PERFORMANCE DATA
0.31
Radiated Sound Power
Discharge Sound Power
W
2
2
5.875
5.875
59 56 47 41 39 36 73 65 57 51 47 40
5.875
5.875
63 59 50 43 40 35 76 69 61 54 50 46
5.875
5.875
63 59 51 47 47 43 80 71 62 56 53 48
8.125
7.125
66 61 53 46 45 42 79 72 63 55 55 52
67 61 53 47 45 44 79 72 64 56 55 52
3
4
5
6
7
3
4
5
6
7
8.125
7.125
11.125
10.125 71 62 52 45 42 35 79 69 63 54 53 49
11.125
10.125 69 64 56 51 52 52 82 72 65 59 57 52
In order to participate in this program, member compa12
1600 0.51 13.125 11.125 73 66 60 58 60 58 84 74 68 60 61 57
nies pay annual dues based on sales volume, submit pub14
2100 0.31 16.125 12.500 72 65 56 48 46 40 83 72 66 59 59 54
lished performance data for all applicable model types,
16
2800 0.39 16.125 15.125 76 66 60 52 49 45 85 75 68 63 63 58
and agree to provide a number of randomly selected
product samples for annual rounds of independent testing at the manufacturers’ expense. All verification test- PEDV, PEDC, DEDV WITH INTEGRAL ATTENUATOR & MIXING BAFFLE
ing is conducted in accordance with ASHRAE Standard
Discharge
Radiated Sound Power
Discharge Sound Power
Inlet
Rated Min
130 ‘Methods of Testing Air Terminal Units’. These tests
Size
CFM ∆Ps
H
W
2 3 4 5 6 7 2 3 4 5 6 7
are conducted to verify that a manufacturer’s published
certified ratings are within the test tolerances outlined in
04
150
0.41 5.875 5.875 54 53 44 38 36 31 74 65 57 50 50 45
AHRI Standard 880 ‘Performance Rating of Air Terminals’.
05
250
0.47 5.875 5.875 56 54 47 40 39 35 74 67 59 51 53 50
Any failure to demonstrate the certified performance is
06
400
0.91 5.875 5.875 55 57 49 43 41 37 73 67 60 54 55 54
punished by additional testing requirements, mandatory
performance re-rating, monetary penalties and possible
07
550
0.53 8.125 7.125 63 57 51 45 45 41 74 69 60 53 56 54
expulsion from the Certified Directory.
08
700
0.55 8.125 7.125 61 59 50 43 41 40 73 71 61 55 57 56
Product samples provided for certification testing are
standard production units with standard ½” dual density fiberglass lining (unless otherwise specified) and no
optional appurtenances such as add-on attenuators or
heating/cooling coils. The certified ratings are measured
at the standard operating points under the following test
conditions:
M38
1100
Discharge
H
• Rated airflow (cfm) – Based on an inlet velocity of
2000 fpm
• Rated Min ∆Ps (in wg) – Minimum static pressure
drop from the cold inlet to discharge at rated airflow
with damper full open
• Rated ∆Ps (in wg) – A static pressure drop of 1.5 in
wg from cold inlet to discharge with the hot damper
fully closed
• Rated sound power by octave band (dB, re 10-12
watts) – Radiated and discharge sound performance
conducted in a reverberation room that meets both
the broadband and pure tone qualifications of AHRI
Standard 220
09
900
0.23
11.125
10.125 66 57 50 45 46 45 78 68 59 55 58 57
10
1100
0.38
11.125
10.125 64 57 49 43 42 41 79 69 61 57 59 61
12
1600
0.44
13.125
11.125 68 62 58 55 58 57 79 70 62 58 60 61
14
2100
0.34
16.125
12.500 67 60 53 47 48 49 78 69 62 58 61 62
16
2800
0.40
16.125
15.125 70 61 56 50 51 51 79 69 62 59 62 64
PEDV, DEDV WITHOUT ATTENUATOR
Inlet
Size
Rated
CFM
Min
∆Ps
Discharge
Radiated Sound Power
Discharge Sound Power
H
2
2
04
150
0.04
8
24.125 60 57 46 41 40 37 73 66 60 54 54 49
05
250
0.03
8
24.125 62 59 49 42 41 37 74 66 61 56 55 50
06
400
0.13
8
24.125 63 61 52 44 42 38 75 71 65 60 57 52
07
550
0.10
10
24.125 64 59 53 47 43 34 74 72 63 59 56 51
08
700
0.02
10
24.125 65 60 53 47 47 45 77 73 63 58 56 52
09
900
0.05
12.5
28.125 64 58 53 47 45 38 77 69 63 59 57 54
10
1100
0.01
12.5
28.125 67 62 57 55 54 43 78 71 65 63 60 55
12
1600
0.01
15
32.125 66 62 59 53 50 44 78 74 68 64 62 58
14
2100
0.04
17.5
40.125 66 62 55 53 50 46 74 69 66 63 63 59
16
2800
0.03
18
48.125 66 61 54 50 50 45 76 70 66 64 62 57
W
3
4
5
6
7
3
4
5
6
7