single / dual duct terminals
Transcription
single / dual duct terminals
single / dual duct terminals M Redefine your comfort zone. ™ | www.titus-hvac.com Redefine your comfort zone™ | www.titus-hvac.com Table of Contents SINGLE / DUAL DUCT TERMINALS M M2 single / dual duct terminals single/dual duct terminal products Single / Dual Duct Terminal Products.................................................................................................................................................. M3 single duct terminals ESV Single Duct................................................................................................................................................................................... M5 Design Features............................................................................................................................................................................ M5 Control Strategies......................................................................................................................................................................... M7 ESV - Basic Unit with Controls..................................................................................................................................................... M9 Dimensions................................................................................................................................................................................. M10 Accessories................................................................................................................................................................................ M11 Performance Data....................................................................................................................................................................... M14 Electric Coils............................................................................................................................................................................... M21 AHRI Certification...................................................................................................................................................................... M23 dual duct terminals EDV/MDV Dual Duct.......................................................................................................................................................................... M24 Design Features.......................................................................................................................................................................... M24 Control Strategies....................................................................................................................................................................... M25 EDV - Dual Duct without Attenuator.......................................................................................................................................... M26 Dimensions................................................................................................................................................................................. M27 Performance Data....................................................................................................................................................................... M28 EDV/EDC - Dual Duct with Attenuator....................................................................................................................................... M30 Dimensions................................................................................................................................................................................. M31 Performance Data....................................................................................................................................................................... M32 MDV/MDC - Dual Duct High Performance Blending................................................................................................................. M34 Dimensions................................................................................................................................................................................. M35 Performance Data....................................................................................................................................................................... M36 AHRI Certification...................................................................................................................................................................... M38 Single / Dual Duct Terminal Products single / dual duct terminals ESV AVAILABLE CONFIGURATIONS CONTROL OPTIONS UNIT ACCESSORIES • With integral attenuator • With water coils • With integral electric coil section • • • • • • • • • • • • • • • Pneumatic Electric TA1 electronic DDC controls Factory mounting of controls by others OEM controls (Titus Alpha BACnet) EcoShield lining Fibre Free lining Steri-Loc™ lining UltraLoc lining Multi-outlet section Round outlet adapter Removable flow sensor Access door 20g construction Redefine your comfort zone™ | www.titus-hvac.com single duct terminals pages: M5-M23 M SINGLE / DUAL DUCT TERMINALS For detailed controls information, please refer to the Terminal Unit Accessories section M3 single / dual duct terminals Redefine your comfort zone™ | www.titus-hvac.com Single / Dual Duct Terminal Products (continued) dual duct terminals pages: M24-M33 EDV AVAILABLE CONFIGURATIONS CONTROL OPTIONS UNIT ACCESSORIES • Non-mixing • With integral attenuator/mixing section • Optional mixing baffle • • • • • • • • • • M Pneumatic DDC controls Factory mounting of controls by others OEM controls (Titus Alpha BACnet) dual duct terminals SINGLE / DUAL DUCT TERMINALS pages: M34-M38 M4 EcoShield lining Fibre Free lining SteriLoc™ lining UltraLoc lining Removable flow sensor 20g construction MDV AVAILABLE CONFIGURATIONS CONTROL OPTIONS UNIT ACCESSORIES • Special high performance blending • • • • • • • • • • Pneumatic DDC controls Factory mounting of controls by others OEM controls (Titus Alpha BACnet) EcoShield lining Fibre Free lining SteriLoc™ lining UltraLoc lining Removable flow sensor 20g construction single / dual duct terminals Single Duct Design Features Single duct terminals are the fundamental building blocks for a variable air volume (VAV) system. Their primary function is to regulate airflow to a zone, in response to zone temperature requirements. The Titus ESV is unique as it incorporates many design features that increase performance, decrease installation and service cost and offers increased value, over and above this basic function. All VAV terminals are not equal! By specifying the Titus ESV, you are assured of accurate, AHRI Certified performance ratings. All units are tested, and data shown, in accordance with AHRI Standards. A wide selection of unit configurations, accessories and control types provide considerable scope for problem solving and cost-effective innovation. Building owners will benefit from the energy efficient low leakage design, reducing utility expenses. Control accuracy, especially at minimum flow rates, is easier to achieve with a Titus multi-point inlet velocity sensor. Control accuracy is critical in maintaining good air quality reducing energy waste. The ESV’s standard insulation is a dual density liner. The skin resists abrasion and erosion from air movement. The body maximizes thermal and acoustical performance. The Titus single blade damper design helps reduce noise levels too, for a quieter work environment. Redefine your comfort zone™ | www.titus-hvac.com LEADING THE INDUSTRY: THE TITUS ESV SINGLE DUCT VAV TERMINAL The ESV’s compact size and easy access for service saves time and expense in installation. The ESV fits easily in cramped mechanical spaces, either in new building construction or retrofit. ESV Casing Leakage, cfm INLET SIZE 4, 5, 6 7, 8 9, 10 12 14 16 0.5 2 4 4 5 6 7 ∆PS, IN WG 1.0 2.0 3 4 5 7 6 8 7 10 9 13 10 14 Damper Leakage, cfm INLET SIZE 4, 5, 6 7, 8 9, 10 12 14 16 3.0 5 9 10 12 16 17 1.0 3 3 3 3 3 4 ∆PS, IN WG 2.0 4.0 4 6 4 6 4 6 4 6 5 7 5 7 6.0 7 7 7 7 8 9 M MORE REASONS TO SPECIFY AND SELECT THE TITUS ESV: Titus innovation carries through the widest array of standard single duct terminal configurations. ETL listed electric coils, manufactured by Titus, are installed, wired and functionally tested as an integral unit before shipment for quicker, trouble-free job-site installation. Multiple outlets with standard locking balancing dampers and integral attenuators are also available. Fibre Free eliminates the requirement for foil linings and solid inner liners since there is no fiberglass in the airstream. Additionally, Fibre Free minimizes mold growth since it holds no moisture, is acoustically preferable to foil or solid metal linings and maintains acceptable thermal protection. All of these benefits are available at a competitive price and significantly less than solid metal liners. EcoShield is a sustainable liner comprised of recycled denim making it environmentally friendly and contains no harmful irritants or chemicals. Titus - experts in DDC zone control! With a detailed understanding developed through years of selling and supporting the powerful TD1 digital controller, and now the Titus BACnet OEM controls, Titus has industry leading experience in the application of Direct Digital Control (DDC) to terminals. This same expertise is made available when your project requires quality engineering, coordination and manufacturing for factory mounting when controls are supplied by others. Count on Titus - the industry leader in VAV! DESIGN FEATURES Titus continues to offer the most innovative and popular lining alternatives for special applications including Fibre Free; the industry benchmark SteriLoc; and the premium double wall liner, UltraLoc and EcoShield which is the only natural fiber insulation on the market. SteriLoc adds the feature of a very high density, rigid insulation and special “Z-Strip” construction for an extremely rigid terminal. Sound levels are generally superior to dual wall construction, while offering virtually identical levels of protection. SteriLoc provides a smooth, nonporous skin to guard against mold and bacteria growth. Erosion is eliminated, as there is no glass fiber exposure to the airstream. It has reinforced surfaces that can be wiped down. M5 single / dual duct terminals Redefine your comfort zone™ | www.titus-hvac.com Design Features (continued) M Removable flow sensor (optional) Unique integral fold fabrication method increases lining and casing integrity and minimizes leakage Beaded inlet for consistent roundness and low leakage construction, sized to fit standard round duct Standard insulation is ½-inch dual density fiberglass, to resist erosion at surface velocities up to 5,000 fpm. Meets requirements of NFPA 90A and UL181. Delrin® damper bearings provide smoother damper operation AeroCrossTM multi-point, center averaging sensor amplifies flow signal for best control of low flow rates. Center averaging feature provides signal accuracy regardless of inlet duct configuration. Damper design provides smoother airflow for reduced sound levels and lower leakage DESV Flow measurement taps for easy balancing connections NEMA 1 control enclosure available for protection of electronic controls. Double backplane construction for strength and easier control installation, with no exposed screw tips for safe handling. Optional Fibre Free, reinforced sealed skin SteriLoc, or metal lined UltraLoc liners guard against environments favoring bacteria and mold growth. Fibre Free & EcoShield are ideal IAQ insulation providing acoustical and thermal characteristics of fiberglass insulation without the concern of fiberglass in the airstream. All liners meet UL 181 and NFPA 225 (25/50). UL Class II transformers and disconnect switches available installed for use with any electronic control configuration DESIGN FEATURES Multiple knockouts in sizes from 7/16-inch to 11/8-inch to accommodate almost any field connection requirement M6 DESV SINGLE DUCT CONTROL STRATEGIES single / dual duct terminals Pneumatic: See pg. O18 / Analog: See pg. O11 / Digital: See pg. O5 cfm Increase For detailed information on specific control types, refer to the following pages in Section O: Max. Min. Room Temperature Increase ow Fl cfm Increase er at Pneumatic: See pg. O18 / Analog: See pg. O11 / Digital: See pg. O5 Max. tW Ho VAV Cooling, Hot Water Reheat As the room temperature increases, the unit modulates the hot water coil valve toward the closed position. On a further increase in room temperature, the unit modulates the cold airflow from the minimum (which must be greater than zero) to the maximum setting. Redefine your comfort zone™ | www.titus-hvac.com Variable Air Volume - VAV Cooling As the room temperature increases over setpoint, the unit modulates the cold airflow from the minimum (which may be zero flow) to the maximum setting. Min. Room Temperature Increase Ho VAV Cooling, Dual Minimum Flows with Hot Water Reheat In the cooling mode, as the room temperature increases, the unit thermostat modulates the cold airflow from the lower minimum to the maximum setting. ow VAV Cooling and VAV Heating, Local Heat Flows In the heating mode, as the room temperature increases, the unit modulates the airflow from maximum to minimum and modulates the hot water coil valve toward the closed position. Max. Max. Room Temperature Increase VAV Cooling and VAV Heating, Central Heat Flows In the heating mode, as the room temperature increases, the unit modulates the airflow from maximum to minimum and modulates the hot water coil valve toward the closed position. Max. A further increase in room temperature changes the operation to the cooling mode, and the unit modulates the cold airflow from minimum to maximum, which is different from the heating maximum (usually higher). Both the heating and the cooling maximum airflows are adjustable. Pneumatic: See pg. O18 / Analog: See pg. O11 / Digital: See pg. O5 cfm Increase Max. CONTROL STRATEGIES low rF ate cfm Increase tW Ho Pneumatic: See pg. O18 / Analog: See pg. O11 / Digital: See pg. O5 Min. Room Temperature Increase Pneumatic: See pg. O18 / Analog: See pg. O11 / Digital: See pg. O5 A further increase in room temperature changes the operation to the cooling mode, and the unit modulates the cold airflow from minimum to maximum, which is the same as the heating maximum. Alt. Min. M Fl In the heating mode, the unit references the alternate (higher) minimum airflow. As the room temperature decreases, the unit modulates the airflow from the maximum to the higher minimum, then modulates the hot water coil valve toward the open position. The valve operates only in the heating mode. cfm Increase er at tW Max. Room Temperature Increase M7 single / dual duct terminals Constant Volume, Hot Water Reheat The cold airflow remains constant regardless of changes in duct pressure or room temperature. As the room temperature increases, the unit modulates the hot water coil valve toward the closed position. low rF cfm Increase a te tW Pneumatic: See pg. O18 / Analog: See pg. O11 / Digital: See pg. O5 Ho Room Temperature Increase VAV Cooling, Electric Reheat As the room temperature increases, the unit de-energizes the electric heating coil one step at a time. On a further increase in room temperature, the unit modulates the cold airflow from the minimum (which must be greater than zero) to the maximum setting. Pneumatic: See pg. O18 / Analog: See pg. O11 / Digital: See pg. O5 Step 2 Max. Step 1 cfm Increase Redefine your comfort zone™ | www.titus-hvac.com Control Strategies (continued) Min. Room Temperature Increase VAV Cooling, Dual Minimum Flows with Electric Reheat In the cooling mode, as the room temperature increases, the room thermostat modulates the cold airflow from the lower minimum to the maximum setting. In the heating mode, as the room temperature decreases, the unit modulates the airflow from the lower minimum to the higher minimum, then energizes the electric heating coil stages. Pneumatic: See pg. O18 / Analog: See pg. O11 / Digital: See pg. O5 Step 2 Alt. Min. cfm Increase M Max. Step 1 Min. Room Temperature Increase M8 When the signal is removed, the unit resumes normal control of airflow. With the central system now supplying cold air, as room temperature increases, the unit modulates the cold airflow from minimum to the maximum setting. Pneumatic: See pg. O18 / Analog: See pg. O11 / Digital: See pg. O5 Max. cfm Increase CONTROL STRATEGIES VAV Cooling with Morning Warmup When provided the appropriate signal, the damper in the terminal modulates to maximum or fully open position. Heated air from the central system moves through the duct (the flow may be pressure dependent with some control types). Min. Room Temperature Increase Single Duct Terminal Units single / dual duct terminals Redefine your comfort zone™ | www.titus-hvac.com ESV • ESV can be installed horizontally, vertically or at any angle; unit operation is not affected by position • Choice of right or left hand control location • Standard AeroCross multi-point center averaging velocity sensor (except EESV) • Standard dual density insulation • Controls supplied by Titus are factory calibrated for a quicker start-up • Standard 22-gauge casing with slip and drive connection ESV See website for Specifications AVAILABLE MODELS: PESV / Pneumatic EESV / Electric AESV / Analog Electronic DESV / Digital Electronic M ESV cutaway view OVERVIEW Single Duct terminals are the fundamental building blocks for Variable Air Volume (VAV) systems. Their primary function is to regulate airflow to a zone, in response to zone temperature requirements. The Titus ESV is unique as it incorporates many design features that increase performance, decrease service and installation costs, and offer increased value, over and above this basic function. ESV M9 single / dual duct terminals Redefine your comfort zone™ | www.titus-hvac.com DIMENSIONS M ESV UNIT DIMENSIONS Pneumatic Actuator PESV W M L Thermostat & 20 psi Main Air Connections for ¼” Dia. Tubing Slip and Drive Cleat Connection D H Multi-Point Center Averaging Velocity Sensor DESV AESV EESV 4½” F W Control Cover (optional) M F L G 12¼” H F D Control Enclosure 6½” Slip & Drive Cleat Connection 18” DIMENSIONS (Optional for cooling only) M10 F INLET SIZE CFM RANGE D 4 5 6 7 8 9 10 12 14 16 24X16 0-225 0-350 0-500 0-650 0-900 0-1050 0-1400 0-2000 0-3000 0-4000 0-8000 37/8 47/8 57/8 67/8 77/8 87/8 97/8 117/8 137/8 157/8 7 23 /8 - 157/8 PESV 17/8 17/8 17/8 7 /8 7 /8 7 /8 AESV DESV EESV 21/8 21/8 21/8 11/8 11/8 11/8 G H L M W 73/8 73/8 73/8 73/8 73/8 53/8 53/8 53/8 33/8 33/8 53/8 8 8 8 10 10 12½ 12½ 15 17½ 18 18 15½ 15½ 15½ 15½ 15½ 15½ 15½ 15½ 15½ 15½ 15 53/8 53/8 33/8 33/8 33/8 33/8 33/8 33/8 33/8 33/8 33/8 12 12 12 12 12 14 14 16 20 24 38 All dimensions are in inches single / dual duct terminals ACCESSORIES Titus’ unique integral design minimizes casing leakage and disturbance to airflow with no casing or insulation seams. 39½ 6½ W 18 INTEGRAL ELECTRIC COIL 12¼ With a rigid one piece assembly, Titus locates the heating elements for optimal heat transfer and insets them for protection during shipment and installation. STANDARD FEATURES: • Primary automatic reset thermal cutout (one per coil) • Secondary manual reset thermal cutout • Airflow switch (differential pressure) • Derated nickel chrome heating elements • Magnetic or safety contactors (as required) • Line terminal block • Control terminal block • ETL listed • 80/20 nickel chrome element wire H 6¼ 39½ W 12 Redefine your comfort zone™ | www.titus-hvac.com INTEGRAL SOUND ATTENUATOR H 365/8 M L W Side View End View OPTIONAL FEATURES: • • • • • • Class ll, 24 volt control transformer Mercury contactors Door interlock disconnect switch Main supply fuses Dust tight construction Removable flow sensor H HOT WATER REHEAT COILS 39½ M Details on water coil features are shown on performance pages M18-22. L W H INTEGRAL SOUND ATTENUATOR WITH OPTIONAL HOT WATER REHEAT COIL Side View H M W 4, 5 6 7, 8 9, 10 12 14 16 24 x 16 8 8 10 12½ 15 17½ 18 18 53/8 33/8 33/8 33/8 33/8 33/8 33/8 33/8 12 12 12 14 16 20 24 38 WATER COIL L (1-2 ROW) L (3-4 ROW) 5 7¼ 5 7¼ 5 7¼ 5 7¼ 5 7¼ 7½ 9¾ 7½ 9¾ 5 7¼ ACCESSORIES INLET SIZE End View Note: The total length of the ESV basic unit and accessories (attenuators and coils) is the summation of basic unit length and the accessories length All dimensions are in inches M11 single / dual duct terminals Redefine your comfort zone™ | www.titus-hvac.com ACCESSORIES MULTI-OUTLET PLENUMS FOR SINGLE DUCT TERMINALS 2 Outlets 3 Outlets 36” 33/8” TYP. G 2 Outlets W M G H ESV Unit Sizes Outlet Size D 4, 5, 6 7, 8 8 9, 10 9, 10 12 12 14 14 16 16 57/8 77/8 77/8 97/8 77/8 117/8 97/8 117/8 97/8 117/8 97/8 W D TYP. 36” M H 33/8” TYP. G 5 Outlets W D TYP. D TYP. D TYP. 33/8” TYP. 4 Outlets M 3 Outlets 5 Outlets 36” 33/8” TYP. G H D TYP. 4 Outlets 36” D TYP. W H D TYP. 2 Outlets G M 43/8 53/8 53/8 63/8 63/8 63/8 - 3 Outlets G M 43/8 53/8 53/8 53/8 63/8 63/8 63/8 63/8 63/8 63/8 - 4 Outlets G M 53/8 12 53/8 14 53/8 12 63/8 14 63/8 14 63/8 14 5 Outlets G M 53/8 12 63/8 14 63/8 14 63/8 14 H W 8 10 10 12½ 12½ 15 15 17½ 17½ 18 18 12 12 12 14 14 16 16 20 20 24 24 ROUND OUTLETS ACCESSORIES 33/8“ M12 D 4“ W D H All dimensions are in inches D TYP. Unit Size 4 5 6 7 8 9 10 12 14 16 D 37/8 47/8 57/8 67/8 77/8 87/8 97/8 117/8 137/8 157/8 H 8 8 8 10 10 12½ 12½ 15 17½ 18 W 12 12 12 12 12 14 14 16 20 24 single / dual duct terminals ACCESSORIES Redefine your comfort zone™ | www.titus-hvac.com REMOVABLE FLOW SENSOR Removable Sensor Installed #8 Sheet metal screw 6 places Sensor Removed Removable flow sensor assembly M ESV WITH ACCESS DOOR OPTION ESV Terminal Unit Gasket (Access door is sealed with foam gasket material) Insulation type specified per order Access Door (Insulated) 6.00 6.00 2.25 2.25 9.00 9.00 39.50 0.50 0.50 ACCESSORIES 15.50 Right Hand Unit Shown Basic Unit w/Attenuator (Bottom View) Basic Unit (Bottom View) All dimensions are in inches M13 single / dual duct terminals Redefine your comfort zone™ | www.titus-hvac.com PERFORMANCE DATA M RECOMMENDED PRIMARY AIR CFM RANGES / ALL TERMINALS Control Types: PESV / Pneumatic AESV / Analog Electronic DESV / Digital Electronic QUICK SELECTION PROCEDURE 1.Select unit inlet size based upon acoustic parameters and/or maximum pressure drop requirements, using pages M15-M16 2.Check inlet size selection against cfm control limits based on control type shown on this page 3.Select accessories (multi-outlets, attenuators) as required 4.Select reheat coil, if required. Make your selection using the actual heating flow rate, not cooling. cfm Ranges of Minimum and Maximum Settings Inlet Size Total cfm Range 4 5 6 7 8 9 10 12 14 16 24 x 16 0-225 0-350 0-500 0-650 0-900 0-1050 0-1400 0-2000 0-3000 0-4000 0-8000 PESV - Pneumatic PESV - Pneumatic AESV - Analog Electronic DESV - Digital Titus II Controller Titus I Controller TA1 Controller Typical Controller Minimum 45*-170 65*-270 80*-330 105*-425 145*-590 175*-700 230*-925 325*-1330 450*-1800 580*-2350 1400*-5200 Maximum 80-225 120-350 150-500 190-650 265-900 315-1050 415-1400 600-2000 810-3000 1100-4000 2600-8000 Minimum 55*-170 85*-270 105*-330 135*-425 190*-590 225*-700 300*-925 425*-1330 575*-1800 750*-2350 1800*-5200 Maximum 80-225 120-350 150-500 190-650 265-900 315-1050 415-1400 600-2000 810-3000 1100-4000 2600-8000 MINIMUM 45*-225 65*-350 80*-500 105*-650 145*-900 175*-1050 230*-1400 325*-2000 450*-3000 580*-4000 1400*-7500 MAXIMUM 45-225 65-350 80-500 105-650 145-900 175-1050 230-1400 325-2000 450-3000 580-4000 1400-7500 MINIMUM 30*-225 40*-350 45*-500 70*-650 90*-900 120*-1050 145*-1400 190*-2000 300*-3000 385*-4000 720*-7500 MAXIMUM 30-225 40-350 45-500 70-650 90-900 120-1050 145-1400 190-2000 300-3000 385-4000 720-7500 *Factory cfm settings (except zero) will not be made below this range because control accuracy is reduced. On pressure dependent units, minimum cfm is always zero and there is no maximum. PERFORMANCE DATA Note: On controls mounted by Titus but supplied by others (FMA or Factory Mounting Authorization), these values are guidelines only. Controls mounted on an FMA basis are calibrated in the field. M14 single / dual duct terminals PERFORMANCE DATA Size 4 5 6 7 8 9 10 12 14 40 100 125 150 175 200 150 200 250 300 350 300 350 400 450 500 450 500 550 600 650 600 650 700 750 800 800 850 900 950 1000 900 1000 1100 1200 1300 1200 1400 1600 1800 2000 1500 1800 2100 2400 2700 2000 2400 2800 3200 3600 3900 4600 5300 6000 6700 Min ∆Ps 0.02 0.03 0.04 0.06 0.08 0.01 0.02 0.03 0.04 0.06 0.07 0.10 0.13 0.16 0.20 0.07 0.09 0.10 0.12 0.15 0.02 0.02 0.02 0.02 0.03 0.04 0.04 0.05 0.06 0.06 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.02 0.03 0.04 0.05 0.06 0.02 0.02 0.03 0.04 0.05 0.03 0.04 0.06 0.07 0.09 2 49 52 55 58 60 49 53 55 58 60 55 57 58 59 59 59 60 60 61 62 59 60 60 61 62 58 58 59 59 60 60 60 61 62 63 58 60 61 61 62 56 58 59 60 62 55 57 59 61 62 70 73 75 77 79 3 45 49 52 55 57 44 48 52 54 56 49 52 53 55 56 48 50 51 53 54 50 51 52 53 54 47 48 49 50 50 50 51 52 53 54 50 52 53 55 56 51 53 54 55 56 48 51 53 55 56 65 68 71 73 75 0.5” ∆Ps 4 5 6 36 33 31 39 36 32 41 37 34 42 39 35 44 40 36 36 32 31 39 35 34 41 37 35 43 39 37 45 40 38 40 35 32 42 37 34 44 39 35 45 40 36 47 42 37 42 38 33 43 39 34 44 40 35 45 42 35 46 43 36 44 40 38 44 41 39 45 42 40 46 43 40 47 43 41 43 36 34 43 37 34 44 37 35 44 37 35 44 38 36 47 45 42 48 46 43 48 47 44 48 47 45 49 48 45 47 41 37 48 42 38 50 43 40 51 44 41 52 45 43 45 43 40 46 44 41 47 45 42 48 46 43 49 47 44 43 41 39 45 43 41 46 44 42 48 46 44 49 47 45 63 59 57 66 62 59 68 64 61 71 66 63 72 67 64 7 26 27 28 29 30 25 27 29 30 31 28 29 30 31 32 24 24 25 25 26 32 32 33 34 34 30 31 31 31 31 29 30 32 32 33 30 32 34 35 36 36 36 37 38 38 31 33 34 36 37 54 55 56 57 58 NC 11 16 20 23 25 10 15 20 22 24 16 20 21 23 24 20 22 22 23 24 20 22 22 23 24 19 19 20 20 22 22 22 23 24 25 20 22 24 25 26 18 21 22 23 24 36 18 21 23 24 38 41 43 47 48 2 52 55 58 61 63 53 56 59 62 63 59 60 61 62 63 61 62 63 63 64 62 63 63 64 65 61 61 62 62 63 63 64 65 65 66 62 63 64 65 66 60 62 63 64 66 59 61 63 65 66 72 75 78 80 82 3 48 52 55 58 60 49 53 56 59 61 54 57 58 60 61 54 55 57 58 59 55 56 57 58 59 53 54 55 56 56 57 58 58 59 60 56 57 59 60 61 56 58 59 60 61 53 56 58 60 61 68 71 73 75 77 Octave Band Sound Power, Lw 1.0” ∆Ps 1.5” ∆Ps 4 5 6 7 NC 2 3 4 5 6 39 36 35 31 15 53 50 41 37 37 42 38 36 32 20 57 54 44 40 39 44 40 38 34 23 60 57 46 41 40 46 42 39 34 27 63 59 48 43 41 47 43 40 35 29 65 62 49 44 42 41 36 35 30 16 55 51 43 38 37 44 38 37 32 21 59 55 46 40 40 46 40 39 34 24 62 59 49 42 41 48 42 41 35 28 64 61 50 44 43 49 43 42 36 30 66 63 52 45 44 45 39 37 33 22 61 57 48 41 39 47 41 38 34 25 62 59 50 43 40 49 42 39 35 27 63 61 52 44 42 50 44 40 36 29 64 63 53 46 43 51 45 41 37 30 65 64 54 47 44 48 42 38 30 23 62 57 51 45 41 49 43 39 30 24 63 58 52 46 42 50 45 40 31 25 64 59 53 47 43 51 46 41 31 27 65 61 54 48 44 52 47 41 32 28 65 62 55 49 44 49 43 43 39 24 64 58 52 46 45 50 44 44 40 25 65 59 53 47 46 50 45 44 41 25 65 60 53 47 47 51 46 45 41 27 66 61 54 48 48 52 47 46 42 28 66 62 55 49 48 49 42 40 35 23 62 57 52 46 44 49 43 41 35 23 63 58 53 46 45 50 43 41 35 24 64 58 53 47 45 50 43 42 36 24 64 59 54 47 45 50 44 42 36 25 65 60 54 47 46 53 50 48 37 27 65 60 57 53 52 54 51 49 38 28 66 61 57 54 53 54 52 50 39 28 67 62 57 55 54 54 53 51 40 28 67 63 58 56 55 55 53 52 41 29 68 63 58 56 55 52 47 43 37 26 64 59 56 50 46 54 48 45 39 28 65 60 57 52 48 55 49 46 40 29 66 62 59 53 50 56 50 48 41 30 67 63 60 54 51 57 51 49 43 31 68 64 61 55 52 50 48 45 41 24 62 59 53 51 48 51 49 46 42 27 64 60 54 52 49 52 50 47 43 28 66 62 55 53 50 53 51 48 43 29 67 63 56 54 51 54 52 49 44 30 68 64 57 55 52 47 45 44 38 21 61 56 50 47 47 49 47 46 39 24 64 59 52 49 49 51 48 47 41 27 66 61 54 50 50 52 50 49 42 29 67 62 55 52 52 54 51 50 44 30 69 64 56 53 53 66 62 61 58 41 74 69 67 63 63 68 64 63 60 43 77 72 70 66 65 71 66 65 61 47 79 74 72 68 67 73 68 66 62 49 81 76 74 70 68 75 70 68 63 51 83 78 76 71 70 • Radiated sound is the noise transmitted through the unit casing • Min ∆Ps is the static pressure drop from the unit inlet to the unit outlet with primary damper full open • Sound power levels are in dB, ref 10-12 watts • Sound performance based on units lined with standard dual density fiberglass lining 7 34 36 37 38 38 33 35 37 38 39 36 37 38 39 40 33 34 34 35 35 44 45 45 46 47 38 38 38 38 39 41 42 43 44 45 41 42 44 45 47 45 45 46 47 47 41 43 45 46 48 61 63 64 65 66 NC 17 22 25 28 31 18 23 28 30 33 25 28 30 33 34 25 27 28 30 31 27 28 29 30 31 26 27 27 28 29 31 31 31 33 33 30 31 34 35 36 28 29 31 33 34 24 28 30 31 34 42 46 48 50 52 2 55 58 61 64 66 57 60 63 65 67 63 64 65 66 67 63 64 66 66 66 65 66 67 67 68 63 64 65 65 66 67 67 68 69 69 66 67 68 69 69 64 66 67 69 70 63 65 67 69 71 75 78 80 82 84 3 51 55 58 61 63 53 57 61 63 65 59 62 63 65 67 59 60 62 63 64 60 61 62 63 64 59 60 61 62 62 63 64 64 65 66 61 63 64 65 67 61 63 64 65 66 58 61 63 64 66 70 73 75 77 79 2.0” ∆Ps 4 5 6 43 38 39 45 41 40 47 42 42 49 44 43 51 45 44 45 39 39 48 42 41 51 44 43 52 45 44 54 47 45 50 42 41 52 44 42 54 46 43 55 47 45 56 49 46 53 46 43 54 48 44 55 49 45 56 50 46 57 51 46 54 47 47 55 48 48 56 49 49 56 50 50 57 51 50 55 48 47 55 49 47 56 49 48 56 49 48 57 50 48 59 56 54 59 56 55 60 57 56 60 58 57 61 58 58 58 53 49 60 54 51 61 55 52 62 56 54 63 57 55 55 53 50 56 54 51 58 55 52 58 56 53 59 57 54 52 49 49 54 51 51 55 52 52 57 53 54 58 55 55 68 64 65 71 67 67 73 69 68 75 71 70 77 72 71 7 36 38 39 40 41 35 37 39 40 41 38 39 40 41 42 35 36 37 37 38 47 48 48 49 50 40 40 40 40 40 44 45 46 47 48 43 45 47 48 49 47 48 49 49 50 44 46 48 49 50 63 64 66 67 68 NC 18 23 27 30 33 21 25 30 33 35 28 31 33 35 37 28 29 31 33 34 29 30 31 33 34 29 29 30 31 31 34 34 35 35 36 32 35 36 37 38 30 33 34 35 36 27 30 33 34 36 43 47 49 51 53 • All performance based on tests conducted in accordance with ASHRAE 130-2008 and AHRI 880-2011 • All NC levels determined using AHRI 885-2008 Appendix E. See Terminal Unit Engineering Guidelines. • Dash (-) in space denotes NC value less than NC10 • Only highlighted data points are AHRI certified. See page M23 for AHRI Certified Performance Listings. M PERFORMANCE DATA 16 CFM Redefine your comfort zone™ | www.titus-hvac.com PESV, AESV, DESV / RADIATED SOUND PERFORMANCE M15 single / dual duct terminals Redefine your comfort zone™ | www.titus-hvac.com PERFORMANCE DATA PESV, AESV, DESV / DISCHARGE SOUND PERFORMANCE Size 4 5 6 7 M 8 9 10 12 PERFORMANCE DATA 14 M16 16 40 CFM 100 125 150 175 200 150 200 250 300 350 300 350 400 450 500 450 500 550 600 650 600 650 700 750 800 800 850 900 950 1000 900 1000 1100 1200 1300 1200 1400 1600 1800 2000 1500 1800 2100 2400 2700 2000 2400 2800 3200 3600 3900 4600 5300 6000 6700 Min ∆Ps 0.02 0.03 0.04 0.06 0.08 0.01 0.02 0.03 0.04 0.06 0.07 0.10 0.13 0.16 0.20 0.07 0.09 0.10 0.12 0.15 0.02 0.02 0.02 0.02 0.03 0.04 0.04 0.05 0.06 0.06 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.02 0.03 0.04 0.05 0.06 0.02 0.02 0.03 0.04 0.05 0.03 0.04 0.06 0.07 0.09 2 70 72 73 75 76 68 71 73 74 76 68 69 71 72 73 71 71 72 72 72 73 74 74 75 75 73 74 74 75 75 75 76 76 77 78 73 74 75 76 76 69 70 71 72 72 68 70 71 73 74 76 77 79 80 81 3 56 60 63 65 67 53 57 60 62 64 60 62 63 65 66 61 62 64 65 66 63 64 65 66 67 61 62 63 63 64 62 63 63 64 65 64 65 66 68 69 57 59 60 61 62 59 62 64 65 67 70 71 73 74 75 0.5” ∆Ps 4 5 6 47 42 40 50 44 42 52 47 44 54 48 45 56 50 46 47 43 41 50 46 43 53 49 45 55 51 47 57 52 48 54 50 45 55 52 47 57 54 48 58 55 49 60 56 50 54 51 47 55 52 48 56 54 49 57 55 49 58 56 50 56 52 48 57 53 48 57 54 49 58 54 49 58 55 50 57 53 49 57 53 49 58 54 50 58 54 50 59 55 50 58 55 50 59 56 50 59 57 51 60 57 52 61 58 52 60 55 53 62 56 54 63 57 55 64 58 55 65 59 56 56 53 50 58 53 50 59 54 51 60 54 51 61 54 51 57 54 52 59 55 53 61 57 55 63 58 56 65 59 57 66 62 61 67 63 63 69 65 64 70 66 65 71 67 67 7 33 35 36 37 38 34 36 38 39 40 39 40 41 42 43 40 40 41 42 43 40 41 41 42 42 43 43 43 44 44 44 44 45 45 46 46 47 48 49 50 44 44 44 44 45 45 46 48 49 50 56 58 60 61 62 NC 28 30 31 34 35 25 29 31 29 31 21 22 25 26 28 25 25 26 26 26 28 29 29 28 28 25 26 26 28 28 28 29 29 30 31 25 26 28 29 29 20 21 22 24 24 19 21 22 25 26 29 30 33 34 35 2 71 73 75 76 77 70 73 75 77 78 72 74 75 76 77 74 74 75 75 75 76 77 77 77 78 76 76 77 78 78 77 78 79 79 80 76 77 78 79 79 72 73 74 75 76 71 73 75 76 77 81 82 84 85 86 3 59 63 65 68 70 58 61 65 67 69 65 67 69 70 72 66 68 69 70 72 69 70 71 72 73 66 67 68 68 69 67 68 69 70 70 69 71 72 73 74 63 65 66 67 68 63 66 68 69 71 75 77 78 79 80 Octave Band Sound Power, Lw 1.0” ∆Ps 1.5” ∆Ps 4 5 6 7 NC 2 3 4 5 6 51 46 47 41 29 72 61 54 49 50 54 49 49 43 31 74 64 57 52 52 57 51 50 44 34 76 67 60 54 54 59 53 51 45 35 77 69 62 56 55 61 55 53 46 36 78 72 63 58 56 52 47 47 42 28 72 60 55 50 51 56 51 49 44 31 75 64 59 53 53 58 53 51 45 34 77 67 61 56 55 60 55 53 46 33 78 70 63 58 56 62 57 54 47 34 80 72 65 60 57 59 54 51 46 26 75 68 62 57 54 61 56 52 47 29 76 70 64 59 55 62 58 53 48 30 78 72 65 60 57 64 59 54 49 31 79 73 67 62 58 65 61 55 50 33 80 75 68 63 59 59 54 51 46 29 75 70 61 56 54 60 56 52 47 29 76 71 63 58 55 61 57 53 48 30 76 73 64 59 56 62 58 54 48 30 77 74 64 60 57 63 59 55 49 32 77 75 65 61 58 60 55 52 47 31 78 72 62 56 55 61 56 53 47 33 78 73 63 57 55 61 56 53 48 33 79 74 64 58 56 62 57 54 48 31 79 75 64 58 56 63 58 54 49 32 79 76 65 59 57 61 57 54 49 29 77 69 63 59 57 61 57 54 50 29 78 70 63 59 57 62 57 55 50 30 79 70 64 59 57 62 58 55 50 31 79 71 64 60 58 62 58 55 50 31 80 72 65 60 58 62 59 55 50 30 78 70 65 61 58 63 60 56 51 31 79 71 66 62 59 64 61 56 51 33 80 72 66 63 60 64 61 57 52 33 81 73 67 64 60 65 62 58 53 34 81 74 68 65 61 64 59 57 52 29 78 72 66 62 60 66 61 59 53 30 79 74 68 63 61 67 62 59 55 31 80 75 69 64 62 68 63 60 56 33 80 76 71 65 63 69 64 61 56 33 81 77 72 66 64 56 59 57 53 24 74 67 56 62 62 58 59 58 53 25 75 68 58 63 62 59 60 58 54 26 76 69 59 63 63 60 60 59 54 28 77 70 60 64 63 61 61 59 54 29 78 71 61 64 63 57 58 56 51 22 73 66 57 61 59 59 60 58 52 25 75 68 59 62 61 61 61 59 54 28 77 70 61 64 62 63 62 60 55 29 78 72 63 65 63 65 63 61 56 30 79 73 65 66 64 66 67 67 62 35 84 78 66 69 70 67 68 68 64 37 85 80 67 71 71 69 69 70 65 39 87 81 69 72 73 70 71 71 67 40 88 82 70 73 74 71 72 72 68 42 89 83 71 74 75 • Discharge sound is the noise emitted from the unit discharge into the downstream ductwork • Min ∆Ps is the static pressure drop from the unit inlet to the unit outlet with primary damper full open • Sound power levels are in dB, ref 10-12 watts • Sound performance based on units lined with standard dual density fiberglass lining 7 46 47 49 50 51 46 48 50 51 52 50 51 52 53 54 49 50 51 52 53 51 51 52 52 53 53 54 54 54 54 54 55 55 56 56 56 57 58 59 60 59 59 59 59 60 54 56 57 59 60 66 67 69 70 71 NC 30 33 35 36 38 30 34 36 34 36 30 31 34 35 36 30 31 33 34 36 34 34 35 34 36 30 31 33 33 34 31 33 34 35 35 31 33 34 36 37 26 28 29 30 31 25 28 30 31 33 39 40 43 44 45 2 73 75 76 78 79 73 76 78 79 81 77 78 79 81 82 77 77 78 78 79 79 79 80 80 81 78 79 80 80 81 79 80 81 82 82 79 80 81 81 82 76 77 78 78 79 74 76 78 79 81 86 88 89 90 91 3 62 65 68 71 73 62 66 69 72 74 70 72 74 76 77 72 74 75 76 77 75 76 77 78 78 71 72 72 73 74 73 74 74 75 76 74 76 77 78 79 69 71 72 73 74 68 70 72 73 75 80 82 83 84 85 2.0” ∆Ps 4 5 6 56 51 53 59 54 55 61 56 57 64 58 58 65 60 59 58 52 53 61 55 55 63 58 57 66 60 59 67 61 60 64 58 56 66 60 58 67 62 59 69 63 60 70 65 61 63 58 56 64 59 57 65 60 58 66 61 59 67 62 59 64 57 57 65 58 57 65 59 58 66 60 58 67 60 59 65 60 59 65 61 59 66 61 59 66 61 60 66 62 60 67 63 61 68 64 61 68 65 62 69 66 63 69 66 63 68 64 62 70 65 63 71 66 64 72 67 65 73 68 66 56 65 65 58 65 65 59 66 66 60 66 66 61 67 66 57 63 61 59 64 62 61 66 64 63 67 65 65 68 66 66 71 72 67 73 74 69 74 75 70 75 76 71 76 77 7 49 51 52 53 54 49 51 53 54 55 53 54 55 56 57 52 53 54 55 55 54 54 55 55 56 56 56 57 57 57 57 57 58 59 59 59 60 61 62 63 62 63 63 63 63 57 58 60 61 62 68 70 71 73 74 NC 31 34 35 38 39 31 35 38 35 38 33 34 35 38 39 33 34 36 37 38 36 37 38 38 38 31 33 34 34 35 33 34 35 36 36 33 36 37 38 39 29 30 31 32 33 26 29 31 33 35 42 44 45 47 48 • All performance based on tests conducted in accordance with ASHRAE 130-2008 and AHRI 880-2011 • All NC levels determined using AHRI 885-2008 Appendix E. See Terminal Unit Engineering Guidelines. • Dash (-) in space denotes NC value less than NC10 • Only highlighted data points are AHRI certified. See page M23 for AHRI Certified Performance Listings. single / dual duct terminals PERFORMANCE DATA Sizes 4-5-6 Rows One-Row Two-Row Sizes 7-8 Rows One-Row Two-Row Sizes 9-10 Rows One-Row Two-Row Rows Size 12 Two-Row 50 3.7 3.8 3.9 3.9 0.01 5.0 5.4 5.4 5.5 0.01 100 5.6 5.9 6.1 6.1 0.01 8.1 9.0 9.2 9.3 0.03 150 6.8 7.3 7.6 7.7 0.02 10.3 11.9 12.2 12.4 0.05 200 7.8 8.5 8.9 9.0 0.04 12.0 14.2 14.7 15.0 0.08 Head gpm Loss 1.0 0.64 2.0 2.46 3.0 5.38 4.0 9.39 Airside DPs 1.0 0.17 3.0 1.40 5.0 3.77 7.0 7.24 Airside DPs 100 6.2 6.6 6.7 6.8 0.01 8.8 9.7 9.9 10.0 0.02 200 8.9 9.7 10.0 10.1 0.02 13.4 15.6 16.2 16.5 0.05 300 10.7 11.8 12.3 12.5 0.05 16.3 20.0 21.0 21.4 0.10 400 12.1 13.5 14.1 14.4 0.07 18.5 23.4 24.8 25.5 0.16 Head gpm Loss 2.0 0.41 3.0 0.90 5.0 2.41 6.0 3.43 Airside DPs 2.0 0.47 4.0 1.84 6.0 4.08 8.0 5.00 Airside DPs 200 11.0 11.4 11.8 11.9 0.01 16.4 17.6 18.0 18.3 0.03 300 13.5 14.1 14.7 14.9 0.02 21.0 23.0 23.8 24.2 0.05 400 15.4 16.3 17.1 17.3 0.04 24.5 27.3 28.5 29.1 0.09 500 17.0 18.1 19.0 19.3 0.06 27.4 31.0 32.5 33.3 0.12 Head gpm Loss 2.0 0.54 3.0 1.19 5.0 3.18 6.0 4.52 Airside DPs 2.0 0.55 4.0 2.15 6.0 4.75 8.0 6.16 Airside DPs 300 15.5 16.2 16.9 17.0 0.01 23.2 25.3 26.1 26.5 0.03 500 19.8 21.0 22.1 22.4 0.03 30.8 34.8 36.4 37.2 0.07 700 22.9 24.5 26.0 26.5 0.06 36.2 41.9 44.3 45.6 0.13 900 25.2 27.2 29.1 29.7 0.09 40.2 47.6 50.7 52.5 0.20 Airflow, cfm 250 8.6 9.5 10.0 10.1 0.05 13.4 16.2 16.9 17.3 0.12 Airflow, cfm 500 13.1 14.8 15.5 15.9 0.11 20.2 26.3 28.0 28.8 0.23 Airflow, cfm 600 18.3 19.6 20.7 21.0 0.08 29.8 34.2 36.0 37.0 0.17 Airflow, cfm 1100 27.1 29.5 31.7 32.4 0.13 43.5 52.3 56.1 58.3 0.27 Performance notes appear at end of table 300 9.3 10.3 10.9 11.0 0.07 14.5 17.9 18.8 19.2 0.16 350 9.9 11.0 11.7 11.8 0.10 15.5 19.4 20.5 21.0 0.21 400 10.4 11.6 12.4 12.6 0.12 16.3 20.7 22.0 22.6 0.26 450 10.8 12.2 13.1 13.3 0.15 17.0 22.0 23.4 24.1 0.32 600 14.0 16.0 16.8 17.2 0.15 21.5 28.6 30.8 31.8 0.32 700 14.7 16.9 17.9 18.4 0.19 22.6 30.7 33.2 34.4 0.41 800 15.3 17.8 18.8 19.4 0.24 23.6 32.5 35.3 36.7 0.51 900 15.9 18.5 19.7 20.3 0.30 24.4 34.1 37.2 38.8 0.62 700 19.5 20.9 22.2 22.5 0.10 31.8 36.9 39.1 40.3 0.22 800 20.5 22.0 23.5 23.9 0.13 33.6 39.4 41.8 43.2 0.27 900 21.3 23.0 24.6 25.1 0.15 35.1 41.5 44.3 45.9 0.33 1000 22.1 23.9 25.7 26.2 0.19 36.5 43.5 46.6 48.3 0.40 1300 28.7 31.4 34.0 34.7 0.17 46.1 56.3 60.8 63.3 0.36 1500 30.1 33.0 35.9 36.7 0.22 48.3 59.7 64.8 67.8 0.46 1700 31.2 34.5 37.6 38.5 0.27 50.2 62.7 68.4 71.7 0.57 1900 32.3 35.7 39.2 40.1 0.33 51.9 65.4 71.6 75.3 0.68 M PERFORMANCE DATA One-Row Head gpm Loss 1.0 0.48 2.0 1.82 4.0 6.98 5.0 10.75 Airside DPs 1.0 0.12 3.0 1.04 5.0 2.80 7.0 5.38 Airside DPs Redefine your comfort zone™ | www.titus-hvac.com PESV, AESV, DESV / HOT WATER COIL CAPACITY, MBH / 1- AND 2-ROW M17 single / dual duct terminals PESV, AESV, DESV / HOT WATER COIL CAPACITY, MBH / 1- AND 2-ROW Rows One-Row Size 14 Redefine your comfort zone™ | www.titus-hvac.com PERFORMANCE DATA Two-Row Rows Size 16 One-Row M Two-Row Rows Size 24 x 16 One-Row PERFORMANCE DATA Two-Row M18 • • • • • • • • Head gpm Loss 2.0 0.43 3.0 0.96 5.0 2.63 6.0 3.77 Airside DPs 2.0 0.39 4.0 1.51 6.0 3.36 8.0 3.95 Airside DPs 400 20.4 21.6 22.7 23.1 0.01 30.1 33.5 34.9 35.6 0.03 700 26.3 28.4 30.5 31.0 0.03 40.3 47.1 49.9 51.5 0.07 1000 30.3 33.2 36.0 36.8 0.06 47.0 56.8 61.1 63.5 0.12 1300 33.2 36.8 40.3 41.3 0.09 51.8 64.3 69.9 73.1 0.19 Head gpm Loss 3.0 1.07 5.0 2.92 7.0 5.65 9.0 6.48 Airside DPs 3.0 0.53 5.0 1.46 7.0 2.84 9.0 2.54 Airside DPs 600 29.5 31.4 32.4 32.9 0.02 43.1 47.0 49.0 50.2 0.04 1000 37.4 40.6 42.1 43.1 0.04 55.9 63.1 66.8 69.0 0.08 1400 42.8 47.2 49.3 50.6 0.07 64.7 74.6 80.0 83.3 0.14 1800 47.0 52.3 55.0 56.6 0.10 71.1 83.5 90.3 94.6 0.22 Head gpm Loss 3.0 1.31 5.0 3.57 7.0 6.89 9.0 8.50 Airside DPs 3.0 0.59 5.0 1.63 7.0 3.17 9.0 3.06 Airside DPs 600 35.3 37.6 38.7 39.3 0.01 48.8 53.1 55.2 56.4 0.02 1200 49.4 54.2 56.5 58.0 0.02 70.9 81.0 86.2 89.4 0.05 1800 58.3 65.2 68.7 70.8 0.05 84.3 99.4 107.6 112.8 0.10 2400 64.7 73.4 77.9 80.7 0.08 93.4 112.9 123.8 130.8 0.16 All coil performance in accordance with AHRI 410-2001 Heating capacities are in MBH Data based on 180°F entering water and 55°F entering air For temperature differentials other than 125°, multiply MBH by correction factors below Head loss is in feet of water Always supply water to lowest connection pipe to prevent air entrapment Air temperature rise = 927 x MBH/cfm Water temperature drop = 2.04 x MBH/gpm Airflow, cfm 1600 35.5 39.7 43.8 45.0 0.13 55.5 70.3 77.2 81.1 0.27 Airflow, cfm 2200 50.4 56.5 59.7 61.6 0.14 76.1 90.7 98.8 104.1 0.30 Airflow, cfm 3000 69.6 79.9 85.4 88.7 0.11 100.1 123.3 136.6 145.3 0.24 1900 27.4 42.0 47.8 48.2 0.17 58.5 75.3 83.3 88.0 0.36 2200 39.0 44.1 49.3 50.9 0.22 60.9 79.6 88.6 93.9 0.46 2500 40.4 45.9 51.6 53.3 0.27 62.9 83.2 93.2 99.2 0.57 2800 41.5 47.4 53.6 55.4 0.33 64.7 86.4 97.3 103.8 0.69 2600 53.1 60.1 63.7 65.9 0.19 80.1 96.6 106.0 112.1 0.40 3000 55.5 63.1 67.1 69.6 0.24 83.4 101.6 112.1 119.0 0.51 3400 57.5 65.8 70.2 72.9 0.30 86.2 105.9 117.5 125.1 0.63 3800 59.3 68.2 72.9 75.9 0.36 88.6 109.7 122.2 130.5 0.76 3600 73.5 85.3 91.6 95.5 0.15 105.3 131.6 147.1 157.3 0.32 4200 76.8 89.9 96.9 101.3 0.20 109.4 138.5 155.9 167.5 0.42 4800 79.6 93.8 101.5 106.4 0.25 112.8 144.3 163.5 176.4 0.52 5400 82.0 97.3 105.6 110.9 0.30 115.7 149.3 170.0 184.2 0.63 • Connection size is ½” OD male solder for 1-row coil sizes 04-08. All other coils have 7/8” OD male solder. • Coils are not intended for steam applications and are labeled for a maximum water temperature of 200°F • Coils are tested for leakage at test pressure of 500 psi • Water volumes less than those shown may result in laminar flow and reduced heating capacity. If possible reduce the number of coil rows to increase water velocity into turbulent range. Correction Factors for Other Entering Conditions ∆T 50 60 70 80 90 100 110 125 140 150 Factor 0.40 0.48 0.56 0.64 0.72 0.80 0.88 1.00 1.12 1.20 Note: Airside ∆Ps reflects the air pressure drop of the hot water coil single / dual duct terminals PERFORMANCE DATA Sizes 4-5-6 Rows ThreeRow FourRow Sizes 7-8 Rows ThreeRow FourRow Sizes 9-10 Rows ThreeRow FourRow ThreeRow FourRow 50 6.1 6.1 6.2 6.2 0.01 6.5 6.5 6.5 6.5 0.02 100 10.8 11.0 11.1 11.2 0.04 11.9 12.1 12.2 12.2 0.05 150 14.4 14.9 15.2 15.3 0.08 16.5 16.8 17.1 17.2 0.10 200 17.5 18.2 18.8 18.9 0.12 20.5 20.9 21.4 21.6 0.16 Head gpm Loss 2.0 0.50 4.0 1.95 6.0 4.33 8.0 5.42 Airside DPs 4.0 1.40 6.0 3.12 8.0 3.53 10.0 5.46 Airside DPs 100 11.2 11.6 11.7 11.7 0.02 12.4 12.5 12.6 12.6 0.03 200 18.6 19.8 20.2 20.4 0.08 22.1 22.5 22.7 22.9 0.10 300 23.8 26.0 26.9 27.3 0.15 29.6 30.6 31.1 31.4 0.20 400 27.9 31.1 32.3 33.0 0.24 358.0 37.3 38.1 38.6 0.32 Head gpm Loss 3.0 0.80 5.0 2.19 7.0 4.26 9.0 4.49 Airside DPs 4.0 1.16 5.0 1.80 8.0 2.75 10.0 4.25 Airside DPs 200 21.0 21.6 21.9 22.1 0.04 23.5 23.7 24.1 24.2 0.05 300 27.9 29.2 29.8 30.2 0.08 32.2 32.7 33.6 33.9 0.11 400 33.4 35.5 36.5 37.0 0.13 39.4 40.4 41.8 42.3 0.17 500 38.0 40.8 42.2 43.0 0.19 45.6 46.9 49.0 49.8 0.25 Head gpm Loss 3.0 0.91 4.0 1.61 6.0 3.57 8.0 4.32 Airside DPs 4.5 1.63 5.0 2.01 7.0 2.88 9.0 4.11 Airside DPs 300 30.3 31.0 31.8 32.2 0.05 34.6 34.8 35.1 35.6 0.06 500 42.2 44.0 45.9 46.9 0.11 50.5 51.1 52.6 53.4 0.15 700 50.9 53.8 56.9 58.5 0.19 62.9 63.9 66.5 68.0 0.26 900 57.6 61.5 65.8 68.2 0.29 72.7 74.2 78.0 80.3 0.39 Airflow, cfm 250 20.0 21.0 21.8 22.1 0.18 23.9 24.5 25.2 25.5 0.24 Airflow, cfm 500 31.1 35.3 37.0 37.9 0.35 40.9 43.0 44.2 44.9 0.47 Airflow, cfm 600 41.8 45.5 47.2 48.3 0.25 50.9 52.6 55.4 56.4 0.34 Airflow, cfm 1100 63.0 67.8 73.3 76.3 0.41 80.8 82.7 87.7 90.8 0.55 Performance notes appear at end of table 300 22.3 23.5 24.6 24.9 0.24 26.8 27.7 25.6 29.1 0.32 350 24.2 25.7 27.0 27.4 0.31 29.5 30.6 31.7 32.3 0.41 400 25.9 27.6 29.2 29.7 0.39 34.8 33.1 34.5 35.3 0.52 450 27.4 29.4 31.3 31.8 0.47 34.0 35.5 37.1 38.0 0.63 600 33.7 38.8 41.0 42.1 0.47 45.3 48.0 49.5 50.4 0.63 700 35.9 41.9 44.5 45.9 0.61 49.1 52.4 54.2 55.4 0.82 800 37.8 44.7 47.6 49.2 0.77 52.4 56.3 58.4 59.8 1.02 900 39.4 47.1 50.4 52.2 0.93 55.3 59.7 62.2 63.8 1.25 700 45.2 49.6 51.7 53.0 0.33 55.5 57.7 61.2 62.4 0.43 800 48.1 53.2 55.7 57.3 0.41 59.6 62.2 66.4 67.9 0.54 900 50.7 56.5 59.4 61.2 0.50 63.2 66.2 71.1 72.9 0.66 1000 52.9 59.4 62.7 64.7 0.59 66.5 69.8 75.5 77.5 0.79 1300 67.4 73.1 79.7 83.4 0.54 87.6 89.9 96.1 99.9 0.72 1500 71.1 77.6 85.2 89.6 0.69 93.4 96.0 103.4 107.9 0.92 1700 74.3 81.5 90.1 95.1 0.85 98.4 101.4 109.8 115.1 1.13 1900 77.0 84.9 94.5 100.0 1.02 102.8 106.1 115.6 121.5 1.36 M PERFORMANCE DATA Size 12 Rows Head gpm Loss 2.0 0.70 3.0 1.54 5.0 4.14 6.0 5.90 Airside DPs 3.0 1.11 4.0 1.95 6.0 4.33 8.0 5.42 Airside DPs Redefine your comfort zone™ | www.titus-hvac.com PESV, AESV, DESV / HOT WATER COIL CAPACITY, MBH / 3- AND 4-ROW M19 single / dual duct terminals PESV, AESV, DESV / HOT WATER COIL CAPACITY, MBH / 3- AND 4-ROW Rows Size 14 ThreeRow FourRow Rows ThreeRow Size 16 Redefine your comfort zone™ | www.titus-hvac.com PERFORMANCE DATA M FourRow Rows Size 24 x 16 ThreeRow PERFORMANCE DATA FourRow M20 • • • • • • • • Head gpm Loss 4.0 1.30 5.0 2.01 6.0 2.88 8.0 3.27 Airside DPs 6.0 2.06 7.0 2.79 8.0 2.03 10.0 3.15 Airside DPs 400 41.3 42.1 42.6 43.3 0.04 46.7 47.1 47.4 47.8 0.05 700 59.8 61.8 63.2 65.0 0.10 71.1 72.2 73.1 74.4 0.14 1000 73.0 76.3 78.6 81.7 0.19 89.5 91.6 93.3 95.6 0.25 1300 83.0 87.6 90.8 95.2 0.29 104.0 107.1 109.5 113.0 0.38 Head gpm Loss 6.0 1.71 8.0 1.51 10.0 2.35 12.0 3.36 Airside DPs 9.0 1.58 10.0 1.95 11.0 2.36 12.0 2.80 Airside DPs 600 58.5 60.1 61.1 61.8 0.06 67.4 67.9 68.3 68.6 0.08 1000 80.9 84.4 86.7 88.2 0.14 97.6 98.8 99.7 100.5 0.18 1400 97.0 102.5 106.1 108.6 0.24 120.6 122.6 124.2 125.6 0.32 1800 109.3 116.7 121.6 125.1 0.37 138.8 141.6 144.0 146.0 0.49 Head gpm Loss 6.0 1.86 8.0 1.76 10.0 2.74 12.0 3.92 Airside DPs 9.0 1.80 10.0 2.22 11.0 2.68 12.0 3.18 Airside DPs 600 65.0 66.4 67.2 67.8 0.03 72.6 73.0 73.3 73.5 0.04 1200 103.8 108.6 111.5 113.6 0.09 124.0 125.5 126.7 127.7 0.12 1800 129.6 138.0 143.4 147.2 0.17 161.1 164.1 166.5 168.6 0.23 2400 148.2 160.0 167.9 173.4 0.27 189.2 193.6 197.3 200.5 0.37 All coil performance in accordance with AHRI 410-2001 Heating capacities are in MBH Data based on 180°F entering water and 55°F entering air For temperature differentials other than 125°, multiply MBH by correction factors below Head loss is in feet of water Always supply water to lowest connection pipe to prevent air entrapment Air temperature rise = 927 x MBH/cfm Water temperature drop = 2.04 x MBH/gpm Airflow, cfm 1600 90.9 96.6 100.7 106.3 0.41 115.7 119.8 123.0 127.7 0.54 Airflow, cfm 2200 119.2 128.3 134.4 138.8 0.51 153.7 157.3 160.3 162.9 0.68 Airflow, cfm 3000 162.3 177.3 187.4 194.7 0.40 211.2 217.1 222.0 226.3 0.53 1900 97.3 104.1 109.0 115.8 0.54 125.5 130.4 134.4 140.2 0.72 2200 102.7 110.4 116.1 124.0 0.69 133.7 139.5 144.1 151.1 0.93 2500 107.3 115.8 122.2 131.2 0.86 140.8 147.4 152.7 160.7 1.15 2800 111.1 120.5 127.6 137.5 1.04 146.9 154.2 160.2 169.2 1.39 2600 127.3 138.0 145.3 150.5 0.68 166.2 170.5 174.1 177.3 0.90 3000 134.0 146.2 154.6 160.7 0.86 176.8 181.8 186.0 189.8 1.15 3400 139.9 153.4 162.7 169.6 1.06 185.9 191.6 196.4 200.7 1.42 3800 144.9 159.6 169.9 177.5 1.28 193.9 200.2 205.6 210.3 1.71 3600 173.5 191.2 203.4 212.3 0.54 229.0 236.2 242.3 247.6 0.72 4200 182.5 202.8 216.9 227.3 0.70 243.6 252.1 259.3 265.6 0.93 4800 190.1 212.6 228.5 240.3 0.88 256.0 265.6 273.9 281.1 1.17 5400 196.5 221.1 238.6 251.6 1.07 266.7 277.2 286.4 294.5 1.42 • Connection size is ½” OD male solder for 1-row coil sizes 04-08. All other coils have 7/8” OD male solder. • Coils are not intended for steam applications and are labeled for a maximum water temperature of 200°F • Coils are tested for leakage at test pressure of 500 psi • Water volumes less than those shown may result in laminar flow and reduced heating capacity. If possible reduce the number of coil rows to increase water velocity into turbulent range. Correction Factors for Other Entering Conditions ∆T 50 60 70 80 90 100 110 125 140 150 Factor 0.40 0.48 0.56 0.64 0.72 0.80 0.88 1.00 1.12 1.20 Note: Airside ∆Ps reflects the air pressure drop of the hot water coil single / dual duct terminals ELECTRIC COILS Recommended Coil Selection Data The table at the right describes the maximum recommended kW capacities and number of stages available for Titus single duct terminals. To make a coil selection: 1.Check the desired kW is available in desired unit size and number of stages. (Required to prevent excessive watt density and current draw, while taking into account unit size limitations.) 2.Check the desired minimum airflow limit is within recommended operating range. (Ensures velocity pressure will be sufficient to close airflow sensing switch.) 3.Multiply desired minimum airflow limit by a factor of 0.0142 and check the result is equal to or greater than desired kW. (Limits temperature rise across the coil to 45°F.) kW ≤ cfm x 0.0142 Titus electric heating coils are specifically designed for use with VAV terminal units. They include an extended plenum section and diffuser plate to minimize stratification. The heating elements are designed to minimize hot spots and nuisance tripping of the thermal cutouts. must be within recommended ranges to ensure proper operation and long service life. For optimum diffuser performance and maximum thermal comfort, coil discharge temperatures should not be more than 15°F above desired room temperatures. For proper coil operation it is recommended that coil discharge temperatures do not to exceed 100°F. These requirements established to prevent excessive temperature rise caused by low airflow and/or oversized coils. Minimum airflow limits M PESV, AESV, DESV / APPLICATION DATA (STAGED HEAT) Inlet Size Heating cfm Range 55-225 5 85-350 6 105-500 7 135-650 8 190-900 9 225-1050 10 300-1400 12 425-2000 14 575-3000 16 750-4000 24x16 1800-8000 Min 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 0.5 1.0 1.5 0.5 1.0 1.5 0.5 1.0 1.5 0.5 1.0 1.5 0.5 1.0 1.5 0.5 1.0 1.5 0.5 1.0 1.5 0.5 1.0 1.5 1.0 2.0 3.0 1.0 2.0 3.0 1.0 2.0 3.0 Max 3.0 5.0 7.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 9.5 240V 1 Phase kW Range Min 1.0 1.5 2.0 1.0 1.5 2.0 1.0 1.5 2.0 1.0 1.5 2.0 1.0 1.5 2.0 1.0 1.5 2.0 1.0 1.5 2.0 1.0 1.5 2.0 1.0 2.0 3.0 1.0 2.0 3.0 1.0 2.0 3.0 Max 3.0 5.0 7.5 9.5 11.0 11.0 11.0 11.0 11.0 11.0 11.0 277V 1 Phase kW Range Min 1.0 1.5 2.5 1.0 1.5 2.5 1.0 1.5 2.5 1.0 1.5 2.5 1.0 1.5 2.5 1.0 1.5 2.5 1.0 1.5 2.5 1.0 1.5 2.5 1.5 2.0 3.0 1.5 2.0 3.0 1.5 3.0 4.5 208V 3 Phase kW Range 480V 3 Phase kW Range Max Min Max Min Max 3.0 1.5 3.0 2.5 3.0 5.0 1.5 5.0 2.5 5.0 7.5 1.5 7.5 2.5 7.5 9.5 1.5 9.5 2.5 9.5 13.0 1.5 13.0 2.5 13.0 13.0 1.5 16.0 2.5 16.0 13.0 1.5 16.0 2.5 21.0 13.0 1.5 16.0 2.5 30.0 16.0 3.0 36.0 16.0 3.0 36.0 16.0 4.0 36.0 13.0 13.0 13.0 1.5 2.0 3.0 1.5 2.0 3.0 1.5 2.0 3.0 Note: The Titus 480V, 3-phase electric heat configuration is 4-wire wye. Contact your Titus representative for other configuration options. ELECTRIC COILS 4 208V 1 Phase kW Range Number of Steps Available Redefine your comfort zone™ | www.titus-hvac.com SELECTION AND CAPACITIES Useful formulas: kW= cfm x ∆T 3160 Where ∆T = air temperature rise. or ∆T= kW x 3160 cfm or cfm = kW x 3160 ∆T M21 single / dual duct terminals Redefine your comfort zone™ | www.titus-hvac.com ELECTRIC COILS ELECTRIC COILS M M22 PESV, AESV, DESV / APPLICATION DATA (LYNERGY HEAT) Inlet Size Heating cfm Range 208V 1 Phase kW Range 240V 1 Phase kW Range 277V 1 Phase kW Range 208V 3 Phase kW Range 480V 3 Phase kW Range Min Max Min Max Min Max Min Max Min Max 4 55-225 0.5 3.0 1.0 3.0 1.0 3.0 1.5 3.0 2.5 3.0 5 85-350 0.5 5.0 1.0 5.0 1.0 5.0 1.5 5.0 2.5 5.0 6 105-500 0.5 7.5 1.0 7.5 1.0 7.5 1.5 7.5 2.5 7.5 7 135-650 0.5 9.5 1.0 9.5 1.0 9.5 1.5 9.5 2.5 9.5 8 190-900 0.5 9.5 1.0 11.0 1.0 13.0 1.5 10.5 2.5 13.0 9 225-1050 0.5 9.5 1.0 11.0 1.0 13.0 1.5 10.5 2.5 16.0 10 300-1400 0.5 9.5 1.0 11.0 1.0 13.0 1.5 10.5 2.5 21.0 12 425-2000 0.5 9.5 1.0 11.0 1.0 13.0 1.5 10.5 2.5 25.0 14 575-3000 1.0 9.5 1.0 11.0 1.5 13.0 1.5 10.5 3.0 25.0 16 750-4000 1.0 9.5 1.0 11.0 1.5 13.0 1.5 10.5 3.0 25.0 24x16 1800-8000 1.0 9.5 1.0 11.0 1.5 13.0 1.5 10.5 4.0 25.0 single / dual duct terminals PERFORMANCE DATA Titus is a charter member company and current partici- PESV, AESV, DESV pant in the AHRI Directory of Certified Performance. This Inlet Rated Min voluntary certification program was developed by parSize CFM ∆Ps ticipating manufacturers in conjunction with the former Air-Conditioning and Refrigeration Institute (ARI) in the 04 150 0.04 1990’s. It is currently administrated by the Air-Condi05 250 0.03 tioning, Heating, and Refrigeration Institute (AHRI). The 06 400 0.13 purpose of this program is to provide for the independent verification of manufacturers’ published performance 07 550 0.10 data. Only participating products are authorized to bear 08 700 0.02 the AHRI VAV Certification Mark. Certified data may be 09 900 0.05 viewed and downloaded at www.ahrinet.org. In order to participate in this program, member companies pay annual dues based on sales volume, submit published performance data for all applicable model types, and agree to provide a number of randomly selected product samples for annual rounds of independent testing at the manufacturers’ expense. All verification testing is conducted in accordance with ASHRAE Standard 130 ‘Methods of Testing Air Terminal Units’. These tests are conducted to verify that a manufacturer’s published certified ratings are within the test tolerances outlined in AHRI Standard 880 ‘Performance Rating of Air Terminals’. Any failure to demonstrate the certified performance is punished by additional testing requirements, mandatory performance re-rating, monetary penalties and possible expulsion from the Certified Directory. Discharge Radiated Sound Power Discharge Sound Power H W 2 2 8 12 60 57 46 41 40 37 76 67 60 54 54 49 8 12 62 59 49 42 41 37 77 67 61 56 55 50 8 12 63 61 52 44 42 38 78 72 65 60 57 52 10 12 64 59 53 47 43 34 76 73 64 59 56 51 3 4 5 6 7 3 4 5 6 7 10 12 65 60 53 47 47 45 79 74 64 58 56 52 12.5 14 64 58 53 47 45 38 79 70 64 59 57 54 10 1100 0.01 12.5 14 67 62 57 55 54 43 80 72 66 63 60 55 12 1600 0.01 15 16 66 62 59 53 50 44 80 75 68 64 62 58 14 2100 0.04 17.5 20 66 62 55 53 50 46 76 69 66 63 63 59 16 2800 0.03 18 24 66 61 54 50 50 45 77 70 66 64 62 57 40 5300 0.06 18 38 79 74 72 68 67 64 87 81 77 72 73 69 Redefine your comfort zone™ | www.titus-hvac.com AHRI Directory Of Certified Performance M Product samples provided for certification testing are standard production units with standard ½” dual density fiberglass lining (unless otherwise specified) and no optional appurtenances such as add-on attenuators or heating/cooling coils. The certified ratings are measured at the standard operating points under the following test conditions: PESV, EESV, AESV, DESV PERFORMANCE DATA • Rated airflow (cfm) – Based on an inlet velocity of 2000 fpm • Rated Min ∆Ps (in wg) – Minimum static pressure drop from the unit inlet to discharge at rated airflow with damper full open • Rated ∆Ps (in wg) – A static pressure drop of 1.5 in wg from unit inlet to discharge • Rated sound power by octave band (dB, re 10-12 watts) – Radiated and discharge sound performance conducted in a reverberation room that meets both the broadband and pure tone qualifications of AHRI Standard 220 M23 single / dual duct terminals Redefine your comfort zone™ | www.titus-hvac.com Dual Duct Design Features TITUS DUAL DUCT TERMINAL - LEADERSHIP IN A RE-EMERGING TECHNOLOGY! The concern for IAQ has led to renewed interest in the benefits of dual duct systems. Dual duct systems are an ideal vehicle for alternative ventilation strategies and humidity control. Additionally, total filtration of all air delivered to the zone is possible. Titus dual duct terminals provide high performance and value, making them the preferred selection for these applications. Titus dual duct terminals vary the airflow individually between hot and cold inlets for highly accurate temperature control. As the ratio of hot and cold air is critical in most applications, pressure independent controls are used with a separate velocity control loop to each inlet. Titus dual duct terminals are available in three styles. In those instances where no blending of airstreams is required, the EDV without the integral attenuator assembly can be an effective choice. When blending of hot and cold supply air is needed for accurate temperature control with minimum flow requirements, the EDV or EDC with integral attenuator should be used. The attenuator reduces discharge sound levels and provides some mixing benefit. An optional mixing baffle is available for use with the attenuator to provide maximum blending of hot and cold airstreams. Less than 1°F temperature variation is provided at the discharge with a 10°F inlet temperature differential! M EDV NON MIXING EDV WITH OPTIONAL MIXING BAFFLE MDV WITH INTEGRAL MIXING ATTENUATOR All Titus dual duct terminals are available with Fibre-Free and other lining options. DESIGN FEATURES The Titus MDV/MDC Dual Duct Terminals have been specially designed for those applications where comfort levels are critical, as in hospitals, research facilities, and other institutional applications. M24 Like the EDV/EDC, the MDV/MDC terminals use separate pressure independent velocity control loops for each inlet, rather than a single velocity controller for discharge volume control only. This provides superior temperature control during blending, as each inlet can compensate for duct pressure changes without affecting the other. The unique internal mixing baffle design provides for exceptional mixing characteristics. Less than 1°F temperature variation is provided at the discharge with a 20°F inlet temperature differential. Additional ductwork is not required downstream to achieve proper mixing, allowing for immediate take-off to diffusers. This is also beneficial for installations with space limitations. The tightly sealed casing typically allows less than 1 percent leakage of conditioned air to the space at 1.5 inches wg. differential static pressure, making this one of the most energy efficient dual duct terminals. The dampers are the improved Titus low leakage design. All Titus dual duct terminals are also available with EcoShield, Fibre Free and SteriLoc lining options. Specify the MDV/MDC and you will be providing the best performing dual duct terminal available. DUAL DUCT CONTROL STRATEGIES single / dual duct terminals Pneumatic: O20 / Digital: O6 / Model: EDV Max HTG cfm Increase As this is a non-blending application, a mixer/attenuator section is not required. For detailed information on specific control types, refer to the following pages in Section O: Max CLG* Room Temperature Increase Pneumatic: O20 / Digital: O6 / Model: EDV or MDV Max CLG cfm Increase VAV, Minimum Mix Equal to Maximum HTG - blending In cooling mode, as temperature approaches setpoint, cold air modulates from maximum to a minimum mix flow rate. As temperature continues to drop, hot airflow modulates open as cold airflow closes, maintaining a minimum total flow rate. Lower heating flow rates require unequal inlet sizes to maintain control. A mixer/attenuator section is required. Max HTG M Room Temperature Increase VAV, Minimum Mix, Unequal Maximum Flows - blending Similar in cooling mode to the sequence above, when entering the heating mode a flow rate higher than the minimum mix is employed. Maximum flow rates may be close enough that equal inlet sizes may be used. A mixer/attenuator section is required. Max HTG Max CLG cfm Increase Pneumatic: O20 / Digital: O6 / Model: EDV or MDV Redefine your comfort zone™ | www.titus-hvac.com VAV, Zero Minimum - non-blending In cooling mode, as temperature approaches setpoint, cold airflow modulates from maximum to zero flow. As room temperature drops below setpoint, hot airflow modulates from zero to maximum. Heating and cooling maximum flow rates can be different. A deadband may be utilized. Room Temperature Increase Constant Volume Discharge - blending In this sequence cooling and heating maximum flow rates are the same and minimum mix flow rates are the same as maximums. The result is a constant airflow over the entire cooling and heating range. A mixer/attenuator section is required. cfm Increase Max CLG Room Temperature Increase Optional Censor Location Configuration For blending applications with integral mixer/attenuator. Multi-point velocity sensors are available in four different configurations to match any application and control requirement. Configurations 3B and 3C are to match hot or cold inlet control requirements. 3A Discharge 3B Pneumatic: O20 / Digital: O6 3C CONTROL STRATEGIES Pneumatic: O20 / Digital: O6 / Model: EDC or MDC Max HTG 3D Inlet = Sensor Location M25 Redefine your comfort zone™ | www.titus-hvac.com Dual Duct without Attentuator single / dual duct terminals EDV • Standard AeroCrossTM multi-point center averaging velocity sensors in each inlet for accurate flow control • Standard matte faced insulation for maximum thermal and acoustic performance • Mechanically sealed and gasketed, leak resistant construction • Choice of right or left hand cold duct location; right hand is standard • Standard 22 gauge casing with slip and drive discharge connection • Controls supplied by Titus are factory calibrated for quicker start-up EDV M AVAILABLE MODELS: PEDV / Pneumatic DEDV / Digital Electronic OVERVIEW For Non-Blending Applications Only Titus Dual Duct terminals vary the airflow individually between hot and cold inlets for highly accurate temperature control. Dual duct systems are an ideal vehicle for alternative ventilation strategies and humidity control. Additionally, total filtration of all air delivered to the zone is possible. Titus dual duct terminals provide high performance and value, making them the preferred selection for these applications. ADDITIONAL FEATURES EDV • Direct digital control package supplied by Titus includes: direct digital controller, damper actuators and flow tranducers • Dual density insulation, coated to prevent air erosion, meet requirements of NFPA 90A and UL 181 M26 See website for Specifications single / dual duct terminals DIMENSIONS PEDV - Basic Unit with Controls W 4½” M 4½” L Pneumatic Actuator D H Discharge F A Control Cover (optional) M DEDV - Basic Unit with Controls L M W F Redefine your comfort zone™ | www.titus-hvac.com EDV UNIT DIMENSIONS G 12¼” D H Discharge A F Inlet Size cfm Range 0-225 0-350 0-500 0-650 0-900 0-1050 0-1400 0-2000 0-3000 0-4000 D 121/8 121/8 121/8 121/8 121/8 141/8 141/8 161/8 201/8 241/8 37/8 47/8 57/8 67/8 77/8 87/8 97/8 117/8 137/8 157/8 6½” F PEDV 17/8 17/8 17/8 7 /8 7 /8 - DEDV 21/8 21/8 21/8 11/8 11/8 - Slip & Drive Cleat Connection G H L M W 73/8 73/8 73/8 73/8 73/8 53/8 53/8 53/8 33/8 33/8 8 8 8 10 10 12½ 12½ 15 17½ 18 15½ 15½ 15½ 15½ 15½ 15½ 15½ 15½ 15½ 15½ 53/8 53/8 33/8 33/8 33/8 33/8 33/8 33/8 33/8 33/8 241/8 241/8 241/8 241/8 241/8 281/8 281/8 321/8 401/8 481/8 All dimensions are in inches DIMENSIONS 4 5 6 7 8 9 10 12 14 16 A 18” Control Enclosure M27 single / dual duct terminals Redefine your comfort zone™ | www.titus-hvac.com PERFORMANCE DATA PEDV, DEDV WITHOUT ATTENUATOR - RADIATED SOUND PERFORMANCE Size 4 5 6 7 M 8 9 10 12 PERFORMANCE DATA 14 M28 16 CFM 100 125 150 175 200 150 200 250 300 350 300 350 400 450 500 450 500 550 600 650 600 650 700 750 800 800 850 900 950 1000 900 1000 1100 1200 1300 1200 1400 1600 1800 2000 1500 1800 2100 2400 2700 2000 2400 2800 3200 3600 Min ∆Ps 0.02 0.03 0.04 0.06 0.08 0.01 0.02 0.03 0.04 0.06 0.07 0.10 0.13 0.16 0.20 0.07 0.09 0.10 0.12 0.15 0.02 0.02 0.02 0.02 0.03 0.04 0.04 0.05 0.06 0.06 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.02 0.03 0.04 0.05 0.06 0.02 0.02 0.03 0.04 0.05 2 52 55 58 61 63 53 56 59 62 63 59 60 61 62 63 61 62 63 63 64 62 63 63 64 65 61 61 62 62 63 63 64 65 65 66 62 63 64 65 66 60 62 63 64 66 59 61 63 65 66 3 48 52 55 58 60 49 53 56 59 61 54 57 58 60 61 54 55 57 58 59 55 56 57 58 59 53 54 55 56 56 57 58 58 59 60 56 57 59 60 61 56 58 59 60 61 53 56 58 60 61 1.0” ∆Ps 4 5 6 39 36 35 42 38 36 44 40 38 46 42 39 47 43 40 41 36 35 44 38 37 46 40 39 48 42 41 49 43 42 45 39 37 47 41 38 49 42 39 50 44 40 51 45 41 48 42 38 49 43 39 50 45 40 51 46 41 52 47 41 49 43 43 50 44 44 50 45 44 51 46 45 52 47 46 49 42 40 49 43 41 50 43 41 50 43 42 50 44 42 53 50 48 54 51 49 54 52 50 54 53 51 55 53 52 52 47 43 54 48 45 55 49 46 56 50 48 57 51 49 50 48 45 51 49 46 52 50 47 53 51 48 54 52 49 47 45 44 49 47 46 51 48 47 52 50 49 54 51 50 7 31 32 34 34 35 30 32 34 35 36 33 34 35 36 37 30 30 31 31 32 39 40 41 41 42 35 35 35 36 36 37 38 39 40 41 37 39 40 41 43 41 42 43 43 44 38 39 41 42 44 NC 15 20 23 27 29 16 21 24 28 30 22 25 27 29 30 23 24 25 27 28 24 25 25 27 28 23 23 24 24 25 27 28 28 28 29 26 28 29 30 31 24 27 28 29 30 21 24 27 29 30 Octave Band Sound Power, Lw 1.5” ∆Ps 2 3 4 5 6 7 53 50 41 37 37 34 57 54 44 40 39 36 60 57 46 41 40 37 63 59 48 43 41 38 65 62 49 44 42 38 55 51 43 38 37 33 59 55 46 40 40 35 62 59 49 42 41 37 64 61 50 44 43 38 66 63 52 45 44 39 61 57 48 41 39 36 62 59 50 43 40 37 63 61 52 44 42 38 64 63 53 46 43 39 65 64 54 47 44 40 62 57 51 45 41 33 63 58 52 46 42 34 64 59 53 47 43 34 65 61 54 48 44 35 65 62 55 49 44 35 64 58 52 46 45 44 65 59 53 47 46 45 65 60 53 47 47 45 66 61 54 48 48 46 66 62 55 49 48 47 62 57 52 46 44 38 63 58 53 46 45 38 64 58 53 47 45 38 64 59 54 47 45 38 65 60 54 47 46 39 65 60 57 53 52 41 66 61 57 54 53 42 67 62 57 55 54 43 67 63 58 56 55 44 68 63 58 56 55 45 64 59 56 50 46 41 65 60 57 52 48 42 66 62 59 53 50 44 67 63 60 54 51 45 68 64 61 55 52 47 62 59 53 51 48 45 64 60 54 52 49 45 66 62 55 53 50 46 67 63 56 54 51 47 68 64 57 55 52 47 61 56 50 47 47 41 64 59 52 49 49 43 66 61 54 50 50 45 67 62 55 52 52 46 69 64 56 53 53 48 • Radiated sound is the noise transmitted through the unit casing • Min ∆Ps is the static pressure drop from the unit inlet to the unit outlet with the cold damper full open • Sound power levels are in dB, ref 10-12 watts • Sound performance based on units lined with standard dual density fiberglass lining NC 17 22 25 28 31 18 23 28 30 33 25 28 30 33 34 25 27 28 30 31 27 28 29 30 31 26 27 27 28 29 31 31 31 33 33 30 31 34 35 36 28 29 31 33 34 24 28 30 31 34 2 55 58 61 64 66 57 60 63 65 67 63 64 65 66 67 63 64 66 66 66 65 66 67 67 68 63 64 65 65 66 67 67 68 69 69 66 67 68 69 69 64 66 67 69 70 63 65 67 69 71 3 51 55 58 61 63 53 57 61 63 65 59 62 63 65 67 59 60 62 63 64 60 61 62 63 64 59 60 61 62 62 63 64 64 65 66 61 63 64 65 67 61 63 64 65 66 58 61 63 64 66 4 43 45 47 49 51 45 48 51 52 54 50 52 54 55 56 53 54 55 56 57 54 55 56 56 57 55 55 56 56 57 59 59 60 60 61 58 60 61 62 63 55 56 58 58 59 52 54 55 57 58 2.0” ∆Ps 5 6 38 39 41 40 42 42 44 43 45 44 39 39 42 41 44 43 45 44 47 45 42 41 44 42 46 43 47 45 49 46 46 43 48 44 49 45 50 46 51 46 47 47 48 48 49 49 50 50 51 50 48 47 49 47 49 48 49 48 50 48 56 54 56 55 57 56 58 57 58 58 53 49 54 51 55 52 56 54 57 55 53 50 54 51 55 52 56 53 57 54 49 49 51 51 52 52 53 54 55 55 7 36 38 39 40 41 35 37 39 40 41 38 39 40 41 42 35 36 37 37 38 47 48 48 49 50 40 40 40 40 40 44 45 46 47 48 43 45 47 48 49 47 48 49 49 50 44 46 48 49 50 NC 18 23 27 30 33 21 25 30 33 35 28 31 33 35 37 28 29 31 33 34 29 30 31 33 34 29 29 30 31 31 34 34 35 35 36 32 35 36 37 38 30 33 34 35 36 27 30 33 34 36 • All performance based on tests conducted in accordance with ASHRAE 130-2008 and AHRI 880-2011 • All NC levels determined using AHRI 885-2008 Appendix E. See Terminal Unit Engineering Guidelines. • Dash (-) in space denotes NC value less than NC10 • Only highlighted data points are AHRI certified. Refer to page M38 for AHRI Certified Performance Listings. single / dual duct terminals PERFORMANCE DATA Size 4 5 6 7 8 9 10 12 14 100 125 150 175 200 150 200 250 300 350 300 350 400 450 500 450 500 550 600 650 600 650 700 750 800 800 850 900 950 1000 900 1000 1100 1200 1300 1200 1400 1600 1800 2000 1500 1800 2100 2400 2700 2000 2400 2800 3200 3600 Min ∆Ps 0.02 0.03 0.04 0.06 0.08 0.01 0.02 0.03 0.04 0.06 0.07 0.10 0.13 0.16 0.20 0.07 0.09 0.10 0.12 0.15 0.02 0.02 0.02 0.02 0.03 0.04 0.04 0.05 0.06 0.06 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.02 0.03 0.04 0.05 0.06 0.02 0.02 0.03 0.04 0.05 2 68 70 72 73 74 67 70 72 74 75 69 71 72 73 74 72 72 73 73 73 74 75 75 75 76 74 74 75 76 76 75 76 77 77 78 74 75 76 77 77 70 71 72 73 74 70 72 74 75 76 3 58 62 64 67 69 57 60 64 66 68 64 66 68 69 71 65 67 68 69 71 68 69 70 71 72 65 66 67 67 68 66 67 68 69 69 68 70 71 72 73 63 65 66 67 68 63 66 68 69 71 1.0” ∆Ps 4 5 6 51 46 47 54 49 49 57 51 50 59 53 51 61 55 53 52 47 47 56 51 49 58 53 51 60 55 53 62 57 54 59 54 51 61 56 52 62 58 53 64 59 54 65 61 55 58 54 51 59 56 52 60 57 53 61 58 54 62 59 55 59 55 52 60 56 53 60 56 53 61 57 54 62 58 54 60 57 54 60 57 54 61 57 55 61 58 55 61 58 55 61 59 55 62 60 56 63 61 56 63 61 57 64 62 58 63 59 57 65 61 59 66 62 59 67 63 60 68 64 61 61 59 57 62 59 58 64 60 58 65 60 59 66 61 59 60 58 56 63 60 58 65 61 59 66 62 60 68 63 61 7 41 43 44 45 46 42 44 45 46 47 46 47 48 49 50 46 47 48 48 49 47 47 48 48 49 49 50 50 50 50 50 51 51 52 53 52 53 55 56 56 53 53 54 54 54 51 52 54 55 56 NC 25 28 30 31 33 24 28 30 29 30 23 25 27 28 31 26 26 28 28 31 29 30 30 30 31 26 26 28 29 29 28 29 30 30 31 26 28 30 31 32 21 23 24 25 26 21 24 26 28 30 Octave Band Sound Power, Lw 1.5” ∆Ps 2 3 4 5 6 7 69 60 54 49 50 46 71 63 57 52 52 47 73 66 60 54 54 49 74 68 62 56 55 50 75 71 63 58 56 51 69 59 55 50 51 46 72 63 59 53 53 48 74 66 61 56 55 50 75 69 63 58 56 51 77 71 65 60 57 52 72 67 62 57 54 50 73 69 64 59 55 51 75 71 65 60 57 52 76 72 67 62 58 53 77 74 68 63 59 54 73 69 60 56 54 49 74 70 62 58 55 50 74 72 63 59 56 51 75 73 63 60 57 52 75 74 64 61 58 53 76 71 61 56 55 51 76 72 62 57 55 51 77 73 63 58 56 52 77 74 63 58 56 52 77 75 64 59 57 53 75 68 62 59 57 53 76 69 62 59 57 54 77 69 63 59 57 54 77 70 63 60 58 54 78 71 64 60 58 54 76 69 64 61 58 54 77 70 65 62 59 55 78 71 65 63 60 55 79 72 66 64 60 56 79 73 67 65 61 56 76 71 65 62 60 56 77 73 67 63 61 57 78 74 68 64 62 58 78 75 70 65 63 59 79 76 71 66 64 60 72 67 63 62 62 59 73 68 65 63 62 59 74 69 66 63 63 59 75 70 68 64 63 59 76 71 69 64 63 60 72 66 62 61 59 54 74 68 64 62 61 56 76 70 66 64 62 57 77 72 68 65 63 59 78 73 70 66 64 60 • Discharge sound is the noise emitted from the unit discharge into the downstream ductwork • Min ∆Ps is the static pressure drop from the unit inlet to the unit outlet with the cold damper full open • Sound power levels are in dB, ref 10-12 watts • Sound performance based on units lined with standard dual density fiberglass lining NC 26 29 31 33 34 26 30 33 30 33 26 28 31 32 34 28 30 32 33 34 31 32 33 33 34 28 29 30 30 31 29 30 31 33 33 30 32 33 34 36 25 26 27 28 30 24 26 29 31 32 2 70 72 73 75 76 70 73 75 76 78 74 75 76 78 79 75 75 76 76 77 77 77 78 78 79 76 77 78 78 79 77 78 79 80 80 77 78 79 79 80 74 75 76 76 77 73 75 77 78 80 3 61 64 67 70 72 61 65 68 71 73 69 71 73 75 76 71 73 74 75 76 74 75 76 77 77 70 71 71 72 73 72 73 73 74 75 73 75 76 77 78 69 71 72 73 74 68 70 72 73 75 4 56 59 61 64 65 58 61 63 66 67 64 66 67 69 70 62 63 64 65 66 63 64 64 65 66 64 64 65 65 65 66 67 67 68 68 67 69 70 71 72 65 67 68 69 70 63 66 68 70 71 2.0” ∆Ps 5 6 51 53 54 55 56 57 58 58 60 59 52 53 55 55 58 57 60 59 61 60 58 56 60 58 62 59 63 60 65 61 58 56 59 57 60 58 61 59 62 59 57 57 58 57 59 58 60 58 60 59 60 59 61 59 61 59 61 60 62 60 63 61 64 61 65 62 66 63 66 63 64 62 65 63 66 64 67 65 68 66 65 65 65 65 66 66 66 66 67 66 63 61 64 62 66 64 67 65 68 66 7 49 51 52 53 54 49 51 53 54 55 53 54 55 56 57 52 53 54 55 55 54 54 55 55 56 56 56 57 57 57 57 57 58 59 59 59 60 61 62 63 62 63 63 63 63 57 58 60 61 62 NC 28 30 31 34 35 28 31 34 31 34 29 31 33 36 37 31 33 34 36 37 34 36 37 37 37 29 30 31 31 33 31 32 33 34 34 32 34 36 37 38 27 30 31 32 33 26 28 31 32 34 • All performance based on tests conducted in accordance with ASHRAE 130-2008 and AHRI 880-2011 • All NC levels determined using AHRI 885-2008 Appendix E. See Terminal Unit Engineering Guidelines. • Dash (-) in space denotes NC value less than NC10 • Only highlighted data points are AHRI certified. Refer to page M38 for AHRI Certified Performance Listings. M PERFORMANCE DATA 16 CFM Redefine your comfort zone™ | www.titus-hvac.com PEDV, DEDV WITHOUT ATTENUATOR - DISCHARGE SOUND PERFORMANCE M29 Redefine your comfort zone™ | www.titus-hvac.com Dual Duct with Attentuator single / dual duct terminals EDV / EDC • Standard AeroCrossTM multi-point center averaging velocity sensors in four location combinations to match any control requirement • Standard matte faced insulation for maximum thermal and acoustic performance • Mechanically sealed and gasketed, leak resistant construction • Choice of right or left hand cold duct location; right hand is standard • Standard 22 gauge casing with slip and drive discharge connection • Controls supplied by Titus are factory calibrated for quicker start-up EDV / EDC M AVAILABLE MODELS: PEDV / Pneumatic PEDC / Pneumatic DEDV / Digital Electronic OVERVIEW For Blending or Non-Blending Applications Titus Dual Duct terminals vary the airflow individually between hot and cold inlets for highly accurate temperature control. Dual duct systems are an ideal vehicle for alternative ventilation strategies and humidity control. Additionally, total filtration of all air delivered to the zone is possible. Titus dual duct terminals provide high performance and value, making them the preferred selection for these applications. ADDITIONAL FEATURES EDV / EDC • Direct digital control package supplied by Titus includes: direct digital controller, damper actuators and flow tranducers • Dual density insulation, coated to prevent air erosion, meet requirements of NFPA 90A and UL 181 M30 See website for Specifications single / dual duct terminals DIMENSIONS PEDV - Basic Unit with Controls 4” L G H J F D A W Discharge D E Slip & Drive Cleat Connection Controller 4½” Redefine your comfort zone™ | www.titus-hvac.com EDV UNIT DIMENSIONS Pneumatic Actuator M DEDV - Basic Unit with Controls G 4" L H F D W Discharge A D E Slip and Drive Duct Connection 6½" 18" K K 12¼" Inlet Size cfm Range 0-225 0-350 0-500 0-650 0-900 0-1050 0-1400 0-2000 0-3000 0-4000 D E F G H L W 87/8 87/8 87/8 107/8 107/8 127/8 127/8 147/8 167/8 187/8 37/8 47/8 57/8 67/8 77/8 87/8 97/8 117/8 137/8 157/8 513/16 513/16 513/16 71/16 71/16 101/16 101/16 111/16 129/16 151/16 513/16 513/16 513/16 81/16 81/16 111/16 111/16 131/16 161/16 161/16 53/8 53/8 33/8 6¾ 33/8 6¾ 33/8 33/8 33/8 33/8 81/8 81/8 81/8 101/8 101/8 125/8 125/8 151/8 18 18 191/8 191/8 191/8 231/8 231/8 271/8 271/8 311/8 351/8 381/8 19 19 19 23 23 27 27 31 35 38 All dimensions are in inches PEDV J 17/8 17/8 17/8 7 /8 7 /8 - DEDV K 2 2 2 1 1 - DIMENSIONS 4 5 6 7 8 9 10 12 14 16 A M31 single / dual duct terminals Redefine your comfort zone™ | www.titus-hvac.com PERFORMANCE DATA PEDV, PEDC, DEDV WITH INTEGRAL ATTENUATOR AND MIXING BAFFLES / RADIATED SOUND PERFORMANCE Size 4 5 6 7 M 8 9 10 12 PERFORMANCE DATA 14 M32 16 CFM 100 125 150 175 200 150 200 250 300 350 300 350 400 450 500 450 500 550 600 650 600 650 700 750 800 800 850 900 950 1000 900 1000 1100 1200 1300 1200 1400 1600 1800 2000 1500 1800 2100 2400 2700 2000 2400 2800 3200 3600 Min ∆Ps 0.18 0.29 0.41 0.56 0.73 0.17 0.30 0.47 0.67 0.92 0.51 0.70 0.91 1.15 1.42 0.35 0.44 0.53 0.63 0.74 0.40 0.47 0.55 0.63 0.71 0.18 0.21 0.23 0.26 0.29 0.25 0.31 0.38 0.45 0.53 0.25 0.33 0.44 0.55 0.68 0.18 0.25 0.34 0.45 0.57 0.21 0.30 0.40 0.53 0.67 2 3 46 46 48 49 50 51 52 52 53 54 48 45 51 48 53 51 55 53 57 54 51 51 52 53 52 54 NA NA NA NA 59 52 60 53 61 54 62 55 62 56 58 52 58 53 59 54 59 55 60 56 62 53 63 53 63 54 64 54 65 55 60 52 60 52 61 53 61 54 61 55 64 56 65 57 65 58 66 59 66 60 62 54 63 56 64 57 65 58 65 60 65 55 66 57 66 58 67 59 68 60 1.0” ∆Ps 4 5 6 7 NC 37 31 29 23 12 40 33 31 25 16 42 35 33 26 18 44 37 34 28 20 45 38 36 29 22 38 32 32 25 11 42 35 35 28 15 44 37 37 31 18 47 39 38 33 21 48 40 40 35 22 43 38 36 30 18 44 39 37 31 21 46 41 38 32 22 NA NA NA NA NA NA NA NA NA NA 46 41 40 35 20 47 42 41 36 22 48 43 41 37 23 49 43 42 37 24 49 44 43 38 24 45 39 37 35 20 46 39 38 36 21 46 40 38 36 22 47 41 39 37 23 47 41 39 38 24 45 41 42 40 24 45 42 42 40 25 46 42 42 40 25 46 42 43 40 27 46 43 43 41 28 44 40 38 37 22 45 41 39 37 22 46 41 40 38 23 47 42 40 39 23 47 42 40 39 23 52 50 53 52 27 54 51 53 52 28 55 52 54 52 29 56 52 54 52 30 57 53 54 52 31 47 42 43 43 24 49 43 44 44 25 51 45 45 45 27 52 46 46 46 28 53 47 47 47 29 50 45 47 47 28 52 46 48 47 29 54 47 48 47 29 56 48 49 47 31 57 49 49 47 32 Octave Band Sound Power, Lw 1.5” ∆Ps 2 3 4 5 6 7 49 49 39 33 33 28 52 52 42 36 35 29 54 53 44 38 36 31 55 55 46 39 38 32 57 57 48 41 39 33 51 48 41 35 35 29 54 51 44 37 37 32 56 54 47 40 39 35 58 56 49 41 41 37 60 58 51 43 43 39 54 54 46 40 39 34 55 56 47 42 40 35 55 57 49 43 41 37 55 58 50 45 42 38 55 60 51 46 43 39 61 56 49 43 43 40 62 57 50 44 44 41 63 57 51 45 45 41 64 58 52 46 45 42 65 59 52 47 46 43 60 57 49 42 40 39 61 58 49 42 41 40 61 59 50 43 41 40 62 60 51 44 41 41 62 60 51 44 42 42 64 56 49 44 45 45 65 57 49 45 46 45 66 57 50 45 46 45 66 58 50 46 46 45 67 58 50 46 46 45 63 55 47 42 41 39 63 56 48 43 41 40 64 57 49 43 42 41 64 58 49 44 42 42 65 59 50 45 43 42 68 59 55 54 57 57 68 61 57 55 58 57 68 62 58 55 58 57 69 63 59 56 58 57 69 64 60 56 58 58 66 57 50 44 46 47 67 59 52 46 47 48 67 60 53 47 48 49 68 62 55 48 49 49 69 63 56 49 49 50 68 59 52 47 50 51 69 60 54 48 50 51 70 61 56 50 51 51 70 62 58 51 51 51 71 63 59 51 52 51 • Radiated sound is the noise transmitted through the unit casing • Min ∆Ps is the static pressure drop from the unit inlet to the unit outlet with the cold damper full open • Sound power levels are in dB, ref 10-12 watts • Sound performance based on units lined with standard dual density fiberglass lining NC 16 20 21 23 25 15 18 22 24 27 22 24 25 27 29 24 25 25 27 28 25 27 28 29 29 27 28 29 29 31 25 25 27 27 28 32 32 32 34 35 29 31 31 32 33 32 33 34 34 36 2 52 54 56 58 59 53 56 58 60 62 57 57 57 57 58 63 64 65 65 66 62 63 63 64 64 66 66 67 68 68 65 66 66 66 67 70 70 71 71 72 68 69 70 70 71 70 71 72 73 73 3 51 53 55 57 59 50 54 56 58 60 57 58 60 61 62 58 59 60 61 61 60 61 62 63 64 59 59 60 61 61 58 59 60 61 61 62 63 64 65 66 60 61 63 64 65 61 62 64 65 66 4 41 44 46 48 49 43 46 49 51 53 48 50 51 52 53 51 52 53 54 55 51 52 53 53 54 52 52 52 53 53 49 50 51 51 52 58 59 60 61 62 52 54 55 57 58 53 56 58 59 61 2.0” ∆Ps 5 6 35 35 38 37 40 39 41 40 43 41 36 36 39 39 41 41 43 43 45 44 42 41 44 42 45 44 47 45 48 45 45 45 46 46 47 47 48 48 48 48 44 42 44 43 45 43 46 43 46 44 47 48 47 48 47 48 48 49 48 49 44 42 44 43 45 44 46 44 46 44 57 60 58 61 58 61 59 61 59 62 46 47 47 49 49 49 50 50 51 51 49 51 50 52 51 53 52 53 53 54 7 31 33 34 36 37 32 35 38 40 42 37 39 40 41 42 43 44 45 45 46 42 43 43 44 44 48 48 48 49 49 41 42 43 44 44 61 61 61 61 61 49 50 51 52 53 53 53 53 53 53 NC 18 21 23 25 28 17 22 24 27 29 25 27 29 30 31 27 28 29 30 30 29 30 31 33 34 29 29 31 32 32 28 29 29 30 31 34 34 36 36 37 32 33 34 34 36 34 36 37 38 38 • All performance based on tests conducted in accordance with ASHRAE 130-2008 and AHRI 880-2011 • All NC levels determined using AHRI 885-2008 Appendix E. See Terminal Unit Engineering Guidelines. • Dash (-) in space denotes NC value less than NC10 • Only highlighted data points are AHRI certified. Refer to page M38 for AHRI Certified Performance Listings. single / dual duct terminals PERFORMANCE DATA Size 4 5 6 7 8 9 10 12 14 100 125 150 175 200 150 200 250 300 350 300 350 400 450 500 450 500 550 600 650 600 650 700 750 800 800 850 900 950 1000 900 1000 1100 1200 1300 1200 1400 1600 1800 2000 1500 1800 2100 2400 2700 2000 2400 2800 3200 3600 Min ∆Ps 0.18 0.29 0.41 0.56 0.73 0.17 0.30 0.47 0.67 0.92 0.51 0.70 0.91 1.15 1.42 0.35 0.44 0.53 0.63 0.74 0.40 0.47 0.55 0.63 0.71 0.18 0.21 0.23 0.26 0.29 0.25 0.31 0.38 0.45 0.53 0.25 0.33 0.44 0.55 0.68 0.18 0.25 0.34 0.45 0.57 0.21 0.30 0.40 0.53 0.67 2 67 70 72 74 76 65 69 72 74 76 68 69 70 N/A N/A 69 71 72 73 74 70 71 71 72 72 74 75 75 76 77 74 75 76 76 77 73 74 76 77 77 71 73 75 76 77 73 74 75 76 77 3 58 61 64 66 68 57 61 64 67 69 62 63 64 N/A N/A 65 66 67 68 69 66 67 68 68 69 64 64 65 65 66 63 64 65 66 67 64 65 67 68 69 62 64 65 66 67 62 64 66 67 68 1.0” ∆Ps 4 5 6 50 45 44 53 48 47 56 50 49 58 52 51 60 54 53 49 44 45 53 48 48 56 50 50 59 52 52 61 54 54 54 50 50 56 51 52 58 53 53 N/A N/A N/A N/A N/A N/A 55 50 51 57 51 52 58 52 53 59 53 54 60 54 55 57 52 53 57 53 54 58 54 54 59 54 55 59 55 55 55 52 54 55 52 55 56 52 55 56 53 55 57 53 56 55 52 56 56 53 56 57 53 57 57 54 57 58 54 57 56 53 56 58 54 57 59 55 58 61 56 59 62 57 60 55 53 56 57 54 57 59 55 58 60 56 59 61 57 60 55 53 58 57 55 59 59 56 60 61 58 61 62 59 61 Octave Band Sound Power, Lw 1.5” ∆Ps 7 NC 2 3 4 5 6 7 36 24 68 59 51 46 45 38 40 28 71 62 54 49 48 41 43 30 74 65 57 51 50 45 46 33 76 67 59 53 52 47 48 35 78 69 61 55 54 50 40 21 67 59 52 46 48 43 44 26 71 63 56 50 50 47 47 30 74 67 59 52 53 50 50 29 76 69 61 54 54 53 52 31 78 71 63 56 56 55 48 21 71 65 57 52 53 51 49 22 72 66 59 53 54 53 51 24 73 67 60 55 55 54 N/A N/A 74 68 62 56 56 55 N/A N/A 75 69 63 57 57 56 48 24 71 67 58 53 54 51 49 25 73 68 59 54 55 53 50 26 74 69 60 54 56 54 52 28 75 71 61 55 56 55 53 29 76 72 62 56 57 56 51 25 72 69 59 54 55 54 52 26 73 70 60 55 56 55 52 27 73 71 61 56 57 56 53 26 74 72 62 56 57 57 54 27 74 72 62 57 58 57 52 26 77 67 58 55 57 56 52 28 77 68 59 55 57 56 53 28 78 68 59 55 58 57 54 29 79 69 60 56 58 57 54 30 79 69 60 56 58 58 55 26 77 67 59 55 58 59 56 28 78 68 60 56 59 60 57 29 79 69 61 57 59 61 58 29 80 70 61 57 60 62 59 30 80 71 62 57 60 62 55 25 76 68 59 56 58 58 57 26 78 69 61 57 59 60 58 29 79 70 62 58 60 61 59 30 80 71 64 59 61 62 60 30 81 72 65 60 62 63 56 22 75 66 59 56 58 59 58 25 76 68 61 57 60 61 59 28 78 69 62 58 61 62 61 29 79 70 63 59 62 64 62 30 80 71 65 60 62 65 58 25 76 66 58 56 60 61 60 26 78 68 60 58 61 63 61 28 79 69 62 59 62 64 62 29 80 71 64 60 63 66 63 30 81 72 65 61 64 67 • Discharge sound is the noise emitted from the unit discharge into the downstream ductwork • Min ∆Ps is the static pressure drop from the unit inlet to the unit outlet with the cold damper full open • Sound power levels are in dB, ref 10-12 watts • Sound performance based on units lined with standard dual density fiberglass lining NC 25 29 33 35 38 24 29 33 31 34 25 26 28 29 30 26 28 29 31 32 28 30 31 31 31 30 30 31 33 33 30 31 33 34 34 29 31 33 34 35 28 29 31 33 34 29 31 33 34 35 2 69 72 75 77 79 68 72 75 77 79 73 75 76 76 77 73 74 75 76 77 74 74 75 76 76 79 79 80 81 81 79 80 81 82 83 79 80 81 82 83 77 79 80 82 83 79 80 82 83 84 3 60 63 66 68 70 61 65 68 71 73 67 68 70 71 72 69 70 71 72 73 72 72 73 74 75 70 70 71 71 72 70 71 72 73 73 70 72 73 74 75 69 70 72 73 74 69 71 72 73 75 4 52 55 58 60 62 53 57 60 63 65 59 61 63 64 65 60 61 62 63 64 61 62 63 64 64 61 62 62 62 63 62 63 63 64 64 62 63 65 66 67 61 63 65 66 67 60 63 64 66 67 2.0” ∆Ps 5 6 47 46 50 49 52 52 54 54 56 55 48 49 51 52 54 54 56 56 57 58 53 55 55 56 56 57 57 58 58 59 54 56 55 57 56 57 57 58 58 59 56 57 57 58 57 58 58 59 59 59 57 59 57 59 57 59 58 60 58 60 58 60 58 60 59 61 59 61 60 62 58 60 59 61 60 62 61 63 62 63 58 60 59 61 60 62 61 63 62 64 58 62 60 63 61 64 62 65 63 65 7 39 43 46 49 51 45 49 52 55 57 54 55 56 58 59 54 55 56 58 59 57 57 58 59 60 58 59 60 60 61 61 62 63 64 65 61 62 64 65 66 62 63 65 66 67 64 65 67 68 69 NC 26 30 34 36 39 25 30 34 33 35 28 30 31 31 33 28 30 31 32 33 32 32 33 33 34 33 33 34 35 35 33 34 35 36 38 33 34 35 36 38 30 33 34 36 38 33 34 36 38 39 • All performance based on tests conducted in accordance with ASHRAE 130-2008 and AHRI 880-2011 • All NC levels determined using AHRI 885-2008 Appendix E. See Terminal Unit Engineering Guidelines. • Dash (-) in space denotes NC value less than NC10 • Only highlighted data points are AHRI certified. Refer to page M38 for AHRI Certified Performance Listings. M PERFORMANCE DATA 16 CFM Redefine your comfort zone™ | www.titus-hvac.com PEDV, PEDC, DEDV WITH INTEGRAL ATTENUATOR AND MIXING BAFFLES / DISCHARGE SOUND PERFORMANCE M33 Redefine your comfort zone™ | www.titus-hvac.com Dual Duct High Performance Blending single / dual duct terminals MDV / MDC • Standard AeroCrossTM multi-point center averaging velocity sensors in multiple location combinations to match any control requirement • Standard matte faced insulation for maximum thermal and acoustic performance • Mechanically sealed and gasketed, leak resistant construction • High performance mixing section • Choice of right or left hand cold duct location; right hand is standard • Standard 22 gauge casing with slip and drive discharge connection • Controls supplied by Titus are factory calibrated for quicker start-up MDV / MDC M AVAILABLE MODELS: PMDV / Pneumatic PMDC / Pneumatic DMDV / Digital Electronic OVERVIEW Titus Dual Duct terminals vary the airflow individually between hot and cold inlets for highly accurate temperature control. Dual duct systems are an ideal vehicle for alternative ventilation strategies and humidity control. Additionally, total filtration of all air delivered to the zone is possible. Titus dual duct terminals provide high performance and value, making them the preferred selection for these applications. ADDITIONAL FEATURES MDV / MDC • Direct digital control package supplied by Titus includes: direct digital controller, damper actuators and flow tranducers • Dual density insulation, coated to prevent air erosion, meet requirements of NFPA 90A and UL 181 M34 See website for Specifications single / dual duct terminals DIMENSIONS PMDV/PMDC - Basic Unit with Controls G L 4" H F D A W Discharge D E Slip and Drive Duct Connection J Controllers 4½" Pneumatic Actuator DMDV - Basic Unit with Controls 8" Max G 4" L Redefine your comfort zone™ | www.titus-hvac.com MDV / MDC UNIT DIMENSIONS H M 6½" F D W Discharge A D E Slip and Drive Duct Connection 6½" 18" K K 12¼" Inlet Size cfm Range 0-225 0-350 0-500 0-650 0-900 0-1050 0-1400 0-2000 0-3000 0-4000 D E F G H L W 87/8 87/8 87/8 107/8 107/8 127/8 127/8 147/8 167/8 187/8 37/8 47/8 57/8 67/8 77/8 87/8 97/8 117/8 137/8 157/8 57/8 57/8 57/8 71/8 71/8 101/8 101/8 111/8 12½ 151/8 57/8 57/8 57/8 81/8 81/8 111/8 111/8 131/8 161/8 161/8 53/8 53/8 33/8 6¾ 33/8 6¾ 33/8 33/8 33/8 33/8 8¼ 8¼ 8¼ 10¼ 10¼ 12¾ 12¾ 15¼ 181/8 181/8 34 34 34 42 42 50 50 58 66 72 19 19 19 23 23 27 27 31 35 38 All dimensions are in inches PMDV DMDV K J 7 1 /8 2 17/8 2 17/8 2 7 /8 1 7 /8 1 - DIMENSIONS 4 5 6 7 8 9 10 12 14 16 A M35 single / dual duct terminals Redefine your comfort zone™ | www.titus-hvac.com PERFORMANCE DATA PMDV, PMDC, DMDV / RADIATED SOUND PERFORMANCE Size 4 5 6 7 M 8 9 10 12 PERFORMANCE DATA 14 M36 16 CFM 100 125 150 175 200 150 200 250 300 350 300 350 400 450 500 450 500 550 600 650 600 650 700 750 800 800 850 900 950 1000 900 1000 1100 1200 1300 1200 1400 1600 1800 2000 1500 1800 2100 2400 2700 2000 2400 2800 3200 3600 Min ∆Ps 0.18 0.29 0.41 0.56 0.74 0.15 0.27 0.42 0.60 0.82 0.43 0.58 0.76 0.96 0.39 0.32 0.39 0.47 0.56 0.66 0.37 0.43 0.50 0.57 0.65 0.20 0.22 0.25 0.28 0.31 0.21 0.26 0.31 0.37 0.44 0.29 0.39 0.51 0.64 0.80 0.16 0.23 0.31 0.41 0.52 0.20 0.28 0.39 0.50 0.64 2 55 56 57 58 59 55 58 60 62 63 58 59 60 60 63 62 63 64 64 65 62 63 63 64 64 67 67 68 68 68 63 64 65 65 66 68 69 70 70 71 66 67 68 69 70 70 71 72 73 74 3 50 52 53 55 56 51 54 55 57 58 54 54 55 56 57 56 57 58 58 59 56 57 57 58 58 57 58 58 58 59 58 59 59 60 61 60 61 62 63 64 58 60 61 62 63 60 61 62 63 64 1.0” ∆Ps 4 5 6 42 36 35 43 38 36 44 39 37 45 39 38 46 40 38 43 34 29 45 37 34 46 39 37 48 41 40 49 43 42 46 41 41 47 42 42 48 44 43 48 45 44 48 43 41 48 42 40 48 43 41 49 43 41 49 44 42 50 45 42 48 42 40 49 43 41 50 44 41 50 45 42 50 45 43 47 40 38 48 41 39 48 42 40 49 42 40 49 43 41 51 47 47 52 48 48 53 48 49 53 49 49 54 49 49 54 53 54 55 54 55 57 54 56 58 55 57 58 56 57 49 41 38 52 43 41 54 45 43 56 47 45 57 49 47 53 45 42 55 47 44 57 50 47 59 51 49 61 53 51 7 31 32 33 34 34 21 27 32 36 40 37 38 38 39 36 36 36 37 37 37 38 39 39 40 40 29 30 30 31 31 47 47 48 48 48 52 52 53 54 54 31 34 36 38 40 37 40 42 44 45 NC 17 20 21 23 24 18 22 23 25 27 22 22 23 24 25 24 25 27 27 28 24 25 25 27 27 31 31 32 32 32 27 28 28 29 30 32 33 34 34 36 29 31 32 33 34 34 36 37 38 40 Octave Band Sound Power, Lw 1.5” ∆Ps 2 3 4 5 6 7 57 53 45 38 37 34 58 55 46 40 38 35 59 56 47 41 39 36 60 58 48 42 40 36 61 59 49 42 41 37 58 55 47 37 32 24 60 57 49 40 36 30 63 59 50 43 40 35 64 60 52 45 42 40 66 62 53 46 45 43 61 58 50 44 45 41 66 62 53 46 45 43 63 59 51 47 47 43 64 60 52 48 48 43 64 60 53 49 49 44 64 60 51 45 44 41 65 61 52 46 45 42 66 61 53 46 45 42 67 62 53 47 46 42 68 62 54 48 46 43 65 61 52 45 44 43 66 61 53 46 45 43 67 61 53 47 45 44 67 62 54 48 46 44 68 62 54 48 47 45 70 61 51 43 41 34 70 62 52 44 42 34 71 62 52 45 42 35 71 62 52 46 43 35 71 63 53 46 44 36 68 63 54 50 51 51 69 63 55 51 52 51 69 64 56 51 52 52 70 65 56 52 53 52 70 65 57 52 53 53 71 63 58 57 58 57 72 65 59 58 59 58 73 66 60 58 60 58 74 67 61 59 61 59 75 67 62 60 62 59 70 62 52 43 40 35 71 64 54 46 43 37 72 65 56 48 46 40 73 66 58 50 48 42 74 67 60 51 50 44 74 64 56 48 44 41 75 65 58 50 47 43 76 66 60 52 49 45 77 68 62 54 51 47 78 68 64 56 53 49 • Radiated sound is the noise transmitted through the unit casing • Min ∆Ps is the static pressure drop from the unit inlet to the unit outlet with the cold damper full open • Sound power levels are in dB, ref 10-12 watts • Sound performance based on units lined with standard dual density fiberglass lining NC 21 23 24 27 28 23 25 28 29 31 27 31 28 29 29 29 30 30 31 32 30 30 31 31 32 34 34 36 36 36 33 33 34 35 35 36 37 38 40 41 34 36 37 38 40 40 41 42 43 45 2 58 60 61 62 62 59 62 64 66 67 64 67 65 66 67 66 67 68 69 70 68 68 69 69 70 72 72 73 73 73 71 72 73 73 74 74 75 76 77 78 73 74 75 76 77 77 78 79 80 80 3 55 57 58 60 61 57 59 61 63 64 61 64 62 63 63 62 63 64 64 65 63 64 64 65 65 64 65 65 65 66 66 66 67 68 68 66 67 68 69 70 65 66 68 69 69 67 68 69 70 71 2.0” ∆Ps 4 5 6 47 40 39 49 41 40 50 42 41 50 43 41 51 44 42 50 39 34 52 42 38 53 45 41 55 47 44 56 48 47 52 47 47 56 48 47 54 49 50 55 50 51 56 51 52 54 47 47 56 51 52 55 48 48 56 49 49 56 50 49 55 47 47 56 48 47 56 49 48 57 50 49 57 50 49 54 46 43 54 46 44 55 47 45 55 48 45 56 49 46 57 52 54 57 53 54 58 53 55 59 54 55 59 54 56 60 60 61 61 61 62 62 61 63 63 62 64 64 63 65 54 45 42 56 48 45 58 50 47 60 52 50 62 53 51 58 50 46 60 52 49 62 54 51 64 56 53 66 58 55 7 36 37 38 39 39 26 33 38 42 45 44 45 46 46 47 45 47 46 46 46 46 47 47 48 48 37 38 38 39 39 54 54 55 55 55 60 61 62 62 63 37 40 42 44 46 43 46 48 50 51 NC 23 25 27 29 30 25 28 30 33 34 30 34 31 33 33 31 33 34 34 35 33 34 34 35 35 37 37 38 38 38 36 37 38 38 40 40 41 42 43 45 38 40 41 42 43 43 45 46 47 47 • All performance based on tests conducted in accordance with ASHRAE 130-2008 and AHRI 880-2011 • All NC levels determined using AHRI 885-2008 Appendix E. See Terminal Unit Engineering Guidelines. • Dash (-) in space denotes NC value less than NC10 • Only highlighted data points are AHRI certified. Refer to page M38 for AHRI Certified Performance Listings. single / dual duct terminals PERFORMANCE DATA Size 4 5 6 7 8 9 10 12 14 100 125 150 175 200 150 200 250 300 350 300 350 400 450 500 450 500 550 600 650 600 650 700 750 800 800 850 900 950 1000 900 1000 1100 1200 1300 1200 1400 1600 1800 2000 1500 1800 2100 2400 2700 2000 2400 2800 3200 3600 Min ∆Ps 0.18 0.29 0.41 0.56 0.74 0.15 0.27 0.42 0.60 0.82 0.43 0.58 0.76 0.96 0.39 0.32 0.39 0.47 0.56 0.66 0.37 0.43 0.50 0.57 0.65 0.20 0.22 0.25 0.28 0.31 0.21 0.26 0.31 0.37 0.44 0.29 0.39 0.51 0.64 0.80 0.16 0.23 0.31 0.41 0.52 0.20 0.28 0.39 0.50 0.64 2 65 68 71 73 75 68 72 75 77 79 74 76 77 78 79 74 76 77 78 79 75 76 76 77 78 75 76 76 77 78 76 77 78 79 80 78 80 81 82 83 76 78 80 82 83 79 81 82 84 85 3 57 60 63 65 67 59 63 67 69 72 65 67 68 69 70 67 69 70 71 72 68 69 69 70 71 65 65 66 66 66 66 67 68 69 70 67 69 71 72 74 64 67 69 71 73 67 70 72 73 75 1.0” ∆Ps 4 5 6 50 45 38 52 47 42 55 49 45 56 51 48 58 53 50 52 46 38 55 49 44 58 52 48 60 54 51 62 56 54 56 51 46 57 53 49 58 54 51 59 55 53 60 53 52 58 52 50 59 53 52 60 54 53 61 55 55 62 56 56 59 53 51 60 54 52 61 54 53 62 55 54 62 56 55 58 50 48 59 51 49 59 52 50 59 52 51 60 53 52 59 54 52 60 55 53 61 56 55 62 57 56 63 58 58 61 54 53 63 56 56 64 58 59 66 60 61 67 61 63 59 51 51 61 54 54 63 56 57 65 59 59 67 60 61 61 55 54 63 58 58 66 61 60 67 63 63 69 65 65 7 28 34 38 42 46 31 39 45 50 54 39 43 45 48 48 45 48 50 52 54 46 48 50 51 53 44 45 47 48 49 46 48 50 52 53 49 52 55 57 59 45 48 51 54 56 49 52 56 58 61 NC 21 25 29 31 34 25 30 34 33 35 29 31 33 34 35 29 31 33 34 35 30 31 31 30 31 28 29 29 30 31 29 30 31 33 34 31 34 35 36 38 29 31 34 36 38 33 35 36 39 40 Octave Band Sound Power, Lw 1.5” ∆Ps 2 3 4 5 6 7 67 59 52 47 40 30 70 62 55 50 44 36 73 65 57 52 47 40 75 67 59 54 50 44 77 69 60 55 52 47 69 61 54 48 40 33 73 65 58 52 46 40 76 69 61 55 50 46 79 71 63 57 53 51 81 74 65 59 56 55 77 68 59 54 48 42 81 74 65 59 56 55 80 71 62 57 53 48 81 73 63 58 55 50 81 74 64 59 56 53 76 70 61 54 51 47 78 71 62 56 53 50 79 72 63 56 55 52 80 74 64 57 57 54 81 75 65 58 58 56 78 71 63 56 52 48 78 72 64 57 54 50 79 72 64 57 55 52 80 73 65 58 56 53 80 74 66 59 57 55 78 68 62 53 51 47 79 69 62 54 52 48 79 69 63 54 53 49 80 70 63 55 54 50 80 70 63 56 54 51 80 70 63 56 54 49 81 71 64 58 55 51 82 72 65 59 57 52 82 72 65 60 58 54 83 73 66 60 60 56 81 70 64 56 55 51 82 72 66 58 58 54 84 74 68 60 61 57 85 75 69 62 63 59 86 77 70 64 65 61 79 68 62 53 53 47 81 70 64 56 56 51 83 72 66 59 59 54 84 74 68 61 61 56 86 76 70 63 63 58 82 70 64 57 56 51 84 73 66 60 60 55 85 75 68 63 63 58 87 77 70 65 65 60 88 78 72 67 67 63 • Discharge sound is the noise emitted from the unit discharge into the downstream ductwork • Min ∆Ps is the static pressure drop from the unit inlet to the unit outlet with the cold damper full open • Sound power levels are in dB, ref 10-12 watts • Sound performance based on units lined with standard dual density fiberglass lining NC 24 28 31 34 36 26 31 35 35 38 33 38 36 38 38 31 34 35 36 38 34 34 35 34 34 31 33 33 34 34 34 35 36 36 38 35 36 39 40 42 33 35 38 39 42 36 39 40 43 44 2 68 71 74 76 78 71 75 78 80 82 79 82 81 82 83 78 80 80 81 82 80 80 81 82 82 80 81 81 82 82 82 83 84 85 86 83 84 86 87 88 81 83 85 86 88 84 86 88 89 90 3 60 63 66 68 70 62 67 70 73 75 70 75 74 75 76 71 75 74 75 76 73 74 75 75 76 71 71 72 72 73 72 73 74 75 76 72 74 76 78 79 70 73 75 77 78 73 75 77 79 80 4 54 57 59 61 62 56 60 62 65 67 62 67 64 66 66 63 65 65 66 67 65 66 67 67 68 64 65 65 66 66 65 66 67 68 69 66 68 70 71 73 64 66 68 70 72 65 68 70 72 74 2.0” ∆Ps 5 6 49 42 52 45 54 49 56 51 57 54 50 42 54 47 57 51 59 55 61 57 56 50 61 57 59 54 60 56 61 58 56 52 61 58 58 56 59 58 60 59 58 54 59 55 60 56 60 57 61 58 55 52 56 53 57 54 57 55 58 56 58 55 60 57 61 58 62 60 62 61 58 57 60 60 62 62 64 64 65 66 55 54 58 57 60 60 62 63 64 65 59 58 62 61 65 64 67 66 69 69 7 32 37 42 46 49 34 41 47 52 56 43 56 49 52 54 48 54 53 55 57 50 51 53 55 56 48 50 51 52 53 50 52 54 56 57 53 56 58 61 63 49 53 55 58 60 53 56 59 62 64 NC 25 29 33 35 38 29 34 38 36 39 35 39 38 39 40 34 36 36 38 39 36 36 38 36 36 34 35 35 36 36 36 38 39 40 42 38 39 42 43 44 35 38 40 42 44 39 42 44 45 47 • All performance based on tests conducted in accordance with ASHRAE 130-2008 and AHRI 880-2011 • All NC levels determined using AHRI 885-2008 Appendix E. See Terminal Unit Engineering Guidelines. • Dash (-) in space denotes NC value less than NC10 • Only highlighted data points are AHRI certified. Refer to page M38 for AHRI Certified Performance Listings. M PERFORMANCE DATA 16 CFM Redefine your comfort zone™ | www.titus-hvac.com PMDV, PMDC, DMDV / DISCHARGE SOUND PERFORMANCE M37 single / dual duct terminals Redefine your comfort zone™ | www.titus-hvac.com PERFORMANCE DATA M AHRI Directory of Certified Performance Titus is a charter member company and current partici- PMDV, PMDC, DMDV pant in the AHRI Directory of Certified Performance. This Inlet Rated Min voluntary certification program was developed by parSize CFM ∆Ps ticipating manufacturers in conjunction with the former Air-Conditioning and Refrigeration Institute (ARI) in the 04 150 0.41 1990’s. It is currently administrated by the Air-Condi05 250 0.42 tioning, Heating, and Refrigeration Institute (AHRI). The 06 400 0.76 purpose of this program is to provide for the independent 07 550 0.47 verification of manufacturers’ published performance data. Only participating products are authorized to bear 08 700 0.50 the AHRI VAV Certification Mark. Certified data may be 09 900 0.25 viewed and downloaded at www.ahrinet.org. 10 PEDV, PEDC, PMDV, PMDC, DEDV, DMDV PERFORMANCE DATA 0.31 Radiated Sound Power Discharge Sound Power W 2 2 5.875 5.875 59 56 47 41 39 36 73 65 57 51 47 40 5.875 5.875 63 59 50 43 40 35 76 69 61 54 50 46 5.875 5.875 63 59 51 47 47 43 80 71 62 56 53 48 8.125 7.125 66 61 53 46 45 42 79 72 63 55 55 52 67 61 53 47 45 44 79 72 64 56 55 52 3 4 5 6 7 3 4 5 6 7 8.125 7.125 11.125 10.125 71 62 52 45 42 35 79 69 63 54 53 49 11.125 10.125 69 64 56 51 52 52 82 72 65 59 57 52 In order to participate in this program, member compa12 1600 0.51 13.125 11.125 73 66 60 58 60 58 84 74 68 60 61 57 nies pay annual dues based on sales volume, submit pub14 2100 0.31 16.125 12.500 72 65 56 48 46 40 83 72 66 59 59 54 lished performance data for all applicable model types, 16 2800 0.39 16.125 15.125 76 66 60 52 49 45 85 75 68 63 63 58 and agree to provide a number of randomly selected product samples for annual rounds of independent testing at the manufacturers’ expense. All verification test- PEDV, PEDC, DEDV WITH INTEGRAL ATTENUATOR & MIXING BAFFLE ing is conducted in accordance with ASHRAE Standard Discharge Radiated Sound Power Discharge Sound Power Inlet Rated Min 130 ‘Methods of Testing Air Terminal Units’. These tests Size CFM ∆Ps H W 2 3 4 5 6 7 2 3 4 5 6 7 are conducted to verify that a manufacturer’s published certified ratings are within the test tolerances outlined in 04 150 0.41 5.875 5.875 54 53 44 38 36 31 74 65 57 50 50 45 AHRI Standard 880 ‘Performance Rating of Air Terminals’. 05 250 0.47 5.875 5.875 56 54 47 40 39 35 74 67 59 51 53 50 Any failure to demonstrate the certified performance is 06 400 0.91 5.875 5.875 55 57 49 43 41 37 73 67 60 54 55 54 punished by additional testing requirements, mandatory performance re-rating, monetary penalties and possible 07 550 0.53 8.125 7.125 63 57 51 45 45 41 74 69 60 53 56 54 expulsion from the Certified Directory. 08 700 0.55 8.125 7.125 61 59 50 43 41 40 73 71 61 55 57 56 Product samples provided for certification testing are standard production units with standard ½” dual density fiberglass lining (unless otherwise specified) and no optional appurtenances such as add-on attenuators or heating/cooling coils. The certified ratings are measured at the standard operating points under the following test conditions: M38 1100 Discharge H • Rated airflow (cfm) – Based on an inlet velocity of 2000 fpm • Rated Min ∆Ps (in wg) – Minimum static pressure drop from the cold inlet to discharge at rated airflow with damper full open • Rated ∆Ps (in wg) – A static pressure drop of 1.5 in wg from cold inlet to discharge with the hot damper fully closed • Rated sound power by octave band (dB, re 10-12 watts) – Radiated and discharge sound performance conducted in a reverberation room that meets both the broadband and pure tone qualifications of AHRI Standard 220 09 900 0.23 11.125 10.125 66 57 50 45 46 45 78 68 59 55 58 57 10 1100 0.38 11.125 10.125 64 57 49 43 42 41 79 69 61 57 59 61 12 1600 0.44 13.125 11.125 68 62 58 55 58 57 79 70 62 58 60 61 14 2100 0.34 16.125 12.500 67 60 53 47 48 49 78 69 62 58 61 62 16 2800 0.40 16.125 15.125 70 61 56 50 51 51 79 69 62 59 62 64 PEDV, DEDV WITHOUT ATTENUATOR Inlet Size Rated CFM Min ∆Ps Discharge Radiated Sound Power Discharge Sound Power H 2 2 04 150 0.04 8 24.125 60 57 46 41 40 37 73 66 60 54 54 49 05 250 0.03 8 24.125 62 59 49 42 41 37 74 66 61 56 55 50 06 400 0.13 8 24.125 63 61 52 44 42 38 75 71 65 60 57 52 07 550 0.10 10 24.125 64 59 53 47 43 34 74 72 63 59 56 51 08 700 0.02 10 24.125 65 60 53 47 47 45 77 73 63 58 56 52 09 900 0.05 12.5 28.125 64 58 53 47 45 38 77 69 63 59 57 54 10 1100 0.01 12.5 28.125 67 62 57 55 54 43 78 71 65 63 60 55 12 1600 0.01 15 32.125 66 62 59 53 50 44 78 74 68 64 62 58 14 2100 0.04 17.5 40.125 66 62 55 53 50 46 74 69 66 63 63 59 16 2800 0.03 18 48.125 66 61 54 50 50 45 76 70 66 64 62 57 W 3 4 5 6 7 3 4 5 6 7