PKFY NAMU, NGMU, NFMU Engineering Manual
Transcription
PKFY NAMU, NGMU, NFMU Engineering Manual
Wall-mounted PKFY-P-NAMU-E, NGMU-E, NFMU-E 1. SPECIFICATIONS...................................................................................................................................................PKFY-3 2. EXTERNAL DIMENSIONS......................................................................................................................................PKFY-5 3. ELECTRICAL WIRING DIAGRAMS........................................................................................................................PKFY-9 4. SOUND PRESSURE LEVELS..............................................................................................................................PKFY-11 4-1. Sound Pressure Levels...............................................................................................................................PKFY-11 4-2. NC Curves...................................................................................................................................................PKFY-11 5. CAPACITY TABLES...............................................................................................................................................PKFY-12 5-1. Cooling Capacity in Combination with PUHY-HP72,96THMU; -HP144,192TSHMU...................................PKFY-12 5-2. Heating Capacity in Combination with PUHY-HP72,96THMU; -HP144,192TSHMU...................................PKFY-14 6. TEMPERATURE/AIRFLOW DISTRIBUTIONS......................................................................................................PKFY-16 6-1. Temperature Distributions...........................................................................................................................PKFY-16 6-2. Airflow Distributions.....................................................................................................................................PKFY-17 7. OPTIONAL PARTS................................................................................................................................................PKFY-18 7-1. Optional Parts Line Up for the Indoor Unit..................................................................................................PKFY-18 7-2. L-shaped Connection Pipe PAC-SC84PI-E for PKFY-P-NFMU-E...............................................................PKFY-18 7-3. External Heater Adapter PAC-YU24HT.......................................................................................................PKFY-19 PKFY-P-NAMU-E PKFY-P-NGMU-E PKFY-P-NFMU-E PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E PKFY- Wall-mounted Wall mounted DATA U3 I.Wall mounted PKFY-P-NAMU-E PKFY-P-NGMU-E PKFY-P-NFMU-E PKFY-P-NAMU-E PKFY-P-NGMU-E PKFY-P-NFMU-E PKFY-P-NFMU-A Elegant design design and and compact compactdimensions dimensionsideal idealfor foroffices, offices,stores storesand andresidential residentialuses uses, etc. Elegant needs. Ŷ A wide selection for your design and performance needs Ŷ Operation is among the quietest available Ŷ They are more compact and weigh less than most competitive units. In addition, they are extremely quiet with one of the lowest sound ratings available from any manufacturer. Optimized airflow passage. Avoid turbo air returning. Avoid dewing at outlet. optimal air air distribution distribution Ŷ The The PKFY PKFY auto-vane auto-vane feature feature delivers delivers optimal the space. and uniform temperature throughout your space. PKFY-P-NAMU-E PKFY-P-NGMU-E PKFY-P-NFMU-E Ŷ All of the performance and design flexibility come in a unit that is remarkably easy to install and maintain. Ŷ Front grille opens for easy filter cleaning plate shipped shipped with with each each Ŷ The The template template and and back-mounting back mounting plate installation a snap. unit makes application Front grille opens out Wall mounted Nominal cooling cap.*1 BTU/h Nominal heating cap.*2 BTU/h P06 P08 P12 P15 P18 P24 P27 P30 P36 P48 P54 P72 P96 0.8HP 6,000 6,700 1.0HP 8,000 9,000 1.3HP 12,000 13,500 1.6HP 15,000 17,000 2.0HP 18,000 20,000 2.5HP 24,000 27,000 2.8HP 27,000 30,000 3.2HP 30,000 34,000 4.0HP 36,000 40,000 5.0HP 48,000 54,000 5.6HP 54,000 60,000 8.0HP 72,000 80,000 10.0HP 96,000 108,000 PKFY-P-NAMU-E PKFY-P-NGMU-E PKFY-P-NFMU-E * Nominal conditions *1, atinthe sheet. *1, *2 *2 are are referable referred to theSpecification Specification sheet. PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E PKFY-P-NAMU-E, NGMU-E, NFMU-E IUPKFY- -H-2 1. SPECIFICATIONS DATA U3 1. SPECIFICATIONS Model PKFY-P06NAMU-E PKFY-P08NAMU-E Power source PKFY-P12NGMU-E PKFY-P15NGMU-E 1-phase 208-230 V 60Hz Cooling capacity *1 BTU / h 6,000 8,000 12,000 (Nominal) *1 kW 1.8 2.3 3.5 4.4 kW 0.03 0.03 0.07 0.07 Power input Current input A Heating capacity *2 BTU / h 0.15 0.15 0.34 0.34 6,700 9,000 13,500 17,000 *2 kW 2.0 2.6 4.0 5.0 Power input kW 0.03 0.03 0.07 0.07 Current input A 0.15 0.15 0.34 (Nominal) External finish 0.34 2.60Y 8.66/0.69 External dimension H x W x D Net weight 0.70Y 8.59/0.97 in. 11-5/8 x 32-3/32 x 6-1/4 11-5/8 x 32-3/32 x 6-1/4 13-13/32 x 39 x 9-9/32 13-13/32 x 39 x 9-9/32 mm 295 x 815 x 158 295 x 815 x 158 340 x 990 x 235 340 x 990 x 235 19 (9) 19 (9) 36 (16) 36 (16) lbs (kg) Heat exchanger FAN 15,000 Cross fin Type x Quantity External in.WG static static pressure press Pa Line flow fan x 1 Line flow fan x 1 Line flow fan x 1 Line flow fan x 1 0.000 (208V) 0.000 (208V) 0.000 (208V) 0.000 (208V) 0 0 0 0 0.000 (230V) 0.000 (230V) 0.000 (230V) 0.000 (230V) 0 0 0 0 0.030 0.030 in.WG Pa Motor type 1-phase induction motor Motor output kW 0.017 0.017 Driving mechanism Direct-driven Airflow rate cfm (Low-Mid1-Mid2-High) m3 / min 173-184-198-208 173-184-198-208 283-335-371-406 283-335-371-406 4.9-5.2-5.6-5.9 4.9-5.2-5.6-5.9 8.0-9.5-10.5-11.5 8.0-9.5-10.5-11.5 L/s 82-87-93-98 82-87-93-98 133-158-175-192 133-158-175-192 32-33-35-36 (208-230V) 32-33-35-36 (208-230V) 32-36-40-42 (208-230V) 32-36-40-42 (208-230V) dB <A> - - - - dB <A> - - - - R410A,R22 CITY MULTI Sound pressure level (Low-Mid1-Mid2-High) dB <A> Noise level (Low-Mid1-Mid2-High) (measured in anechoic room) Insulation material Polyethylene foam Air filter PP honeycomb Protection device Fuse Refrigerant control device LEV Connectable outdoor unit Diameter of Liquid (R410A) refrigerant pipe (O.D.) (R22) Gas (R410A) (R22) Field drain pipe size Drawing R410A CITY MULTI R410A CITY MULTI R410A,R22 CITY MULTI 1/4 (6.35) Flare 1/4 (6.35) Flare 1/4 (6.35) Flare 1/4 (6.35) Flare - - 1/4 (6.35) Flare 1/4 (6.35) Flare 1/2 (12.7) Flare 1/2 (12.7) Flare 1/2 (12.7) Flare 1/2 (12.7) Flare - - 1/2 (12.7) Flare 1/2 (12.7) Flare in. (mm) in. (mm) I.D. 5/8 (16) I.D. 5/8 (16) I.D.13/16 5/8 (16) I.D. (20) I.D.13/16 5/8 (16) I.D. (20) External in. (mm) RG01N979 RG01N979 RG01N981 RG01N981 Wiring RG79N933 RG79N933 RG79N931 RG79N931 - - - - Refrigerant cycle Standard Document Installation Manual,Installation Book attachment Accessory Optional parts External Heater Adaptor - - PAC-YU24HT-F PAC-YU24HT-F Remark Installation Note : Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual. *1 Nominal cooling conditions Indoor : 80degF D.B. / 67degF W.B. (26.7degC D.B. / 19.4degC W.B.) Outdoor : 95degF D.B. (35degC D.B.) Pipe length : 25 ft. (7.6 m) Level difference : 0 ft. (0 m) *2 Nominal heating conditions Unit converter 70degF D.B. kcal/h = kW x 860 (21.1degC D.B.) BTU/h = kW x 3,412 47degF D.B. / 43degF W.B. cfm = m3/min x 35.31 (8.3degC D.B. / 6.1degC W.B.) lbs = kg / 0.4536 25 ft. (7.6 m) 0 ft. (0 m) *Above specification data is subject to rounding variation. *Due to continuing improvement, above specification may be subject to change without notice. Ref.: Spec_PKFY-P06-15NAMU,NGMU-E PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E PKFY-P-NAMU-E, NGMU-E, NFMU-E IUPKFY- -H-3 PKFY-P-NAMU-E PKFY-P-NGMU-E PKFY-P-NFMU-E Ventilation Air: Providing sufficient ventilation air is an important part of every building design. ASHRAE standard 62 provides the minimum ventilation air requirements. Also check local codes. 1. SPECIFICATIONS DATA U3 Model PKFY-P18NFMU-E PKFY-P24NFMU-E Power source PKFY-P30NFMU-E 1-phase 208-230 V 60Hz Cooling capacity *1 BTU / h 18,000 24,000 (Nominal) *1 kW 5.3 7.0 8.8 kW 0.09 0.09 0.12 Power input Current input A Heating capacity *2 BTU / h 30,000 0.44 0.44 0.58 20,000 27,000 34,000 10.0 *2 kW 5.9 7.9 Power input kW 0.09 0.09 0.12 Current input A 0.44 0.44 0.58 in. 13-13/32 x 55-1/8 x 9-9/32 13-13/32 x 55-1/8 x 9-9/32 13-13/32 x 66-5/32 x 9-9/32 340 x 1,400 x 235 340 x 1,400 x 235 340 x 1,680 x 235 53 (24) 53 (24) (Nominal) External finish 3.4Y 7.7/0.8 External dimension H x W x D mm Net weight lbs (kg) 62 (28) Heat exchanger FAN Cross fin Type x Quantity External in.WG static static pressure press Pa Line flow fan x 2 Line flow fan x 2 Line flow fan x 2 0.000 (208V) 0.000 (208V) 0.000 (208V) 0 0 0 0.000 (230V) 0.000 (230V) 0.000 (230V) 0 0 0 in.WG Pa Motor type 1-phase induction motor Motor output kW 0.045 0.045 0.070 Driving mechanism Direct-driven Airflow rate cfm 494-636 494-636 777-989 (Low-High) m3 / min 14.0-18.0 14.0-18.0 22.0-28.0 233-300 233-300 367-467 Sound pressure level (Low-High) Noise level (Low-High) dB <A> L/s 39-45 (208-230V) 39-45 (208-230V) 46-49 (208-230V) (measured in anechoic room) dB <A> - - - dB <A> - - - Insulation material Polyethylene foam Air filter PP honeycomb Protection device Fuse Refrigerant control device LEV Connectable outdoor unit R410A,R22 CITY MULTI Diameter of Liquid (R410A) refrigerant pipe (O.D.) (R22) Gas (R410A) (R22) Field drain pipe size Drawing in. (mm) in. (mm) 5/8 (15.88) Flare 5/8 (15.88) Flare 5/8 (15.88) Flare 5/8 (15.88) Flare I.D. 13/16 (20) I.D. 13/16 (20) I.D. 13/16 (20) RG01N980-1 RG01N980-1 RG01N980-2 RG79N931 RG79N931 RG79N931 - - - Wiring Refrigerant cycle attachment Accessory Optional parts 3/8 (9.52) Flare 3/8 (9.52) Flare 1/2 (12.7) Flare in. (mm) Document 3/8 (9.52) Flare 3/8 (9.52) Flare 5/8 (15.88) Flare External Standard 1/4 (6.35) Flare 3/8 (9.52) Flare Installation Manual,Installation Book External Heater Adaptor PAC-YU24HT-F PAC-YU24HT-F PAC-YU24HT-F L-Shaped Connection Pipe(15.88) PAC-SC84PI-E PAC-SC84PI-E PAC-SC84PI-E PKFY-P-NAMU-E PKFY-P-NGMU-E PKFY-P-NFMU-E Remark Ventilation Air: Providing sufficient ventilation air is an important part of every building design. ASHRAE standard 62 provides the minimum ventilation air requirements. Also check local codes. Installation Note : Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation Manual. *1 Nominal cooling conditions Indoor : 80degF D.B. / 67degF W.B. (26.7degC D.B. / 19.4degC W.B.) Outdoor : 95degF D.B. (35degC D.B.) Pipe length : 25 ft. (7.6 m) Level difference : 0 ft. (0 m) *2 Nominal heating conditions Unit converter 70degF D.B. kcal/h = kW x 860 (21.1degC D.B.) BTU/h = kW x 3,412 47degF D.B. / 43degF W.B. cfm = m3/min x 35.31 (8.3degC D.B. / 6.1degC W.B.) lbs = kg / 0.4536 25 ft. (7.6 m) 0 ft. (0 m) *Above specification data is subject to rounding variation. *Due to continuing improvement, above specification may be subject to change without notice. Ref.: Spec_PKFY-P18-30NFMU-E PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E PKFY-P-NAMU-E, NGMU-E, NFMU-E IUPKFY- -H-4 31/32(24.4) 2-1/8(54) C Detailed figure dwg (ABC) (Knock out hole) 15 ) 8) 1-25/32 (45) B PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E PKFY-P-NAMU-E, NGMU-E, NFMU-E 3-19/32 (91.5) 3/32(2.5) 13/32(10) 1-11/32(34) ) 6(R8 R5/1 A ) Knock out hole for under piping Knock out hole of 5/8(16) remocon wiring (R 12 15) /32(R R19 R5/1 6(R 8) Knock out hole for left piping 19 /3 2( R /16 R5 R B 17-23/32(450) Gas pipe 20-25/32(520) Liquid pipe 1-25/32(45) 1(25.5) Air intake Air intake (Direction) Terminal block 1/2(13) Knock out hole for remocon wiring 0 12-29/32(328) 12-29/32 (328) 16-1/32(407.5) A 2-25/32(70.3) installation plate 3/16(5) Air outlet 6-7/32(158) 3-17/32(90) 4-1/32(102.5) 4-7/8(124) 19/32(15) 6-1/4(159) 5-1/4(133) 4-13/16(122.5) 3-27/32(97.5) 3-11/32(85) 2-27/32(72.5) 2-3/8(60) 1-7/8(47.5) 7/8(22.5) 3-11/32(85) 8-27/32(225) 8-1/16(205) 6-7/8(175) 6-11/16(170) 3-15/16(100) or more 6-3/32(155) 7-3/32(180) 7-15/32(190) 10-1/4(260) 9-1/4(235) 3-11/32(85) 8-27/32(225) 6-5/8(168) 5-5/16(135) 4-29/32(125) 4-11/32(110) 5-1/8(130) or more 1-3/8(35) 13/32(10) 0 1-3/32(27.5) 1-9/16(40) 2-3/32(53) 2-9/16(65) 3-7/16(87) 4-7/16(113) 5-1/32(128) Sleeve Through hole 3.Sleeves are available on the market. I.D.5/8"(16) 1/4 F 1/2 F Liquid pipe Gas pipe Drain pipe Refrigerant piping Notes 1.Use M10 or W3/8 screw for installation plate. 2.Extension piping side. Supporting piece Installation space Knock of hole 13/32(10) 0 13/32(10) 4-23/32(120) 1-31/32(50) 1-23/32(44) 16-1/32(407.5) 3/16x1-15/32 (4.5x37) 4 holes 3/16x1-9/16 (4.5x40) 4 holes Details of installation plate 10-1/4(260) 6-11/16(170) 6-7/8(175) 8-1/16(205) 9-1/4(235) Installation plate Wiring entrance holes Air outlet (Direction) 1-11/16(42.5) Knock out hole of right piping 4-9/16(116) 4-11/32(110) 5-3/4 (146) 2-3/8 (60) 1-11/ 32(34) intake Air outlet 26-31/32(660) (Drain pipe total 29-29/32(760)) Air 24-13/16(630) 27-3/8(695) 5-29/32(150) 1-5/8(40.5) Air intake 2-3/8(60) 3/32(2.5) Air outlet 9-3/4(247.5) 1-15/32(37.4) 7-15/32(190) 6-1/4(159) 6-3/32(155) 4-23/32(120) 11-23/32(298) 1-3/16(30) 0 1-3/16(30) 1-3/4(45) 25/32(20) or more 32-3/32(815) 1-31/32(50) 11-5/8(295) ) 27/32(21.5) 13/32(10) 1/2(13) 1-31/32 (50) 2-1/8(54) of more left piping left-rear piping 30-13/16(783) 5/8 (16) C 15 (R 9 (R R1 /32 13/32(10) PKFY-P06,08NAMU-E PKFY-P-NAMU-E PKFY-P-NGMU-E PKFY-P-NFMU-E /3 2 5 R1 3/32(2.5) 5/32(4) Air intake 7-3/32(180) 11-23/32(298) Installation plate balance point hole 2. EXTERNAL DIMENSIONS DATA U3 2. EXTERNAL DIMENSIONS Drw. : IU-RG01N979 Unit : in(mm) IUPKFY- -H-5 11-5/8(295) 15-15/16(405) 16-17/32(420) 14-3/16(360) 19-1/2(495) Less than 5-1/8(130) 1-13/16(30) or more Unit center Installation plate balance point hole R5 2. 5) Right-rear piping hole 13-3/8(340) 27-3/4(705) Air outlet Filter grip 9-1/4(235) 7-15/32(190) 6-5/16(160) 27-9/16(700) (Flexible hose total length 31-1/2(800)) 3/16(5) 15-9/16(395) 2-3/4(70) 22-7/8(581) 17-11/16(449) Front view (top open the grille) 15-3/4(400) 9-3/16(233) 8-27/32(225) Auto vane 11-1/32(280) Air intake 12-Louvers (manual) Liquid pipe 1/4 F Gas pipe 1/2 F Drain hose I.D.1(25) (Left side piping 1-3/8(35) installation) 10-23/32(272) 12-7/32(310) 9-1/16(230) 7-15/32(190) 5-1/8(130) 0 1-3/8(35) 2-5/32(55) 3-5/32(80) 1-31/32(50) Lower side 39(990) 3-5/32(80) 1-9/16(40) 1-3/8(35) Less than 19/32(15) Knock out hole for right piping Refrigerant pipe.Drain pipe. Wiring hole 1-5/16(33) 2-1/8(54) 3-3/8(86) 6-1/32(153) (Right side piping installation) Wiring entrance holes Service panel (Power supply access) Knock out hole for under piping Refrigerant piping.Drain pipe. Wiring hole 9-1/4(235) 2-3/8(60) Address board Right side 13/16(21) 28-5/32(715) Air intake 13-3/8(340) Air intake 3-1/8(80) Front view PKFY-P12,15NGMU-E PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E PKFY-P-NAMU-E, NGMU-E, NFMU-E Through hole 6( Knock out hole for right-rear piping .5) 6(R52 R2-1/1 R2 1 1/ Knock out hole for left-rear piping Left-rear piping hole for tapping screw for bolts 11-13/16(300) (Necessary clearance for Unit installation) 3-3/4(95) Details of installation plate 9-21/32(245) 13/16(21) 8-1/16(205) 6-11/16(170) 7-15/32(190) 1-31/32(50) or more 5-29/32(150) 2-3/8(60) 19-1/2(495) 9-21/32(245) 2-3/4(70) 10-1/4(260) 5-29/32(150) or more 7-15/32(190) 7-3/32(180) or more 2-15/16(75) 1-1/4(32) 25/32(20) 0 1-3/8(35) .5) ( Right side 12-19/32(320) 13-19/32(345) 2-3/32(53) 3-1/8(79) Service space required around indoor unit 16-23/32(425) 7-25/32(198) Air intake 2-3/8(60) 1(25) Left side 11-1/32(280) Knock out hole for left piping Refrigerant pipe.Drain pipe.Wiring hole. 5-5/16(135) R5 2 /16 -1 R2 2- .5 ) 9-1/16(230) 8-9/32(210) R 52 1-7/32(31) (R 1 6 /1 0 1-11/32(34) 9-21/32(245) 2-3/4(70) PKFY-P-NAMU-E PKFY-P-NGMU-E PKFY-P-NFMU-E 2. EXTERNAL DIMENSIONS DATA U3 Drw. : IU-RG01N981 Unit : in(mm) IUPKFY- -H-6 3-15/16(100) 1-17/32(39) 1-15/32(37) 2-29/32(74) 1-9/16(39) 1-3/16(30) PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E PKFY-P-NAMU-E, NGMU-E, NFMU-E for bolts for tapping screws 23/32(18) 35-7/16(900) 23/32(18) 3-19/32(91) 12-1/4(6) holes for tapping screws C 3-17/32(90) Range for left rear piping hole 24-1/32(610) 12-3/8(314) 3/4(19) 11-7/32(285) 9-21/32(245) 13-3/8(340) Rear piping hole 1-25/32(45) 1-25/32(45) 9-1/4(235) Knock out hole for under-piping Refrigerant pipe /Drain pipe 21-23/32(552) Air outlet 44-3/32(1120) 9-7/16(240) Louvers(Manual) Wiring entrance holes 43-11/16(1110) Drain hose 21-23/32(552) Air outlet 9-1/4(235) Drain hose I.D.1(25) 42-29/32(1090) Air intake 55-1/8(1400) Lower side Auto vanes Front view 9-1/4(235) 1-25/32(45) Under panel(Removable at left-hand side piping) Drain hose for left-hand side piping 31/32(25) Knock out hole for left piping Left side Drainage range on right-hand side A Less than 9-27/32(250) 2-29/32(74) 17-29/32(455) Unit center 38-31/32(990) 1-1/4(32) 1-15/32(37) 1-3/16(30) 8-27/32(225) 9-7/16(240) 7-3/32(180) 11-1/32(280) Wall fixture Drainage range on left hand side B 3-27/32(98) Details of installation plate A Knock out hole for wiring 9-27/32(250) or more 9-1/4(235) 7-3/4(197) 2 Terminal block B 1 3/8 F 5/8 F 4-3/8(111) 4-7/32(107) Drain hose Bolt Less than 19/32(15) Knock out hole for right piping C Through hole on the market. Sleeve 1 Liquid pipe 2 Gas pipe 15/16(24) 2-5/32(55) 4-23/32(120) 7-7/32(183) 9-1/4(235) Right side PKFY-P18,24NFMU-E PKFY-P-NAMU-E PKFY-P-NGMU-E PKFY-P-NFMU-E 5/32(4) 9-27/32(250) or more 1-15/32(37) 2-9/16(65) 1-3/16(30) or more 1-17/32(39) 3-15/16(100) 5/32(4) 1-31/32(50) or more 7-1/4(184) 1-3/16(30) Air outlet 13/32(10) 1-3/16(30) 1-3/16(30) Air intake 1-5/32(29) 3-1/8(80) Service space required around indoor unit 11-1/32(280) 2-3/8(60) 2-15/32(62.5) 1/2(13) 1-5/16(34) 1-7/16(36) 1-21/32(42) 2-9/32(58) Top side 2. EXTERNAL DIMENSIONS DATA U3 Drw. : IU-RG01N980-1 Unit : in(mm) IUPKFY- -H-7 1-17/32(39) 3-15/16(100) A 11-5/8(295) 2-9/16(65) 1-15/32(37) 50(1270) PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E PKFY-P-NAMU-E, NGMU-E, NFMU-E for tapping screws A Less than 5-29/32(150) 23-7/16(595) Front view 1-25/32(45) 9-1/4(235) 3-9/16(90) 9-1/4(235) Auto vanes 27-5/16(694) Air outlet Rear piping hole 1-25/32(45) 9-1/4(235) 66-1/8(1680) 1-25/32(45) 9-1/4(235) Louvers(Manual) 27-5/16(694) Air outlet Knock out hole for under-piping Refrigerant pipe /Drain pipe Under panel(Removable at left-hand side piping) 55-1/8(1400) 43-11/16(1110) Drain hose 9-1/4(235) Right side 2 Terminal block B Through hole 3/8 F 5/8 F 4-3/8(111) 4-1/32(102) Bolt on the market. Sleeve C Less than 9/16(15) 1 Liquid pipe 2 Gas pipe 1 15/16(24) 2-5/32(55) 4-23/32(120) 7-7/32(183) 9-7/16(240) Knock out hole for right piping 9-1/4(235) Drain hose I.D.1(25) Wiring entrance holes 53-15/16(1370) Air intake 1-25/32(45) Lower side Drain hose for left-hand side piping 31/32(25) Range for left rear piping hole 29-17/32(750) 12-3/8(314) 3-19/32(91) 3/4(19) 11-7/32(285) Knock out hole for left piping Left side 9-21/32(245) Drainage range on right-hand side 2-29/32(74) C 35-7/16(900) Unit center 1-1/4(32) 1-15/32(37) 8-27/32(225) 9-7/16(240) 7-3/32(180) 11-1/32(280) 23/32(18) 23/32(18) Wall fixture Air outlet 1-3/16(30) 9-27/32(250) or more Top side PKFY-P30NFMU-E for bolts for tapping screws 3-27/32(98) Unit out line 2-29/32(74) 1-17/32(39) 1-15/32(37) 1-3/16(30) B Knock out hole for wiring 9-27/32(250) or more 1-31/32(50) or more Drainage range on left hand side 5/32(4) 1-3/16(30) or more 3-15/16(100) 5/32(4) Air intake 1-17/32(39) Service space required around indoor unit 13-3/8(340) 1-3/16(30) 1-3/16(30) 1-5/32(29) 3-5/32(80) 7-1/4(184) 13/32(10) 1-3/16(30) 11-1/32(280) 2-3/8(60) 2-15/32(62.5) 1/2(13) 7-3/4(197) 1-5/16(34) 1-7/16(36) 1-21/32(42) 2-9/32(58) PKFY-P-NAMU-E PKFY-P-NGMU-E PKFY-P-NFMU-E 2. EXTERNAL DIMENSIONS DATA U3 Drw. : IU-RG01N980-2 Unit : in(mm) IUPKFY- -H-8 3. ELECTRICAL WIRING DIAGRAMS DATA U3 3. ELECTRICAL WIRING DIAGRAMS PKFY-P06,08NAMU-E Drw. : IU-RG79N933 [ LEGEND ] SYMBOL NAME SYMBOL CIRCUIT BOARD (ADDRESS) A. B P. B NAME SYMBOL LEV LINEAR EXPANSION VALVE MODE SELECTION C CAPACITOR (FAN MOTOR) MF FAN MOTOR SW5 VOLTAGE SELECTION F.C FAN PHASE CONTROL MV VANE MOTOR SW11 ADDRESS SETTING 1ST DIGIT FUSE FUSE (6A/250V) TB2 SW12 ADDRESS SETTING 2ST DIGIT ZNR VARISTOR TB5 TERMINAL BLOCK SW14 CONNECTION No. TH21 THERMISTOR SW1 SWITCH M. B TRANSMISSION TH22 REMOTE SWITCH CENTRALLY CONTROL CN51 TH23 REMOTE INDICATION CN52 CAPACITY CODE MODE SELECTION 5 A.B 5VDC SUPPLY SW5 (RED) 4 ADDRESS 3 CN43 2 230V SW1 1 3RD 2ND 1ST DIGIT DIGIT DIGIT NO. LED2 YLW ORN BRN 1 2 CN2M M-NET 1 2 3 (BLU) 1 2 CN3A CN20 (BLU) INTAKE (RED) CN53M POWER BOARD 1 2 3 4 5 (RED) BLK YLW ORN RED BRN SW2 CN35M POWER BOARD 1 2 3 (BLU) See fig : 1 M.B 1 2 3 CN35P MICON BOARD (BLU) 5 4 3 2 1 CN53P F.C MICON BOARD (RED) 1 2 3 4 5 6 FAN (GRN) BLU BLU 1 2 1 2 3 4 5 SW3 5 4 3 2 CONNECTION 1 SW14 0 Notes: 1 2 CN29 CN21 GAS LIQUID (BLK) (WHT) 1 2 3 4 1 2 3 4 5 6 7 8 CN51 CN52 CENTRALLY REMOTE CN42 CN81 CONTROL INDICATION ADDRESS ADDRESS (WHT) (GRN) (RED) (RED) 8 12345678910 1234 SW12 SW11 0 0 1 2 3 4 5 1 2 3 1 2 3 CN32 CN34 REMOTE (GRN) SWITCH (WHT) ON OFF 12345678910 (RED) 8 ADDRESS 7 CN82 6 4 CN5V (BLU) RED CN60 LEV (WHT) ORN 1 2 3 4 5 6 1 2 3 4 5 S(SHIELD) MF YLW GRY BRN RED BLU ORN YLW WHT YLW ORN BLU RED BRN 6 M1 M2 TB5 1 2 TB2 GRN/YLW MV RED LEV TO OUTDOOR UNIT BC CONTROLLER ME REMOTE CONTROLLER DC24-30V TO MA-REMOTE CONTROLLER DC8.7-13V TH23 TH22 TH21 ORN SW3 BLK SWITCH BLU WHT SW2 208V POWER SUPPLY INDOOR CONTROLLER BOARD CONNECTOR CN32 ON OFF NAME INDOOR POWER BOARD TO NEXT INDOOR UNIT L1 L2 GR PULL BOX FUSE (15A) BREAKER (15A) 1 2 3 POWER SUPPLY ~/N 208-230V 60Hz CND (RED) C ZNR FUSE 250V 6A LED1 P.B 1.At servicing for outdoor unit, always follow the wiring diagram of outdoor unit. 2.In case of connecting MA-Remote controller, please connect MA remote controller cable in an accessory to the connector 1 2 . (Remote controller wire is non-polar.) 3.In case of using M-NET, please connect to TB5. (Transmission line is non-polar.) 4.Symbols used in wiring diagram above are, : terminal block, : connecter, : direct wire connection. 5.Please set the switch SW5 according to the power supply voltage. Set SW5 to 230V side when the power supply is 230 volts. When the power supply is 208 volts, set SW5 to 208V side. MODELS SW2 ON PKFY-P06NAMU-E OFF 6. The setting of the SW2 dip switches differs in the capacity for the detail, refer to the fig : 1. 1234 ON PKFY-P08NAMU-E OFF 1234 LED on indoor board for service Mark Meaning Main power supply LED2 Power supply for MA -Remote controller Function PKFY-P-NAMU-E PKFY-P-NGMU-E PKFY-P-NFMU-E LED1 PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E PKFY-P-NAMU-E, NGMU-E, NFMU-E IUPKFY- -H-9 3. ELECTRICAL WIRING DIAGRAMS DATA U3 PKFY-P12,15NGMU-E PKFY-P18,24,30NFMU-E Drw. : IU-RG79N934 [LEGEND] SYMBOL I. B NAME SYMBOL INDOOR CONTROLLER BOARD NAME C CAPACITOR (FAN MOTOR) SYMBOL NAME TH23 THERMISTOR A. B SW1 SWITCH HEATER LEV LINEAR EXPANSION VALVE CN32 REMOTE SWITCH MF FAN MOTOR (WITH INNER THERMOSTAT) CN51 CENTRALLY CONTROL MV VANE MOTOR CN52 REMOTE INDICATION P.B INDOOR POWER BOARD SW5 VOLTAGE SELECTION CN24 CONNECTOR CIRCUIT BOARD (ADDRESS) MODE SELECTION F.C FAN PHASE CONTROL TB2 TERMINAL POWER SUPPLY SW11 ADDRESS SETTING 1ST DIGIT FUSE FUSE (6A/250V) TB5 BLOCK TRANSMISSION SW12 ADDRESS SETTING 2ND DIGIT SW2 SWITCH MA-REMOTE CONTROLLER SW14 CONNECTION No. SWC OPTION SELECTOR CAPACITY CODE TB15 SW3 MODE SELECTION TH21 SW4 MODEL SELECTION X4 AUX. RELAY (FAN MOTOR) ZNR VARISTOR THERMISTOR TH22 TO NEXT INDOOR UNIT P.B AC208-230V MF RED WHT BLK (RED) CNSK 3 2 1 BLK WHT C I.B FAN (WHT) 1 3 5 CND (RED) 1 3 X4 F.C X4 LED1 DRAIN CN31(WHT) 3 2 1 (YLW) HEATER CN24 REMOTE CENTRALLY INDICATION CONTROL CN52(GRN) CN51(WHT) 5 1 5 LEV CN60(WHT) BRN RED ORN YLW PNK BLU MV ON OFF PKFY-P-NAMU-E PKFY-P-NGMU-E PKFY-P-NFMU-E 3RD 2ND 1ST DIGIT DIGIT DIGIT CN2D 1 (WHT) 2 BLK WHT M-NET 1 CN2M 2 (BLU) BLU BLU CN3A 1 (BLU) 3 ORN ORN POWER SUPPLY ~/N 208-230V 60HZ TB5 TO OUTDOOR UNIT M2 BC CONTROLLER ME REMOTE CONTM1 ROLLER DC24-30V S(SHIELD) TB15 1 2 TO MA-REMOTE CONTROLLER DC8.7-13V BRN RED BLU ORN YLW WHT 5 4 3 2 CONNECTION 1 NO. PKFY-P12NGMU-E ON OFF PKFY-P15NGMU-E ON OFF PKFY-P18NFMU-E ON OFF PKFY-P24NFMU-E ON OFF PKFY-P30NFMU-E ON OFF SW14 0 TH21 TH22 TH23 SW2 Models 8 7 1 0 BREAKER (15A) (RED) (WHT) (BLK) SW4 ON INTAKE LIQUID GAS CN20 CN21 CN29 OFF 2 1 2 1 2 1 LED2 12345 LEV ADDRESS CN82(RED) 6 SW12 SW11 SWC 0 4 4 3 ADDRESS 2 CN43(RED) 12345678910 FUSE (15A) 5VDC SUPPLY 230V SW1 3 PULL BOX 6 SW5 208V REMOTE SWITCH CN32(WHT) 1 6 5 4 3 2 1 1 ADDRESS ADDRESS SW3 SW2 CN81(RED) CN42(RED) ON 8 7 6 5 4 3 2 1 4 3 2 1 OFF 123456 12345678910 8 A.B TRANS ZNR VANE CN6V(GRN) 6 5 4 3 2 1 DC13.1V (WHT) CN2S 2 1 1 3 CNDK (RED) FUSE 250V 6A TB2 RED L1 BLU L2 GRN/YLW GR 123456 123456 123456 123456 123456 SW3 ON OFF ON OFF ON OFF ON OFF ON OFF 1 2 3 4 5 6 7 8 910 1 2 3 4 5 6 7 8 910 1 2 3 4 5 6 7 8 910 1 2 3 4 5 6 7 8 910 1 2 3 4 5 6 7 8 910 SW4 ON OFF ON OFF ON OFF ON OFF ON OFF 12345 12345 12345 12345 12345 Notes: 1. At servicing for outdoor unit, always follow the wiring diagram of outdoor unit. 2. In case of using MA-Remote controller, please connect to TB15. (Remote controller wire is non-polar.) 3. In case of using M-NET, please connect to TB5. (Transmission line is non-polar.) 4. Symbol [S] of TB5 is the shield wire connection. 5. Symbols used in wiring diagram above are, :terminal block, :connecter. 6. The setting of the SW2/SW3/SW4 dip switches differs in the capacity for the detail, refer to the fig : 7. Please set the switch SW5 according to the power supply voltage. Set SW5 to 230V side when the power supply is 230 volts. When the power supply is 208 volts, set SW5 to 208V side. LED on indoor board for service Mark Meaning LED1 Main power supply LED2 Power supply for MA -Remote controller Function PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E PKFY-P-NAMU-E, NGMU-E, NFMU-E IUPKFY-10 - H - 10 4. SOUND PRESSURE LEVELS DATA U3 4-1. 4-1.Sound SoundPressure PressureLevels Levels 4. SOUND LEVELS Wall mounted Operating sound level (Low-Middle2-Middle1-High) Unit Wall 3-1/4 ft (1.0m) Model 3-1/4 ft (1.0m) Unit : dB(A) Sound pressure level (A weighted) PKFY-P06,08NAMU-E 32-33-35-36 PKFY-P12,15NGMU-E 32-36-40-42 PKFY-P18,24NFMU-E 39-45 PKFY-P30NFMU-E 46-49 Measurement location 4-2. 4-2.NC NCCurves curves PKFY-P06,08NAMU-E PKFY-P12,15NGMU-E PKFY-P18,24NFMU-E External Static Pressure: 0Pa Power Source: 208-230V, 60Hz External Static Pressure: 0Pa Power Source: 208-230V, 60Hz External Static Pressure: 0Pa Power Source: 208-230V, 60Hz 70.0 High Low Middle1 Middle2 65.0 60.0 70.0 60Hz 60Hz 60Hz 60Hz NC-60 55.0 50.0 NC-50 45.0 40.0 NC-40 35.0 30.0 NC-30 25.0 20.0 15.0 10.0 High Low Middle1 Middle2 65.0 60.0 70.0 60Hz 60Hz 60Hz 60Hz NC-60 55.0 50.0 NC-50 45.0 40.0 NC-40 35.0 30.0 NC-30 25.0 20.0 Approximate minimum audible limit on continuous noise 63 125 250 NC-20 500 1k 2k 4k 8k Octave band center frequencies <Hz> 15.0 10.0 60Hz 60Hz 60.0 NC-60 55.0 50.0 NC-50 45.0 40.0 NC-40 35.0 30.0 NC-30 25.0 20.0 Approximate minimum audible limit on continuous noise 63 125 250 NC-20 500 1k 2k 4k 8k Octave band center frequencies <Hz> Ref.:NC_PKFY-P06,08NAMU-E High Low 65.0 15.0 10.0 Approximate minimum audible limit on continuous noise 63 125 250 NC-20 500 1k 2k 4k 8k Octave band center frequencies <Hz> Ref.:NC_PKFY-P12,15NGMU-E Ref.:NC_PKFY-P18,24NFMU-E PKFY-P30NFMU-E External Static Pressure: 0Pa Power Source: 208-230V, 60Hz 70.0 High Low 65.0 60Hz 60Hz 60.0 NC-60 55.0 50.0 NC-50 45.0 40.0 NC-40 35.0 30.0 NC-30 PKFY-P-NAMU-E PKFY-P-NGMU-E PKFY-P-NFMU-E 25.0 20.0 15.0 10.0 Approximate minimum audible limit on continuous noise 63 125 250 NC-20 500 1k 2k 4k 8k Octave band center frequencies <Hz> Ref.:NC_PKFY-P30NFMU-E PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E PKFY-P-NAMU-E, NGMU-E, NFMU-E IUPKFY-11 - H - 11 5. CAPACITY TABLES 5-1. Cooling Capacity in Combination with PUHY-HP72,96THMU; -HP144,192TSHMU VII.Wall 1. CAPACITY mounted TABLES PKFY-P-NAMU/NGMU/NFMU-E Model Outdoor size air temp. 06 08 12 15 PKFY-P-NAMU-E PKFY-P-NGMU-E PKFY-P-NFMU-E 18 24 30 CA : Capacity(kW) SHC : Sensible Heat Capacity(kW) Indoor air temp. 21.7degC D.B. 22.8degC D.B. 25degC D.B. 27.2degC D.B. 27.8degC D.B. 30degC D.B. 32.2degC D.B. 15degC W.B. 16.1degC W.B. 17.8degC W.B. 18.9degC W.B. 20degC W.B. 22.2degC W.B. 23.9degC W.B. degC D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC 20.0 1.6 1.3 1.7 1.3 1.8 1.3 1.9 1.4 2.0 1.4 2.1 1.4 2.2 1.4 22.8 1.6 1.3 1.7 1.3 1.8 1.3 1.9 1.4 2.0 1.4 2.1 1.4 2.2 1.4 25.0 1.6 1.3 1.7 1.3 1.8 1.3 1.9 1.4 2.0 1.4 2.1 1.3 2.2 1.4 27.8 1.6 1.3 1.7 1.3 1.8 1.3 1.9 1.4 2.0 1.4 2.1 1.3 2.2 1.4 30.0 1.6 1.2 1.7 1.3 1.8 1.3 1.9 1.4 1.9 1.4 2.0 1.3 2.1 1.3 32.8 1.6 1.2 1.7 1.3 1.7 1.3 1.8 1.4 1.9 1.3 2.0 1.3 2.1 1.3 35.0 1.6 1.2 1.6 1.2 1.7 1.3 1.8 1.4 1.9 1.3 1.9 1.3 2.0 1.3 37.8 1.5 1.2 1.6 1.2 1.7 1.3 1.8 1.4 1.8 1.3 1.9 1.3 2.0 1.3 40.0 1.5 1.2 1.6 1.2 1.7 1.3 1.7 1.4 1.8 1.3 1.9 1.3 1.9 1.3 43.3 1.5 1.2 1.6 1.2 1.6 1.2 1.7 1.3 1.7 1.3 1.8 1.2 1.9 1.3 20.0 2.0 1.6 2.2 1.6 2.3 1.7 2.5 1.8 2.6 1.7 2.7 1.7 2.9 1.7 22.8 2.0 1.6 2.2 1.6 2.3 1.7 2.5 1.8 2.6 1.7 2.7 1.7 2.9 1.7 25.0 2.0 1.6 2.2 1.6 2.3 1.7 2.5 1.8 2.5 1.7 2.7 1.7 2.8 1.7 27.8 2.0 1.6 2.2 1.6 2.3 1.6 2.4 1.8 2.5 1.7 2.6 1.7 2.8 1.7 30.0 2.0 1.6 2.1 1.6 2.3 1.6 2.4 1.8 2.5 1.7 2.6 1.7 2.7 1.7 32.8 2.0 1.6 2.1 1.6 2.2 1.6 2.3 1.7 2.4 1.7 2.5 1.6 2.6 1.7 35.0 2.0 1.6 2.1 1.6 2.2 1.6 2.3 1.7 2.4 1.7 2.5 1.6 2.6 1.6 37.8 2.0 1.5 2.1 1.5 2.2 1.6 2.3 1.7 2.3 1.6 2.4 1.6 2.5 1.6 40.0 2.0 1.5 2.0 1.5 2.1 1.6 2.2 1.7 2.3 1.6 2.4 1.6 2.5 1.6 43.3 1.9 1.5 2.0 1.5 2.1 1.6 2.2 1.7 2.2 1.6 2.3 1.6 2.4 1.6 20.0 3.1 2.5 3.3 2.6 3.5 2.7 3.7 2.9 3.9 2.8 4.1 2.8 4.4 2.8 22.8 3.1 2.5 3.3 2.6 3.5 2.7 3.7 2.9 3.9 2.8 4.1 2.8 4.4 2.8 25.0 3.1 2.5 3.3 2.6 3.5 2.7 3.7 2.9 3.9 2.8 4.1 2.7 4.3 2.8 27.8 3.1 2.5 3.3 2.6 3.5 2.7 3.7 2.9 3.8 2.8 4.0 2.7 4.2 2.8 30.0 3.1 2.5 3.3 2.6 3.4 2.6 3.6 2.9 3.7 2.7 3.9 2.7 4.1 2.7 32.8 3.0 2.5 3.2 2.5 3.4 2.6 3.6 2.8 3.7 2.7 3.9 2.7 4.0 2.7 35.0 3.0 2.5 3.2 2.5 3.4 2.6 3.5 2.8 3.6 2.7 3.8 2.6 4.0 2.7 37.8 3.0 2.5 3.1 2.5 3.3 2.6 3.4 2.8 3.5 2.7 3.7 2.6 3.9 2.6 40.0 3.0 2.5 3.1 2.5 3.3 2.6 3.4 2.8 3.5 2.6 3.6 2.6 3.8 2.6 43.3 3.0 2.5 3.0 2.5 3.2 2.5 3.3 2.7 3.4 2.6 3.5 2.5 3.7 2.6 20.0 3.9 3.0 4.2 3.1 4.4 3.2 4.7 3.5 4.9 3.4 5.2 3.3 5.5 3.4 22.8 3.9 3.0 4.2 3.1 4.4 3.2 4.7 3.5 4.9 3.4 5.2 3.3 5.5 3.4 25.0 3.9 3.0 4.2 3.1 4.4 3.2 4.7 3.5 4.9 3.3 5.1 3.3 5.4 3.3 27.8 3.9 3.0 4.1 3.1 4.4 3.2 4.6 3.4 4.8 3.3 5.0 3.2 5.3 3.3 30.0 3.8 3.0 4.1 3.1 4.3 3.2 4.6 3.4 4.7 3.3 4.9 3.2 5.2 3.3 32.8 3.8 3.0 4.0 3.0 4.3 3.1 4.5 3.4 4.6 3.2 4.8 3.2 5.1 3.2 35.0 3.8 3.0 4.0 3.0 4.2 3.1 4.4 3.3 4.5 3.2 4.8 3.1 5.0 3.2 37.8 3.8 3.0 3.9 3.0 4.1 3.1 4.3 3.3 4.4 3.2 4.7 3.1 4.9 3.1 40.0 3.8 3.0 3.9 3.0 4.1 3.1 4.3 3.3 4.4 3.1 4.6 3.1 4.8 3.1 43.3 3.7 3.0 3.8 2.9 4.0 3.0 4.2 3.2 4.3 3.1 4.4 3.0 4.6 3.1 20.0 4.7 3.9 5.0 3.9 5.3 4.1 5.7 4.4 5.9 4.3 6.2 4.2 6.6 4.3 22.8 4.7 3.9 5.0 3.9 5.3 4.1 5.7 4.4 5.9 4.3 6.2 4.2 6.6 4.3 25.0 4.7 3.9 5.0 3.9 5.3 4.1 5.7 4.4 5.9 4.3 6.2 4.2 6.5 4.3 27.8 4.7 3.9 5.0 3.9 5.3 4.1 5.6 4.4 5.7 4.2 6.1 4.1 6.4 4.2 30.0 4.6 3.9 4.9 3.9 5.2 4.0 5.5 4.4 5.7 4.2 6.0 4.1 6.2 4.2 32.8 4.6 3.8 4.9 3.9 5.1 4.0 5.4 4.3 5.6 4.1 5.8 4.1 6.1 4.1 35.0 4.6 3.8 4.8 3.9 5.1 4.0 5.3 4.3 5.5 4.1 5.7 4.0 6.0 4.1 37.8 4.5 3.8 4.7 3.8 5.0 3.9 5.2 4.2 5.4 4.1 5.6 4.0 5.9 4.0 40.0 4.5 3.8 4.7 3.8 4.9 3.9 5.1 4.2 5.3 4.0 5.5 3.9 5.7 4.0 43.3 4.5 3.8 4.6 3.8 4.8 3.9 5.0 4.2 5.1 4.0 5.4 3.9 5.6 4.0 20.0 6.2 4.8 6.6 4.9 7.1 5.0 7.5 5.5 7.8 5.3 8.2 5.2 8.7 5.3 22.8 6.2 4.8 6.6 4.9 7.1 5.0 7.5 5.5 7.8 5.3 8.2 5.2 8.7 5.3 25.0 6.2 4.8 6.6 4.9 7.1 5.0 7.5 5.5 7.7 5.3 8.2 5.1 8.6 5.2 27.8 6.2 4.8 6.6 4.9 7.0 5.0 7.4 5.4 7.6 5.2 8.0 5.1 8.4 5.2 30.0 6.1 4.8 6.5 4.8 6.9 5.0 7.2 5.4 7.5 5.2 7.9 5.0 8.2 5.1 32.8 6.1 4.7 6.4 4.8 6.8 4.9 7.1 5.3 7.3 5.1 7.7 5.0 8.1 5.1 35.0 6.0 4.7 6.4 4.8 6.7 4.9 7.0 5.3 7.2 5.0 7.6 4.9 7.9 5.0 37.8 6.0 4.7 6.3 4.7 6.6 4.8 6.9 5.2 7.1 5.0 7.4 4.9 7.7 4.9 40.0 6.0 4.7 6.2 4.7 6.5 4.8 6.8 5.2 7.0 4.9 7.3 4.8 7.6 4.9 43.3 5.9 4.7 6.1 4.6 6.4 4.7 6.6 5.1 6.8 4.9 7.1 4.7 7.4 4.8 20.0 7.8 6.5 8.3 6.6 8.9 6.8 9.4 7.4 9.8 7.1 10.4 7.0 11.0 7.2 22.8 7.8 6.5 8.3 6.6 8.9 6.8 9.4 7.4 9.8 7.1 10.4 7.0 11.0 7.2 25.0 7.8 6.5 8.3 6.6 8.9 6.8 9.4 7.4 9.7 7.1 10.3 7.0 10.8 7.1 27.8 7.7 6.5 8.3 6.6 8.8 6.8 9.2 7.3 9.5 7.0 10.1 6.9 10.6 7.0 30.0 7.7 6.4 8.2 6.5 8.7 6.7 9.1 7.3 9.4 7.0 9.9 6.8 10.4 7.0 32.8 7.6 6.4 8.1 6.5 8.5 6.7 8.9 7.2 9.2 6.9 9.7 6.8 10.1 6.9 35.0 7.6 6.4 8.0 6.4 8.4 6.6 8.8 7.2 9.1 6.9 9.5 6.7 9.9 6.8 37.8 7.6 6.4 7.9 6.4 8.3 6.6 8.7 7.1 8.9 6.8 9.3 6.6 9.7 6.8 40.0 7.5 6.4 7.8 6.3 8.2 6.5 8.5 7.0 8.8 6.7 9.1 6.6 9.5 6.7 43.3 7.5 6.3 7.7 6.3 8.0 6.5 8.3 7.0 8.5 6.7 8.9 6.5 9.3 6.6 kcal/h = kW x 860, BTU/h = kW x 3,412 Ref.: PKFY_NAMU-E_CC_USDB_PUHY-HP PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E 2 PKFY-12 5. CAPACITY TABLES PKFY-P-NAMU/NGMU/NFMU-E Model Outdoor size air temp. 06 08 12 15 18 30 71degF D.B. 73degF D.B. 77degF D.B. 81degF D.B. 82degF D.B. 86degF D.B. 90degF D.B. 59degF W.B. 61degF W.B. 64degF W.B. 66degF W.B. 68degF W.B. 72degF W.B. 75degF W.B. degF D.B. CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC 68.0 5,400 4,300 5,800 4,400 6,200 4,500 6,600 4,900 6,800 4,700 7,200 4,600 7,600 4,700 73.0 5,400 4,300 5,800 4,400 6,200 4,500 6,600 4,900 6,800 4,700 7,200 4,600 7,600 4,700 77.0 5,400 4,300 5,800 4,400 6,200 4,500 6,600 4,900 6,800 4,700 7,200 4,600 7,500 4,700 82.0 5,400 4,300 5,800 4,300 6,100 4,500 6,500 4,800 6,700 4,600 7,000 4,500 7,400 4,600 86.0 5,400 4,300 5,700 4,300 6,000 4,400 6,400 4,800 6,600 4,600 6,900 4,500 7,200 4,600 91.0 5,300 4,200 5,600 4,300 6,000 4,400 6,200 4,700 6,400 4,600 6,800 4,400 7,100 4,500 95.0 5,300 4,200 5,600 4,200 5,900 4,400 6,200 4,700 6,300 4,500 6,600 4,400 6,900 4,500 100.0 5,300 4,200 5,500 4,200 5,800 4,300 6,000 4,700 6,200 4,500 6,500 4,400 6,800 4,400 104.0 5,200 4,200 5,400 4,200 5,700 4,300 5,900 4,600 6,100 4,400 6,400 4,300 6,700 4,400 110.0 5,200 4,200 5,300 4,100 5,600 4,200 5,800 4,600 6,000 4,400 6,200 4,200 6,500 4,300 68.0 6,900 5,400 7,400 5,500 7,900 5,700 8,400 6,100 8,700 5,900 9,200 5,800 9,800 5,900 73.0 6,900 5,400 7,400 5,500 7,900 5,700 8,400 6,100 8,700 5,900 9,200 5,800 9,800 5,900 77.0 6,900 5,400 7,400 5,500 7,900 5,700 8,400 6,100 8,700 5,900 9,200 5,800 9,600 5,900 82.0 6,900 5,400 7,400 5,400 7,800 5,600 8,200 6,000 8,500 5,800 9,000 5,700 9,400 5,800 86.0 6,900 5,300 7,300 5,400 7,700 5,600 8,100 6,000 8,400 5,800 8,800 5,600 9,200 5,700 91.0 6,800 5,300 7,200 5,400 7,600 5,500 8,000 5,900 8,200 5,700 8,600 5,600 9,000 5,700 95.0 6,800 5,300 7,100 5,300 7,500 5,500 7,900 5,900 8,100 5,700 8,500 5,500 8,900 5,600 100.0 6,700 5,300 7,000 5,300 7,400 5,400 7,700 5,800 7,900 5,600 8,300 5,400 8,700 5,500 104.0 6,700 5,300 7,000 5,200 7,300 5,400 7,600 5,800 7,800 5,500 8,200 5,400 8,500 5,500 110.0 6,600 5,200 6,800 5,200 7,200 5,300 7,400 5,700 7,600 5,500 7,900 5,300 8,300 5,400 68.0 10,500 8,700 11,300 8,800 12,000 9,100 12,800 9,900 13,300 9,600 14,100 9,400 14,900 9,600 73.0 10,500 8,700 11,300 8,800 12,000 9,100 12,800 9,900 13,300 9,600 14,100 9,400 14,900 9,600 77.0 10,500 8,700 11,300 8,800 12,000 9,100 12,800 9,900 13,200 9,500 13,900 9,300 14,600 9,500 82.0 10,500 8,600 11,200 8,800 11,900 9,100 12,500 9,800 13,000 9,400 13,700 9,200 14,300 9,400 86.0 10,400 8,600 11,100 8,700 11,800 9,000 12,400 9,700 12,800 9,300 13,400 9,100 14,100 9,300 91.0 10,400 8,600 11,000 8,700 11,600 8,900 12,100 9,600 12,500 9,300 13,100 9,000 13,800 9,200 95.0 10,300 8,600 10,800 8,600 11,400 8,900 12,000 9,600 12,300 9,200 12,900 9,000 13,500 9,100 100.0 10,300 8,500 10,700 8,500 11,300 8,800 11,700 9,500 12,100 9,100 12,600 8,900 13,200 9,000 104.0 10,200 8,500 10,600 8,500 11,100 8,700 11,600 9,400 11,900 9,000 12,400 8,800 12,900 8,900 110.0 10,100 8,500 10,400 8,400 10,900 8,600 11,300 9,300 11,600 8,900 12,100 8,700 12,600 8,800 68.0 13,200 10,400 14,200 10,600 15,100 10,900 16,100 11,800 16,700 11,500 17,700 11,200 18,700 11,500 73.0 13,200 10,400 14,200 10,600 15,100 10,900 16,100 11,800 16,700 11,500 17,700 11,200 18,700 11,500 77.0 13,200 10,400 14,200 10,600 15,100 10,900 16,100 11,800 16,600 11,400 17,500 11,200 18,400 11,400 82.0 13,200 10,400 14,100 10,500 15,000 10,900 15,800 11,700 16,300 11,300 17,200 11,000 18,000 11,200 86.0 13,100 10,300 14,000 10,500 14,800 10,800 15,500 11,600 16,000 11,200 16,900 10,900 17,700 11,100 91.0 13,000 10,300 13,800 10,400 14,600 10,700 15,300 11,500 15,700 11,000 16,500 10,800 17,300 11,000 95.0 13,000 10,300 13,600 10,300 14,400 10,600 15,000 11,400 15,500 10,900 16,200 10,700 17,000 10,900 100.0 12,900 10,200 13,400 10,200 14,100 10,500 14,800 11,300 15,200 10,800 15,900 10,500 16,600 10,700 104.0 12,800 10,200 13,300 10,200 14,000 10,400 14,500 11,200 14,900 10,700 15,600 10,400 16,300 10,600 110.0 12,700 10,100 13,100 10,100 13,700 10,300 14,200 11,000 14,600 10,600 15,200 10,300 15,800 10,500 68.0 15,900 13,200 17,100 13,500 18,200 13,900 19,400 15,100 20,100 14,600 21,300 14,300 22,500 14,700 73.0 15,900 13,200 17,100 13,500 18,200 13,900 19,400 15,100 20,100 14,600 21,300 14,300 22,500 14,700 77.0 15,900 13,200 17,100 13,500 18,200 13,900 19,300 15,100 20,000 14,600 21,100 14,300 22,200 14,600 82.0 15,900 13,200 17,000 13,400 18,000 13,800 19,000 15,000 19,600 14,400 20,700 14,100 21,700 14,400 86.0 15,800 13,200 16,800 13,300 17,800 13,800 18,700 14,900 19,300 14,300 20,300 14,000 21,300 14,300 91.0 15,700 13,100 16,600 13,200 17,500 13,600 18,400 14,700 18,900 14,100 19,900 13,800 20,800 14,100 95.0 15,600 13,100 16,400 13,100 17,300 13,500 18,100 14,600 18,700 14,000 19,600 13,700 20,400 14,000 100.0 15,500 13,000 16,200 13,000 17,000 13,400 17,800 14,500 18,300 13,900 19,100 13,500 20,000 13,800 104.0 15,400 13,000 16,000 13,000 16,800 13,300 17,500 14,400 18,000 13,800 18,800 13,400 19,600 13,700 110.0 15,300 12,900 15,800 12,800 16,500 13,200 17,100 14,200 17,500 13,600 18,300 13,200 19,000 13,500 68.0 21,100 16,300 22,600 16,700 24,100 17,200 25,600 18,600 26,600 18,000 28,100 17,700 29,700 18,000 73.0 21,100 16,300 22,600 16,700 24,100 17,200 25,600 18,600 26,600 18,000 28,100 17,700 29,700 18,000 77.0 21,100 16,300 22,600 16,700 24,100 17,200 25,500 18,600 26,400 18,000 27,900 17,600 29,300 17,900 82.0 21,000 16,300 22,400 16,600 23,800 17,100 25,100 18,400 25,900 17,700 27,300 17,400 28,600 17,600 86.0 20,900 16,300 22,200 16,500 23,500 17,000 24,700 18,300 25,500 17,600 26,900 17,200 28,100 17,500 91.0 20,700 16,200 21,900 16,300 23,200 16,800 24,300 18,100 25,000 17,400 26,300 17,000 27,500 17,200 95.0 20,600 16,100 21,700 16,200 22,900 16,700 23,900 17,900 24,600 17,200 25,800 16,800 27,000 17,100 100.0 20,500 16,100 21,400 16,100 22,500 16,500 23,500 17,700 24,100 17,000 25,300 16,600 26,400 16,800 104.0 20,400 16,000 21,200 16,000 22,200 16,400 23,100 17,600 23,800 16,900 24,800 16,400 25,900 16,700 110.0 20,200 15,900 20,800 15,800 21,800 16,200 22,600 17,300 23,200 16,600 24,100 16,200 25,100 16,400 68.0 26,500 22,100 28,400 22,500 30,300 23,300 32,200 25,300 33,400 24,400 35,400 23,900 37,400 24,500 73.0 26,500 22,100 28,400 22,500 30,300 23,300 32,200 25,300 33,400 24,400 35,400 23,900 37,400 24,500 77.0 26,500 22,100 28,400 22,500 30,300 23,300 32,100 25,300 33,200 24,300 35,000 23,800 36,800 24,300 82.0 26,400 22,000 28,200 22,400 29,900 23,100 31,500 25,000 32,600 24,000 34,300 23,500 36,000 24,000 86.0 26,300 22,000 27,900 22,200 29,600 23,000 31,100 24,800 32,100 23,900 33,800 23,300 35,400 23,800 91.0 26,100 21,900 27,600 22,100 29,100 22,800 30,500 24,600 31,500 23,600 33,000 23,100 34,600 23,600 95.0 25,900 21,800 27,300 21,900 28,700 22,600 30,100 24,400 31,000 23,400 32,500 22,900 33,900 23,300 100.0 25,800 21,800 26,900 21,800 28,300 22,400 29,500 24,200 30,300 23,200 31,800 22,600 33,100 23,100 104.0 25,600 21,700 26,600 21,600 27,900 22,300 29,100 24,000 29,900 23,000 31,200 22,400 32,500 22,900 110.0 25,400 21,600 26,200 21,400 27,400 22,000 28,400 23,700 29,100 22,700 30,400 22,100 31,600 22,600 kcal/h = kW x 860, BTU/h = kW x 3,412 Ref.: PKFY_NAMU-E_CC_USDB_PUHY-HP PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E 3 PKFY-13 PKFY-P-NAMU-E PKFY-P-NGMU-E PKFY-P-NFMU-E 24 CA : Capacity(BTU/h) SHC : Sensible Heat Capacity(BTU/h) Indoor air temp. 5. CAPACITY TABLES PKFY-P-NAMU-E PKFY-P-NGMU-E PKFY-P-NFMU-E 5-2. Heating Capacity in Combination with PUHY-HP72,96THMU; -HP144,192TSHMU PKFY-P-NAMU/NGMU/NFMU-E SHC : Sensible Heat Capacity(kW) Model Outdoor Indoor air temp. size air temp. 15.0degC D.B. 21.1degC D.B. 25.0degC D.B. 27.2degC D.B. degC W.B. SHC SHC SHC SHC -25.0 1.5 1.5 1.5 1.4 -20.0 1.8 1.8 1.7 1.4 -15.0 2.0 2.0 1.7 1.4 -10.0 2.2 2.0 1.7 1.4 06 -5.0 2.3 2.0 1.7 1.4 0.0 2.3 2.0 1.7 1.4 3.0 2.3 2.0 1.7 1.4 6.0 2.4 2.0 1.7 1.4 8.0 2.4 2.0 1.7 1.4 10.0 2.5 2.0 1.7 1.4 13.0 2.6 2.0 1.7 1.4 16.0 2.7 2.0 1.7 1.4 18.0 2.8 2.0 1.7 1.4 -25.0 2.0 2.0 2.0 1.9 -20.0 2.3 2.3 2.2 1.9 -15.0 2.6 2.6 2.2 1.9 -10.0 2.9 2.6 2.2 1.9 08 -5.0 3.0 2.6 2.2 1.9 0.0 3.0 2.6 2.2 1.9 3.0 3.0 2.6 2.2 1.9 6.0 3.1 2.6 2.2 1.9 8.0 3.2 2.6 2.2 1.9 10.0 3.2 2.6 2.2 1.9 13.0 3.4 2.6 2.2 1.9 16.0 3.5 2.6 2.2 1.9 18.0 3.6 2.6 2.2 1.9 -25.0 3.0 3.0 3.0 2.9 -20.0 3.5 3.5 3.4 2.9 -15.0 4.0 4.0 3.4 2.9 -10.0 4.5 4.0 3.4 2.9 12 -5.0 4.6 4.0 3.4 2.9 0.0 4.6 4.0 3.4 2.9 3.0 4.6 4.0 3.4 2.9 6.0 4.7 4.0 3.4 2.9 8.0 4.9 4.0 3.4 2.9 10.0 5.0 4.0 3.4 2.9 13.0 5.2 4.0 3.4 2.9 16.0 5.4 4.0 3.4 2.9 18.0 5.5 4.0 3.4 2.9 -25.0 3.8 3.8 3.8 3.6 -20.0 4.4 4.4 4.2 3.6 -15.0 5.0 5.0 4.2 3.6 -10.0 5.6 5.0 4.2 3.6 15 -5.0 5.8 5.0 4.2 3.6 0.0 5.8 5.0 4.2 3.6 3.0 5.8 5.0 4.2 3.6 6.0 5.9 5.0 4.2 3.6 8.0 6.1 5.0 4.2 3.6 10.0 6.2 5.0 4.2 3.6 13.0 6.5 5.0 4.2 3.6 16.0 6.7 5.0 4.2 3.6 18.0 6.9 5.0 4.2 3.6 -25.0 4.4 4.4 4.4 4.2 -20.0 5.2 5.2 5.0 4.2 -15.0 5.9 5.9 5.0 4.2 -10.0 6.6 5.9 5.0 4.2 18 -5.0 6.8 5.9 5.0 4.2 0.0 6.8 5.9 5.0 4.2 3.0 6.8 5.9 5.0 4.2 6.0 7.0 5.9 5.0 4.2 8.0 7.2 5.9 5.0 4.2 10.0 7.4 5.9 5.0 4.2 13.0 7.6 5.9 5.0 4.2 16.0 7.9 5.9 5.0 4.2 18.0 8.1 5.9 5.0 4.2 -25.0 5.9 5.9 5.9 5.7 -20.0 7.0 7.0 6.6 5.7 -15.0 7.9 7.9 6.6 5.7 -10.0 8.8 7.9 6.6 5.7 24 -5.0 9.1 7.9 6.6 5.7 0.0 9.1 7.9 6.6 5.7 3.0 9.1 7.9 6.6 5.7 6.0 9.3 7.9 6.6 5.7 8.0 9.6 7.9 6.6 5.7 10.0 9.9 7.9 6.6 5.7 13.0 10.2 7.9 6.6 5.7 16.0 10.6 7.9 6.6 5.7 18.0 10.9 7.9 6.6 5.7 kcal/h = kW x 860, BTU/h = kW x 3,412 Ref.: PKFY_NAMU-E_HC_USDB_PUHY-HP Model size 30 Outdoor air temp. degC W.B. -25.0 -20.0 -15.0 -10.0 -5.0 0.0 3.0 6.0 8.0 10.0 13.0 16.0 18.0 SHC : Sensible Heat Capacity(kW) Indoor air temp. 15.0degC D.B. 21.1degC D.B. 25.0degC D.B. 27.2degC D.B. SHC SHC SHC SHC 7.5 7.5 7.5 7.2 8.8 8.8 8.4 7.2 10.0 10.0 8.4 7.2 11.1 10.0 8.4 7.2 11.5 10.0 8.4 7.2 11.5 10.0 8.4 7.2 11.5 10.0 8.4 7.2 11.8 10.0 8.4 7.2 12.1 10.0 8.4 7.2 12.5 10.0 8.4 7.2 13.0 10.0 8.4 7.2 13.4 10.0 8.4 7.2 13.8 10.0 8.4 7.2 kcal/h = kW x 860, BTU/h = kW x 3,412 Ref.: PKFY_NAMU-E_HC_USDB_PUHY-HP PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E 4 PKFY-14 5. CAPACITY TABLES SHC : Sensible Heat Capacity(BTU/h) Indoor air temp. 70degF D.B. 77degF D.B. 81degF D.B. SHC SHC SHC 5,100 5,100 4,900 6,000 5,700 4,900 6,800 5,700 4,900 6,800 5,700 4,900 6,800 5,700 4,900 6,800 5,700 4,900 6,800 5,700 4,900 6,800 5,700 4,900 6,800 5,700 4,900 6,800 5,700 4,900 6,800 5,700 4,900 6,800 5,700 4,900 6,800 5,700 4,900 6,700 6,700 6,400 7,800 7,500 6,400 8,900 7,500 6,400 8,900 7,500 6,400 8,900 7,500 6,400 8,900 7,500 6,400 8,900 7,500 6,400 8,900 7,500 6,400 8,900 7,500 6,400 8,900 7,500 6,400 8,900 7,500 6,400 8,900 7,500 6,400 8,900 7,500 6,400 10,200 10,200 9,800 12,000 11,500 9,800 13,600 11,500 9,800 13,600 11,500 9,800 13,600 11,500 9,800 13,600 11,500 9,800 13,600 11,500 9,800 13,600 11,500 9,800 13,600 11,500 9,800 13,600 11,500 9,800 13,600 11,500 9,800 13,600 11,500 9,800 13,600 11,500 9,800 12,800 12,800 12,300 15,000 14,300 12,300 17,100 14,300 12,300 17,100 14,300 12,300 17,100 14,300 12,300 17,100 14,300 12,300 17,100 14,300 12,300 17,100 14,300 12,300 17,100 14,300 12,300 17,100 14,300 12,300 17,100 14,300 12,300 17,100 14,300 12,300 17,100 14,300 12,300 15,100 15,100 14,500 17,700 16,900 14,500 20,100 16,900 14,500 20,100 16,900 14,500 20,100 16,900 14,500 20,100 16,900 14,500 20,100 16,900 14,500 20,100 16,900 14,500 20,100 16,900 14,500 20,100 16,900 14,500 20,100 16,900 14,500 20,100 16,900 14,500 20,100 16,900 14,500 20,200 20,200 19,400 23,700 22,600 19,400 27,000 22,600 19,400 27,000 22,600 19,400 27,000 22,600 19,400 27,000 22,600 19,400 27,000 22,600 19,400 27,000 22,600 19,400 27,000 22,600 19,400 27,000 22,600 19,400 27,000 22,600 19,400 27,000 22,600 19,400 27,000 22,600 19,400 kcal/h = kW x 860, BTU/h = kW x 3,412 Ref.: PKFY_NAMU-E_HC_USDB_PUHY-HP Model size 30 Outdoor air temp. degF W.B. -13.0 -4.0 5.0 14.0 23.0 32.0 37.4 43.0 46.0 50.0 55.0 60.0 65.0 59degF D.B. SHC 25,600 30,000 34,100 38,000 39,300 39,300 39,300 40,300 41,400 42,600 44,200 45,900 47,000 SHC : Sensible Heat Capacity(BTU/h) Indoor air temp. 70degF D.B. 77degF D.B. 81degF D.B. SHC SHC SHC 25,600 25,600 24,600 30,000 28,700 24,600 34,100 28,700 24,600 34,100 28,700 24,600 34,100 28,700 24,600 34,100 28,700 24,600 34,100 28,700 24,600 34,100 28,700 24,600 34,100 28,700 24,600 34,100 28,700 24,600 34,100 28,700 24,600 34,100 28,700 24,600 34,100 28,700 24,600 kcal/h = kW x 860, BTU/h = kW x 3,412 Ref.: PKFY_NAMU-E_HC_USDB_PUHY-HP PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E PKFY-P-NAMU-E PKFY-P-NGMU-E PKFY-P-NFMU-E PKFY-P-NAMU/NGMU/NFMU-E Model Outdoor size air temp. 59degF D.B. degF W.B. SHC -13.0 5,100 -4.0 6,000 5.0 6,800 14.0 7,600 06 23.0 7,900 32.0 7,900 37.4 7,900 43.0 8,100 46.0 8,300 50.0 8,500 55.0 8,800 60.0 9,200 65.0 9,400 -13.0 6,700 -4.0 7,800 5.0 8,900 14.0 9,900 08 23.0 10,200 32.0 10,200 37.4 10,200 43.0 10,500 46.0 10,800 50.0 11,100 55.0 11,500 60.0 11,900 65.0 12,200 -13.0 10,200 -4.0 12,000 5.0 13,600 14.0 15,200 12 23.0 15,700 32.0 15,700 37.4 15,700 43.0 16,100 46.0 16,600 50.0 17,000 55.0 17,700 60.0 18,300 65.0 18,800 -13.0 12,800 -4.0 15,000 5.0 17,100 14.0 19,000 15 23.0 19,600 32.0 19,600 37.4 19,600 43.0 20,200 46.0 20,700 50.0 21,300 55.0 22,100 60.0 22,900 65.0 23,500 -13.0 15,100 -4.0 17,700 5.0 20,100 14.0 22,400 18 23.0 23,200 32.0 23,200 37.4 23,200 43.0 23,800 46.0 24,500 50.0 25,100 55.0 26,100 60.0 27,100 65.0 27,700 -13.0 20,200 -4.0 23,700 5.0 27,000 14.0 30,000 24 23.0 31,000 32.0 31,000 37.4 31,000 43.0 31,900 46.0 32,700 50.0 33,600 55.0 34,900 60.0 36,200 65.0 37,100 5 PKFY-15 6. TEMPERATURE/AIRFLOW DISTRIBUTIONS DATA U3 6-1. 6-1.Temperature TemperatureDistributions distributions 6. TEMPERATURE/AIRFLOW DISTRIBUTIONS 2 (6' 6-3/4") 2.7 (8' 10-5/16") 27 (81) 1 (3' 3-3/8") 25 (77) 21 (70) 0 1 (3' 3-3/8") 0 23 (73) 23 (73) 25 (77) Height <m(ft)> Height <m(ft)> 2.7 (8' 10-5/16") PKFY-P06,08NAMU-E <Cooling mode> Horizontal air flow 2 (6' 6-3/4") 3 (9' 10-1/8") 2 (6' 6-3/4") 33 (91) 1 (3' 3-3/8") 23(73) 31 (88) 27 29 (81) (84) 0 4 (13' 1-1/2") Floor distance <m(ft)> <Heating mode> Downward air flow 0 25(77) 2 (6' 6-3/4") 3 (9' 10-1/8") 4 (13' 1-1/2") Floor distance <m(ft)> Ref.:TD_PKFY-P-NAMU-E_H PKFY-P12,15NGMU-E <Cooling mode> <Heating mode> 2.7 2.7 (8' 10-5/16") (8' 10-5/16") 27 (81) 25 (77) 2 (6' 6-3/4") Height <m(ft)> Height <m(ft)> 27(81) 1 (3' 3-3/8") Ref.:TD_PKFY-P-NAMU-E_C 21 (70) 23(73) 1 (3' 3-3/8") 0 29 (84) 31 (88) 23(73) 25(77) 1 (3' 3-3/8") 0 2 (6' 6-3/4") 3 (9' 10-1/8") 4 (13' 1-1/2") 2 (6' 6-3/4") 27 (81) 35 (95) 1 (3' 3-3/8") 23 (73) 0 5 5.5 (16' 4-7/8") (18' 9/16") 0 25 (77) 25(77) 29 (84) 31(88) 1 (3' 3-3/8") Floor distance <m(ft)> 27(81) 29(84) 31(88) 2 (6' 6-3/4") 3 (9' 10-1/8") 4 (13' 1-1/2") 5 5.5 (16' 4-7/8") (18' 9/16") Floor distance <m(ft)> Ref.:TD_PKFY-P-NGMU-E_C10 2.7 8' 10-5/16" 23(73) 33 (91) Ref.:TD_PKFY-P-NGMU-E_H70 PKFY-P18,24,30NFMU-E <Cooling mode> Horizontal air flow ºC (ºF) Height <m(ft)> 23 (73) 1 3' 3-3/8" 21 (70) 25 (77) 23 (73) aa 1 3' 3-3/8" 2.7 8' 10-5/16" Height <m(ft)> PKFY-P-NAMU-E PKFY-P-NGMU-E PKFY-P-NFMU-E 25 (77) 2 6' 6-3/4" 2 6' 6-3/4" 3 9' 10-1/8" PKFY-P18,24,30NFMU-E <Heating mode> Downward air flow 4 13' 1-1/2" Floor Distance <m(ft)> 5 16' 4-7/8" 6 19' 8-3/16" 7 22' 11-11/16" 8 26' 2-15/16" ºC (ºF) 2 6' 6-3/4" 27 (81) 1 3' 3-3/8" 25 (77) aa 33 (91) 27 (81) 31 (88) 25 (77) 29 (84) 29 31 (88) (84) 1 3' 3-3/8" 2 6' 6-3/4" 3 9' 10-1/8" 4 13' 1-1/2" 5 16' 4-7/8" 6 19' 8-3/16" 7 22' 11-11/16" 8 26' 2-15/16" Floor Distance <m(ft)> PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E PKFY-P-NAMU-E, NGMU-E, NFMU-E IUPKFY-16 - H - 32 6. TEMPERATURE/AIRFLOW DISTRIBUTIONS DATA U3 6-2. 6-2.Airflow AirflowDistributions distributions PKFY-P06,08NAMU-E <Fan mode> Horizontal air flow 2.7 (8' 10-5/16") 2 (6' 6-3/4") m/s (ft/s) 2.7 (8' 10-5/16") 0 0.5(1' 7-11/16") 1 (3' 3-3/8") 0 Height <m(ft)> Height <m(ft)> 1 (3' 3-3/8") 3.0(9' 10-1/8") 2.0(6' 6-3/4") 1 (3' 3-3/8") 2 (6' 6-3/4") 3 (9' 10-1/8") 1.0 0.5 (1' 7-11/16") 1.0 (3' 3-3/8") 3 (3' 3- /8") 0 4 (13' 1-1/2") m/s (ft/s) 2.0(6' 6-3/4") 1 (3' 3-3/8") 2.7 (8' 10-5/16") Height <m(ft)> Height <m(ft)> 0.5(1' 7-11/16") 3.0(9' 10-1/8") 1.0(3' 3-3/8") 1 (3' 3-3/8") 0 2 (6' 6-3/4") 3 (9' 10-1/8") 4 (13' 1-1/2") 5 5.5 (16' 4-7/8") (18' 9/16") <Fan mode> Flow angle : 70 1 (3' 3-3/8") m/s (ft/s) 3.0 (9' 10-1/8") 0.5 1.0 (1' 7-11/16") (3' 3-3/8") 2.0(6' 6-3/4") 0 0 1 (3' 3-3/8") Floor distance <m(ft)> 1.0(3' 3-3/8") 2 (6' 6-3/4") 0.5(1' 7-11/16") 3 (9' 10-1/8") 4 (13' 1-1/2") 5 5.5 (16' 4-7/8") (18' 9/16") Floor distance <m(ft)> Ref.:AD_PKFY-P-NGMU-E_10 PKFY-P18,24,30NFMU-E <Fan mode> Horizontal air flow 4 (13' 1-1/2") 4.0 (13' 1-1/2") 2 (6' 6-3/4") 0.5(1' 7-11/16") 0 3 (9' 10-1/8") Ref.:AD_PKFY-P-NAMU-E_2 PKFY-P12,15NGMU-E <Fan mode> 4.0 (13' 1-1/2") 2 (6' 6-3/4") Floor distance <m(ft)> Ref.:AD_PKFY-P-NAMU-E_1 2.7 (8' 10-5/16") 0.5 (1' 7-11/16") 1 (3' 3-3/8") 0 Floor distance <m(ft)> 2 (6' 6-3/4") m/s (ft/s) 2 (6' 6-3/4") 3.0(9' 10-1/8") 2.0(6' 6-3/4") 1.0 (3' 3-3/8") <Fan mode> Downward air flow Ref.:AD_PKFY-P-NGMU-E_70 2 6' 6-3/4" 0.5 (1' 7-5/8") 4.0 (13' 1-1/2" 3.0 (9' 10-1/8") 2.0 (6' 6-3/4") 1 3' 3-3/8" 0.5 (1' 7-5/8") aa 1 3' 3-3/8" 1.0 (3' 3-3/8") 3 9' 10-1/8" 2 6' 6-3/4" 4 13' 1-1/2" 5 16' 4-7/8" 6 19' 8-3/16" 7 22' 11-11/16" 8 26' 2-15/16" Floor Distance <m(ft)> PKFY-P18,24,30NFMU-E <Fan mode> Downward air flow Height <m(ft)> 2.7 8' 10-5/16" 2 6' 6-3/4" 4.0 (13' 1-1/2") 3.0 (9' 10-1/8") 1 3' 3-3/8" 2.0 (6' 6-3/4") 0.5 (1' 7-5/8") 1.0 (3' 3-3/8") 0.5 (1' 7-5/8") 1.0 (3' 3-3/8") aa 1 3' 3-3/8" 2 6' 6-3/4" 3 9' 10-1/8" 4 13' 1-1/2" 5 16' 4-7/8" 6 19' 8-3/16" 7 22' 11-11/16" 8 26' 2-15/16" Floor Distance <m(ft)> PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E PKFY-P-NAMU-E, NGMU-E, NFMU-E IUPKFY-17 - H - 33 PKFY-P-NAMU-E PKFY-P-NGMU-E PKFY-P-NFMU-E Height <m(ft)> 2.7 8' 10-5/16" 7. OPTIONAL PARTS DATA U3 parts Line line up 7-1. Optional Parts Upfor forthe theIndoor Indoorunit Unit 7. OPTIONAL PARTS L-Shaped Connection Pipe(15.88) Condensate pump External heater adaptor PAC-SC84PI-E SI1730-230 EE1750-230 SI1730-230 EE1750-230 SI1730-230 EE1750-230 PAC-YU24HT-F PAC-YU24HT-F PKFY-P06,08NAMU-E PKFY-P12,15NGMU-E PKFY-P18,24,30NFMU-E PKFY-P-NFMU-E Pipe cover provided attached to indoor unit Band (large) attached to indoor unit Connection Pipe Pipe cover Tighten using two bands . (Apply heat insulation processing to flare connection part.) 7-2. 7-2.L-shaped L-shapedConnection connection Pipe pipe PAC-SC84PI-E PAC-SC84PI-E for for PKFY-P-NFMU-E PKFY-P-NFMU-E PKFY-P-NAMU-E PKFY-P-NGMU-E PKFY-P-NFMU-E This connection pipe is used when refrigerant pipe (gas pipe) is to be drawn out to the left, the left rear, the right, or the right rear on the wall type indoor unit. Item Quantity Pipe diameter (mm) Number of pipes Pipe material Heat insulator Connection Pipe (gas pipe) 1 Φ 5/8" (15.88mm)* 15.88 (5/8") 1 (for gas) Phosphate deocidized copper C1220T-OL (JIS H3300) EPT sponge rubber Pipe cover 1 Band 2 PAC-SC84PI-E... 15.88 (5/8") Shape Detailed installation information should be referred to in itsthe Technical Service Manual Technical Service Manual. * In order to use PAC-SC84PI-E with PKFY-P18, a pipe adjuster must be used (included in PKFY-P18 components). 7-3. Condensate pump EE1750-230 To be conformed. PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E PKFY-P-NAMU-E, NGMU-E, NFMU-E IUPKFY-18 - H - 34 7. OPTIONAL PARTS DATA U3 7-3. Adapter PAC-YU24HT PAC-YU24HT 7-4. External Heater heater adapter External heater adapter PAC-YU24HT is a set of special wiring parts for controlling the electric heater* with the air-conditioner air conditioner system. *The electric heater should be designed and prepared at the site. follows:(For Manual.) A basic connection method is shown as follows: (Fordetails, details,refer referto toits in Installation the Installation Manual.) Remote control Board Relay circuit Indoor unit control board Adapter Outdoor unit control board X X Electric Heater 1 White 2 Red 1 Red 2 Yellow Red Dip switch SW5-2 "ON" CN22 Green Electric Heater power source CN24 Maximum cable length is 10 m (32ft) Preparations in the field For relay X use the specifications given below Operation coil Rated voltage : 12VDC Power consumption : 0.9W or less * Use the diode that is recommended by the relay manufacturer at both ends of the relay coil. The length of the electrical wiring for the PAC-YU24HT is 2 meters (6-1/2 ft) To extend this length, use sheathed 2-core cable. Control cable type : CVV, CVS, CPEV or equivalent. Cable size : 0.5 mm2 ~ 1.25 mm2 (16 to 22 AWG) Don’t extend the cable more than 10 meters (32ft) Recommended circuit R 1-phase power supply Wiring diagram S 208V, 230V/60Hz R 88H FS1 H1 88H FS2 FS1 H2 S FS1, 2 ----- Thermal fuse FS2 88H Control board 26H H1, H2 ----- Heater 26H --------- Overheat protection thermostat 88H --------- Electromagnetic contactor CN24 Item Quantity External output cable 2 Fan speed setting cable with resistance 2 Shape PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E PKFY-P-NAMU-E, NGMU-E, NFMU-E PKFY-P-NAMU-E PKFY-P-NGMU-E PKFY-P-NFMU-E Wiing Installation Manual. (WT04645X02) Wiringdetails detailsand andInstallation Installationdetails detailsshould shouldbe berefrerred referred to to its in the Installation Manual. (WT04645X02) IUPKFY-19 - H - 35 PKFY-P-NAMU-E PKFY-P-NGMU-E PKFY-P-NFMU-E PKFY-P-NAMU-E/PKFY-P-NGMU-E/PKFY-P-NFMU-E PKFY-20