Pink Datenblatt PinkChiller - bei Pink Energie und Speichertechnik

Transcription

Pink Datenblatt PinkChiller - bei Pink Energie und Speichertechnik
Pink Chiller
PC19
Driven by hot water out of:
Waste heat, CHP, District heating,
Solar-thermal, Biomass, etc...
■ Brine-production up to –7°C
■ Little space requirement
■ Integrated Energy-balancing due
to modern sensor technology
■ Integrated remote access and
data-logging
■ Complete cooling-kits including
heat-rejection available
■ Made in AUSTRIA
Absorption Chiller
Pink Chiller
PC19
Technical Data:
■
■
■
■
■
■
Working Solution:
Nominal cooling power:
Operation weight:
Dimensions (WxDxH):
Electrical connection:
Electrical Power consumption
Ammonia/Water
19 kW
app. 550 kg
0,8 x 0,6 x 1,9 m
400 V, 3~, 50 Hz
app. 450 W
■ Cooling ceiling
■ Fan-Coil
■ Minus-Cold
Performance data
Cold water circuit (LT)
Hot water circuit (HT)
Heat rejection circuit (MT)
recooling
Power
Temperatures in/out
Flow rate
Connection
Power
Temperatures in/out
Flow rate
Connection
Power
Temperatures in/out
Flow rate
Connection
Unit
kW
°C
m³/h
Internal tread
kW
°C
m³/h
Internal tread
kW
°C
m³/h
Internal tread
Minus-Cold
12,3
0/-3
3,5
1“
26
95/88
3,2
1“
38
24/30
5,5
6/4“
Fan-Coils
18,6
12/6
2,7
1“
30
85/78
3,6
1“
49
24/30
6,9
6/4“
Cooling ceiling
19,5
18/15
5,6
1“
27
75/68
3,3
1“
47
24/30
6,7
6/4“
Recommended value, subject to change, dated 08. 2012
Kühlsysteme
Pink
Energie- & SpeicherPink GmbH
Energie- und Speichertechnik
Bahnhofstrasse 22
A-8665 Langenwang
Tel.: +43 (0) 3854 - 3666 - 0
Fax: +43 (0) 3854 - 3666 - 40
[email protected]
www.pink.co.at