Installation manual Mixing module HHM
Transcription
Installation manual Mixing module HHM
Installation manual Mixing module 6 720 615 683-00.1I Mixing module HHM For the installer 6 720 640 430 (2009/12) en Read carefully before commissioning Table of Contents Table of Contents 1 Explanation of symbols and safety information 3 1.1 Explanation of symbols . . . . . . . . . . . . . . . 3 1.2 Safety precautions . . . . . . . . . . . . . . . . . . 3 2 Included in the delivery . . . . . . . . . . . . . . . . . . . 4 2.1 Included in the delivery . . . . . . . . . . . . . . . 4 2.2 Not included in delivery . . . . . . . . . . . . . . 4 3 Mixing module . . . . . . . . . . . . . . . . . . . . . . . . . . 5 4 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 5 Technical information . . . . . . . . . . . . . . . . . . . . . 7 5.1 System solutions . . . . . . . . . . . . . . . . . . . . 7 5.2 Technical information . . . . . . . . . . . . . . . 12 6 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6.1 CAN-BUS . . . . . . . . . . . . . . . . . . . . . . . . . 6.2 Handling circuit boards . . . . . . . . . . . . . . 6.3 Address selection . . . . . . . . . . . . . . . . . . 6.4 Assembly . . . . . . . . . . . . . . . . . . . . . . . . . 7 Electrical connections . . . . . . . . . . . . . . . . . . . 16 7.1 Wiring diagram, mixing module . . . . . . . . 16 7.2 Mixing module . . . . . . . . . . . . . . . . . . . . . 18 7.3 XB2 settings . . . . . . . . . . . . . . . . . . . . . . 19 7.4 Connection for heat pump and mixing modules . . . . . . . . . . . . . . . . . . . . . . . . . . 20 8 Pool (accessory) . . . . . . . . . . . . . . . . . . . . . . . . 22 8.1 Diagnostics/monitoring . . . . . . . . . . . . . . 24 9 Pool function, mixed circuit . . . . . . . . . . . . . . . 26 13 13 14 15 15 10 Factory values . . . . . . . . . . . . . . . . . . . . . . . . . . 27 10.1 Pool (accessory) . . . . . . . . . . . . . . . . . . . 27 10.2 Pool function, mixed circuit . . . . . . . . . . 28 2 Mixing module HHM - Subject to change without notice Explanation of symbols and safety information 1 Explanation of symbols and safety information 1.1 Explanation of symbols Warning symbols Safety instructions in this document are framed and identified by a warning triangle which is printed on a grey background. Electrical hazards are identified by a lightning symbol surrounded by a warning triangle. Signal words indicate the seriousness of the hazard in terms of the consequences of not following the safety instructions. • NOTICE indicates possible damage to property or equipment, but where there is no risk of injury. • CAUTION indicates possible injury. • WARNING indicates possible severe injury. • DANGER indicates possible risk to life. 1.2 1 Safety precautions General B Read the guide carefully and keep it to hand for future use. Installation and commissioning B Installation and start-up may only be carried out by a qualified installer. Service and maintenance B Only qualified personnel may carry out repairs. Incorrect repairs can lead to serious risks to the user, and a reduction in savings. B Only use original spare parts. B Service and maintenance must be carried out annually by an authorised service representative. Important information Notes contain important information in cases where there is no risk of personal injury or material losses and are identified by the symbol shown on the left. They are bordered by horizontal lines above and below the text. Additional symbols Symbol Meaning B a step in an action sequence Æ a reference to a related part in the document or to other related documents • a list entry – a list entry (second level) Tab. 1 Mixing module HHM - Subject to change without notice 3 2 Included in the delivery 2 Included in the delivery 2.1 Included in the delivery Mixing module Installation manual 2.2 Not included in delivery CAN-BUS cable Sensor Mixing valve Circulation pump Room temperature sensor 4 Mixing module HHM - Subject to change without notice Mixing module 3 3 Mixing module The mixing module has been designed for operation connected to Buderus heat pumps in conjunction with the HMC 10 control unit; Logatherm WPS 22...60. It has an XB2 board which is used to control an additional mixed circuit. A maximum of three mixing modules can be used per heat pump with the Logatherm WPS 22...60. PKSET does not count as a mixed additional circuit. This means that three mixing modules can be used if PKSET is used. Units that are connected to a mixing module are displayed and can also be adjusted at the control panel for the heat pump.The mixing module can also be used to control a pool with the Logatherm WPS 22...60. If a mixing module is used for controlling a pool, only two mixing modules can be used to control additional circuits. The mixing valve is closed completely once a day for 3-5 minutes to calibrate the function. No heat is supplied to the heating circuits for this time. When an air handling unit (Program Version 2.0) is installed in the circuit, a different calibration method is used to prevent freezing of the heating battery. The settings for circuit 3-4 are described under Settings in the Logatherm WPS installation manual. The settings for the cooling system are described under Settings in the PKSET installation instructions. In addition to the mixing module, an additional mixed circuit must also be equipped with a mixing valve, circulation pump, flow temperature sensor and possibly a room temperature sensor. Circuit 1 must always be installed and used. The task of the heat pump is to keep circuit 1 at the correct temperature in accordance with the heat curve. The flow temperature in circuit 2-4 cannot be higher than the value of circuit 1. This means that an underfloor heating system in circuit 1 cannot be combined with radiators in another circuit. Under certain conditions, a room temperature reduction in circuit 1 may affect the other circuits. When the Use temperature from circuit with highest temperature function under Circuit 1 is used, the heat curve for Circuit 1 does not need to be adapted to the mixed circuits. The heat pump automatically selects the highest flow temperature set point value. The mixing valve is controlled via PID regulation in order to achieve the required flow temperatures. To allow the mixing valve control system to operate properly, it is crucial to set the correct mixing valve running time in the menu for the relevant heating circuit. The mixing valve running time is normally specified on the mixing valve. For more information, refer to Settings in the installation manual for the heat pump. Mixing module HHM - Subject to change without notice 5 4 4 Dimensions Dimensions 6 720 615 683-14.1I Fig. 1 Height and width in mm. 6 720 615 683-16.1I Fig. 2 Depth in mm. 6 720 615 683-15.1I Fig. 3 6 Connection dimensions in mm. Mixing module HHM - Subject to change without notice Technical information 5 Technical information 5.1 System solutions 5.1.1 System solution explanations E10 E10.T2 Outdoor temperature sensor Tab. 2 E11 E11.C101 E11.C111 E11.F101 E11.F111 E11.G1 E11.P101 E11.P111 E11.P112 E11.Q101 E11.Q102 E11.R101 E11.T1 E11.TT Expansion vessel Buffer tank Safety valve Ventilation (automatic) Heating system pump Pressure gauge Thermometer Thermometer Shut-off valve Shut-off valve Non-return valve Flow temperature sensor Room temperature sensor Tab. 3 E12 E12.G1 E12.P112 E12.Q101 E12.Q102 E12.Q11 E12.R101 E12.T1 E12.TT Heating system pump Thermometer Shut-off valve Shut-off valve Mixing valve Non-return valve Flow temperature sensor Room temperature sensor Tab. 4 E13 E13.G1 E13.P112 E13.Q101 E13.Q102 E13.Q11 E13.R101 E13.T1 E13.TT Heating system pump Thermometer Shut-off valve Shut-off valve Mixing valve Non-return valve Flow temperature sensor Room temperature sensor Tab. 5 E14 E14.E14 E14.G1 E14.P112 E14.Q101 E14.Q102 E14.Q11 E14.R101 E14.T1 E14.TT E14.V101 5 Heat exchanger Heating system pump Thermometer Shut-off valve Shut-off valve Mixing valve Non-return valve Flow temperature sensor Room temperature sensor Non-return valve Tab. 6 E21 E21 E21.F111 E21.G2 E21.G3 E21.Q102 E21.Q21 E21.R101 E21.R102 E21.T8 E21.T9 E21.T10 E21.T11 E21.V102 Heat pump Ventilation (automatic) Heat carrier pump Collector circuit pump Shut-off valve Three-way valve Non-return valve Non-return valve Heat transfer fluid out Heat transfer fluid in Collector circuit in Collector circuit out Filter Tab. 7 E22 E22 E22.F101 E22.G2 E22.G3 E22.Q101 E22.R101 E22.R102 E22.T8 E22.T9 E22.T10 E22.T11 E22.V101 Heat pump Safety valve Heat carrier pump Collector circuit pump Shut-off valve Non-return valve Non-return valve Heat transfer fluid out Heat transfer fluid in Collector circuit in Collector circuit out Filter Tab. 8 Mixing module HHM - Subject to change without notice 7 5 Technical information E31 E31 E31.C101 E31.F101 E31.F111 E31.F102 E31.Q21 E31.Q22 E31.Q23 E31.Q24 E31.V101 Collector circuit compressor 1 Expansion vessel Safety valve Ventilation (automatic) Safety valve Ball valve, filling unit Ball valve, filling unit Shut-off valve Shut-off valve Filter Tab. 9 E41 E41 E41.E1 E41.F101 E41.F102 E41.G6 E41.P111 E41.P112 E41.Q101 E41.Q104 E41.Q105 E41.Q106 E41.Q111 E41.R101 E41.R102 E41.T3 E41.V41 E41.W41 Hot water cylinder Hot water electric heater Safety valve Safety valve Circulation pump hot water Thermometer Thermometer Shut-off valve Shut-off valve Shut-off valve Shut-off valve Balancing valve Non-return valve Non-return valve Hot water sensor Hot water Cold water Tab. 10 E81 E81.E81 E81.G1 E81.Q81 E81.T82 E81.V101 Pool heat exchanger Pool pump Pool mixing valve Pool sensor Filter Tab. 11 E81 8 Mixing module HHM - Subject to change without notice Technical information 5.1.2 5 Logatherm WPS 22...60 with additional circuits 6 720 616 846-01.1I Fig. 4 Monovalent unmixed and mixed heating circuit with buffer tank and two mixing modules each with one circuit. Circuits E11 and E12 are controlled by the heat pump. Circuits E13 and E14 are controlled by the relevant mixing module. The selectable room temperature sensors E11.TT and E12.TT are connected to the heat pump. E13.TT and E14.TT are connected to the respective mixing module. Mixing module HHM - Subject to change without notice 9 5 Technical information Logatherm WPS 22...60 with pool Fig. 5 Monoenergetic unmixed heating circuit with pool. 6 720 617 644-04.1I 5.1.3 10 Mixing module HHM - Subject to change without notice Technical information 5.1.4 5 Logatherm WPS 22...60 with pool (mixed circuit) 6 720 617 644-06.1I Fig. 6 Mixed heating circuit with pool. Mixing module HHM - Subject to change without notice 11 5 Technical information 5.2 Technical information 5.2.1 Mixing module Values for electrical connection Unit Electrical connections V WS/Hz 230 V/1-50 Hz Degree of protection IP X1 Dimensions (Width x Depth x Height) mm 255 x 180 x 77 Weight kg 1.5 General Information Tab. 12 12 Mixing module HHM - Subject to change without notice Installation 6 Installation 6.1 CAN-BUS The various circuit boards in the heat pump are joined by a communications cable, CAN-BUS. CAN (Controller Area Network) is a two-wire system for communication between microprocessor based modules/circuit boards. CAUTION: Interference. B The CAN-BUS cable must be screened and laid separately from the power cable. Suitable cable for external laying is cable LIYCY (TP) 2x2x0.5. The cable must be twisted pair and screened. The screen must only be earthed at one end and to the chassis. Maximum cable length is 30 m. CAN-BUS cable must not be laid alongside power supply cables. Minimum distance 100 mm. They may be laid alongside sensor cables. CAN-BUS 6 CAUTION: Do not mix up the 12V and CANBUS connections! The processors are destroyed if 12V is connected to the CAN-BUS. B Check that the four cables are connected to the contacts with the corresponding marking on the circuit board. The connection between the circuit boards is by four wires, because the 12V-supply between the circuit boards must also be connected. The circuit boards have markings for both the 12V and CAN-BUS connections. Switch Term is used to mark the start and end of a CANBUS loop. Ensure that the correct circuit board is terminated and that all other switches are in the opposite position. CAN-BUS 6 720 614 967-31.2I Fig. 7 GND CANL CANH +12V EWP Earth CAN low CAN high Connection 12V Heat pump Mixing module HHM - Subject to change without notice 13 6 6.2 Installation Handling circuit boards Circuit boards with control electronics are sensitive to discharges of static electricity (ESD – ElectroStatic Discharge) when handled. To prevent damaging the components, special care is therefore required when handled. CAUTION: Never grasp a circuit board without wearing a ground-connected bracelet. A condition for good ESD protection is a ground-connected bracelet when handling electronics. This bracelet must be put on before opening the screened metal bag/ packaging or before exposing an installed board. The bracelet must be worn until the circuit board is enclosed in its screen packaging or closed electric box. Replaced, returned circuit boards must be handled in the same way. 6 720 614 366-24.1I Fig. 8 Bracelet Damage is usually latent, and a circuit board can operate impeccably during commissioning but show signs of problems later. Charged objects may only be problematic if they are in close proximity to the electronics. Keep a distance of at least one metre from expanded polystyrene, protective plastic and other packaging, synthetic material (e.g. fleeces) and similar before starting work. 14 6 720 614 366-25.1I Fig. 9 Mixing module HHM - Subject to change without notice Installation 6.3 Address selection 6.3.1 Circuit 3-4 6.4 6 Assembly 6 720 615 683-22.1I Fig. 12 6 720 615 683-17.1I Fig. 10 Address selection, circuit 3-4. B Select the correct address and program for the mixing module (XB2 board). The address selection of additional mixed circuit 1 must be set to 1 (circuit E13) and the address selection of additional mixed circuit 2 must be set to 2 (circuit E14). If more mixing modules are added, make sure that with each additional module switch A is numbered consecutively in accordance with the heating circuits. The program selection for the additional mixed circuit 1 and 2 must be set to 0. The settings for the cooling system are described in the PKSET installation manual. 6.3.2 B Fasten the mixing module to the wall near the heat pump. Mount the unit at the four corners with screws. B Establish the electrical connections once the unit has been fastened to the wall. B Screw down the cover of the mixing module on the unit. 6.4.1 Room sensor T5 (accessory) It is only the room where the room sensor is located that can influence regulation of the temperature for the relevant heating circuit. Installation location requirements: • If possible, interior wall without drafts or heat radiation. • Unimpeded circulation of room air under room sensor T5 (dotted area in figure 13 must be kept clear). Pool 0,3 m 0,6 m 1,2 - 1,5 m T5 0,3 m 6 720 615 683-18.1I 6 720 614 366-34.1I Fig. 11 Address selection, pool. B Select correct program and address at XB2 board. The address selection and program selection for the pool control system must be set to 0 and 1 respectively. Mixing module HHM - Subject to change without notice Fig. 13 Recommended installation location for room sensor T5 15 7 Electrical connections 7 Electrical connections 7.1 Wiring diagram, mixing module 6 720 619 226-05.1I Fig. 14 Wiring diagram, circuit 3-4 E1x.Q11 E1x.G1 E1x.T1 E1x.TT.T5 E1x.TT.P1 E1x.B11 E1x.F51 E1x.F52 Continuous line = always connected. Dotted line = accessory, optional: x = 3, 4 1 If circuit board XB2 is the last board in the CAN-BUS loop, Mixing valve, 230 V / 0-10 V the switch must be in the TERM position. Circulation pump 2 The switch must be in the 0 position. Flow temperature sensor 3 The switch must be in the 0 position. Room temperature sensor 4 Program selection (Æ Fig. 10) Room temperature sensor LED 5 Address selection (Æ Fig. 10) External input Cables: Fuse 6.3 A Fuse 250 mA Terminal L, N, PE Input voltage Min. 1.5 mm² Terminal 51-58 Connections 230 V Min. 0.75 mm² Terminal 1-11 Sensor connections Min. 0.5 mm² Terminal 31-38 CAN-BUS (Æ Chapter 6.1) Tab. 13 16 Mixing module HHM - Subject to change without notice 7 6 720 615 683-03.2I Electrical connections Fig. 15 Wiring diagram, pool 1 2 3 4 5 E81.Q81 E81.T1 E81.T82 E81.B11 Continuous line = always connected. Dotted line = accessory, optional: If circuit board XB2 is the last board in the CANE81.G1.F21 Alarm, pool pump BUS loop, the switch must be in the Term posiE81.F51 Fuse 6.3 A tion. E81.F52 Fuse 250 mA Switch must be in position 0. Cables: Switch must be in position 0. Program selection (Æ Fig. 11) Terminal L, N, PE Input voltage Address selection (Æ Fig. 11) Terminal 51-58 Connections 230 V Mixing valve, 230 V / 0-10 V Terminal 1-11 Sensor connections Flow temperature sensor Terminal 31-38 CAN-BUS Pool sensor External input Tab. 14 Mixing module HHM - Subject to change without notice Min. 1.5 mm² Min. 0.75 mm² Min. 0.5 mm² (Æ Chapter 6.1) 17 7 7.2 Electrical connections Mixing module 6 720 615 683-01.1I Fig. 16 Mixing module XB2 1 2 3 4 5 6 7 8 9 10 18 Termination switch Switch, emergency operation function (not used) Switch 12 V, internal/external Program selection (assignment as mixed circuit, 0 = mixed circuit) Address selection (assignment of heating circuit) High voltage connecting terminal (230 V) Fuse 250 mA Fuse 6.3 A Low voltage connecting terminal (12 V) CAN-BUS connecting terminal Mixing module HHM - Subject to change without notice Electrical connections 7.3 7 XB2 settings 1 5 2 6 3 7 4 6 720 615 683-21.1I Fig. 17 Address selection, XB2 board 1 2 3 4 5 6 7 Switch off: factory setting, 12 V for mixing module supplied via CAN-BUS. Switch on: not used, factory setting (0) must be applied. Switch off: factory setting, transformer powers the mixing module. Switch on: not used, factory setting (0) must be applied. Additional mixed circuit, circuit 3. Additional mixed circuit, circuit 4. Pool Mixing module HHM - Subject to change without notice 19 7 Electrical connections 7.4 Connection for heat pump and mixing modules 7.4.1 Connection for WPS 22 - WPS 60 and mixing modules LCD J4 J6 J5 4 3 4 3 2 1 2 1 PEL CAN1 CAN1 0,1uF J5 75Ω 75Ω J2 J4 CAN1 J3 J7 1 2 3 4 TERM J6 T1 1 5 PEL BAS(2) CAN1 CAN1 J3 J6 J5 J18 J19 1 2 1 2 3 4 3 4 J5 J2 J4 CAN1 J3 J7 T2 J2 1 2 3 4 TERM A=1 P=0 4 XB1(1) 6 BAS(1) A=0 P=0 A=0 P=0 J3 J8 J9 4 3 4 3 2 1 2 1 J5 J3 J1 J18 3 J19 1 2 1 2 3 4 3 4 J2 2 7 XB2 (2) XB2 (1) 8 TR1 J4 T4 J5 J4 CAN1 CAN1 CAN1 CAN1 6 720 616 846-02.1I T3 J5 TERM TR1 A=1 P=0 TERM A=2 P=0 Fig. 18 1 2 3 4 5 6 7 8 20 CAN-BUS cable 1-8 PEL (2) - PEL (1) PEL (1) - BAS (1) BAS (1) - XB1 (1) XB1 (1) - BAS (2) BAS (2) - LCD PEL (1) - XB2 (1) XB2 (1) - XB2 (2) XB2 (2) - XB2 (?) A P T1 T2 T3 T4 Address selection Program select. Is terminated Is not terminated Is terminated Is not terminated Mixing module HHM - Subject to change without notice Electrical connections 7.4.2 7 Connection of WPS 22 - WPS 60 to pool LCD J4 J6 J5 4 3 4 3 2 1 2 1 PEL CAN1 CAN1 0,1uF J5 75Ω 75Ω J2 J4 CAN1 J3 J7 1 2 3 4 TERM J6 T1 1 5 PEL BAS(2) CAN1 CAN1 J3 J5 J18 J19 1 2 1 2 3 4 3 4 J5 J6 J2 J4 CAN1 J3 J7 T2 J2 1 2 3 4 TERM A=1 P=0 4 XB1(1) A=0 P=0 A=0 P=0 J3 J8 J9 4 3 4 3 2 1 2 1 J5 J3 J1 6 BAS(1) J18 3 J19 1 2 1 2 3 4 3 4 J2 2 XB2 (1) T4 J5 J4 CAN1 CAN1 6 720 617 644-05.1I TR1 TERM A=0 P=1 Fig. 19 1 2 3 4 5 6 CAN-BUS cable 1-6 PEL (2) - PEL (1) PEL (1) - BAS (1) BAS (1) - XB1 (1) XB1 (1) - BAS (2) BAS (2) - LCD PEL (1) - XB2 (1) Mixing module HHM - Subject to change without notice A P T1 T2 T3 T4 Address selection Program selection Is terminated Is not terminated Is terminated Is not terminated 21 8 8 Pool (accessory) Pool (accessory) The settings are only displayed if the pool was installed in accordance with (Æ Chapter 5.1.3). An electric additional heater (0-10 V) must be connected to provide additional heat for the pool. > Activate Factory setting No Alternative Yes/No Tab. 15 Activating the pool > Pool temperature Factory setting 5 min Lowest value 0 min Highest value 30 min Tab. 20 Ramp time close B Adjust the time that the additional heater can take to reach the maximum pool heating output once a CH requirement has ended. > Heat pump x Factory setting 28.0 °C Lowest value 10.0 °C Highest value 40.0 °C Tab. 16 Pool temperature >> Active in pool heating Factory setting HP 1: No, HP 2: Yes Alternative No/Yes Tab. 21 Active with pool heating > Additional heat >> Allow additional heat during pool heating Factory setting Alternative > Ramp time close Never • Never • With heating >> Maximum pool hysteresis Factory setting 2K Lowest value 0.2K Highest value 5K Tab. 22 Maximum pool hysteresis • Always Tab. 17 Allow additional heat >>Minimum pool hysteresis > Additional heat start delay Factory setting 0.2K 300 min Lowest value 0.2K Lowest value 0 min Highest value 5K Highest value 1200 min Factory setting Tab. 18 Additional heater, start delay Tab. 23 Minimum pool hysteresis >>Time factor pool hysteresis This menu is only displayed if an additional heater is allowed with pool heating. Factory setting 10 > Ramp time open Lowest value 1 Highest value 20 Factory setting 5 min Lowest value 0 min Highest value 30 min Tab. 24 Time factor pool hysteresis Tab. 19 Ramp time open B Adjust the time that the additional heater can take to reach the maximum pool heating output in the event of an additional heat demand. 22 Mixing module HHM - Subject to change without notice Pool (accessory) > Pool heating start delay >> Maximum PID signal Factory setting 60 min Factory setting Lowest value 15 min Lowest value 0% Highest value 240 min Highest value 100% Tab. 25 Pool heating, start delay Tab. 31 Maximum PID signal The start delay only applies if more than one compressor is allowed in pool mode. The first compressor to reach the start status starts first. The next compressor start is prevented during the delay time. >>Mixing valve running time > Acknowledge extra pool sensor T81 Factory setting Yes (if T81 is connected) Alternative 8 Yes/No Tab. 26 Extra pool sensor T81 > Regulator settings >> P constant Factory setting 1.0 Lowest value 0.1 Highest value 30.0 Factory setting 100% 300s Lowest value 1s Highest value 6000s Tab. 32 Mixing valve running time B Set the run time that is indicated on the mixing valve and indicate value in number of seconds. If there is no time indication on the mixing valve, run it manually (Æ Chapter 8.1.3) and measure how long it takes to go from fully closed to a fully open mixing valve (the mixing valve stops sounding and the endposition switch switches off). Tab. 27 P constant >> I constant Factory setting 300.0 Lowest value 5.0 Highest value 600.0 Tab. 28 I constant >> D constant Factory setting 0.0 Lowest value 0.0 Highest value 10.0 Tab. 29 D constant >> Minimum PID signal Factory setting 0% Lowest value 0% Highest value 100% Tab. 30 Minimum PID signal Mixing module HHM - Subject to change without notice 23 8 8.1 Pool (accessory) Diagnostics/monitoring 8.1.1 Temperatures > Pool >> Additional pool sensor T81 >>> Adjust T81 >> Pool T82 >>> Adjust T82 8.1.2 Inputs The status of all Inputs is displayed here. Only connected Inputs are displayed. > Inputs >> External input pool 8.1.3 Outputs The function of various central components can be tested in the Outputs menu. B Set the number of minutes for manual operation. Different vital components can be put into operation/ turned off separately. With 0min, status, e.g., On or Off, is displayed for each component. With the pool control system, it is essential that the mixing valve (E81.Q81) opens and closes in the right direction towards the heating system. When the mixing valve is fully open, the entire flow is directed to the heating system. When the mixing valve is fully closed, the entire flow is directed to the pool exchanger. The relevant components for the Pool function appear under: > Outputs >> Pool >>> Mixing valve signal >>> Mixing valve open >>> Mixing valve close 24 Mixing module HHM - Subject to change without notice 8 Pool (accessory) 8.1.4 Timers Access level 0 = Customer Access level 1 = Installer Timers Setting Factory setting Access level 300 min 1 Timer, pool > Pool additional heat start delay Diagnostics/monitoring\Timers \Additional heat timers\Pool additional heat start delay Tab. 33 Timers Mixing module HHM - Subject to change without notice 25 9 9 Pool function, mixed circuit Pool function, mixed circuit One of the mixed circuits can be used to control the pool (Æ Chapter 5.1.4, circuit 4 (E14)). The settings in this chapter only apply to the pool function. B Make the following settings to obtain pool functionality. >>> Heat curve >>>> Type of heating system Factory setting Alternative Underfloor Radiator/Underfloor > Settings Tab. 38 Type of heating system >> Circuit 1 Heating B The value must not be changed. >>> General >>>> Flow temperature at minimum outdoor temperature >>>> Use temperature from circuit with highest temperature Factory setting 35.0 °C No Lowest value 22.0 °C Yes/No Highest value 45.0 °C Factory setting Alternative Tab. 34 Temperature from circuit with highest temperature B Change setting to Yes. Tab. 39 Underfloor B Reduce the flow temperature to 22 °C. >>>> Parallel offset >>> Heat curve Factory setting >>>> Type of heating system Factory setting Alternative Underfloor Radiator/Underfloor Tab. 35 Type of heating system B Change to Radiator at Yes in Use temperature from circuit with highest temperature. >>>> Flow temperature at minimum outdoor temperature 0.0K Lowest value -10.0K Highest value 10.0K Tab. 40 Parallel offset B Use Parallel offset to set the desired pool temperature. For example, 6.0 K for a pool temperature of 28°C. B Switch to customer level. > Room and hot water program >> Circuit 4 Factory setting 60.0 °C >>> Active program Lowest value 22.0 °C B Select HP optimized. Highest value 80.0 °C B Go back to the installer level and select Diagnostics/ monitoring. Tab. 36 Radiators B At Yes in Use temperature from circuit with highest temperature, set a low value for the flow temperature, e.g., 22 °C. >> Circuit 4 > Diagnostics/monitoring >> Temperatures >>> Circuit 4 >>>> Damped room sensor T5 >>> Mixing valve mode Factory setting Alternative Off Heating/Off Tab. 37 Mixing valve operating mode B Select Heating to use the circuit for the pool. 26 Factory setting 0.25h Lowest value 0.00h Highest value 48h Tab. 41 Damped room sensor T5 B Set damping to 0.00 h. Mixing module HHM - Subject to change without notice 10 Factory values 10 Factory values 10.1 Pool (accessory) Access level 0 = Customer Access level 1 = Installer Pool Factory setting Activate Pool temperature Additional heat Allow additional heat during pool heating Additional heat start delay Heat pump x No 0 28.0 °C 0 Never 0 300 min 0 Ramp time open 5 min 1 Ramp time close 5 min 1 Active in pool heating Yes 1 Maximum pool hysteresis 2.0K 1 Minimum pool hysteresis 0.2K 1 10 1 Time factor pool hysteresis Pool heating start delay Acknowledge extra pool sensor T81 Regulator settings Access level 60 min 1 No 1 1 P constant 1.0 I constant 300.0 1 D constant 0.0 1 1 Minimum PID signal 0% Maximum PID signal 100% 1 Mixing valve running time 300s 1 Tab. 42 Factory values pool accessory Mixing module HHM - Subject to change without notice 27 10 Factory values 10.2 Pool function, mixed circuit Access level 0 = Customer Access level 1 = Installer The settings applicable for the pool function with mixed circuit are shown in bold text. Factory setting Circuit 1 Heating General External set point value No 1 Use temperature from circuit with highest temperature No 1 Fixed temperature Shut down protection during change over from hot water to heating Heat curve Type of heating system Flow temperature at minimum outdoor temperature, Radiator/Underfloor Parallel offset Highest permitted flow temperature T1, Radiator/Underfloor No (0.0 °C) 1 300s 1 Underfloor 1 60/35 °C 1 0.0K 1 80/45 °C 1 Lowest permitted flow temperature T1 10 °C 1 Heat curve hysteresis heat pump x Maximum Minimum Time factor 16.0K 4.0K 10.0 1 1 1 Room sensor Room temperature influence (if installed) Knob's operating range (if installed) Acknowledge room sensor 3.0 6K (Auto) 1 1 1 Setting temp. increase/decrease (no room temperature sensor) Limit value for left or right end point Change when much colder/warmer Change when colder/warmer 0.0 °C 8% 3% 1 1 1 3.0 1 Room temperature influence (no room temperature sensor) Circuit 2, 3... Access level Air handling unit in circuit No Mixing valve mode Off Heat curve See Circuit 1 Heating Room sensor (accessory) Room temperature influence (if installed) Acknowledge room sensor Setting temp. increase/decrease (no room temperature sensor) See Circuit 1 Heating Room temperature influence (no room temperature sensor) Regulator settings P constant I constant D constant Minimum PID signal Maximum PID signal Mixing valve running time Mixing valve fully closed Mixing valve start closing Connected to output type 1 1 3.0 (Auto) 1 1 1 3.0 1 1 300 0.0 0% 100% 300s 2K 2K Op/Cl 1 1 1 1 1 1 1 1 1 Tab. 43 Factory values pool mixed circuit 28 Mixing module HHM - Subject to change without notice 10 Notes Mixing module HHM - Subject to change without notice 29 10 30 Mixing module HHM - Subject to change without notice 10 Mixing module HHM - Subject to change without notice 31