installation manual
Transcription
installation manual
NOVELLA 24-31-45 RAI 24-31 RAI PV BOILERS INSTALLATION MANUAL CAST IRON BASE INSTALLATION MANUAL Novella boilers conform to the basic requirements of the following directives: • Gas Appliances Directive 2009/142/CE • Boiler Efficiency Directive 92/42/CEE (✫✫) • Electromagnetic Compatibility Directive 2004/108/CE • Low Voltage Directive 2006/95/CE Novella boilers are therefore CE marked. 0694 2 The following symbols are used in this manual: b CAUTION! = Indicates actions that require caution and adequate preparation aSTOP! = Identifies actions that you MUST NOT do CONTENTS 1 SAFETY INFORMATION AND PRECAUTIONS......................................... 4 2 DESCRIPTION OF THE APPLIANCE......................................................... 5 2.1Description of the appliance................................................................................................................5 2.2Optional accessories...........................................................................................................................5 2.3Main parts of the boiler........................................................................................................................6 2.4Control panel.......................................................................................................................................7 2.5Technical specifications.......................................................................................................................7 2.6Identification.........................................................................................................................................8 2.7Material supplied..................................................................................................................................9 2.8Handling...............................................................................................................................................9 2.9Overall dimensions and water fittings................................................................................................10 2.10Water circuit.......................................................................................................................................11 2.11Wiring diagram...................................................................................................................................13 3INSTALLATION.......................................................................................... 14 3.1Installation standards.........................................................................................................................14 3.2Place of installation............................................................................................................................14 3.3Installation in existing systems..........................................................................................................14 3.4Water connections.............................................................................................................................15 3.5Electrical connections........................................................................................................................15 3.6Gas connections................................................................................................................................17 3.7Gas supply conversion......................................................................................................................17 3.8Flue gas vent and air intake..............................................................................................................19 3.9Filling the water circuit.......................................................................................................................19 3.10Emptying the water circuit.................................................................................................................20 4 START-UP AND FUNCTIONING............................................................... 21 4.1Preliminary checks.............................................................................................................................21 4.2Ignition...............................................................................................................................................21 4.3Final checks.......................................................................................................................................23 5SHUT-DOWN ............................................................................................ 24 6MAINTENANCE ........................................................................................ 25 6.1Scheduled maintenance....................................................................................................................25 6.2Extraordinary maintenance................................................................................................................25 7 OPTIONAL ACCESSORIES...................................................................... 26 3 INSTALLATION MANUAL 1 SAFETY INFORMATION AND PRECAUTIONS bbThis manual and the operation manual associated with it form integral parts of the product. Make sure that they are always kept with the boiler even if it is transferred to another owner or user, or re-installed elsewhere. If you damage or lose this manual, order a replacement immediately from your local Technical Assistance Service. bbThe boiler must only be installed and serviced by qualified personnel, in conformity to applicable legislation (in Italy, law 46 of the 05/03/1990) and applicable technical standards (in Italy, UNICIG 7129 and 7131 standards and subsequent updates thereto). • Switch the boiler OFF at the control panel and at the mains power switch • Close the boiler’s fuel cock, central heating circuit shut-off cock and domestic hot water circuit shut-off cock • Empty the central heating circuit and domestic hot water circuit if there is any risk of freezing - The boiler must be serviced at least once a year. Servicing must be arranged in advance with the manufacturer’s Technical Assistance Service Observe the following precautions to ensure safe operation of the boiler. aaDo not allow children or uninformed persons to operate the boiler. bbThe boiler must only be used for the pur- aaDo not operate any electrical devices or pose for which it is designed. The manufacturer declines all responsibility, contractual or other, for damage to property or injury to persons or animals caused by improper installation, adjustment, maintenance or use. bbAs soon as you open the packaging, check immediately that the contents are all present and undamaged. Contact the reseller from whom you purchased the product if you notice any problems. 4 equipment, including switches or domestic appliances, etc., if you can smell fuel or fumes. In the event of a gas leak, thoroughly ventilate the room by opening wide all doors and windows, close the gas shut-off valve and call the manufacturer’s Technical Assistance Service immediately to arrange urgent assistance by professionally qualified personnel. aaDo not touch the boiler while barefoot or wet. bbThe safety valve must be connected to aaNever a suitable collection and drain system. The manufacturer declines all responsibility for damage caused by the operation of an improperly connected safety valve. bbThe following instructions must be pas sed on to the user on installation of the boiler. - If water leaks from the boiler, turn off the water supply and contact the manufacturer’s Technical Assistance Service immediately. - Periodically check that operating pressure in the water circuit is over 1 bar. If necessary, contact the manufacturer’s Technical Assistance Service to arrange servicing by professionally qualified personnel. - If the boiler is not going to be used for an extended period of time, contact the manufacturer’s Technical Assistance Service to have at least the following operations performed: clean the boiler without first disconnecting it from the mains electricity supply by turning the mains power switch and the control panel switch OFF. aaDo not tamper with or adjust the boiler’s safety or control devices without prior authorisation and instructions from the manufacturer. aaDo not pull, disconnect, or twist the elec- trical cables coming from the boiler even if it is disconnected from the mains electricity supply. aaDo not obstruct or restrict vents in the room where the boiler is installed. Adequate ventilation is essential for correct combustion. aaDo not store containers of flammable substances in the room where the boiler is installed. aaDo not leave items of packaging within the reach of children. 2 DESCRIPTION OF THE APPLIANCE 2.1 Description of the appliance Novella boilers are gas fuelled boilers for domestic heating. They are equipped with an atmospheric burner and a cast iron primary heat exchanger. They incorporate an open (type B11BS) combustion chamber and are fitted with a hood that ensures proper flue gas venting even with a fluctuating flue draught. They are also equipped with a flue gas thermostat, as required by applicable safety standards. The burner is a stainless steel unit with stabilised flame and smooth ignition. The burner is fitted with an ionisation type flame detection system. The boiler’s control and safety devices conform to applicable technical and safety standards and are enclosed in a functional control panel integrated in the body of the appliance. Novella boilers use total shut-down logic and do not waste energy because they only start up when heat is actually needed by the central heating system (i.e. when the room thermostat trips). Novella boilers can be connected to a storage cylinder to produce domestic hot water, and can be equipped with temperature controllers in the form of specific accessories. Installation, maintenance and access to internal components is facilitated by a large front panel. The key features of these boilers include: -- electronic ignition with ionisation flame detection -- adjustable smooth ignition -- gas supply solenoid valve with built-in pressure stabiliser and double shutter for burner control -- domestic hot water temperature control -- water circuit temperature and pressure gauge -- provision for room thermostat or timer. Novella RAI PV models also feature: -- central heating circuit pump -- 12 litre expansion vessel -- 3 bar central heating circuit safety valve. 2.2 Optional accessories -- Wall-mounted weekly timer thermostat (part number 1100279) -- Pump manifold kit (part number 694769) -- High head pump kit (part number 1100269) -- RO120 storage cylinder (part number 696339) -- Pump or valve controlled multizone central heating kit with total shut-down function (part number 696439) -- Lifting brackets (part number 696429) 5 INSTALLATION MANUAL 2.3 Main parts of the boiler Novella 24 - 31 RAI PV boilers Key 1 2 3 4 5 6 7 8 9 10 11 12 Control panel Temperature sensor sockets Boiler body Electronic ignition and flame detection unit CH pump Water circuit drain cock Ignition electrode Flame detection sensor Burner Gas supply solenoid valve Lifting points Expansion vessel 11 1 2 3 10 4 9 5 8 6 7 12 6 Fig. 2.1 Novella 24 - 31 - 45 RAI boilers Key 13 Control panel 14 Temperature sensor sockets 15 Boiler body 16 Electronic ignition and flame detection unit 17 Ignition electrode 18 Water circuit drain cock 19 Flame detection sensor 20 Burner 21 Gas supply solenoid valve 22 Lifting points 22 13 14 15 21 20 16 17 19 18 Fig. 2.2 2.4 Control panel 23 31 24 30 25 26 29 28 Key 23 Main switch 24 Central heating temperature control 25 Water circuit temperature and pressure gauge 26 Safety thermostat (manual reset) 27 Flue gas thermostat (manual reset) 28 Burner lockout LED warning light 29 Power on LED indicator 30 Quick reference guide 31 Burner reset button 27 30 Fig. 2.3 2.5 Technical specifications Rated heat input, CH Rated heat output, CH Electrical consumption Boiler class Power supply voltage Index of protection Losses from stack and casing with burner off Central heating circuit characteristics Maximum pressure - temperature CH temperature setting range Expansion vessel Gas pressure Rated gas pressure, methane (G 20) Rated gas pressure, LPG (G31) (G 30 - G 31) Water connections CH flow – return Gas inlet Emissions with G 20 gas CO below CO2 NOx (according to EN 297) Flue gas Δt Boiler dimensions Height Width Depth Weight of boiler kW kcal/h kW kcal/h W 24 RAI PV 24 RAI 103 15 26,6 22880 24,0 20640 V ~ Hz IP % bar -°C °C litres 31 RAI PV Ø Ø 3/4" 1/2" 93 1,23 -- 20 28-30/37 °C 15 3 - 100 34-82 12 mbar mbar 5,6 50,0 43000 45,0 38700 103 II 2H3+ 230 ~ 50 40 1,37 -- p.p.m. % 45 RAI 34,4 29590 31,0 26660 1,65 12 31 RAI 21 5,7 19 5,5 96 113 Class 1 mm mm mm kg 850 450 700 108 675 100 700 126 675 118 600 720 154 7 INSTALLATION MANUAL 8 PARAMETER Lower Wobbe index (at 15°C-1013 mbar) G30 (MJ/m3) (MJ/m3) (at 15°C-1013 mbar) G31 (MJ/m3) G20 Ø mm (at 15°C-1013 mbar) G20 24 RAI 31 RAI 45 RAI 45,5 80,9 70,9 Main burner Number of nozzles Nozzle diameter Nozzle pressure (downstream from valve in central heating only mode) 4 6 2,40 2,40 G30 Ø mm 1,50 1,50 1,45 G31 Ø mm 1,50 1,50 1,45 G20 G30 Maximum gas flow rate, CH (*) 3 2,40 Δp 13,5 13,5 12,7 mm H2O Δp 138 138 129 mbar Δp 28,4 28,0 27,8 mm H2O Δp 289 285 283 mbar G31 mbar Δp 36,5 34,7 35,7 372 354 364 G20 mm H2O Δp m3/h 2,80 3,50 5,10 G30 kg/h 2,09 2,70 3,92 G31 kg/h 2,05 2,66 3,86 (*) Temperature 15°C; Pressure 1013 mbar. 2.6 Identification Novella boilers are identified by a product name plate giving the boiler’s serial number, model and main technical and performance data. bbIt is essential to specify the correct model of boiler when ordering spare parts or requesting technical assistance. If the name plate or any other means of clearly identifying the product is defaced, removed or lost, proper installation and servicing may be rendered difficult. GAS FUELLED BOILER Model Serial No. Code PIN Code Year Heat input at furnace (Qn/Hi) Boiler water capacity Useful heat output (Pn) Heat exchanger surface area Maximum working pressure (mwp) Maximum admissible temperature Power supply Maximum current draw NOx class Maximum energy consumption Gas supply pressure Index of protection OBLIGATORY GROUND CONNECTION CLASS OF BOILER TYPE OF BOILER COUNTRY OF DESTINATION Fig. 2.4 2.7 Material supplied The boiler is delivered in a wooden cage. Proceed as follows to remove this. -- Remove the staples fixing the wooden cage to the pallet. -- Lift off the wooden cage. The following items are delivered in a plastic bag inside the boiler: -- Operation manual -- Installation manual -- LPG conversion kit (nozzles, label, seals). Fig. 2.5 Net weight Gross weight 24 RAI 100 119 24 RAI PV 108 127 MODEL 31 RAI 31 RAI PV 118 126 138 146 45 RAI 154 174 Instruction manuals are integral parts of the boiler. On unpacking, locate the manuals and keep them safe. kg kg 2.8 Handling C Once you have removed the packaging, proceed as follows to handle the boiler. -- Remove the screws securing the boiler to the wooden pallet. -- Remove the front panel (P) and top panel (C) from the casing (fig. 2.6). -- Lift the boiler using two 3/4” pipes (1) pushed through the lifting points (2) (fig. 2.7). P Fig. 2.6 2 bbWear suitable personal protective equipment and use suitable safety devices. aaDo not leave items of packaging within the reach of children. 1 Fig. 2.7 9 INSTALLATION MANUAL 2.9 Overall dimensions and water fittings Novella 24, 31 RAI PV boilers Fig. 2.8 Novella 24, 31, 45 RAI boilers 10 Fig. 2.9 DESCRIPTION A B 24 RAI 24 RAI PV 675 700 450 MODEL 31 RAI 31 RAI PV 675 700 45 RAI 154 720 mm mm 2.10 Water circuit Novella 24, 31 RAI PV boilers GAS RI MI E AB D C F B G A A Water circuit drain cock B Water circuit expansion vessel C Water circuit safety valve D CH circuit pump E CH circuit temperature control sensor F Water circuit temperature gauge sensor G Safety thermostat temperature sensor MI CH flow RI CH return AB Storage cylinder connection GASGas supply Fig. 2.10 11 Novella 24, 31, 45 RAI boilers GAS MI RI B A C D A Water circuit drain cock B CH circuit temperature control sensor C Water circuit temperature gauge sensor D Safety thermostat temperature sensor MI CH flow RI CH return GASGas supply Fig. 2.11 Novella RAI PV series boilers are pre-fitted with a pump to which all water and electrical connections have already been made. Pump performance is illustrated by the curves in the following graph. The pump is configured in the factory to run at maximum speed, i.e. speed III. Slower pump speeds may nevertheless be set with low load loss systems in order to reduce energy consumption. 5 4,5 Useful head (m approx.) INSTALLATION MANUAL Useful head of pump 4 3,5 3 2,5 2 Speed III 1,5 1 0,5 0 Speed II Speed I 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 Flow rate (l/h) Fig. 2.12 bbOn initial start-up and at least every year, aaNever run the pump dry. Fig. 2.13 Boiler’s water-side pressure drop Novella RAI boilers come without a pump. A pump must therefore be provided as part of the installation. In order to choose a pump of the right size, bear in mind the boiler’s waterside pressure drop, as shown in the following graph. 1,4 Pressuredidrop (m (m.c.a.) approx.) Perdite carico 12 check that all the pumps in the system rotate freely. Sludge and limescale can build up and cause seizure, especially after long periods of disuse. Novella 24, 31 1,2 1 0,8 Novella 45 0,6 0,4 0,2 0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 Flow rate(l/h) (l/h) Portata Fig. 2.14 IG FU LV LR RS TR TS TF Main switch Fuse Green “power on” LED indicator Red “burner lockout” LED warning light Burner reset button CH circuit temperature control Safety thermostat (manual reset) Flue gas thermostat (manual reset) PI AP VG EA ER CH pump Ignition and flame detection unit Gas supply solenoid valve Ignition electrode Flame detection sensor 2.11 Wiring diagram Fig. 2.15 13 INSTALLATION MANUAL 3 INSTALLATION 3.1 Installation standards 3.3 Installation in existing systems The boiler must be only be installed by qualified personnel in conformity to the following reference standards: -- UNI-CIG 7129 -- UNI-CIG 7131 -- IEC 64-8. Installers must also ensure conformity to fire prevention standards, gas safety standards and local bylaws. Perform the following checks before installing Novella boilers in existing systems. -- Check that the characteristics of the boiler’s pump (see the graph on page 12) are suitable for the existing system. Existing pumps are no longer needed. 3.2 Place of installation -- Make sure that the central heating circuit has been flushed out to remove all sludge and limescale, and that it has been properly de-aerated. Novella RAI boilers must be installed in rooms with vents that conform to applicable technical standards and safety legislation. -- Make sure that the system is fitted with safety and control devices that conform to applicable legislation and standards. aaBoilers must be installed indoors. They are not designed for outdoor use and are not fitted with automatic frost protection devices. 14 -- Check that the flue is large enough and suitable for the characteristics of the boiler. IMPORTANT Before installing the boiler, thoroughly flush out all pipes to remove any dirt and deposits that could compromise the correct functioning of the boiler. Install a water collector under the safety valve and connect it to the nearest drain to evacuate any water coming out of the safety in the event of overpressure. The domestic hot water circuit does not require a safety valve but the installer should nevertheless check that the water supply pressure does not exceed 6 bar. If necessary, install a pressure reducer. Before lighting the burner for the first time, make sure that the boiler is configured for use with the type of gas supplied. The type of gas is specified on the packaging label and on the boiler’s own name plate. Make sure that the flue is able to withstand the temperature of the flue gases and that it has been designed and made in conformity to applicable standards. The flue must also be as straight as possible, sealed, insulated and not blocked or choked. -- Check the hardness of the water supply to ascertain whether a softening system is required. Refer to the following values. REFERENCE VALUES pH 6-8 Electrical conductivity less than 200 mV/cm (25°C) Chlorine ions less than 50 ppm Sulphuric acid ions less than 50 ppm Total iron less than 0,3 ppm Alkalinity M less than 50 ppm Total hardness 35° F Sulphur ions none Ammonia ions none Silicon ions less than 30 ppm 3.4 Water connections Novella 24, 31 RAI PV Novella boilers are designed and made for use in central heating systems, but can also be used to generate domestic hot water if connected to a suitable storage cylinder. The specifications of the water fittings are as follows. MI RI Novella 24, 31 RAI PV boilers MI CH flow 3/4” M RI CH return 3/4” M AB Storage cylinder connection 3/4” M AB Fig. 3.1 Novella 24, 31, 45 RAI Novella 24, 31 RAI boilers MI CH flow RI CH return 3/4” M 3/4” M Novella 45 RAI boilers MI CH flow RI CH return 1” M 1” M bbThe choice of system components and the method of their installation are left up to the heating engineer installing the system. Installers must use their expertise to ensure proper installation and functioning in conformity to all applicable legislation. MI RI bbCircuits filled with anti-freeze must be fitted with water disconnectors. DESCRIPTION A Fig. 3.2 MODEL 24 RAI 31 RAI 45 RAI 64 28 28 mm 3.5 Electrical connections Use a multi-pole disconnector with a contact gap of at least 3 mm to connect the appliance to the mains electricity supply. The appliance functions on an alternating current supply of 230 V, 50 Hz. Consumption is 150 W. The appliance conforms to EN 60335-1 standard. bbThe following instructions are mandatory. -Install a multi-pole magnetic thermal trip switch and disconnector conforming to IEC-EN standards (with a contact gap of at least 3 mm). -Respect the polarity of the L1 (Phase) N (Neutral) connections. -Use cables with insulation and cross section conforming to applicable standards (minimum cross section 1.5 mm2). -Always refer to the electrical wiring diagrams in this manual when performing any electrical work. -Ensure that an efficient ground connection is provided. aaIt is strictly forbidden to use fuel and/ or water pipes to ground the appliance. The manufacturer declines all responsibility for damage caused by failing to ground the appliance adequately. 15 INSTALLATION MANUAL -- Unscrew the two fixing screws and remove the protective cover (A) from the casing (fig. 3.3). -- The electrical connection terminals are located underneath (fig. 3.3). -- Connect up the (optional) room thermostat and/or timer as shown in the electrical wiring diagrams in this manual. Fig. 3.3 -- Connect up the electrical power supply (fig. 3.4). 16 Fig. 3.4 -- Connect up the room thermostat (TA) (fig. 3.5). bbIf a room thermostat is connected, remove the bridge from terminals 4-5. bbThe contacts of the room thermostat must be able to function at a voltage of 230 V, 50 Hz. Fig. 3.5 3.6 Gas connections daia Novella RAI boilers must be connected to the methane or LPG gas supply in conformity to applicable standards (figs. 3.6 and 3.7). Perform the following checks before making the connection. -- Check that the boiler is compatible with the type of gas supply. -- Check that the gas supply pipes are thoroughly clean. GAS Fit a suitably sized filter in the gas supply pipe if the gas supply contains any solid particles. Fig. 3.6 GAS - Gas supply bbThe gas supply line must be suitable for the flow rate demanded by the burner. The gas supply must also be equipped with all the necessary safety and control devices required by applicable legislation and standards. bbOn completion of the installation, check that all joints are sealed in conformity to the relevant installation standards. GAS DESCRIPTION A GAS - Gas supply MODEL 24 RAI 31 RAI 45 RAI 50 28 36 mm Fig. 3.7 3.7 Gas supply conversion The boiler comes ready for use with methane gas (G20), but can be converted to work with LPG (G30/G31) using the conversion kit provided. Conversion must be performed by the manufacturer’s Technical Assistance Service. The boiler can be converted even after installation. To do so, proceed as follows. Fig. 3.8 REPLACING THE NOZZLES -- Remove the front panel from the casing. -- Unscrew the two nozzles from the methane burner and replace them with the LPG nozzles provided in the kit, using the aluminium seals also provided (fig. 3.8). 17 INSTALLATION MANUAL DISABLING THE PRESSURE REGULATOR For the boiler to work with LPG fuel, the pressure regulator on the valve group needs to be disabled. To do so, proceed as follows: -- Screw the pressure regulator screw (1) all the way in (fig. 3.9). -- Unscrew the pressure measurement point screw (A) about 3 turns and connect up the pressure gauge (fig. 3.9). A SMOOTH IGNITION -- Turn the ignition adjuster screw (B) to obtain the correct pressure for smooth ignition (fig. 3.10). Fig. 3.9 Start up the boiler as instructed on page 21. NOZZLE PRESSURE -- Adjust the pressure regulator on the LPG supply until the pressure gauge reads out the value specified in the table below (fig. 3.11): 24 RAI G30 18 1 31 RAI G31 G30 G31 B Fig. 3.10 45 RAI G30 G31 28,4 36,5 28,8 34,7 27,8 35,7 mbar -- Disconnect the pressure gauge and close the pressure measurement point. Fig. 3.11 -- Check the tightness of all the joints disconnected previously. -- Apply the LPG label supplied with the boiler to the inside of the boiler casing (fig. 3.12). -- Remove any METHANE (G20) labels from the outside and inside of the boiler casing (fig. 3.12). Country of destination: __ 0694 Tipo de aparato : C13,C33,C43,C53,C63 Categoría del aparato : II2H3P Boiler configured for: G30+G32 28-30/37 mbar L.P.G. Country of destination: .... Presión alimentación gas: G20 20 mbar G31 37 mbar Regulación realizado por el fabricante: G20 - 20 mbar - 2H METANO ATENCIÓN Leer cuidadosamente el manual de instrucciones antes de la instalación y puesta en servicio de la caldera. Fig. 3.12 3.8 Flue gas vent and air intake Flues and stack connections must be made in conformity to all applicable local and national laws and standards. The use of rigid pipes is mandatory. All joints between pipe sections must be hermetically sealed and all parts of the flue must be resistant to high temperatures, condensate and mechanical stress. bbNovella boilers are equipped with a flue gas thermostat, located inside the hood. This thermostat shuts down the boiler immediately in the event of flue gas blowback. Fig. 3.13 bbUninsulated flue pipes are potentially dangerous and can cause burns. MODEL DESCRIPTION 24 RAI 31 RAI 45 RAI B 72 77 97 mm ØI 132 142 182 Ø mm 3.9 Filling the water circuit Novella RAI boilers must be fitted with a water circuit filling system connected to the central heating return line (fig. 3.14). RI Fig. 3.14 -- Make sure that the boiler drain cock is closed before attempting to fill the boiler (fig. 3.5) Fig. 3.15 -- Open the water circuit shut-off cocks and slowly fill the circuit until the pressure gauge reads out a value of 1.5 bar (cold) -- Close the water circuit shut-off cocks(fig. 3.16). RI Fig. 3.16 19 INSTALLATION MANUAL 20 3.10 Emptying the water circuit -- Turn the electricity supply off by switching the boiler’s mains power switch and control panel switch OFF (0) before starting to empty the boiler (fig. 3.17). ON OFF Fig. 3.17 -- Make sure that the water circuit shut-off cocks are closed. -- Connect a rubber hose to the hose union on the boiler’s drain cock and open the cock (fig. 3.18). Fig. 3.18 4 START-UP AND FUNCTIONING 4.1 Preliminary checks Remove the front panel of the boiler and perform the following checks before switching the boiler on or testing any of its functions. -- Check that the fuel and water circuit shut-off cocks are open -- Check that the type and pressure of the gas supply are as specified for the boiler -- Check that the water circuit pressure gauge shows a pressure over 1 bar with the system cold. Check also that the central heating circuit is properly de-aerated. -- Check that the pressure in the central heating circuit expansion vessel is sufficient (about 1 bar). -- Check that the electrical connections to the mains supply and to the system’s control and safety devices have been made correctly. -- Check that the flue is properly constructed. 4.2 Ignition Once you have completed all the preparatory steps, proceed as follows to start up the boiler for the first time. -- Turn the boiler’s mains power switch ON (fig. 4.1). Fig. 4.1 -- Set the room thermostat to the required temperature (~ 20°C) or, if the system has a timer or timer-thermostat, make sure that this is switched “On” and adjusted to the required temperature (~ 20°C) (fig. 4.2). Fig. 4.2 -- Adjust the boiler’s own temperature control to the desired temperature (not necessary if the boiler is equipped with a temperature controller) (fig. 4.3). Fig. 4.3 -- Switch the boiler on at the control panel switch and check that the green power indicator lights (fig. 4.4). Fig. 4.4 21 INSTALLATION MANUAL The boiler will now start up and the burner will remain lit until the set temperature is reached. If any ignition or functioning errors occur, the boiler enters “LOCK-OUT” and the red LED on the control panel comes on to indicate this (fig. 4.5). Proceed as follows to reset the safety thermostat. Fig. 4.5 -- Wait for about 1 minute, then press the "burner reset" button (fig. 4.6). -- Wait for the burner to complete the entire start-up cycle again, up to the ignition of the flame. The boiler will also shut down if the flue gas thermostat trips. To reset the boiler in this case, remove the hood and reset the flue gas thermostat (fig. 4.7). Fig. 4.6 bbIf the flue gas thermostat trips repeatedly, make sure that the flue gas pipes are not blocked and that the flue is properly constructed. 22 Fig. 4.7 4.3 Final checks Once the boiler has started up, make sure that it shuts down and re-starts properly when the following actions are taken. Fig. 4.8 -- The boiler’s temperature control is turned down (fig. 4.8). -- The control panel switch is switched OFF (fig. 4.8). -- The temperature setting on the room thermostat or timer is reduced (fig. 4.9). Fig. 4.9 -- Make sure that the pump (if fitted) is free and rotates in the right direction (fig. 4.10). -- Turn the mains power switch OFF and make sure that the boiler shuts down completely. Provided these conditions are satisfied, restart the boiler. Fig. 4.10 23 ON OFF Fig. 4.11 INSTALLATION MANUAL 5 SHUT-DOWN If the boiler is not going to be used for an extended period of time, perform the following operations. -- Switch the boiler off at the control panel switch and check that the green power indicator goes out (fig. 5.1). Fig. 5.1 -- Turn the mains power switch OFF (fig. 5.2). ON OFF -- Close the boiler’s fuel cock and water circuit cocks (fig. 5.3). Fig. 5.2 bbEmpty the boiler if there is any risk of freezing. Fig. 5.3 24 6 MAINTENANCE To maintain maximum functionality and efficiency, and to comply with applicable legislation, have the boiler serviced at regular intervals. The frequency at which servicing should be performed depends on installation and operating conditions. The boiler should nevertheless be inspected by specialist personnel from the manufacturer’s Technical Assistance Service at least once a year. Always switch the boiler off if any work or servicing has to be done on other equipment installed near the flue gas vent pipes and/or flues and associated accessories. On completion of work, have the efficiency of the flue checked by qualified personnel. bbSwitch the boiler off at its control panel and at the mains power switch, and turn the gas supply off by closing the gas shut-off cock before performing any cleaning or maintenance on the boiler. 6.1 Scheduled maintenance Scheduled maintenance normally consists of the following operations: -- Remove encrustations from the burner. -- Remove encrustations from the heat exchangers. -- Check and clean the flue pipes. -- Check the efficiency of the external casing. -- Check the ignition, normal functioning and shutdown of the boiler in DHW and CH modes. -- Check the tightness of the gas and water pipe joints. -- Check gas consumption at maximum and minimum power. -- Check the position of the ignition electrode and flame detection sensor. -- Check the gas failure safety system. Do not use flammable substances (e.g. petrol, alcohol etc.) to clean the boiler or any of its parts. Do not use paint thinners to clean the casing or any painted or plastic parts of the boiler. Use only soapy water to clean the boiler casing. 6.2 Extraordinary maintenance Extraordinary maintenance involves actions designed to restore the functioning of the boiler to its design specifications and to ensure conformity to legal requirements after a failure or malfunction. These actions can be: -- Replacement of parts -- Repairs -- Reconditioning of parts. These actions generally require special tools and equipment. 25 INSTALLATION MANUAL 7 OPTIONAL ACCESSORIES Wall-mounted weekly timer thermostat (fig. 7.1) (part number 1100279). Fig. 7.1 Pump or valve controlled multizone central heating kit with total shut-down function (fig. 7.2) (part number 696439). Fig. 7.2 RO120 storage cylinder (fig. 7.3) (part number 696339). 26 Fig. 7.3 Pump manifold (fig. 7.4) (part number 694769). Fig. 7.4 High head pump (fig. 7.5) (part number 1100269). Fig. 7.5 Cod. 20048744 - 02/12 Ed. 0 Via Risorgimento, 13 - 23900 Lecco (LC) Servizio Clienti 199.13.31.31* Assistenza Tecnica Numero Unico 199.12.12.12* www.berettaclima.it Beretta is constantly improving its products and therefore reserves the right to modify the characteristics and specifications of the appliance described in this manual at any time and without prior notice. The contents of this manual are not contractually binding on the manufacturer.