235700-01 Reviewed Coils and Heat Exchangers Submittal Review

Transcription

235700-01 Reviewed Coils and Heat Exchangers Submittal Review
SUBMITTAL REVIEW
To:
Intergroup Architects
2000 W. Littleton Blvd
Littleton, CO 80120
Attention:
Ryan Brown
Project:
UCH Garfield/FMC Suites
Date:
5/29/2015
TBG Project No:
15013
We are transmitting the following shop drawings with comments listed below.
NET:
RR:
CMT:
No Exceptions Taken
Revise and Resubmit
See Comment Below
Copies
pdf
MCN:
SSI:
Make Corrections Noted
Submit Specified Item
Item
Manufacturer
Received 5/22/2015
FUR-2,3,5
FUR-6
CU-2,3,5
CU-6
ZONEX
SYSTEM
COMPONENTS
Carrier 59TN6A100V21--22
Carrier 59TB6A120V24--22
Carrier 24ABC648A003
Carrier 24ABC660A003
Zonex System 2000 GEN II
Zonex 101AHDM
Zonex RZKIT
Zonex SAMOD II
Zonex 101ASPC
Zonex ModStat/MODS2
Zonex GCLK
Zonex STMRTD
RX:
Rejected
NET MCN RR RX SSI
CMT
X
X
X
X
1
3
1
1
X
2
X
X
X
X
X
X
X
Comments:
1.
MC to coordinate revised power requirements with Electrical Contractor.
2.
Provide Zonex STMPD (ZCD-7-6 & ZCD-8-5) and STBP (ZBD-7 & ZBD-8) as indicated on
schedule. Contractor to verify all existing duct sizes prior to ordering equipment.
3.
Per Note 7 on the Air Delivery Table (pdf page 15) airflows over 1800 cfm requires bottom or side
and bottom return connections. Set FUR-6 on 12” tall plenum box connect to side and bottom of
furnace.
Signed:
Austin Kempsell / Matt Doll
Q:\15\15013\Construction\Submittals\HVAC\15013 235700-01 Coils and Heat Exchangers Submittal Review 150527.doc
Lakewood:
Fort Collins:
2525 South Wadsworth Blvd., Suite 200
Lakewood, CO 80227
4730 South College Ave., Suite 203
Fort Collins, CO 80525
www.TheBallardGroup.com
P: 303-988-4514
P: 970-568-8762
F: 303-988-4517
F: 303-988-4517
Submittal Stamp Sheet
UCH Garfield/FMC Suites
Project:
Phipps’ Job #: 15D5138
Submittal #: 235700-01 Coils and Heat Exchangers
Gerald H. Phipps, Inc.:
Architect:
SUBMITTED
GH Phipps
Construction Companies
GH Phipps has reviewed, approved, and
herby submits the attached in accordance
with the contract documents.
Note to Subcontractor/Material Supplier:
Subcontractor/Material Supplier remains
responsible for the confirmation and
correlation of dimensions at the jobsite;
fabrication processes and construction
techniques; coordination of the work with
the work of other trades; and satisfactory
performance of the work.
Engineer:
Other:
NO EXCEPTIONS TAKEN
MAKE CORRECTIONS NOTED
REJECTED
REVISE AND RESUBMIT
SUBMIT SPECIFIED ITEM
CHECKING IS ONLY FOR GENERAL CONFORMANCE WITH THE
DESIGN CONCEPT OF THE PROJECT AND GENERAL COMPLIANCE
WITH THE INFORMATION GIVEN IN THE CONTRACT DOCUMENTS.
ANY ACTION SHOWN IS SUBJECT TO THE REQUIREMENTS OF THE
PLANS AND SPECIFICATIONS. CONTRACTOR IS RESPONSIBLE
FOR: DIMENSIONS WHICH SHALL BE CONFIRMED AND
CORRELATED AT THE JOB SITE; FOR QUANTITIES OF EQUIPMENT;
FABRICATION PROCESSES AND TECHNIQUES OF CONSTRUCTION;
COORDINATION OF HIS WORK WITH THAT OF ALL OTHER TRADES;
AND SATISFACTORY PERFORMANCE OF HIS WORK.
The Ballard Group, Inc.
Mechanical Consulting Engineers
05/27/2015
AKemp
DATE: ________________________
BY: ______________________________________
sell
SEE ATTACHED SUBMITTAL REVIEW FORM FOR ACTION TAKEN & COMMENTS
NOTES:
Signed:
GH Phipps Representative
Transmittal of Submittal
May 19, 2015
GH Phipps Construction Company
5995 Greenwood Plaza Blvd., Suite 100
Greenwood Village, CO 80111
Attention:
Blain Dodgion
Reference: Poudre Valley Health - UCH & FMC Renovation
1025 Garfield Street
Subject:
Submittals for Specification Section 23 57 00
Dear Blain:
RK Mechanical, Inc. is providing GH Phipps Construction Company the enclosed submittals for Specification
Section 23 57 00 - Coils and Heat Exchangers, as listed below:
ITEM
COPIES
REV
1
1
0
2
1
3
1
4
5
SUBMITTAL DESCRIPTION
STATUS
DUE BACK
FUR-5,6
For Approval
05/26/2015
0
CU-5,6
For Approval
05/26/2015
0
FUR-1,2
For Approval
05/25/2015
1
0
CU-1,2
For Approval
05/25/2015
1
0
HVAC Control System
For Approval
05/26/2015
Your immediate review and processing is requested to ensure these submittals are returned back to RK
Mechanical, Inc. on or before the DUE BACK date(s) listed above.
We are available to discuss any comments or questions you may have concerning these submittals.
Sincerely,
RK Mechanical, Inc.
Matthew Kaufman
xc: RK Job # 5086- Main Files
3800 Xanthia Street
Denver, Colorado 80238
ph: 303.355.9696
fx: 303.355.8666
www.rkmi.com
Carrier/Payne units
Carrier West
4800 Osage St Denver CO 80221
x
303-825-4328
SUBMITTAL COVER SHEET
JOB:
PVH UCH Macc Team and FMC Renovation
LOCATION:
Fort Collins
CONTRACTOR:
RK Mechanical Inc
ENGINEER:
CCRD
NUMBER OF SUBMITTALS:
1
EQUIPMENT
TAG
QTY
MODEL NUMBER
DESCRIPTION
FUR-5
59TN6A100V21--22
100k btuh, 5 ton, ECM 21” Furnace
FUR-6
59TN6A120V24--22
120K btuh, 5 ton ECM 24” Furnace
CU-5
24ABC648A003
16 SEER 4 ton CU 208-1
CU-6
24ABC660A003
16 SEER 5 ton CU 208-1
FUR-2,3
59TN6A100V21--22
100k btuh, 5 ton, ECM 21” Furnace
CU-2,3
24ABC648A003
16 SEER 4 ton CU 208-1
ZONEX
GEN II, 101AHDM/RZKIT,
SAMOD, 101ASPC/RZKIT
Zonex Universal System Controller, Retrofit
Zone Controller, Auto Change Over Stand Alone
Controller, Retrofit Bypass Controller
LOHMILLER & COMPANY CERTIFIES THE ABOVE DATA TO BE A TRUE ABSTRACT OF
MANUFACTURES’ CURRENT RATINGS FOR THE PRODUCTS SHOWN.
DATE: 5/19/15
4800 OSAGE STREET
PREPARED BY: Chris Hill
DENVER, COLORADO 80221
PHONE: (303) 825-4328
WWW.LOHMILLER.COM
FAX: (303) 820-2302
Submittal Cover Sheet
Date Submitted:
May 19, 2015
Date Due Back:
May 26, 2015
RK Submittal No.:
235700.00 - 0
Specification Section:
23 57 00 - Coils and Heat Exchangers
Project Name:
Poudre Valley Health - UCH & FMC Renovation
1025 Garfield Street
General Contractor:
GH Phipps Construction Company
5995 Greenwood Plaza Blvd., Suite 100
Greenwood Village, CO 80111
Mechanical Contractor:
RK Mechanical, Inc.
3800 Xanthia Street
Denver, CO 80238
Subcontractor/Supplier:
RK Mechanical, Inc.
3800 Xanthia Street
Denver, CO 80238
ITEM
COPIES
REV
1
1
0
SUBMITTAL DESCRIPTION
DRAWING
MANUFACTURER
FUR-5,6
3800 Xanthia Street
Denver, Colorado 80238
ph: 303.355.9696
fx: 303.355.8666
www.rkmi.com
TAG
FUR - 5
Model
59TN6A100V21--22
Qty
1
Voltage
115-1-60
4800 OSAGE STREET
DENVER, COLORADO 80221
PHONE: (303) 825-4328
WWW.LOHMILLER.COM
FAX: (303) 820-2302
TAG
FUR-6
Model
59TN6A120V24--22
Qty
1
Voltage
120-1-60
4800 OSAGE STREET
DENVER, COLORADO 80221
PHONE: (303) 825-4328
WWW.LOHMILLER.COM
FAX: (303) 820-2302
59TN6A
InfinityR Two---Stage, Variable Speed
4---Way Multipoise
Condensing Gas Furnace
Series 1
Product Data
A11263
The 59TN6A Multipoise Variable--Speed Condensing Gas Furnace
features the two--stage InfinityR System. The Comfort Heat
TechnologyR two--stage gas system is at the heart of the comfort
provided by this furnace, along with the Infinity variable--speed
ECM blower motor, and two--speed inducer motor. With an
Annual Fuel Utilization Efficiency (AFUE) of up to 96.7%, the
Infinity two--stage gas furnace provides exceptional savings when
compared to a standard furnace. This Infinity Gas Furnace also
features 4--way multipoise installation flexibility, and is available
in five model sizes. The 59TN6A can be vented for direct
vent/two--pipe, ventilated combustion air, or single--pipe
applications. A Carrier Infinity Control and Infinity Air
Conditioner or Heat Pump can be used to form a complete Infinity
System. All units meet California Air Quality Management District
emission requirements. All sizes are design certified in Canada.
STANDARD FEATURES
S InfinityR System; compatible with single-- and multiple--zone
Infinity systems.
S All sizes meet ENERGY STARR Version 4.0 criteria for gas
furnaces: 95+ AFUE; AMACF electrical rating; 2% or less
cabinet airflow leakage.
S Quiet operation. Compare for yourself at HVACpartners.com.
S Ideal height 35--in. (889 mm) cabinet: short enough for taller
coils, but still allows enough room for service.
S Infinity Features—match with the Infinity Control for Infinity
System benefits.
S Integral part of the Ideal Humidity SystemR Technology.
S Silicon Nitride Power Heat Hot Surface Igniter.
S SmartEvap technology helps control humidity levels in the
home when used with a compatible humidity control system.
S ComfortFan technology allows control of continuous fan
speed from a compatible thermostat.
S External Media Filter Cabinet included.
S 4--way multipoise design for upflow, downflow or horizontal
installation, with unique vent elbow and optional through-the--cabinet downflow venting capability.
S Variable--Speed blower motor, two--speed inducer motor, and
two--stage gas valve.
S Self--diagnostics and extended diagnostic data through the
Advanced Product Monitor (APM) accessory or Infinity User
Interface.
S Adjustable blower speed for cooling, continuous fan, and
dehumidification.
S Aluminized--steel primary heat exchanger.
S Stainless--steel condensing secondary heat exchanger.
S Propane convertible (See Accessory list).
S Factory--configured ready for upflow applications.
S Fully--insulated casing including blower section.
S Convenient Air Purifier and Humidifier connections.
S Direct--vent/sealed combustion, single--pipe venting or
ventilated combustion air.
S Installation flexibility: (sidewall or vertical vent).
S Residential installations may be eligible for consumer financing
through the Retail Credit Program.
S Certified to leak 2% or less of nominal air conditioning CFM
delivered when pressurized to 1--in. water column with all
present air inlets, air outlets, and condensate drain port(s) sealed.
Always Ask For
CERTIFIED
1
Use of the AHRI Certified TM Mark indicates a
manufacturer’s participation in the program. For
verification of certification for individual products,
go to www.ahridirectory.org.
SAP ORDERING
NO.
F-5,2,3
F-6
59TN6A060V17--14
59TN6A080V17--14
59TN6A080V21--20
59TN6A100V21--22
59TN6A120V24--22
CASING
DIMENSIONS
(IN.)
H
D
35
35
35
35
35
30
30
30
30
30
W
RATED HEATING
OUTPUT† (BTUH)
High
17.5 58,000
17.5 78,000
21.0 78,000
21.0 98,000
24.5 117,000
Low
AFUE
38,000
50,000
51,000
63,000
76,000
96.3%
96.2%
96.7%
96.1%
96.7%
HEATING AIRFLOW
CFM‡
(Low
Heating)
855
1060
1095
1385
1640
CFM
(High
Heating)
1075
1500
1345
1575
1820
Rated
High Heating
ESP
0.12
0.15
0.15
0.20
0.20
† Capacity in accordance with DOE test procedures. Ratings are position dependent. See rating plate.
‡ Heating CFM at factory default blower motor heating settings.
constant
ESP --- External Static Pressure
59TN6A
FEATURES AND BENEFITS
Comfort Heat TechnologyR feature — This feature with
Adaptive Control is a proprietary function that promotes
homeowner comfort through two stages of heating. This Carrier
furnace offers a patented algorithm that continually monitors and
adjusts furnace operation by looking at both current and past
conditions to determine the most effective stage of heating and the
amount of time to run each stage, every cycle.
Ideal Humidity SystemR Technology — The Ideal Humidity
system actively controls both temperature and humidity in the
home to provide the best comfort all year long. Other systems
depend on heating or cooling demand to manage the moisture in
the air. But, Ideal Humidity gives the homeowner the right amount
of humidity day and night, even in mild weather. No other
manufacturer can do this! Ideal Humidity saves energy, too. By
keeping humidity under control, the homeowner can set their
thermostat lower to stay comfortable and save energy.
SmartEvapt Technology — When paired with a compatible
thermostat, this dehumidification feature overrides the cooling
blower off-delay when there is a call for dehumidification. By
deactivating the blower off-delay, SmartEvap technology prevents
condensate that remains on the coil after a dehumidification cycle
from re-humidifying throughout the home. This results in reduced
humidity and a more comfortable indoor environment for the
homeowner.
Unlike competitive systems, SmartEvap technology only overrides
the cooling blower off--delay when humidity control is needed.
Once humidity is back in control, SmartEvap re-enables the
energy-saving cooling blower off-delay.
ComfortFant Technology — Sometimes the constant fan setting
on a standard furnace system can actually reduce homeowner
comfort by providing too much or too little air! Comfort Fan
technology improves comfort all year long by allowing the
homeowner to select the continuous fan speed of their choice using
a compatible thermostat.
HYBRID HEATR Dual Fuel System — This system can provide
more control over your monthly energy bills by automatically
selecting the most economical method of heating. With HYBRID
HEAT components, our system automatically switches between the
gas furnace and the electric heat pump as outside temperatures
change to maintain greater efficiency and comfort than with any
traditional single-source heating system. The heat pump also
delivers high-efficiency cooling in the summer.
Power Heatt Igniter — Carrier’s unique SiN igniter is not only
physically robust but it is also electrically robust. It is capable of
running at line voltage and does not require complex voltage
regulators as do other brands. This unique feature further enhances
the gas furnace reliability and continues Carrier’s tradition of
technology leadership and innovation in providing a reliable and
durable product.
Full-Featured, Communicating, Variable Speed Motors — Our
ECMs (Electronically Commutated Motors) provide variable-speed
operation to optimize comfort levels in the home year round;
features such as passive/active dehumidification, ramping profiles,
COOLING
CFM @ 0.5
ESP
MOTOR HP
(VARIABLE
SPEED)
MEDIA
CABINET
SUPPLIED
(IN.)
APPROX.
SHIP WT.
(LB)
510 - 1335
490 - 1375
750 - 1945
715 - 2160
885 - 2185
1/2
1/2
1
1
1
16
16
20
20
24
140
150
155
165
189
air flow and quiet operation. They can provide cooling
match enhancements to increase the effective SEER of select
Carrier air conditioner or heat pump system, and feature the highest
efficiency of all indoor fan motors.
Reliable Heat Exchanger Design — The aluminized steel, clam
shell primary heat exchanger was re--engineered to achieve greater
efficiency out of a smaller size. The first two passes of the heat
exchanger are based on the current 80% product, a design with
more than ten years of field-proven performance and success.
These innovations, paired with the continuation of a crimped,
no-weld seam create an efficient, robust design for this essential
component.
The condensing heat exchanger, a stainless steel fin and tube
design, is positioned in the furnace to extract additional heat.
Stainless steel coupling box componentry between heat exchangers
has exceptional corrosion resistance in both natural gas and
propane applications.
Media Filter Cabinet — Enhanced indoor air quality in the home
is made easier with our media filter cabinet—a standard accessory
on all deluxe furnaces. When installed as a part of the system, this
cabinet allows for easy and convenient addition of a Carrier high
efficiency air filter.
4-Way Multipoise Design — One model for all applications –
there is no need to stock special downflow or horizontal models
when one unit will do it all. The new heat exchanger design allows
these units to achieve the certified AFUE in all positions.
Direct or Single-pipe Venting, or Optional Ventilated
Combustion Air — This furnace can be installed as a 2-pipe
(Direct Vent) furnace, in an optional ventilated combustion air
application, or in single-pipe, non-direct vent applications. This
provides added flexibility to meet diverse installation needs.
Sealed Combustion System — This furnace brings in combustion
air from outside the furnace, which results in especially quiet
operation. By sealing the entire combustion vestibule, the entire
furnace can be made quieter, not just the burners.
Insulated Casing — Foil-faced insulation in the heat exchanger
section of the casing minimizes heat loss. The acoustical insulation
in the blower compartment reduces air and motor noise for quiet
operation.
Monoport Burners — The burners are specially designed and
finely tuned for smooth, quiet combustion and economical
operation.
Bottom Closure — Factory-installed for side return; easily
removable for bottom return. The multi-use bottom closure can
also serve for roll-out protection in horizontal applications, and act
as the bottom closure for the optional return air base accessory.
Blower Access Panel Switch — Automatically shuts off 115-v
power to furnace whenever blower access panel is opened.
Quality Registration — Our furnaces are engineered and
manufactured under an ISO 9001 registered quality system.
Certifications — This furnace is CSA (AGA and CGA) design
certified for use with natural and propane gases. The furnace is
factory--shipped for use with natural gas. A CSA listed gas
conversion kit is required to convert furnace for use with propane
gas. The efficiency is AHRI efficiency rating certified. This furnace
meets California Air Quality Management District emission
requirements.
2
SPECIFICATIONS
Heating Capacity and Efficiency
High
Heat
Input
Low
Heat
High
Heat
Output
Low
Heat
Efficiency
Certified Temperature
Rise Range ºF (ºC)
Airflow Capacity and Blower Data
Rated External Static
Pressure (in. w.c.)
Airflow Delivery
@ Rated ESP (CFM)
Cooling Capacity (tons)
Direct-Drive Motor Type
Direct-Drive Motor HP
Motor Full Load Amps
RPM Range
Speed Selections
Blower Wheel Dia x Width
method to calculate heating load estimates and select the furnace.
Excessive oversizing of the furnace may cause the furnace and/or
vent to fail prematurely, customer discomfort and/or vent freezing.
Failure to follow these guidelines is considered faulty installation
and/or misapplication of the furnace; and resulting failure, damage,
or repairs may impact warranty coverage.
060-14
080-14
080-20
100-22
120-22
(BTUH)
60,000
80,000
80,000
100,000
120,000
(BTUH)
39,000
52,000
52,000
65,000
78,000
(BTUH)
58,000
78,000
78,000
98,000
117,000
(BTUH)
38,000
50,000
51,000
63,000
76,000
96.3
35 - 65
(19 - 36)
30 - 60
(17 - 33)
96.2
40 - 70
(22 - 39)
30 - 60
(17 - 33)
96.7
40 - 70
(22 - 39)
30 - 60
(17 - 33)
96.1
45 - 75
(25 - 42)
30 - 60
(17 - 33)
96.7
45 - 75
(25 - 42)
30 - 60
(17 - 33)
AFUE % (ICS)
High Heat
Low Heat
Heating
Cooling
High Heat
Low Heat
Cooling
400 CFM/ton
350 CFM/ton
060-14
0.12
0.5
1075
855
1335
3
3.5
080-14
080-20
100-22
0.15
0.15
0.20
0.5
0.5
0.5
1500
1345
1575
1060
1095
1385
1375
1945
2160
3.5
4.5
5
4
5.5
6
Electronically Commutated Motor (ECM)
1/2
1
1
7.7
12.8
12.8
300 - 1300
Variable (Communicating)
11 x 8
11x10
11 x 10
Factory Supplied Media Cabinet
Field Supplied Filter
KGAWF**06UFR
1/2
7.7
in.
11 x 8
Air Filtration System
Filter Used for Certified Watt Data*
Electrical Data
Input Voltage
Operating Voltage Range
Maximum Input Amps
Unit Ampacity
Minimum Wire Size
Maximum Wire Length
@ Minimum Wire Size
Maximum Fuse/Ckt Bkr
(Time-Delay Type Recommended)
Transformer Capacity (24vac
output)
External Control Power
Available
Controls
Gas Connection Size
Burners (Monoport)
Gas Valve (Redundant)
060-14
080-14
Volts-Hertz-Phase
080-20
120-22
0.20
0.5
1820
1640
2185
5.5
6
1
12.8
11 x 11
100-22
120-22
115-60-1
Min-Max
Amps
Amps
AWG
Feet
(M)
8.5
11.5
14
32
(9.8)
8.5
11.5
14
32
(9.8)
104-127
13.6
17.9
12
32
(9.8)
13.7
18.0
12
31
(9.4)
13.7
18.0
12
31
(9.4)
Amps
15
15
20
20
20
100-22
120-22
5
6
40 VA
Heating
Cooling
24.3 VA
34.6 VA
060-14
080-14
3
4
Manufacturer
Minimum Inlet Gas pressure (in. wc)
Maximum Inlet Gas pressure (in. wc)
Manufactured (Mobile) Home Kit
Ignition Device
Limit Control
Heating Blower Control (Heating Off-Delay)
Cooling Blower Control (Time Delay Relay)
080-20
1/2" - NPT
4
White Rogers
4.5
13.6
not approved for MH use
Silicon Nitride
170
200
180
Adjustable: 90, 120, 150, 180 seconds
90 seconds
180
3
160
59TN6A
The furnace should be sized to provide 100 percent of the design
heating load requirement plus any margin that occurs because of
furnace model size capacity increments. None of the furnace
model sizes can be used if the heating load is 20,000 BTU or
lower. Use Air Conditioning Contractors of America (Manual J
and S); American Society of Heating, Refrigerating, and
Air-Conditioning Engineers; or other approved engineering
SPECIFICATIONS (CONT.)
Communication System
Thermostat Connections
Accessory Connections
Infinity; Infinity Zoning
R, W/W1, W2 Y/Y2, Y1, G, Com 24V, DHUM
EAC (115vac); HUM (24vac); 1-stg AC (via Y/Y2)
* See Accessory List for part numbers available.
MODEL NUMBER NOMENCLATURE
Example of Model Number
1-2
Family
59
3
Htg. Stages
T
4
Tier
N
5
Base Effy.
6
6
Major Series
A
7-9
Htg. Cap.
11 - 12
Width
17
10
Motor
V
060
13
Voltage
--
14
Minor Series
--
08 - 800 CFM
10 - 1000 CFM
12 - 1200 CFM
14 - 1400 CFM
16 - 1600 CFM
18 - 1800 CFM
20 - 2000 CFM
22 - 2200 CFM
Family
S - Single Stage
T - Two Stage
M - Modulating
59TN6A
C - Comfort
P - Performance
N - Infinity
0 - +90 AFUE
2 - +92 AFUE
3 - +93 AFUE
5 - +95 AFUE
6 - +96 AFUE
7 - +97 AFUE
14 - 14.2”
17 - 17.5”
21 - 21.0”
24 - 24.5”
Major Series
15 - 16
Airflow
14
Minor Series
Voltage
040=40,000 BTU
060=60,000 BTU S - Standard
080=80,000 BTU E - Energy Efficient
100=100,000 BTU V - Variable Speed
120=120,000 BTU
140=140,000 BTU
Not all familes have these models.
A12373
FURNACE COMPONENTS
GAS BURNER
HOT SURFACE
IGNITER
MANUAL RESET
ROLLOUT SWITCH
FLAME
SENSOR
MANUAL RESET
ROLLOUT SWITCH
GAS VALVE
MAIN LIMIT SWITCH
(BEHIND GAS VALVE)
OPERATING INSTRUCTIONS
NOT SHOWN (LOCATED ON
MAIN FURNACE DOOR, SEE
OPERATING INSTRUCTIONS
INSIDE DOOR FIGURE).
INDUCER MOTOR
ASSEMBLY
ELECTRICAL JUNCTION
BOX (IF REQUIRED,
LOCATION MAY VARY)
BLOWER DOOR
SAFETY SWITCH
MEDIA CABINET
BLOWER AND
MOTOR
FURNACE
CONTROL
BOARD
CAPACITOR/
POWER CHOKE
(IF USED)
RATING PLATE NOT SHOWN
(LOCATED ON BLOWER DOOR)
REPRESENTATIVE DRAWING ONLY, SOME MODELS MAY VARY IN APPEARANCE.
A11408
4
ACCESSORIES
Venting Accessories
Vent Kit - Through the Cabinet
Vent Terminal - Concentric - 2” (51 mm)
Vent Terminal - Concentric - 3” (76 mm)
Vent Terminal Bracket - 2” (51 mm)
Vent Terminal Bracket - 3” (76 mm)
Vent Kit --- Rubber Coupling
Condensate Drainage Accessories
Freeze Protect Kit - Heat Tape
CPVC to PVC Drain Adapters - 1/2” CPVC to 3/4” PVC
Horizontal Trap Grommet - Direct Vent
Condensate Neutralizer Kit
External Trap Kit
Ductwork Adapter Accessories
Furnace Base Kit for Combustible Floors
Coil Adapter Kits --- No Offset
Coil Adapter Kits --- Single Offset
Coil Adapter Kits --- Double Offset
Return Air Base (Upflow Applications) 17.5--- in. wide
Return Air Base (Upflow Applications) 21.0--- in. wide
Return Air Base (Upflow Applications) 24.5--- in. wide
IAQ Device Duct Adapters 20.0--- in. IAQ to 16 in. Side Return
IAQ Device Duct Adapters 24.0--- in. IAQ to 16 in. Side Return
Gas Conversion Accessories
Gas Conversion Kit - Nat to LP; Var-speed Products
Gas Conversion Kit - LP to Nat; Var-speed Products
Gas Orifice Kit - #42 (Nat Gas)
Gas Orifice Kit - #43 (Nat Gas)
Gas Orifice Kit - #44 (Nat Gas)
Gas Orifice Kit - #45 (Nat Gas)
Gas Orifice Kit - #46 (Nat Gas)
Gas Orifice Kit - #47 (Nat Gas)
Gas Orifice Kit - #48 (Nat Gas)
Gas Orifice Kit - #54 (LP)
Gas Orifice Kit - #55 (LP)
Gas Orifice Kit - #56 (LP)
Gas Orifice Kit - 1.25mm (LP)
Gas Orifice Kit - 1.30mm (LP)
Control Accessories
ECM Motor Simulator Kit
Advanced Product Monitor - APM
Infinity Touch Control --- Wi--- Fi
Infinity Touch Control --- Non--- Wi--- Fi
IAQ Accessories
Filter Pack (6 pack) --- Washable - 16x25x1 (406x635x25 mm)
Filter Pack (6 pack) --- Washable - 24x25x1 (610x635x25 mm)
EZ-Flex Filter - 16” (406 mm)
EZ-Flex Filter - 20” (508 mm)
EZ-Flex Filter - 24” (610 mm)
EZ-Flex Filter with End Caps - 16” (406 mm)
EZ-Flex Filter with End Caps - 20” (508 mm)
EZ-Flex Filter with End Caps - 24” (610 mm)
Cartridge Media Filter - 16” (406 mm)
Cartridge Media Filter - 20” (508 mm)
Cartridge Media Filter - 24” (610 mm)
Carrier Infinity Air Purifier - 16x25 (406x635 mm)
Carrier Infinity Air Purifier - 20x25 (508x635 mm)
Carrier Infinity Air Purifier Repl. Filter- 16x25 (406x635 mm)
Carrier Infinity Air Purifier Repl. Filter- 20x25 (508x635 mm)
Carrier Performance Air Purifier - 16x25 (508x635 mm)
Carrier Performance Air Purifier - 20x25 (508x635 mm)
Carrier Performance Air Purifier Repl Filter - 16x25 (406x635 mm)
Carrier Performance Air Purifier Repl. Filter - 20x25 (508x635 mm)
PART NUMBER
060-14 080-14 080-20 100-22 120-22
KGADC0101BVC
KGAVT0701CVT
KGAVT0801CVT
KGAVT0101BRA
KGAVT0201BRA
KGAAC0101RVC
D
KGAHT0101CFP
KGAAD0110PVC
KGACK0101HCK
P908--- 0001
KGAET0201ETK
D
D
D
D
D
D
See Venting Tables
See Venting Tables
D
D
D
D
D
D
D
D
All DV Horizontal
D
D
D
D
D
D
KGASB0201ALL
KGADA0101ALL
KGADA0201ALL
KGADA0301ALL
KGARP0301B17
KGARP0301B21
KGARP0301B24
KGAAD0101MEC
KGAAD0201MEC
D
D
D
D
D
D
D
D
D
D
D
D
D
D
KGCNP5201VSP
KGCPN4401VSP
LH32DB207
LH32DB202
LH32DB200
LH32DB205
LH32DB208
LH32DB078
LH32DB076
LH32DB203
LH32DB201
LH32DB206
LH32DB209
LH32DB210
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
KGBSD0301FMS
KGASD0301APM
SYSTXCCITW01
SYSTXCCITN01
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
KGAWF1306UFR
KGAWF1506UFR
EXPXXFIL0016
EXPXXFIL0020
EXPXXFIL0024
EXPXXUNV0016
EXPXXUNV0020
EXPXXUNV0024
FILXXCAR0016
FILXXCAR0020
FILXXCAR0024
GAPAAXCC1625-A08
GAPAAXCC2025-A08
D
D
GAPACCCAR1625-A05
GAPACCCAR2025-A05
PGAPXX1625
PGAPXX2025
PGAPAXXCAR1625
PGAPAXXCAR2025
D = Used with the model furnace
5
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
20”x25” IAQ Devices
24”x25” IAQ Devices
D
D
D
D
D
D
Use with EZXCAB--- 1016
Use with EZXCAB--- 1020
Use with EZXCAB--- 1024
Use with EZXCAB--- 1016
Use with EZXCAB--- 1020
Use with EZXCAB--- 1024
Use with FILCABXL --- 1016
Use with FILCABXL --- 1020
Use with FILCABXL --- 1024
Up to 1600 CFM
Up to 2000 CFM
GAPAAXCC1625--- A08
GAPAAXCC2025--- A08
Up to 1600 CFM
Up to 2000 CFM
GAPAAXCC1625
GAPAAXCC2025
D
D
59TN6A
DESCRIPTION
AIR DELIVERY (CONTINUED)
AND HEATING AIR DELIVERY - CFM (Bottom Return5 With Filter)
(SW1-5 and SW4-3 set to OFF, except as indicated. See notes 1 and 2.)
Unit Size
Clg/CF Switch Settings
SWx-3
SWx-2
SWx-1
0.1
0.2
0.3
External Static Pressure (ESP)
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1805
1780
1770
1095
1295
1480
1825
2115
See note 4
See note 4
1080
1300
1485
1805
2100
1065
1290
1475
1780
2070
1070
1285
1460
1770
2015
100-22
Clg Default:
OFF
OFF
OFF
1820
1825
1840
1845
1840
CF Default:
OFF
OFF
OFF
750
740
745
730
715
See note 4
Cooling (SW2)
Cont Fan
(SW3)
OFF
OFF
OFF
ON
ON
ON
ON
OFF
ON
ON
OFF
OFF
ON
ON
ON
OFF
ON
OFF
ON
OFF
ON
750
900
1070
1280
1440
1820
2135
740
900
1075
1285
1445
1825
2140
745
915
1095
1305
1465
1840
2140
730
910
1095
1305
1465
1845
2135
715
905
1090
1310
1470
1840
2140
1085
1305
1485
1835
2130
Maximum Clg Airflow 2
2160
2165
2175
2170
2160
2150
2135
2120
2065
2020
Heating
(SW1)
High Heat Airflow 3
Low Heat Airflow 3
1570
1365
1575
1385
1595
1395
1595
1395
1600
1395
1605
1400
1600
1400
1600
1405
1590
1395
1575
1380
Unit Size
Clg/CF Switch Settings
SWx-3
SWx-2
SWx-1
0.1
0.2
0.3
0.8
0.9
1.0
1775
1750
1730
CF Default:
Cooling (SW2)
Cont Fan
(SW3)
2.
3.
4.
5.
6.
7.
1825
Clg SW2:
120-22 6
Clg Default:
1.
1835
External Static Pressure (ESP)
0.4
0.5
0.6
0.7
OFF
OFF
OFF
1850
1855
1860
1855
1850
1830
1805
OFF
OFF
OFF
930
925
915
900
885
See note 4
OFF
OFF
OFF
ON
ON
ON
ON
OFF
ON
ON
OFF
OFF
ON
ON
ON
OFF
ON
OFF
ON
OFF
ON
765
930
1095
1265
1465
1850
2200
745
925
1100
1255
1455
1855
2200
740
915
1110
1265
1470
1860
2200
705
900
1105
1280
1465
1855
2190
680
885
1085
1275
1465
1850
2185
1285
1470
1830
2170
1270
1455
1805
2145
See note 4
See note 4
See note 4
1260
1450
1775
2085
1250
1435
1750
1990
1230
1415
1730
1890
Clg SW2:
Maximum Clg Airflow 2
2200
2200
2200
2190
2185
2170
2145
2085
1990
1890
Heating
(SW1)
High Heat Airflow 3
Low Heat Airflow 3
1815
1640
1820
1640
1825
1645
1820
1650
1815
1645
1795
1645
1775
1630
1745
1620
1720
1600
1700
1580
Nominal 350 CFM/ton cooling airflow is delivered with SW1-5 and SW4-3set to OFF.
Set SW1-5 to ON for nominal 400 CFM/ton (+15% airflow).
Set SW4-3 to ON for nominal 325 CFM/ton (-7% airflow).
Set both SW1-5 and SW4-3 to ON for nominal 370 CFM/ton (+7% airflow).
The above adjustments in airflow are subject to motor horsepower range/capacity.
Maximum cooling airflow is achieved when switches SW2-1, SW2-2, SW2-3 and SW1-5 are set to ON, and SW4-3 is set to OFF.
All heating CFM's are when low heat rise adjustment switch (SW1-3) and comfort/efficiency adjustment switch (SW1-4) are both set to OFF.
Ductwork must be sized for high-heating CFM within the operational range of ESP. Operation within the blank areas of the chart is not recommended because high-heat operation will be above 1.0 ESP.
All airflows on 21" (533 mm) casing size furnaces are 5% less on side return only installations.
Side returns for 24.5" (622 mm) casing sizes require two sides, or side and bottom, to allow sufficient airflow at the return of the furnace.
Airflows over 1800 CFM require bottom return, two-side return, or bottom and side return; otherwise excessive watt draws may result. A
minimum filter size of 20" x 25" (508 x 635 mm) is required.
7
59TN6A
COOLING4
MEDIA FILTER CABINET
25-5/8"
(651mm)
24-1/4”
(616mm)
Opening with Flanges Bent
23-1/8”
(588mm)
Opening
23-5/8"
(600mm)
23-3/8”
(594mm)
B Opening
59TN6A
A
Duct Side
Furnace Side
23-3/4”
(603mm)
Centerline Screw Slots
5 3 4"
(146mm)
Media Filter
A
B
Cabinet
16" (406mm) 17" (432mm) 16" (406mm)
20" (508mm) 21" (533mm) 20" (508mm)
24" (610mm) 25" (635mm) 24" (610mm)
NOTE: Media cabinet is matched to the bottom opening on furnace. May also be used for side return.
A12428
TYPICAL WIRING SCHEMATIC
FIELD 24-VOLT WIRING
FIELD 115-, 208/230-, 460-VOLT WIRING
FACTORY 24-VOLT WIRING
FACTORY 115-VOLT WIRING
NOTE 2
W
FIVE
WIRE
BLOWER
DOOR
SWITCH
BLK
Y
R
G
1-STAGE
THERMOSTAT
TERMINALS
FIELD-SUPPLIED
FUSED DISCONNECT
THREE-WIRE
HEATINGONLY
BLK
WHT
C
WHT
GND
115-VOLT FIELD- JUNCTION
SUPPLIED
BOX
FUSED
DISCONNECT
C
O
N
T
R
O
L
208/230- OR
460-VOLT
THREE
PHASE
W2
COM
W/W1
Y/Y2
NOTE 1
R
GND
CONDENSING
UNIT
G
24-VOLT
TERMINAL
BLOCK
FURNACE
208/230VOLT
SINGLE
PHASE
NOTES: 1. Connect Y/Y2-terminal as shown for proper operation.
2. Some thermostats require a "C" terminal connection as shown.
3. If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
A11401
13
59TN6
FURNACE SIZE
060--- 14
080--- 14
080--- 20
100--- 22
120--- 22
25 1/8
[638.7]
14
A
CABINET WIDTH
B
OUTLET WIDTH
C
BOTTOM INLET WIDTH
D
AIR INTAKE
17--- 1/2 (445)
15--- 7/8 (403)
16 (406)
8--- 3/4 (222)
21 (533)
19--- 3/8 (492)
19--- 1/2 (495)
10--- 1/2 (267)
24--- 1/2 (622)
22--- 7/8 (581)
23 (584)
12--- 1/4 (311)
21
[534.0]
26 5/16
[668.8]
22
[558.3] (BOTH SIDES)
1 (BOTH SIDES)
[25.4]
7/8
[22.2]
THERMOSTAT ENTRY
SIDE INLET
2 1/2
[63.5]
7/8
[22.2]
7/8
[22.2]
7/8
[22.2]
4
[101.6]
CONDENSATE DRAIN TRAP
LOCATION
AIR FLOW
19 1/8
[485.8]
20 5/8
[522.7]
23 5/16
[592.9]
26 3/8
[670.0]
26 11/16
[678.1]
TOP VIEW
6 11/16
[170.1]
6 15/16
[176.1]
D
SEE NOTE #3
14 13/16
[376.3]
16 9/16
[420.9]
17 5/16
[439.2]
7/8
[22.2] POWER CONN
3
[76.2]
VENT
1 3/4
[44.5]
GAS CONN
3
[76.2]
AIR INTAKE
3
[76.2]
AIR INTAKE
3
[76.2]
VENT
2 3/10
[58.4]
23 7/16
[595.6] 25 3/16
[639.1]
22 15/16
[581.9]
20 1/4
[513.9]
28 5/8
[726.4]
28 3/16
[715.9]
11/16
[17.5]
32 5/8
[829.5]
5/8
[15.8]
NOTE: ALL DIMENSIONS IN INCH [MM]
C
BOTTOM RETURN
WIDTH
AIR FLOW
B
OUTLET WIDTH
A
2 1/2
[63.5]
1 5/16
[33.3]
6 1/16
[154.0]
16 9/16
[420.9]
17 7/16
[442.3]
20 1/4
[513.9] 18 1/16
[458.6]
24
[609.7]
28 3/8
[720.4]
28 5/8
[726.9]
29 13/16
[757]
11/16
[17.5]
35
[889.0]
3
[76.2 ]
3
[76.2]
AIR INTAKE
2
NEXT SHEET
SD5024-4
PART NUMBER
7/8
[22.2]
4
[101.6]
SIDE INLET
7/8
[22.2] POWER CONN
7/8
[22.2]
1 3/4
[44.5]
GAS CONN
7/8
[22.2]
AIR FLOW
20 5/8
[522.7]
21 1/16
[535.8]
21 15/16
[557.4]
26 3/8
[669.9]
26 11/16
[678.1]
28 3/4
[730.5]
29 1/2
[749.3]
REV
E
SHT
1
BOTTOM INLET
21 5/8
[549.5]
23 3/8
[592.0]
26 5/16
[668.8]
7/8
[22.2]
THERMOSTAT ENTRY
NOTES:
1. Doors may vary by model.
2. Minimum return-air openings at furnace, based on metal duct. If flex duct is used,
see flex duct manufacturer's recommendations for equivalent diameters.
a. For 800 CFM-16-in. (406 mm) round or 14 1/2 x 12-in. (368 x 305 mm) rectangle.
b. For 1200 CFM-20-in. (508 mm) round or 14 1/2 x 19 1/2-in. (368 x 495 mm) rectangle.
c. For 1600 CFM-22-in. (559 mm) round or 14 1/2 x 22 1/16-in. (368 x 560mm) rectangle.
d. Return air above 1800 CFM at 0.5 in. w.c. ESP on 24.5" casing, requires one of the following
configurations: 2 sides, 1 side and a bottom or bottom only. See Air Delivery table in this
document for specific use to allow for sufficient airflow to the furnace.
3. Vent and Combustion air pipes through blower compartment must
use accessory “Vent Kit - Through the Cabinet”. See accessory list for
current part number.
59TN6A
DIMENSIONAL DRAWING
SHIP WT.
LB (KG)
A12267
140.0 (63.0)
150.0 (67.5)
154.5 (70.2)
164.5 (74.0)
188.5 (84.8)
GUIDE SPECIFICATIONS
System Description
Furnish a ______________________ 4--way multipoise
two--stage gas--fired condensing furnace for use with natural gas or
propane (factory-- authorized conversion kit required for propane);
furnish external media cabinet for use with accessory media filter
or standard filter.
Quality Assurance
Unit will be designed, tested and constructed to the current ANSI Z
21.47/CSA 2.3 design standard for gas--fired central furnaces.
Unit will be third party certified by CSA to the current ANSI Z
21.47/CSA 2.3 design standard for gas--fired central furnaces. Unit
will carry the CSA Blue StarR and Blue FlameR labels. Unit
efficiency testing will be performed per the current DOE test
procedure as listed in the Federal Register.
Unit will be certified for capacity and efficiency and listed in the
latest AHRI Consumer’s Directory of Certified Efficiency Ratings.
Unit will carry the current Federal Trade Commission Energy
Guide efficiency label.
Delivery, Storage, and Handling
Unit will be shipped as single package only and is stored and
handled per unit manufacturer’s recommendations.
Warranty (for inclusion by specifying engineer)
U.S. and Canada only. Warranty certificate available upon request.
Equipment
Blower Wheel and ECM Blower Motor
Galvanized blower wheel shall be centrifugal type, statically and
dynamically balanced. Blower motor of ECM type shall be
permanently lubricated with sealed ball bearings, of _______hp,
and have infinitely variable speed from 300--1300 RPM operating
only when motor inputs are provided. Blower motor shall be direct
drive and soft mounted to the blower housing to reduce vibration
transmission.
Filters
Furnace shall have reusable--type filters. Filter shall be ______ in.
(mm) X ________ in. (mm). An accessory highly efficient Media
Filter is available as an option. _____________ Media Filter.
Casing
Casing shall be of .030 in. thickness minimum, pre--painted steel.
Draft Inducer Motor
Draft Inducer motor shall be two--speed PSC design.
Primary Heat Exchangers
Primary heat exchangers shall be 3--Pass corrosion--resistant
aluminized steel of fold--and--crimp sectional design and applied
operating under negative pressure.
Secondary Heat Exchangers
Secondary heat exchangers shall be of a stainless steel
flow--through of fin--and--tube design and applied operating under
negative pressure.
Controls
Controls shall include a micro--processor--based integrated
electronic control board with at least 16 service troubleshooting
codes displayed via diagnostic flashing LED light on the control, a
self--test feature that checks all major functions of the furnace, and
a replaceable automotive--type circuit protection fuse. Multiple
operational settings available, including separate blower speeds for
low heat, high heat, low cooling, high cooling and continuous fan.
Continuous fan speed may be adjusted from the thermostat.
Cooling airflow will be selectable between 325 to 400 CFM per
ton of air conditioning. Features will also include temporary
reduced airflow in the cooling mode for improved
dehumidification when an Infinity Control or TP--PRH edgeR is
selected as the thermostat.
Operating Characteristics
Heating capacity shall be _________________ Btuh input;
______________ Btuh output capacity.
Fuel Gas Efficiency shall be __________ AFUE.
Air delivery shall be ________________ cfm minimum at 0.50 in.
W.C. external static pressure.
Dimensions shall be: depth_________in. (mm); width
__________in. (mm); height___________in. (mm) (casing only).
Height shall be _________in. (mm) with A/C coil and
_________________in. (mm) overall with plenum.
Electrical Requirements
Electrical supply shall be 115 volts, 60 Hz, single--phase (nominal).
Minimum wire size shall be ________AWG; maximum fuse size
of HACR--type designated circuit breaker shall be _________
amps.
Special Features
Refer to section of the product data identifying accessories and
descriptions for specific features and available enhancements.
15
59TN6A
General
CNPVP, CNPVT, CNPVU, CNRVU
Evaporator Coil
N Coil --- Cased and Uncased
Upflow, Downflow
Product Data
A06008
CNPVP
This vertical design N--coil is a furnace coil designed to provide the
highest standards of reliability and durability. The coils are
available for use in R--410A and R--22 refrigerant systems.
Both designs have a painted case and come with factory--installed
thermostatic expansion valves (TXV). The coils are offered in
different width configurations for use in multiple installation
applications. Additionally, they are offered in a transition
configuration, a design which simplifies making field--supplied
transition duct configurations. Easy maintenance is provided as the
coil slides out of the cabinet after removing the access door and
service panel. The coils are available in sizes 018 through 061
(1--1/2 to 5 tons).
Transition coil models CNPVT are designed for use with one size
smaller width furnaces without field modifications.
Aluminum Coils -- “L” models are built with aluminum hairpins,
designed to resist both general pitting corrosion and excessive
indoor Formicary Corrosion. (Formicary Corrosion is an industry
phenomenon.)
STANDARD FEATURES
A06007
CNPVT (Transition)
A06004
CN(P,R)VU
Water Management — These coil designs do an excellent job of
water management. The coils are designed to avoid water blow--off
into the ducts by directing condensate away from the fins and into
the drain pan.
Durable Condensate Pan — Each coil is equipped with a
corrosion--resistant condensate drain pan. The condensate drain
pan is designed with a slope to help ensure proper drainage,
improved moisture removal, and home comfort.
Compact Design — Unique design offers as much as 2 to 4 in. (51
to 102 mm) less in height to aid in tight installations.
Brass Inserts — Every condensate pan features two 3/4 in. female
threaded brass insert connections. The unique brass inserts provide
for a leak--free condensate line connection to prevent water
damage.
Refrigerant Connections — The coils are provided with proven
sweat--connections for leak--free operation maintaining system
reliability.
Burst Pressures — These coils meet or exceed burst pressure of
2100 psi which is at least three to five times the pressure they will
see in actual application.
Thermostatic Expansion Valves (TXV) — All Payne coils have
refrigerant--specific factory--installed TXVs.
Teflon Ring — The ring, installed inside the liquid line connection
at the TXV, is the best option for preventing refrigerant leaks and
future service calls. Teflon works with both R--410A and R--22
refrigerants.
Protective Tube Sheets — Protect the durable copper tubing from
being damaged during the manufacturing and installation process.
MODEL NUMBER NOMENCLATURE
1
2
3
4
5
6
7
8
9
10
11
12
C
N
P
V
P
1
8
1
4
A
C
A
Product
C = Coil
Variations
A = Basic
Type
N = N Coil
Tubing Design
C = Copper (R--- 410A Only)
L = Aluminum (R--- 22 & R--- 410A)
T = Tin--- Plated Copper (R--- 22 & R--- 410A)
Refrigerant Type
P = R--- 410A Refrigerant TXV
R = R--- 22 TXV
Revision Level
A = 1st
Coil Configuration
V = Upflow / Downflow
Cabinet Width
14 = 14--- in. / 356mm
17 = 17--- in. / 432mm
21 = 21--- in. / 533mm
24 = 24--- in. / 610mm
F-5,2,3
Cabinet Finish
P = Painted
U = Uncased
T = Transition N
F-6
Unit Capacity
18 = 1 1/2 Ton
19 = 1 1/2 Ton
24 = 2 Ton
30 = 2 1/2 Ton
31 = 2 1/2 Ton
36 = 3 Ton
Use of the AHRI Certified
TM Mark indicates a
manufacturer’s
participation in the
program For verification
of certification for individual
products, go to
www.ahridirectory.org.
2
37 = 3 Ton
42 = 3 1/2 Ton
43 = 3 1/2 Ton
48 = 4 Ton
60 = 5 Ton
61 = 5 Ton
F-5,2,3
F-6
DIMENSIONS
21 "
E
D
7/8 "
1/2 "
OUTSIDE OF
FLANGES
9/16 "
3/8" I.D.
LIQUID LINE
SWEAT CONNECTION
C
18-9/16 "
OUTSIDE OF
FLANGES
1-9/16 "
1-7/8 " MAX
FI.D.
SUCTION LINE
SWEAT CONNECTION
A
2-1/16 "
B
3/4" PLUGGED DRAIN
2-1/8 "
1-3/8 "
3/4" NPT DRAIN
13/16 "
1-9/16 "
NOTE:
3-1/16 "
1. SERIES DESIGNATION IS THE 14TH POSITION OF UNIT MODEL NUMBER.
2. IN THE ELEVENTH POSITION (#) THE "C" DESIGNATES NON-COATED HAIRPINS
AND "T" DESIGNATES TIN-COATED HAIRPINS.
3. ALL DIMENSIONS ARE IN "INCHES" UNLESS NOTED.
SHIPPING WT
(LBS)
_C_NON-COATED
HAIRPINS
SHIPPING WT
(LBS)
_T_TIN-COATED
HAIRPINS
5/8"
36.0
38.5
SERIES
F
UNIT
CNPVP1814A#A
C
12 5/8"
10 1/16"
5 5/16"
12 1/2"
14 3/16"
CNPVP2414A#A
C
14 5/8"
12 1/16"
5 5/16"
12 1/2"
14 3/16"
5/8"
39.5
40.0
CNPVP2417A#A
C
14 5/8"
10 1/16"
3 9/16"
15 3/4"
17 1/2"
5/8"
39.5
42.5
CNPVP3014A#A
C
17"
13 5/8"
5 5/16"
12 1/2"
14 3/16"
3/4"
46.5
50.0
CNPVP3017A#A
C
17"
13 7/8"
3 9/16"
15 3/4"
17 1/2"
3/4"
47.0
49.5
CNPVP3617A#A
C
17"
13 7/8"
3 9/16"
15 3/4"
17 1/2"
3/4"
48.5
51.0
CNPVP3621A#A
C
17"
13 9/16"
3 9/16"
19 1/4"
3/4"
48.0
51.0
CNPVP4217A#A
C
13 7/8"
3 9/16"
15 3/4"
7/8"
52.0
55.0
CNPVP4221A#A
C
15 5/8"
3 9/16"
19 1/4"
7/8"
56.5
59.5
CNPVP4821A#A
C
22 1/16"
17 1/2"
3 9/16"
19 1/4"
7/8"
65.5
68.5
CNPVP4824A#A
C
22 1/16"
17 1/4"
3 9/16"
22 3/4"
24 1/2"
7/8"
62.0
65.0
CNPVP6024A#A
C
26 7/8"
17 15/16"
3 9/19"
22 3/4"
24 1/2"
7/8"
78.0
80.5
A
21 1/8"
19"
B
C
D
E
21"
17 1/2"
21"
21"
A - Aluminum
Hairpins
A12319
3
PERFORMANCE DATA (cont.)
COOLING CAPACITIES (MBH) -- R--410A REFRIGERANT
CNPV
INDOOR
UNIT
COIL AIR
SIZE CFM EWB
72 (22)
1050 67 (19)
62 (17)
4217
72 (22)
4221
1400 67 (19)
4224
62 (17)
T4221
72 (22)
1750 67 (19)
62 (17)
72 (22)
1050 67 (19)
62 (17)
72 (22)
4324 1400 67 (19)
62 (17)
72 (22)
1750 67 (19)
62 (17)
72 (22)
1200 67 (19)
62 (17)
72 (22)
4821
4824 1600 67 (19)
T4821
62 (17)
72 (22)
2000 67 (19)
62 (17)
72 (22)
1600 67 (19)
62 (17)
72 (22)
6024
T6024 2000 67 (19)
62 (17)
72 (22)
2400 67 (19)
62 (17)
72 (22)
1600 67 (19)
62 (17)
72 (22)
6124
2000 67 (19)
T6124
62 (17)
72 (22)
2400 67 (19)
62 (17)
30 (---1)
TC
SHC
74.40 36.30
62.30 37.60
51.40 38.60
90.20 43.80
75.80 46.00
62.60 47.70
103.00 50.00
86.70 53.10
71.70 55.70
96.72 47.64
80.93 49.26
66.64 50.56
117.07 57.30
98.18 60.23
81.03 62.70
133.38 65.28
112.09 69.50
92.72 73.26
79.30 38.70
66.60 40.20
55.00 41.30
96.00 46.60
80.90 49.20
67.00 51.20
109.40 53.10
92.40 56.70
76.70 59.70
103.20 50.40
86.40 52.10
71.20 53.30
120.70 58.70
101.20 61.30
83.40 63.20
135.60 65.80
113.90 69.30
94.10 72.10
146.13 71.69
122.06 74.12
100.28 76.03
169.63 82.84
142.02 86.75
116.90 89.93
189.44 92.42
158.99 97.85
131.10 102.40
Legend:
CFM --- Cubic Ft. per Minute
SHC --- Gross Sensible Capacity 1000 Btuh
See notes on following page.
BF
0.00
0.02
0.03
0.00
0.05
0.06
0.00
0.08
0.09
0.00
0.01
0.01
0.00
0.03
0.03
0.00
0.04
0.05
0.00
0.02
0.03
0.00
0.04
0.05
0.00
0.06
0.07
0.00
0.02
0.03
0.00
0.03
0.05
0.00
0.05
0.06
0.00
0.02
0.02
0.00
0.03
0.03
0.00
0.04
0.05
SATURATED TEMPERATURE LEAVING EVAPORATOR _F (_C)
35 (2)
40 (4)
45 (7)
TC
SHC
BF
TC
SHC
BF
TC
SHC
BF
68.10 33.10 0.00 61.20 29.70 0.00 53.50 26.20 0.01
56.00 34.20 0.03 48.90 30.60 0.03 41.20 27.00 0.03
44.90 35.00 0.03 37.90 31.40 0.03 30.60 27.80 0.04
82.60 40.10 0.00 74.10 36.20 0.01 64.70 32.00 0.04
68.00 42.00 0.05 59.40 37.70 0.06 50.00 33.40 0.06
54.70 43.50 0.06 46.20 39.20 0.06 37.50 35.00 0.07
94.30 46.00 0.00 84.60 41.50 0.05 73.90 36.80 0.06
77.80 48.60 0.08 68.00 43.90 0.08 57.10 39.00 0.08
62.70 50.90 0.09 53.10 46.20 0.09 43.40 41.50 0.10
89.31 43.85 0.00 80.91 39.78 0.00 71.39 35.44 0.00
73.30 45.20 0.01 64.67 40.88 0.01 54.97 36.34 0.01
58.77 46.28 0.01 50.10 41.84 0.01 40.70 37.29 0.02
108.20 53.03 0.00 98.03 48.31 0.01 86.74 43.33 0.02
89.03 55.55 0.03 78.69 50.55 0.03 66.93 45.19 0.03
71.60 57.72 0.03 61.25 52.56 0.03 50.15 47.21 0.03
123.30 60.58 0.02 111.98 55.48 0.03 99.21 50.01 0.04
101.79 64.41 0.05 90.14 58.95 0.05 76.76 52.99 0.05
82.16 67.85 0.05 70.58 62.18 0.05 58.38 56.24 0.06
72.90 35.40 0.00 65.70 31.90 0.00 57.70 28.20 0.00
60.00 36.60 0.02 52.70 32.90 0.02 44.60 29.10 0.02
48.30 37.60 0.03 40.90 33.80 0.03 33.10 30.00 0.03
88.30 42.90 0.00 79.60 38.90 0.00 69.90 34.50 0.03
72.90 45.00 0.04 64.10 40.70 0.05 54.20 36.10 0.05
58.80 46.80 0.05 49.90 42.30 0.05 40.70 37.90 0.05
100.70 49.10 0.00 90.90 44.60 0.03 79.90 39.80 0.05
83.40 52.20 0.07 73.30 47.40 0.07 62.00 42.20 0.07
67.50 54.90 0.08 57.40 49.90 0.08 47.20 44.90 0.08
94.40 45.90 0.00 84.80 41.10 0.00 74.10 36.30 0.00
77.50 47.20 0.02 67.80 42.30 0.02 57.10 37.20 0.03
62.20 48.30 0.03 52.40 43.30 0.03 42.30 38.30 0.03
110.40 53.60 0.00 99.00 48.20 0.00 86.40 42.50 0.02
90.70 55.70 0.04 79.20 50.00 0.04 66.60 44.10 0.04
72.80 57.40 0.05 61.40 51.60 0.05 49.70 46.00 0.05
124.10 60.30 0.00 111.20 54.40 0.01 97.00 48.00 0.04
102.10 63.20 0.06 89.10 56.90 0.06 74.80 50.30 0.06
82.10 65.70 0.06 69.30 59.30 0.06 56.40 53.00 0.07
134.50 65.77 0.00 121.56 59.54 0.00 106.83 52.86 0.00
110.18 67.82 0.02 96.85 61.17 0.02 81.83 54.15 0.02
88.07 69.40 0.02 74.72 62.59 0.02 60.46 55.67 0.02
156.39 76.39 0.00 141.33 69.41 0.01 124.36 61.86 0.02
128.36 79.72 0.03 112.89 72.20 0.03 95.38 64.18 0.03
102.76 82.43 0.03 87.41 74.75 0.03 71.17 66.88 0.04
174.81 85.58 0.00 158.22 77.98 0.02 139.30 69.76 0.03
143.83 90.25 0.04 126.61 82.05 0.04 107.02 73.24 0.05
115.46 94.29 0.05 98.49 85.91 0.05 80.79 77.29 0.06
EWB --- Entering Wet Bulb
BF --- Bypass Factor
LWB --- Leaving Wet Bulb
MBH --- 1000 Btuh
10
TC
45.00
32.80
24.40
54.40
39.60
30.70
62.00
45.20
36.30
60.74
43.99
32.63
73.81
53.54
41.46
84.49
61.46
49.33
48.80
35.70
26.30
59.10
43.30
33.30
67.50
49.50
39.50
62.40
45.40
33.50
72.60
52.80
40.30
81.30
59.20
46.50
90.32
64.91
48.56
105.10
75.60
58.57
117.75
84.86
67.60
50 (10)
SHC
22.60
23.30
24.40
27.60
28.90
30.70
32.00
33.90
36.30
30.89
31.53
32.63
37.96
39.46
41.46
44.04
46.55
49.33
24.40
25.10
26.30
30.00
31.40
33.30
34.70
36.90
39.50
31.20
32.10
33.50
36.70
38.10
40.30
41.50
43.60
46.50
45.83
46.78
48.56
53.83
55.70
58.57
60.94
63.87
67.60
BF
0.02
0.03
0.08
0.05
0.06
0.13
0.07
0.09
0.18
0.01
0.01
0.07
0.02
0.03
0.11
0.04
0.05
0.15
0.01
0.03
0.07
0.04
0.05
0.11
0.06
0.07
0.16
0.02
0.03
0.07
0.03
0.05
0.11
0.05
0.06
0.14
0.01
0.02
0.08
0.02
0.03
0.11
0.04
0.05
0.14
TC --- Gross Cooling Capacity 1000 Btuh
NOTES:
1. Contact manufacturer for cooling capacities at conditions other than shown in table.
2. Formulas:
Leaving db = entering db -- sensible heat cap.
1.09 x CFM
Leaving wb = wb corresponding to enthalpy of air leaving coil (hLWB)
hLWB = hEWB -- total capacity (Btuh)
4.5 x CFM
3.
4.
5.
6.
7.
8.
9.
10.
11.
Where hEWB = enthalpy of air entering coil
SHC is based on 80°F (27°C) db temperature of air entering the evaporator coil.
Below 80°F (27°C) db, subtract (Correction Factor x CFM) from SHC.
Above 80°F (27°C) db, add (Correction Factor x CFM) to SHC.
Direct interpolation is permissible. Do not extrapolate.
Fan motor heat has not been deducted.
All data points are based on 10°F (--12°C) superheat leaving coil and use of thermostatic expansion valve (TXV) device.
All units have sweat suction--tube connection and a liquid--tube connection. For 1--1/8--in. system suction tube, 3/4 x 1--1/8--in. suction
tube connection adapter is available as accessory.
The CNPVP, CNPVT and CNPVU coils can be used in any properly designed system using R--410A refrigerant.
The CNRVU coils can be used in any properly designed system using R--22 refrigerant.
Before using maximum cfm shown in table, check coil static pressure drop to ensure system blower can provide necessary static pressure needed for coil and duct systems.
Bypass Factor = 0 indicates no psychometric solution. Use bypass factor of next lower EWB for approximation.
BYPASS FACTOR
79 (26)
81 (27)
0.10
0.20
0.30
0.98
0.87
0.76
Interpolation is permissible.
Correction Factor = 1.09 x (1 --- BF) x (db --- 80)
ENTERING AIR DRY BULB TEMPERATURE _F (_C)
77 (25)
76 (24)
75 (24)
Under 75 (24)
83 (28)
84 (29)
84 (29)
Above 85 (29)
Correction Factor
1.96
2.94
3.92
4.91
1.74
2.62
3.49
4.36
Use formula shown below
1.53
2.29
3.05
3.82
78 (26)
82 (28)
11
PERFORMANCE DATA (cont.)
NO R-22
COOLING CAPACITIES (MBH) -- R--22 REFRIGERANT
CNRV
UNIT
SIZE
1814
2414
2417
3014
3017
3617
3621
4221
4224
4821
4824
6024
INDOOR
COIL
AIR
CFM EWB
72 (22)
450 67 (19)
62 (17)
72 (22)
600 67 (19)
62 (17)
72 (22)
750 67 (19)
62 (17)
72 (22)
600 67 (19)
62 (17)
72 (22)
800 67 (19)
62 (17)
72 (22)
1000 67 (19)
62 (17)
72 (22)
750 67 (19)
62 (17)
72 (22)
1000 67 (19)
62 (17)
72 (22)
1250 67 (19)
62 (17)
72 (22)
900 67 (19)
62 (17)
72 (22)
1200 67 (19)
62 (17)
72 (22)
1500 67 (19)
62 (17)
72 (22)
1050 67 (19)
62 (17)
72 (22)
1400 67 (19)
62 (17)
72 (22)
1750 67 (19)
62 (17)
72 (22)
1200 67 (19)
62 (17)
72 (22)
1600 67 (19)
62 (17)
72 (22)
2000 67 (19)
62 (17)
72 (22)
1600 67 (19)
62 (17)
72 (22)
2000 67 (19)
62 (17)
72 (22)
2400 67 (19)
62 (17)
SATURATED TEMPERATURE LEAVING EVAPORATOR _F (_C)
30 (---1)
TC
28.60
24.20
20.20
33.70
28.70
24.00
37.50
32.00
26.90
34.60
29.40
24.70
39.50
33.90
28.60
43.20
37.10
31.50
45.90
38.90
32.30
53.80
45.70
38.30
59.80
50.90
42.70
53.50
45.40
37.90
61.60
52.40
44.00
67.50
57.70
48.60
67.70
57.10
47.40
79.00
66.90
55.70
87.40
74.30
62.20
72.40
61.40
51.20
83.80
71.40
59.80
92.10
78.70
66.30
93.60
78.90
65.40
106.40
89.90
74.70
116.60
98.90
82.30
SHC
13.90
14.80
15.50
16.40
17.80
19.00
18.40
20.30
22.10
16.80
18.30
19.50
19.40
21.60
23.70
21.50
24.50
27.30
22.30
23.70
24.80
26.20
28.40
30.40
29.30
32.30
35.10
26.00
27.90
29.70
30.10
33.10
35.90
33.40
37.40
41.20
32.90
35.00
36.80
38.50
41.80
44.70
42.90
47.40
51.40
35.20
37.70
40.00
41.00
44.90
48.50
45.50
50.90
55.90
45.40
48.10
50.40
51.70
55.50
58.90
57.00
61.90
66.40
Legend:
CFM --- Cubic Ft. per Minute
SHC --- Gross Sensible Capacity 1000 Btuh
See notes previous page.
35 (2)
BF
0.00
0.01
0.01
0.00
0.02
0.02
0.01
0.03
0.03
0.00
0.01
0.02
0.01
0.03
0.03
0.03
0.05
0.05
0.00
0.02
0.02
0.00
0.03
0.04
0.03
0.06
0.06
0.00
0.03
0.03
0.02
0.05
0.06
0.06
0.08
0.08
0.00
0.03
0.03
0.00
0.05
0.06
0.04
0.08
0.09
0.00
0.02
0.03
0.00
0.04
0.05
0.04
0.07
0.07
0.00
0.02
0.03
0.00
0.04
0.04
0.00
0.06
0.06
TC
26.60
22.10
18.00
31.40
26.20
21.50
35.00
29.40
24.20
32.30
27.00
22.20
37.10
31.20
25.80
40.60
34.30
28.60
42.50
35.30
28.30
49.90
41.60
34.00
55.50
46.40
38.30
49.50
41.30
33.50
57.20
47.80
39.40
62.90
52.70
43.70
62.50
51.70
41.90
73.10
60.70
49.40
81.00
67.60
55.30
67.30
55.90
45.50
78.00
65.20
53.40
86.00
72.10
59.60
86.30
71.20
57.70
98.20
81.30
65.90
107.90
89.60
72.90
SHC
12.90
13.70
14.30
15.30
16.60
17.80
17.30
19.10
20.80
15.70
17.10
18.30
18.40
20.40
22.30
20.50
23.20
25.90
20.60
21.90
22.80
24.40
26.40
28.20
27.40
30.20
32.90
24.10
25.90
27.40
28.20
30.90
33.60
31.40
35.10
38.80
30.40
32.20
33.90
35.80
38.70
41.50
40.10
44.20
48.10
32.70
35.00
37.00
38.40
42.00
45.30
42.90
47.80
52.60
41.90
44.20
46.30
47.90
51.30
54.40
53.00
57.50
61.70
EWB --- Entering Wet Bulb
BF --- Bypass Factor
40 (4)
BF
0.00
0.01
0.01
0.00
0.02
0.02
0.01
0.03
0.04
0.00
0.01
0.02
0.01
0.03
0.03
0.04
0.05
0.05
0.00
0.02
0.02
0.01
0.04
0.04
0.04
0.06
0.06
0.00
0.03
0.03
0.03
0.05
0.06
0.06
0.08
0.09
0.00
0.03
0.03
0.02
0.05
0.06
0.06
0.08
0.09
0.00
0.02
0.03
0.02
0.04
0.05
0.05
0.07
0.07
0.00
0.02
0.03
0.00
0.04
0.04
0.03
0.06
0.06
TC
24.20
19.70
15.40
28.70
23.40
18.60
32.10
26.20
21.10
29.60
24.20
19.30
34.20
28.00
22.60
37.50
30.90
25.30
38.60
31.00
24.00
45.40
37.00
29.00
50.60
41.30
33.10
45.10
36.60
28.50
52.10
42.50
34.00
57.40
46.90
38.30
56.50
45.60
35.70
66.20
53.50
42.60
73.60
59.70
47.90
61.20
49.50
39.20
71.30
58.00
46.30
78.70
64.30
52.10
77.90
62.70
49.20
88.80
71.50
56.60
97.70
78.90
62.70
SHC
11.80
12.50
13.00
14.10
15.30
16.40
16.00
17.70
19.30
14.60
15.70
16.80
17.10
19.00
20.80
19.20
21.80
24.30
18.80
19.80
20.60
22.40
24.20
25.80
25.30
27.80
30.30
22.10
23.70
24.90
26.00
28.50
30.90
29.10
32.60
36.10
27.60
29.30
30.80
32.80
35.40
38.10
37.00
40.60
44.50
30.00
32.00
33.90
35.40
38.70
41.90
39.80
44.40
48.90
38.00
40.10
42.00
43.70
46.70
49.70
48.50
52.50
56.70
45 (7)
BF
0.00
0.01
0.01
0.00
0.02
0.02
0.02
0.03
0.04
0.00
0.01
0.02
0.02
0.03
0.04
0.04
0.05
0.06
0.00
0.02
0.02
0.02
0.04
0.04
0.04
0.06
0.07
0.01
0.03
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.00
0.03
0.03
0.04
0.06
0.06
0.07
0.08
0.09
0.00
0.02
0.03
0.03
0.05
0.05
0.05
0.07
0.08
0.00
0.02
0.03
0.02
0.04
0.05
0.04
0.06
0.07
LWB --- Leaving Wet Bulb
MBH --- 1000 Btuh
12
TC
21.60
16.80
12.50
25.60
20.10
15.40
28.70
22.60
17.90
26.50
20.90
16.00
30.70
24.30
19.30
33.80
26.80
22.30
34.10
26.00
19.30
40.30
31.20
23.80
44.80
35.40
27.70
40.00
30.70
23.20
46.20
36.30
28.30
50.80
40.30
32.90
49.70
38.80
28.90
58.30
45.50
35.40
64.90
50.60
40.70
54.20
42.40
32.20
63.30
49.50
39.00
70.10
55.10
44.90
68.30
53.20
39.60
78.00
60.60
46.50
85.90
66.60
52.60
SHC
10.60
11.20
11.70
12.80
13.80
14.80
14.60
16.10
17.70
13.20
14.30
15.30
15.70
17.40
19.10
17.70
20.10
22.30
16.80
17.50
18.30
20.20
21.70
23.20
22.90
25.30
27.50
19.90
21.10
22.30
23.50
25.80
28.00
26.50
29.80
32.90
24.70
26.20
27.50
29.40
31.90
34.50
33.40
36.70
40.70
27.00
28.80
30.50
32.10
35.00
38.30
36.40
40.40
44.90
33.80
35.70
37.40
39.10
41.80
44.80
43.60
47.20
51.60
50 (10)
BF
0.00
0.01
0.01
0.01
0.02
0.03
0.02
0.03
0.05
0.00
0.01
0.02
0.02
0.03
0.05
0.04
0.05
0.11
0.01
0.02
0.03
0.03
0.04
0.06
0.05
0.06
0.09
0.02
0.03
0.05
0.04
0.06
0.08
0.07
0.08
0.13
0.02
0.03
0.04
0.04
0.06
0.08
0.07
0.08
0.11
0.01
0.02
0.03
0.03
0.05
0.07
0.06
0.07
0.11
0.01
0.03
0.04
0.03
0.04
0.06
0.05
0.06
0.08
TC
18.60
13.50
10.20
22.00
16.30
13.00
24.60
18.60
15.40
22.90
17.10
13.40
26.60
20.10
16.80
29.30
22.20
19.60
28.60
20.30
15.90
34.30
24.40
20.00
38.40
27.90
23.70
33.80
24.00
19.30
39.60
28.60
24.10
43.60
32.20
28.30
42.30
30.30
23.80
49.30
36.30
29.90
54.80
40.90
35.20
46.30
34.10
26.70
54.00
40.30
33.40
60.00
44.90
39.20
58.00
41.70
32.50
65.80
48.30
38.90
72.30
53.70
44.70
SHC
9.40
9.70
10.20
11.40
12.20
13.00
13.00
14.40
15.40
11.80
12.60
13.40
14.10
15.60
16.80
16.00
18.20
19.60
14.60
15.10
15.90
17.80
18.80
20.00
20.40
22.20
23.70
17.40
18.30
19.30
20.90
22.60
24.10
23.70
26.50
28.30
21.60
22.60
23.80
25.90
28.10
29.90
29.50
32.80
35.20
23.70
25.20
26.70
28.50
31.20
33.40
32.50
36.30
39.20
29.60
30.80
32.50
34.10
36.60
38.90
38.20
41.80
44.70
BF
0.00
0.01
0.08
0.01
0.02
0.12
0.03
0.03
0.16
0.01
0.02
0.10
0.02
0.03
0.16
0.04
0.05
0.21
0.01
0.02
0.12
0.03
0.04
0.16
0.05
0.06
0.21
0.02
0.03
0.15
0.05
0.06
0.20
0.08
0.09
0.25
0.02
0.03
0.13
0.05
0.06
0.18
0.08
0.09
0.23
0.02
0.03
0.12
0.04
0.05
0.17
0.06
0.07
0.22
0.02
0.03
0.12
0.03
0.04
0.16
0.05
0.06
0.19
TC --- Gross Cooling Capacity 1000 Btuh
PERFORMANCE DATA (cont.)
COIL STATIC PRESSURE DROP (in. w.c.) R--410A and R--22 REFRIGERANTS
UNIT
SIZE
1814
400
500
600
700
800
0.078 0.114 0.156 0.198 0.253
900
Standard CFM
1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200
Dry
0.096 0.138 0.183 0.213 0.277
1917
0.042 0.060 0.080 0.102 0.128
0.055 0.076 0.104 0.127 0.158
2414
0.070 0.103 0.143 0.182 0.233 0.290 0.354
0.089 0.128 0.171 0.214 0.269 0.336 0.413
2417
0.048 0.068 0.090 0.112 0.140 0.170 0.203
0.064 0.091 0.122 0.150 0.188 0.224 0.263
3014
0.065 0.097 0.135 0.173 0.223 0.278 0.339 0.405 0.478
0.078 0.114 0.160 0.206 0.260 0.321 0.388 0.461 0.540
3017
0.042 0.060 0.080 0.102 0.128 0.157 0.188 0.222 0.259
0.055 0.076 0.104 0.127 0.158 0.190 0.225 0.266 0.309
3117
0.031 0.046 0.063 0.083 0.105 0.130 0.156 0.193 0.230
0.039 0.056 0.075 0.097 0.121 0.149 0.179 0.212 0.249
Wet
Dry
Wet
Dry
Wet
Dry
Wet
Dry
Wet
Dry
Wet
Dry
Wet
Dry
3617 0.043 0.061 0.082 0.103 0.128 0.157 0.189 0.221 0.259 0.299 0.341
T3617
Wet
0.056 0.079 0.107 0.133 0.166 0.200 0.236 0.276 0.315 0.361 0.413
Dry
0.035 0.048 0.062 0.076 0.093 0.111 0.132 0.153 0.177 0.201 0.228
3621
Wet
0.049 0.066 0.085 0.100 0.122 0.144 0.171 0.192 0.217 0.245 0.276
Dry
0.025 0.038 0.054 0.072 0.093 0.117 0.143 0.171 0.205 0.233 0.273
3717
Wet
0.030 0.044 0.061 0.079 0.103 0.125 0.154 0.182 0.216 0.251 0.288
Dry
0.072 0.093 0.118 0.145 0.175 0.206 0.243 0.281 0.322
4217
Wet
0.079 0.102 0.130 0.159 0.192 0.228 0.26 0.303 0.348
Dry
4221 0.030 0.041 0.054 0.066 0.082 0.099 0.118 0.137 0.158 0.180 0.205
T4221
Wet
0.043 0.059 0.078 0.101 0.126 0.153 0.181 0.207 0.234 0.260 0.288
Dry
0.053 0.062 0.073 0.084 0.097 0.111 0.126 0.138
4324
Wet
0.067 0.082 0.096 0.112 0.129 0.145 0.163 0.171
Dry
0.047 0.060 0.075 0.092 0.110 0.130 0.152 0.176 0.204
4821
T4821
Wet
0.053 0.067 0.085 0.104 0.125 0.147 0.172 0.200 0.228
Dry
0.015 0.046 0.057 0.069 0.094 0.100 0.119 0.124 0.140
4824
Wet
0.032 0.050 0.066 0.081 0.097 0.114 0.131 0.150 0.169
Dry
0.062 0.073 0.084 0.097 0.111 0.126 0.138
6024
T6024
Wet
0.082 0.096 0.112 0.129 0.145 0.163 0.171
Dry
0.130
6124
T6124
Wet
0.150
13
0.366 0.413
0.396 0.446
0.231 0.259
0.319 0.354
0.154 0.172 0.190 0.210
0.191 0.212 0.235 0.258
0.230 0.256 0.284 0.318
0.259 0.292 0.327 0.365
0.158 0.175 0.195 0.214
0.190 0.211 0.233 0.257
0.154 0.172 0.190 0.210 0.228 0.251 0.273 0.293
0.191 0.212 0.235 0.258 0.283 0.310 0.336 0.366
0.140 0.160 0.180 0.200 0.220 0.240 0.270 0.290
0.170 0.190 0.210 0.230 0.260 0.290 0.310 0.340
Venstar Programmable Thermostat
T2900
STANDARD FEATURES:
• Up to 3-Occupied, 1-Unoccupied periods per day, with copy command for easy programming
• Light Activated occupied period (defeatable)
• Accepts humidification/dehumidification control module (Venstar part number ACC0430)
• Auto changeover, 3-stage heat, 2-stage cool for use with gas/electric, heat pump, electric & hydronic heat
• Configurable for manual changeover, also configurable programmable or non-programmable
• Adjustable deadbands and timers
• Control to, or monitor a second remote sensor
• Can average up to 8 (wired or wireless) remote sensors
• 3 configurable outputs for maximum flexibility (MISC1, MISC2, MISC3)
• Extra 6th and 7th outputs (beyond our standard thermostat)
• Programmable output (control by time, temperature or internet/phone control)
• Energy Watch keeps Track of energy use by tracking heating and cooling hours
• Smart Fan (keeps the fan from running during unoccupied periods)
• Smart recovery
• Pre-occupancy fan purge
• Display shows both heating an cooling setpoints and room temperature simultaneously
• All programming and setpoints stored in non-volatile memory, and are never lost in power failure
• Service filter and service UV lamp indicators
• Red/Green LED shows whether thermostat is calling for heating or cooling
• 5-minute compressor time guard and adjustable cycle limit, both defeatable for servicing equipment
• Outdoor sensor ready with high and low temperature of the day
• Thermoglow backlit electro-luminous display and backlit color coded keys and legends
• Accepts accessory IR Remote Control system (Venstar part number ACC0431)
• Accepts accessory EZ Programmer (Venstar part number ACC0432)
• For accessory locking cover use (Venstar part number ACC0620)
MODEL:
JOB NAME:
LOCATION:
BUYER:
ENGINEER:
T2900
QUANTITY:
DATE:
BUYER P.O.#:
Submittal Cover Sheet
Date Submitted:
May 19, 2015
Date Due Back:
May 26, 2015
RK Submittal No.:
235700.00 - 0
Specification Section:
23 57 00 - Coils and Heat Exchangers
Project Name:
Poudre Valley Health - UCH & FMC Renovation
1025 Garfield Street
General Contractor:
GH Phipps Construction Company
5995 Greenwood Plaza Blvd., Suite 100
Greenwood Village, CO 80111
Mechanical Contractor:
RK Mechanical, Inc.
3800 Xanthia Street
Denver, CO 80238
Subcontractor/Supplier:
RK Mechanical, Inc.
3800 Xanthia Street
Denver, CO 80238
ITEM
COPIES
REV
2
1
0
SUBMITTAL DESCRIPTION
DRAWING
MANUFACTURER
CU-5,6
3800 Xanthia Street
Denver, Colorado 80238
ph: 303.355.9696
fx: 303.355.8666
www.rkmi.com
TAG
CU-5
Model
24ABC648A003
Qty
1
Voltage
208-1-60
4800 OSAGE STREET
DENVER, COLORADO 80221
PHONE: (303) 825-4328
WWW.LOHMILLER.COM
FAX: (303) 820-2302
TAG
CU-6
Model
24ABC660A003
Qty
1
Voltage
208-1-60
4800 OSAGE STREET
DENVER, COLORADO 80221
PHONE: (303) 825-4328
WWW.LOHMILLER.COM
FAX: (303) 820-2302
24ABC6
Comfortt16 Air Conditioner
with Puronr Refrigerant
1---1/2 to 5 Nominal Tons
Product Data
INDUSTRY LEADING
FEATURES / BENEFITS
Efficiency
S 14 -- 16.5 SEER/11.0-- 13.5 EER
S Microtube Technologyt refrigeration system
S Indoor air quality accessories available
Sound
S Sound level as low as 76 dBA
S Sound level as low as 74 dBA with accessory sound
blanket
Comfort
S System supports Edger Thermidistatt or standard
thermostat controls
Reliability
S Puronr refrigerant -- environmentally sound, won’t
deplete the ozone layer and low lifetime servce cost.
Carrier’s Air Conditioners with Puronr refrigerant provide a
collection of features unmatched by any other family of
equipment. The 24ABC has been designed utilizing Carrier’s
Puron refrigerant. The environmentally sound refrigerant allows
you to make a responsible decision in the protection of the earth’s
ozone layer.
This product has been designed and manufactured to meet
Energy Starr criteria for energy efficiency when matched with
appropriate coil components. Refer to the combination ratings in
the Product Data for system combinations that meet Energy Starr
guidelines.
NOTE: Ratings contained in this document are subject to
change at any time. Always refer to the AHRI directory
(www.ahridirectory.org) for the most up--to--date ratings
information.
S Scroll compressor
S Internal pressure relief valve
S Internal thermal overload
S Filter drier
S Balanced refrigeration system for maximum reliability
Durability
WeatherArmort protection package:
S Solid, durable sheet metal construction
S Dense wire coil guard standard
S Baked--on, complete outer coverage, powder paint
Applications
S Long--line -- up to 250 feet (76.20 m) total equivalent
length, up to 200 feet (60.96 m) condenser above
evaporator, or up to 80 ft. (24.38 m) evaporator above
condenser (See Longline Guide for more information.)
S
Low ambient
accessory kit
(down
to
--20_F/--28.9_C)) with
MODEL NUMBER NOMENCLATURE
1
N
2
N
3
A
4
A
5
A/N
6
N
7
N
8
N
9
A/N
10
A/N
11
A/N
12
N
13
N
2
4
A
B
C
6
3
6
A
0
0
3
0
Product
Series
Product
Family
Tier
Major
Series
SEER
Grille
Variations
Open
Open
Voltage
Series
24=AC
A=RES AC
B=Comfort
C=Puron
6=16 SEER
A = Dense
W = Standard
0=Not
Defined
0=Not
Defined
3=208/230 ---1
Cooling
Capacity
Use of the AHRI Certified
TM Mark indicates a
manufacturer’s
participation in the
program For verification
of certification for individual
products, go to
www.ahridirectory.org.
0=
Original
Series
This product has been designed and manufactured to meet
Energy Star criteria for energy efficiency when matched
with appropriate coil components. However, proper
refrigerant charge and proper air flow are critical to achieve
rated capacity and efficiency. Installation of this product
should follow all manufacturing refrigerant charging and air
flow instructions. Failure to confirm proper charge and
air flow may reduce energy efficiency and shorten
equipment life.
CU-5,2,3
CU-6
STANDARD FEATURES
Feature
18
24
30
36
42
48 / 49
Puron Refrigerant
X
X
X
X
X
X
60 / 61
X
Maximum SEER *
16.0
16.0
16.5
16.5
16.0
16.0
16.0
Scroll Compressor
X
X
X
X
X
X
X
Field Installed Filter Drier
X
X
X
X
X
X
X
Front Seating Service Valves
X
X
X
X
X
X
X
Internal Pressure Relief Valve
X
X
X
X
X
X
X
Internal Thermal Overload
X
X
X
X
X
X
X
Long Line capability
X
X
X
X
X
X
X
Low Ambient capability with Kit
X
X
X
X
X
X
X
Dense Grille
X
X
X
X
X
X
X
49--- 30
60--- 30
61--- 30
9.00
(4.08)
14.50
(6.58)
14.50
(6.58)
* With approved combinations
X = Standard
PHYSICAL DATA
UNIT SIZE --- VOLTAGE, SERIES
Compressor Type
REFRIGERANT
Control
Charge lb (kg)
18--- 31
24--- 30
30--- 30
4.60
(2.09)
6.00
(2.72)
6.81
(3.09)
36--- 30
42--- 30
48--- 31
Scroll
Puron (R---410A)
TXV (Puron Hard Shutoff)
6.75
8.62
13.0
(3.06)
(3.91)
(5.90)
Propeller Type, Direct Drive
Vertical
3223
3810
4046
1/12
1/5
1/4
800
800
800
COND FAN
Air Discharge
Vertical
Air Qty (CFM)
1881
2614
2614
4046
4046
4046
Motor HP
1/12
1/10
1/10
1/4
1/4
1/4
Motor RPM
1100
1100
1100
800
800
800
COND COIL
Face Area (Sq ft)
11.50
15.10
17.20
17.60
25.15
25.15
25.15
30.15
30.15
Fins per In.
25
25
25
25
25
20
20
20
20
Rows
1
1
1
1
1
2
1
2
2
Circuits
3
4
4
4
6
7
7
8
8
VALVE CONNECT. (In. ID)
Vapor
3/4
3/4
3/4
7/8
7/8
7/8
7/8
7/8
7/8
Liquid
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
REFRIGERANT TUBES (In. OD)
Rated Vapor*
3/4
7/8
1 ---1/8
Max Liquid Line {
3/8
* Units are rated with 25 ft (7.6 m) of lineset length. See Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of lineset.
Note: See unit Installation Instruction for proper installation.
{ See Liquid Line Sizing For Cooling Only Systems with Puron Refrigerant tables.
2
ACCESSORY THERMOSTATS
PART NUMBER
PROGRAM
TC --- PAC01
TC --- NAC01
TCSNAC01
5--- 2 Day
NP
NP
PART NUMBER
TSTATXXCNV10‡
TX--- LBP01
TX--- MBP01
GAS
Comfort
√
√
√
ELECTRIC
HEAT PUMP
HEAT
COOL
1
1
1
1
1
1
√
√
√
THERMOSTAT ACCESSORIES
DESCRIPTION
Thermostat Conversion Kit (4 to 5 wire) --- 10 pack
Large Decorative Backplate
Medium Decorative Backplate
THERMOSTATS USED WITH
All Carrier branded thermostats
TP--- Pxx, TP--- Nxx, TC --- Pxx
TC --- Nxx, TB--- Pxx
ACCESSORIES
KIT NUMBER
DESCRIPTION
Unit Sizes --- Series
48--- 31
49--- 30
60--- 30
61--- 30
MOTOR FAN BALL BEARING
X
X
X
X
KAACH1201AAA
CRANKCASE HEATER
X
X
KAACH1601AAA
CRANKCASE HEATER
S
S
KAACH1701AAA
CRANKCASE HEATER
X
X
X
X
KAACS0201PTC
START ASSIST PTC
X
X
X
X
X
X
X
X
X
KAAFT0101AAA
FREEZE THERMOSTAT
X
X
X
X
X
X
X
X
X
KAAHI0501PUR
PRESSURE SWITCH
X
X
X
X
X
X
X
X
X
KAALP0401PUR
PRESSURE SWITCH
X
X
X
X
X
X
X
X
X
KAALS0201LLS
LIQUID LINE SOLENOID
X
X
X
X
X
X
X
X
X
KAATD0101TDR
TIME DELAY RELAY
X
X
X
X
X
X
X
X
X
KAAWS0101AAA
WINTER START KIT
X
X
X
X
X
X
X
X
X
KSACY0101AAA
CYCLE PROTECTOR
X
X
X
X
X
X
X
X
X
KSAHS1701AAA
HARD START (CAP/RELAY)
X
X
X
X
X
X
X
X
X
KSALA0301410
LOW AMBIENT KIT
X
X
X
X
X
X
X
X
X
KSALA0601AAA†
MOTORMASTER 230V
X
X
X
X
X
X
X
X
X
KSASF0101AAA
SUPPORT FEET
X
X
X
X
X
X
X
X
KSASF0201AAA
SUPPORT FEET
X
KSASH0601COP
SOUND BLKT KIT
X
X
X
X
X
X
KSASH2101COP
SOUND BLKT KIT
X
X
KSATX0201PUR
TXV PURON HSO
KSATX0301PUR
TXV PURON HSO
KSATX0401PUR
TXV PURON HSO
KSATX0501PUR
TXV PURON HSO
X
X
KSBTX0201PUR
TXV PURON HSO
KSBTX0301PUR
TXV PURON HSO
KSBTX0401PUR
TXV PURON HSO
HC32GE229
MOTOR FAN BALL BEARING
HC32GE234
MOTOR FAN BALL BEARING
HC34GE240
MOTOR FAN BALL BEARING
HC38GE228
MOTOR FAN BALL BEARING
HC40GE228
18--- 31
24--- 30
30--- 30
36--- 30
42--- 30
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
{ Required accessories include ball bearing fan motor, compressor start assist (CAP / Relay), crankcase heater, evaporator freeze stat, hard shut---off TXV.
X = Accessory / S --- Standard
5
ACCESSORY USAGE GUIDELINE
ACCESSORY
Ball Bearing Fan Motor
Compressor Start Assist Capacitor and Relay
Crankcase Heater
Evaporator Freeze Thermostat
Hard Shut---Off TXV
Liquid Line Solenoid Valve
Motor Master Control or
Low---ambient Pressure Switch
Support Feet
Winter Start Control
Yes{
Yes
Yes
Yes
Yes
No
REQUIRED FOR LONG
LINE
APPLICATIONS*
(Over 80 ft./24.38 m)
No
Yes
Yes
No
Yes
No
REQUIRED FOR
SEA COAST
APPLICATIONS
(Within 2 miles/3.22 km)
No
No
No
No
Yes
No
Yes
No
No
Recommended
Yes
No
No
Recommended
No
REQUIRED FOR LOW---AMBIENT COOLING APPLICATIONS
(Below 55F/12.8_C)
* For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 20 ft. (6.09 m) vertical differential, refer to Residential Split---System Longline
Application Guideline.
{ Required for Low---Ambient Controller (full modulation feature) MotorMasterr Control.
Accessory Description and Usage (Listed Alphabetically)
1. Ball--Bearing Fan Motor
A fan motor with ball bearings which permits speed reduction
while maintaining bearing lubrication.
Usage Guideline:
Required on all units when MotorMasterr is used.
2. Compressor Start Assist -- Capacitor and Relay
Start capacitor and relay gives a ”hard” boost to compressor
motor at each start up.
Usage Guideline:
Required for reciprocating compressors in the
following applications:
Long line
Low ambient cooling
Hard shut off expansion valve on indoor coil
Liquid line solenoid on indoor coil
Required for single--phase scroll compressors in the
following applications:
Long line
Low ambient cooling
Suggested for all compressors in areas with a history of
low voltage problems.
3. Compressor Start Assist — PTC Type
Solid state electrical device which gives a ”soft” boost to the
compressor at each start--up.
Usage Guideline:
Suggested in installations with marginal power supply.
4. Crankcase Heater
An electric resistance heater which mounts to the base of the
compressor to keep the lubricant warm during off cycles.
Improves compressor lubrication on restart and minimizes the
chance of liquid slugging.
Usage Guideline:
Required in low ambient cooling applications.
Required in long line applications.
Suggested in all commercial applications.
5. Cycle Protector
The cycle protector is designed to prevent compressor short
cycling. This control provides an approximate 5--minute delay
after power to the compressor has been interrupted for any
reason, including power outage, protector control trip, thermostat
jiggling, or normal cycling.
6. Evaporator Freeze Thermostat
An SPST temperature--actuated switch that stops unit operation
when evaporator reaches freeze--up conditions.
Usage Guideline:
Required when low ambient kit has been added.
7. Low--Ambient Pressure Switch Kit
A long life pressure switch which is mounted to outdoor unit
service valve. It is designed to cycle the outdoor fan motor in
order to maintain head pressure within normal operating limits
(approximately 100 psig to 225 psig). The control will maintain
working head pressure at low--ambient temperatures down to 0_F
(--18_C) when properly installed.
Usage Guideline:
A Low--Ambient Pressure Switch or MotorMasterr
Low--Ambient Controller must be used when cooling operation is
used at outdoor temperatures below 55_F (12.8_C).
8. MotorMasterr Low--Ambient Controller
A fan--speed control device activated by a temperature sensor,
designed to control condenser fan motor speed in response to the
saturated, condensing temperature during operation in cooling
mode only. For outdoor temperatures down to --20_F (--28.9_C),
it maintains condensing temperature at 100_F 10_F (37.8_C 
5.5_C).
Usage Guideline:
A MotorMasterr Low Ambient Controller or
Low--Ambient Pressure Switch must be used when
cooling operation is used at outdoor temperatures
below 55_F (12.8_C).
Suggested for all commercial applications.
9. Outdoor Air Temperature Sensor
Designed for use with Carrier Thermostats listed in this
publication. This device enables the thermostat to display the
outdoor temperature. This device also
is required to enable special thermostat features such as auxiliary
heat lock out.
Usage Guideline:
Suggested for all Carrier thermostats listed in this
publication.
6
Accessory Description and Usage (Listed Alphabetically) (Continued)
13. Time--Delay Relay
An SPST delay relay which briefly continues operation of indoor
blower motor to provide additional cooling after the compressor
cycles off.
NOTE: Most indoor unit controls include this feature. For those
that do not, use the guideline below.
Usage Guideline:
For improved efficiency ratings for certain
combinations of indoor and outdoor units. Refer to
AHRI Unitary Directory.
14. Winter Start Control
This control is designed to alleviate nuisance opening of the
low--pressure switch by bypassing it for the first 3 minutes of
operation.
10. Sound Hood
Wraparound sound reducing cover for the compressor. Reduces
the sound level by about 2 dBA.
Usage Guideline:
Suggested when unit is installed closer than 15 ft (4.57 m) to
quiet areas, bedrooms, etc.
Suggested when unit is installed between two houses less
than 10 ft (3.05 m) apart.
11. Support Feet
Four stick--on plastic feet that raise the unit 4 in. (101.6 mm)
above the mounting pad. This allows sand, dirt, and other debris
to be flushed from the unit base, minimizing corrosion.
Usage Guideline:
Suggested in the following applications:
Coastal installations.
Windy areas or where debris is normally circulating.
Rooftop installations.
For improved sound ratings.
12. Thermostatic Expansion Valve (TXV)
A modulating flow--control valve which meters refrigerant liquid
flow rate into the evaporator in response to the superheat of the
refrigerant gas leaving the evaporator.
Kit includes valve, adapter tubes, and external equalizer tube.
Hard shut off types are available.
NOTE: When using a hard shut off TXV with single phase
reciprocating compressors, a Compressor Start Assist Capacitor
and Relay is required.
Usage Guideline:
Required to achieve AHRI ratings in certain equipment
combinations. Refer to combination ratings.
Hard shut off TXV or LLS required in air conditioner
long line applications.
Required for use on all zoning systems.
7
ELECTRICAL DATA
UNIT SIZE
OPER VOLTS*
V/PH
MCA
MAX FUSE** or
CKT BRK
AMPS
LRA
RLA
FLA
48.0
9.0
0.50
11.8
20
24--- 30
58.3
13.5
0.75
17.7
30
30--- 30
64.0
12.8
0.75
16.8
25
36--- 30
77.0
14.1
0.50
18.1
30
112.0
17.9
1.20
23.6
40
48--- 31
109.0
19.9
1.20
26.1
40
49--- 30
117.0
21.8
1.20
28.4
40
60--- 30
135.0
21.4
1.20
28.0
40
208/230/1 ---60
MIN
FAN
18--- 31
42--- 30
MAX
COMPR
253
197
61--- 30
134.0
25.0
1.20
32.5
* Permissible limits of the voltage range at which the unit will operate satisfactorily
** Time ---Delay fuse.
FLA --- Full Load Amps
LRA --- Locked Rotor Amps
MCA --- Minimum Circuit Amps
RLA --- Rated Load Amps
NOTE: Control circuit is 24 ---V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
All motors/compressors contain internal overload protection.
Complies with 2007 requirements of ASHRAE Standards 90.1
50
A--WEIGHTED SOUND POWER LEVEL (dBA)
Unit Size --Voltage, Series
Standard
Rating (dBA)
018--- 31
024--- 30
030--- 30
036--- 30
042--- 30
048--- 31
049--- 30
060--- 30
061--- 30
76
76
76
76
78
78
78
78
78
125
52.5
57.5
55.0
50.5
52.5
57.5
51.5
55.0
56.5
TYPICAL OCTAVE BAND SPECTRUM (dBA without tone adjustment)
250
500
1000
2000
4000
59.0
65.5
70.5
64.5
59.0
64.0
69.0
71.0
69.0
64.5
63.5
68.0
69.5
67.0
63.5
59.5
64.5
70.5
62.0
59.5
62.0
66.0
73.5
68.0
62.0
61.5
66.0
70.5
65.5
59.5
62.0
67.5
73.5
69.0
64.5
62.5
67.5
70.5
65.0
61.0
63.0
65.5
69.0
67.0
61.5
8000
54.5
60.0
58.5
54.5
55.5
53.5
62.0
53.5
56.0
NOTE: Tested in accordance with AHRI Standard 270 ---08 (not listed in AHRI).
A--WEIGHTED SOUND POWER LEVEL (dBA) WITH SOUND SHIELD
Unit Size --Voltage, Series
Standard
Rating (dBA)
018--- 31
024--- 30
030--- 30
036--- 30
042--- 30
048--- 31
049--- 30
060--- 30
061--- 30
74
75
75
74
76
76
76
75
75
125
55.5
58.0
55.5
51.5
53.0
58.5
53.0
56.5
57.0
TYPICAL OCTAVE BAND SPECTRUM (dBA without tone adjustment)
250
500
1000
2000
4000
59.0
65.0
68.5
63.5
58.0
64.0
69.0
70.5
68.5
64.5
63.0
68.0
69.0
67.0
63.0
58.5
62.0
65.0
61.0
58.0
62.0
65.5
72.0
65.0
61.0
61.5
66.0
69.0
64.0
58.5
61.5
67.5
72.0
68.0
61.5
62.5
66.5
68.0
63.0
59.5
63.0
65.5
67.0
65.5
59.0
NOTE: Tested in accordance with AHRI Standard 270 ---08 (not listed in AHRI).
CHARGING SUBCOOLING (TXV--TYPE EXPANSION DEVICE)
UNIT SIZE --- VOLTAGE, SERIES
18--- 31
24--- 30
30--- 30
36--- 30
42--- 30
48--- 31
49--- 30
60--- 30
61--- 30
REQUIRED SUBCOOLING _F (_C)
10 (5.6)
10 (5.6)
10 (5.6)
10 (5.6)
9 (5.0)
8 (4.4)
8 (4.4)
9 (5.0)
9 (5.0)
8
8000
52.0
59.5
58.5
52.0
54.0
51.0
59.0
51.5
52.5
9
DIMENSIONS -- ENGLISH
11
24”
(609.6)
Service
12”
(304.8)
Note: Numbers in ( ) = mm
18”
(457.2)
24”
(609.6)
Service
Wall
6”
(152.4)
18”
(457.2)
12”
(304.8)
24”
(609.6)
Service
Wall
18”
(457.2)
12”
(304.8)
Clearances (various examples)
24”
(609.6)
Service
12”
(304.8)
24”
(609.6)
Service
Wall
6”
(152.4)
IMPORTANT: When installing multiple units in an alcove, roof well, or partially enclosed area, ensure there is adequate ventilation to prevent re--circulation of discharge air.
CLEARANCES
Wall
CONDENSER ONLY RATINGS CONTINUED
SST
° F (° C)
30
(-1.11)
35
(1.67)
40
(4.44)
45
(7.22)
50
(10.0)
55
(12.78)
30
(-1.11)
35
(1.67)
40
(4.44)
45
(7.22)
50
(10.0)
55
(12.78)
30
(-1.11)
35
(1.67)
40
(4.44)
45
(7.22)
50
(10.0)
55
(12.78)
30
(-1.11)
35
(1.67)
40
(4.44)
45
(7.22)
50
(10.0)
55
(12.78)
55 (12.78)
65 (18.33)
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
37.90
69.80
1.83
41.90
71.20
1.84
46.10
72.70
1.85
50.70
74.20
1.86
55.50
75.80
1.87
60.70
77.40
1.89
36.20
79.20
2.03
40.00
80.60
2.04
44.00
81.90
2.05
48.30
83.30
2.07
52.90
84.80
2.09
57.70
86.40
2.11
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
40.80
67.20
1.98
45.10
68.50
1.91
49.90
69.80
1.80
55.00
71.20
1.65
60.70
72.60
1.46
66.80
74.20
1.22
38.60
76.60
2.28
42.70
77.80
2.24
47.10
79.00
2.16
52.00
80.30
2.05
57.30
81.70
1.90
63.00
83.10
1.72
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
45.00
70.30
2.04
49.80
71.70
1.99
54.90
73.20
1.93
60.40
74.80
1.86
66.20
76.40
1.78
72.40
78.20
1.68
42.40
79.50
2.41
46.80
80.90
2.39
51.50
82.40
2.36
56.60
83.90
2.33
62.00
85.50
2.28
67.70
87.10
2.23
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
49.90
70.90
2.31
55.30
72.50
2.31
61.00
74.10
2.31
67.20
75.80
2.31
73.70
77.60
2.31
80.80
79.50
2.31
47.50
80.40
2.60
52.60
81.80
2.61
58.00
83.40
2.63
63.80
84.90
2.64
70.00
86.60
2.65
76.60
88.40
2.66
CONDENSER ENTERING AIR TEMPERATURES ° F (° C)
75 (23.89)
85 (29.44)
95 (35.0)
105 (40.56)
24ABC642A**30
34.30
32.30
30.10
27.90
88.70
98.10
107.40
116.70
2.26
2.54
2.86
3.22
37.90
35.70
33.30
30.80
89.90
99.20
108.40
117.70
2.28
2.56
2.88
3.24
41.70
39.20
36.70
34.00
91.20
100.40
109.60
118.70
2.30
2.58
2.90
3.26
45.80
43.10
40.20
37.30
92.50
101.60
110.80
119.80
2.32
2.60
2.92
3.29
50.10
47.10
44.00
40.80
93.90
103.00
112.00
121.00
2.34
2.63
2.95
3.32
54.60
51.30
47.90
44.40
95.40
104.40
113.40
122.30
2.36
2.66
2.99
3.36
24ABC648A**31
36.50
34.30
32.10
29.70
86.10
95.50
104.90
114.30
2.56
2.85
3.16
3.50
40.30
37.90
35.40
32.80
87.10
96.50
105.80
115.10
2.55
2.86
3.17
3.52
44.50
41.80
39.00
36.20
88.30
97.50
106.80
116.00
2.50
2.84
3.17
3.53
49.00
46.00
42.90
39.80
89.50
98.60
107.80
117.00
2.43
2.79
3.15
3.53
53.90
50.50
47.10
43.60
90.70
99.80
108.90
118.00
2.32
2.72
3.11
3.51
59.20
55.40
51.60
47.70
92.10
101.10
110.10
119.10
2.17
2.61
3.04
3.47
24ABC649A**30
39.90
37.40
34.90
32.30
88.90
98.20
107.60
116.90
2.75
3.08
3.44
3.84
44.00
41.20
38.50
35.60
90.10
99.40
108.70
118.00
2.75
3.10
3.47
3.87
48.40
45.30
42.20
39.10
91.50
100.70
109.90
119.00
2.75
3.12
3.50
3.91
53.00
49.60
46.20
42.80
92.90
102.00
111.10
120.20
2.75
3.14
3.53
3.95
58.00
54.20
50.50
46.70
94.50
103.40
112.40
121.40
2.73
3.15
3.56
3.99
63.20
59.10
55.00
50.90
96.10
104.90
113.80
122.60
2.71
3.16
3.59
4.02
24ABC660A**30
45.10
42.40
39.60
36.70
89.80
99.20
108.50
117.80
2.90
3.24
3.61
4.05
49.80
46.90
43.90
40.70
91.20
100.50
109.70
118.90
2.93
3.27
3.65
4.08
54.90
51.70
48.40
45.00
92.60
101.80
111.00
120.10
2.95
3.29
3.68
4.12
60.30
56.90
53.30
49.60
94.10
103.20
112.30
121.40
2.97
3.32
3.71
4.15
66.20
62.40
58.50
54.50
95.70
104.70
113.70
122.70
2.99
3.35
3.75
4.19
72.40
68.30
64.00
59.80
97.30
106.20
115.20
124.00
3.02
3.39
3.79
4.24
See notes on page 20
19
115 (46.11)
125 (51.67)
25.50
125.90
3.63
28.30
126.80
3.65
31.20
127.80
3.67
34.30
128.90
3.70
37.50
130.00
3.73
40.80
131.20
3.77
23.00
135.10
4.09
25.60
136.00
4.10
28.30
136.90
4.13
31.10
137.90
4.15
34.10
138.90
4.19
37.10
140.00
4.22
27.20
123.60
3.88
30.10
124.40
3.91
33.20
125.20
3.92
36.50
126.10
3.94
40.00
127.10
3.94
43.70
128.10
3.92
24.60
132.90
4.33
27.30
133.60
4.35
30.10
134.40
4.36
33.10
135.20
4.38
36.30
136.10
4.39
39.60
137.00
4.39
29.50
126.20
4.32
32.60
127.20
4.34
35.80
128.20
4.38
39.30
129.20
4.41
42.90
130.30
4.45
46.70
131.40
4.49
26.40
135.40
4.89
29.30
136.30
4.90
32.30
137.20
4.92
35.50
138.10
4.94
38.70
139.10
4.98
42.10
140.10
5.01
33.50
127.00
4.56
37.30
128.10
4.59
41.40
129.20
4.63
45.70
130.40
4.66
50.40
131.60
4.70
55.30
132.90
4.74
30.20
136.30
5.17
33.80
137.30
5.19
37.60
138.30
5.22
41.70
139.40
5.25
46.10
140.50
5.28
50.70
141.60
5.32
GUIDE SPECIFICATIONS
GENERAL
System Description
Outdoor--mounted, air--cooled, split--system air conditioner unit
suitable for ground or rooftop installation. Unit consists of a
hermetic compressor, an air--cooled coil, propeller--type
condenser fan, and a control box. Unit will discharge supply air
upward as shown on contract drawings. Unit will be used in a
refrigeration circuit to match up to a packaged fan coil or coil
unit.
Quality Assurance
— Unit will be rated in accordance with the latest edition
of AHRI Standard 210.
— Unit will be certified for capacity and efficiency, and
listed in the latest AHRI directory.
— Unit construction will comply with latest edition of
ANSI/ ASHRAE and with NEC.
— Unit will be constructed in accordance with UL
standards and will carry the UL label of approval. Unit
will have c--UL--us approval.
— Unit cabinet will be capable of withstanding Federal
Test Method Standard No. 141 (Method 6061) 500--hr
salt spray test.
— Air--cooled condenser coils will be leak tested at 150
psig and pressure tested at 450 psig.
— Unit constructed in ISO9001 approved facility.
Delivery, Storage, and Handling
— Unit will be shipped as single package only and is
stored and handled per unit manufacturer’s
recommendations.
Warranty (for inclusion by specifying engineer)
— U.S. and Canada only.
PRODUCTS
Equipment
Factory assembled, single piece, air--cooled air conditioner unit.
Contained within the unit enclosure is all factory wiring, piping,
controls, compressor, refrigerant charge Puronr (R--410A), and
special features required prior to field start--up.
Unit Cabinet
— Unit cabinet will be constructed of galvanized steel,
bonderized, and coated with a powder coat paint.
AIR--COOLED, SPLIT--SYSTEM AIR CONDITIONER
24ABC6
1--1/2 TO 5 NOMINAL TONS
Fans
— Condenser fan will be direct--drive propeller type,
discharging air upward.
— Condenser fan motors will be totally enclosed, 1--phase
type with class B insulation and permanently lubricated
bearings. Shafts will be corrosion resistant.
— Fan blades will be statically and dynamically balanced.
— Condenser fan openings will be equipped with coated
steel wire safety guards.
Compressor
— Compressor will be hermetically sealed.
— Compressor will be mounted on rubber vibration
isolators.
Condenser Coil
— Condenser coil will be air cooled.
— Coil will be constructed of aluminum fins mechanically
bonded to copper tubes which are then cleaned,
dehydrated, and sealed.
Refrigeration Components
— Refrigeration circuit components will include
liquid--line shutoff valve with sweat connections,
vapor--line shutoff valve with sweat connections,
system charge of Puronr (R--410A) refrigerant, and
compressor oil.
— Unit will be equipped with filter drier for Puron
refrigerant.
Operating Characteristics
— The capacity of the unit will meet or exceed _____
Btuh at a suction temperature of _____ _F/_C. The
power consumption at full load will not exceed _____
kW.
— Combination of the unit and the evaporator or fan coil
unit will have a total net cooling capacity of _____
Btuh or greater at conditions of _____ CFM entering
air temperature at the evaporator at _____ _F/_C wet
bulb and _____ _F/_C dry bulb, and air entering the
unit at _____ _F/_C.
— The system will have a SEER of _____ Btuh/watt or
greater at DOE conditions.
Electrical Requirements
— Nominal unit electrical characteristics will be _____ v,
single phase, 60 hz. The unit will be capable of
satisfactory operation within voltage limits of _____ v
to _____ v.
— Unit electrical power will be single point connection.
— Control circuit will be 24v.
Special Features
— Refer to section of this literature identifying accessories
and descriptions for specific features and available
enhancements.
21
SYSTEM DESIGN SUMMARY
1.
2.
3.
4.
5.
6.
7.
8.
9.
Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01--in. wc.
Minimum outdoor operating air temperature for cooling mode without low--ambient operation accessory is 55_F (12.8_C).
Maximum outdoor operating air temperature is 125_F (51.7_C).
For reliable operation, unit should be level in all horizontal planes.
For interconnecting refrigerant tube lengths greater than 80 ft (23.4 m) and/or 35 ft (10.7 m) vertical differential, consult Residential
Piping and Longline Guideline and Service Manual available from equipment distributor.
If any refrigerant tubing is buried, provide a 6 in. (152.4 mm) vertical rise to the valve connections at the unit. Refrigerant tubing
lengths up to 36 in. (914.4 mm) may be buried without further consideration. Do not bury refrigerant lines longer than 36 in. (914.4
mm).
Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector
provided.
Do not apply capillary tube indoor coils to these units.
Factory--supplied filter drier must be installed.
Copyright 2015 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231
Edition Date: 04/15
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
22
Catalog No: 24ABC6---5PD
Replaces: 24ABC6--- 4PD
Submittal Cover Sheet
Date Submitted:
May 19, 2015
Date Due Back:
May 26, 2015
RK Submittal No.:
235700.00 - 0
Specification Section:
23 57 00 - Coils and Heat Exchangers
Project Name:
Poudre Valley Health - UCH & FMC Renovation
1025 Garfield Street
General Contractor:
GH Phipps Construction Company
5995 Greenwood Plaza Blvd., Suite 100
Greenwood Village, CO 80111
Mechanical Contractor:
RK Mechanical, Inc.
3800 Xanthia Street
Denver, CO 80238
Subcontractor/Supplier:
RK Mechanical, Inc.
3800 Xanthia Street
Denver, CO 80238
ITEM
COPIES
REV
3
1
0
SUBMITTAL DESCRIPTION
DRAWING
MANUFACTURER
FUR-1,2
3800 Xanthia Street
Denver, Colorado 80238
ph: 303.355.9696
fx: 303.355.8666
www.rkmi.com
TAG
FUR-2,3
Model
59TN6A100V21--22
Qty
2
Voltage
120-1-60
4800 OSAGE STREET
DENVER, COLORADO 80221
PHONE: (303) 825-4328
WWW.LOHMILLER.COM
FAX: (303) 820-2302
59TN6A
InfinityR Two---Stage, Variable Speed
4---Way Multipoise
Condensing Gas Furnace
Series 1
Product Data
A11263
The 59TN6A Multipoise Variable--Speed Condensing Gas Furnace
features the two--stage InfinityR System. The Comfort Heat
TechnologyR two--stage gas system is at the heart of the comfort
provided by this furnace, along with the Infinity variable--speed
ECM blower motor, and two--speed inducer motor. With an
Annual Fuel Utilization Efficiency (AFUE) of up to 96.7%, the
Infinity two--stage gas furnace provides exceptional savings when
compared to a standard furnace. This Infinity Gas Furnace also
features 4--way multipoise installation flexibility, and is available
in five model sizes. The 59TN6A can be vented for direct
vent/two--pipe, ventilated combustion air, or single--pipe
applications. A Carrier Infinity Control and Infinity Air
Conditioner or Heat Pump can be used to form a complete Infinity
System. All units meet California Air Quality Management District
emission requirements. All sizes are design certified in Canada.
STANDARD FEATURES
S InfinityR System; compatible with single-- and multiple--zone
Infinity systems.
S All sizes meet ENERGY STARR Version 4.0 criteria for gas
furnaces: 95+ AFUE; AMACF electrical rating; 2% or less
cabinet airflow leakage.
S Quiet operation. Compare for yourself at HVACpartners.com.
S Ideal height 35--in. (889 mm) cabinet: short enough for taller
coils, but still allows enough room for service.
S Infinity Features—match with the Infinity Control for Infinity
System benefits.
S Integral part of the Ideal Humidity SystemR Technology.
S Silicon Nitride Power Heat Hot Surface Igniter.
S SmartEvap technology helps control humidity levels in the
home when used with a compatible humidity control system.
S ComfortFan technology allows control of continuous fan
speed from a compatible thermostat.
S External Media Filter Cabinet included.
S 4--way multipoise design for upflow, downflow or horizontal
installation, with unique vent elbow and optional through-the--cabinet downflow venting capability.
S Variable--Speed blower motor, two--speed inducer motor, and
two--stage gas valve.
S Self--diagnostics and extended diagnostic data through the
Advanced Product Monitor (APM) accessory or Infinity User
Interface.
S Adjustable blower speed for cooling, continuous fan, and
dehumidification.
S Aluminized--steel primary heat exchanger.
S Stainless--steel condensing secondary heat exchanger.
S Propane convertible (See Accessory list).
S Factory--configured ready for upflow applications.
S Fully--insulated casing including blower section.
S Convenient Air Purifier and Humidifier connections.
S Direct--vent/sealed combustion, single--pipe venting or
ventilated combustion air.
S Installation flexibility: (sidewall or vertical vent).
S Residential installations may be eligible for consumer financing
through the Retail Credit Program.
S Certified to leak 2% or less of nominal air conditioning CFM
delivered when pressurized to 1--in. water column with all
present air inlets, air outlets, and condensate drain port(s) sealed.
Always Ask For
CERTIFIED
1
Use of the AHRI Certified TM Mark indicates a
manufacturer’s participation in the program. For
verification of certification for individual products,
go to www.ahridirectory.org.
SAP ORDERING
NO.
F-5,2,3
F-6
59TN6A060V17--14
59TN6A080V17--14
59TN6A080V21--20
59TN6A100V21--22
59TN6A120V24--22
CASING
DIMENSIONS
(IN.)
H
D
35
35
35
35
35
30
30
30
30
30
W
RATED HEATING
OUTPUT† (BTUH)
High
17.5 58,000
17.5 78,000
21.0 78,000
21.0 98,000
24.5 117,000
Low
AFUE
38,000
50,000
51,000
63,000
76,000
96.3%
96.2%
96.7%
96.1%
96.7%
HEATING AIRFLOW
CFM‡
(Low
Heating)
855
1060
1095
1385
1640
CFM
(High
Heating)
1075
1500
1345
1575
1820
Rated
High Heating
ESP
0.12
0.15
0.15
0.20
0.20
† Capacity in accordance with DOE test procedures. Ratings are position dependent. See rating plate.
‡ Heating CFM at factory default blower motor heating settings.
constant
ESP --- External Static Pressure
59TN6A
FEATURES AND BENEFITS
Comfort Heat TechnologyR feature — This feature with
Adaptive Control is a proprietary function that promotes
homeowner comfort through two stages of heating. This Carrier
furnace offers a patented algorithm that continually monitors and
adjusts furnace operation by looking at both current and past
conditions to determine the most effective stage of heating and the
amount of time to run each stage, every cycle.
Ideal Humidity SystemR Technology — The Ideal Humidity
system actively controls both temperature and humidity in the
home to provide the best comfort all year long. Other systems
depend on heating or cooling demand to manage the moisture in
the air. But, Ideal Humidity gives the homeowner the right amount
of humidity day and night, even in mild weather. No other
manufacturer can do this! Ideal Humidity saves energy, too. By
keeping humidity under control, the homeowner can set their
thermostat lower to stay comfortable and save energy.
SmartEvapt Technology — When paired with a compatible
thermostat, this dehumidification feature overrides the cooling
blower off-delay when there is a call for dehumidification. By
deactivating the blower off-delay, SmartEvap technology prevents
condensate that remains on the coil after a dehumidification cycle
from re-humidifying throughout the home. This results in reduced
humidity and a more comfortable indoor environment for the
homeowner.
Unlike competitive systems, SmartEvap technology only overrides
the cooling blower off--delay when humidity control is needed.
Once humidity is back in control, SmartEvap re-enables the
energy-saving cooling blower off-delay.
ComfortFant Technology — Sometimes the constant fan setting
on a standard furnace system can actually reduce homeowner
comfort by providing too much or too little air! Comfort Fan
technology improves comfort all year long by allowing the
homeowner to select the continuous fan speed of their choice using
a compatible thermostat.
HYBRID HEATR Dual Fuel System — This system can provide
more control over your monthly energy bills by automatically
selecting the most economical method of heating. With HYBRID
HEAT components, our system automatically switches between the
gas furnace and the electric heat pump as outside temperatures
change to maintain greater efficiency and comfort than with any
traditional single-source heating system. The heat pump also
delivers high-efficiency cooling in the summer.
Power Heatt Igniter — Carrier’s unique SiN igniter is not only
physically robust but it is also electrically robust. It is capable of
running at line voltage and does not require complex voltage
regulators as do other brands. This unique feature further enhances
the gas furnace reliability and continues Carrier’s tradition of
technology leadership and innovation in providing a reliable and
durable product.
Full-Featured, Communicating, Variable Speed Motors — Our
ECMs (Electronically Commutated Motors) provide variable-speed
operation to optimize comfort levels in the home year round;
features such as passive/active dehumidification, ramping profiles,
COOLING
CFM @ 0.5
ESP
MOTOR HP
(VARIABLE
SPEED)
MEDIA
CABINET
SUPPLIED
(IN.)
APPROX.
SHIP WT.
(LB)
510 - 1335
490 - 1375
750 - 1945
715 - 2160
885 - 2185
1/2
1/2
1
1
1
16
16
20
20
24
140
150
155
165
189
air flow and quiet operation. They can provide cooling
match enhancements to increase the effective SEER of select
Carrier air conditioner or heat pump system, and feature the highest
efficiency of all indoor fan motors.
Reliable Heat Exchanger Design — The aluminized steel, clam
shell primary heat exchanger was re--engineered to achieve greater
efficiency out of a smaller size. The first two passes of the heat
exchanger are based on the current 80% product, a design with
more than ten years of field-proven performance and success.
These innovations, paired with the continuation of a crimped,
no-weld seam create an efficient, robust design for this essential
component.
The condensing heat exchanger, a stainless steel fin and tube
design, is positioned in the furnace to extract additional heat.
Stainless steel coupling box componentry between heat exchangers
has exceptional corrosion resistance in both natural gas and
propane applications.
Media Filter Cabinet — Enhanced indoor air quality in the home
is made easier with our media filter cabinet—a standard accessory
on all deluxe furnaces. When installed as a part of the system, this
cabinet allows for easy and convenient addition of a Carrier high
efficiency air filter.
4-Way Multipoise Design — One model for all applications –
there is no need to stock special downflow or horizontal models
when one unit will do it all. The new heat exchanger design allows
these units to achieve the certified AFUE in all positions.
Direct or Single-pipe Venting, or Optional Ventilated
Combustion Air — This furnace can be installed as a 2-pipe
(Direct Vent) furnace, in an optional ventilated combustion air
application, or in single-pipe, non-direct vent applications. This
provides added flexibility to meet diverse installation needs.
Sealed Combustion System — This furnace brings in combustion
air from outside the furnace, which results in especially quiet
operation. By sealing the entire combustion vestibule, the entire
furnace can be made quieter, not just the burners.
Insulated Casing — Foil-faced insulation in the heat exchanger
section of the casing minimizes heat loss. The acoustical insulation
in the blower compartment reduces air and motor noise for quiet
operation.
Monoport Burners — The burners are specially designed and
finely tuned for smooth, quiet combustion and economical
operation.
Bottom Closure — Factory-installed for side return; easily
removable for bottom return. The multi-use bottom closure can
also serve for roll-out protection in horizontal applications, and act
as the bottom closure for the optional return air base accessory.
Blower Access Panel Switch — Automatically shuts off 115-v
power to furnace whenever blower access panel is opened.
Quality Registration — Our furnaces are engineered and
manufactured under an ISO 9001 registered quality system.
Certifications — This furnace is CSA (AGA and CGA) design
certified for use with natural and propane gases. The furnace is
factory--shipped for use with natural gas. A CSA listed gas
conversion kit is required to convert furnace for use with propane
gas. The efficiency is AHRI efficiency rating certified. This furnace
meets California Air Quality Management District emission
requirements.
2
SPECIFICATIONS
Heating Capacity and Efficiency
High
Heat
Input
Low
Heat
High
Heat
Output
Low
Heat
Efficiency
Certified Temperature
Rise Range ºF (ºC)
Airflow Capacity and Blower Data
Rated External Static
Pressure (in. w.c.)
Airflow Delivery
@ Rated ESP (CFM)
Cooling Capacity (tons)
Direct-Drive Motor Type
Direct-Drive Motor HP
Motor Full Load Amps
RPM Range
Speed Selections
Blower Wheel Dia x Width
method to calculate heating load estimates and select the furnace.
Excessive oversizing of the furnace may cause the furnace and/or
vent to fail prematurely, customer discomfort and/or vent freezing.
Failure to follow these guidelines is considered faulty installation
and/or misapplication of the furnace; and resulting failure, damage,
or repairs may impact warranty coverage.
060-14
080-14
080-20
100-22
120-22
(BTUH)
60,000
80,000
80,000
100,000
120,000
(BTUH)
39,000
52,000
52,000
65,000
78,000
(BTUH)
58,000
78,000
78,000
98,000
117,000
(BTUH)
38,000
50,000
51,000
63,000
76,000
96.3
35 - 65
(19 - 36)
30 - 60
(17 - 33)
96.2
40 - 70
(22 - 39)
30 - 60
(17 - 33)
96.7
40 - 70
(22 - 39)
30 - 60
(17 - 33)
96.1
45 - 75
(25 - 42)
30 - 60
(17 - 33)
96.7
45 - 75
(25 - 42)
30 - 60
(17 - 33)
AFUE % (ICS)
High Heat
Low Heat
Heating
Cooling
High Heat
Low Heat
Cooling
400 CFM/ton
350 CFM/ton
060-14
0.12
0.5
1075
855
1335
3
3.5
080-14
080-20
100-22
0.15
0.15
0.20
0.5
0.5
0.5
1500
1345
1575
1060
1095
1385
1375
1945
2160
3.5
4.5
5
4
5.5
6
Electronically Commutated Motor (ECM)
1/2
1
1
7.7
12.8
12.8
300 - 1300
Variable (Communicating)
11 x 8
11x10
11 x 10
Factory Supplied Media Cabinet
Field Supplied Filter
KGAWF**06UFR
1/2
7.7
in.
11 x 8
Air Filtration System
Filter Used for Certified Watt Data*
Electrical Data
Input Voltage
Operating Voltage Range
Maximum Input Amps
Unit Ampacity
Minimum Wire Size
Maximum Wire Length
@ Minimum Wire Size
Maximum Fuse/Ckt Bkr
(Time-Delay Type Recommended)
Transformer Capacity (24vac
output)
External Control Power
Available
Controls
Gas Connection Size
Burners (Monoport)
Gas Valve (Redundant)
060-14
080-14
Volts-Hertz-Phase
080-20
120-22
0.20
0.5
1820
1640
2185
5.5
6
1
12.8
11 x 11
100-22
120-22
115-60-1
Min-Max
Amps
Amps
AWG
Feet
(M)
8.5
11.5
14
32
(9.8)
8.5
11.5
14
32
(9.8)
104-127
13.6
17.9
12
32
(9.8)
13.7
18.0
12
31
(9.4)
13.7
18.0
12
31
(9.4)
Amps
15
15
20
20
20
100-22
120-22
5
6
40 VA
Heating
Cooling
24.3 VA
34.6 VA
060-14
080-14
3
4
Manufacturer
Minimum Inlet Gas pressure (in. wc)
Maximum Inlet Gas pressure (in. wc)
Manufactured (Mobile) Home Kit
Ignition Device
Limit Control
Heating Blower Control (Heating Off-Delay)
Cooling Blower Control (Time Delay Relay)
080-20
1/2" - NPT
4
White Rogers
4.5
13.6
not approved for MH use
Silicon Nitride
170
200
180
Adjustable: 90, 120, 150, 180 seconds
90 seconds
180
3
160
59TN6A
The furnace should be sized to provide 100 percent of the design
heating load requirement plus any margin that occurs because of
furnace model size capacity increments. None of the furnace
model sizes can be used if the heating load is 20,000 BTU or
lower. Use Air Conditioning Contractors of America (Manual J
and S); American Society of Heating, Refrigerating, and
Air-Conditioning Engineers; or other approved engineering
SPECIFICATIONS (CONT.)
Communication System
Thermostat Connections
Accessory Connections
Infinity; Infinity Zoning
R, W/W1, W2 Y/Y2, Y1, G, Com 24V, DHUM
EAC (115vac); HUM (24vac); 1-stg AC (via Y/Y2)
* See Accessory List for part numbers available.
MODEL NUMBER NOMENCLATURE
Example of Model Number
1-2
Family
59
3
Htg. Stages
T
4
Tier
N
5
Base Effy.
6
6
Major Series
A
7-9
Htg. Cap.
11 - 12
Width
17
10
Motor
V
060
13
Voltage
--
14
Minor Series
--
08 - 800 CFM
10 - 1000 CFM
12 - 1200 CFM
14 - 1400 CFM
16 - 1600 CFM
18 - 1800 CFM
20 - 2000 CFM
22 - 2200 CFM
Family
S - Single Stage
T - Two Stage
M - Modulating
59TN6A
C - Comfort
P - Performance
N - Infinity
0 - +90 AFUE
2 - +92 AFUE
3 - +93 AFUE
5 - +95 AFUE
6 - +96 AFUE
7 - +97 AFUE
14 - 14.2”
17 - 17.5”
21 - 21.0”
24 - 24.5”
Major Series
15 - 16
Airflow
14
Minor Series
Voltage
040=40,000 BTU
060=60,000 BTU S - Standard
080=80,000 BTU E - Energy Efficient
100=100,000 BTU V - Variable Speed
120=120,000 BTU
140=140,000 BTU
Not all familes have these models.
A12373
FURNACE COMPONENTS
GAS BURNER
HOT SURFACE
IGNITER
MANUAL RESET
ROLLOUT SWITCH
FLAME
SENSOR
MANUAL RESET
ROLLOUT SWITCH
GAS VALVE
MAIN LIMIT SWITCH
(BEHIND GAS VALVE)
OPERATING INSTRUCTIONS
NOT SHOWN (LOCATED ON
MAIN FURNACE DOOR, SEE
OPERATING INSTRUCTIONS
INSIDE DOOR FIGURE).
INDUCER MOTOR
ASSEMBLY
ELECTRICAL JUNCTION
BOX (IF REQUIRED,
LOCATION MAY VARY)
BLOWER DOOR
SAFETY SWITCH
MEDIA CABINET
BLOWER AND
MOTOR
FURNACE
CONTROL
BOARD
CAPACITOR/
POWER CHOKE
(IF USED)
RATING PLATE NOT SHOWN
(LOCATED ON BLOWER DOOR)
REPRESENTATIVE DRAWING ONLY, SOME MODELS MAY VARY IN APPEARANCE.
A11408
4
ACCESSORIES
Venting Accessories
Vent Kit - Through the Cabinet
Vent Terminal - Concentric - 2” (51 mm)
Vent Terminal - Concentric - 3” (76 mm)
Vent Terminal Bracket - 2” (51 mm)
Vent Terminal Bracket - 3” (76 mm)
Vent Kit --- Rubber Coupling
Condensate Drainage Accessories
Freeze Protect Kit - Heat Tape
CPVC to PVC Drain Adapters - 1/2” CPVC to 3/4” PVC
Horizontal Trap Grommet - Direct Vent
Condensate Neutralizer Kit
External Trap Kit
Ductwork Adapter Accessories
Furnace Base Kit for Combustible Floors
Coil Adapter Kits --- No Offset
Coil Adapter Kits --- Single Offset
Coil Adapter Kits --- Double Offset
Return Air Base (Upflow Applications) 17.5--- in. wide
Return Air Base (Upflow Applications) 21.0--- in. wide
Return Air Base (Upflow Applications) 24.5--- in. wide
IAQ Device Duct Adapters 20.0--- in. IAQ to 16 in. Side Return
IAQ Device Duct Adapters 24.0--- in. IAQ to 16 in. Side Return
Gas Conversion Accessories
Gas Conversion Kit - Nat to LP; Var-speed Products
Gas Conversion Kit - LP to Nat; Var-speed Products
Gas Orifice Kit - #42 (Nat Gas)
Gas Orifice Kit - #43 (Nat Gas)
Gas Orifice Kit - #44 (Nat Gas)
Gas Orifice Kit - #45 (Nat Gas)
Gas Orifice Kit - #46 (Nat Gas)
Gas Orifice Kit - #47 (Nat Gas)
Gas Orifice Kit - #48 (Nat Gas)
Gas Orifice Kit - #54 (LP)
Gas Orifice Kit - #55 (LP)
Gas Orifice Kit - #56 (LP)
Gas Orifice Kit - 1.25mm (LP)
Gas Orifice Kit - 1.30mm (LP)
Control Accessories
ECM Motor Simulator Kit
Advanced Product Monitor - APM
Infinity Touch Control --- Wi--- Fi
Infinity Touch Control --- Non--- Wi--- Fi
IAQ Accessories
Filter Pack (6 pack) --- Washable - 16x25x1 (406x635x25 mm)
Filter Pack (6 pack) --- Washable - 24x25x1 (610x635x25 mm)
EZ-Flex Filter - 16” (406 mm)
EZ-Flex Filter - 20” (508 mm)
EZ-Flex Filter - 24” (610 mm)
EZ-Flex Filter with End Caps - 16” (406 mm)
EZ-Flex Filter with End Caps - 20” (508 mm)
EZ-Flex Filter with End Caps - 24” (610 mm)
Cartridge Media Filter - 16” (406 mm)
Cartridge Media Filter - 20” (508 mm)
Cartridge Media Filter - 24” (610 mm)
Carrier Infinity Air Purifier - 16x25 (406x635 mm)
Carrier Infinity Air Purifier - 20x25 (508x635 mm)
Carrier Infinity Air Purifier Repl. Filter- 16x25 (406x635 mm)
Carrier Infinity Air Purifier Repl. Filter- 20x25 (508x635 mm)
Carrier Performance Air Purifier - 16x25 (508x635 mm)
Carrier Performance Air Purifier - 20x25 (508x635 mm)
Carrier Performance Air Purifier Repl Filter - 16x25 (406x635 mm)
Carrier Performance Air Purifier Repl. Filter - 20x25 (508x635 mm)
PART NUMBER
060-14 080-14 080-20 100-22 120-22
KGADC0101BVC
KGAVT0701CVT
KGAVT0801CVT
KGAVT0101BRA
KGAVT0201BRA
KGAAC0101RVC
D
KGAHT0101CFP
KGAAD0110PVC
KGACK0101HCK
P908--- 0001
KGAET0201ETK
D
D
D
D
D
D
See Venting Tables
See Venting Tables
D
D
D
D
D
D
D
D
All DV Horizontal
D
D
D
D
D
D
KGASB0201ALL
KGADA0101ALL
KGADA0201ALL
KGADA0301ALL
KGARP0301B17
KGARP0301B21
KGARP0301B24
KGAAD0101MEC
KGAAD0201MEC
D
D
D
D
D
D
D
D
D
D
D
D
D
D
KGCNP5201VSP
KGCPN4401VSP
LH32DB207
LH32DB202
LH32DB200
LH32DB205
LH32DB208
LH32DB078
LH32DB076
LH32DB203
LH32DB201
LH32DB206
LH32DB209
LH32DB210
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
KGBSD0301FMS
KGASD0301APM
SYSTXCCITW01
SYSTXCCITN01
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
KGAWF1306UFR
KGAWF1506UFR
EXPXXFIL0016
EXPXXFIL0020
EXPXXFIL0024
EXPXXUNV0016
EXPXXUNV0020
EXPXXUNV0024
FILXXCAR0016
FILXXCAR0020
FILXXCAR0024
GAPAAXCC1625-A08
GAPAAXCC2025-A08
D
D
GAPACCCAR1625-A05
GAPACCCAR2025-A05
PGAPXX1625
PGAPXX2025
PGAPAXXCAR1625
PGAPAXXCAR2025
D = Used with the model furnace
5
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
20”x25” IAQ Devices
24”x25” IAQ Devices
D
D
D
D
D
D
Use with EZXCAB--- 1016
Use with EZXCAB--- 1020
Use with EZXCAB--- 1024
Use with EZXCAB--- 1016
Use with EZXCAB--- 1020
Use with EZXCAB--- 1024
Use with FILCABXL --- 1016
Use with FILCABXL --- 1020
Use with FILCABXL --- 1024
Up to 1600 CFM
Up to 2000 CFM
GAPAAXCC1625--- A08
GAPAAXCC2025--- A08
Up to 1600 CFM
Up to 2000 CFM
GAPAAXCC1625
GAPAAXCC2025
D
D
59TN6A
DESCRIPTION
AIR DELIVERY (CONTINUED)
AND HEATING AIR DELIVERY - CFM (Bottom Return5 With Filter)
(SW1-5 and SW4-3 set to OFF, except as indicated. See notes 1 and 2.)
Unit Size
Clg/CF Switch Settings
SWx-3
SWx-2
SWx-1
0.1
0.2
0.3
External Static Pressure (ESP)
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1805
1780
1770
1095
1295
1480
1825
2115
See note 4
See note 4
1080
1300
1485
1805
2100
1065
1290
1475
1780
2070
1070
1285
1460
1770
2015
100-22
Clg Default:
OFF
OFF
OFF
1820
1825
1840
1845
1840
CF Default:
OFF
OFF
OFF
750
740
745
730
715
See note 4
Cooling (SW2)
Cont Fan
(SW3)
OFF
OFF
OFF
ON
ON
ON
ON
OFF
ON
ON
OFF
OFF
ON
ON
ON
OFF
ON
OFF
ON
OFF
ON
750
900
1070
1280
1440
1820
2135
740
900
1075
1285
1445
1825
2140
745
915
1095
1305
1465
1840
2140
730
910
1095
1305
1465
1845
2135
715
905
1090
1310
1470
1840
2140
1085
1305
1485
1835
2130
Maximum Clg Airflow 2
2160
2165
2175
2170
2160
2150
2135
2120
2065
2020
Heating
(SW1)
High Heat Airflow 3
Low Heat Airflow 3
1570
1365
1575
1385
1595
1395
1595
1395
1600
1395
1605
1400
1600
1400
1600
1405
1590
1395
1575
1380
Unit Size
Clg/CF Switch Settings
SWx-3
SWx-2
SWx-1
0.1
0.2
0.3
0.8
0.9
1.0
1775
1750
1730
CF Default:
Cooling (SW2)
Cont Fan
(SW3)
2.
3.
4.
5.
6.
7.
1825
Clg SW2:
120-22 6
Clg Default:
1.
1835
External Static Pressure (ESP)
0.4
0.5
0.6
0.7
OFF
OFF
OFF
1850
1855
1860
1855
1850
1830
1805
OFF
OFF
OFF
930
925
915
900
885
See note 4
OFF
OFF
OFF
ON
ON
ON
ON
OFF
ON
ON
OFF
OFF
ON
ON
ON
OFF
ON
OFF
ON
OFF
ON
765
930
1095
1265
1465
1850
2200
745
925
1100
1255
1455
1855
2200
740
915
1110
1265
1470
1860
2200
705
900
1105
1280
1465
1855
2190
680
885
1085
1275
1465
1850
2185
1285
1470
1830
2170
1270
1455
1805
2145
See note 4
See note 4
See note 4
1260
1450
1775
2085
1250
1435
1750
1990
1230
1415
1730
1890
Clg SW2:
Maximum Clg Airflow 2
2200
2200
2200
2190
2185
2170
2145
2085
1990
1890
Heating
(SW1)
High Heat Airflow 3
Low Heat Airflow 3
1815
1640
1820
1640
1825
1645
1820
1650
1815
1645
1795
1645
1775
1630
1745
1620
1720
1600
1700
1580
Nominal 350 CFM/ton cooling airflow is delivered with SW1-5 and SW4-3set to OFF.
Set SW1-5 to ON for nominal 400 CFM/ton (+15% airflow).
Set SW4-3 to ON for nominal 325 CFM/ton (-7% airflow).
Set both SW1-5 and SW4-3 to ON for nominal 370 CFM/ton (+7% airflow).
The above adjustments in airflow are subject to motor horsepower range/capacity.
Maximum cooling airflow is achieved when switches SW2-1, SW2-2, SW2-3 and SW1-5 are set to ON, and SW4-3 is set to OFF.
All heating CFM's are when low heat rise adjustment switch (SW1-3) and comfort/efficiency adjustment switch (SW1-4) are both set to OFF.
Ductwork must be sized for high-heating CFM within the operational range of ESP. Operation within the blank areas of the chart is not recommended because high-heat operation will be above 1.0 ESP.
All airflows on 21" (533 mm) casing size furnaces are 5% less on side return only installations.
Side returns for 24.5" (622 mm) casing sizes require two sides, or side and bottom, to allow sufficient airflow at the return of the furnace.
Airflows over 1800 CFM require bottom return, two-side return, or bottom and side return; otherwise excessive watt draws may result. A
minimum filter size of 20" x 25" (508 x 635 mm) is required.
7
59TN6A
COOLING4
MEDIA FILTER CABINET
25-5/8"
(651mm)
24-1/4”
(616mm)
Opening with Flanges Bent
23-1/8”
(588mm)
Opening
23-5/8"
(600mm)
23-3/8”
(594mm)
B Opening
59TN6A
A
Duct Side
Furnace Side
23-3/4”
(603mm)
Centerline Screw Slots
5 3 4"
(146mm)
Media Filter
A
B
Cabinet
16" (406mm) 17" (432mm) 16" (406mm)
20" (508mm) 21" (533mm) 20" (508mm)
24" (610mm) 25" (635mm) 24" (610mm)
NOTE: Media cabinet is matched to the bottom opening on furnace. May also be used for side return.
A12428
TYPICAL WIRING SCHEMATIC
FIELD 24-VOLT WIRING
FIELD 115-, 208/230-, 460-VOLT WIRING
FACTORY 24-VOLT WIRING
FACTORY 115-VOLT WIRING
NOTE 2
W
FIVE
WIRE
BLOWER
DOOR
SWITCH
BLK
Y
R
G
1-STAGE
THERMOSTAT
TERMINALS
FIELD-SUPPLIED
FUSED DISCONNECT
THREE-WIRE
HEATINGONLY
BLK
WHT
C
WHT
GND
115-VOLT FIELD- JUNCTION
SUPPLIED
BOX
FUSED
DISCONNECT
C
O
N
T
R
O
L
208/230- OR
460-VOLT
THREE
PHASE
W2
COM
W/W1
Y/Y2
NOTE 1
R
GND
CONDENSING
UNIT
G
24-VOLT
TERMINAL
BLOCK
FURNACE
208/230VOLT
SINGLE
PHASE
NOTES: 1. Connect Y/Y2-terminal as shown for proper operation.
2. Some thermostats require a "C" terminal connection as shown.
3. If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
A11401
13
59TN6
FURNACE SIZE
060--- 14
080--- 14
080--- 20
100--- 22
120--- 22
25 1/8
[638.7]
14
A
CABINET WIDTH
B
OUTLET WIDTH
C
BOTTOM INLET WIDTH
D
AIR INTAKE
17--- 1/2 (445)
15--- 7/8 (403)
16 (406)
8--- 3/4 (222)
21 (533)
19--- 3/8 (492)
19--- 1/2 (495)
10--- 1/2 (267)
24--- 1/2 (622)
22--- 7/8 (581)
23 (584)
12--- 1/4 (311)
21
[534.0]
26 5/16
[668.8]
22
[558.3] (BOTH SIDES)
1 (BOTH SIDES)
[25.4]
7/8
[22.2]
THERMOSTAT ENTRY
SIDE INLET
2 1/2
[63.5]
7/8
[22.2]
7/8
[22.2]
7/8
[22.2]
4
[101.6]
CONDENSATE DRAIN TRAP
LOCATION
AIR FLOW
19 1/8
[485.8]
20 5/8
[522.7]
23 5/16
[592.9]
26 3/8
[670.0]
26 11/16
[678.1]
TOP VIEW
6 11/16
[170.1]
6 15/16
[176.1]
D
SEE NOTE #3
14 13/16
[376.3]
16 9/16
[420.9]
17 5/16
[439.2]
7/8
[22.2] POWER CONN
3
[76.2]
VENT
1 3/4
[44.5]
GAS CONN
3
[76.2]
AIR INTAKE
3
[76.2]
AIR INTAKE
3
[76.2]
VENT
2 3/10
[58.4]
23 7/16
[595.6] 25 3/16
[639.1]
22 15/16
[581.9]
20 1/4
[513.9]
28 5/8
[726.4]
28 3/16
[715.9]
11/16
[17.5]
32 5/8
[829.5]
5/8
[15.8]
NOTE: ALL DIMENSIONS IN INCH [MM]
C
BOTTOM RETURN
WIDTH
AIR FLOW
B
OUTLET WIDTH
A
2 1/2
[63.5]
1 5/16
[33.3]
6 1/16
[154.0]
16 9/16
[420.9]
17 7/16
[442.3]
20 1/4
[513.9] 18 1/16
[458.6]
24
[609.7]
28 3/8
[720.4]
28 5/8
[726.9]
29 13/16
[757]
11/16
[17.5]
35
[889.0]
3
[76.2 ]
3
[76.2]
AIR INTAKE
2
NEXT SHEET
SD5024-4
PART NUMBER
7/8
[22.2]
4
[101.6]
SIDE INLET
7/8
[22.2] POWER CONN
7/8
[22.2]
1 3/4
[44.5]
GAS CONN
7/8
[22.2]
AIR FLOW
20 5/8
[522.7]
21 1/16
[535.8]
21 15/16
[557.4]
26 3/8
[669.9]
26 11/16
[678.1]
28 3/4
[730.5]
29 1/2
[749.3]
REV
E
SHT
1
BOTTOM INLET
21 5/8
[549.5]
23 3/8
[592.0]
26 5/16
[668.8]
7/8
[22.2]
THERMOSTAT ENTRY
NOTES:
1. Doors may vary by model.
2. Minimum return-air openings at furnace, based on metal duct. If flex duct is used,
see flex duct manufacturer's recommendations for equivalent diameters.
a. For 800 CFM-16-in. (406 mm) round or 14 1/2 x 12-in. (368 x 305 mm) rectangle.
b. For 1200 CFM-20-in. (508 mm) round or 14 1/2 x 19 1/2-in. (368 x 495 mm) rectangle.
c. For 1600 CFM-22-in. (559 mm) round or 14 1/2 x 22 1/16-in. (368 x 560mm) rectangle.
d. Return air above 1800 CFM at 0.5 in. w.c. ESP on 24.5" casing, requires one of the following
configurations: 2 sides, 1 side and a bottom or bottom only. See Air Delivery table in this
document for specific use to allow for sufficient airflow to the furnace.
3. Vent and Combustion air pipes through blower compartment must
use accessory “Vent Kit - Through the Cabinet”. See accessory list for
current part number.
59TN6A
DIMENSIONAL DRAWING
SHIP WT.
LB (KG)
A12267
140.0 (63.0)
150.0 (67.5)
154.5 (70.2)
164.5 (74.0)
188.5 (84.8)
GUIDE SPECIFICATIONS
System Description
Furnish a ______________________ 4--way multipoise
two--stage gas--fired condensing furnace for use with natural gas or
propane (factory-- authorized conversion kit required for propane);
furnish external media cabinet for use with accessory media filter
or standard filter.
Quality Assurance
Unit will be designed, tested and constructed to the current ANSI Z
21.47/CSA 2.3 design standard for gas--fired central furnaces.
Unit will be third party certified by CSA to the current ANSI Z
21.47/CSA 2.3 design standard for gas--fired central furnaces. Unit
will carry the CSA Blue StarR and Blue FlameR labels. Unit
efficiency testing will be performed per the current DOE test
procedure as listed in the Federal Register.
Unit will be certified for capacity and efficiency and listed in the
latest AHRI Consumer’s Directory of Certified Efficiency Ratings.
Unit will carry the current Federal Trade Commission Energy
Guide efficiency label.
Delivery, Storage, and Handling
Unit will be shipped as single package only and is stored and
handled per unit manufacturer’s recommendations.
Warranty (for inclusion by specifying engineer)
U.S. and Canada only. Warranty certificate available upon request.
Equipment
Blower Wheel and ECM Blower Motor
Galvanized blower wheel shall be centrifugal type, statically and
dynamically balanced. Blower motor of ECM type shall be
permanently lubricated with sealed ball bearings, of _______hp,
and have infinitely variable speed from 300--1300 RPM operating
only when motor inputs are provided. Blower motor shall be direct
drive and soft mounted to the blower housing to reduce vibration
transmission.
Filters
Furnace shall have reusable--type filters. Filter shall be ______ in.
(mm) X ________ in. (mm). An accessory highly efficient Media
Filter is available as an option. _____________ Media Filter.
Casing
Casing shall be of .030 in. thickness minimum, pre--painted steel.
Draft Inducer Motor
Draft Inducer motor shall be two--speed PSC design.
Primary Heat Exchangers
Primary heat exchangers shall be 3--Pass corrosion--resistant
aluminized steel of fold--and--crimp sectional design and applied
operating under negative pressure.
Secondary Heat Exchangers
Secondary heat exchangers shall be of a stainless steel
flow--through of fin--and--tube design and applied operating under
negative pressure.
Controls
Controls shall include a micro--processor--based integrated
electronic control board with at least 16 service troubleshooting
codes displayed via diagnostic flashing LED light on the control, a
self--test feature that checks all major functions of the furnace, and
a replaceable automotive--type circuit protection fuse. Multiple
operational settings available, including separate blower speeds for
low heat, high heat, low cooling, high cooling and continuous fan.
Continuous fan speed may be adjusted from the thermostat.
Cooling airflow will be selectable between 325 to 400 CFM per
ton of air conditioning. Features will also include temporary
reduced airflow in the cooling mode for improved
dehumidification when an Infinity Control or TP--PRH edgeR is
selected as the thermostat.
Operating Characteristics
Heating capacity shall be _________________ Btuh input;
______________ Btuh output capacity.
Fuel Gas Efficiency shall be __________ AFUE.
Air delivery shall be ________________ cfm minimum at 0.50 in.
W.C. external static pressure.
Dimensions shall be: depth_________in. (mm); width
__________in. (mm); height___________in. (mm) (casing only).
Height shall be _________in. (mm) with A/C coil and
_________________in. (mm) overall with plenum.
Electrical Requirements
Electrical supply shall be 115 volts, 60 Hz, single--phase (nominal).
Minimum wire size shall be ________AWG; maximum fuse size
of HACR--type designated circuit breaker shall be _________
amps.
Special Features
Refer to section of the product data identifying accessories and
descriptions for specific features and available enhancements.
15
59TN6A
General
CNPVP, CNPVT, CNPVU, CNRVU
Evaporator Coil
N Coil --- Cased and Uncased
Upflow, Downflow
Product Data
A06008
CNPVP
This vertical design N--coil is a furnace coil designed to provide the
highest standards of reliability and durability. The coils are
available for use in R--410A and R--22 refrigerant systems.
Both designs have a painted case and come with factory--installed
thermostatic expansion valves (TXV). The coils are offered in
different width configurations for use in multiple installation
applications. Additionally, they are offered in a transition
configuration, a design which simplifies making field--supplied
transition duct configurations. Easy maintenance is provided as the
coil slides out of the cabinet after removing the access door and
service panel. The coils are available in sizes 018 through 061
(1--1/2 to 5 tons).
Transition coil models CNPVT are designed for use with one size
smaller width furnaces without field modifications.
Aluminum Coils -- “L” models are built with aluminum hairpins,
designed to resist both general pitting corrosion and excessive
indoor Formicary Corrosion. (Formicary Corrosion is an industry
phenomenon.)
STANDARD FEATURES
A06007
CNPVT (Transition)
A06004
CN(P,R)VU
Water Management — These coil designs do an excellent job of
water management. The coils are designed to avoid water blow--off
into the ducts by directing condensate away from the fins and into
the drain pan.
Durable Condensate Pan — Each coil is equipped with a
corrosion--resistant condensate drain pan. The condensate drain
pan is designed with a slope to help ensure proper drainage,
improved moisture removal, and home comfort.
Compact Design — Unique design offers as much as 2 to 4 in. (51
to 102 mm) less in height to aid in tight installations.
Brass Inserts — Every condensate pan features two 3/4 in. female
threaded brass insert connections. The unique brass inserts provide
for a leak--free condensate line connection to prevent water
damage.
Refrigerant Connections — The coils are provided with proven
sweat--connections for leak--free operation maintaining system
reliability.
Burst Pressures — These coils meet or exceed burst pressure of
2100 psi which is at least three to five times the pressure they will
see in actual application.
Thermostatic Expansion Valves (TXV) — All Payne coils have
refrigerant--specific factory--installed TXVs.
Teflon Ring — The ring, installed inside the liquid line connection
at the TXV, is the best option for preventing refrigerant leaks and
future service calls. Teflon works with both R--410A and R--22
refrigerants.
Protective Tube Sheets — Protect the durable copper tubing from
being damaged during the manufacturing and installation process.
MODEL NUMBER NOMENCLATURE
1
2
3
4
5
6
7
8
9
10
11
12
C
N
P
V
P
1
8
1
4
A
C
A
Product
C = Coil
Variations
A = Basic
Type
N = N Coil
Tubing Design
C = Copper (R--- 410A Only)
L = Aluminum (R--- 22 & R--- 410A)
T = Tin--- Plated Copper (R--- 22 & R--- 410A)
Refrigerant Type
P = R--- 410A Refrigerant TXV
R = R--- 22 TXV
Revision Level
A = 1st
Coil Configuration
V = Upflow / Downflow
Cabinet Width
14 = 14--- in. / 356mm
17 = 17--- in. / 432mm
21 = 21--- in. / 533mm
24 = 24--- in. / 610mm
F-5,2,3
Cabinet Finish
P = Painted
U = Uncased
T = Transition N
F-6
Unit Capacity
18 = 1 1/2 Ton
19 = 1 1/2 Ton
24 = 2 Ton
30 = 2 1/2 Ton
31 = 2 1/2 Ton
36 = 3 Ton
Use of the AHRI Certified
TM Mark indicates a
manufacturer’s
participation in the
program For verification
of certification for individual
products, go to
www.ahridirectory.org.
2
37 = 3 Ton
42 = 3 1/2 Ton
43 = 3 1/2 Ton
48 = 4 Ton
60 = 5 Ton
61 = 5 Ton
F-5,2,3
F-6
DIMENSIONS
21 "
E
D
7/8 "
1/2 "
OUTSIDE OF
FLANGES
9/16 "
3/8" I.D.
LIQUID LINE
SWEAT CONNECTION
C
18-9/16 "
OUTSIDE OF
FLANGES
1-9/16 "
1-7/8 " MAX
FI.D.
SUCTION LINE
SWEAT CONNECTION
A
2-1/16 "
B
3/4" PLUGGED DRAIN
2-1/8 "
1-3/8 "
3/4" NPT DRAIN
13/16 "
1-9/16 "
NOTE:
3-1/16 "
1. SERIES DESIGNATION IS THE 14TH POSITION OF UNIT MODEL NUMBER.
2. IN THE ELEVENTH POSITION (#) THE "C" DESIGNATES NON-COATED HAIRPINS
AND "T" DESIGNATES TIN-COATED HAIRPINS.
3. ALL DIMENSIONS ARE IN "INCHES" UNLESS NOTED.
SHIPPING WT
(LBS)
_C_NON-COATED
HAIRPINS
SHIPPING WT
(LBS)
_T_TIN-COATED
HAIRPINS
5/8"
36.0
38.5
SERIES
F
UNIT
CNPVP1814A#A
C
12 5/8"
10 1/16"
5 5/16"
12 1/2"
14 3/16"
CNPVP2414A#A
C
14 5/8"
12 1/16"
5 5/16"
12 1/2"
14 3/16"
5/8"
39.5
40.0
CNPVP2417A#A
C
14 5/8"
10 1/16"
3 9/16"
15 3/4"
17 1/2"
5/8"
39.5
42.5
CNPVP3014A#A
C
17"
13 5/8"
5 5/16"
12 1/2"
14 3/16"
3/4"
46.5
50.0
CNPVP3017A#A
C
17"
13 7/8"
3 9/16"
15 3/4"
17 1/2"
3/4"
47.0
49.5
CNPVP3617A#A
C
17"
13 7/8"
3 9/16"
15 3/4"
17 1/2"
3/4"
48.5
51.0
CNPVP3621A#A
C
17"
13 9/16"
3 9/16"
19 1/4"
3/4"
48.0
51.0
CNPVP4217A#A
C
13 7/8"
3 9/16"
15 3/4"
7/8"
52.0
55.0
CNPVP4221A#A
C
15 5/8"
3 9/16"
19 1/4"
7/8"
56.5
59.5
CNPVP4821A#A
C
22 1/16"
17 1/2"
3 9/16"
19 1/4"
7/8"
65.5
68.5
CNPVP4824A#A
C
22 1/16"
17 1/4"
3 9/16"
22 3/4"
24 1/2"
7/8"
62.0
65.0
CNPVP6024A#A
C
26 7/8"
17 15/16"
3 9/19"
22 3/4"
24 1/2"
7/8"
78.0
80.5
A
21 1/8"
19"
B
C
D
E
21"
17 1/2"
21"
21"
A - Aluminum
Hairpins
A12319
3
PERFORMANCE DATA (cont.)
COOLING CAPACITIES (MBH) -- R--410A REFRIGERANT
CNPV
INDOOR
UNIT
COIL AIR
SIZE CFM EWB
72 (22)
1050 67 (19)
62 (17)
4217
72 (22)
4221
1400 67 (19)
4224
62 (17)
T4221
72 (22)
1750 67 (19)
62 (17)
72 (22)
1050 67 (19)
62 (17)
72 (22)
4324 1400 67 (19)
62 (17)
72 (22)
1750 67 (19)
62 (17)
72 (22)
1200 67 (19)
62 (17)
72 (22)
4821
4824 1600 67 (19)
T4821
62 (17)
72 (22)
2000 67 (19)
62 (17)
72 (22)
1600 67 (19)
62 (17)
72 (22)
6024
T6024 2000 67 (19)
62 (17)
72 (22)
2400 67 (19)
62 (17)
72 (22)
1600 67 (19)
62 (17)
72 (22)
6124
2000 67 (19)
T6124
62 (17)
72 (22)
2400 67 (19)
62 (17)
30 (---1)
TC
SHC
74.40 36.30
62.30 37.60
51.40 38.60
90.20 43.80
75.80 46.00
62.60 47.70
103.00 50.00
86.70 53.10
71.70 55.70
96.72 47.64
80.93 49.26
66.64 50.56
117.07 57.30
98.18 60.23
81.03 62.70
133.38 65.28
112.09 69.50
92.72 73.26
79.30 38.70
66.60 40.20
55.00 41.30
96.00 46.60
80.90 49.20
67.00 51.20
109.40 53.10
92.40 56.70
76.70 59.70
103.20 50.40
86.40 52.10
71.20 53.30
120.70 58.70
101.20 61.30
83.40 63.20
135.60 65.80
113.90 69.30
94.10 72.10
146.13 71.69
122.06 74.12
100.28 76.03
169.63 82.84
142.02 86.75
116.90 89.93
189.44 92.42
158.99 97.85
131.10 102.40
Legend:
CFM --- Cubic Ft. per Minute
SHC --- Gross Sensible Capacity 1000 Btuh
See notes on following page.
BF
0.00
0.02
0.03
0.00
0.05
0.06
0.00
0.08
0.09
0.00
0.01
0.01
0.00
0.03
0.03
0.00
0.04
0.05
0.00
0.02
0.03
0.00
0.04
0.05
0.00
0.06
0.07
0.00
0.02
0.03
0.00
0.03
0.05
0.00
0.05
0.06
0.00
0.02
0.02
0.00
0.03
0.03
0.00
0.04
0.05
SATURATED TEMPERATURE LEAVING EVAPORATOR _F (_C)
35 (2)
40 (4)
45 (7)
TC
SHC
BF
TC
SHC
BF
TC
SHC
BF
68.10 33.10 0.00 61.20 29.70 0.00 53.50 26.20 0.01
56.00 34.20 0.03 48.90 30.60 0.03 41.20 27.00 0.03
44.90 35.00 0.03 37.90 31.40 0.03 30.60 27.80 0.04
82.60 40.10 0.00 74.10 36.20 0.01 64.70 32.00 0.04
68.00 42.00 0.05 59.40 37.70 0.06 50.00 33.40 0.06
54.70 43.50 0.06 46.20 39.20 0.06 37.50 35.00 0.07
94.30 46.00 0.00 84.60 41.50 0.05 73.90 36.80 0.06
77.80 48.60 0.08 68.00 43.90 0.08 57.10 39.00 0.08
62.70 50.90 0.09 53.10 46.20 0.09 43.40 41.50 0.10
89.31 43.85 0.00 80.91 39.78 0.00 71.39 35.44 0.00
73.30 45.20 0.01 64.67 40.88 0.01 54.97 36.34 0.01
58.77 46.28 0.01 50.10 41.84 0.01 40.70 37.29 0.02
108.20 53.03 0.00 98.03 48.31 0.01 86.74 43.33 0.02
89.03 55.55 0.03 78.69 50.55 0.03 66.93 45.19 0.03
71.60 57.72 0.03 61.25 52.56 0.03 50.15 47.21 0.03
123.30 60.58 0.02 111.98 55.48 0.03 99.21 50.01 0.04
101.79 64.41 0.05 90.14 58.95 0.05 76.76 52.99 0.05
82.16 67.85 0.05 70.58 62.18 0.05 58.38 56.24 0.06
72.90 35.40 0.00 65.70 31.90 0.00 57.70 28.20 0.00
60.00 36.60 0.02 52.70 32.90 0.02 44.60 29.10 0.02
48.30 37.60 0.03 40.90 33.80 0.03 33.10 30.00 0.03
88.30 42.90 0.00 79.60 38.90 0.00 69.90 34.50 0.03
72.90 45.00 0.04 64.10 40.70 0.05 54.20 36.10 0.05
58.80 46.80 0.05 49.90 42.30 0.05 40.70 37.90 0.05
100.70 49.10 0.00 90.90 44.60 0.03 79.90 39.80 0.05
83.40 52.20 0.07 73.30 47.40 0.07 62.00 42.20 0.07
67.50 54.90 0.08 57.40 49.90 0.08 47.20 44.90 0.08
94.40 45.90 0.00 84.80 41.10 0.00 74.10 36.30 0.00
77.50 47.20 0.02 67.80 42.30 0.02 57.10 37.20 0.03
62.20 48.30 0.03 52.40 43.30 0.03 42.30 38.30 0.03
110.40 53.60 0.00 99.00 48.20 0.00 86.40 42.50 0.02
90.70 55.70 0.04 79.20 50.00 0.04 66.60 44.10 0.04
72.80 57.40 0.05 61.40 51.60 0.05 49.70 46.00 0.05
124.10 60.30 0.00 111.20 54.40 0.01 97.00 48.00 0.04
102.10 63.20 0.06 89.10 56.90 0.06 74.80 50.30 0.06
82.10 65.70 0.06 69.30 59.30 0.06 56.40 53.00 0.07
134.50 65.77 0.00 121.56 59.54 0.00 106.83 52.86 0.00
110.18 67.82 0.02 96.85 61.17 0.02 81.83 54.15 0.02
88.07 69.40 0.02 74.72 62.59 0.02 60.46 55.67 0.02
156.39 76.39 0.00 141.33 69.41 0.01 124.36 61.86 0.02
128.36 79.72 0.03 112.89 72.20 0.03 95.38 64.18 0.03
102.76 82.43 0.03 87.41 74.75 0.03 71.17 66.88 0.04
174.81 85.58 0.00 158.22 77.98 0.02 139.30 69.76 0.03
143.83 90.25 0.04 126.61 82.05 0.04 107.02 73.24 0.05
115.46 94.29 0.05 98.49 85.91 0.05 80.79 77.29 0.06
EWB --- Entering Wet Bulb
BF --- Bypass Factor
LWB --- Leaving Wet Bulb
MBH --- 1000 Btuh
10
TC
45.00
32.80
24.40
54.40
39.60
30.70
62.00
45.20
36.30
60.74
43.99
32.63
73.81
53.54
41.46
84.49
61.46
49.33
48.80
35.70
26.30
59.10
43.30
33.30
67.50
49.50
39.50
62.40
45.40
33.50
72.60
52.80
40.30
81.30
59.20
46.50
90.32
64.91
48.56
105.10
75.60
58.57
117.75
84.86
67.60
50 (10)
SHC
22.60
23.30
24.40
27.60
28.90
30.70
32.00
33.90
36.30
30.89
31.53
32.63
37.96
39.46
41.46
44.04
46.55
49.33
24.40
25.10
26.30
30.00
31.40
33.30
34.70
36.90
39.50
31.20
32.10
33.50
36.70
38.10
40.30
41.50
43.60
46.50
45.83
46.78
48.56
53.83
55.70
58.57
60.94
63.87
67.60
BF
0.02
0.03
0.08
0.05
0.06
0.13
0.07
0.09
0.18
0.01
0.01
0.07
0.02
0.03
0.11
0.04
0.05
0.15
0.01
0.03
0.07
0.04
0.05
0.11
0.06
0.07
0.16
0.02
0.03
0.07
0.03
0.05
0.11
0.05
0.06
0.14
0.01
0.02
0.08
0.02
0.03
0.11
0.04
0.05
0.14
TC --- Gross Cooling Capacity 1000 Btuh
NOTES:
1. Contact manufacturer for cooling capacities at conditions other than shown in table.
2. Formulas:
Leaving db = entering db -- sensible heat cap.
1.09 x CFM
Leaving wb = wb corresponding to enthalpy of air leaving coil (hLWB)
hLWB = hEWB -- total capacity (Btuh)
4.5 x CFM
3.
4.
5.
6.
7.
8.
9.
10.
11.
Where hEWB = enthalpy of air entering coil
SHC is based on 80°F (27°C) db temperature of air entering the evaporator coil.
Below 80°F (27°C) db, subtract (Correction Factor x CFM) from SHC.
Above 80°F (27°C) db, add (Correction Factor x CFM) to SHC.
Direct interpolation is permissible. Do not extrapolate.
Fan motor heat has not been deducted.
All data points are based on 10°F (--12°C) superheat leaving coil and use of thermostatic expansion valve (TXV) device.
All units have sweat suction--tube connection and a liquid--tube connection. For 1--1/8--in. system suction tube, 3/4 x 1--1/8--in. suction
tube connection adapter is available as accessory.
The CNPVP, CNPVT and CNPVU coils can be used in any properly designed system using R--410A refrigerant.
The CNRVU coils can be used in any properly designed system using R--22 refrigerant.
Before using maximum cfm shown in table, check coil static pressure drop to ensure system blower can provide necessary static pressure needed for coil and duct systems.
Bypass Factor = 0 indicates no psychometric solution. Use bypass factor of next lower EWB for approximation.
BYPASS FACTOR
79 (26)
81 (27)
0.10
0.20
0.30
0.98
0.87
0.76
Interpolation is permissible.
Correction Factor = 1.09 x (1 --- BF) x (db --- 80)
ENTERING AIR DRY BULB TEMPERATURE _F (_C)
77 (25)
76 (24)
75 (24)
Under 75 (24)
83 (28)
84 (29)
84 (29)
Above 85 (29)
Correction Factor
1.96
2.94
3.92
4.91
1.74
2.62
3.49
4.36
Use formula shown below
1.53
2.29
3.05
3.82
78 (26)
82 (28)
11
PERFORMANCE DATA (cont.)
COOLING CAPACITIES (MBH) -- R--22 REFRIGERANT
CNRV
UNIT
SIZE
1814
2414
2417
3014
3017
3617
3621
4221
4224
4821
4824
6024
INDOOR
COIL
AIR
CFM EWB
72 (22)
450 67 (19)
62 (17)
72 (22)
600 67 (19)
62 (17)
72 (22)
750 67 (19)
62 (17)
72 (22)
600 67 (19)
62 (17)
72 (22)
800 67 (19)
62 (17)
72 (22)
1000 67 (19)
62 (17)
72 (22)
750 67 (19)
62 (17)
72 (22)
1000 67 (19)
62 (17)
72 (22)
1250 67 (19)
62 (17)
72 (22)
900 67 (19)
62 (17)
72 (22)
1200 67 (19)
62 (17)
72 (22)
1500 67 (19)
62 (17)
72 (22)
1050 67 (19)
62 (17)
72 (22)
1400 67 (19)
62 (17)
72 (22)
1750 67 (19)
62 (17)
72 (22)
1200 67 (19)
62 (17)
72 (22)
1600 67 (19)
62 (17)
72 (22)
2000 67 (19)
62 (17)
72 (22)
1600 67 (19)
62 (17)
72 (22)
2000 67 (19)
62 (17)
72 (22)
2400 67 (19)
62 (17)
SATURATED TEMPERATURE LEAVING EVAPORATOR _F (_C)
30 (---1)
TC
28.60
24.20
20.20
33.70
28.70
24.00
37.50
32.00
26.90
34.60
29.40
24.70
39.50
33.90
28.60
43.20
37.10
31.50
45.90
38.90
32.30
53.80
45.70
38.30
59.80
50.90
42.70
53.50
45.40
37.90
61.60
52.40
44.00
67.50
57.70
48.60
67.70
57.10
47.40
79.00
66.90
55.70
87.40
74.30
62.20
72.40
61.40
51.20
83.80
71.40
59.80
92.10
78.70
66.30
93.60
78.90
65.40
106.40
89.90
74.70
116.60
98.90
82.30
SHC
13.90
14.80
15.50
16.40
17.80
19.00
18.40
20.30
22.10
16.80
18.30
19.50
19.40
21.60
23.70
21.50
24.50
27.30
22.30
23.70
24.80
26.20
28.40
30.40
29.30
32.30
35.10
26.00
27.90
29.70
30.10
33.10
35.90
33.40
37.40
41.20
32.90
35.00
36.80
38.50
41.80
44.70
42.90
47.40
51.40
35.20
37.70
40.00
41.00
44.90
48.50
45.50
50.90
55.90
45.40
48.10
50.40
51.70
55.50
58.90
57.00
61.90
66.40
Legend:
CFM --- Cubic Ft. per Minute
SHC --- Gross Sensible Capacity 1000 Btuh
See notes previous page.
35 (2)
BF
0.00
0.01
0.01
0.00
0.02
0.02
0.01
0.03
0.03
0.00
0.01
0.02
0.01
0.03
0.03
0.03
0.05
0.05
0.00
0.02
0.02
0.00
0.03
0.04
0.03
0.06
0.06
0.00
0.03
0.03
0.02
0.05
0.06
0.06
0.08
0.08
0.00
0.03
0.03
0.00
0.05
0.06
0.04
0.08
0.09
0.00
0.02
0.03
0.00
0.04
0.05
0.04
0.07
0.07
0.00
0.02
0.03
0.00
0.04
0.04
0.00
0.06
0.06
TC
26.60
22.10
18.00
31.40
26.20
21.50
35.00
29.40
24.20
32.30
27.00
22.20
37.10
31.20
25.80
40.60
34.30
28.60
42.50
35.30
28.30
49.90
41.60
34.00
55.50
46.40
38.30
49.50
41.30
33.50
57.20
47.80
39.40
62.90
52.70
43.70
62.50
51.70
41.90
73.10
60.70
49.40
81.00
67.60
55.30
67.30
55.90
45.50
78.00
65.20
53.40
86.00
72.10
59.60
86.30
71.20
57.70
98.20
81.30
65.90
107.90
89.60
72.90
SHC
12.90
13.70
14.30
15.30
16.60
17.80
17.30
19.10
20.80
15.70
17.10
18.30
18.40
20.40
22.30
20.50
23.20
25.90
20.60
21.90
22.80
24.40
26.40
28.20
27.40
30.20
32.90
24.10
25.90
27.40
28.20
30.90
33.60
31.40
35.10
38.80
30.40
32.20
33.90
35.80
38.70
41.50
40.10
44.20
48.10
32.70
35.00
37.00
38.40
42.00
45.30
42.90
47.80
52.60
41.90
44.20
46.30
47.90
51.30
54.40
53.00
57.50
61.70
EWB --- Entering Wet Bulb
BF --- Bypass Factor
40 (4)
BF
0.00
0.01
0.01
0.00
0.02
0.02
0.01
0.03
0.04
0.00
0.01
0.02
0.01
0.03
0.03
0.04
0.05
0.05
0.00
0.02
0.02
0.01
0.04
0.04
0.04
0.06
0.06
0.00
0.03
0.03
0.03
0.05
0.06
0.06
0.08
0.09
0.00
0.03
0.03
0.02
0.05
0.06
0.06
0.08
0.09
0.00
0.02
0.03
0.02
0.04
0.05
0.05
0.07
0.07
0.00
0.02
0.03
0.00
0.04
0.04
0.03
0.06
0.06
TC
24.20
19.70
15.40
28.70
23.40
18.60
32.10
26.20
21.10
29.60
24.20
19.30
34.20
28.00
22.60
37.50
30.90
25.30
38.60
31.00
24.00
45.40
37.00
29.00
50.60
41.30
33.10
45.10
36.60
28.50
52.10
42.50
34.00
57.40
46.90
38.30
56.50
45.60
35.70
66.20
53.50
42.60
73.60
59.70
47.90
61.20
49.50
39.20
71.30
58.00
46.30
78.70
64.30
52.10
77.90
62.70
49.20
88.80
71.50
56.60
97.70
78.90
62.70
SHC
11.80
12.50
13.00
14.10
15.30
16.40
16.00
17.70
19.30
14.60
15.70
16.80
17.10
19.00
20.80
19.20
21.80
24.30
18.80
19.80
20.60
22.40
24.20
25.80
25.30
27.80
30.30
22.10
23.70
24.90
26.00
28.50
30.90
29.10
32.60
36.10
27.60
29.30
30.80
32.80
35.40
38.10
37.00
40.60
44.50
30.00
32.00
33.90
35.40
38.70
41.90
39.80
44.40
48.90
38.00
40.10
42.00
43.70
46.70
49.70
48.50
52.50
56.70
45 (7)
BF
0.00
0.01
0.01
0.00
0.02
0.02
0.02
0.03
0.04
0.00
0.01
0.02
0.02
0.03
0.04
0.04
0.05
0.06
0.00
0.02
0.02
0.02
0.04
0.04
0.04
0.06
0.07
0.01
0.03
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.00
0.03
0.03
0.04
0.06
0.06
0.07
0.08
0.09
0.00
0.02
0.03
0.03
0.05
0.05
0.05
0.07
0.08
0.00
0.02
0.03
0.02
0.04
0.05
0.04
0.06
0.07
LWB --- Leaving Wet Bulb
MBH --- 1000 Btuh
12
TC
21.60
16.80
12.50
25.60
20.10
15.40
28.70
22.60
17.90
26.50
20.90
16.00
30.70
24.30
19.30
33.80
26.80
22.30
34.10
26.00
19.30
40.30
31.20
23.80
44.80
35.40
27.70
40.00
30.70
23.20
46.20
36.30
28.30
50.80
40.30
32.90
49.70
38.80
28.90
58.30
45.50
35.40
64.90
50.60
40.70
54.20
42.40
32.20
63.30
49.50
39.00
70.10
55.10
44.90
68.30
53.20
39.60
78.00
60.60
46.50
85.90
66.60
52.60
SHC
10.60
11.20
11.70
12.80
13.80
14.80
14.60
16.10
17.70
13.20
14.30
15.30
15.70
17.40
19.10
17.70
20.10
22.30
16.80
17.50
18.30
20.20
21.70
23.20
22.90
25.30
27.50
19.90
21.10
22.30
23.50
25.80
28.00
26.50
29.80
32.90
24.70
26.20
27.50
29.40
31.90
34.50
33.40
36.70
40.70
27.00
28.80
30.50
32.10
35.00
38.30
36.40
40.40
44.90
33.80
35.70
37.40
39.10
41.80
44.80
43.60
47.20
51.60
50 (10)
BF
0.00
0.01
0.01
0.01
0.02
0.03
0.02
0.03
0.05
0.00
0.01
0.02
0.02
0.03
0.05
0.04
0.05
0.11
0.01
0.02
0.03
0.03
0.04
0.06
0.05
0.06
0.09
0.02
0.03
0.05
0.04
0.06
0.08
0.07
0.08
0.13
0.02
0.03
0.04
0.04
0.06
0.08
0.07
0.08
0.11
0.01
0.02
0.03
0.03
0.05
0.07
0.06
0.07
0.11
0.01
0.03
0.04
0.03
0.04
0.06
0.05
0.06
0.08
TC
18.60
13.50
10.20
22.00
16.30
13.00
24.60
18.60
15.40
22.90
17.10
13.40
26.60
20.10
16.80
29.30
22.20
19.60
28.60
20.30
15.90
34.30
24.40
20.00
38.40
27.90
23.70
33.80
24.00
19.30
39.60
28.60
24.10
43.60
32.20
28.30
42.30
30.30
23.80
49.30
36.30
29.90
54.80
40.90
35.20
46.30
34.10
26.70
54.00
40.30
33.40
60.00
44.90
39.20
58.00
41.70
32.50
65.80
48.30
38.90
72.30
53.70
44.70
SHC
9.40
9.70
10.20
11.40
12.20
13.00
13.00
14.40
15.40
11.80
12.60
13.40
14.10
15.60
16.80
16.00
18.20
19.60
14.60
15.10
15.90
17.80
18.80
20.00
20.40
22.20
23.70
17.40
18.30
19.30
20.90
22.60
24.10
23.70
26.50
28.30
21.60
22.60
23.80
25.90
28.10
29.90
29.50
32.80
35.20
23.70
25.20
26.70
28.50
31.20
33.40
32.50
36.30
39.20
29.60
30.80
32.50
34.10
36.60
38.90
38.20
41.80
44.70
BF
0.00
0.01
0.08
0.01
0.02
0.12
0.03
0.03
0.16
0.01
0.02
0.10
0.02
0.03
0.16
0.04
0.05
0.21
0.01
0.02
0.12
0.03
0.04
0.16
0.05
0.06
0.21
0.02
0.03
0.15
0.05
0.06
0.20
0.08
0.09
0.25
0.02
0.03
0.13
0.05
0.06
0.18
0.08
0.09
0.23
0.02
0.03
0.12
0.04
0.05
0.17
0.06
0.07
0.22
0.02
0.03
0.12
0.03
0.04
0.16
0.05
0.06
0.19
TC --- Gross Cooling Capacity 1000 Btuh
PERFORMANCE DATA (cont.)
COIL STATIC PRESSURE DROP (in. w.c.) R--410A and R--22 REFRIGERANTS
UNIT
SIZE
1814
400
500
600
700
800
0.078 0.114 0.156 0.198 0.253
900
Standard CFM
1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200
Dry
0.096 0.138 0.183 0.213 0.277
1917
0.042 0.060 0.080 0.102 0.128
0.055 0.076 0.104 0.127 0.158
2414
0.070 0.103 0.143 0.182 0.233 0.290 0.354
0.089 0.128 0.171 0.214 0.269 0.336 0.413
2417
0.048 0.068 0.090 0.112 0.140 0.170 0.203
0.064 0.091 0.122 0.150 0.188 0.224 0.263
3014
0.065 0.097 0.135 0.173 0.223 0.278 0.339 0.405 0.478
0.078 0.114 0.160 0.206 0.260 0.321 0.388 0.461 0.540
3017
0.042 0.060 0.080 0.102 0.128 0.157 0.188 0.222 0.259
0.055 0.076 0.104 0.127 0.158 0.190 0.225 0.266 0.309
3117
0.031 0.046 0.063 0.083 0.105 0.130 0.156 0.193 0.230
0.039 0.056 0.075 0.097 0.121 0.149 0.179 0.212 0.249
Wet
Dry
Wet
Dry
Wet
Dry
Wet
Dry
Wet
Dry
Wet
Dry
Wet
Dry
3617 0.043 0.061 0.082 0.103 0.128 0.157 0.189 0.221 0.259 0.299 0.341
T3617
Wet
0.056 0.079 0.107 0.133 0.166 0.200 0.236 0.276 0.315 0.361 0.413
Dry
0.035 0.048 0.062 0.076 0.093 0.111 0.132 0.153 0.177 0.201 0.228
3621
Wet
0.049 0.066 0.085 0.100 0.122 0.144 0.171 0.192 0.217 0.245 0.276
Dry
0.025 0.038 0.054 0.072 0.093 0.117 0.143 0.171 0.205 0.233 0.273
3717
Wet
0.030 0.044 0.061 0.079 0.103 0.125 0.154 0.182 0.216 0.251 0.288
Dry
0.072 0.093 0.118 0.145 0.175 0.206 0.243 0.281 0.322
4217
Wet
0.079 0.102 0.130 0.159 0.192 0.228 0.26 0.303 0.348
Dry
4221 0.030 0.041 0.054 0.066 0.082 0.099 0.118 0.137 0.158 0.180 0.205
T4221
Wet
0.043 0.059 0.078 0.101 0.126 0.153 0.181 0.207 0.234 0.260 0.288
Dry
0.053 0.062 0.073 0.084 0.097 0.111 0.126 0.138
4324
Wet
0.067 0.082 0.096 0.112 0.129 0.145 0.163 0.171
Dry
0.047 0.060 0.075 0.092 0.110 0.130 0.152 0.176 0.204
4821
T4821
Wet
0.053 0.067 0.085 0.104 0.125 0.147 0.172 0.200 0.228
Dry
0.015 0.046 0.057 0.069 0.094 0.100 0.119 0.124 0.140
4824
Wet
0.032 0.050 0.066 0.081 0.097 0.114 0.131 0.150 0.169
Dry
0.062 0.073 0.084 0.097 0.111 0.126 0.138
6024
T6024
Wet
0.082 0.096 0.112 0.129 0.145 0.163 0.171
Dry
0.130
6124
T6124
Wet
0.150
13
0.366 0.413
0.396 0.446
0.231 0.259
0.319 0.354
0.154 0.172 0.190 0.210
0.191 0.212 0.235 0.258
0.230 0.256 0.284 0.318
0.259 0.292 0.327 0.365
0.158 0.175 0.195 0.214
0.190 0.211 0.233 0.257
0.154 0.172 0.190 0.210 0.228 0.251 0.273 0.293
0.191 0.212 0.235 0.258 0.283 0.310 0.336 0.366
0.140 0.160 0.180 0.200 0.220 0.240 0.270 0.290
0.170 0.190 0.210 0.230 0.260 0.290 0.310 0.340
Venstar Programmable Thermostat
T2900
STANDARD FEATURES:
• Up to 3-Occupied, 1-Unoccupied periods per day, with copy command for easy programming
• Light Activated occupied period (defeatable)
• Accepts humidification/dehumidification control module (Venstar part number ACC0430)
• Auto changeover, 3-stage heat, 2-stage cool for use with gas/electric, heat pump, electric & hydronic heat
• Configurable for manual changeover, also configurable programmable or non-programmable
• Adjustable deadbands and timers
• Control to, or monitor a second remote sensor
• Can average up to 8 (wired or wireless) remote sensors
• 3 configurable outputs for maximum flexibility (MISC1, MISC2, MISC3)
• Extra 6th and 7th outputs (beyond our standard thermostat)
• Programmable output (control by time, temperature or internet/phone control)
• Energy Watch keeps Track of energy use by tracking heating and cooling hours
• Smart Fan (keeps the fan from running during unoccupied periods)
• Smart recovery
• Pre-occupancy fan purge
• Display shows both heating an cooling setpoints and room temperature simultaneously
• All programming and setpoints stored in non-volatile memory, and are never lost in power failure
• Service filter and service UV lamp indicators
• Red/Green LED shows whether thermostat is calling for heating or cooling
• 5-minute compressor time guard and adjustable cycle limit, both defeatable for servicing equipment
• Outdoor sensor ready with high and low temperature of the day
• Thermoglow backlit electro-luminous display and backlit color coded keys and legends
• Accepts accessory IR Remote Control system (Venstar part number ACC0431)
• Accepts accessory EZ Programmer (Venstar part number ACC0432)
• For accessory locking cover use (Venstar part number ACC0620)
MODEL:
JOB NAME:
LOCATION:
BUYER:
ENGINEER:
T2900
QUANTITY:
DATE:
BUYER P.O.#:
Submittal Cover Sheet
Date Submitted:
May 19, 2015
Date Due Back:
May 26, 2015
RK Submittal No.:
235700.00 - 0
Specification Section:
23 57 00 - Coils and Heat Exchangers
Project Name:
Poudre Valley Health - UCH & FMC Renovation
1025 Garfield Street
General Contractor:
GH Phipps Construction Company
5995 Greenwood Plaza Blvd., Suite 100
Greenwood Village, CO 80111
Mechanical Contractor:
RK Mechanical, Inc.
3800 Xanthia Street
Denver, CO 80238
Subcontractor/Supplier:
RK Mechanical, Inc.
3800 Xanthia Street
Denver, CO 80238
ITEM
COPIES
REV
4
1
0
SUBMITTAL DESCRIPTION
DRAWING
MANUFACTURER
CU-1,2
3800 Xanthia Street
Denver, Colorado 80238
ph: 303.355.9696
fx: 303.355.8666
www.rkmi.com
TAG
CU-2,3
Model
24ABC648A003
Qty
2
Voltage
208-1-60
4800 OSAGE STREET
DENVER, COLORADO 80221
PHONE: (303) 825-4328
WWW.LOHMILLER.COM
FAX: (303) 820-2302
24ABC6
Comfortt16 Air Conditioner
with Puronr Refrigerant
1---1/2 to 5 Nominal Tons
Product Data
INDUSTRY LEADING
FEATURES / BENEFITS
Efficiency
S 14 -- 16.5 SEER/11.0-- 13.5 EER
S Microtube Technologyt refrigeration system
S Indoor air quality accessories available
Sound
S Sound level as low as 76 dBA
S Sound level as low as 74 dBA with accessory sound
blanket
Comfort
S System supports Edger Thermidistatt or standard
thermostat controls
Reliability
S Puronr refrigerant -- environmentally sound, won’t
deplete the ozone layer and low lifetime servce cost.
Carrier’s Air Conditioners with Puronr refrigerant provide a
collection of features unmatched by any other family of
equipment. The 24ABC has been designed utilizing Carrier’s
Puron refrigerant. The environmentally sound refrigerant allows
you to make a responsible decision in the protection of the earth’s
ozone layer.
This product has been designed and manufactured to meet
Energy Starr criteria for energy efficiency when matched with
appropriate coil components. Refer to the combination ratings in
the Product Data for system combinations that meet Energy Starr
guidelines.
NOTE: Ratings contained in this document are subject to
change at any time. Always refer to the AHRI directory
(www.ahridirectory.org) for the most up--to--date ratings
information.
S Scroll compressor
S Internal pressure relief valve
S Internal thermal overload
S Filter drier
S Balanced refrigeration system for maximum reliability
Durability
WeatherArmort protection package:
S Solid, durable sheet metal construction
S Dense wire coil guard standard
S Baked--on, complete outer coverage, powder paint
Applications
S Long--line -- up to 250 feet (76.20 m) total equivalent
length, up to 200 feet (60.96 m) condenser above
evaporator, or up to 80 ft. (24.38 m) evaporator above
condenser (See Longline Guide for more information.)
S
Low ambient
accessory kit
(down
to
--20_F/--28.9_C)) with
MODEL NUMBER NOMENCLATURE
1
N
2
N
3
A
4
A
5
A/N
6
N
7
N
8
N
9
A/N
10
A/N
11
A/N
12
N
13
N
2
4
A
B
C
6
3
6
A
0
0
3
0
Product
Series
Product
Family
Tier
Major
Series
SEER
Grille
Variations
Open
Open
Voltage
Series
24=AC
A=RES AC
B=Comfort
C=Puron
6=16 SEER
A = Dense
W = Standard
0=Not
Defined
0=Not
Defined
3=208/230 ---1
Cooling
Capacity
Use of the AHRI Certified
TM Mark indicates a
manufacturer’s
participation in the
program For verification
of certification for individual
products, go to
www.ahridirectory.org.
0=
Original
Series
This product has been designed and manufactured to meet
Energy Star criteria for energy efficiency when matched
with appropriate coil components. However, proper
refrigerant charge and proper air flow are critical to achieve
rated capacity and efficiency. Installation of this product
should follow all manufacturing refrigerant charging and air
flow instructions. Failure to confirm proper charge and
air flow may reduce energy efficiency and shorten
equipment life.
CU-5,2,3
CU-6
STANDARD FEATURES
Feature
18
24
30
36
42
48 / 49
Puron Refrigerant
X
X
X
X
X
X
60 / 61
X
Maximum SEER *
16.0
16.0
16.5
16.5
16.0
16.0
16.0
Scroll Compressor
X
X
X
X
X
X
X
Field Installed Filter Drier
X
X
X
X
X
X
X
Front Seating Service Valves
X
X
X
X
X
X
X
Internal Pressure Relief Valve
X
X
X
X
X
X
X
Internal Thermal Overload
X
X
X
X
X
X
X
Long Line capability
X
X
X
X
X
X
X
Low Ambient capability with Kit
X
X
X
X
X
X
X
Dense Grille
X
X
X
X
X
X
X
49--- 30
60--- 30
61--- 30
9.00
(4.08)
14.50
(6.58)
14.50
(6.58)
* With approved combinations
X = Standard
PHYSICAL DATA
UNIT SIZE --- VOLTAGE, SERIES
Compressor Type
REFRIGERANT
Control
Charge lb (kg)
18--- 31
24--- 30
30--- 30
4.60
(2.09)
6.00
(2.72)
6.81
(3.09)
36--- 30
42--- 30
48--- 31
Scroll
Puron (R---410A)
TXV (Puron Hard Shutoff)
6.75
8.62
13.0
(3.06)
(3.91)
(5.90)
Propeller Type, Direct Drive
Vertical
3223
3810
4046
1/12
1/5
1/4
800
800
800
COND FAN
Air Discharge
Vertical
Air Qty (CFM)
1881
2614
2614
4046
4046
4046
Motor HP
1/12
1/10
1/10
1/4
1/4
1/4
Motor RPM
1100
1100
1100
800
800
800
COND COIL
Face Area (Sq ft)
11.50
15.10
17.20
17.60
25.15
25.15
25.15
30.15
30.15
Fins per In.
25
25
25
25
25
20
20
20
20
Rows
1
1
1
1
1
2
1
2
2
Circuits
3
4
4
4
6
7
7
8
8
VALVE CONNECT. (In. ID)
Vapor
3/4
3/4
3/4
7/8
7/8
7/8
7/8
7/8
7/8
Liquid
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
REFRIGERANT TUBES (In. OD)
Rated Vapor*
3/4
7/8
1 ---1/8
Max Liquid Line {
3/8
* Units are rated with 25 ft (7.6 m) of lineset length. See Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of lineset.
Note: See unit Installation Instruction for proper installation.
{ See Liquid Line Sizing For Cooling Only Systems with Puron Refrigerant tables.
2
ACCESSORY THERMOSTATS
PART NUMBER
PROGRAM
TC --- PAC01
TC --- NAC01
TCSNAC01
5--- 2 Day
NP
NP
PART NUMBER
TSTATXXCNV10‡
TX--- LBP01
TX--- MBP01
GAS
Comfort
√
√
√
ELECTRIC
HEAT PUMP
HEAT
COOL
1
1
1
1
1
1
√
√
√
THERMOSTAT ACCESSORIES
DESCRIPTION
Thermostat Conversion Kit (4 to 5 wire) --- 10 pack
Large Decorative Backplate
Medium Decorative Backplate
THERMOSTATS USED WITH
All Carrier branded thermostats
TP--- Pxx, TP--- Nxx, TC --- Pxx
TC --- Nxx, TB--- Pxx
ACCESSORIES
KIT NUMBER
DESCRIPTION
Unit Sizes --- Series
48--- 31
49--- 30
60--- 30
61--- 30
MOTOR FAN BALL BEARING
X
X
X
X
KAACH1201AAA
CRANKCASE HEATER
X
X
KAACH1601AAA
CRANKCASE HEATER
S
S
KAACH1701AAA
CRANKCASE HEATER
X
X
X
X
KAACS0201PTC
START ASSIST PTC
X
X
X
X
X
X
X
X
X
KAAFT0101AAA
FREEZE THERMOSTAT
X
X
X
X
X
X
X
X
X
KAAHI0501PUR
PRESSURE SWITCH
X
X
X
X
X
X
X
X
X
KAALP0401PUR
PRESSURE SWITCH
X
X
X
X
X
X
X
X
X
KAALS0201LLS
LIQUID LINE SOLENOID
X
X
X
X
X
X
X
X
X
KAATD0101TDR
TIME DELAY RELAY
X
X
X
X
X
X
X
X
X
KAAWS0101AAA
WINTER START KIT
X
X
X
X
X
X
X
X
X
KSACY0101AAA
CYCLE PROTECTOR
X
X
X
X
X
X
X
X
X
KSAHS1701AAA
HARD START (CAP/RELAY)
X
X
X
X
X
X
X
X
X
KSALA0301410
LOW AMBIENT KIT
X
X
X
X
X
X
X
X
X
KSALA0601AAA†
MOTORMASTER 230V
X
X
X
X
X
X
X
X
X
KSASF0101AAA
SUPPORT FEET
X
X
X
X
X
X
X
X
KSASF0201AAA
SUPPORT FEET
X
KSASH0601COP
SOUND BLKT KIT
X
X
X
X
X
X
KSASH2101COP
SOUND BLKT KIT
X
X
KSATX0201PUR
TXV PURON HSO
KSATX0301PUR
TXV PURON HSO
KSATX0401PUR
TXV PURON HSO
KSATX0501PUR
TXV PURON HSO
X
X
KSBTX0201PUR
TXV PURON HSO
KSBTX0301PUR
TXV PURON HSO
KSBTX0401PUR
TXV PURON HSO
HC32GE229
MOTOR FAN BALL BEARING
HC32GE234
MOTOR FAN BALL BEARING
HC34GE240
MOTOR FAN BALL BEARING
HC38GE228
MOTOR FAN BALL BEARING
HC40GE228
18--- 31
24--- 30
30--- 30
36--- 30
42--- 30
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
{ Required accessories include ball bearing fan motor, compressor start assist (CAP / Relay), crankcase heater, evaporator freeze stat, hard shut---off TXV.
X = Accessory / S --- Standard
5
ACCESSORY USAGE GUIDELINE
ACCESSORY
Ball Bearing Fan Motor
Compressor Start Assist Capacitor and Relay
Crankcase Heater
Evaporator Freeze Thermostat
Hard Shut---Off TXV
Liquid Line Solenoid Valve
Motor Master Control or
Low---ambient Pressure Switch
Support Feet
Winter Start Control
Yes{
Yes
Yes
Yes
Yes
No
REQUIRED FOR LONG
LINE
APPLICATIONS*
(Over 80 ft./24.38 m)
No
Yes
Yes
No
Yes
No
REQUIRED FOR
SEA COAST
APPLICATIONS
(Within 2 miles/3.22 km)
No
No
No
No
Yes
No
Yes
No
No
Recommended
Yes
No
No
Recommended
No
REQUIRED FOR LOW---AMBIENT COOLING APPLICATIONS
(Below 55F/12.8_C)
* For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 20 ft. (6.09 m) vertical differential, refer to Residential Split---System Longline
Application Guideline.
{ Required for Low---Ambient Controller (full modulation feature) MotorMasterr Control.
Accessory Description and Usage (Listed Alphabetically)
1. Ball--Bearing Fan Motor
A fan motor with ball bearings which permits speed reduction
while maintaining bearing lubrication.
Usage Guideline:
Required on all units when MotorMasterr is used.
2. Compressor Start Assist -- Capacitor and Relay
Start capacitor and relay gives a ”hard” boost to compressor
motor at each start up.
Usage Guideline:
Required for reciprocating compressors in the
following applications:
Long line
Low ambient cooling
Hard shut off expansion valve on indoor coil
Liquid line solenoid on indoor coil
Required for single--phase scroll compressors in the
following applications:
Long line
Low ambient cooling
Suggested for all compressors in areas with a history of
low voltage problems.
3. Compressor Start Assist — PTC Type
Solid state electrical device which gives a ”soft” boost to the
compressor at each start--up.
Usage Guideline:
Suggested in installations with marginal power supply.
4. Crankcase Heater
An electric resistance heater which mounts to the base of the
compressor to keep the lubricant warm during off cycles.
Improves compressor lubrication on restart and minimizes the
chance of liquid slugging.
Usage Guideline:
Required in low ambient cooling applications.
Required in long line applications.
Suggested in all commercial applications.
5. Cycle Protector
The cycle protector is designed to prevent compressor short
cycling. This control provides an approximate 5--minute delay
after power to the compressor has been interrupted for any
reason, including power outage, protector control trip, thermostat
jiggling, or normal cycling.
6. Evaporator Freeze Thermostat
An SPST temperature--actuated switch that stops unit operation
when evaporator reaches freeze--up conditions.
Usage Guideline:
Required when low ambient kit has been added.
7. Low--Ambient Pressure Switch Kit
A long life pressure switch which is mounted to outdoor unit
service valve. It is designed to cycle the outdoor fan motor in
order to maintain head pressure within normal operating limits
(approximately 100 psig to 225 psig). The control will maintain
working head pressure at low--ambient temperatures down to 0_F
(--18_C) when properly installed.
Usage Guideline:
A Low--Ambient Pressure Switch or MotorMasterr
Low--Ambient Controller must be used when cooling operation is
used at outdoor temperatures below 55_F (12.8_C).
8. MotorMasterr Low--Ambient Controller
A fan--speed control device activated by a temperature sensor,
designed to control condenser fan motor speed in response to the
saturated, condensing temperature during operation in cooling
mode only. For outdoor temperatures down to --20_F (--28.9_C),
it maintains condensing temperature at 100_F 10_F (37.8_C 
5.5_C).
Usage Guideline:
A MotorMasterr Low Ambient Controller or
Low--Ambient Pressure Switch must be used when
cooling operation is used at outdoor temperatures
below 55_F (12.8_C).
Suggested for all commercial applications.
9. Outdoor Air Temperature Sensor
Designed for use with Carrier Thermostats listed in this
publication. This device enables the thermostat to display the
outdoor temperature. This device also
is required to enable special thermostat features such as auxiliary
heat lock out.
Usage Guideline:
Suggested for all Carrier thermostats listed in this
publication.
6
Accessory Description and Usage (Listed Alphabetically) (Continued)
13. Time--Delay Relay
An SPST delay relay which briefly continues operation of indoor
blower motor to provide additional cooling after the compressor
cycles off.
NOTE: Most indoor unit controls include this feature. For those
that do not, use the guideline below.
Usage Guideline:
For improved efficiency ratings for certain
combinations of indoor and outdoor units. Refer to
AHRI Unitary Directory.
14. Winter Start Control
This control is designed to alleviate nuisance opening of the
low--pressure switch by bypassing it for the first 3 minutes of
operation.
10. Sound Hood
Wraparound sound reducing cover for the compressor. Reduces
the sound level by about 2 dBA.
Usage Guideline:
Suggested when unit is installed closer than 15 ft (4.57 m) to
quiet areas, bedrooms, etc.
Suggested when unit is installed between two houses less
than 10 ft (3.05 m) apart.
11. Support Feet
Four stick--on plastic feet that raise the unit 4 in. (101.6 mm)
above the mounting pad. This allows sand, dirt, and other debris
to be flushed from the unit base, minimizing corrosion.
Usage Guideline:
Suggested in the following applications:
Coastal installations.
Windy areas or where debris is normally circulating.
Rooftop installations.
For improved sound ratings.
12. Thermostatic Expansion Valve (TXV)
A modulating flow--control valve which meters refrigerant liquid
flow rate into the evaporator in response to the superheat of the
refrigerant gas leaving the evaporator.
Kit includes valve, adapter tubes, and external equalizer tube.
Hard shut off types are available.
NOTE: When using a hard shut off TXV with single phase
reciprocating compressors, a Compressor Start Assist Capacitor
and Relay is required.
Usage Guideline:
Required to achieve AHRI ratings in certain equipment
combinations. Refer to combination ratings.
Hard shut off TXV or LLS required in air conditioner
long line applications.
Required for use on all zoning systems.
7
ELECTRICAL DATA
UNIT SIZE
OPER VOLTS*
V/PH
MCA
MAX FUSE** or
CKT BRK
AMPS
LRA
RLA
FLA
48.0
9.0
0.50
11.8
20
24--- 30
58.3
13.5
0.75
17.7
30
30--- 30
64.0
12.8
0.75
16.8
25
36--- 30
77.0
14.1
0.50
18.1
30
112.0
17.9
1.20
23.6
40
48--- 31
109.0
19.9
1.20
26.1
40
49--- 30
117.0
21.8
1.20
28.4
40
60--- 30
135.0
21.4
1.20
28.0
40
208/230/1 ---60
MIN
FAN
18--- 31
42--- 30
MAX
COMPR
253
197
61--- 30
134.0
25.0
1.20
32.5
* Permissible limits of the voltage range at which the unit will operate satisfactorily
** Time ---Delay fuse.
FLA --- Full Load Amps
LRA --- Locked Rotor Amps
MCA --- Minimum Circuit Amps
RLA --- Rated Load Amps
NOTE: Control circuit is 24 ---V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
All motors/compressors contain internal overload protection.
Complies with 2007 requirements of ASHRAE Standards 90.1
50
A--WEIGHTED SOUND POWER LEVEL (dBA)
Unit Size --Voltage, Series
Standard
Rating (dBA)
018--- 31
024--- 30
030--- 30
036--- 30
042--- 30
048--- 31
049--- 30
060--- 30
061--- 30
76
76
76
76
78
78
78
78
78
125
52.5
57.5
55.0
50.5
52.5
57.5
51.5
55.0
56.5
TYPICAL OCTAVE BAND SPECTRUM (dBA without tone adjustment)
250
500
1000
2000
4000
59.0
65.5
70.5
64.5
59.0
64.0
69.0
71.0
69.0
64.5
63.5
68.0
69.5
67.0
63.5
59.5
64.5
70.5
62.0
59.5
62.0
66.0
73.5
68.0
62.0
61.5
66.0
70.5
65.5
59.5
62.0
67.5
73.5
69.0
64.5
62.5
67.5
70.5
65.0
61.0
63.0
65.5
69.0
67.0
61.5
8000
54.5
60.0
58.5
54.5
55.5
53.5
62.0
53.5
56.0
NOTE: Tested in accordance with AHRI Standard 270 ---08 (not listed in AHRI).
A--WEIGHTED SOUND POWER LEVEL (dBA) WITH SOUND SHIELD
Unit Size --Voltage, Series
Standard
Rating (dBA)
018--- 31
024--- 30
030--- 30
036--- 30
042--- 30
048--- 31
049--- 30
060--- 30
061--- 30
74
75
75
74
76
76
76
75
75
125
55.5
58.0
55.5
51.5
53.0
58.5
53.0
56.5
57.0
TYPICAL OCTAVE BAND SPECTRUM (dBA without tone adjustment)
250
500
1000
2000
4000
59.0
65.0
68.5
63.5
58.0
64.0
69.0
70.5
68.5
64.5
63.0
68.0
69.0
67.0
63.0
58.5
62.0
65.0
61.0
58.0
62.0
65.5
72.0
65.0
61.0
61.5
66.0
69.0
64.0
58.5
61.5
67.5
72.0
68.0
61.5
62.5
66.5
68.0
63.0
59.5
63.0
65.5
67.0
65.5
59.0
NOTE: Tested in accordance with AHRI Standard 270 ---08 (not listed in AHRI).
CHARGING SUBCOOLING (TXV--TYPE EXPANSION DEVICE)
UNIT SIZE --- VOLTAGE, SERIES
18--- 31
24--- 30
30--- 30
36--- 30
42--- 30
48--- 31
49--- 30
60--- 30
61--- 30
REQUIRED SUBCOOLING _F (_C)
10 (5.6)
10 (5.6)
10 (5.6)
10 (5.6)
9 (5.0)
8 (4.4)
8 (4.4)
9 (5.0)
9 (5.0)
8
8000
52.0
59.5
58.5
52.0
54.0
51.0
59.0
51.5
52.5
9
DIMENSIONS -- ENGLISH
11
24”
(609.6)
Service
12”
(304.8)
Note: Numbers in ( ) = mm
18”
(457.2)
24”
(609.6)
Service
Wall
6”
(152.4)
18”
(457.2)
12”
(304.8)
24”
(609.6)
Service
Wall
18”
(457.2)
12”
(304.8)
Clearances (various examples)
24”
(609.6)
Service
12”
(304.8)
24”
(609.6)
Service
Wall
6”
(152.4)
IMPORTANT: When installing multiple units in an alcove, roof well, or partially enclosed area, ensure there is adequate ventilation to prevent re--circulation of discharge air.
CLEARANCES
Wall
CONDENSER ONLY RATINGS CONTINUED
SST
° F (° C)
30
(-1.11)
35
(1.67)
40
(4.44)
45
(7.22)
50
(10.0)
55
(12.78)
30
(-1.11)
35
(1.67)
40
(4.44)
45
(7.22)
50
(10.0)
55
(12.78)
30
(-1.11)
35
(1.67)
40
(4.44)
45
(7.22)
50
(10.0)
55
(12.78)
30
(-1.11)
35
(1.67)
40
(4.44)
45
(7.22)
50
(10.0)
55
(12.78)
55 (12.78)
65 (18.33)
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
37.90
69.80
1.83
41.90
71.20
1.84
46.10
72.70
1.85
50.70
74.20
1.86
55.50
75.80
1.87
60.70
77.40
1.89
36.20
79.20
2.03
40.00
80.60
2.04
44.00
81.90
2.05
48.30
83.30
2.07
52.90
84.80
2.09
57.70
86.40
2.11
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
40.80
67.20
1.98
45.10
68.50
1.91
49.90
69.80
1.80
55.00
71.20
1.65
60.70
72.60
1.46
66.80
74.20
1.22
38.60
76.60
2.28
42.70
77.80
2.24
47.10
79.00
2.16
52.00
80.30
2.05
57.30
81.70
1.90
63.00
83.10
1.72
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
45.00
70.30
2.04
49.80
71.70
1.99
54.90
73.20
1.93
60.40
74.80
1.86
66.20
76.40
1.78
72.40
78.20
1.68
42.40
79.50
2.41
46.80
80.90
2.39
51.50
82.40
2.36
56.60
83.90
2.33
62.00
85.50
2.28
67.70
87.10
2.23
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
TCG
SDT
KW
49.90
70.90
2.31
55.30
72.50
2.31
61.00
74.10
2.31
67.20
75.80
2.31
73.70
77.60
2.31
80.80
79.50
2.31
47.50
80.40
2.60
52.60
81.80
2.61
58.00
83.40
2.63
63.80
84.90
2.64
70.00
86.60
2.65
76.60
88.40
2.66
CONDENSER ENTERING AIR TEMPERATURES ° F (° C)
75 (23.89)
85 (29.44)
95 (35.0)
105 (40.56)
24ABC642A**30
34.30
32.30
30.10
27.90
88.70
98.10
107.40
116.70
2.26
2.54
2.86
3.22
37.90
35.70
33.30
30.80
89.90
99.20
108.40
117.70
2.28
2.56
2.88
3.24
41.70
39.20
36.70
34.00
91.20
100.40
109.60
118.70
2.30
2.58
2.90
3.26
45.80
43.10
40.20
37.30
92.50
101.60
110.80
119.80
2.32
2.60
2.92
3.29
50.10
47.10
44.00
40.80
93.90
103.00
112.00
121.00
2.34
2.63
2.95
3.32
54.60
51.30
47.90
44.40
95.40
104.40
113.40
122.30
2.36
2.66
2.99
3.36
24ABC648A**31
36.50
34.30
32.10
29.70
86.10
95.50
104.90
114.30
2.56
2.85
3.16
3.50
40.30
37.90
35.40
32.80
87.10
96.50
105.80
115.10
2.55
2.86
3.17
3.52
44.50
41.80
39.00
36.20
88.30
97.50
106.80
116.00
2.50
2.84
3.17
3.53
49.00
46.00
42.90
39.80
89.50
98.60
107.80
117.00
2.43
2.79
3.15
3.53
53.90
50.50
47.10
43.60
90.70
99.80
108.90
118.00
2.32
2.72
3.11
3.51
59.20
55.40
51.60
47.70
92.10
101.10
110.10
119.10
2.17
2.61
3.04
3.47
24ABC649A**30
39.90
37.40
34.90
32.30
88.90
98.20
107.60
116.90
2.75
3.08
3.44
3.84
44.00
41.20
38.50
35.60
90.10
99.40
108.70
118.00
2.75
3.10
3.47
3.87
48.40
45.30
42.20
39.10
91.50
100.70
109.90
119.00
2.75
3.12
3.50
3.91
53.00
49.60
46.20
42.80
92.90
102.00
111.10
120.20
2.75
3.14
3.53
3.95
58.00
54.20
50.50
46.70
94.50
103.40
112.40
121.40
2.73
3.15
3.56
3.99
63.20
59.10
55.00
50.90
96.10
104.90
113.80
122.60
2.71
3.16
3.59
4.02
24ABC660A**30
45.10
42.40
39.60
36.70
89.80
99.20
108.50
117.80
2.90
3.24
3.61
4.05
49.80
46.90
43.90
40.70
91.20
100.50
109.70
118.90
2.93
3.27
3.65
4.08
54.90
51.70
48.40
45.00
92.60
101.80
111.00
120.10
2.95
3.29
3.68
4.12
60.30
56.90
53.30
49.60
94.10
103.20
112.30
121.40
2.97
3.32
3.71
4.15
66.20
62.40
58.50
54.50
95.70
104.70
113.70
122.70
2.99
3.35
3.75
4.19
72.40
68.30
64.00
59.80
97.30
106.20
115.20
124.00
3.02
3.39
3.79
4.24
See notes on page 20
19
115 (46.11)
125 (51.67)
25.50
125.90
3.63
28.30
126.80
3.65
31.20
127.80
3.67
34.30
128.90
3.70
37.50
130.00
3.73
40.80
131.20
3.77
23.00
135.10
4.09
25.60
136.00
4.10
28.30
136.90
4.13
31.10
137.90
4.15
34.10
138.90
4.19
37.10
140.00
4.22
27.20
123.60
3.88
30.10
124.40
3.91
33.20
125.20
3.92
36.50
126.10
3.94
40.00
127.10
3.94
43.70
128.10
3.92
24.60
132.90
4.33
27.30
133.60
4.35
30.10
134.40
4.36
33.10
135.20
4.38
36.30
136.10
4.39
39.60
137.00
4.39
29.50
126.20
4.32
32.60
127.20
4.34
35.80
128.20
4.38
39.30
129.20
4.41
42.90
130.30
4.45
46.70
131.40
4.49
26.40
135.40
4.89
29.30
136.30
4.90
32.30
137.20
4.92
35.50
138.10
4.94
38.70
139.10
4.98
42.10
140.10
5.01
33.50
127.00
4.56
37.30
128.10
4.59
41.40
129.20
4.63
45.70
130.40
4.66
50.40
131.60
4.70
55.30
132.90
4.74
30.20
136.30
5.17
33.80
137.30
5.19
37.60
138.30
5.22
41.70
139.40
5.25
46.10
140.50
5.28
50.70
141.60
5.32
GUIDE SPECIFICATIONS
GENERAL
System Description
Outdoor--mounted, air--cooled, split--system air conditioner unit
suitable for ground or rooftop installation. Unit consists of a
hermetic compressor, an air--cooled coil, propeller--type
condenser fan, and a control box. Unit will discharge supply air
upward as shown on contract drawings. Unit will be used in a
refrigeration circuit to match up to a packaged fan coil or coil
unit.
Quality Assurance
— Unit will be rated in accordance with the latest edition
of AHRI Standard 210.
— Unit will be certified for capacity and efficiency, and
listed in the latest AHRI directory.
— Unit construction will comply with latest edition of
ANSI/ ASHRAE and with NEC.
— Unit will be constructed in accordance with UL
standards and will carry the UL label of approval. Unit
will have c--UL--us approval.
— Unit cabinet will be capable of withstanding Federal
Test Method Standard No. 141 (Method 6061) 500--hr
salt spray test.
— Air--cooled condenser coils will be leak tested at 150
psig and pressure tested at 450 psig.
— Unit constructed in ISO9001 approved facility.
Delivery, Storage, and Handling
— Unit will be shipped as single package only and is
stored and handled per unit manufacturer’s
recommendations.
Warranty (for inclusion by specifying engineer)
— U.S. and Canada only.
PRODUCTS
Equipment
Factory assembled, single piece, air--cooled air conditioner unit.
Contained within the unit enclosure is all factory wiring, piping,
controls, compressor, refrigerant charge Puronr (R--410A), and
special features required prior to field start--up.
Unit Cabinet
— Unit cabinet will be constructed of galvanized steel,
bonderized, and coated with a powder coat paint.
AIR--COOLED, SPLIT--SYSTEM AIR CONDITIONER
24ABC6
1--1/2 TO 5 NOMINAL TONS
Fans
— Condenser fan will be direct--drive propeller type,
discharging air upward.
— Condenser fan motors will be totally enclosed, 1--phase
type with class B insulation and permanently lubricated
bearings. Shafts will be corrosion resistant.
— Fan blades will be statically and dynamically balanced.
— Condenser fan openings will be equipped with coated
steel wire safety guards.
Compressor
— Compressor will be hermetically sealed.
— Compressor will be mounted on rubber vibration
isolators.
Condenser Coil
— Condenser coil will be air cooled.
— Coil will be constructed of aluminum fins mechanically
bonded to copper tubes which are then cleaned,
dehydrated, and sealed.
Refrigeration Components
— Refrigeration circuit components will include
liquid--line shutoff valve with sweat connections,
vapor--line shutoff valve with sweat connections,
system charge of Puronr (R--410A) refrigerant, and
compressor oil.
— Unit will be equipped with filter drier for Puron
refrigerant.
Operating Characteristics
— The capacity of the unit will meet or exceed _____
Btuh at a suction temperature of _____ _F/_C. The
power consumption at full load will not exceed _____
kW.
— Combination of the unit and the evaporator or fan coil
unit will have a total net cooling capacity of _____
Btuh or greater at conditions of _____ CFM entering
air temperature at the evaporator at _____ _F/_C wet
bulb and _____ _F/_C dry bulb, and air entering the
unit at _____ _F/_C.
— The system will have a SEER of _____ Btuh/watt or
greater at DOE conditions.
Electrical Requirements
— Nominal unit electrical characteristics will be _____ v,
single phase, 60 hz. The unit will be capable of
satisfactory operation within voltage limits of _____ v
to _____ v.
— Unit electrical power will be single point connection.
— Control circuit will be 24v.
Special Features
— Refer to section of this literature identifying accessories
and descriptions for specific features and available
enhancements.
21
SYSTEM DESIGN SUMMARY
1.
2.
3.
4.
5.
6.
7.
8.
9.
Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01--in. wc.
Minimum outdoor operating air temperature for cooling mode without low--ambient operation accessory is 55_F (12.8_C).
Maximum outdoor operating air temperature is 125_F (51.7_C).
For reliable operation, unit should be level in all horizontal planes.
For interconnecting refrigerant tube lengths greater than 80 ft (23.4 m) and/or 35 ft (10.7 m) vertical differential, consult Residential
Piping and Longline Guideline and Service Manual available from equipment distributor.
If any refrigerant tubing is buried, provide a 6 in. (152.4 mm) vertical rise to the valve connections at the unit. Refrigerant tubing
lengths up to 36 in. (914.4 mm) may be buried without further consideration. Do not bury refrigerant lines longer than 36 in. (914.4
mm).
Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector
provided.
Do not apply capillary tube indoor coils to these units.
Factory--supplied filter drier must be installed.
Copyright 2015 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231
Edition Date: 04/15
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
22
Catalog No: 24ABC6---5PD
Replaces: 24ABC6--- 4PD
Submittal Cover Sheet
Date Submitted:
May 19, 2015
Date Due Back:
May 26, 2015
RK Submittal No.:
235700.00 - 0
Specification Section:
23 57 00 - Coils and Heat Exchangers
Project Name:
Poudre Valley Health - UCH & FMC Renovation
1025 Garfield Street
General Contractor:
GH Phipps Construction Company
5995 Greenwood Plaza Blvd., Suite 100
Greenwood Village, CO 80111
Mechanical Contractor:
RK Mechanical, Inc.
3800 Xanthia Street
Denver, CO 80238
Subcontractor/Supplier:
RK Mechanical, Inc.
3800 Xanthia Street
Denver, CO 80238
ITEM
COPIES
REV
5
1
0
SUBMITTAL DESCRIPTION
DRAWING
MANUFACTURER
HVAC Control System
3800 Xanthia Street
Denver, Colorado 80238
ph: 303.355.9696
fx: 303.355.8666
www.rkmi.com
TAG
ZONEX, ZONE DAMPERS, STAND ALONE, BYPASS
Model
2 X GENII
9 X 101AHDM/RZKIT
2 X SAMOD
2 X 101ASPC/RZKIT
4800 OSAGE STREET
DENVER, COLORADO 80221
PHONE: (303) 825-4328
WWW.LOHMILLER.COM
FAX: (303) 820-2302
SYSTEM 2000 GEN II CONTROLLER
SUBMITTAL
System 2000
GEN II Controller
DESCRIPTION
The System 2000 GEN II is a microcontroller based,
auto changeover Universal Gas / Electric or Heat
Pump system controller (Part # GENII). The GEN II
controls a zoned 2H/2C Gas/Electric HVAC unit or
3H/2C zoned Heat Pump unit and communicates with
and supports up to 17 zones, utilizing pressure
dependent, modulating dampers.
The GEN II gathers information every 60 seconds from
each thermostat in the system over an unshielded twowire data link.
The GEN II is equipped with integrated capacity
control. The HVAC unit is staged on leaving air
temperature and time. The Leaving Air Temperature
is also displayed on the system controller. Cooling or
Heating management is vote based, predicated upon
first called, first served, with majority regulating
changeover.
When the current mode callers are satisfied, a fiveminute purge cycle is initiated prior to mode changeover.
Additional control strategies, including variance from
setpoint, are also selectable features to initiate
changeover. The GEN II provides a software based
feature to assign priority. A priority vote of 1, 2 or 3
votes may be established for every stat in the system
at the GEN II controller.
The GEN II controller is equipped with a lock / unlock
feature providing a central point to remotely lock all the
ModStats in the system. Locked thermostats will
support a +/- 2 degree local adjustment.
Each
thermostat also supports a two-hour override during
unoccupied periods at the touch of a button.
A night / day switch on the controller allows the ability
to establish an unoccupied Heat and Cool setpoint to
be set on each thermostat. An optional time clock
toggles the system from occupied to unoccupied mode
of operation.
TECHNICAL DATA
Electrical
Supply Voltage: 24vac
Power consumption: 0.7 VA
Inputs:
24vac
1 Temperature Sensing Thermistor
Outputs:
24vac
5 SPST dry contacts, 1A @ 24vac
Fuse protection: Use Fused Transformer
Environmental
Operating temperature: 32 to 160° F (0 to 71° C)
Operating humidity: 10-95%, non-condensing
Storage temperature: 0 to 160° F (-18 to 71° C)
General
Communications: 2 wire twisted pair - Belden 8740
Enclosure Dimensions: 7¼” H x 10” W x 3” D
5622 Engineer Drive / Huntington Beach, CA 92649 / Office (800) 228-2966 / Fax (714) 898-6802
Page 1 of 2
SYSTEM 2000 GEN II CONTROLLER
TERMINAL FUNCTIONS
TX – Data Transmit
RX – Data Receive
SS – Leaving / supply air sensor input
G – Fan output
W2 – Stage 2 heat output
W1 – Stage 1 heat
output
O/B – HP Reversing Valve
Y2 – Stage 2 cool output
Y1 – Stage 1 cool output
R – 24vac from unit transformer
TC
Time Clock input for Occupied /
TC
Unoccupied operation
TR1 – 24vac power input
TR2 – 24vac power common
R
Thermostat Power – daisy chain
C
stat to stat
ORDERING INFORMATION
Part No.
Description
GEN II
Universal Gas / Electric or Heat Pump
Controller supports 2-17 zones/unit
Accessories
GCLK 1 channel, 7-day time clock. Optional for
occupied/unoccupied operation
FEATURES
•
•
•
•
•
•
•
•
Universal vote based auto changeover controller
Fully modulating System
Support up to 17 zones per unit
Integrated capacity control
Leaving air temperature display
Automatic purge and ventilation modes
Auxiliary heat control included for each zone
Night setback operation included
•
•
•
•
•
•
Remote Thermostat locking feature
Two-hour override capability
Simple Startup Diagnostic
2-wire daisy chain - No home run wiring
required
No programming required
Very easy to install - No computer required
for setup or operation
10/12/12
5622 Engineer Drive / Huntington Beach, CA 92649 / Office (800) 228-2966 / Fax (714) 898-6802
Page 2 of 2
101AHDM ACTUATOR
SUBMITTAL
101AHDM
Direct Coupled Actuator
DESCRIPTION
The Zonex Systems 101AHDM is a power open, power
close 24vac actuator. This actuator is used on Zonex
Systems Medium Pressure and Heavy Duty dampers. It
can also be used to retrofit generic VAV boxes and
dampers, which use ¼” to ⅝” x 2” shafts, to Zonex
control systems. The 101AHDM is compatible with all
Zonex control systems for specified 2-position and
modulating applications.
For further information, see
Installation Instructions for the specific Zonex control system
application, or contact Zonex Systems Technical Support.
The AHDM actuator has many unique installation
features:
● Actuator connects directly to damper shaft
● Anti rotation strap for damper or VAV box installation
● Reflective visual damper position indicator
● Manual drive release button
● Digital rotation sensing (DRS) for end of travel hold
● Adjustable open/close stops
● Direction reverse switch
● Quiet operation - 35 dB sound rating
● 3-wire screw terminal block
TECHNICAL DATA
General Specifications:
●
●
●
●
●
●
●
●
●
Power Open / Power close - Floating
Rotation - 95° max. Mechanical open/close stops
Manual drive release button
95 second full stroke
Torque – 45 in-lb
Housing – NEMA 1
3-wire screw terminal block
Reversible direction switch
Weight – 1.1 Lbs
Electrical:
Supply Voltage: 24vac +/- 10% 50/60 Hz
Power consumption: 2 VA maximum (1.5 watt)
Wire Size: 18 ga. min. Solid
Environmental:
Ambient Temperature: -22° to 122°F (-30°C to +50 °C)
Operating humidity: 5 to 95% non-condensing
Storage temperature: -40°F to 176 ° F (-40°C to 66 °C)
Rev 2/14/08
5622 Engineer Drive / Huntington Beach, CA 92649 / Office (800) 228-2966 / Fax (714) 898-6802
Page 1 of 1
RZKIT Retrozone
SUBMITTAL
RZKIT
Retrofit Actuator and
Communicating / Modulating
Zone Thermostat
DESCRIPTION
The RZKIT includes a MODSTAT communicating
modulating thermostat and a 101AHDM replacement
actuator motor.
The Zonex Systems ModStat thermostat is a
microprocessor based, auto changeover, communicating
zone thermostat. The ModStat controls modulating
medium pressure and heavy duty dampers.
The
ModStat communicating zone thermostat is used with
the ModCom II, ZonexCommander (Plus) DDC systems
and the System 2000 GEN II zoning system.
The Zonex Systems 101AHDM is used on Zonex
Systems medium pressure and heavy duty dampers. It
can also be used to retrofit generic VAV boxes and
dampers, which use ¼” to ⅝” x 2” shafts, to Zonex
control systems. The 101AHDM is compatible with all
Zonex control systems for specified 2-position and
modulating applications. For further information, see
Installation Instructions for the specific Zonex control
system application, or contact Zonex Systems Technical
Support.
Zonex Systems has paired the MODSTAT and
101AHDM (RZKIT) with the System 2000 GEN II for
non-communicating systems and Zonex Commander
(Plus) or ModCom II for installation where onsite or
remote communications are required.
The RZKIT provides a simple, low cost solution
allowing the contractor to utilize existing dampers
and much of the existing controls wiring in the
retrofitting of existing VVT or older controls systems.
For further information, refer to the submittal for the
individual component: MODSTAT and 101AHDM.
Technical data for the MODSTAT and 101AHDM can
be found on Page 2 of this document.
5622 Engineer Drive / Huntington Beach, CA 92649 / Office (800) 228-2966 / Fax (714) 898-6802
Page 1 of 2
RZKIT Retrozone
TECHNICAL DATA
101AHDM
MODSTAT
General Specifications:
Electrical:
Supply voltage: 24vac
●
●
●
●
●
●
●
●
●
Power Open / Power close - Floating
Rotation - 95° max. Mechanical open/close stops
Manual drive release button
95 second full stroke
Torque – 45 in-lb
Housing – NEMA1
3-wire screw terminal block
Reversible direction switch
Weight – 1.1 lbs
Electrical:
Supply Voltage: 24vac +/- 10% 50/60 Hz
Power consumption: 2 VA maximum (1.5 watt)
Wire Size: 18 ga. min. Solid
Environmental:
Ambient Temperature: -22 to 122F (-30°C to +50C)
Operating humidity: 5 to 95% non-condensing
Storage temperature: -40°F to 176 F (-40°C to 66C)
Power consumption: 2 va maximum
Input:
• 24vac
• Platinum Thermistor
Outputs:
• RO RC W2 Triacs - 24vac @ .3 amp max
• W1 Relay - 24vac @ 1.0 amp maximum
Communication: RS485
Twisted pair or shielded twisted pair
Environmental:
Operating Temperature: 35° to 130° F (2° to 54° C)
Operating Humidity: 5 to 95% non-condensing
Storage Temperature: 0° to 150° (-18° to 66° C)
General:
Dimensions: 4 ½” H x 2 7/8” W x 1” D
Temperature Display Range: 55° to 95° F
Accuracy: +/- 0.8° F
Memory: Non-volatile EEPROM
Display: Grey backlight LCD
Rev 1/4/11
5622 Engineer Drive / Huntington Beach, CA 92649 / Office (800) 228-2966 / Fax (714) 898-6802
Page 2 of 2
SAMOD II
SUBMITTAL
SAMOD II
Stand Alone Modulating Thermostat
DESCRIPTION
The Zonex Systems Stand Alone Modulating thermostat,
SAMOD II, is a microprocessor based, auto changeover
modulating thermostat. The SAMOD II is used in stand alone
damper applications where independent sub control is required.
The SAMOD II does not control or cycle the HVAC equipment.
The space ambient temperature is continuously displayed on
the SAMOD II. An accurate duct sensor is installed upstream
of the damper. For Auto changeover operation the duct
temperature is compared to the room ambient for changeover.
If the DAT is 3 F. or less than room ambient, the SAMOD II
recognizes that cooling air is available for the zone. If the DAT
is 7 F. or warmer than the room ambient, the SAMOD II has
warm air available for heating the zone. The damper will
modulate to maintain room temperature based on variance from
set point.
If no heating or cooling calls exist, the Supply air temperatures
between the changeover set points will be considered as a
ventilation mode, and the damper will provide ventilation and
continuous circulation to the space.
By holding the UP and DN buttons on the SAMOD II, duct
temperature readings will be displayed at the thermostat
providing current temperature information and set points. In the
event of power loss, the set points are stored in a non-volatile
memory, without need for battery backup.
The SAMOD II is equipped with a Auxiliary contact to control a
supplemental heating source, such as baseboard, radiant, duct
heater or VAV box. The second stage is activated from the
thermostat when the room temperature falls 2 below the heat
set point.
NOTE: An air proving switch (field supplied) must be used for
reheat applications. A field supplied relay may be required for
VAV box applications.
SAMOD II is very versatile and may be utilized in a communicating format with the ZonexCommander family of
DDC products. The room temperature and set points may
be remotely displayed and revised via the Zonex software.
This software also provides 7-day scheduling, the ability to
remotely lock the SAMOD II, review or modify set points,
and trend log on site or remotely over the Internet.
TECHNICAL DATA
Electrical:
Supply Voltage: 24vac
Power consumption: 4 VA maximum
(10 VA maximum w/ STMPD damper)
Inputs:

24vac

NTC Thermistor

Duct Thermistor
Outputs: 2- triac, 24vac @ 2.5 VA
Environmental:
Operating temperature: 35 to 130 F (2 to 54 C)
Operating humidity: 5-95% non-condensing
Storage temperature: 0 to 150 F (-18 to 66 C)
General:
Dimensions: 4 1/2” H x 2 7/8” W x 1” D
Range: 55 - 95 F.
Accuracy: +/- 0.8 F.
Memory: Non-volatile EEPROM
Display: Backlit Multi-icon LCD
Communication: RS 485
Twisted Pair – with Zonex DDC systems
A Remote Sensor is available for the SAMOD II. The RS
option allows a Remote Sensor to be located up to 200’ from
the thermostat, using standard 18 GA thermostat wire.
5622 Engineer Drive / Huntington Beach, CA 92649 / Office (800) 228-2966 / Fax (714) 898-6802
Page 1 of 2
Rev 3/10/10
SAMOD II
ORDERING INFORMATION
Part No.
Description
SAMOD
SAMODRS
Stand alone modulating damper thermostat with duct sensor
Stand alone modulating damper thermostat, with duct and remote sensor
TERMINAL FUNCTIONS
R - 24vac power input
C - 2vac power common
RO - damper run open signal
RC - damper run closed signal
MC - 24V motor common
DS - duct temperature sensor
DS - duct temperature sensor
AUX - Auxiliary Heat
Note: The SAMOD II is used with Zonex
Systems modulating STMPD (round) and
STCD (rectangular) dampers or D-Fuser.
FEATURES







Auto changeover dual set point
No batteries required
Attractive, compact design
Off white color
Accurate temperature control
Large LCD display
Duct sensor included







Easy to adjust or calibrate
Ability to switch off
Illuminated for night viewing
Non-volatile memory: Retains stored set points
Remote sensor capability
Displays duct temperature
Used in a communicating format with Zonex DDC systems
5622 Engineer Drive / Huntington Beach, CA 92649 / Office (800) 228-2966 / Fax (714) 898-6802
Page 2 of 2
101ASPC STATIC PRESSURE SENSOR
SUBMITTAL
101ASPC
Static Pressure Sensor
DESCRIPTION
TECHNICAL DATA
The 101ASPC static pressure sensor is a single pole,
double throw diaphragm type switch used to modulate a
STMPD or STCD damper in bypass applications. The
101ASPC monitors differential pressure between the
supply duct and the ambient pressure.
Electrical:
The contacts will switch state as the static pressure in
the supply duct changes with varying zone damper
positions. As the 101ASPC set point is obtained, the
contacts will remain neutral within a +/- range of .04”
w.c. , The damper will then remain in its last position.
When the static pressure in the duct changes beyond
the hysteresis, contact state will be made according to
the change in duct pressure.
Supply Voltage: N/A
Power consumption: N/A
Input:
• 24vac
Outputs:
• 24vac (Run open)
• 24vac (Run closed)
General:
Range: 0 to 2.0” w.c.
Hysteresis: .04” w.c.
Dimensions: 5 3/4” H x 3 1/4” W x 3” D
24vac is switched to the run open or run closed
terminals of the bypass damper as determined by the
101ASPC.
When there is zero airflow, the bypass damper will
remain in its last position until fan operation is initialized.
5622 Engineer Drive / Huntington Beach, CA 92649 / Office (800) 228-2966 / Fax (714) 898-6802
1 of 2
101ASPC STATIC PRESSURE SENSOR
SENSOR LOCATION
TYPICAL SENSOR WIRING
DIMENSIONS
D= 3.0”
5 3/4”
3 1/4”
5622 Engineer Drive / Huntington Beach, CA 92649 / Office (800) 228-2966 / Fax (714) 898-6802
2 of 2
ModStat / MODS2 THERMOSTATS
SUBMITTAL
ModStat / MODS2 Thermostats
Communicating / Modulating / 2 Position
Zone Thermostat
DESCRIPTION
TECHNICAL DATA
The ModStat and MODS2 are microprocessor based,
auto changeover, communicating zone thermostats. The
ModStats control modulating medium pressure and
heavy duty dampers, and the MODS2 controls 2position, low pressure dampers. These communicating
zone thermostats are used with the ModCom, Zonex
Commander (Plus) DDC systems, and the System 2000
GEN II zoning system.
Electrical:
Supply voltage: 24vac
ModStat / MODS2 thermostats communicate to the
command centers or zone controller to initiate Heat or
Cool calls in the system. Zone status and system
operation are displayed on the large easy-to-read backlit
LCD display.
Outputs:
• RO RC W2 Triacs - 24vac @ .3 amp max
• W1 Relay - 24vac @ 1.0 amp maximum
The ModStat / MODS2 thermostats are easy to
configure and make manual adjustments with the
function buttons located on the front cover.
The space ambient temperature is continuously
displayed with a range of 55° to 95° F. Programmed
setpoints can be manually adjusted or electronically
locked through the program to provide limited manual
setpoint adjustment. Two-hour override is provided for
after hours temporary operation, with a touch of a button.
The thermostat can be easily field calibrated, if required.
Power consumption: 4 va maximum
Input:
• 24vac
• Platinum Thermistor
Communication: RS485
Twisted pair or shielded twisted pair
Environmental:
Operating Temperature: 35° to 130° F (2° to 54° C)
Operating Humidity: 5 to 95% non-condensing
Storage Temperature: 0° to 150° (-18° to 66° C)
General:
Dimensions: 4 ½” H x 2 7/8” W x 1” D
Temperature Display Range: 55° to 95° F
Accuracy: +/- 0.8° F
Memory: Non-volatile EEPROM
Display: Grey backlight LCD
The ModStat can be field configured for baseboard,
panel and reheat operations, including Fan Powered
Boxes. NOTE: an air proving switch must be used for
this application; field supplied.
5622 Engineer Drive / Huntington Beach, CA 92649 / Office (800) 228-2966 / Fax (714) 898-6802
Page 1 of 2
Rev 4/14/10
ModStat / MODS2 THERMOSTATS
TERMINAL FUNCTIONS
24V Terminal Block
RO – Run Open, damper (not used for MODS2)
RC – Run Close, damper
AUX – Reheat/AUX Heat Fan
R – 24vac power input
C-MC – 24vac common / damper common
(18 ga. Minimum wire size)
Communication Terminal Block
TX – Data Transmit
RX – Data Receive
TX – Data Transmit
RX – Data Receive
(Twisted pair or shielded twisted pair)
FEATURES
•
•
•
•
•
Attractive compact design
No batteries required
Neutral off-white color
Accurate temperature control
Electronic lock
•
•
•
•
•
Large display with grey backlight
Function buttons on front cover
Configurable Reheat and Auxiliary heat output
ModStat to control power open/close dampers
MODS2 to control power close/spring open dampers
ACCESSORIES
Part No.
Description
ModStatRS
ModStatC
WPLT
RZKIT
ModStat thermostat with remote sensor
For Celsius version add "C" to thermostat Part No.
Wall Plate – when upgrading VVT and VVHC thermostats
Thermostat and actuator as a package for VVT, and other, upgrade.
5622 Engineer Drive / Huntington Beach, CA 92649 / Office (800) 228-2966 / Fax (714) 898-6802
Page 2 of 2
GCLK 7-DAY PROGRAMMABLE CLOCK
SUBMITTAL
GCLK
7-Day Programmable Time Clock
For System 2000 GEN II
DESCRIPTION
The GCLK is a 24-volt, 7-day time clock designed
for the System 2000 GEN II zoning system. This
unique, compact time clock provides a single
channel, 24-hour or 7-day global scheduling for
Occupied (on) and Unoccupied (off) system
operation. A maximum of 20 program events are
provided for On-Off schedules.
This time clock also features a 100-hour backup
battery to maintain program memory and display in
the event of a power failure. There is a manual
override provision for troubleshooting or temporary
operation.
TECHNICAL DATA
Electrical:
Supply Voltage: 24vac (+ /- 10%) 1 VA
Output: 1 SPDT dry contacts 1.6 amp @24vac
Wire Connections: Screw terminals
Mounting:
Surface mount using 3 screws (provided) for base
Removable display cover and lens
Removable wire terminal cover
NOTE: Time clock must be mounted next to the
System 2000 GEN II controller.
Environmental:
The terminal strip on the time clock requires only
four wires: two for 24vac power and two for the
output relay switching contacts.
The output
contacts on the time clock are wired to the “TC”
terminals on the System 2000 GEN II controller.
The time clock has a clear LCD display for time of
day and switch program status. Four simple push
buttons are located on the face for programming
and manual override. No enclosure is required.
Ambient Temperature Range: -14°F to 131°F
(-10°C to 55°C)
Dimensions:
2 7/8” W x 4 1/4” H x 2 1/4” D
Rev 7/14/08
5622 Engineer Drive / Huntington Beach, CA 92649 / Office (800) 228-2966 / Fax (714) 898-6802
Page 1 of 1
STMRTD RECTANGULAR MEDIUM PRESSURE SUPPLY DAMPER
SUBMITTAL
STMRTD
Rectangular medium pressure
supply damper
DESCRIPTION
TECHNICAL DATA
The STMRTD WxH is a medium pressure opposed
blade supply air damper, and is available from 6” x 6” to
24” x 24” dimensions, in 2” increments. This damper is
rated for a maximum pressure differential of 1.0” S.P. for
HVAC systems of 7.5 tons or less. A bottom mount
option is available in all sizes.
Electrical:
The actuator is installed on the Height dimension unless
the damper is ordered as Bottom Mount, which will put
the actuator on the Width dimension.
Environmental:
The STMRTD is a “cut-in” style damper, which is
designed to slide into the rectangular supply duct. The
damper assembly consists of a heavy duty extruded
aluminum frame, to provide maximum rigidity. All
opposed blade shafts pivot in nylon bushings to reduce
friction and ensure quiet operation. A high density rubber
gasket affords an efficient seal to minimize blade to
frame leakage.
Supply Voltage: 24vac
Power consumption: 2 VA maximum (1.5 watt)
Wire Size: 18 ga. Solid Minimum
Operating temperature: -22° to 122° F (-30 to 50° C)
Operating humidity: 5-95% non-condensing
Storage temperature: -10° to 150° F (-23° to 66° C)
General:
Frame: .050 extruded aluminum
Linkage: Stainless steel
Actuator: Power Open / Power Close
Stroke: 90°
Pressure drop: < .09” W.C. @ nominal CFM
STMRTD dampers can be wired in paralleled to provide
additional zone CFM capacity when required.
Minimum open and close positions can be manually
adjusted on the actuator for air balance requirements.
5622 Engineer Drive / Huntington Beach, CA 92649 / Office (800) 228-2966 / Fax (714) 898-6802
Page 1 of 1
Rev 5/29/08