Installation Instructions
Transcription
Installation Instructions
INSTALLATION INSTRUCTIONS AIR HANDLERS FEATURING R-22 REFRIGERANT: (-)HLA High Efficiency (-)HSA Standard Efficiency FEATURING EARTH-FRIENDLY R-410A REFRIGERANT: refrigerant (-)HLL High Efficiency (-)HSL Standard Efficiency ! RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION! ! WARNING ! ▲WARNING THESE INSTRUCTIONS ARE INTENDED AS AN AID TO These instructions are intended asPERSONNEL an aid to qualified licensed QUALIFIED, LICENSED SERVICE FOR PROPER service personnel for properAND installation, adjustment and INSTALLATION, ADJUSTMENT OPERATION OF THIS UNIT. operation of this unit. Read these instructions thoroughly before READ THESE INSTRUCTIONS THOROUGHLY BEFORE attempting installation or operation. Failure to follow ATTEMPTING INSTALLATION OR OPERATION. FAILURE TO these FOLinstructions result in improper installation, adjustment, LOW THESEmay INSTRUCTIONS MAY RESULT IN IMPROPER service or maintenance possibly resulting fire, electrical INSTALLATION, ADJUSTMENT, SERVICE ORinMAINTENANCE shock, property damage, personal injuryELECTRICAL or death. POSSIBLY RESULTING IN FIRE, SHOCK, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH. ISO 9001:2000 DO NOT DESTROY THIS MANUAL PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE BY A SERVICEMAN 92-20521-32-04 SUPERSEDES 92-20521-32-03 TABLE OF CONTENTS 1.0 SAFETY INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2.0 GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 2.1 Important Information About Efficiency and Indoor Air Quality. . . . . . . . . . . . 5 2.2 Receiving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 2.3 Clearances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 2.4 Model Number Explanation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 2.4A Available Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 2.5 Dimensions and Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 3.0 APPLICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 3.1 Vertical Upflow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 3.2 Vertical Downflow. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 3.3 Horizontal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 3.4 Installation in an Unconditioned Space . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 4.0 ELECTRICAL WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 4.1 Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 4.2 Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 4.3 Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 4.4 Copper Wire Size. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 4.5 Blower Motor Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 4.5A Blower Motor Electrical Data: (-)HSA/(-)HSL. . . . . . . . . . . . . . . . . . . . 15 4.5B Blower Motor Electrical Data: (-)HLA/(-)HLL . . . . . . . . . . . . . . . . . . . . 15 4.6 Electric Heat Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 4.6A Electric Heat Electrical Data: (-)HSA/(-)HSL . . . . . . . . . . . . . . . . . . . . 16 4.6B Electric Heat Electrical Data: (-)HLA/(-)HLL . . . . . . . . . . . . . . . . . . . . 18 4.6C Heater Kit Supplemental Information . . . . . . . . . . . . . . . . . . . . . . . . . 20 5.0 AIRFLOW PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 5.1 Airflow Operatng Limits (-)HSA/(-)HSL . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 5.2 240V Airflow Performance Data (-)HSA/(-)HSL . . . . . . . . . . . . . . . . . . . . . . 22 5.3 115/208/480V Airflow Performance Data (-)HSA/(-)HSL . . . . . . . . . . . . . . . 24 5.4 115/208/240V Airflow Performance Data (-)HLA/(-)HLL . . . . . . . . . . . . . . . 26 6.0 DUCTWORK. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 7.0 REFRIGERANT CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 7.1 TEV Sensing Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 7.2 Condensate Drain Tubing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 7.3 Duct Flanges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 8.0 AIR FILTER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 9.0 SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 9.1 Cooling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 9.2 Heating (electric heat only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 9.3 Heating (heat pump) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 9.4 Blower Time Delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 9.5 Defrost Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 9.6 Emergency Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 9.7 Room Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 10.0 CALCULATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 10.1 Calculating Temperature Rise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 10.2 Calculating BTUH Heating Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 10.3 Calculating Airflow CFM. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 10.4 Calculating Correction Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 11.0 PRE-START CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 12.0 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 12.1 Air Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 12.2 Indoor Coil/Drain Pan/Drain Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 12.3 Blower Motor & Wheel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 12.4 Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 12.5 Blower Assembly Removal & Replacement. . . . . . . . . . . . . . . . . . . . . . . . . 33 12.6 Motor Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 12.7 Blower Wheel Replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 13.0 REPLACEMENT PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 14.0 ACCESSORIES - KITS - PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 2 ! WARNING (SEE SECTION 4.0: ELECTRICAL WIRING) Disconnect all power to unit before installing or servicing. More than one disconnect switch may be required to de-energize the equipment. Hazardous voltage can cause severe personal injury or death. ! WARNING (SEE SECTION 12.5: BLOWER ASSEMBLY REMOVAL & REPLACEMENT) If removal of the blower assembly is required, all disconnect switches supplying power to the equipment must be de-energized and locked (if not in sight of unit) so the field power wires can be safely removed from the blower assembly. Failure to do so can cause electrical shock resulting in personal injury or death. ! WARNING Because of possible damage to equipment or personal injury, installation, service, and maintenance should be performed by a trained, qualified service personnel. Consumer service is recommended only for filter cleaning/ replacement. Never operate the unit with the access panels removed. 1.0 SAFETY INFORMATION ! WARNING Duct leaks can create an unbalanced system and draw pollutants such as dirt, dust, fumes and odors into the home causing property damage. Fumes and odors from toxic, volatile or flammable chemicals, as well as automobile exhaust and carbon monoxide (CO), can be drawn into the living space through leaking ducts and unbalanced duct systems causing personal injury or death (see Figure 1). • If air-moving equipment or ductwork is located in garages or off-garage storage areas - all joints, seams, and openings in the equipment and duct must be sealed to limit the migration of toxic fumes and odors including carbon monoxide from migrating into the living space. • If air-moving equipment or ductwork is located in spaces containing fuel burning appliances such as water heaters or boilers - all joints, seams, and openings in the equipment and duct must also be sealed to prevent depressurization of the space and possible migration of combustion byproducts including carbon monoxide into the living space. ! WARNING These instructions are intended as an aid to qualified, licensed service personnel for proper installation, adjustment and operation of this unit. Read these instructions thoroughly before attempting installation or operation. Failure to follow these instructions may result in improper installation, adjustment, service or maintenance possibly resulting in fire, electrical shock, property damage, personal injury or death. ! WARNING (SEE WARNINGS IN REGARD TO DUCTWORK) Do not install this unit in manufactured (mobile) homes. Improper installation is more likely in manufactured housing due to ductwork material, size, location, and arrangement. Installations in manufactured housing can cause a fire resulting in property damage, personal injury or death. EXCEPTION: Manufactured housing installations are approved only with documentation by a recognized inspection authority that the installation has been made in compliance with the instructions and all warnings have been observed. ! WARNING (SEE SECTION 3.2: VERTICAL DOWNFLOW) The RXHB-17, RXHB-21 or RXHB-24 combustible floor base is required when some units with electric heat are applied downflow on combustible flooring. Failure to use the base can cause a fire resulting in property damage, personal injury or death. See CLEARANCES for units requiring a combustible floor base. See the accessory section in this manual for combustible floor base RXHB. ! WARNING (SEE SECTION 4.3: GROUNDING) The unit must be permanently grounded. Failure to do so can result in electrical shock causing personal injury or death. ! WARNING (SEE SECTION 12.0: MAINTENANCE) Units with circuit breaker(s) meet requirements as a service disconnect switch, however, if access is required to the line side (covered) of the circuit breaker, this side of the breaker(s) will be energized with the breaker(s) de-energized. Contact with the line side can cause electrical shock resulting in personal injury or death. ! WARNING (SEE SECTION 5.0: DUCTWORK) Do not, under any circumstances, connect return ductwork to any other heat producing device such as fireplace insert, stove, etc. Unauthorized use of such devices may result in fire, carbon monoxide poisoning, explosion, personal injury or property damage. Continued on next page ➜ 3 ! WARNING PROPOSITION 65: This appliance contains fiberglass insulation. Respirable particles of fiberglass are known to the State of California to cause cancer. All manufacturer products meet current Federal OSHA Guidelines for safety. California Proposition 65 warnings are required for certain products, which are not covered by the OSHA standards. California's Proposition 65 requires warnings for products sold in California that contain or produce any of over 600 listed chemicals known to the State of California to cause cancer or birth defects such as fiberglass insulation, lead in brass, and combustion products from natural gas. All “new equipment” shipped for sale in California will have labels stating that the product contains and/or produces Proposition 65 chemicals. Although we have not changed our processes, having the same label on all our products facilitates manufacturing and shipping. We cannot always know “when, or if” products will be sold in the California market. You may receive inquiries from customers about chemicals found in, or produced by, some of our heating and air-conditioning equipment, or found in natural gas used with some of our products. Listed below are those chemicals and substances commonly associated with similar equipment in our industry and other manufacturers. • • • • Glass Wool (Fiberglass) Insulation Carbon Monoxide (CO). Formaldehyde Benzene More details are available at the websites for OSHA (Occupational Safety and Health Administration), at www.osha.gov and the State of California’s OEHHA (Office of Environmental Health Hazard Assessment), at www.oehha.org. Consumer education is important since the chemicals and substances on the list are found in our daily lives. Most consumers are aware that products present safety and health risks, when improperly used, handled and maintained. ! WARNING (SEE SECTION 12.6: MOTOR REPLACEMENT) To avoid electrical shock which can result in personal injury or death, use only the screws furnished in the motor shell mounting holds. Screws are #8-18 x .25 in. long blunt nose thread forming. Screws longer than 1/4 in. may contact the motor winding. ! WARNING (SEE SECTION 7.0: AIR FILTER) Do not operate the system without filters. A portion of the dust entrained in the air may temporarily lodge in the duct runs and at the supply registers. Any circulated dust particles could be heated and charred by contact with the air handler elements. This residue could soil ceilings, walls, drapes, carpets and other articles in the house. Soot damage may occur with filters in place, when certain types of candles, oil lamps or standing pilots are burned. ! WARNING The first 36 inches of supply air plenum and ductwork must be constructed of sheet metal as required by NFPA 90B. The supply air plenum or duct must have a solid sheet metal bottom directly under the unit with no openings, registers or flexible air ducts located in it. If flexible supply air ducts are used they may be located only in the vertical walls of a rectangular plenum, a minimum of 6 inches from the solid bottom. Metal plenum or duct may be connected to the combustible floor base, if not, it must be connected to the unit supply duct flanges such that combustible floor or other combustible material is not exposed to the supply air opening from the downflow unit. Exposing combustible (non-metal) material to the supply opening of a downflow unit can cause a fire resulting in property damage, personal injury or death. Exceptions to downflow warnings: • Installations on concrete floor slab with supply air plenum and ductwork completely encased in not less than 2 inches of concrete (See NFPA 90B). ! CAUTION (SEE SECTION 3.3: HORIZONTAL) Horizontal units must be configured for right hand air supply or left hand air supply. Horizontal drain pan must be located under indoor coil. Failure to use the drain pan can result in property damage. ! CAUTION (SEE SECTION 2.1: RECEIVING) In compliance with recognized codes, it is recommended that an auxiliary drain pan be installed under all evaporator coils or units containing evaporator coils that are located in any area of a structure where damage to the building or building contents may occur as a result of an overflow of the coil drain pan or a stoppage in the primary condensate drain piping. See accessories for auxiliary horizontal overflow pan RXBM. ! CAUTION When used in cooling applications, excessive sweating may occur when unit is installed in an unconditioned space. This can result in property damage. ! NOTICE Improper installation, or installation not made in accordance with the Underwriters Laboratory (UL) certification or these instructions, can result in unsatisfactory operation and/or dangerous conditions and are not covered by the unit warranty. ! NOTICE In compliance with recognized codes, it is recommended that an auxiliary drain pan be installed under all evaporator coils or units containing evaporator coils that are located in any area of a structure where damage to the building or building contents may occur as a result of an overflow of the coil drain pan or a stoppage in the primary condensate drain piping. See accessories section of these instructions for auxiliary horizontal overflow pan information (model RXBM). 4 2.0 GENERAL INFORMATION 2.1 IMPORTANT INFORMATION ABOUT EFFICIENCY AND INDOOR 2.1 AIR QUALITY Central cooling and heating equipment is only as efficient as the duct system that carries the cooled or heated air. To maintain efficiency, comfort and good indoor air quality, it is important to have the proper balance between the air being supplied to each room and the air returning to the cooling and heating equipment. Proper balance and sealing of the duct system improves the efficiency of the heating and air conditioning system and improves the indoor air quality of the home by reducing the amount of airborne pollutants that enter homes from spaces where the ductwork and / or equipment is located. The manufacturer and the U.S. Environmental Protection Agency’s Energy Star Program recommend that central duct systems be checked by a qualified contractor for proper balance and sealing. FIGURE 1 MIGRATION OF DANGEROUS SUBSTANCES, FUMES, AND ODORS INTO LIVING SPACES ! WARNING Duct leaks can create an unbalanced system and draw pollutants such as dirt, dust, fumes and odors into the home causing property damage. Fumes and odors from toxic, volatile or flammable chemicals, as well as automobile exhaust and carbon monoxide (CO), can be drawn into the living space through leaking ducts and unbalanced duct systems causing personal injury or death (see Figure 1). • If air-moving equipment or ductwork is located in garages or off-garage storage areas - all joints, seams, and openings in the equipment and duct must be sealed to limit the migration of toxic fumes and odors including carbon monoxide from migrating into the living space. • If air-moving equipment or ductwork is located in spaces containing fuel burning appliances such as water heaters or boilers - all joints, seams, and openings in the equipment and duct must also be sealed to prevent depressurization of the space and possible migration of combustion byproducts including carbon monoxide into the living space. ! NOTICE Improper installation, or installa-tion not made in accordance with the Underwriters Laboratory (UL) certification or these instructions, can result in unsatisfactory operation and/or dangerous condi-tions and are not covered by the unit warranty. 5 ! NOTICE In compliance with recognized codes, it is recommended that an auxiliary drain pan be installed under all evaporator coils or units containing evaporator coils that are located in any area of a structure where damage to the building or building contents may occur as a result of an overflow of the coil drain pan or a stoppage in the primary condensate drain piping. See accessories section of these instructions for auxiliary horizontal overflow pan information (model RXBM). 2.2 RECEIVING Immediately upon receipt, all cartons and contents should be inspected for transit damage. Units with damaged cartons should be opened immediately. If damage is found, it should be noted on the delivery papers, and a damage claim filed with the last carrier. • After unit has been delivered to job site, remove carton taking care not to damage unit. • Check the unit rating plate for unit size, electric heat, coil, voltage, phase, etc. to be sure equipment matches what is required for the job specification. • Read the entire instructions before starting the installation. • Some building codes require extra cabinet insulation and gasketing when unit is installed in attic applications. • If installed in an unconditioned space, apply caulking around the power wires, control wires, refrigerant tubing and condensate line where they enter the cabinet. Seal the power wires on the inside where they exit conduit opening. Caulking is required to pre-vent air leakage into and condensate from forming inside the unit, control box, and on electrical controls. • Install the unit in such a way as to allow necessary access to the coil/filter rack and blower/control compartment. • Install the unit in a level position to ensure proper condensate drainage. Make sure unit is level in both directions within 1/8”. • Install the unit in accordance with any local code which may apply and the national codes. Latest editions are available from: “National Fire Protection Association, Inc., Batterysmarch Park, Quincy, MA 02269.” These publications are: • ANSI/NFPA No. 70-(Latest Edition) National Electrical Code. • NFPA90A Installation of Air Conditioning and Ventilating Systems. • NFPA90B Installation of warm air heating and air conditioning systems. • The equipment has been evaluated in accordance with the Code of Federal Regulations, Chapter XX, Part 3280. 2.3 CLEARANCES • All units are designed for “0” inches clearance to combustible material on all cabinet surfaces. • Some units require supply duct clearances and combustible floor bases depending on the heating kW. The following table should be used to determine these requirements: Model Cabinet Size 17 21 24 Model Designation kW 15 20 25 Units with electric heating kW above that listed in the table require a one inch clearance to combustible material for the first three feet of supply plenum and ductwork. Additionally, if these units are installed downflow, a combustible floor base is required. Units with electric heating kW equal to or less than the values listed in the table do not require supply ductwork clearances or combustible floor bases. • Vertical units require clearance on at least one side of the unit for electrical connections. Horizontal units require clearance on either top or bottom for electrical connections. Refrigerant and condensate drain connections are made on the front of the unit. • All units require 24 inches minimum access to the front of the unit for service. • These units may be installed in either ventilated or nonventilated spaces. 6 2.4 MODEL NUMBER EXPLANATION FIGURE 2 MODEL NUMBER EXPLANATION (-) H S A — HM 18 17 J A DESIGN VARIATION A = 1ST DESIGN VOLTAGE A = 115/1/60 D = 480V-3-60 J = 208/240/1/60 CABINET SIZE 17 = 17.5" (600 - 1200 CFM) 21 = 21" (1200 - 1600 CFM) 24 = 24.5" (1600 -1800 CFM) CAPACITY 18 = 18,000 BTU/H 24 = 24,000 BTU/H 30 = 30,000 BTU/H 36 = 36,000 BTU/H 42 = 42,000 BTU/H 48 = 48,000 BTU/H 60 = 60,000 BTU/H HM = A/C OR HP MULTI-POSITION HM = (Vertical Upflow/Horizontal Left is the factory configuration) REFRIGERANT A = R-22 L = R-410A S = STANDARD MODEL (PSC MOTOR) CLASSIFICATION H = AIR HANDLER TRADE BRAND (-) H L A — HM 24 17 J A DESIGN VARIATION A = 1ST DESIGN VOLTAGE A = 115/1/60 J = 208/240/1/60 CABINET SIZE 17 = 17.5" (600 - 1200 CFM) 21 = 21" (1400 - 1600 CFM) 24 = 24.5" (1600 - 1800 CFM) CAPACITY 24 = 18,000 / 24,000 BTU/H 36 = 30,000 / 36,000 BTU/H 48 = 42,000 / 48,000 BTU/H 60 = 60,000 BTU/H HM = A/C OR HP MULTI-POSITION HM = (Vertical Upflow/Horizontal Left is the factory configuration) REFRIGERANT A = R-22 L = R-410A L = HIGH EFFICIENCY (X-13 MOTOR) CLASSIFICATION H = AIR HANDLER TRADE BRAND 7 2.4A AVAILABLE MODELS AVAILABLE MODELS AT A VOLTAGE (-)HSA(L)-HM1817AA (-)HSA(L)-HM2417AA (-)HSA(L)-HM3017AA (-)HSA(L)-HM3617AA (-)HSA(L)-HM4221AA (-)HSA(L)-HM4821AA (-)HLA(L)-HM2417AA (-)HLA(L)-HM3617AA (-)HLA(L)-HM4821AA (-)HLA(L)-HM4824AA (-)HLA(L)-HM6024AA AVAILABLE MODELS AT J VOLTAGE (-)HSA-HM1817JA (-)HSA-HM2417JA (-)HSA-HM3017JA (-)HSA-HM3617JA (-)HSA-HM3621JA (-)HSA-HM4221JA (-)HSA-HM4821JA (-)HSA-HM4824JA (-)HSA-HM6024JA (-)HLA(L)-HM2417JA (-)HLA(L)-HM3617JA (-)HLA(L)-HM4821JA (-)HLA(L)-HM4824JA (-)HLA(L)-HM6024JA AVAILABLE MODELS AT D VOLTAGE (-)HSA(L)-HM3617DA (-)HSA(L)-HM3621DA (-)HSA(L)-HM4221DA (-)HSA(L)-HM4821DA (-)HSA(L)-HM4824DA (-)HSA(L)-HM6024DA Notes: • Supply circuit protective devices may be fuses or “HACR” type circuit breakers. • Largest motor load is included in single circuit and multiple circuit 1. • If non-standard fuse size is specified, use next size larger fuse size. • J Voltage (230V) single phase air handler is designed to be used with single or three phase 230 volt power. In the case of connecting 3-phase power to the air handler terminal block, bring only two leads to the terminal block. Cap, insulate and fully secure the third lead. • (-)HSA-HM6024JA is ARI rated for three phase application only. • The air handlers are shipped from the factory with the proper indoor coil installed, and cannot be ordered without a coil. • The air handlers do not have an internal filter rack. An external filter rack or other means of filtration is required. 8 2.5 DIMENSIONS & WEIGHTS FIGURE 3 NOTE: 24" CLEARANCE REQUIRED IN FRONT OF UNIT FOR FILTER AND COIL MAINTENANCE. DIMENSIONS AND WEIGHTS ELECTRICAL CONNECTIONS MAY EXIT TOP OR EITHER SIDE SUPPLY AIR HIGH VOLTAGE CONNECTION 7/8". 1 3/32", 1 31/32" DIA. KNOCK OUTS. FLANGES ARE PROVIDED FOR FIELD INSTALLATION 105/16 W A LOW VOLTAGE CONNECTION 5/8" AND 7/8" KNOCK OUT (OUTSIDE OF CABINET) Return Air Opening Dimensions Model Cabinet Size 17 21 24 Return Air Opening Width (Inches) 157⁄8 193⁄8 227⁄8 Return Air Opening Depth/Length (Inches) 193⁄4 193⁄4 193⁄4 H AUXILIARY DRAIN CONNECTION 3/4" FEMALE PIPE THREAD (NPT) HORIZONTAL APPLICATION ONLY PRIMARY DRAIN CONNECTION 3/4" FEMALE PIPE THREAD (NPT) AUXILIARY DRAIN CONNECTION 3/4" FEMALE PIPE THREAD (NPT) UPFLOW/DOWNFLOW APPLICATION ONLY 191/2 RETURN AIR OPENING 2111/16 LIQUID LINE CONNECTION COPPER (SWEAT) A-1038-01 UPFLOW UNIT SHOWN; UNIT MAY BE INSTALLED UPFLOW, DOWNFLOW. HORIZONTAL RIGHT, OR LEFT AIR SUPPLY. VAPOR LINE CONNECTION COPPER (SWEAT) DIMENSIONAL DATA UNIT HEIGHT IN. [mm] UNIT WIDTH “W” IN. [mm] SUPPLY DUCT “A” IN. [mm] 1817/2417 421/2" [1080] 171/2" [444.5] 3017/3617 421/2" [1080] 3621 MODEL SIZE AIRFLOW COIL (NOM.) [L/s] UNIT WEIGHT / SHIPPING WEIGHT (LBS.) [kg] LO HI UNIT WITH COIL (MAX. kW.) 16" [406.4] 600 [283] 800 [378] 82/96 [37.1]/[43.5] 16" [406.4] 1000 [472] 1200 [566] 92/106 [41.7]/[48.0] 421/2" [1080] 171/2" [444.5] 21" [533.4] 191/2" [495.3] 1200 [566] — 97/112 [43.9]/[50.8] 4221/4821 501/2" [1283] 21" [533.4] 150/166 [68.0]/[75.2] 551/2" [1410] 241/2" [622.3] 1400 [661] 1600 [755] 1600 [755] 4824 191/2" [495.3] 23" [581.2] — 162/180 [73.4]/[81.6] 6024 551/2" [1410] 241/2" [622.3] 23" [581.2] — 1800 [850] 181/198 [82.1]/[89.8] 9 3.0 APPLICATIONS 3.1 VERTICAL UPFLOW • Vertical Upflow is the factory configuration for all models (see Figure 3). • If a side return air opening is required, field fabricate a return air plenum with an opening large enough to supply unit and strong enough to support unit weight. • If return air is to be ducted, install duct flush with floor. Use fireproof resilient gasket 1/8 to 1/4 in. thick between duct, unit and floor. Set unit on floor over opening FIGURE 4 DIMENSIONS FOR FRONT CONNECT COIL 515/16 41/8 31/16 13/16 11/8 11/16 13/8 213/16 51/4 53/8 3.2 VERTICAL DOWNFLOW Conversion to Vertical Downflow: A vertical upflow unit may be converted to vertical downflow. Remove the door and indoor coil and reinstall 180° from original position (see Figure 5). IMPORTANT: To comply with certification agencies and the National Electric Code for horizontal right application, the circuit breaker(s) on field-installed electric heater kits must be re-installed per procedure below so that the breaker switch “on” position and marking is up and, “off” position and marking is down. - To turn breaker(s): Rotate one breaker pair (circuit) at a time starting with the one on the right. Loosen both lugs on the load side of the breaker. Wires are bundles with wire ties, one bundle going to the right lug and one bundle going to the left lug. - Using a screwdriver or pencil, lift white plastic tab with hole away from breaker until breaker releases from mounting opening (see Figure 5). - With breaker held in hand, rotate breaker so that “on” position is up, “off” position is down with unit in planned vertical mounting position. Insert right wire bundle into top right breaker lug, ensuring all strands of all wires are inserted fully into lug, and no wire insulation is in lug. - Tighten lug as tight as possible while holding circuit breaker. Check wires and make sure each wire is secure and none are loose. Repeat for left wire bundle in left top circuit breaker lug. - Replace breaker by inserting breaker mounting tab opposite white pull tab in opening, hook mounting tab over edge in opening. 10 FIGURE 5 ROTATING CIRCUIT BREAKER - With screwdriver or pencil, pull white tab with hole away from breaker while setting that side of breaker into opening. When breaker is in place, release tab, locking circuit breaker into location in opening. - Repeat above operation for remaining breaker(s) (if more than one is provided). - Replace single point wiring jumper bar, if it is used, on line side of breaker and tighten securely. - Double check wires and lugs to make sure all are secure and tight. Check to make sure unit wiring to circuit breaker load lugs match that shown on the unit wiring diagram. • RXHB combustible floor base is used for all unit sizes. Unit must be centered on combustible base in the width dimension (143/8”). (See Section 14.0 for more information on the combustible floor base.) ! WARNING The RXHB-17, RXHB-21 or RXHB-24 combustible floor base is required when some units with electric heat are applied downflow on combustible flooring. Failure to use the base can cause a fire resulting in property damage, personal injury or death. See CLEARANCES for units requiring a combustible floor base. See the accessory section in this manual for combustible floor base RXHB. 3.3 HORIZONTAL Horizontal left is the default factory configuration for “HM” (airflow direction) units. Conversion to Horizontal: A vertical upflow unit (AU) may be converted to horizontal by removing the indoor coil and installing horizontal drain pan on coil as shown for right hand or left hand air supply. Reinstall coil in unit as shown for right or left hand air supply. See Figures 6 & 7. (See Section 14.0 for more information on the Horizontal Adapter Kit.) • Rotate unit into the downflow position, with the coil compartment on top and the blower compartment on bottom. • Reinstall the indoor coil 180° from original position. Ensure the retaining channel is fully engaged with the coil rail. (See Figure 6, Detail A.) • Secondary drain pan kits RXBM- are required when the unit is configured for the horizontal right position over a finished ceiling and/or living space. (See Section 14.0: Accessories - Kits - Parts.) IMPORTANT: Units cannot be installed horizontally laying on or suspended from the back of the unit. 11 FIGURE 6 VERTICAL DOWNFLOW & HORIZONTAL RIGHT APPLICATIONS DETAIL A ENSURE THE RETAINING CHANNEL IS FULLY ENGAGED WITH THE COIL RAIL. RAILS RAILS FIGURE 7 INDOOR COIL AND DRAIN PAN SET-UP STRAPS REAR WATER CATCHER HORIZONTAL ADAPTER KIT TOP AIR STOP FRONT WATER CATCHER VAPOR LINE CONNECTION AUXILIARY HORIZONTAL DRAIN CONNECTION PRIMARY DRAIN CONNECTION AUXILIARY UPFLOW/DOWNFLOW DRAIN CONNECTION LIQUID LINE CONNECTION VERTICAL DRAIN PAN A-1037-01 ! CAUTION Horizontal units must be configured for right hand air supply or left hand air supply. Horizontal drain pan must be located under indoor coil. Failure to use the drain pan can result in property damage. 12 Conversion in Horizontal Direction: Horizontal left-hand supply can be changed to horizontal right-hand supply by removing the indoor coil and reinstalling 180° from original. (See Figure 5.) 3.4 INSTALLATION IN AN UNCONDITIONED SPACE IMPORTANT: There are two pairs of coil rails in the air handler for default and counter flow application. If the air handler is installed in an unconditioned space, the two unused coil rails should be removed to minimize air handler surface sweating. (See Figure 5.) The coil rails can be easily removed by taking off the 6 mounting screws from both sides of the cabinet. 4.0 ELECTRICAL WIRING Field wiring must comply with the National Electric Code (C.E.C. in Canada) and any applicable local ordinance. ! WARNING Disconnect all power to unit before installing or servicing. More than one disconnect switch may be required to de-energize the equipment. Hazardous voltage can cause severe personal injury or death. 4.1 POWER WIRING It is important that proper electrical power is available for connection to the unit model being installed. See the unit nameplate, wiring diagram and electrical data in the installation instructions. • If required, install a branch circuit disconnect of adequate size, located within sight of, and readily accessible to the unit. • IMPORTANT: After the Electric Heater is installed, units may be equipped with one, two, or three 30/60 amp. circuit breakers. These breaker(s) protect the internal wiring in the event of a short circuit and serve as a disconnect. Circuit breakers installed within the unit do not provide over-current protection of the supply wiring and therefore may be sized larger than the branch circuit protection. • Supply circuit power wiring must be 75°C minimum copper conductors only. See Electrical Data in this section for ampacity, wire size and circuit protector requirement. Supply circuit protective devices may be either fuses or “HACR” type circuit breakers. • Power wiring may be connected to either the right, left side or top. Three 7/8”, 13/32”, 131/32” dia. concentric knockouts are provided for connection of power wiring to unit. • Power wiring is connected to the power terminal block in unit control compartment. 13 4.2 CONTROL WIRING IMPORTANT: Class 2 low voltage control wire should not be run in conduit with power wiring and must be separated from power wiring, unless class 1 wire of proper voltage rating is used. • Low voltage control wiring should be 18 Awg. color-coded. For lengths longer than 100 ft., 16 Awg. wire should be used. • Low voltage control connections are made to low voltage pigtails extending from top of air handler (upflow position - see Figure 3). Connections for control wiring are made with wire nuts. Control wiring knockouts (5/8 and 7/8) are also provided on the right and left side of the unit for side connection. • See wiring diagrams attached to indoor and outdoor sections to be connected, or control wiring diagram booklet supplied with outdoor heat pump section for wiring connection. • Make sure, after installation, separation of control wiring and power wiring has been maintained. 4.3 GROUNDING ! WARNING The unit must be permanently grounded. Failure to do so can result in electrical shock causing personal injury or death. • Grounding may be accomplished by grounding metal conduit when installed in accordance with electrical codes to the unit cabinet. • Grounding may also be accomplished by attaching ground wire(s) to ground lug(s) provided in the unit wiring compartment. • Ground lug(s) are located close to wire entrance on left side of unit (upflow). Lug(s) may be moved to marked locations near wire entrance on right side of unit (upflow), if alternate location is more convenient. • Use of multiple supply circuits require grounding of each circuit to lug(s) provided in unit. 14 4.4 ELECTRICAL WIRING POWER WIRING • Field wiring must comply with the National Electrical Code (C.E.C. in Canada) and any applicable local ordinance. • Supply wiring must be 75°C minimum copper conductors only. • See electrical data for product Ampacity rating and Circuit Protector requirement. GROUNDING • This product must be sufficiently grounded in accordance with National Electrical Code (C.E.C. in Canada) and any applicable local ordinance. • A grounding lug is provided. 4.5 ELECTRICAL DATA – BLOWER MOTOR ONLY – NO ELECTRIC HEAT 4.5A Electrical Data – Blower Motor Only – No Electric Heat: (-)HSA/(-)HSL NOMINAL COOLING CAPACITY TONS 11/2 2 21/2 3 31/2 4 11/2 2 21/2 3 31/2 4 5 3 31/2 4 5 VOLTAGE 115 PHASE* 1 MINIMUM MAXIMUM CIRCUIT CIRCUIT AMPACITY PROTECTOR HERTZ HP RPM SPEEDS CIRCUIT AMPS. 60 1/5 1/5 1/4 1/3 1/2 3/4 1075 1075 1075 1075 1075 1075 2 2 2 2 2 2 2.3 3.8 4.7 6.1 7.9 8.4 3.0 5.0 6.0 8.0 10.0 11.0 15 15 15 15 15 15 1/5 1/5 1/4 1/3 1/2 3/4 1075 1075 1075 1075 1075 1075 2 2 2 2 2 2 1.7 1.7 2.5 2.5 5.2 5.2 3.0 3.0 4.0 4.0 7.0 7.0 15 15 15 15 15 15 3/4 1/3 1075 1075 2 2 5.2 1.4 7.0 2.0 15 15 1/3 3/4 3/4 1075 1075 1075 2 2 2 2.2 2.2 2.2 3.0 3.0 3.0 15 15 15 208/240 1&3 60 208/240 3 60 480 3 60 4.5B Electrical Data – Blower Motor Only – No Electric Heat: (-)HLA/(-)HLL NOMINAL COOLING CAPACITY TONS MINIMUM MAXIMUM CIRCUIT CIRCUIT AMPACITY PROTECTOR HP RPM SPEEDS CIRCUIT AMPS. 1/3 300-1100 4 1.6 2 15 1/2 300-1100 4 2.7 4 15 31/2 & 4 3/4 300-1100 4 3.8 5 15 5 3/4 300-1100 4 4.6 6 15 11/2 & 2 1/3 300-1100 4 4.8 6 15 1/2 300-1100 4 6.8 9 15 31/2 & 4 3/4 300-1100 4 8.4 11 15 5 3/4 300-1100 4 8.4 11 15 VOLTAGE PHASE* HERTZ 11/2 & 2 21/2 & 3 208/240 1&3 60 21/2 & 3 115 1 60 *Blower motors are all single phase motors. 15 4.6 ELECTRICAL DATA – WITH ELECTRIC HEAT Installation of the UL Listed original equipment manufacturer provided heater kits listed in the following table is recommended for all auxiliary heating requirements. 4.6A ELECTRICAL DATA – WITH ELECTRIC HEAT: (-)HSA/(-)HSL COOLING CAPACITY TONS CABINET SIZE (-)HSA/(-)HSL 1-1/2 & 2 17 MODEL NO. HEATER KW 208/240V RXBH-17A03J RXBH-17A05J RXBH-17A07J RXBH-17A10J RXBH-17A13J 2.25/3.0 3.6/4.8 5.4/7.2 7.2/9.6 9.4/12.5 3.1/4.2 6.3/8.3 5.4/7.2 7.2/9.6 9.4/12.5 2.25/3.0 3.6/4.8 5.4/7.2 7.2/9.6 9.4/12.5 3.1/4.2 6.3/8.3 10.8/14.4 3.6/4.8 7.2/9.6 12.8/17.0 4.3/5.7 8.5/11.3 5.4/7.2 7.2/9.6 9.4/12.5 10.8/14.4 12.8/17.0 7.2 9.6 14.4 17 3.6/4.8 5.4/7.2 7.2/9.6 10.8/14.4 3.6/4.8 7.2/9.6 12.8/17.0 6.4/8.5 6.4/8.5 5.4/7.2 7.2/9.6 10.8/14.4 12.8/17.0 7.2 9.6 14.4 17 RXBH-17A13J RXBH-17A07C RXBH-17A10C RXBH-17A13C RXBH-17A03J RXBH-17A05J RXBH-17A07J RXBH-17A10J RXBH-17A13J (-)HSA/(-)HSL 2-1/2 & 3 17 RXBH-17A13J RXBH-17A15J RXBH-17A15J RXBH-17A18J RXBH-17A18J RXBH-17A07C RXBH-17A10C RXBH-17A13C RXBH-17A15C RXBH-17A18C RXBH-17A07D RXBH-17A10D RXBH-17A15D RXBH-17A18D RXBH-24A05J RXBH-24A07J RXBH-24A10J RXBH-24A15J (-)HSA/(-)HSL 3 21 RXBH-24A15J RXBH-24A18J RXBJ-24A18J RXBH-24A07C RXBH-24A10C RXBH-24A15C RXBH-24A18C RXBH-24A07D RXBH-24A10D RXBH-24A15D RXBH-24A18D 16 TYPE SUPPLY NO. CIRCUIT PH/HZ ELEMENTS SINGLE - KW PER MULTIPLECIRCUIT CIRCUIT 1/60 1/60 1/60 1/60 1/60 1/60 1/60 3/60 3/60 3/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 1-3.0 1-4.8 2-3.6 2-4.8 3-4.17 1-4.17 2-4.17 3-2.4 3-3.2 3-4.17 1-3.0 1-4.8 2-3.6 2-4.8 3-4.17 1-4.17 2-4.17 3-4.8 1-4.8 2-4.8 3-5.68 1-5.68 2-5.68 3-2.4 3-3.2 3-4.17 3-4.8 3-5.68 2-3.6 3-3.2 3-4.8 3-5.68 1-4.8 2-3.6 2-4.8 3-4.8 1-4.8 2-4.8 4-4.26 2-4.26 2-4.26 3-2.4 3-3.2 3-4.8 3-5.68 2-3.6 3-3.2 3-4.8 3-5.68 SINGLE SINGLE SINGLE SINGLE SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE CIRCUIT AMPS. 10.8/12.5 17.3/20.0 26.0/30.0 34.6/40.0 45.1/52.1 15.0/17.4 30.1/34.7 15.0/17.3 20.0/23.1 26.1/30.1 10.8/12.5 17.3/20.0 26.0/30.0 34.6/40.0 45.1/52.1 15.0/17.4 30.1/34.7 51.9/60.0 17.3/20.0 34.6/40.0 61.6/70.8 20.5/23.6 41.1/47.2 15.0/17.3 20.0/23.1 26.1/30.1 30.0/34.6 35.5/41.0 8.7 11.6 17.3 20.4 17.3/20.0 26.0/30.0 34.6/40.0 51.9/60.0 17.3/20.0 34.6/40.0 61.6/70.8 30.8/35.4 30.8/35.4 15.0/17.3 20.0/23.1 30.0/34.6 35.5/41.0 8.7 11.6 17.3 20.4 MINIMUM MOTOR CIRCUIT AMPACITY AMPACITY 1.7 1.7 1.7 1.7 1.7 1.7 0 1.7 1.7 1.7 2.5 2.5 2.5 2.5 2.5 2.5 0 2.5 2.5 0 2.5 2.5 0 2.5 2.5 2.5 2.5 2.5 1.4 1.4 1.4 1.4 2.5 2.5 2.5 2.5 2.5 0 2.5 2.5 0 2.5 2.5 2.5 2.5 1.4 1.4 1.4 1.4 16/18 24/28 35/40 46/53 59/68 21/24 38/44 21/24 28/31 35/40 17/19 25/29 36/41 47/54 60/69 22/25 38/44 68/79 25/29 44/50 81/92 29/33 52/59 22/25 29/32 36/41 41/47 48/55 13 17 24 28 25/29 36/41 47/54 68/79 25/29 44/50 81/92 42/48 39/45 22/25 29/32 41/47 48/55 13 17 24 28 MAXIMUM CIRCUIT PROTECTION 20/20 25/30 35/40 50/60 60/70 25/25 40/45 25/25 30/35 35/40 20/20 25/30 40/45 50/60 60/70 25/25 40/45 70/80 25/30 45/50 90/100 30/35 60/60 25/25 30/35 40/45 45/50 50/60 15 20 25 30 25/30 40/45 50/60 70/80 25/30 45/50 90/100 45/50 40/45 25/25 30/35 45/50 50/60 15 20 25 30 4.6A ELECTRICAL DATA – WITH ELECTRIC HEAT: (-)HSA/(-)HSL - continued COOLING CAPACITY TONS CABINET SIZE (-)HSA/(-)HSL 3-1/2 & 4 21 and 4 24 (-)HSA/(-)HSL 5 24 MODEL NO. HEATER KW 208/240V RXBH-24A05J 3.6/4.8 RXBH-24A07J 5.4/7.2 RXBH-24A10J 7.2/9.6 RXBH-24A15J 10.8/14.4 RXBH-24A15J 3.6/4.8 7.2/9.6 RXBH-24A18J 12.8/17 RXBH-24A18J 6.4/8.5 6.4/8.5 RXBH-24A20J 14.4/19.2 RXBH-24A20J 7.2/9.6 7.2/9.6 RXBH-24A25J 18.0/24.0 RXBH-24A25J 6.0/8.0 6.0/8.0 (4-ton only) 6.0/8.0 RXBH-24A07C 5.4/7.2 RXBH-24A10C 7.2/9.6 RXBH-24A15C 10.8/14.4 RXBH-24A18C 12.8/17.0 RXBH-24A20C* 14.4/19.2 RXBH-24A20C 7.2/9.6 7.2/9.6 RXBH-24A25C* 18.0/24.0 RXBH-24A25C 9.0/12.0 (4-ton only) 9.0/12.0 RXBH-24A07D 7.2 RXBH-24A10D 9.6 RXBH-24A15D 14.4 RXBH-24A18D 17 RXBH-24A20D 19.2 RXBH-24A25D 24.0 (4-ton only) RXBH-24A05J 3.6/4.8 RXBH-24A07C 5.4/7.2 RXBH-24A10C 7.2/9.6 RXBH-24A15C 10.8/14.4 RXBH-24A18C 12.8/17.0 RXBH-24A20C* 14.4/19.2 7.2/9.6 RXBH-24A20C 7.2/9.6 RXBH-24A25C* 18.0/24.0 RXBH-24A25C 9.0/12.0 9.0/12.0 RXBH-24A30C* 21.6/28.8 RXBH-24A30C 10.8/14.4 10.8/14.4 RXBH-24A07D 7.2 RXBH-24A10D 9.6 RXBH-24A15D 14.4 RXBH-24A18D 17 RXBH-24A20D 19.2 RXBH-24A25D 24.0 RXBH-24A30D* 28.8 TYPE SUPPLY NO. CIRCUIT PH/HZ ELEMENTS SINGLE - KW PER MULTIPLECIRCUIT CIRCUIT CIRCUIT AMPS. MINIMUM MOTOR CIRCUIT AMPACITY AMPACITY MAXIMUM CIRCUIT PROTECTION 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/6 1/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 1-4.8 2-3.6 2-4.8 3-4.8 1-4.8 2-4.8 4-4.26 2-4.26 2-4.26 4-4.8 2-4.8 2-4.8 6-4.0 2-4.0 2-4.0 2-4.0 3-2.4 3-3.2 3-4.8 3-2.84 3-3.2 3-3.2 3-3.2 6-4.0 3-4.0 3-4.0 2-3.6 3-3.2 3-4.8 3-5.68 6-3.2 SINGLE SINGLE SINGLE SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 MULTIPLE CKT 3 SINGLE SINGLE SINGLE SINGLE SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE SINGLE SINGLE SINGLE SINGLE 17.3/20.0 26.0/30.0 34.6/40.0 51.9/60.0 17.3/20.0 34.6/40.0 61.6/70.8 30.8/35.4 30.8/35.4 69.2/80 34.6/40.0 34.6/40.0 86.4/99.9 28.8/33.3 28.8/33.3 28.8/33.3 15.0/17.3 20.0/23.1 30.0/34.6 35.6/41.0 40.0/46.2 20.0/23.1 20.0/23.1 50.0/57.8 25.0/28.9 25.0/28.9 8.7 11.6 17.3 20.4 23.2 4.0 4.0 4.0 4.0 4.0 0.0 4.0 4.0 0.0 4.0 4.0 0.0 4.0 4.0 0.0 0.0 4.0 4.0 4.0 4.0 4.0 4.0 0.0 4.0 4.0 0.0 2.2 2.2 2.2 2.2 2.2 27/30 38/43 49/55 70/80 27/30 44/50 82/94 44/50 39/45 92/105 49/55 44/50 113/130 42/47 36/42 36/42 24/27 30/34 43/49 50/57 55/63 30/34 25/29 68/78 37/42 32/37 14 18 25 29 32 30/30 40/45 50/60 70/80 30/30 45/50 90/100 45/50 40/45 100/110 50/60 45/50 125/150 45/50 40/45 40/45 25/30 30/35 45/50 50/60 60/70 30/35 25/30 70/80 40/45 35/40 15 20 25 30 35 3/60 6-4.0 SINGLE 28.8 2.2 39 40 1/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 1-4.8 3-2.4 3-3.2 3-4.8 3-2.84 3-3.2 3-3.2 3-3.2 6-4.0 3-4.0 3-4.0 6-4.8 3-4.8 3-4.8 2-3.6 3-3.2 3-4.8 3-5.68 6-3.2 6-4.0 6-4.8 SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE 17.3/20.0 15.0/17.3 20.0/23.1 30.0/34.6 35.6/41.0 40.0/46.2 20.0/23.1 20.0/23.1 50.0/57.8 25.0/28.9 25.0/28.9 60.0/69.4 30.0/34.7 30.0/34.7 8.7 11.6 17.3 20.4 23.2 28.8 34.6 4.4 4.4 4.4 4.4 4.4 4.4 4.4 0 4.4 4.4 0 4.4 4.4 0 2.2 2.2 2.2 2.2 2.2 2.2 2.2 28/31 25/28 31/35 43/49 50/57 56/64 31/35 25/29 68/78 37/42 32/37 81/93 43/49 38/44 14 18 25 29 32 39 46 30/35 25/30 35/35 45/50 50/60 60/70 35/35 25/30 70/80 40/45 35/40 90/100 45/50 40/45 15 20 25 30 35 40 50 *Values only. No single point kit available. NOTES: • Electric heater BTUH - (heater watts + motor watts) x 3.414 (see airflow table for motor watts.) • Supply circuit protective devices may be fuses or “HACR” type circuit breakers. • If non-standard fuse size is specified, use next size larger standard fuse size. • Largest motor load is included in single circuit or circuit 1 of multiple circuits. • Heater loads are balanced on 3 phase models with 3 or 6 heaters only. • No electrical heating elements are permitted to be used with A Voltage (115V) air handler. • J Voltage (230V) signal phase air handler is designed to be used with single or three phase 230 volt electric heaters. In the case of connecting 3 phase power to air handler terminal block without the heater, bring only two leads to terminal block, cap, insulate and fully secure the third lead. • Do not use 480 volts electrical heaters on 230 volts air handler. • Do not use 230 volts electrical heaters on 480 volts air handler. • If the kit is listed under both single and multiple circuits, the kit is shipped from factory as multiple circuits. For single phase application, Jumper bar kit RXBJ-A21 and RXBJ-A31 can be used to convert multiple circuits to a single supply circuit. Refer to Accessory Section for details. 17 4.6B ELECTRICAL DATA – WITH ELECTRIC HEAT: (-)HLA/(-)HLL Installation of the UL Listed original equipment manufacturer provided heater kits listed in the following table is recommended for all auxiliary heating requirements. COOLING CAPACITY TONS CABINET SIZE (-)HLA/(-)HLL 1-1/2 & 2 17 (-)HLA/(-)HLL 2-1/2 & 3 17 (-)HLA/(-)HLL 3-1/2 & 4 21 18 MODEL NO. HEATER KW 208/240V RXBH-17A03J RXBH-17A05J RXBH-17A07J RXBH-17A10J RXBH-17A13J TYPE SUPPLY NO. CIRCUIT PH/HZ ELEMENTS SINGLE - KW PER MULTIPLECIRCUIT CIRCUIT CIRCUIT AMPS. MINIMUM MOTOR CIRCUIT AMPACITY AMPACITY MAXIMUM CIRCUIT PROTECTION 2.25/3.0 3.6/4.8 5.4/7.2 7.2/9.6 9.4/12.5 3.1/4.2 RXBH-17A13J 6.3/8.3 RXBH-17A07C 5.4/7.2 RXBH-17A10C 7.2/9.6 RXBH-17A13C 9.4/12.5 RXBH-17A03J 2.25/3.0 RXBH-17A05J 3.6/4.8 RXBH-17A07J 5.4/7.2 RXBH-17A10J 7.2/9.6 RXBH-17A13J 9.4/12.5 3.1/4.2 RXBH-17A13J 6.3/8.3 1/60 1/60 1/60 1/60 1/60 1/60 1/60 3/60 3/60 3/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1-3.0 1-4.8 2-3.6 2-4.8 3-4.17 1-4.17 2-4.17 3-2.4 3-3.2 3-4.17 1-3.0 1-4.8 2-3.6 2-4.8 3-4.17 1-4.17 2-4.17 SINGLE SINGLE SINGLE SINGLE SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 10.8/12.5 17.3/20.0 26.0/30.0 34.6/40.0 45.1/52.1 15.0/17.4 30.1/34.7 15.0/17.3 20.0/23.1 26.1/30.1 10.8/12.5 17.3/20.0 26.0/30.0 34.6/40.0 45.1/52.1 15.0/17.4 30.1/34.7 1.6 1.6 1.6 1.6 1.6 1.6 0 1.6 1.6 1.6 2.7 2.7 2.7 2.7 2.7 2.7 0 16/18 24/27 35/40 46/52 59/68 21/24 38/44 21/24 27/31 35/40 17/19 25/29 36/41 47/54 60/69 23/26 38/44 20/20 25/30 35/40 50/60 60/70 25/25 40/45 25/25 30/35 35/40 20/20 25/30 40/45 50/60 60/70 25/30 40/45 RXBH-17A15J 10.8/14.4 3.6/4.8 RXBH-17A15J 7.2/9.6 RXBH-17A18J 12.8/17.0 4.3/5.7 RXBH-17A18J 8.5/11.3 RXBH-17A07C 5.4/7.2 RXBH-17A10C 7.2/9.6 RXBH-17A13C 9.4/12.5 RXBH-17A15C 10.8/14.4 RXBH-17A18C 12.8/17.0 RXBH-24A05J 3.6/4.8 RXBH-24A07J 5.4/7.2 RXBH-24A10J 7.2/9.6 RXBH-24A15J 10.8/14.4 3.6/4.8 RXBH-24A15J 7.2/9.6 RXBH-24A18J 12.8/17.0 6.4/8.5 RXBJ-24A18J 6.4/8.5 RXBH-24A20J 14.4/19.2 7.2/9.6 RXBH-24A20J 7.2/9.6 RXBH-24A25J 18.0/24.0 6.0/8.0 RXBH-24A25J 6.0/8.0 (4-ton only) 6.0/8.0 RXBH-24A07C 5.4/7.2 RXBH-24A10C 7.2/9.6 RXBH-24A15C 10.8/14.4 RXBH-24A18C 12.8/17.0 RXBH-24A20C* 14.4/19.2 7.2/9.6 RXBH-24A20C 7.2/9.6 RXBH-24A25C* 18.0/24.0 RXBH-24A25C 9.0/12.0 (4-ton only) 9.0/12.0 1/60 1/60 1/60 1/60 1/60 1/60 3/60 3/60 3/60 3/60 3/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3-4.8 1-4.8 2-4.8 3-5.68 1-5.68 2-5.68 3-2.4 3-3.2 3-4.17 3-4.8 3-5.68 1-4.8 2-3.6 2-4.8 3-4.8 1-4.8 2-4.8 4-4.26 2-4.26 2-4.26 4-48 2-4.8 2-4.8 6-4.0 2-4.0 2-4.0 2-4.0 3-2.4 3-3.2 3-4.8 3-2.84 3-3.2 3-3.2 3-3.2 6-4.0 3-4.0 3-4.0 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 MULTIPLE CKT 3 SINGLE SINGLE SINGLE SINGLE SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 51.9/60.0 17.3/20.0 34.6/40.0 61.6/70.8 20.5/23.6 41.1/47.2 15.0/17.3 20.0/23.1 26.1/30.1 30.0/34.6 35.5/41.0 17.3/20.0 26.0/30.0 34.6/40.0 51.9/60.0 17.3/20.0 34.6/40.0 61.6/70.8 30.8/35.4 30.8/35.4 69.2/80 34.6/40.0 34.6/40.0 86.4/99.9 28.8/33.3 28.8/33.3 28.8/33.3 15.0/17.3 20.0/23.1 30.0/34.6 35.6/41.0 40.0/46.2 20.0/23.1 20.0/23.1 50.0/57.8 25.0/28.9 25.0/28.9 2.7 2.7 0 2.7 2.7 0 2.7 2.7 2.7 2.7 2.7 3.8 3.8 3.8 3.8 3.8 0.0 3.8 3.8 0.0 3.8 3.8 0.0 3.8 3.8 0.0 0.0 3.8 3.8 3.8 3.8 3.8 3.8 0.0 3.8 3.8 0.0 69/79 25/29 44/50 81/92 29/33 52/59 23/25 29/33 36/41 41/47 48/55 27/30 38/43 48/55 70/80 27/30 44/50 82/94 44/49 39/45 92/105 48/55 44/50 113/130 41/47 36/42 36/42 24/27 30/34 43/48 50/56 55/63 30/34 25/29 68/77 36/41 32/37 70/80 25/30 45/50 90/100 30/35 60/60 25/25 30/35 40/45 45/50 50/60 30/30 40/45 50/60 70/80 30/30 45/50 90/100 45/50 40/45 100/110 50/60 45/50 125/150 45/50 40/45 40/45 25/30 30/35 45/50 50/60 60/70 30/35 25/30 70/80 40/45 35/40 4.6B Electrical Data – With Electric Heat: (-)HLA/(-)HLL - continued COOLING CAPACITY TONS CABINET SIZE (-)HLA/(-)HLL 4&5 24 MODEL NO. HEATER KW 208/240V RXBH-24A07J 5.4/7.2 RXBH-24A10J 7.2/9.6 RXBH-24A15J 10.8/14.4 3.6/4.8 RXBH-24A15J 7.2/9.6 RXBH-24A18J 12.8/17 6.4/8.5 RXBH-24A18J 6.4/8.5 RXBH-24A20J 14.4/19.2 7.2/9.6 RXBH-24A20J 7.2/9.6 RXBH-24A25J 18.0/24.0 6.0/8.0 RXBH-24A25J 6.0/8.0 6.0/8.0 RXBH-24A30J 21.6/28.8 7.2/9.6 RXBH-24A30J 7.2/9.6 (5-ton only) 7.2/9.6 RXBH-24A07C 5.4/7.2 RXBH-24A10C 7.2/9.6 RXBH-24A15C 10.8/14.4 RXBH-24A18C 12.8/17.0 RXBH-24A20C* 14.4/19.2 7.2/9.6 RXBH-24A20C 7.2/9.6 RXBH-24A25C* 18.0/24.0 9.0/12.0 RXBH-24A25C 9.0/12.0 RXBH-24A30C* 21.6/28.8 RXBH-24A30C 10.8/14.4 (5-ton only) 10.8/14.4 TYPE SUPPLY NO. CIRCUIT PH/HZ ELEMENTS SINGLE - KW PER MULTIPLECIRCUIT CIRCUIT 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 1/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 3/60 2-3.6 2-4.8 3-4.8 1-4.8 2-4.8 4-4.26 2-4.26 2-4.26 4-4.8 2-4.8 2-4.8 6-4.0 2-4.0 2-4.0 2-4.0 6-4.8 2-4.8 2-4.8 2-4.8 3-2.4 3-3.2 3-4.8 3-2.84 3-3.2 3-3.2 3-3.2 6-4.0 3-4.0 3-4.0 6-4.8 3-4.8 3-4.8 SINGLE SINGLE SINGLE MULTIPLE CKT1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 MULTIPLE CKT 3 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 MULTIPLE CKT 3 SINGLE SINGLE SINGLE SINGLE SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 SINGLE MULTIPLE CKT 1 MULTIPLE CKT 2 CIRCUIT AMPS. 26.0/30.0 34.6/40.0 51.9/60.0 17.3/20.0 34.6/40.0 61.6/70.8 30.8/35.4 30.8/35.4 69.2/80 34.6/40.0 34.6/40.0 86.4/99.9 28.8/33.3 28.8/33.3 28.8/33.3 103.8/120. 34.6/40.0 34.6/40.0 34.6/40.0 15.0/17.3 20.0/23.1 30.0/34.6 35.6/41.0 40.0/46.2 20.0/23.1 20.0/23.1 50.0/57.8 25.0/28.9 25.0/28.9 60.0/69.4 30.0/34.7 30.0/34.7 MINIMUM MOTOR CIRCUIT AMPACITY AMPACITY 4.6 4.6 4.6 4.6 0 4.6 4.6 0 4.6 4.6 0 4.6 4.6 0 0 4.6 4.6 0 0 4.6 4.6 4.6 4.6 4.6 4.6 0 4.6 4.6 0 4.6 4.6 0 39/44 49/56 71/81 28/31 44/50 83/95 45/50 39/45 93/106 49/56 44/50 114/131 42/48 36/42 36/42 136/156 49/56 44/50 44/50 25/28 31/35 44/49 51/57 56/64 31/35 25/29 69/78 37/42 32/37 81/93 44/50 38/44 MAXIMUM CIRCUIT PROTECTION 40/45 50/60 80/90 30/35 45/50 90/100 45/50 40/45 100/110 50/60 45/50 125/150 45/50 40/45 40/45 150/175 50/60 45/50 45/50 25/30 35/35 45/50 60/60 60/70 35/35 25/30 70/80 40/45 35/40 90/100 45/50 40/45 *Values only. No single point kit available. NOTES: • Electric heater BTUH - (heater watts + motor watts) x 3.414 (see airflow table for motor watts.) • Supply circuit protective devices may be fuses or “HACR” type circuit breakers. • If non-standard fuse size is specified, use next size larger standard fuse size. • Largest motor load is included in single circuit or circuit 1 of multiple circuits. • Heater loads are balanced on 3 phase models with 3 or 6 heaters only. • No electrical heating elements are permitted to be used with A Voltage (115V) air handler. • J Voltage (230V) signal phase air handler is designed to be used with single or three phase 230 volt electric heaters. In the case of connecting 3 phase power to air handler terminal block without the heater, bring only two leads to terminal block, cap, insulate and fully secure the third lead. • Do not use 480 volts electrical heaters on 230 volts air handler. • Do not use 230 volts electrical heaters on 480 volts air handler. • If the kit is listed under both single and multiple circuits, the kit is shipped from factory as multiple circuits. For single phase application, Jumper bar kit RXBJ-A21 and RXBJ-A31 can be used to convert multiple circuits to a single supply circuit. Refer to Accessory Section for details. 19 4.6C HEATER KIT SUPPLEMENTAL INFORMATION AIR CONDITIONING DIVISION (-)HLA-HM4821JA MARK HEATER INSTALLED/ L’APPAREIL DE CHAUFFAGE DE MARQUE A INSTALLE If a heater kit is listed both Single and Multicircuit, the kit is shipped as a Multicircuit and will require a single point kit Only listed kits can be applied Contractor should “mark or check” the left column for the kit installed These are the required maximum and minimum circuit breaker sizes for overcurrent protection and should not be confused with the size of the breakers installed in the heater kit. Heater Kit Supplemental Information: What allows the manufacturer to use standard Circuit Breakers up to 60 amps inside the air handler, when using an approved Heater Kit? National Electric Code (Section 424-22b) and our UL requirements allow us to subdivide heating element circuits, of less than 48 amps, using breakers of not more than 60 amps and, additionally by, NEC 424-3b, a rating not less than 125 percent of the load and NEC 424-22c, which describes the supplementary overcurrent protection required to be factory-installed within, or on the heater. The breakers in the heater kit are not, and have never been, by NEC, intended to protect pwer wiring leading to the air handler unit. The breakers in the heating kit are for short circuit proteciton. All internal unit wiring, where the breakers apply, has been UL approved for short circuit protection. Ampacity, (not breaker size), determines supply circuit wire size. The ampacity listed on the unit rating plate and the Maximum and Minimum circuit breaker size (noted above) or in the units specification sheet or installation instructions provides the information to properly select wire and circuit breaker/protector size. The National Electric Code (NEC) specifies that the supply or branch circuit must be protected at the source. 20 5.0 AIRFLOW PERFORMANCE Airflow performance data is based on cooling performance with a coil and no filter in place. Select performance table for appropriate unit size, voltage and number of electric heaters to be used. Make sure external static applied to unit allows operation within the minimum and maximum limits shown in table below for both cooling and electric heat operation. For optimum blower performance, operate the unit in the .3 to .7 in W.C. external static range. Units with coils should be applied with a minimum of .1 in W.C. external static. 5.1 AIRFLOW OPERATING LIMITS Cabinet Size 17 17 21 24 Cooling BTUH x 1,000 Cooling Tons Nominal -018 1.5 -024 2 -030 2.5 -036 3 -042 3.5 -048 4 -048 4 -060 5 Heat Pump or Air Conditioning Maximum Heat/Cool CFM [L/s] (37.5 CFM [18 L/s]/1,000 BTUH) (450 CFM [212 L/s]/Ton Nominal) 675 [319] 900 [425] 1125 [531] 1350 [637] 1575 [743] 1800 [850] 1800 [850] 1930 [911] Heat Pump or Air Conditioning Nominal Heat/Cool CFM [L/s] (33.3 CFM [16 L/s]/1,000 BTUH) (400 CFM [189 L/s]/Ton Nominal) 600 [283] 800 [378] 1000 [472] 1200 [566] 1400 [661] 1600 [755] 1600 [755] 1800 [850] Heat Pump or Air Conditioning Minimum Heat/Cool CFM [L/s] (30.0 CFM [14 L/s]/1,200 BTUH) (360 CFM [170 L/s]/Ton Nominal) 540 [255] 720 [340] 900 [425] 1080 [510] 1260 [595] 1440 [680] 1440 [680] 1620 [765] Maximum kW Electric Heating & Minimum Electric Heat CFM [L/s] 10 500 [236] 10 650 [308] 15 865 [408] 15 1015 [480] 20 1200 [566] 20 1400 [660] Maximum Electric Heat Rise °F [°C] 85 [29] 85 [29] 85 [29] 85 [29] 85 [29] 85 [29] 20 25 1400 [660] 1730 [821] 85 [29] 85 [29] 21 5.2 240V AIRFLOW PERFORMANCE DATA – (-)HSA/(-)HSL (PSC MOTOR) Model Number Motor Speed From Factory Manufacturer Recommended Air Flow Range (Min / Max) CFM Blower Size/ Motor H.P. # of Speeds Motor Speed 0.10 [.02] 0.20 [.05] 0.30 [.07] 0.40 [.10] 0.50 [.12] 0.60 [.15] 0.70 [.17] Low 1817 No heater Low 240 V 517/711CFM [244/336 L/s] 10x6 1/5 [149] 2 Speed High Low 1817 with 13kw heater Low 240 V 2417 No heater Low 240 V 467/661 CFM [230/312 L/s] 10x6 1/5 [149] 2 Speed High Low 647/888 [305.419 L/s] 10x6 1/5 [149] 2 Speed High Low 2417 with 13kw heater Low 240 V 3017 No heater Low 240 V 617/638 [291/395 L/s] 10x6 1/5 [149] 2 Speed High Low 864/1004 [408/474 L/s] 10x8 1/4 [186] 2 Speed High 3017 with 18kw heater Low Low 240 V 814/904 CFM [384/427 L/s] 10x8 1/4 [186] 2 Speed High Low 3617/3621 No heater Low 240 V 1104/1248 CFM [521/589 L/s] 10x8 1/3 [249] 2 Speed High 3617/3621 with 18kw heater Low Low 240 V 1054/1148 CFM [497/542 L/s] 10x8 1/3 [249] 2 Speed High Low 4221 No heater Low 240 V 1241/1537 CFM [586/725 L/s] 10x10 1/2 [373] 2 Speed High 4221 with 20kw heater 22 Low Low 240 V 1225/1500 CFM [553/678 L/s] PSC CFM[L/s] Air Delivery/RPM/Watts-240 Volts External Static Pressure-Inches W.C. 10x10 1/2 [373] 2 Speed High CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts 668 [315] 541 180 — — — 638 [301] 571 171 — — — 817 [386] 616 239 — — — 787 [371] 646 230 — — — 1022 [482] 700 344 — — — 972 [459] 750 324 — — — 637 [301] 596 171 — — — 607 [286] 626 162 — — — 779 [368] 667 230 — — — 749 [353] 697 221 — — — 987 [466] 754 313 — — — 937 [442] 804 293 — — — 595 [281] 657 166 — — — 565 [267] 687 157 — — — 757 [357] 715 221 — — — 727 [343] 745 212 — — — 940 [444] 794 302 — — — 890 [420] 844 282 — — — 560 [264] 706 161 — — — 530 [250] 736 152 — — — 693 [327] 770 206 — — — 663 [313] 800 197 — — — 903 [426] 833 294 — — — 853 [403] 883 274 — — — 517 [244] 761 155 711 [336] 812 243 487 [230] 791 146 661 [312] 837 232 647 [305] 808 196 888 [419] 875 331 617 [291] 838 187 838 [395] 900 320 864 [408] 870 288 1004 [474] 924 364 814 [384] 920 268 904 [427] 949 334 — — — 662 [312] 853 227 — — — 612 [289] 878 216 — — — 828 [391] 908 313 — — — 778 [367] 933 302 — — — 951 [449] 953 352 — — — 851 [402] 978 322 — — — 614 [290] 890 210 — — — 564 [266] 915 199 — — — 774 [365] 958 301 — — — 724 [342] 983 290 — — — 883 [417] 975 344 — — — 783 [370] 1000 314 1229 [580] 1201[567] 1170 [552] 1141 [538] 1104 [521] — 788 833 872 909 951 — 466 462 427 406 395 — — — — — 1248 [589] 1194 [563] — — — — 1008 1028 — — — — 488 475 1179 [556] 1151 [543] 1120 [529] 1091 [515] 1054 [497] — 838 883 922 959 1001 — 446 442 407 386 375 — — — — — 1148 [542] 1094 [516] — — — — 1033 1053 — — — 1133 [535] 1042 454 — — — 1033 [487] 1067 — — — — 458 445 1526 [720] 1474 [696] 1427 [673] 1307 [617] 1241 [586] — 834 870 902 948 968 — 560 549 535 476 462 — — — — — 1537 [725] 1418 [669] — — — — 1072 1077 — — — — 860 835 1456 [687] 1404 [663] 1357 [640] 1237 [584] 1171 [553] — 886 906 925 959 992 — 542 524 505 468 431 — — — — — 1437 [678] 1318 [622] — — — — 1080 1090 — — — — 840 800 424 — — — 1334 [630] 1085 820 — — — 1234 [582] 1105 785 5.2 240V AIRFLOW PERFORMANCE DATA – (-)HSA/(-)HSL (PSC MOTOR) - continued Model Number Motor Speed From Factory Manufacturer Recommended Air Flow Range (Min / Max) CFM Blower Size/ Motor H.P. # of Speeds Motor Speed 0.10 [.02] 0.20 [.05] 0.30 [.07] 0.40 [.10] 0.50 [.12] 0.60 [.15] 0.70 [.17] Low 4821/4824 No heater Low 240 V 1572/1824 CFM [742/861 L/s] 10x10 3/4 [559] 2 Speed High Low 4821/4824 with 25kw heater Low 240 V 6024 No heater Low 240 V 1225/1500 [709/814 L/s] 10x10 3/4 [559] 2 Speed High Low 1766/1965 CFM [833/927 L/s] 11x11 3/4 [559] 2 Speed High 6024 with 30kw heater Low Low 240 V 1225/1500 PSC CFM[L/s] Air Delivery/RPM/Watts-240 Volts External Static Pressure-Inches W.C. 11x11 3/4 [559] 2 Speed High CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts 1741 [822] 878 785 — — — 1671 [789] 945 715 — — — 1944 [917] 764 779 — — — 1844 [870] 839 745 — — — 1719 [811] 920 757 — — — 1649 [778] 965 685 — — — 1912 [902] 803 763 — — — 1812 [855] 865 729 — — — 1667 [787] 950 707 — — — 1597 [754] 995 650 — — — 1860 [878] 838 747 — — — 1760 [831] 890 713 — — — 1628 [768] 981 667 — — — 1558 [735] 1025 630 — — — 1813 [856] 865 729 — — — 1713 [808] 913 696 — — — 1572 [742] 1007 641 1824 [861] 1102 871 1502 [709] 1050 610 1724 [814] 1116 810 1766 [833] 889 708 1965 [927] 943 828 1666 [786] 935 678 1865 [880] 987 788 — — — 1767 [834] 1112 830 — — — 1667 [787] 1119 780 — — — 1908 [900] 967 799 — — — 1808 [853] 1001 766 — — — 1653 [780] 1121 770 — — — 1553 [733] 1130 730 — — — 1854 [875] 977 795 — — — 1754 [828] 1014 744 NOTE: • All 208/240V PSC motors have voltage taps for 208 and 240 volts. • All 208/240V PSC motors are shipped on high speed and 240 volts. • If the application external static is less than 0.5” WC, adjust the motor speed to the low static speed as described below. - Unplug the black motor wire off the relay on the control board and plug in the red motor wire. - Replace the cap on the black motor wire. • Voltage change (208/240V motors): - Move the orange lead to transformer 208V tap from 240V tap. Replace the wire cap on 240V tap. - Unplug the purple motor wire off the transformer and plug in the yellow motor wire. - Replace the cap on the purple motor wire. • The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model. • The following formula can be used to calculate the approximate airflow, if a smaller (N kw) than the maximum heater kit is installed. Approximate Airflow = Airflow without heater - (Airflow without heater - Airflow with maximum heater) X (N kw/maximum heater kw) 23 5.3 115/208/480V AIRFLOW PERFORMANCE DATA – (-)HSA/(-)HSL (PSC MOTOR) Model Number Motor Speed From Factory Manufacturer Recommended Air Flow Range (Min / Max) CFM Blower Size/ Motor H.P. # of Speeds Motor Speed 0.10 [.02] 0.20 [.05] 0.30 [.07] 0.40 [.10] 0.50 [.12] 0.60 [.15] 0.70 [.17] Low 1817 No heater High 523/705CFM [247/333 L/s] 10x6 1/5 [149] 2 Speed High 1817 with 13kw heater Low High 487/661 CFM [230/312 L/s] 10x6 1/5 [149] 2 Speed High Low 2417 No heater High 647/888 [305.419 L/s] 10x6 1/5 [149] 2 Speed High 2417 with 13kw heater Low High 617/838 [291/395 L/s] 10x6 1/5 [149] 2 Speed High Low 3017 No heater High 864/1004 [408/474 L/s] 10x8 1/4 [186] 2 Speed High 3017 with 18kw heater Low High 814/904 CFM [384/427 L/s] 10x8 1/4 [186] 2 Speed High Low 3617/3621 No heater High 1104/1248 CFM [521/589 L/s] 10x8 1/3 [249] 2 Speed High 3617/3621 with 18kw heater Low High 1054/1148 CFM [497/542 L/s] 10x8 1/3 [249] 2 Speed High Low 4221 No heater High 1241/1537 CFM [586/725 L/s] 10x10 1/2 [373] 2 Speed High 4221 with 20kw heater 24 Low High 1225/1500 CFM [553/678 L/s] PSC CFM[L/s] Air Delivery/RPM/Watts-115/208/480 Volts External Static Pressure-Inches W.C. 10x10 1/2 [373] 2 Speed High CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts 681 [321] 541 193 — — — 651 [307] 571 184 — — — 875 [413] 648 259 — — — 845 [399] 678 250 — — — 1038 [490] 721 325 — — — 988 [466] 771 305 — — — 636 [300] 601 181 — — — 606 [286] 631 172 — — — 806 [380] 700 255 — — — 776 [366] 730 246 — — — 1010 [477] 771 314 — — — 960 [453] 821 294 — — — 606 [286] 670 173 — — — 576 [272] 700 164 — — — 787 [371] 745 243 — — — 757 [357] 775 234 — — — 976 [461] 799 303 — — — 926 [437] 849 283 — — — 567 [268] 714 164 — — — 537 [253] 744 155 — — — 739 [349] 794 234 — — — 709 [335] 824 225 — — — 925 [437] 848 290 — — — 875 [413] 898 270 — — — 523 [247] 768 157 705 [333] 815 239 493 [233] 798 148 655 [309] 840 228 682 [322] 827 227 897 [423] 906 332 652 [308] 857 218 847 [400] 931 321 883 [417] 880 286 1015 [479] 928 356 833 [393] 930 266 915 [432] 953 326 — — — 650 [307] 861 227 — — — 600 [283] 886 216 — — — 851 [402] 925 318 — — — 801 [378] 950 307 — — — 963 [454] 955 341 — — — 863 [407] 980 311 — — — 599 [283] 989 204 — — — 549 [259] 1014 193 — — — 765 [361] 955 306 — — — 715 [337] 980 295 — — — 890 [420] 974 329 — — — 790 [373] 999 299 1201 [567] 1170[552] 1141 [538] 1104 [521] 1062 [501] — 833 872 909 951 965 — 462 427 406 396 385 — — — — — 1194 [563] 1134 [535] — — — — 1024 1042 — — — — 475 454 1151 [543] 1120 [529] 1091 [515] 1054 [497] 1012 [478] — 883 922 959 1001 1015 — 442 407 386 376 365 — — — — — 1094 [516] 1034 [488] — — — — 1049 1067 — — — 1078 [509] 1060 417 — — — 978 [462] 1085 — — — — 445 424 1493 [705] 1449 [684] 1363 [643] 1287 [607] 1211 [571] — 822 858 885 931 958 — 540 519 506 484 459 — — — — — 1514 [714] 1411 [666] — — — — 1061 1069 — — — — 710 702 1423 [672] 1379 [651] 1293 [610] 1217 [574] 1141 [538] — 870 882 925 957 992 — 514 508 490 461 431 — — — — — 1414 [667] 1311 [619] — — — — 1067 1080 — — — — 700 678 387 — — — 1315 [621] 1078 677 — — — 1215 [573] 1094 665 5.3 115/208/480V AIRFLOW PERFORMANCE DATA – (-)HSA/(-)HSL (PSC MOTOR) - continued Model Number Motor Speed From Factory Manufacturer Recommended Air Flow Range (Min / Max) CFM Blower Size/ Motor H.P. # of Speeds Motor Speed 0.10 [.02] 0.20 [.05] 0.30 [.07] 0.40 [.10] 0.50 [.12] 0.60 [.15] 0.70 [.17] Low 4821/4824 No heater High 1572/1824 CFM [742/861 L/s] 10x10 3/4 [559] 2 Speed High 4821/4824 with 25kw heater Low High 1225/1500 [709/814 L/s] 10x10 3/4 [559] 2 Speed High Low 6024 No heater High 1766/1965 CFM [833/927 L/s] 11x11 3/4 [559] 2 Speed High 6024 with 30kw heater Low High 1225/1500 [553/678 L/s] PSC CFM[L/s] Air Delivery/RPM/Watts-115/208/480 Volts External Static Pressure-Inches W.C. 11x11 3/4 [559] 2 Speed High CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts 1711 [807] 863 765 — — — 1641 [774] 930 700 — — — 1866 [881] 764 778 — — — 1796 [848] 828 735 — — — 1689 [797] 905 737 — — — 1619 [764] 950 660 — — — 1833 [865] 803 756 — — — 1763 [832] 860 718 — — — 1637 [773] 935 687 — — — 1567 [739] 985 630 — — — 1806 [852] 824 733 — — — 1736 [819] 878 705 — — — 1598 [754] 966 647 — — — 1528 [721] 1015 600 — — — 1772 [836] 856 715 — — — 1702 [803] 890 695 — — — 1542 [728] 992 621 1787 [843] 1089 695 1472 [695] 1041 580 1687 [796] 1095 670 1710 [807] 886 701 1967 [928] 948 850 1640 [774] 1001 678 1867 [881] 989 818 — — — 1679 [792] 1098 665 — — — 1579 [745] 1107 635 — — — 1916 [904] 959 827 — — — 1816 [857] 1005 795 — — — 1575 [743] 1110 630 — — — 1475 [696] 1120 615 — — — 1863 [879] 991 816 — — — 1763 [832] 1020 780 NOTE: • All 208/240V PSC motors have voltage taps for 208 and 240 volts. • All 208/240V PSC motors are shipped on high speed and 240 volts. • All 115V PSC motors are shipped on high speed. • If the application external static is less than 0.5” WC, adjust the motor speed to the low static speed as described below: - Unplug the black motor wire off the relay on the control board and plug in the red motor wire. - Replace the cap on the black motor wire. • Voltage change (208/240V motors): - Move the orange lead to transformer to 208V tap from 240V tap. Replace the wire cap on 240V tap. - Unplug the purple motor wire off the transformer and plug in the yellow motor wire. - Replace the cap on the purple motor wire. • All 480V PSC motors are shipped on high speed. • If the application external static is less than 0.5” WC, adjust the motor speed to the low static speed as described below for 3-ton through 4-ton air handlers. - Unplug the black motor wire off the relay and remove the cap from the red motor wire. - Plug the red motor wire to the relay and connect the black motor wire with the yellow motor wire. • For 5-ton air handler, unplug the black motor wire off the relay and plug in the red motor wire, then cap the black motor wire. There is no yellow motor wire on 5-ton air handler. WARNING: Do not connect red motor wire with yellow motor wire in any circumstance on 480V PSC motors. Connecting red motor wire with yellow motor wire will result in permanent motor damage. • The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model. • The following formula can be used to calculate the approximate airflow, if a smaller (N kw) than the maximum heater kit is installed. Approximate Airflow = Airflow without heater - (Airflow without heater - Airflow with maximum heater) X (N kw/maximum heater kw) 25 5.4 115/208/240V AIRFLOW PERFORMANCE DATA – (-)HLA/(-)HLL (X-13 MOTOR) Model Number Tonnage Application Motor Speed From Factory Manufacturer Recommended Air Flow Range (Min / Max) CFM Blower Size/ Motor H.P. # of Speeds Motor Speed 0.10 [.02] 0.20 [.05] 0.30 [.07] 0.40 [.10] 0.50 [.12] 0.60 [.15] 0.70 [.17] 2 2417 No heater 1.5 5 509/681CFM [240/321 L/s] 10x6 1/3 [249] 5 Speed 3 2417 with 13kw heater 2 1.5 5 490/666 CFM [231/314 L/s] 10x6 1/3 [249] 5 Speed 3 4 2417 No heater 2.0 5 730/651 CFM [345/307 L/s] 10x6 1/3 [249] 5 Speed 5 2417 with 13kw heater 4 2.0 5 711/626 CFM [336/295 L/s] 10x6 1/3 [249] 5 Speed 5 2 3617 No heater 2.5 5 935/1084 CFM [441/512 L/s] 10x8 1/2 [373] 5 Speed 3 3617 with 18kw heater 2 2.5 5 910/1059 CFM [429/500 L/s] 10x8 1/2 [373] 5 Speed 3 4 3617 No heater 3.0 5 1130/1275 CFM [533/602 L/s] 10x8 1/2 [373] 5 Speed 5 3617 with 18kw heater 4 3.0 5 1105/1250 CFM [521/590 L/s] 10x8 1/2 [373] 5 Speed 5 2 4821 No heater 3.5 5 1337/1447 CFM [631/683 L/s] 10x10 3/4 [559] 5 Speed 3 4221 with 20kw heater 26 2 3.5 5 1297/1333 CFM [612/629 L/s] X-13 CFM[L/s] Air Delivery/RPM/Watts-115/208/240 Volts External Static Pressure-Inches W.C. 10x10 3/4 [559] 5 Speed 3 CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts 689 [325] 580 66 — — — 670 [316] 608 75 — — — 875 [413] 679 121 — — — 856 [404] 707 130 — — — 1093 [516] 671 153 — — — 1068 [504] 711 164 — — — 644 [304] 602 [284] 633 683 84 86 — — — — — — 625 [295] 583 [275] 661 711 93 95 — — — — — — 839 [396] 804 [379] 724 765 131 135 — — — — — — 820 [387] 785 [370] 752 793 140 144 — — — — — — 1050 [496] 1017 [480] 725 764 168 174 — — — — — — 1025 [484] 992 [468] 765 804 179 185 — — — — — — 563 [266] 728 88 — — — 544 [257] 756 97 — — — 762 [360] 810 142 — — — 743 [351] 838 151 — — — 977 [461] 809 180 — — — 952 [449] 849 191 — — — 509 [240] — 781 — 91 — 681 [321] 644 [304] 835 879 136 143 490 [231] — 809 — 100 — 666 [314] 629 [297] 855 899 144 151 730 [345] — 852 — 143 — 862 [407] 828 [391] 904 940 203 215 711 [336] — 880 — 152 — 837 [395] 803 [379] 924 960 211 223 935 [441] — 852 — 188 — 1084 [512] 1040 [491] 896 936 249 257 910 [429] — 892 — 199 — 1059 [500] 1015 [479] 936 976 260 268 — — — 603 [285] 916 152 — — — 588[277] 936 160 — — — 801 [378] 970 220 — — — 776 [366] 990 228 — — — 1001 [472] 971 261 — — — 976 [461] 1011 272 1270 [599] 1237 [584] 1199 [566] 1165 [550] 1130 [533] — 775 816 846 882 926 — 237 249 259 268 277 — — — — — 1275 [602] 1244 [587] — — — — 963 999 — — — — 338 348 1245 [588] 1212 [572] 1174 [554] 1140 [538] 1105 [521] — 815 856 886 922 966 — 248 260 270 279 288 — — — — — 1250 [590] 1219 [575] — — — — 1003 1039 — — — 1211 [571] 1029 363 — — — 1186 [560] 1069 — — — — 349 359 1473 [695] 1442 [681] 1401 [661] 1373 [648] 1337 [631] — 781 825 867 905 949 — 257 271 303 307 315 — — — — — 1447 [683] 1433 [676] — — — — 987 1034 — — — — 394 406 1433 [676] 1402 [662] 1361 [642] 1333 [629] 1297 [612] — 831 875 919 954 989 — 277 295 313 319 325 — — — — — 1333 [629] 1300 [613] — — — — 1011 1046 — — — — 350 364 374 — — — 1402 [662] 1065 405 — — — 1267 [598] 1080 377 5.4 115/208/240V AIRFLOW PERFORMANCE DATA – (-)HLA/(-)HLL (X-13 MOTOR) - continued Model Number Tonnage Application Motor Speed From Factory Manufacturer Recommended Air Flow Range (Min / Max) CFM Blower Size/ Motor H.P. # of Speeds Motor Speed 0.10 [.02] 0.20 [.05] 0.30 [.07] 0.40 [.10] 0.50 [.12] 0.60 [.15] 0.70 [.17] 4 4821 No heater 4.0 5 1535/1654 CFM [724/781 L/s] 10x10 3/4 [559] 5 Speed 5 4821 with 25kw heater 4 4.0 5 1495/1614 CFM [706/762 L/s] 10x10 3/4[559] 5 Speed 5 2 4824 No heater 4.0 3 1545/1732 CFM [729/817 L/s] 11x11 3/4 [559] 5 Speed 3 4824 with 25kw heater 2 4.0 3 1505/1692 CFM [710/798 L/s] 11x11 3/4 [559] 5 Speed 3 4 6024 No heater 5.0 5 1739/1905 CFM [821/899 L/s] 11x11 3/4 [559] 5 Speed 5 6024 with 33kw heater 4 5.0 5 1699/1865 CFM [802/880 L/s] X-13 CFM[L/s] Air Delivery/RPM/Watts-115/208/240 Volts External Static Pressure-Inches W.C. 11x11 3/4 [559] 5 Speed 5 CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts CFM RPM Watts 1665 [786] 853 351 — — — 1625 [767] 894 389 — — — 1748 [825] 660 297 — — — 1708 [806] 680 305 — — — 1902 [898] 712 389 — — — 1862 [879] 750 410 — — — 1631 [770] 893 387 — — — 1591 [751] 932 400 — — — 1669 [788] 698 311 — — — 1629 [769] 736 330 — — — 1862 [879] 749 409 — — — 1822 [860] 790 420 — — — 1601 [756] 934 401 — — — 1561 [737] 970 410 — — — 1639 [773] 734 326 — — — 1599 [755] 760 341 — — — 1809 [854] 787 419 — — — 1769 [835] 810 430 — — — 1572 [742] 968 406 — — — 1532 [723] 1020 430 — — — 1599 [755] 762 340 — — — 1559 [736] 790 350 — — — 1781 [840] 815 432 — — — 1741 [822] 850 455 — — — 1535 [724] 1015 422 1654 [781] 1036 500 1495 [706] 1052 450 1614 [762] 1085 514 1545 [729] 795 353 1732 [817] 840 448 1505 [710] 820 361 1692 [798] 865 460 1739 [821] 856 459 1905 [899] 894 565 1699 [802] 880 479 1865 [880] 920 565 — — — 1624 [766] 1078 513 — — — 1584 [748] 1090 520 — — — 1683 [794] 872 467 — — — 1643 [775] 890 470 — — — 1866 [881] 924 570 — — — 1826 [862] 945 587 — — — 1563 [738] 1095 523 — — — 1523 [719] 1105 530 — — — 1630 [769] 899 480 — — — 1590 [750] 1014 481 — — — 1832 [865] 950 592 — — — 1792 [846] 970 610 NOTE: X-13 motor speed changes All X-13 motors have 5 speed tabs. Speed tab 1 is for continuous fan. Speed tab 2 (low static) and Speed tab 3 (high static) are for lower tonnage. Speed tab 4 (low static) and Speed tab 5 (high static) are for higher tonnage. X-13 air handlers are always shipped from factory at speed tab 5, except for -4824, which is set at speed tab 3. For instance, RHLA-HM2417JA is always shipped at high static 2-ton airflow (Speed tab 5). To change to 1.5-ton airflow, move the blue wire to Speed tab 2 or 3 on the X-13 motor. The low static Speed tab 2 (lower tonnage) and 4 (higher tonnage) are used for external static below 0.5” WC. The high static Speed tab 3 (lower tonnage) and 5 (higher tonnage) are used for external static exceeding 0.5” WC. Move the blue wire to the appropriate speed tab as required by the application needs. • The airflow for continuous fan (Speed tab 1) is always set at 50% of the Speed tab 4. • The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model. • The following formula can be used to calculate the approximate airflow, if a smaller (N kw) than the maximum heater kit is installed. Approximate Airflow = Airflow without heater - (Airflow without heater - Airflow with maximum heater) X (N kw/maximum heater kw) 27 6.0 DUCTWORK Field ductwork must comply with the National Fire Protection Association NFPA 90A, NFPA 90B and any applicable local ordinance. ! WARNING Do not, under any circumstances, connect return ductwork to any other heat producing device such as fireplace insert, stove, etc. Unauthorized use of such devices may result in fire, carbon monoxide poisoning, explosion, personal injury or property damage. Sheet metal ductwork run in unconditioned spaces must be insulated and covered with a vapor barrier. Fibrous ductwork may be used if constructed and installed in accordance with SMACNA Construction Standard on Fibrous Glass Ducts. Ductwork must comply with National Fire Protection Association as tested by U/L Standard 181 for Class I Air Ducts. Check local codes for requirements on ductwork and insulation. • Duct system must be designed within the range of external static pressure the unit is designed to operate against. It is important that the system airflow be adequate. Make sure supply and return ductwork, grills, special filters, accessories, etc. are accounted for in total resistance. See airflow performance tables in this manual. • Design the duct system in accordance with “ACCA” Manual “D” Design for Residential Winter and Summer Air Conditioning and Equipment Selection. Latest editions are available from: “ACCA” Air Conditioning Contractors of America, 1513 16th Street, N.W., Washington, D.C. 20036. If duct system incorporates flexible air duct, be sure pressure drop information (straight length plus all turns) shown in “ACCA” Manual “D” is accounted for in system. • Supply plenum is attached to the 3/4” duct flanges supplied with the unit. Attach flanges around the blower outlet. IMPORTANT: If an elbow is included in the plenum close to the unit, it must not be smaller than the dimensions of the supply duct flange on the unit. • IMPORTANT: The front flange on the return duct if connected to the blower casing must not be screwed into the area where the power wiring is located. Drills or sharp screw points can damage insulation on wires located inside unit. • Secure the supply and return ductwork to the unit flanges, using proper fasteners for the type of duct used and tape the duct-to-unit joint as required to prevent air leaks. 7.0 REFRIGERANT CONNECTIONS Keep the coil connections sealed until refrigerant connections are to be made. See the Installation Instructions for the outdoor unit for details on line sizing, tubing installation, and charging information. Coil is shipped with a low (5 - 10 PSIG) pressure charge of dry nitrogen. Evacuate the system before charging with refrigerant. Install refrigerant tubing so that it does not block service access to the front of the unit. Nitrogen should flow through the refrigerant lines while brazing. Use a brazing shield to protect the cabinet’s paint from being damaged by torch flames. After the refrigerant connections are made, seal the gap around the connections with pressure sensitive gasket. If necessary, cut the gasket into two pieces for a better seal (See Figure 4.) 7.1 TEV SENSING BULB IMPORTANT: DO NOT perform any soldering with the TEV bulb attached to any line. After soldering operations have been completed, clamp the TEV bulb securely on the suction line at the 10 to 2 o’clock position with the strap provided in the parts bag. Insulate the TEV sensing bulb and suction line with the provided pressure sensitive insulation (size 4” x 7”) and secure with provided wire ties. IMPORTANT: TEV sensing bulb should be located on a horizontal section of suction line, just outside of coil box. 7.2 CONDENSATE DRAIN TUBING Consult local codes or ordinances for specific requirements. IMPORTANT: When making drain fitting connections to the drain pan, use a thin layer of Teflon paste, silicone or Teflon tape and install hand tight. 28 FIGURE 8 CONDENSATE DRAIN TRAP DO NOT OPERATE UNIT WITHOUT CONDENSATE DRAIN TRAP. UNIT 3'' 3'' DO NOT OVERTIGHTEN DRAIN FITTING UNIT MUST BE SLIGHTLY INCLINED TOWARD DRAIN CONNECTION. IMPORTANT: When making drain fitting connections to drain pan, do not overtighten. Overtightening fittings can split pipe connetions on the drain pan. • Install drain lines so they do not block service access to front of the unit. Minimum clearance of 24 inches is required for filter, coil or blower removal and service access. • Make sure unit is level or pitched slightly toward primary drain connection so that water will drain completely from the pan. (See Figure 8.) • Do not reduce drain line size less than connection size provided on condensate drain pan. • All drain lines must be pitched downward away from the unit a minimum of 1/8” per foot of line to ensure proper drainage. • Do not connect condensate drain line to a closed or open sewer pipe. Run condensate to an open drain or outdoors. • The drain line should be insulated where necessary to prevent sweating and damage due to condensate forming on the outside surface of the line. • Make provisions for disconnecting and cleaning of the primary drain line should it become necessary. Install a 3 in. trap in the primary drain line as close to the unit as possible. Make sure that the top of the trap is below connection to the drain pan to allow complete drainage of pan (See Figure 8). • Auxiliary drain line should be run to a place where it will be noticeable if it becomes operational. Occupant should be warned that a problem exists if water should begin running from the auxiliary drain line. • Plug the unused drain connection with the plugs provided in the parts bag, using a thin layer of teflon paste, silicone or teflon tape to form a water tight seal. • Test condensate drain pan and drain line after installation is complete. Pour water into drain pan, enough to fill drain trap and line. Check to make sure drain pan is draining completely, no leaks are found in drain line fittings, and water is draining from the termination of the primary drain line. 7.3 DUCT FLANGES Field-installed duct flanges (4 pieces) are shipped with units. Install duct flanges as needed on top of the unit. (See Figure 3.) 8.0 AIR FILTER (not factory-installed) • External filter or other means of filtration is required. Units should be sized for a maximum of 300 feet/min. air velocity or that recommended for the type filter installed. Filter application and placement are critical to airflow, which may affect the heating and cooling system performance. Reduced airflow can shorten the life of the system’s major components, such as motor, limits, elements, heat relays, evaporator coil or compressor. Consequently, we recommend that the return air duct system have only one filter location. For systems with a return air filter grill or multiple filter grills, can have a filter installed at each of the return air openings. If high efficiency filters or electronic air cleaners are used in the system, it is important that the airflow is not reduced to maximize system performance and life. Always verify that the system’s airflow is not impaired by the filtering system that has been installed, by performing a temperature rise and temperature drop test. 29 IMPORTANT: DO NOT DOUBLE FILTER THE RETURN AIR DUCT SYSTEM. DO NOT FILTER THE SUPPLY AIR DUCT SYSTEM. ! WARNING Do not operate the system without filters. A portion of the dust entrained in the air may temporarily lodge in the duct runs and at the supply registers. Any circulated dust particles could be heated and charred by contact with the air handler elements. This residue could soil ceilings, walls, drapes, carpets and other articles in the house. Soot damage may occur with filters in place, when certain types of candles, oil lamps or standing pilots are burned. 9.0 SEQUENCE OF OPERATION 9.1 COOLING (COOLING ONLY OR HEAT PUMP) • When the thermostat “calls for cooling,” the circuit between R and G is completed, causing the blower relay (BR) to energize. The N.O. contacts will close, causing the indoor blower motor (IBM) to operate. The circuit between R and Y is also completed: This circuit closes the contactor (CC) in the outdoor unit starting the compressor (COMP) and outdoor fan motor (OFM). 9.2 HEATING (ELECTRIC HEAT ONLY) • When the thermostat “calls for heat,” the circuit between R and W is completed, and the heater sequencer (HR1) is energized. The heating elements (HE) and the indoor blower motor (IBM) will come on. Units with a second heater sequencer (HR2) can be connected with the first sequencer (HR1) to W on the thermostat sub-base or connected to a second stage W2 on the sub-base. 9.3 HEATING (HEAT PUMP) • When the thermostat “calls for heat,” the circuits between R and B, R and Y and R and G are completed. Circuit R and B energizes the reversing valve (RV) switching it to the heating position (remains energized as long as selector switch is in “heat” position). Circuit R and Y energizes the contactor (CC) starting the outdoor fan motor (OFM) and compressor (COMP). Circuit R and G energizes the blower relay (BR) starting the indoor blower motor (IBM). • If the room temperature should continue to fall, circuit R and W is completed by the second-stage heat room thermostat. Circuit R-W energizes a heat sequencer (HR ). The completed circuit will energize supplemental electric heat. Units with a second heater sequencer (HR ) can be connected with first sequencer (HR ) to W on thermostat or connected to a third heating stage W on the thermostat sub-base. A light on the thermostat indicates when supplemental heat is being energized. 2 2 2 1 1 2 2 9.4 BLOWER TIME DELAY (HEATING OR COOLING) • All models are equipped with a blower time delay (BTD) in lieu of a blower relay (BR) (see wiring diagram). The blower will run for 30 seconds after the blower time delay (BTD) is de-energized. 9.5 DEFROST (DEFROST HEAT CONTROL) • For sequence of operation for defrost controls, see outdoor heat pump installation instructions. • Supplemental heat during defrost can be provided by connecting the purple (PU) pigtail in the outdoor unit to the W on the thermostat. This will complete the circuit between R and W through a set of contacts in the defrost relay (DR) when the outdoor heat pump is in defrost. This circuit, if connected, will help prevent cold air from being discharged from the indoor unit during defrost. • For most economical operation, if cold air is not of concern during defrost, the purple wire can be left disconnected. Supplemental heat will then come on only when called for by second stage room thermostat. 30 9.6 EMERGENCY HEAT (HEATING HEAT PUMP) • If selector switch on thermostat is set to the emergency heat position, the heat pump will be locked out of the heating circuit, and all heating will be electric heat. Jumper should be placed between W and E on the thermostat sub-base so that the electric heat control will transfer to the first stage heat on the thermostat. This will allow the indoor blower to cycle on and off with the electric heat when the fan switch is in the auto position. 2 9.7 ROOM THERMOSTAT (ANTICIPATOR SETTING) See instructions with outdoor section, condensing unit or heat pump for recommended room thermostats. • On units with one electric heat sequencer (HR ) (see wiring diagram on unit), heat anticipator setting should be .16. • On units with two electric heat sequencers (HR & HR ) (see wiring diagram on unit), heat anticipator setting should be .32 if both are connected to same stage on thermostat. Setting should be .16 if (HR &HR ) are connected to separate stages. NOTE: Some thermostats contain a fixed, non-adjustable heat anticipator. Adjustment is not permitted. • The thermostat should be mounted 4 to 5 feet above the floor on an inside wall of the living room or a hallway that has good air circulation from the other rooms being controlled by the thermostat. It is essential that there be free air circulation at the location of the same average temperature as other rooms being controlled. Movement of air should not be obstructed by furniture, doors, draperies, etc. The thermostat should not be mounted where it will be affected by drafts, hot or cold water pipes or air ducts in walls, radiant heat from fireplace, lamps, the sun, T.V. or an outside wall. See instruction sheet packaged with thermostat for mounting and installation instructions. 1 1 1 2 2 10.0 CALCULATIONS 10.1 CALCULATING TEMPERATURE RISE • The formula for calculating air temperature rise for electric resistance heat is: 3.16 x Watts Temperature Rise °F = CFM Where: 3.16 = Constant, CFM = Airflow 10.2 CALCULATING BTUH HEATING CAPACITY • The formula for calculating BTUH heating capacity for electric resistance heat is: BTUH Heating = Watts x 3.412 Where: 1 kW = 1000 Watts, 3.412 = Btuh/Watt 10.3 CALCULATING AIRFLOW CFM • The formula for calculating airflow using temperature rise and heating BTUH for units with electric resistance heat is: CFM = Heating BTUH 1.08 x Temp. Rise 10.4 CALCULATING CORRECTION FACTOR • For correction of electric heat output (kW or BTUH) or temperature rise at voltages other than rated voltage multiply by the following correction factor: Correction Factor = Applied Voltage Rated Voltage 2 2 31 11.0 PRE-START CHECKLIST PRE-START CHECKLIST ❍ YES ❍ NO Is unit properly located, level, secure and serviceable? ❍ YES ❍ NO Has auxiliary pan been provided under the unit with separate drain? (Units installed above a finished ceiling). ❍ YES ❍ NO Is condensate line properly sized, run, trapped, pitched and tested? ❍ YES ❍ NO Is ductwork correctly sized, run, taped and insulated? ❍ YES ❍ NO Have all cabinet openings and wiring been sealed with caulking? ❍ YES ❍ NO Is the filter clean, in place and of adequate size? ❍ YES ❍ NO Is the wiring tight, correct and to the wiring diagram? ❍ YES ❍ NO Is the unit properly grounded and protected (fused)? ❍ YES ❍ NO Is the thermostat heat anticipator been set properly? ❍ YES ❍ NO Is the unit circuit breaker(s) rotated properly “on” up - “off” down? ❍ YES ❍ NO Are the unit circuit breaker(s) line lug cover(s) in place? ❍ YES ❍ NO Are all access panels in place and secure? Refer to outdoor unit installation instructions for system start-up instructions and refrigerant charging instructions. 12.0 MAINTENANCE For continuing high performance, and to minimize possible equipment failure, it is essential that periodic maintenance be performed on this equipment. Consult your local dealer as to the proper frequency of maintenance and the availability of a maintenance contract IMPORTANT: Before performing any service or maintenance procedures, see the “Safety Information” section at the front of this manual. ! WARNING Units with circuit breaker(s) meet requirements as a service disconnect switch, however, if access is required to the line side (covered) of the circuit breaker, this side of the breaker(s) will be energized with the breaker(s) de-energized. Contact with the line side can cause electrical shock resulting in personal injury or death. 12.1 AIR FILTER (NOT FACTORY-INSTALLED) Check the system filter every ninety days or as often as found to be necessary and if obstructed, clean or replace at once. FILTER MAINTENANCE Have your qualified installer, service agency or HVAC professional instruct you on how to access your filters for regular maintenance. IMPORTANT: Do not operate the system without a filter in place. • New filters are available from your local distributor. 32 12.2 INDOOR COIL - DRAIN PAN - DRAIN LINE Inspect the indoor coil once each year for cleanliness and clean as necessary. In some cases, it may be necessary to remove the filter and check the return side of the coil with a mirror and flashlight. IMPORTANT: Do not use caustic household drain cleaners, such as bleach, in the condensate pan or near the indoor coil. Drain cleaners will quickly damage the indoor coil. 12.3 BLOWER MOTOR AND WHEEL Inspect the blower motor and wheel for cleanliness. It should be several years before it would become necessary to clean the blower motor and wheel. • If it becomes necessary to remove the blower assembly from the unit, see instructions on removal and disassembly of motor, blower and heater parts. • The blower motor and wheel may be cleaned by using a vacuum with a soft brush attachment. Remove grease with a mild solvent such as hot water and detergent. Be careful not to disturb the balance weights (clips) on the blower wheel blades. Do not drop or bend wheel as balance will be affected. 12.4 LUBRICATION The blower motor sleeve bearings are pre-lubricated by the motor manufacturer and do not have oiling ports. Motor should be run for an indefinite period of time without additional lubrication. 12.5 BLOWER ASSEMBLY REMOVAL AND REPLACEMENT Removing the blower assembly is not required for normal service and maintenance. Removal is necessary for replacement of defective parts such as motor, blower wheel. After extended use, removal of the blower assembly may become necessary for a thorough cleaning of the blower motor and wheel. ! WARNING If removal of the blower assembly is required, all disconnect switches supplying power to the equipment must be de-energized and locked (if not in sight of unit) so the field power wires can be safely removed from the blower assembly. Failure to do so can cause electrical shock resulting in personal injury or death. • Mark field power supply wiring (for replacement) attached to terminal block or circuit breaker(s) on blower assembly. Remove wiring from terminal block or circuit breaker(s). • Mark low voltage control wiring (for replacement) where attached to unit control pigtails on right side of blower housing. Remove wire nuts attaching field control wiring to unit control pigtails. • Remove 4 screws holding blower assembly to front channel of cabinet and pull blower assembly from cabinet. • To replace blower assembly, slide blower assembly into blower deck. Make sure blower assembly engages lances in deck properly. If assembly hangs up, check to make sure top and bottom are lined up in proper locations. • Slide blower assembly to back of cabinet and make sure it is completely engaged. • Replace 4 screws holding blower assembly to front channel of cabinet. Take care not to strip screws, just snug into place. • Replace low voltage control wiring with wire nuts and make sure wiring is to wiring diagram and a good connection has been made. • Replace field power wiring to terminal block or circuit breaker(s) on control area of blower assembly. Make sure wires are replaced as they were, check wiring diagram if necessary. Tighten supply power wiring securely to terminals lugs. • Make sure wiring is within cabinet and will not interfere with access door. Make sure proper separation between low voltage control wiring and field power wiring has been maintained. • Replace blower assembly control access panel before energizing equipment. 33 12.6 MOTOR REPLACEMENT With the blower assembly removed, the indoor blower motor can be removed and replaced using the following procedure: • Remove motor leads from the motor capacitor and blower relay. Note lead locations for ease of reassembly. Pull leads from plastic bushing in blower side. • Loosen the set screw holding blower wheel onto the motor shaft. Shaft extends through blower hub so that a wrench can be used on the extended shaft to break the shaft loose if necessary. Be careful not to damage shaft. A wheel puller can be used on the groove in the blower hub if necessary. • Remove 4 metal screws holding motor mounts to blower side and remove motor from blower assembly. • To install new motor, remove 1 screw holding motor mounts to motor shell and remove mounts (four) from motor. • Install (four) motor mounts to motor using same screw or screws supplied with replacement motor. ! WARNING To avoid electrical shock which can result in personal injury or death, use only the screws furnished in the motor shell mounting holds. Screws are #8-18 x .25 in. long blunt nose thread forming. Screws longer than 1/4 in. may contact the motor winding. • To reassemble, insert motor shaft through hub in blower wheel and orient motor to original position with motor leads and motor label to front of blower (control area). • Reassemble 12 sheet metal screws through motor mounts into blower side. Do not overtorque screws, blower side is light gage sheet metal, just snug screws tight enough to hold motor mounts in position. • Turn motor shaft so that flat on shaft is located under blower wheel setscrew, and blower wheel is centered in blower housing with the same distance on each side between the inlet venturi and outside of blower wheel. Tighten setscrew on motor shaft. Turn wheel by hand to make sure it runs true without hitting blower sides. • Reassemble motor wiring to capacitor and blower relay making sure that wires match wiring diagram and are tight and secure. 12.7 BLOWER WHEEL REPLACEMENT With the blower assembly removed and the motor assembly removed (see above instructions), remove the 4 screws holding the blower wrap (cutoff) to the blower sides. • With wrap (cutoff) screws removed, cut off end of blower wrap will spring up. Lifting wrap blower wheel is removed through the discharge opening in the blower housing. • To replace, make sure wheel is oriented properly with hub to the opposite side from the motor. Lift blower wrap and insert blower wheel through discharge opening in the blower housing. • Hold blower wrap down into position and replace two screws holding blower wrap to blower sides. • See motor replacement and blower assembly instructions for remaining assembly procedure. 13.0 REPLACEMENT PARTS Any replacement part used to replace parts originally supplied on equipment must be the same as or an approved alternate to the original part supplied. The manufacturer will not be responsible for replacement parts not designed to physically fit or operate within the design parameters the original parts were selected for. These parts include but are not limited to: Circuit breakers, heater controls, heater limit controls, heater elements, motor, motor capacitor, blower relay, control transformer, blower wheel, filter, indoor coil and sheet metal parts. 34 When ordering replacement parts, it is necessary to order by part number and include with the order the complete model number and serial number from the unit data plate. (See parts list for unit component part numbers). 14.0 ACCESSORIES-KITS-PARTS • Combustible Floor Base RXHB- for downflow applications. Model Cabinet Size Combustible Floor Base Model Number 17 21 24 RXHB-17 RXHB-21 RXHB-24 • Jumper Bar Kit 3 Ckt. to 1 Ckt. RXBJ-A31 is used to convert single phase multiple three circuit units to a single supply circuit. Kit includes cover and screw for line side terminals. • Jumper Bar Kit 2 Ckt. to 1 Ckt. RXBJ-A21 is used to convert single phase multiple two circuit units to a single supply circuit. Kit includes cover and screw for line side terminals. NOTE: No jumper bar kit is available to convert three phase multiple two circuit units to a single supply circuit. • External Filter Base RXHF- (See Figure 9) Model Cabinet Size Filter Size 17 21 24 16 x 20 [406 x 508] 20 x 20 [508 x 508] 25 x 20 [635 x 508] Part Number RXHF-17 RXHF-21 RXHF-24 Accommodate 1” or 2” filter A B 15.70 19.20 22.70 17.50 21.00 25.50 • External Filter Rack: RXHF-B (See Figure 9) FIGURE 9 EXTERNAL FILTER BASE: RXHF- Model Cabinet Size 17 21 24 Filter Size 16 x 20 20 x 20 25 x 20 Part Number RXHF-B17 RXHF-B21 Accommodate 1” filter RXHF-B24 A 16.90 20.40 25.00 B 20.77 20.77 21.04 35 FIGURE 10 EXTERNAL FILTER RACK: RXHF- B17, B21, B24 ➦ ➦ 1.50 A B • Horizontal Adapter Kit RXHHThis horizontal adapter kit is used to convert Upflow/Downflow only models to horizontal flow. See the following table to order proper horizontal adapter kit. Coil Model 2414 2417 3617/3621 4821/4824 6024 Horizontal Adapter Kit Model Number (Single Qty.) RXHH-A01 RXHH-A02 RXHH-A03 RXHH-A04 RXHH-A05 Horizontal Adapter Kit Model Number (10-pak Qty.) RXHH-A01x10 RXHH-A02x10 RXHH-A03x10 RXHH-A04x10 RXHH-A05x10 • Auxiliary Horizontal Overflow Pan RXBM- 36 Nominal Cooling Capacity Tons Auxiliary Horizontal Overflow Pan Accessory Model Number 11⁄2 - 3 RXBM-AC48 31⁄2 - 5 RXBM-AC61 CM 0707