Installation Instructions

Transcription

Installation Instructions
INSTALLATION INSTRUCTIONS
AIR HANDLERS
FEATURING R-22 REFRIGERANT:
(-)HLA High Efficiency
(-)HSA Standard Efficiency
FEATURING EARTH-FRIENDLY R-410A REFRIGERANT:
refrigerant
(-)HLL High Efficiency
(-)HSL Standard Efficiency
!
RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION!
! WARNING
!
▲WARNING
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO
These
instructions
are intended
asPERSONNEL
an aid to qualified
licensed
QUALIFIED,
LICENSED
SERVICE
FOR PROPER
service
personnel
for properAND
installation,
adjustment
and
INSTALLATION,
ADJUSTMENT
OPERATION
OF THIS UNIT.
operation
of this unit.
Read these instructions
thoroughly
before
READ THESE
INSTRUCTIONS
THOROUGHLY
BEFORE
attempting
installation
or operation.
Failure
to follow
ATTEMPTING
INSTALLATION
OR OPERATION.
FAILURE
TO these
FOLinstructions
result in improper
installation,
adjustment,
LOW THESEmay
INSTRUCTIONS
MAY RESULT
IN IMPROPER
service
or maintenance
possibly
resulting
fire, electrical
INSTALLATION,
ADJUSTMENT,
SERVICE
ORinMAINTENANCE
shock,
property
damage, personal
injuryELECTRICAL
or death.
POSSIBLY
RESULTING
IN FIRE,
SHOCK,
PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
ISO 9001:2000
DO NOT DESTROY THIS MANUAL
PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE BY A SERVICEMAN
92-20521-32-04
SUPERSEDES 92-20521-32-03
TABLE OF CONTENTS
1.0 SAFETY INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.0 GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1 Important Information About Efficiency and Indoor Air Quality. . . . . . . . . . . . 5
2.2 Receiving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.3 Clearances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.4 Model Number Explanation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.4A Available Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.5 Dimensions and Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.0 APPLICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.1 Vertical Upflow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.2 Vertical Downflow. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.3 Horizontal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.4 Installation in an Unconditioned Space . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.0 ELECTRICAL WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.1 Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.2 Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.3 Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.4 Copper Wire Size. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.5 Blower Motor Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.5A Blower Motor Electrical Data: (-)HSA/(-)HSL. . . . . . . . . . . . . . . . . . . . 15
4.5B Blower Motor Electrical Data: (-)HLA/(-)HLL . . . . . . . . . . . . . . . . . . . . 15
4.6 Electric Heat Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.6A Electric Heat Electrical Data: (-)HSA/(-)HSL . . . . . . . . . . . . . . . . . . . . 16
4.6B Electric Heat Electrical Data: (-)HLA/(-)HLL . . . . . . . . . . . . . . . . . . . . 18
4.6C Heater Kit Supplemental Information . . . . . . . . . . . . . . . . . . . . . . . . . 20
5.0 AIRFLOW PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
5.1 Airflow Operatng Limits (-)HSA/(-)HSL . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
5.2 240V Airflow Performance Data (-)HSA/(-)HSL . . . . . . . . . . . . . . . . . . . . . . 22
5.3 115/208/480V Airflow Performance Data (-)HSA/(-)HSL . . . . . . . . . . . . . . . 24
5.4 115/208/240V Airflow Performance Data (-)HLA/(-)HLL . . . . . . . . . . . . . . . 26
6.0 DUCTWORK. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
7.0 REFRIGERANT CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
7.1 TEV Sensing Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
7.2 Condensate Drain Tubing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
7.3 Duct Flanges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
8.0 AIR FILTER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
9.0 SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
9.1 Cooling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
9.2 Heating (electric heat only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
9.3 Heating (heat pump) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
9.4 Blower Time Delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
9.5 Defrost Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
9.6 Emergency Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
9.7 Room Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
10.0 CALCULATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
10.1 Calculating Temperature Rise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
10.2 Calculating BTUH Heating Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
10.3 Calculating Airflow CFM. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
10.4 Calculating Correction Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
11.0 PRE-START CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
12.0 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
12.1 Air Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
12.2 Indoor Coil/Drain Pan/Drain Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
12.3 Blower Motor & Wheel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
12.4 Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
12.5 Blower Assembly Removal & Replacement. . . . . . . . . . . . . . . . . . . . . . . . . 33
12.6 Motor Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
12.7 Blower Wheel Replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
13.0 REPLACEMENT PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
14.0 ACCESSORIES - KITS - PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
2
! WARNING
(SEE SECTION 4.0:
ELECTRICAL WIRING)
Disconnect all power to unit
before installing or servicing.
More than one disconnect switch
may be required to de-energize
the equipment. Hazardous voltage
can cause severe personal injury
or death.
! WARNING
(SEE SECTION 12.5: BLOWER
ASSEMBLY REMOVAL &
REPLACEMENT)
If removal of the blower assembly is
required, all disconnect switches
supplying power to the equipment
must be de-energized and locked (if
not in sight of unit) so the field
power wires can be safely removed
from the blower assembly. Failure to
do so can cause electrical shock
resulting in personal injury or
death.
! WARNING
Because of possible damage to
equipment or personal injury,
installation, service, and maintenance should be performed by a
trained, qualified service personnel. Consumer service is recommended only for filter cleaning/
replacement. Never operate the
unit with the access panels
removed.
1.0 SAFETY INFORMATION
! WARNING
Duct leaks can create an unbalanced system and draw pollutants such as
dirt, dust, fumes and odors into the home causing property damage.
Fumes and odors from toxic, volatile or flammable chemicals, as well as
automobile exhaust and carbon monoxide (CO), can be drawn into the living space through leaking ducts and unbalanced duct systems causing
personal injury or death (see Figure 1).
• If air-moving equipment or ductwork is located in garages or off-garage
storage areas - all joints, seams, and openings in the equipment and
duct must be sealed to limit the migration of toxic fumes and odors
including carbon monoxide from migrating into the living space.
• If air-moving equipment or ductwork is located in spaces containing fuel
burning appliances such as water heaters or boilers - all joints, seams,
and openings in the equipment and duct must also be sealed to prevent
depressurization of the space and possible migration of combustion
byproducts including carbon monoxide into the living space.
! WARNING
These instructions are intended as an aid to qualified, licensed service
personnel for proper installation, adjustment and operation of this unit.
Read these instructions thoroughly before attempting installation or operation. Failure to follow these instructions may result in improper installation, adjustment, service or maintenance possibly resulting in fire, electrical shock, property damage, personal injury or death.
! WARNING (SEE WARNINGS IN REGARD TO DUCTWORK)
Do not install this unit in manufactured (mobile) homes. Improper installation is more likely in manufactured housing due to ductwork material, size,
location, and arrangement. Installations in manufactured housing can
cause a fire resulting in property damage, personal injury or death.
EXCEPTION: Manufactured housing installations are approved only with
documentation by a recognized inspection authority that the installation
has been made in compliance with the instructions and all warnings have
been observed.
! WARNING (SEE SECTION 3.2: VERTICAL DOWNFLOW)
The RXHB-17, RXHB-21 or RXHB-24 combustible floor base is required
when some units with electric heat are applied downflow on combustible
flooring. Failure to use the base can cause a fire resulting in property damage, personal injury or death. See CLEARANCES for units requiring a combustible floor base. See the accessory section in this manual for combustible floor base RXHB.
! WARNING (SEE SECTION 4.3: GROUNDING)
The unit must be permanently grounded. Failure to do so can result in electrical shock causing personal injury or death.
! WARNING (SEE SECTION 12.0: MAINTENANCE)
Units with circuit breaker(s) meet requirements as a service disconnect switch,
however, if access is required to the line side (covered) of the circuit breaker,
this side of the breaker(s) will be energized with the breaker(s) de-energized.
Contact with the line side can cause electrical shock resulting in personal
injury or death.
! WARNING (SEE SECTION 5.0: DUCTWORK)
Do not, under any circumstances, connect return ductwork to any other
heat producing device such as fireplace insert, stove, etc. Unauthorized
use of such devices may result in fire, carbon monoxide poisoning, explosion, personal injury or property damage.
Continued on next page ➜
3
! WARNING
PROPOSITION 65: This appliance
contains fiberglass insulation.
Respirable particles of fiberglass
are known to the State of California
to cause cancer.
All manufacturer products meet current Federal OSHA Guidelines for
safety. California Proposition 65
warnings are required for certain
products, which are not covered by
the OSHA standards.
California's Proposition 65 requires
warnings for products sold in
California that contain or produce
any of over 600 listed chemicals
known to the State of California to
cause cancer or birth defects such
as fiberglass insulation, lead in
brass, and combustion products
from natural gas.
All “new equipment” shipped for
sale in California will have labels
stating that the product contains
and/or produces Proposition 65
chemicals. Although we have not
changed our processes, having the
same label on all our products facilitates manufacturing and shipping.
We cannot always know “when, or
if” products will be sold in the
California market.
You may receive inquiries from customers about chemicals found in, or
produced by, some of our heating
and air-conditioning equipment, or
found in natural gas used with some
of our products. Listed below are
those chemicals and substances
commonly associated with similar
equipment in our industry and other
manufacturers.
•
•
•
•
Glass Wool (Fiberglass) Insulation
Carbon Monoxide (CO).
Formaldehyde
Benzene
More details are available at the
websites for OSHA (Occupational
Safety and Health Administration),
at www.osha.gov and the State of
California’s OEHHA (Office of
Environmental Health Hazard
Assessment), at www.oehha.org.
Consumer education is important
since the chemicals and substances
on the list are found in our daily
lives. Most consumers are aware
that products present safety and
health risks, when improperly used,
handled and maintained.
! WARNING (SEE SECTION 12.6: MOTOR REPLACEMENT)
To avoid electrical shock which can result in personal injury or death, use only
the screws furnished in the motor shell mounting holds. Screws are #8-18 x .25
in. long blunt nose thread forming. Screws longer than 1/4 in. may contact the
motor winding.
! WARNING (SEE SECTION 7.0: AIR FILTER)
Do not operate the system without filters. A portion of the dust entrained in the
air may temporarily lodge in the duct runs and at the supply registers. Any circulated dust particles could be heated and charred by contact with the air handler elements. This residue could soil ceilings, walls, drapes, carpets and other
articles in the house.
Soot damage may occur with filters in place, when certain types of candles, oil
lamps or standing pilots are burned.
! WARNING
The first 36 inches of supply air plenum and ductwork must be constructed of
sheet metal as required by NFPA 90B. The supply air plenum or duct must have
a solid sheet metal bottom directly under the unit with no openings, registers
or flexible air ducts located in it. If flexible supply air ducts are used they may
be located only in the vertical walls of a rectangular plenum, a minimum of 6
inches from the solid bottom. Metal plenum or duct may be connected to the
combustible floor base, if not, it must be connected to the unit supply duct
flanges such that combustible floor or other combustible material is not
exposed to the supply air opening from the downflow unit. Exposing combustible (non-metal) material to the supply opening of a downflow unit can
cause a fire resulting in property damage, personal injury or death.
Exceptions to downflow warnings:
• Installations on concrete floor slab with supply air plenum and ductwork
completely encased in not less than 2 inches of concrete (See NFPA 90B).
! CAUTION (SEE SECTION 3.3: HORIZONTAL)
Horizontal units must be configured for right hand air supply or left hand air
supply. Horizontal drain pan must be located under indoor coil. Failure to use
the drain pan can result in property damage.
! CAUTION (SEE SECTION 2.1: RECEIVING)
In compliance with recognized codes, it is recommended that an auxiliary
drain pan be installed under all evaporator coils or units containing evaporator coils that are located in any area of a structure where damage to the
building or building contents may occur as a result of an overflow of the
coil drain pan or a stoppage in the primary condensate drain piping. See
accessories for auxiliary horizontal overflow pan RXBM.
! CAUTION
When used in cooling applications, excessive sweating may occur when
unit is installed in an unconditioned space. This can result in property
damage.
! NOTICE
Improper installation, or installation not made in accordance with the
Underwriters Laboratory (UL) certification or these instructions, can result
in unsatisfactory operation and/or dangerous conditions and are not covered by the unit warranty.
! NOTICE
In compliance with recognized codes, it is recommended that an auxiliary
drain pan be installed under all evaporator coils or units containing evaporator coils that are located in any area of a structure where damage to the
building or building contents may occur as a result of an overflow of the
coil drain pan or a stoppage in the primary condensate drain piping. See
accessories section of these instructions for auxiliary horizontal overflow
pan information (model RXBM).
4
2.0 GENERAL INFORMATION
2.1 IMPORTANT INFORMATION ABOUT EFFICIENCY AND INDOOR
2.1 AIR QUALITY
Central cooling and heating equipment is only as efficient as the duct system that carries the cooled or heated air. To maintain efficiency, comfort and good indoor air quality,
it is important to have the proper balance between the air being supplied to each room
and the air returning to the cooling and heating equipment.
Proper balance and sealing of the duct system improves the efficiency of the heating
and air conditioning system and improves the indoor air quality of the home by reducing
the amount of airborne pollutants that enter homes from spaces where the ductwork and
/ or equipment is located. The manufacturer and the U.S. Environmental Protection
Agency’s Energy Star Program recommend that central duct systems be checked by a
qualified contractor for proper balance and sealing.
FIGURE 1
MIGRATION OF DANGEROUS SUBSTANCES, FUMES, AND ODORS INTO LIVING SPACES
! WARNING
Duct leaks can create an unbalanced system and draw pollutants such as
dirt, dust, fumes and odors into the home causing property damage.
Fumes and odors from toxic, volatile or flammable chemicals, as well as
automobile exhaust and carbon monoxide (CO), can be drawn into the living space through leaking ducts and unbalanced duct systems causing
personal injury or death (see Figure 1).
• If air-moving equipment or ductwork is located in garages or off-garage
storage areas - all joints, seams, and openings in the equipment and
duct must be sealed to limit the migration of toxic fumes and odors
including carbon monoxide from migrating into the living space.
• If air-moving equipment or ductwork is located in spaces containing fuel
burning appliances such as water heaters or boilers - all joints, seams,
and openings in the equipment and duct must also be sealed to prevent
depressurization of the space and possible migration of combustion
byproducts including carbon monoxide into the living space.
! NOTICE
Improper installation, or installa-tion not made in accordance with the
Underwriters Laboratory (UL) certification or these instructions, can result
in unsatisfactory operation and/or dangerous condi-tions and are not covered by the unit warranty.
5
! NOTICE
In compliance with recognized codes, it is recommended that an auxiliary
drain pan be installed under all evaporator coils or units containing evaporator coils that are located in any area of a structure where damage to the
building or building contents may occur as a result of an overflow of the
coil drain pan or a stoppage in the primary condensate drain piping. See
accessories section of these instructions for auxiliary horizontal overflow
pan information (model RXBM).
2.2 RECEIVING
Immediately upon receipt, all cartons and contents should be inspected for transit damage. Units with damaged cartons should be opened immediately. If damage is found, it
should be noted on the delivery papers, and a damage claim filed with the last carrier.
• After unit has been delivered to job site, remove carton taking care not to damage
unit.
• Check the unit rating plate for unit size, electric heat, coil, voltage, phase, etc. to be
sure equipment matches what is required for the job specification.
• Read the entire instructions before starting the installation.
• Some building codes require extra cabinet insulation and gasketing when unit is
installed in attic applications.
• If installed in an unconditioned space, apply caulking around the power wires, control
wires, refrigerant tubing and condensate line where they enter the cabinet. Seal the
power wires on the inside where they exit conduit opening. Caulking is required to
pre-vent air leakage into and condensate from forming inside the unit, control box,
and on electrical controls.
• Install the unit in such a way as to allow necessary access to the coil/filter rack and
blower/control compartment.
• Install the unit in a level position to ensure proper condensate drainage. Make sure
unit is level in both directions within 1/8”.
• Install the unit in accordance with any local code which may apply and the national
codes. Latest editions are available from: “National Fire Protection Association, Inc.,
Batterysmarch Park, Quincy, MA 02269.” These publications are:
• ANSI/NFPA No. 70-(Latest Edition) National Electrical Code.
• NFPA90A Installation of Air Conditioning and Ventilating Systems.
• NFPA90B Installation of warm air heating and air conditioning systems.
• The equipment has been evaluated in accordance with the Code of Federal
Regulations, Chapter XX, Part 3280.
2.3 CLEARANCES
• All units are designed for “0” inches clearance to combustible material on all cabinet
surfaces.
• Some units require supply duct clearances and combustible floor bases depending on
the heating kW. The following table should be used to determine these requirements:
Model Cabinet Size
17
21
24
Model Designation kW
15
20
25
Units with electric heating kW above that listed in the table require a one inch clearance to combustible material for the first three feet of supply plenum and ductwork.
Additionally, if these units are installed downflow, a combustible floor base is
required.
Units with electric heating kW equal to or less than the values listed in the table do
not require supply ductwork clearances or combustible floor bases.
• Vertical units require clearance on at least one side of the unit for electrical connections. Horizontal units require clearance on either top or bottom for electrical connections. Refrigerant and condensate drain connections are made on the front of the unit.
• All units require 24 inches minimum access to the front of the unit for service.
• These units may be installed in either ventilated or nonventilated spaces.
6
2.4 MODEL NUMBER EXPLANATION
FIGURE 2
MODEL NUMBER EXPLANATION
(-) H S A — HM 18 17 J A
DESIGN VARIATION
A = 1ST DESIGN
VOLTAGE
A = 115/1/60
D = 480V-3-60
J = 208/240/1/60
CABINET SIZE
17 = 17.5" (600 - 1200 CFM)
21 = 21" (1200 - 1600 CFM)
24 = 24.5" (1600 -1800 CFM)
CAPACITY
18 = 18,000 BTU/H
24 = 24,000 BTU/H
30 = 30,000 BTU/H
36 = 36,000 BTU/H
42 = 42,000 BTU/H
48 = 48,000 BTU/H
60 = 60,000 BTU/H
HM = A/C OR HP MULTI-POSITION
HM = (Vertical Upflow/Horizontal Left is the factory configuration)
REFRIGERANT
A = R-22
L = R-410A
S = STANDARD MODEL (PSC MOTOR)
CLASSIFICATION
H = AIR HANDLER
TRADE BRAND
(-) H L A — HM 24 17 J A
DESIGN VARIATION
A = 1ST DESIGN
VOLTAGE
A = 115/1/60
J = 208/240/1/60
CABINET SIZE
17 = 17.5" (600 - 1200 CFM)
21 = 21" (1400 - 1600 CFM)
24 = 24.5" (1600 - 1800 CFM)
CAPACITY
24 = 18,000 / 24,000 BTU/H
36 = 30,000 / 36,000 BTU/H
48 = 42,000 / 48,000 BTU/H
60 = 60,000 BTU/H
HM = A/C OR HP MULTI-POSITION
HM = (Vertical Upflow/Horizontal Left is the factory configuration)
REFRIGERANT
A = R-22
L = R-410A
L = HIGH EFFICIENCY (X-13 MOTOR)
CLASSIFICATION
H = AIR HANDLER
TRADE BRAND
7
2.4A AVAILABLE MODELS
AVAILABLE MODELS AT A VOLTAGE
(-)HSA(L)-HM1817AA
(-)HSA(L)-HM2417AA
(-)HSA(L)-HM3017AA
(-)HSA(L)-HM3617AA
(-)HSA(L)-HM4221AA
(-)HSA(L)-HM4821AA
(-)HLA(L)-HM2417AA
(-)HLA(L)-HM3617AA
(-)HLA(L)-HM4821AA
(-)HLA(L)-HM4824AA
(-)HLA(L)-HM6024AA
AVAILABLE MODELS AT J VOLTAGE
(-)HSA-HM1817JA
(-)HSA-HM2417JA
(-)HSA-HM3017JA
(-)HSA-HM3617JA
(-)HSA-HM3621JA
(-)HSA-HM4221JA
(-)HSA-HM4821JA
(-)HSA-HM4824JA
(-)HSA-HM6024JA
(-)HLA(L)-HM2417JA
(-)HLA(L)-HM3617JA
(-)HLA(L)-HM4821JA
(-)HLA(L)-HM4824JA
(-)HLA(L)-HM6024JA
AVAILABLE MODELS AT D VOLTAGE
(-)HSA(L)-HM3617DA
(-)HSA(L)-HM3621DA
(-)HSA(L)-HM4221DA
(-)HSA(L)-HM4821DA
(-)HSA(L)-HM4824DA
(-)HSA(L)-HM6024DA
Notes:
• Supply circuit protective devices may be fuses or “HACR” type circuit breakers.
• Largest motor load is included in single circuit and multiple circuit 1.
• If non-standard fuse size is specified, use next size larger fuse size.
• J Voltage (230V) single phase air handler is designed to be used with single or three
phase 230 volt power. In the case of connecting 3-phase power to the air handler terminal block, bring only two leads to the terminal block. Cap, insulate and fully secure
the third lead.
• (-)HSA-HM6024JA is ARI rated for three phase application only.
• The air handlers are shipped from the factory with the proper indoor coil installed, and
cannot be ordered without a coil.
• The air handlers do not have an internal filter rack. An external filter rack or other
means of filtration is required.
8
2.5 DIMENSIONS & WEIGHTS
FIGURE 3
NOTE: 24" CLEARANCE REQUIRED
IN FRONT OF UNIT FOR FILTER
AND COIL MAINTENANCE.
DIMENSIONS AND WEIGHTS
ELECTRICAL CONNECTIONS
MAY EXIT TOP OR EITHER SIDE
SUPPLY AIR
HIGH VOLTAGE CONNECTION 7/8".
1 3/32", 1 31/32" DIA. KNOCK OUTS.
FLANGES ARE PROVIDED
FOR FIELD INSTALLATION
105/16
W
A
LOW VOLTAGE CONNECTION
5/8" AND 7/8" KNOCK OUT
(OUTSIDE OF CABINET)
Return Air Opening Dimensions
Model
Cabinet Size
17
21
24
Return Air
Opening Width
(Inches)
157⁄8
193⁄8
227⁄8
Return Air Opening
Depth/Length
(Inches)
193⁄4
193⁄4
193⁄4
H
AUXILIARY DRAIN CONNECTION
3/4" FEMALE PIPE THREAD (NPT)
HORIZONTAL APPLICATION ONLY
PRIMARY DRAIN CONNECTION
3/4" FEMALE PIPE THREAD (NPT)
AUXILIARY DRAIN CONNECTION
3/4" FEMALE PIPE THREAD (NPT)
UPFLOW/DOWNFLOW APPLICATION
ONLY
191/2
RETURN AIR OPENING
2111/16
LIQUID LINE CONNECTION
COPPER (SWEAT)
A-1038-01
UPFLOW UNIT SHOWN;
UNIT MAY BE INSTALLED UPFLOW, DOWNFLOW.
HORIZONTAL RIGHT, OR LEFT AIR SUPPLY.
VAPOR LINE CONNECTION
COPPER (SWEAT)
DIMENSIONAL DATA
UNIT
HEIGHT
IN. [mm]
UNIT
WIDTH
“W” IN.
[mm]
SUPPLY
DUCT
“A” IN.
[mm]
1817/2417
421/2"
[1080]
171/2"
[444.5]
3017/3617
421/2"
[1080]
3621
MODEL
SIZE
AIRFLOW
COIL (NOM.) [L/s]
UNIT WEIGHT / SHIPPING
WEIGHT (LBS.) [kg]
LO
HI
UNIT WITH
COIL (MAX. kW.)
16"
[406.4]
600
[283]
800
[378]
82/96
[37.1]/[43.5]
16"
[406.4]
1000
[472]
1200
[566]
92/106
[41.7]/[48.0]
421/2"
[1080]
171/2"
[444.5]
21"
[533.4]
191/2"
[495.3]
1200
[566]
—
97/112
[43.9]/[50.8]
4221/4821
501/2"
[1283]
21"
[533.4]
150/166
[68.0]/[75.2]
551/2"
[1410]
241/2"
[622.3]
1400
[661]
1600
[755]
1600
[755]
4824
191/2"
[495.3]
23"
[581.2]
—
162/180
[73.4]/[81.6]
6024
551/2"
[1410]
241/2"
[622.3]
23"
[581.2]
—
1800
[850]
181/198
[82.1]/[89.8]
9
3.0 APPLICATIONS
3.1 VERTICAL UPFLOW
• Vertical Upflow is the factory configuration for all models (see Figure 3).
• If a side return air opening is required, field fabricate a return air plenum with an opening large enough to supply unit and strong enough to support unit weight.
• If return air is to be ducted, install duct flush with floor. Use fireproof resilient gasket 1/8
to 1/4 in. thick between duct, unit and floor. Set unit on floor over opening
FIGURE 4
DIMENSIONS FOR FRONT CONNECT COIL
515/16
41/8
31/16
13/16
11/8
11/16
13/8
213/16
51/4
53/8
3.2 VERTICAL DOWNFLOW
Conversion to Vertical Downflow: A vertical upflow unit may be converted to vertical
downflow. Remove the door and indoor coil and reinstall 180° from original position (see
Figure 5).
IMPORTANT: To comply with certification agencies and the National Electric Code for
horizontal right application, the circuit breaker(s) on field-installed electric heater kits
must be re-installed per procedure below so that the breaker switch “on” position and
marking is up and, “off” position and marking is down.
- To turn breaker(s): Rotate one breaker pair (circuit) at a time starting with the one on the
right. Loosen both lugs on the load side of the breaker. Wires are bundles with wire ties,
one bundle going to the right lug and one bundle going to the left lug.
- Using a screwdriver or pencil, lift white plastic tab with hole away from breaker until
breaker releases from mounting opening (see Figure 5).
- With breaker held in hand, rotate breaker so that “on” position is up, “off” position is down
with unit in planned vertical mounting position. Insert right wire bundle into top right
breaker lug, ensuring all strands of all wires are inserted fully into lug, and no wire insulation is in lug.
- Tighten lug as tight as possible while holding circuit breaker. Check wires and make sure
each wire is secure and none are loose. Repeat for left wire bundle in left top circuit
breaker lug.
- Replace breaker by inserting breaker mounting tab opposite white pull tab in opening,
hook mounting tab over edge in opening.
10
FIGURE 5
ROTATING CIRCUIT BREAKER
- With screwdriver or pencil, pull white tab with hole away from breaker while setting that
side of breaker into opening. When breaker is in place, release tab, locking circuit breaker into location in opening.
- Repeat above operation for remaining breaker(s) (if more than one is provided).
- Replace single point wiring jumper bar, if it is used, on line side of breaker and tighten
securely.
- Double check wires and lugs to make sure all are secure and tight. Check to make sure
unit wiring to circuit breaker load lugs match that shown on the unit wiring diagram.
• RXHB combustible floor base is used for all unit sizes. Unit must be centered on combustible base in the width dimension (143/8”). (See Section 14.0 for more information
on the combustible floor base.)
! WARNING
The RXHB-17, RXHB-21 or RXHB-24 combustible floor base is required
when some units with electric heat are applied downflow on combustible
flooring. Failure to use the base can cause a fire resulting in property damage, personal injury or death. See CLEARANCES for units requiring a combustible floor base. See the accessory section in this manual for combustible floor base RXHB.
3.3 HORIZONTAL
Horizontal left is the default factory configuration for “HM” (airflow direction) units.
Conversion to Horizontal: A vertical upflow unit (AU) may be converted to horizontal by
removing the indoor coil and installing horizontal drain pan on coil as shown for right
hand or left hand air supply. Reinstall coil in unit as shown for right or left hand air supply. See Figures 6 & 7. (See Section 14.0 for more information on the Horizontal Adapter
Kit.)
• Rotate unit into the downflow position, with the coil compartment on top and the blower compartment on bottom.
• Reinstall the indoor coil 180° from original position. Ensure the retaining channel is fully
engaged with the coil rail. (See Figure 6, Detail A.)
• Secondary drain pan kits RXBM- are required when the unit is configured for the horizontal right position over a finished ceiling and/or living space. (See Section 14.0:
Accessories - Kits - Parts.)
IMPORTANT: Units cannot be installed horizontally laying on or suspended from the
back of the unit.
11
FIGURE 6
VERTICAL DOWNFLOW & HORIZONTAL RIGHT APPLICATIONS
DETAIL A
ENSURE THE RETAINING CHANNEL IS FULLY
ENGAGED WITH THE
COIL RAIL.
RAILS
RAILS
FIGURE 7
INDOOR COIL AND DRAIN PAN SET-UP
STRAPS
REAR WATER CATCHER
HORIZONTAL ADAPTER
KIT
TOP AIR STOP
FRONT WATER
CATCHER
VAPOR LINE
CONNECTION
AUXILIARY
HORIZONTAL
DRAIN
CONNECTION
PRIMARY
DRAIN
CONNECTION
AUXILIARY
UPFLOW/DOWNFLOW
DRAIN CONNECTION
LIQUID LINE
CONNECTION
VERTICAL
DRAIN PAN
A-1037-01
! CAUTION
Horizontal units must be configured for right hand air supply or left hand air
supply. Horizontal drain pan must be located under indoor coil. Failure to use
the drain pan can result in property damage.
12
Conversion in Horizontal Direction: Horizontal left-hand supply can be changed to horizontal right-hand supply by removing the indoor coil and reinstalling 180° from original.
(See Figure 5.)
3.4 INSTALLATION IN AN UNCONDITIONED SPACE
IMPORTANT: There are two pairs of coil rails in the air handler for default and counter
flow application. If the air handler is installed in an unconditioned space, the two unused
coil rails should be removed to minimize air handler surface sweating. (See Figure 5.)
The coil rails can be easily removed by taking off the 6 mounting screws from both sides
of the cabinet.
4.0 ELECTRICAL WIRING
Field wiring must comply with the National Electric Code (C.E.C. in Canada) and any
applicable local ordinance.
! WARNING
Disconnect all power to unit before installing or servicing. More than one
disconnect switch may be required to de-energize the equipment.
Hazardous voltage can cause severe personal injury or death.
4.1 POWER WIRING
It is important that proper electrical power is available for connection to the unit model
being installed. See the unit nameplate, wiring diagram and electrical data in the installation instructions.
• If required, install a branch circuit disconnect of adequate size, located within sight of,
and readily accessible to the unit.
• IMPORTANT: After the Electric Heater is installed, units may be equipped with one,
two, or three 30/60 amp. circuit breakers. These breaker(s) protect the internal wiring
in the event of a short circuit and serve as a disconnect. Circuit breakers installed
within the unit do not provide over-current protection of the supply wiring and therefore may be sized larger than the branch circuit protection.
• Supply circuit power wiring must be 75°C minimum copper conductors only. See
Electrical Data in this section for ampacity, wire size and circuit protector requirement.
Supply circuit protective devices may be either fuses or “HACR” type circuit breakers.
• Power wiring may be connected to either the right, left side or top. Three 7/8”, 13/32”,
131/32” dia. concentric knockouts are provided for connection of power wiring to unit.
• Power wiring is connected to the power terminal block in unit control compartment.
13
4.2 CONTROL WIRING
IMPORTANT: Class 2 low voltage control wire should not be run in conduit with power
wiring and must be separated from power wiring, unless class 1 wire of proper voltage
rating is used.
• Low voltage control wiring should be 18 Awg. color-coded. For lengths longer than
100 ft., 16 Awg. wire should be used.
• Low voltage control connections are made to low voltage pigtails extending from top
of air handler (upflow position - see Figure 3). Connections for control wiring are
made with wire nuts. Control wiring knockouts (5/8 and 7/8) are also provided on the
right and left side of the unit for side connection.
• See wiring diagrams attached to indoor and outdoor sections to be connected, or control wiring diagram booklet supplied with outdoor heat pump section for wiring connection.
• Make sure, after installation, separation of control wiring and power wiring has been
maintained.
4.3 GROUNDING
! WARNING
The unit must be permanently grounded. Failure to do so can result in electrical shock causing personal injury or death.
• Grounding may be accomplished by grounding metal conduit when installed in accordance with electrical codes to the unit cabinet.
• Grounding may also be accomplished by attaching ground wire(s) to ground lug(s)
provided in the unit wiring compartment.
• Ground lug(s) are located close to wire entrance on left side of unit (upflow). Lug(s)
may be moved to marked locations near wire entrance on right side of unit (upflow), if
alternate location is more convenient.
• Use of multiple supply circuits require grounding of each circuit to lug(s) provided in
unit.
14
4.4 ELECTRICAL WIRING
POWER WIRING
• Field wiring must comply with the National Electrical Code (C.E.C. in Canada) and
any applicable local ordinance.
• Supply wiring must be 75°C minimum copper conductors only.
• See electrical data for product Ampacity rating and Circuit Protector requirement.
GROUNDING
• This product must be sufficiently grounded in accordance with National Electrical
Code (C.E.C. in Canada) and any applicable local ordinance.
• A grounding lug is provided.
4.5 ELECTRICAL DATA – BLOWER MOTOR ONLY – NO ELECTRIC HEAT
4.5A Electrical Data – Blower Motor Only – No Electric Heat: (-)HSA/(-)HSL
NOMINAL
COOLING
CAPACITY
TONS
11/2
2
21/2
3
31/2
4
11/2
2
21/2
3
31/2
4
5
3
31/2
4
5
VOLTAGE
115
PHASE*
1
MINIMUM
MAXIMUM
CIRCUIT
CIRCUIT
AMPACITY PROTECTOR
HERTZ
HP
RPM
SPEEDS
CIRCUIT
AMPS.
60
1/5
1/5
1/4
1/3
1/2
3/4
1075
1075
1075
1075
1075
1075
2
2
2
2
2
2
2.3
3.8
4.7
6.1
7.9
8.4
3.0
5.0
6.0
8.0
10.0
11.0
15
15
15
15
15
15
1/5
1/5
1/4
1/3
1/2
3/4
1075
1075
1075
1075
1075
1075
2
2
2
2
2
2
1.7
1.7
2.5
2.5
5.2
5.2
3.0
3.0
4.0
4.0
7.0
7.0
15
15
15
15
15
15
3/4
1/3
1075
1075
2
2
5.2
1.4
7.0
2.0
15
15
1/3
3/4
3/4
1075
1075
1075
2
2
2
2.2
2.2
2.2
3.0
3.0
3.0
15
15
15
208/240
1&3
60
208/240
3
60
480
3
60
4.5B Electrical Data – Blower Motor Only – No Electric Heat: (-)HLA/(-)HLL
NOMINAL
COOLING
CAPACITY
TONS
MINIMUM
MAXIMUM
CIRCUIT
CIRCUIT
AMPACITY PROTECTOR
HP
RPM
SPEEDS
CIRCUIT
AMPS.
1/3
300-1100
4
1.6
2
15
1/2
300-1100
4
2.7
4
15
31/2 & 4
3/4
300-1100
4
3.8
5
15
5
3/4
300-1100
4
4.6
6
15
11/2 & 2
1/3
300-1100
4
4.8
6
15
1/2
300-1100
4
6.8
9
15
31/2 & 4
3/4
300-1100
4
8.4
11
15
5
3/4
300-1100
4
8.4
11
15
VOLTAGE
PHASE*
HERTZ
11/2 & 2
21/2 & 3
208/240
1&3
60
21/2 & 3
115
1
60
*Blower motors are all single phase motors.
15
4.6 ELECTRICAL DATA – WITH ELECTRIC HEAT
Installation of the UL Listed original equipment manufacturer provided heater kits listed in the following table is recommended for all
auxiliary heating requirements.
4.6A ELECTRICAL DATA – WITH ELECTRIC HEAT: (-)HSA/(-)HSL
COOLING
CAPACITY TONS
CABINET SIZE
(-)HSA/(-)HSL
1-1/2 & 2
17
MODEL
NO.
HEATER
KW
208/240V
RXBH-17A03J
RXBH-17A05J
RXBH-17A07J
RXBH-17A10J
RXBH-17A13J
2.25/3.0
3.6/4.8
5.4/7.2
7.2/9.6
9.4/12.5
3.1/4.2
6.3/8.3
5.4/7.2
7.2/9.6
9.4/12.5
2.25/3.0
3.6/4.8
5.4/7.2
7.2/9.6
9.4/12.5
3.1/4.2
6.3/8.3
10.8/14.4
3.6/4.8
7.2/9.6
12.8/17.0
4.3/5.7
8.5/11.3
5.4/7.2
7.2/9.6
9.4/12.5
10.8/14.4
12.8/17.0
7.2
9.6
14.4
17
3.6/4.8
5.4/7.2
7.2/9.6
10.8/14.4
3.6/4.8
7.2/9.6
12.8/17.0
6.4/8.5
6.4/8.5
5.4/7.2
7.2/9.6
10.8/14.4
12.8/17.0
7.2
9.6
14.4
17
RXBH-17A13J
RXBH-17A07C
RXBH-17A10C
RXBH-17A13C
RXBH-17A03J
RXBH-17A05J
RXBH-17A07J
RXBH-17A10J
RXBH-17A13J
(-)HSA/(-)HSL
2-1/2 & 3
17
RXBH-17A13J
RXBH-17A15J
RXBH-17A15J
RXBH-17A18J
RXBH-17A18J
RXBH-17A07C
RXBH-17A10C
RXBH-17A13C
RXBH-17A15C
RXBH-17A18C
RXBH-17A07D
RXBH-17A10D
RXBH-17A15D
RXBH-17A18D
RXBH-24A05J
RXBH-24A07J
RXBH-24A10J
RXBH-24A15J
(-)HSA/(-)HSL
3
21
RXBH-24A15J
RXBH-24A18J
RXBJ-24A18J
RXBH-24A07C
RXBH-24A10C
RXBH-24A15C
RXBH-24A18C
RXBH-24A07D
RXBH-24A10D
RXBH-24A15D
RXBH-24A18D
16
TYPE SUPPLY
NO.
CIRCUIT
PH/HZ ELEMENTS SINGLE
- KW PER MULTIPLECIRCUIT
CIRCUIT
1/60
1/60
1/60
1/60
1/60
1/60
1/60
3/60
3/60
3/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
1-3.0
1-4.8
2-3.6
2-4.8
3-4.17
1-4.17
2-4.17
3-2.4
3-3.2
3-4.17
1-3.0
1-4.8
2-3.6
2-4.8
3-4.17
1-4.17
2-4.17
3-4.8
1-4.8
2-4.8
3-5.68
1-5.68
2-5.68
3-2.4
3-3.2
3-4.17
3-4.8
3-5.68
2-3.6
3-3.2
3-4.8
3-5.68
1-4.8
2-3.6
2-4.8
3-4.8
1-4.8
2-4.8
4-4.26
2-4.26
2-4.26
3-2.4
3-3.2
3-4.8
3-5.68
2-3.6
3-3.2
3-4.8
3-5.68
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
MULTIPLE CKT 1
MULTIPLE CKT 2
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
MULTIPLE CKT 1
MULTIPLE CKT 2
SINGLE
MULTIPLE CKT 1
MULTIPLE CKT 2
SINGLE
MULTIPLE CKT 1
MULTIPLE CKT 2
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
MULTIPLE CKT 1
MULTIPLE CKT 2
SINGLE
MULTIPLE CKT 1
MULTIPLE CKT 2
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
CIRCUIT
AMPS.
10.8/12.5
17.3/20.0
26.0/30.0
34.6/40.0
45.1/52.1
15.0/17.4
30.1/34.7
15.0/17.3
20.0/23.1
26.1/30.1
10.8/12.5
17.3/20.0
26.0/30.0
34.6/40.0
45.1/52.1
15.0/17.4
30.1/34.7
51.9/60.0
17.3/20.0
34.6/40.0
61.6/70.8
20.5/23.6
41.1/47.2
15.0/17.3
20.0/23.1
26.1/30.1
30.0/34.6
35.5/41.0
8.7
11.6
17.3
20.4
17.3/20.0
26.0/30.0
34.6/40.0
51.9/60.0
17.3/20.0
34.6/40.0
61.6/70.8
30.8/35.4
30.8/35.4
15.0/17.3
20.0/23.1
30.0/34.6
35.5/41.0
8.7
11.6
17.3
20.4
MINIMUM
MOTOR
CIRCUIT
AMPACITY AMPACITY
1.7
1.7
1.7
1.7
1.7
1.7
0
1.7
1.7
1.7
2.5
2.5
2.5
2.5
2.5
2.5
0
2.5
2.5
0
2.5
2.5
0
2.5
2.5
2.5
2.5
2.5
1.4
1.4
1.4
1.4
2.5
2.5
2.5
2.5
2.5
0
2.5
2.5
0
2.5
2.5
2.5
2.5
1.4
1.4
1.4
1.4
16/18
24/28
35/40
46/53
59/68
21/24
38/44
21/24
28/31
35/40
17/19
25/29
36/41
47/54
60/69
22/25
38/44
68/79
25/29
44/50
81/92
29/33
52/59
22/25
29/32
36/41
41/47
48/55
13
17
24
28
25/29
36/41
47/54
68/79
25/29
44/50
81/92
42/48
39/45
22/25
29/32
41/47
48/55
13
17
24
28
MAXIMUM
CIRCUIT
PROTECTION
20/20
25/30
35/40
50/60
60/70
25/25
40/45
25/25
30/35
35/40
20/20
25/30
40/45
50/60
60/70
25/25
40/45
70/80
25/30
45/50
90/100
30/35
60/60
25/25
30/35
40/45
45/50
50/60
15
20
25
30
25/30
40/45
50/60
70/80
25/30
45/50
90/100
45/50
40/45
25/25
30/35
45/50
50/60
15
20
25
30
4.6A ELECTRICAL DATA – WITH ELECTRIC HEAT: (-)HSA/(-)HSL - continued
COOLING
CAPACITY TONS
CABINET SIZE
(-)HSA/(-)HSL
3-1/2 & 4
21
and
4
24
(-)HSA/(-)HSL
5
24
MODEL
NO.
HEATER
KW
208/240V
RXBH-24A05J 3.6/4.8
RXBH-24A07J 5.4/7.2
RXBH-24A10J 7.2/9.6
RXBH-24A15J 10.8/14.4
RXBH-24A15J 3.6/4.8
7.2/9.6
RXBH-24A18J 12.8/17
RXBH-24A18J 6.4/8.5
6.4/8.5
RXBH-24A20J 14.4/19.2
RXBH-24A20J 7.2/9.6
7.2/9.6
RXBH-24A25J 18.0/24.0
RXBH-24A25J 6.0/8.0
6.0/8.0
(4-ton only)
6.0/8.0
RXBH-24A07C 5.4/7.2
RXBH-24A10C 7.2/9.6
RXBH-24A15C 10.8/14.4
RXBH-24A18C 12.8/17.0
RXBH-24A20C* 14.4/19.2
RXBH-24A20C 7.2/9.6
7.2/9.6
RXBH-24A25C* 18.0/24.0
RXBH-24A25C 9.0/12.0
(4-ton only)
9.0/12.0
RXBH-24A07D
7.2
RXBH-24A10D
9.6
RXBH-24A15D
14.4
RXBH-24A18D
17
RXBH-24A20D
19.2
RXBH-24A25D
24.0
(4-ton only)
RXBH-24A05J 3.6/4.8
RXBH-24A07C 5.4/7.2
RXBH-24A10C 7.2/9.6
RXBH-24A15C 10.8/14.4
RXBH-24A18C 12.8/17.0
RXBH-24A20C* 14.4/19.2
7.2/9.6
RXBH-24A20C
7.2/9.6
RXBH-24A25C* 18.0/24.0
RXBH-24A25C 9.0/12.0
9.0/12.0
RXBH-24A30C* 21.6/28.8
RXBH-24A30C 10.8/14.4
10.8/14.4
RXBH-24A07D
7.2
RXBH-24A10D
9.6
RXBH-24A15D
14.4
RXBH-24A18D
17
RXBH-24A20D
19.2
RXBH-24A25D
24.0
RXBH-24A30D*
28.8
TYPE SUPPLY
NO.
CIRCUIT
PH/HZ ELEMENTS SINGLE
- KW PER MULTIPLECIRCUIT
CIRCUIT
CIRCUIT
AMPS.
MINIMUM
MOTOR
CIRCUIT
AMPACITY AMPACITY
MAXIMUM
CIRCUIT
PROTECTION
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/6
1/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
1-4.8
2-3.6
2-4.8
3-4.8
1-4.8
2-4.8
4-4.26
2-4.26
2-4.26
4-4.8
2-4.8
2-4.8
6-4.0
2-4.0
2-4.0
2-4.0
3-2.4
3-3.2
3-4.8
3-2.84
3-3.2
3-3.2
3-3.2
6-4.0
3-4.0
3-4.0
2-3.6
3-3.2
3-4.8
3-5.68
6-3.2
SINGLE
SINGLE
SINGLE
SINGLE
MULTIPLE CKT 1
MULTIPLE CKT 2
SINGLE
MULTIPLE CKT 1
MULTIPLE CKT 2
SINGLE
MULTIPLE CKT 1
MULTIPLE CKT 2
SINGLE
MULTIPLE CKT 1
MULTIPLE CKT 2
MULTIPLE CKT 3
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
MULTIPLE CKT 1
MULTIPLE CKT 2
SINGLE
MULTIPLE CKT 1
MULTIPLE CKT 2
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
17.3/20.0
26.0/30.0
34.6/40.0
51.9/60.0
17.3/20.0
34.6/40.0
61.6/70.8
30.8/35.4
30.8/35.4
69.2/80
34.6/40.0
34.6/40.0
86.4/99.9
28.8/33.3
28.8/33.3
28.8/33.3
15.0/17.3
20.0/23.1
30.0/34.6
35.6/41.0
40.0/46.2
20.0/23.1
20.0/23.1
50.0/57.8
25.0/28.9
25.0/28.9
8.7
11.6
17.3
20.4
23.2
4.0
4.0
4.0
4.0
4.0
0.0
4.0
4.0
0.0
4.0
4.0
0.0
4.0
4.0
0.0
0.0
4.0
4.0
4.0
4.0
4.0
4.0
0.0
4.0
4.0
0.0
2.2
2.2
2.2
2.2
2.2
27/30
38/43
49/55
70/80
27/30
44/50
82/94
44/50
39/45
92/105
49/55
44/50
113/130
42/47
36/42
36/42
24/27
30/34
43/49
50/57
55/63
30/34
25/29
68/78
37/42
32/37
14
18
25
29
32
30/30
40/45
50/60
70/80
30/30
45/50
90/100
45/50
40/45
100/110
50/60
45/50
125/150
45/50
40/45
40/45
25/30
30/35
45/50
50/60
60/70
30/35
25/30
70/80
40/45
35/40
15
20
25
30
35
3/60
6-4.0
SINGLE
28.8
2.2
39
40
1/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
1-4.8
3-2.4
3-3.2
3-4.8
3-2.84
3-3.2
3-3.2
3-3.2
6-4.0
3-4.0
3-4.0
6-4.8
3-4.8
3-4.8
2-3.6
3-3.2
3-4.8
3-5.68
6-3.2
6-4.0
6-4.8
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
MULTIPLE CKT 1
MULTIPLE CKT 2
SINGLE
MULTIPLE CKT 1
MULTIPLE CKT 2
SINGLE
MULTIPLE CKT 1
MULTIPLE CKT 2
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
17.3/20.0
15.0/17.3
20.0/23.1
30.0/34.6
35.6/41.0
40.0/46.2
20.0/23.1
20.0/23.1
50.0/57.8
25.0/28.9
25.0/28.9
60.0/69.4
30.0/34.7
30.0/34.7
8.7
11.6
17.3
20.4
23.2
28.8
34.6
4.4
4.4
4.4
4.4
4.4
4.4
4.4
0
4.4
4.4
0
4.4
4.4
0
2.2
2.2
2.2
2.2
2.2
2.2
2.2
28/31
25/28
31/35
43/49
50/57
56/64
31/35
25/29
68/78
37/42
32/37
81/93
43/49
38/44
14
18
25
29
32
39
46
30/35
25/30
35/35
45/50
50/60
60/70
35/35
25/30
70/80
40/45
35/40
90/100
45/50
40/45
15
20
25
30
35
40
50
*Values only. No single point kit available.
NOTES:
• Electric heater BTUH - (heater watts + motor watts) x 3.414 (see airflow table for motor watts.)
• Supply circuit protective devices may be fuses or “HACR” type circuit breakers.
• If non-standard fuse size is specified, use next size larger standard fuse size.
• Largest motor load is included in single circuit or circuit 1 of multiple circuits.
• Heater loads are balanced on 3 phase models with 3 or 6 heaters only.
• No electrical heating elements are permitted to be used with A Voltage (115V) air handler.
• J Voltage (230V) signal phase air handler is designed to be used with single or three phase 230 volt electric heaters. In the case of connecting 3
phase power to air handler terminal block without the heater, bring only two leads to terminal block, cap, insulate and fully secure the third lead.
• Do not use 480 volts electrical heaters on 230 volts air handler.
• Do not use 230 volts electrical heaters on 480 volts air handler.
• If the kit is listed under both single and multiple circuits, the kit is shipped from factory as multiple circuits. For single phase application, Jumper
bar kit RXBJ-A21 and RXBJ-A31 can be used to convert multiple circuits to a single supply circuit. Refer to Accessory Section for details.
17
4.6B ELECTRICAL DATA – WITH ELECTRIC HEAT: (-)HLA/(-)HLL
Installation of the UL Listed original equipment manufacturer provided heater kits listed in the following table is recommended for all
auxiliary heating requirements.
COOLING
CAPACITY TONS
CABINET SIZE
(-)HLA/(-)HLL
1-1/2 & 2
17
(-)HLA/(-)HLL
2-1/2 & 3
17
(-)HLA/(-)HLL
3-1/2 & 4
21
18
MODEL
NO.
HEATER
KW
208/240V
RXBH-17A03J
RXBH-17A05J
RXBH-17A07J
RXBH-17A10J
RXBH-17A13J
TYPE SUPPLY
NO.
CIRCUIT
PH/HZ ELEMENTS SINGLE
- KW PER MULTIPLECIRCUIT
CIRCUIT
CIRCUIT
AMPS.
MINIMUM
MOTOR
CIRCUIT
AMPACITY AMPACITY
MAXIMUM
CIRCUIT
PROTECTION
2.25/3.0
3.6/4.8
5.4/7.2
7.2/9.6
9.4/12.5
3.1/4.2
RXBH-17A13J
6.3/8.3
RXBH-17A07C 5.4/7.2
RXBH-17A10C 7.2/9.6
RXBH-17A13C 9.4/12.5
RXBH-17A03J 2.25/3.0
RXBH-17A05J 3.6/4.8
RXBH-17A07J 5.4/7.2
RXBH-17A10J 7.2/9.6
RXBH-17A13J 9.4/12.5
3.1/4.2
RXBH-17A13J
6.3/8.3
1/60
1/60
1/60
1/60
1/60
1/60
1/60
3/60
3/60
3/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1-3.0
1-4.8
2-3.6
2-4.8
3-4.17
1-4.17
2-4.17
3-2.4
3-3.2
3-4.17
1-3.0
1-4.8
2-3.6
2-4.8
3-4.17
1-4.17
2-4.17
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
MULTIPLE CKT 1
MULTIPLE CKT 2
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
MULTIPLE CKT 1
MULTIPLE CKT 2
10.8/12.5
17.3/20.0
26.0/30.0
34.6/40.0
45.1/52.1
15.0/17.4
30.1/34.7
15.0/17.3
20.0/23.1
26.1/30.1
10.8/12.5
17.3/20.0
26.0/30.0
34.6/40.0
45.1/52.1
15.0/17.4
30.1/34.7
1.6
1.6
1.6
1.6
1.6
1.6
0
1.6
1.6
1.6
2.7
2.7
2.7
2.7
2.7
2.7
0
16/18
24/27
35/40
46/52
59/68
21/24
38/44
21/24
27/31
35/40
17/19
25/29
36/41
47/54
60/69
23/26
38/44
20/20
25/30
35/40
50/60
60/70
25/25
40/45
25/25
30/35
35/40
20/20
25/30
40/45
50/60
60/70
25/30
40/45
RXBH-17A15J 10.8/14.4
3.6/4.8
RXBH-17A15J
7.2/9.6
RXBH-17A18J 12.8/17.0
4.3/5.7
RXBH-17A18J
8.5/11.3
RXBH-17A07C 5.4/7.2
RXBH-17A10C 7.2/9.6
RXBH-17A13C 9.4/12.5
RXBH-17A15C 10.8/14.4
RXBH-17A18C 12.8/17.0
RXBH-24A05J 3.6/4.8
RXBH-24A07J 5.4/7.2
RXBH-24A10J 7.2/9.6
RXBH-24A15J 10.8/14.4
3.6/4.8
RXBH-24A15J
7.2/9.6
RXBH-24A18J 12.8/17.0
6.4/8.5
RXBJ-24A18J
6.4/8.5
RXBH-24A20J 14.4/19.2
7.2/9.6
RXBH-24A20J 7.2/9.6
RXBH-24A25J 18.0/24.0
6.0/8.0
RXBH-24A25J
6.0/8.0
(4-ton only)
6.0/8.0
RXBH-24A07C 5.4/7.2
RXBH-24A10C 7.2/9.6
RXBH-24A15C 10.8/14.4
RXBH-24A18C 12.8/17.0
RXBH-24A20C* 14.4/19.2
7.2/9.6
RXBH-24A20C
7.2/9.6
RXBH-24A25C* 18.0/24.0
RXBH-24A25C 9.0/12.0
(4-ton only)
9.0/12.0
1/60
1/60
1/60
1/60
1/60
1/60
3/60
3/60
3/60
3/60
3/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3-4.8
1-4.8
2-4.8
3-5.68
1-5.68
2-5.68
3-2.4
3-3.2
3-4.17
3-4.8
3-5.68
1-4.8
2-3.6
2-4.8
3-4.8
1-4.8
2-4.8
4-4.26
2-4.26
2-4.26
4-48
2-4.8
2-4.8
6-4.0
2-4.0
2-4.0
2-4.0
3-2.4
3-3.2
3-4.8
3-2.84
3-3.2
3-3.2
3-3.2
6-4.0
3-4.0
3-4.0
SINGLE
MULTIPLE CKT 1
MULTIPLE CKT 2
SINGLE
MULTIPLE CKT 1
MULTIPLE CKT 2
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
MULTIPLE CKT 1
MULTIPLE CKT 2
SINGLE
MULTIPLE CKT 1
MULTIPLE CKT 2
SINGLE
MULTIPLE CKT 1
MULTIPLE CKT 2
SINGLE
MULTIPLE CKT 1
MULTIPLE CKT 2
MULTIPLE CKT 3
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
MULTIPLE CKT 1
MULTIPLE CKT 2
SINGLE
MULTIPLE CKT 1
MULTIPLE CKT 2
51.9/60.0
17.3/20.0
34.6/40.0
61.6/70.8
20.5/23.6
41.1/47.2
15.0/17.3
20.0/23.1
26.1/30.1
30.0/34.6
35.5/41.0
17.3/20.0
26.0/30.0
34.6/40.0
51.9/60.0
17.3/20.0
34.6/40.0
61.6/70.8
30.8/35.4
30.8/35.4
69.2/80
34.6/40.0
34.6/40.0
86.4/99.9
28.8/33.3
28.8/33.3
28.8/33.3
15.0/17.3
20.0/23.1
30.0/34.6
35.6/41.0
40.0/46.2
20.0/23.1
20.0/23.1
50.0/57.8
25.0/28.9
25.0/28.9
2.7
2.7
0
2.7
2.7
0
2.7
2.7
2.7
2.7
2.7
3.8
3.8
3.8
3.8
3.8
0.0
3.8
3.8
0.0
3.8
3.8
0.0
3.8
3.8
0.0
0.0
3.8
3.8
3.8
3.8
3.8
3.8
0.0
3.8
3.8
0.0
69/79
25/29
44/50
81/92
29/33
52/59
23/25
29/33
36/41
41/47
48/55
27/30
38/43
48/55
70/80
27/30
44/50
82/94
44/49
39/45
92/105
48/55
44/50
113/130
41/47
36/42
36/42
24/27
30/34
43/48
50/56
55/63
30/34
25/29
68/77
36/41
32/37
70/80
25/30
45/50
90/100
30/35
60/60
25/25
30/35
40/45
45/50
50/60
30/30
40/45
50/60
70/80
30/30
45/50
90/100
45/50
40/45
100/110
50/60
45/50
125/150
45/50
40/45
40/45
25/30
30/35
45/50
50/60
60/70
30/35
25/30
70/80
40/45
35/40
4.6B Electrical Data – With Electric Heat: (-)HLA/(-)HLL - continued
COOLING
CAPACITY TONS
CABINET SIZE
(-)HLA/(-)HLL
4&5
24
MODEL
NO.
HEATER
KW
208/240V
RXBH-24A07J 5.4/7.2
RXBH-24A10J 7.2/9.6
RXBH-24A15J 10.8/14.4
3.6/4.8
RXBH-24A15J
7.2/9.6
RXBH-24A18J 12.8/17
6.4/8.5
RXBH-24A18J
6.4/8.5
RXBH-24A20J 14.4/19.2
7.2/9.6
RXBH-24A20J
7.2/9.6
RXBH-24A25J 18.0/24.0
6.0/8.0
RXBH-24A25J 6.0/8.0
6.0/8.0
RXBH-24A30J 21.6/28.8
7.2/9.6
RXBH-24A30J
7.2/9.6
(5-ton only)
7.2/9.6
RXBH-24A07C 5.4/7.2
RXBH-24A10C 7.2/9.6
RXBH-24A15C 10.8/14.4
RXBH-24A18C 12.8/17.0
RXBH-24A20C* 14.4/19.2
7.2/9.6
RXBH-24A20C
7.2/9.6
RXBH-24A25C* 18.0/24.0
9.0/12.0
RXBH-24A25C
9.0/12.0
RXBH-24A30C* 21.6/28.8
RXBH-24A30C 10.8/14.4
(5-ton only) 10.8/14.4
TYPE SUPPLY
NO.
CIRCUIT
PH/HZ ELEMENTS SINGLE
- KW PER MULTIPLECIRCUIT
CIRCUIT
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
1/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
3/60
2-3.6
2-4.8
3-4.8
1-4.8
2-4.8
4-4.26
2-4.26
2-4.26
4-4.8
2-4.8
2-4.8
6-4.0
2-4.0
2-4.0
2-4.0
6-4.8
2-4.8
2-4.8
2-4.8
3-2.4
3-3.2
3-4.8
3-2.84
3-3.2
3-3.2
3-3.2
6-4.0
3-4.0
3-4.0
6-4.8
3-4.8
3-4.8
SINGLE
SINGLE
SINGLE
MULTIPLE CKT1
MULTIPLE CKT 2
SINGLE
MULTIPLE CKT 1
MULTIPLE CKT 2
SINGLE
MULTIPLE CKT 1
MULTIPLE CKT 2
SINGLE
MULTIPLE CKT 1
MULTIPLE CKT 2
MULTIPLE CKT 3
SINGLE
MULTIPLE CKT 1
MULTIPLE CKT 2
MULTIPLE CKT 3
SINGLE
SINGLE
SINGLE
SINGLE
SINGLE
MULTIPLE CKT 1
MULTIPLE CKT 2
SINGLE
MULTIPLE CKT 1
MULTIPLE CKT 2
SINGLE
MULTIPLE CKT 1
MULTIPLE CKT 2
CIRCUIT
AMPS.
26.0/30.0
34.6/40.0
51.9/60.0
17.3/20.0
34.6/40.0
61.6/70.8
30.8/35.4
30.8/35.4
69.2/80
34.6/40.0
34.6/40.0
86.4/99.9
28.8/33.3
28.8/33.3
28.8/33.3
103.8/120.
34.6/40.0
34.6/40.0
34.6/40.0
15.0/17.3
20.0/23.1
30.0/34.6
35.6/41.0
40.0/46.2
20.0/23.1
20.0/23.1
50.0/57.8
25.0/28.9
25.0/28.9
60.0/69.4
30.0/34.7
30.0/34.7
MINIMUM
MOTOR
CIRCUIT
AMPACITY AMPACITY
4.6
4.6
4.6
4.6
0
4.6
4.6
0
4.6
4.6
0
4.6
4.6
0
0
4.6
4.6
0
0
4.6
4.6
4.6
4.6
4.6
4.6
0
4.6
4.6
0
4.6
4.6
0
39/44
49/56
71/81
28/31
44/50
83/95
45/50
39/45
93/106
49/56
44/50
114/131
42/48
36/42
36/42
136/156
49/56
44/50
44/50
25/28
31/35
44/49
51/57
56/64
31/35
25/29
69/78
37/42
32/37
81/93
44/50
38/44
MAXIMUM
CIRCUIT
PROTECTION
40/45
50/60
80/90
30/35
45/50
90/100
45/50
40/45
100/110
50/60
45/50
125/150
45/50
40/45
40/45
150/175
50/60
45/50
45/50
25/30
35/35
45/50
60/60
60/70
35/35
25/30
70/80
40/45
35/40
90/100
45/50
40/45
*Values only. No single point kit available.
NOTES:
• Electric heater BTUH - (heater watts + motor watts) x 3.414 (see airflow table for motor watts.)
• Supply circuit protective devices may be fuses or “HACR” type circuit breakers.
• If non-standard fuse size is specified, use next size larger standard fuse size.
• Largest motor load is included in single circuit or circuit 1 of multiple circuits.
• Heater loads are balanced on 3 phase models with 3 or 6 heaters only.
• No electrical heating elements are permitted to be used with A Voltage (115V) air handler.
• J Voltage (230V) signal phase air handler is designed to be used with single or three phase 230 volt electric heaters. In the case of connecting 3
phase power to air handler terminal block without the heater, bring only two leads to terminal block, cap, insulate and fully secure the third lead.
• Do not use 480 volts electrical heaters on 230 volts air handler.
• Do not use 230 volts electrical heaters on 480 volts air handler.
• If the kit is listed under both single and multiple circuits, the kit is shipped from factory as multiple circuits. For single phase application, Jumper
bar kit RXBJ-A21 and RXBJ-A31 can be used to convert multiple circuits to a single supply circuit. Refer to Accessory Section for details.
19
4.6C HEATER KIT SUPPLEMENTAL INFORMATION
AIR CONDITIONING DIVISION
(-)HLA-HM4821JA
MARK HEATER INSTALLED/
L’APPAREIL DE CHAUFFAGE DE MARQUE A INSTALLE
If a heater
kit is listed
both
Single
and Multicircuit, the
kit is
shipped
as a Multicircuit and
will
require a
single
point kit
Only listed kits can be applied
Contractor
should “mark
or check” the
left column for
the kit installed
These are the
required maximum and minimum circuit
breaker sizes
for overcurrent
protection and
should not be
confused with
the size of the
breakers
installed in the
heater kit.
Heater Kit Supplemental Information: What allows the manufacturer to use standard Circuit Breakers
up to 60 amps inside the air handler, when using an approved Heater Kit?
National Electric Code (Section 424-22b) and our UL requirements allow us to subdivide heating element
circuits, of less than 48 amps, using breakers of not more than 60 amps and, additionally by, NEC 424-3b, a
rating not less than 125 percent of the load and NEC 424-22c, which describes the supplementary overcurrent protection required to be factory-installed within, or on the heater. The breakers in the heater kit are not,
and have never been, by NEC, intended to protect pwer wiring leading to the air handler unit. The breakers
in the heating kit are for short circuit proteciton. All internal unit wiring, where the breakers apply, has been
UL approved for short circuit protection.
Ampacity, (not breaker size), determines supply circuit wire size. The ampacity listed on the unit rating plate
and the Maximum and Minimum circuit breaker size (noted above) or in the units specification sheet or
installation instructions provides the information to properly select wire and circuit breaker/protector size. The
National Electric Code (NEC) specifies that the supply or branch circuit must be protected at the source.
20
5.0 AIRFLOW PERFORMANCE
Airflow performance data is based on cooling performance with a coil and no filter in place.
Select performance table for appropriate unit size, voltage and number of electric heaters to
be used. Make sure external static applied to unit allows operation within the minimum and
maximum limits shown in table below for both cooling and electric heat operation. For optimum blower performance, operate the unit in the .3 to .7 in W.C. external static range. Units
with coils should be applied with a minimum of .1 in W.C. external static.
5.1 AIRFLOW OPERATING LIMITS
Cabinet Size
17
17
21
24
Cooling BTUH x 1,000
Cooling Tons Nominal
-018
1.5
-024
2
-030
2.5
-036
3
-042
3.5
-048
4
-048
4
-060
5
Heat Pump or Air Conditioning
Maximum Heat/Cool CFM [L/s]
(37.5 CFM [18 L/s]/1,000 BTUH)
(450 CFM [212 L/s]/Ton Nominal)
675
[319]
900
[425]
1125
[531]
1350
[637]
1575
[743]
1800
[850]
1800
[850]
1930
[911]
Heat Pump or Air Conditioning
Nominal Heat/Cool CFM [L/s]
(33.3 CFM [16 L/s]/1,000 BTUH)
(400 CFM [189 L/s]/Ton Nominal)
600
[283]
800
[378]
1000
[472]
1200
[566]
1400
[661]
1600
[755]
1600
[755]
1800
[850]
Heat Pump or Air Conditioning
Minimum Heat/Cool CFM [L/s]
(30.0 CFM [14 L/s]/1,200 BTUH)
(360 CFM [170 L/s]/Ton Nominal)
540
[255]
720
[340]
900
[425]
1080
[510]
1260
[595]
1440
[680]
1440
[680]
1620
[765]
Maximum kW Electric Heating
& Minimum Electric Heat CFM [L/s]
10
500 [236]
10
650 [308]
15
865 [408]
15
1015 [480]
20
1200 [566]
20
1400 [660]
Maximum Electric Heat Rise °F [°C]
85 [29]
85 [29]
85 [29]
85 [29]
85 [29]
85 [29]
20
25
1400 [660] 1730 [821]
85 [29]
85 [29]
21
5.2 240V AIRFLOW PERFORMANCE DATA – (-)HSA/(-)HSL (PSC MOTOR)
Model
Number
Motor
Speed
From
Factory
Manufacturer
Recommended
Air Flow Range
(Min / Max) CFM
Blower Size/
Motor H.P.
# of Speeds
Motor
Speed
0.10 [.02] 0.20 [.05] 0.30 [.07] 0.40 [.10] 0.50 [.12] 0.60 [.15] 0.70 [.17]
Low
1817
No heater
Low
240 V
517/711CFM
[244/336 L/s]
10x6
1/5 [149]
2 Speed
High
Low
1817
with 13kw
heater
Low
240 V
2417
No heater
Low
240 V
467/661 CFM
[230/312 L/s]
10x6
1/5 [149]
2 Speed
High
Low
647/888
[305.419 L/s]
10x6
1/5 [149]
2 Speed
High
Low
2417
with
13kw heater
Low
240 V
3017
No heater
Low
240 V
617/638
[291/395 L/s]
10x6
1/5 [149]
2 Speed
High
Low
864/1004
[408/474 L/s]
10x8
1/4 [186]
2 Speed
High
3017
with
18kw heater
Low
Low
240 V
814/904 CFM
[384/427 L/s]
10x8
1/4 [186]
2 Speed
High
Low
3617/3621
No heater
Low
240 V
1104/1248 CFM
[521/589 L/s]
10x8
1/3 [249]
2 Speed
High
3617/3621
with
18kw heater
Low
Low
240 V
1054/1148 CFM
[497/542 L/s]
10x8
1/3 [249]
2 Speed
High
Low
4221
No heater
Low
240 V
1241/1537 CFM
[586/725 L/s]
10x10
1/2 [373]
2 Speed
High
4221
with
20kw heater
22
Low
Low
240 V
1225/1500 CFM
[553/678 L/s]
PSC
CFM[L/s] Air Delivery/RPM/Watts-240 Volts
External Static Pressure-Inches W.C.
10x10
1/2 [373]
2 Speed
High
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
668 [315]
541
180
—
—
—
638 [301]
571
171
—
—
—
817 [386]
616
239
—
—
—
787 [371]
646
230
—
—
—
1022 [482]
700
344
—
—
—
972 [459]
750
324
—
—
—
637 [301]
596
171
—
—
—
607 [286]
626
162
—
—
—
779 [368]
667
230
—
—
—
749 [353]
697
221
—
—
—
987 [466]
754
313
—
—
—
937 [442]
804
293
—
—
—
595 [281]
657
166
—
—
—
565 [267]
687
157
—
—
—
757 [357]
715
221
—
—
—
727 [343]
745
212
—
—
—
940 [444]
794
302
—
—
—
890 [420]
844
282
—
—
—
560 [264]
706
161
—
—
—
530 [250]
736
152
—
—
—
693 [327]
770
206
—
—
—
663 [313]
800
197
—
—
—
903 [426]
833
294
—
—
—
853 [403]
883
274
—
—
—
517 [244]
761
155
711 [336]
812
243
487 [230]
791
146
661 [312]
837
232
647 [305]
808
196
888 [419]
875
331
617 [291]
838
187
838 [395]
900
320
864 [408]
870
288
1004 [474]
924
364
814 [384]
920
268
904 [427]
949
334
—
—
—
662 [312]
853
227
—
—
—
612 [289]
878
216
—
—
—
828 [391]
908
313
—
—
—
778 [367]
933
302
—
—
—
951 [449]
953
352
—
—
—
851 [402]
978
322
—
—
—
614 [290]
890
210
—
—
—
564 [266]
915
199
—
—
—
774 [365]
958
301
—
—
—
724 [342]
983
290
—
—
—
883 [417]
975
344
—
—
—
783 [370]
1000
314
1229 [580] 1201[567] 1170 [552] 1141 [538] 1104 [521]
—
788
833
872
909
951
—
466
462
427
406
395
—
—
—
—
—
1248 [589] 1194 [563]
—
—
—
—
1008
1028
—
—
—
—
488
475
1179 [556] 1151 [543] 1120 [529] 1091 [515] 1054 [497]
—
838
883
922
959
1001
—
446
442
407
386
375
—
—
—
—
—
1148 [542] 1094 [516]
—
—
—
—
1033
1053
—
—
—
1133 [535]
1042
454
—
—
—
1033 [487]
1067
—
—
—
—
458
445
1526 [720] 1474 [696] 1427 [673] 1307 [617] 1241 [586]
—
834
870
902
948
968
—
560
549
535
476
462
—
—
—
—
—
1537 [725] 1418 [669]
—
—
—
—
1072
1077
—
—
—
—
860
835
1456 [687] 1404 [663] 1357 [640] 1237 [584] 1171 [553]
—
886
906
925
959
992
—
542
524
505
468
431
—
—
—
—
—
1437 [678] 1318 [622]
—
—
—
—
1080
1090
—
—
—
—
840
800
424
—
—
—
1334 [630]
1085
820
—
—
—
1234 [582]
1105
785
5.2 240V AIRFLOW PERFORMANCE DATA – (-)HSA/(-)HSL (PSC MOTOR) - continued
Model
Number
Motor
Speed
From
Factory
Manufacturer
Recommended
Air Flow Range
(Min / Max) CFM
Blower Size/
Motor H.P.
# of Speeds
Motor
Speed
0.10 [.02] 0.20 [.05] 0.30 [.07] 0.40 [.10] 0.50 [.12] 0.60 [.15] 0.70 [.17]
Low
4821/4824
No heater
Low
240 V
1572/1824 CFM
[742/861 L/s]
10x10
3/4 [559]
2 Speed
High
Low
4821/4824
with
25kw heater
Low
240 V
6024
No heater
Low
240 V
1225/1500
[709/814 L/s]
10x10
3/4 [559]
2 Speed
High
Low
1766/1965 CFM
[833/927 L/s]
11x11
3/4 [559]
2 Speed
High
6024
with
30kw heater
Low
Low
240 V
1225/1500
PSC
CFM[L/s] Air Delivery/RPM/Watts-240 Volts
External Static Pressure-Inches W.C.
11x11
3/4 [559]
2 Speed
High
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
1741 [822]
878
785
—
—
—
1671 [789]
945
715
—
—
—
1944 [917]
764
779
—
—
—
1844 [870]
839
745
—
—
—
1719 [811]
920
757
—
—
—
1649 [778]
965
685
—
—
—
1912 [902]
803
763
—
—
—
1812 [855]
865
729
—
—
—
1667 [787]
950
707
—
—
—
1597 [754]
995
650
—
—
—
1860 [878]
838
747
—
—
—
1760 [831]
890
713
—
—
—
1628 [768]
981
667
—
—
—
1558 [735]
1025
630
—
—
—
1813 [856]
865
729
—
—
—
1713 [808]
913
696
—
—
—
1572 [742]
1007
641
1824 [861]
1102
871
1502 [709]
1050
610
1724 [814]
1116
810
1766 [833]
889
708
1965 [927]
943
828
1666 [786]
935
678
1865 [880]
987
788
—
—
—
1767 [834]
1112
830
—
—
—
1667 [787]
1119
780
—
—
—
1908 [900]
967
799
—
—
—
1808 [853]
1001
766
—
—
—
1653 [780]
1121
770
—
—
—
1553 [733]
1130
730
—
—
—
1854 [875]
977
795
—
—
—
1754 [828]
1014
744
NOTE:
• All 208/240V PSC motors have voltage taps for 208 and 240 volts.
• All 208/240V PSC motors are shipped on high speed and 240 volts.
• If the application external static is less than 0.5” WC, adjust the motor speed to the low static speed as described below.
- Unplug the black motor wire off the relay on the control board and plug in the red motor wire.
- Replace the cap on the black motor wire.
• Voltage change (208/240V motors):
- Move the orange lead to transformer 208V tap from 240V tap. Replace the wire cap on 240V tap.
- Unplug the purple motor wire off the transformer and plug in the yellow motor wire.
- Replace the cap on the purple motor wire.
• The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each
model.
• The following formula can be used to calculate the approximate airflow, if a smaller (N kw) than the maximum heater kit is installed.
Approximate Airflow = Airflow without heater - (Airflow without heater - Airflow with maximum heater) X (N kw/maximum heater kw)
23
5.3 115/208/480V AIRFLOW PERFORMANCE DATA – (-)HSA/(-)HSL (PSC MOTOR)
Model
Number
Motor
Speed
From
Factory
Manufacturer
Recommended
Air Flow Range
(Min / Max) CFM
Blower Size/
Motor H.P.
# of Speeds
Motor
Speed
0.10 [.02] 0.20 [.05] 0.30 [.07] 0.40 [.10] 0.50 [.12] 0.60 [.15] 0.70 [.17]
Low
1817
No heater
High
523/705CFM
[247/333 L/s]
10x6
1/5 [149]
2 Speed
High
1817
with 13kw
heater
Low
High
487/661 CFM
[230/312 L/s]
10x6
1/5 [149]
2 Speed
High
Low
2417
No heater
High
647/888
[305.419 L/s]
10x6
1/5 [149]
2 Speed
High
2417
with
13kw heater
Low
High
617/838
[291/395 L/s]
10x6
1/5 [149]
2 Speed
High
Low
3017
No heater
High
864/1004
[408/474 L/s]
10x8
1/4 [186]
2 Speed
High
3017
with
18kw heater
Low
High
814/904 CFM
[384/427 L/s]
10x8
1/4 [186]
2 Speed
High
Low
3617/3621
No heater
High
1104/1248 CFM
[521/589 L/s]
10x8
1/3 [249]
2 Speed
High
3617/3621
with
18kw heater
Low
High
1054/1148 CFM
[497/542 L/s]
10x8
1/3 [249]
2 Speed
High
Low
4221
No heater
High
1241/1537 CFM
[586/725 L/s]
10x10
1/2 [373]
2 Speed
High
4221
with
20kw heater
24
Low
High
1225/1500 CFM
[553/678 L/s]
PSC
CFM[L/s] Air Delivery/RPM/Watts-115/208/480 Volts
External Static Pressure-Inches W.C.
10x10
1/2 [373]
2 Speed
High
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
681 [321]
541
193
—
—
—
651 [307]
571
184
—
—
—
875 [413]
648
259
—
—
—
845 [399]
678
250
—
—
—
1038 [490]
721
325
—
—
—
988 [466]
771
305
—
—
—
636 [300]
601
181
—
—
—
606 [286]
631
172
—
—
—
806 [380]
700
255
—
—
—
776 [366]
730
246
—
—
—
1010 [477]
771
314
—
—
—
960 [453]
821
294
—
—
—
606 [286]
670
173
—
—
—
576 [272]
700
164
—
—
—
787 [371]
745
243
—
—
—
757 [357]
775
234
—
—
—
976 [461]
799
303
—
—
—
926 [437]
849
283
—
—
—
567 [268]
714
164
—
—
—
537 [253]
744
155
—
—
—
739 [349]
794
234
—
—
—
709 [335]
824
225
—
—
—
925 [437]
848
290
—
—
—
875 [413]
898
270
—
—
—
523 [247]
768
157
705 [333]
815
239
493 [233]
798
148
655 [309]
840
228
682 [322]
827
227
897 [423]
906
332
652 [308]
857
218
847 [400]
931
321
883 [417]
880
286
1015 [479]
928
356
833 [393]
930
266
915 [432]
953
326
—
—
—
650 [307]
861
227
—
—
—
600 [283]
886
216
—
—
—
851 [402]
925
318
—
—
—
801 [378]
950
307
—
—
—
963 [454]
955
341
—
—
—
863 [407]
980
311
—
—
—
599 [283]
989
204
—
—
—
549 [259]
1014
193
—
—
—
765 [361]
955
306
—
—
—
715 [337]
980
295
—
—
—
890 [420]
974
329
—
—
—
790 [373]
999
299
1201 [567] 1170[552] 1141 [538] 1104 [521] 1062 [501]
—
833
872
909
951
965
—
462
427
406
396
385
—
—
—
—
—
1194 [563] 1134 [535]
—
—
—
—
1024
1042
—
—
—
—
475
454
1151 [543] 1120 [529] 1091 [515] 1054 [497] 1012 [478]
—
883
922
959
1001
1015
—
442
407
386
376
365
—
—
—
—
—
1094 [516] 1034 [488]
—
—
—
—
1049
1067
—
—
—
1078 [509]
1060
417
—
—
—
978 [462]
1085
—
—
—
—
445
424
1493 [705] 1449 [684] 1363 [643] 1287 [607] 1211 [571]
—
822
858
885
931
958
—
540
519
506
484
459
—
—
—
—
—
1514 [714] 1411 [666]
—
—
—
—
1061
1069
—
—
—
—
710
702
1423 [672] 1379 [651] 1293 [610] 1217 [574] 1141 [538]
—
870
882
925
957
992
—
514
508
490
461
431
—
—
—
—
—
1414 [667] 1311 [619]
—
—
—
—
1067
1080
—
—
—
—
700
678
387
—
—
—
1315 [621]
1078
677
—
—
—
1215 [573]
1094
665
5.3 115/208/480V AIRFLOW PERFORMANCE DATA – (-)HSA/(-)HSL (PSC MOTOR) - continued
Model
Number
Motor
Speed
From
Factory
Manufacturer
Recommended
Air Flow Range
(Min / Max) CFM
Blower Size/
Motor H.P.
# of Speeds
Motor
Speed
0.10 [.02] 0.20 [.05] 0.30 [.07] 0.40 [.10] 0.50 [.12] 0.60 [.15] 0.70 [.17]
Low
4821/4824
No heater
High
1572/1824 CFM
[742/861 L/s]
10x10
3/4 [559]
2 Speed
High
4821/4824
with
25kw heater
Low
High
1225/1500
[709/814 L/s]
10x10
3/4 [559]
2 Speed
High
Low
6024
No heater
High
1766/1965 CFM
[833/927 L/s]
11x11
3/4 [559]
2 Speed
High
6024
with
30kw heater
Low
High
1225/1500
[553/678 L/s]
PSC
CFM[L/s] Air Delivery/RPM/Watts-115/208/480 Volts
External Static Pressure-Inches W.C.
11x11
3/4 [559]
2 Speed
High
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
1711 [807]
863
765
—
—
—
1641 [774]
930
700
—
—
—
1866 [881]
764
778
—
—
—
1796 [848]
828
735
—
—
—
1689 [797]
905
737
—
—
—
1619 [764]
950
660
—
—
—
1833 [865]
803
756
—
—
—
1763 [832]
860
718
—
—
—
1637 [773]
935
687
—
—
—
1567 [739]
985
630
—
—
—
1806 [852]
824
733
—
—
—
1736 [819]
878
705
—
—
—
1598 [754]
966
647
—
—
—
1528 [721]
1015
600
—
—
—
1772 [836]
856
715
—
—
—
1702 [803]
890
695
—
—
—
1542 [728]
992
621
1787 [843]
1089
695
1472 [695]
1041
580
1687 [796]
1095
670
1710 [807]
886
701
1967 [928]
948
850
1640 [774]
1001
678
1867 [881]
989
818
—
—
—
1679 [792]
1098
665
—
—
—
1579 [745]
1107
635
—
—
—
1916 [904]
959
827
—
—
—
1816 [857]
1005
795
—
—
—
1575 [743]
1110
630
—
—
—
1475 [696]
1120
615
—
—
—
1863 [879]
991
816
—
—
—
1763 [832]
1020
780
NOTE:
• All 208/240V PSC motors have voltage taps for 208 and 240 volts.
• All 208/240V PSC motors are shipped on high speed and 240 volts.
• All 115V PSC motors are shipped on high speed.
• If the application external static is less than 0.5” WC, adjust the motor speed to the low static speed as described below:
- Unplug the black motor wire off the relay on the control board and plug in the red motor wire.
- Replace the cap on the black motor wire.
• Voltage change (208/240V motors):
- Move the orange lead to transformer to 208V tap from 240V tap. Replace the wire cap on 240V tap.
- Unplug the purple motor wire off the transformer and plug in the yellow motor wire.
- Replace the cap on the purple motor wire.
• All 480V PSC motors are shipped on high speed.
• If the application external static is less than 0.5” WC, adjust the motor speed to the low static speed as described below for 3-ton through
4-ton air handlers.
- Unplug the black motor wire off the relay and remove the cap from the red motor wire.
- Plug the red motor wire to the relay and connect the black motor wire with the yellow motor wire.
• For 5-ton air handler, unplug the black motor wire off the relay and plug in the red motor wire, then cap the black motor wire.
There is no yellow motor wire on 5-ton air handler.
WARNING: Do not connect red motor wire with yellow motor wire in any circumstance on 480V PSC motors. Connecting red motor wire with
yellow motor wire will result in permanent motor damage.
• The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each
model.
• The following formula can be used to calculate the approximate airflow, if a smaller (N kw) than the maximum heater kit is installed.
Approximate Airflow = Airflow without heater - (Airflow without heater - Airflow with maximum heater) X (N kw/maximum heater kw)
25
5.4 115/208/240V AIRFLOW PERFORMANCE DATA – (-)HLA/(-)HLL (X-13 MOTOR)
Model
Number
Tonnage
Application
Motor
Speed
From
Factory
Manufacturer
Recommended
Air Flow Range
(Min / Max) CFM
Blower Size/
Motor H.P.
# of Speeds
Motor
Speed
0.10 [.02] 0.20 [.05] 0.30 [.07] 0.40 [.10] 0.50 [.12] 0.60 [.15] 0.70 [.17]
2
2417
No heater
1.5
5
509/681CFM
[240/321 L/s]
10x6
1/3 [249]
5 Speed
3
2417
with
13kw heater
2
1.5
5
490/666 CFM
[231/314 L/s]
10x6
1/3 [249]
5 Speed
3
4
2417
No heater
2.0
5
730/651 CFM
[345/307 L/s]
10x6
1/3 [249]
5 Speed
5
2417
with
13kw heater
4
2.0
5
711/626 CFM
[336/295 L/s]
10x6
1/3 [249]
5 Speed
5
2
3617
No heater
2.5
5
935/1084 CFM
[441/512 L/s]
10x8
1/2 [373]
5 Speed
3
3617
with
18kw heater
2
2.5
5
910/1059 CFM
[429/500 L/s]
10x8
1/2 [373]
5 Speed
3
4
3617
No heater
3.0
5
1130/1275 CFM
[533/602 L/s]
10x8
1/2 [373]
5 Speed
5
3617
with
18kw heater
4
3.0
5
1105/1250 CFM
[521/590 L/s]
10x8
1/2 [373]
5 Speed
5
2
4821
No heater
3.5
5
1337/1447 CFM
[631/683 L/s]
10x10
3/4 [559]
5 Speed
3
4221
with
20kw heater
26
2
3.5
5
1297/1333 CFM
[612/629 L/s]
X-13
CFM[L/s] Air Delivery/RPM/Watts-115/208/240 Volts
External Static Pressure-Inches W.C.
10x10
3/4 [559]
5 Speed
3
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
689 [325]
580
66
—
—
—
670 [316]
608
75
—
—
—
875 [413]
679
121
—
—
—
856 [404]
707
130
—
—
—
1093 [516]
671
153
—
—
—
1068 [504]
711
164
—
—
—
644 [304] 602 [284]
633
683
84
86
—
—
—
—
—
—
625 [295] 583 [275]
661
711
93
95
—
—
—
—
—
—
839 [396] 804 [379]
724
765
131
135
—
—
—
—
—
—
820 [387] 785 [370]
752
793
140
144
—
—
—
—
—
—
1050 [496] 1017 [480]
725
764
168
174
—
—
—
—
—
—
1025 [484] 992 [468]
765
804
179
185
—
—
—
—
—
—
563 [266]
728
88
—
—
—
544 [257]
756
97
—
—
—
762 [360]
810
142
—
—
—
743 [351]
838
151
—
—
—
977 [461]
809
180
—
—
—
952 [449]
849
191
—
—
—
509 [240]
—
781
—
91
—
681 [321] 644 [304]
835
879
136
143
490 [231]
—
809
—
100
—
666 [314] 629 [297]
855
899
144
151
730 [345]
—
852
—
143
—
862 [407] 828 [391]
904
940
203
215
711 [336]
—
880
—
152
—
837 [395] 803 [379]
924
960
211
223
935 [441]
—
852
—
188
—
1084 [512] 1040 [491]
896
936
249
257
910 [429]
—
892
—
199
—
1059 [500] 1015 [479]
936
976
260
268
—
—
—
603 [285]
916
152
—
—
—
588[277]
936
160
—
—
—
801 [378]
970
220
—
—
—
776 [366]
990
228
—
—
—
1001 [472]
971
261
—
—
—
976 [461]
1011
272
1270 [599] 1237 [584] 1199 [566] 1165 [550] 1130 [533]
—
775
816
846
882
926
—
237
249
259
268
277
—
—
—
—
—
1275 [602] 1244 [587]
—
—
—
—
963
999
—
—
—
—
338
348
1245 [588] 1212 [572] 1174 [554] 1140 [538] 1105 [521]
—
815
856
886
922
966
—
248
260
270
279
288
—
—
—
—
—
1250 [590] 1219 [575]
—
—
—
—
1003
1039
—
—
—
1211 [571]
1029
363
—
—
—
1186 [560]
1069
—
—
—
—
349
359
1473 [695] 1442 [681] 1401 [661] 1373 [648] 1337 [631]
—
781
825
867
905
949
—
257
271
303
307
315
—
—
—
—
—
1447 [683] 1433 [676]
—
—
—
—
987
1034
—
—
—
—
394
406
1433 [676] 1402 [662] 1361 [642] 1333 [629] 1297 [612]
—
831
875
919
954
989
—
277
295
313
319
325
—
—
—
—
—
1333 [629] 1300 [613]
—
—
—
—
1011
1046
—
—
—
—
350
364
374
—
—
—
1402 [662]
1065
405
—
—
—
1267 [598]
1080
377
5.4 115/208/240V AIRFLOW PERFORMANCE DATA – (-)HLA/(-)HLL (X-13 MOTOR) - continued
Model
Number
Tonnage
Application
Motor
Speed
From
Factory
Manufacturer
Recommended
Air Flow Range
(Min / Max) CFM
Blower Size/
Motor H.P.
# of Speeds
Motor
Speed
0.10 [.02] 0.20 [.05] 0.30 [.07] 0.40 [.10] 0.50 [.12] 0.60 [.15] 0.70 [.17]
4
4821
No heater
4.0
5
1535/1654 CFM
[724/781 L/s]
10x10
3/4 [559]
5 Speed
5
4821
with
25kw heater
4
4.0
5
1495/1614 CFM
[706/762 L/s]
10x10
3/4[559]
5 Speed
5
2
4824
No heater
4.0
3
1545/1732 CFM
[729/817 L/s]
11x11
3/4 [559]
5 Speed
3
4824
with
25kw heater
2
4.0
3
1505/1692 CFM
[710/798 L/s]
11x11
3/4 [559]
5 Speed
3
4
6024
No heater
5.0
5
1739/1905 CFM
[821/899 L/s]
11x11
3/4 [559]
5 Speed
5
6024
with
33kw heater
4
5.0
5
1699/1865 CFM
[802/880 L/s]
X-13
CFM[L/s] Air Delivery/RPM/Watts-115/208/240 Volts
External Static Pressure-Inches W.C.
11x11
3/4 [559]
5 Speed
5
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
CFM
RPM
Watts
1665 [786]
853
351
—
—
—
1625 [767]
894
389
—
—
—
1748 [825]
660
297
—
—
—
1708 [806]
680
305
—
—
—
1902 [898]
712
389
—
—
—
1862 [879]
750
410
—
—
—
1631 [770]
893
387
—
—
—
1591 [751]
932
400
—
—
—
1669 [788]
698
311
—
—
—
1629 [769]
736
330
—
—
—
1862 [879]
749
409
—
—
—
1822 [860]
790
420
—
—
—
1601 [756]
934
401
—
—
—
1561 [737]
970
410
—
—
—
1639 [773]
734
326
—
—
—
1599 [755]
760
341
—
—
—
1809 [854]
787
419
—
—
—
1769 [835]
810
430
—
—
—
1572 [742]
968
406
—
—
—
1532 [723]
1020
430
—
—
—
1599 [755]
762
340
—
—
—
1559 [736]
790
350
—
—
—
1781 [840]
815
432
—
—
—
1741 [822]
850
455
—
—
—
1535 [724]
1015
422
1654 [781]
1036
500
1495 [706]
1052
450
1614 [762]
1085
514
1545 [729]
795
353
1732 [817]
840
448
1505 [710]
820
361
1692 [798]
865
460
1739 [821]
856
459
1905 [899]
894
565
1699 [802]
880
479
1865 [880]
920
565
—
—
—
1624 [766]
1078
513
—
—
—
1584 [748]
1090
520
—
—
—
1683 [794]
872
467
—
—
—
1643 [775]
890
470
—
—
—
1866 [881]
924
570
—
—
—
1826 [862]
945
587
—
—
—
1563 [738]
1095
523
—
—
—
1523 [719]
1105
530
—
—
—
1630 [769]
899
480
—
—
—
1590 [750]
1014
481
—
—
—
1832 [865]
950
592
—
—
—
1792 [846]
970
610
NOTE:
X-13 motor speed changes
All X-13 motors have 5 speed tabs. Speed tab 1 is for continuous fan. Speed tab 2 (low static) and Speed tab 3 (high static) are for lower tonnage. Speed tab 4 (low static) and Speed tab 5 (high static) are for higher tonnage.
X-13 air handlers are always shipped from factory at speed tab 5, except for -4824, which is set at speed tab 3. For instance, RHLA-HM2417JA is always shipped at high
static 2-ton airflow (Speed tab 5). To change to 1.5-ton airflow, move the blue wire to Speed tab 2 or 3 on the X-13 motor.
The low static Speed tab 2 (lower tonnage) and 4 (higher tonnage) are used for external static below 0.5” WC. The high static Speed tab 3 (lower tonnage) and 5 (higher
tonnage) are used for external static exceeding 0.5” WC. Move the blue wire to the appropriate speed tab as required by the application needs.
• The airflow for continuous fan (Speed tab 1) is always set at 50% of the Speed tab 4.
• The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model.
• The following formula can be used to calculate the approximate airflow, if a smaller (N kw) than the maximum heater kit is installed.
Approximate Airflow = Airflow without heater - (Airflow without heater - Airflow with maximum heater) X (N kw/maximum heater kw)
27
6.0 DUCTWORK
Field ductwork must comply with the National Fire Protection Association NFPA 90A,
NFPA 90B and any applicable local ordinance.
! WARNING
Do not, under any circumstances, connect return ductwork to any other
heat producing device such as fireplace insert, stove, etc. Unauthorized
use of such devices may result in fire, carbon monoxide poisoning, explosion, personal injury or property damage.
Sheet metal ductwork run in unconditioned spaces must be insulated and covered with a
vapor barrier. Fibrous ductwork may be used if constructed and installed in accordance
with SMACNA Construction Standard on Fibrous Glass Ducts. Ductwork must comply
with National Fire Protection Association as tested by U/L Standard 181 for Class I Air
Ducts. Check local codes for requirements on ductwork and insulation.
• Duct system must be designed within the range of external static pressure the unit is
designed to operate against. It is important that the system airflow be adequate. Make
sure supply and return ductwork, grills, special filters, accessories, etc. are accounted
for in total resistance. See airflow performance tables in this manual.
• Design the duct system in accordance with “ACCA” Manual “D” Design for Residential
Winter and Summer Air Conditioning and Equipment Selection. Latest editions are
available from: “ACCA” Air Conditioning Contractors of America, 1513 16th Street,
N.W., Washington, D.C. 20036. If duct system incorporates flexible air duct, be sure
pressure drop information (straight length plus all turns) shown in “ACCA” Manual
“D” is accounted for in system.
• Supply plenum is attached to the 3/4” duct flanges supplied with the unit. Attach
flanges around the blower outlet.
IMPORTANT: If an elbow is included in the plenum close to the unit, it must not be
smaller than the dimensions of the supply duct flange on the unit.
• IMPORTANT: The front flange on the return duct if connected to the blower casing
must not be screwed into the area where the power wiring is located. Drills or sharp
screw points can damage insulation on wires located inside unit.
• Secure the supply and return ductwork to the unit flanges, using proper fasteners for
the type of duct used and tape the duct-to-unit joint as required to prevent air leaks.
7.0 REFRIGERANT CONNECTIONS
Keep the coil connections sealed until refrigerant connections are to be made. See the
Installation Instructions for the outdoor unit for details on line sizing, tubing installation,
and charging information.
Coil is shipped with a low (5 - 10 PSIG) pressure charge of dry nitrogen. Evacuate the
system before charging with refrigerant.
Install refrigerant tubing so that it does not block service access to the front of the unit.
Nitrogen should flow through the refrigerant lines while brazing.
Use a brazing shield to protect the cabinet’s paint from being damaged by torch flames.
After the refrigerant connections are made, seal the gap around the connections with
pressure sensitive gasket. If necessary, cut the gasket into two pieces for a better seal
(See Figure 4.)
7.1 TEV SENSING BULB
IMPORTANT: DO NOT perform any soldering with the TEV bulb attached to any line.
After soldering operations have been completed, clamp the TEV bulb securely on the
suction line at the 10 to 2 o’clock position with the strap provided in the parts bag.
Insulate the TEV sensing bulb and suction line with the provided pressure sensitive insulation (size 4” x 7”) and secure with provided wire ties.
IMPORTANT: TEV sensing bulb should be located on a horizontal section of suction
line, just outside of coil box.
7.2 CONDENSATE DRAIN TUBING
Consult local codes or ordinances for specific requirements.
IMPORTANT: When making drain fitting connections to the drain pan, use a thin layer of
Teflon paste, silicone or Teflon tape and install hand tight.
28
FIGURE 8
CONDENSATE DRAIN TRAP
DO NOT OPERATE UNIT WITHOUT
CONDENSATE DRAIN TRAP.
UNIT
3''
3''
DO NOT OVERTIGHTEN DRAIN FITTING
UNIT MUST BE SLIGHTLY INCLINED
TOWARD DRAIN CONNECTION.
IMPORTANT: When making drain fitting connections to drain pan, do not overtighten.
Overtightening fittings can split pipe connetions on the drain pan.
• Install drain lines so they do not block service access to front of the unit. Minimum
clearance of 24 inches is required for filter, coil or blower removal and service access.
• Make sure unit is level or pitched slightly toward primary drain connection so that
water will drain completely from the pan. (See Figure 8.)
• Do not reduce drain line size less than connection size provided on condensate drain
pan.
• All drain lines must be pitched downward away from the unit a minimum of 1/8” per
foot of line to ensure proper drainage.
• Do not connect condensate drain line to a closed or open sewer pipe. Run condensate to an open drain or outdoors.
• The drain line should be insulated where necessary to prevent sweating and damage
due to condensate forming on the outside surface of the line.
• Make provisions for disconnecting and cleaning of the primary drain line should it
become necessary. Install a 3 in. trap in the primary drain line as close to the unit as
possible. Make sure that the top of the trap is below connection to the drain pan to
allow complete drainage of pan (See Figure 8).
• Auxiliary drain line should be run to a place where it will be noticeable if it becomes
operational. Occupant should be warned that a problem exists if water should begin
running from the auxiliary drain line.
• Plug the unused drain connection with the plugs provided in the parts bag, using a
thin layer of teflon paste, silicone or teflon tape to form a water tight seal.
• Test condensate drain pan and drain line after installation is complete. Pour water into
drain pan, enough to fill drain trap and line. Check to make sure drain pan is draining
completely, no leaks are found in drain line fittings, and water is draining from the termination of the primary drain line.
7.3 DUCT FLANGES
Field-installed duct flanges (4 pieces) are shipped with units. Install duct flanges as
needed on top of the unit. (See Figure 3.)
8.0 AIR FILTER (not factory-installed)
• External filter or other means of filtration is required. Units should be sized for a maximum of 300 feet/min. air velocity or that recommended for the type filter installed.
Filter application and placement are critical to airflow, which may affect the heating and
cooling system performance. Reduced airflow can shorten the life of the system’s major
components, such as motor, limits, elements, heat relays, evaporator coil or compressor.
Consequently, we recommend that the return air duct system have only one filter location. For systems with a return air filter grill or multiple filter grills, can have a filter
installed at each of the return air openings.
If high efficiency filters or electronic air cleaners are used in the system, it is important
that the airflow is not reduced to maximize system performance and life. Always verify
that the system’s airflow is not impaired by the filtering system that has been installed,
by performing a temperature rise and temperature drop test.
29
IMPORTANT: DO NOT DOUBLE FILTER THE RETURN AIR DUCT SYSTEM. DO NOT
FILTER THE SUPPLY AIR DUCT SYSTEM.
! WARNING
Do not operate the system without filters. A portion of the dust entrained in the
air may temporarily lodge in the duct runs and at the supply registers. Any circulated dust particles could be heated and charred by contact with the air handler elements. This residue could soil ceilings, walls, drapes, carpets and other
articles in the house.
Soot damage may occur with filters in place, when certain types of candles, oil
lamps or standing pilots are burned.
9.0 SEQUENCE OF OPERATION
9.1 COOLING (COOLING ONLY OR HEAT PUMP)
• When the thermostat “calls for cooling,” the circuit between R and G is completed,
causing the blower relay (BR) to energize. The N.O. contacts will close, causing the
indoor blower motor (IBM) to operate. The circuit between R and Y is also completed:
This circuit closes the contactor (CC) in the outdoor unit starting the compressor
(COMP) and outdoor fan motor (OFM).
9.2 HEATING (ELECTRIC HEAT ONLY)
• When the thermostat “calls for heat,” the circuit between R and W is completed, and
the heater sequencer (HR1) is energized. The heating elements (HE) and the indoor
blower motor (IBM) will come on. Units with a second heater sequencer (HR2) can be
connected with the first sequencer (HR1) to W on the thermostat sub-base or connected to a second stage W2 on the sub-base.
9.3 HEATING (HEAT PUMP)
• When the thermostat “calls for heat,” the circuits between R and B, R and Y and R
and G are completed. Circuit R and B energizes the reversing valve (RV) switching it
to the heating position (remains energized as long as selector switch is in “heat” position). Circuit R and Y energizes the contactor (CC) starting the outdoor fan motor
(OFM) and compressor (COMP). Circuit R and G energizes the blower relay (BR)
starting the indoor blower motor (IBM).
• If the room temperature should continue to fall, circuit R and W is completed by the
second-stage heat room thermostat. Circuit R-W energizes a heat sequencer (HR ).
The completed circuit will energize supplemental electric heat. Units with a second
heater sequencer (HR ) can be connected with first sequencer (HR ) to W on thermostat or connected to a third heating stage W on the thermostat sub-base. A light on
the thermostat indicates when supplemental heat is being energized.
2
2
2
1
1
2
2
9.4 BLOWER TIME DELAY (HEATING OR COOLING)
• All models are equipped with a blower time delay (BTD) in lieu of a blower relay (BR)
(see wiring diagram). The blower will run for 30 seconds after the blower time delay
(BTD) is de-energized.
9.5 DEFROST (DEFROST HEAT CONTROL)
• For sequence of operation for defrost controls, see outdoor heat pump installation
instructions.
• Supplemental heat during defrost can be provided by connecting the purple (PU) pigtail in the outdoor unit to the W on the thermostat. This will complete the circuit
between R and W through a set of contacts in the defrost relay (DR) when the outdoor heat pump is in defrost. This circuit, if connected, will help prevent cold air from
being discharged from the indoor unit during defrost.
• For most economical operation, if cold air is not of concern during defrost, the purple
wire can be left disconnected. Supplemental heat will then come on only when called
for by second stage room thermostat.
30
9.6 EMERGENCY HEAT (HEATING HEAT PUMP)
• If selector switch on thermostat is set to the emergency heat position, the heat pump
will be locked out of the heating circuit, and all heating will be electric heat. Jumper
should be placed between W and E on the thermostat sub-base so that the electric
heat control will transfer to the first stage heat on the thermostat. This will allow the
indoor blower to cycle on and off with the electric heat when the fan switch is in the
auto position.
2
9.7 ROOM THERMOSTAT (ANTICIPATOR SETTING)
See instructions with outdoor section, condensing unit or heat pump for recommended
room thermostats.
• On units with one electric heat sequencer (HR ) (see wiring diagram on unit), heat
anticipator setting should be .16.
• On units with two electric heat sequencers (HR & HR ) (see wiring diagram on unit),
heat anticipator setting should be .32 if both are connected to same stage on thermostat. Setting should be .16 if (HR &HR ) are connected to separate stages.
NOTE: Some thermostats contain a fixed, non-adjustable heat anticipator. Adjustment
is not permitted.
• The thermostat should be mounted 4 to 5 feet above the floor on an inside wall of the
living room or a hallway that has good air circulation from the other rooms being controlled by the thermostat. It is essential that there be free air circulation at the location
of the same average temperature as other rooms being controlled. Movement of air
should not be obstructed by furniture, doors, draperies, etc. The thermostat should
not be mounted where it will be affected by drafts, hot or cold water pipes or air ducts
in walls, radiant heat from fireplace, lamps, the sun, T.V. or an outside wall. See
instruction sheet packaged with thermostat for mounting and installation instructions.
1
1
1
2
2
10.0 CALCULATIONS
10.1 CALCULATING TEMPERATURE RISE
• The formula for calculating air temperature rise for electric resistance heat is:
3.16 x Watts
Temperature Rise °F =
CFM
Where: 3.16 = Constant, CFM = Airflow
10.2 CALCULATING BTUH HEATING CAPACITY
• The formula for calculating BTUH heating capacity for electric resistance heat is:
BTUH Heating = Watts x 3.412
Where: 1 kW = 1000 Watts, 3.412 = Btuh/Watt
10.3 CALCULATING AIRFLOW CFM
• The formula for calculating airflow using temperature rise and heating BTUH for units
with electric resistance heat is:
CFM =
Heating BTUH
1.08 x Temp. Rise
10.4 CALCULATING CORRECTION FACTOR
• For correction of electric heat output (kW or BTUH) or temperature rise at voltages
other than rated voltage multiply by the following correction factor:
Correction Factor =
Applied Voltage
Rated Voltage
2
2
31
11.0 PRE-START CHECKLIST
PRE-START CHECKLIST
❍ YES
❍ NO
Is unit properly located, level, secure and serviceable?
❍ YES
❍ NO
Has auxiliary pan been provided under the unit with
separate drain? (Units installed above a finished
ceiling).
❍ YES
❍ NO
Is condensate line properly sized, run, trapped,
pitched and tested?
❍ YES
❍ NO
Is ductwork correctly sized, run, taped and insulated?
❍ YES
❍ NO
Have all cabinet openings and wiring been sealed
with caulking?
❍ YES
❍ NO
Is the filter clean, in place and of adequate size?
❍ YES
❍ NO
Is the wiring tight, correct and to the wiring diagram?
❍ YES
❍ NO
Is the unit properly grounded and protected (fused)?
❍ YES
❍ NO
Is the thermostat heat anticipator been set properly?
❍ YES
❍ NO
Is the unit circuit breaker(s) rotated properly “on” up
- “off” down?
❍ YES
❍ NO
Are the unit circuit breaker(s) line lug cover(s) in
place?
❍ YES
❍ NO
Are all access panels in place and secure?
Refer to outdoor unit installation instructions for system
start-up instructions and refrigerant charging instructions.
12.0 MAINTENANCE
For continuing high performance, and to minimize possible equipment failure, it is essential that periodic maintenance be performed on this equipment. Consult your local dealer
as to the proper frequency of maintenance and the availability of a maintenance contract
IMPORTANT: Before performing any service or maintenance procedures, see the
“Safety Information” section at the front of this manual.
! WARNING
Units with circuit breaker(s) meet requirements as a service disconnect switch,
however, if access is required to the line side (covered) of the circuit breaker,
this side of the breaker(s) will be energized with the breaker(s) de-energized.
Contact with the line side can cause electrical shock resulting in personal
injury or death.
12.1 AIR FILTER (NOT FACTORY-INSTALLED)
Check the system filter every ninety days or as often as found to be necessary and if
obstructed, clean or replace at once.
FILTER MAINTENANCE
Have your qualified installer, service agency or HVAC professional instruct you on how
to access your filters for regular maintenance.
IMPORTANT: Do not operate the system without a filter in place.
• New filters are available from your local distributor.
32
12.2 INDOOR COIL - DRAIN PAN - DRAIN LINE
Inspect the indoor coil once each year for cleanliness and clean as necessary. In some
cases, it may be necessary to remove the filter and check the return side of the coil with
a mirror and flashlight.
IMPORTANT: Do not use caustic household drain cleaners, such as bleach, in the condensate pan or near the indoor coil. Drain cleaners will quickly damage the indoor coil.
12.3 BLOWER MOTOR AND WHEEL
Inspect the blower motor and wheel for cleanliness. It should be several years before it
would become necessary to clean the blower motor and wheel.
• If it becomes necessary to remove the blower assembly from the unit, see instructions
on removal and disassembly of motor, blower and heater parts.
• The blower motor and wheel may be cleaned by using a vacuum with a soft brush
attachment. Remove grease with a mild solvent such as hot water and detergent. Be
careful not to disturb the balance weights (clips) on the blower wheel blades. Do not
drop or bend wheel as balance will be affected.
12.4 LUBRICATION
The blower motor sleeve bearings are pre-lubricated by the motor manufacturer and do
not have oiling ports. Motor should be run for an indefinite period of time without additional lubrication.
12.5 BLOWER ASSEMBLY REMOVAL AND REPLACEMENT
Removing the blower assembly is not required for normal service and maintenance.
Removal is necessary for replacement of defective parts such as motor, blower wheel.
After extended use, removal of the blower assembly may become necessary for a thorough cleaning of the blower motor and wheel.
! WARNING
If removal of the blower assembly is required, all disconnect switches supplying power to the equipment must be de-energized and locked (if not in sight of
unit) so the field power wires can be safely removed from the blower assembly.
Failure to do so can cause electrical shock resulting in personal injury or
death.
• Mark field power supply wiring (for replacement) attached to terminal block or circuit
breaker(s) on blower assembly. Remove wiring from terminal block or circuit breaker(s).
• Mark low voltage control wiring (for replacement) where attached to unit control pigtails on right side of blower housing. Remove wire nuts attaching field control wiring to
unit control pigtails.
• Remove 4 screws holding blower assembly to front channel of cabinet and pull blower
assembly from cabinet.
• To replace blower assembly, slide blower assembly into blower deck. Make sure
blower assembly engages lances in deck properly. If assembly hangs up, check to
make sure top and bottom are lined up in proper locations.
• Slide blower assembly to back of cabinet and make sure it is completely engaged.
• Replace 4 screws holding blower assembly to front channel of cabinet. Take care not
to strip screws, just snug into place.
• Replace low voltage control wiring with wire nuts and make sure wiring is to wiring
diagram and a good connection has been made.
• Replace field power wiring to terminal block or circuit breaker(s) on control area of
blower assembly. Make sure wires are replaced as they were, check wiring diagram if
necessary. Tighten supply power wiring securely to terminals lugs.
• Make sure wiring is within cabinet and will not interfere with access door. Make sure
proper separation between low voltage control wiring and field power wiring has been
maintained.
• Replace blower assembly control access panel before energizing equipment.
33
12.6 MOTOR REPLACEMENT
With the blower assembly removed, the indoor blower motor can be removed and
replaced using the following procedure:
• Remove motor leads from the motor capacitor and blower relay. Note lead locations
for ease of reassembly. Pull leads from plastic bushing in blower side.
• Loosen the set screw holding blower wheel onto the motor shaft. Shaft extends
through blower hub so that a wrench can be used on the extended shaft to break the
shaft loose if necessary. Be careful not to damage shaft. A wheel puller can be used
on the groove in the blower hub if necessary.
• Remove 4 metal screws holding motor mounts to blower side and remove motor from
blower assembly.
• To install new motor, remove 1 screw holding motor mounts to motor shell and
remove mounts (four) from motor.
• Install (four) motor mounts to motor using same screw or screws supplied with
replacement motor.
! WARNING
To avoid electrical shock which can result in personal injury or death, use only
the screws furnished in the motor shell mounting holds. Screws are #8-18 x .25
in. long blunt nose thread forming. Screws longer than 1/4 in. may contact the
motor winding.
• To reassemble, insert motor shaft through hub in blower wheel and orient motor to
original position with motor leads and motor label to front of blower (control area).
• Reassemble 12 sheet metal screws through motor mounts into blower side. Do not
overtorque screws, blower side is light gage sheet metal, just snug screws tight
enough to hold motor mounts in position.
• Turn motor shaft so that flat on shaft is located under blower wheel setscrew, and
blower wheel is centered in blower housing with the same distance on each side
between the inlet venturi and outside of blower wheel. Tighten setscrew on motor
shaft. Turn wheel by hand to make sure it runs true without hitting blower sides.
• Reassemble motor wiring to capacitor and blower relay making sure that wires match
wiring diagram and are tight and secure.
12.7 BLOWER WHEEL REPLACEMENT
With the blower assembly removed and the motor assembly removed (see above
instructions), remove the 4 screws holding the blower wrap (cutoff) to the blower sides.
• With wrap (cutoff) screws removed, cut off end of blower wrap will spring up. Lifting
wrap blower wheel is removed through the discharge opening in the blower housing.
• To replace, make sure wheel is oriented properly with hub to the opposite side from
the motor. Lift blower wrap and insert blower wheel through discharge opening in the
blower housing.
• Hold blower wrap down into position and replace two screws holding blower wrap to
blower sides.
• See motor replacement and blower assembly instructions for remaining assembly
procedure.
13.0 REPLACEMENT PARTS
Any replacement part used to replace parts originally supplied on equipment must be the
same as or an approved alternate to the original part supplied. The manufacturer will not
be responsible for replacement parts not designed to physically fit or operate within the
design parameters the original parts were selected for.
These parts include but are not limited to: Circuit breakers, heater controls, heater limit
controls, heater elements, motor, motor capacitor, blower relay, control transformer,
blower wheel, filter, indoor coil and sheet metal parts.
34
When ordering replacement parts, it is necessary to order by part number and include
with the order the complete model number and serial number from the unit data plate.
(See parts list for unit component part numbers).
14.0 ACCESSORIES-KITS-PARTS
• Combustible Floor Base RXHB- for downflow applications.
Model Cabinet Size
Combustible Floor
Base Model Number
17
21
24
RXHB-17
RXHB-21
RXHB-24
• Jumper Bar Kit 3 Ckt. to 1 Ckt. RXBJ-A31 is used to convert single phase multiple
three circuit units to a single supply circuit. Kit includes cover and screw for line side
terminals.
• Jumper Bar Kit 2 Ckt. to 1 Ckt. RXBJ-A21 is used to convert single phase multiple
two circuit units to a single supply circuit. Kit includes cover and screw for line side
terminals.
NOTE: No jumper bar kit is available to convert three phase multiple two circuit units
to a single supply circuit.
• External Filter Base RXHF- (See Figure 9)
Model Cabinet Size
Filter Size
17
21
24
16 x 20 [406 x 508]
20 x 20 [508 x 508]
25 x 20 [635 x 508]
Part Number
RXHF-17
RXHF-21
RXHF-24
Accommodate
1” or 2”
filter
A
B
15.70
19.20
22.70
17.50
21.00
25.50
• External Filter Rack: RXHF-B (See Figure 9)
FIGURE 9
EXTERNAL FILTER BASE: RXHF-
Model Cabinet Size
17
21
24
Filter Size
16 x 20
20 x 20
25 x 20
Part Number
RXHF-B17
RXHF-B21 Accommodate
1” filter
RXHF-B24
A
16.90
20.40
25.00
B
20.77
20.77
21.04
35
FIGURE 10
EXTERNAL FILTER RACK: RXHF- B17, B21, B24
➦
➦
1.50
A
B
• Horizontal Adapter Kit RXHHThis horizontal adapter kit is used to convert Upflow/Downflow only models to horizontal flow. See the following table to order proper horizontal adapter kit.
Coil Model
2414
2417
3617/3621
4821/4824
6024
Horizontal Adapter Kit
Model Number (Single Qty.)
RXHH-A01
RXHH-A02
RXHH-A03
RXHH-A04
RXHH-A05
Horizontal Adapter Kit
Model Number (10-pak Qty.)
RXHH-A01x10
RXHH-A02x10
RXHH-A03x10
RXHH-A04x10
RXHH-A05x10
• Auxiliary Horizontal Overflow Pan RXBM-
36
Nominal Cooling
Capacity Tons
Auxiliary Horizontal
Overflow Pan Accessory
Model Number
11⁄2 - 3
RXBM-AC48
31⁄2 - 5
RXBM-AC61
CM 0707