Pulsar Radiant Panel

Transcription

Pulsar Radiant Panel
Heating / Air Conditioning
Pulsar Radiant Panel
Heating / Air Conditioning
ENVIRONMENTAL COMFORT
Sabiana s.p.a. • via Piave, 53 • 20011 Corbetta • Milano • Italy • phone +39.02.97203.1 r.a. / +39.02.97270429 / +39.02.97270576
fax +39.02.9777282 / +39.02.9772820 • www.sabiana.it • [email protected]
Copertina PULSAR Inglese.indd 1
C/07/09
COD. A4830100
PULSAR - EX - 07/09
Pulsar Radiant Panel
ISO 9001 - Cert. n° 0545/4
Unit heaters
Radiant panels
Fan coils
Air handling units
Flues
ENVIRONMENTAL COMFORT
25-06-2009 9:55:40
NON-ACTIVE AESTHETIC PANEL - W MODEL
Pulsar
The aesthetic panels are used when the active panels do not need to be installed and when, for
aesthetic reasons or local specifications, a non-active panel has to be installed to complete a strip.
Available in 2 models:
He a t i n g
Air Con d i t i o n i n g
Size
1
2
Length (mm)
610
1234
Code
9083480
9083490
Can be cut to measure on site.
ENVIRONMENTAL COMFORT
Hanging holes
on the lateral sides of the panel.
Hanging holes on the sides
of the hanging brackets (distance 521 mm).
ACCESSORIES FOR PANELS NOT INSTALLED INTO FALSE CEILINGS - W MODEL
CONTENTS
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
INTRODUCTION
MAIN ADVANTAGES OF THE PULSAR
TECHNICAL SPECIFICATIONS
MEAN SURFACE TEMPERATURE OF THE PULSAR PANEL
LOWEST WATER FLOW
PRESSURE DROP
WATER CONNECTION DIAGRAM
OPERATING LIMITS
SUGGESTED LOWEST INSTALLATION HEIGHT
TABLE OF POSSIBLE COMBINATIONS
POSSIBLE CONNECTIONS
ACCESSORIES
HANGING SYSTEMS
INTEGRATION WITHIN FALSE CEILINGS
INSTALLATION WITHOUT FALSE CEILING
PULSAR WITH PERFORATED PANEL
NON-ACTIVE AESTHETIC PANEL
ACCESSORIES FOR PANELS NOT INSTALLED INTO FALSE CEILINGS
Page
Page
Pages
Page
Page
Pages
Page
Page
Page
Page
Page
Page
Page
Page
Page
Page
Page
Page
3
4
5/8
9
9
9 / 10
11
11
11
12
12
13 / 14
15
16
17
18
18 / 19
19
The descriptions and illustrations provided in this publication are not binding: Sabiana reserves the right,
whilst maintaining the essential characteristics of the types described and illustrated, to make, at any time,
without the requirement to promptly update this piece of literature, any changes that it considers useful
for the purpose of improvement or for any other manufacturing or commercial requirements.
Copertina PULSAR Inglese.indd 2
Inspection panel
19
25-06-2009 9:55:44
INTRODUCTION
Pulsar
SABIANA is the leading company in Europe in the design, production and sale of radiant panels
operating on hot water, high temperature hot water and steam.
Since 1971, over 5 million square metres of panels installed in different environments (small, medium
and large industries, hangars, gyms and theatres, small and large offices) prove the quality of the
SABIANA radiant heating system and products.
Heat by radiation means absolute silence, no movement of air and a uniform temperature in the
entire environment. In effect, being distributed better, the heat is more pleasant and comfort is
optimised, without increasing the air temperature. The result is a feeling of absolute comfort with
an air temperature that is 3°C lower than the operative temperature perceived by people.
The efficiency of the SABIANA radiant panels is also economic. In fact, besides the energy savings
due to the fact that the operative temperature is different from the air temperature, this totally static
product does not, unlike the traditional systems, have an electric motor and does not require
maintenance nor the consumption of electricity.
This translates into long-lasting efficiency. The SABIANA radiant panels have a practically unlimited
duration.
The SABIANA radiant panels can be described as the hygienic heating system par excellence.
The system does not create noise nor movement of air and therefore dust. In addition, it avoids
annoying streams of air and the circulation of germs, dust and fragrances and thus represents
an important contribution to the prevention of allergies and illnesses.
MAIN ADVANTAGES OF THE PULSAR
Pulsar
Thermal performance
-The PULSAR radiant panel is totally static (no circulation of air and no movement of dust).
-Very low thermal gradient between the floor and the ceiling.
-Extremely fast response to changes in settings, without thermal inertia.
-The operating principle of the PULSAR radiant panels is reversible, and thus cooling operation is possible using
the radiant ceiling panels, by connection to a chiller or heat pump.
Appearance
-None of the peripheral walls are affected by the installation.
-The PULSAR radiant panel can be perfectly integrated into all types of false ceiling.
-The visible side is perfectly smooth, adapting to any type of architecture.
-Other RAL colours available on request.
Modularity
-Given its modular dimensions and the design of the water connections, the PULSAR panels can be installed in
sequence with ceiling light panels, in complete compliance with the regulations on artificial lighting.
Hygiene
-The design of the PULSAR panel allows it to be installed in any building, including hospitals and clinics. Indeed, its
completely smooth visible surface is recommended, as it allows sanitisation by spraying for combating nosocomial
illnesses in hospitals.
-The radiation concept, by avoiding considerable movements of air, prevents the spreading of microbes and
bacteriological pollution.
Safety
-The PULSAR radiant panels are inaccessible to the people in the room. Therefore there is no risk of burning or
electric shock in schools and paramedical environments.
-No risk of vandalism, in any environment.
Comfort
-By design, the PULSAR radiant panel guarantees a uniform temperature in all seasons.
-The PULSAR radiant panel is a totally static heating system without the circulation of air and without lifting dust.
-The operation of the PULSAR is completely silent.
-In summer, the PULSAR panel can be used for cooling without creating steams of air and with a uniform temperature
throughout the environment.
Savings
-The heating requirement of a building heated with the PULSAR radiant panels is, according to the EN 12831 standard,
much lower than the requirement
with traditional heating systems.
-The experience acquired by SABIANA
in the field of radiant panels guarantees
the reliability of the PULSAR over
time.
-The PULSAR does not require special
maintenance and consequently has
no maintenance costs.
Assembly
-The dimensions of the PULSAR
radiant panels make them easy to
handle on site.
-The panels are connected by flexible
pipes without welding.
Connections supplied not mounted
Pulsar
TECHNICAL SPECIFICATIONS
Technical description
The SABIANA PULSAR radiant panels are supplied in four sizes, which can be perfectly integrated into any false
ceiling.
Indeed, the lengths of 1.20, 1.80, 2.40 and 3.00 m ensure optimum integration into 600 x 600 mm modular ceilings,
the standard dimension for false ceiling panels in Europe.
The visible side is perfectly flat, meaning that the PULSAR radiant panels can match all types of false ceiling panels
available on the market.
As standard, the panels are supplied in the colour RAL 9010, with a satin finish created by an epoxy-polyester coat
dried in a furnace at 180°C. Other RAL colours are also available for the architect to choose from.
The PULSAR radiant panels are made of a radiating galvanized steel plate, 1 mm thick.
On the panel is fixed a copper pipe, 0.75 mm
thick and with 22 mm of external diameter.
The pipe is oblong-shaped in order to optimize
the contact surface with the radiant panel.
The galvanized hanging strips welded to the
panels hold the correct spacing of the tubes
and secure the best surface contact between
the tube and the panel.
The paint complies with the European Standard 76/769/EEC.
Class of reaction to fire: A1
Emission of the radiant surface: Є = 0,96
The PULSAR is supplied with an insulating layer of mineral wool (30 mm thick) protected by an aluminium sheet
(25 micron thick) to be mounted on the top of the panel.
Insulation specifications:
Class A1 according to EN 13501-1 standards
Thermal conductivity 0,037 W/mK (according to UNI CTI 7745 and UNI FA 112 standard)
Density 14 kg/m3
Thermal resistance 0,81 m2K/W
P Model
W Model
Pulsar
TECHNICAL SPECIFICATIONS
Pulsar P installed within false ceilings
Weights and Dimensions
Pulsar P STANDARD
Pulsar PA
Pulsar PB
Size
1
2
3
4
P STANDARD
Model
Code
P.1
0083090
P.2
0083150
P.3
0083210
P.4
0083270
PA
Model
PA.1
PA.2
PA.3
PA.4
Code
0083091
0083151
0083211
0083271
PB
Model
PB.1
PB.2
PB.3
PB.4
Code
0083092
0083152
0083212
0083272
Length
(mm)
Weight
(kg)
Water content
(litres)
1195
1795
2395
2995
13.8
20.7
27.6
34.5
1.3
2.0
2.8
3.5
Pulsar
TECHNICAL SPECIFICATIONS
Pulsar W not installed within false ceilings
Weights and Dimensions
Pulsar W STANDARD
Pulsar WA
Pulsar WB
Size
1
2
3
4
W STANDARD
Model
Code
0083100
W.1
0083160
W.2
0083220
W.3
0083280
W.4
WA
Model
WA.1
WA.2
WA.3
WA.4
Code
0083101
0083161
0083221
0083281
Model
WB.1
WB.2
WB.3
WB.4
WB
Code
0083102
0083162
0083222
0083282
Length
(mm)
Weight
(kg)
Water content
(litres)
1234
1858
2482
3106
14
21
28
35
1.3
2.0
2.8
3.5
Pulsar
TECHNICAL SPECIFICATIONS
Emission
Characteristic curve of the PULSAR taken from tests carried out as per the EN 14037 standard:
Q = K • (∆Tm)n
Q
= emission W/m
K
= heating coefficient of the unit = 3,28086 W/m
∆Tm = difference between the mean water temperature and the room temperature
n
= heating exponent of the unit = 1,1536
The emission of the Sabiana PULSAR radiant panels has been certified by the laboratory at the University of Stuttgart
H.L.K. applying the harmonised European Standard EN 14037, with the report number DC205 D12.2108
In accordance with part 2 of the standard, the K coefficient is equal to the above one divided by 1.1.
Nominal emission for a meter of P.1 ÷ P.4 Pulsar panels with ∆Tm = 55°C : 334 W/m
Total nominal emission of Pulsar panels with ∆Tm = 55°C:
Pulsar P.1
L = 1186 mm
Pulsar P.2
L = 1786 mm
Pulsar P.3
L = 2386 mm
Pulsar P.4
L = 2986 mm
EN 14037
05
NOTE: the emission of the W panel are the same of the P panel.
Ceiling
radiant panels
Thermal emissions in accordance with the European Standard EN 14037
∆tm
°C
89
88
87
86
85
84
83
82
81
80
79
78
77
76
Emission
W/m
582
574
567
559
552
544
537
529
522
515
507
500
492
485
∆tm
°C
75
74
73
72
71
70
69
68
67
66
65
64
63
62
Emission
W/m
478
470
463
456
448
441
434
427
419
412
405
398
391
383
∆tm
°C
61
60
59
58
57
56
55
54
53
52
51
50
49
48
Emission
W/m
376
369
362
355
348
341
334
327
320
313
306
299
292
285
∆tm
°C
47
46
45
44
43
42
41
40
39
38
37
36
35
34
Emission
W/m
279
272
265
258
251
245
238
231
225
218
211
205
198
192
∆tm
°C
33
32
31
30
29
28
27
26
25
24
23
22
21
20
Emission
W/m
185
179
172
166
160
153
147
141
134
128
122
116
110
104
Cooling emissions in accordance with the European Standard EN 14240
∆tm
°C
5
6
7
8
9
10
11
12
13
14
15
Cooling emission
With insulation
Without insulation
W/m2
W/m
W/m
W/m2
52
38
22
30
63
47
28
37
74
32
55
43
86
38
64
50
98
43
73
57
110
81
47
64
122
90
53
71
134
58
99
79
146
63
108
86
158
69
117
93
171
74
127
100
Example:
Water temperature 17/21°C,
air temperature 28°C - 50%
means ∆tm = 9°C.
The cooling emission
of the PULSAR is 43 W/m.
∆tm =difference between
the average water temperature
and the room temperature
Pulsar
MEAN SURFACE TEMPERATURE
OF THE PULSAR PANEL
LOWEST WATER FLOW
Lowest water flow to be supplied in order to obtain the correct emission.
Leaving water temperature
Lowest water flow
°C
l/h
40
65
60
48
80
37
PRESSURE DROP
PRESSURE DROP
10
Pulsar
Pulsar
WATER CONNECTION DIAGRAM
OPERATING LIMITS
Water circuit
Maximum water pressure: 4 bar
Maximum entering water temperature: +90°C
SUGGESTED LOWEST INSTALLATION HEIGHT (in m above the floor)
Maximum water temperature °C
50
60
70
80
90
m
2.5
2.7
2.9
3.1
3.3
11
TABLE OF POSSIBLE COMBINATIONS
Pulsar
P Model
Total
Composition without
length (m) intermediate panel
1,20
1,80
2,40
3,00
3,60
4,20
4,80
5,40
6,00
6,60
7,20
8,40
9,00
P.1
P.2
P.3
P.4
2 x P.2
P.2 + P.3
2 x P.3
P.3 + P.4 or 3 x P.2
2 x P.4
2 x P.3 + 1 x P.2
3 x P.3
2 x P.4 + 1 x P.3
3 x P.4
Composition
Composition without
with intermediate panel * intermediate panel
W Model
Composition
with intermediate panel *
W.1
W.2
W.3
W.4
P.1 + Panel + P.1
W.1 + Panel + W.1
2 x W.2
P.2 + Panel + P.2
W.2 + Panel + W.2
W.2 + W.3
2 x W.3
W.3 + W.4 or 3 x W.2
P.3 + Panel + P.3
W.3 + Panel + W.3
2 x W.4
2 x W.3 + 1 x W.2
P.4 + Panel + P.4
W.4 + Panel + W.4
3 x W.3
P.3 + Panel + P.3 + Panel + P.3 2 x W.4 + 1 x W.3 W.3 + Panel + W.3 + Panel + W.3
3 x W.4
-
POSSIBLE CONNECTIONS
Connection of 2 or 3 panels in series
Connection in parallel
*
12
This may be a false ceiling panel, a light or one of the PULSAR non-active aesthetic panels
ACCESSORIES
Pulsar
FITTINGS
Screw fittings (Caleffi)
Code 9083455
1.
2.
3.
4.
Ring nut
Metal ring
Black O-ring seals
Fitting
Pressfittings (Geberit)
Code 9083456
NOTE: two kits of fittings must be used for PA, PB, WA and WB panels (1 kit = 2 fittings).
13
Pulsar
ACCESSORIES
Flexible pipe compliant with CSTB standard
- Diameter 1/2”
- Made of: EPDM rubber
- With external stainless steel layer
- Operation between -20°C and +110°C
Assembly of 2 Standard Pulsar
Assembly of 3 Standard Pulsar
Flexible pipe length
mm
1450
2000
Flexible pipe length
mm
2800
3300
Code
6083521
6083522
Code
9083473
9083474
Assembly of 3 PA / WA and PB / WB panels
Model
1
2
3
4
Model
1
2
3
4
14
Code
PA
WA
0083091
0083101
0083151
0083161
0083211
0083221
0083271
0083281
Code
PB
WB
0083092
0083102
0083152
0083162
0083212
0083222
0083272
0083282
Pulsar
HANGING SYSTEMS
Hanging brackets
Pulsar P.1 and P.2 / W.1 and W.2
Pulsar P.3 and P.4 / W.3 and W.4
Code
0083090
0083150
0083210
0083270
0083100
0083160
0083220
0083280
Description
Pulsar P.1
Pulsar P.2
Pulsar P.3
Pulsar P.4
Pulsar W.1
Pulsar W.2
Pulsar W.3
Pulsar W.4
L
1195
1795
2395
2995
1234
1858
2482
3106
A
900
1500
1050
1350
864
1488
1056
1368
B
595
595
595
595
610
610
610
610
C
133.5
133.5
133.5
133.5
171
171
171
171
D
161.5
161.5
161.5
161.5
199
199
199
199
E
37
37
37
37
44.5
44.5
44.5
44.5
The maximum vertical bending f of the Pulsar radiant panels
between two suspension points is less than 2 mm.
The maximum bending from the longitudinal axis of the 3m panels is 5mm.
Typical hanging options
15
INTEGRATION WITHIN FALSE CEILINGS
Pulsar
P Model
False ceiling structure
16
Covered false ceiling structure
INSTALLATION WITHOUT FALSE CEILING
Pulsar
W Model
with side skirts
Composition
Ceiling installation (with suspension wire)
Code
6083550
6083551
6083552
6083553
Mounting of side skirts
W1
Description
Side skirt (length 4000mm)
Side skirt bracket (length 4000mm)
Corner
Suspension steel wire
Quantiy for installation
Quantity for each Pulsar
W2
W3
W4
(Length installation mm x 2) + 600
4000
2
2
2
2
2
3
2
3
Example with W3 Pulsar + inspection panel:
•Installation length = 2482mm + 305mm = 2787mm
•Needed side skirts = [(2787mm x 2) + 600mm] / 4000mm = 6174mm / 4000mm = 1,54 unit
•Side skirts are supplied only in lengths of 4000mm, so 2 units are needed
The order
should then be made
as follow:
Code
6083550
6083551
6083552
6083553
Description
Side skirt (length 4000mm)
Side skirt bracket (length 4000mm)
Corner
Suspension steel wire
Quantity
2
2
2
3
17
Pulsar
PULSAR WITH PERFORATED PANEL
Special version with perforated panel:
it is supplied with extra thermal acoustic insulation,
which allows the attenuation
of noise reverberation in the room.
Weights and dimensions like
Standard panel.
NON-ACTIVE AESTHETIC PANEL - P MODEL
The aesthetic panels are used when the active
panels do not need to be installed and when,
for aesthetic reasons or local specifications, a
non-active panel has to be installed to complete
a strip.
Available in 2 models:
Size
1
2
Length (mm)
595
1195
Code
9083350
9083410
Can be cut to measure on site.
Hanging holes
on the lateral sides of the panel.
18
Hanging holes
on the sides of the hanging brackets
(distance 521 mm).
NON-ACTIVE AESTHETIC PANEL - W MODEL
Pulsar
The aesthetic panels are used when the active panels do not need to be installed and when, for
aesthetic reasons or local specifications, a non-active panel has to be installed to complete a strip.
Available in 2 models:
He a t i n g
Air Con d i t i o n i n g
Size
1
2
Length (mm)
610
1234
Code
9083480
9083490
Can be cut to measure on site.
ENVIRONMENTAL COMFORT
Hanging holes
on the lateral sides of the panel.
Hanging holes on the sides
of the hanging brackets (distance 521 mm).
ACCESSORIES FOR PANELS NOT INSTALLED INTO FALSE CEILINGS - W MODEL
CONTENTS
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
INTRODUCTION
MAIN ADVANTAGES OF THE PULSAR
TECHNICAL SPECIFICATIONS
MEAN SURFACE TEMPERATURE OF THE PULSAR PANEL
LOWEST WATER FLOW
PRESSURE DROP
WATER CONNECTION DIAGRAM
OPERATING LIMITS
SUGGESTED LOWEST INSTALLATION HEIGHT
TABLE OF POSSIBLE COMBINATIONS
POSSIBLE CONNECTIONS
ACCESSORIES
HANGING SYSTEMS
INTEGRATION WITHIN FALSE CEILINGS
INSTALLATION WITHOUT FALSE CEILING
PULSAR WITH PERFORATED PANEL
NON-ACTIVE AESTHETIC PANEL
ACCESSORIES FOR PANELS NOT INSTALLED INTO FALSE CEILINGS
Page
Page
Pages
Page
Page
Pages
Page
Page
Page
Page
Page
Page
Page
Page
Page
Page
Page
Page
3
4
5/8
9
9
9 / 10
11
11
11
12
12
13 / 14
15
16
17
18
18 / 19
19
The descriptions and illustrations provided in this publication are not binding: Sabiana reserves the right,
whilst maintaining the essential characteristics of the types described and illustrated, to make, at any time,
without the requirement to promptly update this piece of literature, any changes that it considers useful
for the purpose of improvement or for any other manufacturing or commercial requirements.
Copertina PULSAR Inglese.indd 2
Inspection panel
19
25-06-2009 9:55:44
Heating / Air Conditioning
Pulsar Radiant Panel
Heating / Air Conditioning
ENVIRONMENTAL COMFORT
Sabiana s.p.a. • via Piave, 53 • 20011 Corbetta • Milano • Italy • phone +39.02.97203.1 r.a. / +39.02.97270429 / +39.02.97270576
fax +39.02.9777282 / +39.02.9772820 • www.sabiana.it • [email protected]
Copertina PULSAR Inglese.indd 1
C/09/09
COD. A4830100
PULSAR - EX - 09/09
Pulsar Radiant Panel
ISO 9001 - Cert. n° 0545/4
Unit heaters
Radiant panels
Fan coils
Air handling units
Flues
ENVIRONMENTAL COMFORT
30-07-2009 8:59:21

Similar documents

Pulsar FE Brochure

Pulsar FE Brochure The descriptions and illustrations provided in this publication are not binding: Sabiana reserves the right, whilst maintaining the essential characteristics of the types described and illustrated,...

More information