Air Cooled Chiller

Transcription

Air Cooled Chiller
sm
Air Cooled Chiller
Product Data Catalog
For chillers with R-410A refrigerant
For Modules: ASP010X
ASP015X
ASP020X
ASP030X
ASP060X
PMP01
PMP02
PMP03
PMP04
FCP01
FCP02
FCP03
FCP04
ASP-00T
ASP-00G
AIRSTACK PACKAGED AIR COOLED
Table of Contents
Product Introduction................................................................................................................................................... 3
Performance Data....................................................................................................................................................... 4
Pump Selection Charts................................................................................................................................................. 6
General Data Table...................................................................................................................................................... 7
Pressure Drop Tables................................................................................................................................................... 9
Selection Data........................................................................................................................................................... 10
Chiller Drawing......................................................................................................................................................... 12
Required Piping and Electrical Data............................................................................................................................ 14
Mechanical Specifications.......................................................................................................................................... 15
Model Number Nomenclature
Existing
MS
50
New
MS
X
050
1
X
H
N
1
W
1
H
0
R-410A
1
A
0
A
A
-410A
Refrigerant
Condenser6
Evaporator5
AHRI Version - if applicable
Application4
Module Number (1 - single, 2 - multiple)
Voltage3
Configuration2
AHRI Certified (C - certified, N - Not certified)
Compressor Type1
Module Nominal Capacity (10 - 160 tons)
Series
B: Bristol, C: Trane Cornerstone, R: Bitzer Screw, S: Trane Scroll, T: Danfoss Turbocor, Z: Copeland scroll (old elec), X: Copeland Scroll (ZP), A: Copeland Scroll (ZR)
1- Standard, 2- Total access, 3 - Evap extended headers, 4 - Cond extended headers, 5 - Both extended headers, V - others
3
A - 208/3/60, L - 230/3/60, H - 460/3/60, C - 575/3/60, D - 200/3/50, E - 400/3/50, F - 380/3/60, S - 220/230/1/60, V - other
4
C - Single module temp controller, A-Air Cooled split, D - Cond unit, F - Fluid cooler (high temp),H - Heat recovery, R - Heat pump, W - Water cooled
5
A - Brazed SS, B - Brazed SMO, C- S&T copper, D - S&T cu-Ni, V - Other
6
A - Brazed SS, B - Brazed SMO, C- S&T copper, D - S&T cu-Ni, E - Double wall brazed, V - Other
1
2
2
AIRSTACK PACKAGED AIR COOLED
Features
AIRSTACK AIR COOLED MODULAR PACKAGED WATER CHILLER
Highly Dependable
• Multiple independent refrigeration circuits
• Comprehensive computer monitoring of operations
• Automatic diagnostic recording of fault conditions
• Automatic rotation of lead compressors
• Simple to operate
• LCD Screen displays information in plain English
• Simple keypad provides control of system operations
Easy To Install
• Compact modules fit through standard doorways and into elevators
• Modules interconnect easily and quickly to form chillers from 10 to 600 tons
(depending on module)
• All refrigeration systems are factory charged and run tested
Computer Control System
• Operates only the capacity required by the load
• Operates at peak efficiency under any given load
Design Flexibility
• Wide selection of module combinations
-- Free Cooling modules
-- Tanks
-- Glycol shot feeders
-- Pumping package
-- Super-quiet modules
-- Heat-recovery modules (desuperheaters)
• Install only the capacity required at the time
• Wide selection of options
-- Expansion tanks
-- Air separator
-- Copper/copper coils
-- Baked phenolic coatings
-- Stainless-steel construction
-- Specialty coatings
-- Special valving
-- Controls interface
Simple To Service
• Isolate and service modules while remaining in
operation
• Does not require proprietary training
• Service can often be performed on a convenient nonemergency basis
• Most components are standard, off-the-shelf design
3
AIRSTACK PACKAGED AIR COOLED
Performance Data
ASP - 10X Air Cooled Modular Chiller
Ambient Air Temperature °F
Leaving
Chilled
Water
°F
Tons
kW
EER
Tons
kW
EER
Tons
kW
EER
Tons
kW
EER
Tons
kW
EER
40.0
11.7
10.0
13.96
11.1
11.0
12.12
10.4
12.0
10.41
9.7
13.2
8.84
9.0
14.6
7.40
42.0
12.2
10.0
14.55
11.5
10.9
12.62
10.8
12.0
10.85
10.1
13.2
9.22
9.4
14.5
7.73
44.0
12.6
10.0
15.16
12.0
10.9
13.15
11.3
12.0
11.31
10.5
13.1
9.62
9.8
14.5
8.08
45.0
12.9
10.0
15.47
12.2
10.9
13.42
11.5
11.9
11.54
10.8
13.1
9.82
10.0
14.5
8.25
46.0
13.1
10.0
15.79
12.4
10.9
13.69
11.7
11.9
11.77
11.0
13.1
10.03
10.2
14.5
8.43
48.0
13.6
9.9
16.44
12.9
10.9
14.25
12.2
11.9
12.26
11.4
13.1
10.45
10.6
14.4
8.80
50.0
14.1
9.9
17.12
13.4
10.8
14.83
12.6
11.9
12.76
11.8
13.1
10.88
11.0
14.4
9.17
(A suitable antifreeze solution is required for operation below 40°F Ambient)
65.0
75.0
85.0
95.0
105.0
AHRI specification points are in bold.
ASP - 15X Air Cooled Modular Chiller
Ambient Air Temperature °F
Leaving
Chilled
Water
°F
Tons
kW
EER
Tons
kW
EER
Tons
kW
EER
Tons
kW
EER
Tons
kW
EER
40.0
16.1
13.1
14.67
15.2
14.5
12.55
14.2
16.1
10.63
13.2
17.9
8.87
12.1
20.0
7.28
42.0
16.7
13.1
15.24
15.8
14.5
13.05
14.8
16.1
11.07
13.8
17.9
9.25
12.7
20.0
7.60
44.0
17.4
13.2
15.83
16.4
14.5
13.56
15.4
16.1
11.51
14.3
17.8
9.64
13.2
19.9
7.94
45.0
17.7
13.2
16.12
16.7
14.5
13.83
15.7
16.1
11.74
14.6
17.8
9.84
13.5
19.9
8.11
46.0
18.0
13.2
16.42
17.1
14.5
14.09
16.0
16.1
11.97
14.9
17.8
10.04
13.7
19.9
8.28
48.0
18.7
13.2
17.03
17.7
14.5
14.63
16.7
16.1
12.44
15.5
17.8
10.45
14.3
19.9
8.63
50.0
19.5
13.2
17.65
18.4
14.6
15.17
17.3
16.1
12.92
16.1
17.8
10.87
14.9
19.9
8.99
(A suitable antifreeze solution is required for operation below 40°F Ambient)
65.0
75.0
85.0
95.0
105.0
AHRI specification points are in bold.
ASP - 20X Air Cooled Modular Chiller
Ambient Air Temperature °F
Leaving
Chilled
Water
°F
Tons
kW
EER
Tons
kW
EER
Tons
kW
EER
Tons
kW
EER
Tons
kW
EER
40.0
21.5
17.6
14.65
20.3
19.1
12.78
19.0
21.0
10.86
17.5
23.3
9.02
16.0
26.1
7.34
42.0
22.3
17.6
15.17
21.1
19.1
13.27
19.8
21.0
11.31
18.3
23.3
9.41
16.7
26.1
7.68
44.0
23.1
17.7
15.70
21.9
19.1
13.77
20.6
21.0
11.76
19.1
23.3
9.82
17.4
26.0
8.03
45.0
23.5
17.7
15.97
22.3
19.1
14.02
21.0
21.0
11.99
19.5
23.3
10.02
17.8
26.0
8.21
46.0
24.0
17.7
16.24
22.8
19.1
14.28
21.4
21.0
12.22
19.9
23.3
10.23
18.2
26.0
8.39
48.0
24.8
17.7
16.79
23.6
19.2
14.79
22.2
21.0
12.70
20.7
23.3
10.65
19.0
26.0
8.76
50.0
25.7
17.7
17.35
24.5
19.2
15.32
23.1
21.0
13.18
21.5
23.3
11.08
19.8
26.0
9.13
(A suitable antifreeze solution is required for operation below 40°F Ambient)
65.0
75.0
AHRI specification points are in bold.
4
85.0
95.0
105.0
AIRSTACK PACKAGED AIR COOLED
Performance Data
ASP - 30X Air Cooled Modular Chiller
Ambient Air Temperature °F
Leaving
Chilled
Water
°F
Tons
kW
EER
Tons
kW
EER
Tons
kW
EER
Tons
kW
EER
Tons
kW
EER
40.0
30.2
25.8
14.08
28.7
27.9
12.34
27.0
30.5
10.64
25.2
33.4
9.04
23.2
36.9
7.56
42.0
31.4
25.9
15.56
29.8
28.0
12.78
28.1
30.5
11.04
26.2
33.5
9.39
24.2
36.9
7.86
44.0
32.6
26.0
15.04
31.0
28.1
13.22
29.2
30.6
11.44
27.3
33.6
9.75
25.2
37.0
8.17
45.0
33.2
26.1
15.28
31.6
28.2
13.45
29.8
30.7
11.65
27.8
33.6
9.93
25.7
37.0
8.33
46.0
33.8
26.2
15.52
32.2
28.2
13.67
30.4
30.7
11.85
28.4
33.7
10.11
26.2
37.0
8.49
48.0
35.1
26.3
16.00
33.4
28.4
14.12
31.5
30.8
12.26
29.5
33.7
10.48
27.3
37.1
8.81
50.0
36.4
26.5
16.48
34.7
28.5
14.57
32.7
31.0
12.68
30.6
33.8
10.85
28.3
37.2
9.14
(A suitable antifreeze solution is required for operation below 40°F Ambient)
65.0
75.0
85.0
95.0
105.0
AHRI specification points are in bold.
ASP - 60X (61X) Air Cooled Modular Chiller
Ambient Air Temperature °F
Leaving
Chilled
Water
°F
Tons
kW
EER
Tons
kW
EER
Tons
kW
EER
Tons
kW
EER
Tons
kW
EER
40.0
63.7
53.3
14.34
60.4
58.0
12.48
56.8
63.6
12.72
53.0
69.9
9.09
49.0
77.2
7.61
42.0
66.3
53.5
14.85
62.8
58.2
12.94
59.1
63.7
11.12
55.2
70.1
9.44
51.0
77.3
7.91
44.0
68.9
53.8
15.36
65.3
58.5
13.40
61.5
63.9
11.53
57.4
70.3
9.80
53.1
77.5
8.22
45.0
70.2
53.9
15.62
66.6
58.6
13.63
62.7
64.0
11.74
58.6
70.4
9.98
54.2
77.6
8.38
46.0
71.6
54.1
15.88
67.8
58.7
13.87
63.9
64.1
11.95
59.7
70.5
10.16
55.3
77.7
8.53
48.0
74.3
54.4
16.40
70.5
59.0
14.34
66.4
64.4
12.37
62.0
70.7
10.53
57.5
77.9
8.85
50.0
77.2
54.7
16.93
73.2
59.2
14.82
68.9
64.6
12.80
64.4
70.9
10.91
59.7
78.1
9.17
(A suitable antifreeze solution is required for operation below 40°F Ambient)
65.0
75.0
85.0
95.0
105.0
AHRI specification points are in bold.
IPLV Performance Chart
25%
50%
75%
100%
IPLV
ASP-10
.676
.775
.973
1.247
.851
ASP-15
.642
.744
.949
1.244
.823
ASP-20
.680
.751
.931
1.222
.823
ASP-30
.702
.785
.965
1.230
.855
ASP-60
.679
.768
.955
1.224
.840
Based on AHRI standard percentage ratio point.
NOTES:
1. Capacity is based on pure water. For performance using Glycol Solution, see Adjustment Factor on Page 9.
2. All full-load performance data is based on a 10°F chilled-water temperature drop
through the evaporator.
3. Fan and controls kW are included in tabular kW data.
4. For total chiller performance, multiply above output (Tons) and input (kW) by the
number of modules.
5. Leaving water temps below 40° requires freeze protection.
6. Based on 0.0001 fouling water for the evaporator.
7. Following ARI 550/590 Standard 29.92 inches mercury barometric pressure is
used for the data basis.
5
AIRSTACK PACKAGED AIR COOLED
Performance Data
FCP1, Free Cooling Module, Single Module Performance Data
For use with ASP-10,-15
Ambient
°F
30° F
35°F
40° F
30 gpm
15.5
10.2
5.1
45
60 gpm
14.0
9.3
4.7
Capacity in Refrigeration Tons
LEAVING WATER TEMPERATURE/GPM
90 gpm
13.3
8.9
4.5
30 gpm
21.2
15.8
10.4
50
60 gpm
18.7
14.1
9.4
90 gpm
17.8
13.3
8.9
30 gpm
27.0
21.5
16.0
55
60 gpm
23.5
18.8
14.1
90 gpm
22.3
17.8
13.4
55
60 gpm
45.8
36.5
27.4
90 gpm
42.9
34.4
25.7
55
60 gpm
72.3
57.7
43.2
90 gpm
63.6
50.9
38.2
55
60 gpm
72.3
57.7
43.2
90 gpm
63.6
50.9
38.2
FCP2, Free Cooling Module, Single Module Performance Data
For use with ASP-20
Ambient
°F
30° F
35°F
40° F
30 gpm
28.9
18.9
9.3
45
60 gpm
27.0
18.0
9.0
Capacity in Refrigeration Tons
LEAVING WATER TEMPERATURE/GPM
90 gpm
25.6
17.1
8.5
30 gpm
41.0
30.1
19.9
50
60 gpm
36.2
27.3
18.1
90 gpm
34.2
25.7
17.1
30 gpm
53.8
42.8
31.3
FCP3, Free Cooling Module, Single Module Performance Data
For use with ASP-30 , -60, -61
Capacity in Refrigeration Tons
LEAVING WATER TEMPERATURE/GPM
Ambient
°F
45
50
30 gpm
60 gpm
90 gpm
30 gpm
60 gpm
90 gpm
30 gpm
30° F
60.4
42.9
37.8
82.2
57.5
50.8
104.3
35°F
40.0
28.6
25.3
61.1
43.1
37.9
82.8
40° F
19.3
14.4
12.7
40.1
28.8
25.4
61.7
Notes: 1. Capacity is based on pure water. For performance using Glycol solution, see Adjustment Factor on Page 9.
2. A suitable antifreeze solution is required for operation below 40°F Ambient
FCP4, Free Cooling Module, Single Module Performance Data
For use with ASP-30 , -60, -61
Capacity in Refrigeration Tons
LEAVING WATER TEMPERATURE/GPM
Ambient
°F
45
50
30 gpm
60 gpm
90 gpm
30 gpm
60 gpm
90 gpm
30 gpm
30° F
60.4
42.9
37.8
82.2
57.5
50.8
104.3
35°F
40.0
28.6
25.3
61.1
43.1
37.9
82.8
40° F
19.3
14.4
12.7
40.1
28.8
25.4
61.7
Notes: 1. Capacity is based on pure water. For performance using Glycol solution, see Adjustment Factor on Page 9.
2. A suitable antifreeze solution is required for operation below 40°F Ambient
General Data Table of Air Cooled Standard –Free Cool Modules
Condenser Fans
Motor Type
HP
Quantity
Fan Type
Fan Material
Air Flow (cfm) (per module)
FCP1
FCP2
Totally Enclosed
1
2
Axial
Comp
8,500
FCP1
Totally Enclosed
2
2
Axial
Comp
16,000
FCP2
FCP3
Totally Enclosed Totally Enclosed
2
2
2
2
Axial
Axial
Comp
Comp
22,000
FCP3
FCP4
Condenser Coils*
Fin Material
Aluminum
Aluminum
Aluminum
Tube Material
Copper
Copper
Copper
Tube Diameter (in.)
1/2
1/2
1/2
Number of Rows
6
6
6
Coil Dimensions (Quantity)
30 x 49 (2)
30 x 611/2 (2)
42 x 731/2 (2)
Free Cooling Coil Water Volume (gallons)
10.8
15.2
30.8
Module Dry Weight (lb.)
1150
1550
1850
*On Free Cool Modules, coils are utilized as water precoolers rather than for refrigerant condensing.
6
FCP4
Aluminum
Copper
1/2
6
AIRSTACK PACKAGED AIR COOLED
General Data
Compressor
Type
Nominal Capacity (per compressor)
Quantity
General Data Table of Air Cooled Standard –X Modules
ASP-10X
SCROLL
5
2-TANDEM
ASP-15X
SCROLL
7.5
2-TANDEM
ASP-20X
SCROLL
10
2-TANDEM
ASP-30X
SCROLL
15
2-TANDEM
ASP-60X
SCROLL
30
2-TANDEM
ASP-61X
SCROLL
30
2-TANDEM
Evaporator
Type
Weight
Evap Water Storage (gallons each)
Quantity
Header Storage (gallons per header)
Refrigerant Type
Number of Circuits
ASP-10X
BRAZED PLATE
54.4
1.08
1
3.2
410a
1
Condenser Fans
Motor Type
HP
Quantity
Fan Type
Fan Material
Air Flow (cfm) (per module)
ASP-10X
ASP-15X
ASP-20X
ASP-30X
ASP-60X
ASP-61X
Totally Enclosed Totally Enclosed Totally Enclosed Totally Enclosed Totally Enclosed Totally Enclosed
1
1
2
2
2
15
2
2
2
2
4
1
Axial
Axial
Axial
Axial
Axial
Axial
Composite
Composite
Composite
Composite
Composite
Composite
6,600
8,500
16,000
22,000
44,000
44,000
Condenser Coils*
Fin Material
Tube Material
Tube Diameter (in.)
Number of Rows
Coil Dimensions (Quantity)
Free Cooling Coil Water Volume (gallons)
Module Dry Weight (lb.)
ASP-10X
Aluminum
Copper
3/8
4
32 x 51 (2)
3.5
1370
ASP-15X
ASP-20X
ASP-30X
ASP-60X
ASP-61X
BRAZED PLATE BRAZED PLATE BRAZED PLATE BRAZED PLATE BRAZED PLATE
63.8
83.7
100
214.4
214.4
1.4
2.03
2.54
5.86
5.86
1
1
1
1
1
3.2
6.24
10.5
18.2
18.2
410a
410a
410a
410a
410a
1
1
1
1
1
ASP-15X
Aluminum
Copper
3/8
6
30 x 49 (2)
3.5
1400
ASP-20X
Aluminum
Copper
3/8
6
30 x 611/2 (2)
4.6
1700
ASP-30X
Aluminum
Copper
3/8
6
42 x 731/2 (2)
4.6
2100
Refrigerant Type
R410a
R410a
R410a
Charge (lbs./circuit)
40
60
Number of Circuits
1
1
1
Operating Weight (with AL/CU coils)
1430
1470
1820
Shipping Weight (with AL/CU coils)
1370
1400
1700
Operating Weight (with CU/CU coils)
1650
1770
2300
Shipping Weight (with CU/CU coils)
1590
1700
2180
*On Free Cool Modules, coils are utilized as water precoolers rather than for refrigerant condensing.
R410a
55
1
2290
2100
2920
2730
ASP-60X
Aluminum
Copper
3/8
6
42 x 731/2 (4)
7.2
4,000
ASP-61X
Aluminum
Copper
3/8
6
42 x 731/2 (4)
7.2
5,400
R410a
R410a
1
4350
4000
5610
5260
1
5750
5400
7010
6660
7
AIRSTACK PACKAGED AIR COOLED
Pump Selection Charts
ASP DUAL PUMP SELECTION CHART
(ALL PUMPS IN PRIMARY/STANDBY ARRANGEMENT–DATA FOR SINGLE PUMP)
Charts Show Pump BHP Requirement at Given Condition
ARMSTRONG SERIES 4382 – 3x3x6 Pump
Total head in feet
Flow (USGPM)
60
80
100
120
140
40
3.07
3.87
4.66
5.47
80
3.58
4.47
5.37
6.29
120
3.55
4.52
5.51
6.50
7.51
160
4.82
5.91
7.00
8.09
9.20
200
6.71
7.94
9.13
10.34
10.97
12.27
240
ARMSTRONG SERIES 4382 – 4x4x6 Pump
Total head in feet
Flow (USGPM)
60
80
100
120
140
50
3.80
4.89
6.10
7.44
100
4.52
5.77
7.12
8.57
9.71
150
3.98
5.30
6.70
8.16
200
4.78
6.26
7.79
9.39
250
5.81
7.54
9.14
10.90
300
7.16
9.03
10.91
350
8.90
11.07
ARMSTRONG SERIES 4382 – 6x6x6 Pump
Total head in feet
Flow (USGPM)
60
200
300
80
100
120
140
7.86
10.24
12.78
15.47
9.75
12.39
15.15
400
8.99
11.82
14.73
17.72
500*
10.93*
14.14*
17.34*
20.59*
600*
13.06*
16.68*
20.26*
700*
15.48*
19.51*
800*
18.35*
22.76*
*For selections above 400 gpm contact Multistack®
Notes:
1.
2.
3.
4.
8
DO NOT SELECT IN SHADED AREA.
All selections are based on 40% Ethylene Glycol solution.
Pump speed is 3,600 rpm.
All pump modules have automatic changeover controls in the event of loss of flow and manual lead/lag selector switch.
AIRSTACK PACKAGED AIR COOLED
Adjustment Factors
Figure 3. Ethylene Glycol Adjustment Factor
Figure 1. Performance Adjustment Factor
PERFORMANCE ADJUSTMENT FACTOR
Pressure Drop
GPM
KW
Capacity
Figure 4. Propylene Glycol Adjustment Factor
Figure 2. Water Pressure Drop
A- ASP-10X
D- ASP-30X
B- ASP-15X
E- ASP-60X (61X)
C- ASP-20X
A
B
C D
E
Pressure Drop
GPM
KW
Capacity
9
AIRSTACK PACKAGED AIR COOLED
Selection Data
SELECTION
To select an AIRSTACK Air Cooled chiller, the following
information is required.
1. Load (in tons) of refrigeration.
2. Chilled-water temperature drop.
3. Leaving chilled-water temperature.
4. Design ambient-air temperature.
CAPACITY TABLES
Capacity tables are based on a 10°F temperature drop
through the evaporator. For other than a 10°F temperature
drop, apply the respective performance adjustment factors
from Figure 1.
EVAPORATOR WATER FLOW RATE
Evaporator water flow is determined as follows:
gpm = (24) (tons) / temperature drop
WATERSIDE PRESSURE DROP
Evaporator waterside pressure drops are provided in
Figure 2. To use Figure 2, divide the total chilled-water gpm
by the number of modules in the chiller.
CHILLED-WATER SELECTION SAMPLE
(Assumes ASP-15 Modules)
1. System load = 55 tons. Chilled-water drop at 12°F.
2. Leaving chilled-water temperature of 45°F. Design ambient-air
temperature of 95°F.
3. Use the Figure 1 adjustment factor to convert tons at 12°F to
equivalent tons at 10°F for use with capacity tables.
Tons = 55/1.012 = 54.3 tons
4. Select the appropriate performance table based on the module to
be used. Read the capacity and kW of a single module at the water
temperature specified (45°F) and design ambient-air temperature
(95°F). capacity = 14.4 tons, kW = 15.8
Divide the equivalent tons required at 10°F temperature drop by the
single module capacity from the tables.
Modules required = 54.3/14.4 = 3.8 modules
Chiller capacity = 14.4 x 4 = 57.6 tons
Power input = 15.8 x 4 = 63.2 kW at 12°F temperature drop; applying
the Figure 1 performance adjustment factor results in: tons = (57.6)
(1.012) = 58.3 vs. system load of 55 tons.
5. To determine the evaporator water flow and pressure drop, first
determine gpm.
gpm = (24)(54.3)/12=108.6
gpm/module = 108.6/4 = 27.2
From Figure 2, read pressure drop from curve C pressure drop = 2.4 ft.
of water.
10
LOW-TEMPERATURE OPERATION WITH GLYCOL
(Assumes ASP-15 Modules)
Ethylene Glycol adjustment factors (Figure 3) should be used to adjust
performance depending on the percent of glycol use in the evaporator
circuit. The factors in Figure 3 are based on a 10°F change in fluid
temperature through the evaporators. Capacity and kW should be
obtained by extrapolating no more than 10°F from the lowest leaving
chilled-water temperature shown in the capacity tables. Multistack
should be contacted if leaving Glycol temperatures below 32°F are
required.
Adjustment factors for Propylene Glycol are shown in Figure 4, and are
used in the same way given in the following example.
ETHYLENE GLYCOL SELECTION
EXAMPLE (Assumes ASP-15 Modules)
Determine the capacity, gpm, pressure drop, and kW for an
ASP-15 module cooling 30% Ethylene Glycol from 45°F to
35°F, with design ambient-air temperature of 95°F.
1. By extrapolating from the performance tables: capacity: 11.5
tons; 15.8 kW
2. Evaporator water flow and pressure drop are determined for
water as in the previous example.
gpm = (24) (11.5) = 27.6 gpm
10
From Figure 2, read the pressure drop from the curve C pressure
drop = 2.6 ft of water
To convert performance for water to performance with Ethylene
Glycol, read adjustment factors from Figure 3 at 30% Glycol.
Capacity adjustment: 0.94
kW adjustment: 0.99
gpm adjustment: 1.10
Pressure drop adjustment: 1.22
Calculate performance with 30% Ethylene Glycol by multiplying
performance for water by adjustment factors.
Capacity: 11.5 x .94 = 10.8 tons
kW: 15.8 x .99 = 15.6 kW
gpm: 27.6 x 1.10 = 30.4 gpm
Pressure drop: 2.6 x 1.22 = 3.2 ft of water
If a water-temperature drop greater or less than 10°F is required, begin
by first multiplying the capacity using the performance adjustment
factor from Figure 1.
AIRSTACK PACKAGED AIR COOLED
Selection Data
IMPORTANT MODULE CONFIGURATION INFORMATION
ASP-00P PUMP MODULE:
1.When present, a Pump Module is only allowed in the “Front”
position.
2.Incoming water to the chiller system must enter at the Pump
Module.
3.Leaving water from the chiller system may be from either end
of the chiller.
ASP-1FX, 2FX, 3FX FREE COOL MODULE:
1.When present, incoming system water must enter through the
Free Cool Modules prior to entering an ASP-10X, 15X, 20X, 30X,
60X or 61X Chiller Module.
2.You may not attach a Rear Free Cool Module to a Front ASP-10X,
15X, 20X, 30X, 60X or 61X Chiller Module.
ASP-00G GLYCOL FEEDER MODULE:
1. An ASP-00G Glycol Feeder Module may be attached in any
rear position.
ASP-10X, 15X, 20X, 30X, 60X, 61X CHILLER MODULE:
1.The maximum number of ASP-10X, 15X, 20X, or 30X,modules
with a single Master Module is 14 (i.e., (1) Front-Master, (6)
Front-Slaves, and (7) Rear-Slaves). For 60X and 61X modules,
the maximum is nine modules.
2.You may have more than one Master Module in a single
chiller bank.
3.Piping sides of an ASP-10X, 15X, 20X, 30X, 60X or 61X chiller
without Free Cool or Pump Modules attached are field
selectable.
LEGEND: FIRST LETTER
VALID CONFIGURATIONS
Tank
FF
PF
MF
SR
SR
SR
SR
SR
PF
SF
SF
SF
SF
SR
SR
PF
MF
SF
FR
FR
SR
SR
PF
FF
MF
SF
SF
SR
GR
SR
SR
SR
MF
SF
SF
MF
SF
SF
SR
SR
SR
PF
MF
SF
FR
SR
SR
SR
PF
FF
MF
SF
SR
SR
SR
SF
SF
INVALID CONFIGURATIONS
SR
SR
SR
MF
SF
SF
M=Master Chiller Module (ASP-10X, 15X, 20X, 30X or 60X)
S = Slave Chiller Module (ASP-10X, 15X, 20X, 30X or 60X)
P= Pump Module (ASP-00P)
F = Free Cool Module (ASP-1FX, 2FX, 3FX)
G = Glycol Feeder Module (ASP-00G)
Problem: Cannot have a stand alone rear module.
Solution: Make Slave Rear a Slave Front.
SECOND LETTER
Problem: Pump module after Master.
Solution: Swap placement so incoming water enters at the pump module.
F = Front Module
R = Rear Module
FRONT OF CHILLER BANK IS TOWARD
THE BOTTOM OF THE PAGE
(Master Module location determines front of chiller)
For other configurations, contact your local Multistack® Representative.
MF
SR
SR
PF
SF
SR
SR
SR
PF
MF
GF
Problem: Glycol Feeder Module is attached in a front position.
Solution: Move Glycol Feeder Module to rear position and exchange Slave Rear Module for
Slave Front Module.
TYPICAL ASP-60X or 61X CONFIGURATION
M
S
S
S
11
AIRSTACK PACKAGED AIR COOLED
Diagrams
All ASP-60X units come standard with four multi-blade vane axial condenser fans. The ASP-61X is a single fan unit available with a Low Sound (polyresin reinforced) Blade or Ultra Low Sound (fiberglass construction) Blade option. Testing has shown a sound reduction of 6dB with the Low Sound
and an additional 4dB with the Ultra Low Sound design.
INTAKE
NOTES:
· NO OBSTRUCTIONS ALLOWED ABOVE CONDENSER FANS.
· REQUIRED SERVICE CLEARANCE AT MODULE ENDS: 42”.
· REQUIRED AIR INTAKE (FRONT) CLEARANCE: 42”
· REQUIRED CLEARANCE FROM ANY HIGH VOLTAGE PANEL: 42”
INTAKE
12
ASP-60X and ASP-61X Notes:
1. No obstructions allowed above condenser fans.
2. Required service clearance at module ends: 42”
3. Required air intake (front) clearance: 42”
4. Required clearance from any high voltage panel 42”
5. Required clearance from any grounded wall: 42”
Any non-grounded wall: 36”
AIRSTACK PACKAGED AIR COOLED
Diagrams
NUMBER OF MODULES X “A” + 4”
2”
ASP-010X, -015X ASP-020X
TOP VIEW
NOTES:
1. NO OBSTRUCTIONS ALLOWED ABOVE CONDENSER FANS.
2. REQUIRED SERVICE CLEARANCE AT MODULE ENDS: 36”.
3. REQUIRED AIR INTAKE CLEARANCE: 42”. (Unobstructed)*
4. REQUIRED CLEARANCE FROM ANY HIGH VOLTAGE PANEL: 42”
ASP-030X
“D”
“D”
DISCHARGE
DISCHARGE
CONDENSER COIL
ELECTRICAL PANEL
“C”
“C”
INTAKE
FRONT VIEW
INTAKE
FRONT VIEW
“B”
2”
“A”
2”
ASP-010X, -015X ASP-020X ASP-030X
“D”
NOTES:
1. NO OBSTRUCTIONS ALLOWED ABOVE CONDENSER FANS.
2. REQUIRED SERVICE CLEARANCE AT MODULE ENDS: 36”.
3. REQUIRED AIR INTAKE CLEARANCE: 42”.*
4. REQUIRED CLEARANCE FROM ANY HIGH VOLTAGE PANEL: 42”.
5. REQUIRED CLEARANCE FROM ANY GROUNDED WALL: 36”.
6. NO CLEARANCE REQUIRED FROM REAR.
DISCHARGE
CONDENSER COIL
ELECTRICAL PANEL
“C”
INTAKE
FRONT VIEW
RIGHT SIDE VIEW
REAR VIEW
*Note: If insullation is in a pit or near walls that are taller than modules, please contact Multistack for clearances.
13
AIRSTACK PACKAGED AIR COOLED
Electrical Data
REQUIRED CHILLED-WATER PIPING
(SUPPLIED AND INSTALLED BY OTHERS)
(*If ASP -00P Pump Module is Supplied by Airstack, eliminate external pump shown below.)
ELECTRICAL DATA
Model
ASP - 10X
ASP - 15X
ASP - 20X
ASP - 30X
ASP - 60X
ASP - 61X
ASP - 1FX
ASP - 2FX
ASP - 3FX
ASP - 00P
ASP - 00P
ASP - 00P
ASP - 00P
ASP - 00P
ASP - 00P
ASP - 00G
Number of
Compressors
2
2
2
2
2
2
N/A
N/A
N/A
RLA per Compressor
3 phase
1 phase
208/460/575V
230V
19.5/8.7/7.2
25.0
31/14.0/11.5
N/A
35/15.5/12.0
N/A
55/26.0/21.0
N/A
N
/A/47.0/38.0
N/A
N
/A/47.0/38.0
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Number of
Fan Motors
2
2
2
2
4
1
2
2
2
WIRING SIZING (MCA= MINIMUM CIRCUIT AMPACITY)
MCA = (1.25 x RLA1*) + RLA2 + RLA3 . . . . . .
FUSE SIZING (MFS = MAXIMUM FUSE SIZE)
MFS = (2.25 x RLA1*) + RLA2 + RLA3 . . . . . .
Where MFS does not equal a standard size fuse, the next larger
fuse should be used.
NOTES:
1. Compressor Rated Load Amps (RLA) are based on 125°F
Saturated Condensing Temperature.
2. *RLA1 = RLA of the largest motor in the system. RLA2 &
RLA3 = RLA of other motors in the system.
3. Wire sizing is based on Nat. Electr. Code (NEC)rating for 75°C
wire, with 3 wires per conduit.
4. Wiring distance from branch circuit shall not exceed 100
feet.
14
FLA per Fan Motor
3 phase
1 phase
208/460/575V
230V
4.0/2.0/1.5
5.0
4.0/2.0/1.5
N/A
7.4/3.6/2.8
N/A
7.4/3.6/2.8
N/A
N
/A/3.6/2.8
N/A
N
/A/18.1/14.8
N/A
4.0/2.0/1.5
N/A
7.4/3.6/2.8
N/A
7.4/3.6/2.8
N/A
Pump HP
Max Pump FLA
3 phase
1 phase
208/460/575V
230V
5
7.5
10
15
20
25
N/A
16.7/7.6/6.1
24.2/11/9
30.8/14/11
46.2/21/17
59.4/27/22
74.8/34/27
2/1/1
28
N/A
N/A
N/A
N/A
N/A
2
MCA
WIRE SIZE (AWG) 75°
(3 Conductors/1Conduit)
MCA
WIRE SIZE (AWG) 75°
(6 Conductors/2Conduit)
50
65
85
100
115
130
150
175
200
230
255
285
310
335
380
420
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250 MCM
300 MCM
350 MCM
400 MCM
500 MCM
600 MCM
510
570
620
670
760
800
250 MCM
300 MCM
350 MCM
400 MCM
500 MCM
600 MCM
AIRSTACK PACKAGED AIR COOLED
Specifications
GENERAL
Chiller Modules shall be ETL listed in accordance with UL Standard 1995, CSA
certified per Standard C22.2#236, and bear the ASME UM stamp on all waterto-refrigerant heat exchangers.
Modules shall ship wired and charged with refrigerant. All modules shall
be factory run-tested prior to shipment. Compressors, heat exchangers,
condenser fans, piping, and controls shall be mounted on a heavy-gauge
steel frame. Electrical controls, contactors, and relays for each module shall
be mounted within that module. The module shall be provided within a steel
enclosure suitable for outdoor use. Exposed steel surfaces shall be provided
with a powder-coat paint finish.
CHILLED-WATER MAINS
Each module shall include supply and return mains for chilled water. Grooved
end connections are provided for interconnection to four-inch (ASP 10X, 15X),
six-inch (ASP 20X and 30X) or eight-inch (60X and 61X) standard piping with
Victaulic-type couplings. Each inlet water header shall incorporate a built-in,
30-mesh in-line strainer system to prevent heat exchanger fouling.
EVAPORATORS
Each evaporator shall be a brazed-plate heat exchanger constructed of 316
stainless steel, and be designed, tested, and stamped in accordance with U.L.
1995 650 PSIG working pressure.
COMPRESSOR
Each module shall contain hermetic scroll compressor(s) mounted to the
module with rubber-in-shear isolators. Each system shall also include high
discharge-pressure and low suction-pressure safety cut-outs.
CONDENSER COILS
Air cooled condenser coils shall have aluminum fins mechanically bonded
to copper tubing. Condensers shall have integral subcooling circuitry and be
factory leak-tested.
CONDENSER FANS
Each module shall contain dual condenser fans for each refrigerant circuit. These
fans shall be multi-blade vane-axial type, made of plastic composite material
for quiet operation. Fans shall be direct driven at a maximum rpm of 1,150. All
fan motors shall be pressure controlled and suitable for outdoor use. ASP 60X
modules have four fans, ASP 61X have a single unit fan.
CENTRAL CONTROL SYSTEM
Scheduling of the various compressors shall be performed by a microprocessorbased control system (Master Controller). A new lead compressor is selected
every 24 hours to ensure even distribution of compressor run time. The
Master Controller shall monitor and report the following on each refrigeration
system:
• Discharge Pressure Fault
-- Suction Pressure Fault
-- Compressor Winding Temperature Fault
-- Suction Temperature
-- Evaporator Leaving Chilled-Water Temperature
The Master Controller shall monitor and report the following system
parameters:
• Chilled-Water Entering and Leaving Temperature
-- Discharge Refrigerant Temperature
-- Chilled-Water Flow Fault
An out-of-tolerance indication from these controls or sensors shall cause a
“fault” indication at the Master Controller and shutdown of that compressor,
with the transfer of load requirements to the next available compressor. In the
case of a System Fault, the entire chiller will be shut down. When a fault occurs,
the Master Controller shall record conditions at the time of the fault and store
the data for recall. This information shall be capable of being recalled through
the keypad of the Master Controller and displayed on the Master Controller’s
LCD. A history of faults shall be maintained, including date and time-of-day of
each fault (up to the last 20 occurrences).
Individual monitoring of leaving chilled-water temperatures from each
refrigeration system shall be programmed to protect against freeze-up.
The control system shall monitor entering and leaving chilled water
temperatures to determine system load, and select the number of compressor
circuits required to operate. Response times and set points shall be adjustable.
LOW AMBIENT OPERATION
Each refrigerant circuit shall include all refrigerant specialties to provide reliable
operation down to 20°F ambient. With proper freeze protection.
OPTIONAL LOW AMBIENT TO -20°F
The chiller shall incorporate appropriate refrigerant specialties, including a
properly sized refrigerant receiver and flooded head pressure control valves for
operation to -20°F.
OPTIONAL SINGLE-POINT POWER CONNECTION
The chiller shall be provided with a single-point power connection. This will
include pre-engineered wiring for field installation and connection to a factorymounted chiller junction box. The junction box shall include individual fusing
for each Module Set and provide a single point of connection to building power.
OPTIONAL Free CoolING MODULE
Free Cooling Modules shall interconnect through the common chiller header
system and require no additional water connections. Free Cooling Modules shall
include glycol cooling coils, temperature-controlled fans, and an automatic
3-way bypass valve to eliminate the need for mechanical cooling under lowambient conditions. The module shall be completely factory-assembled and
tested before shipment.
OPTIONAL PUMP MODULE
The Pump Module shall be interconnected through the common chiller header
system and require no additional water connections. The Pump Module
will become an integral part of the chiller system. The Pump Module shall
incorporate dual in-line centrifugal pumps in a Primary/Standby pumping
arrangement. Pump starters and controls shall be provided to enable manual
selection of lead pump. In addition, in the event of a loss-of-flow failure of
the chilled-water system, the Pump Module controls shall disable the lead
pump and automatically start the standby pump. The Pump Module shall be
completely factory assembled and tested prior to shipment.
OPTIONAL TANK MODULE
A factory-assembled Tank Module shall be provided, including an insulated
chilled water tank. The tank shall be pressure-rated at 150 psi minimum.
Tank Modules shall interconnect through the common chiller header system
and require no additional water connections. The Tank Module will become
an integral part of the chiller system. The Tank Module shall be provided with
proper drain and fill valving.
Cont’d on next page…
15
OPTIONAL GLYCOL FEEDER MODULE
The optional Glycol Feeder and Expansion Tank shall be incorporated into the chiller system through a modular arrangement and interconnect through the
common chiller header system, requiring no additional water connections. The system shall include a 48-gallon storage/mixing tank with lid and cover, pump
suction hose with inlet strainer, pressure pump with thermal cut-out and integral pressure switch, pre-charged accumulator tank with EPDM diaphragm,
manual diverter valve for purging and agitating contents of storage tank, adjustable 5-55 psi pressure regulating valve with pressure gauge, fast fill lever,
integral replaceable strainer, built-in check valve, and built-in shutoff valve. The glycol feeder system shall be compatible with glycol solutions of up to 50%
concentration. The pump shall be capable of running dry without damage. The expansion tank shall be welded steel with a butylrubber diaphragm, and
capable of a maximum operating temperature of 240°F and a maximum working pressure of 100 psig. The tank shall be interconnected through the common
chiller header system and require no additional water connections. The module shall be completely factory assembled and -tested prior to shipment.
OPTIONAL SOUND-ATTENUATION MODULE
1. Each Free Cooling module shall have VFD-controlled condenser fan motors soft start and precise fan speed control.
2. Each mechanical cooling module shall have oversized condenser coils and VFD controlled condenser fan motors that modulate to maintain head pressure for precise fan speed control. Fans shall have acoustically optimized fan blades utilizing a composite material. Compressors shall be wrapped with
high-temperature acoustic covers consisting of a dense-design fabric exterior with quilted acoustical fiberglass interior and open edges sealed with
silicone coated fabric with hook and loop closures.
1065 Maple Avenue P.O. Box 510 Sparta, WI 54656
Phone 608-366-2400 • Fax 608-366-2450
www.multistack.com
F154ACSD0610

Similar documents