Air Cooled Chiller
Transcription
Air Cooled Chiller
sm Air Cooled Chiller Product Data Catalog For chillers with R-410A refrigerant For Modules: ASP010X ASP015X ASP020X ASP030X ASP060X PMP01 PMP02 PMP03 PMP04 FCP01 FCP02 FCP03 FCP04 ASP-00T ASP-00G AIRSTACK PACKAGED AIR COOLED Table of Contents Product Introduction................................................................................................................................................... 3 Performance Data....................................................................................................................................................... 4 Pump Selection Charts................................................................................................................................................. 6 General Data Table...................................................................................................................................................... 7 Pressure Drop Tables................................................................................................................................................... 9 Selection Data........................................................................................................................................................... 10 Chiller Drawing......................................................................................................................................................... 12 Required Piping and Electrical Data............................................................................................................................ 14 Mechanical Specifications.......................................................................................................................................... 15 Model Number Nomenclature Existing MS 50 New MS X 050 1 X H N 1 W 1 H 0 R-410A 1 A 0 A A -410A Refrigerant Condenser6 Evaporator5 AHRI Version - if applicable Application4 Module Number (1 - single, 2 - multiple) Voltage3 Configuration2 AHRI Certified (C - certified, N - Not certified) Compressor Type1 Module Nominal Capacity (10 - 160 tons) Series B: Bristol, C: Trane Cornerstone, R: Bitzer Screw, S: Trane Scroll, T: Danfoss Turbocor, Z: Copeland scroll (old elec), X: Copeland Scroll (ZP), A: Copeland Scroll (ZR) 1- Standard, 2- Total access, 3 - Evap extended headers, 4 - Cond extended headers, 5 - Both extended headers, V - others 3 A - 208/3/60, L - 230/3/60, H - 460/3/60, C - 575/3/60, D - 200/3/50, E - 400/3/50, F - 380/3/60, S - 220/230/1/60, V - other 4 C - Single module temp controller, A-Air Cooled split, D - Cond unit, F - Fluid cooler (high temp),H - Heat recovery, R - Heat pump, W - Water cooled 5 A - Brazed SS, B - Brazed SMO, C- S&T copper, D - S&T cu-Ni, V - Other 6 A - Brazed SS, B - Brazed SMO, C- S&T copper, D - S&T cu-Ni, E - Double wall brazed, V - Other 1 2 2 AIRSTACK PACKAGED AIR COOLED Features AIRSTACK AIR COOLED MODULAR PACKAGED WATER CHILLER Highly Dependable • Multiple independent refrigeration circuits • Comprehensive computer monitoring of operations • Automatic diagnostic recording of fault conditions • Automatic rotation of lead compressors • Simple to operate • LCD Screen displays information in plain English • Simple keypad provides control of system operations Easy To Install • Compact modules fit through standard doorways and into elevators • Modules interconnect easily and quickly to form chillers from 10 to 600 tons (depending on module) • All refrigeration systems are factory charged and run tested Computer Control System • Operates only the capacity required by the load • Operates at peak efficiency under any given load Design Flexibility • Wide selection of module combinations -- Free Cooling modules -- Tanks -- Glycol shot feeders -- Pumping package -- Super-quiet modules -- Heat-recovery modules (desuperheaters) • Install only the capacity required at the time • Wide selection of options -- Expansion tanks -- Air separator -- Copper/copper coils -- Baked phenolic coatings -- Stainless-steel construction -- Specialty coatings -- Special valving -- Controls interface Simple To Service • Isolate and service modules while remaining in operation • Does not require proprietary training • Service can often be performed on a convenient nonemergency basis • Most components are standard, off-the-shelf design 3 AIRSTACK PACKAGED AIR COOLED Performance Data ASP - 10X Air Cooled Modular Chiller Ambient Air Temperature °F Leaving Chilled Water °F Tons kW EER Tons kW EER Tons kW EER Tons kW EER Tons kW EER 40.0 11.7 10.0 13.96 11.1 11.0 12.12 10.4 12.0 10.41 9.7 13.2 8.84 9.0 14.6 7.40 42.0 12.2 10.0 14.55 11.5 10.9 12.62 10.8 12.0 10.85 10.1 13.2 9.22 9.4 14.5 7.73 44.0 12.6 10.0 15.16 12.0 10.9 13.15 11.3 12.0 11.31 10.5 13.1 9.62 9.8 14.5 8.08 45.0 12.9 10.0 15.47 12.2 10.9 13.42 11.5 11.9 11.54 10.8 13.1 9.82 10.0 14.5 8.25 46.0 13.1 10.0 15.79 12.4 10.9 13.69 11.7 11.9 11.77 11.0 13.1 10.03 10.2 14.5 8.43 48.0 13.6 9.9 16.44 12.9 10.9 14.25 12.2 11.9 12.26 11.4 13.1 10.45 10.6 14.4 8.80 50.0 14.1 9.9 17.12 13.4 10.8 14.83 12.6 11.9 12.76 11.8 13.1 10.88 11.0 14.4 9.17 (A suitable antifreeze solution is required for operation below 40°F Ambient) 65.0 75.0 85.0 95.0 105.0 AHRI specification points are in bold. ASP - 15X Air Cooled Modular Chiller Ambient Air Temperature °F Leaving Chilled Water °F Tons kW EER Tons kW EER Tons kW EER Tons kW EER Tons kW EER 40.0 16.1 13.1 14.67 15.2 14.5 12.55 14.2 16.1 10.63 13.2 17.9 8.87 12.1 20.0 7.28 42.0 16.7 13.1 15.24 15.8 14.5 13.05 14.8 16.1 11.07 13.8 17.9 9.25 12.7 20.0 7.60 44.0 17.4 13.2 15.83 16.4 14.5 13.56 15.4 16.1 11.51 14.3 17.8 9.64 13.2 19.9 7.94 45.0 17.7 13.2 16.12 16.7 14.5 13.83 15.7 16.1 11.74 14.6 17.8 9.84 13.5 19.9 8.11 46.0 18.0 13.2 16.42 17.1 14.5 14.09 16.0 16.1 11.97 14.9 17.8 10.04 13.7 19.9 8.28 48.0 18.7 13.2 17.03 17.7 14.5 14.63 16.7 16.1 12.44 15.5 17.8 10.45 14.3 19.9 8.63 50.0 19.5 13.2 17.65 18.4 14.6 15.17 17.3 16.1 12.92 16.1 17.8 10.87 14.9 19.9 8.99 (A suitable antifreeze solution is required for operation below 40°F Ambient) 65.0 75.0 85.0 95.0 105.0 AHRI specification points are in bold. ASP - 20X Air Cooled Modular Chiller Ambient Air Temperature °F Leaving Chilled Water °F Tons kW EER Tons kW EER Tons kW EER Tons kW EER Tons kW EER 40.0 21.5 17.6 14.65 20.3 19.1 12.78 19.0 21.0 10.86 17.5 23.3 9.02 16.0 26.1 7.34 42.0 22.3 17.6 15.17 21.1 19.1 13.27 19.8 21.0 11.31 18.3 23.3 9.41 16.7 26.1 7.68 44.0 23.1 17.7 15.70 21.9 19.1 13.77 20.6 21.0 11.76 19.1 23.3 9.82 17.4 26.0 8.03 45.0 23.5 17.7 15.97 22.3 19.1 14.02 21.0 21.0 11.99 19.5 23.3 10.02 17.8 26.0 8.21 46.0 24.0 17.7 16.24 22.8 19.1 14.28 21.4 21.0 12.22 19.9 23.3 10.23 18.2 26.0 8.39 48.0 24.8 17.7 16.79 23.6 19.2 14.79 22.2 21.0 12.70 20.7 23.3 10.65 19.0 26.0 8.76 50.0 25.7 17.7 17.35 24.5 19.2 15.32 23.1 21.0 13.18 21.5 23.3 11.08 19.8 26.0 9.13 (A suitable antifreeze solution is required for operation below 40°F Ambient) 65.0 75.0 AHRI specification points are in bold. 4 85.0 95.0 105.0 AIRSTACK PACKAGED AIR COOLED Performance Data ASP - 30X Air Cooled Modular Chiller Ambient Air Temperature °F Leaving Chilled Water °F Tons kW EER Tons kW EER Tons kW EER Tons kW EER Tons kW EER 40.0 30.2 25.8 14.08 28.7 27.9 12.34 27.0 30.5 10.64 25.2 33.4 9.04 23.2 36.9 7.56 42.0 31.4 25.9 15.56 29.8 28.0 12.78 28.1 30.5 11.04 26.2 33.5 9.39 24.2 36.9 7.86 44.0 32.6 26.0 15.04 31.0 28.1 13.22 29.2 30.6 11.44 27.3 33.6 9.75 25.2 37.0 8.17 45.0 33.2 26.1 15.28 31.6 28.2 13.45 29.8 30.7 11.65 27.8 33.6 9.93 25.7 37.0 8.33 46.0 33.8 26.2 15.52 32.2 28.2 13.67 30.4 30.7 11.85 28.4 33.7 10.11 26.2 37.0 8.49 48.0 35.1 26.3 16.00 33.4 28.4 14.12 31.5 30.8 12.26 29.5 33.7 10.48 27.3 37.1 8.81 50.0 36.4 26.5 16.48 34.7 28.5 14.57 32.7 31.0 12.68 30.6 33.8 10.85 28.3 37.2 9.14 (A suitable antifreeze solution is required for operation below 40°F Ambient) 65.0 75.0 85.0 95.0 105.0 AHRI specification points are in bold. ASP - 60X (61X) Air Cooled Modular Chiller Ambient Air Temperature °F Leaving Chilled Water °F Tons kW EER Tons kW EER Tons kW EER Tons kW EER Tons kW EER 40.0 63.7 53.3 14.34 60.4 58.0 12.48 56.8 63.6 12.72 53.0 69.9 9.09 49.0 77.2 7.61 42.0 66.3 53.5 14.85 62.8 58.2 12.94 59.1 63.7 11.12 55.2 70.1 9.44 51.0 77.3 7.91 44.0 68.9 53.8 15.36 65.3 58.5 13.40 61.5 63.9 11.53 57.4 70.3 9.80 53.1 77.5 8.22 45.0 70.2 53.9 15.62 66.6 58.6 13.63 62.7 64.0 11.74 58.6 70.4 9.98 54.2 77.6 8.38 46.0 71.6 54.1 15.88 67.8 58.7 13.87 63.9 64.1 11.95 59.7 70.5 10.16 55.3 77.7 8.53 48.0 74.3 54.4 16.40 70.5 59.0 14.34 66.4 64.4 12.37 62.0 70.7 10.53 57.5 77.9 8.85 50.0 77.2 54.7 16.93 73.2 59.2 14.82 68.9 64.6 12.80 64.4 70.9 10.91 59.7 78.1 9.17 (A suitable antifreeze solution is required for operation below 40°F Ambient) 65.0 75.0 85.0 95.0 105.0 AHRI specification points are in bold. IPLV Performance Chart 25% 50% 75% 100% IPLV ASP-10 .676 .775 .973 1.247 .851 ASP-15 .642 .744 .949 1.244 .823 ASP-20 .680 .751 .931 1.222 .823 ASP-30 .702 .785 .965 1.230 .855 ASP-60 .679 .768 .955 1.224 .840 Based on AHRI standard percentage ratio point. NOTES: 1. Capacity is based on pure water. For performance using Glycol Solution, see Adjustment Factor on Page 9. 2. All full-load performance data is based on a 10°F chilled-water temperature drop through the evaporator. 3. Fan and controls kW are included in tabular kW data. 4. For total chiller performance, multiply above output (Tons) and input (kW) by the number of modules. 5. Leaving water temps below 40° requires freeze protection. 6. Based on 0.0001 fouling water for the evaporator. 7. Following ARI 550/590 Standard 29.92 inches mercury barometric pressure is used for the data basis. 5 AIRSTACK PACKAGED AIR COOLED Performance Data FCP1, Free Cooling Module, Single Module Performance Data For use with ASP-10,-15 Ambient °F 30° F 35°F 40° F 30 gpm 15.5 10.2 5.1 45 60 gpm 14.0 9.3 4.7 Capacity in Refrigeration Tons LEAVING WATER TEMPERATURE/GPM 90 gpm 13.3 8.9 4.5 30 gpm 21.2 15.8 10.4 50 60 gpm 18.7 14.1 9.4 90 gpm 17.8 13.3 8.9 30 gpm 27.0 21.5 16.0 55 60 gpm 23.5 18.8 14.1 90 gpm 22.3 17.8 13.4 55 60 gpm 45.8 36.5 27.4 90 gpm 42.9 34.4 25.7 55 60 gpm 72.3 57.7 43.2 90 gpm 63.6 50.9 38.2 55 60 gpm 72.3 57.7 43.2 90 gpm 63.6 50.9 38.2 FCP2, Free Cooling Module, Single Module Performance Data For use with ASP-20 Ambient °F 30° F 35°F 40° F 30 gpm 28.9 18.9 9.3 45 60 gpm 27.0 18.0 9.0 Capacity in Refrigeration Tons LEAVING WATER TEMPERATURE/GPM 90 gpm 25.6 17.1 8.5 30 gpm 41.0 30.1 19.9 50 60 gpm 36.2 27.3 18.1 90 gpm 34.2 25.7 17.1 30 gpm 53.8 42.8 31.3 FCP3, Free Cooling Module, Single Module Performance Data For use with ASP-30 , -60, -61 Capacity in Refrigeration Tons LEAVING WATER TEMPERATURE/GPM Ambient °F 45 50 30 gpm 60 gpm 90 gpm 30 gpm 60 gpm 90 gpm 30 gpm 30° F 60.4 42.9 37.8 82.2 57.5 50.8 104.3 35°F 40.0 28.6 25.3 61.1 43.1 37.9 82.8 40° F 19.3 14.4 12.7 40.1 28.8 25.4 61.7 Notes: 1. Capacity is based on pure water. For performance using Glycol solution, see Adjustment Factor on Page 9. 2. A suitable antifreeze solution is required for operation below 40°F Ambient FCP4, Free Cooling Module, Single Module Performance Data For use with ASP-30 , -60, -61 Capacity in Refrigeration Tons LEAVING WATER TEMPERATURE/GPM Ambient °F 45 50 30 gpm 60 gpm 90 gpm 30 gpm 60 gpm 90 gpm 30 gpm 30° F 60.4 42.9 37.8 82.2 57.5 50.8 104.3 35°F 40.0 28.6 25.3 61.1 43.1 37.9 82.8 40° F 19.3 14.4 12.7 40.1 28.8 25.4 61.7 Notes: 1. Capacity is based on pure water. For performance using Glycol solution, see Adjustment Factor on Page 9. 2. A suitable antifreeze solution is required for operation below 40°F Ambient General Data Table of Air Cooled Standard –Free Cool Modules Condenser Fans Motor Type HP Quantity Fan Type Fan Material Air Flow (cfm) (per module) FCP1 FCP2 Totally Enclosed 1 2 Axial Comp 8,500 FCP1 Totally Enclosed 2 2 Axial Comp 16,000 FCP2 FCP3 Totally Enclosed Totally Enclosed 2 2 2 2 Axial Axial Comp Comp 22,000 FCP3 FCP4 Condenser Coils* Fin Material Aluminum Aluminum Aluminum Tube Material Copper Copper Copper Tube Diameter (in.) 1/2 1/2 1/2 Number of Rows 6 6 6 Coil Dimensions (Quantity) 30 x 49 (2) 30 x 611/2 (2) 42 x 731/2 (2) Free Cooling Coil Water Volume (gallons) 10.8 15.2 30.8 Module Dry Weight (lb.) 1150 1550 1850 *On Free Cool Modules, coils are utilized as water precoolers rather than for refrigerant condensing. 6 FCP4 Aluminum Copper 1/2 6 AIRSTACK PACKAGED AIR COOLED General Data Compressor Type Nominal Capacity (per compressor) Quantity General Data Table of Air Cooled Standard –X Modules ASP-10X SCROLL 5 2-TANDEM ASP-15X SCROLL 7.5 2-TANDEM ASP-20X SCROLL 10 2-TANDEM ASP-30X SCROLL 15 2-TANDEM ASP-60X SCROLL 30 2-TANDEM ASP-61X SCROLL 30 2-TANDEM Evaporator Type Weight Evap Water Storage (gallons each) Quantity Header Storage (gallons per header) Refrigerant Type Number of Circuits ASP-10X BRAZED PLATE 54.4 1.08 1 3.2 410a 1 Condenser Fans Motor Type HP Quantity Fan Type Fan Material Air Flow (cfm) (per module) ASP-10X ASP-15X ASP-20X ASP-30X ASP-60X ASP-61X Totally Enclosed Totally Enclosed Totally Enclosed Totally Enclosed Totally Enclosed Totally Enclosed 1 1 2 2 2 15 2 2 2 2 4 1 Axial Axial Axial Axial Axial Axial Composite Composite Composite Composite Composite Composite 6,600 8,500 16,000 22,000 44,000 44,000 Condenser Coils* Fin Material Tube Material Tube Diameter (in.) Number of Rows Coil Dimensions (Quantity) Free Cooling Coil Water Volume (gallons) Module Dry Weight (lb.) ASP-10X Aluminum Copper 3/8 4 32 x 51 (2) 3.5 1370 ASP-15X ASP-20X ASP-30X ASP-60X ASP-61X BRAZED PLATE BRAZED PLATE BRAZED PLATE BRAZED PLATE BRAZED PLATE 63.8 83.7 100 214.4 214.4 1.4 2.03 2.54 5.86 5.86 1 1 1 1 1 3.2 6.24 10.5 18.2 18.2 410a 410a 410a 410a 410a 1 1 1 1 1 ASP-15X Aluminum Copper 3/8 6 30 x 49 (2) 3.5 1400 ASP-20X Aluminum Copper 3/8 6 30 x 611/2 (2) 4.6 1700 ASP-30X Aluminum Copper 3/8 6 42 x 731/2 (2) 4.6 2100 Refrigerant Type R410a R410a R410a Charge (lbs./circuit) 40 60 Number of Circuits 1 1 1 Operating Weight (with AL/CU coils) 1430 1470 1820 Shipping Weight (with AL/CU coils) 1370 1400 1700 Operating Weight (with CU/CU coils) 1650 1770 2300 Shipping Weight (with CU/CU coils) 1590 1700 2180 *On Free Cool Modules, coils are utilized as water precoolers rather than for refrigerant condensing. R410a 55 1 2290 2100 2920 2730 ASP-60X Aluminum Copper 3/8 6 42 x 731/2 (4) 7.2 4,000 ASP-61X Aluminum Copper 3/8 6 42 x 731/2 (4) 7.2 5,400 R410a R410a 1 4350 4000 5610 5260 1 5750 5400 7010 6660 7 AIRSTACK PACKAGED AIR COOLED Pump Selection Charts ASP DUAL PUMP SELECTION CHART (ALL PUMPS IN PRIMARY/STANDBY ARRANGEMENT–DATA FOR SINGLE PUMP) Charts Show Pump BHP Requirement at Given Condition ARMSTRONG SERIES 4382 – 3x3x6 Pump Total head in feet Flow (USGPM) 60 80 100 120 140 40 3.07 3.87 4.66 5.47 80 3.58 4.47 5.37 6.29 120 3.55 4.52 5.51 6.50 7.51 160 4.82 5.91 7.00 8.09 9.20 200 6.71 7.94 9.13 10.34 10.97 12.27 240 ARMSTRONG SERIES 4382 – 4x4x6 Pump Total head in feet Flow (USGPM) 60 80 100 120 140 50 3.80 4.89 6.10 7.44 100 4.52 5.77 7.12 8.57 9.71 150 3.98 5.30 6.70 8.16 200 4.78 6.26 7.79 9.39 250 5.81 7.54 9.14 10.90 300 7.16 9.03 10.91 350 8.90 11.07 ARMSTRONG SERIES 4382 – 6x6x6 Pump Total head in feet Flow (USGPM) 60 200 300 80 100 120 140 7.86 10.24 12.78 15.47 9.75 12.39 15.15 400 8.99 11.82 14.73 17.72 500* 10.93* 14.14* 17.34* 20.59* 600* 13.06* 16.68* 20.26* 700* 15.48* 19.51* 800* 18.35* 22.76* *For selections above 400 gpm contact Multistack® Notes: 1. 2. 3. 4. 8 DO NOT SELECT IN SHADED AREA. All selections are based on 40% Ethylene Glycol solution. Pump speed is 3,600 rpm. All pump modules have automatic changeover controls in the event of loss of flow and manual lead/lag selector switch. AIRSTACK PACKAGED AIR COOLED Adjustment Factors Figure 3. Ethylene Glycol Adjustment Factor Figure 1. Performance Adjustment Factor PERFORMANCE ADJUSTMENT FACTOR Pressure Drop GPM KW Capacity Figure 4. Propylene Glycol Adjustment Factor Figure 2. Water Pressure Drop A- ASP-10X D- ASP-30X B- ASP-15X E- ASP-60X (61X) C- ASP-20X A B C D E Pressure Drop GPM KW Capacity 9 AIRSTACK PACKAGED AIR COOLED Selection Data SELECTION To select an AIRSTACK Air Cooled chiller, the following information is required. 1. Load (in tons) of refrigeration. 2. Chilled-water temperature drop. 3. Leaving chilled-water temperature. 4. Design ambient-air temperature. CAPACITY TABLES Capacity tables are based on a 10°F temperature drop through the evaporator. For other than a 10°F temperature drop, apply the respective performance adjustment factors from Figure 1. EVAPORATOR WATER FLOW RATE Evaporator water flow is determined as follows: gpm = (24) (tons) / temperature drop WATERSIDE PRESSURE DROP Evaporator waterside pressure drops are provided in Figure 2. To use Figure 2, divide the total chilled-water gpm by the number of modules in the chiller. CHILLED-WATER SELECTION SAMPLE (Assumes ASP-15 Modules) 1. System load = 55 tons. Chilled-water drop at 12°F. 2. Leaving chilled-water temperature of 45°F. Design ambient-air temperature of 95°F. 3. Use the Figure 1 adjustment factor to convert tons at 12°F to equivalent tons at 10°F for use with capacity tables. Tons = 55/1.012 = 54.3 tons 4. Select the appropriate performance table based on the module to be used. Read the capacity and kW of a single module at the water temperature specified (45°F) and design ambient-air temperature (95°F). capacity = 14.4 tons, kW = 15.8 Divide the equivalent tons required at 10°F temperature drop by the single module capacity from the tables. Modules required = 54.3/14.4 = 3.8 modules Chiller capacity = 14.4 x 4 = 57.6 tons Power input = 15.8 x 4 = 63.2 kW at 12°F temperature drop; applying the Figure 1 performance adjustment factor results in: tons = (57.6) (1.012) = 58.3 vs. system load of 55 tons. 5. To determine the evaporator water flow and pressure drop, first determine gpm. gpm = (24)(54.3)/12=108.6 gpm/module = 108.6/4 = 27.2 From Figure 2, read pressure drop from curve C pressure drop = 2.4 ft. of water. 10 LOW-TEMPERATURE OPERATION WITH GLYCOL (Assumes ASP-15 Modules) Ethylene Glycol adjustment factors (Figure 3) should be used to adjust performance depending on the percent of glycol use in the evaporator circuit. The factors in Figure 3 are based on a 10°F change in fluid temperature through the evaporators. Capacity and kW should be obtained by extrapolating no more than 10°F from the lowest leaving chilled-water temperature shown in the capacity tables. Multistack should be contacted if leaving Glycol temperatures below 32°F are required. Adjustment factors for Propylene Glycol are shown in Figure 4, and are used in the same way given in the following example. ETHYLENE GLYCOL SELECTION EXAMPLE (Assumes ASP-15 Modules) Determine the capacity, gpm, pressure drop, and kW for an ASP-15 module cooling 30% Ethylene Glycol from 45°F to 35°F, with design ambient-air temperature of 95°F. 1. By extrapolating from the performance tables: capacity: 11.5 tons; 15.8 kW 2. Evaporator water flow and pressure drop are determined for water as in the previous example. gpm = (24) (11.5) = 27.6 gpm 10 From Figure 2, read the pressure drop from the curve C pressure drop = 2.6 ft of water To convert performance for water to performance with Ethylene Glycol, read adjustment factors from Figure 3 at 30% Glycol. Capacity adjustment: 0.94 kW adjustment: 0.99 gpm adjustment: 1.10 Pressure drop adjustment: 1.22 Calculate performance with 30% Ethylene Glycol by multiplying performance for water by adjustment factors. Capacity: 11.5 x .94 = 10.8 tons kW: 15.8 x .99 = 15.6 kW gpm: 27.6 x 1.10 = 30.4 gpm Pressure drop: 2.6 x 1.22 = 3.2 ft of water If a water-temperature drop greater or less than 10°F is required, begin by first multiplying the capacity using the performance adjustment factor from Figure 1. AIRSTACK PACKAGED AIR COOLED Selection Data IMPORTANT MODULE CONFIGURATION INFORMATION ASP-00P PUMP MODULE: 1.When present, a Pump Module is only allowed in the “Front” position. 2.Incoming water to the chiller system must enter at the Pump Module. 3.Leaving water from the chiller system may be from either end of the chiller. ASP-1FX, 2FX, 3FX FREE COOL MODULE: 1.When present, incoming system water must enter through the Free Cool Modules prior to entering an ASP-10X, 15X, 20X, 30X, 60X or 61X Chiller Module. 2.You may not attach a Rear Free Cool Module to a Front ASP-10X, 15X, 20X, 30X, 60X or 61X Chiller Module. ASP-00G GLYCOL FEEDER MODULE: 1. An ASP-00G Glycol Feeder Module may be attached in any rear position. ASP-10X, 15X, 20X, 30X, 60X, 61X CHILLER MODULE: 1.The maximum number of ASP-10X, 15X, 20X, or 30X,modules with a single Master Module is 14 (i.e., (1) Front-Master, (6) Front-Slaves, and (7) Rear-Slaves). For 60X and 61X modules, the maximum is nine modules. 2.You may have more than one Master Module in a single chiller bank. 3.Piping sides of an ASP-10X, 15X, 20X, 30X, 60X or 61X chiller without Free Cool or Pump Modules attached are field selectable. LEGEND: FIRST LETTER VALID CONFIGURATIONS Tank FF PF MF SR SR SR SR SR PF SF SF SF SF SR SR PF MF SF FR FR SR SR PF FF MF SF SF SR GR SR SR SR MF SF SF MF SF SF SR SR SR PF MF SF FR SR SR SR PF FF MF SF SR SR SR SF SF INVALID CONFIGURATIONS SR SR SR MF SF SF M=Master Chiller Module (ASP-10X, 15X, 20X, 30X or 60X) S = Slave Chiller Module (ASP-10X, 15X, 20X, 30X or 60X) P= Pump Module (ASP-00P) F = Free Cool Module (ASP-1FX, 2FX, 3FX) G = Glycol Feeder Module (ASP-00G) Problem: Cannot have a stand alone rear module. Solution: Make Slave Rear a Slave Front. SECOND LETTER Problem: Pump module after Master. Solution: Swap placement so incoming water enters at the pump module. F = Front Module R = Rear Module FRONT OF CHILLER BANK IS TOWARD THE BOTTOM OF THE PAGE (Master Module location determines front of chiller) For other configurations, contact your local Multistack® Representative. MF SR SR PF SF SR SR SR PF MF GF Problem: Glycol Feeder Module is attached in a front position. Solution: Move Glycol Feeder Module to rear position and exchange Slave Rear Module for Slave Front Module. TYPICAL ASP-60X or 61X CONFIGURATION M S S S 11 AIRSTACK PACKAGED AIR COOLED Diagrams All ASP-60X units come standard with four multi-blade vane axial condenser fans. The ASP-61X is a single fan unit available with a Low Sound (polyresin reinforced) Blade or Ultra Low Sound (fiberglass construction) Blade option. Testing has shown a sound reduction of 6dB with the Low Sound and an additional 4dB with the Ultra Low Sound design. INTAKE NOTES: · NO OBSTRUCTIONS ALLOWED ABOVE CONDENSER FANS. · REQUIRED SERVICE CLEARANCE AT MODULE ENDS: 42”. · REQUIRED AIR INTAKE (FRONT) CLEARANCE: 42” · REQUIRED CLEARANCE FROM ANY HIGH VOLTAGE PANEL: 42” INTAKE 12 ASP-60X and ASP-61X Notes: 1. No obstructions allowed above condenser fans. 2. Required service clearance at module ends: 42” 3. Required air intake (front) clearance: 42” 4. Required clearance from any high voltage panel 42” 5. Required clearance from any grounded wall: 42” Any non-grounded wall: 36” AIRSTACK PACKAGED AIR COOLED Diagrams NUMBER OF MODULES X “A” + 4” 2” ASP-010X, -015X ASP-020X TOP VIEW NOTES: 1. NO OBSTRUCTIONS ALLOWED ABOVE CONDENSER FANS. 2. REQUIRED SERVICE CLEARANCE AT MODULE ENDS: 36”. 3. REQUIRED AIR INTAKE CLEARANCE: 42”. (Unobstructed)* 4. REQUIRED CLEARANCE FROM ANY HIGH VOLTAGE PANEL: 42” ASP-030X “D” “D” DISCHARGE DISCHARGE CONDENSER COIL ELECTRICAL PANEL “C” “C” INTAKE FRONT VIEW INTAKE FRONT VIEW “B” 2” “A” 2” ASP-010X, -015X ASP-020X ASP-030X “D” NOTES: 1. NO OBSTRUCTIONS ALLOWED ABOVE CONDENSER FANS. 2. REQUIRED SERVICE CLEARANCE AT MODULE ENDS: 36”. 3. REQUIRED AIR INTAKE CLEARANCE: 42”.* 4. REQUIRED CLEARANCE FROM ANY HIGH VOLTAGE PANEL: 42”. 5. REQUIRED CLEARANCE FROM ANY GROUNDED WALL: 36”. 6. NO CLEARANCE REQUIRED FROM REAR. DISCHARGE CONDENSER COIL ELECTRICAL PANEL “C” INTAKE FRONT VIEW RIGHT SIDE VIEW REAR VIEW *Note: If insullation is in a pit or near walls that are taller than modules, please contact Multistack for clearances. 13 AIRSTACK PACKAGED AIR COOLED Electrical Data REQUIRED CHILLED-WATER PIPING (SUPPLIED AND INSTALLED BY OTHERS) (*If ASP -00P Pump Module is Supplied by Airstack, eliminate external pump shown below.) ELECTRICAL DATA Model ASP - 10X ASP - 15X ASP - 20X ASP - 30X ASP - 60X ASP - 61X ASP - 1FX ASP - 2FX ASP - 3FX ASP - 00P ASP - 00P ASP - 00P ASP - 00P ASP - 00P ASP - 00P ASP - 00G Number of Compressors 2 2 2 2 2 2 N/A N/A N/A RLA per Compressor 3 phase 1 phase 208/460/575V 230V 19.5/8.7/7.2 25.0 31/14.0/11.5 N/A 35/15.5/12.0 N/A 55/26.0/21.0 N/A N /A/47.0/38.0 N/A N /A/47.0/38.0 N/A N/A N/A N/A N/A N/A N/A Number of Fan Motors 2 2 2 2 4 1 2 2 2 WIRING SIZING (MCA= MINIMUM CIRCUIT AMPACITY) MCA = (1.25 x RLA1*) + RLA2 + RLA3 . . . . . . FUSE SIZING (MFS = MAXIMUM FUSE SIZE) MFS = (2.25 x RLA1*) + RLA2 + RLA3 . . . . . . Where MFS does not equal a standard size fuse, the next larger fuse should be used. NOTES: 1. Compressor Rated Load Amps (RLA) are based on 125°F Saturated Condensing Temperature. 2. *RLA1 = RLA of the largest motor in the system. RLA2 & RLA3 = RLA of other motors in the system. 3. Wire sizing is based on Nat. Electr. Code (NEC)rating for 75°C wire, with 3 wires per conduit. 4. Wiring distance from branch circuit shall not exceed 100 feet. 14 FLA per Fan Motor 3 phase 1 phase 208/460/575V 230V 4.0/2.0/1.5 5.0 4.0/2.0/1.5 N/A 7.4/3.6/2.8 N/A 7.4/3.6/2.8 N/A N /A/3.6/2.8 N/A N /A/18.1/14.8 N/A 4.0/2.0/1.5 N/A 7.4/3.6/2.8 N/A 7.4/3.6/2.8 N/A Pump HP Max Pump FLA 3 phase 1 phase 208/460/575V 230V 5 7.5 10 15 20 25 N/A 16.7/7.6/6.1 24.2/11/9 30.8/14/11 46.2/21/17 59.4/27/22 74.8/34/27 2/1/1 28 N/A N/A N/A N/A N/A 2 MCA WIRE SIZE (AWG) 75° (3 Conductors/1Conduit) MCA WIRE SIZE (AWG) 75° (6 Conductors/2Conduit) 50 65 85 100 115 130 150 175 200 230 255 285 310 335 380 420 8 6 4 3 2 1 1/0 2/0 3/0 4/0 250 MCM 300 MCM 350 MCM 400 MCM 500 MCM 600 MCM 510 570 620 670 760 800 250 MCM 300 MCM 350 MCM 400 MCM 500 MCM 600 MCM AIRSTACK PACKAGED AIR COOLED Specifications GENERAL Chiller Modules shall be ETL listed in accordance with UL Standard 1995, CSA certified per Standard C22.2#236, and bear the ASME UM stamp on all waterto-refrigerant heat exchangers. Modules shall ship wired and charged with refrigerant. All modules shall be factory run-tested prior to shipment. Compressors, heat exchangers, condenser fans, piping, and controls shall be mounted on a heavy-gauge steel frame. Electrical controls, contactors, and relays for each module shall be mounted within that module. The module shall be provided within a steel enclosure suitable for outdoor use. Exposed steel surfaces shall be provided with a powder-coat paint finish. CHILLED-WATER MAINS Each module shall include supply and return mains for chilled water. Grooved end connections are provided for interconnection to four-inch (ASP 10X, 15X), six-inch (ASP 20X and 30X) or eight-inch (60X and 61X) standard piping with Victaulic-type couplings. Each inlet water header shall incorporate a built-in, 30-mesh in-line strainer system to prevent heat exchanger fouling. EVAPORATORS Each evaporator shall be a brazed-plate heat exchanger constructed of 316 stainless steel, and be designed, tested, and stamped in accordance with U.L. 1995 650 PSIG working pressure. COMPRESSOR Each module shall contain hermetic scroll compressor(s) mounted to the module with rubber-in-shear isolators. Each system shall also include high discharge-pressure and low suction-pressure safety cut-outs. CONDENSER COILS Air cooled condenser coils shall have aluminum fins mechanically bonded to copper tubing. Condensers shall have integral subcooling circuitry and be factory leak-tested. CONDENSER FANS Each module shall contain dual condenser fans for each refrigerant circuit. These fans shall be multi-blade vane-axial type, made of plastic composite material for quiet operation. Fans shall be direct driven at a maximum rpm of 1,150. All fan motors shall be pressure controlled and suitable for outdoor use. ASP 60X modules have four fans, ASP 61X have a single unit fan. CENTRAL CONTROL SYSTEM Scheduling of the various compressors shall be performed by a microprocessorbased control system (Master Controller). A new lead compressor is selected every 24 hours to ensure even distribution of compressor run time. The Master Controller shall monitor and report the following on each refrigeration system: • Discharge Pressure Fault -- Suction Pressure Fault -- Compressor Winding Temperature Fault -- Suction Temperature -- Evaporator Leaving Chilled-Water Temperature The Master Controller shall monitor and report the following system parameters: • Chilled-Water Entering and Leaving Temperature -- Discharge Refrigerant Temperature -- Chilled-Water Flow Fault An out-of-tolerance indication from these controls or sensors shall cause a “fault” indication at the Master Controller and shutdown of that compressor, with the transfer of load requirements to the next available compressor. In the case of a System Fault, the entire chiller will be shut down. When a fault occurs, the Master Controller shall record conditions at the time of the fault and store the data for recall. This information shall be capable of being recalled through the keypad of the Master Controller and displayed on the Master Controller’s LCD. A history of faults shall be maintained, including date and time-of-day of each fault (up to the last 20 occurrences). Individual monitoring of leaving chilled-water temperatures from each refrigeration system shall be programmed to protect against freeze-up. The control system shall monitor entering and leaving chilled water temperatures to determine system load, and select the number of compressor circuits required to operate. Response times and set points shall be adjustable. LOW AMBIENT OPERATION Each refrigerant circuit shall include all refrigerant specialties to provide reliable operation down to 20°F ambient. With proper freeze protection. OPTIONAL LOW AMBIENT TO -20°F The chiller shall incorporate appropriate refrigerant specialties, including a properly sized refrigerant receiver and flooded head pressure control valves for operation to -20°F. OPTIONAL SINGLE-POINT POWER CONNECTION The chiller shall be provided with a single-point power connection. This will include pre-engineered wiring for field installation and connection to a factorymounted chiller junction box. The junction box shall include individual fusing for each Module Set and provide a single point of connection to building power. OPTIONAL Free CoolING MODULE Free Cooling Modules shall interconnect through the common chiller header system and require no additional water connections. Free Cooling Modules shall include glycol cooling coils, temperature-controlled fans, and an automatic 3-way bypass valve to eliminate the need for mechanical cooling under lowambient conditions. The module shall be completely factory-assembled and tested before shipment. OPTIONAL PUMP MODULE The Pump Module shall be interconnected through the common chiller header system and require no additional water connections. The Pump Module will become an integral part of the chiller system. The Pump Module shall incorporate dual in-line centrifugal pumps in a Primary/Standby pumping arrangement. Pump starters and controls shall be provided to enable manual selection of lead pump. In addition, in the event of a loss-of-flow failure of the chilled-water system, the Pump Module controls shall disable the lead pump and automatically start the standby pump. The Pump Module shall be completely factory assembled and tested prior to shipment. OPTIONAL TANK MODULE A factory-assembled Tank Module shall be provided, including an insulated chilled water tank. The tank shall be pressure-rated at 150 psi minimum. Tank Modules shall interconnect through the common chiller header system and require no additional water connections. The Tank Module will become an integral part of the chiller system. The Tank Module shall be provided with proper drain and fill valving. Cont’d on next page… 15 OPTIONAL GLYCOL FEEDER MODULE The optional Glycol Feeder and Expansion Tank shall be incorporated into the chiller system through a modular arrangement and interconnect through the common chiller header system, requiring no additional water connections. The system shall include a 48-gallon storage/mixing tank with lid and cover, pump suction hose with inlet strainer, pressure pump with thermal cut-out and integral pressure switch, pre-charged accumulator tank with EPDM diaphragm, manual diverter valve for purging and agitating contents of storage tank, adjustable 5-55 psi pressure regulating valve with pressure gauge, fast fill lever, integral replaceable strainer, built-in check valve, and built-in shutoff valve. The glycol feeder system shall be compatible with glycol solutions of up to 50% concentration. The pump shall be capable of running dry without damage. The expansion tank shall be welded steel with a butylrubber diaphragm, and capable of a maximum operating temperature of 240°F and a maximum working pressure of 100 psig. The tank shall be interconnected through the common chiller header system and require no additional water connections. The module shall be completely factory assembled and -tested prior to shipment. OPTIONAL SOUND-ATTENUATION MODULE 1. Each Free Cooling module shall have VFD-controlled condenser fan motors soft start and precise fan speed control. 2. Each mechanical cooling module shall have oversized condenser coils and VFD controlled condenser fan motors that modulate to maintain head pressure for precise fan speed control. Fans shall have acoustically optimized fan blades utilizing a composite material. Compressors shall be wrapped with high-temperature acoustic covers consisting of a dense-design fabric exterior with quilted acoustical fiberglass interior and open edges sealed with silicone coated fabric with hook and loop closures. 1065 Maple Avenue P.O. Box 510 Sparta, WI 54656 Phone 608-366-2400 • Fax 608-366-2450 www.multistack.com F154ACSD0610