VITOFLAME 200 50 kW GB

Transcription

VITOFLAME 200 50 kW GB
Service
instructions
for heating engineers
Vitoflame 200
Oil pressure jet burner (typeVEK)
H up to 40 kW with oil pre−heater
H from 50 kW without oil pre−heater
Vitorond200 and Vitorond222
See notes on applicability, page2.
VITOFLAME 200
Vitoflame 200 oil burner
fitted to Vitorond200
5692452 GB2/2002
File in: Service folder
General Information
Safety instructions
Please follow these safety instructions closely to prevent accidents and material losses.
Work on the equipment
Installation, initial start−up,
maintenance and repairs must only
be carried out by a competent
person (heating engineers/
installation contractors) (EN50110,
part1, and VDE1000, part10, or
local regulations).
Before working on the equipment/
heating system, isolate the mains
electrical supply (e. g. by removing a
separate mains fuse or by means of
a mains electrical isolator) and
safeguard against unauthorised
reconnection.
Disconnection must be carried out
by means of an isolating device
which simultaneously isolates all
non−earthed conductors with at least
3 mm contact separation.
Repair work
It is not permitted to carry out
repairs on parts that fulfil a safety
function.
Use only original Viessmann spare
parts or equivalent which have been
approved by Viessmann.
Initial start−up
This must be carried out by the
system installer or a commissioning
engineer designated by him; all
actual values should be recorded in a
commissioning/service report.
Instructing the system user
The system installer must hand the
operating instructions to the system
user and instruct him/her in the
operation of the system.
This symbol is a reference
to other instructions which
must be observed.
Work requiring the control unit to be
opened must not subject internal
components to electrostatic
discharges.
Applicability
Applicable to burners from serial no.:
7159805200001kkk,
7159806200001kkk,
7159807200001kkk,
7159808200001kkk,
7159809200001kkk,
7159810200001kkk,
7159811200001kkk,
7159812200001kkk
Operating and service documents
2. File all parts lists, operating and
service instructions in the folder
and hand over to the system user.
5692452 GB
1. Complete and separate the
customer registration card:
H Hand the system user section
to the user for safekeeping.
H Keep the heating engineer
portion.
2
Contents
Page
General Information
Initial start−up,
inspection and maintenance
Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
Applicability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
Operating and service documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
Procedure summary
.........................................................................................
4
..................................................................................................
5
Implementation
Burner control unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Troubleshooting
Procedure summary
.........................................................................................
18
Diagnosis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Additional information
Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Standard values for burner settings
.........................................................
22
Component summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Parts list
.................................................................................................................
27
Commissioning/service report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
........................................................................................................................
32
5692452 GB
Index
3
Initial start−up, inspection and maintenance
Procedure summary
Initial start−up steps
Steps for biannual inspection
Maintenance steps
I
I
I
I
1. System start−up
I
I
I
I
I
I
2. Oil pressure adjustment and vacuum check
....................................................................
Page 5
Page 6
3. Air volume fine adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7
4. Checking the burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 8
5. Flame monitor check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 8
6. Heating system shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 8
7. Checking the electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 9
8. Cleaning the burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 9
9. Checking the impeller fixings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 10
10. Checking the flame tube fixings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 10
11. Nozzle replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 11
12. Checking and adjusting the ignition electrodes
.............................................................
13. Burner cover installation on the burner housing
...........................................................
Page 12
Page 12
14. Cleaning or, if necessary, replacing the oil pump filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 13
15. Pre−filter element replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 13
16. System start−up
.............................................................................................................................
Page 14
17. Checking all oil pipes and connections for leaks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 14
18. Re−checking the burner
..............................................................................................................
Page 14
5692452 GB
I
I
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
.............................................................................................................................
4
Initial start−up, inspection and maintenance
Implementation
To obtain the optimum combustion values, it is essential to adjust the burner
with the boiler heated to operating temperature.
Check the CO content, CO2 content, flue gas temperature, room temperature
and chimney draught after 2minutes operation and at 60 ºC boiler water
temperature with fitted burner hood.
Remove the burner hood before commencing maintenance work.
Initial start−up
1. System start−up
Service instructions
Boiler control unit
Please note:
Vitoflame 200 oil burners have
excellent combustion values which
are achieved without the use of fuel
oil additives to improve combustion.
We do not therefore recommend the
use of such combustion improvers.
1. Check whether the flame tube
attachment (for 15 to 33 kW
output) has been fitted.
2. Check the heating system
pressure and the oil level in the
tank.
3. Open the shut−off valves in the oil
supply lines on the oil tank and on
the filter.
4. Fill the oil suction line and filter
with fuel oil using the manual oil
suction pump before switching on
the burner.
5. Switch on the mains electrical
isolator (outside the boiler room).
5692452 GB
6. Switch on system On/Off
switchB on the control unit.
If fault indicator lampA on the
control unit illuminates, press reset
buttonC on the burner.
Please note:
For Vitorond 222:
For balanced flue operation the air
supply duct should be fitted before
burner setup. Observe the following
values during this step:
H Pressure loss in the air supply duct
max. 35 Pa,
H Air inlet temperature in the inlet
adaptor min. 5°C/max. 30°C.
5
Initial start−up, inspection and maintenance
Implementation (cont.)
Initial start−up
Maint.
2. Oil pressure adjustment and vacuum check
Please note:
The oil pressure is preset at the factory according to the oil throughput.
Adjust the oil pressure, if necessary.
1. Isolate the mains electricity
supply and safeguard against
reconnection.
2. Unscrew drain plug"P" A from
the oil pump.
3. Unscrew drain plug"V" B from
the oil pump.
Please note:
This allows the oil to drain from
the oil pump.
4. Insert a pressure gauge (range
0 25bar) and a vacuum gauge
(range 0 1bar); seal the gauges
only with copper or aluminium
rings or O−rings.
Please note:
Do not use tape to seal these
joints.
5. Start up the burner.
The solenoid valve opens.
6. Read off the oil and vacuum
pressures of the pump on the
relevant gauges (vacuum should
be max. 0.35bar given a head of
3 m between the oil pump and
the bottom of the tank).
Where the vacuum measures
higher than 0.35bar, check the
filter for cleanliness or the pipe
run.
7. If necessary, set the oil pressure
on oil pump pressure setting
screw C (for Danfoss pumps:
depending on the model either on
the front or the side).
Turning clockwise³pressure
increases
Turning anti−clockwise³pressure
decreases.
Please note:
For standard values for burner
settings, see page22.
Danfoss oil pump, typeBFP21
8. Check the emission values after
checking the oil pressure.
9. Isolate the mains electricity
supply and safeguard against
reconnection.
10. Remove the pressure and
vacuum gauges.
11. Insert drain plugs"P" A
and"V" B.
12. Start up the burner and
check the plugs for leaks.
6
Please note:
Check the plug seal rings
for possible damage and replace,
if necessary.
5692452 GB
Suntec oil pump, typeAL35
Initial start−up, inspection and maintenance
Implementation (cont.)
Initial start−up
Maint.
3. Air volume fine adjustment
Please note:
The oil pressure is preset at the factory. Re−adjust the air volume if necessary.
Starting up the burner may require a fine adjustment.
1. Modify the sensor plate position
inside the flame tube. To do this,
turn the blast tube connection
setscrewC:
H Anti−clockwise³greater
cross−section³more air,
H clockwise³smaller cross
section³less air.
Please note:
For standard values for burner
settings, see page22.
2. Check the static burner pressure at
test nippleB.
3. Check the emission values by
measurement.
Please note:
Do not slacken sealed clamping
screw E, otherwise the zero point of
the blast tube connection will be
altered.
5692452 GB
A Air damper
B Test nipple
C Blast tube connection setscrew
D Blast tube connection
E Terminal screw
F Sensor plate
G Flame tube
7
Initial start−up, inspection and maintenance
Implementation (cont.)
Initial start−up
Maint.
4. Checking the burner
Record all test values in the order of
the commissioning/service report on
the penultimate page of this manual.
Inspection Maint.
Please note:
The flue pipe must be sealed on
the boiler adaptor. Infiltrating air
leads to false readings.
5. Flame monitor check
1. Pull flame monitorA from
flangeB.
2. Clean the flame monitor.
.
.
Safety check
Response
Burner start with darkened flame monitor
Fault shutdown at the end of
the safety period
Burner start with flame monitor lit from
an outside source
Fault shutdown not later than
after 40 sec.
3. Push flame monitorA into
flange B, until strap C
noticeably clicks into place.
Please note:
Observe the angle and distance.
Safety check
Response
Burner operation with simulated flame
interruption: to do this pull plug D from
the solenoid valve during operation and
leave in this condition.
Restart followed by fault
shutdown at the end of the
safety period
E Sight glass of the flame monitor
F Strap centering tab
Inspection Maint.
6. System shutdown
1. Isolate the mains electricity supply
and safeguard against
reconnection.
3. Close the oil supply line (oil filter
valve).
8
5692452 GB
2. Pull plug−connectorfA from the
burner.
Initial start−up, inspection and maintenance
Implementation (cont.)
Inspection Maint.
7. Checking the electrical connections
Check the plug−connections on the
burner components and the cable
bushes for tight fit.
Maint.
8. Cleaning the burner
1. Burner in the maintenance
position.
Cleaning the combustion
chamber and hot gas flues,
see service instructions.
5692452 GB
2. Clean the housingand the flame
tube, sensor plateA, ignition
electrodesB, flame monitorC
and impellerD.
9
Initial start−up, inspection and maintenance
Implementation (cont.)
Inspection Maint.
9. Checking the impeller fixings
See maintenance item8.
Inspection Maint.
10. Checking the flame tube fixings
5692452 GB
Please note:
The flame tube must be finger
tight.
10
Initial start−up, inspection and maintenance
Implementation (cont.)
Maint.
11. Nozzle replacement
1. Plug the burner chassis, with the
blast tube connection pointing
upwards, onto the burner housing.
Please note:
This avoids air−locks being created
when replacing nozzles.
15 to 33 kW
2. Pull flame monitorD from its
retainer.
3. Release screwC by two full
turns.
4. Remove sensor plateA from the
blast tube connection.
5. Unscrew nozzleF (whilst holding
the blast tube connection).
6. Insert the replacement nozzle
(whilst holding the blast tube
connection).
Please note:
For make and type of nozzle, see
standard values for burner
settings, page22.
40 kW
7. Only for 15 to 33 kW:
Check seal ringB on deflectorE
of the sensor plate and apply
instrument grease; replace the
seal ring, if necessary.
8. Push sensor plateA onto the
blast tube connection up to the
end−stop of the oil pre−heater and
re−tighten fixing screwC.
9. Push flame monitor D into its
retainer.
Please note:
The flame monitor, type QRB,
should be positioned at the sensor
plate (see page 8).
5692452 GB
50 and 63 kW
11
Initial start−up, inspection and maintenance
Implementation (cont.)
Inspection Maint.
12. Checking and adjusting the ignition electrodes
Check ignition electrodesA for
wear and size (see fig.) and replace,
if necessary.
.
.
.
.
.
.
15 up to 33kW
.
.
.
.
40 up to 63kW
13. Burner chassis installation on the burner housing
5692452 GB
Maint.
12
Initial start−up, inspection and maintenance
Implementation (cont.)
Maint.
14. Cleaning or, if necessary, replacing the oil pump filter
Danfoss oil pump
typeBFP21
1. Unscrew filter plugA from the
pump cover with a 4mmAllen key.
2. Remove plugA with cartridge
filterC.
3. Carefully disconnect filterC from
plugA with a screwdriver.
4. Change theO−ringB on plugA.
5. Push the new filter onto plugA.
6. Insert the plug and filter into the
oil pump.
Suntec oil pump, typeAL35
1. Unscrew the four screws from the
pump housing and remove the
cover.
2. Subject to the level of
contamination, flush out the oil
pump filterAwith clean fuel oil
or replace the filter.
3. During re−assembly, renew flat
gasketB of coverD and
OringsC for the plug.
Maint.
15. Replacing the pre−filter element
5692452 GB
Check the Oring, which seals the
filter cup, for possible damage and
replace, if necessary.
13
Initial start−up, inspection and maintenance
Implementation (cont.)
Inspection Maint.
16. System start−up
1. Open the oil filter valve.
2. Switch on the mains electrical
isolator (outside the boiler room).
3. Switch on the system On/Off
switch on the control unit.
Inspection Maint.
17. Checking the oil pipes and connections for leaks
The presence of air bubbles in the
prefilter is a sign of a leak in the
suction line. Check oil pipes and
connecting pipes on the oil tanks.
Leaks will cause the fuel oil to
continue to be injected (run−on) and
produce soot deposits on the sensor
plate and on the flame tube
attachment.
Maint.
18. Re−checking the burner
Please note:
The flue pipe must be sealed on
the boiler adaptor. Infiltrating air
leads to false readings.
5692452 GB
Record all test values in the order of
the commissioning/service report on
the penultimate page of this manual.
14
Initial start−up, inspection and maintenance
Burner control unit
You may use the following burner
control units with this burner:
Burner control unit LOA 14.171B2V
For programming sequence, see the
wiring diagram on page 25.
Sensor current:
H min. requirement 50 µA
H max. permissible without flame
5.5µA
Undervoltage
When the mains voltage falls below
165 V~, the burner will be prevented
from starting or the oil flow will be
interrupted; simultaneously the
system will be initiating a fault
shutdown.
Fault position
A lamp in the reset button also
indicates the fault shutdown of the
burner control unit.
Please note:
If the power supply is 2×127 V and a
red flashing code: 10×flashing (see
page 19) refer to your local
Viessmann sales office.
Control sequence in case of faults
The fuel valve outputs and the
ignition system are immediately shut
down (< 1 s) if the system shuts
down because of faults.
Burner control unit LMO 14.113A2
For programming sequence, see the
wiring diagram on page 25.
Sensor current:
H min. requirement 40 µA
H max. permissible without flame
5.5µA
Undervoltage
If the mains voltage falls below
165V~ the burner control unit
initiates a safety shutdown.
The system re−starts when the mains
voltage rises again above approx.
175 V~.
Cause
Response
After mains power failure
Re−start
After falling below the undervoltage level
Re−start
In case of premature, faulty flame signal during the
pre−flush time t1
Fault shutdown at the end of the pre−flush time
t1
In case of premature, faulty flame signal during the
oil pre−heat time t0
Starting will be inhibited after a maximum of
40sec. fault shutdown
If the burner does not light within the safety limit t2
Fault shutdown at the end of the safety period t2
If the flame fails during operation
Max. 3 start repeats, then fault shutdown
No heating or oil pre−heater enabling within 10 min.
Fault shutdown
System creates a fault shutdown
After a fault shutdown, the burner
control unit remains locked out
(non−modifiable fault shutdown) and
the red lamp illuminates.
This state is also maintained after
the mains power supply has failed.
5692452 GB
Controlled intermittent operation
After a maximum of 24 hours
non−stop operation, the burner
control unit implements an
automatic safety shutdown with
subsequent re−start.
Resetting the boiler control unit
The system can be immediately reset
after a fault shutdown. Hold down
the reset button for approx. 1 sec.
(<3 s).
Ignition sequence
The system is re−ignited, if the flame
fails within the safety period,
however not later than at the end of
the safety period. This allows several
ignition attempts within the safety
period, see program sequence on
page 25.
switch−on (through temperature or
pressure regulators, thermostat or
pressure limiters or safety limiters).
Repeat restriction
The system may be re−ignited up to
3times, if the flame fails during
operation. The fourth flame failure
during operation triggers a fault
shutdown. The count of these
repeats begins with every controlled
15
Initial start−up, inspection and maintenance
Burner control unit (cont.)
Burner control unit LMO 14.113A2 (cont.)
Operating controls
The reset button "ET" is
the central control for
resetting the system
and for activating and
deactivating the
diagnostic system.
Both elements ("ET" and "LED") are
located under the clear cover of the
reset button.
Visual diagnosis
Operational display or fault cause
diagnosis
During normal operation the various
conditions are indicated by colour
code acc. to the following colour
code table.
The multi−coloured
signal lamp "LED" is
yellow the central display
green element for the visual
diagnosis as well as the
interface diagnosis.
red
Colour code table
Condition
Colour code
Colour
Oil pre−heater active, oil pre−heat
time t0
\\\\\\\\\\\\\
yellow
Ignition phase, ignition activated
\0\0\0\0\0\0\
yellow off
Operation, flame OK
JJJJJJJJJJJJJJ
green
Operation, poor flame
J0J0J0J0J0J0J
green off
Undervoltage
\Y\Y\Y\Y\Y\Y\
yellow red
Fault, alarm
YYYYYYYYYYYYYY
red
Fault code output
Y0Y0Y0Y0Y0Y0Y
red off
Extraneous light before burner start
JYJYJYJYJYJYJY
green red
Interface diagnosis
YYYYYYYYYYYYYY
red flickering light
5692452 GB
Legend:
0 off
\ yellow
J
green
Y red
16
Initial start−up, inspection and maintenance
Burner control unit (cont.)
Burner control unit LMO 14.113A2 (cont.)
Diagnosis of fault causes
After a fault shutdown the red signal
lamp is constantly on. In this state,
the visual diagnosis of fault causes
can be activated in accordance with
Fault setting
the fault code table, by activating the
reset button >3 s.
The diagnosis of fault causes is
activated as follows:
Fault setting
Visual diagnosis
flashing
on
reset
5692452 GB
Fault code table
17
Troubleshooting
Procedure summary
Diagnosis
1. Establish faults/ascertain system behaviour
2. Look for the corresponding cause of the fault in the diagnosis tables
3. Establish the action required from the table
4. Correct the fault
5692452 GB
Remedy
18
Troubleshooting
Diagnosis
Fault/system characteristics
Flashing code
red
at LMO14
Cause of fault
Check
No voltage
Check fuse or connectoraBÖ in control
unit, or check electrical connections,
setting of heating system on/off switch
on control unit and mains electrical
isolator
High limit safety cut−out
activated
Press reset button on boiler control unit
Burner does not start (no fault 10× flashes
display), signal lamp
DDDDDDDDDD
illuminates
Faulty electrical
connection, wires"L1"
and "N" interchanged or
faulty burner control unit
Check electrical connection
If phases are correctly connected,
replace burner control unit
Burner does not start up (with 2× flashes
fault)
DD
Motor faulty
Replace motor
2× flashes
DD
Coupler between motor
and oil pump faulty
Replace coupler
2× flashes
DD
Oil pump seized or stiff
Clean or, if necessary, replace oil pump
8× flashes
DDDDDDDD
Oil pre−heater faulty
Replace oil pre−heater
Burner starts up, but no flame 2× flashes
is formed
DD
Ignition electrodes
incorrectly adjusted
Adjust correctly (see page12)
2× flashes
DD
Ignition electrodes damp
and contaminated
Clean ignition electrode block
2× flashes
DD
Insulation of ignition
electrode cracked
Replace ignition electrode block
2× flashes
DD
Ignition transformer faulty Replace ignition transformer
2× flashes
DD
Ignition cable faulty
Replace ignition cable
2× flashes
DD
Pump does not feed oil
Install pressure and vacuum gauges on
pump and check build−up of pressure
(see following paragraph)
2× flashes
DD
Shut−off valves closed at
filter or in oil pipe
Open valves
2× flashes
DD
Filter blocked
Clean filter (pre−filter and pump filter)
2× flashes
DD
Coupler between motor
and pump faulty
Replace coupler
2× flashes
DD
Leak in suction line or
filter cup
Tighten connections
Check oil pipes and connections for leaks
and tighten if necessary
2× flashes
DD
Oil flow and return hoses
interchanged
Connect correctly acc. to instructions on
pump
2× flashes
DD
Vacuum in suction line too Check cross−section of oil pipes. Replace
high (higher than 0.35bar) filter
Check external fuel oil valve
2× flashes
DD
External fuel oil valve
faulty
Burner does not start (no fault display), signal lamp does not
illuminate
Check and, if necessary, replace external
oil valve
5692452 GB
Pump does not feed oil
19
Troubleshooting
Diagnosis (cont.)
Fault/system characteristics
Flashing code
red
at LMO14
Cause of fault
Check
Burner starts up, but no oil
j
injected
2× flashes
DD
Solenoid coil faulty
Replace solenoid coil
2× flashes
DD
Oil pump faulty
Replace oil pump
2× flashes
DD
Nozzle blocked
Replace nozzle
4× flashes
DDDD
Oil pump solenoid valve
fails to close
Replace oil pump
4× flashes
DDDD
Flame monitor faulty
Replace flame monitor
4× flashes
DDDD
Ignition electrodes
incorrectly adjusted or
worn
Check ignition electrodes and replace, if
necessary
2× flashes
DD
Flame monitor
contaminated
Clean flame monitor
2× flashes
DD
Flame monitor receives
insufficient light
Clean sensor plate
2× flashes
DD
Flame monitor faulty
Replace flame monitor
2× flashes
DD
Burner control unit faulty
Replace burner control unit
2× flashes
DD
Carbon deposits on flame
tube or on sensor plate
Clean flame tube
7× flashes
DDDDDDD
Air in suction line
Seal line and filter
7× flashes
DDDDDDD
Nozzle faulty
Nozzle replacement
7× flashes
DDDDDDD
Burner incorrectly
adjusted
Re−instate factory pre−set values
(see page22)
7× flashes
DDDDDDD
Sensor plate
contaminated
Clean sensor plate
7× flashes
DDDDDDD
Flame monitor
contaminated
Clean flame monitor
7× flashes
DDDDDDD
Sensor plate
contaminated
Clean sensor plate
7× flashes
DDDDDDD
Nozzle contaminated or
faulty
Nozzle replacement
Fan pressure too high
Check fan pressure via test nipple on top
of fan housing (U−shaped pressure
gauge). Set air damper or blast tube
connection, so that lower value of static
burner pressure (see Standard values
for burner setting", page22) will not be
exceeded
Oil consumption too high
Correctly adjust oil pressure
(see page22)
Extraneous light during
pre−purge
phase
p
p g p
Burner starts up and flame is
formed,, but burner cuts out
after safety time expires
Flame extinguishes during
operation
p
Ignition switches on during
operation
5692452 GB
Flame pulsates
20
Troubleshooting
Diagnosis (cont.)
Fault/system characteristics
Flashing code
red
at LMO14
Cause of fault
Check
Burner sooty
Too little or too much air
Correct setting
Check and clean impeller
Check boiler room ventilation
Insufficient chimney
draught
Check flue and flue gas baffles
Nozzle faulty
Replace nozzle and install correct nozzle
(see page22)
Flame tube attachment is
missing (for 15 to 33 kW)
Install flame tube attachment
(for 15 to 33 kW)
Incorrect setting
Check setting (see page22)
Infiltrating air
Seal flue pipe at boiler adaptor
Tighten fixing screws on the combustion
chamber cover and flue gas cover
Oil consumption too high
Match oil flow to rated output of boiler
Boiler contaminated
Clean boiler and correct burner
settings
Turbulators are missing
from boiler
Install turbulators
Constant light
flicker
Interface diagnosis
Press reset button> 3 s
CO2 content too low
Flue g
gas temperature
p
too high
g 5692452 GB
Burner operates
21
Additional information
Specification
Rated output
kW
Type of burner
15
18
22
27
33
40
50
63
VEK I1
VEK I1
VEK I1
VEK I1
VEK I1
VEK I2
VEK II1
VEK II2
Type test no.
acc. to DINEN267
5G971/2001S
5G972/2001S
Voltage
V
230
Frequency
Hz
50
Motor speed
rpm
2 800
Version
single stage
Oil pump
output
Connections
Suction and return
line on oil hoses
(part of standard
delivery).
Litres/h
45
R (female thread)
e"
Standard values for burner settings
Please note:
Check whether service instructions are valid for boiler concerned (see notes on applicability, page2 and serial no. on
burner type plate).
kW
Oil burner nozzle
Make
Fluidics*1
Type
Make
Danfoss
Gph
Type
Gph
Oil pressure approx.*2
bar
Oil flow rate
kg/h
Litres/h
Air damper setting
Position of air damper
see page 7
Blast tube connection
setting
Position of setscrew
see page 7
mm
Static burner pressure*3
Position of test nipple
see page 7
Aluminium deflector
of sensor plate
No. of plugs remaining
in deflector
mbar
*1The
15
18
22
27
33
40
50
63
60ºSF/
60ºHF
0.40 0.45/0.50
60ºHF
45ºSF
45ºSF
60ºS
80ºH
0.60
/
0.75
60ºSR
0.85
1.00
1.25
1.50
60ºSF
9.0
9.0
9.0
8.5
9.0
10.0
11.5
10.5
1.40
1.65
1.68
1.98
2.06
2.42
2.53
2.97
3.09
3.63
3.74
4.40
4.68
5.50
5.89
6.93
7.5
8.0
8.5
10.0
13.5
16.5
17.0
25.0
3.0
3.0
5.0
8.0
10.0
8.0
10.0
14.0
3.23.6
3.23.6
3.23.6
3.03.3
2.53.0
2.53.0
3.23.7
2.53.0
0
0
2
0
0
0
0
0
requirements laid down for the certificate of environmental excellence were verified only with the nozzles shown.
to nozzle tolerances and varying oil characteristics, the oil pressure may vary from that indicated by the values shown.
*3To check the burner settings.
*2Due
22
5692452 GB
Rated output
Additional information
Component summary
K Solenoid valve
M Blast tube connection setscrew
M Oil supply line
N Ignition transformer
O Ignition cable
P Ignition electrode
R Flame tube
S Flame tube attachment
T Sensor plate
U Oil burner nozzle
V Flame monitor
W Blast tube connection with oil
pre−heater
X Impeller
Y Burner housing
5692452 GB
A Air regulating valve
B Oil burner control unit
C Reset button with extension
D Connection panel
E Return line
F Suction line
G Fan motor
H Oil pump
23/24
Additional information
Wiring diagram
Legend
A’
A’
B
C
D
Control unit
components
Start of oil pre−heat time
Start−up
Timing of flame
being established
Operating position
Controlled switch−off
fA
Burner plug on the
control unit
F 1.1
Fuse in the control unit
F6
High limit safety cut−out
F7
Thermostat
Mains electrical switch
S1
S2
Test button
Burner relay
K1
1 qW Plug−in terminals on the
oil burner control unit
Flame monitor
Control program LOA X4 . . . .
Solenoid valve t0
Ignition t1
transformer t2
Pre−flush time
Safety time
up to 2min
approx.
Control program LMO 14 .113
t0
Oil pre−heat time 2)
13s
t1
Pre−flush time
up to 2min
approx.
16s
max.
10s
t2
Safety time
max.
10s
approx.
13s
t3
Pre−ignition time
approx.
15s
Burner motor
t3n Post−ignition time approx.
if the flame is established
15s
t3n Post−ignition time approx.
if the flame is established
3s
Oil pre−heater
2) Depending on the temperature of the
fuel oil supplied
t3
Oil burner control unit
Oil pre−heat time 2)
Pre−ignition time
Colour coding conforming to
DIN/IEC757
BK
BN
black
brown
BU
blue
Function sequence on start−up
1) Connection
Ext. fault
lamp
25/26
Op. lamp
plug−in panel
Oil pre−heater
15 to 40 kW
Solenoid valve for
ext. connection via
separate adaptor
Burner
motor
Flame
monitor
Ignition
transformer
Operating lamp
or hours run counter
ext. (control unit)
Solenoid valve
on the oil pump
Please note:
This wiring diagram only applies in
conjunction with Viessmann
products.
5692452 GB
On−site
supply
of assembly modules and
accessories via system plug−in
connectorfA (e.g. KNL, extension lead,
etc.)
2) Connection of external safety
equipment via system plug−in
connector aBÖ
3) Connection of external control
off−switch via system plug−in
connector aBÖ
4) Connection for external burner ON
Additional information
Parts list
When ordering spare parts:
Quote the type and serial no. (see
type plate) and the item no. of the
required part (as per parts list).
You can obtain common parts from
your local supplier.
Parts
001 Flame tube
002 Sealing plate ∅182×30×3
004 Burner housing
005 Profile stud
006 Fan motor
007 Oil pipe
009 Burner hood
010 Insulation mat with adhesive
011 Suppressor extension
012 Oil burner control unit
013 Electronic ignition
014 Burner flange
018 Blast tube connection setting
024 Air damper
028 Connection panel
burner control unit
049 Burner hood latches
080 Small parts comprising:
80a Locking spigot Allen screw
head 4mm
80b Plug spigot compression spring
80c Plug spigot lockwasher
80d Cheese−head screwM5×10
80e Cheese−head screwM5×45
Thread length 30mm
80f Cheese−head screwM6×20
80g Cable clamp
80h Cheese−head screwM6×30
80i Grub screw M6×10
80k Machine screwAM4×10H
80l Spring washerA5
80mO−ring 192.5 VIOR
80o Straight connector
80p GasketA10×14×1.5
80r Cheese−head screwM5×12
Wear parts
008 Plug−in coupler
017 Flame tube attachment
15 33kW
A Type plate
005
049
017
80h
010
001
002
80i
014
A
004
018
009
013
80k
024
80e
80r
80f
80e
006
028
008
007
80a
80b
80c
80g
011
5692452 GB
012
27/28
Additional information
Parts list (cont.)
Parts
019 Impeller
020 Oil hose − flow
021 Oil hose − return
027 Sensor plate
030 Blast tube connection with oil
pre−heater
032 O−ring 54×3
033 Solenoid valve coil for Suntec
oil pump
034 Solenoid valve nut for
Suntec oil pump
038 Suntec oil pump
039 Solenoid valve core for Suntec
oil pump
040 Danfoss oil pump
041 Solenoid valve coil for Danfoss
oil pump
042 Ignition cables (set)
043 Flame monitor QRB
080 Small parts comprising:
80a Locking spigot Allen screw
head 4mm
80b Plug spigot compression spring
80c Plug spigot lockwasher
80d Cheese−head screwM5×10
80e Cheese−head screwM5×45
Thread length 30mm
80f Cheese−head screwM6×20
80g Cable clamp
80h Cheese−head screwM6×30
80i Grub screw M6×10
80k Machine screwAM4×10H
80l Spring washerA5
80mO−ring 192.5 VIOR
80o Straight connector
80p GasketA10×14×1.5
80r Cheese−head screw M5×12
80d
80l
041
042
044
047
030
045
80m
80o
032
80p
040
027
020
043
021
80d
034
019
033
039
Parts (not shown)
071 Installation instructions
072 Service instructions
079 Burner pack
038
5692452 GB
Wear parts
044 Ignition electrode block
045 Nozzle
046 Spare parts set for Suntec oil
pump
047 Cartridge filter for Danfoss oil
pump
046
29/30
bar
bar
read as
after maintenance
% by vol
set
%
set
mm
mm
read as
set
Air damper
setting
mm
mm
hPa (1hPa=1 mbar)
Blast tube con− read as
nection setting set
Draught (at the read as
boiler end)
set
hPa (1hPa=1 mbar)
%
read as
Flue gas loss
ºC
Flue gas tempe− read as
rature (gross)
set
ºC
% by vol
read as
Oxygen
content O2
% by vol
set
% by vol
bar
set
read as
bar
read as
Carbon dioxide read as
content CO2
set
Soot indicator
Vacuum
Oil pressure
5692452 GB
Maint./Service
Date:
By:
Initial start−up
Date:
By:
By:
Maint./Service
Date:
By:
Maint./Service
Date:
By:
Maint./Service
Date:
By:
Maint./Service
Date:
Additional information
Commissioning/service report
31
Additional information
Index
B
Burner, cleaning,9
Burner control unit,15
Burner, installation on burner
housing, 12
Burner settings, standard values,22
Burner values, checking,8
C
Commissioning/service report,31
Component summary,23
D
Diagnosis,18,19
E
Electrical connections, checking,9
I
Ignition electrodes, checking,12
Ignition electrodes, setting,12
Impeller fixings, checking,10
L
Leaks, checking for,14
N
Nozzle replacement,11
O
Oil connections,14
Oil lines,14
Oil pressure adjustment,6
Oil pump filter, cleaning and
replacement,13
S
Safety instructions,2
Specification,22
System start−up,5,14
System shut−down,8
T
Troubleshooting,18
V
Checking the vacuum,6
W
Wiring diagram,25
Printed on environmentally friendly,
chlorine−free bleached paper.
A
Air volume readjustment,6
Applicability,2
P
Parts list,27
Pre−filter element replacement,13
Procedure summary,4,18
Viessmann Werke GmbH & Co
D35107 Allendorf
Tel:
(0 64 52) 700
Fax:
(0 64 52) 7027 80
www.viessmann.de
Viessmann Limited
Hortonwood 30, Telford
Shropshire, TF1 7YP, GB
Tel:
(01952) 670261
Fax:
(01952) 670103
32
5692452 GBSubject to technical modifications.
F
Flame monitor, checking,8
Flame tube fixings, checking,10