Online UPS 1:1 phase
UM700
UM Series
UM700-RM
0.7KVA - 700VA
UM1000
UM1000-RM
Voltage Range
700VA - 3000VA
1:1 Phase
Small network, servers and other IT equipment.
UM3000
UM3000-RM
3KVA / 3000VA
70 - 138 VAC
45 - 65 Hz
Phase
Single phase
Power Factor
0.97
Voltage Range
110 / 115 / 120 VAC ± 2%
Frequency Range
50Hz / 60Hz (auto-sensing)
THD (linear load)
<3%
THD (non-linear load)
<6%
Overload Capability
>100% 30S to bypass; >150% 300mS to bypass
Crest Factor
3:1 (max)
Short Circuit Protection
5 cycles turn off inverter, no transfer to bypass, provide alarm (AC mode)
5 cycles turn off inverter, provide alarm (battery mode)
input fuse blown or breaker action (bypass mode)
Pure sine wave
Between AC mode and battery mode: 0mS
Transfer Time
Between AC mode and Bypass mode: 4mS (typical value 2.5mS)
>83%
Efficency
>85%
12V sealed lead acid maintenance free
Model
36VDC
DC Voltage
1. High frequency and double conversion online technology
2. Fully digitized microprocessor control
3. Wide input voltage range
4. LCD display
5. UPS start up without battery
6. Cold start
7. Advanced battery management
8. Automatic battery charging in UPS off mode
9. Lightning and surge protection
10. Short circuit and overload protection
11. Fan speed auto control when loads varies
12. Network/fax/modem surge protection
13. Optional extension battery pack
14. Battery voltage display
15. Load capacity display
16. EMI/RFI noise filter
17. Smart RS232 communication with monitoring software
18. Optional SNMP card slot
19. EPO function (optional)
20. Input L and N reversed alarm function
UM2000-RM
2KVA / 2000VA
Frequency Range
Waveform
1. LCD
2. ON/OFF Button
3. Self-test/Silence Button
4. Scroll Button
5. Normal
6. Alarm
7. Abnormal
UM2000
1KVA / 1000VA
96VDC
Battery
3x12V/9AH
3x12V/7AH
8x12V/7AH
8x12V/7AH
Backup Time (half load)
22min
12min
19min
16min
Backup Time (full load)
10min
5min
8min
5min
Charge Current (standard unit)
1A (minimum)
1A (minimum)
1A (minimum)
1A (minimum)
Charge Current (long time unit)
7A
7A
7A
7A
Recharge Time
80% capacity after 4 hrs charging
RS232 ; SNMP (optional)
1. Input voltage/frequency, battery voltage, output voltage/frequency, load watt/VA and percent,
inverter temperature.
2. Operation mode such as “on line”, “on batt” or “on bypass”.
1. Green LED for normal operation.
2. Yellow LED for warning condition.
3. Red LED for abnormal operation.
<45dB
Rear Panel
SNMP slot
Rs232
Battery socket
Fan
Rj45
www.upsonic.net
Tower
From 0 to 40 ºC
Humidity
0% - 95% (non-condensing)
<1500m
Altitude
-25 to
Storge Temperature
Output socket
Rack mounted
Temperature
Input socket
Input breaker
55 ºC
Standard Unit Net/Gross Weight
14.7/16.7Kg
14.7/16.7Kg
14/16Kg
14/16Kg
33/35Kg
34/36Kg
34/36Kg
35/37Kg
Long Time Unit Net/Gross Weight
8.2/9.7Kg
8.2/10.7Kg
7.5/9Kg
8/10Kg
14/16Kg
19/21Kg
15/17Kg
20/22Kg
Dimension (WxDxH)mm
144x419x215 483x400x89 144x419x215 483x400x89 191x478x339 483x520x89 191x478x339 483x520x89
Packing (WxDxH)mm
258x524x334 587x550x254 258x524x334 587x550x254 332x603x482 592x665x292 332x603x482 592x665x292
1. Tower and rack mount.
2. Advanced battery managment technology, comprehensive protection, local and remote monitoring.
3. Provide high security to the load. Wide input voltage range 70 ~ 138VAC, without discharge batteries.
4. High MTBF (Mean Time Between Failure) >100.000 hours.

Similar documents

Silencio® range

Silencio® range UM650 UM650++UM601 UM601 UM650 UM650++UM601 UM601 UM700 UM700++UM655 UM655 UM700 UM700++UM602 UM602 UM650 UM650++UM601 UM601 UM602 UM602++UM602 UM602 UM700 UM700++UM602 UM602 UM700 UM700++UM655 UM655

More information