ACCESSORY KIT INSTALLATION MANUAL
HURRICANE KIT (S1-1HK0601) (Clip A)
FOR AC MODELS: GCGD, YCJD (1PH & 3PH), TCJD (1PH & 3PH), RAC13J, CCGD, YCJF, TCJF, RAC14J, YCD, TC3B,
RAC13L, QC3B, GAW14L, YCE, TC4B, RAC14L, QC4B, YCS, TW4B, RAW14L, QW4B, YFD, TF3B, RAC13F, YFE, TF4B,
RAC14F, YCG, CC7, TC7, RAC17L SERIES
FOR HP MODELS: GHGD, YHJD (1PH & 3PH), THJD (1PH & 3PH), RHP13J, YHJR, THJR, RHP13R, YHJF, THJF, RHP14J,
CHJD, YHE, TH4B, RHP14L, QH4B, THE, YHM, CH16B, TH16B SERIES
GENERAL INFORMATION
CONTENTS
The purpose of this hurricane accessory kit is to keep the unit
intact and secured to the concrete pad or equivalent approved
support in the event of hurricane force winds.
This kit contains twelve brackets and twenty-four sheet metal
screws.
Screws provided in this kit are used to connect brackets to the
outdoor unit. Anchors to connect brackets to concrete pad or
equivalent approved support to be field supplied. Refer to Table
1 on Page 3 for approved anchor types.
TOOLS REQUIRED
•
•
•
•
•
•
•
•
Hammer Drill
1/4” Masonry Drill Bit
Hammer
Socket Set
Cordless Drill
1/8” Twist Drill bit
5/16” Hex Head Bit
Marker or Pencil
INSTALLATION
Using the attached instructions as a guide, install the appropriate number of clips per the requirements of the site.
!
CAUTION
Use caution when drilling pilot holes through unit. DO NOT
drill into outdoor coil.
7,('2:1&/,3$
176
Johnson Controls Unitary Products
$
035-24608-001-A-0316
9?3URMHFWV?2'&RQGHQVLQJ8QLW7HVW3URWRFRO?:3?12$6XEPLWWDO?BN2'&RQGHQVLQJ8QLW&/,(17&23<GZJ
LQWHUQ
(4
83/,)7
36)
83/,)7
36)
176
7,('2:1&/,3%
176
7,('2:1&/,3$
(4
36)
/$7(5$/
36)
/$7(5$/
0$;,080'(6,*1:,1'35(6685(6
*5281'
02817
522)
02817
$33529(''(6,*1&5,7(5,$
%<$0(5,&$17(67/$%2)
6287+)/25,'$
7(675(32576
7+,6(1*,1((5(''5$:,1*,6,17(1'('72
&(57,)<7+(&$%,1(75<$1'7,('2:172+267
$77$&+0(176)257+(81,702'(/6'(6&5,%('
+(5(,1)25:,1'/2$',1*21/<7+,6
&(57,),&$7,21'2(6127,1&/8'(,03$&7
5(6,67$1&(
6&23(
>/W
(;$03/(6+2:16((6+((76
)2563(&,),&02'(/6
,620(75,&9,(:
2'&21'(16,1*81,7
7+(81,702'(/6/,67('$%29(:(5(7(67('$1''(6,*1('$6
:2567&$6(&21),*85$7,216$'',7,21$/81,702'(/60$<%(
&(57,),('%<7+,6$33529$/$6/21*$67+(<+$9(,'(17,&$/
&216758&7,21$1'&20321(176$67+26(/,67('$%29($1'
$5(2)(48$/25/(66(56,=(/(1*7+:,'7++(,*+7
‚',0(16,2166+2:10($685(')520287(5026732,1762)
81,7,1&/8',1*6&5(:+($'6
DK>η
&Ϭϰϴϭϰ
z:&ϲϬ^ϰϭ^Ϯ
Zϭϰ:ϲϬϰ^Ϯϭ
z&ϲϬϮϭ^
Zϭϰ&ϲϬϮϭ^
z,ϲϬϮϭ^
Z,Wϭϰ>ϲϬϮϭ^
WWZKshE/ddzW^Ύ
/DE^/KE^Ώ
^,d
Ϯͬϴ
ϰϮ͘ϮϱΗdžϯϰ͘ϬϬΗdžϰϬ͘ϬϬΗ
ϯͬϴ
ϯϰ͘ϬϬΗdžϯϰ͘ϬϬΗdžϰϬ͘ϮϱΗ
ϰͬϴ
ϯϰ͘ϬϬΗdžϯϰ͘ϬϬΗdžϰϬ͘ϮϱΗ
ϱͬϴ
ϯϴ͘ϬϬΗdžϯϰ͘ϮϱΗdžϯϵ͘ϱϬΗ
ϲͬϴ
ϯϴ͘ϬϬΗdžϯϰ͘ϮϱΗdžϯϵ͘ϱϬΗ
ϳͬϴ
ϯϴ͘ϬϬΗdžϯϰ͘ϮϱΗdžϰϮ͘ϳϱΗ
ϴͬϴ
ϯϴ͘ϬϬΗdžϯϰ͘ϮϱΗdžϰϮ͘ϳϱΗ
2'&21'(16,1*81,76
$7*5$'($1'522)723$33/,&$7,216
2
SP
<25.,17(51$7,21$/&253
7+(6(6<67(06+$9(%((1'(6,*1('$1'6+$//%(
)$%5,&$7(',1$&&25'$1&(:,7+7+(5(48,5(0(1762)
7+()/25,'$%8,/',1*&2'(),)7+(',7,21
$6&(7+(6(6<67(060$<%(86(':,7+,1$1'
2876,'(7+(+,*+9(/2&,7<+855,&$1(=21(7+(6(
'(6,*16$5(127,17(1'('72&(57,)<,03$&7
5(6,67$1&(2)7+(0(&+$1,&$/81,7&$%,1(75<7(676
:(5(3(5)250(',1$&&25'$1&(:,7+7$6$1'
$670(
12,1&5($6(,1$//2:$%/(675(66+$6%((1
86(',17+('(6,*12)7+,66<67(0
'(6,*1&(57,),&$7,212)7+(81,7&$%,1(75<,6
$33529('7+528*+7(675(3257 %<
$0(5,&$17(67/$%2)6287+)/25,'$
$//',0(16,216$1'7+(0,1,080:(,*+762)
0(&+$1,&$/81,766+$//&21)25072/,0,7$7,216
67$7('+(5(,1$//0(&+$1,&$/63(&,),&$7,216&/($5
63$&(7211$*((7&6+$//%($63(50$18)$&785(5
5(&200(1'$7,216$1'$5(7+((;35(66
5(63216,%,/,7<2)7+(&2175$&725
$//6+((70(7$/6&5(:686('72)$67(1%5$&.(7672
0(&+$1,&$/81,766+$//%(0,17+5($'63(5
,1&+$670)67$,1/(6667((/25(48,9$/(17
21/<%2/7686('72)$67(1$/80,180$1*/(672
6833257,1*)5$0(%<27+(566+$//%($670)
67$,1/(6667((/25(48,9$/(17$1'6+$//87,/,=(6$(
*5$'(:$6+(5618763529,'(3,7&+(60,1,080
3$677+(7+5($'3/$1()256+((70(7$/6&5(:6$//
)$67(1(566+$//+$9($335235,$7(&25526,21
3527(&7,217235(9(17(/(&752/<6,6$//)$67(1(5
&211(&7,21672$/80,1806+$//3529,'([',$0(7(5
('*(',67$1&(
7+(&2175$&725,65(63216,%/(72,168/$7($//
0(0%(56)520',66,0,/$50$7(5,$/67235(9(17
(/(&752/<6,6
(/(&75,&$/*5281':+(15(48,5('72%('(6,*1('
,167$//('%<27+(56
7+($'(48$&<2)$1<(;,67,1*6758&785(72
:,7+67$1'683(5,0326('/2$'66+$//%(9(5,),('%<
7+(216,7('(6,*1352)(66,21$/$1',6127,1&/8'('
,17+,6&(57,),&$7,21(;&(37$6(;35(66/<3529,'('
+(5(,112$'',7,21$/&(57,),&$7,21625
$)),50$7,216$5(,17(1'('
7+(6<67(0'(7$,/('+(5(,1,6*(1(5,&$1''2(6127
3529,'(,1)250$7,21)25$63(&,),&6,7()256,7(
&21',7,216',))(5(17)5207+(&21',7,216'(7$,/('
+(5(,1$/,&(16('(1*,1((5255(*,67(5('
$5&+,7(&76+$//35(3$5(6,7(63(&,),&'2&80(176
)2586(,1&21-81&7,21:,7+7+,6'2&80(17
:$7(57,*+71(662)(;,67,1*+26768%675$7(6+$//
%(7+()8//5(63216,%,/,7<2)7+(,167$//,1*
&2175$&725&2175$&7256+$//(1685(7+$7$1<
5(029('25$/7(5(':$7(53522),1*0(0%5$1(,6
5(6725('$)7(5)$%5,&$7,21$1',167$//$7,212)
6758&785(352326('+(5(,17+,6(1*,1((56+$//127
%(5(63216,%/()25$1<:$7(53522),1*25/($.$*(
,668(6:+,&+0$<2&&85$6:$7(57,*+71(666+$//
%(7+()8//5(63216,%,/,7<2)7+(,167$//,1*
&2175$&725
*(1(5$/127(6
$//2:$%/(/2$'9$/8(6$5('(5,9(')5207+(7(675(3257
326,7,9($1'1(*$7,9('(6,*135(6685(6&$/&8/$7(')2586(
:,7+7+(6(81,766+$//%('(7(50,1('%<27+(5621$
-2%63(&,),&%$6,6,1$&&25'$1&(:,7+7+(*29(51,1*&2'(
6,7(63(&,),&/2$'5(48,5(0(176)25:,1'/2$'6+$//%(
'(7(50,1(',1$&&25'$1&(:,7+$6&($1'7+()/25,'$
%8,/',1*&2'(),)7+(',7,21$6$33/,&$%/(%<6(3$5$7(
(1*,1((5,1*&(57,),&$7,21$1'6+$//%(/(667+$125(48$/72
7+(326,7,9(251(*$7,9('(6,*135(6685(&$3$&,7<9$/8(6
/,67('+(5(,1)25$1<$66(0%/<$66+2:1
&23<5,*+7(1*,1((5,1*(;35(66 ‹
035-24608-001-A-0316
Johnson Controls Unitary Products
V:\Projects\15-2783 OD Condensing Unit Test Protocol\WP\NOA Submittal\15-2783_k OD Condensing Unit (CLIENT COPY).dwg
intern1
04/04/2016 - 3:10pm
BACK
RIGHT
CZF04814C PLAN VIEW
LEFT
34.0"
FRONT
PLAN
ELEVATION
CZF04814C BACK VIEW
34.0"
ELEVATION
CZF04814C FRONT VIEW
34.0"
STEEL (15 GA
MIN)
ALUMINUM
(1/8" 6063-T6
MIN)
WOOD (G=0.55
MIN)
1/4" SAE GR 5 THRU-BOLT W/
WASHERS
1/4" SAE GR 5 THRU-BOLT W/
WASHERS
3/8" LAG SCREW W/ 1 3/4" MIN
THREAD PENETRATION & 1" MIN
EDGE DIST
1/4" POWERS WEGDE BOLT W/ 2"
MIN EMBED & 3" MIN EDGE DIST
OR
CONCRETE (3 KSI 1/4" ITW TAPCON W/ 1 3 4" EMBED
1
& 2 2" MIN EDGE DIST
MIN)
OR
1/4" ELCO ULTRACON W/ 1 3 4"
EMBED & 21 2" MIN EDGE DIST
TABLE 1: UNIT ANCHORAGE TO HOST (ALL UNITS)
SUBSTRATE
ANCHOR TYPE
ELEVATION
CZF04814C LEFT VIEW
42.3"
ELEVATION
CZF04814C RIGHT VIEW
42.3"
40.0"
OD CONDENSING UNITS
CZF04814C MODEL
LEFT
38.7"
4.0"
FRONT
34.0"
BACK
29.3"
5.0"
RIGHT
4.1"
3.5"
4.0"
BACK
28.0"
34.0"
5.0"
4.1"
NOT APPROVED FOR
ATTACHMENT TO WOOD
RIGHT
UNIT BASE
CLIP TYPE B
SEE TABLE 1 FOR
HOST ANCHORAGE
OPTIONS
PROVIDE (1) #10-16
#10-1 x 3 8" SAE
GR. 5 SMS W/ 5 16" SLOTTED HEX
HEAD AND 0.40"Ø x 0.025"
THICK INTEGRATED LOCK
WASHER
STEEL
CORNERPOST
PLAN
AS NEEDED: MARK AND DRILL
AD
ADDITIONAL
HOLES USING A
1
8 " DRILL INTO THE CORNER
POST
POS BEING CAREFUL NOT TO
DAMAGE THE COIL.
PLAN
CZF04814C TIEDOWN LAYOUT - ROOF INSTALL
LEFT
CLIP QTY: 8
4.3"
29.3"
FRONT
CZF04814C TIEDOWN LAYOUT - GROUND INSTALL
CLIP QTY: 4
42.3"
YORK INTERNATIONAL CORP.
42.3"
37.5"
40.0"
40.0"
42.3"
37.0"
Johnson Controls Unitary Products
40.0"
FOR SMALLER MODELS:
SMALLER MODEL BASE PROFILES SHALL
HAVE THE SAME CLIP PATTERN AS SHOWN
W/ THE SAME CLIP COUNT PER SIDE. THE
FIRST CLIP FROM EACH CORNER SHALL BE
AT THE SAME DISTANCES SHOWN [FOR
EXAMPLE: THE CLIP CIRCLED BELOW WILL
ALWAYS BE AT 4.1" FROM THE FRONT
RIGHT CORNER OF ANY SMALLER UNIT
WITH IN BETWEEN CLIPS (IF ANY) SPACED
AT SCALED DOWN DISTANCES IN
RELATION TO UNIT SHOWN]
2
COPYRIGHT ENGINEERING EXPRESS
©
035-24608-001-A-0316
3
V:\Projects\15-2783 OD Condensing Unit Test Protocol\WP\NOA Submittal\15-2783_k OD Condensing Unit (CLIENT COPY).dwg
intern1
04/04/2016 - 3:11pm
BACK
34.0"
FRONT
RIGHT
PLAN
ELEVATION
YCJF60S41S2 LEFT VIEW
34.0"
ELEVATION
YCJF60S41S2 RIGHT VIEW
40.3"
38.4"
YCJF60S41S2 PLAN VIEW
LEFT
ELEVATION
YCJF60S41S2 BACK VIEW
34.0"
ELEVATION
YCJF60S41S2 FRONT VIEW
3.0"
FRONT
BACK
34.0"
21.4"
2.6"
12.2"
RIGHT
2.5"
34.0"
BACK
2.8"
11.8"
20.6"
RIGHT
CLIP TYPE A
SEE TABLE 1 FO
FOR
HOST ANCHOR
ANCHORAGE
OPTIONS
#10-16 x 3 8" SAE
PROVIDE (2) #
GR. 5 SMS W/ 5 16" SLOTTED HEX
0.40"Ø x 0.025"
HEAD AND 0.4
INTEGRATED LOCK
THICK INTEGR
WASHER
NTS
ELEVATION
YCJF60S41S2 TIEDOWN DIRECTIVE
AS NEEDED: MARK AND
ND DRILL
ADDITIONAL HOLES USING A
1
E BASE
8" DRILL INTO THE
FLANGE BEING CAREFUL
FUL NOT
TO DAMAGE THE COIL.
STEEL UNIT
BASE
PLAN
YCJF60S41S2 TIEDOWN LAYOUT - ROOF INSTALL
LEFT
CLIP QTY: 12
15.3"
2.6"
FRONT
30.1"
PLAN
YCJF60S41S2 TIEDOWN LAYOUT - GROUND INSTALL
LEFT
CLIP QTY: 6
34.0"
34.0"
30.1"
34.0"
34.0"
30.6"
17.6"
40.3"
38.4"
40.3"
38.4"
30.7"
12.2"
OD CONDENSING UNITS
YCJF60S41S2 MODEL
30.7"
YORK INTERNATIONAL CORP.
34.0"
21.5"
4
40.3"
38.4"
FOR SMALLER MODELS:
SMALLER MODEL BASE PROFILES SHALL
HAVE THE SAME CLIP PATTERN AS SHOWN
W/ THE SAME CLIP COUNT PER SIDE. THE
FIRST CLIP FROM EACH CORNER SHALL BE
AT THE SAME DISTANCES SHOWN [FOR
EXAMPLE: THE CLIP CIRCLED BELOW WILL
ALWAYS BE AT 2.6" FROM THE FRONT
LEFT CORNER OF ANY SMALLER UNIT
WITH IN BETWEEN CLIPS (IF ANY) SPACED
AT SCALED DOWN DISTANCES IN
RELATION TO UNIT SHOWN]
3
COPYRIGHT ENGINEERING EXPRESS
©
035-24608-001-A-0316
Johnson Controls Unitary Products
V:\Projects\15-2783 OD Condensing Unit Test Protocol\WP\NOA Submittal\15-2783_k OD Condensing Unit (CLIENT COPY).dwg
intern1
04/04/2016 - 3:11pm
BACK
RIGHT
PLAN
ELEVATION
RAC14J604S21 LEFT VIEW
LOUVERS CONTINUE
34.0"
ELEVATION
RAC14J604S21 RIGHT VIEW
40.3"
RAC14J604S21 PLAN VIEW
LEFT
FRONT
34.0"
ELEVATION
RAC14J604S21 BACK VIEW
LOUVERS CONTINUE
34.0"
SOME LOUVERS NOT SHOWN FOR
CLARITY, THIS SHEET
ELEVATION
RAC14J604S21 FRONT VIEW
LOUVERS CONTINUE
3.6"
FRONT
34.0"
BACK
23.0"
3.4"
11.2"
RIGHT
PLAN
3.6"
BACK
34.0"
3.8"
13.2"
23.1"
RIGHT
CLIP TYPE A
SEE TABLE 1 FOR
F
HOST ANCHORAGE
ANCHOR
OPTIONS
PROVIDE (2) #10-16
x 3 8" SAE
#
GR. 5 SMS W/ 516 " SLOTTED HEX
0.40"Ø x 0.025"
HEAD AND 0.4
INTEGRATED LOCK
THICK INTEGR
WASHER
NTS
ELEVATION
RAC14J604S21 TIEDOWN DIRECTIVE
AS NEEDED: MARK AND
D DRILL
ADDITIONAL HOLES USING A
1
8" DRILL INTO THE BASE
FLANGE BEING CAREFUL
UL NOT
TO DAMAGE THE COIL.
STEEL UNIT
BASE
PLAN
RAC14J604S21 TIEDOWN LAYOUT - ROOF INSTALL
LEFT
CLIP QTY: 12
30.5"
15.9"
3.4"
34.0"
FRONT
RAC14J604S21 TIEDOWN LAYOUT - GROUND INSTALL
CLIP QTY: 6
LEFT
34.0"
LOUVERS CONTINUE
30.8"
30.8"
34.0"
18.3"
40.3"
40.3"
30.8"
11.2"
34.0"
30.8"
OD CONDENSING UNITS
RAC14J604S21 MODEL
YORK INTERNATIONAL CORP.
34.0"
21.1"
Johnson Controls Unitary Products
40.3"
FOR SMALLER MODELS:
SMALLER MODEL BASE PROFILES SHALL
HAVE THE SAME CLIP PATTERN AS SHOWN
W/ THE SAME CLIP COUNT PER SIDE. THE
FIRST CLIP FROM EACH CORNER SHALL BE
AT THE SAME DISTANCES SHOWN [FOR
EXAMPLE: THE CLIP CIRCLED BELOW WILL
ALWAYS BE AT 3.4" FROM THE FRONT
LEFT CORNER OF ANY SMALLER UNIT
WITH IN BETWEEN CLIPS (IF ANY) SPACED
AT SCALED DOWN DISTANCES IN
RELATION TO UNIT SHOWN]
4
COPYRIGHT ENGINEERING EXPRESS
©
035-24608-001-A-0316
5
V:\Projects\15-2783 OD Condensing Unit Test Protocol\WP\NOA Submittal\15-2783_k OD Condensing Unit (CLIENT COPY).dwg
intern1
04/04/2016 - 3:11pm
BACK
38.0"
39.5
RIGHT
PLAN
ELEVATION
YFE60B21S LEFT VIEW
38.0"
ELEVATION
YFE60B21S RIGHT VIEW
YFE60B21S PLAN VIEW
LEFT
34.3"
FRONT
ELEVATION
YFE60B21S BACK VIEW
34.3"
ELEVATION
YFE60B21S FRONT VIEW
3.3"
FRONT
BACK
34.3"
20.8"
2.9"
RIGHT
3.3"
3.1"
BACK
34.3"
20.8"
13.0"
RIGHT
CLIP TYPE A
NTS
PLAN
SEE TABLE 1 FOR HOST
ANCHORAGE OPTIONS
PROVIDE (2) #10-16 x 3 8" SAE
GR. 5 SMS W/ 5 16" SLOTTED
SL
HEX
HEAD AND 0.40"Ø x 0.025"
0
THICK INTEGRATED LOCK
L
WASHER
ELEVATION
YFE60B21S TIEDOWN DIRECTIVE
AS NEEDED: MARK
ARK AND DRILL
OLES USING A
ADDITIONAL HOLES
1
TO THE BASE
8" DRILL INTO
FLANGE BEING CAREFUL NOT
TO DAMAGE
E THE COIL.
STEEL UNIT
BASE
PLAN
YFE60B21S TIEDOWN LAYOUT - ROOF INSTALL
LEFT
CLIP QTY: 12
30.5"
18.0"
2.9"
34.3"
FRONT
YFE60B21S TIEDOWN LAYOUT - GROUND INSTALL
CLIP QTY: 6
LEFT
38.0"
38.0"
38.0"
34.8"
34.8"
34.3"
18.6"
OD CONDENSING UNITS
YFE60B21S MODEL
13.0"
13.0"
YORK INTERNATIONAL CORP.
33.9"
39.5
39.5
33.9"
25.0"
6
39.5
FOR SMALLER MODELS:
SMALLER MODEL BASE PROFILES SHALL
HAVE THE SAME CLIP PATTERN AS SHOWN
W/ THE SAME CLIP COUNT PER SIDE. THE
FIRST CLIP FROM EACH CORNER SHALL BE
AT THE SAME DISTANCES SHOWN [FOR
EXAMPLE: THE CLIP CIRCLED BELOW WILL
ALWAYS BE AT 2.9" FROM THE FRONT
LEFT CORNER OF ANY SMALLER UNIT
WITH IN BETWEEN CLIPS (IF ANY) SPACED
AT SCALED DOWN DISTANCES IN
RELATION TO UNIT SHOWN]
5
COPYRIGHT ENGINEERING EXPRESS
©
035-24608-001-A-0316
Johnson Controls Unitary Products
V:\Projects\15-2783 OD Condensing Unit Test Protocol\WP\NOA Submittal\15-2783_k OD Condensing Unit (CLIENT COPY).dwg
intern1
04/04/2016 - 3:11pm
BACK
LOUVERS CONTINUE
RIGHT
PLAN
ELEVATION
RAC14F604B21S LEFT VIEW
LOUVERS CONTINUE
38.0"
ELEVATION
RAC14F604B21S RIGHT VIEW
RAC14F604B21S PLAN VIEW
LEFT
34.3"
FRONT
ELEVATION
RAC14F604B21S BACK VIEW
LOUVERS CONTINUE
34.3"
SOME LOUVERS NOT SHOWN FOR
CLARITY, THIS SHEET
ELEVATION
RAC14F604B21S FRONT VIEW
LOUVERS CONTINUE
38.0"
3.4"
FRONT
34.3"
BACK
20.8"
2.9"
13.0"
RIGHT
3.4"
3.8"
13.2"
20.8"
34.3"
BACK
RIGHT
PLAN
CLIP TYPE A
SEE TABLE 1 FOR
F
HOST ANCHOR
ANCHORAGE
OPTIONS
x 3 8" SAE
PROVIDE (2) #10-16
#
GR. 5 SMS W/ 516 " SLOTTED HEX
0.40"Ø x 0.025"
HEAD AND 0.4
INTEGRATED LOCK
THICK INTEGR
WASHER
NTS
ELEVATION
RAC14F604B21S TIEDOWN DIRECTIVE
AS NEEDED: MARK AND
ND DRILL
ADDITIONAL HOLES USING A
1
8" DRILL INTO THE BASE
FLANGE BEING CAREFUL
FUL NOT
TO DAMAGE THE COIL.
STEEL UNIT
BASE
PLAN
RAC14F604B21S TIEDOWN LAYOUT - ROOF INSTALL
LEFT
CLIP QTY: 12
2.9"
18.0"
34.3"
30.5"
FRONT
RAC14F604B21S TIEDOWN LAYOUT - GROUND INSTALL
LEFT
CLIP QTY: 6
38.0"
34.3"
34.9"
34.9"
OD CONDENSING UNITS
RAC14F604B21S MODEL
18.8"
YORK INTERNATIONAL CORP.
13.0"
39.5"
39.5"
38.0"
33.9"
39.5"
39.5"
33.9"
21.1"
Johnson Controls Unitary Products
38.0"
FOR SMALLER MODELS:
SMALLER MODEL BASE PROFILES SHALL
HAVE THE SAME CLIP PATTERN AS SHOWN
W/ THE SAME CLIP COUNT PER SIDE. THE
FIRST CLIP FROM EACH CORNER SHALL BE
AT THE SAME DISTANCES SHOWN [FOR
EXAMPLE: THE CLIP CIRCLED BELOW WILL
ALWAYS BE AT 2.9" FROM THE FRONT
LEFT CORNER OF ANY SMALLER UNIT
WITH IN BETWEEN CLIPS (IF ANY) SPACED
AT SCALED DOWN DISTANCES IN
RELATION TO UNIT SHOWN]
6
COPYRIGHT ENGINEERING EXPRESS
©
035-24608-001-A-0316
7
V:\Projects\15-2783 OD Condensing Unit Test Protocol\WP\NOA Submittal\15-2783_k OD Condensing Unit (CLIENT COPY).dwg
intern1
04/04/2016 - 3:11pm
3.1"
20.8"
13.0"
BACK
RIGHT
YHE60B21S PLAN VIEW
LEFT
34.3"
PLAN
RIGHT
NOT APPROVED FOR
ATTACHMENT TO WOOD
RIGHT
PLAN
CLIP TYPE A
SEE TABLE 1 FOR HOST
ANCHORAGE OPTIONS
PROVIDE (2) #10-16 x 3 8" SAE
GR. 5 SMS W/ 516 " SL
SLOTTED HEX
HEAD AND 0.40"Ø x 0.025"
0
LOCK
THICK INTEGRATED L
WASHER
NTS
ELEVATION
YHE60B21S TIEDOWN DIRECTIVE
AS NEEDED: MARK
ARK AND DRILL
OLES USING A
ADDITIONAL HOLES
1
TO THE BASE
8" DRILL INTO
FLANGE BEING CAREFUL NOT
TO DAMAGE
E THE COIL.
STEEL UNIT
BASE
PLAN
YHE60B21S TIEDOWN LAYOUT - ROOF INSTALL
BACK
3.3"
34.3"
LEFT
CLIP QTY: 12
2.9"
18.0"
30.5"
34.3"
FRONT
ELEVATION
FRONT
BACK
34.3"
20.8"
FRONT
ELEVATION
38.0"
YHE60B21S LEFT VIEW
38.0"
ELEVATION
YHE60B21S RIGHT VIEW
42.8"
YHE60B21S BACK VIEW
34.3"
ELEVATION
YHE60B21S FRONT VIEW
3.3"
2.9"
YHE60B21S TIEDOWN LAYOUT - GROUND INSTALL
CLIP QTY: 6
LEFT
38.0"
38.0"
38.0"
34.8"
34.8"
34.3"
18.6"
OD CONDENSING UNITS
YHE60B21S MODEL
13.0"
13.0"
YORK INTERNATIONAL CORP.
33.9"
42.8"
42.8"
33.9"
25.0"
8
42.8"
FOR SMALLER MODELS:
SMALLER MODEL BASE PROFILES SHALL
HAVE THE SAME CLIP PATTERN AS SHOWN
W/ THE SAME CLIP COUNT PER SIDE. THE
FIRST CLIP FROM EACH CORNER SHALL BE
AT THE SAME DISTANCES SHOWN [FOR
EXAMPLE: THE CLIP CIRCLED BELOW WILL
ALWAYS BE AT 2.9" FROM THE FRONT
LEFT CORNER OF ANY SMALLER UNIT
WITH IN BETWEEN CLIPS (IF ANY) SPACED
AT SCALED DOWN DISTANCES IN
RELATION TO UNIT SHOWN]
7
COPYRIGHT ENGINEERING EXPRESS
©
035-24608-001-A-0316
Johnson Controls Unitary Products
V:\Projects\15-2783 OD Condensing Unit Test Protocol\WP\NOA Submittal\15-2783_k OD Condensing Unit (CLIENT COPY).dwg
intern1
04/04/2016 - 3:11pm
LOUVERS CONTINUE
BACK
FRONT
34.3"
RIGHT
PLAN
ELEVATION
RHP14L60B21S LEFT VIEW
38.0"
ELEVATION
RHP14L60B21S RIGHT VIEW
RHP14L60B21S PLAN VIEW
LEFT
ELEVATION
RHP14L60B21S BACK VIEW
34.3"
SOME LOUVERS NOT SHOWN FOR
CLARITY, THIS SHEET
ELEVATION
RHP14L60B21S FRONT VIEW
3.5"
FRONT
BACK
34.3"
22.1"
2.6"
RIGHT
3.5"
3.4"
BACK
34.3"
12.4"
21.0"
RIGHT
NOT APPROVED FOR
ATTACHMENT TO WOOD
CLIP TYPE A
SEE TABLE 1 FOR
HOST ANCHORAGE
OPTIONS
PROVIDE (2) #10-16 x 3 8" SAE
GR. 5 SMS W/ 516 " SLOTTED HEX
HEAD AND 0.40"Ø x 0.025"
THICK INTEGRATED LOCK
WASHER
NTS
ELEVATION
RHP14L60B21S TIEDOWN DIRECTIVE
AS NEEDED: MARK AND
ND DRILL
ADDITIONAL HOLES USING A
1
E BASE
8" DRILL INTO THE
FLANGE BEING CAREFUL
EFUL NOT
TO DAMAGE THE COIL.
STEEL UNIT
BASE
PLAN
RHP14L60B21S TIEDOWN LAYOUT - ROOF INSTALL
LEFT
CLIP QTY: 12
2.6"
17.8"
FRONT
30.5"
PLAN
RHP14L60B21S TIEDOWN LAYOUT - GROUND INSTALL
CLIP QTY: 6
LEFT
38.0"
38.0"
38.0"
34.9"
34.3"
35.4"
18.9"
42.8"
42.8"
13.7"
13.0"
OD CONDENSING UNITS
RHP14L60B21S MODEL
38.0"
34.4"
42.8"
YORK INTERNATIONAL CORP.
LOUVERS CONTINUE
35.1"
23.7"
Johnson Controls Unitary Products
42.8"
FOR SMALLER MODELS:
SMALLER MODEL BASE PROFILES SHALL
HAVE THE SAME CLIP PATTERN AS SHOWN
W/ THE SAME CLIP COUNT PER SIDE. THE
FIRST CLIP FROM EACH CORNER SHALL BE
AT THE SAME DISTANCES SHOWN [FOR
EXAMPLE: THE CLIP CIRCLED BELOW WILL
ALWAYS BE AT 2.6" FROM THE FRONT
LEFT CORNER OF ANY SMALLER UNIT
WITH IN BETWEEN CLIPS (IF ANY) SPACED
AT SCALED DOWN DISTANCES IN
RELATION TO UNIT SHOWN]
8
COPYRIGHT ENGINEERING EXPRESS
©
035-24608-001-A-0316
9
NOTES
Subject to change without notice. Published in U.S.A.
Copyright © 2016 by Johnson Controls, Inc. All rights reserved.
York International Corp.
5005 York Drive
Norman, OK 73069
035-24608-001-A-0316
Supersedes: 035-24114-001-A-0514

Similar documents

Catálogo general - Euroveterinaria

Catálogo general - Euroveterinaria positivo, negativo 0,5 ml Ref. C+BB / C-BB positivo, negativo 0,5 ml Ref. C+8121 / C-8121 positivo, negativo 1 ml Ref. 211-P-LD / 211-N-LD

More information

Service Manual - Pinnacle RV Appliances

Service Manual - Pinnacle RV Appliances 7KHZDVKHUFRPERFDQ¶WVWRSWRILOODIWHUWKHZDWHUOHYHOUHDFKHVWKHVHWYDOXHWKLVXQLWZLOORYHUILOO$QG WKHHUURUFRGHRI(ZLOOEHGLVSOD\HGRQ9)' $LUOHDNDJHRQWKHK

More information