VariTrane® Products Catalog - Single/Dual Duct (VAV-DS-14
Transcription
VariTrane® Products Catalog - Single/Dual Duct (VAV-DS-14
Single-Duct and Dual-Duct VariTrane® Units 53 Model Number Description Single-Duct VAV Terminals Single-Duct VAV Terminal Units SIZE 5WO 5W 6WO 6W 8WO 8W 10WO 10W 12WO 14WO Outlet Size 5" Outlet w/o Bal. Damper 5" Outlet w/ Bal. Damper 6" Outlet w/o Bal. Damper 6" Outlet w/ Bal. Damper 8" Outlet w/o Bal. Damper 8" Outlet w/ Bal. Damper 10" Outlet w/o Bal. Damper 10" Outlet w/ Bal. Damper 12" Outlet w/o Bal. Damper 14" Outlet w/o Bal. Damper APNL WITH Access Panel Access Panel The features of the single-duct VAV terminal units are described by the product categories shown below in bold. Within each category the options available are listed. Model VCCE Model VCWE MODL VCCE VCWE VCEE Unit Model Single-Duct Cooling Only Terminal Single-Duct With Hot Water Heat Single-Duct With Electric Heat DSEQ H Design Sequence H Design Sequence ATEN WITH Attenuator Attenuators VALV 03 06 11 17 24 32 42 Air Valve Size 03 Air Valve 06 Air Valve 11 Air Valve 17 Air Valve 24 Air Valve 32 Air Valve 42 Air Valve CTRL Unit Control INSL MT.5 MT1 FF.5 FF1 DW.5 DW1 Unit Insulation 1/2" Matte Faced 1" Matte Faced 1/2" Foil Faced 1" Foil Faced Double-Wall w/ 1/2" Matte Faced Double-Wall w/ 1" Matte Faced OUTL FL SD X A Outlet Connection Flanged Outlet Connection Slip and Drive Connection Rectangular Sheet Metal Frame 1 Right Hand Side Outlet Connection 1 End Outlet Connection 1 Left Hand Side Outlet Connection 1 Right Hand Side And 1 End Outlet Connection 1 Left Hand Side And 1 End Outlet Connection 1 Right Hand Side And 1 Left Hand Side Outlet Connection 2 End Outlet Connections 1 Left Hand Side, 1 Right Hand Side, And 1 End Outlet Connection 1 Left Hand Side, 1 Right Hand Side, And 2 End Outlet Connection B C D E F G H J Model VCEE 54 DDC Options DD00 Actuator Wired To Term. Strip DD01 W/O Remote Heat - Cooling Only DD02 N.C. On/Off H.W. Valve Control DD03 Proportional Hot Water Valve Control DD04 On/Off Electric Heat Control DD05 Pulse Width Modulation DD07 N.O. On/Off H.W. Valve Control FM00 Actuator Furn. w/ Factory Mount Of Customer Supplied Controls Pneumatic Options PN01 N.O. Valve Actuator Only (R.A. Stat) PN04 N.O. Valve 3025 PVR (D.A. Stat) PN05 N.O. Valve 3025 PVR (R.A. Stat) PN06 N.O. Valve 2017 PVR (D.A. Stat) PN30 N.O. Valve 3025 PVR, Const. Volume PN31 N.O. Valve 2017 PVR, Const. Volume PC01 N.C. Valve Actuator Only (D.A. Stat) PC02 N.C. Valve 3025 PVR (D.A. Stat) PN32 N.O. Valve 3025 PVR, N.O. Hot Water, Const. Volume (D.A. Stat) PN33 N.O.Valve 2017 PVR N.O. Hot Water, Const. Volume (D.A. Stat) PN07 N.O. Valve 2017 PVR (R.A. Stat) PN34 N.O. Valve 3025 PVR, Const. Volume (R.A. Stat ) PN35 N.O.Valve 2017 PVR, Const. Volume (R.A. Stat) Analog Electronic Options EI01 PI - Cooling Only-Basic Operation EI05 PI - Basic Oper. w/Remote Heat Capability EI28 PI - Basic Oper. w/Rem. Heat Capability and Automatic Dual Minimum EI29 PI - Basic Oper. w/Remote Heat Capability and Const. Volume EI30 PI - Basic Oper. w/Constant Volume STAT Static Pressure Control Model Number Description Single-Duct VAV Terminals XFMR 120 208 240 277 480 347 575 Transformer 120/24 Volt Transformer 208/24 Volt Transformer 240/24 Volt Transformer 277/24 Volt Transformer 480/24 Volt Transformer 347/24 Volt Transformer 575/24 Volt Transformer DCTR DISW Control Disconnect Switch Control Disconnect Switch FCTR FUSE Control Fuse Control Line Fuse HTKW 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0 9.0 10.0 11.0 12.0 13.0 14.0 15.0 16.0 17.0 18.0 20.0 22.0 24.0 26.0 Electric Heater Kilowatts 0.5 kW 1.0 kW 1.5 kW 2.0 kW 2.5 kW 3.0 kW 3.5 kW 4.0 kW 4.5 kW 5.0 kW 5.5 kW 6.0 kW 6.5 kW 7.0 kW 7.5 kW 8.0 kW 9.0 kW 10.0 kW 11.0 kW 12.0 kW 13.0 kW 14.0 kW 15.0 kW 16.0 kW 17.0 kW 18.0 kW 20.0 kW 22.0 kW 24.0 kW 26.0 kW CNTR MAGN MERC PEMA PEME Electric Heater Control 24 Volt Magnetic Contactors 24 Volt Mercury Contactors P.E. w/Magnetic Contactors P.E. w/Mercury Contactors DHTR DISW Electric Heater Disconnect Swt Electric Heater Door Disconnect Switch FHTR FUSE Electric Heater Line Fuse Electric Heater Line Fuse HWCL Hot Water Coil STHW Standard Capacity Hot Water Coil HIHW High Capacity Hot Water Coil VOLT 2081 2083 2401 2771 4801 4803 3471 5751 5753 STGE 1 2 3 Electric Heater Voltage 208/60/1 Voltage Heater 208/60/3 Unbalanced 240/60/1 Voltage Heater 277/60/1 Voltage Heater 480/60/1 Voltage Heater 480/60/3, Unbalanced Voltage Heater 347/60/1 Voltage Heater 575/60/1 Voltage Heater 575/60/3 Voltage Heater (unbalanced) Electric Heater Stage 1 Stage Of Heat 2 Equal Stages Of Heat 3 Equal Stages Of Heat 55 Model VDDE Model Number Description Dual-Duct VAV Terminals Dual-Duct VAV Terminal Units The features of the dual-duct VAV terminal units are described by the product categories shown below in bold. Within each category the options available are listed. SIZE 5WO 5W 6WO 6W 8WO 8W 10WO 10W Outlet Size 5" Outlet w/o Bal. Damper 5" Outlet w/ Bal. Damper 6" Outlet w/o Bal. Damper 6" Outlet w/ Bal. Damper 8" Outlet w/o Bal. Damper 8" Outlet w/ Bal. Damper 10" Outlet w/o Bal. Damper 10" Outlet w/ Bal. Damper MODL Unit Model VDDE Double-Duct Control Terminal ATEN FL DSEQ E Design Sequence E Design Sequence SD Attenuator Attenuators With Flanged Connection Attenuators With Slip And Drive Conn. HTCL 0303 0306 0606 0611 1111 1117 1717 1124 1724 2424 3232 4242 Dual-Duct Valve Combinations 03 Htg Air Valve, 03 Clg Air Valve 03 Htg Air Valve, 06 Clg Air Valve 06 Htg Air Valve, 06 Clg Air Valve 06 Htg Air Valve, 11 Clg Air Valve 11 Htg Air Valve, 11 Clg Air Valve 11 Htg Air Valve, 17 Clg Air Valve 17 Htg Air Valve, 17 Clg Air Valve 11 Htg Air Valve, 24 Clg Air Valve 17 Htg Air Valve, 24 Clg Air Valve 24 Htg Air Valve, 24 Clg Air Valve 32 Htg Air Valve, 32 Clg Air Valve 42 Htg Air Valve, 42 Clg Air Valve CTRL DD00 DD01 INSL MT.5 MT1 FF.5 FF1 DW.5 Unit Insulation 1/2"Matte Faced 1" Matte Faced 1/2" Foil Faced 1" Foil Faced Double-Wall w/ 1/2" Matte Faced OUTL Outlet Connection NONE Field Supplied Flanged Connection A 1 Right Hand Side Outlet Connection B 1 End Outlet Connection C 1 Left Hand Side Outlet Connection D 1 Right Hand Side and 1End Outlet Connection E 1 Left Hand Side and 1 End Outlet Connection F 1 Right Hand Side and 1Left Hand Side Outlet Connection G 2 End Outlet Connections H 1 Right Hand Side, 1 End and 1 Left Hand Side Outlet Connections J 1 Right Hand Side, 2 End and 1 Left Hand Side Outlet Connections 56 FM00 Unit Control DDC Options Actuator Wired To Term. Strip Direct Digital Controls - Cooling Only Actuator Furn. w/ Factory Mount Customer Supplied Pneumatic Options PN08 N.O. Heating Valve & N.O. Cooling Valve - Actuator Only PN09 N.O. Heating Valve & N.O. Cooling Valve - Two 3025 PVR’s PN10 Constant Volume Discharge N.O. Heating Valve & N.O. Cooling Valve - Two 3525 PVR’s PC03 N.C. Heating Valve & N.O. Cooling Valve - Two 3025 PVR’s XFMR 120 208 240 277 347 480 575 Control Power Transformer 120/24 Volt Transformer 208/24 Volt Transformer 240/24 Volt Transformer 277/24 Volt Transformer 347/24 Volt Transformer 480/24 Volt Transformer 575/24 Volt Transformer DISW DCTR Control Disconnect Switch Control Disconnect Switch FUSE FCTR Control Line Fuse Control Line Fuse This section describes the catalog selection of single and dual-duct VAV terminal units with specific examples. A computer selection program is also available to aid in selection of VAV terminal units, but is not described here. Selection of single and dual-duct VAV terminal units can involve three elements: 1. Air Valve selection 2. Heating coil selection (if required) 3. Acoustics Air Valve Selection The wide open static requirement pressure versus airflow curve is found in the performance data section of the catalog. To select an air valve, locate the required design cooling airflow for your terminal unit type and find its vertical intersection, with the smallest air valve size that has a pressure drop equal to or lower than the maximum wide open static pressure requirement. Selection Procedure Single and Dual-Duct Terminal Units Hot Water Heat Select a hot water coil sufficient to meet the design heat loss. Selection: Select 7.5 kW from the electric heat table in the voltage and stages required. The table shows the minimum cfm allowable for the kW selected. At 7.5 kW, the minimum allowable airflow is 510 cfm. The minimum cfm must be increased to 510 to assure adequate airflow over the 7.5 kW electric coil. The static pressure requirement is shown as 0.17 in. wg. for this example with a design cooling flow of 1700 cfm. Example: VCWE, Hot Water Unit Heat, Size 17 (See air Valve Selection) Design heating airflow: 850 cfm Hot water flow: 1.0 GPM Winter room design Temperature: T = 68 F Design Heat Loss MBh: Q = 25 Select hot water coil from the coil performance table in the Performance Data section of the catalog. Selection: A Standard Capacity coil is sufficient to meet design conditions. From the Hot Water Coil Capacity Data of the Performance Data Section, a standard capacity coil for a Size 17 air valve will operate at the above conditions as follows: Coil Capacity: 25.7 MBh Water pressure drop: 0.33 ft WPD Example: Cooling Only VCCE Terminal Unit Design cooling airflow: 1700 cfm Maximum wide open air pressure drop: 0.25 in. wg Minimum cooling airflow: 300 cfm Air pressure drop (APD) of the hot water coil is included in the chart preceding the hot water coil performance data section. From the performance data charts, select a valve size 17 which has a wide open static pressure drop of 0.16 in. wg. Electric Heat Determine the kW required to meet zone design heat loss. Check the minimum and maximum cfm desired with the minimum and maximum cfm allowed in the table in the general data section. The maximum setting of 1700 cfm is within the acceptable range. The desired minimum setting of 300 cfm is acceptable for the cooling only box desired. Note that if an electric reheat box was selected, the minimum cfm would be dependent upon the kW of the electric heater. (See Electric Heat Unit Selection.) MBh = Design Heat Loss Heating Coil Selection (If required) First, determine the amount of heat required to meet space and downstream duct heat losses from a load calculation. APD = 0.042 in. wg kW = MBh / 3.414 Select nearest available kW with voltage and steps desired from the electric heater kW guideline table in the Performance Data section of the catalog. Example: VCEE, Electric Unit Heat, Size 17 (See Air Valve Selection) Design heating airflow: 850 cfm Minimum unit airflow: 300 cfm Voltage: 277/60/1 VAC Winter room design temperature: T = 68 F Design Heat Loss: Q = 25 MBh kW = Q / 3.414 kW = 25 / 3.414 kW = 7.3 57 Check Leaving Air Temperature LAT = Q +T 1.085 x CFM Decide if leaving air temperature of 95.8 F is satisfactory for your application. LAT = 3414 x 7.5 + 68 = 95.8 1.085 x 850 Acoustics The acoustical data found in the Performance Data section of the VAV catalog is used to make a determination of the amount of noise the terminal unit will generate. Locate the table for the VAV terminal unit of interest. Sound power data and an equivalent NC level for an ARI 885-90 transfer function is listed. Example: VCCE, Cooling Only Terminal Unit, Size 17 (See air Valve Selection) Cooling Airflow Cfm = 1700 Maximum inlet static pressure: 1.5 in. wg. Downstream static pressure requirement: 0.30 in. wg. Maximum NC Criteria = NC-35 Maximum Inlet Static Pressure is the maximum static at the inlet to the box. Downstream Static Pressure requirement is the static loss downstream of the VAV box, which includes everything from the discharge of the box to the room. The catalog assumes 0.5 inches of downstream static pressure for all but the minimum inlet static pressure valves. Since we have a downstream static pressure loss of 0.30 inches, the static across the box will be more than the catalog’s assumption using 0.5 inches downstream. Look into the catalog’s acoustic table at 1.5 + (0.5-0.3) or 1.7 inches. Selection Procedure Single and Dual-Duct Terminal Units Interpolation gives sound power data of: Octave Band Rad. Sound Power Disch. Sound Power 2 68 71 3 61 68 4 55 69 5 49 66 6 42 58 7 35 55 NC 27 20 The NC level above is determined by using either the catalog’s ARI 885-90 transfer function for the conditions shown in the acoustics table. A different transfer function could be applied as conditions dictate. The maximum NC level is NC-26 which is less than the maximum NC for this example of NC-35. If the maximum NC level was exceeded, it would have been necessary to reselect the next larger air valve size. Computer selection of VAV terminal units greatly simplifies this task. 58 Performance Data General Data Primary Air Control VCCE, VCWE, VDDE CFM Setting Guidelines Control Type UCM - Direct Digital (Max flow must be greater than or equal to the minimum) Pneumatic With Volume Regulator and Pressure-Independent Electronic Valve Size 03 06 11 17 24 32 42 03 06 11 17 24 32 42 Nominal CFM 300 600 1100 1700 2400 3200 4200 300 600 1100 1700 2400 3200 4200 Maximum Setting 0, 30-330 CFM 0, 60-660 CFM 0, 110-1210 CFM 0, 170-1870 CFM 0, 240-2640 CFM 0, 320-3520 CFM 0, 420-4620 CFM 135-415 CFM 215-650 CFM 400-1200 CFM 650-1930 CFM 930-2800 CFM 1270-3800 CFM 1660-5000 CFM Minimum Setting 0, 30-330 CFM 0, 60-660 CFM 0, 110-1210 CFM 0, 170-1870 CFM 0, 240-2640 CFM 0, 320-3520 CFM 0, 420-4620 CFM 60-220 CFM 90-340 CFM 170-640 CFM 270-1020 CFM 390-1480 CFM 530-2000 CFM 700-2630 CFM Constant Volume Maximum Setting 0, 14-156 L/s 0, 28-311 L/s 0, 52-571 L/s 0, 80-883 L/s 0, 113-1246 L/s 0, 151-1661 L/s 0, 198-2180 L/s 64-196 L/s 101-307 L/s 189-566 L/s 307-911 L/s 439-1 321 L/s 599-1 793 L/s 783-2 360 L/s Minimum Setting 0, 14-156 L/s 0, 28-311 L/s 0, 52-571 L/s 0, 80-883 L/s 0, 113-1246 L/s 0, 151-1661 L/s 0, 198-2180 L/s 60-220 L/s 90-340 L/s 170-640 L/s 270-1020 L/s 390-1480 L/s 530-2000 L/s 700-2630 L/s Constant Volume 60-415 90-650 170-1200 270-1930 390-2800 530-3800 700-5000 Primary Air Control VCCE, VCWE, VDDE L/s Setting Guidelines (Metric) Control Type UCM - Direct Digital (Max flow must be greater than or equal to the minimum) Pneumatic With Volume Regulator and Pressure-Independent Electronic Valve Size 03 06 11 17 24 32 42 03 06 11 17 24 32 42 Nominal L/s 142 283 519 802 1 133 1 510 1 982 142 283 519 802 1 133 1 510 1 982 59 60-415 90-650 170-1200 270-1930 390-2800 530-3800 700-5000 Performance Data Setting Guidelines VCEE – CFM Settings Guidelines Valve Size 03 06 11 17 24 32 42 Nominal CFM 300 600 1100 1700 2400 3200 4200 Control Type UCM UCM UCM UCM UCM UCM UCM 20% NOM. 60-300 120-600 220-1100 340-1700 480-2400 640-3200 840-4200 Minimum Setttings 30% NOM. 40% NOM. 90-300 120-300 180-600 240-600 330-1100 440-1100 510-1700 680-1700 720-2400 960-2400 960-3200 1280-3200 1260-4200 1680-4200 50% NOM. 150-300 300-600 550-1100 850-1700 1200-2400 1600-3200 2100-4200 Maximum Settings 150-315 300-630 550-1155 850-1758 1200-2520 1600-3460 2100-4410 Constant Volume Control Type PNEUMATIC/PI PNEUMATIC/PI PNEUMATIC/PI PNEUMATIC/PI PNEUMATIC/PI PNEUMATIC/PI PNEUMATIC/PI 20% NOM. 60-220 120-340 220-640 340-1020 480-1480 640-2000 840-2630 Minimum Setttings 30% NOM. 40% NOM. 90-220 120-220 180-340 240-340 330-640 440-640 510-1020 680-1020 720-1480 960-1480 960-2000 1280-2000 1260-2630 1680-2630 50% NOM. 150-220 300-340 550-640 850-1020 1200-1480 1600-2000 2100-2630 Maximum Settings 135-415 215-650 400-1200 650-1930 930-2800 1270-3800 1660-5000 Constant Volume 60-415 120-650 220-1200 340-1930 480-2800 640-3800 840-5000 20% NOM. 28-142 57-283 104-519 160-802 227-1 133 302-1 510 396-1 982 Minimum Setttings 30% NOM. 40% NOM. 42-142 57-142 85-283 113-283 156-519 208-519 241-802 321-802 340-1 133 453-1 133 453-1 510 604-1 510 595-1 982 793-1 982 50% NOM. 71-142 142-283 260-519 401-802 566-1 133 755-1 510 991-1 982 Maximum Settings 71-149 142-297 260-545 401-842 566-1 189 755-1 633 991-2 081 Constant Volume Maximum Settings 64-196 101-307 189-566 307-911 439-1 321 599-1 793 783-2 360 Constant Volume 28-196 57-307 104-566 160-911 277-1 321 302-1 793 396-2 360 VCEE – CFM Settings Guidelines Valve Size 03 06 11 17 24 32 42 Nominal CFM 300 600 1100 1700 2400 3200 4200 VCEE – L/s Settings Guidelines (Metric) Valve Size 03 06 11 17 24 32 42 Nominal CFM 142 283 519 802 1 133 1 510 1 982 Control Type UCM UCM UCM UCM UCM UCM UCM VCEE – L/s Settings Guidelines (Metric) Minimum Setttings Valve Size Nominal CFM Control Type 20% NOM. 30% NOM. 40% NOM. 50% NOM. 03 142 PNEUMATIC/PI 28-104 42-104 57-104 71-104 06 283 PNEUMATIC/PI 57-160 85-160 113-160 142-160 11 519 PNEUMATIC/PI 104-302 156-302 208-302 260-302 17 802 PNEUMATIC/PI 160-481 241-481 321-481 401-481 24 1 133 PNEUMATIC/PI 227-698 340-698 453-698 566-698 32 1 510 PNEUMATIC/PI 302-944 453-944 604-944 755-944 42 1 982 PNEUMATIC/PI 396-1 241 595-1 241 793-1 241 991-1 241 Notes: 1. Minimum flow and maximum flow settings must have at least a .05 delta P flow sensor signal difference. 2. Flow rings are provided with all unit sizes. 3. A minimum flow setting of zero is permissible, except for hot water and electric reheat. 4. UCM-DDC control - The minimum heating flow setting is factory set to 30% of nominal air valve flow. This is field adjustable. 5. On Model VDDE - Constant Volume = (Heat Min. + Cool Max. = Heat Max. + Cool Min.) Example: Constant Volume = 1200 CFM Heat Max. = 800 Cool Max. = 1200 Heat Min. = 0 Cool Min. = 400 6. Minimum cfm’s could increase due to kW requirements. 60 DP Chart CFM Guidelines Performance Data Flow Sensor Delta P Signal vs. Air Flow Delivery Static Pressure Required to Deliver Nominal Airflow Inches VCCE VCWE (STHW) VCWE (HIHW) VCEE VDDE 300 600 5 0.422 0.472 0.498 0.481 0.432 6 0.291 0.498 0.543 0.32 0.34 Nominal CFM 1700 Inlet Size (Inches) 8 10 0.206 0.168 0.506 0.398 0.65 0.486 0.351 0.181 0.47 0.378 1100 2400 3200 4200 12 0.144 0.388 0.463 0.186 0.185 14 0.22 0.36 0.48 0.25 0.23 16 0.191 0.47 0.63 0.202 0.541 1510 1982 356 54.81 89.69 119.59 62.28 57.30 406 47.59 117.09 156.96 50.33 134.78 Static Pressure Required to Deliver Nominal Airflow Metric - Pascals 142 283 519 Nominal L/S 802 Inlet Size (mm) 254 41.86 99.16 121.08 45.09 45.09 1133 127 152 203 305 VCCE 105.14 72.50 51.32 35.88 VCWE (STHW) 117.59 124.07 126.06 96.67 VCWE (HIHW) 124.07 135.28 161.94 115.35 VCEE 119.84 79.72 87.45 46.34 VDDE 107.63 84.71 117.09 46.09 Notes: Static requirement for losses downstream of the box are not included. Losses shown are for outlet connection code FL or SD. 61 Performance Data Single and Dual-Duct Terminal Units Plenum Outlet Static Pressure Requirements Table PD-1 — Models VCCE, VCWE, VDDE ( Inches W.G.) Outlet Conn. A,B,C D,E,F G H J Dia in. 5 6 8 10 12 14 5 6 8 10 6 8 10 5 6 8 10 5 6 8 10 150 0.15 0.08 0.02 0.05 0.03 0.01 0.02 0.01 03 225 0.31 0.17 0.04 0.11 0.06 0.02 0.05 0.03 300 0.51 0.28 0.07 0.20 0.09 0.04 0.09 0.04 300 06 450 600 0.28 0.07 0.54 0.17 1.62 0.30 0.20 0.09 0.04 0.09 0.04 0.01 0.45 0.23 0.10 0.21 0.12 0.05 0.78 0.39 0.17 0.36 0.19 0.08 550 Unit Size 11 825 1100 0.27 0.09 0.69 0.25 1.20 0.46 0.26 0.10 0.05 0.23 0.14 0.05 0.66 0.29 0.16 0.59 0.35 0.14 1.12 0.50 0.29 1.03 0.62 0.25 850 17 1275 1700 0.37 0.16 Note 3 0.86 0.33 1.58 0.59 0.27 0.15 0.57 0.31 0.96 0.47 0.13 0.30 0.53 0.31 0.13 0.06 0.67 0.29 0.15 1.13 0.52 0.27 0.19 0.09 0.40 0.21 0.75 0.35 1200 24 1800 2400 0.24 0.14 Note 3 0.65 0.34 1.18 0.63 0.21 0.46 0.82 0.12 0.29 0.52 0.15 0.09 0.34 0.21 0.60 0.38 0.08 0.05 0.19 0.11 0.35 0.20 Notes: 1. Add static pressure requirements for integral outlets to Outlet Connection Code FL or SD pressure drop from appropriate chart on previous pages. 2. Size 32 and 42 not available with integral outlets on VDDE only. Size 24 not available with integral outlets. 3. Outlet Connection Code B, Model VCCE ONLY. Table PD-1A — Models VCCE, VCWE, VDDE (Metric)(Pascals) Outlet Conn. A,B,C D,E,F G H J Dia mm 127 152 203 254 305 356 127 152 203 254 152 203 254 127 152 203 254 127 152 203 254 71 37.35 19.92 4.98 12.45 7.47 2.49 4.98 2.49 03 106 77.19 42.33 9.96 27.39 14.94 4.98 12.45 7.47 142 127.00 69.72 17.43 49.80 22.41 9.96 22.41 9.96 142 06 212 283 69.72 17.43 134.5 42.33 403.40 74.70 49.80 22.41 9.96 22.41 9.96 2.49 112.1 57.27 24.90 52.29 29.88 12.45 194.20 97.11 42.33 89.64 47.31 19.92 260 Unit Size 11 389 519 67.23 22.41 171.8 62.25 298.8 114.5 64.74 24.90 12.45 57.27 34.86 12.45 164.3 72.21 39.84 146.9 87.15 34.86 278.9 124.5 72.21 256.5 154.4 62.25 401 17 602 802 92.13 39.84 Note 3 214.1 82.17 393.4 146.9 67.23 37.35 141.9 77.19 239 117 32.37 74.7 132 77.19 32.37 14.94 166.8 72.21 37.35 281.4 129.5 67.23 47.31 22.41 99.6 52.29 186.8 87.15 566 24 850 1133 59.76 34.86 Note 3 161.9 84.66 293.8 156.9 52.29 114.5 204.20 29.88 72.21 129.50 37.35 22.41 84.66 52.29 149.40 94.62 19.92 12.45 47.31 27.39 87.15 49.80 Notes: 1. Add static pressure requirements for integral outlets to Outlet Connection Code FL or SD pressure drop from appropriate chart on previous pages. 2. Size 32 and 42 not available with integral outlets on VDDE only. Size 24 not available with integral outlets. 3. Outlet Connection Code B, Model VCCE ONLY. 62 Performance Data Single and Dual-Duct Terminal Units Attenuation Table PD-2 — Attenuator: Static Pressure Requirements Unit Size 03 06 11 17 24 32 42 CFM 150 225 300 300 450 600 550 825 1100 850 1275 1700 1200 1800 2400 1600 2400 3200 2100 3150 4200 Inches W.G. 0.004 0.007 0.010 0.010 0.021 0.033 0.007 0.016 0.028 0.003 0.007 0.013 0.003 0.008 0.013 0.006 0.010 0.013 0.007 0.012 0.017 Table PD-2A — Attenuator (Metric) Unit Size 03 06 11 17 24 32 42 L/s 71 106 142 142 212 283 260 389 519 401 602 802 566 850 1133 755 1133 1510 991 1487 1982 63 Pa 0.996 1.743 2.490 2.490 5.229 8.217 1.743 3.984 6.972 0.747 1.743 3.237 0.747 1.992 3.237 1.494 2.490 3.237 1.743 2.988 4.233 Performance Data Single and Dual-Duct Terminal Units Unit Pressure Drop Chart PD-1 – Model VCCE Outlet – Straight Flanged or Slip and Drive Chart PD-2 – Model VCWE Outlet – Straight Flanged or Slip and Drive Standard Capacity Coil (Unit and Coil) Chart PD-3 – Model VCWE Outlet – Straight Flanged or Slip and Drive High Capacity Coil (Unit and Coil) 64 Performance Data Single and Dual-Duct Terminal Units Unit Pressure Drop Chart PD-4 – Model VCEE Outlet – Flanged or Slip and Drive (Unit and Coil) Chart PD-5 – Model VDDE Outlet – Flanged or Slip and Drive 65 Performance Data Single-Duct VAV Terminal Units – VCWE Table PD-3 — Size 03, 06 Hot Water Coil Capacity Data (MBh) Airflow (CFM) 45 Standard Capacity Coil (STHW) with 144 Fins per foot Leaving Water Coil Water Air Temperature Capacity Pressure GPM Temperature Drop (F) (MBH) Drop (ft) 0.5 1.0 1.5 2.0 2.5 150.4 156.2 158.2 159.3 160.0 18.6 9.9 6.7 5.1 4.1 4.7 4.9 5.0 5.1 5.1 0.79 2.63 5.36 8.91 13.23 0.5 1.0 1.5 2.0 2.5 141.2 147.9 150.3 151.6 152.4 22.4 12.1 8.3 6.3 5.1 5.6 6.0 6.2 6.3 6.3 0.79 2.63 5.37 8.92 13.24 0.5 1.0 1.5 2.0 2.5 127.5 135.1 137.9 139.4 140.4 28.3 15.6 10.8 8.2 6.7 7.1 7.8 8.1 8.2 8.3 0.79 2.64 5.38 8.93 13.26 0.5 1.0 1.5 2.0 2.5 123.9 131.6 134.6 136.1 137.1 29.9 16.6 11.5 8.8 7.1 7.5 8.3 8.6 8.8 8.9 0.79 2.64 5.38 8.94 13.26 0.5 1.0 1.5 2.0 2.5 110.5 118.5 121.6 123.3 124.4 36.1 20.6 14.4 11.0 9.0 9.0 10.3 10.8 11.1 11.3 0.80 2.65 5.39 8.96 13.29 0.5 1.0 1.5 2.0 2.5 101.7 109.6 112.8 114.5 115.6 40.5 23.7 16.7 12.9 10.5 10.1 11.8 12.5 12.9 13.2 0.80 2.66 5.41 8.97 13.31 0.5 1.0 1.5 2.0 2.5 91.1 98.2 101.3 103.0 104.1 47.0 28.1 20.0 15.6 12.8 11.7 14.0 15.1 15.6 16.0 0.81 2.67 5.42 8.99 13.34 0.5 1.0 1.5 2.0 2.5 84.6 91.0 94.0 95.6 96.7 51.3 31.2 22.5 17.6 14.4 12.8 15.6 16.9 17.6 18.1 0.81 2.68 5.44 9.01 13.36 0.5 1.0 1.5 2.0 2.5 80.1 86.1 88.9 90.4 91.5 54.5 33.7 24.5 19.2 15.8 13.6 16.9 18.4 19.2 19.8 0.81 2.68 5.45 9.03 13.38 0.5 1.0 1.5 2.0 2.5 76.8 82.5 85.1 86.6 87.6 56.9 35.8 26.1 20.5 16.9 14.2 17.9 19.6 20.5 21.2 0.82 2.69 5.45 9.04 13.40 Airflow (CFM) 45 60 60 90 90 100 100 150 150 200 200 300 300 400 400 500 500 600 600 High Capacity Coil (HIHW) with 192 Fins per foot Leaving Water Coil Air Temperature Capacity GPM Temperature Drop (F) (MBH) 0.5 137.8 16.1 4.0 1.0 144.6 8.7 4.4 2.0 148.4 4.6 4.6 3.0 149.7 3.1 4.6 4.0 150.4 2.3 4.7 5.0 150.9 1.9 4.7 0.5 133.7 20.5 5.1 1.0 142.4 11.4 5.7 2.0 147.2 6.0 6.0 3.0 149.0 4.1 6.1 4.0 149.9 3.1 6.2 5.0 150.5 2.5 6.2 0.5 123.6 26.8 6.7 1.0 134.4 15.5 7.8 2.0 140.8 8.4 8.4 3.0 143.2 5.7 8.6 4.0 144.5 4.4 8.7 5.0 145.3 3.5 8.8 0.5 120.5 28.4 7.1 1.0 131.6 16.6 8.3 2.0 138.4 9.0 9.0 3.0 140.9 6.2 9.3 4.0 142.3 4.7 9.5 5.0 143.1 3.8 9.6 0.5 107.5 34.2 8.6 1.0 119.3 20.9 10.5 2.0 127.0 11.7 11.7 3.0 130.0 8.1 12.2 4.0 131.6 6.2 12.5 5.0 132.6 5.0 12.6 0.5 98.5 37.8 9.4 1.0 110.0 23.8 11.9 2.0 117.7 13.6 13.6 3.0 120.8 9.5 14.3 4.0 122.6 7.3 14.7 5.0 123.6 5.9 14.9 0.5 87.5 42.3 10.6 1.0 97.4 27.6 13.8 2.0 104.7 16.2 16.2 3.0 107.8 11.4 17.2 4.0 109.5 8.9 17.7 5.0 110.6 7.2 18.1 0.5 81.0 45.0 11.3 1.0 89.7 30.1 15.0 2.0 96.4 17.9 18.0 3.0 99.3 12.8 19.2 4.0 100.9 9.9 19.9 5.0 101.9 8.1 20.4 0.5 76.6 47.0 11.7 1.0 84.5 31.9 16.0 2.0 90.6 19.3 19.3 3.0 93.3 13.8 20.8 4.0 94.9 10.8 21.6 5.0 95.9 8.9 22.2 0.5 73.6 48.4 12.1 1.0 80.8 33.5 16.8 2.0 86.4 20.4 20.5 3.0 89.0 14.7 22.1 4.0 90.5 11.5 23.1 5.0 91.4 9.5 23.7 Note: 1. Fouling Factor = 0.00025 2. Capacities based on 180 F entering water and 55 F entering air temperatures. See capacity correction factors at other temperature differences. 3. The following equations may be used in calculating Leaving Air Temperature (LAT) and Water Temperature Difference (WTD). WTD = EWT - LWT = 2 x MBH LAT = EAT + MBH x 921.7 CFM GPM ( ) 66 Water Pressure Drop (ft) 0.14 0.50 1.81 3.87 6.65 10.15 0.14 0.50 1.81 3.87 6.66 10.15 0.14 0.50 1.81 3.88 6.66 10.16 0.14 0.50 1.81 3.88 6.67 10.16 0.14 0.50 1.82 3.88 6.67 10.17 0.14 0.50 1.82 3.89 6.68 10.18 0.14 0.50 1.82 3.89 6.68 10.19 0.14 0.51 1.82 3.89 6.69 10.19 0.14 0.51 1.83 3.90 6.69 10.20 0.14 0.51 1.83 3.90 6.70 10.20 Performance Data Single-Duct VAV Terminal Units – VCWE Table PD-4 — Size 11 Hot Water Coil Capacity Data (MBh) Standard Capacity Coil (STHW) with 144 Fins per foot High Capacity Coil (HIHW) with 192 Fins per foot Leaving Water Coil Water Leaving Water Coil Airflow Air Temperature Capacity Pressure Airflow Air Temperature Capacity (CFM) GPM Temperature Drop (F) (MBH) Drop (ft) (CFM) GPM Temperature Drop (F) (MBH) 165 0.5 112.2 40.9 10.2 0.21 165 2.0 138.7 15.0 15.0 1.0 123.4 24.5 12.2 0.73 3.0 142.5 10.4 15.7 2.0 130.2 13.4 13.5 2.57 4.0 144.6 8.0 16.0 3.0 132.9 9.3 13.9 5.41 5.0 145.9 6.5 16.3 4.0 134.2 7.1 14.2 9.22 6.0 146.8 5.5 16.4 5.0 135.1 5.7 14.3 13.95 7.0 147.5 4.7 16.6 200 0.5 105.8 44.1 11.0 0.21 200 2.0 133.0 16.9 16.9 1.0 117.0 26.9 13.4 0.73 3.0 137.1 11.9 17.8 2.0 124.0 15.0 15.0 2.57 4.0 139.4 9.1 18.3 3.0 126.7 10.4 15.6 5.42 5.0 140.9 7.4 18.6 4.0 128.2 7.9 15.9 9.22 6.0 141.9 6.3 18.8 5.0 129.1 6.4 16.1 13.95 7.0 142.6 5.4 19.0 300 0.5 94.1 50.9 12.7 0.21 300 2.0 119.5 21.0 21.0 1.0 104.3 32.1 16.0 0.73 3.0 124.0 15.0 22.5 2.0 111.3 18.3 18.3 2.58 4.0 126.6 11.6 23.3 3.0 114.1 12.8 19.2 5.42 5.0 128.2 9.5 23.8 4.0 115.7 9.9 19.7 9.23 6.0 129.3 8.1 24.2 5.0 116.6 8.0 20.1 13.97 7.0 130.2 7.0 24.5 400 0.5 86.9 55.3 13.8 0.21 400 2.0 109.8 23.7 23.8 1.0 96.2 35.7 17.9 0.73 3.0 114.3 17.1 25.7 2.0 103.0 20.8 20.8 2.58 4.0 116.8 13.4 26.8 3.0 105.8 14.7 22.0 5.43 5.0 118.5 11.0 27.6 4.0 107.3 11.3 22.7 9.24 6.0 119.7 9.3 28.1 5.0 108.3 9.2 23.1 13.98 7.0 120.5 8.1 28.4 500 0.5 81.9 58.4 14.6 0.21 500 2.0 102.6 25.8 25.8 1.0 90.6 38.6 19.3 0.73 3.0 107.0 18.8 28.2 2.0 97.1 22.8 22.8 2.58 4.0 109.5 14.8 29.5 3.0 99.8 16.2 24.3 5.44 5.0 111.1 12.2 30.4 4.0 101.3 12.5 25.1 9.25 6.0 112.3 10.3 31.1 5.0 102.2 10.2 25.6 13.99 7.0 113.1 9.0 31.5 600 0.5 600 2.0 97.2 27.4 27.4 1.0 86.5 41.0 20.5 0.74 3.0 101.3 20.1 30.2 2.0 92.6 24.4 24.5 2.59 4.0 103.8 15.9 31.7 3.0 95.2 17.4 26.2 5.44 5.0 105.4 13.1 32.8 4.0 96.7 13.5 27.1 9.25 6.0 106.5 11.2 33.5 5.0 97.6 11.1 27.7 14.00 7.0 107.3 9.7 34.1 700 0.5 700 2.0 92.9 28.8 28.8 1.0 83.3 43.0 21.5 0.74 3.0 96.9 21.2 31.8 2.0 89.0 25.8 25.8 2.59 4.0 99.3 16.8 33.6 3.0 91.6 18.5 27.8 5.44 5.0 100.8 13.9 34.8 4.0 93.0 14.4 28.9 9.26 6.0 101.9 11.9 35.6 5.0 93.9 11.8 29.6 14.00 7.0 102.7 10.3 36.2 800 0.5 800 2.0 89.5 29.9 30.0 1.0 80.7 44.6 22.3 0.74 3.0 93.4 22.2 33.3 2.0 86.2 27.0 27.0 2.59 4.0 95.6 17.6 35.3 3.0 88.6 19.4 29.2 5.45 5.0 97.1 14.6 36.6 4.0 90.0 15.2 30.4 9.26 6.0 98.2 12.5 37.5 5.0 90.9 12.4 31.2 14.01 7.0 99.0 10.9 38.2 900 0.5 900 2.0 86.8 31.0 31.0 1.0 78.6 46.0 23.0 0.74 3.0 90.4 23.0 34.6 2.0 83.8 28.1 28.1 2.59 4.0 92.6 18.4 36.7 3.0 86.2 20.3 30.4 5.45 5.0 94.1 15.2 38.2 4.0 87.5 15.9 31.7 9.27 6.0 95.1 13.0 39.2 5.0 88.4 13.0 32.6 14.02 7.0 95.9 11.4 39.9 1000 0.5 1000 2.0 84.5 32.0 32.0 1.0 76.8 47.2 23.6 0.74 3.0 88.0 23.8 35.8 2.0 81.8 29.1 29.1 2.59 4.0 90.1 19.0 38.1 3.0 84.1 21.0 31.5 5.45 5.0 91.6 15.8 39.6 4.0 85.4 16.5 33.0 9.27 6.0 92.6 13.6 40.7 5.0 86.2 13.5 33.9 14.02 7.0 93.3 11.9 41.6 1100 0.5 1100 2.0 82.6 32.9 32.9 1.0 75.2 48.3 24.1 0.74 3.0 85.9 24.6 36.9 2.0 80.1 29.9 29.9 2.60 4.0 88.0 19.7 39.4 3.0 82.3 21.7 32.6 5.46 5.0 89.4 16.4 41.0 4.0 83.6 17.0 34.1 9.28 6.0 90.4 14.1 42.2 5.0 84.4 14.0 35.1 14.03 7.0 91.1 12.3 43.1 Note: 1. Fouling Factor = 0.00025 2. Capacities based on 180 F entering water and 55 F entering air temperatures. See capacity correction factors at other temperature differences. 3. The following equations may be used in calculating Leaving Air Temperature (LAT) and Water Temperature Difference (WTD). WTD = EWT - LWT = 2 x MBH LAT = EAT + MBH x 921.7 CFM GPM ( ) 67 Water Pressure Drop (ft) 1.05 2.25 3.86 5.89 8.32 11.14 1.05 2.25 3.86 5.89 8.32 11.15 1.05 2.25 3.87 5.90 8.33 11.16 1.06 2.25 3.87 5.90 8.33 11.16 1.06 2.26 3.87 5.90 8.34 11.17 1.06 2.26 3.88 5.91 8.34 11.17 1.06 2.26 3.88 5.91 8.34 11.18 1.06 2.26 3.88 5.91 8.35 11.18 1.06 2.26 3.88 5.91 8.35 11.19 1.06 2.26 3.88 5.92 8.35 11.19 1.06 2.26 3.89 5.92 8.36 11.19 Performance Data Single-Duct VAV Terminal Units – VCWE Table PD-5 — Size 17 Hot Water Coil Capacity Data (MBh) Airflow (CFM) 350 450 550 650 750 850 1000 1100 1300 1500 1700 Standard Capacity Coil (STHW) with 144 Fins per foot Leaving Water Coil Water Air Temperature Capacity Pressure GPM Temperature Drop (F) (MBH) Drop (ft) 1.0 105.5 38.3 19.2 0.33 2.0 114.3 22.5 22.5 1.18 3.0 117.8 15.9 23.8 2.51 4.0 119.8 12.3 24.6 4.30 5.0 121.0 10.0 25.0 6.53 6.0 121.8 8.4 25.4 9.21 1.0 98.1 42.0 21.0 0.33 2.0 106.6 25.2 25.2 1.18 3.0 110.2 17.9 26.9 2.51 4.0 112.1 13.9 27.9 4.30 5.0 113.4 11.4 28.5 6.54 6.0 114.3 9.6 28.9 9.21 1.0 92.9 45.2 22.6 0.33 2.0 100.9 27.4 27.4 1.19 3.0 104.4 19.6 29.5 2.52 4.0 106.4 15.3 30.6 4.30 5.0 107.6 12.5 31.4 6.54 6.0 108.5 10.6 31.9 9.22 1.0 88.8 47.7 23.8 0.33 2.0 96.5 29.2 29.2 1.19 3.0 99.9 21.1 31.7 2.52 4.0 101.8 16.5 33.0 4.31 5.0 103.1 13.5 33.9 6.54 6.0 103.9 11.5 34.5 9.22 1.0 85.6 49.7 24.9 0.33 2.0 92.9 30.8 30.8 1.19 3.0 96.2 22.3 33.5 2.52 4.0 98.1 17.5 35.1 4.31 5.0 99.3 14.4 36.1 6.55 6.0 100.2 12.2 36.8 9.22 1.0 82.9 51.5 25.7 0.33 2.0 89.9 32.2 32.2 1.19 3.0 93.2 23.4 35.2 2.52 4.0 95.0 18.4 36.9 4.31 5.0 96.2 15.2 38.0 6.55 6.0 97.1 12.9 38.8 9.23 1.0 79.7 53.6 26.8 0.33 2.0 86.4 34.0 34.1 1.19 3.0 89.5 24.9 37.4 2.52 4.0 91.3 19.6 39.3 4.31 5.0 92.4 16.2 40.6 6.55 6.0 93.2 13.8 41.5 9.23 1.0 78.0 54.8 27.4 0.33 2.0 84.5 35.1 35.1 1.19 3.0 87.4 25.8 38.7 2.52 4.0 89.2 20.4 40.7 4.31 5.0 90.3 16.8 42.1 6.55 6.0 91.1 14.3 43.1 9.23 1.0 75.2 56.9 28.4 0.34 2.0 81.3 37.0 37.0 1.19 3.0 84.0 27.2 40.9 2.53 4.0 85.7 21.6 43.3 4.32 5.0 86.8 17.9 44.8 6.56 6.0 87.6 15.3 45.9 9.24 1.0 73.0 58.5 29.2 0.34 2.0 78.7 38.6 38.6 1.19 3.0 81.3 28.6 42.9 2.53 4.0 82.9 22.7 45.4 4.32 5.0 84.0 18.8 47.1 6.56 6.0 84.7 16.1 48.4 9.24 1.0 71.2 59.9 29.9 0.34 2.0 76.7 39.9 39.9 1.19 3.0 79.2 29.7 44.6 2.53 4.0 80.7 23.6 47.3 4.32 5.0 81.7 19.7 49.2 6.56 6.0 82.4 16.8 50.6 9.25 Airflow (CFM) 350 450 550 650 750 850 1000 1100 1300 1500 1700 High Capacity Coil (HIHW) with 192 Fins per foot Leaving Water Coil Air Temperature Capacity GPM Temperature Drop (F) (MBH) 2.0 121.7 25.3 25.3 6.0 137.8 10.5 31.4 10.0 141.8 6.6 33.0 14.0 143.7 4.8 33.7 18.0 144.8 3.8 34.1 20.0 145.1 3.4 34.2 2.0 113.1 28.3 28.4 6.0 130.0 12.2 36.6 10.0 134.3 7.7 38.7 14.0 136.4 5.7 39.7 18.0 137.6 4.5 40.3 20.0 138.1 4.1 40.5 2.0 106.3 30.6 30.6 6.0 123.3 13.6 40.7 10.0 127.8 8.7 43.4 14.0 130.0 6.4 44.7 18.0 131.3 5.0 45.5 20.0 131.7 4.6 45.8 2.0 100.9 32.3 32.3 6.0 117.6 14.7 44.1 10.0 122.2 9.5 47.3 14.0 124.4 7.0 48.9 18.0 125.7 5.5 49.8 20.0 126.2 5.0 50.2 2.0 96.5 33.7 33.7 6.0 112.7 15.6 46.9 10.0 117.3 10.1 50.7 14.0 119.5 7.5 52.5 18.0 120.9 5.9 53.6 20.0 121.4 5.4 54.0 2.0 92.9 34.9 34.9 6.0 108.6 16.4 49.4 10.0 113.1 10.7 53.6 14.0 115.4 7.9 55.6 18.0 116.7 6.3 56.9 20.0 117.2 5.7 57.3 2.0 88.5 36.4 36.4 6.0 103.4 17.5 52.5 10.0 107.9 11.5 57.3 14.0 110.1 8.5 59.7 18.0 111.4 6.8 61.2 20.0 111.9 6.2 61.7 2.0 86.2 37.2 37.2 6.0 100.5 18.1 54.3 10.0 104.9 11.9 59.5 14.0 107.1 8.9 62.1 18.0 108.4 7.1 63.7 20.0 108.9 6.4 64.3 2.0 82.4 38.6 38.6 6.0 95.8 19.1 57.5 10.0 100.0 12.7 63.4 14.0 102.1 9.5 66.4 18.0 103.4 7.6 68.2 20.0 103.8 6.9 68.8 2.0 79.4 39.8 39.8 6.0 92.0 20.1 60.2 10.0 96.0 13.3 66.8 14.0 98.1 10.0 70.1 18.0 99.3 8.0 72.1 20.0 99.8 7.3 72.9 2.0 77.1 40.7 40.7 6.0 89.0 20.9 62.6 10.0 92.9 13.9 69.8 14.0 94.9 10.5 73.5 18.0 96.1 8.4 75.7 20.0 96.5 7.6 76.5 Note: 1. Fouling Factor = 0.00025 2. Capacities based on 180 F entering water and 55 F entering air temperatures. See capacity correction factors at other temperature differences. 3. The following equations may be used in calculating Leaving Air Temperature (LAT) and Water Temperature Difference (WTD). WTD = EWT - LWT = 2 x MBH LAT = EAT + MBH x 921.7 CFM GPM ( ) 68 Water Pressure Drop (ft) 0.22 1.82 4.94 9.55 15.63 19.23 0.22 1.82 4.94 9.55 15.63 19.23 0.22 1.82 4.94 9.55 15.63 19.23 0.22 1.82 4.94 9.55 15.64 19.23 0.22 1.82 4.94 9.55 15.64 19.23 0.22 1.82 4.94 9.55 15.64 19.23 0.22 1.82 4.94 9.55 15.64 19.23 0.22 1.82 4.94 9.55 15.64 19.23 0.22 1.82 4.94 9.55 15.64 19.24 0.22 1.82 4.94 9.55 15.64 19.24 0.22 1.82 4.94 9.55 15.64 19.24 Performance Data Single-Duct VAV Terminal Units – VCWE Table PD-6 — Size 24 Hot Water Coil Capacity Data (MBh) Airflow (CFM) 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 Standard Capacity Coil (STHW) with 144 Fins per foot Leaving Water Coil Air Temperature Capacity GPM Temperature Drop (F) (MBH) 1.0 107.1 45.2 22.6 2.0 116.9 26.8 26.9 3.0 120.9 19.0 28.6 4.0 123.1 14.8 29.5 5.0 124.5 12.0 30.1 6.0 125.4 10.2 30.6 1.0 95.5 52.7 26.3 2.0 104.5 32.2 32.2 3.0 108.5 23.2 34.8 4.0 110.7 18.1 36.2 5.0 112.1 14.9 37.2 6.0 113.1 12.6 37.8 1.0 88.2 57.7 28.8 2.0 96.5 36.0 36.0 3.0 100.4 26.2 39.4 4.0 102.6 20.6 41.3 5.0 104.0 17.0 42.5 6.0 105.0 14.4 43.4 1.0 2.0 91.1 39.1 39.1 3.0 94.7 28.7 43.0 4.0 96.8 22.6 45.3 5.0 98.2 18.7 46.8 6.0 99.1 15.9 47.9 1.0 2.0 87.0 41.6 41.6 3.0 90.4 30.7 46.0 4.0 92.4 24.3 48.7 5.0 93.7 20.1 50.4 6.0 94.7 17.2 51.6 1.0 2.0 83.8 43.7 43.7 3.0 87.0 32.4 48.6 4.0 88.9 25.7 51.5 5.0 90.2 21.4 53.5 6.0 91.2 18.3 54.9 1.0 2.0 81.2 45.5 45.5 3.0 84.3 33.9 50.8 4.0 86.1 27.0 54.0 5.0 87.4 22.5 56.2 6.0 88.3 19.2 57.8 1.0 2.0 79.1 47.0 47.0 3.0 82.1 35.2 52.8 4.0 83.8 28.1 56.2 5.0 85.0 23.4 58.6 6.0 85.9 20.1 60.3 1.0 2.0 77.3 48.4 48.4 3.0 80.2 36.4 54.6 4.0 81.9 29.1 58.3 5.0 83.0 24.3 60.8 6.0 83.9 20.9 62.6 1.0 2.0 75.8 49.6 49.6 3.0 78.6 37.5 56.2 4.0 80.2 30.0 60.1 5.0 81.3 25.1 62.7 6.0 82.1 21.5 64.7 1.0 2.0 74.5 50.6 50.6 3.0 77.1 38.4 57.6 4.0 78.7 30.9 61.8 5.0 79.8 25.8 64.6 6.0 80.6 22.2 66.6 Water Pressure Drop (ft) 0.37 1.31 2.78 4.74 7.18 10.10 0.37 1.32 2.78 4.74 7.19 10.11 0.37 1.32 2.79 4.75 7.20 10.12 Airflow (CFM) 400 600 800 1000 1.32 2.79 4.75 7.20 10.12 1200 1.32 2.79 4.76 7.21 10.13 1400 1.33 2.79 4.76 7.21 10.14 1600 1.33 2.80 4.76 7.22 10.14 1800 1.33 2.80 4.77 7.22 10.15 2000 1.33 2.80 4.77 7.22 10.15 2200 1.33 2.80 4.77 7.23 10.16 2400 1.33 2.80 4.77 7.23 10.16 High Capacity Coil (HIHW) with 192 Fins per foot Leaving Water Coil Air Temperature Capacity GPM Temperature Drop (F) (MBH) 2.0 123.1 29.5 29.5 6.0 139.7 12.2 36.7 10.0 143.7 7.7 38.5 14.0 145.6 5.6 39.3 18.0 146.7 4.4 39.8 20.0 147.1 4.0 40.0 2.0 109.6 35.5 35.5 6.0 127.6 15.7 47.2 10.0 132.3 10.1 50.3 14.0 134.6 7.4 51.8 18.0 135.9 5.8 52.6 20.0 136.4 5.3 53.0 2.0 100.2 39.2 39.2 6.0 118.0 18.2 54.6 10.0 122.9 11.8 58.9 14.0 125.3 8.7 61.0 18.0 126.7 6.9 62.2 20.0 127.2 6.3 62.7 2.0 93.6 41.9 41.9 6.0 110.5 20.0 60.2 10.0 115.4 13.1 65.5 14.0 117.8 9.7 68.1 18.0 119.3 7.7 69.7 20.0 119.8 7.0 70.3 2.0 88.8 43.9 43.9 6.0 104.6 21.5 64.6 10.0 109.4 14.2 70.8 14.0 111.8 10.6 73.9 18.0 113.3 8.4 75.8 20.0 113.8 7.6 76.5 2.0 85.0 45.5 45.5 6.0 99.9 22.7 68.2 10.0 104.6 15.0 75.3 14.0 106.9 11.3 78.8 18.0 108.3 9.0 81.0 20.0 108.9 8.2 81.8 2.0 81.9 46.8 46.7 6.0 96.1 23.8 71.3 10.0 100.6 15.8 79.2 14.0 102.9 11.9 83.1 18.0 104.3 9.5 85.5 20.0 104.8 8.6 86.4 2.0 79.5 47.8 47.8 6.0 92.9 24.7 74.1 10.0 97.3 16.5 82.6 14.0 99.5 12.4 86.9 18.0 100.9 9.9 89.6 20.0 101.4 9.0 90.5 2.0 77.5 48.7 48.7 6.0 90.3 25.5 76.5 10.0 94.5 17.1 85.7 14.0 96.7 12.9 90.4 18.0 98.0 10.4 93.3 20.0 98.5 9.4 94.3 2.0 75.7 49.5 49.5 6.0 88.0 26.2 78.7 10.0 92.1 17.7 88.5 14.0 94.2 13.4 93.6 18.0 95.5 10.7 96.7 20.0 96.0 9.8 97.8 2.0 74.3 50.3 50.3 6.0 86.0 26.9 80.8 10.0 90.0 18.2 91.2 14.0 92.1 13.8 96.6 18.0 93.4 11.1 99.9 20.0 93.9 10.1 101.1 Note: 1. Fouling Factor = 0.00025 2. Capacities based on 180 F entering water and 55 F entering air temperatures. See capacity correction factors at other temperature differences. 3. The following equations may be used in calculating Leaving Air Temperature (LAT) and Water Temperature Difference (WTD). WTD = EWT - LWT = 2 x MBH LAT = EAT + MBH x 921.7 CFM GPM ( ) 69 Water Pressure Drop (ft) 0.23 1.90 5.13 9.90 16.18 19.88 0.23 1.90 5.13 9.90 16.18 19.89 0.23 1.90 5.13 9.90 16.18 19.89 0.23 1.90 5.13 9.90 16.18 19.89 0.23 1.90 5.13 9.90 16.19 19.89 0.23 1.90 5.14 9.90 16.19 19.90 0.23 1.90 5.14 9.90 16.19 19.90 0.23 1.90 5.14 9.90 16.19 19.90 0.23 1.90 5.14 9.91 16.19 19.90 0.23 1.90 5.14 9.91 16.19 19.90 0.23 1.90 5.14 9.91 16.20 19.91 Performance Data Single-Duct VAV Terminal Units – VCWE Table PD-7 — Size 32 Hot Water Coil Capacity Data (MBh) Airflow (CFM) 700 900 1100 1300 1500 1700 2000 2300 2600 2900 3200 Standard Capacity Coil (STHW) with 144 Fins per foot Leaving Water Coil Air Temperature Capacity GPM Temperature Drop (F) (MBH) 0.7 2.0 110.1 41.8 41.8 4.0 118.8 24.2 48.4 6.0 122.2 17.0 51.0 8.0 124.1 13.1 52.5 10.0 125.3 10.7 53.4 0.7 2.0 102.3 46.2 46.2 4.0 110.9 27.3 54.6 6.0 114.4 19.3 58.0 8.0 116.3 15.0 59.9 10.0 117.6 12.2 61.1 0.7 2.0 96.9 50.0 50.0 4.0 105.0 29.8 59.6 6.0 108.5 21.2 63.8 8.0 110.4 16.5 66.1 10.0 111.6 13.5 67.5 0.7 2.0 92.6 53.1 53.0 4.0 100.3 31.9 63.9 6.0 103.7 22.9 68.7 8.0 105.6 17.8 71.4 10.0 106.9 14.6 73.1 0.7 2.0 89.1 55.6 55.5 4.0 96.5 33.8 67.5 6.0 99.9 24.3 73.0 8.0 101.8 19.0 76.1 10.0 103.0 15.6 78.0 0.7 2.0 86.3 57.7 57.6 4.0 93.4 35.4 70.7 6.0 96.7 25.6 76.8 8.0 98.5 20.0 80.2 10.0 99.7 16.5 82.4 0.7 2.0 4.0 89.6 37.5 75.0 6.0 92.7 27.2 81.8 8.0 94.5 21.4 85.7 10.0 95.7 17.6 88.2 0.7 2.0 4.0 86.6 39.4 78.7 6.0 89.5 28.7 86.1 8.0 91.3 22.6 90.4 10.0 92.4 18.6 93.3 0.7 2.0 4.0 84.1 41.0 82.0 6.0 86.9 29.9 89.9 8.0 88.6 23.6 94.7 10.0 89.7 19.5 97.8 0.7 2.0 4.0 82.0 42.4 84.8 6.0 84.7 31.1 93.3 8.0 86.3 24.6 98.4 10.0 87.4 20.3 101.8 0.7 2.0 4.0 80.2 43.7 87.3 6.0 82.8 32.1 96.5 8.0 84.3 25.4 101.8 10.0 85.4 21.1 105.5 Water Pressure Drop (ft) Airflow (CFM) 700 1.14 4.14 8.87 15.29 23.36 900 1.14 4.14 8.88 15.30 23.37 1100 1.14 4.14 8.88 15.31 23.38 1300 1.14 4.15 8.89 15.31 23.39 1500 1.14 4.15 8.89 15.32 23.39 1700 1.14 4.15 8.90 15.32 23.40 2000 4.15 8.90 15.33 23.41 2300 4.16 8.90 15.34 23.42 2600 4.16 8.91 15.34 23.43 2900 4.16 8.91 15.35 23.43 3200 4.17 8.92 15.35 23.44 High Capacity Coil (HIHW) with 192 Fins per foot Leaving Water Coil Air Temperature Capacity GPM Temperature Drop (F) (MBH) 5.0 130.5 22.9 57.3 9.0 137.5 13.9 62.6 13.0 140.5 10.0 64.9 17.0 142.2 7.8 66.2 21.0 143.3 6.4 67.0 23.0 143.7 5.8 67.3 5.0 122.2 26.2 65.6 9.0 129.6 16.2 72.8 13.0 132.8 11.7 76.0 17.0 134.7 9.1 77.8 21.0 135.9 7.5 79.0 23.0 136.4 6.9 79.4 5.0 115.3 28.8 72.0 9.0 122.8 18.0 80.9 13.0 126.2 13.1 85.0 17.0 128.2 10.3 87.3 21.0 129.5 8.4 88.8 23.0 129.9 7.8 89.4 5.0 109.7 30.8 77.1 9.0 117.1 19.4 87.6 13.0 120.6 14.2 92.4 17.0 122.5 11.2 95.2 21.0 123.9 9.2 97.1 23.0 124.4 8.5 97.8 5.0 105.0 32.5 81.3 9.0 112.3 20.7 93.2 13.0 115.7 15.2 98.8 17.0 117.7 12.0 102.0 21.0 119.0 9.9 104.1 23.0 119.5 9.1 105.0 5.0 101.0 33.9 84.8 9.0 108.2 21.8 98.1 13.0 111.6 16.0 104.3 17.0 113.5 12.7 107.9 21.0 114.8 10.5 110.3 23.0 115.3 9.7 111.3 5.0 96.2 35.7 89.3 9.0 103.1 23.2 104.3 13.0 106.4 17.1 111.4 17.0 108.3 13.6 115.6 21.0 109.6 11.3 118.4 23.0 110.1 10.4 119.5 5.0 92.3 37.2 93.1 9.0 98.9 24.3 109.5 13.0 102.1 18.1 117.5 17.0 104.0 14.4 122.2 21.0 105.3 11.9 125.4 23.0 105.8 11.0 126.6 5.0 89.3 38.6 96.6 9.0 95.5 25.4 114.2 13.0 98.6 18.9 122.9 17.0 100.4 15.1 128.1 21.0 101.7 12.5 131.6 23.0 102.2 11.5 133.0 5.0 86.7 39.8 99.6 9.0 92.6 26.3 118.3 13.0 95.6 19.6 127.8 17.0 97.4 15.7 133.5 21.0 98.7 13.1 137.3 23.0 99.1 12.1 138.8 5.0 84.5 40.9 102.3 9.0 90.2 27.1 122.1 13.0 93.1 20.3 132.3 17.0 94.9 16.3 138.4 21.0 96.1 13.6 142.5 23.0 96.5 12.5 144.1 Note: 1. Fouling Factor = 0.00025 2. Capacities based on 180 F entering water and 55 F entering air temperatures. See capacity correction factors at other temperature differences. 3. The following equations may be used in calculating Leaving Air Temperature (LAT) and Water Temperature Difference (WTD). WTD = EWT - LWT = 2 x MBH LAT = EAT + MBH x 921.7 CFM GPM ( ) 70 Water Pressure Drop (ft) 1.23 3.83 7.83 13.20 19.94 23.82 1.23 3.83 7.83 13.20 19.95 23.83 1.23 3.83 7.83 13.21 19.95 23.83 1.23 3.83 7.83 13.21 19.95 23.83 1.23 3.83 7.83 13.21 19.95 23.83 1.23 3.83 7.83 13.21 19.95 23.83 1.23 3.83 7.83 13.21 19.95 23.84 1.23 3.84 7.83 13.21 19.96 23.84 1.23 3.84 7.84 13.21 19.96 23.84 1.23 3.84 7.84 13.22 19.96 23.84 1.23 3.84 7.84 13.22 19.96 23.85 Performance Data Single-Duct VAV Terminal Units – VCWE Table PD-8 — Size 42 Hot Water Coil Capacity Data (MBh) Airflow (CFM) 900 1200 1500 1800 2000 2400 2800 3200 3600 4000 4200 Standard Capacity Coil (STHW) with 144 Fins per foot Leaving Water Coil Air Temperature Capacity GPM Temperature Drop (F) (MBH) 0.7 2.0 102.8 46.7 46.7 4.0 111.4 27.5 55.0 6.0 114.9 19.5 58.4 8.0 116.8 15.1 60.3 10.0 118.0 12.3 61.5 0.7 2.0 95.1 52.2 52.2 4.0 103.0 31.2 62.4 6.0 106.4 22.3 66.9 8.0 108.3 17.3 69.4 10.0 109.5 14.2 71.0 0.7 2.0 89.6 56.3 56.2 4.0 96.9 34.1 68.2 6.0 100.3 24.6 73.7 8.0 102.2 19.2 76.8 10.0 103.4 15.7 78.7 0.7 2.0 85.4 59.4 59.3 4.0 92.4 36.5 73.0 6.0 95.7 26.4 79.4 8.0 97.5 20.7 82.9 10.0 98.7 17.0 85.2 0.7 2.0 4.0 90.0 37.9 75.9 6.0 93.1 27.5 82.7 8.0 94.9 21.6 86.6 10.0 96.1 17.8 89.1 0.7 2.0 4.0 86.1 40.4 80.9 6.0 89.0 29.5 88.4 8.0 90.7 23.2 92.9 10.0 91.8 19.2 95.9 0.7 2.0 4.0 83.0 42.5 85.0 6.0 85.7 31.1 93.3 8.0 87.4 24.6 98.4 10.0 88.5 20.3 101.7 0.7 2.0 4.0 80.5 44.3 88.5 6.0 83.2 32.6 97.7 8.0 84.7 25.8 103.2 10.0 85.8 21.3 106.8 0.7 2.0 4.0 78.5 45.8 91.6 6.0 81.0 33.9 101.6 8.0 82.5 26.8 107.4 10.0 83.5 22.3 111.4 0.7 2.0 4.0 76.7 47.1 94.2 6.0 79.2 35.0 105.0 8.0 80.6 27.8 111.2 10.0 81.6 23.1 115.4 0.7 2.0 4.0 76.0 47.7 95.5 6.0 78.4 35.5 106.6 8.0 79.8 28.2 113.1 10.0 80.8 23.5 117.3 Water Pressure Drop (ft) Airflow (CFM) 900 1.14 4.14 8.87 15.30 23.36 1200 1.14 4.14 8.88 15.30 23.38 1500 1.14 4.15 8.89 15.31 23.39 1800 1.14 4.15 8.89 15.32 23.40 2000 4.15 8.90 15.32 23.40 2400 4.16 8.90 15.33 23.41 2800 4.16 8.91 15.34 23.42 3200 4.16 8.91 15.35 23.43 3600 4.17 8.92 15.35 23.44 4000 4.17 8.92 15.36 23.45 4200 4.17 8.92 15.36 High Capacity Coil (HIHW) with 192 Fins per foot Leaving Water Coil Air Temperature Capacity GPM Temperature Drop (F) (MBH) 5.0 122.6 26.4 66.0 9.0 129.8 16.2 73.0 13.0 133.0 11.7 76.2 17.0 134.9 9.2 77.9 21.0 136.0 7.5 79.1 23.0 136.5 6.9 79.5 5.0 113.1 30.2 75.6 9.0 120.5 18.9 85.2 13.0 123.9 13.8 89.6 17.0 125.8 10.8 92.2 21.0 127.1 8.9 93.8 23.0 127.6 8.2 94.5 5.0 105.8 33.0 82.6 9.0 113.1 21.0 94.5 13.0 116.5 15.4 100.0 17.0 118.5 12.1 103.3 21.0 119.8 10.0 105.4 23.0 120.3 9.2 106.2 5.0 100.1 35.2 88.0 9.0 107.2 22.6 101.8 13.0 110.5 16.7 108.4 17.0 112.5 13.2 112.2 21.0 113.8 10.9 114.8 23.0 114.3 10.1 115.7 5.0 97.0 36.4 91.0 9.0 103.9 23.5 106.0 13.0 107.2 17.4 113.2 17.0 109.1 13.8 117.4 21.0 110.4 11.4 120.2 23.0 110.9 10.5 121.2 5.0 91.9 38.4 96.1 9.0 98.5 25.1 113.1 13.0 101.6 18.7 121.4 17.0 103.5 14.8 126.3 21.0 104.8 12.3 129.5 23.0 105.2 11.4 130.8 5.0 88.1 40.2 100.5 9.0 94.2 26.4 119.0 13.0 97.3 19.7 128.3 17.0 99.1 15.7 133.8 21.0 100.3 13.1 137.5 23.0 100.8 12.1 138.9 5.0 85.0 41.7 104.3 9.0 90.8 27.6 124.2 13.0 93.7 20.7 134.4 17.0 95.5 16.5 140.5 21.0 96.7 13.8 144.6 23.0 97.1 12.7 146.2 5.0 82.5 43.0 107.5 9.0 88.0 28.6 128.8 13.0 90.8 21.5 139.8 17.0 92.5 17.2 146.5 21.0 93.7 14.4 151.0 23.0 94.1 13.3 152.7 5.0 80.4 44.1 110.3 9.0 85.7 29.5 133.0 13.0 88.4 22.3 144.8 17.0 90.1 17.9 152.0 21.0 91.2 14.9 156.9 23.0 91.6 13.8 158.8 5.0 79.5 44.7 111.6 9.0 84.6 30.0 135.0 13.0 87.3 22.6 147.2 17.0 89.0 18.2 154.7 21.0 90.1 15.2 159.7 23.0 90.5 14.0 161.7 Note: 1. Fouling Factor = 0.00025 2. Capacities based on 180 F entering water and 55 F entering air temperatures. See capacity correction factors at other temperature differences. 3. The following equations may be used in calculating Leaving Air Temperature (LAT) and Water Temperature Difference (WTD). WTD = EWT - LWT = 2 x MBH LAT = EAT + MBH x 921.7 CFM GPM ( ) 71 Water Pressure Drop (ft) 1.23 3.83 7.83 13.20 19.94 23.82 1.23 3.83 7.83 13.20 19.95 23.83 1.23 3.83 7.83 13.21 19.95 23.83 1.23 3.83 7.83 13.21 19.95 23.83 1.23 3.83 7.83 13.21 19.95 23.83 1.23 3.83 7.83 13.21 19.95 23.83 1.23 3.84 7.83 13.21 19.96 23.84 1.23 3.84 7.84 13.21 19.96 23.84 1.23 3.84 7.84 13.22 19.96 23.84 1.23 3.84 7.84 13.22 19.96 23.85 1.23 3.84 7.84 13.22 19.96 23.85 Performance Data Single-Duct VAV Terminal Units – VCWE Table PD-9 — Temperature Correction Factors for Water Pressure Drop (WPD) Average Water Temperature Correction Factor 200 .97 190 .985 180 1.0 170 1.02 160 1.03 150 1.05 140 1.08 130 1.1 120 1.13 110 1.15 100 1.18 80 0.722 90 0.814 100 0.907 110 1.000 120 1.093 Table PD-10 — Temperature Difference Correction Factors for Coil Capacity (MBH) Entering Water Minus Entering Air Correction Factor 20 0.176 30 0.265 40 0.355 50 0.446 60 0.537 70 0.629 130 1.187 Coils – Water Weights Unit Type VCWE VCWE VCWE VCWE VCWE VCWE VCWE VCWE VCWE VCWE VCWE VCWE VCWE VCWE Unit Size 03 06 11 17 24 32 42 03 06 11 17 24 32 42 Coil Type STHW STHW STHW STHW STHW STHW STHW HIHW HIHW HIHW HIHW HIHW HIHW HIHW # Hairpins 5 5 6 6 6 8 8 4 4 6 8 8 9 9 # Returns 4 4 4 3 3 4 4 2 2 3 0 0 0 0 # Headers 0 0 2 2 2 2 2 2 2 2 2 2 2 2 # Circuits 1 1 2 3 3 4 4 2 2 3 8 8 9 9 72 LeqHairpin 27.571 27.571 33.571 45.821 58.821 76.071 76.071 27.571 27.571 33.571 45.821 58.821 76.071 76.071 IdHeader 0 0 0.785 0.785 0.785 0.785 0.785 0.785 0.785 0.785 1.025 1.025 1.025 1.025 LHeader 0 0 7 11 11 15 15 7 7 9 15 15 17 17 Internal Volume (Cu. In.) 14.73 14.73 28.69 40.31 48.34 78.98 78.98 19.04 19.04 30.81 65.06 75.76 101.41 101.41 Internal Volume (Gal.) 0.064 0.064 0.124 0.175 0.209 0.342 0.342 0.082 0.082 0.133 0.282 0.328 0.439 0.439 Water Weight (Lbs.) 0.531 0.531 1.034 1.454 1.743 2.848 2.848 0.687 0.687 1.111 2.346 2.732 3.657 3.657 Performance Data Single-Duct VAV Terminal Units – VCEE Table PD-11 — VCEE Size 03 Single-Duct VAV Terminal Unit Electric Heater kW Guidelines Voltage 208/60/1 240/60/1 277/60/1 347/60/1 480/60/1 575/60/1 208/60/3 480/60/3 575/60/3 Stage(s) 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 Min. kW 0.5 0.5 1.0 0.5 0.5 1.0 0.5 0.5 1.0 0.5 0.5 — 0.5 1.0 — 1.0 — — 0.5 0.5 1.0 1.0 1.0 — — — — 60 CFM through 89 CFM — — — — — — — — — — — — — — — — — — — — — — — — — — — Maximum kW allowed at each of the following Airflows (CFM) 90 CFM 120 CFM through through 119 CFM 149 CFM 0.5 1.0 0.5 1.0 — 1.0 0.5 1.0 0.5 1.0 — 1.0 0.5 1.0 0.5 1.0 — 1.0 0.5 1.0 0.5 1.0 — — 0.5 1.0 — 1.0 — — — 1.0 — — — — 0.5 1.0 0.5 1.0 — 1.0 — 1.0 — 1.0 — — — — — — — — Greater than 150 CFM 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 — 1.5 1.5 — 1.5 1.5 — 1.5 1.5 1.5 1.5 1.5 — 1.5 1.5 — Notes: 1. Adequate airflow over heater is necessary. As kW requirements increase, so must minimum airflow. The above chart indicates the minimum cfm required for each kW range. 2. Coils available with electric, electric with mercury contactors, pneumatic-electric switches and pneumatic-electric switches with mercury contactors. 3. Available kW increments are by 0.5 kW from 0.5 to 8.0 kW, by 1.0 kW from 9.0 to 17.0 kW and by 2.0 kW from 18.0 to 22.0 kW. 4. Each stage will be equal in kW output. 5. Single-stage and single-phase heaters are always balanced. On three-phase heaters the lineload is unbalanced. 6. Current draw for devices is as follows. Electric actuators each draw 1.0 amp. The contactor for each stage of heat draws 0.5 amp. The current draw for the heater elements is calculated by one of the formulas below. 7. Minimum circuit ampacity is equal to 1.25 times the total current draw for the unit. 8. Overcurrent protective devices shall be rated for 2.25 times the total current draw of the unit Useful Formulas kW = CFM x ATD 3145 1 Φ amps = ATD = kW x 3145 CFM kW x 1000 Primary Voltage 3 Φ amps = kW x 1000 Primary Voltage x √ 3 Example: A Model VCEE, electric unit heat size 03 terminal unit has 480/3 phase 1.0 kW electric heat with 3 stages. Electric Actuator = .5 Amps DDC UCM or Analog Electronic Control Board = .5 Amps 1.0 kW 3-phase heater 1.0 x 1000 480 x 1.73 Three heat outputs (at .5 amps max each) = 1.2 Amps = 1.5 Amps 3.7 Amps Max 73 Performance Data Single-Duct VAV Terminal Units – VCEE Table PD-12 — VCEE Size 06 Single-Duct VAV Terminal Unit Electric Heater kW Guidelines Voltage 208/60/1 240/60/1 277/60/1 347/60/1 480/60/1 575/60/1 208/60/3 480/60/3 575/60/3 Stage(s) 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 Min. kW 0.5 0.5 1.0 0.5 0.5 1.0 0.5 0.5 1.0 0.5 0.5 2.0 0.5 1.0 — 1.0 1.5 — 0.5 0.5 1.0 1.0 1.0 3.0 1.5 1.5 — 120 CFM through 179 CFM 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 — 1.0 1.0 — 1.0 — — 1.0 1.0 1.0 1.0 1.0 — — — — Maximum kW allowed at each of the following Airflows (CFM) 180 CFM 240 CFM through through 239 CFM 299 CFM 2.5 3.5 2.5 3.5 2.5 3.5 2.5 3.5 2.5 3.5 2.5 3.5 2.5 3.5 2.5 3.5 2.5 3.5 2.5 3.5 2.5 3.5 2.5 3.5 2.5 3.5 2.5 3.5 — — 2.5 3.5 2.5 3.5 — — 2.5 3.5 2.5 3.5 2.5 3.5 2.5 3.5 2.5 3.5 — 3.5 2.5 3.5 2.5 3.5 — — Greater than 300 CFM 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 — 4.0 4.0 — 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 — Notes: 1. Adequate airflow over heater is necessary. As kW requirements increase, so must minimum airflow. The above chart indicates the minimum cfm required for each kW range. 2. Coils available with electric, electric with mercury contactors, pneumatic-electric switches and pneumatic-electric switches with mercury contactors. 3. Available kW increments are by 0.5 kW from 0.5 to 8.0 kW, by 1.0 kW from 9.0 to 17.0 kW and by 2.0 kW from 18.0 to 22.0 kW. 4. Each stage will be equal in kW output. 5. Single-stage and single-phase heaters are always balanced. On three-phase heaters the lineload is unbalanced. 6. Current draw for devices is as follows. Electric actuators each draw 1.0 amp. The contactor for each stage of heat draws 0.5 amp. The current draw for the heater elements is calculated by one of the formulas below. 7. Minimum circuit ampacity is equal to 1.25 times the total current draw for the unit. 8. Overcurrent protective devices shall be rated for 2.25 times the total current draw of the unit Useful Formulas kW = CFM x ATD 3145 1 Φ amps = ATD = kW x 3145 CFM kW x 1000 Primary Voltage 3 Φ amps = kW x 1000 Primary Voltage x √ 3 Example: A Model VCEE, electric unit heat size 06 terminal unit has 480 / 3 phase 3.0 kW electric heat with 3 stages. Electric Actuator = .5 Amps DDC UCM or Analog Electronic Control Board = .5 Amps 3.0 kW 3-phase heater 3.0 x 1000 480 x 1.73 Three heat outputs (at .5 amps max each) = 3.6 Amps = 1.5 Amps 6.1 Amps Max 74 Performance Data Single-Duct VAV Terminal Units – VCEE Table PD-13 — VCEE Size 11 Single-Duct VAV Terminal Unit Electric Heater kW Guidelines Voltage 08/60/1 240/60/1 277/60/1 347/60/1 480/60/1 575/60/1 208/60/3 480/60/3 575/60/3 Stage(s) 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 Min. kW 0.5 0.5 1.0 0.5 0.5 1.0 0.5 0.5 1.0 0.5 0.5 1.0 0.5 1.0 2.0 0.5 1.0 2.5 0.5 0.5 1.0 1.0 1.0 2.0 1.0 1.0 2.5 220 CFM through 329 CFM 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 Maximum kW allowed at each of the following Airflows (CFM) 330 CFM 440 CFM through through 439 CFM 549 CFM 5.5 7.5 5.5 7.5 5.5 7.5 5.5 7.5 5.5 7.5 5.5 7.5 5.5 7.5 5.5 7.5 5.5 7.5 5.5 7.5 5.5 7.5 5.5 7.5 5.5 7.5 5.5 7.5 5.5 7.5 5.5 7.5 5.5 7.5 5.5 7.5 5.5 7.5 5.5 7.5 5.5 7.5 5.5 7.5 5.5 7.5 5.5 7.5 5.5 7.5 5.5 7.5 5.5 7.5 Greater than 550 CFM 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 9.0 Notes: 1. Adequate airflow over heater is necessary. As kW requirements increase, so must minimum airflow. The above chart indicates the minimum cfm required for each kW range. 2. Coils available with electric, electric with mercury contactors, pneumatic-electric switches and pneumatic-electric switches with mercury contactors. 3. Available kW increments are by 0.5 kW from 0.5 to 8.0 kW, by 1.0 kW from 9.0 to 17.0 kW and by 2.0 kW from 18.0 to 22.0 kW. 4. Each stage will be equal in kW output. 5. Single-stage and single-phase heaters are always balanced. On three-phase heaters the lineload is unbalanced. 6. Current draw for devices is as follows. Electric actuators each draw 1.0 amp. The contactor for each stage of heat draws 0.5 amp. The current draw for the heater elements is calculated by one of the formulas below. 7. Minimum circuit ampacity is equal to 1.25 times the total current draw for the unit. 8. Overcurrent protective devices shall be rated for 2.25 times the total current draw of the unit Useful Formulas kW = CFM x ATD 3145 1 Φ amps = ATD = kW x 3145 CFM kW x 1000 Primary Voltage 3 Φ amps = kW x 1000 Primary Voltage x √ 3 Example: A Model VCEE, electric unit heat size 11 terminal unit has 480 / 3 phase 5.0 kW electric heat with 3 stages. Electric Actuator = .5 Amps DDC UCM or Analog Electronic Control Board = .5 Amps 5.0 kW 3-phase heater 5.0 x 1000 480 x 1.73 Three heat outputs (at .5 amps max each) = 6.0 Amps = 1.5 Amps 8.5 Amps Max 75 Performance Data Single-Duct VAV Terminal Units – VCEE Table PD-14 — VCEE Size 17 Single-Duct VAV Terminal Unit Electric Heater kW Guidelines Voltage 208/60/1 240/60/1 277/60/1 347/60/1 480/60/1 575/60/1 208/60/3 480/60/3 575/60/3 Stage(s) 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 Min. kW 0.5 0.5 1.0 0.5 0.5 1.0 0.5 0.5 1.0 0.5 0.5 1.0 0.5 0.5 1.0 0.5 0.5 1.5 0.5 0.5 1.0 0.5 0.5 1.0 0.5 0.5 1.5 340 CFM through 509 CFM 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 Maximum kW allowed at each of the following Airflows (CFM) 510 CFM 680 CFM through through 679 CFM 849 CFM 7.5 9.0 7.5 9.0 7.5 9.0 7.5 9.0 7.5 9.0 7.5 9.0 7.5 9.0 7.5 9.0 7.5 9.0 7.5 9.0 7.5 9.0 7.5 9.0 7.5 9.0 7.5 9.0 7.5 9.0 7.5 9.0 7.5 9.0 7.5 9.0 7.5 9.0 7.5 9.0 7.5 9.0 7.5 9.0 7.5 9.0 7.5 9.0 7.5 9.0 7.5 9.0 7.5 9.0 Greater than 850 CFM 9.0 9.0 9.0 11.0 11.0 11.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 12.0 Notes: 1. Adequate airflow over heater is necessary. As kW requirements increase, so must minimum airflow. The above chart indicates the minimum cfm required for each kW range. 2. Coils available with electric, electric with mercury contactors, pneumatic-electric switches and pneumatic-electric switches with mercury contactors. 3. Available kW increments are by 0.5 kW from 0.5 to 8.0 kW, by 1.0 kW from 9.0 to 17.0 kW and by 2.0 kW from 18.0 to 22.0 kW. 4. Each stage will be equal in kW output. 5. Single-stage and single-phase heaters are always balanced. On three-phase heaters the lineload is unbalanced. 6. Current draw for devices is as follows. Electric actuators each draw 1.0 amp. The contactor for each stage of heat draws 0.5 amp. The current draw for the heater elements is calculated by one of the formulas below. 7. Minimum circuit ampacity is equal to 1.25 times the total current draw for the unit. 8. Overcurrent protective devices shall be rated for 2.25 times the total current draw of the unit Useful Formulas kW = CFM x ATD 3145 1 Φ amps = ATD = kW x 3145 CFM kW x 1000 Primary Voltage 3 Φ amps = kW x 1000 Primary Voltage x √ 3 Example: A Model VCEE, electric unit heat size 17 terminal unit has 480 / 3 phase 5.0 kW electric heat with 3 stages. Electric Actuator = .5 Amps DDC UCM or Analog Electronic Control Board = .5 Amps 5.0 kW 3-phase heater 5.0 x 1000 480 x 1.73 Three heat outputs (at .5 amps max each) = 6.0 Amps = 1.5 Amps 8.5 Amps Max 76 Performance Data Single-Duct VAV Terminal Units – VCEE Table PD-15 — VCEE Size 24 Single-Duct VAV Terminal Unit Electric Heater kW Guidelines Voltage 208/60/1 240/60/1 277/60/1 347/60/1 480/60/1 575/60/1 208/60/3 480/60/3 575/60/3 Stage(s) 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 Min. kW 0.5 0.5 1.0 0.5 0.5 1.0 0.5 0.5 1.0 0.5 0.5 1.0 0.5 0.5 1.0 0.5 0.5 1.0 0.5 0.5 1.0 0.5 0.5 1.0 0.5 0.5 1.0 480 CFM through 719 CFM 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 Maximum kW allowed at each of the following Airflows (CFM) 720 CFM 960 CFM through through 959 CFM 1199 CFM 9.0 9.0 9.0 9.0 9.0 9.0 11.0 11.0 11.0 11.0 11.0 11.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 16.0 13.0 16.0 13.0 16.0 13.0 18.0 13.0 18.0 13.0 18.0 13.0 18.0 13.0 18.0 13.0 18.0 13.0 15.0 13.0 15.0 13.0 15.0 13.0 18.0 13.0 18.0 13.0 18.0 13.0 18.0 13.0 18.0 13.0 18.0 Greater than 1200 CFM 9.0 9.0 9.0 11.0 11.0 11.0 13.0 13.0 13.0 16.0 16.0 16.0 22.0 22.0 22.0 22.0 22.0 22.0 15.0 15.0 15.0 22.0 22.0 22.0 22.0 22.0 22.0 Notes: 1. Adequate airflow over heater is necessary. As kW requirements increase, so must minimum airflow. The above chart indicates the minimum cfm required for each kW range. 2. Coils available with electric, electric with mercury contactors, pneumatic-electric switches and pneumatic-electric switches with mercury contactors. 3. Available kW increments are by 0.5 kW from 0.5 to 8.0 kW, by 1.0 kW from 9.0 to 17.0 kW and by 2.0 kW from 18.0 to 22.0 kW. 4. Each stage will be equal in kW output. 5. Single-stage and single-phase heaters are always balanced. On three-phase heaters the lineload is unbalanced. 6. Current draw for devices is as follows. Electric actuators each draw 1.0 amp. The contactor for each stage of heat draws 0.5 amp. The current draw for the heater elements is calculated by one of the formulas below. 7. Minimum circuit ampacity is equal to 1.25 times the total current draw for the unit. 8. Overcurrent protective devices shall be rated for 2.25 times the total current draw of the unit Useful Formulas kW = CFM x ATD 3145 1 Φ amps = ATD = kW x 3145 CFM kW x 1000 Primary Voltage 3 Φ amps = kW x 1000 Primary Voltage x √ 3 Example: A Model VCEE, electric unit heat size 24 terminal unit has 480 / 3 phase 5.0 kW electric heat with 3 stages. Electric Actuator = .5 Amps DDC UCM or Analog Electronic Control Board = .5 Amps 5.0 kW 3-phase heater 5.0 x 1000 480 x 1.73 Three heat outputs (at .5 amps max each) = 6.0 Amps = 1.5 Amps 8.5 Amps Max 77 Performance Data Single-Duct VAV Terminal Units – VCEE Table PD-16 — VCEE Size 32 Single-Duct VAV Terminal Unit Electric Heater kW Guidelines Voltage 208/60/1 240/60/1 277/60/1 347/60/1 480/60/1 575/60/1 208/60/3 480/60/3 575/60/3 Stage(s) 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 Min. kW 0.5 0.5 1.0 0.5 0.5 1.0 0.5 0.5 1.0 0.5 0.5 1.0 0.5 0.5 1.0 0.5 0.5 1.0 0.5 0.5 1.0 0.5 0.5 1.0 0.5 0.5 1.0 640 CFM through 959 CFM 9.0 9.0 9.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0 Maximum kW allowed at each of the following Airflows (CFM) 960 CFM 1280 CFM through through 1279 CFM 1599 CFM 9.0 9.0 9.0 9.0 9.0 9.0 11.0 11.0 11.0 11.0 11.0 11.0 13.0 13.0 13.0 13.0 13.0 13.0 16.0 16.0 16.0 16.0 16.0 16.0 18.0 20.0 18.0 20.0 18.0 20.0 18.0 20.0 18.0 20.0 18.0 20.0 15.0 15.0 15.0 15.0 15.0 15.0 18.0 20.0 18.0 20.0 18.0 20.0 18.0 20.0 18.0 20.0 18.0 20.0 Greater than 1600 CFM 9.0 9.0 9.0 11.0 11.0 11.0 13.0 13.0 13.0 16.0 16.0 16.0 22.0 22.0 22.0 24.0 24.0 24.0 15.0 15.0 15.0 24.0 24.0 24.0 24.0 24.0 24.0 Notes: 1. Adequate airflow over heater is necessary. As kW requirements increase, so must minimum airflow. The above chart indicates the minimum cfm required for each kW range. 2. Coils available with electric, electric with mercury contactors, pneumatic-electric switches and pneumatic-electric switches with mercury contactors. 3. Available kW increments are by 0.5 kW from 0.5 to 8.0 kW, by 1.0 kW from 9.0 to 17.0 kW and by 2.0 kW from 18.0 to 22.0 kW. 4. Each stage will be equal in kW output. 5. Single-stage and single-phase heaters are always balanced. On three-phase heaters the lineload is unbalanced. 6. Current draw for devices is as follows. Electric actuators each draw 1.0 amp. The contactor for each stage of heat draws 0.5 amp. The current draw for the heater elements is calculated by one of the formulas below. 7. Minimum circuit ampacity is equal to 1.25 times the total current draw for the unit. 8. Overcurrent protective devices shall be rated for 2.25 times the total current draw of the unit Useful Formulas kW = CFM x ATD 3145 1 Φ amps = ATD = kW x 3145 CFM kW x 1000 Primary Voltage 3 Φ amps = kW x 1000 Primary Voltage x √ 3 Example: A Model VCEE, electric unit heat size 32 terminal unit has 480 / 3 phase 10.0 kW electric heat with 3 stages. Electric Actuator = .5 Amps DDC UCM or Analog Electronic Control Board = .5 Amps 10.0 kW 3-phase heater 10.0 x 1000 480 x 1.73 Three heat outputs (at .5 amps max each) = 12.0 Amps = 1.5 Amps 14.5 Amps Max 78 Performance Data Single-Duct VAV Terminal Units – VCEE Table PD-17 — VCEE Size 42 Single-Duct VAV Terminal Unit Electric Heater kW Guidelines Voltage 208/60/1 240/60/1 277/60/1 347/60/1 480/60/1 575/60/1 208/60/3 480/60/3 575/60/3 Stage(s) 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 Min. kW 0.5 0.5 1.0 0.5 0.5 1.0 0.5 0.5 1.0 0.5 0.5 1.0 0.5 0.5 1.0 0.5 0.5 1.0 0.5 0.5 1.0 0.5 0.5 1.0 0.5 0.5 1.0 840 CFM through 1259 CFM 9.0 9.0 9.0 11.0 11.0 11.0 13.0 13.0 13.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 Maximum kW allowed at each of the following Airflows (CFM) 1260 CFM 1680 CFM through through 1679 CFM 2099 CFM 9.0 9.0 9.0 9.0 9.0 9.0 11.0 11.0 11.0 11.0 11.0 11.0 13.0 13.0 13.0 13.0 13.0 13.0 16.0 16.0 16.0 16.0 16.0 16.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 26.0 22.0 26.0 22.0 26.0 15.0 15.0 15.0 15.0 15.0 15.0 22.0 26.0 22.0 26.0 22.0 26.0 22.0 26.0 22.0 26.0 22.0 26.0 Greater than 2100 CFM 9.0 9.0 9.0 11.0 11.0 11.0 13.0 13.0 13.0 16.0 16.0 16.0 22.0 22.0 22.0 26.0 26.0 26.0 15.0 15.0 15.0 26.0 26.0 26.0 26.0 26.0 26.0 Notes: 1. Adequate airflow over heater is necessary. As kW requirements increase, so must minimum airflow. The above chart indicates the minimum cfm required for each kW range. 2. Coils available with electric, electric with mercury contactors, pneumatic-electric switches and pneumatic-electric switches with mercury contactors. 3. Available kW increments are by 0.5 kW from 0.5 to 8.0 kW, by 1.0 kW from 9.0 to 17.0 kW and by 2.0 kW from 18.0 to 22.0 kW. 4. Each stage will be equal in kW output. 5. Single-stage and single-phase heaters are always balanced. On three-phase heaters the lineload is unbalanced. 6. Current draw for devices is as follows. Electric actuators each draw 1.0 amp. The contactor for each stage of heat draws 0.5 amp. The current draw for the heater elements is calculated by one of the formulas below. 7. Minimum circuit ampacity is equal to 1.25 times the total current draw for the unit. 8. Overcurrent protective devices shall be rated for 2.25 times the total current draw of the unit Useful Formulas kW = CFM x ATD 3145 1 Φ amps = ATD = kW x 3145 CFM kW x 1000 Primary Voltage 3 Φ amps = kW x 1000 Primary Voltage x √ 3 Example: A Model VCEE, electric unit heat size 42 terminal unit has 480 / 3 phase 10.0 kW electric heat with 3 stages. Electric Actuator = .5 Amps DDC UCM or Analog Electronic Control Board = .5 Amps 10.0 kW 3-phase heater 10.0 x 1000 480 x 1.73 Three heat outputs (at .5 amps max each) = 12.0 Amps = 1.5 Amps 14.5 Amps Max 79 Performance Data Single-Duct VAV Terminal Units Acoustical Data Table PD-18 — Air Valve Size 03 Discharge Sound Data Air Valve Size VALV 03 Airflow (CFM) 300 225 150 75 300 225 150 75 300 225 150 75 300 225 150 75 Inlet Static Pressure (IN. W.G.) Min. Min. Min. Min. 1.5 1.5 1.5 1.5 2.0 2.0 2.0 2.0 3.0 3.0 3.0 3.0 2 62 57 46 43 67 64 56 47 68 64 56 46 69 62 55 47 3 58 53 42 34 64 62 55 48 66 62 55 48 67 62 54 48 Primary Valve Discharge Sound Octave Band 4 5 6 56 52 45 50 47 39 40 35 25 26 20 14 61 59 50 59 57 46 57 55 46 47 48 41 62 61 52 61 60 50 58 57 49 48 49 42 65 66 56 64 65 55 59 60 53 49 51 45 7 39 32 20 16 45 43 40 37 48 45 43 40 51 49 48 43 NC — — — — 20 17 — — 22 17 — — 24 17 — — 3 45 42 38 35 52 49 43 38 66 48 42 38 54 48 42 38 Primary Valve Discharge Sound Octave Band 4 5 6 40 34 30 33 27 22 25 19 15 21 18 13 47 41 35 50 44 33 48 43 33 35 31 24 62 61 52 53 48 37 48 44 35 36 32 25 56 54 43 56 53 42 49 45 38 38 34 27 7 25 18 17 16 29 26 24 19 48 29 26 20 36 34 30 23 NC — — — — 15 19 16 — 22 22 16 — 25 25 17 — Table PD-19 — Air Valve Size 03 Radiated Sound Data Air Valve Size VALV 03 Airflow (CFM) 300 225 150 75 300 225 150 75 300 225 150 75 300 225 150 75 Inlet Static Pressure (IN. W.G.) Min. Min. Min. Min. 1.5 1.5 1.5 1.5 2.0 2.0 2.0 2.0 3.0 3.0 3.0 3.0 2 51 47 43 41 57 53 46 42 68 52 45 42 58 51 45 43 1. Inlet Static Pressure includes 0.5" downstream static pressure for ductwork and diffusers. 2. All data are measured in accordance with Industry Standard ARI 880. 3. All sound power levels, DB re: 10-12 Watts. 4. “MIN” inlet static pressure is the minimum primary wide open pressure drop of the unit at the specified primary airflow. Static pressures other than minimum reflect actual presure drop across the air valve. 5. “—” represents NC levels below NC 15. 6. NC Values are calculated using modeling assumptions based on ARI 885-90. RADIATED NC LEVEL ASSUMPTIONS: Octave Band 1.) Environmental Adjustment 2.) Mineral Fiber Ceiling Tile 5/8" thickness and 35 lb/ft3 density 3.) Space Effect Factor – V = 5000 cu. ft., R = 10 ft. RADIATED TRANSFER FUNCTION 2 -3 -9 -10 -22 3 -2 -10 -11 -23 4 -1 -12 -12 -25 2 -3 -2 3 -2 -6 4 -1 -16 -4 -6 -11 -7 -0 -4 -9 -6 -8 -0 -29 -33 5 -1 -14 -13 -28 6 -1 -15 -13 -29 7 -1 -15 -14 -30 5 -1 -45 6 -1 -45 7 -1 -27 -4 -23 -2 -9 -1 -4 -25 0 -10 -5 -4 -22 0 -10 -7 -4 -13 0 --11 -5 -31 -51 -81 -78 -52 -35 -56 -90 -89 -61 DISCHARGE NC LEVEL ASSUMPTIONS: Octave Band 1.) Environmental Adjustment 2.) 10 Feet of 12"x12" Rectangular Metal Ductwork with a 1" lining 3.) Flow Division Losses - 40% Area Reduction 4.) 6 Feet of Lined Flexible Duct with a 8" Diameter 5.) Linear Slot Diffuser End Reflection - 8" Mean Duct Width 6.) Space Effect Factor – V = 5000 cu. ft., R = 5 ft. 7.) Rectangular Tee Attenuation Entering Branch Duct 90 deg Elbow, 5" Mean Duct Width, No Lining) UNIT 03, 06, and 11 DISCHARGE TRANSFER FUNCTION (using the above factors 1.), 2.), 4.), 5.), & 6.)) UNIT 17, 24, 32, and 42 DISCHARGE TRANSFER FUNCTION (using all the above factors) 80 Performance Data Single-Duct VAV Terminal Units Acoustical Data Table PD-20 — Air Valve Size 06 Discharge Sound Data Air Valve Size VALV 06 Airflow (CFM) 600 450 300 150 600 450 300 150 600 450 300 150 600 450 300 150 Inlet Static Pressure (IN. W.G.) Min. Min. Min. Min. 1.5 1.5 1.5 1.5 2.0 2.0 2.0 2.0 3.0 3.0 3.0 3.0 2 71 62 53 38 72 68 66 55 72 70 67 54 74 72 68 53 3 65 56 47 33 67 63 61 55 68 64 62 56 70 67 64 55 Primary Valve Discharge Sound Octave Band 4 5 6 61 56 48 43 48 41 43 39 30 26 20 12 66 64 54 62 61 51 59 54 46 57 55 44 67 66 56 63 62 53 62 56 48 58 58 48 69 69 60 66 65 56 65 62 53 59 61 52 7 43 35 23 14 48 45 41 36 50 47 44 40 53 51 49 46 NC 22 — — — 24 19 — — 25 21 17 — 27 24 20 — 3 52 45 37 31 56 53 50 45 57 54 52 45 59 56 53 45 Primary Valve Discharge Sound Octave Band 4 5 6 46 44 40 39 36 33 31 26 21 21 18 13 54 49 42 50 46 37 45 39 32 50 44 32 56 51 41 51 47 39 48 42 34 51 46 36 57 53 46 53 49 42 53 49 40 52 50 41 7 33 25 17 16 35 30 25 23 36 32 30 26 38 35 35 32 NC 19 — — — 23 19 — 19 25 20 16 20 26 22 22 21 Table PD-21 — Air Valve Size 06 Radiated Sound Data Air Valve Size VALV 06 Airflow (CFM) 600 450 300 150 600 450 300 150 600 450 300 150 600 450 300 150 Inlet Static Pressure (IN. W.G.) Min. Min. Min. Min. 1.5 1.5 1.5 1.5 2.0 2.0 2.0 2.0 3.0 3.0 3.0 3.0 2 61 53 44 41 62 58 56 45 62 60 57 45 64 62 58 45 1. Inlet Static Pressure includes 0.5" downstream static pressure for ductwork and diffusers. 2. All data are measured in accordance with Industry Standard ARI 880. 3. All sound power levels, DB re: 10-12 Watts. 4. “MIN” inlet static pressure is the minimum primary wide open pressure drop of the unit at the specified primary airflow. Static pressures other than minimum reflect actual presure drop across the air valve. 5. “—” represents NC levels below NC 15. 6. NC Values are calculated using modeling assumptions based on ARI 885-90. RADIATED NC LEVEL ASSUMPTIONS: Octave Band 1.) Environmental Adjustment 2.) Mineral Fiber Ceiling Tile 5/8" thickness and 35 lb/ft3 density 3.) Space Effect Factor – V = 5000 cu. ft., R = 10 ft. RADIATED TRANSFER FUNCTION 2 -3 -9 -10 -22 3 -2 -10 -11 -23 4 -1 -12 -12 -25 2 -3 -2 3 -2 -6 4 -1 -16 -4 -6 -11 -7 -0 -4 -9 -6 -8 -0 -29 -33 5 -1 -14 -13 -28 6 -1 -15 -13 -29 7 -1 -15 -14 -30 5 -1 -45 6 -1 -45 7 -1 -27 -4 -23 -2 -9 -1 -4 -25 0 -10 -5 -4 -22 0 -10 -7 -4 -13 0 --11 -5 -31 -51 -81 -78 -52 -35 -56 -90 -89 -61 DDISCHARGE NC LEVEL ASSUMPTIONS: Octave Band 1.) Environmental Adjustment 2.) 10 Feet of 12"x12" Rectangular Metal Ductwork with a 1" lining 3.) Flow Division Losses - 40% Area Reduction 4.) 6 Feet of Lined Flexible Duct with a 8" Diameter 5.) Linear Slot Diffuser End Reflection - 8" Mean Duct Width 6.) Space Effect Factor – V = 5000 cu. ft., R = 5 ft. 7.) Rectangular Tee Attenuation Entering Branch Duct 90 deg Elbow, 5" Mean Duct Width, No Lining) UNIT 03, 06, and 11 DISCHARGE TRANSFER FUNCTION (using the above factors 1.), 2.), 4.), 5.), & 6.)) UNIT 17, 24, 32, and 42 DISCHARGE TRANSFER FUNCTION (using all the above factors) 81 Performance Data Single-Duct VAV Terminal Units Acoustical Data Table PD-22 — Air Valve Size 11 Discharge Sound Data Air Valve Size VALV 11 Airflow (CFM) 1100 825 550 275 1100 825 550 275 1100 825 550 275 1100 825 550 275 Inlet Static Pressure (IN. W.G.) Min. Min. Min. Min. 1.5 1.5 1.5 1.5 2.0 2.0 2.0 2.0 3.0 3.0 3.0 3.0 2 70 63 52 40 71 66 60 56 72 67 62 56 72 69 66 56 3 64 57 46 34 67 63 57 58 68 64 60 59 68 65 63 60 Primary Valve Discharge Sound Octave Band 4 5 6 61 58 48 54 51 43 44 39 31 29 24 15 66 63 55 63 59 51 58 53 47 56 53 42 68 65 56 64 62 54 60 54 49 60 58 47 70 68 59 66 65 57 64 57 52 63 65 54 7 44 37 24 15 51 47 42 39 52 49 44 42 55 52 49 48 NC 21 — — — 24 19 — — 25 20 15 — 25 21 19 15 3 56 48 39 32 61 57 51 48 62 58 53 49 64 60 56 50 Primary Valve Discharge Sound Octave Band 4 5 6 49 48 41 42 41 33 36 29 21 21 18 13 57 51 42 53 46 37 47 40 32 48 42 29 58 52 44 54 48 38 48 42 34 52 47 35 61 55 46 56 51 42 51 45 38 55 54 44 7 32 23 16 16 35 31 26 25 36 33 28 28 39 36 33 33 NC 20 — — — 24 22 15 16 27 23 16 21 31 25 20 24 Table PD-23— Air Valve Size 11 Radiated Sound Data Air Valve Size VALV 11 Airflow (CFM) 1100 825 550 275 1100 825 550 275 1100 825 550 275 1100 825 550 275 Inlet Static Pressure (IN. W.G.) Min. Min. Min. Min. 1.5 1.5 1.5 1.5 2.0 2.0 2.0 2.0 3.0 3.0 3.0 3.0 2 61 53 42 41 64 59 53 47 65 60 55 48 67 63 58 50 1. Inlet Static Pressure includes 0.5" downstream static pressure for ductwork and diffusers. 2. All data are measured in accordance with Industry Standard ARI 880. 3. All sound power levels, DB re: 10-12 Watts. 4. “MIN” inlet static pressure is the minimum primary wide open pressure drop of the unit at the specified primary airflow. Static pressures other than minimum reflect actual presure drop across the air valve. 5. “—” represents NC levels below NC 15. 6. NC Values are calculated using modeling assumptions based on ARI 885-90. RADIATED NC LEVEL ASSUMPTIONS: Octave Band 1.) Environmental Adjustment 2.) Mineral Fiber Ceiling Tile 5/8" thickness and 35 lb/ft3 density 3.) Space Effect Factor – V = 5000 cu. ft., R = 10 ft. RADIATED TRANSFER FUNCTION 2 -3 -9 -10 -22 3 -2 -10 -11 -23 4 -1 -12 -12 -25 2 -3 -2 3 -2 -6 4 -1 -16 -4 -6 -11 -7 -0 -4 -9 -6 -8 -0 -29 -33 5 -1 -14 -13 -28 6 -1 -15 -13 -29 7 -1 -15 -14 -30 5 -1 -45 6 -1 -45 7 -1 -27 -4 -23 -2 -9 -1 -4 -25 0 -10 -5 -4 -22 0 -10 -7 -4 -13 0 --11 -5 -31 -51 -81 -78 -52 -35 -56 -90 -89 -61 DISCHARGE NC LEVEL ASSUMPTIONS: Octave Band 1.) Environmental Adjustment 2.) 10 Feet of 12"x12" Rectangular Metal Ductwork with a 1" lining 3.) Flow Division Losses - 40% Area Reduction 4.) 6 Feet of Lined Flexible Duct with a 8" Diameter 5.) Linear Slot Diffuser End Reflection - 8" Mean Duct Width 6.) Space Effect Factor – V = 5000 cu. ft., R = 5 ft. 7.) Rectangular Tee Attenuation Entering Branch Duct 90 deg Elbow, 5" Mean Duct Width, No Lining) UNIT 03, 06, and 11 DISCHARGE TRANSFER FUNCTION (using the above factors 1.), 2.), 4.), 5.), & 6.)) UNIT 17, 24, 32, and 42 DISCHARGE TRANSFER FUNCTION (using all the above factors) 82 Performance Data Single-Duct VAV Terminal Units Acoustical Data Table PD-24 — Air Valve Size 17 Discharge Sound Data Air Valve Size VALV 17 Airflow (CFM) 1700 1275 850 425 1700 1275 850 425 1700 1275 850 425 1700 1275 850 425 Inlet Static Pressure (IN. W.G.) Min. Min. Min. Min. 1.5 1.5 1.5 1.5 2.0 2.0 2.0 2.0 3.0 3.0 3.0 3.0 2 68 60 50 37 71 66 61 56 72 68 62 58 74 69 63 61 3 64 56 46 33 68 64 61 60 68 66 62 62 71 67 63 64 Primary Valve Discharge Sound Octave Band 4 5 6 62 59 52 54 49 44 45 40 33 21 18 13 69 66 58 66 60 54 63 56 50 53 49 44 71 68 60 68 62 56 64 58 52 56 54 51 74 71 62 72 65 59 66 61 56 61 62 60 7 48 37 24 15 55 50 45 39 56 52 48 46 59 55 52 55 NC 15 — — — 20 15 — — 21 15 — — 24 19 — 15 3 51 45 37 32 61 57 53 47 62 58 54 48 65 61 55 49 Primary Valve Discharge Sound Octave Band 4 5 6 45 45 37 38 34 29 30 24 18 21 18 13 55 49 42 54 44 35 50 41 32 38 33 25 58 52 43 56 47 38 50 43 34 42 40 34 61 55 45 59 51 42 51 46 37 48 49 46 7 29 21 16 15 35 28 24 19 36 30 26 28 38 34 30 37 NC 16 — — — 27 23 19 — 29 25 19 — 31 29 20 19 Table PD-25 — Air Valve Size 17 Radiated Sound Data Air Valve Size VALV 17 Airflow (CFM) 1700 1275 850 425 1700 1275 850 425 1700 1275 850 425 1700 1275 850 425 Inlet Static Pressure (IN. W.G.) Min. Min. Min. Min. 1.5 1.5 1.5 1.5 2.0 2.0 2.0 2.0 3.0 3.0 3.0 3.0 2 59 51 41 41 68 62 56 50 69 64 58 52 70 66 60 53 1. Inlet Static Pressure includes 0.5" downstream static pressure for ductwork and diffusers. 2. All data are measured in accordance with Industry Standard ARI 880. 3. All sound power levels, DB re: 10-12 Watts. 4. “MIN” inlet static pressure is the minimum primary wide open pressure drop of the unit at the specified primary airflow. Static pressures other than minimum reflect actual presure drop across the air valve. 5. “—” represents NC levels below NC 15. 6. NC Values are calculated using modeling assumptions based on ARI 885-90. RADIATED NC LEVEL ASSUMPTIONS: Octave Band 1.) Environmental Adjustment 2.) Mineral Fiber Ceiling Tile 5/8" thickness and 35 lb/ft3 density 3.) Space Effect Factor – V = 5000 cu. ft., R = 10 ft. RADIATED TRANSFER FUNCTION 2 -3 -9 -10 -22 3 -2 -10 -11 -23 4 -1 -12 -12 -25 2 -3 -2 3 -2 -6 4 -1 -16 -4 -6 -11 -7 -0 -4 -9 -6 -8 -0 -29 -33 5 -1 -14 -13 -28 6 -1 -15 -13 -29 7 -1 -15 -14 -30 5 -1 -45 6 -1 -45 7 -1 -27 -4 -23 -2 -9 -1 -4 -25 0 -10 -5 -4 -22 0 -10 -7 -4 -13 0 --11 -5 -31 -51 -81 -78 -52 -35 -56 -90 -89 -61 DISCHARGE NC LEVEL ASSUMPTIONS: Octave Band 1.) Environmental Adjustment 2.) 10 Feet of 12"x12" Rectangular Metal Ductwork with a 1" lining 3.) Flow Division Losses - 40% Area Reduction 4.) 6 Feet of Lined Flexible Duct with a 8" Diameter 5.) Linear Slot Diffuser End Reflection - 8" Mean Duct Width 6.) Space Effect Factor – V = 5000 cu. ft., R = 5 ft. 7.) Rectangular Tee Attenuation Entering Branch Duct 90 deg Elbow, 5" Mean Duct Width, No Lining) UNIT 03, 06, and 11 DISCHARGE TRANSFER FUNCTION (using the above factors 1.), 2.), 4.), 5.), & 6.)) UNIT 17, 24, 32, and 42 DISCHARGE TRANSFER FUNCTION (using all the above factors) 83 Performance Data Single Duct VAV Terminal Units Acoustical Data Table PD-26 — Air Valve Size 24 Discharge Sound Data Air Valve Size VALV 24 Airflow (CFM) 2400 1800 1200 600 2400 1800 1200 600 2400 1800 1200 600 2400 1800 1200 600 Inlet Static Pressure (IN. W.G.) Min. Min. Min. Min. 1.5 1.5 1.5 1.5 2.0 2.0 2.0 2.0 3.0 3.0 3.0 3.0 2 70 62 51 39 75 70 63 60 76 70 64 62 76 72 66 63 3 65 57 46 34 70 66 62 60 72 68 63 62 74 70 65 65 Primary Valve Discharge Sound Octave Band 4 5 6 61 58 51 55 49 42 44 39 29 29 21 13 68 64 57 65 59 53 60 53 49 52 49 44 70 66 58 68 60 54 62 56 51 55 51 46 73 69 61 71 64 58 65 59 55 59 57 53 7 46 36 22 15 54 49 45 40 56 51 48 45 58 55 52 52 NC 16 — — — 22 17 — — 25 21 — — 27 22 16 16 3 54 46 38 31 62 58 54 48 64 60 55 50 66 62 57 52 Primary Valve Discharge Sound Octave Band 4 5 6 48 46 39 44 37 32 33 26 18 22 19 14 55 49 42 53 43 36 47 38 30 38 33 26 58 50 43 55 46 38 48 40 30 41 36 30 61 54 45 58 49 40 51 44 36 46 44 37 7 32 24 15 15 35 30 23 21 36 32 27 26 39 36 33 33 NC 19 — — — 30 22 17 — 31 25 19 — 34 27 21 15 Table PD-27 — Air Valve Size 24 Radiated Sound Data Air Valve Size VALV 24 Airflow (CFM) 2400 1800 1200 600 2400 1800 1200 600 2400 1800 1200 600 2400 1800 1200 600 Inlet Static Pressure (IN. W.G.) Min. Min. Min. Min. 1.5 1.5 1.5 1.5 2.0 2.0 2.0 2.0 3.0 3.0 3.0 3.0 2 61 53 43 41 70 64 57 52 71 65 58 54 73 67 61 56 1. Inlet Static Pressure includes 0.5" downstream static pressure for ductwork and diffusers. 2. All data are measured in accordance with Industry Standard ARI 880. 3. All sound power levels, DB re: 10-12 Watts. 4. “MIN” inlet static pressure is the minimum primary wide open pressure drop of the unit at the specified primary airflow. Static pressures other than minimum reflect actual presure drop across the air valve. 5. “—” represents NC levels below NC 15. 6. NC Values are calculated using modeling assumptions based on ARI 885-90. RADIATED NC LEVEL ASSUMPTIONS: Octave Band 1.) Environmental Adjustment 2.) Mineral Fiber Ceiling Tile 5/8" thickness and 35 lb/ft3 density 3.) Space Effect Factor – V = 5000 cu. ft., R = 10 ft. RADIATED TRANSFER FUNCTION 2 -3 -9 -10 -22 3 -2 -10 -11 -23 4 -1 -12 -12 -25 2 -3 -2 3 -2 -6 4 -1 -16 -4 -6 -11 -7 -0 -4 -9 -6 -8 -0 -29 -33 5 -1 -14 -13 -28 6 -1 -15 -13 -29 7 -1 -15 -14 -30 5 -1 -45 6 -1 -45 7 -1 -27 -4 -23 -2 -9 -1 -4 -25 0 -10 -5 -4 -22 0 -10 -7 -4 -13 0 --11 -5 -31 -51 -81 -78 -52 -35 -56 -90 -89 -61 DISCHARGE NC LEVEL ASSUMPTIONS: Octave Band 1.) Environmental Adjustment 2.) 10 Feet of 12"x12" Rectangular Metal Ductwork with a 1" lining 3.) Flow Division Losses - 40% Area Reduction 4.) 6 Feet of Lined Flexible Duct with a 8" Diameter 5.) Linear Slot Diffuser End Reflection - 8" Mean Duct Width 6.) Space Effect Factor – V = 5000 cu. ft., R = 5 ft. 7.) Rectangular Tee Attenuation Entering Branch Duct 90 deg Elbow, 5" Mean Duct Width, No Lining) UNIT 03, 06, and 11 DISCHARGE TRANSFER FUNCTION (using the above factors 1.), 2.), 4.), 5.), & 6.)) UNIT 17, 24, 32, and 42 DISCHARGE TRANSFER FUNCTION (using all the above factors) 84 Performance Data Single-Duct VAV Terminal Units Acoustical Data Table PD-28 — Air Valve Size 32 Discharge Sound Data Air Valve Size VALV 32 Airflow (CFM) 3200 2400 1600 800 3200 2400 1600 800 3200 2400 1600 800 3200 2400 1600 800 Inlet Static Pressure (IN. W.G.) Min. Min. Min. Min. 1.5 1.5 1.5 1.5 2.0 2.0 2.0 2.0 3.0 3.0 3.0 3.0 2 71 64 54 41 74 69 67 61 75 70 68 64 77 72 69 68 3 67 59 50 36 72 70 65 55 74 72 66 58 77 74 67 61 Primary Valve Discharge Sound Octave Band 4 5 6 64 58 53 56 50 45 46 42 34 32 28 16 71 65 60 66 61 57 61 57 53 52 49 46 72 66 62 68 63 59 63 59 54 55 52 48 76 70 65 71 66 62 66 62 56 58 57 53 7 47 38 26 15 56 52 47 41 58 54 50 44 62 57 54 51 NC 19 — — — 25 22 16 — 27 25 17 — 31 27 19 — 3 57 51 57 33 62 60 56 46 64 62 58 49 67 65 59 53 Primary Valve Discharge Sound Octave Band 4 5 6 53 45 40 46 39 33 52 46 37 24 18 13 58 53 47 54 48 43 50 45 39 40 35 28 61 54 48 56 50 44 52 46 40 42 38 32 65 58 51 60 53 47 54 48 41 46 43 38 7 29 25 33 15 38 36 28 21 40 39 30 25 42 43 33 32 NC 22 — 21 — 27 25 20 — 31 27 22 — 35 31 24 16 Table PD-29 — Air Valve Size 32 Radiated Sound Data Air Valve Size VALV 32 Airflow (CFM) 3200 2400 1600 800 3200 2400 1600 800 3200 2400 1600 800 3200 2400 1600 800 Inlet Static Pressure (IN. W.G.) Min. Min. Min. Min. 1.5 1.5 1.5 1.5 2.0 2.0 2.0 2.0 3.0 3.0 3.0 3.0 2 60 54 59 41 68 62 57 50 68 64 58 53 70 66 60 57 1. Inlet Static Pressure includes 0.5" downstream static pressure for ductwork and diffusers. 2. All data are measured in accordance with Industry Standard ARI 880. 3. All sound power levels, DB re: 10-12 Watts. 4. “MIN” inlet static pressure is the minimum primary wide open pressure drop of the unit at the specified primary airflow. Static pressures other than minimum reflect actual presure drop across the air valve. 5. “—” represents NC levels below NC 15. 6. NC Values are calculated using modeling assumptions based on ARI 885-90. RADIATED NC LEVEL ASSUMPTIONS: Octave Band 1.) Environmental Adjustment 2.) Mineral Fiber Ceiling Tile 5/8" thickness and 35 lb/ft3 density 3.) Space Effect Factor – V = 5000 cu. ft., R = 10 ft. RADIATED TRANSFER FUNCTION 2 -3 -9 -10 -22 3 -2 -10 -11 -23 4 -1 -12 -12 -25 2 -3 -2 3 -2 -6 4 -1 -16 -4 -6 -11 -7 -0 -4 -9 -6 -8 -0 -29 -33 5 -1 -14 -13 -28 6 -1 -15 -13 -29 7 -1 -15 -14 -30 5 -1 -45 6 -1 -45 7 -1 -27 -4 -23 -2 -9 -1 -4 -25 0 -10 -5 -4 -22 0 -10 -7 -4 -13 0 --11 -5 -31 -51 -81 -78 -52 -35 -56 -90 -89 -61 DISCHARGE NC LEVEL ASSUMPTIONS: Octave Band 1.) Environmental Adjustment 2.) 10 Feet of 12"x12" Rectangular Metal Ductwork with a 1" lining 3.) Flow Division Losses - 40% Area Reduction 4.) 6 Feet of Lined Flexible Duct with a 8" Diameter 5.) Linear Slot Diffuser End Reflection - 8" Mean Duct Width 6.) Space Effect Factor – V = 5000 cu. ft., R = 5 ft. 7.) Rectangular Tee Attenuation Entering Branch Duct 90 deg Elbow, 5" Mean Duct Width, No Lining) UNIT 03, 06, and 11 DISCHARGE TRANSFER FUNCTION (using the above factors 1.), 2.), 4.), 5.), & 6.)) UNIT 17, 24, 32, and 42 DISCHARGE TRANSFER FUNCTION (using all the above factors) 85 Performance Data Single-Duct VAV Terminal Units Acoustical Data Table PD-30 — Air Valve Size 42 Discharge Sound Data Air Valve Size VALV 42 Airflow (CFM) 4200 3150 2100 1050 4200 3150 2100 1050 4200 3150 2100 1050 4200 3150 2100 1050 Inlet Static Pressure (IN. W.G.) Min. Min. Min. Min. 1.5 1.5 1.5 1.5 2.0 2.0 2.0 2.0 3.0 3.0 3.0 3.0 2 72 65 55 42 75 71 67 61 76 72 68 64 78 74 69 69 3 67 61 50 36 71 70 66 56 73 72 67 59 76 75 68 64 Primary Valve Discharge Sound Octave Band 4 5 6 65 59 53 56 50 43 45 39 29 29 20 14 70 66 60 66 62 57 63 58 53 54 52 47 72 68 62 68 64 59 66 60 55 56 54 50 75 70 65 71 67 62 69 64 59 59 57 53 7 47 36 21 14 55 52 47 43 58 54 50 46 61 57 55 50 NC 20 — — — 24 19 17 — 26 25 19 — 30 29 20 15 3 61 55 46 35 64 60 56 48 66 62 58 50 69 64 60 55 Primary Valve Discharge Sound Octave Band 4 5 6 54 49 42 48 41 34 39 29 20 23 18 14 58 53 47 54 49 43 50 43 36 41 36 29 60 54 48 56 50 44 52 45 38 44 38 32 62 57 51 60 53 46 56 48 41 47 41 35 7 32 21 15 15 37 37 27 22 40 37 29 25 44 38 33 30 NC 26 19 — — 31 25 20 — 32 27 22 — 36 30 25 19 Table PD-31 — Air Valve Size 42 Radiated Sound Data Air Valve Size VALV 42 Airflow (CFM) 4200 3150 2100 1050 4200 3150 2100 1050 4200 3150 2100 1050 4200 3150 2100 1050 Inlet Static Pressure (IN. W.G.) Min. Min. Min. Min. 1.5 1.5 1.5 1.5 2.0 2.0 2.0 2.0 3.0 3.0 3.0 3.0 2 61 53 48 41 71 66 59 51 72 67 60 53 74 69 63 56 1. Inlet Static Pressure includes 0.5" downstream static pressure for ductwork and diffusers. 2. All data are measured in accordance with Industry Standard ARI 880. 3. All sound power levels, DB re: 10-12 Watts. 4. “MIN” inlet static pressure is the minimum primary wide open pressure drop of the unit at the specified primary airflow. Static pressures other than minimum reflect actual presure drop across the air valve. 5. “—” represents NC levels below NC 15. 6. NC Values are calculated using modeling assumptions based on ARI 885-90. RADIATED NC LEVEL ASSUMPTIONS: Octave Band 1.) Environmental Adjustment 2.) Mineral Fiber Ceiling Tile 5/8" thickness and 35 lb/ft3 density 3.) Space Effect Factor – V = 5000 cu. ft., R = 10 ft. RADIATED TRANSFER FUNCTION 2 -3 -9 -10 -22 3 -2 -10 -11 -23 4 -1 -12 -12 -25 2 -3 -2 3 -2 -6 4 -1 -16 -4 -6 -11 -7 -0 -4 -9 -6 -8 -0 -29 -33 5 -1 -14 -13 -28 6 -1 -15 -13 -29 7 -1 -15 -14 -30 5 -1 -45 6 -1 -45 7 -1 -27 -4 -23 -2 -9 -1 -4 -25 0 -10 -5 -4 -22 0 -10 -7 -4 -13 0 --11 -5 -31 -51 -81 -78 -52 -35 -56 -90 -89 -61 DISCHARGE NC LEVEL ASSUMPTIONS: Octave Band 1.) Environmental Adjustment 2.) 10 Feet of 12"x12" Rectangular Metal Ductwork with a 1" lining 3.) Flow Division Losses - 40% Area Reduction 4.) 6 Feet of Lined Flexible Duct with a 8" Diameter 5.) Linear Slot Diffuser End Reflection - 8" Mean Duct Width 6.) Space Effect Factor – V = 5000 cu. ft., R = 5 ft. 7.) Rectangular Tee Attenuation Entering Branch Duct 90 deg Elbow, 5" Mean Duct Width, No Lining) UNIT 03, 06, and 11 DISCHARGE TRANSFER FUNCTION (using the above factors 1.), 2.), 4.), 5.), & 6.)) UNIT 17, 24, 32, and 42 DISCHARGE TRANSFER FUNCTION (using all the above factors) 86 Performance Data Single-Duct VAV Terminal Units Acoustical Data Table PD-32 — Primary Air Valve Discharge Sound Data, ARI Conditions Air Valve Size VALV 03 VALV 06 VALV 11 VALV 17 VALV 24 VALV 32 VALV 42 Inlet Static Pressure (IN. W.G.) 1.5 1.5 1.5 1.5 1.5 1.5 1.5 Airflow (CFM) 250 400 700 1100 1600 2100 2800 2 65 67 63 64 68 68 70 3 63 62 60 63 65 68 69 Primary Valve Discharge Sound Octave Band 4 5 60 58 61 59 61 56 65 58 63 57 64 60 65 61 6 47 49 49 52 52 56 56 7 44 44 45 48 48 50 50 Primary Valve Discharge Sound Octave Band 4 5 49 43 48 44 50 43 52 43 51 41 52 47 53 47 6 34 35 35 34 34 42 41 7 27 28 29 26 28 33 34 Table PD-33 — Primary Air Valve Radiated Sound Data, ARI Conditions Air Valve Size VALV 03 VALV 06 VALV 11 VALV 17 VALV 24 VALV 32 VALV 42 Inlet Static Pressure (IN. W.G.) 1.5 1.5 1.5 1.5 1.5 1.5 1.5 Airflow (CFM) 250 400 700 1100 1600 2100 2800 2 54 57 56 60 62 60 64 3 50 52 54 55 57 58 59 Table PD-34 — Average Appurtenance Effect - Single-Duct Attenuator Air Valve Size VALV 03 VALV 06 VALV 11 VALV 17 VALV 24 VALV 32 VALV 42 2 -2 -3 0 0 -1 0 -1 3 -4 -4 -3 -2 -3 1 -1 Discharge Sound Attenuation Octave Band 4 5 -10 -17 -9 -16 -7 -13 -6 -11 -5 -12 -4 -9 -4 -8 6 -25 -26 -24 -15 -11 -10 -8 7 -16 -17 -13 -11 -8 -8 -5 Transfer Function Assumptions Single and Dual-Duct VAV Terminal Units Trane Assumptions RADIATED NC LEVEL ASSUMPTIONS: 1.) Environmental Adjustment 2.) Mineral Fiber Ceiling Tile 5/8" thickness and 35 lb/ft3 density 3.) Space Effect Factor – V = 5000 cu. ft., R = 10 ft. Radiated Transfer Function 2 3 -9 -10 -22 3 2 -10 -11 -23 Octave Band 4 5 -1 -1 -12 -14 -12 -13 -25 -28 6 -1 -15 -13 -29 7 -1 -15 -14 -30 2 -3 -2 -4 3 -2 -6 -4 Octave Band 4 5 -1 -1 -16 -45 -4 -4 6 -1 -45 -4 7 -1 -27 -4 -6 -11 -9 -6 -23 -2 -25 0 -22 0 -13 0 -7 -8 -9 -10 -10 -11 -0 -0 -1 -5 -7 -5 -29 -31 -51 -81 -78 -52 -33 -35 -56 -90 -89 -61 DISCHARGE NC LEVEL ASSUMPTIONS: 1.) Environmental Adjustment 2.) 10 Feet of 12"x12" Rectangular Metal Ductwork with a 1" lining 3.) Flow Division Losses - 40% Area Reduction 4.) 6 Feet of Lined Flexible Duct with a 8" Diameter 5.) Linear Slot Diffuser End Reflection - 8" Mean Duct Width 6.) Space Effect Factor V = 5000 cu. ft., R = 5 ft. 7.) Rectangular Tee Attenuation Entering Branch Duct (90 deg Elbow, 5" Mean Duct Width, No Lining) Unit 03, 06 and 11 Discharge Transfer Function (using the above factors 1.), 2.), 4.), 5.), & 6.) Unit 17, 24, 32 and 42 Discharge Transfer Function (using the above factors 1.), 2.), 3.), 4.), 5.), 6.), & 7.) 87 Performance Data Single-Duct VAV Terminal Units Acoustical Data Acoustical Data – Double-Wall Effect Unit Small single-duct - Air Valve Sizes 03, 06, 11 Large single-duct - Air Valve Sizes 17, 24, 32, 42 Small dual-duct - Air Valve Sizes 03, 06, 11 Large dual-duct - Air Valve Sizes 17, 24, 32, 42 Octave Band 1 63 Hz 1 -5 3 -4 Octave Band 2 125 Hz 0 1 4 -2 Octave Band 3 250 Hz 1 1 4 -2 Discharge Octave Octave Band 4 Band 5 500 Hz 1000 Hz 1 6 4 7 2 5 1 3 Octave Band 6 2000 Hz 9 10 8 6 Octave Band 7 4000 Hz 10 12 9 6 Octave Band 8 8000 Hz 9 13 9 7 Unit Small single-duct - Air Valve Sizes 03, 06, 11, 17 Large single-duct - Air Valve Sizes 24, 32, 42 Small dual-duct - Air Valve Sizes 03, 06, 11, 17 Large dual-duct - Air Valve Sizes 24, 32, 42 Octave Band 1 63 Hz -1 -2 -3 -2 Octave Band 2 125 Hz -1 0 -4 -1 Octave Band 3 250 Hz 2 5 0 1 Casing Radiated Octave Octave Band 4 Band 5 500 Hz 1000 Hz 0 0 5 8 -2 -3 -1 -2 Octave Band 6 2000 Hz 5 10 -1 -2 Octave Band 7 4000 Hz 5 9 -2 -1 Octave Band 8 8000 Hz 0 7 -1 -2 88 Performance Data Dual-Duct VAV Terminal Unit Acoustical Data Table PD-35 — Air Valve Size 03 Discharge Sound Data Air Valve Size VALV 03 Airflow (CFM) 300 225 150 75 300 225 150 75 300 225 150 75 300 225 150 75 Inlet Static Pressure (IN. W.G.) Min. Min. Min. Min. 1.5 1.5 1.5 1.5 2.0 2.0 2.0 2.0 3.0 3.0 3.0 3.0 2 58 52 43 41 63 62 54 44 64 62 53 44 66 61 54 45 3 53 47 38 32 59 58 51 38 61 58 51 38 63 58 50 39 Primary Valve Discharge Sound Octave Band 4 5 6 50 46 42 44 40 34 33 29 21 21 17 14 56 54 46 54 52 43 56 54 44 44 43 35 58 56 48 58 56 46 55 52 42 46 44 36 62 61 52 64 62 52 57 58 48 48 47 39 7 36 27 17 16 42 40 39 32 44 42 36 34 48 46 44 38 NC — — — — — — — — 16 — — — 19 — — — 3 44 39 33 31 52 51 46 40 54 51 46 40 56 51 44 41 Primary Valve Discharge Sound Octave Band 4 5 6 39 34 31 33 27 24 27 22 17 22 18 13 47 43 35 46 42 33 48 44 33 39 35 27 50 46 38 50 48 37 48 46 36 40 36 28 55 53 42 54 54 44 49 50 41 42 39 31 7 25 18 16 16 28 26 24 20 31 28 27 22 35 33 32 27 NC — — — — — — 16 — 19 19 16 — 24 24 20 — Table PD-36 — Air Valve Size 03 Radiated Sound Data Air Valve Size VALV 03 Airflow (CFM) 300 225 150 75 300 225 150 75 300 225 150 75 300 225 150 75 Inlet Static Pressure (IN. W.G.) Min. Min. Min. Min. 1.5 1.5 1.5 1.5 2.0 2.0 2.0 2.0 3.0 3.0 3.0 3.0 2 52 44 41 41 57 54 45 41 58 54 46 41 59 54 48 41 1. Inlet Static Pressure includes 0.5" downstream static pressure for ductwork and diffusers. 2. All data are measured in accordance with Industry Standard ARI 880. 3. All sound power levels, DB re: 10-12 Watts. 4. “MIN” inlet static pressure is the minimum primary wide open pressure drop of the unit at the specified primary airflow. Static pressures other than minimum reflect actual presure drop across the air valve. 5. “—” represents NC levels below NC 15. 6. When using different heating and cooling air valve sizes, select acoustical data for the largest air valve. This is due to testing procedures established by ARI 880. 7. NC Values are calculated using modeling assumptions based on ARI 885-90. RADIATED NC LEVEL ASSUMPTIONS: Octave Band 1.) Environmental Adjustment 2.) Mineral Fiber Ceiling Tile 5/8" thickness and 35 lb/ft3 density 3.) Space Effect Factor – V = 5000 cu. ft., R = 10 ft. RADIATED TRANSFER FUNCTION 2 -3 -9 -10 -22 3 -2 -10 -11 -23 4 -1 -12 -12 -25 2 -3 -2 3 -2 -6 4 -1 -16 -4 -6 -11 -7 -0 -4 -9 -6 -8 -0 -29 -33 5 -1 -14 -13 -28 6 -1 -15 -13 -29 7 -1 -15 -14 -30 5 -1 -45 6 -1 -45 7 -1 -27 -4 -23 -2 -9 -1 -4 -25 0 -10 -5 -4 -22 0 -10 -7 -4 -13 0 --11 -5 -31 -51 -81 -78 -52 -35 -56 -90 -89 -61 DISCHARGE NC LEVEL ASSUMPTIONS: Octave Band 1.) Environmental Adjustment 2.) 10 Feet of 12"x12" Rectangular Metal Ductwork with a 1" lining 3.) Flow Division Losses - 40% Area Reduction 4.) 6 Feet of Lined Flexible Duct with a 8" Diameter 5.) Linear Slot Diffuser End Reflection - 8" Mean Duct Width 6.) Space Effect Factor – V = 5000 cu. ft., R = 5 ft. 7.) Rectangular Tee Attenuation Entering Branch Duct 90 deg Elbow, 5" Mean Duct Width, No Lining) UNIT 03, 06, and 11 DISCHARGE TRANSFER FUNCTION (using the above factors 1.), 2.), 4.), 5.), & 6.)) UNIT 17, 24, 32, and 42 DISCHARGE TRANSFER FUNCTION (using all the above factors) 89 Performance Data Dual-Duct VAV Terminal Unit Acoustical Data Table PD-37 — Air Valve Size 06 Discharge Sound Data Air Valve Size VALV 06 Airflow (CFM) 600 450 300 150 600 450 300 150 600 450 300 150 600 450 300 150 Inlet Static Pressure (IN. W.G.) Min. Min. Min. Min. 1.5 1.5 1.5 1.5 2.0 2.0 2.0 2.0 3.0 3.0 3.0 3.0 2 64 57 48 37 67 63 60 51 68 65 62 52 70 69 65 54 3 59 51 43 31 62 58 55 52 63 60 57 53 65 62 59 54 Primary Valve Discharge Sound Octave Band 4 5 6 53 49 45 45 42 37 37 33 27 22 17 13 60 57 48 56 54 45 51 48 41 55 52 39 61 59 50 57 56 48 54 51 43 56 55 43 62 62 54 59 58 51 60 57 48 56 59 48 7 41 33 26 16 44 40 36 34 46 42 40 48 49 46 45 43 NC — — — — 17 — — — 19 15 — — 21 20 15 — 3 51 44 36 31 57 52 49 48 58 53 51 48 59 55 53 48 Primary Valve Discharge Sound Octave Band 4 5 6 47 47 42 40 40 34 35 28 23 21 18 13 53 50 42 49 46 38 45 40 33 49 45 33 54 52 44 50 47 40 48 44 36 49 48 37 56 54 46 52 50 42 54 50 41 49 51 42 7 34 26 18 16 36 31 27 24 38 33 30 27 40 37 35 32 NC 17 — — — 22 17 — 17 23 19 16 18 25 21 23 21 Table PD-38 — Air Valve Size 06 Radiated Sound Data Air Valve Size VALV 06 Airflow (CFM) 600 450 300 150 600 450 300 150 600 450 300 150 600 450 300 150 Inlet Static Pressure (IN. W.G.) Min. Min. Min. Min. 1.5 1.5 1.5 1.5 2.0 2.0 2.0 2.0 3.0 3.0 3.0 3.0 2 58 52 43 41 62 57 55 44 62 59 56 46 64 62 57 48 1. Inlet Static Pressure includes 0.5" downstream static pressure for ductwork and diffusers. 2. All data are measured in accordance with Industry Standard ARI 880. 3. All sound power levels, DB re: 10-12 Watts. 4. “MIN” inlet static pressure is the minimum primary wide open pressure drop of the unit at the specified primary airflow. Static pressures other than minimum reflect actual presure drop across the air valve. 5. “—” represents NC levels below NC 15. 6. When using different heating and cooling air valve sizes, select acoustical data for the largest air valve. This is due to testing procedures established by ARI 880. 7. NC Values are calculated using modeling assumptions based on ARI 885-90. RADIATED NC LEVEL ASSUMPTIONS: Octave Band 1.) Environmental Adjustment 2.) Mineral Fiber Ceiling Tile 5/8" thickness and 35 lb/ft3 density 3.) Space Effect Factor – V = 5000 cu. ft., R = 10 ft. RADIATED TRANSFER FUNCTION 2 -3 -9 -10 -22 3 -2 -10 -11 -23 4 -1 -12 -12 -25 2 -3 -2 3 -2 -6 4 -1 -16 -4 -6 -11 -7 -0 -4 -9 -6 -8 -0 -29 -33 5 -1 -14 -13 -28 6 -1 -15 -13 -29 7 -1 -15 -14 -30 5 -1 -45 6 -1 -45 7 -1 -27 -4 -23 -2 -9 -1 -4 -25 0 -10 -5 -4 -22 0 -10 -7 -4 -13 0 --11 -5 -31 -51 -81 -78 -52 -35 -56 -90 -89 -61 DISCHARGE NC LEVEL ASSUMPTIONS: Octave Band 1.) Environmental Adjustment 2.) 10 Feet of 12"x12" Rectangular Metal Ductwork with a 1" lining 3.) Flow Division Losses - 40% Area Reduction 4.) 6 Feet of Lined Flexible Duct with a 8" Diameter 5.) Linear Slot Diffuser End Reflection - 8" Mean Duct Width 6.) Space Effect Factor – V = 5000 cu. ft., R = 5 ft. 7.) Rectangular Tee Attenuation Entering Branch Duct 90 deg Elbow, 5" Mean Duct Width, No Lining) UNIT 03, 06, and 11 DISCHARGE TRANSFER FUNCTION (using the above factors 1.), 2.), 4.), 5.), & 6.)) UNIT 17, 24, 32, and 42 DISCHARGE TRANSFER FUNCTION (using all the above factors) 90 Performance Data Dual-Duct VAV Terminal Unit Acoustical Data Table PD-39 — Air Valve Size 11 Discharge Sound Data\ Air Valve Size VALV 11 Airflow (CFM) 1100 825 550 275 1100 825 550 275 1100 825 550 275 1100 825 550 275 Inlet Static Pressure (IN. W.G.) Min. Min. Min. Min. 1.5 1.5 1.5 1.5 2.0 2.0 2.0 2.0 3.0 3.0 3.0 3.0 2 70 61 50 38 73 66 59 55 73 68 63 56 74 70 69 56 Primary Valve Discharge Sound Octave Band 4 5 6 55 55 47 48 47 39 37 35 27 24 19 14 62 59 51 59 55 47 54 49 43 56 51 39 64 61 53 60 58 49 56 51 46 60 56 44 67 64 56 62 61 53 59 55 49 63 63 53 3 60 52 40 32 63 58 51 53 64 59 54 54 65 61 58 54 7 43 34 20 16 47 43 39 37 49 46 42 40 52 49 47 45 NC 21 — — — 25 16 — — 25 19 — — 26 21 20 — Table PD-40 — Air Valve Size 11 Radiated Sound Data Inlet Static Primary Valve Discharge Sound Airflow Pressure Octave Band (CFM) (IN. W.G.) 2 3 4 5 6 7 NC 1100 Min. 62 56 47 43 38 31 20 825 Min. 56 49 41 36 31 21 — 550 Min. 45 38 30 25 17 15 — 275 Min. 41 31 21 18 13 15 — 1100 1.5 68 62 55 49 42 35 27 825 1.5 63 59 52 45 38 31 24 550 1.5 56 51 47 40 33 28 15 275 1.5 49 49 47 42 32 28 15 1100 2.0 69 64 58 52 44 37 30 825 2.0 64 60 54 48 40 34 25 550 2.0 58 52 48 42 35 30 16 275 2.0 50 50 51 48 38 30 20 1100 3.0 71 66 61 55 46 40 32 825 3.0 66 61 56 51 43 38 26 550 3.0 62 55 51 45 39 36 20 275 3.0 51 55 50 56 46 36 26 1. Inlet Static Pressure includes 0.5" downstream static pressure for ductwork and diffusers. 2. All data are measured in accordance with Industry Standard ARI 880. 3. All sound power levels, DB re: 10-12 Watts. 4. “MIN” inlet static pressure is the minimum primary wide open pressure drop of the unit at the specified primary airflow. Static pressures other than minimum reflect actual presure drop across the air valve. 5. “—” represents NC levels below NC 15. 6. When using different heating and cooling air valve sizes, select acoustical data for the largest air valve. This is due to testing procedures established by ARI 880. 7. NC Values are calculated using modeling assumptions based on ARI 885-90. Air Valve Size VALV 11 RADIATED NC LEVEL ASSUMPTIONS: Octave Band 1.) Environmental Adjustment 2.) Mineral Fiber Ceiling Tile 5/8" thickness and 35 lb/ft3 density 3.) Space Effect Factor – V = 5000 cu. ft., R = 10 ft. RADIATED TRANSFER FUNCTION 2 -3 -9 -10 -22 3 -2 -10 -11 -23 4 -1 -12 -12 -25 2 -3 -2 3 -2 -6 4 -1 -16 -4 -6 -11 -7 -0 -4 -9 -6 -8 -0 -29 -33 5 -1 -14 -13 -28 6 -1 -15 -13 -29 7 -1 -15 -14 -30 5 -1 -45 6 -1 -45 7 -1 -27 -4 -23 -2 -9 -1 -4 -25 0 -10 -5 -4 -22 0 -10 -7 -4 -13 0 --11 -5 -31 -51 -81 -78 -52 -35 -56 -90 -89 -61 DISCHARGE NC LEVEL ASSUMPTIONS: Octave Band 1.) Environmental Adjustment 2.) 10 Feet of 12"x12" Rectangular Metal Ductwork with a 1" lining 3.) Flow Division Losses - 40% Area Reduction 4.) 6 Feet of Lined Flexible Duct with a 8" Diameter 5.) Linear Slot Diffuser End Reflection - 8" Mean Duct Width 6.) Space Effect Factor – V = 5000 cu. ft., R = 5 ft. 7.) Rectangular Tee Attenuation Entering Branch Duct 90 deg Elbow, 5" Mean Duct Width, No Lining) UNIT 03, 06, and 11 DISCHARGE TRANSFER FUNCTION (using the above factors 1.), 2.), 4.), 5.), & 6.)) UNIT 17, 24, 32, and 42 DISCHARGE TRANSFER FUNCTION (using all the above factors) 91 Performance Data Dual-Duct VAV Terminal Unit Acoustical Data Table PD-41 — Air Valve Size 17 Discharge Sound Data Air Valve Size VALV 17 Airflow (CFM) 1700 1275 850 425 1700 1275 850 425 1700 1275 850 425 1700 1275 850 425 Inlet Static Pressure (IN. W.G.) Min. Min. Min. Min. 1.5 1.5 1.5 1.5 2.0 2.0 2.0 2.0 3.0 3.0 3.0 3.0 2 73 64 52 37 73 67 61 54 74 68 64 60 76 70 68 61 3 62 52 41 32 63 60 57 45 64 62 58 52 67 64 60 54 Primary Valve Discharge Sound Octave Band 4 5 6 59 55 50 51 46 42 41 37 30 26 21 13 65 61 55 62 55 50 58 51 46 45 41 38 67 62 56 64 57 52 59 53 48 52 49 47 70 66 58 68 60 55 60 56 52 57 56 51 7 47 36 22 15 52 47 42 32 54 49 45 42 56 52 49 44 NC 20 — — — 20 — — — 21 — — — 24 16 — — 3 56 48 39 33 62 59 55 47 63 60 56 49 65 63 57 51 Primary Valve Discharge Sound Octave Band 4 5 6 48 46 39 41 36 30 35 27 20 21 18 13 57 51 45 54 46 39 50 40 32 38 32 25 60 52 46 56 48 40 51 42 34 42 38 33 63 56 48 59 51 43 52 45 36 48 48 43 7 31 21 16 15 41 35 26 20 42 36 28 28 45 38 31 36 NC 22 — — — 27 24 19 — 30 25 20 — 33 29 21 18 Table PD-42 — Air Valve Size 17 Radiated Sound Data Air Valve Size VALV 17 Airflow (CFM) 1700 1275 850 425 1700 1275 850 425 1700 1275 850 425 1700 1275 850 425 Inlet Static Pressure (IN. W.G.) Min. Min. Min. Min. 1.5 1.5 1.5 1.5 2.0 2.0 2.0 2.0 3.0 3.0 3.0 3.0 2 64 55 45 41 68 63 59 52 69 64 60 53 71 66 62 54 1. Inlet Static Pressure includes 0.5" downstream static pressure for ductwork and diffusers. 2. All data are measured in accordance with Industry Standard ARI 880. 3. All sound power levels, DB re: 10-12 Watts. 4. “MIN” inlet static pressure is the minimum primary wide open pressure drop of the unit at the specified primary airflow. Static pressures other than minimum reflect actual presure drop across the air valve. 5. “—” represents NC levels below NC 15. 6. When using different heating and cooling air valve sizes, select acoustical data for the largest air valve. This is due to testing procedures established by ARI 880. 7. NC Values are calculated using modeling assumptions based on ARI 885-90. RADIATED NC LEVEL ASSUMPTIONS: Octave Band 1.) Environmental Adjustment 2.) Mineral Fiber Ceiling Tile 5/8" thickness and 35 lb/ft3 density 3.) Space Effect Factor – V = 5000 cu. ft., R = 10 ft. RADIATED TRANSFER FUNCTION 2 -3 -9 -10 -22 3 -2 -10 -11 -23 4 -1 -12 -12 -25 2 -3 -2 3 -2 -6 4 -1 -16 -4 -6 -11 -7 -0 -4 -9 -6 -8 -0 -29 -33 5 -1 -14 -13 -28 6 -1 -15 -13 -29 7 -1 -15 -14 -30 5 -1 -45 6 -1 -45 7 -1 -27 -4 -23 -2 -9 -1 -4 -25 0 -10 -5 -4 -22 0 -10 -7 -4 -13 0 --11 -5 -31 -51 -81 -78 -52 -35 -56 -90 -89 -61 DISCHARGE NC LEVEL ASSUMPTIONS: Octave Band 1.) Environmental Adjustment 2.) 10 Feet of 12"x12" Rectangular Metal Ductwork with a 1" lining 3.) Flow Division Losses - 40% Area Reduction 4.) 6 Feet of Lined Flexible Duct with a 8" Diameter 5.) Linear Slot Diffuser End Reflection - 8" Mean Duct Width 6.) Space Effect Factor – V = 5000 cu. ft., R = 5 ft. 7.) Rectangular Tee Attenuation Entering Branch Duct 90 deg Elbow, 5" Mean Duct Width, No Lining) UNIT 03, 06, and 11 DISCHARGE TRANSFER FUNCTION (using the above factors 1.), 2.), 4.), 5.), & 6.)) UNIT 17, 24, 32, and 42 DISCHARGE TRANSFER FUNCTION (using all the above factors) 92 Performance Data Dual-Duct VAV Terminal Unit Acoustical Data Table PD-43 — Air Valve Size 24 Discharge Sound Data\ Air Valve Size VALV 24 Airflow (CFM) 2400 1800 1200 600 2400 1800 1200 600 2400 1800 1200 600 2400 1800 1200 600 Inlet Static Pressure (IN. W.G.) Min. Min. Min. Min. 1.5 1.5 1.5 1.5 2.0 2.0 2.0 2.0 3.0 3.0 3.0 3.0 2 67 60 49 39 71 66 58 51 72 68 62 57 74 70 64 59 3 63 55 44 34 66 62 55 52 67 63 59 61 69 65 61 63 Primary Valve Discharge Sound Octave Band 4 5 6 59 55 50 53 46 42 42 37 29 25 19 13 64 61 55 61 56 51 53 47 43 44 41 36 66 62 56 64 58 52 58 52 48 52 48 44 68 65 59 67 61 55 61 56 52 57 55 53 7 45 36 23 14 52 48 38 31 54 50 44 41 56 53 49 49 NC — — — — 17 — — — 19 — — — 21 16 — — 3 58 50 42 33 65 62 57 52 66 64 60 54 69 66 61 56 Primary Valve Discharge Sound Octave Band 4 5 6 51 46 44 44 40 36 34 30 23 23 18 14 59 50 46 58 46 40 47 38 31 42 36 29 62 52 47 61 49 42 53 44 36 46 41 34 67 57 49 65 54 46 54 48 41 52 51 44 7 35 27 17 16 39 34 25 23 40 36 32 30 44 41 36 38 NC 22 — — — 31 27 21 15 32 31 25 17 37 35 26 21 Table PD-44 — Air Valve Size 24 Radiated Sound Data Air Valve Size VALV 24 Airflow (CFM) 2400 1800 1200 600 2400 1800 1200 600 2400 1800 1200 600 2400 1800 1200 600 Inlet Static Pressure (IN. W.G.) Min. Min. Min. Min. 1.5 1.5 1.5 1.5 2.0 2.0 2.0 2.0 3.0 3.0 3.0 3.0 2 62 55 46 41 70 65 58 55 71 66 62 56 73 68 64 58 1. Inlet Static Pressure includes 0.5" downstream static pressure for ductwork and diffusers. 2. All data are measured in accordance with Industry Standard ARI 880. 3. All sound power levels, DB re: 10-12 Watts. 4. “MIN” inlet static pressure is the minimum primary wide open pressure drop of the unit at the specified primary airflow. Static pressures other than minimum reflect actual presure drop across the air valve. 5. “—” represents NC levels below NC 15. 6. When using different heating and cooling air valve sizes, select acoustical data for the largest air valve. This is due to testing procedures established by ARI 880. 7. NC Values are calculated using modeling assumptions based on ARI 885-90. RADIATED NC LEVEL ASSUMPTIONS: Octave Band 1.) Environmental Adjustment 2.) Mineral Fiber Ceiling Tile 5/8" thickness and 35 lb/ft3 density 3.) Space Effect Factor – V = 5000 cu. ft., R = 10 ft. RADIATED TRANSFER FUNCTION 2 -3 -9 -10 -22 3 -2 -10 -11 -23 4 -1 -12 -12 -25 2 -3 -2 3 -2 -6 4 -1 -16 -4 -6 -11 -7 -0 -4 -9 -6 -8 -0 -29 -33 5 -1 -14 -13 -28 6 -1 -15 -13 -29 7 -1 -15 -14 -30 5 -1 -45 6 -1 -45 7 -1 -27 -4 -23 -2 -9 -1 -4 -25 0 -10 -5 -4 -22 0 -10 -7 -4 -13 0 --11 -5 -31 -51 -81 -78 -52 -35 -56 -90 -89 -61 DISCHARGE NC LEVEL ASSUMPTIONS: Octave Band 1.) Environmental Adjustment 2.) 10 Feet of 12"x12" Rectangular Metal Ductwork with a 1" lining 3.) Flow Division Losses - 40% Area Reduction 4.) 6 Feet of Lined Flexible Duct with a 8" Diameter 5.) Linear Slot Diffuser End Reflection - 8" Mean Duct Width 6.) Space Effect Factor – V = 5000 cu. ft., R = 5 ft. 7.) Rectangular Tee Attenuation Entering Branch Duct 90 deg Elbow, 5" Mean Duct Width, No Lining) UNIT 03, 06, and 11 DISCHARGE TRANSFER FUNCTION (using the above factors 1.), 2.), 4.), 5.), & 6.)) UNIT 17, 24, 32, and 42 DISCHARGE TRANSFER FUNCTION (using all the above factors) 93 Performance Data Dual-Duct VAV Terminal Unit Acoustical Data Table PD-45 — Air Valve Size 32 Discharge Sound Data Air Valve Size VALV 32 Airflow (CFM) 3200 2400 1600 800 3200 2400 1600 800 3200 2400 1600 800 3200 2400 1600 800 Inlet Static Pressure (IN. W.G.) Min. Min. Min. Min. 1.5 1.5 1.5 1.5 2.0 2.0 2.0 2.0 3.0 3.0 3.0 3.0 2 69 62 50 39 72 66 62 56 73 68 63 60 75 70 65 64 Primary Valve Discharge Sound Octave Band 4 5 6 61 54 49 53 47 41 42 36 27 25 18 12 67 60 54 61 54 49 56 50 46 49 44 40 69 62 56 64 56 51 58 52 48 52 46 42 73 64 58 68 61 55 62 57 52 56 52 47 3 65 57 47 34 70 66 62 53 72 68 63 56 75 71 64 60 7 45 36 22 15 51 45 42 36 52 48 44 40 55 52 49 47 NC 16 — — — 22 17 — — 25 20 — — 29 24 15 — Table PD-46 — Air Valve Size 32 Radiated Sound Data Inlet Static Primary Valve Discharge Sound Airflow Pressure Octave Band (CFM) (IN. W.G.) 2 3 4 5 6 7 NC 3200 Min. 61 58 52 47 41 31 22 2400 Min. 55 52 45 40 32 22 15 1600 Min. 46 43 35 27 18 15 — 800 Min. 41 33 22 18 13 15 — 3200 1.5 69 64 57 51 43 35 30 2400 1.5 65 62 54 47 39 31 27 1600 1.5 60 58 50 43 35 28 22 800 1.5 54 50 42 37 30 26 — 3200 2.0 70 66 59 52 44 37 32 2400 2.0 66 64 57 49 41 34 30 1600 2.0 62 60 52 46 38 31 25 800 2.0 56 52 44 39 31 26 15 3200 3.0 72 69 63 56 47 41 36 2400 3.0 69 67 61 53 45 39 34 1600 3.0 64 62 55 49 42 35 27 800 3.0 59 56 49 44 36 29 20 1. Inlet Static Pressure includes 0.5" downstream static pressure for ductwork and diffusers. 2. All data are measured in accordance with Industry Standard ARI 880. 3. All sound power levels, DB re: 10-12 Watts. 4. “MIN” inlet static pressure is the minimum primary wide open pressure drop of the unit at the specified primary airflow. Static pressures other than minimum reflect actual presure drop across the air valve. 5. “—” represents NC levels below NC 15. 6. When using different heating and cooling air valve sizes, select acoustical data for the largest air valve. This is due to testing procedures established by ARI 880. 7. NC Values are calculated using modeling assumptions based on ARI 885-90. Air Valve Size VALV 32 RADIATED NC LEVEL ASSUMPTIONS: Octave Band 1.) Environmental Adjustment 2.) Mineral Fiber Ceiling Tile 5/8" thickness and 35 lb/ft3 density 3.) Space Effect Factor – V = 5000 cu. ft., R = 10 ft. RADIATED TRANSFER FUNCTION 2 -3 -9 -10 -22 3 -2 -10 -11 -23 4 -1 -12 -12 -25 2 -3 -2 3 -2 -6 4 -1 -16 -4 -6 -11 -7 -0 -4 -9 -6 -8 -0 -29 -33 5 -1 -14 -13 -28 6 -1 -15 -13 -29 7 -1 -15 -14 -30 5 -1 -45 6 -1 -45 7 -1 -27 -4 -23 -2 -9 -1 -4 -25 0 -10 -5 -4 -22 0 -10 -7 -4 -13 0 --11 -5 -31 -51 -81 -78 -52 -35 -56 -90 -89 -61 DISCHARGE NC LEVEL ASSUMPTIONS: Octave Band 1.) Environmental Adjustment 2.) 10 Feet of 12"x12" Rectangular Metal Ductwork with a 1" lining 3.) Flow Division Losses - 40% Area Reduction 4.) 6 Feet of Lined Flexible Duct with a 8" Diameter 5.) Linear Slot Diffuser End Reflection - 8" Mean Duct Width 6.) Space Effect Factor – V = 5000 cu. ft., R = 5 ft. 7.) Rectangular Tee Attenuation Entering Branch Duct 90 deg Elbow, 5" Mean Duct Width, No Lining) UNIT 03, 06, and 11 DISCHARGE TRANSFER FUNCTION (using the above factors 1.), 2.), 4.), 5.), & 6.)) UNIT 17, 24, 32, and 42 DISCHARGE TRANSFER FUNCTION (using all the above factors) 94 Performance Data Dual-Duct VAV Terminal Unit Acoustical Data Table PD-47 — Air Valve Size 42 Discharge Sound Data Air Valve Size VALV 42 Airflow (CFM) 4200 3150 2100 1050 4200 3150 2100 1050 4200 3150 2100 1050 4200 3150 2100 1050 Inlet Static Pressure (IN. W.G.) Min. Min. Min. Min. 1.5 1.5 1.5 1.5 2.0 2.0 2.0 2.0 3.0 3.0 3.0 3.0 2 72 64 54 42 76 71 64 58 77 72 66 62 78 74 69 66 3 67 59 49 37 72 67 63 55 73 68 64 58 74 70 66 63 Primary Valve Discharge Sound Octave Band 4 5 6 63 57 52 55 49 43 44 38 29 26 18 12 68 63 57 64 59 52 58 54 48 51 50 44 70 65 58 66 61 54 60 56 50 54 52 46 72 68 61 69 64 58 63 60 55 57 54 49 7 47 36 30 14 52 47 43 38 54 50 46 41 56 54 51 46 NC 19 — — — 25 19 — — 26 20 15 — 27 22 17 — 3 63 56 47 36 66 61 57 50 68 62 58 53 70 65 61 57 Primary Valve Discharge Sound Octave Band 4 5 6 56 51 44 49 42 36 42 31 22 24 18 14 59 54 47 55 49 42 51 44 38 43 39 34 60 56 48 57 50 44 53 46 40 45 40 36 63 58 51 61 54 47 56 50 44 48 44 40 7 33 23 15 15 40 35 32 28 42 38 35 30 45 42 40 35 NC 29 20 — — 32 25 21 — 35 27 22 — 37 31 26 21 Table PD-48 — Air Valve Size 42 Radiated Sound Data Air Valve Size VALV 42 Airflow (CFM) 4200 3150 2100 1050 4200 3150 2100 1050 4200 3150 2100 1050 4200 3150 2100 1050 Inlet Static Pressure (IN. W.G.) Min. Min. Min. Min. 1.5 1.5 1.5 1.5 2.0 2.0 2.0 2.0 3.0 3.0 3.0 3.0 2 65 58 50 41 71 66 60 53 72 67 62 56 75 70 65 59 1. Inlet Static Pressure includes 0.5" downstream static pressure for ductwork and diffusers. 2. All data are measured in accordance with Industry Standard ARI 880. 3. All sound power levels, DB re: 10-12 Watts. 4. “MIN” inlet static pressure is the minimum primary wide open pressure drop of the unit at the specified primary airflow. Static pressures other than minimum reflect actual presure drop across the air valve. 5. “—” represents NC levels below NC 15. 6. When using different heating and cooling air valve sizes, select acoustical data for the largest air valve. This is due to testing procedures established by ARI 880. 7. NC Values are calculated using modeling assumptions based on ARI 885-90. RADIATED NC LEVEL ASSUMPTIONS: Octave Band 1.) Environmental Adjustment 2.) Mineral Fiber Ceiling Tile 5/8" thickness and 35 lb/ft3 density 3.) Space Effect Factor – V = 5000 cu. ft., R = 10 ft. RADIATED TRANSFER FUNCTION 2 -3 -9 -10 -22 3 -2 -10 -11 -23 4 -1 -12 -12 -25 2 -3 -2 3 -2 -6 4 -1 -16 -4 -6 -11 -7 -0 -4 -9 -6 -8 -0 -29 -33 5 -1 -14 -13 -28 6 -1 -15 -13 -29 7 -1 -15 -14 -30 5 -1 -45 6 -1 -45 7 -1 -27 -4 -23 -2 -9 -1 -4 -25 0 -10 -5 -4 -22 0 -10 -7 -4 -13 0 --11 -5 -31 -51 -81 -78 -52 -35 -56 -90 -89 -61 DISCHARGE NC LEVEL ASSUMPTIONS: Octave Band 1.) Environmental Adjustment 2.) 10 Feet of 12"x12" Rectangular Metal Ductwork with a 1" lining 3.) Flow Division Losses - 40% Area Reduction 4.) 6 Feet of Lined Flexible Duct with a 8" Diameter 5.) Linear Slot Diffuser End Reflection - 8" Mean Duct Width 6.) Space Effect Factor – V = 5000 cu. ft., R = 5 ft. 7.) Rectangular Tee Attenuation Entering Branch Duct 90 deg Elbow, 5" Mean Duct Width, No Lining) UNIT 03, 06, and 11 DISCHARGE TRANSFER FUNCTION (using the above factors 1.), 2.), 4.), 5.), & 6.)) UNIT 17, 24, 32, and 42 DISCHARGE TRANSFER FUNCTION (using all the above factors) 95 Performance Data Dual-Duct VAV Terminal Unit Acoustical Data Table PD-49 — Primary Air Valve Discharge Sound Data, ARI Conditions Air Valve Size VALV 03 VALV 06 VALV 11 VALV 17 VALV 24 VALV 32 VALV 42 Airflow (CFM) 250 400 700 1100 1600 2100 2800 Inlet Static Pressure (IN. W.G.) 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2 62 62 63 65 64 64 69 3 58 57 55 59 61 64 66 Primary Valve Discharge Sound Octave Band 4 5 55 53 54 52 57 52 60 53 60 54 59 52 62 57 6 44 44 45 48 49 48 51 7 41 39 41 45 46 44 46 Primary Valve Discharge Sound Octave Band 4 5 46 42 48 44 50 43 52 44 56 45 52 46 54 47 6 34 36 36 36 38 38 41 7 27 30 30 31 32 30 34 Table PD-50 — Primary Air Valve Radiated Sound Data, ARI Conditions Air Valve Size VALV 03 VALV 06 VALV 11 VALV 17 VALV 24 VALV 32 VALV 42 Airflow (CFM) 250 400 700 1100 1600 2100 2800 Inlet Static Pressure (IN. W.G.) 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2 55 56 60 61 63 63 64 3 51 51 55 57 61 60 60 1. All data are measured in accordance with Industry Standard ARI 880. 2. All sound power levels, DB re: 10-12 Watts. 3. Appuurtenances, such as multiple outlet connections, reheat coils, etc. are not a part of the ARI Certification program. Certified ratings could be affected by their use. Table PD-51 — Average Appurtenance Effect – Single Duct Attenuator Air Valve Size VALV 03 VALV 06 VALV 11 VALV 17 VALV 24 VALV 32 VALV 42 2 -2 -3 0 0 -1 0 -1 3 -4 -4 -3 -2 -3 1 -1 Primary Valve Discharge Sound Octave Band 4 5 -10 -17 -9 -16 -7 -13 -6 -11 -5 -12 -4 -9 -4 -8 1. When using different heating and cooling air valve sizes, select acoustical data for the largest air valve. 96 6 -25 -26 -24 -15 -11 -10 -8 7 -16 -17 -13 -11 -8 -8 -5 Jobsite Connections Single Duct VAV Terminal Units VCEE – Pneumatic Control – Heater Terminal Box 277/60/1, 347/60/1 VCEE – Pneumatic Control – Heater Terminal Box 480/60/1, 575/60/1 97 Jobsite Connections Single Duct VAV Terminal Units VCEE – Pneumatic Control – Heater Terminal Box 208/60/1, 240/60/1 98 Jobsite Connections Single Duct VAV Terminal Units VCEE – Pneumatic Control – Heater Terminal Box 480/60/3 VCEE – Pneumatic Control – Heater Terminal Box 208/60/3, 575/60/3 99 Jobsite Connections Single Duct VAV Terminal Units VCEE – Electronic or DDC/UCM – Heater Terminal Box 277/60/1, 347/60/1 VCEE – Electronic or DDC/UCM – Heater Terminal Box 208/60/1, 240/60/1, 480/60/1, 575/60/1 100 Jobsite Connections Single/Dual-Duct VAV Terminal Units VCEE – Electronic or DDC/UCM – Heater Terminal Box 208/60/3, 480/60/3, 575/60/3 101 Jobsite Connections Electric Heat Terminal with Electronic or Direct Digital Controls Hot Water or Cooling Only Terminal with Electric or Direct Digital Controls 102 Single Duct VAV Terminal Units Dimensional Data 103 Single Duct VAV Terminal Units Dimensional Data 104 Single Duct VAV Terminal Units Dimensional Data 105 Single Duct VAV Terminal Units Dimensional Data 106 Single Duct VAV Terminal Units Dimensional Data Slip and Drive Connections 107 Single Duct VAV Terminal Units Dimensional Data 108 Dual Duct VAV Terminal Units Dimensional Data 109 Dual Duct VAV Terminal Units Dimensional Data 110 Dual Duct VAV Terminal Units Dimensional Data 111 Single/Dual-Duct VAV Terminal Units MODELS VCCE, VCWE and VCEE Single-Duct Terminal Units CASING 22 gauge galvanized steel. AGENCY LISTING Agency Listing – The unit is UL and Canadian UL listed as a room air terminal unit. Control # 9N65. ARI 880 Listed. INSULATION 1 /2" Matte Insulation – The interior surface of the unit casing is acoustically and thermally lined with 1/2-inch, 1.75 lb./cu. ft. density glass fiber with a high density facing. The insulation R-Value is 1.9. The insulation is UL listed and meets NFPA-90A and UL 181 standards. 1" Matte Insulation – The interior surface of the unit casing is acoustically and thermally lined with 1 inch, 1.55 lb./ cu. ft. density glass fiber with a high density facing. The insulation R-Value is 3.8. The insulation is UL listed and meets NFPA-90A and UL 181 standards. 1 /2" Foil Faced Insulation – The interior surface of the unit casing is acoustically and thermally lined with 1/2-inch, 2.0 lb./ cu. ft. density glass fiber with foil facing. The insulation R-Value is 2.2. The insulation is UL listed and meets NFPA-90A and UL 181 standards as well as bacteriological standard ASTM C 665. Mechanical Specifications Single-Duct VAV Terminal Units 1" Double-Wall Insulation – The interior surface of the unit casing is acoustically and thermally lined with a 1-inch 1.55 lb./cu. Ft. density glass fiber with high density facing. The insulation R-value is 3.8. The insulation is UL listed and meets NFPA-90A and UL 181 standards. The insulation is covered by an interior liner made of 26 gauge galvanized steel. All cut edges of the insulation are covered by metal flanges and all wire penetrations are covered by grommets. OUTLET CONNECTION PRIMARY AIR VALVE Cylindrical flow control device with integral pneumatic or electric actuator. The valve inlet is die cast aluminum and tapered to fit standard round flexible ductwork. Maximum leak rate is 1% at 4-inches wg. inlet static pressure. Integral multiple point, averaging flow sensing ring is provided for primary airflow measurement within ± 5% of unit nominal airflow with 11/2 diameters of straight duct upstream of the unit. Integral flow taps and a calibration chart are provided on each unit. Air valve sizes available: Air Valve Size 03 06 11 17 24 32 42 Nominal Airflow 300 CFM 600 CFM 1100 CFM 1700 CFM 2400 CFM 3200 CFM 4200 CFM 1" Foil Faced Insulation – The interior surface of the unit casing is acoustically and thermally lined with 1-inch, 2.0 lb./ cu. ft. density glass fiber with foil facing. The insulation R-Value is 4.3. The insulation is UL listed and meets NFPA-90A and UL 181 standards as well as bacteriological standard ASTM C 665. Flanged Connection – A rectangular opening on the unit discharge to accept a 90 degree flanged ductwork connection. Slip and Drive Connection – A slip and drive connection has two straight flanges on the top and bottom and two drive connections on the left and right sides. The drive sides are straight flanges which form a “U” shape. The mating ductwork has a similar setup. The two top and bottom pieces are shaped like a compressed “S” with sealant in the hollow of the “S”. These pieces will slide over the top and bottom straight flanges. The top and bottom flanges of the mating ductwork will slide into the other side of these pieces. The two side-pieces are shaped like a “C” and are called “Drives”. These pieces will slide over the “U” shaped flanges so the connection can not be pulled apart. These pieces are usually hammered into place. No screws are required and by removing the drives, the ducts may be disconnected. Integral Outlets – A sheet metal box with circular opening(s) is factory connected to the main unit. The circular opening(s) are centered on the unit plenum to accept round ductwork connections. Integral Outlets with Balancing Dampers – A sheet metal box with circular opening(s) is factory connected to the main unit. The circular opening(s) with balancing damper(s) are centered on the unit plenum to accept round ductwork connections. HOT WATER COIL The hot water reheat coil is factory mounted on the discharge outlet. Coils are available in standard or high capacity versions. Standard capacity coils have 144 aluminum Sigma-Flo plated fins per foot. High capacity coils have 192 aluminum Sigma-Flo plated fins per foot. Full fin collars are provided for accurate fin spacing and maximum fin-tube contact. Seamless copper tubes are mechanically expanded into the fin collars. Coils are leak tested at 300 psig air pressure under water. Female sweat-type water connections are provided, with sameside connections. Both right hand and left hand connections are available for the units. 1/2" Double-Wall Insulation – The interior surface of the unit casing is acoustically and thermally lined with 1/ 2-inch, 1.75 lb./cu. ft. density glass fiber with a high density facing. The insulation R-Value is 1.9. The insulation is UL listed and meets NFPA-90A and UL 181 standards. The insulation is covered by an interior liner made of 26 gauge galvanized steel. All cut edges of the insulation are covered by metal flanges and all wire penetrations are covered by grommets. 112 ELECTRIC HEAT COIL The coil is factory provided and mounted on the discharge outlet. The coils have a resistance open-type heater with a disc-type automatic reset thermal primary safety device. Heater element material is nickel-chromium. The heater terminal box is provided with 7/8" knockouts for customer power supply. Terminal connections are plated steel with ceramic or phenolic insulators. Electric Heat Options Transformer An optional 50 VA transformer is an integral component of the heater control panel to provide 24 VAC for controls. Contactors Magnetic Contactor – An electric heater contact for use with direct digital control or analog electronic controls. Mercury Contactor – An electric heater contact for use with direct digital control or analog electronic controls. P.E. Switch with Magnetic Contactor – This switch and magnetic contact is for use with an electric heater with pneumatic controls. P.E. Switch with Mercury Contactor – This switch and mercury contact is for use with an electric heater with pneumatic controls. Airflow Switch An air pressure device designed to disable the heater when the unit fan is off. Line Fuse A safety fuse located in the electric heater’s line of power to prevent power surge damage to the electric heater. Disconnect Switch A factory provided disconnect switch with an interlocking door on the heater control panel. UNIT CONTROLS SEQUENCE OF OPERATION The unit controller continuously monitors the zone temperature against its setpoint and varies the primary airflow as required to meet zone setpoints. Airflow is limited by minimum and maximum position setpoints. Upon a further call for heat after the air valve is at minimum, any hot water or electric heat associated with the unit is enabled. Mechanical Specifications Single-Duct VAV Terminal Units DIRECT DIGITAL CONTROLS System Communications – The Controller is designed to send and receive data from a Tracer Summit® or Tracer VAV Command Unit configuration. Current unit status conditions and setpoints may be monitored and/or edited via this data communication feature. The network type is a twisted wire pair shielded serial communication. DDC Actuator – Electric pressureindependent. Integral to patented Trane air valve. The actuator operates using a 24 VAC signal. Travel is terminated by end switches at fully open and closed positions to eliminate motor stall. Direct Digital Controller – The microprocessor based terminal unit controller provides accurate, pressureindependent control through the use of a proportional integral control algorithm and direct digital control technology. The controller, named the Unit Control Module or UCM, monitors zone temperature setpoints, zone temperature and its rate of change and valve airflow, using a differential pressure signal. The controller is provided in an enclosure with 7/8" knockouts for remote control wiring. A Trane UCM zone sensor is required. UCM Zone Sensor – The UCM controller senses zone temperature through a sensing element located in the zone sensor. In addition to the sensing element, zone sensor options may include an externally adjustable setpoint, communications jack for use with a portable edit device and an override button to change the individual controller from unoccupied to occupied mode. The override button has a cancel feature that will return the system to unoccupied. Wired zone sensors utilize a thermistor to vary the voltage output in response to changes in the zone temperature. Wiring to the UCM controller must be 18 to 22 awg. twisted pair wiring. The setpoint adjustment range is 50 - 88 F. Depending upon the features available in the model of sensor selected, the zone sensor may require from a 2-wire to a 5-wire connection. Wireless zone sensors report the same zone information as wired zone sensors, but do so using radio transmitter technology. No wiring from the zone sensor to the UCM controller is necessary. 113 The following direct digital control options are available with VariTrane single-duct terminal units: 1. Controls Option DD00 – Electric Actuator Wired to a Terminal Strip 2. Controls Option DD01 – Basic Operation: Cooling Only - No Remote Heat 3. Controls Option DD02 – Basic Operation: Normally Closed On/Off Hot Water Valve (Normally Open Outputs) 4. Controls Option DD03 – Basic Operation: Proportional Hot Water Valve (Normally Open Outputs) 5. Controls Option DD04 – Basic Operation: On/Off Staged Electric Heat (Normally Open Outputs) 6. Controls Option DD05 – Basic Operation: Pulse Width Modulation of Electric Heat (Normally Open Outputs) 7. Controls Option DD07 – Basic Operation: Normally Open On/Off Hot Water Valve (Normally Closed Outputs) 8. Controls Option FM00 – Factory Mounting of Customer Supplied Controls The following override commands may be received by the Unit Control Module (UCM) from the Tracer Summit® or Tracer Command Unit configuration. 1. Control Mode – The UCM Control Mode may be edited from occupied to unoccupied to accommodate night setback / setup. 2. Control Action – The Control Action may be edited from cooling to heating, changing the primary air damper to a heating source. This will accommodate a cooling / heating changeover system. 3. Control Offset – Enabling Control Offset will increase the cooling temperature setpoint and decrease the heating temperature setpoint by a control offset value stored at the UCM. This function facilitates demand limiting in the occupied mode. 4. Drive damper fully open. 5. Drive damper fully closed. 6. Drive damper to maximum airflow setpoint. 7. Drive damper to minimum airflow setpoint. 8. Disable unit fan. 9. Disable unit heat. 10. Reset – Enabling the reset function forces the controller and the flow sensor to recalibrate. 11. Programmable hot water valve drive time. 12. Programmable air damper drive time. The following unit setpoints reside in the UCM in nonvolatile memory. These setpoints are editable from the Command Unit or Tracer via the communications link. 1. Occupied cooling temperature setpoint (60 - 80 F). 2. Occupied heating temperature setpoint (60 - 80 F). 3. Unoccupied cooling temperature setpoint (60 - 100 F). 4. Unoccupied heating temperature setpoint (30 - 100 F). 5. Minimum cooling flow setpoint (0, 10- 110% of unit equivalent nominal airflow). 6. Minimum heating flow setpoint (0, 10 - 110% of unit equivalent nominal airflow). 7. Maximum flow setpoint (0, 10 110% of unit equivalent nominal airflow. Must be greater than or equal to minimum). Mechanical Specifications Single-Duct VAV Terminal Units 8. Heating Setpoint Offset – This determines at what point the first stage of reheat turns on. Expressed in degrees below cooling setpoint. 9. Zone temperature, auxiliary temperature and zone setpoint calibration corrections (adjustable from ±10.0 F). 10. Flow measurement calibration correction (50 - 150%). 11. Cooling Setpoint Low Limit Applies low limit to programmed occupied cooling setpoint or zone sensor cooling setpoint (0 - 100 F). 12. Heating Setpoint High Limit – Applies high limit to programmed occupied heating setpoint or zone sensor heating setpoint (0 - 100 F). 13. RTD / Thermistor – Determines what type of zone temperature sensor will be used. 14. Occupied and Unoccupied Outside Air Requirements – Determines the percent of outdoor air required in the zone for air quality requirements. ANALOG ELECTRONIC CONTROLS In addition to the above setpoints, the following status information can be transmitted to the Tracer Summit® or Tracer Command Unit configuration. 1. Active cooling temperature setpoint. 2. Active heating temperature setpoint. 3. Current unit primary airflow. 4. Current zone temperature. 5. Unit heat status (On/Off). 6. Auxiliary Air Temperature – Available only if the unit has an auxiliary temperature sensor. 7. Failure-Indicators – The UCM will indicate the following: 8. Temperature Sensor Failure 9. Flow Sensor Failure 10. Local Zone Sensor Setpoint Failure 11. Communications Line Failure 12. Ventilation Ratio. 114 Analog Actuator – An electric actuator is integral to a patented Trane air valve. The actuator operates by a 24 VAC signal. Travel is terminated by end switches at fully open and closed positions to eliminate motor stall. Analog Electronic Controller – The controller consists of a circuit board that offers basic VAV unit operation and additional override functions and operates using 24 VAC power. The controller uses a capacitive type pressure transducer to maintain consistent air delivery regardless of system pressure changes in an enclosure with 7/8" knockouts for remote control wiring. A Trane electronic zone sensor is required. Electronic Zone Sensor This single temperature, wall mounted electronic device utilizes a thermistor to vary the voltage output in response to changes in the zone temperature. Connections to the VAV unit circuit board are made using standard three conductor thermostat wire. The setpoint adjustment range is 63 - 85 F. The sensor is available in two models. One model has a concealed, internally adjustable setpoint. The other model has an externally adjustable setpoint. The following analog electronic control options are available with VariTrane single-duct terminal units: 1. Controls Option EI01 – Basic Operation: VAV Cooling Only 2. Controls Option EI05 – Basic Operation: VAV Cooling with Reheat 3. Controls Option EI28 – Basic Operation: VAV Cooling with Reheat Auto Dual Minimum 4. Controls Option EI29 – Basic Operation: VAV Cooling with Reheat Constant Volume 5. Controls Option EI30 – Basic Operation: VAV Cooling - Constant Volume PNEUMATIC CONTROLS Pneumatic Actuator – A normally open or normally closed pneumatic actuator is integral to a patented Trane air valve. The type of actuator will vary depending upon the pneumatic control option selected. The normally open actuator operates over a 3 to 8 psig spring range. The normally closed actuator operates over an 8 to 13 psig spring range. 2017 Volume Regulator – Factory mounted and piped to the actuator. The regulator is a thermostat reset velocity controller which provides consistent air delivery within 10% of nominal flow down to 25% of unit nominal cfm, independent of changes in system static pressure. Factory calibrated, field adjustable setpoints for minimum and maximum flows. Average total unit main air consumption, excluding thermostat, is 12 scim at 20 psig supply. 3025 Volume Regulator Factory mounted and piped to the actuator. The regulator is a thermostat reset velocity controller which provides consistent air delivery within 5% of nominal flow down to 15% of unit nominal cfm, independent of changes in system static pressure. Factory calibrated, field adjustable setpoints for minimum and maximum flows. Average total unit main air consumption, excluding thermostat, is 46.1 scim at 20 psig supply. Room Thermostat – As needed by the chosen control option, a direct-acting or a reverse-acting, one-pipe or twopipe pneumatic room thermostat shall control the available air valve, reheat and fan switch to maintain room temperature setpoint. Room thermostat is field supplied and installed. The following pneumatic control options are available with VariTrane single-duct terminal units: 1. Controls Option PN01 – Normally Open Valve Actuator Only, (Reverse-Acting Thermostat) 2. Controls Option PN04 – Normally Open Valve Actuator, 3025 Volume Regulator, (Direct-Acting Thermostat) Mechanical Specifications Single-Duct VAV Terminal Units 3. Controls Option PN05 – Normally Open Valve Actuator, 3025 Volume Regulator, (Reverse-Acting Thermostat) 4. Controls Option PN06 – Normally Open Valve Actuator, 2017 Volume Regulator, (Direct-Acting Thermostat) 5. Controls Option PN07 – Normally Open Valve Actuator, 2017 Volume Regulator, (Reverse-Acting Thermostat) 6. Controls Option PN30 – Normally Open Valve Actuator, 3025 Volume Regulator, Constant Volume 7. Controls Option PN31 – Normally Open Valve Actuator, 2017 Volume Regulator, Constant Volume 8. Controls Option PN32 – Normally Open Valve Actuator, 3025 Volume Regulator, Constant Volume, (Direct-Acting Thermostat) 9. Controls Option PN33 – Normally Open Valve Actuator, 2017 Volume Regulator, Constant Volume, (Direct-Acting Thermostat) 10. Controls Option PN34 – Normally Open Valve Actuator, 3025 Volume Regulator, Constant Volume, (Reverse-Acting Thermostat) 11. Controls Option PN35 – Normally Open Valve Actuator, 2017 Volume Regulator, Constant Volume, (Reverse-Acting Thermostat) 12. Controls Option PC01 – Normally Closed Valve Actuator Only (DirectActing Thermostat) 13. Controls Option PC02 – Normally Closed Valve Actuator, 3025 Volume Regulator, (Direct-Acting Thermostat) HOT WATER VALVES OPTIONS Access Panel A 105/8" x 105/8" access panel is provided and centered in the bottom of the unit for access to the primary air valve. Transformer The 50 VA transformer is factory mounted in an enclosure with 7/8" knockouts to provide 24 VAC for controls. Disconnect Control Breaks both power wiring legs entering controls box. Fuse Control Optional fuse is factory mounted in the primary voltage hot leg. 115 Two-Position Valve The valve is a field adaptable 2-way or 3-way configuration and ships with a cap to be field installed when configured as a 2-way valve. All connections are National Pipe Thread (NPT). The valve body is forged brass with a stainless steel base and bearing plate. The cover is aluminum. The actuator is a hysteresis synchronous motor. Upon demand, the motor strokes the valve. When the actuator drive stops, a spring returns the valve to its fail-safe position. Pressure and Temperature Ratings Maximum system pressure - 300 psi. Maximum static pressure - 400 psi. Overall Diameter - 1/2" NPT Flow Capacity - 1.0 Cv, 2.5 Cv, 5.0 Cv Close Off Pressure - 50 psi, 25 psi, 10 psi Electrical Rating - 6.5 VA at 24 VAC. An eight foot long plenum rated wire lead is provided. Proportional Water Valve The valve is a field adaptable 2-way or 3-way configuration and ships with a cap over the bottom port. This configures the valve for 2-way operation. For 3-way operation, remove the cap and install a NPT adapter. Adequate adapters are included for all configurations. The valve is designed with an equal percentage plug. The intended fluid is water or water and glycol (50% maximum glycol). The actuator is a synchronous motor drive. The valve is driven to a predetermined position by the UCM controller using a proportional plus integral control algorithm. If power is removed, the valve stays in its last position. The actuator is plastic material and rated for plenum applications under UL 94-5V and UL 873 standards. Pressure and Temperature Ratings The valve is designed and tested in full compliance with ANSI B16.15 Class 250 pressure/temperature ratings, ANSI B16.104 Class IV control shutoff leakage and ISA S75.11 flow characteristic standards. Flow Capacity - 4.60 Cv, 1.80 Cv, 0.73 Cv Overall Diameter - 1/2-inch NPT Maximum Operating Pressure 345 psi, 281 F Maximum Actuator Close-Off Pressure - 55 psi Electrical Rating - 4.0 VA at 24 VAC. 10 ft. of plenum rated 22 gauge wire for connection. Terminations are #6 stabs. MODEL VDDE Dual-duct terminal unit. CASING 22 gauge galvanized steel. AGENCY LISTING Agency Listing – The unit is UL and Canadian UL listed as a room air terminal unit. Control # 9N65. ARI 880 Listed. INSULATION 1/2" Matte Insulation – The interior surface of the unit casing is acoustically and thermally lined with 1/2-inch, 1.75 lb./cu. ft. density glass fiber with a high density facing. The insulation R-Value is 1.9. The insulation is UL listed and meets NFPA-90A and UL 181 standards. 1" Matte Insulation – The interior surface of the unit casing is acoustically and thermally lined with 1inch, 1.55 lb./ cu. ft. density glass fiber with a high density facing. The insulation R-Value is 3.8. The insulation is UL listed and meets NFPA-90A and UL 181 standards. 1/2" Foil Faced Insulation – The interior surface of the unit casing is acoustically and thermally lined with 1/2-inch, 2.0 lb./cu. ft. density glass fiber with foil facing. The insulation R-Value is 2.2. The insulation is UL listed and meets NFPA-90A and UL 181 standards as well as bacteriological standard ASTM C 665. Mechanical Specifications Dual-Duct VAV Terminal Units 1" Double-Wall Insulation – The interior surface of the unit casing is acoustically and thermally lined with a 1-inch 1.55 lb./cu. Ft. density glass fiber with high density facing. The insulation R-value is 3.8. The insulation is UL listed and meets NFPA-90A and UL 181 standards. The insulation is covered by an interior liner made of 26 gauge galvanized steel. All cut edges of the insulation are covered by metal flanges and all wire penetrations are covered by grommets. OUTLET CONNECTION Flanged sheet metal connection at unit discharge to facilitate ductwork installation. PRIMARY AIR VALVES Cylindrical flow control devices with integral pneumatic or electric actuators. The valve inlets are die cast aluminum and tapered to fit standard round flexible ductwork. Maximum leak rate is 1% at 4 inches wg. inlet static pressure. Integral multiple point, averaging flow sensing rings are provided for primary airflow measurement within ± 5% of unit nominal airflow with 1 1/2 diameters of straight duct upstream of the unit. Integral flow taps and a calibration chart are provided on each unit. Air valve sizes available: Two air valves provided. Air Valve Size 03 06 11 17 24 32 42 Nominal Airflow 300 CFM 600 CFM 1100 CFM 1700 CFM 2400 CFM 3200 CFM 4200 CFM 1" Foil Faced Insulation – The interior surface of the unit casing is acoustically and thermally lined with 1-inch, 2.0 lb./ cu. ft. density glass fiber with foil facing. The insulation R-Value is 4.3. The insulation is UL listed and meets NFPA-90A and UL 181 standards as well as bacteriological standard ASTM C 665. 1/2" Double-Wall Insulation – The interior surface of the unit casing is acoustically and thermally lined with 1/ 2-inch, 1.75 lb./cu. ft. density glass fiber with a high density facing. The insulation R-Value is 1.9. The insulation is UL listed and meets NFPA-90A and UL 181 standards. The insulation is covered by an interior liner made of 26 gauge galvanized steel. All cut edges of the insulation are covered by metal flanges and all wire penetrations are covered by grommets. 116 Integral Outlets – A sheet metal box with circular opening(s) is factory connected to the main unit. The circular opening(s) are centered on the unit plenum to accept round ductwork connections. Integral Outlets with Balancing Dampers – A sheet metal box with circular opening(s) is factory connected to the main unit. The circular opening(s) with balancing damper(s) are centered on the unit plenum to accept round ductwork connections. ACCESS PANEL The entire bottom panel is removable to provide access to the primary air valves. UNIT CONTROLS SEQUENCE OF OPERATION The unit controller continuously monitors the zone temperature against its setpoint and varies the primary airflow as required to meet zone setpoints. Airflow is limited by minimum and maximum position setpoints. DIRECT DIGITAL CONTROLS DDC Actuators – Electric pressureindependent. Integral to patented Trane air valve. The actuators operate using a 24 VAC signal. Travel is terminated by end switches at fully open and closed positions to eliminate motor stall. Direct Digital Controller – The microprocessor based terminal unit controller provides accurate, pressureindependent control through the use of a proportional integral control algorithm and direct digital control technology. The controller, named the Unit Control Module or UCM, monitors zone temperature setpoints, zone temperature and its rate of change and valve airflow, using a differential pressure signal. The controller is provided in an enclosure with 7/8" knockouts for remote control wiring. A Trane UCM zone sensor is required. UCM Zone Sensor – The UCM controller senses zone temperature through a sensing element located in the zone sensor. In addition to the sensing element, zone sensor options may include an externally adjustable setpoint, communications jack for use with a portable edit device and an override button to change the individual controller from unoccupied to occupied mode. The override button has a cancel feature which will return the system to unoccupied. Wired zone sensors utilize a thermistor to vary the voltage output in response to changes in the zone temperature. Wiring to the UCM controller must be 18 to 22 awg. twisted pair wiring. The setpoint adjustment range is 50 - 88 F. Depending upon the features available in the model of sensor selected, the zone sensor may require from a 2-wire to a 5-wire connection. Wireless zone sensors report the same zone information as wired zone sensors, but do so using radio transmitter technology. No wiring from the zone sensor to the UCM controller is necessary. Mechanical Specifications Dual-Duct VAV Terminal Units System Communications – The Controller is designed to send and receive data from a Tracer Summit® or Tracer Command Unit configuration. Current unit status conditions and setpoints may be monitored and/or edited via this data communication feature. The network type is a twisted wire pair serial communication. The following unit setpoints reside in the UCM in nonvolitale memory. These setpoints are editable from the Tracer Summit® or Tracer Command Unit via the communications link. 1. Occupied cooling temperature setpoint (60 - 80 F). 2. Occupied heating temperature setpoint (60 - 80 F). 3. Unoccupied cooling temperature setpoint (60 - 100 F). 4. Unoccupied heating temperature setpoint (30 - 100 F). 5. Minimum cooling flow setpoint (0, 10 - 110% of unit equivalent nominal airflow). 6. Minimum heating flow setpoint (0, 10 - 110% of unit equivalent nominal airflow). 7. Maximum flow setpoint (0, 10 110% of unit equivalent nominal airflow. Must be greater than or equal to minimum.). 8. Heating Setpoint Offset – This determines at what point the first stage of reheat turns on. Expressed in degrees below cooling setpoint. 9. Zone temperature, auxiliary temperature and zone setpoint calibration corrections (adjustable from ±10.0 F). 10. Flow measurement calibration correction (50 - 150%). 11. Cooling Setpoint Low Limit – Applies low limit to programmed occupied cooling setpoint or zone sensor cooling setpoint (30 - 100 F). 12. Heating Setpoint High Limit – Applies high limit to programmed occupied heating setpoint or zone sensor heating setpoint (30 - 100 F). 13. RTD / Thermistor – Determines what type of zone temperature sensor will be used. 14. Occupied and Unoccupied Outside Air Requirements – Determines the percent of outdoor air required in the zone for air quality requirements. The following direct digital control options are available with VariTrane dual-duct units: 1. Controls Option DD00 – Electric Actuators Wired to Terminal Strips 2. Controls Option DD01 – Basic Operation - Air Valve Only Control 3. Controls Option FM00 – Factory Mounting of Customer Supplied Controls The following override commands may be received by the Unit Control Module (UCM) from the Tracer Summit® or Tracer Command Unit configuration. 1. Control Mode – The UCM Control Mode may be edited from occupied to unoccupied to accommodate night setback / setup. 2. Control Action – The Control Action may be edited from cooling to heating, changing the primary air damper to a heating source. This will accommodate a cooling / heating changeover system. 3. Control Offset – Enabling Control Offset will increase the cooling temperature setpoint and decrease the heating temperature setpoint by a control offset value (stored at limiting in the occupied mode). 4. Drive damper fully open. 5. Drive damper fully closed. 6. Drive damper to maximum airflow setpoint. 7. Drive damper to minimum airflow setpoint. 8. Disable unit fan. 9. Disable unit heat. 10. Reset – Enabling the reset function forces the controller and the flow sensor to recalibrate. 11. Programmable hot water valve drive time. 12. Programmable air damper drive time. 117 Mechanical Specifications Dual-Duct VAV Terminal Units In addition to the previous setpoints, the following status information can be transmitted to the Tracer Summit® or Tracer Command Unit configuration. 1. Active cooling temperature setpoint. 2. Active heating temperature setpoint. 3. Current unit primary airflow. 4. Current zone temperature. 5. Unit heat status (On/Off). 6. Auxiliary Air Temperature – Available only if the unit has an auxiliary temperature sensor. 7. Failure Indicators – The UCM will indicate the following: • Temperature Sensor Failure • Flow Sensor Failure • Local Zone Sensor Setpoint Failure • Communications Line Failure 8. Ventilation Ratio. Room Thermostat – As needed by the chosen control option, a direct-acting or a reverse-acting, one-pipe or twopipe pneumatic room thermostat shall control the available air valve, reheat and fan switch to maintain room temperature setpoint. Room thermostat is field supplied and installed. PNEUMATIC CONTROLS Pneumatic Actuators – Pneumatic actuators are integral to patented Trane air valves. Normally open pneumatic actuators operate over a 3 to 8 psig spring range. Normally closed pneumatic actuators operate over an 8 to 13 psig spring range. 3025 Volume Regulators – Factory mounted and piped to the actuators. The regulators are thermostat reset velocity controllers which provide consistent air delivery within 5% of nominal flow down to 15% of unit nominal cfm, independent of changes in system static pressure. Factory calibrated, field adjustable setpoints for minimum and maximum flows. Average total unit main air consumption, excluding thermostat, is 46.1 scim at 20 psig supply. 3525 Volume Regulators – Factory mounted and piped to the actuators. The regulators are thermostat reset velocity controllers which provide consistent air delivery within 10% of nominal flow down to 25% of unit nominal cfm, independent of changes in system static pressure. Factory calibrated, field adjustable setpoints for minimum and maximum flows. Average total unit main air consumption, excluding thermostat, is 58 scim at 20 psig supply. 118 The following pneumatic control options are available with VariTrane dual-duct units 1. Controls Option PN08 – Normally Open Heating Valve Actuator, Normally Open Cooling Valve Actuator Only (Reverse-Acting Thermostat) 2. Controls Option PN09 – Normally Open Heating Valve Actuator, 3025 Volume Regulator, Normally Open Cooling Valve Actuator, 3025 Volume Regulator, (Direct-Acting Thermostat) 3. Controls Option PN10 – Normally Open Heating Valve Actuator, 3525 Volume Regulator, Normally Open Cooling Valve Actuator, 3525 Volume Regulator, Constant Volume Unit Discharge, (Direct-Acting Thermostat) 4. Controls Option PC03 – Normally Closed Heating Valve Actuator, 3025 Volume Regulator, Normally Open Cooling Valve Actuator, 3025 Volume Regulator, (Direct-Acting Thermostat) OPTIONS TRANSFORMER The 50 VA transformer is factory mounted in an enclosure with 7/8" knockouts to provide 24 VAC for controls. DISCONNECT Control – Breaks both power wiring legs entering controls box. FUSE Control – Optional fuse is factory mounted in the primary voltage hot leg.