TOSHIBA
Transcription
TOSHIBA
No. 2A201-384E”C TOSHIBA SITE PLANNING FOR WHOLE-BODY X-RAY CT SCANNER 4 steion MODELS MANUAL SERIES TSX-021A, TSX-OZIB (2A201-384E*C) TOSHIBA @ TOSHIBA CORPORATION CORPORATION ALL RIGHTS RESERVED 1998 No. 9. 9.1 AIR CONDITIONING/WATER Air Conditioning (1) Air conditioning SUPPLY AND DRAINAGE 2A201-384E WORKS system Refer to calorific values and environmental requirements of each room given in appended table 1 and install an air conditioning system which satisfies the given environmental requirements. Insure appropriate air flow in the rooms so that temperature distribution is uniform. Take extreme care with air conditioning Temperature fluctuation in this room in the specification. The temperature throughout year. It is important to calibration data is acquired as when It is recommended, however, that the approximately 26% for patient comfort. in the scanning room. must be within the range given setting need not be constant have the same temperature when examinations are performed. temperature be maintained at The temperature in the scanning room should be within the tolerance 1.5 hours before the first examination every morning. When the door is opened, for example, to bring the patient in or out, the temperature can be outside the tolerance for a short time (approximately 3 minutes). The appropriate temperature, however, should be restored until scanning of the next patient is started. In addition, take care that the temperature near the floor does not get too low or high, because air near the floor is taken into the gantry. (Check for the presence of a boiler room downstairs or if air is cold near the floor because the scanning room is located in the basement.) 9-1 No. Timer ON Temperature CAUTION: (2) Air conditioning ON KPC scanning room Starting time conditions in the The scanning room must be provided with an independent air conditioning system. Even if the room is maintained within the permissible temperature range, gradual temperature shifts (for example, a slow increase in room temperature from morning to evening) may adversely affect system performance. Therefore, the room temperature must be under constant control as shown in the above figure. Dust Since the inside of the console extreme care to keep dust from 9.2 Tolerance: 2A201-384E Water A water however, Supply is the easily console. affected by dust, take and Drainage supply it is and drainage recommended facility is not that a washstand 9-2 required for be provided. this system, No. 10. APPENDED ZAZOl-384E TABLES AND FIGURES (1) Appended table (2) Appended tables 2-l (3) Appended tables 3-l (4) Appended figure (5) Appended figure (6) Appended figure (7) Appended figures (8) Appended figure (9) Appended (10) 1 : Heat generation environmental and 2-2 : External to : List 1 : External dimensions gantry and required bringing-in entrance 2 : System layout space required consideration 3-3 3 by units conditions dimensions of and and mass inter-unit cables and mass of size of the planned taking for maintenance the into : Pit : Power supply 5 : Cable connections figure 6 : Inter-unit Appended figure 7 : Floor resin (11) Appended figure 8 : Gantry (12) Appended figure 9 : Grounding the gantry and anchoring positions and the patient couch (13) Appended figure 10 : Layout couch the (14) Appended figure 11 : Console (15) Appended figure 12 : Speaker (16) Appended figure 13 : Patient (including (17) Appended figure 14 : Video display the patient (18) Appended figure 15 : System 4-l to 4-4 10-l layout the example system distances levelling work and patient of and patient camera and stand) monitor transformer epoxy couch gantry monitoring lens using for monitoring (CETF005B) of No. APPENDIX 1 APPENDED Appended table Names of rooms and units 1. Scanning Heat FIGURES AND OUTLINE generation Maximum heat generation*’ by units (3.0) (10800) 8.9 32070 2.7 9720 I 0.5 1800 1 0.3 1080 2. Scan control room (2.7) (9720) (2.7) (9720) 0 Console 2.7 9720 2.7 9720 Gantry l Patient couch Maximum scanning heat generation is performed Normal heat performed. at generation 1 kW = 860 kcal/h, 1 cal *3 A temperature operated. O°C to the heat = 4.19 40°C is that conditions Environmental Temperature” (“C) 1 A-l (%) 40% to 80% (No condensation) 40% to 80% (No condensation) generated when continuous rating of the unit. generated when scanning units are J permissible humidity I 16°C to 28°C is conditions Relative 20°C to 26°C Tolerance: 52°C is the heat that is the maximum output is *2 from and environmental WV [kJ/hl [kW] [kJ/h]? (33870) l DRAWINGS Normal heat generation*’ (9.4) *1 room 1 TABLES, ZAZOl-384E if the not is not No. Appended Note: table The values in angle mass for multislice 2-l External brackets system. (< >) are T Unit name Gantry (with cover) Patient couch dimensions and mass external dimens .ons I- External dimensions Width (mm) Depth (mm) Height (mm) 1970 c 1970> 860 <890> 1760 < 1760> 620 Navibox the 480 <lOlO> ZAZOl-384E*B and Mass (kg) 1300 cl 300> 2390 390 330 760 e420> 700 <700> 220 <135> Keyboard 574 247 90 3 21-inch monitor 496 520 419 33 17-inch monitor 404 450 426 20 Speaker 140 135 200 2 Appended table 2-2 External dimensions External Unit name Patient monitor Camera (including System transformer lens and stand) Width (mm) and mass (optional) dimensions Depth (mm) Height (mm) Mass (kg) 225 260 240 6 105 380 315 4 800 770 980 550 A-2 Appended Power table 3-1 List’of inter-unit cables (l/2) cables - Cable No. Wiring pit PO1 Connected to: (1) Connected to: (2) System trans. Console Standard length (ml Eff ective len gth -(m: 1 a 10 System trans. Gantry a 11 P ? w System trans. Gantry a 11 P Gantry Console 14 12 I L 3 cores x 5.5 17.5 1.5 while connecting to (1) 1.5 while connecting to (1) 1.5 while connecting to (1) 0.5 while connecting to (2) Connector diameter (mm) Solderless contact while connecting to (1) Solderless contact while connecting to (2) 15 3 cores x 5.5 17.5 Solderless contact while connecting to (1) Open wire while connecting to (2) 15 3 cores x 35 35.2 Solderless contact while connecting to (1) Open wire while connecting to (2) 1.5 while connecting to (2) PO4 20 Outer cable diameter (mm) 1.5 while connecting to (2) PO3 1.5 while connecting to (1) Number of Vlaximum cores x section ength (m) area (mm’) 0.5 while connecting to (2) PO2 Retract length (m) 19 6 cores x 0.75 11.5 Solderless contact while connecting to (1) Connector (28 x 21 x 28) plus solderless contact Remarks Appended Power table 3-1 List’of inter-unit cables (2/2) cables Connected to: (1) Connected to: (2) Standard length (m) Fffective ength :m) 3 Power box Retract length (m) ?.5 while connecting to (1) Vlaximum ength (m) Number of cores x section area (mm2) 3uter cable diameter :mm) Connector diameter (mm) 5 3 cores x 35 35.3 Solderless contact while connecting to (2) 15 1 core x 35 12.2 Solderless contact while connecting to (1) 0.5 while connecting to (2) Power box 1.5 while connecting to (1) 1.5 while connecting to (2) EOO P ? c- E02 i P -I- Power box System trans. Power box Console 5 15 1.5 while con netting to (1) Solderless contact while connecting to (2) 5 1 core x 35 11.94 Solderless contact while connecting to (2) 27 1 core x 5.5 4.4 Solderless contact while connecting to (1) 0.5 while con netting to (2) 13 1.5 while con netting to (1) 0.5 while con. netting to (2) Solderless contact while connecting to (2) Remarks Appended Signal table 3-2-l List of inter-unit cables (TSX-021A/lC, lD, /2C, cables Cable No. /Wring Iit so1 S Connected to: (1) Engcted Standard length Cm> Effective length 0-N Console Gantry 14 12 Retract length (m) 0.5 while connecting to (1) Number of Maximum cores x section length (m) area (mm2) 19 50 cores x 0.08 shielding Outer cable diameter (mm) 12.3 1.5 while connecting to (2) so2 S Console Gantry 14 12 0.5 while connecting to (1) Console diameter (mm) Connector (77 x 20 x 52) while connecting to (1) 19 36 cores x 0.08 shielding 11.3 Connector (62 x 20 x 52) while connecting to (1) Connector (62 x 20 x 52) while connecting to (2) (a) Gantry 14 12 0.5 while connecting to (1) 19 3 cores x 0.18 shielding 4.2 Connector ($29 x 52) while connecting to (1) (b) Speaker (Gantry) 14 12 1.5 while connecting to (2)-(a) 19 2 cores x 0.5 shielding 5.1 Connector ($25 x 49) while connecting to (2)-(a) (c) Speaker (C-room) 11 9 1.5 while connecting to G?-(b) 11 2 cores x 0.5 shielding 5.1 ? UI S Connector Connector (77 x 20 x 52) while connecting to (2) 1.5 while connecting to (2) so3 2D and TSX-021B) r-r 1.5 while connecting to W-(c) Remarks Appended Signal Cable No. table 3-2-2 List of inter-unit cables (TSX-021A/3C, /3D: multislice systems) cables Niring Iit Connected to: (1) Connected to: (2) Console Gantry Standard length Cm> Effective length Cm> Retract Maximum ength (m) length (m) Number of cores x section area (mm2) Outer cable diameter (mm> 50 cores x 0.08 shielding 12.3 Connector diameter (mm) I so1 14 12 IO.5 while connetting to (1) 19 Connector (53 x 18 x 41) while connecting to (1) 1.5 while connecting to (2) Connector (73 x 19 x 50) while connecting to (2) I Console Gantry 14 12 0.5 while connecting to (1) 19 36 cores x 0.08 shielding 11.3 Connector (62 x 20 x 52) while connecting to (1) 1.5 while connecting to (2) Console (a) Gantry 14 12 0.5 while connecting to (1) (b) Speaker Gantry) 14 12 1.5 while connecting to (2)-(a) (c) Speaker (Groom) 11 9 1.5 while connecting (2)-(b) to Connector (62 x 20 x 52) while connecting to (2) I 19 3 cores x 0.18 shielding 4.2 Connector ($29 x 52) while connecting to (1) 19 2 cores x 0.5 shielding 5.1 Connector ($25 x 49) while connecting to (2)-(a) 11 2 cores x 0.5 shielding 5.1 1.5 while connecting to ww Console Gantry 14 12 0.5 while connecting to (1) 1.5 while connecting to (2) I 26 cores x 0.08 10.0 Connector (38 x 14 x 41) while connecting to (1) Connector (76 x 16 x 50) while connecting to (2) Remarks Appended Cables Cable No. attached to Wiring Connected /pit /to: (1) the table 3-3 List of inter-unit cables gantry Connected 1to: (2) Standard length (ml Effective length ON Retract length (m) Maximum length (m) Number of cores x section area (mm’) Outer cable diameter (mm) Connector diameter (mm) Remarks FCS12 S Gantry Patient couch - - Connector (77 x 20 x 52) while connecting to (2) (1) connected inside gantry FCP40 P Gantry Patient couch - - Connector (28 x 33 x 28) Compound cable (1) connected inside gantry FCP39 P Gantry - - FCEOI ( E 1Gantry (;:;;;t - - - I - I 4 cores x 0.5 - 6.5 Compound cable I 1 core x 8.9 7.8 I Solderless contact while connecting to (2) (1) connected inside gantry No. Recommended values for bringing-in 2A201-384E"B route Door height 1860 mm or more Door width 980 mm or more Mass: *1: Appended This dimension systems). figure 1 is 890 mm for External dimensions and required size A-7 of TSX-021A/3C, and mass of the the bringing-in /3D 1300 kg (multislice gantry entrance No. (1) Since the scanner front mm for opening/closing cover opens the cover. (2) Provide a clearance the LCSR. MUDAT. of at least 600 mm behind (3) Provide a clearance of at least 700 mm for KGTS. (4) Provide etc. a clearance of at least 350 mm for servicing (5) Provide a clearance couch for servicing (6) Provide a clearance of the front for servicing (7) It is desirable the headrest. xl> <2> <3> <4> Gantry Patient Patient Console couch monitoring Appended Note: to of at least the patient outward, provide the a clearance scanner 400 mm from couch. the rear at least 500 mm with the console. the Navibox reserve a clearance of more than 2A201-384E"B for the servo edge of pulled 400 mm for of 1500 servicing amplifier the patient out toward the use of system figure 2 System layout for maintenance The console <4> above is for For the console for multislice planned into single-slice systems, A-8 taking the consideration space systems. refer to appended required figure 11-2. No. EZ7ZZZZA I] <l> <2> <3> <4> Gantry Patient Patient Console couch monitor Power supply pit Signal pit .ng system Appended Note: ZAZOl-384E*B figure The console <4> above is for For the console for multislice 3 Pit layout single-slice systems, A-9 examp .e systems. refer to appended figure 11-Z. Nominal Voltage 200 V 75 kVA (Actual load 62 kVA) 600 V, IV wire used Conduit wiring r 0 1-0 20 30 40 70 60 50 80 sectional 90 area for the wiring cables 100 Distance between the power receiving transformer and the power distribution board (unit: m) Appended figure 4-1 Power supply system (mm21 Voltage 2dO V 75 kVA (Actual load 62 kVA) Nominal sectional area for the wiring cables (mm2) 600 V, 3-core CV wire used Conduit wiring 60 / Transformer capacity 150 kVd 4 100 kVA 75 kVA 3 2 40 50 60 70 80 90 Distance between the power receiving transformer and the power distribution board (unit: m) Appended figure 4-2 Power supply system Nominal Voltage 200 V 75 kVA (Actual load 57 kVA) 600 V, IV wire used Conduit wiring sectional area for the wiring cables (mm’) Transform 2 1 40 20 100 60 50 Distance between the power receiving transformer and the power distribution board (unit: m) Appended figure 4-3 Power supply system Voltage 200 V 75 kVA (Actual load 57 kVA) 600 V, 3-core CV wire used Conduit wirina Nominal sectional area for the wiring cables 60 / Transformer 4 capacity 150 kVA 100 kVA 75 kVA ? P w 3 2 1 Distance between the power receiving transformer and the power distribution board (unit: m) Appended figure 4-4 Power supply system Voltage 200 V 50 kVA (Actual load 44 kVA) 600 V, IV wire used Conduit wiring Transformercapacity Nominal sectional area for the wiring cables (mmZ) 150 kVA 100 kVA 75 kVA 50 kVA 70 90 100 Distance between the power receiving transformer and the power distribution board (unit: m) Appended figure 4-4A Power supply system Voltage 200 V 50 kVA (Actual load 44 kVA) 600 V, 3 core-CV wire used Conduit wiring Transformercapacity Nominal sectional area for the wiring cables (mm’) 150 kVA 100 kVA 75 kVA 50 kVA ? t: m 3. 50 60 70 80 90 100 Distance between the power receiving transformer and the power distribution board (unit: m) Appended figure 4-4B Power supply system Nominal Voltage 200 V 75 kVA (Actual load 77 kVA) 600 V, IV wire used Conduit wiring 70 60 80 sectional area for the wiring cables (mm2) 90 100 Distance between the power receiving transformer and the power distribution board (unit: m) Appended figure 4-4C Power supply system Nominal Voltage 200 V 75 kVA (Actual load 77 kVA) 600 V, 3-core CV wire used Conduit wiring sectional area for the wiring cables (mm’) 60 / ? t; u Distance between the power receiving transformer and the power distribution board (unit: m) Appended figure 4-4D Power supply system [COLOR : BLACK] rp SO3 : (CX70-02726-I) [CNN 41 _ [CNN I] 1 PO0 tEP 11 C PO2 : (PX70-02582-I) EOI : (PX70-02585-I) C -j ~2OW I 3 [El EOO -a ITB 21 I] POWER Box c E E02 PO1:(CX70-02724-I) lTB 11 12ow [ [CNN 21 [CN 4561 [CN 505] [GTSXC] PO4 : (CX70-02735-l) [CNN 51 - [ PAS1 SO2 : (CX70-02731-I) [CNN 21 - [TBII [INTERCOM] SO1 : (CX70-02730-I) _ [CN 5171 _ [EP 11 _- *POWER(FCP40:CX77-96518-1) ] [CNN l]*l) *EARTH(FCEOl :CX77-96579-1) O IFCGB~~ CGGT [COLOR:BLUE] Note: Appended figure The FCPOO and FCP39 cables are connected to CNNl of CBTB. The CNNl connector is mounted to FCP40 and the FCP39 cable 5-1 Cable connections (TSX-OZlA/lC, lD, is ZC, 2D and TSX-021B) connected later. [COLOR SO3 : (CX70-02845-l) [CNN4] [INTERCOM] SO1 : (CX70-02800-I [CNNI] ) PAS1 SO2 : (CX70-02731-I) [CNN2] [GTS . XC] SO4 : (CX70-02801-I) [CNN3] P-1 PO4 : (CX70-02725-l) [CNN5] PTB21 PO0 PO2 : (PX70-02582-I [TBll[ ) EOI : (PX70-02585-I WIIC VW [ ] ] [2OOV] ’ ) 3 [El PO3 : (PX70-02583-l) : BLACK] POWER Box C IE E02 EOO -B PO1 : (CX70-02724-I [2OOV] [ ) [TBI ] [2OOV] CETF [CN456] [ [CN505] [ [CN517] [ W’ll [ *SIGNAL (FCS12 : CX77-96541-1) *POWER (FCP40 : CX77-96518-l) *POWER (FCP39 : CX77-96519-l) *EARTH (FCEOI : CX77-96579-1) CGGT [COLOR ] [CNN2] ] [CNNl]*l) 3 PI CBTB CKCN [COLOR : WHITE] : BULE] Note: Appended figure The FCP40 and FCP39 cables are connected to CNNl of CBTB. The CNNl connector is mounted to FCP40 and the FCP39 cable 5-2 Cable connections (TSX-021A/3C, /3D: multislice is connected systems) later. No. 2A201-384E*B 12(17) Console (Navibox) w W2) Distance (Distance The distances are enclosed between between the units W 8) the units = Cable length (Ref. table 3-1 and 3-2) when cables of standard between the units when cables with parentheses ( ). Appended figure 6 Inter-unit A-15 with - Retract lengths the maximum distances length are used) length are used No. Appended Note: During above (1) floor work, to make the Epoxy l l figure 7 Floor pour epoxy installation levelling resin into surface. Time using the epoxy range resin shown in the figure resin Epoxy resin (Epichlon 857) Hardener (Epichlon B-065) Mixture work 2A201-384E*A ratio: required specific specific gravity gravity 857: B-065 = 3:l (w/w) The proper mixture ratio the manufacturer because depending on the particular for hardening: 48 hours (ambient should be confirmed the ratio differs formulation. at ordinary temperature (2) Complete this work before carrying of 2 to 5 days is required for the depending on the temperature). (3) For procedures for pouring epoxy resin, LEVELLING WORK MANUAL" attached to this (4) The tolerance for the dimensions given in within k1 mm, which can be measured using A-16 1.2 1.2 room temperature 25°C) in the system because epoxy resin to harden refer site with a period (differs to APPENDIX 3 "FLOOR planning manual. the figure above a tape measure. is Conl OL _ ._R---_ PANfL 3 I tI.RA1 HORIIONIAL SCM ARIA PLANt IO COUCH DISIANCfI m l---=-T (Al BObI SCAN j. 1100 ,j \OUCH 1OP IEI IllAD SCAN This dimension is 361 mm for This dimension is 1900 mm for TSX-021A/3C, TSX-021A/3C, /3D /3D (multislice (multislice systems). 2. systems). K Appended figure 8 Gantry and patient couch -.7 -.-.-+-.-.---.---. .__________ ____d I 3-.$I ((307)) I(31 DETAIL 5)) FROM X-RAY I3 DRILL 90 DEEP FOR PLANE “A” v-? M 1630 I I Appended-figure Ml2 I 307 _I_ I- 845 I- 980 (MIN) L&J-.-L ANCHOR 9 Grounding and anchoring positions of the gantry and the patient couch WALL - 340 3880 POINT \CABLE (OUTLET) REFERENCE GANTRY COUCH _. 7-l 1 HEAD REST (STANDARD) 330 ----jam 2390 i Appended figure 10 Layout of the gantry and patient couch 0 r-2 0 N LD cl > x2> c3> <4> t Cable length lYiicl- <3> - l l c2> l Between the console and the keyboard : 2 m Between the console and the monitor : 1.9 m Between the keyboard and the mouse : 3 m 1400 1 800 t I Appended (Note: Monitor Mouse Keyboard Navibox The above figure shows the 11-l Console recommended desk. (for single-slice I Unit: systems) A desk must be purchased at each site.) mm <I> 1st monitor <2> Mouse <3> 1st keyboard <4> 2nd monitor c5> 2nd keyboard <6> Navibox Cable length l ~27 l l Between the Navibox and the keyboard: 2 m Maximum length: 6 m Between the Navibox and the monitor: 1.9 m Maximum length: 6 m Between the keyboard and the mouse: 3 m <6> ,I l-l UJ -a - 1010 Unit: Appended * (Note : The above figure shows the figure recommended 11-2 desk. Console (for An appropriate multislice systems) desk must be purchased at the site.) mm 4 - 135 140 86 Approx. Appended figure 12 Speaker 2 kg No. ZAZOl-384E 4-411 hole Approx. Appended figure 13 Patient monitoring (including lens A-22 camera and stand) (option) 4 kg No. 2A201-384E 260 I< u IIIIIIIIIIIIIIIIIIIIIII u Approx. Appended figure 14 Video display monitor A-23 for monitoring the patient 6 kg No. 800 2A201-384E > I Rear side PL I Front side Metal screen Onlv two sides Approx. Appended figure 15 System A-24 transformer (CETF005B) 550 kg No. APPENDIX 1. 2 HANDLING 2.1 Effects to EMC, information are described below. of EM1 Noise regarding EM1 noise and static and Countermeasures Symptoms Some of 2.2 EMC Introduction With regard electricity 2. ZAZOl-384E the symptoms of EM1 noise are screen an ultrasound (1) Noise occurs on the the CT system. (2) Waveforms irregular. (3) Noise (4) An abnormal image or a communication scalpel or a microwave unit is used. obtained which of listed by ECG equipment causes flickering below: used system near on CRTs used error being the near used CT system the near are CT system. may occur if an electric Causes The X-ray unit of the CT system includes a large capacity inverter unit. When this inverter unit operates, EM1 noise in the MHz range level conforms to the IEC60601-1-2 standards, some system combinations may generate noise problems. In particular, the system, Possible when an ultrasound system is used in the former is easily affected by noise produced routes of of EM1 noise are listed of a CT latter. below. (1) EM1 noise is radiated from the CT system, CT cables, etc. to the air in the form of the electric wave and enters the ultrasound system via the ultrasound system cable or some other unit connected with the ultrasound system which plays the role of an antenna. (This is called radiation noise.) (2) EM1 noise transmits ultrasound system this cable. (This The routes of noise simultaneously. 2.3 transmission vicinity by the through a CT system cable, and enters the is called conduction entry described above cable, transfers to an ultrasound system through noise.) may often exist Countermeasures There are two main approaches to counter noise generation in the system generating of noise entry into the system affected must be investigated as countermeasures. Actual countermeasures are described ultrasound system, electric scalpel, combination with a CT system. A-25 this problem; the noise, by the noise. the prevention and the prevention Both approaches below for the example and a microwave unit of an used in of No. (1) Countermeasures for the CT system Table Cause/route identification l l l Turn OFF the power of the CT system and check whether there is any change in the noise characteristics of the ultrasound system. Turn OFF the power of the CT system and check whether there is any change in the noise characteristics of the ultrasound system. Turn OFF the power of the CT system and check whether there is any change in the noise characteristics of the ultrasound system. 0 Perform simple shielding of the cables of the CT system using aluminum foil, ground the cables, and check the results. (Difficulty: High) l Remove the electric scalpel or microwave unit from the CT system. Alternatively, turn OFF the power of the electric scalpel or microwave unit. (When the CT system is affected) A-l Cause/route procedure 0 System radiation Countermeasures receives noise. l l l l ZAZOl-384E Conduction noise via the powersupply line Conduction noise via the ground cable l l Change the orientation position of the system receiving noise. or If the problem still occurs after the above measures have been taken, the scanning room must be shielded using sinteredferrite or a rubber material that absorbs the noisecausing signals. Insert an EM1 filter power-supply line. Asteion, the filter already installed.) in the (For is Make the connections independent. For example, place a new ground cable for the CT system. (Difficulty: l Radiation noise from CT cables If the noise is reduced, the cause is radiation noise from CT cables. 0 System radiation receives noise. Shield the cables using mesh-type shielding material. (Difficulty: High) (Since CT systems have several units and many cables, this procedure may be difficult.) l l l A-26 High) Orient the CT X-ray unit so that the noise is minimum. If the problem still occurs after the above measures have been taken, the scanning room must be shielded using sinteredferrite or a rubber material that absorbs the noisecausing signals. No. (2) Countermeasures for the ultrasound Table Cause/route identification l l l l l l l l Move the ultrasound system to a location far from the CT system. Check whether is reduced. the system A-2 Cause/route procedure Radiation l Countermeasures noise l noise Disconnect all the cables of optional units (printer, VCR, imager, etc.) connected to the ultrasound system. l ZAZOl-384E The transducer acts as an antenna for the entry radiation noise. l Ask the customer to use the ultrasound system at a location away from the CT system if possible. Replace the transducer. Insert the power supply filter in the powersupply line of the ultrasound system. If the noise vanishes as a result of these actions, the route of entry of the noise lies in one of the cables. If the noise does not the transducer vanish, could also be the cause. Change the transducer of the ultrasound system to a transducer with reinforced shielding (for example, a double shielded transducer). Remove filter status result. the power-supply in the above and check the l Conduction noise from the powersupply line or the ground A-27 l Insert filter. the power-supply No. Cause/route identification l l Cause/route procedure Connect the cables of the optional units one by one to identify which cables are the noise routes. l l Conduction via cables Countermeasures I noise l Entry from cables exposed to radiation noise Since several cables may be noise routes, check all the cables. l l l l Check whether the cables of the ultrasound system and the optional units are close to the cables, etc. of the CT system. l Change the cable routing to increase the distance between the sets of cables and check whether the noise is reduced. 0 Perform simple shielding of the cables of the ultrasound system using aluminum foil and ground the cables. l Radiation noise from the cables of the CT system transfers to the cables of the ultrasound system and enters the system via the cables. Radiation noise enters the ultrasound system via the cables. A-28 ZAZOl-384E l l Connect the power cable of the unit (printer, VCR, etc.) connected to the cable acting as the noise route to the power-supply filter. Insert a core and filter between the ultrasound system and the cable playing the role of the noise route. For the BNC cable of imager, a filter for connector is provided. the BNC Change the cable routing increase the distance between the cables. Shield the cables using mesh type of shielding material. to a No. 3. Influence 3.1 What of is Static static Electricity and Required 2A201-384E Countermeasures electricity? The Static Electricity Handbook of the Static Electricity Institute (published by Ohm Inc.) defines static electricity as "electricity where the spatial movement of electric charges is small and the effects of the magnetic field due to the slight spatial movement of electric charges are negligible in comparison to the effects of the electric field." That is, static electricity is electricity which resides in the material and moves little. To study actual dynamic electricity static electricity phenomena related to static phenomena (for example, phenomena must be included electricity, however, static discharge) caused in the scope of study. by Thus, the study of static electricity phenomena includes the study of some dynamic electricity phenomena. It should be noted that the voltages involved in static electricity phenomena are generally higher in comparison to those involved dynamic electricity phenomena, but the total amount of electricity (electric charge) involved is generally much less for static electricity phenomena than for dynamic electricity phenomena. A-29 No. 3.2 Necessity of countermeasures CT systems contain sensitive to static The following table device is damaged. various semiconductor electricity. shows the Table Type of component VMOS MOS FET GaAs FET EPROM JFET SAW OP-AMP CMOS Schottky diodes Film resistors Bipolar transistors ECL SCR Schottky TTL against static static ZAZOl-384E electricity devices which electricity levels are very at which each A-3 Voltage range resulting component damage (V) I 30 to 1.800 100 to 200 I I 100 to 300 100 I I 140 to 7.000 150 to 500 I 190 to 2,500 250 to 3.000 300 to 2,500 300 to 3.000 380 to 7,000 500 to 1,500 680 to 1,000 1,000 to 2,500 in The level of static electricity that can cause damage differs depending on the type of device. Damage may be result from static electricity levels of less than 100 V as shown in the above table. This system conforms to EMC standards IEC60601-1-2 and therefore is not damaged due to supplied voltage of 3 kV (contact) or 8 kV (in the air). If this system is to be used in an atmosphere where static electricity of more than 3 kV is present, countermeasures against static electricity must include the CT system as well as the environment in which the CT system is installed as targets. A-30 No. 3.3 Suppression and prevention Antistatic (1) measures Increasing for of static electricity nonconductors relative humidity As shown in tables A-4 and A-5, the generation of static can be prevented by increasing the relative humidity. Table A-4 Static Dependence of generated relative humidity electricity generated Walking on a carpet Walking on a vinyl Working at Table A-5 voltage on I Static electricity voltage (V) 10% to floor 20% RH 65% to 90% RH 1,500 table 6,000 100 work in/from a vinyl 7,000 600 chair with cushion can be reduced Relationship electricity 20,000 1,200 18,000 1,500 a work a to less than l/l0 between the humidity voltage for various Static Fiber electricity 250 Sitting on a work polyurethane foam The voltage humidity. static 35,000 Picking up an ordinary polyethylene bag from table *: by electricity 12,000 a work Storing/removing instructions cover ZAZOl-384E 50% RH electricity by increasing and the fibers voltage 65% RH (kV) 80% RH Wool 4.9 2.0 0.8 Cotton 0.1 0.0 0.0 Viscose rayon 4.7 1.6 0.5 Acetate rayon 6.0 3.5 3.3 A-31 static the No. However, increasing humidity (Refer to figure A-l.) too much causes Overall Y. clean L 10 ___---2b IX I The above systems / I ,’ A’ Humic lity L-. narard 40I A-l hazara hazard hazard -3b hazard. ratio ~om~O-~icity 50I Relative Figure hazard c__r_ I humidity ZAZOl-384E 60I 70I humidity 8; - 100, &) The relation between relative hazard ratio relationship indicates should be controlled in 90 relative humidity and that the relative humidity the 50X to 55X range as far for as possible. (2) Countermeasures using conductive materials The above method (increasing relative humidity) optimal because humidity hazard may be caused. preventive measures using conductive materials below. (An example comparing conductive shoes shoes is presented.) Walking in place: alking Standing in place; x lam- aNormal shoes Figure A-2 Standing x i 1 Time is not always Therefore, are outlined with normal 2 2 (min) Time Nonconductive flooring material Figure A-3 (min) Conductive material flooring Figure A-2 illustrates an example of walking in place followed by standing on a nonconductive floor with normal shoes and conductive shoes. (The static electricity voltage may be higher depending on the material of the clothes, etc.) Wearing conductive shoes makes it possible to decrease the static electricity voltage level. However, the static electricity voltage even at this level could damage devices, as shown in table A-3. A-32 No. ZAZOl-384E Figure A-3 illustrates an example of walking in place followed by standing on a conductive floor with normal shoes and conductive shoes. Preventive measures against static electricity using a conductive floor and conductive shoes are extremely effective. This method should therefore prevent damage due to static service personnel. Materials Reference and manufacturers manufacturer: l Conductive floor l Conductive slippers . Conductive shoes be used electricity are Achilles ------ listed Inc. Conductive --- ------ during site planning caused by users to or below. floor tiles SKY-11 ICS-0100 ICMOlOO ICM0230 (for (for men) women) The installation area of the conductive floor is shown in the attachment. (Refer to figure A-4 "Room layout example".) It is recommended that special consultation with the flooring material manufacturer be held before building the floor. A-33 No. <l> Gantry <z> Patient <37 Patient <47 Console couch monitoring system The conductive floor grounding grounding point of the gantry the console must be connected cable near the gantry must be connected floor grounding cable and the conductive to the grounding point of the console. Figure Note: The console 2A201-384E*B <4> for A-4 single-slice Room layout systems A-34 example is shown as an example. to the near No. APPENDIX FLOOR LEVELLING (TECHNIQUES 3 WORK MANUAL FOR USING FOR Asteion A-35 EPOXY RESIN) ZAZOl-384E No. 1. OUTLINE This manual epoxy resin and patient describes the procedures to ensure levelness of couch of the Asteion. This manual, although written applicable to other models. 2. ZAZOl-384E TOOLS AND MATERIALS Tools or materials for the performing installation specifically for the floor floor work using for the gantry Asteion, is also REQUIRED Quantity required (1) Plastic L-angle plates (20 x 20 x 1830 mm) (2) Adhesive tape 18 mm x 35 m) (3) Cutter 2 Used to covering (4) Saw 1 Used to cut angle plates. (5) Basin bucket 1 Used for resin. mixing epoxy (6) Ladle 1 Used for resin. mixing epoxy (7) Caulking Silicone clear compound (joint sealant Cemedine 1 Used to prevent the epoxy resin. (8) Caulking gun 1 Used to apply compound (9) Tape measure 2 Used to measure dimensions and to draw lines. 1 For (60 (10) Spatula (11) Epoxy (12) Winter-use (Epichlon (13) Rags (14) Grinder (15) Technodisk (external (product cm in resin 12 Remarks number diameter) (Epichlon 252, 4 rolls or sealant) 8060 857) hardener B-065) Used for applying (reusable) the frames epoxy resin Used to fix angle plates. the remove plastic the the 18 liters/can 1 can 18 liters/can leakage caulking 1 bundle 1 diameter (16) Plastic sheet (17) Spray lubricant 100 mm) (2 m x 2 m) 1 (CRC-556) 1 A-36 Used for finishing epoxy resin L- floor plastic caulking 1 can for L- of No. <Supplier Epoxy NOTE: of resin the epoxy and hardener: ZAZOl-384E resin> Dai-Nippon Ink & Chemicals, Inc. Although two different hardeners are available for the epoxy resin (winter-use hardener and summer-use hardener), the winter-use hardener must be used. The summer-use hardener is not suitable for work in hospitals or clinics because it requires a long hardening time and, in some cases, the application of heat may be necessary to achieve hardening. A-37 No. 3. WORK PROCEDURES The main work procedures are Marking off as follows: the floor 1 Drilling the Removing Making the the frames anchor floor for holes covering resin I application I Applying ! resin Finishin;[orming) ! A-38 ZAZOl-384E No. The following shows the application full-scale gauge be used for marking 2-@22 DRILL 90 DEEP area. (It and anchor FOR Ml6 is recommended hole drilling 195 \ A-39 2A201-384E*A that the work.) No. 3.1 3.2 2A201-384E Marking (1) Determine the installation couch (refer to appended (2) Mark off determined Drilling the the (1) Drill drill (2) Cut a slit cutter. locations figure 2). for resin application areas installation locations. Anchor Holes and Removing the anchor holes with a 22-mm bit. at the 10 to 15 mm inside the on the the marked the gantry floor sections Floor Covering positions using marking line on the Remove inside (4) Clean the the the floor covering marking line) area from which inside the the floor A-40 marking covering patient of the an electric floor using Cut the dotted-line section with a cutter (over the entire edge) (3) and the line. has been (Entire removed. area a No. 3.3 Making the Frames (1) Cut off the saw. Treat (2) Tape been (a) for the Application plastic L-angle plates along the corners as shown below. along the cut off. Tape Resin marking outside line of the of the Use the spatula to spread corner inside the L-angle Caulking plastic r Adhesive A-41 marking L-angle L-angle the caulking plate. compound the plastic n (b) 2A201-384E plate line plates to tape a that have secure Secure with adhesive compound using all it. tape over the No. (c) Tape outside plates. (d) Cut out part of the plastic the patient couch to make (This gantry (e) job must and the sections of the corners L-angle an epoxy between the ZAZOl-384E plastic L-angle plates for the gantry resin passageway. be performed to ensure that patient couch are flush.) the bottoms of and the Using a spatula, apply caulking compound (joint sealant) to all sections where the resin may leak, such as the connections at the corners of, and the joints between, the plastic L-angle plates, the clearances between the installation surface and the base, etc. APPLYthe tape. 1 Epoxy resin passa .-.- (f) Wind paper on the tape. Insert this caulking. anchor a couple of times anchor into the anchor and fix it using hole and perform the Anchor-, Caulking Paper NOTE: The anchor must be well caulked to prevent the epoxy resin from being intruded into the anchor hole. The paper wound on the anchor must be higher than the epoxy resin depth. A-42 3.4 Applying (1) ZAZOl-384E into a basin, Resin Place epoxy resin (major and mix them thoroughly Mixture ratio Specific NOTE: No. : gravity: agent), hardener, using a ladle. Epoxy resin: hardener Epoxy resin Hardener 1.20 1.20 1. This job must be performed and pigment = 3:l (w/w) with a plastic floor-covering sheet laid on the floor. 2. Before mixing the liquid agents, they must be accurately replenishment container. weighed using an oil 3. The oil replenishment container that has been used for weighing used to apply the resin. 4. Gloves, eye protection, etc. must be worn when handling the resin. 5. During handling of the resin, good ventilation volatile chemical. (2) Pour the liquid mixture into the must be provided since it is a frames. Since the resin has a certain degree of viscosity, the The amount of mixture poured should be poured evenly. the minimum thickness of the resin is about 5 mm. 3.5 must not be mixture must be such that (3) Allow about one hour after the start of pouring to observe closely for leakage of the resin from the frames. If leakage is seen, immediately seal the leak using adhesive tape or caulking compound (joint sealant). (4) After pouring to the epoxy resin surface Finishing the has been completed, apply a spray lubricant resin surface. This eliminates any bubbles to ensure a smooth finish. Resin CRC-556 from the Surface (1) After allowing the resin to stand for 48 hours or more, check the surface has become hard (press the surface with a push-pull gauge and confirm that the surface is not dented). (2) Remove the passageway (3) Remove any rough using a grinder. smooth. frames. Remove using a saw. the gantry-to-couch epoxy resin edges or bulges from the corners and the Finish the entire surface so that it is A-43 that surface flat and 1385,SHIMOISHIGAMI,OTAWARA-SHI,TOCHIGI-KEN 324-8550,JAPAN