I2 I6 I7 I11

Transcription

I2 I6 I7 I11
earthing and jumpers
I2
I6
I7
I11
H6
H6
the energy network
earthing and
jumpers
EARTHING EQUIPMENT & ACCESSORIES
Portable Earthing Devices (PED) Overview
Commonly known as “Earthsets, Earthsticks, Earthing Devices, Portable Earthing Devices or PED’s”. These devices attach temporarily to de-energised conductors or contact points and a known earth.
PED’s are safety devices that are type tested and manufactured to withstand the maximum fault current for the specific portion of the network being worked on in the event that the conductor or contact point becomes energised.
PED’s are designed so that they provide enough time, usually several milliseconds to carry fault current long enough for a circuit breaker or fuse to interrupt the flow of current. Consult your local network or
asset owner for applicable legislative requirements. Always prove conductors are de-energised using an approved voltage detector before applying PEDs.
Storage, Care & Maintenance of PED’s
Storage
To prolong the life of your PED’s they should be:
•
•
•
Neatly coiled in a protective carry bag
Stored in a dedicated area away from sharp or heavy objects
Stored in a cool dry area
EN
Call T D
E
for a P
on
selecti
chart
Care & Maintenance
PED’s should be visually inspected and cleaned with a suitable cleaning product before each use.
Ensure that bolted connections are still tight, clamps are operating correctly and that there is no damage
to cable or joints.
Remove from service and tag accordingly any PED with visual defects such as:
•
•
•
•
•
•
Cuts
Badly mashed or flattened cable
Cracked or broken ferrules and clamps
Exposed or broken strands
Extensively damaged sheath material
Swollen jacket or soft spots indicating internal corrosion
PED’s should never be modified under any circumstance without the consent of the manufacturer.
Components and assembly methods used are fault current type tested, so exact manufacturer specifications
must be used at all times.
PED’s are intended to carry fault current once. After being subjected to fault current they should be removed
from service and destroyed.
References: IEC 61230, ASTM F855
I1
Portable Earth Testers are available, refer to Test Equipment page N39
Earth Storage Bags are available, refer to Storage page M6
Quality Electrical Equipment for Generation, Transmission & Distribution
the energy network
Portable Earthing Devices (PED)
•
•
•
•
•
•
earthing and
jumpers
Part No: Various
PED’s are made to customer’s specific requirements
Aluminium or copper cable
Manufactured to IEC 61230 requirements
Supplied resistance tested and tagged
Technical information including type test reports available
To obtain further information contact TEN
Assembly Types
•
Examples of typical configurations with drawing, description and
most common application
Picture
Earth
Description
3 Phase with
Separate
Downlead
3 Phase with
Centre Attached
Downlead
3 Phase
Trifurcating Plate
with Attached
Downlead
Downlead Only,
Single
3 Phase Linked
Downlead
2 Phase, Jumper
Earth
Common
Application
Distribution
Distribution
Distribution
Transmission &
Distribution
Distribution
Distribution
Aluminium Cable
•
•
•
Single core, stranded aluminium
Yellow PVC with stripe insulated 1kV jacket
UV stabilised
Fault Current Rating
(kA/0.5sec)
Approx. Weight
Per Metre
Continuous Current
Rating (Amps)
Diameter (mm)
OD
Bend Radius
(mm)
55mm2
10
0.22
194
12.8
51
85mm2
16
0.32
253
15.5
62
130mm2
25
0.47
335
18.5
74
Cable Lengths
Phase Lengths
1. Phase to Phase Length (A-B)
2. Phase to Phase Length (B-C)
Download/Earth Tail
3. Phase to Ground Earth
Heat Shrink
•
•
Clear (Non-mastic) and black (Mastic) heat shrink available for stress relief
Black mastic heat shrink provides superior water ingress protection and increased stress relief at terminations
www.tengroup.com.au | 1300 ASK TEN
I2
the energy network
earthing and
jumpers
Earthing Clamps
Phase Clamps
•
•
Specifications of commonly used phase clamps
Clamps available to suit every application
Part No
MT-613
MT-815
MT-1911
MT-1921
MT-701
Type
Snap On
Screw Up
Screw Up
Screw Up
Rat Trap
Tongue & Platform
P
-
-
-
-
Bayonet
-
-E
-E
-E
-
Spindle Types Available (refer below)
Shotgun
-
-S
-S
-S
-
Rubber Handle
-
-RH
-RH
-RH
-
Round
5 – 30
5 - 40
8 - 18
10 - 25
12-48
Horizontal Bar
-
16 - 40
-
-
-
Vertical Bar
-
5 - 40
-
-
-
Fixed Ball Joint
-
-
20
25
-
Notes
Requires Applicator
/ Removal Tool
-
-
-
Requires Lanyard /
Sandbag System
(kA/0.5sec)
25
45
-
45
45
OD Range (mm)
Max Fault Current
(kA/1sec)
17
30
20
30
30
Material
Al Alloy
Al Alloy
Cu/Al Bronze
Cu/Al Bronze
Al Alloy
Weight (kg)
0.56
0.65
0.58
0.69
1.61
Earth Clamps
•
•
Specifications of commonly used earth clamps
More clamps available to suit every application
Part No
Type
MT-840
MT-1911
MT-1921
T Handle
Screw Up
Screw Up
Spindle types available (refer below)
Bayonet
-
-E
-E
Shotgun
-
-S
-S
Rubber Handle
-
-RH
-RH
OD Range (mm)
Round
6 - 25
8 - 18
10 - 25
Horizontal Bar
0 - 25
-
-
Vertical Bar
-
-
-
Fixed Joint
-
20
25
Max Fault Current
I3
(kA/0.5sec)
16
-
45
(kA/1sec)
11
20
30
Material
Cu/Al Bronze
Cu/Al Bronze
Cu/Al Bronze
Weight (kg)
0.48
0.58
0.69
Quality Electrical Equipment for Generation, Transmission & Distribution
the energy network
Phase & Earth Clamp Spindle Types
Clamps shown below are for illustrative purposes only, clamp attachment refers to
application/removal mechanism
Picture
Clamp
Attachment
Tongue*
Main
Application
Phase
Shotgun Screw Up Bayonet Screw Up
Phase
Phase
Rubber Handle
Fixed Stick
Tee Handle1
Phase/Earth
Phase
Earth
* MT-613 snap-on clamp only
MT-840 / MT-841 Only
1
Rat Trap Tower Earths
earthing and
jumpers
•
Part No: MT701
•
•
•
Custom made to customer specification
Lightweight transmission earth sets
All rat trap tower earth kits come complete with hauling
lanyard and sandbag
Call TEN for more information
Fixed Ball Joints
Part No: MT Series
•
•
•
Installed on busbar, angled steel or tower for earth connection point
Tin plated copper with stainless steel bolts
Provides visual earth reference point
Dimensions
Picture
Part No
Model
MT-2951
Fault
Torque Ball
Rating
(Nm)
OD
(kA/sec)
Thread
Bolt
Nut
Length Depth
Body
A/F
Width
Suits
Clamp
Weight
(kg)
20/1
60
20
M12 Internal
-
19
24
MT-1911
0.2
30/1
60
25
M12 Internal
-
22
19
MT-1921
0.2
MT-3952
45/0.5
70
25
M16 Internal
-
25
24
MT-1921
0.2
MT-2951/1
20/1
60
20
M12 Bolt
35
19
19
MT-1911
0.2
20/1
60
20
M12 Bolt
45
19
19
MT-1911
0.2
30/1
60
25
M12 Bolt
45
22
19
MT-1921
0.3
45/0.5
70
25
M16 Bolt
45
25
24
MT-1921
0.4
20/1
60
20
M12 Bolt
35
N/A
19
MT-1911
0.3
45/0.5
70
25
M16 Bolt
35
N/A
24
MT-1921
0.3
MT-3951
MT-2951/2
MT-3951/1
Straight
Straight
MT-3952/1
MT-2950/35*
Angled
MT-3950/35*
Drop-Out Fusing Earth Adaptor
Part No: DOFEA
•
•
•
Provides an earth point on bottom of drop out fuse carriers
Link adaptor required for operation (Refer to page I5)
Brass and stainless steel construction
www.tengroup.com.au | 1300 ASK TEN
I4
the energy network
earthing and
jumpers
Earthing Attachments & Accessories
Part No: Various
Stick attachment fitting types
Picture
Stick Attachment
Universal
Shotgun
Hex
Part Number Suffix
K
S
C
Picture (Top Only)
Description
Part Number
Stick Attachment
MT-630-K
Universal
MT-630-S
Shotgun
MT-630-C
Hex
CRA/K
Universal
CRA/S
Shotgun
CRA/C
Hex
LKA/K
Universal
LKA/S
Shotgun
LKA/C
Hex
LLCR/K
Universal
LLCR/S
Shotgun
LLCR/C
Hex
Mounting Platform
For attaching MT-613
snap-on clamps
Clamp Remover
For removal of MT-613
snap-on clamps
Link adaptor
For attachment / removal
of drop out fuses prior to
applying # DOFEA
Liveline Clamp
Remover
Refer to pages E19-E22 for Adaptors
Bail Clamps, Stirrups & Adjustable Fixed Points
Part No: Various
•
Provides a point for earthing clamps on large conductors
Bail Clamps & Stirrups
Picture
Part No
Description
Cond. Range (mm)
1
ESTS
Single Conductor
21-33.8
2
ESTD
Double Conductor
21-33.8
3
ESTT
Triple Conductor
21-33.8
4
BBESA-XX.X*
Single Conductor
>33.8
1
2
3
4
* XX.X made specifically to conductor size, dimensions must be supplied
Fixed Points
Picture
I5
Part No
Dimensions
Rating
(kA/1s) Length Width Depth
For Conductor/Busbar
Type
Ø mm
Stud
Ø mm
Weight
(kg)
MT-790
30
255
105
50
Cu
12-60
18
1.40
MT-792
30
270
105
60
Al
12-60
20
0.85
MT-797
20
240
170
60
Al
60-120
20
1.20
Quality Electrical Equipment for Generation, Transmission & Distribution
the energy network
Temporary Earth Rod Driver
•
•
•
•
•
•
•
o
o
o
o
o
o
earthing and
jumpers
Part No: TEMP-ERD
For temporary earthing applications
600mm depth mark on drive rod
Clearance for earth clamp attachment
T-Handle lock screw secures sliding shaft for storage
Available in kits with earth leads
Not fault current tested
Features:
Slide Hammer Drive
Rubber Hand Grips
Stainless Steel Rod
Heavy Duty Top Bash Cap
Chiselled Drive Tip
Lock Screw
Optional Lug Tab
Part No
Length OAL Extended/Retracted (mm)
Depth Mark (mm)
Rod OD (mm)
Weight (kg)
TEMP-ERD
1735 / 1345
600
16
6.5
STRINGING GROUNDS
Standard
Part No: Various
•
Effectively earths conductors during stringing
operations
•
Anchor eye provided to restrain during stringing
•
For earth lead model refer below
9738
Part No
kA Rating/0.5sec
Max Conductor Size
Weight (kg)
78000
25
3.0 – 41.0
4.53
9738
19.1
4.1 – 28.5
1.50
78000
Stringing Earth Assemblies
Part No: Various
•
•
Stringing earth with fault current rated clamp and lead
Customised assembly to customer requirements
To order complete rated and assembled Stringing
Grounds, advise the following:
Required Fault Current
_____ kA/0.5sec
Length of Cable Required _____ metres
Earth End Configuration:
T Handle
www.tengroup.com.au | 1300 ASK TEN
Screwdriver
Handle
Lug Only
I6
the energy network
earthing and
jumpers
EQUIPOTENTIAL MATTING
Equipotential Continuity Mats
Part No: KTM Series
•
•
•
•
•
•
•
•
For establishing temporary equipotential zone during
energised and de-energised work practices
Prevents workers from being exposed to hazardous
differences in electrical potential
Portable, versatile and lightweight
Supplied with clamp on cable and link as standard,
other clamps sold separately
Non-slip black matting also available
Complies with OSHA 1910.269
Manufactured from high amperage tinned copper braid
sewn into grid pattern onto vinyl/polyester fabric
Special sizes and configurations available
Applications
Equipment
Details
Padmount Transformers & Switches
Creates same type of equipotential zone as “Contact Bar” or “Pole Band”
Mechanical Equipment Grounding
Utility vehicles, winches and pulling or stringing machines
Gang Switches
(Transmission & Distribution)
Can eliminate step and touch potential when installing, maintaining or operating
regulators, reclosers and capacitor banks
Substation Grids
For worker protection where substation ground mat integrity is questionable
Hydro-Excavation
For safety of workers during vacuum excavation of soil near underground power
Part No
Colour
Style
Dimensions (m)
Lead Length (m)
Clamp
AKTM5-5-1.5T
Orange
Kit, Mat with Clamp in Bag
1.5 x 1.5
1.5
LCM121H12
AKTMNS5-5-1.5T
Black
Kit, Non-Slip Mat with Clamp in Bag
1.5 x 1.5
1.5
LCM121H12
Standard
Clamp
Part Number
LCM121H12
(See page I10)
Kit Picture
Large Area Configuration Example
Part Number
AKTM5-5-1.5T
Custo
desig m
ns
mach for
in
availa es
ble
Large Area Configuration
Joining together mats for a larger protection area is easy with the Cascading
Clamp or Screwdriver handle clamp. Connected together, the conductive grid
becomes one. Whenever a larger area is needed, simply connect as many mats
together as required, using Cascading or Screwdriver Clamps.
Contact TEN for details on cascading clamp
Storage, Care & Maintenance of Equipotential Matting
Matting can be folded or rolled and stored in a dry protective carry bag. Keeping your mat away from the elements when not is use will prolong the life expectancy and properties.
Use a hose to clean mat but never store wet or damp.
I7
Quality Electrical Equipment for Generation, Transmission & Distribution
the energy network
DISCHARGE STICKS
earthing and
jumpers
Discharge Stick
Part No: 100 Series
•
•
•
•
•
•
•
•
Safely drains capacitive charge after a circuit has
been de-energised
Insulating stick with handguard and rubber end cap
Stainless steel hook
Earth lead included
Supplied with or without clamp
Stick tested to ASTM F-711
Discharge limiting resistor sold separately
Earth cable is copper with yellow neoprene jacket
Stick Hook Length / OD Opening / OD
(mm)
(mm)
Lead
Length
Weight
(kg)
1.8m
1.2
2.4m
1.4
3.0m
1.7
A1007-CLCM
4.5m
2.3
A1008-CLCM
6.0m
3.0
Part No*
A1004-CLCM
A1005-CLCM
A1006-CLCM
600 / 32
34.9 / 6.35
A1004-CLCM
* LCM12H/12 Clamp Used
Discharge Limiting Resistor
Part No
Description
Weight (kg)
6753
Resistor Add-On, 10kV 10MΩ
0.3
Discharge Kit
Part No: K-SAFE-1
•
•
•
Example of specially designed kit for mines personnel
Includes operational and test equipment in storage bag
Contact TEN for details
Part No
Item Description
Qty in Kit
A1004-CLCM
Assembled Discharge Stick
1
6753
Add on Resistor Stick
1
LT-220
240V - 220kV Detector voltage
1
5467-2
Sectional Universal Head Stick
1
546-2
Sectional Extension Stick
1
10-090
Silicone Cloth
1
E216YB-10
20kVAC Gloves rubber
1
LPG3S-10
Leather Gloves (pair)
1
M05CHRYTEN-CHP
PVC Carry Bag with Shoulder Straps
1
A18007
32mm Female Base Cap
1
M07GBWYTEN-C1F
Canvas Glove Bag
1
www.tengroup.com.au | 1300 ASK TEN
I8
the energy network
earthing and
jumpers
JUMPERING EQUIPMENT
Cable, LV (Insulated 0.6-1kV)
Part No: EZ Series
•
Fine strand annealed copper conductor with orange outer sheath and white inner insulation
•
Insulation is low smoke, zero halogen, elastomeric rubber splash resistant to oils, petrol and acid
•
Resists ozone and UV, Abrasion resistant
•
Temperature rated for -40 to 110°C
•
Conforms to AS/NZS: 1125; 5000.1 & 3191 •
Marked with voltage rating and conforming standard
Part No
Voltage Rating
(kV)
Continuous
Current Amps
(A)
Short Circuit
Current
(kA)/1.0sec
EZPAXN/1C016OR
0.6/1
105
2.11
EZPAXN/1C025OR
0.6/1
145
3.30
EZPAXN/1C035OR
0.6/1
175
4.62
EZPAXN/1C050OR
0.6/1
215
6.60
EZPAXN/1C070OR
0.6/1
270
9.24
EZPAXN/1C095OR
0.6/1
340
EZPAXN/1C120OR
0.6/1
395
EZPAXN/1C150OR
0.6/1
EZPAXN/1C185OR
0.6/1
Conductor Ø
(mm)
Cable Ø
(mm)
Approx Wt
(kg per m)
4.9
9.5
0.18
6.2
11.2
0.27
7.5
12.5
0.37
9.0
14.2
0.51
10.6
16.0
0.69
12.54
12.5
18.2
0.93
15.84
14.2
20.1
1.15
455
19.80
16.0
22.6
1.44
530
24.42
17.6
24.8
1.77
Cable, LV (Insulated 0.6-1kV)
Part No: BIE-CGC Series
•
•
•
•
•
Super flexible fine soft drawn copper stranding with clear jacket
Temperature rated for -10 to 60°C
Conforms to ASTM-F855, Type III
For use in open areas
Marked with voltage rating and conforming standard
Part No
AWG
Voltage Rating
(kV)
Continuous
Short Circuit
Conductor Ø Cable Ø Approx Wt
Current Amps (A) Current (kA)/1.0sec
(mm)
(mm) (kg per m)
BIE-CGC2
#2
0.6/1
200
18
8.0
15.0
BIE-CGC110
1/0
0.6/1
250
28
10.0
17.0
0.18
0.27
BIE-CGC210
2/0
0.6/1
300
36
11.5
19.0
0.37
BIE-CGC410
4/0
0.6/1
350
46
15.0
23.0
0.51
Cable, HV (Insulated 15-35kV)
Part No: Various
•
•
•
•
•
•
•
I9
Extra flexible alloy coated copper
Flexible at low temperatures and rated to 90°C
Conductive strand shield improves service life, dielectric strength and
eliminates internal corona
Factory tested, insulation meets or exceeds ICEA-NEMA Standard S-68-516
Insulation is cured ethylene propylene rubber. Resists abrasion, heat, moisture & UV
25 & 35kV cable conforms to ASTM-D470
Marked with amperage and voltage rating
Part No
AWG
Jacket Insulation
Rating (kV)
Continuous
Current Amps (A)
Conductor Ø (mm)
Cable Ø (mm)
Approx. Weight
(kg per metre)
12198
#2
15
200
8.53
19.81
0.6
12199
1/0
15
250
10.76
21.97
0.8
12200
2/0
15
300
11.93
23.24
1.0
12201
4/0
15
400
15.29
27.17
1.4
6874
2/0
25
300
12.11
29.21
1.2
6859
1/0
35
250
10.76
34.29
1.5
Quality Electrical Equipment for Generation, Transmission & Distribution
the energy network
Clamps
•
•
Popular line clamps for jumpers/hoppers/bonders
Other clamps available
LCM12H12
LCM101H
12-***H
13004
13765
Clamp Type
C
C
Medium
Medium
Clamp Style
Screw
Screw
Screw
Screw
Handle Type /
Application
Screwdriver Handle
Insulated Handle ***
(1kV)
Moulded Grip
Moulded Grip
Cable Attachment
Lug (M12)
Lug (M12)
Threaded Ferrule
Threaded Ferrule
Continuous Current
Amps (A)
400
400
400
400
Fault Current
(kA)/0.5sec
13kA / 1 sec
13kA / 1 sec
-
-
Min Clamp
Conductor OD (mm)
5
5
4.1
4.1
Max Clamp
Conductor OD (mm)
19
19
19.0
19.0
Part No
Picture
earthing and
jumpers
Part No: Various
*** Length of handle to be specified, screwdriver handle fitted to end is total of 125mm of end.
EXAMPLE: For 500mm total handle length, 375mm shaft # LCM101-375H with 125mm handle is 500mm OL
Part No
11000
13768
G3622-1
C600-0197
Clamp Type
Large
Large
Duckbill
Duckbill
Clamp Style
Screw
Screw
Screw
Screw
Handle Type /
Application
Moulded Grip
Moulded Grip
Shotgun
Shotgun
Cable Attachment
Threaded Ferrule
Threaded Ferrule
Solid Ferrule
Threaded Ferrule
Continuous Current
Amps (A)
400
400
400
400
Fault Current (kA)
-
-
30/0.5sec
21/1sec
30/0.5sec
21/1sec
Min Clamp Conductor
OD (mm)
4.1
4.1
4.1
4.1
Max Clamp
Conductor OD (mm)
24.8
24.8
29.5
38.2
Picture
www.tengroup.com.au | 1300 ASK TEN
I10
the energy network
earthing and
jumpers
Ferrules
Part No: Various
•
Cable connection joints and terminations
Picture
Type
Lugs
Threaded Ferrules
Solid Ferrules
Notes
Various Styles, Makes (Cu/Al) &
Ranges Available
Recommended for all Threaded
Clamp Styles
For Solid Ferrule Clamps
Suits Clamp #
LCM Series & SECR
13004, 13765, 11000, 13768,
G3622-1
C600-0197
Styles & Part
No’s
Lug Styles Available
Part No.
Cable Size AWG
Part No.
Cable Size AWG
Standard
13100
#2
P30244
#2
Bell Mouth or Double Grip
13101
1/0
P30245
1/0
Long Palm/Barrel
13102
2/0
P30246
2/0
Circuit Breaker
13103
4/0
P30247
4/0
Nominate clear non-mastic or black mastic filled heat shrink for your jumper
Assembled Jumpers
Part No: AJH Series
•
•
•
Jumpers are made to customer specific requirements
Quality components from leading industry manufacturers
Dedicated work order number on each unit with manufacture date
Low Voltage, common configurations
Picture
I11
Part No
AJT07(2)F12C70
AJT077(2)F45C70
AJT077(2)F45C70
AJHS85(2)S61S85
Insulation
Voltage (kV)
1
1
1
0.6
Continuous
Current (A)
270
270
270
253
Length Cable (m)
2
2
3 x 2m
2
Clamp Range OD
(mm)
5-19
5-19
5-19
5-30
Quality Electrical Equipment for Generation, Transmission & Distribution
the energy network
Picture
Part No.
AJH01(3)C22H47
AJH74(4)H04H02
AJH59(5)H68H01
Cable Insulation
Voltage (kV)
15
25
35
Cable Continuous
Current (A)
400
300
250
Length Cable (m)
3
4
5
Clamp Part No.
C600-0197
13004
13768
Clamp Type
Duckbill-Shotgun
Medium Range
Large Range
Clamp Range OD
(mm)
4.1 – 38.2
4.1 - 18.9
4.1 – 24.8
earthing and
jumpers
High Voltage, common configurations
Labelling
•
•
•
TEN labels all units with the product code, work order number, date of manufacture and quality check
Customised labels available
Contact TEN for more information
www.tengroup.com.au | 1300 ASK TEN
I12
the energy network
earthing and
jumpers
Inline Switches, Components & Assemblies
Suspension Link Type Switch
Part No: Various
•
•
•
•
•
•
Range of inline suspension switches or links
Light to heavy duty range for MV-HV
For permanent or temporary installation
Available with hanging hooks for temporary installations
Refer below for factory assembled inline switch kits
Arc shute model available #ALTD06200RL
Supplied with hanging hooks,
blade guide and earthing/
parking stubs
Supplied with arc shutes
Model
AEM
Chance
ABB-150*
ABB-200*
Part No
SL200-A6641-031
ALTD06200RL
7505533
7505440
Voltage Rating (kV)
12-36
15-38
24
36
Supplied with blade guide.
Earthing bolt available
Amps Continuous
800
600
800
800
BIL kV
200
200
150
200
Tension kN
70
66.7
70
90
Weight kg
7.3
5.7
5.7
7.5
* Minimum quantity purchase of 10 units
1
Includes hanging hooks & earth bolt
Part No: ILLH Series
•
Hooks for hanging switches onto overhead conductors
Switch Model
AEM*
Chance
ABB-150 & ABB-200
Part No
ILLHA
ILLHC
ILLHB
* Supplied with hanging hooks as standard
Ratchet Spanner Turnbuckles, Folding or Straight
Part No: AT-BUCK-RAT Series
•
•
•
•
•
Turnbuckle with ratchet spanner
1.6 Tonne rated
Folding ratchet supplied standard
Forged steel with galvanised and zinc spray finish
Straight podger supplied if folding version unavailable
Straight Ratchet
Turnbuckle
Picture
I13
Part No
AT-BUCK-RAT-E-E
AT-BUCK-RAT-J-E
AT-BUCK-RAT-J-J
Configuration
Eye to Eye
Jaw to Eye
Jaw to Jaw
Quality Electrical Equipment for Generation, Transmission & Distribution
the energy network
Assembled Inline Switches
•
•
Supplied with standard 2.0m jumper leads terminated with heat shrink and line clamps
Dedicated work order number, date of manufacture and part number on each unit
Picture
Part No
AISAYFF12H012EE
AISBYFH65H742JE
AISCYFH00B202JJ
Switch Type
AEM
ABB
Chance
Switch Rating
Continuous Amps (A)
800
800
600
Switch Rating Voltage
(kV)
12-36
36
15-38
Insulation Voltage of
Cable (kV)
15
25
35
Cable Continuous
Current (A)
400
300
300
Length Cable (m)
2
2
2
Clamp Type
LCM12H12
13765
11000
Clamp Range OD (mm)
5-19
4.1 - 18.9
4.1 - 24.8
earthing and
jumpers
Part No: Various
We assemble in house:
Inline Links & Switches
LV & HV Jumpering
Equipment
Bonding Equipment
For more information or to receive a quote, contact TEN
www.tengroup.com.au | 1300 ASK TEN
I14
the energy network
earthing and
jumpers
LOAD TOOLS
Load Pick-Up
Part No: Various
•
•
•
•
•
Installed with shotgun or glove and barrier method
Completely self contained with priming tool, firing lanyard and safety latch
Clear plastic housing allows quick and easy inspection
Cast aluminium alloy head also serves as storage port for priming tool
Carry case sold separately
6600
1
Conductor Size (mm)
Min
Max
Voltage
Rating (kV)
Continuous Current
(Amps)
Wt (kg)
Tool with Fitted
Jumper Cable
4.1
31.8
27
300
2.7
6605
Tool with Stud for
use with assembled
Jumpers
4.1
31.8
27
300
2.8
01-089
Padded Case
-
-
-
1.2
Part No
Description
6600¹
Cable length & clamp style must be specified
Load Break & Pick Up
Part No: Various
•
•
•
•
•
•
•
Installed with shotgun or glove and barrier method
Simple to use, lightweight and compact
Clear plastic housing allows quick and easy inspection
Positive lock ensures tool stays in open or closed circuit until ready
Stud for use with assembled jumpers
Large yellow band gives visual assurance that tool is closed
Carry case sold separately
Part No
USBS-15-1*
USBS-15-2*
USBS-27-1*
USBS-27-2*
USBS-46-1*
USBS-46-2*
Voltage Rating
(kV)
15
15
27
27
46
46
Load Break
Rating (Amps)
300
300
300
300
200
200
Load Pick-Up
Rating (Amps)
300
300
300
300
200
200
Continuous
Current (Amps)
300
300
300
300
200
200
Conductor Size
(mm)
4.1 -27.9
Head Type
Jumper
Duckbill
Jumper
Duckbill
Jumper
Duckbill
Dimensions
(mm)
685 x 65
685 x 65
787 x 65
787 x 65
991 x 65
991 x 65
Weight (kg)
3.22
3.22
3.60
3.60
4.60
4.60
* Add suffix “-s” for soft carry case
I15