pv direct-driven inverter gmv technical sales guide

Transcription

pv direct-driven inverter gmv technical sales guide
PV DIRECT-DRIVEN INVERTER GMV
TECHNICAL SALES GUIDE
(201506)
TECHNICAL SALES GUIDE-50Hz
CAPACITY RANGE:12~16kW
SUPER HIGH AMBIENT OPERATION TO 54
GREE ELECTRIC APPLIANCES INC.OF ZHUHAI
CONTENTS
1. OUTLINE OF MULTI GMV ...........................................................................................................3
2. SUMMARY OF SYSTEM EQUIPMENTS .......................................................................................7
3. BASIC SYSTEM CONFIGURATION ............................................................................................8
4. EQUIPMENT SELECTION PROCEDURE .....................................................................................9
5. REFRIGERANT PIPING DESIGN ...............................................................................................13
6. WIRING DESIGN ....................................................................................................................17
7. ACCESSORIES .......................................................................................................................18
8. TECHNICAL SPECIFICATIONS ................................................................................................18
9. DIMENSIONAL DRAWINGS ....................................................................................................19
10.PART OF PV INTRODUCTION..................................................................................................21
2
Pv Direct-Driven Inverter GMV
PV Direct-Driven Inverter GMV Technical Sales Guide
1 OUTLINE OF MULTI GMV
1.1 Product List
GMV-HY120WLT/A
Model
GMV-HY140WLT/A
GMV-HY160WLT/A
1.2 Product Features
1.2.1 Summary of Features
Photovoltaic direct-driven inverter GMV combine GREE bipolar compress with solar technology,
it is best photovoltaic GMV product also us company strongly detrude newly resource product.use
parallel connection of small bipolar compress.air-condition have many the quality of being
outstanding or extremely good, such as high efficiency,wide operation range,big resist ability
fineness at a disadvantage condition, high control precision, use highly dependable. solar
energy translate into DC electricity base on photoemission and provide electricity for air-condition
or generate for grid. Product’s Cooling Capacity from 12kw to 16kw, indoor unit have mucy capacity to choose.
1.2.2 Introduction of Features
˄˅+LJK(IILFLHQF\
The system adopts all DC motor,which greatly improves efficiency .The highest IPLV reaches 7.05,
which is increased greatly compared with other company.
8
7
6
5
4
7.05
6.6
6.2
6.2
4.8
4.4
6.5
5.6
4.8
4.6
6
5.4
4.6
DK company
H
3
2
1
0
PV GMV only grid
company
DZ company
M
12KW
14KW
company
16KW
Pv Direct-Driven Inverter GMV
3
˄˅%LJUHVLVWDELOLW\DWVFXUYLQHVVFRQGLWLRQ
3KRWRYROWDLFGLUHFWGULYHQLQYHUWHU*09V\VWHPXVH*5((ELSRODUFRPSUHVVILUVWO\LQWKH
DLUFRQGLWLRQVFRSHV7KHSURGXFWLVHQGRZHGZLWKWKHIHDWXUHRIELJUHVLVWDELOLW\DWVFXUYLQHVV
FRQGLWLRQ,WFDQRSHUDWLRQYHU\JRRG([SHULPHQWGDWHLQGLFDWH3KRWRYROWDLFGLUHFWGULYHQLQYHUWHU
*09LVEHWWHUUXQLQJDWVFXUYLQHVVFRQGLWLRQWKDQFRPPRQ*09
scurviness condition capacity compare
120.0%
100.0%
80.0%
common GMV
solar GMV
106.2% 14.3%
15.2%
22.6%
92.9%
91.6%
79.7%
79.5%
65.0%
60.0%
44.3%
21.6%
90.0%
68.7%
74.0%
47.6%
40.0%
20.0%
0.0%
7/6 Heating
2/1 Heating
-7 Heating
-15Heating
43Cooling
˄˅:LGHRSHUDWLRQUDQJH
&RPPRQ*09V\VWHPFDQÿWZHOOUXQDWVFXUYLQHVVFRQGLWLRQEHFDXVHLWPDNHXSRIPRQRSROH
FRPSUHVV6RODU*09V\VWHPPDNHXSRIELSRODUFRPSUHVVVRLWKDYHZLGHRSHUDWLRQUDQJH
3KRWRYROWDLFGLUHFWGULYHQLQYHUWHU*09FRXOGUHSO\WRVFXUYLQHVVFRQGLWLRQ3KRWRYROWDLF
GLUHFWGULYHQLQYHUWHU*09FRXOGRSHUDWLRQIURPćWRć
ď
ď
ď
ď
ď
ď
ď
ď
ď
ď
M company
4
Pv Direct-Driven Inverter GMV
H company
R company
D company
solar GMV
PV Direct-Driven Inverter GMV Technical Sales Guide
˄˅+LJKSUHFLVLRQFRQWURO
3KRWRYROWDLFGLUHFWGULYHQLQYHUWHU*09V\VWHPPDNHXSDFRXSOHRILVRPHWULFFRPSUHVVRUWKDW
FRPSUHVVRUFDSDELOLW\LVVPDOOHU,QFRPSUHVVRUFRQWUROIUHTXHQF\FRQWURODVSHFWVPDOOHULVRPHWULF
LVKLJKHUSUHFLVLRQFRQWUROWKDQELJJHU6PDOOHULVRPHWULFFRPSUHVVRUIUHTXHQF\FKDQJHK]
FRUUHVSRQGWRELJJHUFKDQJH+=7KHSURGXFWLVHQGRZHGZLWKWKHIHDWXUHRIZHOOHFRQRPL]HUHVRXUFH
KLJKSUHFLVLRQFRQWUROLQGRRUWHPSHUDWXUHKLJKFRPIRUW7KHSURGXFWKDYHPDQ\KLJKSUHFLVLRQSUHVVXUH
VHQVRUVWKDWWKH\DUHERWKFROOHFWLRQLQJDQGIHHGEDFNLQJ
Compressor
control
Fan control
‡ International one-up frequency conversion control
technique /0.5Hz precision frequency control
Collection
Feedback
‡ unbrush DC archive timing fan control
Electron expansion ‡ PID intellingent high precision electron expansion
valve control
valve control
High precision
pressure sensor
date collection
system
˄˅3HUIHFWSURWHFWLRQIXQFWLRQ
3KRWRYROWDLFGLUHFWGULYHQLQYHUWHU*09V\VWHPKDYHPDQ\SURWHFWLRQIXQFWLRQVWKDWVXFKDV
+LJK/RZSUHVVXUHSURWHFWFRPSUHVVRUSRZHUSURWHFWH[KDXVWWHPSHUDWXUHSURWHFWFRPSUHVVRURYHU
ORDGLQJSURWHFWDQGVRRQ7KHIXQFWLRQVFRXOGGHFUHDVHKDUGZDUHPDOIXQFWLRQ
Familiar fault 1
Compressor burnout
Familiar fault 2
control burnout
countermeasure
countermeasure
compressor power protect
module temperature protect
High/Low pressure protect
High/Low pressure protect
exhaust temperature
protect
compressor over loading protect
current protect
insurance tube break protect
˄˅/DWHVW&$1EXVFRPPXQLFDWLRQ
3KRWRYROWDLFGLUHFWGULYHQLQYHUWHU*09DGRSWODWHVW&$1EXVFRPPXQLFDWLRQWHFKQLTXHWKDWLW
KDYHKHUHLQDIWHUVRPHH[FHOOHQF\
ķ/RZIDXOWUDWH+DUGZDUHFKHFNRXWPHDVXUHEHXVHGZKLFKORZIDXOWUDWHXQLWGRQRWZRUNFRQWURO
V\VWHPIDXOW
ĸ$QWLMDPPLQJVWURQJ&$1EXVFRPPXQLFDWLRQKDYHVPDOOHUFXUUHQWXQHDV\PLQLVKFRPPXQLFDWLRQGDWD
Ĺ/RQJFRPPXQLFDWLRQOLQH&$1EXVFRPPXQLFDWLRQEHWZHHQLQGRRUXQLWDQGRXWGRRUXQLWFDQEH
DVORQJDVP
ĺ&$1EXVFRPPXQLFDWLRQWHFKQLTXHLVQRQSRODUGHVLJQZKLFKLWGRHVQRWGLVWLQJXLVKLQJOLQHVWDWLRQ
Low fault rate
CAN bus
communi- Anti-jamming strong
cation
Long communication
technique
nonpolar design
Unit control credibility decrease fault
Needless use specialties communication line
Fully content GMV indoor unit fact
unafraid turn over communication line
Pv Direct-Driven Inverter GMV
5
˄˅+LJKHIILFLHQF\DQGGHSHQGDEOHDGGHQWKDOS\FRQWUROWHFKQLTXH
Two-stage compressor is used which deal with filling gas add enthalpy control technique.Unit control
UHSDLUZKHWKHUZHOORUEDGFRQQHFWLRQZLWKFDSDELOLW\DQGGHSHQGDELOLW\SKRWRYROWDLF
gad to
GLUHFWGULYHQLQYHUWHU*09PDNHXVHRIDGGHQWKDOS\FRQWUROWHFKQLTXHWKDWZHZRUNHGYHU\ORQJ
RQGD\DQGQLJKW7KHWHFKQLTXHHQVXUHWKDWXQLWPRYHQRUPDOO\QD\FDSDELOLW\DQGHIILFLHQF\
REWDLQEHVWDGYDQFH
High efficiency and dependability add
enthalpy control technique
Exactly electron
expansion valve
control
Perfect
superheat
control
intelligentize
judgement function
capability and efficiency best exert
avoid liquid refrigeration enter compressor
˄˅3HUIHFWO\XWLOL]HVRODUQHZUHVRXUFH
$LUFRQGLWLRQDQGKHDWLQJGHSOHWLRQDUHPRVWO\PDNLQJXSRIDUFKLWHFWXUHGHSOHWLRQQRZˈLW
LVUXQQLQJVKRUWRIHOHFWULFSRZHUEUXPHDQGKD]HDUHYHU\JUDYHVRRXUSKRWRYROWDLFGLUHFWGULYHQ
LQYHUWHU*09VKRXOGEULQJYHU\JUHDWHFRQRP\EHQHILWDQGVRFLHW\EHQHILW
Highly efficiency avail
solar resource
decrease air-condition
consume
generate to grid for contributing
6
Pv Direct-Driven Inverter GMV
renewablecunpollute
3KRWRYROWDLF
GLUHFWGULYHQ
LQYHUWHU*09
decrease carbon to release
tranquilization
easy popularization
PV Direct-Driven Inverter GMV Technical Sales Guide
2
SUMMARY OF SYSTEM EQUIPMENTS
2.1 Outdoor Unit
Model
Cooling
Heating
Capacity(kW) Capacity(kW)
Code
GMV-HY120WL
T/A
KN870W0020
12
Power
Supply
Refrigerant
type
14
220V̚ 50Hz
GMV-HY140WL
T/A
GMV-HY140WL
T/A
Appearance
KN870W0030
14
16
KN870W0010
16
18
R410a
2.1.1 Nomenclature
GMV
ƶ
1
2
-
No.
Description
1
Code for type
2
Climate type
3
Units series
ƶ
ƶ
ƶ
W
ƶ
3
4
5
6
7
/
ƶ
ƶ
ƶ
ƶ
8
9
10
11
Options
GMV – Gree Multi Variable
Default – T1 condition
huose—H
commercial—Na
6
Function code Q – Heat recovery unit; S – Water heater; W – Water-cooled unit; X – Fresh air unit
Y-photovoltaic
Cooling
Nominal cooling capacity/100(W)
capacity
Outdoor unit
W
7
Construction
4
5
L – Non-modular side discharge
8
Refrigerant
9
Series number
Product serial number: A, B, C… or 1, 2, 3…
R410A: Na
10
Power supply
Within 7000~18000W; Single phase power supply: Na
11
Export
Na
2.1.2 Rated Conditions
Indoor side inlet air status
Dry bulb temperature
Wet bulb temperature
Outdoor side inlet air status
Dry bulb temperature
Wet bulb a
temperature
Cooling
27
19
35
24
Heating
20
—
7
6
Pv Direct-Driven Inverter GMV
7
2.1.3 Branching joints
Model name
Usage
GMV-HY120WLT/A
Y-shape
branching joint
Y-shape
branching
joint
GMV-HY140WLT/A
FQ01A
to other branching
joint or indoor unit
Inlet
pipes used in the field
ODU
GMV-HY160WLT/A
3
Appearance
BASIC SYSTEM CONFIGURATION
3.1 System legend(ex.)
Model name of outdoor unit: GMV-HY160WLT/A
Allowed capacity code of indoor unit: Min:8000W Max: 21600W
DŽ
Note: The total capacity code of indoor units shall be within 50%~135% of the capacity code
of selected outdoor unit.
ODU
GMV-ND25PL/B
GMV-ND72PL/B
GMV-ND25PL/B
GMV-ND50PL/B
GMV-ND36PL/B
GMV-HY160WLT/A Total capacity code of indoor units is 25×2+72+36+50=208, so the selec
-ted outdoor unit is GMV-HY160WLT/A.
8
Pv Direct-Driven Inverter GMV
PV Direct-Driven Inverter GMV Technical Sales Guide
4
EQUIPMENT SELECTION PROCEDURE
Calculate the heat load of the room
Correction of indoor unit capacity
Select indoor unit model
Select indoor unit model
Correction of outdoor unit capacity
Select outdoor unit model
4.2 Combination conditions for indoor unit and outdoor unit
1) The capacity code of indoor units = The capacity co de of indoor units = total capa
-city code of outdoor unit×(50%~135%).
2) For outdoor unit, maximum No. of connectable indoor units and total capacity code of i
.
-ndoor units are decided.
Model name of outdoor unit
Capacity code of outdoor unit
Max. No. of indoor units
GMV-HY120WLT/A
12KW
6
GMV-HY140WLT/A
14KW
8
GMV-HY160WLT/A
16KW
9
4.3 Cooling/Heating capacity characteristics
(1)Cooling capacity calculation method.
(2)Heating capacity calculation method.
Cooling or heating capacity calculation method:
R410A outdoor unit capacity = outdoor unit capacity in rated condition × correction fac
-tor of indoor and outdoor temperature condition × connection pipe distance, correction
factor of height difference between indoor unit and outdoor unit.
ķIf the total capacity code of indoor units is smaller than the capacity code of outdoor u
-nit, the capacity
of outdoor unit in rated condition equals to the total capacity code of ind
-oor units;
ĸIf the total capacity code of indoor units is bigger than the capacity code of outdoor un
-it, the capacity of outdoor unit in rated condition equals to its rated cooling capacity;
ĹCorrection factor of indoor and outdoor temperature condition.
Pv Direct-Driven Inverter GMV
9
1) Correction factor of cooling capacity
43
40
35
30
25
20
16
14
16
18
20
22
24
26
2) Correction factor of heating capacity
27
26
24
22
20
18
16
14
12
10
-15
ĺCorrection
-10
-5
0
5
10
15 16
factor of connection pipe distance and height difference
Symbol instruction:
Hp: Height difference (m) between indoor unit and outdoor unit when indoor unit is lower
than outdoor unit;
Hm: Height difference (m) between indoor unit and outdoor unit when indoor unit is
higher than outdoor unit;
L: Single-pass equivalent connection pipe length L
The following chart is the capacity change rate in 100% load under standard condition (th
-ermostat is seWLQćLQFRROLQJDQGVHWLQćLQKHDWLQJ˅
10
Pv Direct-Driven Inverter GMV
PV Direct-Driven Inverter GMV Technical Sales Guide
50
40
30
20
Hp(m)
10
10 20 30 40 50 60 70 80 90 100 110 120 130 140 150
L( m)
Hm(m) 10
20
30
0. 95
0. 97
0. 99
40
50
40
20
Hp (m)
1.0
30
10
10 20 30 40 50 60 70 80 90 10 0 110 120 130 140 150
L(m)
Hm (m) 10
20
30
40
(3) Capacity of each indoor unit=Capacity of outdoor unit × Total capacity of indoor
units/Total capacity of synchronously operating indoor units.
(4) Operating temperature rang.
Temperature range
Cooling
10~52 oC
Heating
-30~27 oC
4.4 Example of equipment selection
(1)Overview of building model
a.Temperature condition
Outdoor temperature:35ćDB; Indoor temperature: 17
ćWB
b.Load in cooling
Load
Room A
Room B
Room C
Room D
Room E
2
7
2
4.7
3.2
(2)Selection Criteria for each floor
Pipe length: 55m; Height difference between indoor unit and outdoor unit: 25m (indoor
unit is higher than outdoor unit).
(3)Procedure and result of equipment selection
a.Procedure of equipment selection
Introduce the equipment selection procedure step by
. step
b.Equipment selection and capacity check
ķSelection of indoor unit.
Select suitable indoor unit according to the corrected load of indoor unit capac
-ity.Corrected load of indoor unit capacity=Load/Corrected ratio of cooling capaci
-ty related to temperature condition. Referring to the corrected ratio chart of
cooling capacity related to temperature condition, under outdoor temperature of 35
ć'%DQG indoor temperature of 17ćWB, the corrected ratio of cooling capacity is
0.94.
Selection result is as below:
Pv Direct-Driven Inverter GMV
11
Load (KW)
Corrected load
of capacity (KW)
Unit size
Capacity code
ĸ
Room A
Room B
Room C
Room D
Room E
2
7
2
4.7
3.2
2.12
7.45
2.12
5
3.40
25 unit
72 unit
25 unit
50 unit
36 unit
25
72
25
50
36
Selection of outdoor unit
The total capacity code of indoor units is 208. Please select suitable outdoor unit
according to the total capacity of indoor units and corrected situation.Capacity of
outdoor unit=Total capacity of indoor units/(Corrected ratio of cooling capacity rel
-ated to temperature condition × Correction of connection pipe length and height di
-fference) .After calculating the capacity of outdoor unit, select suitable outdoor
unit according to 50%~135% of the capacity of outdoor unit.
In the example, capacity of outdoor unit=208/(0.94×0.95)=233
Select the outdoor unit with capacity code of 160 and nominal cooling capacity of 16KW.
The capacity code ratio between indoor unit and outdoor unit is 208/160×100%=130%,
which is within 50%~135% and accords with the equipment selection standard.
Ĺ Correction of outdoor unit capacity
Suppose the combination situation between indoor unit and outdoor unit is as below.
Outdoor unit:GMV-HY160WLT/A
Indoor unit: GMV-ND25PL/B×2, GMV-ND72PL/B×1, GMV-ND50PL/B×1, GMV-ND36PL/B×1
If the total capacity code of indoor units is bigger than the capacity code of outdoor
unit, the capacity of outdoor unit in rated condition equals to its rated cooling capa
-city. So the capacity of outdoor unit under rated condition is 16KW.
ĺ Referring to the corrected ratio chart of cooling capacity related to temperature
FRQGLWLRQXQGHURXWGRRUWHPSHUDWXUHRIć'%DQGLQGRRUWHPSHUDWXUHRIć:%WKH
corrected ratio of cooling capacity is 0.94.
ĻReferring to the corrected ratio of connection pipe of 55m long and height difference
between indoor unit and outdoor unit of 25m (outdoor unit is lower than indoor unit),
the corrected ratio is 0.95.
ļCorrection of indoor unit capacity
Capacity of each indoor unit=Capacity of outdoor unit × Total capacity of indoor unit
s/Total capacity
of synchronously operating indoor units.
GMV-ND25PL/B ˖16×25/208=1.92KW
GMV-ND72PL/B ˖16×72/208=5.54KW
GMV-ND50PL/B ˖16×50/208=3.85KW
GMV-ND36PL/B ˖16×36/208=2.77KW
The result is as below:
Air conditioning load
Floor RoomNo
Cooling
1
12
Pv Direct-Driven Inverter GMV
A
B
C
D
E
Equipment selection
Indoor air
conditioning load
2
7
2
4.7
3.2
Indoor unit
Model
GMV-ND25PL/B
GMV-ND72PL/B
GMV-ND25PL/B
GMV-ND50PL/B
GMV-ND36PL/B
Capacity(kW)
Cooling
2.5
7.2
2.5
5.0
3.6
Outdoor unit
Model
Capacity(kW)
Cooling
GMV-HY160WLT/A
16
PV Direct-Driven Inverter GMV Technical Sales Guide
Piping distance
Floor
1
Room
No.
A
B
C
D
Equivalent
length(m)
85
Height
difference(m)
25m(ODU is lower
than IDU)
E
Capacity correction Capacity check after correction
Pipe correction ×
Capacity
Capacity(kW)
temp. correction
Judgment
Cooling
Cooling
Heating
The
1.92KW
selection
5.54KW
should
1.92KW
14.29
accord
3.85KW
with the
2.77KW
standard
c.Schematic diagram
Explain the location of units in each room and connection way of indoor unit and outdoor
unit with single-line chart.
ODU
5
REFRIGERANT PIPING DESIGN
5.1 Warning on refrigerant leakage
(1)Introduction of leakage detection method
Procedures of leakage detection.Before ex-factory, the cut-off valves of gap pipe and liquid pipe of
outdoor unit are closed. Please confirm it before installation.Before testing, apply some suitable lubricant
on the joint of cap and pipe. Use two wrenches when fixing the cap.Connecting outdoor pipeline for
testing is not allowed during leakage detection. The testing pressure of R410A system is 4.15MPa (for
R22 system, it is 3.0Mpa). The medium of airproof test must be dry nitrogen. Increase the pressure
slowly in three steps:
Step one: Slowly increase pressure to 0.5MPa and maintain pressure for 5min. Big leakage may be
found during leakage detection;
Step two: Slowly increase pressure to 1.5MPa and maintain pressure for 5min. Small leakage may be
found during airproof test;
Step three: For R410A system, slowly increase pressure to 4.15MPa(for R22 system, it is 3.0Mpa) and
maintain pressure for 5min. Tiny leakage may be found during strength test. Increase pressure to testing
pressure and maintain pressure for 24h. Check if the pressure decreases. The test is passed if pressure
doesn’t decrease.
(2) Introduction of handling method of leakage
Firstly, discharge the refrigerant and then charge nitrogen for leakage welding. The nitrogen charging
way is the same as that in airproof test. Blow away the impurities and clean the pipeline after finishing
welding. Finally, rearrange airproof test for leakage detection until there is no leakage.
Pv Direct-Driven Inverter GMV
13
5.2 Free branching system
5.3
Allowable length/height difference of refrigerant piping
Note: The equivalent length of one Y shape branching joint is 0.5m.
14
Pv Direct-Driven Inverter GMV
PV Direct-Driven Inverter GMV Technical Sales Guide
Total extension of pipe (Liquid pipe, real length)
Pipe
length
Allowable
value
300
Real length
120
Equivalent length
150
Farthest piping length
Height
difference
L1+L2+L3+a+b++c+d
L1+L2+L3+d
Equivalent length of farthest piping from 1st branching
Height between indoor and
outdoor units
Piping section
40
L2+L3+d
Upper outdoor unit
50
——
Lower outdoor unit
40
——
Upper outdoor unit
15
——
Lower outdoor unit
15
——
Height between indoor units
5.4 Selection of refrigerant piping
(1)Size of main pipe
Model
Gas pipe
Liquid pipe
GMV-HY120WLT/A
Ø15.9
Ø9.52
GMV-HY140WLT/A
Ø15.9
Ø9.52
GMV-HY160WLT/A
Ø19.05
Ø9.52
(2)Pipe size between branching joints
Total capacity code of indoor units at downstream side
Gas pipe
Liquid pipe
C İ5.6
Ø12.7
Ø 6.35
5.6 ˘ &”14.2
Ø15.9
Ø 9.52
14.2 ˘ &”22.0
Ø19.05
Ø 9.52
Pv Direct-Driven Inverter GMV
15
(3)Piping of indoor unit
Capacity rank of indoor unit
Gas pipe
Liquid pipe
&İ2.8
Ø9.52
Ø6.35
2.8 ˘ &İ5.0
Ø12.7
Ø6.35
5.0 ˘ &İ14.0
Ø15.9
Ø9.52
14.0 ˘ &İ16.0
Ø19.05
Ø9.52
16.0 ˘ &İ28.0
Ø22.2
Ø9.52
(4) Selection for branching section
Total capacity code of indoor unit
Y-shape branching joint
&İ20.0
Model name
FQ01A
5.5 Charging requirement with additional refrigerant
(1)Refrigerant in the system when shipped from the factory
Model name
Refrigerant amount
charged in factory (kg)
GMV-HY120WLT/A
GMV-HY140WLT/A
GMV-HY160WLT/A
8.0
8.0
8.0
(2)$GGLWLRQDOUHIULJHUDQWFKDUJHDPRXQW ě/HQJWKRIOLTXLGSLSHhUHIULJHUDQWFKDUJHDPRXQWSHU
meter
Note ˖
ķ The refrigerant amount inside the system before ex-factory doesn’t include the required additional
refrigerant charge amount inside the pipeline system of indoor units and the pipeline system
connecting indoor unit and outdoor unit.
ĸ For the length of connection pipe in field, the required additional refrigerant charge amount shall be
confirmed according to liquid pipe size in field and its length.
Ĺ Record additional refrigerant charge amount for future reference.
Note: If the total length of liquid pipe is within 20m, no additional refrigerant is needed.
When the compressor is not working after ensuring there is no leakage, charge the required additional
refrigerant amount to the unit from the valve of liquid pipe of outdoor unit. When the pipe pressure
increases and the additional refrigerant can’t be charged to the required amount quickly, please set
the unit in cooling operation status and charge refrigerant from the low pressure maintenance port of
outdoor unit.
16
Pv Direct-Driven Inverter GMV
PV Direct-Driven Inverter GMV Technical Sales Guide
6
WIRING DESIGN
6.1 General wiring principle
(1)All electrical work shall be done by professionals according to national and local laws and
regulations.
(2)The unit must be grounded reliably according to the related requirement of GB 50169.
(3) Connect wire according to the wiring diagram stuck on the unit.
6.2 Electrical wiring design
(1)Wiring drawing
D1 D2 G1 G2
communicationl
communication line
ine
Communicationl
Communication line
ine
Power
cable
Powerccable
Power
able
There are two wiring diagrams for communication wires of indoor/outdoor units and remote monitor:
1) Real line method;
2) Broken line method. Please select it based on the actual installation situation.
There are two wiring diagrams for power cord:
1) Real line method;
2) Broken line method. Please select it based on the actual installation situation.
(2) Selection of power supply cord and fuse of units
Power supply wiring
Model
Outdoor Unit
Wire size
GMV-HY120WLT/A
GMV-HY140WLT/A
GMV-HY160WLT/A
Outdoor Unit
4.00mm
4.00mm
6.00mm
Field fuse
2
32A
32A
40A
2
2
6.3 Wiring diagram of units
Communication wire
between IDU and ODU
ODU
D1
D2
G1
G2
Communication wire of IDU
G
Wired
controller
Power
D1
D2
H1
H2
G
G
G
Remote
monitor
Power
D1
D2
H1
H2
D1
D2
H1
H2
Wire
(resistance-matching)
Communication wire of IDU
Wired
controller
Wired
controller
Power
Power
Pv Direct-Driven Inverter GMV
17
6.4 Parameters
(1)Outdoor unit
Voltage Range
Compressor
Min
Max
RLA
LRA
kW
Fan Motor
FLA
MCA
Power Supply
GMV-HY120WLT/A
185
232
21
/
0.12
0.5A
28.1
32
/
GMV-HY140WLT/A
185
232
21
/
0.12
0.5A
31.8
32
/
GMV-HY160WLT/A
185
232
21
/
0.12
0.5A
33.6
40
/
Model name
LEGEND:
MCA: Minimum Circuit Amps
MOCP: Maximum Overcurrent Protection(Amps)
ICF: Maximum Instantaneous Current Flow Star
RLA: Rated Load Amps
7
MOCP
ICF
LRA: Locked Rotor Amps
FLA: Full Load Amps
kW: Fan Motor Rated Output(kW)
ACCESSORIES
Model name
Standard
GMV-HY120WLT/A
Ĝ
GMV-HY140WLT/A
Ĝ
GMV-HY160WLT/A
FQ01A Y FQ01A Y shape
branching joint
Condensate pipe
Ĝ
Option
Provide for oneself
Ĝ
Ĝ
Ĝ
Power cord
Ĝ
Filter
Signal wires among units
8
TECHNICAL SPECIFICATIONS
Model
Cooling capacity
-
GMV-HY120WLT/A
GMV-HY140WLT/A
GMV-HY160WLT/A
kW
12
14
16
Heating capacity
kW
14
16
18
Air volume
m 3 /h
6000
6300
6600
dB(A)
53
54
56
-
220~50Hz
220~50Hz
220V~50Hz
Noise (sound pressure level)
Power supply
18
Ĝ
Cooling power input
kW
2.7
3.6
4.35
Heating
kW
2.95
3.8
4.4
power input
Cooling current input
A
15
19.2
23.4
Heating
A
15.8
19.3
23
Maximum power input
kW
5.7
6.3
6.8
Maximum current
A
32
32
32
current input
Compressor type
-
Number of compressors
N
Inverter Rotary
2
Inverter Rotary
2
Inverter Rotary
2
Ambient temperature range of cooling
°C
10~54
10~54
10~54
Ambient temperature range of heating
°C
-30~27
-30~27
-30~27
Refrigerant type
-
R410A
R410A
R410A
Pv Direct-Driven Inverter GMV
PV Direct-Driven Inverter GMV Technical Sales Guide
Refrigerant charge volume
kg
8.0
8.0
8.0
Maximum qty of connected indoor units
unit
6
8
9
mm
¶15.9
¶15.9
¶19.05
Liquid pipe size
mm
¶9.52
¶9.52
¶9.52
Gas pipe size
External dimension (width)
mm
900
900
900
External dimension (depth)
mm
340
340
340
External dimension (height)
mm
1345
1345
1345
Packaging dimension (width)
mm
998
998
998
Packaging dimension (depth)
mm
458
458
458
Packaging dimension (height)
mm
1515
1515
1515
Net weight
kg
140
140
140
Gross weight
kg
151
151
151
Notes:
c.Rated cooling capacity test conditions: indoor 27°C DB/19°C WB, outdoor 35°C DB; connection pipe
length: 5 m, without height drop between units
d. Rated heating capacity test conditions: indoor 20°C DB, outdoor 7°C DB/6 °C WB; connection pipe
length: 5 m, without height drop between units
e. The total capacity of connected indoor units must be in the range of 50%~135% of the outdoor unit
capacity. The relevant parameters can be corrected by referring to the unit capacity correction table.
f.dThe above parameters are tested based on the standard connection pipe length. In the actual
project, the parameters should be corrected referring to the capacity correction for the long connection
pipe of units
9
DIMENSIONAL DRAWINGS
Include the required dimension of installation space of main unit and single unit.
A
B
C
D
E
Pv Direct-Driven Inverter GMV
19
Model
A
B
C
D
E
GMV-HY120WLT/A
GMV-HY140WLT/A
GMV-HY160WLT/A
900
340
1345
572
378
Installation dimension:
Wall
Wall
1000
500
500
500
500
Wall
Wall
(3) ranching join
Length of each kind of Y-shape branching joint and the dimension of connection pipe port.
Y-shape branching joint
˖FQ01A
Gas pipe
20
Pv Direct-Driven Inverter GMV
Liquid pipe
PV Direct-Driven Inverter GMV Technical Sales Guide
10
PART OF PV INTRODUCTION
10.1 PV of development and future
Solar is renewable resource and it was attached importance which clean,cheap,enough. solar is used
more and more openly on the world. It was for cutting down the cost of production. such as advancing
to decrease resource for architecture,depressing to let co2 and so on.The development process is as
follows.Basis on EPIA forecast,the cut-off date to forecast is 2050,solar generate
to grid more than 24% on all resource.
10.2 Photovoltaic direct-driven inverter GMV mode
10.2.1 Photovoltaic direct-driven inverter GMV system of configuration
GREE photovoltaic direct-driven inverter GMV is very well air-condition system which can
generation to grid and supply electricity to unit.The system reach to high level first of
all.It have fine mode to work.generation or supply need to less than 10ms at short notice.
The system process is as follows.
Pv Direct-Driven Inverter GMV
21
10.2.2 Photovoltaic direct-driven inverter GMV of fine mode
˄˅2QO\DLUFRQGLWLRQPRYHPRGH
,IVRODUGRQRWJHQHUDWLRQHOHFWULFLW\JULGVXSSO\HOHFWULFLW\WRUXQXQLWZKLFKLVFDOOHGRQO\
DLUFRQGLWLRQPRYHPRGH
˄˅2QO\VRODUJHQHUDWLRQWRJULGPRGH
8QLWGRQRWZRUNVRODUV\VWHPVXSSO\SRZHUWRJULGZKLFKLVFDOOHGRQO\VRODUJHQHUDWLRQWRJULGPRGH
˄˅2QO\VRODUJHQHUDWLRQHOHFWULFLW\WRXQLWPRGH
$OOVRODUV\VWHPJHQHUDWLRQHOHFWULFLW\HTXDOWRXQLWFRQVXPHIRUUXQQLQJZKLFKLVFDOOHGRQO\VRODU
JHQHUDWLRQHOHFWULFLW\WRXQLWPRGH
22
Pv Direct-Driven Inverter GMV
PV Direct-Driven Inverter GMV Technical Sales Guide
˄˅6RODUJHQHUDWLRQHOHFWULFLW\VXSSO\WRXQLWDQGJULGPRGH
6RODUJHQHUDWLRQHOHFWULFLW\LVPRUHWKDQXQLWFRQVXPHWRPRYLQJ7KHV\VWHPJHQHUDWLRQHOHFWULFLW\WRUXQ
XQLWRWKHUJHQHUDWLRQWRJULGZKLFKLVFDOOHG6RODUJHQHUDWLRQHOHFWULFLW\VXSSO\WRXQLWDQGJULGPRGH
˄˅6RODUJHQHUDWLRQHOHFWULFLW\DQGJULGVXSSO\WRXQLWPRGH
6RODUJHQHUDWLRQHOHFWULFLW\LVOHVVWKDQXQLWFRQVXPHWRPRYLQJ$OOVRODUV\VWHPJHQHUDWLRQHOHFWULFLW\WRXQLW
DQGUXQVKRUWRIXQLWJDLQWRJULGZKLFKLVFDOOHG6RODUJHQHUDWLRQHOHFWULFLW\DQGJULGVXSSO\WRXQLWPRGH
10.2.3 Dynamic load follow up the scent MPPT technique
ZHVWXG\WRIROORZZLQJXSWKHVFHQW0337WHFKQLTXHZKLFKFRPELQHWRREVHUYHZD\ZLWKWRIL[XSSDUDPHWHU
7KHWHFKQLTXHFDQVXSSO\ELJJHVWHOHFWULFLW\SRZHU
Pv Direct-Driven Inverter GMV
23
10.2.4 Photovoltaic direct-driven inverter GMV of configuration
Photovoltaic direct-driven inverter GMV combinative photovoltaic converse and outdoor.It has
consolidate and simpleness so on.
line. PV DC is direct current,connect line
Photovoltaic direct-driven inverter GMV connect
positive pole“L+”cathode poleĀ/ā˗$&is alternating current connect line“L”,“N”.
24
Pv Direct-Driven Inverter GMV
Gree Electric Appliances, Inc. of Zhuhai, founded in 1991, is the world's largest air
conditioner enterprise integrating R&D, manufacturing, marketing and services.
Technology Innovation and quality are always our priority. With efforts of
thousands of Gree's engineers, we own more than 3500 patents for our products.
Nowadays, we have 7 production bases in Zhuhai, Chongqing, Hefei and
Zhengzhou(China), as well as Brazil, Pakistan and Vietnam, with annual
production capacity of 30 million sets of residential air conditioners and 4 million
sets of commercial air conditioners.
With the installation of Gree commercial air conditioners in important projects at
home and abroad like Media Village for 2008 Beijing Olympic Games, Stadiums
for 2010 World Cup in South Africa, as well as India Telecom base station, Gree
commercial air conditioners are ready to develop steadily to every corner in the
world, to present a more comfortable and harmonious working environment and
family atmosphere.
GREE MAKING BETTER AIR CONDITIONERS GREE MAKING BETTER AIR CONDITIONERS GREE MAKING BETTER AIR
CONDITIONER GREE MAKIN BETTER
Add: West Jinji Rd,Qianshan Zhuhai,Guangdong,China519070
Tel: (+86-756)8614883
Fax: (+86-756)8614998
Http://www.gree.com
Email: [email protected]
For continous improvement in the products, Gree reserves the right to modify
without incurring and obligations.

Similar documents

January-February 2009 San Antonio Lawyer

January-February 2009 San Antonio Lawyer +HUQDQGH] WKLV VHPLQDU JDYH DWWRUQH\V LQIRUPDWLRQRQFRPPXQLW\DQGSROLFHUH VRXUFHV WKH FULPLQDO MXVWLFH V\VWHP DQG WULDOODZ\HUV·SHUVSHFWLYHVRQIDPLO\YLR OHQFHLQGLYRUFHDQGF...

More information

Service Manual for Portable DVD DPC-7909 Series

Service Manual for Portable DVD DPC-7909 Series Fully digital servo processing (focusing, tracking, sledge and spindle servo control)

More information

Design and Test of Nitrous Oxide Injectors for a Hybrid

Design and Test of Nitrous Oxide Injectors for a Hybrid 7$% 0DWHULDOSURSHUWLHVRIQLWURXVR[LGH 7KH LQMHFWLRQ DQJOHV DQG D UDZ LPSUHVVLRQ RI WKH DWRPL]DWLRQSURFHVVDUHILOPHGE\DKLJKVSHHGFDPHUD$ &DQRQ (;) ZDV XVHG IRU WKH ...

More information