Service Manual

Transcription

Service Manual
OC343A-1.qxp
06.8.2 11:31 AM
Page 1
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
August 2006
No. OC343
REVISED EDITION-A
TECHNICAL & SERVICE MANUAL
R410A
[Models]
PCFY-P15NGMU-E
PCFY-P24NGMU-E
PCFY-P30NGMU-E
PCFY-P36NGMU-E
R22
Revision:
• RoHS PARTS LIST is added.
• Some descriptions have been
modified.
• Please void OC343.
NOTE:
• This manual describes only
service data of the indoor
units.
• RoHS compliant products
have <G> mark on the spec
name plate.
• For servicing of RoHS
compliant products, refer to
the RoHS PARTS LIST.
CONTENTS
INDOOR UNIT
1. FEATURES ··········································2
2. PART NAMES AND FUNCTIONS ·······4
3. SPECIFICATIONS ·······························6
4. OUTLINES AND DIMENSIONS···········9
5. WIRING DIAGRAM····························13
6. REFRIGERANT SYSTEM DIAGRAM ··14
7. MICROPROCESSOR CONTROL······15
8. TROUBLE SHOOTING······················22
9. DISASSEMBLY PROCEDURE··········29
10. PARTS LIST······································33
11. RoHS PARTS LIST ··························40
12. OPTIONAL PARTS ··························47
OC343A-1.qxp
1
06.8.2 11:31 AM
Page 2
FEATURES
Indoor unit
Models
Cooling capacity / Heating capacity
PCFY-P15NGMU-E
PCFY-P24NGMU-E
PCFY-P30NGMU-E
PCFY-P36NGMU-E
15,000
24,000
30,000
36,000
/
/
/
/
17,000
27,000
34,000
40,000
Btu/h
Btu/h
Btu/h
Btu/h
Protruding portion B
Unifies the air speed
with the vane
1. EASY TO CLEAN ; FLOCKLESS VANE
With our original air current control mechanism, a flockless vane is
newly adapted.
The flockless vane prevents the condensation on the vane.
By changing the vane to the flockless type, the unit can be cleaned
much easier with mild household detergent.
B
Flockless vane
A
Air outlet
Protruding portion A
Sending the air to the upper
area of the vane
Prevents the air comes from
cntering from outside the unit
2. NEW MATERIALS FOR BETTER OIL RESISTANCE
We have changed the materials of grill, filer, fan and fan casing from ABS to P.P. (polypropylene) for better oil
resistance. As a result, oil crazing is cut in half.
3. SIMPLIFIED INSTALLATION WORK (DIRECT SUSPENDING METHOD)
Simplified the installation work by changing the suspending method to the direct suspending method (suspending
the unit directly from the suspension fixture).
In this way, the unit can be attached to the suspension fixture without removing the installation parts off (Only the
side cover is removed). This method is much simpler than the “One-time installation method”.
2
OC343A-1.qxp
06.8.2 11:31 AM
Page 3
4. IMPROVING EFFICIENCY OF PIPING WORK
1 Removed the knockout work by separating the piping
space from the air outlet for efficiency of the piping work.
Side panel
Back panel
U-cut
Rubber plug
Drain pan
G L
open
G
D
L
2 Improved the flexibility by making it possible for
drainage pipe to exit not only from the right side
back but also from the left side back.
Insulation cover
(attached)
open
Joint coupler
(attached)
Insulation
cover
D
L : Liquid pipe
G : Gas pipe
D : Drain pipe
w Knockout work is needed for the top part. When optional drain-up machine is installed, the refrigerant pipe
exits out from the top.
Drain pipe
(purchased locally)
Band
(attached)
w Please move the rubber plug for the unit to the right joint
when drainage pipe exits from the left side.
5. EASY MAINTENANCE FILTER ; NO MAINTENANCE NECESSARY FOR 2500 HOURS
The new long-life air filter can be used continuously 2500 hours without maintenance (at general office use).
3
OC343A-1.qxp
2
06.8.2 11:31 AM
Page 4
PART NAMES AND FUNCTIONS
● Indoor Unit
Left/right guide vanes
Change the direction of airflow
from the horizontal blower.
Air outlet
Long-life filter
Removes dust and foreigh matter from air coming in
through the grille (Recommended cleaning interval :
Approx, every 2,500 operating hours)
Air intake
Up/down guide vanes
Change the direction of airflow from the
vartical blower.
Intake grille
● Remote controller [PAR-21MAA]
● Once the controls are set, the same operation mode can be repeated
by simply pressing the ON/OFF button.
● Operation buttons
ON/OFF button
Set Temperature buttons
Down
Fan Speed button
Up
Timer Menu button
(Monitor/Set button)
Filter
button
(<Enter> button)
Mode button (Return button)
TEMP.
ON/OFF
Set Time buttons
Check button (Clear button)
Back
Ahead
Test Run button
MENU
BACK
MONITOR/SET
ON/OFF
FILTER
DAY
CHECK TEST
Airflow Up/Down button
Timer On/Off button
(Set Day button)
PAR-21MAA
OPERATION
CLOCK
CLEAR
Louver button
(
Operation button)
To preceding operation
number
Opening the
door
Ventilation button
(
Operation button)
To next operation number
4
OC343A-1.qxp
06.8.2 11:31 AM
Page 5
● Display
“Sensor” indication
Displayed when the remote controller
sensor is used.
Day-of-Week
For purposes of this explanation,
all parts of the display are shown
as lit. During actual operation, only
the relevant items will be lit.
Shows the current day of the week.
Time/Timer Display
“Locked” indicator
Shows the current time, unless the simple or Auto Off
timer is set.
If the simple or Auto Off timer is set, shows the time
remaining.
Indicates that remote controller buttons have been locked.
Identifies the current operation
“Clean The Filter” indicator
Shows the operating mode, etc.
* Multilanguage display is supported.
Comes on when it is time to clean the
filter.
TIME SUN MON TUE WED THU FRI SAT
TIMER
Hr
ON
AFTER
FUNCTION
FILTER
˚F˚C
“Centrally Controlled” indicator
Indicates that operation of the remote controller has been prohibited by a master controller.
Timer indicators
AFTER OFF
ERROR CODE
˚F˚C
The indicator comes on if the corresponding timer is set.
WEEKLY
SIMPLE
AUTO OFF
ONLY1Hr.
Fan Speed indicator
Shows the selected fan speed.
“Timer Is Off” indicator
Indicates that the timer is off.
Temperature Setting
Shows the target temperature.
Up/Down Air Direction indicator
Room Temperature display
Shows the room temperature.
The indicator
shows the direction of the outcoming airflow.
Louver display
“One Hour Only” indicator
Indicates the action of the swing
louver. Does not appear if the
louver is stationary.
Displayed if the airflow is set to
Low and downward during COOL
or DRY mode. (Operation varies
according to model.)
The indicator goes off after one
hour, at which time the airflow
direction also changes.
Ventilation indicator
Appears when the unit is running in
Ventilation mode.
(Power On indicator)
Indicates that the power is on.
Caution
● Only the Power on indicator lights when the unit is stopped and power supplied to the unit.
● If you press a button for a feature that is not installed at the indoor unit, the remote controller will display the “Not Available”
message.
If you are using the remote controller to operate multiple indoor units, this message will appear only if the feature is not
present at every unit connected.
● When power is turned ON for the first time, it is normal that “PLEASE WAIT” is displayed on the room temperature
indication (For max. 2minutes). Please wait until this “PLEASE WAIT” indication disappear then start the operation.
5
OC343A-1.qxp
3
06.8.2 11:31 AM
Page 6
SPECIFICATIONS
3-1. SPECIFICATIONS
Item
PCFY-P15NGMU-E
PCFY-P24NGMU-E
·
PCFY-P30NGMU-E
PCFY-P36NGMU-E
V Hz
Cooling capacity
Btu/h
15,000
24,000
30,000
36,000
Heating capacity
Electric characteristic
Power
Single phase 208/230V 60Hz
Btu/h
17,000
27,000
34,000
40,000
Cooling
kW
0.08
0.09
0.23
0.27
Heating
kW
0.08
0.09
0.23
0.27
Cooling
A
0.40
0.45
1.12
1.32
Heating
A
0.40
0.45
1.12
1.32
Input
Current
Exterior
(munsell symbol)
Unit : Munsell<0.70Y 8.59/0.97>
—
8-9/32
10-5/8
Height
in.
Dimensions Width
in.
Depth
in.
26-25/32
Heat exchanger
—
Cross fin(Aluminum plate fin and copper tube)
Fan ✕ No
F Air flow W2 DRY
a
WET
n
External
Sirocco fan ✕ 2
CFM
280-350-390-420
420-490-570-640
640-710-810-880
920-990-1120-1230
CFM
250-310-350-380
380-470-530-600
600-670-770-830
870-930-1050-1160
0.09
0.15
Air filter
—
Sirocco fan ✕ 4
Sirocco fan ✕ 3
Pa
kW
Pipe
dimensions
63-3/4
51-9/16
—
static pressure
Fan motor
output
Gas
side
Liquid
side
39-5/8
0
0.054
0.07
PP honey comb
in.
1/2"
5/8"
5/8" / 3/4"(compatible)
in.
1/4"
3/8"
3/8"
Unit drain pipe size
in.
Noise level W2
dB
29-33-36-38
32-34-37-39
36-38-41-43
37-39-42-44
Product weight
lb
60
75
82
95
Note 1.
W 2.
Rating conditions
Cooling : Indoor :
outdoor :
Heating : Indoor :
outdoor :
Air flow and the noise
1" I.D. (PVC pipe VP-20 connectable)
D.B. 80_F W.B. 67_F
D.B. 95_F W.B. 75_F
D.B. 70_F
D.B. 47_F W.B. 43_F
level are indicated as Low - Medium2 - Medium1 - High.
6
OC343A-1.qxp
06.8.2 11:31 AM
Page 7
3-2. ELECTRICAL PARTS SPECIFICATIONS
Model
Symbol
PCFY-P15NGMU-E
PCFY-P24NGMU-E
PCFY-P30NGMU-E
PCFY-P36NGMU-E
Parts name
Room temperature
thermistor
TH21
Resistance 30_F/15.8k", 50_F/9.6k", 70_F/6.0k", 80_F/4.8k", 90_F/3.9k", 100_F/3.2k"
Liquid pipe temperature
thermistor
TH22
Resistance 30_F/15.8k", 50_F/9.6k", 70_F/6.0k", 80_F/4.8k", 90_F/3.9k", 100_F/3.2k"
Gas pipe temperature
thermistor
TH23
Resistance 30_F/15.8k", 50_F/9.6k", 70_F/6.0k", 80_F/4.8k", 90_F/3.9k", 100_F/3.2k"
Fuse
(Indoor controller board)
FUSE
Fan motor
(with inner-thermostat)
MF
250V 6A
4-Pole Output 54W
D09B4P54MS
4-Pole Output 70W
D09C4P70MS
Inner-thermostat
3µF ✕ 440V
4-Pole Output 90W
D10C4P90MS
4-Pole Output 150W
D10D4P150MS
OFF 266˚F ±41˚F
4µF ✕ 440V
5µF ✕ 440V
7µF ✕ 440V
Fan motor capacitor
C1
Vane motor
MV
MP35EA
DC12V
MP42EA
DC12V
Linear expansion valve
LEV
DC12V Stepping motor drive
port [3.2 (0~2000pulse) EDM-40YGME
DC12V Stepping motor drive
port [5.2 (0~2000pulse) EDM-80YGME
Power supply
terminal block
TB2
(L1, L2, GR) 330V 30A
Transmission
terminal block
TB5
(M1, M2, S) 250V 20A
MA remote controller
terminal block
TB15
(1, 2) 250V 10A
7
OC343A-1.qxp
06.8.2 11:31 AM
Page 8
3-3. NOISE CRITERION CURVES
CEILING
1m
UNIT
1m
About 1.4m
MICROPHONE
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
NC-20
10
APPROXIMATE THRESHOLD OF HEARING
FOR CONTINUOUS NOISE
125
250
500 1000 2000 4000
BAND CENTER FREQUENCIES, Hz
PCFY-P30NGMU-E
NOTCH SPL(dB)
High
43
Medium1
41
38
Medium2
Low
36
PCFY-P24NGMU-E
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
LINE
90
63
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
NOTCH SPL(dB)
High
38
Medium1
36
33
Medium2
Low
29
LINE
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-20
10
63
125
250
500 1000 2000 4000
BAND CENTER FREQUENCIES, Hz
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
125
250
500 1000 2000 4000
BAND CENTER FREQUENCIES, Hz
NOTCH SPL(dB)
High
44
Medium1
42
39
Medium2
Low
37
8000
LINE
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-20
10
63
8
NC-20
10
PCFY-P36NGMU-E
8000
LINE
80
63
90
NOTCH SPL(dB)
High
39
Medium1
37
34
Medium2
Low
32
90
8000
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
PCFY-P15NGMU-E
125
250
500 1000 2000 4000
BAND CENTER FREQUENCIES, Hz
8000
2
1
2
3
4
5
6
7
8
9
7/16(11)
9-1/32(229)
2
4
3-11/16(86)
5-7/16(138)
6-3/4(171)
1
Air outlet
5-5/32(131)
Drainage pipe connection(1-1/32(26mm)I.D.)
Drainage pipe connection(for the left arrangement)
Knock out hole for left drain-piping arrangement
Refrigerant-pipe connection(gas pipe side/flared connection)
Refrigerant-pipe connection(liquid pipe side/flared connection)
Knock out hole for upper pipe arrangement
Knock out hole for left drain pipe arrangement
Knock out hole for wiring arrangement
Air intake
Knock out hole for fresh air intake
7
Electrical box
10-3/8(263)
5
11-13/16(300)
13-7/8(352)
2-3/4(70)
36-17/32(928)
1-3/4(45)
20-21/32(525)
Ceiling
3-1/8(79)
1-1/2(38)
1-1/2(38)
1-15/16(49)
2-7/16(62)
1/16(1)
6-7/8
(175)
1-13/16(46)
1-1/4(32)
7-1/16(179)
1-21/32(42)
1/4~9/32
(7~8)
6-11/32(161)
When electrical box
is pulled down
3
8
(Suspension bolt pitch)
2-3/4(70)
3-17/32(90)
or more
10-5/8(270)
5/8(16)
39-3/8(1000)
Ceiling
Rear wall
3-7/16(87)
liquid 1/4F([6.35)
gas 1/2F([12.7)
(Drainage)
or more
11-13/16(300)
Less than
9-13/16(230)
Allowing clearances
7-3/16(182)
7-15/16(201)
9-1/2(241)
NOTES.
1.Use M10 or W3/8 screw for anchor bolt.
2.Please be sure when installing the drain-up machine
(option parts),refrigerant pipe will be only
upper drain pipe arrangement.
INDOOR UNIT
PCFY-P15NGMU-E
36-5/32(918)
6-3/8(161)
39-5/8(1000)
35-19/32(904)
38-11/16(983)
36-23/32(933)
23/32(18)
5-29/32
(150)
5-1/2(140)
6
8-9/32(210)
26-25/32(680)
3-1/8(80)
12-5/8(320)
6-3/16(157)
9
Less than
(FRONT VIEW)
26-25/32(680)
Electrical box
3-25/32(96)
3-3/16(81)
10(254)
7-3/32(180)
2-7/32(56)
19-29/32(506)
9
or more
4
19-11/16(500)
06.8.2 11:31 AM
1/16(1)
(Gap to ceiling)
OC343A-1.qxp
Page 9
OUTLINES AND DIMENSIONS
Unit: in.(mm)
1/4~9/32
(6~7)
1-1/4(32)
6-11/32(161)
1
2
3
4
5
6
7
8
9
2-1/4(57)
7/16(11)
9
10-3/8(263)
2-3/4(70)
2
16-3/8(416)
11-13/16(300)
4
Air outlet
6-3/4(171)
5-7/16(138)
3-3/8(86)
1
5-5/32(131)
Drainage pipe connection(1-1/32(26mm)I.D.)
Drainage pipe connection(for the left arrangement)
Knock out hole for left drain-piping arrangement
Refrigerant-pipe connection(gas pipe side/flared connection)
Refrigerant-pipe connection(liquid pipe side/flared connection)
Knock out hole for upper pipe arrangement
Knock out hole for left drain pipe arrangement
Knock out hole for wiring arrangement
Air intake
Knock out hole for fresh air intake
7
Electrical box
48-5/8(1235)
8
9-1/32(229)
3-15/16(100)
Ceiling
20-21/32(525)
2-1/8(54)
3-1/8(79)
1-1/2(38)
1-1/2(38)
1/16(1)
6-7/8
(175)
1-13/16(46)
48-3/8(1228)
47-13/16(1214)
51-9/16(1310)
6-3/8(161)
(Suspension bolt pitch)
50-13/16(1290)
48-13/16(1240)
23/32(18)
5-29/32
(150)
5-1/2(140)
2-3/4(70)
8-9/32(210)
or more
10-5/8(270)
3-17/32(90)
3-1/8(80)
12-5/8(320)
6-3/16(157)
7-1/16(179)
1-21/32(42)
When electrical box
is pulled down
2
7-3/32(180)
2-7/32(56)
3
6
51-9/16(1310)
Ceiling
Rear wall
5/8(16)
3-7/16(87)
liquid 3/8F([9.52)
gas 5/8F([15.88)
(Drainage)
or more
11-13/16(300)
Less than
9-13/16(250)
Allowing clearances
7-3/16(182)
7/15/16(201)
9-1/2(241)
NOTES.
1.Use M10 or W3/8 screw for anchor bolt.
2.Please be sure when installing the drain-up machine
(option parts),refrigerant pipe will be only
upper drain pipe arrangement.
Less than
(FRONT VIEW)
5
26-25/32(680)
Electrical box
3-25/32(96)
2-3/16(81)
10(254)
10
19-29/32(506)
26-25/32(680)
PCFY-P24NGMU-E
1/16(1)
(Gap to ceiling)
06.8.2 11:31 AM
19-11/16(500)
OC343A-1.qxp
Page 10
Unit : in.(mm)
or more
1
2
3
4
5
6
7
8
9
6-5/16
Electrical box
9-1/32(229)
2-3/4(70)
2
13(330)
3-3/8(86)
4
Air outlet
6-3/4(171)
5-7/16(138)
1
7-9/16
1/4~9/32
(6~7)
Drainage pipe connection(1-1/32(26mm)I.D.)
Drainage pipe connection(for the left arrangement)
Knock out hole for left drain-piping arrangement
Refrigerant-pipe connection(gas pipe side/flared connection)
Refrigerant-pipe connection(liquid pipe side/flared connection)
Knock out hole for upper pipe arrangement
Knock out hole for left drain pipe arrangement
Knock out hole for wiring arrangement
Air intake
Knock out hole for fresh air intake
7
2-3/16(55)
7/16(11)
5-7/8(150)
48-5/8(1235)
8
10-3/8(263)
5-1/2(140)
27-1/16(687)
7-7/8(200)
1-1/2(38)
1-1/2(38)
1/16(1)
(196)
3-21/32(93)
(160)
20-21/32(525)
Ceiling
9
9-9/32(236)
1-25/32(45)
7-2/32(289)
1-21/32(42)
When electrical
box is pulled
down
3
2
23/32(18)
5-29/32(150)
48-3/8(1228)
51-9/16(1310)
47-13/16(1214)
6-3/8(160)
(Suspension bolt pitch)
50-13/16(1290)
48-13/16(1240)
5-1/2(140)
2-3/4(70)
or more
10-5/8(270)
3-1/8(80)
12-5/8(320)
5/8(16)
3-7/16(87)
51-9/16(1310)
Ceiling
Rear wall
9-5/8(245)
7-13/16(198)
7-3/16(182)
5/8F([15.88)
(300)
or more
11-13/16
Less than
9-13/16(250)
Allowing clearances
(Drainage)
gas
liquid 3/8F([9.52)
NOTES.
1.Use M10 or W3/8 screw for anchor bolt.
2.Please be sure when installing the drain-up machine
(option parts),refrigerant pipe will be only
upper drain pipe arrangement.
PCFY-P30NGMU-E
3-17/32(90)
6
(56)
3-25/32(96)
3-3/16(81)
10(254)
8-5/32(207)
2-7/32
19-29/32(506)
10-5/8(270)
26-25/32(680)
5
8-17/32(217)
(FRONT VIEW)
26-25/32(680)
Electrical box
Less than
11
19-11/16(500)
06.8.2 11:31 AM
1/16(1)
(Gap to ceiling)
OC343A-1.qxp
Page 11
Unit: in.(mm)
7-1/16(239)
1-21/32(42)
3-21/32(93)
1/4~9/32(6~7)
1
2
3
4
5
6
7
8
9
7
2-3/4(70)
9-1/32(229)
2
Electrical box
27-1/16(687)
7-7/8(200)
5-1/2(140)
Air outlet
13(330)
10-3/8(263)
3-3/8(86)
5-7/16(138)
6-3/4(171)
4
Drainage pipe connection(1-1/32(26mm)I.D.)
Drainage pipe connection(for the left arrangement)
Knock out hole for left drain-piping arrangement
Refrigerant-pipe connection(gas pipe side/flared connection)
Refrigerant-pipe connection(liquid pipe side/flared connection)
Knock out hole for upper pipe arrangement
Knock out hole for left drain pipe arrangement
Knock out hole for wiring arrangement
Knock out hole for fresh air intake
Air intake
When electrical box
is pulled down
6-5/16(160)
1-1/2(38)
1-1/2(38)
7-9/16(192)
1/16(1)
9-9/32(236)
1-25/32(45)
2-3/16(55)
7/16(11)
5-7/8(150)
60-13/16(1545)
20-21/32(525)
Ceiling
23/32(18)
5-29/32(150)
60-7/16(1535)
63-3/4(1620)
6-3/8(161)
(Suspension bolt pitch)
60(1524)
60-29/32(1547)
5-1/2(140)
2-3/4(70)
8-5/32(207)
2-7/32(56)
2 3
or more
10-5/8(270)
3-17/32(90)
3-1/8(80)
12-5/8(320)
5/8(16)
3-7/16(87)
PCFY-P36NGMU-E
63-3/8(1620)
Ceiling
Rear wall
9-5/8(245)
7-13/16(198)
7-3/16(182)
RG01N982
or more
11-13/16(300)
Less than
9-13/16(250)
Allowing clearances
liquid 3/8F([9.52)
gas 5/8F/3/4F(Compatible)
([15.88/[19.05)
(Drainage)
NOTES.
1.Use M10 or W3/8 screw for anchor bolt.
2.Please be sure when installing the drain-up machine
(option parts),refrigerant pipe will be only
upper drain pipe arrangement.
Less than
1
3-25/32(96)
3-3/16(81)
10(254)
10-5/8(270)
26-25/32(680)
8 5
8-17/32(217)
9
6
26-25/32(680)
(FRONT VIEW)
or more
Electrical box
19-11/16(500)
12
19-29/32(506)
PCFY-P36NGMU-E
(Gap to ceiling)
06.8.2 11:31 AM
1/16(1)
OC343A-1.qxp
Page 12
Unit : in.(mm)
OC343A-1.qxp
06.8.2 11:31 AM
5
Page 13
WIRING DIAGRAM
PCFY-P15NGMU-E PCFY-P24NGMU-E PCFY-P30NGMU-E PCFY-P36NGMU-E
Legend
Symbol
I. B
CN24
Name
Indoor controller board
Connector
Heater
Symbol
P. B
Name
INDOOR POWER BOARD
C1
Capacitor (fan motor)
Symbol
A. B
SW1
Name
Circuit board Address
Switch
Mode selection
CN32
Remote switch
LEV
Linear expansion valve
SW5
Voltage selection
CN51
Centrally control
MF
Fan motor (with inner thermo)
SW11
Address setting 1st digit
CN52
Remote indication
MV
Vane motor
SW12
Address setting 2nd digit
CNP
Drain-up machine
TH21
Thermistor
F.C
Fan phase control
FUSE
FUSE (6A/250V)
SW2
Switch
TH22
Capacity code
SW3
Mode selection
SW4
Model selection
Aux.Relay
X1
X4
SW14
(32°F/15k", 77°F/5.4k")
SWA
Ceiling height Selector
Pipe temp, detection/Iiguid
SWC
Option Selector
Connection No.
(32°F/15k", 77°F/5.4k")
TH23
Pipe temp, detection/Gas
(32°F/15k", 77°F/5.4k")
Drain-up machine
TB2
Terminal
Fan motor
TB5
block
Varistor
ZNR
Room temp, detection
Power supply
Transmission
TB15
MA-remote controller
TO NEXT INDDOR UNIT
w2
RED
BLU
TB2
GRN/YLW
P.B
MF
1 3 5
BLK
WHT
(RED)
LED1
X1
X4
(GRN)
VANE
CN6V
1 3 CNDK
(WHT)
DRAIN
CN31
ZNR
6 5 4 3 2 1
BREAKER
(15A)
FUSE
250V
6A
X4
X1
(RED)
ADDRESS
CN81
(RED)
ADDRESS
CN42
3 2 1
(GRN)
(WHT)
REMOTE CENTRALLY
INDICATION CONTROL
CN52
CN51
5
15
1 6 5
SW2
(WHT)
LEV
CN60
4 3 2 1
SW3
SW4
ON
8 7 6 5 4 3 2 1 4 3 2 1 OFF
123456 12345678910
12345
(WHT)
REMOTO
SWITCH
CN32
1
3
CN2D 1
(WHT) 2
CN2M 1
(BLU)
M-NET 2
1
CN3A 2
(BLU)
3
(RED) (WHT) (BLK)
INTAKE LIQUID GAS
ON CN20 CN21 CN29
OFF
2 1 2 1 2 1 LED2
6
2 1
8
See fig:w1
MV
2 1
POWER SUPPLY
~/N 208-230V 60Hz
BLK
WHT
BLU
BLU
ORN
ORN
TB5 S(SHIELD)
TO OUTDOOR UNIT
M2
BC CONTROLLER
M1
REMOTE CONTROLLER
DC24-30V
TB15
1
TO MA-REMOTE
CONTROLLER
2
DC8.7-13V
MODEL
PCFY-P30NGMU-E
(GRN)
VAHE
CN6V
6 5 4 3 2 1
MODEL
PCFY-P36NGMU-E
(GRN)
VAHE
CN6V
A.B
6 5 4 3 2 1
SWA (RED)
ADDRESS 3
3
CN43 2
2
1
1
ON
(RED)
OFF
12345678910
ADDRESS
SW12 SW11 SWC SW14 CN82
0
0 2
0
208V
6
TH21 TH22
TH23
5
6 5 4 3 2 1
6 5 4 3 2 1
MV
MV
<w 1>
3RD 2ND 1ST 1
DIGIT DIGIT DIGIT
Models
SW2
PCFY-P15NGMU-E
ON
OFF
PCFY-P24NGMU-E
ON
OFF
PCFY-P30NGMU-E
ON
OFF
CONNECTION
NO.
SW3
ON
OFF
123456
1 2 3 4 5 6 7 8 910
123456
ON
OFF
123456
PCFY-P36NGMU-E
1 2 3 4 5 6 7 8 910
ON
OFF
123456
LED on indoor board for service
Meaning
Mark
Function
Main power supply(Indoor unit:208-230V)
LED1 Main power supply
power on➝Iamp is Iit
Power supply for MA-Remote controller
Power supply for
LED2 MA-Remote controller on➝Iamp is lit
< w 2> Use Copper Supply Wire.
13
230V
SW1
LEV
Note
1.At servicing for outdoor unit, always follow the wiring diagram of outdoor unit.
2.In case of using MA-Remote controller, please connect to TB15.
(Remote controller wire is non-polar.)
3.In case of using M-NET, please connect to TB5. (Transmission line is non-polar.)
4.Symbol [S] of TB5 is the shield wire connection.
5.Symbols used in wiring diagram above are,
: terminal block,
: connector.
6.The setting of the SW2/SW3 dip switches differs in the capacity.
For the detail, refer to the fig:w 1.
7.Please set the switch SW5 according to the power supply voltage.
Set SW5 to 230V side when the power supply is 230 volts.
When the power supply is 208 volts, set SW5 to 208V side.
4
SW5
6 5 4 3 2 1
BRN
RED
ORN
YLW
WHT
BLU
6 5 4 3 2 1
4
BRN
RED
BLU
ORN
YLW
WHT
6
FUSE(15A)
2
1
RED
ORN
YLW
WHT
BLU
CNP 1 3
(BLU)
TRANS
PULL BOX
BRN
RED
ORN
YLW
WHT
BLU
CND 1 3
(RED)
F.C
(YLW)
HEATER
CN24
RED
BLU
FAN 1 3 5
(WHT)
DC13.1V
(WHT)
CN2S
3
2
1
RED
WHT
BLK
C1
I.B
AC208-230V
(RED)
CNSK
L1
L2
GR
8
7
6
5
4
3
2
1
OC343A-1.qxp
6
06.8.2 11:31 AM
Page 14
REFRIGERANT SYSTEM DIAGRAM
PCFY-P15NGMU-E
PCFY-P24NGMU-E
PCFY-P30NGMU-E
PCFY-P36NGMU-E
Gas pipe temperature
thermistor TH23
Strainer (#100mesh)
Gas pipe
Liquid pipe temperature
thermistor TH22
Flare connection
Liquid pipe
Heat exchanger
Linear expansion valve
Strainer (# 50mesh)
Strainer (#100mesh)
Room temperature thermistor TH21
Unit : mm(in.)
Model
PCFY-P15NGMU-E
PCFYP24/P30NGMU-E
Gas pipe
{12.7(1/2”)
{15.88(5/8”)
Liquid pipe
{6.35(1/4”)
{9.52(3/8”)
Item
14
PCFY-P36NGMU-E
{15.88(5/8”)/{19.05(3/4”)
(compatible)
{9.52(3/8”)
OC343A-1.qxp
06.8.2 11:31 AM
7
Page 15
MICROPROCESSOR CONTROL
INDOOR UNIT CONTROL
7-1. COOL OPERATION
TIME SUN MON TUE WED THU FRI SAT
TIMER
Hr
ON
AFTER
AFTER OFF
ERROR CODE
FUNCTION
FILTER
˚F˚C
˚F˚C
WEEKLY
SIMPLE
AUTO OFF
ONLY1Hr.
TEMP.
MENU
BACK
PAR-21MAA
MONITOR/SET
ON/OFF
ON/OFF
CHECK TEST
OPERATION
CLEAR
Control modes
1. Thermoregulating
function
button is
FILTER
DAY
CLOCK
<How to operate>
1 Press POWER ON/OFF button.
2 Press the operation MODE button to display COOL.
3 Press the TEMP. button to set the desired temperature.
NOTE: The set temperature changes 2°F when the
or
pressed one time Cooling 67 to 87°F.
Control details
Remarks
1-1. Thermoregulating function (Function to prevent restarting for 3 minutes)
• Room temperature ] desired temperature + 2°F ···Thermo ON
• Room temperature [ desired temperature ···Thermo OFF
1-2. Frozen prevention control
Detected condition : When the liquid pipe temp. (TH22) is 32°F or less in 16
minutes from compressor start up, anti-freezing control
starts and the thermo OFF.
Released condition : The timer which prevents reactivating is set for 3 minutes,
and anti- freezing control is cancelled when any one of the
following conditions is satisfied.
1 Liquid pipe temp. (TH22) turns to be 50°F or above.
2 The condition of the thermo OFF become complete
by thermoregulating, etc.
3 The operation modes become mode other than COOL.
4 The operation stops.
2. Fan
By the remote controller setting (switch of 4 speeds)
Type
Fan speed notch
4 speeds
[Low], [Med2], [Med1], [High]
To be continued to the next page
15
OC343A-1.qxp
06.8.2 11:31 AM
Page 16
From the preceding page
Control modes
3. Drain pump
Remarks
Control details
Drain pump control
•Always drain pump ON during the COOL and DRY mode operation
(Regardless of the thermo ON/ OFF)
•When the operation mode has changed from the COOL or DRY to the others
(including Stop), OFF the control after the drain pump ON for 3 minutes.
Drain sensor function
• Energize drain sensor at a fixed voltage for a fixed duration. After energizing,
compare the drain sensor’s temperature to the one before energizing, and judge
whether the sensor is in the air or in the water.
· Drain sensor
Indoor control
p.c. board
CN31 1
2
3
→
Basic control system
• While drain pump is turned on, repeat the following control system and judge
whether the sensor is in the air or in the water.
Timing of
energizing
drain sensor
ON
·······Repeat
OFF
Stand by for
a minute
30
sec.
Stand by for
a minute
30
sec.
Detect the
temperature
before
energizing
(T0)
Detect the
temperature
after
energizing
(T1)
Judge whether
the sensor is in
the air or in the
water.
•Drain sensor temperature rise (∆t)
•Temperature of drain sensor before current is applied (T0)
•Temperature of drain sensor after current is applied (T1)
[ ∆t = T1 – T0 ]
(1) Initial setting : Start at COOL mode and horizontal vane position.
(up/ down vane change) (2) Vane position : Horizontal →Downward A →Downward B →Downward C→Swing
→
4. Vane
(3) Restriction of the downward vane setting
When setting the downward vane A, B or C in [Med1], [Med2] or [Low] of the fan
speed notch, the vane changes to horizontal position after 1 hour.
16
· "SET FOR 1 HOUR"
appears on the
wired remote
controller.
OC343A-1.qxp
06.8.2 11:31 AM
Page 17
7-2. DRY OPERATION
<How to operate>
1 Press POWER ON/OFF button.
2 Press the operation MODE button to display DRY.
3 Press the TEMP. button to set the desired temperature.
NOTE: The set temperature changes 2°F when the
or
pressed one time. Dry 67 to 87°F.
TIME SUN MON TUE WED THU FRI SAT
TIMER
Hr
ON
AFTER
AFTER OFF
ERROR CODE
FUNCTION
FILTER
˚F˚C
˚F˚C
WEEKLY
SIMPLE
AUTO OFF
ONLY1Hr.
TEMP.
MENU
BACK
PAR-21MAA
MONITOR/SET
ON/OFF
ON/OFF
FILTER
DAY
CLOCK
CHECK TEST
OPERATION
CLEAR
Control modes
1. Thermoregulating
function
1-1. Thermoregulating function (Function to prevent restarting for 3 minutes)
Setting the Dry thermo by the thermoregulating signal and the
room temperature (TH1).
Dry thermo ON Room temperature ] desired temperature + 2°F
Dry thermo OFF Room temperature [ desired temperature
Dry thermo Dry thermo
ON
OFF
Thermoregulating signal Room temperature (T1) time (min) time (min)
3 min. passed since starting operation
ON
Over 64°F
OFF
T1 ] 83°F
9
3
83°F > T1 ] 79°F
7
3
79°F > T1 ] 75°F
5
75°F > T1
3
3
3
3
10
Unconditional
Dry thermo OFF
Less than 64°F
1-2. Frozen prevention control
No control function
Indoor fan speed depends on the compressor conditions.
Dry thermo
Fan speed notch
ON
[Low]
OFF
Stop
Note: Remote controller setting is not acceptable.
3. Drain pump
Remarks
Control details
Room
temperature
2. Fan
button is
Same control as COOL operation
4. Vane
Same control as COOL operation
(up/ down vane change)
17
OC343A-1.qxp
06.8.2 11:31 AM
Page 18
7-3. FAN OPERATION
<How to operate>
1 Press POWER ON/OFF button.
2 Press the operation MODE button to display FAN.
TIME SUN MON TUE WED THU FRI SAT
TIMER
Hr
ON
AFTER
AFTER OFF
ERROR CODE
FUNCTION
FILTER
˚F˚C
˚F˚C
WEEKLY
SIMPLE
AUTO OFF
ONLY1Hr.
TEMP.
MENU
BACK
PAR-21MAA
MONITOR/SET
ON/OFF
ON/OFF
FILTER
DAY
CLOCK
CHECK TEST
OPERATION
CLEAR
Control modes
1. Fan
2. Drain pump
Control details
Set by remote controller.
Type
Fan speed notch
4 speeds
[Low], [Med2], [Med1], [High]
2-1. Drain pump control
The drain pump turns ON for the specified amount of time when any of the following
conditions is satisfied:
1 ON for 3 minutes after the operation mode is switched from COOL or DRY to
another operation mode (FAN).
2 ON for 6 minutes after the drain sensor is determined to be submerged using the
liquid level detection method given below.
3 ON for 6 minutes after indoor piping (liquid piping) temperature – indoor intake
temperature [ -18°F, AND the drain sensor input is at the short or open level.
(If condition 2 or 3 is still being met after the drain pump has been turned ON for 6
minutes, the drain pump is kept ON for a further 6 minutes.)
2-2. Liquid level detection method
The liquid level is detected by determining whether or not the drain sensor is
submerged, based on the temperature rise after self-heating the sensor. This
process is performed if any of the following conditions is satisfied:
1 Drain pump is ON.
2 Indoor piping (liquid piping) temperature – indoor intake temperature [ -18°F
3 Indoor piping (liquid piping) temperature or indoor intake temperature is at the
short or open level temperature.
4 Every hour after the drain pump is switched from ON to OFF.
Same as the control performed during the COOL operation, but with no restriction
3. Vane
(up/ down vane change) on the vane's downward blow setting
18
Remarks
OC343A-1.qxp
06.8.2 11:31 AM
Page 19
7-4. HEAT OPERATION
<How to operate>
1 Press POWER ON/OFF button.
2 Press the operation MODE button to display HEAT.
3 Press the TEMP. button to set the desired temperature.
NOTE: The set temperature changes 2°F when the
or
pressed one time. Heating 63 to 83°F.
TIME SUN MON TUE WED THU FRI SAT
TIMER
Hr
ON
AFTER
AFTER OFF
ERROR CODE
FUNCTION
FILTER
˚F˚C
˚F˚C
WEEKLY
SIMPLE
AUTO OFF
ONLY1Hr.
TEMP.
MENU
BACK
PAR-21MAA
MONITOR/SET
ON/OFF
ON/OFF
CLOCK
<Display in HEAT operation>
[DEFROST]
The [DEFROST] symbol is only displayed during the defrost operation.
[STANDBY]
The [STANDBY] symbol is only displayed from the time the heating operation
starts unit the heated air begins to blow.
FILTER
DAY
CHECK TEST
OPERATION
button is
CLEAR
Control modes
Control details
Remarks
1. Thermoregulating 1-1. Thermoregulating function (Function to prevent restarting for
3 minutes)
function
• Room temperature [ desired temperature -2°F ···Thermo ON
• Room temperature ] desired temperature ···Thermo OFF
2. Fan
Controlled by the remote controller (4-speed)
Priority is given to below-mentioned controlled mode
2-1. Hot adjuster mode
2-2. Preheating exclusion mode
2-3. Thermo OFF mode (When the compressor off by the
thermoregulating)
2-4. Cool air prevention mode (Defrosting mode)
2-5. Capacity increasing mode
2-1. Hot adjuster mode
The fan controller becomes the hot adjuster mode for the
following conditions.
1 When starting the HEAT operation
2 When the thermoregulating function changes from OFF to ON.
3 When releasing the HEAT defrosting operation
Hot adjuster mode ✻1
Set fan speed by the remote controller
✻1 "STAND BY" will be displayed
during the hot adjuster mode.
[Low]
[Extra Low]
A
B
C
A: HOT adjuster mode start
B: 5 min after the condition A or the indoor
liquid pipe temperature turned 95°F or more
C: 2 min after the condition A
(Terminating the hot adjuster mode)
2-2. Preheating exclusion mode
When the condition changes, the auxiliary heater ON to OFF
(thermoregulating or operation stop, etc), the indoor fan
operates in [Low] mode for 1 minute.
· This control is same for the model
without auxiliary heater.
To be continued to the next page.
19
OC343A-1.qxp
06.8.2 11:31 AM
Page 20
From the preceding page
Control details
Control modes
2. Fan
Remarks
2-3. Thermo OFF mode
When the thermoregulating function changes to OFF, the
indoor fan operates in [Extra low].
2-4. Heat defrosting mode
The indoor fan stops.
3. Drain pump
No drain pump operation
However, when the control changes from COOL or DRY
operation, the drain pump operates for 3 minutes.
→
4. Vane control (1) Initial setting : OFF → HEAT···[last setting]
When changing the mode from exception of HEAT
(Up/ down vane
to HEAT operation. ···[Downward C]
change)
(2) Vane position :
Horizontal →Downward A →Downward B →Downward C→Swing
(3) Restriction of vane position
The vane is horizontally fixed for the following modes.
(The control by the remote controller is temporally invalidated
and it is controlled by the unit.)
•Thermo OFF
•Hot adjuster [Extra low] mode
•Heat defrost mode
20
OC343A-1.qxp
06.8.2 11:31 AM
Page 21
7-5. AUTO OPERATION [AUTOMATIC COOL/HEAT CHANGE OVER OPERATION]
TIME SUN MON TUE WED THU FRI SAT
TIMER
Hr
ON
AFTER
AFTER OFF
ERROR CODE
˚F˚C
˚F˚C
TEMP.
MENU
BACK
PAR-21MAA
MONITOR/SET
FUNCTION
FILTER
WEEKLY
SIMPLE
AUTO OFF
ONLY1Hr.
ON/OFF
ON/OFF
FILTER
DAY
CLOCK
CHECK TEST
OPERATION
<How to operate>
1 Press POWER ON/OFF button.
2 Press the operation MODE button to display AUTO.
3 Press the TEMP. button to set the desired temperature.
NOTE: The set temperature changes 2°F when the
or
button is
pressed one time. Automatic 67 to 83°F.
“AUTO” works to change by itself the operation mode either to cooling
or heating to the room temperature.
CLEAR
Control details
Control modes
Remarks
1. Initial value of HEAT mode for room temperature < Desired temperature
operation mode COOL mode for room temperature ] Desired temperature
2. Mode change (1) HEAT mode → COOL mode
Room temperature ] Desired temperature + 3°F. or 3 min. has passed
(2) COOL mode → HEAT mode
Room temperature [ Desired temperature - 3°F. or 3 min. has passed
3. COOL mode
Same control as cool operation
4. HEAT mode
Same control as heat operation
7-6. WHEN UNIT IS STOPPED
Control modes
Control details
1. Drain pump
1-1. Drain pump control
The drain pump turns ON for the specified amount of time when any of the following
conditions is satisfied (regardless of whether the compressor is ON or OFF)
1 ON for 3 minutes after the operation mode is switched from COOL or DRY to another
operation mode (HEAT mode).
2 ON for 6 minutes after the drain sensor is determined to be submerged using the
liquid level detection method given below.
3 ON for 6 minutes after indoor piping (liquid piping) temperature – indoor intake
temperature [ 14°F, AND the drain sensor input is at the short or open level.
(If condition 2 or 3 is still being met after the drain pump has been turned ON for 6
minutes, the drain pump is kept ON for a further 6 minutes.)
1-2. Liquid level detection method
The liquid level is detected by determining whether or not the drain sensor is
submerged, based on the amount the temperature rises after self-heating the sensor.
This process is performed if any of the following conditions is satisfied:
1 Drain pump is ON.
2 Indoor piping (liquid piping) temperature – indoor intake temperature [14°F
(except during defrosting)
3 Indoor piping (liquid piping) temperature or indoor intake temperature is at the short
or open level temperature.
4 Every hour after the drain pump is switched from ON to OFF.
21
Remarks
OC343A-1.qxp
06.8.2 11:31 AM
8
Page 22
TROUBLE SHOOTING
8-1. HOW TO CHECK THE PARTS
PCFY-P15NGMU-E PCFY-P24NGMU-E PCFY-P30NGMU-E PCFY-P36NGMU-E
Parts name
Check points
Room temperature
thermistor
(TH21)
Liquid pipe temperature
thermistor
(TH22)
Gas pipe temperature
thermistor
(TH23)
Fan motor (MF)
Disconnect the connector then measure the resistance using a tester.
(Surrounding temperature 50°F~86°F)
Normal
Abnormal
4.3k"~9.6k"
Open or short
Measure the resistance between the terminals using a tester.
Relay connector
1
3
5
Refer to the next page for the details.
Red
1
White
3
Black
5
Motor terminal
or
Relay connector
Normal
Abnormal
PCFYP15NGMU-E P24NGMU-E P30NGMU-E P36NGMU-E
Red-Black
70.6"
45.0"
41.1"
20.4"
White-Black
69.6"
44.8"
54.3"
20.7"
Open or short
Protector
Linear expansion
Blue
valve (LEV)
Disconnect the connector then measure the resistance valve using a tester.
Brown
M
Yellow
Normal
White-Red
Yellow-Brown Orange-Red
Blue-Brown
Open or short
150k" i10%
White Red Orange
Vane motor (MV)
Orange
Red
Abnormal
M
Measure the resistance between the terminals using a tester.
(Surrounding temperature 68°F~86°F)
Connector
Pink
Normal
PCFY-P15NGMU-E PCFY-P24NGMU-E
Abnormal
Brown — Yellow
Yellow Brown Blue
Brown — Blue
Red — Orange
186~214"
140~160"
Open or short
Red — Pink
Pink
M
Orange
Connector
Normal
PCFY-P30NGMU-E, PCFY-P36NGMU-E
Abnormal
Red — Blue
Red
Yellow
Blue
Red — Yellow
Red — Pink
140~160"
Red — Orange
22
Open or short
Refer to the next
page for the details.
OC343A-1.qxp
06.8.2 11:31 AM
Page 23
<Thermistor characteristic graph>
Thermistor <Room temperature detection> (TH21)
Thermistor for
lower temperature Thermistor <Liquid pipe temperature detection> (TH22)
Thermistor <Gas pipe temperature detection> (TH23)
Thermistor R0=15k' ± 3%
Fixed number of B=3480K ± 2%
< Thermistor for lower temperature >
50
Rt=15exp { 3480(
1
)}
273
15.8k'
9.6k'
6.0k'
4.8k'
3.9k'
3.2k'
40
Resistance (K")
30_F
50_F
70_F
80_F
90_F
100_F
1
273+(t-32)/1.8
30
20
10
0
-20
0
20
40
60
80
Temperature (°F)
100
120
Linear expansion valve
1 Operation summary of the linear expansion valve
• Linear expansion valve open/close through stepping motor after receiving the pulse signal from the indoor controller board.
• Valve opening can be changed in proportion to the number of pulse signal.
<Connection between the indoor controller board and the linear expansion valve>
Controller board
Relay connector
Linear expansion valve
4
M
6
5
2
1
White Red
3
Orange
Blue
Brown
Yellow
DC12V
2
Brown
6
5
Red
5
[4
Drive circuit
[4
1
Blue
4
[3
3
Orange
3
[3
[2
4
Yellow
2
[2
[1
6
White
1
[1
Connector(CN60)
Note : Since the number of the connector at the controller board side and the relay connector are different, follow the color of
the lead wire.
23
OC343A-1.qxp
06.8.2 11:31 AM
Page 24
<Output pulse signal and the valve operation>
Output
(Phase)
Closing a valve : 1 → 2 → 3 → 4 → 1
Opening a valve : 4 → 3 → 2 → 1 → 4
The output pulse shift as above order.
Output
number
1
2
3
4
{1
ON
OFF
OFF
ON
{2
ON
ON
OFF
OFF
{3
OFF
ON
ON
OFF
{4
OFF
OFF
ON
ON
❈ 1. When linear expansion valve operation stops, all output phase
become OFF.
2. At phase interruption or when phase does not shift in order, the
motor does not rotate smoothly and motor will lock and vibrate.
2 Linear expansion valve operation
C
D
Close
Open
2000 pulse
Open the valve
all the way
A
E
B
❈ When the switch is turned on, 2200 pulse closing valve signal
will be send till it goes to A point in order to define the valve
position.
When the valve move smoothly, there is no noise or vibration
occur from the linear expansion valve : however, when the pulse
number moves from E to A or when the valve is locked, more
noise can be heard than normal situation.
❈ Noise can be detected by placing the ear against the screw driver handle while putting the screw driver to the linear expansion
valve.
Pulse number
Extra tightning (80~100pulse)
3 Trouble shooting
Check points
Symptom
Countermeasures
Operation circuit fail- Disconnect the connector on the controller board, then con- Exchange the indoor conure of the micro
nect LED for checking.
troller board at drive circuit
processor
failure.
6
5
4
3
2
1
1T LED
Pulse signal will be sent out for 10 seconds as soon as the
main switch is turn on. If there is LED with lights on or lights
off, it means the operation circuit is abnormal.
Linear expansion
valve mechanism is
locked
Motor will idle and make ticking noise when motor is operated Exchange the linear
while the linear expansion valve is locked. This ticking sound expansion valve.
is the sign of the abnormality.
Short or breakage of Measure the resistance between the each coil (red-white,
the motor coil of the red-orange, brown-yellow, brown-blue) using a tester. It is
linear expansion
normal if the resistance is in the range of 150"I10%
valve
Exchange the linear
expansion valve.
Valve doesn't close To check the linear expansion valve, operate the indoor unit If large amount of thermiscompletely (thermis- in fan mode and at the same time operate other indoor units tor is leaked, exchange the
linear expansion valve.
tor leaking).
in cooling mode, then check the pipe temperature <liquid
pipe temperature> of the indoor unit by the
outdoor multi controller board operation
monitor. During fan operation, linear
expansion valve is closed completely and if
Thermistor
(Liquid pipe) there are some leakage, detecting temperLinear
ature of the thermistor will go lower. If the
expansion
detected temperature is much lower than
valve
the temperature indicated in the remote
controller, it means the valve is not closed all the way. It is
not necessary to exchange the linear expansion valve, if the
leakage is small and not making any trouble.
Wrong connection of Check the color of lead wire and missing terminal of the con- Disconnect the connector
at the controller board,
the connector or
nector.
then check the continuity.
contact failure
24
OC343A-1.qxp
06.8.2 11:31 AM
Page 25
8-2. FUNCTION OF DIP SWITCH
PCFY-P15NGMU-E PCFY-P24NGMU-E PCFY-P30NGMU-E PCFY-P36NGMU-E
Operation by switch
Switch Pole
Function
Remarks
ON
OFF
1
Room temperature thermistor
position
Built-in remote controller
Indoor unit
2
Filter clogging detection
Provided
Not provided
Address board
<At delivery>
ON
OFF
3
Filter cleaning sign
2500hr
100hr
4
Air intake
Effective
Not effective
Remote indication switching
Thermostat ON signal indication Fan output indication
1 2 3 4 5 6 7 8 9 10
SW1 5
Mode 6
Selection
7
Humidifier control
Always operated while the heating mode w1 Operation depends on the condition
Air flow set in case of
Fix to LOW
w3
Fix to EXTRA LOW
8
heat thermostat OFF
Depends on setting remote controller
w3
Depends on SW1-7
9
Auto reset function
Effective
Not effective
Power resource ON/OFF
Effective
Not effective
10
w2
w3
NOTE:
w1 At Heating mode, fan
operating.
w2 At Heater mode, operating
heat thermostat ON.
w3 SW1-7=OFF, SW1-8=ON
→Setting air flow.
SW1-7=ON, SW1-8=ON
→Indoor fan stop.
Indoor controller board
Set while the unit is off.
Model name
SW2
Capacity
1~6
code
setting
SW2
PCFYP15NGMU-E
ON
OFF
PCFYP36NGMU-E
ON
OFF
1 2 3 4 5 6
Model name
PCFYP24NGMU-E
SW2
ON
OFF
1 2 3 4 5 6
Model name
PCFYP30NGMU-E
SW2
Heat pump/Cool only
Cooling only
Heat pump
2
Louver
Available
Not available
3
Vane
Available
Not available
4
SW3 5
Function
Selection 6
7
Vane swing function
Available
Not available
Vane horizontal angle
Second setting
First setting
Set for each capacity.
Indoor controller board
Set while the unit is off.
<At delivery>
ON
OFF
1 2 3 4 5 6 7 8 9 10
Vane cooling limit angle setting w4 Horizontal angle
Down B,C
Indoor linear expansion
valve opening
Effective
Not effective
8
Heater 4 degrees up
Not effective
Effective
9
Target Superheat setting w5 9 degrees
6 degrees
Target Subcool setting
10 degrees
SW4
Unit 1~4
Selection
1 2 3 4 5 6
1 2 3 4 5 6
1
10
<At delivery>
ON
OFF
15 degrees
NOTE:
w4 At cooling mode, each
angle can be used only 1
hour.
w5 SW3-9 setting
P15 = ON
P24/P30/P36 = OFF
Indoor controller board
Set while the unit is off.
ON
OFF
<At delivery>
1 2 3 4 5
ON
OFF
1 2 3 4 5
25
OC343A-1.qxp
06.8.2 11:31 AM
Page 26
Switch
Operation by switch
❈ Ceiling height can be changed depends on
SW A setting.
SWA
Set the
ceiling
height
(High)
1~3
3
Remarks
Address board
<At delivery>
3
2
1
(Standard) 2
(Low)
1
Address board
2
When the optional high performance filter elements (filter casement) is attached to the unit,
be sure to set switch to the option side in
order to prevent the airflow reducing.
Option
(Standard)
90 1
78
SW11
90 1
23
45 6
1
SW12
23
10
remote controller is being used.
78
78
78
90 1
23
Rotary switch
SW11
90 1
Address can be set while the
unit is stopped.
Address setting should be done when M-NET
<At delivery>
45 6
SW12
23
SW12
2nd digit
address
setting
Option
Address board
45 6
SW11
1st digit
address
setting
<At delivery>
45 6
SWC
Option
45 6
CDE
AB
<At delivery>
SW14
F01
23
This is the switch to be used when the indoor
unit is operated with R2 series outdoor unit
as a set.
F01
45 6
CDE
AB
SW14
23
789
789
SW14
Connection
No. setting
Rotary switch
Address board
Address board
SW5
Voltage
selection
2
220V
(208V)
240V
(230V)
If the unit is used at the 230V area, set the
voltage to 230V.
If the unit is used at the 208V, set the voltage
to 208V.
26
<At delivery>
220V
(208V)
240V
(230V)
OC343A-1.qxp
06.8.2 11:31 AM
Page 27
8-3. TEST POINT DIAGRAM
8-3-1. Indoor controller board
PCFY-P15NGMU-E PCFY-P24NGMU-E
PCFY-P30NGMU-E PCFY-P36NGMU-E
CN2D
Connect to the indoor
power board (CN2S)
1 (+))
12.5-13.7V DC (Pin1
CN2M
Connect to the terminal block (TB5)
(M-NET transmission connecting wire)
24-30V DC (non-polar)
CN3A
Connect to the terminal block (TB15)
(MA-Remote controller connecting wire)
1 (+))
Between 1 to 3 8.7-13V DC (Pin1
LED1
Main power supply
(Indoor unit : 208/230V)
CN29
Pipe temperature
thermistor/Gas (TH23)
CN21
Pipe temperature
thermistor/Liquid (TH22)
LED2
Power supply for
MA-Remote controller
CN20
Room temperature
thermistor (TH21)
CN32
Connector
(Remote switch)
CND
Power supply for
indoor controller board
Between 1 to 3 208/230V AC
SW4
Model selection
CN60
Linear expansion valve
output (LEV)
CNP
Drain-up machine output (DP)
Between 1 to 3 208/230V AC
CN31
Drain sensor (DS)
SW3
Mode selection
CN51
Centrally control
FUSE
6A 250V
SW2
Capacity setting
CN52
Remote indication
CNDK
Connect to the indoor power
board (CNSK)
Between 1 to 3 208/230V AC
CN6V
Vane motor output (MV)
FAN
Fan motor output (MF)
27
OC343A-1.qxp
06.8.2 11:31 AM
Page 28
8-3-2. Indoor power board
PCFY-P15NGMU-E
PCFY-P24NGMU-E
PCFY-P30NGMU-E
PCFY-P36NGMU-E
CN2S
Connect to the indoor power board (CN2D)
1 (+))
Between 1 to 3 12.6-13.7V DC (Pin1
CNSK
Connect to the indoor controller board (CNDK)
Between 1 to 3 208/230V AC
28
OC343A-1.qxp
06.8.2 11:31 AM
9
Page 29
DISASSEMBLY PROCEDURE
INDOOR UNIT :
PCFY-P15NGMU-E PCFY-P24NGMU-E PCFY-P30NGMU-E PCFY-P36NGMU-E
OPERATING PROCEDURE
PHOTOS & ILLUSTRATIONS
1. Removing the air intake grille
(1) Slide the intake grille holding knobs at backward to open
the intake grille.
(2) When the intake grille opens, push the stoppers on the
rear hinges (at two locations) to pull out the intake grille.
Figure 1
intake grille
slide
intake grille
holding knobs
hinges
Pull out the intake grille
2. Removing the electrical box
(1) Remove the air intake grille.
(2) Remove the screw from the beam and remove the beam.
(3) Remove the screws from the electrical cover, and remove
the electrical cover.
(4) Disconnect the following wires from the indoor control
board.
• Fan motor : FAN
• Vane motor : CN6V
• Linear expansion valve : CN60
• Room temperature thermistor : CN20
• Liquid pipe temperature thermistor : CN21
• Gas pipe temperature thermistor : CN29
(5) Remove the screws from the electrical box and pull out
the electrical box.
<Electrical parts in the electrical box>
Terminal block (for power supply)
Terminal block (for transmission)
Terminal block (for MA remote controller)
Indoor control board
Address board
Power board
Capacitor
Figure 2
beam
Slide to the left
electrical cover
clamp
screws
(electrical
cover)
screws(electrical box)
Photo 1
Address board
Capacitor
Power board
Indoor
control
board
29
Terminal block
(transmission)
Terminal block
(power supply)
Terminal block
(MA remote
controller)
OC343A-1.qxp
06.8.2 11:31 AM
Page 30
OPERATING PROCEDURE
PHOTOS & ILLUSTRATIONS
3. Removing the fan motor
(1) Remove the intake grille.
(2) Disconnect the fan motor connector.
(3) Remove the screw for removing the motor support at both
left and right side.
(4) Loosen the set screws at the fan motor side of the connecting joint.
(5) Slide the fan motor to the left side and pull it out.
Photo 2
Motor
Screws
Motor support
4. Removing the sirocco fan
(1) Remove the air intake grille.
(2) Remove 1 beam.
(3) Remove the lower casing while pressing the stoppers at
upper side of the casing.
(4) Loosen the set screws at the connecting joint.
(5) Remove the sirocco fan and shaft together by sliding the
shaft to the left.
set screws
connecting joint
Photo 3
Casing
Motor Set screw Catch
(Note)
Make sure that the upper side casing is snapped to the fan
plate securely with catch.
Connecting joint
Shaft
Sirocco fan
5. Removing the side panel
(1) Remove the air intake grille.
(2) Remove the screw from the side panel, and remove the
side panel by sliding the panel to the front.
Figure 3
Bearing
Screws
side panel
sliding the panel
to the front
screw
30
OC343A-2.qxp
06.8.2 11:52 AM
Page 31
OPERATING PROCEDURE
PHOTOS & ILLUSTRATIONS
6. Removing the vane motor
(1) Remove the intake grille.
(2) Remove the left side panel.
(3) Remove the relay connector of vane motor.
(4) Remove the electrical box.
(5) Remove the screws of vane motor, then remove vane
motor.
(Note)
Connect the lead wires and connectors properly and place
them in the proper position so that the wires are not pinched
by other parts.
Photo 4
Screws
Relay connector of
the vane motor
Vane motor
7. Removing the pipe temperature thermistor
(1) Remove the air intake grille.
(2) Remove the right side panel.
(3) Remove the relay connector of the pipe temperature thermistor.
(4) Remove the screw, and remove the check panel.
(5) Extract the pipe temperature thermistor from the holder.
<Caution for the installation>
There is a possibility for the short circuit when connector gets
wet by water through the thermistor lead wire.
Therefore, lead wire of the pipe temperature thermistor
should be trapped as shown in photo 6.
(6) Gas pipe temperature thermistor is inserted to the holder
of the gas pipe (Header)
Photo 5
Screw
Check
panel
Relay connector of
the pipe temperature
thermistor
Left side
panel
Photo 6
Figure 4
Check panel
Liquid pipe thermistor
Gas pipe (Header)
Gas pipe thermistor
Hold
8. Removing the under panel
(1) Remove the air intake grille.
(2) Remove the beam.
(3) Remove the side panel (right and left).
(4) Unscrew the screws of the under panel, then remove the
lower panel.
❈ Weight of the lower panel : Approx. 2kg.
Photo 7
Pipe temperature thermistor
Screws
Under panel
31
Trap
OC343A-2.qxp
06.8.2 11:52 AM
Page 32
OPERATING PROCEDURE
PHOTOS & ILLUSTRATIONS
9. Removing the drain pan
(1) Remove the air intake grille.
(2) Remove the beam.
(3) Remove the side panel (right and left).
(4) Remove the under panel. Remove the screws of the right
and left side drain pan.
(5) Remove the insulation in centre of the drain pan, and
after removing the screw, remove the drain pan.
Photo 8
(Note)
Please note that there might be drain left in the drain pan
when you remove the drain pan.
Screw
10. Removing the guide vane
(1) Remove the intake grille.
(2) Remove the beam.
(3) Remove the side panel (right and left).
(4) Remove the under panel.
(5) Remove the drain pan.
(6) Remove the screw from the guide vane, then remove the
guide vane.
Drain pan
Screw
Photo 9
Drain pan
11. Removing the Auto vane
(1) Remove the intake grille.
(2) Remove the left side panel.
(3) Remove the left side box.
(4) Remove the under panel.
(5) Remove the screw from the auto vane.
(6) Slide the auto vane to the right side and pull the auto
vane out.
Screws
(Insulation)
Screw
Guide vane
Photo 10
Auto vane
32
Screw
OC343A-2.qxp
06.8.2 11:52 AM
10
Page 33
PARTS LIST (non-RoHS compliant)
ELECTRICAL PARTS
PCFY-P15NGMU-E
PCFY-P24NGMU-E
PCFY-P30NGMU-E
PCFY-P36NGMU-E
8
9
7
6
1
2
3
4
5
TEMP.
11
10
Q'ty/set
No.
Parts No.
Parts Name
PCFY-P • NGMU-E
Specifications
15
1
T7W E10 255 CAPACITOR
3= 440V
T7W E12 255 CAPACITOR
4= 440V
T7W E07 255 CAPACITOR
5= 440V
R01 E03 255 CAPACITOR
7= 440V
24
30
36
Wiring RecomRemarks
Diagram mended
(Drawing No.) Symbol
Q'ty
C1
1
C1
1
C1
1
2 T7W E42 310 INDOOR CONTROLLER BOARD
1
C1
1
1
1
1
I.B
3 T7W E11 716 TERMINAL BLOCK
3P(L1,L2,GR)
1
1
1
1
TB2
4 T7W E17 716 TERMINAL BLOCK
3P(M1,M2,S)
1
1
1
1
TB5
2P(1,2)
1
1
1
1
5
6
R01 556 246 TERMINAL BLOCK
—
CONTROL BOX
1
1
1
1
7 T7W E00 294 ADDRESS BOARD
1
1
1
1
8
R01 05A 304 ADDRESS CABLE
1
1
1
1
9
R01 E02 313 POWER BOARD
1
1
1
1
10
11
—
BOX COVER
—
BOX COVER
—
BOX COVER
—
REMOTE CONTROLLER PAR-21MAA
1
1
A.B
P.B
1
1
(BG02A804G21)
(BG02A804G22)
1
33
TB15
(BG00N015G31)
(BG02A804G20)
1
1
ON/OFF
1
Price
Unit Amount
OC343A-2.qxp
06.8.2 11:52 AM
Page 34
STRUCTURAL PART
PCFY-P15NGMU-E
27
26 25 24 23 22 21 20
1
2
19
3
4
18
17
16
15
5
6
7
8
9 10 11 12 13 14
Part number that is circled is not shown in the figure.
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
Parts No.
T7W
R01
R01
R01
R01
R01
R01
R01
T7W
T7W
R01
T7W
R01
R01
R01
R01
T7W
R01
R01
T7W
T7W
R01
R01
R01
R01
R01
E01
A15
17J
18J
17J
17J
A14
—
17J
—
E00
E01
17J
E05
17J
17J
17J
E00
E04
17J
18J
E00
E04
17J
E03
17J
17J
17J
666
500
061
691
691
054
500
669
070
665
808
668
661
067
085
033
651
002
086
501
676
068
223
809
662
523
Parts Name
S.PLATE-L
L.L FILTER
GRILLE HINGE
GRILLE ASSY
GRILLE ASSY
GRILLE CATCH
L.L FILTER
REAR SUPPORT
UNDER PANEL
BEAM(GA)
W.BOARD CASE
S.PLATE-R
RIGHT LEG (R)
SERVICE PANEL
RIGHT SIDE PANEL
RIGHT SIDE BOX
G.V ASSY-6R
VANE SUPPORT
FRONT PANEL
AUTO VANE
G.V ASSY-6L
AIR FILTER
REAR PANEL
LEFT SIDE BOX
VANE MOTOR
LEFT LEG (L)
LEFT SIDE PANEL
JOINT SOCKET
Specifications
Q'ty/set
PCFYP15NGMU-E
1
1
4
1
1
4
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
34
Remarks
(Drawing No.)
Wiring RecomDiagram mended
Symbol Q'ty
(BG02H454K01)
(BG17H464H08)
MV
Price
Unit Amount
OC343A-2.qxp
06.8.2 11:52 AM
Page 35
26 25 24 23
STRUCTURAL PART
PCFY-P24NGMU-E
PCFY-P30NGMU-E
22
21
20
1
2
3
4
5
19
18
17
16
15
14
6
7
8
9
10
11 12 13
Part number that is circled is not show in the figure.
No.
Parts No.
Parts Name
Specifications
Q'ty/set
PCFYP24NGMU-E P30NGMU-E
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
R01
R01
R01
T7W
T7W
T7W
T7W
R01
R01
R01
R01
R01
T7W
T7W
T7W
R01
R01
R01
T7W
T7W
R01
R01
T7W
T7W
R01
R01
R01
R01
R01
R01
R01
R01
R01
R01
T7W
T7W
R01
R01
R01
R01
R01
17J
35J
17J
E01
E00
E05
E00
17J
17J
17J
A14
29J
E00
—
—
E01
E02
17J
35J
17J
E05
E01
17J
35J
E05
E00
29J
E03
E00
E01
17J
37J
29J
37J
18J
37J
E01
051
17J
E00
29J
35J
17J
662
662
809
666
666
676
676
061
054
691
500
669
070
665
665
661
661
808
668
668
067
067
651
651
002
002
033
033
085
085
087
087
086
086
501
501
068
068
223
223
523
Remarks
(Drawing No.)
Wiring RecomDiagram mended
Symbol
Q'ty
1
LEFT SIDE PANEL
LEFT SIDE PANEL
LEFT LEG
S.PLATE-L
S.PLATE-L
REAR PANEL
REAR PANEL
GRILLE HINGE
GRILLE CATCH
GRILLE ASSY
L.L FILTER
UNDER PANEL
W.BOARD CASE
REAR SUPPORT
BEAM (GA)
S.PLATE-R
S.PLATE-R
RIGHT SIDE PANEL
RIGHT SIDE PANEL
RIGHT LEG
SERVICE PANEL
SERVICE PANEL
RIGHT SIDE BOX
RIGHT SIDE BOX
FRONT PANEL
FRONT PANEL
AUTO VANE
AUTO VANE
VANE SUPPORT
VANE SUPPORT
G.V ASSY-6R
G.V ASSY-6R
G.V ASSY-6C
G.V ASSY-6C
G.V ASSY-6L
G.V ASSY-6L
AIR FILTER
AIR FILTER
LEFT SIDE BOX
LEFT SIDE BOX
VANE MOTOR
VANE MOTOR
JOINT SOCKET
1
1
1
1
1
1
4
4
2
2
1
1
1
2
1
1
4
4
2
2
1
1
1
2
(BG02H454K01)
(BG17H464H08)
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
35
1
1
MV
MV
Price
Unit Amount
OC343A-2.qxp
06.8.2 11:52 AM
Page 36
STRUCTURAL PART
PCFY-P36NGMU-E
28
26 25 24
27
23
22
21
1
2
20
3
4
5
6
19
18
17
16
15
14
7
8
10 11
9
12 13
Part number that is circled is not shown in the figure.
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
Parts No.
R01
T7W
T7W
R01
R01
R01
R01
R01
R01
R01
T7W
R01
R01
T7W
R01
T7W
T7W
R01
R01
R01
R01
R01
T7W
R01
R01
R01
R01
35J
E00
E01
A15
17J
18J
17J
17J
A14
41J
E00
—
—
35J
17J
E01
35J
E02
E01
E04
41J
43J
E01
42J
051
E00
35J
17J
17J
662
666
676
500
061
691
054
691
500
669
070
661
808
668
067
665
651
002
085
087
033
086
501
068
223
809
523
Parts Name
LEFT SIDE PANEL
S.PLATE-L
REAR PANEL
L.L FILTER
GRILLE HINGE
GRILLE ASSY
GRILLE CATCH
GRILLE ASSY
L.L FILTER
UNDER PANEL
W.BOARD CASE
REAR SUPPORT
BEAM(GA)
RIGHT SIDE PANEL
RIGHT LEG
SERVICE PANEL
RIGHT SIDE BOX
S.PLATE-R
FRONT PANEL
AUTO VANE
G.V ASSY-5R
G.V ASSY-5C
VANE SUPPORT
G.V ASSY-5L
AIR FILTER
LEFT SIDE BOX
VANE MOTOR
LEFT LEG
JOINT SOCKET
Specifications
Q'ty/set
PCFYP36NGMU-E
1
1
1
1
6
1
6
2
2
1
1
1
3
1
1
1
1
1
1
1
1
2
3
1
1
1
1
1
1
36
Remarks
(Drawing No.)
Wiring RecomDiagram mended
Symbol Q'ty
(BG02H454K01)
(BG17H464H08)
MV
Price
Unit Amount
OC343A-2.qxp
06.8.2 11:52 AM
Page 37
FAN PARTS
PCFY-P15NGMU-E
12
1
11
2
3
10
4
9
3
2
5
6
7
8
Part number that is circled is not shown in the figure.
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
Parts No.
R01
T7W
R01
R01
R01
T7W
R01
T7W
R01
R01
R01
T7W
T7W
17J
B06
17J
E26
43E
23J
17J
E19
E27
E60
17J
K21
E00
130
110
114
202
126
762
524
529
202
401
202
480
072
Parts Name
Specifications
MOTOR LEG
CASING
SIROCCO FAN
ROOM TEMPERATURE THERMISTOR
2pcs/set
PIECE (MOTOR)
D09B4P54MS
FAN MOTOR
DRAIN PLUG
DRAIN PAN ASSY
LIQUID PIPE TEMPERATURE THERMISTOR
LINEAR EXPANSION VALVE
GAS PIPE TEMPERATURE THERMISTOR
HEAT EXCHANGER
DRAIN HOSE COVER
37
Q'ty/set
PCFYP15NGMU-E
1
2
2
1
1
1
1
1
1
1
1
1
1
Remarks
(Drawing No.)
Wiring RecomDiagram mended
Symbol Q'ty
TH21
MF
TH22
LEV
TH23
Price
Unit Amount
OC343A-2.qxp
06.8.2 11:52 AM
Page 38
FAN PARTS
PCFY-P24NGMU-E
PCFY-P30NGMU-E
17
1
16
2
3
4
15
5
14
13
12
11
6
7
8
10
9
Part number that is circled is not shown in the figure.
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Parts Name
Parts No.
R01
R01
R01
T7W
T7W
R01
R01
R01
R01
R01
R01
R01
R01
R01
T7W
T7W
T7W
T7W
R01
R01
R01
R01
R01
R01
T7W
T7W
T7W
29J
35J
43E
30J
E14
700
29J
35J
E26
29J
E00
29J
35J
17J
E20
E15
B06
B07
33J
39J
E27
E60
E61
17J
K22
K23
E00
130
130
126
762
762
116
114
114
202
100
103
145
145
524
529
529
110
110
114
114
202
401
401
202
480
480
072
Specifications
MOTOR LEG
MOTOR LEG
2pcs/set
PIECE(MOTOR)
D09C4P70MS
FAN MOTOR
D10C4P90MS
FAN MOTOR
SHAFT JOINT
SIROCCO FAN
SIROCCO FAN
ROOM TEMPERATURE THERMISTOR
SHAFT
SLEEVE BEARING
BEARING SUPPORT
BEARING SUPPORT
DRAIN PLUG
DRAIN PAN ASSY
DRAIN PAN ASSY
CASING
CASING
SIROCCO FAN
SIROCCO FAN
LIQUID PIPE TEMPERATURE THERMISTOR
LINEAR EXPANSION VALVE
LINEAR EXPANSION VALVE
GAS PIPE TEMPERATURE THERMISTOR
HEAT EXCHANGER
HEAT EXCHANGER
DRAIN HOSE COVER
Q'ty/set
Price
Wiring RecomRemarks
Diagram mended
PCFY(Drawing No.)
Unit Amount
Symbol Q'ty
P24NGMU-E P30NGMU-E
1
1
1
1
MF
1
MF
1
1
1
2
2
TH21
1
1
1
1
1
1
1
1
1
1
1
1
3
3
1
1
TH22
1
1
LEV
1
LEV
1
TH23
1
1
1
1
1
1
38
OC343A-2.qxp
06.8.2 11:52 AM
Page 39
FAN PARTS
PCFY-P36NGMU-E
18
1
2
3
4
17
5
16
15
6
12
13·14
7
8
9
10
11
Part number that is circled is not shown in the figure.
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
Parts No.
R01
R01
R01
R01
R01
T7W
R01
T7W
R01
R01
R01
T7W
R01
R01
R01
R01
R01
T7W
T7W
29J
41J
43E
41J
E26
E15
35J
E16
700
39J
17J
B07
E00
35J
E27
E61
17J
K24
E00
100
130
126
114
202
762
114
529
116
114
524
110
103
145
202
401
202
480
072
Parts Name
Specifications
SHAFT
MOTOR LEG
PIECE (MOTOR)
2pcs/set
SIROCCO FAN
ROOM TEMPERATURE THERMISTOR
FAN MOTOR
D10D4P150MS
SIROCCO FAN
DRAIN PAN ASSY
SHAFT JOINT
SIROCCO FAN
DRAIN PLUG
CASING
SLEEVE BEARING
BEARING SUPPORT
LIQUID PIPE TEMPERATURE THERMISTOR
LINEAR EXPANSION VALVE
GAS PIPE TEMPERATURE THERMISTOR
HEAT EXCHANGER
DRAIN HOSE COVER
39
Q'ty/set
PCFYP36NGMU-E
1
1
1
1
1
1
2
1
1
1
1
4
1
1
1
1
1
1
1
Remarks
(Drawing No.)
Wiring RecomDiagram mended
Symbol Q'ty
TH21
MF
TH22
LEV
TH23
Price
Unit Amount
OC343A-2.qxp
11
06.8.2 11:52 AM
Page 40
RoHS PARTS LIST
ELECTRICAL PARTS
PCFY-P15NGMU-E
PCFY-P24NGMU-E
PCFY-P30NGMU-E
PCFY-P36NGMU-E
8
9
7
6
1
2
3
4
5
TEMP.
11
1
RoHS
10
No.
Q'ty/set
Parts No.
Parts Name
Specifications
G T7W E15 255 CAPACITOR
3= 440V
G T7W E18 255 CAPACITOR
4= 440V
G T7W E19 255 CAPACITOR
5= 440V
G R01 E14 255 CAPACITOR
7= 440V
2 G T7W E57 310 INDOOR CONTROLLER BOARD
3 G T7W E41 716 TERMINAL BLOCK
4 G R01 E27 246 TERMINAL BLOCK
5 G R01 E21 246 TERMINAL BLOCK
6 G
PCFY-P • NGMU-E
15
—
24
30
36
Wiring RecomRemarks
Diagram mended
(Drawing No.) Symbol
Q'ty
C1
1
C1
1
C1
1
1
C1
1
1
1
1
I.B
3P(L1,L2,GR)
1
1
1
1
TB2
3P(M1,M2,S)
1
1
1
1
TB5
2P(1,2)
1
1
1
1
CONTROL BOX
1
1
1
1
7 G T7W E01 294 ADDRESS BOARD
1
1
1
1
8 G R01 A01 304 ADDRESS CABLE
1
1
1
1
9 G R01 E38 313 POWER BOARD
1
1
1
1
G
—
BOX COVER
10 G
—
BOX COVER
G
—
BOX COVER
11 G
—
REMOTE CONTROLLER PAR-21MAA
TB15
(BG00N015G31)
A.B
P.B
(BG02A804G20)
1
1
1
1
40
1
(BG02A804G21)
(BG02A804G22)
1
1
ON/OFF
1
Price
Unit Amount
OC343A-2.qxp
06.8.2 11:52 AM
Page 41
STRUCTURAL PART
PCFY-P15NGMU-E
26 25 24 23 22 21 20
27
1
2
19
3
4
18
17
16
15
5
6
7
8
9 10 11 12 13 14
No.
RoHS
Part number that is circled is not shown in the figure.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
Parts No.
T7W
R01
R01
R01
R01
R01
R01
R01
T7W
T7W
R01
T7W
R01
R01
R01
R01
T7W
R01
R01
T7W
T7W
R01
R01
R01
R01
R01
E02
A30
18J
19J
20J
19J
A29
—
31J
—
E03
E03
18J
E10
18J
18J
40J
E02
E07
31J
40J
E02
E06
18J
E11
18J
18J
18J
666
500
061
691
691
054
500
669
070
665
808
668
661
067
085
033
651
002
086
501
676
068
223
809
662
523
Parts Name
Specifications
S.PLATE-L
L.L FILTER
GRILLE HINGE
GRILLE ASSY
GRILLE ASSY
GRILLE CATCH
L.L FILTER
REAR SUPPORT
UNDER PANEL
BEAM(GA)
W.BOARD CASE
S.PLATE-R
RIGHT LEG (R)
SERVICE PANEL
RIGHT SIDE PANEL
RIGHT SIDE BOX
G.V ASSY-6R
VANE SUPPORT
FRONT PANEL
AUTO VANE
G.V ASSY-6L
AIR FILTER
REAR PANEL
LEFT SIDE BOX
VANE MOTOR
LEFT LEG (L)
LEFT SIDE PANEL
JOINT SOCKET
41
Q'ty/set
PCFYP15NGMU-E
1
1
4
1
1
4
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Remarks
(Drawing No.)
Wiring RecomDiagram mended
Symbol Q'ty
(BG02H454K01)
(BG17H464H08)
MV
Price
Unit Amount
OC343A-2.qxp
06.8.2 11:52 AM
Page 42
26 25 24 23
STRUCTURAL PART
PCFY-P24NGMU-E
PCFY-P30NGMU-E
22
21
20
1
2
3
4
5
19
18
17
16
15
14
6
7
8
9
10
11 12 13
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
RoHS
Part number that is circled is not show in the figure.
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
Parts No.
Parts Name
Specifications
Q'ty/set
PCFYP24NGMU-E P30NGMU-E
R01
R01
R01
T7W
T7W
T7W
T7W
R01
R01
R01
R01
R01
T7W
T7W
T7W
R01
R01
R01
T7W
T7W
R01
R01
T7W
T7W
R01
R01
R01
R01
R01
R01
R01
R01
R01
R01
T7W
T7W
R01
R01
R01
R01
R01
18J
36J
18J
E02
E03
E07
E08
18J
19J
19J
A29
30J
E03
—
—
E03
E04
18J
36J
18J
E10
E11
18J
36J
E08
E09
30J
E14
E02
E03
40J
38J
40J
38J
40J
38J
E03
E04
18J
E01
E10
E12
18J
662
662
809
666
666
676
676
061
054
691
500
669
070
665
665
661
661
808
668
668
067
067
651
651
002
002
033
033
085
085
087
087
086
086
501
501
068
068
223
223
523
LEFT SIDE PANEL
LEFT SIDE PANEL
LEFT LEG
S.PLATE-L
S.PLATE-L
REAR PANEL
REAR PANEL
GRILLE HINGE
GRILLE CATCH
GRILLE ASSY
L.L FILTER
UNDER PANEL
W.BOARD CASE
REAR SUPPORT
BEAM (GA)
S.PLATE-R
S.PLATE-R
RIGHT SIDE PANEL
RIGHT SIDE PANEL
RIGHT LEG
SERVICE PANEL
SERVICE PANEL
RIGHT SIDE BOX
RIGHT SIDE BOX
FRONT PANEL
FRONT PANEL
AUTO VANE
AUTO VANE
VANE SUPPORT
VANE SUPPORT
G.V ASSY-6R
G.V ASSY-6R
G.V ASSY-6C
G.V ASSY-6C
G.V ASSY-6L
G.V ASSY-6L
AIR FILTER
AIR FILTER
LEFT SIDE BOX
LEFT SIDE BOX
VANE MOTOR
VANE MOTOR
JOINT SOCKET
Remarks
(Drawing No.)
Wiring RecomDiagram mended
Symbol
Q'ty
1
1
1
1
1
1
1
4
4
2
2
1
1
1
2
1
1
4
4
2
2
1
1
1
2
(BG02H454K01)
(BG17H464H08)
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
42
1
1
MV
MV
Price
Unit Amount
OC343A-2.qxp
06.8.2 11:52 AM
Page 43
STRUCTURAL PART
PCFY-P36NGMU-E
28
26 25 24
27
23
22
21
1
2
20
3
4
5
6
19
18
17
16
15
14
7
9
8
10 11
12 13
No.
RoHS
Part number that is circled is not shown in the figure.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
Parts No.
R01
T7W
T7W
R01
R01
R01
R01
R01
R01
R01
T7W
R01
R01
T7W
R01
T7W
T7W
R01
R01
R01
R01
R01
T7W
R01
R01
R01
R01
36J
E03
E09
A30
18J
20J
19J
19J
A29
32J
E03
—
—
36J
18J
E11
36J
E04
E10
E15
39J
39J
E03
39J
E04
E01
E12
18J
18J
662
666
676
500
061
691
054
691
500
669
070
661
808
668
067
665
651
002
085
087
033
086
501
068
223
809
523
Parts Name
Specifications
LEFT SIDE PANEL
S.PLATE-L
REAR PANEL
L.L FILTER
GRILLE HINGE
GRILLE ASSY
GRILLE CATCH
GRILLE ASSY
L.L FILTER
UNDER PANEL
W.BOARD CASE
REAR SUPPORT
BEAM(GA)
RIGHT SIDE PANEL
RIGHT LEG
SERVICE PANEL
RIGHT SIDE BOX
S.PLATE-R
FRONT PANEL
AUTO VANE
G.V ASSY-5R
G.V ASSY-5C
VANE SUPPORT
G.V ASSY-5L
AIR FILTER
LEFT SIDE BOX
VANE MOTOR
LEFT LEG
JOINT SOCKET
43
Q'ty/set
PCFYP36NGMU-E
1
1
1
1
6
1
6
2
2
1
1
1
3
1
1
1
1
1
1
1
1
2
3
1
1
1
1
1
1
Remarks
(Drawing No.)
Wiring RecomDiagram mended
Symbol Q'ty
(BG02H454K01)
(BG17H464H08)
MV
Price
Unit Amount
OC343A-2.qxp
06.8.2 11:52 AM
Page 44
FAN PARTS
PCFY-P15NGMU-E
12
1
11
2
3
10
4
9
3
2
5
6
7
8
No.
RoHS
Part number that is circled is not shown in the figure.
1
2
3
4
5
6
7
8
9
10
11
12
13
G
G
G
G
G
G
G
G
G
G
G
G
G
Parts No.
R01
T7W
R01
R01
R01
R01
R01
T7W
R01
R01
R01
T7W
T7W
31J
B08
E16
H08
45E
18J
18J
E29
H10
H02
H09
H00
E01
130
110
114
202
126
220
524
529
202
401
202
480
072
Parts Name
Specifications
MOTOR LEG
CASING
SIROCCO FAN
ROOM TEMPERATURE THERMISTOR
2pcs/set
PIECE (MOTOR)
D09B4P54MS
FAN MOTOR
DRAIN PLUG
DRAIN PAN ASSY
LIQUID PIPE TEMPERATURE THERMISTOR
LINEAR EXPANSION VALVE
GAS PIPE TEMPERATURE THERMISTOR
HEAT EXCHANGER
DRAIN HOSE COVER
Q'ty/set
PCFYP15NGMU-E
1
2
2
1
1
1
1
1
1
1
1
1
1
44
Remarks
(Drawing No.)
Wiring RecomDiagram mended
Symbol Q'ty
TH21
MF
TH22
LEV
TH23
Price
Unit Amount
OC343A-2.qxp
06.8.2 11:52 AM
Page 45
FAN PARTS
PCFY-P24NGMU-E
PCFY-P30NGMU-E
17
1
16
2
3
4
15
5
14
13
12
11
6
7
8
9
10
Part number that is circled is not shown in the figure.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Q'ty/set
Price
Wiring RecomRemarks
Diagram mended
PCFY(Drawing No.) Symbol Q'ty Unit Amount
P24NGMU-E P30NGMU-E
1
G R01 30J 130 MOTOR LEG
G R01 32J 130 MOTOR LEG
1
2pcs/set
1
G R01 45E 126 PIECE(MOTOR)
1
D09C4P70MS
MF
1
G T7W 40J 762 FAN MOTOR
D10C4P90MS
MF
G T7W E31 762 FAN MOTOR
1
1
G R01 800 116 SHAFT JOINT
1
2
G R01 E17 114 SIROCCO FAN
G R01 E19 114 SIROCCO FAN
2
TH21
1
G R01 H08 202 ROOM TEMPERATURE THERMISTOR
1
1
G R01 30J 100 SHAFT
1
1
G R01 E02 103 SLEEVE BEARING
1
1
G R01 30J 145 BEARING SUPPORT
G R01 36J 145 BEARING SUPPORT
1
1
G R01 18J 524 DRAIN PLUG
1
1
G T7W E30 529 DRAIN PAN ASSY
G T7W E31 529 DRAIN PAN ASSY
1
3
G T7W B08 110 CASING
G T7W B09 110 CASING
3
1
G R01 E15 114 SIROCCO FAN
G R01 E20 114 SIROCCO FAN
1
TH22
1
G R01 H10 202 LIQUID PIPE TEMPERATURE THERMISTOR
1
LEV
1
G R01 H02 401 LINEAR EXPANSION VALVE
LEV
G R01 E86 401 LINEAR EXPANSION VALVE
1
TH23
1
G R01 H09 202 GAS PIPE TEMPERATURE THERMISTOR
1
1
G T7W H01 480 HEAT EXCHANGER
G T7W K30 480 HEAT EXCHANGER
1
1
G T7W E01 072 DRAIN HOSE COVER
1
RoHS
No.
Parts No.
Parts Name
Specifications
45
OC343A-2.qxp
06.8.2 11:52 AM
Page 46
FAN PARTS
PCFY-P36NGMU-E
18
1
2
3
4
17
5
16
15
6
12
13·14
7
8
9
10
11
No.
RoHS
Part number that is circled is not shown in the figure.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
Parts No.
R01
R01
R01
R01
R01
T7W
R01
T7W
R01
R01
R01
T7W
R01
R01
R01
R01
R01
T7W
T7W
30J
33J
45E
E18
H08
E32
E19
E32
800
E20
18J
B09
E02
36J
H10
E86
H09
K31
E01
100
130
126
114
202
762
114
529
116
114
524
110
103
145
202
401
202
480
072
Parts Name
Specifications
SHAFT
MOTOR LEG
2pcs/set
PIECE (MOTOR)
SIROCCO FAN
ROOM TEMPERATURE THERMISTOR
FAN MOTOR
D10D4P150MS
SIROCCO FAN
DRAIN PAN ASSY
SHAFT JOINT
SIROCCO FAN
DRAIN PLUG
CASING
SLEEVE BEARING
BEARING SUPPORT
LIQUID PIPE TEMPERATURE THERMISTOR
LINEAR EXPANSION VALVE
GAS PIPE TEMPERATURE THERMISTOR
HEAT EXCHANGER
DRAIN HOSE COVER
Q'ty/set
PCFYP36NGMU-E
1
1
1
1
1
1
2
1
1
1
1
4
1
1
1
1
1
1
1
46
Remarks
(Drawing No.)
Wiring RecomDiagram mended
Symbol Q'ty
TH21
MF
TH22
LEV
TH23
Price
Unit Amount
OC343A-2.qxp
06.8.2 11:52 AM
12
Page 47
OPTIONAL PARTS
HIGH EFFICIENCY FILTER
Part No.
Applied Service Ref.
PAC-SE80KF-E
PAC-SE81KF-E
PAC-SE82KF-E
PCFY-P15NGMU-E
PCFY-P24NGMU-E
PCFY-P30NGMU-E
PCFY-P36NGMU-E
47
OC343A-2.qxp
06.8.2 11:52 AM
Page 48
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO100-8310, JAPAN
cCopyright 2005 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.
Distributed in Aug. 2006 No. OC343 REVISED EDITION-A PDF 9
Distributed in Jun. 2005 No. OC343 PDF 10
Made in Japan
New publication, effective Aug. 2006
Specifications subject to change without notice