ITB-CD-CME-16-02 Palm Coast Wastewater
Transcription
ITB-CD-CME-16-02 Palm Coast Wastewater
ADDENDUM NO. 6 ITB-CD-CME-16-02 PALM COAST WASTEWATER TREATMENT PLANT NO. 2 ISSUE DATE: December 18, 2015 BID DATE: January 7, 2016 SUBJECT: Statements, Questions and Answers _____________________________________________________________________________________________ INTENT: This addendum is issued prior to the date bids are due in order to incorporate the following clarifications, additions, omissions, deletions, or changes into the Contract Documents. Except as hereinafter specified, the work shall be in accordance with the drawings and specifications. Bidders are to use the changed quantities of the items listed in this addendum in their proposals, and it shall become a part of the Contract Documents when construction is executed. Bidders are reminded that this addendum must be noted on the “Official City Acknowledgment Form” when they submit their proposal. A signed copy of the addendum must also be included with the bid submittal. _____________________________________________________________________________________________ Statements: 1. SECTION 01520 – TEMPORARY FACILITIES AND CONTROLS Section 2.04 A - Delete this paragraph in its entirety. 2. SECTION 02605 – PRECAST STRUCTURES AND ACCESSORIES Section 2.05 – Delete this paragraph in its entirety and insert the following in its place: 2.05 Lift Station Wet Well A. Base, riser, and top shall be in accordance with details on the Drawings. B. All precast construction shall be in accordance with ASTM C-478, minimum wall thickness of 6 inches. C. Exterior coatings shall be bituminous epoxy coating, minimum dry film thickness of 16 mils. Page 1 of 16 ITB-CD-CM E-16-02 - PALM COAST WASTEWATER TREATMENT PLANT NO. 6 D. Wet well liners shall be fiberglass, meeting the requirements of ASTM D3753, minimum thickness of 0.308 inches. E. Gaskets shall be Ramnek type and to be used at all joints on wet well riser. Section 2.10 – Delete this paragraph in its entirety and insert the following in its place: A. Interior – Concrete Coating shall be Conseal CS-55 manufactured by Concrete Sealants, Inc. or Tnemec Series 61 Tneme-liner, 12 mils thick and grey in color. B. Exterior - Concrete Coating shall be Conseal CS-55 manufactured by Concrete Sealants, Inc. or Tnemec Series 61 Tneme-liner, 8 mils thick and grey in color. Section 2.05 – Delete this paragraph in its entirety and insert the following in its place: 3. SECTION 02512 – RECLAIMED WATER DISTRIBUTION SYSTEM Added new Section 02512 “Reclaimed Water Distribution System”. 4. SECTION 02535 – SANITARY SEWER FORCE MAIN SYSTEMS Section 2.03 A – Delete this paragraph in its entirety and insert the following in its place: 1. 2. 5. Minimum 40 mils dry film thickness (60 mils nominal) of ceramic epoxy lining, as manufactured under the name of “Protecto 401", or Tnemec Series 431 Perma-Shield PL, or equal. Minimum 40 mils dry film thickness (60 mils nominal) of fusion bonded epoxy and polyethylene lining, as manufactured under the name of “Polybond Plus", or Tnemec Series 431 Perma-Shield PL, or equal. SECTION 09750 – PROTECTIVE FLOOR COATING Section 2.01 H – Delete this paragraph in its entirety and insert the following in its place: 1. 2. 3. 4. The material shall be ChemProof Polymers, Inc., Perma TEC 5000, available through ACR Process Equipment, Inc. of Lake Mary, Florida; or approved equal. A Non-Skid roughness of first coat shall be equal to 60 grit sandpaper. Sanitile 945, aggregate floor system as manufactured by Carboline, Inc. Stonshield, slip resistant flooring system, as manufactured by Stonehard, Inc. Tnemec Series 239SC Chembloc and a topcoat of Tnemec Series 282 Tneme-Glaze for the floor system Page 2 of 16 ITB-CD-CM E-16-02 - PALM COAST WASTEWATER TREATMENT PLANT NO. 6 5. 6. 6. Tnemec Stranlok approved with a topcoat of Tnemec Series 282 TnemeGlaze Or approved equal. SECTION 11388 – COARSE BUBBLE AERATION Section 1.03.B., change “Wilfley Weber, Inc., of Englewood, Colorado” TO “Aquarius Technologies”. Section 1.03. C., change “Wilfley Weber” TO “Aquarius Technologies” Section 2.04.A.6., change “304L” and REPLACE with “304” Section 2.04.B.2., change “23” TO “45” Section 2.04.B.3., change “23” TO “45” Section 2.04.D.1., delete “Florida” 7. SECTION 11350 – ODOR CONTROL SYSTEM 2.02 B. – Replace bullets a. and f. as the following: a. The system controls will consist of a NEMA 4X enclosure with integrated touchscreen HMI. A 30A reset ON/OFF switch shall be located on the front of the unit, lower right of the control panel. f. The base unit includes a blower/compressor(s) (based upon nozzle configuration) and an oxygen concentration unit that produces 65‐90% oxygen prior to use by the process. -– Replace bullets c. as the following 2.03 c. Nozzle: Gray PVC (Std Nozzle), engineered polymer cap (LV Nozzle) 3.03 A – Change 1.03 C to 1.03 D. Questions and Answers Question 1: DUCTILE IRON PIPE CONNECTION : Section – A on drawing M – 36 is showing the 8 “ Sludge Feed Line coming up through the floor on the left hand side of the section view. There is an oval ring with a callout indicating “ install FXF connection above grating to allow pipe removal while working on cake pump“ . We have seen the callout “ FXF “ used on several different piping configurations but they are usually shown with a little more information. We are not sure what is meant by the FXF at this location. This is for a Depend-O-Lok flange adapter or some other kind of flange adapter? Please review and clarify. Answer: A Depend-O-Lok flange adapter is acceptable for this application. Question 2: DUCTILE IRON PIPE CONNECTION: Section – A on drawing M – 36 is showing the 8 “Sludge Feed Line coming up through the floor on the left hand side of the section view. There is an oval ring with a callout indicating “install FXF connection above grating to allow pipe removal while working on cake Page 3 of 16 ITB-CD-CM E-16-02 - PALM COAST WASTEWATER TREATMENT PLANT NO. 6 pump“. Looking at this section view – A, the way it is drawn it does appear that the 8 “sludge line is coming up through the bottom of the trench. Looking at the plan view we see that the 8 “sludge pipe is coming up through the floor slab closer to the wall line. Also looking in section – B on sheet M – 37, it shows the line coming up through the floor slab and not in the trench area. Please review and clarify the note. Answer: This line is coming through the slab as shown on M-35 and M-37. Question 3: PLANT REUSE WATER: Drawing M – 35 is showing the Plant Service Water Booster pumps inside the Sludge Dewatering Building. The suction piping going to the two pumps is indicated to be 2 ½” stainless steel pipe and threaded fittings. The suction lines are shown with threaded gate valves, see mark item – 34. The specifications for smaller diameter gate valves appears to indicate providing bronze body valves. We were not sure if you want to have stainless steel body valves in the stainless steel piping. Please review and clarify if stainless steel valves or bronze valves are required in the stainless steel piping. Answer: Stainless steel valves shall be installed in this application. Question 4: PLANT SERVICE WATER – HOSE BIBBS : Drawing M – 35 is showing the Sludge Handling Building and the PVC Plant Service Water lines coming up to and going into the building for hose bibb stations. The left hand corner of the plan is showing a line next to the overhead door with a hose bibb inside the building and one outside the building. For the hose bibb outside the building do you want a freeze proof hose bibb extending through the wall to the exterior ? Do you want a freeze proof yard type hydrant buried outside the wall ? The plans do not clarify how these are to be configured. Please review and clarify. Answer: See detail on Sheet M-7. Question 5: PLANT SERVICE WATER – HOSE BIBBS : Drawing M – 35 is showing the Sludge Handling Building and the PVC Plant Service Water lines coming up to and going into the building for hose bibb stations. The Plant Service Water going to the three hose bibs is called out to be mark item – 20, which is ¾ “ PVC pipe. Do you want ¾” hose bibs to be installed at these three locations ? The hose bibb details on sheet M – 7 are indicating 1 “ supply lines and hose bibs. Please review and clarify. Answer: The supply lines to the hose bibbs shall be 1" as indicated on Sheet M-7. Question 6: PLANT SERVICE WATER – HOSE BIBBS : Drawing M – 35 is showing the Sludge Handling Building and the PVC Plant Service Water lines coming up to and going into the building for hose bibb stations. The Plant Service Water going to the three hose bibs is called out to be mark item – 20, which is ¾ “ PVC pipe. The two hose bibbs inside the building are to mounted along the interior wall. Do you want ¾ “galvanized steel pipe risers coming up through the floor ? Please review and clarify. Page 4 of 16 ITB-CD-CM E-16-02 - PALM COAST WASTEWATER TREATMENT PLANT NO. 6 Answer: The riser shall be 1" GSP as indicated on Sheet M-7. Question 7: PLANT SERVICE WATER – HOSE BIBBS : Drawing M – 35 is showing the Sludge Handling Building and the PVC Plant Service Water lines coming up to and going into the building for hose bibb stations. The left hand corner of the plan is showing a line next to the overhead door with a hose bibb inside the building and one outside the building. There is a note point to the hose rack outside the building stating “see detail on sheet “ Mechanical Piping Details “ . The only two sheets we found with this wording was on sheets C – 23 & 24. These two sheets did not have hose bibb details on them . We did find hose bibb details on sheet M – 7, at the Headworks Structure. Please review and clarify which hose bibb details are to be used for hose bibbs at other locations. Answer: The hose bibb details can be found on Sheet M-7. Question 8: POLYMER TUBING : Is there a specification section describing the ¾” polymer tubing in the Sludge Handling Building ? We need data for material, clear or not, braided or not, ID, OD, pressure rating and temperature. Please review and provide. Answer: The tubing shall be clear braided PVC tubing. Question 9: RECLAIMED WATER PIPING : We have been reviewing the Division – 2 Site Construction specifications for the buried yard piping systems materials. We found systems section – 02510 – Water Distribution Systems, which is indicated to be for “ public drinking water distribution systems, per paragraph 1.01, A. Then we found section – 02530 – Sanitary Sewer Systems and section – 02535 – Sanitary Sewer Force Main Systems. We did not find a system specifically including piping for the Reclaimed Water System. Please review and clarify. Answer: Please refer to Spec 02512 “Reclaimed Water Piping System” added. Question 10: RECLAIMED WATER PIPING : We found systems section – 02510 – Water Distribution Systems, which is indicated to be for “ public drinking water distribution systems, per paragraph 1.01, A. We reviewed the PVC pipe material description to see if it would be appropriate for the reuse water lines. The pipe described in section 02510 , 2.06, PVC Pressure Pipe, E, is described as being blue in color with “ Potable Water Main “. We did not think this would be acceptable for a “ Reuse Water “ line. Please review and clarify the PVC pressure pipe to be used for the buried Reuse Water System piping . Answer: Please refer to Spec 02512 “Reclaimed Water Piping System” added. Question 11: RECLAIMED WATER RECYCLE PIPING : Drawing C – 13 is showing line – 8 , 8 “ PVC Reclaimed Water Recycle line. The upper left hand corner of the sheet is indicating a fitting marked # 59 which is described as an 8 “ DIP 90 deg. Bend, MJ. Following the Reclaimed Water Recycle line to the right from this fitting we Page 5 of 16 ITB-CD-CM E-16-02 - PALM COAST WASTEWATER TREATMENT PLANT NO. 6 find two 90 degree bends with mark # 158. Looking at the descriptions for this mark number, it is described as an 8 “ PVC 90 deg. bend, MJ. Are you indicating that you want the fittings marked – 158 to be PVC fittings and not to be ductile iron fittings ? We do not know of a PVC fitting with MJ or mechanical joint ends. This also occurs on sheet C – 14. Please review and clarify what is required for these fittings. Answer: See revisions to Sheet C-13. Question 12: WAS YARD PIPE : Drawing C – 15 is showing line – 12, “ 6 “ DIP WAS line along the south side of the MBR Basins equipment slab. The line is shown coming out from under the equipment slab and coming to a buried tee fitting with mark # - 68. Then the line extends south to a fitting # 65 which is described as an 8 “ x 6 “ DIP reducer, MJ, fitting. Then it connects to an 8 “ MJ tee fitting with mark # 64. Looking at the large area piping drawing M – 9, this layout appears to be showing a buried MJ plug valve between the two MJ tee fittings. Please review and clarify if there is to be a valve at this location. Answer: See revisions to Sheet C-15. Question 13: WORKSHOP – GARAGE BUILDING : Drawing C – 18 is showing the Workshop and Garage building. There appears to be a drain line coming from the northwest corner of the building connecting to the line mark – 14, 3 “ PVC Wastewater Force Main. (We did not think force mains and gravity drain lines were usually combined or connected. This seems to provide the possibility for the force main to be pumped up into the building if there is ever a clog in the line. ) There is no size indicated for the drain line. There is also a water line going up to the building. We have not found any plumbing drawings for this structure. The architectural drawing appears to show a sink in the workbench area of the workshop. Please review and clarify the plumbing piping required for this building. Answer: See revisions to Sheets C-18 and C-19. Question 14: SANITARY SEWER FORCE MAIN : There is a 3 “ PVC Sanitary Sewer Force Main called out on drawings C – 19, C -18 and C – 13, going into the new InPlant Pump Station. The specification section – 02535 – Sanitary Sewer Force Mains, does not include a description for 3 “PVC pipe. We did find the various yard pipe systems general notes on sheet G – 3. There is a section for Force Main General Notes and it does include a description for 3 “ pipe to be PVC SDR – 21 with a water pressure rating of 200 psi, in item # 22. The fittings for the force main are described in paragraph item # 26, which indicates they are to be ductile iron for both PVC and ductile iron pipe. Drawing C – 18 is describing the PVC fittings marked – 61 & 62 to be solvent weld type PVC fittings. Please review and clarify the fittings to be used with the 3 “ SDR – 21 PVC pipe force main line. Answer: See revisions to Sheet C-18 Page 6 of 16 ITB-CD-CM E-16-02 - PALM COAST WASTEWATER TREATMENT PLANT NO. 6 Question 15: DUMPSTER FLOOR DRAIN LINE – YARD : Drawing C – 13 is showing the Headworks Structure. We see on the east side of the structure the Presswash unit dumpster is located. There is a mark item – 17 shown at the dumpster pad. This item is described as a 6 “ PVC dumpster floor drain. We see what we believe to be the 6 “ PVC drain line extending out from the pad to the north east, then stops. We do not know where this line should be routed. Looking on sheet M – 8 of the Headworks Structure, we see details 8 & 9 showing the two dumpster pads and the floor drains. These details are indicating that the floor drains and lines are 4 “ diameter in size. Should there be PVC reducers added to the line in increase it to be 6 “ ? Please review and clarify the drain line from the dumpster pad. Answer: The dumpster drain line shall connect to the 6" Gravity Sewer to the north (Mark Item 33). The line shall increase from 4" to 6" prior to connection. Question 16: SLUDGE DEWATERING BUILDING DRAIN LINES : Drawing C – 12 is showing line – 15 coming from the Sludge Dewatering Building loading area drive through. Line – 15 is described in the schedule as being a 10 “ PVC Gravity Sewer line. This line extends over to the new manhole # 2. Looking at the enlarged piping layout on sheet M – 35 of the Sludge Dewatering Building we see the drive through area and it is showing a 12 “ ductile iron drain pipe extending out to the east side. See mark item – 8 on sheet M – 35. Please review and clarify the sewer drain line from the Sludge Dewatering Building, is it PVC or is it ductile iron? Is it to be 10 “ diameter or is it to be 12 “ diameter ? Please clarify. Answer: The line shall be 12" DIP. Question 17: SLUDGE DEWATERING BUILDING DRAIN LINES : Drawing C – 12 is showing line – 16 coming from the Sludge Dewatering Building restroom. Line – 16 is described in the schedule as being a 6 “ PVC Sanitary Drain line. This line extends south to the drain line marked – 15. Looking at the plumbing drawing for the restroom on sheet P – 02, it is showing a 4 “ sanitary drain line coming out of the building. We do not see where the lines changes from 4 “ to be 6 “ diameter. Please review and clarify the sanitary drain line coming out of the restroom of the Sludge Dewatering Building. Answer: The line shall be 6" as shown on Sheet C-12. Question 18: SLUDGE HOLDING TANK – SUPERNATANT LINE : Drawing C – 12 is showing line mark item – 19, Supernatant line, on the south side of the Sludge Holding Tanks at manhole # 2. Looking at the enlarged piping layout of the Sludge Holding Tanks on sheet M – 30 we see the two 8 “ ductile iron lines coming out from under the tank slabs to two 8 “ MJ plug valves then coming to an 8 “ MJ tee fitting, then branching off to the south. The callout on M-30 is indicating that the line is a “ 8 “ Decant Line to on site drainage system “. The call out does not use the term or phrase “ Supernatant “. Should they both use the same name? Page 7 of 16 ITB-CD-CM E-16-02 - PALM COAST WASTEWATER TREATMENT PLANT NO. 6 Please review and clarify that these two lines are the same since they have different designations. Answer: The callout on Sheet M-20 shall read 8" Supernatant Line. Question 19: SLUDGE HOLDING TANK – SUPERNATANT LINE: Drawing C – 12 is showing line mark item – 19, Supernatant line, on the south side of the Sludge Holding Tanks at manhole # 2. The description on sheet C – 12 lists the pipe to be 8 “PVC, DR – 18. Looking at the enlarged piping layout of the Sludge Holding Tanks on sheet M – 30 we see the two 8 “ ductile iron lines coming out from under the tank slabs to two 8 “ MJ plug valves then coming to an 8 “ MJ tee fitting, then branching off to the south. The line coming out of the tanks is ductile iron and the pipe shown on the yard pipe layout, C – 12 is indicated to be PVC. We do not know where you want to make the transition from ductile iron to PVC. Please review and clarify this pipe line material. Answer: See Civil Pipe Legend revisions. Question 20: SLUDGE HOLDING TANK – SUPERNATANT LINE : Drawing C – 12 is showing line mark item – 19, Supernatant line, on the south side of the Sludge Holding Tanks at manhole # 2. Looking at the enlarged piping layout of the Sludge Holding Tanks on sheet M – 30 we see the two 8 “ ductile iron lines coming out from under the tank slabs to two 8 “ MJ plug valves then coming to an 8 “ MJ tee fitting, then branching off to the south. The pipe layout on sheet C – 12 is showing a valve marked # 118, which is a MJ gate valve. Do you want all three valves installed in this line ? Please review and clarify how many valves are required. Answer: All three valves shall be installed on the line. Question 21: SLUDGE HOLDING TANK – SUPERNATANT LINE : Drawing C – 12 is showing line mark item – 19, Supernatant line, on the south side of the Sludge Holding Tanks at manhole # 2. Looking at the enlarged piping layout of the Sludge Holding Tanks on sheet M – 30 we see the two 8 “ ductile iron lines coming out from under the tank slabs to two 8 “ MJ plug valves then coming to an 8 “ MJ tee fitting, then branching off to the south. Drawing M – 30 is showing a stub out for future connection. The pipe layout on sheet C – 12 does not show this, it is different. Which layout should be used for the project ? Please review and clarify. Answer: The layout on Sheet M-30 shall be used. Question 22: IN PLANT PUMP STATION – DISCHARGE LINE : Drawing C – 13 is showing the In Plant Pump Station and the discharge line Marked # 20 extending over to the Headworks Structure. The pipe line description indicated on sheet C – 13 for Mark item – 20 is “ 8 “ DIP “. Looking at the enlarged detail sheet for the In Plant Pump Station on sheet M – 43, we see the pump station discharge line going above ground then turning down 45 deg. to a buried 8 “ MJ 45 bend. At the outer side of the MJ 45 bend there is a callout for the discharge pipe to be 8 “ PVC , Page 8 of 16 ITB-CD-CM E-16-02 - PALM COAST WASTEWATER TREATMENT PLANT NO. 6 DR – 18. This conflicts with the designation given on sheet C -13 for the line. Please review and clarify which pipe material is to be used for this line. Answer: The discharge piping for the In-Plant Pump Station shall be DIP. Question 23: PLANT POTABLE WATER PIPING : Drawing C – 12 and C – 18 and is showing line – 27 , 8 “ PVC Potable Water line. The lower right hand corner of sheet C – 18 is indicating a fitting marked # 159 which is described as an 8 “ PVC 45 deg. Bend, MJ. This line # 27 extends on to sheet C – 12 and lists another 45 deg. bend with mark item # 159. The line # 27 extends to the left to a mark item # 162 fitting, an 8 “ x 2 “ PVC tee fitting. Are you indicating that you want the fittings marked – 162 and 158 to be PVC fittings and not to be ductile iron fittings? We do not know of a PVC fitting with MJ or mechanical joint ends. Please review and clarify what is required for these 8 “ Potable Water line fittings. Answer: Please see revisions to Pipe Legend. Question 24: PLANT POTABLE WATER PIPING : Drawing C – 12 and C – 18 and is showing line – 27 , 8 “ PVC Potable Water line. The line goes to sheet C – 12 and extends across the sheet to a new fire hydrant. Looking in specification section – 02510, Water Distribution Systems, 2.06, PVC Pressure Pipe, D, it states that “ water main pipe shall be class 235 ( DR18 ) , “ fire mains shall be class 305 ( DR14). The line 27 is indicated to be a “ Plant Potable Water “ line, but is also is supplying water to a fire hydrant. Does this line qualify as a “ fire main “ ? Please review and clarify this line and the type of pipe to be provided. Answer: The line classifies as a fire main. Question 25: PLANT POTABLE WATER PIPING : Drawing C – 12 is showing mark item – 66 and is described as a “ 6” x 4 “ PVC “. The description is obviously not complete. This fitting is providing a branch to a line # 28, which is a 2 “ PVC Potable Water line. Rather than this fitting be a PVC fitting, we are assuming that a 6 “ MJ 2 “ tapped tee fitting can be provided to provide the 2 “ branch off of this line. We have noticed several other locations where branches were indicated to come off of larger lines. We were assuming that we can provide other MJ tapped tee fittings for these 2” branches. Please review and advise if these type MJ fittings will be acceptable rather than PVC fittings. Answer: MJ tapped Tee Fittings are acceptable. Question 26: PLANT POTABLE WATER PIPING : Drawing C – 12 is showing mark item – 69, which is a fire hydrant. Before the fire hydrant there is a 6 “ MJ gate valve mark item – 67. The fire hydrant is in the branch off of a 6 “ MJ tee fitting, see mark item – 68. There is a MJ plug in the run of the 6 “ MJ tee, for possibly an extension of this line. Looking at the standard fire hydrant detail – 20, from Palm Coast Utilites, it is showing an isolation valve on the branch. Our question is, do we need to provide a second 6 “ valve before the hydrant ? Was your intention by the way it was drawn that the 6 “ gate valve before the 6 “ MJ tee, to provide Page 9 of 16 ITB-CD-CM E-16-02 - PALM COAST WASTEWATER TREATMENT PLANT NO. 6 the isolation of the hydrant ? Please review and clarify the piping configuration of the fire hydrant and isolation valve. Answer: See revisions to Sheet C-12. Question 27: LINE – 28 – PVC POTABLE WATER YARD PIPING: Drawing C – 12 is showing the line – 28 on the east side of the Sludge Dewatering Building. The line is shown branching off of the line – 27 at the MJ tapped tee fitting # - 66. The line – 28 is shown extending north to the first 2 “ PVC 90 bend, mark item – 71, turning east and continuing to the Sludge Handling Building. Before the line reaches the Sludge Handling Building there is a branch line coming off of the line – 28 at a tee fitting – 87. The description for this mark item – 87 fitting is “ 3 “ PVC tee, solvent weld “ . Just above the tee fitting is a gate valve symbol with mark item – 135, which is indicated to be a 3 “ gate valve. The pipe line is indicated to be mark item – 44, which is described to be “ 3 “ PVC RW Service Main “. We believe is has been mislabeled, since this is coming off of a potable water line. This line is going up to a hose bibb station, see mark item – 82. Should this line extending north be shown coming off of the mark item line – 44? Please review and clarify this potable and service water piping. Answer: Mark item 87 does in fact come off a reclaimed line. See mark item 44. Question 28: DUCTILE IRON BURIED AIR PIPING – YARD : The yard piping drawings are indicating lines 29, 30 and 31 to be buried air lines to the Equalization Tanks. We have not found a specification description for buried ductile iron pipe for the process air piping. We do not know what class of pipe to provide. We did notice the pipe line and fitting descriptions indicated them to be “ epoxy “ lined. We are assuming that it is to be the same Protecto 401 epoxy lining as indicated for other fluid process lines. Please review and clarify. Answer: Protecto 401 epoxy lining is acceptable. Question 29: DRAIN LINE : Drawing M – 40 is showing the Sodium Hypochlorite / Alum Feed System Building piping. There is a drain line that comes out of the trench at the center of the building and extends out to the east side. There is no indication if there is a floor drain where the drain line starts. There is no size indicated for the drain line nor what pipe material is to be provided. Please review and clarify the drain line. Answer: See revisions to Sheet C-14. Question 30: DRAIN LINE: Drawing C– 14 is showing the Sodium Hypochlorite / Alum Feed System Building . There is a drain line that comes out of the building and extends out to the east side to the manhole # 1. There is no size indicated for the drain line nor what pipe material is to be provided. Please review and clarify the drain line. Answer: See revisions to Sheet C-14. Page 10 of 16 ITB-CD-CM E-16-02 - PALM COAST WASTEWATER TREATMENT PLANT NO. 6 Question 31: HEADWORKS DRAINS : Drawing C – 13 is showing two gravity sewer lines marked # 33, extending from the grit dumpster pads over to the In Plant Pump Station. There is a drain line shown coming away from the east side Grit Classifier and Auger. It is drawn as if there is a floor drain in the concrete slab, but there is no mark item indicated at the circular symbol. Looking at the enlarged piping layout on sheet M – 4, it does not show this drain line. It does show the 4 “ PVC drain line coming from the grit dumpster pad. Please review and clarify is there is a floor drain and drain line to be installed at this location. Answer: See revisions to Sheet C-13. Question 32: HEADWORKS DRAINS : Drawing M – 3, detail – 3, is showing the Grit Classifier and Auger unit with the 6 “ DIP drain line with a note to connect the DIP to the 6 “ Gravity Sewer line. Refer to the plan view shown on sheet M – 4. The drain line is shown coming off of the end of the Classifier unit, which is the south side. Looking at the yard piping layout for the Headworks Structure, on sheet C – 13, we do not find this 6 “DIP drain line. Please review and clarify. Answer: See revisions to Sheet C-13. Question 33: RW SERVICE WATER LINES : Drawings C – 14 and C – 15 are showing several RW Service Water lines extending up to the Biological Process Tanks feed hose bibb stations. These lines are marked with number – 42. Looking at the Piping Legend for this line number indicates that these lines are to be 2 “ PVC RW Service Mains. Looking at the enlarged piping layout for the Biological Process Tanks on sheet M – 17, we see the Plant Service Water lines extending up to the tanks. These lines have the mark number – 1 which is indicated to be 1 ½ “ PVC lines. There is a conflict between the two sheets. One is showing 2 “ and the other is indicating 1 ½” size lines. Please review and clarify. Answer: See revisions to Sheet M-17. Question 34: PROCESS AIR PIPE BURIED IN THE YARD : Looking at the Blower Pad on sheet M – 33 we see the two process air lines going down into the ground. Looking at section – B, the pipe on the right side, which is heading south, is shown to reduce down in size from 16 “ to 14 “ diameter. Looking at the yard piping at the Blower Pad we see the process air line extending to the south with the designation number – 30. Looking at the pipe legend we see that it is described as a 16 “DIP Air Pipe. Is the line to 14 “or 16 “ diameter ? Please review and clarify the air piping. Answer: See Civil Pipe Legend Revisions. Question 35: BURIED DUCTILE IRON PROCESS AIR PIPE: Does the buried ductile iron process air piping have to be restrained as indicated for the water process pipe ? Please review and clarify. Answer: Yes, it needs to be restrained. Page 11 of 16 ITB-CD-CM E-16-02 - PALM COAST WASTEWATER TREATMENT PLANT NO. 6 Question 36: POTABLE WATER YARD PIPE: The yard pipe drawings are indicating that the pipe line mark item # - 27 is 8 “PVC potable water. The specifications in section – 025110 – 5, 2.06 – PVC Pressure Pipe, describes pipe 4 “and larger. Looking at the yard piping drawings, there is a Potable Water line with mark – 28, that is a 2 “PVC water line. We have not been able to find a specification description for this size pipe material. We do not know if it is to be schedule 40 or 80 or even SDR – 21. Please review and clarify. Answer: This piping shall be SCH 80. Question 37: On the Bid Schedule (Section 00200) Note 1 states that the Section 11100 scope of supply should be carried in Bid Item 1. Section 11100 references several other sections: 11125, 11140, 11150, 11155, and 13311. Should costs from these sections be included in Item 1 as well? Also, should sales tax be included in this Bid Item? Answer: Note 1in the Bid Form is revised to refer to Section 11000. Sales tax should not be included in this Bid Item. Question 38: Please reference the yard piping plans. The 8” Service Water Line from the Reclaimed Distribution Pumps Station is marked with Note 46, which per the Master Piping Legend is 8” PVC C900. The same line on drawing M-27 Section “C” is marked with Note 56 which calls for “8” DIP MJ”. Please clarify whether the line should be Ductile Iron Pipe or PVC. Answer: See revisions to Sheet C-17. Question 39: Please reference the yard piping plans. The 8” Reclaimed Water Recycle Line from the Reclaimed Water Recycle Pump Station is marked with Note 8, which per the Master Piping Legend is 8” PVC. The same line on drawing M-29 Section “” is marked with Note 4 which calls for “8” DIP. Please clarify whether the line should be Ductile Iron Pipe or PVC. Answer: See revisions to Sheet C-17. Question 40: Master Piping Schedule items 158, 159, 160 and 161 call for 6” and 8” diameter fittings with MJ connections. Should these be Ductile Iron MJ fittings for use with C900 pipe? Answer: See Civil pipe legend revisions. Question 41: Please provide a specification for the pre-engineered metal roof trusses. Answer: The pre-engineered metal roof trusses shall be installed as shown on the drawings. Page 12 of 16 ITB-CD-CM E-16-02 - PALM COAST WASTEWATER TREATMENT PLANT NO. 6 Question 42: Reference Drawing 2A.3: Building Section 1/2A.3 calls for Type A wall to be 12” concrete block wall. Building Section 2/2A.3 calls for Type A wall to be 8” concrete block wall. Please clarify. Answer: Please refer to Revised Building Section 1/2A.3; Type A wall shall be 8” concrete block. Question 43: Reference Drawing 5A.5: Building Section 3/5A.5 calls for Type A walls to be both 12” concrete block walls and 8” concrete block walls. Please clarify. Answer: Please refer to Revised Building Section 3/5A.5, Type A wall shall be 8” concrete block. Question 44: Drawing M-35 has as a note detailing sloped grout in the area below the Belt Filter Presses. Please indicate the depth and slopes of the grout fill to be provided. Answer: See revisions to sheet M-35. Question 45: Drawing 1A.3, General Note 8, calls for an 8’ high liner wall around interior of building. Please provide construction details and material specifications as required for the liner wall. Answer: Please refer to Revised Drawing 1A.3; note referring to wall liner has been eliminated. Not required. Question 46: Sheet S-17 details a 6” slab on grade, with #5 bar reinforcing, surrounding the Belt Filter Press recessed area at the Sludge Dewatering Building. Sheets 1A.6 and 1A.7 both detail this slab as 8” thick with WWF reinforcing. Please clarify. Answer: The slab shall be a 6” slab on grade, with #5 bar reinforcing. Question 47: Please reference drawing M-33 Section B. The Air piping running south from the blowers is shown reduced to 14” diameter as it runs below ground, however this line is detailed as 16” on the Yard Piping plans. Please clarify the correct size. Answer: See Civil pipe legend revisions. Question 48: Please reference drawing M-35. The drain line running out of the south side of the building is called out as 12” DIP per Keynote 8. The same line in the yard piping plans is marked with Keynote 15 which specifies 10” PVC Gravity Sewer. Please clarify which is correct. Answer: The line shall be 12" DIP. Page 13 of 16 ITB-CD-CM E-16-02 - PALM COAST WASTEWATER TREATMENT PLANT NO. 6 Question 49: In-Plant Pump Station Discharge piping is shown as 8” PVC on Drawing M-43, and as 8” DIP on the Yard Piping plans (key note 20). Please clarify which is correct. Answer: The piping shall be 8" DIP. Question 50: Please provide further details on the stairs and operations platform shown at the belt filter press on Drawings S-17 and M-35. Answer: See revisions to Sheet M-35. Question 51: YARD PIPING – MICRO C-G PIPING : Drawing C – 19 is showing four 2 “ PVC Micro C-G lines coming out of the west side of the existing Micro C-G Storage building. Two lines are stubbed out and are capped. Two other lines extend to the Pre-Anoxic Tanks. Looking at the enlarged piping plan for the Micro C-G building on drawing M – 39, we only see two Micro C-G lines. Where do the other two lines come from inside the building? Please review and clarify. Answer: See revisions to Sheet C-19 Question 52: POTABLE WATER METER: Drawing C – 18 is showing a 1 “water meter on the potable water line going to the Workshop and Garage building. We did not find a detail of a water meter on the drawings. Does the contractor provide the water meter or does the Palm Coast Utility? Please review and clarify. Answer: The Contractor shall provide the meter. Question 53: Reference drawing M-29. Bullet 4 indicates that the 8” reclaimed water line to the headworks is to be ductile iron. Reference drawing C-16. Line 8 indicated that the 8” reclaimed water line to the headworks is to be PVC. Please clarify. On line 8, there are two PVC 8” 90 bends (reference number 158 in the fitting legend) and one ductile iron8” 90 bend (reference number 59 in the fitting legend). Please verify that these fittings are correct. Answer: See Civil Sheets Revisions. Question54: Sheet S-1 indicates a total of eight 18”x18”x12” sumps, in the 20” base slab, at the Biological Process Tanks. Sheet M-9 confirms this, but Sheet M-17 details these sumps as 2’-6”x1’-6”x12” deep. Please clarify. Answer: The sumps shall be 18”x18”x12” per sheet M-9. Question55: Sheets M-30 (as well as Section B on sheet M-31) and E-44 appear to show a supported concrete walkway platform at the Sludge Holding Tanks. There is no Page 14 of 16 ITB-CD-CM E-16-02 - PALM COAST WASTEWATER TREATMENT PLANT NO. 6 indication of this platform on the S Drawings. Please provide structural details, including reinforcing, for this. Answer: See sheet M-45 for Stair Details. Question55: Refer to Drawing M-8. Please provide details and specifications for the structural beams, columns and roof deck shown at the Dumpster Housings. Answer: See sheets S-23 and S-24 for details. Question56: Please confirm that there is no sprinkler system required for this project. Answer: See Irrigation Plans for details. Question 57: Sheet 5A.2 shows a ramp at the northwest corner of the Workshop Building. Please provide a detail for this ramp. Answer: No detail is required as this is not a handicapped ramp with a handrail. The sidewalk shall be sloped 8% or less with a 5.5” rise. Question 58: Addendum # 2, item # 1, specification section 01650.1.02.D for startup states the Contractor shall provide all water or purchase water from the Owner, if available, that is required for testing of equipment, process subsystems, and facility start-up. Specification section 01520.2.04.B states that the Owner will provide reasonable amounts of water for testing at no costs to the Contractor. Please clarify if water will be provided to the Contractor by the Owner, at no cost to the Contractor, for testing purposes. Answer: Section 01520 is for the temporary Facilities and 2.04B is revised. Question 59: In Addendum # 2, Item #4, the revised specification Section 09820.1.01.A.1.b indicates that all above grade exterior concrete walls & slab surfaces of the process tanks shall receive a cementitious coating. Are the Biological Process Tanks, the Chlorine Contact Chambers, and the Sludge Holding Tanks to be considered as process tanks? Please clarify what particular slab surfaces are being referenced (i.e. traffic surface of 8” concrete slab for walkway at Biological, traffic surface of 12” concrete slab at Chlorine Contact Chambers, etc.) as these type surfaces are typically coated with a deck traffic coating. Answer: Yes, the Biological Process Tanks, the Chlorine Contact Chambers, and the Sludge Holding Tanks are considered as process tanks. Deck traffic coating is acceptable for the slab surface for walkway. Question 60: Please provide the 100 year flood elevation for the site. Answer: It is 35’. Page 15 of 16 ITB-CD-CM E-16-02 - PALM COAST WASTEWATER TREATMENT PLANT NO. 6 Question 61: Reference drawing M-35. Bullet 8 indicates that the line leaving the Sludge Dewatering Building towards manhole #2 is a 12” DIP. Reference drawing C-12. Line 15 indicates that the sewer line leaving the Sludge Dewatering Building towards manhole #2 is a 10” PVC pipe. Please clarify. Answer: The line shall be 12” DIP. Drawings: Added new drawings S-22, S-23, and S-24. Acknowledgment: ______________________________________________ Signature and Date ______________________________________________ Printed Name and Title ______________________________________________ Company Name END OF ADDENDUM NO. 6 (39 pages to follow) Page 16 of 16 ITB-CD-CM E-16-02 - PALM COAST WASTEWATER TREATMENT PLANT NO. 6 SECTION 02512 RECLAIMED WATER DISTRIBUTION SYSTEMS PART 1 GENERAL 1.01 1.02 1.03 1.04 Section Includes A. Piping, fittings and valves, for reclaimed water distribution systems B. Testing Related Sections A. Section 00902 - FDEP Supplementary Conditions (Construction) B. Section 02320 - Trenching, Bedding and Backfilling C. Section 02955 - Cleaning and Flushing Of Underground Piping D. Section 15100 - Control Valves American Iron and Steel Requirements A. All of the iron and steel products, including ductile iron pipe, fittings, valves, valve box lids, and tracer wire used on this project are to be produced in the United States, subject to the American Iron and Steel requirements outlined in Appendix D in Section 00902. B. Per Section 00902 Appendix D, the term "iron and steel products" means the following products made primarily of iron or steel: lined or unlined pipes and fittings, manhole covers and other municipal castings, hydrants, tanks, flanges, pipe clamps and restraints, valves, structural steel, reinforced precast concrete, and construction materials. References A. American Water Works Association (AWWA) and American National Standards Institute (ANSI) latest edition: 1. ANSI/AWWA C104/A21.4 - Cement Mortar Lining for Ductile Iron Pipe and Fittings for Water Reclaimed Water Distribution System 02512-1 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. B. American Society for Testing and Materials (ASTM) latest edition: 1. 2. 3. 4. 5. 6. 1.05 ANSI/AWWA C105/A21.5 - Polyethylene Encasement for Ductile Iron Pipe Systems ANSI/AWWA C110/A21.10 - Ductile Iron and Gray Iron Fittings, 3 Inch Through 48 Inch, for Water ANSI/AWWA C111/A21.11 - Rubber Gasket Joints for Ductile Iron Pressure Pipe and Fittings ANSI/AWWA C115/A21.15 - Flanged Ductile Iron Pipe with Ductile Iron or Gray Iron Threaded Fittings ANSI/AWWA C150/A21.50 - Thickness Design of Ductile Iron Pipe ANSI/AWWA C151/A21.51 - Ductile Iron Pipe, Centrifugally Cast, for Water ANSI/AWWA C153/A21.53 - Compact Ductile Iron Fittings for Water Service AWWA C504 - Rubber Seated Butterfly Valves AWWA C509 - Resilient Seated Gate Valves for Water Supply Service AWWA C515 - Reduced-Wall, Resilient-Seated Gate Valves for Water Supply Service AWWA C550 - Protective Epoxy Interior Coatings for Valves and Hydrants AWWA C600 - Installation of Ductile Iron Water Mains and Their Appurtenances AWWA C605 - Underground Installation of PVC Pipe and Fittings for Water AWWA C800 - Underground Service Line Valves and Fittings AWWA C900 - PVC Pressure Pipe, and Fabricated Fittings, 4 Inch Through 12 Inch, for Water Distribution AWWA C901 - Polyethylene Pressure Pipe and Tubing, ½ Inch Through 3 Inch for Water Service AWWA C905 - PVC Pressure Pipe and Fabricated Fittings, 14 Inch Through 48 Inch AWWA C906 - Polyethylene Pressure Pipe and Fittings, 4 Inch Through 63 Inch for Water Distribution and Transmission AWWA M23 - PVC Pipe Design and Installation Manual ASTM A307 - Carbon Steel Bolts and Studs ASTM A536 - Ductile Iron Castings ASTM D1784 - Rigid PVC Compounds and CPVC Compounds ASTM D2000 - Classification System for Rubber Products in Automotive Applications ASTM F1674 - Test Method for Joint Restraint Products for Use with PVC Pipe ASTM F2164 - Field Leak Testing of Polyethylene (PE) Pressure Piping Systems Using Hydrostatic Pressure Submittals A. Product data for gaskets, pipe, joints, joint restraint, fittings, valves, coatings. Reclaimed Water Distribution System 02512-2 1.06 B. Product data for all locate wire, tape, markers, warning tape C. Piping specialties and installation details. D. Certification from the manufacturer that its proposed iron and steel products are produced in the United States and are in compliance with the requirements in H.R. 3547, “Consolidated Appropriations Act, 2014,” (Appropriations Act). E. Product data and painting schedule for field applied paint and coatings. F. Final coat paint colors. Definitions Reclaimed Water = water that has received at least secondary treatment and basic disinfection and is reused after flowing out of a domestic wastewater treatment facility. 1.07 Product Delivery, Storage, and Handling Exercise care in transporting and handling pipe and fittings in order to avoid damage to materials or coatings. Lifting shall be by hoist or on skids when hand lifting is not feasible. Dropping shall not be permitted. Store pipe as recommended by the manufacturer. Damaged pipe and fittings shall be replaced. PART 2 PRODUCTS 2.01 Ductile Iron Pipe A. Buried pipe shall conform with ANSI/AWWA C150/A21.50 and C151/ A21.51, and shall have a minimum working pressure of 150 psi. Buried pipe shall comply with the following pressure class (PC) designations unless otherwise indicated on the Drawings: 1. 2. 3. B. Exposed pipe 4 inches and larger shall be flanged and shall conform with AWWA/ANSI C115/A21.15, and shall have a minimum working pressure of 150 psi. Flanged pipe shall comply with the following thickness class (TC) designations unless otherwise indicated on the Drawings: 1. 2. C. 2.02 12 inch diameter and smaller = PC 350 14 inch through 24 inch diameter = PC 250 30 inch through 64 inch diameter = PC 200 4 inch diameter = TC 54 6 inch through 24 inch diameter = TC 53 All flanges shall be class 125, and shall be fully machine faced after being screwed tightly on the pipe. Bolts and nut shall conform to ASTM A307, Grade B. Fittings for Ductile Iron and PVC Pipe Reclaimed Water Distribution System 02512-3 2.03 2.04 2.05 A. Fittings shall be manufactured of ductile iron, conforming to ANSI/AWWA C110/A21.10 or ANSI/AWWA C153/A21.53. B. All full body (C110/A21.10) fittings shall be pressure rated to 250 psi, minimum. All compact fittings (C153/A21.53) shall be pressure rated to 350 psi, minimum. C. Fitting joints shall be compatible with the type of pipe in use or specified, e.g., flange fittings for flange pipe and mechanical joint for mechanical joint pipe and push-on joint pipe. Linings and Coatings for Ductile Iron Pipe and Fittings A. Interior lining shall be standard thickness cement mortar lining and bituminous seal coat, conforming to ANSI/AWWA C104/A21.4. B. Exterior coating for buried pipe and fittings shall be a petroleum asphaltic coating in accordance with ANSI/AWWA C110/A21.10. C. All exposed pipe and fittings shall be painted with a three coat system. The first coat shall be primer, 2.5-3.5 mil Dry Film Thickness (DFT) Tnemec Series 135 ChemBuild or approved equal; the intermediate coat shall be 4.0-10.0 mil DFT Tnemec Color Hi-Build Epoxoline II Series N69 or approved equal, and the final coat shall be 2.0-3.0 mil DFT Tnemec EnduraShield Series 73 or approved equal. The final coat paint color shall be as selected by the City. Joints for Ductile Iron Pipe and Fittings A. Mechanical and push-on joints shall be rubber gasketed, conforming to ANSI/AWWA C111/A21.11. Mechanical joint bolts and nuts shall conform to ASTM A307, Grade B. Ductile iron glands shall be provided with ductile iron pipe. B. Lubricants other than that furnished by the pipe manufacturer with the pipe shall not be used. Restrained Joints for Ductile Iron Pipe and Fittings A. Restrained joints for ductile iron pipe bell joints shall be American Fast Grip Gasket, McWane Sure Grip 350 Gasket, U.S. Pipe Field Lok 350 Gasket, or EBAA Iron Mega Lug Series 1100HD. B. Restrained joints for ductile iron pipe and fitting mechanical joints shall be EBAA Iron Mega Lug Series 1100, Star Grip Series 3000, or Tyler Union Tuf-Grip Series TLD. C. Locking bell joint restraint shall be American Flex Ring Joint, American Lok-Ring Joint, or U.S. Pipe TR-Flex. Reclaimed Water Distribution System 02512-4 D. 2.06 2.07 2.08 2.09 Pipe joints shall be restrained upstream and downstream of fittings in accordance with the manufacturer’s requirements or the table shown in the Drawings, whichever is greater. PVC Pressure Pipe A. Pipe 4 inch through 12 inch diameter shall conform to AWWA C900. B. Pipe 14 inch through 30 inch diameter shall conform to AWWA C905. C. Pipe and fittings for PVC pipe smaller than 4 inch diameter shall be Schedule 80 PVC per ASTM D1784. D. Pipe shall conform to ASTM D1784, Type I, Grade I, 4000 psi design stress, and shall be National Sanitation Federation (NSF) approved. E. Reclaimed water main pipe shall be class 235 (DR18). All pipe shall contain markings on each section showing conformance to the above specifications. F. PVC pipes shall be color coded purple and stenciled (0.75-inch lettering on the pipe in at least three areas per pipe section) “Reclaimed Water Main”. PVC Pressure Pipe Joints A. Joints shall be rubber gasketed conforming to AWWA C900 or C905 B. The bell shall be integral with the pipe and of equal or greater pressure rating. The bell of pipe and fittings using push-on joints shall have an integral groove to retain the gasket in place. C. Provide adapters as required to join PVC pipe to pipe, fittings and equipment of other materials. Restrained Joints for PVC Pressure Pipe A. Restrained joints for PVC pipe mechanical joints shall be Tyler Union Series 2000 Tuf Grip TLP, JCM Sur-Grip Bell Restrainer, Ford Uni-Flange Series 1500 Circle Lock, or EBAA Iron Mega Lug Series 2000PV. B. Restrained joints for PVC pipe push on joints shall be EBAA Iron Mega Lug Series 1500 or Series 1600 (C900 PVC), Series 2800 (C905 PVC), Ford UniFlange Series 1390, or Smith-Blair Bell-Lok Series 165. C. Pipe joints shall be restrained upstream and downstream of fittings in accordance with the manufacturer’s requirements or the table shown in the Drawings, whichever is greater. Polyethylene Pipe and Fittings (4 Inches and Larger) Reclaimed Water Distribution System 02512-5 2.10 A. Polyethylene pipe and fittings shall be in accordance with AWWA C906, standard code designation standard code designation PE 3408. Pipe 4-30 inch diameter shall be DR11, PC 160. The manufacturer shall certify that the materials used to manufacture pipe and fittings meet these requirements. The pipe sizing shall be in accordance with Ductile Iron Sizing System (DIOD). Pipe using the newer ASTM designations for the material is acceptable, provided it is stamped “PE3408/PE4710 - AWWA C906” or “PE3408/PE3608/PE4710 - AWWA C906”. B. Polyethylene mechanical joint adapters and flange adapters shall be manufactured in accordance with AWWA C906. Mechanical joint adapters shall be fitted with gland rings pressure rated equal to or greater than the mating pipe, and shall be made with sufficient through-bore length to be clamped in a heat fusion joining machine without the use of sub-end holder. The sealing surface of the flange adapter shall be machined with a series of small v-shaped grooves to provide gastketless sealing, or to restrain the gasket against blow-out. C. Below grade HDPE pipe terminations shall be fitted with a mechanical joint adapter kit that will enable the HDPE pipe to be joined with mechanical joint fittings. The adapter shall be AWWA compliant, and the pressure rating for the adapter shall match the pressure rating for the HDPE pipe. Mechanical Joint adapter kits shall be manufactured in standard DIPS sizes for connecting DIPS sized polyethylene pipe to mechanical joint fittings and shall contain a HDPE anchor fitting, stainless steel reinforcing collar, AWWA C110 ductile iron gland ring, gasket and extra length T-bolts. D. Back-Up Rings and Flange Bolts. Flange adapters shall be fitted with lap joint flanges pressure rated equal to or greater than the mating pipe. The lap joint flange bore shall be chamfered or radiused to provide clearance to the flange adapter radius. Flange bolts and nuts shall be grade 2 or higher. E. All polyethylene pipe shall be black, and shall contain a continuous purple colored stripe, 2 inches wide, located at no greater than 90 degree intervals around the pipe. Polyethylene (PE) Pressure Pipe and Tubing, Joints and Fittings (½ Inch through 3 inch) A. Polyethylene pipe and tubing used for service lines ½-3 inch diameter shall be purple polyethylene in accordance with AWWA C901, standard code designation PE 4710, SDR 9 (outside diameter based dimension ratio), 250 psi. Pipe and fittings shall be NSF approved for the usage to which they are to be applied. B. Joints in SDR-PR PE pipe shall be butt heat fusion or socket heat fusion type. C. Fittings shall be manufactured of the same material as the pipe and shall be of the same DR. D. Provide adapters as required to join PE pipe-to-pipe, fittings and equipment of other materials. Reclaimed Water Distribution System 02512-6 2.11 Service Saddles Service saddles shall meet the requirements of AWWA C800 and shall consist of epoxy coated ductile iron bodies in accordance with ASTM A536, with double stainless steel straps, bolts, washers and nuts. Stainless steel shall be Type 304, and nuts are to be Teflon coated. The ductile iron body is to be fusion bonded nylon coated, minimum thickness 12 mils, outlet of saddle is to have NPT threads. Service saddles shall be manufactured by Ford, Mueller, or Smith-Blair. 2.12 Tapping Sleeves Tapping sleeves are to be 18-8 type 304 stainless steel and stainless steel outlet, as manufactured by JCM or approved equal. 2.13 Polyethylene Encasement – N/A 2.14 General Valve Requirements A. Unless otherwise indicated or specified, all valves two inches and smaller shall be all brass or bronze; valves over two inches shall be iron body, fully bronze or bronze mounted. B. Where required for satisfactory operation of valves, provide valve operators, extension stems, stem guides, cast iron valve boxes, floor boxes, handwheels, operator stands, position indicators, and other valve appurtenances. Extension stems shall be complete with guide bearings, wrench nut, and tee handle wrench. All machinery stuffing boxes shall be packed with material selected for the service intended. Maintain all packing until final acceptance by the City. C. Manufacturer's name, service, and pressure marking shall be cast into the body. D. Valve operators shall be sized for operation at the pressure and flow conditions required for proper operation. E. Extension stems shall be provided for all valves in buried locations and in other locations where indicated on the Drawings. F. Extension stems shall be fabricated from solid steel shafting not smaller in diameter than the stem of the valve or from galvanized steel pipe having an internal diameter not smaller than the diameter of the valve stem. Stem couplings shall be both threaded and keyed to the coupled stems and shall be of standard design and construction. Pipe couplings will not be acceptable. G. Stems for buried valves shall extend to within 6 inches of the surface of the ground. Each extension stem shall be connected to the valve operator with a suitable universal joint type coupling. All connections shall be pinned. Each extension stem shall be provided with spacers which will center the stem in a valve box having an inside diameter of approximately 5 inches, and shall be equipped with a standard AWWA wrench nut as described in AWWA C500, except where handwheels are indicated. Reclaimed Water Distribution System 02512-7 2.15 2.16 Linings and Coatings for Valves A. Exterior coating on buried valves shall be rust inhibiting epoxy primer, followed by a coal tar epoxy, total minimum dry film thickness of 16 mils, applied at the factory. Exterior coating of exposed valves shall be factory applied rust inhibiting epoxy primer, minimum 3 mils dry film thickness. B. After installation, exterior surfaces shall be painted with a two coat system. The first coat (intermediate coat) shall be 4.0-10.0 mil DFT Tnemec Color Hi-Build Epoxoline II Series N69 or approved equal, and the final coat shall be 2.0-3.0 mil DFT Tnemec EnduraShield Series 73 or approved equal. The final coat paint color shall be as selected by the City. C. The interior of valves with a cast iron or ductile iron body shall be coated with an epoxy protective coating meeting NSF International Standard 61 and AWWA C550. Gate Valves A. Gate valves 3 inches and larger shall be resilient wedge gate valves, conforming to AWWA C509 or AWWA C515. The valves shall be iron body, cast iron fully encapsulated molded rubber wedge complying with ASTM D2000, non-rising stem with O-ring seals. Valves shall open counterclockwise. Resilient wedge to be US Food and Drug Administration approved for potable water and have an EPDM visible marking. B. Valves shall have an unobstructed waterway equal to or greater than the full nominal diameter of the valve. C. All valves will have 250 psig working pressure and a 500 psi static test pressure. The valves shall be non-rising stems and the stem material shall be 18-8 stainless steel, Type 304, ANSI 420/ASTM A276 with no measurable level of lead content. Valves shall have two upper o-ring seals on the stem above the thrust collar and at least one o-ring seal below the collar so designed to allow for replacement of the upper o-rings with the valve under full operating pressure. Valves shall have thrust washers located above and below the thrust collar to insure a smooth frictionless operation. D. All valves shall have a 2 inch ductile iron wrench nut with direction of valve operation clearly visible when looking down on the nut. Hold down nut or bolt shall be Type 316 stainless steel. All exterior bonnet and thrust collar fasteners, whether recessed or exposed, are to be Type 316 Stainless Steel and marked by type. E. The waterway seat area will be smooth without ridges or cavities and valves will have full size bore throughout the flow-way. All valves will be hydrostatically pressure tested prior to shipment in accordance with AWWA C509 and are to be covered by the manufacturers Ten Year Limited Warranty from date of purchase by the end user. Reclaimed Water Distribution System 02512-8 2.17 F. The resilient sealing mechanism shall provide zero leakage at test and normal working pressure when installed with the line flow from either direction. G. Gate valves larger than 12 inches shall be resilient seated and shall include either spur gear actuators (for valves to be installed in a vertical position) or bevel gear and side actuators (for valves to be installed in a horizontal position). H. Standard gate valves 2½ inches and smaller shall be Class 150 bronze gate valves by Powell Valves or approved equal. I. Gate valves 3”-12” shall be American Flow Control Series 2500, Clow Series F6100, or Mueller Series A-2360. J. Gate Valves large than 12 inches shall be American Flow Control Series 2500 or Mueller Series A-2361. Tapping Valves Tapping valves shall be resilient seated gate valves and shall conform to the requirements of AWWA C509. Tapping Valves shall be American Flow Control Series 2500, Clow Series F-6100, or Mueller Series A2361. 2.18 Butterfly Valves (N/A) - Refer to Section 15100 for Electrically Operated Butterfly Valves 2.19 Air Release Valves 2.20 A. Air release valves along the below grade reclaimed water transmission main shall be single body air release valves designed to release large quantities of air at start up and release air in operation. B. Air release valves shall be made of a reinforced nylon body, foamed polypropylene float, NBR 70 O-ring and reinforced nylon base. C. Air release valves shall be capable of withstanding operating pressures of 150 psi. D. Valves shall be ARI S-021. Corporation Stops Corporation stops shall be 1 inch, 1½ inch, 2 inch, or 2½ inch brass ball type, equipped with connections suitable for service piping. Conformance with AWWA C800 and C901 is required. Corporation stops shall be Ford FB1000 or McDonald 4701B-22. 2.21 Curb Stops Curb stops shall be manufactured of 85-5-5-5 bronze conforming to ASTM B62. Conformance with AWWA C800 and C901 Is required. Curb stops at meters shall be Reclaimed Water Distribution System 02512-9 sized to match the meter size. Curb stops shall be ball type reduced type Ford B11333W or McDonald 6101W. Curb stops at meters shall be ball type compression Ford B43-342W, B43-777W or McDonald 6100MW-22. 2.22 2.23 Valve Boxes A. All buried valves shall be provided with adjustable valve boxes approximately 5 inches in square and shall be heavy duty traffic rated. B. Valve boxes shall be cast iron. Valve box lids shall be cast iron H-20 load rated. C. Valve boxes shall be of sufficient length to operate all valves buried in the ground. Valve boxes shall consist of base, center section, and top section with cover. All valve box extensions shall be cast iron. D. Valve box lids in paved areas shall be lockable. E. Valve boxes shall be screw type. F. Valve boxes shall have valve box covers with the inscription "REUSE" cast thereon. G. All valve box covers shall be painted with a three coat system. The first coat shall be primer, 2.5-3.5 mil Dry Film Thickness (DFT) Tnemec Series 135 ChemBuild or approved equal; the intermediate coat shall be 4.0-10.0 mil DFT Tnemec Color Hi-Build Epoxoline II Series N69 or approved equal, and the final coat shall be 2.0-3.0 mil DFT Tnemec EnduraShield Series 73 or approved equal. The final coat paint color shall be purple as approved by the City. H. Acceptable manufacturers: Tyler Union, Sigma Corporation, Star Pipe Products. Curb Boxes Boxes for curb stops shall be manufactured of heavy cast iron and shall be of the telescopic type with a tar base enamel coating inside and outside. Base of curb boxes shall be Minneapolis type. Covers for curb boxes shall be marked “Reclaimed Water”. 2.24 ARV Boxes Air Release valves shall be installed in a precast manhole in accordance with the Drawings. 2.25 Line Stops - N/A 2.26 Meter Boxes - N/A 2.27 Pipeline Identification Tape Reclaimed Water Distribution System 02512-10 2.28 A. Identification tape shall be an inert plastic film specifically formulated for prolonged underground use. Minimum thickness 4 mils, width 6 inches, letter size 1 inch. Lettering shall be continuous. B. Tape shall be the standard product of a manufacturer regularly engaged in the supply of this tape. Provide tape with adhesive backing for attachment to pipe. C. Identification tape shall be color coded purple with black or yellow lettering "RECLAIMED WATER MAIN". Pipeline Warning Tape Warning tape shall be 6 inch wide vinyl continuous tape, for identification and warning purposes. It shall be color coded purple with black lettering “CAUTION: RECLAIMED WATER MAIN BURIED BELOW”. 2.29 Locating Wire and Tracer Wire A. Locating wire along open cut pipeline shall be color-coded 10 gage continuous insulated wire. Color coding shall be purple. B. Tracer wire along directional bored pipeline shall be color-coded 10 gauge continuous insulated wire, with HDPE jacket (min. thickness of 45 mils) specifically manufactured for use in horizontal directional drill installations. The color of the wire jacket shall be purple. PART 3 EXECUTION 3.01 General Installation Requirements A. All lengths of pipe shall be dimensioned accurately to measurements established at the site, and shall be worked into place without springing or forcing. B. Cut all pipe and drill all holes that may be necessary. Cut sections of pipe shall be reamed or filed to remove all burrs. The pipe interior and joints shall be thoroughly cleaned before being installed and kept clean during construction. C. All changes in direction shall be made with fittings or approved joint deflection. Bending of pipe, except copper and polyethylene, is prohibited. Joint deflection shall not exceed 75 percent of the manufacturer's recommended maximum deflection. D. Any transition from one pipe size to another shall be made with a reducing fitting. Reducing bushings are prohibited except where specifically indicated on the Drawings or approved by the Engineer. E. Make adequate provision for expansion and contraction of piping. F. Trenching, bedding and backfilling shall be in accordance with Section 02320. Reclaimed Water Distribution System 02512-11 3.02 G. Valves shall be installed in all pipe ahead of appliances and equipment not furnished with stops, and elsewhere as required for proper control and isolation of sections of systems for maintenance purposes. H. Minimum cover over pipe shall be 36 inches. Concrete Cradles and Encasement Concrete cradles and encasement shall be as indicated on the Drawings, or as directed by the Engineer. All concrete cradles and anchors shall be of Class B concrete. 3.03 Separation of Non-Potable and Potable Water Lines A. The horizontal separation between water mains and sanitary sewer, storm sewer, wastewater force mains, stormwater force mains, reclaimed water mains and onsite sewage treatment and disposal systems shall be in accordance with the following: 1. 2. 3. B. The outside of water mains shall be a minimum of three feet from the outside of any existing or proposed storm sewer, stormwater force main, vacuum type sanitary sewer and reclaimed water main. The outside of water mains shall be a minimum of six feet from the outside of any existing or proposed gravity sanitary sewer and wastewater force main. The minimum horizontal separation distance between the outside of water mains and the outside of gravity sanitary sewers can be reduced to three feet where the bottom of the water main is at least six inches above the top of the sewer. The outside of water mains shall be a minimum of ten feet from all parts of any existing or proposed onsite sewage treatment and disposal system such as septic tanks, drainfields, and grease traps. Onsite sewage treatment and disposal systems do not include package sewage treatment facilities and public wastewater treatment facilities. The vertical separation between water mains and sanitary and storm sewer, wastewater or stormwater force mains, and reclaimed water mains shall be in accordance with the following: 1. 2. Wherever possible, water mains shall cross over existing or proposed gravity sanitary sewer, vacuum type sanitary sewer, and storm sewer, so the outside of the water main is at least six inches above the outside of the sewer. Where it is not possible for the water main to cross over existing or proposed gravity sanitary sewer, vacuum type sanitary sewer, and storm sewer, then the water main can cross under these types of pipeline systems provided the outside of the water main is at least 12 inches below the outside of the pipeline. At the crossing, the proposed pipe joints shall be arranged so that all water main joints are at least three feet from vacuum type sanitary sewer or storm sewer joints, and at least six feet from gravity sanitary sewer joints. Wherever possible, water mains shall cross over existing or proposed reclaimed water mains, wastewater force mains and stormwater force Reclaimed Water Distribution System 02512-12 mains. Whether the water main crosses over or under these types of pipeline systems, the outside of the water main shall be at least 12 inches from the outside of the existing or proposed reclaimed water main, wastewater force main and stormwater force main. At the crossing, the proposed pipe joints shall be arranged so that all water main joints are at least three feet from reclaimed water main joints and stormwater force main joints, and at least six feet from the joints of wastewater force mains. C. No water main shall pass through or come in contact with any part of a sanitary sewer manhole. D. The following are acceptable alternative construction features to be considered for cost evaluation with no guarantee they will be approved for implementation where it is not possible to meet the separation requirements. Exceptions from meeting the pipe separation requirements, without mitigation, shall be allowed only by FDEP if technical or economic justifications for each exception provided by the Engineer are acceptable to FDEP and are only to be implemented upon receipt of expressed written consent from the Engineer and approval from FDEP on a case by case basis. All possible measures to achieve compliance with the pipe separation requirements shall be considered first along with design changes to meet the requirements before the Engineer submits a justification of an exception to FDEP for approval. Implementation of these measures without the expressed written consent of the Engineer and approval by FDEP could result in the requirement that the installed unapproved measures be removed and replaced at no cost to the City. 1. Where a water main is less than the required minimum horizontal distance from another pipeline or where a water main crosses another pipeline and joints in the water main are less than the minimum required distance between the joints in the other pipeline: a. b. c. 2. Where a water main is less than three feet horizontally from another pipeline or where a water main crosses another pipeline less than the required minimum separation: a. 3.04 Use of pressure rated pipe conforming to AWWA standards for a gravity or vacuum type pipeline. Use of welded, fused, or otherwise restrained joints for either pipeline. Use of watertight casing pipe or concrete encasement at least four inches thick for either pipe. Use of pipe or casing pipe, having high impact strength (at least equal to 0.25 inch thick ductile iron pipe), or concrete encasement at least four inches thick for the water main and for the other pipeline if the other pipeline coveys wastewater or reclaimed water. Plugs Reclaimed Water Distribution System 02512-13 3.05 3.06 3.07 A. Installed piping systems shall be temporarily plugged at the end of each day's work, or other interruption to progress on a given line. Plugging shall be adequate to prevent entry of small animals or persons into the pipe or the entrance or insertion of deleterious materials. B. Standard plugs shall be inserted into all dead-end pipes, tees, or crosses; spigot ends shall be capped; flanged and mechanical joint ends shall have blind flanges of metal. C. Plugs installed for pressure testing shall be blind flanges fully secured and blocked to withstand the test pressure. D. Where plugging is required because of contract division or phasing for later connection, the ends of such lines shall be equipped with a permanent type plug or blind flange. Installation or removal of such plugging shall be considered incidental to the work. Ductile Iron Pipe A. Mechanical joints: install according to the manufacturer's specifications. Socket and gasket shall be clean and gasket shall be properly centered before joint is made. B. Push-On Type Joints: Remove any foreign matter in the gasket seat, wipe gasket clean, flex and place in socket. Apply thin film of lubricant to inside surface of gasket. Complete joint assembly by forcing the plain end of the entering pipe past the gasket until it makes contact with the bottom of the socket. C. Flanged Joints: Bolt flanged joints with care so there is no restraint on the opposite end of the piece, which would prevent pressure from being evenly and uniformly applied upon the gasket. The pipe or fitting must be free to move in any direction while bolting. Gradually tighten bolts, each in turn, at a uniform rate of gasket compression around the entire flange. O-Ring Type Push-On Joints for PVC Pipe A. Clean the pipe end and the bell thoroughly. Insert O-Ring gasket, making certain it is properly oriented. Lubricate the spigot well with an approved lubricant; do not lubricate the bell or O-ring. Insert the spigot end of the pipe carefully into the bell until the reference mark on the spigot is flush with the bell. B. Field cut pipe shall be beveled, have all burrs removed, and shall have a reference mark applied the correct distance from the end. Butt Heat Fusion Joints for PE (Polyethylene) Pipe A. Equipment for butt heat fusion joints shall be as recommended by the pipe manufacturer. Reclaimed Water Distribution System 02512-14 B. 3.08 3.09 Carefully face pipe ends and check for squareness prior to heating ends. Apply clamps as necessary to match outside pipe end diameters. Follow the pipe manufacturer's recommendations concerning temperature, melt time, heat soak times, and joining time. Maintain joining pressure until pipe has cooled to a temperature of 150-160 degrees F. Handle pipe carefully until joint has returned to ambient temperature. Inspect all joints carefully for any irregularities; cut out and re-do all defective joints. Socket Heat Fusion for PE (Polyethylene) Pipe A. Equipment for socket heat fusion shall be as recommended by the pipe manufacturer. B. Bevel the pipe end and remove burrs before making joint. Clean heating tool thoroughly and, if tool is not Teflon coated, spray with a silicone release solution. Heat tool to the temperature recommended by the pipe manufacturer. Place both pipe and fitting on the tool until the correct degree of melt is achieved. Remove pipe and fitting from the tool simultaneously and insert the pipe squarely into the fitting; do not turn pipe or fitting during insertion. Avoid any movement of the joint for 10 to 15 seconds. Handle pipe carefully until the joint has returned to ambient temperature. Polyethylene Pipe Joining (4 Inches and Larger Pipe) A. Joints between plain end pipes and fittings shall be made by butt fusion, and joints between the main and saddle branch fittings shall be made using saddle fusion using only procedures that are recommended by the pipe and fitting manufacturer. The Contractor shall ensure that persons making heat fusion joints have received training in the manufacturer's recommended procedure. The Contractor shall maintain records of trained personnel, and shall certify that training was received not more than 12 months before commencing construction. External and internal beads shall not be removed. B. Upon request, the manufacturer shall provide training in the manufacturer's recommended butt fusion and saddle fusion procedures to the Contractor's installation personnel, and to inspectors representing the City. C. Mechanical joints are only allowed where joining polyethylene pipe to another material. Mechanical couplings shall be fully pressure rated and fully thrust restrained such that when installed in accordance with manufacturer's recommendations, a longitudinal load applied to the mechanical coupling will cause the pipe to yield before the mechanical coupling disjoins. External joint restraints shall not be used in lieu of fully restrained mechanical couplings. Mechanical joints and flange connections shall be installed in accordance with the manufacturer's recommended procedure. Flange faces shall be centered and aligned to each other before assembling and tightening bolts. In no case shall the flange bolts be used to draw the flanges into alignment. Bolt threads shall be lubricated, and flat washers shall be fitted under the flange nuts. Bolts shall be evenly tightened according to the tightening pattern and torque step recommendations of the manufacturer. At least 1 hour after initial assembly, Reclaimed Water Distribution System 02512-15 flange connections shall be re-tightened following the tightening pattern and torque step recommendations of the manufacturer. The final tightening torque shall be 100 ft-lbs or less as recommended by the manufacturer. D. Branch connections to the main shall be made with saddle fittings or tees. Polyethylene saddle fittings shall be saddled fused to the main pipe per Heat Fusion Joining. 3.10 Polyethylene Encasement Installation – N/A 3.11 Buried and Exposed Valves 3.12 A. Buried valves 6 inch diameter and larger shall be set on a foundation of solid concrete or stone not less than 8 inches thick nor less than one cubic foot in volume. Foundations shall be set on firmly compacted ground. B. The height of the valve and its supporting foundation shall conform to the height of the connecting pipe. Valves shall be set in a vertical position, except where indicated on the Drawings or as determined in the field to require a horizontal installation as determined by the Engineer and City. Where valves are required to be installed in a horizontal position, provide with a bevel gear side actuator. C. Exposed valves shall be installed in a vertical position wherever possible. Unless otherwise indicated or directed by the Engineer, valve stems shall never be below a horizontal position. D. Open and close each valve observing full operation prior to installing successive lengths of pipe. Air Release Valves Air release valves shall be placed at high points of the pipeline to permit escape of trapped air and at locations indicated on the Drawings. The valve size, location and method of installation shall be indicated on the Drawings or as directed by the Engineer. 3.13 Valve Boxes and Curb Boxes A. Boxes shall rest on the valve and shall be adjusted so that the cover may be set flush with paving; in areas without paving, set the cover as directed by the Engineer. Boxes shall be set to allow equal movement above and below finish grade. B. The base of the box shall be centered over the valve, and the top of the base section shall be approximately on line with the nut on top of the valve stem. The entire assembly shall be plumb. 3.14 Line Stops - N/A 3.15 Meter Boxes - N/A Reclaimed Water Distribution System 02512-16 3.16 Installation of Identification and Warning Tape A. Install identification tape on all pipelines. Place tape as follows: 1. 2. 3. 3.17 3.18 2 inch through 8 inch diameter pipe - center along top half of pipe 10 inch through 18 inch diameter pipe - place along both sides of the top half of pipe 20 inch diameter and larger pipe - place on both sides of top half of pipe with a third strip centered along top half of pipe B. Place tape from joint to joint on every section of pipe. C. Install warning tape along all pipelines. Install 2 feet above pipe, minimum of 1 foot below grade. Locator and Tracer Wire A. Install locator wire along all pressurized pipelines 4 inch diameter and larger. B. Terminate locator wires at top of the valve box with 12 inches of extra wire. C. Install required tracer wire along polyethylene pipe prior to pulling through bore hole. Tape wire to pipe every 5 feet minimum along the pipeline. D. Test the locate wire and tracer for continuity and submit report documenting the continuity testing. Repair or replace locate wire at failed test locations as directed by the City. Testing General Requirements A. Hydrostatic testing shall be in accordance with AWWA C600 (Ductile iron water mains), AWWA C605 (PVC water mains) and ASTM F2164 (polyethylene water mains). B. Test procedures and method of disposal of water shall be approved by the Engineer. All tests shall be made in the presence of the Engineer and the City. Preliminary tests made by the Contractor without being observed by the Engineer will not be accepted. Notify the Engineer and the City at least 48 hours before any work is to be inspected or tested. C. All defects in piping systems shall be repaired and/or replaced and retested until acceptable. Repairs shall be made to the standard of quality specified for the entire system. D. Sections of the system may be tested separately, but any defect which may develop in a section previously tested and accepted shall be promptly corrected and retested. Pressure tests shall be made between valves to demonstrate ability of valves to sustain pressure. Reclaimed Water Distribution System 02512-17 3.19 E. Provide all necessary test equipment. Increments on gages used for pressure pipe testing shall be of scaled to the nearest 1 psi. Gages, pumps, and hoses shall be in good working order with no noticeable leaks. F. Tests for any exposed piping shall be made before covering and insulation is placed. G. The pressure and leakage test for buried piping shall be made after all jointing operations are completed and restraints have been in place at least seven days. Lines tested before backfill is in place shall be retested after compacted backfill is placed. H. All service connections to reclaimed water mains shall be completed prior to testing. I. Sections of piping between valves and other short sections of line may be isolated for testing. If shorter sections are tested, test plugs or bulkheads required at the ends of the test section shall be furnished and installed by Contractor, together with all anchors, braces, and other devices required to withstand the hydrostatic pressure without imposing any thrust on the pipe line. Contractor shall be solely responsible for any damage that results from the failure of test plugs or supports. J. All items including valves and controls shall be given a thorough test. The entire system shall be operated for two days to prove compatibility of equipment and to achieve proper adjustment for operation. Valves, pipes, tanks, and other items that are non-operating or occasional-operating shall be tested for ability to meet design criteria. Sequence of Testing and Disinfection A. The sequence of testing and disinfection shall be as follows: 1. 2. 3.20 Conduct pressure and leakage testing. Perform flushing. Pressure and Leakage Testing (PVC and DI Mains) A. Piping shall be slowly filled with water and all air expelled. Care shall be taken that all air valves are installed and open in the section being filled, and that the rate of filling does not exceed the venting capacity of the air valves. B. Apply hydrostatic test pressure of 150 psi for 10 minutes and for such additional period necessary for the Engineer to complete the inspection of the line under test. Do not exceed pipe manufacturer's suggested time duration at the test pressure. If defects are noted, repairs shall be made and the test repeated until all parts of the line withstand the test pressure. C. Apply leakage test pressure of 150 psi. Maintain pressure at a maximum variation of 5 percent during the entire leakage test. The duration of the leakage Reclaimed Water Distribution System 02512-18 test shall be two hours minimum, and for such additional time necessary for the Engineer to complete inspection of the section of line under test. Leakage measurements shall not be started until a constant test pressure has been established. The line leakage shall be measured by means of a water meter installed on the supply side of the pressure pump. 3.21 D. No leakage is allowed in exposed piping, buried piping with flanged, threaded, or welded joints or buried non-potable piping in conflict with potable water lines. E. The testing allowance shall be defined as the quantity of water that must be applied to the pipe section being tested to maintain a pressure within 5 psi of the specified hydrostatic test pressure. No installation will be accepted if the quantity of makeup water is greater than that determined by the following formula: L= S x D x P 0.5 148,000 L S D P = = = = Testing Allowance (quantity of makeup water) in gallons per hour Length of line being tested, in feet Nominal internal diameter (in inches) of the pipe. The average test pressure during the pressure test, in pounds per square inch (gauge) This actual pressure shall be determined by finding the difference between the average elevation of all tested pipe joints and the elevation of the pressure gauge and adding the difference in elevation head to the authorized test pressure. F. All leaks shall be repaired by removing and replacing defective pipe and joints with pipe and joints free of defects, after which the lines shall be retested. Such repair and retesting shall be done until the lines pass the specified retest. G. All apparent leaks discovered within one year from the date of final acceptance of the work by the City shall be located and repaired by Contractor, regardless of the total line leakage rate. Pressure and Leakage Testing (Polyethylene Mains) A. Conduct hydrostatic pressure testing of installed polyethylene pipe in accordance with ASTM F2164 and as indicated herein. B. Piping shall be slowly filled with water and all air expelled. Care shall be taken that all air valves are installed and open in the section being filled, and that the rate of filling does not exceed the venting capacity of the air valves. C. Subject pipeline to be tested to a 4 hour expansion phase prior to commencing leakage testing. Pipeline expansion shall be accomplished by applying hydrostatic test pressure of 150 psi. In order to compensate for the initial expansion of the pipeline, add sufficient make-up water at hourly intervals to return to the required test pressure. At the end of the fourth hour, the test phase is to commence. Reclaimed Water Distribution System 02512-19 D. At the conclusion of the fourth hour of the expansion phase, fill the pipeline again with makeup water to return to the test pressure. The test phase shall consist of a two hour or three hour pressure test, as required by the Engineer. At the end of the test phase, measure the amount of makeup water required to return to the test pressure. The pipeline passes the pressure test if the makeup water required does not exceed the following: Nominal Pipe Size (In) 2 4 6 8 10 12 16 18 20 3.22 Allowable Makeup Water (Gallons / 100 Ft Of Pipeline) Two Hour Test Three Hour Test 0.11 0.19 0.25 0.4 0.6 0.9 1.0 1.5 1.3 2.1 2.3 3.4 3.3 5.0 4.3 6.5 5.5 8.0 D. If any defects or leaks are revealed, they should be corrected and the pipeline retested after a minimum 24 hour recuperation period between tests. Total testing conducted on a section of pipeline shall not exceed 8 hours within a 24 hour period. E. All apparent leaks discovered within one year from the date of final acceptance of the work by the City shall be located and repaired by Contractor, regardless of the total line leakage rate. Placing the Reclaimed Water Main Into Service The reclaimed water main can only be placed into service upon approval by the City. END OF SECTION Reclaimed Water Distribution System 02512-20 Proposed Wastewater Treatment Plant No. 2 Civil Drawings HAMMOCK BEACH ESTATES N SECTION 37 THE SANTUARY SECTION 15 SECTION 10 HAMMOCK SHORES LIMITS OF WATER SERVICE AREA SECTION 14 SECTION 35 SECTION 9 4B DUNES COMMUNITY DEVELOPMENT DISTRICT 4A 3C 6B 3B 3D THE OAKS/ PALM HARBOR CITY LIMITS LINE SECTION 7 SEC.5 6A EE SECTION 12 SECTION 8 HAMMOCK DUNES BB HAMMOCK ON THE RIVER SECTION 1 LIMITS OF WATER SERVICE AREA PALM COAST WWTF LOCATION 3A WTP NO. 1 SECTION 11 AA IA C10 CC SECTION 13 IC C1 C8 81N C5 C7 C6 IB C4 FORREST PARK 81E,F C2 DD C9 C3WWTP. SECTION 21 81A,B,C 81M SECTION 20 SECTION 25 WASTEWATER SERVICE AREA SECTION 18 SECTION 22 WASTEWATER SERVICE AREA SECTION 19 SECTION 27 SECTION 24 PALM COAST PLANTATION SECTION 23 SECTION 32 SECTION 26 OCEAN CITY U SECTION 30 SECTION 33 CITY LIMITS LINE SECTION 31 SECTION 28 SECTION 29 G-1 G-2 G-3 C-1 C-2 C-3 C-4 C-5 C-6 C-7 C-8 C-9 C-10 C-11 C-12 C-13 C-14 C-15 C-16 C-17 C-18 C-19 C-20 C-21 C-22 C-23 C-24 C-25 Structural Drawings S-0 S-0.1 S-0.2 S-1 S-2 S-3.1 S-3.2 S-3.3 S-3.4 S-3.5 S-4 S-5 S-6 S-7 S-8 S-9 S-10 S-11 S-12 S-13 S-14 S-15 Cover Sheet Index Of Sheets, Standard Abbreviations, and Location Map General Notes Survey - Cover Sheet Survey - Boundary Survey - Wetland Locations Existing Topography Site Dimension Plan Site Grading Plan Paving, Grading, and Drainage Details Erosion Control Plan Erosion Control Notes and Details General Piping Symbols Overall Piping Plan Site Piping Plan Site Piping Plan Site Piping Plan Site Piping Plan Site Piping Plan Site Piping Plan Site Piping Plan Site Piping Plan Yard Piping Details 1 Yard Piping Details 2 Yard Piping Details 3 Miscellaneous Piping Details 1 Miscellaneous Piping Details 2 Miscellaneous Civil Details LEHIGH R.R Landscape Drawings C11 SECTION 34 C12 BUNNELL FLAGLER BEACH C13 FLAGLER COUNTY AIRPORT Standard Abbreviations AL. or ALUM. ASPH. Ba.V. BLDG. BM BT B.V. CFS CIP or CI CONC. CONST. CONT. CMU C.V. C.Y. DIA. DIP or DI DOT DR. or DW. EA ED ESM'T EF EFF. ELEC. ELEV. or EL. EQUIP. EXIST. EXP. EXT. EW FD FDOT F.E. F.F. FLEX. FLG. FM GALV. GM GPM GS GSP G.V. HB HORIZ. HP HWL ID I.D. INF. I.P. INV. L.F. MANF. MATL. Aluminum Asphalt Ball Valve Building Bench Mark Buried Telephone Butterfly Valve Cubic Feet Per Second Cast Iron Pipe Concrete Construction Continued Concrete Masonry Unit Check Valve Cubic Yards Diameter Ductile Iron Pipe Dept. Of Transportation Drive Or Driveway Each Equipment Drain Easement Each Face Effluent Electrical Elevation Equipment Existing Expansion Extended Each Way Floor Drain Florida Department of Transportation Fire Extinguisher Finish Floor Flexible Flanged Force Main Galvanized Gas Main Gallons Per Minute Galvanized Steel Galvanized Steel Pipe Gate Valve Hose Bibb Horizontal Horsepower High Water Level Identification Inside Diameter Influent Iron Pipe Invert Linear Feet Manufacturer Material CITY OF PALM COAST - WASTEWATER TREATMENT PLAN NO. 2 - CPH JOB NO. P61117.27A Index of Sheets Vicinity Map MAX. MG MGD NG NPW NTS NWL OC OD OH. E. PAV PE PL. PP PROP. PT P.V. PVC PVMT. PW R RAS RCP RED. REINF. Reuse RT. RWM R/W SAN S.F. SPEC. STA. SQ. SS STN. STL. SWD SW (S/W). S.Y. T TBM TOF TRANS. TYP. UE UG UT VCP VAC. VERT. WAS W.L. W.F. WM Maximum Million Gallons Million Gallons Per Day Natural Grade Non-potable Water Not To Scale Normal Water Level On Center Outside Diameter Overhead Electric Reinforced Concrete Pipe Plain End Plate Power Pole Proposed Pressure Treated Plug Valve Polyvinyl Chloride Pavement Potable Water Radius Return Activated Sludge Reinforced Concrete Pipe Reducer Reinforced Required Reuse Water Right Reclaimed Water Main Right-of-way Sanitary Square Feet Specification Station Square Stainless Steel Stainless Steel Side Water Depth Sidewalk Square Yards Telephone Cable Temporary Benchmark Top Of Floor Transformer Typical Underground Electric Underground Underground Telephone Vitrified Clay Pipe Vacuum Vertical Waste Activated Sludge Water Line Water Fountain Water Main L-1 L-2 L-3 L-4 L-5 L-6 IR-1 IR-2 IR-3 IR-4 IR-5 IR-6 6 Overall Landscape Plan Landscape Plan Landscape Plan Landscape Plan Landscape Plan Landscape Notes & Details Overall Irrigation Plan Irrigation Plan Irrigation Plan Irrigation Plan Irrigation Plan Irrigation Notes & Details Mechanical Drawings M-1 M-2 M-3 M-4 M-5 M-6 M-7 M-8 M-9 M-10 M-11 M-12 M-13 M-14 M-15 M-16 M-17 M-18 M-19 M-20 M-21 M-22 M-23 M-24 M-25 M-26 M-27 M-28 M-29 M-30 M-31 M-32 M-33 M-34 M-35 M-36 M-37 M-38 M-39 M-40 M-41 M-42 M-43 M-44 M-45 M-46 M-47 M-48 M-49 M-50 Process Flow Schematic Hydraulic Profile Headworks - (First Floor) Mechanical Plan Headworks - (Second Floor) Mechanical Plan Headworks - Mechanical Section Headworks - Odor Control Layout Headworks - Plant Service Water Influent Meter, Composite Sampler, and Dumpster Housing Details Biological Processes Tanks - Mechanical Plan Equalization Tank Sections and Details Equalization Pumps - Mechanical Plan and Details AXR Pumps - Mechanical Plan and Details IRQ Pumps - Mechanical Plan and Details Aeration and RAS Details Scum Pump Plan and Details Scum Pump Details Biological Processes Tanks - Miscellaneous Details Biological Processes Tanks - Miscellaneous Details MBR Tanks/RAS Pumps/Blowers - Mechanical Plan MBR Tanks/RAS Pumps/Blowers - Mechanical Sections 1 MBR Tanks/RAS Pumps/Blowers - Mechanical Sections 2 MBR Tanks/RAS Pumps/Blowers - Membrane Cleaning Dosing Station Details Chlorine Contact Chambers - Mechanical Plan Chlorine Contact Chambers - Mechanical Sections Sluice Gate Details Quality Control Valve Station Reclaimed Water Distribution Pump Station - Mechanical Plan Reclaimed Water Distribution Pump Station - Mechanical Sections and Details Reclaimed Water Recycling Pump Station Sludge Holding Tanks - Mechanical Plan Sludge Holding Tanks - Mechanical Sections Sludge Holding Tanks - Miscellaneous Mechanical Details EQ and Sludge Holding Tank Blowers - Mechanical Plan and Details Belt Filter Press Sludge Feed Pump Station - Mechanical Plan and Details Sludge Dewatering Building - Mechanical Plan Sludge Dewatering Building - Mechanical Sections Sludge Dewatering Building - Mechanical Sections Sludge Dewatering Building - Belt Filter Press Details Micro CG Storage and Feeding System - Mechanical Plan Sodium Hypoclorite/Alum Feed System Building - Mechanical Plan Sodium Hypoclorite/Alum and Micro CG Feed System - Details Micro CG Feed System - Sections In-Plant Pump Station Piping Supports and Miscellaneous Details Stair Details Sludge Holding Tanks Stair Details Biological Processes Tanks (East Staircase) Stair Details Biological Processes Tanks (North Staircase) Ground Storage Tank - Plan and Details Ground Storage Tank - Section and Details Ground Storage Tank - Miscellaneous Details S-16 S-17 S-18 S-19 S-20 S-21 S-22 S-23 S-24 Structural Notes Typical Details Typical Details Biological Processes Tanks - Foundation Plan Biological Processes Tanks - Top Slab Framing Plan Biological Processes Tanks - Structural Sections Biological Processes Tanks - Structural Sections Biological Processes Tanks - Structural Sections Biological Tank/Headworks Bridge - Structural Plans Biological Tank/Headworks Bridge - Structural Plans Chlorine Contact Chambers - Foundation Plan Chlorine Contact Chambers - Top Slab Framing Plan Chlorine Contact Chambers - Structural Sections Chlorine Contact Chambers - Structural Sections Chlorine Contact Chambers - Structural Sections Sludge Holding Tanks 1 and 2 - Foundation Plan Sludge Holding Tanks 1 and 2 - Structural Sections Headworks - Foundation Plan and Sections Headworks - Top Slab Framing Plan and Sections Workshop Building - Structural Plans Workshop Building - Structural Sections Reclaimed Water Distribution Pump Station MCC Building Structural Plans Chemical Feed Building - Structural Plans Sludge Dewatering Building - Foundation Plan Sludge Dewatering Building - Roof Framing Plan Sludge Dewatering Building - Structural Sections Main Electrical MCC Building - Structural Plans Main Electrical MCC Building - Structural Sections Emergency Generator Building Foundation Plan and Sections Dumpster Housing Structural Plans Dumpster Housing Typical Details and Structural Sections Architectural Drawings 1A-1 1A-2 1A-3 1A-4 1A-5 1A-6 1A-7 1A-8 1A-9 1A-10 1A-11 1A-12 1A-13 2A-1 2A-2 2A-3 2A-4 2A-5 2A-6 3A-1 3A-2 3A-3 3A-3 4A-1 4A-2 5A-1 5A-2 5A-3 5A-4 5A-5 5A-6 Sludge Dewatering Building - General Information Sludge Dewatering Building - Life Safety Plan, Key Plan Sludge Dewatering Building - Floor Plan Sludge Dewatering Building - Elevations Sludge Dewatering Building - Elevations Sludge Dewatering Building - Building Section Sludge Dewatering Building - Building Section Sludge Dewatering Building - Roof Plan Sludge Dewatering Building - Schedules Sludge Dewatering Building - Wall Sections Sludge Dewatering Building - Restroom Plan and Elevations Sludge Dewatering Building - Reflected Ceiling Plan Sludge Dewatering Building - ADA Requirements Main Electrical MCC Building - Life Safety Plan, Key Plan Main Electrical MCC Building - Floor Plan / Ceiling Plan Main Electrical MCC Building - Roof Plan / Building Section Main Electrical MCC Building - Elevations Main Electrical MCC Building - Wall Sections Main Electrical MCC Building - Schedules Reclaimed Water Distribution Pump Station MCC Building Life Safety Plan Reclaimed Water Distribution Pump Station MCC Building Floor Plan, Elevs, Sect Reclaimed Water Distribution Pump Station MCC Building Roof Details, Wall Section Reclaimed Water Distribution Pump Station MCC Building Schedules Chemical Feed Building - Flr Plan / Key Plan/ Elev Chemical Feed Building - Roof Plan / Sections Workshop Building - Life Safety Plan Workshop Building - Floor Plan Workshop Building - Roof Plan, Reflected Ceiling Plan Workshop Building - Elevations, Section Workshop Building - Elevations, Section Workshop Building - Schedules Electrical Drawings E-01 E-02 E-03 E-04 E-05 E-06 E-07 E-08 E-09 E-10 E-11 E-12 E-13 E-14 E-15 E-16 E-17 E-18 E-19 E-20 E-21 E-22 E-23 E-24 E-25 E-26 E-27 Electrical Symbols, Abbreviations and Notes Overall Electrical Site Plan Ductbank Sections Generator Building - 480 Volts Single Line Diagram Main Electrical MCC Building - Single Line Diagram Switchgear Control Diagrams MCC-1 Single Line Diagram MCC-1 Single Line Diagram MCC-2 Single Line Diagram MCC-2 Single Line Diagram MCC-3 and MCC-4 Single Line Diagrams MCC-5 Single Line Diagram MCC-6 Single Line Diagram Switchboard Front View Switchboard Front View (Continued) MCC-1 & MCC-2 Front Views Future MCC-1B &Mcc-2B Front Views MCC-3 Thru MCC-6 Equipment Front Views Control Wiring Diagram Elementary Diagrams-1 Elementary Diagrams-2 Elementary Diagrams-3 Emergency Generator Building Power Plan Main Electrical Building No.1 Power Plan Main Electrical Building No.1 Lighting Plan Main Electrical Building No.1 Lightning Protection and Grounding Plan Headworks Electrical Plans E-28 E-29 E-30 E-31 E-32 E-33 E-34 E-35 E-36 E-37 E-38 E-39 E-40 E-41 E-42 E-43 E-44 E-45 E-46 E-47 E-48 E-49 E-50 E-51 E-52 E-53 E-54 E-55 Biological Process Tanks Electrical Plan Biological Processes Tanks Lower Level Electrical Plan Biological Processes Tanks Lower Level Lighting Plan and Quality Control Valve Station Electrical Plan Chlorine Contact Chambers Electrical Plan Reclaimed Water Distribution Pump Station Electrical Building No.2 Power Plan Reclaimed Water Distribution Pump Station Electrical Building No.2 Lighting Plan Reclaimed Water Distribution Pump Station Electrical Building No.2 Lightning Protection and Grounding Plan Reclaimed Water Distribution Pump Station Electrical Plan In-Plant Duplex Pumping Station Electrical Plan and Reclaimed Ground Storage Tank Partial Electrical Plan In-Plant Station Details Micro CG Storage and Feeding System Electrical Plan WWTP Chemical Feed Building Electrical Plan Chemical Feed Building Lighting and Lightning Protection/ Grounding Plan Sludge Dewatering Building Power Plan Sludge Dewatering Building Lighting Plan Sludge Dewatering Building Lightning Protection/ Grounding Plan Sludge Holding Tanks No.1 & 2 Electrical Plan Workshop Building Electrical Plan Workshop Building Lighting Plan Workshop Building Grounding and Lightning Protection Plan RO Membrane Building Electrical Room Power Plan Panel Schedules - 1 Panel Schedules - 2 Lighting Fixture Schedules and Details Electrical Details-1 Electrical Details-2 Electrical Details-3 Electrical Details-4 "THIS IS TO CERTIFY THAT THE DESIGN REFLECTED IN THE PLANS AND SPECIFICATIONS REPRESENT SOUND ENGINEERING PRINCIPLES AND IS CONSISTENT WITH THE APPLICABLE REQUIREMENTS OF THE FLORIDA ADMINISTRATIVE CODE" Fire Alarm FA-01 FA-02 FA-03 FA-04 Fire Alarm Riser Diagram Legend and Notes Main Electrical MCC Building - Fire Alarm Plan Sludge Dewatering Building - Fire Alarm Plan Reclaimed Water Distribution Pump Station MCC Building Fire Alarm Plan FA-05 Workshop Building - Fire Alarm Plan HVAC Drawings H-01 H-02 H-03 H-04 H-05 H-06 HVAC Notes, Legend and Abbreviations Sludge Dewatering Building - HVAC Plan Emergency Generator Building - HVAC Plan Main Electrical Room - HVAC Plan Reclaimed Water Distribution Pump Station MCC Building HVAC Plan HVAC Details and Schedules (C.O.A. No. 3215) (Lic. No. AA2600926) (L.B. No. 7143) (Lic. No. LC0000298) Instrumentation Drawings I-01 I-02 I-03 I-04 I-05 I-06 I-07 I-08 I-09 I-10 Instrumentation Notes and Legend Process & Instrumentation Diagram - Influent Process & Instrumentation Diagram - Primary Process & Instrumentation Diagram - MBR Tanks Process & Instrumentation Diagram - Effluent Process & Instrumentation Diagram - RAS/WAS and Blowers Process & Instrumentation Diagram - Solids Treatment Process & Instrumentation Diagram - NaOCI and Alum Systems Process & Instrumentation Diagram - Micro C-G System Process Control System Simplified Block Diagram Plumbing Drawings P-01 P-02 P-03 Plumbing Legend and Details Sludge Dewatering Building - Plumbing Plan Emergency Generator Building - Fuel Piping Plan C 2015 INDEX OF SHEETS, STANDARD ABBREVIATIONS, AND LOCATION MAP Wastewater Treatment Plant No. 2 Sheet No. No. Date 6 12-11-15 By ADDENDUM 6 JCS JOB# P61117.27A DATE: DECEMBER, 2015 YINHUI XU, PhD., P.E. c 2015 72186 Drawing name: J:\P61117.27A\Civil\DWG\Design\PLANT No2\PLNT_STRUCT\S-24.dwg Dec 17, 2015 - 9:19am jshoemaker HIGGENBOTHAM BID SET No. Date Revision By No. 1 5 2 6 3 7 4 8 Date 12/4/15 Revision ADDENDUM NO. 6 By DD Offices In: Florida Puerto Rico Connecticut Maryland Texas Designed by: Drawn by: HGH RED Checked by: HGH Approved by: Job No. Scale: AS NOTED HGH P61117.27A Plans Prepared By: Date: 12/4/2015 C 2015 Wastewater Treatment Plant No. 2 CPH, Inc. 500 West Fulton St. Sanford, Fl. 32771 Phone: 407.322.6841 Licenses: Eng. C.O.A. No. 3215 Arch. Lic. No. AA2600926 Survey L.B. No. 7143 Landscp. Lic. No. LC0000298 DUMPSTER HOUSING TYP.DETAILS AND STRUCTURAL SECTIONS REG.# 56467 Sheet No. Drawing name: J:\P61117.27A\Civil\DWG\Design\PLANT No2\PLNT_STRUCT\S-23.dwg Dec 17, 2015 - 9:18am jshoemaker GIRT REMOVAL DUMPSTER HOUSING - Foundation Plan ROTARY SCREEN DUMPSTER HOUSING - Foundation Plan SCALE: 3/8" = 1'-0" SCALE: 3/8" = 1'-0" HIGGENBOTHAM GIRT REMOVAL DUMPSTER HOUSING - Top Slab Framing Plan ROTARY SCREEN DUMPSTER HOUSING - Top Slab Framing Plan SCALE: 3/8" = 1'-0" SCALE: 3/8" = 1'-0" BID SET No. Date Revision By No. 1 5 2 6 3 7 4 8 Date Revision By 12/4/15 ADDENDUM NO. 6 DD Offices In: Florida Puerto Rico Connecticut Maryland Texas Designed by: Drawn by: HGH RED Checked by: HGH Approved by: Job No. Scale: AS NOTED HGH P61117.27A Plans Prepared By: Date: 12/4/2015 C 2015 Wastewater Treatment Plant No. 2 Sheet No. CPH, Inc. 500 West Fulton St. Sanford, Fl. 32771 Phone: 407.322.6841 Licenses: Eng. C.O.A. No. 3215 Arch. Lic. No. AA2600926 Survey L.B. No. 7143 Landscp. Lic. No. LC0000298 DUMPSTER HOUSING STRUCTURAL PLANS REG.# 56467 Drawing name: J:\P61117.27A\Civil\DWG\Design\PLANT No2\PLNT_STRUCT\S-22.dwg Dec 17, 2015 - 9:17am jshoemaker HIGGENBOTHAM BID SET No. Date Revision By No. 1 5 2 6 3 7 4 8 Date 12/4/15 Revision ADDENDUM NO. 6 By DD Offices In: Florida Puerto Rico Connecticut Maryland Texas Designed by: Drawn by: HGH RED Checked by: HGH Approved by: Job No. Scale: AS NOTED HGH P61117.27A Plans Prepared By: Date: 12/4/2015 C 2015 Wastewater Treatment Plant No. 2 CPH, Inc. 500 West Fulton St. Sanford, Fl. 32771 Phone: 407.322.6841 Licenses: Eng. C.O.A. No. 3215 Arch. Lic. No. AA2600926 Survey L.B. No. 7143 Landscp. Lic. No. LC0000298 EMERGENCY GENERATOR BUILDING FOUNDATION PLAN AND SECTIONS REG.# 56467 Sheet No. Piping Legend 56'-8" 2 1 1 POLYMER DISTRIBUTION BLOCK B 3 EXHAUST FAN 4 20 14 19 6 7 ALUMINUM TREADS 1'-4" HANDRAIL 26 SLOPE 5 8" D.I. WYE, FLG. 6 8" PLUG VALVE 7 8" x 6" D.I. REDUCER, FLG. 8 12" D.I.P. 9 EL 37.75 1 10 DEWATERED SLUDGE PROG. CAVITY PUMP WITH STAINLESS STEEL HOPPER MOUNTED TO BFP DISCHARGE CHUTE 11 8" x 5" D.I. REDUCER, FLG 12 8" D.I. BLIND FLG W/ 2" THRD OUTLET 13 3/4" POLYMER TUBING IN 4" PVC SLEEVE MOUNTED TO TRENCH WALL 14 4" PVC SLEEVE FOR POLYMER TUBING 16'-0" 14'-0" 3 8'-6" POLYMER INJECTION RING ON RISER. POLYMER MIXER ON RISER. SEE "SECTION B" ON SHEET "SLUDGE DEWATERING BUILDING MECHANICAL SECTIONS 2 ALUMINUM GRATING ALUMINUM SLOPE HB 2 15 AIR COMPRESSOR 12" 1 2 PRESS CONTROL PANEL WASHWATER BOOSTER PUMPS SEE DETAIL THIS SHEET REUSE WATER SUPPLY LINE 8" DIP 14 GROUT TRENCH BOTTOM AND SLOPE TO DRAIN (TYP.) Electrical Room (16'-0" X 14'-0") 10 29 35'-4" 9 3 1 33 30 34 Unisex Bathroom Storage (9'-11" X 7'-8") EL 37.75 32 A 7 NOTE: SEE PLUMBING PLAN FOR DOMESTIC WATER LINES AND DRAINS IN THIS AREA. (7'-6" x 7'-6") 11 23 6 6 6'-8" 35 COMBINATION EYEWASH AND SHOWER. SEE DETAIL ON SHEET "MECHANICAL PIPING DETAILS" 15 Office/Lab (17'-8" x 10'-6") OVERHEAD DOOR REUSE WATER SUPPLY LINE FOR POLYMER MAKE UP WATER 14 13 17 20 21 WASH HOSE RACK. TYP. FOR 3 LOCATIONS. SEE DETAIL ON SHEET "MECHANICAL PIPING DETAILS" ASPHALT PAVEMENT 1-1/2" SCH. 80 PVC 19 4" PVC REUSE WATER LINE C900 DR18 20 3/4" SCH. 80 PVC 21 1-1/2" GATE VALVE & BOX 22 1" GATE VALVE & BOX 23 2" SS (SCH. 40), THREADED 24 FLANGE COUPLING ADAPTER 25 26 3" SS (SCH. 40), THREADED 27 4" SS FLANGE W/ 2-12" NTP OUTLET 28 3" SS FLANGE W/ 2-12" NTP OUTLET 29 2" GATE VALVE 31 18 2-1/2" SS (SCH. 40), THREADED 33 2-1/2" SS (SCH. 40) TEE, THREADED 34 2-1/2" GATE VALVE 35 1" SCH. 80 PVC Notes: 21'-0" 1. PROVIDE 1" MAX SEPARATION BETWEEN GRATING AND BELT FILTER PRESS EQUIPMENT. DROP 29 SLOPE 30 10'-6" Drawing name: J:\P61117.27A\Civil\DWG\Design\PLANT No2\PLNT_MECH\P61117.27A M-35.dwg Dec 17, 2015 - 8:48am jshoemaker 18 8 SLOPE DROP 2. GRATING TO BE SUPPORTED BY FRAMING SYSTEM WITH FLOOR MOUNTED SUPPORTS AS DESIGNED BY THE GRATING MANUFACTURER. 23 23 1" x 3/4" REDUCER SLUDGE LOADING SCREW CONVEYOR (OVER HEAD). SEE "SECTION B" ON SHEET "SLUDGE DEWATERING BUILDING - MECHANICAL SECTIONS 2" DROP 34 17 30 ASPHALT PAVEMENT SLOPE 23 18 22 18 10'-6" 35 WASHWATER BOOSTER PUMP POTABLE WATER SERVICE 12" HB 20 REUSE WATER SUPPLY LINE 1-1/2" x 1" REDUCER 32 SLOPE SECTION HB 12" 16 OVERHEAD CABINETS BFP POLYMER FEED SYSTEM WATER HEATER ~ END 4" SLEEVE AT 2" ABOVE FINISH FLOOR. TYP. FOR 2 LOCATIONS 16'-8" 8 SLOPE POLYMER TOTE 5'-8" LAB COUNTER 32 GRATING 25'-8" 11'-8" 12" OVERHEAD CABINETS 31 16 SLOPE 13'-2" LOUVER WASHWATER BOOSTER PUMP 3 15 SCREW CONVEYOR MOTOR FDOT TYPE "C" CONCRETE DRAINAGE INLET WITH TRAFFIC BEARING GRATE (H2O LOADING) 3. GRATING FRAMEWORK IS NOT TO BE SUPPORTED BY THE BELT FILTER PRESS EQUIPMENT. 4. ALL GRATING SUPPORTS AND HARDWARE TO BE CORROSION RESISTANT. 30 31 18 28 24 31 32 CONCRETE PAVING. SEE STRUCTURAL DRAWINGS 16" x 16" CONCRETE COLUMN (TYP.) SEE STRUCTURAL DRAWINGS 25 5. NO SINGLE PIECE OF GRATING SHALL WEIGH NO MORE THAN 80 POUNDS. 6. OVERHEAD PIPE SUPPORT BEAMS TO BE INCORPORATED INTO BUILDING DESIGN. CEILING MOUNTED HANGING PIPE SUPPORTS ON ALL OVERHEAD PIPING. PIPING SUPPORTS TO BE 10' ON CENTER, MAX. 26 7. ALL PIPE INSTALLED UNDER THE SLAB SHALL BE CONCRETE ENCASED TO A DISTANCE OF 5' OUTSIDE OF THE BUILDING. 35'-4" 24 No. Date 1 12-17-15 27 Washwater Booster Pumps Detail Sludge Dewatering Building Plan SCALE: 1/2" = 1'-0" SCALE: 1/4" = 1'-0" Revision By No. ADDENDUM 6 JCS 5 2 6 3 7 4 8 Date Revision By Offices In: Florida Puerto Rico Connecticut Maryland Texas Designed by: Drawn by: YCL JCS Checked by: YX Approved by: Job No. YX P61117.27A C 2015 CROSS REFERENCE SHEET TITLE SECTION A SECTION B SLUDGE DEWATERING BUILDING - MECHANICAL SECTIONS 1 SLUDGE DEWATERING BUILDING - MECHANICAL SECTIONS 2 Plans Prepared By: Date: 12/17/2015 Scale: AS NOTED SEC/DET Wastewater Treatment Plant No. 2 CPH, Inc. 500 West Fulton St. Sanford, Fl. 32771 Phone: 407.322.6841 Licenses: Eng. C.O.A. No. 3215 Arch. Lic. No. AA2600926 Survey L.B. No. 7143 Landscp. Lic. No. LC0000298 YINHUI XU, PhD., P.E. FL. P.E. NO. 72186 SLUDGE DEWATERING BUILDING MECHANICAL PLAN Sheet No. TO HEADWORKS N 6 3 6 4 3 REFERENCE DETAIL 3 7 2 7 7 REFERENCE DETAIL 1 7 26 4" X 9" BLOCKOUT BENEATH CONCRETE WALKWAY 2 24 55.50 EQUALIZATION TANK NO. 1 ANAEROBIC TANK NO. 1 24 35.00 21 18 52.21 MBR TANK NO. 1 51.72 10' FIXED WEIR BAFFLE PLATE MIXER 23 26 26 22 20 MIXER 10' FIXED WEIR 55.50 17 48.50 1'-6" 7' FIXED WEIR POST ANOXIC NO. 1 6' FIXED WEIR 53.00 4 OXIC TANK NO. 1 16' FIXED WEIR 55.50 2' SLUICE GATE PRE ANOXIC NO. 1 1 24 55.50 1 55.50 24 24 22 19 2 52.79 MIXER 2 22 MIXER 20 20 55.50 22 20 7 TROUGH 55.50 MIXER 1 55.50 55.50 3X MBR TANK NO. 2 1 STOP GATE 2 55.50 20 20 24 MIXER MIXER 22 24 PRE ANOXIC NO. 2 52.79 24 16' FIXED WEIR 17 22 24 MIXER POST ANOXIC NO. 2 OXIC TANK NO. 2 4 55.50 20 55.50 55.50 EQUALIZATION TANK NO. 2 1'-6" 53.00 26 20 23 51.72 22 MIXER 21 35.00 MBR TANK NO. 3 2 2' SLUICE GATE 2" SCH. 80 PVC PEMEATE VENT PIPING ANAEROBIC TANK NO. 2 10' FIXED WEIR 2' SLUICE GATE REFERENCE SLUICE GATE DEATILS (TYP.) BOTTOM 35.0 11'-0" x 10'-0" 18 2 2 MBR TANK NO. 4 26 55.50 7 2" SCH. 80 PVC PEMEATE VENT PIPING 3 BAFFLE PLATE 52.21 10' FIXED WEIR FINISHED GRADE 39.50 CHEMICAL PIPING UNDER CONCRETE WALKWAY SEE SECTIONS S AND T 6' FIXED WEIR 7' FIXED WEIR MIXER MBR DISTRIBUTION 25 22 2" SCH. 80 PVC PEMEATE VENT PIPING 2 35.00 4" X 6" BLOCKOUT BENEATH CONCRETE WALKWAY 2" SCH. 80 PVC PEMEATE VENT PIPING 26 3 7 7 Drawing name: J:\P61117.27A\Civil\DWG\Design\PLANT No2\PLNT_MECH\P61117.27A M-9 M-17 M-19~M-22.dwg Dec 17, 2015 - 11:31am jshoemaker 1 1 3 Plan View - Biological Process Tanks PIPING SCHEDULE No. SCALE: 1/8" = 1'-0" 1 1 1/2" PVC PLANT SERVICE WATER 12 3/4" PVC GLOBE VALVE 23 MIXER AND RAIL FURNISHED AND INSTALLED BY CONTRACTOR 2 1" HOSE BIB & HOSE RACK 13 3/4" X 3/8" PVC REDUCER 24 2'-6" X 1'-6" X 12" DEEP SUMP WITH 6" D.I.P. 3 2" PVC PLANT SERVICE WATER 14 3/8" MICRO C-G FLOW METER 4 2" PVC MICRO C-G 15 3/8" ALUM FLOW METER 5 2" PVC MICRO C-G 16 6 1 1/2" PVC ALUM 7 ATTACH VERTICAL PIPING TO CONCRETE WITH THREE 1 1/2"x 1/16" S.S. BAND ATTACHED WITH 1 4" DIAMETER S.S. EXP ANCHOR 17 MICRO C-G SIMILAR TO SECTIONS S AND T 18 MICRO C-G AND ALUM FEED POINT 19 26 2" PVC MICRO C-G AND 1 1/2" ALUM 1 12" X 116" S.S. BAND ATTACH TO CONCRETE WITH 14" DIAMETER 2" X 2" X 3/4" PVC TEE 9 1 1/2" X 1 1/2" X 3/4" PVC TEE 20 EMBED FOR MIXER HOIST FURNISHED BY OVIVO INSTALLED BY CONTRACTOR 10 3/4" PVC MICRO C-G 21 EMBED FOR MIXER HOIST FURNISHED AND INSTALLED BY CONTRACTOR 11 3/4" PVC ALUM 22 MIXER AND RAIL FURNISHED BY OVIVO INSTALLED BY CONTRACTOR Revision By No. 1 5 2 6 3 7 4 25 MIXER EMBED FOR REMOVAL OF STOP GATE. EMBED TO BE FURNISHED AND INSTALLED BY THE CONTRACTOR. 8 Date * 8 Date Revision By 12-17-15 ADDENDUM 6 JCS Offices In: Florida Puerto Rico Connecticut Maryland Texas Designed by: Drawn by: YCL JCS Checked by: YX Approved by: Job No. YX P61117.27A C 2015 CROSS REFERENCE SHEET TITLE SECTION A SECTION B SECTION C SECTION D SECTION E SECTION F SECTION G SECTION H SECTION I SECTION K SECTION M SECTION X 1 THIS SHEET THIS SHEET THIS SHEET THIS SHEET THIS SHEET THIS SHEET PROCESS TANKS MISCELLANEOUS DETAILS 2 PROCESS TANKS MISCELLANEOUS DETAILS 2 PROCESS TANKS MISCELLANEOUS DETAILS 2 PROCESS TANKS MISCELLANEOUS DETAILS 2 PROCESS TANKS MISCELLANEOUS DETAILS 2 THIS SHEET THIS SHEET Plans Prepared By: Date: 12/17/2015 Scale: AS NOTED SEC/DET Wastewater Treatment Plant No. 2 CPH, Inc. 500 West Fulton St. Sanford, Fl. 32771 Phone: 407.322.6841 Licenses: Eng. C.O.A. No. 3215 Arch. Lic. No. AA2600926 Survey L.B. No. 7143 Landscp. Lic. No. LC0000298 YINHUI XU, PhD., P.E. FL. P.E. NO. 72186 BIOLOGICAL PROCESS TANKS MISCELLANEOUS DETAILS Sheet No. Match Line - C-15 for Continuation Match Line - C-18 for Continuation 6 NOTE NO.1 6 0 20 10 GRAPHIC SCALE Note: 1. EXISTING PVC GRAVITY SEWER TO REMAIN IN SERVICE FOR DURATION OF CONSTRUCTION. Drawing name: J:\P61117.27A\Civil\DWG\Design\PLANT No2\PLNT_CIVIL\P61117.27A C-11~C-19.dwg Dec 18, 2015 - 1:30pm jshoemaker 6 6 6 6 6 6 6 No. Date Revision By No. 1 5 2 6 3 7 4 8 Date Revision By 12-17-15 ADDENDUM 6 JCS Offices In: Florida Puerto Rico Connecticut Maryland Texas Designed by: Drawn by: YCL JCS Checked by: YX Approved by: YX Job No. P61117.27A Plans Prepared By: Date: 12/18/2015 Scale: AS NOTED C 2015 Wastewater Treatment Plant No. 2 Sheet No. CPH, Inc. 500 West Fulton St. Sanford, Fl. 32771 Phone: 407.322.6841 Licenses: Eng. C.O.A. No. 3215 Arch. Lic. No. AA2600926 Survey L.B. No. 7143 Landscp. Lic. No. LC0000298 SITE PIPING PLAN YINHUI XU, PhD., P.E. FL. P.E. NO. 72186 6 6 6 6 Match Line - C-13 and C-14 for Continuation 6 Drawing name: J:\P61117.27A\Civil\DWG\Design\PLANT No2\PLNT_CIVIL\P61117.27A C-11~C-19.dwg Dec 17, 2015 - 4:37pm jshoemaker 6 6 0 10 20 GRAPHIC SCALE Match Line - C-19 for Continuation No. Date Revision By No. 1 5 2 6 3 7 4 8 Date Revision By 12-17-15 ADDENDUM 6 JCS Offices In: Florida Puerto Rico Connecticut Maryland Texas Designed by: Drawn by: YCL JCS Checked by: YX Approved by: YX Job No. P61117.27A Plans Prepared By: Date: 12/17/2015 Scale: AS NOTED C 2015 Wastewater Treatment Plant No. 2 Sheet No. CPH, Inc. 500 West Fulton St. Sanford, Fl. 32771 Phone: 407.322.6841 Licenses: Eng. C.O.A. No. 3215 Arch. Lic. No. AA2600926 Survey L.B. No. 7143 Landscp. Lic. No. LC0000298 SITE PIPING PLAN YINHUI XU, PhD., P.E. FL. P.E. NO. 72186 Match Line - C-15 for Continuation Match Line - C-16 for Continuation 6 0 20 10 GRAPHIC SCALE Drawing name: J:\P61117.27A\Civil\DWG\Design\PLANT No2\PLNT_CIVIL\P61117.27A C-11~C-19.dwg Dec 18, 2015 - 1:29pm jshoemaker 6 6 6 6 6 6 6 No. Date Revision By No. 1 5 2 6 3 7 4 8 Date Revision By 12-17-15 ADDENDUM 6 JCS Offices In: Florida Puerto Rico Connecticut Maryland Texas Designed by: Drawn by: YCL JCS Checked by: YX Approved by: YX Job No. P61117.27A Plans Prepared By: Date: 12/18/2015 Scale: AS NOTED C 2015 Wastewater Treatment Plant No. 2 Sheet No. CPH, Inc. 500 West Fulton St. Sanford, Fl. 32771 Phone: 407.322.6841 Licenses: Eng. C.O.A. No. 3215 Arch. Lic. No. AA2600926 Survey L.B. No. 7143 Landscp. Lic. No. LC0000298 SITE PIPING PLAN YINHUI XU, PhD., P.E. FL. P.E. NO. 72186 Match Line - C-14 for Continuation Match Line - C-17 for Continuation 0 20 10 GRAPHIC SCALE Drawing name: J:\P61117.27A\Civil\DWG\Design\PLANT No2\PLNT_CIVIL\P61117.27A C-11~C-19.dwg Dec 17, 2015 - 4:35pm jshoemaker 6 6 6 6 6 6 6 No. Date Revision By No. 1 5 2 6 3 7 4 8 Date Revision By 12-17-15 ADDENDUM 6 JCS Offices In: Florida Puerto Rico Connecticut Maryland Texas Designed by: Drawn by: YCL JCS Checked by: YX Approved by: YX Job No. P61117.27A Plans Prepared By: Date: 12/17/2015 Scale: AS NOTED C 2015 Wastewater Treatment Plant No. 2 Sheet No. CPH, Inc. 500 West Fulton St. Sanford, Fl. 32771 Phone: 407.322.6841 Licenses: Eng. C.O.A. No. 3215 Arch. Lic. No. AA2600926 Survey L.B. No. 7143 Landscp. Lic. No. LC0000298 SITE PIPING PLAN YINHUI XU, PhD., P.E. FL. P.E. NO. 72186 Match Line - C-19 for Continuation Match Line - C-16 and C-17 for Continuation Match Line - C-14 for Continuation 6 0 20 10 GRAPHIC SCALE Drawing name: J:\P61117.27A\Civil\DWG\Design\PLANT No2\PLNT_CIVIL\P61117.27A C-11~C-19.dwg Dec 18, 2015 - 1:34pm jshoemaker 6 6 6 6 6 6 6 No. Date Revision By No. 1 5 2 6 3 7 4 8 Date Revision By 12-17-15 ADDENDUM 6 JCS Offices In: Florida Puerto Rico Connecticut Maryland Texas Designed by: Drawn by: YCL JCS Checked by: YX Approved by: YX Job No. P61117.27A Plans Prepared By: Date: 12/18/2015 Scale: AS NOTED C 2015 Wastewater Treatment Plant No. 2 Sheet No. CPH, Inc. 500 West Fulton St. Sanford, Fl. 32771 Phone: 407.322.6841 Licenses: Eng. C.O.A. No. 3215 Arch. Lic. No. AA2600926 Survey L.B. No. 7143 Landscp. Lic. No. LC0000298 SITE PIPING PLAN YINHUI XU, PhD., P.E. FL. P.E. NO. 72186 Match Line - C-18 for Continuation Match Line - C-16 for Continuation Match Line - C-13 for Continuation 6 6 6 Match Line - C-15 for Continuation 0 10 20 GRAPHIC SCALE Drawing name: J:\P61117.27A\Civil\DWG\Design\PLANT No2\PLNT_CIVIL\P61117.27A C-11~C-19.dwg Dec 17, 2015 - 4:33pm jshoemaker 6 6 6 6 6 6 6 No. Date Revision By No. 1 5 2 6 3 7 4 8 Date Revision By 12-17-15 ADDENDUM 6 JCS Offices In: Florida Puerto Rico Connecticut Maryland Texas Designed by: Drawn by: YCL JCS Checked by: YX Approved by: YX Job No. P61117.27A Plans Prepared By: Date: 12/17/2015 Scale: AS NOTED C 2015 Wastewater Treatment Plant No. 2 Sheet No. CPH, Inc. 500 West Fulton St. Sanford, Fl. 32771 Phone: 407.322.6841 Licenses: Eng. C.O.A. No. 3215 Arch. Lic. No. AA2600926 Survey L.B. No. 7143 Landscp. Lic. No. LC0000298 SITE PIPING PLAN YINHUI XU, PhD., P.E. FL. P.E. NO. 72186 6 6 Match Line - C-18 for Continuation 6 6 6 6 Match Line - C-14 for Continuation 0 20 10 GRAPHIC SCALE Drawing name: J:\P61117.27A\Civil\DWG\Design\PLANT No2\PLNT_CIVIL\P61117.27A C-11~C-19.dwg Dec 17, 2015 - 4:33pm jshoemaker 6 6 6 6 6 6 6 No. Date Revision By No. 1 5 2 6 3 7 4 8 Date Revision By 12-17-15 ADDENDUM 6 JCS Offices In: Florida Puerto Rico Connecticut Maryland Texas Designed by: Drawn by: YCL JCS Checked by: YX Approved by: YX Job No. P61117.27A Plans Prepared By: Date: 12/17/2015 Scale: AS NOTED C 2015 Wastewater Treatment Plant No. 2 Sheet No. CPH, Inc. 500 West Fulton St. Sanford, Fl. 32771 Phone: 407.322.6841 Licenses: Eng. C.O.A. No. 3215 Arch. Lic. No. AA2600926 Survey L.B. No. 7143 Landscp. Lic. No. LC0000298 SITE PIPING PLAN YINHUI XU, PhD., P.E. FL. P.E. NO. 72186 6 Match Line - C-13 for Continuation 0 20 10 GRAPHIC SCALE Drawing name: J:\P61117.27A\Civil\DWG\Design\PLANT No2\PLNT_CIVIL\P61117.27A C-11~C-19.dwg Dec 17, 2015 - 4:32pm jshoemaker 6 6 6 6 6 6 6 No. Date Revision By No. 1 5 2 6 3 7 4 8 Date Revision By 12-17-15 ADDENDUM 6 JCS Offices In: Florida Puerto Rico Connecticut Maryland Texas Designed by: Drawn by: YCL JCS Checked by: YX Approved by: YX Job No. P61117.27A Plans Prepared By: Date: 12/17/2015 Scale: AS NOTED C 2015 Wastewater Treatment Plant No. 2 Sheet No. CPH, Inc. 500 West Fulton St. Sanford, Fl. 32771 Phone: 407.322.6841 Licenses: Eng. C.O.A. No. 3215 Arch. Lic. No. AA2600926 Survey L.B. No. 7143 Landscp. Lic. No. LC0000298 SITE PIPING PLAN YINHUI XU, PhD., P.E. FL. P.E. NO. 72186 Drawing name: J:\P61117.27A\Civil\DWG\Design\PLANT No2\PLNT_CIVIL\P61117.27A C-11~C-19.dwg Dec 17, 2015 - 4:31pm jshoemaker 6 6 6 6 6 6 6 No. Date Revision By No. 1 5 2 6 3 7 4 8 Date Revision By 12-17-15 ADDENDUM 6 JCS Offices In: Florida Puerto Rico Connecticut Maryland Texas Designed by: Drawn by: YCL JCS Checked by: YX Approved by: Job No. Scale: AS NOTED YX P61117.27A Plans Prepared By: Date: 12/17/2015 C 2015 Wastewater Treatment Plant No. 2 Sheet No. CPH, Inc. 500 West Fulton St. Sanford, Fl. 32771 Phone: 407.322.6841 Licenses: Eng. C.O.A. No. 3215 Arch. Lic. No. AA2600926 Survey L.B. No. 7143 Landscp. Lic. No. LC0000298 YINHUI XU, PhD., P.E. FL. P.E. NO. 72186 OVERALL PIPING PLAN 12 12 4 4 OPEN SOUTH ELEVATION NORTH ELEVATION KEYNOTES : STANDING SEAM METAL ROOFING Drawing name: J:\P61117.27A\Architecture\01_Architectural\P61117.27 WWTP No.2, Palm Coast\CAD Drawings\WorkShop Building\Architectural\5A.5 Elevations.dwg Dec 18, 2015 - 11:20am gcleavenger DRIP EDGE ROOF CONSTRUCTION: 24 G.A. PRE-FINISHED KYNAR 500 STEEL STANDING SEAM ROOF SYSTEM OVER 40# PEEL & STICK OVER 1/4" G-P DENSDECK DURAGUARD W/ CONCEALLED CLIPS. INSTALL OVER 1.5" RIGID POLYISOCYANURATE INSULATION OVER 1.5" METAL DECK OVER P.E. METAL TRUSSES. MANUFACTURER TO PROVIDE COMPLETE SYSTEM OF ACCESSORIES, INCLUDING CLIPS, FLASHINGS, DRIP EDGE AND CLOSURES. ACCEPTABLE PRODUCTS FOR ROOFING SYSTEM: "SNAP-CLAD 16" BY PETERSEN ALUMINUM CORPORATION OR EQUIVALENT. ALUM BREAK METAL FASCIA 6" X 1-1/2" PLASTER TRIM BAND 1 HR FIRE SEPARATION 5/8" GWB ON BOTH SIDES OF 3 58" METAL STUD @ 16" O.C. PROVIDE DRAFT FACE PAPER BACKED INSULATION ON WARM SIDE(GARAGE) LIGHT SPANISH TEXTURE STUCCO FINISH DRAFT STOP 1/2" DENS-GLASS ON PRE-ENGINEERED" METAL TRUSS. PROVIDE KRAFT FACE PAPER BACKED INSULATION ON THE WARM SIDE (GARAGE) ALUMINUM DOUBLE DOOR (REFER TO DOOR SCHEDULE) 1/2"X 1/2" STUCCO REVEAL (5) # 10 TEK SCREWS (SEE STRUCTURAL) 12" 12" 4" STUCCO CONTROL JOINT 4" PRE-ENGINEERED ROOF TRUSSES ALUMINUM SINGLE DOOR (REFER TO DOOR SCHEDULE) CONCRETE STOOP. (SEE FLOORPLAN) ENVOY SOLID DOUBLE 6" PVC COATED U-GROOVE SOFFIT CODE; SAX12219T NON-VENTIALTED OVER 2-1/2" C-FURRING @ 16" O.C. 1 2" "" TYPE A: CMU WALL CONSTRUCTION: EPOXY PAINT ON 8" CONCRETE BLOCK WALL WITH LADDER TYPE HORIZONTAL JOINT REINFORCE (EQUIV. TO "DUR-O-WALL") AT 16" C.C VERT. PROVIDE FULL HEIGHT #5 VERT. BARS IN GROUT FILL AT BOTH SIDES OF ALL WINDOWS AND DOORS OPENINGS, IN 3 CELLS AT ALL MASS.. CORNERS AT 48" C/C THROUGHOUT. PROVIDE CORE FILL 500 TAILORED FOAM INSULATION IN MASONRY WALLS.ITERIOR SURFACE TO BE PAINTED. TYPE A: CMU WALL CONSTRUCTION:5/8" STUCCO (3-COATS) WITH LIGHT SPANISH TEXTURE ON 8" CONCRETE 6 BLOCK WALL WITH LADDER TYPE HORIZONTAL JOINT REINFORCE (EQUIV. TO "DUR-O-WALL") AT 16" C.C VERT. PROVIDE FULL HEIGHT #5 VERT. BARS IN GROUT FILL AT BOTH SIDES OF ALL WINDOWS AND DOORS OPENINGS, IN 3 CELLS AT ALL MASS.. CORNERS AT 48" C/C THROUGHOUT. PROVIDE CORE FILL 500 TAILORED FOAM INSULATION IN MASONRY WALLS.ITERIOR SURFACE TO BE PAINTED. PROVIDE 24"X48" WHITE ACOUSTICAL CEILING TILES IN WHITE 1" T-BAR METAL SUSPENSION SYSTEM. ENVOY SOLID DOUBLE 6" PVC COATED U-GROOVE SOFFIT CODE; SAX12219T NON-VENTIALTED OVER 2-1/2" C-FURRING @ 16" O.C. PRO-BEAD 8" NON-VENTILATED (VINYL) SOFFIT, 0.040" THK, MATTE FIN, WHITE ENVOY SOLID DOUBLE 6"ALUM PVC COATED U-GROOVE SOFFIT CODE; SAX12219T NON-VENTIALTED. DOUBLE KNOCK-OUT BLOCK, REFER TO STRUCTURAL LINTEL, REFER TO STRUCTURAL SLOPE 4" 1/4"=1'-0" FINISH GRADE FLOOR SLAB CONSTRUCTION: 8" THICK. 3000 P.S.I.. CONCRETE FLOOR SLAB W/6X6 W1.4 X W1.4 ON 10 MIL POLYETHYLENE VAPOR BARRIER (LAPPED AND SEALED) ON PREPARED SUBGRADE W/TERMITE-TREATED COMPACTED FILL PER GEOTHECNICAL REPORT. REFER TO STRUCTURAL DRAWINGS FOR DETAILS. GARAGE DOOR 16 X 16 R.C. COLUMN (SEE STRUCTURAL PLAN) WALL SECTION No. Date Revision By No. 1 5 2 6 3 7 4 8 Date Revision BUILDING SECTION By Offices In: · Florida · Puerto Rico · Connecticut · Maryland · Texas Designed by: Drawn by: VQT SI/KM Checked by: VQT/GC Approved by: Job No. Scale: AS NOTED VQT P61117.27A Plans Prepared By: Date: 12/18/2015 C 2015 Wastewater Treatment Plant No. 2 WORKSHOP BUILDING CPH, Inc. 500 West Fulton St. Sanford, Fl. 32771 Phone: 407.322.6841 Licenses: Eng. C.O.A. No. 3215 Arch. Lic. No. AA2600926 Survey L.B. No. 7143 Landscp. Lic. No. LC0000298 VICTOR Q. TAN, AIA DATE ELEVATIONS/ SECTION Sheet No. ROOF CONSTRUCTION: PRE-FIN. 24 G.A. KYNAR 500 STEEL STANDING SEAM ROOF SYSTEM OVER 1/4" G-P DENSDECK DURAGUARD & 1.5" RIGID POLYISOCYANURATE INSULATION W/ CONCEALLED CLIPS, INSTALLED ABOVE ROOF MEMBRANE. FABRICATE PANELS FROM NO. 24 MSG GALV. STEEL PANELS. PROVIDE CONCEALLED 18 MSG GALV. STEEL CLIPS W/ SCREW SPACING AS SPECIFIED BY MFR. FOR U.L. CLASS 90 WIND UPLIFT RESISTANCE. PROVIDE W/ MFR'S COMPLETE SYSTEM OF ACCESSORIES, INCLUDING CLIPS, FLASHINGS, DRIP EDGE AND CLOSURES. ACCEPTABLE PRODUCTS FOR ROOFING SYSTEM: "SNAP-CLAD 16" BY PETERSEN ALUMINUM CORPORATION, OR APPROVED EQUAL. 7/8"(3 COATS) THK STUCCO FINISH OVER 1/2" DENSGLASS GOLD BACK TO BACK ON METAL FRAMING PROVIDE INSULATION. 12 4 RIDGE HEIGHT ELEVATION 119'-4" ROOF MEMBRANE: PROVIDE 40 MIL. PEEL AND STICK ROOF MEMBRANE, WITH WEATHERTIGHT EDGE AND END LAPS. INSTALL TO PROVIDE COMPLETE WATERTIGHT PERFORMANCE, INCLUDING ADDITIONAL SEALANT AT PENETRATIONS AND FLASHING LOCATIONS. ACCEPTABLE PRODUCTS INCLUDE "ICE & WATER SHIELD" BY W.R. GRACE, AND "STORM GUARD" BY GAF. 1-1/2" TYPE B GAGE G90 GALV. STEEL STRUCTURAL DECK,SCREWED TO GALV. STEEL TRUSSES PER STRUCTURAL DRAWINGS. SEE STRUCTURAL DRAWINGS FOR FRAME , SUB-FRAME @ 16" O.C. AND SUB-DECK DETAILS. TRUSS BEARING ELEVATION 113'-4" 1/2" THICK DENS GLASS GOLD ON METAL STUDS TYPE A: CMU WALL CONSTRUCTION:5/8" STUCCO (3-COATS) WITH LIGHT SPANISH TEXTURE ON 8" CONCRETE 6 BLOCK WALL WITH LADDER TYPE HORIZONTAL JOINT REINFORCE (EQUIV. TO "DUR-O-WALL") AT 16" C.C VERT. PROVIDE FULL HEIGHT #5 VERT. BARS IN GROUT FILL AT BOTH SIDES OF ALL WINDOWS AND DOORS OPENINGS, IN 3 CELLS AT ALL MASS.. CORNERS AT 48" C/C THROUGHOUT. PROVIDE CORE FILL 500 TAILORED FOAM INSULATION IN MASONRY WALLS.ITERIOR SURFACE TO BE PAINTED. PROVIDE 24"X24" WHITE CEILING TILES IN WHITE 1" T-BAR METAL SUSPENSION SYSTEM. SEE STRUCTURAL AS REQUIRED FLOOR SLAB CONSTRUCTION: 8" THICK. 3000 P.S.I.. CONCRETE FLOOR SLAB W/6X6 W1.4 X W1.4 ON 10 MIL POLYETHYLENE VAPOR BARRIER (LAPPED AND SEALED) ON PREPARED SUBGRADE W/TERMITE-TREATED COMPACTED FILL PER GEOTHECNICAL REPORT. REFER TO STRUCTURAL DRAWINGS FOR DETAILS. 2" EAVE FLASHING W/FINISH TO MATCH ROOFING PANEL SYTEM. COMPLY W/ METAL ROOFING MFR'S RECOMMENDED DETAIL FOR FIELD CUTTING AND BENDING BOTTOM EDGE OF ROOF PANEL TO HOOK OVER RETURN LEG ON EAVE FLASHING (INSTALLED W/ SEALANT). ACCEPTABLE PRODUCTS INCLUDE "PA-126 EAVE FLASHING AND PA-5 KEEPER" BY PETERSEN ALUMINUM CORPORATION, OR EQUIVALENT BY MBCI. PRE-ENGINEERED ROOF TRUSSES EQUAL EQUAL FINISH FLOOR LINE ELEVATION 100'-0" CONTIN. 10" x 24 GA. PRE-FINISHED STEEL FASCIA FOR HORIZONTAL RUNNERS BETWEEN TRUSS TAILS. SECURE BLOCKING TO TRUSS TAILS W/ GALV. CLIP ANGLES W/ MIN. (2) 1" SCREWS AT EA. LEG. .040 FASCIA AND FLASHING SOFFIT SYSTEM TO MATCH ROOF PANEL, FORMED W/ BOTTOM DRIP EDGE W/ CONCEALED CLIPS. SPLICE JOINTS TO BE BUTTED W/ CONCEALED BACK PLATE AND ADHESIVE SEALANT IN JOINT. 2'-0" PRO-BEAD 8" NON VENTILATED SOFFIT, 0.040" THK, MATTE FIN, WHITE (VINYL) 5/8" (3 COATS) STUCCO FINISH OVER 8" CONCRETE BLOCK WALL PAINT OVER CMU EAVES DETAIL BUILDING SECTION Drawing name: J:\P61117.27A\Architecture\01_Architectural\P61117.27 WWTP No.2, Palm Coast\CAD Drawings\Main Electrical Building\Architectural\2A.3 Bldg Sect.dwg Dec 18, 2015 - 11:19am gcleavenger PREFINISHED RIDGE/HIP COPING SEALANT PREFINISHED J-CHANNEL STEEL BAR ROOF JOIST REFER TO STRUCTURAL DRAWINGS FOR DETAILS. KYNAR 500 PRE-FINISH STANDING SEAM ME ROOFING SYSTEM BY "SNAP-CLAD 16" PETE ALUMINUM CORP. RIDGE HEIGHT ELEVATION 119'-4" 1/4" G-P DENS-DECK 1.5" RIGID POLYISOCYANURATE INSULATION CONCEALLED CLIPS, INSTALLED OVER STEE DECK 12 TRUSS BEARING ELEVATION 113'-4" 4 TYPE A: CMU WALL CONSTRUCTION:5/8" STUCCO (3-COATS) WITH LIGHT SPANISH TEXTURE ON 8" CONCRETE BLOCK WALL WITH LADDER TYPE HORIZONTAL JOINT REINFORCE (EQUIV. TO "DUR-O-WALL") AT 16" C.C VERT. PROVIDE FULL HEIGHT #5 VERT. BARS IN GROUT FILL AT BOTH SIDES OF ALL WINDOWS AND DOORS OPENINGS, IN 3 CELLS AT ALL MASS.. CORNERS AT 48" C/C THROUGHOUT. PROVIDE CORE FILL 500 TAILORED FOAM INSULATION IN MASONRY WALLS.ITERIOR SURFACE TO BE PAINTED. PROVIDE 24"X24" WHITE CEILING TILES IN WHITE 1" T-BAR METAL SUSPENSION SYSTEM. SIM 3 2 FINISH FLOOR LINE ELEVATION 100'-0" RIDGE DETAIL No. Date Revision By No. 1 5 2 6 3 7 4 8 FLOOR SLAB CONSTRUCTION: 4" THICK. 3000 P.S.I.. CONCRETE FLOOR SLAB W/6X6 W1.4 X W1.4 ON 10 MIL POLYETHYLENE VAPOR BARRIER (LAPPED AND SEALED) ON PREPARED SUBGRADE W/TERMITE-TREATED COMPACTED FILL PER GEOTHECNICAL REPORT. REFER TO STRUCTURAL DRAWINGS FOR DETAILS. BUILDING SECTION Date Revision By 12-17-15 ADDENDUM 6 GEC Offices In: · Florida · Puerto Rico · Connecticut · Maryland · Texas Designed by: Drawn by: VQT SI/KM Checked by: VQT/GC Approved by: Job No. Scale: AS NOTED VQT P61117.27A Plans Prepared By: Date: 12/18/2015 C 2015 Wastewater Treatment Plant No. 2 MAIN ELECTRICAL MCC BUILDING CPH, Inc. 500 West Fulton St. Sanford, Fl. 32771 Phone: 407.322.6841 Licenses: Eng. C.O.A. No. 3215 Arch. Lic. No. AA2600926 Survey L.B. No. 7143 Landscp. Lic. No. LC0000298 VICTOR Q. TAN, AIA DATE ROOF PLAN/ BLDG SECTION Sheet No. 8" MASONRY WALL CAULK MARK WINDOW SIZE WINDOW MATERIALS FIRE RATING 4'-8" X 4'-0" ALUM/GLASS 6 12''-0" X 10'-0"' ALUM/LOUVER 2-1/2" x 5" E.S.P. ALUM. WINDOWS TO SIT IN ESP. ALUM. PAN FLASHING W/ 1/2" HIGH INSIDE AND OUTSIDE LEGS, 9/16" LAMINATED FIXED GLASS UNLESS OTHERWISE NOTED, AND SCREENS INCLUDED" ANCHORAGE UTILIZING SHEAR BLOCK SYSTEM FOR ALL GLAZING TO BE 1/4" TEMPERED GLASS (REGARDLESS OF LOCATIONS). PROVIDE CONTIN. MASTIC SEALANT BED BELOW PAN FLASHING. ALL GLAZING TO BE SET INTO CONTINUOUS BED OF SILICONE GLAZING SEALANT FOR MAX. BOND STRENGTH. MASONRY OPENING MASONRY OPENING HARDWARE WIDTH HEIGHT GLASS 0 9/16" LAMINATED 4'-8" 0 N/A 12'-0" 6 4'-0" PER MFR. 10'-0" PER MFR. REMARKS FIXED (IMPACT RESISTANT) (IMPACT RESISTANT) 6 WINDOW NOTES: ALUM. STOREFRONT WINDOWS TO SIT IN ESP. ALUM. PAN FLASHING. 9/16" LAMINATEDGLASS IN FIXED UNIT. ANCHOR UTILIZING SHEAR BLOCK SYSTEM FOR ALL GLAZING. PROVIDE CONTIN. MASTIC SEALANT BED BELOW PAN FLASHING. ALL GLAZING TO BE SET INTO CONTINUOUS BED OF SILICONE GLAZING SEALANT FOR MAX. BOND STRENGTH. 6 PROVIDE CULTURED MARBLE SILL AT EACH WINDOW (PER SPECIFICATIONS) DOOR SCHEDULE 6 NOTE: 1. EGRESS DOORS WITH LOCKS SHALL ALSO INCLUDE A READILY VISIBLE SIGN STATING "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED." SIGN SHALL BE IN ONE INCH LETTERS ON CONTRASTING BACKGROUND. 2. ALL EXTERIOR DOORS TO HAVE HINGES WITH NON-REMOVABLE PINS. DOOR NO. LOCATION DOOR FUNCTION TYPE SIZE THK FRAME MATERIAL FINISH TYPE MATERIAL FINISH HARDWARE GROUP REMARKS 01 SLUDGE DEWATERING BUILDING ELECTRICAL ROOM ENTRANCE/EXIT DOOR A 6'-0" x 7'-0" 1 3/4" ALUMINUM PRE-FINISH 1 ALUMINUM PRE-FINISH 2 INSULATED DOUBLE SWING DOOR 02 SLUDGE DEWATERING BUILDING MAIN ENTRANCE DOOR B 3'-0" x 7'-0" 1 3/4" ALUMINUM PRE-FINISH 2 ALUMINUM PRE-FINISH 5 SINGLE SWING DOOR 03 SLUDGE DEWATERING BUILDING OPERATION AREA DOOR E - STEEL MFR N/A MFR MFR 10 ROLL UP STEEL DOOR 6 12'-0" X 10'-0" 6 6 6 04 SLUDGE DEWATERING BUILDING OFFICE B1 3'-0" x 7'-0" 1 3/4" ALUMINUM PRE-FINISH 2 ALUMINUM PRE-FINISH 8 SGL DOOR W/ NARROW LITE VIEW PANEL 05 SLUDGE DEWATERING BUILDING STORAGE ROOM DOOR B1 3'-0" x 7'-0" 1 3/4" ALUMINUM PRE-FINISH 2 ALUMINUM PRE-FINISH 7 SGL DOOR W/ NARROW LITE VIEW PANEL 06 SLUDGE DEWATERING BUILDING ELECTRICAL ROOM DOOR B1 3'-0" X 7'-0" 1 3/4" ALUMINUM PRE-FINISH 2 ALUMINUM PRE-FINISH 6 45 MINUTES FIRE RATED DOOR 07 SLUDGE DEWATERING BUILDING RESTROOM DOOR B2 3'-0" x 7'-0" 1 3/4" H/M PAINTED 2A H/M PAINTED 9 SINGLE SWING DOOR 6 DR HEAD 1 2 4 2A Drawing name: J:\P61117.27A\Architecture\01_Architectural\P61117.27 WWTP No.2, Palm Coast\CAD Drawings\Sludge Building\Architectural\1A.9 Schedules.dwg Dec 18, 2015 - 11:22am gcleavenger 6 ALUM WINDOW HEAD A DR JAMB B B1 B3 B2 DR HEAD 6 ALUM WINDOW SILL No. Date Revision ALUM THRESHOLD By No. 1 5 2 6 3 7 4 8 Date Revision By 12-17-15 ADDENDUM 6 GEC C DR JAMB Offices In: · Florida · Puerto Rico · Connecticut · Maryland · Texas Designed by: Drawn by: VQT SI/KM Checked by: VQT/GC Approved by: Job No. VQT P61117.27A C 2015 E Plans Prepared By: Date: 12/18/2015 Scale: AS NOTED D Wastewater Treatment Plant No. 2 SLUDGE DEWATERING BUILDING CPH, Inc. 500 West Fulton St. Sanford, Fl. 32771 Phone: 407.322.6841 Licenses: Eng. C.O.A. No. 3215 Arch. Lic. No. AA2600926 Survey L.B. No. 7143 Landscp. Lic. No. LC0000298 VICTOR Q. TAN, AIA DATE SCHEDULES Sheet No. X 56'-8" 39'-0" 17'-8" 5'-0" 1'-4" 16'-4" 01 8'-8" 06 9'-3" 7'-5" 6'-0" 5'-0" 6. OVERHEAD PIPE SUPPORT BEAMS TO BE INCORPORATED INTO BUILDING DESIGN TO ALLOW FOR CURRENT AND FUTURE CEILING MOUNTED HANGING PIPE SUPPORTS ON ALL OVERHEAD PIPING. PIPING SUPPORTS TO BE 10' ON CENTER, MAX. F.D. 13'-4" 6 9. ALL PIPE INSTALLED UNDER THE SLAB SHALL BE CONCRETE ENCASED TO A DISTANCE OF 5' OUTSIDE OF THE BUILDING. 20'-4" OVERHEAD CABINETS 8. NOT USED 3/4" PLYWOOD SHELF WITH PLASTIC LAMINATE FINISH 10.CONTRACTOR TO INSTALL THREE (3) POLYMER FEED LINES AND SPOOL PIECES TO THE LOCATIONS REQUIRED BY THE BELT FILTER PRESS MANUFACTURER FOR PROPER OPERATION OF THE BELT FILTER PRESS. H20 HEATER 3/4" PLYWOOD CABINET WITH PLASTIC LAMINATE FINISH 12'-0" SLOPE ADJUSTABLE STANDARD 7. ROOF INSULATION TO BE R-19 MIN., WALLS TO BE R-11 (MIN) 04 POLYMER TOTE 1'x4" WOOD BLOCKING 5. NO SINGLE PIECE OF GRATING SHALL WEIGH NO MORE THAN 80 POUNDS. 8'-4" 3'-4" 05 07 EMERGENCY EYEWASH AND SHOWER (TYP.) ROLL-UP DOOR BACK MOUNTED PULL 6 PROVIDE BLOCKING AT WALL (TYP) 4'-0" LAB COUNTER A1 OVERHEAD CABINETS 12'-8" 3. GRATING FRAMEWORK IS NOT TO BE SUPPORTED BY THE BELT FILTER PRESS EQUIPMENT. 4. ALL GRATING SUPPORTS AND HARDWARE TO BE CORROSION RESISTANT. A1 GRATING SOD 2. GRATING TO BE SUPPORTED BY FRAMING SYSTEM WITH FLOOR MOUNTED SUPPORTS AS DESIGNED BY THE GRATING MANUFACTURER. SLOPE B THERE SHALL BE NO CHANGE IN FINISH FLOOR ELEVATION GREATER THAN 1/2", UNLESS A TRANSITION STRIP OR RAMP IS UTILIZED TO PROVIDE A 1:12 MAX. SLOPE. PROVIDE A CONTIN. TAPERED TRANSITION STRIP WHERE THIN FLOORING SYSTEM (SUCH AS CARPET OR VINYL) ABUTS A THICKER FLOORING SYSTEM (SUCH AS CERAMIC TILE). TRANSITION STRIPS SHALL BE MARBLE WHEN ABUTTING CERAMIC OR QUARRY TILE, AND MAY BE METAL WHEN ABUTTING ONLY CARPET OR VINYL FLOORING. 1. PROVIDE 1" MAX SEPARATION BETWEEN GRATING BELT FILTER PRESS EQUIPMENT. 35'-4" 3'-4" 12'-0" 35'-4" SLOPE GENERAL NOTES RAMP UP 6" A1 3'-4" 15'-0" PRESS CONTROL PANEL 10'-0" 10'-8" A 6 TYPE B: INTERIOR PARTITION CONSTRUCTION: 5/8" GYPSUM BOARD (M.R. IN RESTROOMS, JANITOR AND WET AREAS) EACH SIDE OVER 6" OR 3-5/8" MTL STUD AT 24" O.C. USE 20 GA. STUD UP TO 10' AND 18 GA. FROM 10' TO 14'. SEE STRUCTURAL DRAWINGS FOR TALLER. SOUND ATTENUATION IN REST ROOMS, AND PRIVATE OFFICES. CERAMIC TILE IN BATHROOM UP TO 6'-6". 6'-4" SLOPE AIR COMPRESSOR OPERATIONS PLATFORM BFP POLYMER FEED SYSTEM TYPE A1: INTERIOR CMU WALL CONSTRUCTION: 8" CONCRETE BLOCK WALL WITH LADDER TYPE HORIZONTAL JOINT REINFORCE (EQUIV. TO "DUR-O-WALL") AT 16" C.C VERT. PROVIDE FULL HEIGHT #5 VERT. BARS IN GROUT FILL AT BOTH SIDES OF ALL WINDOWS AND DOORS OPENINGS, IN 3 CELLS AT ALL MASS.. CORNERS AT 32" C/C THROUGHOUT. PROVIDE 1/2" DENS ARMOR PLUS INTERIOR DRYWALL IN OFFICE SIDES OVER 1/2" HAT FURRING CHANNELS AT 16" O.C. AND M.R. DRYWALL IN RESTROOM AND STORAGE AREA. 7'-4" 22'-8" WALLS AND PARTITIONS LEGEND CR 4" 6Ø BOLLARD CONCRETE DRIVEWAY 6Ø BOLLARD 02 03 2'-0" 12'-0" 3'-4" 7'-4" 4'-4" SINK AND FAUCET ; REFER TO PLUMBING DRAWINGS 14'-4" PLASTIC LAMINATE COUNTER WITH 4"H CONTINUOUS BACK SPLASH ROOF LINE ABOVE SMOOTH DOME TOP 6" DIA. X 4'-0" HIGH (8'-0" TOTAL LENGTH) SCHED. 40 GALV. STEEL PIPE BOLLARD, WITH CONC. FILL AND CROWNED CONC. CAP (ALL PAINTED). 6" CONCRETE DUMPSTER PAD 8'-0" 1/2" GWB 27" MIN 6Ø BOLLARD 2'-10" SEALANT 1" PLASTIC LAMINATE VERTICAL SUPPORT @ 3'-0" O.C. TYP. PROVIDE INSULATED PIPE SLEEVES OVER EXPOSED PIPES FIXED PLASTIC LAMINATE BOTTOM SHELF 4'-0" 6Ø BOLLARD CONCRETE DRIVEWAY ENGINEERED FILL 10'-6" SLOPE DRAINAGE INLET, REFER TO CIVIL, STRUCTURAL, AND MEP DRAWINGS 3/4"x2 1/2" SPACER 1" PLYWOOD SUPPORTS EACH SIDE OF SINK 4'-0" SLOPE 1/4" =1'-0" (TYP.) SLOPE 2'-0" PLASTIC LAMINATE COUNTER TOP W/BACKSPLASH AND WITH 6" FRONT PANEL 2'-10" 8'-4" SLOPE 10'-6" 7'-0" 21'-0" 17'-8" 17'-8" 4"H VINYL BASE 6" Drawing name: J:\P61117.27A\Architecture\01_Architectural\P61117.27 WWTP No.2, Palm Coast\CAD Drawings\Sludge Building\Architectural\1A.3 Floor Plan.dwg Dec 18, 2015 - 11:21am gcleavenger 1/2" RECESS 35'-4" 4"H VINYL BASE 24" DIA. 3000 PSI CONCRETE FOOTING FLOOR PLAN 2 1A.3 No. Date Revision By No. 1 5 2 6 3 7 4 8 Date Revision By 12-17-15 ADDENDUM 6 GEC Offices In: · Florida · Puerto Rico · Connecticut · Maryland · Texas Designed by: Drawn by: VQT SI/KM Checked by: VQT/GC Approved by: Job No. SCALE 1/2" =1'-0" C 2015 3 1A.3 SECTION AT SINK SCALE 1/2" =1'-0" 4 1A.3 Plans Prepared By: Date: 12/18/2015 VQT P61117.27A 2 X 4 WOOD BRACING, TYP. 24" PIPE GUARD DETAILS Scale: AS NOTED 1'-10 1/2" 1'-10 1/2" Wastewater Treatment Plant No. 2 SCALE 1/2" =1'-0" SLUDGE DEWATERING BUILDING CPH, Inc. 500 West Fulton St. Sanford, Fl. 32771 Phone: 407.322.6841 Licenses: Eng. C.O.A. No. 3215 Arch. Lic. No. AA2600926 Survey L.B. No. 7143 Landscp. Lic. No. LC0000298 UPPER CABINETS & COUNTER VICTOR Q. TAN, AIA DATE FLOOR PLAN Sheet No.