View - Temperzone

Transcription

View - Temperzone
VRF Multi-split Air Conditioning System
SET-FREE FSN2 Indoor Units
INVERTER-DRIVEN MULTI-SPLIT SYSTEM
Heat Pump Air Conditioners
INVERTER-DRIVEN MULTI-SPLIT SYSTEM
Heat Pump Air Conditioners
Models
Indoor Units
Technical Catalogue
for Indoor Unit
In-the-Ceiling Type
RPI-0.8FSN2
RPI-1.0FSN2
RPI-2.0FSN2
RPI-2.5FSN2
RPI-4.0FSN2
RPI-5.0FSN2
RPI-8FSN
RPI-10FSN
RPI-1.5FSN2
RPI-3.0FSN2
4-Way Cassette Type
RCI-1.0FSN2
RCI-1.5FSN2
RCI-2.5FSN2
RCI-3.0FSN2
RCI-5.0FSN2
RCI-2.0FSN2
RCI-4.0FSN2
2-Way Cassette Type
RCD-1.0FSN2
RCD-1.5FSN2
RCD-2.5FSN2
RCD-3.0FSN2
RCD-5.0FSN2
RCD-2.0FSN2
RCD-4.0FSN2
Wall Type
RPK-1.0FSNSM2 RPK-1.5FSNSM2
RPK-2.5FSNSM2 RPK-3.0FSNSM2
Floor Type
RPF-1.0FSN2E
RPK-2.0FSNSM2
RPK-4.0FSNSM2
RPF-1.5FSN2E
Floor Concealed Type
RPFI-1.0FSN2E
RPFI-1.5FSN2E
Ceiling Type
RPC-2.0FSN2
RPC-4.0FSN2
RPC-2.5FSN2
RPC-5.0FSN2
RPC-3.0FSN2
System Equipment
Total Heat Exchangers
KPI-2521
KPI-5021
KPI-8021
KPI-10021
SET-FREE FSN2 Indoor Units
TIPS ON ENERGY EFFICIENT VRF DESIGN
TIP No 1:
Shorter pipe run will
minimize capacity loss
and reduce refrigerant
charge in system.
TIP No 2:
Take advantage
of diversity factor
will reduce your
initial capital as
well as ongoing
running cost.
TIP No 3:
Each zone served
by dedicated
unit will help to
increase comfort
level and reduce
Energy waste.
TIPS ON ENERGY EFFICIENT VRF DESIGN
TIP No 4:
Heat recovery system will
not only provide simultaneous
cooling and heating, but also
recover energy that would
be lost in traditional system.
TIP No 5:
Having minimum
Change Over box in same
zone will prevent units
from fighting against each
others and save energy.
TIP No 6:
Unbalanced selection
will cause small unit
starve from Refrigerant
and run longer than
it should be.
CONTENTS
Technical Data
Items
1. Features
Page
1-5
1.1 System Features
1-5
1.2 Features on Indoor Unit
1-12
1.2.1
In-the-Ceiling Type
1-12
1.2.2
4-Way Cassette Type
1-13
1.2.3
2-Way Cassette Type
1-16
1.2.4
Wall Type
1-18
1.2.5
Floor Type
1-20
1.2.6
Floor Concealed Type
1-20
1.2.7
Ceiling Type
1-21
1.3 Features on Total Heat Exchangers
1-22
1.4 Features on Optional Liquid Crystal Remote Control Switch,
Wireless Remote Control Switch, Half Size Remote Control Switch,
7-Day Timer and Central Stations
1-23
1.4.1
Lineup
1-23
1.4.2
Liquid Crystal Remote Control Switch, PC-AR (Optional)
1-23
1.4.3
Wireless Remote Control Switch, PC-LH3A (Optional)
1-25
1.4.4
Half Size Remote Control Switch, PC-ARH (Optional)
1-26
1.4.5
7-Day Timer, PSC-A1T (Optional)
1-27
1.4.6
Central Station, PSC-5S (Optional) and PSC-A64S (Optional)
1-28
1.4.7
Centralized ON/OFF Controller, PSC-A16RS (Optional)
1-30
2. General Data
1-31
3. Dimensional Data
1-43
3.1 Dimensional Data for Indoor Units
1-43
3.2 Dimensional Data for Total Heat Exchangers
1-56
4. Selection Data
1-57
4.1 Operation Space
1-57
4.2 Selection Guide
1-60
4.3 Sensible Heat Factor (SHF)
1-62
4.4 Fan Performance
1-63
4.5 Model Selection of Total Heat Exchangers
1-68
5. Electrical Data
1-72
6. Sound Data
1-74
7. Working Range
1-87
iv
CONTENTS
Technical Data
Items
8. Optional Accessories
8.1 for Control Systems
Page
1-88
1-88
8.1.1
Liquid Crystal Remote Control Switch (PC-AR)
1-88
8.1.2
Wireless Remote Control Switch (PC-LH3A)
1-88
8.1.3
Half Size Remote Control Switch (PC-ARH)
1-88
8.1.4
7-Day Timer (PSC-A1T)
1-88
8.1.5
Central Station (PSC-5S and PSC-A64S)
1-89
8.1.6
Centralized ON/OFF Controller (PSC-A16RS)
1-93
8.1.7
Receiver Kit (PC-ALH, PC-ALHD, PC-ALHP and PC-ALHZ)
1-93
8.1.8
Remote Control Cable <for PC-AR>
(PRC-5K, PRC-10K and PRC-15K)
1-93
8.1.9
3P Connector Cable (PCC-1A)
1-93
8.1.10 Remote Sensor (THM-R2A)
8.2 for Indoor Units
1-93
1-94
8.2.1
for In-the-Ceiling Type
1-94
8.2.2
for 4-Way Cassette Type
1-98
8.2.3
for 2-Way Cassette Type
1-109
9. Component Data
10. Control System
1-117
1-124
10.1 Refrigeration Cycle
1-124
10.2 System Control
1-130
10.2.1 Control in a Room
1-130
10.2.2 Group Control from a Remote Place
1-131
10.2.3 Control in a Room/Control from a Remote Place
1-131
10.3 Standard Operation Sequence
1-132
10.4 Safety and Control Device Setting
1-138
10.5 Optional Dip Switch Setting for Capacity Adjustment
1-138
10 6 Electrical
10.6
El t i l Wiring
Wi i Diagram
Di
1-139
1 139
11. Miscellaneous Notes
12. Standard Specifications
1-149
1-151A-B-C
1-151
v
CONTENTS
Installation and Operation
Page
Indoor Unit Type
Items
RPI
RPI
(0.8 to 5.0HP) (8 and 10HP)
RCI
RCD
RPK
RPF
RPFI
RPC
1. Safety Summary
2-5
2-19
2-31
2-43
2-55
2-73
2-83
2. Structure
2-5
2-19
2-31
2-43
2-55
2-73
2-83
2.1 Indoor Unit
2-5
2-19
2-31
2-43
2-55
2-73
2-83
2.2 Refrigerant Cycle
2-7
2-20
2-32
2-44
2-58
2-74
2-84
2.3 Necessary Tools and
Instruments List for Installation
2-7
2-20
2-32
2-44
2-58
2-74
2-84
2-7
2-20
2-32
2-44
2-58
2-74
2-84
3.1 Transportation
2-7
2-20
2-32
2-44
2-58
2-74
2-84
3.2 Handling of Indoor Unit
2-7
2-20
2-32
2-44
2-58
2-74
2-84
2-7
2-21
2-33
2-45
2-59
2-75
2-85
4.1 Factory-Supplied Accessories
2-7
2-21
2-33
2-45
2-59
2-75
2-85
4.2 Initial Check
2-9
2-22
2-34
2-46
2-60
2-76
2-86
4.3 Installation
2-10
2-23
2-35
2-47
2-62
2-77
2-87
2-13
2-25
2-37
2-49
2-67
2-78
2-88
5.1 Piping Materials
2-13
2-25
2-37
2-49
2-67
2-78
2-88
5.2 Piping Connection
2-13
2-25
2-37
2-49
2-67
2-78
2-88
6. Drain Piping
2-14
2-27
2-38
2-50
2-69
2-79
2-90
7. Electrical Wiring
2-15
2-28
2-40
2-52
2-70
2-80
2-91
7.1 General Check
2-15
2-28
2-40
2-52
2-70
2-80
2-92
7.2 Electrical Wiring Connection
2-15
2-28
2-40
2-52
2-70
2-80
2-92
8. Test Run
2-17
2-30
2-42
2-54
2-72
2-82
2-93
9. Safety and Control Device Setting
2-17
2-30
2-42
2-54
2-72
2-82
2-93
3. Transportation and Handling
4. Indoor Unit Installation
5. Refrigerant Piping Work
10. Common
2-95
10.1 Field Minimum Wire Size for
Power Source
2-95
10.2 Setting of Dip Switches
2-96
10.3 Setting the Filter Indication Interval
2-101
10.4 Setting of High Speed Tap
2-102
10.5 Setting of External Pressure
2-102
vi
CONTENTS
Installation and Operation
Items
11. Installation of Optional Air Panel
Page
2-103
11.1 Air Panel for 4-Way Cassette Type: P-N23WA
2-103
11.2 Air Panel for 2-Way Cassette Type: P-N23DWA and P-N46DWA
2-108
12. Installation of Optional Controller
2-113
12.1 Remote Control Switch : PC-AR
2-114
12.2 Wireless Remote Control Switch: PC-LH3A
2-132
12.3 7-Day Timer : PSC-A1T
2-137
12.4 Central Station: PSC-5S
2-151
12.5 Central Station: PSC-A64S
2-169
12.6 Centralized ON/OFF Controller: PSC-A16RS
2-192
12.7 Wireless Receiver Kit: PC-ALH (for 4-Way Cassette Type)
2-204
12.8 Wireless Receiver Kit: PC-ALHD, PC-ALHP and PC-ALHZ
(for 2-Way Cassette Type, Ceiling Type, In-the-Ceiling Type,
Floor Type, Floor Concealed Type and Wall Type)
2-210
13. Total Heat Exchanger
2-220
13.1 Safety Summary
2-220
13.2 Structure
2-220
13.3 Transportation and Handling
2-221
13.4 Installation
2-221
13.5 Electrical Wiring
2-225
13.6 Test Run
2-232
13.7 Safety and Control Device Setting
2-232
14. Maintenance
2-233
15. Operation
2-234
15.1 Remote Control Switch
2-234
15.2 Before Operation
2-236
15.3 Operation Method
2-236
15.4 Setting of Automatic Swing Louver Direction
2-237
15.5 Automatic Control
2-244
15.6 Identifying of Indoor Units Installed Side by Side
2-245
15.7 Filter Cleaning
2-246
15.8 Filter and Element Cleaning for Total Heat Exchanger
2-249
15.9 Replacing Batteries for Wireless Remote Control Switch
2-250
16. Troubleshooting
2-251
16.1 Initial Troubleshooting
2-251
16.2 Troubleshooting by Alarm Code
2-252
16.3 Troubleshooting in Check Mode by Remote Control Switch
2-254
16.4 Self-Checking of PCB using Remote Control Switch
2-260
16.5 Self-Checking of Remote Control Switch
2-262
vii
TECHNICAL DATA
GENERAL DATA
2. General Data
Indoor Unit Type
Model
Indoor Unit Power Supply
Nominal Cooling
kW
Capacity *1)
kcal/h
Btu/h
Nominal Cooling
kW
Capacity *2)
kcal/h
Btu/h
Nominal Heating
kW
Capacity
kcal/h
Btu/h
Sound Pressure Level
(Overall A Scale)
dB
Outer Dimensions
Height
mm
(in.)
Width
mm
(in.)
Depth
mm
(in.)
Net Weight
kg
(lbs.)
Refrigerant
Indoor Fan
Air Flow Rate
m3/min.
(Hi/Me/Lo)
(cfm)
External Pressure *3)
Pa
Motor
W
Connections
Refrigerant Piping
Liquid Line
mm
(in.)
Gas Line
mm
(in.)
Condensate Drain
Approximate
Packing Measurement
m3
RPI-0.8FSN2
2.3
2,000
7,900
2.2
1,900
7,500
2.5
2,100
8,500
35-33-31
In-the-Ceiling Type
RPI-1.0FSN2
RPI-1.5FSN2
AC 1, 220-240V/50Hz, 220V/60Hz
2.9
4.1
2,500
3,550
9,900
14,100
2.8
4.0
2,400
3,400
9,600
13,600
3.2
4.8
2,800
4,100
10,900
16,400
35-33-31
35-33-31
RPI-2.0FSN2
5.8
5,000
19,800
5.6
4,800
19,100
6.3
5,400
21,500
35-33-31
270
270
270
270
(10-5/8)
(10-5/8)
(10-5/8)
(10-5/8)
650+75
650+75
650+75
900+75
(25-9/16+2-15/16)
(25-9/16+2-15/16)
(25-9/16+2-15/16)
(35-7/16+2-15/16)
720
720
720
720
(28-3/8)
(28-3/8)
(28-3/8)
(28-3/8)
26
26
26
35
(57)
(57)
(57)
(77)
R410A / R407C / R22 (Nitrogen-Charged for Corrosion-Resistance)
8/7/6
(283/247/212)
50 (80-30)
60
8/7/6
13/11/9
(283/247/212)
(459/388/318)
50 (80-30)
50 (80-30)
60
60
Flare-Nut Connection (with Flare Nuts)
15/13/11
(530/459/388)
50 (80-30)
75
6.35
(1/4)
12.7
(1/2)
VP25
6.35
(1/4)
12.7
(1/2)
VP25
6.35
(1/4)
12.7
(1/2)
VP25
6.35
(1/4)
15.88
(5/8)
VP25
0.21
0.21
0.21
0.27
NOTES:
1. The nominal cooling capacity is the combined capacity of the HITACHI standard split system, and is based on the JIS standard B8616.
Cooling Operation Conditions
Indoor Air Inlet Temperature:
Outdoor Air Inlet Temperature:
Heating Operation Conditions
Indoor Air Inlet Temperature:
Outdoor Air Inlet Temperature:
Piping Length: 7.5 Meters
27oC DB (80oF DB)
*1) 19.5oC WB (67oF WB)
*2) 19.0oC WB (66.2oF WB)
35oC DB (95oF DB)
20oC DB (68oF DB)
7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1.5 Meter Beneath the Unit.
With Discharge Duct (2.0m) and Return Duct (1.0m).
Voltage of the power source for the indoor fan motor is 220V.
In case of the power source of 240V, the sound pressure level increases by about 1 dB.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
3. The data for external pressure *3) indicates "Standard Pressure Setting (High Pressure Setting - Low Pressure Setting)"
values when a filter is not used.
The sound pressure level is based on the Standard Pressure Setting.
1-31
GENERAL DATA
Indoor Unit Type
Model
Indoor Unit Power Supply
Nominal Cooling
kW
Capacity *1)
kcal/h
Btu/h
Nominal Cooling
kW
Capacity *2)
kcal/h
Btu/h
Nominal Heating
kW
Capacity
kcal/h
Btu/h
Sound Pressure Level
(Overall A Scale)
dB
Outer Dimensions
Height
mm
(in.)
Width
mm
(in.)
Depth
mm
(in.)
Net Weight
kg
(lbs.)
Refrigerant
Indoor Fan
Air Flow Rate
m3/min.
(Hi/Me/Lo)
(cfm)
External Pressure *3)
Pa
Motor
W
Connections
Refrigerant Piping
Liquid Line
mm
(in.)
Gas Line
mm
(in.)
Condensate Drain
Approximate
Packing Measurement
m3
RPI-2.5FSN2
7.3
6,300
25,000
7.1
6,100
24,200
8.5
7,300
29,000
36-34-32
In-the-Ceiling Type
RPI-3.0FSN2
RPI-4.0FSN2
AC 1, 220-240V/50Hz, 220V/60Hz
8.3
11.6
7,100
10,000
28,200
39,700
8.0
11.2
6,900
9,600
27,300
38,200
9.0
12.5
7,700
10,700
30,700
42,600
42-39-35
RPI-5.0FSN2
14.5
12,500
49,600
14.0
12,000
47,800
16.0
13,800
54,600
43-40-36
44-41-37
270
350
350
350
(10-5/8)
(13-3/4)
(13-3/4)
(13-3/4)
900+75
650+75
900+75
1,300+75
(35-7/16+2-15/16)
(25-9/16+2-15/16)
(35-7/16+2-15/16)
(51-3/16+2-15/16)
720
800
800
800
(28-3/8)
(31-1/2)
(31-1/2)
(31-1/2)
35
37
46
58
(77)
(82)
(101)
(128)
R410A / R407C / R22 (Nitrogen-Charged for Corrosion-Resistance)
16/14/12
(565/494/424)
50 (80-30)
75
19/17/14
27/23/19
(671/600/494)
(954/812/671)
120 (170-60)
120 (170-60)
150
290
Flare-Nut Connection (with Flare Nuts)
37/31/25
(1,306/1,095/883)
120 (170-60)
290
9.53
(3/8)
15.88
(5/8)
VP25
9.53
(3/8)
15.88
(5/8)
VP25
9.53
(3/8)
15.88 *4
(5/8)
VP25
9.53
(3/8)
15.88 *4)
(5/8)
VP25
0.27
0.29
0.38
0.52
NOTES:
1. The nominal cooling capacity is the combined capacity of the HITACHI standard split system, and is based on the JIS standard B8616.
Cooling Operation Conditions
Indoor Air Inlet Temperature:
Outdoor Air Inlet Temperature:
Heating Operation Conditions
Indoor Air Inlet Temperature:
Outdoor Air Inlet Temperature:
Piping Length: 7.5 Meters
27oC DB (80oF DB)
*1) 19.5oC WB (67oF WB)
*2) 19.0oC WB (66.2oF WB)
35oC DB (95oF DB)
20oC DB (68oF DB)
7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1.5 Meters Beneath the Unit.
With Discharge Duct (2.0m) and Return Duct (1.0m).
Voltage of the power source for the indoor fan motor is 220V.
In case of the power source of 240V, the sound pressure level increases by about 1 or 2 dB.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
3. The data for external pressure *3) indicates "Standard Pressure Setting (High Pressure Setting - Low Pressure Setting)"
values when a filter is not used.
The sound pressure level is based on the Standard Pressure Setting.
4. *4) In case of using R407C or R22, use the accessory adaptor and 19.05 piping.
1-32
GENERAL DATA
Indoor Unit Type
Model
Indoor Unit Power Supply
Nominal Cooling
kW
Capacity *1)
kcal/h
Btu/h
Nominal Cooling
kW
Capacity *2)
kcal/h
Btu/h
Nominal Heating
kW
Capacity
kcal/h
Btu/h
Sound Pressure Level
(Overall A Scale) *3)
dB
Outer Dimensions
Height
mm
(in.)
Width
mm
(in.)
Depth
mm
(in.)
Net Weight
kg
(lbs.)
Refrigerant
Indoor Fan
Air Flow Rate
m3/min.
(cfm)
External Pressure *4)
380/415V
Pa
Motor
kW
Connections
Refrigerant Piping
Liquid Line
mm
(in.)
Gas Line
mm
(in.)
Condensate Drain
Approximate
Packing Measurement
m3
In-the-Ceiling Type
RPI-8FSN
RPI-10FSN
AC 3 4W, 380-415V/50Hz, 380V/60Hz
23.3
20,000
79,400
22.4
19,300
76,400
25.0
21,500
85,300
29.1
25,000
99,200
28.0
24,100
95,500
31.5
27,100
107,500
45 (42)*
52 (50)*
470
470
(18-1/2)
(18-1/2)
1,250
1,250
(49-1/4)
(49-1/4)
1,120
1,120
(44-1/12)
(44-1/12)
100
100
(221)
(221)
R410A / R407C / R22 (Nitrogen-Charged for Corrosion-Resistance)
58 (58)*
(2,048 (2,048)*)
72 (72)*
(2,542 (2,542)*)
220 (110)* / 260 (130)*
0.76 (0.51)*
220 (110)* / 260 (130)*
1.08 (0.81)*
Brazing Connection
9.53 *5)
(3/8)
19.05 *6)
(3/4)
VP25
9.53 *5)
(3/8)
22.2 *7)
(7/8)
VP25
1.06
1.06
NOTES:
1. The nominal cooling capacity is the combined capacity of the HITACHI standard split system, and is based on the JIS standard B8616.
Cooling Operation Conditions
Indoor Air Inlet Temperature:
Outdoor Air Inlet Temperature:
Heating Operation Conditions
Indoor Air Inlet Temperature:
Outdoor Air Inlet Temperature:
Piping Length: 7.5 Meters
27oC DB (80oF DB)
*1) 19.5oC WB (67oF WB)
*2) 19.0oC WB (66.2oF WB)
35oC DB (95oF DB)
20oC DB (68oF DB)
7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Lift: 0 Meter
2. The sound pressure level *3) is based on following conditions.
1.5 Meters Beneath the Unit.
With Discharge Duct (2.0m) and Return Duct (1.0m).
Voltage of the power source for the indoor fan motor is 380V.
In case of the power source of 415V, the sound pressure level increases by about 2 dB.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
3. The values with ( )* of sound pressure level, air flow rate, external pressure and motor output indicate the values
in case of external static pressure setting at 110Pa (130Pa for 415V).
4. The external pressure *4) indicates the values when a filter is not used.
5. *5) In case of using R407C or R22, use the accessory reducer and 12.7 piping.
*6) In case of using R407C or R22, use the accessory reducer and 25.4 piping.
*7) In case of using R407C or R22, use the accessory reducer and 28.6 piping.
1-33
GENERAL DATA
Indoor Unit Type
Model
Indoor Unit Power Supply
Nominal Cooling
kW
Capacity *1)
kcal/h
Btu/h
Nominal Cooling
kW
Capacity *2)
kcal/h
Btu/h
Nominal Heating
kW
Capacity
kcal/h
Btu/h
Sound Pressure Level
(Overall A Scale)
dB
Outer Dimensions
Height
mm
(in.)
Width
mm
(in.)
Depth
mm
(in.)
Net Weight
kg
(lbs.)
Refrigerant
Indoor Fan
Air Flow Rate
m3/min.
(Hi/Me/Lo)
(cfm)
Motor
W
Connections
Refrigerant Piping
Liquid Line
mm
(in.)
Gas Line
mm
(in.)
Condensate Drain
Approximate
Packing Measurement
m3
Adaptable Panel Model
Color
Outer Dimensions
Height
mm
(in.)
Width
mm
(in.)
Depth
mm
(in.)
Net Weight
kg
(lbs.)
Approximate
Packing Measurement
m3
2.9
2,500
9,900
2.8
2,400
9,600
3.2
2,800
10,900
4-Way Cassette Type
RCI-1.5FSN2
AC 1, 220-240V/50Hz, 220V/60Hz
4.1
3,550
14,100
4.0
3,400
13,600
4.8
4,100
16,400
30-28-27
30-28-27
RCI-1.0FSN2
RCI-2.0FSN2
5.8
5,000
19,800
5.6
4,800
19,100
6.3
5,400
21,500
30-28-27
248
248
248
(9-3/4)
(9-3/4)
(9-3/4)
840
840
840
(33-1/16)
(33-1/16)
(33-1/16)
840
840
840
(33-1/16)
(33-1/16)
(33-1/16)
23
23
24
(51)
(51)
(53)
R410A / R407C / R22 (Nitrogen-Charged for Corrosion-Resistance)
13/12/11
(459/424/388)
56
15/13.5/12
(530/477/424)
56
Flare-Nut Connection (with Flare Nuts)
16/14/12
(565/494/424)
56
6.35
(1/4)
12.7
(1/2)
VP25
6.35
(1/4)
12.7
(1/2)
VP25
6.35
(1/4)
15.88
(5/8)
VP25
0.22
P-N23WA
0.22
P-N23WA
Silky White
0.22
P-N23WA
37
(1-7/16)
950
(37-3/8)
950
(37-3/8)
6
(13)
37
(1-7/16)
950
(37-3/8)
950
(37-3/8)
6
(13)
37
(1-7/16)
950
(37-3/8)
950
(37-3/8)
6
(13)
0.09
0.09
0.09
NOTES:
1. The nominal cooling capacity is the combined capacity of the HITACHI standard split system, and is based on the JIS standard B8616.
Cooling Operation Conditions
Indoor Air Inlet Temperature:
Outdoor Air Inlet Temperature:
Heating Operation Conditions
Indoor Air Inlet Temperature:
Outdoor Air Inlet Temperature:
Piping Length: 7.5 Meters
27oC DB (80oF DB)
*1) 19.5oC WB (67oF WB)
*2) 19.0oC WB (66.2oF WB)
35oC DB (95oF DB)
20oC DB (68oF DB)
7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1.5 Meters Beneath the Unit.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
1-34
GENERAL DATA
Indoor Unit Type
Model
Indoor Unit Power Supply
Nominal Cooling
kW
Capacity *1)
kcal/h
Btu/h
Nominal Cooling
kW
Capacity *2)
kcal/h
Btu/h
Nominal Heating
kW
Capacity
kcal/h
Btu/h
Sound Pressure Level
(Overall A Scale)
dB
Outer Dimensions
Height
mm
(in.)
Width
mm
(in.)
Depth
mm
(in.)
Net Weight
kg
(lbs.)
Refrigerant
Indoor Fan
Air Flow Rate
m3/min.
(Hi/Me/Lo)
(cfm)
Motor
W
Connections
Refrigerant Piping
Liquid Line
mm
(in.)
Gas Line
mm
(in.)
Condensate Drain
Approximate
Packing Measurement
m3
Adaptable Panel Model
Color
Outer Dimensions
Height
mm
(in.)
Width
mm
(in.)
Depth
mm
(in.)
Net Weight
kg
(lbs.)
Approximate
Packing Measurement
m3
RCI-2.5FSN2
7.3
6,300
25,000
7.1
6,100
24,200
8.5
7,300
29,000
32-30-28
248
(9-3/4)
840
(33-1/16)
840
(33-1/16)
24
(53)
4-Way Cassette Type
RCI-3.0FSN2
RCI-4.0FSN2
AC 1, 220-240V/50Hz, 220V/60Hz
8.3
11.6
7,100
10,000
28,200
39,700
8.0
11.2
6,900
9,600
27,300
38,200
9.0
12.5
7,700
10,700
30,700
42,600
32-30-28
RCI-5.0FSN2
14.5
12,500
49,600
14.0
12,000
47,800
16.0
13,800
54,600
38-35-33
39-37-35
298
298
298
(11-3/4)
(11-3/4)
(11-3/4)
840
840
840
(33-1/16)
(33-1/16)
(33-1/16)
840
840
840
(33-1/16)
(33-1/16)
(33-1/16)
26
29
29
(57)
(64)
(64)
R410A / R407C / R22 (Nitrogen-Charged for Corrosion-Resistance)
20/17/15
(706/600/530)
56
21/18/15
32/28/24
(741/635/530)
(1,130/989/847)
56
124
Flare-Nut Connection (with Flare Nuts)
34/29/25
(1,201/1,024/883)
124
9.53
(3/8)
15.88
(5/8)
VP25
9.53
(3/8)
15.88
(5/8)
VP25
9.53
(3/8)
15.88 *3)
(5/8)
VP25
9.53
(3/8)
15.88 *3)
(5/8)
VP25
0.22
P-N23WA
0.26
P-N23WA
0.26
P-N23WA
0.26
P-N23WA
Silky White
37
(1-7/16)
950
(37-3/8)
950
(37-3/8)
6
(13)
37
(1-7/16)
950
(37-3/8)
950
(37-3/8)
6
(13)
37
(1-7/16)
950
(37-3/8)
950
(37-3/8)
6
(13)
37
(1-7/16)
950
(37-3/8)
950
(37-3/8)
6
(13)
0.09
0.09
0.09
0.09
NOTES:
1. The nominal cooling capacity is the combined capacity of the HITACHI standard split system, and is based on the JIS standard B8616.
Cooling Operation Conditions
Indoor Air Inlet Temperature:
Outdoor Air Inlet Temperature:
Heating Operation Conditions
Indoor Air Inlet Temperature:
Outdoor Air Inlet Temperature:
Piping Length: 7.5 Meters
27oC DB (80oF DB)
*1) 19.5oC WB (67oF WB)
*2) 19.0oC WB (66.2oF WB)
35oC DB (95oF DB)
20oC DB (68oF DB)
7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1.5 Meters Beneath the Unit.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
3. *3) In case of using R407C or R22, use the accessory adaptor and 19.05 piping.
1-35
GENERAL DATA
Indoor Unit Type
Model
Indoor Unit Power Supply
Nominal Cooling
kW
Capacity *1)
kcal/h
Btu/h
Nominal Cooling
kW
Capacity *2)
kcal/h
Btu/h
Nominal Heating
kW
Capacity
kcal/h
Btu/h
Sound Pressure Level
(Overall A Scale)
dB
Outer Dimensions
Height
mm
(in.)
Width
mm
(in.)
Depth
mm
(in.)
Net Weight
kg
(lbs.)
Refrigerant
Indoor Fan
Air Flow Rate
m3/min.
(Hi/Me/Lo)
(cfm)
Motor
W
Connections
Refrigerant Piping
Liquid Line
mm
(in.)
Gas Line
mm
(in.)
Condensate Drain
Approximate
Packing Measurement
m3
Standard Accessories
Adaptable Panel Model
Color
Outer Dimensions
Height
mm
(in.)
Width
mm
(in.)
Depth
mm
(in.)
Net Weight
kg
(lbs.)
Approximate
Packing Measurement
m3
2.9
2,500
9,900
2.8
2,400
9,600
3.2
2,800
10,900
2-Way Cassette Type
RCD-1.5FSN2
AC 1, 220-240V/50Hz, 220V/60Hz
4.1
3,550
14,100
4.0
3,400
13,600
4.8
4,100
16,400
34-32-30
35-32-30
RCD-1.0FSN2
RCD-2.0FSN2
5.8
5,000
19,800
5.6
4,800
19,100
6.3
5,400
21,500
35-32-30
298
298
298
(11-3/4)
(11-3/4)
(11-3/4)
860
860
860
(33-7/8)
(33-7/8)
(33-7/8)
620
620
620
(24-7/16)
(24-7/16)
(24-7/16)
27
27
27
(60)
(60)
(60)
R410A / R407C / R22 (Nitrogen-Charged for Corrosion-Resistance)
10/9/8
(353/318/282)
35
13/11/9
(459/388/318)
35
Flare-Nut Connection (with Flare Nuts)
15/13/11
(530/459/388)
35
6.35
(1/4)
12.7
(1/2)
VP25
6.35
(1/4)
12.7
(1/2)
VP25
6.35
(1/4)
15.88
(5/8)
VP25
0.23
0.23
Mounting Bracket
P-N23DWA
Silky White
0.23
P-N23DWA
P-N23DWA
30
(1-3/16)
1,100
(43-5/16)
710
(27-15/16)
6
(13)
30
(1-3/16)
1,100
(43-5/16)
710
(27-15/16)
6
(13)
30
(1-3/16)
1,100
(43-5/16)
710
(27-15/16)
6
(13)
0.10
0.10
0.10
NOTES:
1. The nominal cooling capacity is the combined capacity of the HITACHI standard split system, and is based on the JIS standard B8616.
Cooling Operation Conditions
Indoor Air Inlet Temperature:
Outdoor Air Inlet Temperature:
Heating Operation Conditions
Indoor Air Inlet Temperature:
Outdoor Air Inlet Temperature:
Piping Length: 7.5 Meters
27oC DB (80oF DB)
*1) 19.5oC WB (67oF WB)
*2) 19.0oC WB (66.2oF WB)
35oC DB (95oF DB)
20oC DB (68oF DB)
7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1.5 Meters Beneath the Unit.
Voltage of the power source for the indoor fan motor is 220V.
In case of the power source of 240V, the sound pressure level increases by about 1 dB.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
1-36
GENERAL DATA
Indoor Unit Type
Model
Indoor Unit Power Supply
Nominal Cooling
kW
Capacity *1)
kcal/h
Btu/h
Nominal Cooling
kW
Capacity *2)
kcal/h
Btu/h
Nominal Heating
kW
Capacity
kcal/h
Btu/h
Sound Pressure Level
(Overall A Scale)
dB
Outer Dimensions
Height
mm
(in.)
Width
mm
(in.)
Depth
mm
(in.)
Net Weight
kg
(lbs.)
Refrigerant
Indoor Fan
Air Flow Rate
m3/min.
(Hi/Me/Lo)
(cfm)
Motor
W
Connections
Refrigerant Piping
Liquid Line
mm
(in.)
Gas Line
mm
(in.)
Condensate Drain
Approximate
Packing Measurement
m3
Standard Accessories
Adaptable Panel Model
Color
Outer Dimensions
Height
mm
(in.)
Width
mm
(in.)
Depth
mm
(in.)
Net Weight
kg
(lbs.)
Approximate
Packing Measurement
m3
RCD-2.5FSN2
7.3
6,300
25,000
7.1
6,100
24,200
8.5
7,300
29,000
38-34-31
298
(11-3/4)
860
(33-7/8)
620
(24-7/16)
30
(66)
2-Way Cassette Type
RCD-3.0FSN2
RCD-4.0FSN2
AC 1, 220-240V/50Hz, 220V/60Hz
8.3
11.6
7,100
10,000
28,200
39,700
8.0
11.2
6,900
9,600
27,300
38,200
9.0
12.5
7,700
10,700
30,700
42,600
38-34-31
RCD-5.0FSN2
14.5
12,500
49,600
14.0
12,000
47,800
16.0
13,800
54,600
40-36-33
43-40-36
298
298
298
(11-3/4)
(11-3/4)
(11-3/4)
860
1,420
1,420
(33-7/8)
(55-7/8)
(55-7/8)
620
620
620
(24-7/16)
(24-7/16)
(24-7/16)
30
48
48
(66)
(106)
(106)
R410A / R407C / R22 (Nitrogen-Charged for Corrosion-Resistance)
19/16/14
(671/565/494)
55
19/16/14
29/24/21
(671/565/494)
(1,024/847/742)
55
35 x 2
Flare-Nut Connection (with Flare Nuts)
9.53
(3/8)
15.88
(5/8)
VP25
9.53
(3/8)
15.88
(5/8)
VP25
0.23
0.23
P-N23DWA
34/29/25
(1,201/1,024/883)
55 x 2
9.53
(3/8)
15.88 *3)
(5/8)
VP25
0.37
Mounting Bracket
P-N23DWA
P-N46DWA
Silky White
9.53
(3/8)
15.88 *3)
(5/8)
VP25
0.37
P-N46DWA
30
(1-3/16)
1,100
(43-5/16)
710
(27-15/16)
6
(13)
30
(1-3/16)
1,100
(43-5/16)
710
(27-15/16)
6
(13)
30
(1-3/16)
1,660
(65-3/8)
710
(27-15/16)
8
(18)
30
(1-3/16)
1,660
(65-3/8)
710
(27-15/16)
8
(18)
0.10
0.10
0.15
0.15
NOTES:
1. The nominal cooling capacity is the combined capacity of the HITACHI standard split system, and is based on the JIS standard B8616.
Cooling Operation Conditions
Indoor Air Inlet Temperature:
Outdoor Air Inlet Temperature:
Heating Operation Conditions
Indoor Air Inlet Temperature:
Outdoor Air Inlet Temperature:
Piping Length: 7.5 Meters
27oC DB (80oF DB)
*1) 19.5oC WB (67oF WB)
*2) 19.0oC WB (66.2oF WB)
35oC DB (95oF DB)
20oC DB (68oF DB)
7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1.5 Meters Beneath the Unit.
Voltage of the power source for the indoor fan motor is 220V.
In case of the power source of 240V, the sound pressure level increases by about 1 dB.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
3. *3) In case of using R407C or R22, use the accessory adaptor and 19.05 piping.
1-37
GENERAL DATA
Indoor Unit Type
Model
Indoor Unit Power Supply
Nominal Cooling
kW
Capacity *1)
kcal/h
Btu/h
Nominal Cooling
kW
Capacity *2)
kcal/h
Btu/h
Nominal Heating
kW
Capacity
kcal/h
Btu/h
Sound Pressure Level
(Overall A Scale)
dB
Cabinet Color
Outer Dimensions
Height
mm
(in.)
Width
mm
(in.)
Depth
mm
(in.)
Net Weight
kg
(lbs.)
Refrigerant
Indoor Fan
Air Flow Rate
m3/min.
(Hi/Me/Lo)
(cfm)
Motor
kW
Connections
Refrigerant Piping
Liquid Line
mm
(in.)
Gas Line
mm
(in.)
Condensate Drain
Approximate
Packing Measurement
m3
Standard Accessories
RPK-1.0FSNSM2
2.9
2,500
9,900
2.8
2,400
9,600
3.2
2,800
10,900
38-36-34
Wall Type
RPK-1.5FSNSM2
AC 1, 220-240V/50Hz, 220V/60Hz
4.1
3,550
14,100
4.0
3,400
13,600
4.8
4,100
16,400
RPK-2.0FSNSM2
5.8
5,000
19,800
5.6
4,800
19,100
6.3
5,400
21,500
40-38-36
White
41-39-37
280
280
295
(11)
(11)
(11-5/8)
780
780
1,030
(30-11/16)
(30-11/16)
(40-9/16)
210
210
208
(8-1/4)
(8-1/4)
(8-3/16)
10
10
12
(22)
(22)
(26)
R410A / R407C / R22 (Nitrogen-Charged for Corrosion-Resistance)
10/8/7
(353/283/247)
0.02
11/10/9
(388/353/318)
0.02
Flare-Nut Connection (with Flare Nuts)
14/12/10
(494/424/353)
0.03
6.35
(1/4)
12.7
(1/2)
VP16
6.35
(1/4)
12.7
(1/2)
VP16
6.35
(1/4)
15.88 or 12.7 (*1)
(5/8) or (1/2)
VP16
0.07
0.07
Wall Mounting Bracket
0.11
(*1) The refrigerant piping size may be required to change depending on the outdoor unit to be connected.
If 12.7 pipe is used at the gas side, remove the flare adaptor at the indoor unit gas piping.
Then attach the flare nut (accessory) for pipe connection.
NOTES:
1. The nominal capacity is the combined capacity of the HITACHI standard SET-FREE system, and is based on the JIS standard B8616.
Cooling Operation Conditions
Indoor Air Inlet Temperature:
Outdoor Air Inlet Temperature:
Heating Operation Conditions
Indoor Air Inlet Temperature:
Outdoor Air Inlet Temperature:
Piping Length: 7.5 Meters
27oC DB (80oF DB)
*1) 19.5oC WB (67oF WB)
*2) 19.0oC WB (66.2oF WB)
35oC DB (95oF DB)
20oC DB (68oF DB)
7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1 meter beneath the unit and 1 meter from inlet grille.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
1-38
GENERAL DATA
Indoor Unit Type
Model
Indoor Unit Power Supply
Nominal Cooling
kW
Capacity *1)
kcal/h
Btu/h
Nominal Cooling
kW
Capacity *2)
kcal/h
Btu/h
Nominal Heating
kW
Capacity
kcal/h
Btu/h
Sound Pressure Level
(Overall A Scale)
dB
Cabinet Color
Outer Dimensions
Height
mm
(in.)
Width
mm
(in.)
Depth
mm
(in.)
Net Weight
kg
(lbs.)
Refrigerant
Indoor Fan
Air Flow Rate
m3/min.
(Hi/Me/Lo)
(cfm)
Motor
kW
Connections
Refrigerant Piping
Liquid Line
mm
(in.)
Gas Line
mm
(in.)
Condensate Drain
Approximate
Packing Measurement
m3
Standard Accessories
RPK-2.5FSNSM2
7.3
6,300
25,000
7.1
6,100
24,200
8.5
7,300
29,000
43-40-37
Wall Type
RPK-3.0FSNSM2
AC 1, 220-240V/50Hz, 220V/60Hz
8.3
7,100
28,200
8.0
6,900
27,300
9.0
7,700
30,700
43-40-37
White
RPK-4.0FSNSM2
11.6
10,000
39,700
11.2
9,600
38,200
12.5
10,700
42,600
49-46-43
333
333
333
(13-1/8)
(13-1/8)
(13-1/8)
1,150
1,150
1,150
(45-1/4)
(45-1/4)
(45-1/4)
245
245
245
(9-5/8)
(9-5/8)
(9-5/8)
18
18
18
(40)
(40)
(40)
R410A / R407C / R22 (Nitrogen-Charged for Corrosion-Resistance)
17/16/14
(600/565/494)
0.03
17/16/14
(600/565/494)
0.03
Flare-Nut Connection (with Flare Nuts)
22/20/17
(777/706/600)
0.03
9.53
(3/8)
15.88
(5/8)
VP16
9.53
(3/8)
15.88
(5/8)
VP16
9.53
(3/8)
15.88
(5/8)
VP16
0.13
0.13
Wall Mounting Bracket
0.13
NOTES:
1. The nominal capacity is the combined capacity of the HITACHI standard SET-FREE system, and is based on the JIS standard B8616.
Cooling Operation Conditions
Indoor Air Inlet Temperature:
Outdoor Air Inlet Temperature:
Heating Operation Conditions
Indoor Air Inlet Temperature:
Outdoor Air Inlet Temperature:
Piping Length: 7.5 Meters
27oC DB (80oF DB)
*1) 19.5oC WB (67oF WB)
*2) 19.0oC WB (66.2oF WB)
35oC DB (95oF DB)
20oC DB (68oF DB)
7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1 meter beneath the unit and 1 meter from inlet grille.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
1-39
GENERAL DATA
Indoor Unit Type
Model
Indoor Unit Power Supply
Nominal Cooling
kW
Capacity *1)
kcal/h
Btu/h
Nominal Cooling
kW
Capacity *2)
kcal/h
Btu/h
Nominal Heating
kW
Capacity
kcal/h
Btu/h
Sound Pressure Level
(Overall A Scale)
dB
Cabinet Color
Outer Dimensions
Height
mm
(in.)
Width
mm
(in.)
Depth
mm
(in.)
Net Weight
kg
(lbs.)
Refrigerant
Indoor Fan
Air Flow Rate
m3/min.
(Hi/Me/Lo)
(cfm)
Motor
W
Connections
Refrigerant Piping
Liquid Line
mm
(in.)
Gas Line
mm
(in.)
Condensate Drain
Approximate
Packing Measurement
m3
Standard Accessories
Floor Type
RPF-1.0FSN2E
2.9
2,500
9,900
2.8
2,400
9,600
3.2
2,800
10,900
Floor Concealed Type
RPF-1.5FSN2E
RPFI-1.0FSN2E
RPFI-1.5FSN2E
AC 1, 220-240V/50Hz, 220V/60Hz
4.1
2.9
4.1
3,550
2,500
3,550
14,100
9,900
14,100
4.0
2.8
4.0
3,400
2,400
3,400
13,600
9,600
13,600
4.8
3.2
4.8
4,100
2,800
4,100
16,400
10,900
16,400
35-32-29
38-35-31
35-32-29
-
Spring White
630
(24-13/16)
1,045
(41-1/8)
220
(8-11/16)
25
(55)
38-35-31
-
630
620
620
(24-13/16)
(24-7/16)
(24-7/16)
1,170
848
973
(46-1/16)
(33-3/8)
(38-5/16)
220
220
220
(8-11/16)
(8-11/16)
(8-11/16)
28
19
23
(62)
(42)
(51)
R410A / R407C / R22 (Nitrogen-Charged for Corrosion-Resistance)
8.5/7/6
(300/247/212)
20
12/10/9
8.5/7/6
(424/353/318)
(300/247/212)
28
20
Flare-Nut Connection (with Flare Nuts)
6.35
(1/4)
12.7
(1/2)
18.5 OD
6.35
(1/4)
12.7
(1/2)
18.5 OD
0.22
0.24
12/10/9
(424/353/318)
28
6.35
(1/4)
12.7
(1/2)
18.5 OD
6.35
(1/4)
12.7
(1/2)
18.5 OD
0.22
0.23
OD: Outer Diameter
NOTES:
1. The nominal cooling capacity is the combined capacity of the HITACHI standard split system, and is based on the JIS standard B8616.
Cooling Operation Conditions
Indoor Air Inlet Temperature:
Outdoor Air Inlet Temperature:
Heating Operation Conditions
Indoor Air Inlet Temperature:
Outdoor Air Inlet Temperature:
Piping Length: 7.5 Meters
27oC DB (80oF DB)
*1) 19.5oC WB (67oF WB)
*2) 19.0oC WB (66.2oF WB)
35oC DB (95oF DB)
20oC DB (68oF DB)
7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1 meter from the unit.
1 meter from floor level.
Voltage of the power source for the indoor fan motor is 220V.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
1-40
GENERAL DATA
Indoor Unit Type
Model
Indoor Unit Power Supply
Nominal Cooling
kW
Capacity *1)
kcal/h
Btu/h
Nominal Cooling
kW
Capacity *2)
kcal/h
Btu/h
Nominal Heating
kW
Capacity
kcal/h
Btu/h
Sound Pressure Level
(Overall A Scale)
dB
Cabinet Color
Outer Dimensions
Height
mm
(in.)
Width
mm
(in.)
Depth
mm
(in.)
Net Weight
kg
(lbs.)
Refrigerant
Indoor Fan
Air Flow Rate
m3/min.
(Hi/Me/Lo)
(cfm)
Motor
W
Connections
Refrigerant Piping
Liquid Line
mm
(in.)
Gas Line
mm
(in.)
Condensate Drain
Approximate
Packing Measurement
m3
Standard Accessories
Ceiling Type
RPC-2.5FSN2
RPC-3.0FSN2
RPC-4.0FSN2
AC 1, 220-240V/50Hz, 220V/60Hz
7.3
8.3
11.6
6,300
7,100
10,000
25,000
28,200
39,700
7.1
8.0
11.2
6,100
6,900
9,600
24,200
27,300
38,200
8.5
9.0
12.5
7,300
7,700
10,700
29,000
30,700
42,600
RPC-2.0FSN2
5.8
5,000
19,800
5.6
4,800
19,100
6.3
5,400
21,500
40-37-34
40-37-34
40-37-34
Silky White
44-41-38
RPC-5.0FSN2
14.5
12,500
49,600
14.0
12,000
47,800
16.0
13,800
54,600
44-41-38
210
(8-1/4)
1,100
(43-5/16)
670
(26-3/8)
26
(57)
210
210
270
(8-1/4)
(8-1/4)
(10-5/8)
1,320
1,320
1,320
(51-15/16)
(51-15/16)
(51-15/16)
670
670
670
(26-3/8)
(26-3/8)
(26-3/8)
30
30
34
(66)
(66)
(75)
R410A / R407C / R22 (Nitrogen-Charged for Corrosion-Resistance)
270
(10-5/8)
1,580
(62-3/16)
670
(26-3/8)
42
(93)
14/12/10
(494/424/353)
35
18/15/12
18/15/12
25/21/18
(636/530/424)
(636/530/424)
(883/742/636)
50
50
95
Flare-Nut Connection (with Flare Nuts)
33/28/23
(1,165/989/812)
135
6.35
(1/4)
15.88
(5/8)
VP20
9.53
(3/8)
15.88
(5/8)
VP20
9.53
(3/8)
15.88
(5/8)
VP20
9.53
(3/8)
15.88 *3)
(5/8)
VP20
9.53
(3/8)
15.88 *3)
(5/8)
VP20
0.30
0.36
0.36
Mounting Bracket
0.43
0.50
NOTES:
1. The nominal cooling capacity is the combined capacity of the HITACHI standard split system, and is based on the JIS standard B8616.
Cooling Operation Conditions
Indoor Air Inlet Temperature:
Outdoor Air Inlet Temperature:
27oC DB (80oF DB)
*1) 19.5oC WB (67oF WB)
*2) 19.0oC WB (66.2oF WB)
35oC DB (95oF DB)
Heating Operation Conditions
Indoor Air Inlet Temperature:
Outdoor Air Inlet Temperature:
20oC DB (68oF DB)
7oC DB (45oF DB)
6oC WB (43oF WB)
Piping Length: 7.5 Meters
Piping Lift: 0 Meter
2. The sound pressure level is based on following conditions.
1 Meter Beneath the Unit and 1 Meter from Discharge Grille.
Voltage of the power source for the indoor fan motor is 220V.
In case of the power source of 240V, the sound pressure level increases by about 1 dB.
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
3. *3) In case of using R407C or R22, use the accessory adaptor and 19.05 piping.
1-41
GENERAL DATA
Unit Type
Model
Unit Power Supply
Air Flow Rate
(Hi/Me/Lo)
External Pressure
(Hi/Me/Lo)
Temp. Exchange Efficiency
(Hi/Me/Lo)
Enthalpy Exchange Efficiency
For Heating (Hi/Me/Lo)
For Cooling (Hi/Me/Lo)
Sound Pressure Level (Over A Scale)
at 1.5m from the unit (under)
(Hi/Me/Lo) *2), *4)
at Air Outlet
(Hi/Me/Lo) *3), *4)
Outer Dimensions
Height
Width
Depth
Net Weight
Connection Duct Diameter
Width
Depth
Net Weight
Connection Duct Diameter
KPI-10021 *1)
m3/h
250/250/165
500/500/350
800/800/670
1,000/1,000/870
Pa
65/40/20
150/60/30
140/100/70
160/100/80
%
78/78/83
77/77/82
78/78/80.5
79/79/81
%
%
69/69/74
62.5/62.5/68
67/67/73
61.5/61.5/68
71/71/73
64.5/64.5/68
70/70/73
64.5/64.5/67
dB
26.5-27.5/25-26
/21-22
33.5-34.5/32-33
/26-27
32.5-33.5/30-31
/23.5-24.5
40.5-41.5/38-39
/29.5-30.5
33.5-34.5/32-33
/30-31
44.5-45.5/43-44
/40-41
36-37/34-35
/31.5-32.5
47-48/45-46
/41.5-42.5
mm
(in.)
mm
(in.)
mm
(in.)
kg
(lbs.)
mm
275
(10-13/16)
735
(28-15/16)
780
(30-11/16)
21
(46)
150
317
(12-1/2)
1,016
(40)
888
(34-15/16)
33
(73)
200
398
(15-11/16)
1,004
(39-1/2)
1,164
(45-13/16)
61
(134)
250
398
(15-11/16)
1,231
(48-7/16)
1,164
(45-13/16)
72
(159)
250
KPI-2521
In-the-Ceiling Type
KPI-5021
KPI-8021
AC 1, 220/60Hz
dB
Unit Type
Model
Unit Power Supply
Air Flow Rate
(Hi/Me/Lo)
External Pressure
(Hi/Me/Lo)
Temp. Exchange Efficiency
(Hi/Me/Lo)
Enthalpy Exchange Efficiency
For Heating (Hi/Me/Lo)
For Cooling (Hi/Me/Lo)
Sound Pressure Level (Over A Scale)
at 1.5m from the unit (under)
(Hi/Me/Lo) *2), *4)
at Air Outlet
(Hi/Me/Lo) *3), *4)
Outer Dimensions
Height
Total Heat Exchanger
KPI-5021
KPI-8021
AC 1, 220-240V/50Hz
KPI-2521
KPI-10021 *1)
m3/h
250/250/150
500/500/300
800/800/660
1,000/1,000/720
Pa
100/50/20
200/60/20
230/120/80
200/110/60
%
78/78/84
77/77/83.5
78/78/81
79/79/83
%
%
69/69/75
62.5/62.5/70
67/67/75
61.5/61.5/70
71/71/73.5
64.5/64.5/68.5
70/70/76
64.5/64.5/71
dB
28.5/25.5/21
32.5/28.5/23
35/31/29
36/34/30
dB
35.5/32.5/26
40.5/36.5/29
46/42/39
47/45/40
mm
(in.)
mm
(in.)
mm
(in.)
kg
(lbs.)
mm
275
(10-13/16)
735
(28-15/16)
780
(30-11/16)
21
(46)
150
317
(12-1/2)
1,016
(40)
888
(34-15/16)
33
(73)
200
398
(15-11/16)
1,004
(39-1/2)
1,164
(45-13/16)
61
(134)
250
398
(15-11/16)
1,231
(48-7/16)
1,164
(45-13/16)
72
(159)
250
NOTES:
*1): KPI-10021 has different units according to the applied power supply, 220-240V/50Hz and 220V/60Hz.
*2): The sound pressure level is based on following conditions.
1.5 meters beneath the unit and this data was measured in an anechoic chamber so that reflected sound should be taken
into consideration in the field.
*3): The noise at the air outlets is the values at a 45o angle, 1.5 meters in front of the unit.
*4): The sound pressure level is based on the total heat exchange mode.
In case of the bypass ventilation mode, the sound pressure level increase by approximately 1 dB(A).
1-42
DIMENSIONAL DATA
3. Dimensional Data
3.1
Dimensional Data for Indoor Units
In-the-Ceiling Type
Models: RPI-0.8FSN2, RPI-1.0FSN2, RPI-1.5FSN2, RPI-2.0FSN2, RPI-2.5FSN2, RPI-3.0FSN2,
RPI-4.0FSN2 and RPI-5.0FSN2
Unit: mm
l - 6
(Around the Flange)
b
a
40
e
c x 300 = d
4 - 40 x 12
(for Suspension Bolt)
Air Inlet
22
n
m
x
22
30
20
300
Remote Control Switch
g
33.5
30
22
Viewed from A
20
120
l - 6
300
Drain Pipe Connection
(2.0 to 5.0HP Standard Position) (VP25)
(Around the Flange)
c x 300 = d
Drain Pipe Connection
(0.8 to 1.5HP with Drain-Up
Mechanism)
Refrigerant Liquid Pipe Connection
(With h Flare Nut)
45
A
v
2x90=180
u
f
48.5
35
23
s
t
p
97
q
220
75 (Electrical Control Box)
r
a
2xv=w
Refrigerant Gas Pipe Connection
(With i Flare Nut)
Air Outlet
90
e
j (Refrigerant Gas Pipe Connection)
246 (Refrigerant Liquid Pipe Connection)
321 (Refrigerant Gas Pipe Connection)
377 (Drain Pipe Connection: 2.0 to 5.0HP)
402 (Drain Pipe Connection: 0.8 to 1.5HP)
90 (Drain Pipe Connection)
k (Refrigerant Liquid Pipe Connection)
Dimension
HP
0.8
1.0
1.5
2.0
2.5
3.0
4.0
5.0
a
b
c
d
e
f
g
h
i
j
k
650
650
650
900
900
650
900
1300
730
730
730
980
980
730
980
1380
1
1
1
2
2
1
2
3
300
300
300
600
600
300
600
900
215
215
215
190
190
215
190
240
553
553
553
803
803
553
803
1203
583
583
583
833
833
583
833
1233
6.35
6.35
6.35
6.35
9.53
9.53
9.53
9.53
12.7
12.7
12.7
15.88
15.88
15.88
15.88 (19.05)*1
15.88 (19.05)*1
70
70
70
77
77
77
81
81
92
92
92
92
95
95
95
95
*1: In case of using R407C or R22, use 19.05
Dimension
HP
0.8
1.0
1.5
2.0
2.5
3.0
4.0
5.0
l
m
n
p
q
r
s
t
u
v
w
x
10
10
10
12
12
10
12
14
676
676
676
676
676
756
756
756
720
720
720
720
720
800
800
800
23
23
23
23
23
103
103
103
270
270
270
270
270
350
350
350
182
182
182
182
182
204
204
204
222
222
222
222
222
244
244
244
43
43
43
43
43
123
123
123
220
220
220
220
220
300
300
300
100
100
100
100
100
140
140
140
200
200
200
200
200
280
280
280
226
226
226
226
226
306
306
306
1-43
DIMENSIONAL DATA
In-the-Ceiling Type
Models: RPI-8FSN and RPI-10FSN
Unit: mm
21 - 3
1034 (for Suspension Bolts)
1100 (Duct Size <outer size>)
1372
(170)
78
100
420
(Duct Size <outer size>)
23
1250 (Unit)
50 x 20 = 1000
50
15
10
102
25
Air Intake Side
2, 3
Air Discharge Side
3
1326 (for Suspension Bolts)
4 - M10 Holes
(for Suspension Bolts)
50 x 21 = 1050
1100 (Duct Size <outer size>)
22 - 3
340
60
(Duct Size <outer size>)
1124
1120
24
1067
29
10
Drain Pipe Connection
(for using Drain-up Mechanism)
15
Refrigerant Liquid Pipe Connection
(b: Brazing)
Cutout for Remote Control Switch Cable
470
340
105
249
327
44
41
95
Cutout for Power Source Cable
164
35
30
420
50 x 7 = 350
20
120
50x6=300
Refrigerant Gas Pipe Connection
(a: Brazing)
Electrical Control Box
20
Remote Control Switch
PC-AR (Optional)
422
Drain Pipe Connection (VP-25)
489
Min. 20
(Standard Drain Piping Position)
Switch Box
JISC8336-1985
(Field-Supplied)
Wall Mounting
20
Service Access Panel
Embedding Cable
in the Wall
Service Space
1 : Secure the service space of false ceiling
for cleaning the heat exchanger.
2 : Use the air filter (field-supplied) at the intake side.
And secure the service space for the air filter.
3 : Use the canvas duct between the indoor unit and duct
for duct connection in order to eliminate vibration.
(at intake and discharge sides)
730
0
~20
150
200
Ceiling
* Prepare the Service Access Panel for service.
* In case that the ceiling board is not be detachable
for servicing, prepare a service access panel below
the indoor unit for removing the indoor unit.
Mounting for Remote Control Switch PC-AR (Optional)
800
~30
Dim.
0
450
50
450
Service Access Panel
50
Min. 20
20
0
135
1
HP
Ref.
8.0
10.0
R410A
R22, R407C (*)
R410A
R22, R407C (*)
a
b
19.05
25.4
22.2
28.6
9.53
12.7
9.53
12.7
(*): In case of using R22 or R407C, use the accessory adaptor.
1-44
DIMENSIONAL DATA
4-Way Cassette Type
Models: RCI-1.0FSN2, RCI-1.5FSN2, RCI-2.0FSN2 and RCI-2.5FSN2 with Air Panel P-N23WA (Optional)
Unit: mm
Mark
1
2
3
4
5
6
7
8
9
10
11
12
13
20
840
860~910
(Opening Hole for Ceiling)
20
4-14 x 26 Holes
(for Suspension Bolt)
760
(for Suspension Bolt)
Name
Air Outlet
Air Inlet
Refrigerant Gas Pipe Connection
Refrigerant Liquid Pipe Connection
Drain Pipe Connection
Wiring Hole for Conduit Tube
Wiring Hole
Suspension Bracket
Suspension Bolt
Supply Duct Connection
Supply Duct Connection
Remote Control Switch (PC-AR)
Shielded Twist-Pair Cable for PC-AR
Dimension
HP
20
B
110 (Gas Pipe)
180 (Liquid Pipe)
8
710 (Drain Pipe)
3
1.0
1.5
2.0
2.5
4
9
Suspension Bolts M10 or W3/8
(Field-Supplied)
a
b
12.7
12.7
15.88
15.88
6.35
6.35
6.35
9.53
Remark
4-Way
with a Flare Nut
with b Flare Nut
VP25
32.5 Knockout Hole
30 x 39 Hole
4-M10 or W3/8
150 x 385 Knockout Hole
150 x 400 Knockout Hole
without Cable
Min. 0.75mm2, Field-Supplied
D
Duct Adapter Connection
5
Viewed from C
E
E
248
7
30
220
100
6 In case of using this,
31
127
25
5
145
cut the insulation material
along to the line indicated
opening position.
9-M4
(for Self-Tapping Screw)
85
25
75
135
75
135
Enlarged View of D
Viewed from B
950
385
150
1
2
120
10
In case of using this,
cut the insulation material
along to the line indicated
opening position.
46
13 (Field-Supplied)
10
12
Air Inlet Grille
Optional Air Panel
11
In case of using this,
cut the insulation material
along to the line indicated
opening position.
400
50
220
100
150
145
Switch Box
JISC8336-1985
(Field-Supplied)
20
Viewed from A
Embedding Cable
in the Wall
Wall Mounting
9-M4
(for Self-Tapping Screw)
Min.
500
Surroundings
in the Ceiling
Min.
500
135
135
75
Min.
100
Min.
100
Min.
100
Min.
500
10
75
Enlarged View of E
Mounting for Remote Control Switch (Optional)
Service Space
10
20
25
950
Min.
3000
Min.
500
NOTE:
Piping Connection
Service Access Panel
Separated Installation
Service Access Panel
Piping Connection
Min.
100
Min.
100
Distance between the wall and panel edge must be
a min. 1500mm to prevent short circuiting.
Min.
100
Optional
6
37
102
A
7
118 (Drain Pipe)
31
36
102 (Gas Pipe)
127 (Liquid Pipe)
C
46
24 (Drain Pipe)
860~910
(Opening Hole for Ceiling)
840
760
(for Suspension Bolt)
14
18 (Gas Pipe)
25 (Liquid Pipe)
20
Service Access
Panel
Piping Connection
Closed Installation
1-45
DIMENSIONAL DATA
4-Way Cassette Type
Models: RCI-3.0FSN2, RCI-4.0FSN2 and RCI-5.0FSN2 with Air Panel P-N23WA (Optional)
Unit: mm
20
860~910
(Opening Hole for Ceiling)
840
20
4-14 x 26 Holes
(for Suspension Bolt)
760
(for Suspension Bolt)
20
860~910
(Opening Hole for Ceiling)
760
(for Suspension Bolt)
840
18 (Gas Pipe)
Name
Air Outlet
Air Inlet
Refrigerant Gas Pipe Connection
Refrigerant Liquid Pipe Connection
Drain Pipe Connection
Wiring Hole for Conduit Tube
Wiring Hole
Suspension Bracket
Suspension Bolt
Supply Duct Connection
Supply Duct Connection
Remote Control Switch (PC-AR)
Shielded Twist-Pair Cable for PC-AR
Dimension
20
3.0
4.0
5.0
110 (Gas Pipe)
180 (Liquid Pipe)
8
9
Suspension Bolts M10 or W3/8
(Field-Supplied)
710 (Drain Pipe)
4-Way
with a Flare Nut
with b Flare Nut
VP25
32.5 Knockout Hole
30 x 39 Hole
4-M10 or W3/8
150 x 385 Knockout Hole
150 x 400 Knockout Hole
without Cable
Min. 0.75mm2, Field-Supplied
a
b
15.88
15.88 (19.05)*1
15.88 (19.05)*1
9.53
9.53
9.53
HP
B
Remark
*1: In case of using R407C or R22, use 19.05.
D
Duct Adapter Connection
3
4
Viewed from C
5
E
298
1
7
145
25
5
127
31
30
100
6 In case of using this,
cut the insulation material
along to the line indicated
opening position.
9-M4
(for Self-Tapping Screw)
85
25
75
135
135
75
Enlarged View of D
Viewed from B
950
385
220
150
2
120
10
In case of using this,
cut the insulation material
along to the line indicated
opening position.
96
13 (Field-Supplied)
10
12
Air Inlet Grille
Optional Air Panel
400
220
11
In case of using this,
cut the insulation material
along to the line indicated
opening position.
50
100
150
145
Switch Box
JISC8336-1985
(Field-Supplied)
950
Embedding Cable
in the Wall
Min.
500
Min.
500
Surroundings
in the Ceiling
Min.
100
Min.
100
Service Space
Min.
500
9-M4
(for Self-Tapping Screw)
10
75
135
135
75
Enlarged View of E
Min.
100
Mounting for Remote Control Switch (Optional)
10
20
Wall Mounting
25
20
Viewed from A
Min.
3000
Min.
500
NOTE:
Piping Connection
Service Access Panel
Separated Installation
Service Access Panel
Piping Connection
Min.
100
Min.
100
Distance between the wall and panel edge must be
a min. 1500mm to prevent short circuiting.
Min.
100
Optional
6
37
102
A
7
118 (Drain Pipe)
31
36
102 (Gas Pipe)
127 (Liquid Pipe)
C
E
96
24 (Drain Pipe)
14
25 (Liquid Pipe)
Mark
1
2
3
4
5
6
7
8
9
10
11
12
13
Service Access
Panel
Piping Connection
Closed Installation
1-46
DIMENSIONAL DATA
2-Way Cassette Type
Models:
RCD-1.0FSN2, RCD-1.5FSN2, RCD-2.0FSN2, RCD-2.5FSN2 and RCD-3.0FSN2
with Air Panel P-N23DWA (Optional)
Unit: mm
20
1060 (Opening Hole for Ceiling)
Mark
1
2
3
4
5
6
7
8
9
10
11
12
13
20
890 (for Suspension Bolt)
4-12x32 Hole
(for Suspension Bolt)
860
20
8
670
(Opening Hole for Ceiling)
540
(for Suspension Bolt)
620
20
12
Name
Air Outlet
Air Inlet
Refrigerant Gas Pipe Connection
Refrigerant Liquid Pipe Connection
Drain Pipe Connection
Wiring Hole for Conduit Tube
Wiring Hole
Suspension Bracket
Suspension Bolt
Electrical Control Box
Supply Duct Connection
Remote Control Switch (PC-AR)
Shielded Twist-Pair Cable for PC-AR
Remark
with a Flare Nut
with b Flare Nut
VP25
32.5
30 x 39 Hole
4-M10 or W3/8
2-150 x 400
Optional
Min. 0.75mm2, Field-Supplied
410
95 (Gas Pipe)
5
95 (Liquid Pipe)
4
3
285
Dimension
9
HP
1.0
1.5
2.0
2.5
3.0
205
25 (Drain Pipe)
50
125
298
E
b
12.7
12.7
15.88
15.88
15.88
6.35
6.35
6.35
9.53
9.53
30
B
260
115
D
a
11
445
A
In case of using 11 ,
Cut out the insulation
material along this line.
9-M4
(for Self-Tapping Screw)
Optional
13
12
170
(Field-Supplied)
400
10
120
710
135
Cut out the insulation
material along this line.
30
15
6
7
15
180
150
1
55
140
70
150
135 80
430
90
Enlarged View of D
2
11
1
50
1100
9-M4
(for Self-Tapping Screw)
400
Viewed from B
Viewed from A
35
150
180
Service Access Panel
170
70
120
55
120 120
In case of using 11 ,
Cut out the insulation
material along this line.
Service Access Panel
185
MIN.
100
Separated Installation
MIN.
500
MIN.
500
MIN.
500
MIN.
3000
Viewed from E
MIN.
100
MIN.
500
185
430
Piping Connection
MIN.
100
15
30
MIN.
500
Surroundings
in the ceiling
15
110
Piping Connection
MIN.
500
Switch Box
JISC8336-1985
(Field-Supplied)
20
MIN.
500
Wall Mounting
Embedding Cable
in the Wall
Mounting for Remote Control Switch (Optional)
Closed Installation
Service Space
20
NOTE:
1. Distance between the wall and panel edge must
be a min. 1500mm to prevent short circuiting.
1-47
DIMENSIONAL DATA
2-Way Cassette Type
Models: RCD-4.0FSN2 and RCD-5.0FSN2 with Air Panel P-N46DWA (Optional)
Unit: mm
20
1620 (Opening Hole for Ceiling)
20
1450 (for Suspension Bolt)
4-12 x 32 Hole
(for Suspension Bolt)
1420
670
620
Name
Air Outlet
Air Inlet
Refrigerant Gas Pipe Connection
Refrigerant Liquid Pipe Connection
Drain Pipe Connection
Wiring Hole for Conduit Tube
Wiring Hole
Suspension Bracket
Suspension Bolt
Electrical Control Box
Supply Duct Connection
Remote Control Switch (PC-AR)
Shielded Twist-Pair Cable for PC-AR
Remark
with 15.88 (19.05)*1 Flare Nut
with 9.53 Flare Nut
VP25
32.5
30 x 39 Hole
4-M10 or W3/8
2-150 x 610
Optional
Min. 0.75mm2, Field-Supplied
*1: In case of using R407C or R22, use 19.05.
20
540
20
12
Mark
1
2
3
4
5
6
7
8
9
10
11
12
13
8
95 (Gas Pipe)
410
5
95 (Liquid Pipe)
4
3
285
25 (Drain Pipe)
205
E
125
30
115
B
50
298
D
260
9
445
A
(Field-Supplied)
170
10-M4
(for Self-Tapping Screw)
610
160
15
150
55
10
120
180
70
140
1
30
13
180
Optional
12
15
710
180
180
11
140
In case of using 11 ,
Cut out the insulation
material along this line.
640
2
Enlarged View of D
1660
In case of using 11 ,
11
610
Cut out the insulation
material along this line.
160
160
170
160
55
Viewed from A
80
70
1
15
110
MIN.
500
Surroundings
in the ceiling
150
180
Service Access Panel
Piping Connection
30
10-M4
(for Self-Tapping Screw)
Service Access Panel
190
200
190
640
Viewed from E
MIN.
500
MIN.
100
MIN.
3000
Piping Connection
MIN.
500
Cut out the insulation
material along this line.
6
Switch Box
JISC8336-1985
(Field-Supplied)
MIN.
100
MIN.
500
Closed Installation
Separated Installation
20
90
Wall Mounting
50
MIN.
500
MIN.
500
MIN.
100
MIN.
500
7
Viewed from B
20
Embedding Cable
in the Wall
Mounting for Remote Control Switch (Optional)
Service Space
NOTE:
1. Distance between the wall and panel edge must
be a min. 1500mm to prevent short circuiting.
1-48
DIMENSIONAL DATA
Wall Type
Models: RPK-1.0FSNSM2 and RPK-1.5FSNSM2
Unit: mm
Name
Mark
Piping
Piping
Piping
2
Air Outlet
2
Air Inlet
3
Refrigerant Gas Pipe Connection
with 12.7 Flare Nut
4
Refrigerant Liquid Pipe Connection
with 6.35 Flare Nut
5
Drain Pipe Connection
VP16
6
Wiring and Piping Hole
Knockout Hole
7
Wiring and Piping Hole
65 Knockout Hole
8
Wiring and Piping Hole
65 Knockout Hole
9
Suspension Bracket
10
Remote Control Switch
(Option)
Wired
PC-AR
Wireless
PC-LH3A
2
780
210
6
5
5
60
280
6
60
Remark
1
47
Auto Louver
47
Receiver Part
1
10 Option
125
A
120
540
(PC-AR)
56
(PC-LH3A)
410
5
4
480
3
108
Viewed from A
44
Outline of the Unit
60
5
38
20
65
45
280
45
Flange Part for Inserting
Suspension Bracket
190
50 20 20 20 20 20 20
25 25 25 30 25 25 25
20
20x3=6
20
20
20
15 35 27 24 20
28
400
15
8
8
23 30 30
20 20 20
34 20 20 20 15 30 30 23 42 37
7.5
190
37.5
7.5
5
38
5
115
20
530
10
8
9
Min. 150
780
7
20
Wall Mounting
20
Embedding Cable
in the Wall
Min. 100
Min. 1000
Switch Box
JISC8336-1985
(Field-Supplied)
Min. 100
Unit: mm
Mounting for Remote Control Switch (Option)
(In case of using PC-AR)
Service Space
1-49
DIMENSIONAL DATA
Wall Type
Model: RPK-2.0FSNSM2
Unit: mm
Mark
Piping
2
Air Inlet
3
Refrigerant Gas Pipe Connection
with 15.88 or 12.7 Flare Nut (*1)
4
Refrigerant Liquid Pipe Connection
with 6.35 Flare Nut
5
Drain Pipe Connection
VP16
6
Wiring and Piping Hole
Knockout Hole
7
Wiring and Piping Hole
65 Knockout Hole
8
Wiring and Piping Hole
65 Knockout Hole
9
Suspension Bracket
10
Remote Control Switch
(Option)
Piping
2
Wired
PC-AR
Wireless
PC-LH3A
(*1): The refrigerant piping size may be required to change depending
on the outdoor unit to be connected. If 12.7 pipe is used at
the gas side, remove the flare adaptor at the indoor unit gas piping.
Then attach the flare nut (accessory) for pipe connection.
2
1030
208
6
60
5
60
295
6
5
Remark
Air Outlet
Piping
1019
Name
1
47
47
Auto Louver
1
Indication Part
10 Option
Receiver Part
A
3
125
4
120
(PC-AR)
Pipe Diameter
a
15.88
440
12.7
410
P
Gas Pipe Connection
(12.7)
56
Flare Adaptor
(PC-LH3A)
a
5
470
550
Gas Pipe Connection
(15.88)
150
Enlarged View P
Viewed from A
Flange Part for Inserting
Suspension Bracket
Outline of the Unit
314
20
38.1
50 50 40
266
38.1 24.9
40 50 50
13.1
22
20x5=100
20
20 20
20 20
20
30 30
40 40
20 12
8.5
15
55
20
4
21.9
15
8.5
8
150
6.5
48.5
20
12.5
8.5
7
9
Min. 150
200
15x4=60
80
30 30
45
48.5
45 49
295
9.5
25
450
21.9
13.1
25
1030
Switch Box
JISC8336-1985
(Field-Supplied)
Wall Mounting
20
Embedding Cable
in the Wall
Min. 100
Min. 100
Min. 1000
20
Unit: mm
Mounting for Remote Control Switch (Option)
(In case of using PC-AR)
Service Space
1-50
DIMENSIONAL DATA
Wall Type
Models: RPK-2.5FSNSM2, RPK-3.0FSNSM2 and RPK-4.0FSNSM2
Unit: mm
Mark
Air Outlet
2
Air Inlet
3
Refrigerant Gas Pipe Connection
with 15.88 Flare Nut
4
Refrigerant Liquid Pipe Connection
with 9.53 Flare Nut
5
Drain Pipe Connection
VP16
6
Wiring and Piping Hole
Knockout Hole
7
Wiring and Piping Hole
80 Knockout Hole
8
Wiring and Piping Hole
80 Knockout Hole
9
Suspension Bracket
10
Remote Control Switch
(Option)
Piping
Piping
2
Remark
1
1140
Piping
Name
Wired
PC-AR
Wireless
PC-LH3A
2
1150
245
6
70
60
60
Auto Louver
1
Indication Part
Receiver Part
A
10 Option
5
125
4
8
8
70
333
6
120
56
(PC-AR)
(PC-LH3A)
550
3
572
654
141
Viewed from A
565
433.6
780
660
560
105
250
50x4
28
100
105
87
50x4
42
300
300
58
8
Outline of the Unit
7
141
9
1150
Flange Part for
Inserting Suspension Bracket
Min. 100
42
93
60
10
Switch Box
JISC8336-1985
(Field-Supplied)
20
Wall Mounting
20
Embedding Cable
in the Wall
Min. 100
Min. 200
Min. 1000
333
229
20
141
20
221
40 20
20
25
20
20x5
100
Unit: mm
Mounting for Remote Control Switch (Option)
(In case of using PC-AR)
Service Space
1-51
1-51
DIMENSIONAL DATA
Floor Type
Models: RPF-1.0FSN2E and RPF-1.5FSN2E
30
Unit: mm
157
168
40
163
220
156
52
133
134
260
388
529
630
182
a
View from Front Side
Location of Fixing Holes on
Floor for Wood Screws (4-M5)
b
c
d
a
a
Location of Fixing Holes
on Floor for Bolts (2-M8)
228
630
315
220
103
For Bolt
2-12, 15x18
c
140
b
a
220
85
60
View from Upper Side
Location of Fixing Holes on Wall
630
Min.
1000
Ceiling
Min.
300
Wall
a
Min.
300
Wall
Service Access
Mark
1
2
3
4
5
6
7
8
9
10
11
12
Name
Air Intlet
Air Outlet
Refrigerant Gas Line
Refrigerant Liquid Line
Condensate Drain Hose
Drain Pan
Fixing Hole on Wall
Adjusting Screw
Fixing Hole on Floor
Fixing Hole on Floor
Opening for Wiring
Space for Piping Connection on Floor
Dimension
HP
1.0
1.5
Remark
Piping Connection with Flare Nut 12.7
Piping Connection with Flare Nut 6.35
18.5 Outer Diameter
4-14 (Rear)
For Installation
4-7 for Wood Screw
Rear Side
a
b
c
d
1045
1170
754
879
217
217
732
857
1-52
DIMENSIONAL DATA
Floor Concealed Type
Models: RPFI-1.0FSN2E and RPFI-1.5FSN2E
220
Unit: mm
220
122
72
64
133
19
13
50
52
529
100
114
134
260
388
620
315
52
25
55
b
36
85 60
a
103
View from Front Side
b
a
b
c
138
620
315
220
103
220
85
60
View from Upper Side
c
d
a
a
77
640
620
Min.
1000
Location of Fixing Holes on
Floor for Wood Screws (4-M5)
Min.
240
a
Mark
1
2
3
4
5
6
7
8
9
Min.
240
Min.
240
Name
Air Intlet
Air Outlet
Refrigerant Gas Line
Refrigerant Liquid Line
Condensate Drain Hose
Drain Pan
Fixing Hole on Wall
Adjusting Screw
Fixing Hole on Floor
Dimension
HP
1.0
1.5
a
Min.
240
Remark
Piping Connection with Flare Nut 12.7
Piping Connection with Flare Nut 6.35
18.5 Outer Diameter
4-14 (Rear)
For Installation
4-7 for Wood Screw
a
b
c
d
863
988
754
879
66
66
732
857
1-53
DIMENSIONAL DATA
Ceiling Type
Models: RPC-2.0FSN2, RPC-2.5FSN2 and RPC-3.0FSN2
Unit: mm
370
3
92
Cut out the resin along this line.
12
(Field-Supplied)
11
Optional
110
70
110
670
280
148
27
9
120
4-12
(Hole for Suspension Bolt)
b
(50)
10
(50)
a
Max.50
Suspension Bolt Length
c
160
52
8
70
118
12
70
4
216
210
38
Suspension Bracket
12
1
74
Left Side
176
Switch Box
JISC8336-1985
(Field-Supplied)
20
20
305
Wall Mounting
Embedding Cable
in the Wall
Mounting for Remote Control Switch (Optional)
2
Refrigerant Gas Piping
with 15.88 Flare Nut
Refrigerant Liquid Piping
with e Flare Nut
205
5
106
7
Cut out the resin along this line.
135
40
130
40
104
67
d
156
175
102
370
6
Piping Position
9
MIN.
300
MIN.40
MIN.
500
Mark
Name
1
Air Outlet
2
Air Inlet
3
Hole for Refrigerant Piping
MIN.8
MIN.400
Separated Installation
MIN.40
MIN.
300
Closed Installation
Service Space
Remark
MIN.
300
4
Hole for Refrigerant Piping
5
Hole for Refrigerant Piping
6
Drain Piping Connection
7
Hole for Drain Piping
8
Hole for Drain Piping
9
10
11
12
Wiring Hole for Conduit Tube
Suspension Bracket
Remote Control Switch (PC-AR)
Shielded Twist-Pair Cable for PC-AR
Dimension
HP
2.0
2.5
3.0
Hole for Upper Side Arrangement
Knockout Hole
for Right Side Arrangement
Hole for Rear Side Arrangement
VP20
(for Rear Right Side Arrangement)
VP20
(for Rear Left Side Arrangement)
Knockout Hole
for Left Side Arrangement
26.5 Hole
Optional
Min. 0.75mm2, Field-Supplied
a
b
c
d
e
1100
1320
1320
1000
1220
1220
960
1180
1180
200
195
195
6.35
9.53
9.53
1-54
DIMENSIONAL DATA
Ceiling Type
Models: RPC-4.0FSN2 and RPC-5.0FSN2
Unit: mm
280
9
Cut out the resin
along this line.
70
92
(Field-Supplied)
110
12
147
27
110
3
Optional
670
280
11
120
4-12
(Hole for Suspension Bolt)
b
(50)
10
c
52
8
118
70
12
270
70
4
Max.50
Suspension Bolt Length
38
Suspension Bracket
160
1
12
a
276
(50)
74
Left Side
176
Switch Box
JISC8336-1985
(Field-Supplied)
20
20
305
Wall Mounting
Embedding Cable
in the Wall
Mounting for Remote Control Switch (Optional)
2
210
Refrigerant Gas Piping with 15.88 (*1) Flare Nut
195
Refrigerant Liquid Piping with 9.53 Flare Nut
156
5
106
7
Cut out the resin along this line.
40
130
104
67
*1: In case of using R407C or R22, use 19.05.
135
175
103
280
6
9
MIN.
300
MIN.40
Separated Installation
MIN.40
MIN.
300
Closed Installation
Service Space
MIN.
500
Piping Position
Mark
Name
1
Air Outlet
2
Air Inlet
3
Hole for Refrigerant Piping
MIN.8
MIN.
400
MIN.
300
Remark
4
Hole for Refrigerant Piping
5
Hole for Refrigerant Piping
6
Drain Piping Connection
7
Hole for Drain Piping
8
Hole for Drain Piping
9
10
11
12
Wiring Hole for Conduit Tube
Suspension Bracket
Remote Control Switch (PC-AR)
Shielded Twist-Pair Cable for PC-AR
Dimension
HP
4.0
5.0
Hole for Upper Side Arrangem
Knockout Hole
for Right Side Arrangement
Hole for Rear Side Arrangem
VP20
(for Rear Right Side Arrangem
VP20
(for Rear Left Side Arrangem
Knockout Hole
for Left Side Arrangement
26.5 Hole
Optional
Min. 0.75mm2, Field-Supplied
a
b
c
1320
1580
1220
1480
1180
1440
1-55
DIMENSIONAL DATA
3.2
Dimensional Data for Total Heat Exchangers
Total Heat Exchangers
Models: KPI-2521, KPI-5021, KPI-8021 and KPI-10021
Unit: mm
EA and OA ducts are applicable from this side.
K
Damper plate
E
Air Exhaust Fan
EA
RA
(Exhaust Air)
(Standard Position)
D
F
A
(Return Air)
Power Cord Opening
SA
115
OA
(Outside Air)
(Standard Position)
(Supply Air)
K
150 to 250
Min.600
22
10
C
Air Supply Fan
Service Access
Panel Position
Electrical Control Box
Service Cover
Heat Exchanging Element
G
B
G
K
J
H
Suspension Bracket
Air Filters
Model
KPI-2521
KPI-5021
Duct
Diameter
A
B
C
D
E
F
G
H
J
735
780
275
765
700
530
63
142
160
1,016
888
317
1,048
790
745
79
192
208
1,004
1,164
398
1,036
1,030
690
79
242
258
1,231
1,164
398
1,263
1,030
920
79
242
258
Duct
(direction change)
K
102
124
149
149
Outer
Dimension
For
Suspension Bolt
Duct
KPI-8021 KPI-10021
1-56
SELECTION DATA
4. Selection Data
4.1
Operation Space
In-the-Ceiling Type
Models: RPI-0.8FSN2, RPI-1.0FSN2, RPI-1.5FSN2, RPI-2.0FSN2, RPI-2.5FSN2, RPI-3.0FSN2,
RPI-4.0FSN2 and RPI-5.0FSN2
Electrical Box
Service Space
of False Ceiling
400
600
275
Rear Side
In case that the
ceiling board can
not be detected
for servicing,
prepare a service
access door
below the indoor
unit for removing
the indoor unit.
Min.
1000
Rear Side
100
Service Access
Door (Min. 450)
Front Side
View from Bottom
(130)
Min.
1000
35
Front Side
Min.
600
Min. 600
View from Top
Models: RPI-8FSN and RPI-10FSN
Min. 20
Service Space
730
800
150
~30
~20
0
0
0
450
135
50
50
Service Access Panel
Secure the service space
of false ceiling for cleaning
the heat exchanger.
450
Min. 20
200
Ceiling
* Prepare the Service Access Panel for service.
* In case that the ceiling board is not be detachable
for servicing, prepare a service access panel below
the indoor unit for removing the indoor unit.
Service Access Panel
4-Way Cassette Type
Models: RCI-1.0FSN2, RCI-1.5FSN2, RCI-2.0FSN2, RCI-2.5FSN2, RCI-3.0FSN2,
RCI-4.0FSN2 and RCI-5.0FSN2
Min.
1500
Min. 500
Min.
1500
Min.
1500
Min.
3000
Min.
1500
Min.
1500
Min.
1500
Min.
1500
Min.
1500
Min.
1500
Min.
1500
Unit: mm
Min. 100
Piping
Connection
Side
Min. 100
Min. 500
Min. 1000
Piping Connection
Service Access Door
Separated Installation
Piping Connection
Service Access Door
Piping Connection
Service Space
Service Access Door
Closed Installation
Distance from Wall Side
1-57
SELECTION DATA
2-Way Cassette Type
Models: RCD-1.0FSN2, RCD-1.5FSN2, RCD-2.0FSN2, RCD-2.5FSN2, RCD-3.0FSN2,
RCD-4.0FSN2 and RCD-5.0FSN2
Service
Access
Panel
Min. 1500
Min.
1500
Min. 1500
10 to 20mm
298mm
Unit Height
in False Celling
Service
Access
Panel
Min.
1500
Min.
1500
Unit Height in False Celling
Min.
1500
Min. 1500
Min. 3000
Piping Connection Side
Separated Installation
Service
Access
Panel
Min.
1500
Min. 100
Min. 500
Piping
Connection
Side
Min.
1500
Min. 1500
Min. 500
Min. 500
Min. 1000
Piping Connection Side
Service Space
Closed Installation of Two Units
Distance from Wall Side
Wall Type
Models: RPK-1.0FSNSM2 and RPK-1.5FSNSM2
Model: RPK-2.0FSNSM2
Min.
100
Min.
100
Min.
100
Min.
100
Min.
1000
Unit: mm
Min.
1000
Min.
150
Min.
150
Unit: mm
Unit: mm
Min.
100
Min.
200
Min.
1000
Min.
100
Models: RPK-2.5FSNSM2, RPK-3.0FSNSM2 and RPK-4.0FSNSM2
1-58
SELECTION DATA
Floor Type
Models: RPF-1.0FSN2E and RPF-1.5FSN2E
Min.
1000
Ceiling
Wall
630
Wall
Floor
1170 (1.5HP)
1045 (1.0HP)
Min. 300
Min. 300
Floor Concealed Type
Models: RPFI-1.0FSN2E and RPFI-1.5FSN2E
Ceiling
620
Front Air Outlet
640
Upward Air Outlet
Short
Flexible Duct
Min.
1000
Ceiling
Min.
240
Floor
Min.
Min.
240
901 (1.5HP) 240
776 (1.0HP)
Floor
901 (1.5HP)
776 (1.0HP)
Min.
240
Service Space
Ceiling Type
Models: RPC-2.0FSN2, RPC-2.5FSN2, RPC-3.0FSN2, RPC-4.0FSN2 and RPC-5.0FSN2
Min. 500
(mm)
Min. 300
Min. 40
Min. 8
Min. 400
150 to 250
EA
RA
OA
SA
450
Min. 600
Min. 200
Total Heat Exchangers
Models: KPI-2521, KPI-5021, KPI-8021 and KPI-10021
Service Access
Door (450 x 450)
450
1-59
SELECTION DATA
4.3
Sensible Heat Factor (SHF)
The sensible heat factor of indoor units at each fan speed (Hi, Me, Lo) based on the JIS Standard B8616, is
given in the below.
Model
RPI-0.8FSN2
RPI-1.0FSN2
RPI-1.5FSN2
RPI-2.0FSN2
RPI-2.5FSN2
RPI-3.0FSN2
RPI-4.0FSN2
RPI-5.0FSN2
RPI-8FSN
RPI-10FSN
RCI-1.0FSN2
RCI-1.5FSN2
RCI-2.0FSN2
RCI-2.5FSN2
RCI-3.0FSN2
RCI-4.0FSN2
RCI-5.0FSN2
RCD-1.0FSN2
RCD-1.5FSN2
RCD-2.0FSN2
RCD-2.5FSN2
RCD-3.0FSN2
RCD-4.0FSN2
RCD-5.0FSN2
RPK-1.0FSNSM2
RPK-1.5FSNSM2
RPK-2.0FSNSM2
RPK-2.5FSNSM2
RPK-3.0FSNSM2
RPK-4.0FSNSM2
RPF-1.0FSN2E
RPF-1.5FSN2E
RPFI-1.0FSN2E
RPFI-1.5FSN2E
RPC-2.0FSN2
RPC-2.5FSN2
RPC-3.0FSN2
RPC-4.0FSN2
RPC-5.0FSN2
Hi
0.73
0.73
0.74
0.73
0.70
0.71
0.69
0.73
0.72
0.71
0.85
0.81
0.74
0.74
0.74
0.72
0.70
0.81
0.73
0.74
0.70
0.69
0.70
0.69
0.78
0.73
0.69
0.71
0.74
0.71
0.73
0.73
0.73
0.73
0.74
0.72
0.71
0.73
0.70
SHF
Me
0.71
0.71
0.71
0.70
0.68
0.67
0.67
0.68
0.83
0.77
0.71
0.70
0.67
0.71
0.66
0.76
0.70
0.70
0.69
0.69
0.68
0.67
0.74
0.72
0.68
0.69
0.70
0.69
0.69
0.69
0.69
0.69
0.71
0.69
0.68
0.70
0.68
Lo
0.68
0.68
0.67
0.66
0.66
0.63
0.64
0.65
0.81
0.72
0.69
0.68
0.65
0.68
0.64
0.75
0.68
0.67
0.67
0.67
0.66
0.65
0.71
0.70
0.67
0.68
0.69
0.68
0.65
0.65
0.65
0.65
0.68
0.67
0.66
0.68
0.66
1-62
SELECTION DATA
4.4
Fan Performance
RPI-0.8FSN2, 1.0FSN2
RPI-1.5FSN2
: Normal Mode (at shipping)
: High Static Pressure Mode
: Low Staitc Pressue Mode
140
140
130
130
120
120
110
110
100
90
80
Hi
70
Me
60
50
Lo
Hi
Me
40
Lo
30
90
Hi
80
70
60
Me
50
40
Hi
Me
Lo
Hi
Lo
Hi
Me
20
Lo
Lo
10
10
0
0
2
3
4
5
6
7
8
9
10
11
5
6
7
8
9
10
11
12
13
14
AIR VOLUME (m3/min)
AIR VOLUME (m3/min)
The setting of Normal, High Static Pressure,and Low Static Pressure Mode
can be changed by Remote Control Switch.
The setting of Normal, High Static Pressure,and Low Static Pressure Mode
can be changed by Remote Control Switch.
RPI-2.0FSN2
RPI-2.5FSN2
: Normal Mode (at shipping)
: High Static Pressure Mode
: Low Staitc Pressue Mode
150
140
140
130
130
120
120
110
110
100
90
Hi
80
70
60
Me
Hi
50
40
Lo
Me
30
90
Hi
80
70
60
Me
Hi
50
40
Me
Lo
Hi
Me
Lo
Me
20
100
30
Hi
Lo
: Normal Mode (at shipping)
: High Static Pressure Mode
: Low Staitc Pressue Mode
150
EXTERNAL STATIC PRESSURE (Pa)
EXTERNAL STATIC PRESSURE (Pa)
100
30
Me
20
: Normal Mode (at shipping)
: High Static Pressure Mode
: Low Staitc Pressue Mode
150
EXTERNAL STATIC PRESSURE (Pa)
EXTERNAL STATIC PRESSURE (Pa)
150
20
Lo
Lo
10
10
0
0
7
8
9
10
11
12
13
14
15
16
8
9
10
11
12
13
14
15
16
18
AIR VOLUME (m3/min)
AIR VOLUME (m3/min)
The setting of Normal, High Static Pressure,and Low Static Pressure Mode
can be changed by Remote Control Switch.
The setting of Normal, High Static Pressure,and Low Static Pressure Mode
can be changed by Remote Control Switch.
1-63
SELECTION DATA
PI-3.0FSN2
RPI-4.0FSN2
320
320
: Normal Mode (at shipping)
: High Static Pressure Mode
: Low Staitc Pressue Mode
280
280
260
260
240
240
220
220
200
180
Hi
160
140
Me
Hi
120
Me
100
Lo
80
Lo
: Normal Mode (at shipping)
: High Static Pressure Mode
: Low Staitc Pressue Mode
300
EXTERNAL STATIC PRESSURE (Pa)
EXTERNAL STATIC PRESSURE (Pa)
300
Hi
200
180
Hi
160
140
Hi
120
Me
100
Me
Lo
80
60
60
40
40
Lo
Lo
20
20
0
Hi
Me
Lo
Me
0
11
12
13
14
15
16
17
18
19
20
13
15
17
19
21
23
25
27
29
31
AIR VOLUME (m3/min)
AIR VOLUME (m3/min)
The setting of Normal, High Static Pressure, and Low Static Pressure Mode
can be changed by Remote Control Switch.
The setting of Normal, High Static Pressure,and Low Static Pressure Mode
can be changed by Remote Control Switch.
PI-5.0FSN2
320
: Normal Mode (at shipping)
: High Static Pressure Mode
: Low Staitc Pressue Mode
300
280
260
EXTERNAL STATIC PRESSURE (Pa)
240
220
200
180
Hi
160
140
Hi
120
Me
100
Lo
80
60
Me
Hi
Lo
Me
40
Lo
20
0
23
25
27
29
31
33
35
37
39
41
AIR VOLUME (m3/min)
The setting of Normal, High Static Pressure,and Low Static Pressure Mode
can be changed by Remote Control Switch.
1-64
SELECTION DATA
RPI-8FSN
High Static Pressure Setting: 220Pa (at shipping)
Low Static Pressure Setting: 110Pa
High Static Pressure Setting: 260Pa (at shipping)
Low Static Pressure Setting: 130Pa
380V/50Hz
380V/60Hz
415V/50Hz
350
100
50
250
200
150
Upper Limit of Air Volume
150
Upper Limit of Air Volume
200
300
Lower Limit of Air Volume
250
Lower Limit of Air Volume
EXTERNAL STATIC PRESSURE (Pa)
300
EXTERNAL STATIC PRESSURE (Pa)
350
100
50
0
40
45
50
55
65
60
70
0
75
40
45
3
50
55
60
65
70
75
AIR VOLUME (m3/min)
AIR VOLUME (m /min)
The setting of High Static Pressure and Low Static Pressure Mode can be
changed by changing the position of the connector inside of the indoor unit.
The setting of High Static Pressure and Low Static Pressure Mode can be
changed by changing the position of the connector inside of the indoor unit.
RPI-10FSN
High Static Pressure Setting: 220Pa (at shipping)
Low Static Pressure Setting: 110Pa
380V/50Hz
380V/60Hz
350
High Static Pressure Setting: 260Pa (at shipping)
Low Static Pressure Setting: 130Pa
415V/50Hz
350
100
50
0
200
150
Upper Limit of Air Volume
150
250
Lower Limit of Air Volume
200
Upper Limit of Air Volume
250
EXTERNAL STATIC PRESSURE (Pa)
300
Lower Limit of Air Volume
EXTERNAL STATIC PRESSURE (Pa)
300
100
50
55
60
65
70
80
75
85
90
3
AIR VOLUME (m /min)
The setting of High Static Pressure and Low Static Pressure Mode can be
changed by changing the position of the connector inside of the indoor unit.
0
55
60
65
70
75
80
85
90
AIR VOLUME (m3/min)
The setting of High Static Pressure and Low Static Pressure Mode can be
changed by changing the position of the connector inside of the indoor unit.
1-65
SELECTION DATA
KPI-2521
Fan Performance and Heat Exchange Efficiency Curve
Model:KPI-2521
Fan Performance and Heat Exchange Efficiency Curve
Model: KPI-2521
(50Hz)
Heat Exchange Efficiency (%)
70
60
Total Heat Exchanger Efficiency
(Heating Operation)
Total Heat Exchanger Efficiency
(Cooling Operation)
250
External Static Pressure (Pa)
70
60
50
150
Duct
Length
200
150
Hi
30m
Me
100
20m
Lo
50
10m
50
100
150
200
250
300
350
Total Heat Exchange Efficiency
(Heating Operation)
Total Heat Exchange Efficiency
(Cooling Operation)
250
150
Duct
Length
200
40m
0
0
Temperature Exchange
Efficiency
80
External Static Pressure (Pa)
Heat Exchange Efficiency (%)
Temperature Exchange
Efficiency
80
50
(60Hz)
90
90
40m
Hi
150
30m
Me
100
20m
Lo
50
0
0
10m
50
100
150
200
250
300
350
400
400
3
Air Volume (m /h)
3
Air Volume (m /h)
KPI-5021
Model: KPI-5021
Fan Performance and Heat Exchange Efficiency Curve
Model: KPI-5021
(50Hz)
90
Total Heat Exchanger Efficiency
(Heating Operation)
80
70
Total Heat Exchanger Efficiency
(Heating Operation)
60 300
Total Heat Exchanger Efficiency
(Cooling Operation)
50 250
200
Duct
Length
200
Hi
60m
50m
150
Me
40m
Lo
100
30m
20m
50
10m
0
0
100
200
300
400
Air Volume (m3/h)
500
600
700
(60Hz)
90
Temperature Exchange
Efficiency
80 400
70 350
60 300
Total Heat Exchange Efficiency
(Cooling Operation)
50 250
200
Duct
Length
Hi
External Static Pressure (Pa)
Heat Exchange Efficiency (%)
Temperature Exchange
Efficiency
External Static Pressure (Pa)
Heat Exchange Efficiency (%)
Fan Performance and Heat Exchange Efficiency Curve
200
60m
50m
150
Me
40m
Lo
100
30m
20m
50
10m
0
0
100
200
300
400
500
600
700
Air Volume (m3/h)
1-66
SELECTION DATA
KPI-8021
Model:KPI-8021
Fan Performance and Heat Exchange Efficiency Curve
(50Hz)
Model: KPI-8021
90
Temperature Exchange
Efficiency
600
70
500
Temperature Exchange
Efficiency
Heat Exchange Efficiency (%)
80
Total Heat Exchanger Efficiency
(Heating Operation)
60
400
Total Heat Exchanger Efficiency
(Cooling Operation)
External Static Pressure (Pa)
50
(60Hz)
90
300
250
Duct
Length
Hi
Lo
100m
80m
Me
60m
40m
20m
0
0
200
400
600
800
1000
600
70
500
Total Heat Exchange Efficiency
(Heating Operation)
60
1200
400
Total Heat Exchange Efficiency
(Cooling Operation)
50
200
100
80
External Static Pressure (Pa)
Heat Exchange Efficiency (%)
Fan Performance and Heat Exchange Efficiency Curve
300
250
Duct
Length
Hi
Lo
100m
200
80m
60m
Me
100
40m
20m
0
0
200
400
600
800
1000
1200
Air Volume (m3/h)
3
Air Volume (m /h)
Do not use the condition that External Static
Pressure is under than 29Pa.
Do not use the condition that the External Static
Pressure is under than 29Pa.
KPI-10021
Model:KPI-10021
Fan Performance and Heat Exchange Efficiency Curve
(50Hz)
Model: KPI-10021
(60Hz)
90 700
90 700
80 600
70 500
Total Heat Exchanger Efficiency
(Heating Operation)
60 400
Total Heat Exchanger Efficiency
(Cooling Operation)
250
Duct
Length
50 300
Heat Exchange Efficiency (%)
Temperature Exchange
Efficiency
Temperature Exchange
Efficiency
80 600
70 500
Total Heat Exchange Efficiency
(Heating Operation)
60 400
Total Heat Exchange Efficiency
(Cooling Operation)
250
Duct
Length
Hi
100m
50 300
Hi
Lo
80m
200
60m
Me
40m
100
20m
0
0
200
400
600
800
1000
1200
3
Air Volume (m /h)
Do not use the condition that the External Static
Pressure is under than 49Pa.
1400
External Static Pressure (Pa)
External Static Pressure (Pa)
Heat Exchange Efficiency (%)
Fan Performance and Heat Exchange Efficiency Curve
100m
Me
80m
Lo
200
60m
40m
100
20m
0
0
200
400
600
800
1000
1200
1400
Air Volume (m3/h)
Do not use the condition that External Static
Pressure is under than 49Pa.
1-67
ELECTRICAL DATA
5. Electrical Data
< 50 Hz >
Indoor Unit
Model
In-the-Ceiling
Type
4-Way
Cassette Type
2-Way
Cassette Type
Wall Type
Floor Type
Floor
Concealed Type
Ceiling Type
RPI-0.8FSN2
RPI-1.0FSN2
RPI-1.5FSN2
RPI-2.0FSN2
RPI-2.5FSN2
RPI-3.0FSN2
RPI-4.0FSN2
RPI-5.0FSN2
RPI-8FSN
RPI-10FSN
RCI-1.0FSN2
RCI-1.5FSN2
RCI-2.0FSN2
RCI-2.5FSN2
RCI-3.0FSN2
RCI-4.0FSN2
RCI-5.0FSN2
RCD-1.0FSN2
RCD-1.5FSN2
RCD-2.0FSN2
RCD-2.5FSN2
RCD-3.0FSN2
RCD-4.0FSN2
RCD-5.0FSN2
RPK-1.0FSNSM2
RPK-1.5FSNSM2
RPK-2.0FSNSM2
RPK-2.5FSNSM2
RPK-3.0FSNSM2
RPK-4.0FSNSM2
RPF-1.0FSN2E
RPF-1.5FSN2E
RPFI-1.0FSN2E
RPFI-1.5FSN2E
RPC-2.0FSN2
RPC-2.5FSN2
RPC-3.0FSN2
RPC-4.0FSN2
RPC-5.0FSN2
Unit Main Power
Applicable Voltage
Indoor Fan Motor
VOL
PH
HZ
Maximum
Minimum
PH
220/240
1
50
264
198
1
380/415
3
50
456
342
3
220/240
1
50
264
198
1
220/240
1
50
264
198
1
220/240
1
50
264
198
1
220/240
1
50
264
198
1
220/240
1
50
264
198
1
220/240
1
50
264
198
1
RNC
0.5/0.5
0.5/0.5
0.7/0.7
0.7/0.7
0.7/0.7
0.9/0.9
1.3/1.4
1.9/2.0
1.6/1.6
2.0/2.0
0.2/0.2
0.2/0.2
0.2/0.2
0.3/0.3
0.4/0.3
0.7/0.6
0.8/0.8
0.2/0.2
0.3/0.4
0.3/0.4
0.4/0.5
0.5/0.6
0.6/0.6
0.8/0.9
0.2/0.2
0.3/0.3
0.3/0.3
0.3/0.3
0.3/0.3
0.5/0.5
0.2/0.2
0.2/0.2
0.2/0.2
0.2/0.2
0.4/0.4
0.5/0.5
0.5/0.5
0.8/1.0
0.9/1.0
IPT
0.10/0.11
0.10/0.11
0.14/0.15
0.14/0.15
0.14/0.15
0.19/0.20
0.28/0.31
0.40/0.46
0.99/0.99
1.23/1.23
0.03/0.03
0.03/0.03
0.04/0.04
0.06/0.06
0.07/0.07
0.13/0.13
0.16/0.16
0.05/0.06
0.07/0.08
0.07/0.08
0.09/0.11
0.11/0.13
0.12/0.14
0.18/0.20
0.03/0.03
0.03/0.03
0.03/0.03
0.04/0.04
0.04/0.04
0.06/0.06
0.04/0.04
0.05/0.05
0.04/0.04
0.05/0.05
0.08/0.09
0.09/0.12
0.09/0.12
0.17/0.22
0.18/0.22
Total Heat Exchangers
Model
Total Heat
Exchangers
VOL:
PH:
HZ:
KPI-2521
KPI-5021
KPI-8021
KPI-10021
Unit Main Power
Applicable Voltage
Indoor Fan Motor
VOL
PH
HZ
Max.
Min.
PH
220/240
1
50
264
198
1
Rated Unit Power Supply Voltage (Plated)(V)
Phase ()
Frequency (Hz)
RNC:
IPT:
RNC
0.5/0.6
1.0/1.0
1.8/1.8
2.3/2.3
IPT
0.11/0.13
0.21/0.23
0.39/0.42
0.50/0.53
Running Current (A)
Input (kW)
1-72
ELECTRICAL DATA
< 60 Hz >
Indoor Unit
Model
In-the-Ceiling
Type
4-Way
Cassette Type
2-Way
Cassette Type
Wall Type
Floor Type
Floor
Concealed Type
Ceiling Type
RPI-0.8FSN2
RPI-1.0FSN2
RPI-1.5FSN2
RPI-2.0FSN2
RPI-2.5FSN2
RPI-3.0FSN2
RPI-4.0FSN2
RPI-5.0FSN2
RPI-8FSN
RPI-10FSN
RCI-1.0FSN2
RCI-1.5FSN2
RCI-2.0FSN2
RCI-2.5FSN2
RCI-3.0FSN2
RCI-4.0FSN2
RCI-5.0FSN2
RCD-1.0FSN2
RCD-1.5FSN2
RCD-2.0FSN2
RCD-2.5FSN2
RCD-3.0FSN2
RCD-4.0FSN2
RCD-5.0FSN2
RPK-1.0FSNSM2
RPK-1.5FSNSM2
RPK-2.0FSNSM2
RPK-2.5FSNSM2
RPK-3.0FSNSM2
RPK-4.0FSNSM2
RPF-1.0FSN2E
RPF-1.5FSN2E
RPFI-1.0FSN2E
RPFI-1.5FSN2E
RPC-2.0FSN2
RPC-2.5FSN2
RPC-3.0FSN2
RPC-4.0FSN2
RPC-5.0FSN2
Unit Main Power
Applicable Voltage
Indoor Fan Motor
VOL
PH
HZ
Maximum
Minimum
PH
220
1
60
242
198
1
380
3
60
418
342
3
220
1
60
242
198
1
220
1
60
242
198
1
220
1
60
242
198
1
220
1
60
242
198
1
220
1
60
242
198
1
220
1
60
242
198
1
RNC
0.6
0.6
0.8
0.8
0.8
1.2
1.5
2.3
1.9
2.3
0.2
0.2
0.2
0.3
0.4
0.7
0.8
0.2
0.4
0.4
0.5
0.6
0.7
1.2
0.2
0.3
0.3
0.3
0.3
0.5
0.2
0.2
0.2
0.2
0.4
0.7
0.7
0.9
0.9
IPT
0.12
0.12
0.16
0.16
0.16
0.26
0.32
0.49
1.14
1.41
0.03
0.03
0.04
0.06
0.07
0.13
0.16
0.05
0.08
0.08
0.11
0.13
0.14
0.24
0.03
0.03
0.03
0.04
0.04
0.06
0.04
0.05
0.04
0.05
0.09
0.15
0.15
0.20
0.20
Total Heat Exchangers
Model
Total Heat
Exchangers
VOL:
PH:
HZ:
KPI-2521
KPI-5021
KPI-8021
KPI-10021
Unit Main Power
Applicable Voltage
Indoor Fan Motor
VOL
PH
HZ
Max.
Min.
PH
220
1
60
242
198
1
Rated Unit Power Supply Voltage (Plated)(V)
Phase ()
Frequency (Hz)
RNC:
IPT:
RNC
0.6
1.2
2.1
2.8
IPT
0.13
0.26
0.46
0.60
Running Current (A)
Input (kW)
1-73
SOUND DATA
6. Sound Data
In-the-Ceiling Type
Model: RPI-0.8FSN2
Model: RPI-1.0FSN2
Power Supply: 220V, 50/60Hz
Power Supply: 220V, 50/60Hz
Measurement Point: 1.5 Meters Beneath the Unit
Measurement Point: 1.5 Meters Beneath the Unit
90
90
Noise Criteria Curve
Octave Sound Pressure Level (dB: Overall C Scale)
Octave Sound Pressure Level (dB: Overall C Scale)
Noise Criteria Curve
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
Hi
30
NC-30
Me
Lo
20
Approximate
Threshold of
Hearing for
Continuous Noise
NC-2
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
Hi
30
NC-30
Me
Lo
20 Approximate
Threshold of
Hearing for
Continuous Noise
0
NC-2
0
10
10
63
125
250
500
1000
2000
4000
63
8000
Central Frequency (Cycle per Second)
Model: RPI-1.5FSN2
125
250
500
Power Supply: 220V, 50/60Hz
Model: RPI-2.0FSN2
Measurement Point: 1.5 Meters Beneath the Unit
2000
4000
8000
Power Supply: 220V, 50/60Hz
Measurement Point: 1.5 Meters Beneath the Unit
90
90
Noise Criteria Curve
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
Hi
30
NC-30
Me
Lo
20 Approximate
Threshold of
Hearing for
Continuous Noise
Noise Criteria Curve
Octave Sound Pressure Level (dB: Overall C Scale)
Octave Sound Pressure Level (dB: Overall C Scale)
1000
Central Frequency (Cycle per Second)
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
Hi
30
NC-30
Me
Lo
20 Approximate
Threshold of
Hearing for
Continuous Noise
NC-2
0
10
NC-20
10
63
125
250
500
1000
2000
4000
Central Frequency (Cycle per Second)
8000
63
125
250
500
1000
2000
4000
8000
Central Frequency (Cycle per Second)
1-74
SOUND DATA
Model: RPI-2.5FSN2
Model: RPI-3.0FSN2
Power Supply: 220V, 50/60Hz
Measurement Point: 1.5 Meters Beneath the Unit
Power Supply: 220V, 50/60Hz
Measurement Point: 1.5 Meters Beneath the Unit
90
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
Hi
30
NC-30
Me
Lo
Noise Criteria Curve
Octave Sound Pressure Level (dB: Overall C Scale)
Octave Sound Pressure Level (dB: Overall C Scale)
Noise Criteria Curve
80
70
NC-70
60
NC-6
0
50
NC-5
0
Hi
40
Me
NC-4
0
NC-3
0
30
Lo
20
Approximate
Threshold of
Hearing for
Continuous Noise
20 Approximate
Threshold of
Hearing for
Continuous Noise
NC-2
0
10
63
125
250
500
1000
2000
4000
10
8000
63
Central Frequency (Cycle per Second)
Model: RPI-4.0FSN2
125
NC-
20
250
500
Power Supply: 220V, 50-60Hz
Model: RPI-5.0FSN2
Measurement Point: 1.5 Meters Beneath the Unit
4000
8000
Power Supply: 220V, 50/60Hz
90
Noise Criteria Curve
Octave Sound Pressure Level (dB: Overall C Scale)
Noise Criteria Curve
80
70
NC-70
60
NC-60
50
NC-50
Hi
40
Me
30
NC-40
NC-30
80
70
NC-70
60
NC-60
50
NC-50
Hi
Me
40
NC-40
30
NC-30
Lo
20
2000
Measurement Point: 1.5 Meters Beneath the Unit
90
Octave Sound Pressure Level (dB: Overall C Scale)
1000
Central Frequency (Cycle per Second)
Approximate
Threshold of
Hearing for
Continuous Noise
Lo
20
NC-2
0
Approximate
Threshold of
Hearing for
Continuous Noise
NC-2
0
10
10
63
125
250
500
1000
2000
4000
Central Frequency (Cycle per Second)
8000
63
125
250
500
1000
2000
4000
8000
Central Frequency (Cycle per Second)
1-75
SOUND DATA
Model: RPI-8FSN
Model: RPI-8FSN
Power Supply: 380V, 50/60Hz
220Pa
110Pa
90
Power Supply: 415V, 50Hz
Measurement Point: 1.5 Meter Beneath the Unit
Measurement Point: 1.5 Meter Beneath the Unit
260Pa
130Pa
90
Noise Criteria Curve
Octave Sound Pressure Level (dB: Overall C Scale)
Octave Sound Pressure Level (dB: Overall C Scale)
Noise Criteria Curve
80
70
NC-70
60
NC-6
0
50
NC-5
0
40
NC-4
0
30
NC-3
0
20
10
Approximate
Threshold of
Hearing for
Continuous Noise
63
125
NC-
20
250
500
1000
2000
4000
80
70
NC-70
60
NC-6
0
50
NC-5
0
40
NC-4
0
30
NC-3
0
20 Approximate
Threshold of
Hearing for
Continuous Noise
NC-
10
8000
63
500
Model: RPI-10FSN
Power Supply: 380V, 50/60Hz
Measurement Point: 1.5 Meter Beneath the Unit
60
NC-6
0
50
NC-5
0
40
NC-4
0
30
NC-3
0
20 Approximate
Threshold of
Hearing for
Continuous Noise
NC-
10
63
125
20
250
500
1000
2000
4000
Central Frequency (Cycle per Second)
4000
8000
260Pa
130Pa
90
Noise Criteria Curve
Octave Sound Pressure Level (dB: Overall C Scale)
Octave Sound Pressure Level (dB: Overall C Scale)
80
NC-70
2000
Power Supply: 415V, 50Hz
Noise Criteria Curve
70
1000
Measurement Point: 1.5 Meter Beneath the Unit
220Pa
110Pa
90
250
Central Frequency (Cycle per Second)
Central Frequency (Cycle per Second)
Model: RPI-10FSN
125
20
8000
80
70
NC-70
60
NC-6
0
50
NC-5
0
40
NC-4
0
30
NC-3
0
20 Approximate
Threshold of
Hearing for
Continuous Noise
NC-
10
63
125
20
250
500
1000
2000
4000
8000
Central Frequency (Cycle per Second)
NOTES:
1. The sound pressure level is based on following conditions, 1.5 Meter Beneath the Unit.
2. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in
the field.
1-76
SOUND DATA
4-Way Cassette Type
Model: RCI-1.0FSN2
Model: RCI-1.5FSN2
Power Supply: 220-240V/220V, 50/60Hz
Measurement Point: 1.5 Meters Beneath the Unit
Power Supply: 220-240V/220V, 50/60Hz
Measurement Point: 1.5 Meters Beneath the Unit
90
90
80
70
NC-70
60
NC-6
0
50
NC-5
0
NC-4
0
40
Hi
30
Me
Noise Criteria Curve
Octave Sound Pressure Level (dB: Overall C Scale)
Octave Sound Pressure Level (dB: Overall C Scale)
Noise Criteria Curve
NC-3
0
80
70
NC-70
60
NC-6
0
50
NC-5
0
NC-4
0
40
Hi
Me
NC-3
0
30
Lo
20
10
Approximate
Threshold of
Hearing for
Continuous Noise
63
125
20 Approximate
Threshold of
Hearing for
Continuous Noise
NC-
20
250
500
1000
2000
4000
10
8000
63
Central Frequency (Cycle per Second)
Model: RCI-2.0FSN2
125
NC-
20
Lo
250
500
Model: RCI-2.5FSN2
Power Supply: 220-240V/220V, 50/60Hz
Measurement Point: 1.5 Meters Beneath the Unit
90
Octave Sound Pressure Level (dB: Overall C Scale)
Octave Sound Pressure Level (dB: Overall C Scale)
80
60
NC-6
0
50
NC-5
0
NC-4
0
40
30
NC-3
0
Hi
4000
8000
Power Supply: 220-240V/220V, 50/60Hz
Noise Criteria Curve
Noise Criteria Curve
NC-70
2000
Measurement Point: 1.5 Meters Beneath the Unit
90
70
1000
Central Frequency (Cycle per Second)
80
70
NC-70
60
NC-6
0
50
NC-5
0
Hi
NC-4
0
40
Me
NC-3
0
30
Me
20 Approximate
Threshold of
Hearing for
Continuous Noise
10
63
125
NC-
Lo
250
20
20
500
1000
2000
4000
Central Frequency (Cycle per Second)
8000
10
Approximate
Threshold of
Hearing for
Continuous Noise
63
125
NC-
20
Lo
250
500
1000
2000
4000
8000
Central Frequency (Cycle per Second)
1-77
SOUND DATA
Model: RCI-3.0FSN2
Model: RCI-4.0FSN2
Power Supply: 220-240V/220V, 50/60Hz
Measurement Point: 1.5 Meters Beneath the Unit
Measurement Point: 1.5 Meters Beneath the Unit
90
90
80
70
NC-70
60
NC-6
0
50
NC-5
0
Hi
NC-4
0
40
Me
NC-3
0
30
20 Approximate
Threshold of
Hearing for
Continuous Noise
63
125
Noise Criteria Curve
Octave Sound Pressure Level (dB: Overall C Scale)
Octave Sound Pressure Level (dB: Overall C Scale)
Noise Criteria Curve
10
Power Supply: 220-240V/220V, 50/60Hz
NC-
80
70
NC-70
60
NC-6
0
Hi
40
Lo
250
500
1000
2000
4000
8000
Central Frequency (Cycle per Second)
Model: RCI-5.0FSN2
Me
10
NC-4
0
NC-3
0
30
20
20
NC-5
0
50
Approximate
Threshold of
Hearing for
Continuous Noise
63
125
NC-
20
Lo
250
500
1000
2000
4000
8000
Central Frequency (Cycle per Second)
Power Supply: 220-240V/220V, 50/60Hz
Measurement Point: 1.5 Meters Beneath the Unit
90
Octave Sound Pressure Level (dB: Overall C Scale)
Noise Criteria Curve
80
70
NC-70
60
NC-6
0
Hi
NC-5
0
50
Me
40
NC-4
30
NC-3
0
0
Lo
20 Approximate
Threshold of
Hearing for
Continuous Noise
10
63
125
NC-
20
250
500
1000
2000
4000
8000
Central Frequency (Cycle per Second)
1-78
SOUND DATA
2-Way Cassette Type
Model: RCD-1.5FSN2
Power Supply: 220V, 50/60Hz
Model: RCD-1.0FSN2
Measurement Point: 1.5 Meters Beneath the Unit
Power Supply: 220V, 50/60Hz
Measurement Point: 1.5 Meters Beneath the Unit
90
90
80
70
NC-70
60
NC-60
50
NC-50
Hi
40
NC-40
Me
30
NC-30
20 Approximate
Threshold of
Hearing for
Continuous Noise
Noise Criteria Curve
Octave Sound Pressure Level (dB: Overall C Scale)
Octave Sound Pressure Level (dB: Overall C Scale)
Noise Criteria Curve
70
NC-70
60
NC-60
50
NC-50
Hi
40
0
10
30
NC-30
NC-2
0
Lo
10
63
125
250
500
1000
2000
4000
8000
63
Central Frequency (Cycle per Second)
Model: RCD-2.0FSN2
125
250
500
1000
2000
4000
8000
Central Frequency (Cycle per Second)
Power Supply: 220V, 50/60Hz
Model: RCD-2.5FSN2, RCD-3.0FSN2
Power Supply: 220V, 50/60Hz
Measurement Point: 1.5 Meters Beneath the Unit
Measurement Point: 1.5 Meters Beneath the Unit
90
90
80
70
NC-70
60
NC-60
50
NC-50
Hi
40
NC-40
Me
30
NC-30
20 Approximate
Threshold of
Hearing for
Continuous Noise
80
70
NC-70
60
NC-60
50
NC-50
Hi
Me
40
0
NC-40
30
NC-30
20 Approximate
Threshold of
Hearing for
Continuous Noise
NC-2
Lo
Noise Criteria Curve
Octave Sound Pressure Level (dB: Overall C Scale)
Noise Criteria Curve
Octave Sound Pressure Level (dB: Overall C Scale)
NC-40
Me
20 Approximate
Threshold of
Hearing for
Continuous Noise
NC-2
Lo
80
NC-2
0
Lo
10
10
63
125
250
500
1000
2000
4000
Central Frequency (Cycle per Second)
8000
63
125
250
500
1000
2000
4000
8000
Central Frequency (Cycle per Second)
1-79
SOUND DATA
Model: RCD-4.0FSN2
Model: RCD-5.0FSN2
Power Supply: 220V, 50/60Hz
Power Supply: 220V, 50/60Hz
Measurement Point: 1.5 Meters Beneath the Unit
Measurement Point: 1.5 Meters Beneath the Unit
90
90
80
70
NC-70
60
NC-60
50
NC-50
Hi
Me
40
NC-40
30
Noise Criteria Curve
Octave Sound Pressure Level (dB: Overall C Scale)
Octave Sound Pressure Level (dB: Overall C Scale)
Noise Criteria Curve
NC-30
80
70
NC-70
60
NC-60
Hi
50
NC-50
Me
40
NC-40
30
NC-30
Lo
Lo
20 Approximate
Threshold of
Hearing for
Continuous Noise
10
63
125
20 Approximate
Threshold of
Hearing for
Continuous Noise
NC-2
0
NC-2
0
10
250
500
1000
2000
4000
Central Frequency (Cycle per Second)
8000
63
125
250
500
1000
2000
4000
8000
Central Frequency (Cycle per Second)
1-80
SOUND DATA
Wall Type
90
Model: RPK-1.0FSNSM2
Power Supply: 220V, 50/60Hz
Measurement Point: 1 Meter Beneath the Unit and
1 Meter From Discharge Grille
Model: RPK-1.5FSNSM2
Power Supply: 220V, 50/60Hz
90
Measurement Point: 1 Meter Beneath the Unit and
1 Meter From Discharge Grille
80
70
NC-70
60
NC-6
0
50
NC-5
0
40
NC-4
0
Hi
NC-3
0
30
Lo
20
10
Me
NC-
Approximate
Threshold of
Hearing for
Continuous Noise
63
125
Noise Criteria Curve
Octave Sound Pressure Level (dB: Overall C Scale)
Octave Sound Pressure Level (dB: Overall C Scale)
Noise Criteria Curve
20
250
500
1000
80
70
NC-70
60
NC-6
0
50
NC-5
0
4000
NC-3
0
Approximate
Threshold of
Hearing for
Continuous Noise
63
Central Frequency (Cycle per Second)
125
NC-
20
250
500
90
90
NC-6
0
50
NC-5
0
Hi
40
Me
NC-4
0
NC-3
0
30
Lo
20 Approximate
Threshold of
Hearing for
Continuous Noise
10
63
125
20
500
1000
2000
4000
Central Frequency (Cycle per Second)
8000
80
70
NC-70
60
NC-6
0
50
NC-5
0
Hi
NC-4
0
40
Me
30
NC-3
0
Lo
Approximate
20 Threshold of
Hearing for
Continuous Noise
NC-
250
4000
Noise Criteria Curve
Octave Sound Pressure Level (dB: Overall C Scale)
Octave Sound Pressure Level (dB: Overall C Scale)
80
60
2000
Model: RPK-2.5 FSNSM2, RPK-3.0FSNSM2
Power Supply: 220V, 50/60Hz
Measurement Point: 1 Meter Beneath the Unit and
1 Meter From Discharge Grille
Noise Criteria Curve
NC-70
1000
Central Frequency (Cycle per Second)
Model: RPK-2.0FSNSM2
Power Supply: 220V, 50/60Hz
Measurement Point: 1 Meter Beneath the Unit and
1 Meter From Discharge Grille
70
NC-4
0
Lo
10
8000
Hi
30
20
2000
Me
40
8000
10
63
125
NC-
20
250
500
1000
2000
4000
8000
Central Frequency (Cycle per Second)
1-81
SOUND DATA
90
Model: RPK-4.0FSNSM2
Power Supply: 220V, 50/60Hz
Measurement Point: 1 Meter Beneath the Unit and
1 Meter From Discharge Grille
Octave Sound Pressure Level (dB: Overall C Scale)
Noise Criteria Curve
80
70
NC-70
60
NC-6
0
Hi
50
NC-5
0
NC-4
0
40
Me
NC-3
0
30
20
10
Lo
Approximate
Threshold of
Hearing for
Continuous Noise
63
125
NC-
20
250
500
1000
2000
4000
8000
Central Frequency (Cycle per Second)
1-82
SOUND DATA
Floor Type
Model: RPF-1.0FSN2E
Power Supply: 220V, 50/60Hz
Model: RPF-1.5FSN2E
Measurement Point: 1.5 Meter from the Unit
1.5 Meter from Floor Level
Noise Criteria Curve
Noise Criteria Curve
Hi/Me/Lo: 35/32/29 dBA
Hi/Me/Lo: 38/35/31 dBA
80
Octave Sound Pressure Level (dB: Overall C Scale)
80
Octave Sound Pressure Level (dB: Overall C Scale)
Power Supply: 220V, 50/60Hz
Measurement Point: 1.5 Meter from the Unit
1.5 Meter from Floor Level
70
60
50
40
30
70
60
50
40
30
20
20
Approximate
Threshold of
Hearing for
Continuous Noise
10
63
125
250
Approximate
Threshold of
Hearing for
Continuous Noise
10
500
1000
2000
4000
63
8000
Central Frequency (Cycle per Second)
125
250
500
1000
2000
4000
8000
Central Frequency (Cycle per Second)
Floor Concealed Type
Model: RPFI-1.0FSN2E
Power Supply: 220V, 50/60Hz
Model: RPFI-1.5FSN2E
Power Supply: 220V, 50/60Hz
Measurement Point: 1.5 Meter from the Unit
1.5 Meter from Floor Level
Noise Criteria Curve
Noise Criteria Curve
Hi/Me/Lo: 35/32/29 dBA
Hi/Me/Lo: 38/35/31 dBA
80
80
Octave Sound Pressure Level (dB: Overall C Scale)
Octave Sound Pressure Level (dB: Overall C Scale)
Measurement Point: 1.5 Meter from the Unit
1.5 Meter from Floor Level
70
60
50
40
30
20
70
60
50
40
30
20
Approximate
Threshold of
Hearing for
Continuous Noise
10
63
125
250
Approximate
Threshold of
Hearing for
Continuous Noise
10
500
1000
2000
4000
Central Frequency (Cycle per Second)
8000
63
125
250
500
1000
2000
4000
8000
Central Frequency (Cycle per Second)
1-83
SOUND DATA
Ceiling Type
90
Power Supply: 220V, 50/60Hz
Model: RPC-2.0FSN2
Measurement Point: 1 Meter Beneath the Unit and
1 Meter From Discharge Grille
Model: RPC-2.5FSN2, RPC-3.0FSN2
90
70
NC-70
60
NC-60
50
NC-50
40
NC-40
Hi
30
Noise Criteria Curve
Octave Sound Pressure Level (dB: Overall C Scale)
Octave Sound Pressure Level (dB: Overall C Scale)
Noise Criteria Curve
80
NC-30
Me
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
Hi
30
NC-30
Me
Lo
Lo
20 Approximate
Threshold of
Hearing for
Continuous Noise
20 Approximate
Threshold of
Hearing for
Continuous Noise
NC-2
0
NC-2
0
10
10
63
125
250
500
1000
2000
4000
63
8000
Central Frequency (Cycle per Second)
90
125
250
500
Power Supply: 220V, 50/60Hz
Model: RPC-4.0FSN2
Measurement Point: 1 Meter Beneath the Unit and
1 Meter From Discharge Grille
90
NC-70
60
NC-60
50
NC-50
Hi
40
NC-40
30
2000
4000
8000
Power Supply: 220V, 50/60Hz
Model: RPC-5.0FSN2
Measurement Point: 1 Meter Beneath the Unit and
1 Meter From Discharge Grille
Noise Criteria Curve
Octave Sound Pressure Level (dB: Overall C Scale)
80
70
1000
Central Frequency (Cycle per Second)
Noise Criteria Curve
Octave Sound Pressure Level (dB: Overall C Scale)
Power Supply: 220V, 50/60Hz
Measurement Point: 1 Meter Beneath the Unit and
1 Meter From Discharge Grille
NC-30
Me
80
NC-70
70
60
NC-60
50
NC-50
Hi
40
NC-40
30
NC-30
Me
Lo
Lo
20 Approximate
Threshold of
Hearing for
Continuous Noise
20 Approximate
Threshold of
Hearing for
Continuous Noise
NC-2
0
10
NC-2
0
10
63
125
250
500
1000
2000
4000
Central Frequency (Cycle per Second)
8000
63
125
250
500
1000
2000
4000
8000
Central Frequency (Cycle per Second)
1-84
SOUND DATA
Total Heat Exchangers
Model: KPI-2521
Power Supply: 220-240V/50Hz
Model: KPI-5021
Measurement Point: 1.5 Meter Beneath the Unit
and with a Sound-Proof Duct
Power Supply: 220-240V/50Hz
Measurement Point: 1.5 Meter Beneath the Unit
and with a Sound-Proof Duct
90
90
Noise Criteria Curve
Noise Criteria Curve
80
NC-70
70
60
NC-6
50
NC-5
40
NC-4
30
NC-3
0
0
0
0
Me
Lo
Hi
NC-
20
10
Octave Sound Pressure Level (dB: Overall C Scale)
Octave Sound Pressure Level (dB: Overall C Scale)
80
125
250
500
1000
2000
NC-70
60
NC-6
50
NC-5
40
NC-4
0
0
0
30
NC-3
4000
Me
10
8000
Lo
63
Central Frequency (Cycle per Second)
Model: KPI-8021
125
250
500
NC-20
1000
2000
4000
8000
Central Frequency (Cycle per Second)
Power Supply: 220-240V/50Hz
Model: KPI-10021
Measurement Point: 1.5 Meter Beneath the Unit
and with a Sound-Proof Duct
Power Supply: 220-240V/50Hz
Measurement Point: 1.5 Meter Beneath the Unit
and with a Sound-Proof Duct
90
90
Noise Criteria Curve
Noise Criteria Curve
80
80
70
NC-70
60
NC-6
50
NC-5
40
NC-4
Octave Sound Pressure Level (dB: Overall C Scale)
Octave Sound Pressure Level (dB: Overall C Scale)
0
Hi
20
20
63
70
0
0
0
30
NC-3
0
Lo
Hi
Me
20
70
NC-70
60
NC-6
50
NC-5
40
NC-4
0
0
0
Hi
Lo
30
NC-3
0
Me
NC-
20
20
NC-20
10
63
125
250
500
1000
2000
4000
Central Frequency (Cycle per Second)
8000
10
63
125
250
500
1000
2000
4000
8000
Central Frequency (Cycle per Second)
NOTES:
1. The sound pressure level is based on following conditions, 1.5 Meter Beneath the Unit. (Total heat exchange mode)
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in
the field.
2. The sound pressure level emitted from the air outlet to the duct is higher than the values indicated in the GENERAL
DATA table by 5 to 6 dB(A) approximately. It is recommended that a sound-proof duct.
1-85
SOUND DATA
Power Supply: 220V/60Hz
Model: KPI-2521
90
Power Supply: 220V/60Hz
Model: KPI-5021
Measurement Point: 1.5 Meter Beneath the Unit
and with a Sound-Proof Duct
90
Measurement Point: 1.5 Meter Beneath the Unit
and with a Sound-Proof Duct
Noise Criteria Curve
Octave Sound Pressure Level (dB: Overall C Scale)
Noise Criteria Curve
Octave Sound Pressure Level (dB: Overall C Scale)
80
70
NC-70
60
NC-6
50
NC-5
0
0
40
NC-4
Hi
0
Me
30
NC-30
Lo
80
70
NC-70
60
NC-6
50
NC-5
0
40
NC-2
0
Me
30
NC-30
10
125
250
500
1000
2000
4000
NC-2
20
0
10
8000
0
63
Power Supply: 220V/60Hz
Model: KPI-8021
125
250
500
90
NC-6
50
NC-5
40
NC-4
0
0
0
Hi
30
NC-30
Me
8000
Noise Criteria Curve
Octave Sound Pressure Level (dB: Overall C Scale)
Octave Sound Pressure Level (dB: Overall C Scale)
80
60
4000
Measurement Point: 1.5 Meter Beneath the Unit
and with a Sound-Proof Duct
Noise Criteria Curve
NC-70
2000
Power Supply: 220V/60Hz
Model: KPI-10021
Measurement Point: 1.5 Meter Beneath the Unit
and with a Sound-Proof Duct
70
1000
Central Frequency (Cycle per Second)
Central Frequency (Cycle per Second)
90
NC-4
Hi
Lo
20
63
0
80
70
NC-70
60
NC-6
50
NC-5
0
0
NC-4
0
40
Hi
30
NC-30
Lo
Lo
Me
20
NC-2
0
20
NC-20
10
10
63
125
250
500
1000
2000
4000
Central Frequency (Cycle per Second)
8000
63
125
250
500
1000
2000
4000
8000
Central Frequency (Cycle per Second)
NOTES:
1. The sound pressure level is based on following conditions, 1.5 Meter Beneath the Unit. (Total heat exchange mode)
The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in
the field.
2. The sound pressure level emitted from the air outlet to the duct is higher than the values indicated in the GENERAL
DATA table by 5 to 6 dB(A) approximately. It is recommended that a sound-proof duct.
1-86
ELECTRICAL WIRING DIAGRAM (FOR MODELS: RPI-0.8FSN2, RPI-1.0FSN2, RPI-1.5FSN2, RPI-2.0FSN2, RPI-2.5FSN2, RPI-3.0FSN2, RPI-4.0FSN2 AND RPI-5.0FSN2)
ctrical Wiring Diagram
CONTROL SYSTEM
1-139
ELECTRICAL WIRING DIAGRAM (FOR MODELS: RPI-8FSN AND RPI-10FSN)
CONTROL SYSTEM
1-140
ELECTRICAL WIRING DIAGRAM (FOR MODELS: RCI-1.0FSN2, RCI-1.5FSN2, RCI-2.0FSN2, RCI-2.5FSN2, RCI-3.0FSN2, RCI-4.0FSN2 AND RCI-5.0FSN2)
CONTROL SYSTEM
1-141
ELECTRICAL WIRING DIAGRAM (FOR MODELS: RCD-1.0FSN2, RCD-1.5FSN2, RCD-2.0FSN2, RCD-2.5FSN2, RCD-3.0FSN2, RCD-4.0FSN2 AND RCD-5.0FSN2)
CONTROL SYSTEM
1-142
ELECTRICAL WIRING DIAGRAM (FOR MODELS: RPK-1.0FSNSN2 AND RPK-1.5FSNSM2)
CONTROL SYSTEM
1-143
ELECTRICAL WIRING DIAGRAM (FOR MODELS: RPK-2.0FSNSM2)
CONTROL SYSTEM
1-144
ELECTRICAL WIRING DIAGRAM (FOR MODELS: RPK-2.5FSNSM2, RPK-3.0FSNSM2 AND RPK-4.0FSNSM2)
CONTROL SYSTEM
1-145
CN2
CN17
C55
DM1
C16
EF2
DSW7
L1
C2
CN1
CN14
CN19
CN7
PCB Sockets location
Main Switch
Main Switch
CN5
CN8
CN10
IC1
EF3
PCN5
CN11
PCN1
1~
220V/60Hz
(3~)
1N~
220V/60Hz
(3N~)
1N~
220/240V
50Hz (3N~)
CN3
DSW3
DSW4
YH2
PCN6
SK1
YLO
P
(17G )
THM5 THM3 THM1
RSW1
THM4 THM2
RSW2
TP
YME
PCN11
DSW6
DSW5
Y52H
PCN3
EFS1
EFR1
YSLO
PCN10
YH1
CAUTION HIGH VOLTAGE
PCN8
PCN7
for Communication
2 wire RCS (PC-AR)
PCN2
OUTPUT1
Electrical Control Box of Indoor Unit
INPUT
Inlet
OUTPUT2
Outlet
Liquid
·X·
– ·· – ·· –
- –- –- –
––––––
Mark
CA
CN
DSW3
DSW5
DSW6
DSW7
RSW
EFR1,EFS1,EF1
ITI
LD1~3
MIF
MV
PCB
RCS
RSW1, RSW2
SSW
TB
THM1
THM2
THM3
THM5
TF
YME
YLO
YSLO
YH1
Gas
for RCS
Name
Capacitor for Indoor Fan
Connector
Unit Capacity Code
Refrigerant Cycle No.
Unit Models Code
Fuse Recover/Remote Controller Selector
Indoor Unit No. Setting
Fuse
Internal Thermostat for Indoor Fan Motor
Alarm Code
Motor for Indoor Fan
Expansion Valve
Printed Circuit Board
Remote Control Switch
Indoor Unit No. Settings
Slide Switch
Terminal Board
Inlet Air Thermistor
Outlet Air Thermistor
Liquid Pipe Thermistor
Gas Pipe Thermistor
Transformer
Relay for ME Fan Motor Tap
Relay for LO Fan Motor Tap
Relay for SLO Fan Motor Tap
Relay for Hi Fan Motor Tap
Terminals
Field Connection
Field Wiring
Earth Wiring
Factory Wiring
ELECTRICAL WIRING DIAGRAM (FOR MODELS: RPF-1.0FSN2E, RPF-1.5FSN2E, RPFI-1.0FSN2E AND RPFI-1.5FSN2E)
DC Coil
DC Coil
DC Coil
DC Coil
On PCB
On PCB
On PCB
On PCB
Optional Part
On PCB
On PCB
On PCB
On PCB
On PCB
On PCB
On PCB
On PCB
On PCB
Remarks
CONTROL SYSTEM
1-146
ELECTRICAL WIRING DIAGRAM (FOR MODELS: RPC-2.0FSN2, RPC-2.5FSN2, RPC-3.0FSN2, RPC-4.0FSN2 AND RPC-5.0FSN2)
CONTROL SYSTEM
1-147
MISCELLANEOUS NOTES
11. Miscellaneous Notes
Special Notes
1. Provide a service access door near the unit
piping connection part on the false ceiling for the
cassette type units.
2. Consider the air distribution from the unit to the
space of the room, and select a suitable location
so that uniform air temperature in the room can
be obtained.
Cassette and Ceiling Types - Avoid unit
installation in a room where the ceiling height
(distance between the floor to the false ceiling)
exceeds three meters. If the indoor unit is
installed in a room with a ceiling of higher than 3
meters, it is recommended that an air circulation
fan be installed separately to obtain uniform air
temperature in the room, especially during the
heating operation.
3. Check to ensure that the ceiling slab is strong
enough and that the false ceiling is flat and level.
4. Avoid obstacles which may restrict the air intake
or the discharge flow.
5. Do not install the unit in a machinery shop or
kitchen where vapor from oil or its mist can enter
to the unit.
The oil will deposit on the heat exchanger,
thereby reducing the unit performance, and may
deform, in the worst case, break the plastic parts
of the unit.
6. Pay attention to the following points when the
unit is installed in a hospital or other facilities
where electromagnetic wave is radiated from
medical equipment.
(A) Do not install the unit where the
electromagnetic wave is directly radiated to
the electrical box, remote control cable or
remote control switch.
(B) Install the unit and component as far as
practical (at least three meters) from the
electromagnetic wave radiator.
(C) Prepare a steel box and install the remote
control switch in it. Prepare a steel conduit
pipe and wire the remote control cable in it.
And then, connect earth wire with the box
and the pipe.
(D) Install a noise filter when the power supply
emits harmful noise.
7. Do not install the units in an acid or alkaline
environment due to the corrosive action on the
heat exchanger. In the case that outdoor units
are installed near the sea, it is recommended
that optional corrosion-resistant type outdoor
unit be used.
8. Do not install the units in a flammable
environment due to the danger of an explosion.
9. Regarding cassette type indoor units, consider
the direct and reflected sound level, when
selecting the unit for spaces where extremely
low sound is required.
10. During heating operation, the outdoor heat
exchanger produces condensate dew or
melting water from frost.
Install the outdoor unit where drainage of
such water is convenient, or provide a drain
passage.
11. Heating Performance: The heating capacity
normally decreases when outdoor temperatures
decrease. Therefore, provide an auxiliary
heating unit if outdoor temperatures are very
low.
12. In the case that an outdoor temperature is
low and humidity is high, the outdoor heat
exchanger will covered with frost, resulting in
lower heating capacity. In order to remove
the frost, the unit is automatically changed to
the defrosting mode. During this defrosting
operation, the unit is stopped for approximately
3 to 10 minutes.
13. As this unit is of heat pump type by circulating
hot air in the whole room space, it takes time to
heat up the room temperature.
14. The operating sound data is based on an
anechoic chamber. Therefore, the actual
operating sound will be higher due to reflected
sound from the floor and wall.
15. In the case that the unit is operated for a long
time higher than the indoor temperature of
27oCDB or the humidity of 80%, dewing may
occur on the cabinets resulting in dew drops. If
dewing, it is required to add thermal insulator
on the cabinets.
16. Provide snow-protection hoods to prevent the
outdoor heat exchanger from snow clogging.
If the unit is operated in an are where it snows
heavily, provide a base under the outdoor
unit which should be 50cm higher than the
presumable maximum snow height.
17. It is recommended that periodical service and
maintenance be performed by authorized
service engineers before air conditioning
seasons, in order to avoid performance
decrease due to dust or dirt.
18. This heat pump air conditioner has been
designed for normal air conditioning for men.
Do not apply to other purposes such as for
food, animals, plants, high precision machines
or work of art. Also do not apply to vehicles
or vessels. It will results in water leakage or
electrical leakage.
19. It is recommended that the system be installed
by authorized engineers. If not, it may cause
water leakage, electric shock or fire.
20. In a place where fibers or dusts are floating, the
air filter or heat exchangers or the drain pipe
may be clogged, resulting in water leakage
from the drain pan.
1-149
MISCELLANEOUS NOTES
Special Notes on Refrigerant, R410A
Use tools and measuring instruments only for the new refrigerant which is directly touch to refrigerant.
: Interchangeability is available with current R22
: Prohibited
Measuring Instrument and Tool
Pipe Cutter
Chamfering Reamer
Flaring Tool
Interchangeability
with R22
R410A
R407C
-
Extrusion
Adjustment Gauge
-
Pipe Bender
Brazing Tool
Nitrogen Gas
* The flaring tools for R407C are applicable to R22.
* If using flaring tube, make dimension of tube larger
for R410A.
* In case of material 1/2H, flaring is not available.
* In case of material 1/2H, bending is not available.
Use elbow for bend and braze.
* In case of material 1/2H, expanding of tube is not
available. Use socket for connecting tube.
* For 12.7, 15.88, spanner size is up 2mm.
* For 6.35, 9.53, 19.05, spanner size is the same.
* Perform correct brazing work.
* Strict Control against Contamin
(Blow nitrogen during brazing.)
Lubrication Oil
(for Flare Surface)
Refrigerant
Cylinder
Vacuum Pump
Adapter for
Vacuum Pump
Manifold Valve
Charging Hose
Charging Cylinder
Weight Scale
Refrigerant
Charge
Reason of Non-Interchangeability and Attention
(: Strictly Required)
Refrigerant Expanding Tool
Pipe
Torque Wrench
Vacuum
Drying
: only for Refrigerant R410A (No Interchangeability with R22)
: only for Refrigerant R407C (No Interchangeability with R22)
Refrigerant Gas
Leakage Detector
Use
Cutting Pipe
Removing Burrs
Flaring for Tubes
Dimensional Control
for Extruded Portion
of Tube after Flaring
Bending
Expanding Tubes
Connection of
Flare Nut
Brazing for Tubes
Prevention from
Oxidation during
Brazing
* Use a synthetic oil which is equivalent to the oil used Applying Oil to
in the refrigeration cycle.
the Flared Surface
* Synthetic oil absorbs moisture quickly.
* Check refrigerant cylinder color.
Refrigerant Charging
Liquid refrigerant charging is required regarding
zeotoropic refrigerant.
Vacuum Pumping
The current ones are applicable. However, it is
required to mount a vacuum pump adapter which
can prevent from reverse flow when a vacuum pump
stops, resulting in no reverse oil flow.
* No interchangeability is available due to higher
pressures when compared with R22.
Do not use current ones to the different refrigerant.
If used, mineral oil will flow into the cycle and cause
sludges, resulting in clogging or compressor failure.
Connection diameter is different; R410A: UNF1/2,
R407C: UNF7/16.
Vacuum Pumping,
Vacuum Holding,
Refrigerant Charging
and Check of
Pressures
* Use the weight scale.
Measuring
Instrument for
Refrigerant Charging
Gas Leakage Check
* The current gas leakage detector (R22) is not
applicable due to different detecting method.
: Interchangeability with R407C.
1-150
STANDARD SPECIFICATIONS
Standard Specification for the
Hitachi Premium Range of Air Cooled Modular Set Free VRF Systems
Preamble
Air cooled Condenser FSXN SERIES
The units shall be manufactured by Hitachi, and shall
meet or exceed the requirements of this specification.
Units shall be designed in accordance with the relevant
standards, and tested to JIS Standard JIS B8616
packaged air conditioner and shall be compliant
with AS/NZS1677 refrigerating system. Units shall
be suitable for providing continuous operation in
ambient conditions between -20˚C and 43˚C without
excessive head pressure, unstable operation or icing.
Refrigerant shall be R410A.Acoustic performance
is to be fully documented within the manufacturers
standard technical literature, and is to be measured
in accordance with JIS 8616. Noise spectrum results
commencing at the 63Hz band and finishing at the 8K
Hz band are to be provided, along with an overall noise
level Noise data is to be provided for the following:
Indoor unit
• Sound Pressure Level
• Outdoor Unit
Sound Pressure Level
• Sound Power Level
Cabinet - The cabinet shall be constructed from
galvanized sheet complete with a baked polyester
powder coat finish. All fasteners exposed to the
weather shall be galvanized steel. The condenser
cabinet shall be rated to IP 45, fully weatherproofed
and suitable for outdoor operation, housing
compressor, outdoor coil, condenser fan, motor
and main electric controls interfacing Hitachi H-Link
network. Access panel shall be provided for routine
inspection and maintenance.
Compressor - Shall control inverter scroll
compressor speed from 20HZ to 100HZ with 80
steps, quickly reach the set point then maintain in
a stable energy saving operation. FSXN8/10/12
shall be fit with one inverter driven scroll compressor
and FSXN14/16/18 shall be fit with one inverter
driven scroll compressor and one constant scroll
compressor. Compressor shall be protected by a
quick response over current relay, a high pressure
switch, a wrap around type oil heater and a discharge
gas thermistor. Crankcase heater shall be factory
supplied and mounted.
Condenser Fan - Shall be plastic propeller type
fan direct driven by variable speed motor with
permanently lubricated bearings for vertical flow
air discharge. Propeller fan shall be statically and
dynamically self balanced. Fan shall be provided with
guard to prevent from contact with moving parts.
Refrigeration Circuit - Shall include, but not be
limited to the following:
System description
The variable capacity heat pump as well as heat
recovery air conditioning system shall be Hitachi
inverter driven Modular FSXN series that use universal
condensing units with R410A refrigerant. The FSXN
Series shall be either 3 pipe heat recovery multi
split inverter system or 2 pipe heat pump multi split
system. The base module shall be FSXN8/10/12 and
FSXN14/16/18 and shall be capable to form up to
54HP with 3 standard modules.
The 3 pipe heat recovery system shall consist
of Hitachi Modular FSXN outdoor unit/s, CH
(changeover) Boxes, multiple indoor units and
associated local and central controls. Each indoor
unit or group/zone shall be capable of operating
independently and system shall be capable of
operating in either cooling, heating or simultaneous
cooling and heating mode. Each indoor unit or
group/zone shall be able to change mode with no
interruption to whole system operation.
The 2 pipe heat pump system shall consist of Hitachi
FSXN outdoor unit/s, multiple indoor units and
associated local and central controls. Each refrigerant
group shall be capable of operating independently and
system shall be capable of operating in either cooling
or heating mode.
The single VRF system shall be capable of handling
range from 50%-130% connected indoor capacity
and up to 64 indoor units without unstable operation.
The total refrigerant piping length shall be able to run
up to 1000 m max and Max single piping length shall
be able to run up to 165 m. The lift between outdoor
and indoor units shall be within 50m.
• DC inverter scroll Compressor/s
• Electronic Expansion Valve
• Head Pressure Control
• Common fault indication
• Anti short cycle timer
• Frost protection
• Liquid & Suction service valves
• Di – Ice control based on time/temperature initiation
- Hot gas by – pass defrost type control
shall not be used
• DC inverter Compressor – scroll compressor
- Crank case heater fitted to the compressor
- The compressor is to be located within an
isolated compressor compartment
• Compressor minimum run time
Condenser Coil - Shall be multi pass, cross finned
tube type manufactured by Hitachi, and will comprise
copper tube, complete with anti corrosion aluminium
fin stock mechanically bonded to the copper tubes.
Frames shall be aluminium, suitable for outdoor use.
The coil shall be designed to allow for the full coil
1-151 A
STANDARD SPECIFICATIONS
to be de-frosted where necessary. Coil shall be
cleaned, dehydrated and pressure tested at factory
and shall be charged with correct refrigerant charge
before shipment.
Clearance shall be provided around units for condenser
air flow and maintenance access. Hot discharge air
shall not be short-circuited to condenser intake.
CH Change Over Box
Cabinet - The cabinet shall be compact, light
weight, constructed from galvanized sheet complete
with high density foam insulation suitable for indoor
installation. All fasteners exposed to the weather shall
be galvanized steel. The sheet metal cabinet shall be
housing expansion valves, refrigeration control solenoid
valves, control circuit board and other electric controls
interfacing Hitachi H-Link network. Access panel shall
be provided for routine inspection and maintenance.
Changeover box shall be capable of control refrigerant
flow for either one unit or a group of up to 8 units.
It shall have 2 incoming gas pipes (low pressure and
high pressure) and 1 outgoing gas pipe. Liquid pipe
shall not be run through changeover box to save
on pipe joints.
Ducted Indoor Unit RPI SERIES
Cabinet - Shall be fabricated using galvanized steel
with high density foam insulation. The cabinet shall
include indoor coils, piping, supply air fan, motor,
electronic expansion valve, control circuit board,
accessories and electrical connections mounted
within an insulated enclosure with four brackets to
accommodate suspension. Access panels shall be
easily removed and sized to provide adequate access
to interior for routine inspection and maintenance,
and shall be air tight. The cabinet is to be insulated
for thermal & acoustic performance, using
polyethylene insulation.
Evaporator Coil - Shall be manufactured by Hitachi,
and shall be direct expansion type manufactured from
inner grooved copper tubes expanded into aluminum
fins to form a mechanical bond. Coil shall be pressure
tested at factory and shall be charged with dry air or
dry nitrogen before shipment.
Condensate Drain Pan - Shall be sized and
sloped to catch all condensate, and to allow it to
drain away freely, and shall be constructed to be
corrosion resistant.
Evaporator Fan - Shall be direct drive centrifugal
fan, minimum 3 speeds. Indoor centrifugal fan shall be
statically and dynamically self balanced and shall be
driven by high efficient DC fan motor with permanently
lubricated bearings. Fan curves showing the airflow
limits, available external static, and input power for
each fan speed are to be documented within the
manufacturer’s standard literature.
Cassette Indoor Unit RCI/RCD SERIES
Cabinet - Shall be fabricated using galvanized steel
coated with high density foam insulation with unit height
within 300mm. The cabinet shall include indoor
coils, piping, supply air fan, drain pump, electronic
expansion valve, control circuit board, accessories
and electrical connections mounted within an
insulated enclosure. Facial Panel shall be either a
four-way or a two-way air distribution type, impact
resistant, stain resistant and washable decoration
panel. The supply air is distributed via motorized
louvers which can be horizontally and vertically
adjusted from 0° to 90°. Access panels shall be
easily removed and sized to provide adequate
access to interior for routine inspection and
maintenance, and shall be air tight. The cabinet is
to be insulated for thermal & acoustic performance,
using polyethylene insulation.
Evaporator Coil - Shall be manufactured
by Hitachi, and shall be direct expansion type
manufactured from inner grooved copper tubes
expanded into aluminum fins to form a mechanical
bond. Coil shall be pressure tested at factory
and shall be charged with dry air or dry nitrogen
before shipment.
Condensate Drain Pan - Shall be sized and
sloped to catch all condensate, and to allow it to
drain away freely, and shall be constructed to be
corrosion resistant. A condensate pan with drain
connections shall be provided under the coil.
The unit shall also include a built-in, automatic
condensate lift mechanism that will be able to
raise drain water 850mm above the condensate
pan. The lift mechanism shall be equipped with
a positive acting liquid level sensor to shut down
the indoor unit if liquid level in the drain pan
reaches maximum level.
Evaporator Fan - Shall be direct drive turbo
fan, minimum 3 speeds. Indoor turbo fan shall
be statically and dynamically self balanced and
shall be driven by high efficient DC fan motor with
permanently lubricated bearings.
The four-way indoor unit shall have an adjustable
air outlet system offering 4-way airflow, 3-way
airflow, or 2-way airflow with switches that can be
set to provide optimum airflow based on ceiling
height and number of outlets used.
Wall Mounted Indoor Unit RPK SERIES
Cabinet - Shall be fabricated with high strength
moulded plastic and sufficient insulation and shall
be suitable to be mounted firmly on the factory
supplied mounting template. It Shall include indoor
coils, piping, supply air fan, motor, electronic
expansion valve, control circuit board, accessories
and electrical connections within an insulated
enclosure. Front panel shall be easily removed
to provide access to interior of unit for routine
inspection and maintenance.
Evaporator Coil - Shall be manufactured
by Hitachi, and shall be direct expansion type
manufactured from inner grooved copper tubes
1-151 B
STANDARD SPECIFICATIONS
expanded into aluminum fins to form a mechanical
bond. Coil shall be pressure tested at factory and
shall be charged with dry air or dry nitrogen
before shipment.
Condensate Drain Pan - Shall be sized and
sloped to catch all condensate, and to allow it to
drain away freely, and shall be constructed to be
corrosion resistant.
Evaporator Fan - Shall be tangential type fan
direct driven by single phase motor with permanently
lubricated bearings, minimum 3 speeds. Indoor
tangential fan shall be statically and dynamically
balanced.
Under ceiling Mounted Indoor Unit RPC SERIES
Cabinet - Shall be fabricated with galvanised steel
with white power coating and sufficient insulation and
shall be suitable to be mounted firmly under ceiling.
It Shall include indoor coils, piping, supply air fan,
motor, electronic expansion valve, control circuit
board, accessories and electrical connections within
an insulated enclosure. Front panel shall be easily
removed to provide access to interior of unit
for routine inspection and maintenance.
Evaporator Coil - Shall be manufactured by Hitachi,
and shall be direct expansion type manufactured from
inner grooved copper tubes expanded into aluminum
fins to form a mechanical bond. Coil shall be pressure
tested at factory and shall be charged with dry air or
dry nitrogen before shipment.
Condensate Drain Pan - Shall be sized and
sloped to catch all condensate, and to allow it to
drain away freely, and shall be constructed to be
corrosion resistant.
Evaporator Fan - Shall be sirocco type fan
direct driven by single phase motor with permanently
lubricated bearings, minimum 3 speeds. Indoor
sirocco fan shall be statically and dynamically
balanced.
Floor Mounted Indoor Unit RPF/RPFI SERIES
Cabinet - Shall be fabricated with galvanised
steel for floor concealed type and galvanised steel
with white power coating for floor exposed type
and sufficient insulation and shall be suitable to
be mounted firmly on the floor. It Shall include
indoor coils, piping, supply air fan, motor, electronic
expansion valve, control circuit board, accessories
and electrical connections within an insulated
enclosure. Front panel shall be easily removed
to provide access to interior of unit for routine
inspection and maintenance.
Evaporator Coil - Shall be manufactured by Hitachi,
and shall be direct expansion type manufactured from
inner grooved copper tubes expanded into aluminum
fins to form a mechanical bond. Coil shall be pressure
tested at factory and shall be charged with dry air or
dry nitrogen before shipment.
Condensate Drain Pan - Shall be sized and
sloped to catch all condensate, and to allow it to
drain away freely, and shall be constructed to be
corrosion resistant.
Evaporator Fan - Shall be sirocco type fan direct
driven by single phase motor with permanently
lubricated bearings, minimum 3 speeds. Indoor sirocco
fan shall be statically and dynamically balanced.
Control
General - shall consist of Hitachi local control,
central control, central on/off control, schedule timer,
web based CS Net and Open interface including
Bacnet and Lonworks gateway.
Wiring - Shall be no-polar 2 conductor, twisted
shielded pair and shall be wired in daisy chain
configuration from outdoor units to changeover boxes
and from changeover box to indoor units. Control
wiring for central control, schedule timer, CS net
shall be installed in daisy chain from outdoor units to
outdoor units and to these controls.
Local Remote Control - shall be LCD wired remote
control PC-AR OR PC-ART with weekly timer function.
General: Provide microprocessor controller with the
following functions:
- Power ON/OFF switch.
- Mode selector switch:
DEHUMIDIFY - COOL - HEAT - AUTO
- Temperature settings
- Evaporator fan speed selector
- Indicating lamps, LEDs or LCD display for unit
operating or fault
- Self diagnosis functions
- Group control up to 16 units by one single control
Central Control - shall be LCD wired control or web
based as listed,
- Schedule timer: PSC-A1T (weekly timer with
3 programs/day, winter and summer schedule)
- Central on/off control: PSC-A16RS (up to 16 groups
or 160 units collectively on/off control)
- Central station control: PSC-A64S OR PSC-5S
(up to 64 groups or 160 units collectively control)
- Web based control: PSC-6WTX (up to 64 groups or
1024 units collectively control over net)
Quality assurance
The complete VRF system shall be designed
within the guarantee working range published in the
technical literature and installed within guide line of
manufacturer published technical literature and shall
be commissioned and certified by factory trained
technicians or factory trained agents.
The complete system shall be complete assembled
and tested in ISO9001 and ISO14001 certified
manufacturing facilities and shall be tested to comply
with current Australian safety and EMC standards.
1-151 C
IMPORTANT NOTICE
• Upon receiving this product, inspect it for any shipping damage.
Claims for damage, either apparent or concealed, should be filed immediately with the shipping company.
• Check the model number, electrical characteristics (power supply, voltage and frequency) and accessories
to determine if they are correct.
The standard utilization of the unit shall be explained in these instructions.
Therefore, the utilization of the unit other than those indicated in these instructions is not recommended.
Please contact your local agent, as the occasion arises.
HITACHI’s liability shall not cover defects arising from the alteration performed by a customer without
HITACHI’s consent in a written form.
CAUTION
• Use shielded wires of operation line between the indoor unit and the outdoor unit.
And connect the shielded part to the earth screw in the electrical box of the indoor unit as shown in the Fig. 1.
(Example: RPI-8FSN)
Protect the earth wire not to contact
with the live part.
Earth Terminal
TB1
*Earth the tip of shield wires
as shown.
TB2
A B 1 2
DO NOT connect the wiring
to these terminals. (TB1-1,2)
Power Source Cable
Remote Control
Switch Cable
Shielded
Part
Transmission Cable
*In case of Australia, ensure to
earth shield wire tip of both ends.
*ELB
*ELB: Earth Leakage Breaker
Power
Source
Fig. 1 Earth Wiring

Similar documents

Technical Catalogue

Technical Catalogue 7.2.1. RCI-(1.0-6.0)FSN3 - 4-way cassette........................................................................................................ 193 7.2.2. RCI-(1.0-6.0)FSN3Ei - 4-way cassette.....

More information

Vent-Axia_Brochure

Vent-Axia_Brochure previous regulations, in line with the Code for Sustainable

More information

Two-way cassette RCD

Two-way cassette RCD Nominal Heating Capacity(2) UK Cooling Capacity (sensible)(3) Noise Level (sound pressure) (L / M / H)(4) Noise level (sound power)(5) Air flow cooling mode (L / M / H) Dimensions (H x W x D) Weigh...

More information