View - Temperzone
Transcription
View - Temperzone
VRF Multi-split Air Conditioning System SET-FREE FSN2 Indoor Units INVERTER-DRIVEN MULTI-SPLIT SYSTEM Heat Pump Air Conditioners INVERTER-DRIVEN MULTI-SPLIT SYSTEM Heat Pump Air Conditioners Models Indoor Units Technical Catalogue for Indoor Unit In-the-Ceiling Type RPI-0.8FSN2 RPI-1.0FSN2 RPI-2.0FSN2 RPI-2.5FSN2 RPI-4.0FSN2 RPI-5.0FSN2 RPI-8FSN RPI-10FSN RPI-1.5FSN2 RPI-3.0FSN2 4-Way Cassette Type RCI-1.0FSN2 RCI-1.5FSN2 RCI-2.5FSN2 RCI-3.0FSN2 RCI-5.0FSN2 RCI-2.0FSN2 RCI-4.0FSN2 2-Way Cassette Type RCD-1.0FSN2 RCD-1.5FSN2 RCD-2.5FSN2 RCD-3.0FSN2 RCD-5.0FSN2 RCD-2.0FSN2 RCD-4.0FSN2 Wall Type RPK-1.0FSNSM2 RPK-1.5FSNSM2 RPK-2.5FSNSM2 RPK-3.0FSNSM2 Floor Type RPF-1.0FSN2E RPK-2.0FSNSM2 RPK-4.0FSNSM2 RPF-1.5FSN2E Floor Concealed Type RPFI-1.0FSN2E RPFI-1.5FSN2E Ceiling Type RPC-2.0FSN2 RPC-4.0FSN2 RPC-2.5FSN2 RPC-5.0FSN2 RPC-3.0FSN2 System Equipment Total Heat Exchangers KPI-2521 KPI-5021 KPI-8021 KPI-10021 SET-FREE FSN2 Indoor Units TIPS ON ENERGY EFFICIENT VRF DESIGN TIP No 1: Shorter pipe run will minimize capacity loss and reduce refrigerant charge in system. TIP No 2: Take advantage of diversity factor will reduce your initial capital as well as ongoing running cost. TIP No 3: Each zone served by dedicated unit will help to increase comfort level and reduce Energy waste. TIPS ON ENERGY EFFICIENT VRF DESIGN TIP No 4: Heat recovery system will not only provide simultaneous cooling and heating, but also recover energy that would be lost in traditional system. TIP No 5: Having minimum Change Over box in same zone will prevent units from fighting against each others and save energy. TIP No 6: Unbalanced selection will cause small unit starve from Refrigerant and run longer than it should be. CONTENTS Technical Data Items 1. Features Page 1-5 1.1 System Features 1-5 1.2 Features on Indoor Unit 1-12 1.2.1 In-the-Ceiling Type 1-12 1.2.2 4-Way Cassette Type 1-13 1.2.3 2-Way Cassette Type 1-16 1.2.4 Wall Type 1-18 1.2.5 Floor Type 1-20 1.2.6 Floor Concealed Type 1-20 1.2.7 Ceiling Type 1-21 1.3 Features on Total Heat Exchangers 1-22 1.4 Features on Optional Liquid Crystal Remote Control Switch, Wireless Remote Control Switch, Half Size Remote Control Switch, 7-Day Timer and Central Stations 1-23 1.4.1 Lineup 1-23 1.4.2 Liquid Crystal Remote Control Switch, PC-AR (Optional) 1-23 1.4.3 Wireless Remote Control Switch, PC-LH3A (Optional) 1-25 1.4.4 Half Size Remote Control Switch, PC-ARH (Optional) 1-26 1.4.5 7-Day Timer, PSC-A1T (Optional) 1-27 1.4.6 Central Station, PSC-5S (Optional) and PSC-A64S (Optional) 1-28 1.4.7 Centralized ON/OFF Controller, PSC-A16RS (Optional) 1-30 2. General Data 1-31 3. Dimensional Data 1-43 3.1 Dimensional Data for Indoor Units 1-43 3.2 Dimensional Data for Total Heat Exchangers 1-56 4. Selection Data 1-57 4.1 Operation Space 1-57 4.2 Selection Guide 1-60 4.3 Sensible Heat Factor (SHF) 1-62 4.4 Fan Performance 1-63 4.5 Model Selection of Total Heat Exchangers 1-68 5. Electrical Data 1-72 6. Sound Data 1-74 7. Working Range 1-87 iv CONTENTS Technical Data Items 8. Optional Accessories 8.1 for Control Systems Page 1-88 1-88 8.1.1 Liquid Crystal Remote Control Switch (PC-AR) 1-88 8.1.2 Wireless Remote Control Switch (PC-LH3A) 1-88 8.1.3 Half Size Remote Control Switch (PC-ARH) 1-88 8.1.4 7-Day Timer (PSC-A1T) 1-88 8.1.5 Central Station (PSC-5S and PSC-A64S) 1-89 8.1.6 Centralized ON/OFF Controller (PSC-A16RS) 1-93 8.1.7 Receiver Kit (PC-ALH, PC-ALHD, PC-ALHP and PC-ALHZ) 1-93 8.1.8 Remote Control Cable <for PC-AR> (PRC-5K, PRC-10K and PRC-15K) 1-93 8.1.9 3P Connector Cable (PCC-1A) 1-93 8.1.10 Remote Sensor (THM-R2A) 8.2 for Indoor Units 1-93 1-94 8.2.1 for In-the-Ceiling Type 1-94 8.2.2 for 4-Way Cassette Type 1-98 8.2.3 for 2-Way Cassette Type 1-109 9. Component Data 10. Control System 1-117 1-124 10.1 Refrigeration Cycle 1-124 10.2 System Control 1-130 10.2.1 Control in a Room 1-130 10.2.2 Group Control from a Remote Place 1-131 10.2.3 Control in a Room/Control from a Remote Place 1-131 10.3 Standard Operation Sequence 1-132 10.4 Safety and Control Device Setting 1-138 10.5 Optional Dip Switch Setting for Capacity Adjustment 1-138 10 6 Electrical 10.6 El t i l Wiring Wi i Diagram Di 1-139 1 139 11. Miscellaneous Notes 12. Standard Specifications 1-149 1-151A-B-C 1-151 v CONTENTS Installation and Operation Page Indoor Unit Type Items RPI RPI (0.8 to 5.0HP) (8 and 10HP) RCI RCD RPK RPF RPFI RPC 1. Safety Summary 2-5 2-19 2-31 2-43 2-55 2-73 2-83 2. Structure 2-5 2-19 2-31 2-43 2-55 2-73 2-83 2.1 Indoor Unit 2-5 2-19 2-31 2-43 2-55 2-73 2-83 2.2 Refrigerant Cycle 2-7 2-20 2-32 2-44 2-58 2-74 2-84 2.3 Necessary Tools and Instruments List for Installation 2-7 2-20 2-32 2-44 2-58 2-74 2-84 2-7 2-20 2-32 2-44 2-58 2-74 2-84 3.1 Transportation 2-7 2-20 2-32 2-44 2-58 2-74 2-84 3.2 Handling of Indoor Unit 2-7 2-20 2-32 2-44 2-58 2-74 2-84 2-7 2-21 2-33 2-45 2-59 2-75 2-85 4.1 Factory-Supplied Accessories 2-7 2-21 2-33 2-45 2-59 2-75 2-85 4.2 Initial Check 2-9 2-22 2-34 2-46 2-60 2-76 2-86 4.3 Installation 2-10 2-23 2-35 2-47 2-62 2-77 2-87 2-13 2-25 2-37 2-49 2-67 2-78 2-88 5.1 Piping Materials 2-13 2-25 2-37 2-49 2-67 2-78 2-88 5.2 Piping Connection 2-13 2-25 2-37 2-49 2-67 2-78 2-88 6. Drain Piping 2-14 2-27 2-38 2-50 2-69 2-79 2-90 7. Electrical Wiring 2-15 2-28 2-40 2-52 2-70 2-80 2-91 7.1 General Check 2-15 2-28 2-40 2-52 2-70 2-80 2-92 7.2 Electrical Wiring Connection 2-15 2-28 2-40 2-52 2-70 2-80 2-92 8. Test Run 2-17 2-30 2-42 2-54 2-72 2-82 2-93 9. Safety and Control Device Setting 2-17 2-30 2-42 2-54 2-72 2-82 2-93 3. Transportation and Handling 4. Indoor Unit Installation 5. Refrigerant Piping Work 10. Common 2-95 10.1 Field Minimum Wire Size for Power Source 2-95 10.2 Setting of Dip Switches 2-96 10.3 Setting the Filter Indication Interval 2-101 10.4 Setting of High Speed Tap 2-102 10.5 Setting of External Pressure 2-102 vi CONTENTS Installation and Operation Items 11. Installation of Optional Air Panel Page 2-103 11.1 Air Panel for 4-Way Cassette Type: P-N23WA 2-103 11.2 Air Panel for 2-Way Cassette Type: P-N23DWA and P-N46DWA 2-108 12. Installation of Optional Controller 2-113 12.1 Remote Control Switch : PC-AR 2-114 12.2 Wireless Remote Control Switch: PC-LH3A 2-132 12.3 7-Day Timer : PSC-A1T 2-137 12.4 Central Station: PSC-5S 2-151 12.5 Central Station: PSC-A64S 2-169 12.6 Centralized ON/OFF Controller: PSC-A16RS 2-192 12.7 Wireless Receiver Kit: PC-ALH (for 4-Way Cassette Type) 2-204 12.8 Wireless Receiver Kit: PC-ALHD, PC-ALHP and PC-ALHZ (for 2-Way Cassette Type, Ceiling Type, In-the-Ceiling Type, Floor Type, Floor Concealed Type and Wall Type) 2-210 13. Total Heat Exchanger 2-220 13.1 Safety Summary 2-220 13.2 Structure 2-220 13.3 Transportation and Handling 2-221 13.4 Installation 2-221 13.5 Electrical Wiring 2-225 13.6 Test Run 2-232 13.7 Safety and Control Device Setting 2-232 14. Maintenance 2-233 15. Operation 2-234 15.1 Remote Control Switch 2-234 15.2 Before Operation 2-236 15.3 Operation Method 2-236 15.4 Setting of Automatic Swing Louver Direction 2-237 15.5 Automatic Control 2-244 15.6 Identifying of Indoor Units Installed Side by Side 2-245 15.7 Filter Cleaning 2-246 15.8 Filter and Element Cleaning for Total Heat Exchanger 2-249 15.9 Replacing Batteries for Wireless Remote Control Switch 2-250 16. Troubleshooting 2-251 16.1 Initial Troubleshooting 2-251 16.2 Troubleshooting by Alarm Code 2-252 16.3 Troubleshooting in Check Mode by Remote Control Switch 2-254 16.4 Self-Checking of PCB using Remote Control Switch 2-260 16.5 Self-Checking of Remote Control Switch 2-262 vii TECHNICAL DATA GENERAL DATA 2. General Data Indoor Unit Type Model Indoor Unit Power Supply Nominal Cooling kW Capacity *1) kcal/h Btu/h Nominal Cooling kW Capacity *2) kcal/h Btu/h Nominal Heating kW Capacity kcal/h Btu/h Sound Pressure Level (Overall A Scale) dB Outer Dimensions Height mm (in.) Width mm (in.) Depth mm (in.) Net Weight kg (lbs.) Refrigerant Indoor Fan Air Flow Rate m3/min. (Hi/Me/Lo) (cfm) External Pressure *3) Pa Motor W Connections Refrigerant Piping Liquid Line mm (in.) Gas Line mm (in.) Condensate Drain Approximate Packing Measurement m3 RPI-0.8FSN2 2.3 2,000 7,900 2.2 1,900 7,500 2.5 2,100 8,500 35-33-31 In-the-Ceiling Type RPI-1.0FSN2 RPI-1.5FSN2 AC 1, 220-240V/50Hz, 220V/60Hz 2.9 4.1 2,500 3,550 9,900 14,100 2.8 4.0 2,400 3,400 9,600 13,600 3.2 4.8 2,800 4,100 10,900 16,400 35-33-31 35-33-31 RPI-2.0FSN2 5.8 5,000 19,800 5.6 4,800 19,100 6.3 5,400 21,500 35-33-31 270 270 270 270 (10-5/8) (10-5/8) (10-5/8) (10-5/8) 650+75 650+75 650+75 900+75 (25-9/16+2-15/16) (25-9/16+2-15/16) (25-9/16+2-15/16) (35-7/16+2-15/16) 720 720 720 720 (28-3/8) (28-3/8) (28-3/8) (28-3/8) 26 26 26 35 (57) (57) (57) (77) R410A / R407C / R22 (Nitrogen-Charged for Corrosion-Resistance) 8/7/6 (283/247/212) 50 (80-30) 60 8/7/6 13/11/9 (283/247/212) (459/388/318) 50 (80-30) 50 (80-30) 60 60 Flare-Nut Connection (with Flare Nuts) 15/13/11 (530/459/388) 50 (80-30) 75 6.35 (1/4) 12.7 (1/2) VP25 6.35 (1/4) 12.7 (1/2) VP25 6.35 (1/4) 12.7 (1/2) VP25 6.35 (1/4) 15.88 (5/8) VP25 0.21 0.21 0.21 0.27 NOTES: 1. The nominal cooling capacity is the combined capacity of the HITACHI standard split system, and is based on the JIS standard B8616. Cooling Operation Conditions Indoor Air Inlet Temperature: Outdoor Air Inlet Temperature: Heating Operation Conditions Indoor Air Inlet Temperature: Outdoor Air Inlet Temperature: Piping Length: 7.5 Meters 27oC DB (80oF DB) *1) 19.5oC WB (67oF WB) *2) 19.0oC WB (66.2oF WB) 35oC DB (95oF DB) 20oC DB (68oF DB) 7oC DB (45oF DB) 6oC WB (43oF WB) Piping Lift: 0 Meter 2. The sound pressure level is based on following conditions. 1.5 Meter Beneath the Unit. With Discharge Duct (2.0m) and Return Duct (1.0m). Voltage of the power source for the indoor fan motor is 220V. In case of the power source of 240V, the sound pressure level increases by about 1 dB. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field. 3. The data for external pressure *3) indicates "Standard Pressure Setting (High Pressure Setting - Low Pressure Setting)" values when a filter is not used. The sound pressure level is based on the Standard Pressure Setting. 1-31 GENERAL DATA Indoor Unit Type Model Indoor Unit Power Supply Nominal Cooling kW Capacity *1) kcal/h Btu/h Nominal Cooling kW Capacity *2) kcal/h Btu/h Nominal Heating kW Capacity kcal/h Btu/h Sound Pressure Level (Overall A Scale) dB Outer Dimensions Height mm (in.) Width mm (in.) Depth mm (in.) Net Weight kg (lbs.) Refrigerant Indoor Fan Air Flow Rate m3/min. (Hi/Me/Lo) (cfm) External Pressure *3) Pa Motor W Connections Refrigerant Piping Liquid Line mm (in.) Gas Line mm (in.) Condensate Drain Approximate Packing Measurement m3 RPI-2.5FSN2 7.3 6,300 25,000 7.1 6,100 24,200 8.5 7,300 29,000 36-34-32 In-the-Ceiling Type RPI-3.0FSN2 RPI-4.0FSN2 AC 1, 220-240V/50Hz, 220V/60Hz 8.3 11.6 7,100 10,000 28,200 39,700 8.0 11.2 6,900 9,600 27,300 38,200 9.0 12.5 7,700 10,700 30,700 42,600 42-39-35 RPI-5.0FSN2 14.5 12,500 49,600 14.0 12,000 47,800 16.0 13,800 54,600 43-40-36 44-41-37 270 350 350 350 (10-5/8) (13-3/4) (13-3/4) (13-3/4) 900+75 650+75 900+75 1,300+75 (35-7/16+2-15/16) (25-9/16+2-15/16) (35-7/16+2-15/16) (51-3/16+2-15/16) 720 800 800 800 (28-3/8) (31-1/2) (31-1/2) (31-1/2) 35 37 46 58 (77) (82) (101) (128) R410A / R407C / R22 (Nitrogen-Charged for Corrosion-Resistance) 16/14/12 (565/494/424) 50 (80-30) 75 19/17/14 27/23/19 (671/600/494) (954/812/671) 120 (170-60) 120 (170-60) 150 290 Flare-Nut Connection (with Flare Nuts) 37/31/25 (1,306/1,095/883) 120 (170-60) 290 9.53 (3/8) 15.88 (5/8) VP25 9.53 (3/8) 15.88 (5/8) VP25 9.53 (3/8) 15.88 *4 (5/8) VP25 9.53 (3/8) 15.88 *4) (5/8) VP25 0.27 0.29 0.38 0.52 NOTES: 1. The nominal cooling capacity is the combined capacity of the HITACHI standard split system, and is based on the JIS standard B8616. Cooling Operation Conditions Indoor Air Inlet Temperature: Outdoor Air Inlet Temperature: Heating Operation Conditions Indoor Air Inlet Temperature: Outdoor Air Inlet Temperature: Piping Length: 7.5 Meters 27oC DB (80oF DB) *1) 19.5oC WB (67oF WB) *2) 19.0oC WB (66.2oF WB) 35oC DB (95oF DB) 20oC DB (68oF DB) 7oC DB (45oF DB) 6oC WB (43oF WB) Piping Lift: 0 Meter 2. The sound pressure level is based on following conditions. 1.5 Meters Beneath the Unit. With Discharge Duct (2.0m) and Return Duct (1.0m). Voltage of the power source for the indoor fan motor is 220V. In case of the power source of 240V, the sound pressure level increases by about 1 or 2 dB. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field. 3. The data for external pressure *3) indicates "Standard Pressure Setting (High Pressure Setting - Low Pressure Setting)" values when a filter is not used. The sound pressure level is based on the Standard Pressure Setting. 4. *4) In case of using R407C or R22, use the accessory adaptor and 19.05 piping. 1-32 GENERAL DATA Indoor Unit Type Model Indoor Unit Power Supply Nominal Cooling kW Capacity *1) kcal/h Btu/h Nominal Cooling kW Capacity *2) kcal/h Btu/h Nominal Heating kW Capacity kcal/h Btu/h Sound Pressure Level (Overall A Scale) *3) dB Outer Dimensions Height mm (in.) Width mm (in.) Depth mm (in.) Net Weight kg (lbs.) Refrigerant Indoor Fan Air Flow Rate m3/min. (cfm) External Pressure *4) 380/415V Pa Motor kW Connections Refrigerant Piping Liquid Line mm (in.) Gas Line mm (in.) Condensate Drain Approximate Packing Measurement m3 In-the-Ceiling Type RPI-8FSN RPI-10FSN AC 3 4W, 380-415V/50Hz, 380V/60Hz 23.3 20,000 79,400 22.4 19,300 76,400 25.0 21,500 85,300 29.1 25,000 99,200 28.0 24,100 95,500 31.5 27,100 107,500 45 (42)* 52 (50)* 470 470 (18-1/2) (18-1/2) 1,250 1,250 (49-1/4) (49-1/4) 1,120 1,120 (44-1/12) (44-1/12) 100 100 (221) (221) R410A / R407C / R22 (Nitrogen-Charged for Corrosion-Resistance) 58 (58)* (2,048 (2,048)*) 72 (72)* (2,542 (2,542)*) 220 (110)* / 260 (130)* 0.76 (0.51)* 220 (110)* / 260 (130)* 1.08 (0.81)* Brazing Connection 9.53 *5) (3/8) 19.05 *6) (3/4) VP25 9.53 *5) (3/8) 22.2 *7) (7/8) VP25 1.06 1.06 NOTES: 1. The nominal cooling capacity is the combined capacity of the HITACHI standard split system, and is based on the JIS standard B8616. Cooling Operation Conditions Indoor Air Inlet Temperature: Outdoor Air Inlet Temperature: Heating Operation Conditions Indoor Air Inlet Temperature: Outdoor Air Inlet Temperature: Piping Length: 7.5 Meters 27oC DB (80oF DB) *1) 19.5oC WB (67oF WB) *2) 19.0oC WB (66.2oF WB) 35oC DB (95oF DB) 20oC DB (68oF DB) 7oC DB (45oF DB) 6oC WB (43oF WB) Piping Lift: 0 Meter 2. The sound pressure level *3) is based on following conditions. 1.5 Meters Beneath the Unit. With Discharge Duct (2.0m) and Return Duct (1.0m). Voltage of the power source for the indoor fan motor is 380V. In case of the power source of 415V, the sound pressure level increases by about 2 dB. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field. 3. The values with ( )* of sound pressure level, air flow rate, external pressure and motor output indicate the values in case of external static pressure setting at 110Pa (130Pa for 415V). 4. The external pressure *4) indicates the values when a filter is not used. 5. *5) In case of using R407C or R22, use the accessory reducer and 12.7 piping. *6) In case of using R407C or R22, use the accessory reducer and 25.4 piping. *7) In case of using R407C or R22, use the accessory reducer and 28.6 piping. 1-33 GENERAL DATA Indoor Unit Type Model Indoor Unit Power Supply Nominal Cooling kW Capacity *1) kcal/h Btu/h Nominal Cooling kW Capacity *2) kcal/h Btu/h Nominal Heating kW Capacity kcal/h Btu/h Sound Pressure Level (Overall A Scale) dB Outer Dimensions Height mm (in.) Width mm (in.) Depth mm (in.) Net Weight kg (lbs.) Refrigerant Indoor Fan Air Flow Rate m3/min. (Hi/Me/Lo) (cfm) Motor W Connections Refrigerant Piping Liquid Line mm (in.) Gas Line mm (in.) Condensate Drain Approximate Packing Measurement m3 Adaptable Panel Model Color Outer Dimensions Height mm (in.) Width mm (in.) Depth mm (in.) Net Weight kg (lbs.) Approximate Packing Measurement m3 2.9 2,500 9,900 2.8 2,400 9,600 3.2 2,800 10,900 4-Way Cassette Type RCI-1.5FSN2 AC 1, 220-240V/50Hz, 220V/60Hz 4.1 3,550 14,100 4.0 3,400 13,600 4.8 4,100 16,400 30-28-27 30-28-27 RCI-1.0FSN2 RCI-2.0FSN2 5.8 5,000 19,800 5.6 4,800 19,100 6.3 5,400 21,500 30-28-27 248 248 248 (9-3/4) (9-3/4) (9-3/4) 840 840 840 (33-1/16) (33-1/16) (33-1/16) 840 840 840 (33-1/16) (33-1/16) (33-1/16) 23 23 24 (51) (51) (53) R410A / R407C / R22 (Nitrogen-Charged for Corrosion-Resistance) 13/12/11 (459/424/388) 56 15/13.5/12 (530/477/424) 56 Flare-Nut Connection (with Flare Nuts) 16/14/12 (565/494/424) 56 6.35 (1/4) 12.7 (1/2) VP25 6.35 (1/4) 12.7 (1/2) VP25 6.35 (1/4) 15.88 (5/8) VP25 0.22 P-N23WA 0.22 P-N23WA Silky White 0.22 P-N23WA 37 (1-7/16) 950 (37-3/8) 950 (37-3/8) 6 (13) 37 (1-7/16) 950 (37-3/8) 950 (37-3/8) 6 (13) 37 (1-7/16) 950 (37-3/8) 950 (37-3/8) 6 (13) 0.09 0.09 0.09 NOTES: 1. The nominal cooling capacity is the combined capacity of the HITACHI standard split system, and is based on the JIS standard B8616. Cooling Operation Conditions Indoor Air Inlet Temperature: Outdoor Air Inlet Temperature: Heating Operation Conditions Indoor Air Inlet Temperature: Outdoor Air Inlet Temperature: Piping Length: 7.5 Meters 27oC DB (80oF DB) *1) 19.5oC WB (67oF WB) *2) 19.0oC WB (66.2oF WB) 35oC DB (95oF DB) 20oC DB (68oF DB) 7oC DB (45oF DB) 6oC WB (43oF WB) Piping Lift: 0 Meter 2. The sound pressure level is based on following conditions. 1.5 Meters Beneath the Unit. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field. 1-34 GENERAL DATA Indoor Unit Type Model Indoor Unit Power Supply Nominal Cooling kW Capacity *1) kcal/h Btu/h Nominal Cooling kW Capacity *2) kcal/h Btu/h Nominal Heating kW Capacity kcal/h Btu/h Sound Pressure Level (Overall A Scale) dB Outer Dimensions Height mm (in.) Width mm (in.) Depth mm (in.) Net Weight kg (lbs.) Refrigerant Indoor Fan Air Flow Rate m3/min. (Hi/Me/Lo) (cfm) Motor W Connections Refrigerant Piping Liquid Line mm (in.) Gas Line mm (in.) Condensate Drain Approximate Packing Measurement m3 Adaptable Panel Model Color Outer Dimensions Height mm (in.) Width mm (in.) Depth mm (in.) Net Weight kg (lbs.) Approximate Packing Measurement m3 RCI-2.5FSN2 7.3 6,300 25,000 7.1 6,100 24,200 8.5 7,300 29,000 32-30-28 248 (9-3/4) 840 (33-1/16) 840 (33-1/16) 24 (53) 4-Way Cassette Type RCI-3.0FSN2 RCI-4.0FSN2 AC 1, 220-240V/50Hz, 220V/60Hz 8.3 11.6 7,100 10,000 28,200 39,700 8.0 11.2 6,900 9,600 27,300 38,200 9.0 12.5 7,700 10,700 30,700 42,600 32-30-28 RCI-5.0FSN2 14.5 12,500 49,600 14.0 12,000 47,800 16.0 13,800 54,600 38-35-33 39-37-35 298 298 298 (11-3/4) (11-3/4) (11-3/4) 840 840 840 (33-1/16) (33-1/16) (33-1/16) 840 840 840 (33-1/16) (33-1/16) (33-1/16) 26 29 29 (57) (64) (64) R410A / R407C / R22 (Nitrogen-Charged for Corrosion-Resistance) 20/17/15 (706/600/530) 56 21/18/15 32/28/24 (741/635/530) (1,130/989/847) 56 124 Flare-Nut Connection (with Flare Nuts) 34/29/25 (1,201/1,024/883) 124 9.53 (3/8) 15.88 (5/8) VP25 9.53 (3/8) 15.88 (5/8) VP25 9.53 (3/8) 15.88 *3) (5/8) VP25 9.53 (3/8) 15.88 *3) (5/8) VP25 0.22 P-N23WA 0.26 P-N23WA 0.26 P-N23WA 0.26 P-N23WA Silky White 37 (1-7/16) 950 (37-3/8) 950 (37-3/8) 6 (13) 37 (1-7/16) 950 (37-3/8) 950 (37-3/8) 6 (13) 37 (1-7/16) 950 (37-3/8) 950 (37-3/8) 6 (13) 37 (1-7/16) 950 (37-3/8) 950 (37-3/8) 6 (13) 0.09 0.09 0.09 0.09 NOTES: 1. The nominal cooling capacity is the combined capacity of the HITACHI standard split system, and is based on the JIS standard B8616. Cooling Operation Conditions Indoor Air Inlet Temperature: Outdoor Air Inlet Temperature: Heating Operation Conditions Indoor Air Inlet Temperature: Outdoor Air Inlet Temperature: Piping Length: 7.5 Meters 27oC DB (80oF DB) *1) 19.5oC WB (67oF WB) *2) 19.0oC WB (66.2oF WB) 35oC DB (95oF DB) 20oC DB (68oF DB) 7oC DB (45oF DB) 6oC WB (43oF WB) Piping Lift: 0 Meter 2. The sound pressure level is based on following conditions. 1.5 Meters Beneath the Unit. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field. 3. *3) In case of using R407C or R22, use the accessory adaptor and 19.05 piping. 1-35 GENERAL DATA Indoor Unit Type Model Indoor Unit Power Supply Nominal Cooling kW Capacity *1) kcal/h Btu/h Nominal Cooling kW Capacity *2) kcal/h Btu/h Nominal Heating kW Capacity kcal/h Btu/h Sound Pressure Level (Overall A Scale) dB Outer Dimensions Height mm (in.) Width mm (in.) Depth mm (in.) Net Weight kg (lbs.) Refrigerant Indoor Fan Air Flow Rate m3/min. (Hi/Me/Lo) (cfm) Motor W Connections Refrigerant Piping Liquid Line mm (in.) Gas Line mm (in.) Condensate Drain Approximate Packing Measurement m3 Standard Accessories Adaptable Panel Model Color Outer Dimensions Height mm (in.) Width mm (in.) Depth mm (in.) Net Weight kg (lbs.) Approximate Packing Measurement m3 2.9 2,500 9,900 2.8 2,400 9,600 3.2 2,800 10,900 2-Way Cassette Type RCD-1.5FSN2 AC 1, 220-240V/50Hz, 220V/60Hz 4.1 3,550 14,100 4.0 3,400 13,600 4.8 4,100 16,400 34-32-30 35-32-30 RCD-1.0FSN2 RCD-2.0FSN2 5.8 5,000 19,800 5.6 4,800 19,100 6.3 5,400 21,500 35-32-30 298 298 298 (11-3/4) (11-3/4) (11-3/4) 860 860 860 (33-7/8) (33-7/8) (33-7/8) 620 620 620 (24-7/16) (24-7/16) (24-7/16) 27 27 27 (60) (60) (60) R410A / R407C / R22 (Nitrogen-Charged for Corrosion-Resistance) 10/9/8 (353/318/282) 35 13/11/9 (459/388/318) 35 Flare-Nut Connection (with Flare Nuts) 15/13/11 (530/459/388) 35 6.35 (1/4) 12.7 (1/2) VP25 6.35 (1/4) 12.7 (1/2) VP25 6.35 (1/4) 15.88 (5/8) VP25 0.23 0.23 Mounting Bracket P-N23DWA Silky White 0.23 P-N23DWA P-N23DWA 30 (1-3/16) 1,100 (43-5/16) 710 (27-15/16) 6 (13) 30 (1-3/16) 1,100 (43-5/16) 710 (27-15/16) 6 (13) 30 (1-3/16) 1,100 (43-5/16) 710 (27-15/16) 6 (13) 0.10 0.10 0.10 NOTES: 1. The nominal cooling capacity is the combined capacity of the HITACHI standard split system, and is based on the JIS standard B8616. Cooling Operation Conditions Indoor Air Inlet Temperature: Outdoor Air Inlet Temperature: Heating Operation Conditions Indoor Air Inlet Temperature: Outdoor Air Inlet Temperature: Piping Length: 7.5 Meters 27oC DB (80oF DB) *1) 19.5oC WB (67oF WB) *2) 19.0oC WB (66.2oF WB) 35oC DB (95oF DB) 20oC DB (68oF DB) 7oC DB (45oF DB) 6oC WB (43oF WB) Piping Lift: 0 Meter 2. The sound pressure level is based on following conditions. 1.5 Meters Beneath the Unit. Voltage of the power source for the indoor fan motor is 220V. In case of the power source of 240V, the sound pressure level increases by about 1 dB. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field. 1-36 GENERAL DATA Indoor Unit Type Model Indoor Unit Power Supply Nominal Cooling kW Capacity *1) kcal/h Btu/h Nominal Cooling kW Capacity *2) kcal/h Btu/h Nominal Heating kW Capacity kcal/h Btu/h Sound Pressure Level (Overall A Scale) dB Outer Dimensions Height mm (in.) Width mm (in.) Depth mm (in.) Net Weight kg (lbs.) Refrigerant Indoor Fan Air Flow Rate m3/min. (Hi/Me/Lo) (cfm) Motor W Connections Refrigerant Piping Liquid Line mm (in.) Gas Line mm (in.) Condensate Drain Approximate Packing Measurement m3 Standard Accessories Adaptable Panel Model Color Outer Dimensions Height mm (in.) Width mm (in.) Depth mm (in.) Net Weight kg (lbs.) Approximate Packing Measurement m3 RCD-2.5FSN2 7.3 6,300 25,000 7.1 6,100 24,200 8.5 7,300 29,000 38-34-31 298 (11-3/4) 860 (33-7/8) 620 (24-7/16) 30 (66) 2-Way Cassette Type RCD-3.0FSN2 RCD-4.0FSN2 AC 1, 220-240V/50Hz, 220V/60Hz 8.3 11.6 7,100 10,000 28,200 39,700 8.0 11.2 6,900 9,600 27,300 38,200 9.0 12.5 7,700 10,700 30,700 42,600 38-34-31 RCD-5.0FSN2 14.5 12,500 49,600 14.0 12,000 47,800 16.0 13,800 54,600 40-36-33 43-40-36 298 298 298 (11-3/4) (11-3/4) (11-3/4) 860 1,420 1,420 (33-7/8) (55-7/8) (55-7/8) 620 620 620 (24-7/16) (24-7/16) (24-7/16) 30 48 48 (66) (106) (106) R410A / R407C / R22 (Nitrogen-Charged for Corrosion-Resistance) 19/16/14 (671/565/494) 55 19/16/14 29/24/21 (671/565/494) (1,024/847/742) 55 35 x 2 Flare-Nut Connection (with Flare Nuts) 9.53 (3/8) 15.88 (5/8) VP25 9.53 (3/8) 15.88 (5/8) VP25 0.23 0.23 P-N23DWA 34/29/25 (1,201/1,024/883) 55 x 2 9.53 (3/8) 15.88 *3) (5/8) VP25 0.37 Mounting Bracket P-N23DWA P-N46DWA Silky White 9.53 (3/8) 15.88 *3) (5/8) VP25 0.37 P-N46DWA 30 (1-3/16) 1,100 (43-5/16) 710 (27-15/16) 6 (13) 30 (1-3/16) 1,100 (43-5/16) 710 (27-15/16) 6 (13) 30 (1-3/16) 1,660 (65-3/8) 710 (27-15/16) 8 (18) 30 (1-3/16) 1,660 (65-3/8) 710 (27-15/16) 8 (18) 0.10 0.10 0.15 0.15 NOTES: 1. The nominal cooling capacity is the combined capacity of the HITACHI standard split system, and is based on the JIS standard B8616. Cooling Operation Conditions Indoor Air Inlet Temperature: Outdoor Air Inlet Temperature: Heating Operation Conditions Indoor Air Inlet Temperature: Outdoor Air Inlet Temperature: Piping Length: 7.5 Meters 27oC DB (80oF DB) *1) 19.5oC WB (67oF WB) *2) 19.0oC WB (66.2oF WB) 35oC DB (95oF DB) 20oC DB (68oF DB) 7oC DB (45oF DB) 6oC WB (43oF WB) Piping Lift: 0 Meter 2. The sound pressure level is based on following conditions. 1.5 Meters Beneath the Unit. Voltage of the power source for the indoor fan motor is 220V. In case of the power source of 240V, the sound pressure level increases by about 1 dB. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field. 3. *3) In case of using R407C or R22, use the accessory adaptor and 19.05 piping. 1-37 GENERAL DATA Indoor Unit Type Model Indoor Unit Power Supply Nominal Cooling kW Capacity *1) kcal/h Btu/h Nominal Cooling kW Capacity *2) kcal/h Btu/h Nominal Heating kW Capacity kcal/h Btu/h Sound Pressure Level (Overall A Scale) dB Cabinet Color Outer Dimensions Height mm (in.) Width mm (in.) Depth mm (in.) Net Weight kg (lbs.) Refrigerant Indoor Fan Air Flow Rate m3/min. (Hi/Me/Lo) (cfm) Motor kW Connections Refrigerant Piping Liquid Line mm (in.) Gas Line mm (in.) Condensate Drain Approximate Packing Measurement m3 Standard Accessories RPK-1.0FSNSM2 2.9 2,500 9,900 2.8 2,400 9,600 3.2 2,800 10,900 38-36-34 Wall Type RPK-1.5FSNSM2 AC 1, 220-240V/50Hz, 220V/60Hz 4.1 3,550 14,100 4.0 3,400 13,600 4.8 4,100 16,400 RPK-2.0FSNSM2 5.8 5,000 19,800 5.6 4,800 19,100 6.3 5,400 21,500 40-38-36 White 41-39-37 280 280 295 (11) (11) (11-5/8) 780 780 1,030 (30-11/16) (30-11/16) (40-9/16) 210 210 208 (8-1/4) (8-1/4) (8-3/16) 10 10 12 (22) (22) (26) R410A / R407C / R22 (Nitrogen-Charged for Corrosion-Resistance) 10/8/7 (353/283/247) 0.02 11/10/9 (388/353/318) 0.02 Flare-Nut Connection (with Flare Nuts) 14/12/10 (494/424/353) 0.03 6.35 (1/4) 12.7 (1/2) VP16 6.35 (1/4) 12.7 (1/2) VP16 6.35 (1/4) 15.88 or 12.7 (*1) (5/8) or (1/2) VP16 0.07 0.07 Wall Mounting Bracket 0.11 (*1) The refrigerant piping size may be required to change depending on the outdoor unit to be connected. If 12.7 pipe is used at the gas side, remove the flare adaptor at the indoor unit gas piping. Then attach the flare nut (accessory) for pipe connection. NOTES: 1. The nominal capacity is the combined capacity of the HITACHI standard SET-FREE system, and is based on the JIS standard B8616. Cooling Operation Conditions Indoor Air Inlet Temperature: Outdoor Air Inlet Temperature: Heating Operation Conditions Indoor Air Inlet Temperature: Outdoor Air Inlet Temperature: Piping Length: 7.5 Meters 27oC DB (80oF DB) *1) 19.5oC WB (67oF WB) *2) 19.0oC WB (66.2oF WB) 35oC DB (95oF DB) 20oC DB (68oF DB) 7oC DB (45oF DB) 6oC WB (43oF WB) Piping Lift: 0 Meter 2. The sound pressure level is based on following conditions. 1 meter beneath the unit and 1 meter from inlet grille. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field. 1-38 GENERAL DATA Indoor Unit Type Model Indoor Unit Power Supply Nominal Cooling kW Capacity *1) kcal/h Btu/h Nominal Cooling kW Capacity *2) kcal/h Btu/h Nominal Heating kW Capacity kcal/h Btu/h Sound Pressure Level (Overall A Scale) dB Cabinet Color Outer Dimensions Height mm (in.) Width mm (in.) Depth mm (in.) Net Weight kg (lbs.) Refrigerant Indoor Fan Air Flow Rate m3/min. (Hi/Me/Lo) (cfm) Motor kW Connections Refrigerant Piping Liquid Line mm (in.) Gas Line mm (in.) Condensate Drain Approximate Packing Measurement m3 Standard Accessories RPK-2.5FSNSM2 7.3 6,300 25,000 7.1 6,100 24,200 8.5 7,300 29,000 43-40-37 Wall Type RPK-3.0FSNSM2 AC 1, 220-240V/50Hz, 220V/60Hz 8.3 7,100 28,200 8.0 6,900 27,300 9.0 7,700 30,700 43-40-37 White RPK-4.0FSNSM2 11.6 10,000 39,700 11.2 9,600 38,200 12.5 10,700 42,600 49-46-43 333 333 333 (13-1/8) (13-1/8) (13-1/8) 1,150 1,150 1,150 (45-1/4) (45-1/4) (45-1/4) 245 245 245 (9-5/8) (9-5/8) (9-5/8) 18 18 18 (40) (40) (40) R410A / R407C / R22 (Nitrogen-Charged for Corrosion-Resistance) 17/16/14 (600/565/494) 0.03 17/16/14 (600/565/494) 0.03 Flare-Nut Connection (with Flare Nuts) 22/20/17 (777/706/600) 0.03 9.53 (3/8) 15.88 (5/8) VP16 9.53 (3/8) 15.88 (5/8) VP16 9.53 (3/8) 15.88 (5/8) VP16 0.13 0.13 Wall Mounting Bracket 0.13 NOTES: 1. The nominal capacity is the combined capacity of the HITACHI standard SET-FREE system, and is based on the JIS standard B8616. Cooling Operation Conditions Indoor Air Inlet Temperature: Outdoor Air Inlet Temperature: Heating Operation Conditions Indoor Air Inlet Temperature: Outdoor Air Inlet Temperature: Piping Length: 7.5 Meters 27oC DB (80oF DB) *1) 19.5oC WB (67oF WB) *2) 19.0oC WB (66.2oF WB) 35oC DB (95oF DB) 20oC DB (68oF DB) 7oC DB (45oF DB) 6oC WB (43oF WB) Piping Lift: 0 Meter 2. The sound pressure level is based on following conditions. 1 meter beneath the unit and 1 meter from inlet grille. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field. 1-39 GENERAL DATA Indoor Unit Type Model Indoor Unit Power Supply Nominal Cooling kW Capacity *1) kcal/h Btu/h Nominal Cooling kW Capacity *2) kcal/h Btu/h Nominal Heating kW Capacity kcal/h Btu/h Sound Pressure Level (Overall A Scale) dB Cabinet Color Outer Dimensions Height mm (in.) Width mm (in.) Depth mm (in.) Net Weight kg (lbs.) Refrigerant Indoor Fan Air Flow Rate m3/min. (Hi/Me/Lo) (cfm) Motor W Connections Refrigerant Piping Liquid Line mm (in.) Gas Line mm (in.) Condensate Drain Approximate Packing Measurement m3 Standard Accessories Floor Type RPF-1.0FSN2E 2.9 2,500 9,900 2.8 2,400 9,600 3.2 2,800 10,900 Floor Concealed Type RPF-1.5FSN2E RPFI-1.0FSN2E RPFI-1.5FSN2E AC 1, 220-240V/50Hz, 220V/60Hz 4.1 2.9 4.1 3,550 2,500 3,550 14,100 9,900 14,100 4.0 2.8 4.0 3,400 2,400 3,400 13,600 9,600 13,600 4.8 3.2 4.8 4,100 2,800 4,100 16,400 10,900 16,400 35-32-29 38-35-31 35-32-29 - Spring White 630 (24-13/16) 1,045 (41-1/8) 220 (8-11/16) 25 (55) 38-35-31 - 630 620 620 (24-13/16) (24-7/16) (24-7/16) 1,170 848 973 (46-1/16) (33-3/8) (38-5/16) 220 220 220 (8-11/16) (8-11/16) (8-11/16) 28 19 23 (62) (42) (51) R410A / R407C / R22 (Nitrogen-Charged for Corrosion-Resistance) 8.5/7/6 (300/247/212) 20 12/10/9 8.5/7/6 (424/353/318) (300/247/212) 28 20 Flare-Nut Connection (with Flare Nuts) 6.35 (1/4) 12.7 (1/2) 18.5 OD 6.35 (1/4) 12.7 (1/2) 18.5 OD 0.22 0.24 12/10/9 (424/353/318) 28 6.35 (1/4) 12.7 (1/2) 18.5 OD 6.35 (1/4) 12.7 (1/2) 18.5 OD 0.22 0.23 OD: Outer Diameter NOTES: 1. The nominal cooling capacity is the combined capacity of the HITACHI standard split system, and is based on the JIS standard B8616. Cooling Operation Conditions Indoor Air Inlet Temperature: Outdoor Air Inlet Temperature: Heating Operation Conditions Indoor Air Inlet Temperature: Outdoor Air Inlet Temperature: Piping Length: 7.5 Meters 27oC DB (80oF DB) *1) 19.5oC WB (67oF WB) *2) 19.0oC WB (66.2oF WB) 35oC DB (95oF DB) 20oC DB (68oF DB) 7oC DB (45oF DB) 6oC WB (43oF WB) Piping Lift: 0 Meter 2. The sound pressure level is based on following conditions. 1 meter from the unit. 1 meter from floor level. Voltage of the power source for the indoor fan motor is 220V. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field. 1-40 GENERAL DATA Indoor Unit Type Model Indoor Unit Power Supply Nominal Cooling kW Capacity *1) kcal/h Btu/h Nominal Cooling kW Capacity *2) kcal/h Btu/h Nominal Heating kW Capacity kcal/h Btu/h Sound Pressure Level (Overall A Scale) dB Cabinet Color Outer Dimensions Height mm (in.) Width mm (in.) Depth mm (in.) Net Weight kg (lbs.) Refrigerant Indoor Fan Air Flow Rate m3/min. (Hi/Me/Lo) (cfm) Motor W Connections Refrigerant Piping Liquid Line mm (in.) Gas Line mm (in.) Condensate Drain Approximate Packing Measurement m3 Standard Accessories Ceiling Type RPC-2.5FSN2 RPC-3.0FSN2 RPC-4.0FSN2 AC 1, 220-240V/50Hz, 220V/60Hz 7.3 8.3 11.6 6,300 7,100 10,000 25,000 28,200 39,700 7.1 8.0 11.2 6,100 6,900 9,600 24,200 27,300 38,200 8.5 9.0 12.5 7,300 7,700 10,700 29,000 30,700 42,600 RPC-2.0FSN2 5.8 5,000 19,800 5.6 4,800 19,100 6.3 5,400 21,500 40-37-34 40-37-34 40-37-34 Silky White 44-41-38 RPC-5.0FSN2 14.5 12,500 49,600 14.0 12,000 47,800 16.0 13,800 54,600 44-41-38 210 (8-1/4) 1,100 (43-5/16) 670 (26-3/8) 26 (57) 210 210 270 (8-1/4) (8-1/4) (10-5/8) 1,320 1,320 1,320 (51-15/16) (51-15/16) (51-15/16) 670 670 670 (26-3/8) (26-3/8) (26-3/8) 30 30 34 (66) (66) (75) R410A / R407C / R22 (Nitrogen-Charged for Corrosion-Resistance) 270 (10-5/8) 1,580 (62-3/16) 670 (26-3/8) 42 (93) 14/12/10 (494/424/353) 35 18/15/12 18/15/12 25/21/18 (636/530/424) (636/530/424) (883/742/636) 50 50 95 Flare-Nut Connection (with Flare Nuts) 33/28/23 (1,165/989/812) 135 6.35 (1/4) 15.88 (5/8) VP20 9.53 (3/8) 15.88 (5/8) VP20 9.53 (3/8) 15.88 (5/8) VP20 9.53 (3/8) 15.88 *3) (5/8) VP20 9.53 (3/8) 15.88 *3) (5/8) VP20 0.30 0.36 0.36 Mounting Bracket 0.43 0.50 NOTES: 1. The nominal cooling capacity is the combined capacity of the HITACHI standard split system, and is based on the JIS standard B8616. Cooling Operation Conditions Indoor Air Inlet Temperature: Outdoor Air Inlet Temperature: 27oC DB (80oF DB) *1) 19.5oC WB (67oF WB) *2) 19.0oC WB (66.2oF WB) 35oC DB (95oF DB) Heating Operation Conditions Indoor Air Inlet Temperature: Outdoor Air Inlet Temperature: 20oC DB (68oF DB) 7oC DB (45oF DB) 6oC WB (43oF WB) Piping Length: 7.5 Meters Piping Lift: 0 Meter 2. The sound pressure level is based on following conditions. 1 Meter Beneath the Unit and 1 Meter from Discharge Grille. Voltage of the power source for the indoor fan motor is 220V. In case of the power source of 240V, the sound pressure level increases by about 1 dB. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field. 3. *3) In case of using R407C or R22, use the accessory adaptor and 19.05 piping. 1-41 GENERAL DATA Unit Type Model Unit Power Supply Air Flow Rate (Hi/Me/Lo) External Pressure (Hi/Me/Lo) Temp. Exchange Efficiency (Hi/Me/Lo) Enthalpy Exchange Efficiency For Heating (Hi/Me/Lo) For Cooling (Hi/Me/Lo) Sound Pressure Level (Over A Scale) at 1.5m from the unit (under) (Hi/Me/Lo) *2), *4) at Air Outlet (Hi/Me/Lo) *3), *4) Outer Dimensions Height Width Depth Net Weight Connection Duct Diameter Width Depth Net Weight Connection Duct Diameter KPI-10021 *1) m3/h 250/250/165 500/500/350 800/800/670 1,000/1,000/870 Pa 65/40/20 150/60/30 140/100/70 160/100/80 % 78/78/83 77/77/82 78/78/80.5 79/79/81 % % 69/69/74 62.5/62.5/68 67/67/73 61.5/61.5/68 71/71/73 64.5/64.5/68 70/70/73 64.5/64.5/67 dB 26.5-27.5/25-26 /21-22 33.5-34.5/32-33 /26-27 32.5-33.5/30-31 /23.5-24.5 40.5-41.5/38-39 /29.5-30.5 33.5-34.5/32-33 /30-31 44.5-45.5/43-44 /40-41 36-37/34-35 /31.5-32.5 47-48/45-46 /41.5-42.5 mm (in.) mm (in.) mm (in.) kg (lbs.) mm 275 (10-13/16) 735 (28-15/16) 780 (30-11/16) 21 (46) 150 317 (12-1/2) 1,016 (40) 888 (34-15/16) 33 (73) 200 398 (15-11/16) 1,004 (39-1/2) 1,164 (45-13/16) 61 (134) 250 398 (15-11/16) 1,231 (48-7/16) 1,164 (45-13/16) 72 (159) 250 KPI-2521 In-the-Ceiling Type KPI-5021 KPI-8021 AC 1, 220/60Hz dB Unit Type Model Unit Power Supply Air Flow Rate (Hi/Me/Lo) External Pressure (Hi/Me/Lo) Temp. Exchange Efficiency (Hi/Me/Lo) Enthalpy Exchange Efficiency For Heating (Hi/Me/Lo) For Cooling (Hi/Me/Lo) Sound Pressure Level (Over A Scale) at 1.5m from the unit (under) (Hi/Me/Lo) *2), *4) at Air Outlet (Hi/Me/Lo) *3), *4) Outer Dimensions Height Total Heat Exchanger KPI-5021 KPI-8021 AC 1, 220-240V/50Hz KPI-2521 KPI-10021 *1) m3/h 250/250/150 500/500/300 800/800/660 1,000/1,000/720 Pa 100/50/20 200/60/20 230/120/80 200/110/60 % 78/78/84 77/77/83.5 78/78/81 79/79/83 % % 69/69/75 62.5/62.5/70 67/67/75 61.5/61.5/70 71/71/73.5 64.5/64.5/68.5 70/70/76 64.5/64.5/71 dB 28.5/25.5/21 32.5/28.5/23 35/31/29 36/34/30 dB 35.5/32.5/26 40.5/36.5/29 46/42/39 47/45/40 mm (in.) mm (in.) mm (in.) kg (lbs.) mm 275 (10-13/16) 735 (28-15/16) 780 (30-11/16) 21 (46) 150 317 (12-1/2) 1,016 (40) 888 (34-15/16) 33 (73) 200 398 (15-11/16) 1,004 (39-1/2) 1,164 (45-13/16) 61 (134) 250 398 (15-11/16) 1,231 (48-7/16) 1,164 (45-13/16) 72 (159) 250 NOTES: *1): KPI-10021 has different units according to the applied power supply, 220-240V/50Hz and 220V/60Hz. *2): The sound pressure level is based on following conditions. 1.5 meters beneath the unit and this data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field. *3): The noise at the air outlets is the values at a 45o angle, 1.5 meters in front of the unit. *4): The sound pressure level is based on the total heat exchange mode. In case of the bypass ventilation mode, the sound pressure level increase by approximately 1 dB(A). 1-42 DIMENSIONAL DATA 3. Dimensional Data 3.1 Dimensional Data for Indoor Units In-the-Ceiling Type Models: RPI-0.8FSN2, RPI-1.0FSN2, RPI-1.5FSN2, RPI-2.0FSN2, RPI-2.5FSN2, RPI-3.0FSN2, RPI-4.0FSN2 and RPI-5.0FSN2 Unit: mm l - 6 (Around the Flange) b a 40 e c x 300 = d 4 - 40 x 12 (for Suspension Bolt) Air Inlet 22 n m x 22 30 20 300 Remote Control Switch g 33.5 30 22 Viewed from A 20 120 l - 6 300 Drain Pipe Connection (2.0 to 5.0HP Standard Position) (VP25) (Around the Flange) c x 300 = d Drain Pipe Connection (0.8 to 1.5HP with Drain-Up Mechanism) Refrigerant Liquid Pipe Connection (With h Flare Nut) 45 A v 2x90=180 u f 48.5 35 23 s t p 97 q 220 75 (Electrical Control Box) r a 2xv=w Refrigerant Gas Pipe Connection (With i Flare Nut) Air Outlet 90 e j (Refrigerant Gas Pipe Connection) 246 (Refrigerant Liquid Pipe Connection) 321 (Refrigerant Gas Pipe Connection) 377 (Drain Pipe Connection: 2.0 to 5.0HP) 402 (Drain Pipe Connection: 0.8 to 1.5HP) 90 (Drain Pipe Connection) k (Refrigerant Liquid Pipe Connection) Dimension HP 0.8 1.0 1.5 2.0 2.5 3.0 4.0 5.0 a b c d e f g h i j k 650 650 650 900 900 650 900 1300 730 730 730 980 980 730 980 1380 1 1 1 2 2 1 2 3 300 300 300 600 600 300 600 900 215 215 215 190 190 215 190 240 553 553 553 803 803 553 803 1203 583 583 583 833 833 583 833 1233 6.35 6.35 6.35 6.35 9.53 9.53 9.53 9.53 12.7 12.7 12.7 15.88 15.88 15.88 15.88 (19.05)*1 15.88 (19.05)*1 70 70 70 77 77 77 81 81 92 92 92 92 95 95 95 95 *1: In case of using R407C or R22, use 19.05 Dimension HP 0.8 1.0 1.5 2.0 2.5 3.0 4.0 5.0 l m n p q r s t u v w x 10 10 10 12 12 10 12 14 676 676 676 676 676 756 756 756 720 720 720 720 720 800 800 800 23 23 23 23 23 103 103 103 270 270 270 270 270 350 350 350 182 182 182 182 182 204 204 204 222 222 222 222 222 244 244 244 43 43 43 43 43 123 123 123 220 220 220 220 220 300 300 300 100 100 100 100 100 140 140 140 200 200 200 200 200 280 280 280 226 226 226 226 226 306 306 306 1-43 DIMENSIONAL DATA In-the-Ceiling Type Models: RPI-8FSN and RPI-10FSN Unit: mm 21 - 3 1034 (for Suspension Bolts) 1100 (Duct Size <outer size>) 1372 (170) 78 100 420 (Duct Size <outer size>) 23 1250 (Unit) 50 x 20 = 1000 50 15 10 102 25 Air Intake Side 2, 3 Air Discharge Side 3 1326 (for Suspension Bolts) 4 - M10 Holes (for Suspension Bolts) 50 x 21 = 1050 1100 (Duct Size <outer size>) 22 - 3 340 60 (Duct Size <outer size>) 1124 1120 24 1067 29 10 Drain Pipe Connection (for using Drain-up Mechanism) 15 Refrigerant Liquid Pipe Connection (b: Brazing) Cutout for Remote Control Switch Cable 470 340 105 249 327 44 41 95 Cutout for Power Source Cable 164 35 30 420 50 x 7 = 350 20 120 50x6=300 Refrigerant Gas Pipe Connection (a: Brazing) Electrical Control Box 20 Remote Control Switch PC-AR (Optional) 422 Drain Pipe Connection (VP-25) 489 Min. 20 (Standard Drain Piping Position) Switch Box JISC8336-1985 (Field-Supplied) Wall Mounting 20 Service Access Panel Embedding Cable in the Wall Service Space 1 : Secure the service space of false ceiling for cleaning the heat exchanger. 2 : Use the air filter (field-supplied) at the intake side. And secure the service space for the air filter. 3 : Use the canvas duct between the indoor unit and duct for duct connection in order to eliminate vibration. (at intake and discharge sides) 730 0 ~20 150 200 Ceiling * Prepare the Service Access Panel for service. * In case that the ceiling board is not be detachable for servicing, prepare a service access panel below the indoor unit for removing the indoor unit. Mounting for Remote Control Switch PC-AR (Optional) 800 ~30 Dim. 0 450 50 450 Service Access Panel 50 Min. 20 20 0 135 1 HP Ref. 8.0 10.0 R410A R22, R407C (*) R410A R22, R407C (*) a b 19.05 25.4 22.2 28.6 9.53 12.7 9.53 12.7 (*): In case of using R22 or R407C, use the accessory adaptor. 1-44 DIMENSIONAL DATA 4-Way Cassette Type Models: RCI-1.0FSN2, RCI-1.5FSN2, RCI-2.0FSN2 and RCI-2.5FSN2 with Air Panel P-N23WA (Optional) Unit: mm Mark 1 2 3 4 5 6 7 8 9 10 11 12 13 20 840 860~910 (Opening Hole for Ceiling) 20 4-14 x 26 Holes (for Suspension Bolt) 760 (for Suspension Bolt) Name Air Outlet Air Inlet Refrigerant Gas Pipe Connection Refrigerant Liquid Pipe Connection Drain Pipe Connection Wiring Hole for Conduit Tube Wiring Hole Suspension Bracket Suspension Bolt Supply Duct Connection Supply Duct Connection Remote Control Switch (PC-AR) Shielded Twist-Pair Cable for PC-AR Dimension HP 20 B 110 (Gas Pipe) 180 (Liquid Pipe) 8 710 (Drain Pipe) 3 1.0 1.5 2.0 2.5 4 9 Suspension Bolts M10 or W3/8 (Field-Supplied) a b 12.7 12.7 15.88 15.88 6.35 6.35 6.35 9.53 Remark 4-Way with a Flare Nut with b Flare Nut VP25 32.5 Knockout Hole 30 x 39 Hole 4-M10 or W3/8 150 x 385 Knockout Hole 150 x 400 Knockout Hole without Cable Min. 0.75mm2, Field-Supplied D Duct Adapter Connection 5 Viewed from C E E 248 7 30 220 100 6 In case of using this, 31 127 25 5 145 cut the insulation material along to the line indicated opening position. 9-M4 (for Self-Tapping Screw) 85 25 75 135 75 135 Enlarged View of D Viewed from B 950 385 150 1 2 120 10 In case of using this, cut the insulation material along to the line indicated opening position. 46 13 (Field-Supplied) 10 12 Air Inlet Grille Optional Air Panel 11 In case of using this, cut the insulation material along to the line indicated opening position. 400 50 220 100 150 145 Switch Box JISC8336-1985 (Field-Supplied) 20 Viewed from A Embedding Cable in the Wall Wall Mounting 9-M4 (for Self-Tapping Screw) Min. 500 Surroundings in the Ceiling Min. 500 135 135 75 Min. 100 Min. 100 Min. 100 Min. 500 10 75 Enlarged View of E Mounting for Remote Control Switch (Optional) Service Space 10 20 25 950 Min. 3000 Min. 500 NOTE: Piping Connection Service Access Panel Separated Installation Service Access Panel Piping Connection Min. 100 Min. 100 Distance between the wall and panel edge must be a min. 1500mm to prevent short circuiting. Min. 100 Optional 6 37 102 A 7 118 (Drain Pipe) 31 36 102 (Gas Pipe) 127 (Liquid Pipe) C 46 24 (Drain Pipe) 860~910 (Opening Hole for Ceiling) 840 760 (for Suspension Bolt) 14 18 (Gas Pipe) 25 (Liquid Pipe) 20 Service Access Panel Piping Connection Closed Installation 1-45 DIMENSIONAL DATA 4-Way Cassette Type Models: RCI-3.0FSN2, RCI-4.0FSN2 and RCI-5.0FSN2 with Air Panel P-N23WA (Optional) Unit: mm 20 860~910 (Opening Hole for Ceiling) 840 20 4-14 x 26 Holes (for Suspension Bolt) 760 (for Suspension Bolt) 20 860~910 (Opening Hole for Ceiling) 760 (for Suspension Bolt) 840 18 (Gas Pipe) Name Air Outlet Air Inlet Refrigerant Gas Pipe Connection Refrigerant Liquid Pipe Connection Drain Pipe Connection Wiring Hole for Conduit Tube Wiring Hole Suspension Bracket Suspension Bolt Supply Duct Connection Supply Duct Connection Remote Control Switch (PC-AR) Shielded Twist-Pair Cable for PC-AR Dimension 20 3.0 4.0 5.0 110 (Gas Pipe) 180 (Liquid Pipe) 8 9 Suspension Bolts M10 or W3/8 (Field-Supplied) 710 (Drain Pipe) 4-Way with a Flare Nut with b Flare Nut VP25 32.5 Knockout Hole 30 x 39 Hole 4-M10 or W3/8 150 x 385 Knockout Hole 150 x 400 Knockout Hole without Cable Min. 0.75mm2, Field-Supplied a b 15.88 15.88 (19.05)*1 15.88 (19.05)*1 9.53 9.53 9.53 HP B Remark *1: In case of using R407C or R22, use 19.05. D Duct Adapter Connection 3 4 Viewed from C 5 E 298 1 7 145 25 5 127 31 30 100 6 In case of using this, cut the insulation material along to the line indicated opening position. 9-M4 (for Self-Tapping Screw) 85 25 75 135 135 75 Enlarged View of D Viewed from B 950 385 220 150 2 120 10 In case of using this, cut the insulation material along to the line indicated opening position. 96 13 (Field-Supplied) 10 12 Air Inlet Grille Optional Air Panel 400 220 11 In case of using this, cut the insulation material along to the line indicated opening position. 50 100 150 145 Switch Box JISC8336-1985 (Field-Supplied) 950 Embedding Cable in the Wall Min. 500 Min. 500 Surroundings in the Ceiling Min. 100 Min. 100 Service Space Min. 500 9-M4 (for Self-Tapping Screw) 10 75 135 135 75 Enlarged View of E Min. 100 Mounting for Remote Control Switch (Optional) 10 20 Wall Mounting 25 20 Viewed from A Min. 3000 Min. 500 NOTE: Piping Connection Service Access Panel Separated Installation Service Access Panel Piping Connection Min. 100 Min. 100 Distance between the wall and panel edge must be a min. 1500mm to prevent short circuiting. Min. 100 Optional 6 37 102 A 7 118 (Drain Pipe) 31 36 102 (Gas Pipe) 127 (Liquid Pipe) C E 96 24 (Drain Pipe) 14 25 (Liquid Pipe) Mark 1 2 3 4 5 6 7 8 9 10 11 12 13 Service Access Panel Piping Connection Closed Installation 1-46 DIMENSIONAL DATA 2-Way Cassette Type Models: RCD-1.0FSN2, RCD-1.5FSN2, RCD-2.0FSN2, RCD-2.5FSN2 and RCD-3.0FSN2 with Air Panel P-N23DWA (Optional) Unit: mm 20 1060 (Opening Hole for Ceiling) Mark 1 2 3 4 5 6 7 8 9 10 11 12 13 20 890 (for Suspension Bolt) 4-12x32 Hole (for Suspension Bolt) 860 20 8 670 (Opening Hole for Ceiling) 540 (for Suspension Bolt) 620 20 12 Name Air Outlet Air Inlet Refrigerant Gas Pipe Connection Refrigerant Liquid Pipe Connection Drain Pipe Connection Wiring Hole for Conduit Tube Wiring Hole Suspension Bracket Suspension Bolt Electrical Control Box Supply Duct Connection Remote Control Switch (PC-AR) Shielded Twist-Pair Cable for PC-AR Remark with a Flare Nut with b Flare Nut VP25 32.5 30 x 39 Hole 4-M10 or W3/8 2-150 x 400 Optional Min. 0.75mm2, Field-Supplied 410 95 (Gas Pipe) 5 95 (Liquid Pipe) 4 3 285 Dimension 9 HP 1.0 1.5 2.0 2.5 3.0 205 25 (Drain Pipe) 50 125 298 E b 12.7 12.7 15.88 15.88 15.88 6.35 6.35 6.35 9.53 9.53 30 B 260 115 D a 11 445 A In case of using 11 , Cut out the insulation material along this line. 9-M4 (for Self-Tapping Screw) Optional 13 12 170 (Field-Supplied) 400 10 120 710 135 Cut out the insulation material along this line. 30 15 6 7 15 180 150 1 55 140 70 150 135 80 430 90 Enlarged View of D 2 11 1 50 1100 9-M4 (for Self-Tapping Screw) 400 Viewed from B Viewed from A 35 150 180 Service Access Panel 170 70 120 55 120 120 In case of using 11 , Cut out the insulation material along this line. Service Access Panel 185 MIN. 100 Separated Installation MIN. 500 MIN. 500 MIN. 500 MIN. 3000 Viewed from E MIN. 100 MIN. 500 185 430 Piping Connection MIN. 100 15 30 MIN. 500 Surroundings in the ceiling 15 110 Piping Connection MIN. 500 Switch Box JISC8336-1985 (Field-Supplied) 20 MIN. 500 Wall Mounting Embedding Cable in the Wall Mounting for Remote Control Switch (Optional) Closed Installation Service Space 20 NOTE: 1. Distance between the wall and panel edge must be a min. 1500mm to prevent short circuiting. 1-47 DIMENSIONAL DATA 2-Way Cassette Type Models: RCD-4.0FSN2 and RCD-5.0FSN2 with Air Panel P-N46DWA (Optional) Unit: mm 20 1620 (Opening Hole for Ceiling) 20 1450 (for Suspension Bolt) 4-12 x 32 Hole (for Suspension Bolt) 1420 670 620 Name Air Outlet Air Inlet Refrigerant Gas Pipe Connection Refrigerant Liquid Pipe Connection Drain Pipe Connection Wiring Hole for Conduit Tube Wiring Hole Suspension Bracket Suspension Bolt Electrical Control Box Supply Duct Connection Remote Control Switch (PC-AR) Shielded Twist-Pair Cable for PC-AR Remark with 15.88 (19.05)*1 Flare Nut with 9.53 Flare Nut VP25 32.5 30 x 39 Hole 4-M10 or W3/8 2-150 x 610 Optional Min. 0.75mm2, Field-Supplied *1: In case of using R407C or R22, use 19.05. 20 540 20 12 Mark 1 2 3 4 5 6 7 8 9 10 11 12 13 8 95 (Gas Pipe) 410 5 95 (Liquid Pipe) 4 3 285 25 (Drain Pipe) 205 E 125 30 115 B 50 298 D 260 9 445 A (Field-Supplied) 170 10-M4 (for Self-Tapping Screw) 610 160 15 150 55 10 120 180 70 140 1 30 13 180 Optional 12 15 710 180 180 11 140 In case of using 11 , Cut out the insulation material along this line. 640 2 Enlarged View of D 1660 In case of using 11 , 11 610 Cut out the insulation material along this line. 160 160 170 160 55 Viewed from A 80 70 1 15 110 MIN. 500 Surroundings in the ceiling 150 180 Service Access Panel Piping Connection 30 10-M4 (for Self-Tapping Screw) Service Access Panel 190 200 190 640 Viewed from E MIN. 500 MIN. 100 MIN. 3000 Piping Connection MIN. 500 Cut out the insulation material along this line. 6 Switch Box JISC8336-1985 (Field-Supplied) MIN. 100 MIN. 500 Closed Installation Separated Installation 20 90 Wall Mounting 50 MIN. 500 MIN. 500 MIN. 100 MIN. 500 7 Viewed from B 20 Embedding Cable in the Wall Mounting for Remote Control Switch (Optional) Service Space NOTE: 1. Distance between the wall and panel edge must be a min. 1500mm to prevent short circuiting. 1-48 DIMENSIONAL DATA Wall Type Models: RPK-1.0FSNSM2 and RPK-1.5FSNSM2 Unit: mm Name Mark Piping Piping Piping 2 Air Outlet 2 Air Inlet 3 Refrigerant Gas Pipe Connection with 12.7 Flare Nut 4 Refrigerant Liquid Pipe Connection with 6.35 Flare Nut 5 Drain Pipe Connection VP16 6 Wiring and Piping Hole Knockout Hole 7 Wiring and Piping Hole 65 Knockout Hole 8 Wiring and Piping Hole 65 Knockout Hole 9 Suspension Bracket 10 Remote Control Switch (Option) Wired PC-AR Wireless PC-LH3A 2 780 210 6 5 5 60 280 6 60 Remark 1 47 Auto Louver 47 Receiver Part 1 10 Option 125 A 120 540 (PC-AR) 56 (PC-LH3A) 410 5 4 480 3 108 Viewed from A 44 Outline of the Unit 60 5 38 20 65 45 280 45 Flange Part for Inserting Suspension Bracket 190 50 20 20 20 20 20 20 25 25 25 30 25 25 25 20 20x3=6 20 20 20 15 35 27 24 20 28 400 15 8 8 23 30 30 20 20 20 34 20 20 20 15 30 30 23 42 37 7.5 190 37.5 7.5 5 38 5 115 20 530 10 8 9 Min. 150 780 7 20 Wall Mounting 20 Embedding Cable in the Wall Min. 100 Min. 1000 Switch Box JISC8336-1985 (Field-Supplied) Min. 100 Unit: mm Mounting for Remote Control Switch (Option) (In case of using PC-AR) Service Space 1-49 DIMENSIONAL DATA Wall Type Model: RPK-2.0FSNSM2 Unit: mm Mark Piping 2 Air Inlet 3 Refrigerant Gas Pipe Connection with 15.88 or 12.7 Flare Nut (*1) 4 Refrigerant Liquid Pipe Connection with 6.35 Flare Nut 5 Drain Pipe Connection VP16 6 Wiring and Piping Hole Knockout Hole 7 Wiring and Piping Hole 65 Knockout Hole 8 Wiring and Piping Hole 65 Knockout Hole 9 Suspension Bracket 10 Remote Control Switch (Option) Piping 2 Wired PC-AR Wireless PC-LH3A (*1): The refrigerant piping size may be required to change depending on the outdoor unit to be connected. If 12.7 pipe is used at the gas side, remove the flare adaptor at the indoor unit gas piping. Then attach the flare nut (accessory) for pipe connection. 2 1030 208 6 60 5 60 295 6 5 Remark Air Outlet Piping 1019 Name 1 47 47 Auto Louver 1 Indication Part 10 Option Receiver Part A 3 125 4 120 (PC-AR) Pipe Diameter a 15.88 440 12.7 410 P Gas Pipe Connection (12.7) 56 Flare Adaptor (PC-LH3A) a 5 470 550 Gas Pipe Connection (15.88) 150 Enlarged View P Viewed from A Flange Part for Inserting Suspension Bracket Outline of the Unit 314 20 38.1 50 50 40 266 38.1 24.9 40 50 50 13.1 22 20x5=100 20 20 20 20 20 20 30 30 40 40 20 12 8.5 15 55 20 4 21.9 15 8.5 8 150 6.5 48.5 20 12.5 8.5 7 9 Min. 150 200 15x4=60 80 30 30 45 48.5 45 49 295 9.5 25 450 21.9 13.1 25 1030 Switch Box JISC8336-1985 (Field-Supplied) Wall Mounting 20 Embedding Cable in the Wall Min. 100 Min. 100 Min. 1000 20 Unit: mm Mounting for Remote Control Switch (Option) (In case of using PC-AR) Service Space 1-50 DIMENSIONAL DATA Wall Type Models: RPK-2.5FSNSM2, RPK-3.0FSNSM2 and RPK-4.0FSNSM2 Unit: mm Mark Air Outlet 2 Air Inlet 3 Refrigerant Gas Pipe Connection with 15.88 Flare Nut 4 Refrigerant Liquid Pipe Connection with 9.53 Flare Nut 5 Drain Pipe Connection VP16 6 Wiring and Piping Hole Knockout Hole 7 Wiring and Piping Hole 80 Knockout Hole 8 Wiring and Piping Hole 80 Knockout Hole 9 Suspension Bracket 10 Remote Control Switch (Option) Piping Piping 2 Remark 1 1140 Piping Name Wired PC-AR Wireless PC-LH3A 2 1150 245 6 70 60 60 Auto Louver 1 Indication Part Receiver Part A 10 Option 5 125 4 8 8 70 333 6 120 56 (PC-AR) (PC-LH3A) 550 3 572 654 141 Viewed from A 565 433.6 780 660 560 105 250 50x4 28 100 105 87 50x4 42 300 300 58 8 Outline of the Unit 7 141 9 1150 Flange Part for Inserting Suspension Bracket Min. 100 42 93 60 10 Switch Box JISC8336-1985 (Field-Supplied) 20 Wall Mounting 20 Embedding Cable in the Wall Min. 100 Min. 200 Min. 1000 333 229 20 141 20 221 40 20 20 25 20 20x5 100 Unit: mm Mounting for Remote Control Switch (Option) (In case of using PC-AR) Service Space 1-51 1-51 DIMENSIONAL DATA Floor Type Models: RPF-1.0FSN2E and RPF-1.5FSN2E 30 Unit: mm 157 168 40 163 220 156 52 133 134 260 388 529 630 182 a View from Front Side Location of Fixing Holes on Floor for Wood Screws (4-M5) b c d a a Location of Fixing Holes on Floor for Bolts (2-M8) 228 630 315 220 103 For Bolt 2-12, 15x18 c 140 b a 220 85 60 View from Upper Side Location of Fixing Holes on Wall 630 Min. 1000 Ceiling Min. 300 Wall a Min. 300 Wall Service Access Mark 1 2 3 4 5 6 7 8 9 10 11 12 Name Air Intlet Air Outlet Refrigerant Gas Line Refrigerant Liquid Line Condensate Drain Hose Drain Pan Fixing Hole on Wall Adjusting Screw Fixing Hole on Floor Fixing Hole on Floor Opening for Wiring Space for Piping Connection on Floor Dimension HP 1.0 1.5 Remark Piping Connection with Flare Nut 12.7 Piping Connection with Flare Nut 6.35 18.5 Outer Diameter 4-14 (Rear) For Installation 4-7 for Wood Screw Rear Side a b c d 1045 1170 754 879 217 217 732 857 1-52 DIMENSIONAL DATA Floor Concealed Type Models: RPFI-1.0FSN2E and RPFI-1.5FSN2E 220 Unit: mm 220 122 72 64 133 19 13 50 52 529 100 114 134 260 388 620 315 52 25 55 b 36 85 60 a 103 View from Front Side b a b c 138 620 315 220 103 220 85 60 View from Upper Side c d a a 77 640 620 Min. 1000 Location of Fixing Holes on Floor for Wood Screws (4-M5) Min. 240 a Mark 1 2 3 4 5 6 7 8 9 Min. 240 Min. 240 Name Air Intlet Air Outlet Refrigerant Gas Line Refrigerant Liquid Line Condensate Drain Hose Drain Pan Fixing Hole on Wall Adjusting Screw Fixing Hole on Floor Dimension HP 1.0 1.5 a Min. 240 Remark Piping Connection with Flare Nut 12.7 Piping Connection with Flare Nut 6.35 18.5 Outer Diameter 4-14 (Rear) For Installation 4-7 for Wood Screw a b c d 863 988 754 879 66 66 732 857 1-53 DIMENSIONAL DATA Ceiling Type Models: RPC-2.0FSN2, RPC-2.5FSN2 and RPC-3.0FSN2 Unit: mm 370 3 92 Cut out the resin along this line. 12 (Field-Supplied) 11 Optional 110 70 110 670 280 148 27 9 120 4-12 (Hole for Suspension Bolt) b (50) 10 (50) a Max.50 Suspension Bolt Length c 160 52 8 70 118 12 70 4 216 210 38 Suspension Bracket 12 1 74 Left Side 176 Switch Box JISC8336-1985 (Field-Supplied) 20 20 305 Wall Mounting Embedding Cable in the Wall Mounting for Remote Control Switch (Optional) 2 Refrigerant Gas Piping with 15.88 Flare Nut Refrigerant Liquid Piping with e Flare Nut 205 5 106 7 Cut out the resin along this line. 135 40 130 40 104 67 d 156 175 102 370 6 Piping Position 9 MIN. 300 MIN.40 MIN. 500 Mark Name 1 Air Outlet 2 Air Inlet 3 Hole for Refrigerant Piping MIN.8 MIN.400 Separated Installation MIN.40 MIN. 300 Closed Installation Service Space Remark MIN. 300 4 Hole for Refrigerant Piping 5 Hole for Refrigerant Piping 6 Drain Piping Connection 7 Hole for Drain Piping 8 Hole for Drain Piping 9 10 11 12 Wiring Hole for Conduit Tube Suspension Bracket Remote Control Switch (PC-AR) Shielded Twist-Pair Cable for PC-AR Dimension HP 2.0 2.5 3.0 Hole for Upper Side Arrangement Knockout Hole for Right Side Arrangement Hole for Rear Side Arrangement VP20 (for Rear Right Side Arrangement) VP20 (for Rear Left Side Arrangement) Knockout Hole for Left Side Arrangement 26.5 Hole Optional Min. 0.75mm2, Field-Supplied a b c d e 1100 1320 1320 1000 1220 1220 960 1180 1180 200 195 195 6.35 9.53 9.53 1-54 DIMENSIONAL DATA Ceiling Type Models: RPC-4.0FSN2 and RPC-5.0FSN2 Unit: mm 280 9 Cut out the resin along this line. 70 92 (Field-Supplied) 110 12 147 27 110 3 Optional 670 280 11 120 4-12 (Hole for Suspension Bolt) b (50) 10 c 52 8 118 70 12 270 70 4 Max.50 Suspension Bolt Length 38 Suspension Bracket 160 1 12 a 276 (50) 74 Left Side 176 Switch Box JISC8336-1985 (Field-Supplied) 20 20 305 Wall Mounting Embedding Cable in the Wall Mounting for Remote Control Switch (Optional) 2 210 Refrigerant Gas Piping with 15.88 (*1) Flare Nut 195 Refrigerant Liquid Piping with 9.53 Flare Nut 156 5 106 7 Cut out the resin along this line. 40 130 104 67 *1: In case of using R407C or R22, use 19.05. 135 175 103 280 6 9 MIN. 300 MIN.40 Separated Installation MIN.40 MIN. 300 Closed Installation Service Space MIN. 500 Piping Position Mark Name 1 Air Outlet 2 Air Inlet 3 Hole for Refrigerant Piping MIN.8 MIN. 400 MIN. 300 Remark 4 Hole for Refrigerant Piping 5 Hole for Refrigerant Piping 6 Drain Piping Connection 7 Hole for Drain Piping 8 Hole for Drain Piping 9 10 11 12 Wiring Hole for Conduit Tube Suspension Bracket Remote Control Switch (PC-AR) Shielded Twist-Pair Cable for PC-AR Dimension HP 4.0 5.0 Hole for Upper Side Arrangem Knockout Hole for Right Side Arrangement Hole for Rear Side Arrangem VP20 (for Rear Right Side Arrangem VP20 (for Rear Left Side Arrangem Knockout Hole for Left Side Arrangement 26.5 Hole Optional Min. 0.75mm2, Field-Supplied a b c 1320 1580 1220 1480 1180 1440 1-55 DIMENSIONAL DATA 3.2 Dimensional Data for Total Heat Exchangers Total Heat Exchangers Models: KPI-2521, KPI-5021, KPI-8021 and KPI-10021 Unit: mm EA and OA ducts are applicable from this side. K Damper plate E Air Exhaust Fan EA RA (Exhaust Air) (Standard Position) D F A (Return Air) Power Cord Opening SA 115 OA (Outside Air) (Standard Position) (Supply Air) K 150 to 250 Min.600 22 10 C Air Supply Fan Service Access Panel Position Electrical Control Box Service Cover Heat Exchanging Element G B G K J H Suspension Bracket Air Filters Model KPI-2521 KPI-5021 Duct Diameter A B C D E F G H J 735 780 275 765 700 530 63 142 160 1,016 888 317 1,048 790 745 79 192 208 1,004 1,164 398 1,036 1,030 690 79 242 258 1,231 1,164 398 1,263 1,030 920 79 242 258 Duct (direction change) K 102 124 149 149 Outer Dimension For Suspension Bolt Duct KPI-8021 KPI-10021 1-56 SELECTION DATA 4. Selection Data 4.1 Operation Space In-the-Ceiling Type Models: RPI-0.8FSN2, RPI-1.0FSN2, RPI-1.5FSN2, RPI-2.0FSN2, RPI-2.5FSN2, RPI-3.0FSN2, RPI-4.0FSN2 and RPI-5.0FSN2 Electrical Box Service Space of False Ceiling 400 600 275 Rear Side In case that the ceiling board can not be detected for servicing, prepare a service access door below the indoor unit for removing the indoor unit. Min. 1000 Rear Side 100 Service Access Door (Min. 450) Front Side View from Bottom (130) Min. 1000 35 Front Side Min. 600 Min. 600 View from Top Models: RPI-8FSN and RPI-10FSN Min. 20 Service Space 730 800 150 ~30 ~20 0 0 0 450 135 50 50 Service Access Panel Secure the service space of false ceiling for cleaning the heat exchanger. 450 Min. 20 200 Ceiling * Prepare the Service Access Panel for service. * In case that the ceiling board is not be detachable for servicing, prepare a service access panel below the indoor unit for removing the indoor unit. Service Access Panel 4-Way Cassette Type Models: RCI-1.0FSN2, RCI-1.5FSN2, RCI-2.0FSN2, RCI-2.5FSN2, RCI-3.0FSN2, RCI-4.0FSN2 and RCI-5.0FSN2 Min. 1500 Min. 500 Min. 1500 Min. 1500 Min. 3000 Min. 1500 Min. 1500 Min. 1500 Min. 1500 Min. 1500 Min. 1500 Min. 1500 Unit: mm Min. 100 Piping Connection Side Min. 100 Min. 500 Min. 1000 Piping Connection Service Access Door Separated Installation Piping Connection Service Access Door Piping Connection Service Space Service Access Door Closed Installation Distance from Wall Side 1-57 SELECTION DATA 2-Way Cassette Type Models: RCD-1.0FSN2, RCD-1.5FSN2, RCD-2.0FSN2, RCD-2.5FSN2, RCD-3.0FSN2, RCD-4.0FSN2 and RCD-5.0FSN2 Service Access Panel Min. 1500 Min. 1500 Min. 1500 10 to 20mm 298mm Unit Height in False Celling Service Access Panel Min. 1500 Min. 1500 Unit Height in False Celling Min. 1500 Min. 1500 Min. 3000 Piping Connection Side Separated Installation Service Access Panel Min. 1500 Min. 100 Min. 500 Piping Connection Side Min. 1500 Min. 1500 Min. 500 Min. 500 Min. 1000 Piping Connection Side Service Space Closed Installation of Two Units Distance from Wall Side Wall Type Models: RPK-1.0FSNSM2 and RPK-1.5FSNSM2 Model: RPK-2.0FSNSM2 Min. 100 Min. 100 Min. 100 Min. 100 Min. 1000 Unit: mm Min. 1000 Min. 150 Min. 150 Unit: mm Unit: mm Min. 100 Min. 200 Min. 1000 Min. 100 Models: RPK-2.5FSNSM2, RPK-3.0FSNSM2 and RPK-4.0FSNSM2 1-58 SELECTION DATA Floor Type Models: RPF-1.0FSN2E and RPF-1.5FSN2E Min. 1000 Ceiling Wall 630 Wall Floor 1170 (1.5HP) 1045 (1.0HP) Min. 300 Min. 300 Floor Concealed Type Models: RPFI-1.0FSN2E and RPFI-1.5FSN2E Ceiling 620 Front Air Outlet 640 Upward Air Outlet Short Flexible Duct Min. 1000 Ceiling Min. 240 Floor Min. Min. 240 901 (1.5HP) 240 776 (1.0HP) Floor 901 (1.5HP) 776 (1.0HP) Min. 240 Service Space Ceiling Type Models: RPC-2.0FSN2, RPC-2.5FSN2, RPC-3.0FSN2, RPC-4.0FSN2 and RPC-5.0FSN2 Min. 500 (mm) Min. 300 Min. 40 Min. 8 Min. 400 150 to 250 EA RA OA SA 450 Min. 600 Min. 200 Total Heat Exchangers Models: KPI-2521, KPI-5021, KPI-8021 and KPI-10021 Service Access Door (450 x 450) 450 1-59 SELECTION DATA 4.3 Sensible Heat Factor (SHF) The sensible heat factor of indoor units at each fan speed (Hi, Me, Lo) based on the JIS Standard B8616, is given in the below. Model RPI-0.8FSN2 RPI-1.0FSN2 RPI-1.5FSN2 RPI-2.0FSN2 RPI-2.5FSN2 RPI-3.0FSN2 RPI-4.0FSN2 RPI-5.0FSN2 RPI-8FSN RPI-10FSN RCI-1.0FSN2 RCI-1.5FSN2 RCI-2.0FSN2 RCI-2.5FSN2 RCI-3.0FSN2 RCI-4.0FSN2 RCI-5.0FSN2 RCD-1.0FSN2 RCD-1.5FSN2 RCD-2.0FSN2 RCD-2.5FSN2 RCD-3.0FSN2 RCD-4.0FSN2 RCD-5.0FSN2 RPK-1.0FSNSM2 RPK-1.5FSNSM2 RPK-2.0FSNSM2 RPK-2.5FSNSM2 RPK-3.0FSNSM2 RPK-4.0FSNSM2 RPF-1.0FSN2E RPF-1.5FSN2E RPFI-1.0FSN2E RPFI-1.5FSN2E RPC-2.0FSN2 RPC-2.5FSN2 RPC-3.0FSN2 RPC-4.0FSN2 RPC-5.0FSN2 Hi 0.73 0.73 0.74 0.73 0.70 0.71 0.69 0.73 0.72 0.71 0.85 0.81 0.74 0.74 0.74 0.72 0.70 0.81 0.73 0.74 0.70 0.69 0.70 0.69 0.78 0.73 0.69 0.71 0.74 0.71 0.73 0.73 0.73 0.73 0.74 0.72 0.71 0.73 0.70 SHF Me 0.71 0.71 0.71 0.70 0.68 0.67 0.67 0.68 0.83 0.77 0.71 0.70 0.67 0.71 0.66 0.76 0.70 0.70 0.69 0.69 0.68 0.67 0.74 0.72 0.68 0.69 0.70 0.69 0.69 0.69 0.69 0.69 0.71 0.69 0.68 0.70 0.68 Lo 0.68 0.68 0.67 0.66 0.66 0.63 0.64 0.65 0.81 0.72 0.69 0.68 0.65 0.68 0.64 0.75 0.68 0.67 0.67 0.67 0.66 0.65 0.71 0.70 0.67 0.68 0.69 0.68 0.65 0.65 0.65 0.65 0.68 0.67 0.66 0.68 0.66 1-62 SELECTION DATA 4.4 Fan Performance RPI-0.8FSN2, 1.0FSN2 RPI-1.5FSN2 : Normal Mode (at shipping) : High Static Pressure Mode : Low Staitc Pressue Mode 140 140 130 130 120 120 110 110 100 90 80 Hi 70 Me 60 50 Lo Hi Me 40 Lo 30 90 Hi 80 70 60 Me 50 40 Hi Me Lo Hi Lo Hi Me 20 Lo Lo 10 10 0 0 2 3 4 5 6 7 8 9 10 11 5 6 7 8 9 10 11 12 13 14 AIR VOLUME (m3/min) AIR VOLUME (m3/min) The setting of Normal, High Static Pressure,and Low Static Pressure Mode can be changed by Remote Control Switch. The setting of Normal, High Static Pressure,and Low Static Pressure Mode can be changed by Remote Control Switch. RPI-2.0FSN2 RPI-2.5FSN2 : Normal Mode (at shipping) : High Static Pressure Mode : Low Staitc Pressue Mode 150 140 140 130 130 120 120 110 110 100 90 Hi 80 70 60 Me Hi 50 40 Lo Me 30 90 Hi 80 70 60 Me Hi 50 40 Me Lo Hi Me Lo Me 20 100 30 Hi Lo : Normal Mode (at shipping) : High Static Pressure Mode : Low Staitc Pressue Mode 150 EXTERNAL STATIC PRESSURE (Pa) EXTERNAL STATIC PRESSURE (Pa) 100 30 Me 20 : Normal Mode (at shipping) : High Static Pressure Mode : Low Staitc Pressue Mode 150 EXTERNAL STATIC PRESSURE (Pa) EXTERNAL STATIC PRESSURE (Pa) 150 20 Lo Lo 10 10 0 0 7 8 9 10 11 12 13 14 15 16 8 9 10 11 12 13 14 15 16 18 AIR VOLUME (m3/min) AIR VOLUME (m3/min) The setting of Normal, High Static Pressure,and Low Static Pressure Mode can be changed by Remote Control Switch. The setting of Normal, High Static Pressure,and Low Static Pressure Mode can be changed by Remote Control Switch. 1-63 SELECTION DATA PI-3.0FSN2 RPI-4.0FSN2 320 320 : Normal Mode (at shipping) : High Static Pressure Mode : Low Staitc Pressue Mode 280 280 260 260 240 240 220 220 200 180 Hi 160 140 Me Hi 120 Me 100 Lo 80 Lo : Normal Mode (at shipping) : High Static Pressure Mode : Low Staitc Pressue Mode 300 EXTERNAL STATIC PRESSURE (Pa) EXTERNAL STATIC PRESSURE (Pa) 300 Hi 200 180 Hi 160 140 Hi 120 Me 100 Me Lo 80 60 60 40 40 Lo Lo 20 20 0 Hi Me Lo Me 0 11 12 13 14 15 16 17 18 19 20 13 15 17 19 21 23 25 27 29 31 AIR VOLUME (m3/min) AIR VOLUME (m3/min) The setting of Normal, High Static Pressure, and Low Static Pressure Mode can be changed by Remote Control Switch. The setting of Normal, High Static Pressure,and Low Static Pressure Mode can be changed by Remote Control Switch. PI-5.0FSN2 320 : Normal Mode (at shipping) : High Static Pressure Mode : Low Staitc Pressue Mode 300 280 260 EXTERNAL STATIC PRESSURE (Pa) 240 220 200 180 Hi 160 140 Hi 120 Me 100 Lo 80 60 Me Hi Lo Me 40 Lo 20 0 23 25 27 29 31 33 35 37 39 41 AIR VOLUME (m3/min) The setting of Normal, High Static Pressure,and Low Static Pressure Mode can be changed by Remote Control Switch. 1-64 SELECTION DATA RPI-8FSN High Static Pressure Setting: 220Pa (at shipping) Low Static Pressure Setting: 110Pa High Static Pressure Setting: 260Pa (at shipping) Low Static Pressure Setting: 130Pa 380V/50Hz 380V/60Hz 415V/50Hz 350 100 50 250 200 150 Upper Limit of Air Volume 150 Upper Limit of Air Volume 200 300 Lower Limit of Air Volume 250 Lower Limit of Air Volume EXTERNAL STATIC PRESSURE (Pa) 300 EXTERNAL STATIC PRESSURE (Pa) 350 100 50 0 40 45 50 55 65 60 70 0 75 40 45 3 50 55 60 65 70 75 AIR VOLUME (m3/min) AIR VOLUME (m /min) The setting of High Static Pressure and Low Static Pressure Mode can be changed by changing the position of the connector inside of the indoor unit. The setting of High Static Pressure and Low Static Pressure Mode can be changed by changing the position of the connector inside of the indoor unit. RPI-10FSN High Static Pressure Setting: 220Pa (at shipping) Low Static Pressure Setting: 110Pa 380V/50Hz 380V/60Hz 350 High Static Pressure Setting: 260Pa (at shipping) Low Static Pressure Setting: 130Pa 415V/50Hz 350 100 50 0 200 150 Upper Limit of Air Volume 150 250 Lower Limit of Air Volume 200 Upper Limit of Air Volume 250 EXTERNAL STATIC PRESSURE (Pa) 300 Lower Limit of Air Volume EXTERNAL STATIC PRESSURE (Pa) 300 100 50 55 60 65 70 80 75 85 90 3 AIR VOLUME (m /min) The setting of High Static Pressure and Low Static Pressure Mode can be changed by changing the position of the connector inside of the indoor unit. 0 55 60 65 70 75 80 85 90 AIR VOLUME (m3/min) The setting of High Static Pressure and Low Static Pressure Mode can be changed by changing the position of the connector inside of the indoor unit. 1-65 SELECTION DATA KPI-2521 Fan Performance and Heat Exchange Efficiency Curve Model:KPI-2521 Fan Performance and Heat Exchange Efficiency Curve Model: KPI-2521 (50Hz) Heat Exchange Efficiency (%) 70 60 Total Heat Exchanger Efficiency (Heating Operation) Total Heat Exchanger Efficiency (Cooling Operation) 250 External Static Pressure (Pa) 70 60 50 150 Duct Length 200 150 Hi 30m Me 100 20m Lo 50 10m 50 100 150 200 250 300 350 Total Heat Exchange Efficiency (Heating Operation) Total Heat Exchange Efficiency (Cooling Operation) 250 150 Duct Length 200 40m 0 0 Temperature Exchange Efficiency 80 External Static Pressure (Pa) Heat Exchange Efficiency (%) Temperature Exchange Efficiency 80 50 (60Hz) 90 90 40m Hi 150 30m Me 100 20m Lo 50 0 0 10m 50 100 150 200 250 300 350 400 400 3 Air Volume (m /h) 3 Air Volume (m /h) KPI-5021 Model: KPI-5021 Fan Performance and Heat Exchange Efficiency Curve Model: KPI-5021 (50Hz) 90 Total Heat Exchanger Efficiency (Heating Operation) 80 70 Total Heat Exchanger Efficiency (Heating Operation) 60 300 Total Heat Exchanger Efficiency (Cooling Operation) 50 250 200 Duct Length 200 Hi 60m 50m 150 Me 40m Lo 100 30m 20m 50 10m 0 0 100 200 300 400 Air Volume (m3/h) 500 600 700 (60Hz) 90 Temperature Exchange Efficiency 80 400 70 350 60 300 Total Heat Exchange Efficiency (Cooling Operation) 50 250 200 Duct Length Hi External Static Pressure (Pa) Heat Exchange Efficiency (%) Temperature Exchange Efficiency External Static Pressure (Pa) Heat Exchange Efficiency (%) Fan Performance and Heat Exchange Efficiency Curve 200 60m 50m 150 Me 40m Lo 100 30m 20m 50 10m 0 0 100 200 300 400 500 600 700 Air Volume (m3/h) 1-66 SELECTION DATA KPI-8021 Model:KPI-8021 Fan Performance and Heat Exchange Efficiency Curve (50Hz) Model: KPI-8021 90 Temperature Exchange Efficiency 600 70 500 Temperature Exchange Efficiency Heat Exchange Efficiency (%) 80 Total Heat Exchanger Efficiency (Heating Operation) 60 400 Total Heat Exchanger Efficiency (Cooling Operation) External Static Pressure (Pa) 50 (60Hz) 90 300 250 Duct Length Hi Lo 100m 80m Me 60m 40m 20m 0 0 200 400 600 800 1000 600 70 500 Total Heat Exchange Efficiency (Heating Operation) 60 1200 400 Total Heat Exchange Efficiency (Cooling Operation) 50 200 100 80 External Static Pressure (Pa) Heat Exchange Efficiency (%) Fan Performance and Heat Exchange Efficiency Curve 300 250 Duct Length Hi Lo 100m 200 80m 60m Me 100 40m 20m 0 0 200 400 600 800 1000 1200 Air Volume (m3/h) 3 Air Volume (m /h) Do not use the condition that External Static Pressure is under than 29Pa. Do not use the condition that the External Static Pressure is under than 29Pa. KPI-10021 Model:KPI-10021 Fan Performance and Heat Exchange Efficiency Curve (50Hz) Model: KPI-10021 (60Hz) 90 700 90 700 80 600 70 500 Total Heat Exchanger Efficiency (Heating Operation) 60 400 Total Heat Exchanger Efficiency (Cooling Operation) 250 Duct Length 50 300 Heat Exchange Efficiency (%) Temperature Exchange Efficiency Temperature Exchange Efficiency 80 600 70 500 Total Heat Exchange Efficiency (Heating Operation) 60 400 Total Heat Exchange Efficiency (Cooling Operation) 250 Duct Length Hi 100m 50 300 Hi Lo 80m 200 60m Me 40m 100 20m 0 0 200 400 600 800 1000 1200 3 Air Volume (m /h) Do not use the condition that the External Static Pressure is under than 49Pa. 1400 External Static Pressure (Pa) External Static Pressure (Pa) Heat Exchange Efficiency (%) Fan Performance and Heat Exchange Efficiency Curve 100m Me 80m Lo 200 60m 40m 100 20m 0 0 200 400 600 800 1000 1200 1400 Air Volume (m3/h) Do not use the condition that External Static Pressure is under than 49Pa. 1-67 ELECTRICAL DATA 5. Electrical Data < 50 Hz > Indoor Unit Model In-the-Ceiling Type 4-Way Cassette Type 2-Way Cassette Type Wall Type Floor Type Floor Concealed Type Ceiling Type RPI-0.8FSN2 RPI-1.0FSN2 RPI-1.5FSN2 RPI-2.0FSN2 RPI-2.5FSN2 RPI-3.0FSN2 RPI-4.0FSN2 RPI-5.0FSN2 RPI-8FSN RPI-10FSN RCI-1.0FSN2 RCI-1.5FSN2 RCI-2.0FSN2 RCI-2.5FSN2 RCI-3.0FSN2 RCI-4.0FSN2 RCI-5.0FSN2 RCD-1.0FSN2 RCD-1.5FSN2 RCD-2.0FSN2 RCD-2.5FSN2 RCD-3.0FSN2 RCD-4.0FSN2 RCD-5.0FSN2 RPK-1.0FSNSM2 RPK-1.5FSNSM2 RPK-2.0FSNSM2 RPK-2.5FSNSM2 RPK-3.0FSNSM2 RPK-4.0FSNSM2 RPF-1.0FSN2E RPF-1.5FSN2E RPFI-1.0FSN2E RPFI-1.5FSN2E RPC-2.0FSN2 RPC-2.5FSN2 RPC-3.0FSN2 RPC-4.0FSN2 RPC-5.0FSN2 Unit Main Power Applicable Voltage Indoor Fan Motor VOL PH HZ Maximum Minimum PH 220/240 1 50 264 198 1 380/415 3 50 456 342 3 220/240 1 50 264 198 1 220/240 1 50 264 198 1 220/240 1 50 264 198 1 220/240 1 50 264 198 1 220/240 1 50 264 198 1 220/240 1 50 264 198 1 RNC 0.5/0.5 0.5/0.5 0.7/0.7 0.7/0.7 0.7/0.7 0.9/0.9 1.3/1.4 1.9/2.0 1.6/1.6 2.0/2.0 0.2/0.2 0.2/0.2 0.2/0.2 0.3/0.3 0.4/0.3 0.7/0.6 0.8/0.8 0.2/0.2 0.3/0.4 0.3/0.4 0.4/0.5 0.5/0.6 0.6/0.6 0.8/0.9 0.2/0.2 0.3/0.3 0.3/0.3 0.3/0.3 0.3/0.3 0.5/0.5 0.2/0.2 0.2/0.2 0.2/0.2 0.2/0.2 0.4/0.4 0.5/0.5 0.5/0.5 0.8/1.0 0.9/1.0 IPT 0.10/0.11 0.10/0.11 0.14/0.15 0.14/0.15 0.14/0.15 0.19/0.20 0.28/0.31 0.40/0.46 0.99/0.99 1.23/1.23 0.03/0.03 0.03/0.03 0.04/0.04 0.06/0.06 0.07/0.07 0.13/0.13 0.16/0.16 0.05/0.06 0.07/0.08 0.07/0.08 0.09/0.11 0.11/0.13 0.12/0.14 0.18/0.20 0.03/0.03 0.03/0.03 0.03/0.03 0.04/0.04 0.04/0.04 0.06/0.06 0.04/0.04 0.05/0.05 0.04/0.04 0.05/0.05 0.08/0.09 0.09/0.12 0.09/0.12 0.17/0.22 0.18/0.22 Total Heat Exchangers Model Total Heat Exchangers VOL: PH: HZ: KPI-2521 KPI-5021 KPI-8021 KPI-10021 Unit Main Power Applicable Voltage Indoor Fan Motor VOL PH HZ Max. Min. PH 220/240 1 50 264 198 1 Rated Unit Power Supply Voltage (Plated)(V) Phase () Frequency (Hz) RNC: IPT: RNC 0.5/0.6 1.0/1.0 1.8/1.8 2.3/2.3 IPT 0.11/0.13 0.21/0.23 0.39/0.42 0.50/0.53 Running Current (A) Input (kW) 1-72 ELECTRICAL DATA < 60 Hz > Indoor Unit Model In-the-Ceiling Type 4-Way Cassette Type 2-Way Cassette Type Wall Type Floor Type Floor Concealed Type Ceiling Type RPI-0.8FSN2 RPI-1.0FSN2 RPI-1.5FSN2 RPI-2.0FSN2 RPI-2.5FSN2 RPI-3.0FSN2 RPI-4.0FSN2 RPI-5.0FSN2 RPI-8FSN RPI-10FSN RCI-1.0FSN2 RCI-1.5FSN2 RCI-2.0FSN2 RCI-2.5FSN2 RCI-3.0FSN2 RCI-4.0FSN2 RCI-5.0FSN2 RCD-1.0FSN2 RCD-1.5FSN2 RCD-2.0FSN2 RCD-2.5FSN2 RCD-3.0FSN2 RCD-4.0FSN2 RCD-5.0FSN2 RPK-1.0FSNSM2 RPK-1.5FSNSM2 RPK-2.0FSNSM2 RPK-2.5FSNSM2 RPK-3.0FSNSM2 RPK-4.0FSNSM2 RPF-1.0FSN2E RPF-1.5FSN2E RPFI-1.0FSN2E RPFI-1.5FSN2E RPC-2.0FSN2 RPC-2.5FSN2 RPC-3.0FSN2 RPC-4.0FSN2 RPC-5.0FSN2 Unit Main Power Applicable Voltage Indoor Fan Motor VOL PH HZ Maximum Minimum PH 220 1 60 242 198 1 380 3 60 418 342 3 220 1 60 242 198 1 220 1 60 242 198 1 220 1 60 242 198 1 220 1 60 242 198 1 220 1 60 242 198 1 220 1 60 242 198 1 RNC 0.6 0.6 0.8 0.8 0.8 1.2 1.5 2.3 1.9 2.3 0.2 0.2 0.2 0.3 0.4 0.7 0.8 0.2 0.4 0.4 0.5 0.6 0.7 1.2 0.2 0.3 0.3 0.3 0.3 0.5 0.2 0.2 0.2 0.2 0.4 0.7 0.7 0.9 0.9 IPT 0.12 0.12 0.16 0.16 0.16 0.26 0.32 0.49 1.14 1.41 0.03 0.03 0.04 0.06 0.07 0.13 0.16 0.05 0.08 0.08 0.11 0.13 0.14 0.24 0.03 0.03 0.03 0.04 0.04 0.06 0.04 0.05 0.04 0.05 0.09 0.15 0.15 0.20 0.20 Total Heat Exchangers Model Total Heat Exchangers VOL: PH: HZ: KPI-2521 KPI-5021 KPI-8021 KPI-10021 Unit Main Power Applicable Voltage Indoor Fan Motor VOL PH HZ Max. Min. PH 220 1 60 242 198 1 Rated Unit Power Supply Voltage (Plated)(V) Phase () Frequency (Hz) RNC: IPT: RNC 0.6 1.2 2.1 2.8 IPT 0.13 0.26 0.46 0.60 Running Current (A) Input (kW) 1-73 SOUND DATA 6. Sound Data In-the-Ceiling Type Model: RPI-0.8FSN2 Model: RPI-1.0FSN2 Power Supply: 220V, 50/60Hz Power Supply: 220V, 50/60Hz Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit 90 90 Noise Criteria Curve Octave Sound Pressure Level (dB: Overall C Scale) Octave Sound Pressure Level (dB: Overall C Scale) Noise Criteria Curve 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 Hi 30 NC-30 Me Lo 20 Approximate Threshold of Hearing for Continuous Noise NC-2 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 Hi 30 NC-30 Me Lo 20 Approximate Threshold of Hearing for Continuous Noise 0 NC-2 0 10 10 63 125 250 500 1000 2000 4000 63 8000 Central Frequency (Cycle per Second) Model: RPI-1.5FSN2 125 250 500 Power Supply: 220V, 50/60Hz Model: RPI-2.0FSN2 Measurement Point: 1.5 Meters Beneath the Unit 2000 4000 8000 Power Supply: 220V, 50/60Hz Measurement Point: 1.5 Meters Beneath the Unit 90 90 Noise Criteria Curve 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 Hi 30 NC-30 Me Lo 20 Approximate Threshold of Hearing for Continuous Noise Noise Criteria Curve Octave Sound Pressure Level (dB: Overall C Scale) Octave Sound Pressure Level (dB: Overall C Scale) 1000 Central Frequency (Cycle per Second) 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 Hi 30 NC-30 Me Lo 20 Approximate Threshold of Hearing for Continuous Noise NC-2 0 10 NC-20 10 63 125 250 500 1000 2000 4000 Central Frequency (Cycle per Second) 8000 63 125 250 500 1000 2000 4000 8000 Central Frequency (Cycle per Second) 1-74 SOUND DATA Model: RPI-2.5FSN2 Model: RPI-3.0FSN2 Power Supply: 220V, 50/60Hz Measurement Point: 1.5 Meters Beneath the Unit Power Supply: 220V, 50/60Hz Measurement Point: 1.5 Meters Beneath the Unit 90 90 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 Hi 30 NC-30 Me Lo Noise Criteria Curve Octave Sound Pressure Level (dB: Overall C Scale) Octave Sound Pressure Level (dB: Overall C Scale) Noise Criteria Curve 80 70 NC-70 60 NC-6 0 50 NC-5 0 Hi 40 Me NC-4 0 NC-3 0 30 Lo 20 Approximate Threshold of Hearing for Continuous Noise 20 Approximate Threshold of Hearing for Continuous Noise NC-2 0 10 63 125 250 500 1000 2000 4000 10 8000 63 Central Frequency (Cycle per Second) Model: RPI-4.0FSN2 125 NC- 20 250 500 Power Supply: 220V, 50-60Hz Model: RPI-5.0FSN2 Measurement Point: 1.5 Meters Beneath the Unit 4000 8000 Power Supply: 220V, 50/60Hz 90 Noise Criteria Curve Octave Sound Pressure Level (dB: Overall C Scale) Noise Criteria Curve 80 70 NC-70 60 NC-60 50 NC-50 Hi 40 Me 30 NC-40 NC-30 80 70 NC-70 60 NC-60 50 NC-50 Hi Me 40 NC-40 30 NC-30 Lo 20 2000 Measurement Point: 1.5 Meters Beneath the Unit 90 Octave Sound Pressure Level (dB: Overall C Scale) 1000 Central Frequency (Cycle per Second) Approximate Threshold of Hearing for Continuous Noise Lo 20 NC-2 0 Approximate Threshold of Hearing for Continuous Noise NC-2 0 10 10 63 125 250 500 1000 2000 4000 Central Frequency (Cycle per Second) 8000 63 125 250 500 1000 2000 4000 8000 Central Frequency (Cycle per Second) 1-75 SOUND DATA Model: RPI-8FSN Model: RPI-8FSN Power Supply: 380V, 50/60Hz 220Pa 110Pa 90 Power Supply: 415V, 50Hz Measurement Point: 1.5 Meter Beneath the Unit Measurement Point: 1.5 Meter Beneath the Unit 260Pa 130Pa 90 Noise Criteria Curve Octave Sound Pressure Level (dB: Overall C Scale) Octave Sound Pressure Level (dB: Overall C Scale) Noise Criteria Curve 80 70 NC-70 60 NC-6 0 50 NC-5 0 40 NC-4 0 30 NC-3 0 20 10 Approximate Threshold of Hearing for Continuous Noise 63 125 NC- 20 250 500 1000 2000 4000 80 70 NC-70 60 NC-6 0 50 NC-5 0 40 NC-4 0 30 NC-3 0 20 Approximate Threshold of Hearing for Continuous Noise NC- 10 8000 63 500 Model: RPI-10FSN Power Supply: 380V, 50/60Hz Measurement Point: 1.5 Meter Beneath the Unit 60 NC-6 0 50 NC-5 0 40 NC-4 0 30 NC-3 0 20 Approximate Threshold of Hearing for Continuous Noise NC- 10 63 125 20 250 500 1000 2000 4000 Central Frequency (Cycle per Second) 4000 8000 260Pa 130Pa 90 Noise Criteria Curve Octave Sound Pressure Level (dB: Overall C Scale) Octave Sound Pressure Level (dB: Overall C Scale) 80 NC-70 2000 Power Supply: 415V, 50Hz Noise Criteria Curve 70 1000 Measurement Point: 1.5 Meter Beneath the Unit 220Pa 110Pa 90 250 Central Frequency (Cycle per Second) Central Frequency (Cycle per Second) Model: RPI-10FSN 125 20 8000 80 70 NC-70 60 NC-6 0 50 NC-5 0 40 NC-4 0 30 NC-3 0 20 Approximate Threshold of Hearing for Continuous Noise NC- 10 63 125 20 250 500 1000 2000 4000 8000 Central Frequency (Cycle per Second) NOTES: 1. The sound pressure level is based on following conditions, 1.5 Meter Beneath the Unit. 2. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field. 1-76 SOUND DATA 4-Way Cassette Type Model: RCI-1.0FSN2 Model: RCI-1.5FSN2 Power Supply: 220-240V/220V, 50/60Hz Measurement Point: 1.5 Meters Beneath the Unit Power Supply: 220-240V/220V, 50/60Hz Measurement Point: 1.5 Meters Beneath the Unit 90 90 80 70 NC-70 60 NC-6 0 50 NC-5 0 NC-4 0 40 Hi 30 Me Noise Criteria Curve Octave Sound Pressure Level (dB: Overall C Scale) Octave Sound Pressure Level (dB: Overall C Scale) Noise Criteria Curve NC-3 0 80 70 NC-70 60 NC-6 0 50 NC-5 0 NC-4 0 40 Hi Me NC-3 0 30 Lo 20 10 Approximate Threshold of Hearing for Continuous Noise 63 125 20 Approximate Threshold of Hearing for Continuous Noise NC- 20 250 500 1000 2000 4000 10 8000 63 Central Frequency (Cycle per Second) Model: RCI-2.0FSN2 125 NC- 20 Lo 250 500 Model: RCI-2.5FSN2 Power Supply: 220-240V/220V, 50/60Hz Measurement Point: 1.5 Meters Beneath the Unit 90 Octave Sound Pressure Level (dB: Overall C Scale) Octave Sound Pressure Level (dB: Overall C Scale) 80 60 NC-6 0 50 NC-5 0 NC-4 0 40 30 NC-3 0 Hi 4000 8000 Power Supply: 220-240V/220V, 50/60Hz Noise Criteria Curve Noise Criteria Curve NC-70 2000 Measurement Point: 1.5 Meters Beneath the Unit 90 70 1000 Central Frequency (Cycle per Second) 80 70 NC-70 60 NC-6 0 50 NC-5 0 Hi NC-4 0 40 Me NC-3 0 30 Me 20 Approximate Threshold of Hearing for Continuous Noise 10 63 125 NC- Lo 250 20 20 500 1000 2000 4000 Central Frequency (Cycle per Second) 8000 10 Approximate Threshold of Hearing for Continuous Noise 63 125 NC- 20 Lo 250 500 1000 2000 4000 8000 Central Frequency (Cycle per Second) 1-77 SOUND DATA Model: RCI-3.0FSN2 Model: RCI-4.0FSN2 Power Supply: 220-240V/220V, 50/60Hz Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit 90 90 80 70 NC-70 60 NC-6 0 50 NC-5 0 Hi NC-4 0 40 Me NC-3 0 30 20 Approximate Threshold of Hearing for Continuous Noise 63 125 Noise Criteria Curve Octave Sound Pressure Level (dB: Overall C Scale) Octave Sound Pressure Level (dB: Overall C Scale) Noise Criteria Curve 10 Power Supply: 220-240V/220V, 50/60Hz NC- 80 70 NC-70 60 NC-6 0 Hi 40 Lo 250 500 1000 2000 4000 8000 Central Frequency (Cycle per Second) Model: RCI-5.0FSN2 Me 10 NC-4 0 NC-3 0 30 20 20 NC-5 0 50 Approximate Threshold of Hearing for Continuous Noise 63 125 NC- 20 Lo 250 500 1000 2000 4000 8000 Central Frequency (Cycle per Second) Power Supply: 220-240V/220V, 50/60Hz Measurement Point: 1.5 Meters Beneath the Unit 90 Octave Sound Pressure Level (dB: Overall C Scale) Noise Criteria Curve 80 70 NC-70 60 NC-6 0 Hi NC-5 0 50 Me 40 NC-4 30 NC-3 0 0 Lo 20 Approximate Threshold of Hearing for Continuous Noise 10 63 125 NC- 20 250 500 1000 2000 4000 8000 Central Frequency (Cycle per Second) 1-78 SOUND DATA 2-Way Cassette Type Model: RCD-1.5FSN2 Power Supply: 220V, 50/60Hz Model: RCD-1.0FSN2 Measurement Point: 1.5 Meters Beneath the Unit Power Supply: 220V, 50/60Hz Measurement Point: 1.5 Meters Beneath the Unit 90 90 80 70 NC-70 60 NC-60 50 NC-50 Hi 40 NC-40 Me 30 NC-30 20 Approximate Threshold of Hearing for Continuous Noise Noise Criteria Curve Octave Sound Pressure Level (dB: Overall C Scale) Octave Sound Pressure Level (dB: Overall C Scale) Noise Criteria Curve 70 NC-70 60 NC-60 50 NC-50 Hi 40 0 10 30 NC-30 NC-2 0 Lo 10 63 125 250 500 1000 2000 4000 8000 63 Central Frequency (Cycle per Second) Model: RCD-2.0FSN2 125 250 500 1000 2000 4000 8000 Central Frequency (Cycle per Second) Power Supply: 220V, 50/60Hz Model: RCD-2.5FSN2, RCD-3.0FSN2 Power Supply: 220V, 50/60Hz Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit 90 90 80 70 NC-70 60 NC-60 50 NC-50 Hi 40 NC-40 Me 30 NC-30 20 Approximate Threshold of Hearing for Continuous Noise 80 70 NC-70 60 NC-60 50 NC-50 Hi Me 40 0 NC-40 30 NC-30 20 Approximate Threshold of Hearing for Continuous Noise NC-2 Lo Noise Criteria Curve Octave Sound Pressure Level (dB: Overall C Scale) Noise Criteria Curve Octave Sound Pressure Level (dB: Overall C Scale) NC-40 Me 20 Approximate Threshold of Hearing for Continuous Noise NC-2 Lo 80 NC-2 0 Lo 10 10 63 125 250 500 1000 2000 4000 Central Frequency (Cycle per Second) 8000 63 125 250 500 1000 2000 4000 8000 Central Frequency (Cycle per Second) 1-79 SOUND DATA Model: RCD-4.0FSN2 Model: RCD-5.0FSN2 Power Supply: 220V, 50/60Hz Power Supply: 220V, 50/60Hz Measurement Point: 1.5 Meters Beneath the Unit Measurement Point: 1.5 Meters Beneath the Unit 90 90 80 70 NC-70 60 NC-60 50 NC-50 Hi Me 40 NC-40 30 Noise Criteria Curve Octave Sound Pressure Level (dB: Overall C Scale) Octave Sound Pressure Level (dB: Overall C Scale) Noise Criteria Curve NC-30 80 70 NC-70 60 NC-60 Hi 50 NC-50 Me 40 NC-40 30 NC-30 Lo Lo 20 Approximate Threshold of Hearing for Continuous Noise 10 63 125 20 Approximate Threshold of Hearing for Continuous Noise NC-2 0 NC-2 0 10 250 500 1000 2000 4000 Central Frequency (Cycle per Second) 8000 63 125 250 500 1000 2000 4000 8000 Central Frequency (Cycle per Second) 1-80 SOUND DATA Wall Type 90 Model: RPK-1.0FSNSM2 Power Supply: 220V, 50/60Hz Measurement Point: 1 Meter Beneath the Unit and 1 Meter From Discharge Grille Model: RPK-1.5FSNSM2 Power Supply: 220V, 50/60Hz 90 Measurement Point: 1 Meter Beneath the Unit and 1 Meter From Discharge Grille 80 70 NC-70 60 NC-6 0 50 NC-5 0 40 NC-4 0 Hi NC-3 0 30 Lo 20 10 Me NC- Approximate Threshold of Hearing for Continuous Noise 63 125 Noise Criteria Curve Octave Sound Pressure Level (dB: Overall C Scale) Octave Sound Pressure Level (dB: Overall C Scale) Noise Criteria Curve 20 250 500 1000 80 70 NC-70 60 NC-6 0 50 NC-5 0 4000 NC-3 0 Approximate Threshold of Hearing for Continuous Noise 63 Central Frequency (Cycle per Second) 125 NC- 20 250 500 90 90 NC-6 0 50 NC-5 0 Hi 40 Me NC-4 0 NC-3 0 30 Lo 20 Approximate Threshold of Hearing for Continuous Noise 10 63 125 20 500 1000 2000 4000 Central Frequency (Cycle per Second) 8000 80 70 NC-70 60 NC-6 0 50 NC-5 0 Hi NC-4 0 40 Me 30 NC-3 0 Lo Approximate 20 Threshold of Hearing for Continuous Noise NC- 250 4000 Noise Criteria Curve Octave Sound Pressure Level (dB: Overall C Scale) Octave Sound Pressure Level (dB: Overall C Scale) 80 60 2000 Model: RPK-2.5 FSNSM2, RPK-3.0FSNSM2 Power Supply: 220V, 50/60Hz Measurement Point: 1 Meter Beneath the Unit and 1 Meter From Discharge Grille Noise Criteria Curve NC-70 1000 Central Frequency (Cycle per Second) Model: RPK-2.0FSNSM2 Power Supply: 220V, 50/60Hz Measurement Point: 1 Meter Beneath the Unit and 1 Meter From Discharge Grille 70 NC-4 0 Lo 10 8000 Hi 30 20 2000 Me 40 8000 10 63 125 NC- 20 250 500 1000 2000 4000 8000 Central Frequency (Cycle per Second) 1-81 SOUND DATA 90 Model: RPK-4.0FSNSM2 Power Supply: 220V, 50/60Hz Measurement Point: 1 Meter Beneath the Unit and 1 Meter From Discharge Grille Octave Sound Pressure Level (dB: Overall C Scale) Noise Criteria Curve 80 70 NC-70 60 NC-6 0 Hi 50 NC-5 0 NC-4 0 40 Me NC-3 0 30 20 10 Lo Approximate Threshold of Hearing for Continuous Noise 63 125 NC- 20 250 500 1000 2000 4000 8000 Central Frequency (Cycle per Second) 1-82 SOUND DATA Floor Type Model: RPF-1.0FSN2E Power Supply: 220V, 50/60Hz Model: RPF-1.5FSN2E Measurement Point: 1.5 Meter from the Unit 1.5 Meter from Floor Level Noise Criteria Curve Noise Criteria Curve Hi/Me/Lo: 35/32/29 dBA Hi/Me/Lo: 38/35/31 dBA 80 Octave Sound Pressure Level (dB: Overall C Scale) 80 Octave Sound Pressure Level (dB: Overall C Scale) Power Supply: 220V, 50/60Hz Measurement Point: 1.5 Meter from the Unit 1.5 Meter from Floor Level 70 60 50 40 30 70 60 50 40 30 20 20 Approximate Threshold of Hearing for Continuous Noise 10 63 125 250 Approximate Threshold of Hearing for Continuous Noise 10 500 1000 2000 4000 63 8000 Central Frequency (Cycle per Second) 125 250 500 1000 2000 4000 8000 Central Frequency (Cycle per Second) Floor Concealed Type Model: RPFI-1.0FSN2E Power Supply: 220V, 50/60Hz Model: RPFI-1.5FSN2E Power Supply: 220V, 50/60Hz Measurement Point: 1.5 Meter from the Unit 1.5 Meter from Floor Level Noise Criteria Curve Noise Criteria Curve Hi/Me/Lo: 35/32/29 dBA Hi/Me/Lo: 38/35/31 dBA 80 80 Octave Sound Pressure Level (dB: Overall C Scale) Octave Sound Pressure Level (dB: Overall C Scale) Measurement Point: 1.5 Meter from the Unit 1.5 Meter from Floor Level 70 60 50 40 30 20 70 60 50 40 30 20 Approximate Threshold of Hearing for Continuous Noise 10 63 125 250 Approximate Threshold of Hearing for Continuous Noise 10 500 1000 2000 4000 Central Frequency (Cycle per Second) 8000 63 125 250 500 1000 2000 4000 8000 Central Frequency (Cycle per Second) 1-83 SOUND DATA Ceiling Type 90 Power Supply: 220V, 50/60Hz Model: RPC-2.0FSN2 Measurement Point: 1 Meter Beneath the Unit and 1 Meter From Discharge Grille Model: RPC-2.5FSN2, RPC-3.0FSN2 90 70 NC-70 60 NC-60 50 NC-50 40 NC-40 Hi 30 Noise Criteria Curve Octave Sound Pressure Level (dB: Overall C Scale) Octave Sound Pressure Level (dB: Overall C Scale) Noise Criteria Curve 80 NC-30 Me 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 Hi 30 NC-30 Me Lo Lo 20 Approximate Threshold of Hearing for Continuous Noise 20 Approximate Threshold of Hearing for Continuous Noise NC-2 0 NC-2 0 10 10 63 125 250 500 1000 2000 4000 63 8000 Central Frequency (Cycle per Second) 90 125 250 500 Power Supply: 220V, 50/60Hz Model: RPC-4.0FSN2 Measurement Point: 1 Meter Beneath the Unit and 1 Meter From Discharge Grille 90 NC-70 60 NC-60 50 NC-50 Hi 40 NC-40 30 2000 4000 8000 Power Supply: 220V, 50/60Hz Model: RPC-5.0FSN2 Measurement Point: 1 Meter Beneath the Unit and 1 Meter From Discharge Grille Noise Criteria Curve Octave Sound Pressure Level (dB: Overall C Scale) 80 70 1000 Central Frequency (Cycle per Second) Noise Criteria Curve Octave Sound Pressure Level (dB: Overall C Scale) Power Supply: 220V, 50/60Hz Measurement Point: 1 Meter Beneath the Unit and 1 Meter From Discharge Grille NC-30 Me 80 NC-70 70 60 NC-60 50 NC-50 Hi 40 NC-40 30 NC-30 Me Lo Lo 20 Approximate Threshold of Hearing for Continuous Noise 20 Approximate Threshold of Hearing for Continuous Noise NC-2 0 10 NC-2 0 10 63 125 250 500 1000 2000 4000 Central Frequency (Cycle per Second) 8000 63 125 250 500 1000 2000 4000 8000 Central Frequency (Cycle per Second) 1-84 SOUND DATA Total Heat Exchangers Model: KPI-2521 Power Supply: 220-240V/50Hz Model: KPI-5021 Measurement Point: 1.5 Meter Beneath the Unit and with a Sound-Proof Duct Power Supply: 220-240V/50Hz Measurement Point: 1.5 Meter Beneath the Unit and with a Sound-Proof Duct 90 90 Noise Criteria Curve Noise Criteria Curve 80 NC-70 70 60 NC-6 50 NC-5 40 NC-4 30 NC-3 0 0 0 0 Me Lo Hi NC- 20 10 Octave Sound Pressure Level (dB: Overall C Scale) Octave Sound Pressure Level (dB: Overall C Scale) 80 125 250 500 1000 2000 NC-70 60 NC-6 50 NC-5 40 NC-4 0 0 0 30 NC-3 4000 Me 10 8000 Lo 63 Central Frequency (Cycle per Second) Model: KPI-8021 125 250 500 NC-20 1000 2000 4000 8000 Central Frequency (Cycle per Second) Power Supply: 220-240V/50Hz Model: KPI-10021 Measurement Point: 1.5 Meter Beneath the Unit and with a Sound-Proof Duct Power Supply: 220-240V/50Hz Measurement Point: 1.5 Meter Beneath the Unit and with a Sound-Proof Duct 90 90 Noise Criteria Curve Noise Criteria Curve 80 80 70 NC-70 60 NC-6 50 NC-5 40 NC-4 Octave Sound Pressure Level (dB: Overall C Scale) Octave Sound Pressure Level (dB: Overall C Scale) 0 Hi 20 20 63 70 0 0 0 30 NC-3 0 Lo Hi Me 20 70 NC-70 60 NC-6 50 NC-5 40 NC-4 0 0 0 Hi Lo 30 NC-3 0 Me NC- 20 20 NC-20 10 63 125 250 500 1000 2000 4000 Central Frequency (Cycle per Second) 8000 10 63 125 250 500 1000 2000 4000 8000 Central Frequency (Cycle per Second) NOTES: 1. The sound pressure level is based on following conditions, 1.5 Meter Beneath the Unit. (Total heat exchange mode) The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field. 2. The sound pressure level emitted from the air outlet to the duct is higher than the values indicated in the GENERAL DATA table by 5 to 6 dB(A) approximately. It is recommended that a sound-proof duct. 1-85 SOUND DATA Power Supply: 220V/60Hz Model: KPI-2521 90 Power Supply: 220V/60Hz Model: KPI-5021 Measurement Point: 1.5 Meter Beneath the Unit and with a Sound-Proof Duct 90 Measurement Point: 1.5 Meter Beneath the Unit and with a Sound-Proof Duct Noise Criteria Curve Octave Sound Pressure Level (dB: Overall C Scale) Noise Criteria Curve Octave Sound Pressure Level (dB: Overall C Scale) 80 70 NC-70 60 NC-6 50 NC-5 0 0 40 NC-4 Hi 0 Me 30 NC-30 Lo 80 70 NC-70 60 NC-6 50 NC-5 0 40 NC-2 0 Me 30 NC-30 10 125 250 500 1000 2000 4000 NC-2 20 0 10 8000 0 63 Power Supply: 220V/60Hz Model: KPI-8021 125 250 500 90 NC-6 50 NC-5 40 NC-4 0 0 0 Hi 30 NC-30 Me 8000 Noise Criteria Curve Octave Sound Pressure Level (dB: Overall C Scale) Octave Sound Pressure Level (dB: Overall C Scale) 80 60 4000 Measurement Point: 1.5 Meter Beneath the Unit and with a Sound-Proof Duct Noise Criteria Curve NC-70 2000 Power Supply: 220V/60Hz Model: KPI-10021 Measurement Point: 1.5 Meter Beneath the Unit and with a Sound-Proof Duct 70 1000 Central Frequency (Cycle per Second) Central Frequency (Cycle per Second) 90 NC-4 Hi Lo 20 63 0 80 70 NC-70 60 NC-6 50 NC-5 0 0 NC-4 0 40 Hi 30 NC-30 Lo Lo Me 20 NC-2 0 20 NC-20 10 10 63 125 250 500 1000 2000 4000 Central Frequency (Cycle per Second) 8000 63 125 250 500 1000 2000 4000 8000 Central Frequency (Cycle per Second) NOTES: 1. The sound pressure level is based on following conditions, 1.5 Meter Beneath the Unit. (Total heat exchange mode) The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field. 2. The sound pressure level emitted from the air outlet to the duct is higher than the values indicated in the GENERAL DATA table by 5 to 6 dB(A) approximately. It is recommended that a sound-proof duct. 1-86 ELECTRICAL WIRING DIAGRAM (FOR MODELS: RPI-0.8FSN2, RPI-1.0FSN2, RPI-1.5FSN2, RPI-2.0FSN2, RPI-2.5FSN2, RPI-3.0FSN2, RPI-4.0FSN2 AND RPI-5.0FSN2) ctrical Wiring Diagram CONTROL SYSTEM 1-139 ELECTRICAL WIRING DIAGRAM (FOR MODELS: RPI-8FSN AND RPI-10FSN) CONTROL SYSTEM 1-140 ELECTRICAL WIRING DIAGRAM (FOR MODELS: RCI-1.0FSN2, RCI-1.5FSN2, RCI-2.0FSN2, RCI-2.5FSN2, RCI-3.0FSN2, RCI-4.0FSN2 AND RCI-5.0FSN2) CONTROL SYSTEM 1-141 ELECTRICAL WIRING DIAGRAM (FOR MODELS: RCD-1.0FSN2, RCD-1.5FSN2, RCD-2.0FSN2, RCD-2.5FSN2, RCD-3.0FSN2, RCD-4.0FSN2 AND RCD-5.0FSN2) CONTROL SYSTEM 1-142 ELECTRICAL WIRING DIAGRAM (FOR MODELS: RPK-1.0FSNSN2 AND RPK-1.5FSNSM2) CONTROL SYSTEM 1-143 ELECTRICAL WIRING DIAGRAM (FOR MODELS: RPK-2.0FSNSM2) CONTROL SYSTEM 1-144 ELECTRICAL WIRING DIAGRAM (FOR MODELS: RPK-2.5FSNSM2, RPK-3.0FSNSM2 AND RPK-4.0FSNSM2) CONTROL SYSTEM 1-145 CN2 CN17 C55 DM1 C16 EF2 DSW7 L1 C2 CN1 CN14 CN19 CN7 PCB Sockets location Main Switch Main Switch CN5 CN8 CN10 IC1 EF3 PCN5 CN11 PCN1 1~ 220V/60Hz (3~) 1N~ 220V/60Hz (3N~) 1N~ 220/240V 50Hz (3N~) CN3 DSW3 DSW4 YH2 PCN6 SK1 YLO P (17G ) THM5 THM3 THM1 RSW1 THM4 THM2 RSW2 TP YME PCN11 DSW6 DSW5 Y52H PCN3 EFS1 EFR1 YSLO PCN10 YH1 CAUTION HIGH VOLTAGE PCN8 PCN7 for Communication 2 wire RCS (PC-AR) PCN2 OUTPUT1 Electrical Control Box of Indoor Unit INPUT Inlet OUTPUT2 Outlet Liquid ·X· – ·· – ·· – - –- –- – –––––– Mark CA CN DSW3 DSW5 DSW6 DSW7 RSW EFR1,EFS1,EF1 ITI LD1~3 MIF MV PCB RCS RSW1, RSW2 SSW TB THM1 THM2 THM3 THM5 TF YME YLO YSLO YH1 Gas for RCS Name Capacitor for Indoor Fan Connector Unit Capacity Code Refrigerant Cycle No. Unit Models Code Fuse Recover/Remote Controller Selector Indoor Unit No. Setting Fuse Internal Thermostat for Indoor Fan Motor Alarm Code Motor for Indoor Fan Expansion Valve Printed Circuit Board Remote Control Switch Indoor Unit No. Settings Slide Switch Terminal Board Inlet Air Thermistor Outlet Air Thermistor Liquid Pipe Thermistor Gas Pipe Thermistor Transformer Relay for ME Fan Motor Tap Relay for LO Fan Motor Tap Relay for SLO Fan Motor Tap Relay for Hi Fan Motor Tap Terminals Field Connection Field Wiring Earth Wiring Factory Wiring ELECTRICAL WIRING DIAGRAM (FOR MODELS: RPF-1.0FSN2E, RPF-1.5FSN2E, RPFI-1.0FSN2E AND RPFI-1.5FSN2E) DC Coil DC Coil DC Coil DC Coil On PCB On PCB On PCB On PCB Optional Part On PCB On PCB On PCB On PCB On PCB On PCB On PCB On PCB On PCB Remarks CONTROL SYSTEM 1-146 ELECTRICAL WIRING DIAGRAM (FOR MODELS: RPC-2.0FSN2, RPC-2.5FSN2, RPC-3.0FSN2, RPC-4.0FSN2 AND RPC-5.0FSN2) CONTROL SYSTEM 1-147 MISCELLANEOUS NOTES 11. Miscellaneous Notes Special Notes 1. Provide a service access door near the unit piping connection part on the false ceiling for the cassette type units. 2. Consider the air distribution from the unit to the space of the room, and select a suitable location so that uniform air temperature in the room can be obtained. Cassette and Ceiling Types - Avoid unit installation in a room where the ceiling height (distance between the floor to the false ceiling) exceeds three meters. If the indoor unit is installed in a room with a ceiling of higher than 3 meters, it is recommended that an air circulation fan be installed separately to obtain uniform air temperature in the room, especially during the heating operation. 3. Check to ensure that the ceiling slab is strong enough and that the false ceiling is flat and level. 4. Avoid obstacles which may restrict the air intake or the discharge flow. 5. Do not install the unit in a machinery shop or kitchen where vapor from oil or its mist can enter to the unit. The oil will deposit on the heat exchanger, thereby reducing the unit performance, and may deform, in the worst case, break the plastic parts of the unit. 6. Pay attention to the following points when the unit is installed in a hospital or other facilities where electromagnetic wave is radiated from medical equipment. (A) Do not install the unit where the electromagnetic wave is directly radiated to the electrical box, remote control cable or remote control switch. (B) Install the unit and component as far as practical (at least three meters) from the electromagnetic wave radiator. (C) Prepare a steel box and install the remote control switch in it. Prepare a steel conduit pipe and wire the remote control cable in it. And then, connect earth wire with the box and the pipe. (D) Install a noise filter when the power supply emits harmful noise. 7. Do not install the units in an acid or alkaline environment due to the corrosive action on the heat exchanger. In the case that outdoor units are installed near the sea, it is recommended that optional corrosion-resistant type outdoor unit be used. 8. Do not install the units in a flammable environment due to the danger of an explosion. 9. Regarding cassette type indoor units, consider the direct and reflected sound level, when selecting the unit for spaces where extremely low sound is required. 10. During heating operation, the outdoor heat exchanger produces condensate dew or melting water from frost. Install the outdoor unit where drainage of such water is convenient, or provide a drain passage. 11. Heating Performance: The heating capacity normally decreases when outdoor temperatures decrease. Therefore, provide an auxiliary heating unit if outdoor temperatures are very low. 12. In the case that an outdoor temperature is low and humidity is high, the outdoor heat exchanger will covered with frost, resulting in lower heating capacity. In order to remove the frost, the unit is automatically changed to the defrosting mode. During this defrosting operation, the unit is stopped for approximately 3 to 10 minutes. 13. As this unit is of heat pump type by circulating hot air in the whole room space, it takes time to heat up the room temperature. 14. The operating sound data is based on an anechoic chamber. Therefore, the actual operating sound will be higher due to reflected sound from the floor and wall. 15. In the case that the unit is operated for a long time higher than the indoor temperature of 27oCDB or the humidity of 80%, dewing may occur on the cabinets resulting in dew drops. If dewing, it is required to add thermal insulator on the cabinets. 16. Provide snow-protection hoods to prevent the outdoor heat exchanger from snow clogging. If the unit is operated in an are where it snows heavily, provide a base under the outdoor unit which should be 50cm higher than the presumable maximum snow height. 17. It is recommended that periodical service and maintenance be performed by authorized service engineers before air conditioning seasons, in order to avoid performance decrease due to dust or dirt. 18. This heat pump air conditioner has been designed for normal air conditioning for men. Do not apply to other purposes such as for food, animals, plants, high precision machines or work of art. Also do not apply to vehicles or vessels. It will results in water leakage or electrical leakage. 19. It is recommended that the system be installed by authorized engineers. If not, it may cause water leakage, electric shock or fire. 20. In a place where fibers or dusts are floating, the air filter or heat exchangers or the drain pipe may be clogged, resulting in water leakage from the drain pan. 1-149 MISCELLANEOUS NOTES Special Notes on Refrigerant, R410A Use tools and measuring instruments only for the new refrigerant which is directly touch to refrigerant. : Interchangeability is available with current R22 : Prohibited Measuring Instrument and Tool Pipe Cutter Chamfering Reamer Flaring Tool Interchangeability with R22 R410A R407C - Extrusion Adjustment Gauge - Pipe Bender Brazing Tool Nitrogen Gas * The flaring tools for R407C are applicable to R22. * If using flaring tube, make dimension of tube larger for R410A. * In case of material 1/2H, flaring is not available. * In case of material 1/2H, bending is not available. Use elbow for bend and braze. * In case of material 1/2H, expanding of tube is not available. Use socket for connecting tube. * For 12.7, 15.88, spanner size is up 2mm. * For 6.35, 9.53, 19.05, spanner size is the same. * Perform correct brazing work. * Strict Control against Contamin (Blow nitrogen during brazing.) Lubrication Oil (for Flare Surface) Refrigerant Cylinder Vacuum Pump Adapter for Vacuum Pump Manifold Valve Charging Hose Charging Cylinder Weight Scale Refrigerant Charge Reason of Non-Interchangeability and Attention (: Strictly Required) Refrigerant Expanding Tool Pipe Torque Wrench Vacuum Drying : only for Refrigerant R410A (No Interchangeability with R22) : only for Refrigerant R407C (No Interchangeability with R22) Refrigerant Gas Leakage Detector Use Cutting Pipe Removing Burrs Flaring for Tubes Dimensional Control for Extruded Portion of Tube after Flaring Bending Expanding Tubes Connection of Flare Nut Brazing for Tubes Prevention from Oxidation during Brazing * Use a synthetic oil which is equivalent to the oil used Applying Oil to in the refrigeration cycle. the Flared Surface * Synthetic oil absorbs moisture quickly. * Check refrigerant cylinder color. Refrigerant Charging Liquid refrigerant charging is required regarding zeotoropic refrigerant. Vacuum Pumping The current ones are applicable. However, it is required to mount a vacuum pump adapter which can prevent from reverse flow when a vacuum pump stops, resulting in no reverse oil flow. * No interchangeability is available due to higher pressures when compared with R22. Do not use current ones to the different refrigerant. If used, mineral oil will flow into the cycle and cause sludges, resulting in clogging or compressor failure. Connection diameter is different; R410A: UNF1/2, R407C: UNF7/16. Vacuum Pumping, Vacuum Holding, Refrigerant Charging and Check of Pressures * Use the weight scale. Measuring Instrument for Refrigerant Charging Gas Leakage Check * The current gas leakage detector (R22) is not applicable due to different detecting method. : Interchangeability with R407C. 1-150 STANDARD SPECIFICATIONS Standard Specification for the Hitachi Premium Range of Air Cooled Modular Set Free VRF Systems Preamble Air cooled Condenser FSXN SERIES The units shall be manufactured by Hitachi, and shall meet or exceed the requirements of this specification. Units shall be designed in accordance with the relevant standards, and tested to JIS Standard JIS B8616 packaged air conditioner and shall be compliant with AS/NZS1677 refrigerating system. Units shall be suitable for providing continuous operation in ambient conditions between -20˚C and 43˚C without excessive head pressure, unstable operation or icing. Refrigerant shall be R410A.Acoustic performance is to be fully documented within the manufacturers standard technical literature, and is to be measured in accordance with JIS 8616. Noise spectrum results commencing at the 63Hz band and finishing at the 8K Hz band are to be provided, along with an overall noise level Noise data is to be provided for the following: Indoor unit • Sound Pressure Level • Outdoor Unit Sound Pressure Level • Sound Power Level Cabinet - The cabinet shall be constructed from galvanized sheet complete with a baked polyester powder coat finish. All fasteners exposed to the weather shall be galvanized steel. The condenser cabinet shall be rated to IP 45, fully weatherproofed and suitable for outdoor operation, housing compressor, outdoor coil, condenser fan, motor and main electric controls interfacing Hitachi H-Link network. Access panel shall be provided for routine inspection and maintenance. Compressor - Shall control inverter scroll compressor speed from 20HZ to 100HZ with 80 steps, quickly reach the set point then maintain in a stable energy saving operation. FSXN8/10/12 shall be fit with one inverter driven scroll compressor and FSXN14/16/18 shall be fit with one inverter driven scroll compressor and one constant scroll compressor. Compressor shall be protected by a quick response over current relay, a high pressure switch, a wrap around type oil heater and a discharge gas thermistor. Crankcase heater shall be factory supplied and mounted. Condenser Fan - Shall be plastic propeller type fan direct driven by variable speed motor with permanently lubricated bearings for vertical flow air discharge. Propeller fan shall be statically and dynamically self balanced. Fan shall be provided with guard to prevent from contact with moving parts. Refrigeration Circuit - Shall include, but not be limited to the following: System description The variable capacity heat pump as well as heat recovery air conditioning system shall be Hitachi inverter driven Modular FSXN series that use universal condensing units with R410A refrigerant. The FSXN Series shall be either 3 pipe heat recovery multi split inverter system or 2 pipe heat pump multi split system. The base module shall be FSXN8/10/12 and FSXN14/16/18 and shall be capable to form up to 54HP with 3 standard modules. The 3 pipe heat recovery system shall consist of Hitachi Modular FSXN outdoor unit/s, CH (changeover) Boxes, multiple indoor units and associated local and central controls. Each indoor unit or group/zone shall be capable of operating independently and system shall be capable of operating in either cooling, heating or simultaneous cooling and heating mode. Each indoor unit or group/zone shall be able to change mode with no interruption to whole system operation. The 2 pipe heat pump system shall consist of Hitachi FSXN outdoor unit/s, multiple indoor units and associated local and central controls. Each refrigerant group shall be capable of operating independently and system shall be capable of operating in either cooling or heating mode. The single VRF system shall be capable of handling range from 50%-130% connected indoor capacity and up to 64 indoor units without unstable operation. The total refrigerant piping length shall be able to run up to 1000 m max and Max single piping length shall be able to run up to 165 m. The lift between outdoor and indoor units shall be within 50m. • DC inverter scroll Compressor/s • Electronic Expansion Valve • Head Pressure Control • Common fault indication • Anti short cycle timer • Frost protection • Liquid & Suction service valves • Di – Ice control based on time/temperature initiation - Hot gas by – pass defrost type control shall not be used • DC inverter Compressor – scroll compressor - Crank case heater fitted to the compressor - The compressor is to be located within an isolated compressor compartment • Compressor minimum run time Condenser Coil - Shall be multi pass, cross finned tube type manufactured by Hitachi, and will comprise copper tube, complete with anti corrosion aluminium fin stock mechanically bonded to the copper tubes. Frames shall be aluminium, suitable for outdoor use. The coil shall be designed to allow for the full coil 1-151 A STANDARD SPECIFICATIONS to be de-frosted where necessary. Coil shall be cleaned, dehydrated and pressure tested at factory and shall be charged with correct refrigerant charge before shipment. Clearance shall be provided around units for condenser air flow and maintenance access. Hot discharge air shall not be short-circuited to condenser intake. CH Change Over Box Cabinet - The cabinet shall be compact, light weight, constructed from galvanized sheet complete with high density foam insulation suitable for indoor installation. All fasteners exposed to the weather shall be galvanized steel. The sheet metal cabinet shall be housing expansion valves, refrigeration control solenoid valves, control circuit board and other electric controls interfacing Hitachi H-Link network. Access panel shall be provided for routine inspection and maintenance. Changeover box shall be capable of control refrigerant flow for either one unit or a group of up to 8 units. It shall have 2 incoming gas pipes (low pressure and high pressure) and 1 outgoing gas pipe. Liquid pipe shall not be run through changeover box to save on pipe joints. Ducted Indoor Unit RPI SERIES Cabinet - Shall be fabricated using galvanized steel with high density foam insulation. The cabinet shall include indoor coils, piping, supply air fan, motor, electronic expansion valve, control circuit board, accessories and electrical connections mounted within an insulated enclosure with four brackets to accommodate suspension. Access panels shall be easily removed and sized to provide adequate access to interior for routine inspection and maintenance, and shall be air tight. The cabinet is to be insulated for thermal & acoustic performance, using polyethylene insulation. Evaporator Coil - Shall be manufactured by Hitachi, and shall be direct expansion type manufactured from inner grooved copper tubes expanded into aluminum fins to form a mechanical bond. Coil shall be pressure tested at factory and shall be charged with dry air or dry nitrogen before shipment. Condensate Drain Pan - Shall be sized and sloped to catch all condensate, and to allow it to drain away freely, and shall be constructed to be corrosion resistant. Evaporator Fan - Shall be direct drive centrifugal fan, minimum 3 speeds. Indoor centrifugal fan shall be statically and dynamically self balanced and shall be driven by high efficient DC fan motor with permanently lubricated bearings. Fan curves showing the airflow limits, available external static, and input power for each fan speed are to be documented within the manufacturer’s standard literature. Cassette Indoor Unit RCI/RCD SERIES Cabinet - Shall be fabricated using galvanized steel coated with high density foam insulation with unit height within 300mm. The cabinet shall include indoor coils, piping, supply air fan, drain pump, electronic expansion valve, control circuit board, accessories and electrical connections mounted within an insulated enclosure. Facial Panel shall be either a four-way or a two-way air distribution type, impact resistant, stain resistant and washable decoration panel. The supply air is distributed via motorized louvers which can be horizontally and vertically adjusted from 0° to 90°. Access panels shall be easily removed and sized to provide adequate access to interior for routine inspection and maintenance, and shall be air tight. The cabinet is to be insulated for thermal & acoustic performance, using polyethylene insulation. Evaporator Coil - Shall be manufactured by Hitachi, and shall be direct expansion type manufactured from inner grooved copper tubes expanded into aluminum fins to form a mechanical bond. Coil shall be pressure tested at factory and shall be charged with dry air or dry nitrogen before shipment. Condensate Drain Pan - Shall be sized and sloped to catch all condensate, and to allow it to drain away freely, and shall be constructed to be corrosion resistant. A condensate pan with drain connections shall be provided under the coil. The unit shall also include a built-in, automatic condensate lift mechanism that will be able to raise drain water 850mm above the condensate pan. The lift mechanism shall be equipped with a positive acting liquid level sensor to shut down the indoor unit if liquid level in the drain pan reaches maximum level. Evaporator Fan - Shall be direct drive turbo fan, minimum 3 speeds. Indoor turbo fan shall be statically and dynamically self balanced and shall be driven by high efficient DC fan motor with permanently lubricated bearings. The four-way indoor unit shall have an adjustable air outlet system offering 4-way airflow, 3-way airflow, or 2-way airflow with switches that can be set to provide optimum airflow based on ceiling height and number of outlets used. Wall Mounted Indoor Unit RPK SERIES Cabinet - Shall be fabricated with high strength moulded plastic and sufficient insulation and shall be suitable to be mounted firmly on the factory supplied mounting template. It Shall include indoor coils, piping, supply air fan, motor, electronic expansion valve, control circuit board, accessories and electrical connections within an insulated enclosure. Front panel shall be easily removed to provide access to interior of unit for routine inspection and maintenance. Evaporator Coil - Shall be manufactured by Hitachi, and shall be direct expansion type manufactured from inner grooved copper tubes 1-151 B STANDARD SPECIFICATIONS expanded into aluminum fins to form a mechanical bond. Coil shall be pressure tested at factory and shall be charged with dry air or dry nitrogen before shipment. Condensate Drain Pan - Shall be sized and sloped to catch all condensate, and to allow it to drain away freely, and shall be constructed to be corrosion resistant. Evaporator Fan - Shall be tangential type fan direct driven by single phase motor with permanently lubricated bearings, minimum 3 speeds. Indoor tangential fan shall be statically and dynamically balanced. Under ceiling Mounted Indoor Unit RPC SERIES Cabinet - Shall be fabricated with galvanised steel with white power coating and sufficient insulation and shall be suitable to be mounted firmly under ceiling. It Shall include indoor coils, piping, supply air fan, motor, electronic expansion valve, control circuit board, accessories and electrical connections within an insulated enclosure. Front panel shall be easily removed to provide access to interior of unit for routine inspection and maintenance. Evaporator Coil - Shall be manufactured by Hitachi, and shall be direct expansion type manufactured from inner grooved copper tubes expanded into aluminum fins to form a mechanical bond. Coil shall be pressure tested at factory and shall be charged with dry air or dry nitrogen before shipment. Condensate Drain Pan - Shall be sized and sloped to catch all condensate, and to allow it to drain away freely, and shall be constructed to be corrosion resistant. Evaporator Fan - Shall be sirocco type fan direct driven by single phase motor with permanently lubricated bearings, minimum 3 speeds. Indoor sirocco fan shall be statically and dynamically balanced. Floor Mounted Indoor Unit RPF/RPFI SERIES Cabinet - Shall be fabricated with galvanised steel for floor concealed type and galvanised steel with white power coating for floor exposed type and sufficient insulation and shall be suitable to be mounted firmly on the floor. It Shall include indoor coils, piping, supply air fan, motor, electronic expansion valve, control circuit board, accessories and electrical connections within an insulated enclosure. Front panel shall be easily removed to provide access to interior of unit for routine inspection and maintenance. Evaporator Coil - Shall be manufactured by Hitachi, and shall be direct expansion type manufactured from inner grooved copper tubes expanded into aluminum fins to form a mechanical bond. Coil shall be pressure tested at factory and shall be charged with dry air or dry nitrogen before shipment. Condensate Drain Pan - Shall be sized and sloped to catch all condensate, and to allow it to drain away freely, and shall be constructed to be corrosion resistant. Evaporator Fan - Shall be sirocco type fan direct driven by single phase motor with permanently lubricated bearings, minimum 3 speeds. Indoor sirocco fan shall be statically and dynamically balanced. Control General - shall consist of Hitachi local control, central control, central on/off control, schedule timer, web based CS Net and Open interface including Bacnet and Lonworks gateway. Wiring - Shall be no-polar 2 conductor, twisted shielded pair and shall be wired in daisy chain configuration from outdoor units to changeover boxes and from changeover box to indoor units. Control wiring for central control, schedule timer, CS net shall be installed in daisy chain from outdoor units to outdoor units and to these controls. Local Remote Control - shall be LCD wired remote control PC-AR OR PC-ART with weekly timer function. General: Provide microprocessor controller with the following functions: - Power ON/OFF switch. - Mode selector switch: DEHUMIDIFY - COOL - HEAT - AUTO - Temperature settings - Evaporator fan speed selector - Indicating lamps, LEDs or LCD display for unit operating or fault - Self diagnosis functions - Group control up to 16 units by one single control Central Control - shall be LCD wired control or web based as listed, - Schedule timer: PSC-A1T (weekly timer with 3 programs/day, winter and summer schedule) - Central on/off control: PSC-A16RS (up to 16 groups or 160 units collectively on/off control) - Central station control: PSC-A64S OR PSC-5S (up to 64 groups or 160 units collectively control) - Web based control: PSC-6WTX (up to 64 groups or 1024 units collectively control over net) Quality assurance The complete VRF system shall be designed within the guarantee working range published in the technical literature and installed within guide line of manufacturer published technical literature and shall be commissioned and certified by factory trained technicians or factory trained agents. The complete system shall be complete assembled and tested in ISO9001 and ISO14001 certified manufacturing facilities and shall be tested to comply with current Australian safety and EMC standards. 1-151 C IMPORTANT NOTICE • Upon receiving this product, inspect it for any shipping damage. Claims for damage, either apparent or concealed, should be filed immediately with the shipping company. • Check the model number, electrical characteristics (power supply, voltage and frequency) and accessories to determine if they are correct. The standard utilization of the unit shall be explained in these instructions. Therefore, the utilization of the unit other than those indicated in these instructions is not recommended. Please contact your local agent, as the occasion arises. HITACHI’s liability shall not cover defects arising from the alteration performed by a customer without HITACHI’s consent in a written form. CAUTION • Use shielded wires of operation line between the indoor unit and the outdoor unit. And connect the shielded part to the earth screw in the electrical box of the indoor unit as shown in the Fig. 1. (Example: RPI-8FSN) Protect the earth wire not to contact with the live part. Earth Terminal TB1 *Earth the tip of shield wires as shown. TB2 A B 1 2 DO NOT connect the wiring to these terminals. (TB1-1,2) Power Source Cable Remote Control Switch Cable Shielded Part Transmission Cable *In case of Australia, ensure to earth shield wire tip of both ends. *ELB *ELB: Earth Leakage Breaker Power Source Fig. 1 Earth Wiring
Similar documents
Technical Catalogue
7.2.1. RCI-(1.0-6.0)FSN3 - 4-way cassette........................................................................................................ 193 7.2.2. RCI-(1.0-6.0)FSN3Ei - 4-way cassette.....
More informationTwo-way cassette RCD
Nominal Heating Capacity(2) UK Cooling Capacity (sensible)(3) Noise Level (sound pressure) (L / M / H)(4) Noise level (sound power)(5) Air flow cooling mode (L / M / H) Dimensions (H x W x D) Weigh...
More information