Screw Type Air-Cooled Packaged Chillers ACWC - Dunham
Transcription
Screw Type Air-Cooled Packaged Chillers ACWC - Dunham
! ••••••••••••••••••••••••••••• •• •• •• • • •• •• ••• •• • •• •• •• •• •• •• • • •• •• •• • •• ACWC-SD Screw Type Air-Cooled Packaged Chillers Installation, Operation, and Maintenance Manual TABLE OF CONTENTS DESCRIPTION Inspection & Handling PAGE NO. 2 Location and Mounting Wiring Chiller Piping Start-Up Maintenance Slide Valve Unloading System Low Ambient Operation Control Settings Unit Operating Limitations Sequence of Operation Safety Controls, Field Wiring, Star Delta Start Control Wiring Diagrams ACWC 40 thru 70 ACWC 90 thru 135 ACWC 145 thru 200 ACWC 215 thru 265 Power Wiring Diagrams ACWC 40 thru 70 ACWC 90 thru 135 ACWC 145 thru 200 ACWC 215 thru 265 Electrical Data Cooler Pressure Drops Unit Loading/Suspension Points Troubleshooting Guide Causes & Prevention of Freeze-Up Start-up Check List Operating Data Maintenance • • •• •• •• ••••••••••••••••••••••• Form No. 6184 2 2 2 2&3 3 4 5 5 5 6 & 7 7 8 & 9 10 & 11 12 & 13 14 & 15 16 16 17 17 18 & 19 20 21 22 22 23 24 24 DUNHAM-BUSH USA INSPECTION & HANDLING CHILLER PIPING When unit is received, it is the responsibility of the contractor to inspect the unit for shipping damage at time of off loading and make note of damage on carrier's freight bill. The chiller inlet (return) water pipe should be connected to the water connection closest to the control panel end of the unit and the outlet (supply) water pipe connected to the water connection on the opposite end of the cooler(s). ACWC units are factory mounted on (2) carbon steel angle beams. Sizes 45 thru 90 have three lifting holes per side. Sizes 110 thru 215 have four lifting holes per side and sizes 240 thru 265 have five lifting holes per side to facilitate lifting. Spreader bars must be used between rigging lines to prevent damage to the unit. Rollers may be used under the skids to facilitate moving the unit a short distance. Models ACWC-40DF thru 22DC are factory mounted on two permanent angle beam, carbon steel skids. A minimum of four 2 7/8" lifting eyes are provided in the skids to allow rigging. Physical damage to the unit, after acceptance, is not the responsibility of the factory. LOCATION & MOUNTING Model ACWC Air Cooled Packaged Water Chillers are designed for outdoor application and may be mounted on roof or at ground level. Air lIow through the condenser is vertical and the unit may be located adjacent to outside of building or on roof without regard for prevailing wind direction. Since these units are air cooled, the flow of air to and from the condenser coil must not be impeded. There must be no obstruction above the unit that would tend to dellect discharge air downward where it could be recirculated back to the inlet of the unit. The required overhead air space should be a minimum of eight feet. Ductwork must not be applied to the fan outlets. A flow switch must be installed in a straight horizontal section of the chilled water piping. This is to be field installed. Gauges should be installed in the piping to and from the chiller to measure the pressure drop and to insure the proper (GPM) flow rate in accordance with submittal data. A strainer should be installed in the piping on the inlet side of the chiller and vibration eliminators should be employed on both the inlet and outlet pipes. Air vents should be located at all high points in the piping system. Vents should be located to be accessible to servicing. Drain connections should be provided at all low points to permit complete drainage of chiller and piping system. The chilled water piping should be insulated to reduce heat pickup and to prevent condensation. If the system is for year-round operation or if it will not be drained in the winter, the chilled water piping should be protected against freezing by electric heating cable or other suitable means. Upon completion of chiller piping, start the system water pump and purge air from the system. Air purging should be done from the high points in the water circuit. Purging of the chiller barrel may be accomplished through the vent pipe located on the top of the chiller compartment Failure to purge air from the water circuit will result in inadequate water flow and may cause the unit to cutout. START·UP Refer to start, test, and check list included with this manual. The unit must be installed with sufficient clearance for air entrance to the condenser coil and for servicing access. The unit should be located no closer than four feet from any wall or other obstruction. Clearance must be provided at either end of the unit to permit removal of tubes from the chiller. Unit must be set on a solid and level foundation. On roof installations the unit should be mounted on support beams which span load-bearing walls to prevent excessive vibration. On ground level installations, the unit should be mounted on a substantial base that will not settle. A one-piece concrete slab with footings extended below the frost line is recommended. A space should be left between the slab and the building to prevent the transmission of sound and vibration. Vibration mounts may be used for roof-mounted units or other locations where noise might be objectionable. WIRING A unit wiring diagram showing the required power supply characteristics and all factory supplied wiring details are provided with unit. Separate, field supplied, disconnects must be installed for the power and control circuits and should be within the sight of the unit. Separate 115-volt power source must be field supplied to provide power for control and heater circuits if optional control circuit transformer is not provided. All electrical connections should be periodically tightened. 2 CAUTION: The discharge line valve must be open before starting the compressor. Liquid line valves must also be open for sustained operation. 3. COMPRESSOR REPAIRS (internal) - Contact factory or an authorized DB Service Agency if a compressor malfunction is suspected. 4. COMPRESSOR REPAIRS (External) - Proper operation of All compressors are solid mounted on isopads, therefore, compressor hold-down bolts must not be loosened. Loosening these bolts will cause excessive vibration of the compressor and may result in refrigerant line breakage. Prior to start-up check all compressor hold-down bolts for tightness. unloaded ban, loading, and unloading is controlled by solenoid valves UL-1, UL-2 and UL-3. Any of these three (3) solenoid valves may be repaired or replaced in the field, as required. 5. Standard oil acid test kit is not compatible with synthetic oil. See DB color chart for oil condition. MAINTENANCE CONDENSER Units are equipped with direct drive fans that have inherently protected motors with permanently lubricated bearings. HIGHPRESSURE PORT The air inlet of the condenser coil should be kept clean through a regular maintenance program. COMPRESSOR 1. 2. OIL LEVEL - The oil level in the compressor(s) should be checked periodically, with the compressor either running or stopped. If the oil level is below one-half (1/2) the sight glass, oil must be added. I SIGHT GLASS CRANKCASE HEATER RECOMMENDED OIL -- The unit 4 factory-charged with DB SR-30 refrigeration 01. Do not add any other type of oil to this factory charge. Do not operate compressor If 011 level Is below one-half (1/2) sight glass. If the oil level is below the minimum specified above, and DB SR-30 is not on hand, you may drain the entire factory oil charge, then refill with SUNISO 4GS refrigeration oil. The factory (DB) oil is of the synthetic type and will not mix with SUNISO 4GS. Do not attempt to operate the screw compressor with any oil other than these two specified above. It is suggested that a gallon or mom of DB SR-30 oil be obtained and kept on hand at the job site. The substitution of SUNISO 4GS oil, as outlined above, will result in a 2% to 491 capacity loss, and no reduction in input K.W. PROCEDURE FOR ADDING OIL Install temporary jumper wire around L.P.control contacts of circuit to be serviced. Manually close liquid line service valve. Lower return water T-STAT (T1) setting to start compressor. Run compressor until minimum positive pressure reading on suction service gauge. (Do not run compressor in vacuum!) Place the system on/off switch in the off position. Close the line valve in the discharge line between compressor & condenser. Equalized pressure should now be a minimum of refrigerant vapor. Reopen discharge line valve. Remove jumper wire from pressure control. Open liquid line service valve. 3 SLIDE VALVE UNLOADING SYSTEM The Rotary screw compressor capacity control system for infinite modulation consists of a slide valve and hydraulic piston/cylinder operator intemal to the compressor; plus three hydraulic solenoid valves (UL-1, UL-2 & UL-3). pressure) line. The slide valve will move to the right (unloading) whenever UL-2 opens the oil supply (high pressure) line, since the force of the oil exceeds that of the discharge gas. The temperature controller sends a series of power (energizing) "pulses" to the appropriate solenoid to adjust to load conditions. The further the supply water temperature is from the controller set point, the longer is the duration of the pulses. The series of pulses will continue until the controller is satisfied. As the water temperature approaches the set point, the pulses become quite brief to prevent overshooting the set point. The slide valve forms a portion of the chamber wall in which the rotors turn; thus, its position with respect to the rotors determines the effective rotor length and thereby the percent of full load capacity. Upon compressor start-up, UL-3 is opened. This allows oil pressure to act upon the hydraulic piston, holding it in the fully unloaded position. After 30 seconds, during which time full oil flow is established to all bearings surfaces, UL-3 is closed. At this point the temperature controller is free to open and close UL-1 or UL-2 in response to the supply water temperature. This method of compressor unloading in conjunction with supply water sensing minimizes action/reaction lag time and overshoot resulting in an exceptionally precise and stable control of supply water temperature. The slide valve will move to the left (loading) by force of discharge pressure, whenever UL-1 opens to permit flow to the oil return (low Hydraulic Piston Load Unload ~ ¢::J Oil Pressure Slide Valve Oil Pressure Lines Screw Rotor Oil Return Oil Supply The following table lists solenoid valve position for all three operating modes. Starting Loadinq Unloading 4 UL-1 Close Open Close UL-2 Close Close Open UL-3 Open Close Close LOW AMBIENT OPERATION Due to the wide range of applications, it is sometimes necessary to operate the Air Cooled Packaged Water Chillers at ambients below summer conditions. Without proper control, when ambients drop below 60°F. the pressure differential between the condenser and the evaporator is below the level to insure proper thermal expansion valve operation. As a result, the unit may cycle off. Two types of system control are available allowing the units to operate at the ambients indicated: COOLER FREEZE PROTECTION-LOW AMBIENT Cooler freeze protection is a major concern with air cooled chillers. To protect against freeze-up, a heater cable is provided as standard, which protects the cooler to -12°F. However, there is no freeze protection in the event of power failure or heater cable burnout, so the following should be considered for additional protection: 1. Drain the cooler and chilled water piping if the chiller is not to be operated over the winter months. Drain connections are provided on the coolers. FAN CYCLING MEDIUM AMBIENT CONTROL TO 30°F. (STANDARD EQUIPMENT-FACTORY INSTALLED) A fan cycling control is standard on all Air Cooled Packaged Water Chillers to provide proper operating head pressures, in ambient conditions to 30°F. This is an automatic operation in which the condenser fans are cycled on and off, as required, in response to head pressure. This arrangement provides positive start-up control down to +30°F by delaying the condenser fan operation until a predetermined head pressure is obtained. 2. Add ethylene glycol to the chilled water system. Freeze point should be approximately 10°F.below minimum design ambient temperature. See Page 11 for Glycol Performance. The cooler heater is wired to the control panel and is operational from the factory offered control transformer or field supplied control power. COOLER FREEZE PROTECTION-oPERATION The ACWC-SD chiller is provided with a temperature sensing freezstat (38° set point) and a field installed flow switch, shutting off the compressors on loss of water flow, is also required. LOW AMBIENT CONTROL TO O°F. In conjunction with the standard fan cycling feature, all compressors are enclosed in individual housings. This housing assures adequate compressor oil temperature for lubrication. A five minute time delay relay provides a bypass around the low pressure control to prevent nuisance trip-out during cold start up. Optional low pressure or hot gas bypass freeze protection is also available on the ACWC-SD. If these options have not been purchased it is extremely important to guarantee proper chiller water gpm as well as double checking the temperature sensing freezstat calibration. ACWC-SD CONTROL SETTINGS CUT-IN/CUT-OUT (PSIG) UNIT FLP1 44-55 70 280/170 260/160 90 110-135 260/160 145-160 185-200 215 260/160 280/170 280/170 240 260/160 260/160 265 260/160 FLP2 295/180 FLP3 275/175 275/175 2751175 2951180 295/180 275/175 260/160 260/160 2901215 FLP4 FLP5 FLP6 FLP7 FLP8 FLP9 FLP10 FLP11 FLP12 FLP13 2901215 260/160 275/175 2901215 2851210 2951235 2601160 275/175 285/210 2951235 260/160 275/175 2901215 260/160 275/175 2901215 260/160 275/175 2951235 2951235 260/160 275/175 285/210 2951235 2901215 260/160 2901215 2901215 260/160 275/175 290/215 260/160 275/175 290/215 275/175 275/175 2901215 2901215 260/160 260/160 275/175 275/175 2851210 2851210 295/235 275/175 275/175 2851210 2851210 295/235 2951235 260/160 260/160 275/175 275/175 285/210 TEMPERATURE ACTUATED LEGEND Chiller Low Water Temperature Thermostat Chiller Heater Thermostat I(Non-Adiustable) Oil Temperature Safety Control (Adjustable) Manual Reset Capacity Control Thermostat (Adj.) Mode Control Position T2 Included With CBH1 Heater OTS 1 OTS 2 OTS3 T1 FLP14 ISM 2951235 2851210 2951235 FACTORY SETTING Cut-Out Cut-In Cut-Out 3rF 40°F 45°F Cut-Out 240°F Dial Set At 44°F UNIT OPERATING LIMITATIONS 1. 2. 3. 4. Maximum ambient air to condenser is 110°F. (60 Hertz operation) Maximum allowable cooler water pressure is 150 PSIG. Maximum allowable water temperature to cooler is 75°F. Units must not have leaving water temperatures of 42°F or lower unless used with a glycol solution. 5 KEY TO WIRING DIAGRAM INDEXING SYSTEM The wiring diagrams and sequence instructions on the following pages have been devised to simplify the understanding and tracing of circuit theory. The following key shows how the indexing system can be used. 12 Line number on wiring diagram [12] Line number in text (R5) Component identification symbol in text (Relay #5) [E] [E] Normally open contact - line number location Normally closed contact - line number location @ Holding coil - line number location .& Note number SEQUENCE OF OPERATION (TYPICAL) MODELS ACWC 90-135 SO The following sequence of operation is typical for all ACWC SD Models. Refer to the wiring diagram furnished with the unit for specific information. ( ) Control Identification Symbol [ ] Circuit Line Number Important Notel With all the control circuit switches (SW1-SW3) in the "off' position and the staging thermostat (T1) to its highest temperature, Terminals #2 and #4 on the Terminal Board (TER5) must have 115 volts sup plied for a minimum of 24 hours to energize the compressor crank case heaters (CCH1, 2) [6, 8]. Preliminary Sequence Close the main power disconnect switch. Check to see that the red indicating light on the phase loss monitor (PLM 1) is lit. (Note: There will be two phase loss monitors, (PLM1) and (PLM2) on dual power block models.) This light must be on to indicate proper phase rotation for the compressors. If the light is not on, disconnect the main power and reverse any two phase legs at the Main Incoming Power Terminal Block. (WARNING! DO NOT REVERSE THE LEADS ON THE PHASE LOSS MONITOR FOR THIS WILL ALLOW THE COMPRESSORS TO RUN BACKWARDS, CAUSING SEVERE DAMAGE, AND WILL VOID THE COMPRESSOR WARRANTY!) The crankcase heater relay contacts (R3) [6] and (R4) [8] are closed and are supplying power to the compressor crankcase heaters. Power is also supplied to the chiller barrel heater (CBH1) [13). the optional receiver heaters (RH1, 2 [10,11] and the optional convenience outlet (CO) [14]. Control power goes through the control panel circuit breaker (CB1) [8] and field supplied remote time clock [36]. Check to make sure time clock contacts close during occupied modes. Start up the chilled water pump. The water flow is confirmed when the water flow switch completes the electrical circuit across Terminals #15 and #16 [38] on Terminal Board (TER5). Terminals #17 [47] and #18 [49] provide an interlock for the water pump starter(s) when either compressor is in operation. Set the thermostat (T1) to the desired leaving water temperature (e.g. 44°F.). Set point adjustment is ac complished directly on the control. Place the three (3) control circuit switches (SW1-SW3) in the "On" position, thus energizing the balance of the control circuit. [23], [33], [36]. The system will be in the "Time-In" mode for five minutes before the first compressor will start. The low ambient lockout thermostat (LAT1) [38] and temperature freezestat (T2) [38] must also be satisfied to allow compressor opera tion. Stage 1 Starting Upon demand for cooling, the first stepof the staging thermostat (T1) will be to close energizing relays (R1) [61], time delay (TD1) [60] and the optional time delay (TD3) [62]. If all the safety controls and switches are closed, (see "Safety Controls" section for more detail) the control 6 circuit for Compressor No.1 will energize, allowing the compressor to start. Relay (R5) [20] will energize, closing the normally open (NO) set of contacts [23], which energize the liquid line solenoid valve (SOL1) [23]. Another set of NO contacts on (R5) [20) provide a series inter lock with all the safety and operating controls, which will lock out the compressor if any safety trips during normal operation. (See Note 6 on Wire Diagram.) The last set of NO contacts on (R5) [48) provides an interlock circuit for the water circuiting pump(s). The fan contactor (C13) [23] will also close, supplying power to the side of the fan cycling pressure controls. (See Power Wiring Diagram.) Note: The fan motors are controlled by their own fan cycling controls and will cut in at different factory set head pressures. Time Delay (TD1) [601) has two (2) sets of contacts: the first set of (TD1) [19] normally closed (NC) contacts provide a 30 second jumper around the low pressure control (LP1) [20] to prevent short cycling during start-up. The second set of (TD1) [24) contacts in the NC posi tion power the unloader solenoid (UL3-1) [24], which hold the com pressor in the full unload position for 30 seconds. After (TD1) [60] times out (30 seconds), the contacts for the unloader solenoid (UL3-1) open and the NO set close, which energize the relay (R3) [25]. Stage 1 Modulation Upon energizing relay (R3) [25), the crankcase heater (CCH 1) [6] is de-energized and the NO contacts of relay (R3) [45, 48] are closed, allowing the thermostat (T1) to energize the load solenoid (UL1-1) [45) and the unload solenoid (UL2-1) [481] upon demand. The op tional time delay (TD3) [62] is used to bypass low pressure control (LP1) [20] for five minutes for low ambient starts. Stage 2 Starting Subsequent to the start of Compressor No.1 an approximate five minute time delay is incorporated into the microprocessor. After this time delay, and a further call for cooling, the second step of the stag ing thermostat (T1) will close. This will energize relay (R2) [58], time delay (TD2) [57] and the optional time delay (TD4) [59]. If all the safety controls and switches are closed, (see "Safety Control" section for more details) the control circuit for Compressor No.2 will energize, allowing the compressor to start. Relay (R6) [3D] will energize, allow ing the liquid line solenoid valve (SOL2) [331] to energize. Relay (R6) [3D] will also interlock the water pump starters and the safety controls the same as Compressor No. 1 circuit. The fan contactor (C14) [33] will close, supplying power to the line side of the fan cycling pressure controls. (See Power Wiring Diagram.) Time delay (TD2) will provide a 30 second jumper around the low pressure control (LP2) [30] and will energize the full unload solenoid (UL 3-2) [34] for 30 seconds then energize relay (R4) [35]. Upon energizing relay (R4) [35], the crankcase heater (CCH2) [8] is de-energized and the NO contacts of relay (R4) [46, 49) are closed, allowing the thermostat (T1) to energize the load solenoid (UL2-1) [46] and the unload solenoid (UL2-2) [49] upon demand. SHUTDOWN SEQUENCE Stage 2 Shutdown Stage 1 Shutdown After both compressors have unloaded fully and the leaving water temperature is still lower than the setpoint, the second step of the thermostat (T1) will open and de-energize relay (R2) [58], providing an approximate five minute time delay again integral with the micro processor has expired subsequent to the start of Compressor No.2. This will close the liquid line solenoid (SOL2) [33] and turn off Com pressor No.2. Compressor No. 1 will load and unload as required. Compressor No.2 will not be able to restart for five minutes due to integral time delays. If the leaving water temperature is still lower than the setpoint, the first step of the thermostat (T1) will open and de-energize relay(RI) [61].This will close the liquid line solenoid (SOL 1) [23] and turn off Compressor NO.1 as long as it has run for approximately three minutes. Compres sor NO.1 will not be able to restart for five minutes. SAFETY CONTROLS FIELD CONTROL WIRING The unit is protected by the following safety controls: 1. 2. 3. 4. 5. 6. 7. 8. 9. High Pressure (HP) Low Pressure (LP) (automatic reset) High Discharge Temperature (OTS) Compressor Solid State Module (CSTM) Low Water Temperature (T2) Low Ambient Thermostat (LAT) Compressor Starter Overloads (OLH) (optional) Phase Loss Monitor (PLM) Control Circuit Breaker (CB1) If any of these devices should open due to abnormal conditions, the compressor(s) will automatically stop. All controls must be manually reset, except low ambient thermostat (LAT) and phase loss monitor (PLM). The individual compressor safeties (HP, LP, OTS and CSTM) contacts are found on Lines 20 (CTT1) or Line 30 (CTT1). The other safeties, listed above, are discussed in the "preliminary sequence section. In addition to 3 phase power (and optional 115 volt control) wiring described above, the following control interlock wiring is recommended. The "as built" control schematic, provided with the unit, provides detailed information. Typical control schematics are as shown on pages 8-15. 1) Alarm Circuit -Terminals 6-13 (2 per compressor circuit) can be used to trigger remote failure lights or alarm bells in the event of a refrigeration failure. 2) Time Clock - All unit on-off control should be done through terminals 15 and 16. An open contact shuts down the unit. Time clock, night shut down, and energy management shut down should all be done from these terminals and contacts should be applied in series. 3) Flow Switch - The flow switch contacts should be installed between terminals 15 and 16 and be in series with time clock contacts. 4) Chilled Water Pump - The control of the chilled water pump must be worked out by the system designer. It is necessary for the pump to be on during any compressor operation and terminals 17 and 18 should be used to energize the pump starter. However it is likely that the pump should remain on throughout all occupied operation or even at night for freeze protection. Terminals 17 and 18 should not be the sole means of controlling pump operation. STAR·DELTA STARTING OPEN TRANSITION (OPTIONAL) Typical For All Compressors On initial call for cooling staging relay (R1) holding coil will energize. The (R1) contacts 7-4 close, energizing star contactor (S1) and the five second transition timer (TD5). Transition contactor (S1) power contacts close, tying the center legs of the compressor motor windings together into "Star" (WYE) configuration. At the same time (S1) N.C. (Normally Closed) auxiliary contacts open preventing (C2) from closing, (S1) N.O. (Normally Open) auxiliary contacts then close, energizing contactor (C1). The (C1) power contacts close, applying power to the compressor winding. (C1) N.O. (Normally Open) auxiliary contacts close locking (C1) in the energized position. The compressor operates in the "Star" mode until (TD5) transition timer times out (five seconds) at which time contacts N.C. open and de-energize (S1). Star contactor (S1) N.C. auxiliary contacts close, (TD5) timer N.O. contacts close, energizing compressor contactor (C2), power contacts close, thereby completing the "Delta" wiring configuration. Compressor contactor (C2) N.C. auxiliary contacts open, preventing (S1) star contactor from energizing until the next starting sequence. 7 ex> -~ H' '''USUIIlI[ conROL LOW A••'INT ,"[!twO'fI.' lOW '''n,ultt CONTIIlIOL OIL TUI"I'".. rUIIlI( SA";" 'HAS[ /,,01$ MONt TO" LUI PLU, H'.'. . 'O ounn C TOO , NO " NC f Cl "'UI ~ cl AU. 14 I 51 (I 5"~U' -~ DELTA START DETAIL" A" COMV[N'f,..e£: SlAM ~ COl TO' ,. TO) ~ jllfM'1 21 ZtA ZOI LU .. & 'OA III[Cll\"[" H[Ut" '''USUIIll[ CONTIIOLS ~tCtJVIIl: N(AUIII '14(""0""''1 "wI: DtLAY& LOW ""Utu". LOCK our rt .. ( O(L ... '.'I....NSlTIO ... COHTA('TOIl: (O"~"USO" COH'''''Olll • iTA" OlL ... IUCIIY[1II H[AUIIIS "H.OT LIGHTS CUtCUl' '''[&1(('' -"(criVElli Kuru CIACUff 'AUK(jIIf • CO"\"["I("C( OVTLlT (ONUOL IfJll ,AIrIS UNLoaot" ,OL(NOID • (OM,,,n,oll, '" I..."o,ndtlt THUMOSTn -LOW n"'llIIUU"[ TtItWINAL 10&1110'c unowEIt ."UNI J Tl'UflUl 10"'''0 -'''CTOIII., WIlW.O. TlM[ HUT' calli! CONT•• LOW 'I£n. L.OCC 0\1.' 'LI· , .H' I ....,--- ., J rI CtftCUlT I J... A...... CNlCUl'T 1I - ,w' It...,. •• l.!f 0 on OIS ~' til 11 OLHJ, .",,.,,I[D 01.."1 COMPRESSOR CIRCUIT I l.OO,IOH.L"- - - __ J 1M "n ,OLMI - - U WI HZ CUH' ~ ., O' ITl~ll "'ll ----ij.- --, •• , -.... I .1"tD .MIN r> • f' N / I ,I lI... J """"-<l'" ~~ ~ - _ WTI~AL I I 0' 'I <:» II. I JI ... -"!lJ.. i'OOw _ W.T 01 Til so lie NO we T' II. 1,..4 1111 k .. ~ "' TO) -..4" • ItS fll '11" "VIoJ·' "~Ll l v • o. WHT .HT - 0[0 t;\ L. tB ill CI)' :I: ' tON"L ~:r.- --1 MillI ~ r- I "HT HTAIL·.~ III01l~:: tMOwN CI ..J .& 1& ..u.' I~ ! .L1}-i,r--------,I Q"~~A'" f' "'1 u., I ~ : .. TH ! .., I L-.!ll~_ A -., ... .1 ~O}I 10 rc TOt O'''OHAI.~ r-- I 2."!!!':::N.~~~.,~----------= I==~===~I =: ... ~J .. II If II .. IS tt .,'0 II II If II oS 11 It II 00 ~i ~ ,. UI Ijlf - -_- - - - - - -O.OC"M - - - - - - - - 0." - - - -.... - - - -'!.!lL ----, l! - -.[0 ""cu ... \ cal I IL OI'''ONAL r----------, Q I I en coo J ... - - - - - - - - - -..... - - I r- L rO~'!.2:"~L, I.. • & I fH("MOSTAT· S[OU[NeEIt I ~ ) Cit ! • ... : ~~ • 'LOII 0\.'....·5 LLTl ~*(. tU'IILT IISV/IO",,/I' WHIt[ SWITCH' "'''STEN SWITCN"COW'''U'D'' C'''CUITS '(;,L[NOIO· L.lOUIO LINI "(LAY· tNUftLOCK 1t[L,U-U'.CITY ~"'OL • CI...,.,ltC,,5I: lllELAT· tTAGIHO HOUA W(fIAS LOAO LI.. ,T '"(IIIWOSTAT O\"(IIILOAO "fUUIS CI'I ..., en ell O"IOHAl _....... Ul.I·Z TO' TIllS! T[lIl S Tl '10. " ,w, SOL.I ,0) ... .11 enst VI c:o..,."U,OIlll esr ... "PI SOLID 'TAU' MOOULt CHllL.r:. . . .,UlU "[ATIII CUNe(ASE Hu,n" elHI CCHI (,"CUlT· '''£AMIII • CONT"OL ('''CUlT CUtCUIT ."U«III .. HIATEItI CONTAClO"· 'ANS CU•• el) el' 1 "'m rr •• -'-' COHTACTQft· (:0"""[5101t5 CI-Z LEGEND s'aNO"IIlIG G> cn 0;;0 Z c:e ...... r e 0 --I ~;;o U'lz .1::0000 ~ s:~ o o c.> (I) r inn <0 'OWIIt DllQ'U." '0'1 COMU,CTI AND S t flit,,,., WILL ALSO LOC_ OUT (\.let.U· VONIN""ILf PO" CO"'•.••. 6 o 6! o c. CONUClI WIf" l.IN( NO. NOTt "ITH L'Nt NO. N. 0 CONTACTS WItK liNt NO. N. HO,-O'NG COI,- Wit" 1.1N( NO. GUION AnONS 11 nMH,,"'u"l UNI()1II MUST HAV( SHllLDID CA,U I' LOMe" T"'" II no; OR: ItUM W'TM ItOWI" LIAH. uri NT IT H-'"", IT• •""O ",N''ft. 0-' '011 '"" ."II~"T KITI. lU..urD, .'ttl III IICOMa-aU,. Y SUI. to. '0 COW"'•••• ."10" \,.OCATID .11 WHEN u.TI It NOT '0fII ..NO IIlETUIIPt W4TP LU.. •. LLTI lIT AT .0'" CON.... CTO" WUUHO 7. :~::S:lt~1 ~~:,,~:::~'::( 1:.~~~~t:l!D;O:O" 0'" CALL'! WHIM ""' IA'ITY TH[I( CON· '"OLI CAJrf II IIEMT IT TUft"I"1 tWITCH •• "DU. 1111 .. COW,III:ISOR MODULES dC NOM·AU",VAT.C So ,,'Crt,. TO ."00 MANUAL ,all HT,OtNT AND ~1"0l IANO !M,TIIUCTtONS. IIrCO ....tNOm IMIT,AL COH'''«. ""0 'UTI"I It 4. •• '011 UOV "HAIl LOIS »ON.TO"S, TElu'rNAU • AND' 0111 , .... IICO"( I AND' AU,(CflY£LY. L.OCUID 1M ••'U OUTUT. 1 ,. AND '1 nWP(IU 'ultl S(NICtf'1 .... I I. '111'114"0""(" ,"U II NOf TO I( ."CuNOIO ON UtI: seCOHOUI' liD(. sn ... ,N I. 'Olt C.ONTACTO" COILS CI-I • CtS ~ r~T~- .. no. ~ ~ " I I .r:» "'~"'~1 I I wUIIII I ,.,,., C"ILLlfi I ITA"f[1II ,ItVN' IWITt"i I I I I I r----- flOW 5WlfCH C"ll.l.(O ..41(" ~--- IC"tMQT€ COMTIt01. TIM! Cl..otll.' I ": ': ,& ., V I I 14'1 100 OK__ STAG( ~: ~: ] 0) unl..ln OJ ,,[..ou ,urO'NT 01 0 ~ ~ C \:..J • & (j\CO~'_ ~ T! !-t C~P W U . rr. CO:L~ 4 00"" 10 "0 10 COOl.. • V'LOAO:r-: In ,o,,.y ., 0 'CO Hit 1.0AO CO...l.01.. ."NO·' ] CM'NG( avrlt • Joun • 0 10 rCOHO 0.1 f" fill .00] g 1 " . 7100-' . ] CO'D' lJ.-L7 1'0 OH" f TANI It" 00. ~ I ~ I I -I 5_1 I I 11I1 III _~ n' ~~ I._ I I I ._. III .'A vu·, VL'" lIT IS 01 II '0 •• II 17 . II . u 01 II 10 •• •• .7 •• •• I •• AS ., ., '0 so so S1 ,. IS -I .., -< 0 G> Z c:;tl CIJ- Q:E ..... r t: ~:;tI UlZ .+-1 ~O iii" 0 s:::E o 0 c.» CD r -I o ~ tlNI .OLENOtD...LlOUID LINt '."C"'''(OM",IIIOII (,lIIieLf'" THI.IIOIT6T· SlOUl.CU 'MC""ot'., ..LOW TlM'e""U.1 IOLI'S IWI·, I. I TI n CO, TI"M ... AL IO""D" 'o\C'0It1 .UIINt TIMe OCL.U·CAII! CONT. a LOW 'IUt. LOCK OUT 2....~f DELTA START DE1AIL~" ...r 11:::. II. II & II 10' t 10. CIJtCUIT '.UIIlEIt .. ftEC£IV!E" HIA'I" ('''CUIT .1IIUIIlI:1II.. CONY(NIENCE OUTUT CONnlo\' .01 'AN$ HOYIll MUI"I l,.OAO LlIlIIT TH(" .. OITAT OVC"LOAO MIAn"l ~HAII: LOIS MONITO" ~f"OT LIOHTS "ICIIVE. HEUE". "rCIIVE" MU.TlIt 'ltIISUIll( CONTItOLI "C:CC:lvllt NEAfllt T"l"WOSTAlI TINe HLAY" LOW ""Invltl LOC"" OUT ftlll. DUAT· T"A"SITION CONTAC TOIll CO.... "(lIO" CONTACTO'" 'TA" Dnu COWCtllltNCI ountT ' ' 'N,PD''WIU' UNLOAOlilt 10L(NOI0 .. CO"'''IIIOIllI STAR ) "'"Tl·1 TOJ· 4 1'Ot-1 $'·1 ""1"1 ItMlI'Ct·l OL""'" "L,1lI1 "LI· J lLTI Mill 1,,1 CUI COl cn Oft'lo",tL ULI·a '''st TO'· I fl• • TlER"'••L lOAJIIO·CUlTo .. tJII WUUNt WI eM- ""UIER MU'''CANc.n CO'fTltOI.• C""NICCASE ",ItS ItILA'" INTI"LOCIC It .... 4 •••• fllLAY .I'AOINI III,·a OU.. n ..,ru,'ulltl 'AnTT LOW Hl:I:IIUIII COftTJlOL LOW ' ....e.T fMllltMO'TAT "USU'I CO. TOOL 'HA. ,-0 •• MOHIfOIt a Nt C"'N«CAU NCAn" CO"""UIO" 10LIO 'TAU: MOOULIE C,"culT 0111-1 11'' 1111 loP." ""--1 LAT. csnu·a CCHI·t CI'CUIT "UNI.· HUTI" eNU"LlIII '.''''Il. "IAUIt C.IICUfT ,IIICAICCIII .. CONTJIIOL CONTACTO"", ..., CII C.' cn • CONlACTIM ~ COlllfllltUtOJII, LtGEND Ct- 4 tUNoalllO _.---".... ALA" .. ,NlCUfT ClflCUIT I I I AUR.. CIlltCUIT CIRCUIT' I , I• 'OWE" IV'''-' utv/lO"\f!I' "'1IllI 1IU-- 10$ t. I , 1.1 ,., I 1& / I I Ill~ "I J ~ -. J - t- __ !oJ.! __ Ill'" .lD ""-. --, oJt )~II ~ -. ~l A- .JI 0' "OHA I. ~G __ :: _~L:_J II.,AIO r.--- COMPRESSOR CIRCUIT 0(0 oj/o WHIN JU'''L1l0 'I I OLMI OL"' O'T10NAI. IL~ro OLM' I' WlllltO CII ;: .!"~".!.L_ -""7. - Cit O'TIO.... L •• •• I • I TO 140 "' " J - ... lOLl ITI I I (CIS) ""T __ ---------~~------- -:r:- -.....et L O"tONAL il------~---l ~~ --~-., L __________ C O I..f.!._J I rI I ... I r I I r- - - - -10,- 10. I" O"IOIllAL, r----. I IL ___ b,..... : ' I ' ', ' I I I 'f'B, I I ILK'S r", L PL.. ' ell ----!!.!!:. prIlgjf~, "ITI T I &1 ... &. II' ~ + t t >0 •• 27 ....•• . II .." '0 II II II ., IS I. IS II II 10 ~li ) G) Z C~ ~:E cn- ....e ,...0 °z :r-l ., ::0 (") CDo l/I ~,... -I -< 3:::2 o o Q.» ...... ...... ...,-.... STA~T In .... 'N "OWl" 0"5111." ,~ IZ /'\. JlALD 10-' AND . .10ft II NOT 1V"",lrD. wllII[ toIlICOMn v .." 0·' LOW MI._' O. CONTACTS wnw LINI NO. N. C. CONUClI WITH UNI NO. ~ fItOTI .,," LI"I NO. A '"'ILOID "'A""" UIIITI. lOTI. ve MOLDINfl COIL .It" LtNI NO. o .. Q o DESIGNATIONS P'CA _ 'I TlNH:"ATURC SlNSOIt MUtT " .. C"ILC. .,,,. til.. LU' " KT IT LOCATUI II 1t11VMI _Tat. WIN LUI" NOT SU'PLI.D, WIIIIC OJ lleo. . . It. WMIH ,,-.,2 " WI'" _ no. .. " I " ~ I I I t"~"'~1 1"".."SWlTCHI I I , •• I :~~,. t "'.." I , I j r----- 'LOW SWITCH '.ILUO .ATOO ~ l'lItt".,( c"oce. 1.1.1 r~T;"'T"~"I MOTI CON JOI LD'" I JI C'OIfTACTcUt W,lIt,Nt: COM"• . • ,. HTolIL ... ,0'1 COtf"CTO" .''''HI "'lIt C.'lt.•I.ITC. II. LATI . . AT 10'" 10 t • ~:r:.I~~ ~~: ~~::T':t:I:c~~I!:~D;:' 1. ,b" COM"1II1t1O'l MOGULI. N(tN-aUTOMATlC flan. flS" • • '1.1. ALSO &.OeM·OUT luerllt,· CAL"'Y WHIM AN' IUITT TIIIIP,. TMUI CON.. TflOLI CA. . . . lItUI1 IT TU"NING ,WITCM.' 0" IlIOWlflITA"'L' fOtt CO"'lIt• • '. ,wITCH_. on WONlflIT.JIIIL' POllt COW"".• I, In:. a , • . ANa "rco....rNHD IUTI.... S ""I: INITIAL CONTlIIiOL ....fIII0 .t "OINT 'HA.I LOSS MONI'O"., n'''f1Na.... • AND' ON rc... I(COM( f AIrfD I lItU,rCTIY(U. 'GlIt nov TI AND TI TI"'.""'U"I IIN'OIIt ..". LOCATIO IN ...nlll: GUlUT. ,. lItc,rlll TO ."00 "ANUAL ,.,.. COfrtT"OI. UND INS'ttUCTIOtrl.. (I I ON 'HI SrCONOAIll'f StOl:. lOa I II-I. CONTACTS. 'Dill CONTACTOIlI COtLS (1·4. (IS·14 AND I ----, DELTA ~ I. f""HI'O" .. !:" Uti IS NOT TO IE alllauNDIO I ~ C"UK OZ'UK )--11- 0 'TA~ .a_NI 4000HN CTAN) '100"" .-. :::". ,wi 00. I I '[COOIO ... ICy ] "AU 01 0' Of 01] e s IAULIt. .,·J tUPlOINT "IMon 4 ]IIUft • 2 lOAOt--O a"TIONAL L1It- .. - .J fA 0 '' '' co CONTIlIDt. I"NO-' v ~ I fj\COflP W iI I _ _ I ... rl: u,- ' £ WHIT I ...ACK '0~r=: u WfIOO" 010 ] , ("'NGI 0'11" 0· 00 01 TO "J - ,It TI lS. CONP~E~)CUlT ILK ' 1.1 • I •• n' f n' \ IlU 01 o;iiO'NAt I rA; I ~ II .. .. .0 II II 11 I' 10 f. f1 .. f. '1 ff f' f. f' 00 .1 II sr i. .~ (;) z C~ t::E CJ) ~r- l: ~;;o 0 °z r+-i o ego 1Il !or 1:1.» ~ :5::E o o ... ~ . :~ .. -. :... ~ ~ ~ .. .;~i• .·s. ~ !: .. ! r------~, 1-'" I I I :J,J I I I I I I , I I , I I I I IL. _ _ .JI I I I _.J ... .. ~ I I: : = ~ ~ • : : ~ : : % =:~I;;:; . ;: ;; a • • ... a • .. ... • as coe ruq; SV~ siapow ~NI~IM lO~.lN03 lV3ldAl. 4 .i ~ 1I .. .. !~FirI1 u'~: III, -.: I I _ a .: ! ..... 00000 - !:I:=I:::I~I~~~:::;;:~»,I!I:I:"!!I.:!tI:I'I~.&I~ as ooz nJ4l sv ~ siapow ~NI~IM lO~l.NO::> TV::>ldAl ~ .j>. ...... ...,, nc.IIOff.... LOW . . . . . . . COIITINM. LDW MlMtrf ........... COtI,... ~C . . . . . . . . . . ." eM.ca....., .. CI"",rr .......... .cAfE• QtILU. . . . . . . . . . .TI1I ,MI. IIII."t,Y·CMOOC. LOW TPIIIU"'LIOMI-'ACTCNtf Wi.... 'ICIIYI'I ,,",... iiiLiiUiiii ~LDM fIlAR" PMI& LOll . .lTV. .....U.' TMI•..,., ~..,.U, ea-t:UlT 1ItU••lI" ooww:lIttlff'c:e OUn.n c.TIlGI. Ie:- , ..... CMUtT 1M."." "ClIYDl NCAfill ..LOAM. 1Ot.I1tOlD .. CO.........OA. U*(OUf n- ..".. iii OUfUT D[TA'~ .O(no)"" D[~TA STAIIT ~ STAN ..... -.' STAN D(~TA ITAIIT "' ITAA OEL.TA ITAJIIT DITA'~ 'A' coww:..... !!!T ~-':4t:iiT::::::' ~:'" • ~ . iii=ii ..,-:- '.we ••,.. ~ IIRII'IIJt ....T. . HllII"'AIl CO«f..... ~ IIICCIVP .,1T1lt '"C••OffATt 'iii:'i &.OW 'IC"" .... IUT "",." ;u:'i ';Uii" U3I iLiii=i' ;;t;::; CiPi'=i ~ HIe. nll."-' "'D-CUlTQIIUt W'''''' 11II."_"'·LOW TIIIfN".TUIlIC lIl_ ...."N ..COW'UUOItC...UllTl • • 01· .... lit TMCMI08TAT .. tc_ltCIlit lOLl..... t..NIU_L'" .UY·I.OCI* ......,..CAMIm' CIIIII'.DL • C'U_CA• fllU.Y" _ftMOea ItlLAY.. ... - flU-" .... "'' I.... fI .... " o. aw, ... , "-II 1t1S-1. .. ... 'n·. 00-. MODIAI. CMCUrT IItIMIA .. co-'lto.. c.-cVIT CC*fa,CTOI:.. cown...' COIITACToa.., • • l£ItND ClL n ....."TU.. U,." "'1-4 ..... , "".LOte ..,.• n ..... ~ LA" .. CIT"'-" ...... CC".... C,-I CIS-I. .. _- ..• "......lIt. co_. M.AMI eNtalIT ... If -~ .. & III _T. ........ .. •r IOA~ .. .1\. II. .. POWI" ......., III./IQ"W'" ., 10 "II n ••·- " , •• .. ....., , I"' e.. wo, '1,& I A ... a"'~ .r '" .. J at~'04 .., .N 5---, 0/.. CO..,NUSOII CINCUIT Z ... .. '" ... .., ,. "' .. , ------------------- ---- - ---- - - ---,...... co. r-~-!·!--=-~~' IL C.6 J = _J I I L I ~.1I r~ • I I COM""USON C'NCUIT , I '-~ I r0.t"!2llJ.... I'- ~ oJI • II I'" I ~ • I&. ~ I It· rn"~ co. U__~ r~----Ef1 . ..•• .. ... II .r u .0 II .. II II IO , If .. II . •• II II " to 10 " I." If I. II II " ~. » G> cZ cn:;o g:e N' :f" c:: 0 ~-1 UlZ ~O .... () Vi' <D :s:~ o - c.() ~: I: ~ ~ /I ,. ,. [>O(]O ! : ~ ! i ! i : :Ii ~ i • ~ ~ : ; il 2 ! I ,. 2 a ~ iii ••• ! ! I::: I! I ~,,~.: =:;l;: ~ iI. I ~:: I I I!!: I:!t I: 1111" & ~~ as ooz nJ4l SP~ SlapoUII ~NI~IM 10U1NO:l lV:lldA.l TYPICAL POWER WIRING Models 45 thru 70 SC --.... -. I,'01 :: "I ,Ii . ~. _ I -ti-' , " .~_- rYl31 lniJ ....-' "'': . :. LII•••• PC _ & - I I... _ . . . - . - - . . . . . . ~ TYPICAL POWER WIRING Models 90 thru 135 SC - ...... .....-.--.. ~rfh.: ........ _" .........Tt . . . . . . . . . ".c.~ tP ~ "!!'_III ... ...... --- _ II!lJ , • .... .... "'"- . . . MIl M'f _ _ • .. - _.~--~ 16 "Ie ~ ------- .- ...... I\" r-- ~ TYPICAL POWER WIRING Models 145 thru 200 SC _. _ .... --...1a1' . . . . . . . . . . IIUrI: . . ...,.. . ·rFti~v • , !i I I ...... ... I r:-~ ,r;, .."............. ~,~'~' i~i .TaII..".... IIOMLI tN T",", 100 WTIOII.... ~ 011 lilOOCL, t::1.... .... a. L t I ••• ' ~ ~, ~ ....... III 2 !!Il!D -- ........ --- C!·ClM . . ~ eo teO ac CIKUr1' .~ .......... - hJ'OH.r I t. "" ~ ~l ~ ....... TYPICAL POWER WIRING Models 215 thru 265 SC --rt-h l •• ---au ItUU I -i c~ A a ' I "~Mfl 'III; !;nII! ~/-,t:-'-.J rn 11 1_ . i f1 !.f.t fi i- ~~m, ' ~~~ "" . . ~i~-~ --rt-f, 1D....,. Wll;:1U.1I. fIa. -.:rMI: r;;~ I " • c lli'\.'" =.. ~~~.CI1 ~uf""" .'R~~"'" 'LL~~"'-" ~ l'~"t ~~ ..~!ll!!,A!,i4I 'IrMi' luv'"~'" • .. I ... • it .. d. " ," Lll-l~j ~nL 4111 I '=, '=' '! WlJj litI ••• I UGEND ~!! -. , L . , ._~~~ I !!2!!! ~ (11_1 ~ H.~ ... " .. . . . CUlTMIt. tff'C_) . .Ll"" N" .. .. ..-r_ 0# 1ItCIIIl'0A'I lllQUlllCo.. as -.0-. • ."•• fI PC:.. ' 110' lNJCll,II a Olil 1100£1. II'; 111',', 'el",' 1101 ItCOU_' 011 IIOOI:L140. I. , ... I.. '011 CI-('. H[ (;0"'110\. (fMCun - - - 'l(lD .IM,•• ."u•• '"........ --".CTOtt'..",•• L ~l .OJ c..~ ~~~--- ~:), ~·"I .. ~._.J _ I__ Ntl'f 110. e414-7 17 ELECTRICAL DATA Model ACWC SC Volts 60 Hz 3 Ph. Type of Start 45 208/230 208/230 208 XL YO XL YO XL YO XL YO XL YO XL YO XL YO XL YO XL YO XL YO XL YO XL YO XL 208 YO 230 XL 230 YO 460 XL 460 YO 208 208 230 230 460 460 208 XL YO XL YO XL YO XL 208 YO 230 XL 230 YO 460 XL 460 YO 208 208 230 230 460 460 XL YO XL YO 460 460 55 208/230 208/230 460 460 70 90 110 208/230 208/230 460 460 208 208 230 230 460 460 208 208 230 230 460 460 125 I 135 145 160 XL YO COMPRESSOR Qty. RLA Starting Curro Ea. HP Ea. 1040 178.8 (1) 50 178.8 347 73.7 422 73.7 141 205.1 1228 205.1 (1) 60 409 90.4 485 90.4 162 208.3 1415 (1) 75 208.3 472 97.4 539 97.4 180 178.8 1040 178.8 347 (2) 50 178.8 1040 178.8 347 73.7 422 73.7 141 205.1 1228 205.1 409 (2) 60 205.1 1228 205.1 409 914 485 90.4 162 (1) 60 205.1 1228 (1) 75 208.3 1415 205.1 (1) 60 409 (1) 75 208.3 472 (1) 60 205.1 1228 (1) 75 208.3 165 (1) 60 409 205.1 (1) 75 208.3 472 (1) 60 90.4 485 (1 \ 75 97.4 539 (1) 60 90.4 162 (1) 75 180 97.4 208.3 1415 208.3 472 (2) 75 208.3 1415 208.3 472 97.4 539 97.4 180 (2) SO 178.8 1040 (1) 60 205.1 1228 (2) 50 178.8 347 (1\ 60 205.1 409 (2) 50 178.8 1040 (1) 60 2011 1228 (2) 50 178.8 347 (1) 60 205.1 409 (2) 50 73.7 422 (1) 60 90.4 485 (2) SO 731 141 (1)60 90.4 162 205.1 1228 205.1 409 (3) 60 205.1 1228 205.1 409 90.4 485 90.4 167 FAN MOTORS FLA LRA Ea. Ea. (4) 7.0 (4) 38.0 (4) 7.0 (4) 380 (4) 3.5 (4) 19.0 (4) 35 (4) 19.0 (4) 7.0 (4) 38.0 (4) 7.0 (4) 38.0 (4) 3.5 (4) 19.0 (4) 3.5 (4) 19.0 (6) 7.0 (6) 38.0 (6) 7.0 (6) 380 (6) 35 (6) 19.0 (6) 3.5 (6\ 19.0 (6) 7.0 (6) 38.0 (6) 7.0 (6) 38.0 (6) 7.0 (6) 38.0 (6) 7.0 (6) 38.0 (6) 3.5 (6) 19.0 (6) 3.5 . (6) 19.0 (8) 7.0 (8) 38.0 (8) 7.0 (8) 38.0 (8) 7.0 (8) 38.0 (8) 7.0 (8) 38.0 (8) 3.5 (8) 19.0 (8) 3.5 (8) 19.0 MIN. CIRCUIT AMPACITY Circ.2 Circ.1 252 252 106 106 284 284 127 127 302 302 143 143 266 266 266 266 187 187 312 312 312 312 231 231 - RECOMMENDED WIRE SIZE Circ.2 Circ.1 - 250 250 2 2 300 300 1 1 350 350 0 0 300 300 300 300 000 000 400 400 350 350 0000 0000 - - -- - 224 224 224 224 - - 256 256 256 256 - - MAXIMUM FUSESIZE eire. 2 Circ.1 400 400 175 175 450 450 200 200 500 500 225 225 400 400 400 400 400 400 - - - - 0000 0000 0000 0000 - 300 300 300 300 400 250 250 250 500 SOO =1 :;g 450 450 - 500 300 300 (8) 7.0 (8) 38.0 312 260 400 300 500 450 (8) 7.0 (8) 38.0 312 260 400 300 500 450 (8) 7.0 (8) 38.0 312 260 350 300 500 450 (8) 70 (8) 38.0 02 260 350 300 500 450 (8) 3..5 (8) 19.0 240 - 250 - 300 - - 300 - 500 500 500 500 300 300 450 450 450 450 500 (8) 3.5 (8) 19.0 240 (8) 7.0 (8) 7.0 (8) 7.0 (8) 7.0 (8) 35 (8i 3.5 (8) (8) (8) (8) (8) (8) 316 316 316 316 247 247 38.0 38.0 38.0 38.0 19.0 19.0 260 260 260 260 - 250 400 400 400 400 250 250 - 300 300 300 300 - - (10) 7.0 (10) 38.0 326 402 400 0000 (10) 7.0 (10) 38.0 326 402 400 0000 500 500 (10) 7.0 (10) 38.0 326 402 400 0000 500 500 (10) 7.0 (10) 38.0 326 402 400 0000 500 500 (10) 35 (10) 19.0 295 - 350 350 - 10 (3.5) (10)19.0 295 - 350 - (10) (10) (10) (10) (10) (10) (10) (10) (10) (10) (10) (10) 326 326 326 326 329 329 462 462 462 462 400 400 400 400 400 400 (2)250 (2)250 (2)250 (2)250 500 500 500 500 400 400 38.0 38.0 38.0 38.0 19.0 19.0 - - 350 I - 500 7.0 7.0 7.0 7.0 3.5 3.5 I 400 600 600 600 600 - NOTES: 1. XL: Across the Line;YO:Star Delta 2. RLA: Rated LoadAmps (rated in accordance with ARI Standard 590.) LRA: LockedRotorAmps 3. Wire Size Amps equal125%of the ratedloadampsfor the largestmotorin the circuitplus 100%of the ratedloadamps for all other motorsin the circuit, per N.E.C. 4. Wire size based on copperconductorswith75'C. insulation, perN.E.C.Table310-16. Terminal block lugs are sizedaccordingly. Use of oversize wiring may not lit in terminal blocks. 5. Maximum fuse size is basedon 175%to 225%of the rated load ampsfor the largestmotorin the circuit plus 100%of the rated loadampsfor a other motors in the circuit per N.E.C. VOLTAGE TOLERANCES: 208V-230V: min. 187V.,Max 253V 480V: Min.414V., Max.506V. 18 I 'I ELECTRICAL DATA Model ACWC SC Volts 3 Ph. Type of Start 208 XL 208 YO 230 XL 230 YO 460 XL 460 YO 208 208 230 230 460 460 208 208 230 230 460 460 208 XL YO 208 YO 230 XL 230 YO 460 XL 460 YO 60 Hz 185 200 215 COMPRESSOR Oty. RLA Starting Curro Ea. HP Ea. (1) 60 (2) 75 (1) 60 (2) 75 (1) 60 12\ 75 (1) 60 (2) 75 (1) 60 (2) 75 (1) 60 (2) 75 XL XL YO XL 265 (4) 60 YO XL YO XL 240 208 208 230 230 460 460 (3) 75 YO XL YO (2) 60 (2) 75 (2) 60 (2) 75 (2) 60 (2) 75 (2) 60 (2) 75 (2) 60 12\ 75 (2) 60 (2) 75 XL YO XL XL XL YO (4) 75 205.1 208.3 205.1 208.3 205.1 208.3 205.1 208.3 90.4 97.4 90.4 97.4 208.3 208.3 208.3 208.3 97.4 97.4 205.1 205.1 205.1 205.1 90.4 90.4 205.1 208.3 205.1 208.3 205.1 208.3 2011 208.3 90.4 97.4 90.4 97.4 208.3 208.3 208.3 208.3 97.4 97.4 FAN MOTORS FLA LRA Ea. Ea. 1228 (12) 7.0 1415 409 (12) 7.0 472 1228 (12)7.0 1415 409 (12) 7.0 472 485 (12) 3.5 539 162 (12) 180 1415 (12) 7.0 472 (12) 7.0 1415 (12) 7.0 472 (12) 7.0 539 (12) 3.5 180 1(12) 3.5 1228 (12) 7.0 409 (12) 7.0 1228 (12) 7.0 409 (12) 7.0 485 (12) 3.5 (12) 3.5 162 1228 (14) 7.0 1415 409 (14) 7.0 472 1228 (14) 7.0 1415 409 (14) 7.0 472 485 (14) 3.5 539 162 (14) 3.5 180 1415 (16) 7.0 1415 (16) 7.0 (16) 7.0 1415 472 (16) 7.0 539 (16) 3.5 (16) 3.5 539 MIN.CIRCUIT AMPACITY Cire.1 Cire.2 RECOMMENDED WIRESIZE Cire.1 Cire.2 MAXIMUM FUSE SIZE Cire.1 Cire.2 (12) 38.0 341 469 500 (2) 250 500 600 (12) 38.0 341 469 500 (2) 250 500 600 (12) 38.0 341 469 500 (2) 250 500 600 (12) 38.0 341 469 500 (2) 250 500 600 (12) 19.0 352 - 500 - 400 - .5(12)19. 352 - 500 - 400 - (12) 38.0 (12) 38.0 (12) 38.0 (12) 19.0 (12) 19.0 (12) 19.0 (12) 38.0 (12) 38.0 (12) 38.0 (12) 38.0 (12) 19.0 (12) 19.0 (14) 38.0 345 345 345 345 359 359. 504 504 504 504 225 225 504 469 469 469 469 600 600 600 600 (14) 38.0 (2) 250 (2) 250 (2) 250 (2) 250 504 504 504 504 225 225 525 500 500 500 500 500 500 (2) 250 (2) 250 (2) 250 (2) 250 0000 0000 (2}250 (2) 250 (2) 250 (2) 250 (2) 250 0000 0000 (2)300 500 500 500 500 450 450 700 700 700 700 300 300 700 504 525 (2) 250 (2)300 700 700 (14) 38.0 504 525 (2)250 (2)300 700 700 (14) 38.0 504 525 (2) 250 (2)300 700 700 (14) 19.0 225 248 0000 250 300 300 (14) 19.0 225 248 410 250 300 300 (16) (16) (16) (16) (16) (16\ 525 525 525 525 248 248 525 525 525 525 248 248 (2)300 (2)300 (2}300 (2}300 250 250 (2)300 (2)300 (2}300 (2}300 250 250 700 700 700 700 300 300 700 700 700 700 300 300 38.0 38.0 38.0 38.0 38.0 38.0 - - - - - 700 700 700 700 300 300 700 NOTES: 1. 2. 3. 4. 5. XL: Across the Line; YO: Star Delta RLA: Rated Load Amps (rated in accordance with ARI Standard 590.) LRA: Locked Rotor Amps Wire Size Amps equal 125% of the rated load amps for the largest motor in the circuit plus 100% of the rated load amps for all other motors in the circuit, per N.E.C. Wire size based on copper conductors with 75°G. insulation. per N.E.G. Table 310-16. Terminal block lugs are sized accordingly. Use of oversize wiring may not fit in terminal blocks. Maximum fuse size is based on 175% to 225% of the rated load amps for the largest motor in the circuit plus 100% of the rated load amps for a other motors in the circuit per N.E.G. VOLTAGE TOLERANCES: 208V-230V: min. 187V., Max 253V. 480V: Min.414V., Max.506V. 19 006 009 00" 0;;: (Wd~) 3.lV~ M01::1 ~3.1VM OOt OOl: OS L. 00 L. os 0" Ot 'V ::D m (I) (I) c: m :D c :D o'V ." m m -t o ." ~ ~ m :D aoao 3~nSS3~d ~3100~ APPLICATION DATA POINT LOADING rMi I A *, 1 5 *1 ACWC 45 THRU 10 SC COMPRESSOR SECTION 13'10 CONDENSER SECTION ._ 2 • *1 *4 ~ 1 • A .... *, COMPREIlOfl IECnoN *2 , *J I'·' . CONDENSER SECTION , -, *4 ., A 45 55 70 90 110 125 135 145 160 185 200 215 240 265 91 91 145 145 60 60 60 138% 1383/0 138% 138% 106 106 133% Dimensions B C D - - - - - - - 40 40 40 74 74 129 129 82% 82% 110 160 160 160 107% 107% 107% 107% 106% 134 134 - - 80 107% 107% C ACwe 110 THRU 200 Ie 13'10 Model Size *5 1:..1 Model Size 45 55 70 90 110 125 135 145 160 185 200 215 240 265 Loadlnu (LBS) 1&2 3&4 765 585 705 810 660 890 1025 1500 1195 635 1255 690 1255 665 1330 2380 1330 2440 1235 2575 1275 2635 1010 2270 1115 2550 1380 2980 5&6 550 635 700 1175 1525 1835 1880 2160 2280 2980 3020 2590 2870 3515 7&8 9 &10 - - 995 1115 1105 1450 1515 1360 1380 2240 2715 2750 - - - - - 840 1125 1175 ... , ACWC 2t5 THRU 215 SC 13'10 L " · .. 2 ,,4 lIf' 11" to I..I i, 21 TROUBLESHOOTING GUIDE CHILLER UNIT WILL NOT START REMEDY 1. Check main disconnect switch 2. Check main fuses 3. Check the wiring diagram 4. Tiqhten all terminals 5. Check phase loss monitor, flow switch, circuit breakers, temperature control, low ambient thermostat, low temperature thermostat, remote switch, etc. 6. Wait POSSIBLE CAUSE 1. Power off 2. Main line open 3. Incorrect wiring 4. Loose terminals 5. Control circuit open 6. Time delay COMPRESSOR HUMS BUT DOES NOT START REMEDY POSSIBLE CAUSE 1 a. Check at service and unit for loss 1. Low voltage b. Consult power company POSSIBLE CAUSE 1. Refrigerant shortage 2. Restriction in liquid line 3. Low water flow thru cooler COMPRESSOR CUTS OUT ON LOW PRESSURE SAFETY CONTROL REMEDY 1. Check for leaks -- add refrigerant 2a. Plugged strainer - dean or replace b. Liquid line valve partially closed - open valves fully c. Expansion valve clogged or inoperative - clean or replace as required d. Solenoid valve partially open - clean or replace as required 3. Check water flow thru cooler and correct as required COMPRESSOR CYCLES ON HIGH PRESSURE CONTROL REMEDY POSSIBLE CAUSE 1. Compressor discharge valve partially closed 1. Open valve fully 2. Operate condenser fans with compressors off. If condenser 2. Non-condensible gases in system pressure exceeds saturated pressure corresponding to condenser entering air temperature, then purge air from discharge line. 3. Purge system while in operation until head pressure reaches a 3. Overcharge of R-22 normal level 4. Clean the condenser 4. Dirty condenser 5. Replace if necessary 5. Compressor discharge check valve not operating properly 6. Check pressure control setting 6. Fans not running CAUSES AND PREVENTION OF FREEZE-UP PREVENTION 1. Charge per manufacturer's recommendation. 2. Check the safety time delay low pressure control for proper setting at the beginning of each season. 3. Use an ample sized cleanable strainer in the chilled water circuit. Improper chilled water circulation Make certain the strainer is clean to insure full flow and velocity of chilled water. It may sometimes be necessary to treat the water to prevent formation of deposits. Not draining for winter shutdown 4. When the system is shut down for the winter, remove the drain plugs and drain the cooler. Blowout any remaining water with air. Improper pump shutdown 5. Make sure chiller barrel heater is working and flow switch is installed per wiring diagrams Low ambient during air conditioning season 6. Make sure chiller barrel heater is working CAUSES 1. Improper charging 2. Improperly set safety time delay 3. 4. 5. 6. NOTE: If the ambient temperature is below 32°F, freezing can be completely prevented by one of two methods: 1. Drain all water from the equipment. 2. Add antifreeze to the water. 22 START-UP CHECK LIST Unit Model No. Setting unit: Yes No a. Vibration isolator used b. Spring isolator adjusted for equal height c. If rubber-in-shear isolators are used, is unit leveled by shimming Wiring: a. Power wiring complete b. Control wiring complete c. Electric service adequate for load d. Power source voltage correct for motor(s) used e. Motor circuit has proper size fusetrons f. System wired per diagram g. All lead connections tight h. Wiring complies with local codes i. Flow switch operation Piping: a. Piping complies with applicable codes b. External piping independently supported c. Chilled water lines insulated Alignment: a. All belts adjusted and checked for tension b. All pulleys checked and adjusted for proper pitch, tightness and alignment Before Start-Up: a. Open compressor discharge service valve b. Open liquid valve(s) c. Open suction, and discharge valves to pressure gauges (if supplied) d. Check rotation of all fan motors e. Start auxiliary equipment (pumps, fans, etc.) f. Is crankcase heater operating? Operate 24 hours prior to unit startup g. Check the compressor oil level through the crankcase sight glass. The oil level should be to the top of the glass. If the level is low, add oil in accordance with the directions in the maintenance instruction h. Check all control settings as specified in Table 1. I. Air purged from chilled water system After Start-Up: a. Check high pressure control b. Check oil temperature safety switch c. Check and adjust low pressure or temperature freeze control d. Check and adjust operating thermostat e. Check and adjust low pressure operating control f. Check and adjust expansion valve superheat g. Check and adjust capacity control thermostat 23 OPERATING DATA CHILLER Voltage: L-1 L-2 L-3 _ Pressure Gauge Readings: #1 Suction psig #1 Discharge psig; #2 Suction psig psig #3 Suction psig #3 Discharge psig; #4 Suction High pressure switch setting: #1 (Cut-in) psig psig (Out); #2 (Cut-in) psig psig #3 (Cut-in) psig psig (Out); #4 (Cut-In) Checked Setting - Yes - No (each circuit) Low Pressure Switch Setting: #1 (Cut-in) psig psig (Out); #2 (Cut-in) psig psig #3 (Cut-In) psig psig (Out); #4 (Cut-in) Checked Setting -Yes -No (each circuit) #1 Oil Temperature Safety Switch Cut Out; #2 Oil Temperature Safety Switch #3 Oil Temperature Safety Switch Cut Out; #4 Oil Temperature Safety Switch If Star-Delta start, time delay is seconds. Temperature of air entering condenser "F, Temperature of air leaving condenser of. Temperature of chilled water entering chiller OF. Temperature of water (chilled) leaving chiller "F, Chilled water pressure entering chiller psig Chilled water pressure leaving chiller psig #2 Discharge #4 Discharge _ psig; _ psig psig (Out); psig (Out) psig (Out); psig (Out) Cut Out; Cut Out MAINTENANCE Good maintenance practice will prolong the chiller life and will reduce the Ask of system breakdown and expensive service calls. A weekly check of the ACWC-SD unit requires only a few minutes and will prove beneficial in insuring long trouble free operation. WEEKLY CHECKS- with unit in operation for at least four hours. 1) Check compressor oil level - At least above 1/2 of sight glass 2) Record suction and discharge pressures Typical Condition: R22 Ambient 95°F: Return water 55°F., Leaving water 45°F. Suction 62 psig: Discharge 270 psig 3) Record ambient temperature 4) Check liquid sight glass Make sure liquid is clear - no bubbles 5) Check that all fans are running 6) Check entering face of condenser coil for cleanliness 7) Record voltage at unit All of the above can be performed by building maintenance personnel. If oil levels are low or any of the above checked items are questionable consult a qualified serviceman. At least once a year a qualified serviceman should check unit oil levels, superheat and control operation. DUNHAM-BUSH USA Bmgess RO~, Harrisonburg, VA 22801 Phone: (540) 434-0711 FAX (540) 434-~ 2'1'18 wvvw.dunham-bush.com P l) • 130 x UtUC t01 Form No. 6184