UniMix air insulated medium voltage switchgear
Transcription
UniMix air insulated medium voltage switchgear
© BA PTMV - BU Switchgear - 1 03-2007 - Salvi BA PTMV BU Switchgear Product Marketing Manuel Salvi UniMix air insulated medium voltage switchgear UniMix Standards Compliance Compliant with new IEC 62271-200 (ex 60298) that classifies reliability and operating risks. Classified by IEC 62271-200 as: metal-enclosed partition metallic (compartments segregation) LSC2A Loss of Continuity: Feeder Service: Compartment © ABB - Page 2 Is compliant with IEC 60129 for indications. UniMix characteristics Maximum Flexibility up to 24kV Interchangeable SF6/vacuum CBs Sensors/DIN CT’s/Ring CT’s Compact dimensions (375/500/750mm) Wall standing Bus bars CTs & VTs (W>375mm) Full Int.Arc Proof 16kAx1s (0.5s for W=375mm) All earthed metal segregation Welded tank © ABB - Page 3 Short delivery time UniMix Characteristics EARTHED metallic segregation between bus bar and feeder compartments Maximum safety during maintenance and operations in the cable or fuse compartment even with bus bars energized. © ABB - Page 4 Reduced risk of short circuit between phases or between the two insulators of the same phase UniMix Characteristics Electrical Data Rated insulation voltage kV 12 17 24 Test Voltage (50-60 Hz/1 min) kV 28 38 50 Impulse withstand voltage kV 75 95 125 Rated frequency Hz 50/60 50/60 50/60 Rated main busbar current A 630/1250 Rated feeder current A 630/1250 Max. short-time current kA 25x1s 25x1s 25x1s Max. making capacity kA 62.5x1s 62.5x1s 62.5x1s SHS2 Gas absolute pressure (20 °C; SF6 350g) kPa 125 © ABB - Page 5 LBS motor kit Available UniMix Internal Arc Proof Internal arc proof withstand current 500/750mm width units 16kA for 1 second 20kA for 0.5 second Tranne P1E e P1A 375mm width units 12.5kA for 1 second 16kA for 0.5 second “Light” version © ABB - Page 6 12.5kA for 1 second UniMix Internal Arc Proof Arc-proof test according to IEC 298 standards, appendix AA, class A, criteria 1 to 5 / IEC 62271-200 Testing setup Criteria: 1 Correctly secured doors, covers do not open. 2 Parts which may cause a hazard do not fly off. 3 No holes in the freely accessible external parts of the enclosure. 4 Horizontally and vertically arranged indicators do not ignite. © ABB - Page 7 Infrared camera 5 Earthing connections are still effective. UniMix SHS2 type Switch disconnector SF6 insulated Stainless steel enclosure 3 position: LINE – OPEN – EARTH Making capacity Earthing Switch Separate slots for SD and ES IEC 60129 for indications © ABB - Page 8 Motor operated mechanism on request UniMix SHS2 basic structure 2 2 1 4 4 2 5 8 77 3 6 © ABB - Page 9 2 Legend: 1. Switching shaft - 2. Isolators - 3. Enclosure - 4. Fixed contacts - 5. Moving Contacts 6. Earthing contacts - 7. Operating mechanism - 8. Rupture disk UniMix SHS2: Three positions SD © ABB - Page 10 LINE OPEN EARTH UniMix SHS2: Accessories 3 3 3 1 4 © ABB - Page 11 2 1 Caption: 1 Line key locks 2 Earth key locks 3 Auxiliary contacts (2+2) 4 Opening coil 5 Voltage indicators 5 UniMix Circuit breakers 230mm pole distance On board PR521 relay and sensors SF6 pressure switch on request © ABB - Page 12 Motorised on request UniMix Protection & Control PR512 & ring core type CTs PR521 & dedicated current sensors on board of CB © ABB - Page 13 DIN 43625 Fuses REF542 Plus UniMix Instrument transformers Current and voltage transformers Combisensor Ring core type DIN 42600 © ABB - Page 14 DIN 42600 UniMix New Units: P1/A Rated insulation voltage kV 24 Test Voltage (50-60 Hz/1 min) kV 50 Impulse withstand voltage kV 125 Rated frequency Hz 50/60 Rated main busbar current A 630/1250 Rated feeder current A 400/630 Max. short-time current kA 16x1s Max. making capacity kA 62.5x1s (ES excluded) © ABB - Page 15 Maintenance of CB (opening of door) keeping MV cables enegised UniMix New Units: P1/E Rated insulation voltage kV 24 Test Voltage (50-60 Hz/1 min) kV 50 Impulse withstand voltage kV 125 Rated frequency Hz 50/60 Rated main busbar current A 630/1250 Rated feeder current A 630/1250 Max. short-time current kA 25x1s Max. making capacity kA 62.5x1s Internal arc proof kA 16x1S Withdrawable Circuit Breaker with front operating mechanism © ABB - Page 16 Feeder current up to 1250A DIN CTs and DIN VTs can be both housed in the feeder unit UniMix © ABB - Page 17 New Units: P1/E UniMix Unit P3 – Switch disconnector Opening coil Motor operated mechanism Bus Tie Unit Available for 500 mm width units: - DIN CTs (2 or 3) - DIN VTs - Busbars DIN CTs © ABB - Page 18 - Busbars DIN VTs UniMix Unit P2 – Fused Switch disconnector Opening coil Bus Tie Unit Available for 500 mm width units: - Busbars DIN CTs © ABB - Page 19 - Busbars DIN VTs UniMix Unit P1/F – Circuit breaker DIN CTs (2 or 3) DIN VTs On board current sensors for PR521 © ABB - Page 20 Bus Tie unit UniMix Unit ASR – Switched Incoming Bus Tie unit Available for 500 mm width units: - DIN CTs (2 or 3) - DIN VTs - Busbars DIN CTs © ABB - Page 21 - Busbars DIN VTs UniMix Unit A – Direct Incoming Available for 500 mm width units: - DIN CTs (2 or 3) © ABB - Page 22 - DIN VTs UniMix Unit R - Riser Available for 500mm width units: - DIN CTs (2 or 3) © ABB - Page 23 - DIN VTs UniMix Unit Rac – Direct cable Incoming Available for 500mm width units: - DIN CTs (2 or 3) © ABB - Page 24 - DIN VTs UniMix Unit M – Measure Busbars DIN CTs © ABB - Page 25 DIN VTs Secondary Distribution typical applications Manufacturing industry Secondary substations Shopping centres Airports Undergrounds Windmills © ABB - Page 26 Production = 9’000 units/year Unimix factory and Production process © ABB - Page 27 Loreto Aprutino Workshop : sqm. 5300 Offices : sqm. 400 UniMix on inside.abb.com General information Documents download Service and support © ABB - Page 28 Training & Technical Support Audit & Consulting Retrofit & Upgrades © ABB - Page 29