Level - Tetisan

Transcription

Level - Tetisan
2015ofcobc_Layout 4 7/7/14 3:38 PM Page 1
CT-D-I
Instrumentation leaders for over 80 years through
innovation, service & quality
www.dwyer-inst.com
pressure
air quality
flow
temperature
level
process control
test equipment
valves
RIGHT CHOICE. RIGHT PRICE. RIGHT NOW.
2015
Phone: 219/879-8000 | Fax: 219/872-9057
www.dwyer-inst.com
www.dwyer-inst.com
2015
TO ORDER:
DWYER INSTRUMENTS, INC.
DWYER INSTRUMENTS, INC.
INSTRUMENTATION & CONTROL
DWYER INSTRUMENTS, INC.
pressure
air quality
flow
temperature
level
process control
test equipment
valves
2015
RIGHT CHOICE. RIGHT PRICE. RIGHT NOW.
Printed in U.S.A. 09/14 - INTL
287_Layout 1 7/8/14 12:07 PM Page 287
Level Indicators
pages 290-293
Water Leak
Detectors
page 294
Level Switches,
Float
pages 295-305
Level Switches,
Optical
page 306
Level Switches,
Displacer
page 306
Level Switches,
Conductivity
page 307
Level Switches,
Capacitive
pages 308-309
Level Switches,
Tilt
page 310
Level Switches,
Tuning Fork
pages 311-312
Level Switches,
Vibrating Rod
page 313
Level Switches,
Paddle
pages 314-315
Level Switches,
Diaphragm
pages 316-317
Level Transmitters,
Submersible
pages 318-321
Level Transmitters,
Capacitive
page 322
Level Data
Loggers
page 323
Level Transmitters,
Ultrasonic
pages 323-329
Level Transmitters,
Float
page 330
Level Transmitters,
Mechanical
page 331
Level/Pump
Controllers
pages 332-334
Pump Leak Detectors
page 334
Bin Vibrators/
Aerators
pages 335-338
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
LEVEL | TABLE OF CONTENTS
TYPICAL
APPLICATIONS
pages 288-289
287
LEVEL
288_Layout 1 7/8/14 12:06 PM Page 288
Proximity™ Series PLS is used to indicate level status in pneumatic
conveying systems.
Mercoid® pump controller with level transmitter control pumps in
wastewater lift stations.
Pneumatic conveying systems use air to transport powder and dry bulk solids through
conveying lines. The air is pressurized by positive pressure or vacuum to move the
product through the lines into and out of silos, transporters, and receivers. Typical
applications have high and low level indication in the storage bins to control the flow
of product in or out. The PLS is perfect for level use in these storage bins. It has a
rotating paddle that is inserted into the bin. As the product level builds up in the bin it
stops the paddle from rotating and triggers the level output. The PLS is great for this
application as it not affected by pressure changes in the bin.
Lift stations are used to transmit wastewater to the treatment facility. Wastewater is
transmitted by gravity feed so it has to be continually elevated to provide height to
generate the flow. Lift stations are pits located at points in the wastewater system to
collect the wastewater that usually have two submersible pumps. Wastewater in the
lift station is pumped out to a higher level from where it can flow on to the next lift
station or to the treatment facility. The Mercoid® Series MPC pump controller is used
with the Series PBLT level transmitter to control the level in the lift station. The PBLT
is a level transmitter that is submersed in the tank and sends a linear output of the
height of wastewater above it. The MPC takes the height input and controls the pumps
according to how it has been programmed.
Grain hopper level controlled by Series PLS Paddle Level Switch.
Custom level sensing devices are built to meet each customer’s
specific requirements, providing visual indication, continuous
measurement, and point level control.
Typical Applications
The supply of grain pneumatically conveyed to this dispensing hopper is controlled
by two Proximity™ Series PLS paddle level switches. When the grain level falls to the
low limit switch, the supply is turned on until the hopper fills to the level of the high
limit switch which turns off the supply. Since grain dust is explosive, the explosionproof Series PLS provides the required safety protection. The PLS is a paddle level
switch and is not affected by the varying pressure in the hopper due to the cycling of
the pneumatic conveying system.
288
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
To meet various tank level measuring needs, Dwyer Instruments, Inc. offers customconfigured products built to customer specifications that provide visual indication,
continuous level measurement, and multiple point level measurement. Series VR or
MVR View-Rite Level Indicators are a safe way to keep the process isolated while
providing true visible indication. Unlike sight glasses, which can crack or break, ViewRite Indicators contain liquids entirely within their stainless steel enclosure. For
continuous level measurement needs, the Series CLT uses reed switch technology
to offer a more economical solution than expensive ultrasonic, submersible or RT
transmitters. Lastly, the Series F7-MQ can be used in virtually any tank to indicate
high and low alarms or to control pumps and valves.
289_Layout 1 7/8/14 12:05 PM Page 289
Industrial sumps and other underground tanks are ideal applications for top-mounted
Mercoid® displacer type level controls. Easily installed, these controls use porcelain
displacers that do not float on the surface of liquids, but are suspended on a coil
spring and cable. As the liquid in the tank reaches the level of the upper displacers,
their weight decreases by an amount equal to the liquid displaced, allowing the spring
to move the cable upward, actuating the switch and the pump is turned on. As the
liquid level falls below the upper displacers they move only a small amount, staying
within the switch deadband until the liquid level falls to the center of the bottom
displacer. At this point the switch is deactivated stopping the pump. The pump will
remain deactivated until the water level rises to the upper displacers, repeating the
cycle. The displacers are not affected by turbulence, pressure or chemicals and are
excellent for tanks with viscous or dirty liquids. The level differential is easily adjusted
by repositioning of the displacers on the 316SS cable.
Standard float switches require at least an inch of liquid to attain enough buoyancy
to switch. This can be a problem in applications where low level sensing is required.
The hat-shaped design of W.E. Anderson’s F7-LL provides necessary buoyancy for
switching in only 5/8˝ of water. This is essential for air conditioner drip pans, low level
sumps, and drains. The F7-LL is also ideal for low alarms, where running the process
dry can result in catastrophic failure.
Mercoid® Model 123 level controls provide high and low alarm on
large de-aerator tank.
W.E. Anderson® Series OLS indicates level in heavy equipment
radiator.
Liquid level in the external piping equals level in the tank. When level rises to high
limit, float in upper Model 123 is lifted, actuating switch to sound high level alarm.
When level drops to low limit, lower Model 123 sounds low level alarm.
Many types of heavy industrial equipment use a liquid cooling system for the motor.
A vibratory trench roller is a machine that compacts sub-bases for roads, parking lots,
etc., and is an example of the type of equipment that would utilize this system. This
machine incorporates a radiator cooling system. In the system, cooling liquid
circulates through the engine preventing it from over heating. As the engine is cooled
the cooling fluid heats up. The fluid returns to the radiator to cool down before being
circulated through again. If there is not enough cooling fluid in the system the engine
will not be cooled enough and damage will occur. A W. E. Anderson® Series OLS
optical level switch is installed as a low level alarm. The level alarm is signaled by the
OLS before the cooling fluid gets to a critical low level, warning the operator of the
problem. The OLS uses an optical detection system superior for this application as
float controls may trip from machine vibration. Also the compact insertion length is
ideal for a small radiator.
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
289
Typical Applications
Low level float switch enables sensing in air conditioner drip pans
and other shallow level applications.
LEVEL
Mercoid® displacer type level control is ideal for controlling industrial
sump pumps.
290_Layout 1 7/8/14 12:04 PM Page 290
Series
VR
View-Rite Level Indicator
Customized to Fit Any Application, Durable, 316 SS Housing and Float
Top & Bottom
Side & Side
L1
C to C
L1 & C to C
Typical Measurements
C to C = L1 + 10.25˝ (260.35 mm) C to C = L1
Customize level indicators to meet application requirements. View-Rite level
indicators are low maintenance, environmentally friendly, durable, and require no
external power. Specify any indication length up to 96˝ (244 cm). View-Rite level indicators
incorporate a pressure tight housing with internal float that magnetically activates
external level indication flags, switches, or transmitter. Consult factory for pressure rating
up to 700 psi (48 bar) or temperature rating to 750°F (339°C).
OPTIONAL SWITCH MODULES
Clamp onto the level indicator. SPST, rated .17A @ 120 VAC, .08A @ 240 VAC,
.13A @ 120 VDC, .06A @ 240 VDC.
VR-S1, Maximum temperature is 300°F (148.9°C). Polysulfone with 1/4˝ female
NPT conduit connection.
VR-S2, Maximum temperature is 750°F (399°C). 316 SS with 1/2˝ male NPT
conduit connection.
VR-S3, Maximum temperature is 750°F (399°C). Explosion-proof terminal box
with 1/2˝ female NPT conduit connection.
Models are built to your specifications
VR S SS 1 TP D 0.8 150 090 080 P
VR
S
TB
SS
1
Process
2
Connection
4
5
6
7
Float Access
TP
BM
TB
N
Drain
D
and Vent
V
B
0.0
Spec. Gravity
000
Operating Pressure
000
Operating Temp.
Indicating Length, L1
000
P
Indicating Flags
A
Visual
Indicating
Scale
Output Options
Level Indicators
LEVEL
Example
Construction
Wetted Materials
Configuration
290
SPECIFICATIONS
Service: Clean, low-viscosity liquids.
Pressure Limits: 275 psi (18.9 bar), 225 psi (15.5 bar) @ 100°F (37.8°C), 215 psi
(14.8 bar) @ 300°F (148.9°C), 195 psi (13.4 bar) @ 400°F (204.4°C).
Tube Diameter: 2-1/2˝ (64 mm).
1 I VR-SSS1-TPD-0.8-150-090-080P1-I
View-Rite Level Indicator
316 L SS, Fluoroelastomer O-ring
Top/Bottom Connections
Side/Side Connections
1/2˝ NPT (Female on TB, and Male on SS Configuration)
1˝ NPT (Female on TB, and Male on SS Configuration)
1˝ 150# RF Flange
2˝ 150# RF Flange
1˝ 300# RF Flange
2˝ 300# RF Flange
Top
Bottom
Top and Bottom (Only with SS Configuration)
None
Drain, 1/2˝ female NPT (Only with SS Configuration)
Vent, 1/2˝ female NPT (Only with SS Configuration)
Drain and Vent (Only with SS Configuration)
Specific Gravity of fluid, minimum 0.8
Operating Pressure, in psi. Maximum is 275 psi (18.9 bar)
Operating Temperature of the fluid, in °F. Maximum is 400°F (204°C)
Length of level indicator, in whole inches. Maximum of 240˝ (6.1 m); Minimum of 6˝ (15.25 cm)
Plastic, white and orange [300°F (149°C) maximum]
Aluminum, silver and black
N
None
1
Feet and Inches
2
Inches Only
I 4 to 20 mA transmitter of level [300°F (149°) maximum]
V 0 to 5 VDC transmitter of level
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
291_Layout 1 7/8/14 12:04 PM Page 291
Series
MVR
Mini View-Rite Level Indicator
Customized, Visual Level Indication, Compact Size
Top & Bottom
Side & Side
L1
C to C
L1 & C to C
Typical Measurements
C to C = L1 + 7.72˝ (196.09 mm) C to C = L1
Miniature custom level indicators are ideal for high-visibility level indication in tight
spaces. All SS housing provides rugged durability with a diameter of only 1-1/4˝ (32 mm).
Select the mounting type that will best fit your application and an indication length of up
to 96˝ (244 cm). View-Rite level indicators incorporate a pressure tight housing with
internal float that magnetically activates external level indication flags, switches, or
transmitter.
Models are built to your specifications
Example
MVR S SS 1 TP
Construction
MVR
S
Wetted Materials
TB
Configuration
SS
Process
1
Connection
3
Float
TP
Access
BM
TB
Drain
and
Vent
1
I
N
D
V
B
0.0
000
000
OPTIONAL SWITCH MODULES
Clamp onto the level indicator. SPST, rated .17A @ 120 VAC, .08A @ 240 VAC,
.13A @ 120 VDC, .06A @ 240 VDC.
MVR-S1, Maximum temperature is 300°F (148.9°C). Polysulfone with 1/4˝
female NPT conduit connection.
MVR-S2, Maximum temperature is 750°F (399°C). 316 SS with 1/2˝ male NPT
conduit connection.
MVR-S3, Maximum temperature is 750°F (399°C). Explosion-proof terminal box
with 1/2˝ female NPT conduit connection.
MVR-SSS1-TPD-0.8-150-090-080P1-I
Mini View-Rite Level Indicator
316 L SS Housing, 316 L SS Float, Fluoroelastomer O-ring
Top/Bottom Connections
Side/Side Connections
1/2˝ NPT (Female on TB, and Male on SS Configuration)
1/2˝ 150# RF Flange
Top
Bottom
Top and Bottom (Only with SS Configuration)
None
Drain, 1/2˝ female NPT (Only with SS Configuration)
Vent, 1/2˝ female NPT (Only with SS Configuration)
Drain and Vent (Only with SS Configuration)
Specific Gravity of fluid, minimum 0.8
Operating Pressure, in psi. Maximum is 400 psi (27.6 bar)
LEVEL
Operating Temperature of the fluid, in °F. Maximum is 400°F (204°C)
000
Length of level indicator, in whole inches. Maximum of 240˝ (6.1 m); Minimum of 6˝ (15.25 cm)
P
A
N
1
2
I
V
Plastic, white and orange [300°F (149°C) maximum]
Aluminum, silver and black
None
Feet and Inches
Inches Only
4 to 20 mA transmitter of level [300°F (149°C) maximum]
0 to 5 VDC transmitter of level
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
Level Indicators
Spec. Gravity
Operating
Pressure
Operating
Temperature
Indicating
Length, L1
Indicating
Flags
Visual
Indicating
Scale
Output
Options
D 0.8 150 090 080 P
SPECIFICATIONS
Service: Clean, low-viscosity liquids.
Pressure Limits: ≤300°F, 400 psi (27.6 bar); ≥ 300°F, 373 psi (25.7 bar).
Tube Diameter: 1-1/4˝ (32 mm).
291
292_Layout 1 7/8/14 12:03 PM Page 292
Series
DTM
Dip Tape Level Indicator Metal
Customizable, Lightweight, No Electricity Needed
PVC CAP
1/2˝ NPT
Ø2 [Ø50.80]
FLOAT
DIMENSIONS
3/4 MIN.
[19.05]
Ø1-7/8
[Ø47.63]
Ø2-1/16
[Ø52.39]
F1 Float
BUNA N
FLOAT
6 HOLES [Ø.750]
EQUALLY SPACED
ON A [6.000 B.C.]
PVC CAP
1/2˝ NPT
1/8
[3.18]
Ø1-7/8
[Ø47.63]
3/4 MIN.
[19.05]
The Series DTM is a manual, no electricity required indicator that is compact, providing
uninterrupted liquid level indication for use in storage tanks or vessels. With a sturdy,
lightweight design, the DTM is ideal for 30 or 55 gallon tanks. Stem and mounting fixtures
are available in 316 SS or brass. Strong brass or stainless steel units are perfect for the
use in water and oils offering the best temperature and pressure capabilities. The float
and stem are the only parts of the DTM that make contact with the liquid, so the indication
tape is always clean and easy to read. It is simple to customize the DTM level indicator in
order to meet a particular application requirement. A custom configurable DTM is available
in lengths ranging from 6 in (15.2 cm) up to 6 ft (182.9 cm). This level indicator is ideal for
quick readouts taken periodically. The DTM is accurate to 1/16 of an inch or 1 mm, and is
especially useful in remote areas where power is unavailable, or undesirable.
Type 1
LEVEL
Float Type
Level Indicators
Description
Brass, Buna N float, 2˝ NPT, 30 gallon horizontal drum, 17.5˝
Brass, Buna N float, 2˝ NPT, 55 gallon horizontal drum, 22˝
Brass, Buna N float, 2˝ NPT, 30 gallon vertical drum, 26.5˝
Brass, Buna N float, 2˝ NPT, 55 gallon vertical drum, 33˝
316 SS, 2˝ NPT, 30 gallon horizontal drum, 17.5˝
316 SS, 2˝ NPT, 55 gallon horizontal drum, 22˝
316 SS, 2˝ NPT, 30 gallon vertical drum, 26.5˝
316 SS, 2˝ NPT, 55 gallon vertical drum, 33˝
DTM B 1 F1 N
Example
DTM
Series
B
Stem &
S
Connection
C
Material
1
Connection
2
Type
F1
F2
N
Indication
C
Markings
Length
*Order length must be in inches.
292
6.00
DTM-B1F1N-6.00
Dip Tape Metal
Brass (not available with conn. type 2)
316 SS
316 SS with carbon steel flange (not available with conn. type 1)
2˝ NPT
3˝ 150 # ANSI flange
Material
Min. s.g. Max. Pressure
Buna N
300 psi (21 bar)
0.45
316 SS
750 psi (52 bar), 2˝ NPT
0.67
150 psi (10 bar), 3˝ 150 # ANSI flange
Inches, 1/16 in increments
Centimeters, 1 mm increments
00.00 6 to 72˝ (15.2 to 182.9 cm)*
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
Ø7-1/2 [190.49]
Type 2
SPECIFICATIONS
Service: Compatible liquids.
Wetted Materials: See model chart.
Temperature Limits:
Buna N: -40 to 230°F (-40 to 110°C) for oil, up to 180°F (82.2°C) for water;
316 SS: -40 to 300°F (-40 to 148.8°C).
Pressure Limits: See model chart.
Mounting Orientation: Vertically in either vertical or horizontal tanks.
Indication Markings: 1/16 in or 1 mm increments.
PRINCIPLE OF OPERATION
The float located on the DTM is equipped with a magnet that moves with the liquid
level, vertically, along the stem, inside the storage vessel. Level reading is acquired
by simply removing the protective cap located on the top of the unit and lifting the
calibrated measuring tape until the magnetic interlock with the float causes a slight
pull. The indicator tape remains at this point while the level is read where the
calibration aligns with the top of the mounting. The indicator tape can then be
lowered back inside the unit stem for storage and protection.
Model
DTM-B1F1N-17.50
DTM-B1F1N-22.00
DTM-B1F1N-26.50
DTM-B1F1N-33.00
DTM-S1F2N-17.50
DTM-S1F2N-22.00
DTM-S1F2N-26.50
DTM-S1F2N-33.00
11/16
[17.48]
2˝ NPT
1-13/16
[46.04]
1-1/4
[31.75]
Liquid Measurement
Detail
(Inches Tape Shown)
F2 Float
MOUNTING
DIMENSIONS
INCHES OF
INDICATION
2-3/32
[53.18]
1-13/16
[46.04]
2˝ NPT
TAKE READING
AT THIS POINT
293_Layout 1 7/8/14 12:02 PM Page 293
Series
DTP
Dip Tape Level Indicator Plastic
Customizable, Lightweight, No Electricity Needed
PVC CAP
1/2˝ NPT
MOUNTING
DIMENSIONS
FLOAT
DIMENSIONS
3˝ NPT
15/16
23.8]
INCHES OF
NDICATION
PVC CAP
Ø3
[Ø76.20]
1/2˝ NPT
3˝ 150 LB
FLANGE
1/2˝ NPT
3˝ NPT
2-3/8
[60.33]
PVC
FLOAT
2-3/8
[60.33]
6 HOLES [Ø.750] EQUALLY
SPACED ON A [6.000 B.C.]
TAKE
READING AT
THIS
POINT
HIGHEST
LEVEL
INDICATED
27/32
[21.34]
15/16
[23.8]
Liquid Measurement
Detail
(Inches Tape Shown)
15/16
[23.8]
Ø7-1/2
[190.49]
Type 1
Type 2
Ø3
[Ø76.20]
The Series DTP is a manual, no electricity required indicator that is compact, providing
uninterrupted liquid level indication for use in storage tanks or vessels. With a sturdy,
lightweight design, the DTP is ideal for 30 or 55 gallon tanks. Stem and mounting fixtures
are available in PVC, PVDF, or polypropylene. With a choice of three highly resistive,
engineered plastic materials, and large floats, the DTP provides rugged durability in almost
any chemical tank. The float and stem are the only parts of the DTP that make contact
with the liquid, so the indication tape is always clean and easy to read. It is simple to
customize the DTP level indicator in order to meet a particular application requirement. A
custom configurable DTP is available in lengths ranging from 6 in (15.2 cm) up to 6 ft (182.9
cm). This level indicator is ideal for quick readouts taken periodically. The DTP is accurate
to 1/16 of an inch or 1 mm, and is especially useful in remote areas where power is
unavailable, or undesirable.
PRINCIPLE OF OPERATION
The float located on the DTP is equipped with a magnet that moves with the liquid
level, vertically, along the stem, inside the storage vessel. Level reading is acquired
by simply removing the protective cap located on the top of the unit and lifting the
calibrated measuring tape until the magnetic interlock with the float causes a slight
pull. The indicator tape remains at this point while the level is read where the
calibration aligns with the top of the mounting. The indicator tape can then be
lowered back inside the unit stem for storage and protection.
Series
DTV
SPECIFICATIONS
Pressure Limit: See model chart.
Service: Compatible liquids.
Mounting Orientation: Vertically in
Wetted Materials: See model chart.
either vertical or horizontal tanks.
Temperature Limits: 40 to 140°F (4.4
Indication Markings: 1/16 in or 1 mm
to 60°C).
increments.
DTP P 1 F1 N 6.00 DTP-P1F1N-6.00
Example
DTP
Dip Tape Plastic
Series
P
PVC (only available with F1)
Stem &
L
Polypropylene (only available with F2)
Connection
F
PVDF (only available with F3)
Material
1
3˝ NPT
Connection
2
3˝ 150 # ANSI flange
Type
Material
Min. s.g. Max. Pressure
F1
Float Type
50 psi (3.4 bar)
PVC
0.65
F2
50 psi (3.4 bar)
Polypropylene 0.46
F3
50 psi (3.4 bar)
PVDF
0.83
N
Inches, 1/16 in increments
Indication
C
Centimeters, 1 mm increments
Markings
00.00 6 to 72˝ (15.2 to 182.9 cm)*
Length
Dip Tape Level Indicator PVC
Customizable, Lightweight, No Electricity Needed
PVC CAP
1/2˝ NPT
1/4 MIN.
[6.35]
MOUNTING
DIMENSIONS
FLOAT
DIMENSIONS
2˝ NPT
35/64
[13.72]
1-5/8
[41.28]
INCHES OF
INDICATION
1/2˝ NPT
1-1/2
[38.10]
2˝ NPT
Ø7-1/2
[190.49]
Liquid Measurement
Detail
(Inches Tape Shown)
Type 1
Type 2
The Series DTV is a manual, no electricity required indicator that is compact, providing
uninterrupted liquid level indication for use in storage tanks or vessels. With a sturdy,
lightweight design, the DTV is ideal for 30 or 55 gallon tanks. Stem and mounting consists
of PVC. Ideal for chemical storage tanks, our PVC indicator offers one of our best values
for liquid level monitoring. This light duty version is recommended for use in calm liquids
and ambient temperature and pressure levels. The float and stem are the only parts of the
DTV that make contact with the liquid, so the indication tape is always clean and easy to
read. It is simple to customize the DTV level indicator in order to meet a particular
application requirement promptly and affordably. A custom configurable DTV is available
in lengths ranging from 6 in (15.2 cm) up to 6 ft (182.9 cm). This level indicator is ideal for
quick readouts taken periodically. The DTV is accurate to 1/16 of an inch or 1 mm, and is
especially useful in remote areas where power is unavailable, or undesirable.
SPECIFICATIONS
Pressure Limit: See model chart.
Service: Compatible liquids.
Mounting Orientation: Vertically in
Wetted Materials: See model chart.
either vertical or horizontal tanks.
Temperature Limits: 0 to 140°F (-17.7
Indication Markings: 1/16 in or 1 mm
to 60°C).
increments.
Model
Description
DTV-1N-17.50
PVC, 2˝ NPT, 30 gallon horizontal drum, 17.5˝
DTV-1N-22.00
PVC, 2˝ NPT, 55 gallon horizontal drum, 22˝
DTV-1N-26.50
PVC, 2˝ NPT, 30 gallon vertical drum, 26.5˝
DTV-1N-33.00
PVC, 2˝ NPT, 55 gallon vertical drum, 33˝
PRINCIPLE OF OPERATION
The float located on the DTV is equipped with a magnet that moves with the liquid
level, vertically, along the stem, inside the storage vessel. Level reading is acquired
by simply removing the protective cap located on the top of the unit and lifting the
calibrated measuring tape until the magnetic interlock with the float causes a slight
pull. The indicator tape remains at this point while the level is read where the
calibration aligns with the top of the mounting. The indicator tape can then be
lowered back inside the unit stem for storage and protection.
DTV-1N-6.00
Dip Tape PVC
Float Material Min. s.g. Max. Pressure
0.65
15 psi (1 bar)
PVC
1
2˝ NPT
Connection
2
3˝ 150 # lb ANSI flange
Type
N
Inches, 1/16 in increments
Indication
C
Centimeters, 1 mm increments
Markings
00.00 6 to 72˝ (15.2 to 182.9 cm)*
Length
*Order length must be in inches.
DTV 1
DTV
N
6.00
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
Level Indicators
Example
Series
LEVEL
Ø1-1/2
[Ø38.10]
Ø1-1/2
[Ø38.10]
1/2˝ NPT
3˝ 150 LB
FLANGE
PVC CAP
1/4 MIN.
[6.35]
PVC
FLOAT
1-5/8
[41.28]
6 HOLES [Ø.750] EQUALLY
SPACED ON A [6.000 B.C.]
TAKE
READING
AT THIS
POINT
293
294_Layout 1 7/14/14 8:29 AM Page 294
Series
WD3
Water Leak Detector
Battery or External Powered, SPST or DPDT Relays
RoHS
3-5/8
[91.70]
3
[76.68]
1-3/16
[30.12]
5/16
[7.52]
1-5/16
[33.15]
5/8
[16.58]
4-1/8
[105.23]
WD3-BP
Scan here
to watch
product video
Output
SPST NO SSR
DPDT Relay
DPDT Relay
5/8
[16.18]
Bracket
WD3
The Series WD3 Water Leak Detector protects equipment from water damage by
detecting the presence of water in drip pans in air handler units, under raised floors in
data centers, or on floors around sump pumps and drains. Water is detected once it
reaches a level that bridges the two conductive strips on the bottom of the housing.
Depending on the model ordered, audible and visual alerts provide local indication of the
alarm condition and an internal switch will give remote indication or control to prevent
further build up of water.
For applications where power is not available, the Model WD3-BP-D1-A is battery powered.
Otherwise, either AC or DC supply voltages can be used to power the water detector. The
sensing height can be adjusted to as low as 1/32˝ using the included adjustable mounting
bracket. The mounting bracket can attach to any flat surface by either using the attached
adhesive strips or mounting screws.
Model
WD3-BP-D1-A
WD3-LP-D2
WD3-LP-D2-A
1/8
[2.50]
2
[50.66]
WD3-LP
Power
Battery
11 to 27 VAC/DC
11 to 27 VAC/DC
Audible Alarm
Yes
No
Yes
ACCESSORY
A-WD3-BRK, Replacement Mounting Bracket
Model
WD
SPECIFICATIONS
Service: Water or conductive fluids.
Minimum Sensing Gap: 1/32˝.
Switch Type: Battery Powered
Models: SPST NO SSR; External
Powered Models: DPDT relay.
Electrical Ratings:
Battery Powered Model: Pilot duty
rating 250 mA @ 24 VDC;
External Powered Models: 1A @ 24
VAC/DC.
Audible Alarm: At least 85 dB @ 1
foot distance (depends on model).
Visual Alarm: Red LED for water level;
Yellow LED for low battery (battery
powered models only); Green LED for
power condition (external powered
models only).
Temperature Limits: 32 to 122°F (0 to
50°C).
Power Requirements:
Battery Powered Model: 3V CR2450
lithium metal battery, installed
functional, user replaceable;
External Powered Models: 11 to 27
VAC/DC.
Power Consumption:
Battery Powered Model: 0.9 mA
steady state / 3.0 mA during alarm
condition;
External Powered Models: 30 mA
steady state / 85 mA during alarm
condition.
Battery Life: 5 years steady state / 48
hours during alarm condition.
Electrical Connections: 4.9´ (1.5 m),
22 AWG, PVC, UL plenum rated cable.
Enclosure Material: ABS and
polycarbonate with flammability
classification UL 94 V-0.
Enclosure Rating:
Audible Alarm Models: Water-tight up
to 3/4 of the body height;
Non-Audible Alarm Models: NEMA 6P
(IP 68) submersible.
Weight: 4.85 oz (137.5 g).
Agency Approvals: CE, RoHS.
Water Detector and Sensor Tape
Detects Low Levels Of Conductive Liquids
Ø1/4
[Ø6.35]
LEVEL
1/2˝ CONDUIT OR FLEX
CONNECTOR
Ø7/8
[Ø22.23]
1/4
4-1/4 [6.35]
[107.32]
4-3/4
AMBER LED
[120.02]
LIGHT
WD
WATER DETECTOR
PUSH
BUTTON
ALARM
TEST
POWER
15 PIN CABLE
CONNECTION
Water Leak Detectors
1-1/2
[38.10]
The small and discreet Model WD Water Detector is designed for dependable
detection of low levels of conductive liquids. The module features a sturdy and reliable
aluminum enclosure and is powered by 24 VAC or 24 to 30 VDC. Water sensing tape
attaches to module and if any liquid comes in contact with the tape the resistance is
changed and the alarm will be triggered. The tape is hydrophobic so it does not absorb any
of the liquid it is detecting which makes for a faster drying time and faster return to service
after a water leak.
The sensing tape is 1˝ wide and can be bought in lengths of 5´, 10´, 15´ and 25´. Multiple
tapes can be connected together to extend the coverage area which makes it ideal for
domestic as well as commercial applications. Features include power and alarm LED’s,
alarm test switch, continuous tape integrity self check and extendable tape sensor.
294
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
SPECIFICATIONS
Service: Conductive liquid.
Switch Type: DPDT.
Electrical Rating: 1 A @ 24 VAC/VDC.
Power Requirements: 24 VAC, 24 to
30 VDC.
Power Consumption: 35 mA
maximum.
Model
WD
TP05
TP10
TP15
TP25
Description
Water Module
5´ (1.52 m) Tape
10´ (3.05 m) Tape
15´ (4.57 m) Tape
25´ (7.62 m) Tape
3
[76.38]
GREEN LED
LIGHT
1/8
[2.10]
1-3/4
[44.17]
Electrical Connections: Screw
terminals.
Conduit Connections: Hole for 1/2˝
conduit.
Enclosure: Extruded aluminum.
Sensor Tape: 1˝ (25.4 mm) wide and
5´, 10´, 15´ or 25´ long.
Weight: 8 oz (.23 kg).
295_Layout 1 7/21/14 8:03 AM Page 295
Series
L4
Float Switch
Magnetically Operated Switch, Leak Proof Body, Explosion-Proof
SWITCH BODY OF
BRASS OR 316 SS EXPLOSION PROOF
HOUSING WITH 3/4
FLOAT ARM DEFLECTION
CONDUIT CONNECTION
FLOAT OF 316 SS
AND
BLOCK
STOP
(STANDARD)
1-1/2
16 GA. LEADS,
316 SS OR BRASS
NPT
6 [152.4] LONG
HINGE
PIN
2-1/2
1-5/8
[63.5] 3-11/32
[41.28]
[84.93]
LOCK MAGNET
HEX FLOAT
3-15/16
NUT
KEEPER
CONNECTION
[100.01]
430 SS
5
6
5-31/32 [151.61]
[127]
[152.4]
8-5/32 [207.17]
19-5/32 [486.57]
Scan here
to watch
product video
Rugged and reliable the Series L4 Flotect® Level switch operates automatically to
indicate tank level. Perfect for starting or stopping pumps, opening or closing valves, or
actuate level alarm signals. A unique magnetically actuated switching design gives
superior performance. There are no bellows, springs, or seals to fail. Instead, the freeswinging float attracts a magnet within the solid metal switch body, actuating a snap
switch by means of a simple lever arm. Float arm hinge design limits the arm angle to
prevent vertical hangup.
FEATURES
• Leak proof body machined from bar stock
• Choice of floats dependent on maximum pressure and specific gravity
• Weatherproof, designed to meet NEMA 4 (IP56)
• Explosion-proof (listings included in specifications)
• Installs directly and easily into tank with a thredolet or flange (see application
drawings)
• Electrical assembly can be easily replaced without removing the unit from the
installation so that the process does not have to be shut down
• Horizontal installation or optional top mount vertical installation
APPLICATIONS
• Direct pump control for maintaining level
• Automatic tank dump operations
• Control levels or provide alarms in sumps, scrubber systems, hydro-pneumatic
tanks, low pressure boilers, and various waste water/sewage treatment processes
Model
L4
L4-NH**
L4-SS
L4-SS-NH**
Description
Brass body, side wall mounting
Brass body, side wall mounting, no housing
316SS* body, sidewall mounting
316SS* body, sidewall mounting, no housing
Application Drawings For Flotect® Float Switches
1-1/2 THREADED
BRANCH
CONNECTION
ANSI RF THREADED
REDUCING FLANGE
CUT HOLE
1-15/16 [49] DIA.
Standard Installation
2-1/2
THREADED BRANCH
CUT HOLE
CONNECTION
2-7/8 [73] DIA.
Horizontal, Flange Installation
3/4 NPT
ANSI RF THREADED
REDUCING FLANGE
*
Horizontal, 2-1/2 Threaded Branch
Connection Installation with Optional
2-1/2 [64] Spherical Float
*FLANGE FACE TO CENTERLINE OF FLOAT
SPECIFIED BY CUSTOMER. NORMALLY
SHOULD NOT EXCEED 20˝ [508 mm].
Vertical, Flange Installation
*316SS body and float with 430SS magnet keeper (wetted part).
**No Housing Option (-NH) has no approvals.
Consult factory for price and availability of fittings for L4 installation. Threaded Branch
Connection, bushings, and flanges are available in a variety of sizes and materials.
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
295
Level Switches,
Float
2-1/2 X 1-1/2
FACE BUSHING
OPTIONS FOR L4 SWITCHES ABOVE — Add suffixes to model numbers
DPDT contacts, add suffix -D
Gold Plated Contacts option for dry circuits, add suffix -MV
(see electrical rating in specifications, no listings or approvals)
High Temperature option rated 400°F (204°C), add suffix -MT
(see electrical rating in specifications, no listings or approvals)
Time Delay Relay option with 2 SPDT contacts, adjustable from 0-1 to 0-31 minutes
add suffix -TRI (increasing flow) or
-TRD (decreasing flow) (no listings or approvals)
*316 SS Magnet Keeper option to replace standard 430 SS, add suffix -316
ATEX compliant construction, add suffix -AT
IECEx certified construction, add suffix -IEC
Top Mounted option for vertical flange installation [distance from flange face to
centerline of float to be specified, 20˝ (508 mm) max], add suffix -TOP
Optional Floats (all 2-1/2˝ spherical):
304 SS rated 50 psig (3.5 bar) and 0.5 min. s.g., add suffix -50
316 SS rated 150 psig (10.3 bar) and 0.7 min. s.g., add suffix -150
304 SS rated 300 psig (20.7 bar) and 0.7 min. s.g., add suffix -300
LEVEL
11-3/4
[298.5]
3/4 NPT
SPECIFICATIONS
Service: Liquids compatible with wetted materials.
Wetted Materials: Float and Rod: 316 SS; Body: Brass or 316 SS standard;
Magnet Keeper: 430 SS standard, 316 SS or nickel optional.
Temperature Limits: 4 to 275°F (-20 to 135°C) standard, MT high temperature
option 400°F (205°C) [MT option not UL, CSA, ATEX or IECEx]. ATEX and IECEx
options: Ambient temperature -4 to 163°F (-20 to 73°C); Process temperature -4 to
163°F (-20 to 73°C).
Pressure Limit: Brass body 1000 psig (69 bar), 316 SS body 2000 psig (138 bar).
Standard float rated 100 psig (6.9 bar). For other floats, see options.
Enclosure Rating: Weatherproof and Explosion-proof. **Listed with UL and CSA
for Class I, Groups C and D; Class II, Groups E, F, and G.
ATEX
0344
II 2 G Ex d IIB T6 Gb -20°C≤Tamb≤73°C.
-20°C≤Process Temp≤73°C.
EC-Type Certificate No.: KEMA 03 ATEX 2383.
ATEX Standards: EN60079-0: 2009; EN60079-1: 2007.
IECEx Certified: For Ex d IIB T6 Gb -20°C≤Tamb≤73°C. -20°C≤Process
Temp≤73°C.
IECEx Certificate of Conformity: IECEx DEK 11.0071.
IECEx Standards: IEC 60079-0: 2007; IEC 60079-1: 2007.
Switch Type: SPDT snap switch standard, DPDT snap switch optional.
Electrical Rating: UL, FM, ATEX and IECEx models: 10A @ 125/250 VAC (V~).
CSA models: 5A @ 125/250 VAC (V~); 5A res., 3A ind. @ 30 VDC (V ). MV
option: 1A @ 125 VAC (V~); 1A res., .5A ind. @ 30 VDC (V ). MT option: 5A @
125/250 VAC (V~). [MT and MV option not UL, CSA, FM, ATEX or IECEx].
Electrical Connections: UL and CSA models: 16 AWG, 6˝ (152 mm) long. ATEX
and IECEx unit: terminal block.
Process Connection: 1-1/2˝ male NPT standard, 2-1/2˝ male NPT standard
optional floats.
Mounting Orientation: Horizontal installation standard, optional vertical top
mount.
Weight: 4 lb 9 oz (2.07 kg).
Dead Band: 3/4˝ (19 mm) for standard float.
Specific Gravity: 0.7 minimum with standard float. For other floats see model
chart.
Agency Approvals: ATEX, CE, CSA, FM, IECEx, UL**.
296_Layout 1 7/21/14 1:37 PM Page 296
Series
L6
Liquid Level Switch
Easy In-wall or External Installation, Up to 2000 psig (138 bar)
Model L6 with External Float Chamber
1 FEMALE
NPT TYP 2 PLACES
3/4 MALE NPT
CONDUIT
CONNECTION
Model L6 with Spherical Float
Ø1 [25.40]
1 MALE NPT
3/4 MALE NPT
Ø1-1/16
CONDUIT
[26.99] CONNECTION
3-5/64
[78.18]
1-9/64
[28.97]
2 [50.80]
HEX
Ø1-1/16
[26.99]
8-9/16 [217.49]
1-3/4
[44.45]
6
[152.40]
3/4
[19.05]
Model L6 with Cylindrical Float
3/4 MALE NPT
CONDUIT CONNECTION
Ø1 [25.40] x 2 [50.80]
LONG FLOAT
Ø1-1/16
1 MALE NPT
[26.99]
6-1/2
2-7/8
[165.10]
[73.03] 1-1/16 [26.99]
Scan here
to watch
product video
Level Switches,
Float
LEVEL
Surprisingly compact, the Series L6 Flotect® Level switch is designed and built for years of
trouble-free service in a wide variety of process liquid level applications. Operation is simple and
dependable with no mechanical linkage as the level switch is magnetically actuated. The float lever
pivoted within the body moves when the process liquid displaces the float. A magnet on the
opposite end of the float lever controls a second magnet on the switch actuating lever located in the
switch housing.
FEATURES
• Leak proof lower body machined from bar stock
• Choice of models for direct side wall mounting or mounted in a tee to act as an external
float chamber
• Weatherproof
• Explosion-proof (listings included in specifications)
• Electrical assembly can be easily replaced without removing the unit from the installation
so that the process does not have to be shut down
• Sensitive to level changes of less than 1/2˝ (12 mm)
Max.
Min.
Pressure
Sp.
Float
psig
Model
Gr.
Body Installation
Material
(bar)
L6EPB-B-S-3-O Brass Side Wall Mounting
0.9
Polypropylene 1000 (69)
Spherical
L6EPB-B-S-3-A Brass Side Wall Mounting
0.5
304 SS
200 (13.8)
Cylindrical
L6EPB-B-S-3-C Brass Side Wall Mounting
0.7
304 SS
350 (24.1)
Spherical
L6EPB-B-S-3-B Brass Brass External Float Polypropylene 250 (17.2)
0.9
Chamber (Tee)
Spherical
L6EPB-B-S-3-H Brass Brass External Float 304 SS
0.7
250 (17.2)
Chamber (Tee)
Spherical
L6EPS-S-S-3-O 303 SS Side Wall Mounting
0.9
Polypropylene 2000 (138)
Spherical
L6EPS-S-S-3-A 303 SS Side Wall Mounting
0.5
304 SS
200 (13.8)
Cylindrical
L6EPS-S-S-3-C 303 SS Side Wall Mounting
0.7
304 SS
350 (24.1)
Spherical
L6EPS-S-S-3-S 303 SS 304 SS External Float Polypropylene 2000 (138)
0.9
Chamber (Tee)
Spherical
L6EPS-S-S-3-L 303 SS 304 SS External Float 304 SS
0.7
350 (24.1)
Chamber (Tee)
Spherical
OPTIONS
Gold Plated Contacts option for dry circuits, add suffix -MV (see electrical rating in
specifications)
High Temperature option rated 400°F (204°C), add suffix -MT (see electrical rating in
specifications, no listings or approvals, only available on models with stainless steel floats)
CSA and UL approved construction, includes weatherproof and explosion-proof junction
box, add suffix -CSA
ATEX compliant construction includes, weatherproof and explosion-proof, junction box, add
suffix -AT
IECEx certified construction, add suffix -IEC
DPDT contacts, change seventh character in model number to “D”.
Example: L6EPB-B-D-3-O
Options Not Shown: 1-1/2˝ and 2˝ male NPT process connection, 2˝ female NPT
connection tee, and top mount.
296
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
SPECIFICATIONS
Service: Liquids compatible with wetted materials.
Wetted Materials:
Float: Solid polypropylene or 304 SS.
Lower Body: Brass or 303 SS.
Magnet: Ceramic.
External Float Chamber (Tee): Matches lower body choice of brass or
303 SS.
Other: Lever Arm, Spring, Pin, etc.: 301 SS.
Temperature Limit: -4 to 220°F (-20 to 105°C) Standard, MT high
temperature option 400°F (205°C)(MT not UL, CSA, ATEX, IECEx and KC).
ATEX compliant AT, IECEx IEC and KC option ambient temperature -4 to
167°F (-20 to 75°C) process temperature: -4 to 220°F (-20 to 105°C).
Pressure Limits: See model chart.
Enclosure Rating: Weatherproof and Explosion-proof. Listed with UL and
CSA for Class I, Groups A, B, C and D; Class II, Groups E, F, and G.
(Group A on stainless steel body models only).
ATEX
0344
II 2 G Ex d IIC T6 Gb Process Temp≤75°C.
EC-Type Certificate No.: KEMA 04ATEX2128.
ATEX Standards: EN 60079-0: 2009; EN60079-1: 2007.
IECEx Certified: For Ex d IIC T6 Gb Process Temp≤ 75°C.
IECEx Certificate of Conformity: IECEx DEK II.0039.
IECEx Standards: IEC 60079-00: 2007; IEC 60079-1: 2007.
Korean Certified (KC) for Ex d IIC T6 Gb Process Temp≤75°C.
KTL Certificate Number: 2012-2454-75.
Switch Type: SPDT snap switch standard, DPDT snap switch optional.
Electrical Rating: UL models: 5A @ 125/250 VAC (V~). CSA, ATEX and
IECEx models: 5A @ 125/250 VAC (V~); 5A res., 3A ind. @ 30 VDC (V ).
MV option: .1A @ 125 VAC (V~). MT option: 5A @125/250 VAC (V~). [MT
option not UL, CSA, ATEX or IECEx].
Electrical Connections: UL models: 18 AWG, 18˝ (460 mm) long.
ATEX/CSA/IECEx models: terminal block.
Upper Body: Brass or 303 SS.
Conduit Connection: 3/4˝ male NPT standard, 3/4˝ female NPT on
junction box models.
Process Connection: 1˝ male NPT on models without external float
chamber, 1˝ female NPT on models with external float chamber.
Mounting Orientation: Horizontal with index arrow pointing down.
Weight: Approximately 1 lb (.5 kg) without external float chamber, 1.75 lb
(.8 kg) with external float chamber.
Specific Gravity: See chart.
Agency Approvals: ATEX, CE, CSA, IECEx, KTL, UL.
297_Layout 1 7/8/14 12:00 PM Page 297
Series
L8
Liquid Level Switch
Low Cost, Leak Proof Body, Excellent Chemical Resistance
L8
(3) 18 AWG
LEAD WIRES
18 [457.2] LONG
Ø1-21/32
[42.07]
4-17/32
[115.09]
L8-WP2
1-5/16 [33.32] OCTAGON
8-5/16
[211.12]
3-1/16
[77.79]
1/2˝ NPT(M)
1˝ NPT(M)
FLOAT
SWITCH
BODY
11-13/64
[284.56]
4-5/16
[109.52]
3-1/16
[77.79]
Ø1-21/32
[42.07]
4-5/16
[109.52]
1 NPTM
1/2 NPTM
1-5/16 OCTAGON
[33.32]
2-17/32
[64.29]
4-17/32
[115.09]
2-17/32
[64.29]
Ø1-1/8
[28.58 ]
Ø1-1/8
[28.58]
Scan here
to watch
product video
Model L8 Flotect® Liquid Level Switch features a leak proof body and float
constructed from tough, durable polyphenylene sulfide which has excellent chemical
resistance. Because the liquid level snap switch is magnetically actuated, there is no direct
mechanical linkage to leak or fail, assuring longer life and decreased maintenance costs.
This inexpensive unit is ideal for liquid level alarm, indication or control. Installation is
quick and easy — simply install in a horizontal position with the index arrow pointing down.
The L8 Flotect® Liquid Level Switch is UL recognized as an industrial motor controller per
UL standard 508, suitable for mounting in a protected environment. This lightweight
switch can be used in numerous chemical processes, industrial systems and similar
applications where process conditions are compatible with polyphenylene sulfide, ceramic
8 and 316 SS. This liquid level switch provides accurate setpoint control of liquids with
specific gravities as low as 0.6. This compact and reliable control is designed to handle
temperatures up to 212°F (100°C) and pressures to 150 psig (10 bar).
APPLICATIONS
The Model L8 Flotect® Liquid Level Switch is ideal for predetermined liquid levels in
tanks through pump control or solenoid valve control. It provides excellent liquid
level alarm or indication when combined with the Series AN14 Indicating
Annunciator.
Environmental control
Chemical/Petroleum processing
Waste water
Plating and washing tanks
Scrubber systems
Sewage treatment
Holding tanks
Car washes
Cooling towers
Remediation systems
Series L8, Level Switch
Inconel® is a registered trademark of Huntington Alloys Corporation
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
297
Level Switches,
Float
OPTIONS
Gold Plated Contacts, for dry circuits. Rated 1A @ 125 VAC; 1A resistive, 0.5A
inductive @ 30 VDC. To order add suffix -MV.
Example: L8-MV
Inconel® Alloy Option. Inconel® Alloy replaces standard 316 SS wetted parts.
Wetted parts are Inconel® Alloy, ceramic 8, and Polyphenylene Sulfide. To order add
suffix -INC.
Example: L8-INC
Weatherproof Enclosure. Optional housing is phenylpolioxide and provides
weatherproof protection for electrical wiring. To order add suffix -WP. (Not UL
approved)
Example: L8-WP
Weatherproof Enclosure. Optional housing is aluminum and provides
weatherproof protection for electrical wiring. To order add suffix -WP2. (Not UL
approved)
Example: L8-WP2
LEVEL
•
•
•
•
•
•
•
•
•
•
SPECIFICATIONS
Service: Compatible liquids.
Wetted Materials:
Float and body: Polyphenylene sulfide (PPS);
Pin and spring: 316 SS or Inconel®;
Magnet: Ceramic 8.
Temperature Limit: 212°F (100°C).
Pressure Limit: 150 psig (10.34 bar).
Enclosure Rating: General purpose. WP/WP2 option is weatherproof.
Switch Type: SPDT snap switch. MV option is a SPDT gold contact snap switch.
Electrical Rating: 5A @ 125/250 VAC, 5A resistive, 3A inductive @ 30 VDC. MV
option: 1A @ 125 VAC, 1A resistive, 0.5A inductive @ 30 VDC.
Electrical Connections: 18 AWG, 18˝ (460 mm) long.
Conduit Connection: 1/2˝ male NPT, 1/2˝ female NPT on WP and WP2.
Process Connection: 1˝ male NPT.
Mounting Orientation: Horizontal with index arrow pointing down.
Weight: 5 oz (0.142 kg).
Agency Approvals: CE, cUR, UR.
Specific Gravity: 0.6 minimum.
298_Layout 1 7/8/14 12:00 PM Page 298
Series
L10
Mini-Size Level Switch
Easy In-wall or External Installation, Specific Gravities as Low as 0.5
Spherical Float
3/4
[19.05]
Ø1
[25.40]
1-3/4
[44.45]
3-1/4
[82.55]
Cylindrical Float
1/4 [6.35]
TRAVEL TO NORMALLY
CLOSED POSITION
2-7/8
[73.07]
1 NPT
1 [25.40]
4 [101.6]
18 AWG
LEAD WIRE
19 [482.6]
CABLE
1/4 [6.35] TRAVEL
TO NORMALLY CLOSED POSITION
2-7/8
1
3-1/2
[73.03]
[25.40]
[88.90]
1-1/16
[26.99]
2-7/8
[73.07]
19
Ø1 [25.40] X
2 [50.80] LONG 1 NPT [482.6]
CABLE
4 [101.6]
18 AWG
LEAD WIRE
The Mini-Size Series L10 Flotect® Level Switches combine low cost with top quality
materials and construction for great value and years of reliable liquid level control. Wide
media compatibility is assured with a choice of brass or SS bodies and external tees;
polypropylene or SS floats. Two basic configurations are offered; with 1" male NPT
threads for direct side mounting through a half coupling or with factory installed tee for
external mounting.
All Series L10 switches feature a hermetically sealed, magnetically actuated SPST reed
switch which is encapsulated in a polypropylene housing. Units are quickly and easily
adjusted for your choice of normally open or normally closed operation thanks to a unique
design. Just loosen two screws and instantly slide the switch assembly to the action
required. NO and NC markings are clearly visible. This feature also speeds switch
replacement if damage occurs.
Three types of floats are offered to accommodate liquids with specific gravities as low as
0.5; max pressures to 2000 psig (137.8 bar). These controls are UL recognized and CSA
listed.
Model
L10-B-3-O
L10-B-3-A
L10-B-3-C
L10-B-3-B
L10-B-3-H
L10-S-3-O
L10-S-3-A
L10-S-3-C
L10-S-3-S
L10-S-3-L
Body Material
Brass
Brass
Brass
Brass
Brass
303 SS
303 SS
303 SS
303 SS
303 SS
Installation/Mounting
Side Wall Mounting
Side Wall Mounting
Side Wall Mounting
Brass Tee
Brass Tee
Side Wall Mounting
Side Wall Mounting
Side Wall Mounting
304 SS Tee
304 SS Tee
Model
F7-MLK
External Float Chamber
Float Material
Polypropylene Spherical
304 SS Cylindrical
304 SS Spherical
Polypropylene Spherical
304 SS Spherical
Polypropylene Spherical
304 SS Cylindrical
304 SS Spherical
Polypropylene Spherical
304 SS Spherical
1
[25.40]
5-7/16 [138.13]
2-3/8
[60.33]
3
[76.20]
Min. S.G.
0.9
0.5
0.7
0.9
0.7
0.9
0.5
0.7
0.9
0.7
1/4 [6.35]
TRAVEL TO
NORMALLY
CLOSED
POSITION
2-7/8
[73.07]
19
[482.6]
CABLE
1 NPT
4 [101.6]
18 AWG
LEAD WIRE
SPECIFICATIONS
Service: Compatible liquids.
Wetted Materials:
Float: Solid polypropylene or 304 SS;
Body: Brass or 303 SS;
Magnet: Ceramic;
External float chamber (tee): None,
brass, or 304 SS;
Other: Lever arm, pin, spring, etc.:
301 SS, 302 SS, 316 SS.
Temperature Limit: 200°F (93°C).
Pressure Limit: See chart.
Enclosure Rating: Weatherproof,
meets NEMA 4X (IP66).
Max. Press. psig (bar)
1000 (69)
200 (13.8)
350 (24.1)
250 (17.2)
250 (17.2)
2000 (137.8)
200 (13.8)
350 (24.1)
2000 (137.8)
350 (24.1)
1
[25.40]
Switch Type: SPST hermetically
sealed reed switch. Field adjustable for
normally open or normally closed.
Electrical Rating: 1.5 A @ 24 VDC
res., 0.001 A @ 200 VDC res., 0.5A @
125 VAC.
Electrical Connections: 18 AWG, 19˝
(483 mm) long, PVC jacket. Rated
221°F (105°C).
Process Connection: 1˝ male NPT
standard on models without external
float chamber. Change 3 in model
number to 4 for 1-1/4˝, to 5 for 1-1/2˝,
or 6 for 2˝. 1˝ female NPT on models
with external float chamber.
Mounting Orientation: Horizontal with
index arrow pointing down.
Weight: Approximately 10 oz (0.283
kg) without external float chamber, 2.32
lb (1.05 kg) with external float chamber.
Specific Gravity: See chart.
Agency Approvals: CSA, UR.
Switch Enclosure: Nylon.
Multi-Level Switch Kit
One or Two Station Level Switch, Vertically Mount
1/2
[12.70]
2 NPT
TUBE
CONNECTOR
4
[101.60]
LEVEL
FLOAT TUBE
AND SWITCH
STATION
TUBE
UNION
TUBE
UNION
FLOAT TUBE
AND SWITCH
STATION
2-1/2
[63.50]
1/2˝
NPT
1 FITTING
ASSEMBLY
2˝ NPT
PIPE
MOUNTING
Level Switches,
Float
TUBE END
FITTINGS
1/2
[12.70]
Customize a level system to suit your application requirements. The F7-MLK MultiLevel Switch Kit contains all the components necessary for the design and fabrication of a
1 or 2 station level switch for pipe plug mounting. User can customize stem length (maximum
36˝), actuation point, distance between floats, and lead wire lengths. The switch kit is ideal
for general purpose, low specific gravity, gas and oil applications. Model F7-MLK includes
two level stations (switch, tube, and Buna-N float), two brass extension tubes 12˝ length,
four brass tube unions, one end fitting, and one mounting plug.
Model F7-MLK, Multi-Level Switch Kit
298
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
7/8 [22.23]
2 SWITCHES
1/2
[12.70]
10-29/32
[276.99]
9-7/32
12
8 [234.19]
[304.80]
[202.97]
2
EXTENSION
TUBES
1/2 [12.70]
SPECIFICATIONS
Service: Compatible liquids.
Wetted Materials (Float/Stem): BunaN/Brass.
Temperature Limits: 221°F (105°C).
Pressure Limits: 150 psig (10 bar).
Switch Type: SPST, normally open or
normally closed.
Electrical Rating: 60 Watts: 0.4A @
220 VAC, 0.5A @ 110 VAC,
0.2A @ 120 VDC, 0.5A @ 24 VDC.
7/8
[22.23]
1-1/8 [28.64]
7/8
[22.23]
4 TUBE
UNIONS
1-31/32
[49.91]
1-1/4
[31.75]
2 BUNA-N
FLOATS
1-29/32
[48.67]
1 TUBE
END FITTING
Electrical Connections: 22 AWG x
72˝ (183 cm) leads.
Process Connection: 2˝ male NPT
pipe plug.
Mounting Orientation: Up to 30°
angle from vertical.
Stem Length: 36˝ (91 cm) maximum.
Tube/Fitting Size: 1/2˝ OD.
Minimum Specific Gravity: 0.45.
Weight: 3.5 lb (1.6 kg).
299_Layout 1 7/14/14 11:55 AM Page 299
Series
F6 & F7
Level Switches - Horizontal/Specialty
Low Cost, Hermetically Sealed Contacts
Horizontal
F6-HPS-11
13/64 [5.16]
F6-MHS
M16 X 2
33/64
[13.1]
11-13/16
[300] 51/64
[20.24]
F6-MHS2
ø11/64
[ø17.46]
16-9/64
[420.69]
1/4
[6.35]
1-23/32 [43.66]
9/32 [7.14]
Specialty
F7-SS6
21/64 [8.33]
15/16 [23.81]
33/64
[13.1] 2X 3/4
[19.05]
21/64
[8.33]
3/8-24 UNF-2A
3/4 HEX
[19.05 HEX]
1-3/4 [44.45]
F7-EB
JUNCTION BOX
F7-EBX ONLY
2-3/4 [70]
7 [178]
Ø43/64
[17.02]
11/64
[4.31]
13/16 MIN
1-7/32 MAX [31.0] [20.6]
3/32
[2.54]
4-5/8 MAX
[116.8]
1-5/32 MAX [29.2]
APPROXIMATE ACTUATION LEVEL
3/4
[19.05]
F7-LL
1/2-14 NPT
1/8 NPT
2-3/32
[53]
1-15/32
[37] 15/16 1/4
[24] [6.4]
3-1/4
[82.55]
ø5/16
[ø7.94]
1/2 NPT
FEMALE
Ø5/16
[8.00]
1-19/32
[40.61]
FITTING CENTERLINE
F7-HSS
1
[25.4]
ø1-1/2
[ø38.1]
ø43/64
[ø17.07]
3-17/64 [83.10]
2X 11/16
[17.28]
ø11/16
[ø17.46]
1/2 NPT
15
[381]
3/8 [9.56]
1/2˝ NPT
1-13/32 [35.72]
3/4
21/64 [19.05]
[8.33]
3/4
[19.05]
F6-HPS-31
4-1/4
[107.95]
11-13/16
[300]
3-7/8
[98.43]
2-11/64 [55.17]
2-11/64 [8.33]
1/2 NPT
33/64
[13.1]
19/32
[15.03]
3/4 [19.05]
13/64 [5.16]
F6-HPS-21
M16 X 2
21/64 [8.33] 1-27/64 [36.12]
ø45/64 [ø17.86]
1/2 [12.7] HEX
Ø 5/16
[8]
Ø 1-7/8 [47]
F7-WBB
3-1/2
[89]
1-3/4 [44.5]
1-5/16
[33]
4-1/4 [108]
Ø2-5/8 [67]
Electrical
Rating
20 VA: 0.08A @
220 VAC N.O. operation
20 VA: 0.08A @
220 VAC N.C. operation
20 VA: 0.08A @
240 VAC
20 VA: 0.08A @
240 VAC
20 VA: 0.08A @
240 VAC
Wire
Leads
22 AWG,
24˝ (61 cm)
22 AWG,
24˝ (61 cm)
18 AWG,
24˝ (61 cm)
22 AWG,
72˝ (182 cm)
22 AWG,
25´ (7.6 m)
Mtg
3/8˝-24˝
UNF-2A
3/8˝-24˝
UNF-2A
3/4˝ NPT
female
1/8˝ NPT
male
–
Weight
oz (g)
2 (58)
2 (58)
5 lb 5 oz
(2.4 kg)
2 (58)
Level Switches,
Float
Style/
Material
Temperature Pressure
Min.
Applications
Float/Stem
Limits
Limits
S.G.
Bent stem/
316 SS/316 SS 300°F (149°C) 100 psig (7 bar)
0.70
Liquids with metal particles
316 SS/316 SS 300°F (149°C) 100 psig (7 bar)
0.70
F7-SS6B Bent stem/
Liquids with metal particles
Brass/316 SS 300°F (149°C) 500 psig (34 bar)
0.75
F7-EB‡** Non-intrusive bottle type/
Outside tank mounting
(Brass housing)
Vertical/
Polysulfone/
180°F (82°C) 50 psig (3 bar)
–
F7-LL
Detect levels as low as 5/8˝ Buna-N
25´ cable, slosh shield/
Brass/Buna-N 180°F (82°C) 150 psig (10 bar)
0.45
F7-WBB
Sumps, stand pipes
† F7-HSS is rated explosion-proof for Class I, Groups A, B, C, D; Class II, Groups E, F, G; Class III.
‡ Explosion proof model available with DPDT switch. Specify F7-EBX
**Model available with Normally Closed Switch. Specify F7-EBNC
Model
F7-SS6
LEVEL
Ø1-7/16 [37]
2-1/8 [54]
Series F6 & F7 Horizontal Mount Level Switches are designed to mount through the
Series F6 & F7 Specialty Level Switches are designed for unique applications. Model
walls of tanks and other vessels. Internally mounted models F6-HPS-11, F6-MHS and F7F7-SS6 can be used with viscous liquids or liquids with suspended metal particles. Use
SS6 are secured to the wall of the tank or vessel from the inside while model F6-HPS-21 is
model F7-LL for low level detection (≥5/8˝). The non-intrusive bottle style F7-EB mounts
mounted from the outside (externally). Models F7-HSS and F6-MHS2 can be installed
completely outside the tank at the actuation level. Suspend model F7-WBB in stand pipes
internally or externally.
or sumps for leak detection or drop into wells for ground-water monitoring.
Weight
Material
Temperature Pressure
Min. Electrical
Wire
Limits
oz (g)
Applications
Model
Float/Stem
Limits
S.G. Rating
Leads
Mtg
1.23 (38)
F6-HPS-11 Water, Oils, Chemicals
Polypropylene/ 176°F (80°C) 116 psig (8 bar)
0.60 20 VA: 0.08A @
20 AWG,
M16 x 2
Polypropylene
240 VAC
11.8˝ (30 cm)
1.23 (38)
F6-HPS-21 Water, Oils, Chemicals
Polypropylene/ 176°F (80°C) 116 psig (8 bar)
0.60 20 VA: 0.08A @
20 AWG,
1/2˝ NPT
Polypropylene
240 VAC
11.8˝ (30 cm)
1.41 (40)
F6-HPS-31 Water, Oils, Chemicals
Polypropylene/ 176°F (80°C) 116 psig (8 bar)
0.60 20 VA: 0.08A @
20 AWG,
1/2˝ NPT
Polypropylene
240 VAC
11.8˝ (30 cm)
3.35 (95)
F6-MHS
Corrosives
304 SS/304 SS 257°F (125°C) 218 psig (15 bar)
0.85 20 VA: 0.08A @
22 AWG,
M16 x 2
240 VAC
11.8˝ (30 cm)
4.8 (136)
F6-MHS2 Water, Oils, Chemicals
304 SS/304 SS 257°F (125°C) 363 psig (25 bar)
0.85 70 VA: 0.7A @
22 AWG,
1/2˝ NPT
250 VAC
11.8˝ (30 cm)
3 (94)
F7-HSS† High temp/pressure,
316 SS/316 SS 392°F (200°C) 300 psig (20.7 bar) 0.60 30 VA: 0.14A @
22 AWG,
1/2˝ NPT
corrosive, Expl.
220 VAC
24˝ (61 cm) (int/ext)
10.8 (310)
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
299
300_Layout 1 7/8/14 11:59 AM Page 300
Series
F6 & F7
Level Switches - Vertical
Low Cost, Reliable and Compact, Hermetically Sealed Contacts
1/8 NPT
F7-SB
F7-ST713
A
D
C
B
Series F6 & F7 compact level switches combine low cost and reliability with fast,
simple installation. Hermetically sealed reed switches are actuated by magnets
permanently bonded inside the float and can be easily adapted to open or close a circuit on
rising or falling levels. Vertical mount models are shipped with normally open switch
contacts which close as the float rises toward the mounting threads. Reverse switch action
by removing the float, rotating it end-for-end and replacing it on the stem. Vertical models
mount internally, oriented within 30° of vertical, or select optional fittings for external
mounting. Switch ratings are suitable for many solid state control systems and monitors
or alarms. Simple relay interfaces can be used for higher current applications.
Material
Float/Stem
Buna-N & Epoxy/
316 SS
High temp/pressure, 316 SS (CYC)/
F7-SS2
corrosives
316 SS
Corrosives
316 SS/
F6-SS
316 SS
Broad chemical
Polypropylene/
F7-MPP**
compatibility
Polypropylene
Polypropylene/
F7-MPP-NO** Broad chemical
compatibility
Polypropylene
Broad chemical
F7-PP
Polypropylene &
compatibility
Epoxy/Polypropylene
Oils & Fuels
F7-BT
Buna-N & Epoxy/
PBT*
Food/beverage,
F7-K
PVDF/
corrosives
PVDF
General purpose
F7-C11
Buna-N/
Brass
Oils & water,
F7-C21
Buna-N/
general purpose
316 SS
High viscosity liquids Buna-N/
F7-BB
Brass
Water-based liquids, Polysulfone/
F7-PS
complies with FDA
Polysulfone†
Chemical & plating
F7-PVC
CPVC/
CPVC
Viscous, sticky or
F7-T1
PTFE/
corrosive liquids
TFE
F7-ST713
Oils, water &
316 SS/
chemicals
316 SS
Level Switches,
Float
LEVEL
Model
F7-SB
Applications
General purpose
Temp.
Limits
220°F
(105°C)
300°F
(149°C)
257°F
(125°C)
180°F
(82°C)
176°F (80°C)
220°F
(105°C)
220°F (105°C)
180°F
(82°C)
180°F
(82°C)
180°F
(82°C)
180°F
(82°C)
225°F
(107°C)
180°F
(82°C)
300°F
(149°C)
300°F
(149°C)
Press.
Limits
150 psig
10 bar
450 psig
31 bar
218 psig
15 bar
100 psig
6.89 bar
100 psig
6.89 bar
100 psig
6.89 bar
150 psig
10 bar
100 psig
6.89 bar
150 psig
10 bar
150 psig
10 bar
150 psig
10 bar
50 psig
3 bar
15 psig
1 bar
30 psig
2 bar
750 psig
52 bar
300
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
Model
F7-SB
F7-SS2
F6-SS
F7-MPP
F7-PP
F7-BT
F7-K
F7-C11
F7-C21
F7-BB
F7-PS
F7-PVC
F7-T1
F7-ST713
F7-ST714
(A) Stem
Length
2.75 (70)
2.06 (52)
2.17 (55)
1.63 (41)
2.18 (55)
2.18 (55)
2.13 (54)
2.06 (52)
2.06 (24)
3.19 (81)
3.38 (86)
3.44 (87)
3.47 (88)
3.38 (86)
3.38 (86)
Min. Electrical
S.G. Rating
0.60 25 VA: 1A @
220 VAC
0.75 25 VA: 1A @
200 VAC
0.65 20 VA: 0.08A @
240 VAC
0.90 10 VA: 0.1A @
100 VAC
0.90 50 VA: 0.2A @
240 VAC
0.60 30 VA: 0.14A @
220 VAC
0.45 30 VA: 0.14A @
220 VAC
1.00 50 VA: 0.25A @
150 VAC
0.45 20 VA: 0.08A @
240 VAC
0.45 20 VA: 0.08A @
240 VAC
0.55 20 VA: 0.08A @
240 VAC
0.55 20 VA: 0.08A @
240 VAC
0.85 20 VA: 0.08A @
240 VAC
0.80 20 VA: 0.08A @
240 VAC
0.80 20 VA: 0.08A @
240 VAC
①Distance between hex and liquid (S.G. = 1.0) level at actuation point will vary with
specific gravity changes.
*PBT - Polybutylene Terephthalate.
†Incudes 316 SS clip.
‡Spherical floats.
** F7-MPP is normally closed/F7-MPP-NO is normally open
UL Listed
Dimensions in Inches (mm)
(B) Float
Diameter
1.38 (35)
1.0 (25)
1.11 (28)
0.63 (16)
1.18 (30)
1.18 (30)
1.0 (25)
1.0 (25)
1.0 (25)
1.88 (48)
1.88 (48)
1.5 (38)
2.13 (54)
2.06 (52)
2.06 (52)
(C) Float
Height
1.13 (29)
1.0 (25)
1.11 (28)
0.63 (16)
1.0 (25)
1.0 (25)
1.0 (25)
1.0 (25)
1.0 (25)
1.81 (46)
1.88 (48)
1.81 (46)
1.94 (49)
2.06 (52)
2.06 (52)
(D) Actuation
from Hex①
1.2 (31)
0.73 (19)
–
0.47 (12)
0.69 (18)
0.69 (18)
0.65 (17)
0.56 (14)
0.56 (14)
1.19 (30)
1.25 (32)
0.75 (19)
0.92 (22)
1.09 (28)
1.09 (28)
Wire
Leads
22 AWG 18˝ (45 cm)
Mtg
NPT (M)
1/8˝
Weight
oz (g)
2 (58)
22 AWG 18˝ (45 cm)
1/8˝
1.2 (34)
20 AWG 11.8˝ (30 cm) 1/8˝
1.59 (45)
22 AWG 24˝ (61 cm)
1/8˝
0.8 (23)
22 AWG 24˝ (61 cm)
1/8˝
0.8 (23)
22 AWG 24˝ (61 cm)
1/8˝
0.8 (23)
22 AWG 24˝ (61 cm)
1/8˝
0.7 (20)
22 AWG 24˝ (61 cm)
1/8˝
1.5 (43)
22 AWG 24˝ (61 cm)
1/8˝
1.5 (43)
22 AWG 24˝ (61 cm)
1/8˝
1.5 (43)
22 AWG 24˝ (61 cm)
1/4˝
5 (140)
22 AWG 24˝ (61 cm)
1/4˝
4 (110)
22 AWG 24˝ (61 cm)
1/4˝
5 (140)
22 AWG 24˝ (61 cm)
1/4˝
6 (170)
22 AWG 24˝ (61 cm)
1/4˝
6 (170)
OPTIONAL FITTINGS — For external mounting of vertical models
A-347, 1/8˝ x 1-1/4˝ NPT carbon steel adapter
A-347-SS, 1/8˝ x 1-1/4˝ NPT 316 SS adapter
A-348, 1/8˝ x 1-1/2˝ NPT carbon steel adapter
301_Layout 1 7/9/14 11:22 AM Page 301
Series
F7-MQ
Quick-Ship Multi-Station Level Switch
Fast Delivery, Customized, Up to Four Actuation Levels
Float Dimensions
L4
A
1-3/4
[44.45]
L3
Ø 1-1/4
[31.75]
LO
L2
B
F1
1-13/16
[46.02]
2-3/32
[53.16]
Ø 1-7/8
[47.62]
Ø 2-1/16
[52.37]
F2
F3
L1
D
A
B
D
1-1/2˝
3˝
2˝
(38.10 mm) (76.20 mm) (50.80 mm)
Actuation Levels
Each switching point requires one float.
A = Minimum distance from actuation point to bottom of mounting.
B = Minimum distance between actuation levels.
D = Minimum distance from end of unit to lowest actuation point.
Customize level switches to meet application requirements quickly and affordably.
Switches can be configured with up to four different control points and stem lengths up to
72˝ (1.82 m). Stems and floats are available in 316 SS or brass.
Models are built to your specifications
Example
Construction
Stem & Connection
Material
Connection Type
Set Point Distance
Overall Length
Options
L4
L3
L2
L1
L0
Type 1
Type 2
1/2 NPT
1-1/4 SQ
[31.75]
2 NPT
Type 3
SPECIFICATIONS
Service: Compatible liquids.
Temperature Limits: F1 and F2 with water: 0 to 180°F (-18 to 82°C); Oil: -40 to
230°F (-40 to 110°C); F3: -40 to 300°F (-40 to 149°C).
Electrical Connections: 24˝ (61 cm) free leads; #22 AWG TFE and #18 AWG
polymeric.
Mounting Orientation: Vertical ±30°.
00.00
00.00
00.00
00.00
LEVEL
Switch Type
1/2 NPT
1.000 SQ
[25.40]
1-1/4 NPT
1/2 NPT
J F7-MQB1-4F33-07.00-11.00-15.00-20.00-24.00-J
Multi-station level, 1 to 4 switch points
Brass with Beryllium copper stops
316SS with SS ARMCO PH-15-7MO stops
1/2˝ NPT (Float F2, F3 only)
1-1/4˝ NPT (Float F1 only)
2˝ NPT (Float F2, F3 only)
Put 1 to 4 for the number of switch points desired
Buna-N, min. s.g. 0.75, 150 psi (10.3 bar) max. pres.
Buna-N, min. s.g. 0.55, 150 psi (10.3 bar) max. pres.
316SS, min. s.g. 0.75, 750 psi (51.7 bar) max. pres.
SPST, .17A @ 120 VAC, .08A @ 240 VAC, .13A @ 120 VDC, .06A @ 240 VDC
SPDT, .17A @ 120 VAC, .08A @ 240 VAC, .13A @ 120 VDC, .06A @ 240 VDC
NO switch is standard. For NC place an “*” after the corresponding set point distance in the model number.
In inches referenced from bottom of connection
F7-MQ B 1 4 F3 3
F7-MQ
B
S
1
2
3
#
F1
F2
F3
1
3
Switch Points
Float Type
Mounting Dimensions
Repeat for each switch point with dashes in between.
No numbers needed beyond the number of switches specified. In inches for example 12.25 would be
12.25˝ from the bottom of the process connection.
Minimum length is L1+D. Maximum length with Connection Length is 72˝ (1.82 m)
00.00
J Junction box for wire leads, NEMA 4 (Not available with Connection Type 1)
Level Switches,
Float
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
301
302_Layout 1 7/9/14 11:49 AM Page 302
Series
F7-MM
Miniature Multi-Station Level Switch
Custom, Lightweight, Low Cost, 316 SS or Buna-N Floats
Float Dimensions
L5
15/16
[23.80]
A
Ø1.000
[25.40]
L4
F1
B
L3
LO
1-3/32
[27.79]
Ø 29/32
[22.86]
F3
1-7/32
[30.99]
1-1/32
[26.16]
F6
F4, F5
L2
Ø 1-1/2
[38.10]
F2
1-19/32
[40.49]
Ø 29/32
[22.61]
1
[25.40]
1-1/4
[31.75]
Ø 29/32
[22.86]
1-1/8
[28.58]
1-9/64
[29.79]
F7
F8
Mounting Dimensions
L1
A (in.)
7/8
3/4
3/4
13/16
9/16
15/16
13/16
3/4
B (in.)
1-3/4
1-7/8
1-13/16
2-7/16
2-7/16
1-7/8
2
1-7/8
D (in.)
3/4
1-1/16
15/16
1-7/16
1-3/4
7/8 (NO); 1-3/16 (NC)
1-1/8
1-1/16
Actuation Levels
Each switching point requires one float.
A = Minimum distance from actuation point to bottom of mounting.
B = Minimum distance between actuation levels.
D = Minimum distance from end of unit to lowest actuation point.
LEVEL
Example
Construction
Stem & Connection
Material
Connection Type
Switch Points
Float Type
F1
F2
F3
F4
F5
F6
F7
F8
Switch Type
Level Switches,
Float
F7-MM B 1 5 F1 1
F7-MM
B
S
1
2
3
4
5
6
#
1
2
Set Point Distance L5
L4
L3
L2
L1
Overall Length
L0
302
00.00
00.00
00.00
00.00
00.00
1 NPT
Type 2
Type 1
Ø 3-5/8
[92.08]
1/8 NPT
6 HOLES
Ø 5/16
[7.95]
EQUALLY
SPACED
ON A
3.000 B.C.
[76.20]
Type 3
1-1/2 HEX
[38.10]
3/8-24
THREAD
1-5/16-12
THREAD
3/16
[4.78]
Miniature custom level switches with a sturdy, lightweight design are ideal for tanks
less than four feet (1.2 m) deep. Control up to five different level points across a maximum
length of 48˝ (121 cm). Stems and mounting fixtures are available in 316 SS or brass.
Models are built to your specifications
1-5/16 HEX
[33.32]
3/4 NPT
1/2 HEX
[12.7]
D
Float Type
F1
F2
F3
F4
F5
F6
F7
F8
1-1/16 HEX
[26.97]
1/8 NPT
[.125]
Type 4
Type 5
Type 6
SPECIFICATIONS
Service: Compatible liquids.
Wetted Materials: Stem, connection, and float.
Temperature Limits: F1 and F2: Water, 180°F (82.2°C); Oil, -40 to 250°F
(-40 to 121.1°C). All other floats: -40 to 300°F (-40 to 148.9°C).
Electrical Connection: 24˝ (61 cm) free leads #22 AWG, TFE jacketed.
Mounting Orientation: Vertical ±30°.
F7-MMB1-5F11-03.00-07.00-11.00-15.00-20.00-25.00
Multi-station level, 1 to 5 switch points
Brass with Beryllium copper stops
316SS with SS ARMCO PH-15-7MO stops
1/8˝ NPT
3/4˝ NPT (Cannot be used with float F1, F3, F7 and F8)
1˝ NPT (Cannot be used with float F3)
3-5/8˝ Flange [Maximum pressure is 50 psi (3.45 bar)]
1-5/16-12UNF-2A (Cannot be used with float F3)
3/8-24
Put 1 to 5 for the number of switch points desired
Material Min. s.g. Max. Pres. psi (bar)
Buna-N .45
300 (20.68)
Buna-N .60
250 (17.24)
316SS
.70
100 (6.89)
316SS
.85
150 (10.34)
316SS
1.1
400 (27.58)
PTFE
.65
1000 (68.95)
316SS
.85
275 (18.96)
316SS
.90
600 (41.37)
SPST, .17A @ 120 VAC, .08A @ 240 VAC, .13A @ 120 VDC, .06A @ 240 VDC
SPST, .8A @ 120 VAC, .4A @ 240 VAC
NO switch is standard. For NC place an “*” after the corresponding set point distance in the model number.
In inches referenced from bottom of connection
Repeat for each switch point with dashes in between.
No numbers needed beyond the number of switches specified. In inches for example 12.25 would be
12.25˝ from the bottom of the process connection.
00.00 Maximum overall length of 48 inches (121 cm). Minimum length is L1 + D.
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
303_Layout 1 7/9/14 11:45 AM Page 303
Series
F7-MS
Multi-Station Level Switch
Customize To Fit Application, Up to Six 316 SS or Buna-N Floats
Float Dimensions
L6 A
L5
Ø 1-1/4
[31.75]
L4
Ø 1-7/8
[47.62]
F2
F1
B
Mounting Dimensions
1/2 NPT
L2
Type 1
L1
1/2
NPT
D
1-1/4
NPT
A
B
D
1-1/2˝
3˝
2˝
(38.10 mm) (76.20 mm) (50.80 mm)
Customize level switches to meet application requirements. These switches can be
configured with up to six different control points and stem lengths up to 140˝ (3.56 m).
Stems and floats are available in 316 SS or brass.
Models are built to your specifications
Set Point Distance
Overall Length
Options
L6
L5
L4
L3
L2
L1
L0
1
[25.40]
1/2 NPT
1/2 NPT
1-1/4 SQ
[31.75]
2 NPT
Type 3
Type 4, 5
SPECIFICATIONS
Service: Compatible liquids.
Wetted Materials: Stem, connection, and float.
Temperature Limits: Buna-N floats: 180°F (82.2°C) in water, -40 to 230°F (-40 to
110°C) in oil; SS floats: -40 to 300°F (-40 to 148.9°C).
Wire Leads: 24˝ (61 cm) free leads; #22 AWG, TFE jacketed, and #18 AWG
polymeric.
Mounting Orientation: Vertical ±30°.
J F7-MSB1-5F31-04.00-07.00-11.00-15.00-20.00-24.00-J
Multi-station level, 1 to 6 switch points
Brass with Beryllium copper stops
316SS with SS ARMCO PH-15-7MO stops
1/2˝ NPT (Float F2, F3 only)
1-1/4˝ NPT (Float F1 only)
2˝ NPT
3˝ 150# Flange Carbon Steel (Conn. material S only, float F2, F3 only) [Max. pres. 150 psi (10.3 bar)]
3˝ 150# Flange 316SS (Conn. material S only, float F2, F3 only) [Max. pres. 150 psi (10.3 bar)]
Put 1 to 6 for the number of switch points desired
Buna-N, min. s.g. 0.75, 150 psi (10.3 bar) max. pres.
Buna-N, min. s.g. 0.55, 150 psi (10.3 bar) max. pres.
316SS, min. s.g. 0.75, 750 psi (51.7 bar) [units >72˝: 300 psi (20.7) bar] max. pres.
SPST, .17A @ 120 VAC, .08A @ 240 VAC, .13A @ 120 VDC, .06A @ 240 VDC
SPST, .8A @ 120 VAC, .4A @ 240 VAC
SPDT, .17A @ 120 VAC, .08A @ 240 VAC, .13A @ 120 VDC, .06A @ 240 VDC
NO switch is standard. For NC place an “*” after the corresponding set point distance in the model number.
In inches referenced from bottom of connection.
00.00
00.00
00.00
00.00
00.00
00.00
LEVEL
F7-MS B 1 5 F3 1
F7-MS
B
S
1
2
3
4
5
#
F1
F2
F3
1
2
3
Switch Type
Ø7-1/2
[190.5]
1.000 SQ
[25.40]
Type 2
Actuation Levels
Each switching point requires one float.
A = Minimum distance from actuation point to bottom of mounting.
B = Minimum distance between actuation levels.
D = Minimum distance from end of unit to lowest actuation point.
Switch Points
Float Type
F3
6 HOLES
Ø 3/4 [19.05]
EQUALLY
SPACED
ON A
6.000 B.C.
[152.4]
LO
L3
Example
Construction
Stem & Connection
Material
Connection Type
2-3/32
[53.16]
Ø2-1/16
[52.37]
1-13/16
[46.02]
1-3/4
[44.45]
Repeat for each switch point with dashes in between.
No numbers needed beyond the number of switches specified. In inches for example 12.25 would be
12.25˝ from the bottom of the process connection.
00.00
Minimum length is L1+D. Maximum length with Connection Type 1: 36˝ (91.4 cm),
Type 2: 60˝ (152.4 cm), and Types 3, 4, 5: 140˝ (355.6 cm).
J Junction box for wire leads, NEMA 4 (Not available with Connection Type 1)
Level Switches,
Float
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
303
304_Layout 1 7/9/14 11:54 AM Page 304
Series
123
Boiler Water Level Control
Heavy Duty, Cast Iron Chamber
1 NPT
1-1/8
[28.58] 3-9/16
[90.50]
Ø5-3/4
[146.05]
1/2 PIPE PLUG
TYP 2 PLACES
5-3/8
[136.53]
5-1/2
7 [139.70]
[177.80]
A special snap action mechanism eliminates frequent operation due to surging water level.
Visible operation adds convenience in servicing. SS trim and hand reset are available if
required. Options include DPDT switch, two stage, and weatherproof housing.
APPLICATIONS
• Boiler low water cut-off
• Boiler feed-water control
• Condensate tanks
• Deaerators
Model
123-153
123-7000-153
Switch Type
SPDT Mercury
SPDT Snap
Series
102
7-1/8
[180.98]
SPECIFICATIONS
Service: Compatible liquids. Cast iron
is not for use with lethal or flammable
substances either liquid or gaseous.
Wetted Materials: Body: Cast iron;
Float: 304 SS; Trim and packing gland:
Brass; Packing: Carbon; Body gasket:
Carbon.
Temperature Limit: 365°F (185°C).
Pressure Limit: 150 psig (10.34 bar).
Enclosure Rating: General purpose.
Optional weatherproof.
Switch Type: SPDT snap switch or
mercury switch. Optional DPDT or two
stage.
3-9/16
[90.50]
4-3/4
[120.65]
2-7/16
[61.91]
Electrical Rating: Snap switch: 15A @
120/240/480 VAC, 0.5A @ 120 VDC
resistive, 0.25A @ 240 VDC resistive;
Mercury switch: 4A @ 120 VAC/DC, 2A
@ 240 VAC/DC.
Electrical Connections: Screw
terminal.
Conduit Connection: 7/8˝ (22.23 mm)
hole for 1/2˝ (12.7 mm) conduit.
Process Connections: 1˝ female NPT.
Mounting Orientation: Vertical.
Weight: 20 lb (9.1 kg).
Agency Approvals: CSA, UL. (Snap
switch is not rated).
Deadband: Approximately 1-1/2˝
(38.1 mm).
Specific Gravity: 0.88 min.
Options: Manual reset.
Flanged Chamber Type Level Control
Operating Pressures to 300 PSIG
6-3/4
[171.45]
Ø5-3/4
[146.05]
3/4 NPT CONDUIT
CONNECTION. CAN
BE ROTATED 360˚.
1 NPT
17-1/2
[444.5]
SP. GR. A
1.0
5-1/16
(129 mm)
0.6
5-13/16
(148 mm)
B
8-1/4
[209.55]
A
LEVEL
1-5/8
[41.28]
Flanged inspection plate allows periodic inspection and clean-out of Model 102 float
chamber, making this unit ideal for use in refineries, chemical plants, and other areas with
potentially dirty liquids. Low cost cast iron chamber is standard. Carbon steel and SS
chambers are available on special order. SS float is standard.
Switch Type
SPDT Mercury
SPDT Snap
SPDT Hermetically Sealed Snap
Level Switches,
Float
Model
102-WT-4810-C-60
102-WT-7810-C-60
102-WT-7810HM-C-60
304
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
3-1/4 4-7/8
[82.55][123.83]
B
3/4
(19 mm)
1
(25.4 mm)
6-1/8
[155.58]
SPECIFICATIONS
Service: Compatible liquids. Cast iron
is not for use with lethal or flammable
substances either liquid or gaseous.
Wetted Materials: Body: Cast iron.
Optional cast steel or 316 SS; Float
and trim: 303 SS, 304 SS, 316 SS, and
430 SS. Option of all 316 SS; Body
gasket: Carbon.
Temperature Limit: 425°F (218°C).
Pressure Limit: 300 psig (20.7 bar).
Optional rating to 400 psig (27.6 bar).
Enclosure Rating: NEMA 4X (IP66).
Optional general purpose or explosionproof.
Repeatability: ±1/4˝ (6.4 mm).
Switch Type: SPDT snap switch,
hermetically sealed snap switch, or
mercury switch. Optional DPDT or two
stage.
Electrical Rating: Snap switch: 12A @
120 VAC, 5A @ 240 VAC, 0.5A @ 125
VDC resistive, 0.25A @ 250 VDC
resistive; Hermetically sealed snap
switch: 5A @ 125 VAC, 5A @ 240
VAC, 5A @ 30 VDC resistive; Mercury
switch: 4A @ 120 VAC/DC, 2A @ 240
VAC/DC. Higher contact ratings
available for the mercury switch.
Electrical Connections: Screw
terminal.
Conduit Connection: 3/4˝ female
NPT.
Process Connections: 1˝ female NPT.
Mounting Orientation: Vertical.
Set Point Adjustment: ±1˝ (25.4 mm).
Weight: 35 lb (15.9 kg).
Agency Approvals: UL.
Specific Gravity: 0.6 min.
305_Layout 1 7/8/14 11:54 AM Page 305
Series
CFS2
Cable Float Switch
Mercury-Free, UL/CSA Approved Options
1-41/64 [41.50]
5-5/32
[131.00]
3-3/16 [81.00]
6-15/64
[158.50]
4-9/64
[105.00]
Scan here
to watch
product video
The Series CFS2 Cable Float Switch is a mechanically actuated floating switch
intended to activate electrical components, usually pumps, to start and stop automatically.
The CFS2 is perfect for simple level control of liquids for filling or draining reservoirs and
tanks. Float switches such as the CFS2 are the most universally used for pump automation,
due to their high reliability, economical pricing, and easy installation. Counterweights and
cable hangers are available to suit a variety of mounting applications. Optional cables
available include those with UL/CSA approval, higher chemical compatibility, high
temperature durability, oil resistance, and drinking water suitability. Contact factory for
piggyback plug option, gold contact switch option and cable length options ranging from
10 to 70 ft (3.04 to 21.34 m).
SPECIFICATIONS
Service: Compatible liquids.
Wetted Materials: Enclosure:
Polypropylene; Cable: See model
chart.
Temperature Limits: 32 to 122°F (0 to
50°C).
Pressure Limits: 14.5 psi (1 bar).
Enclosure Rating: IP68.
Switch Type: See model chart.
Electrical Rating:
CFS2-XXBXX-XX:
10 (8) A @ 250 VAC;
CFS2-XXDXX-XX:
1 HP @ 125 VAC 16 FLA;
2 HP @ 250 VAC 12 FLA.
Shipping Weight:
Enclosure: 5.43 oz (154 g);
Cable: 0.77 oz (21.27 g) per ft.
Agency Approvals: See model chart.
ACCESSORIES
A-457, 7.76 oz (220 g) counterweight
A-459, Cable hanger
Model
CFS2-ONBPN-20
CFS2-ONBPN-30
CFS2-ONBPN-40
CFS2-ONBPN-50
CFS2-CNBPN-20
CFS2-CNBPN-30
CFS2-CNBPN-40
CFS2-CNBPN-50
CFS2-DNBPN-7
CFS2-DNBPN-10
CFS2-DNBPN-15
CFS2-DNBPN-20
CFS2-DNBPN-30
Cable Type
PVC
PVC
PVC
PVC
PVC
PVC
PVC
PVC
PVC
PVC
PVC
PVC
PVC
Approvals
CE
CE
CE
CE
CE
CE
CE
CE
CE
CE
CE
CE
CE
Series
FSW2
Switch Type
SPST NO
SPST NO
SPST NO
SPST NO
SPST NC
SPST NC
SPST NC
SPST NC
SPDT
SPDT
SPDT
SPDT
SPDT
Cable Length
20 ft (6.10 m)
30 ft (9.14 m)
40 ft (12.19 m)
50 ft (15.24 m)
20 ft (6.10 m)
30 ft (9.14 m)
40 ft (12.19 m)
50 ft (15.24 m)
7 ft (2.13 m)
10 ft (3.05 m)
15 ft (4.57 m)
20 ft (6.10 m)
30 ft (9.14 m)
Model
CFS2-DNBPN-40
CFS2-DNBPN-50
CFS2-DNBPN-60
CFS2-DNBPN-80
CFS2-DNBPN-100
CFS2-OGDSN-20
CFS2-OGDSN-30
CFS2-OGDSN-40
CFS2-OGDSN-50
CFS2-CGDSN-20
CFS2-CGDSN-30
CFS2-CGDSN-40
CFS2-CGDSN-50
Cable Type
PVC
PVC
PVC
PVC
PVC
SJOW
SJOW
SJOW
SJOW
SJOW
SJOW
SJOW
SJOW
Approvals Switch Type
CE
SPDT
CE
SPDT
CE
SPDT
CE
SPDT
CE
SPDT
UL/CSA
SPST NO
UL/CSA
SPST NO
UL/CSA
SPST NO
UL/CSA
SPST NO
UL/CSA
SPST NC
UL/CSA
SPST NC
UL/CSA
SPST NC
UL/CSA
SPST NC
Cable Length
40 ft (12.19 m)
50 ft (15.24 m)
60 ft (19.29 m)
80 ft (24.38 m)
100 ft (30.48 m)
20 ft (6.10 m)
30 ft (9.14 m)
40 ft (12.19 m)
50 ft (15.24 m)
20 ft (6.10 m)
30 ft (9.14 m)
40 ft (12.19 m)
50 ft (15.24 m)
Free-Floating Level Switch
Designed for Industrial Applications, Mercury-Free, Self Counter-Weighted
8-23/64
[212.50]
5/8
[16.00]
SPECIFICATIONS
Service: Compatible liquids, slurries.
Wetted Materials: Enclosure:
Polypropylene; Cable: PVC.
Operating Temperature: 32 to 122°F
(0 to 50°C).
Pressure Limits: 29 psi (2 bar).
Enclosure Rating: IP68.
Cable Length
10 ft (3.05 m)
15 ft (4.57 m)
20 ft (6.10 m)
30 ft (9.14 m)
40 ft (12.19 m)
50 ft (15.24 m)
60 ft (18.29 m)
80 ft (24.38 m)
100 ft (30.48 m)
4-23/64
[110.83]
Switch Type: See model chart.
Electrical Rating: 10 (8) A @ 250
VAC.
Mounting Orientation: Vertical.
Shipping Weight:
Enclosure: 2.4 lb (1100 g);
Cable: 0.77 oz (21.27 g) per ft.
Agency Approval: CE.
Level Switches,
Float
The Series FSW2 Free-Floating Level Switch is a mercury-free self counterweighted floating switch designed for the automation of pumps, specifically filling and
draining of tanks, wells, and reservoirs. The FSW2 body is free of any irregularities
making it ideal for use in sewage water applications. The polypropylene body consists of a
double airtight chamber with high-pressure melted polypropylene re-injection sealing to
ensure a perfect seal against infiltration. Cable hangers are available to suit a variety of
mounting applications. Featuring CE approval and optional cables available that include
higher chemical compatibility, high temperature durability, oil resistance, and drinking
water suitability. Contact factory for piggyback plug option, and cable length options
ranging from 10 to 70 ft (3.04 to 21.34 m).
Model
Model
Switch Type
Switch Type
Cable Length
FSW2-ONPN-20 SPST NO
FSW2-DNPN-10 SPDT
20 ft (6.10 m)
FSW2-ONPN-30 SPST NO
FSW2-DNPN-15 SPDT
30 ft (9.14 m)
FSW2-ONPN-40 SPST NO
FSW2-DNPN-20 SPDT
40 ft (12.19 m)
FSW2-ONPN-50 SPST NO
FSW2-DNPN-30 SPDT
50 ft (15.24 m)
FSW2-CNPN-20 SPST NC
FSW2-DNPN-40 SPDT
20 ft (6.10 m)
FSW2-CNPN-30 SPST NC
FSW2-DNPN-50 SPDT
30 ft (9.14 m)
FSW2-CNPN-40 SPST NC
FSW2-DNPN-60 SPDT
40 ft (12.19 m)
FSW2-CNPN-50 SPST NC
FSW2-DNPN-80 SPDT
50 ft (15.24 m)
FSW2-DNPN-100 SPDT
LEVEL
4-45/64
[119.50]
ACCESSORY
A-459, Cable hanger
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
305
306_Layout 1 7/29/14 3:10 PM Page 306
Series
OLS
Optical Level Switch
Low Cost, Compact, LED Indication, No Moving Parts
1/2 NPT
7/8 HEX
[22.23 HEX]
OLS-10
OLS-11
1/16
[1.59]
1-3/4
[44.45]
OLS-12
Low cost, rugged optical level switch provides rapid response while employing no
moving parts for stable process control. The bright red and green LED’s indicate the
presence or absence of liquid for true, local indication. Three optional materials, 316 SS,
polysulfone and PFA provide application flexibility. Compact switch can be quickly mounted
horizontally or vertically for each installation.
SPECIFICATIONS
Service: Noncoating compatible
liquids.
Wetted Materials: See model chart.
Temperature Limit: Process: OLS-10,
11: 200°F (93.3°C), OLS-12: 120°F
(48.9°C); Ambient: OLS-10, 11: 175°F
(79.4°C), OLS-12: 120°F (48.9°C).
Pressure Limit: OLS-11, 12: 200 psig
(13.8 bar); OLS-10: 1000 psig (69 bar).
Repeatability: ±0.02˝ (0.5 mm).
Switch Type: NPN open collector.
Principles of Operation
The optical level switch employs an LED, which transmits infrared light. This light is sent
through a prism and reflected back to a photo-transistor utilizing two 90° light reflections.
With the prism surrounded by a gas, the light source is cast back to the photo transistor.
When a translucent liquid is introduced to the prism at or above the point where the light
source makes contract with the prism, the light is reflected into the liquid, not allowing
the photo-transistor to energize.
Model
OLS-10
OLS-11
OLS-12
APPLICATIONS
• Food and beverage systems
• Liquid holding tanks
• Hydraulic reservoirs
• Sumps
• Pharmaceutical systems
• Air conditioning systems
Series
B-190
HIGH
RED,
LOW
BLK, GNO
WHT, CONTROL
15/64
[5.95]
Power Requirements: 10 to 28 VDC.
Output Signal: Vout (max) = 28 VDC,
Isink (max) = 100 mA.
Current Consumption: 35 mA
maximum.
Electrical Connections: 38˝ (965.2
mm) 3 conductor cable, 22 AWG wire.
Process Connection: 1/2˝ male NPT.
Mounting Orientation: Can be
mounted in any position.
Weight: 3 oz (0.085 kg).
Specific Gravity: No minimum.
Wetted Materials
316 SS/Polysulfone
Polysulfone
PFA
Liquid Level Switches-Controls
Top Mounted Displacer Type, Adjustable Setpoints,
Magnetic Operation, Optional Hermetically Sealed Snap Switch
6-3/4 [171.45]
Ø5-3/4[146.05]
3/4
NPT
9-13/16
[249.24]
3 [76.20]
Dimensions for 1.0 s.g. @ 100°F (38°C)
A
TB
C
Max.
Min.
Max. Min.
Max.
116-1/2˝ 6-1/2 ˝
114˝ 6-3/4 ˝
2-1/2˝
(2.66m) (165mm) (2.9m) (172mm) (64mm)
A
B
OPERATES
ON LEVEL
RISE
C
LEVEL
TB
One of our most versatile level controls, the model B-l90 can be used on all types of
tank or sump level control applications. Three porcelain displacers provide deadband
adjustment. Unit can start a sump pump (for example) when liquid reaches the high set
point and turn the pump off when the level drops to the low set point. Unit works equally
well in pressurized tanks. Two stage units also available.
Switch Type
SPDT Mercury
SPDT Snap
SPDT Hermetically Sealed Snap
Level Switches
Optical/Displacer
Model
B190-WT-4810-P-A-1.0-2
B190-WT-7810-P-A-1.0-2
B190-WT-7810HM-P-A-1.0-2
306
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
B
Min.
122-1/4˝
(3.1m)
OPERATES
ON LEVEL
DROP
TO BOTTOM
Electrical Connections: Screw
SPECIFICATIONS
terminal.
Service: Compatible liquids.
Conduit Connection: 3/4˝ female
Wetted Materials: Cable, spring and
NPT.
stops: 316 SS. Optional Inconel®
spring; Displacers: Porcelain. Optional
Process Connections: 4˝ 125 cast
304 SS, 316 SS, or carbon graphite.
iron flange. Other material, size, and
Temperature Limits: 32 to 200°F (0 to
rating flanges are available.
93.3°C). Higher ratings available.
Mounting Orientation: Vertical.
Pressure Limit: 125 psig (8.6 bar).
Set Point Adjustment: Adjustable by
Higher ratings available.
moving displacers see dimension chart
Enclosure Rating: NEMA 4X. Optional
for minimum and maximum values.
general purpose or explosion-proof.
Weight: 25 lb (11.34 kg).
Switch Type: SPDT snap switch,
Agency Approvals: UL (None on HM
hermetically sealed snap switch, or
switch).
mercury switch. Optional DPDT or two
Deadband: Adjustable by moving
stage.
displacers see dimension chart for
Electrical Rating: Snap switch: 12A @
minimum and maximum values.
120 VAC, 5A @ 240 VAC, 0.5A @ 125
Specific Gravity: Standard is 1.0.
VDC resistive, 0.25A @ 250 VDC
Specify when ordering by replacing 1.0
resistive; Hermetically sealed snap
in model number with specific gravity
switch: 5A @ 120 VAC, 5A @ 240
setting desired. Settable range is 0.5 to
VAC, 5A @ 30 VDC resistive; Mercury
1.2.
switch: 4A @ 120 VAC/DC, 2A @ 240
Cable Length: 10´ (3 m) standard.
VAC/DC. Higher contact ratings
Optional up to 100´ (30.5 m).
available for the mercury switch.
Inconel® is a registered trademark of Huntington Alloys Corporation.
307_Layout 1 7/21/14 1:49 PM Page 307
Model
CLP
Conductivity Level Probe
Low Cost, Compact Design
ø3/8
[ø9.53]
ø7/16
[ø11.11]
1/2˝ NPT
ø1/8
[ø3.18]
ø23/64
[ø9.92]
19/32
[15.03]
1/4
[6.35]
51/64
[20.24]
2-13/32
[61.12]
3-35/64
[90.09]
ø1/4
[ø6.35]
9/16
[14.29]
6-19/32
[167.48]
Series CLP Conductivity Level Probes are used to determine the presence of a
conductive liquid at a set level by sensing conductivity. The Series CLP is coupled with the
Series TSWB Temperature Level Controller for a complete level control system. These
probes allow for the measurement of conductivity between the probe fitting and end, which
is isolated by a ceramic insulator, or between the probe ends of two probes. The CLP can
be mounted in any orientation in a tank, tee fitting, or any compatible threaded port. The
probe end is solid stainless steel allowing substantial resistance to heat and corrosion.
Model
CLP-1
Description
Conductivity Level Probe, 1/2˝ NPT
Model
DPL110
SPECIFICATIONS
Service: Conductive liquids compatible with wetted materials.
Wetted Materials:
Probe end: 430SS;
Insulator: Ceramic;
Fitting: Nickel-plated iron;
Seal: Silicone.
Temperature Limits: 392°F (200°C).
Pressure Limits: 87 psi (6 bar).
Electrical Connections: Snap-type post.
Process Connection: 1/2˝ NPT.
Mounting: Threaded port, any orientation.
Weight: 2 oz (57 g).
Dual Point Level Switch
Tank High/Low Control, Conductivity Technology, Up to 72” Probes
3-1/8
Ø2-17/64 [78.99]
[Ø57.40]
1-13/32
[35.43]
2-25/64
[60.58]
43/64
[16.89]
27-1/16
[687.39]
1 INCH NPT
24
[609.6]
Ø1/8
[Ø3.18]
Model DPL110, Dual Point Level Switch
59/64
[23.40]
3-47/64
[94.77]
SPECIFICATIONS
Electrodes: 1/8˝ dia, 24˝ (609.6 mm) L, standard.
Wetted Materials: 316 SS, polypropylene.
Mounting, Sensor Head: 1˝ male NPT.
Pressure Limits: 30 psig (2.06 bar).
Temperature Limits: 212°F (100°C).
Probe Enclosure: NEMA 6 (IP67).
Maximum Probe Length: 72˝ (1.8 m) with optional extensions.
Connecting Cable, Probe to Controller: 10´ (3.0 m).
Sensing Voltage: 12 VAC.
Power Supply: 120 VAC 50/60 Hz.
Output: SPDT, 5 A @ 240 VAC.
Mounting, Controller: Standard octal socket or 35 mm DIN rail.
Weight, Probe Assembly: 1.5 lb (0.68 kg).
Weight, Controller: 1.0 lb (0.45 kg).
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
Level Switches,
Conductivity
ACCESSORY
Model DPL5, Electrode Extensions includes three 24˝ (610 mm) electrode extensions
and mounting hardware
1-47/64 2-13/16
[43.94] [71.37]
LEVEL
Maintain liquid level high and low limits with the Model DPL Dual Point Level
Switch. Units can be used for single or dual point level control in semi-solid liquids,
industrial slurries or heavy-bodied liquids like wastewater. Standard 24 inch electrodes
can be cut by the end-user to a shorter length or lengthened by adding up to two 24˝
extensions (sold separately) to reach the max recommended length of 72˝. Model DPL
contains no moving parts to get stuck or wear out. Controller features adjustable
sensitivity and DIN rail-mountable socket mount.
CONTROLLER
2-15/64
[56.64]
307
308_Layout 1 7/8/14 11:53 AM Page 308
Series
CLS2
Capacitive Level Switch
Powder, Bulk, or Liquids, Auto-Calibration
4-3/16
[106.36]
Ø3/8
[Ø9.53]
4-1/8
[104.78]
2-19/64
[58.34]
22-21/64
[567.14]
19
[482.60]
3-19/32
[91.28]
Scan here
to watch
product video
The CLS2 is a capacitive technology level switch that does not have any moving parts
- no jams, no wear, nothing to break, and no maintenance. State of the art sensing
technology in the CLS2, using impulse RF admittance measurement combined with an
active guard, provides excellent level measurement and stability while being insensitive to
material buildup. This technology also provides immunity to external RF sources like
walkie-talkies and cell phones as well as minimal interference with radio communication
or other electronic systems.
Capacitive level technology can be used for liquids, powders, and bulk materials and is great
for difficult applications such as slurries, coating products, and liquids with solids. The
CLS2 is ideal for level indication in silos, receivers, and transporters in pneumatic conveying
systems. The CLS2 can also be used for liquid interface applications to detect the level of
two immiscible liquids that have different dielectric constants such as oil and water. Wetted
materials of PVDF and 316 SS assure great chemical compatibility and meet food grade
requirements.
FEATURES
• Automatic Calibration: No need to turn calibration pots, just push the
calibration button. The CLS2 even has an external magnet to activate the
calibration without having to open the enclosure.
• Universal Power Supply: One model works from 12 to 240 VAC/DC without
any jumpers or settings.
• Coat Guard: Unit is not affected by sticky, dusty, or clingy materials that coat or
build up on the probe, preventing false alarms.
• Failsafe Setting: Output switches can be set for NO or NC condition on loss of
power.
• Status Indication: Ultra high brightness external red LED switch status
indicator, and internal indicators for power, sensor, and switch status that can be
seen externally with window cap option (external LED on weatherproof model
only).
• Time Delay: Prevent false alarms from material splashing, agitation, etc.
• Removable Terminals: Removable terminal block snaps in and out enabling
easy wiring outside of the enclosure.
4-5/32
[105.57]
SPECIFICATIONS
Service: Liquids, powder, and bulk materials compatible with wetted materials.
Wetted Materials: 316 SS and polyvinylidene fluoride (PVDF).
Temperature Limits: Ambient: -40 to 185°F (-40 to 85°C), -4 to 185°F (-20 to
85°C) with under 24 VAC/DC power supply; Process: -40 to 250°F (-40 to 121°C).
Pressure Limit: 365 psi (25 bar).
Enclosure Rating: Weatherproof, NEMA 4X (IP66).
Switch Type: DPDT (two form C).
Electrical Rating: 8A @ 120/240 VAC res., 30 VDC. 1/2 hp @ 120 VAC and 1/4
hp @ 240 VAC ind.
Power Requirements: 12 to 240 VAC/DC.
Power Consumption: 2.8 watts max.
Electrical Connection: 1/2˝ NPT conduit opening, screw termination with
removable terminal block.
Process Connection: See model chart.
Mounting Orientation: Vertical or horizontal.
Set Point Adjustment: Trips when product touches probe. Cut or extend probe to
length of desired trip point. Can be cut as short as 1˝ and can be extended by
welding on to probe. (Minimum length will be effected by material being sensed.)
Response Time: 0.2 seconds.
Time Delay: Adjustable, 0 to 60 seconds.
Spark/Static Protection: 10 M Ω dissipation resistance with spark gap. Surge
current to 100A max.
Sensitivity: 8 Selectable settings, 1, 2, 4, 6, 8, 10, 14, 20 pF (at 30 pF nominal
free capacitance).
Agency Approvals: CE, cUL, UL.
Example
Series
Enclosure
Switch
LEVEL
Power
Supply
Probe Type
CLS2 W 1 1 R K 1 019 M20 CLS2-W11RK1-019-M20
CLS2
Capacitive Level Switch
W
Weatherproof
1
DPDT rated 8A @ 12/240 VAC, 30
VDC res.
12-240 VAC/DC
1
R
T
Standard Rod: 316 SS, .375˝ diameter
Threaded Rod: 316 SS (can attach
field extensions.)
Cable: 316 SS with weight
PVDF
C
Insulator
Material
Process
Connection
Level Switches,
Capacitive
Probe
Length
Options
308
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
K
1
2
3
4
5
6
8
9
3/4˝ male NPT
1˝ male NPT
1-1/2˝ male NPT
3/4˝ BSPT
1˝ BSPT
1-1/2˝ BSPT
1-1/2˝ sanitary clamp
2˝ sanitary clamp
XXX
Insertion length in inches. Example
019 is 19˝ length. (Minimum length
is 6˝, with 3/4˝ sensing tip)
M20 M20 conduit connection with cable
gland
WC Window Cap
309_Layout 1 7/8/14 11:53 AM Page 309
Model
FCLS
Flush Capacitance Level Switch
Maintenance Free, Flush Mounting
4-3/8
[110.95]
4-9/32
[108.83]
7-11/32
[186.34]
5-57/64
[149.43]
1/2˝ NPT
3-25/32
[96.16]
6-3/32
[154.94]
The Model FCLS Flush Capacitance Level Switch is ideal for level measurement of
liquids and bulk solids to trigger an alarm or close a filler inlet. No probe design allows for
installation where space is constrained or where material flow or material build up would
damage a probe. With no moving parts, this level switch assures no jams, no wear, nothing
to break, and no maintenance. Comes standard with IP65 housing with a maximum
pressure limit of 285 psi (19.7 bar).
Model FCLS-01, Flush Capacitance Level Switch
Model
CLS1
SPECIFICATIONS
Service: Liquids, powder, and bulk
materials compatible with wetted
materials.
Wetted Materials: 304 SS.
Insulated Materials: PTFE.
Temperature Limits: Ambient: -4 to
140°F (-20 to 60°C); Process: -4 to
176°F (-20 to 80°C).
Pressure Limit: 285 psi (19.7 bar).
Power Requirements: 110 or 220
VAC.
Power Consumption: 2 W.
Enclosure: Aluminum, painted.
Enclosure Rating: IP65.
Switch Type: SPDT.
Electrical Rating: 3 A @ 250 VAC.
Electrical Connections: Screw
terminals.
Conduit Connection: 2 x 1/2˝ female
NPT.
Process Connection: 2.5˝ - x 5 kg/cm2
JIS flange.
Mounting Orientation: Side mount.
Fail Safe: Selectable fail high or fail
low.
Adjustable Sensitivity: 1 to 20 pF.
Time Delay: 0 to 6 s.
Weight: 7.1 lb (3.2 kg).
Capacitance Level Switch
For Solids, Liquids or Slurries, Fail-Safe Protection, <1 pF Sensitivity
1-11/16
[42.88]
7/8
[22.23]
1/2 FEMALE
NPT CONDUIT
CONNECTION
6-3/16
[157.15]
21/32
[16.67]
1 MALE NPS
PROCESS
CONNECTION
1-13/16
[46.05]
8-5/8
[219.08]
3-13/16
[96.84]
1-7/64
[28.18]
APPLICATIONS
High or low level detection in bins, silos, tanks, hoppers, chutes and other vessels
where liquids, solids or slurries are stored.
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
309
Level Switches,
Capacitive
Model CLS1, Capacitance Level Switch
SPECIFICATIONS
Service: Solids, liquids, or slurries.
Wetted Material: CPVC.
Temperature Limits: Process: -40 to 240°F (-40 to 116°C); Ambient: -40 to 185°F
(-40 to 85°C).
Enclosure Rating: NEMA 4X (IP66), PVC, dust tight, water resistant.
Switch Type: SPDT.
Electrical Rating: 5A @ 250 VAC.
Power Requirements: 120 VAC, 1.5VA.
Conduit Connection: 3/4˝ female NPT.
Process Connection: 1˝ male NPS.
Mounting Orientation: Vertical or horizontal.
Sensitivity: Adjustable to <1 pF.
Fail-Safe: Switch selectable, high/Low.
Time Delay: Adjustable 1 to 30 seconds.
Weight: 2.0 lb (0.91 kg).
LEVEL
Model CLS1 Capacitance Level Switch provides reliable point level measurement of
solids, liquids and slurries in metallic or non-metallic tanks and vessels. Model CLS1
detects the presence or absence of material in contact with the probe by sensing a change
in the capacitance. Electronics provide highly sensitive measurement detection (requires
less than a 1 picofarad shift from ambient). State of the art technology ignores material
build-up on the vessel sidewall or along the probe assembly. One time calibration is simple
with a single multi-turn potentiometer. Red LED on housing indicates sensor status. Unit
features an adjustable 1-30 second time delay and a 5 amp, SPDT fail-safe relay output.
Model CLS1 can be mounted vertically or horizontally.
310_Layout 1 7/8/14 11:52 AM Page 310
Series
LTS
Tilt Switch Probe
Non-Mercury Probes
Probe
Type
Standard
Compact
A
A
in (cm)
9 (22.86)
6 (15.24)
B
in (cm)
1-7/8 (47.63)
1-7/16 (36.51)
B
The Series LTS Tilt Switch Probes are able to sense either the presence or absence
of material when other sensors won’t work due to bin vibration, or actual walls aren’t
available for mounting other types of measuring units. The probes are designed for use
where the bulk material to be sensed is exposed or open. Typical applications include high
or low level detection in large hoppers, silos, crushers, or trippers, high level control under
stackers, and detection of plugged conditions at conveyor transfer points. Series LTS
probes can also be used to detect the presence or absence of bulk material on belt
conveyors, on chutes to indicate product flow, and to aid in loading rail cars or trucks.
All probe models are airtight, dust tight, and waterproof. The compact probe should be
used for applications involving small bins and hoppers where space is limited, while the
heavy duty probe should be used for applications where a heavy duty abrasion-resistant
probe is necessary.
Model
LTS-N11G-025
LTS-N21G-025
LTS-N12G-025
LTS-N22G-025
Size
Standard
Compact
Standard
Compact
Probe Material
Steel
Steel
SS
SS
SPECIFICATIONS
Service: Powder and bulk.
Temperature Limit: -40 to 150°F (-40 to 66°C).
Switch Type: SPST, normally closed.
Electrical Rating: 0.25 A max, 60 V max, 3 VA max.
Electrical Connection: 16-3 type SO connection cable.
Cable Length: 25´ (7.6 m).
Probe Length: Standard: 9˝ (23 cm); Compact: 6˝ (15 cm).
Signal Voltage: 15 VDC (when used with LTC controller).
Actuation Angle: 25° from vertical.
Material: Steel or SS.
Switch Surrounding: Epoxy encapsulated.
Mounting Orientation: Vertical.
Weight: Standard: 4.75 lb (2.15 kg); Compact: 2.5 lb (1.13 kg).
Features: Fittings for hangers.
Enclosure Rating: Meets NEMA 4 (IP56).
Consult factory for custom cable lengths.
Series
LTC
Tilt Switch Control Unit
Adjustable Time Delay
1-9/32
[32.54]
4
[101.6]
1-21/32
[42.06]
RED LENS
8-1/4
[209.55]
9-1/2
[241.3]
6-3/64
[153.59]
LEVEL
8-3/4
[222.25]
GREEN LENS
4-7/8
[123.83]
3-29/32
[99.16]
Level Switches,
Tilt
The Series LTC Tilt Probe Control Units feature an adjustable time delay and a logic
selector switch. The logic selector switch determines when the output relay actuates and
de-actuates, thus while in position one, the relay is energized when the probe is in the
vertical position and de-energizes when the probe is in the titled position, and while in
position two, the actions are opposite. In addition, an adjustable time-delay feature may be
assigned to either the vertical or the tilt position to prevent false signals. The relay assumes
the de-energized position upon reaching the end of the delay period as well as upon failure
of power to the controller.
Model
LTC2
LTC3
310
Enclosure
NEMA 4
No-enclosure
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
SPECIFICATIONS
Temperature Limit: 125°F (52°C).
Power Requirements: 115 VAC @ 50/60 Hz.
Power Consumption: 10W.
Switch Type: DPDT.
Electrical Rating: 10 A @ 115 VAC.
Enclosure: None or carbon steel housing with polyester coating.
Enclosure Rating: None or NEMA 4 (IP56).
Electrical Connections: Screw terminal.
Conduit Connection: None.
Indicator Lights: Green (when relay is energized and probe vertical), Red (when
relay is de-energized and probe tilted).
Indication Light Power Required: 18 VDC.
Time Delay: 1 to 10 sec. Adjustment will delay output relay action.
311_Layout 1 7/8/14 11:52 AM Page 311
Series
TFLS
Tuning Fork Level Switch
Perfect for Sensing Low Bulk Density or Low Dielectric Materials
3/4 CONDUIT
CONNECTION
1-1/2 NPT
SERIES
TFLS TUNING FORK LEVEL SWITCH
7/8
[22.23]
MOD TFLSSERIAL:
ø4-7/16
[112.73]
4-7/8
[123.83]
3-5/8 [92.08]
COVER REMOVAL
Series TFLS tuning fork level switch is ideal for level control of powders and fine
grained solids, especially those with a low bulk density. The TFLS incorporates a
piezoelectric crystal that vibrates the fork at its natural frequency. When the fork comes
in contact with material the vibration is dampened and the switch changes state. As the
fork becomes free of material the switch changes back to its normal state. Featured in the
TFLS is user-selectable fail-safe operation of the contacts. Unit is not affected by vibration
from conveying systems, motors, or the movement of material. It can be mounted in any
position and is available with factory built extensions for mounting on the top of the storage
vessel.
Series TFLS is easy to use with no calibration required and with no mechanical moving
parts there is no routine maintenance required. The TFLS is unaffected by the dielectric
constant of the sensed material making it superior to a capacitance level switch for
applications where the dielectric constant is too low, where there is more than one material
being used in one vessel, and when material moisture content can change. The level switch
is also good for applications when the bulk density is too low for a rotating paddle level
switch. It can also detect granular material submerged in liquids of low viscosity, for
example sand, gravel, or polyester chips in water.
FEATURES
• No calibration required
• Vibrating fork design: Great for low bulk density and low dielectric constant
products. Will detect products down to 1.8 lb/ft3 (30 g/l)
• Universal power supply: One model works with 90 to 265 VAC and 24 VDC
• Adjustable sensitivity: Can be set to ignore lighter bulk density products and only
detect heavier products, such as sand in water
• Status indication: External LED switch indicator, and internal indicators for
normal and alarm status
• Failsafe setting: Output switch can be set for NO or NC condition on loss of
power
• Time delay: Prevent false alarms from material surges
4-7/32
[107.14]
7-5/8
[193.68]
8-5/8
[219.08]
“A”
Extension
Length
None
6 in
12 in
18 in
24 in
36 in
48 in
DIM
“A”
9-1/4 (234.95)
15-7/8 (403.23)
21-7/8 (555.63)
27-7/8 (708.03)
33-7/8 (860.43)
45-7/8 (1165.23)
57-7/8 (1470.03)
SPECIFICATIONS
Service: Dry powder or bulk materials compatible with wetted materials. Can
detect bulk materials submerged in liquid.
Sensitivity: Minimum bulk density of 1.8 lb/ft3 (30 g/l), max particle size 0.4´ (10
mm).
Wetted Materials: 316 SS.
Temperature Limits: Ambient: -4 to 140˚F (-20 to 60˚C); Process: -4 to 176˚F (-20
to 80˚C).
Pressure Limit: 145 psig (10 bar).
Power Requirement: 90 to 265 VAC, 50/60 Hz; 24 VDC.
Power Consumption: 4 VA.
Enclosure: Aluminum, powder coated.
Enclosure Rating: Weatherproof, NEMA 4X (IP66).
Switch Type: SPDT.
Electrical Rating: 5A @ 230 VAC.
Electric Connections: Screw terminals.
Conduit Connection: 3/4˝ female NPT.
Process Connection: 1-1/2˝ male NPT.
Weight: 5.5 lb (2.5 kg).
Indication Lights: External: Red LED; Internal: Green and red LED’s.
Sensing Delay: (Max) covered probe: 2 seconds; Uncovered probe: 3 to 7
seconds.
Time Delay: Separate settings for covering and uncovering the probe. Adjustable
from 2 to 20 s.
Series TFLS-W11SR1
Contact factory for fork extension options in carbon steel or stainless steel.
LEVEL
APPLICATIONS
Lime, styrofoam, tobacco, dry cereals, sugar, animal feed, milk powder, flour,
insulation, cement, paper shavings, plastic granules, sawdust, carbon black, light
fibers, detergent powders, dyes, chalk, silica, sand, wood chips.
Level Switches,
Tuning Fork
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
311
312_Layout 1 7/21/14 8:13 AM Page 312
Model
TFLS2
Compact Tuning Fork Level Switch
Compact, Cost Effective, For Bulk Solids
3-5/16
[84.00]
1˝ NPT
4-9/64 25/32
[105.00] [19.99]
Scan here
to watch
product video
63/64
[25.06]
The Model TFLS2 Compact Tuning Fork Level Switch is an ideal choice for level
control for powders. The TFLS2 incorporates a piezoelectric crystal that vibrates the fork
at its natural frequency. When the fork comes in contact with a material, the vibration is
dampened and the switch changes state. As the material is removed from the fork, the
switch changes back to its normal state. Featured in the TFLS2 is user selectable fail-safe
operation of the contacts. The unit is not affected by vibration from conveying systems,
motors, or the movement of material. Its compact size allows for mounting in places a
larger tuning fork level switch may not fit, providing great versatility.
The Model TFLS2 is easy to use with adjustable calibration, and no mechanical moving
parts means no routine maintenance. The TFLS2 is not affected by the dielectric constant
of the sensed material, making it superior to a comparable capacitance level switch for
applications where the dielectric constant is low, more than one material is being used in
the single vessel, and when material moisture content can change. The level switch is also
great for applications when the bulk density is too low for a rotating paddle level switch,
making it the ideal choice for low density bulk solids and liquids.
Model
CTF
SPECIFICATIONS
Service: Dry powder compatible with
wetted materials.
Sensitivity: Min. bulk solid density: 4.4
lb/ft3 (70 g/l); Max. particle size: 0.4˝
(10 mm).
Wetted Materials: 316 L SS.
Temperature Limits:
Ambient: -40 to 140°F (-40 to 60°C);
Process: -40 to 266°F (-40 to 130°C).
Pressure Limit: 600 psi (40 bar).
Power Requirement: 20 to 250 VAC,
50/60 Hz.
Power Consumption: 10 VA.
Enclosure: Aluminum, painted.
Enclosure Rating: IP65.
Switch Type: SPDT.
Electrical Rating: 5 A @ 250 VAC.
Electric Connections: Screw
terminals.
Conduit Connection: 1/2˝ female NPT
x 2.
Process Connections: 1˝ male NPT.
Indication Lights: Internal: Green and
red LED’s.
Sensing Delay: 0 to 6 s.
Weight: 2.4 lb (1.09 kg).
Model TFLS2-01, Compact Tuning Fork Level Switch
Mini Tuning Fork Level Switch
Compact, Cost Effective, DIN Connection
1˝ NPT
1-3/16
[30.00]
4-9/64
[105.00]
3-15/16
[100.00]
Ø1-1/2
[38.00]
Level Switches,
Tuning Fork
LEVEL
Scan here
to watch
product video
The Model CTF Mini Tuning Fork Level Switch is an ideal choice for level control for
powders. The CTF incorporates a piezoelectric crystal that vibrates the fork at its natural
frequency. When the fork comes in contact with a material, the vibration is dampened and
the switch changes state. As the material is removed from the fork, the switch changes
back to its normal state. The unit is not affected by vibration from conveying systems,
motors, or the movement of material. Its compact size and DIN connection allow for
application in places a larger tuning fork level switch may not be suitable, providing great
versatility.
The Model CTF is easy to use with no calibration required, and no mechanical moving parts
mean no routine maintenance. The CTF is not affected by the dielectric constant of the
sensed material, making it superior to a comparable capacitance level switch for
applications where the dielectric constant is low, more than one material is being used in
the single vessel, and when material moisture content can change. The level switch is also
great for applications when the bulk density is too low for a rotating paddle level switch,
making it the ideal choice for low density bulk solids and liquids. Comes standard with a
user friendly PNP/NPN configurable output.
APPLICATIONS
Lime, styrofoam, tobacco, dry cereals, sugar, animal feed, milk powder, flour,
insulation, cement, paper shavings, plastic granules, sawdust, carbon black, light
fibers, detergent powders, dyes, chalk, silica, sand, wood chips.
312
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
HEX1/5˝
SPECIFICATIONS
Service: Dry powder compatible with
wetted materials.
Sensitivity: Min. bulk solid density: 4.4
lb/ft3 (70 g/l).
Wetted Materials: 304 SS and 316L
SS.
Temperature Limits:
Ambient: -40 to 140°F (-40 to 60°C);
Process: -40 to 212°F (-40 to 100°C).
Pressure Limit: 600 psi (40 bar).
Power Requirement: 12 to 55 VDC.
Power Consumption: 10 mA @ 12 to
24 VDC; 0.5 W (max.).
Enclosure: Aluminum, painted.
Enclosure Rating: IP65.
Switch Type: 3-wire PNP/NPN output.
Electrical Rating: 350 mA (max) @ 12
to 55 VDC.
Conduit Connection: Valve plug DIN
43650.
Process Connections: 1˝ male NPT.
Indication Lights: External red LED.
Sensing Delay: Max. covered probe: 1
to 3 s.; Uncovered probe: 1 to 3 s.
Weight: 2.2 lb (1.0 kg).
Model CTF-01, Mini Tuning Fork Level Switch
313_Layout 1 7/9/14 12:02 PM Page 313
Model
VRLS
Vibrating Rod Level Switch
Economical, No Material Build Up, For Powder or Bulk Solids
4-29/64
[113.03]
4-9/32
[108.83]
51/64
[20.19]
1˝ NPT
10-27/32˝
[275.35]
Scan here
to watch
product video
Ø3/4
[18.87]
The Model VRLS Vibrating Rod Level Switch is an economical choice in level
detection of powders and bulk solids. The VRLS utilizes a piezoelectric crystal that
vibrates the rod at a natural frequency. Once the rod comes in contact with the material,
the vibration will be dampened and the switch will change state. Once the rod is uncovered
by the material, the switch will revert to its normal state. Perfect for silo or hopper
applications, its probe design allows for self-cleaning, ensuring no build-up or bridging of
material and accurate detection. Sensitivity is adjustable for detection ranging from large
granular material to small powders with low bulk densities. The failsafe mode can be set
for failure on high level or failure on low level using a selector switch in the enclosure.
SPECIFICATIONS
Service: Dry powder or bulk materials compatible with wetted materials.
Sensitivity: Min. bulk density of 20 lb/ft3 (320 kg/m3).
Wetted Materials: 304 SS.
Temperature Limits:
Ambient: -40 to 140°F (-40 to 60°C);
Process: -40 to 176°F (-40 to 80°C).
Pressure Limit: 150 psi (10 bar).
Power Requirement: 20 to 250 VAC/VDC, 50/60 Hz.
Power Consumption: 15 VA.
Enclosure: Aluminum, painted.
Enclosure Rating: IP65.
Switch Type: SPDT.
Electrical Rating: 5 A @ 250 VAC.
Electrical Connections: Screw terminals.
Conduit Connection: 1/2˝ female NPT x 2.
Process Connection: 1˝ male NPT.
Indication Lights: Internal: green and red LED.
Sensing Delay: 0 to 6 s.
Weight: 4.4 lb (2.0 kg).
APPLICATIONS
Lime, styrofoam, tobacco, dry cereals, sugar, animal feed, milk powder, flour,
insulation, cement, paper shavings, plastic granules, sawdust, carbon black, light
fibers, detergent powders, dyes, chalk, silica, and wood chips.
Model VRLS-01, Vibrating Rod Level Switch
Model
DBLM
Mini-Bin Dry Bulk Level Monitor
Compact, 4-Vane Paddle
1-27/32
[46.83]
Ø2-9/16
[Ø65.09]
11/32 [8.7] DIA. HOLE
6-PLACES
6-25/32
[172.2]
1-37/64 [40.08]
1-7/32 [30.94]
8 [203.2]
DIA.
3-5/32
[80.02]
Range F1 with
Half Coupling Side Mount
The Mini-Bin provides reliable level sensing for dry bulk solids where mounting
space is limited. This compact, side mount control reports high, intermediate, and low level
conditions, eliminating overflows, choking, clogs or empty vessels. Model DBLM Mini-Bin
operates by using a 1 rpm synchronous motor to rotate a four vane, plastic paddle. When
material surrounds paddle and impedes rotation, the motor is de-energized and triggers a
SPDT snap switch. Mount the Mini-Bin with optional 1-1/4" to 3/4" reducer to replace
standard size units.
Power Supply
110 VAC
220 VAC
F1, 8˝ x 1-1/4˝ NPT flexible carbon steel mounting flange
A-335, 1-1/4˝ to 3/4˝ reducer
SPECIFICATIONS
Service: Dry bulk solids.
Wetted Materials: Polycarbonate paddle, SS shaft, PTFE washer.
Temperature Limits: -4 to 140°F (-20 to 60°C).
Enclosure Rating: Polycarbonate, NEMA 1 (IP10).
Switch Type: SPDT snap switch.
Electrical Rating: 3A @ 250 VAC.
Power Requirements: 110 VAC, 50/60 Hz, 220 VAC optional, consult factory.
Power Consumption: 1.5 Watts.
Electrical Connections 18 AWG, 12˝ leads wrapped in conduit.
Process Connection: 3/4˝ male NPT, optional flange and 1-1/4˝ to 3/4˝ reducer.
Mounting Orientation: Side mount.
Weight: 0.77 Ib (350 g).
Agency Approvals: CE.
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
313
Level Switches
Vibrating Rod
Model
DBLM3040
DBLM3140
15/32
[11.9]
LEVEL
3/4 NPT
7 [177.8]
DIA.
BOLT
CIRCLE
314_Layout 1 7/9/14 12:03 PM Page 314
Series
PLS2
Paddle Level Switch
3 Sensitivity Settings, Top or Side Mounting
4-59/64
[125.00]
4-23/32
[120.00]
3-15/16
[100.00]
1-29/64
[37.00]
5-1/8
[130.00]
2X 3/4˝
NPT
3-15/16
[100.00]
PLS2-PL1
5-29/32
[150.00]
25/64
[10.00]
1-1/4˝
NPT
1-3/8
[35.00]
3-15/61
[100.00]
7-7/8
[200.06]
3-5/8
[92.00]
PLS2-PL2
Scan here
to watch
product video
The Series PLS2 is an electromechanical level switch designed for level monitoring of
bulk materials. The rotating measuring vane is driven by a brushless synchronous motor
at one revolution per minute. As product builds up, the paddle rotation is impeded and the
resulting motor torque activates the output switch and stops the motor. A spring
mechanism reactivates the motor and returns the switch to normal state when the material
no longer impedes the paddle rotation. A torque adjusting mechanism eliminates the need
for different sized paddles. The PLS2 is designed with the industry standard 1-1/4˝ male
NPT connection and unit can be side or top mounted.
FEATURES
• 3 sensitivity settings
• Top or side mountable
• Brushless synchronous motor: Assures long term reliability and efficiency
• Motor shuts off when paddle stalls
• Screw cover: For easy access with no worries about losing bolts or screws
APPLICATION
• Level monitoring of bulk materials
Model
PLS2-E-1-1
PLS2-E-1-2
PLS2-E-1-3
Description
Explosion-proof paddle level switch, 115 VAC power supply
Explosion-proof paddle level switch, 230 VAC power supply
Explosion-proof paddle level switch, 24 VDC power supply
ACCESSORIES
PLS2-PL1, Single Sided Spring Paddle
PLS2-PL2, Double Sided Spring Paddle
PLS2-EX1, 8.5˝ Shaft Extension
PLS2-EX2, 19.6˝ Shaft Extension
PLS2-EX3, 39.4˝ Shaft Extension
PLS2-EX4, 78.7˝ Shaft Extension
Level Switches,
Paddle
LEVEL
Models include single sided non-spring paddle.
314
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
SPECIFICATIONS
Service: Dry powder or bulk materials compatible with wetted materials.
Wetted Materials:
Paddle: 304 SS;
Exposed shaft: 303 SS;
Shaft seal: NBR;
Process connection: Aluminum.
Temperature Limits:
Process: -13 to 176°F (-25 to 80°C);
Ambient: -4 to 140°F (-20 to 60°C).
Pressure Limit: 11.6 psi (0.8 bar).
Power Requirement: Select by model number: 115 VAC, 230 VAC or 24 VDC.
Power Consumption: AC versions: 4 VA; DC version: 2.5 watt.
Enclosure: Aluminum, powder coated.
Enclosure Rating:
NEMA 4 (IP66);
Rated for Class II & III, Div. 1, Group E, F, G.
Switch Type: SPDT micro switch.
Electrical Rating: 5 A @ 250 VAC, 3 A @ 30 VDC.
Electric Connections: Screw terminals.
Conduit Connection: 3/4˝ female NPT.
Process Connection: 1-1/4˝ male NPT.
Mounting Orientation: Side or top mounting.
Sensitivity: Min. material density of 6 lb/ft3 (96 kg/m3).
Permitted Mechanical Loading:
Standard shaft: 67 lbf (300 N) max;
Optional extension: 22 lbf (100 N) max.
Weight: 2.6 lb (1.2 kg).
Agency Approvals: CE, FM.
315_Layout 1 7/9/14 3:59 PM Page 315
Series
PLS
Paddle Level Switch
Economical Rotary Paddle Level Control, Top or Side Mounting for Dry Bulk Materials
3/4˝ CONDUIT
CONNECTION
4-11/32
[110.31]
4-1/2
[113.69]
CLEARANCE FOR
COVER REMOVAL
Incorporated in the design of the PLS is a magnetic drive that is time proven by
decades of use in our Mark Series valve position indicator product line. A 1 rpm
synchronous motor rotates the paddle utilizing a magnetic drive. As product builds up the
paddle is impeded from moving and the resulting motor torque activates the output
switches and stops the motor. A spring mechanism reactivates the motor and returns the
switches to normal state when the product no longer impedes the paddle rotation.
Standard construction is weatherproof with explosion-proof optional, and the unit can be
side or top mounted. The PLS is designed with the industry standard 1-1/4˝ male NPT
connection and mounting flanges.
FEATURES
• Magnetic drive that isolates and completely seals the control head from the process
and environment preventing material or dust from entering the control head
• Motor shuts-off when paddle stalls increasing motor life, preventing motor burnout,
and decreasing power usage
• Slip clutch design enabled by the magnetic drive that prevents damage to motor
and drive mechanism from sudden or excessive loading on the paddle.
• Status indication light on weatherproof models
• Screw cover on the enclosure for easy access with no worries about losing bolts
or screws
• Modular design to allow field installation of any paddle, flanges, shaft extensions,
or shaft guards
PLS-W-S-1-2-CSH-0-0
Flanges
FLG-CSH
FLG-CSF
FLG-SSH
FLG-SSF
PDL-4. Minimum bulk
density of 70 lb/ft3 (1122
kg/m3). Fits through 1-1/4˝
coupling eliminating the
need for a mounting
flange.
Description
Weatherproof construction, SPDT switch,
120 VAC power supply. Order paddles and
flanges separately.
Weatherproof construction, SPDT switch, 120
VAC power supply, includes PDL-3 paddle.
Weatherproof construction, SPDT switch, 120
VAC power supply, includes PDL-1 paddle and
FLG-CSH flange.
SPECIFICATIONS
Service: Dry powder or bulk materials compatible with wetted materials.
Sensitivity: Min material density of 5 lb/ft3 (80 kg/m3), max of 200 lb/ft3 (3200
kg/m3).
Wetted Materials:
Paddles: 316 SS; Exposed shaft: 316 SS; Shaft seal: PTFE;
Mounting boss: Aluminum; Flexible coupling: 316 SS;
Mounting flanges: Carbon steel or 316 SS
Shaft extension and shaft guards: Galvanized steel or 316 SS.
Temperature Limits:
Standard construction: Process: -40 to 300°F (-40 to 148.9°C);
Ambient: -40 to 185°F (-40 to 85°C);
High temperature option: Process: -40 to 500°F (-40 to 260°C);
Ambient: -40 to 185°F (-40 to 85°C).
Pressure Limit: 30 psig (2.07 bar) max for .5 micron or larger material.
Power Requirement: Select by part number: 110 to 120 VAC, 230 VAC, 24 VAC,
48 VAC, 12 VDC, or 24 VDC.
Power Consumption: Weatherproof models: 5 watts; Explosion-proof models: 3
watts.
Enclosure: Aluminum, powder coated.
Enclosure Rating: Weatherproof (W, WH construction): NEMA 4X (IP66);
Explosion- proof (E, EH construction): NEMA 4X (IP66) and rated for Class I, Div. 1
& 2, Groups C & D, Div. 1 & 2, Groups E, F, & G.
Switch Type: SPDT or optional DPDT snap switch.
Electrical Rating: 15A @ 120/230 VAC, 5A @ 24 VDC.
Electric Connections: Screw terminals.
Conduit Connection: 3/4˝ female NPT.
Process Connection: 1-1/4˝ male NPT. Optional flange.
Weight: Control head only: 4 lb (1.81 kg).
Indication Light: Red LED that activates when switch is made or when switch is
not made with RL option (Not available on explosion-proof models).
Options: Time delay relay, high temperature construction, top mount, shaft
extensions, shaft shields, flexible couplings, other power voltages, reversed light.
Agency Approvals: cUL approved as an auxiliary device or as an auxiliary device
for hazardous locations.
Description
Carbon Steel with Half Coupling
Carbon Steel with Full Coupling
316 SS with Half Coupling
316 SS with Full Coupling
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
Level Switches,
Paddle
Paddles
PDL-1
PDL-2
PDL-3
PDL-4
PDL-3. Minimum bulk
density of 30 lb/ft3 (481
kg/m3). Fits through a 11/4˝ coupling eliminating
the need for a mounting
flange.
LEVEL
PLS-W-S-1-3-0-0-0
PDL-2. Minimum bulk
density of 30 lb/ft3 (481
kg/m3).
4-31/32
[126.19]
6-3/8
[162.05]
8-33/64
[216.26]
10-5/16
[261.92]
Side Mount
Scan here
to watch
product video
Control
Assemblies
PLS-W-S-1-0-0-0-0
PDL-1. Minimum bulk
density of 5 lb/ft3 (80
kg/m3).
315
316_Layout 1 7/9/14 12:05 PM Page 316
™
Explosion-Proof Ultra Mag Level Switches
For Powder & Bulk Solids
SUSPENSION HUB – 1˝ NPT
SEALED
JUNCTION BOX
DRIVING
MAGNET
DRIVEN
MAGNET
EPOXY SEAL
SEALED
SWITCH CAVITY
DIAPHRAGM
DIAMETER 5-7/8˝
7-1/2
3-3/8˝
Suspension Mounting
Flange Adapter Ring
CONDUIT ENTRANCE 1/2˝ NPT
(6) 5/16˝
DIA. HOLES ON
8-3/8˝ B.C.
7-1/4˝
DIAPHRAGM
DIAMETER 5-7/8˝
9-1/8˝
Flange Mounting
3/8˝
3-1/8˝
Scan here
to watch
product video
A unique Magnetic Linkage isolates the electrical compartment from controlled product,
reducing maintenance and improving sensitivity. The sealed switch compartment and
sealed leads yield the utmost in reliable operation. A wide selection of diaphragms and
switches are available with choices of flange or suspension mounting to fit your specific
application. The dry level Ultra-Mag™ Level Switch is extremely sensitive and very economical.
The magnetic linkage makes this simple explosion-proof diaphragm switch the most rugged
and reliable level control for a variety of products (see cut-away above).
Mounting Selection: A choice of either suspension or flange mounting is available to
match your application. Flange mounting is the best choice for control of low or
intermediate level in vessels containing granular product that does not “bridge”, “rathole”,
or otherwise build up on vessel walls. Choose suspension mounting for high level in vessels
and for better operation with “bridging” product.
Diaphragm Selection: A wide variety of diaphragms are available to match product bulk
density, flowability, abrasiveness and temperature requirements while providing maximum
sensitivity. The best choice for vessels subject to pressure or vacuum is “breathable” fabric
(P Series), requiring no venting. Non-porous elastomer (G Series) type diaphragms are
the best choice for more abrasive product and broader temperature range applications.
Venting is always required with the G series and if used in pressurized vessels, venting to
the tank atmosphere is required to allow pressure equalization. A slide rule “Diaphragm
Selector” is available from the factory to help you choose the diaphragm best suited to your
application.
Level Switches,
Diaphragm
LEVEL
Note: The mounting configuration is represented by the letter “S” for suspension or
“F” for flange which is the second digit in the part number.
SPECIFICATIONS Service: Compatible powder or bulk solids.
Wetted Materials:
Mounting Flange: See model chart. Aluminum or 304 SS;
Diaphragm: See model chart. Urethane, Buna-N, PTFE, silicone rubber,
polyester, fluoroelastomers, white Buna-N (food grade), or EPDM.
Temperature Limits: Depends on diaphragm material, see model chart.
Standard switch: -40 to 185°F (-40 to 85°C);
High temperature switch: -40 to 350°F (-40 to 176°C).
Pressure Limit: 60 psig (4.14 bar).
Enclosure Rating: General purpose or weatherproof and explosion-proof. See
model chart.
Switch Type: See model chart.
Electrical Rating: See model chart.
Electrical Connections: 18 gage solid core, 600 volt TEW 105°C, style 1015.
Epoxy sealed at conduit entrance. 12˝ (304.8 mm) long.
Conduit Connection: 1/2˝ female NPT.
Process Connection: For flanged models standard is 8-3/8˝ (212.725 mm)
diameter bolt hole circle.
Mounting Orientation: Flange mount or suspend depending on model.
Set Point Adjustment: Internal screw.
Weight: 7 lb (3.18 kg).
Options: Suspension kits and flange adapter rings.
Agency Approvals: CSA and UL.
Suspension and Flange Mounting Kits: See page 317 (Ultra Mag™)
Part Number: See page 317 (Ultra Mag™)
316
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
317_Layout 1 7/21/14 1:52 PM Page 317
™
Proximity Ultra Mag Level Switch
Diaphragm Selection Guide
Complete Model Chart
Suggested
Suggested
Product
Diaphragm* Product
Diaphragm*
Abrasive
3D Polypropylene Powder
7A
Aggregate
3D Polypropylene Resin
17
Alumina
3D Polystyrene Beads
3D
Ash, Dry
3D Pot Ash
3D
Baking Powder
7B Powdered Metal
3D
Baking Soda
7B Powdered Ore
3D
Barite
3D PVC Powder
7A
Bark, Ground
6G PVC Resin
17
Barley, Ground or Meal 17 Rice
17
Barley, Whole
4B Rye
3D
Beans, Edible
4B Salt
3D
Bentonite
3D Sand, Dry
3D
Bond, Foundry
17 Sand, Dry Silica
3D
Carbon Black
7A Sand, Foundry Prepared
5A
Cement, Klinker
8A Sand, Shake Out
3D
Cement, Portland
4B Sawdust, Dry
6G
Chips, Hogged Fuel
6G Sea Coal
3D
Coal
3D Sesame Seed
3D
Compost
5A Shale, Crushed
3D
Core Sand, Foundry
3D Silica, Flour
3D
Corn, Shelled
8A Sludge, Sewage Dried
1A
Diatomaceous Earth
7A Sludge, Sewage, Ground
1A
Drill Mud
3D Soda Ash
3D
Flour
7B Soybeans, Cracked
3D
Fly Ash
3D Soybean, Flake
7A
Glass Batch
3D Soybean, Flour
7A
Gravel
3D Soybean Meal
3D
Iron Ore, Crushed
3D Soybean, Whole
3D
Kaolin Clay
3D Sugar Beets, Whole
6H
Lime, Hydrated
5A Sugar Refined
7B
Lime, Stone
3D Sunflower Seed
7A
Oats
4B Taconite Pellets
3D
Peanuts in Shell
7A Talcum Powder
3D
Peanuts, Shelled
3D Walnut Shells, Crushed
3D
Perlite
7A Wheat
8A
Phosphate, Rock
3D Wheat, Wet
5A
Polyethylene Powder
7A Wood, Chips
6G
Polyethylene Resin
17 Wood, Dust
6G
Polypropylene Fluff
7A
*Diaphragm codes become 4th and 5th characters in model
number.
PREFIX - Certification
E X = Explosion-proof (UL & CSA) Class I, Div I & II, Groups C & D; Class II, Div I & II, Groups E, F, & G.
X = Explosion-proof (CSA) Class II, Div I & II, Groups F & G.
= General Purpose (No Code)
* GS - G series suspended controls require suspension vent fittings. (**) Non-UL/CSA listed
Note: The ˝EX˝ prefix must he added to the 6-digit model number for ˝explosion-proof standard˝.
General purpose units do not require the ˝EX˝ or other prefix.
Model
Tank OD Model
126-016
126-009 15˝
126-017
126-010 30˝
126-018
126-011 36˝
126-019
126-012 42˝
126-020
126-013 48˝
126-021
126-014 60˝
126-015 72˝
Note: OD = Outside Diameter
Tank OD
84˝
96˝
10´
12´
14´
24´
“P” and “G” Series Suspension Assembly Kits
Model
901-409
901-412
Description
˝P Series Suspension Assembly includes 1/2˝ pipe (56˝ Std length), 1˝ pipe (48˝
Std length), 1˝ pipe coupling, 1-1/2 NPT strain relief on 1˝ pipe. Galvanized mild
steel pipe, explosion proof, standard.
˝G˝ Series Suspension Assembly includes 1/2˝ pipe (56˝ Std length), watertight
strain relief and 1˝ coupling, upper 1˝ pipe (28˝ Std length), lower 1˝ pipe (20˝
Std length), strain relief with 1-1/2˝ NPT, 1˝x1˝x1˝ Tee, 1˝ Street Ell and 1˝ pipe4˝ long Stilling Pot. Galvanized steel pipe, explosion proof, standard.
Specials include aluminum or stainless steel assemblies. Flange port and cover assemblies are sold
separately. CONSULT FACTORY for details.
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
317
Level Switches,
Diaphragm
Suspension Assembly Kits: Pre-assembled kits are available
from the factory, or you can build your own kits using standard pipe
fittings shown in our Proximity Bill of Materials (Form No. 101).
Pipes and fittings are normally galvanized steel, but aluminum and
SS pipes and fittings are available. Units are secured to a steel cover
plate that rests on a rectangular steel flange welded into the top of
the vessel. Aluminum and stainless coverplates and flanges are also
available. Standard 48˝ L x 1˝ pipe provides working depth (WD) up
to 48˝. Longer pipe (to provide greater WD) is available. GS Series
switches have upper (L1 = 28˝ standard) and lower (L2 = 20˝
standard) 1˝ pipes, with a tee (for stilling pot) in between. A stilling
pot is required to equalize pressure and keep dirt from building up
behind the diaphragm. PS series require a 1/2˝ conduit in 1˝
suspension pipe for explosion-proof applications. The 1/2˝ conduit
(56˝ standard length) is a standard part of the GS series assembly.
6TH DIGIT - Switch Type
A = Standard, SPDT, 15A @ 125, 250 VAC
T = High temp, SPDT, 5A @ 125, 250 VAC; 24 VDC(**)
V = High vibration, SPDT, 15A @ 125, 250 VAC
G = Gold contacts, SPDT, 1A @ 125 VAC, 1/2 A @ 24 VDC
SUFFIX-SPECIAL CONTROLS
-A2 = Wood Chip Control (with ˝6G˝ diaphragm only)
-A3 = High sensitivity actuator (for very light product)
E X G S D 3 D A = EXAMPLE MODEL NUMBER*A
LEVEL
Suspension Mounting is normally
used for high level monitoring in vessels.
For product over 20 lb/ft3, the level switch
(diaphragm face) should be located about
1/3 of the distance from the vessel wall to
1/3
the point of entry of the product. For
1/2
3
product less than 20 lb/ft , the unit should
be located closer to the point of entry of
the product, about 1/2 the distance from
the vessel wall to the point of entry.
Pressure required to depress the diaphragm and trip the switch is
in the range of 5 to 15 oz in the horizontal direction (perpendicular
to the diaphragm). Suspension mounting provides the easiest
vertical adjustment capability, greatest sensitivity and best
maintenance conditions.
1ST DIGIT - Basic Magnetic Pressure Sensing Series
G = Elastomeric Diaphragm-Venting required*. (Diaphragms 1A - 8A)
P = Breathable Fabric Diaphragm-No venting required. (Diaphragms 16 & 17 only)
2ND DIGIT - Mounting (Top = Suspension/Side = Flanged)
S = Suspended (G series require suspension vent fittings)*
Subtract 10 lbs./cu. ft.-greater sensitivity.
F = Flanged, Aluminum standard
T = Flanged, 304 SS
3RD DIGIT - Housing Material
D = Aluminum
A = Aluminum, Anodized
E = Aluminum, Epoxy Coated
4TH & 5TH DIGITS - Diaphragm Material (Temperature) (Bulk Density)
3 D = Urethane, .031˝ thick, (10 to 150°F), (> 30 lb/ft3)
G
3 E = Urethane, orange, .062˝ thick, (10 to 150°F), (> 90 lb/ft3)
G
4 B = Buna-N, black, .020˝ thick, (-20 to 212°F), (20 to 90 lb/ft3)
G
5 A = PTFE/Glass on Sil Rubber, .024˝ thick, (-40 to 350°F), (> 35 lb/ft3)
G
6 D = Silicone Rubber, gray, .062˝ thick, (-40 to 350°F), (15 to 30 lb/ft3)
G
6 E = Silicone Rubber on Glass, red, .032˝ thick, (-40 to 350°F), (> 90 lb/ft3)
G
6 G = ˝6C˝ w/Urethane overlay, (-40 to 350°F), (wood chips diaphragm with ˝A2˝)
G
7 A = Silicone Rubber on Glass (White), .015˝ thick, (-40 to 350°F), (5 to 40 lb/ft3)
G
7 B = Buna-N (Food Applications-white), .060˝ thick, (-20 to 212°F), (30 to 90 lb/ft3)
G
8 A = EPDM, black, .036˝ thick, (-40 to 275°F), (40 to 90 lb/ft3)
G
1 6 = Polyester Filter Fabric, white, 150 micron permeability, (-30 to 275°F),
P
(30 to 90 lb/ft3)
1 7 = Polyester Nitex, white, 15 micron permeability (-30 to 275°F), (30 to 90 lb/ft3)
P
318_Layout 1 7/8/14 11:47 AM Page 318
Series
SBLT2
&
SBLTX
Submersible Level Transmitters
Perfect for Ground Water and Wells, Lightning Protected
6-45/64
[170.26]
1/2 NPT
SUBMERSIBLE
CABLE
SBLT2
Ø1
[Ø25.40]
BREATHER
TUBE
6-15/16
[176.21]
1/2 NPT
SUBMERSIBLE
CABLE
SBLTX
Ø1
[Ø25.40]
Scan here
to watch
product video
BREATHER TUBE
SBLT2 and SBLTX Submersible Level Transmitters are manufactured for years of
trouble free service in the harshest applications. Both measure the height of liquid above
the position in the tank referenced to atmospheric pressure. The transmitters consist of
a piezoresistive sensing element, encased in a 316 SS housing. Bullet nose design protects
the diaphragm from damage.
The SBLT2 incorporates lightning and surge protection utilizing dual arrestor technology,
grounded to case, eliminating both power supply surges and lightning ground strike
transients (surge protection is not guaranteed and is not covered by warranty). The SBLTX
is UL approved intrinsically safe for use in hazardous locations when used with proper
barrier.
Units come equipped with a 270-pound tensile strength shielded and vented cable.
Ventilation tube in the cable automatically compensates for changes in atmospheric
pressure above the tank. The vent is protected with a maintenance free filter eliminating
particulate or water droplets from entering the transducers.
Level Transmitters,
Submersible
LEVEL
FEATURES
• Excellent chemical compatibility
• Lightning and surge protection on SBLT2 models
• Maintenance free vent filter
• UL approved intrinsically safe on SBLTX models
• Slim design for tight applications
APPLICATIONS
Well monitoring; Ground water monitoring; Environmental remediation; Surface
water monitoring; Down hole; Water tanks.
Model
SBLT2-5-40-ETFE
SBLT2-10-40-ETFE
SBLT2-15-60-ETFE
SBLT2-20-60-ETFE
SBLT2-5-40
SBLT2-10-40
SBLT2-15-60
SBLT2-20-60
SBLT2-3.5M-5M
SBLT2-5M-10M
SBLT2-10M-18M
Range psi
(ft w.c.) [m w.c.]
5 (11.54) [3.52]
10 (23.09) [7.04]
15 (34.63) [10.56]
20 (46.18) [14.08]
5 (11.54) [3.52]
10 (23.09) [7.04]
15 (34.63) [10.56]
20 (46.18) [14.08]
4.97 (11.48) [3.5]
14.21 (32.81) [10]
25.58 (59.06) [18]
Cable Length
ft (m)
40 (12.2)
40 (12.2)
60 (18.3)
60 (18.3)
40 (12.2)
40 (12.2)
60 (18.3)
60 (18.3)
16.40 (5)
32.81 (10)
59.06 (18)
Cable Type
ETFE
ETFE
ETFE
ETFE
Polyurethane
Polyurethane
Polyurethane
Polyurethane
Polyurethane
Polyurethane
Polyurethane
OPTIONS
Intrinsically Safe Approval - Change model number from SBLT2 to SBLTX
Custom ranges or Cable Lengths- Contact the factory
318
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
SPECIFICATIONS
Service: Compatible liquids.
Wetted Materials: 316 SS, 316L SS,
epoxy; Cable: Polyurethane or ETFE;
Bullet nose: PVC.
Accuracy: ±0.25% of full-scale.
Temperature Limit: SBLT2: 0 to 150°F
(-18 to 66°C); SBLTX: 0 to 176°F (-18
to 80°C).
Compensated Temperature Range:
SBLT2: 0 to 140°F (-18 to 60°C);
SBLTX: 0 to 176°F (-18 to 80°C).
Thermal Effect: ±0.02% full-scale/°F.
Pressure Limit: 2X full-scale.
Power Requirement: SBLT2: 13 to 30
VDC; SBLTX: 10 to 28 VDC.
Output Signal: 4 to 20 mA DC, 2-wire.
Response Time: 50 ms.
Max. Loop Resistance: 900 Ω at 30
VDC.
Electrical Connections: Wire pigtail.
Mounting Orientation: Suspended in
tank below level being measured.
Weight: 2.2 lb (1.0 kg).
Electrical Protection: SBLT2:
Lightning and surge protection; SBLTX:
None.
Agency Approvals: SBLT2: None;
SBLTX: CE, cUL intrinsically safe for
Class I, Div. 1, Groups A, B, C, D;
Class II, Div. 1, Groups E, F, G; Class
III Div. 1. (According to control drawing
01-700797-00).
ACCESSORIES
MTL5041, intrinsically safe galvanic isolator
MTL7706, intrinsically safe zener barrier
A-297, Dessicant Filter for vent tube. Removes humidity for protection
of the sensor. Changes color to show saturation
A-625, 316 SS Cable Hanger use with NPT option for attaching chain
for easy pulling out of application
319_Layout 1 7/21/14 1:55 PM Page 319
Series
MBLT
Miniature Submersible Level Transmitter
Only 0.63˝ in Diameter, Perfect for Wells and Boreholes, Up to ±0.10% Accuracy
6-1/4
[158.30]
SUBMERSIBLE
CABLE
Ø5/8
[Ø15.87]
BREATHER
TUBE
Scan here
to watch
product video
The MBLT Miniature Submersible Level Transmitter is only 0.63˝ in diameter
making it ideal for level monitoring in well and borehole applications. Constructed for
years of trouble free service, the MBLT has a welded 316 SS body and 316 SS nose cap.
Body top is also 316 SS and tapered to prevent damage or snares when pulling the unit out
of the installation. Featured in the MBLT is a precision ±0.10% or 0.25% of full scale
accuracy output, better than BFSL or BSL rated outputs used by most competitors.
Lightning and surge protection (not guaranteed or covered by standard warranty) is
included standard to stand up in harsh applications. MBLT comes with a choice of polyether
polyurethane or ETFE cable materials and all are vented for barometric pressure
compensation. Vent is covered with a maintenance-free filter preventing particulate or
water droplets from entering the transmitter.
APPLICATIONS
Ballast tanks, ground water monitoring, surface water monitoring, dewatering, down
hole, remediation and other environmental monitoring applications.
Model ±0.25%*
MBLT-2SC-IVPP-5-40
MBLT-2SC-IVPF-15-40
MBLT-2SC-IVPM-5-12.2
MBLT-2SC-IVPM-60-66
MBLT-2SC-IVPM-100-106
MBLT-2SC-IVPM-200-206
MBLT-2SC-IVPM-10-30*
MBLT-2SC-IVPF-20-40
MBLT-2SC-IVPF-30-50
MBLT-2SC-IVPM-10-15.2
MBLT-2SC-IVPF-50-70
MBLT-2SC-IVPM-20-26
MBLT-2SC-IVPM-30-36
MBLT-2SC-IVPF-100-120
MBLT-2SC-IVPM-40-46
MBLT-2SC-IVPF-150-170
MBLT-2SC-IVPM-60-66
MBLT-2SC-IVPF-200-220
MBLT-2SC-IVPF-350-370
MBLT-2SC-IVPM-100-106
MBLT-2SC-IVPM-200-206
MBLT-2SC-IVPF-690-710
*4.3 to 4.9 psi (10 to 11.54 in w.c.) configured ranges ±0.30% FS accuracy
Cable Length
40 ft
40 ft
12.2 m
66 m
106 m
206 m
9.14 m
40 ft
50 ft
15.2 m
70 ft
26 m
36 m
120 ft
46 m
170 ft
66 m
220 ft
370 ft
106 m
206 m
710 ft
Cable Type
Polyether polyurethane
Polyether polyurethane
Polyether polyurethane
Polyether polyurethane
Polyether polyurethane
Polyether polyurethane
Polyether polyurethane
Polyether polyurethane
Polyether polyurethane
Polyether polyurethane
Polyether polyurethane
Polyether polyurethane
Polyether polyurethane
Polyether polyurethane
Polyether polyurethane
Polyether polyurethane
Polyether polyurethane
Polyether polyurethane
Polyether polyurethane
Polyether polyurethane
Polyether polyurethane
Polyether polyurethane
ACCESSORY
A-297, Dessicant Filter for vent tube. Removes humidity for
protection of the sensor. Changes color to show saturation
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
Level Transmitters,
Submersible
OPTIONS
For factory calibration certificate, add suffix -FC to model numbers.
Example: MBLT-2SB-IVPF-20-40-FC
Range psi
(´ w.c.) [m w.c.]
5 (11.54) [3.52]
2.82 (15) [4.57]
7.10 (16.40) [5]
14.21 (196.85) [60]
25.58 (328.08) [100]
25.58 (656.17) [200]
4.33 (10) [3.05]
8.66 (20) [6.10]
12.99 (30) [9.14]
14.21 (32.81) [10]
21.65 (50) [15.24]
28.42 (65.62) [20]
42.63 (98.43) [30]
43.31 (100) [30.48]
56.83 (131.23) [40]
64.96 (150) [45.72]
85.25 (196.85) [60]
86.62 (200) [60.96]
151.58 (350) [3.52]
142.09 (328.08) [100]
284.18 (656.17) [200]
298.83 (690) [210.31]
Pressure Limit: 2 x FS.
Power Requirements: 10 to 33 VDC.
Output Signal: 4 to 20 mA DC 2-wire.
Response Time: < 50 ms.
Max Loop Resistance: 1000 Ω @ 30
VDC.
Electrical Connections: Wire pigtail.
Mounting Connection: Suspended
below point being monitored.
Electrical Protection: Surge/lightning
protected per EN61000-4-5, Class 5.
Weight:
Body: 0.235 lb (0.107 kg);
Cable: 0.037 lb (0.009 kg) per foot.
Agency Approval: CE.
LEVEL
Model ±0.10%
MBLT-2SB-IVPF-20-40
MBLT-2SB-IVPF-30-50
MBLT-2SB-IVPM-10-15.2
MBLT-2SB-IVPF-50-70
MBLT-2SB-IVPM-20-26
MBLT-2SB-IVPM-30-36
MBLT-2SB-IVPF-100-120
MBLT-2SB-IVPM-40-46
MBLT-2SB-IVPF-150-170
MBLT-2SB-IVPM-60-66
MBLT-2SB-IVPF-200-220
MBLT-2SB-IVPF-350-370
MBLT-2SB-IVPM-100-106
MBLT-2SB-IVPM-200-206
MBLT-2SB-IVPF-690-710
SPECIFICATIONS
Service: Compatible liquids.
Wetted Materials:
Body and nose: 316 SS;
Cable: Polyether polyurethane or
ETFE;
Seals: Fluoroelastomer;
Label: Polyethylene polyamid.
Accuracy: ±0.25% FS (10´ w.c. range
is ±0.30% FS) or ±0.10% FS.
Temperature Limits: -4 to 176°F (-20
to 80°C).
Compensated Temperature Limits:
0.25%: (0 to 70°C); 0.10% (0 to 60°C).
Thermal Effect: 0.25%: ±0.45% FS
TEB; 0.10%: ±0.30% FS TEB.
319
320_Layout 1 7/8/14 11:46 AM Page 320
Series
PBLT2
&
PBLTX
Submersible Level Transmitters
Perfect for Sludge and Slurries, Lightning Protected
8-3/32
[205.58]
1/2 NPT
Ø1 [25.40]
SUBMERSIBLE
CABLE
PBLTX
ø3-7/16
[ø87.31]
ø1/4 [ø6.35] x THRU
ON A ø1-39/64 [ø40.88] B.C.
2-3/16
[55.56]
BREATHER TUBE
ø1/4 x THRU
[ø6.35 x THRU]
7-63/64
[202.80]
Ø1-1/2 1/2 NPT
[Ø38.10]
60˚
TYP
SUBMERSIBLE
CABLE
PBLT2
2-3/16
[55.56]
Scan here
to watch
product video
BREATHER TUBE
PBLT2 and PBLTX Submersible Level Transmitters are manufactured for years of
trouble free service in the harshest applications. Both measure the height of liquid above
the position in the tank referenced to atmospheric pressure. The transmitters consist of a
piezoresistive sensing element, encased in a 316 SS housing. Perfect for wastewater and
slurry applications with features to protect the unit from these demanding applications.
Large diameter 316 SS diaphragm seal is non-clogging and damage resistant to floating
solids.
The PBLT2 incorporates lightning and surge protection utilizing dual arrestor technology,
grounded to case, eliminating both power supply surges and lightning ground strike
transients (surge protection is not guaranteed and is not covered by warranty). The PBLTX
is UL approved intrinsically safe for use in hazardous locations when used with proper
barrier.
Units come equipped with a 270-pound tensile strength shielded and vented cable.
Ventilation tube in the cable automatically compensates for changes in atmospheric
pressure above the tank. The vent is protected with a maintenance free filter eliminating
particulate or water droplets from entering the transducers.
Level Transmitters,
Submersible
LEVEL
FEATURES
• Excellent chemical compatibility with 316 construction and ETFE cable
• Lightning and surge protection on PBLT2 models
• Maintenance free vent filter
• UL approved intrinsically safe on PBLTX models
• Large diameter, non-clogging, damage resistant, 316 SS diaphragm seal
APPLICATIONS
Wastewater: Sludge pits, clarifiers, digesters; Alum tanks; Chemical storage tanks;
Oil tanks; Lime slurry; Sumps; Reservoirs.
Model
PBLT2-5-40
PBLT2-10-40
PBLT2-15-60
PBLT2-20-60
PBLT2-5-40-PU
PBLT2-10-40-PU
PBLT2-15-60-PU
PBLT2-20-60-PU
PBLT2-3.5M-5M-PU
PBLT2-5M-10M-PU
PBLT2-10M-18M-PU
320
Range psi
(ft w.c.) [m w.c.]
5 (11.54) [3.52]
10 (23.09) [7.04]
15 (34.63) [10.56]
20 (46.18) [14.08]
5 (11.54) [3.52]
10 (23.09) [7.04]
15 ( 34.63) [10.56]
20 (46.18) [14.08]
4.97 (11.48) [3.5]
14.21 (32.81) [10]
25.58 (59.06) [18]
Cable Length
ft (m)
40 (12.2)
40 (12.2)
60 (18.3)
60 (18.3)
40 (12.2)
40 (12.2)
60 (18.3)
60 (18.3)
16.40 (5)
32.81 (10)
59.06 (18)
Cable Type
ETFE
ETFE
ETFE
ETFE
Polyurethane
Polyurethane
Polyurethane
Polyurethane
Polyurethane
Polyurethane
Polyurethane
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
SPECIFICATIONS
Service: Compatible liquids.
Wetted Materials: 316 SS, 316L SS,
epoxy, cable: ETFE or polyurethane.
Accuracy: ±0.25% full-scale (includes
linearity, hysteresis, and repeatability).
Temperature Limit: PBLT2: 0 to 200˚F
(-18 to 93°C); PBLTX: 0 to 176˚F (-18
to 80°C).
Compensated Temperature Range:
PBLT2: 0 to 180°F (-18 to 82°C);
PBLTX: 0 to 176°F (-18 to 80°C).
Thermal Effect: ±0.02% FS/°F.
Pressure Limit: 2X full-scale.
Power Requirement: PBLT2: 13 to 30
VDC, PBLTX: 10 to 28 VDC.
Output Signal: 4 to 20 mA DC, two
wire.
Response Time: 50 ms.
Loop Resistance: 900 Ω.
Electrical Connection: Wire pigtail.
Mounting Orientation: Suspended in
tank below level being measured.
Weight: 4.3 lb (2.0 kg).
Electrical Protection: PBLT2:
Lightning and surge protection, PBLTX:
none.
Agency Approvals: PBLT2: None,
PBLTX: CE, cUL intrinsically safe for
Class I, Div. 1, Groups A, B, C, D;
Class II, Div. 1, Groups E, F, G; Class
III, Div. 1. (According to control drawing
01-700797-00).
OPTIONS
Intrinsically Safe Approval - Change model number from PBLT2 to PBLTX
Custom ranges or Cable Lengths - Contact the factory
ACCESSORIES
MTL5041, intrinsically safe galvanic isolator
MTL7706, intrinsically safe zener barrier
A-297, Dessicant Filter for vent tube. Removes humidity for
protection of the sensor. Changes color to show saturation
A-625, 316 SS Cable Hanger use with NPT option for attaching
chain for easy pulling out of application
321_Layout 1 7/21/14 10:27 AM Page 321
Series
FBLT
Flush Tip Submersible Level Transmitter
Perfect for Sludge and Slurries, Lightning Protected, ±0.25% Accuracy
5-15/16
[150.83]
SUBMERSIBLE CABLE
Ø5/8
[Ø15.87]
Ø1-3/16
[Ø30.16]
5-15/16
[150.83]
BREATHER TUBE
1-7/8
[47.63]
1/2
[12.69]
15/16 HEX
1/2˝ NPT
Ø1-3/16
[Ø30.16]
SUBMERSIBLE
CABLE
Ø5/8
[Ø15.87]
FBLT
1-1/8
[29.33]
BREATHER TUBE
FBLT with NPT Option
NPT Option
Scan here to watch product video
The Series FBLT Submersible Level Transmitter is designed with a flush
diaphragm tip that will not clog in harsh applications such as sewage lift stations.
Narrow body design allows the FBLT to fit into stilling wells and narrow installations.
The FBLT features a robust FKM fluoroelastomer diaphragm that is PTFE coated
for a stick resistant surface that will hold up in aggressive fluids. The diaphragm
cavity is filled with a gel that will not leak out versus oil or grease that our competitors
use. Body is constructed of 316 SS and the cable is either polyurethane or ETFE
for more corrosive applications.
The unit measures the height of liquid above the position that it is mounted in a tank
or pit in reference to atmospheric pressure. Ventilation tube in the cable automatically
compensates for changes in atmospheric pressure above the fluid. The vent is
protected with a maintenance free filter, eliminating particulate or water droplets from
entering the transmitter. For extra protection against humidity, we offer the A-297
desiccant filter that can be attached to the vent tube.
The FBLT incorporates lighting and surge protection (not guaranteed or covered by
warrantee) to stand up in harsh applications. Optional NPT connection allows the
unit to be rigidly installed in a pipe/conduit, or to attach our A-625 hanging loop for
attaching a chain for pulling out of the installation.
APPLICATIONS
Sewage lift stations, industrial slurries, industrial sumps, landfill leachate, reservoirs,
sludge pits, oil tanks, etc.
Range psi
(´ w.c.) [m w.c.]
4.33 (10) [3.05]
4.33 (10) [3.05]
5 (11.54) [3.52]
4.33 (10) [3.05]
6.50 (15) [4.57]
8.66 (20) [6.10]
12.99 (30) [9.14]
5 (11.54) [3.52]
2.82 (15) [4.57]
8.66 (20) [6.10]
12.99 (30) [9.14]
10 (32.09) [7.04]
15 (34.63) [10.56]
10 (32.09) [7.04]
10 (32.09) [7.04]
15 (34.63) [10.56]
15.16 (35) [10.67]
20 (196.85) [60]
Cable
Length
20´
30´
40´
40´
40´
40´
50´
40´
40´
40´
50´
40´
60´
40´
60´
60´
60´
60´
Cable
Type
Polyurethane
Polyurethane
Polyurethane
Polyurethane
Polyurethane
Polyurethane
Polyurethane
ETFE
ETFE
ETFE
ETFE
ETFE
ETFE
Polyurethane
Polyurethane
Polyurethane
Polyurethane
Polyurethane
ACCESSORIES
A-297, Dessicant Filter for vent tube. Removes humidity for
protection of the sensor. Changes color to show saturation
LEVEL
Model
FBLT-2SC-IVPF-10-20*
FBLT-2SC-IVPF-10-30*
FBLT-2SC-IVPP-5-40
FBLT-2SC-IVPF-10-40*
FBLT-2SC-IVPF-15-40
FBLT-2SC-IVPF-20-40
FBLT-2SC-IVPF-30-50
FBLT-2SC-IVEP-5-40
FBLT-2SC-IVEF-15-40
FBLT-2SC-IVEF-20-40
FBLT-2SC-IVEF-30-50
FBLT-2SC-IVEP-10-40
FBLT-2SC-IVEP-15-60
FBLT-2SC-IVPP-10-40
FBLT-2SC-IVPP-10-60
FBLT-2SC-IVPP-15-60
FBLT-2SC-IVPF-35-60
FBLT-2SC-IVPP-20-60
SPECIFICATIONS
Service: Compatible liquids.
Wetted Materials:
Body: 316 SS;
Cable: Polyether polyurethane or ETFE;
Diaphragm: PTFE coated FKM fluoroelastomer;
Label: Polyethylene polyamid.
Accuracy: ±0.25% FS (10´ w.c. range is ±0.30% FS).
Temperature Limits: -4 to 176°F (-20 to 80°C).
Compensated Temperature Limits: 32 to 140°F (0 to 60°C).
Thermal Effect: ±0.0075%/°F (±0.0135%/°C).
Pressure Limit: 2x range.
Power Requirements: 10 to 33 VDC.
Output Signal: 4 to 20 mA DC 2-wire.
Response Time: < 50 ms.
Max Loop Resistance: 1000 Ω @ 30 VDC.
Electrical Connections: Wire pigtail.
Mounting Connection: Suspended below point being monitored.
Electrical Protection: Surge/lightning protected per EN61000-4-5, Class 5.
Weight:
Body: 0.3 lb (0.136 kg);
Cable: 0.037 lb (0.009 kg) per foot.
Agency Approval: CE.
A-625, 316 SS Cable Hanger use with NPT option for attaching chain
for easy pulling out of application
*4.3 to 4.9 psi (10 to 11.54 in w.c.) configured ranges ±0.30% FS accuracy
Level Transmitters,
Submersible
OPTIONS
Cables can be ordered shorter or longer in polyurethane or ETFE.
Other ranges are available and can be ordered in psi, ft w.c., or m w.c.
NPT connection. Add suffix -NPT, for a 1/2˝ NPT connection to connect conduit,
piping, or cable hanger. All 316 SS
For factory calibration certificate, add suffix -FC to model numbers.
Example: FBLT-2SC-IVPF-20-40-FC
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
321
322_Layout 1 7/8/14 11:45 AM Page 322
Series
CRF2
Capacitive Level Transmitter
Powder, Bulk or Liquids
2X 1/2 FEMALE
NPT CONDUIT
CONNECTION
3-19/32
[91.28]
9/16
[14.29]
2X 1/2 FEMALE NPT
CONDUIT CONNECTION
6
[152.4]
3-5/32
[80.2]
CONTINUOUS LEVEL TRANSMITTER
4-7/16
[112.7]
4-1/2
[114.30]
MOD CRF2
SERIAL:
A DIVISION OF
DWYER INSTRUMENTS, INC.
MICHIGAN CITY, IN 46360, U.S.A.
INDUSTRIAL CONTROL EQUIPMENT
MOUNTING
BRACKET
2-3/8
[60.3]
3/4 MALE
NPT PROCESS
CONNECTION
4-3/16
[106.36]
“L”
1-3/8
[34.9]
3/4 MALE NPT
PROCESS CONNECTION
“L”
2-3/4
[70.0]
3-1/4
[82.6]
2X 3/4 [19.05]
CLEARANCE FOR
COVER REMOVAL
Remote Mount Housing
The Series CRF2 is a level transmitter providing a two-wire 4 to 20 mA output to indicate
level of liquids, powders and bulk materials. State of the art sensing technology in the
CRF2, using impulse RF admittance measurement provides excellent accuracy and
stability. The CRF2 senses capacitance changes resulting from the height of the material
in the tank between the probe and the tank wall. In non-metallic tanks or tanks that do not
have the wall parallel to the probe a ground reference must be used.
The CRF2 comes with either a rigid or flexible probe depending on application installation
need and probe length required. Featured in the CRF2 is easy push button calibration of
zero and span. Custom order the CRF2 to any length probe that you need for your
application. FEP covered probe is ideal for use with corrosive media. This technology also
provides immunity to external RF sources like walkie-talkies and cell phones as well as
minimal interference with radio communication or other electronic systems.
The CRF2 is perfect for level indication in bins, hoppers, or small silos of powder and bulk
materials.
Example Models:
CRF2-WR01T-072
CRF2-WR01T-096
CRF2 W R 0 1T 048 M20 CRF2-WR01T-048-M20
CRF2
Capacitive Level Transmitter
W
Weatherproof
R
Remote Mount Weatherproof Housing
Probe Type
R
Rod
C
Cable
Ground
0
None Included
A
Attached ground rod (3˝ or 4˝ flange process connection types only)
U
Unattached ground rod
Process
1T
3/4˝ NPT male
Connection
2T
1˝ NPT male
3T
1-1/2˝ NPT male
1B
3/4˝ BSPT
2B
1˝ BSPT
3B
1-1/2˝ BSPT
1S
1˝ sanitary clamp
2S
1-1/2˝ sanitary clamp
3S
2˝ sanitary clamp
1F
2˝ 150# flange, 316 SS
2F
2˝ 150# flange, PVC
3F
3˝ 150# flange, 316 SS
4F
3˝ 150# flange, PVC
5F
4˝ 150# flange, 316 SS
6F
4˝ 150# flange, PVC
Probe Length
XXX
Insertion length in inches. Example 048 is 48˝ L.
Rod Type: min: 24˝, max: 144˝
Cable Type: min: 24˝, max: 360˝
M20 M20 conduit connection with cable gland
Options
LEVEL
Example
Series
Enclosure
Level Transmitters,
Capacitive
SPECIFICATIONS
Service: Liquids, powders, and bulk
materials compatible with wetted
materials.
Wetted Materials: Standard:
Rod/cable: FEP, Connection: 316 SS;
Ground option: Rod/cable and
connection: 316 SS; Cable spacers:
PVC; Flange option: Material of flange.
Capacitance Range: 0 to 2000 pF.
Sensitivity: 0.15 pF.
Minimum Span: 8 pF.
Accuracy: ±0.5 pF or ±0.25% of span,
whichever is greater.
Repeatability: ±0.25 pF or ±0.1% of
span, whichever is greater.
Temperature Limits: Ambient: -40 to
185°F (-40 to 85°C); Process: -40 to
250°F (-40 to 121°C).
322
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
Pressure Limit: 100 psi (6.9 bar).
Power Requirements: 12 to 35 VDC.
Output Signal: 4 to 20 mA or 20 to 4
mA, 2 wire.
Response Time: 0.5 seconds.
Electrical Connection: Screw
terminal.
Conduit Connection: 1/2˝ NPT
female.
Process Connection: Standard: 3/4˝
NPT male; Optional: See model chart.
Enclosure Rating: NEMA 4X (IP66)
weather-tight/corrosion resistant.
Spark/Static Protection: 106 Ω
dissipation resistance with spark gap.
Surge current to 100A max.
Calibration: Zero, span, 4 mA, 20 mA.
Mounting Orientation: Vertical.
Weight: 6 ft rod type: 3.6 lb (1.63 kg).
323_Layout 1 7/8/14 11:45 AM Page 323
Model
LDL2-030
Vented Water Level Data Logger
SS, Automatically Compensates for Atmospheric Pressure
1-1/4
[31.75]
7-1/32
[178.44]
8-53/61
[224.41]
1 [25.40]
Sensor End
6-53/64
[173.33]
CONNECTED TO
SENSOR END BY
30 FOOT CABLE
The Model LDL2-030 Vented Water Level Data Logger has a vented cable and end
cap to allow it to automatically compensate for atmospheric pressure fluctuations. The data
logger measures water level up to 30 ft (9.14 m) and has an internal temperature sensor
that accurately records temperatures between -40 to 176°F (-40 to 80°C). The innovative
design makes it ideal for use in wastewater treatment facilities as well as monitoring well
and ground water levels. The battery-powered data logger can store over 16,000
measurements per channel, and the software allows for user selectable sampling rates. The
easy to use DL700 software allows the LDL2-030 to be easily started and stopped from a
PC or delayed to start up to six months in advance.
Model LDL2-030, Vented Water Level Data Logger
ACCESSORIES
DL700, Software, Manual and USB Interface Cable
TL-2150, Replacement battery for Series LDL2-030
CONNECTED TO
RECEIVER END BY
30 FOOT CABLE
4-19/32
[116.84]
Receiver End
Computer Requirements: Windows®
95, Windows® 98, Windows® 2000,
Windows® ME, Windows NT®, and
Windows® XP operating systems, one
free USB port.
Power Requirements: 3.6 V TL2150
lithium metal battery, installed
functional, user replaceable.
Battery Life: 1 yr (approx).
Interface: USB port (interface cable
required).
Wetted Materials: 303 SS; Cable:
Polyurethane.
Weight: 3 lb (1.4 kg).
Agency Approvals: CE.
SPECIFICATIONS
Range: Temperature: -40 to 176°F (-40
to 80°C); Water level: 0´ to 30´ (0 to
9.14 m).
Memory Size: 16,383 readings per
channel.
Accuracy: ±0.9°F (±0.5°C), ±0.3%
FSR @ 77°F (25°C).
Resolution: Temperature: 0.2°F
(0.1°C); Water level: 0.02˝ (0.051 cm).
Sampling Method: Stop on memory
full.
Sampling Rate: Selectable from 2 s to
12 hrs.
Windows®, Windows NT®, and Windows Vista® are registered
trademarks of Microsoft Corporation.
Series
ULB
&
ULL
Ultrasonic Level Transmitter
Integrated LCD Display, Automatic Temperature Compensation, Non-Contact Level Sensing
4-7/32
[107.0]
1-15/32
[37.0]
1-3/16
[30.0]
7-5/8 35°
[194.0]
1/2˝ NPT
13/32
[10.0]
2˝ NPT
Scan here
to watch
product video
FEATURES
• Direct installation
• Integral LCD display
• High accuracy (0.25% of max. range)
• Automatic ambient temperature compensation
Description
Bulk Solids
Bulk Solids
Liquids
Liquids
Max. Range
11.5 ft (3.5 m)
28 ft (8.5 m)
16.4 ft (5 m)
49.2 ft (15 m)
SPECIFICATIONS
Service: ULB: Bulk solids; ULL:
Compatible liquids.
Wetted Materials: Sensor:
Polypropylene; Acoustic window:
ECTFE.
Ranges: ULB-11: .82 to 11.5 ft (0.25 to
3.5 m); ULB-12: 1.96 to 28 ft (0.6 to 8.5
m); ULL-1XXX: 0.82 to 16.4 ft (0.25 to
5 m); ULL-2XXX: 1.96 to 49.2 ft (0.6 to
15 m).
Accuracy: 0.25% of max. range (at
20°C).
Resolution: 0.04˝ (1 mm).
Blind Zone: ULB-11: 0.8´ (.25 m);
ULB-12: 1.96´ (0.6 m); ULL-1XXX: 0.8´
(0.25 m).
Beam Angle: 5° @ 3 db point.
Temperature Limits: -40 to 158°F (-40
to 70°C); ULL-2XXX: 1.96´ (0.6 m).
Temperature Compensation:
Automatic.
Pressure Limits: 13.5 to 30 psi (0.9 to
2 bar).
Power Requirement: 18 to 28 VDC.
Output Signal: 4 to 20 mA.
Loop Resistance: Max. 727 Ω @ 28
VDC.
Electrical Connections: Screw
terminal.
Conduit Connection: 1/2˝ NPT, cable
gland (optional).
Process Connection: 2˝ NPT, 2˝ BSP
(optional).
Enclosure: Plastic enclosure: ABS &
UV resistant body.
Enclosure Rating: NEMA 4 (IP65).
Mounting Orientation: Vertical.
Failsafe: 3 min delay before
transmission of an error signal.
Memory: Non-volatile.
Display: 4 digit LCD.
Units: ft, m (optional).
Programming: 4 button.
Weight: 3.1 lb (1.4 kg).
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
323
Level Data Loggers
Model
ULB-11
ULB-12
ULL-1KFN
ULL-2KFN
2-5/32
[55.0]
LEVEL
The Series ULB is a direct-install level transmitter designed for non-contact measurement
of solid levels. The ULB utilizes ultrasonic technology paired with automatic temperature
compensation to provide reliable and accurate measurements in virtually all conditions.
Sophisticated algorithms are used to overcome acoustic interferences and false echoes. An
integrated LCD screen and four push buttons allow for quick and easy programming on a
simple menu structure. Diagnostic capabilities and a failsafe output signal make the ULB
an essential choice in critical applications.
3-3/4
[95.0]
2-9/16 1 [25.1]
[65.0]
324_Layout 1 7/8/14 11:44 AM Page 324
Ultrasonic Level Transmitter
Series
ULT
Explosion-proof, Mapping Software
3 29/32
[99.21]
4 9/32
[108.74]
2X 1/2 NPT
ø3 21/64
[84.53]
8 1/16
[204.79]
Scan here
to watch
product video
Series ULT Ultrasonic Level Transmitter provides reliable, accurate, noncontact
measurement of liquid levels. Ultrasonic non-contact technology offers no moving parts to
wear, jam, corrode, or get coated like contact technologies. Mapping software makes
effective measuring surface only a 3˝ diameter column. No concerns with ladders, pipes,
or other tank intrusions in the remaining sound cone. Unit is FM approved explosion-proof
making it ideal for use in hazardous locations. The ULT features easy programming with
6 digit LCD display and simple menu structure. Output range is adjustable with choices of
inputting tank dimensions or just fill and empty the tank while calibrating and it
automatically scales to levels it senses. Window cover allows early viewing of display.
Failsafe output options and diagnostic capabilities makes the ULT a good choice for critical
applications.
Model
ULT-11
ULT-21
Range
24.6´ (7.5 m)
32.8´ (10 m)
TEMPERATURE/PRESSURE DERATING
LEVEL
OPERATING PRESSURE PSI
40
UNACCEPTABLE
RANGE
30
20
ACCEPTABLE
RANGE
10
0
-40
-20
0
20
40
60
80
Level Transmitters,
Ultrasonic
TEMPERATURE °C
324
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
SPECIFICATIONS
Service: Compatible fluids. Not for use with powder and bulk solids.
Wetted Materials:
Sensor: PVDF;
Process connection: 303 SS;
O-ring: fluoroelastomer.
Ranges: 24.6´ (7.5 m), 32.8´ (10 m).
Accuracy: ±0.2% of max range.
Resolution: 0.079˝ (2 mm).
Blind Zone: Under 8˝ (20 cm).
Beam Width: 3˝ (7.6 cm) diameter.
Temperature Limits:
Ambient: -40 to 140°F (-40 to 60°C);
Process: -4 to 140°F (-20 to 60°C).
Temperature Compensation: -40 to 140°F (-40 to 60°C).
Pressure Limits: 30 psi (2 bar) up to 25°C (77°C). Above 25°C (77°F), rating
decreases 1.667 psi per 1°C increase. See chart.
Power Requirement: 18 to 28 VDC (Two-wire).
Output Signal: 4 to 20 mA or 20 to 4 mA (Two-wire).
Max. Loop Resistance: 250 Ω at 24 VDC.
Electrical Connections: Screw terminal.
Conduit Connection: 1/2˝ NPT female (two) or optional M20.
Process Connection: 2˝ NPT male or optional BSPT.
Enclosure Rating: Weather-proof meets NEMA 4X (IP66), explosion-proof rated
Class I, Div. 1, Groups B, C, D; Class II/III, Div. 1, Groups E, F, G.
Mounting Orientation: Vertical.
Failsafe: On lost echo after 30 seconds, user selectable to 4, 20, 21, 22 mA or last
signal.
Memory: Non-volatile.
Display: 6 character LCD.
Units: In, cm, ft, m, percent.
Memory: Non-volatile.
Programming: 4 button.
Weight: 4.0 lb (1.8 kg).
Agency Approvals: CE, FM.
325_Layout 1 7/21/14 1:58 PM Page 325
Series
UTC
Ultrasonic Liquid Transmitter & Controller
No Moving Parts, 5 Independent SPDT Relays, Liquid Level & Flow In One
3-9/32
[83.34]
6-5/32
[156.37]
3-5/16
[84.14]
3-11/64
[80.57]
2-7/8
[73.03]
7-17/32
[191.29]
6-7/64
[155.18]
9-11/16
[246.06]
2-1/64
[51.20]
7-51/64
[198.04]
Series UTC Ultrasonic Liquid Transmitter Controller provides reliable, accurate,
non-contact measurement of liquid level and open channel flow even under extremely harsh
conditions. Overcoming vapors, agitators or light foam, with no moving parts to wear or
jam. It supports a full range of process monitoring and storage level measurement
applications, such as high process tanks and large storage vessels. The UTC has a 6-digit
LCD display and a simple menu structure with multiple indications, making programming
simple. Its dual part system allows for the control unit to be located up to 656 ft (200 m)
away from sensor (model UTS purchased separately), and installation is simple with
included mounting bracket. In addition, this series also supports the Modbus RTU*
communication protocol, and offers RS-232 and 4 to 20 mA communications. Featuring
five independent SPDT relays and embedded firmware for volume and flow totalization,
this series is perfect for liquid level and open channel flow applications.
*Controller only, Series UTS sensor must be purchased in conjuction.
Controller UTC-1XX-XXXX-X compatible with sensor UTS-1XX-XXXX-X only;
Controller UTC-2XX-XXXX-X compatible with sensor UTS-2XX-XXXX-X only.
*UTC-1XX-XXX-X modbus read only
Model
UTC-111-111-1
UTC-111-211-1
Description
18 to 30 VDC Power Requirement, RS-232
100 to 240 VAC Power Requirement, RS-232
Model
UTS
3-5/32
[80.17]
2-19/64
[58.34]
SPECIFICATIONS
Ranges: (Series UTS Sensor Dependent) 2 to 82 ft (0.6 to 25 m).
Accuracy: 0.25% of max. range.
Resolution: 0.04˝ (1 mm).
Temperature Limits: UTC-XXX-1XX-X: -40 to 140°F (-40 to 60°C); UTC-XXX2XX-X: -4 to 140°F (-20 to 60°C).
Temperature Compensation: Automatic.
Power Requirement: UTC-XXX-1XX-X: 18 to 30 VDC 6 W; UTC-XXX-2XX-X: 100
to 240 VAC 50/60 Hz.
Switch Type: 5 SPDT relays.
Electrical Rating: 1 A @ 300 VAC, 1 A @ 150 VDC.
Output Signal: 4 to 20 mA.
Max. Loop Resistance: 750 Ω @ 24 VDC.
Electrical Connections: Screw terminal.
Conduit Connection: 1/2˝ female NPT, M20 x 2.5 (optional).
Enclosure Material: ECTFE.
Enclosure Rating: NEMA 4X (IP65).
Mounting Orientation: Vertical.
Memory: Non-volatile.
Display: LCD (6 digit).
Units: m, in, ft, m3/hr, GPM interchangeable.
Programming: 4 button.
Weight: (3.5 lb) 1.6 kg.
Ultrasonic Liquid Transmitter Sensor
Compatible with Series UTC, 25 kHz Sensor
2˝ NPT OR BSP
1˝ NPT OR BSP
LEVEL
2-3/16
[55.56]
4-21/64
[109.93]
Model UTS Ultrasonic Level Transmitter Sensor is a series of sensors made to
accompany Dwyer Instrument, Inc.’s Series UTC Ultrasonic Level Controllers. This series
has two different transducer frequencies, and a variety of measuring lengths and materials.
Description
25 kHz Sensor, Polypropylene, Standard Range,
2 ˝ NPT Connection, 50 ft (15 m) Cable
Temperature Compensation:
Automatic.
Pressure Limits: Atmospheric.
Transducer Frequency: 25 kHz.
Process Connection: 2˝ male NPT, 2˝
male BSP (optional).
Electrical Connection: 16.4´ (5 m) 5
conductor 0.75 mm2 cable.
Enclosure Rating: NEMA 4 (IP65).
Weight: (3.5 lb) 1.6 kg.
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
325
Level Transmitters,
Ultrasonic
Model
UTS-121-1102-1
SPECIFICATIONS
Service: Compatible liquids.
Wetted Materials: Polypropylene.
Range: 2 to 82 ft (0.6 to 25 m).
Blind Zone: 2 ft (0.6 m).
Beam Width: 3˝ (7.6 cm) diameter.
Beam Angle: 5° @ 3 db point.
Temperature Limits: -40 to 176°F (-40
to 80°C).
326_Layout 1 7/8/14 11:43 AM Page 326
Model
ULTM
Ultrasonic Level Transmitter - Mobile
SMS Capability, Can Be Externally Battery Powered
2 X 1/2˝ NPT
CABLE GLANDS
4-1/8
[104.75]
Series ULTM
Ultrasonic Level Transmitter Mobile
Model: ULTM-H
Temperature rating: -2 to 70°C (-4 to 158°F)
Power Supply: 8-33 VDC
Serial No: X XX XX X
Made in: ISRAEL
DC: WW/YYYY
10-61/64
[278.27]
Enclosure Rating: IP68
5-13/32
[137.45]
1-1/2˝ NPT
2-59/64
[74.04]
Model ULTM is a level transmitter with embedded cellular communications. This product
is fit for any site where SMS is available and features flexibility for customized alerts and
reports. It features a cellular (GSM) link for transmission of measured data, supporting
SMS and GPRS, as well as a USB for quick set up and local monitoring. The Model ULTM
provides periodic reports on the hour, and SMS reports to assigned personnel on demand.
There are no on-going fees for this model’s control software due to complete data
ownership. It houses an embedded, as well as an optional external temperature sensor,
making it ideal for situations where rapid temperature variations may occur. The Model
ULTM is a cost-effective solution perfect for remote monitoring in applications such as fuel
theft detection and river flood alerts.
APPLICATIONS
Model ULTM is ideal for managing fuel tanks at remote sites for various uses such
as fuel theft and leakage detection, inaccurate refueling, and continuous inventory
with the use of the programmable switch tracking. Due to its low power option with
the use of external battery, it features a long battery life based operation. The Model
ULTM can be useful for wastewater monitoring, 24/7 monitoring of sewer junctions,
and identification of overflow or blockage. The Model ULTM requires no road digging
and is fit for harsh weather conditions, making installation simple in a variety of
locations.
Note:
• Does not include SIM card or any cellular package.
• Works with AT&T and T-Mobile SIM cards in the U.S. Please make sure it will work
will your cellular carrier before purchasing.
• Must be a mini-SIM card.
Model ULTM-00, Level Transmitter
Level Transmitters,
Ultrasonic
LEVEL
ACCESSORIES*
ULTM-EXT, External Thermistor, NTC 10KΩ 5%
ULTM-PTS, Programmable Timer Switch
*ULTM-00 only supports one accessory at a time. External battery not included.
326
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
SPECIFICATIONS
Service: Compatible solids and liquids.
Wetted Materials: PVDF.
Range:
Liquids: 26.25´ (8 m);
Solids: 19.69´ (6 m).
Accuracy: ±0.5 cm (±0.2˝) or 0.2% of max. range.
Repeatability: 0.2% of measured range.
Resolution: 0.04˝ (1 mm).
Blind Zone: 5.91˝ (15 cm).
Beam Angle: 5° @ 3 db point.
Temperature Limits: -4 to 158°F (-20 to 70°C).
Temperature Compensation: Automatic.
Power Requirements: 8 to 33 VDC.
Current Consumption:
Continuous: 10 mA @ 24 VDC;
SMS Transmission: 40 mA @ 24 VDC;
Switch Output: 160 mA @ 24 VDC.
Process Tracking Rate (max.): 0.55 ft/s (10 m/min).
Electrical Connections: Screw terminal.
Conduit Connections: 1/2˝ female NPT.
Process Connections: 1-1/2˝ male NPT, 1-1/2˝ BSP optional.
Enclosure Material: Plastic PC/ABS+UV.
Enclosure Rating: IP65/IP67, IP68 (96 hours at 5.91’ (1.8 m) water depth).
Mounting Orientation: Vertical.
Memory: Non-volatile.
Display: 64 x 128 graphic LCD.
Units: m, m/min, °F or °C (selectable).
Programming: 4-button.
Weight: 1.95 lb (884.51 g).
CELLULAR MODEM
Band: Quad band 850/900/1800/1900 mHz.
Output Power: Class 4 (33 dBm) for EGSM850/EGSM900; Class 1 (30 dBm) for
GSM180/GSM1900.
SMS: Point-to-point MO and MT.
GPRS: Multi-slot class 10.
Reports Display: Level, volume, temperature.
SMS Resolution: 0.04˝ (1 mm).
Report Type: Empty, full, theft alert, refilling alert and periodic report.
Accuracy:
0.5 to 2´ (0.15 to 0.6 m): ±0.6˝ (±1.5 mm);
2 to 16.5´ (0.6 to 5 m): ±0.3% of measured range;
16.5 to 26.25´ (5 to 8 m): ±0.2% of max. range.
327_Layout 1 7/9/14 12:09 PM Page 327
Model
ULSS
Ultrasonic Level Sensor
4.1´(1.25 m) Measuring Range, Non-Contact Transmitter,
SPST Programmable Relays
RoHS
4´
[1.2 m]
3-1/4
[82.55]
ULSS-10: 1˝ NPT
Scan here
to watch
product video
The Model ULSS Ultrasonic Level Sensor provides non-contact, continuous ultrasonic
level measurement of fluids for short range applications. Ultrasonic technology paired with
automatic temperature compensation provides accurate and reliable measurements in
almost all conditions. The Model ULSS has failsafe logic that is easily configured to custom
applications via free software removing the need for target calibration. Using the free
software, the Model ULSS can be programmed to transmit an output signal as well as set
the four relays for control applications. This rugged design comes with a NEMA 6P
submersible enclosure rating to ensure a long lasting unit.
FEATURES
• Selectable deadband
• Fail-safe logic for control applications
• Four programmable relays
• Narrow beam width and short dead band
• Automatic temperature compensation
APPLICATIONS
• Dirty, corrosive, or sticky fluids
• Bulk containers
• Sump and process tanks
• Small tanks
Model
ULSS-10*
Range
4.1 ft (1.25 m)
*USB adapter necessary for calibration. One adapter can program multiple units.
SPECIFICATIONS
Service: Compatible fluids.
Wetted Materials: Sensor: PVDF; O-ring: FKM.
Ranges: 4.1´ (1.25 m).
Accuracy: 0.125˝ (3 mm).
Resolution: 0.019˝ (0.5 mm).
Blind Zone: 2˝ (5 cm).
Beam Width: 2˝ (5 cm).
Temperature Limits:
Process: 20 to 140°F (-7 to 60°C);
Ambient: -31 to 140°F (-35 to 60°C).
Temperature Compensation: Automatic.
Pressure Limit: 30 psi (2 bar).
Power Requirement: 12 to 28 VDC.
Output Signal: 4 to 20 mA, 2-wire;
Invert: 4 to 20 mA or 20 to 4 mA;
Fail-safe: 4 mA, 20 mA, 21 mA, 22 mA, or hold last.
Loop Resistance: 400 Ω max.
Electrical Connections: 4´ (1.2 m) 9 conductor shielded cable.
Contact Type: 4 SPST relays.
Contact Rating: 1 A max @ 28 VDC max.
Deadband: Selectable (no hysteresis, 1/4˝, 1/2˝, 1˝, 1/2 cm, 1 cm, 2 cm, 5 cm or
not available).
Process Connection: 1˝ NPT, 1˝ BSPP (optional).
Enclosure Rating: NEMA 6P (IP68).
Enclosure Material: Polycarbonate; Gland: TPE.
Mounting Orientation: Vertical.
Memory: Non-volatile.
Failsafe:
Contact: Power loss: Holds Last contact;
Power on: Open, close, or last contact.
Programming: Free PC software download (USB adapter required).
Weight: 1 lb (0.45 kg).
Agency Approvals: CE, RoHS.
LEVEL
ACCESSORIES
ULS-ACC-USB, USB Adapter for Calibration
ULS-ACC-121, 1˝ x 1˝ NPT Reducer Bushing Fitting (Sch. 40), PVC
ULS-ACC-122, 1˝ x 1˝ NPT Reducer Bushing Fitting (Sch. 80), PVC
ULS-ACC-221, 2˝ Socket x 1” NPT Reducer Bushing Fitting (Sch. 40), PVC
ULS-ACC-222, 2˝ Socket x 1” NPT Reducer Bushing Fitting (Sch. 80), PVC
ULS-ACC-510, 1˝ NPT Polypropylene Side Mount Bracket
2
[50.85]
Level Transmitters,
Ultrasonic
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
327
328_Layout 1 7/9/14 12:10 PM Page 328
Model
ULSM
Ultrasonic Level Sensor
9.8´(3 m) Measuring Range, Non-Contact Transmitter,
4 SPST Programmable Relays
RoHS
4´
[1.2 m]
2-45/64
[68.66]
ULSM-10: 1˝ NPT
Scan here
to watch
product video
The Model ULSM Ultrasonic Level Sensor provides non-contact, continuous
ultrasonic level measurement of fluids for medium range applications. Ultrasonic
technology paired with automatic temperature compensation provides accurate and reliable
measurements in almost all conditions. The Model ULSM has failsafe logic that is easily
configured to custom applications via free software removing the need for target
calibration. Using the free software, the Model ULSM can be programmed to transmit an
output signal as well as set the four relays for control applications. This rugged design
comes with a NEMA 6P submersible enclosure rating to ensure a long lasting unit.
FEATURES
• Selectable deadband
• Fail-safe logic for control applications
• Four programmable relays
• Narrow beam width and short dead band
• Automatic temperature compensation
APPLICATIONS
• Dirty, corrosive, or sticky fluids
• Bulk containers
• Sump and process tanks
Model
ULSM-10*
Range
9.8 ft (3 m)
ACCESSORIES
ULS-ACC-USB, USB Adapter for Calibration
ULS-ACC-121, 1˝ x 1˝ NPT Reducer Bushing Fitting (Sch. 40), PVC
ULS-ACC-122, 1˝ x 1˝ NPT Reducer Bushing Fitting (Sch. 80), PVC
ULS-ACC-221, 2˝ Socket x 1” NPT Reducer Bushing Fitting (Sch. 40), PVC
ULS-ACC-222, 2˝ Socket x 1” NPT Reducer Bushing Fitting (Sch. 80), PVC
ULS-ACC-510, 1˝ NPT Polypropylene Side Mount Bracket
Level Transmitters,
Ultrasonic
LEVEL
*USB Adapter necessary for calibration. One adapter can program multiple units.
328
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
1-11/64
[29.90]
3-5/64
[78.18]
SPECIFICATIONS
Service: Compatible fluids.
Wetted Materials: Sensor: PVDF; O-ring: FKM.
Ranges: 9.8´ (3 m).
Accuracy: ±0.2% of range.
Resolution: 0.039˝ (1 mm).
Blind Zone: 4˝ (10 cm).
Beam Width: 2˝ (5 cm).
Temperature Limits:
Process: 20 to 140°F (-7 to 60°C);
Ambient: -31 to 140°F (-35 to 60°C).
Temperature Compensation: Automatic.
Pressure Limits: 30 psi (2 bar).
Power Requirement: 12 to 28 VDC.
Output Signal: 4 to 20 mA, 2-wire;
Invert: 4 to 20 mA or 20 to 4 mA;
Fail-safe: 4 mA, 20 mA, 21 mA, 22 mA, or hold last.
Loop Resistance: 400 Ω max.
Electrical Connections: 4´ (1.2 m) 9 conductor shielded cable.
Contact Type: 4 SPST relays.
Contact Rating: 1 A max @ 28 VDC max.
Deadband: Selectable (no hysteresis, 1/4˝, 1/2˝, 1˝, 1/2 cm, 1 cm, 2 cm, 5 cm or
not available).
Process Connection: 1˝ NPT, 1˝ BSPP (optional).
Enclosure Rating: NEMA 6P (IP68).
Enclosure Material: Polycarbonate; Gland: TPE.
Mounting Orientation: Vertical.
Memory: Non-volatile.
Failsafe:
Contact: Power loss: Hold last contact;
Power on: Open, close, or last contact.
Programming: Free PC software download (USB adapter required).
Weight: 1.5 lb (0.68 kg).
Agency Approvals: CE, RoHS.
329_Layout 1 7/8/14 11:42 AM Page 329
Model
ULSL
Ultrasonic Level Sensor
18´(5.5 m) Measuring Range, Non-Contact Transmitter,
4 SPST Programmable Relays
1-5/64
[27.30]
RoHS
4´
[1.2 m]
1-1/16
[27.10]
2-43/64
[68.05]
ULSL-10: 2˝ NPT
2-45/64
[68.67]
Scan here
to watch
product video
The Model ULSL Ultrasonic Level Sensor provides non-contact, continuous ultrasonic
level measurement of fluids for short range applications. Ultrasonic technology paired with
automatic temperature compensation provides accurate and reliable measurements in
almost all conditions. The Model ULSL has failsafe logic that is easily configured to custom
applications via free software removing the need for target calibration. Using the free
software, the Model ULSL can be programmed to transmit an output signal as well as set
the four relays for control applications. This rugged design comes with a NEMA 6P
submersible enclosure rating to ensure a long lasting unit.
FEATURES
• Selectable deadband
• Fail-safe logic for control applications
• Four programmable relays
• Narrow beam width and short dead band
• Automatic temperature compensation
APPLICATIONS
• Dirty, corrosive, or sticky fluids
• Bulk containers
• Sump and process tanks
Model
ULSL-10*
Range
18 ft (5.5 m)
*USB adapter necessary for calibration. One adapter can program multiple units.
SPECIFICATIONS
Service: Compatible fluids.
Wetted Materials: Sensor: PVDF; O-ring: FKM.
Ranges: 18´ (5.5 m).
Accuracy: ±0.2% of range.
Resolution: 0.079˝ (2 mm).
Blind Zone: 8˝ (20 cm).
Beam Width: 3˝ (7.62 cm).
Temperature Limits:
Process: 20 to 140°F (-7 to 60°C);
Ambient: -31 to 140°F (-35 to 60°C).
Temperature Compensation: Automatic.
Pressure Limits: 30 psi (2 bar).
Power Requirement: 12 to 28 VDC.
Output Signal: 4 to 20 mA, 2-wire.
Invert: 4 to 20 mA or 20 to 4 mA;
Fail-safe: 4 mA, 20 mA, 21 mA, 22 mA, or hold last.
Loop Resistance: 400 Ω max.
Electrical Connections: 4´ (1.2 m) 9 conductor shielded cable.
Contact Type: 4 SPST relays.
Contact Rating: 1 A max @ 28 VDC max.
Deadband: Selectable (no hysteresis, 1/4˝, 1/2˝, 1˝, 1/2 cm, 1 cm, 2 cm, 5 cm or
not available).
Process Connection: 2˝ NPT, 2˝ BSPP (optional).
Enclosure Rating: NEMA 6P (IP68).
Enclosure Material: Polycarbonate; Gland: TPE.
Mounting Orientation: Vertical.
Memory: Non-volatile.
Failsafe:
Contact: Power loss: Hold last contact;
Power on: Open, close, or last contact.
Programming: Free PC software download (USB adapter required).
Weight: 3 lb (1.36 kg).
Agency Approvals: CE, RoHS.
LEVEL
ACCESSORIES
ULS-ACC-USB, USB Adapter for Calibration, PVC
ULS-ACC-131, 3˝ x 3˝ NPT Reducer Bushing Fitting (Sch. 40), PVC
ULS-ACC-132, 3˝ x 3˝ NPT Reducer Bushing Fitting (Sch. 80), PVC
ULS-ACC-142, 4˝ x 4˝ NPT Reducer Bushing Fitting (Sch. 80), PVC
ULS-ACC-231, 3˝ Socket x 2” NPT Reducer Bushing Fitting (Sch. 40), PVC
ULS-ACC-232, 3˝ Socket x 2” NPT Reducer Bushing Fitting (Sch. 80), PVC
ULS-ACC-241, 4˝ Socket x 2” NPT Reducer Bushing Fitting (Sch. 40), PVC
ULS-ACC-242, 4˝ Socket x 2” NPT Reducer Bushing Fitting (Sch. 80), PVC
ULS-ACC-520, 2˝ NPT Polypropylene Side Mount Bracket
3-5/64
[78.18]
Level Transmitters,
Ultrasonic
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
329
330_Layout 1 7/9/14 12:17 PM Page 330
Series
CLT
Continuous Level Transmitter
Customize To Fit Application, 316 SS or Buna-N Floats
Float Dimensions
1-7/8˝
[47.6]
2-1/16˝
[52.4]
1-1/4˝
[31.8]
JUNCTION BOX
[CURRENT OUTPUT ONLY]
4-9/16˝
[115.9]
5/16˝
[7.9]
1-5/16˝
[33.3]
TYP.
1-13/16˝
[46.0]
TYP.
5/16˝
[8]
F2
F1
2˝ NPT
Mounting Dimensions
INCHES
OF
INDICATION
B
Type 1
1/2 NPT
1-1/4 SQ
[31.75]
2 NPT
1/2 NPT
1.000 SQ
[25.40]
1-1/4 NPT
Type 2
Type 3
Continuous Output Level Transmitters provide up to the minute tank level
monitoring. Customize level transmitters to meet application requirements. Transmitters
can be configured for 4 to 20 mA or proportional voltage output, stainless steel or BunaN floats, and lengths up to 72˝ (183 cm).
Models are built to your specifications
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
LEVEL
Ø7-1/2
[190.5]
1/2 NPT
1
[25.40]
Type 4, 5
SPECIFICATIONS
Service: Compatible liquids.
Resolution: 1/4˝.
Temperature Limits: Buna-N floats: 180°F (82°C) in water, -40 to 230°F
(-40 to 110°C) in oil; SS floats: -40 to 230°F (-40 to 110°C).
Pressure Limits: Buna-N floats: 150 psig (10 bar); SS floats: 300 psig
(21 bar).
Power Requirements: Proportional voltage output models: 10 to 30 VDC;
4-20 mA output models: 10 to 40 VDC.
Loop Resistance: 1.4 kΩ max.
Electrical Connections: Proportional voltage output: 24˝ (61 cm) free leads #22
AWG, TFE jacketed; 4-20 mA output: Junction box.
Enclosure Rating: 4-20 mA models, NEMA 4 (IP56) junction box.
Mounting Orientation: Vertical ±20°.
CLT V S 5 F3 20.25 02.00 25.75 CLT-VS5F3-20.25-02.00-25.75
Continuous Level Transmitter
CLT
Voltage, proportional signal of 0 to supply voltage
V
4 to 20 mA (Junction box provided)
C
Brass with Beryllium copper stops
B
Stem & Connection
316 SS with SS ARMCO PH-15-7MO stops
S
Material
1
1/2˝ NPT (Output Type V only)
Connection Type
1-1/4˝ NPT (Float F1 only)
2
3
2˝ NPT
3˝ 150# Flange, Carbon Steel (Connection material S only)
4
[Max. pres. 150 psi (10.3 bar)]
5
3˝ 150# Flange, 316 SS (Connection material S only)
[Max. pres. 150 psi (10.3 bar)]
Material
Min s.g.
Max Pres. psi (bar)
Float Factor in (mm)
Float Type
Buna N
0.55
150 (10.3)
2.0 (50.8)
F1
Buna N
0.55
150 (10.3)
2.5 (63.5)
F2
316 SS
0.75
300 (20.7)
3.5 (52.4)
F3
Length that the unit sends an output for level. Maximum is 68˝ (173 cm).
00.00
Indication Length
Distance from bottom of mounting connection to upper float stop.
00.00
Top Float Stop”C”
Minimum is 1/4˝ (6.4 mm)
Dimension Overall
00.00 To calculate overall length, add Indication Length, Top Float
Length “B”
Stop Dimension “C”, and Float Factor. Maximum length is 72˝ (1.82 m)
Example
Construction
Output
Level Transmitters,
Float
F3
1/2 NPT
LOWEST
LEVEL
330
5/16˝ [8]
6 HOLES Ø 3/4 [19.05]
EQUALLY SPACED
ON A 6.000 B.C.
[152.4]
C
HIGHEST
LEVEL
2-3/4˝
[69.8]
TYP.
331_Layout 1 7/21/14 2:01 PM Page 331
Series
DBOB
Continuous Level Measuring System
Simple Installation, Tangle Free Tape-Based System
7-9/32
[185.00]
5-45/64
[145.00]
8-21/32
[220.00]
5-45/64
[145.00]
10-1/32
[255.00]
2-3/4
[70.00]
3/4˝ NPT
CONDUIT
OPENING
1-1/2˝
NPT
3-15/16
[100.00]
Scan here
to watch
product video
1-37/64
[40.00]
The Series DBOB is a low maintenance, electromechanical device designed for the
continuous measurement of level or volumes in silos, tanks, or hoppers. The DBOB utilizes
an internal motor that drives a weight suspended by a firm stainless steel tape down to
the bulk material level. Upon reaching the material, the unit reverses and the weight is
drawn back into the upper stop position. The distance the weight descends is electronically
measured based on the internal rotations of the unwinding tape. The DBOB is userprogrammable to output either a height signal or a volumetric signal based on the vessel
geometry. The unit’s two programmable relays offer even more customization.
The 1-1/2˝ NPT process connection allows for simple installation on horizontal surfaces
and an optional aiming flange is available for inclines. The integrated tape cleaner keeps
the internal process protected from difficult material and the tough cast housing protects
the unit from its surroundings. With an easy to understand measurement principle and
inherent low maintenance qualities, the Series DBOB is perfect for your level measuring
needs.
FEATURES
• Measurement range up to 100 ft (30 m)
• Optional aiming flange for versatile mounting
• Accurate measurement
• Independent of bulk material properties
• Tangle free tape-based system
Model
DBOB-1-1
Description
Continuous level measuring system,
115 VAC power supply
ACCESSORIES
DBOB-AF, Aiming Flange
DBOB-PC, Weather Protection Cover
DBOB-W1, PVC Weight
DBOB-W2, PVC Weight with Pin
DBOB-W3, SS Weight
DBOB-W4, SS Weight with Pin
DBOB-W5, SS Spider Weight
1-1/2˝
NPT
7-3/32
[180.00]
8-35/64
[217.00]
DBOB-PC
10-13/64
[259.00]
9-29/64
[240.00]
ø3-3/16
[ø81.00]
DBOB-W1
6-19/64
[160.00]
Ø1-21/32
[ø42.00]
DBOB-W3
25/32
[20.00]
23-5/8
[600.00]
Level Transmitters,
Mechanical
DBOB-AF
2-61/64
[75.00]
9-13/32
[239.00]
11-17/64
[286.00]
7-3/32
[180.00]
4-23/32
[120.00]
SPECIFICATIONS
Service: Powder and bulk materials compatible with wetted materials.
Wetted Materials:
Mounting Thread: Aluminum;
Aiming flange: Aluminum and 304 SS;
Tape: 301 SS;
Sensor weight: PVC or 303 SS;
Fixing elements between tape and sensor weight: Aluminum and 303 SS.
Other Material: Housing: Powder-coated aluminum.
Temperature Limits:
Process temperature: -40 to 176°F (-40 to 80°C);
Ambient temperature: -4 to 140°F (-20 to 60°C)
(Relative humidity: 0 to 100%).
Pressure Limit: -3.0 to 3.0 psi (-0.2 to 0.2 bar).
Enclosure Rating: NEMA 4 (IP66).
Electrical Rating: 2 A @ 250 VAC.
Power Requirements: 115 VAC, 50/60 Hz.
Output Signal: 4 to 20 mA.
Accuracy of Output Requirement: 1% of measured length.
Power Consumption: AC model: 150 VA.
Electrical Connection: One 3/4˝ NPT and two 1/2˝ NPT conduit opening, screw
termination with removable terminal block.
Connection Terminals: AWG 26 to 14 (0.14 to 2.5 mm2).
Process Connection: 1-1/2˝ male NPT.
Mounting Orientation: Vertical.
Deviation of Vertical Mounting: Max. 2°.
Set Point Adjustment: Trips when weight reaches product.
Sensitivity: Min. powder density: 18 lb/ft3 (300 g/l).
Measuring Range: 100 ft (30 m).
Measuring Speed: Average 0.6 ft/sec (0.2 m/s).
Maximum Permitted Tractive Force: 180 lbf (800 N).
Maximum Altitude: 6562 ft (2000 m) for CE approval.
Display: LCD.
Indication Light: LED: Power on, relay, failure.
Memory: Non-volatile: >10 years data retention (no backup battery required).
Weight: 20 lb (9 kg).
Approvals: CE, FM Class. II, III Div. 1 Gr. E-G.
LEVEL
7-3/4
[197.00]
4-1/64
[102.00]
2 X 1/2˝ NPT
CONDUIT OPENING
DBOB-W5
Warning: Do not use the DBOB-PC Weather Protection Cover in hazardous locations.
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
331
332_Layout 1 7/8/14 11:40 AM Page 332
Series
MPC
Pump Controller
One or Two Pump Control with Built-In Alternation,
Over Temperature Protection and Seal Failure Monitoring
4-1/2
[114.3]
3-19/32
[91.3]
3-25/32
[95.9]
PANEL CUT-OUT: 3.620 X 3.620 IN, +0.032/-0.000
(92 X 92 MM, +0.8/-0.0).
ALLOW FOR 0.5 IN (13 MM) CLEARANCE
AT THE REAR OF THE INSTRUMENT.
LEVEL
The Mercoid® MPC Pump Controller provides versatile level control in a standard 1/4
DIN package. Designed for use with almost any style level transmitter the unit displays
the present level and main set point value. Incorporated in the MPC is programmable level
differential for on/off control of one or two pumps, valves, or other devices through two
SPDT relays. Also featured are two additional programmable alarm contacts with front
alarm light indication.
The MPC is flexible and incorporates a user-friendly programming menu. The front face
meets NEMA 4X (IP66) for outdoor panel mounting. So many features are combined into
the MPC that it eliminates many components in a pump control system.
FEATURES
• Selectable pump alternation when used with two pumps to minimize pump wear.
With alternation “on” a seal failure or over temperature condition will force the
non-failed pump to lead status and stop alternation.
• When used with a submersible pump including a moisture sensor th MPC has
alarm light indication of seal failure.
• When used with a pump including a thermostat the MPC has alarm light
indication of pump over temperature and removes the pump from service. The
pump can be brought back into service automatically or by manual reset when
the pump has cooled down.
• Alarms can be programmed for output indication of pump seal failure or over
temperature.
• Selectable time delay, for pump two, on power up to prevent both pumps from
starting at the same time. If power is lost, upon regaining power a time delay of
up to 60 seconds can be selected to prevent too large of a current draw.
• Integral 24 VDC power supply for level transmitter.
• Displays pump run time from a front panel button.
• Test system function that simulates the process input to ensure the pumps are
operating or to test programming.
• User selectable security lock-out of programming and/or set points.
• Process input retransmission as a current (4 to 20 mA) or voltage (2 to 10 VDC)
analog signal*.
*Standard model MPC is set for current retransmission. For voltage retransmission
add suffix “-RV”.
3-25/32
[95.9]
17/32
[13.5]
MEETS IP66 (UL TYPE 4X)
MAX. PANEL
THICKNESS 0.25 [6.35]
SPECIFICATIONS
Inputs: 4 (or 0) to 20 mA DC or 2 (or 0) to 10 VDC selectable.
Input Impedance: Current = 10 Ω; Voltage = 100 K Ω.
Output Ratings:
Control relays: SPDT, rated 10A @ 240 VAC res., 1/4 hp @ 120 VAC, 1/3 hp @
240 VAC;
Alarm relays: SPST, 3A @ 240 VAC res., 1/10 hp @ 120 VAC.
Control Type: On/off, reverse (pump out) or direct (pump in) acting.
Power Requirements: 100 to 240 VAC nominal, +10%-15%,
50 to 400 Hz, single phase; 132 to 240 VDC nominal, +10%-15%.
Power Consumption: 7.5 VA maximum.
Accuracy: ±0.25% of span, ±1 least significant digit.
Display: Two 4 digit, 7 segment 0.56˝ high LED’s.
Display Resolution: 1 count.
Memory Backup: Nonvolatile memory (no batteries required).
Serial Communications: Optional RS-232 or RS-485 with Modbus®
protocol.
Ambient Operating Temperature/RH: 14 to 131°F (-10 to 55°C)/0 to 90% up to
104°F (40°C) non-condensing, 10 to 50% at 131°F (55°C) non-condensing.
Weight: 16 oz. (454 g).
Front Panel Rating: Meets UL Type 4X (IP66).
Loop Power Supply (isolated): 24 VDC @ 50 mA, regulated.
Seal Failure (Moisture Sensor):
Power: 2.5 VDC;
Search Current: 3 micro amps;
Resolution: 10K to 500K Ω in 10K Ω steps.
Agency Approvals: CE, cUL, UL.
Series MPC, Pump Controller
OPTIONS
RS-232 Modbus®-RTU Serial Communications.
Add suffix – 232
RS-485 Modbus®-RTU Serial Communications.
Add suffix – 485
ACCESSORY
Weatherproof Enclosures, NEMA 4X (IP66).
Level/Pump
Controllers
Modbus® is a registered trademark of Schneider Automation, Inc.
Compatible Level Transmitters: See page 318 (Series SBLT2)
See page 320 (Series PBLT2)
Additional Digital Control Panel Meters: See page 346 (Series APM)
See page 347 (Series MPM)
See page 348 (Series PPM)
See page 351 (Series A-900 & A-901)
A-901
332
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
333_Layout 1 7/8/14 11:40 AM Page 333
Series
MPC Jr.
Pump Controller
One or Two Pump Control with Built-In Alternation
4-1/2
[114.3]
3-19/32
[91.3]
3-25/32
[95.9]
PANEL CUT-OUT: 3.620 X 3.620 IN, +0.032/-0.000
(92 X 92 MM, +0.8/-0.0).
ALLOW FOR 0.5 IN (13 MM) CLEARANCE
AT THE REAR OF THE INSTRUMENT.
The Mercoid® MPC Junior Pump Controller provides versatile level control in a
standard 1/4 DIN package. Designed for use with almost any style level transmitter the
unit displays the present level and main set point value. Incorporated in the MPC Jr. is
programmable level differential for on/off control of one or two pumps, valves, or other
devices through two SPDT relays. Also featured are two additional programmable alarm
contacts with front alarm light indication.
The MPC Jr. is flexible and incorporates a user-friendly programming menu. The front
face meets NEMA 4X (IP66) for outdoor panel mounting.
FEATURES
• Selectable pump alternation when used with two pumps to minimize pump wear.
• Integral 24 VDC power supply for transmitter.
• User selectable security lock-out of programming and/or set points.
• Optional process input retransmission as a current (4 to 20 mA) or voltage (2 to
10 VDC) analog signal.
• Analog output of pump “on” condition for activation of separate pump run time
meters.
3-25/32
[95.9]
17/32
[13.5]
MEETS IP66 (UL TYPE 4X)
MAX. PANEL
THICKNESS 0.25 [6.35]
SPECIFICATIONS
Inputs: 4 (or 0) to 20 mA DC or 2 (or 0) to 10 VDC selectable.
Input Impedance: Current = 10 Ω; Voltage = 5 K Ω.
Output Ratings:
Control relays: SPDT, rated 10A @ 240 VAC res.,1/4 hp @ 120 VAC, 1/3 hp @
240 VAC;
Alarm relays: SPST, 3A @ 240 VAC res., 1/10 hp @ 120 VAC;
Others: 15 VDC @ 20 mA for output one and output two.
Control Type: On/off, reverse (pump out) or direct (pump in) acting.
Power Requirements: 100 to 240 VAC nominal, +10%-15%,
50 to 400 Hz, single phase; 132 to 240 VDC nominal, +10%-15%.
Power Consumption: 7.5 VA maximum.
Accuracy: ±0.25% of span, ±1 least significant digit.
Display: Two 4-digit, 7 segment 0.56˝ high LED’s.
Display Resolution: 1 count.
Memory Backup: Nonvolatile memory (no batteries required).
Serial Communications: Optional RS-232 or RS-485 with Modbus® protocol.
Ambient Operating Temperature/RH: 14 to 131°F (-10 to 55°C)/0 to 90% up to
104°F (40°C) non-condensing, 10 to 50%
at 131°F (55°C) non-condensing.
Weight: 16 oz (454 g).
Front Panel Rating: Meets UL Type 4X (IP66).
Loop Power Supply (isolated): 24 VDC @ 50 mA, regulated.
Agency Approvals: CE, cUL, UL.
Series MPCJR, Pump Controller
LEVEL
ACCESSORY
Weatherproof Enclosures, NEMA 4X (IP66).
OPTIONS
Retransmission of input, 4 to 20 mA,
Add suffix – RC
Retransmission of input, 0 to 10 VDC,
Add suffix – RV
RS-232 Modbus®-RTU Serial Communications
Add suffix – 232
RS-485 Modbus®-RTU Serial Communications
Add suffix – 485
A-901
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
333
Level/Pump
Controllers
Modbus® is a registered trademark of Schneider Automation.
Compatible Level Transmitters: See page 318 (Series SBLT2)
See page 320 (Series PBLT2)
See page 351 (Series A-900 & A-901)
334_Layout 1 7/8/14 11:40 AM Page 334
Panel Meters and Pump Controllers
Open Channel Flow, Rate and Total, Multi-Pump Control
APM
MPM
The Series APM Analog Panel Meter is a 1/8 DIN digital panel meter perfect for
displaying flow rate and total simultaneously from several analog inputs such as a 4 to 20
mA or 0 to 10 V from any flow transmitter. When utilized with an ultrasonic level
transmitter, such as the Mercoid Series ULT, this series provides an economical way to
measure open channel flow. The dual line display can be configured to read flow rate, total,
grand total, as well as engineering units.
PPM
The Series PPM Pulse Panel Meter is a 1/8 DIN digital panel meter specifically designed
for a variety of pulse inputs. This series is particularly well-suited for flow applications with
its large six-digit, dual-line display that can display flow rate and total simultaneously with
up to 4 programmable relay options and 4 to 20 mA output. This series features latching,
non-latching, sampling, and fail-safe action in addition to its pump alternation function.
The Series MPM Multi Pump Meter is also a 1/8 DIN digital panel meter but for multipump alternation control. This series features, non-latching, sampling, and fail-safe action
in addition to its ability to alternate up to four pumps. This series is also capable of
linearizing nonlinear inputs with a variety of pre-programmed math functions. This is
helpful in applications where volume is monitored in odd shaped tanks as well as open
channel flow monitoring. It accepts 0 to 20 mA, 4 to 20 mA, 0 to 5 V, 1 to 5 V or 0 to ±10 V
standard.
Series
DLD
For more information on these products:See page 346 (APM)
See page 347 (MPM)
See page 348 (PPM)
Dual Channel Leak Detection Relay
Shaft Seal Leak Protection
19/64
[7.54]
2-3/8
[60.32]
LEVEL
3
[76.20]
Series DLD Dual Channel Leak Detection Relay is used to monitor the shaft seals
of two submersible pumps to detect a leak before pump failure. A leak is detected by
sensing the status of a float or conductivity switch installed in the seal cavity. When this
resistance drops below the set sensitivity, the output relay energizes and the corresponding
LED indicator illuminates. The DLD offers normally open relay contacts to energize an
alarm or de-energize the pump in the event of a leak. When the seal failure condition clears,
the relay automatically resets.
Sensitivity
10 K to 25 K Ω adjustable
4.7 K to 100 K Ω adjustable
Pump Leak Detectors
Model
DLD-ACY
DLD-ACZ
334
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
1-3/4
[44.45]
SPECIFICATIONS
Power Requirement: 120 VAC, 50/60 Hz.
Power Consumption: 2 VA (approximate).
Isolation Voltage: 2500 V.
Temperature Limits:
Operating: -4 to 131°F (-20 to 55°C);
Storage: -40 to 185°F (-40 to 85°C).
Switch Type: (2) N.O. SPST.
Switch Voltage 9 VDC.
Electrical Rating: 5 A @ 120 VAC resistive, 345 VA inductive.
Response Times:
Energize: 6 ms (approximate);
Release: 2.5 ms (approximate).
Indicators: Respective red LED illuminates when leak is detected.
Enclosure: Polycarbonate dust cover.
Mounting: 8-pin octal.
Weight: 8 oz (227 g).
Agency Approvals: cUR, UR.
335_Layout 1 7/8/14 11:39 AM Page 335
Bin Aerator Pad
Series
BAP
Inexpensive, Quiet Operation
1/8 FEMALE NPT
FOR TANK NIPPLE
11/16
[17.46]
7-1/2
[190.50]
RUBBER
GASKET
5/32
[3.81]
2X
WASHERS
3-3/4
[95.25]
BAP Aerator
Series BAP Bin Aerator Pad provides positive flow of dry, finely ground materials from
any bin using the proven principle of aeration. Low pressure air is introduced into the
product, restoring its natural ability to flow. In this way congestion, bridging and rat-holing
are overcome without resorting to brute force. Series BAP is non-clogging and provides
equal distribution and consumption of air. The aerator pads feature simple and quick
installation, are inexpensive, and adapt to any bin configuration. Aeration gives the best
results on materials with a 60 mesh size or smaller and with a 3% or less moisture content.
Model
BAP-C
BAP-SSC
BAP-F
BAP-SSF
BAP-K
Mounting Hardware
SPECIFICATIONS
Temperature Limit:
BAP-C and BAP-SSC: 180°F (82°C);
BAP-F and BAP-SSF: 600°F (316°C).
Supply Pressure: 3 to 5 psi (0.2 to 0.3 bar).
Air Consumption: See chart.
Air Connection: 1/8˝ NPT male.
Materials: See model chart.
Air Consumption Guide
Air Pressure, psi (bar) CFM (lpm)
1 (0.07)
4.2 (118.9)
2 (0.14)
5.7 (161.4)
3 (0.21)*
6.5 (184.1)
4 (0.28)
7.1 (201.0)
5 (0.34)
7.6 (215.2)
Description
Zinc Plated Steel with Gal. Steel Mesh & Cotton Diffuser
316SS with 316SS Mesh & Cotton Diffuser
Zinc Plated Steel with Gal. Steel Mesh & Fiberglass Diffuser
316SS with 316SS Mesh & Fiberglass Diffuser
Optional External Mounting Kit
*Recommended for most applications
Models
FD-1/
MFD-1
3/4˝ NUT
1/8 NPT X 2˝
TANK NIPPLE
BAP-K Optional External Mounting Kit
Fluidizer Disks
Self-Cleaning, Abrasion-Resistant, Easy to Install
Ø2-11/64
[55.0]
4-3/32 [104.0]
1-19/64
[33.0]
2-1/8
[54.0]
4-19/64
[109.0]
1/4˝ BSP
1/2˝ BSP
FD-1
MFD-1
COMPRESSION
FITTING
3/8˝ BSP
SPECIFICATIONS
Temperature Limits: -40 to 340°F (-40 to 170°C).
Air Connection:
FD-1: 3/8˝ female BSP and 1/2˝ male BSP;
MFD-1: 1/4˝ male BSP and 1/4˝ ID compression fitting.
Air Supply: 29 to 87 psi (2 to 6 bar).
Air Consumption: See chart.
Material: Consult factory.
Weight:
FD-1: 7.9 oz (0.23 kg);
MFD-1: 2.5 oz (0.07 kg).
Silo cutaway showing in use.
Model
FD-1
MFD-1
87 psi (6 bar)
LPM
CFM
120
4.23
Bin Vibrators/
Aerators
Air Consumption
29 psi (2 bar) 58 psi (4 bar)
LPM
CFM
LPM
CFM
70
2.47
90
3.17
LEVEL
The Model FD-1 & MFD-1 Fluidizer Disks combine aeration and vibration to solve the
most difficult bulk solid flow applications. Made from FDA approved materials, the special
design creates a vibration as the air flows between the disk boot and bin wall. This provides
a very effective flow aid for all types of dry products. The MFD is half the size of the FD,
making it capable of fitting into tight locations. Your pneumatic system pressure can range
from 29 to 87 psi.
Description
Fluidizer Disk
Micro Fluidizer Disk
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
335
336_Layout 1 7/8/14 11:38 AM Page 336
Series
BPV
Pneumatic Ball Vibrator
Small Size and Light Weight
IN
OUT
STEEL
RING
T
ØH
SOLENOID
VALVE
A
D
BALL
E
C
B
Model
BPV-1
BPV-2 & BPV-3
BPV-4 & BPV-5
BPV-6
A
2-1/32 [51.59]
2-41/64 [67.07]
3-9/32 [83.34]
4-1/16 [103.19]
B
3-27/64 [86.92]
4-29/64 [113.11]
5-3/64 [128.19]
6-5/16 [160.34]
Series BPV Pneumatic Ball Vibrators are the best choice for bridge-break in thin
walls and small tanks. This model can be used in vibrating separators, vibrating conveyors,
and against electroplating build-up. It can also be used on material compacted while packing
or sand compacted while molding. The aluminum body is equipped with a steel ring and
ball inside that is tightly closed by plastic side covers. Vibration is caused when the internal
ball, pushed by compressed air, runs in a rotary motion to produce centrifugal force.
Frequency (V.P.M.)
Pressure Input
Model 29 psi (2 bar) 58 psi (4 bar) 87 psi (6 bar)
BPV-1 22500
34000
28000
BPV-2 15000
22500
18500
BPV-3 13000
19500
17000
BPV-4 10500
16500
14500
BPV-5 9200
14000
12200
BPV-6 7800
12500
9700
V.P.M. = vibrations per minute
Series
PRV
Force lbf (N)
Pressure Input
29 psi (2 bar) 58 psi (4 bar)
106 (470)
56 (250)
124 (550)
72 (320)
180 (800)
101(450)
274 (1220)
162 (720)
353 (1570)
209 (930)
555 (2470)
339 (1510)
C
2-11/16 [68.26]
3-35/64 [90.09]
4-7/64 [104.38]
5-1/8 [130.18]
D
31/64 [12.30]
41/64 [16.27]
41/64 [16.27]
51/64 [20.24]
SPECIFICATIONS
Temperature Limits: 212ºF (100ºC).
Noise Level: 75 to 95 dBA.
Supply Pressure: 29 to 87 psi (2 to 6
bar).
Air Consumption: See model chart.
E
51/64 [20.24]
61/64 [24.21]
1-15/16 [33.34]
1-47/64 [44.05]
H
9/32 [7.14]
23/64 [9.13]
23/64 [9.13]
7/16 [11.11]
IN/OUT
1/4 BSPT
1/4 BSPT
1/4 BSPT
3/8 BSPT
Air Connections: 1/4˝ BSPT female
with 1/4˝ OD push to connect adapter on
BPV-1, BPV-2, BPV-3, BPV-4 and BPV5; 3/8˝ BSPT female with 3/8˝ OD push
to connect on BPV-6. Also includes
muffler for exhaust port.
Housing Material: Aluminum.
Air Consumption cfm (l/min)
Pressure Input
87 psi (6 bar) 29 psi (2 bar) 58 psi (4 bar) 87 psi (6 bar)
160 (710)
3.25 (92)
7.06 (200)
5.30 (150)
195 (870)
3.32 (94)
7.95 (225)
5.58 (158)
247 (1100)
4.31 (122)
9.89 (280)
7.06 (200)
387 (1720)
4.59 (130)
12.01 (340)
8.12 (230)
461 (2050)
5.65 (160)
15.01 (425)
10.24 (290)
722 (3210)
7.59 (215)
20.13 (570)
13.24 (375)
Weight
lb (kg)
.31 (0.14)
.57 (.26)
.66 (.30)
1.2 (.53)
1.4 (.63)
2.54 (1.15)
Pneumatic Roller Vibrator
Prevent Material Jams
IN
RING
T
ØH
SOLENOID
VALVE
A
ROLLER
D
C
E
B
LEVEL
Model
PRV-1
PRV-2
PRV-3
PRV-4
A
2-1/32 [51.59]
2-41/64 [67.07]
3-9/32 [83.34]
4-1/16 [103.19]
Bin Vibrators/
Aerators
Series PRV Pneumatic Roller Vibrators have a high vibration frequency feature that
can prevent material jams in pipe delivery. It can also be applied for bridge-break or
concrete injection operation conditions. The special aluminum body is equipped with a
roller and ring with multi-nozzles. It is tightly closed by plastic side covers. Vibration is
caused when the roller pushed by compressed air runs in a rotary motion to produce
centrifugal force.
Model
PRV-1
PRV-2
PRV-3
PRV-4
Frequency (V.P.M.)
Pressure Input
29 psi (2 bar) 58 psi (4 bar)
35000
25000
21000
19000
18500
15500
14000
11000
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
C
2-11/16 [68.26]
3-35/64 [90.09]
4-7/64 [104.38]
5-1/8 [130.18]
D
31/64 [12.30]
41/64 [16.27]
41/64 [16.27]
51/64 [20.24]
E
1-5/32 [29.37]
1-15/32 [37.31]
1-11/16 [42.86]
2-1/16 [52.39]
H
9/32 [7.14]
23/64 [9.13]
23/64 [9.13]
7/16 [11.11]
IN
1/8 BSPT
1/4 BSPT
1/4 BSPT
3/8 BSPT
SPECIFICATIONS
Temperature Limit: 212°F (100°C).
Noise Level Range: 75-100 dBA.
Supply Pressure: 29 to 87 psi (2 to 6 bar).
Air Consumption: See model chart.
Air Connection: 1/8˝ BSPT female with 1/4˝ OD push to connect adapter on PRV1; 1/4˝ BSPT female with 1/4˝ OD push to connect adapter on PRV-2 and PRV-3;
3/8˝ BSPT female with 3/8˝ OD push to connect adapter on PRV-4.
Force lbf (N)
Pressure Input
87 psi (6 bar) 29 psi (2 bar) 58 psi (4 bar) 87 psi (6 bar)
36000
656 (2920)
241 (1070)
948 (4200)
26000
1086 (4830) 1376 (6120)
614 (2730)
19000
1369 (6090) 1675 (7450)
674 (3000)
16000
1517 (6750) 2001 (8900)
843 (3750)
V.P.M. = vibrations per minute
336
B
3-27/64 [86.92]
4-29/64 [113.11]
5-3/64 [128.19]
6-5/16 [160.34]
Air Consumption cfm (l/min)
Pressure Input
29 psi (2 bar) 58 psi (4 bar) 87 psi (6 bar)
3.53 (100)
5.12 (145)
6.89 (195)
7.06 (200)
10.59 (300)
14.13 (400)
0.24 (290)
15.19 (430)
20.13 (570)
13.07 (370) 19.42 (550)
25.78 (730)
Weight
lb (kg)
.53 (0.24)
1.19 (0.54)
2.1 (0.95)
3.97 (1.8)
337_Layout 1 7/8/14 11:37 AM Page 337
Series
PTV
Pneumatic Turbine Vibrator
Low Noise, High Vibration Frequency
IN
OUT
T
SOLENOID
VALVE
HOLE
ØH
A
D
Cu
E
C
B
Model
PTV-1
PTV-2 & PTV-3
PTV-4 & PTV-5
PTV-6
A
2-1/32 [51.59]
2-41/64 [67.07]
3-9/32 [83.34]
4-1/16 [103.19]
B
C
3-27/64 [86.92] 2-11/16 [68.26]
4-29/64 [113.11] 3-35/64 [90.09]
5-3/64 [128.19] 4-7/64 [104.38]
6-5/16 [160.34] 5-1/8 [130.18]
D
31/64 [12.30]
41/64 [16.27]
41/64 [16.27]
51/64 [20.24]
E
1-5/16 [33.34]
1-21/32 [42.07]
2-7/32 [56.36]
2-7/8 [73.03]
H
9/32 [7.14]
23/64 [9.13]
23/64 [9.13]
7/16 [11.11]
IN/OUT
1/8 BSPT
1/4 BSPT
1/4 BSPT
3/8 BSPT
Air Connection: 1/8˝ BSPT female with
1/4˝ OD push to connect adapter on
PTV-1. 1/4˝ BSPT female with 1/4˝ OD
push to connect adapter on PTV-2, PTV3, PTV-4, and PTV-5. 3/8˝ BSPT female
with 3/8˝ OD push to connect adapter on
PTV-6. Also includes muffler for exhaust
port.
Housing Material: Aluminum.
Frequency (V.P.M.) Pressure Input
Force lbf (N) Pressure Input
Air Consumption cfm (l/min) Pressure Input
Weight
lb (kg)
Model 29 psi (2 bar) 58 psi (4 bar) 87 psi (6 bar) 29 psi (2 bar) 58 psi (4 bar) 87 psi (6 bar) 29 psi (2 bar) 58 psi (4 bar) 87 psi (6 bar)
.56 (0.26)
4.0 (112)
PTV-1 27500
35000
37500
189 (840)
312 (1390)
540 (2400)
1.62 (46)
2.83 (80)
1.25 (0.57)
10.2 (290)
PTV-2 26000
30000
33000
315 (1400)
549 (2440)
839 (3730)
4.24 (120)
7.06 (200)
1.28 (0.58)
10.2 (290)
PTV-3 17000
21500
24000
274 (1220)
470 (2090)
710 (3160)
4.24 (120)
7.06 (200)
2.4 (1.1)
16.1 (455)
PTV-4 17000
20000
23000
488 (2170)
908 (4040)
1241 (5520) 6.53 (185)
11.5 (325)
2.4 (1.1)
16.1 (455)
PTV-5 12000
15500
17000
477 (2120)
789 (3510)
1140 (5070) 6.53 (185)
11.5 (325)
4.8 (2.2)
PTV-6 13000
14000
16000
760 (3380)
1221 (5430) 1695 (7540) 11.65 (330)
18.71 (530) 26.3 (745)
V.P.M. = vibrations per minute
Series PTV Pneumatic Turbine Vibrators are the best choice of high vibration
frequency types for a low noise environment. It is usually installed on a vibrating separator,
conveyor, automatic arrangement machine, packing machine, or filling machine. The
vibration is produced by centrifugal force which arises from the imbalance of movement
when compressed air impacts the tangent of the turbine to make it move. The operation
noise is low because of ball bearing supports on the running turbine.
Series
APV
SPECIFICATIONS
Temperature Limit: : 212ºF (100ºC).
Noise Level: 60 to 75 dBA.
Supply Pressure: 29 to 87 psi (2 to 6
bar).
Air Consumption: See model chart.
Piston Vibrator
Air Cushioned or Piston Vibrators
IN
OUT
A
Model
APV-X1
APV-X2
APV-X3
A
5-7/16 [138.11]
6-35/64 [166.69]
8-13/64 [208.36]
B
3-5/32 [80.17]
3-15/16 [100.01]
5-33/64 [140.10]
C
2-3/8 [60.33]
2-61/64 [75.01]
4-9/64 [105.17]
D
31/64 [12.30]
41/64 [16.27]
41/64 [16.27]
H
23/64 [9.13]
7/16 [11.11]
19/32 [15.08]
IN/OUT
1/8 BSPT
1/4 BSPT
1/4 BSPT
D
ØH
ØC
ØB
Series APV-C Piston Vibrators are air cushioned to provide low noise. This makes it
suitable for quiet area applications. It is a good solution to prevent clogs on tank walls and
material delivery problems. It can also be applied on vibrating separators and conveyors.
LEVEL
Series APV-I Impact Version Piston Vibrators can help to get rid of dust or material
accumulated inside of pipes or tanks. It allows direct impact on the tank with low specific
gravity and high moisture materials inside. It also helps prevent material build-up, pipe
clogs, and rust.
SPECIFICATIONS
Temperature Limit: 212°F (100°C).
Noise Level Range: APV-C: 60-75 dBA; APV-I: 80-115 dBA.
Supply Pressure: 29 to 87 psi (2 to 6 bar).
Air Consumption: See model chart.
Air Connection: 1/8˝ BSPT female with 1/4˝ OD push to connect adapter on APVC1 and APV-I1; 1/4˝ BSPT female with 1/4˝ OD push to connect adapter on APVC2, APV-C3, APV-I2 and APV-I3. Also includes muffler for exhaust port.
Housing Material: Aluminum.
How They Operate
There are air-breathing tubes located in both ends of the cylinder. Compressed air
pushes the piston from one side to the other. Vibration power arises when the piston
moves back and forth in the body. In APV-C air cushion at both ends produced by
the to-and-fro motion will keep the piston from striking the body. Therefore, the piston
will not produce much noise. In APV-I, air cushion at the top end is produced by the
to-and-fro compression. This will keep the piston from striking onto the body top.
The piston will strike directly on the bottom side of the body to produce a strong
impact.
Force lbf (N) Pressure Input
29 psi (2 bar) 58 psi (4 bar) 87 psi (6 bar)
44 (195)
85 (380)
126 (560)
62 (275)
119 (531)
161 (715)
91 (404)
175 (780)
231 (1030)
1818 (8086) 3044 (13542) 3996 (17776)
3245 (14443) 4934 (21948) 6048 (26904)
3470 (15434) 7799 (34692) 8276 (36816)
Air Consumption
cfm (l/min)
8.12 (230)
8.79 (249)
9.50 (269)
8.8 (250)
9.5 (270)
10.6 (300)
Weight
lb (kg)
1.98 (0.9)
4.19 (1.9)
9.92 (4.5)
2.2 (1.0)
4.6 (2.1)
10.6 (4.8)
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
Bin Vibrators/
Aerators
Frequency (V.P.M.) Pressure Input
Model 29 psi (2 bar) 58 psi (4 bar) 87 psi (6 bar)
APV-C1 1765
2308
2857
APV-C2 1333
1677
1875
APV-C3 1000
1200
1340
APV-I1 1973
2885
3571
APV-I2 1744
2459
3000
APV-I3 1277
1875
1973
V.P.M. = vibrations per minute
337
338_Layout 1 7/8/14 11:36 AM Page 338
Series
IPV
Air Hammer
Single Impacting Type
IN
A
Model
IPV-1
IPV-2
IPV-3
IPV-3
A
5-7/16 [138.11]
6-35/64 [166.69]
8-13/64 [208.36]
10-19/32 [269.08]
B
3-5/32 [80.17]
3-15/16 [100.01]
5-33/64 [140.10]
6-25/32 [172.24]
C
2-3/8 [60.33]
2-61/64 [75.01]
4-9/64 [105.17]
5-33/64 [140.10]
D
31/64 [12.30]
41/64 [16.27]
41/64 [16.27]
61/64 [24.21]
H
23/64 [9.13]
7/16 [11.11]
19/32 [15.08]
3/4 [19.05]
Series IPV Air Hammer (single impact model) focuses on a limited target. Other
equipment of the target is minimally affected by it. It is often applied onto a pipe or clean
elbow in a tank filled with humidity or low specific gravity material.
FEATURES
• One impact wave caused by one shot
• High strength aluminum structure
• Impact force and interval timing can be set based on needs
• Magnetic hammer stores magnetic strength to increase the piston’s impact power
Model
IPV-1
IPV-2
IPV-3
IPV-4
Impulse
lbf•s (N•S)
.225 (1.0)
.630 (2.8)
1.66 (7.4)
2.81 (12.5)
Weight
lb (kg)
2.43 (1.1)
3.97 (1.8)
8.82 (4.0)
18.52 (8.4)
Air Consumption
in3 (l) per stroke
1.71 (0.028)
5.0 (0.082)
14.0 (0.228)
27.8 (0.455)
IN
1/4 NPT
1/4 NPT
1/4 NPT
3/8 NPT
OUT
1/4 NPT
1/4 NPT
1/4 NPT
3/8 NPT
OUT
D
ØH
ØC
ØB
SPECIFICATIONS
Temperature Limit: 212°F (100°C).
Noise Level Range: 60 to 75 dBA.
Supply Pressure: 43.5 to 87 psi (3 to 6 bar).
Air Consumption: See model chart.
Air Connection: 1/4˝ BSPT female with 1/4˝ OD push to connect adapter on IPV-1,
IPV-2 and IPV-3; 3/8˝ BSPT female with 3/8˝ OD push to connect adapter on IPV-4.
Also includes muffler for exhaust port.
How It Operates
The IPV series air hammer contains a powerful magnet inside the hammer. The
hammer and magnet are tightly closed before activation. As the inlet air pressure
gets higher than the force, this tightens the hammer and magnet. The hammer and
magnet will separate and cause more strength for impact power. The spring will bring
the hammer back to the initial position automatically after the impact. By doing this,
the air pressure will be released and the strength of the air pressure will be delivered
to the target impact container. It will help to smooth the flow and prevent accumulation
inside the container.
Electric Bin Vibrator
Series
EBV
Adjustable Vibration Intensity
LEVEL
B
Dimensions-Inches (mm)
Model A
B
EBV-1 5-1/8 (130) 5-23/64 (136)
EBV-2 5-1/8 (130) 5-23/64 (136)
EBV-3 5-1/8 (130) 6-17/64 (159)
EBV-4 6-7/64 (155) 6-23/32 (170)
C
8-5/16 (211)
8-5/16 (211)
9-3/32 (231)
10-23/64 (263)
D
4-11/64 (106)
4-11/64 (106)
4-11/64 (106)
4-7/16 (113)
E
2-43/64 (68)
2-43/64 (68)
2-43/64 (68)
5-1/8 (130)
Bin Vibrators/
Aerators
The Series EBV Electric Bin Vibrator incorporates adjustable force features without
creating irritating noise. The low amperage draw at 120V reduces power consumption and
makes the vibrators useable in any application. The EBV eliminates drawbacks associated
with non-adjustable constant force units. The conventional fix force units are sized with
narrow operating limits and may not move material from bins or pack material in
containers if the moisture content changes. The adjustable force feature increases
application flexibility; reducing equipment downtime and labor expense. The EBV is
capable of running continuously at 100% force output without overheating or mechanical
damage.
Model
EBV-1
EBV-2
EBV-3
EBV-4
338
Max Power
Kw
Hp
0.09 0.12
0.11 0.15
0.21 0.28
0.28 0.38
Centrifugal Force
Kg
Lb
71
156.5
95
209.4
189
416.7
323
712.1
Current
Max Amps
1.03
1.3
2.62
3.43
Weight
Lb
9.3
10.1
15.4
21.6
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
A
E
C
D
SPECIFICATIONS
Power Requirements: 120 VAC.
Power Consumption: See model
chart.
Temperature Limits: -4 to 104°F (-20
to 40°C).
Enclosure: Aluminum.
Enclosure Rating: NEMA 4X (IP66).
Noise Level: 20 dB.
Electrical Connection: Electrical
junction box.
Rotational Speed: 3600 RPM.
Weight: See model chart.
Approvals: CE.
FEATURES
• Continuous operation at 100% force output
• NEMA 4X (IP66)
• Robust aluminum body
• Silent operation (20 dB)
• Adjustable centrifugal force