VisionPRO 8000 Touchscreen Programmable Thermostat

Transcription

VisionPRO 8000 Touchscreen Programmable Thermostat
VisionPRO™ 8000 Touchscreen
Programmable Thermostat
PRODUCT DATA
FEATURES
• Large, clear display with backlight shows the current
and set temperature and time—even in the dark.
• Menu-driven programming make setup effortless.
• Beautiful ergonomic design is smart and sophisticated
to match your customers’ lifestyle.
• Touchscreen interaction
• Real-time clock keeps time during power failures and
automatically updates to daylight savings.
• "Saving Changes" notification lets you know when the
schedule changes have been saved.
• Change/check reminders let you know when to service
or replace filters or batteries.
• Various Hold options allow you to override the
program schedule, as desired.
APPLICATION
The VisionPRO 8000 Touchscreen Programmable Thermostat
is an effortless, 7-Day programmable thermostat that provides
universal system compatibility, precise comfort control and is
easy-to-program.
• Speedy same-schedule programming—no need to
copy multiple days.
• Armchair programming allows you to remove the
thermostat from the wall for programming.
• Programmable fan offers increased air quality when
combined with a Honeywell whole-house air cleaner.
The TH8110 Thermostats provide temperature control for gas,
oil, electric and heat pumps for 1 heat, 1 cool systems.
The TH8320 Thermostats provide temperature control for gas,
oil, electric and heat pumps for up to 3 heat, 2 cool systems
including dual fuel operation.
The TH8321 Thermostats provide temperature control for gas,
oil, electric and heat pumps for up to 3 heat, 2 cool systems
including dual fuel operation plus dehumidification control.
Contents
Application/Features..........................................................1
Specifications/Ordering Information ..................................2
Installation .........................................................................4
Wiring ................................................................................5
Power the Thermostat .......................................................11
Installer Setup ...................................................................15
Installer System Test .........................................................20
Operation...........................................................................21
Programming.....................................................................23
Troubleshooting.................................................................38
® U.S. Registered Trademark
© 2011 Honeywell International Inc.
All Rights Reserved
68-0280-01
VisionPROTM 8000 Touchscreen Programmable Thermostat
SPECIFICATIONS
Shipping Temperature:
TH8000 VisionPRO™ Thermostats: -30 °F to 150 °F
(-34.4°C to 65.6°C).
Thermostat Description:
Feature
Operating Relative Humidity (Non-condensing):
TH8000 VisionPRO Thermostats: 5% to 90%.
C7089U: 5% to 95%.
C7189U: 5% to 95%.
Description
Powering methods
• Battery only
• Common wire only
• Common wire with battery backup
System types (up to • Gas, oil or electric heat with air
conditioning
3 heat/2 cool or up
• Warm air, hot water, high-efficiency
to 1heat/1cool,
furnaces, heat pumps, steam and
depending on
gravity
model)
• Heat only—includes power to open
and power to close zone valves
(series 20) and normally-open zone
valves
• Heat only with fan
• Cool only
• 750 mV heating systems
Changeover
Manual or Auto changeover selectable
System setting
Heat-Off-Cool-Auto (Em. Heat for heat
pumps)
Fan setting
Auto-On-Circ
Electrical Ratings:
Terminal
Voltage (50/60 Hz)
Running Current
W Heating
20 - 30 Vac
.02 - 1.0A
W Heating
(Powerpile)
750 mV dc
100 mA dc
Y Cooling
20 - 30 Vac
.02 - 1.0A
G Fan
20 - 30 Vac
.02 - .60A
Humidity Setting Range (TH8321 models only):
Cooling: 40% to 80% RH.
Humidity Display Range (TH8321 models only):
0% to 99%.
Cycle Rates (at 50% Load):
Heating: Selectable 1 - 12 cycles per hour.
Cooling: Selectable 1 - 6 cycles per hour.
Finish:
TH8000 VisionPRO™ Thermostats: Premier White® color.
C7189U Wall Mount Remote Indoor Sensor: Premier White®
color.
Clock Accuracy: +/- 1 minute per month.
Batteries:
Three replaceable AAA alkaline batteries: Power thermostats
when 24 Vac common is not used. Non-replaceable
lithium battery with ten-year life under normal use to hold
calendar and time settings. Alkaline batteries keep calendar and time after lithium battery is no longer functional.
Resistance Characteristics of Remote Sensors:
C7089U Outdoor Sensor: Negative temperature coefficient
(NTC) means that resistance decreases as the
temperature increases. See Table 13 in the Operation
section for sensor resistance characteristics.
C7189U Remote Indoor Sensor: Negative temperature
coefficient (NTC), means that resistance decreases as the
temperature increases. See Table 14 in the Operation
section for sensor resistance characteristics.
Temperature Setting Range:
Heating: 40°F to 90°F(4.5°C to 32°C).
Cooling: 50°F to 99°F (10°C to 37°C).
Cool Indication:
TH8000 VisionPRO™ Touchscreen Thermostats show "Cool
On" on the screen when Cool is activated.
Operating Ambient Temperature:
TH8000 VisionPRO™ Thermostats: 0°F to 120°F
(-18°C to 49°C).
C7089U: -40°F to 120°F (-40°C to 49°C).
C7189U: 45°F to 88°F (7.2°C to 32°C).
Heat Indication:
TH8000 VisionPRO™ Touchscreen Thermostats show “Heat
On” on the screen when Heat is activated.
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1985 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Toronto, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
68-0280—01
2
VisionPROTM 8000 Touchscreen Programmable Thermostat
Auxiliary Heat Indication:
TH8000 VisionPRO™ Touchscreen Thermostats show “Aux.
Heat On” on the screen when Auxiliary Heat is activated.
WALLPLATE
3-3/8 (86)
Emergency Heat Indication:
TH8000 VisionPRO™ Touchscreen Thermostats show “Heat
On” on the screen when Emergency Heat is activated and
the System mode is in the Em. Heat position.
3-3/8 (86)
Calibration:
C7089U, C7189U and TH8000 VisionPRO™ Touchscreen
Thermostats are factory-calibrated and require no field
calibration.
Interstage Differential:
TH8000 VisionPRO™ Touchscreen Thermostats operate with
droopless control. Once the thermostat senses that
1st stage is running at 90% capacity, the thermostat
energizes 2nd stage.
THERMOSTAT
AND WALLPLATE
THERMOSTAT
6 (152)
1-3/8 (35)
Nomenclature:
4-9/16
(116)
Series
VisionPRO™
8000
Touchscreen
System
Stages
Application
Power and System
Changeover
11 - 1H/1C 0 - Standard U - Universal (Auto
32 - 3H/2C 1 - Humidity changeover and/or
Sensor
manual changeover) dual powered,
system flexibility,
schedule flexibility.
M22421
Fig. 1. TH8000 Touchscreen Thermostat
dimensions in in. (mm).
Mounting Means:
TH8000 VisionPRO™ Touchscreen Thermostat: Mounts
directly on the wall in the living space using mounting
screws and anchors provided. Fits a vertical or horizontal
2 x 4 in. junction box.
C7089U Outdoor Sensor: Mounts outside of living space with
mounting clip and screws provided.
C7189U Remote Indoor Sensor: Mounts directly on the wall
using mounting screws and anchors provided. Fits a
vertical 2 x 4 in. junction box.
Cover Plate:
32003796-001 Cover Plate is used to cover marks left on the
wall by the old thermostat.
Dimensions:
TH8000 Touchscreen Thermostat: see Fig. 1.
C7089U Outdoor Sensor Mounting Clip: see Fig. 2.
32003796-001 Cover Plate: see Fig. 3.
C7189U Remote Indoor Sensor: see Fig. 4.
1-1/2 (38)
M4488
Fig. 2. C7089U Outdoor Sensor Mounting Clip
dimensions in in. (mm).
7-7/8 (200)
3-5/16 (84)
5-1/2
(140)
3-5/16
(84)
M22139
Fig. 3. 32003796-001 Cover Plate dimensions in in. (mm).
3
68-0280—01
VisionPROTM 8000 Touchscreen Programmable Thermostat
4-5/8
(117)
4-5/8
(117)
1-1/8
(29)
2-3/4 (70)
FRONT VIEW
M4465
3-1/4
(83)
2-3/4 (70)
SIDE VIEW
FRONT VIEW (COVER OFF)
Fig. 4. C7189U Remote Indoor Sensor dimensions in in. (mm).
INSTALLATION
When Installing this Product...
1.
2.
3.
4.
Read these instructions carefully. Failure to follow the
instructions can damage the product or cause a hazardous condition.
Check the ratings given in the instructions to make sure
the product is suitable for your application.
Installer must be a trained, experienced service
technician.
After completing installation, use these instructions to
check out the product operation.
Do not install the thermostat where it can be affected by:
— Drafts or dead spots behind doors and in corners.
— Hot or cold air from ducts.
— Radiant heat from sun or appliances.
— Concealed pipes and chimneys.
— Unheated (uncooled) areas such as an outside wall behind
the thermostat.
Installing Wallplate
CAUTION
Electrical Hazard.
Can cause electrical shock or equipment damage.
Disconnect power before wiring.
Selecting Location
Install the thermostat about 5 ft. (1.5m) above the floor in an
area with good air circulation at average temperature. See
Fig. 5.
The thermostat can be mounted horizontally on the wall or on
a 4 in. x 2 in. (101.6 mm x 50.8 mm) wiring box.
1.
2.
3.
YES
NO
NO
5 FEET
[1.5 METERS]
NO
M19925
Fig. 5. Selecting thermostat location.
68-0280—01
4
Position and level the wallplate (for appearance only).
Use a pencil to mark the mounting holes.
Remove the wallplate from the wall and, if drywall, drill
two 3/16-in. holes in the wall, as marked. For firmer
material such as plaster, drill two 7/32-in. holes. Gently
tap anchors (provided) into the drilled holes until flush
with the wall.
VisionPROTM 8000 Touchscreen Programmable Thermostat
4.
5.
Position the wallplate over the holes, pulling wires
through the wiring opening. See Fig. 6.
Insert the mounting screws into the holes and tighten.
Table 1. Selecting Terminal Identifications for
System Type.
WALL
WIRES THROUGH WALL
AND WIRE SLOT
System Type
Wallplate
Terminal
Identifications
Wiring
Diagram
Reference
WALL ANCHORS (2)
MOUNTING
HOLES
MOUNTING
SCREWS (2)
Standard Heat/Cool
Conventional
9, 10
Heat Only
Conventional
11
Heat Only with Fan
Conventional
12
Heat Only (Series 20)
Power to open and
power to close zone
valves
Conventional
13
Normally Open Zone
Valves—Heat Only
Conventional
14
Cool Only
Conventional
15
Standard Multistage up
to 2 Heat/2 Cool
Conventional
16, 17
Heat Pump with No
Auxiliary Heat
Heat Pump
18, 19
Heat Pump with
Auxiliary Heat
Heat Pump
20, 21
M19916
Fig. 6. Mounting wallplate.
WIRING (FIG. 9 - 21)
All wiring must comply with local electrical codes and
ordinances.
1.
2.
3.
4.
5.
6.
Select set of terminal identifications (Table 1) that
corresponds with system type (conventional or heat
pump in Fig. 7).
Loosen the screws for the appropriate system type
selected; see Table 1. See Table 2 for terminal
designation descriptions. Insert wires in the terminal
block under the loosened screw. See Fig. 8.
Securely tighten each screw.
Push excess wire back into the hole.
Plug the hole with nonflammable insulation to prevent
drafts from affecting the thermostat.
See Fig. 9 through 21 for typical wiring hookups.
M19917
HEAT PUMP
CONVENTIONAL
Y2
Y2
L
E
Fig. 8. Inserting wires in terminal block.
RC
RC
R
R
W
O/B
AUX
W2
Y
Y
S1
S1
G
G
S2
S2
C
C
SCREW TERMINALS
IMPORTANT
Use 18 gauge thermostat wire.
M19951
Fig. 7. Selecting terminal identifications for
system type.
5
68-0280—01
VisionPROTM 8000 Touchscreen Programmable Thermostat
Table 2. Terminal Designation Descriptions.
Terminal
Designation
Rc (see Note
1)
R (see Note 1)
C (see Note 2)
CONVENTIONAL
Y2
Description
Power for cooling--connect to
secondary side of cooling system
transformer
W2
S1
S2
Power for heating--connect to
secondary side of heating system
transformer
RC
R
W
Y
G
C
2
R
C
OPTIONAL
24 VAC
COMMON
CONNECTION
3
FAN
RELAY
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
Common wire from secondary side of
cooling system transformer
1
COMPRESSOR
CONTACTOR
HEAT RELAY
W
Heat relay
Y
Compressor contactor
G
Fan relay
Y2
Second stage cooling
W2
Second stage heat relay
O/B (see Note
3)
Changeover valve for heat pump
systems
AUX
Auxiliary heat relay for heat pump
systems
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2
FACTORY INSTALLED JUMPER.
3
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE
ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE
FROM THE THERMOSTAT CABLE.
M19895
Fig. 9. Typical hookup of conventional single-stage heat
and cool system with single transformer
(1H/1C conventional).
CONVENTIONAL
E
Emergency heat relay for heat pump
systems
L (see note 4)
S1, S2
NOTES:
1.
2.
3.
4.
68-0280—01
Y2
Equipment monitor for heat pump
systems
W2
S1
S2
Optional outdoor or indoor remote
sensor
3
When used in a single-transformer system, leave
metal jumper wire in place between Rc and R. If
used on a two-transformer system, remove metal
jumper wire between Rc and R.
Common wire is optional when thermostat is used
with batteries.
If thermostat is configured for a heat pump system
in the Installer Setup, configure changeover valve
for cool (O-factory setting) or heat (B).
L terminal is an input (system monitor) when the
System mode is in the Heat, Off, Cool or Auto
position. L terminal is a 24 Vac output when
System mode is Emergency Heat. Must connect
the 24 Vac Common when using the L terminal.
See LED Indication section for more details.
6
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
RC
R
W
Y
G
C
2
1
R
C
OPTIONAL
24 VAC
COMMON
CONNECTION
FAN
RELAY
COMPRESSOR
CONTACTOR
HEAT RELAY
1
C
R
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2
REMOVE FACTORY INSTALLED JUMPER.
3
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE
ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE
FROM THE THERMOSTAT CABLE.
M19896
Fig. 10. Typical hookup of conventional single-stage heat
and cool system with two transformers
(1H/1C conventional).
VisionPROTM 8000 Touchscreen Programmable Thermostat
CONVENTIONAL
Y2
W2
S1
S2
RC
R
W
Y
G
C
CONVENTIONAL
Y2
2
1
R
W2
S1
S2
C
OPTIONAL
24 VAC
COMMON
CONNECTION
3
RC
R
W
Y
G
C
2
1
R
C
3
HEAT RELAY
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
W
TR
B
R
SERIES 20
MOTOR OR
TR
VALVE
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2
FACTORY INSTALLED JUMPER.
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
3
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE
ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE
FROM THE THERMOSTAT CABLE.
M19897
2
FACTORY INSTALLED JUMPER.
3
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE
ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE
FROM THE THERMOSTAT CABLE.
M19899
Fig. 11. Typical hookup of heat-only system
(1 H conventional).
Fig. 13. Typical hookup of heat only power to open and
power to close zone valve (Series 20) system.
CONVENTIONAL
CONVENTIONAL
Y2
W2
S1
S2
RC
R
W
Y
G
C
2
3
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
1
Y2
R
C
W2
S1
S2
OPTIONAL
24 VAC
COMMON
CONNECTION
RC
R
W
Y
G
C
2
1
R
C
OPTIONAL
24 VAC
COMMON
CONNECTION
FAN
RELAY
3
HEAT RELAY
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2
FACTORY INSTALLED JUMPER.
3
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE
ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE
FROM THE THERMOSTAT CABLE.
M19898
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
Fig. 12. Typical hookup of heat only system with fan
(1H conventional).
4
NORMALLY OPEN
ZONE VALVE
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2
FACTORY INSTALLED JUMPER.
3
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE
ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE
FROM THE THERMOSTAT CABLE.
4
CONFIGURE SYSTEM TYPE TO HEAT ONLY WITH NORMALLY OPEN
ZONE VALVES IN INSTALLER SETUP.
M22422
Fig. 14. Typical hookup of heat only system with normally
open zone valves.
7
68-0280—01
VisionPROTM 8000 Touchscreen Programmable Thermostat
CONVENTIONAL
CONVENTIONAL
Y2
W2
S1
S2
RC
R
W
Y
G
C
2
1
C
W2
S1
S2
OPTIONAL
24 VAC
COMMON
CONNECTION
2
3
COMPRESSOR
CONTACTOR
1
OPTIONAL
24 VAC
COMMON
CONNECTION
MUST COME
FROM THE
COOLING
TRANSFORMER.
2
FACTORY INSTALLED JUMPER.
3
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE
ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE
FROM THE THERMOSTAT CABLE.
M19900
COOL RELAY 2
HEAT RELAY 2
HEAT RELAY 1
W2
S1
S2
2
3
1
OPTIONAL
24 VAC
COMMON
CONNECTION
MUST COME
FROM THE
COOLING
TRANSFORMER.
R
C
FAN
RELAY
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
COOL RELAY 2
HEAT RELAY 2
HEAT RELAY 1
COOL RELAY 1
1
C
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2
FACTORY INSTALLED JUMPER.
3
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE
ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE
FROM THE THERMOSTAT CABLE.
M19902B
Fig. 17. Typical hookup of conventional multistage
two-stage heating and two-stage cooling in a
two-transformer system (2H/2C, 2H/1C or
1H/2C conventional).
CONVENTIONAL
RC
R
W
Y
G
C
C
R
Fig. 15. Typical hookup of cool only system
(1C conventional).
Y2
R
FAN
RELAY
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
COOL RELAY 1
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2
FACTORY INSTALLED JUMPER.
3
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE
ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE
FROM THE THERMOSTAT CABLE.
M22438B
Fig. 16. Typical hookup of conventional multistage
two-stage heating and two-stage cooling in a
single-transformer system
(2H/2C, 2H/1C or 1H/2C conventional).
68-0280—01
RC
R
W
Y
G
C
FAN
RELAY
3
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
1
Y2
R
8
VisionPROTM 8000 Touchscreen Programmable Thermostat
HEAT PUMP
1
R
Y2
L
E
3
Y
G
C
SI
OPTIONAL 24 VAC
COMMON CONNECTION
FAN RELAY
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
4
C
RC
R
2
CHANGEOVER
VALVE
COMPRESSOR
RELAY
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 FACTORY INSTALLED JUMPER.
3 "O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP.
4 OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE
FROM THE THERMOSTAT CABLE.
M19903B
Fig. 18. Typical hookup of single-stage heat pump with no auxiliary/backup heat (1H/1C heat pump).
HEAT PUMP
1
R
Y2
3
L
E
4
Y
G
C
SI
5
C
RC
R
2
OPTIONAL 24 VAC
COMMON CONNECTION
FAN RELAY
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
COMPRESSOR 2
CHANGEOVER
VALVE
COMPRESSOR 1
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 FACTORY INSTALLED JUMPER.
3 MUST CONNECT THE 24 VAC COMMON WHEN USING L. THE TERMINAL IS SHOWN AS EQUIPMENT MONITOR, CAN ALSO BE USED AS A 24 VAC
OUTPUT. SEE "HEAT PUMP LED" SECTION FOR MORE INFORMATION.
4 "O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP.
5 OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE FROM THE
THERMOSTAT CABLE.
M19904
Fig. 19. Typical hookup of multistage heat pump with no auxiliary/backup heat (2H/2C heat pump).
9
68-0280—01
VisionPROTM 8000 Touchscreen Programmable Thermostat
EQUIPMENT
MONITOR
HEAT PUMP
1
R
C
Y2
5
L
E
2
R
6
Y
G
C
SI
3
FAN RELAY
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
4
OPTIONAL 24 VAC
COMMON CONNECTION
CHANGEOVER
VALVE
COMPRESSOR
RELAY
EMERGENCY
HEAT RELAY
HEAT 2 RELAY
(AUXILIARY HEAT)
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 FACTORY INSTALLED JUMPER.
3 OUTDOOR SENSOR REQUIRED IN SYSTEM WITH FOSSIL FUEL BACKUP HEAT THAT IS NOT USING AN EXTERNAL FOSSIL FUEL KIT.
4 OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE
FROM THE THERMOSTAT CABLE.
5 MUST CONNECT THE 24 VAC COMMON WHEN USING L. THE TERMINAL IS SHOWN AS EQUIPMENT MONITOR, CAN ALSO BE USED AS
A 24 VAC OUTPUT. SEE "HEAT PUMP LED" SECTION FOR MORE INFORMATION.
6 "O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP.
M19905
Fig. 20. Typical hookup of single-stage heat pump with auxiliary/backup heat (2H/1C heat pump).
EQUIPMENT
MONITOR
HEAT PUMP
1
R
C
Y2
5
L
E
2
R
6
Y
G
C
SI
3
4
FAN RELAY
OUTDOOR/INDOOR
TEMPERATURE
SENSOR
HEAT 2 RELAY
(AUXILIARY HEAT)
OPTIONAL 24 VAC
COMMON CONNECTION
CHANGEOVER
VALVE
EMERGENCY
HEAT RELAY
COMPRESSOR 2
COMPRESSOR 1
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 FACTORY INSTALLED JUMPER.
3 OUTDOOR SENSOR REQUIRED IN SYSTEM WITH FOSSIL FUEL BACKUP HEAT THAT IS NOT USING AN EXTERNAL FOSSIL FUEL KIT.
4 OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE
FROM THE THERMOSTAT CABLE.
5 MUST CONNECT THE 24 VAC COMMON WHEN USING L. THE TERMINAL IS SHOWN AS EQUIPMENT MONITOR, CAN ALSO BE USED AS
A 24 VAC OUTPUT. SEE "HEAT PUMP LED" SECTION FOR MORE INFORMATION.
6 "O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP.
M19906
Fig. 21. Typical hookup of multistage heat pump with auxiliary/backup heat (3H/2C heat pump).
68-0280—01
10
VisionPROTM 8000 Touchscreen Programmable Thermostat
POWER THE THERMOSTAT
Wiring 24 Vac Common
Locate and remove the tab labeled, Remove, in the
lower left corner on the thermostat back. See
Fig. 23.
REMOVE
TAB
REMOVE DURING
INSTALLATION
• Single-Transformer System—Connect the common side of
the transformer to the C screw terminal of the thermostat
wallplate. Leave the metal jumper wire in place between
Rc and R.
• Two-Transformer System—Connect the common side of
the cooling transformer to the C screw terminal of the
thermostat wallplate. Remove the metal jumper wire
between Rc and R.
2.
REMOVE DURING
INSTALLATION
You can choose from three methods to power the thermostat:
• Batteries only (AAA alkaline).
• 24 Vac common wire only.
• 24 Vac common wire with battery backup (AAA alkaline).
Installing Batteries
1.
Install three AAA alkaline batteries on the back of the
thermostat as marked on the thermostat. See
Fig. 22.
M19920
Fig. 23. Remove tab labeled, Remove, on
thermostat back.
Mount Thermostat to Wallplate
1.
Align the terminal screw blocks with the pins on the
back of the thermostat. Push the thermostat straight
onto the wallplate until it snaps into place. See Fig 24.
WALLPLATE
BATTERIES (3)
M19918
PINS ON
BACK OF
THERMOSTAT
Fig. 22. Installing batteries.
TERMINAL
SCREW
BLOCK
M22213
Fig. 24. Mount thermostat to wallplate.
11
68-0280—01
VisionPROTM 8000 Touchscreen Programmable Thermostat
Locate and Mount C7089U Outdoor
Temperature Sensor (Optional)
Mount the sensor where (see Fig. 25):
• cannot tamper with settings.
• there is good air circulation.
• it can measure true outdoor ambient temperature.
• surface is flat.
• wire distance between C7089 and thermostat is less than
200 feet.
IMPORTANT
Erratic temperature readings from a sensor can
occur as a result of any of the wiring practices
described below. Avoid these practices to assure
correct operation. Use shielded cable to reduce
interference if rerouting sensor wiring is not possible.
— Be sure wires have a cable separate from the
thermostat cable.
— Do not route temperature sensor wiring with building
power wiring, next to control contactors or near light
dimming circuits, electric motors or welding
equipment.
— Avoid poor wiring connections.
— Avoid intermittent or missing building earth ground.
Do not mount the sensor:
• in direct sunlight.
• where hot or cold air blows on the sensor. Discharge line
from an outdoor compressor unit, vent or fan causes
inaccurate temperature readings.
• where snow, ice or debris can cover it.
CAUTION
Use the following steps to mount the sensor:
1. Remove the sensor from the mounting clip.
2. Mark the area on the location selected for mounting the
sensor mounting clip.
3. Mount the clip.
Electrical Shock Hazard.
Can cause electrical shock or equipment damage.
Disconnect power supply before connecting wiring.
Wiring must comply with applicable codes, ordinances and
regulations:
1.
2.
3.
Wire C7089 Outdoor Sensor to S1and S2 terminals on
the thermostat. If leadwire provided is not long enough
(60 in.), run a cable to a hole at C7089 location.
a. Using color-coded, 18-gauge thermostat wire is
recommended. For example of general wiring of
C7089, see Fig. 26.
b. Pigtail wiring can be used.
Mount C7089 in its mounting clip.
Plug wiring hole using nonhardening caulk or putty.
1
C7089
WIRING HOLE
THROUGH
2 STRUCTURE
M7514
Fig. 25. Typical locations for C7089U Outdoor Sensor.
Wire C7089U Outdoor Sensor
CAUTION
Electrical Interference (Noise) Hazard.
Can cause erratic system operation.
Keep wiring at least one foot away from large inductive
loads such as motors, line starters, lighting ballasts
and large power distribution panels.
Use shielded cable to reduce interference when
rerouting is not possible.
68-0280—01
12
1 USE APPROPRIATE MOUNTING MEANS FOR THE
TYPE OF STRUCTURE.
2 PLUG WIRING HOLE WITH NON-HARDENING CAULK
OR PUTTY.
M19970
Fig. 26. Wire C7089 Outdoor Sensor to the thermostat.
VisionPROTM 8000 Touchscreen Programmable Thermostat
Locate and Mount C7189U Remote Indoor
Temperature Sensor (Optional)
1.
2.
3.
4.
5.
Wire C7189 Indoor Sensor
Choose a location (see Fig. 27) for mounting the sensor
on an inside wall about 5 ft (1.5m) above the floor. A
vertically-mounted standard 2 x 4 in. (51 x 102 mm)
junction box can also be used.
Be sure wire distance between C7189 and thermostat is
less than 200 feet.
Make sure there is good air circulation at average
temperature at the chosen location. Avoid the following
locations because they can introduce errors in sensor
measurements. See Fig. 27.
a. Hot areas caused by:
(a) Concealed pipes or ducts.
(b) Drafts from fireplaces or other heat sources.
(c) Convection or radiant heat from the sun or
electrical equipment.
b. Cold areas caused by:
(a) Concealed pipes or ducts.
(b) Drafts from windows and doors.
(c) Unheated areas on the other side of the wall
location.
c. Dead air areas:
(a) Behind doors, furniture and curtains.
(b) In corners and alcoves.
Mark the area on the wall selected for mounting the
C7189 Sensor or junction box.
Run wire cable to a hole at the selected wall location.
Pull approximately three inches of wire through the
opening. Color-coded, 18-gauge thermostat wire is
recommended.
CAUTION
Electrical Interference (Noise) Hazard.
Can cause erratic system operation.
Keep wiring at least one foot away from large inductive
loads such as motors, line starters, lighting ballasts
and large power distribution panels.
IMPORTANT
Erratic temperature readings from a sensor can
occur as a result of any of the wiring practices
described below. Avoid these practices to assure
correct operation.
— Be sure wires have a cable separate from the
thermostat cable.
— Do not route temperature sensor wiring with building
power wiring, next to control contactors or near light
dimming circuits, electric motors or welding
equipment.
— Avoid poor wiring connections.
— Avoid intermittent or missing building earth ground.
CAUTION
Electrical Shock Hazard.
Can cause electrical shock or equipment damage.
Disconnect power supply before connecting wiring.
Wiring must comply with applicable codes, ordinances and
regulations.
1.
YES
NO
2.
NO
5 FEET
(1.5 METERS)
3.
4.
NO
5.
6.
Wire C7189 Indoor Sensor to S1and S2 terminals on
the thermostat. For an example of general wiring of
C7189, see Fig. 28 to wire one sensor and 29 to wire
multiple sensors.
Push excess wire back into the hole. Plug the hole
using nonhardening caulk, putty or insulation to prevent
drafts from affecting performance.
Remove C7189 cover.
Mount C7189 to the wall or junction box using the
screws and anchors provided.
Level the C7189 for appearance only. Device functions
correctly even when not level.
Install C7189 cover.
M4476
Fig. 27. Typical location for C7189 Indoor Sensor.
13
68-0280—01
VisionPROTM 8000 Touchscreen Programmable Thermostat
Set Calendar and Time
Thermostat keeps current time and day for up to ten years
under normal use after the calendar is set.
C7189
2
3
When the thermostat is first powered, the display is ready to
set the calendar and time.
RC
R
Y2
1
NOTE: Calendar can also be set in the Installer Setup.
R
C
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
2
IF MORE THAN ONE C7189 REMOTE SENSOR IS REQUIRED,
REFER TO FIGURE 3.
3
WIRES MUST HAVE A CABLE SEPARATE FROM THE
THERMOSTAT CABLE.
1.
2.
Press the arrow keys to set the year, month and day.
Press the Done key.
SET CURRENT DAY
SET MONTH
MO
TUE
WE
E
TH
FR
R
SA
SU
M19972
Fig. 28. Wiring a single C7189 Indoor Sensor.
DONE
Y2
W2
1
S2
1
USE ARROWS TO SET YEAR AND TIME
2
C7189
C7189
C7189
C7189
M22424
3.
4.
Press the arrow keys to set the current time.
Press the Done Key.
Y2
USE ARROWS TO SET YEAR AND TIME
W2
1
2
1
2
C7189
C7189
C7189
MO
C7189
C7189
C7189
C7189
C7189
C7189
WE
W
TH
FR
SA
SU
DONE
1
2
SENSORS MUST BE ARRANGED IN THIS
CONFIGURATION TO OPERATE CORRECTLY.
M22425
WIRES MUST HAVE A CABLE SEPARATE FROM THE
THERMOSTAT CABLE.
M19973
Fig. 29. Wiring Multiple C7189 Sensors.
68-0280—01
14
VisionPROTM 8000 Touchscreen Programmable Thermostat
INSTALLER SETUP
Follow these steps to enter the Installer Setup:
1.
3.
Press and release the System Key.
Release the two blank keys when the screen on the
thermostat matches the screen below.
THU
FAN
ON
Inside
Set To
AUTO
Following
Schedule
SYSTEM
EM HEAT
OFF
A
M
COOL
DONE
SCHED
HOLD
CLOCK SCREE
M22442
M22426A
2.
Press and hold the two blank keys on either side of the
center blank key for approximately five seconds until
screen changes.
4.
MON
TUE
WED
Inside
DONE
FRI
SAT
AT
SUN
ADVANCE TO NEXT
INSTALLER SETUP
Set To
INSTALLER
SETUP
NUMBER
Following
Schedule
SYSTEM
EM HEAT
OFF
COOL
THU
See screen below to review how the thermostat keys
are used during Installer Setup. See Tables 3-5 for the
Installer Setup Numbers and Settings.
CURRENT
SETTING
PM
CANCEL
MON
WED
THU
U
FRI
SAT
AT
SUN
DONE
O
M19923
PRESS TO EXIT
INSTALLER SETUP
5.
15
CHANGE THE
CURRENT
SETTING
M22443
Press the Done key to exit the Installer Setup screen.
68-0280—01
VisionPROTM 8000 Touchscreen Programmable Thermostat
Table 3. Installer Setup Menu.
Installer Setup
Number
Installer Setup Name
Settings
Notes
0120
Date (Year Upper)
Select first two digits of current calendar year (2005, etc)
0130
Date (Year Lower)
Select last two digits of current calendar year (05 for year 2001 - 2178 available
2005, etc)
0140
Date (Month)
Select number that represents current calendar month
—
0150
Date (Day)
Select number that represents current calendar date
—
0160
Schedule Options
0—nonprogrammable
4—7-day programmable
—
0170
System Type Selection
1—1 heat/1 cool conventional (factory setting)
2—single-stage heat pump (no auxiliary heat)
3—heat only conventional (no fan) Also for 750mV.
4—heat only conventional (with fan)
5—heat only (power to open and power to close zone
valves or normally-open zone valves)
6—cool only conventional
7—2 heat/1 cool heat pump (with auxiliary heat)
8—2 heat/2 cool multistage conventional
9—2 heat/1 cool multistage conventional
10—1 heat/2 cool multistage conventional
11—2 heat/2cool heat pump (no auxiliary heat)
12—3 heat/2cool heat pump (with auxiliary heat)
Available options and
defaults vary by
thermostat. System
selection automatically
modifies some default
settings and/or hides
other Installer Setup
options.
0180
Fan Control in Heating
0—gas or oil furnace equipment controls fan in heating
(factory setting)
1—electric furnace—thermostat controls fan in heating
Only shown if
conventional system is
selected. If heat pump is
chosen, fan defaults to
electric.
0190
Changeover Valve—O/B
Terminal Energized in
Heating or Cooling
(Heat Pumps Only)
0—changeover valve—O/B terminal is energized in
cooling (factory setting)
1—changeover valve—O/B terminal is energized in
heating
Only shown if heat pump
system is chosen.
0200
Backup Heat Source
(Auxiliary Heat)
0—heat pump backup heat source is electric (factory
setting)
1—heat pump backup heat source is fossil fuel
Only shown if 2 heat/
1 cool or 3 heat/2 cool
heat pump is chosen
0210
External Fuel Fossil
Fuel Kit
0—no external fossil fuel kit is controlling heat pump
Only shown if fossil fuel is
backup heat. This thermostat controls the dual fuel. Must chosen as backup heat
install outdoor sensor and set Installer Setup Number
source.
0340 to number 2.
1—external fossil fuel kit is controlling heat pump backup
heat
0220
Cycles per hour (cph) for 3—cph recommended for compressors (factory setting)
1st Stage Compressor 1, 2, 4, 5, 6—other cycle rate settings
—
0230
Cycles per hour (cph) for 3—cph recommended for compressors (factory setting)
2nd Stage Compressor 1, 2, 4, 5, 6—other cycle rate settings
Only shown if two stages
of cool are selected.
0240
Cycles per hour (cph) for 1— 1 cph used for steam and gravity
1st Stage Conventional 3—3 cph used for hot water system and high efficiency
Heat
(90% or better) furnaces
5—5 cph used for standard fossil fuel forced air (less than
80% efficient) systems (factory setting)
9—9 cph used for electric furnaces
2, 4, 6, 7, 8, 10, 11, 12—other cycle rate settings
Not shown if system
selection is heat pump.
0250
68-0280—01
Cycles per hour (cph) for
2nd Stage Heat (Aux
Heat for 2H/1C Heat
Pumps)
2001 - 2178 available
Selection in this stage
changes default cph for
2nd stage heat.
Only shown if two stages
1—1 cph used for steam and gravity
3—3 cph for hot water systems and high efficiency (90% of heat are selected.
or better) furnaces
5—5 cph for standard fossil fuel forced air (less than 90%
efficient) systems (factory setting)
9—9 cph used for electric furnaces or electric auxiliary
heat for heat pump systems
2, 4, 6, 7, 8, 10, 11, 12—other cycle rate settings
16
VisionPROTM 8000 Touchscreen Programmable Thermostat
Table 3. Installer Setup Menu. (Continued)
Installer Setup
Number
Installer Setup Name
Settings
Notes
Only shown if 3H/2C
1—1 cph used for steam and gravity
3—3 cph for hot water systems and high efficiency (90% heat pump is selected.
or better) furnaces
5—5 cph for standard fossil fuel forced air (less than 90%
efficient) systems (factory setting)
9—9 cph used for electric furnaces or electric auxiliary
heat for heat pump systems
2, 4, 6, 7, 8, 10, 11, 12—other cycle rate settings
0260
Cycles per hour (cph) for
3rd Stage Heat
(Aux Heat for 3H/2C
Heat Pumps)
0270
Cycles per hour (cph) for 3—3 cph for hot water systems and high efficiency (90% Only shown if 2H/1C or
Em Heat
or better) furnaces
3H/2C heat pump is
5—5 cph for standard fossil fuel forced air (less than 90% selected.
efficient or better) systems
9—9 cph for electric strip heat for heat pumps
0280
Continuous Backlight
0—Backlight not on continuously. Thermostat backlight
comes on with each key press.
1—Backlight is on continuously (thermostat must have a
common wire attached for this function).
Option is always shown;
however, continuously on
backlight works only if
thermostat is wired with
24 Vac Common.
0300
Changeover
0—manual changeover (factory setting)
1—auto changeover
—
0310
Deadband
Heating and cooling setpoints can be set no closer than
chosen value:
2—2°F (1.5°C)
3—3°F (2°C)
4—4°F (2.5°C)
5—5°F (3°C)
6—6°F (3.5°C)
7—7°F (4°C)
8—8°F (4.5°C)
9—9°F (5°C)
Shown only if automatic
changeover is selected.
0320
Temperature Indication
Scale
0—fahrenheit temperature display (factory setting)
1—celsius temperature display
—
0330
Daylight Savings
1—daylight savings is on (factory setting).
0—daylight savings is off.
Set to 0 in areas that do
not follow daylight
savings.
0340
Remote Temperature
Sensor (Outdoor or
Indoor)
0—no remote temperature sensor
1—outdoor temperature sensor for display only.
2—outdoor temperature sensor for control. Outdoor
sensor used for Heat Pump Lockout settings. (See Heat
Pump Temperature Lockout section for more details.)
3—indoor temperature sensor
Defaults and Options
depend on System Type
selection.
0350
Heat Pump Compressor 0—no compressor lockout.
Lockout or (Balance
15°F (-9.5°C)
Point)
20°F (-6.5°C)
25°F (-4°C)
30°F (-1°C)
35°F (1.5°C)
40°F (4.5°C)
45°F (7°C)
17
Indoor Temperature
Sensor uses an averaging
network and does not
include on-board sensor.
Default depends on other
selections. Shown if
Outdoor Temperature for
control is selected. (See
Advanced Features
section for more
information.)
68-0280—01
VisionPROTM 8000 Touchscreen Programmable Thermostat
Table 3. Installer Setup Menu. (Continued)
Installer Setup
Number
Installer Setup Name
Settings
0360
Heat Pump Auxiliary
Lockout
0—no auxiliary heat lockout.
40°F (4.5°C)
45°F (7°C)
50°F (10°C)
55°F (13°C)
60°F (15.5°C)
0380
Indoor Dehumidification 0—No indoor dehumidification control.
Control
1—Dehumidification control activated.
Notes
Shown if electric is
chosen for backup heat
source and outdoor
temperature sensor for
control is selected. (See
Advanced Features
section for more
information.)
Available on select
models.
If dehumidification control
is activated and autochangeover is selected in
Installer Setup Number
0300, the deadband
minimum is defaulted to
5°F (3°C) in Number
0310.
Furnace Change
Reminder
0510
Humidifier Pad
0—humidifier pad replacement reminder off
Replacement Reminder 1—90 calendar days
2—180 calendar days
3—365 calendar days
—
0520
UV Lamp Replacement
Reminder
0—UV lamp replacement reminder off
1—365 calendar days
—
0530
Adaptive Intelligent
Recovery™
1—Adaptive Intelligent Recovery™ control is activated
(system starts early so setpoint is reached by start of
program period).
0—Conventional Recovery (system starts recovery at
programmed time)
—
0540
Number of Periods
2—two periods available (Wake and Sleep)
4—four periods available (Wake, Leave, Return and
Sleep)
Not shown if nonprogrammable is
selected. 2 or 4 applies to
all days of the week.
0580
Minimum Compressor
Off Time
5—five-minute compressor off-time setting (factory
setting)
0, 2, 3, 4—other compressor off-time settings
—
0600
Heat Temperature
Range Stop
40-90—temperature range (1°F increments) of heating
setpoint.
Shown in 1/2 °C.
0610
Cool Temperature
Range Stop
50-99—temperature range (1°F increments) of cooling
setpoint.
Shown in 1/2 °C.
0640
Clock Format
12—12 hour clock (factory setting)
24—24 hour clock
—
68-0280—01
0—furnace filter reminder off
1—10 run time days
2—30 run time days
3—60 run time days
4—90 run time days
5—120 run time days
6—365 run time days
Run time based on call for
fan.
0500
18
VisionPROTM 8000 Touchscreen Programmable Thermostat
Table 3. Installer Setup Menu. (Continued)
Installer Setup
Number
Installer Setup Name
Settings
Notes
0650
Extended Fan OnTime
Heat
0—no extended fan operation after call for heat ends
90— fan operation is extended 90 seconds after call for
heat ends.
Not shown if fan operation
is set to fossil fuel or in
Cool Only Systems
0660
Extended Fan On Time
Cool
0—no extended fan operation after call for cool ends
90—fan operation is extended 90 seconds after call for
cool ends.
Not shown in Heat Only
Systems.
0670
Keypad Lockout
0—unlocked keypad
1—partially locked keypad
2—fully locked keypad
Unlocked—all functions
are available.
Partially locked—only
temperature up and down
keys and ability to enter
and modify Installer Setup
mode are available.
Fully locked—only ability
to enter and modify
Installer Setup mode are
available.
0680
Temperature Control in
Heat
1—less aggressive temperature control (could cause
temperature undershoot)
2—Standard temperature control in heating (factory
setting)
3—more aggressive temperature control (could cause
temperature overshoot)
Applies to recovery ramp
and use of auxiliary heat
during recovery.
Choose 1 if getting
temperature overshoot.
Choose 3 if getting
temperature undershoot.
0690
Temperature Control in
Cool
1—less aggressive temperature control (could cause
temperature undershoot)
2—Standard temperature control in cooling
(factory setting)
3—more aggressive temperature control (could cause
temperature overshoot)
Applies to recovery ramp.
—
Choose 1 if getting
temperature overshoot.
Choose 3 if getting
temperature undershoot.
0700
Temperature Display
Offset
-3 —°F (-1.5°C)
-2 —°F (-1°C)
-1 —°F (-.5°C)
0 —°F (0. °C) — (no difference in displayed temperature
and actual room temperature )
1 —°F (.5°C)
2 —°F (1°C
3 —°F (1.5°C)
0710
Reset Thermostat
Only calendar settings
0—no thermostat reset.
1—resets all Installer Setup Options to default values and and time are retained.
resets schedule to default setting.
19
68-0280—01
VisionPROTM 8000 Touchscreen Programmable Thermostat
INSTALLER SYSTEM TEST
Use the Installer System Test to test the heating, cooling and
fan (and emergency heat for heat pump systems).
SYSTEM TEST
NUMBER
CAUTION
SYSTEM STATUS
NUMBER
UP ARROW
TURNS THE
SYSTEM ON
Equipment Damage Hazard.
Minimum compressor off time is bypassed during
Installer System Test
Avoid cycling compressor quickly.
How to Use the Installer System Test
The Installer Test is part of the Installer Setup Menu.
1.
2.
3.
Enter the Installer System Test by entering the Installer
Setup.
Note that the test appears at the end of the Installer
Setup Numbers.
See Fig. 30 to review how the thermostat buttons are
used during the Installer System Test. See Table 6 for
available Installer System Tests.
DONE
DONE KEY
UP ARROW KEY
EXITS INSTALLER ADVANCES TO
SYSTEM TEST
NEXT SYSTEM
TEST NUMBER
DOWN ARROW
TURNS THE
SYSTEM OFF
M22428
Fig. 30. Review thermostat buttons used during Installer
System Test.
Installer System Tests
IMPORTANT
Use the Installer System Test to test the heating, cooling, fan and emergency heat. The setting you choose for System
Type (Installer Setup Number 0170) may prevent some System Test Numbers from appearing.
Table 4. Installer System Test.
System Test Number
Test Type
System Status Number and Description
Test 1
Cooling System Test
1—Cool stage 1 turns on.
2—Cool stage 1 and stage 2 turn on.
0—Cool is off.
Test 2
Fan System Test
1—Fan turns on.
0—Fan turns off.
Test 3
Heating System Test
1—Heat stage 1 turns on.
2—Heat stage 1 and stage 2 (aux heat) turn
on.
0—Heat is off.
Test 4
Emergency Heat Test
1—Emergency heat turns on.
2—Emergency heat and auxiliary heat turn on.
0—Emergency heat turns off.
Press the Next button to go to the beginning of the Installer Setup or press the Done button to exit the Installer
System Test.
68-0280—01
20
VisionPROTM 8000 Touchscreen Programmable Thermostat
OPERATION
System and Fan Settings
Thermostat Keys
System
The System key selections vary based on your heating and/or
cooling system type.
SYSTEM
DOWN ARROW
SELECTS EM.
HEAT/HEAT/OFF/COOL
LOWERS TEMPERATURE
SETTING
Heat — Thermostat controls the heating system.
Off — Both heating and cooling systems are off.
Cool — Thermostat controls the cooling system.
Auto — Thermostat automatically changes between heating
and cooling operation, depending on indoor temperature.
Em. Heat — Emergency heat cycles to maintain temperature.
Compressor is locked out (used only for 2H/1C or 3H/2C heat
pump systems) and auxiliary heat turns on as second stage if
needed.
UP ARROW
FAN
RAISES
TEMPERATURE
SETTING
SELECTS
ON/AUTO/CIRC
TUE
U
FAN
Inside
n
Set To
AUTO
Fan
Following
Schedule
SYSTEM
The Fan key selections vary based on the heating and/or
cooling system type.
HEAT
AM
SCHED
HOLD
CLOCK
SCREEN
SCHED
CLOCK
MORE
ENTERS
SCHEDULING
MODE
SETS THE
TIME
FORWARD
OR BACK
SHOWS ADDITIONAL
ACCESSORY AND
MAINTENANCE
OPTIONS
HOLD
On — Fan runs continuously. Use this setting for improved air
circulation or for more efficient central air cleaning.
Auto — fan follows the fan program schedule.
Circ — fan runs randomly approximately 35% of the time.
Use this setting for improved air circulation or for more
efficient central air cleaning when you do not want the fan
running continuously.
MORE
SCREEN
SETS A PERMANENT
HOLD AND ACTIVITIES
VACATION HOLD
User Setup
LOCKS OUT THE
SCREEN TO ALLOW
FOR CLEANING
M22444
Follow these steps to enter the User Setup:
1.
Thermostat Display
Press and release the System key.
INSIDE TEMPERATURE
TUE
SHOWS THE CURRENT INSIDE
TEMPERATURE
SHOWS CURRENT DAY
OF THE WEEK
SET TO
TEMPERATURE
FAN
SHOWS FAN
SETTING
THU
FAN
ON
SHOWS THE
CURRENT SET
TEMPERATURE
Inside
Set To
AUTO
Following
Schedule
SYSTEM
EM HEAT
TUE
FAN
OFF
A
M
COOL
SCHED
Inside
HOLD
CLOCK SCREE
Set To
AUTO
Following
Schedule
SYSTEM
HEAT
M22426A
AM
SCHED
HOLD
CLOCK
SCREEN
SYSTEM
TIME
SHOWS
CURRENT
SYSTEM
POSITION
DISPLAY CURRENT
TIME OF DAY, HOLD
TIME REMAINING OR
NUMBER OF VACATION
DAYS REMAINING
MORE
FOLLOWING
SCHEDULE
SHOWS THE
THERMOSTAT IS
FOLLOWING THE
PROGRAMMED
SCHEDULE
M22239
21
68-0280—01
VisionPROTM 8000 Touchscreen Programmable Thermostat
2.
Press and hold the center blank key for approximately
five seconds until the screen changes.
4.
See the screen below to review how the thermostat
keys are used during the User Setup. See Table 5 for
the User Setup numbers and settings.
ADVANCE TO NEXT
USER SETUP
USER SETUP
NUMBER
CURRENT
SETTING
TUE
CHANGE FILTER UV LAMP HUMIDIFIER PAD
Inside
Set To
Following
Schedule
SYSTEM
EM HEAT
OFF
COOL
DONE
MON
WED
THU
U
FRI
SAT
AT
SUN
PM
CANCEL
DONE
O
M22439
3.
Release the center blank key when the screen on the
thermostat matches the screen below.
PRESS TO EXIT
USER SETUP
5.
CHANGE THE
CURRENT
SETTING
M19922
Press the Done key to exit the User Setup screen.
Table 5. User Setup Settings.
User
Setup
Number
DONE
M22440
68-0280—01
22
User Setup
Name
Settings
0120
Date (first two
digits of year)
Select first two digits of
current calendar year (20
for year 2005, etc)
0130
Date (last two
digits of year)
Select last two digits of
current calendar year (05
for year 2005, etc)
0140
Date (month)
Select number of current
calendar month (1-12)
0150
Date (day)
Select number of current
calendar date (1-31)
0160
Schedule options
0—Non-programmable
4—7-day programmable
(factory setting)
0320
Display
temperature
in °F or °C
0—°F setting (factory
setting)
1—°C setting
0330
Daylight savings
time
1—Daylight savings is on
(factory setting)
0—Daylight savings is off
VisionPROTM 8000 Touchscreen Programmable Thermostat
PROGRAMMING
Table 5. User Setup Settings.
User
Setup
Number
0500
0510
User Setup
Name
Furnace air filter
Preprogrammed Energy-saving Settings
Settings
Table 6 shows default program settings.
0—off (factory setting)
1—10 fan run time days
(about one month)
2—30 fan run time days
(about three months)
3—60 fan run time days
(about six months)
4—90 fan run time days
(about nine months)
5—120 fan run time days
(about one year)
6—365 fan run time days
(about three years)
Table 6. Energy-saving Default Program Settings.
Schedule
Period
Setpoints
Fan
Setting
Time
Heat
Cool
Wake
6:00AM
70°F
(21°C)
78°F
(25.5°C)
Auto
Leave
8:00AM
62°F
(16.5°C)
85°F
(29.50C)
Auto
Humidifier pad
reminder
0—off
1—3 months
2—6 months
3—12 months
Return
6:00PM
70°F
(21°C)
78°F
(25.5°C)
Auto
0520
UV lamp reminder
0—off (factory setting)
1—1 year
Sleep
10:00PM
62°F
(16.5°C)
82°F
(28°C)
Auto
0540
Number of
schedule periods
available
2—two (Wake and Sleep)
4—four (Wake, Leave,
Return, Sleep)—factory
setting
0640
Clock format
12—12-hour clock
(factory setting)
24—24-hour clock
0670
Screen lockout
0—all keys available;
screen is unlocked
(factory setting)
1—screen is partially
locked. All key functions
locked except Temperature Up and Down keys
and Cancel key.
2—screen is fully locked
23
Program Heating and Cooling Schedule
Your thermostat can control up to four different schedule
periods per day:
Wake—Period when you awaken and want your home at a
comfortable temperature.
Leave—Period when you are away from home and want an
energy-saving temperature.
Return—Period when you return home and want your home
back to a comfortable temperature.
Sleep—Period when you are asleep and want an energysaving temperature.
NOTE: Schedule times are in 15-minute intervals.
68-0280—01
VisionPROTM 8000 Touchscreen Programmable Thermostat
Edit Schedule
1.
NOTE: The Fan setting can be programmed for On, Auto, or
Circ for each period selected. See Fan Schedule
section for more information.
Press Sched key.
6.
7.
8.
9.
FRI
FAN
Inside
Set To
AUTO
Press Leave key and repeat step 5.
Press Return key and repeat step 5.
Press Sleep key and repeat step 5.
When complete, press Done key. “Saving Changes”
appears on the screen to indicate changes are being
saved to the day(s) modified.
Following
Schedule
SYSTEM
HEAT
MON
TUE
WED
THU
FRI
AM
PM
SCHED
HOLD
CLOCK
SCREEN
SAVING
CHANGES
M22445
2.
Press Edit key.
MON
FAN
TUE
WED
THU
FRI
SAT
Inside
Set To
M19956
CANCEL
PERIOD
SYSTEM
EM HEAT
HEAT
OFF
COOL
AUTO
Following
Schedule
AM
PM
SCHED
EDIT
HOLD
WAKE
NOTE: To set a Program Schedule for the remaining days of
the week, repeat steps 1-9. Example: If Mon - Fri
was selected first, go back and repeat steps 1-9 for
Sat and Sun.
HEAT
AUTO
DONE
SUN
OK TO PICK MULTIPLE DAYS SCREEN LOCKED
10.
COOL
CLOCK
LEAVE
SCREEN
RETURN
SLEEP
Cancel a Schedule Period
CANCEL
1.
2.
3.
4.
M22553
3.
To exit schedule without saving changes, press Cancel
key any time.
It is OK to pick multiple days. Select any combination of
days to edit. These days are scheduled with the same
times and temperatures. Check marks appear next to
days selected.
5.
Press Sched key.
Press Edit key.
Select the Day(s) of the week desired.
Press schedule period you want to cancel (Wake,
Leave, Return or Sleep). Once selected, the period
flashes.
Press Cancel Period key.
MON
MON
FAN
ON
AUTO
CIRC
TUE
WED
THU
FRI
SAT
FAN
SUN
OK TO PICK MULTIPLE DAYS
TUE
WED
THU
FRI
SAT
Inside
Set To
HEAT
AUTO
HEAT
AM
CANCEL
PERIOD
SYSTEM
EM HEAT
HEAT
OFF
COOL
AUTO
CANCEL
PERIOD
COOL
Following
Schedule
AM
PM
SCHED
DONE
SUN
OK TO PICK MULTIPLE DAYS SCREEN LOCKED
HOLD
WAKE
COOL
CLOCK
LEAVE
SCREEN
RETURN
SLEEP
CANCEL
M22446
DONE
4.
5.
WAKE
LEAVE
RETURN
SLEEP
CANCEL
M19955
Press Wake key. Once pressed, Wake flashes to show it
is selected.
Press Up and Down keys to modify time and heat and
cool temperatures from this screen.
68-0280—01
24
6.
The time, temperature(s) and fan setting disappear. The
bar above the selected period is removed, indicating the
scheduled period was cancelled.
VisionPROTM 8000 Touchscreen Programmable Thermostat
NOTE: To reinstate a schedule period, press arrow keys to
set desired time and temperatures.
TUE
MON
WED
THU
FRI
SAT
SUN
OK TO PICK MULTIPLE DAYS
FAN
Fan Control (Table 7)
If the Fan program is scheduled, Auto is shown and any
programmable mode that is set; for example, if during Wake
period, Fan is set to Auto, only Auto is shown in the Fan area.
However, if during the Wake period, fan is scheduled to On,
both Auto and On are shown. Auto indicates fan is running its
schedule; On indicates Fan schedule is set to On.
HEAT
THU
FAN
ON
AUTO
COOL
Inside
Set To
Following
Schedule
SYSTEM
DONE
WAKE
LEAVE
RETURN
SLEEP
CANCEL
HEAT
AM
M19957
7.
Press Done key.
SCHED
HOLD
CLOCK
SCREEN
Fan Schedule
M19962
Press Fan key while in the Scheduling Screen to program the
System Fan. Choices available from the Scheduling Screen:
Auto (default position)—fan runs with equipment.
Programmable for all schedule periods (Wake, Leave, Return
and Sleep).
On—fan runs continuously (programmable for all schedule
periods).
Circ—fan runs randomly for approximately 35% of schedule
period (programmable for all schedule periods).
MON
FAN
TUE
WED
THU
FRI
SAT
Inside
Set To
HEAT
AUTO
CANCEL
PERIOD
SYSTEM
EM HEAT
HEAT
OFF
COOL
AUTO
HOLD
WAKE
Fan
Setting
Fan
Program
Schedule
Call
for
Action
Energize
Terminal
Fan
Status
shown on
Screen
Auto
Auto
None
None
Auto
Auto
On
Fan
G
Auto/On
Auto
Circ
None
None
Auto/Circ
Auto
Circ
Fan
G
Auto/Circ
Following
Schedule
AM
PM
SCHED
DONE
SUN
OK TO PICK MULTIPLE DAYS SCREEN LOCKED
Table 7. Fan Program Operation and Screen Status.
COOL
CLOCK
LEAVE
SCREEN
RETURN
SLEEP
CANCEL
M22447
25
68-0280—01
VisionPROTM 8000 Touchscreen Programmable Thermostat
Manual Override of Fan Schedule (Table 8)
Auto—fan is automatically following the Fan schedule
(choices are Auto, On or Circulate).
On—overrides Fan schedule. Fan is continuously On.
Circ—overrides Fan schedule. Fan circulates randomly for
approximately 35% of time until the Auto position is selected.
Operate VisionPRO™ 8000 Touchscreen
Set Time
1.
2.
Press Clock.
Use arrows to set current time.
TUE
Table 8. Manual Override of Fan Schedule Operation.
Fan
Setting
Fan
Schedule
Override
Setting
Call
for
Action
Energize
Terminal
Screen
Message
Under
Fan
Setting
Auto
On
Fan
G
On
Auto
Circ
None
None
Circ
Auto
Circ
Fan
G
Circ
On
Autoa
On
Circ
None
None
Circ
On
Circ
Fan
G
Circ
Circ
Autoa
Circ
On
AM
DONE
CANCEL
M19958
—
—
—
Fan
—
—
G
3.
Press Done key.
IMPORTANT
The current day of the week should already be set
correctly. If not, see Installer Setup to set the day.
—
Set Temperature Overrides
The thermostat has three temperature override options: Hold
Temperature Until, Permanent Hold and Vacation Hold.
On
aAuto
HOLD TEMPERATURE UNTIL (TEMPORARY HOLD)
Holds temperature temporarily until the next scheduled period
time or until the time the user sets.
Override resumes the Fan Program in each schedule
period (Wake, Leave, Return and Sleep)
1.
Press Up or Down arrow next to the temperature you
want to adjust. “Hold Temperature Until” time appears
on the screen. The Hold Temperature Until time defaults
to the start time of the next scheduled period.
NOTE: The Time Up and Down arrows are shown for
approximately seven seconds. Pressing on the
screen time (where the Hold Temperature Until time
is shown) allows the arrows to reappear.
68-0280—01
26
VisionPROTM 8000 Touchscreen Programmable Thermostat
2.
3.
Press Up or Down arrow next to the Time key to set
desired time for the thermostat to resume schedule.
NOTE: Days Up and Down arrows appear for approximately
seven seconds. Pressing just below Hold Temperature Until on the screen allows the Days Up and
Down arrows to reappear.
TUE
FAN
Press Up and Down arrow keys to change the number
of Days you desire thermostat to override the schedule.
Inside
Set To
AUTO
SYSTEM
HEAT
THU
Hold Temperature
Until
FAN
PM
SCHED
HOLD
CLOCK
SCREEN
HEAT
M19959
SCHED
PERMANENT HOLD
Permanent Hold changes the temperature setting until
Permanent Hold is cancelled.
2.
Hold Temperature
Until
DAYS
Press the Cancel or Sched key to cancel “Hold
Temperature Until” and resume schedule.
NOTE: Once “Hold Temperature Until” time is reached, the
thermostat shows “Following Schedule” on the
screen to indicate that “Temporary Hold” has ended.
1.
Set To
SYSTEM
CANCEL
3.
Inside
AUTO
CLOCK
SCREEN
CANCEL
M19961
4.
To cancel the Vacation Hold override early, press the
Cancel key.
NOTE: When the number of days of Vacation Hold expires,
the screen shows “Following Schedule” to indicate
that Vacation Hold has ended.
Press Hold key. “Permanent Hold” appears on the
screen.
Press Up or Down arrow next to the temperature you
want to set during “Hold.”
Clean Thermostat Screen
The thermostat has a touch screen interaction. Follow these
steps to clean the screen without making thermostat changes:
1. Press the Screen key. Thermostat locks out all touch
keys for 30 seconds to allow for cleaning.
TUE
FAN
Inside
Set To
AUTO
SYSTEM
OK TO
CLEAN
SCREEN
HEAT
AM
Permanent
Hold
SCHED
HOLD
CLOCK
SCREEN
CANCEL
M19960
3.
M19964
Press Cancel key to cancel “Permanent Hold” and
resume the schedule.
2.
VACATION HOLD
Changes temperature setting for a designated number of
days.
1. Press the Up and Down arrow keys to set the desired
temperature while away on vacation. Notice that “Hold
Temperature Until” time is shown on the screen. (This is
the time the Vacation Hold override expires after the
number of days ends.)
2. Press Hold key twice. Screen shows “Hold Temperature
Until” one day.
27
3.
Use damp cloth slightly moistened with water or household glass cleaner to clean the screen.
Repeat the above steps, as necessary.
IMPORTANT
Do not spray any type of liquid directly on the
thermostat itself. If using household glass cleaner,
spray cleaner on cloth. Then use a cloth to clean
the thermostat screen.
4.
Press the Done key to return to the Home Screen and
normal operation.
68-0280—01
VisionPROTM 8000 Touchscreen Programmable Thermostat
Replace Batteries
1.
4.
When the LO Battery indicator is flashing, replace the
batteries promptly with three fresh AAA alkaline
batteries
Align the screw blocks with the pins on the back of the
thermostat.
WALLPLATE
PINS ON
BACK OF
THERMOSTAT
TERMINAL
SCREW
BLOCK
M19963
2.
Remove thermostat from the wallplate by pulling
straight out.
WALL
M22213
5.
Push the thermostat straight onto the wallplate until it
snaps into place.
Battery Tips
1.
2.
3.
Replace the batteries as soon as LO Batt flashes in the
display. The LO Battery indicator flashes in the display
one month before the batteries run down completely.
Always use fresh AAA alkaline batteries. Non-alkaline
batteries do not last as long and can leak, causing
thermostat damage.
Although the thermostat has a Low Battery indicator,
replace the batteries once a year to prevent the thermostat and heating/cooling system from shutting down due
to lack of battery power.
M22430
3.
Screen Locks
Remove the old batteries and insert three fresh AAA
alkaline batteries, as marked on the thermostat.
TUE
BACK OF THERMOSTAT
FAN
SCREEN LOCKED
Inside
Set To
AUTO
Following
Schedule
SYSTEM
+
HEAT
+
PM
+
SCHED
BATTERIES
(3)
68-0280—01
HOLD
CLOCK
SCREEN
MORE
M19965
M22212
28
VisionPROTM 8000 Touchscreen Programmable Thermostat
Partially Locked Screen
When partially locked, the screen indicates Screen Locked for
5 to 7 seconds whenever the user attempts to press a key that
is locked. Pressing a locked key, while Screen Locked is
shown, flashes “Screen Locked” on the screen.
Remote Indoor Temperature
If a remote indoor temperature sensor is installed, the
thermostat displays the inside temperature on the screen from
the remote sensor(s).The thermostat internal temperature
sensor is not used.
In this mode, all keys are locked except the Temperature Up
and Down arrow keys:
— User can change temperature up or down but cannot
change schedule settings.
— Temporary temperature change lasts until next scheduled
period and that time shows on screen.
— To cancel temperature override and begin following
schedule, press Cancel key.
— To unlock screen, see Installer Setup section.
MON
FAN
MON
FAN
TUE
WED
THU
Inside
FRI
SAT
AT
SUN
Set To
Outside
HOLD
CLOCK
SCREEN
SUN
Set To
Heat On
Following
Schedule
HEAT
AM
SCHED
HOLD
CLOCK
SCREEN
MORE
M19974
ONE REMOTE INDOOR SENSOR INSTALLED (OPTIONAL)
If one remote indoor temperature sensor is used, the screen
showing the Inside temperature reading shows the
temperature at the indoor remote sensor location. The
thermostat internal temperature sensor is not used.
Filter Change Reminder
AM
SCHED
SAT
AT
Indoor Air Quality Reminders
Following
Schedule
HEAT
Inside
FRI
MULTIPLE REMOTE INDOOR SENSORS INSTALLED (OPTIONAL)
If more than one remote indoor sensor is used, the screen
showing Inside temperature reading shows the average of all
the remote indoor sensors. The thermostat internal
temperature sensor is not used.
AUTO
SYSTEM
THU
SYSTEM
In this mode, all keys are locked and not functional. To unlock
screen, see Installer Setup section. The screen continuously
displays “Screen Locked.”
If an outdoor temperature sensor is installed, the thermostat
displays the outside temperature in the lower right corner of
the Home Screen.
WED
AUTO
Fully Locked Screen
Outdoor Temperature
TUE
The filter change reminder must be turned on from the
Installer Setup. Once expired, the screen flashes, “Change
Filter” and a Reset key appears. Press the Reset key to reset
the change reminder.
MORE
M22453
If thermostat is set to Auto Changeover System mode, press
the More key until the outside temperature is shown on the
screen.
MON
FAN
TUE
WED
THU
FRI
SAT
AT
SUN
OK TO PICK MULTIPLE DAYS SCREEN LOCKED
CHANGE FILTER
R UV LAMP HUMIDIFIER PAD
Inside
Set To
AUTO
MON
TUE
WED
THU
FRI
SAT
SUN
SYSTEM
Following
Schedule
RESET
HEAT
PM
SCHED
HOLD
CLOCK
SCREEN
MORE
Outside
M19975
SCHED
DONE
HOLD
WAKE
CLOCK
LEAVE
SCREEN
RETURN
SLEEP
NOTE: The days are counted as fan run time, so anytime
the fan is running, the reminder is counting that time
against the number of days selected.
CANCEL
M22448
29
68-0280—01
VisionPROTM 8000 Touchscreen Programmable Thermostat
The remaining run time days can be viewed by pressing the
More key; the remaining days can be edited using the More
key or from the Installer Setup. To view or reset the reminder
before it expires, follow these steps using the More key:
1.
4.
Press the Done key to go back to the viewing screen.
MON
Press the More key until the filter reminder appears on
the screen. This is the number of fan run-time days
remaining on the filter reminder.
TUE
WED
THU
FRI
SAT
SUN
CHANGE FILTER UV LAMP HUMIDIFIER PAD
RESET
MON
TUE
WED
THU
FRI
SAT
SUN
DAYS
CHANGE FILTER UV LAMP HUMIDIFIER PAD
DONE
SCHED
EDIT
HOLD
WAKE
CLOCK
LEAVE
SCREEN
RETURN
MORE
SLEEP
RESET
M22449
5.
DAYS
DONE
SCHED
EDIT
HOLD
WAKE
CLOCK
LEAVE
SCREEN
RETURN
MORE
SLEEP
Press the Reset key to activate the new number of days
selected in the previous screen.
CANCEL
MON
M22449
2.
3.
CANCEL
Press the Edit key.
Use the Up and Down keys to change the number of
run-time days.
TUE
WED
THU
FRI
SAT
SUN
CHANGE FILTER UV LAMP HUMIDIFIER PAD
RESET
MON
TUE
WED
THU
FRI
SAT
SUN
DAYS
CHANGE FILTER UV LAMP HUMIDIFIER PAD
DONE
SCHED
EDIT
HOLD
WAKE
CLOCK
LEAVE
SCREEN
RETURN
MORE
SLEEP
CANCEL
M22451
6.
DAYS
SCHED
DONE
HOLD
WAKE
CLOCK
LEAVE
SCREEN
RETURN
SLEEP
CANCEL
M22450
68-0280—01
30
Press the Done key to return to the Home screen.
VisionPROTM 8000 Touchscreen Programmable Thermostat
Humidifier Pad Reminder
The Humidifier Pad change reminder must be turned on from
the Installer Setup. Once expired, the screen flashes,
“Change Humidifier Pad” and a Reset key appears. Press the
Reset key to reset the change reminder.
The remaining calendar days can be viewed by pressing the
More key. The remaining days can be edited using the More
key or from the Installer Setup. To view or reset the reminder
before it expires, follow these steps using the More key:
1.
2.
3.
4.
5.
6.
Press the More key until the Humidifier Pad change
reminder appears on the screen. This is the number of
calendar days remaining on the Humidifier Pad
reminder.
Press the Edit key.
Use the Up and Down keys to change the number of
calendar days.
Press the Done key to go back to the viewing screen.
Press the Reset key to activate the new number of days
selected in the previous screen.
Press the Done key to return to the Home Screen.
UV Lamp Reminder
The UV Lamp change reminder must be turned on from the
Installer Setup. Once expired, the screen flashes, “Change
UV Lamp” and a Reset key appears. Press the Reset key to
reset the change reminder.
The remaining calendar days can be viewed by pressing the
More key. The remaining days can be edited using the More
key or from the Installer Setup. To view or reset the reminder
before it expires, follow these steps using the More key:
1.
2.
3.
4.
5.
6.
Press the More key until the UV Lamp change reminder
appears on the screen. This is the number of calendar
days remaining on the UV Lamp reminder.
Press the Edit key.
Use the Up and Down keys to change the number of
calendar days.
Press the Done key to go back to the viewing screen.
Press the Reset key to activate the new number of days
selected in the previous screen.
Press the Done key to return to the Home Screen.
Temperature Recovery
The thermostat feature, Adaptive Intelligent Recovery™,
eliminates all guesswork when setting the thermostat
schedule.
Simply set the program schedule to the time that the comfort
temperature is desired. The thermostat then turns on the
heating or cooling at just the right time to have the home
reach the scheduled temperature at the scheduled time.
For example—get up at 6:00 AM and want the temperature to
be 70°F. Set the Wake period for 6:00 AM and 70°F. The
thermostat then turns on the heat before 6:00 AM to raise the
temperature to 70°F by 6:00 AM.
31
The thermostat alerts that the heating or cooling system is
coming on before a scheduled time by showing “Recovery” on
the screen.
TUE
FAN
Inside
Set To
AUTO
Following
Schedule
SYSTEM
Recovery
HEAT
PM
SCHED
HOLD
CLOCK
SCREEN
MORE
M22301
NOTE: It takes about a week for the thermostat to adjust to
local weather, the schedule, the construction of the
home and the heating and/or cooling system. Each
day it adjusts the next day’s recovery start time
accordingly.
P+I Control
The thermostat microprocessor-based control requires that
the user understands temperature control and thermostat
performance. A conventional mechanical or electronic
thermostat does not control temperature precisely at setpoint.
Typically there is an offset (droop) in the control point as the
system load changes. This is a phenomenon that most people
in the industry know and accept. Many factors contribute to
offset including switch differential, thermal lag, overshoot,
cycle rates and system load.
The thermostat microprocessor simultaneously gathers,
compares and computes data. Using this data, it controls a
wide variety of functions. The special proprietary algorithm
(program) in the thermostat eliminates the factors causing
offset. This makes temperature control more accurate than
the conventional mechanical or electronic thermostats. The
temperature control algorithm is called proportional plus
integral (P+I) control.
The thermostat sensor, located on the thermostat or remote,
senses the current space temperature. The proportional error
is calculated by comparing the sensed temperature to the
programmed setpoint. The deviation from the setpoint is the
proportional error.
The thermostat also determines integral error, which is a
deviation based on the length of error time. The sum of the
two errors is the (P+I) error. The cycle rate used to reach and
maintain the setpoint temperature is computed using the P+I.
The additon of the integral error is what differentiates the
thermostat from many other electronic and mechanical
thermostats. See Fig. 31.
68-0280—01
VisionPROTM 8000 Touchscreen Programmable Thermostat
Inside Humidity Level
Select models can sense the humidity level in the home. The
humidity level in the home is shown in the lower right corner of
the Home Screen.
THERMOSTAT
COOL SETPOINT
PROPORTIONAL COOL
CONTROL POINT
TEMPERATURE
P+I CONTROL
POINT
TUE
P+I CONTROL POINT
FAN
PROPORTIONAL HEAT
CONTROL POINT
Inside
Set To
AUTO
THERMOSTAT
HEAT SETPOINT
Following
Schedule
SYSTEM
HEATING
COOLING
HEAT
100
50
0
PERCENT LOAD
50
PM
100
Humidity
M4414
SCHED
Fig. 31. Proportional temperature control versus P+ I
temperature control.
The Thermostat has built-in compressor protection (minimumoff timer) that prevents the compressor from restarting too
early after a shutdown.
The minimum-off timer is activated after the compressor turns
off.
MON
SCHED
DONE
Following
Schedule
SYSTEM
THU
HOLD
WAKE
CLOCK
LEAVE
FRI
SAT
SUN
AM
PM
HOLD
CLOCK
SCREEN
SCREEN
RETURN
SLEEP
CANCEL
M22452
HEAT
MORE
M22244
When the minimum-off timer expires, “Cool On” or “Heat On”a
appears solidly in the display and the compressor and fan turn
on.
_________
Pumps only.
68-0280—01
WED
Set To
WaitCool
aHeat
TUE
WED
Inside
SCHED
MORE
Inside
AUTO
COOL
SCREEN
If thermostat is set to Auto Changeover System mode, press
the More key until the humidity level is shown on the screen.
If there is a call during the minimum-off timer, the thermostat
shows “Wait” in the display.
FAN
CLOCK
M19966
Minimum Off-Timer
TUE
HOLD
32
VisionPROTM 8000 Touchscreen Programmable Thermostat
Control Dehumidification Setting (Select Models)
Select models read the inside humidity level and allow for a
dehumidification setting:
1. Press the More key until the inside humidity percent and
dehumidification setpoint are shown.
Heat Pump Emergency Heat LED Indication
(Requires 24 Vac Common Connection)
The thermostat uses a red LED indicator that lights when the
thermostat is in the Emergency Heat mode. The LED is
located in the upper right corner of the thermostat. It is visible
only when on. When the thermostat is in the Em. Heat system
mode, the L terminal is continuously energized and the LED is
on.
Heat Pump Temperature Lockouts
Inside
Humidity
Dual Fuel Heat Pump and Outdoor Temperature
Sensor
DEHUMIDIFIER
In this operation, there is no external fossil fuel kit (dual fuel
kit) installed; the thermostat controls this function.
1.
CANCEL
M19967
2.
3.
2.
Use Up and Down arrow keys, located to the right of the
dehumidifier setpoint, to set desired humidity level for
dehumidification in the summer.
Press Done key.
Dehumidification Droop Control
Special Heat Pump Operation
Heat Pump LED Indication (Requires 24 Vac
Common Connection)
A red LED indication is located in the upper right corner of the
thermostat. It is only visible when lighted.
When the L terminal is wired to an equipment monitor, the
LED signals when a check or fail signal is sent to the
thermostat from the system. This is operational in the Heat,
Off, Cool or Auto positions. See Fig. 32.
OPERATION IN HEAT MODE ABOVE BALANCE POINT (OUTDOOR
TEMPERATURE)
When the outdoor temperature is above the selected Balance
Point Temperature (ISU 0350), only the compressor operates
and the fan (G terminal) energizes when the thermostat calls
for heat. See Fig. 33.
COMPRESSOR ONLY
BALANCE
POINT
30
FOSSIL FUEL ONLY
M22441
Fig. 33. Dual Fuel Heat Pump Operation in Heat mode with
Balance Point Set.
OPERATION IN HEAT MODE BELOW BALANCE POINT (OUTDOOR
TEMPERATURE)
When the outdoor temperature is below the selected Balance
Point Temperature (ISU 0350), only the Fossil Fuel (auxiliary
heat) operates and the fan (G terminal) does not energize
when the thermostat calls for heat.
TO C
EQUIPMENT
MONITOR
L
4.
5.
The dehumidification control attempts to control to the user's
humidity setpoint by turning on the air conditioner. In
extremely high humidity conditions, the thermostat keeps the
air conditioner running (energizing Y and G) for up to 3°F
below the temperature setpoint. It does this while trying to
achieve the desired humidity setpoint and balancing that with
the temperature setpoint. The thermostat controls up to 3° F
below the temperature setting until either the humidity is
satisfied or conditions change.
C
3.
Choose correct heat pump application in Installer Setup
Number 0170.
Choose Fossil Fuel Option as the backup heat source
in Installer Setup Number 0200.
Choose No External Fossil Fuel Kit Option is controlling back up heat in Installer Setup Number 0210.
Choose Outdoor Temperature Sensor for Heat Pump
Temperature Lockouts Option in Installer Setup Number 0340.
Choose appropriate Balance Point Temperature in
Installer Setup Number 0350.
OUTDOOR TEMPERATURE
DONE
TO R
M19907
Fig. 32. L terminal switch to R (power) side of system
transformer.
33
68-0280—01
OPERATION IN EMERGENCY HEAT MODE
The balance point (outside) temperature is not used in the
Emergency heat mode. When the thermostat is moved to the
Emergency Heat position, the compressor is locked out. The
first stage of heat is whatever is connected to the E terminal.
The second stage of heat is what is connected to the Aux.
terminal. Often there is only one source of non-compressor
heat and the E terminal is jumped to the Aux. terminal.
Heat Pump with Electric Auxiliary (Backup) Heat and
Outdoor Temperature Sensor
1.
2.
3.
4.
5.
Choose correct heat pump application in Installer Setup
Number 0170.
Choose Electric as Auxiliary (Backup) Heat Source in
Installer Setup Number 0200.
Choose Outdoor Temperature Sensor for
Control Option in Installer Setup Number 0340.
Choose Compressor Lockout Temperature in
Installer Setup Number 0350.
Choose Auxiliary Lockout Temperature in Installer
Setup Number 0360.
NOTE: There is a 5°F deadband between the Compressor
and Auxiliary Heat Lockout Temperatures.
Operation in Heat Mode
When the outdoor temperature is below the Compressor
Lockout Temperature, only the Auxiliary Heat operates.
OUTDOOR TEMPERATURE
VisionPROTM 8000 Touchscreen Programmable Thermostat
COMPRESSOR ONLY
AUXILIARY
LOCKOUT
TEMPERATURE
50
BOTH COMPRESSOR AND
AUXILIARY HEAT
COMPRESSOR
LOCKOUT
TEMPERATURE
35
AUXILIARY ONLY
M19950
Fig. 34. Heat Pump Operation with Lockout
Temperatures Set.
When the outdoor temperature is between the two
temperatures, both the Compressor and Auxiliary Heat
operate.
Operation in Emergency Heat Mode
Once the thermostat is placed into the Emergency Heat
mode, the compressor and auxiliary lockout features are
turned off. In the Emergency heat mode, the compressor is
locked out. The first stage of heat is whatever is connected to
the E terminal. The second stage of heat is connected to the
Aux. terminal. Usually the emergency and auxiliary heat
sources are electric strip heat in these cases.
Operating Sequence
When the outdoor temperature is above the Auxiliary Lockout
Temperature, only the Compressor operates. See Fig. 34.
The thermostat energizes specific terminal(s), depending on
the demand for heating, cooling or fan. The thermostat screen
shows the time, inside temperature, system and fan
selections. Additional indicators are shown when the heating,
cooling or fan is energized. See Tables 9 - 11 for specification
information.
Table 9. Sequence of Operation for Conventional Systems.
System Setting
Fan Setting
Call for Action
Energize Terminals
Screen Message
Off
Auto
None
None
None
Cool
Auto
None
None
None
Cool or Auto
Auto
Stage 1 Cooling
Y, G
Cool On
Cool or Auto
Auto
Stage 1 and Stage 2 Cooling
Y, Y2b, G
Cool On
Heat
Auto
None
None
None
Heat or Auto
Auto
Stage 1 Heating
W, Ga
Heat On
Heat or Auto
Auto
Stage 1 and Stage 2 Heating
W, W2c, Ga
Heat On
aG
energizes only if Installer Setup number 0180 is set to Electric.
Installer Setup System type is set to two stages of cooling.
cIf Installer Setup System type is set to two stages of heating.
bIf
68-0280—01
34
VisionPROTM 8000 Touchscreen Programmable Thermostat
Table 10. Sequence of Operation for Power Open and Power Closed Valves or Normally Open Valves.
System Setting
Fan Setting
Call for Action
Energize Terminals
Screen message
Off
N/A
None
Y
None
Heat
N/A
None
Y
None
Heat
N/A
Heat
W
Heat On
Table 11. Sequence of Operation for Heat Pump Systems.
System Setting
Fan Setting
Call for Action
Energize Terminals
Screen message
Off
Auto
None
O/Ba
None
Cool
Auto
None
O/Ba
None
Cool or Auto
Auto
Stage 1 Cooling
Y, G, O/Ba
Cool On
Cool or Auto
Auto
Stage 1 and Stage 2 Cooling
Y, Y2d, G, O/Ba
Cool On
Heat
Auto
None
O/Ba
None
Heat or Auto
Auto
Stage 1 Heating
Y, G, O/Ba
Heat On
Heat or Auto
Auto
Stage 1 and Stage 2 Heating
Y, AUXc, G, O/Ba
Aux Heat On
Heat or Auto
Auto
Stage 1, 2 and 3 Heating
Y, Y2d, AUXe, G, O/Ba
Aux Heat On
Em. Heat
Auto
None
Lb, O/Ba
None
Em. Heat
Auto
Stage 1 Heating
E, G, Lb, O/Ba
Heat On
Em. Heat
Auto
Stage 1 and Stage 2 Heating
E, AUX, G, Lb, O/Ba
Aux. Heat On
aConfigure
O/B in Installer Setup. Based on last piece of equipment called (cooling = O or heating = B).
Red LED is on. See LED Indication section for more details.
c
If Installer Setup System Type is set to 2Heat/1Cool Heat Pump with Auxiliary Heat.
d
If Installer Setup System Type is set to 3Heat/2Cool Heat Pump with Auxiliary Heat.
eThis terminal does not energize if Installer Setup System type is set to 2 Heat/2 Cool Heat Pump with no Auxiliary Heat.
b
Second Stage Heat and Cool Control
While maintaining setpoint, several factors affect when 2nd
stage energizes such as load conditions, environmental
conditions, P+I control, and home insulation. The second
stage energizes when the thermostat senses 1st stage is
running at 90% capacity. This operation is droopless control.
35
68-0280—01
VisionPROTM 8000 Touchscreen Programmable Thermostat
C7089U Outdoor Temperature Sensor
Table 12. Sensor Resistance at Outdoor Temperature.
Operation
When installed with Thermostat Installer Setup Number 0340
set to 1 or 2, the outside temperature can be displayed on the
thermostat. See Fig. 35.
MON
FAN
TUE
WED
THU
Inside
FRI
SAT
AT
SUN
Set To
AUTO
SYSTEM
HEAT
HOLD
CLOCK
°F
°C
°F
°C
Ohms of
Resistance
-20
-28.9
106926
52
11.1
17136
-18
-27.8
100923
54
12.2
16387
-16
-26.7
95310
56
13.3
15675
-14
-25.6
90058
58
14.4
14999
-12
-24.4
85124
60
15.6
14356
-10
-23.3
80485
62
16.7
13743
-8
-22.2
76137
64
17.8
13161
Outside
-6
-21.1
72060
66
18.9
12607
-4
-20.0
68237
68
20.0
12081
SCREEN
MORE
M22453
Fig. 35. Outside temperature reading on
TH8000 Series Thermostat.
The C7089 Outdoor Sensor converts outdoor ambient
temperature to a resistance that the thermostat can interpret.
The C7089 has a negative temperature coefficient (TC), which
means that resistance decreases as the temperature
increases. See Table 12.
Checkout
Allow C7089U Outdoor Sensor to absorb outdoor air for a
minimum of twenty minutes before taking a reading.
With an accurate thermometer (±1°F [0.5°C]) measure the
temperature at the sensor location, allowing time for the
thermometer to stabilize before reading.
To verify sensor resistance, remove one wire from one of the
C7089 60-in. leadwires. Use an ohmmeter to measure the
resistance across the sensor. Then verify the sensor accuracy
with the temperature/resistance in Table 12.
Calibration
The C7089 Outdoor Sensor is calibrated at the factory and
cannot be recalibrated in the field.
68-0280—01
Outdoor
Temperature
Ohms of
Resistance
Following
Schedule
AM
SCHED
Outdoor
Temperature
36
-2
-18.9
64631
70
21.1
11578
0
-17.8
61246
72
22.2
11100
2
-16.7
58066
74
23.3
10644
4
-15.6
55077
76
24.4
10210
6
-14.4
53358
78
25.6
9795
8
-13.3
49598
80
26.7
9398
10
-12.2
47092
82
27.8
9020
12
-11.1
44732
84
28.9
8659
14
-10.0
42506
86
30.0
8315
16
-8.9
40394
88
31.1
7986
18
-7.8
38400
90
32.2
7672
20
-6.7
36519
92
33.3
7372
22
-5.6
34743
94
34.4
7086
24
-4.4
33063
96
35.6
6813
26
-3.3
31475
98
36.7
6551
28
-2.2
29975
100
37.8
6301
30
-1.1
28558
102
38.9
6062
32
0.0
27219
104
40.0
5834
34
1.1
25949
106
41.1
5614
36
2.2
24749
108
42.2
5404
38
3.3
23613
110
43.3
5203
40
4.4
22537
112
44.4
5010
42
5.6
21516
114
45.6
4826
44
6.7
20546
116
46.7
4649
46
7.8
19626
118
47.8
4479
48
8.9
18754
120
48.9
4317
50
10.0
17926
—
VisionPROTM 8000 Touchscreen Programmable Thermostat
C7189U Remote Indoor Temperature Sensor
Operation
When installed with Thermostat Installer Setup Number 0340
set to 3, the remote inside temperature is displayed on the
Thermostat Home Screen as Inside Temperature. The
thermostat internal temperature sensor is not used. See Fig.
36.
MON
FAN
TUE
WED
THU
Inside
FRI
SAT
AT
Calibration
The C7189 Wall Mount Temperature Sensor is calibrated at
the factory and cannot be recalibrated in the field.
Table 13. Sensor Resistance at Room Temperature.
SUN
Room
Temperature
Set To
AUTO
To verify sensor resistance, remove one wire from one of
C7189 wiring terminals. Use an ohmmeter to measure the
resistance across the sensor. Then verify the sensor accuracy
with the temperature/resistance in Table 13.
Heat On
22537
72
22.2
11100
5.6
21516
74
23.3
10644
44
6.7
20546
76
24.4
10210
46
7.8
19626
78
25.6
9795
48
8.9
18754
80
26.7
9398
50
10.0
17926
82
27.8
9020
The C7189 Wall Mount Temperature Sensor converts room
temperature to a resistance that the thermostat can interpret.
52
11.1
17136
84
28.9
8659
54
12.2
16387
86
30.0
8315
The C7189 has a negative temperature coefficient (NTC),
which means that resistance decreases as the temperature
increases. See Table 13.
56
13.3
15675
88
31.1
7986
58
14.4
14999
90
32.2
7672
The C7189 can be used to provide one remote sensor input
(see Fig. 28) or as a temperature averaging network with
multiple C7189 Sensors connected, as shown in Fig. 29.
60
15.6
14356
92
33.3
7372
62
16.7
13743
94
34.4
7086
Checkout
64
17.8
13161
96
35.6
6813
For best results, allow C7189 Wall Mount Temperature Sensor
to absorb the air moving through the room for a minimum of
twenty minutes before taking a resistance measurement.
66
18.9
12607
98
36.7
6551
68
20.0
12081
100
37.8
6301
With an accurate thermometer (±1°F [0.5°C]) measure the
temperature at the sensor location, allowing time for the
thermometer to stabilize before reading.
70
21.1
11578
HEAT
40
4.4
42
Ohms
of
Resistance
°C
SYSTEM
°C
Room
Temperature
°F
Following
Schedule
°F
Ohms
of
Resistance
AM
SCHED
HOLD
CLOCK
SCREEN
MORE
M19974
Fig. 36. Inside temperature reading on
TH8000 Series Thermostat.
37
—
68-0280—01
VisionPROTM 8000 Touchscreen Programmable Thermostat
TROUBLESHOOTING (TABLE 14)
Table 14. Troubleshooting.
Symptom
Possible Cause
Action
Display does not come on.
Thermostat is not being powered.
Check for 24 Vac between C and Rc.
Check that AAA batteries are installed
correctly and are good.
Temperature settings do not
change.
The upper or lower temperature limits
were reached.
Check temperature setpoints.
Check Installer Setup Numbers 0600 and
0610; modify as needed.
The keypad is fully locked.
Check Installer Setup Number 0670 to
change keypad locked options.
Thermostat minimum off-time is
activated.
Wait up to five minutes for the system to
respond.
System selection is not set to Heat or
Cool.
Set system Selection to correct position.
System type Selection is incorrect.
Check Installer Setup Number 0170 and
make sure correct System type is chosen.
Heating or cooling does not
come on.
Thermostat is calling for Heat Heating or cooling equipment is not
(Heat on) or Cool (Cool on) but operating.
no heating or cooling is
running.
Check wiring.
Check Installer Setup Number 0170 and
make sure correct system type is chosen.
Verify operation of equipment in System Test
mode.
Heat does not turn on (Heat
On is solid in the display).
Check for 24 Vac at the equipment on the
secondary side of the transformer between
power and common. If voltage is not present,
check the heating equipment to find the cause
of the problem.
Heating equipment failure.
Check for 24 Vac between the heat terminal
(W) and transformer common. If 24 Vac is
present, the thermostat is functional. Check
the heating equipment to find the cause of the
problem.
Loose or broken wire connection
between thermostat and heating
equipment.
Cooling does not turn on (Cool Cooling equipment failure.
On is solid in the display).
Check for 24 Vac between the heat terminal
(W) and transformer common. If voltage is not
present, check wire connection (loose or
broken) between the thermostat and the
heating equipment.
Check for 24 Vac at the equipment on the
secondary side of the transformer between
power and common. If voltage is not present,
check the cooling equipment to find the cause
of the problem.
Check for 24 Vac between the cool terminal
(Y) and transformer common. If 24 Vac is
present, the thermostat is functional. Check
the cooling equipment to find the cause of the
problem.
Fan does not turn on in a call
for heat (electric furnace).
68-0280—01
Loose or broken wire connection
between thermostat and cooling
equipment.
Check for 24 Vac between the cool terminal
(Y) and transformer common. If voltage is not
present, check the wire connection (loose or
broken) between the thermostat and the
cooling equipment.
Fan Control in Heating is set to Gas or
Oil Furnace (Setting 0180).
Set Fan Control in Heating to Electric Furnace
(Setting 0180).
38
VisionPROTM 8000 Touchscreen Programmable Thermostat
Table 14. Troubleshooting. (Continued)
Symptom
Possible Cause
Heat pump puts out cool air in Changeover Valve (Installer Setup
the heat mode and warm air in Number 0190) is not configured to
the cool mode.
match the changeover required by the
installed heat pump.
Action
Set Changeover Valve (Installer Setup
Number 0190) to match the changeover
required by the installed heat pump.
The heating equipment is not a heat
pump but the System Type (Installer
Setup Number 0170) is set to Heat
Pump.
Set System Type (Installer Setup Number
0170) to match the installed heating and/or
cooling equipment.
Heating and cooling wires are shorted
together.
Separate the shorted heating and cooling
wires.
Heating equipment is not a heat pump
but System Type (Installer Setup
Number 0170) is set to Heat Pump.
Set System Type (Installer Setup Number
0170) to match the installed heating and/or
cooling equipment.
Heating equipment is not a heat pump
Heating equipment does not
turn off and heat temperature but System Type (Installer Setup
Number 0170) is set to Heat Pump.
setting is set below room
temperature (Heat On is not in
the display).
Set System Type (Installer Setup Number
0170) to match the installed heating and/or
cooling equipment.
Cannot set the system setting System Type (Installer Setup Number
to Heat.
0170) is set to Cool Only.
Set System Type (Installer Setup Number
0170) to match the installed heating and/or
cooling equipment.
Cannot set the system setting System Type (Installer Setup Number
to Cool.
0170) is set to Heat Only or Heat Only
with Fan.
Set System Type (Installer Setup Number
0170) to match the installed heating and/or
cooling equipment.
Both the heating and cooling
equipment are running at the
same time.
Heating equipment is running
in the cool mode.
Heat On is not in the display.
System setting is not set to Heat and/or Set the system setting to Heat and set the
temperature setting above the room
temperature setting is not set above
temperature.
room temperature.
Cool On is not in the display.
System setting is not set to Cool and/or Set the system setting to Cool and set the
the temperature setting is not set below temperature setting below the room
room temperature.
temperature.
Wait is in the display.
Compressor minimum off timer is
active.
Wait up to five minutes for the cooling or
heating (heat pump) equipment to turn on.
“Screen Locked” appears on
the screen and all or some of
the keys do not respond.
The keypad is fully or partially locked.
Check Installer Setup Number 0670 to
change keypad locked options.
39
68-0280—01
VisionPROTM 8000 Touchscreen Programmable Thermostat
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
68-0280—01
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Toronto, Ontario
M1V 4Z9
M.S. Rev. 03-11
Printed in U.S.A.
www.honeywell.com/yourhome