Technical Specifications Template

Transcription

Technical Specifications Template
Mackay Entertainment and
Convention Centre
Technical Specifications
Updated
7/1/2013
Technical Services Coordinator:
Phone number:
Mobile:
Fax number:
Email address:
07 4961 9711
0418 617 657
07 4961 9778
[email protected]
Production Services Coordinator:
Phone number:
Mobile:
Fax number:
Email address:
Corby Stuart
Catherine Batterson
07 4961 9715
0418 794 417
07 4961 9778
[email protected]
Venue:
Phone number: 07 4961 9700
Fax number:
07 4961 9778
Website:
www.mackayentertainment.com.au
Venue address: Corner Alfred & Macalister Streets
Postal address: PO Box 41, Mackay, Queensland, 4740.
Additional contact details are located on the final page
Generated from the APACA Technical Specifications Template. For more details visit www.apaca.com.au
MECC Technical Specifications - APACA - Updated 7 1 13
STAGING
Brief Stage Description:
Unraked stage with a proscenium arch and flying facilities. Stage construction is,
tongue & groove pine over hardwood bearers sheeted with Masonite. Screwing into
surface permitted but larger holes to be authorised by the Technical Services
Coordinator or Head of Staging. Stage crossover behind US fly line.
Stage distributed load limit
750kg/m2
Stage point load limit
450kg
Stage rake
Nil
Stage Dimensions:
Proscenium
Width 12 metres
Height variable between 5 & 7 metres
Setting Line
2.4 metres from DS edge of stage to rear of House Curtain
Distance From (SL = Setting Line, CL = Centre Line)
SL to DS edge of apron
2.4 metres
SL to DS edge of Orchestra Lift/Pit
6.1 metres
SL to first fly line
200 mm
SL to last upstage fly line
9.95 metres
SL to rear wall
11.5 metres
CL to OP wall (or obstruction)
12.5 metres
CL to PS wall (or obstruction)
11.3 metres
Stage to underside of grid
17.8 metres
Overhead Obstructions
PS & OP Fly gallery to stage floor
7.45 metres
Auditorium:
Auditorium is stalls only
Seating capacity with additional
Orchestra lift/pit seating installed
Seating capacity without
Orchestra lift/pit seating installed
1090
1036
(16 Auditorium seats are removable to accommodate 4 x wheelchairs if required)
Orchestra Lift / Pit:
Electric screw-jack operated orchestra lift
Set positions for orchestra lift where lift at auditorium level is 0mm
Stage level at 1.0 metre above auditorium.
Orchestra pit level at 2.75 metres below auditorium.
Lift can be set at any height
YES
SWL of orchestra lift
750kg/m2
Dimensions of the orchestra pit
Orchestra pit is 12 metres wide x 3.7 metres
deep at Centre stage, with a convex front edge
Orchestra pit maximum capacity
30 persons
2
MECC Technical Specifications - APACA - Updated 7 1 13
Flying Facilities:
Fly System
Single purchase counter weight fly system.
Fly System Details
Operating Position
Total number of Lines
Panorama Lines
Batten Drift
Batten Type
Batten Length
Batten Extensions
Batten Pick-ups
intervals
Batten Point Load
Batten W.L.L.
Cradle Capacity
LX bars
LX bars can be swung
Fly bars can be swung
PS at Stage level
51 + House Curtain
2 - 1 bar PS; 1 bar OP
17 metres
48.5mm O/D pipe & 75mm x 50mm RHS
16.4 metres
N/A
(5) Pick-ups, (1) at Centre then others at approximately 3m
144 kg
720 kg
450 kg
600 kg
YES (with difficulty)
YES
SEE HANGING PLOT FOR LINE ALLOCATIONS AND FURTHER INFO
Hanging Plot:
Line Type: SP = Single purchase
W.L.L.: Maximum distributed load including bar weight
Mackay Hanging Plot: as at 3/5/2012
Line #
H/C
1
2
3
4
5
6
8
10
11
12
13
14
15
16
17
19
21
22
23
24
25
26
27
Distance from
rear of prosc.
0.46m
0.74m
0.89m
1.04m
1.19m
1.34m
1.49m
1.79m
2.09m
2.24m
2.39m
2.54m
2.69m
2.84m
2.99m
3.14m
3.44m
3.74m
3.89m
4.34m
4.49m
4.64m
4.79m
4.94m
Type
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
W.L.L
Venue Allocation
400kg
450kg
450kg
450kg
450kg
450kg
600kg
450kg
450kg
450kg
450kg
450kg
450kg
450kg
450kg
450kg
600kg
450kg
450kg
450kg
450kg
450kg
450kg
450kg
House Curtain
Intended Use
Border
Leg
LX 1
AV Screen
Border
Leg
¼ stage Tab
LX 2
Border
Leg
3
MECC Technical Specifications - APACA - Updated 7 1 13
28
29
30
31
32
33
34
35
36
37
38
39
41
43
44
45
46
47
48
49
50
51
53
55
57
58
59
60
61
62
63
64
5.09m
5.24m
5.39m
5.54m
5.69m
5.84m
5.99m
6.14m
6.29m
6.44m
6.59m
6.74m
7.04m
7.34m
7.49m
7.64m
7.79m
7.94m
8.09m
8.24m
8.69m
8.84m
9.14m
9.44m
9.74m
9.89m
10.04m
10.19m
10.34m
10.49m
10.64m
10.79m
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
450kg
450kg
450kg
450kg
450kg
450kg
450kg
450kg
450kg
450kg
450kg
450kg
600kg
450kg
450kg
450kg
450kg
450kg
450kg
450kg
450kg
450kg
450kg
450kg
450kg
450kg
450kg
450kg
450kg
450kg
450kg
450kg
½ stage Tab
Border
Leg
LX 3
¾ stage Tab
Border
Leg
LX 4
Flood Bar
Tab
New Cyc
O.P. Panorama bar
P.S. Panorama bar
4
MECC Technical Specifications - APACA - Updated 7 1 13
Drapery:
*Type
Material
Colour
House Curtain
Borders
Legs
Tabs / Smother
Cyclorama (old)
Cyclorama (new)
Scrim
Velour
Wool, 100% fullness
Wool, 100% fullness
Wool, 100% fullness
Star Cloth
Tab
ILED ROBW Wool
Wool Flat
Crimson
Black
Black
Black
(off) White
White
Black
White
Black
Black
Sharks tooth gauze
Width
4m
4m
Height
6m
7m
Quan
tity
1
5
5
4
1
1
2
2
4
14
Materials Handling:
Komatsu Electric Forklift FB20A-12
Rated Capacity 2000kg
2 x Hand Pallet Trucks
Rated Capacity 2500kg
2 x Hand Pallet Trucks (Narrow)
Rated Capacity 1500kg
Height Access Equipment:
Elevated Work Platforms
JLG Electric Scissor Lift 3246 ES
Platform Height - 9.68 metres
Working Height - 11.68 metres
Genie Electric Scissor Lift GS-2032
Platform Height - 6.1 metres
Working Height - 8.1 metres
JLG Electric Mast Lift 20MVL - Drivable
Platform Height - 5.94 metres
Working Height - 7.77 metres
Genie Electric Mast Lift AWP-30S - Push around
Platform Height - 9 metres
Working Height - 10.8 metres
Restrictions - outriggers must be used at all times, one staff member to be located at base whilst in use.
Ladders
Aluminium Tallescope -7.2 metres
Fibreglass Double Sided ‘A’ Frame, 3.6 metres
5
MECC Technical Specifications - APACA - Updated 7 1 13
Fibreglass Single Sided (dual), ‘A’ Frame - 2.4 metres, Straight – 4.4 metres
Fibreglass Double Sided ‘A’ Frame, 1.8 metres
Fibreglass Double Sided ‘A’ Frame, .5 metres
Staging Units:
Plenary Halls A & B
Sico Fold and Set (Can be set heights from 910mm to 1370mm)
56 x dual sided decks (black carpet one side/ tuff deck other) 2.4m x 1.2m
12 x Frame Units
7 x 2.4m Hand Rails
2 x 1.2m Hand Rails
4 x 7 Step Stair Units
Masking for 3 sides of full stage
Sico Tri-Height stage (Meeting Room Stage)
2 x Stage Units 2.4m x 1.8m (460mm, 610mm, 760mm heights)
4 x 4 Step Stair Unit
Masking for all 4 sides
Disabled Stage access
Ascension Wheelchair lift
North Foyer Stage
10 x Prostage folding leg unit 2m x 1m (heights 600m to 900mm)
5 x Prostage bridging unit
Masking and treads to suit
(Positioned in corner of room, stage is triangle in shape)
Additional Staging:
Rider Units
20 x Prolyte Stagedex unit 2m x 1m
36 x 300mm Legs
36 x 450mm Legs
36 x 750mm Legs
24 x Adjustable Legs 900mm x 1400mm
52 x 1200mm Legs
Rostra Bases
14 x Timber Rostra - 2m x 1m x 0.75m
4 x Timber Rostra - 2m x 1m x 0.45m
4 x Timber Rostra - 2m x 1m x 0.30m
32 x Timber Rostra - 2m x 1m x 0.09m
2 x Timber Rostra - 1m x 1m x 0.75m
8 x Timber Rostra - Triangle Section - 1m x 1m x 0.75m
Rostra Tops
25 x Varnished 2m x 1m
20 x Black 2m x 1m
2 x Black 1m x 1m
8 x Triangle Black 1m x 1m
6
MECC Technical Specifications - APACA - Updated 7 1 13
Rigging:
Chain hoists
16 x Prolyft 1t Chain Hoists (15m Chain)
4 x Prolyft 1t Chain Hoists (20m Chain)
Truss
16 x 2m Prolyte S36R Box Truss
16 x 3m Prolyte S36R Box Truss
12 x S36R 6-Way Box Corner
9 x 1.5m Prolyte H30 Ladder Truss
Load Monitoring
10 Channel load cell system
Assorted Rigging
500kg, 750kg, 1t, 2t, 3.25t and 4.75t Shackles
2t Black Slings
Snotter Straps
Loading Docks:
Access
Vehicle access to docks from Macalister St
Main Auditorium - Loading Dock Height
External Door Dimensions
Internal Door Dimensions
Convention Centre – Flat Floor
External Door Dimensions
Internal Door Dimensions
0.6 metres
6.0 metres high
3.6 metres wide
5.7 metres high
2.8 metres wide
5.3 metres high
5.8 metres wide
5.9 metres high
5.9 metres wide
7
MECC Technical Specifications - APACA - Updated 7 1 13
LIGHTING - Auditorium
Positions:
See hanging plot for standard LX bar locations
FOH Bridge #1
Setting Line to lighting bar
Usable bar width
FOH Bridge #2
Setting Line to lighting bar
Usable bar width
FOH Bridge #3
Setting Line to lighting bar
Usable bar width
FOH ‘Rose’ Bar
Setting Line to lighting bar
Usable bar width
FOH Perches (PS & OP)
Setting Line to FOH Perch
9.5 metres @ 60o
12 metres
15 metres @ 45o
12 metres
19 metres @ 30o
12 metres
28 metres @ 10o
6 metres
13 metres @ 60o (two per side)
Distances are to the highest downstage point of boom or perch.
Maximum lanterns per perch
3 x 1kW profiles
.
FOH Booms (PS & OP)
Setting Line to FOH Boom
7.5 metres@ 45o
Distances are to the highest downstage point of boom or perch.
Maximum lanterns per boom
4 x 1kW profiles
Control:
Lighting desk
Signal distribution
Grand MA 2 Light
Two streams of DMX to dimmer room, then distributed to
various points around stage, bridges and galleries
Dimmer Racks:
Dimmer Locations
20A Dimmer Racks
12A Dimmer Racks
Dimmer room located off OP box boom position
134x LSC EKO (installed)
2x 12way JANDS HP-12 (free standing)
House Lights:
Control
Control Positions
Fade time adjustable
Dynalite system at listed locations, and LX desk
Control room, Prompt corner, SM console, rear of
auditorium (FX position).
From LX desk only
Stage Luminaries:
Profiles
Make
Model
Selecon
ETC
ETC
Selecon
Selecon
Pacific
Source 4
Source 4
Narrow Zoom
Medium Zoom
Angle
12o-28o
15o-30o
26o
8o-16o
12o-28o
Detail / Accessories
Watt
Total
1000
750
575
1200
1200
35
30
12
4
14
8
MECC Technical Specifications - APACA - Updated 7 1 13
Fresnels
Make
Model
Detail / Accessories
Watt
Total
Selecon
Arena
Barn doors
2000
36
Par Cans
Make
Model
Angle
Par 64
Par 64
120 Volt
240 Volt
MFL
MFL
Detail / Accessories
Watt
Total
1000
1000
18
8
Wash
Make
Model
Detail / Accessories
Watt
Total
CCT
Strand
Starlette
Orion
4 compartment (cyc flood)
4 compartment (ground row)
1000
1000
5
5
Make
Model
Control
Channels
Watt
Total
NeoNeon /
Genie
OBY 5
575
5
Detail / Accessories
Watt
Total
6 colour magazine; MSD
lamp
1200
2
Watt
Total
Movers
Detail / Accessories
16
Follow spots
Make
Model
Angle
Robert Juliet
Topaz
7-14.5o
Additional Lighting
Item
Mirror Ball
UV 400
Strobe
Smoke machine
Hazer
Haze maker
Gobo rotator
DMX Fan
Make
Model
Detail / Accessories
36in diameter ball with motor
Data Flash
Martin Gem
Unique2
Nebula
Vortex 360
Martin
AF1000 HO1 high output lamps
ZR44
AF-1
1
2
4
2
1
1
4
2
9
MECC Technical Specifications - APACA - Updated 7 1 13
Patching:
Location
Quantity
Numbering
Detail / Accessories
(PS to OP)
FOH Bridge 3
FOH Bridge 2
FOH Bridge 1
Perch 3 PS
Perch 3 OP
Perch 2 PS
Perch 2 OP
Perch 1 PS
Perch 1 OP
OP Fly Floor
PS Fly Floor
PS diptrap DS
PS diptrap MS
PS diptrap US
OP diptrap DS
OP diptrap MS
OP diptrap US
Orchestra Pit dips
20
30
30
8
8
8
8
12
12
14
20
10
10
10
10
5
5
10
5
5
5
5
5
5
5
5
2
2
1 - 20
21 - 50
51 - 80
81 - 88
89 - 96
97 - 104
105 -112
113 - 120, 284 - 287
121 - 128, 288 - 291
129 - 148
161 - 180
181 - 190
191 - 200
201 - 210
231 - 240
241 - 245
246 - 250
211 - 220
221 - 225
226 - 230
251 - 255
256 - 260
261 - 265
266 - 270
271 - 275
276 - 280
292, 293
294, 295
18, 19, 20 are 20amp
48, 49, 50 are 20amp
78, 79, 80 are 20amp
81, 82 are 20amp
89, 90 are 20amp
97, 98 are 20amp
105, 106 are 20amp
113, 114, 284, 285 are 20amp
121, 122, 288, 289 are 20amp
129, 130, 131, 132 are 20amp
161, 162, 163, 164 are 20amp
181, 182 are 20amp
191, 192 are 20amp
201, 202, 203, 204 are 20amp
231, 232 are 20amp
241, 242 are 20amp
246, 247 are 20amp
211, 212 are 20amp
221, 222 are 20amp
226, 227 are 20amp
251, 252 are 20amp
256, 257 are 20amp
261, 262 are 20amp
266, 267 are 20amp
271, 272 are 20amp
276, 277 are 20amp
Power:
3 Phase Outlets
Midstage O/P - 3 x 32A Wilco outlets, or 1 x 160A / leg available for hard wiring
Prompt Corner - 1 x 32A Wilco outlet
Workshop - 2 x 32A Wilco outlets (15 metres from US OP)
Rear Auditorium - 1 x 32A Wilco outlet
Dimmer Room - 6 x 32A Wilco outlets
Cabling:
240v Extension Cable
The theatre has a good stock of extension leads to accommodate the venue’s
standard lighting rig.
Looms
4 x 6 way 20 metre Socapex looms
2 x 6 way 15 metre Socapex looms
2 x 6 way 10 metre Socapex looms
6 x 6 cct Headers
6 x 6 cct Tails,
10
MECC Technical Specifications - APACA - Updated 7 1 13
4 x 6 cct Spot bar sections
3 phase Extensions
6 x 32A Wilco 3 phase extensions (various lengths)
LIGHTING – Convention Centre
Profiles
Make
Model
Selecon
Pacific
Angle
Detail / Accessories
Watt
Total
14o-35o
80 volt DMX units
1200
14
Detail / Accessories
Par Cans
Make
Model
Angle
Par 64
120 Volt
MFL
Watt
Total
1000
15
Watt
Total
Wash
Make
Model
Detail / Accessories
Honeycomb
Honeycomb 72
LED wash bar RGB 6 channel
Make
Model
Control
Channels
Studio Due
Shark 250
7
Movers
Detail / Accessories
Watt
Total
250
12
Detail / Accessories
Watt
Total
6 colour magazine
1200
1
13
Follow spot
Make
Model
Robert Juliet
Topaze
Angle
Control:
Lighting desk
Signal distribution
Other
Grand MA Ultra Light
Fully patchable DMX distribution system to any point in
the halls
Jands DD8 DMX splitter
ETC Smartfade ML (2)
Dimmer Racks:
8 x LSC Epro/T 12 channel dimmer racks, 40A 3 phase connectors
Power Distribution:
1 x Jands 400A Powerlock 3 phase distribution board
3 x Powerwise 32A 3 phase to 12 GPO
Rigging:
10 x Jands JLX PRO1 lighting bars
10 x 20m 6 cct Socapex multicore looms
OTHER LANTERNS (used in other small venues in the complex)
Make
Model
Detail / Accessories
Watt
Total
Strand
Strand
Harmony
Cantata
Barn doors
Barn doors
1000
1200
4
10
11
MECC Technical Specifications - APACA - Updated 7 1 13
AUDIO
Control Positions:
Auditorium
Located in centre of rows X,Y,& Z at rear of stalls
Plenary Halls A & B
Where required
North Foyer
In front of bar facing stage, control booth
Other
Prompt Corner
Audio Consoles:
Primary
Auditorium
1 x Digico S - SD8
Plenary Halls A & B
1 x Digico S - SD8
North Foyer
1 x Digico SD8 - 24
Secondary
1 x Mackie CFX12 MKII
1 x Yamaha MG16/6
1 x Soundcraft MPM 12/2
System Processing:
Auditorium
2 x Nexo NX242ES4 TD Controller
1 x Xilica DLP-4080 Controller (Pit Fill)
Plenary Halls A & B
4 x Nexo NX242ES4 TD Controller
North Foyer
2 x Nexo NX242 TD Controller
Monitors
4 x Nexo PS15 UTD Controller
4 x Nexo PS10 UTD Controller
Floating PA
2 x Nexo GEO S12 UTD Controller
12
MECC Technical Specifications - APACA - Updated 7 1 13
EQ:
Auditorium
1 x Klark Teknik DN 9340 Helix (FOH)
Monitors
4 x Klark Teknik DN 360
FX:
1 x Lexicon MPX 1
1 x Yamaha REV 500
1 x Lexicon MPX 1
1 x Yamaha REV 500
1 x Yamaha SPX 990
Compression:
1 x DBX 1066 Stereo Compressor / Limiter / Gate
1 x DBX 1046 Quad Compressor / Limiter
1 x Drawmer MX40 Quad punchgate
1 x DBX 1066 Stereo Compressor / Limiter / Gate
1 x LA Audio TCX20 Dual tube compressor
3 x DBX 166XL Stereo Compressor / Limiter / Gate
Amplification:
Auditorium
4 x Camco Vortex 6
1 x Crown CE Series 1000 (Pit Fill)
Plenary Halls A & B
8 x Camco Vortex 6
North Foyer
1 x Camco Q Power 10
1 x Camco Techton 38.4
Floating system
2 x Camco Techton 38.4
Monitors
4 x Camco Q Power 10
2 x Crown CE Series 4000
Backup
2 x Camco Vortex 6
13
MECC Technical Specifications - APACA - Updated 7 1 13
Speakers:
FOH Speakers
Auditorium
Left
8 x Nexo GEO S1210
2 x Nexo GEO S1230
4 x Nexo RS15 Sub
Apron Fill
4 x JBL Marquis MS26
Side Fill
2 x Nexo GEO S1230
Plenary Halls A & B Combined
(System can be split to a 6 box, 2 sub / side, to service both halls)
24 x Nexo GEO S1210
2 x Nexo GEO S1230
8 x Nexo RS15 Sub
North Foyer
8 x Nexo GEO S805
2 x Nexo GEO S830
2 x Nexo CD 12 Sub
Floating System
2 x Nexo GEO S1230
Monitors
8 x Nexo PS10
8 x Nexo PS15 (Matched Pairs)
Other
2 x JBL EON G2 (Powered)
4 x JBL Control 1
Playback:
Item
Make
Model
CD Player
CD Player
CD Player
CD Player
CD Burner
Shortcut Editor
Minidisc
Denon
Denon
Denon
Denon
HHB
360 Systems
Sony
DNC 635
DN - C630
DN - 2000 F MkIII
DN - C635
CDR-882
SC-182
MDS - E12
Detail
Dual
Dual Burn
Total
2
2
1
2
1
1
1
14
MECC Technical Specifications - APACA - Updated 7 1 13
Microphones:
Make
Model
Detail / Accessories
Use
Shure
Shure
Shure
Shure
Countryman
DPA
DPA
Sennheiser
Sennheiser
Shure
Shure
Shure
Shure
Shure
Shure
Shure
Shure
Shure
Shure
Shure
AKG
AKG
AKG
AKG
AKG
Shure
Schertler
EV
Shure
Rode
EV
DPA
Beyer
LA Audio
LA Audio
SCV
ARX
Aust Monitor
Radial
Radial
Radial
EMO
UR4D+
U2 MA87
UR1
U2-MA Beta87
WCE6T
4088-F
4060
MK2
MK2 Gold
WL93
Beta 91
Beta 52
Beta 98 D/S
Beta 56
Beta 57
Beta 58A
Beta 87
SM 57
SM 58
PG48
CK91
C451 EB
C3000
D112
C568 EB
MX 418-S
DYN-GP
CT 30
MX391/0
NT5
RE90H
4021 (Pair)
M88
D12
D12 MKIII
D12 MKII
Audibox
AMIS-DI 1
PC MK3
PRO AV 1
PRO AV 2
Wireless systems
Antenna signal amplifier
Belt pack transmitters
Hand-held transmitters
Earset
Headset
Lapel Microphone
Lapel Microphone
Lapel Microphone
Lapel Microphone
Vocals
Switchable
Shotgun Microphone
Lectern Microphone
Electrodynamic Transducer
Boundary
Mini Boundary
Choir Microphone
Piano kit
Active DI
Active DI
Active DI
USB DI
Passive DI
Stereo DI
Passive DI
Piano / Bass
Total
8
2
16
10
27
6
6
2
6
2
2
1
4
3
2
12
2
14
3
2
2
2
1
1
4
8
2
1
1
6
2
2
2
2
4
3
4
1
1
2
1
2
Audio Cable:
The theatre has an extensive stock of microphone and speaker cable to accommodate
the venue’s own equipment.
15
MECC Technical Specifications - APACA - Updated 7 1 13
Multicore:
Auditorium
1 x DIGIRACK SD8 - RACK
48 Input
8 Return
P/S
32 Input stage box, splitable to FOH / MON
16 Input stage box
O/P
8 Input stage box
12 Return lines
Plenary Halls A & B
2 x DIGIRACK SD8 - RACK
48 Input
16 Return
2 x RME MADI Converter
2 x RME MADI Bridge
(Over fibre network)
(CAT 6 network also available)
North Foyer
1 x DIGIRACK SD8 - RACK
48 Input
8 Return
Other
1 x Klark Teknik 8 Channel Square One Active Splitter
Audio Power:
Auditorium
100A supply (1 x 32A Outlet Prompt and 1 x 32A outlet OP).
Plenary Halls A & B
400A supply Litton Veam Powerlock
North Foyer
32A supply
Distribution
1 x Jands PD453 (4 x 50A Outlets)
7 x Powerwise PD 620
1 x Jands PDS12R
16
MECC Technical Specifications - APACA - Updated 7 1 13
AUDIO VISUAL
Projection:
Auditorium
1 x Panasonic PT-DW5100E, 16:9 Native Aspect Ratio, 5100 ANSI Lumens (DLP)
Long throw lens ET-DLE310
(Projector rigged on ‘Rose’ bar at rear of Auditorium)
Plenary Halls
2 x Barco CLM HD8, 16:9 Native Aspect Ratio, 8500 ANSI Lumens (DLP)
1080i Resolution, DMX Control, HDSDI Input, Lens Throw Distance 27 metres.
Meeting Room 1
1 x Sanyo PLCXU115, 4:3 Native Aspect Ratio, 4000 ANSI Lumens
Meeting Room 2
1 x Sanyo PLCXU115, 4:3 Native Aspect Ratio, 4000 ANSI Lumens
Meeting Room 3
1 x Sanyo PLCXU88, 4:3 Native Aspect Ratio, 3000 ANSI Lumens
Meeting Room 4
1 x Sanyo PLCXU88, 4:3 Native Aspect Ratio, 3000 ANSI Lumens
North Foyer
1 x Sony VPL-PX40, 4:3 Native Aspect Ratio, 3500 ANSI Lumens (LCD)
Space
1 x Mitsubishi XD480U, 4:3 Native Aspect Ratio, 3000 ANSI Lumens (DLP)
Projection Screens:
Auditorium
1 x Draper Truss Cinefold 5.9 x 3.6 meter, 16:9 Aspect Ratio, Front Projection
Screen.
Plenary Halls
2 x Draper Truss Cinefold 6.4 x 3.8 metre, 16:9 Aspect Ratio, Front Projection
Screen.
Meeting Room 1
1 x Motorised 2.7 x 3.6 metre, 4:3 Aspect Ratio, Front Projection Screen.
Meeting Room 2
1 x Motorised 2.7 x 3.6 metre, 4:3 Aspect Ration, Front Projection Screen.
Meeting Room 3
1 x Motorised 2.3 x 3 metre, 4:3 Aspect Ratio, Front Projection Screen.
Meeting Room 4
1 x Motorised 2.3 x 3 metre, 4:3 Aspect Ratio, Front Projection Screen.
17
MECC Technical Specifications - APACA - Updated 7 1 13
North Foyer
1 x Motorised Luna 3.6 x 2.8 meters, 4:3 Aspect Ratio, Front Projection Screen..
Space
1 x Pull Down Gilkon 2.4 x 2.4 meter, 4:3 Aspect Ratio, Front Projection Screen.
Portable
1 x Push Up 2.4 x 2.4 meter, 4:3 Aspect Ratio, Front Projection Screen.
AV Playback:
Item
Make
Model
Detail
DVD Player
DVD Player
VCR
DVD Player
Denon
Denon
Sony
Sony
DV300
DNV310
SLV EZ70
DVP NS50P
Professional
Professional
HiFi
Domestic
Total
2
4
2
1
Vision Mixing / Switching:
2 x Kramer VP-724xl switcher / scaler
1 x Panasonic WJ AVE55 vision mixer
1 x Kramer VP-727/VP-727T, WXVGA/DVI Output
2 x Data Video TLM-702, Rack Mount LCD Preveiw Monitors
Display Panels:
Fixed Digital Signage
(All fixed screens and the mobile 52” NEC Portrait Mode panel have their own video servers running
Omnivex signage display software, unless otherwise indicated).
JPEG files formatted to 16x9 size to be provided by client for display monitor screens.
Plenary Hall A Entry
1 x NEC 3215 - BK, 32” LCD Panel
Plenary Hall B Entry
1 x NEC 3215 - BK, 32” LCD Panel
Meeting Room 1 & 2 Entry
1 x NEC 3215 - BK, 32” LCD Panel
Meeting Room 3 & 4 Entry
1 x NEC 3215 - BK, 32” LCD Panel
South Foyer Bar
1 x NEC 4620 – BK, 46” LCD Panel
South Foyer Registration
1 x NEC 4620 – BK, 46” LCD Panel
South Foyer Box Office
1 x NEC 4620 – BK, 46” LCD Panel
18
MECC Technical Specifications - APACA - Updated 7 1 13
Mobile Display Panels
4 x Sony Bravia LCD with Sony BlueRay players mounted on Stands with shelf for
Laptops
1 x Sanyo CE52LH1R, 52” LCD Panel
1 x NEC GXDL52H1, 52” LCD Panel (Portrait Mode)
Floating Equipment:
4 x Toshiba Laptop U500 VGA / HDMI out
2 x Panasonic UB2315C, Electronic White Boards
Cabling:
The theatre has a good stock of coaxial and VGA cable to accommodate the venue’s
own equipment.
BACKSTAGE
Stage Managers Console:
Stage Managers desk is located in prompt corner. The desk has limited movement
within this area and is fitted with Desk Lights
7”LCD Video Monitor
Lecturn Cue Light Control
Paging Mic
Telephone / Internet (ADSL)
Talkback Master Stations
Talkback:
Auditorium
Master Unit - 1 x Telex Audiocom MS 2002 (2 Channel)
Wireless Master Unit - 1 x Telex Radiocom BTR 700 (4 Channel)
9 x BP 1002 Belt Packs
1 x BP 2002 (2 channel)
4 x TR 700 Wireless Packs
14 x Telex PH100 Headsets
2 x Telex SS2002 Audiocom Squawk Box, (Control room / FOH Audio)
Talkback Patching Locations
SM Console
P/S Fly Rail
Prompt Corner D/S
OP D/S
Fly Galleries
Row L
FOH Mix Position
Control Room
FOH Bridge #3 Followspots (2)
19
MECC Technical Specifications - APACA - Updated 7 1 13
Plenary Halls
Master Unit - 2 x Telex Audiocom MS 2002 (2 Channel)
Wireless Master Unit - 1 x Telex Radiocom BTR 700 (4 Channel)
4 x BP 1002 Belt Packs
4 x TR 700 Wireless Packs
8 x Beyer DT108 Headsets
Paging / Show relay:
Backstage paging is available from the stage managers console.
Paging and show relay is distributed to all dressing rooms, backstage corridors,
studio space and green room.
Monitors:
Dressing Rooms, Green Room, Foyer, Auditorium Doors, SM Position, Prompt & O/P.
Camera located centre of the FOH ‘Rose’ Bar.
Dressing Rooms:
Dressing Room
Capacity
1
2
3
4
5
6
7
2
2
4
4
6
20-30
20-30
Toilets
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Shower
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Details
Attached to Space Theatre
Attached to Space Theatre
Upstairs
upstairs
Laundry / Wardrobe:
Washing Machines
Dryer
Drying Rooms
Iron / Ironing Board
Clothes Racks
1 x washing machine
1 x dryer
N/A
1 of each
1 or 2 per room
Production Facilities:
Production Desk
Production Desk set-up in centre of stalls (Row L) Table accommodates 4 people.
Talkback available.
Greenroom
Tea / Coffee Facilities
Fridge / Freezer
Microwave
Running Hot/Cold Water
YES
YES
YES
YES
Stage Door Access
Stage Door is located beside the loading dock on Macalister St.
Access during bump-in / out will be controlled by the Venue Supervisor.
20
MECC Technical Specifications - APACA - Updated 7 1 13
Additional Facilities & Information:
Orchestral
Steinway Concert Grand Model D (Auditorium only)
Beale BA 73 Parlour Grand (Foyer)
Yamaha WX5 Upright
Pailing Bros. Upright (Green Room)
Backline
1 x Fender Twin Reverb Combo Guitar Amplifier
1 x Hartke KM200 Keyboard Amplifier
1 x Ampeg SVTPROU, Bass Amp Head
1 x Ampeg SVT410HE, 4 x 10” Bass Speaker Cabinet
1 x Ampeg SVT15E, 1 x 15” Bass Speaker Cabinet
Staff Contacts:
Head of Audio / Visual
Phone Number:
Email Address:
James Loveless
07 4961 9710
[email protected]
Head of Lighting
Phone Number:
Email Address:
TBC
07 4961 9713
[email protected]
Head of Staging
Phone Number:
Email Address:
TBC
07 4961 9712
@mackay.qld.gov.au
Venue Supervisor
Phone Number:
07 4961 9716
Box Office & Administration Coordinator
Denise Holley
Phone Number:
07 4961 9749
Email Address:
[email protected]
Fax Number:
07 4961 9778
Venue Information:
The Mackay Entertainment & Convention Centre operates nine
performance/conference spaces. The main auditorium is a traditional theatre space
with seating for 1090 people. The studio Space has retractable seating for 100
people. The spacious North Foyer seats 350 theatre style and 300 around tables.
The Mackay Entertainment & Convention Centre is a business unit of Mackay
Regional Council.
21