1.
REFER TO SWITCH BANK DETAIL, DETAIL E2/DRAWING E1.0, FOR SWITCHING OF SALES
FLOOR LIGHTING.
2.
REFER TO ARCHITECTURAL SHEETS FOR ACCESS PANEL FOR SIGNAGE IN THIS SOFFIT
AREA.
3.
PROVIDE HIGHLITES EMERGENCY BATTERY PACK 'PGN' (SEE DETAIL E3/DRAWING E1.0).
4.
PROVIDE TEMPERATURE SEAL/FIRE STOP FOR ALL CONDUITS AND HOME RUNS IN
THESE AREAS PER NEC 300.7.
A.
COORDINATE ALL WORK WITH OTHER TRADES AND THE PROJECT MANAGER.
B.
VERIFY LOCATION AND MOUNTING HEIGHT OF ALL LIGHT FIXTURES WITH THE
ARCHITECT/OWNER PRIOR TO ROUGH-IN.
C.
THE EXIT, EMERGENCY AND NIGHT LIGHT FIXTURES SHALL NOT BE SWITCHED.
D.
RGS CONDUIT SHALL BE USED IN ALL EXTERIOR LOCATIONS.
E.
MINIMUM CONDUIT SIZE SHALL BE 1/2".
F.
MINIMUM WIRE SIZE SHALL BE #12 THHN/THWN CU.
G.
ALL EXTERIOR LIGHT FIXTURES SHALL BE CONTROLLED VIA PHOTOCELL.
H.
REFER TO THE PANEL SCHEDULE ON DRAWING E4.0 FOR CONDUIT/WIRE SIZE AND
LOAD DESIGNATIONS. THERE SHALL BE NO SHARED NEUTRALS.
I.
CONDUIT(S) SHALL NOT BE ROUTED EXPOSED ON ANY EXTERIOR WALL.
J.
ALL EXTERIOR DEVICES SHALL BE WEATHERPROOF RATED.
K.
REFER TO DRAWING E1.5 FOR THE LIGHT FIXTURE SCHEDULE.
L.
PROVIDE STAINLESS STEEL SWITCH COVER PLATES FOR ALL CUSTOMER ACCESSIBLE
AREAS. (RESTROOMS, HALLWAY, COOLER, SALES AREA)
1430 W. Peachtree St., Suite 200
Atlanta, GA 30309
t: 404 601 4000 f: 404 601 3980
mn
2
4
A
B
B
A
A
A
A
A
F
A
F
OS
F
BE
B
F
1
F
B
H
A
AE
A
A
AE
H
4
H
H
OS
A
B
H
B
OS
H
F
B
C
M
CIRCLE K
STORES, INC.
H
A
M
C
F
A
A
A
A
A
A
A
A
A
BE
C
H
SPRING
4
OS
TEXAS
C
C
H
F
C
A
AE
A
A
AE
A
A
AE
A
A
5725 LOUETTA RD.
SPRING, TX 77379
HARRIS COUNTY
F
H
B
C
C
OS
4
C
C
2
C
C
H
H
H
H
A
A
A
A
A
A
A
A
F
A
AE
3
2
2
2
F
KEY NOTES
GENERAL NOTES
A. ALL EXTERIOR DEVICES TO BE WEATHERPROOF.
1
3/4" CONDUIT FOR TANK MONITOR CONTROL.
B. ALL FUEL ISLAND CONDUITS SHALL BE ROUTED TO THE RESPECTIVE PANELS
AND/OR TO THE FUEL CONTROL PANELS LOCATED IN THE MANAGERS
OFFICE/STORAGE ROOM.
2
3/4" CONDUIT FOR VR SENSOR CONTROL.
PULL AND TERMINATE VEEDER ROOT WIRING AT PUMPS, AUTO TANK GAUGES,
BRINE SENSORS, HOOK SWITCHES AND TLS350. PROVIDE BELDEN 8860 OR
EQUIV. 18/2 STRANDED, OAS, JACKETED, PLENUM CABLE. VERIFY/ COORDINATE
WITH FUEL PIPING PLANS.
3
3/4" CONDUIT TO EQUIPMENT ROOM FOR INTERCOM.
PULL AND TERMINATE INTERCOM WIRING. 22/2 STRANDED, OAS, JACKETED,
PLENUM CABLE. VERIFY/ COORDINATE WITH FUEL PIPING PLANS.
4
3/4" EMPTY CONDUIT - (EXTRA).
5
PROVIDE SEAL-OFF FITTINGS AT EACH END OF CONDUIT IN
CONJUNCTION WITH/G.V.R. DISPENSER MANUAL. SEE DETAIL #4 ON
THIS SHEET.
6
CONTRACTOR TO PROVIDE 3-1" CONDUITS TO WP J-BOX FOR POLE
SIGN. VERIFY EXACT LOCATION WITH OWNER. (SING INSTALLED
UNDER SEPARATE PERMIT)
C.PROVIDE ALL EMPTY CONDUITS WITH PULL STRING AND CAP AT BOTH ENDS.
D.ELECTRICAL CONTRACTOR SHALL CONTACT POWER COMPANY REGARDING
EXACT LOCATION OF ALL PRIMARY SERVICE EQUIPMENT, TRENCH LOCATIONS,
TRANSFORMER LOCATION, METER LOCATION, ETC.
E. ELECTRICAL CONTRACTOR SHALL PROVIDE NECESSARY SECONDARY
CONDUITS, POWER TRENCHING, BACKFILL, CONCRETE PADS FOR
TRANSFORMERS AND SERVICE EQUIPMENT AND CONDUIT STUBS INTO
TRENCH AS REQUIRED BY POWER COMPANY AND TO THEIR SPECIFICATIONS.
B06
F. ELECTRICAL CONTRACTOR SHALL CONTACT TELEPHONE COMPANY REGARDING
EXACT LOCATION OF ALL PRIMARY SERVICE EQUIPMENT, SERVICE EQUIPMENT,
TRENCH LOCATIONS, ETC.
G.ELECTRICAL CONTRACTOR SHALL PROVIDE ALL NECESSARY TELEPHONE
TRENCHING, BACKFILL, AND CONDUIT STUBS INTO TRENCH AS REQUIRED BY
TELEPHONE COMPANY AND TO THEIR SPECIFICATIONS.
H.ALL WIRING OUTSIDE SHALL BE A MINIMUM OF #10 COPPER WITH TYPE
'XHHW-2' INSULATION. FOR UNDERGROUND CIRCUITS RUN IN P.V.C., PROVIDE
A #10 COPPER BOND IN ADDITION TO CIRCUIT CONDUCTORS.
23
P2C-25
I. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR COORDINATION AND
COMPLIANCE WITH THE UTILITY COMPANY'S REQUIREMENTS. WITH-IN TWO
WEEKS AFTER AWARD OF CONTRACT, SUBMIT (2) COMPLETE SETS OF PLANS,
INCLUDING PLOT OF SURVEY, TO UTILITY COMPANY FOR COORDINATION.
ROUTING OF INCOMING POWER AND TELEPHONE SERVICE SHOWN ARE FOR
ESTIMATING PURPOSES ONLY. ACTUAL ROUTING, CONDUIT, TRENCH, AND PAD
REQUIREMENTS SHALL BE AS SPECIFIED BY THE UTILITY COMPANY. CONFIRM
ALL REQUIREMENTS WITH UTILITIES PRIOR TO INSTALLATION.
J. ALL UNDERGROUND CABLE, PIPE, AND CONDUITS SHALL BE DETECTIBLE
(METALLIC) OR HAVE A DETECTABLE UNDERGROUND DEVICE INSTALLED PER
AZ STATUTE 40-360.22,M.
K. ALL EXTERIOR LIGHTING SHALL BE FULL CUT OFF AND HORIZONTALLY TO THE
GROUND.
5
1430 W. Peachtree St., Suite 200
Atlanta, GA 30309
t: 404 601 4000 f: 404 601 3980
1" CONDUIT FOR POWER HOMERUN.
7
8
SERVICE ENTRANCE LOCATION.
9
(4) 4" EMPTY CONDUITS FOR SECONDARY FEEDERS.
10
11
PROPOSED LOCATION FOR PAD MOUNTED UTILITY TRANSFORMER.
VERIFY FINAL LOCATION AND ROUTING WITH UTILITY.
NOT USED
12
NOT USED
13
(2) 3" EMPTY CONDUITS FOR TELEPHONE SERVICE. VERIFY EXACT QUANTITY
AND SIZE WITH SERVING TELEPHONE COMPANY.
14
"EMERGENCY POWER OFF" SWITCH PER NEC 2008. NEC ART 514.11. PROVIDE
SIGNAGE PER IFC SECTION 2204, 2205. (VERIFY EXACT LOCATION WITH
CIRCLE 'K).
15
WP J-BOX FOR COMPLETE CONNECTION OF CANOPY SIGN. VERIFY EXACT
LOCATION IN FIELD.
16
WP J-BOX FOR COMPLETE CONNECTION OF WATER/AIR FILL STATION.
VERIFY EXACT LOCATION IN FIELD, AND VERIFY REQUIREMENTS PRIOR TO
ROUGH-IN.
1"C CONDUIT FROM ELECTRICAL ROOM/MECHANICAL ROOM, TO CLOSEST
CANOPY COLUMN. ROUTE UP TO CANOPY DECK FOR SPEAKER CONNECTION.
17
18
NOT USED
19
NOT USED
20
LIGHTING CIRCUITS SHALL BE ROUTED VIA 20A 12 POLE ELECTRICALLY HELD
LIGHTING CONTACTOR CONTROLLED BY THE 'EPO' SWITCH LOCATED ON THE GAS
CANOPY. SEE DETAIL 1 SHEET E1.5.
21
NOT USED.
22
NOT USED
23
TANK FILL POINT.
24
3/4" CONDUIT FROM GAS CANOPY TO ELECTRICAL RM FOR MUSIC/SPEAKERS.
25
NOT USED.
B08
B08
8
CIRCLE K
STORES, INC.
SPRING
TEXAS
HANDHOLE W/NON-FERROUS
20'-0" SQ. STEEL POLE
TAMPER PROOF SCREWS
W/ DARK BRONZE FINISH
BASE PLATE 8"SQ.
BASE TAMPER
WITH 8-1/2 BULT CIRCLE
PROOF COVER WITH
DARK BRONZE FINISH AND
1"X45" CHAMFER
ROUNDED CORNERS
(4) 3/4"X18"x3" GALV
ANCHOR RODS PER ASTM A-153
A40
A40
A40
A40
A40
A40
A40
A40
A40
8
8
8
8
8
8
8
8
A40
& 3/4" BOLTS PER ATTACHED
EXPOSED CONC BASE
8
8
SHALL BE PAINTED
A40 10
10
10
A40
10
A40
A40
10
10
A40
A40
10
10
A40
A40
10
SCHEDULE
FINISH GRADE
10
A40
A40
GROUND ROD
12
J
A40
12
A40
12
A40
12
A40
12
A40
12
A40
12
A40
12
A40
12
A40
12
A40
CONDUIT & CONDUCTORS
J
REINF. RODS
J
BASE W/C-1 MIX.
REFERENCE STRUCTURAL DETAIL 107 ON
SHEET S4.1, RESOLVE ANY CONFLICTS WITH
ARCHITECTURAL SHEET SD1.3 (MAXIMUM OF
30" DIAMETER.)
20'-0" BARE #6 CU. AT BOTTOM OF BASE.
5725 LOUETTA RD.
SPRING, TX 77379
HARRIS COUNTY
1430 W. Peachtree St., Suite 200
Atlanta, GA 30309
t: 404 601 4000 f: 404 601 3980
OS
CIRCLE K
STORES, INC.
SPRING
TEXAS
5725 LOUETTA RD.
SPRING, TX 77379
HARRIS COUNTY
A.
B.
C.
COORDINATE ALL WORK WITH OTHER TRADES AND THE PROJECT MANAGER.
REFER TO SHEET E3.0 FOR ONE-LINE DIAGRAM.
15. CONTRACTOR SHALL PROVIDE AND INSTALL NEW 3/4" C, 2 #12 CU.,
1 #12 CU. GND., TO IPaCS CONTROLS.
2.
NEW CPI INTEGRATED PANEL AND CONTROL SYSTEM INCLUDING ELECTRICAL PANELS,
DISPENSER CONTROLLER, DISPENSER ISOLATION, EMERGENCY SHUT-OFF CONTROLS,
AND OUTDOOR LIGHTING CONTROLS. REFER TO SHEET E3.0 FOR ONE-LINE DIAGRAM.
16. EMERGENCY PUMP SHUT-OFF SWITCH AND RESET AT CASHIER, (MOUNTED ON
CASHIER COUNTER). CONTRACTOR SHALL PROVIDE AND INSTALL NEW 3/4" C, 4 #12
CU., 1 #12 CU. GND., TO IPaCS.
3.
NEW PUMP CONTROLLERS AND DATA DISTRIBUTION BOX.
17. OVERFILL ALARM. REFER TO FUEL PLANS (UNDER SEPARATE SUBMITTAL)
4.
NEW PHONE/DATA OUTLET, (TYPICAL). CONTRACTOR SHALL PROVIDE AND INSTALL
NEW 3/4" C, WITH PULLSTRING, FROM BACK BOX TO 6" ABOVE DROPPED CEILING,
AND A 90 DEG. SWEEP FOR PHONE/DATA WIRING BY OTHERS.
18. NEW 30A, 240VAC, NEMA 12, HEAVY DUTY, FUSED DISCONNECT SWITCH WITH FRN-R
FUSES SIZED PER MANUFACTURER'S RECOMMENDATION.
5.
NEW DATA OUTLET, (TYPICAL). CONTRACTOR SHALL PROVIDE AND INSTALL NEW 3/4"
C, WITH PULLSTRING, FROM BACK BOX TO 6" ABOVE DROPPED CEILING AND A 90 DEG.
SWEEP, FOR DATA WIRING BY OTHERS.
1.
ELECTRICAL CONTRACTOR SHALL FIELD VERIFY ALL CONNECTION REQUIREMENTS
(HP, AMPS, VOLTAGE, PHASE AND DISCONNECTING MEANS), FOR ALL EQUIPMENT
SUPPLIED BY OTHERS.
VERIFY LOCATION AND MOUNTING HEIGHT OF ALL DEVICES WITH THE
ARCHITECT/OWNER PRIOR TO ROUGH-IN.
D.
ALL RECEPTACLES WITHIN 6'-0" OF A SINK AND LOCATED AT FOOD SERVICE AREA
AND BEVERAGE COUNTERS SHALL BE GFCI TYPE.
E.
RGS CONDUIT SHALL BE USED IN ALL EXTERIOR LOCATIONS.
1430 W. Peachtree St., Suite 200
Atlanta, GA 30309
t: 404 601 4000 f: 404 601 3980
19. POWERWARE UPS MODEL: 9170+ / PW6S6K. VERIFY EXACT LOCATION WITH CIRCLE K.
F.
MINIMUM CONDUIT SIZE SHALL BE 1/2".
G.
MINIMUM WIRE SIZE SHALL BE #12 THHN/THWN CU.
H.
REFER TO THE PANEL SCHEDULES ON SHEET E4.0 FOR CONDUIT/WIRE SIZE AND
LOAD DESIGNATIONS. THERE SHALL BE NO SHARED NEUTRALS.
I.
CONTRACTOR SHALL PROVIDE AND INSTALL RECEPTACLES FOR ALL EQUIPMENT, TO
MATCH VENDOR FURNISHED PLUGS.
J.
CONDUITS ENTERING THE COOLER AND FREEZER ENCLOSURE SHALL BE FILLED WITH
AN APPROVED MATERIAL TO PREVENT THE CIRCULATION OF WARM AIR TO A COLDER
SECTION OF THE CONDUITS.
K.
ALL EXTERIOR RECEPTACLES SHALL BE FURNISHED WITH A METALLIC TAYMAC
COVER, TO COMPLY WITH N.E.C. 406.8(B)(1).
L.
ALL DISCONNECT SWITCHES SHALL BE MOUNTED TO SATISFY N.E.C. CLEARANCE
REQUIREMENTS.
M.
PROVIDE HOMERUN CONDUITS AS FOLLOWS:
- FRAME RACK TO MANAGER'S OFFICE
- FRAME RACK TO ATM
- FRAME RACK TO POS - SALES COUNTER
- MANAGER'S OFFICE TO POS - SALES COUNTER
(ACCOMMODATE SECURITY INTERFACES AS WELL)
21. COORDINATE THE RECEPTACLE AND CIRCUIT BREAKER REQUIREMENTS WITH VENDOR
PRIOR TO INSTALLATION.
6.
NEW WIREMOLD WITH DEVICES CONFIGURED AS SHOWN, +48" AFF.
7.
BATTERY OPERATED DOOR ALARM.
8.
CONTRACTOR SHALL PROVIDE AND INSTALL J-BOX ON WALL AND 3/4" CONDUITS
WITH PULL ROPE TO J-BOXES IN BACK ROOM, WALK-IN COOLERS AND BEER CAVE FOR
BATTERY OPERATED 'RODANN' DOOR CHIME. VERIFY EXACT REQUIREMENTS PRIOR TO
ROUGH-IN.
9.
20. MAIN CIRCUIT BREAKERS INCLUDING HOUSEKEEPING PAD SHALL NOT BE MOUNTED
HIGHER THAN 6'-8" AFF.
22. J-BOX LOW VOLTAGE POWER SUPPLY FOR ELECTRICAL DOOR LOCK. CONTRACTOR
VERIFY FINAL LOCATION WITH OWNER AND VENDOR PRIOR TO INSTALLATION.
23. LOW VOLTAGE DOOR LOCK SOLENOID ACTIVATED FROM COUNTER. VERIFY FINAL
LOCATION AND REQUIREMENTS WITH LOW VOLTAGE VENDOR.
24. PROVIDE FOUR J-BOXES FOR BEER CAVE SIGNS. VERIFY FINAL LOCATION.
NEW 2' X 4' X 3/4" PLYWOOD TELEPHONE MOUNTING BOARD. CONTRACTOR SHALL
PROVIDE AND INSTALL NEW CU. BUS WITH 1 #6 CU. GND. TO THE GROUNDING
ELECTRODE.
25. PROVIDE WATER PIPE HEAT TAPE. TIE TO CIRCUIT SHOWN.
10. RECEPTACLE SHALL BE MOUNTED IN A FLOOR BOX. CONDUIT TO RECEPTACLE SHALL
BE RUN UNDERGROUND AT 6" BELOW THE SLAB.
11. CONTRACTOR SHALL PROVIDE AND INSTALL NEW 1" C, WITH PULL ROPE TO
TELEPHONE BACKBOARD FOR TELEPHONE/CATEGORY 5 CABLES.
12. CONTRACTOR SHALL PROVIDE AND INSTALL NEW 1" C, WITH PULL ROPE AS SPARE
FOR FUTURE USE.
13. CONTRACTOR SHALL PROVIDE AND INSTALL NEW 1" C, WITH PULL ROPE TO
COMMUNICATIONS RACK FOR TELEPHONE/CATEGORY 5 CABLES.
N. ELECTRICAL CONTRACTOR TO PROVIDE FUSES FOR ALL DISCONNECTS
14. EMERGENCY SHUT-OFF SWITCH FOR PUMPS. ALTERNATE LOCATION PER SITE. VERIFY
FINAL LOCATION.
1
12
13
11
8
19
7
9
3
30A/1P
20
2
18
18
30A/1P
21
21
ESO
ESO
16
8
24
18
23
22
21
30A/1P
16
30A/1P
8
4
10
23
5
18
CIRCLE K
STORES, INC.
23
10
6
SPRING
TEXAS
18
30A/1P
5725 LOUETTA RD.
SPRING, TX 77379
HARRIS COUNTY
10
10
23
10
10
30A/1P
10
18
14
ESO
ESO
17
15
25
25
15
14
1.
NEW FEEDER FROM PANEL 'P1' TO THE HP UNIT, VIA 60A, 240VAC, 3 POLE, NEMA 3R,
HEAVY DUTY, FUSED DISCONNECT SWITCH WITH FRN-R FUSES SIZED PER
MANUFACTURER'S RECOMMENDATION.
2.
NEW 60A, 240VAC, 3 POLE, NEMA 3R, HEAVY DUTY, FUSED DISCONNECT SWITCH
WITH FRN-R FUSES SIZED PER MANUFACTURER'S RECOMMENDATION.
3.
NEW 30A, 240VAC, NEMA 3R, HEAVY DUTY, FUSED DISCONNECT SWITCH WITH FRN-R
FUSES SIZED PER MANUFACTURER'S RECOMMENDATION.
A.
COORDINATE ALL WORK WITH OTHER TRADES AND THE PROJECT MANAGER.
B.
ELECTRICAL CONTRACTOR SHALL FIELD VERIFY ALL CONNECTION REQUIREMENTS
(HP, AMPS, VOLTAGE, PHASE AND DISCONNECTING MEANS), FOR ALL EQUIPMENT
SUPPLIED BY OTHERS.
C.
VERIFY LOCATION AND MOUNTING HEIGHT OF ALL DEVICES WITH THE
ARCHITECT/OWNER PRIOR TO ROUGH-IN.
D.
RGS CONDUIT SHALL BE USED IN ALL EXTERIOR LOCATIONS.
E.
MINIMUM CONDUIT SIZE SHALL BE 1/2".
F.
MINIMUM WIRE SIZE SHALL BE #12 THHN/THWN CU.
G.
REFER TO THE PANEL SCHEDULES ON SHEET E4.0 FOR CONDUIT/WIRE SIZE AND
LOAD DESIGNATIONS. THERE SHALL BE NO SHARED NEUTRALS.
H.
ALL EXTERIOR RECEPTACLES SHALL BE FURNISHED WITH A METALLIC TAYMAC
COVER, TO COMPLY WITH N.E.C. 406.8(B)(1).
I.
ALL CONDUIT SHALL BE ROUTED IN THE CEILING SPACE AND STUBBED UP TO THE
EQUIPMENT/DEVICE ON THE ROOF.
J.
ALL DISCONNECT SWITCHES SHALL BE MOUNTED TO SATISFY N.E.C. CLEARANCE
REQUIREMENTS.
1430 W. Peachtree St., Suite 200
Atlanta, GA 30309
t: 404 601 4000 f: 404 601 3980
1
2
3
3
3
CIRCLE K
STORES, INC.
1
3
3
SPRING
TEXAS
5725 LOUETTA RD.
SPRING, TX 77379
HARRIS COUNTY
3
2
1430 W. Peachtree St., Suite 200
Atlanta, GA 30309
t: 404 601 4000 f: 404 601 3980
#3/0 CU. EQUIP. BOND
N
G
BUILDING STEEL
PIPINGS SYSTEMS
#4 CU. UFER GROUND
INTEGRATED POWER INTEGRITY / EQUIPMENT ROOM CONDUIT PENETRATION DETAILS
#4/0 CU. BOND TO
METALLIC COLD WATER
PIPING SYSTEMS
FOR REFERENCE ONLY. POWER INTEGRTIY TO SUPPLY PROJECT SPECIFIC DETAILS.
'DP' DISTRIBUTION PANEL
POWER INTEGRITY #PDS-CIRCLEK01
GROUNDING DETAIL
TIMECLOCK AND
LTG. CONTROL RELAY(S)
N.T.S.
C
TC
REF# 72-1960-248746 DATED 11/11/2009
CONTACT: BRENDA BELTON (Email [email protected])
#12CU.
(8-FT MIN.)
TO UTILITY COMPANY.
3 SETS OF (4)-4#500, 4"C
COORDINATE ROUTING
X
45"
36"
SECTION #1
SECTION #2
SPRING
20"
TEXAS
SECTION #3
208/120V
208/120V
208/120V
208/120V
208/120V
208/120V
PANEL
'P2C'
PANEL
'P2A'
PANEL
'P2E'
PANEL
'P2B'
PANEL
'P2D'
PANEL
'CW'
F4
F5
F8
8'X 12"
F1
CIRCLE K
STORES, INC.
3
F3
4
3
F6
4
3
4
3
4
6'-7"
N
CT
REFER TO
GROUND DETAIL
#2/E3.0.
TRANSFORMER
(SEE SITE PLAN)
(FOR LOCATION)
BY LOCAL UTILITY
COMPANY.
FURNISH AND INSTALL
PAD AS REQUIRED BY
LOCAL UTILITY COMPANY.
5725 LOUETTA RD.
SPRING, TX 77379
HARRIS COUNTY
400
400
65K
CT
208/120V
CONTROL PANEL
1200
1000
65K
CONDUIT AREA
NOTE: FACTORY INSTALLED FEEDERS
FROM DP PANEL TO PANEL BOARDS
1
PANEL
'U'
POWERWARE
UPS
9170+
PW6S6K
F9
6kVA
SERIES RATING GENERAL NOTES
THE MOTOR CONTRIBUTION TO THE FAULT CURRENT MEETS THE 1% CRITERIA. AS PER NEC
240.86(C)
X F2
3 SETS OF
4#400MCM
1#2/0 GND
3 Inch C
RUN BELOW FLOOR SLAB OR GROUND, (3)
SETS OF (4)-4#500, 4"C.
(FURNISHED AND INSTALLED BY E.C.)
NO DESIGN CHANGES MAY BE MADE TO THE SYSTEM WITHOUT THE PRIOR APPROVAL OF THE DESIGN
ELECTRICAL ENGINEER AND THE ELECTRICAL INSPECTOR.
2 SETS OF
4#3/0
1#3 GND
3 Inch C
FAULT CURRENT CALCULATIONS
-
THE FOLLOWING CALCULATIONS ARE BASED ONT THE "POINT-BY-POINT" METHOD WHERE:
M= 1/(1+f)
Isc = Isc x M
ONE LINE DIAGRAM
f = 1.73 x L x I
CxExn
XFMR:
IP(sca)= IP(sca)x Vp x%Z
100,000xKVA
Vs
(ALL CALCULATIONS UTILIZE COPPER CONDUCTORS)
* PROVIDE CLASS RK5 FUSES SIZED PER
MANUFACTURERS SPECIFICATIONS
REFER TO PANEL SCHEDULES FOR WIRE AND
CONDUIT SIZE FOR ROOF TOP UNITS.
Fault
MAXIMUM CIRCUIT BREAKER HEIGHT
Point
1
2
3
4
5
6
7
8
9
EQUAL TO 6'-7" AFF OR AFG
Panel /
Transformer
SES
DIST. P1
PANEL 'P2A'
PANEL 'P2B'
PANEL 'P2D'
PANEL 'P2E'
NOT USED
PANEL 'P2C'
PANEL 'U'
Source
(Fault
Source I
Conduit
Type
1
2
2
2
2
(amps)
51,502
51,502
35,762
35,762
35,762
35,762
NM
M
M
M
M
3
1
1
1
1
Set(s)
Set(s)
Set(s)
Set(s)
Set(s)
2
2
35,762
35,762
M
M
1
1
Set(s) of
Set(s) of
Point)
'C' value
E (volts)
L (length)
400 KCML
3/0
3/0
3/0
3/0
22737
12844
12844
12844
12844
208
208
208
208
208
1/0
10
8925
981
208
208
Wire/Bus Size
of
of
of
of
of
X'FMR
X'FMR
KVA
Z
SERIES RATING KEY NOTES
IS(sca)= Vp x M x IS(sca)
f
M
70
0
0
0
0
0.440
0.000
0.000
0.000
0.000
0.69
1.00
1.00
1.00
1.00
Isc
51,502
35,762
35,762
35,762
35,762
35,762
0
0
0.000
6.693
1.00
0.13
35,762
4,649
1
THIS SERVICE IS A SERIES RATED SYSTEM: 2-TIER 65/10. ALL MAIN SERVICE . SYSTEM
COMPONENTS SHALL BE RATED 65K, WITH SERIES RATED DOWNSTREAM.
2
CONTRACTOR SHALL LABEL MAIN DISCONNECT "CAUTION" - SERIES RATED SYSTEM (65/10). 65,000
AMPS AVAILABLE IDENTIFIED REPLACEMENT COMPONENT REQUIRED." IN ACCORDANCE WITH NEC
110-22.
3
4
CONTRACTOR SHALL LABEL PANEL(S) "CAUTION" - SERIES RATED SYSTEM (65/10). "15,329" AMPS
AVAILABLE IDENTIFIED REPLACEMENT COMPONENT REQUIRED." IN ACCORDANCE WITH NEC 110-22.
(REFER TO SHORT CIRCUIT CALCULATIONS FOR ACTUAL AMPS TO BE LABELED).
CIRCUIT BREAKERS SHALL BE A BOLT-ON TYPE, U.L.-LISTED SERIES-RATED COMBINATION WITH
THE BREAKERS AT DISTRIBUTION PANEL 'DP'.
1430 W. Peachtree St., Suite 200
Atlanta, GA 30309
t: 404 601 4000 f: 404 601 3980
CIRCLE K
STORES, INC.
SPRING
TEXAS
5725 LOUETTA RD.
SPRING, TX 77379
HARRIS COUNTY
1430 W. Peachtree St., Suite 200
Atlanta, GA 30309
t: 404 601 4000 f: 404 601 3980
CIRCLE K
STORES, INC.
SPRING
TEXAS
5725 LOUETTA RD.
SPRING, TX 77379
HARRIS COUNTY