Mitsubishi Electric Ducted Air Conditioning Systems

Transcription

Mitsubishi Electric Ducted Air Conditioning Systems
Enhance your living environment with
Mitsubishi Electric Ducted
Air Conditioning Systems.
The Mitsubishi Electric Story.
Mitsubishi Electric have a proud history in the manufacturing and supply of leading edge electrical
and electronic equipment for both domestic and commercial use. Our efforts to make indoor life
more comfortable began in 1921, with the introduction of our first electric fan which became an instant hit.
Some 10 years later we began to manufacture coolers, which were just as popular.
Since then our understanding that technology is the driving factor of change in our lives has seen us
become a world leader in energy efficient air conditioning systems. However our development of breakthrough
technologies and products is not just restricted to heating and cooling.
Since 1980 to the present day the pace at which Mitsubishi Electric has introduced and refined products
that benefit society, industry and individuals, has been nothing less than astonishing.
These technologies include the world’s first large scale LED Screen for sports arenas, the world’s largest
CRT television screen for the consumer market, the world’s first spiral escalator, the world’s fastest elevators,
the antenna technology behind the world’s first in-flight internet service, solar cell technology and much more.
Today Mitsubishi Electric is a global giant with operations in over 35 countries, with more than
97,000 employees.
Our commitment to quality service, research and development has helped us gain a leading position
in today’s marketplace in a wide variety of areas including heating, cooling and air conditioning.
Mitsubishi Electric’s ‘today technology’ provides climate controlled comfort wherever you live, work and relax.
Whether it’s consistent heating and cooling for the home or office, Mitsubishi Electric offers you
state-of-the-art technology that is quiet, simple to use, reliable and above all, energy efficient.
Our commitment to quality, service, research
and development has helped us gain a leading
position in today’s marketplace.
To enhance your living environment
has to be the ultimate in comfort.
With Mitsubishi Electric Ducted Inverter Systems, climate control is at the touch of a button.
Warm even heat during Winter and clean cool air during Summer. Our Ducted Systems are ideal for multiple
room applications and can incorporate zone selection if required.
The Outdoor Inverter Unit that provides the power, is positioned outside your home, while the Indoor Fan Coil
Unit is positioned out of sight in either the ceiling void, or under the floor. Cool or warm air is then ducted quietly
into each room through visually appealing Air Diffusers positioned in the ceiling, wall or floor. Warm or cool air is then
filtered and returned to the Indoor Fan Coil Unit through the Return Air Grille.
The system is easily operated via a wall mounted LCD Control Panel.
Ductwork
Delivers the conditioned
air throughout the rooms
of your home.
System Controller
Located conveniently within
the home generally near
the return air grille.
Linear Diffuser
Round Diffuser
Indoor Fan Coil Unit
Delivers the conditioned air
to the ductwork.
4 Way Diffuser
Air Diffuser
Diffusers are available
in many designs to suit
the decor of your home.
Outdoor Unit
Quietly delivers refrigerant
to the indoor unit.
Return Air Grille
and Filter
Filters the air as it returns
it back to the indoor unit.
Mitsubishi Electric’s Ducted Inverter
Technology gives you the edge.
Mitsubishi Electric’s Advanced Technology Inverter Systems are more economical
and efficient than conventional systems.
Conventional non-inverter systems run at a fixed speed. To maintain a set
temperature the compressor switches on/off so room temperatures continually
fluctuate, falling, rising and falling again.
To overcome this problem Mitsubishi Electric’s advanced inverter technology gently
increases or decreases power to suit the prevailing conditions reaching the desired
temperature quicker, more efficiently without severe temperature fluctuations.
The resulting reduction in electricity consumption by our energy saving technology
not only saves you money but also reduces your carbon footprint on the
environment.
Mitsubishi Electric’s Outdoor Inverter units have been aesthetically designed to
minimise their visual impact on your environment.
Each contains a number of innovative features that makes them quieter, more
energy efficient and reliable, placing them at the cutting edge in the industry.
Conventional air conditioner:
Unstable temperature control
Temperature fluctuation
Too hot
Set temperature
Too cold
ON
OFF
ON
Compressor operation
OFF
Time
Inverter operation:
Uniform temperature control
Uniform temperature control
Set temperature
Compressor operation
Time
Reducing Energy
Consumption.
Cost performance comparison
Inverter model vs. non-Inverter model:
Thanks to the new Inverter System, a large
reduction in power consumption is now possible.
This results in one of the highest COP* (Co-efficient
of Performance) ratings in the industry, helping to
lower overall running costs and provide greater
savings.
Case Study 1– Power Consumption
Based on our calculations on the operating conditions
shown below, the new Inverter
System can reduce
reduction
power consumption by
up to 70% compared to
an old model installed
8 years ago.
70%
Quiet Operation
outdoor unit noise comparison
Improvements in the
design of our fan blades
combined with a new
grille shape has seen
us become No 1
in the industry.
Suppressing to
about 1/2 audible sound
compared to daytime
The outdoor unit is even
quieter when the outside
temperatures drops, as
it automatically switches
to low noise mode which
reduces it’s operating
noise by a further 3dB.
Low-Noise
mode
DAY
DAY
50dB
47dB
(in cooling mode)
(in cooling mode)
*At outdoor temperature of 25ºC
¬Noise level
Train interior
Quiet passenger
car interior
(40km/h)
Library interior
80dB
60dB
40dB
Human
Sound of
hearing limits
rustling leaves (Extremely quiet)
10dB
Conditions of trial calculation
( according to Japan Refrigerant Association )
Place
Office in Tokyo (Japan)
Operating
time
8AM to 8PM (12 hours/day) &
6 days/week
Operating
period
Cooling: April 16–November 8
Heating: December 14–March 23
Set
temperature
DC Fan Motor
Before replacement:
Installed 8 years ago
After replacement:
Power Inverter
Model name
PLH-3GKHB/
PUH-3YKA
Model name
PLA-RP71AA/
PUHZ-RP71VHA
Case Study 2 – COP*
Comparison of COP between non-Inverter and
Power Inverter (4 way cassette type) models.
COP
Average
33%
3.60
3.5
60%
UP
increase
3.30
3.21
26%
UP
3.0
2.61
26%
UP
2.55
2.25
Outdoor Unit
Power Inverter
3HP
4HP
2.81
5HP
17%
UP 2.40
6HP
Non-Inverter (R407C)
*COP is a performance and efficiency rating similar to the Star Energy
Rating System. The higher the COP, the more efficient the system.
A highly efficient DC Motor
drives the fan of the outdoor
unit, offering up to 60%
greater efficiency than the
equivalent AC Motor.
The compact configuration provides
larger airflow with low noise.
Peace of Mind
All Mitsubishi Electric air conditioners used in
residential applications are
covered by a full 5 year
parts and labour
warranty.
Mitsubishi Electric
air conditioners
have been designed
and built to deliver
optimum performance
year in year out.
Higher performance, lower power
consumption and longer life.
When it comes to comfort, efficiency and durability, Mitsubishi Electric has a distinct advantage
over the opposition, we call it MEQ – Mitsubishi Electric Quality. Simply put it is a superior
standard that we apply to our own business. While other systems may meet stringent industry
standards, Mitsubishi Electric continually strives to exceed them. MEQ delivers air conditioning
systems at the leading edge of technology that operate efficiently in extreme weather conditions,
year in, year out.
MEQ Gives Us 3 Important Advantages:
Comfort
We have created products that are designed to provide you with exceptional
comfort in your surroundings, in all weather conditions.
Efficiency
We strive for the perfect balance of performance, reliability, low power consumption
and a long operational life span for all our products. The result is an air conditioning range that is
rated amongst the best in the industry in terms of design, quality and energy efficiency.
Durability
We subject the indoor and outdoor units of all our systems to rigorous durability testing, which includes
harsher temperature extremes than are likely to be found anywhere in the world. This allows us to produce
higher quality products that protect your investment through years of reliable service.
Standard Inverter
Our New Inverter features Energy Saving, Compact Design, Light Weight,
and Basic Performances as well.
Compact Inverter.
A Product Line of 19 Models in 5 Types Responds to
Your Versatile Needs.
The Advanced Technology in Mitsubishi
Electric’s Compact Inverter makes it the perfect
To meet your interior or space designing, optimum indoor units can be
solution for today’s diversified Residential
requirements.
selected and
from 5Commercial
types. A combination
with differentFor
typehomes,
indoor units in two or
rooms besides
1:1 combination
can be constituted
various
or small to medium size offices, ourthree
Compact
Inverter
Ducted System
gives you
costapplications.
effective
climate control for both heating and cooling. Technological advances have increased output
and efficiency, allowing you to reach and
maintain your chosen temperature faster, without
5.0kW
6.0kW
fluctuations, while using less energy. The
Compact Inverter is
7.1kW
Model Size
71
100
10.0kW
smaller and lighter, making handling and
installation
easier
12.5kW
Compact
Inverter
SUZ
which gives you more flexibility in your 14.0kW
choice of location.
*50/60/71 models are for Twin/Triple use.
Quiet Operation
Single Phase
•
100mm
from wall
125
•
500mm from unit
140
•
Easier Installation Work Thanks to
Single Phase
The outdoor unit model BP100 counts for 943mm only
for the height and 66kg for the mass. A significant
weight
Three Phase
reduction of 55kg has been attained compared to the
technology has also madePower
it possible
to
pipe
refrigerant
Inverter. The burdening of installation/transportawork
can be lightened
by Fan
the compact
design and
metres from the Inverter totionthe
concealed
Indoor
Coil Unit,
light weight. BP200/250 became compact as well!!
Longer Maximum Piping Length
The new
up to 70
giving you more choice and versatility in the layout of your Ducted System
and positioning your Outdoor Unit.
Flexibility in Layout Planning is further enhanced by the integration
R22
66
of the Compact Inverter or Power Inverter
outdoor
units
Power Inverter 121
New Inverter
Fixed Speed 94
and our range of Concealed Indoor Units.
kg
kg
kg
Concealed Indoor Unit
Mitsubishi Electric’s range of Concealed Indoor Units are versatile
and easy to install even where roof or under floor space is limited.
New Inverter
Computerised Dehumidification
•
PUHZ-RP
•
•
•
•
The silent operation of the outdoor unit Model BP100
has attained
Further 3dB can
• down to• 50dB (cooling).
•
be reduced under the Silent Operation Mode.
Suppressing to
about 1/2 audible sound
(compared to daytime)
50dB
3dB reduction
47dB
Max Height
Difference Possible
Max Piping Length
Heating
Operation
Even at 15°C Outside Temperature
66kg
Compact Inverter
SUZ-KA71
15
30
PUHZ-BP100,125,140VHA
30
50
Piping Length for Easier
30
Installation
70
Power Inverter
PUHZ-RP71VHA2
Even when the ductwork is very long, the volume of airflow
remains consistent due to the high static pressure available from
the fan coil unit’s multiple speed fan motor.
•
Silent Outdoor Unit
PUHZ-BP200/250VHA
High Output Fan Capability
Top flow 198kg
250
•
Three Phase
The Compact Inverter operates at noise levels
Compact and Light WeightPower
Design
Inverter
that are at the leading edge of Industry Standards.
200
PUHZ-BP
Refrigerant piping can
30be extended up to 50m
50 or 70m
by charging refrigerant additionally.
PUHZ-RP100,125,140VHA2
30
75
PUHZ-RP100,125,140YHA2
BP100
131kg
30
20m
20m
30m
75
50m
50m
70m
Side flow
BP125/140
BP200/250
Concealed Indoor Unit
Another possibility! Compact S series outdoor unit can now be connected to
P series indoor unit as well.
This feature allows you to reduce the
humidity
inside
yourbehome
keeping you
S series
outdoor
unit can
connected
SUZ-KA25
not only with SLZ and SEZ but also some
SUZ-KA35
comfortable in all seasons.
SUZ-KA50
P series indoor units. Greater inverter line
up satisfies your various requirement.
Power Inverter.
PEA - RP125EA
PEA - RP100EA2
SUZ-KA60
SUZ-KA71
Ideal for larger homes or medium to large offices, the Mitsubishi Electric Power Inverter
boasts all of the technological advances of the Compact Inverter with a number
of design features that further reduce power consumption and make it ideally suited
to commercial applications.
100mm
from wall
Ultra Quiet Operation
500mm from unit
Suppressing to
Improvements to the design of the dual fan blades and a new grille shape
deliver operating noise levels that are the best in the industry. A Low Noise
Priority function is also available, where the noise of the outdoor unit can be
reduced via a switch or time clock.
about 1/2 audible sound
compared to daytime
Longer Maximum Piping Length
The Power Inverter can pipe refrigerant up to 75 metres to the concealed
ceiling unit, further adding to it’s versatility and efficiency in getting airflow
to where it is most effective.
Multi System Use
The Mitsubishi Electric Power Inverter can be connected to a number of concealed
indoor units that can be centrally controlled by one remote controller.
(
)
(
) (
Twin
)
Triple
Compact Inverter
PUHZ-BP140VHA
2 x PEA-RP71
PUHZ-BP200VHA
2 x PEA-RP100EA-2
PUHZ-BP250VHA
2 x PEA-RP125
PUHZ-BP250VHA
3 x PEA-RP71
Power Inverter
PUHZ-RP140VHA2
2 x PEA-RP71
PUHZ-RP140YHA2
2 x PEA-RP71
Indoor unit
PEA-RP71EA
Outdoor unit
Function
Capacity Rated
kW
Input
Indoor unit
EER Rated Outdoor unit
EER Partload Function
see*3
kW
COP
PEA-RP125EA
PEA-RP100EA2
PEA-RP140EA2
PEA-RP170WGA
SUZ-KA71VA
PUHZ-BP100VHA
PUHZ-BP170YHA
PUHZ-BP125VHA
PUHZ-BP140VHA
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
6.9
8
9.2
9.5
11.2
12.5
13
14.8
17.0
20.0
(0.9-8.1) (0.9-10.2)
(3.5-10) (3.5-11.2) (5.2-12.5)
(4.7-14)
(5.2-15.2) (4.7-17.4) (9.0-21.0) (9.5-23.5)
2.49
3.82
3.02
4.65
4.07
5.39
4.48
7.3PEA-RP250WGA
7.18
PEA-RP125EA
PEA-RP140EA2
PEA-RP71EA 2.9
PEA-RP100EA2
PEA-RP170WGA
PEA-RP200WGA
3.08
2.41
3.31
2.31
3.22
2.34
3.39
2.53PUHZ-BP250YHA
3.01
SUZ-KA71VA 2.34 PUHZ-BP100VHA
PUHZ-BP200YHA
PUHZ-BP170YHA
PUHZ-BP125VHA
PUHZ-BP140VHA
3.04 Cooling Heating
2.94
2.91 Cooling
Cooling
Heating
Cooling
Heating
Cooling2.86Heating
Cooling
Heating
Heating 3.19
Cooling
Heating
Concealed
Units
Capacity (min-max)Indoor kW
PEA-RP20
PUHZ-BP2
Cooling
19
(9-22.4)
7.3
2.53
3.19
Capacity Rated
kW
6.9
8
9.2
9.5
11.2
12.5
13
14.8
17.0
20.0
19
22.4
22
25
Capacity (min-max)
kW
(0.9-8.1) (0.9-10.2)
(3.5-10) (3.5-11.2) (5.2-12.5)
(4.7-14)
(5.2-15.2) (4.7-17.4) (9.0-21.0) (9.5-23.5) (9-22.4)
(9.5-25)
(11.2-28) (12.5-31.5)
Input
kW
2.9
2.49
3.82
3.02
4.65
4.07
5.39
4.48
7.3
7.18
7.3
7.18
8.53
7.58
Indoor unit
PEA-RP125EA
PEA-RP140EA2
PEA-RP71EA
PEA-RP100EA2
PEA-RP170WGA
PEA-RP200WGA
PEA-RP250WGA
EER Rated
COP
2.34
3.08
2.41
3.31
2.31
3.22
2.34
3.39
2.53
3.01
2.53
3.01
2.49
3.21
Outdoor
unit
SUZ-KA71VA
PUHZ-BP100VHA
PUHZ-BP200YHA
PUHZ-BP250YHA
PUHZ-BP170YHA
PUHZ-BP125VHA
PUHZ-BP140VHA
3.04
2.94
2.86
3.19
3.19
3.07
EER Partload see
2.91
*3
Function
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
Capacity Rated IndoorIndoor
6.9
8 PEA-RP71EA
9.2
9.5
11.2
12.5
13
14.8
17.0
20.0
19
22.4 PEA-RP170WGA
22
25
unit kWunit
PEA-RP125EA
PEA-RP140EA2
PEA-RP71EA
PEA-RP100EA2
PEA-RP170WGA
PEA-RP200WGA
PEA-RP250WGA
PEA-RP100EA2
PEA-RP125EA
PEA-RP140EA2
PEA-RP20
Capacity (min-max)
kW
(0.9-8.1) (0.9-10.2)
(3.5-10) (3.5-11.2) (5.2-12.5)
(4.7-14)
(5.2-15.2) (4.7-17.4) (9.0-21.0) (9.5-23.5) (9-22.4)
(9.5-25)
(11.2-28) (12.5-31.5)
Outdoor
unit supply
SUZ-KA71VA
PUHZ-BP100VHA
PUHZ-BP200YHA
PUHZ-BP250YHA Three phase, 50H
PUHZ-BP170YHA
PUHZ-BP125VHA Single
PUHZ-BP140VHA
Power
phase,4.48
50Hz, 220-240V
Input
kW
2.9
2.49
3.82
3.02
4.65
4.07
5.39
7.3
7.18
7.3
7.18
8.53
7.58
Cooling
Heating 367-450
Cooling
Heating
Cooling 450-567
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
Airflow
(Lo-Hi) Function COP L/S
567-700
800-1000
EER
Rated
2.34
3.08
2.41
3.31
2.31
3.22
2.34
3.39
2.53
3.01
2.53
3.01
2.49
3.21800-1000
Capacity
RatedseeIndoor
6.9
8
9.2
9.5
11.2
12.5
13
14.8
17.0
20.0
19
22.4
22
25
PEA-RP71EA
PEA-RP100EA2
PEA-RP125EA
PEA-RP140EA2
PEA-RP170WGA
PEA-RP200WGA
PEA-RP250WGA
3.04
2.94
2.86
3.19
3.19
3.07
EER
2.91
*3 unit kW
Ext Partload
static
pressure
Pa
125 (9.0-21.0)
150
Capacity
(min-max)
(0.9-8.1) (0.9-10.2)
(3.5-10) (3.5-11.2)
(5.2-12.5)
(4.7-14)
(5.2-15.2)
(4.7-17.4)
(9.5-23.5)
(9.5-25)
Power supply kW
Single
phase, 50Hz,
220-240V
Three(9-22.4)
phase, 50Hz,
380-415V(11.2-28) (12.5-31.5)
Sound
pressure
level
dB(A)
52-55
54-58
51-55
Input (Lo-Hi)
kW
2.9 367-4502.49
3.82 450-567
3.02
4.65 567-700
4.07
5.39
7.3
7.18800-10007.3
7.18
8.53
7.58 47-51
Airflow
L/S
1067-1333
800-10004.48
EERstatic
Ratedpressure
COP
2.34
3.08
2.41
3.31
2.31 125 428
3.22
2.34
3.39
2.53
3.01
2.49
3.21 465
Ext
Pa
Height (mm)
428
428
4282.53 150 3.01
3.04
2.94
3.19
3.19
3.07 53-55
EER Partload
2.91 51-55
Sound
pressuresee
level
dB(A)
54-58 2.86
47-51
*3
Dimensions
Width (mm) 52-55
785
1,055
1,255
1,600
1,415
Height (mm)
428
428
428
465
465
428
Depth (mm)
690
614
690PEA-RP200WGA
Indoor unit Width (mm)
PEA-RP71EA
PEA-RP100EA2
PEA-RP125EA
PEA-RP140EA2
PEA-RP170WGA 1,600
PEA-RP250WGA
Dimensions
785
1,055
1,255690
1,600
1,415 690
Weight
kg
Power supply Depth (mm)
Single phase, 690
50Hz,
Three
46
59220-240V
72
74
76phase, 50Hz, 380-415V
690
690
614
614
690
Weight
kg
Airflow (Lo-Hi)
L/S
367-450
450-567
567-700
1067-1333
800-1000
800-1000
46
59
72
80
74
76
Ext static pressure
Pa
125
150
Indoor unit
PEA-RP71EA
PEA-RP100EA2
PEA-RP125EA
PEA-RP140EA2
PEA-RP170WGA
PEA-RP200WGA
PEA-RP250WGA
Sound pressure level
dB(A)
52-55
54-58
53-55
47-51
51-55
Power supply
Single phase, 50Hz, 220-240V
Three phase, 50Hz, 380-415V
Height (mm)
428
428
428
465
465
428
Airflow (Lo-Hi)
L/S
367-450
450-567
567-700
1067-1333
800-1000
800-1000
Dimensions
Width (mm)
785
1,055
1,255
1,600
1,600
1,415
Ext static pressure
125
150
PUHZ-BP125VHA
PUHZ-BP140VHA
PUHZ-BP170YHA
Outdoor
unit Pa unit
SUZ-KA71V A SUZ-KA71V
PUHZ-BP100VHA
PUHZ-BP200YHA
PUHZ-BP250YHA
PUHZ-BP125VHA
PUHZ-BP140VHA
PUHZ-BP170YHA
Outdoor
A690
PUHZ-BP100VHA
PUHZ-BP2
Depth (mm)
690
690
614
614
690
Sound
level
52-55
54-58
53-55
47-51
51-55
finish dB(A)
Munsell
3Y 7.8/1.1
Weight pressure External
kgfinish
46
59
72
80
74
76
External
Munsell
7.8/1.1
(mm)
428
428
465
4653Y
428
Power
supply Height
Single428
phase, 50Hz, 220-240V
Three
phase,
50Hz, 380-415V
supply
Single
220-240V
Three phase, 50Hz
Dimensions output Power kW
Width
(mm)
785
1,255
1,600
1,600
3.9
5.5
Compressor
1.3
2 1,055
3.4 phase, 50Hz, 1,415
4.7
Depth (mm)
690
690
614
614
690
Airflow
L/S
818
1170
2167
3.9
Compressor output
kW
1.3 1000690
2
3.4
4.7
Weight pressure level (dB)
kg
46
72
80
74
76
54
Sound
Cooling
mode
53
50 59
52
59
Airflow
L/S
818
1000
1170
2167
PUHZ-BP125VHA
PUHZ-BP140VHA
PUHZ-BP170YHA
Outdoor unit Silent mode
SUZ-KA71V A
PUHZ-BP100VHA
PUHZ-BP200YHA
PUHZ-BP250YHA
51
47
49
56
54
Sound pressure
level
(dB)
Cooling mode 55
53 54
50
52
59
External
finish
Munsell56
3Y 7.8/1.1
Heating mode
55
59
Power supply dB(A)
Single
Three
380-415V
74
Sound power level
70 phase, 50Hz, 220-240V
72
77
51phase, 50Hz,
Silent mode 68
47
49
56
3.9
5.5
Compressor output
kW
1.3
2
3.4
4.7
Height (mm)
850
943
1350
56PUHZ-BP200YHA
Heating mode
55 1000
54
55
59
PUHZ-BP125VHA
PUHZ-BP140VHA
PUHZ-BP170YHA
Outdoor unit
SUZ-KA71V A
PUHZ-BP100VHA
PUHZ-BP250YHA
Airflow
L/S (mm)
818
1170
2167
Dimensions
Width
840
950
950
finish
Munsell 3Y 7.8/1.1
74 330+30
Soundpressure
powerExternal
level
dB(A)
68 50
70
72
77
54
Sound
level
(dB)
Cooling(mm)
mode
53
52
59
Depth
330
330+30
Power supply
phase, 50Hz, 220-240V
Three phase, 50Hz, 380-415V
51
Silent mode
47
49
56
Height (mm) 1.3
850 Single
943
1350
84
133
Weight
kg
53
66
80
126
3.9
5.5
Compressor output
kW
2
3.4
4.7
56
Heating mode
55
54
55
59
Chargeless
piping length
m
7
20
30
Dimensions
Width (mm) 818
840 1000
950
950
Airflow
L/S
1170
2167
74
Sound
power
level
dB(A)
68
70
72
77
Max
piping
length
m
30
50
70
54 330+30
Sound pressure level (dB)
Cooling mode
53
52
59
Depth (mm) 850
330 50
330+3
Height (mm)
943 HP switch
1350HP switch
Protection device
Discharge thermo,
Shell thermo,
51
Silent mode
47
49
56
84
Weight
kg
5315.26/11.68
66
126
Dimensions
Width
840
950
950
19.46/15.3880
11.0/12.0
Rated
running current
Amps (mm)
18.24/15.64
9.47/9.88
56
Heating mode
55
54
55
59
Depth (mm)
330
330+30
330+30
40
Breaker
size piping length
Amps
20
25
32
32
Chargeless
m
7
20
30
74
Sound
power level
dB(A)
68
70
72
77
84
133
Weight
kg
53
80
126
Height (mm)
850
943
1350
Max piping length
m
30 66
50
70
Chargeless piping length
m
7
20
30
Dimensions
Width (mm)
840
950
950
Protection
device
Discharge thermo, HP switch
Shell thermo, H
Max
piping length
m
30
50
70
Depth (mm)
330
330+30
330+30
PEA-RP71EA
Indoor
unit
PEA-RP100EA2
PEA-RP125EA
PEA-RP140EA2
Protection
device
Discharge
thermo,
HP
switch
Shell
thermo,
HP
switch
19.46/15.38
Rated running current kg
Amps
15.26/11.68
18.24/15.64
9.47/9.88
84
133
Weight
53
66
80
126
11.0/12.0
Rated
running
current
Amps Amps
18.24/15.64
PEA-RP71EA
PEA-RP100EA2
40
Breaker
size
2015.26/11.68
25 PEA-RP125EA19.46/15.3832 PEA-RP140EA2 9.47/9.88
32
Chargeless
piping Indoor
length unit m
7
20
30
Ÿ Capacities
Breaker size
Amps
20 Heating
25
32
32
stated are based
Cooling 30
Cooling
Heating
Cooling
Heating40
Cooling
Heating
Max piping length Function m
50
70
on HP
indoor
unit connected to
Capacity Rated
(min-max)Ÿ
kW
7.1 (3.3-8.1) 8.4(3.5-10.2) 10 (4.9-11.4) 11.2(4.5-14.0)
12.5(5.5-14.0)
14(5.0-16.0)
14(5.5-15.3)
16(5.0-18.0) Shell thermo,
Protection
device
Discharge thermo,
HP switch
switch
PUHZ-RP series outdoor
units
Input
kW
2.48
2.51
3.25
3.2
4.42
4.07
5.03
4.51 9.47/9.88
19.46/15.38
11.0/12.0
Rated running current
Amps
15.26/11.68
18.24/15.64
EER Rated
see*3 COP
2.73 20 3.21
2.97 25
3.33
2.69/3.43
3.31 40
2.67/3.26
3.50
Breaker
size/ Partload
32
32
PEA-RP71EA
Indoorsupply
unit Amps
PEA-RP100EA2
PEA-RP125EA
PEA-RP140EA2
Power
Single
phase,
50Hz,
220-240V
Indoor unit
PEA-RP100EA2
PEA-RP125EA
PEA-RP140EA2
PEA-RP71EA
PEA-RP71EA
Indoor unit L/S
PEA-RP100EA2
PEA-RP125EA
PEA-RP140EA2
Airflow (Lo-Hi)
367-450
450-567
567-700
800-1000
Ÿ Capacities
PEA-RP71EA
Indoor
PEA-RP125EA
PEA-RP140EA2
stated are based
Cooling
Heating
Cooling
Heating PEA-RP100EA2
Cooling
Heating
Cooling
Heating
Ext static pressure Function
Paunit
125
Ÿ
Ÿ Cap
onCooling
indoor unit connected Heating
to
Capacity
Rated (min-max)
kW
7.1 (3.3-8.1)
8.4(3.5-10.2)
12.5(5.5-14.0)
14(5.0-16.0)
14(5.5-15.3)
Sound
pressure
level
dB(A)
52-55
54-58
51-5516(5.0-18.0)
PEA-RP71EA
Indoor Function
unit
PEA-RP100EA2
PEA-RP125EA
PEA-RP140EA2
Cooling10 (4.9-11.4)
Heating11.2(4.5-14.0)
Cooling
Heating
Cooling
Heating
PUHZ-RP
series
outdoor units
Input
kWŸ (mm)
2.48
3.25
3.2
4.42
4.07
5.03
4.51
428 2.51
428
428
428
PEA-RP71EA
Indoor
unit Height
PEA-RP100EA2
PEA-RP125EA
PEA-RP140EA2
on in
Capacity Rated
(min-max)
kW
7.1 (3.3-8.1) 8.4(3.5-10.2)
10(4.9-11.4)
11.2(4.5-14.0)
12.5(5.5-14.0)
14(5.0-16.0)
14(5.5-15.3)
16 (5.0-18.0)
EER Rated / Partload see*3 COP
2.73 785 3.21
2.97 1,055 3.33
2.69/3.431,255 3.31
2.67/3.261,415
3.50
Dimensions
Width (mm)
Ÿ Capacities stated are based
Function
Cooling
Heating
Heating 3.25 Cooling
Heating
Cooling
PUH
Input
kW
2.48 Cooling
2.51
4.42 690 Heating
4.07
5.03
4.51
Power supply
Single phase, 50Hz, 220-240V
Depth (mm)
690
690
690 3.2
Ÿ
on
indoor
unit
connected
to
Capacity Rated (min-max)
kW 3
7.1 (3.3-8.1) 8.4(3.5-10.2) 10 (4.9-11.4) 11.2(4.5-14.0) 12.5(5.5-14.0) 14(5.0-16.0)
14(5.5-15.3)
16(5.0-18.0)
Weight
kg
Airflow
(Lo-Hi) Partload see
L/S
367-450
450-567
567-700
800-1000
46
59
72 3.33
76
EER Rated/
2.73
2.69/3.43
3.31
2.67/3.26
3.50
COP
PUHZ-RP
series outdoor units
Input
kW
2.48
2.51
3.253.21
3.2 2.97 4.42
4.07
5.03
4.51
Ext static pressure
Pa
125
supply
Single
220-240V3.50
EER Rated / Partload Power
see*3 COP
2.73
3.21
2.97
3.33
2.69/3.43
3.31phase, 50Hz,
2.67/3.26
Sound pressure level
dB(A)
52-55
54-58
51-55
Power supply
220-240V
Airflow (Lo-Hi)
L/S
367-450 428 Single phase, 50Hz,
450-567
567-700
800-1000
Height (mm)
428
428
428
Airflow (Lo-Hi)
L/S
367-450
450-567
567-700
800-1000
Dimensions
Width (mm)
785
1,055
1,255
1,415
Ext
static
pressure
Pa
125
Ext static pressure
Pa
125
Depth
(mm)
690
690
690
690
Sound pressure level dB(A) dB(A)
52-55
54-58
51-55
Sound
52-55
54-58
51-55
Weight pressure level
kg
46
59
72
76
Height (mm)
428
428
428
Height (mm)
428
428 428
428
428
Outdoor unit
PUHZ-RP71VHA2
PUHZ-RP100V/YHA2
PUHZ-RP125V/YHA2
PUHZ-RP140V/YHA2
Dimensions
Width
(mm)
785
1,055
1,255
1,415
Munsell 3.0Y
7.8/1.1
Dimensions External finish
Width (mm)
785
1,055
1,255
1,415
690
690 50Hz, 220-240v Y: Three690
690
Power supply Depth (mm)
V: Single phase,
phase, 50Hz, 380-415V
Depth (mm) 1.6
690
690 2.4
690
690
Weight
kg
46
59
72
76
Compressor output
kW
1.9
3.9
Weight
kg
46
59
72
76
Airflow
L/S
920
1000
1170
Sound pressure level (dB)
Cooling mode
47
50
52
54
Outdoor unit
PUHZ-RP71VHA2
PUHZ-RP100V/YHA2
PUHZ-RP125V/YHA2
PUHZ-RP140V/YHA2
Silent mode
44
47
49
51
External finish Heating mode
Munsell 3.0Y 7.8/1.155
48
54
56
Power supply dB(A)
V: Single phase,
phase, 50Hz, 380-415V
Sound power level
66
70 50Hz, 220-240v Y: Three 72
74
Compressor output
kW
1.6
1.9
2.4
3.9
Height
(mm)
1350
943
Outdoor unit
PUHZ-RP71VHA2
PUHZ-RP100V/YHA2
PUHZ-RP125V/YHA2
PUHZ-RP140V/YHA2
Airflow
L/S (mm)
920
1000
1170
Dimensions
Width
950
External finish
Munsell 3.0Y 7.8/1.1
Sound pressure level (dB)
Cooling(mm)
mode
47
50
52
54
Depth
330+30
Power supply
V: Single phase, 50Hz, 220-240v Y: Three phase, 50Hz, 380-415V
Silent mode
44
47
49
51
Weight
kg
75
121
116
116
Outdoor unit
PUHZ-RP71VHA2
PUHZ-RP100V/YHA2
PUHZ-RP125V/YHA2
PUHZ-RP140V/YHA2
Compressor
output
kW
1.6
1.9
2.4
3.9
Heating
mode
48
54
55
56
Chargeless piping length
m
30
30
Airflow
L/S
920
1000
1170
finish
Munsell
3.0Y 7.8/1.1
Sound
power
level External
dB(A)
66
70
7275
74
Max
piping
length
m
50
Sound pressure level (dB)
Cooling mode
47
50
52
54
Height
(mm)
1350
943
Protection device
Discharge
thermo,
HP switch
Power Silent
supply
V: Single
phase,
50Hz, 220-240v Y: Three51phase, 50Hz, 380-415V
mode
44
47
49
Dimensions
Width (mm)
950
Rated
running current
Amps
8.04/9.74
V:1.6
12.53/12.39 Y:4.08/4.03
V:
15.53/15.98
V: 19.65/19.92
Y:6.37/6.46
Compressor
output
kW
1.9 55 Y:5.04/5.20
2.4
3.9
Heating mode
48
54
56
Depth (mm)
330+30 V:32 Y:16
Breaker size
Amps
25
V:32 Y:16
V:40 Y:16
Sound
power level
dB(A)
66
70
72
74
Airflow
L/S
920
1000 116
1170
Weight
kg
75
121
116
Height (mm)
1350
943
Sound pressure
level (dB)
Cooling mode 30
47
50
52
54
Chargeless
piping length
m
30
Dimensions
Width (mm)
950
Max piping length
m
75
Silent mode 50
44
49
51
Depth (mm)
330+3047
Protection device
Discharge thermo, HP switch
Weight
kg
75
121
116
Heating mode
48
54 116
55
56
Rated running current
Amps
8.04/9.74
V: 12.53/12.39 Y:4.08/4.03
V: 15.53/15.98 Y:5.04/5.20
V: 19.65/19.92 Y:6.37/6.46
Chargeless
piping level
length
m
30
Soundsize
power
66 V:32 Y:16
70V:32 30
74
Breaker
Amps dB(A)
25
Y:16
V:40 72
Y:16
Max piping length
m
50
75
Height (mm)
1350
943
Protection device
Discharge thermo, HP switch
Dimensions
950
Rated
running current
Amps Width (mm) 8.04/9.74
V: 12.53/12.39 Y:4.08/4.03
V: 15.53/15.98 Y:5.04/5.20
V: 19.65/19.92 Y:6.37/6.46
Breaker size
Amps Depth (mm)
25
V:32 Y:16
V:32 Y:16
330+30 V:40 Y:16
Compact Inverter – Outdoor units
Power Inverter – Indoor units
*
Power Inverter – Outdoor units
Weight
Chargeless piping length
Max piping length
Protection device
Rated running current
Breaker size
kg
m
m
75
30
50
Amps
Amps
8.04/9.74
25
Guaranteed
Operating
Range
121
116
30
75
Discharge thermo, HP switch
V: 12.53/12.39 Y:4.08/4.03
V: 15.53/15.98 Y:5.04/5.20
V:32 Y:16
V:32 Y:16
SUZ-KA
with AS/NZS 3823.2:2005 Clause 3.4 (Amdt1).
PUHZ-RP/BP
50/60/71
all
46°C
43°C
46°C
10°C
15°C
24°C
24°C
the optional air outlet guide, the operation at 15°C outdoor temperature is possible.
3 Complies
V: 19.65/19.92 Y:6.37/6.46
V:40 Y:16
25/35
15°C
1 With
116
10°C
2
11°C for PUHZ-RP71.
5°C ( 15°C
21°C
20°C
2
1)
Concealed Bulkhead.
Ideal for apartments or offices where ceiling access is not available for ducting,
the ceiling concealed model compresses installation space to just 270 mm in height
with the KA series and an even smaller 200mm when using the new KD series.
The KD series offers a number of improvements on the KA series including higher
static pressure (50Pa) that allows it to be ducted to a limited number of outlets and
the choice of hard wired control panel (VA) or infra red remote control (VAL).
Whisper Quiet Operation
When operating at full capacity the Bulkhead Unit generates just 28dB of sound,
so other than feeling the benefit of the even temperature that it delivers, you would
hardly know that it is operating.
¬Noise level
Train interior
Quiet passenger
car interior
(40km/h)
Library interior
80dB
60dB
40dB
Human
Sound of
hearing limits
rustling leaves (Extremely quiet)
10dB
SEZ-KA35/50/60/71VA
SPECIFICA
TIONS: BULKHEAD INVERTER TYPE
Specification
Chart Concealed Bulkhead
Indoor unit
TIONS:
BULKHEAD
INVERTER TYPE
Outdoor
unit
Function
Capacity (min-max) Indoor unit
kW
Outdoor unit kW
Input
Function
EER Rated
COP
Capacity (min-max)
kW
Input
kW
EER Rated
COP
SEZ-KA35VA
SUZ-KA35VA
Cooling
Heating
SEZ-KA35VA0.9 - 5.0
1.0 - 3.9
SUZ-KA35VA 1.1
1.06
Cooling
Heating
3.33
3.65
1.0 - 3.9
0.9 - 5.0
1.06
1.1
3.33
3.65
SPECIFICA
Indoor unit
Power supply
SEZ-KA35VA
Airflow (Lo-Hi)
Ext static pressure Indoor unit
Power supply
Sound pressure level
Airflow (Lo-Hi)
Ext static pressure
Dimensions
Sound pressure level
167-217
SEZ-KA35VA
L/S
Pa
dB(A)
L/S
Height
(mm)
Pa
Width
(mm)
dB(A) (mm)
Depth
Height (mm)
W eight
kg
Dimensions
Width (mm)
Indoor unit*1 Depth (mm)
W eight
Outdoor unit kg
Function
Capacity (min-max) Indoor unit*1 kW
Outdoor unit kW
Input
Function
EER Rated
COP
Capacity (min-max)
kW
Input
kW
EER Rated
COP
Indoor unit*1
SEZ-KA50VA
SUZ-KA50VA
Cooling
Heating
SEZ-KA50VA1.1 - 7.2
1.1- 5.6
1.78SUZ-KA50VA 1.84
Cooling
Heating
2.76
3.21
1.1- 5.6
1.1 - 7.2
1.78
1.84
2.76
3.21
Picture
SEZ-KA50VA
Single phase, 50Hz, 220-240V
Picture
200-283
SEZ-KA50VA
Standard:
30, Max: 50
Single phase,31-39
50Hz, 220-240V
200-283
270
Standard: 30, Max: 50 1,100
31-39
700
270
33.5
1,100
700
SEZ-KD50VA
33.5
SUZ-KA50VA
30-35
167-217
30-35
SEZ-KD25VA
SUZ-KA25VA
Cooling
Heating
0.9 SEZ-KD25VA
- 3.2
0.9 - 4.5
SUZ-KA25VA0.83
0.778
Cooling
Heating
3.12
3.47
0.9 - 3.2
0.9 - 4.5
0.778
0.83
3.12
3.47
SEZ-KD35VA
SUZ-KA35VA
Cooling
Heating
SEZ-KD35VA0.9 - 5.0
1.0 - 3.9
SUZ-KA35VA 1.108
1.09
Cooling
Heating
3.06
3.43
1.0 - 3.9
0.9 - 5.0
1.09
1.108
3.06
3.43
SEZ-KD25VA/VAL
Ext static pressure
Indoor unit*1
Power supply
Sound pressure level
Airflow (Lo-Med-Hi)
(Low-Mid-High)
Ext static pressure
Sound pressure level
Dimensions
(Low-Mid-High)
W eight
Dimensions
W eight
SEZ-KA60VA
SEZ-KD35VA/VAL
SEZ-KA71VA
SUZ-KA71VA
Cooling
Heating
0.9 SEZ-KA71VA
- 8.3
0.9 - 10.4
SUZ-KA71VA2.36
2.46
Cooling
Heating
2.89
3.38
0.9 - 8.3
0.9 - 10.4
2.46
2.36
2.89
3.38
SEZ-KA71VA
200-333
SEZ-KA60VA
SEZ-KA71VA
32-43
200-333
32-43
35
SEZ-KD60VA
SUZ-KA61VA
Cooling
Heating
SEZ-KD60VA 0.9 - 8.0
1.1 - 6.3
1.89SUZ-KA61VA 2.05
Cooling
Heating
2.81
3.25
1.1 - 6.3
0.9 - 8.0
1.89
2.05
2.81
3.25
Cooling
Heating
SEZ-KD50VA1.1 - 7.2
1.1- 5.6
1.78SUZ-KA50VA 1.87
Cooling
Heating
2.72
3.07
1.1- 5.6
1.1 - 7.2
1.78
1.87
2.72
3.07
SEZ-KD50VA/VAL
Power supply
Airflow (Lo-Med-Hi)
SEZ-KA60VA
SUZ-KA61VA
Cooling
Heating
SEZ-KA60VA 0.9 - 8.0
1.1 - 6.3
1.96SUZ-KA61VA 2.45
Cooling
Heating
2.76
2.77
1.1 - 6.3
0.9 - 8.0
1.96
2.45
2.76
2.77
SEZ-KD71VA
35
SUZ-KA71VA
Cooling
Heating
0.9 SEZ-KD71VA
- 8.3
0.9 - 10.4
SUZ-KA71VA2.37
2.53
Cooling
Heating
2.77
3.29
0.9 - 8.3
0.9 - 10.4
2.53
2.37
2.77
3.29
SEZ-KD60VA/VAL
SEZ-KD71VA/VAL
200-250-300
SEZ-KD60VA/VAL
200-266-333
SEZ-KD71VA/VAL
Single phase, 50Hz, 220-240V
L/S
Pa
92-1 16-150
SEZ-KD25VA/VAL
dB(A)
L/S
116-150-183
SEZ-KD35VA/VAL
23-26-30
92-1 16-150
Pa
Height (mm)
dB(A)
Width (mm)
200
23-26-30
700
Depth (mm)
Height (mm)
kg
Width (mm)
700
200
18
700
Depth (mm)
700
kg
166-208-250
SEZ-KD50VA/VAL
5-15-35-50
Single phase, 50Hz, 220-240V
30-34-37
166-208-250
23-28-33
116-150-183
23-28-33
21
200
900
700
200
900
30-34-38
200-250-300
5-15-35-50
30-34-37
30-34-38
21
200
1,100
30-35-40
700
200
27
1,100
23
700
18
30-35-40
200-266-333
700
23
27
Specification Chart Outdoor Bulkhead Units
Outdoor unit
External finish
Power supply
Compressor output Outdoor unit
External finish
Airflow
Power supply
Sound pressure level
Compressor output
Airflow power level
Sound
Sound pressure level
Dimensions
Sound power level
W eight
Dimensions piping length
Chargeless
Max piping length
W eight size
Breaker
Chargeless piping length
Max piping length
Breaker size
SUZ-KA25VA
kW
L/S
Cooling mode
kW
Heating
mode
L/S
dB(A)
Cooling(mm)
mode
Height
Heating
mode
Width
(mm)
dB(A) (mm)
Depth
Height (mm)
kg
Width (mm)
m
Depth (mm)
m
kg
Amps
m
m
Amps
SUZ-KA25VA
0.55
568/534
46
0.55
46
568/534
59
46
46
59
1
SEZ-KD models available with wireless remote controller.
2
Complies with AS/NZS 3823.2:2005 Clause 3.4 (Amdt1).
33
33
SUZ-KA35VA
550
800
285
550
800
285
20
10
SUZ-KA50VA
Munsell 3Y 7.8/1.1
Single phase, 50Hz, 220-240V
SUZ-KA35VA
SUZ-KA50VA
0.65
Munsell 3Y 7.8/1.1
551
Single phase, 50Hz, 220-240V
47
0.65
48
551
61
47
48
61
37
0.85
818
0.85
818
53
7
37
53
SUZ-KA61VA
SUZ-KA71VA
SUZ-KA61VA
SUZ-KA71VA
1.3
53
55
68
53
850
55
840
68
330
850
840
330
30
20
7
20
10
30
20
1.3
58
58
hange
ontrol.
.can change
OFF control.
ar day.
Economical
onomical
&
&Space saving
Relay box (to be purchased locally)
D
Air conditioner can be started/
stopped remotely. In addition, the
ON/OFF by local remote controller
can be prohibited/permitted.
Relay box (to be purchased locally)
Adapter for
remote
ON/OFF
Indoor CN32
Controlling your comfort is easy in
anyone’s Elanguage. Operation Lock
Remote
control
panel
Remote
control
panel
Wired remote
controller
(Example of 1 : 1 system x 2)
PAR-SL97A-E
(Example of 1 : 1 system x 2)
Relay box (to be purchased locally)
Our new state of the art Controller allows you to get the most
out of your Mitsubishi Electric Ducted Air Conditioning System.
To aid communication in today’s multicultural society,
the control can be switched to 8 different languages.
Operation othe
(adjustment of
speed, and air
example) can
when remote
is prohibited.
Timer control i
external timer.
Adapter for
remote
ON/OFF
Relay box (to be purchased locally)
Adapter for
remote
ON/OFF
Operation othe
(adjustment of
speed, and air
example) can
when remote
is prohibited.
Timer control i
external timer.
Adapter for
remote
ON/OFF
The operation of all buttons on the control can be locked
with the exception of the On/Off button.
Indoor CN51
This
stops little children or any Remote
unauthorised person
Remote
control
control
changing
temperatures
or settings
panel
Wired remote
panel that may in turn
PAR-SL97A-E
controller
waste valuable
energy and increase
running
costs.
2007_SLIM_Aus
07.8.8
1:46
PM
ページ
21
(Example
of 1 : 1 system x 2) 07.8.8
(Example
1 : 1 system
x 2)
2007_SLIM_Aus
1:46ofPM
ページ
21
New Weekly Timer
English
Spanish
French
Russian
F
Operation/eme
Remote operation adapter
Italian
German
Chinese
Japanese
Operating status can be
displayed at a distant place.
The Weekly Timer allows you to programme the unit with
be received at
up to 8 different automatic On/Off and Temperature changes (no-voltage sig
per day, 7 days in advance, which means your home or office
can be at the optimum temperature whenever required.
Indoor CN51
CN51
Remote
Versatility
Is TheIndoor
Key
To Comfort
Control
Remote
display
display
Easy To Read Display
The large type in the dot Liquid Crystal Display allows the
status of your system to be viewed at a glance, day or night.
While most remote controls can be confusing our control
G to be more user friendly.
has been specifically designed
Allows
ON/OFF
with timer
The Slimline styling has been
designed
to fit unobtrusively
*For the control by external
with any décor. The only visible
buttons
are
those
most
timer, refer to D Operation
frequently used: On/Off and Control
Temperature
Up/Down.
by Level Signal.
panel
panel
((P
Controls
system contro
PAR-SL97A-E
To allow youPAR-21
climate System
control of your
home
or office
number of)) Versatile
System
Controls
PaSeries
Series
Versatile system contro
MAA-G
Control System options are available. Three of the most popular are:
A
A either fixed or Infra red,
• Multiple Control Units,
Standard System
Standard
System each of which
positioned in different rooms,
can control your system.
• Multiple Systems controlled by their individual
PAR-21MAA
Control Units or via one Central System
B
B be operated locally or
Control
can
(Example which
of 1 : 1 system)
With 2 remote controllers, control
With 2 the
remote
controllers,
control
“dialled into” through
World
Wide
can be performed
locally
andWeb,
can be performed locally and
remotely
from 2system
spots.
allowing you control
of your
remotely
from 2 spots. from
anywhere in the world.
H
Energy Saving Control
Limiting the set temperature range
Setting upper and lower temperature limits prevents the unit
from excessive heating and cooling, thereby saving energy
further and reducing your power bill.
I
26
Busy
time frame
time frame
higher temperature
25
26
24
6
Opening
time
Busy
time frame
1
25
23
24
Opening time
Setting to
lower temperature
2
1
3
5
Lunch time
22
Setting to
higher temperature
6
Lunch time
3
4
2
23
Less busy
time frame
4
10
10 12
12
14
16
14
18
Centralized rem
connected to e
interface.
centralized
rem
remote
ON/OFF
ON/OFF
Conventional inspection work
Indoor unit
Outdoor unit
LOSSNAY operation cable
Measure
the intake air
temperature
Measure the discharge
temperature
Remove the
service panel
5
24 (Hr.)
FF
ON/OFF
Remote
Remote
display
display
panel
panel
Indoor unit
(Example of 1 : 1 system)
of 1 : 1 system)
Intake(Example
air
temperature (˚C)
Number of ON/OFF
Discharge
5
times (x10 times) Allows ON/OFF
temperature
(˚C)
with
timer
8
Heat exchanger
temperature (˚C)
Operating
current (A)
9
Filter operating
time* (Hours)
2
G
G
4
Heat exchanger
temperature (˚C)
Allows ON/OFF with timer
*For
control
*For the
theOutdoor
control by
by external
external
timer,
to
6 refer
timer,
refer
to D
D Operation
Operation
temperature
(˚C)
Control
by
Level
Signal.
Control by Level Signal.
*The filter operating time is the time elapsed since the filter was reset.
*Based on our internal calculation
Indoor CN51
Indoor CN51
PAR-21
PAR-21
MAA-G
MAA-G
7
Accumulated operating
time (x10 hours)
3
*Based on our internal calculation
Outdoor unit
1
*Result of cooperative
study withstudy
Japan Facility
Solution Co,
Ltd.
*Result
of cooperative
with Japan
Facility
Solution Co, Ltd.
ce saving
controller
Wired remote
TEMP.
22
Re
LOSSNAY can
Re
co
Wired remote
indoor
unit. paco
Wired remote
pa
controller
Remote
control
control
panel
panel
Operating
Operating status
status can
can be
be
(Example of 1 : 1 system)
displayed
displayed at
at aa distant
distant place.
place.
7 Closing time
Dinner time
24 (Hr.)20
Indoor CN51
Indoor CN51
Discharge
controller temperature 64˚C
Easy maintenance information
22 18
Measure the outdoor air
Remotetemperature
(Example of 1 : 1 system x 2)
(Example of 1 : 1 system x 2)
LOSSNAY
Compressor
16
20
(Ex
Relay box (to be purchased locally)
Relay box (to be purchased locally)
Adapter for
Adapter for
remote
remote
ON/OFF
ON/OFF
Your System Control
also give
you
a complete
Aircan
conditioner
can be
started/
Air conditioner
can be started/
MAC-821SC-E
stopped remotely. In addition, the
Indoor CN32
stopped remotely.
In indoor
addition, and
the outdoor units
diagnostic on the condition
of
your
Indoor CN32
Remote
Re
ON/OFF by local remote controller
Remote
Re
ON/OFF by local remote controller
control
co
Individual
ON/
can be prohibited/permitted.
control
co
at the touch of a button,
which
means
you
can
be
sure
panel
Wired remote
pa
can be prohibited/permitted.
panel
Wired remote
pa
controller
OFF
at
a
time
controller
that your system is operating efficiently at all times. (Example
of 1 : 1 system x 2)
con
(Example of 1 : 1centralized
system x 2)
Indoor unit
In turn if any future service workMAC-397IF-E
is required,
ON/OFF
s
Relay box (to beThe
purchased
locally)
Relay box (to be purchased locally)
Outdoor unit
be confirmed
b
Adapter for
fault diagnostic
timeE
Eis drastically reduced.
Adapter for
remote
22
0
0
(
(
Mounting the
connection to
allows
MELAN
MAC-397IF-E*
MAC-397IF-E*
connection.
Easy Maintenance
D
D Function
Closing time
Dinner time
(Example of 1 : 1 system)
(Example of 1 : 1 system)
(Example of 1 : 1 system x 2)
New improved method
7
* Set "Main"
and "Sub"timer and
*Simple
* remote
Set "Main"
and "Sub"
controllers.
remote controllers.
cannot be used a
One remote controller can control
One remote controller can control
plural air conditioners simultaneously
plural air conditioners simultaneously
under a same setting.
PAR-21MAAcentral
Allows
under a same setting.
M-NET adapter
PAR-21MAA
* The setting of the refrigerant
addPAC-SF80MA-E
MELANS.
* The setting of the refrigerant
address
is
required
for
outdoor
unit.
(Connection
with M-NET
system)unit.
ress is required
for outdoor
(Ex
(Example of 1 : 1 system x 2)
Centralized remote
controller G-50, etc.
LOSSNAY can be controlled
with remote
controller
Less busy
Setting to
Setting to
lower temperature
Weekly timer
ON/OFF and u
temperatures
calendar day. (
PAR-21MAA
Simple timer:
PAR-21MAA
ON/OFF can b(E
(Example of 1 : 1 system)
(Example of 1 within
: 1 system)
(
72 hr. in
Auto-off time
Operation will
after elapsing
Set time can b
PAR-21MAA
30 min. to 4 hr
PAR-21MAA
C
C
Power supply unit
Centralized control of
Total Control At Your Fingertips
dispersed air conditioning
equipment allows effective
Simply open the front panel and total
monitoring/controlling.
control of your comfort is there at the
touch of a button. From temperature
control to automatic stop/start
Up on
to 8a indoor units can be
daily or weekly basis, it’s all switched
there at ON/OFF with one
remote controller.
your fingertips.
(Example of Simultaneous Twin)
(Example of 1 : 1 system)
• Locating the System Control Unit in a central position,
typically near the return air grille.
PAR-21MAA
PAR-21MAA
(Example of 1 : 1 system)
(Example of 1 : 1 system)
(
(
Warm, even heat in winter and cool fresh
air in summer is only a phone call or
click away.
Simply contact your nearest Mitsubishi Electric Specialist today and you can find out all there is to know about
how to enhance your living environment. Our Specialists are fully qualified to give you all the right advice on which
Mitsubishi Electric Ducted Air Conditioning System is right for you.
To locate your nearest Mitsubishi Electric Specialist go to our website
www.mitsubishielectric.com.au
EP
IE
NC
DARD
AN
NT
P L I A NC
ST
M
E
M
C O EFF
IC
S
�
MINIM U
All Mitsubishi Electric Compact and Power Inverter Systems are MEPS (Minimum Efficiency
Performance Standard) Compliant, so you can be sure that they will give you the performance
and efficiency that they were designed to deliver.
M
They will determine whether a Compact Inverter System or a Power Inverter System best suits your needs,
both in comfort and efficiency. You can either visit one of our Specialist’s Showrooms, or they will happily arrange
for one of their Consultants to come to your home.
Y PERFORM
A
MITSUBISHI ELECTRIC AUSTRALIA PTY LTD.
www.mitsubishielectric.com.au (Incorporated in New South Wales)
ABN 58 001 215 792
New South Wales
348 Victoria Road
Rydalmere NSW 2116
Phone 02 9684 7555
Fax 02 9898 1043
Queensland/Northern Territory
Unit 12, 469 Nudgee Road
Hendra QLD 4011
Phone 07 3623 2000
Fax 07 3630 1888
South Australia
77 Port Road
Hindmarsh SA 5007
Phone 08 8340 2000
Fax 08 8340 0555
Victoria/Tasmania
Suite 28
Omnico Business Park
270 Ferntree Gully Road
Notting Hill vic 3168
Phone 03 9535 7800
Fax 03 9535 7801
North QLD - Townsville
Mitsubishi Electric Office
Phone 07 4728 5223
Fax 07 4728 5102
Capricorn Air
13 Mackley Street
Garbutt QLD 4814
Phone 07 4775 5222
Fax 07 4775 5305
Western Australia
Unit 5, 329 Collier Road
Bassendean WA 6054
Phone 08 9377 3400
Fax 08 9377 3499
Head Office Tokyo Building 2-7-3 Marunouchi, Chiyoda-Ku 100-8310, Japan
Mitsubishi Electric Shizuoka Works acquired ISO9001 certification under Series
9000 of the International Standard Organisation (ISO) based on a review of Quality
warranties for the production of air conditioning equipment. The plant also acquired
environmental management system standard ISO 14001 certification.
Publication effective August 2008. Specifications subject to change without notice. Printed in Australia.