TopMaster Air Handling Unit

Transcription

TopMaster Air Handling Unit
TopMaster Air Handling Unit
Control and Regulation Equipment
TopMaster Air Handling unit
CONTROL AND REGULATION EQUIPMENT
Contents
Electrical connection
Electrical cabinet.......................................................... 3
Electrical connection and fuse protection................. 3
Sensors and accessories
Sensors and accessories............................................... 4
Temperature sensor .................................................... 5
Damper actuator.......................................................... 5
Water heater ................................................................. 6
Liquid cooling ............................................................. 6
Electrical heater............................................................ 6
DX -cooling .................................................................. 6
Valve actuator and
valve for heating and cooling..................................... 7
Connection of external components.......................... 8
Installation and connection
Installation of control panel..............................................9
User instructions
General, general buttons and symbols..........................10
Home screen......................................................................11
Basic operation, overview...............................................12
Submenus..........................................................................13
Settings
Configuring time, date and language ..........................14
Installers and service personnel.....................................15
Login..................................................................................15
Commissioning Wizard
Commissioning of fan speeds........................................16
Schedules
Schedules...........................................................................17
Control and regulation functions
Control and regulation functions...................................20
Parameter list
Parameter list....................................................................23
Fläkt Woods
8217 GB 2014.07.022
Specifications are subject to alteration without notice
TopMaster Air Handling unit
CONTROL AND REGULATION EQUIPMENT
Electrical cabinet – Electrical connection and
fuse protection
Electrical connection and fuse protection
Electrical cabinet
Electrical connection is made to the terminals in the ectrical cabinet. A separate switch -disconnector must be
used, e. g. RDTZ-89-016.
1
Fuse protection
The fuse protects the unit’s incoming supply:
Size 030 rated at 10 AT,
Size 050 rated at 16 AT.
Fuse protection for DX -cooling is carried out separately.
2
Feed
3 x 400 V for units with electric coil.
1 x 230 V for units with water coil, phase connected to
terminal L1.
3
4
5
1. Connection incoming supply
2. Control card
3. Condenser, rotor
4. Fuses
5.Transformer, 230 V/24 V
Fläkt Woods
8217 GB 2014.07.023
Specifications are subject to alteration without notice
TopMaster Air Handling unit
CONTROL AND REGULATION EQUIPMENT
Sensors and accessories
Sensors and accessories
All sensors and accessories are connected to TopMaster
via connections in the electrical cabinet. Cables to external components are secured in the electrical cabinet using
the tie-rail with a cable tie, for example.. The cable is then
placed against the cellular plastic strip on the unit (see
figure 1).
When all cables are connected to terminals and the
cables are secured on the tie rail, the cover is positioned
on the electrical cabinet and secured using the appropriate screws (see figure 2). The cellular plastic, which is
semi-elastic, will slowly adapt to the shape of the cables
and in doing so the lead-through will seal (see figure 3).
Information about how the different sensors and
accessories should be fitted and connected is provided in
the following section.
Figure 1. T
he cables are secured on the tie rail using a cable tie and
placed against the cellular plastic strip on the unit.
Figure 2. W
hen the cables are connected to the terminals and then
secured to the tie rail, the cover is fitted on the electrical
cabinet.
Figure 3. T
he semi-elastic cellular plastic slowly adapts itself to the
shape of the cables and the lead-through seals.
Fläkt Woods
8217 GB 2014.07.024
Specifications are subject to alteration without notice
TopMaster Air Handling unit
CONTROL AND REGULATION EQUIPMENT
Sensors and accessories
Temperature sensors
The TopMaster is equipped as standard with three factorymounted temperature sensors:
Supply air sensor GT1
Positioned at the supply air inlet connection spigot.
Outdoor air sensor GT3
Positioned at the outdoor air inlet spigot.
Extract air sensor GT12
Positioned at the extract air inlet connection spigot.
Filter monitors (accessories)
The filter monitors GP1 and GP2 are enclosed separately.
Connect hose to test point. Set the required alarm limit
across the filter using the knob on the sensor. For installation, see enclosed instruction.
Air flow monitors (accessories)
The air flow monitors GP1 and GP2 are enclosed separately. For installation, see enclosed instruction. Connect
hose to test point. Air flow monitors cannot be combined
with filter monitors.
Damper with actuator (accessory)
2 positions with spring return, 15 Nm, 24 VAC.
Other sensors:
Room temperature sensor GT2
Damper with mounted actuator is delivered separately.
Included when room control is selected, and then replaces extract air sensor GT12. It is intended for placement
Timer, prolonged, forced mode
on an inner wall. The sensor should be placed in an
area with good air circulation and it should not be exposed to direct sunlight. It is delivered loose without
any cable.
Any timers are enclosed separately. When the push button is used the internal timer in the controller must be set
to the required time.
Function of control inputs Timer 1 (T1) and Timer 2
(T2) can be selected according to the following table.
Freeze-protection sensor GT5
Included as standard when the unit is equipped with
heat water coil. To be mounted on the heater’s return
line.
Note! If a cooling coil is mounted in
the duct, the supply air sensor must
be moved from the unit into the duct,
and placed after the coil.
Timer Function 1
Manual/Automatic Mode
Trickle
Normal
Boost
Timer 1
0
1
0
1
Timer 2
0
0
1
1
Timer Function 2 (default)
Manual/Automatic Mode
Trickle
Boost
Stop
Timer 1
0
1
0
1
Timer 2
0
0
1
1
Timer Function 3
Manual/Automatic Mode
Normal
Boost
Stop
Timer 1
0
1
0
1
Timer 2
0
0
1
1
Timer Function 4
Stop
Manual/Automatic Mode
Stop
Boost
Timer 1
0
1
0
1
Timer 2
0
0
1
1
Timer Function 5
Stop
Manual/Automatic Mode
Stop
Normal
Fläkt Woods
8217 GB 2014.07.025
Timer 1
Timer 2
0
0
1
0
0 1
1
1
Specifications are subject to alteration without notice
TopMaster Air Handling unit
CONTROL AND REGULATION EQUIPMENT
Sensors and accessories
Rotor pressure switch
Rotor pressure switch (GP7) for defrosting, factory -mounted.
Water heater
Circulation pump (CP1) and valve actuator (SV1) for water heating is connected as in the table below. If the pump
motor does not have an integrated alarm unit, the motor
protection can be used to receive an alarm signal.
Component
Terminal
Connection Comments
Circulation
CP1 Start C-N-PE
pump CP1
Pump supply
(230 VAC max 2A*)
CP1 Start N0 - L1
Clamp at circulation
pump
CP1 Alarm NO - C
34 - 35
Potential-free alarm
input, supplied design
as NO, can be
configured
Valve actuator SV1 Control Y-M-G- GO
38 -39-40-41
*) T
otal power consumption for cooling
and heating may amount to max 2 A
Circulation pump (CP2) and valve actuators (SV2) for
liquid cooling mode are connected as shown in the table
below. If the pump motor does not have built-in alarm
device, motor protection is used to obtain an alarm signal.
Terminal
If an electric heater has been ordered, this is connected
when supplied. The electric coil is factory mounted.
DX-cooling
The Curo™ control system is able to control DX -cooling,
1-stage. Note! DX -coil is not a part of the unit delivery.
For setup, see chapter on Control and Regulation functions. Electrical connection is as shown in the following
table.
ComponentFunction Terminal Connection Design
specification
1-stageStart
CP2 Start C-NO
DX -cooling
cooling
Start: 10%,
Stop: 0%
Alarm
CP2 Alarm NO - C
36 - 37
NO
Fire protection function
External fire alarm can be connected to terminal in electrical cabinet to stop the unit.
Alarm output
Liquid cooling
Component
Electric heater
Potential-free connection, max. load 24 V, 200 mA.
TopMaster has a total alarm output which can be selected, allowing you to indicate just A alarms or both A and
B alarms.
Connection Comments
CirculationCP2 Start C-N-PE
pump CP2
Pump supply
(230 VAC max 2A*)
CP2 Start N0 - L1
Clamp at circulation
pump
CP2 Alarm NO - C
36 - 37
Potential-free alarm
input, supplied design as NO, can be
configured
Valve actuator SV1 Control Y-M-G- GO
42 -43-44-45
*) T
otal power consumption for cooling
and heating may amount to max 2 A
Note!
If a cooling coil is mounted in the
duct, the supply air sensor must be moved
from the unit into the duct, and placed
after the coil.
Fläkt Woods
8217 GB 2014.07.026
Specifications are subject to alteration without notice
TopMaster Air Handling unit
CONTROL AND REGULATION EQUIPMENT
Sensors and accessories
Valve actuator for heating SV1 and
cooling SV2
Connected to terminal in electrical cabinet. Stroke length
5.5 mm. Intended for assembly on 2-way and 3-way
valves of the type VVG44 or VXG44.
3-way valve VXG
The bypass is closed by turning the spindle inwards, the
bypass is opened by turning the spindle outwards.
Accepted installation method
Accepted installation method
Valve for heating and cooling
When installing a 3-port valve check as follows:
The valve and valve actuator can be easily installed with­
out special tools. A particle filter should be fitted before
the valve to extend its service life.
Mixture from A/B to AB
2-way valve VVG
Distribution from AB to A/B
The flow is increased by turning the spindle inwards, the
flow is reduced by moving the spindle outwards.
Note that the two-way valve cannot be used as a threeway valve.
The flow direction in the valve is indicated by the arrow.
Accepted installation method
Fläkt Woods
8217 GB 2014.07.027
Specifications are subject to alteration without notice
TopMaster Air Handling unit
CONTROL AND REGULATION EQUIPMENT
Sensors and accessories
Connection of external components
10
1
2
3 4 5 6 7 8 9
12
11
14
13
1. CP1/SK1 Start
2. CP2/DX Start
3. CO2
4. ST1
5. ALM, Alarm output, max 24 V, 200 mA
6. Fire, Fire alarm
7. TMR1, Timer input 1
8. TMR2, Timer input 2
9. CP1, alarm heating
10.CP2, alarm cooling
11. SV1 CTRL, control signal heating
12. SV2 CTRL, control signal cooling
13.GT1
14.GT3
15. SK1 Supply, supply electric coil
16. TF Supply
17. FF Supply
18.GP3
19.GP4
20.GT5
21.GT2
22.GS1
23.GP7
24.GP1
25.GP2
26. MODB, Modbus RS485
27. TF CTRL, control signal supply air fan
28. FF CTRL, control signal extract air fan
16
15
18
17
Fläkt Woods
20
19
22
21
24
23
25
26
28
27
8217 GB 2014.07.028
Specifications are subject to alteration without notice
TopMaster Air Handling unit
CONTROL AND REGULATION EQUIPMENT
Installation and connection
1. Open the control panel using a screwdriver
5. Connect the cable to the back of the display as shown
above. Note. Please do not touch the electronics.
Note!
The control panel is only for indoor use.
2. Lift the display out of the enclosure.
3. Push the connection cable through a suitable hole and
if needed make an outlet for the cable in the side of the
cover.
4.Mount the enclosure directly on the wall or using
screws in a junction box. Push back the display in the
enclosure.
Fläkt Woods
8217 GB 2014.07.029
Specifications are subject to alteration without notice
TopMaster Air Handling unit
CONTROL AND REGULATION EQUIPMENT
General, general buttons and symbols
General
General buttons and symbols
This section of the instructions provides an introduction on how the Curo™ touch control panel works and
it is intended to supplement the instructions for the air
handling unit.
The control panel is provided with a touch display. To
navigate the menus, use either your finger or the back of
a pen.
When power is switched on all the menus are loaded
up, which takes about 20–30 seconds. Then the panel displays the Home screen.
The following buttons and symbols are universal and
available on many menu pages.
Home key, to return to the Home screen.
Back button, to cancel and return to the
previous page.
Confirm button to confirm and proceed.
Cleaning the screen
Changing a value:
Disconnect the power cord. Gently wipe the screen with
a soft, dry non-abrasive cloth.
If the marks remain, moisten the cloth slightly with a
detergent that is de­signed for LCD or mobile screens and
wipe the screen gently from top to bottom.
Never use detergents, as these may contain ammonia
or other additives.
IMPORTANT:
Option 1: Press the arrow keys to increase or
decrease the value.
Option 2: Press the displayed number to
numerically adjust the value.
Use the number buttons to
enter a value.
Home
• Never spray, or pour liquids directly on to the screen.
• Do not clean the screen while the system is on.
65
Confirm with or
cancel with .
Values that can only be read, but not written,
are displayed without a surrounding window.
Values that can be both read and written, are
displayed with a surrounding window.
Settings
1. Schedule
2. Run Commissioning Wizard
3. Timer Control
Some submenus have several pages. Touch the upper
or lower part of the scroll
list to navigate between
pages.
4. Fan Control
5. Heating / Cooling
Fläkt Woods
8217 GB 2014.07.0210
Specifications are subject to alteration without notice
TopMaster Air Handling unit
CONTROL AND REGULATION EQUIPMENT
Home screen overview
Status line
Heat recovery active
Post-heater active
Defrosting in progress
Cooling active
Current set point
value
18°C
Clock
11:08
Operating status
Alarm
Manual mode
No alarm
Automatic mode
Alarm B
Constant pressure
Alarm A
Constant air volume
Timer 1
Timer 2
Timer 1/Timer 2
Operating modes
Stop
Trickle or low speed
Normal or medium speed
Boost or high speed
Fläkt Woods
8217 GB 2014.07.0211
Specifications are subject to alteration without notice
TopMaster Air Handling unit
CONTROL AND REGULATION EQUIPMENT
Operation, home screen and submenus
Shortcut to set the
temperature set point
Shortcut to set the
time and date
Setpoint Temp
Set Time
Setpoint
Temp.
Alarm
18°C
11:08
Select operating mode
See page 13.
See page 13.
User settings
See page 13.
Trickle or
low speed
Normal or
medium speed
Boost or
high speed
Press each field to select the operating mode.
Only active in Manual mode.
Fläkt Woods
8217 GB 2014.07.0212
Specifications are subject to alteration without notice
TopMaster Air Handling unit
CONTROL AND REGULATION EQUIPMENT
Operation, submenus
Operating modes
User settings
The operating status icon on the Home screen displays the
current operating mode. To change the operating mode,
press in the middle of the large fan icon.
Manual Mode
Stop Mode
Automatic mode, the unit is controlled using
sche­dules.
Alarms
No Alarm
Alarm B
Alarm A
Here you set the desired setpoint. The default
factory setting is 18 ° C. Other temperatures are
read-only.
Fan control status
Symbol on Home screen shows alarm status.
Setpoint temperatures
Fan speeds and possible pressures and flow
rates only for reading.
Air quality
Not in use for TopMaster.
System overview
Summarizes the unit’s main operating para­
meters. See section “Parameter list” on pages
23–27.
Press the icon to enter the Alarm screen.
No active alarms
Active alarms
Ack all
Sensor fault supply air
Ack
Schedules
Filter alarm
Ack
See section ”Schedules” on pages 17–19.
Advanced operations
Example 1: No alarm
Example 2: Several alarms
See section ”Advanced operations” on pages
14–15.
Resetting the alarm
To reset the alarm, press the Ack button after each alarm
or Ack All (top right).
If the alarm persists, it reappears on the display and the
cause must be corrected before resetting.
Fläkt Woods
8217 GB 2014.07.0213
Specifications are subject to alteration without notice
TopMaster Air Handling unit
CONTROL AND REGULATION EQUIPMENT
Configuring time, date and language
Settings
Time/Date
To enter the settings menu:
Set Time
21 C
2:01 am
1. Press the gear cog button.
1. Set the time and press the Confirm button
Set Date
2. Press the spanner button.
2. Set the date and press the Confirm button.
Choose language
Settings
Set Language
Set Time and Date
Set Language
Login
3. In this menu you set the date, time and language. It is
also possible for installers and service personnel to log
in and access additional parameters.
Fläkt Woods
8217 GB 2014.07.0214
1. Choose the appropriate language flag and press
the Confirm button.
Note, further language flags are available after
pressing the right arrow icon.
Specifications are subject to alteration without notice
TopMaster Air Handling unit
CONTROL AND REGULATION EQUIPMENT
Advanced settings
Login
Settings for installer and service personnel
To enter the “Settings” menu for installers and service
personnel requires login.
The default passcode is 0000. This can be changed
later.
Enter passcode
Settings
1. Schedule
2. Run Commissioning Wizard
3. Timer Control
****
4. Fan Control
5. Heating / Cooling
Settings
6. Air Qualty
7. Alarm Configuration
8. Configure
9. Save Settings
10. Load Settings
Settings
11. Logout
1. Enter the correct passcode and press the Confirm button.
For commissioning of fans, see following section
“Commissioning Wizard” on page 16.
For other settings, see Parameter list on pages 23–27.
Fläkt Woods
8217 GB 2014.07.0215
Specifications are subject to alteration without notice
TopMaster Air Handling unit
CONTROL AND REGULATION EQUIPMENT
Commissioning Wizard
Commissioning Wizard
The Commissioning Wizard allows the fan settings to be
configured in a simple and intuitive manner.
The Commissioning Wizard is accessed by selecting
the “Run Commissioning Wizard” option from the Settings screen.
Settings
Home
65
1. Schedule
2. Run Commissioning Wizard
3. Timer Control
4. Fan Control
5. Heating / Cooling
Option 2 - Use the numerical keypad, confirm with.
Option 1
Option 2
2. Extract Fan
2. Extract Fan
Trickle
35%
Trickle
35%
Normal
65%
Normal
67%
Boost
Boost
100%
The speeds for each operating mode can be changed in
two ways:
Option 1 - Press Trickle, Normal or Boost
Option 2 - Press the value
100%
When finished with the settings, press the Confirm button
and then make the corresponding settings for the supply
fan.
2. Extract Fan
-1
Trickle
35%
Normal
65%
Boost
-10
+1
100%
+10
Option 1 - Use the ±-buttons
Fläkt Woods
8217 GB 2014.07.0216
Specifications are subject to alteration without notice
TopMaster Air Handling unit
CONTROL AND REGULATION EQUIPMENT
Schedules
Schedules
Schedule
The controller has three types of internal time schedules:
Weekly, Single date and Date period.
First, program the weekly schedule with the required
times. Then use any single date programs and the period to
enter exceptions, such as weekends and holidays.
Each schedule also needs to be activated. This is done by
pressing the grey tick button. A green tick indicates that the
schedule is active.
16. Date period 4
Priority
When several enabled applications overlap, the following
applies:
Highest priority:
Date period 4
––
–
Date period 1
–
Day 4
––
––
–
Single date 1
–
Weekly 8
–
–
Lowest priority:
Weekly 1
1.9. Date period 1
Schedule
1. Weekly 1
21
2. Weekly 2
3. Weekly 3
Weekly- schedule (1–8)
With help of a weekly schedule the unit can be programmed to operate at trickle, normal and boost speed alternatively stop.
Example 1
Below is an example of a weekly schedule configured to
run the fans at normal speed from 08.00 to 18.00 Monday
to Friday. At all other times, the fans are turned off.
Day
Time
Fan speed
Monday8–18 Normal
Tuesday8–18 Normal
Wednesday8–18
Normal
Thursday8–18
Normal
Friday 8–18Normal
Other time
Stop
4. Weekly 4
5. Weekly 5
1 Weekly 1
Fan speed
Schedule
6. Weekly 6
7. Weekly 7
Normal
Temp set point
Rel
From
Mon
Daily
08:00
0°C
To
Fri
18:00
8. Weekly 8
Single date 1
9. Single date 1
10. Single date 2
Only Weekly 1 should be activated.
Schedule
11. Single date 3
12. Single date 4
13. Date period 1
14. Date period 2
15. Date period 3
Fläkt Woods
8217 GB 2014.07.0217
Specifications are subject to alteration without notice
TopMaster Air Handling unit
CONTROL AND REGULATION EQUIPMENT
Schedules (cont.)
Example 2
Example 3
Below is an example of a weekly schedule configured to
run the fans at normal speed from 08.00 to 18.00 Monday
to Thursday, from 08.00 to 17.00 on Friday and 10.00 to
14.00 on Saturday. At all other times, the fans are turned off.
Below is an example of a weekly schedule configured to
run the fans at normal speed from 08.00 to 18.00 Monday
to Friday. At all other times, the fans are configured to
run at trickle speed. At trickle speed the temperature set
point will be decreased by two degrees.
Day
Time
Fan speed
Monday8–18Normal
Tuesday8–18Normal
Wednesday8–18
Normal
Thursday8–18 Normal
Friday 8–17Normal
Saturday10–14 Normal
Other time Stop
Day
Time
Monday
8–18
Normal
0 °C
Tuesday
8–18
Normal
0 °C
Wednesday
8–18
Normal
0 °C
Thursday
8–18
Normal
0 °C
Friday
8–18
Normal
0 °C
Trickle (Low)
–2 °C
Other time
1 Weekly 1
1 Weekly 1
Fan speed
Normal
Temp set point
Rel
From
Mon
Daily
08:00
0°C
To
Fan speed
Fri
From
Mon
18:00
Daily
00:00
Stop
Rel
Fri
Daily
17:00
Rel
To
-2°C
Sun
23:59
2 Weekly 2
Fan speed
From
Trickle
Temp Setpoint
2 Weekly 2
Tem Setpoint
Fan speed Temp. setpoint
0°C
To
Fan speed
Normal
Temp Setpoint
Rel
Fri
From
Mon
18:00
Daily
08:00
To
0°C
Fri
18:00
Only Weekly 1–2 should be activated.
3 Weekly 3
Fan speed
Normal
Temp Setpoint
Rel
From
Sat
Daily
10:00
To
0°C
Sat
14:00
Only Weekly 1–3 should be activated.
Fläkt Woods
8217 GB 2014.07.0218
Specifications are subject to alteration without notice
TopMaster Air Handling unit
CONTROL AND REGULATION EQUIPMENT
Schedules (cont.)
Single date schedule (1–4)
A single date schedule is defined as a one-off schedule
that automati­cally starts and finishes on the same date.
Example
The unit must be switched off on 6 June.
Note!
Remember to enable the desired time
channels by pressing
1. Single date 1
Stop
Fan speed
Temp Setpoint
Rel
Date
6-Jun-2014
0°C
Date period schedule (1-4)
A date period schedule is defined as a one-off schedule
that is configured to run between any two dates.
Example
The unit must be switched off between 24 December and
26 December.
Stop
Fan speed
Fläkt Woods
Temp Setpoint
Rel
Start date
24-Dec-2014
Stop date
26-Dec-2014
0C
8217 GB 2014.07.0219
Specifications are subject to alteration without notice
TopMaster Air Handling unit
CONTROL AND REGULATION EQUIPMENT
Control functions
• Continuously rotating heat exchangers
Room control and exhaust air control is the same
control type with the difference that in combination with
room control an external room sensor is needed (separate
ordering code). In addition it is possible to use outdoor
temperature compensation. This control mode cannot be
combined with extract air control or room control.
The unit is configured for supply air control as standard. To obtain other control modes, first the controller
must be changed from standard mode to cascade mode.
Then control mode is selected by changing the cascade
reference to extract air control/room control (0) or outdoor temperature compensation (1). Below is a description
of the different control modes.
Choice of cooling
Supply air control
1. Rotor, heating and cooling
The unit is configured differently with regard to heating,
heat recovery and cooling, see below.
Choice of heating function
• No heater
• Electric heater
• A water heater with frost-guard function
Heat recovery
• No cooling
To maintain a constant supply air temperature, the controller works from a fixed setpoint and the supply air
temperature. Based on these parameters, the controller
controls the current heating, heat recovery and cooling
sequences.
• Water -cooling
• DX cooling, 1-stage
Control function
The control function works as follows:
Regardless of control mode the unit tries to achieve the
desired setpoint.
This is done by the unit depending on the needs,
demand for heat recovery, heating or cooling. Built into
the system is also a dead zone. The dead zone function
(usually 2°C) acts as a temperature zone between heat
recovery and cooling unit where neither calls for heat recovery or cooling.
The reason for having a dead zone, is that the temperature will be slightly lower in winter, and slightly higher
in summer. This is energy-efficient and in practice even
more convenient for people staying in the room.
Control signal, %
Sequence control
Extract air control
The exhaust air temperature gives a good average value
of the temperature in different rooms. Using this the
unit controls the supply air temperature to maintain the
extract temperature at a desired level.
This method is suitable for ventilation systems that
supply a number of similar rooms. In cases where different rooms have different heating requirements, this
method should not be used. This is because the unit cannot detect the varying heating needs, but can only read
an average temperature.
The limits on the supply air temperature (min. temp.
/ max. temp.) ensure that the supply air temperature is
maintained within the set range.
Default parameters for extract air control
ver
o
Rec
ting
Hea
Coo
ling
100
1. Controller = 2
Selects cascade control
3. Cascade A = 0.5
When the sensor gets colder
than given setpoint value
2. Cascade reference = 0
y
50
4. Cascade B = –0.5 5. Min. temp. = 15°C
T0
T1
T2
T3
T4
Temperature, °C
Figure 1. The figure shows the controller’s output signals to the
various unit components at different temperatures. The
figure also shows two temperatures, one for heating (T2)
and one for cooling (T3). The zone between T2 and T3 is
called the dead zone. Note that heating is activated only
when heat recovery is working at 100%.
2. Temperature controls
TopMaster has three temperature control options, supply
air, extract air control and room control.
Fläkt Woods
8217 GB 2014.07.0220
6. Max. temp. = 25°C
Selects extract air control
When the sensor gets hotter
than given setpoint value
Sets lowest supply air
temperature
Sets highest supply air
temperature
Example
1. Setpoint = 18°C
2. Extract air temperature = 16°C
This means that the new calculated setpoint for the
supply air controller is:
Calculated setpoint = setpoint + (setpoint – exhaust air
temperature) x cascade A = 18 + (18-16) x 0.5 = 19 ° C.
Specifications are subject to alteration without notice
TopMaster Air Handling unit
CONTROL AND REGULATION EQUIPMENT
Control functions (cont.)
Room control
Room control gives the best control of temperature in a
specific room and is used when only one unit serves this
room. This method works best for larger premises.
By replacing the exhaust temperature sensor with a
room temperature sensor placed in the room in question,
a good room temperature value is achieved.
This enables the unit to regulate the supply air temperature in a way that maintains the room temperature at a
desired level.
Limitation of the supply air temperature (min. temp.
and max. temp.) ensures that the supply air temperature
is maintained within the set range.
Default parameters for room control
1. Controller = 2
Selects cascade control
3. Cascade A = 0.5
When the sensor gets colder
than given setpoint value
2. Cascade reference = 0
4. Cascade B = –0.5 Selects room control
When the sensor gets hotter
than given setpoint value
5. Min. temp. = 15°C
Sets lowest supply air
temperature
6. Max. temp. = 25°C
Sets highest supply air temperature
Example
1. Setpoint = 18°C
2. Room temperature = 22°
This means that the new calculated setpoint for the supply air controller is:
Calculated setpoint = setpoint + (setpoint – room air temperature) x cascade B = 18 – (18 – 22) x (–0.5) = 16°C.
Outdoor temperature compensation
The setpoint temperature for supply air can be adjusted
up or down depending on the outdoor temperature. By
setting a higher set point value both on cold winter days
and hot summer days indoors comfort is improved.
In summer, this will increase energy savings. Outdoor
temperature compensation can not be combined with extract air control or room control.
Default parameters for outdoor temperature
compensation
1. Controller = 2
2. Cascade reference = 1
3. Cascade A = 0,05
4. Cascade B = 0.03
5. Min. temp. = 15°C
6. Max. temp. = 25°C
Fläkt Woods
Selects cascade control.
Selects outdoor temperature
compensation.
When the sensor gets colder
than given setpoint value.
When the sensor gets hotter
than given setpoint value.
Sets lowest supply air
temperature.
Sets highest supply air
temperature.
8217 GB 2014.07.0221
Setpoint
Outdoor temperature compensation
+30
+25
+20
+15
–20 –15 –10 –5
0
5 10 15 20 25 30 35
Outdoor temperature, °C
Example 1
1. Setpoint = 18°C
2. Outdoor air temperature = –2°C
This means that the new calculated setpoint for the
supply air controller is:
Calculated setpoint = setpoint + (setpoint – outdoor air
temperature) x cascade A = 18 + (18 –(-2)) x 0.05 = 19°C
Example 2
1. Setpoint = 18°C
2. Outdoor air temperature = 28°C
This means that the new calculated setpoint for the
supply air controller is:
Calculated setpoint = setpoint + (setpoint – outdoor air
temperature) x cascade B = 18 – (18 – 28)) x 0.30 = 21°C.
3. Freeze protection
Warning! Do not change these parameters unless it is
absolutely necessary. If the unit is misconfigured the
water coil can freeze up and cause water damage to
property.
Freeze protection is used during low outdoor temperatures to prevent the coil from freezing. When the unit
is stopped, the temperature in the water coil is maintained at the setpoint to keep the unit warm. If there is a
risk of freezing in the water coil the motorized valve is
controlled to open.
If the temperature drops below the adjustable limit
value an A-alarm is obtained, which then stops the unit.
4. Defrost function
The defrost function is used to prevent the rotor from
freezing. By measuring the pressure across the rotor it is
possible to verify when the rotor needs to be defrosted.
When the pressure over the rotor becomes too high it
activates a time delay before defrosting. Then defrosting
starts. When the pressure is below the given limit value it
starts a time delay. When the time delay has elapsed, the
defrosting stops
Defrosting is achieved by running the rotor sectionwise. Fan speeds are not affected.
Specifications are subject to alteration without notice
TopMaster Air Handling unit
CONTROL AND REGULATION EQUIPMENT
Control functions (cont.)
5. Cooling recovery
Cooling energy recovery is used when cooling load is
needed by taking advantage of any room cooling. Cooling recovery is activated if the outdoor temperature is 2°
C higher than the extract air temperature and the unit is
operating in “summer mode”. If this condition is satisfied
the rotor starts and supplies 100%.
6. Night cooling
Night cooling is used in summertime to reduce cooling
load at unit start-up and to limit the maximum temperature during non-working hours. This is done by making
use of cold outside air during cool summer nights.
Parameters
Yes
Room setpoint night cooling
5°C
Min difference room temp.
2°C
Hysteresis for night cooling
Hysteresis
Test time, start
kl. 22.00
Start time for night cooling test
Test time, off
kl.22.15
Stop time for night cooling test
Max time
540 minutes
Maximal activation time
for night cooling
1. Starting conditions
a. Night cooling activated
b. Auto mode enabled
c. The unit is in the stop position as scheduled
2. Test period and evaluation
a. The unit is started at. 22.00 and then operates at
normal speed
b. At 22.15 it is determined whether night cooling is
needed or not. The following conditions must be met:
1. The unit is in “Summer mode” .
3. Extract temperature > Room setpoint + Hysteresis.
c.
Control principle in which the unit maintains a constant
duct flow. Pressure sensors are supplied as loose accesso­
ries. Using a measurement pressure Dpm in Pa and a constant k, the airflow q in l/s is calculated with the follo­wing
formula:
q = 1000 x Δpm
k
Activated night cooling
22°C
Delta
Constant Flow Control (CAV)
Value (exemple) Comment
Night cooling activated
Room setpoint
Pressure control regulates air pressure in index duct (duct
with a maximum pressure drop, and where the static pressure is lowest). The pressure sensor (GP3) is placed at the
beginning of this duct The exhaust sensor (GP4) is placed
in the exhaust duct at a suitable location with representative pressure. For settings see the Parameter list.
2.Outdoor temperature < Extract temperature – Delta.
If the above conditions are met the night cooling
starts. 3. The following take place during night cooling
a. Rotor, afterheater and any cooling are blocked.
b. The fans are switched to the high speed setting.
The measuring pressure, Dpm, is the difference between
the pressure in the empty section at the fan inlet and the
pressure inside the inlet cone.
The pressure sensor is connected via two externally
placed measuring nipples.
Value of the constant (k) is shown in the table below.
For settings see the parameter list.
Size
k-value extract air fan
k-value supply air fan
a. Unit is in “Summer mode”.
b. Outdoor temperature < Extract temperature – Delta.
c. Extract temperature > Room setpoint.
d. Function’s maximum activation time is not reached.
6. Pressure or flow control
Pressure control (COP)
Control principle in which the unit maintains a constant
duct pressure. Normally used in variable flow systems
(VAV). Pressure sensor is supplied as a loose accessory.
Fläkt Woods
8217 GB 2014.07.0222
050
41
49
Connection of pressure sensors
The pressure sensor shall be set to the working range of
0 –500 Pa.
Location
Terminal Connection
Y
Supply air duct GP3
G0
G
Y
Extract air duct GP4
G0
G
No.
Pressure sensor
520–10 V
51
GND
50
24 V DC
550–10 V
54
GND
53
24 V DC
Zero point-calibration
push-button
LED
4. Night cooling takes place as long as the
following conditions are fulfilled:
030
56
55
LED
Jumper 1
Jumper 2
Jumper 3
0-10V
4-20mA
24VDC
GND
Jumper 1
Jumper 2
Jumper 3
The sensors must be zeroed during commissioning. They
should then be zeroed annually. The sensors should have
been energized for approximately one hour before calibration is carried out. After that, remove the hoses from
the sensors. To start calibration press the push-button
next to the pressure range jumpers. The red LED lights
up and goes out after about a second. Reassemble the air
hoses. Done!
Specifications are subject to alteration without notice
TopMaster Air Handling unit
CONTROL AND REGULATION EQUIPMENT
Parameter list
Some parameters and functions have a more detailed explanation after the parameter list. The Curo ™ Touch control
panel has a wide range of applications. Only relevant parameters are listed below. It is strongly recommended to avoid
the adjustment of any system parameters that are not outlined in this section.
Parameter
Type of value1)
Range
Unit Default value Comments
Temperature status
Setpoint
R/W15–35
°C
18
Desired setpoint.
Actual setpoint for supply air.
Actual setpoint
R
15–35
°C
-
Used for extract air control or out
door temperature compensation.
Supply air
R
-40–100
°C
-
Supply air temperature.
Outdoor air
R
-40-100
°C
-
Outdoor air temperature.
Extract / Room
R
-40–100
°C
-
Extract air / Room temperature.
Freeze protection
R
-40–100
°C
-
Freeze protection temperature.
Fan status
Supply air fan, speed
R
0 or 30–100%
-
Extract air fan, speed
R
0 or 30–100%
-
Air qual ity
No such function in TopMaster.
Overview
This menu is used for maintenance and troubleshooting.
Software version, Control panel
R
-
-
-
Speed, Supply air fan
R
0 or 30–100%
-
Speed, Extract air fan
R
0 or 30–100%
-
Output, Post-heater
E
0–100%
-
Output, Pre-heater
R
-
-
-
No such function in TopMaster.
Output, Heat recovery
R
0–100%
-
Outout, Cooling
R
0–100%
-
Summer/Winter mode
R
Summer/Winter -
-
Supply air temperature
R
-40–100°C
-
Supply air temperature
R
-40–100°C
-
Extract air temperature
R
-40–100°C
-
“Cold corner” temperature
R
-
-
-
No such function in Topmaster.
Freeze protection temperature
R
-40–100
°C
-
Only in case of water heating.
Setpoint set
R/W
15–35°C 18
Operation codes
R
-
-
-
No such function in Topmaster.
Schedules
Only reading, programming of
schedules is done under Settings.
Weekly 1-8
R
Daily 1-4
R
Date period 1-4
R
Settings
Time / Date
R/W
This can also be done directly
from the home page.
Choose language
R/W
English
Login
R/W0000–9999
0000
For installers and service personnel.
Settings
For installers and service personnel.
1. Schedules
See page 17.
1) R/W = Read and write value, R = Read only value
Fläkt Woods
8217 GB 2014.07.0223
Specifications are subject to alteration without notice
TopMaster Air Handling unit
CONTROL AND REGULATION EQUIPMENT
Parameter list (cont.)
Parameter
Type of value1)
Range
Unit Default value Comments
2. Commissioning Wizard
See page 16
3. Timer functions
See page 5.
Timer function
R/W
1–5 2
Timer off delay
R/W
0–999min 0
4. Fans
4.1 Speed of fans
Commissioning of fans is done in menu 2, Commissioning Wizard.
Automatic return to the previous
Auto Stop forced mode
R/W
Yes/No
No
operating mode in the choice of
high speed.
Forcing time
R/W
0–9999
min
120
Time before return, see above.
Start delay
R/W
0–32767
s
10
During this time SF and rotor run.
Off delay
R/W
0–32767
s
0
After cooling, set to 180 s at
electric heater.
Pressure/Flow control of fans
4.2 Pressure / Flow
The unit must be equipped with pressure sensors. See page xx.
If pressure control
Pressure control supply air
R/W
Yes/No
Yes
Pressure control extract air
R/W
Yes/No
Yes
Only SF, EF slave
R/W
Yes/No
No
Proportion SF / EF
R/W
0–200
%
100
Only if the above parameter is active.
Supply air pressure setpoint
R/W
0–2000Pa 150
Extract air pressure setpoint
R/W
0–2000Pa 150
If flow control
Flow control supply air
R/W
Yes/No
Yes
Flow control extract air
R/W
Yes/No
Yes
Only SF, EF slave
R/W
Yes/No
No
Proportion SF / EF
R/W
0–200
%
100
Only if the above parameter is active.
Supply air flow, low speed
R/W
0–9999l/s 80
Supply air flow, normal speed
R/W
0–9999l/s 100
Supply air flow, high speed
R/W
0–9999l/s 120
Extract air flow, low speed
R/W
0–9999l/s 80
Extract air flow, normal speed
R/W
0–9999l/s 100
Extract air flow, high speed
R/W
0–9999 120
5. Heating / Cooling
5.1 Pre-heater
No such function in TopMaster.
5.2 Heating / Cooling
See also pages 20–22.
Control mode
R/W
1-2
1
1 = Standard, supply air control
2 = Cascade control.
Cascade reference
R/W
0-1
0
0 = Extract air control
1 = Outdoor air compensation.
Cooling sequence
R/W
Yes/No
No
Cooling sequence activated.
DX-cooling
R/W Yes/No No
Dead zone cooling
R/W
Yes/No
Yes
Dead zone cooling activated.
Dead zone
R/W
0–25°C 2
Block cooling in winter
R/W
Yes/No
Yes
Block heating in summer
R/W
Yes/No
Yes
Post-heater
R/W Yes/No Yes
Absolute/Relative temperature
R/W
abs/rel
rel
Absolute or relative temperature
in schedules.
1) R/W = Read and write value, R = Read only value
Fläkt Woods
8217 GB 2014.07.0224
Specifications are subject to alteration without notice
TopMaster Air Handling unit
CONTROL AND REGULATION EQUIPMENT
Parameter list (cont.)
Parameter
Type of value1)
Range
Unit Default value Comments
5.3 Night cooling
See also pages 20-22.
Night cooling
R/W
Yes/No
No
Activated from factory if unit is
ordered with night cooling.
Set point room temperature
R/W
15-50
°C
20
Test time start
R/W
19.00–04:00
22.00
Test time stop
R/W
19.00–04:00
22.5
Hysteresis
R/W 0-20°C 2
Delta
R/W 0-20°C 5
Max. time
R/W
1-720
min
540
5.4 Defrosting
Parameters unalterable.
See also pages 20-22.
5.5 Cooling recovery
See also pages 20-22. Cooling recovery
R/W
Yes/No
-
Yes
Temperature difference
R/W 0-15°C 2
Outdoor air – Extract air
5.6 Summer / Winter mode
Summer / Winter mode
R
Summer/Winter -
-
Summer, if outdoor temp. >18° or
>15 ° for more than 6 hours or Automatic / Manually
R/W
Auto/Manually
-
Auto
Winter, if outdoor temperature <12°
<15° for >6 hours.
Winter/Summer
R/W Summer/Winter-
Winter
5.7 Freeze protection
See also page 20-22.
Keeping warm
R/W
0–50°C 25
Setpoint min. mode temp.
R/W
0–50°C 12
Setpoint freeze protection alarm
R/W
0–50°C 5
Pump stop
R/W
Yes/No
Yes
No = continuous operation of pumps
Heat pump runs when heating is
required, cooling pump runs when
Pump stop mode
R/W
Summer/Winter, heating/cooling S / W = heat pump runs in winter,
heating/cooling
cooling pump runs in the summer.
Anti-jamming of pumps takes place
12.00 to 12.05 every day.
6. Air quality
No such function in TopMaster.
7. Alarm handling
7.1 Alarm
Filter alarm time
R/W
0–600
days
0
0 = Disabled.
Yes = Sum alarm at both A and
B alarm. No = Sum alarm at Sumalarm output A+B
R/W
Yes/No
Yes
A alarm. Sum alarm output
max 24V, 200mA.
Activate temperature alarm
R/W
Yes/No
No
No = Temperature alarm disabled.
Temperature alarm
R/W
-10–10
°C
10
The alarm occurs when the supply
air temperature is lower than the
limit >10 min.
7.2 Alarm categories
Fire alarm
R/W
A/B
A
Sensor fault supply air
R/W
A/B
A
Sensor fault outdoor air
R/W
A/B
A
Sensor fault extract air/room
R/W
A/B
A
Sensor fault freeze protection
R/W
A/B
A
1) R/W = Read and write value, R = Read only value
Fläkt Woods
8217 GB 2014.07.0225
Specifications are subject to alteration without notice
TopMaster Air Handling unit
CONTROL AND REGULATION EQUIPMENT
Parameter list (cont.)
Parameter
Type of value1)
Range
Unit Default value Comments
Sensor fault Cold corner
Not used in TopMaster.
Sensor fault UI1
Not used in TopMaster.
Sensor fault UI2
Not used in TopMaster.
Sensor fault UI3
Not used in TopMaster.
Sensor fault UI4
Not used in TopMaster.
Sensor fault UI5
Not used in TopMaster.
Filter alarm
Not used in TopMaster.
Fan monitor supply air
R/W
A/B
A
Fan monitor extract air
R/W
A/B
A
Pressure switch HRU
R/W
A/B
B
Rotor pressure switch
R/W
A/B
B
Filter alarm supply air
R/W
A/B
B
Filter alarm extract air
R/W
A/B
B
Overheating electric heater
R/W
A/B
A
Circualation pump heating
R/W
A/B
A
Freeze-protection
R/W A/B A
Sum alarm cooling
R/W
A/B
A
Circulation pump cooling
R/W
A/B
A
Temperature alarm
R/W
A/B
A
Rotor belt alarm
R/W
A/B
A
7.3 Alarm delays
Fire alarm delay
R/W
0–9999s
2
Sensor fault supply air delay
R/W
0–9999s
5
Sensor fault outdoor air delay
R/W
0–9999s
5
Sensor f. extract air/room delay
R/W
0–9999s
5
Sensor f. freeze-protection delay
R/W
0–9999s
5
Sensor fault Cold corner delay
Not used in TopMaster.
Sensor fault UI1 delay
Not used in TopMaster.
Sensor fault UI2 delay
Not used in TopMaster.
Sensor fault UI3 delay
Not used in TopMaster.
Sensor fault UI4 delay
Not used in TopMaster.
Sensor fault UI5 delay
Not used in TopMaster.
Fan monitor supply air delay
R/W
0–9999s
2
Fan monitor extract air delay
R/W
0–9999s
2
Rotor pressure switch delay
R/W
0–9999s
2
Filter alarm supply air delay
R/W
0–9999s 60
Filter alarm extract air delay
R/W
0–9999s 60
Overheat electric heater delay
R/W
0–9999s
2
Circulation pump heating delay
R/W
0–9999s
2
Freeze-protection delay
R/W
0–9999s
2
Sum alarm cooling delay
R/W
0–9999s
2
Circulation pump cooling delay
R/W
0–9999s
2
Temperature alarm delay
R/W
0–9999min 10
7.4 Contact functions
DI1 Timer input 1
R/W
0=NC, 1=NO
NO
DI2 Timer input 2
R/W
0=NC, 1=NO
NO
DI3 Rotor pressure switch
R/W
0=NC, 1=NO
NO
DI4 Pressure switch defrosting
R/W
0=NC, 1=NO
NO
DI5 Fan prot./Filter monitor SF
R/W
0=NC, 1=NO
NO
DI6 Fan prot./Filter monitor EF
R/W
0=NC, 1=NO
NO
UI1 Fire alarm
R/W
0=NC, 1=NO
NC
UI2
Not used in TopMaster.
UI3 Alarm heater
R/W
0=NC, 1=NO
NO
NC at electric heater.
UI4 Alarm cooler
R/W
0=NC, 1=NO
NO
UI5 Tacho signal rotor
R/W
0=NC, 1=NO
NO
Not to be changed.
1) R/W = Read and write value, R = Read only value
Fläkt Woods
8217 GB 2014.07.0226
Specifications are subject to alteration without notice
TopMaster Air Handling unit
CONTROL AND REGULATION EQUIPMENT
Parameter list (cont.)
Parameter
Type of value1)
Range
Unit Default value Comments
8. Configuration
8.1 IP address
Static = IP address is manually set. Static/Dynamic
R/W
Static/Dynamic
Dynamic
Dynamic = IP-address is automa tically set via DHCP.
IP- address
Subnet mask
8.2 Menu configuration
Logon to USB
R/W
Yes/No
No
Is set to Yes for copying the log files to the USB memory.
Unit type
L
TopMaster
Auto logout
R/W
0–32767
min
10
Time before automatic logout
occurs in the control panel.
Thresholds
Not used in Topmaster.
8.3 Screen saver
Screen saver
R/W
Yes / No
Yes
Time
R/W
min
10
Time before the screen saver is
activated in the control panel.
8.4 Modbus
Sea also the Modbus manual.
Address BMS
R/W
2
Baud rate
R/W
9600, 19200, 9600
38400
Parity
R/W
none, odd, even
none
Data bit
R/W
7,8
8
Stop bit
R/W
1,2
1
8.5 MAC address
Displays the network card
MAC address
L
MAC address.
8.7 Password
Automatic logout
R/W
Yes/No
Yes
Password 1
R/W
0000-9999
0000
The password can be changed. If passcode is forgotten, Fläkt Woods must be contacted.
8.8 About
Software HMI
L
Displays the current software
version of the control panel.
Software Control card
L
Displays the current software
of the control card.
9. Save values
Store the set values ​​in the control
panel (to copy to another unit).
10.Uploading values
Uploading saved values to unit.
11. Save to SD
Stored values can
​​
be saved in SD
card, this requires that the values
have already been saved in
​​ menu 9.
12.Load from SD
Stored values ​​may be loaded from
the SD card.
13. Log out
1) R/W = Read and write value, R = Read only value
Fläkt Woods
8217 GB 2014.07.0227
Specifications are subject to alteration without notice
We Bring Air to Life
Fläkt Woods is a global leader in air management.
We specialize in the design and manufacture of a wide
range of air climate and air movement solutions.
FWG_TopMaster_Control and Regulation equipment_GB 2014.07.02_8217
© Copyright 2014 Fläkt Woods Group
Condesign_ABS5953
Our collective experience is unrivalled.
We are constantly aiming to provide systems that
precisely deliver the required features and performance as
well as maximum energy efficiency.
Fläkt Woods Group SA
18, avenue Louis Casaï, CH-1209 Geneva, Switzerland
Tel. +41 22 309 3800
email [email protected] www.flaktwoods.com
See global website for international sales offices www.flaktwoods.com