TopMaster Air Handling Unit
Transcription
TopMaster Air Handling Unit
TopMaster Air Handling Unit Control and Regulation Equipment TopMaster Air Handling unit CONTROL AND REGULATION EQUIPMENT Contents Electrical connection Electrical cabinet.......................................................... 3 Electrical connection and fuse protection................. 3 Sensors and accessories Sensors and accessories............................................... 4 Temperature sensor .................................................... 5 Damper actuator.......................................................... 5 Water heater ................................................................. 6 Liquid cooling ............................................................. 6 Electrical heater............................................................ 6 DX -cooling .................................................................. 6 Valve actuator and valve for heating and cooling..................................... 7 Connection of external components.......................... 8 Installation and connection Installation of control panel..............................................9 User instructions General, general buttons and symbols..........................10 Home screen......................................................................11 Basic operation, overview...............................................12 Submenus..........................................................................13 Settings Configuring time, date and language ..........................14 Installers and service personnel.....................................15 Login..................................................................................15 Commissioning Wizard Commissioning of fan speeds........................................16 Schedules Schedules...........................................................................17 Control and regulation functions Control and regulation functions...................................20 Parameter list Parameter list....................................................................23 Fläkt Woods 8217 GB 2014.07.022 Specifications are subject to alteration without notice TopMaster Air Handling unit CONTROL AND REGULATION EQUIPMENT Electrical cabinet – Electrical connection and fuse protection Electrical connection and fuse protection Electrical cabinet Electrical connection is made to the terminals in the ectrical cabinet. A separate switch -disconnector must be used, e. g. RDTZ-89-016. 1 Fuse protection The fuse protects the unit’s incoming supply: Size 030 rated at 10 AT, Size 050 rated at 16 AT. Fuse protection for DX -cooling is carried out separately. 2 Feed 3 x 400 V for units with electric coil. 1 x 230 V for units with water coil, phase connected to terminal L1. 3 4 5 1. Connection incoming supply 2. Control card 3. Condenser, rotor 4. Fuses 5.Transformer, 230 V/24 V Fläkt Woods 8217 GB 2014.07.023 Specifications are subject to alteration without notice TopMaster Air Handling unit CONTROL AND REGULATION EQUIPMENT Sensors and accessories Sensors and accessories All sensors and accessories are connected to TopMaster via connections in the electrical cabinet. Cables to external components are secured in the electrical cabinet using the tie-rail with a cable tie, for example.. The cable is then placed against the cellular plastic strip on the unit (see figure 1). When all cables are connected to terminals and the cables are secured on the tie rail, the cover is positioned on the electrical cabinet and secured using the appropriate screws (see figure 2). The cellular plastic, which is semi-elastic, will slowly adapt to the shape of the cables and in doing so the lead-through will seal (see figure 3). Information about how the different sensors and accessories should be fitted and connected is provided in the following section. Figure 1. T he cables are secured on the tie rail using a cable tie and placed against the cellular plastic strip on the unit. Figure 2. W hen the cables are connected to the terminals and then secured to the tie rail, the cover is fitted on the electrical cabinet. Figure 3. T he semi-elastic cellular plastic slowly adapts itself to the shape of the cables and the lead-through seals. Fläkt Woods 8217 GB 2014.07.024 Specifications are subject to alteration without notice TopMaster Air Handling unit CONTROL AND REGULATION EQUIPMENT Sensors and accessories Temperature sensors The TopMaster is equipped as standard with three factorymounted temperature sensors: Supply air sensor GT1 Positioned at the supply air inlet connection spigot. Outdoor air sensor GT3 Positioned at the outdoor air inlet spigot. Extract air sensor GT12 Positioned at the extract air inlet connection spigot. Filter monitors (accessories) The filter monitors GP1 and GP2 are enclosed separately. Connect hose to test point. Set the required alarm limit across the filter using the knob on the sensor. For installation, see enclosed instruction. Air flow monitors (accessories) The air flow monitors GP1 and GP2 are enclosed separately. For installation, see enclosed instruction. Connect hose to test point. Air flow monitors cannot be combined with filter monitors. Damper with actuator (accessory) 2 positions with spring return, 15 Nm, 24 VAC. Other sensors: Room temperature sensor GT2 Damper with mounted actuator is delivered separately. Included when room control is selected, and then replaces extract air sensor GT12. It is intended for placement Timer, prolonged, forced mode on an inner wall. The sensor should be placed in an area with good air circulation and it should not be exposed to direct sunlight. It is delivered loose without any cable. Any timers are enclosed separately. When the push button is used the internal timer in the controller must be set to the required time. Function of control inputs Timer 1 (T1) and Timer 2 (T2) can be selected according to the following table. Freeze-protection sensor GT5 Included as standard when the unit is equipped with heat water coil. To be mounted on the heater’s return line. Note! If a cooling coil is mounted in the duct, the supply air sensor must be moved from the unit into the duct, and placed after the coil. Timer Function 1 Manual/Automatic Mode Trickle Normal Boost Timer 1 0 1 0 1 Timer 2 0 0 1 1 Timer Function 2 (default) Manual/Automatic Mode Trickle Boost Stop Timer 1 0 1 0 1 Timer 2 0 0 1 1 Timer Function 3 Manual/Automatic Mode Normal Boost Stop Timer 1 0 1 0 1 Timer 2 0 0 1 1 Timer Function 4 Stop Manual/Automatic Mode Stop Boost Timer 1 0 1 0 1 Timer 2 0 0 1 1 Timer Function 5 Stop Manual/Automatic Mode Stop Normal Fläkt Woods 8217 GB 2014.07.025 Timer 1 Timer 2 0 0 1 0 0 1 1 1 Specifications are subject to alteration without notice TopMaster Air Handling unit CONTROL AND REGULATION EQUIPMENT Sensors and accessories Rotor pressure switch Rotor pressure switch (GP7) for defrosting, factory -mounted. Water heater Circulation pump (CP1) and valve actuator (SV1) for water heating is connected as in the table below. If the pump motor does not have an integrated alarm unit, the motor protection can be used to receive an alarm signal. Component Terminal Connection Comments Circulation CP1 Start C-N-PE pump CP1 Pump supply (230 VAC max 2A*) CP1 Start N0 - L1 Clamp at circulation pump CP1 Alarm NO - C 34 - 35 Potential-free alarm input, supplied design as NO, can be configured Valve actuator SV1 Control Y-M-G- GO 38 -39-40-41 *) T otal power consumption for cooling and heating may amount to max 2 A Circulation pump (CP2) and valve actuators (SV2) for liquid cooling mode are connected as shown in the table below. If the pump motor does not have built-in alarm device, motor protection is used to obtain an alarm signal. Terminal If an electric heater has been ordered, this is connected when supplied. The electric coil is factory mounted. DX-cooling The Curo™ control system is able to control DX -cooling, 1-stage. Note! DX -coil is not a part of the unit delivery. For setup, see chapter on Control and Regulation functions. Electrical connection is as shown in the following table. ComponentFunction Terminal Connection Design specification 1-stageStart CP2 Start C-NO DX -cooling cooling Start: 10%, Stop: 0% Alarm CP2 Alarm NO - C 36 - 37 NO Fire protection function External fire alarm can be connected to terminal in electrical cabinet to stop the unit. Alarm output Liquid cooling Component Electric heater Potential-free connection, max. load 24 V, 200 mA. TopMaster has a total alarm output which can be selected, allowing you to indicate just A alarms or both A and B alarms. Connection Comments CirculationCP2 Start C-N-PE pump CP2 Pump supply (230 VAC max 2A*) CP2 Start N0 - L1 Clamp at circulation pump CP2 Alarm NO - C 36 - 37 Potential-free alarm input, supplied design as NO, can be configured Valve actuator SV1 Control Y-M-G- GO 42 -43-44-45 *) T otal power consumption for cooling and heating may amount to max 2 A Note! If a cooling coil is mounted in the duct, the supply air sensor must be moved from the unit into the duct, and placed after the coil. Fläkt Woods 8217 GB 2014.07.026 Specifications are subject to alteration without notice TopMaster Air Handling unit CONTROL AND REGULATION EQUIPMENT Sensors and accessories Valve actuator for heating SV1 and cooling SV2 Connected to terminal in electrical cabinet. Stroke length 5.5 mm. Intended for assembly on 2-way and 3-way valves of the type VVG44 or VXG44. 3-way valve VXG The bypass is closed by turning the spindle inwards, the bypass is opened by turning the spindle outwards. Accepted installation method Accepted installation method Valve for heating and cooling When installing a 3-port valve check as follows: The valve and valve actuator can be easily installed with out special tools. A particle filter should be fitted before the valve to extend its service life. Mixture from A/B to AB 2-way valve VVG Distribution from AB to A/B The flow is increased by turning the spindle inwards, the flow is reduced by moving the spindle outwards. Note that the two-way valve cannot be used as a threeway valve. The flow direction in the valve is indicated by the arrow. Accepted installation method Fläkt Woods 8217 GB 2014.07.027 Specifications are subject to alteration without notice TopMaster Air Handling unit CONTROL AND REGULATION EQUIPMENT Sensors and accessories Connection of external components 10 1 2 3 4 5 6 7 8 9 12 11 14 13 1. CP1/SK1 Start 2. CP2/DX Start 3. CO2 4. ST1 5. ALM, Alarm output, max 24 V, 200 mA 6. Fire, Fire alarm 7. TMR1, Timer input 1 8. TMR2, Timer input 2 9. CP1, alarm heating 10.CP2, alarm cooling 11. SV1 CTRL, control signal heating 12. SV2 CTRL, control signal cooling 13.GT1 14.GT3 15. SK1 Supply, supply electric coil 16. TF Supply 17. FF Supply 18.GP3 19.GP4 20.GT5 21.GT2 22.GS1 23.GP7 24.GP1 25.GP2 26. MODB, Modbus RS485 27. TF CTRL, control signal supply air fan 28. FF CTRL, control signal extract air fan 16 15 18 17 Fläkt Woods 20 19 22 21 24 23 25 26 28 27 8217 GB 2014.07.028 Specifications are subject to alteration without notice TopMaster Air Handling unit CONTROL AND REGULATION EQUIPMENT Installation and connection 1. Open the control panel using a screwdriver 5. Connect the cable to the back of the display as shown above. Note. Please do not touch the electronics. Note! The control panel is only for indoor use. 2. Lift the display out of the enclosure. 3. Push the connection cable through a suitable hole and if needed make an outlet for the cable in the side of the cover. 4.Mount the enclosure directly on the wall or using screws in a junction box. Push back the display in the enclosure. Fläkt Woods 8217 GB 2014.07.029 Specifications are subject to alteration without notice TopMaster Air Handling unit CONTROL AND REGULATION EQUIPMENT General, general buttons and symbols General General buttons and symbols This section of the instructions provides an introduction on how the Curo™ touch control panel works and it is intended to supplement the instructions for the air handling unit. The control panel is provided with a touch display. To navigate the menus, use either your finger or the back of a pen. When power is switched on all the menus are loaded up, which takes about 20–30 seconds. Then the panel displays the Home screen. The following buttons and symbols are universal and available on many menu pages. Home key, to return to the Home screen. Back button, to cancel and return to the previous page. Confirm button to confirm and proceed. Cleaning the screen Changing a value: Disconnect the power cord. Gently wipe the screen with a soft, dry non-abrasive cloth. If the marks remain, moisten the cloth slightly with a detergent that is designed for LCD or mobile screens and wipe the screen gently from top to bottom. Never use detergents, as these may contain ammonia or other additives. IMPORTANT: Option 1: Press the arrow keys to increase or decrease the value. Option 2: Press the displayed number to numerically adjust the value. Use the number buttons to enter a value. Home • Never spray, or pour liquids directly on to the screen. • Do not clean the screen while the system is on. 65 Confirm with or cancel with . Values that can only be read, but not written, are displayed without a surrounding window. Values that can be both read and written, are displayed with a surrounding window. Settings 1. Schedule 2. Run Commissioning Wizard 3. Timer Control Some submenus have several pages. Touch the upper or lower part of the scroll list to navigate between pages. 4. Fan Control 5. Heating / Cooling Fläkt Woods 8217 GB 2014.07.0210 Specifications are subject to alteration without notice TopMaster Air Handling unit CONTROL AND REGULATION EQUIPMENT Home screen overview Status line Heat recovery active Post-heater active Defrosting in progress Cooling active Current set point value 18°C Clock 11:08 Operating status Alarm Manual mode No alarm Automatic mode Alarm B Constant pressure Alarm A Constant air volume Timer 1 Timer 2 Timer 1/Timer 2 Operating modes Stop Trickle or low speed Normal or medium speed Boost or high speed Fläkt Woods 8217 GB 2014.07.0211 Specifications are subject to alteration without notice TopMaster Air Handling unit CONTROL AND REGULATION EQUIPMENT Operation, home screen and submenus Shortcut to set the temperature set point Shortcut to set the time and date Setpoint Temp Set Time Setpoint Temp. Alarm 18°C 11:08 Select operating mode See page 13. See page 13. User settings See page 13. Trickle or low speed Normal or medium speed Boost or high speed Press each field to select the operating mode. Only active in Manual mode. Fläkt Woods 8217 GB 2014.07.0212 Specifications are subject to alteration without notice TopMaster Air Handling unit CONTROL AND REGULATION EQUIPMENT Operation, submenus Operating modes User settings The operating status icon on the Home screen displays the current operating mode. To change the operating mode, press in the middle of the large fan icon. Manual Mode Stop Mode Automatic mode, the unit is controlled using schedules. Alarms No Alarm Alarm B Alarm A Here you set the desired setpoint. The default factory setting is 18 ° C. Other temperatures are read-only. Fan control status Symbol on Home screen shows alarm status. Setpoint temperatures Fan speeds and possible pressures and flow rates only for reading. Air quality Not in use for TopMaster. System overview Summarizes the unit’s main operating para meters. See section “Parameter list” on pages 23–27. Press the icon to enter the Alarm screen. No active alarms Active alarms Ack all Sensor fault supply air Ack Schedules Filter alarm Ack See section ”Schedules” on pages 17–19. Advanced operations Example 1: No alarm Example 2: Several alarms See section ”Advanced operations” on pages 14–15. Resetting the alarm To reset the alarm, press the Ack button after each alarm or Ack All (top right). If the alarm persists, it reappears on the display and the cause must be corrected before resetting. Fläkt Woods 8217 GB 2014.07.0213 Specifications are subject to alteration without notice TopMaster Air Handling unit CONTROL AND REGULATION EQUIPMENT Configuring time, date and language Settings Time/Date To enter the settings menu: Set Time 21 C 2:01 am 1. Press the gear cog button. 1. Set the time and press the Confirm button Set Date 2. Press the spanner button. 2. Set the date and press the Confirm button. Choose language Settings Set Language Set Time and Date Set Language Login 3. In this menu you set the date, time and language. It is also possible for installers and service personnel to log in and access additional parameters. Fläkt Woods 8217 GB 2014.07.0214 1. Choose the appropriate language flag and press the Confirm button. Note, further language flags are available after pressing the right arrow icon. Specifications are subject to alteration without notice TopMaster Air Handling unit CONTROL AND REGULATION EQUIPMENT Advanced settings Login Settings for installer and service personnel To enter the “Settings” menu for installers and service personnel requires login. The default passcode is 0000. This can be changed later. Enter passcode Settings 1. Schedule 2. Run Commissioning Wizard 3. Timer Control **** 4. Fan Control 5. Heating / Cooling Settings 6. Air Qualty 7. Alarm Configuration 8. Configure 9. Save Settings 10. Load Settings Settings 11. Logout 1. Enter the correct passcode and press the Confirm button. For commissioning of fans, see following section “Commissioning Wizard” on page 16. For other settings, see Parameter list on pages 23–27. Fläkt Woods 8217 GB 2014.07.0215 Specifications are subject to alteration without notice TopMaster Air Handling unit CONTROL AND REGULATION EQUIPMENT Commissioning Wizard Commissioning Wizard The Commissioning Wizard allows the fan settings to be configured in a simple and intuitive manner. The Commissioning Wizard is accessed by selecting the “Run Commissioning Wizard” option from the Settings screen. Settings Home 65 1. Schedule 2. Run Commissioning Wizard 3. Timer Control 4. Fan Control 5. Heating / Cooling Option 2 - Use the numerical keypad, confirm with. Option 1 Option 2 2. Extract Fan 2. Extract Fan Trickle 35% Trickle 35% Normal 65% Normal 67% Boost Boost 100% The speeds for each operating mode can be changed in two ways: Option 1 - Press Trickle, Normal or Boost Option 2 - Press the value 100% When finished with the settings, press the Confirm button and then make the corresponding settings for the supply fan. 2. Extract Fan -1 Trickle 35% Normal 65% Boost -10 +1 100% +10 Option 1 - Use the ±-buttons Fläkt Woods 8217 GB 2014.07.0216 Specifications are subject to alteration without notice TopMaster Air Handling unit CONTROL AND REGULATION EQUIPMENT Schedules Schedules Schedule The controller has three types of internal time schedules: Weekly, Single date and Date period. First, program the weekly schedule with the required times. Then use any single date programs and the period to enter exceptions, such as weekends and holidays. Each schedule also needs to be activated. This is done by pressing the grey tick button. A green tick indicates that the schedule is active. 16. Date period 4 Priority When several enabled applications overlap, the following applies: Highest priority: Date period 4 –– – Date period 1 – Day 4 –– –– – Single date 1 – Weekly 8 – – Lowest priority: Weekly 1 1.9. Date period 1 Schedule 1. Weekly 1 21 2. Weekly 2 3. Weekly 3 Weekly- schedule (1–8) With help of a weekly schedule the unit can be programmed to operate at trickle, normal and boost speed alternatively stop. Example 1 Below is an example of a weekly schedule configured to run the fans at normal speed from 08.00 to 18.00 Monday to Friday. At all other times, the fans are turned off. Day Time Fan speed Monday8–18 Normal Tuesday8–18 Normal Wednesday8–18 Normal Thursday8–18 Normal Friday 8–18Normal Other time Stop 4. Weekly 4 5. Weekly 5 1 Weekly 1 Fan speed Schedule 6. Weekly 6 7. Weekly 7 Normal Temp set point Rel From Mon Daily 08:00 0°C To Fri 18:00 8. Weekly 8 Single date 1 9. Single date 1 10. Single date 2 Only Weekly 1 should be activated. Schedule 11. Single date 3 12. Single date 4 13. Date period 1 14. Date period 2 15. Date period 3 Fläkt Woods 8217 GB 2014.07.0217 Specifications are subject to alteration without notice TopMaster Air Handling unit CONTROL AND REGULATION EQUIPMENT Schedules (cont.) Example 2 Example 3 Below is an example of a weekly schedule configured to run the fans at normal speed from 08.00 to 18.00 Monday to Thursday, from 08.00 to 17.00 on Friday and 10.00 to 14.00 on Saturday. At all other times, the fans are turned off. Below is an example of a weekly schedule configured to run the fans at normal speed from 08.00 to 18.00 Monday to Friday. At all other times, the fans are configured to run at trickle speed. At trickle speed the temperature set point will be decreased by two degrees. Day Time Fan speed Monday8–18Normal Tuesday8–18Normal Wednesday8–18 Normal Thursday8–18 Normal Friday 8–17Normal Saturday10–14 Normal Other time Stop Day Time Monday 8–18 Normal 0 °C Tuesday 8–18 Normal 0 °C Wednesday 8–18 Normal 0 °C Thursday 8–18 Normal 0 °C Friday 8–18 Normal 0 °C Trickle (Low) –2 °C Other time 1 Weekly 1 1 Weekly 1 Fan speed Normal Temp set point Rel From Mon Daily 08:00 0°C To Fan speed Fri From Mon 18:00 Daily 00:00 Stop Rel Fri Daily 17:00 Rel To -2°C Sun 23:59 2 Weekly 2 Fan speed From Trickle Temp Setpoint 2 Weekly 2 Tem Setpoint Fan speed Temp. setpoint 0°C To Fan speed Normal Temp Setpoint Rel Fri From Mon 18:00 Daily 08:00 To 0°C Fri 18:00 Only Weekly 1–2 should be activated. 3 Weekly 3 Fan speed Normal Temp Setpoint Rel From Sat Daily 10:00 To 0°C Sat 14:00 Only Weekly 1–3 should be activated. Fläkt Woods 8217 GB 2014.07.0218 Specifications are subject to alteration without notice TopMaster Air Handling unit CONTROL AND REGULATION EQUIPMENT Schedules (cont.) Single date schedule (1–4) A single date schedule is defined as a one-off schedule that automatically starts and finishes on the same date. Example The unit must be switched off on 6 June. Note! Remember to enable the desired time channels by pressing 1. Single date 1 Stop Fan speed Temp Setpoint Rel Date 6-Jun-2014 0°C Date period schedule (1-4) A date period schedule is defined as a one-off schedule that is configured to run between any two dates. Example The unit must be switched off between 24 December and 26 December. Stop Fan speed Fläkt Woods Temp Setpoint Rel Start date 24-Dec-2014 Stop date 26-Dec-2014 0C 8217 GB 2014.07.0219 Specifications are subject to alteration without notice TopMaster Air Handling unit CONTROL AND REGULATION EQUIPMENT Control functions • Continuously rotating heat exchangers Room control and exhaust air control is the same control type with the difference that in combination with room control an external room sensor is needed (separate ordering code). In addition it is possible to use outdoor temperature compensation. This control mode cannot be combined with extract air control or room control. The unit is configured for supply air control as standard. To obtain other control modes, first the controller must be changed from standard mode to cascade mode. Then control mode is selected by changing the cascade reference to extract air control/room control (0) or outdoor temperature compensation (1). Below is a description of the different control modes. Choice of cooling Supply air control 1. Rotor, heating and cooling The unit is configured differently with regard to heating, heat recovery and cooling, see below. Choice of heating function • No heater • Electric heater • A water heater with frost-guard function Heat recovery • No cooling To maintain a constant supply air temperature, the controller works from a fixed setpoint and the supply air temperature. Based on these parameters, the controller controls the current heating, heat recovery and cooling sequences. • Water -cooling • DX cooling, 1-stage Control function The control function works as follows: Regardless of control mode the unit tries to achieve the desired setpoint. This is done by the unit depending on the needs, demand for heat recovery, heating or cooling. Built into the system is also a dead zone. The dead zone function (usually 2°C) acts as a temperature zone between heat recovery and cooling unit where neither calls for heat recovery or cooling. The reason for having a dead zone, is that the temperature will be slightly lower in winter, and slightly higher in summer. This is energy-efficient and in practice even more convenient for people staying in the room. Control signal, % Sequence control Extract air control The exhaust air temperature gives a good average value of the temperature in different rooms. Using this the unit controls the supply air temperature to maintain the extract temperature at a desired level. This method is suitable for ventilation systems that supply a number of similar rooms. In cases where different rooms have different heating requirements, this method should not be used. This is because the unit cannot detect the varying heating needs, but can only read an average temperature. The limits on the supply air temperature (min. temp. / max. temp.) ensure that the supply air temperature is maintained within the set range. Default parameters for extract air control ver o Rec ting Hea Coo ling 100 1. Controller = 2 Selects cascade control 3. Cascade A = 0.5 When the sensor gets colder than given setpoint value 2. Cascade reference = 0 y 50 4. Cascade B = –0.5 5. Min. temp. = 15°C T0 T1 T2 T3 T4 Temperature, °C Figure 1. The figure shows the controller’s output signals to the various unit components at different temperatures. The figure also shows two temperatures, one for heating (T2) and one for cooling (T3). The zone between T2 and T3 is called the dead zone. Note that heating is activated only when heat recovery is working at 100%. 2. Temperature controls TopMaster has three temperature control options, supply air, extract air control and room control. Fläkt Woods 8217 GB 2014.07.0220 6. Max. temp. = 25°C Selects extract air control When the sensor gets hotter than given setpoint value Sets lowest supply air temperature Sets highest supply air temperature Example 1. Setpoint = 18°C 2. Extract air temperature = 16°C This means that the new calculated setpoint for the supply air controller is: Calculated setpoint = setpoint + (setpoint – exhaust air temperature) x cascade A = 18 + (18-16) x 0.5 = 19 ° C. Specifications are subject to alteration without notice TopMaster Air Handling unit CONTROL AND REGULATION EQUIPMENT Control functions (cont.) Room control Room control gives the best control of temperature in a specific room and is used when only one unit serves this room. This method works best for larger premises. By replacing the exhaust temperature sensor with a room temperature sensor placed in the room in question, a good room temperature value is achieved. This enables the unit to regulate the supply air temperature in a way that maintains the room temperature at a desired level. Limitation of the supply air temperature (min. temp. and max. temp.) ensures that the supply air temperature is maintained within the set range. Default parameters for room control 1. Controller = 2 Selects cascade control 3. Cascade A = 0.5 When the sensor gets colder than given setpoint value 2. Cascade reference = 0 4. Cascade B = –0.5 Selects room control When the sensor gets hotter than given setpoint value 5. Min. temp. = 15°C Sets lowest supply air temperature 6. Max. temp. = 25°C Sets highest supply air temperature Example 1. Setpoint = 18°C 2. Room temperature = 22° This means that the new calculated setpoint for the supply air controller is: Calculated setpoint = setpoint + (setpoint – room air temperature) x cascade B = 18 – (18 – 22) x (–0.5) = 16°C. Outdoor temperature compensation The setpoint temperature for supply air can be adjusted up or down depending on the outdoor temperature. By setting a higher set point value both on cold winter days and hot summer days indoors comfort is improved. In summer, this will increase energy savings. Outdoor temperature compensation can not be combined with extract air control or room control. Default parameters for outdoor temperature compensation 1. Controller = 2 2. Cascade reference = 1 3. Cascade A = 0,05 4. Cascade B = 0.03 5. Min. temp. = 15°C 6. Max. temp. = 25°C Fläkt Woods Selects cascade control. Selects outdoor temperature compensation. When the sensor gets colder than given setpoint value. When the sensor gets hotter than given setpoint value. Sets lowest supply air temperature. Sets highest supply air temperature. 8217 GB 2014.07.0221 Setpoint Outdoor temperature compensation +30 +25 +20 +15 –20 –15 –10 –5 0 5 10 15 20 25 30 35 Outdoor temperature, °C Example 1 1. Setpoint = 18°C 2. Outdoor air temperature = –2°C This means that the new calculated setpoint for the supply air controller is: Calculated setpoint = setpoint + (setpoint – outdoor air temperature) x cascade A = 18 + (18 –(-2)) x 0.05 = 19°C Example 2 1. Setpoint = 18°C 2. Outdoor air temperature = 28°C This means that the new calculated setpoint for the supply air controller is: Calculated setpoint = setpoint + (setpoint – outdoor air temperature) x cascade B = 18 – (18 – 28)) x 0.30 = 21°C. 3. Freeze protection Warning! Do not change these parameters unless it is absolutely necessary. If the unit is misconfigured the water coil can freeze up and cause water damage to property. Freeze protection is used during low outdoor temperatures to prevent the coil from freezing. When the unit is stopped, the temperature in the water coil is maintained at the setpoint to keep the unit warm. If there is a risk of freezing in the water coil the motorized valve is controlled to open. If the temperature drops below the adjustable limit value an A-alarm is obtained, which then stops the unit. 4. Defrost function The defrost function is used to prevent the rotor from freezing. By measuring the pressure across the rotor it is possible to verify when the rotor needs to be defrosted. When the pressure over the rotor becomes too high it activates a time delay before defrosting. Then defrosting starts. When the pressure is below the given limit value it starts a time delay. When the time delay has elapsed, the defrosting stops Defrosting is achieved by running the rotor sectionwise. Fan speeds are not affected. Specifications are subject to alteration without notice TopMaster Air Handling unit CONTROL AND REGULATION EQUIPMENT Control functions (cont.) 5. Cooling recovery Cooling energy recovery is used when cooling load is needed by taking advantage of any room cooling. Cooling recovery is activated if the outdoor temperature is 2° C higher than the extract air temperature and the unit is operating in “summer mode”. If this condition is satisfied the rotor starts and supplies 100%. 6. Night cooling Night cooling is used in summertime to reduce cooling load at unit start-up and to limit the maximum temperature during non-working hours. This is done by making use of cold outside air during cool summer nights. Parameters Yes Room setpoint night cooling 5°C Min difference room temp. 2°C Hysteresis for night cooling Hysteresis Test time, start kl. 22.00 Start time for night cooling test Test time, off kl.22.15 Stop time for night cooling test Max time 540 minutes Maximal activation time for night cooling 1. Starting conditions a. Night cooling activated b. Auto mode enabled c. The unit is in the stop position as scheduled 2. Test period and evaluation a. The unit is started at. 22.00 and then operates at normal speed b. At 22.15 it is determined whether night cooling is needed or not. The following conditions must be met: 1. The unit is in “Summer mode” . 3. Extract temperature > Room setpoint + Hysteresis. c. Control principle in which the unit maintains a constant duct flow. Pressure sensors are supplied as loose accesso ries. Using a measurement pressure Dpm in Pa and a constant k, the airflow q in l/s is calculated with the following formula: q = 1000 x Δpm k Activated night cooling 22°C Delta Constant Flow Control (CAV) Value (exemple) Comment Night cooling activated Room setpoint Pressure control regulates air pressure in index duct (duct with a maximum pressure drop, and where the static pressure is lowest). The pressure sensor (GP3) is placed at the beginning of this duct The exhaust sensor (GP4) is placed in the exhaust duct at a suitable location with representative pressure. For settings see the Parameter list. 2.Outdoor temperature < Extract temperature – Delta. If the above conditions are met the night cooling starts. 3. The following take place during night cooling a. Rotor, afterheater and any cooling are blocked. b. The fans are switched to the high speed setting. The measuring pressure, Dpm, is the difference between the pressure in the empty section at the fan inlet and the pressure inside the inlet cone. The pressure sensor is connected via two externally placed measuring nipples. Value of the constant (k) is shown in the table below. For settings see the parameter list. Size k-value extract air fan k-value supply air fan a. Unit is in “Summer mode”. b. Outdoor temperature < Extract temperature – Delta. c. Extract temperature > Room setpoint. d. Function’s maximum activation time is not reached. 6. Pressure or flow control Pressure control (COP) Control principle in which the unit maintains a constant duct pressure. Normally used in variable flow systems (VAV). Pressure sensor is supplied as a loose accessory. Fläkt Woods 8217 GB 2014.07.0222 050 41 49 Connection of pressure sensors The pressure sensor shall be set to the working range of 0 –500 Pa. Location Terminal Connection Y Supply air duct GP3 G0 G Y Extract air duct GP4 G0 G No. Pressure sensor 520–10 V 51 GND 50 24 V DC 550–10 V 54 GND 53 24 V DC Zero point-calibration push-button LED 4. Night cooling takes place as long as the following conditions are fulfilled: 030 56 55 LED Jumper 1 Jumper 2 Jumper 3 0-10V 4-20mA 24VDC GND Jumper 1 Jumper 2 Jumper 3 The sensors must be zeroed during commissioning. They should then be zeroed annually. The sensors should have been energized for approximately one hour before calibration is carried out. After that, remove the hoses from the sensors. To start calibration press the push-button next to the pressure range jumpers. The red LED lights up and goes out after about a second. Reassemble the air hoses. Done! Specifications are subject to alteration without notice TopMaster Air Handling unit CONTROL AND REGULATION EQUIPMENT Parameter list Some parameters and functions have a more detailed explanation after the parameter list. The Curo ™ Touch control panel has a wide range of applications. Only relevant parameters are listed below. It is strongly recommended to avoid the adjustment of any system parameters that are not outlined in this section. Parameter Type of value1) Range Unit Default value Comments Temperature status Setpoint R/W15–35 °C 18 Desired setpoint. Actual setpoint for supply air. Actual setpoint R 15–35 °C - Used for extract air control or out door temperature compensation. Supply air R -40–100 °C - Supply air temperature. Outdoor air R -40-100 °C - Outdoor air temperature. Extract / Room R -40–100 °C - Extract air / Room temperature. Freeze protection R -40–100 °C - Freeze protection temperature. Fan status Supply air fan, speed R 0 or 30–100% - Extract air fan, speed R 0 or 30–100% - Air qual ity No such function in TopMaster. Overview This menu is used for maintenance and troubleshooting. Software version, Control panel R - - - Speed, Supply air fan R 0 or 30–100% - Speed, Extract air fan R 0 or 30–100% - Output, Post-heater E 0–100% - Output, Pre-heater R - - - No such function in TopMaster. Output, Heat recovery R 0–100% - Outout, Cooling R 0–100% - Summer/Winter mode R Summer/Winter - - Supply air temperature R -40–100°C - Supply air temperature R -40–100°C - Extract air temperature R -40–100°C - “Cold corner” temperature R - - - No such function in Topmaster. Freeze protection temperature R -40–100 °C - Only in case of water heating. Setpoint set R/W 15–35°C 18 Operation codes R - - - No such function in Topmaster. Schedules Only reading, programming of schedules is done under Settings. Weekly 1-8 R Daily 1-4 R Date period 1-4 R Settings Time / Date R/W This can also be done directly from the home page. Choose language R/W English Login R/W0000–9999 0000 For installers and service personnel. Settings For installers and service personnel. 1. Schedules See page 17. 1) R/W = Read and write value, R = Read only value Fläkt Woods 8217 GB 2014.07.0223 Specifications are subject to alteration without notice TopMaster Air Handling unit CONTROL AND REGULATION EQUIPMENT Parameter list (cont.) Parameter Type of value1) Range Unit Default value Comments 2. Commissioning Wizard See page 16 3. Timer functions See page 5. Timer function R/W 1–5 2 Timer off delay R/W 0–999min 0 4. Fans 4.1 Speed of fans Commissioning of fans is done in menu 2, Commissioning Wizard. Automatic return to the previous Auto Stop forced mode R/W Yes/No No operating mode in the choice of high speed. Forcing time R/W 0–9999 min 120 Time before return, see above. Start delay R/W 0–32767 s 10 During this time SF and rotor run. Off delay R/W 0–32767 s 0 After cooling, set to 180 s at electric heater. Pressure/Flow control of fans 4.2 Pressure / Flow The unit must be equipped with pressure sensors. See page xx. If pressure control Pressure control supply air R/W Yes/No Yes Pressure control extract air R/W Yes/No Yes Only SF, EF slave R/W Yes/No No Proportion SF / EF R/W 0–200 % 100 Only if the above parameter is active. Supply air pressure setpoint R/W 0–2000Pa 150 Extract air pressure setpoint R/W 0–2000Pa 150 If flow control Flow control supply air R/W Yes/No Yes Flow control extract air R/W Yes/No Yes Only SF, EF slave R/W Yes/No No Proportion SF / EF R/W 0–200 % 100 Only if the above parameter is active. Supply air flow, low speed R/W 0–9999l/s 80 Supply air flow, normal speed R/W 0–9999l/s 100 Supply air flow, high speed R/W 0–9999l/s 120 Extract air flow, low speed R/W 0–9999l/s 80 Extract air flow, normal speed R/W 0–9999l/s 100 Extract air flow, high speed R/W 0–9999 120 5. Heating / Cooling 5.1 Pre-heater No such function in TopMaster. 5.2 Heating / Cooling See also pages 20–22. Control mode R/W 1-2 1 1 = Standard, supply air control 2 = Cascade control. Cascade reference R/W 0-1 0 0 = Extract air control 1 = Outdoor air compensation. Cooling sequence R/W Yes/No No Cooling sequence activated. DX-cooling R/W Yes/No No Dead zone cooling R/W Yes/No Yes Dead zone cooling activated. Dead zone R/W 0–25°C 2 Block cooling in winter R/W Yes/No Yes Block heating in summer R/W Yes/No Yes Post-heater R/W Yes/No Yes Absolute/Relative temperature R/W abs/rel rel Absolute or relative temperature in schedules. 1) R/W = Read and write value, R = Read only value Fläkt Woods 8217 GB 2014.07.0224 Specifications are subject to alteration without notice TopMaster Air Handling unit CONTROL AND REGULATION EQUIPMENT Parameter list (cont.) Parameter Type of value1) Range Unit Default value Comments 5.3 Night cooling See also pages 20-22. Night cooling R/W Yes/No No Activated from factory if unit is ordered with night cooling. Set point room temperature R/W 15-50 °C 20 Test time start R/W 19.00–04:00 22.00 Test time stop R/W 19.00–04:00 22.5 Hysteresis R/W 0-20°C 2 Delta R/W 0-20°C 5 Max. time R/W 1-720 min 540 5.4 Defrosting Parameters unalterable. See also pages 20-22. 5.5 Cooling recovery See also pages 20-22. Cooling recovery R/W Yes/No - Yes Temperature difference R/W 0-15°C 2 Outdoor air – Extract air 5.6 Summer / Winter mode Summer / Winter mode R Summer/Winter - - Summer, if outdoor temp. >18° or >15 ° for more than 6 hours or Automatic / Manually R/W Auto/Manually - Auto Winter, if outdoor temperature <12° <15° for >6 hours. Winter/Summer R/W Summer/Winter- Winter 5.7 Freeze protection See also page 20-22. Keeping warm R/W 0–50°C 25 Setpoint min. mode temp. R/W 0–50°C 12 Setpoint freeze protection alarm R/W 0–50°C 5 Pump stop R/W Yes/No Yes No = continuous operation of pumps Heat pump runs when heating is required, cooling pump runs when Pump stop mode R/W Summer/Winter, heating/cooling S / W = heat pump runs in winter, heating/cooling cooling pump runs in the summer. Anti-jamming of pumps takes place 12.00 to 12.05 every day. 6. Air quality No such function in TopMaster. 7. Alarm handling 7.1 Alarm Filter alarm time R/W 0–600 days 0 0 = Disabled. Yes = Sum alarm at both A and B alarm. No = Sum alarm at Sumalarm output A+B R/W Yes/No Yes A alarm. Sum alarm output max 24V, 200mA. Activate temperature alarm R/W Yes/No No No = Temperature alarm disabled. Temperature alarm R/W -10–10 °C 10 The alarm occurs when the supply air temperature is lower than the limit >10 min. 7.2 Alarm categories Fire alarm R/W A/B A Sensor fault supply air R/W A/B A Sensor fault outdoor air R/W A/B A Sensor fault extract air/room R/W A/B A Sensor fault freeze protection R/W A/B A 1) R/W = Read and write value, R = Read only value Fläkt Woods 8217 GB 2014.07.0225 Specifications are subject to alteration without notice TopMaster Air Handling unit CONTROL AND REGULATION EQUIPMENT Parameter list (cont.) Parameter Type of value1) Range Unit Default value Comments Sensor fault Cold corner Not used in TopMaster. Sensor fault UI1 Not used in TopMaster. Sensor fault UI2 Not used in TopMaster. Sensor fault UI3 Not used in TopMaster. Sensor fault UI4 Not used in TopMaster. Sensor fault UI5 Not used in TopMaster. Filter alarm Not used in TopMaster. Fan monitor supply air R/W A/B A Fan monitor extract air R/W A/B A Pressure switch HRU R/W A/B B Rotor pressure switch R/W A/B B Filter alarm supply air R/W A/B B Filter alarm extract air R/W A/B B Overheating electric heater R/W A/B A Circualation pump heating R/W A/B A Freeze-protection R/W A/B A Sum alarm cooling R/W A/B A Circulation pump cooling R/W A/B A Temperature alarm R/W A/B A Rotor belt alarm R/W A/B A 7.3 Alarm delays Fire alarm delay R/W 0–9999s 2 Sensor fault supply air delay R/W 0–9999s 5 Sensor fault outdoor air delay R/W 0–9999s 5 Sensor f. extract air/room delay R/W 0–9999s 5 Sensor f. freeze-protection delay R/W 0–9999s 5 Sensor fault Cold corner delay Not used in TopMaster. Sensor fault UI1 delay Not used in TopMaster. Sensor fault UI2 delay Not used in TopMaster. Sensor fault UI3 delay Not used in TopMaster. Sensor fault UI4 delay Not used in TopMaster. Sensor fault UI5 delay Not used in TopMaster. Fan monitor supply air delay R/W 0–9999s 2 Fan monitor extract air delay R/W 0–9999s 2 Rotor pressure switch delay R/W 0–9999s 2 Filter alarm supply air delay R/W 0–9999s 60 Filter alarm extract air delay R/W 0–9999s 60 Overheat electric heater delay R/W 0–9999s 2 Circulation pump heating delay R/W 0–9999s 2 Freeze-protection delay R/W 0–9999s 2 Sum alarm cooling delay R/W 0–9999s 2 Circulation pump cooling delay R/W 0–9999s 2 Temperature alarm delay R/W 0–9999min 10 7.4 Contact functions DI1 Timer input 1 R/W 0=NC, 1=NO NO DI2 Timer input 2 R/W 0=NC, 1=NO NO DI3 Rotor pressure switch R/W 0=NC, 1=NO NO DI4 Pressure switch defrosting R/W 0=NC, 1=NO NO DI5 Fan prot./Filter monitor SF R/W 0=NC, 1=NO NO DI6 Fan prot./Filter monitor EF R/W 0=NC, 1=NO NO UI1 Fire alarm R/W 0=NC, 1=NO NC UI2 Not used in TopMaster. UI3 Alarm heater R/W 0=NC, 1=NO NO NC at electric heater. UI4 Alarm cooler R/W 0=NC, 1=NO NO UI5 Tacho signal rotor R/W 0=NC, 1=NO NO Not to be changed. 1) R/W = Read and write value, R = Read only value Fläkt Woods 8217 GB 2014.07.0226 Specifications are subject to alteration without notice TopMaster Air Handling unit CONTROL AND REGULATION EQUIPMENT Parameter list (cont.) Parameter Type of value1) Range Unit Default value Comments 8. Configuration 8.1 IP address Static = IP address is manually set. Static/Dynamic R/W Static/Dynamic Dynamic Dynamic = IP-address is automa tically set via DHCP. IP- address Subnet mask 8.2 Menu configuration Logon to USB R/W Yes/No No Is set to Yes for copying the log files to the USB memory. Unit type L TopMaster Auto logout R/W 0–32767 min 10 Time before automatic logout occurs in the control panel. Thresholds Not used in Topmaster. 8.3 Screen saver Screen saver R/W Yes / No Yes Time R/W min 10 Time before the screen saver is activated in the control panel. 8.4 Modbus Sea also the Modbus manual. Address BMS R/W 2 Baud rate R/W 9600, 19200, 9600 38400 Parity R/W none, odd, even none Data bit R/W 7,8 8 Stop bit R/W 1,2 1 8.5 MAC address Displays the network card MAC address L MAC address. 8.7 Password Automatic logout R/W Yes/No Yes Password 1 R/W 0000-9999 0000 The password can be changed. If passcode is forgotten, Fläkt Woods must be contacted. 8.8 About Software HMI L Displays the current software version of the control panel. Software Control card L Displays the current software of the control card. 9. Save values Store the set values in the control panel (to copy to another unit). 10.Uploading values Uploading saved values to unit. 11. Save to SD Stored values can be saved in SD card, this requires that the values have already been saved in menu 9. 12.Load from SD Stored values may be loaded from the SD card. 13. Log out 1) R/W = Read and write value, R = Read only value Fläkt Woods 8217 GB 2014.07.0227 Specifications are subject to alteration without notice We Bring Air to Life Fläkt Woods is a global leader in air management. We specialize in the design and manufacture of a wide range of air climate and air movement solutions. FWG_TopMaster_Control and Regulation equipment_GB 2014.07.02_8217 © Copyright 2014 Fläkt Woods Group Condesign_ABS5953 Our collective experience is unrivalled. We are constantly aiming to provide systems that precisely deliver the required features and performance as well as maximum energy efficiency. Fläkt Woods Group SA 18, avenue Louis Casaï, CH-1209 Geneva, Switzerland Tel. +41 22 309 3800 email [email protected] www.flaktwoods.com See global website for international sales offices www.flaktwoods.com