ED 9035-1 Rooftop Air Handler Dimensional Data

Transcription

ED 9035-1 Rooftop Air Handler Dimensional Data
Engineering Data
Rooftop Air Handler Dimensional Data
ED: 9035-1
Group: Applied AIr
Date: October 2007
Supercedes: 9035
Type RDS 708B, 800C & 802C
Type RAH 047C & 077C
©2007 McQuay International
Dimensional Data — RDS 708B
Section Options and Locations
Figures show section options, curb lengths, and relative positions. Curb lengths (in inches) are shown below each icon.
Figure 1: RDS 708B
Position A
Outdoor Return Air
Position B
Filter
Position C
Heat/Cool
Position D
Supply Air Fan
Position E
Blank
Position F
Final Filter*
Position G
Discharge Plenum
Outdoor Air Hood
Angular
Drain Pan Only
Front Discharge
Blank Access
Cartridge
Discharge Plenum
0”
33”
48”
33”
33”
33”
33”
Return Plenum
Cartridge
Short Coil
Down Discharge
Blank Access
33”
33”
S
P
A
3
2
1
C
E
R
33”
33”
48”
30% Outside Air
Long Coil
S
P
A
3
2
1
C
E
R
33”
48”
Mixing Box
Short Coil with
Face & Bypass
S
P
3
2
1
A
C
E
R
33”
Economizer
Long Coil with
Face & Bypass
* When Final Filter section is provided, a Blank section (Position E)
and a Discharge Plenum (Position G) are required.
S
1
P
3
2
A
C
E
R
48”
66”
Economizer with
Return Air Fan
66”
Section Diagram — RDS 708B
P o s itio n E
B la n k
P o s itio n A
O u td o o r/R e tu rn
A ir
©2007 McQuay International
P o s itio n B
F ilte r
P o s itio n C
H e a t/C o o l
P o s itio n D
S u p p ly A ir F a n
P o s itio n F
F in a l F ilte r *
B lo w - T h r o u g h
S e c tio n s
P o s itio n G
D is c h a r g e P le n u m
M a n d a to r y S e c tio n
S e le c tio n R e q u ir e d
O p tio n a l S e c tio n
2
Basic Unit
Figure 2: Basic Unit
Fan Size
7.75
52.0
A
B
C
15” x 6”
10.38
27.94
17.00
15” x 9”
13.94
26.19
17.00
15” x 15”
19.75
23.25
17.00
16”
24.75
20.75
22.80
Airflow
Optional Outlet Dampers
7.75
Draw-Through Coil Section
Angular Filter
Section
Supply Fan Section
67.5
2.88
50.88
45.0
C
11.0
3.0
1.5*
114.0
B
B
A
66.25
*Dimension is distance from bottom of unit floor to top of roof curb.
Position A - Outdoor/Return Air Section
Figure 3: Outside Air Hood
o
o
Figure 4: Return Air Plenum
o
L e s s D a m p e rs
W ith D a m p e r s
o
B o tto m R e tu rn
B a c k R e tu rn
8 .7 5
7 .7 5
B o tto m
1 1 .2 5
7 .7 5
R e t u r n O p e n in g
5 2 .0
5 2 .0
A ir flo w
A ir flo w
4 5 .0
5 0 .0
7 .7 5
7 .7 5
1 1 .2 5
6 .5
8 .7 5
6 .5
2 8 .0
O p t io n a l 1 0 0 %
D a m p e rs
O p t io n a l B o tto m
R e tu r n O p e n in g
3 2 .0
9 .5
2 2 .0
2 0 .0
4 .5
3 3 .0
N o t e : T h is o p t io n d o e s n o t a ffe c t u n it c u r b le n g th .
©2007 McQuay International
3
Position A - Outdoor/Return Air Section (continued)
Figure 5: Return AIr Plenum - 30% Outside AIr Hood
o
o
Figure 6: Outside/Return Air Mixing Box
B o tto m R e tu rn
B a c k R e tu rn
o
8 .7 5
7 .7 5
B o tto m
B o tto m
R e tu rn
R e t u r n O p e n in g
7 .7 5
5 2 .0
A ir flo w
5 0 .0
5 0 .0
2 0 .0
6 .5
8 .7 5
R e t u r n O p e n in g
5 2 .0
A ir flo w
7 .7 5
B o tto m
8 .7 5
1 2 .0
7 .7 5
M a n u a l D a m p e r L in k a g e
6 .5
8 .7 5
2 0 .0
O u t s id e A ir D a m p e r s
W e a th e rh o o d
1 3 .7 5
2 2 .0
3 3 .0
4 .5
2 8 .0
O p t io n a l B o tto m
R e tu r n O p e n in g
3 3 .0
R e tu r n A ir
D a m p e rs
2 0 .0
Figure 7: Economizer
o
B o tto m R e tu rn
B a c k R e tu rn
o
R e t
o 1
o 1
o 1
o 1
u r
5 "
5 "
6 "
6 "
n F
x 1
x 1
A ir
A ir
B o tto m
a n :
5 " F o rw a rd C u rv e d
5 " F o r w a r d C u r v e d w ith In le t V a n e s
fo il
fo il w it h In le t V a n e s
R e t u r n O p e n in g
O u t s id e A ir In le t H o o d s
8 .7 5
1 1 .0
A ir flo w
5 0 .0
Fan Size
a n S iz e
15” x F 15”
16”
1 5 " x 1 5 "
1 6 "
O u t s id e a n d
R e tu rn D a m p e rs
A
A 7.81
7 .8 1
9 . 8 8 9.88
1 1 .0
8 .7 5
O p t io n a l B a c k
R e tu r n O p e n in g
1 1 .0
E x h a u s t d a m p e r a n d H o o d
6 .5
3 0 .0
O p t io n a l R e t u r n F a n
A
3 8 .0
5 .0
O p t io n a l In le t D a m p e r
( w ith R e tu r n F a n o n ly )
N o t e : O p tio n a l in le t d a m p e r a v a ila b le w ith fo r w a r d c u r v e d r e tu r n fa n o n ly .
©2007 McQuay International
4
Position B - Draw-through Filter Section — Mandatory Selection
Figure 8: Angular Filters
o
o
o
Figure 9:
T h ro w a w a y
3 0 % E ffic ie n c y
C le a n a b le
o
o
Cartridge Filter with Prefilter
6 5 %
9 5 %
E ffic ie n c y
E ffic ie n c y
A ir flo w
A ir flo w
P r e filte r s
A n g u la r F ilte r s
C a r tr id g e F ilte r s
3 3 .0
3 3 .0
F ilte r Q u a n
4 - 2 0 x 2
o
6 - 2 0 x 2
r
tity & S iz e
5 x 2 (1 )
6 5 % E ffic
1 - 2 4 x 2 4 x 1 2
1 -1 2 x 2 4 x
o r
2 - 2 4 x 2 4 x
2 - 1 2 x 2 4
5 x 2 (2 )
N o te s :
( 1 ) F ilte r r e q u ir e m e n t fo r a 1 5 " x 6 " s u p p ly fa n o n ly .
( 2 ) F ilte r r e q u ir e m e n t f o r a 1 5 " x 9 " , 1 5 " x 1 5 " o r 1 6 " s u p p ly fa n .
F
ie
(
1
ilte r Q u a n tity & S iz e
n c y
9 5 % E ffic
1 )
2
2 - 2 4 x 2 4
o r
1 2 (2 )
2 - 2 4 x 2 4
x 1 2
3 - 1 2 x 2
ie n c y
x 1 2 (1 )
4
x 1 2 (2 )
x 1 2
N o te s :
( 1 ) F ilte r r e q u ir e m e n t fo r a 1 5 " x 6 " s u p p ly fa n o n ly .
( 2 ) F ilte r r e q u ir e m e n t f o r a 1 5 " x 9 " , 1 5 " x 1 5 " o r 1 6 " s u p p ly fa n .
Position C - Draw-through Heat/Cool Section — Mandatory Selection
Figure 10: Drain Pan Only
o
Figure 11: Drain Connection Detail
D r a in P a n O n ly
A ir flo w
A ir flo w
3 .8 3
1 -1 /2 " M P T
D r a in C o n n e c tio n
( S e e D r a in D e ta il)
1 -1 /2 "
M P T
1 2 .6 8
4 8 .0
©2007 McQuay International
5
Position C — Draw-through Heat/Cool Section — Mandatory Selection
Figure 12: Short Coil
o
Figure 14: Short Coil with Face & Bypass
o
o
C h ille d W a te r
E v a p o ra to r
H o t W a te r
S te a m
o
o
o
o
o
R e c o m m e n d e d
C o il P ip in g
E n te ra n c e
1 .0
3 3 .0
C h ille d W a te r
E v a p o ra to r
H o t W a te r
S te a m
R e c o m m e n d e d
C o il P ip in g
E n te ra n c e
8 .0
A ir flo w
F a c e & B y p a s s
D a m p e rs
1 - 1 /2 " M P T D r a in
C o n n e c tio n
( S e e D r a in D e ta il)
S
S
P
A
3
2
C
P
A
C
E
E
R
Figure 15: Long Coil with Face & Bypass
Figure 13: Long Coil
o
6 .0
N o te C o il
P o s itio n s
6 .0
N o te C o il
P o s itio n s
o
3
2
1
R
o
1 - 1 /2 " M P T D r a in
C o n n e c tio n
( S e e D r a in D e ta il)
4 8 .0
4 8 .0
o
8 .0
9 .0
9 .0
A ir flo w
1
1 .0
3 3 .0
o
C h ille d W a te r
E v a p o ra to r
H o t W a te r
S te a m
o
o
o
R e c o m m e n d e d
C o il P ip in g
E n te ra n c e
1 .0
6 .0
C h ille d W a te r
E v a p o ra to r
H o t W a te r
S te a m
8 .0
R e c o m m e n d e d
C o il P ip in g
E n te ra n c e
1 .0
6 .0
8 .0
1 8 .0
1 8 .0
A ir flo w
A ir flo w
1 - 1 /2 " M P T D r a in
C o n n e c tio n
( S e e D r a in D e ta il)
F a c e & B y p a s s
D a m p e rs
1 - 1 /2 " M P T D r a in
C o n n e c tio n
( S e e D r a in D e ta il)
4 8 .0
4 8 .0
S
P
1
A
S
3
2
C
E
1
R
P
3
2
C
A
E
R
N o te C o il
P o s itio n s
6 .0
N o te C o il
P o s itio n s
6 .0
N o t e : C o il p ip in g v e s tib u le r e q u ir e d ( s e e F ig u r e X X fo r d e t a il d r a w in g ) .
©2007 McQuay International
6
Position D — Supply Air Fan Section — Mandatory Selection
Figure 16: Front Discharge Fan
o
o
o
o
o
o
1 5 "
1 5 "
1 5 "
1 5 "
1 6 "
1 6 "
x 6 "
x 9 "
x 1 5
x 1 5
A ir fo
A ir fo
F o rw a
F o rw a
" F o rw
" F o rw
il
il w it h
rd C
rd C
a rd
a rd
u rv e
u rv e
C u rv
C u rv
Figure 18: Down Discharge Fan
o
d
d
o
o
e d
o
e d w it h In le t V a n e s
1 5 "
1 5 "
1 5 "
1 5 "
x 6 "
x 9 "
x 1 5
x 1 5
F o
F o
" F
" F
rw a r
rw a r
o rw a
o rw a
d C u
d C u
rd C
rd C
rv e
rv e
u rv
u rv
d
d
e d
e d w it h In le t V a n e s
In le t V a n e s
0 .6 3
F a
1 5
1 5
1 5
n
" x
" x
" x
1 6
S iz e
6 "
9 "
1 5 "
"
1 0
1 3
1 9
2 4
A
.3
.9
.7
.7
8
4
5
2 7
2 6
2 3
2 0
5
B
.9
.1
.2
.7
4
9
5
5
1 7
1 7
1 7
2 2
C
.0
.0
.0
.8
0
0
0
B
0
A
A ir flo w
B
F a
1 5
1 5
1 5
3 3 .0
O p t io n a l O u tle t D a m p e r s
S u p p ly F a n
n
" x
" x
" x
1 6
S iz e
6 "
9 "
1 5 "
"
1 0
1 3
1 9
2 4
A
.3
.9
.7
.7
8
5
4
2 7
2 6
2 3
2 0
5
B
.9
.1
.2
.7
5
4
9
5
1 7
1 7
1 7
2 2
C
.0
.0
.0
.8
0
0
0
D
5 .1 3
5 .1 3
5 .1 3
1 0 .0 0
0
3 3 .0
0 .6 3
S u p p ly F a n
A ir flo w
C
A
B
B
O p t io n a l
O u t le t
D a m p e rs
1 1 .0
N o te : O p t io n a l In le t D a m p e r a v a ila b le w ith fo r w a r d c u r v e d s u p p ly fa n o n ly .
C
D
N o te : O p t io n a l In le t D a m p e r a v a ila b le w ith fo r w a r d c u r v e d s u p p ly fa n o n ly .
Blank Access Sections — Positions E & F
Final Filter Section — Position F
Figure 17: Blank Access Section
Figure 19: Cartridge Filter
o
B la n k S e c tio n L
o P o s itio n
o P o s itio n
3 3 " S e c
o c a tio n
E - B lo
F - F in
t io n
s :
w - th r o u g h B la n k A c c e s s S e c tio n ( 1 )
a l F ilte r S e c tio n ( 2 )
o
9 5 %
E ffic ie n c y
A ir flo w
A ir flo w
C a r tr id g e F ilte r
3 3 .0
3 3 .0
N o te s :
( 1 ) B la n k s e c tio n in p o s itio n E r e q u ir e s a d is c h a r g e p le n u m in p o s itio n G .
( 2 ) B la n k s e c tio n in p o s it io n F r e q u ir e s a b la n k s e c tio n in p o s it io n E a n d
a d is c h a r g e p le n u m in p o s itio n G .
©2007 McQuay International
F ilte r Q u a tity & S iz e
2 - 2 4 x 2 4 x 1 2
3 - 1 2 x 2 4 x 2
7
Position G — Discharge Plenum
Vestibule Detail Drawing
Figure 20: Discharge Plenum
Figure 21: Field Installed Coil Piping Vestibule
o
o
B o tto m D is c h a r g e
F r o n t D is c h a r g e
1 8
(4 5 7 )
4 8 .2 5
(1 2 2 6 )
B o tto m
8 .7 5
D is c h a r g e O p e n in g
A ir flo w
7 .7 5
5 2 .0
5 0 .0
4 9 .5
(1 2 5 7 )
2 0 .0
6 .5
8 .7 5
O p t io n a l F r o n t
D is c h a r g e O p e n in g
0 .5
(1 3 )
2 2 .0
3 3 .0
7 .7 5
N o t e : V e s tib u le r e q u ir e d fo r 4 8 " lo o n g c o il w ith p ip in g e n te r in g w ith in th e
c u r b a n d r e c o m m e n d e d fo r p ip in g e n te r in g th e s id e o f th e u n it.
4 .5
Blank Access and Drain Pan Only Section Detail Drawings
Figure 22: Cross Section Detail
Figure 23: Access Door Detail
A
A
C
A ir flo w
B
B
A
6 3 .5
B
4 5 .0
C
U n it F lo o r
B a s e R a il
6 2 .0
A = D o o r - to - d o o r ( w ith lin e r s )
B = C e ilin g - to - flo o r ( w ith lin e r s )
C = U p r ig h t- to - u p r ig h t, lo c a te d b e tw e e n s e c tio n s
C a b in e t H e ig h t
5 0 .8 8
A
D o o r O p e n in g
4 2 .0
B
4 5 .0
N o t e : H e a t/C o il s e c tio n a c c e s s o p p o s ite to d r a in c o n n e c tio n .
©2007 McQuay International
8
Roof Curbs
Figure 24: Roof Curb Knockouts
2 0 .0
2 .3
B
S e e N o te (1 )
C
D
1 .6 3
5 0 .0
5 3 .3 1
A ir flo w
B
A
B
A
1 .6 3
A
D
2 ,0 T y p .
4 ,0 T y p .
U n it L e n g th M in u s 8 - 1 1 /1 6 ( 2 2 1 )
1 6 .0
Figure 25: Curb Cross Section A-A
Curb Cross Section B-B
U n it
L e n g th
6 6 .2 5
U n it E n d P a n e l
6 .5
4 .3 8
U n it B a s e
2 ,0
U n it D o o r
U n it D u c t C o lla r
C u r b G a s k e tin g
U n it D u c t C o lla r
1 .2 5
C o u n te r fla s h in g
( n o t fu r n is h e d )
0 .3 8
2 x 4 N a ile r S tr ip
R ig id In s u lla tio n
( n o t fu r n is h e d )
1 6 .0
1 4 .8 8
R o o fin g M a te r ia l
C a n t S tr ip
( n o t fu r n is h e d )
1 2 G a u g e
G a lv a n iz e d
C u rb
4 .0
©2007 McQuay International
9
Dimensional Data — RDS 800C
Section Options and Locations — RDS 800C
Figures show section options, curb lengths, and relative positions. Curb lengths (in inches) are shown below each icon.
Figure 26: RDS 800C
Position A
Position B
OA Hood
Angular
0”
22”
Plenum
Cartridge
24 sq. ft.
40”
22”
Position C
Position D
Blank Access Drain Pan Only
40”
Position E
Position F
Position G
Steam/Hot
Water
20.3 sq.ft.
(2) 15” FC
with Unit
Cooling Coil
26.0 sq.ft.
Steam/Hot
Water
20.3 sq.ft.
40”
40”
Unit Htg/Clg
Blank Access 21.1 sq.ft. HT Blank Access
26.0 sq.ft. CW
27.3 sq.ft. DX
40”
Blank Access
Contractor
Htg/Clg
40”
22”
40”
Position J
(2) 15” FC
Electric
40”
40”
Position K
Position L
Discharge
Plenum
Blank
Compartment
(out of airstream)
40”
40”
40”
28”
40”
40”
Unit Cooling
w/Gas or
Blank Access 26.0 sq.ft. CW Electric Heat
27.3 sq.ft. DX
24.0 sq.ft.
52”
52”
40”
40”
30% OA
Position I
w/Clg Only
Blank Access Drain Pan Only Steam or Hot
Water Heat
24.0 sq.ft.
40”
52”
Position H
20” AF with
Unit Cooling
Gas
Coil
26.0 sq.ft. CW 200-1000 mbh
27.3 sq.ft. DX
Unit Hg/Clg
21.1 sq.ft.HT Blank Access
26.0 sq.ft. CW
27.3 sq.ft. DX
28”
40”
40”
52”
Economizer
Blank Access
20” AF
Blank Access
Contractor
Htg/Clg
Blank Access
40”
28”
52”
40”
40”
52”
Econ. with
30” FC
RA Fan
62”
Econ. with
(2) 15x15 FC
RA Fan
DX = Direct Expansion Cooling
CW = Chilled Water Cooling
HT = Hot Water or Steam Heating
62”
Section Diagram — RDS 800C
P o s itio n G
H e a t/B la n k
P o s itio n A
O u td o o r/R e tu rn
A ir
P o s itio n B
F ilte r
P o s itio n H
B la n k
D ra w -T h ro u g h
S e c tio n s
P o s itio n I
H e a t/C o o l
P o s itio n F
D ra w -th ro u g h
C lg /S u p p ly A ir F a n
P o s itio n J
F in a l F ilte r
P o s itio n K
D is c h a r g e P le n u m
P o s itio n L
B la n k C o m p a r tm e n t
B lo w - T h r o u g h
S e c tio n s
M a n d a to r y S e c tio n
S e le c tio n R e q u ir e d
P o s itio n C
B la n k
©2007 McQuay International
P o s itio n D
H e a t/C o o l
P o s itio n E
H e a t/B la n k
O p tio n a l S e c tio n
10
Application Considerations — RDS 800C
Unit Coils
Electric Heat
Unit cooling coils are available in either direct expansion
or chilled water type and can be located in the Heat/Cool
sections, position D and I, and in the Draw-through Cooling/Supply Air Fan section, position F.
l
Unit chilled water coils are available with or without a factory installed control valve when provided without a combination heating coil.
l
l
Unit heating coils are available in either steam or hot
water type and can be located in the Heat/Cool sections,
positions D and I, or the Heat sections, positions E and G.
l
Unit heating coils are available with or without a factory
installed control valve in the Heat sections, positions E
and G.
l
Gas Heat
l
Contractor coils are available in direct expansion, chilled
water, steam and hot water type and are located in the
Heat/Cool sections, positions D and I.
Contractor coils are available with or without factory
installed face and bypass dampers less actuator.
l
A gas heating furnace is located in the Blow-through
Heat section, position G only.
Final Filters
l
Final filters are not available with a drain pan only or any
option with a cooling coil located in the Blow-through
Heat/Cool section, position 1.
Blank Access Compartment
l
Contractor Coils
l
Electric heating coils are located in the Blow-through
Heat section, position G only.
The blank access compartment is available on units with
a discharge plenum in position K with bottom or side discharge only.
General
l
When any section is located in position H (Blank Access
section), I (Blow-through Heat/Cool section), or J (Final
Filter section), a heating or blank section must be placed
in position G to provide proper airflow diffusion for the
sections that follow the supply air fan.
Position A - Outdoor/Return Air Section — RDS 800C
Figure 27: Outside Air Hood
1 0 0 %
o
o
Figure 28: Return Air Plenum
O u td o o r a ir h o o d
W ith d a m p e r s
W ith o u t d a m p e r s
R e tu r n A ir P le n u m
o B o tto m re tu rn
o B a c k re tu rn
2 4 .0
6 .0
1 0 .0
9 0 .0
8 2 .0
8 6 .5
B a c k
R e tu rn
9 4 .0
9 4 .0
6 .0
3 .8
B o tto m R e tu rn
O p e n in g
2 3 .6
A ir flo w
5 5 .5
B a c k R e t u r n O p e n in g
4 0 .0
A ir flo w
5 5 .5
2 0 .0
3 .6
N o t e : T h is o p tio n d o e s n o t a ffe c t u n it c u r b le n g th
©2007 McQuay International
11
Position A - Outdoor/Return Air Section (continued) — RDS 800C
Figure 29: Return AIr Plenum - 30% Outside AIr Hood
Figure 31: Economizer with Return Air Fan
R e tu r n A ir P le n u m
o B o tto m re tu rn
o B a c k re tu rn
E c o n o m iz e r w ith r e tu r n a ir fa n
o 2 - 1 5 " x 1 5 " fo r w a r d c u r v e d w ith b o tto m r e tu r n
o 2 - 1 5 " x 1 5 " fo r w a r d c u r v e d w ith b a c k r e tu r n
O p tio n :
o W ith lig h t, r e c e p ta c le a n d s w itc h
2 4 .0
2 4 .0
6 .0
1 0 .0
1 0 .0
}
8 2 .0
8 6 .5
B a c k
R e tu rn
6 .0
T y p .
3 .8
T y p .
6 .0
9 .7
3 .8
B o tto m R e tu rn
O p e n in g
}
8 2 .0
B o tto m
R e tu rn
8 6 .5
B a c k
R e tu rn
9 4 .0
O u t s id e A ir
}
R e tu r n A ir
O u t s id e A ir
B o tto m R e tu rn
O p e n in g
(2 ) 1 5 " R e tu rn F a n s
6 2 .0
B a c k R e t u r n O p e n in g
4 0 .0
2 9 .6
2 5 .9
3 0 %
H o o d
A ir flo w
A ir flo w
5 5 .5
2 0 .0
3 .6
2 0 .0
3 .6
B a c k R e t u r n O p e n in g
Figure 30: Economizer
E c o
o 1
o 1
o 1
o 1
n o
- 3
- 3
- 3
- 3
m iz
0 " A
0 " A
0 " A
0 " A
e r w
ir fo
ir fo
ir fo
ir fo
il
il
il
il
ith
w
w
w
w
re
ith
ith
ith
ith
tu
b o
b a
v a
v a
rn
tto
c k
r ia
r ia
a ir fa n
re tu rn
re tu rn
b le in le t v a n e s w ith b o tto m r e t u r n
b le in le t v a n e s w ith b a c k r e tu r n
m
O p tio n :
o W ith lig h t, r e c e p ta c le a n d s w itc h
2 4 .0
1 0 .0
}
3 .8
T y p .
O u t s id e A ir L o u v e r s
( b o th s id e s )
Figure 32: Economizer with Return Air Fan
E c o n o m iz e r
o B o tto m re tu rn
o B a c k re tu rn
8 6 .5
B a c k
R e tu rn
5 5 .5
}
8 2 .0
B o tto m
R e tu rn
O u t s id e A ir
}
R e tu r n A ir
O u t s id e A ir
3 0 .0
1 0 .0
1 6 .5
}
9 0 .0
H o o d
8 6 .5
B a c k
R e tu rn
}
7 6 .0
B o tto m
R e tu rn
9 .7
6 .0
T y p .
B o tto m R e tu rn
O p e n in g
2 .0
T y p .
3 .8
T y p .
9 .0
T y p .
4 0 .0
O u t s id e A ir
5 2 .0
B a c k R e t u r n O p e n in g
H o o d
2 9 .6
5 5 .5
2 5 .9
}
R e tu r n A ir
B o tto m R e tu rn
O p e n in g
(2 ) 1 5 " R e tu rn F a n s
B a c k R e t u r n O p e n in g
O u t s id e A ir
A ir flo w
A ir flo w
2 9 .3
5 5 .5
2 0 .0
2 6 .2
3 .6
©2007 McQuay International
O u t s id e A ir L o u v e r s
( b o th s id e s )
1 6 .0
3 .6
O u t s id e A ir L o u v e r s
( b o th s id e s )
12
Position B - Draw-through Filter Section — Mandatory Selection — RDS 800C
Figure 33: Angular Filters
Figure 34: Cartridge Filter with Prefilter
Cartridge filter wi th prefilter
65% Efficiency - 24 sq.ft. (2.23m2)
95% Efficiency - 24 sq.ft. (2.23m2)
Angular filters
Throwaway
30% Efficiency
94.0
94.0
22.0
28.0
Airflow
Airflow
55.5
55.5
Filter quantity & size
10 - 16 x 25 x 2
10 - 16 x 20 x 2
Filter quantity & size
4 - 24 x 24 x 12
4 - 12 x 24 x 12
Blank Access Sections — positions B, C, E, H and J — RDS 800C
Figure 35: Blank Access Section
Figure 36: Blank Access Section
Blank access section
Blank - 28" section
Blank access section
Blank - 22" section
Selection location:
Position B - Draw-through filter section
Selection location: (1)
Position B - Draw-through filter section
Position J - Final filter section (2)
94.0
94.0
22.0
28.0
Airflow
55.5
Airflow
55.5
Notes:
(1) This section may be located in one or more of the locations listed above.
(2) Blank access section in position J requires a blank or heat section in position G.
©2007 McQuay International
13
Blank Access Sections — positions B, C, E, H and J (continued) — RDS 800C
Figure 37: Short Coil
Figure 38: Short Coil with Face & Bypass
Blank access section
o Blank - 40" section
Blank access section
Blank - 52" section
Selection locations: (1)
Position B - Draw-through blank access section
Position B - Draw-through heat section
Position B - Blow-through heat section
(includes deffuser)
Position B - Blow-through blank access section (2)
Selection locations: (1)
Position C - Draw-through blank access section
Position H - Blow-through blank access section (2)
Position J - Final filter section
94.0
94.0
52.0
40.0
Airflow
Airflow
55.5
55.5
Notes:
(1) This section may be located in one or more of the locations listed above.
(2) Blank access section in position H requires a blank or heat section in position G.
Notes:
(1) This section may be located in one or more of the locations listed above.
(2) Blank access section in position H or J requires a blank or heat section in
position G.
Heat/Cool Section — Drain Pan Only — Position D or I — RDS 800C
Figure 39: Drain Pan Only
Drain pan only
Position B - Draw-through
Position B - Blow-through (1)
3.1
19.3
94.0
89.2
2.4
Typ.
40.0
Airflow
55.5
20.0
Notes:
(1) Drain pan only section in position I requires a blank or heat section in position G.
©2007 McQuay International
14
Section D — Draw-through Heat/Cool Section — RDS 800C
Figure 40: Unit Heating and Cooling
Figure 41: Contractor Heating and Cooling (1)
H e a tin g c o il (2 1 .1 s q .ft.)
o S te a m
o H o t w a te r
H e a tin g c o il
o S te a m
o H o t w a te r
C o o lin g c o il
o C h ille d w a te r ( 2 6 .0 s q .ft.)
o D X e v a p o ra to r (2 7 .3 s q .ft.)
C o o lin g c o il
o C h ille d w a te r
o D X e v a p o ra to r
O p tio n s
o W ith fa c e a n d b y p a s s
d a m p e r le s s a c tu a to r
5 .0
2 .5
1 .5 0 M P T D r a in
5 .0
7 .0 T y p .
2 .5
1 .5 0 M P T D r a in
C o o lin g C o il
7 .0 T y p .
3 8 .0
C o o lin g C o il
9 4 .0
H e a tin g C o il
3 8 .0
3 8 .0
9 4 .0
H e a tin g C o il
3 8 .0
A ll p ip in g e n tr a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
A ll p ip in g e n tr a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
4 0 .0
4 0 .0
A ir flo w
5 5 .5
A ir flo w
5 5 .5
2 0 .0
2 0 .0
Section D — Draw-through Heat Only Section — RDS 800C
Figure 42: Steam/Hot Water Heat
Steam/hot water heat
Steam coil (20.3 sq.ft).
Steam coil with 2-way modulating valve & piping (20.3 sq.ft.)
Hot water coil (20.3 sq.ft.)
Hot water coil with 3-way modulating valve & piping (20.3 sq.ft.)
All piping entrance holes
should fall within this area
94.0
6.5
6.0
29.0
1.0
40.0
Airflow
55.5
Optional Factory Piping
©2007 McQuay International
15
Position F— Draw-through Cooling/Supply Air Fan Section
— Mandatory Section — RDS 800C
Figure 43: Supply Air Fan with Cooling Coil
Figure 45: Supply Air Fan with Cooling Coil
S u p p ly a ir fa n w ith c o o lin g c o il
o 2 -1 5 " x 6 " F o rw a rd c u rv e d
o 2 -1 5 " x 1 5 " F o rw a rd c u rv e d
S u p p ly a ir fa n
o 2 -1 5 " x 6 " F o rw a rd c u rv e d
o 2 -1 5 " x 1 5 " F o rw a rd c u rv e d
C o o
o C
o C
o D
O p tio n s
o W ith lig h t, r e c e p ta c le a n d s w itc h
lin g c
h ille d
h ille d
X e v a
o il
w a te r (2 6 .0 s q .ft.)
w a te r w ith 3 - w a y m o d u la tin g v a lv e a n d p ip in g ( 2 6 .0 s q .ft. )
p o ra to r (2 7 .3 s q .ft.)
O p tio n s
o W ith lig h t, r e c e p ta c le a n d s w itc h
1 7 .5
5 .0
1 .5 0 M P T D r a in
B
5 .0
A ll p ip in g e n tr a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
B
8 .5
9 4 .0
A
C o o lin g C o il
9 4 .0
A
C
C
4 0 .0
4 0 .0
9 .2
9 .2
(2 ) 1 5 " X 1 5 "
S u p p ly fa n
A ir flo w
1 7 .0
5 5 .5
( 2 ) 1 5 " S u p p ly fa n
A ir flo w
1 7 .0
2 9 .3
5 5 .5
2 9 .3
1 1 .0
F a n S iz e
(2 ) 1 5 " x 6 "
(2 ) 1 5 " x 6 "
A
4 9 .0
5 8 .4
B
2 1 .5
1 6 .8
C
2 3 .5
1 8 .8
F a n S iz e
(2 ) 1 5 " x 6 "
(2 ) 1 5 " x 6 "
Figure 44: Supply AIr Fan with Cooling Coil
B
2 1 .5
1 6 .8
C
2 3 .5
1 8 .8
Figure 46: Supply Air Fan
S u p p ly a ir fa n w ith c o o lin g c o il
o 2 -1 5 " x 6 " F o rw a rd c u rv e d
o 2 -1 5 " x 1 5 " F o rw a rd c u rv e d
S u p p ly a ir fa n
o 1 - 2 0 " A ir fo il
o 1 - 2 0 " A ir fo il w ith v a r ia b le in le t v a n e s
C o o
o C
o C
o D
O p tio n s
o W ith lig h t, r e c e p ta c le a n d s w itc h
lin g c
h ille d
h ille d
X e v a
A
4 9 .0
5 8 .4
o il
w a te r (2 6 .0 s q .ft.)
w a te r w ith 3 - w a y m o d u la tin g v a lv e a n d p ip in g ( 2 6 .0 s q .ft. )
p o ra to r (2 7 .3 s q .ft.)
O p tio n s
o W ith lig h t, r e c e p ta c le a n d s w itc h
1 5 .5
8 .5
1 .5 0 M P T D r a in
1 5 .6
8 .5
A ll p ip in g e n tr a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
2 8 .3
2 8 .3
2 9 .8
9 4 .0
2 9 .8
C o o lin g C o il
3 5 .9
3 5 .9
5 2 .0
5 2 .0
6 .7
6 .7
2 0 " S u p p ly fa n
9 4 .0
A ir flo w
2 4 .6
5 5 .5
2 4 .2
2 0 " S u p p ly fa n
A ir flo w
2 4 .6
5 5 .5
2 4 .2
1 1 .0
©2007 McQuay International
16
Position G — Blow-through Heat Only Section — RDS 800C
Figure 47: Steam/Hot Water Heat
S te a m
o S te
o S te
o H o
o H o
/h o t w a t
a m c o il ( 2
a m c o il w
t w a te r c o
t w a te r c o
e r h e a
0 .3 s q
ith 2 - w
il ( 2 0 .3
il w ith
t
.ft)
a y
s q
3 -w
.
Figure 48: Gas Heat
G a s h e a t
o G a s h e a t w it h c o n t r o ls ( 2 0 0 - 1 0 0 0 m b h o u tp u t)
m o d u la tin g v a lv e & p ip in g ( 2 0 .3 s q .ft.)
.ft.)
a y m o d u la tin g v a lv e & p ip in g ( 2 0 .3 s q .f t.)
N o te :
T y p ic a l h o t w a te r p ip in g s h o w n , s e e IM 1 7 8 fo r ty p ic a l s te a m
p ip in g .
A ll p ip in g e n tr a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
A ll p ip in g e n tr a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
1 2 .0
9 4 .0
6 .5
6 .0
6 .0
9 4 .0
2 9 .0
1 .0
5 .0
2 .7
4 0 .0
4 0 .0
A ll p ip in g e n tr a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
A ir flo w
5 5 .5
A ir flo w
5 5 .5
O p t io n a l F a c to r y P ip in g
(S e e n o te )
Figure 49: Electric Heat
E le c tr ic h e a t
o E le c tr ic h e a t
9 4 .0
4 0 .0
5 5 .5
A ir flo w
2 2 .0
©2007 McQuay International
17
Position I — Blow-through Heat/Cool Section — RDS 800C
Figure 50: Unit Cooling Coil Only
C o o
o C
o C
o D
lin g c
h ille d
h ille d
X e v a
Figure 51: Unit Heating Coil Only
H e a tin g c o il (2 1 .1 s q .ft.)
o S te a m
o H o t w a te r
o il
w a te r (2 6 .0 s q .ft.)
w a te r w ith 3 - w a y m o d u la tin g v a lv e a n d p ip in g ( 2 6 .0 s q .ft. )
p o ra to r (2 7 .3 s q .ft.)
C o o lin g c o il
o C h ille d w a te r ( 2 6 .0 s q .ft.)
o D X e v a p o ra to r (2 7 .3 s q .ft.)
5 .0
1 3 .8
2 .5
1 .5 0 M P T D r a in
7 .0 T y p .
C o o lin g C o il
3 8 .0
9 4 .0
C o o lin g C o il
2 .5
1 .5 0 M P T D r a in
7 .0 T y p .
3 8 .0
9 4 .0
H e a tin g C o il
3 8 .0
4 0 .0
A ll p ip in g e n tr a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
A ir flo w
4 0 .0
5 5 .5
A ir flo w
5 5 .5
2 0 .0
N o te :
B lo w - th r o u g h h e a t/c o o l s e c tio n in p o s itio n I r e q u ir e s a
b la n k o r h e a tin g s e c tio n in p o s itio n G .
2 0 .0
Figure 52: Contractor Heating and Cooling
H e a tin g c o il
o S te a m
o H o t w a te r
C o o lin g c o il
o C h ille d w a te r
o D X e v a p o ra to r
O p tio n s
o W ith fa c e a n d b y p a s s d a m p e r le s s a c tu a t o r
5 .0
2 .5
1 .5 0 M P T D r a in
C o o lin g C o il
7 .0 T y p .
3 8 .0
9 4 .0
H e a tin g C o il
3 8 .0
A ll p ip in g e n tr a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
4 0 .0
A ir flo w
5 5 .5
2 0 .0
©2007 McQuay International
18
Position J — Final Filter Section — RDS 800C
Figure 53: Final Filter Section (28”) for Units w Cooling
Only and/or Steam or Hot Water Heat
F i n a l f i l t e r s e c t i o n ( 2 8 " ) f o r u n i t s
a n d / o r s t e a m
o r h o t w a t e r h e a t
o
9 5 %
E f f ic ie n c y
- 2 4 . 0
w
i t h
c o o l i n g
Figure 55: Final Filter Section (52”) for Units with Gas
or Electric Heat
F i n a l f i l t e r s e c t i o n ( 5 2 " ) f o r u n i t s
g a s o r e l e c t r i c h e a t
o n l y
o
s q . f t .
9 5 %
E f f ic ie n c y
- 2 4 . 0
w
i t h
s q . f t .
9 4 .0
9 4 .0
5 2 .0
2 8 .0
A ir flo w
A ir flo w
5 5 .5
5 5 .5
F ilte r q u a n tity & s iz e
4 - 2 4 x 2 4 x 1 2
4 - 1 2 x 2 4 x 1 2
F ilte r q u a n tity & s iz e
4 - 2 4 x 2 4 x 1 2
4 - 1 2 x 2 4 x 1 2
Position K — Discharge Plenum
— RDS 800C
Position L — Blank Compartment Section
— RDS 800C
Figure 54: Discharge Plenum
Figure 56: Blank Compartment
D is c h a r g e
o B o tto m d
o S id e d is c
o F r o n t d is
B la n k c o m p a r tm e n t
o O u t o f a ir s tr e a m - 4 0 " s e c tio n
P le n u m
is c h a r g e
h a rg e
c h a rg e
2 0 .0
6 .0
B o tto m d is c h a r g e
o p e n in g
1 8 .0
9 4 .0
7 6 .0
B o tto m
D is c h a r g e
8 6 .5
F ro n t
D is c h a r g e
1 2 .0
3 .8
P o w e r a n d C o n tro l E n te ra n c e
( s e e F ig u r e x x x )
4 0 .0
F r o n t D is c h a r g e
4 0 .0
5 5 .5
2 0 .0
©2007 McQuay International
A ir flo w
A ir flo w
4 3 .5
O p t io n a l S id e D is c h a r g e
o n o p p o s ite p o w e r s id e
5 5 .5
3 .6
N o te :
B la n k c o m p a r tm e n t r e q u ir e s a d is c h a r g e p le n u m
o r s id e d is c h a r g e in p o s itio n G .
w ith b o tto m
19
Roof Curbs — RDS 800C
Figure 57: Roof Curb without Blank Compartment (Out of Airstream)
2 0 .0
A
C
6 .8
D
1 .5
N o te : C u r b m u s t b e in s ta lle d le v e l.
R A
O P E N IN G
B
S A
O P E N IN G
R e tu
N
(2 ) 1
3 0
7 6 .0
A
rn
o n
5 "
" A
e
F a n
F
A
2 4
F C
2 4
3 0
C
6 .8
6 .8
6 .8
B
8 2
8 2
7 6
D
1 .5
1 .5
4 .5
A
B
D
B
2 .0 T Y P .
7 .5
S e e F ig u r e X X X
4 .0 T Y P .
(U N IT L E N G T H M IN U S 6 .4 IN C H E S )
Figure 58: Roof Curb without Blank Compartment (Out of Airstream)
C
A
4 6 .8
2 0 .0
6 .8
D
1 .5
N o te : C u r b m u s t b e in s ta lle d le v e l.
S A
O P E N IN G
R A
O P E N IN G
B
R e tu
N
(2 ) 1
3 0
7 6 .0
A
rn
o n
5 "
" A
e
F a n
F
F C
A
2 4
B
8 2
3 0
7 6
2 4
C
6 .8
6 .8
6 .8
8 2
D
1 .5
1 .5
4 .5
A
B
D
7 .5
B
2 .0 T Y P .
S e e F ig u r e X X X
4 .0 T Y P .
U N IT L E N G T H
M IN U S 6 .4 IN C H E S
Figure 59: Curb Cross Section A-A Curb Cross Section B-B
4 .5
3 .2
2
2
2
1
9
1 6 .0
9 .8
5
1 0
4 .6
7
K e y
1 U
2 C
3 2
4 G
5 D
6 C
7 R
8 C
9 F
:
n it B a s e
u r b G a s k e tin g
x 4 N a ile r S tr ip
a lv a n iz e d C u r b
u c t S u p p o rt
a n t S tr ip ( N o t F u r n is h
o o fin g M a te r ia l ( N o t F
o u n te r fla s h in g ( N o t F
la s h in g ( N o t F u r n is h e
2
9
1 0
3
e d )
u r n is h e d )
u r n is h e d )
d )
6
5
1 4 .4
1
7
8
4
4
©2007 McQuay International
20
Blank Access and Drain Pan Only Section Detail Drawings — RDS 800C
Figure 60: Cross Section Detail & Access Door Detail
A c c e s s d o o r d e ta il
Cross section detail
3 .6
91.0
86.8
Upright located
between sections
(both sides)
1 .8
1 .8
3 4 .0
3 .0
3 .5
Ceiling (with optional liner)
D o o r O p e n in g
50.2
86.8
Door
(with liner)
4 3 .5
4 3 .5
Door
(with liner)
91.0
A ir flo w
* 5 5 .5
3 4 .0
1 .8
90.0
Base
8 .5
U n it F lo o r
Base
Floor
B a s e R a il
2 .2
1.8 Standing Seam
(located between each section)
Vestibule detail drawing — RDS 800C
Figure 61: Field Installed Coil Piping Vestibule
5 .2
Electrical knockouts — RDS 800C
Figure 62: Discharge Plenum Wiring Entrance Detail
F ie ld in s ta lle d c o il p ip in g v e s tib u le
D is c h a r g e p le n u m
w ir in g e n te r a n c e d e ta il
.9 D IA . K .O .
(Q T Y = 4 )
3 .0 D IA . K .O .
(Q T Y = 3 )
4 0 .0 0
1 6 .0 0
fl
A ir
o w
7 .6
8 .8
6 .6
1 2 .0
1 3 .0
1 5 .4
4 6 .6
1 7 .8
1 8 .8
2 2 .4
2 4 .4
7 .2
N
N o te :
0 .9 d ia m e te r a n d 3 .0 d ia m e te r k n o c k o u ts a r e
e le c tr ic a l e n te r a n c e lo c a tio n s o n th e u n it o n ly .
t
©2007 McQuay International
21
Dimensional Data — RDS 802C
Section options and locations
Figure 63: Section Options and Locations—RDS 802C
Position A Position B Position C Position D Position E Position F Position G Position H Position I Position J Position K Position L
OA/RA
Filter
Blank
OA hood
Angular
Blank access
Drain pan only
0"
22"
40"
40"
Plenum
Cartridge
24 sq ft
Blank access
52"
28"
52"
30% OA
Blank Access
52"
22"
Draw-thru Heat/Blan
Heat/Cool
k
Unit cooling
26.0 sq ft CW
27.3 sq ft DX
40"
Supply
Air Fan
Heat/Blan
k
Steam/hot
water
20.3 sq ft
24" diameter.
Steam/hot
water
20.3 sq ft
40"
62"
40"
Blank
With clg only
steam or hot
water heat
24.0 sq ft
Blank
compartment
(out of
airstream)
Drain pan only
40"
40"
28"
Electric
Blank access
40"
40"
52"
Gas
200-1000 MBh
Unit Cooling
26.0 sq ft CW
27.3 sq ft DX
w/Gas or
Electric Heat
24.0 sq ft
40"
52"
Unit htg/clg
21.1 sq ft HT
26.0 sq ft CW
27.3 sq ft DX
Blank access
Discharge
plenum
40"
40"
28"
40"
40"
Blank
Comp.
Blank access
Blank access
Unit heating &
cooling
21.1 sq ft HT
26.0 sq ft CW
27.3 sq ft DX
Blow-thru Final Filter Discharge
Heat/Cool
Plenum
40"
Economizer
Blank access
Contractor
htg/clg
Blank access
Contractor
htg/clg
Blank access
52"
28"
40"
40"
40"
52"
Econ. with
30" AF
RA fan
52"
Econ. with
40" AF
RA fan
DX = Direct expansion cooling
CW = Chilled water cooling
HT = Hot water or steam heating
80"
Section Diagram — RDS 802C
P o s itio n G
H e a t/B la n k
P o s itio n A
O u td o o r/R e tu rn
A ir
P o s itio n B
F ilte r
P o s itio n H
B la n k
D ra w -T h ro u g h
S e c tio n s
P o s itio n I
H e a t/C o o l
P o s itio n F
D ra w -th ro u g h
C lg /S u p p ly A ir F a n
P o s itio n J
F in a l F ilte r
P o s itio n K
D is c h a r g e P le n u m
P o s itio n L
B la n k C o m p a r tm e n t
B lo w - T h r o u g h
S e c tio n s
M a n d a to r y S e c tio n
S e le c tio n R e q u ir e d
P o s itio n C
B la n k
©2007 McQuay International
P o s itio n D
H e a t/C o o l
P o s itio n E
H e a t/B la n k
O p tio n a l S e c tio n
22
Application Considerations — RDS 802C
Unit Coils
l
Electric Heat
Unit cooling coils are available in either direct expansion
or chilled water type and can be located in the Heat/Cool
sections, position D and I.
l
Unit chilled water coils are available with or without a factory installed control valve when provided without a combination heating coil.
l
Unit heating coils are available in either steam or hot
water type and can be located in the Heat/Cool sections,
positions D and I, or the Heat sections, positions E and G.
l
Unit heating coils are available with or without a factory
installed control valve in the Heat sections, positions E
and G.
Contractor Coils
l
Contractor coils are available in direct expansion, chilled
water, steam and hot water type and are located in the
Heat/Cool sections, positions D and I.
l
Contractor coils are available with or without factory
installed face and bypass dampers less actuator.
l
Electric heating coils are located in the Blow-through
Heat section, position G only.
Gas Heat
l
A gas heating furnace is located in the Blow-through
Heat section, position G only.
Final Filters
l
Final filters are not available with a drain pan only or any
option with a cooling coil located in the Blow-through
Heat/Cool section, position I.
Blank Access Compartment
l
The blank access compartment is available on units with
a discharge plenum in position K with bottom or side discharge only.
General
l
When any section is located in position H (Blank Access
section), I (Blow-through Heat/Cool section), or J (Final
Filter section), a heating or blank section must be placed
in position G to provide proper airflow diffusion for the
sections that follow the supply air fan.
Position A — Outdoor/Return Air Section — RDS 802C
Figure 64: Outside Air Hood & Return Air Plenum
1 0 0 %
o
o
O u td o o r a ir h o o d
W ith d a m p e r s
W ith o u t d a m p e r s
R e tu r n A ir P le n u m
o B o tto m re tu rn
o B a c k re tu rn
2 4 .0
6 .0
1 0 .0
9 0 .0
8 2 .0
8 6 .5
B a c k
R e tu rn
9 4 .0
9 4 .0
6 .0
3 .8
B o tto m R e tu rn
O p e n in g
2 3 .6
A ir flo w
5 5 .5
B a c k R e t u r n O p e n in g
5 2 .0
A ir flo w
5 5 .5
2 0 .0
3 .6
N o t e : T h is o p tio n d o e s n o t a ffe c t u n it c u r b le n g th
©2007 McQuay International
23
Position A — Outdoor/Return Air Section — RDS 802C (continued)
Figure 65: Return Air Plenum with 30% Outside Air Hood & Economizer
R e tu r n A ir P le n u m
o B o tto m re tu rn
o B a c k re tu rn
w ith 3 0 %
E c o n o m iz e r
o B o tto m re tu rn
o B a c k re tu rn
o u ts id e a ie h o o d
2 4 .0
2 4 .0
6 .0
1 0 .0
1 0 .0
}
8 2 .0
8 6 .5
B a c k
R e tu rn
8 6 .5
B a c k
R e tu rn
B o tto m R e tu rn
O p e n in g
2 5 .9
3 0 %
}
R e tu r n A ir
O u t s id e A ir
9 .7
6 .0
T y p .
B o tto m R e tu rn
O p e n in g
5 2 .0
B a c k R e t u r n O p e n in g
5 2 .0
2 9 .6
}
8 2 .0
B o tto m
R e tu rn
3 .8
T y p .
6 .0
9 .7
3 .8
9 4 .0
O u t s id e A ir
H o o d
H o o d
2 9 .6
A ir flo w
5 5 .5
2 0 .0
5 5 .5
2 0 .0
2 5 .9
3 .6
B a c k R e t u r n O p e n in g
3 .6
Figure 66: Economizer with Return Air Fan
A ir flo w
O u t s id e A ir L o u v e r s
( b o th s id e s )
Figure 67: Economizer with Return Air Fan
E c o n o m iz e r w ith r e tu r n a ir fa n
o 1 - 3 0 " A ir fo il w ith b a c k r e tu r n
o 1 - 3 0 " A ir f o il w ith v a r ia b le in le t v a n e s w ith b a c k r e tu r n
E c o n o m iz e r w ith r e tu r n a ir fa n
o 1 - 4 0 " A ir fo il w ith b o t to m r e tu r n
o 1 - 4 0 " A ir f o il w ith v a r ia b le in le t v a n e s w ith b a c k r e tu r n
O p tio n :
o W ith lig h t, r e c e p ta c le a n d s w itc h
O p tio n :
o W ith lig h t, r e c e p ta c le a n d s w itc h
3 0 .0
1 0 .0
1 6 .5
1 6 .8
}
9 0 .0
H o o d
2 .0
T y p .
8 6 .5
B a c k
R e tu rn
}
7 6 .0
B o tto m
R e tu rn
3 .8
T y p .
9 .0
T y p .
3 6 .0
}
O u t s id e A ir
}
R e tu r n A ir
9 0 .0
H o o d
}
7 8 .0
B o tto m
R e tu rn
O u t s id e A ir
2 .0
T y p .
B o tto m R e tu rn
O p e n in g
(2 ) 1 5 " R e tu rn F a n s
1 8 .0
8 .0
T y p .
O u t s id e A ir
}
R e tu r n A ir
O u t s id e A ir
B o tto m R e tu rn
O p e n in g
4 0 " R e tu rn F a n
8 0 .0
5 2 .0
B a c k R e t u r n O p e n in g
A ir flo w
2 9 .3
5 5 .5
2 6 .2
1 6 .0
3 .6
©2007 McQuay International
O u t s id e A ir L o u v e r s
( b o th s id e s )
A ir flo w
1 4 .9
5 5 .5
2 0 .6
O u t s id e A ir
L o u v e rs
( b o th s id e s )
24
Position B — Draw-through Filter Section — RDS 802C — mandatory selection
Figure 68: Angular Filters
Cartridge Filter with Pre-filter
Angular filters
Throwaway
30% Efficiency
Cartridge filter wi th prefilter
65% Efficiency - 24 sq.ft. (2.23m2)
95% Efficiency - 24 sq.ft. (2.23m2)
94.0
94.0
22.0
28.0
Airflow
Airflow
55.5
55.5
Filter quantity & size
4 - 24 x 24 x 12
4 - 12 x 24 x 12
Filter quantity & size
10 - 16 x 25 x 2
10 - 16 x 20 x 2
Blank Access Sections — Positions B, C, E G, H and J — RDS 802C
Figure 69: Blank Access Sections
Blank access section
Blank - 22" section
Blank access section
Blank - 28" section
Selection location:
Position B - Draw-through filter section
Selection location: (1)
Position B - Draw-through filter section
Position J - Final filter section (2)
94.0
94.0
28.0
22.0
Airflow
Airflow
55.5
55.5
Notes:
(1) This section may be located in one or more of the locations listed above.
(2) Blank access section in position J requires a blank or heat section in position G.
©2007 McQuay International
25
Blank Access Sections — Positions B, C, E G, H and J — RDS 802C
Figure 70: Blank Access Sections
B la n k a c c e s s s e c tio n
o B la n k - 4 0 " s e c tio n
S e l
o P
o P
o P
o P
e c
o
o
o
o
tio n
s itio
s itio
s itio
s itio
lo c a tio
n C - D ra
n E - D ra
n G - B lo
n H - B lo
n s : (1 )
w -th ro u
w -th ro u
w -th ro u
w -th ro u
g h
g h
g h
g h
b la n k
h e a t s
h e a t s
b la n k
a c
e c
e c
a c
c e
tio
tio
c e
s s s e c tio n
n
n ( in c lu d e s d e ffu s e r )
s s s e c tio n ( 2 )
9 4 .0
4 0 .0
5 5 .5
A ir flo w
N o te s :
( 1 ) T h is s e c tio n m a y b e lo c a te d in o n e o r m o r e o f th e lo c a tio n s lis te d a b o v e .
( 2 ) B la n k a c c e s s s e c tio n in p o s itio n H r e q u ir e s a b la n k o r h e a t s e c tio n in p o s itio n G .
Figure 71: Blank Access Sections
B la n k a c c e s s s e c tio n
o B la n k - 5 2 " s e c tio n
S e l
o P
o P
o P
e c
o
o
o
tio n
s itio
s itio
s itio
lo c a tio n s : (1 )
n C - D r a w - th r o u g h b la n k a c c e s s s e c tio n
n H - B lo w - th r o u g h b la n k a c c e s s s e c tio n ( 2 )
n J - F in a l filte r s e c tio n
9 4 .0
5 2 .0
5 5 .5
A ir flo w
N o te s :
( 1 ) T h is s e c tio n m a y b e lo c a te d in o n e o r m o r e o f th e lo c a tio n s lis te d a b o v e .
( 2 ) B la n k a c c e s s s e c tio n in p o s itio n H o r J r e q u ir e s a b la n k o r h e a t s e c tio n in p o s itio n G .
©2007 McQuay International
26
Position D — Draw-through only Heat/Cool Section — RDS 802C
Figure 72: Drain Pan Only
D r a in
p a n
Unit Cooling Coil Only
o n ly
C o o
o C
o C
o D
lin g c
h ille d
h ille d
X e v a
o il
w a te r (2 6 .0 s q .ft.)
w a te r w ith 3 - w a y m o d u la tin g v a lv e a n d p ip in g ( 2 6 .0 s q .ft. )
p o ra to r (2 7 .3 s q .ft.)
1 9 .3
3 .1
1 3 .8
2 .5
1 .5 0 M P T D r a in
9 4 .0
8 9 .2
7 .0 T y p .
3 8 .0
9 4 .0
C o o lin g C o il
4 0 .0
2 .4
T y p .
4 0 .0
A ir flo w
5 5 .5
A ir flo w
5 5 .5
2 0 .0
2 0 .0
Figure 73: Unit Heating and Cooling
Contractor Heating and Cooling
H e a tin g c o il (2 1 .1 s q .ft.)
o S te a m
o H o t w a te r
H e a tin g c o il
o S te a m
o H o t w a te r
C o o lin g c o il
o C h ille d w a te r ( 2 6 .0 s q .ft.)
o D X e v a p o ra to r (2 7 .3 s q .ft.)
C o o lin g c o il
o C h ille d w a te r
o D X e v a p o ra to r
O p tio n s
o W ith fa c e a n d b y p a s s
d a m p e r le s s a c tu a to r
5 .0
2 .5
1 .5 0 M P T D r a in
5 .0
7 .0 T y p .
2 .5
1 .5 0 M P T D r a in
C o o lin g C o il
7 .0 T y p .
3 8 .0
9 4 .0
H e a tin g C o il
3 8 .0
C o o lin g C o il
3 8 .0
9 4 .0
H e a tin g C o il
3 8 .0
A ll p ip in g e n tr a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
A ll p ip in g e n tr a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
4 0 .0
4 0 .0
A ir flo w
5 5 .5
A ir flo w
5 5 .5
2 0 .0
©2007 McQuay International
2 0 .0
27
Position E — Draw-Through Only Heat/Cool Section — RDS 802C
Figure 74: Steam/Hot Water Heat
S te a m
o S te
o S te
o H o
o H o
/h o t w a t
a m c o il ( 2
a m c o il w
t w a te r c o
t w a te r c o
e r h e a
0 .3 s q
ith 2 - w
il ( 2 0 .3
il w ith
t
.ft)
a y
s q
3 -w
.
m o d u la tin g v a lv e & p ip in g ( 2 0 .3 s q .ft.)
.ft.)
a y m o d u la tin g v a lv e & p ip in g ( 2 0 .3 s q .f t.)
N o te :
T y p ic a l h o t w a te r p ip in g s h o w n , s e e IM 1 7 8 fo r ty p ic a l s te a m
p ip in g .
A ll p ip in g e n tr a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
9 4 .0
6 .5
6 .0
2 9 .0
1 .0
4 0 .0
A ir flo w
5 5 .5
O p t io n a l F a c to r y P ip in g
(S e e n o te )
Position F — Supply Air Fan Section — Mandatory Selection — RDS 802C
Figure 75: Supply Air Fan
Angular filters
Throwaway
30% Efficiency
94.0
22.0
Airflow
55.5
Filter quantity & size
10 - 16 x 25 x 2
10 - 16 x 20 x 2
©2007 McQuay International
28
Position G — Blow-Through Heat Only Section — RDS 802C
Figure 76: Steam/Hot Water Heat
S te a m
o S te
o S te
o H o
o H o
/h o t w a t
a m c o il ( 2
a m c o il w
t w a te r c o
t w a te r c o
e r h e a
0 .3 s q
ith 2 - w
il ( 2 0 .3
il w ith
t
.ft)
a y
s q
3 -w
.
Electric Heat
E le c tr ic h e a t
o E le c tr ic h e a t
m o d u la tin g v a lv e & p ip in g ( 2 0 .3 s q .ft.)
.ft.)
a y m o d u la tin g v a lv e & p ip in g ( 2 0 .3 s q .f t.)
N o te :
T y p ic a l h o t w a te r p ip in g s h o w n , s e e IM 1 7 8 fo r ty p ic a l s te a m
p ip in g .
9 4 .0
A ll p ip in g e n tr a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
9 4 .0
6 .5
2 9 .0
1 .0
6 .0
4 0 .0
4 0 .0
5 5 .5
A ir flo w
A ir flo w
5 5 .5
2 2 .0
O p t io n a l F a c to r y P ip in g
(S e e n o te )
Figure 77: Gas Heat
G a s h e a t
o G a s h e a t w it h c o n t r o ls ( 2 0 0 - 1 0 0 0 m b h o u tp u t)
A ll p ip in g e n tr a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
9 4 .0
1 2 .0
6 .0
5 .0
2 .7
4 0 .0
A ll p ip in g e n tr a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
©2007 McQuay International
5 5 .5
A ir flo w
29
Position I — Blow-Through Heat/Cool Section — RDS 802C
Figure 78: Drain Pan Only
D
r a i n
p a n
Unit Cooling Coil Only
C o o
o C
o C
o D
o n l y
3 .1
lin g c
h ille d
h ille d
X e v a
o il
w a te r (2 6 .0 s q .ft.)
w a te r w ith 3 - w a y m o d u la tin g v a lv e a n d p ip in g ( 2 6 .0 s q .ft. )
p o ra to r (2 7 .3 s q .ft.)
1 9 .3
1 3 .8
2 .5
1 .5 0 M P T D r a in
7 .0 T y p .
9 4 .0
8 9 .2
3 8 .0
9 4 .0
C o o lin g C o il
2 .4
T y p .
4 0 .0
4 0 .0
A ir flo w
5 5 .5
A ir flo w
2 0 .0
5 5 .5
N o te :
B lo w - th r o u g h h e a t/c o o l s e c tio n in p o s itio n I r e q u ir e s a
b la n k o r h e a tin g s e c tio n in p o s itio n G .
2 0 .0
N o te :
B lo w - th r o u g h h e a t/c o o l s e c tio n in p o s itio n I r e q u ir e s a
b la n k o r h e a tin g s e c tio n in p o s itio n G .
Figure 79: Unit Heating and Cooling
Contractor Heating and Cooling
H e a tin g c o il (2 1 .1 s q .ft.)
o S te a m
o H o t w a te r
H e a tin g c o il
o S te a m
o H o t w a te r
C o o lin g c o il
o C h ille d w a te r ( 2 6 .0 s q .ft.)
o D X e v a p o ra to r (2 7 .3 s q .ft.)
C o o lin g c o il
o C h ille d w a te r
o D X e v a p o ra to r
O p tio n s
o W ith fa c e a n d b y p a s s d a m p e r le s s a c tu a t o r
5 .0
2 .5
1 .5 0 M P T D r a in
C o o lin g C o il
7 .0 T y p .
2 .5
1 .5 0 M P T D r a in
3 8 .0
9 4 .0
H e a tin g C o il
5 .0
C o o lin g C o il
7 .0 T y p .
3 8 .0
3 8 .0
9 4 .0
H e a tin g C o il
3 8 .0
A ll p ip in g e n tr a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
A ll p ip in g e n tr a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
4 0 .0
4 0 .0
A ir flo w
5 5 .5
A ir flo w
5 5 .5
2 0 .0
©2007 McQuay International
2 0 .0
30
Position J — Final Filter Section — RDS 802C
Figure 80: 28” Section-Cooling Only and/or Steam or Hot Water
Heat — 52” Section - with Gas or Electric Heat
F i n a l f i l t e r s e c t i o n ( 2 8 " ) f o r u n i t s
a n d / o r s t e a m
o r h o t w a t e r h e a t
o
9 5 %
E f f ic ie n c y
- 2 4 . 0
w
i t h
c o o l i n g
o n l y
s q . f t .
F i n a l f i l t e r s e c t i o n ( 5 2 " ) f o r u n i t s
g a s o r e l e c t r i c h e a t
o
9 5 %
E f f ic ie n c y
- 2 4 . 0
w
i t h
s q . f t .
9 4 .0
9 4 .0
2 8 .0
5 2 .0
A ir flo w
A ir flo w
5 5 .5
5 5 .5
F ilte r q u a n tity & s iz e
4 - 2 4 x 2 4 x 1 2
4 - 1 2 x 2 4 x 1 2
Position K — Discharge Plenum
— RDS 802C
Position K — Blank Compartment Section
— RDS 802C
Figure 82: Blank Compartment
Figure 81: Discharge Plenum
D is c h a r g e
o B o tto m d
o S id e d is c
o F r o n t d is
F ilte r q u a n tity & s iz e
4 - 2 4 x 2 4 x 1 2
4 - 1 2 x 2 4 x 1 2
B la n k c o m p a r tm e n t
o O u t o f a ir s tr e a m - 4 0 " s e c tio n
P le n u m
is c h a r g e
h a rg e
c h a rg e
2 0 .0
6 .0
B o tto m d is c h a r g e
o p e n in g
1 8 .0
9 4 .0
7 6 .0
B o tto m
D is c h a r g e
8 6 .5
F ro n t
D is c h a r g e
1 2 .0
3 .8
4 0 .0
P o w e r a n d C o n tro l E n te ra n c e
( s e e F ig u r e x x x )
5 5 .5
F r o n t D is c h a r g e
4 0 .0
A ir flo w
4 3 .5
5 5 .5
2 0 .0
O p t io n a l S id e D is c h a r g e
o n o p p o s ite p o w e r s id e
©2007 McQuay International
A ir flo w
3 .6
N o te :
B la n k c o m p a r tm e n t r e q u ir e s a d is c h a r g e p le n u m
o r s id e d is c h a r g e in p o s itio n G .
w ith b o tto m
31
Roof Curbs — RDS 802C
Figure 83: Roof Curb without Blank Compartment (Out of Airstream)
2 0 .0
A
C
6 .8
D
1 .5
N o te : C u r b m u s t b e in s ta lle d le v e l.
R A
O P E N IN G
B
S A
O P E N IN G
R e tu
N
3 0
4 0
7 6 .0
A
rn
o n
" A
" A
e
F a n
F
A
2 4
3 0
F
3 6
B
8 2
7 6
7 8
C
6 .8
6 .8
1 4 .8
D
1 .5
4 .5
3 .5
A
B
D
B
2 .0 T Y P .
7 .5
S e e F ig u r e X X X
4 .0 T Y P .
(U N IT L E N G T H M IN U S 6 .4 IN C H E S )
Figure 84: Roof Curb with Blank Compartment (Out of Airstream)
C
A
4 6 .8
2 0 .0
6 .8
D
1 .5
N o te : C u r b m u s t b e in s ta lle d le v e l.
S A
O P E N IN G
R A
O P E N IN G
B
R e tu
N
3 0
4 0
7 6 .0
A
rn
o n
" A
" A
e
F a n
F
A
2 4
B
8 2
3 6
7 8
3 0
F
C
6 .8
6 .8
1 4 .8
7 6
D
1 .5
4 .5
3 .5
A
B
D
7 .5
B
2 .0 T Y P .
S e e F ig u r e X X X
4 .0 T Y P .
U N IT L E N G T H M IN U S 6 .4 IN C H E S
Figure 85: Curb Cross Section A-A
Curb Cross Section B-B
4 .5
3 .2
2
2
2
1
9
1 6 .0
9 .8
5
1 0
4 .6
7
K e y
1 U
2 C
3 2
4 G
5 D
6 C
7 R
8 C
9 F
:
n it B a s e
u r b G a s k e tin g
x 4 N a ile r S tr ip
a lv a n iz e d C u r b
u c t S u p p o rt
a n t S tr ip ( N o t F u r n is h
o o fin g M a te r ia l ( N o t F
o u n te r fla s h in g ( N o t F
la s h in g ( N o t F u r n is h e
2
9
1 0
3
e d )
u r n is h e d )
u r n is h e d )
d )
6
5
1 4 .4
1
7
8
4
4
©2007 McQuay International
32
Blank Access and Drain Pan Only Section Detail Drawings
Figure 86: Cross Section Detail
Access Door Detail
A c c e s s d o o r d e ta il
Cross section detail
3 .6
91.0
86.8
Upright located
between sections
(both sides)
1 .8
1 .8
3 4 .0
3 .0
3 .5
Ceiling (with optional liner)
D o o r O p e n in g
50.2
86.8
Door
(with liner)
4 3 .5
4 3 .5
Door
(with liner)
A ir flo w
* 5 5 .5
3 4 .0
91.0
1 .8
90.0
Base
8 .5
U n it F lo o r
Base
Floor
B a s e R a il
2 .2
1.8 Standing Seam
(located between each section)
5 .2
* C a b in e t h e ig h t
Vestibule Detail Drawing
Electrical Knockouts
Figure 87: Field Installed Coil Piping Vestibule
Figure 88: Discharge Plenum Wiring Entrance Detail
F ie ld in s ta lle d c o il p ip in g v e s tib u le
0.9 diameter K.O.
(quantity = 4)
12.1
5.1
3.4
3.0 diameter K.O.
(quantity = 3)
4 0 .0 0
1 6 .0 0
flo
A ir
2.1
w
3.1
4.3
2.0
4.6
4.8
9.7
4 6 .6
7 .2
N o te :
V e s tib u le r e q u ir e d fo r c o il p ip [in g e n te r in g w ith in th e c u r b a n d r e c o m m e n d e d f o r p ip in g
e n te r in g th e s id e o f th e u n it. U n it c o o lin g c o il a lo n e d o e s n o t r e q u ir e a p ip in g v e s tib u le .
©2007 McQuay International
33
Dimensional Data — RAH047C
Section options and locations
Figure 89: Standard Face Area Coils—RAH 047C
Position A Position B Position C Position D Position E Position F Position G Position H Position I Position J Position K Position L
Outdoor/R
Filter
Blank
Heat/Cool Heat/Blan Supply Air Heat/Blan
Blank
Heat/Cool
Final
Disch.
Blank
eturn Air
k
Fan
k
Filter
Plenum
Comp.
Outside air
hood
0"
Plenum
48"
30% outside air
48"
Mixing box
48"
Economizer
72"
Angular
Drain pan only
Blank access
48"
24"
48"
Cooling
38.0 sq ft CW
40.1 sq ft DX
Cartridge
40 sq ft
24"
Steam/hot
water
29.7 sq ft
A
48"
DWDI
27" diameter
72"
Electric
48"
72"
48"
33" diameter
96"
48"
Blank access
Blank access
Drain pan only
48"
48"
48"
30" diameter
Cooling with
face & bypass
27.7 sq ft CW
48"
A
Blank Access
48"
Cartridge
48 sq ft
Steam/hot
water
29.7 sq ft
Gas
200-1000 mbh
Cooling
38.0 sq ft CW
40.1 sq ft DX
48"
48"
48"
Blank access
Htg/clg
29.7 sq ft HT
38.0 sq ft CW
40.1 sq ft DX
Htg/clg
29.7 sq ft HT
38.0 sq ft CW
40.1 sq ft DX
40" diameter
48"
72"
Blank access
72"
72"
48"
Heating with
face & bypass
20.3sq ft HT
44" diameter
Heating with
face & bypass
20.3sq ft HT
48"
Blank access
48"
24"
Blank
compartment
(out of
airstream)
Cartridge
48 sq ft
48"
72"
72"
48"
48"
Econ. with
RA fan
Discharge
plenum
Cooling with
face & bypass Blank access
27.7 sq ft CW
48"
SWSI
Cartridge
40 sq ft
48"
Econ w/prop exh Econ w/prop exh
fans, bottom or
and side ret
back ret
DX = Direct expansion cooling
CW = Chilled water cooling
HT = Hot water or steam heating
72"
120"
72"
Section Diagram — RAH047C
P o s itio n G
H e a t/B la n k
P o s itio n A
O u td o o r/R e tu rn
A ir
P o s itio n B
F ilte r
P o s itio n H
B la n k
D ra w -T h ro u g h
S e c tio n s
P o s itio n I
H e a t/C o o l
P o s itio n F
S u p p ly A ir F a n
P o s itio n J
F in a l F ilte r
P o s itio n K
D is c h a r g e P le n u m
P o s itio n L
B la n k C o m p a r tm e n t
B lo w - T h r o u g h
S e c tio n s ( 1 )
M a n d a to r y S e c tio n
S e le c tio n R e q u ir e d
P o s itio n C
B la n k
P o s itio n D
H e a t/C o o l
P o s itio n E
H e a t/B la n k
O p tio n a l S e c tio n
( 1 ) B lo w - th r o u g h s e c tio n s n o t a v a ila b le o n u n its w ith a S W S I s u p p ly fa n .
©2007 McQuay International
34
Figure 90: Large Face Area Coils—RAH 047C
Position A Position B Position C Position D Position E Position F Position G Position H Position I Position J Position K Position L
Outdoor/R
Filter
Blank
Heat/Cool Heat/Blan Supply Air Heat/Blan
Blank
Heat/Cool Final Filter Disch.
Blank
eturn Air
k
Fan
k
Plenum
Comp.
OA hood
Angular
Blank access
0"
24"
48"
Plenum
48"
30% OA
48"
Cooling
47.4 sq ft DX
45.0 sq ft CW
48"
Cooling with
face & bypass
45.0 sq ft CW
Cartridge
40 sq ft
24"
Steam/hot
water
29.7 sq ft
A
48"
27" Diameter
72"
48"
Electric
48"
72"
48"
Htg/Clg
29.7 sq ft HT
47.4 sq ft DX
45.0 sq ft CW
33" diameter
96"
48"
Gas
200–1000 MBh
Blank access
Cooling
47.4 sq ft DX
45.0 sq ft CW
Blank access
Cartridge
40 sq ft
Discharge
plenum
48"
48"
48"
48"
Cooling with
face & bypass
45.0 sq ft CW
Blank
compartment
(out of
airstream)
72"
Cartridge
48 sq ft
72"
48"
Htg/Clg
29.7 sq ft HT
47.4 sq ft DX
45.0 sq ft CW
Blank access
48"
48"
SWSI
Drain pan only
Blank access
A
30" diameter
48"
Economizer
Steam/hot
water
29.7 sq ft
Blank access
48"
Cartridge
48 sq ft
DWDI
48"
Drain pan only
Blank access
40" diameter
72"
48"
24"
48"
48"
72"
72"
Econ. with
30" FC
RA fan
72"
Heating with
face & bypass
20.3 sq ft HT
Blank access
48"
Heating with
face & bypass
20.3 sq ft HT
44" diameter
72"
48"
48"
Econ w/prop
Econ w/prop
exh fans,
Econ. with
bottom or back exh and side ret
(2) 15x15 FC
ret
RA fan
48"
72"
DX = Direct expansion cooling
CW = Chilled water cooling
HT = Hot Water or steam heating
120"
Section Diagram — RAH047C
P o s itio n G
H e a t/B la n k
P o s itio n A
O u td o o r/R e tu rn
A ir
P o s itio n B
F ilte r
P o s itio n H
B la n k
D ra w -T h ro u g h
S e c tio n s
P o s itio n I
H e a t/C o o l
P o s itio n F
S u p p ly A ir F a n
P o s itio n J
F in a l F ilte r
P o s itio n K
D is c h a r g e P le n u m
P o s itio n L
B la n k C o m p a r tm e n t
B lo w - T h r o u g h
S e c tio n s ( 1 )
M a n d a to r y S e c tio n
S e le c tio n R e q u ir e d
P o s itio n C
B la n k
P o s itio n D
H e a t/C o o l
P o s itio n E
H e a t/B la n k
O p tio n a l S e c tio n
( 1 ) B lo w - th r o u g h s e c tio n s n o t a v a ila b le o n u n its w ith a S W S I s u p p ly fa n .
©2007 McQuay International
35
Unit Considerations — RAH047C
Splitting Units
Gas Heat
All units with DWDI supply fans may be split at the
Supply Air Fan section outlet.
l
l
Cooling Coils
Cooling Coils are available in either direct expansion or
chilled water type and can be located in the Heat/Cool
sections.
Chilled water cooling coils are available with or without
factory installed three-way modulating control valve as
well as face and bypass dampers and actuator.
Factory wired control of cooling coils is limited to one
cooling coil section per unit.
l
l
l
Heating Media - Steam/Hot Water
Heating coils are available in either steam or hot water
type and can be located in either the Heat/Cool sections
or the Heat sections.
Heating coils are available with or without factory
installed face and bypass dampers and actuator in the
Heat/Cool sections. Factory installed control valves are
not available on heating coils in the Heat/Cool sections.
Heating coils are available with or without a factory
installed control valve in the Heat sections. Factory
installed face and bypass dampers are not available on
heating coils in the Heat sections.
l
l
l
Electric heating coils can be located in the Blow-through
Heat section, position G only on units with a DWDI
supply fan
l
Final Filters
l
If final filters are installed, a Discharge Plenum section is
required in position K.
l
Final filters are not available on units with a SWSI supply
fan.
l
Final filters are not available on units with a blow-through
cooling coil in the Heat/Cool section, position I.
Blank access compartment
l
The blank access compartment is available on units with
a discharge plenum in position K with bottom or side
discharge only.
l
The blank access compartment is not available on units
with a SWSI supply fan
General
l
Electric Heat
A gas heating furnace can be located in the Blowthrough Heat section, position G only on units with a
DWDI supply fan. Factory wired control of cooling coils is
limited to one heating section per unit.
When any selection is located in position H (Blank
access section), I (Blow-through Heat/Cool Section), or J
(Final Filter Section) a heating or blank section must be
placed in position G to provide proper airflow diffusion for
the sections that follow the supply fan
Position A — Outdoor/Return Air Section — RAH047C — Mandatory Selection
Figure 91: Outside Air Hood
1 0 0 %
o
o
Return Air Plenum
R e tu r n A ir P le n u m
o B o tto m re tu rn
o B a c k re tu rn
O u td o o r a ir h o o d
W ith d a m p e r s
W ith o u t d a m p e r s
3 8 .0
6 .0
1 0 .0
B a c k R e tu rn
O p e n in g
9 6 .5
9 9 .0
9 3 .5
B a c k
R e tu rn
8 7 .0
2 .8
6 .0
9 9 .0
3 2 .0
A ir flo w
6 6 .3
5 5 .7
7 3 .0
4 8 .0
B a c k R e t u r n O p e n in g
7 3 .0
A ir flo w
3 1 .8
2 .7
7 .8 to d o o r
N o t e : T h is o p tio n d o e s n o t a ffe c t u n it c u r b le n g th
©2007 McQuay International
36
Position A — Outdoor/Return Air Section — RAH047C (continued)
Figure 92: Return Air Plenum with 30% Outside Air Hood Economizer
R e tu r n A ir P le n u m
o B o tto m re tu rn
o B a c k re tu rn
w ith 3 0 %
O u td o o r A ir H o o d
E c o n o m iz e r
o B o tto m re tu rn
o B a c k re tu rn
3 8 .0
1 0 .0
6 .0
4 .5
3 8 .0
1 0 .0
6 .0
2 .8
9 .0
9 3 .5
B a c k
R e tu rn
8 1 .0
E x h a u s t
O u ts id e A ir
9 0 .0
A IR
L O U V E R S
8 7 .0
B O T T O M
R E T U R N
9 9 .0
8 7 .0
B o tto m
R e tu rn
R e tu r n A ir
O u ts id e A ir
4 .5
2 .8
6 .0
9 .0
B o tto m
B O T T O M R E T U R N
O P E N IN G
4 8 .0
B a c k R e tu r n O p e n in g
3 0 .9
7 3 .0
A ir flo w
7 3 .0
3 6 .2
3 1 .8
B a c k
R e tu rn
7 .8 T O
7 .8 to d o o r
D O O R
O u t s id e A ir L o u v e r s
( B o th S id e s )
Figure 93: Economizer with Return Air Fan
E c o n o m iz e r w ith r e tu r n fa n
o B o tto m re tu rn
o B a c k re tu rn
s
Figure 94: Outdoor/Return Air Mixing Box
O u td o o r /r e tu r n a ir m ix in g b o x
o B o tto m re tu rn
b e lt g u a r d
lig h t, r e c e p ta c le a n d s w itc h
lig h t, r e c e p ta c le , s w itc h a n d b e lt g u a r d
2 .8
1 0 .0
6 .0
9 .0
1 0 .0
9 3 .5
B a c k
R e tu rn
8 1 .0
E x h a u s t
8 7 .0
B o tto m
R e tu rn
6 .0
9 9 .0
8 7 .0
B O T T O M
R E T U R N
9 6 .5
H O O D
R e tu r n A ir
6 .0
4 8 .0
B o tto m R e tu rn
O p e n in g
4 0 " R e tu r n A ir F a n
6 .0
B O T T O M R E T U R N
O P E N IN G
O u ts id e A ir
9 .0
3 8 .0
3 8 .0
O u ts id e A ir
2 .8
A ir flo w
3 2 .5 E x h a u s t
3 7 .6
io n
ith
ith
ith
7 2 .0
E x h a u s t D a m p e rs
A IR L O U V E R S
O p t
o W
o W
o W
6 .0
R e t u r n O p e n in g
3 2 .0
A ir flo w
7 2 .0
E x h a u s t D a m p e rs
6 6 .3
B a c k R e tu r n O p e n in g
7 3 .0
5 5 .7
A ir flo w
3 2 .5 E x h a u s t
7 3 .0
7 .8 T O
D O O R
3 6 .2
7 .8 to d o o r
O u t s id e A ir L o u v e r s
( B o th S id e s )
©2007 McQuay International
37
Position A — Outdoor/Return Air Section — RAH047C
Figure 95: RAH047C - Back Return Propeller Exhaust Fans (2 Shown)
Figure 96: RAH047C - Side Return Propeller Exhaust Fans
©2007 McQuay International
38
Position B — Draw-through Filter Section — RAH047C — mandatory selection
Figure 97: Angular Filters 2-Foot Section
Angular filters - 2-foot section
Throwaway
30% Efficiency
Cartridge Filter with Pre-Filter 2-Foot Section
40.0 sq. ft. cartridge wi th prefilter - 2-foot section
65% Efficiency
95% Efficiency
99.0
99.0
24.0
24.0
73.0
Airflow
Airflow
73.0
5.6
3.2
5.6
Filter quantity & size
7 - 16 x 20 x 2
21 - 16 x 25 x 2
Figure 98: 48.0 sq. ft. Cartridge with Pre-Filters — 4-Foot Section
48.0 sq. ft. cartridge wi th prefilter - 4-foot section
65% Efficiency - staggered
95% Efficiency - staggered
Filter quantity & size
4 - 12 x 24 x 12
8 - 12 x 24 x 12
Blank Section
Blank section
Bottom return - 2-foot section
99.0
99.0
24.0
48.0
Airflow
73.0
73.0
Airflow
A
5.6
30.8
Filter quantity & size
8 - 12 x 24 x 12
8 - 24 x 24 x 12
©2007 McQuay International
39
Blank Access Sections — 4 foot section — Positions B, C, E G and H — RAH047C
Figure 99:
Section Locations
Section locations
Position B - draw-through filter section
Position C - draw-through blank access section
Position E - draw-through heat section
Position G - blow-through heat section (includes diffuser)
Position H - blow-through blank access section (2)
99.0
48.0
73.0
Notes:
(1) This section may be located in one or more of the locations listed above.
(2) Blank Access section in position G and H not available on units with a SWSI supply fan.
(3) Blank Access section in position H requires a blank or heat section in position G.
Heat/Cool Section — Drain Pipe Only — Positions D or I
Figure 100: Section Location
Section locations
Position D - draw-through
Position I - blow-through (2)
1.50 MPT Drain
39.0
2.1
8.5
6.5
1.0
6.0
42.0
99.0
42.0
94.8
6.0
2.1
1.0
All piping entrance holes
should fall eithin this area
6.5
48.0
73.0
24.0
Notes:
(1) Heat/Cool section in position I not available on units with a SWSI supply fan.
(2) Drain pan only section in position I requires a blank or heat section in position G.
©2007 McQuay International
40
Position D — Draw-Through Heat/Cool Section — Large Face Area Coil — RAH047C
Figure 101: Cooling Unit Only - Staggered
C o o
o C
o C
o D
lin g c
h ille d
h ille d
X e v a
o il o
w a te
w a te
p o ra
n ly
r w
r w
to r
Cooling Coil with Face & Bypass Damper - Staggered
C o o lin g c o il w ith fa c e & b y p a s s d a m p e r - s ta g g e r e d
o C h ille d w a te r w ith o u t v a lv e & p ip in g ( 4 5 .0 s q .ft.)
o C h ille d w a t e r w ith 3 - w a y m o d u la tin g v a lv e & p ip in g ( 4 5 .0 s q .ft.)
- s ta g g e re d
ith o u t v a lv e & p ip in g ( 4 5 .0 s q .ft. )
ith 3 - w a y m o d u la tin g v a lv e & p ip in g ( 4 5 .0 s q .ft.)
(4 7 .4 s q .ft.)
D a m p e r a c u a to r
o W ith d a m p e r a c u a to r
o W ith o u t d a m p e r a c u a to r
2 0 .0
1 .0
2 0 .0
1 .0
1 .5 0 M P T D r a in
1 .5 0 M P T D r a in
6 .0
6 .0
C o o lin g C o il
4 2 .0
C o o lin g C o il
4 2 .0
9 9 .0
9 9 .0
F a c e D a m p e r
B y p a s s D a m p e r
A ll p ip in g e n tr a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
A ll p ip in g e n tr a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
4 8 .0
4 8 .0
2 4 .0
A ir flo w
A ir flo w
7 3 .0
7 3 .0
3 .8
2 4 .0
1 4 .7
2 8 .5
2 4 .0
5 3 .1
Position E — Draw-Through Only
Heat/Cool Section — RAH047C Heating
Only Section
Figure 102: Combination Heating & Cooling
C o m b in a tio n h e a tin g a n d c o o lin g
H e a tin g c o il (2 1 .7 s q .ft.)
o S te a m c o il w ith o u t v a lv e a n d p ip in g
o H o t w a te r c o il w ith o u t v a lv e a n d p ip in g
C o o
o C
o C
o D
lin g c
h ille d
h ille d
X e v a
Figure 103:Heating Only Section
o il
w a te r w ith o u t v a lv e & p ip in g ( 4 5 .0 s q .ft. )
w a t e r w ith 3 - w a y m o d u la tin g v a lv e & p ip in g ( 4 5 .0 s q .ft.)
p o ra to r (4 7 .4 s q .ft.)
2 0 .0
1 .0
1 .5 0 M P T D r a in
C o o lin g C o il
H e a
o H
o H
o S
o S
tin
o t
o t
te a
te a
g o
w a
w a
m
m
n ly
te r c
te r c
c o il
c o il
s e c
o il w
o il w
w ith
w ith
tio n
ith o u t v a lv e
ith 3 - w a y m
o u t v a lv e &
2 -w a y m o d
&
o d
p ip
u la
p ip in g
u la tin g
in g ( 2 9
tin g v a
(2 9 .7 s q .ft.)
v a lv e & p ip in g ( 2 9 .7 s q .f t.)
.7 s q .ft.)
lv e & p ip in g ( 2 9 .7 s q .ft.)
N o te : T y p ic a l h o t w a t e r p ip in g s h o w n , s e e IM
6 .0
4 8 7 fo r ty p ic a l s te a m
p ip in g .
4 2 .0
H e a tin g C o il
9 9 .0
4 2 .0
6 .0
N o te :D o
v e s tib u le
c o il c o n n
fo r v e s tib
o r p e
re q u
e c tio
u le d
A ll p ip in g e n tr a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
1 .0
1 2 .0
n e tr a tio n o r
ir e d fo r h e a tin g
n . S e e F ig u r e x x x
e ta ils .
2 4 .0
9 9 .0
9 .0
A ll p ip in g e n tr a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
4 8 .0
6 .0
4 8 .0
A ir flo w
7 3 .0
3 7 .0
1 .0
O p t io n a l F a c to r y P ip in g
(S e e n o te )
A ir flo w
7 3 .0
1 4 .0
2 7 .8
4 8 .0
5 2 .5
©2007 McQuay International
3 8 .0
41
Position F — Supply Air Fan Section — Mandatory Selection — RAH047C
Figure 104: Supply Air Fan — DWDI
S u p p ly a ir fa n - D W D I
o 3 3 "
Supply air fan - DWDI
27"
30"
Fan type
Forward curve
Airfoil
Airfoil with variable inlet vanes
Options
With belt guard
With light, receptacle and switch
With light, receptacle, switch and belt guard
F a n
o F
o A
o A
ty p e
o rw a rd c u rv e
ir fo il
ir fo il w ith v a r ia b le in le t v a n e s
O p t
o W
o W
o W
io n
ith
ith
ith
s
b e lt g u a r d
lig h t, r e c e p ta c le a n d s w itc h
lig h t, r e c e p ta c le , s w itc h a n d b e lt g u a r d
1 9 .3
C
3 0 .1
D
24.0
9 9 .0
4 9 .6
99.0
A
48.0
4 8 .0
E
Supply Fan
4 .3
Airflow
B
4 8 .0
3 3 " S u p p ;y F a n
73.0
A ir flo w
4 6 .4
7 3 .0
Diameter
27”
30”
A
B
C
D
E
41.4
38.8
27.6
30.0
9.1
45.5
42.0
25.6
27.9
4.3
Figure 105: Supply Air Fan — SWSI
S u p p ly a ir fa n - S W S I
o 4 0 " o 4 4 "
F a n ty p e
o A ir fo il w ith o u t v a r ia b le in le t v a n e s
o A ir fo il w ith v a r ia b le in le t v a n e s
D is c h a r g e o p e n in g
o B o tto m d is c h a r g e
o S id e d is c h a r g e
O p t
o W
o W
o W
io n
ith
ith
ith
s
b e lt g u a r d
lig h t, r e c e p ta c le a n d s w itc h
lig h t, r e c e p ta c le , s w itc h a n d b e lt g u a r d
2 8 .0
S u p p ly A ir O p e n in g
6 .0
1 0 .0
8 1 .0
9 9 .0
P o w e r a n d C o n tro l E n te ra n c e
( S e e F ig u r e x x x )
2 4 .0
4 8 .0
4 2 .0
3 .0
A ir flo w
6 1 .0
7 3 .0
8 .5
©2007 McQuay International
O p t io n a l s id e d is c h a r g e
o n o p p o s ite p o w e r s id e .
42
Position G — Blow-Through Heat Only Section — RAH047C
Figure 106: Heat Only Section
H e a
o H
o H
o S
o S
tin
o t
o t
te a
te a
g o
w a
w a
m
m
n ly
te r c
te r c
c o il
c o il
s e c
o il w
o il w
w ith
w ith
tio n
ith o u t v a lv e
ith 3 - w a y m
o u t v a lv e &
2 -w a y m o d
&
o d
p ip
u la
p ip
u la
in g
tin g
in g
tin g
(2 9
v a
N o te : T y p ic a l h o t w a t e r p ip in g s h o w n , s e e IM
S e e N o te o n b o tto m
H e a tin g o n ly s e c tio n
o E le c tr ic h e a t
(2 9 .7 s q .ft.)
v a lv e & p ip in g ( 2 9 .7 s q .f t.)
.7 s q .ft.)
lv e & p ip in g ( 2 9 .7 s q .ft.)
4 8 7 fo r ty p ic a l s te a m
S e e N o te o n b o tto m
o f p a g e .
p ip in g .
o f p a g e .
9 9 .0
A ll p ip in g e n tr a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
9 9 .0
3 .0 d ia . K .O . ( 2 )
9 .0
.9 d ia . K .O .
6 .0
4 8 .0
3 7 .0
1 .0
P o w e r a n d C o n tro l
E n te ra n c e
( S e e F ig u r e x x x )
A ir flo w
7 3 .0
4 8 .0
O p t io n a l F a c to r y P ip in g
(S e e n o te )
A ir flo w
3 3 .0
7 3 .0
3 8 .0
Figure 107: Heat Only Section
H e a tin g o n ly s e c tio n
o G a s h e a t w it h c o n t r o ls ( 2 0 0 - 1 0 0 0 M B h o u tp u t)
S e e N o te o n b o tto m
o f p a g e .
A ll p ip in g e n tr a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
9 9 .0
8 .6
6 .0
4 .2
4 .0
4 8 .0
A ir flo w
7 3 .0
Note:
Heat only section in position G not available on units with a SWSI supply fan.
©2007 McQuay International
43
Position I — Blow-Through Heat/Cool Section - Standard Face Area Coils — RAH047C
Figure 108: Cooling Coil Only
C o o
o C
o C
o D
lin g c
h ille d
h ille d
X e v a
o il o
w a te
w a te
p o ra
Cooling Coil with Face & Bypass Damper
C o o lin g c o il w ith fa c e & b y p a s s d a m p e r
o C h ille d w a te r w ith o u t v a lv e & p ip in g ( 2 7 .7 s q .ft. )
o C h ille d w a t e r w ith 3 - w a y m o d u la tin g v a lv e & p ip in g ( 2 7 .7 s q .ft.)
n ly
r w ith o u t v a lv e & p ip in g ( 3 8 .0 s q .ft. )
r w ith 3 - w a y m o d u la tin g v a lv e & p ip in g ( 3 8 .0 s q .ft.)
to r (4 0 .1 s q .ft.)
S e e n o te s a t b o tto m
D a m p e r a c u a to r
o W ith d a m p e r a c u a to r
o W ith o u t d a m p e r a c u a to r
o f p a g e .
S e e n o te s a t b o tto m
o f p a g e .
1 0 .0
1 0 .0
1 .0
1 .5 0 M P T D r a in
1 .0
1 .5 0 M P T D r a in
6 .0
4 2 .0
4 2 .0
C o o lin g C o il
6 .0
F a c e a n d B y p a s s D a m p e r
9 9 .0
9 9 .0
C o o lin g C o il
A ll p ip in g e n tr a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
A ll p ip in g e n tr a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
4 8 .0
4 8 .0
A ir flo w
A ir flo w
7 3 .0
7 3 .0
3 .8
2 1 .0
2 4 .0
2 4 .0
Figure 109: Combination Heating and Cooling
H e a tin g c o il w ith fa c e & b y p a s s d a m p e r (2 0 .3 s q .ft.)
o S te a m c o il w ith o u t v a lv e a n d p ip in g
o H o t w a te r c o il w ith o u t v a lv e a n d p ip in g
H e a tin g c o il (2 9 .7 s q .ft.)
o S te a m c o il w ith o u t v a lv e a n d p ip in g
o H o t w a te r c o il w ith o u t v a lv e a n d p ip in g
C o o
o C
o C
o D
lin g c
h ille d
h ille d
X e v a
D a m p e r a c u a to r
o W ith d a m p e r a c u a to r
o W ith o u t d a m p e r a c u a to r
o il
w a te r w ith o u t v a lv e & p ip in g ( 3 8 .0 s q .ft. )
w a t e r w ith 3 - w a y m o d u la tin g v a lv e & p ip in g ( 3 8 .0 s q .ft.)
p o ra to r (4 0 .1 s q .ft.)
S e e n o te s a t b o tto m
Heating Coil with Face & Bypass Damper (20.3 sq. ft.)
S e e n o te s a t b o tto m
o f p a g e .
o f p a g e .
A ll p ip in g e n tr a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
1 0 .0
1 .0
1 .5 0 M P T D r a in
1 .5 0 M P T D r a in
6 .0
C o o lin g C o il
C o o lin g C o il
4 2 .0
9 9 .0
H e a tin g C o il
9 9 .0
F a c e a n d B y p a s s D a m p e r
4 2 .0
D o o r p e n e tr a tio n o r
v e s tib u le r e q u ir e d fo r
h e a tin g c o il c o n n e c tio n
4 2 .0
6 .0
1 .0
D o
v e
h e
S e
1 0 .0
A ll p ip in g e n tr a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
o r p e n
s tib u le
a tin g c
e F ig u
e tr a tio n o
r e q u ir e d
o il c o n n e
re fo r v e s
r
fo r
c tio n .
tib u le d e t a ils
1 .0
6 .0
1 0 .0
4 8 .0
4 8 .0
A ir flo w
A ir flo w
7 3 .0
7 3 .0
2 1 .0
7 .0
2 1 .0
2 4 .0
2 4 .0
Notes: (1) Heat/Cool section in position I not available on units with a SWSI supply fan.
(2) Heat/Cool section in position I requires a blank or heating section in position G.
©2007 McQuay International
44
Position I — Blow-Through Heat/Cool Section Large Face Area Coils — RAH047C
Figure
Coil Only - Staggered
g 110:y Cooling
g g
o
o
o
Cooling Coil with Face & Bypass Damper - Staggered
o
C h ille d w a te r w ith o u t v a lv e & p ip in g ( 4 5 .0 s q .ft. )
C h ille d w a t e r w ith 3 - w a y m o d u la tin g v a lv e & p ip in g ( 4 5 .0 s q .ft.)
D X e v a p o ra to r (4 7 .4 s q .ft.)
S e e n o te s a t b o tto m
C h ille d w a te r w ith o u t v a lv e & p ip in g ( 4 5 .0 s q .ft.)
C h ille d w a t e r w ith 3 - w a y m o d u la tin g v a lv e & p ip in g ( 4 5 .0 s q .ft.)
o
D a m p e r a c u a to r
o W ith d a m p e r a c u a to r
o W ith o u t d a m p e r a c u a to r
o f p a g e .
S e e n o te s a t b o tto m
o f p a g e .
2 0 .0
1 .0
2 0 .0
1 .5 0 M P T D r a in
1 .0
1 .5 0 M P T D r a in
6 .0
6 .0
C o o lin g C o il
4 2 .0
4 2 .0
C o o lin g C o il
9 9 .0
9 9 .0
F a c e D a m p e r
B y p a s s D a m p e r
A ll p ip in g e n tr a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
A ll p ip in g e n tr a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
4 8 .0
4 8 .0
2 4 .0
A ir flo w
A ir flo w
7 3 .0
7 3 .0
3 .8
1 4 .7
2 4 .0
2 4 .0
2 8 .5
5 3 .1
Figure 111: Combination Heating and Cooling
H e a tin g c o il (2 9 .7 s q .ft.)
o S te a m c o il w ith o u t v a lv e a n d p ip in g
o H o t w a te r c o il w ith o u t v a lv e a n d p ip in g
C o o
o C
o C
o D
lin g c
h ille d
h ille d
X e v a
o il
w a te r w ith o u t v a lv e & p ip in g ( 4 5 .0 s q .ft. )
w a t e r w ith 3 - w a y m o d u la tin g v a lv e & p ip in g ( 4 5 .0 s q .ft.)
p o ra to r (4 7 .4 s q .ft.)
2 0 .0
S e e n o te s a t b o tto m o f p a g e .
1 .0
1 .5 0 M P T D r a in
C o o lin g C o il
6 .0
4 2 .0
H e a tin g C o il
9 9 .0
4 2 .0
6 .0
N o te :D o
v e s tib u le
c o il c o n n
fo r v e s tib
o r p e
re q u
e c tio
u le d
1 .0
1 2 .0
A ll p ip in g e n tr a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
n e tr a tio n o r
ir e d fo r h e a tin g
n . S e e F ig u r e x x x
e ta ils .
2 4 .0
4 8 .0
A ir flo w
7 3 .0
1 4 .0
2 7 .8
4 8 .0
5 2 .5
Notes: (1) Heat/Cool section in position I not available on units with a SWSI supply fan.
(2) Heat/Cool section in position I requires a blank or heating section in position G.
©2007 McQuay International
45
Position J — Final Filter Section — RAH047C
Figure 112: 40 sq. ft. Cartridge - 4 Foot Section
48 sq. ft. Cartridge - 6 Foot Section
40.0 sq. ft. cartridge - 4-foot section
95% Efficiency
40.0 sq. ft. cartridge - 6-foot section
95% Efficiency - staggered
See notes at bottom of page.
See notes at bottom of page.
99.0
99.0
24.0
24.0
24.0
48.0
Airflow
Airflow
73.0
73.0
29.6
54.8
29.6
Filter quantity & size
4 - 12 x 24 x 12
8 - 24 x 24 x 12
Filter quantity & size
8 - 12 x 24 x 12
8 - 24 x 24 x 12
Figure 113: Blank Access Section
Blank access section
Blank - 6-foot section
Blank access section
Blank - 4-foot section
See notes at bottom of page.
See notes at bottom of page.
99.0
99.0
24.0
24.0
48.0
24.0
Airflow
Airflow
73.0
73.0
Notes:
(1) Final Filter section not available on units with a SWSI supply fan.
(2) Final filters are not available on units with a blow-through cooling coil in the Heat/Cool section, position I.
(3) Final filter option requires a discharge plenum in position K.
(4) Final filter option requires a blank or heating section in position G.
©2007 McQuay International
46
Position K — Discharge Plenum
— RAH047C
Position K — Blank Compartment Section
— RAH047C
Figure 114:Discharge Plenum
Figure 115:Blank Compartment
Discharge plenum
Bottom discharge
Front discharge
Side discharge
B lank com partm ent
Out fo iarstr
eam -6 fo
ot
N otes:
(1) Blank com partment equi
r res a discharge plenum with
otto
bm or side discharge ni positi
on K.
(2) Blank com partment si available afte
r a SW SI uppl
s y
n fa
secti
on.
Note:
(1) Discharge plenum not available with a SWSI supply fan.
28.0
6.0
10.0
Optional Front
Discharge Opening
99.0
81.0
Bottom
Discharge
93.5
Front
Discharge
2.8
Power and Control Entrance
99.0
Bottom
Discharge
Opening
48.0
48.0
42.0
24.0
3.0
Airfl
ow
31.8 Front
Discharge
Optional side discharge
on opposite power side
73.0
61.0
Side 73.0
Discharge
2.7 8.5
Blank Access & Drain Pan Only Section Detail Drawings
Figure 116: Cross Section DetailAccess Door Detail
Cross section detail
Access door detail
3.6
D
Upright located
between sections
(both sides)
E
1.8
1.8
3.0
42.0
3.5
Ceiling (with optional liner)
Door Opening
C
E
Door
(with liner)
Door
(with liner)
61.0
85.0
D
Airflow
*73.0
42.0
F
Base
1.8
Base
Floor
8.5
1.8 Standing Seam
(located between each section)
Unit Floor
RAH
047C
C
67.7
D
96.0
E
91.8
C = Ceiling to floor (with liners)
D = Door to door (with liners)
E = Upright to upright, located between sections
F = Base to base
©2007 McQuay International
F
95.0
Base Rail
2.2
5.2
*Cabinet height
47
Vestibule Detail Drawings
Figure 117: Heat Coil Piping Vestibule — 4 Foot 2 Foot
H e a t c o il p ip in g v e s tib u le - 2 -fo o t
4 8 .0 0
2 4 .0 0
1 6 .0 0
fl
A ir
o w
1 6 .0 0
flo
A ir
A
7 .1 8
©2007 McQuay International
w
6 4 .1 1
7 .1 8
48
Roof Curbs — RAH047C
Figure 118: Roof Curb without Blank Compartment
6.8
A
B
6.8
1.5
1.5
RA
OPENING
87.0
SA
OPENING
81.0
A
A
B
1.5
B
7.5
2.0 TYP.
4.0 TYP.
Dimension (in.)
A
B
RAH047C
38.0
28.0
(UNIT LENGTH MINUS 6.4 INCHES)
Figure 119: Roof Curb with Blank Compartment
A
6.8
78.8
B
1.5
6.8
SA
OPENING
RA
OPENING
87.0
1.5
A
81.0
A
B
1.5
7.5
B
2.0 TYP.
4.0 TYP.
UNIT LENGTH MINUS 6.4 INCHES
Figure 120: Curb Cross Section A-A
Curb Cross Section B-B
4 .5
3 .2
2
2
2
1
9
1 6 .0
9 .8
5
1 0
4 .6
7
K e y
1 U
2 C
3 2
4 G
5 D
6 C
7 R
8 C
9 F
:
n it B a s e
u r b G a s k e tin g
x 4 N a ile r S tr ip
a lv a n iz e d C u r b
u c t S u p p o rt
a n t S tr ip ( N o t F u r n is h
o o fin g M a te r ia l ( N o t F
o u n te r fla s h in g ( N o t F
la s h in g ( N o t F u r n is h e
2
9
1 0
3
e d )
u r n is h e d )
u r n is h e d )
d )
6
5
1 4 .4
1
7
8
4
4
©2007 McQuay International
49
Electrical Knockouts—RAH 047C and 077C
Figure 121: Discharge Plenum Power and Control Wiring Entrance Detail
8 .8
7 .6
3 .0 D IA . K .O .
(Q T Y = 3 )
6 .6
3 .4
3 .4
.9 D IA . K .O .
(Q T Y = 4 )
1 5 .3
2 .0
1 2 .9
4 .6
4 .8
N o t e : 0 .9 d ia m e te r a n d 3 .0 d ia m e te r k n o c k o u ts a r e e le c tr ic a l e n te r a n c e lo c a tio n s o n th e u n it o n ly .
Figure 122: Electric Heat Power and Control Entrance Detail
7 .6
3 .0 D IA . K .O .
(Q T Y = 2 )
.9 D IA . K .O .
(Q T Y = 1 )
8 .8
6 .6
1 5 .3
1 7 .7
1 8 .7
N o t e : 0 .9 d ia m e te r a n d 3 .0 d ia m e te r k n o c k o u ts a r e e le c tr ic a l e n te r a n c e lo c a tio n s o n th e u n it o n ly .
©2007 McQuay International
50
Dimensional Data — RAH077C
Section options and locations
Figure 123:Standard Face Area Coils—RAH 077C
Position A Position B
Outdoor/R
Filter
eturn Air
OA hood
0"
Plenum
72"
30% OA
72"
Economizer
96"
Econ. with
return air fan
96"
Mixing box
Angular
Position C
Blank
Position D Position E Position F Position G Position H Position I Position J Position K Position L
Heat/Cool
Heat/
Supply Heat/Blank Blank
Heat/Cool
Final
Disch.
Blank
Blank
Air Fan
Filter
Plenum
Comp.
Blank access
Drain pan only
24"
48"
48"
Cartridge
64 sq ft
Cartridge
56 sq ft
Cooling
51.9 sq ft CW
54.7 sq ft DX
24"
48"
Cartridge
80 sq ft
Blank access
48"
33" diameter
Steam/hot
water
42.2 sq ft
48"
72"
48"
Blank access
36" diameter
Electric
48"
96"
48"
Cooling with
face & bypass
36.3 sq ft CW
24"
72"
Gas
40" diameter 500–1400 MBh
96"
48"
Blank Access
DWDI
Steam/hot
water
42.2 sq ft
48"
44" diameter
Gas
1500–2000
MBh
48"
72"
48"
49" diameter
Blank access
96"
48"
Cartridge
56 sq ft
Discharge
plenum
48"
48"
48"
Cooling
51.9 sq ft CW
54.7 sq ft DX
120"
72"
48"
72"
72"
Cooling with
face & bypass
36.3 sq ft CW
Cartridge
80 sq ft
48"
96"
Htg/clg
42.2 sq ft HT Blank access
51.9 sq ft CW
54.7 sq ft DX
48"
Heating with
Econ w/prop exh, Econ w/prop exh,
face & bypass
back ret
side ret
28.1sq ft HT
Blank
compartment
(out of
airstream)
Cartridge
64 sq ft
48"
48"
Htg/clg
42.2 sq ft HT
51.9 sq ft CW
54.7 sq ft DX
SWSI
Blank access Drain pan only
48"
48"
Heating with
face & bypass Blank access
28.1sq ft HT
72"
48"
Econ w/prop exh,
bottom return
DX = Direct expansion cooling
CW = Chilled water cooling
HT = Hot water or steam heating
72"
96"
Section Diagram — RAH077C
P o s itio n G
H e a t/B la n k
P o s itio n A
O u td o o r/R e tu rn
A ir
P o s itio n B
F ilte r
P o s itio n H
B la n k
D ra w -T h ro u g h
S e c tio n s
P o s itio n I
H e a t/C o o l
P o s itio n F
S u p p ly A ir F a n
P o s itio n J
F in a l F ilte r
P o s itio n K
D is c h a r g e P le n u m
P o s itio n L
B la n k C o m p a r tm e n t
B lo w - T h r o u g h
S e c tio n s ( 1 )
M a n d a to r y S e c tio n
S e le c tio n R e q u ir e d
P o s itio n C
B la n k
P o s itio n D
H e a t/C o o l
P o s itio n E
H e a t/B la n k
O p tio n a l S e c tio n
( 1 ) B lo w - th r o u g h s e c tio n s n o t a v a ila b le o n u n its w ith a S W S I s u p p ly fa n .
( 2 ) B u r g la r b a r s a n d is o la tio n d a m p e r s n o t a v a ila b le w h e n t h e r e a r e n o s e c tio n s b e tw e e n th e s u p p ly fa n
a n d th e d is c h a r g e p le n u m fo r u n its w ith b o tto m d is c h a g e .
©2007 McQuay International
51
Figure 124: Large Face Area Coils—RAH 077C
Position A
Position B
Position C
Position D
Position E
Position F
Filter
Blank
Heat/Cool
Heat/Blank
Supply Air Fan
OA hood
Angular
Blank access
0"
24"
48"
Outdoor/Return
Air
Plenum
72"
30% OA
72"
Economizer
96"
Econ. with
return air fan
96"
Mixing box
Steam/hot
water
42.2 sq ft
48"
48"
72"
Cooling with
face & bypass Blank access
62.3 sq ft CW
Cartridge
56 sq ft
24"
48"
96"
Cartridge
80 sq ft
Blank access
Htg/clg
42.2 sq ft HT
76.6 sq ft DX
72.6 sq ft CW
72"
24"
48"
72"
36" diameter
Electric
96"
48"
96"
Drain pan only
Blank
SWSI
48"
44" diameter
Gas
1500–2000
MBh
72"
48"
49" diameter
Blank access
Heating with
Econ w/prop exh Econ w/prop exh face & bypass
fans, back return fans, side return 28.1 sq ft HT
120"
96"
48"
Position J
Position K
Position L
Heat/Cool
Final Filter
Disch. Plenum
Blank Comp.
Cartridge
56 sq ft
Discharge
plenum
Blank
compartment
(out of
airstream)
48"
48"
48"
72"
Cooling with
face & bypass
62.3 sq ft CW
Cartridge
64 sq ft
96"
72"
Htg/clg
42.2 sq ft HT
76.6 sq ft DX
72.6 sq ft CW
Cartridge
80 sq ft
48"
72"
96"
96"
Drain pan only Blank access
48"
48"
72"
Position I
Cooling
Blank access 76.6 sq ft DX
72.6 sq ft CW
Gas
40" diameter 500-1400 mbh
96"
48"
Heat/Blank
DWDI
Cooling
Steam/hot
76.6 sq ft DX
water
42.2
sq
ft
72.6 sq ft CW
33" diameter
Cartridge
64 sq ft
Blank access
Position G Position H
48"
Heating with
face & bypass
Blank access
28.1 sq ft HT
48"
72"
Econ w/prop exh fans,
bottom return
DX = Direct expansion cooling
CW = Chilled water cooling
HT = Hot Water or steam heating
72"
96"
Section Diagram — RAH077C
P o s itio n G
H e a t/B la n k
P o s itio n A
O u td o o r/R e tu rn
A ir
P o s itio n B
F ilte r
P o s itio n H
B la n k
D ra w -T h ro u g h
S e c tio n s
P o s itio n I
H e a t/C o o l
P o s itio n F
S u p p ly A ir F a n
P o s itio n J
F in a l F ilte r
P o s itio n K
D is c h a r g e P le n u m
P o s itio n L
B la n k C o m p a r tm e n t
B lo w - T h r o u g h
S e c tio n s ( 1 )
M a n d a to r y S e c tio n
S e le c tio n R e q u ir e d
P o s itio n C
B la n k
P o s itio n D
H e a t/C o o l
P o s itio n E
H e a t/B la n k
O p tio n a l S e c tio n
( 1 ) B lo w - th r o u g h s e c tio n s n o t a v a ila b le o n u n its w ith a S W S I s u p p ly fa n .
( 2 ) B u r g la r b a r s a n d is o la tio n d a m p e r s n o t a v a ila b le w h e n t h e r e a r e n o s e c tio n s b e tw e e n th e s u p p ly fa n
a n d th e d is c h a r g e p le n u m fo r u n its w ith b o tto m d is c h a g e .
©2007 McQuay International
52
Unit Considerations — RAH077C
Splitting Units
Electric Heat
l
All units with DWDI supply fans may be split at the
Supply Air Fan section outlet.
l
Units exceeding 52 feet in length may need to be split at
the Supply Air Fan section outlet for shipping purposes.
l
Gas Heat
l
Cooling Coils
l
Cooling Coils are available in either direct expansion or
chilled water type and can be located in the Heat/Cool
sections.
l
Chilled water cooling coils are available with or without
factory installed three-way modulating control valve as
well as face and bypass dampers and actuator.
l
Factory wired control of cooling coils is limited to one
cooling coil section per unit.
Heating Media - Steam/Hot Water
A gas heating furnace can be located in the Blowthrough Heat section, position G only on units with a
DWDI supply fan. Factory wired control of cooling coils is
limited to one heating section per unit.
Final Filters
l
l
l
If final filters are installed, a Discharge Plenum section is
required in position K.
Final filters are not available on units with a SWSI supply
fan.
Final filters are not available on units with a blow-through
cooling coil in the Heat/Cool section, position I.
Blank access compartment
l
Heating coils are available in either steam or hot water
type and can be located in either the Heat/Cool sections
or the Heat sections.
l
l
Heating coils are available with or without factory
installed face and bypass dampers and actuator in the
Heat/Cool sections. Factory installed control valves are
not available on heating coils in the Heat/Cool sections.
l
Heating coils are available with or without a factory
installed control valve in the Heat sections. Factory
installed face and bypass dampers are not available on
heating coils in the Heat sections.
l
Electric heating coils can be located in the Blow-through
Heat section, position G only on units with a DWDI
supply fan
The blank access compartment is available on units with
a discharge plenum in position K with bottom or side
discharge only.
The blank access compartment is not available on units
with a SWSI supply fan
General
l
When any selection is located in position H (Blank
access section), I (Blow-through Heat/Cool Section), or J
(Final Filter Section) a heating or blank section must be
placed in position G to provide proper airflow diffusion for
the sections that follow the supply fan
Position A — Outdoor/Return Air Section — RAH077C — Mandatory Selection
Figure 125: 100% Outside Air Hood
1 0 0 %
o
o
Return Air Plenum
R e tu r n a ir p le n u m
o
B o tto m re tu rn
o
B a c k re tu rn
O u td o o r a ir h o o d
W ith d a m p e r s
W ith o u t d a m p e r s
6 .0
2 .8
6 2 .0
9 3 .5
B a c k
R e tu rn
9 9 .0
9 6 .5
A
1 0 .0
B o tto m R e tu rn
O p e n in g
9 9 .0
9 3 .5
B a c k
R e tu rn
2 .8
6 .0
3 2 .0
7 9 .8
9 7 .0
A ir flo w
2 4 .0
B a c k
R e tu rn
O p e n in g
A ir flo w
4 1 .8 B a c k
R e tu rn
2 .7
9 7 .0
A
9 0 .3
4 8 .0
7 .8 to d o o r
N o t e : T h is o p tio n d o e s n o t a ffe c t u n it c u r b le n g th
©2007 McQuay International
53
Position A — Outdoor/Return Air Section - RAH077C — Mandatory Selection (continued)
Figure 126: Return Air Plenum with 30% Outside Air Hood Economizer
R e tu r n a ir p le n u m
o
B o tto m re tu rn
o
B a c k re tu rn
B o tto m
w ith 3 0 %
1 0 .0
R e tu r n O p e n in g
4 .5
E c o n o m iz e r
o
B o tto m re tu rn
o
B a c k re tu rn
o u td o o r a ir h o o d
2 .8
2 .8
2 .8
4 8 .0
2 4 .0
5 .0
4 2 .7 A ir L o u v e r s
A ir flo w
O u t s id e A ir
6 .0
E x h a u s t D a m p e rs
B a c k R e t u r n O p e n in g
R e tu r n O p e n in g
R e tu r n A ir
8 7 .0
B o tto m
R e tu rn
9 3 .5
B a c k
R e tu rn
9 9 .0
6 .0
2 .8
6 2 .0
6 .0
8 9 .0
E x h a u s t
8 7 .0
B o tto m
R e tu rn
4 .5
5 .0
O u t s id e A ir
9 3 .5
B a c k
R e tu rn
9 0 .0
A ir
L o u v e rs
B o tto m
1 0 .0
6 2 .0
6 .0
B o tto m R e tu rn
O p e n in g
2 4 .0
7 2 .0
4 7 .6 E x h a u s t
9 7 .0
9 7 .0
4 9 .5 4 1 .8 B a c k re tu rn
4 5 .1
4 7 .6 B a c k
P le n u m
7 .8 to d o o r
2 .7
A ir flo w
7 .8 to d o o r
O u t s id e A ir L o u v e r s
( B o th S id e s )
Figure 127: Economizer with Return Air Fan
E c o n o m iz e r w ith r e tu r n fa n
o
B o tto m re tu rn
o
B a c k re tu rn
O p tio
o
W
o
W
o
W
Figure 128: Outdoor/Return Air Mixing Box
E c o n o m iz e r w ith r e tu r n fa n
o
B o tto m re tu rn
o
B a c k re tu rn
n s
ith b e lt g u a r d
ith lig h t, r e c e p ta c le a n d s w itc h
ith lig h t, r e c e p ta c le , s w itc h a n d b e lt g u a r d
1 0 .0
2 .8
5 .0
6 2 .0
6 .0
1 0 .0
O u t s id e A ir
9 3 .5
B a c k
R e tu rn
2 .8
8 9 .0
E x h a u s t
5 .0
8 7 .0
B o tto m
R e tu rn
R e tu r n A ir
O u t s id e A ir
6 .0
6 2 .0
B o tto m
R e tu rn
B o tto m R e tu rn
O p e n in g
9 6 .5
H o o d
8 7 .0
2 4 .0
9 9 .0
B o tto m
R e tu rn
B o tto m R e tu rn
O p e n in g
E x h a u s t D a m p e rs
B a c k R e t u r n O p e n in g
6 .0
6 .0
7 2 .0
4 8 .0
2 4 .0
3 2 .0
4 7 .6 E x h a u s t
9 7 .0
4 5 .1
A ir flo w
9 0 .3
4 7 .6 B a c k
P le n u m
7 .8 to d o o r
R e tu r n A ir F a n
O u t s id e A ir L o u v e r s
( B o th S id e s )
©2007 McQuay International
7 9 .8
9 7 .0
A ir flo w
7 .8 to d o o r
54
Position A — Outdoor/Return Air Section — RAH077C
Figure 129: RAH077C - Back Return Propeller Exhaust Fans (2 Shown)
Figure 130: RAH077C - Side Return Propeller Exhaust Fans
©2007 McQuay International
55
Position B — Draw-Through Filter Section — RAH077C — Mandatory Selection
Figure 131: Angular Filters — 2-Foot Section
Angular filters - 2-foot section
Throwaway
30% efficiency
Cartridge Filter with Pre-Filter — 2-Foot Section
56 sq. ft. cartridge wi th prefilter - 2 foot section
65% effeciency
95% effeciency
99.0
99.0
24.0
24.0
Airflow
Airflow
97.0
3.2
97.0
Filter quantity & size
11 - 16 x 20 x 2
33 - 16 x 25 x 2
5.6
Figure 132: 64.0 sq. ft. Cartridge with Pre-Filters — 4’ section
Filter quantity & size
4 - 12 x 24 x 12
12 - 24 x 24 x 12
5.6
6’ section
80 sq. ft. cartridge wi th prefilter - 6-foot section
65% effeciency - staggered
95% effeciency - staggered
64 sq. ft. cartridge wi th prefilter - 4 foot section
65% effeciency - staggered
95% effeciency - staggered
99.0
99.0
48.0
48.0
24.0
Airflow
Airflow
97.0
97.0
Filter quantity & size
16 - 24 x 24 x 12
5.6
30.8
5.6
54.8
Filter quantity & size
8 - 12 x 24 x 12
16 - 24 x 24 x 12
Figure 133: Blank Section — 2’ Section
B lank section -2-footsection
99.0
24.0
Airfl
ow
97.0
©2007 McQuay International
56
Blank Access Sections — 4 Foot Section — Positions B, C, E G and H — RAH077C
Figure 134: Section Locations
S e c t
o P
o P
o P
o P
o P
io n lo
o s itio n
o s itio n
o s itio n
o s itio n
o s itio n
c a
B
C
E
G
H
tio
-
n s
d ra
d ra
d ra
d ra
d ra
w -th
w -th
w -th
w -th
w -th
ro
ro
ro
ro
ro
u g
u g
u g
u g
u g
h filte r s
h b la n k
h h e a t s
h h e a t s
h b la n k
e c
a c
e c
e c
a c
tio
c e
tio
t io
c e
n
s s s e c tio n
n
n ( in c lu d e s d iffu s e r )
s s s e c tio n ( 3 )
9 9 .0
4 8 .0
A ir flo w
9 7 .0
N o
(1 )
(2 )
(3 )
te
T
B
B
s :
h is s e c tio n m a y b e lo c a te d in o n e o r m o r e o f th e lo c a tio n s lis te d a b o v e .
la n k A c c e s s s e c tio n in p o s itio n G a n d H n o t a v a ila b le o n u n its w ith a S W S I s u p p ly fa n .
la n k A c c e s s s e c tio n in p o s itio n H r e q u ir e s a b la n k o r h e a t s e c t io n in p o s itio n G .
Heat/Cool Section — Drain Pipe Only — Positions D or I
Figure 135: Section Location
S e c tio n lo c a tio n s
o P o s itio n D - d r a w - th r o u g h
o P o s itio n I - b lo w - th r o u g h ( 2 )
1 .5 0 M P T D r a in
3 9 .0
8 .5
6 .5
1 .0
6 .0
2 .1
4 2 .0
9 4 .8
9 9 .0
4 2 .0
2 .1
A ll p ip in g e n te r a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
6 .0
6 .5
1 .0
4 8 .0
9 7 .0
A ir flo w
2 4 .0
N o te s :
( 1 ) B la n k A c c e s s s e c tio n in p o s itio n I n o t a v a ila b le o n u n its w ith a S W S I s u p p ly fa n .
( 2 ) D r a in p a n o n ly s e c t io n in p o s itio n I r e q u ir e s a b la n k o r h e a t s e c t io n in p o s itio n G .
©2007 McQuay International
57
Position D — Draw-Through Heat/Cool Section — Standard Face Area Coil — RAH077C
Figure 136: Cooling Unit Only
C o o
o C
o C
o D
lin g c
h ille d
h ille d
X e v a
o il o
w a te
w a te
p o ra
Cooling Coil with Face & Bypass Damper
C o o lin g c o il w ith fa c e a n d b y p a s s d a m p e r
o C h ille d w a te r w ith o u t v a lv e a n d p ip in g ( 3 6 .3 s q . ft.)
o C h ille d w a t e r w ith 3 - w a y m o d u la tin g v a lv e a n d p ip in g ( 3 6 .3 s q . ft. )
n ly
r w ith o u t v a lv e a n d p ip in g ( 5 1 .9 s q . f t.)
r w ith 3 - w a y m o d u la tin g v a lv e a n d p ip in g ( 5 1 .9 s q . ft .)
to r (5 4 .7 s q . ft.)
D a m p e r A c tu a to r
o W ith d a m p e r a c tu a to r
o W ith o u t d a m p e r a c tu a to r
1 0 .0
1 0 .0
1 .0
1 .5 0 M P T D r a in
1 .0
1 .5 0 M P T D r a in
6 .0
6 .0
F a c e a n d B y p a s s D a m p e r
4 2 .0
4 2 .0
C o o lin g C o il
9 9 .0
9 9 .0
C o o lin g C o il
A ll p ip in g e n te r a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
A ll p ip in g e n te r a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
4 8 .0
4 8 .0
A ir flo w
A ir flo w
9 7 .0
9 7 .0
2 1 .0
3 .8
2 4 .0
2 4 .0
Figure 137: Combination Heating & Cooling
C o m b in a tio n h e a tin g a n d c o o lin g
Figure 138: Heating Coil with Face and Bypass
Damper (28.1 sq. ft.)
H e a tin g c o il (4 2 .2 s q .ft.)
o S te a m c o il w ith o u t v a lv e a n d p ip in g
o H o t w a te r c o il w ith o u t v a lv e a n d p ip in g
H e a tin g c o il w ith fa c e a n d b y p a s s d a m p e r (2 8 .1 s q .ft.)
o S te a m c o il w ith o u t v a lv e a n d p ip in g
o H o t w a te r c o il w ith o u t v a lv e a n d p ip in g
C o o
o C
o C
o D
D a m p e r A c tu a to r
o W ith d a m p e r a c tu a to r
o W ith o u t d a m p e r a c tu a to r
lin g c
h ille d
h ille d
X e v a
o il
w a te r w ith o u t v a lv e a n d p ip in g ( 5 1 .9 s q . f t.)
w a te r w ith 3 - w a y m o d u la tin g v a lv e a n d p ip in g ( 5 1 .9 s q . ft .)
p o ra to r (5 4 .7 s q . ft.)
1 0 .0
1 .0
1 .5 0 M P T D r a in
6 .0
C o o lin g C o il
4 2 .0
H e a tin g C o il
9 9 .0
4 2 .0
D o o r p e n e tr a tio n o r v e s t ib u le
r e q u ir e d fo r h e a tin g c o il c o n n e c tio n .
( S e e F ig u r e x x x f o r v e s tib u le d e ta ils )
A ll p ip in g e n te r a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
H e a tin g C o il
1 .5 0 M P T D r a in
F a c e a n d B y p a s s D a m p e r
9 9 .0
6 .0
1 .0
4 2 .0
1 0 .0
A ll p ip in g e n te r a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
4 8 .0
D o o r p e n e tr a tio n o r v e s t ib u le
r e q u ir e d fo r h e a tin g c o il c o n n e c tio n .
( S e e F ig u r e x x x f o r v e s tib u le d e ta ils )
6 .0
1 .0
1 0 .0
4 8 .0
A ir flo w
9 7 .0
A ir flo w
9 7 .0
7 .0
2 1 .0
2 4 .0
2 1 .0
2 4 .0
©2007 McQuay International
58
Position D — Draw-Through Heat/Cool Section — Large Face Area Coil — RAH077C
Figure 139: Cooling Unit Only
C o o
o C
o C
o D
lin g c
h ille d
h ille d
X e v a
o il o
w a te
w a te
p o ra
n ly
r w
r w
to r
Cooling Coil with Face & Bypass Damper - Staggered
C o o lin g c o il w ith fa c e a n d b y p a s s d a m p e r - s ta g g e r e d
o C h ille d w a te r w ith o u t v a lv e a n d p ip in g ( 6 2 .3 s q . ft.)
o C h ille d w a t e r w ith 3 - w a y m o d u la tin g v a lv e a n d p ip in g ( 6 2 .3 s q . ft. )
- s ta g g e re d
ith o u t v a lv e a n d p ip in g ( 7 2 .6 s q . f t.)
ith 3 - w a y m o d u la tin g v a lv e a n d p ip in g ( 7 2 .6 s q . ft .)
(7 6 .6 s q . ft.)
D a m p e r A c tu a to r
o W ith d a m p e r a c tu a to r
o W ith o u t d a m p e r a c tu a to r
4 6 .0
4 6 .0
1 .0
1 .0
1 .5 0 M P T D r a in
1 .5 0 M P T D r a in
6 .0
6 .0
C o o lin g C o il
C o o lin g C o il
4 2 .0
4 2 .0
9 9 .0
9 9 .0
F a c e D a m p e r
2 4 .0
A ll p ip in g e n te r a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
B y p a s s D a m p e r
A ll p ip in g e n te r a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
4 8 .0
4 8 .0
4 8 .0
A ir flo w
A ir flo w
9 7 .0
9 7 .0
1 4 .7
3 .8
1 2 .0
2 4 .0
5 2 .5
7 7 .1
Position E — Draw-Through Heat Only Section
Figure 140: Combination Heating & Cooling
C o m b in a tio n h e a tin g a n d c o o lin g
Figure 141: Heat Only Section
H e a tin g c o il (4 2 .2 s q .ft.)
o S te a m c o il w ith o u t v a lv e a n d p ip in g
o H o t w a te r c o il w ith o u t v a lv e a n d p ip in g
C o o
o C
o C
o D
lin g c
h ille d
h ille d
X e v a
H e a
o H
o H
o S
o S
o il
w a te r w ith o u t v a lv e a n d p ip in g ( 7 2 .6 s q . f t.)
w a te r w ith 3 - w a y m o d u la tin g v a lv e a n d p ip in g ( 7 2 .6 s q . ft .)
p o ra to r (7 6 .6 s q . ft.)
tin
o t
o t
te a
te a
g o
w a
w a
m
m
n ly
te r w
te r w
c o il
c o il
s e c tio n
it h o u t v a lv e a n d p ip in g
it h 3 - w a y m o d u la tin g v
w ith o u t v a lv e a n d p ip in
w ith 3 - w a y m o d u la tin g
(4 2 .2 s q . ft.)
a lv e a n d p ip in g ( 4 2 .2 s q . ft.)
g (4 2 .2 s q . ft.)
v a lv e a n d p ip in g ( 4 2 .2 s q . ft.)
4 6 .0
1 .0
1 .5 0 M P T D r a in
6 .0
H e a tin g C o il
A ll p ip in g e n te r a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
4 2 .0
C o o lin g C o il
9 9 .0
9 9 .0
9 .0
4 2 .0
6 .0
6 .0
1 .0
1 2 .0
A ll p ip in g e n te r a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
4 8 .0
D o o r p e n e
r e q u ir e d fo
c o n n e c tio n
S e e F ig u r e
v e s tib u le d
3 7 .0
1 .0
4 8 .0
O p t io n a l F a c to r y P ip in g
A ir flo w
4 8 .0
9 7 .0
tr a tio n v e s t ib u le
r h e a tin g c o il
.
X X X fo r
e ta ils
A ir flo w
9 7 .0
3 8 .0
1 4 .0
2 4 .0
2 7 .8
7 6 .5
©2007 McQuay International
N o t e : T y p ic a l h o t w a t e r p ip in g s h o w n , s e e IM 4 8 7 fo r ty p ic a l s te a m
p ip in g .
59
Position F — Supply Air Fan Section — Mandatory Selection — RAH077C
Figure 142: Supply Air Fan — DWDI
S u p p ly a ir fa n - D W D I
o 3 3 "
S u p p ly a ir fa n - D W D I
o 3 6 "
o 4 0 "
F a n
o F
o A
o A
ty p e
o rw a rd c u rv e d
ir fo il
ir fo il w ith v a r ia b le in le t v a n e s
F a n
o F
o A
o A
ty p e
o rw a rd c u rv e d
ir fo il
ir fo il w ith v a r ia b le in le t v a n e s
O p t
o W
o W
o W
io n
ith
ith
ith
O p t
o W
o W
o W
io n
ith
ith
ith
s
b e lt g u a r d
lig h t, r e c e p ta c le a n d s w itc h
lig h t, r e c e p ta c le , s w itc h a n d b e lt g u a r d
s
b e lt g u a r d
lig h t, r e c e p ta c le a n d s w itc h
lig h t, r e c e p ta c le , s w itc h a n d b e lt g u a r d
2 4 .7
2 2 .1
4 9 .6
9 9 .0
5 4 .8
2 4 .7
2 4 .0
9 9 .0
2 2 .1
4 8 .0
4 8 .0
4 8 .0
1 3 .9
3 6 " S u p p ly F a n
3 3 " S u p p ly F a n
1 7 .9
A ir flo w
4 6 .4
A ir flo w
5 0 .5
9 7 .0
9 7 .0
Figure 143: Supply Air Fan — SWSI
S u p p ly a ir fa n - S W S I
o 4 4 "
S u p p ly a ir fa n - S W S I
o 4 9 "
F a n ty p e
o A ir fo il w ith o u t v a r ia b le in le t v a n e s
o A ir fo il w ith v a r ia b le in le t v a n e s
F a n ty p e
o A ir fo il w ith o u t v a r ia b le in le t v a n e s
o A ir fo il w ith v a r ia b le in le t v a n e s
D is c h a r g e o p e n in g
o B o tto m d is c h a r g e
D is c h a r g e o p e n in g
o B o tto m d is c h a r g e
O p t
o W
o W
o W
io n
ith
ith
ith
s
o
S id e d is c h a r g e
O p t
o W
o W
o W
b e lt g u a r d
lig h t, r e c e p ta c le a n d s w itc h
lig h t, r e c e p ta c le , s w itc h a n d b e lt g u a r d
B o tto m
D is c h a r g e O p e n in g
s
1 0 .0
o
S id e d is c h a r g e
b e lt g u a r d
lig h t, r e c e p ta c le a n d s w itc h
lig h t, r e c e p ta c le , s w itc h a n d b e lt g u a r d
B o tto m
3 8 .0
D is c h a r g e O p e n in g
4 6 .0
1 0 .0
6 .0
8 1 .0
9 9 .0
P o w e r a n d C o n tro l e n te ra n c e
( S e e F ig u r e x x x )
2 4 .0
io n
ith
ith
ith
6 .0
8 1 .0
9 9 .0
P o w e r a n d C o n tro l e n te ra n c e
( S e e F ig u r e x x x )
4 8 .0
4 2 .0
3 .0
4 8 .0
4 8 .0
4 2 .0
3 .0
A ir flo w
8 5 .0
9 7 .0
A ir flo w
8 5 .0
9 7 .0
A ll p ip in g e n te r a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
O p t io n a l S id e D is c h a r g e
o n O p p o s it e P o w e r S id e
8 .5
8 .5
©2007 McQuay International
60
Position G — Blow-Through Heat Only Section — RAH077C
Figure 144: Heat Only Section
H e a
o H
o H
o S
o S
S e e
tin
o t
o t
te a
te a
n o
g o
w a
w a
m
m
te
n ly
te r w
te r w
c o il
c o il
b e lo
s e c tio n
it h o u t v a lv e a n d p ip in g
it h 3 - w a y m o d u la tin g v
w ith o u t v a lv e a n d p ip in
w ith 3 - w a y m o d u la tin g
w
H e a tin g o n ly s e c tio n
o E le c tr ic h e a t
(4 2 .2 s q . ft.)
a lv e a n d p ip in g ( 4 2 .2 s q . ft.)
g (4 2 .2 s q . ft.)
v a lv e a n d p ip in g ( 4 2 .2 s q . ft.)
A ll p ip in g e n te r a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
9 .0
3 .0 D ia . K .O .
(Q ty = 2 )
3 7 .0
1 .0
6 .0
9 9 .0
P o w e r a n d C o n tr o l W ir in g
( S e e F ig u r e x x x )
9 9 .0
.9 D ia . K .O .
4 8 .0
O p t io n a l F a c to r y P ip in g
( S e e n o te b e lo w )
4 8 .0
A ir flo w
A ir flo w
9 7 .0
9 7 .0
3 3 .0
3 8 .0
N o t e : T y p ic a l h o t w a t e r p ip in g s h o w n , s e e IM 4 8 7 fo r ty p ic a l s te a m
p ip in g .
N o t e : H e a t s e c tio n in p o s itio n G
n o t a v a ila b le o n u n its w ith a S W S I s u p p ly f a n .
Figure 145: Heat Only Section
H e a tin g o n ly s e c tio n
o G a s h e a t w it h c o n t r o ls ( 5 0 0 - 1 4 0 0 M B h o u tp u t )
H e a tin g o n ly s e c tio n
o E le c tr ic h e a t
9 9 .0
A ll p ip in g e n te r a n c e h o le s
s h o u ld fa ll w ith in th is a r e a .
9 9 .0
8 .6
2 8 .0
6 .0
4 .2
4 .0
V e s tib u le r e q u ir e d fo r g a s
h e a t p ip in g a n d b u r n e r
( S e e F ig u r e x x x f o r v e s tib u le d e ta ils )
4 8 .0
4 8 .0
A ir flo w
A ir flo w
9 7 .0
9 7 .0
N o t e : H e a t s e c tio n in p o s itio n G
©2007 McQuay International
n o t a v a ila b le o n u n its w ith a S W S I s u p p ly f a n .
N o t e : H e a t s e c tio n in p o s itio n G
n o t a v a ila b le o n u n its w ith a S W S I s u p p ly f a n .
61
Position I — Blow-Through Heat/Cool Section — RAH077C — Standard Face Area Coils
Figure 146: Cooling Coil Only
C o o
o C
o C
o D
lin g c
h ille d
h ille d
X e v a
o il o
w a te
w a te
p o ra
Cooling Coil with Face & Bypass Damper
C o o lin g c o il w ith fa c e a n d b y p a s s d a m p e r
o C h ille d w a te r w ith o u t v a lv e a n d p ip in g ( 3 6 .3 s q . ft.)
o C h ille d w a t e r w ith 3 - w a y m o d u la tin g v a lv e a n d p ip in g ( 3 6 .3 s q . ft. )
n ly
r w ith o u t v a lv e a n d p ip in g ( 5 1 .9 s q . f t.)
r w ith 3 - w a y m o d u la tin g v a lv e a n d p ip in g ( 5 1 .9 s q . ft .)
to r (5 4 .7 s q . ft.)
D a m p e r A c tu a to r
o W ith d a m p e r a c tu a to r
o W ith o u t d a m p e r a c tu a to r
1 0 .0
1 0 .0
1 .0
1 .5 0 M P T D r a in
1 .0
1 .5 0 M P T D r a in
6 .0
6 .0
F a c e a n d B y p a s s D a m p e r
4 2 .0
4 2 .0
C o o lin g C o il
9 9 .0
9 9 .0
C o o lin g C o il
A ll p ip in g e n te r a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
A ll p ip in g e n te r a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
4 8 .0
4 8 .0
A ir flo w
A ir flo w
9 7 .0
9 7 .0
3 .8
2 4 .0
2 1 .0
2 4 .0
N o t e : H e a t/C o o l s e c tio n in p o s itio n I n o t a v a ila b le o n u n it s w it h a S W S I s u p p ly fa n .
H e a t /C o o l s e c tio n in p o s itio n I r e q u ir e s a b la n k o r h e a t in g s e c tio n in p o s itio n G .
Figure 147: Combination Heating and Cooling
N o t e : H e a t/C o o l s e c tio n in p o s itio n I n o t a v a ila b le o n u n it s w it h a S W S I s u p p ly fa n .
H e a t /C o o l s e c tio n in p o s itio n I r e q u ir e s a b la n k o r h e a t in g s e c tio n in p o s itio n G .
Heating Coil with Face & Bypass Damper (28.1 sq. ft.)
H e a tin g c o il (4 2 .2 s q .ft.)
o S te a m c o il w ith o u t v a lv e a n d p ip in g
o H o t w a te r c o il w ith o u t v a lv e a n d p ip in g
H e a tin g c o il w ith fa c e a n d b y p a s s d a m p e r (2 8 .1 s q .ft.)
o S te a m c o il w ith o u t v a lv e a n d p ip in g
o H o t w a te r c o il w ith o u t v a lv e a n d p ip in g
C o o
o C
o C
o D
D a m p e r A c tu a to r
o W ith d a m p e r a c tu a to r
o W ith o u t d a m p e r a c tu a to r
lin g c
h ille d
h ille d
X e v a
o il
w a te r w ith o u t v a lv e a n d p ip in g ( 5 1 .9 s q . f t.)
w a te r w ith 3 - w a y m o d u la tin g v a lv e a n d p ip in g ( 5 1 .9 s q . ft .)
p o ra to r (5 4 .7 s q . ft.)
S e e n o te s b e lo w
S e e n o te s b e lo w
1 0 .0
1 .0
1 .5 0 M P T D r a in
A ll p ip in g e n te r a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
H e a tin g C o il
1 .5 0 M P T D r a in
6 .0
C o o lin g C o il
4 2 .0
H e a tin g C o il
9 9 .0
F a c e a n d B y p a s s D a m p e rs
9 9 .0
4 2 .0
4 2 .0
D o o r p e n e tr a tio n v e s t ib u le r e q u ir e d
fo r h e a tin g c o il c o n n e c tio n .
S e e F ig u r e X X X f o r v e s t ib u le d e ta ils
6 .0
1 .0
1 0 .0
A ll p ip in g e n te r a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
6 .0
1 .0
D o o r p e n e tr a tio n v e s t ib u le r e q u ir e d
fo r h e a tin g c o il c o n n e c tio n .
S e e F ig u r e X X X f o r v e s t ib u le d e ta ils
1 0 .0
4 8 .0
4 8 .0
A ir flo w
A ir flo w
9 7 .0
9 7 .0
7 .0
2 1 .0
2 4 .0
N o t e : H e a t/C o o l s e c tio n in p o s itio n I n o t a v a ila b le o n u n it s w it h a S W S I s u p p ly fa n .
H e a t /C o o l s e c tio n in p o s itio n I r e q u ir e s a b la n k o r h e a t in g s e c tio n in p o s itio n G .
©2007 McQuay International
2 1 .0
2 4 .0
N o t e : H e a t/C o o l s e c tio n in p o s itio n I n o t a v a ila b le o n u n it s w it h a S W S I s u p p ly fa n .
H e a t /C o o l s e c tio n in p o s itio n I r e q u ir e s a b la n k o r h e a t in g s e c tio n in p o s itio n G .
62
Position I — Blow-Through Heat/Cool Section — RAH077C — Large Face Area Coils
Figure 148: Cooling Coil Only - Staggered
C o o
o C
o C
o D
lin g c
h ille d
h ille d
X e va
o il o
w a te
w a te
p o ra
Cooling Coil with Face & Bypass Damper - Staggered
C o o lin g c o il w ith fa c e a n d b y p a s s d a m p e r - s ta g g e r e d
o C h ille d w a te r w ith o u t v a lv e a n d p ip in g ( 6 2 .3 s q . ft.)
o C h ille d w a t e r w ith 3 - w a y m o d u la tin g v a lv e a n d p ip in g ( 6 2 .3 s q . ft. )
n ly - s ta g g e r e d
r w ith o u t v a lv e a n d p ip in g ( 7 2 .6 s q . f t.)
r w ith 3 - w a y m o d u la tin g v a lv e a n d p ip in g ( 7 2 .6 s q . ft .)
to r (7 6 .6 s q . ft.)
D a m p e r A c tu a to r
o W ith d a m p e r a c tu a to r
o W ith o u t d a m p e r a c tu a to r
3 8 .0
9 .0
1 .5 0 M P T D r a in
9 .0
6 .0
C o o lin g C o il
3 8 .0
1 .5 0 M P T D r a in
4 2 .0
6 .0
C o o lin g C o il
4 2 .0
9 9 .0
9 9 .0
F a c e D a m p e r
A ll p ip in g e n te r a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
2 4 .0
A ll p ip in g e n te r a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
B y p a s s D a m p e r
4 8 .0
4 8 .0
4 8 .0
A ir flo w
A ir flo w
9 7 .0
9 7 .0
1 4 .7
3 .8
1 2 .0
2 4 .0
7 7 .1
5 2 .5
N o t e : H e a t/C o o l s e c tio n in p o s itio n I n o t a v a ila b le o n u n it s w it h a S W S I s u p p ly fa n .
H e a t /C o o l s e c tio n in p o s itio n I r e q u ir e s a b la n k o r h e a t in g s e c tio n in p o s itio n G .
N o t e : H e a t/C o o l s e c tio n in p o s itio n I n o t a v a ila b le o n u n it s w it h a S W S I s u p p ly fa n .
H e a t /C o o l s e c tio n in p o s itio n I r e q u ir e s a b la n k o r h e a t in g s e c tio n in p o s itio n G .
Figure 149: Combination Heating and Cooling
H e a tin g c o il (4 2 .2 s q .ft.)
o S te a m c o il w ith o u t v a lv e a n d p ip in g
o H o t w a te r c o il w ith o u t v a lv e a n d p ip in g
C o o
o C
o C
o D
lin g c
h ille d
h ille d
X e v a
o il
w a te r w ith o u t v a lv e a n d p ip in g ( 7 2 .6 s q . f t.)
w a te r w ith 3 - w a y m o d u la tin g v a lv e a n d p ip in g ( 7 2 .6 s q . ft .)
p o ra to r (7 6 .6 s q . ft.)
3 8 .0
9 .0
1 .5 0 M P T D r a in
6 .0
H e a tin g C o il
4 2 .0
C o o lin g C o il
9 9 .0
4 2 .0
6 .0
D o o
re q u
\c o n
S e e
d e ta
r p e
ir e d
n e c
F ig
ils
1 .0
1 2 .0
n e tr a tio n v e s t ib u le
fo r h e a tin g c o il
tio n .
u r e X X X f o r v e s t ib u le
A ll p ip in g e n te r a n c e h o le s
s h o u ld fa ll w ith in th is a r e a
4 8 .0
4 8 .0
A ir flo w
9 7 .0
1 4 .0
2 4 .0
2 7 .8
7 6 .5
N o t e : H e a t/C o o l s e c tio n in p o s itio n I n o t a v a ila b le o n u n it s w it h a S W S I s u p p ly fa n .
H e a t /C o o l s e c tio n in p o s itio n I r e q u ir e s a b la n k o r h e a t in g s e c tio n in p o s itio n G .
©2007 McQuay International
63
Position J — Final Filter Section — RAH077C
Figure 150: 56 sq. ft. Cartridge — 4 Foot Section
5 6
s q . f t . c a r t r i d g e
9 5 %
e f f e c ie n c y
o
S e e
n o t e s
- 4
f o o t s e c t i o n
64 sq. ft. Cartridge — 6 Foot Section
6 4
s q . f t . c a r t r i d g e
9 5 %
e f f e c ie n c y
o
b e lo w
S e e
n o t e s
- 6 f o o t s e c t i o n
- s t a g g e r e d
b e lo w
9 9 .0
2 4 .0
9 9 .0
2 4 .0
2 4 .0
4 8 .0
A ir flo w
A ir flo w
9 7 .0
9 7 .0
F ilte r q u a n tity & s iz e
4 - 1 2 x 2 4 x 1 2
1 2 - 2 4 x 2 4 x 1 2
2 9 .6
5 4 .8
Figure 151: 80 sq. ft. Cartridge — 8 Foot Section
8 0
s q . f t . c a r t r i d g e
9 5 %
e f f e c ie n c y
o
S e e
n o t e s
Blank Access Section
B
- 8 f o o t s e c t i o n
- s t a g g e r e d
l a n k a c c e s s s e c t i o n
B la n k - 4 f o o t s e c t io n
o
S e e
b e lo w
F ilte r q u a n tity & s iz e
1 6 - 2 4 x 2 4 x 1 2
2 9 .6
n o t e s
b e lo w
9 9 .0
4 8 .0
2 4 .0
9 9 .0
2 4 .0
A ir flo w
2 4 .0
2 4 .0
A ir flo w
9 7 .0
9 7 .0
F ilte r q u a n tity & s iz e
8 - 1 2 x 2 4 x 1 2
1 6 - 2 4 x 2 4 x 1 2
2 9 .6
7 8 .8
Figure 152: Blank Access Section
B
l a n k a c c e s s s e c t i o n
B la n k - 6 - f o o t s e c t io n
o
S e e
n o t e s
b e lo w
9 9 .0
2 4 .0
4 8 .0
A ir flo w
9 7 .0
Notes:
(1) Final Filter section not available on units with a SWSI supply fan.
(2) Final filters are not available on units with a blow-through cooling coil in the Heat/Cool section, position I.
(3) Final filter option requires a discharge plenum in position K.
(4) Final filter option requires a blank or heating section in position G.
©2007 McQuay International
64
Position K — Discharge Plenum — RAH077C
Figure 153: RAH077CS - 4 ft Standard Face Area Coil
D is c h a r g e
o B o tto m d
o F r o n t d is
o S id e d is c
p le n u m (4 -fo o t) fo r s ta n d a r d fa c e a r e a c o il u n its
is c h a r g e ( s e e n o te )
c h a rg e
h a rg e
Figure 155: RAH077CL and 077CY Discharge
Plenum 6 ft for Draw -Through
D is c h a r g e p le n u m (6 -fo o t) fo r D r a w -th r o u g h u n its w ith la r g e fa c e a r e a c o ils o r
w ith o u t c o o lin g c o ils in H e a t/C o o l s e c tio n , P le n u m D , a n d w ith o u t F in a l F ilte r
s e c tio n , P o s itio n J .
o B o tto m d is c h a r g e
3 8 .0
6 .0
9 9 .0
1 0 .0
B o tto
O p e n
O p t io
D is c h
8 1 .0
B o tto m
D is c h a r g e
9 3 .5
F ro n t
D is c h a r g e
m
4 6 .0
D is c h a r g e
in g
n a l F ro n t
a r g e O p e n in g
6 .0
9 9 .0
1 0 .0
B o tto m D is c h a r g e
O p e n in g
8 1 .0
B o tto m
D is c h a r g e
2 .8
P o w e r a n d C o n tro l E n te ra n c e
( S e e F ig u r e x x x )
O p t io n a l P o w e r a n d
C o n tro l E n te ra n c e
( S e e F ig u r e x x x )
4 8 .0
4 2 .0
3 .0
2 4 .0
8 5 .0
S id e
D is c h a r g e
4 8 .0
9 7 .0
4 1 .8 F ro n t
D is c h a r g e
9 7 .0
2 .7
8 .5
O p t io n a l s id e d is c h a r g e
o n o p p o s ite p o w e r s id e
N o t e : D is c h a r g e p le n u m
n o t a v a ila b le o n u n its w ith a S W S I s u p p ly fa n .
Figure 154: RAH077CL and 077CY
D is c h a r g e p le n u m (4 -fo o t) fo r B lo w -th r o u g h u n its w ith la r g e fa c e a r e a c o ils o r
w ith o u t c o o lin g c o ils in H e a t/C o o l s e c tio n , P le n u m I, a n d /o r w ith F in a l F ilte r
s e c tio n , P o s itio n J .
o B o tto m d is c h a r g e
o F r o n t d is c h a r g e
o S id e d is c h a r g e
N o t e : B u r g la r b a r s a n d is o la tio n d a m p e r s n o t a v a ila b le w h e n t h e r e a r e n o
s e c tio n s b e tw e e n th e s u p p ly fa n a n d d is c h a r g e p le n u m f o r u n its w ith
b o tto m d is c h a r g e .
Position L — Blank Compartment Section
Figure 156: Blank Compartment
B
o
l a n k c o m p a r t m e n t
O u t o f a ir s t r e a m
- 6 - f o o t
4 6 .0
6 .0
9 9 .0
1 0 .0
B o
O p
O p
D is
8 1 .0
B o tto m
D is c h a r g e
9 3 .5
F ro n t
D is c h a r g e
tto
e n
t io
c h
m D is c h a r g e
in g
n a l F ro n t
a r g e O p e n in g
9 9 .0
4 8 .0
2 4 .0
2 .8
P o w e r a n d C o n tro l E n te ra n c e
( S e e F ig u r e x x x )
4 8 .0
4 2 .0
3 .0
9 7 .0
8 5 .0
S id e
D is c h a r g e
9 7 .0
4 1 .8 F ro n t
D is c h a r g e
8 .5
N o t e : B la n k C o m p a r t m e n t s e c t io n r e q u ir e s a d is c h a r g e p le n u m
o r s id e d is c h a r g e in p o s itio n K .
w ith b o tto m
2 .7
O p t io n a l s id e d is c h a r g e
o n o p p o s ite p o w e r s id e
©2007 McQuay International
65
Blank Access & Drain Pan Only Section Detail Drawings
Figure 157: Cross Section Detail — RAH077C
Access Door Detail — RAH077C
3 .6
D
U p r ig h t lo c a te d
b e tw e e n s e c tio n s
( b o th s id e s )
E
C e ilin g ( w ith o p tio n a l lin e r )
1 .8
1 .8
3 .0
4 2 .0
A c c e s s d o o r d e ta il
3 .5
C
D o o r
( w ith lin e r )
D o o r O p e n in g
E
D o o r
( w ith lin e r )
G
I
A ir flo w
D
*H
4 2 .0
1 .8
F
B a se
8 .5
B a se
F lo o r
B a s e R a il
U n it F lo o r
* C a b in e t h e ig h t
1 .8 S ta n d in g S e a m
( lo c a te d b e tw e e n e a c h s e c tio n )
2 .2
5 .2
Vestibule Detail Drawings — RAH077C
Figure 158: Heat Coil Piping Vestibule
Gas Heat Coil Piping Vestibule (1599 & 2000 MBh)
G a s h e a t p ip in g v e s tib u le (1 5 0 0 &
H e a t c o il p ip in g v e s tib u le
4 8 .0 0
2 0 0 0 M B h o n ly )
4 8 .0 0
1 6 .0 0
fl
A ir
o w
fl
A ir
o w
2 8 .0 0
8 8 .1 1
7 .1 8
4 9 .7 0
8 .5 7
only)
©2007 McQuay International
66
Roof Curbs — RAH077C
Figure 159: Roof Curb without Blank Compartment
6.8
A
B
6.8
1.5
Dimension (in.)
A
B
RAH077C
62.0
see tables below
Discharge Opening Dimension “B” - DWDI Supply Fan
Model
RA
OPENING
SA
OPENING
81.0
077CS
A
B
Supply Air
Opg. “B” (in.)
Chilled Water
(CW)
36.3
38
51.9
38
54.7
38
62.3
46
72.6
46
Chilled Water
(CW)
077CL
7.5
2.0 TYP.
Cooling Coil
Size (sq. ft.)
Direct (DX)
Expansion
A
B
Cooling Coil
Type*
Direct (DX)
Expansion
72.6
46
None
—
46
077CY
*Coil located in draw-through or blow-through position
4.0 TYP.
Discharge Opening Dimension “B” - SWSI Plenum Supply Fan
(UNIT LENGTH MINUS 6.4 INCHES)
Model
SWSI Wheel Dia
(in.)
Supply Air Opg.
“B” (in.)
44
38
49
46
077C
Figure 160: Roof Curb with Blank Compartment
A
6.8
78.8
B
1.5
6.8
SA
OPENING
RA
OPENING
87.0
1.5
A
81.0
A
B
1.5
7.5
B
2.0 TYP.
4.0 TYP.
UNIT LENGTH MINUS 6.4 INCHES
Figure 161: Curb Cross Section A-A
Curb Cross Section B-B
4 .5
3 .2
2
2
2
1
9
1 6 .0
9 .8
5
1 0
4 .6
7
K e y
1 U
2 C
3 2
4 G
5 D
6 C
7 R
8 C
9 F
:
n it B a s e
u r b G a s k e tin g
x 4 N a ile r S tr ip
a lv a n iz e d C u r b
u c t S u p p o rt
a n t S tr ip ( N o t F u r n is h
o o fin g M a te r ia l ( N o t F
o u n te r fla s h in g ( N o t F
la s h in g ( N o t F u r n is h e
2
9
1 0
3
e d )
u r n is h e d )
u r n is h e d )
d )
6
5
1 4 .4
1
7
8
4
4
©2007 McQuay International
67
Electrical Knockouts—RAH 047C and 077C
Figure 162: Discharge Plenum Power and Control Wiring Entrance Detail
8 .8
7 .6
3 .0 D IA . K .O .
(Q T Y = 3 )
6 .6
3 .4
3 .4
.9 D IA . K .O .
(Q T Y = 4 )
1 5 .3
2 .0
1 2 .9
4 .6
4 .8
N o t e : 0 .9 d ia m e te r a n d 3 .0 d ia m e te r k n o c k o u ts a r e e le c tr ic a l e n te r a n c e lo c a tio n s o n th e u n it o n ly .
Figure 163: Electric Heat Power and Control Entrance Detail
7 .6
3 .0 D IA . K .O .
(Q T Y = 2 )
.9 D IA . K .O .
(Q T Y = 1 )
8 .8
6 .6
1 5 .3
1 7 .7
1 8 .7
N o t e : 0 .9 d ia m e te r a n d 3 .0 d ia m e te r k n o c k o u ts a r e e le c tr ic a l e n te r a n c e lo c a tio n s o n th e u n it o n ly .
©2007 McQuay International
68

Similar documents

Download: Advance notice - Ritchie Bros. Auctioneers

Download: Advance notice - Ritchie Bros. Auctioneers Edmonton, AB | September 7–9, 2016 (Wed–Fri)

More information