ROOF DECK, FLOOR DECK AND ACOUSTIC DECK PANELS
Ideal Roofing manufactures a complete range of coated steel roof, floor and acoustic deck panels using
state-of-the-art roll-forming machinery. These panels are cut to length to your specifications and delivered
to the job sites using Ideal’s own fleet of trucks.
Check out Ideal Roofing’s wide range of roofing
and siding panels on the last two pages of this
catalog or visit www.idealroofing.com.
To talk to a sales representative: 1 800 267-0860
Residential
Commercial
Industrial
Table of Contents
Page
Deck Selection. 2
Roof Deck
- IRD-150 / IRD-151 (Imperial) 3-4
- IRD-150 / IRD-151 (Metric)... 5-6
- IRD-300 / IRD-301 (Imperial) 7-8
- IRD-300 / IRD-301 (Metric)... 9-10
Composite Floor Deck
- ICD-150 / ICD-151 (Imperial) 11-12
- ICD-150 / ICD-151 (Metric)... 13-14
- ICD-150 / ICD-151, INVERTED (Imperial).. 15-16
- ICD-150 / ICD-151, INVERTED (Metric). 17-18
- ICD-300 / ICD-301 (Imperial) 19-20
- ICD-300 / ICD-301 (Metric)... 21-22
- ICD-300 / ICD-301, INVERTED (Imperial).. 23-24
- ICD-300 / ICD-301, INVERTED (Metric). 25-26
Acoustic Deck & Metal Closures
- IRD-150 / IRD-151.. 27
- IRD-300 / IRD-301.. 28
Profile Selection29-30
SECTION PROPERTIES (Per foot of width)
IMPERIAL
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
7.5
8.0
8.5
9.0
9.5
10.0
10.5
11.0
Notes:
Coated Steel
Thickness
(G90)
(in.)
Coated
Weight
(psf)
0.030
0.036
0.048
0.060
0.0315
0.0375
0.0495
0.0615
1.61
1.93
2.56
3.20
Sec. Modulus
Midspan Support
3
3
(in. )
(in. )
0.190
0.231
0.314
0.394
0.195
0.242
0.319
0.394
Deflection
Moment of
Inertia
4
BASE STEEL THICKNESS (inches)
0.030 0.036 0.048 0.060
278
339
460
578
421
529
705
877
204
249
338
425
265
333
444
552
157
191
259
325
178
223
297
370
124
151
204
257
125
157
209
260
100
122
166
208
91
114
152
189
83
101
137
172
68
86
114
142
70
85
115
144
53
66
88
110
59
72
98
123
41
52
69
86
51
62
84
106
33
42
55
69
45
54
74
92
27
34
45
56
39
48
65
81
22
28
37
46
35
42
57
72
19
23
31
39
31
38
51
64
16
20
26
32
28
34
46
58
13
17
22
28
25
30
41
52
11
14
19
24
23
28
38
47
10
12
16
20
21
25
34
43
9
11
14
18
1
2
3
4
Based on ASTM A 653 Grade 33 structural steel.
Values in row "S" are based on strength.
Values in row "D" are based on deflection of 1/240th span.
Web crippling not included in strength calculations. See example.
Pe2
End
End
Pi1
Pi2
Interior Interior
(in. )
(lb)
(lb)
(lb)
(lb)
174
258
477
765
43.5
64.5
119
191
305
456
853
1377
51.9
77.6
145
234
BASE STEEL THICKNESS (inches)
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
Specified Web Crippling Data
Pe1
0.174
0.218
0.291
0.362
MAXIMUM UNIFORMLY DISTRIBUTED SPECIFIED LOADS (PSF)
1-SPAN
2-SPAN
SPAN
LENGTH
(ft)
3.0
Base Steel
Thickness
(in.)
0.030 0.036 0.048 0.060
285
355
468
578
1010 1269 1691 2105
210
261
344
425
636
799
1065 1326
161
200
263
325
426
536
713
888
127
158
208
257
299
376
501
624
103
128
168
208
218
274
365
455
85
106
139
172
164
206
274
342
71
89
117
145
126
159
211
263
61
76
100
123
99
125
166
207
52
65
86
106
80
100
133
166
46
57
75
93
65
81
108
135
40
50
66
81
53
67
89
111
36
44
58
72
44
56
74
93
32
39
52
64
37
47
63
78
28
35
47
58
32
40
53
66
26
32
42
52
27
34
46
57
23
29
38
47
24
30
39
49
21
26
35
43
20
26
34
43
Limit States Design principles were used in accordance with CSA Standard S136-01
3-SPAN
BASE STEEL THICKNESS (inches)
0.030 0.036 0.048 0.060
357
444
585
723
796 1000 1332 1658
262
326
430
531
501
630
839 1044
201
249
329
407
336
422
562
699
159
197
260
321
236
296
395
491
128
160
211
260
172
216
288
358
106
132
174
215
129
162
216
269
89
111
146
181
99
125
166
207
76
94
125
154
78
98
131
163
66
81
107
133
63
79
105
130
57
71
94
116
51
64
85
106
50
62
82
102
42
53
70
87
44
55
73
90
35
44
59
73
40
49
65
80
29
37
49
61
36
44
58
72
25
31
42
52
32
40
53
65
21
27
36
45
29
36
48
59
19
23
31
39
27
33
43
54
16
20
27
34
GENERAL INFORMATION
General
Presented in these load tables are maximum uniformly
distributed specified loads.
Limit States Design (LSD)
Strength - Limit States Design principles were used in
the development of the load tables in accordance with
CSA-S136-01, North American Specification for the
Design of Cold Formed Steel Structural Members and
the National Building Code of Canada,. The factored
resistance under consideration, φR, must be equal to or
greater than the effect of the factored loads, i.e.,
φ R ≥ Effect of Factored Loads.
Hence, a short calculation must be carried out to
compute the specified live load. See example.
Serviceability – Maximum specified deflection loads
given in the tables must be compared with their
respective specified live loads.
Steel
Specification - Conforms to ASTM A653M grade
230; Yield strength 230 MPa (33 ksi) and tensile
strength of 310 MPa (45 ksi).
Finishes – ZF 075 (A25) or Z275 (G90). For heavier
galvanizing, refer to ASTM A653-A653M.
Design Considerations
Strength - The maximum uniformly distributed
specified load obtained from the load table must be
equal to or greater than (Specified live load + 0.833
times the specified dead load).
Where 0.833 = 1.25/1.5.
Conservative Strength Approach - The maximum
uniformly distributed specified load obtained from the
load table must be equal to or greater than (Specified
live load + specified dead load).
EXAMPLE
1 1/2” DECK (IMPERIAL)
Given:
Triple span continuous, L = 8 ft each span
Deck thickness, t = 0.030 in
L/180 deflection limit (data in tables are based on
L/240)
Bearing length, n = 2 in.
Specified loads
1) Dead loads (DL)
a) deck
1.6 psf
b) superimposed
8.2 psf
DL = 9.8 psf
2) Live load (LL)
LL = 40 psf
Solution:
Strength
1) Specified loads
[LL + 0.833 DL]
[40 + 0.833 (9.8)] = 48.2 psf
2) Maximum specified load (from Table under “S”)
is 50 psf
Since 50 > 48.2 ∴ ΟΚ
3) Check end web crippling (n = 2 in.)
a) Specified end reaction
0.400(48.2)8.0 = 154 lb/ft
b) Maximum specified end reaction
(from Section Property Table)
Pe = Pe1 + Pe2 n / t
Pe = 174 + 43.5 2 / 0.030 = 529 lb/ft
Since 529 > 154 ∴ ΟΚ
4) Check interior web crippling (n = 2 in.)
a) Specified interior reaction
1.10(48.2)8.0 = 424 lb/ft
b) Maximum specified interior reaction
(from Section Property Table)
Pi = Pi1 + Pi2 n / t
Pi = 305 + 51.9 2 / 0.030 = 729 lb/ft
Since 729 > 424 ∴ ΟΚ
Web Crippling Check – If n/t > 210, use n/t = 210.
Serviceability (Deflection) – The effective moment of
inertia for deflection determination has been calculated
at an assumed specified live load stress of 0.6Fy.
Deflection
From Table under “D” (L/240) = 42 psf
For L/180, multiply 42 by 240/180 = 56 psf.
Since 56 is > 40 ∴ ΟΚ
SECTION PROPERTIES (Per meter of width)
METRIC
1.2
1.4
1.6
1.8
2.0
2.2
2.4
2.6
2.8
3.0
3.2
3.4
3.6
3.8
4.0
Notes:
0.762
0.914
1.219
1.524
0.802
0.954
1.259
1.564
Coated
Mass
2
(kg/m )
7.86
9.42
12.5
15.6
Sec. Modulus
Midspan Support
3
3
3
3
(10 mm ) (10 mm )
10.2
12.4
16.9
21.2
10.4
13.0
17.2
21.2
Specified Web Crippling Data
Deflection
Moment of
Inertia
6
4
BASE STEEL THICKNESS (mm)
0.762 0.914 1.219 1.524
11.3
13.7 18.6 23.4
15.4
19.4 25.8 32.1
7.82
9.52 12.9 16.3
8.91
11.2 14.9 18.6
5.74
6.99 9.49 11.9
5.61
7.05 9.40 11.7
4.40
5.35 7.27 9.14
3.76
4.72 6.30 7.84
3.47
4.23 5.74 7.22
2.64
3.32 4.42 5.51
2.81
3.43 4.65 5.85
1.92
2.42 3.22 4.01
2.33
2.83 3.84 4.83
1.45
1.82 2.42 3.02
1.95
2.38 3.23 4.06
1.11
1.40 1.87 2.32
1.67
2.03 2.75 3.46
0.88
1.10 1.47 1.83
1.44
1.75 2.37 2.98
0.70
0.88 1.18 1.46
1.25
1.52 2.07 2.60
0.57
0.72 0.96 1.19
1.10
1.34 1.82 2.29
0.47
0.59 0.79 0.98
0.97
1.19 1.61 2.02
0.39
0.49 0.66 0.82
0.87
1.06 1.44 1.81
0.33
0.41 0.55 0.69
0.78
0.95 1.29 1.62
0.28
0.35 0.47 0.59
0.70
0.86 1.16 1.46
0.24
0.30 0.40 0.50
1
2
3
4
Based on ASTM A 653 Grade 230 structural steel.
Values in row "S" are based on strength.
Values in row "D" are based on deflection of 1/240th span.
Web crippling not included in strength calculations. See example.
Pe2
End
Pi1
Pi2
Interior Interior
(kN)
(kN)
(kN)
(kN)
0.237
0.298
0.397
0.494
2.57
3.81
7.04
11.3
0.642
0.952
1.76
2.82
4.50
6.73
12.6
20.3
0.766
1.14
2.14
3.45
BASE STEEL THICKNESS (mm)
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
Pe1
End
(10 mm )
MAXIMUM UNIFORMLY DISTRIBUTED SPECIFIED LOADS (kPa)
1-SPAN
2-SPAN
SPAN
LENGTH
(m)
1.0
Base Steel
Thickness
(mm)
Coated Steel
Thickness
(Z275)
(mm)
0.762 0.914 1.219 1.524
11.5 14.4
18.9 23.4
36.9 46.4
61.9 77.1
8.01 9.97
13.2 16.3
21.4 26.9
35.8 44.6
5.88 7.33
9.66 11.9
13.5 16.9
22.6 28.1
4.50 5.61
7.40 9.14
9.02 11.3
15.1 18.8
3.56 4.43
5.84 7.22
6.33 7.96 10.62 13.2
2.88 3.59
4.73 5.85
4.62 5.80
7.74 9.63
2.38 2.97
3.91 4.83
3.47 4.36
5.81 7.24
2.00 2.49
3.29 4.06
2.67 3.36
4.48 5.57
1.71 2.12
2.80 3.46
2.10 2.64
3.52 4.38
1.47 1.83
2.41 2.98
1.68 2.12
2.82 3.51
1.28 1.60
2.10 2.60
1.37 1.72
2.29 2.85
1.13 1.40
1.85 2.29
1.13 1.42
1.89 2.35
1.00 1.24
1.64 2.02
0.94 1.18
1.58 1.96
0.89 1.11
1.46 1.81
0.79 1.00
1.33 1.65
0.80 0.99
1.31 1.62
0.67 0.85
1.13 1.40
0.72 0.90
1.18 1.46
0.58 0.73
0.97 1.20
Limit States Design principles were used in accordance with CSA Standard S136-01
3-SPAN
BASE STEEL THICKNESS (mm)
0.762 0.914 1.219 1.524
14.4 18.0 23.7
29.3
29.1 36.6 48.8
60.7
10.0 12.5 16.4
20.3
16.8 21.2 28.2
35.1
7.35 9.16 12.1
14.9
10.6 13.3 17.8
22.1
5.63 7.01 9.24
11.4
7.10 8.93 11.9
14.8
4.45 5.54 7.30
9.03
4.99 6.27 8.36
10.4
3.60 4.49 5.92
7.31
3.64 4.57 6.09
7.59
2.98 3.71 4.89
6.04
2.73 3.43 4.58
5.70
2.50 3.12 4.11
5.08
2.10 2.64 3.53
4.39
2.13 2.66 3.50
4.33
1.66 2.08 2.77
3.45
1.84 2.29 3.02
3.73
1.33 1.67 2.22
2.76
1.60 1.99 2.63
3.25
1.08 1.35 1.81
2.25
1.41 1.75 2.31
2.86
0.89 1.12 1.49
1.85
1.25 1.55 2.05
2.53
0.74 0.93 1.24
1.54
1.11 1.38 1.83
2.26
0.62 0.78 1.04
1.30
1.00 1.24 1.64
2.03
0.53 0.67 0.89
1.11
0.90 1.12 1.48
1.83
0.45 0.57 0.76
0.95
GENERAL INFORMATION
General
Presented in these load tables are maximum uniformly
distributed specified loads.
Limit States Design (LSD)
Strength - Limit States Design principles were used in
the development of the load tables in accordance with
CSA-S136-01, North American Specification for the
Design of Cold Formed Steel Structural Members and
the National Building Code of Canada,. The factored
resistance under consideration, φR, must be equal to or
greater than the effect of the factored loads, i.e.,
φ R ≥ Effect of Factored Loads.
Hence, a short calculation must be carried out to
compute the specified live load. See example.
Serviceability – Maximum specified deflection loads
given in the tables must be compared with their
respective specified live loads.
Steel
Specification - Conforms to ASTM A653M grade
230; Yield strength 230 MPa (33 ksi) and tensile
strength of 310 MPa (45 ksi).
Finishes – ZF 075 (A25) or Z275 (G90). For heavier
galvanizing, refer to ASTM A653-A653M.
Design Considerations
Strength - The maximum uniformly distributed
specified load obtained from the load table must be
equal to or greater than (Specified live load + 0.833
times the specified dead load).
Where 0.833 = 1.25/1.5.
Conservative Strength Approach - The maximum
uniformly distributed specified load obtained from the
load table must be equal to or greater than (Specified
live load + specified dead load).
EXAMPLE
38 mm (1 1/2”) DECK (METRIC)
Given:
Triple span continuous, L = 2.4 m each span
Deck thickness, t = 0.762 mm
L/180 deflection limit (data in tables are based on
L/240)
Bearing length, n = 50 mm
Specified loads
1) Dead loads (DL)
a) deck
0.1 kPa
b) superimposed
0.4 kPa
DL = 0.5 kPa
2) Live load (LL)
LL = 2.0 kPa
Solution:
Strength
1) Specified loads
[LL + 0.833 DL]
[2.0 + 0.833 (0.5)] = 2.42 kPa
2) Maximum specified load (from Table under “S”)
is 2.50 kPa
Since 2.50 > 2.42 ∴ ΟΚ
3) Check end web crippling (n = 50 mm)
a) Specified end reaction
0.400(2.42)2.4 = 2.32 kN/m
b) Maximum specified end reaction
(from Section Property Table)
Pe = Pe1 + Pe2 n / t
Pe = 2.57 + 0.642 50 / 0.762 = 7.77 kN/m
Since 7.77 > 2.32 ∴ ΟΚ
4) Check interior web crippling (n = 50 mm)
a) Specified interior reaction
1.10(2.42)2.4 = 6.39 kN/m
b) Maximum specified interior reaction
(from Section Property Table)
Pi = Pi1 + Pi2 n / t
Web Crippling Check – If n/t > 210, use n/t = 210.
Serviceability (Deflection) – The effective moment of
inertia for deflection determination has been calculated
at an assumed specified live load stress of 0.6Fy.
Pi = 4.50 + 0.766 50 / 0.762 = 10.7 kN/m
Since 10.7 > 6.39 ∴ ΟΚ
Deflection
From Table under “D” (L/240) = 2.10 kPa
For L/180, multiply 2.10 by 240/180 = 2.8 kPa
Since 2.8 is > 2.0 ∴ ΟΚ
SECTION PROPERTIES (Per foot of width)
IMPERIAL
6.5
7.0
7.5
8.0
8.5
9.0
9.5
10.0
10.5
11.0
11.5
12.0
12.5
13.0
13.5
14.0
Notes:
Coated Steel
Thickness
(G90)
(in.)
Coated
Weight
(psf)
0.030
0.036
0.048
0.060
0.0315
0.0375
0.0495
0.0615
2.16
2.58
3.42
4.26
Sec. Modulus
Midspan Support
3
3
(in. )
(in. )
0.436
0.559
0.769
0.981
0.447
0.564
0.799
0.996
Deflection
Moment of
Inertia
4
BASE STEEL THICKNESS (inches)
0.030 0.036 0.048 0.060
160
205
282
360
234
293
408
515
136
175
240
306
184
230
321
405
117
151
207
264
147
184
257
324
102
131
180
230
120
150
209
264
90
115
159
202
99
124
172
217
80
102
140
179
82
103
144
181
71
91
125
160
69
87
121
153
64
82
112
143
59
74
103
130
58
74
101
129
51
63
88
111
52
67
92
117
44
55
76
96
48
61
84
107
38
48
66
84
43
56
77
98
33
42
58
73
40
51
70
90
29
37
51
64
37
47
65
83
26
32
45
57
34
44
60
77
23
29
40
51
32
40
56
71
21
26
36
45
29
38
52
66
18
23
32
41
1
2
3
4
Based on ASTM A 653 Grade 33 structural steel.
Values in row "S" are based on strength.
Values in row "D" are based on deflection of 1/240th span.
Web crippling not included in strength calculations. See example.
Pe2
End
End
Pi1
Pi2
Interior Interior
(in. )
(lb)
(lb)
(lb)
(lb)
144
216
404
654
36.1
54.0
101
163
273
409
766
1238
46.5
69.5
130
210
BASE STEEL THICKNESS (inches)
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
Specified Web Crippling Data
Pe1
0.773
0.967
1.35
1.70
MAXIMUM UNIFORMLY DISTRIBUTED SPECIFIED LOADS (PSF)
1-SPAN
2-SPAN
SPAN
LENGTH
(ft)
6.0
Base Steel
Thickness
(in.)
0.030 0.036 0.048 0.060
164
207
293
365
562
703
980 1236
140
176
249
311
442
553
771
972
120
152
215
268
354
443
617
778
105
132
187
234
288
360
502
633
92
116
165
206
237
297
414
521
82
103
146
182
198
247
345
435
73
92
130
162
167
208
290
366
65
82
117
146
142
177
247
311
59
74
105
132
121
152
212
267
54
68
96
119
105
131
183
231
49
62
87
109
91
114
159
201
45
56
80
99
80
100
139
175
41
52
73
91
70
88
123
154
38
48
67
84
62
78
108
137
35
44
62
78
55
69
96
121
32
41
58
72
49
62
86
108
30
38
54
67
44
55
77
97
Limit States Design principles were used in accordance with CSA Standard S136-07
3-SPAN
BASE STEEL THICKNESS (inches)
0.030 0.036 0.048 0.060
205
258
366
457
443
554
772
973
175
220
312
389
348
435
607
765
151
190
269
336
279
349
486
613
131
165
234
292
227
283
395
498
115
145
206
257
187
234
326
411
102
129
182
228
156
195
271
342
91
115
163
203
131
164
229
288
82
103
146
182
112
139
194
245
74
93
132
164
96
120
167
210
67
84
120
149
83
103
144
182
61
77
109
136
72
90
125
158
56
70
100
124
63
79
110
138
51
65
91
114
55
69
96
122
47
60
84
105
49
61
85
108
44
55
78
97
44
54
76
96
40
51
72
90
39
49
68
85
38
47
67
84
35
44
61
77
GENERAL INFORMATION
General
Presented in these load tables are maximum uniformly
distributed specified loads.
Limit States Design (LSD)
Strength - Limit States Design principles were used in
the development of the load tables in accordance with
CSA-S136-07, North American Specification for the
Design of Cold Formed Steel Structural Members and
the National Building Code of Canada,. The factored
resistance under consideration, φR, must be equal to or
greater than the effect of the factored loads, i.e.,
φ R ≥ Effect of Factored Loads.
Hence, a short calculation must be carried out to
compute the specified live load. See example.
Serviceability – Maximum specified deflection loads
given in the tables must be compared with their
respective specified live loads.
Steel
Specification - Conforms to ASTM A653M grade
230; Yield strength 230 MPa (33 ksi) and tensile
strength of 310 MPa (45 ksi).
Finishes – ZF 075 (A25) or Z275 (G90). For heavier
galvanizing, refer to ASTM A653-A653M.
Design Considerations
Strength - The maximum uniformly distributed
specified load obtained from the load table must be
equal to or greater than (Specified live load + 0.833
times the specified dead load).
Where 0.833 = 1.25/1.5.
Conservative Strength Approach - The maximum
uniformly distributed specified load obtained from the
load table must be equal to or greater than (Specified
live load + specified dead load).
EXAMPLE
3” ROOF DECK (IMPERIAL)
Given:
Two-span continuous, L = 12 ft each span
Deck thickness, t = 0.036 in
L/180 deflection limit (data in tables are based on
L/240)
Bearing length, n = 3 in. (n/t = 83.3)
Specified loads
1) Dead loads (DL)
a) deck
2.6 psf
b) superimposed
8.2 psf
DL = 10.8 psf
2) Live load (LL)
LL = 40 psf
Solution:
Strength
1) Specified loads
[LL + 0.833 DL]
[40 + 0.833 (10.8)] = 49.0 psf
2) Maximum specified load (from Table under “S”)
is 52 psf
Since 52 > 49.0 ∴ ΟΚ
3) Check end web crippling (n = 3 in.)
a) Specified end reaction
0.375(49.0)12 = 221 lb/ft
b) Maximum specified end reaction
(from Section Property Table)
Pe = Pe1 + Pe2 n / t
Pe = 216 + 54.0 3 / 0.036 = 709 lb/ft
Since 709 > 221 ∴ ΟΚ
4) Check interior web crippling (n = 3 in.)
a) Specified interior reaction
1.25(49.0)12 = 735 lb/ft
b) Maximum specified interior reaction
(from Section Property Table)
Pi = Pi1 + Pi2 n / t
Pi = 409 + 69.5 3 / 0.036 = 1043 lb/ft
Since 1043 > 735 ∴ ΟΚ
Web Crippling Check – If n/t > 210, use n/t = 210.
Serviceability (Deflection) – The effective moment of
inertia for deflection determination has been calculated
at an assumed specified live load stress of 0.6Fy.
Deflection
From Table under “D” (L/240) = 88 psf
For L/180, multiply 88 by 240/180 = 117 psf.
Since 117 is > 40 ∴ ΟΚ
SECTION PROPERTIES (Per meter of width)
METRIC
2.2
2.4
2.6
2.8
3.0
3.2
3.4
3.6
3.8
4.0
4.2
4.4
4.6
4.8
5.0
Notes:
0.762
0.914
1.219
1.524
0.802
0.954
1.26
1.56
Coated
Mass
2
(kg/m )
10.5
12.6
16.7
20.8
Sec. Modulus
Midspan Support
3
3
3
3
(10 mm ) (10 mm )
23.4
30.0
41.3
52.7
24.0
30.3
42.9
53.6
Specified Web Crippling Data
Deflection
Moment of
Inertia
6
4
BASE STEEL THICKNESS (mm)
0.762
6.45
8.56
5.33
6.43
4.48
4.95
3.82
3.90
3.29
3.12
2.87
2.54
2.52
2.09
2.23
1.74
1.99
1.47
1.79
1.25
1.61
1.07
1.46
0.920
1.33
0.800
1.22
0.700
1.12
0.620
1.03
0.550
0.914 1.219 1.524
8.27
11.4
14.6
10.7
14.9
18.9
6.84
9.42
12.0
8.05
11.2
14.2
5.75
7.92
10.1
6.20
8.65
10.9
4.90
6.75
8.61
4.87
6.80
8.58
4.22
5.82
7.42
3.90
5.45
6.87
3.68
5.07
6.47
3.17
4.43
5.58
3.23
4.45
5.68
2.61
3.65
4.60
2.86
3.94
5.03
2.18
3.04
3.84
2.55
3.52
4.49
1.84
2.56
3.23
2.29
3.16
4.03
1.56
2.18
2.75
2.07
2.85
3.64
1.34
1.87
2.36
1.88
2.58
3.30
1.16
1.61
2.04
1.71
2.36
3.01
1.01
1.40
1.77
1.56
2.15
2.75
0.880 1.23
1.55
1.44
1.98
2.53
0.770 1.08
1.36
1.32
1.82
2.33
0.690 0.960 1.21
1
2
3
4
Based on ASTM A 653 Grade 230 structural steel.
Values in row "S" are based on strength.
Values in row "D" are based on deflection of 1/240th span.
Web crippling not included in strength calculations. See example.
Pe2
End
End
Pi1
Pi2
Interior Interior
(kN)
(kN)
(kN)
(kN)
1.05
1.32
1.84
2.32
2.13
3.18
5.96
9.64
0.532
0.796
1.49
2.41
4.03
6.04
11.3
18.3
0.686
1.03
1.92
3.10
BASE STEEL THICKNESS (mm)
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
S
D
Pe1
(10 mm )
MAXIMUM UNIFORMLY DISTRIBUTED SPECIFIED LOADS (kPa)
1-SPAN
2-SPAN
SPAN
LENGTH
(m)
2.0
Base Steel
Thickness
(mm)
Coated Steel
Thickness
(Z275)
(mm)
0.762 0.914 1.219 1.524
6.62
8.35
11.9
14.8
20.6
25.7
35.9
45.2
5.47
6.90
9.79
12.2
15.4
19.3
26.9
34.0
4.60
5.80
8.23
10.3
11.9
14.9
20.8
26.2
3.92
4.94
7.01
8.75
9.35
11.7
16.3
20.6
3.38
4.26
6.05
7.54
7.49
9.37
13.1
16.5
2.94
3.71
5.27
6.57
6.09
7.62
10.6
13.4
2.59
3.26
4.63
5.78
5.02
6.28
8.76
11.0
2.29
2.89
4.10
5.12
4.18
5.23
7.30
9.21
2.04
2.58
3.66
4.56
3.52
4.41
6.15
7.76
1.83
2.31
3.28
4.10
3.00
3.75
5.23
6.59
1.66
2.09
2.96
3.70
2.57
3.21
4.48
5.65
1.50
1.89
2.69
3.35
2.22
2.78
3.87
4.88
1.37
1.73
2.45
3.05
1.93
2.41
3.37
4.25
1.25
1.58
2.24
2.80
1.69
2.11
2.95
3.72
1.15
1.45
2.06
2.57
1.49
1.86
2.59
3.27
1.06
1.34
1.90
2.37
1.31
1.65
2.30
2.89
Limit States Design principles were used in accordance with CSA Standard S136-07
3-SPAN
BASE STEEL THICKNESS (mm)
0.762 0.914 1.219 1.524
8.28
10.4
14.8
18.5
16.2
20.2
28.2
35.6
6.84
8.63
12.2
15.3
12.2
15.2
21.2
26.8
5.75
7.25
10.3
12.8
9.36
11.7
16.3
20.6
4.90
6.18
8.76
10.9
7.36
9.21
12.9
16.2
4.22
5.33
7.56
9.43
5.90
7.38
10.3
13.0
3.68
4.64
6.58
8.21
4.79
6.00
8.37
10.6
3.23
4.08
5.79
7.22
3.95
4.94
6.90
8.70
2.86
3.61
5.13
6.40
3.29
4.12
5.75
7.25
2.56
3.22
4.57
5.70
2.77
3.47
4.84
6.11
2.29
2.89
4.10
5.12
2.36
2.95
4.12
5.19
2.07
2.61
3.70
4.62
2.02
2.53
3.53
4.45
1.88
2.37
3.36
4.19
1.75
2.19
3.05
3.85
1.71
2.16
3.06
3.82
1.52
1.90
2.65
3.35
1.57
1.97
2.80
3.49
1.33
1.66
2.32
2.93
1.44
1.81
2.57
3.21
1.17
1.46
2.04
2.58
1.32
1.67
2.37
2.96
1.04
1.30
1.81
2.28
GENERAL INFORMATION
General
Presented in these load tables are maximum uniformly
distributed specified loads.
Limit States Design (LSD)
Strength - Limit States Design principles were used in
the development of the load tables in accordance with
CSA-S136-07, North American Specification for the
Design of Cold Formed Steel Structural Members and
the National Building Code of Canada,. The factored
resistance under consideration, φR, must be equal to or
greater than the effect of the factored loads, i.e.,
φ R ≥ Effect of Factored Loads.
Hence, a short calculation must be carried out to
compute the specified live load. See example.
Serviceability – Maximum specified deflection loads
given in the tables must be compared with their
respective specified live loads.
Steel
Specification - Conforms to ASTM A653M grade
230; Yield strength 230 MPa (33 ksi) and tensile
strength of 310 MPa (45 ksi).
Finishes – ZF 075 (A25) or Z275 (G90). For heavier
galvanizing, refer to ASTM A653-A653M.
Design Considerations
Strength - The maximum uniformly distributed
specified load obtained from the load table must be
equal to or greater than (Specified live load + 0.833
times the specified dead load).
Where 0.833 = 1.25/1.5.
Conservative Strength Approach - The maximum
uniformly distributed specified load obtained from the
load table must be equal to or greater than (Specified
live load + specified dead load).
EXAMPLE
76 mm (3”) DECK (METRIC)
Given:
Triple span continuous, L = 3.8 m each span
Deck thickness, t = 0.914 mm
L/180 deflection limit (data in tables are based on
L/240)
Bearing length, n = 60 mm (n/t = 65.6)
Specified loads
1) Dead loads (DL)
a) deck
0.15 kPa
b) superimposed
0.85 kPa
1.0 kPa
DL =
2) Live load (LL)
2.0 kPa
LL =
Solution:
Strength
1) Specified loads
[LL + 0.833 DL]
[2.0 + 0.833 (1.0)] = 2.83 kPa
2) Maximum specified load (from Table under “S”)
is 2.89 kPa
Since 2.89 > 2.83 ∴ ΟΚ
3) Check end web crippling (n = 60 mm)
a) Specified end reaction
0.400(2.83)3.8 = 4.30 kN/m
b) Maximum specified end reaction
(from Section Property Table)
Pe = Pe1 + Pe2 n / t
Pe = 3.18 + 0.796 60 / 0.914 = 9.63 kN/m
Since 9.63 > 4.30 ∴ ΟΚ
4) Check interior web crippling (n = 60 mm)
a) Specified interior reaction
1.10(2.83)3.8 = 11.8 kN/m
b) Maximum specified interior reaction
(from Section Property Table)
Pi = Pi1 + Pi2 n / t
Web Crippling Check – If n/t > 210, use n/t = 210.
Serviceability (Deflection) – The effective moment of
inertia for deflection determination has been calculated
at an assumed specified live load stress of 0.6Fy.
Pi = 6.04 + 1.03 60 / 0.914 = 14.4 kN/m
Since 14.4 > 11.8 ∴ ΟΚ
Deflection
From Table under “D” (L/240) = 2.95 kPa
For L/180, multiply 2.95 by 240/180 = 3.93 kPa
Since 3.93 is > 2.0 ∴ ΟΚ
COMPOSITE SLAB SECTION PROPERTIES
(per foot of width)
STEEL PROFILE SECTION PROPERTIES
(per foot of width)
Base Steel
Thickness
(in.)
0.030
0.036
0.048
Area of
Steel
Section Modulus
Midspan
Support
Weight
G90
(psf)
1.69
2.02
2.67
(in. 2)
0.481
0.577
0.769
(in. 3)
0.189
0.230
0.313
Deflection
Inertia
Slab Depth, D (in.)
4.0
4.5
5.0
5.5
6.0
(in. 4)
0.167
0.208
0.288
Slab weight (psf)
41.0
47.3
53.5
59.8
66.0
Concrete Volume (yd3/100ft2)
0.95
1.10
1.26
1.41
1.56
(in. 3)
0.193
0.242
0.319
MAXIMUM SPECIFIED UNIFORMLY DISTRIBUTED LOADS (psf)
Slab Depth, D
(in.)
Base Steel
Thickness
(in.)
0.030
0.036
0.048
Slab
Span
(ft)
5'- 0"
5'- 6"
6'- 0"
6'- 6"
7'- 0"
7'- 6"
8'- 0"
8'- 6"
9'- 0"
9'- 6"
10'- 0"
5'- 0"
5'- 6"
6'- 0"
6'- 6"
7'- 0"
7'- 6"
8'- 0"
8'- 6"
9'- 0"
9'- 6"
10'- 0"
5'- 0"
5'- 6"
6'- 0"
6'- 6"
7'- 0"
7'- 6"
8'- 0"
8'- 6"
9'- 0"
9'- 6"
10'- 0"
4.0
4.5
Deck Span
1
500
423
364
317
279
248
223
202
178
156
138
546
467
406
358
318
286
259
236
212
187
165
600
522
461
411
371
337
309
285
264
241
210
2
500
423
364
317
279
248
223
202
178
156
138
546
467
406
358
318
286
259
236
212
187
165
600
522
461
411
371
337
309
285
264
241
210
Deck Span
3
500
423
364
317
279
248
223
202
178
156
138
546
467
406
358
318
286
259
236
212
187
165
600
522
461
411
371
337
309
285
264
241
210
Note: Shoring required at midspan in shaded areas.
1
581
491
422
368
324
289
259
234
212
186
164
634
543
472
415
370
332
301
274
252
224
198
697
607
536
478
431
392
359
331
306
285
259
2
581
491
422
368
324
289
259
234
212
186
164
634
543
472
415
370
332
301
274
252
224
198
697
607
536
478
431
392
359
331
306
285
259
5.5
5.0
Deck Span
3
581
491
422
368
324
289
259
234
212
186
164
634
543
472
415
370
332
301
274
252
224
198
697
607
536
478
431
392
359
331
306
285
259
1
662
560
481
419
369
329
295
267
243
216
191
722
618
537
473
421
379
343
313
287
261
231
795
691
610
545
491
447
409
377
349
325
304
2
662
560
481
419
369
329
295
267
243
216
191
722
618
537
473
421
379
343
313
287
261
231
795
691
610
545
491
447
409
377
349
325
304
6.0
Deck Span
3
662
560
481
419
369
329
295
267
243
216
191
722
618
537
473
421
379
343
313
287
261
231
795
691
610
545
491
447
409
377
349
325
304
1
743
628
540
470
414
369
331
299
272
246
217
810
694
603
531
473
425
385
351
322
297
264
892
776
685
611
551
501
459
423
392
365
341
2
743
628
540
470
414
369
331
299
272
246
217
810
694
603
531
473
425
385
351
322
297
264
892
776
685
611
551
501
459
423
392
365
341
Deck Span
3
743
628
540
470
414
369
331
299
272
246
217
810
694
603
531
473
425
385
351
322
297
264
892
776
685
611
551
501
459
423
392
365
341
1
823
696
599
521
459
409
367
332
302
276
244
898
769
669
589
524
471
427
389
357
329
297
989
860
759
678
611
556
509
469
434
404
378
2
823
696
599
521
459
409
367
332
302
276
244
898
769
669
589
524
471
427
389
357
329
297
989
860
759
678
611
556
509
469
434
404
378
3
823
696
599
521
459
409
367
332
302
276
244
898
769
669
589
524
471
427
389
357
329
297
989
860
759
678
611
556
509
469
434
404
378
TECHNICAL NOTES
Material Properties
1. The composite steel deck ICD-150 is the IRD-150
roof deck with embossments rolled into the web
elements to achieve the composite interlocking
capacity between the steel deck and concrete.
2. Steel deck section properties were calculated in
accordance with CSA S136-01 (Supplement 2004).
3. Steel conforms to ASTM A653 SS Grade 33 and
A653M SS Grade 230 with Z275 (G90) and ZF75
(A25) surface coatings.
4. Concrete is based on normal density of 2300
3
kg/m (145 pcf) and having a minimum
compressive strength of 20 MPa (3 ksi).
Load Tables
1. Loads are maximum specified uniformly
2.
3.
4.
5.
6.
distributed loads resulting from human occupancy
and should not be used for concentrated loads.
Maximum specified load from load table must be
≥ [LL + 0.833DL];
Where LL = specified live load;
DL = specified dead load; 0.833 = 1.25/1.5
Loads greater than 10 kPa (200 psf) are commonly
the result of large concentrated moving loads.
In such cases, appropriate design consideration
should be used by the structural engineers.
The ICD-150 steel deck provides the positive
reinforcement for the simply supported composite
slab and no additional reinforcing steel is required.
To control shrinkage and temperature cracking,
a minimum steel wire mesh of 152 x 152 –
MW9.1/MW9.1 (6 x 6 - 10/10) is recommended as
per CSSBI S3-03.
Shoring requirements shown in shaded areas of
the load table were established in accordance with
CSSBI 12M-06.
To establish the shear-bond capacity of the
composite slab system, laboratory tests were
carried out at the Structural Testing and Research
laboratory (STAR), Cambridge, Ontario in
accordance with CSSBI S2-02.
All technical information and load tables were
prepared by Dr. R.M. Schuster, Professor
Emeritus of Structural Engineering, University of
Waterloo, Ontario.
EXAMPLE (Imperial)
Determine the specified uniformly distributed live load
that can be placed on the composite floor slab, given
the following information:
Given:
•
•
•
•
•
•
Steel deck thickness = 0.048 in.
Yield strength = 33 ksi
3
Normal density concrete = 145 lb/ft
Overall slab depth = 4.5 in.
Double span, each = 10 ft
Specified superimposed dead load,
DL = 32 psf
Solution:
The maximum specified load in (psf) from load table
must be ≥ [LL + (1.25/1.5)DL],
where
LL = specified live load
DL = specified superimposed dead load
From load table under 10 ft span, the maximum
specified load is 259 psf, therefore,
259 ≥ [LL + (1.25/1.5)32] and solving for LL,
LL = 232 psf
Since this is in the shaded area, one shore support is
required at mid-span in each span.
Note:
-The self-weight of the steel deck and concrete slab
have already been accounted for in the maximum
specified uniformly distributed load given in the
composite slab load table.
-Minimum Bearing Length “n” at end support is
1.5 x height of deck = 2.25”.
-At middle support use n=4”.
COMPOSITE SLAB SECTION PROPERTIES
(per metre of width)
STEEL PROFILE SECTION PROPERTIES
(per metre of width)
Base Steel
Thickness
(mm)
0.762
0.914
1.22
Area of
Steel
Mass
Z275
(mm 2)
1017
1221
1628
(kg/m 2)
8.26
9.86
13.1
Section Modulus
Midspan
Support
(x103mm 3)
10.2
12.4
16.9
(x103mm 3)
10.4
13.0
17.2
Deflection
Inertia
Slab Depth, D (mm)
100
110
120
130
140
(x106mm 4)
0.236
0.293
0.397
Slab weight (kPa)
1.88
2.11
2.33
2.56
2.78
Concrete Volume (m 3/10m 2)
0.76
0.86
0.96
1.06
1.16
MAXIMUM SPECIFIED UNIFORMLY DISTRIBUTED LOADS (kPa)
Slab Depth, D
(mm)
Base Steel
Thickness
(mm)
0.762
0.914
1.22
Slab
Span
(m)
1.5
1.6
1.8
2.0
2.2
2.4
2.5
2.6
2.8
3.0
3.2
1.5
1.6
1.8
2.0
2.2
2.4
2.5
2.6
2.8
3.0
3.2
1.5
1.6
1.8
2.0
2.2
2.4
2.5
2.6
2.8
3.0
3.2
100
110
Deck Span
1
24.2
21.6
17.6
14.6
12.4
10.8
10.0
9.4
8.0
6.8
5.8
26.2
23.6
19.5
16.5
14.2
12.4
11.7
11.0
9.5
8.1
6.9
28.8
26.2
22.1
19.0
16.6
14.8
14.0
13.3
12.0
9.9
8.2
2
24.2
21.6
17.6
14.6
12.4
10.8
10.0
9.4
8.0
6.8
5.8
26.2
23.6
19.5
16.5
14.2
12.4
11.7
11.0
9.5
8.1
6.9
28.8
26.2
22.1
19.0
16.6
14.8
14.0
13.3
12.0
9.9
8.2
120
Deck Span
3
24.2
21.6
17.6
14.6
12.4
10.8
10.0
9.4
8.0
6.8
5.8
26.2
23.6
19.5
16.5
14.2
12.4
11.7
11.0
9.5
8.1
6.9
28.8
26.2
22.1
19.0
16.6
14.8
14.0
13.3
12.0
9.9
8.2
Note: Shoring required at midspan in shaded areas.
1
27.3
24.4
19.8
16.5
14.1
12.1
11.3
10.6
9.2
7.8
6.7
29.6
26.6
22.0
18.6
16.1
14.0
13.2
12.4
11.0
9.4
8.1
32.5
29.6
24.9
21.5
18.8
16.7
15.8
15.0
13.6
12.2
10.5
2
27.3
24.4
19.8
16.5
14.1
12.1
11.3
10.6
9.2
7.8
6.7
29.6
26.6
22.0
18.6
16.1
14.0
13.2
12.4
11.0
9.4
8.1
32.5
29.6
24.9
21.5
18.8
16.7
15.8
15.0
13.6
12.2
10.5
130
Deck Span
3
27.3
24.4
19.8
16.5
14.1
12.1
11.3
10.6
9.2
7.8
6.7
29.6
26.6
22.0
18.6
16.1
14.0
13.2
12.4
11.0
9.4
8.1
32.5
29.6
24.9
21.5
18.8
16.7
15.8
15.0
13.6
12.2
10.5
1
30.4
27.2
22.1
18.4
15.7
13.5
12.7
11.9
10.5
8.9
7.6
33.0
29.7
24.6
20.8
17.9
15.7
14.7
13.9
12.4
10.7
9.2
36.2
33.0
27.8
24.0
21.0
18.6
17.6
16.7
15.1
13.8
12.1
2
30.4
27.2
22.1
18.4
15.7
13.5
12.7
11.9
10.5
8.9
7.6
33.0
29.7
24.6
20.8
17.9
15.7
14.7
13.9
12.4
10.7
9.2
36.2
33.0
27.8
24.0
21.0
18.6
17.6
16.7
15.1
13.8
12.1
140
Deck Span
3
30.4
27.2
22.1
18.4
15.7
13.5
12.7
11.9
10.5
8.9
7.6
33.0
29.7
24.6
20.8
17.9
15.7
14.7
13.9
12.4
10.7
9.2
36.2
33.0
27.8
24.0
21.0
18.6
17.6
16.7
15.1
13.8
12.1
1
33.6
30.0
24.4
20.3
17.3
14.9
14.0
13.1
11.6
10.0
8.5
36.4
32.8
27.1
22.9
19.7
17.3
16.2
15.3
13.7
12.0
10.3
40.0
36.4
30.7
26.4
23.1
20.5
19.4
18.4
16.7
15.2
13.6
2
33.6
30.0
24.4
20.3
17.3
14.9
14.0
13.1
11.6
10.0
8.5
36.4
32.8
27.1
22.9
19.7
17.3
16.2
15.3
13.7
12.0
10.3
40.0
36.4
30.7
26.4
23.1
20.5
19.4
18.4
16.7
15.2
13.6
Deck Span
3
33.6
30.0
24.4
20.3
17.3
14.9
14.0
13.1
11.6
10.0
8.5
36.4
32.8
27.1
22.9
19.7
17.3
16.2
15.3
13.7
12.0
10.3
40.0
36.4
30.7
26.4
23.1
20.5
19.4
18.4
16.7
15.2
13.6
1
36.7
32.8
26.7
22.2
18.9
16.3
15.3
14.3
12.7
11.0
9.4
39.8
35.8
29.6
25.1
21.6
18.9
17.7
16.7
15.0
13.3
11.4
43.7
39.8
33.5
28.9
25.3
22.5
21.3
20.2
18.3
16.7
15.2
2
36.7
32.8
26.7
22.2
18.9
16.3
15.3
14.3
12.7
11.0
9.4
39.8
35.8
29.6
25.1
21.6
18.9
17.7
16.7
15.0
13.3
11.4
43.7
39.8
33.5
28.9
25.3
22.5
21.3
20.2
18.3
16.7
15.2
3
36.7
32.8
26.7
22.2
18.9
16.3
15.3
14.3
12.7
11.0
9.4
39.8
35.8
29.6
25.1
21.6
18.9
17.7
16.7
15.0
13.3
11.4
43.7
39.8
33.5
28.9
25.3
22.5
21.3
20.2
18.3
16.7
15.2
TECHNICAL NOTES
Material Properties
1. The composite steel deck ICD-150 is the IRD-150
roof deck with embossments rolled into the web
elements to achieve the composite interlocking
capacity between the steel deck and concrete.
2. Steel deck section properties were calculated in
accordance with CSA S136-01 (Supplement 2004).
3. Steel conforms to ASTM A653 SS Grade 33 and
A653M SS Grade 230 with Z275 (G90) and ZF75
(A25) surface coatings.
4. Concrete is based on normal density of 2300
3
kg/m (145 pcf) and having a minimum
compressive strength of 20 MPa (3 ksi).
Load Tables
1. Loads are maximum specified uniformly
2.
3.
4.
5.
6.
distributed loads resulting from human occupancy
and should not be used for concentrated loads.
Maximum specified load from load table must be
≥ [LL + 0.833DL];
Where LL = specified live load;
DL = specified dead load; 0.833 = 1.25/1.5
Loads greater than 10 kPa (200 psf) are commonly
the result of large concentrated moving loads.
In such cases, appropriate design consideration
should be used by the structural engineers.
The ICD-150 steel deck provides the positive
reinforcement for the simply supported composite
slab and no additional reinforcing steel is required.
To control shrinkage and temperature cracking,
a minimum steel wire mesh of 152 x 152 –
MW9.1/MW9.1 (6 x 6 - 10/10) is recommended as
per CSSBI S3-03.
Shoring requirements shown in shaded areas of
the load table were established in accordance with
CSSBI 12M-06.
To establish the shear-bond capacity of the
composite slab system, laboratory tests were
carried out at the Structural Testing and Research
laboratory (STAR), Cambridge, Ontario in
accordance with CSSBI S2-02.
All technical information and load tables were
prepared by Dr. R.M. Schuster, Professor
Emeritus of Structural Engineering, University of
Waterloo, Ontario.
EXAMPLE (Metric)
Determine the specified uniformly distributed live load
that can be placed on the composite floor slab, given
the following information:
Given:
•
•
•
•
•
•
Steel deck thickness = 1.22 mm
Yield strength = 230 MPa
3
Normal density concrete = 2300 kg/m
Overall slab depth = 120 mm
Double span, each = 3.0 m
Specified superimposed dead load,
DL = 1.55 kPa
Solution:
The maximum specified load in (kPa) from load table
must be ≥ [LL + (1.25/1.5)DL],
where
LL = specified live load
DL = specified superimposed dead load
From load table under 3.0 m span, the maximum
specified load is 13.8 kPa, therefore,
13.8 ≥ [LL + (1.25/1.5)1.55] and solving for LL,
LL = 12.5 kPa
Since this is in the shaded area, one shore support is
required at mid-span in each span.
Note:
-The self-weight of the steel deck and concrete slab
have already been accounted for in the maximum
specified uniformly distributed load given in the
composite slab load table.
-Minimum Bearing Length “n” at end support is
1.5 x height of deck = 57mm
-At middle support use n=100mm.
COMPOSITE SLAB SECTION PROPERTIES
(per foot of width)
STEEL PROFILE SECTION PROPERTIES
(per foot of width)
Base Steel
Thickness
(in.)
0.030
0.036
0.048
Area of
Steel
Section Modulus
Midspan
Support
Weight
G90
(psf)
1.69
2.02
2.67
(in. 2)
0.481
0.577
0.769
(in. 3)
0.193
0.242
0.319
Deflection
Inertia
Slab Depth, D (in.)
4.0
4.5
5.0
5.5
6.0
(in. 4)
0.183
0.219
0.291
Slab weight (psf)
45.5
51.8
58.0
64.3
70.5
Concrete Volume (yd3/100ft2)
1.06
1.21
1.37
1.52
1.68
(in. 3)
0.189
0.230
0.313
MAXIMUM SPECIFIED UNIFORMLY DISTRIBUTED LOADS (psf)
Slab Depth, D
(in.)
Base Steel
Thickness
(in.)
0.030
0.036
0.048
Slab
Span
(ft)
5'- 0"
5'- 6"
6'- 0"
6'- 6"
7'- 0"
7'- 6"
8'- 0"
8'- 6"
9'- 0"
9'- 6"
10'- 0"
5'- 0"
5'- 6"
6'- 0"
6'- 6"
7'- 0"
7'- 6"
8'- 0"
8'- 6"
9'- 0"
9'- 6"
10'- 0"
5'- 0"
5'- 6"
6'- 0"
6'- 6"
7'- 0"
7'- 6"
8'- 0"
8'- 6"
9'- 0"
9'- 6"
10'- 0"
4.0
4.5
Deck Span
5.5
5.0
Deck Span
Deck Span
6.0
Deck Span
Deck Span
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
401
338
290
252
221
196
176
159
144
132
121
401
338
290
252
221
196
176
159
144
132
121
401
338
290
252
221
196
176
159
144
132
121
461
389
333
289
254
226
202
182
165
151
139
461
389
333
289
254
226
202
182
165
151
139
461
389
333
289
254
226
202
182
165
151
139
520
439
376
327
287
255
228
206
187
171
157
520
439
376
327
287
255
228
206
187
171
157
520
439
376
327
287
255
228
206
187
171
157
580
489
419
364
320
284
254
229
208
190
174
580
489
419
364
320
284
254
229
208
190
174
580
489
419
364
320
284
254
229
208
190
174
639
539
462
401
353
313
280
253
229
210
192
639
539
462
401
353
313
280
253
229
210
192
639
539
462
401
353
313
280
253
229
210
192
454
383
328
285
251
223
199
180
163
149
137
454
383
328
285
251
223
199
180
163
149
137
454
383
328
285
251
223
199
180
163
149
137
521
440
377
328
288
256
229
207
188
171
157
521
440
377
328
288
256
229
207
188
171
157
521
440
377
328
288
256
229
207
188
171
157
589
497
426
370
325
289
259
233
212
194
178
589
497
426
370
325
289
259
233
212
194
178
589
497
426
370
325
289
259
233
212
194
178
656
554
475
412
363
322
288
260
236
216
198
656
554
475
412
363
322
288
260
236
216
198
656
554
475
412
363
322
288
260
236
216
198
724
610
523
455
400
355
318
287
260
238
218
724
610
523
455
400
355
318
287
260
238
218
724
610
523
455
400
355
318
287
260
238
218
535
452
387
337
296
263
236
213
193
177
162
535
452
387
337
296
263
236
213
193
177
162
535
452
387
337
296
263
236
213
193
177
162
615
519
445
387
340
302
271
244
222
203
186
615
519
445
387
340
302
271
244
222
203
186
615
519
445
387
340
302
271
244
222
203
186
694
586
503
437
384
341
306
276
251
229
211
694
586
503
437
384
341
306
276
251
229
211
694
586
503
437
384
341
306
276
251
229
211
774
653
560
487
428
380
341
308
280
255
235
774
653
560
487
428
380
341
308
280
255
235
774
653
560
487
428
380
341
308
280
255
235
853
720
618
537
472
420
376
339
308
282
259
853
720
618
537
472
420
376
339
308
282
259
853
720
618
537
472
420
376
339
308
282
259
Note: Shoring required at midspan in shaded areas.
TECHNICAL NOTES
Material Properties
1. The ICD-150 (INVERTED) is the IRD-150 roof deck
with embossments rolled into the web elements to
achieve the composite interlocking capacity
between the steel deck and concrete.
2. Steel deck section properties were calculated in
accordance with CSA S136-07.
3. Steel conforms to ASTM A653 SS Grade 33 and
A653M SS Grade 230 with Z275 (G90) and ZF75
(A25) surface coatings.
4. Concrete is based on normal density of 2300
3
kg/m (145 pcf) and having a minimum
compressive strength of 20 MPa (3 ksi).
Load Tables
1. Loads are maximum specified uniformly
2.
3.
4.
5.
6.
distributed loads resulting from human occupancy
and should not be used for concentrated loads.
Maximum specified load from load table must be
≥ [LL + 0.833DL];
Where LL = specified live load;
DL = specified dead load; 0.833 = 1.25/1.5
Loads greater than 10 kPa (200 psf) are commonly
the result of large concentrated moving loads.
In such cases, appropriate design consideration
should be used by the structural engineers.
The ICD-150 steel deck provides the positive
reinforcement for the simply supported composite
slab and no additional reinforcing steel is required.
To control shrinkage and temperature cracking, a
minimum steel wire mesh of 152 x 152 –
MW9.1/MW9.1
(6 x 6 - 10/10) is recommended as per
CSSBI S3-03.
Shoring requirements shown in shaded areas of
the load table were established in accordance with
CSSBI 12M-06.
To establish the shear-bond capacity of the IDEAL
inverted composite slab system, laboratory tests
were carried out at the Structural Testing and
Research laboratory (STAR), Cambridge, Ontario
in accordance with CSSBI S2-02.
All technical information and load tables were
prepared by Dr. R.M. Schuster, Professor
Emeritus of Structural Engineering, University of
Waterloo, Ontario.
EXAMPLE (Imperial)
Determine the specified uniformly distributed live load
that can be placed on the IDEAL inverted composite
floor slab, given the following information:
Given:
•
•
•
•
•
•
Steel deck thickness = 0.048 in.
Yield strength = 33 ksi
3
Normal density concrete = 145 lb/ft
Overall slab depth = 5.0 in.
Double span, each = 9.5 ft
Specified superimposed dead load,
DL = 37 psf
Solution:
The maximum specified load in (psf) from load table
must be ≥ [LL + (1.25/1.5)DL],
where
LL = specified live load
DL = specified superimposed dead load
From load table under 9.5 ft span, the maximum
specified load is 229 psf, therefore,
229 ≥ [LL + (1.25/1.5)32] and solving for LL,
LL = 198 psf
Since this is in the shaded area, one shore support is
required at mid-span in each span.
Note:
-The self-weight of the steel deck and concrete slab
have already been accounted for in the maximum
specified uniformly distributed load given in the
composite slab load table.
-Minimum Bearing Length “n” at end support is
1.5 x height of deck = 2.25”.
-At middle support use n=4”.
COMPOSITE SLAB SECTION PROPERTIES
(per metre of width)
STEEL PROFILE SECTION PROPERTIES
(per metre of width)
Base Steel
Thickness
(mm)
0.762
0.914
1.22
Area of
Steel
Mass
Z275
(mm 2)
1017
1221
1628
(kg/m 2)
8.26
9.86
13.1
Section Modulus
Midspan
Support
(x103mm 3)
10.4
13.0
17.2
(x103mm 3)
10.2
12.4
16.9
Deflection
Inertia
Slab Depth, D (mm)
100
110
120
130
140
(x106mm 4)
0.250
0.299
0.397
Slab weight (kPa)
2.06
2.28
2.51
2.73
2.96
Concrete Volume (m 3/10m 2)
0.86
0.96
1.06
1.16
1.26
MAXIMUM SPECIFIED UNIFORMLY DISTRIBUTED LOADS (kPa)
Slab Depth, D
(mm)
Base Steel
Thickness
(mm)
0.762
0.914
1.22
Slab
Span
(m)
1.5
1.6
1.8
2.0
2.2
2.4
2.5
2.6
2.8
3.0
3.2
1.5
1.6
1.8
2.0
2.2
2.4
2.5
2.6
2.8
3.0
3.2
1.5
1.6
1.8
2.0
2.2
2.4
2.5
2.6
2.8
3.0
3.2
100
110
Deck Span
120
Deck Span
130
Deck Span
140
Deck Span
Deck Span
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
19.4
17.3
14.0
11.6
9.9
8.5
7.9
7.4
6.5
5.8
5.2
19.4
17.3
14.0
11.6
9.9
8.5
7.9
7.4
6.5
5.8
5.2
19.4
17.3
14.0
11.6
9.9
8.5
7.9
7.4
6.5
5.8
5.2
21.7
19.3
15.7
13.0
11.0
9.5
8.9
8.3
7.3
6.5
5.9
21.7
19.3
15.7
13.0
11.0
9.5
8.9
8.3
7.3
6.5
5.9
21.7
19.3
15.7
13.0
11.0
9.5
8.9
8.3
7.3
6.5
5.9
24.0
21.4
17.3
14.4
12.2
10.5
9.8
9.2
8.1
7.2
6.5
24.0
21.4
17.3
14.4
12.2
10.5
9.8
9.2
8.1
7.2
6.5
24.0
21.4
17.3
14.4
12.2
10.5
9.8
9.2
8.1
7.2
6.5
26.3
23.4
19.0
15.8
13.4
11.5
10.7
10.1
8.9
7.9
7.1
26.3
23.4
19.0
15.8
13.4
11.5
10.7
10.1
8.9
7.9
7.1
26.3
23.4
19.0
15.8
13.4
11.5
10.7
10.1
8.9
7.9
7.1
28.6
25.5
20.7
17.2
14.6
12.5
11.7
10.9
9.6
8.6
7.7
28.6
25.5
20.7
17.2
14.6
12.5
11.7
10.9
9.6
8.6
7.7
28.6
25.5
20.7
17.2
14.6
12.5
11.7
10.9
9.6
8.6
7.7
21.9
19.5
15.9
13.2
11.2
9.6
9.0
8.4
7.4
6.6
5.9
21.9
19.5
15.9
13.2
11.2
9.6
9.0
8.4
7.4
6.6
5.9
21.9
19.5
15.9
13.2
11.2
9.6
9.0
8.4
7.4
6.6
5.9
24.5
21.9
17.7
14.7
12.5
10.8
10.0
9.4
8.3
7.4
6.6
24.5
21.9
17.7
14.7
12.5
10.8
10.0
9.4
8.3
7.4
6.6
24.5
21.9
17.7
14.7
12.5
10.8
10.0
9.4
8.3
7.4
6.6
27.1
24.2
19.6
16.3
13.8
11.9
11.1
10.4
9.2
8.2
7.4
27.1
24.2
19.6
16.3
13.8
11.9
11.1
10.4
9.2
8.2
7.4
27.1
24.2
19.6
16.3
13.8
11.9
11.1
10.4
9.2
8.2
7.4
29.8
26.5
21.5
17.9
15.2
13.1
12.2
11.4
10.1
9.0
8.1
29.8
26.5
21.5
17.9
15.2
13.1
12.2
11.4
10.1
9.0
8.1
29.8
26.5
21.5
17.9
15.2
13.1
12.2
11.4
10.1
9.0
8.1
32.4
28.8
23.4
19.5
16.5
14.2
13.3
12.4
10.9
9.8
8.8
32.4
28.8
23.4
19.5
16.5
14.2
13.3
12.4
10.9
9.8
8.8
32.4
28.8
23.4
19.5
16.5
14.2
13.3
12.4
10.9
9.8
8.8
25.9
23.1
18.7
15.6
13.2
11.4
10.6
9.9
8.8
7.8
7.0
25.9
23.1
18.7
15.6
13.2
11.4
10.6
9.9
8.8
7.8
7.0
25.9
23.1
18.7
15.6
13.2
11.4
10.6
9.9
8.8
7.8
7.0
29.0
25.8
21.0
17.4
14.8
12.7
11.9
11.1
9.8
8.8
7.9
29.0
25.8
21.0
17.4
14.8
12.7
11.9
11.1
9.8
8.8
7.9
29.0
25.8
21.0
17.4
14.8
12.7
11.9
11.1
9.8
8.8
7.9
32.0
28.6
23.2
19.3
16.4
14.1
13.1
12.3
10.9
9.7
8.7
32.0
28.6
23.2
19.3
16.4
14.1
13.1
12.3
10.9
9.7
8.7
32.0
28.6
23.2
19.3
16.4
14.1
13.1
12.3
10.9
9.7
8.7
35.1
31.3
25.4
21.1
17.9
15.5
14.4
13.5
11.9
10.6
9.6
35.1
31.3
25.4
21.1
17.9
15.5
14.4
13.5
11.9
10.6
9.6
35.1
31.3
25.4
21.1
17.9
15.5
14.4
13.5
11.9
10.6
9.6
38.2
34.1
27.7
23.0
19.5
16.8
15.7
14.7
13.0
11.6
10.4
38.2
34.1
27.7
23.0
19.5
16.8
15.7
14.7
13.0
11.6
10.4
38.2
34.1
27.7
23.0
19.5
16.8
15.7
14.7
13.0
11.6
10.4
Note: Shoring required at midspan in shaded areas.
TECHNICAL NOTES
Material Properties
1. The ICD-150 (INVERTED) is the IRD-150 roof deck
with embossments rolled into the web elements to
achieve the composite interlocking capacity
between the steel deck and concrete.
2. Steel deck section properties were calculated in
accordance with CSA S136-07.
3. Steel conforms to ASTM A653 SS Grade 33 and
A653M SS Grade 230 with Z275 (G90) and ZF75
(A25) surface coatings.
4. Concrete is based on normal density of 2300
3
kg/m (145 pcf) and having a minimum
compressive strength of 20 MPa (3 ksi).
Load Tables
1. Loads are maximum specified uniformly
2.
3.
4.
5.
6.
distributed loads resulting from human occupancy
and should not be used for concentrated loads.
Maximum specified load from load table must be
≥ [LL + 0.833DL];
Where LL = specified live load;
DL = specified dead load; 0.833 = 1.25/1.5
Loads greater than 10 kPa (200 psf) are commonly
the result of large concentrated moving loads.
In such cases, appropriate design consideration
should be used by the structural engineers.
The ICD-150 steel deck provides the positive
reinforcement for the simply supported composite
slab and no additional reinforcing steel is required.
To control shrinkage and temperature cracking, a
minimum steel wire mesh of 152 x 152 –
MW9.1/MW9.1
(6 x 6 - 10/10) is recommended as per
CSSBI S3-03.
Shoring requirements shown in shaded areas of
the load table were established in accordance with
CSSBI 12M-06.
To establish the shear-bond capacity of the IDEAL
inverted composite slab system, laboratory tests
were carried out at the Structural Testing and
Research laboratory (STAR), Cambridge, Ontario
in accordance with CSSBI S2-02.
All technical information and load tables were
prepared by Dr. R.M. Schuster, Professor
Emeritus of Structural Engineering, University of
Waterloo, Ontario.
EXAMPLE (Metric)
Determine the specified uniformly distributed live load
that can be placed on the IDEAL inverted composite
floor slab, given the following information:
Given:
•
•
•
•
•
•
Steel deck thickness = 1.22 mm
Yield strength = 230 MPa
3
Normal density concrete = 2300 kg/m
Overall slab depth = 130 mm
Double span, each = 2.8 m
Specified superimposed dead load,
DL = 1.70 kPa
Solution:
The maximum specified load in (kPa) from load table
must be ≥ [LL + (1.25/1.5)DL],
where
LL = specified live load
DL = specified superimposed dead load
From load table under 2.8 m span, the maximum
specified load is 11.9 kPa, therefore,
11.9 ≥ [LL + (1.25/1.5)1.70] and solving for LL,
LL = 10.5 kPa
Since this is in the shaded area, one shore support is
required at mid-span in each span.
Note:
-The self-weight of the steel deck and concrete slab
have already been accounted for in the maximum
specified uniformly distributed load given in the
composite slab load table.
-Minimum Bearing Length “n” at end support is
1.5 x height of deck = 57mm
-At middle support use n=100mm.
STEEL DECK SECTION PROPERTIES
Base Steel
Thickness
(in.)
0.030
0.036
0.048
0.060
Area of
Steel
(in2 )
0.617
0.741
0.987
1.23
(per foot of width)
Weight
Section Modulus
G90
Midspan
Support
(in3 )
(in3 )
(psf)
2.16
0.436
0.447
2.58
0.559
0.564
3.42
0.769
0.799
4.26
0.981
0.996
COMPOSITE SLAB INFORMATION
(per foot of width)
Deflection
Inertia
(in4 )
0.773
0.967
1.35
1.70
Slab Depth, D (in.)
5.0
5.5
Slab weight (psf)
44.4
50.6
3
6.0
6.5
7.0
56.9
63.1
69.4
1.45
1.61
2
Concrete Volume (yd /100ft )
0.99
1.15
1.30
MAXIMUM SPECIFIED UNIFORMLY DISTRIBUTED LOADS (psf)
Slab Depth, D
(in.)
Base Steel Slab
Thickness Span
(in.)
(ft)
6'-0"
6'-6"
7'-0"
7'-6"
8'-0"
8'-6"
0.030
9'-0"
9'-6"
10'-0"
10'-6"
11'-0"
11'-6"
7'-0"
7'-6"
8'-0"
8'-6"
9'-0"
9'-6"
0.036 10'-0"
10'-6"
11'-0"
11'-6"
12'-0"
12'-6"
8'-0"
8'-6"
9'-0"
9'-6"
10'-0"
10'-6"
0.048 11'-0"
11'-6"
12'-0"
12'-6"
13'-0"
13'-6"
8'-0"
8'-6"
9'-0"
9'-6"
10'-0"
10'-6"
0.060 11'-0"
11'-6"
12'-0"
12'-6"
13'-0"
13'-6"
14'-0"
5.0
5.5
Deck Span
6.0
Deck Span
6.5
Deck Span
7.0
Deck Span
Deck Span
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
307
260
223
194
169
149
132
118
106
96
87
79
265
231
204
181
162
145
132
120
109
100
92
85
268
240
216
196
179
163
150
139
129
120
112
105
268
239
216
196
178
163
150
139
129
120
112
104
98
307
260
223
194
169
149
132
118
106
96
87
79
265
231
204
181
162
145
132
120
109
100
92
85
268
240
216
196
179
163
150
139
129
120
112
105
268
239
216
196
178
163
150
139
129
120
112
104
98
307
260
223
194
169
149
132
118
106
96
87
79
265
231
204
181
162
145
132
120
109
100
92
85
268
240
216
196
179
163
150
139
129
120
112
105
268
239
216
196
178
163
150
139
129
120
112
104
98
353
299
257
223
195
172
152
136
122
110
100
91
305
266
235
208
186
167
151
138
126
115
106
98
309
276
249
226
206
188
173
160
148
138
129
120
308
276
248
225
205
188
173
160
148
138
129
120
113
353
299
257
223
195
172
152
136
122
110
100
91
305
266
235
208
186
167
151
138
126
115
106
98
309
276
249
226
206
188
173
160
148
138
129
120
308
276
248
225
205
188
173
160
148
138
129
120
113
353
299
257
223
195
172
152
136
122
110
100
91
305
266
235
208
186
167
151
138
126
115
106
98
309
276
249
226
206
188
173
160
148
138
129
120
308
276
248
225
205
188
173
160
148
138
129
120
113
400
339
291
252
220
194
173
154
138
125
113
103
345
301
265
236
211
189
171
156
142
130
120
111
349
313
282
255
233
213
196
181
168
156
146
136
349
312
281
255
232
213
196
181
168
156
145
136
128
400
339
291
252
220
194
173
154
138
125
113
103
345
301
265
236
211
189
171
156
142
130
120
111
349
313
282
255
233
213
196
181
168
156
146
136
349
312
281
255
232
213
196
181
168
156
145
136
128
400
339
291
252
220
194
173
154
138
125
113
103
345
301
265
236
211
189
171
156
142
130
120
111
349
313
282
255
233
213
196
181
168
156
146
136
349
312
281
255
232
213
196
181
168
156
145
136
128
446
378
324
281
246
217
193
172
154
139
126
115
385
336
296
263
235
211
191
174
159
145
134
124
390
349
314
285
260
238
219
202
187
174
163
152
389
348
314
285
259
238
218
202
187
174
162
152
143
446
378
324
281
246
217
193
172
154
139
126
115
385
336
296
263
235
211
191
174
159
145
134
124
390
349
314
285
260
238
219
202
187
174
163
152
389
348
314
285
259
238
218
202
187
174
162
152
143
446
378
324
281
246
217
193
172
154
139
126
115
385
336
296
263
235
211
191
174
159
145
134
124
390
349
314
285
260
238
219
202
187
174
163
152
389
348
314
285
259
238
218
202
187
174
162
152
143
492
417
358
311
272
239
213
190
170
154
139
127
425
371
327
290
260
233
211
192
175
161
148
136
430
385
347
315
287
263
242
223
207
192
180
168
430
385
347
314
286
262
241
223
207
192
179
168
158
492
417
358
311
272
239
213
190
170
154
139
127
425
371
327
290
260
233
211
192
175
161
148
136
430
385
347
315
287
263
242
223
207
192
180
168
430
385
347
314
286
262
241
223
207
192
179
168
158
492
417
358
311
272
239
213
190
170
154
139
127
425
371
327
290
260
233
211
192
175
161
148
136
430
385
347
315
287
263
242
223
207
192
180
168
430
385
347
314
286
262
241
223
207
192
179
168
158
Note: Shoring required at midspan in shaded areas.
TECHNICAL NOTES
Material Properties
1. The composite steel deck ICD-300 is the IRD-300
roof deck with embossments rolled into the web
elements to achieve the composite interlocking
capacity between the steel deck and concrete.
2. Steel deck section properties were calculated in
accordance with CSA S136-07.
3. Steel conforms to ASTM A653 SS Grade 33 and
A653M SS Grade 230 with Z275 (G90) and ZF75
(A25) surface coatings.
4. Concrete is based on normal density of 2300
3
kg/m (145 pcf) and having a minimum
compressive strength of 20 MPa (3 ksi).
Load Tables
1. Loads are maximum specified uniformly
2.
3.
4.
5.
6.
distributed loads resulting from human occupancy
and should not be used for concentrated loads.
Maximum specified load from load table must be
≥ [LL + 0.833DL];
Where LL = specified live load;
DL = specified dead load; 0.833 = 1.25/1.5
Loads greater than 10 kPa (200 psf) are commonly
the result of large concentrated moving loads.
In such cases, appropriate design consideration
should be used by the structural engineers.
The ICD-300 steel deck provides the positive
reinforcement for the simply supported composite
slab and no additional reinforcing steel is required.
To control shrinkage and temperature cracking,
a minimum steel wire mesh of 152 x 152 –
MW9.1/MW9.1 (6 x 6 - 10/10) is recommended as
per CSSBI S3-08.
Shoring requirements shown in shaded areas of
the load table were established in accordance with
CSSBI 12M-08.
To establish the shear-bond capacity of the ICD300 composite slab system, laboratory tests were
carried out at the Structural Testing and Research
laboratory (STAR), Cambridge, Ontario in
accordance with CSSBI S2-08.
All technical information and load tables were
prepared by Dr. R.M. Schuster, Professor
Emeritus of Structural Engineering, University of
Waterloo, Ontario.
EXAMPLE (Imperial)
Determine the specified uniformly distributed live load
that can be placed on the composite floor slab, given
the following information:
Given:
•
•
•
•
•
•
Steel deck thickness = 0.036 in.
Yield strength = 33 ksi
3
Normal density concrete = 145 lb/ft
Overall slab depth = 6 in.
Double span, each = 11 ft
Specified superimposed dead load,
DL = 32 psf
Solution:
The maximum specified load in (psf) from load table
must be ≥ [LL + (1.25/1.5)DL],
where
LL = specified live load
DL = specified superimposed dead load
From load table under 11 ft span, the maximum
specified load is 142 psf, therefore,
142 ≥ [LL + (1.25/1.5)32] and solving for LL,
LL = 99 psf
Since this is in the shaded area, one shore support is
required at mid-span in each span.
Note:
-The self-weight of the steel deck and concrete slab
have already been accounted for in the maximum
specified uniformly distributed load given in the
composite slab load table.
-Minimum Bearing Length “n” at end support is
1.5 x height of deck = 4.5”.
-At middle support use n=6”.
STEEL DECK SECTION PROPERTIES
Base Steel
Thickness
(mm)
0.762
0.914
1.219
1.524
Area of
Steel
(mm2 )
1306
1568
2090
2613
COMPOSITE SLAB INFORMATION
(per metre of width)
Mass
Section Modulus
Deflection
Z275
Midspan
Support
Inertia
(kg/m2 )
(x103 mm3 ) (x103mm3) (x106 mm4)
10.5
23.4
24.0
1.05
12.6
30.0
30.3
1.32
16.7
41.3
42.9
1.84
20.8
52.7
53.6
2.32
(per metre of width)
Slab Depth, D (mm)
130
140
150
160
Slab weight (kPa)
2.11
2.34
2.56
2.79
3
170
3.01
2
Concrete Volume (m /10m )
0.85
0.95
1.05
1.15
1.25
MAXIMUM SPECIFIED UNIFORMLY DISTRIBUTED LOADS (kPa)
Slab Depth, D
(mm)
Base Steel Slab
Thickness Span
(mm)
(m)
2.2
2.4
2.5
2.6
2.8
3.0
0.762
3.2
3.4
3.5
3.6
3.8
4.0
2.2
2.4
2.5
2.6
2.8
3.0
0.914
3.2
3.4
3.5
3.6
3.8
4.0
2.5
2.6
2.8
3.0
3.2
3.4
1.219
3.5
3.6
3.8
4.0
4.2
4.4
2.6
2.8
3.0
3.2
3.4
3.5
3.6
1.524
3.8
4.0
4.2
4.4
4.5
4.6
130
140
Deck Span
150
Deck Span
160
Deck Span
170
Deck Span
Deck Span
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
10.4
8.6
7.9
7.3
6.3
5.4
4.7
4.2
3.9
3.7
3.3
3.0
12.4
10.4
9.6
8.9
7.7
6.7
5.9
5.3
5.0
4.7
4.2
3.8
12.7
11.8
10.3
9.1
8.1
7.3
6.9
6.6
6.0
5.4
5.0
4.6
11.8
10.3
9.1
8.1
7.3
6.9
6.6
6.0
5.4
5.0
4.6
4.4
4.3
10.4
8.6
7.9
7.3
6.3
5.4
4.7
4.2
3.9
3.7
3.3
3.0
12.4
10.4
9.6
8.9
7.7
6.7
5.9
5.3
5.0
4.7
4.2
3.8
12.7
11.8
10.3
9.1
8.1
7.3
6.9
6.6
6.0
5.4
5.0
4.6
11.8
10.3
9.1
8.1
7.3
6.9
6.6
6.0
5.4
5.0
4.6
4.4
4.3
10.4
8.6
7.9
7.3
6.3
5.4
4.7
4.2
3.9
3.7
3.3
3.0
12.4
10.4
9.6
8.9
7.7
6.7
5.9
5.3
5.0
4.7
4.2
3.8
12.7
11.8
10.3
9.1
8.1
7.3
6.9
6.6
6.0
5.4
5.0
4.6
11.8
10.3
9.1
8.1
7.3
6.9
6.6
6.0
5.4
5.0
4.6
4.4
4.3
11.5
9.6
8.9
8.2
7.0
6.1
5.3
4.6
4.4
4.1
3.7
3.3
13.8
11.6
10.7
9.9
8.6
7.5
6.6
5.9
5.5
5.2
4.7
4.3
14.1
13.2
11.5
10.2
9.0
8.1
7.7
7.3
6.7
6.1
5.6
5.1
13.1
11.5
10.1
9.0
8.1
7.7
7.3
6.6
6.1
5.6
5.1
4.9
4.8
11.5
9.6
8.9
8.2
7.0
6.1
5.3
4.6
4.4
4.1
3.7
3.3
13.8
11.6
10.7
9.9
8.6
7.5
6.6
5.9
5.5
5.2
4.7
4.3
14.1
13.2
11.5
10.2
9.0
8.1
7.7
7.3
6.7
6.1
5.6
5.1
13.1
11.5
10.1
9.0
8.1
7.7
7.3
6.6
6.1
5.6
5.1
4.9
4.8
11.5
9.6
8.9
8.2
7.0
6.1
5.3
4.6
4.4
4.1
3.7
3.3
13.8
11.6
10.7
9.9
8.6
7.5
6.6
5.9
5.5
5.2
4.7
4.3
14.1
13.2
11.5
10.2
9.0
8.1
7.7
7.3
6.7
6.1
5.6
5.1
13.1
11.5
10.1
9.0
8.1
7.7
7.3
6.6
6.1
5.6
5.1
4.9
4.8
12.7
10.6
9.8
9.0
7.7
6.7
5.8
5.1
4.8
4.5
4.1
3.6
15.2
12.8
11.8
11.0
9.5
8.3
7.3
6.5
6.1
5.8
5.2
4.7
15.6
14.5
12.7
11.2
10.0
8.9
8.5
8.1
7.3
6.7
6.2
5.7
14.5
12.7
11.2
10.0
8.9
8.5
8.1
7.3
6.7
6.1
5.7
5.4
5.2
12.7
10.6
9.8
9.0
7.7
6.7
5.8
5.1
4.8
4.5
4.1
3.6
15.2
12.8
11.8
11.0
9.5
8.3
7.3
6.5
6.1
5.8
5.2
4.7
15.6
14.5
12.7
11.2
10.0
8.9
8.5
8.1
7.3
6.7
6.2
5.7
14.5
12.7
11.2
10.0
8.9
8.5
8.1
7.3
6.7
6.1
5.7
5.4
5.2
12.7
10.6
9.8
9.0
7.7
6.7
5.8
5.1
4.8
4.5
4.1
3.6
15.2
12.8
11.8
11.0
9.5
8.3
7.3
6.5
6.1
5.8
5.2
4.7
15.6
14.5
12.7
11.2
10.0
8.9
8.5
8.1
7.3
6.7
6.2
5.7
14.5
12.7
11.2
10.0
8.9
8.5
8.1
7.3
6.7
6.1
5.7
5.4
5.2
13.9
11.6
10.7
9.8
8.4
7.3
6.4
5.6
5.3
5.0
4.4
4.0
16.6
14.0
12.9
12.0
10.4
9.0
8.0
7.1
6.7
6.3
5.7
5.2
17.1
15.9
13.9
12.2
10.9
9.8
9.3
8.8
8.0
7.3
6.7
6.2
15.9
13.9
12.2
10.9
9.8
9.3
8.8
8.0
7.3
6.7
6.2
6.0
5.7
13.9
11.6
10.7
9.8
8.4
7.3
6.4
5.6
5.3
5.0
4.4
4.0
16.6
14.0
12.9
12.0
10.4
9.0
8.0
7.1
6.7
6.3
5.7
5.2
17.1
15.9
13.9
12.2
10.9
9.8
9.3
8.8
8.0
7.3
6.7
6.2
15.9
13.9
12.2
10.9
9.8
9.3
8.8
8.0
7.3
6.7
6.2
6.0
5.7
13.9
11.6
10.7
9.8
8.4
7.3
6.4
5.6
5.3
5.0
4.4
4.0
16.6
14.0
12.9
12.0
10.4
9.0
8.0
7.1
6.7
6.3
5.7
5.2
17.1
15.9
13.9
12.2
10.9
9.8
9.3
8.8
8.0
7.3
6.7
6.2
15.9
13.9
12.2
10.9
9.8
9.3
8.8
8.0
7.3
6.7
6.2
6.0
5.7
15.1
12.6
11.6
10.7
9.2
7.9
6.9
6.1
5.7
5.4
4.8
4.3
18.1
15.2
14.0
13.0
11.2
9.8
8.7
7.7
7.3
6.9
6.2
5.6
18.5
17.2
15.1
13.3
11.8
10.6
10.1
9.6
8.7
8.0
7.3
6.7
17.2
15.0
13.3
11.8
10.6
10.1
9.6
8.7
8.0
7.3
6.7
6.5
6.2
15.1
12.6
11.6
10.7
9.2
7.9
6.9
6.1
5.7
5.4
4.8
4.3
18.1
15.2
14.0
13.0
11.2
9.8
8.7
7.7
7.3
6.9
6.2
5.6
18.5
17.2
15.1
13.3
11.8
10.6
10.1
9.6
8.7
8.0
7.3
6.7
17.2
15.0
13.3
11.8
10.6
10.1
9.6
8.7
8.0
7.3
6.7
6.5
6.2
15.1
12.6
11.6
10.7
9.2
7.9
6.9
6.1
5.7
5.4
4.8
4.3
18.1
15.2
14.0
13.0
11.2
9.8
8.7
7.7
7.3
6.9
6.2
5.6
18.5
17.2
15.1
13.3
11.8
10.6
10.1
9.6
8.7
8.0
7.3
6.7
17.2
15.0
13.3
11.8
10.6
10.1
9.6
8.7
8.0
7.3
6.7
6.5
6.2
Note: Shoring required at midspan in shaded areas.
TECHNICAL NOTES
Material Properties
1. The composite steel deck ICD-300 is the IRD-300
roof deck with embossments rolled into the web
elements to achieve the composite interlocking
capacity between the steel deck and concrete.
2. Steel deck section properties were calculated in
accordance with CSA S136-07.
3. Steel conforms to ASTM A653 SS Grade 33 and
A653M SS Grade 230 with Z275 (G90) and ZF75
(A25) surface coatings.
4. Concrete is based on normal density of 2300
3
kg/m (145 pcf) and having a minimum
compressive strength of 20 MPa (3 ksi).
Load Tables
1. Loads are maximum specified uniformly
2.
3.
4.
5.
6.
distributed loads resulting from human occupancy
and should not be used for concentrated loads.
Maximum specified load from load table must be
≥ [LL + 0.833DL];
Where LL = specified live load;
DL = specified dead load; 0.833 = 1.25/1.5
Loads greater than 10 kPa (200 psf) are commonly
the result of large concentrated moving loads.
In such cases, appropriate design consideration
should be used by the structural engineers.
The ICD-300 steel deck provides the positive
reinforcement for the simply supported composite
slab and no additional reinforcing steel is required.
To control shrinkage and temperature cracking,
a minimum steel wire mesh of 152 x 152 –
MW9.1/MW9.1 (6 x 6 - 10/10) is recommended as
per CSSBI S3-08.
Shoring requirements shown in shaded areas of
the load table were established in accordance with
CSSBI 12M-08.
To establish the shear-bond capacity of the ICD300 composite slab system, laboratory tests were
carried out at the Structural Testing and Research
laboratory (STAR), Cambridge, Ontario in
accordance with CSSBI S2-08.
All technical information and load tables were
prepared by Dr. R.M. Schuster, Professor
Emeritus of Structural Engineering, University of
Waterloo, Ontario.
EXAMPLE (Metric)
Determine the specified uniformly distributed live load
that can be placed on the composite floor slab, given
the following information:
Given:
•
•
•
•
•
•
Steel deck thickness = 0.914 mm
Yield strength = 230 MPa
3
Normal density concrete = 2300 kg/m
Overall slab depth = 150 mm
Double span, each = 3.5 m
Specified superimposed dead load,
DL = 1.60 kPa
Solution:
The maximum specified load in (kPa) from load table
must be ≥ [LL + (1.25/1.5)DL],
where
LL = specified live load
DL = specified superimposed dead load
From load table under 3.5 m span, the maximum
specified load is 6.1 kPa, therefore,
6.1 ≥ [LL + (1.25/1.5)1.55] and solving for LL,
LL = 4.77 kPa
Since this is in the shaded area, one shore support is
required at mid-span in each span.
Note:
-The self-weight of the steel deck and concrete slab
have already been accounted for in the maximum
specified uniformly distributed load given in the
composite slab load table.
-Minimum Bearing Length “n” at end support is
1.5 x height of deck = 114mm.
-At middle support use n=150mm.
STEEL DECK SECTION PROPERTIES
Base Steel
Thickness
(in.)
0.030
0.036
0.048
0.060
Area of
Steel
2
(in )
0.617
0.741
0.987
1.23
(per foot of width)
Weight
Section Modulus
G90
Midspan
Support
3
3
(in )
(in )
(psf)
2.16
0.447
0.436
2.58
0.564
0.559
3.42
0.799
0.769
4.26
0.996
0.981
COMPOSITE SLAB INFORMATION
(per foot of width)
Deflection
Inertia
4
(in )
0.841
1.02
1.36
1.70
Slab Depth, D (in.)
5.0
5.5
Slab weight (psf)
51.7
57.9
6.0
6.5
7.0
64.2
70.4
76.7
1.63
1.79
3
2
Concrete Volume (yd /100ft )
1.17
1.33
1.48
MAXIMUM SPECIFIED UNIFORMLY DISTRIBUTED LOADS (psf)
Slab Depth, D
(in.)
Base Steel Slab
Thickness Span
(in.)
(ft)
6'-0"
6'-6"
7'-0"
7'-6"
8'-0"
8'-6"
0.030
9'-0"
9'-6"
10'-0"
10'-6"
11'-0"
11'-6"
7'-0"
7'-6"
8'-0"
8'-6"
9'-0"
9'-6"
0.036
10'-0"
10'-6"
11'-0"
11'-6"
12'-0"
12'-6"
8'-0"
8'-6"
9'-0"
9'-6"
10'-0"
10'-6"
0.048
11'-0"
11'-6"
12'-0"
12'-6"
13'-0"
13'-6"
8'-0"
8'-6"
9'-0"
9'-6"
10'-0"
10'-6"
11'-0"
0.060
11'-6"
12'-0"
12'-6"
13'-0"
13'-6"
14'-0"
5.0
5.5
Deck Span
6.0
Deck Span
6.5
7.0
Deck Span
Deck Span
Deck Span
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
367
308
261
224
193
168
148
130
115
103
92
82
295
255
222
195
172
153
137
123
111
100
91
83
275
244
218
196
177
161
146
134
123
114
105
98
275
244
218
196
177
160
146
134
123
114
105
98
91
367
308
261
224
193
168
148
130
115
103
92
82
295
255
222
195
172
153
137
123
111
100
91
83
275
244
218
196
177
161
146
134
123
114
105
98
275
244
218
196
177
160
146
134
123
114
105
98
91
367
308
261
224
193
168
148
130
115
103
92
82
295
255
222
195
172
153
137
123
111
100
91
83
275
244
218
196
177
161
146
134
123
114
105
98
275
244
218
196
177
160
146
134
123
114
105
98
91
418
350
297
254
220
191
168
148
131
117
104
94
336
290
252
221
196
174
156
140
126
114
104
95
313
278
248
223
201
183
167
152
140
129
120
111
313
277
247
222
201
182
166
152
140
129
119
111
103
418
350
297
254
220
191
168
148
131
117
104
94
336
290
252
221
196
174
156
140
126
114
104
95
313
278
248
223
201
183
167
152
140
129
120
111
313
277
247
222
201
182
166
152
140
129
119
111
103
418
350
297
254
220
191
168
148
131
117
104
94
336
290
252
221
196
174
156
140
126
114
104
95
313
278
248
223
201
183
167
152
140
129
120
111
313
277
247
222
201
182
166
152
140
129
119
111
103
468
392
333
285
246
214
188
166
147
131
117
105
376
325
283
248
219
195
174
156
141
128
116
106
351
311
278
249
225
205
187
171
157
145
134
124
350
311
277
249
225
204
186
171
157
145
134
124
116
468
392
333
285
246
214
188
166
147
131
117
105
376
325
283
248
219
195
174
156
141
128
116
106
351
311
278
249
225
205
187
171
157
145
134
124
350
311
277
249
225
204
186
171
157
145
134
124
116
468
392
333
285
246
214
188
166
147
131
117
105
376
325
283
248
219
195
174
156
141
128
116
106
351
311
278
249
225
205
187
171
157
145
134
124
350
311
277
249
225
204
186
171
157
145
134
124
116
518
434
368
316
273
237
208
183
163
145
129
116
416
359
313
275
243
216
193
173
156
142
129
118
388
344
307
276
249
226
206
189
174
160
148
138
388
344
307
276
249
226
206
189
174
160
148
138
128
518
434
368
316
273
237
208
183
163
145
129
116
416
359
313
275
243
216
193
173
156
142
129
118
388
344
307
276
249
226
206
189
174
160
148
138
388
344
307
276
249
226
206
189
174
160
148
138
128
518
434
368
316
273
237
208
183
163
145
129
116
416
359
313
275
243
216
193
173
156
142
129
118
388
344
307
276
249
226
206
189
174
160
148
138
388
344
307
276
249
226
206
189
174
160
148
138
128
568
476
404
346
299
260
228
201
178
159
142
127
457
394
343
301
266
237
212
190
172
155
141
129
426
378
337
303
274
248
226
207
191
176
163
151
426
377
337
303
273
248
226
207
191
176
163
151
141
568
476
404
346
299
260
228
201
178
159
142
127
457
394
343
301
266
237
212
190
172
155
141
129
426
378
337
303
274
248
226
207
191
176
163
151
426
377
337
303
273
248
226
207
191
176
163
151
141
568
476
404
346
299
260
228
201
178
159
142
127
457
394
343
301
266
237
212
190
172
155
141
129
426
378
337
303
274
248
226
207
191
176
163
151
426
377
337
303
273
248
226
207
191
176
163
151
141
Note: Shoring required at midspan in shaded areas.
TECHNICAL NOTES
Material Properties
1. The ICD-300 (INVERTED) is the IRD-300 roof deck
with embossments rolled into the web elements to
achieve the composite interlocking capacity
between the steel deck and concrete.
2. Steel deck section properties were calculated in
accordance with CSA S136-07.
3. Steel conforms to ASTM A653 SS Grade 33 and
A653M SS Grade 230 with Z275 (G90) and ZF75
(A25) surface coatings.
4. Concrete is based on normal density of 2300
3
kg/m (145 pcf) and having a minimum
compressive strength of 20 MPa (3 ksi).
Load Tables
1. Loads are maximum specified uniformly
2.
3.
4.
5.
6.
distributed loads resulting from human occupancy
and should not be used for concentrated loads.
Maximum specified load from load table must be
≥ [LL + 0.833DL];
Where LL = specified live load;
DL = specified dead load; 0.833 = 1.25/1.5
Loads greater than 10 kPa (200 psf) are commonly
the result of large concentrated moving loads.
In such cases, appropriate design consideration
should be used by the structural engineers.
The ICD-300 steel deck provides the positive
reinforcement for the simply supported composite
slab and no additional reinforcing steel is required.
To control shrinkage and temperature cracking, a
minimum steel wire mesh of 152 x 152 –
MW9.1/MW9.1 (6 x 6 - 10/10) is recommended as
per CSSBI S3-08.
Shoring requirements shown in shaded areas of
the load table were established in accordance with
CSSBI 12M-08.
To establish the shear-bond capacity of the ICD300 inverted composite slab system, laboratory
tests were carried out at the Structural Testing and
Research laboratory (STAR), Cambridge, Ontario
in accordance with CSSBI S2-08.
All technical information and load tables were
prepared by Dr. R.M. Schuster, Professor
Emeritus of Structural Engineering, University of
Waterloo, Ontario.
EXAMPLE (Imperial)
Determine the specified uniformly distributed live load
that can be placed on the IDEAL inverted composite
floor slab, given the following information:
Given:
•
•
•
•
•
•
Steel deck thickness = 0.036 in.
Yield strength = 33 ksi
3
Normal density concrete = 145 lb/ft
Overall slab depth = 6.5 in.
Triple span, each = 12 ft
Specified superimposed dead load,
DL = 32.5 psf
Solution:
The maximum specified load in (psf) from load table
must be ≥ [LL + (1.25/1.5)DL],
where
LL = specified live load
DL = specified superimposed dead load
From load table under 12 ft span, the maximum
specified load is 129 psf, therefore,
129 ≥ [LL + (1.25/1.5)32.5] and solving for LL,
LL = 102 psf
Since this is in the shaded area, one shore support is
required at mid-span in each span.
Note:
-The self-weight of the steel deck and concrete slab
have already been accounted for in the maximum
specified uniformly distributed load given in the
composite slab load table.
-Minimum Bearing Length “n” at end support is
1.5 x height of deck = 4.5”.
-At middle support use n=6”.
STEEL DECK SECTION PROPERTIES
Base Steel
Thickness
(mm)
0.762
0.914
1.219
1.524
Area of
Steel
(mm2 )
1306
1568
2090
2613
COMPOSITE SLAB INFORMATION
(per metre of width)
Mass
Section Modulus
Deflection
Z275
Midspan
Support
Inertia
(kg/m2 )
(x103mm3 ) (x103 mm3) (x106 mm4 )
10.5
24.0
23.4
1.15
12.6
30.3
30.0
1.39
16.7
42.9
41.3
1.85
20.8
53.6
52.7
2.32
(per metre of width)
Slab Depth, D (mm)
130
140
150
160
Slab weight (kPa)
2.44
2.67
2.89
3.12
3.35
Concrete Volume (m3/10m2)
0.99
1.09
1.19
1.39
170
1.29
MAXIMUM SPECIFIED UNIFORMLY DISTRIBUTED LOADS (kPa)
Slab Depth, D
(mm)
Base Steel Slab
Thickness Span
(mm)
(m)
2.2
2.4
2.5
2.6
2.8
3.0
0.762
3.2
3.4
3.5
3.6
3.8
4.0
2.2
2.4
2.5
2.6
2.8
3.0
0.914
3.2
3.4
3.5
3.6
3.8
4.0
2.5
2.6
2.8
3.0
3.2
3.4
1.219
3.5
3.6
3.8
4.0
4.2
4.4
2.6
2.8
3.0
3.2
3.4
3.5
3.6
1.524
3.8
4.0
4.2
4.4
4.5
4.6
130
140
Deck Span
150
Deck Span
160
170
Deck Span
Deck Span
Deck Span
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
12.1
9.9
9.0
8.3
7.0
5.9
5.1
4.4
4.1
3.8
3.3
2.9
13.7
11.3
10.4
9.5
8.1
7.0
6.1
5.3
5.0
4.7
4.1
3.7
12.9
12.0
10.3
9.0
7.9
7.0
6.6
6.3
5.6
5.1
4.6
4.2
12.0
10.3
9.0
7.9
7.0
6.6
6.3
5.6
5.1
4.6
4.2
4.0
3.9
12.1
9.9
9.0
8.3
7.0
5.9
5.1
4.4
4.1
3.8
3.3
2.9
13.7
11.3
10.4
9.5
8.1
7.0
6.1
5.3
5.0
4.7
4.1
3.7
12.9
12.0
10.3
9.0
7.9
7.0
6.6
6.3
5.6
5.1
4.6
4.2
12.0
10.3
9.0
7.9
7.0
6.6
6.3
5.6
5.1
4.6
4.2
4.0
3.9
12.1
9.9
9.0
8.3
7.0
5.9
5.1
4.4
4.1
3.8
3.3
2.9
13.7
11.3
10.4
9.5
8.1
7.0
6.1
5.3
5.0
4.7
4.1
3.7
12.9
12.0
10.3
9.0
7.9
7.0
6.6
6.3
5.6
5.1
4.6
4.2
12.0
10.3
9.0
7.9
7.0
6.6
6.3
5.6
5.1
4.6
4.2
4.0
3.9
13.3
10.9
10.0
9.1
7.7
6.5
5.6
4.8
4.5
4.2
3.7
3.2
15.1
12.5
11.5
10.5
9.0
7.7
6.7
5.9
5.5
5.2
4.6
4.1
14.3
13.2
11.4
10.0
8.8
7.8
7.3
6.9
6.2
5.6
5.1
4.7
13.2
11.4
9.9
8.7
7.8
7.3
6.9
6.2
5.6
5.1
4.7
4.5
4.3
13.3
10.9
10.0
9.1
7.7
6.5
5.6
4.8
4.5
4.2
3.7
3.2
15.1
12.5
11.5
10.5
9.0
7.7
6.7
5.9
5.5
5.2
4.6
4.1
14.3
13.2
11.4
10.0
8.8
7.8
7.3
6.9
6.2
5.6
5.1
4.7
13.2
11.4
9.9
8.7
7.8
7.3
6.9
6.2
5.6
5.1
4.7
4.5
4.3
13.3
10.9
10.0
9.1
7.7
6.5
5.6
4.8
4.5
4.2
3.7
3.2
15.1
12.5
11.5
10.5
9.0
7.7
6.7
5.9
5.5
5.2
4.6
4.1
14.3
13.2
11.4
10.0
8.8
7.8
7.3
6.9
6.2
5.6
5.1
4.7
13.2
11.4
9.9
8.7
7.8
7.3
6.9
6.2
5.6
5.1
4.7
4.5
4.3
14.6
12.0
10.9
10.0
8.4
7.2
6.1
5.3
4.9
4.6
4.0
3.5
16.5
13.7
12.5
11.5
9.8
8.4
7.3
6.4
6.0
5.6
5.0
4.4
15.6
14.5
12.5
10.9
9.6
8.5
8.0
7.6
6.8
6.2
5.6
5.1
14.5
12.5
10.9
9.6
8.5
8.0
7.6
6.8
6.2
5.6
5.1
4.9
4.7
14.6
12.0
10.9
10.0
8.4
7.2
6.1
5.3
4.9
4.6
4.0
3.5
16.5
13.7
12.5
11.5
9.8
8.4
7.3
6.4
6.0
5.6
5.0
4.4
15.6
14.5
12.5
10.9
9.6
8.5
8.0
7.6
6.8
6.2
5.6
5.1
14.5
12.5
10.9
9.6
8.5
8.0
7.6
6.8
6.2
5.6
5.1
4.9
4.7
14.6
12.0
10.9
10.0
8.4
7.2
6.1
5.3
4.9
4.6
4.0
3.5
16.5
13.7
12.5
11.5
9.8
8.4
7.3
6.4
6.0
5.6
5.0
4.4
15.6
14.5
12.5
10.9
9.6
8.5
8.0
7.6
6.8
6.2
5.6
5.1
14.5
12.5
10.9
9.6
8.5
8.0
7.6
6.8
6.2
5.6
5.1
4.9
4.7
15.8
13.0
11.9
10.8
9.1
7.8
6.7
5.8
5.4
5.0
4.4
3.8
17.9
14.9
13.6
12.5
10.7
9.2
8.0
7.0
6.5
6.1
5.4
4.8
17.0
15.7
13.6
11.8
10.4
9.2
8.7
8.3
7.4
6.7
6.1
5.5
15.7
13.6
11.8
10.4
9.2
8.7
8.2
7.4
6.7
6.1
5.5
5.3
5.1
15.8
13.0
11.9
10.8
9.1
7.8
6.7
5.8
5.4
5.0
4.4
3.8
17.9
14.9
13.6
12.5
10.7
9.2
8.0
7.0
6.5
6.1
5.4
4.8
17.0
15.7
13.6
11.8
10.4
9.2
8.7
8.3
7.4
6.7
6.1
5.5
15.7
13.6
11.8
10.4
9.2
8.7
8.2
7.4
6.7
6.1
5.5
5.3
5.1
15.8
13.0
11.9
10.8
9.1
7.8
6.7
5.8
5.4
5.0
4.4
3.8
17.9
14.9
13.6
12.5
10.7
9.2
8.0
7.0
6.5
6.1
5.4
4.8
17.0
15.7
13.6
11.8
10.4
9.2
8.7
8.3
7.4
6.7
6.1
5.5
15.7
13.6
11.8
10.4
9.2
8.7
8.2
7.4
6.7
6.1
5.5
5.3
5.1
17.1
14.0
12.8
11.7
9.9
8.4
7.2
6.2
5.8
5.4
4.7
4.2
19.3
16.1
14.7
13.5
11.5
9.9
8.6
7.5
7.0
6.6
5.9
5.2
18.4
17.0
14.7
12.8
11.2
10.0
9.4
8.9
8.0
7.2
6.6
6.0
17.0
14.6
12.8
11.2
10.0
9.4
8.9
8.0
7.2
6.6
6.0
5.7
5.5
17.1
14.0
12.8
11.7
9.9
8.4
7.2
6.2
5.8
5.4
4.7
4.2
19.3
16.1
14.7
13.5
11.5
9.9
8.6
7.5
7.0
6.6
5.9
5.2
18.4
17.0
14.7
12.8
11.2
10.0
9.4
8.9
8.0
7.2
6.6
6.0
17.0
14.6
12.8
11.2
10.0
9.4
8.9
8.0
7.2
6.6
6.0
5.7
5.5
17.1
14.0
12.8
11.7
9.9
8.4
7.2
6.2
5.8
5.4
4.7
4.2
19.3
16.1
14.7
13.5
11.5
9.9
8.6
7.5
7.0
6.6
5.9
5.2
18.4
17.0
14.7
12.8
11.2
10.0
9.4
8.9
8.0
7.2
6.6
6.0
17.0
14.6
12.8
11.2
10.0
9.4
8.9
8.0
7.2
6.6
6.0
5.7
5.5
Note: Shoring required at midspan in shaded areas.
TECHNICAL NOTES
Material Properties
1. The ICD-300 (INVERTED) is the IRD-300 roof deck
with embossments rolled into the web elements to
achieve the composite interlocking capacity
between the steel deck and concrete.
2. Steel deck section properties were calculated in
accordance with CSA S136-07.
3. Steel conforms to ASTM A653 SS Grade 33 and
A653M SS Grade 230 with Z275 (G90) and ZF75
(A25) surface coatings.
4. Concrete is based on normal density of 2300
3
kg/m (145 pcf) and having a minimum
compressive strength of 20 MPa (3 ksi).
Load Tables
1. Loads are maximum specified uniformly
2.
3.
4.
5.
6.
distributed loads resulting from human occupancy
and should not be used for concentrated loads.
Maximum specified load from load table must be
≥ [LL + 0.833DL];
Where LL = specified live load;
DL = specified dead load; 0.833 = 1.25/1.5
Loads greater than 10 kPa (200 psf) are commonly
the result of large concentrated moving loads.
In such cases, appropriate design consideration
should be used by the structural engineers.
The ICD-300 steel deck provides the positive
reinforcement for the simply supported composite
slab and no additional reinforcing steel is required.
To control shrinkage and temperature cracking, a
minimum steel wire mesh of 152 x 152 –
MW9.1/MW9.1 (6 x 6 - 10/10) is recommended as
per CSSBI S3-08.
Shoring requirements shown in shaded areas of
the load table were established in accordance with
CSSBI 12M-08.
To establish the shear-bond capacity of the ICD300 inverted composite slab system, laboratory
tests were carried out at the Structural Testing and
Research laboratory (STAR), Cambridge, Ontario
in accordance with CSSBI S2-08.
All technical information and load tables were
prepared by Dr. R.M. Schuster, Professor
Emeritus of Structural Engineering, University of
Waterloo, Ontario.
EXAMPLE (Metric)
Determine the specified uniformly distributed live load
that can be placed on the IDEAL inverted composite
floor slab, given the following information:
Given:
•
•
•
•
•
•
Steel deck thickness = 0.914 mm
Yield strength = 230 MPa
3
Normal density concrete = 2300 kg/m
Overall slab depth = 160 mm
Triple span, each = 3.5 m
Specified superimposed dead load,
DL = 1.60 kPa
Solution:
The maximum specified load in (kPa) from load table
must be ≥ [LL + (1.25/1.5)DL],
where
LL = specified live load
DL = specified superimposed dead load
From load table under 3.5 m span, the maximum
specified load is 6.5 kPa, therefore,
6.5 ≥ [LL + (1.25/1.5)1.6] and solving for LL,
LL = 4.77 kPa
Since this is in the shaded area, one shore support is
required at mid-span in each span.
Note:
-The self-weight of the steel deck and concrete slab
have already been accounted for in the maximum
specified uniformly distributed load given in the
composite slab load table.
-Minimum Bearing Length “n” at end support is
1.5 x height of deck = 114mm.
-At middle support use n=150mm.
Acoustic roof deck is designed to serve as a sound-absorbing ceiling or an interior wall cladding
(e.g. school gymnasium, training facilities, airports and others) while maintaining most of its
structural properties. Using the IRD-150 and IRD-151 load table, the designer is urged to reduce the
vertical load resistance by 5%. The webs of the roof deck are perforated with 1/8” (3mm) diameter
holes staggered 3/8” (9.53mm) on center.
The sound reduction is achieved by fibreglass strips placed between the perforated webs. These
strips can be supplied by Ideal Roofing and are available as a special order.
IRD-150 and IRD-151 Acoustic Deck is available in 22 gauge (0.030”/0.762mm), 20 gauge
(0.036”/0.914mm) and 18 gauge (0.048”/1.219mm) in galvanized G90 (Z275), galvanized G60
(Z180), galvanneal (satin coat) A25 (ZF075) and pre-painted.
Acoustic roof deck is designed to serve as a sound-absorbing ceiling or an interior wall cladding
(e.g. school gymnasium, training facilities, airports and others) while maintaining most of its
structural properties. Using the IRD-300 and IRD-301 load table, the designer is urged to reduce
the vertical load resistance by 10%. The webs of the roof deck are perforated with 1/8” (3mm)
diameter holes staggered 3/8” (9.53mm) on center.
The sound reduction is achieved by fibreglass strips placed between the perforated webs. These
strips can be supplied by Ideal Roofing and are available as a special order.
IRD-300 and IRD-301 Acoustic Deck is available in 22 gauge (0.030”/0.762mm), 20 gauge
(0.036”/0.914mm) and 18 gauge (0.048”/1.219mm) in galvanized G90 (Z275), galvanized G60
(Z180), galvanneal (satin coat) A25 (ZF075) and pre-painted.