BIG-8 REFLECTIVE DUCT INSULATION

Transcription

BIG-8 REFLECTIVE DUCT INSULATION
TECHNICAL DATA SHEET
BIG-8 REFLECTIVE DUCT INSULATION
www.rFOIL.com
Product Description:
rFOIL™ Big-8 Reflective Duct Insulation consist of two layers of thick
polyethylene bubble pack reflective insulation separated by 2-inch wide strips of
bubble pack insulation. This product has on it a code certification strip that
identifies the brand name and pertinent testing information for duct applications.
This inspector friendly tape means no hassles at the jobsite and peace of mind
for installers.
The Big-8 Reflective Duct Insulation has been tested to an R-8 and is
classified as Class 1/Class A in accordance with the ASTM E84-09 fire test
standard. The product was mounted in accordance to ASTM-E2599-08.
REFLECTIVE SURFACE
BUBBLE
BUBBLE
REFLECTIVE SURFACE
BUBBLE
Stock Sizes Available (Rolls):
Size
Part No.
48" X 50'
2280-48-050
Features:
- R-Value 8
- Approved vapor barrier protection
- Inhibits condensation, mould and fungi growth
- Improves HVAC system efficiency
- No foam corner spacers needed
- Thermal performance unaffected by moisture
- Non-Toxic / Non-Carcinogenic
Applications:
- Duct Insulation without spacers
(R-8)
Physical Properties
Test
Value
THERMAL RESISTANCE
TEMPERATURE RANGE
FIRE RATING
EMISSIVITY
REFLECTIVITY
WATER VAPOR PERMEABILITY
RESISTANCE TO FUNGI & BACTERIA
BLEEDING and DELAMINATION
PLIABILITY
ASTM C335
ASTM C411
ASTM E84-09
ASTM C1371
ASTM E903
ASTM E96
ASTM C1338-08
ASTM C1224-03
ASTM C1224-03
TEMPERATURE and HUMIDITY
RESISTANCE
ASTM C1258
R-8 with BUBBLE SPACERS
250 +/- 25OF
CLASS 1 / CLASS A
0.04
0.096
0.029 Perms
DOES NOT PROMOTE GROWTH
NO BLEEDING or DELAMINATION
NO CRACKING
Evidence of Delamination - NONE
Evidence of Corrosion - NONE
Loss of Metallaization - MINIMAL
279 Humberline Drive Etobicoke, ON M9W 5T6
In CANADA: 1-800-837-8961 In US: 1-888-887-3645
Local: 416-798-1340 Fax: 416-798-1342 Email: [email protected]
Visit our Website: www.rfoil.com
INSTALLATION SHEET
BIG-8 DUCT INSULATION (Duct Insulation continued)
INSTALLATION METHOD #1 - R-8 Insulation with Spacer Strips
1.
2.
3.
4.
5.
Create spacers by attaching 2” wide strips of rFOIL Duct Insulation
(spacers also sold separately). Spacers should be wrapped around
the perimeter at approximately 2' intervals.
Wrap rFOIL BIG-8 Insulation around the duct with spacers and
pull hand-tight (for and R-8 value). Ensure that the printed
Code Certification Strip, taped the entire length of the roll, is
facing out. This information must be visible to inspectors.
Tape all seams and joints using rFOIL Metalized Tape, specially
formulated to adhere to rFOIL Duct Insulation.
- Item Code 15212 (2” x 150')
- Item Code 15213 (3” x 150')
- Use of any tape other than the rFOIL items above will void the
manufacturer's warranty.
Properly installed, the spacers will provide a consistent airspace
around the duct.
Repeat the above steps for the entire length of the ductwork.
www.rFOIL.com
NEW!
BIG 8
Reflective Tape
Spacer Strip
Big-8 Spacer Wrap for an R-8 Value
(With Spacer Strips)
INSTALLATION METHOD #2 - R-6 Insulation for Ducts - Direct Wrap
1. This method does not require spacer strips. However, it is recommended that the product be
loosely wrapped around the duct.
2. Determine the exact perimeter around the duct.
3. Wrap rFOIL BIG-8 Insulation around the duct (without spacers for an R-6 value).
4. For optimal performance, wrap the duct with material length that is approximately
5% longer than the actual duct perimeter. Ensure that the printed Code
Certification Strip, taped the entire length of the roll, is facing out. This
information must be visible to inspectors.
5. Installed loosely, this will create small airspaces between the outer duct wall and
the insulation. These pockets of air will enhance the thermal value of the
system.
6. Tape all seams and joints using rFOIL Metalized Tape, specially formulated to
adhere to rFOIL Duct Insulation.
- Item Code 15212 (2” x 150')
- Item Code 15213 (3” x 150')
- Use of any tape other than the rFOIL items above will void the manufacturer's warranty.
Repeat the above steps for the entire length of the ductwork.
Big-8 Direct Wrap for an R-6 Value
7. Repeat the above steps for the entire length of the ductwork.
BIG 8
(Without Spacer Strips)
SUGGESTED PRODUCTS FOR THIS APPLICATION:
rFOIL™ REFLECTIVE INSULATION
rFOIL™ REFLECTIVE TAPE
› 2280-48-050
› 15212 (2" x 150'),
15213 (3" x 150')
TM
*
Check local building codes for compliance before installation. This installation sheet is intended solely to illustrate the proper location and placement of rFOIL
Reflective Insulation products in specific constructions applications. They are not intended to illustrate proper construction methods (which is ultimately the
TM
responsibility of the builder or contractor). The installation instructions are only recommendations relating to the location and placement of rFOIL Reflective
TM
Insulation products, and rFOIL makes no claims that these construction systems are universally accurate.
TM
** All warranties and performance estimates are void if rFOIL Reflective Insulation products are used in exterior applications, or in non-enclosed systems or
buildings.
TM
*** Exercise caution when using rFOIL Reflective Insulation products near and around electrical wiring and devices.
279 Humberline Drive Etobicoke, ON M9W 5T6
In CANADA: 1-800-837-8961 In US: 1-888-887-3645
Local: 416-798-1340 Fax: 416-798-1342 Email: [email protected]
Visit our Website: www.rfoil.com
MATERIAL SAFETY DATA SHEET
TM
rFOIL BIG-8 Duct Insulation
www.rFOIL.com
SEPTEMBER 2009
SECTION 1: PRODUCT IDENTIFICATION
NAME:
rFOIL BIG-8 DUCT INSULATION
REFLECTIVE DUCT INSULATION R-8
DESCRIPTION:
MANUFACTURER:
COVERTECH FABRICATING INC.
ADDRESS:
279 HUMBERLINE DRIVE
ETOBICOKE, ONTARIO, CANADA
M9W 5T6
TELEPHONE:
800-837-8961
FAX:
416-798-1342
SECTION 2: HAZARDOUS INGREDIENTS
THESE PRODUCTS ARE NOT CONSIDERED TO BE HAZARDOUS, AND ARE NOT CLASSIFIED AS
'CONTROLLED PRODUCTS'. THEY ARE COMPRISED PRINCIPALLY OF POLYETHYLENE AND
METALIZED ALUMINUM THAT ARE NON HAZARDOUS.
SECTION 3: PHYSICAL DATA
BOILING POINT:
TEMPERATURE RANGE:
WATER VAPOUR PERM:
APPEARANCE:
ODOUR:
NOT APPLICABLE
250 +/- 25OF
< 0.029 PERMS
FLEXIBLE SHEET
NONE
SECTION 4: FIRE & EXPLOSION DATA
FLAME SPREAD:
0 (ASTM E84-09)
SMOKE DEVELOPMENT:
50 (ASTM E84-09)
EXTINGUISHING MEDIA:
CO2, DRY CHEMICAL, WATER OR FOAM
USUAL FIRE HAZARDS: BARRIER FOIL MATERIALS ARE NOT HIGHLY
FLAMMABLE, BUT IN CONTACT WITH FLAME THEY WILL MELT AND BURN.
SECTION 5: REACTIVITY DATA
STABILITY:
PRODUCTS ARE STABLE AND INERT TO MOST CHEMICALS.
NONE CAUSE A VIOLENT REACTION.
INCOMPATIBILITY:
CONSULT WITH MANUFACTURER PRIOR TO USING AS A
CONTAINMENT OR BARRIER FOR CHEMICALS OTHER THAN WATER.
SECTION 6: HEALTH HAZARD DATA
INHALATION:
NONE
EYES & SKIN:
NONE
INGESTION:
PRODUCTS SHOULD NOT BE EATEN OR KEPT IN CONTACT WITH FOOD
SECTION 7: SPECIAL PRECAUTION & HANDLING INFORMATION
GENERALLY THE PRODUCTS REQUIRE NO SPECIAL PRECAUTIONS WHEN HANDLING. HOWEVER THE
PRODUCTS MAY BECOME SLIPPERY WHEN WET, AND CARE SHOULD BE TAKEN WHEN WALKING ON
THIS.
SECTION 8: FIRST AID MEASURES
NOT APPLICABLE
NOTE: THE INFORMATION CONTAINED IN THIS SHEET IS DISCLOSED IN GOOD FAITH AND IS PROVIDED TO THE BEST KNOWLEDGE
OF THE MANUFACTURER. NEVERTHELESS IT IS NOT A WARRANTY AND COVERTECH FABRICATING INC. ASSUMES NO
RESPONSIBILITY FOR DAMAGES INCURRED FROM THE USE OR INABILITY TO USE THE PRODUCT
279 Humberline Drive Etobicoke, ON M9W 5T6
In CANADA: 1-800-837-8961 In US: 1-888-887-3645
Local: 416-798-1340 Fax: 416-798-1342 Email: [email protected]
Visit our Website: www.rfoil.com