LIEBERT CHALLENGER 3000
AIR-COOLED SYSTEM
PG1
Job Name
T-MOBILE - OFCI - DENVER, CO - AIR
Model
Quantity
Date
Invoice #
Purchaser
P.O. #
Tag #
Submitted By
BU042ADADEI / MCS028E7AD
3 (Three) / 3 (Three)
December 8, 2014
SWSG
114-068-H01-LIE-P2
Liebert Capitol Office – Jim Grant
Rev 10/10
LIEBERT CHALLENGER
ENGINEERING SPECIFICATION SHEET
Air-Cooled Systems
Project Name:
Date:
Reference No.:
Submitted By:
T-MOBILE - OFCI - DENVER, CO - AIR
December 8, 2014
Q02212338
Liebert Capitol Office – Jim Grant
Model Number: BU042ADADEI
Quantity: 3
Condenser Model Number: MCS028E7AD Quantity: 3
ELECTRICAL SUPPLY REQUIREMENTS
Liebert Room Unit: 460 Volts, 3 Phase, 60 Hertz, 19.8 Full Load Amps, 24.4 Wire Sizing Amps, 25.0 Over-Current Protection
Device, 65,000 Amps Short Circuit Current Rating (SCCR)
Air-Cooled Condenser: 460 Volts, 3 Phase, 60 Hertz, 1.4 Full Load Amps, 1.8 Wire Sizing Amps, 15.0 Over-Current Protection
Device
Liebert Lee-Temp Heater: 120 Volts, 1 Phase, 60 Hertz, 1.4 Full Load Amps, 1.8 Wire Sizing Amps, 15.0 Over-Current
Protection Device
CABINET SECTION
·
Upflow Unit
·
Front Return
·
Unit Color: Main: Z-0420 (IBM Charcoal)
NET CAPACITY DATA
·
75ºF (23.9ºC) DB – 61.1ºF (16.1ºC) WB
·
45% RH
·
Total Capacity: 40,600 BTU/hr (11.9 kW)
·
Sensible Capacity: 35,300 BTU/hr (10.3 kW)
EVAPORATOR FAN SECTION
·
Fan Motor: 0.75 HP (0.56 kW)
·
High Efficiency Motor
·
Air Volume: 1,800 CFM (3,060 CMH)
·
External Static Pressure: 0.3 Inches of Water (74.7 Pa)
COMPRESSOR SECTION
·
One Digital Scroll Compressor with Unloading Solenoid Valve, R-407C Refrigerant
·
Crankcase Heater
HUMIDIFIER SECTION
·
Infrared with Autoflush Humidification – Capacity: 11.0 lbs/hr (5.0 kg/hr) / 4.8 kW
REHEAT SECTION
·
Electric Reheat – Capacity: 33,400 BTU/hr ( 9 kW) (Includes Fan Motor)
·
Number of Stages: 2
EVAPORATIVE COIL
·
Coil Face Area: 6.67 sq. ft. (0.62 sq. m.)
·
Rows of Coil: 3
FILTER SECTION
(Disposable Type - Efficiency based on ASHRAE 52.2)
·
Size: 28.5 in.(724 mm) X 29.5 in.(749mm)
·
4" MERV 8 Filter
·
Extra Filter Sets; Quantity: 1 (One)
MICROPROCESSOR CONTROLER
·
Liebert iCOM microprocessor with Large Graphic Display
·
Display Language is English
MC CONDENSER SECTION
·
Design Ambient: 95ºF (35ºC)
·
Platform Size: Small
·
Control Fan Type: Premium Control & EC Fan
·
Liebert Lee-Temp Receiver and Head Pressure Control
·
Domestic Packaging
PG2
Rev 10/10
·
·
·
Non-Coated Coil
18” High Aluminum Legs
Standard Sound Level
UNIT WEIGHT
·
Module: 615 lbs (279 kg)
·
Condenser (Net): 154 lbs (70 kg)
ADDITIONAL EQUIPMENT
·
Dual Float Condensate Pump
·
Locking Disconnect Switch
·
Reheat and Humidifier Lockout
·
IS-UNITY-DP, Intellislot Dual Protocol Card; Quantity: 1 (One) Unit
·
Smoke Sensor
·
Remote Shutdown Terminals
·
Common Alarm Contacts
·
9” (228 mm) High Floorstand
·
LT410, Point Leak Sensor; Quantity: 1 (One) Per Unit
·
Damper Motor Control Circuit. Quantity: 1 (One) Per Unit
·
1 (One) Year Limited Labor Warranty
·
2 (Two) Years Parts Only Warranty
·
2 (Two) Years Compressor Warranty
PG3
Rev 10/10
LIEBERT BLOWER SELECTION PROGRAM
Page 1 of 1
Liebert Corporation
1050 Dearborn Drive, P.O. Box 29186
Columbus, OH 43229 USA
Blower Selection Program
Version 3.0
12/8/2014
Sales Person:
Sales Office:
Office Address:
Office Phone Number:
Project:
Project Location:
Unit Type
System Type
System Hertz
Description
Model
ACFM
SCFM
Motor Efficiency
Main Filter
Pre-Filter
Reheat
Air Return
Air Supply
Plenum
OK
Unit System: English
Upflow, Challenger
Air Cooled
60
BU - DX Cooling
042A
Standard : 1800
1800
Standard
Merv 8 Std. - 4 inch (102 mm)
None
Electric
Front
Top
None
Blower Model
Number of Fans
Operating HP
Motor HP
RPM
Static Efficiency
TSP, in. H20
ESP, in. H20
A12-9AT
1
0.49
0.75
752
0.46
0.79
0.30
ASHRAE 127-2007
___ Fan Curve _ _ Operating hp
OK
Save A Copy
Copyright © 2014 Liebert Corporation. A division of Emerson
Notice and Conditions
| Contacts
http://applications.liebert.com/BlowerWeb/frmBlower.asp
12/8/2014
AIR COOLED LIEBERT CHALLENGER 3000 MODELS
STANDARD FEATURES
65,000 AMP SHORT CIRCUIT CURRENT RATING (SCCR) The 60Hz electrical panel provides 65kA SCCR. Certain features or
combinations of features may reduce the rating; contact factory for limitations.
COMPRESSOR WITH HOT GAS BYPASS Scroll with a suction gas cooled motor, internal centrifugal oil pump, vibration isolating
mountings, internal thermal overloads, manual reset high pressure switch, and operates at 3500 RPM @ 60 HZ and 2900 RPM @
50 HZ. Factory piped hot gas solenoid valve and externally equalized regulating valve in the refrigerant circuit.
REFRIGERATION SYSTEM Single refrigeration circuit, includes a liquid line filter drier, refrigerant sight glass with moisture indicator,
adjustable externally equalized expansion valve, and liquid line solenoid valve.
COOLING COIL A-frame/V-frame coil design is constructed of copper tubes and aluminum fins. A stainless steel drain pan is
provided.
FAN Centrifugal type, double width, double inlet, with lifetime lubricating self aligning ball bearings rated at a minimum life of 100,000
hours. The motor operates at 1750 RPM for 60 HZ and 1450 RPM for 50 HZ. The drive package is variable speed, sized for 200%
of the fan motor horsepower (the motor is on an adjustable base). The fan draws air through the coil. The fan assembly is located
on an isolated fan deck.
FILTER shall be deep pleated 2” ASHRAE 52.2 MERV 8 rating (40% ASHRAE 52.1) located within the cabinet, and accessible from
the front of the unit.
CABINET AND FRAME Custom powder painted steel panels with 1” (25.4mm), 1 1/2 lbs. (.68kg) insulation. A hinged control access
panel opens to a second front panel which is a protection enclosure for high voltage components. The frame corner posts are
constructed of 14 gauge MIG welded steel. The frame is painted with a powder coat finish to protect against corrosion. The unit is
totally front accessible including any component removal.
HUMIDIFIER High intensity infrared quartz lamps over a stainless steel humidifier pan. An automatic water supply system maintains
water level in the pan and a timed flush system greatly reduces mineral precipitation, and is field adjustable to change the cycle
time.
ELECTRIC REHEAT Electric low watt density 304 stainless steel fin tubular electric reheat elements provide two stages of reheat to
control room dry bulb temperature.
DPN000347
REV 01/12
REV 3
AIR COOLED LIEBERT CHALLENGER 3000 MODELS
OPTIONAL FEATURES (Refer to specification sheet for options supplied)
DIGITAL COMPRESSOR Scroll with a suction gas cooled motor, internal centrifugal oil pump, vibration isolating mountings, internal
thermal overloads, manual reset high pressure switch, unloading solenoid valve and piping and operates at 3500 RPM @ 60 Hz
and 2900 RPM @ 50 Hz.
CONDENSATE PUMP Has a minimum capacity of 100 GPH (379 l/h) at 20 ft. head (58 kPa). (Consult factory for 200V or 230V,
50Hz applications). Pump is complete with integral primary and secondary float switches, pump, motor assembly, and reservoir.
(Shipped loose for field installation on Downflow (BF) Units).
UNIT DISCONNECT SWITCH For 60Hz units: A “Locking-Type” fused disconnect switch is available. For 50Hz units: Two types of
non-fused disconnect switches are available, the “Locking-Type” and a “Non-Locking Type”. The “Non-Locking Type” consists of a
main unit switch operational from the outside of the unit. Access to the high voltage electric panel compartment can be obtained
with the switch in either the “on” or “off” position. The “Locking-Type” is similar except access to the high voltage electric panel
compartment can be obtained only with the switch in the “off” position.
FIRESTAT Is mounted in the unit with the sensing element in the return air flow. Upon activation the high temperature stat will
immediately shut down the entire unit.
SMOKE DETECTOR The smoke detector senses the return air, shuts down the unit upon detection, and sends visual and audible
alarm. Dry contacts are available for a remote customer alarm. This smoke detector is not intended to function as or replace any
room smoke detection system that may be required by local or national codes.
FILTERS The standard and optional filters are available with optional pre-filters. A 2” ASHRAE 52.2 MERV 8 (40% ASHRAE 52.1) prefilter, and 4” ASHRAE 52.2 MERV 8 (40% ASHRAE 52.1) or 4” ASHRAE 52.2 MERV 11 (60-65% ASHRAE 52.1) main filter may
be specified.
LIQUI-TECT SENSOR Is a solid state water sensor that has no moving parts and is hermetically sealed to keep out dust and dirt.
When the sensor detects the presence of moisture the alarm system is activated.
REMOTE TEMPERATURE AND HUMIDITY SENSORS Are provided in a vented case for mounting in the room to be conditioned.
Includes 30 ft. (9m), 60 ft. (18m), 90 ft. (27m), 120 ft. (36m), or 150 ft. (45m) of cable supplied for connecting sensors to unit.
FLOOR STAND Is constructed of MIG welded tubular steel and available in heights from 9” to 24” (229mm to 610mm) with vibration
isolation pads provided on the adjustable legs. An optional factory supplied turning vane is available for field installation if
desired.
PLENUM(S) 4 plenums are available for upflow units: 2 way, 3 way, or 4 way discharge and top duct connection. Each plenum is 18”
(457mm) high and constructed of steel with 1” (25.4mm), 1 1/2 Ib. (.68kg) insulation and is custom painted in unit matching
colors.
STEAM GENERATING CANISTER HUMIDIFIER This system is housed in a steel enclosure and includes a replaceable canister with
integral fill cup, fill and drain valves, and high water indicator. System automatically fills and drains as well as maintains the
required water level based on conductivity.
HEAVY GAUGE INDUSTRIAL PANELS Are 16 ga. outside panels and heavy duty gaskets which replace the standard 20 ga. Panels
and gaskets.
REHEAT/HUMIDIFIER LOCKOUT Includes the necessary relays to disable the reheat and humidifier from an external 24 volt signal.
SCR ELECTRIC REHEAT Is controlled by the unit microprocessor by pulsing the reheat elements for tight temperature control. Not
available in 575 volts.
HIGH EXTERNAL STATIC BLOWERS This blower/motor package is available only on upflow models where external static pressures
are up to 2.0 inches/500 Pa (60Hz) or 1.5 inches/370 Pa (50Hz). These blowers are rigidly mounted for ducting directly to the
blower housing. Heavy gauge panels are recommended with this option.
200K HOUR BEARINGS Lifetime lubricated self-aligning pillow-block ball bearings rated at a minimum L10 life of 200,000 hours;
available on upflow units only.
TWO (2) ADDITIONAL REMOTE SHUTDOWN TERMINALS Provides the customer with a total of three locations to remotely shut
down the unit.
TWO (2) EXTRA COMMON ALARM CONTACTS Provides the customer with a total of three sets of n/o contacts for remote indication
of unit alarms.
MAIN FAN AUXILIARY SWITCH Provides the unit with one n/o set of contacts to indicate that the motor/unit is on.
REMOTE HUMIDIFIER CONTACTS allow the unit’s humidity controller to control a humidifier outside the unit. Power to operate the
remote humidifier does not come from the Challenger unit.
INTELLISLOT ISWEB-LBDS CARD Provides 10/100 baseT Ethernet connectivity for unit monitoring and management. The
supported management interfaces include: SNMP for Network Management Systems and HTTP for web page viewing.
INTELLISLOT OC485-LBDS CARD Provides RS-485 Modbus network connectivity to Building Management Systems for unit
monitoring and management.
DPN000348
REV 11/11
REV 5
Liebert iCOM® Control System
Intelligent Communications & Monitoring
Large Graphic Display
(Unit or Wall-mounted)
Large Graphic Display shown in unit bezel
Large Graphic Display for Wall-Mounting
The Liebert iCOM® Large Graphic Display shall be microprocessor based with a 320x240 dot matrix graphic
monitor with control keys for user inputs mounted in an ergonomic, aesthetically pleasing housing. The display and
housing shall be viewable while the unit panels are open or closed. All parameter changes are password protected.
Wall-Mounted Large Graphic Displays shall be capable of being mounted on a wall and are provided with a power
supply. Wall-mounted displays can be added to a Unit-to-Unit network and remotely located from the cooling unit(s)
to provide convenient monitoring and control capabilities.
Large Graphic Display only features:
The Large Graphic Display provides all of the same features of the Small Graphic Display, plus Large Graphic
Display only features.
Event Log – Automatically stores the last 400 unit and system (U2U communication required) events (messages,
warnings, and alarms)
Spare Parts List - shows a list of key spare parts, their quantity and respective parts numbers
Unit Diary - A free field area where unit history may be stored for reference
View Network – Shows a summarized view of all the cooling units connected on a U2U network
Centralized Operation – View and configure any cooling unit on a U2U network from a Large Graphic Display
System View – View the averages of all operations being performed on the U2U network
Active Alarms on Status Screen – Last two unit/system events are displayed at the bottom of the Status Screen
for rapid identification of critical events without having to enter submenus
Full Text Descriptions – The large screen size eliminates the need for abbreviated text, simplifying user operation
DPN000794
REV 4/09
REV 2
Liebert iCOM® Control System
Intelligent Communications & Monitoring
Small Graphic Display
(Unit-mounted only)
Small Graphic Display shown in unit bezel
The Liebert iCOM® Small Graphic Display shall be microprocessor based with a 128x64 dot matrix graphic monitor with
control keys for user inputs mounted in an ergonomic, aesthetically pleasing housing. The display and housing shall be
viewable while the unit panels are open or closed. All parameter changes are password protected.
Small Graphic Display Features (additional features available with Large Graphic Display):
Temperature Control – Precision temperature control is maintained while maximizing efficiency based on a user entered
setpoint and tolerance.
Humidity Control – The dewpoint level of the room is monitored and controlled based on a user specified Relative
Humidity setpoint and tolerance.
Various Control Types – Selectable Proportional, PI (proportional-integral), PID (proportional-integral-derivative),
Intelligent control types for supply or return temperature; Relative, Compensated, or Predictive humidity control types.
These control types have been developed to maximize component life and maintain precise environmental control.
Unit Alarms – All unit alarms are annunciated, displayed on the screen, automatically recorded in the event log,
communicated to available IntelliSlot monitoring cards, and a red light flashes on the display
Event Log – Automatically stores the last 400 unit-only events (messages, warnings, and alarms).
Temperature and Humidity Graphs – Provides a graphical view of historical room conditions, selectable from 8 minutes
to 16 days
Automatic Component Sequencing – runtimes of multiple components within a unit are automatically balanced to
extend component life
Wellness / Maintenance – Monitors system components to warn of potential issues in advance (helps avoid unplanned
downtime) and prolong component life
Auto Restart – After a loss of power, a cooling unit will return to is previous operating status. Cooling units can be
stagger started to minimize system current draw.
IntelliSlot Cards – IntelliSlot cards allow for external unit communication and control
Service Contact Information – Local service or sales contact information can be conveniently stored
Upgradeable – Multiple units connected through a Unit-to-Unit network can be upgraded simultaneously or cascaded.
Unit-to-Unit (U2U) Communication – Communication via private Ethernet network allows for advanced control
functionality (Teamwork modes, sharing sensor data, Standby Rotation, Lead-Lag, and Cascade operation). Small
Graphic Displays can only configure the cooling unit they are physically connected to, while Large Graphic Displays can
configure any unit on the network.
Cascade – Standby units on a U2U network are automatically activated if active unit(s) cannot control the environment
Lead-Lag – A standby unit on a U2U network is automatically activated if an alarm occurs in an active unit
Standby Rotation – Standby units are rotated through a U2U network to balance system run hours. Units can be set to
automatically rotate daily, weekly, or monthly
Teamwork modes
• Mode No – Units share data but operate independently using local sensor readings
• Mode 1 – All units perform the same operation with the same intensity based on sensor readings from the entire
network; typically for rooms with balanced heat loads
• Mode 2 – All units perform the same operation with varying intensity based on sensor readings from the entire
network; typically for rooms with un-balanced heat loads
DPN000793
REV 4/09
REV 1 CABINET AND FLOOR PLANNING DIMENSIONAL DATA
LIEBERT CHALLENGER 3000
UPFLOW (BU) MODELS
STD 3 & 5T
Hi Static 3T
Hi Static 5T
UNIT
TOP VIEW
32 1/2"
(826mm)
30 1/2"
(775mm)
A
A
11 3/4 (299mm)
8 5/8 (219mm)
11 3/4 (299mm)
8 1/2"
(216mm)
9 5/8"
(244mm)
10 1/4"
(260mm)
13"
(330mm)
Standard Piping Location
12 1/2"
(318mm)
Projection of Display Bezel 5/8"
(16mm)
5 1/2"
(140mm)
32 1/2 "
(826mm)
Overall
Dimension
7 1/2 "
(191mm)
Filter Access
Through Top
18 "
(457mm)
32 1/2 "
(826mm)
Overall
Dimension
1 5/8"
(41mm)
30 1/2"
(775mm)
1 7/8"
(48mm)
32 1/2"
(826mm)
Standard Electrical Outlet
Location Through Unit
6 7/8 "
(175mm)
Standard Electrical Outlet
Location Through Plenum
Air Discharge Grille
29 3/4 "
(756mm)
Plenum available with:
-2, 3 or 4 grilles.
-Solid sides with a 7/8" (22mm)
duct flange on top.
1" (25mm)
FRONT &
SIDES
3/4" (19mm)
REAR
94 "
(2388mm)
2 1/2 "
(67mm)
29 "
(737mm)
UNIT DIMENSIONAL DATA
REAR VIEW
(rear return configuration)
50 HZ
MODELS
BU035E
BU059E
BU040A
BU065A
BU045W
BU070W
BU072C
BU101C
BK058G
DPN000350
UNIT WEIGHT
60 HZ
MODELS
BU036E
BU060E
BU042A
BU067A
BU046W
BU071W
BU068C
BU102C
BK061G
76 "
(1930mm)
1 3/4 "
(44mm)
LBS. (KG)
535 (243)
545 (247)
615 (279)
670 (304)
700 (318)
750 (340)
545 (247)
555 (252)
785 (356)
Blower Outlet with
1" (25.4mm) Flange
7/8" (22.2mm) Flange for
Duct or Plenum Connection
Return Air Louvers
Shaded area indicates a recommended
clearance of 34" (864mm) be provided
for component access. Right side
access suggested for "GLYCOOL" units.
UNIT DIMENSIONAL DATA
FRONT VIEW
(front return configuration)
REV 4/09
REV 1
PIPING: AIR COOLED MODELS
UPFLOW (BU) MODELS
Piping outlet locations through the plenum are
the same as the unit. See below for
descriptions and connection sizes.
Humidifier Water Supply Line
1/4" OD CU
Hot Water Return
5/8" OD CU (optional)
Hot Gas Refrigerant Line
5/8" OD CU on Models BU042A/BU040A
7/8" OD CU on Models BU067A/BU065A
Condensate Pump Line
1/2" OD CU
Used only if optional condensate
pump is ordered.
Liquid Refrigerant Line
3/8" OD CU on Models BU042A/BU040A
1/2" OD CU on Models BU067A/BU065A
Hot Water Supply
5/8" OD CU (optional)
iCOM Control
Panel
Condensate Drain
3/4" FPT
Field pitch a min. of 1/8" (3.2mm) per ft. (305mm). Units without
a condensate pump have a factory-supplied trap in the unit, so a
field trap should not be added. Units with a condensate pump will
require a field-supplied trap downstream from the pump. The
drain line must comply with all applicable codes. (If condensate
pump is ordered piping is out top of unit).
DPN000352
PIPING OUTLET LOCATIONS
(See Cabinet and Floor Planning
Dimensional Data for Piping
Opening Sizes.)
REV 9/08
REV 1
LIEBERT® CHALLENGER
ELECTRICAL FIELD CONNECTION DEFINITIONS AND LOCATIONS
1
1
2 50Hz Only
5
4
9
9
3
w/ MAIN DISCONNECT
Terminal Block*
(for customer connections)
14
75 76 94 95 96 97
w/o MAIN DISCONNECT
6
7
10
6
7
1
8
14
2 60Hz Only
1
8
10
11
37C38C37B 38B 37 38 24 50 51 55 56
13
91 92 93 1
12
2
3
16
4
Electrical Handy Box*
(factory installed with cover)
15
17
18
82 83 84 85 88 89
73
72
71
70
1)
Electric conduit knockouts on top and bottom of electric box. Knockout size 1 3/4” (44.5mm).
2)
Three phase connection. Electric service connection terminals when factory disconnect is NOT supplied.
3)
Three phase connection. Electric service connection terminals when factory disconnect switch is supplied.
4)
Factory installed disconnect switch (Optional). Fused disconnect switch provided on 60Hz units, non-fused disconnect switch
provided on 50Hz units.
5)
Factory installed main fuse block (60Hz only). Factory installed when fused disconnect switch is NOT supplied.
6)
Three phase electric service field supplied.
7)
Earth ground connection (50/60Hz). Connection terminal for field supplied earth grounding wire.
8)
Earth ground bar (50Hz only). Connection terminals with factory ground from each high voltage component for field supplied
earth grounding wire.
9)
Control and monitoring section of electric box.
10) Remote unit shutdown. Replace existing jumper between terminals 37 + 38 with normally closed switch having a minimum
75VA, 24VAC rating. Use field supplied Class 1 wiring. Two additional contact pairs available as an option (labeled as 37B &
38B, 37C & 38C). Replace existing jumper for appropriate pair as done for 37 & 38.
11) Remote Alarm Device (RAD) Connections. Field supplied 24V Class 1 wiring for special alarm. Connection made by adding
normally open contacts. Special alarm connections may be factory wired or field wired. See schematic, RADS1-4, for factory
wired special alarms. For field wired special alarms, use 24V Class 1 wiring to connect normally open contacts between
terminals 24 & 50, 24 & 51, 24 & 55, or 24 & 56.
12) Remote condensing unit connection. Field supplied 24V Class 1 wiring to remote condensing unit terminals 1, 2, 3, & 4 from
(R2) relay (split system only.)
13) Smoke detector alarm connections. Field supplied 24V Class 1 wiring to remote alarm circuits. Factory wired contacts from
optional smoke detector are #91-comm., #92-NO, and #93-NC.
14) Common alarm connection. Field supplied 24V Class 1 wiring to common alarm terminals 75 + 76 (and optional 94 + 95, and
96 + 97), which are factory connected to common alarm relay (R3).
15) Heat rejection connection. Field supplied 24V Class 1 wiring to interlock heat rejection from pigtails 70 + 71 which are factory
connected to compressor side switch (self contained units only) or to GLYCOOL relay (K11, GLYCOOL units only). On Dual Cool
units only, pigtails 72 + 73 connect auxiliary cooling source to GLYCOOL relay K11. See indoor and outdoor electric schematic
for more information.
16) Reheat and Humidifier Lockout. Optional emergency power lockout of reheat and/or humidifier: connections provided for
remote 24V AC source.
17) Main Fan Auxiliary Switch. Optional main fan auxiliary side switch. Terminals located in field wiring compartment for remote
indication that the evaporator fan motor/unit is on. Field to connect 24V maximum.
18) Optional Condensate Alarm (Dual Float Condensate Pump only). Relay terminals located in field wiring compartment for
remote indication.
*Located inside unit on top for Upflow and on base for Downflow.
NOTE: Refer to specification sheet for full load amp and wire size amp ratings.
DPN000354
REV 03/13
REV 4
ELECTRICAL FIELD CONNECTIONS - NETWORKING - U2U
UPFLOW LIEBERT CHALLENGER MODELS WITH iCOM CONTROLS
CAT5 Ethernet connections - field installed
Avoid routing near high voltage wiring.
Secure wiring to prevent damage and
use bushing or edge guard to avoid
sharp edges.
2
Loose
Cable
Ties
To
Display
To P64
To
Display
Use cutout on the electric
box to access control board.
Crossover
Coupler
Crossover
Coupler
A
DETAIL A
Ethernet
Wiring
Notes:
1. On units with the standard Small Graphics
Display, the customer connection point for
unit to unit (U2U) networking is to P64 on
the I/O Board.
Channel
Blower
Blockoff
Plate
2. On units with the optional Large Graphics Display, a
crossover coupler is provided for unit to unit (U2U)
networking. Unplug the red cable from P64 on the I/O
Board and connect to one side of the crossover
coupler. The first customer connection point is to
P64 on the I/O Board. The second customer
connection point is to the other side of the
crossover coupler. This connects the I/O Board and
display to the private U2U network.
DPN001733
Cable Tie To
Secure Wiring
PAGE 1 OF 3
REV 12/12
REV 2
ELECTRICAL FIELD CONNECTIONS - NETWORKING - U2U
UPFLOW LIEBERT CHALLENGER MODELS WITH iCOM CONTROLS
21
22
19
23
24
20
Terminal
Blocks
19) Opening for field wiring. Suggested entry point for HV field wiring to unit. Hole size O 2.5" (63.5 mm)
20) Opening for field wiring. Suggested entry point for LV field wiring to unit.
21) Vacant Intellisot. May contain optional Intellislot cards.
22) Populated Intellislot. Optional Intellislot cards may be placed in either of two supplied Intellislot locations.
23) Remote Temperature / Humidity Sensor connection location. 6-wire CAN cable supplied with optional remote T/H sensor.
24) Loose cable ties. Use to secure field supplied network cables to Intellislot.
DPN001733
PAGE 2 OF 3
REV 12/12
REV 2
ELECTRICAL FIELD CONNECTIONS - NETWORKING - U2U
UPFLOW LIEBERT CHALLENGER MODELS WITH iCOM CONTROLS
U2U NETWORKING CONNECTIONS - SMALL DISPLAY
P66
P64
Customer
Connection
Point
FIGURE 1
1. When Large Display is used, two cables are required.
2. To run both wires through the channel at the
same time, bundle them together as Figure 1 shows.
U2U NETWORKING CONNECTIONS - LARGE DISPLAY
On units with the optional Large Graphics Display, a
crossover coupler is provided for unit to unit (U2U)
networking. Unplug the red cable from P64 on the I/O
Board and connect to one side of the crossover
coupler. The first customer connection point is to
P64 on the I/O Board. The second customer
connection point is to the other side of the
crossover coupler. This connects the I/O Board and
display to the private U2U network.
When Large Display is used,
two cables are required.
P66
Customer
Connection
Points
DPN001733
P64
PAGE 3 OF 3
REV 12/12
REV 2
LIEBERT LIQUI-TECT® 410
Point Leak Detection Sensor
Product Specification Sheet
Description
The Liebert Liqui-tect 410 (LT410) provides a single-point detection
of leaks. The point detection sensor has two gold-plated sensing
probes to prevent corrosion resistance and to provide accurate
readings. The LT410 constantly monitors points for leaks, internal
faults and power failures and warns of any abnormal conditions.
Mounting brackets allow for sensor height adjustment and leveling.
The LT410 is the ideal solution for sensing leaks under a raised
computer floor or air conditioning drip pans. Two independent
outputs provide added flexibility with the capacity to signal both a
local alarm panel and a remote building management system or
external equipment, such as motorized water shut-off valves.
The LT410 is also ideally suited for the following:
Applications
Locations
• Glycol, Chilled Water Cooling
• Large-Scale Network Control
Centers
• Mechanical Equipment
Rooms
• Data Centers
• Sensitive Areas With
Overhead Piping
• Humidification Feed Water Piping
• Condensate Pumps and Drains
• Unit and Ceiling Auxiliary Drip Pans
• Overhead Piping Troughs
• Server Rooms - Closets
• Unattended Remote Shelters
• Industrial Process
Control Rooms
Dimensions - Top, Front & Side Views
TOP VIEW
FRONT VIEW
SIDE VIEW
5.85"
(148.5mm)
4.46"
(113.2mm)
Form-C relay outputs &
power wiring connection
6.35"
(161.2mm)
Adjustable
probe height
0.0–0.5"
(0.0–12.7mm)
Shipping weight: 2 Ibs (0.9 kg)
Mounting holes: #8 screws
1
2.25"
(57.2mm)
Specifications
Placement on Subfloor
Under Cooling Support Equipment
Liqui-tect 410 Sensor
Power
requirements
24 VAC 100 mA, 50/60 Hz,
3 VA (max.)
Dimensions, in. (mm) 6.35" x 2.25" x 4.46"
WxDxH
(161.2 x 57.2 x 113.2)
Weight (assembled)
2.0 lb. (0.9 kg)
Metal enclosure
NEMA 1, IP 30
To a Liebert
environmental
unit and
an optional*
monitoring
panel
Environmental Conditions
Operating
temperature
50°F to 104°F
(10°C to 40°C)
Operating
humidity
10% to 95% relative humidity
(non-condensing)
Operating
altitude
0 to 10,000 ft.
(0 to 3,048 m)
To external
power
supply or
directly
from
unit
(see
Power
Wiring
on 3)
Output Relays
Contact rating
2 Form-C;
3 A rating at 24 VAC
Agency Listings
UL
UL916
C-UL
C22.2, No. 205-M1983
CE
Yes
FCC Compliance
47 CFR, Part 15
LT410
* Output connections to external alarm monitoring panels
such as the Liebert contact closure alarm panels
Wiring Interconnections
(Circuits shown in powered, non-alarm state)
24 VAC @ 3A
24 VAC @ 3A
Class 2 Circuit Only
Class 2 Circuit Only
Class 2 Circuit Only
Gold-plated
probes
Height adjustable
0-0.5" (0-12.7mm)
NOTE: All power and alarm connections Class 2 circuits only
2
2-COM
@ 0.10A, 50-60 Hz, DC
2-NC
Alarm Contact Rating
2-NO
Alarm Contact Rating
1-COM
24 V, AC/DC
1-NC
Yellow Wires
1-NO
Orange Wires
Power
Red Wires
Power
Leak
detection
zone
(directly
beneath
unit)
Power Wiring
The LT410 is rated for 24 VAC, 50/60 Hz and 0.10 amp.
Figure 1 24V from Liebert environmental units to LT410
Challenger, Himod or
Liebert
Deluxe System/3,
MM2DS,
(8 Ton)
Challenger, Himod or Mini-Mate2 (8 ton)
TB1
TB1
LT460
LT410
Red
wires
TB1
T5 (24V)
T5 (24V)
Red
TB1-1
G5 (Ground)
(Ground)
G5
Red
TB1-2
Liebert MM2 (1 to 5 Ton)
LT460
TB1
Power Wiring
4V transformer of
(24V)
here are no
ated terminal
24V(Ground)
from Liebert
tions)
TB1-1
Environmental Unit to LT460
Liebert Deluxe Sys/3,
24V fromHimod
Transformer
Challenger,
or
MM2 (8 Ton)
T5 (24V)
connection
on main
controller
board of
Liebert unit
to LT460
Transformer
LT460
LT460
TB1
TB1
TB1
T5 (24V)
G5
TB1-2
Location of
TB1-1
TB1-1
TB1-2
TB1-2
From 24V
transformer
(Ground)
MM2 (1 to(15 to
Ton)
LiebertLiebert
Mini-Mate2
5 ton)
LT460
LT410
Red
wires
TB1
4V transformer of
(24V)
here are no
From 24V
ated terminal
transformer*
(Ground)
tions)
Red
TB1-1
Red
TB1-2
* Requires a 24V external transformer (there are
no designated terminal connections on the unit)
24V from Transformer to LT460
Figure 2 24V from transformer to LT410
Transformer
Transformer
LT460
LT410
Red
wires
TB1
From
24V24V
From
transformer
transformer
Red
TB1-1
Red
TB1-2
3
Wiring to Auxiliary Alarm Panels
The LT410 has two Form-C dry contact alarm output contacts: orange wires (1) and yellow wires (2). Each
contact is rated for 24 VAC at 3 amp.
Figure 3 LT410 to Liebert environmental units
Liebert Deluxe Sys/3,
Challenger, Himod or
MM2Liebert
(8 Ton) DS
LT460
LT410
Orange
TB2wires
Environmental
Env.unit
Unit
TB2-3
1-NC (N.C.)
TB2-2
1-COM(C)
24 (24V)
(24V)
TB2-1
1-NO (N.O.)
51
50, 51, 55 or 56
LT410
Liebert Deluxe System/3,
Liebert MM2 (1
to 5 Ton)or
Challenger,
Himod
Mini-Mate2 (8 ton)
LT460
Orange
TB2wires
Environmental
Env.unit
Unit
TB2-3
1-NC (N.C.)
TB2-2
1-COM(C)
TB1-1
(24V)
24 (24V)
TB2-1
1-NO (N.O.)
TB1-2
51, 55 or 56
OR
LT410
LT460
Orange
TB2wires
Liebert
Mini-Mate2
Liebert MM2
(1 to 5 Ton)
(1 to 5 ton)
Environmental
Env.unit
Unit
1-NC (N.C.)
TB2-3
1-COM(C)
TB2-2
(24V)
TB1-1 (24V)
1-NO (N.O.)
TB2-1
TB1-2 or TB1-3
TB1-3
Figure 4 LT410 to Liebert contact monitor panel
Liebert Contact
Liebert
contact
Monitor Panel
monitor
panel
LT460
LT410
Yellow
TB2wires
2-NC (N.C.)
TB2-3
Alarm panel
Panel
Input
contact
Contact
(N.O.)
(N.O.)
2-COM(C)
TB2-2
2-NO (N.O.)
TB2-1
Ordering Information
Product Number
Quantity
LT410
3
Description
Point Leak Detection Sensor
Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Telephone: 1-800-877-9222
Facsimile: 1-614-841-6022
www.liebert.com
© 2007 Liebert Corporation
All rights reserved throughout the world. Specifications subject
to change without notice.
® Liebert and the Liebert logo are registered trademarks of
Liebert Corporation. All names referred to are trademarks or
registered trademarks of their respective owners.
SL-31050_REV0_06-07
4
LIEBERT® INTELLISLOT® UNITY PLATFORM CARDS
Product Specification/Installation Sheet
Liebert Intellislot Unity cards are a form, fit and function replacement for several existing Liebert Intellislot Web and 485 cards.
RS-485 - Modbus RTU, BACnet
MSTP, YDN23; Building
Management System
RJ-45-Ethernet—Trellis;
Modbus TCP; BACnet IP;
SNMPv1, v2c, v3; Liebert
Protocol; HTTP; Building
Management System;
Network Management
System
Micro-USB AB
(future release)
IS-UNITY-DP
Reset Button
(Reboot or reset to
factory defaults)
Link
485
Activity
Liebert Sensor Network
(future release)
Description
The Liebert IntelliSlot Unity Platform brings SNMP, BACnet IP, BACnet MSTP, Modbus
TCP, Modbus RTU, YDN23 and Web management capability to many models of Emerson
Network Power’s power and cooling equipment. The cards employ Ethernet and RS-485
networks to monitor and manage a wide range of operating parameters, alarms and
notifications.
See Table 1 for equipment supported and Table 2 for communication protocols supported.
Additional Features
• SNMPv1, SNMPv2c and SNMPv3 with MIB-II support
• DHCP per RFC2131/2132
• HTTP/HTTPS 1.1
• Remote firmware updates via a Web browser
• BootP
• IPv4 and IPv6
Compatibility With Other Emerson Products and Communication Protocols
Table 1
Compatibility with Liebert equipment
Compatible with:
Liebert IntelliSlot Card
™
Liebert APM , Liebert APS , Liebert CRV™, Liebert CW™, Liebert Challenger 3000™
Liebert DCP™, Liebert Deluxe System/3™, Liebert DS™, Liebert DSE™, Liebert HPC™
Liebert HPC-S/M/R/W/Generic™, Liebert HPM™, Liebert NXC™, Liebert NXL™ *, Liebert NXR™,
Liebert PCW™/PDX™, Liebert PeX™ *, Liebert XDC™, Liebert XDP™, Liebert XDP-Cray™
Liebert IS-UNITY-DP
Liebert IS-UNITY-LIFE
Table 2
™
Liebert IntelliSlot card communication protocols
Communication Protocol
HTTP
HTTPS
Emerson
Protocol
Remote
Service
Delivery
Protocol
Liebert IS-UNITY-DP
(IS-UNITY-DP)
✔
✔
✔
✔
✔
✔
✔
✔
✔
Liebert IS-UNITY-LIFE
(IS-UNITY-LIFE)
✔
✔
✔
—
—
—
—
—
—
Liebert IntelliSlot
Card (Part #)
*
Email
SMS
SNMP
v1, v2c, v3
BACnet IP
BACnet MSTP
Modbus TCP
Modbus RTU
YDN23 *
YDN23 supported only for Liebert PeX and Liebert NXL.
1
Dimensions
1/2" (11mm)
Top of Liebert IntelliSlot Unity Card
3" (76mm)
1- 1/2"
(38mm)
2-3/8"
(60.3mm)
Front of Liebert IntelliSlot Unity Card
4-3/4"
(121mm)
Specifications
DC Inputs
Power
Requirements
Power Consumption
Dimensions - W x D x H: in. (mm)
Shipping, lb. (kg)
Ambient Operating Environment, °F (°C)
• 7 (0.2)
• 1.3 (0.6)
• 32 to 104 (0 to 40); 10% to 90% RH (non-condensing)
Ambient Storage Temperature, °F (°C)
Communication
Ports
• 3.6W maximum
• 2.97 x 5.2 x 1.45 (75.5 x 15 x 37)
Net, oz. (kg)
Weight
• 7 to 12VDC
• -4 to 140 (-20 to 60)
Ethernet Communications
RS-485
• RJ-45
• RJ-45 (RJ-45 to 2-Position Terminal Block Adapter)
Wiring Specifications
Maximum Wire Length
Connection
Supported Wire Type
10/100Mb/s Ethernet Connector
Standard Category 5E Cable
328 ft. (100m)
RJ-45 - One-Wire Connector
Liebert® Integrated One-Wire Sensor Cable or 2m Cat 5E to
Modular 1-Wire Sensor.
65.6 ft. (20m)
RJ-45 - RS-485 Connector
ADAPTER RJ45-2POS TERMINAL BLOCK EIA485 to 18-22
AWG Stranded & Shielded 18 AWG recommended Non
Plenum - Belden 9461 Plenum - Belden 88761
3000 ft. (914m)
Micro-USB AB
Standard Micro-USB AB
16.4 ft. (5m)
Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Telephone: 1-800-877-9222
Facsimile: 1-614-841-6022
www.liebert.com
© 2012 Liebert Corporation
All rights reserved throughout the world. Specifications
subject to change without notice.
® Liebert is a registered trademark of Liebert Corporation. All
names referred to are trademarks or registered trademarks
of their respective owners.
SL-52646_REV4_06-14
2
LIEBERT MC
PREMIUM EFFICIENCY CONTROL
STANDARD FEATURES
COIL
Liebert microchannel coils are all‐aluminum construction. Tubes are created by extruding small parallel refrigerant flow paths into
aluminum. Full‐depth louvered aluminum fins fill spaces between the tubes. Tubes, fins and aluminum headers are oven‐brazed to
form a complete refrigerant‐to‐air heat exchange coil. Baffles are used in the headers to separate one coil slab into multiple passes
as needed. Coils are factory leak tested at a minimum of 300 PSIG and dehydrated. Copper stub pipes are electric resistance welded
to aluminum coils and joints are protected with polyolefin to seal joint from environmental corrosive elements. Hot gas and liquid
lines are brazed to the stub pipes with spun closed ends for customer piping connections. Coil pipe assembles are filled and sealed
with a nitrogen holding charge for shipment. One coil is used per fan assembly.
FAN/MOTOR ASSEMBLY The fan/motor assembly is complete with external rotor motor, fan blades and fan/finger guard. Fan blades are
constructed of stamped aluminum or steel extrusion coated with PP plastic. Fan guards are heavy gauge, close meshed, steel wire,
coated with a black corrosion resistant finish. Fan terminal blocks located on the top of the fan guard with IP54 protection class.
Fans are factory balanced and tested before shipment.
Fan Motors Fan motors are specifically designed for variable speed and have ball bearings. The EC fans provide internal overload
protection through the built‐in electronics. Each EC fan motor has built‐in controller and communication module, linked via RS485
communication wire to each fan and the Premium Control Board. This allows each fan to receive and respond to precise fan speed
inputs from the Premium control board..
PREMIUM EFFICIENCY FAN CONTROL The Liebert premium efficiency condenser control system is complete with control board, EC fan
motor(s),refrigerant‐pressure transducer(s), refrigerant‐temperature thermistor(s), ambient‐temperature thermistor, and motor
overload protection in the factory wired control panel. The control board maintains EC fans on the same circuit to the same speed
in order to maintain refrigerant head pressure. The control board receives a run signal from the compressor of the indoor unit via
field‐supplied low voltage interlock wires or with optional, field‐supplied CANBUS communication wires from the indoor unit iCOM.
The system head pressure can be maintained to a minimum ambient temperature of 0 °F (‐18 °C).
HOUSING The condenser housing is constructed of bright aluminum sheet and divided into individual fan sections by full width baffles. Internal
structural support members, including coil support frame, are galvanized steel for strength and corrosion resistance. Panel doors
are provided on two sides of each coil/fan section to provide for coil cleaning. Aluminum legs are provided with rigging holes for
hoisting the unit into position.
UNIT DISCONNECT SWITCH Locking unit disconnect switch is factory installed and wired in attached condenser control section.
OPTIONAL FEATURES
LIEBERT LEE‐TEMP LOW AMBIENT CONTROL Lee‐Temp receiver kits can be added to achieve head pressure control down to minimum ambient
temperatures of ‐30 °F (‐34 °C). The premium efficiency fan control when used with the Liebert Lee‐Temp receiver kits runs the
fan(s) at lower speeds during cold temperatures saving fan energy.
COMMUNICATION The Premium Efficiency Control system provides future communication links with the iCOM control of the indoor Liebert
precision air conditioner. The communication link allows for condenser alarm condition communication to iCOM, communication of
other measurable items on the condenser, and future condenser/fan control features to improve efficiency, sound and wintertime
operation based on iCOM programming.
DPN002155
REV 06/11
REV 0
LIEBERT MC
CABINET & ANCHOR DIMENSIONAL DATA
MCS028 & MCS056 WITH LEE-TEMP RECEIVER
42 3/4"
(1085m m )
Emerson recommends a clearance of
36” (915mm) on each side for proper
operation and component access.
E*
HEIGHT TO TOP
OF FAN GUARD
C
E
B
A
575V TRANSFORMER
ENCLOSURE OPTION
15 1/4"
(387m m )
D
42 1/2"
(1080m m )
FOR DUAL
CIRCUIT ONLY
15 1/4"
(387m m )
ANCHOR PLAN
LEG HEIGHT
42 1/2"
(1079mm)
B
C
IN. (MM.)
IN. (MM.)
IN. (MM.)
18 (457)
31 5/8 (803)
39 5/8 (1006)
36 (914)
49 5/8 (1260)
57 5/8 (1464)
48 (1219)
61 5/8 (1565)
69 5/8 (1768)
60 (1524)
73 5/8 (1870)
81 5/8 (2073)
A*
PROVIDED ON 2-FAN MODEL
Electric Box End
F
35 7/8" 40 7/8"
(910mm) (1038mm)
Typical condenser footprint dimensions
*Cross bracing required for legs longer than 18”. Quantity varies per
13/16"
(21mm)
2 1/2"
(64mm)
model and options selected.
3 5/8"
(93mm)
1 7/8"
(48mm)
2 1/2"
(64mm)
D
E
E*(575V)
F
FANS
IN. (MM.)
IN. (MM.)
IN. (MM.)
IN. (MM.)
MCS028
1
44 1/8 (1120)
50 5/8 (1287)
58 7/8 (1495)
--
MCS056
2
88 3/8 (2245)
94 7/8 (2411)
103 1/8 (2619)
44 1/4 (1124)
LIEBERT
MODEL
NO.
1/2"(12.7mm) x 1"(2 5.4mm)
OBROUND
3 5/8"
(93mm)
NO.
1 7/8"
(48mm)
DPN002373
REV 5/14
REV 5
LIEBERT MC
PIPING: DIMENSIONAL DATA WITH LEE-TEMP
SINGLE CIRCUIT CONDENSERS
METAL CLAMP
ISOLATOR
DETAIL A-A
HOT GAS LINE
TO CONDENSER
ENTERING HOT
GAS LINE
FIELD PIPING
COVER *
B VIEW
B VIEW
POSITION ELBOW TO
DIRECT RELIEF VALVE
DOWNWARD
LIQUID LINE
FROM CONDENSER
GENERAL ARRANGEMENT
LEAVING
LIQUID LINE
FASTEN HOT GAS LINE TO CABINET
USING FLAT SURFACE CLAMPS WITH
ISOLATORS(FIELD SUPPLIED)
SEE DETAIL A-A
LIEBERT SUPPLIED PIPING ASSEMBLY
WILL INCLUDE 1 TO 3 VALVE AND CHECK
VALVES DEPENDENT ON CONDENSER CAPACITY
AND REFRIGERANT.
NOTE:
1.THE FOLLOWING MATERIALS ARE SUPPLIED BY LIEBERT,SHIPPED LOOSE FOR EACH CIRCUIT AND FOR FIELD INSTALLATION:
INSULATED LEE-TEMP RECEIVER TANK WITH ELECTRIC HEATER PADS AND SIGHT GLASSES, PIPING ASSEMBLY WITH HEAD PRESSURE
CONTROL VALVE AND CHECK VALVE, ROTO-LOCK VALVE AND PRESSURE RELIEF VALVE. ALL OTHER PIPING AND ELECTRICAL WIRING
TO BE SUPPLIED AND INSTALLED BY OTHERS. ADDITIONAL CONDENSER LEG PER CIRCUIT WHEN REQUIRED, SHIPS WITH THE CONDENSER.
2.FOR RUNS LONGER, THAN 150FT.(45.7M)EQUIV. LENGTH, CONSULT FACTORY FOR PROPER LINE SIZING.
CONDENSER PIPING CONNECTION SIZES
LEE-TEMP CONNECTIONS
CONDENSER CONNECTIONS(ODS-INCHES)
MODEL NO.
CONDENSER
CIRCUITS
HOT GAS
LIQUID
MCS028
1
7/8
5/8
HOT GAS TEE
LIQ TO L-T VALVE
(IDS-INCHES)
(ODS-INCHES)
7/8
5/8
RECEIVER OUT
ROTO LOCK
(IDS-INCHES)
5/8
MCM040
1
7/8
5/8
7/8
5/8
5/8
MCM080
1
1-1/8
7/8
1-1/8
7/8
1-1/8
MCL055
1
1-1/8
7/8
1-1/8
7/8
7/8
MCL110
1
1-3/8
1-1/8
1-3/8
1-1/8
1-1/8
MCL165
1
1-3/8
1-1/8
1-3/8
1-1/8
1-1/8
MCL220
1
1-5/8
1-3/8
1-5/8
1-3/8
1-3/8
* SHIPPING COVER IS NOT NECESSARY FOR PROPER CONDENSER OPERATION AND
MAY BE RECYCLED IF FIELD PIPING INTERFERES WITH PROPER REATTACHMENT.
DPN002167
REV 08/14
REV 5
LIEBERT MC
PIPING SCHEMATIC
CONDENSER WITH AND WITHOUT LIEBERT LEE-TEMP
Check Valve
Service
Valve
Relief Valve
LIQUID RETURN
Head Pressure
Control Valve
LEE-TEMP RECEIVER
Check Valve
CONDENSER
COIL
CONDENSER
COIL
OPTIONAL FIELD INSTALLED
FUSIBLE PLUG
HOT GAS DISCHARGE
LEE-TEMP
LIQUID
Sensing
Bulb
For rises over 25ft. (7.6m),
trap every 20ft. (6m) or
evenly divided*
EVAPORATOR
COIL
SUCTION
Service
Valve
Service
Check
Valve
Valve COMPRESSOR
Field installed relief valve(s) required
for 50Hz EU CE units.
External
Equalizer
*Isolation
Valve
HOT GAS DISCHARGE
Expansion
Valve Solenoid
Valve
Sight
Glass
Filter Drier
LIQUID LINE
*Isolation
Valve
Trap at base of risers
over 5ft. (1.5m)*
NOTE: SINGLE REFRIGERATION CIRCUIT SHOWN FOR CLARITY.
REFRIGERANT PIPING
*Components are not supplied by
Liebert but are required for
proper circuit operation and
maintenance
FIELD PIPING
SERVICE/SCHRADER (ACCESS) CONNECTION NO VALVE CORE
SERVICE/SCHRADER (ACCESS) CONNECTION WITH VALVE CORE
NOTE: SCHEMATIC REPRESENTATION SHOWN. DO NOT USE FOR SPECIFIC CONNECTION LOCATIONS.
DPN002188
REV 6/14
REV 3
LIEBERT MC
ELECTRICAL FIELD CONNECTIONS
PREMIUM EFFICIENCY CONTROL WITH LEE-TEMP
Electrical Connections for Lee-Temp Receiver
Lee-Temp receiver tank (1 per circuit).
NOTE: Heater pad voltage available for
120V/1 phase/60 Hz or 230V/1 phase/60Hz
150 or 300 Watt, varies by condenser.
FAN2
FAN1
Electrical connection box with cover.
(Cover removed for clarity.)
Electrical service connection. Pigtails in electric handy box
are factory wired to Lee-Temp heater pads for field connection
of separate continuous electric source, wire not by Liebert.
KEY ELECTRICAL DETAILS:
1) Three phase electrical service – Terminals are on top of disconnect switch for one and two fan units. Terminals are on
bottom of disconnect switch for three and four fan units. Three phase service not by Liebert. See Note 5 (below).
2) Earth ground – Field lug terminal for earth ground connection. Ground terminal strip for fan motor ground connection.
3) Primary high voltage entrance – Two 7/8” (22.2mm) diameter knockouts located at the bottom of the enclosure.
4) SPD field connection terminals – High voltage surge protective device (SPD) terminals. SPD is an optional device.
DPN002374
Page 1 of 3
REV 4
REV 05/14
LIEBERT MC
ELECTRICAL FIELD CONNECTIONS
PREMIUM EFFICIENCY CONTROL WITH LEE-TEMP
5) CANbus terminal connections – Field terminals for CANbus cable connection.
 5A is the CANbus connectors.
o TB49-1 is the input terminal for CANbus high.
o TB49-3 is the input terminal for CANbus low.
o TB50-1 is output terminal for CANbus high.
o TB50-3 is the output terminal for CANbus low.
o Each CANbus cable shield is connected to terminal “SH”, item 9.
 5B is the “END OF LINE” jumper.
 5C is the CANbus “DEVICE ADDRESS DIP SWITCH”. CANbus cable not by Liebert. See Note 2 (below).
6) Remote unit shutdown – Replace exiting jumper between terminals TB38-1 and TB38-2 with field supplied normally closed
switch having a minimum 75VA 24VAC rating. Use field supplied Class 1 wiring. (This is an optional feature that may be owner
specified.)
7) Alarm terminal connections –
a. Common Alarm Relay indicates when any type of alarm occurs. TB74-1 is common, TB74-2 is normally open, and
TB74-3 is normally closed. 1 Amp 24VAC is the maximum load. Use Class 1 field supplied wiring.
b. Shutdown Alarm Relay indicates when condenser loses power, or when a critical alarm has occurred that shuts down
the condenser unit. TB74-4 is common, TB74-5 is normally open, and TB74-6 is normally closed. 1 Amp 24VAC is the
maximum load. Use Class 1 field supplied wiring.
8) Indoor unit interlock and SPD alarm terminals –
a. On any call for compressor operation, normally open contact is closed across terminals 70 & 71 for Circuit 1, and
normally open contact is closed across terminals 70 & 230 for Circuit 2 from indoor room unit.
b. During SPD alarm, normally open contact is closed across terminals 12 & 13. SPD is an optional device.
9) CANbus shield terminal – Terminal for field connection of the CANbus field supplied cables. Shield of CANbus field supplied
cables must not be connected to ground.
10) Primary low voltage entrance – One 7/8” (22.2mm) diameter knockout that is free for customer low voltage wiring.
11) SPD entrance – One 7/8” (22.2mm) diameter knockout hole located at the bottom of the enclosure. High voltage surge
protective device (SPD) is optional.
NOTES:
1. Refer to specification sheet for unit voltage rating, full load amp, and wire size amp ratings.
2. The CANbus wiring is field supplied and must be:
a)
shielded
b) 22-18AWG stranded tinned copper,
c) twisted pair (minimum 8 twists per foot),
d) low capacitance (15pf/ft or less),
e) plenum rated(NEC type CMP) if required by local codes,
f) UV and moisture resistant or run within conduit once in an outdoor environment, and
g) must be temperature and voltage rated for conditions present.
h) Examples: Belden part number 89207(plenum rated) or Alpha Wire part number 6454 (UV resistant outdoor rated)
category 5, 5e or higher.
3. Do not run the CANbus cable in the same conduit, raceway, or chase as high voltage.
4. For CANbus network lengths greater than 350ft(107m), contact Liebert factory.
5. All wiring must be sized and selected for insulation case per NEC and other local codes.
DPN002374
Page 2 of 3
REV 4
REV 05/14
LIEBERT MC
ELECTRICAL FIELD CONNECTIONS
PREMIUM EFFICIENCY CONTROL WITH LEE-TEMP
6. The electrically commutated (EC) motors included in the Liebert MC Condenser are suitable for connection to power supplies
with a solidly grounded neutral. (Some platforms can accept power supplies listed under item b below. Contact the factory for
more information.)
a) Acceptable power supplies for 208 to 575V nominal unitsi.
208V wye with solidly grounded neutral and 120V line to ground;
ii.
380V wye with solidly grounded neutral and 220V line to ground;
iii.
480V wye with solidly grounded neutral and 277V line to ground.
iv.
575V wye with solidly grounded neutral and 332V line to ground. (uses step-down transformer)
b) Non-acceptable power supplies for 208V to 575V nominal units –
i.
wye with high resistance (or impedance) ground;
ii.
delta without ground or with floating ground;
iii.
delta with corner ground; or
iv.
delta with grounded center tap.